HomeMy WebLinkAbout918 S Elliot Pl - Plan918 S Elliot Pl 06/02/23 918 S Elliot Pl 06/02/23 918 S Elliot Pl 06/02/23 918 S Elliot Pl 06/02/23 918 S Elliot Pl 06/02/23 918 S Elliot Pl 06/02/23 STRUCTURAL ANALYSIS FOR NEW PHOTOVOLTAIC SOLAR SYSTEM NOTE: THESE CALCULATIONS ARE BASED ON INFORMATION AND MEASUREMENTS PROVIDED BY THE CONTRACTOR FROM HIS SITE INSPECTION. 1 Project Information:PV SOLAR ARRAY: GELVAN RESIDENCE Latitude 33.7352° deg N 918 S. ELLIOT PLACE, SANTA ANA, CA 92704 Longitude -117.925° deg W Wind Speed 110 mph 95 mph (ASCE 7-22) Wind Exposure C Site Class D Seismic Design Category D 2 Loads: Existing Roof Dead Loads: 2 x 4 Trusses @ 24" OC 2.6 psf 1/2" Roof Sheathing 1.7 psf Roof Felt 1.5 psf Composition 5.0 psf Miscellaneous 3.2 psf Total 14.0 psf Existing Snow Load:0.0 psf Existing Roof Live Load:20.0 psf Proposed Roof Live Load:20.0 psf Wind Load: Using CBC 2022 (ASCE 7-22), Chapter 29: Wind Loads on Rooftop Equipment, the following wind pressures were calculated. p = qh (GCp) (ge) (ga) = 8.66 -44.55 psf qh = 0.00256 Kz Kzt Kd Ke V2 = 21.76 psf Kz = 0.85 (0-15 = 0.85, 20 = 0.90, 25 = 0.94, 30 = 0.98, 40 = 1.04) GCp = 0.7 -3.6 (Roof pitch = 14 deg, Zone = 2, Aeff = 21.1 sf) ge = 1.50 ga = 0.80 Lag Bolt Capacity: 5/16" lag bolt capacity = 270 lbs per inch embedment With 2 1/2" minimum embedment, capacity = 675 lbs Required Capacity: 44.55 psf * 20 modules * 21.1 sf = 18800.6 lbs 18800.6 lbs / 32 lag bolt connections = 587.5 lbs The pull-out capacity of the 5/16" lag bolts with a minimum 2 1/2" embedment into the roof rafter is sufficient to meet the demand of the wind uplift force on the solar system. Seismic Load: Per the CEBC 2022 Section 503.4, if the demand-capacity ratio of the lateral load-carrying elements increases less than 10% due to the addition of the solar system, no special provisions or structural modifications are required. Existing Roof Weight = 14.0 psf * 2820 sf = 39480 lbs Weight of Solar System = 20 modules * 50.0 lbs + 211 lbs of racking = 1211 lbs 1211 lbs / 39480 lbs = 0.03 The increase in load from the solar system will not increase the demand-capacity ratio of the existing lateral load-carrying elements by over 10%. NOTICE:VISION CIVIL ENGINEERING: JENNIFER KEMME, PE ANY CHANGES TO OR USES OF THESE DOCUMENTS 12273 11TH STREET, YUCAIPA, CA 92399 WITHOUT THE WRITTEN CONSENT OF VISION 909.754.8300, JENKEMME@VISIONCE.COM CIVIL ENGINEERING IS STRICTLY PROHIBITED.RCE 73054, EXP 12/31/24 Prepared by JENNIFER KEMME 5/11/2023 Page 1 918 S Elliot Pl 06/02/23 STRUCTURAL ANALYSIS FOR NEW PHOTOVOLTAIC SOLAR SYSTEM NOTE: THESE CALCULATIONS ARE BASED ON INFORMATION AND MEASUREMENTS PROVIDED BY THE CONTRACTOR FROM HIS SITE INSPECTION. 3 Analysis of Existing Rafter Capacity:PV SOLAR ARRAY: GELVAN RESIDENCE 918 S. ELLIOT PLACE, SANTA ANA, CA 92704 Rafter Loads: Solar system dead load = 1211 lbs / 32 lag bolts total = 37.8 lbs at each lag bolt Existing roof dead load = 14 psf Snow load = 0 psf Roof live load = 20 psf Wind load = 114.2 lbs, 587.5 lbs Rafter span = 7.0 ft Load Combinations That Apply: #1: D + Lr or S = 14 psf + 37.8 lbs at each lag bolt + 20.0 psf #2: D + 0.75(0.6W) + 0.75(Lr or S) = 14 psf + 37.8 lbs at each lag bolt) + (0.75 (0.6) 114.2 lbs at each lag bolt) + (0.75 ( 20 psf)) #3: 0.6D + 0.6W = 0.6 ( 14 psf + 37.8 lbs at each lag bolt) - (0.6) 587.5 lbs at each lag bolt Calculated Maximum Bending Moment: #1: 208.3 ft/lbs + 66.2 ft/lbs = 274.5 ft/lbs [( 34 psf) ( 7 ft^2)] / 8 = 208.3 ft/lbs [( 37.84 lbs) ( 7.0 ft)] / 4 = 66.2 ft/lbs #2: 85.8 ft/lbs + 66.2 ft/lbs + 90.0 ft/lbs + 91.9 ft/lbs = 333.8 ft/lbs [( 14 psf) ( 7 ft^2)] / 8 = 85.8 ft/lbs [( 37.84 lbs) ( 7.0 ft)] / 4 = 66.2 ft/lbs 114.2 lbs) ( 7 ft)] / 4 = 90.0 ft/lbs 0.75 [( 20 psf) ( 7 ft^2)] / 8 = 91.9 ft/lbs #3: 51.5 ft/lbs + 39.7 ft/lbs - 616.9 ft/lbs = -525.7 ft/lbs 0.6 [( 14 psf) ( 7 ft^2)] / 8 = 51.5 ft/lbs 0.6 [( 37.84 lbs) ( 7.0 ft)] / 4 = 39.7 ft/lbs 0.6 [( 587.5 lbs) ( 7 ft)] / 4 = 616.9 ft/lbs Section Required: 525.7 ft/lbs (12) (0.7) / 1518 psi = 2.9 cu in Section Provided: 1.5 ( 3.5 ^2) / 6 = 3.1 cu in 3.1 cu in > 2.9 cu in, OK Calculated Deflection: [5( 34 psf / 12) ( 84 in^4)] / [384 (1200000) ( 5.4 )] = 0.29 in Allowable Deflection: 84 in / 240 = 0.35 in 0.35 in > 0.29 in, OK NOTICE: VISION CIVIL ENGINEERING: JENNIFER KEMME, PE ANY CHANGES TO OR USES OF THESE DOCUMENTS 12273 11TH STREET, YUCAIPA, CA 92399 WITHOUT THE WRITTEN CONSENT OF VISION 909.754.8300, JENKEMME@VISIONCE.COM CIVIL ENGINEERING IS STRICTLY PROHIBITED. RCE 73054, EXP 12/31/24 0.75 [(0.6)( Prepared by JENNIFER KEMME 5/11/2023 Page 2 918 S Elliot Pl 06/02/23 SCOPE OF WORK: INSTALL (20) Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 SOLAR ELECTRIC MODULES AND (20) SOLAREDGE S440 DC POWER OPTIMIZERS ON THE EXISTING 1ST STORY COMPOSITION ROOF. INSTALL ASSOCIATED MOUNTING HARDWARE, JUNCTION BOXES, CONDUIT, CONDUCTORS AND GROUNDING. INSTALL (1) SOLAREDGE SE7600H-US INVERTER WITH INTEGRATED DC DISCONNECT, (1) AC DISCONNECT, AND INSTALL OCPD IN MAIN SERVICE PANEL. HOMEOWNER: TAYLOR GELVAN & NATALIE CONGHUYEN PH: 949.701.9256 ADDRESS: 918 S. ELLIOT PLACE SANTA ANA, CA 92704 DATE: 5/9/23DATE: 5/9/23 SUN SOLAR US, INC. 16755 VON KARMAN AVENUE #200 IRVINE, CA 92606 PH: 949.242.0088 RONALD RHODES B, C10 - 975072 VICINITY MAP GELVAN & CONGHUYEN RESIDENCE SHEET INDEX: SHEET 1 PROJECT INFO, VICINITY MAP, NOTES, SCOPE OF WORK SHEET 2 SITE/ROOF PLAN, ELEVATION DETAIL SHEET 3 ELECTRIC LINE DRAWING, GROUNDING DETAIL SHEET 4 CALCULATIONS, SIGNS ATTACHED MODULE, INVERTER, MOUNTING HARDWARE SPEC SHEETS STRUCTURAL REPORT NTS SHEET NOTICE: ANY CHANGES TO OR USES OF THESE DOCUMENTS/DRAWINGS WITHOUT THE WRITTEN CONSENT OF JENNIFER KEMME OR SCOTT HARRIS ARE STRICTLY PROHIBITED. 1 OF 4 PLANS PREPARED BY: JENNIFER KEMME PH: 909.748.1300 (20) Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 PEAK POWER = 400 W MAX OPERATING CURRENT = 10.77 A MAX OPERATING VOLTAGE = 37.13 V OPEN CIRCUIT VOLTAGE = 45.30 V SHORT CIRCUIT CURRENT = 11.14 A MAX SERIES FUSE RATING = 20 A TEMP. COEFF. OF Voc = -0.27%/K DIMENSIONS = 74.0" X 41.1" X 1.3" WEIGHT = 48.5 LBS GENERAL NOTES: 1. THIS SYSTEM COMPLIES WITH THE 2022 CRC, 2022 CBC, 2022 CFC, AND THE 2022 CEC. 2. THE SYSTEM WILL NOT BE TURNED-ON UNTIL THE SERVING UTILITY COMPANY HAS BEEN NOTIFIED. 3. THE INSTALLED SOLAR SYSTEM HAS A DISTRIBUTED WEIGHT LESS THAN 4 PSF. 4. THE CONCENTRATED LOAD FOR EACH VERTICAL SUPPORT IS LESS THAN 40 LBS. 5. ALL PV EQUIPMENT IS LISTED BY A RECOGNIZED TESTING LAB. INVERTERS ARE UL 1741 COMPLIANT. 6. THE BACKFED BREAKER WILL BE LOCATED AT THE OPPOSITE END OF THE BUS FROM THE MAIN BREAKER. 7. CONDUCTORS ARE 90° C RATED COPPER WIRE. 8. ANY CONDUCTORS EXPOSED TO SUNLIGHT ARE LISTED AS SUNLIGHT RESISTANT. 9. IF DC CONDUCTORS ARE RUN INSIDE THE BUILDING, THEY WILL BE CONTAINED IN A METAL RACEWAY. 10. ANY CONDUCTORS BETWEEN SEPARATE ARRAYS ON THE ROOF WILL BE PROTECTED IN CONDUIT. 11. THE EQUIPMENT GROUNDING CONDUCTOR ON THE ROOF WILL BE PROTECTED FROM PHYSICAL DAMAGE. IT WILL BE TUCKED NEATLY UNDER THE MODULES AND RAILS AND SECURED IN PLACE. 12. THE MODULES WILL BE ATTACHED TO THE EQUIPMENT GROUNDING CONDUCTOR IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. 13. ALL EXTERIOR CONDUIT, FITTINGS AND BOXES ARE RAIN-TIGHT AND APPROVED FOR USE IN WET LOCATIONS. 14. CLEARANCES AROUND ALL ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH CEC 110.26. 15. SOLAR MODULES WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL OR BUILDING ROOF VENTS. 16. IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A VERIFIABLE GROUNDING ELECTRODE SYSTEM, A GROUNDING ELECTRODE SYSTEM WILL BE INSTALLED PER CEC 250.50.THE ELECTRICAL SERVICE WILL BE BONDED TO THE WATER AND GAS PIPING PER SECTION 250.104 OF THE CEC. 17. A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH CAL-OSHA REGULATIONS. CITY OF SANTA ANA NOTE (2013 CBC SECTION 420, H&S CODE SECTION 13114): THE PROVISION OR VERIFYING FUNCTION OF REQUIRED SMOKE ALARMS AND CARBON MONOXIDE ALARMS IS REQUIRED BY STATE LAW AS A PART OF THIS PROJECT. BE PREPARED TO DEMONSTRATE FUNCTIONALITY AND LOCATIONS OF THE DEVICES TO YOUR SANTA ANA FIELD INSPECTOR. WHEN BATTERY POWERED, 10 YEAR BATTERIES ARE NOW REQUIRED. 74430PV INVERTER/DC DISCONNECT: (1) SOLAREDGE SE7600H-US MAX DC INPUT VOLTAGE = 480 V NOMINAL DC INPUT VOLTAGE = 400 V MAX DC INPUT CURRENT = 20.0 A DC DISCONNECT MAX INPUT CURRENT = 45.0 A NUMBER OF DC INPUTS = 2 RATED AC POWER = 7600 W AC VOLTAGE = 240 V MAX AC OUTPUT CURRENT = 32.0 A NEMA 4X ENCLOSURE DIMENSIONS = 17.7" X 14.6" X 6.8" WEIGHT = 26 LBS PHOTOVOLTAIC SOLAR PROJECT INFORMATION: SYSTEM SIZE: 8.000 kW (DC), 7.600 kW (AC) MODULES: MODULE ADD-ON:(20) SOLAREDGE S440 DC POWER OPTIMIZERS MAX DC INPUT VOLTAGE = 60 V OPERATING VOLTAGE RANGE = 8 V - 60 V MAX DC INPUT CURRENT = 14.5 A MAX DC OUTPUT CURRENT = 15 A DC OUTPUT VOLTAGE = 380 V MAX POWER PER STRING (CONTROLLED BY INVERTER) = 5700 W NEMA 6P ENCLOSURE DIMENSIONS = 5.1" X 6.1" X 1.2" WEIGHT = 1.6 LB ARRAY: INSTALLED WEIGHT = 2.9 PSF ROOF COVERAGE = 425 SF, ARRAYS COVER 15% OF TOTAL ROOF AREA MOUNTING HARDWARE: GRIPAC STANDARD RAIL GRIPAC FLASHED L-FOOT ATTACHMENTS 5 16" STAINLESS STEEL LAG BOLTS @ 72" OC OR LESS WITH A MINIMUM OF 21 2" PENETRATION INTO ROOF RAFTERS EXISTING ROOF INFO: 1 STORY, COMPOSITION SHINGLE 2 X 4 TRUSSES @ 24" OC The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. Bldg# 101115262 Elec# 20179759 Issued 06/01/23 918 S Elliot Pl 06/02/23 TM L-Foot •Weight: 0.25lb •Material: 6063 T6 Aluminum •Hardware Material: 300 Series Aluminum •Pre-Assembled Features: Part #Finish GR-LFT-CS-MILL GR-LFT-CS-CLR GR-LFT-CS-BLK Mill Finish Clear Anodized Black Anodized 3.75 2.00 0.31 0.44 1.38 0.31 1.36 D C B AA B C D 23 4 5 6 78 8 7 6 5 4 3 2 C. Schwartzman DRAWN BY DATE NR Orion Solar Racking 2917 Vail Ave. Commerce, CA 90040 TEL: (310) 409-4616 Copyright © 2011 Orion Racking. orionsolarracking.com MATERIAL DESCRIPTION SIZE A PART NO.REV NTS SHEET 1 OF 1 DO NOT SCALE DRAWING 03/04/15 © , . . TM L-Foot D C B AA B C D 23 4 5 6 7 8 8 7 6 5 4 3 2 C. Schwartzman DRAWN BY DATE NR Orion Solar Racking 2917 Vail Ave. Commerce, CA 90040 TEL: (310) 409-4616 Copyright © 2011 Orion Racking. orionsolarracking.com MATERIAL DESCRIPTION SIZE A PART NO. REV NTS SHEET 1 OF 1 DO NOT SCALE DRAWING 03/04/15 Installation Overview • Locate rafters and chalk horizontal and vertical lines to mark location of penetrations. Drill 1/4” holes and backfll with sealant. •Slide !ashing between composition shingle and line up dimple hole with pilot hole. •Place rubber grommet on top of dimple, then the L-Foot, ensuring a secure fasten. •Take 5/16”-18x3.5 Lag Bolt and tighten into rafter. Completed Install Metal Flashing T-Bolt Assembly 5/16”-18x3.5 Lag Bolt Metal Bonded Sealing Washer L-Foot Rubber Grommet 11.90 3.78 D C B 7 6 5 4 3 2 © , .. 918 S Elliot Pl 06/02/23 SCOPE OF WORK: INSTALL (20) Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 SOLAR ELECTRIC MODULES AND (20) SOLAREDGE S440 DC POWER OPTIMIZERS ON THE EXISTING 1ST STORY COMPOSITION ROOF. INSTALL ASSOCIATED MOUNTING HARDWARE, JUNCTION BOXES, CONDUIT, CONDUCTORS AND GROUNDING. INSTALL (1) SOLAREDGE SE7600H-US INVERTER WITH INTEGRATED DC DISCONNECT, (1) AC DISCONNECT, AND INSTALL OCPD IN MAIN SERVICE PANEL. HOMEOWNER: TAYLOR GELVAN & NATALIE CONGHUYEN PH: 949.701.9256 ADDRESS: 918 S. ELLIOT PLACE SANTA ANA, CA 92704 DATE: 5/9/23DATE: 5/9/23 SUN SOLAR US, INC. 16755 VON KARMAN AVENUE #200 IRVINE, CA 92606 PH: 949.242.0088 RONALD RHODES B, C10 - 975072 NOTE: DIMENSIONS AND FEATURES SHOWN ARE CLOSE TO SCALE BUT WERE TAKEN FROM A FIELD SURVEY AND APPROXIMATIONS MADE USING GOOGLE EARTH. PROPERTY LINE (E) 200 AMP MAIN SERVICE PANEL W KENT AVENUE N SCALE: 1/16"=1' 8 16 32 48 VENT (TYP) (N) AC DISCONNECT (N) INVERTER/ DC DISCONNECT SITE/ROOF PLAN ARRAY #1: (20) MODULES TILT = 14°, AZ = 265° 1 SHEET NOTICE: ANY CHANGES TO OR USES OF THESE DOCUMENTS/DRAWINGS WITHOUT THE WRITTEN CONSENT OF JENNIFER KEMME OR SCOTT HARRIS ARE STRICTLY PROHIBITED. 2 OF 4 PLANS PREPARED BY: JENNIFER KEMME PH: 909.748.1300 NTS ELEVATION DETAIL EXISTING 1-STORY ROOF: COMPOSITION SHINGLE, FELT & 1 2" SHEATHING OVER RAFTERS EXISTING 2 X 4 TRUSSES @ 24" OC MODULES: 74.0" X 41.1" 48.5 LBS EACH 3" MIN. 8" MAX. GRIPAC STANDARD RAIL MOUNTING SYSTEM WITH GRIPRAC FLASHED L-FOOT ROOF ATTACHMENTS (USE 5 16" STAINLESS STEEL LAG BOLTS @ 72" OC OR LESS WITH A MINIMUM EMBEDMENT OF 21 2" INTO ROOF RAFTERS), WATERPROOF ALL CONNECTION LOCATIONS PER MANUFACTURER'S INSTRUCTIONS 1.5' FIRE CLEARANCE 74430PV ROOF ACCESS POINTS ARE AT THE STRUCTURALLY STRONG PART OF THE BUILDING AND DO NOT REQUIRE LADDERING OVER OPENINGS. * TOTAL ROOF AREA = 2820 SF TOTAL SOLAR AREA = 425 SF 425 SF/2820 SF = 0.15 ARRAYS COVER 15% OF TOTAL ROOF AREA S. E L L I O T P L A C E * * 2 3 4 516 17 18 19 20 15 6 714 13 8 11 12 9 10 PROPERTY LINE SKYLIGHT CHIMNEY 3'-5" 4'-3" 5'-11" 19'-9" 27'-11" 2'-2" 3'-3" JENNIFER KEMME No: 73054 Exp: 12/31/24 CIVIL 918 S Elliot Pl 06/02/23 SCOPE OF WORK: INSTALL (20) Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 SOLAR ELECTRIC MODULES AND (20) SOLAREDGE S440 DC POWER OPTIMIZERS ON THE EXISTING 1ST STORY COMPOSITION ROOF. INSTALL ASSOCIATED MOUNTING HARDWARE, JUNCTION BOXES, CONDUIT, CONDUCTORS AND GROUNDING. INSTALL (1) SOLAREDGE SE7600H-US INVERTER WITH INTEGRATED DC DISCONNECT, (1) AC DISCONNECT, AND INSTALL OCPD IN MAIN SERVICE PANEL. HOMEOWNER: TAYLOR GELVAN & NATALIE CONGHUYEN PH: 949.701.9256 ADDRESS: 918 S. ELLIOT PLACE SANTA ANA, CA 92704 DATE: 5/9/23DATE: 5/9/23 SUN SOLAR US, INC. 16755 VON KARMAN AVENUE #200 IRVINE, CA 92606 PH: 949.242.0088 RONALD RHODES B, C10 - 975072 ELECTRICAL LINE DIAGRAM SHEET NOTICE: ANY CHANGES TO OR USES OF THESE DOCUMENTS/DRAWINGS WITHOUT THE WRITTEN CONSENT OF JENNIFER KEMME OR SCOTT HARRIS ARE STRICTLY PROHIBITED. 3 OF 4 PLANS PREPARED BY: JENNIFER KEMME PH: 909.748.1300 MAIN SERVICE INFO: 200 A, 120/240 VAC, 1Ø, 3-WIRE METER #222012-781105 40A 200A EXISTING BUILDING GROUNDING ELECTRODE SYSTEM M EXISTING SERVICE PANEL: 200 A BUS RATED, 240 VAC, 1Ø G L1 L2 60 A, 240 VAC, 1Ø AC DISCONNECT LOCKABLE, VISIBLE KNIFE-BLADE TYPE (3) 8 AWG THWN-2 & (1) 8 AWG GROUND IN 34" EMT CONDUIT (3) 8 AWG THWN-2 & (1) 8 AWG GROUND IN 34" EMT CONDUIT L1 L2 N G SOLAREDGE INTEGRATED DC DISCONNECT & RAPID SHUTDOWN DEVICE SOLAREDGE SE7600H-US 240 VAC, 1Ø TRANSFORMERLESS INVERTER - +Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 + - + - SOURCE CIRCUIT #1: 10 MODULES, 600 VDC + - + - (4) 10 AWG PV IN AIR (10) 600 VDC SOLAREDGE S440 OPTIMIZERS + - + - + - + - SOURCE CIRCUIT #2: 10 MODULES, 600 VDC + - + - + - + - (10) 600 VDC SOLAREDGE S440 OPTIMIZERS NEMA 3R, 600 VDC JUNCTION BOX (4) 10 AWG THWN-2 & (1) 8 AWG GROUND IN 34" EMT CONDUIT USE IRONRIDGE INTEGRATED GROUNDING TO GROUND ALL MODULES, OPTIMIZERS, JUNCTION BOXES AND ANY OTHER METAL PARTS AND #6 AWG SOLID COPPER WHERE NECESSARY Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 74430PV 918 S Elliot Pl 06/02/23 SCOPE OF WORK: INSTALL (20) Q.CELLS Q.PEAK DUO BLK ML-G10+ 400 SOLAR ELECTRIC MODULES AND (20) SOLAREDGE S440 DC POWER OPTIMIZERS ON THE EXISTING 1ST STORY COMPOSITION ROOF. INSTALL ASSOCIATED MOUNTING HARDWARE, JUNCTION BOXES, CONDUIT, CONDUCTORS AND GROUNDING. INSTALL (1) SOLAREDGE SE7600H-US INVERTER WITH INTEGRATED DC DISCONNECT, (1) AC DISCONNECT, AND INSTALL OCPD IN MAIN SERVICE PANEL. HOMEOWNER: TAYLOR GELVAN & NATALIE CONGHUYEN PH: 949.701.9256 ADDRESS: 918 S. ELLIOT PLACE SANTA ANA, CA 92704 DATE: 5/9/23DATE: 5/9/23 SUN SOLAR US, INC. 16755 VON KARMAN AVENUE #200 IRVINE, CA 92606 PH: 949.242.0088 RONALD RHODES B, C10 - 975072 SYSTEM SIGNAGESYSTEM SIGNAGE ALL SIGNAGE SHALL BE REFLECTIVE, UV RESISTANT PLASTIC, RED IN COLOR WITH WHITE LETTERING, AND ATTACHED WITH WEATHERPROOF ADHESIVE OR OTHER APPROVED METHOD. ALL LETTERS SHALL BE A MINIMUM OF 38" HEIGHT AND ALL CAPITALIZED. ALL CONDUIT, JUNCTION BOXES AND OTHER ENCLOSURES SHALL BE MARKED AT 10' MAX INTERVALS AND AT ALL BENDS, TERMINATIONS, SPLICES OR CONNECTIONS WITH "WARNING: PHOTOVOLTAIC POWER SOURCE". WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION TO BE INSTALLED AT ALL SERVICEABLE PANELS OR BOXES AND AT ALL DISCONNECTS: WARNING ELECTRIC SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED MAY BE ENERGIZED SERVICE POINT & UTILITY METERING PV SYSTEM DISCONNECT FOR UTILITY OPERATION SWITCH CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS AS SHOWN. ADDRESS: 918 S. ELLIOT PLACE, SANTA ANA, CA 92704 SOLAR ARRAY (ON ROOF)N INVERTER & DC DISCONNECT TO BE INSTALLED ON THE OUTSIDE COVER OF THE MAIN SERVICE DISCONNECT: PV SOLAR DC DISCONNECT MAXIMUM VOLTAGE = 480.00 V MAXIMUM CIRCUIT CURRENT = 30.00 A MAXIMUM RATED OUTPUT CURRENT OF THE DC-TO-DC CONVERTER = 15.00 A TO BE INSTALLED ON THE FRONT OF THE DC DISCONNECT: RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM RATED AC OUTPUT CURRENT = 32.00 A NOMINAL OPERATING AC VOLTAGE = 240 V TO BE INSTALLED ON THE FRONT OF THE AC DISCONNECT: WARNING POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVICE TO BE INSTALLED AT THE BACKFED BREAKER SERVING THE PV SOLAR SYSTEM: TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TO BE INSTALLED ON THE FRONT OF THE MAIN SERVICE DISCONNECT: "SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN" SHALL BE BLACK LETTERING ON YELLOW BACKGROUND. THE REMAINDER OF THE SIGN SHALL BE BLACK LETTERING ON WHITE BACKGROUND. SHEET NOTICE: ANY CHANGES TO OR USES OF THESE DOCUMENTS/DRAWINGS WITHOUT THE WRITTEN CONSENT OF JENNIFER KEMME OR SCOTT HARRIS ARE STRICTLY PROHIBITED. 4 OF 4 PLANS PREPARED BY: JENNIFER KEMME PH: 909.748.1300 SYSTEM CALCULATIONS: MODULE POWER = 400 W NUMBER OF MODULES IN LONGEST STRING = 10 (10) 400 W = 4000 W OPTIMIZER MAX POWER PER STRING = 6000 W 4000 W < 6000 W, OK OPERATING CURRENT = POWER RATING/OPERATING VOLTAGE = 4000 W/400 V = 10.00 A OPTIMIZER TO INVERTER TARGET VOLTAGE/OPERATING VOLTAGE = 400 V MAX SYSTEM VOLTAGE (Voc) CONTROLLED BY INVERTER = 480 V SHORT-CIRCUIT CURRENT (Isc) CONTROLLED BY OPTIMIZER = 15.00 A INVERTER MAX OUTPUT CURRENT = 32.00 A 32.00 A (1.25) = 40.00 A [Ic], USE 40 A BREAKER MAIN SERVICE PANEL BUS RATING = 200 A MAIN SERVICE PANEL MAIN OCPD = 200 A 200 A + 40 A SOLAR OCPD = 240 A 200 A BUS (1.2) = 240 A 240 A = 240 A, OK WIRE CALCULATIONS: FROM OPTIMIZERS TO INVERTER/DC DISCONNECT: AMBIENT TEMPERATURE = 34°C TEMPERATURE ADDER FOR CONDUIT NOT OFFSET FROM ROOF = 33°C ADJUSTMENT FACTOR PER TABLE 310.15(B)(2)(a) FOR 90°C INSULATED CONDUCTOR AT 34°C + 33°C = 67°C = 0.58 Isc = 15.00 A 15.00 A/0.58 = 25.86 A NUMBER OF CURRENT CARRYING CONDUCTORS IN CONDUIT = 4 ADJUSTMENT FACTOR PER TABLE 310.15(B)(3)(a) FOR CONDUIT FILL (4-6 CONDUCTORS IN CONDUIT) = 0.80 25.86 A/0.80 = 32.33 A SELECT WIRE SIZE WITH AMPACITY GREATER THAN 32.33 A, USE 10 AWG THWN-2 COPPER WIRE WITH AN AMPACITY OF 40 A SELECT CONDUIT FOR (4) 10 AWG THWN-2 & (1) 8 AWG GROUND = 34" EMT CONDUIT FROM THE INVERTER TO THE MAIN SERVICE PANEL: ADJUSTMENT FACTOR PER TABLE 310.15(B)(2)(a) FOR 90°C INSULATED CONDUCTOR AT 34°C = 0.96 Ic = 40.00 A 40.00 A/0.96 = 41.67 A SELECT WIRE SIZE WITH AMPACITY GREATER THAN 41.67 A, USE 8 AWG THWN-2 COPPER WIRE WITH AN AMPACITY OF 55 A SELECT CONDUIT FOR (3) 8 AWG THWN-2 & (1) 8 AWG GROUND = 34" EMT CONDUIT 74430PV 918 S Elliot Pl 06/02/23 918 S Elliot Pl 06/02/23 918 S Elliot Pl 06/02/23 VRODUHGHFRP 2SWLPLHLVWDOODWLRLW !"#DYHWHFROR$% Specicallydesigned toworkwithpoweroptimizers Built-inmodule-levelmonitoring Optional:Fasterinstallationswithbuilt-inconsumption metering(1%accuracy)andproductionrevenuegrade metering(0.5%accuracy,ANSIC12.20) Record-breaking99%weighted e ciency Quickand easyinvertercommissioningdirectly fromasmartphoneusingtheSolarEdgeSetApp Fixedvoltageinverterforlongerstrings UL1741SAcertied,forCPUCRule21gridcompliance Integratedarcfaultprotectionandrapid shutdownforNEC2014and2017,perarticle 690.11and690.12 Small,lightweight,and easytoinstallbothoutdoors orindoors 6L$OH3DVH&YHUWHU LW !"#DYH7HFROR$% IRU1RUW'PHULFD SE3000H-US/SE3800H-US/SE5000H-US/SE6000H-US/ SE7600H-US/SE10000H-US/SE11400H-US ()")* +,'5 #'55'17+ 02 !,-180.,5 6,/444 "866,/944 "86 6,*444 "86 6,:444 "86 6,;:44 "86 6,(4444 "86 6,((<44 "86 '33-&='.-,72&1>,57,56 #&7 3'57180.,5 6,???? "?????.??< 287387 5DWHG !" 3RZHU 2XWSXW #$$$#%$$ # '($9 ##$$ # '$%9 )$$$*$$$ # '($9 )$$$ # '$%9 +*$$,$$$$,,($$ # '($9 ,$$$$ # '$%9 9! 0D -.PXP !" 3RZHU 2XWSXW #$$$#%$$ # '($9 ##$$ # '$%9 )$$$*$$$ # '($9 )$$$ # '$%9 +*$$,$$$$,,($$ # '($9 ,$$$$ # '$%9 9! !" 2XWSXW 9ROWDH 0./11RP10D- 6',, 1 '($ 1 '*(7 9DF !" 2XWSXW 9ROWDH 0./11RP10D- 6,%# 1 '$% 1 ''87 1 1 1 1 9DF !" )UHTXH/F; 61RP./DO7 )8# 1 *$ 1 *$)6,7 += 0D-.PXP "R/W./XRXV 2XWSXW "XUUH/W #'($9 ,'),*',')#'('(+)! 0D-.PXP "R/W./XRXV 2XWSXW "XUUH/W #'$%9 1 ,*1 '(1 1 (%) 3RZHU )DFWRU 1,Adjuable-0.85to0.85 >)', 7BUHVBROG ,! 8W.O.W; 0R/.WRU./E ,VOD/G./ 3URWHFW.R/E CountryCon gurableThresholds <HV &1387 0D -.PXP '" 3RZHU #'($9 (*)$)8$$++)$8#$$,,%$$,))$$,+*)$ J 0D -.PXP '" 3RZHU #'$%9 1 ),$$1 ++)$1 1 ,)) 7UD/VIRUPHU1OHVVE 8/URX/GHG <HV 0D -.PXP ,/SXW 9ROWDH (%$9GF 1RP./DO '" ,/SXW 9ROWDH #%$($$9GF 0D -.PXP ,/SXW "XUUH/W #'($96'7 %),$),#),*)'$'+#$) !GF 0D-.PXP ,/SXW "XUUH/W #'$%96'7 1 8 1 ,#)1 1 '+ !GF 0D- ,/SXW 6BRUW ".UFX.W "XUUH/W ()!GF 5HYHUVH13RODU.W; 3URWHFW.R/<HV >URX/G1)DXOW ,VRODW.R/ 'HWHFW.R/*$$N 6H/V.W.Y.W; MaximumInverterE!ciency88 88'M CECWeightedE!ciency 88 88 # '($9 8%) # '$%9 M 1.BWW.PH 3RZHU "R/VXPSW.R/Q ')J 6,7 )RU RWBHU UH.R/DO VHWW./V SOHDVH FR/WDFW 6RODU(GH VXSSRUW 6'7Ahighercurrentsourcemaybeused;theinverterwilllimititsinputcurrenttothevaluesated 6L$OH3DVH&YHUWHU LW !"#DYH7HFROR$%IRU1RUW'PHULFD SE3000H-US/SE3800H-US/SE5000H-US/SE6000H-US/ SE7600H-US/SE10000H-US/SE11400H-US 918 S Elliot Pl 06/02/23 021805 6 !"86 6# !"86 6$ !"86 6% !"86 6&% !"86 6' !"86 6''( !"86 )*7*21)+)7856 6XSSRUWHGRPPXFDWR,WHUIDFHV 56 !(W"HUHW!#$%HH&RSWRDO'!HOOXODU&RSWRDO' 5HYHXH)UDGH0HWHU$!*16, +-.-/2SWRDO&3' RVXPSWRPHWHU$ ,YHUWHURPP VVR$WiththeSetAppmobileapplicationusingBuilt-inWi-FiAccessPointforLocalConnection 5DSG6"XWGRZ41(-/+DG -/+789/.+-*XWRPDWF5DSG6"XWGRZXSR*)UG'VFRHFW 67)1)5,203*)1, 6DIHW;UL1741,UL1741SA,UL1699B,CSAC22.2,CanadianAFCIaccordingtoT.I.L.M-07 )UGRHFWR6WDGDUGV ,(((+ 7!5XOH-+!5XOH+&+,' (PVVRV )3DUW+ ODVV% *167))7 *2163,*+*,)7*216 *2XWSXWRGXW6?H@*A) 5D$H +BB0DCPXP@+48*A)+BB0DCPXP@+4*A) ',SXWRGXW6?H@ERI6WU$V@ *A)5D$H 1''Maximum/1-2 rings/14-6AWG 1''Maximum/1-3 rings/14-6AWG 'PHVRVZW"6DIHW;6ZWF" &+CAC ''+7.7C+.8C8.@ /C37/C+7-+.3C+.8C7.3@ /C37/C+ @ PP AH$"WZW"6DIHW;6ZWF"--@+/- .+@++.-8.-@++.9 3.@+7.8 lb/kg 1RVHJ- J /G%* RRO$1DWXUDORYHFWR 2SHUDW$7HPSHUDWXUH5D$H4/WRL+/@4/WRL8/&'˚F/˚C 3URWHFWR5DW$1(0*M&,YHUWHUZW"6DIHW;6ZWF"' &3'InverterwithRevenueGradeMeterP/N:SExxxxH-US000BNC4;InverterwithRevenueGradeProductionandConsumptionMeterP/N:SExxxxH-US000BNI4.Forconsumptionmetering,currenttransformers shouldbeorderedseparately:SEACT0750-200NA-20orSEACT0750-400NA-20.20unitsperbox &'Fullpoweruptoatlea 50˚C/122˚F;forpowerde-ratinginformationreferto:https://www.solaredge.com/sites/default/"les/se-temperature-derating-note-na.pdf 6L-.OH3/DVH*-YHUWHU 4LW/!"9DYH7HF/-ROR.:IRU1RUW/)PHULFD SE3000H-US/SE3800H-US/SE5000H-US/SE6000H-US/ SE7600H-US/SE10000H-US/SE11400H-US ©SolarEdgeTechnologies,Inc.Allrightsreserved.SOLAREDGE,theSolarEdgelogo,OPTIMIZEDBYSOLAREDGEaretrademarksorregisteredtrademarksofSolarEdgeTechnologies,Inc.All othertrademarksmentionedhereinaretrademarksoftheirrespectiveowners.Date:01/2020/V01/ENGNAM.Subjecttochangewithoutnotice. !R4WR-DEOH,R-VXPSWLR-0R-LWRUL-. Bysimplywiringcurrenttransformersthroughtheinverter'sexistingACconduitsandconnectingthemtotheservicepanel,homeownerswillgainfullinsightintotheir householdenergyusagehelpingthemtoavoidhighelectricitybills 918 S Elliot Pl 06/02/23 918 S Elliot Pl 06/02/23