Project Name &
Address
Sheet Size
Sheet Number
ANSI B
11" X 17"
PV 0.0
Sheet Name
DRAWN BY
AP
N
:
0
1
0
2
6
3
2
5
SHEET INDEX:
COVER SHEET
SCALE: NTS
2 SATELLITE VIEW
PV 0.0
SCALE: NTS
3 VICINITY MAP
PV 0.0 SCALE: 1/16" = 1'-0"
1 PLOT PLAN
PV 0.0
GENERAL NOTES:
a. INSTALLATION OF SOLAR
PHOTOVOLTAIC SYSTEM SHALL BE IN
ACCORDANCE WITH NEC ARTICLE
690, AND ALL OTHER APPLICABLE
NEC CODES WHERE NOTED OR
EXISTING.
b. PROPER ACCESS AND WORKING
CLEARANCE AROUND EXISTING AND
PROPOSED ELECTRICAL EQUIPMENT
WILL COMPLY WITH NEC ARTICLE 110.
c. ALL CONDUCTORS, INCLUDING THE
GROUNDING ELECTRODE
CONDUCTOR SHALL BE PROTECTED
FROM PHYSICAL DAMAGE IN
ACCORDANCE WITH NEC ARTICLE
250.
d. THE PV MODULES ARE CONSIDERED
NON-COMBUSTIBLE; THIS SYSTEM IS
UTILITY INTERACTIVE PER UL 1741
AND ALSO INCLUDE STORAGE
BATTERIES OR OTHER ALTERNATIVE
STORAGE SOURCES.
e. ALL DC WIRES SHALL BE SIZED
ACCORDING TO [NEC 690.8]
f. DC CONDUCTORS SHALL BE WITHIN
PROTECTED RACEWAYS IN
ACCORDANCE WITH [NEC 690.31]
g. ALL SIGNAGE TO BE PLACED IN
ACCORDANCE WITH LOCAL
JURISDICTIONAL BUILDING CODE.
h. PV MODULES TO BE RATED UL 1703
CLASS C FIRE RATING OR BETTER.
i. ALL EQUIPMENT TO BE CERTIFIED BY
A NATIONALLY RECOGNIZED TESTING
LABORATORY.
PROTECTION OF EMERGENCY RESPONDERS
ALL SHARP EDGES AND FASTENER TIPS SHALL BE COVERED OR
CRIMPED OVER TO ELIMINATE SHARP EDGES, TO MINIMIZE RISK
OF INJURY TO EMERGENCY RESPONDERS.
ALL ROOF MOUNTED CONDUITS, BOXES, AND EQUIPMENT
CROSSING PATHWAYS ARE TO BE CLEARLY IDENTIFIED BY A
RED/WHITE REFLECTIVE TAPE OR OTHER APPROVED MATERIAL.
ROOF ACCESS POINT
ROOF ACCESS POINT SHALL NOT BE LOCATED IN
AREAS THAT DO NOT REQUIRE THE PLACEMENT
OF GROUND LADDERS OVER OPENINGS SUCH AS
WINDOWS OR DOORS, AND LOCATED AT STRONG
POINTS OF BUILDING CONSTRUCTION IN
LOCATIONS WHERE THE ACCESS POINT DOES NOT
CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH
AS TREE LIMBS, WIRES OR SIGNS.
SYSTEM SIZE: 11.520 kW DC
3.800 kW AC
MODULE TYPE & AMOUNT: (32) PANASONIC EVPV360PK 360W
MAIN SERVICE PANEL: EXISTING 100A BUS RATED MAIN PANEL
INVERTER: (01) SOLAREDGE ENERGY HUB SE3800H-USSNBBL14 [240V]
INTERCONNECTION METHOD: LOAD BREAKER
PHOTOVOLTAIC SYSTEM WORK SCOPE:
PHOTOVOLTAIC ROOF MOUNT SYSTEM
32 MODULES-ROOF MOUNTED - 11.520 kW DC, 3.800 kW AC, 917 W MCFADDEN AVE, SANTA ANA, CA 92707
ROOF ACCESS POINT
GOVERNING CODES
ALL WORK SHALL CONFORM TO THE FOLLOWING CODES
· 2022 CALIFORNIA BUILDING CODE
· 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
· 2022 CALIFORNIA EXISTING BUILDINGS CODE
· 2022 CALIFORNIA PLUMBING CODE
· 2022 CALIFORNIA FIRE CODE
· 2022 CALIFORNIA ENERGY CODE
· 2022 CALIFORNIA RESIDENTIAL CODE
· 2022 CALIFORNIA ELECTRIC CODE
· 2020 NATIONAL ELECTRIC CODE
EXISTING EXTERIOR MAIN
SERVICE PANEL TIED TO
EXTERIOR UTILITY METER
PV 0.0: COVER SHEET
PV 1.0: SITE PLAN
S 1.1: MOUNT DETAILS
E 1.1: 3-LINE DIAGRAM
E 1.2: NOTES
E 1.3: WARNING LABELS
- EQUIPMENT SPEC SHEET
ROOF #1
(11) PANASONIC EVPV360PK 360W
SLOPE: 30°
AZIM.: 90°
GATE
MAIN HOUSE
FRONT OF HOUSE
W MCFADDEN AVE
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
PR
O
P
E
R
T
Y
L
I
N
E
PROPERTY LINE
DRIVEWAY
PA
T
H
W
A
Y
GARAGE
FENCE
ROOF #2
(6) PANASONIC EVPV360PK 360W
SLOPE: 30°
AZIM.: 90°
ROOF #3
(15) PANASONIC EVPV360PK 360W
SLOPE: 30°
AZIM.: 270°
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
April 18, 2024
The scope of the plans is for
the installation of the solar
photovoltaic system only and
the approval is subject to
compliance with all
applicable city and state
codes and regulations
regarding construction. The
approval of the plans does
not constitute any
certification of the accuracy,
completeness, or building
permit status of the existing
buildings and structures as
shown.
Bldg# 101119790
Elec# 20183200
917 W McFadden Ave -
101119790 & 201832007/2/2024
M
I
91
7
W
M
C
F
A
D
D
E
N
A
V
E
R
E
S
I
D
E
N
C
E
91
7
W
M
C
F
A
D
D
E
N
A
V
E
,
SA
N
T
A
A
N
A
,
CA
92
7
0
7
Project Name &
Address
Sheet Size
Sheet Number
ANSI B
11" X 17"
PV 1.0
Sheet Name
DRAWN BY
AP
N
:
01
0
2
6
3
2
5
EQUIPMENT
LAYOUT & SITE
PLAN
SCALE:1/8" = 1'-0"
1 SITE PLAN
PV 1.0
ROOF SECTION(S)
MODULE, ARRAY WEIGHT (LOAD CALC'S)
Number of Modules 32
Module Weight 43.0 LBS
Total Module (Array) Weight 1376.00 LBS
Number of Attachment point 78
Mounting System Weight
(Per Module)1.5 LBS
Mounting System Weight 117.00 LBS
Total System Weight
(Module Weight + Mounting System Weight)1493.00 LBS
Weight at Each Attachment Point
(Array Weight / Number of Attachment Point)17.64 LBS
Module Area (69.1"x40.94")19.65 SqFt
Total Array Area 628.66 SqFt
Distributed Load
(Total System Weight / Total Array Area)2.27 Per SqFt
Total Roof Area 1571 SqFt
Total Percentage or Roof Covered
Total Array Area / Total Roof Area)*100 40.02%
SYSTEM SIZE: 11.520 kW DC
3.800 kW AC
MODULE TYPE & AMOUNT:(32) PANASONIC EVPV360PK 360W
MODULE DIMENSIONS:(L/W/H) 69.1"/40.94"/1.2"
INVERTER:(01) SOLAREDGE ENERGY HUB SE3800H-USSNBBL14 [240V]
PHOTOVOLTAIC SYSTEM WORK SCOPE:SYSTEM LEGEND
EXISTING EXTERIOR MAIN SERVICE PANEL & POINT
OF INTERCONNECTION. TIED TO EXTERIOR UTILITY
METER.
M
NEW 01 - SOLAREDGE ENERGY HUB
SE3800H-USSNBBL14 [240V] INVERTER.I
= ATTACHMENT POINTS
= RAFTERS
= ROOF OBSTRUCTIONS
= FIRE PATHWAY
= RACKING SYSTEM
32 NEW PANASONIC EVPV360PK 360W
MODULES WITH SOLAREDGE OPTIMIZER
MOUNTED ON THE BACK OF EACH MODULES.
STRING #1 - 16 MODULES
STRING(S)
EXISTING EXTERIOR MAIN SERVICE
PANEL & POINT OF INTERCONNECTION.
TIED TO EXTERIOR UTILITY METER
MODULE - 15
SLOPE - 30°
AZIMUTH - 270°
MATERIAL - COMP. SHINGLE
RAFTER SIZE & SPACING - 2"X4" @ 24" O.C.
MODULE - 6
SLOPE - 30°
AZIMUTH - 90°
MATERIAL - COMP. SHINGLE
RAFTER SIZE & SPACING - 2"X4" @ 24" O.C.
MODULE - 11
SLOPE - 30°
AZIMUTH - 90°
MATERIAL - COMP. SHINGLE
RAFTER SIZE & SPACING - 2"X4" @ 24" O.C.
ROOF #01
ROOF #02
ROOF #03
NEW SOLAREDGE ENERGY HUB
SE3800H-USSNBBL14 [240V] INVERTER
BILL OF MATERIALS
NUMBER OF MODULES 32 PANASONIC EVPV360PK 360W
NUMBER OF INVERTER 01 SOLAREDGE ENERGY HUB
SE3800H-USSNBBL14 [240V]
OPTIMIZER 32 SOLAREDGE S500 OPTIMIZER
NUMBER OF ATTACHMENTS 78 UNIRAC FLASHKIT PRO ATTACHMENTS
RAILS 21 UNIRAC SM LIGHT RAIL
RAIL SPLICE 8 SPLICE KIT
MID CLAMPS 36 MID CLAMPS
END CLAMPS 56 END CLAMPS / STOPPER SLEEVE
GROUNDING LUG 14 GROUNDING LUG
18
"
F
I
R
E
S
E
T
B
A
C
K
18
"
F
I
R
E
S
E
T
B
A
C
K
NE
W
P
V
A
T
T
A
C
H
M
E
N
T
AT
6
'
-
0
"
O
.
C
.
FRONT OF HOUSE
W MCFADDEN AVE
RO
O
F
#
0
1
36" FIRE SETBACK
STRING #2 - 16 MODULES
RO
O
F
#
0
3
RO
O
F
#
0
2
36" FIRE
SETBACK
36" FIRE SETBACK
18
"
F
I
R
E
S
E
T
B
A
C
K
18
"
F
I
R
E
S
E
T
B
A
C
K
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
April 18, 2024
NOTE:
Engineer of Record assumes that all structural
components of the existing building were
permitted and met the requirements of the
Building Code at the time of construction. Solar
Contractor shall field verify that the roof framing is
in its existing permitted condition and capable of
supporting required live loads. Framing specified
on solar plans shall be assumed to be minimum
size and spacing, actual framing may be different.
917 W McFadden Ave -
101119790 & 201832007/2/2024
91
7
W
M
C
F
A
D
D
E
N
A
V
E
R
E
S
I
D
E
N
C
E
91
7
W
M
C
F
A
D
D
E
N
A
V
E
,
SA
N
T
A
A
N
A
,
CA
92
7
0
7
Project Name &
Address
Sheet Size
Sheet Number
ANSI B
11" X 17"
S 1.1
Sheet Name
DRAWN BY
AP
N
:
01
0
2
6
3
2
5
MOUNT DETAIL
SCALE: NTS
2 ATTACHMENT DETAIL ENLARGED VIEW
S 1.1
SCALE: NTS
1 ATTACHMENT DETAIL (SIDE VIEW)
S 1.1
NOTE:
1.SOLAR INSTALLER MUST VERIFY AND CONFIRM ROOF
SUPPORT IS SUFFICIENT PRIOR TO PV INSTALLATION
SCALE: NTS
1 ATTACHMENT DETAIL (SIDE VIEW)
S 1.1
POINT OF PENETRATIONMID CLAMPEND CLAMP
MAX CANTILEVER 33% RAIL SPAN
6'-0"
L
(
L
X
2
5
%
)
M
A
X
GENERAL STRUCTURAL NOTES:
1.THE SOLAR PANELS ARE TO BE MOUNTED TO THE
ROOF FRAMING USING THE UNIRAC SM LIGHT
RACKING SYSTEM WITH UNIRAC FLASHKIT PRO
ATTACHMENTS. THE MOUNTING FEET ARE TO BE
SPACED AS SHOWN IN THE DETAILS, AND MUST
BE STAGGERED TO ADJACENT FRAMING
MEMBERS TO SPREAD OUT THE ADDITIONAL
LOAD.
2.UNLESS NOTED OTHERWISE, MOUNTING
ANCHORS SHALL BE 5/16" LAG SCREWS WITH A
MINIMUM OF 2-1/2" PENETRATION INTO ROOF
FRAMING.
3.THE PROPOSED PV SYSTEM ADDS 2.6 PSF TO THE
ROOF FRAMING SYSTEM.
4.ROOF LIVE LOAD = 20 PSF TYPICAL, 0 PSF UNDER
NEW PV SYSTEM.
5.GROUND SNOW LOAD = 0 PSF
6.WIND SPEED = 95 MPH
7.EXPOSURE CATEGORY = B
8.RISK CATEGORY = II
GREEN FASTEN GF1
FLASHING
5/16" EPDM BONDED
304-18.8 SS WASHER
LAG BOLT, 5/16"
UNIRAC FLASHKIT PRO
UNIRAC END / MID CLAMP
2"X4" RAFTER @ 24" OC
SEE (2/S 1.1) FOR
ENLARGED VIEW
PV MODULE
(E) COMP. SHINGLE ROOF
2"X4" RAFT
E
R
@
24" OC
PV MODULES
UNIRAC SM LIGHT RAIL
6"
1.2
"
6"
1.2
"
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
April 18, 2024
(1) 5/16" x 3.5" SS LAG
SCREWS WITH 2.5" MIN
EMBEDMENT INTO WOOD
917 W McFadden Ave -
101119790 & 201832007/2/2024
91
7
W
M
C
F
A
D
D
E
N
A
V
E
R
E
S
I
D
E
N
C
E
91
7
W
M
C
F
A
D
D
E
N
A
V
E
,
SA
N
T
A
A
N
A
,
CA
92
7
0
7
Project Name &
Address
Sheet Size
Sheet Number
ANSI B
11" X 17"
E 1.1
Sheet Name
DRAWN BY
AP
N
:
01
0
2
6
3
2
5
3-LINE
DIAGRAM
3800W
Rooftop conductor ampacities designed in compliance with
art. 690.8, Tables 310.15(B)(2)(a), 310.15(B)(3)(a),
310.15(B)(3)(c), 310.15(B)(16), Chapter 9 Table 4, 5, & 9.
Location specific temperature obtained from ASHRAE 2017
data tables
AMBIENT TEMP (HIGH TEMP 2%)
RECORD LOW TEMP 2°C
31°C
CONDUIT HEIGHT 0.5"C
ROOF TOP TEMP 53°C
CONDUCTOR TEMPERATURE RATE 90°C
PHOTOVOLTAIC SYSTEM
DC SYSTEM SIZE (WATTS)
NOMINAL AC VOLTAGE 240V
11520W
AC SYSTEM SIZE (WATTS)
TOTAL NUMBER OF MODULES 32
120% RULE
BUS BAR RATING X 120%) - MAIN BREAKER RATING
=MAX. PV OCPD
(100A x 120%) - 100A = 20A
PV MODULE RATING @ STC
MANUFACTURER
MAX. POWER-POINT CURRENT (IMP)
MAX. POWER-POINT VOLTAGE (VMP)
OPEN-CIRCUIT VOLTAGE (VOC)
SHORT-CIRCUIT CURRENT (ISC)
10.62 AMPS
33.9 VOLTS
40.6 VOLTS
11.26 AMPS
NOM. MAX. POWER AT STC (PMAX)
MAX. SYSTEM VOLTAGE
VOC TEMPERATURE COEFFICIENT
360 WATT
1000V
-0.26 %/°C
SYSTEM SIZE: 11.520 kW DC
3.800 kW AC
MODULE:(32) PANASONIC EVPV360PK 360W
INVERTER:(01) SOLAREDGE ENERGY HUB SE3800H-USSNBBL14 [240V]
INVERTER CHARACTERISTICS - SOLAREDGE SE 3800H-US
MAX OUTPUT POWER 3800 W
SYSTEM OPERATING VOLTAGE 380 V
MAX CONTINOUS OUTPUT CURRENT 16 A
MAX INPUT VOLTAGE 480 V
SYSTEM SHORT CIRCUIT CURRENT 15 A
MAX EFFICIENCY 99 %
PANASONIC EVPV360PK 360W
WIRE
QTY
WIRE
TAG #CONDUIT WIRE TYPE STRING
WATTAGE
OPERATING
VOLTAGE
CONDUIT
FILL:
TEMP
RATING:
WIRE
AMP
TEMP
DE-RATE:
WIRE
OCP:
MAX SYSTEM
VOLTAGE
GRND
SIZE
WIRE
GAUGE:
TERMINAL
75°C RATING:NEC:MAX
AMPS
x x =/x =1.25380V5760W 18.95A30.72A 35A90°C
35A /x =1.25380V5760W 18.95Axx=24.32A90°C
35A /x =1.25 20.00Axx=32.9A75°C
40A#10
40A#10
35A#10
3/4" EMT
3/4" EMT
WIRE FROM - -
JUNCTION BOX TO
INVERTER
INVERTER TO MSP
ARRAY TO
JUNCTION BOX1
2
3
PV WIRE
THWN-2
THWN-2
4 0.80
3 1.00
IN AIR
/
=
=
=
=STRING
AMPS
15.16A
15.16A
16A
x =GRND WIRE
TYPE
480V
480V
240V
#8
#8
THWN-2
THWN-2
0.96
0.76
0.94
#6 SBC40.80
3
=
AC
SOLAREDGE ENERGY HUB
SE3800H-USSNBBL14 [240V] INVERTER
OUTPUT: 240VAC, 16A
99% CEC WEIGHTED EFFICIENCY
NEMA 3R, UL LISTED, INTERNAL GFDI
WITH INTEGRATED DC DISCONNECT
DC
32 NEW PANASONIC EVPV360PK 360W
MODULES WITH SOLAREDGE OPTIMIZER
MOUNTED ON THE BACK OF EACH MODULES.
(N) SOLAREDGE S500
OPTIMIZERS
JUNCTION BOX
600 V, NEMA 4
UL LISTED
1 2
-+
+
-+
++---
=
=
=
=
=
=
-+
2 161
-+
+
-+
++---
=
=
=
=
=
=
-+
2 161
MANUFACTURER
DC INPUT POWER 500W
SOLAREDGE S500
DC MAX INPUT VOLTAGE
DC MAX INPUT CURRENT
DC MAX OUTPUT CURRENT
60V
15A
15A
MAX INPUT VOLTAGE 480A
OPTIMIZER SPECIFICATIONS
(N) 20A FEEDER
BREAKER AT THE OPPOSITE
END OF THE MAIN SERVICE
BUSBAR FROM THE MAIN
OVERCURRENT DEVICE.
G
N
EXISTING GROUNDING
ELECTRODE SYSTEM
100A
M
20A
(E) LOADS
POINT OF INTERCONNECT, LOAD SIDE
EXISTING 240V/100A BUS BAR
RATING, MAIN SERVICE
PANEL, SINGLE PHASE, WITH
A 100A MAIN DISCONNECT
917 W McFadden Ave -
101119790 & 201832007/2/2024
91
7
W
M
C
F
A
D
D
E
N
A
V
E
R
E
S
I
D
E
N
C
E
91
7
W
M
C
F
A
D
D
E
N
A
V
E
,
SA
N
T
A
A
N
A
,
CA
92
7
0
7
Project Name &
Address
Sheet Size
Sheet Number
ANSI B
11" X 17"
E 1.2
Sheet Name
DRAWN BY
AP
N
:
01
0
2
6
3
2
5
NOTES
SITE NOTES:
1.A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A
UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
3.THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL,
OR BUILDING ROOF VENTS.
4.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED
ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
5.ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN
ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S
INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE
BUILDING OR STRUCTURE.
EQUIPMENT LOCATIONS:
1.ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
2.WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED
OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLES
310.15 (B)(2)(A) AND 310.15 (B)(3)(C).
3.JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES
ACCORDING TO NEC 690.34.
4.ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT
WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 2.2.6 ALL EQUIPMENT SHALL BE
INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC
APPLICABLE CODES.
5.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR
USAGE WHEN APPROPRIATE.
STRUCTURAL NOTES:
1.RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO
CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED
SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE
BEYOND EITHER EDGE OF THE ARRAY/SUB ARRAY, ACCORDING TO RAI
MANUFACTURER’S INSTRUCTIONS.
2.JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF
ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL
REQUIREMENTS.
3.ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/
APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.
4.ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE
SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 2.3.6 WHEN
POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED
AMONGST THE ROOF FRAMING MEMBERS.
WIRING & CONDUIT NOTES:
1.ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.
CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.
2.CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
3.VOLTAGE DROP LIMITED TO 1.5%.
4.DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRING SYSTEMS
SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE WIRING CLIPS.
5.AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK
PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3-
BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREY IN
4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE
MARKED ORANGE [NEC 110.15].
GROUNDING NOTES:
1.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND
GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH
USE.
2.PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM
NEC TABLE 250.122.
3.METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES
CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).
4.EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC
690.45 AND MICROINVERTER MANUFACTORERS’ INSTRUCTIONS.
5.EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN
MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE
NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED
GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION
REQUIREMENTS.
6.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT
THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO
ANOTHER MODULE.
7.GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED
GREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]
8.THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50
THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A
GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47
AND AHJ.
9.GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1) AND (2) TO
REDUCE FIRE HAZARDS
DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
1.DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS
OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE
TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).
2.DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE
LOCKABLE, AND BE A VISIBLE-BREAK SWITCH
3.PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID
SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY
RESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D).
4.ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND
240.
5.MICROINVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED
FUSES IN ACCORDANCE WITH NEC 110.3(B).
6.IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION
ACCORDING TO NEC 690.11 AND UL1699B.
INTERCONNECTION NOTES:
1.LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12 (B)]
2.THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAY NOT
EXCEED 120% OF BUSBAR RATING [NEC 705.12(D)(2)(3)].
3.THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT
AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL
NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED
BACKFEED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE
UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)].
4.AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL
RATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF
BUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED
ACCORDING TO NEC 705.12 (B)(2)(3)(C).
5.FEEDER TAP INTERCONECTION (LOADSIDE) ACCORDING TO NEC 705.12 (B)(2)(1)
6.SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITH SERVICE
ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.42 2.7.8BACKFEEDING
BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM ADDITIONAL
FASTENING [NEC 705.12 (B)(5)].
917 W McFadden Ave -
101119790 & 201832007/2/2024
M I
91
7
W
M
C
F
A
D
D
E
N
A
V
E
R
E
S
I
D
E
N
C
E
91
7
W
M
C
F
A
D
D
E
N
A
V
E
,
SA
N
T
A
A
N
A
,
CA
92
7
0
7
Project Name &
Address
Sheet Size
Sheet Number
ANSI B
11" X 17"
E 1.3
Sheet Name
DRAWN BY
AP
N
:
01
0
2
6
3
2
5
WARNING
LABELS
(32) PV MODULES
INVERTER
UTILITY METER &
MAIN SERVICE PANEL
W
M
C
F
A
D
D
E
N
A
V
E
SOLAR PHOTOVOLTAIC
SYSTEMS
(PER CODE: NEC 690)
A
SOLAR PV SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
TURN RAPID
SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUTDOWN PV
SYSTEM AND
REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR
ELECTRIC
PV PANELS
AT INVERTER [IFC 605.11.3.1(1) & 690.56(C)]
PER CODE: NEC 2020
ELECTRICAL SHOCK HAZARD
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING!
LABEL LOCATION:
WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BE
ENERGIZED IN THE OPEN POSITION, A WARNING SIGN SHALL BE
MOUNTED ON OR ADJACENT TO THE DISCONNECTING MEANS.
PER CODE(S): NEC 2020:
NEC 706.15(C)(4) and NEC 690.13(B)
WARNING!DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
LABEL LOCATION:
PRODUCTION / NET METER (BI-DIRECTIONAL)
NEC: 2020
NEC 690.59, 705.12(D)(3)
WARNING: PHOTOVOLTAIC
POWER SOURCE
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT
LABEL LOCATION: MAIN SERVICE DISCONNECT, NEC 2020, 690.13(B)
POWER SOURCE OUTPUT
CONNECTION. DO NOT RELOCATE
THIS OVERCURRENT DEVICE.
WARNING!
LABEL LOCATION:
MAIN SERVICE DISCONNECT
NEC: 2020, 705.12(B)(3)(2)
LABEL LOCATION:
PERMANENT WARNING LABELS SHALL BE APPLIED
TO DISTRIBUTION EQUIPMENT, AC DISCONNECT
NEC: 2020, PER CODE: 705.12(B)(3)(3)
PHOTOVOLTAIC
AC DISCONNECT
LABEL LOCATION:
AC DISCONNECT, NEC: 2020, (NEC 690.13(B)
PHOTOVOLTAIC
DC DISCONNECT
LABEL LOCATION:
DC DISCONNECT
(NEC 690.13(B)
M
A
C
IN
V
E
R
T
E
R
J/B
PV ARRAY
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION :
EXPOSED RACEWAY, CABLE TRAYS, JUNCTION BOX
NEC: 2020, PER CODE: NEC 690.31(D)(2)
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION
NEC: 2020
(PER CODE: NEC 690.54)
PHOTOVOLTAIC SYSTEM AC DISCONNECT
RATED AC OPERATING CURRENT 16 AMPS
AC NOMINAL OPERATING VOLTAGE 240 VOLTS
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
LABEL LOCATION:
UTILITY SERVICE ENTRANCE/METER, INVERTER/DC DISCONNECT IF REQUIRED BY
LOCAL AHJ, OR OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.
PER CODE(S): NEC 2020: ARTICLE 690.56(C)
SOLAR PHOTOVOLTAIC
SYSTEMS
(PER CODE: NEC 690)
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:
MAXIMUM CIRCUIT CURRENT:
MAX RATED OUTPUT CURRENT OF THE CHARGE
CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED):
VDC
ADC
ADC
480
30.32
15
INVERTER #1 (SOLAREDGE ENERGY HUB
SE3800H-USSNBBL14 [240V])
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020,
PER CODE: 690.53
THIS EQUIPMENT FED BY MULTIPLE
SOURCES, TOTAL RATING OF ALL
OVERCURRENT DEVICES,
EXCLUDING MAIN SUPPLY
OVERCURRENT DEVICE, SHALL NOT
EXCEED AMPACITY OF BUSBAR.
WARNING!
CAUTION
MULTIPLE SOURCES OF POWER
N
917 W McFadden Ave -
101119790 & 201832007/2/2024
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
June 5, 2024
917 W McFadden Ave -
101119790 & 201832007/2/2024
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
June 5, 2024
917 W McFadden Ave -
101119790 & 201832007/2/2024
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
June 5, 2024
917 W McFadden Ave -
101119790 & 201832007/2/2024
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
June 5, 2024
917 W McFadden Ave -
101119790 & 201832007/2/2024
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
June 5, 2024
917 W McFadden Ave -
101119790 & 201832007/2/2024
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
June 5, 2024
917 W McFadden Ave -
101119790 & 201832007/2/2024
www. Loyd W Martin .com
Solar Structures Engineering
#2024-0564 Structural Only
June 5, 2024
917 W McFadden Ave -
101119790 & 201832007/2/2024
Certificate Of Completion
Envelope Id: 8259DD555C6B40FFA5C51BDC6FC60C5F Status: Completed
Subject: Complete with DocuSign: Lettter to City of Santa Ana.pdf
Source Envelope:
Document Pages: 1 Signatures: 2 Envelope Originator:
Certificate Pages: 5 Initials: 0 Michelle Griffin
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
michelle@gtechsmartremodeling.com
IP Address: 63.47.105.145
Record Tracking
Status: Original
5/8/2024 9:04:40 PM
Holder: Michelle Griffin
michelle@gtechsmartremodeling.com
Location: DocuSign
Signer Events Signature Timestamp
Ariel Yemini
Ariel@SolarPriceDiscovery.com
CEO
X
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 99.10.72.187
Signed using mobile
Sent: 5/8/2024 9:04:52 PM
Resent: 5/8/2024 9:30:57 PM
Viewed: 5/8/2024 9:33:48 PM
Signed: 5/8/2024 9:33:56 PM
Electronic Record and Signature Disclosure:
Accepted: 5/8/2024 9:33:48 PM
ID: a4fd13cd-d8fe-421c-b80c-a74de4700502
Jenny E Garcia
jenny_gar_1@hotmail.com
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 104.58.251.222
Signed using mobile
Sent: 5/8/2024 9:04:52 PM
Resent: 5/8/2024 9:30:57 PM
Viewed: 5/8/2024 10:13:50 PM
Signed: 5/8/2024 10:14:41 PM
Electronic Record and Signature Disclosure:
Accepted: 5/8/2024 9:16:36 PM
ID: 755a8b2d-2570-423d-adb9-ca2de751c5d0
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 5/8/2024 9:04:53 PM
Envelope Updated Security Checked 5/8/2024 9:30:42 PM
Envelope Updated Security Checked 5/8/2024 9:30:42 PM
917 W McFadden Ave -
101119790 & 201832007/2/2024
Envelope Summary Events Status Timestamps
Certified Delivered Security Checked 5/8/2024 10:13:50 PM
Signing Complete Security Checked 5/8/2024 10:14:41 PM
Completed Security Checked 5/8/2024 10:14:41 PM
Payment Events Status Timestamps
Electronic Record and Signature Disclosure
917 W McFadden Ave -
101119790 & 201832007/2/2024
ELECTRONIC RECORD AND SIGNATURE DISCLOSURE
From time to time, sahar amstat (we, us or Company) may be required by law to provide to you
certain written notices or disclosures. Described below are the terms and conditions for providing
to you such notices and disclosures electronically through the DocuSign system. Please read the
information below carefully and thoroughly, and if you can access this information electronically
to your satisfaction and agree to this Electronic Record and Signature Disclosure (ERSD), please
confirm your agreement by selecting the check-box next to ‘I agree to use electronic records and
signatures’ before clicking ‘CONTINUE’ within the DocuSign system.
Getting paper copies
At any time, you may request from us a paper copy of any record provided or made available
electronically to you by us. You will have the ability to download and print documents we send
to you through the DocuSign system during and immediately after the signing session and, if you
elect to create a DocuSign account, you may access the documents for a limited period of time
(usually 30 days) after such documents are first sent to you. After such time, if you wish for us to
send you paper copies of any such documents from our office to you, you will be charged a
$0.00 per-page fee. You may request deliver y of such paper copies from us by following the
procedure described below.
Withdrawing your consent
If you decide to receive notices and disclosures from us electronically, you may at any time
change your mind and tell us that thereafter you want to receive required notices and disclosures
only in paper format. How you must inform us of your decision to receive future notices and
disclosure in paper format and withdraw your consent to receive notices and disclosures
electronically is described below.
Consequences of changing your mind
If you elect to receive required notices and disclosures only in paper format, it will slow the
speed at which we can complete certain steps in transactions with you and delivering services to
you because we will need first to send the required notices or disclosures to you in paper format,
and then wait until we receive back from you your acknowledgment of your receipt of such
paper notices or disclosures. Further, you will no longer be able to use the DocuSign system to
receive required notices and consents electronically from us or to sign electronically documents
from us.
All notices and disclosures will be sent to you electronically
Electronic Record and Signature Disclosure created on: 3/22/2023 10:59:42 AM
Parties agreed to: Ariel Yemini, Jenny E Garcia 917 W McFadden Ave -
101119790 & 201832007/2/2024
Unless you tell us otherwise in accordance with the procedures described herein, we will provide
electronically to you through the DocuSign system all required notices, disclosures,
authorizations, acknowledgements, and other documents that are required to be provided or made
available to you during the course of our relationship with you. To reduce the chance of you
inadvertently not receiving any notice or disclosure, we prefer to provide all of the required
notices and disclosures to you by the same method and to the same address that you have given
us. Thus, you can receive all the disclosures and notices electronically or in paper format through
the paper mail delivery system. If you do not agree with this process, please let us know as
described below. Please also see the paragraph immediately above that describes the
consequences of your electing not to receive delivery of the notices and disclosures
electronically from us.
How to contact sahar amstat:
You may contact us to let us know of your changes as to how we may contact you electronically,
to request paper copies of certain information from us, and to withdraw your prior consent to
receive notices and disclosures electronically as follows:
To contact us by email send messages to: financing@gtechsmartremodeling.com
To advise sahar amstat of your new email address
To let us know of a change in your email address where we should send notices and disclosures
electronically to you, you must send an email message to us
at financing@gtechsmartremodeling.com and in the body of such request you must state: your
previous email address, your new email address. We do not require any other information from
you to change your email address.
If you created a DocuSign account, you may update it with your new email address through your
account preferences.
To request paper copies from sahar amstat
To request delivery from us of paper copies of the notices and disclosures previously provided
by us to you electronically, you must send us an email
to financing@gtechsmartremodeling.com and in the body of such request you must state your
email address, full name, mailing address, and telephone number. We will bill you for any fees at
that time, if any.
To withdraw your consent with sahar amstat
To inform us that you no longer wish to receive future notices and disclosures in electronic
format you may:
917 W McFadden Ave -
101119790 & 201832007/2/2024
i. decline to sign a document from within your signing session, and on the subsequent page,
select the check-box indicating you wish to withdraw your consent, or you may;
ii. send us an email to financing@gtechsmartremodeling.com and in the body of such request
you must state your email, full name, mailing address, and telephone number. We do not need
any other information from you to withdraw consent.. The consequences of your withdrawing
consent for online documents will be that transactions may take a longer time to process..
Required hardware and software
The minimum system requirements for using the DocuSign system may change over time. The
current system requirements are found here: https://support.docusign.com/guides/signer-guide-
signing-system-requirements.
Acknowledging your access and consent to receive and sign documents electronically
To confirm to us that you can access this information electronically, which will be similar to
other electronic notices and disclosures that we will provide to you, please confirm that you have
read this ERSD, and (i) that you are able to print on paper or electronically save this ERSD for
your future reference and access; or (ii) that you are able to email this ERSD to an email address
where you will be able to print on paper or save it for your future reference and access. Further,
if you consent to receiving notices and disclosures exclusively in electronic format as described
herein, then select the check-box next to ‘I agree to use electronic records and signatures’ before
clicking ‘CONTINUE’ within the DocuSign system.
By selecting the check-box next to ‘I agree to use electronic records and signatures’, you confirm
that:
You can access and read this Electronic Record and Signature Disclosure; and
You can print on paper this Electronic Record and Signature Disclosure, or save or send
this Electronic Record and Disclosure to a location where you can print it, for future
reference and access; and
Until or unless you notify sahar amstat as described above, you consent to receive
exclusively through electronic means all notices, disclosures, authorizations,
acknowledgements, and other documents that are required to be provided or made
available to you by sahar amstat during the course of your relationship with sahar amstat.
917 W McFadden Ave -
101119790 & 201832007/2/2024
Expedited Permit Process for PV Systems 1
Expedited Permit Process for PV Systems
Standard String System
The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro-
cess provides a means to differentiate systems that can be permitted quickly and easily
due to their similarity with the majority of small-scale PV systems. Those systems with
unique characteristics may be handled with small additions to this Expedited Permit
Process or may require much more information, depending on the uniqueness of the
installation.
The following pages contain forms for the Standard String System to use with the Expe-
dited Permit Process. The Micro-Inverter, AC Module, and Supply-Side Connection forms
are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic-
tions that have adopted the Expedited Permit Process for PV Systems, these forms can
be filled out electronically and submitted in either printed form and via email. An elec-
tronic format is used so that the supplied information is standardized and legible for the
local jurisdiction.
917 W McFadden Ave -
101119790 & 201832007/2/2024
Expedited Permit Process for PV Systems 2
Expedited Permit Process for Small-Scale PV Systems
Standard String System
The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations
are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential
systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been
suggested to provide as a path to permit approval.
Required Information for Permit:
1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it
should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings
with a 3’ perimeter space at ridge and sides may not need separate fire service review.
2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects,
required signs, and ac connection to building (see supplied standard electrical diagram).
3. Specification sheets and installation manuals (if available) for all manufactured components including, but not
limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system.
Step 1: Structural Review of PV Array Mounting System
Is the array to be mounted on a defined, permitted roof structure? l Yes l No
If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1.
Roof Information:
1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________
____________________________________________________________________________________________________
If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…).
2. Does the roof have a single roof covering? l Yes l No
If No, submit completed worksheet for roof structure WKS1.
3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________
Mounting System Information:
1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap
beneath the module frames? l Yes l No
If No, provide details of structural attachment certified by a design professional.
2. For manufactured mounting systems, fill out information on the mounting system below:
a. Mounting System Manufacturer ___________Product Name and Model#________________________________
b. Total Weight of PV Modules and Rails ___________lbs
c. Total Number of Attachment Points____________
d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1)
e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for
maximum spacing allowed based on maximum design wind speed)
f. Total Surface Area of PV Modules (square feet)_________________ ft2
g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2
If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1.
Step 2: Electrical Review of PV System (Calculations for Electrical Diagram)
In order for a PV system to be considered for an expedited permit process, the following must apply:
1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems.
2. The PV array is composed of 4 series strings or less per inverter.
3. The total inverter capacity has a continuous ac power output 13,440 Watts or less
4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)).
5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV
system. Interactive PDF diagrams are available at www.solarabcs.org/permitting.
Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant
understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively
communicate, provide an alternative diagram with appropriate detail.
917 W McFadden Ave -
101119790 & 201832007/2/2024
E
x
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
3
Standard String System Site Plan
917 W McFadden Ave -
101119790 & 201832007/2/2024
E
x
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
4
Standard String System Electrical Diagram
917 W McFadden Ave -
101119790 & 201832007/2/2024
E
x
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
5
Notes for Standard String System Electrical Diagram
Contractor Name,
Address and Phone:
_________________
_________________
_________________
_________________
Notes for One-Line Standard Electrical
Diagram for Single-Phase PV Systems
Site Name: __________________________
Site Address: ________________________
System AC Size: ______________________
SIZE FSCM NO DWG NO REV
SCALE NTS Date:SHEET
Drawn By:
Checked By:
MAX POWER-POINT CURRENT (IMP)
MAX POWER-POINT VOLTAGE (VMP)
OPEN-CIRCUIT VOLTAGE (VOC)
SHORT-CIRCUIT CURRENT (ISC)
MAX SERIES FUSE (OCPD)
MAXIMUM POWER (PMAX)
MAX VOLTAGE (TYP 600VDC)
VOC TEMP COEFF (mV/oC or %/oC )
IF COEFF SUPPLIED, CIRCLE UNITS
A
V
V
A
A
W
V
MODULE MAKE
MODULE MODEL
PV MODULE RATINGS @ STC (Guide Section 5)
MAX DC VOLT RATING
MAX POWER @ 40oC
NOMINAL AC VOLTAGE
MAX AC CURRENT
MAX OCPD RATING
V
W
V
A
A
INVERTER MAKE
INVERTER MODEL
INVERTER RATINGS (Guide Section 4)
1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THEREQUIREMENT? YES NO N/A
2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THEREQUIREMENT? YES NO N/A
3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAXCURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT
4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTEROCPD AMPERE RATING. (See Guide Section 9)
5) TOTAL OF ______ INVERTER OCPD(s), ONE FOR EACH INVERTER. DOES TOTALSUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)?YES NO
NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):
1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEANEXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ______oC
2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHESTMONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE _____oC
2.) 2005 ASHRAE FUNDEMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT ATLEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF47oC OR LESS (ALL OF UNITED STATES),
a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLERFUSE. b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLERFUSE.
NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix D):
OCPD = OVERCURRENT PROTECTION DEVICE
NATIONAL ELECTRICAL CODE® REFERENCES
SHOWN AS (NEC XXX.XX)
NOTES FOR ALL DRAWINGS:
SIGNS–SEE GUIDE SECTION 7
SIGN FOR DC DISCONNECT
SIGN FOR INVERTER OCPD AND
AC DISCONNECT (IF USED)
RATED MPP CURRENT
RATED MPP VOLTAGE
MAX SYSTEM VOLTAGE
MAX CIRCUIT CURRENT
A
V
V
A
PHOTOVOLTAIC POWER SOURCE
WARNING: ELECTRICAL SHOCK
HAZARD–LINE AND LOAD MAY BE
ENERGIZED IN OPEN POSITION
AC OUTPUT CURRENT
NOMINAL AC VOLTAGE
A
V
SOLAR PV SYSTEM
AC POINT OF CONNECTION
THIS PANEL FED BY MULTIPLE
SOURCES (UTILITY AND SOLAR)
917 W McFadden Ave -
101119790 & 201832007/2/2024
Dear City of Santa Ana,
I, _____________, am the legal owner of the property located at __________________________________,
and I hereby authorize Ariel Yemeni and the Solar Price Discovery team to act on my behalf in matters
strictly related to the installation of the solar system at the aforementioned property.
This authorization is limited to:
Consulting with me before making any decisions that involve a financial commitment
over$2,000.00.
Obtaining my written approval for any repairs or renovations related to the property that
exceed routine maintenance.
Providing weekly updates on the status of the project, including any communications
with city oAicials, contractors, or other relevant parties.
I understand that this authorization is valid until ______________ or until further notice in
writing from me. I reserve the right to revoke this authorization at any time.
I am responsible for any actions taken by Ariel Yemeni or the Solar Price Discovery Team on my
behalf, within the bounds of the limitations specified above.
Homeowner Signature: ___________________________ Date: _______________
Printed Name: ____________________ Date: _______________
Contractor Signature: ___________________________ Date:________________
DocuSign Envelope ID: 8259DD55-5C6B-40FF-A5C5-1BDC6FC60C5F
Ariel Yemini
5/8/2024
Jenny E Garcia
05/08/2025
917 W. McFadden ave. Santa Ana
5/8/2024
5/8/2024
Jenny E Garcia
917 W McFadden Ave -
101119790 & 201832007/2/2024
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
917 W McFadden Ave, Santa Ana, CA 92707
Solar Discovery
C10 1014977
x
x
x
x
x
x
x
x
x
x
Ariel Yemeni
818-925-1252 x 1
Production@solarpricediscovery.com
3/4/2024
917 W McFadden Ave -
101119790 & 201832007/2/2024
Structural Calculations for a Roof Mounted Solar Photovoltaic System for:
917 W McFadden Ave
Santa Ana, CA 92707
Applicable Codes:
2022 California Building Code, 2022 California Electric Code,
2022 California Mechanical Code, American Society of Civil Engineers
Standard ASCE 7-16 Minimum Design Loads for Buildings and Other
Structures, American Wood Council 2018 National Design Specification
for Wood Construction, Local Municipal Code, and all other codes which
are adopted by reference or enacted by law.
Assumed Design Parameters:
The existing structure has been built under a building permit and is in its
original condition. The existing roof structure is capable of its code
required live load and the ability of the roof structure to support live loads
has not been substantially reduced by the age of the structure, termites or
mold, or unauthorized modifications to the existing structure. Solar Energy
Contractor shall make an inspection of the existing roof framing system
prior to installation of the roof mounted solar energy system to verify that
the existing roof is capable of supporting minimum roof live loads.
Assumed Design Parameters:
All 2x members are grade Douglas Fir #2 or better
All 4X members are grade Douglas Fir #1 or better
All Roof Connectors are Simpson Strong-Tie or Equal
All Concrete Foundations are f'c = 2500 psi or stronger
Sht # 1 of 7
2024-0564 Solar Survey Pro 917 W McFadden Ave April 18, 2024
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Original Structure was built to the Type-V Wood Framed Standards of the
Applicable Building Code at the time of Construction.
917 W McFadden Ave -
101119790 & 201832007/2/2024
Note to Building Official:
Based upon a review of the proposed plans I am confident that the
existing roof framing system is capable of safely supporting the additional
loads caused by the new solar photovoltaic energy system. The contractor
shall field verify that the existing roof structure is in its original permited
condition and verify that it can support the normal code required roof live
loads. Attached in this package are several calculations showing that the
roof members can support the additional weight of the solar array.
Furthermore, an analysis of the solar array's support for wind forces and a
seismic analysis of the existing structure are also included.
Check Existing 2X4 Roof Rafters @ 24" O.C.:
(Assume max rafters span = 7.83 ft.)
w =30 psf x 2 ft. = 60 plf
Total load on rafters = 60 plf x 7.83 ft. = 470 lbs
Sht # 2 of 7
2024-0564 Solar Survey Pro 917 W McFadden Ave April 18, 2024
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
7.83'
917 W McFadden Ave -
101119790 & 201832007/2/2024
Check Existing 2X4 Roof Rafters @ 24" O.C.:
Snow Load =0 psf
Dead Load =14 psf
Live Load =16 psf
WDL + LL =30 psf x 2 ft. = 60 plf
WDL =14 psf x 2 ft. = 28 plf
w =30 psf x 2 ft. = 60 plf
Total load on rafters =( 60 plf x 1.5 ft ) + ( 28 plf x 6.33 ft ) + ( 6' x 1.7' x 3 psf x 4 )
=390 lbs < 470 lbs OK
OK. Per 2022 California Existing Building Code Section 503.3 Alterations
Check attachment of Support to Existing Structure for Wind Uplift
CHECK SOLAR STRUCTURE ATTACHMENTS PER ASCE 7-16 WIND LOADS ON BUILDING
APPURTENANCES AND OTHER STRUCTURES Section 29.4.4 THEREFORE CHECK
ATTACHMENT FOR TYPICAL CRITICAL LOAD WHICH IS THE EDGE ZONE - ZONE 2.
NOTE: PER DEFINITION ON SHEETS 246 & 247 OF ASCE 7-16 EFFECTIVE WIND AREA:
FOR ROOFTOP SOLAR ARRAYS, THE EFFECTIVE WIND AREA IN FIG. 29.4-7 IS
EQUAL TO THE TRIBUTARY AREA FOR THE STRUCTURAL ELEMENT BEING
CONSIDERED, EXCEPT THAT THE WIDTH OF THE EFFECTIVE WIND AREA NEED NOT
BE LESS THAN ONE-THIRD ITS LENGTH.
EFFECTIVE AREA = 15 SQ FT
Sht # 3 of 7
2024-0564 Solar Survey Pro 917 W McFadden Ave April 18, 2024
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
% CHANGE =390 lbs - 470 lbs x 100 =-17% < 5% OK470 lbs
917 W McFadden Ave -
101119790 & 201832007/2/2024
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Tributary Area to Each Solar Mount = 6 ft. x 2.9 ft. = 17.4 sq. ft. ( Max )
Calculate Design Wind Pressure at each support (Wind Speed 130 mph Exposure C):
p = q h (GC p )(γ E )(γ a )Eq'n 29.4-7 ASCE 7-16
q h = 0.00256 K z K zt K d K e V 2 Eq'n 26.10-1 ASCE 7-16
Note:
K z =velocity pressure coefficient Section 29.10.1 ASCE 7-16
K z =0.9 (Exposure C, Height = 20 ft or less)
K zt =Topographical Factor = 1.0
K d =Wind Directionality Factor = 0.85
K e =Ground Elevation Factor = 1.0
V =130 mph ;VASB =101 mph
q h =0.00256 (0.9) (1.0) (0.85) (1.0) (101)²
q h =19.98 psf
GC p =-2.0 (Zone 2 ; Effective Area = 15 sq. ft. )
γ E =Exposure Factor = 1.5
γ a =Solar Array Pressure Equalization Factor = 0.7 Fig. 29.4-8 ASCE 7-16
p = q h (GC p )(γ E )(γ a )
p = 19.98 psf (-2.0) (1.5) (0.7) = 42 psf
Sht # 4 of 7
2024-0564 Solar Survey Pro 917 W McFadden Ave April 18, 2024
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
917 W McFadden Ave -
101119790 & 201832007/2/2024
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Nominal (Unfactored) Uplift at each support = 42 psf x 17.4 sq. ft. = 730.8 lbs
Note: Section 2.4.1 of ASCE 7-16, Basic Load Combinations for Allowable Stress
Design. Note: Applicable Load Combination #5 (D + 0.6W)
Design (Factored) Uplift at each support = 0.6 x 730.8 lbs = 438 lbs
Load per lag screw = 438 lbs / 1 = 438 lbs
Determine allowable load per 5/16" lag screw w/ 2.5" embedment into wood below
according to the 2018 NDS.
W ' = W x Cd x Ct Table 10.3.1 2018 NDS
where
W = 266 lbs / in. of embedment per Table 12.2a
Cd = 1.6 per Table 2.3.2 of 2018 NDS
Ct = 1.0 per Table 2.3.3 of 2018 NDS
W' = 266 lbs/ in. x 2.5 in. x 1.6 x 1.0 = 1,064 lbs > 438 lbs OK
Sht # 5 of 7
2024-0564 Solar Survey Pro 917 W McFadden Ave April 18, 2024
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Use Support connected to 2x Min. Roof Member w/
(1) 5/16" x 3.5" lag screws per connection minimum.
917 W McFadden Ave -
101119790 & 201832007/2/2024
Check Seismic load due to added dead load of photovoltaic system.
Determine Seismic Weight of Existing Building:
Effective Existing Seismic Weight
Area of (E) Building =Approximately 1,500 Sq. ft
Approximate
Effective =1,500 sq. ft. x 30 psf ave. = 45,000 LBS
Seismic Weight
DETERMINE BASE SHEAR
V = Cs W EQ'N 12.8-1 ASCE 7-16
EQ'N 12.8-2 ASCE 7-16
R = THE RESPONSE MODIFICATION FACTOR IN TABLE 12.2-1
R =6.5 WOOD SHEAR WALLS
Ie = 1.0 IMPORTANCE FACTOR
SDS = 2/3 x SMS
SMS = FA x SS
SMS = 1.2 x 1.5 = 1.8
SDS = 2/3 x 1.8 = 1.2
Cs ==0.185 EQ'N 12.8-2 ASCE 7-16
Sht # 6 of 7
2024-0564 Solar Survey Pro 917 W McFadden Ave April 18, 2024
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Cs =SDS
R
Ie
SDS
R
Ie
917 W McFadden Ave -
101119790 & 201832007/2/2024
EXISTING BASE SHEAR
V = 0.185 x 45,000 LBS = 8,325 LBS
DETERMINE NEW BASE SHEAR
Determine Seismic Weight of Building with Solar Array:
EXISTING
SEISMIC =45,000 LBS
WEIGHT
NEW SOLAR
ARRAY =3 PSF x 32 PANELS x 5.8' x 3.4' = 1,894 LBS
NEW
SEISMIC =45,000 LBS + 1,894 LBS = 46,894 LBS
WEIGHT
THEREFORE NEW BASE SHEAR:
V = 0.185 x 46,894 = 8,676 LBS EQ'N 12.8-1 ASCE 7-16
OK. PER ASCE 7-16 SECTION 11B.4 ALTERATIONS
EXISTING LATERAL FORCE RESISTING SYSTEM IS EXEMPT
FROM ANALYSIS SINCE NEW SEISMIC FORCE IS
LESS THAN 10% GREATER THAN EXISTING SEISMIC FORCE
Sht # 7 of 7
2024-0564 Solar Survey Pro 917 W McFadden Ave April 18, 2024
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
"Alterations may be made to any structure without requiring the existing structure to
comply with this standard, provided that the alterations comply with the requirements for a
new structure. Alterations that increase the seismic force in any existing structural element
by more than 10% or decrease the design strength of any existing structural element to
resist seismic forces by more than 10% shall not be permitted unless the entire seismic
force-resisting system is determined to comply with this standard for a new structure."
End of Calculations
Email: loydwmartin@gmail.com www.loydwmartin.com
% CHANGE =8,676 LBS - 8,325 LBS x 100 = 4.2 % < 10 % OK8,325 LBS
917 W McFadden Ave -
101119790 & 201832007/2/2024