HomeMy WebLinkAbout800 N Tustin Ave Unit #H - PlanPLUMBING M0.0 M0.1 M3.0 M3.1 ELECTRICAL MECHANICAL MECHANICAL EQUIPMENT SPECIFICATIONS MECHANICAL DETAILS LEGEND & EQUIPMENT SCHEDULES A2.1 FLOOR PLAN A6.1 A4.1 WALL DETAILS ARCHITECTURAL A1.1 G.1 GENERAL NOTES ACCESSIBILITY DETAILS TITLE SHEET VICINITY MAP ABBREVIATIONS PROJECT DATA SHEET INDEX TI T L E S H E E T G.1 MH G.3 G.4 G.2 DETAIL SECTION REFERENCE FIRE EXTINGUISHER CABINET EXTINGUISHER W/ FIRE EXTINGUISHER WALL-MOUNTED FIRE KEYNOTE INDICATOR DELTA NUMBER REVISION CLOUD & X FE FEC ELEVATION REFERENCE SHEET NUMBER ELEVATION VIEW ELEVATION REFERENCE SHEET NUMBER 1 2 3 4 X XXX X XXX SYMBOLS LEGEND ALIGN ROOM NAME ROOM NUMBER101 OFFICE DETAIL REFERENCEXX XXX SECTION REFERENCE SHEET NUMBER SHEET NUMBER SHEET NUMBER XX XXX NEW DOOR EXISTING DOOR ###DOOR NUMBER (REFER TO DOOR SCHEDULE) NO SCALE N TYPE NUMBER WALL MATERIAL TYPE TYPE NUMBER FLOOR MATERIAL TYPE XX XXX Quarry TileQ.T. West With Water Closet Wood Without Waterproof Wainscot Weight Vertical Vestibule Unfinished Unless Otherwise Noted Urinal Tread Towel Bar Top of Curb Telephone Terrazzo Tongue and Groove Thick Top of Concrete Top of Panel Top of Reveal Top of Deep Recess Top of Mullion Top of Wall Top of Pavement Toilet Paper Dispenser Television Top of Wall Typical W. W/ W.C. WD. W/O WP WSCT. WT. VERT. VEST. UNF. U.O.N. UR. TRD. T.B. T.C. TEL. TER. T. & G. THK. T.O.C. T.O.P. T.O.R. T.O.RC. T.O.M. T.O.W. T.P. T.P.D. T.V. T.W. TYP. South Solid Core Seat Cover Dispenser Schedule Soap Dispenser Section Shelf Shower Sheet Similar Sanitary Napkin Disp. Sanitary Napkin Recept. Specification Square Stainless Steel Service Sink Station Standard Steel Storage Structural Suspended Symmetrical S. S.C. S.C.D. SCHED. S.D. SECT. SH. SHR. SHT. SIM. S.N.D. S.N.R. SPEC. SQ. S.ST. S.SK. STA. STD. STL. STOR. STRL. SUSP. SYS. Riser Radius Roof Drain Reference Refrigerator Register Reinforced Required Resilient Room Rough Opening Redwood Rain Water Leader R. RAD. R.D. REF. REFR. RGTR. REINF. REQ. RESIL. RM. R.O. RWD. R.W.L. Pre-cast Plate Plastic Laminate Plaster Plywood Pair Point Paper Towel Dispenser Combination Paper Towel Partition Paper Towel Receptacle Panel Joint PRCST. PL. P.LAM. PLAS. PLYWD. PR. PT. P.T.D P.T.D/R PTN. P.T.R. P.J. Overall Obscure On Center Outside Diameter (Dim.) Office Opening Opposite O.A. OBS. O.C. O.D. OFF. OPNG. OPP. North Not In Contract Number Nominal Not To Scale N. N.I.C. NO. NOM. N.T.S. Maximum Medicine Mechanical Membrane Metal Manufacturer Manhole Minimum Mirror Miscellaneous Masonry Opening Mounted Mullion MAX. M.C. MECH. MEMB. MET. MFR. MH. MIN. MIR. MISC. M.O. MTD. MUL. Laboratory Laminate Lavatory Locker Light LAB. LAM. LAV. LKR. LT. Janitor Joint Kitchen Knock Out Jan. JT. KIT. K.O. Inside Diameter (Dim.) Insulation Interior I.D. INSUL. INT. Hose Bibb Hollow Core Hardwood Hardware Hollow Metal Horizontal Hour Height H.B. H.C. HDWD. HDWE. H.M. HORIZ. HR. HGT. Gauge Galvanized Grab Bar Glass Ground Grade Gypsum GA. GALV. G.B. GL. GND. GR. GYP. Fire Alarm Flat Bar Floor Drain Foundation Fire Extinguisher Fire Extinguisher Cab Fire Hose Cabinet Finish Floor Flashing Fluorescent Face of Concrete Face of Finish Face of Mullion Face of Stud Fireproof Full Size Foot or Feet Footing Furring Future F.A. F.B. F.D. FDN. F.E. F.E.C. F.H.C. FIN. FL. FLASH. FLUOR. F.O.C. F.O.F. F.O.M. F.O.S. FPRF. F.S. FT. FTG. FURR. FUT. East Each Expansion Joint Elevation Electrical Elevator Emergency Enclosure Electrical Panelboard Equal Equipment Electric Water Cooler Existing Exposed Expansion Exterior E. EA. E.J. EL. ELEC. ELEV. EMER. ENCL. E.P. EQ. EQPT. E.W.C. EXST. EXPO. EXP. EXT. Double Department Drinking Fountain Detail Diameter Dimension Dispenser Down Door Opening Door Drawer Downspout Dry Standpipe Drawing DBL. DEPT. D.F. DET. DIA. DIM. DISP. DN. D.O. DR. DWR. DS. D.S.P. DWG Cabinet Catch Basin Cement Ceramic Cast Iron Corner Guard Ceiling Caulking Closet Clear Cased Opening Column Center of Mullion Concrete Connection Construction Continuous Center of Reveal Corridor Countersunk Counter Center CAB. C.B. CEM. CER. C.I. C.G. CLG. CLKG. CLO. CLR. C.O. COL. C.O.M. CONC. CONN. CONSTR. CONT. C.O.R. CORR. CTSK. CNTR. CTR. Board Bituminous Building Block Blocking Beam Bottom of Concrete Bottom of Mullion Bottom of Panel Bottom of Reveal Bottom BD. BITUM. BLDG. BLK. BLKG. BM. B.O.C. B.O.M. B.O.P. B.O.R. BOT. Acoustical Area Drain Adjustable Aggregate Aluminum Approximate Architectural Asbestos Asphalt ACOUS A.D. ADJ. AGGR. AL. APPROX. ARCH. ASB. ASPH. And At Angle ~ # LC & @ (E) Pound or Number Diameter or Round Existing Centerline P 1 C 1 PL 1 X EQUIPMENT TAG TYPE NUMBER MISC. MATERIAL TYPE PROJECT TEAM PROJECT SCOPE: TENANT OCCUPANCY: EXISTING OCCUPANCY: BUILDING CODES: TENANT- LESSEE UNITED MEDICAL IMAGING OF SANTA ANA 800 N. TUSTIN AVE., SUITE M SANTA ANA, CA 92705 CONTACT: NASSER HIEKALI PHONE: (818) 632-7778 EMAIL: NHIEKALI@UMIH.COM GENERAL CONTRACTOR TBD M MEDICAL OFFICE P1.0 P2.0 PLUMBING DETAILS PLUMBING FLOOR PLANS E0.01 GENERAL NOTES, SHEET INDEX AND SYMBOLS LIST DS/MH 23-16 ACCESSIBILITY DETAILS A6.2 RCP DETAILS EXTERIOR ELEVATIONS LANDLORD A6.3 MILLWORK DETAILS DOOR/WINDOW SCHEDULES PROPOSED OCCUPANCY: B BUSINESS GROUP (MEDICAL OFFICE) A7.1 SITE PLAN 18 SHEETS 9 SHEETS 3 SHEETS 11 SHEETS OCCUPANT LOAD: TABLE 1006.2.1 - MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE 100 FEET NO POINT OF TRAVEL DISTANCE EXCEEDS 100 FEET REQUIREMENT BUSINESS AREA - TABLE 1004.5 TOTAL OCCUPANT 9 OCCUPANTS < THAN 49 EXIT REQUIRED : 1 EXIT PROVIDED : 1 USE SF (NET) OCC. LOAD OCCS. 1,294 SF 150 9 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 P L A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 P L A N C H E C K R E S U B M I T T A L P3.0 A2.0 DEMOLITION PLAN TYPE OF PROCEDURES: THERE ARE NO SURGICAL, SEDATED OR ANY OSHPD 3 REQUIREMENTS. M2.0 MECHANICAL 1ST FLOOR PLAN A2.2 REFLECTED CEILING PLAN BUILDING DEPARTMENT: CITY OF SANTA ANA 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA PLUMBING CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA GREEN BUILDING CODE 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA FIRE CODE MECHANICAL SPECIFICATIONS PLUMBING LEGENDS & EQUIPMENT A.P.N. NUMBER:400-202-03 TYPE OF CONSTRUCTION: V-B (EXISTING) NON-SPRINKLERED NO. OF STORIES: ONE STORY SLAB ON GRADE TOTAL SQUARE FOOTAGE: EXISTING FLOOR AREA 1,245 SF PROPOSED ADDITION 49 SF TOTAL FLOOR AREA 1,294 SF UMIH PLUMBING FIXTURE CALCULATIONS: TABLE 422.1 USE OFFICE 1,294 SF 200 7 OCCUPANTSOCC. LOAD TOTAL PLUMBING FIXTURES REQUIRED: PER UPC SECTIION 422.2 EXCEPTION 3 TOTAL OCCUPANT LOAD OF LESS THAN 50 - ONE UNISEX TOILET ROOM REQUIRED TOTAL PLUMBING FIXTURES PROVIDED: ONE UNISEX TOILET ROOM FLOOR AREA 1 UNITED MEDICAL IMAGING HEALTHCARE 800 N. TUSTIN AVENUE SANTA ANA, CA 92705 TENANT IMPROVEMENT FOR: United Medical Imaging Healthcare S & A MANAGEMENT LLC 129 WEST WILSON SUITE 100 COSTA MESA, CALIFORNIA 92627 CONTACT: RYAN CHASE PHONE: (949) 722-7400 EMAIL: RYANLYLECHASE@GMAIL.COM ELECTRICAL ENGINEER PLUMBING ENGINEER ARCHITECT CONSULTANTS SH PARTNERS, INC 7052 EVENINGSONG DRIVE HUNTINGTON BEACH, CA 92648 ARCHITECT: DEBRA L SANDS, AIA PHONE: (714) 553-2849 EMAIL: DEBS@SHPARTNERS.NET CONTACT: MARCO HANAWI PHONE: (714) 390-8600 EMAIL: MARCOH@SHPARTNERS.NET ENERGYLOGICS, INC. 225 E BROADWAY SUITE 101A, GLENDALE CA 91205 ENERGYLOGICS, INC. 225 E BROADWAY SUITE 101A, GLENDALE CA 91205 MECHANICAL ENGINEER ENERGYLOGICS, INC. 225 E BROADWAY SUITE 101A, GLENDALE CA 91205 CONTACT: HENRY ESTRADA PH: (213) 820-3683 EMAIL: HESTRADA@ELOGICSCE.COM CONTACT: HENRY ESTRADA PH: (213) 820-3683 EMAIL: HESTRADA@ELOGICSCE.COM CONTACT: SAURABH PANDYA PH: (562) 541-4729 EMAIL: ZONING:P - PROFESSIONAL EXIT REQ'D EXIT PROVIDED 1 SUITE - H A2.3 FINISH FLOOR PLAN STRUCTURAL 7 SHEETS 1 A6.4 MISCELLANEOUS DETAILS S-1.0 FOUNDATION PLAN S-1.1 ROOF FRAMING PLAN S-2.0 FOUNDATION DETAILS M3.2 MECHANICAL EQUIPMENT SPECIFICATIONS E0.02 TITLE 24 INDOORE0.03 ELECTRICAL SPECIFICATIONS E2.01 SINGLE LINE DIAGRAM E3.01 PANEL SCHEDULES E6.01 LIGHTING PLAN E5.01 POWER PLAN E7.01 EGRESS PHOTOMETRIC CALCULATIONS M4.0 T-24 COMPLIANCE FORMS M4.1 T-24 COMPLIANCE FORMS S-3.0 ROOF FRAMING DETAILS CONTACT: JEFF BEDDOW PHONE: (949) 722-7400 EMAIL: JEFF.SAPROPERTIES@GMAIL.COM SPANDYA@ELOGICSCE.COM SA N T A A N A FW Y CO S T A M E S A F W Y 17TH STREET E. FRUIT STREET 4TH STREET N. T U S T I N A V E . CA B R I L L O P A R K D R . E. 1ST STREET W. 1ST STREET 5 PROJECT LOCATION 55 A1.2 LINE OF SIGHT A3.1 ROOF PLAN A5.1 INTERIOR ELEVATIONS S-4.0 DETAILS TITLE 24 OUTDOORE0.04 E5.02 MECHANICAL POWER PLAN E5.03 ROOF POWER PLAN S-0 GENERAL NOTES S-0.1 GENERAL NOTES INTERIOR TI TO CREATE NEW IMAGING AND LOBBY ROOMS FOR A NEW PROPOSED MEDICAL OFFICE, NEW ROOF EQUIPMENT W/ SCREENING, NEW EXTERIOR NON-BEARING WALLS, NEW CANVAS CANOPY OVER TWO SEPARATE DOORS, AND A 49 SQ. FT. ADDITION PLAN CHECK NO: 101120961 - BUILDING DEPARTMENT 20184073 - ELECTRICAL 30147809 - PLUMBING 40139552 - MECHANICAL 1 1 1 1 1 1 1 1 1 1 M4.2 T-24 COMPLIANCE FORMS 1 1 1 1 1 E4.01 ELECTRICAL SITE PLAN 1 1 1 1 1 - DELETED 1 1 1 1 1 di g i t a l s t a m p & s i g n a t u r e , d a t e 1 2 - 0 4 - 2 0 2 4 Bldg #101120961 Elect #20184073 Plumb #30147809 Mech #40139552 APPROVALS: PLNG - F. Arias BLDG - CSG POLICE - B. Martin PUBLIC WORKS - B. Sarlak ELECT/PLUMB/MECH - CSG 800 N Tustin Ave Unit #H1/23/2025 T U S T I N A V E N U E CL FRUIT STREETCL 18 7 9 1 14 8 2 H FG E D C B A I J K L M 8 14 8 1 2 50'-0" 30 ' - 0 " T T SCALE: SITE PLAN 11/16" = 1'-0" DS/MH 24-06 SI T E P L A N A1.1 MH 5 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L -- 1.EXISTING PARKING STALL TO REMAIN 2.EXISTING ACCESSIBLE PARKING STALL AND SIGNAGE TO REMAIN. 3.EXISTING VAN ACCESSIBLE PARKING STALL AND SIGNAGE TO REMAIN. 4.EXISTING TRASH ENCLOSURE. 5.EXISTING RAMP TO REMAIN. 6.EXISTING LANDSCAPE TO REMAIN. 7.EXISTING MONUMENT SIGN TO REMAIN. 8.EXISTING PARKING LOT LIGHTING TO REMAIN. 9.EXISTING DRIVEWAY TO REMAIN. 10.EXISTING COURTYARD TO REMAIN. 11.PROPOSED NEW ELECTRICAL TRANSFORMER WITH NEW CONCRETE PAD AND BOLLARDS. INSTALL PER SCE STANDARD. 12.PROPOSED ADDITIONAL 2'-6" X 19'-8" = 49 SQUARE FEET 13.EXISTING PUBLIC SIDEWALK TO REMAIN. 14. EXISTING LANDSCAPE AND IRRIGATION TO REMAIN. 15. NEW 6" CONCRETE CURB WITH LANDSCAPE AND IRRIGATION. KEYNOTES 6 6 6 6 7 8 9 7 8 9 4 1 2 2 3 (E) PATH OF TRAVEL, MINIMUM 48" WIDTH (MAX. 5% SLOPE IN DIRECTION OF TRAVEL AND MAX. 2% CROSS SLOPE) NO ABRUPT CHANGES IN ELEVATION ALONG THE PATH OF TRAVEL SHOWN. LEGEND X INDICATES (E) PARKING COUNT (E) PROPERTY LINE SITE DATA PARKING SUMMARY 16,160 SFEXISTING TOTAL BUILDING SQUARE FOOTAGE: EXISTING OCCUPANCY SUITE H = RETAIL - 5 SPACES/1000 PROPOSED OCCUPANCY SUITE H = MEDICAL OFFICE - 5 SPACES/1000 NO NEW PARKING REQUIRED. 1,245 SFEXISTING SUITE - H SQUARE FOOTAGE: 1,245 SF NOT A PART NOT A PART 10 1 EXISTING PARKING COUNT 1 A4.1 2 A4.1 3 A4.1 PROPOSED PARKING COUNT: 49 SF 11 49 SFPROPOSED ADDITION: 16,209 SFTOTAL: 49 SFPROPOSED ADDITION: 1,294 SFTOTAL: 12 13 13 13 8 8 6 EXISTING OCCUPANCY:M PROPOSED OCCUPANCY:B BUSINESS GROUP (MEDICAL OFFICE) A.P.N. NUMBER: 400-202-03 TYPE OF CONSTRUCTION:V-B (EXISTING) NON-SPRINKLERED NO. OF STORIES:ONE STORY SLAB ON GRADE ZONING:P - PROFESSIONAL 1 1 1 LOST 2 PARKING STALLS FOR NEW SCE TRANSFORMER PAD 1 1 1 14 (E) ELECTRICAL TRANSFORMER TO REMAIN 15 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 RTU FRUIT STREET suite - H 6' - 0 " 17 ' - 0 " ±38'-2 1/2" 3' - 6 " 6'-4 1/2"7'-0" TUSTIN AVENUE RTU suite - H 6' - 0 " 4' - 0 " 17 ' - 0 " ±144'-10" 24'-8"3'-6" 4' - 1 " T U S T I N A V E N U E CL FRUIT STREETCL 18 7 9 1 14 8 2 H FG E D C B A I J K L M 8 14 8 1 2 50'-0" 30 ' - 0 " 3'-6" T T SCALE: LINE OF SIGHT FROM TUSTIN AVENUE (T-T)11/16" = 1'-0" DS/MH 24-06 LI N E O F S I G H T A1.2 MH SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L SCALE: LINE OF SIGHT FROM FRUIT STREET (F-F)21/16" = 1'-0" (E) PROPERTY LINE (E) PROPERTY LINE T - T - F - F - CONTINUOUS EXISTING PARAPET (E) PROPERTY LINE(E) PROPERTY LINE CONTINUOUS EXISTING PARAPET KEY PLAN (E) BUILDING (E) BUILDING (E) COVERED TRASH ENCLOSURE (E) PARKING LOT(E) DRIVEWAY (E) DRIVEWAY (E) DRIVEWAY EXISTING ROOF TOP UNITS, TYP. 1 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 T U S T I N A V E N U E CL FRUIT STREETCL T 20 7 9 1 14 8 2 H FG E D C B A I J K L M 8 14 8 1 2 50'-0" 30 ' - 0 " proposednewelectricaltransformer T U S T I N A V E N U E CL FRUIT STREETCL T 20 7 9 1 14 8 2 H FG E D C B A I J K L M 8 14 8 1 2 50'-0" 30 ' - 0 " proposednewelectricaltransformer 3 B A 2 514 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H SCALE: DEMOLITION PLAN 11/4" = 1'-0" DS/MH 24-06 DE M O L I T I O N P L A N A2.0 MH KEY PLAN 1 A2.1 -- 1.EXISTING CARPET TO BE REMOVED AND PREPPED FOR NEW FINISH FLOOR. 2.EXISTING CABINET BASE/SINK AND UPPER CABINET TO REMOVED. CAP AND SECURE PLUMBING LINES TO BE FLUSH WITH WALL. 3.EXISTING PLUMBING FIXTURES TO BE REMOVED, CAP AND SECURE PLUMBING LINES TO BE FLUSH WITH WALL/FLOOR. 4.EXISTING ELECTRICAL OUTLET/DATA TO BE REMOVED. 5.EXISTING DOOR AND FRAME TO BE REMOVED, SALVAGE PER OWNER'S DIRECTION. 6.EXISTING WINDOW AND FRAME TO BE REMOVED. 7.EXISTING NON BEARING WALL TO BE REMOVED. 8.EXISTING PORTION OF EXTERIOR STUCCO WALL TO BE REMOVED. 9.EXISTING 2'X4' LIGHT FIXTURES TO BE REMOVED. 10.EXISTING 2'X4' CEILING TILE AND CEILING GRIDS TO BE REMOVED. 11.EXISTING DIFFUSER AND DUCTING TO BE REMOVED. 12.EXISTING STOREFRONT TO REMAIN. 13.EXISTING LVT TO BE REMOVED AND PREPPED FOR NEW FINISH FLOOR. 14.EXISTING ELECTRICAL ROOM TO REMAIN. 15.EXISTING ELECTRICAL PANEL TO BE REMOVED. SEE ELECTRICAL DRAWINGS. NOTES EXISTING DEMISING WALL TO REMAIN EXISTING WALL TO BE DEMOLISHED LEGEND DEMOLITION NOTES EXISTING DOOR TO REMAIN EXISTING INTERIOR DOOR AND FRAME TO BE REMOVED 1.DRAWINGS OF EXISTING CONDITIONS HAVE BEEN COMPILED FROM EXISTING DATA SUPPLIED BY THE OWNER TO THE ARCHITECT. THE ARCHITECT MAKES NO WARRANTY, EITHER EXPRESS OR IMPLIED, FOR THE ACCURACY OF THE COMPLETENESS OF THE EXISTING INFORMATION RECORDED. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS THAT MIGHT ARISE IN THE COURSE OF THE DEMOLITION WORK. 2.VERIFY LOCATIONS OF EXISTING MECHANICAL, PLUMBING AND ELECTRICAL UTILITIES. LOCATE AND PROTECT UTILITIES TO REMAIN. DISCONNECT, REMOVE BACK TO NEAREST JUNCTION BOX OR PANEL, AS REQUIRED, AND CAP DESIGNATED UTILITIES WITHIN THE DEMOLITION AREA. REFER TO THE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFO. 3.EXISTING ELECTRICAL AND TELEPHONE OUTLETS LOCATED ON DEMOLISHED WALLS ARE TO BE REMOVED INCLUDING CONDUIT AND WIRING BACK TO JUNCTION BOX. LOCATIONS ARE TO BE PATCHED AND REPAIRED TO BE FLUSH WITH ADJACENT WALL SURFACE. 4.WHERE PLUMBING FIXTURES ARE BEING REMOVED OR WHERE EXPOSED PLUMBING PIPES OCCUR, CAP LINES BEHIND FINISHED SURFACES. PATCH AND REPAIR AS REQUIRED. 5.ALL EXISTING CONSTRUCTION WHERE INDICATED INCLUDING ELECTRICAL, TELEPHONE, PLUMBING AND MECHANICAL DEVICES NOT OTHERWISE INDICATED ON THESE CONSTRUCTION DRAWINGS SHALL BE REMOVED IN A CAREFUL MANNER SO AS NOT TO DAMAGE ADJOINING CONSTRUCTION. 6.IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN HEREON OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE OF REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE EXECUTION OF HIS WORK. 7.ALL EXISTING BUILDING UTILITIES SHALL REMAIN IN OPERATION DURING CONSTRUCTION. PROVIDE REROUTING OF UTILITIES SERVING ADJACENT AREAS THAT ARE TO MAINTAIN UNINTERRUPTED SERVICE. ANY TEMPORARY SUSPENSION OF SERVICE SHALL BE COORDINATED AND APPROVED BY THE FACILITY MANAGER, NOT LESS THAN 24-HOURS IN ADVANCE. 8.THE CONTRACTOR WILL VERIFY AND CONFORM TO ALL REQUIREMENTS OF ALL UTILITY COMPANIES UNLESS OTHERWISE NOTED IN THE PLANS. 9.THE DEMOLITION PLAN KEYNOTES ARE DIAGRAMMATIC AND GENERAL IN NATURE. THE INTENT IS TO ILLUSTRATE THE COMPLETE DEMOLITION OF THE SPACES INDICATED UNLESS NOTED OTHERWISE. FIELD VERIFICATION OF EXISTING CONDITIONS AND SPECIFIC QUANTITIES IS THE RESPONSIBILITY OF THE CONTRACTOR. 10.REMOVAL AND DISPOSAL OF DEMOLITION DEBRIS IS THE RESPONSIBILITY OF THE CONTRACTOR. VERIFY THE HAULING ROUTE THROUGH THE BUILDING, THE DEMOLITION STAGING AREA, AND THE LOCATION OF THE DUMPSTER WITH THE OWNER PRIOR TO THE START OF DEMOLITION. DISPOSAL OF RUBBISH SHALL BE DONE IN A LEGAL MANNER. 11.THE OWNER RESERVES THE RIGHT TO SALVAGE ANY DEMOLISHED ITEM. VERIFY ITEMS TO BE SALVAGED WITH THE OWNER PRIOR TO THE START OF DEMOLITION. REMOVE, PROTECT, CLEAN, REPAIR FOR REUSE AND TURN OVER SUCH ITEMS AS DIRECTED BY THE OWNER. 12.IN ORDER TO INSTALL SOME OF THE NEW WORK (INCLUDING, BUT NOT LIMITED TO MECHANICAL, PLUMBING OR ELECTRICAL) IT WILL BE NECESSARY FOR THE CONTRACTOR AND HIS SUBCONTRACTORS TO REMOVE AND REPLACE (OR REFINISH) EXISTING WALLS, FLOORS, OR CEILING IN THE AREAS OF THE BUILDING NOT SHOWN ON THESE PLANS. THE CONTRACTOR SHALL INCLUDE ALL RELATED COSTS IN HIS BASE BID, WHETHER SHOWN ON THESE PLANS OR NOT. 13.PROTECT ADJACENT SPACES NOT SCHEDULED FOR DEMOLITION. PATCH AND REPAIR DAMAGED FINISHES, ITEMS AND FIXTURES TO REMAIN AND/OR REPLACE IN KIND TO MATCH EXISTING FROM DAMAGE DURING THE PROGRESS OF THE WORK. PROVIDE TEMPORARY SAFETY BARRIERS REQUIRED BY CODE AND AS INDICATED TO INSURE PUBLIC SAFETY AND TO ALLOW BUILDING OCCUPANCY. CONTRACTOR TO SUBMIT FOR APPROVAL, BARRIER LOCATIONS, AND METHOD OF CONSTRUCTION TO THE ARCHITECT PRIOR TO INSTALLATION. 14.NO STRUCTURAL ELEMENTS ARE INCLUDED IN THIS SCOPE OF WORK. 15.PROVIDE DUST BARRIERS AROUND OPENINGS, TO AND FROM THE CONSTRUCTION AREA. PROVIDE ALL MEANS NECESSARY TO INHIBIT DUST FROM ENTERING OTHER PORTIONS OF THE FACILITY. SUBMIT BARRIER LOCATIONS TO THE ARCHITECT FOR APPROVAL, PRIOR TO INSTALLATION. 16.PROVIDE ADEQUATE SHORING, BRACING, BARRICADES AND PROTECTIVE MEASURES AS REQUIRED TO SAFELY EXECUTE THE WORK IN THE CONSTRUCTION AREA AND THE AREAS ADJACENT TO THE CONSTRUCTION AREA. CEASE OPERATIONS AND NOTIFY THE ARCHITECT IMMEDIATELY IF THE STRUCTURE APPEARS TO BE ENDANGERED. DO NOT RESUME OPERATIONS UNTIL CORRECTIVE MEASURES HAVE BEEN TAKEN. 17.CONTRACTOR SHALL MAINTAIN REQUIRED MEANS OF EGRESS AND ENSURE THAT EXIT ROUTES ARE SIGNED, LIGHTED AND PROTECTED IN ACCORDANCE WITH CODE REQUIREMENTS. RELOCATE EXISTING AND/OR PROVIDE SMOKE PROTECTORS AND LIFE SAFETY EQUIPMENT FOR ADEQUATE COVERAGE. 18.PROVIDE TEMPORARY NON-COMBUSTIBLE CONSTRUCTION BARRIERS WHERE REQUIRED BY CODE AND THE GOVERNING FIRE AUTHORITY. MINIMUM REQUIREMENTS: A.FULL HEIGHT WALL FROM FLOOR TO CEILING. B.STUDS AT 24" O.C., WITH 5/8" TYPE 'X' GYPSUM BOARD. C.NON-COMBUSTIBLE ACCESS DOOR WITH (3) HINGES AND SPRING CLOSER. 19.SURVEY EXISTING FLOORS AND CLEARLY MARK ON FLOOR SURFACE THE LOCATIONS OF ALL BEAMS AND JOISTS. MARK ALL CORE DRILL PENETRATIONS AND RECEIVE STRUCTURAL ENGINEER'S APPROVAL PRIOR TO DRILLING CONCRETE. 20.CUT RIGID MATERIALS USING MASONRY SAW OR CORE DRILL. PNEUMATIC TOOLS ARE NOT ALLOWED WITHOUT PRIOR APPROVAL. 21.ALL CORE DRILLING OR OTHER NOISY WORK SHALL BE SCHEDULED 48-HOURS IN ADVANCE WITH THE OWNER. 22.APPLY CEMENT BASE FLOOR PATCH AS REQUIRED TO FILL DINGS, NAIL HOLES, CHIPS AND CRACKS. 23.AT FLOOR AREAS SCHEDULED TO RECEIVE NEW FLOOR COVERING, REMOVE EXISTING FLOOR COVERING AND PREPARE SUBSTRATE FOR NEW FLOOR COVERING PER SPECIFICATIONS AND MANUFACTURER'S REQUIREMENTS. 24.AT ABANDONED PENETRATIONS OF FIRE RATED WALLS, CEILING OR FLOOR CONSTRUCTION, COMPLETELY SEAL VOIDS WITH FIRE RATED MATERIAL TO FULL THICKNESS OF THE PENETRATED ELEMENT. ALL PATCHING OF EXISTING WORK TO REMAIN SHALL MATCH FINISH PER SCHEDULE OR WHERE UNSCHEDULED TO MATCH EXISTING FINISHES TO REMAIN, AND SHALL MEET OR EXCEED FIRE RATING INDICATED ON FLOOR PLAN AND AS REQUIRED BY THE FIRE/LIFE SAFETY INSPECTOR. 25.CONTRACTOR IS RESPONSIBLE FOR BUILDING SECURITY DURING DEMOLITION PHASE. PROTECT ALL OPENINGS FROM WEATHER CONDITIONS AND SECURE THEM TO PREVENT VANDALISM. 26.DO NOT PERFORM ANY WORK THAT WILL VOID WARRANTIES OF EXISTING WEATHER EXPOSED OR MOISTURE RESISTANT ELEMENTS WITHOUT PRIOR APPROVAL FROM THE OWNER. 27.ARCHITECT ASSUMES NO RESPONSIBILITY RELATING TO ANY TOXIC MATERIALS, INCLUDING ASBESTOS, AND ASSUMES NO RESPONSIBILITY TO ITS EXISTENCE OR REMOVAL. THE OWNER WILL TAKE ACTION FOR DIRECTLY CONTRACTING WITH A CONSULTANT OR SPECIALIST, LICENSED BY THE STATE, FOR SUCH SERVICES SHOULD THOSE SERVICES BE REQUIRED ON THE PROJECT. 1 2 3 13 4 5 6 6 6 7 8 8 9 10 11 1212 15 14 1 4 5 7 9 10 11 1 4 5 7 9 10 11 1 4 5 7 9 10 11 1 4 5 7 9 10 11 800 N Tustin Ave Unit #H1/23/2025 12'-8 1/2" 54'-5" 23 ' - 5 " 16 ' - 5 " 19'-10 3/4"7'-11 1/4"23'-8 1/4" 12 ' - 1 " 15'-8"5'-6"6'-8" 6' - 0 " 10 ' - 7 " 7'-6" 7' - 6 " 9'-1" 7' - 0 " 7'-0" 7' - 9 " 6' - 6 " 15 ' - 0 " 7' - 5 " 2'-11" 3 B A 2 514 3' - 0 " 1'-6" 5' - 1 " 4' - 0 " 1'-8" 2' - 6 " 3' - 6 " 3' - 0 " 5'-6" 1' - 9 " 6" +18" +18" +18"+18" +18" +60 +18" +18" +18" +18" +18" +18" +18" +18" +18" +18" +18" 1'-6 3/4" 14 ' - 2 1 / 2 " RF SHIELD MAGNET ROOM SIDE MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G NE C MAGNET ROOM SIDE RF SHIELD MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G 3' - 1 0 " 4' - 0 " 1' - 0 " 4' - 0 " 7' - 0 " 1' - 0 " FEC 5'-5"5'-3" SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L SCALE: FLOOR PLAN 11/4" = 1'-0" DS/MH 24-06 FL O O R P L A N A2.1 MH 1 KEY PLAN 1 A2.1 --NOTES NON-RATED PARTITION WALL, U.N.O. EXISTING DEMISING WALL TO REMAIN EXISTING DOOR TO REMAIN NEW WALLS TO BE INSULATED WITH R-11 ECOTOUCH PINK UNFACED FIBERGLASS SOUND ATTENUATION INSULATION BATT BY OWENS CORNING OR EQUAL. EXISTING WALL TO BE DEMOLISHED RF SHIELDED WALL, PER MRI MANUFACTURER SPECIFICATION. INDICATES NEW INTERIOR WINDOW. SEE SHEET A7.1 FOR WINDOW SCHEDULE# XX INDICATES NEW DOOR. SEE SHEET A7.1 FOR DOOR SCHEDULE. LEGEND 1.RECEPTION DESK, SEE DETAILS 4/A6.3 2.NOT USED 3.PROVIDE ALUMINUM SEMI-RECESSED FIRE EXTINGUISHER CABINET WITH LOCK (JL INDUSTRIES, INC.: ACADEMY SERIES #1027G10); FIRE EXTINGUISHER: PROVIDE (1) 2A-10BC, SEE DETAIL 15/A6.1 4.CHANGING ROOM LOCKER CABINET 12/A6.3 5.CHANGING ROOM BENCH, SEE DETAIL 6/A6.3 6.PROVIDE 2% MAX. SLOPE TO ACCOMMODATE THE THICKNESS OF MRI FLOOR. SEE LATEST MRI DOCUMENTS. 7.NEW EXTERIOR 2X WALL WITH EXTERIOR STUCCO OVER WATER PROOFING MEMBRANE AND METAL LATH, PAINTED TO MATCH EXTERIOR BUILDING COLOR. 8.64" X 34" (PLUS 3/8" FOR ROUGH OPENING 5-SIDES) RECESSED LUMINOUS VIRTUAL WINDOW BY SKY FACTORY TO BE INSTALLED PER MANUFACTURER, SEE ELECTRICAL FOR POWER REQUIREMENT. 9.NOT USED 10.NOT USED 11.ELECTRICAL PANEL, SEE ELECTRICAL DRAWINGS GENERAL NOTES 1.GENERAL CONTRACTOR TO COORDINATE WITH MRI AND CT SCAN MANUFACTURERS LATEST DOCUMENTS FOR ALL OTHER REQUIREMENTS THAT ARE NOT SHOWN IN ARCHITECTURAL PLANS. 2. GENERAL CONTRACTOR SHALL COORDINATE ALL THE RF SHIELDING INSTALLATION WITH RF SUB-CONTRACTOR FEC FIRE EXTINGUISHER, FINAL LOCATION TO BE DETERMINED BY FIRE INSPECTOR 1 103 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGINGROOM 103 OPERATORS104 MRI 105 EQUIPMENT 108 STORAGE 108 102 101 107 106 104 105 100 E 102a 104a B A 100 ELECT. RM. 1 3 4 5 6 7 8 104a 9 1 A5.1 4 A6.3 5 G.4 4 G.4 11 1 1 1 1 di g i t a l s t a m p & s i g n a t u r e , d a t e 1 2 - 0 4 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 T U S T I N A V E N U E CL FRUIT STREETCL 18 7 9 1 14 8 2 H FG E D C B A I J K L M 8 14 8 1 2 50'-0" 30 ' - 0 " T T 3 B A 2 514 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L SCALE: REFLECTED CEILING PLAN 11/4" = 1'-0" DS/MH 24-06 RE F L E C T E D C E I L I N G P L A N A2.2 MH 1 KEY PLAN 1 A2.1 --NOTESGENERAL NOTES 1.TYPICAL CEILING TO BE TYPE A @ 9'-0" A.F.F. U.N.O. CONTRACTOR TO FIELD VERIFY ADEQUATE CLEARANCE IS MAINTAINED ABOVE PLENUM. NOTIFY ARCHITECT IMMEDIATELY FOR CLARIFICATION OF DISCREPANCIES OR EXISTING CONFLICTS PRIOR TO PROCEEDING WITH WORK IN QUESTION. NEW STRUCTURAL ELEMENTS OR EQUIPMENT (HVAC UNITS, DUCTWORKS, PLUMBING, ETC.) SHALL BE LOCATED AS TO NOT INTERFERE WITH OTHER PORTION OF NEW CONSTRUCTION AS SHOWN. 2.LIGHT FIXTURES, HVAC DEVICES AND OTHER CEILING-MOUNTED ELEMENT LOCATIONS ON ARCHITECTURAL REFLECTED CEILING PLANS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON MEP DRAWINGS. 3.NO AIR DIFFUSER SHALL STRADDLE OVER PARTITIONS. PROVIDE NEW BLANK-OFF PLATS AT INTERSECTIONS WITH PARTITIONS AND WHERE NO AIR DEVICE OCCURS, FINISH TO MATCH SLOT DIFFUSER SPECIFICATION. 4.REFER TO ENGINEER'S DRAWINGS FOR FIRE ALARMS, ADA VISUAL STROBES, SMOKE DETECTORS, AND EXIT SIGN LOCATIONS. COMPLETE LIFE SAFETY SYSTEMS INSTALLATION AND TAS REQUIREMENTS TO BE COORDINATED BY THE GENERAL CONTRACTOR. COORDINATE CEILING DEVICE LOCATIONS WITH ARCHITECT FOR ALL GYP. BD., PREMIUM, AND UPGRADED CEILING SPACES. 5.REFER TO MECHANICAL PLAN FOR SUPPLY REGISTERS AND RETURN AIR GRILLE LOCATIONS. 6.ALL PRIVATE OFFICES AND CONFERENCE ROOMS SHALL BE INDIVIDUALLY SWITCHED, UNLESS NOTED OTHERWISE. 7.REFLECTED CEILING PLANS ARE FOR LIGHTING LOCATION AND ARCHITECTURAL NOTES ONLY. REFER TO ENGINEER'S ELECTRICAL LIGHTING PLAN FOR SWITCHING, CIRCUITING, AND SPECIFICATIONS. 8. ALL LAMPS TO BE OF CONSISTENT COLOR AND SHALL MATCH BUILDING STANDARD, UNLESS NOTED OTHERWISE. 9.CENTER ALL CEILING-MOUNTED DEVICES IN UPGRADED CEILING WITH LIGHT FIXTURES. 10.CENTER ALL DOWNLIGHTS, WALL WASHERS, AND OTHER CEILING DEVICES IN CEILING TILE, UNLESS OTHERWISE NOTED OR DIMENSIONED ON PLAN. 11.ALL UNDER-AND ABOVE-CABINET LIGHTING TO BE FURNISHED AND INSTALLED BY THE CONTRACTOR, WITH LAMPS MATCHING ALL OTHERS. CONDUIT TO BE COMPLETELY CONCEALED FROM VIEW. 12.NEW LIGHT SWITCHES SHALL BE GANGED IF MORE THAN ONE IS NOTED. 13.GENERAL CONTRACTOR SHALL PROVIDE SUBMITTALS AND SHOP DRAWINGS TO ARCHITECT FOR WRITTEN APPROVAL ON ALL EQUIPMENT, FIXTURES, LIGHTING DEVICES, AND SPECIALTY ITEMS PROVIDED BY THE GENERAL CONTRACTOR PRIOR TO ORDERING. 14.ALL ROOM WITH MULTIPLE FIXTURE TYPES ARE TO BE SWITCHED WITH SEPARATE LIGHT SWITCHES PER FIXTURE TYPE. 15.COORDINATE WITH PROPERTY MANAGER TO REPAIR LEAKS AT AND ABOVE CEILING. 16.ACCESS PANELS IN GYP. BD. CEILINGS ARE TO BE FLOATABLE ACCESS PANELS. WIND-LOCK STEALTH ACCESS PANEL OR EQUAL. LEGEND SUPPLY DIFFUSER, SEE MECHANICAL DRAWINGS NOTE: NOTE: CEILING-MOUNTED EXIT SIGN W/ BATTERY BACKUP, SHADED QUADRANT INDICATES FACE OF LETTERING, SIGN TO INCLUDE DIRECTIONAL ARROW AS INDICATED. WALL-MOUNTED EXIT SIGN W/ BATTERY BACKUP, SHADED QUADRANT INDICATES FACE OF LETTERING, SIGN TO INCLUDE DIRECTIONAL ARROW AS INDICATED. EXIT SIGNS SHALL BE SELF-LUMINOUS TYPE OR ELECTRICALLY ILLUMINATED & ENERGIZED FROM SEPARATE CIRCUITS, ONE OF WHICH SHALL BE FROM STORAGE BATTERIES OR AN ON-SITE GENERATOR. ADDITIONAL DIRECTIONAL EXIT SIGNS MAY BE REQUIRED PRIOR TO FINAL INSPECTION AND SUBJECT TO BUILDING INSPECTOR. 2'x2' LED LIGHT FIXTURE. SEE ELECTRICAL DRAWINGS 6" DIA. LED DOWNLIGHT FIXTURE. SEE ELECTRICAL DRAWINGS RETURN DIFFUSER, SEE MECHANICAL DRAWINGS EXHAUST DIFFUSER, SEE MECHANICAL DRAWINGS 1.LIGHTED GRAPHIC CEILING TO BE PROVIDED BY OWNER. GENERAL CONTRACTOR TO COORDINATE THE INSTALLATION 2.GYPSUM BOARD CEILING. PREPARE SURFACE TO RECEIVE PAINT 3.LIGHT FIXTURE TO BE CENTERED IN THIS ROOM 4.MEDMASTER DOWNLIGHT, KENALL MODEL: MRIDL6 (TOTAL OF 13) 5.MEDMASTER DOWNLIGHT, KENALL MODEL: MRIDL6 TO BE CONTROLLED SEPARATELY (TOTAL OF 2), ELECTRICAL DRAWINGS 6.LIGHT FIXTURE TO BE CENTERED ON SOFFIT 7.EXHAUST VENT ABOVE CEILING 8.PROVIDE POWER AND DATA ABOVE CEILING, FOR CEILING MOUNTED TV 9.OPEN TO ABOVE 10.EXISTING TO REMAIN 11.PROPOSED ELECTRICAL TRANSFORMER ABOVE CEILING, SEE ELECTRICAL DRAWINGS AND STRUCTURAL DRAWINGS DETAILS 21 AND 22 ON S-3.0 5/8" TYPE "X" GYPSUM BOARD CEILING OR SOFFIT - USE RATED MATERIAL & CONSTRUCTION WHERE REQUIRED. 9'-0" CEILING HEIGHT, TYPICAL U.N.O. HEAVY DUTY SUSPENDED T-BAR CEILING GRID PRELUDE XL WITH 2'X2' LAY-IN ACOUSTICAL ARMSTRONG CEILING PANELS - CALLA HEALTH ZONE AIRASSURE. SQUARE - SMOOTH FINISH. STRATALUME CONNECTS MRI UNDERCABINET LIGHT FIXTURE ABOVE THE PANORAMIC LENSES KENALL MODEL: MRIAUC, SEE ELECTRICAL DRAWINGS 1 1 2 2 2 3 4 TYP. 5 6 5 7 8 9 10 7 A6.2 16 A6.2 16 A6.2 2 A6.2 TYP. 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGING ROOM 103 OPERATORS 104 MRI 105 EQUIPMENT 108 STORAGE 100 ELECT. RM. 11 1 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 T U S T I N A V E N U E CL FRUIT STREETCL T 20 7 9 1 14 8 2 H FG E D C B A I J K L M 8 14 8 1 2 50'-0" 30 ' - 0 " proposednewelectricaltransformer 3 B A 2 514 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E SA N T A A N A C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H SCALE: FINISH PLAN 11/4" = 1'-0" DS/MH 24-06 FI N I S H P L A N A2.3 MH KEY PLAN 1 A2.1 MFR: ITEM: WALL FINISHES COLOR/NO: FINISH: P 1 FINISH LEGEND PAINT - LOBBY/RECEPTION/HALLWAY/SOFFIT BENJAMIN MOORE GRACIEN GREEN/507 EGGSHELL MFR: ITEM: COLOR/NO: SIZE: GROUT: WALL TILE -- -- -- CUSTOM BUILDER -- FLOOR FINISHES LVT 1 MFR: ITEM:LVT (LUXURY VINYL TILE) MISCELLANEOUS FINISHES Q 1 MFR: ITEM: COLOR/NO: MFR: ITEM: COLOR/NO: QUARTZ - MARBLE INSPIRED VADARA CALACATTA DORADAV727 EGGER COLOR/NO: SIZE: GROUT: VALLEY OAK SMOKE/EPL015 8" X 51" - FT 1 MFR: ITEM:PORCELAIN FLOOR TILE DAL-TILE COLOR/NO: SIZE: GROUT: ASH/AV13 9" X 36" CUSTOM BUILDER #172 URBAN PUTTY P 2 PL 1 BASE FINISHES MFR: ITEM:RUBBER BASE BURKE COLOR/NO: SIZE: GROUT: GRAY BEIGE/#209 4.5" HEIGHT - WT 1 MFR: ITEM: COLOR/NO: FINISH: PAINT - CHANGING ROOM BENJAMIN MOORE ABINGDON PUTTY/HC-99 EGGSHELL P 3 MFR: ITEM: COLOR/NO: FINISH: PAINT - XRAY BENJAMIN MOORE DUNE GRASS/492 EGGSHELL P 4 MFR: ITEM: COLOR/NO: FINISH: PAINT - ULTRASOUND BENJAMIN MOORE PALADIN BLUE/HC-144 EGGSHELL P 5 MFR: ITEM: COLOR/NO: FINISH: PAINT - MRI BENJAMIN MOORE SAGE TINT/458 EGGSHELL RB 1 MFR: ITEM: COLOR/NO: PLASTIC LAMINATE - COUNTER TOP WILSONART CALACATTA ORO/4981 PL 2 PLASTIC LAMINATE - CABINET FORMICA GRAY P 6 MFR: ITEM: COLOR/NO: FINISH: PAINT - RESTROOM/OFFICE/STORAGE BENJAMIN MOORE HONEYMOON/AF-345 EGGSHELL P 7 MFR: ITEM: COLOR/NO: FINISH: PAINT - CT ROOM BENJAMIN MOORE BRITTANY BLUE/1633 EGGSHELL 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGING ROOM 103 OPERATORS 104 MRI 105 EQUIPMENT 108 STORAGE 100 ELECT. RM. LVT 1 P 7 RB 1LVT 1 P 7 RB 1LVT 1 RB 1 P 5 LVT 1 RB 1 P 2 P 6 FT 1 WT 1 LVT 1 RB 1 P 1 LVT 1 RB 1 P 6 CON 1 MFR: ITEM:CONCRETE FLOOR - SEALED - CON 1 EXISTING TO REMAIN 800 N Tustin Ave Unit #H1/23/2025 T U S T I N A V E N U E CL FRUIT STREETCL 18 7 9 1 14 8 2 H FG E D C B A I J K L M 8 14 8 1 2 50'-0" 30 ' - 0 " T T E - HVAC (E ) G L B 5- 1 / 2 " X 1 8 " HASKRIS OPC15 CHILLER 1,200 LBS. 8'-0" 16 ' - 0 " PRELIMINARY ROOF PLAN (E) 22" TJI AT 48" O.C. 15'- 0 " 4'-0 " 3 B A 2 514 7 1/2" 24'-8"3'-6" 22'-4 1/2" 320 lb. 140 lb. 120 lb. 140 lb. 5' - 1 1 " 7' - 2 " 6' - 4 1 / 2 " SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L SCALE: ROOF PLAN 11/4" = 1'-0" DS/MH 24-06 RO O F P L A N A3.1 MH KEY PLAN 1 A2.1 --NOTES 1.EXISTING ROOFTOP UNIT TO BE REMOVED PATCH AND REPAIR TO MATCH EXISTING ROOF. 2.EXISTING ROOF HATCH TO REMAIN. 3.HIDDEN LINE INDICATES WALL LINE BELOW. 4.EXISTING TOP OF PARAPET. 5.EXISTING OPEN TO BELOW (COURTYARD) 6.PROPOSED NEW CANVAS CANOPY AT THE ENTRY, "SUNBRELLA" FABRIC COLOR TO MATCH WITH EXISTING STEEL EYEBROW. 7.MECHANICAL ROOF TOP UNITS OVER 8'-0" X 16'-0" MECHANICAL PLATFORM, SEE STRUCTURAL AND MECHANICAL DRAWINGS. 8.EXISTING SINGLE-PLY ROOF TO REMAIN. 9.EXISTING ROOF FRAMING BELOW TO REMAIN. GENERAL NOTES: 1.SEE MECHANICAL DRAWINGS FOR HVAC EQUIPMENTS AND PENETRATION LOCATIONS. 2.CONTRACTOR SHALL VERIFY SIZES AND LOCATIONS OF ALL MECHANICAL EQUIPMENT PLATFORMS AND BASES, POWER, WATER AND DRAIN LOCATIONS AND INSTALLATION REQUIREMENTS WITH EQUIPMENT MANUFACTURERS PRIOR TO PROCEEDING WITH WORK. CHANGES TO ACCOMMODATE FIELD CONDITIONS OR MATERIAL SUBSTITUTIONS SHALL BE MADE WITHOUT ADDITIONAL CHARGE TO OWNER. 3.MECHANICAL AND PLUMBING EQUIPMENT PLATFORM DIMENSIONS SHALL BE A MINIMUM OF 0'-8" ABOVE ADJACENT ROOF ELEVATION. 4.VENTS THROUGH THE ROOF SHALL BE INSTALLED 10'-0" FROM AND TERMINATED 3'-0" ABOVE ANY FRESH AIR INTAKES. 6 7 5 5 1 3 2 3 3 4 4 8 9 8 9 10 A6.4 T A1.2T A1.2 F A1.2 F - 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 T.O.W. 17'-0" 17 ' - 0 " F.F.EL. 0'-0" 32 514 T T T T T TT T 10 ' - 0 " 7' - 0 " 3' - 4 " 7' - 6 " 2' - 6 " 7'-8" 15'-0" TTTTT T.O.W. 17'-0" 17 ' - 0 " F.F.EL. 0'-0" 32 514 8' - 2 " 8'-4"19'-8" 10 ' - 0 " 3' - 0 " 8" T T T TT T T T T T T T T T T T T T TTT T T T T 800 T T T T T T T T T H I J K L M EAST T.O.W. 17'-0" 17 ' - 0 " F.F.EL. 0'-0" 10 ' - 0 " A B UNITED MEDICAL IMAGING OF SANTA ANA United Medical Imaging Healthcare MRI a CT T T T T TT T T T T T T T H T T T T ELECTRICAL ROOM T T T T.O.W. 17'-0" 17 ' - 0 " F.F.EL. 0'-0" 10 ' - 0 " B A ELECTRICAL ROOM SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L EX T E R I O R E L E V A T I O N S A4.1 MH DS/MH 24-06 SCALE: SOUTH ELEVATION (COURTYARD)11/8"=1'-0" SCALE: EAST ELEVATION 21/8"=1'-0" SCALE: WEST ELEVATION 31/8"=1'-0" NOTES 1 6 1.EXISTING EXTERIOR STUCCO TO REMAIN. 2.EXISTING STOREFRONT DOOR AND WINDOW TO REMAIN. 3.EXISTING STEEL CANOPY TO REMAIN. 4.EXISTING EXTERIOR HOLLOW METAL DOORS TO REMAIN. 5.EXISTING DOWNSPOUT TO REMAIN. 6.OPEN TO COURTYARD. 7.SKEWED ELEVATION. 8.PROPOSED NEW CANVAS CANOPY AT THE ENTRY, "SUNBRELLA" FABRIC COLOR TO MATCH THE EXISTING STEEL EYEBROW. 9.EXISTING FIXED STOREFRONT WINDOW AND PORTION OF EXISTING STUCCO WALL TO BE REMOVED. 10.INSTALL PAIR 3'-0" X 7'-0" STOREFRONT DOORS AND SIDE WINDOW. 11.PROPOSED 7" X 16.5" X 9" WALL MOUNTED LIGHT FIXTURE MANUFACTURER: COOPER - MCGRAW EDISON MODEL NO. IST-SA1F-740-U-T4FT 12.PROPOSED ELECTRICAL TRANSFORMER 13.PROPOSED SIGNAGE UNDER SEPARATE PERMIT 1 3 10 7 5 5 3 4 2 1 1 1 3 2 7 7 5 SCOPE OF THIS PERMIT 4'-0" SCOPE OF THIS PERMIT OPEN TO COURT YARD SCOPE OF THIS PERMIT 7 8 SCALE: SOUTHEAST ELEVATION 1a1/8"=1'-0" 10 8 11 9 SCALE: SOUTHEAST DEMO ELEVATION 1b1/8"=1'-0" 12 13 14. EXISTING STOREFRONT WINDOW TO REMOVED. 15. PROPOSED PAIR 4'-0" X 8'-0" HOLLOW METAL DOORS AND FRAME, PAINTED TO MATCH BUILDING COLOR. 16. EXISTING STOREFRONT DOOR AND WINDOWS TO BE BLACKED OUT WITH FILM. 17. PROPOSED PAIR 3'-0" X 7'-0" HOLLOW METAL DOORS AND FRAME WITH LOUVERS, PAINTED TO MATCH BUILDING COLOR. 18. NEW EXTERIOR 2X WALL WITH EXTERIOR STUCCO OVER WATER PROOFING MEMBRANE AND METAL LATH, PAINTED TO MATCH EXTERIOR BUILDING COLOR. 19.EXISTING EXTERIOR STUCCO WALL TO BE DEMOLISHED FOR NEW DOORS. 14 15 16 16 T TEMPERED GLASS 17 18 19 19 5 - SCALE: "SUNBRELLA" CANOPY FRAME 51"=1'-0" 7" 2' - 9 " 3' - 4 " 1/4" X 2-1/2” LONG SIMPSON STRONG TIE - SDS WITH NEOPRENE WASHER AT 16" ON CENTER 3" 6" 1' - 0 " 1' - 0 " CANVAS CANOPY "SUNBRELLA" FABRIC, COLOR TO MATCH THE EXISTING STEEL EYEBROW 15'-0" 5'-0"5'-0"5'-0" 3' - 4 " 1" X 1" PAINTED ANTI-CORROSION STEEL FRAME AT 5'-0" O.C. 1" X 1" PAINTED ANTI-CORROSION STEEL FRAME TOP AND BOTTOM, 1/4" X 2-1/2” LONG SIMPSON STRONG TIE - SDS WITH NEOPRENE WASHER AT 16" O.C. 1" X 1" PAINTED ANTI-CORROSION STEEL FRAME AT 5'-0" O.C. 1 PL A N C H E C K R E S U B M I T T A L 10 - 1 8 - 2 0 2 4 1 1 SCALE: "SUNBRELLA" CANOPY FRAME 41/4"=1'-0" 5 - di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 SCHED. MIRROR (*) * 40" MAX. TO REFLECTIVE SURFACE 12" min.24" min. 2' - 1 0 " 3' - 3 " ( * ) mi n . t o ou t l e t 19 " 42" MIN. 6" max. 7"-9" 2' - 1 0 " WOOD VENEER DOOR 10" STAINLESS STEEL KICK PLATE WALL TILE, FOR ALL 4 WALLS WT 1 STAINLESS STEEL COVE-SHAPED PROFILE WHERE WALL TILE MEETS FLOOR SCHLUTER DILEX-HKS WITH DILEX-EHK-OUT AND IN P 6 P 6 P 6 7" - 9 " 4' - 6 3 / 4 " (4 ' - 0 " M I N . ) C OF FIXTURE L 18" MIN.60" MIN. 17"-18" C OF FIXTURE L 3'-8" SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H SCALE: ENLARGED ACCESSIBLE RESTROOMS 11/2"=1'-0" NOTES NOTE: ALL DIMENSIONS & CALLOUTS TYPICAL FOR EACH ROOM, U.N.O. 2 - A B C D HEIGHT REQUIREMENT LEGEND 17 " - 1 9 " HEIGHT ACCESSIBLE 1 5 2 36" MIN. 3 42" MIN. 33 " - 3 6 " 40 " M A X . TO H I G H E S T OP E R A B L E P A R T 4 TOP 17 " - 1 9 " 8 RE S T R O O M A N D IN T E R I O R E L E V A T I O N S A5.1 MH DS/MH 24-06 LANDLORD'S NOTES: TENANTS MUST INSTALL A LATEX-RUBBER WATERPROOFING MATERIAL UNDER THE FLOOR FINISH IN ALL WET AREAS OF THE SPACE SUCH AS RESTROOMS AND AREAS WITH SINKS, WATER HEATERS, ETC. THE MEMBRANE SHALL LAP UP PERIMETER WALLS UNDERNEATH COVED BASE TO A MINIMUM HEIGHT OF 12" AFF. SCALE: RESTROOM 106 - INTERIOR ELEVATIONS 23/8"=1'-0" B CA D 106 RESTROOM 3 1 2 29 " C L R . 34 " M A X . 7 6" 8" 27 " M I N . 9" MI N . 11 A6.4 11 A6.4 1 ADA - TANK TYPE TOILET TOTO_MS854114E_G_MS853113E, REFER TO PLUMBING DRAWINGS. 2 4 6 GRAB BAR - 36". BOBRICK; MODEL #B-5806X36 OR APPROVED EQUAL. PROVIDE BACKING AS REQUIRED. GRAB BAR - 42". BOBRICK; MODEL #B-5806X42 OR APPROVED EQUAL. PROVIDE BACKING AS REQUIRED. RECESSED PAPER TOWEL DISPENSER AND WASTE RECEPTACLE AMERICAN SPECIALTIES, INC. MODEL #0469 CHANNELED-FRAME MIRROR BOBRICK, MODEL #B-165 2436 SURFACE-MOUNTED GLACIER BAY INNBURG TOILET PAPER HOLDER IN BRUSHED NICKEL. ADA - AMERICAN STANDARD 0356.421.020 LUCERNE WALL-MOUNT OR APPROVED EQUAL, REFER TO PLUMBING DRAWINGS. 7 3 5 TOILET SEAT COVER DISPENSER BOBRICK, MODEL #B-221 OR EQUAL8 4 A6.4ALL TOILET ACCESSORIES REQUIRE BACKING, SEE DETAIL 9 ROVAL HIGH SPEED AUTOMATIC HAND DRYERS - SEMI RECESSED (277V AC) AMERICAN SPECIALTIES, INC. MODEL #20199 SEE ELECTRICAL DRAWINGS. 12 A6.4 5 4 8 9 7 6 3 G.4 3 G.4 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H WA L L D E T A I L S A6.1 mh DS/MH 23-16 2 3 8 7 6 11 1216 15 14 13 SCALE: WALL STUD SCHEDULE N/A SCALE: WALL BASE 3"=1'-0" 1/ 8 " 5/8" GYP. BD. EACH SIDE OVER METAL STUDS, SEE METAL STUD TABLE FOR SIZE & SPACING (TYPE-X AT FIRE RATED WALLS) HILTI X-U 0.157" DIA. POWER DRIVEN @24" O.C. WITH 1" MIN. EMBEDMENT, STAGGERED ICC-ESR-2269 FINISH FLOOR #10 SCREWS (TYP.) WALL BASE @ GYP. BD. WALLS PER SCHEDULE U.O.N. FIRE/SMOKE SEALANT AT PERIMETER OF RATED/NON-RATED PARTITION, TYP. DRYWALL OR STRUCTURAL SHEATHING WALL FRAMING STUD NOTES: 1.BRIDGING TO OCCUR AT 4'-0" MIN VERTICALLY WHERE DRYWALL OR STRUCTURAL SHEATHING IS INSTALLED ON ONE SIDE OF WALL FRAMING. 2.BRIDGING TO OCCUR 12" MAX FROM TOP OF STUDS AT A SLIP TRACK CONNECTION. #8 SCREW ATTACHMENT TAUT 16 GA x 2" FLAT STRAPS TRACK BLOCK PIECE TO MATCH WALL STUD INSTALLED 8'-0" OC, CLIP FLANGE AND BEND WEB SOUND ATENUATION INSULATION AT ACCOUSTICAL PARTITIONS 1- 1 / 2 " M I N . EXISTING FLOOR DECK. METAL STUD, SEE METAL STUD TABLE 5/8" GYP. BD. EACH SIDE OVER METAL STUDS SOUND ATENUATION INSULATION AT ACCOUSTICAL PARTITIONS 3" LONG CONTINUOUS 20 GAUGE MIN. (OR SAME GAUGE AS WALL STUD) DEEP LEG TRACK SCREWED TO UNDERSIDE OF BLOCKING WITH TWO (2) 1/4" X 1-1/4" WOOD SCREWS AT 24" O.C., (2) PER BLOCKING PURLINS OR 2X BLOCKING AT 24" O.C. ATTACH TO EXISTING ROOF FRAMING, WITH 3-16D NAILS - TYP. PARALLEL TO DECK 2" DRYWALL SCREWS. ATTACH GYPSUM BOARD TO STUDS ONLY. DO NOT SCREW WITHIN 2" OF BOTTOM OF DEEP LEG TRACK. SCALE: SINGLE STRAP TYPE BRIDGING N.T.S. 1- 1 / 2 " M I N . EXISTING FLOOR DECK. METAL STUD, SEE METAL STUD TABLE 5/8" GYP. BD. EACH SIDE OVER METAL STUDS SOUND ATENUATION INSULATION AT ACCOUSTICAL PARTITIONS 3" LONG CONTINUOUS 20 GAUGE MIN. (OR SAME GAUGE AS WALL STUD) DEEP LEG TRACK SCREWED TO UNDERSIDE OF BLOCKING WITH TWO (2) 1/4" X 1-1/4" WOOD SCREWS AT 24" O.C., (2) PER BLOCKING PERPENDICULAR TO DECK 2" DRYWALL SCREWS. ATTACH GYPSUM BOARD TO STUDS ONLY. DO NOT SCREW WITHIN 2" OF BOTTOM OF DEEP LEG TRACK. 600S162-43 UNPUNCHED STUD CONTINUOUS HORIZONTAL AS REQUIRED. NOTCH FLANGES AT VERTICAL STUDS. DO NOT CUT FLANGES BETWEEN SUPPORTING STUDS. TOP AND BOTTOM BACKING REQUIRED FOR EACH UPPER CABINET. COORDINATE LOCATION WITH MILLWORK INSTALLER. (3) #8 EACH STUD FRAMED WALL - REFER TO WALL TYPE SCALE: TYPICAL BLOCKING N.T.S. 4" MI N . SCALE: WALL SWAY BRACE 3"=1'-0" BRACE TO STRUCTURE, ALTERNATE SIDES. USE METAL STUDS AT 8'-0" O.C. MAX. W/ (2) #10 WOOD SCREWS W/ 1-1/2" MIN. PENETRATION INTO PURLIN PURLIN OR 4x BLOCKING FLOOR DECK, SEE STRUCTURAL DRAWINGS SCALE: TYPICAL INTERIOR WALL 3"=1'-0" 5/8" TYPE "X" GYPSUM BOARD ON METAL STUDS PER STUD TABLE FOR PARTITION FRAMING, SEE WALL STUD TABLE & REFERENCED DETAILS. SOUND ATTENUATION INSULATION AT ACOUSTICAL PARTITIONS FIRE EXTINGUISHER CABINET 3"= 1'-0" VERIFY ROUGH OPENING W/ MFG. IN FIELD. 5/8" TYPE "X" GYP. BD. TYP. FIRE EXTINGUISHER CABINET NON RATED WALL INSTALLATION METAL STUDS WHERE OCCUR. VARIES PER MANUFACTURER. (4"MAX) 2 3 2 3 1 1 2 SIZE OF WALL AND 33 MILS SIZE OF WALL AND 33 MILS SIZE OF WALL AND 33 MILS 362S 162-33 INT. 362S 162-43 DEMISING SIZE OF WALL AND 33 MILS SIZE OF WALL AND 45 MILS SIZE OF WALL AND 54 MILS 600S 162-33 INT. 600S 162-43 DEMISING 800S 162-43 INT. 800S 162-54 (50 KSI) DEMISING 800S 162-54 INT. 800S 162-68 (50 KSI) DEMISING TO MATCH WALL INT. PARTITION DEMISING WALL DEMISING WALL INT. PARTITION 6'-0" 8'-0" 12'-0" 16'-0" 6'-0" 4'-0" SPANKING STUDS HEADER SIZE 362S 162-33 INT. 600S 162-43 DEMISING ATTACH TRACK TO STUD WITH #8 (#7 AT 18 MIL. STUDS) SCREW AT EACH FLANGE. 33 MIL. TYP. UP TO 10'-0" OPENING. 43 MIL. UP TO 12'-0" OPENING. 54 MIL. UP TO 16'-0" OPENING. ADD CLOSURE STUD AS REQUIRED - typical METAL STUD WALL SIZE & SPACING - REFER TO SECTIONS AND STUD SCHEDULE CONT. TRACK ANCHORED TO SLAB w/ HILTI X-GN (0.118 DIA.) TRACK FASTENERS w/ 3/4" MIN. EMBED AT 16" O.C. PER ICC ESR-1752 OR EQUAL (3) #8 SCREWS ATTACH TRACK TO STUD AT EACH FLANGE w/ #8 SCREWS - typical BACK TO BACK STUDS W/ #8 SCREWS AT 12" O.C. ATTACH TRACK TO STUD AT EACH FLANGE W/ #8 SCREWS #8 SCREWS AT 12" 0.C BUILT-UP HEADER - REFER TO SCHEDULE. ADD CLOSURE STUD AS REQUIRED - typical OPEN OPEN N.T.S.SCALE: PARTIAL TYPICAL HEADER DETAILS SCALE: FULL HEIGHT INTERIOR WALL 3"=1'-0" SCALE: TYPICAL WALL SECTIONS 1"=1'-0" SCALE: FULL HEIGHT INTERIOR WALL 3"=1'-0" 7 - 8 - 11 - (EXAMPLE: 6" = 600 X 1/100 INCHES) ALL MEMEBER DEPTHS ARE TAKEN IN 1/100 INCHES. FOR ALL "T" SECTIONS MEMBER DEPTH IS THE INSIDE DIMENSION. MEMBER DEPTH: 600 S FLANGE WIDTH: (EXAMPLE: 1 5/8" = 1.625" ~ 162X 1/100 INCHES) ALL FLANGE WIDTHS ARE TAKEN IN 1/100 INCHES. STYLE: (EXAMPLE: STUD OR JOIST SECTION = S) THE FOUR ALPHA CHARACTERS UTILIZED BY THE DESIGNATOR SYSTEM ARE: (EXAMPLE: 0.054 IN. = 54 MILS; 1 MIL =1/1000 IN.) MATERIAL THICKNESS IS THE MINIMUM BASE METAL THICKNESS IN MILS. MINIMUM BASE METAL THICKNESS REPRESENTS 95% OF THE DESIGN THICKNESS. MATERIAL THICKNESS:162 54 INTERIOR NON-STRUCTURAL NON-COMPOSITE: (S) STUD MEMBER SPACING (IN.) O.C.5 PSF L/240 12" 16" 24"8'-9" 10'-9" 12'-5"362PDS125-15 (50 KSI) 12" 16" 24"10'-9" 13'-2" 14'-6"362PDS125-18 (70 KSI) 12" 16" 24"13'-9" 15'-9" 17'-4"362PDS125-30 (33 KSI) 12" 16" 24"14'-3" 16'-3" 17'-11"362PDS125-33 (33 KSI) S= STUD OR JOIST, T = TRACK, U = CHANNEL, F= FURRING NOTE: ALL STUD INFORMATION IS BASED ON: CLARKDIETRICH ICC ESR-1166P - VARIES PER MANUFACTURER. (4"MAX) 13 - CEILING HEIGHT L/360 8'-9" 10'-9" 11'-10" 10'-1" 11'-6" 12'-8" 12'-0" 13'-9" 15'-2" 12'-5" 14'-3" 15'-8" L/120 8'-9" 10'-9" 12'-5" 10'-9" 13'-2" 15'-2" 14'-1" 17'-3" 20'-0" 15'-0" 18'-5" 21'-3" INTERIOR WALL HEIGHT WITH STRUCTURAL FRAMING: (S) STUD MEMBER SPACING (IN.) O.C.5 PSF L/240 12" 16" 24"15'-4" 17'-7" 19'-4"362S162-33 12" 16" 24"16'-8" 19'-1" 21'-0 12" 16" 24"17'-11" 20'-6" 22'-6" 12" 16" 24"19'-2" 21'-11" 24'-1" L/360 13'-5" 15'-4" 16'-11" 14'-7" 16'-8" 18'-5" 15'-7" 17'-11" 19'-8" 16'-9" 19'-2" 21'-1" L/120 18'-9" 22'-2" 24'-4" 21'-0" 24'-1" 26'-6" 22'-6" 25'-10" 28'-5" 24'-1" 27'-7" 30'-5" 362S162-43 362S162-54 362S162-68 4 800 N Tustin Ave Unit #H1/23/2025 DE T A I L S A6.2 mh 9 1216 48 6 5 10 33250S137 SECTION: (MIL) LATERAL SUPPORT OF COMPRESSION FLANGE CEILING SPAN TABLE NOTES: 1. VALUES ARE FOR SINGLE SPANS. 2. ALLOWABLE CEILING SPAN CALCULATIONS BASED ON 33KSI YIELD STRENGTH STEEL. 3. FOR FULLY BRACED CEILINGS, USE MID-SPAN BRACED VALUES. 4. END BEARING LENGTH = 1" MINIMUM. 4 PSF UNSUPPORTED JOIST SPACING (IN.) O.C.JOIST SPACING (IN.) O.C. 14'-11" 12"16"24" 11'-10"13'-6" (EXAMPLE: 6" = X 1/100 INCHES) ALL MEMBER DEPTHS ARE TAKEN IN 1/100 INCHES. FOR ALL "T" SECTIONS MEMBER DEPTH IS THE INSIDE DIMENSION. 600 MEMBER DEPTH: 600 S FLANGE WIDTH: (EXAMPLE: 1 5/8" = 1.625" ~ X 1/100 INCHES) ALL FLANGE WIDTHS ARE TAKEN IN 1/100 INCHES. 162 STYLE: (EXAMPLE: STUD OR JOIST SECTION = ) THE FOUR ALPHA CHARACTERS UTILIZED BY THE DESIGNATOR SYSTEM ARE: S (EXAMPLE: 0.054 IN. = MILS; 1 MIL =1/1000 IN.) MATERIAL THICKNESS IS THE MINIMUM BASE METAL THICKNESS IN MILS. MINIMUM BASE METAL THICKNESS REPRESENTS 95% OF THE DESIGN THICKNESS. 54 MATERIAL THICKNESS: 162 54 11'-9" 12"16"24" 9'-9"10'-10" MID-SPAN 43250S137 16'-2"12'-10"14'-8"13'-2"10'-9"12'-1" 33250S162 15'-8"12'-5"14'-2"13'-5"11'-1"12'-5" 43250S162 17'-0"13'-6"15'-5"14'-11"12'-3"13'-9" 33350S137 18'-1"15'-0"16'-9"12'-9"10'-6"11'-9" 43350S137 19'-10"16'-4"18'-4"14'-1"11'-7"13'-0" 33350S162 20'-3"16'-1"18'-5"14'-6"12'-0"13'-5" 43350S162 22'-0"17'-6"20'-0"16'-0"13'-2"14'-9" 33362S137 18'-3"15'-2"16'-11"12'-10"10'-7"11'-11" 43362S137 20'-0"16'-6"18'-6"14'-3"11'-8"13'-1" 33362S162 20'-9"16'-6"18'-11"14'-8"12'-1"13'-6" 43362S162 22'-7"17'-11"20'-7"16'-1"13'-3"14'-10" 33400S137 18'-9"15'-6"17'-4"13'-2"10'-11"12'-2" 43400S137 20'-6"16'-11"18'-11"14'-7"12'-0"13'-5" 33400S162 21'-4"17'-9"19'-10"15'-0"12'-5"13'-10" 43400S162 23'-4"19'-4"21'-7"16'-6"13'-7"15'-3" 33550S137 20'-10"17'-5"19'-4"14'-6"12'-0"13'-5" 43550S137 22'-6"18'-9"20'-10"15'-10"13'-1"14'-7" 33550S162 23'-9"19'-10"22'-0"16'-6"13'-8"15'-3" 43550S162 25'-7"21'-4"23'-9"17'-11"14'-10"16'-7" 43 33 33600S137 600S137 600S162 21'-4"17'-10"19'-10"14'-10"12'-4"13'-9" 23'-1"19'-2"21'-4"16'-2"13'-5"14'-11" 24'-4"20'-4"22'-7"16'-10"14'-1"15'-8" 43600S162 26'-3"21'-10"24'-4"18'-4"15'-3"17'-0" = STUD OR JOIST, = TRACK, = CHANNEL,S T U = FURRINGF - NOTE: ALL STUD INFORMATION IS BASED ON: CEMCO ICC ES ESR-3016 OR CLARKDIETRICH ICC ESR-116P SCALE: ALLOWABLE CEILING SPANS N.T.S. SE E R C P 45 DEG. 12 " ( U . N . O . ) BRACE TO STRUCTURE, ALTERNATE SIDES. USE METAL STUDS AT 8'-0" O.C. MAX., MATCH WALL STUD SIZE & GAUGE (3 5/8" 20 GA. MIN.) PROVIDE BENT LEG & FASTEN TO TOP TRACK. MAX LENGTH OF BRACE 25'-0" TOP TRACK SECURED TO WALL BRACE WITH (2) #8 SHEET METAL SCREWS INSULATION WHERE OCCURS, SEE WALL TYPE SCHEDULE 5/8" GYP. BD. EACH SIDE OVER METAL STUDS, SEE METAL STUD TABLE FOR SIZE & SPACING CEILING JOISTS AT 16" O.C., SEE RCP & CEILING JOISTS TABLE. ATTACHED WITH #10 SMS EACH SIDE, EACH END. SCALE: PARTITION TO ABOVE CEILING 3"=1'-0" SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 13 A6.1SEE FOR WALL SWAY BRACE 5/8" GYP. BD. ESR-1338 ATTACHED WITH #6 SCREWS @ 8" O.C. EDGES AND 12" O.C. FIELD CONTINUOUS TRACK WITH (2) #12 SMS TO EACH METAL STUD NOTE: ALL SCREWS ESR-3223 11 10 1 9 2 5 THE FOLLOWING SPANS ARE BASED UPON STUDS HAVING A 1-5/8" LEG WITH A 3/8" RETURN. DOUBLE STUDS ARE CONNECTED TOGETHER IN THE SHAPE OF A , WITH ONE #6 SHEET METAL SCREW AT 16" O.C.. ATTACH THE METAL STUD TO THE T-BAR MAIN RUNNER WITH TWO #8 SCREWS. SEE DETAILS FOR ATTACHMENT TO STRUCTURE ABOVE. DBL 1-5/8 x 25 GA STEEL STUDS 3-5/8" X 20 GA. STUDS- SCREWED W/ 7/16" 9 GA. FRAMING SCREWS @ 24" O.C. STAGGERED- SANDWICH MAIN RUNNER BACK. & ATTACH W (3) 7/16" FRAMING SCREWS. PRE-MANUFACTURED STRUTS MAY ONLY BE USED IF ENGINEERING IS APPROVED BY THE BUILDING DEPARTMENT. GC TO SUBMIT FOR APPROVAL. 6' - 0 " METAL STUDS: MANUFACTURED STRUTS: MAIN RUNNER 2" MAX 3-5/8" x 25 GA. OC TYP. 12'-0" 12 ' - 0 " OC T Y P . MAIN RUNNER TO 20'-0" TO 10'-0" TO 8'-0" SUSPENDED CEILING SYSTEM, SEE REFLECTED CEILING PLAN FOR SPECIFICATIONS. ICC ESR-2631 (CHICAGO METALLIC), OR ICC ESR-1222 (USG INTERIORS), OR ICC ESR-1308 (WORTHINGTON ARMSTRONG VENTURE) CIRCLE INDICATES REQUIRED LOCATION OF COMPRESSION STRUTS. SEE BELOW. 20GA. MTL. STD COMPRESSION STRUT @ EA. SET OF BRACING WIRES W/(2) #8 SHEET MTL. SCREWS TO THE GRID, SPAN PER TABLE ABOVE. SUSPENDED CEILING SYSTEM. SEE CEILING PLAN. (2) STUD ORIENTATION 12GA. BRACING W/4 TIGHT TURNS IN 1 1/2" EACH END. SPLAY WIRE BRACING IN CLUSTERS OF FOUR WIRES ATTACHED TO MAIN RUNNER WITHIN 2" OF A CROSS TEE SECTION. OCCUR WHEN CEILING AREA EXCEEDS 1000 SF CROSS RUNNER LATERAL FORCE BRACING: A STRUT FASTENED TO THE MAIN RUNNER SHALL BE EXTENDED TO THE STRUCTURAL MEMBERS SUPPORTING THE ROOF OR FLOOR ABOVE. LATERAL FORCE BRACING SHALL BE 12 FEET ON CENTER (MAXIMUM) AND BEGIN NO FARTHER THAN 6 FEET FROM WALLS. LATERAL FORCE BRACING MEMBERS MUST BE SPACED A MINIMUM OF 6" FROM ALL HORIZONTAL PIPING OR DUCT WORK THAT IS NOT PROVIDED WITH BRACING RESTRAINTS FOR HORIZ. FORCES. BRACING WIRES MUST BE ATTACHED TO THE GRID AND TO THE STRUCTURE IN SUCH A MANNER THAT THEY CAN SUPPORT A DESIGN LOAD OF NOT LESS THAN 200 POUNDS OR THE ACTUAL LOADS, WHICHEVER IS GREATER, WITH A SAFETY FACTOR OF 2. ATTACHED UNATTACHED UN A T T A C H E D AT T A C H E D DBL 2-1/2" x 25 GA TO 15'-0" DBL 3-5/8" X 20 GA CEILING SYSTEMS ARE TO BE ATTACHED ONLY AT 2 ADJACENT WALLS OR SOFFITS MA X . LARR #24299 12GA. VERTICAL HANGER WIRE @ 4'-0" O.C. EACH WAY (4' O.C. AT MAIN RUNNER) MINIMUM 3 TIGHT TURNS IN 1-1/2" BOTH ENDS TYPICAL THE FOLLOWING INSTALLATION DETAILS ARE TO BE CONSIDERED TO BE COMPLYING WITH THE ABOVE REQUIREMENTS. NOTES: 1.WHERE THE ROOF SYSTEM IS COMPOSED OF WOOD BEAMS, PURLINS, AND SUB-PURLINS, THE 2 X 4 SUB-PURLINS ARE NOT TO BE CONSIDERED AS STRUCTURAL MEMBERS SUPPORTING THE ROOF. 2.CEILING SUSPENSION SYSTEM SHALL COMPLY WITH 803.9 AND 2506.2.1. COMPONENTS SHALL BE ASTM "HEAVY DUTY" CLASS. 3. THE COMPRESSION STRUT SHALL BE VERTICAL, AND SHALL NOT HANG MORE THAN 1 IN 6 OUT-OF-PLUMB. ACOUSTICAL CEILING SUSPENSION SYSTEM SEISMIC JOINT IF REQ'D. PER PLAN LATERAL FORCE BRACING AND SUSPENSION LIGHT FIXTURE FIRE SPRINKLER ** * * * = 45° LARR #25764 LARR #25032 CEILING GRID SUSPENDED LIGHT FIXTURE (LESS THAN 56 LBS.) LATERAL FORCE BRACING MEMBERS MUST BE SPACED A MINIMUM OF 6" FROM ALL HORIZONTAL PIPING OR DUCT WORK THAT IS NOT PROVIDED WITH BRACING RESTRAINTS FOR HORIZ. FORCES. BRACING WIRES MUST BE ATTACHED TO THE GRID AND TO THE STRUCTURE IN SUCH A MANNER THAT THEY CAN SUPPORT A DESIGN LOAD OF NOT LESS THAN 200 POUNDS OR THE ACTUAL LOADS, WHICHEVER IS GREATER, WITH A SAFETY FACTOR OF 2. PROVIDE MINIMUM OF 2 SCREWS AT OPPOSIT CORNERS OF SUPPORT WIRES, OR SCREW ON T-BAR SAFETY CLIPS AT SIDES OR ENDS. TWO (2) NO. 12 GAUGE WIRES MUST BE SECURED FROM LIGHT & MECHANICAL FIXTURES AT OPPOSING CORNERS ALONG THE FIXTURE'S DIAGONAL. WIRES MAY BE SLACK. WHEN HEAVY-DUTY CEILING SYSTEMS ARE USED, SUPPLEMENTAL HANGERS ARE NOT REQUIRED IF A 48" MODULAR HANGER PATTERN IS FOLLOWED. HEAVY-DUTY CEILING SYSTEMS SEISMIC JOINT CLIP TWO PIECE UNIT W/ SLOTS HORIZONTAL SEISMIC SLOT VERTICAL POSITIONING STAMP MAIN BEAM: SJMR CROSS TEE: SJCG SILHOUETTE AND INTERLUDE CROSS TEE: SJCSI ICC ESR-1308 LARR # 25032 USG ACM7 ICC ESR-1222 OR CHICAGO METALIC SST ICC ESR-2631 OR LARR # 25764 (ARMSTRONG "SJCG" SHOWN) ARMSTRONG SEISMIC JOINT CLIP WORK WITH ARMSTRONG 15/16" AND 9/16" GRID SYSTEMS. (PRELUDE, SUPRAFINE AND SILHOUETTE WALL OR SOFFIT CLOSURE ANGLE MOLDING 7800 WHERE WALL REMAINS UNATTACHED TO CLOSURE ANGLE, 3/4" CLEARANCE TO BE MAINTAINED ACOUSTICAL PANEL SUSPENDED CEILING GRID 3/4" LOOSE SCREW "UNATTACHED WALL" ARMSTRONG BERC2 ICC ESR-1308 8" MAX. SEISMIC CLIP SYSTEM ANCHOR TO WALL OR SOFFIT BY #6 SCREWS AT 24" O.C.PERIMETER HANGER WIRE AT ALL MAIN RUNNERS AND CROSS TEES LARR # 25032 "UNATTACHED WALL" USG ASM7 ICC ESR-1222 OR HANGER AND PERIMETER WIRES MUST BE PLUMB WITHIN 1 IN 6 UNLESS COUNTER SLOPING WIRES ARE PROVIDED "UNATTACHED WALL" CHICAGO METALIC ICC ESR-2631 OR WALL OR SOFFIT CLOSURE ANGLE MOLDING 7800 ACOUSTICAL PANEL SUSPENDED CEILING GRID TIGHT SCREW 8" MAX. SEISMIC CLIP SYSTEM ANCHOR TO WALL OR SOFFIT BY #6 SCREWS AT 24" O.C. PERIMETER HANGER WIRE AT ALL MAIN RUNNERS AND CROSS TEES "ATTACHED WALL" ARMSTRONG BERC2 ICC ESR-1308 LARR # 25032 "ATTACHED WALL" USG ASM7 ICC ESR-1222 OR HANGER AND PERIMETER WIRES MUST BE PLUMB WITHIN 1 IN 6 UNLESS COUNTER SLOPING WIRES ARE PROVIDED "ATTACHED WALL" CHICAGO METALIC ICC ESR-2631 OR 2" 2" CEILING LAY-IN TILES (LARR #24646) MAIN TEE THE FIRST CEILING TILE SHALL BE A MINIMUM 3/4" CLEAR FROM WALL SURFACE. 16 GAUGE ANGLE FINISHED TO MATCH GRID. MINIMUM 2" HORIZONTAL WALL ANGLE LENGTH SHALL BE USED AT PERIMETER WALLS AND AT INTERIOR FULL HEIGHT PARTITIONS. 3/4" MIN NOTE: THIS DETAIL SHALL BE USED IN CONDITIONS WHERE THE SPAN OF THE CEILING SYSTEM EXCEEDS 25 FEET IN BOTH DIRECTIONS. DS/MH 23-16 2 1SCALE: SEISMIC JOINT CLIP 3"=1'-0" SCALE: LIGHT FIXT. AT SUSPENDED CEILING N/A SCALE: UNATTACHED CLOSURE ANGLE 3"=1'-0" SCALE: ATTACHED CLOSURE ANGLE 3"=1'-0" SCALE: CEILING AT PERIMETER WALL 3"=1'-0" SCALE: SUSPENDED CEILING N/A GYPSUM BOARD SOFFIT USE METAL STUDS @ 24" O.C. MAX. MATCH WALL STUD, SIZE, & GAUGE SE E R C P N. T . S . SE E R C P METAL STUD WALL BRACE AT 8'-0" O.C. MAX. WITH (3) #10 METAL SCREWS AT EACH END SCALE: SOFFIT 1-1/2"=1'-0" STRUCTURE ABOVE METAL STUD - SEE STRUCTURAL DRAWINGS SCALE: ACCESS PANEL 3"=1'-0" METAL OR DRYWALL ACCESS PANEL (BY OTHERS) SPECIFICATION BY ARCHITECT, REFERENCE ACCESS PANEL LITERATURE FOR REQUIRED SUPPORT AND ATTACHMENT DETAILS. 5/8" GYPSUM BOARD 3-5/8" METAL STUD. 7 11 A6.1 7 A6.1 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H MI L L W O R K D E T A I L S A6.3 mh DS/MH 23-16 9 12 SCALE: BENCH AT CHANGING ROOM 1"=1'-0" SCALE: RECEPTION DESK WORK SPACE 1"=1'-0" A.UNLESS NOTED OTHERWISE, ALL CABINET CONSTRUCTION SHALL BE PLASTIC LAMINATE CLAD, AND SHALL MEET THE REQUIREMENTS OF AWI SECTION 400, CUSTOM GRADE, FLUSH OVERLAY CONSTRUCTION. ALL WOOD VENEER CLAD CABINET CONSTRUCTION SHALL MEET THE REQUIREMENTS OF AWI SECTION 400, PREMIUM GRADE, FLUSH OVERLAY CONSTRUCTION. COUNTERTOPS SHALL MEET THE REQUIREMENTS OF AWI SECTION 400 WITH EDGE DETAILS AS INDICATED ON THE DRAWINGS. B.FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO SUBMITTING SHOP DRAWINGS FOR ARCHITECT'S REVIEW. C.ALL OPEN SHELVING SHALL CONFORM TO AWI SECTION 400B, CUSTOM GRADE. UNLESS NOTED OTHERWISE, ALL SHELVES SHALL BE PAINTED. SHELVING STANDARDS SHALL BE EQUAL TO KV NO. 82 AND BRACKETS SHALL BE EQUAL TO KV NO.182, UNLESS MORE STRINGENT REQUIREMENTS ARE NOTED. PROVIDE PROPER FIRE-RETARDANT BLOCKING WITHIN PARTITIONS ON WHICH SHELVING IS INSTALLED. D.PROVIDE EXTERIOR-GRADE OR WATER-RESISTANT SUBSTRATE TOE KICKS AT SINKS, LAVATORIES, AND FLOOR TILE LOCATIONS. E.CABINET BODY CONSTRUCTION TO BE VENEER-CORE PLYWOOD OR MDF; EXCEPT AT WET AREAS, USE WATER-RESISTANT SUBSTRATE. F.INTERIOR CONSTRUCTION TO BE WHITE MELAMINE @ NON-WOOD GRAIN PLAM CABINETS, W/BLACK MELAMINE @ WOOD GRAIN PLAM & WOOD VENEER CABINETS. G.ALL EXPOSED SURFACES TO BE CLAD IN PLAM., UNLESS OTHERWISE NOTED. H.PROVIDE SHOP DRAWINGS FOR ALL MILLWORK FOR REVIEW PRIOR TO BEGINNING FABRICATION OF ANY MILLWORK ITEMS. I.UNDERSIDE OF OVERHEAD CABINETS TO MATCH CABINET FINISH. J.ALL FINISHES SHALL BE AS INDICATED IN THE FINISH SCHEDULE AND FINISH KEY, UNLESS NOTED OTHERWISE. K.UNLESS INDICATED OTHERWISE, BASE CABINETS ARE TO BE FLUSH WITH COUNTERTOP; UPPER CABINETS ARE 1'-3" INSIDE CLEAR. L.MILLWORKER TO COORDINATE ALL MILLWORK INSTALLATIONS WITH OTHER SUBCONTRACTORS AND APPLIANCES AND SHALL BEAR ANY COST ASSOCIATED WITH THE RECONFIGURATION OF MILLWORK IN CONFLICT WITH OTHER TRADES. M.ALL INSTALLED CABINETS SHALL BE SCRIBED TO WALL OR CEILING WITHOUT ADDITIONAL OVERLAYS. CAULK ALL JOINTS TO WALLS. N.UNLESS NOTED OTHERWISE, HARDWARE MINIMUM REQUIREMENTS ARE AS FOLLOWS. CONFIRM FINISH WITH ARCHITECT PRIOR TO ORDERING. 1.PULLS: 1-5/8" ROUND KNOB, SATIN NICKEL FINISH, EMTEK 86449 OR EQUAL. 2.HINGES: CONCEALED, SOFT-CLOSING, BLUM CLIP 125 OR EQUAL 3.DRAWER GLIDES: ACCURIDE, CB-3832-20: BLACK ZINC, FULL EXTENSION SLIDE, 100 LBS CAPACITY 4.SHELF SUPPORT: HAFELE, 282.04.711, NICKEL 5.BUMPERS: BLUM #TP1950 CLEAR PLASTIC RESILIENT. PROVIDE AT ALL DOORS & DRAWERS. 6.ELBOW CATCHES: IVES, IV2, CHROME 7.LOCKS: HAFELE, 235.08.054 8.TOUCH LATCH: FERUM, FE944BN ROLLER TOUCH LATCH 9.GROMMET: DOUG MOCKETT, EDP SERIES 2.5" HOLE GENERAL NOTES millwork BASE CABINET CL SCHEDULED MILLWORK PULL DRAWER UPPER CABINET PLASTIC LAMINATE TOP BENCH OVER 3/4" PLYWOOD; MITER EDGE DRAWER AND SLIDE TOE KICK TO MATCH BASE CABINET; SCRIBE TO FLOOR 1'-8" 3" 1 1 / 2 " 1/ 2 " 8" 4" 1' - 6 " 4" 4" FIRM BENCH CUSHION SCALE: CABINET LOCKERS 1"=1'-0" TOE KICK TO MATCH BASE CABINET; SCRIBE TO FLOOR 1'-8" 3" 4" 2' - 6 " 2' - 6 " 2' - 6 " 7' - 6 " 3/4" x 3" STRETCHER, TYP. 1 1 / 2 " 1/ 2 " 1 1 / 2 " 1/ 2 " 1 1 / 2 " 1/ 2 " 4 3/4" PLASTIC LAMINATE CABINET DOOR, TYP. - FINISH BOTH SIDES & PROVIDE EDGE BAND AT ALL 4 EDGES 4" BRUSHED STAINLESS WIRE PULLS MOUNTED HORIZONTALLY, WITH COUNTER-SUNK SCREWS & CAPS, TYP. - PROVIDE SILENCERS AT DOORS FRAMELESS CONCEALED HINGE, TYP. 3/4" MELAMINE TOP W/ EDGE BAND 1/4" MELAMINE BACK, TYP. 4" BRUSHED STAINLESS WIRE PULLS MOUNTED HORIZONTALLY, WITH COUNTER-SUNK SCREWS & CAPS, TYP. - PROVIDE SILENCERS AT DOORS SCALE: RECEPTION DESK 1"=1'-0" 5 6 2'-0" 2' - 6 " BASE AS SCHEDULED COORDINATE OPENING IN FRAMING FOR POWER/DATA QUARTZ COUNTER TOP OVER 3/4" PLYWOOD 16"X14" CENTERLINE BRACKETS, BLACK AT 36" O.C. 18 GA. METAL STUD WITH 3/4" PLYWOOD AND 5/8" GYPSUM BOARD, PAINT TO MATCH WALL COLOR 1 1 / 2 " SCALE: COUNTERTOP 1"=1'-0" PLASTIC LAMINATE OVER 3/4" PLYWOOD WITH 4" BACKSPLASH1'-4" 2' - 6 " 4" 12"X14" CENTERLINE BRACKETS, BLACK AT 36" O.C. BASE AS SCHEDULED 1 1 / 2 " 10 +18" +18" 5' - 6 " 2'-0"3'-0" 5'-0" 5 - A - PLAN B - ELEVATION 4B - 1' - 4 " CERAMIC TILE OVER TILE BACKER BOARD, PER OWNER QUARTZ COUNTERTOP EXISTING WALL TO REMAIN LOW WALL BELOW 9 - 30" X 48" CLEAR SPACE 1 1/2" 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H DE T A I L S A6.4 mh DS/MH 23-16 9 12 4 5 610 INSULATION WHERE OCCURS DOOR FRAME PER SCHEDULE DOOR PER SCHEDULE RO U G H O P E N I N G DO O R D I M . SE E S C H E D U L E 1/ 2 " METAL TRACK 3-5/8" METAL STUD NESTED IN METAL TRACK 1/2" DOOR AND FRAME PER SCHEDULE FOR FINISH FLOOR SEE FINISH PLAN MATERIAL TRANSITION WHERE OCCURS 1/ 2 " M A X SCALE: DOOR HEAD (JAMB SIM.) 3"=1'-0" 5/8" TYPE 'X' GYP. BD. EACH SIDE OVER METAL STUD. SEE STRUCTURAL DRAWINGS FOR SIZE AND SPACING. SCALE: DOOR SILL 6"=1'-0" 1 2 37 8 11 16 GA. METAL STUD 16" O.C. @ ALL BACKING STUD TRACKS 16 GA.X6"X1-1/2" UNPUNCHED METAL TRACK W/LEGS CLIPPED & BENT @ EA. STUD. ATTACH TO EACH STUD W/3(#10) SELF-DRILLING AND SELF-TAPPING SHEET METAL SCREWS (TO MIN. 3 STUDS) EXTEND BACKING 1 BAY BEYOND EDGE OF CABINET / EQUIP. NOTE: DO NOT CUT FLANGES BETWEEN SUPPORTING STUDS W = MAX. 100 lb. PER STUD. ADAPTOR JOHNSONITE CTA-XX-K, 3/8" RESILIENT MATERIAL TO 1/8" RESILIENT MATERIAL, COLOR: T.B.D. 1/8" RESILIENT FLOORING (LVT/SDT/EPOXY) STONE, GRANITE OR CERAMIC TILE MATERIAL. FIXED GLASS. INSULATION WHERE OCCURS 5/8" TYPE 'X' GYP. BD. EACH SIDE OVER METAL STUD. SEE STUD TABLE FOR SIZE AND SPACING. ALUMINUM WINDOW FRAME IN METAL TRACK 3-5/8" METAL STUD NESTED METAL TRACK6" NOTE: PROVIDE METAL BLOCKING BETWEEN STUDS TO MOUNT LIGHT SWITCH/SENSOR & THERMOSTAT AT DIMENSION INDICATED 38 " THERMOSTAT LIGHT SWITCH/SENSOR DOOR HANDLE NOTE: PROVIDE METAL BLOCKING BETWEEN STUDS TO MOUNT LIGHT SWITCH/SENSOR & THERMOSTAT AT DIMENSION INDICATED38 " THERMOSTAT 6" SIDELITE DOOR JAMB PARTIAL PLAN DOOR IN OPEN POSITION (OR @ GLASS FRONT) LIGHT SWITCH/SENSOR DOOR HANDLE METAL FRAMING. ACOUSTICAL INSULATION (WHERE OCCURS). (1) LAYER OF 5/8" DENSSHIELD WALL BOARD THINSET WALL TILE. SS SCHLUTER COVE BASE. THINSET FLOOR TILE. EXISTING FLOOR. SCALE: WINDOW HEAD (JAMB & SILL SIM) 3"=1'-0" CONCRETE FILLED 5" O.D. STD. STEEL GALVANIZED PIPE (MIN. 1/4" WALL THICKNESS). PRIMED AND PAINTED YELLOW CONCRETE FOOTING (E) CONCRETE CURB 1' - 9 " 2' - 0 " 5" MIN. 1'-3" MIN. 5" M I N . SCALE: BOLLARD 1-1/2"=1'-0" SCALE: TILE BASE 1-1/2"=1'-0" WALL - INSTALL PER TCNA W244C-22 FLOOR - INSTALL PER TCNA F180-22 SCALE: TILE TO RESILIENT FLOORING FULL SCALE: LT. SWITCH/T-STAT @ SIDELITE 3/8"=1'-0" SCALE: LT. SWITCH/T-STAT INSTALLATION 3/8"=1'-0" SCALE: BACKING DETAIL FOR MISC. EQUIP. N.T.S. 13 15 EXTERIOR STOREFRONT FRAME INTERIOR ALUMINUM 10 " DOOR FRAME BOTTOM RAIL TO MATCH DOOR STOP AT JAMB BEYOND INSULATED GLASS FILL CONSTRUCTION CONTROL JOINTS THAT CONTINUE UNDER THRESHOLD WITH SEALANT. EXTERIOR RAIN DRIP DOOR BOTTOM SWEEPS (VINYL) WITH STAINLESS STEEL FASTENERS. COLOR TO MATCH DOOR. 1/ 2 " 1/ 2 " THRESHOLD SET IN SEALANT AND SEAL EDGES OF ENDS, FINISH TO MATCH DOOR FRAME. PEMKO 2005 _T 1/2" EXP. JOINT MATERIAL, WHERE OCCURS. COORDINATE WITH SLAB AND EXTERIOR WALLS SCALE: STOREFRONT DOOR 3"=1'-0" INSULATED GLASS ALUMINUM STOREFRONT SYSTEM SCALE: WINDOW HEAD (JAMB SIM.) 3"=1'-0" DOOR DIM. INSULATED GLASS STOREFRONT SYSTEM DOOR STOP ALUMINUM EXTERIOR INTERIOR SCALE: STOREFRONT JAMB 3"=1'-0"16 JAMB BEYOND FINISH FLOOR METAL THRESHOLD 1/4" TOOLED CONC. EDGE DOOR SWEEP/SHOE - SEE HARDWARE SCHEDULE 1 1 / 2 " M A X . SEALANT OVER 1/2" EXP. JOINT MATERIAL DOOR PER SCHEDULE EXTERIOR INTERIOR (SEE DOOR SCHEDULE) MECHANICAL EQUIPMENT WITH HEAVY DUTY STEEL-SPRING ISOLATOR 3" 8" MI N . BASE FLASHING FASTENER AT 8" O.C. (E) ROOFING (E) ROOF DECK 22 GA. G.I. FLASHING LID WITH SOLDERED SEAMS SECURED USING SCREWS THROUGH STEEL / NEOPRENE WASHER AT 12" O.C. SCALE: MECHANICAL UNIT PLATFORM 3"=1'-0" B.O.HEADER SEE WALL SECTIONS EXTERIOR PLASTER OVER METAL LATH AND WRB INSULATION, PER TITLE 24 CALCULATIONS EXISTING EXTERIOR SHEATHING BOARD 2X STUD FRAMING SOFFIT DRIP SCREED SHIM, AS REQUIRED INTERIOREXTERIOR J-MOLD BACKER ROD AND SEALANT OUTLINE OF FINISH NOTE: ANY PENETRATIONS IN WATER PROOFING MEMBRANE/WRB SHALL BE FULLY SEALED. BUILDING LINE BEYOND (JAMB SIM.) SCALE: HOLLOW METAL DOOR HEAD 3"=1'-0" CONTINUOUS CLEAT AND SEALANT SINGLE-PLY ROOFING TO MATCH (E) ROOF, INSTALL PER ROOFING MANUFACTURER'S SPECIFICATIONS - PATCH AND REPAIR AS REQ'D MIN. 2 X 8 CONTINUOUS WOOD CURB SECURED TO UNDERLYING SUBSTRATE SEE "S" DWGS. LANDSCAPE NEW CONCRETE PAD, SEE STRUCTURAL DRAWINGS SCALE: HOLLOW METAL DOOR SILL 3"=1'-0" B.O.HEADER SEE WALL SECTIONS EXTERIOR PLASTER OVER METAL LATH AND WRB INSULATION, PER TITLE 24 CALCULATIONS EXISTING EXTERIOR SHEATHING BOARD 2X STUD FRAMING SOFFIT DRIP SCREED INTERIOR J-MOLD BACKER ROD AND SEALANT OUTLINE OF FINISH EXTERIOR SHIM, AS REQUIRED 800 N Tustin Ave Unit #H1/23/2025 DO O R / W I N D O W S C H E D U L E S A7.1 MH DS/MH 24-06 DOOR NUMBER ROOM NAME DOOR FRAME HARDWARE REMARKSWIDTHHEIGHTTYPEMATERIALFINISHMATERIALFINISH 100 ELECTRICAL ROOM PAIR 3'-0"7'-0"B 102 CT SCAN 102a 103 OPERATOR 104 MRI 104A 105 EQUIPMENT 107 CHANGING ROOM SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L STEEL PAINT F WOOD ALUM CLEAR 3'-6"WOOD ALUM CLEAR 3'-0"C WOOD ALUM CLEAR 4'-0"E WOOD COPPER - PR. 4'-4-1/2" PAIR 4'-0"B 3'-0" DOOR/WINDOW TYPES: 1. VERIFY THAT ALL DOORS AND DOOR HARDWARE MEET THE REQUIREMENTS OF ALL GOVERNING CODES & STANDARDS. NOTIFY THE ARCHITECT IMMEDIATELY IN CASE OF DISCREPANCY. 2. FIELD MEASURE, AS REQUIRED, ALL DOORS PRIOR TO FABRICATION. 3. PROVIDE A SIGN ON OR NEAR THE MAIN EXIT DOOR READING: "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". 4. RATED DOORS SHALL COMPLY WITH REQUIREMENTS OF ALL GOVERNING CODES & STANDARDS AND SHALL BEAR A LABEL FROM A RECOGNIZED AGENCY SHOWING THE SPECIFIC RATINGS. 5. ALL HARDWARE TO BE LEVER-TYPE PER GOVERNING CODES & ACCESSIBILITY STANDARDS. 6. DOOR HANDLES, PULLS OR KNOBS SHALL BE INSTALLED AT 38" ABOVE FINISH FLOOR. ALL OTHER OPERABLE PARTS OF DOOR HARDWARE (SUCH AS DEADBOLTS, KEYHOLES... ETC.) ARE TO BE CENTERED BETWEEN 34" AND 44" ABOVE FINISH FLOOR. IF EXISTING BUILDING STANDARD EXISTS, MATCH BUILDING STANDARD AND CONFIRM COMPLIANCE WITH ACCESSIBILITY REQUIREMENTS. 7. SPECIAL LOCKING DEVICES SHALL BE OF AN APPROVED TYPE. 8. PROVIDE WEATHER SEALS ON ALL EXTERIOR DOORS PER ANSI STANDARDS. 9. CONTRACTOR IS RESPONSIBLE TO COORDINATE & VERIFY ALL DOOR FRAME THROAT THICKNESS' FOR EACH LOCATION. 10. ALL DOOR FRAMES TO BE FACTORY FINISHED. 11. ALL DOOR STOPS TO HAVE 2x6 BACKING IN THE WALL BEHIND. 12. MAXIMUM UNDERCUT OF ALL DOORS NOT IN A RATED CORRIDOR SHALL NOT EXCEED 1/2" ABOVE FINISH FLOOR SURFACE. 13. ALL DOORS TO BE OPERABLE FROM THE INSIDE WITHOUT A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT. 14. ALL DOORS WITH ELECTRONIC SECURITY DOOR LOCKS MUST BE OPENABLE FOR EXITING PURPOSES UNDER ALL CONDITIONS. INCLUDING A POWER OUTAGE. 15. IF BUILDING STANDARDS ARE INCONSISTENT FOR DOORS, RELITES, HARDWARE, DOOR AND RELITE FRAMES OR OTHER STANDARD DETAILS, THEN CONTRACTOR MUST VERIFY WITH DESIGNER AND OWNER PRIOR TO CONSTRUCTION. DOOR NOTES: DOOR HARDWARE: A STOREFRONT DOORS WITH SIDE LIGHT D SCHEDULED WIDTH SC H E D U L E D H E I G H T DOUBLE DOOR WITH LOUVER B SOLID SINGLE DOOR 5' - 0 " SS KICK PLATE 4'-0" 3' - 0 " INTERIOR WINDOW 5 A6.4 INTERIOR WINDOW EXIT, PROVIDE TACTILE EXIT SIGN DOOR AND FRAME SCHEDULE STEEL PAINT ## 3'-0" SOLID SINGLE DOOR WITH ETCHED VISION LITE C SCHEDULED WIDTH SC H E D U L E D H E I G H T SOLID SINGLE SHIELDED DOOR E SCHEDULED WIDTH SC H E D U L E D H E I G H T RF SHIELDED DOOR AND FRAME PER MANUFACTURER MRI 3'-0"F WOOD ALUM CLEAR RESTROOM106 D WOOD ALUM CLEAR TOILET ROOM SIGNAGE RADIUS AT ALL CORNERS 4' - 0 " 4'-0" 3' - 0 " 4' - 0 " SIZE WINDOW HEIGHTWIDTH WINDOW NUMBER A B 4'-0"4'-0"ALUMINUM WINDOW TYPE FRAME MATERIAL ROOM NO. 102 104 REMARKS RF WINDOW AND FRAME PER MANUFACTURER4'-0"4'-0"ALUMINUM WINDOW AND FRAME SCHEDULE FIXED - W2 FIXED - W1MRI CT SCAN ROOM NAME # PROVIDE LEADED GLASS PER PHYSICIST'S RECOMMENDATION 1 A6.4 2 A6.4 9 A6.4 1 A6.4 2 A6.4 5 A6.4 ALL RF WINDOW TO BE COORDINATED WITH RF SUB CONTRACTOR FOR ALL OTHER REQUIREMENTS. W1 W2 RATING 1 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" PLASTIC LAMINATE (*) PLASTIC LAMINATE (*) PLASTIC LAMINATE (*) PLASTIC LAMINATE (*) PLASTIC LAMINATE (*) PLASTIC LAMINATE (*) (*) COLOR TO BE SELECTED BY OWNER PROVIDE 12" X 18" LOUVER; VERIFY W/MRI MANUFACTURER H W W (DOUBLE) T T T T SC H E D U L E D H E I G H T 3' - 0 " SCHEDULED WIDTH 1'-6" 2' - 4 " SOLID SINGLE DOOR F SCHEDULED WIDTH SC H E D U L E D H E I G H T 1 A6.4 2 A6.4 101 LOBBY/RECEPTION PAIR 3'-0"7'-0"A ALUMINUM CHARCOAL ALUMINUM CHARCOAL CT SCAN F SOLID DOUBLE DOOR G SCHEDULED WIDTH SC H E D U L E D H E I G H T 1 A6.4 2 A6.4 STEEL PAINT STEEL PAINT 108 STORAGE 2'-0"F WOOD ALUM CLEAR8'-0"PLASTIC LAMINATE (*) LEADED DOOR AND FRAME PER PHYSICIST'S RECOMMENDATION LEADED DOOR AND FRAME PER PHYSICIST'S RECOMMENDATION E ELECTRICAL ROOM EXISTING TO REMAIN 01 02 03 04 05 06 BY OTHERS 09 10 11 12 5 A6.4 6 A6.4 15 A6.4 13 A6.4 16 A6.4 13 WOOD PLASTIC LAMINATE (*)BI-FOLD 43 " M A X . TO G L A Z I N G 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 GE N E R A L N O T E S G.2 mh 1.THIS PROJECT AND ALL WORK ASSOCIATED WITH PROJECT SHALL CONFORM TO STATE AND LOCAL CODES AND ORDINANCES HAVING JURISDICTION OVER THIS PROJECT. 2.THE TERM "ARCHITECT" OR "DESIGNER" AS USED IN THESE DOCUMENTS REFERS TO SH-PARTNERS. 3.THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCE OF PROCEDURE, OR FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, ALL OF WHICH SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. 4.THE DESIGN ADEQUACY, AND SAFETY OF ERECTION BRACING, SHORING, TEMPORARY SUPPORTS, ETC. DURING DEMOLITION AND/OR CONSTRUCTION IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR, AND HAS NOT BEEN CONSIDERED BY THE STRUCTURAL ENGINEER OR ARCHITECT. 5.THE ARCHITECT ASSUMES NO RESPONSIBILITY FOR THE COMPLETENESS OF PLANS FOR BID PURPOSES PRIOR TO THE ISSUANCE OF THE BUILDING PERMIT. 6.ALL WORK NOTED "N.I.C." OR "NOT IN CONTRACT" IS TO BE ACCOMPLISHED BY A CONTRACTOR OTHER THAN THE GENERAL CONTRACTOR AND IS NOT TO BE PART OF THE CONSTRUCTION AGREEMENT. THE GENERAL CONTRACTOR SHALL COORDINATE WITH "OTHER" CONTRACTORS PER REQUIREMENTS ESTABLISHED BY OWNER AND TENANT. 7.THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS ARE RESPONSIBLE FOR EXAMINING CONTRACT DOCUMENTS, FIELD CONDITIONS, AND CONFIRMING THAT WORK IS BUILDABLE AS SHOWN BEFORE PROCEEDING WITH CONSTRUCTION. IF THERE ARE ANY QUESTIONS REGARDING THESE OR OTHER COORDINATION ITEMS, THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING CLARIFICATION FROM THE ARCHITECT BEFORE PROCEEDING WITH WORK IN QUESTION OR RELATED WORK. 8.CONTRACTOR SHALL MAINTAIN RECORD DOCUMENTS OF CONSTRUCTION CHANGES ("AS-BUILT DRAWINGS") AND SHALL PROVIDE SAID DOCUMENTATION TO THE ARCHITECT UPON COMPLETION OF CONSTRUCTION - NO EXCEPTION ALLOWED. 9.THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE TO COORDINATE WITH ALL SUBCONTRACTORS PER REQUIREMENTS ESTABLISHED BY OWNER, TENANT, OR BOTH, WHICH ARE UNDER SEPARATE CONTRACT WITH THE OWNER, OR TENANT, OR BOTH. 10.THE STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, OTHER DRAWINGS, AND JOB SPECIFICATIONS ARE SUPPLEMENTARY TO ARCHITECTURAL CONSTRUCTION DRAWINGS. ANY DISCREPANCY BETWEEN THESE DOCUMENTS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION. 11.THE INTENT OF DRAWINGS AND SPECIFICATIONS IS TO INCLUDE ALL LABOR, MATERIALS AND SERVICES NECESSARY FOR THE COMPLETION OF ALL WORK SHOWN, DESCRIBED, OR REASONABLY IMPLIED, BUT NOT LIMITED TO THAT EXPLICITLY INDICATED IN THE CONTRACT DOCUMENTS. 12.INSTALL ALL MANUFACTURED ITEMS, MATERIALS, AND EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS, U.O.N. 13.ANY WORK INSTALLED IN CONFLICT WITH THE CONSTRUCTION DRAWINGS, WITHOUT THE PRIOR APPROVAL OF THE OWNER AND THE ARCHITECT SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. 14.THE GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY OF ANY SPECIFIED MATERIALS OR EQUIPMENT WHICH ARE EITHER UNAVAILABLE OR THAT WILL CAUSE A DELAY IN THE CONSTRUCTION COMPLETION SCHEDULE. THE CONTRACTOR SHALL SUBMIT CONFIRMATIONS OF DELIVERY DATES FOR ORDERS OF MATERIALS AND EQUIPMENT HAVING LONG LEAD TIMES. 15.ALL REQUESTS FOR SUBSTITUTIONS OF ITEMS SPECIFIED SHALL BE SUBMITTED IN WRITING AND WILL BE CONSIDERED ONLY IF BETTER SERVICE FACILITIES, A MORE ADVANTAGEOUS DELIVERY DATE, OR A LOWER PRICE WITH CREDIT TO THE OWNER / TENANT WILL BE PROVIDED WITHOUT SACRIFICING QUALITY, APPEARANCE, AND FUNCTION. UNDER NO CIRCUMSTANCES WILL THE ARCHITECT BE REQUIRED TO PROVE THAT A PRODUCT PROPOSED FOR SUBSTITUTION IS OR IS NOT OF EQUAL QUALITY TO THE PRODUCT SPECIFIED. 16.PROJECT SPECIFICATIONS ARE AN INTEGRAL PART OF THESE PLANS - SUBSTITUTIONS FOR SPECIFIED MATERIALS REQUIRE THE WRITTEN APPROVAL FROM THE ARCHITECT. 17.UNLESS OTHERWISE NOTED IN THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL SUBMIT ONE (1) SET OF SHOP DRAWINGS. SHOP DRAWINGS SHOULD INCLUDE DETAILED, FABRICATION AND ERECTION DRAWINGS, SETTING DRAWINGS, DIAGRAMMATIC DRAWINGS, AND MATERIAL SCHEDULES. LOCATION AND ORIENTATION OF ALL ITEMS SHOULD BE CLEARLY INDICATED. BEGIN FABRICATION OF SHOP ITEMS AFTER RECEIVING ARCHITECT'S OR DESIGNER'S APPROVAL OF SHOP DRAWINGS. 18.THE ARCHITECT'S REVIEW OF SHOP DRAWINGS SHALL NOT RELIEVE THE GENERAL CONTRACTOR OR SUBCONTRACTOR FROM RESPONSIBILITY FOR DEVIATIONS FROM THE DRAWINGS OR SPECIFICATIONS UNLESS HE HAS, IN WRITING, AND BROUGHT TO THE ATTENTION OF THE ARCHITECT SUCH DEVIATIONS AT THE TIME OF THE SUBMISSION, NOR SHALL IT RELIEVE HIM (GENERAL CONTRACTOR) FROM RESPONSIBILITY FOR ERRORS OF ANY SORT IN THE SHOP DRAWINGS. 19.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED BUILDING PERMITS PRIOR TO STARTING CONSTRUCTION. 20.PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE APPLICANT SHALL HAVE EVIDENCE OF CURRENT WORKMAN'S COMPENSATION INSURANCE COVERAGE ON FILE WITH THE STATE LABOR DEPARTMENT IN COMPLIANCE WITH CURRENT LABOR CODES. 21.PROVIDE CONTINUOUS INSPECTIONS AS SET FORTH IN STATE AND LOCAL CODES AND PER CONTRACT DOCUMENTS AS NEEDED. 22.PRIOR TO THE ISSUANCE OF FINAL CERTIFICATE OF OCCUPANCY FOR THIS PROJECT, THE GENERAL CONTRACTOR SHALL SUBMIT A SIGNED CERTIFICATE TO THE DEPARTMENT OF BUILDING AND SAFETY STATING THAT ALL WORK HAS BEEN PERFORMED AND MATERIALS INSTALLED ACCORDING TO THE PLANS AND SPECIFICATIONS AFFECTING NON-RESIDENTIAL ENERGY. 23.CONTRACTOR SHALL VERIFY ALL BUILDING STANDARDS WITH BUILDING LANDLORD PRIOR TO BEGINNING ANY WORK. HOWEVER, THERE SHALL BE NO DEVIATIONS WHATSOEVER FROM THE CONTRACTOR DOCUMENTS WITHOUT THE ARCHITECT'S WRITTEN APPROVAL THEREOF. THE CONTRACTOR AGREES TO DEFEND, INDEMNIFY AND HOLD THE ARCHITECT HARMLESS FROM ANY CLAIMS ARISING AS A RESULT OF UNAPPROVED CHANGES. 24.UPON COMPLETION OF CONSTRUCTION, CONTRACTOR IS RESPONSIBLE FOR EMERGENCY RESPONDER RADIO COVERAGE TESTING AND COMPLIANCE. 25.UNLESS OTHERWISE NOTED OR INDICATED, ALL DIMENSIONS ON THESE DOCUMENTS SHALL BE TO FACE OF CURB, FACE OF CONCRETE OR MASONRY, FACE OF FINISH OR CENTERLINE OF GRIDS. 26.ALL VERTICAL DIMENSIONS SHOWN ARE FROM FLOOR SLAB, U.O.N. 27.DIMENSIONS SHOWN IN FIGURES TAKE PRECEDENCE OVER DIMENSIONS SCALED FROM DRAWINGS. LARGE SCALE DRAWINGS AND DETAILS TAKE PRECEDENCE OVER SMALLER SCALE DRAWINGS. 28.THE TERM "ALIGN", AS USED IN THESE DOCUMENTS, SHALL MEAN TO ACCURATELY LOCATE FINISHES IN THE SAME PLANE. 29."TYPICAL" AS USED IN THESE DOCUMENTS SHALL MEAN THAT THE CONDITION IS THE SAME OR REPRESENTATIVE FOR ALL SIMILAR CONDITIONS THROUGHOUT, U.O.N. 30.DETAILS ARE USUALLY KEYED AND NOTED "TYPICAL" ONLY ONCE, WHEN THEY FIRST OCCUR AND ARE REPRESENTATIVE OF ALL SIMILAR CONDITIONS THROUGHOUT, U.O.N. 31.COLUMN CENTERLINES (GRID LINES) ARE SHOWN FOR DIMENSIONING PURPOSES. 32.WHERE CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, THE DETAILS SHALL BE THE SAME AS FOR OTHER SIMILAR WORK IN THE SAME BUILDING. 1.WHERE EXISTING TENANTS/BUSINESSES ARE ADJACENT TO THE JOB SITE/TENANT, THE CONTRACTOR SHALL MINIMIZE CONSTRUCTION NOISE - EXTREME NOISE CONSTRUCTION SHALL OCCUR AT NON-TYPICAL BUSINESS HOURS. CONTRACTOR SHOULD NOTIFY BUILDING REPRESENTATIVE OF SPECIAL CIRCUMSTANCES IN ADVANCE PRIOR TO WORK. 2.THE CONTRACTOR AT HIS OWN EXPENSE, SHALL KEEP THE PROJECT AND SURROUNDING AREA FREE FROM DUST AND DEBRIS. THE WORK SHALL BE IN CONFORMANCE WITH THE AIR AND WATER POLLUTION CONTROL STANDARDS AND REGULATIONS OF THE STATE DEPARTMENT OF HEALTH. 3.CONSTRUCTION DEBRIS AND WASTES SHALL BE DEPOSITED AT AN APPROPRIATE SITE. THE CONTRACTOR SHALL INFORM THE BUILDING REPRESENTATIVE OF THE LOCATION OF DISPOSAL SITES. 4.CONTRACTOR SHALL BE RESPONSIBLE FOR THE GENERAL CLEANING OF THE JOB AFTER ITS COMPLETION. WHERE APPLICABLE, CLEANING SHALL INCLUDE, BUT NOT BE LIMITED TO, THE EXTERIOR AND THE INTERIOR OF THE BUILDING, THE PATH OF TRAVEL TO THE JOB SITE, PARKING LOTS, ELEVATORS, LOBBIES, AND CORRIDOR CARPETS. 5.THE CONTRACTOR SHALL PROVIDE PEDESTRIAN PROTECTION, WHERE REQUIRED PER STATE AND LOCAL CODES. 6.IF TRENCHES OR EXCAVATIONS 5'-0" OR MORE IN DEPTH ARE REQUIRED, OBTAIN ISSUANCE OF A BUILDING OR GRADING PERMIT. 7.NO HAZARDOUS MATERIALS SHALL BE USED OR STORED WITHIN THE BUILDING WHICH DOES NOT COMPLY WITH THE LOCAL FIRE AUTHORITY AND STATE & COUNTY REQUIREMENTS. 8.CONTRACTOR SHALL BE RESPONSIBLE FOR BLOCKING OFF SUPPLY AND RETURN AIR GRILLES, DIFFUSERS & DUCTS TO KEEP DUST FROM ENTERING INTO BUILDING AIR DISTRIBUTION SYSTEMS. 9.BUILDINGS UNDERGOING CONSTRUCTION, ALTERATION OR DEMOLITION SHALL BE DONE SO IN ACCORDANCE WITH STATE & LOCAL CODES. 10.THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO ENSURE THE SAFETY OF THE OCCUPANTS AND WORKERS AT ALL TIMES. 11.THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE SECURITY OF THE BUILDING AND SITE WHILE JOB IS IN PROGRESS AND UNTIL THE JOB IS COMPLETED. 12.WHERE ELECTRICAL, MECHANICAL AND/OR PLUMBING ITEMS, SUCH AS LIGHTS, DUCTS, PIPING, DOWNSPOUTS, ETC. ARE TO PENETRATE ANY BUILDING FOOTINGS, SLABS, FLOORS, STRUCTURAL FRAMING, WALL PARTITIONS, CEILINGS, ETC., IT IS REQUIRED THAT AN APPROPRIATELY SIZED OPENING OR CLEARANCE BE FURNISHED. CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL ITEMS WITH THE CONSTRUCTION DOCUMENTS PRIOR TO THE INSTALLATION OF STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL WORK. ANY CONFLICT OR DISCREPANCY WITHIN CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION FOR CLARIFICATION. 13.CONTRACTOR, ALONG WITH MECHANICAL CONTRACTOR, SHALL PROVIDE AND LOCATE ACCESS DOORS/PANELS IN WALL & CEILING CONSTRUCTION AS REQUIRED TO PROVIDE ACCESS TO MECHANICAL, FIRE SPRINKLER, PLUMBING & ELECTRICAL WORK. CONTRACTOR SHALL SUBMIT A PLAN OF ALL PROPOSED ACCESS PANEL LOCATIONS TO ARCHITECT FOR APPROVAL PRIOR TO INSTALLATION. 14.ALL PENETRATIONS AT RATED CONSTRUCTION SHALL BE PROTECTED TO MAINTAIN RATING. 15.WHERE OCCURS, CONTRACTOR SHALL PATCH ANY EXISTING WALLS AND/OR CEILINGS AS NEEDED TO REFURBISH THE LEASE SPACE AND REPAIR ALL DAMAGES CAUSED BY CONTRACTOR. 16.INTERIOR WALLS AND CEILINGS SHALL BE INSTALLED IN ACCORDANCE TO STATE & LOCAL CODES, INCLUDING REQUIREMENTS FOR FLAME SPREAD AND SMOKE DENSITY RATINGS FOR FINISH MATERIALS. 17.WHEN USED, ALL NOISE BARRIER BATTS (SOUND INSULATION) AND INSULATION BATTS SHALL BE NON-COMBUSTIBLE AND SHALL NOT CONTAIN OR UTILIZE OZONE DEPLETING COMPOUNDS. 18.ALL NEW CONSTRUCTION MATERIALS SHALL BE 100% ASBESTOS-FREE. 19.OUR FIELD VERIFICATION IS BASED ON THOSE BUILDING ELEMENTS WHICH ARE IMMEDIATELY AND READILY VISIBLE WITHOUT THE USE OF DEMOLITION OR REMOVAL OF ANY PERMANENT ELEMENTS. GENERAL NOTES:job site notes: SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H DS/MH 23-16 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 4/G.4 N/A N/A 800 N. TUSTIN AVE., SANTA ANA, CA TENANT IMPROVEMENT A6.4 800 N Tustin Ave Unit #H1/23/2025 DOORS, DOORWAYS & GATES 1/4"=1'-0"DOOR CLEARANCES 18" MIN. @ INTERIOR DOOR 60 " M I N . (A) FRONT APPROACH, PULL SIDE 12" MIN * 48 " M I N . (*) IF BOTH CLOSER AND LATCH ARE PROVIDED 36" MIN. 60 " M I N . (D) HINGE APPROACH, PULL SIDE 22" MIN. 44 " M I N . * (F) (G*) HINGE APPROACH, PUSH SIDE 24" MIN.60 " M I N . (H) LATCH APPROACH, PULL SIDE 24" MIN. 44 " M I N . * (J) (K*) LATCH APPROACH, PUSH SIDE (B) (C*) FRONT APPROACH, PUSH SIDE (*) 48" MIN. IF BOTH CLOSER AND LATCH PROVIDED. (*) 48" MIN. IF CLOSER IS PROVIDED. MANEUVERING CLEARANCE AT MANUAL SWINGING DOORS AND GATES 18" MIN. @ INTERIOR60 " M I N . X > 8 " (A) PULL SIDE MANEUVERING CLEARANCE AT RECESSED DOORS AND GATES 48 " M I N . X > 8 " (B) PUSH SIDE 48 " M I N . X > 8 " (C) PUSH SIDE, DOOR PROVIDED WITH BOTH CLOSER AND LATCH 12" MIN. 24" MIN. @ EXTERIOR SIDE OF EXTERIOR DOOR 24" MIN. @ EXTERIOR 32" MIN.32" MIN.32" MIN. 90 (A) HINGED DOOR (B) SLIDING DOOR (C) FOLDING DOOR CLEAR WIDTH OF DOORWAYS 1.FLOOR OR GROUND SURFACE WITHIN REQUIRED MANEUVERING CLEARANCES SHALL HAVE A SLOPE NOT STEEPER THAN 1:48. CHANGES IN LEVEL ARE NOT PERMITTED AT DOOR LANDINGS. 2.THRESHOLDS, IF PROVIDED AT DOORWAYS SHALL BE 1/2" HIGH MAX. RAISED THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS SHALL COMPLY WITH DETAIL 10. 3.HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERABLE PARTS ON DOORS AND GATES SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OR THE WRIST. 4.THE FORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 LBS (22.5 N) MAX. 5.OPERABLE PARTS OF DOOR HARDWARE SHALL BE 34" MIN. AND 44" MAX. ABOVE THE FINISH FLOOR OR GROUND. 6.WHERE SLIDING DOORS ARE IN THE FULLY OPEN POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES. 7.DOOR AND GATE CLOSERS SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 90° THE TIME REQUIRED TO MOVE THE DOOR TO A POSITION OF 12° FROM THE LATCH IS 5 SECONDS MIN. 8.DOOR AND GATE SPRING HINGES SHALL BE ADJUSTED SO THAT FROM THE OPEN POSITION OF 70° THE DOOR OR GATE SHALL MOVE TO THE CLOSED POSITION IN 1.5 SECONDS MIN. 9.THE FORCE FOR PUSHING OR PULLING OPEN A DOOR OR GATE SHALL BE AS FOLLOWS: 9.1.INTERIOR HINGED DOORS AND GATES: 5 LBS (22.5 N) MAX. 9.2.SLIDING OR FOLDING DOORS: 5 LBS (22.5 N) MAX. 9.3.REQUIRED FIRE DOORS: THE MINIMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE ADMINISTRATIVE AUTHORITY, NOT TO EXCEED 15 LBS (66.7 N). 9.4.EXTERIOR HINGED DOORS: 5 LBS (22.5 N) MAX. 10.SWINGING DOOR AND GATE SURFACES WITHIN 10" OF THE FINISH FLOOR OR GROUND MEASURED VERTICALLY SHALL HAVE A SMOOTH SURFACE ON THE PUSH SIDE EXTENDING THE FULL WIDTH OF THE DOOR OR GATE. PARTS CREATING HORIZONTAL OR VERTICAL JOINTS IN THESE SURFACE SHALL BE WITHIN 1/16" OF THE SAME PLANE AS THE OTHER AND BE FREE OF SHARP OR ABRASIVE EDGES. CAVITIES CREATED BY ADDED KICK PLATES SHALL BE CAPPED. 11.WHERE AUTOMATIC AND POWER-ASSISTED DOORS AND GATES WITHOUT STANDBY POWER ARE PART OF A MEANS OF EGRESS THE CLEAR BREAK OUT OPENING AT SWINGING OR SLIDING DOORS AND GATES SHALL BE 32" MIN. WHEN OPERATED IN EMERGENCY MODE. DOORS, DOORWAYS & GATES 1/4"=1'-0"Door in Series 48" MIN.48" MIN. (A)(B) 48" MIN. (C) FIG. 11B-404.2.4.6 DOORS IN SERIES AND GATES IN SERIES MOUNTING HEIGHTS 1/4"=1'-0"Mounting Height EQUIPMENT PERMITTED IN SHADED AREA FRONT & SIDE APPROACH INSULATE EXPOSED PIPES AND SURFACES 18"-19" 36 " M A X . 27 " MI N . 9" M I N . 6" MAX. 8" MIN. 38 " - 4 3 " 36 " M A X . 24" MAX 17" MIN 6" MAX. 8" MIN. 29 " M I N 27 " MI N . 34 " MA X . 9" M I N . 15" MIN 30" CLR FORWARD APPROACH 13-1/2" MIN. 17 " M A X . 44 " MA X . 6' - 2 " M I N . 40 " M A X . 34 " M A X . 18" MIN. 6' - 2 " M I N . 35 " M A X . 40 " M A X MIN 19"28 " - 3 4 " 27 " MI N . SPOUT OUTLETSPOUT OUTLET15" MIN.5" MAX. MIRROR @ LOCKER ROOMS 54 " M I N . 20 " MA X . 18" MIN WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN MIRROR NOT OVER A LAVATORY FIXED TABLE OR COUNTER STANDING DRINKING FOUNTAIN URINALLAVATORY ACCESSORIESMIRROR @ LAVATORY & CHANGES IN LEVEL N.T.S.Floor Sruface Level 1/ 4 " 1/ 4 " 1/ 2 " MA X . 1/ 4 " M A X . 1/2" MAX. 1/ 2 " MA X . FLOOR OR GROUND SURFACES DOMINANT DIRECTION OF TRAVEL LONG DIMENSION PERPENDICULAR TO DOMINANT DIRECTION OF TRAVEL FIG. 302.3 ELONGATED OPENINGS IN FLOOR OR GROUND SPACE FIG. 302.2 CARPET PILE HEIGHT FIG. 303.2 VERTICAL CHANGE IN LEVEL FIG. 303.3 BEVELED CHANGE IN LEVEL 2 1 NOTES: 1.FLOOR AND GROUND SURFACES SHALL BE STABLE, FIRM AND SLIP RESISTANT. 2.CARPET OR CARPET TILE SHALL BE SECURELY ATTACHED AND SHALL HAVE A FIRM CUSHION, PAD OR BACKING OR NO CUSHION OR PAD. CARPET OR CARPET TILE SHALL HAVE A LEVEL LOOP, TEXTURED LOOP, LEVEL CUT PILE, LEVEL CUT/UNCUT PILE TEXTURE. PILE HEIGHT SHALL COMPLY WITH CARPET PILE HEIGHT FIGURE BELOW. EXPOSED EDGES OF CARPET SHALL BE FASTENED TO FLOOR SURFACES AND SHALL HAVE TRIM ON THE ENTIRE LENGTH OF THE EXPOSED EDGE. CARPET EDGE SHALL COMPLY WITH CHANGE IN LEVEL FIGURES BELOW. DOORS, DOORWAYS & GATES 1/4"=1'-0"doorway and gate 48 " M I N . (a) FRONT APPROACH 24" MIN. 42 " M I N . (b) SIDE APPROACH MANEUVERING CLEARANCE AT DOORWAYS WITHOUT DOORS, SLIDING DOORS, GATES AND FOLDING DOORS 22" MIN.42 " M I N . (c) POCKET OR HINGE APPROACH (d) STOP OR LATCH APPROACH 11B-404.2.4.2 GRAB BARS N.T.S.Grab bars POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR CHILDREN'S USE, GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION 18 INCHES MINIMUM AND 27 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. 12 " M I N . 1- 1 / 2 " M I N . (A) PROJECTING OBJECTS (B) RECESSED OBJECTS SPACING. THE SPACE BETWEEN THE WALL AND THE GRAB BAR SHALL BE 1-1/2 INCHES. THE SPACE BETWEEN THE GRAB BAR AND PROJECTING OBJECTS BELOW AND AT THE ENDS SHALL BE 1-1/2 INCHES MINIMUM. THE SPACE BETWEEN THE GRAB BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES MINIMUM. CIRCULAR CROSS SECTION. GRAB BARS WITH CIRCULAR CROSS SECTIONS SHALL HAVE AN OUTSIDE DIAMETER OF 1-1/4 INCHES MINIMUM AND 2 INCHES MAXIMUM. SPACING OF GRAB BARS FIG. 11B-609.3 609.4 609.3 609.2.1 4"-4.8" PERIMETER 2" MAX. 2" M A X . (A)(B) GRAB BAR NON-CIRCULAR CROSS SECTION FIG. 609.2.2 1-1/2" CLEAR FLOOR OR GROUND SPACE 1/2"=1'-0"Floor space 48" MIN. 30 " M I N . 36" MIN.12" MIN. 12" MIN. 60" MIN. 24 " M I N . 60 " M I N . 36 " M I N . BASE AR M AR M T-SHAPED TURNING SPACE SIZE AND POSITION OF CLEAR FLOOR SPACE Ø60" MIN CIRCULAR TURNING SPACE X > 2 4 " 36" MIN. X > 1 5 " 60" MIN. MANEUVERING CLEARANCE IN AN ALCOVE, FORWARD APPROACH MANEUVERING CLEARANCE IN AN ALCOVE, PARALLEL APPROACH 48 " M I N . 30" MIN. (B) PARALLEL(A) FORWARD 48" MIN. 30 " M I N . SIZE OF CLEAR FLOOR SPACE REACH RANGES 1/4"=1'-0"Reach Range 15 " M I N . 48 " M A X . 48 " M A X . 44 " M A X . (A)(B) 20" MAX.>20"-25" MAX. 15 " M I N . 48 " M A X . 48 " M A X . 46 " M A X . 10" MAX.> 10"- 24" MAX. FIG. 308.3.1 FIG. 308.3.2 FIG. 308.2.2FIG. 308.2.1 UNOBSTRUCTED FORWARD REACH OBSTRUCTED HIGH FORWARD REACH OBSTRUCTED HIGH SIDE REACHUNOBSTRUCTED HIGH SIDE REACH KNEE AND TOE CLEARANCE 1/4"=1'-0"Knee toe clear 9" M I N . 17"-25"6" MAX. 30 " MI N . (A) ELEVATION (B) PLAN 11" MIN. 8" MIN. 27 " MI N . 9" M I N . (A) ELEVATION (B) PLAN 30 " MI N . 25" MAX. FIG. 11B-306.2 TOE CLEARANCE FIG. 11B-306.3 KNEE CLEARANCE 11" MIN. 8" MIN. 27 " MI N . 9" M I N . (C) ELEVATION @ LAVATORY 29 " M I N . COMPARTMENTS & URINALS 1/4"=1'-0"Water_closet_urinal 56 " M I N . 60" MIN. 17"-18"17"-19" (A) WHEELCHAIR ACCESSIBLE WATER CLOSETS (B) AMBULATORY ACCESSIBLE WATER CLOSETS SIZE OF CLEARANCE AT WATER CLOSETS 42" MIN. 12" MAX. 54" MIN. TRANSFER SIDE 24" MIN.12" MIN. SIDE WALL GRAB BAR AT WATER CLOSETS REAR WALL GRAB BAR AT WATER CLOSETS 19 " 7"-9" (B) STALL TYPE (A) WALL HUNG TYPE 17 " M A X . 13-1/2" MIN. HEIGHT AND DEPTH OF URINALS 36" MIN. WATER CLOSETS AND TOILET FIG. 11B-604.2 FIG. 11B-604.3.1 FIG. 11B-604.5.1 FIG. 11B-604.5.2 FIG. 11B-605.2 FIG. 11B-604.7 9" MI N . 6" MIN. 6" MI N . 12 " MI N . 6" MIN. 35"-37" 44 " M I N . AMBULATORY ACCESSIBLE TOILET COMPARTMENT FIG. 11B-604.8.2 WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT TOE CLEARANCES FIG. 11B-604.8.1.4 (A) ELEVATION ADULT (B) ELEVATION CHILDREN (C) PLAN PARTITION PARTITION 6" MIN. 13-1/2" MIN. CLEARANCE DOOR PERMITTED TO SWING OVER HATCHED PORTION OF MANEUVERING SPACE 48 " M I N . 4" MAX. 4" MA X . ALTERNATE DOOR LOCATION WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT DOORS FIG. 11B-604.8.1.2 56" MIN. @ WALL MOUNTED WATER CLOSET 59" MIN. @ FLOOR MOUNTED WATER CLOSET 48" MIN. MANEUVERING SPACE CLEARANCE 56" MIN. @ WALL MOUNTED WATER CLOSET 60 " M I N . 59" MIN. @ FLOOR MOUNTED WATER CLOSET 48" MIN. MANEUVERING SPACE CLEARANCE 36" MIN. WHEN DOOR SWINGS IN 60 " M I N . DISPENSER OUTLET LOCATION DOOR PERMITTED TO SWING OVER HATCHED PORTION OF MANEUVERING SPACE 56" MIN. @ WALL MOUNTED WATER CLOSET 59" MIN. @ FLOOR MOUNTED WATER CLOSET 60" MIN. @ SIDE DOOR MANEUVERING SPACE CLEARANCE 60 " M I N . 56" MIN. @ WALL MOUNTED WATER CLOSET 59" MIN. @ FLOOR MOUNTED WATER CLOSET 60" MIN. MANEUVERING SPACE CLEARANCE 60 " M I N . 36" MIN. WHEN DOOR SWINGS IN DOOR PERMITTED TO SWING OVER HATCHED PORTION OF MANEUVERING SPACE MANEUVERING SPACE WITH END-OPENING DOOR FIG. 11B-604.8.1.1.3 WATER CLOSET LOCATION 17 " - 1 9 " 34" MIN. 4" MAX. 34" MIN. 4" MAX. A DOOR PULL SHALL BE PLACED ON BOTH SIDES OF THE DOOR NEAR THE LATCH SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H AC C E S S I B I L I T Y D E T A I L S G.3 mh DS/MH 23-16 3 812 11 10 913 15 16 4 800 N Tustin Ave Unit #H1/23/2025 "NO SMOKING" SIGN N.T.S.No_smoking SANS-SERIF UPPERCASE CHARACTERS CHARACTERS & BACKGROUND OF SIGNS TO BE NON-GLARE FINISH AND TO CONTRAST WITH EACH OTHER. SMOKING IS PROHIBITED WITHIN 25 FEET OF THIS AREA 10" (*) 7" ( * ) * OR SIZE PER LOCAL REQUIREMENTS TACTILE "EXIT" SIGN 3"= 1'-0"Exit BRAILLE MEASUREMENT N.T.S.Braille 0.300" 0.100" SINGLE BRAILLE CELL 0. 1 0 0 " 0. 3 9 5 " M I N . 0. 4 0 0 " M A X .0.059" MIN. TO 0.063" MAX. BLANK CELL SPACE BETWEEN WORDS RAISED DOT NO RAISED DOT FIG. 703.3.1 DOT HEIGHT 0.025" MIN. TO 0.037" MAX. MEASURED CENTER TO CENTER. GEOMETRIC SYMBOLS N.T.S.Geometric_symbols DOOR ELEVATION EQ. MO U N T 6 0 " A F F TO C E N T E R L I N E OF S I G N EQ. all gender MEN'SWOMEN'S (DOOR MOUNTED) WOMEN'S & MEN'S SIGNAGE 1/4" THICK SOLID SURFACE DOOR-MOUNTED SIGNAGE TO BE LOCATED IN CENTER OF DOOR. TRIANGLE SYMBOL AND CIRCLE SYMBOL SHALL CONTRAST WITH DOOR. UNISEX SIGNAGE 1/4" THICK SOLID TRIANGLE SUPERIMPOSED ON THE 1/4" THICK SOLID CIRCLE SURFACE. TRIANGLE SYMBOL SHALL CONTRAST WITH CIRCLE SYMBOL. CIRCLE SYMBOL SHALL CONTRAST WITH DOOR. DOOR SIGNAGE EDGES OF SIGNS SHALL BE ROUNDED, CHAMFERED OR EASED. CORNERS OF SIGNS SHALL HAVE A MINIMUM RADIUS OF 1/8" 12" AL L S I D E S 10" 12"Ø SEC. 11B-703.7.2.6 SEE DETAIL 7 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L AC C E S S I B I L I T Y D E T A I L S G.4 mh DS/MH 23-16 SIGNS N.T.S.Signs REFUGE AREA OF AREA OF REFUGE 48 " M I N . 60 " M A X . AREA OF REFUGE 3/ 8 " - 1 / 2 " 3/ 8 " MI N . 1' - 6 " MI N . 45 ° 5/ 8 " - 2 " LIBRARY HEIGHT OF RAISED CHARACTERS FIG. 11B-703.2.5 POSITION OF BRAILLE FIG. 11B-703.3.2 HEIGHT OF TACTILE CHARACTERS ABOVE FINISH FLOOR OR GROUND FIG. 11B-703.4.1 1'-6" MIN. CENTERED ON TACTILE CHARACTERS LOCATION OF TACTILE SIGNS AT DOORS FIG. 11B-703.4.2 2 37 6 5 SEE DETAIL 2 FOR LOCATION MI N . 4 8 " A . F . F . TO B A S E L I N E O F TH E L O W E S T T A C T I L E CH A R A C T E R RESTROOM MA X . 6 0 " A . F . F . TO B O T T O M O F T O P L I N E O F T E X T SCALE: WALL MOUNTED SIGNAGE N.T.S. 8 EXIT RAISED CHARACTERS SHALL BE A MINIMUM OF 5/8" AND MAXIMUM OF 2" HIGH. FLOOR LEVEL 1/8" THICK PHOTOPOLYMER WORDING TO READ AS: 1: EXIT 2: TO EXIT 3: EXIT ROUTE 4: EXIT STAIR DOWN 5: EXIT RAMP DOWN 6: EXIT STAIR UP 7: EXIT RAMP UP CALIFORNIA GRADE 2 BRAILLE: DOTS SHALL BE SPACED 1/10" ON CENTERS IN EACH CELL W/ 2/10" SPACE BETWEEN CELLS. DOTS SHALL BE RAISED A MIN. OF 1/40" ABOVE BACKGROUND 3/ 8 " M I N . 1 / 2 " M A X . MI N . 4 8 " A . F . F . TO B O T T O M O F LO W E S T L I N E O F B R A I L L E 6" 6" 41 1 di g i t a l s t a m p & s i g n a t u r e , d a t e 1 2 - 0 4 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 S-0 GE N E R A L N O T E S XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 800 N Tustin Ave Unit #H1/23/2025 S-0.1 GE N E R A L N O T E S XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 800 N Tustin Ave Unit #H1/23/2025 3 B A 2 5142.2 S-1.0 FO U N D A T I O N P L A N XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 R-1 10-28-2024 9980 Indiana Avenue ● Suite 14 ● Riverside ● California ● 92503 ● Phone (951) 688-5400 ● Fax (951) 688-5200 5714 West 96th Street ● Los Angeles ● California ● 90045 ● Phone (310) 590-6699 November 5, 2024 Project No.: 24264-01 United Medical Imaging Healthcare 800 North Tustin Street Unit H Santa Ana, California 92705 SUBJECT: Foundation Plan Review 800 North Tustin Street Unit H Santa Ana, California 92705 REFERENCE: FA Structural Engineering, UMIH Satna Ana, 800 North Tustin Street, Unit H, Santa Ana, Foundation Plan, Sheet S-1.0 Dated October 28, 2024 and Foundation Details Sheet S-2.0 Dated July 1, 2024, Project No. 35-24. As requested by you, this letter presents the results of our review of the above-referenced foundation plan and details. The subject site is an existing one story commercial building built sometime in 1977 and based on the provided plan, the building is supported on shallow foundation and slab on grade. The proposed improvement is located on the south side, inside Unit H of the building. The proposed improvement is a lightly loaded continuous footing and concrete slab to fill the cutout gap. The details show the slab is doweled into the footing. The proposed footing as shown on the plan is 24 inches deep. This depth of footing is applicable for the anticipated light loads. Should you have any questions, please do not hesitate to call this office. Submitted for GeoMat Testing Laboratories, Inc. Haytham Nabilsi, GE 2375 Project Engineer haytham@geomatlabs.com GeoMat Testing Laboratories, Inc Geotechnical Engineering/ Material Testing www.geomatlabs.com info@geomatlabs.com di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 3 B A 2 5142.2 S-1.1 RO O F F R A M I N G P L A N XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 R-1 10-28-2024 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 S-2.0 FO U N D A T I O N D E T A I L S XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 R-1 10-28-2024 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 1 2 DO NOT cut or notch flange. DO NOT cut holes in cantilever reinforcement. 13"11"87 8"61 2"3" 4"2"13"11"87 8"61 2"3"4" ROUND HOLE SIZE 2" TJIDEPTH 360 360 117 8" 117 8" Table A - End Support Minimum distance from edge of hole to inside face of nearest end support Table B - Intermediate or Cantilever Support SQUARE OR RECTANGULAR HOLE SIZE Minimum distance from edge of hole to inside face of nearest intermediate or cantilever support Rectangular holes based on measurement of longest side. S-3.0 RO O F F R A M I N G DE T A I L S XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 R-1 10-28-2024 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 SHEAR WALL & HOLD-DOWNB HOLD-DOWNS AT DIFF. WALL CONDITIONSA HOLD-DOWN STRAP BETWEEN FLOORSD HOLD-DOWN IN-BETWEEN FLOORSE HOLD-DOWN TO FOUNDATIONC S-4.0 DE T A I L S XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 800 N Tustin Ave Unit #H1/23/2025 S-4.1 DE T A I L S XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 800 N Tustin Ave Unit #H1/23/2025 9980 Indiana Avenue ● Suite 14 ● Riverside ● California ● 92503 ● Phone (951) 688-5400 ● Fax (951) 688-5200 5714 West 96th Street ● Los Angeles ● California ● 90045 ● Phone (310) 590-6699 November 5, 2024 Project No.: 24264-01 United Medical Imaging Healthcare 800 North Tustin Street Unit H Santa Ana, California 92705 SUBJECT: Foundation Plan Review 800 North Tustin Street Unit H Santa Ana, California 92705 REFERENCE: FA Structural Engineering, UMIH Satna Ana, 800 North Tustin Street, Unit H, Santa Ana, Foundation Plan, Sheet S-1.0 Dated October 28, 2024 and Foundation Details Sheet S-2.0 Dated July 1, 2024, Project No. 35-24. As requested by you, this letter presents the results of our review of the above-referenced foundation plan and details. The subject site is an existing one story commercial building built sometime in 1977 and based on the provided plan, the building is supported on shallow foundation and slab on grade. The proposed improvement is located on the south side, inside Unit H of the building. The proposed improvement is a lightly loaded continuous footing and concrete slab to fill the cutout gap. The details show the slab is doweled into the footing. The proposed footing as shown on the plan is 24 inches deep. This depth of footing is applicable for the anticipated light loads. Should you have any questions, please do not hesitate to call this office. Submitted for GeoMat Testing Laboratories, Inc. Haytham Nabilsi, GE 2375 Project Engineer haytham@geomatlabs.com GeoMat Testing Laboratories, Inc Geotechnical Engineering/ Material Testing www.geomatlabs.com info@geomatlabs.com 800 N Tustin Ave Unit #H1/23/2025 www.fastructural.com Email : atefg@fastructural.com T: +1 714.519.5027 STRUCTURAL ENGINEERING AND CONSULTING 800 N Tustin St., Santa Ana, CA 92705 Projecct # 35-24 STRUCTURAL CALCULATIONS Date Rev. : R1 # Pages : 27 10/28/2024 800 N Tustin Ave Unit #H1/23/2025 CALCULATION INDEX PART / TITLE Page 1. Gravity Criteria 1 2. Building Weight 2 3. Wind Analysis 3 4. Seismic Analysis Site Latitude & Longitude 4 Spectral Response Coefficients 5 Seismic Analysis 2012 IBC 6 5. Lateral Force Distribution 7 6. Wood Shearwall Design Shearwall Design Tables 9 Shearwall Description 10 Shearwall Design 11 7. Beam Design Beam Design Tables 13 Simply Supported Beam Design 14 8. Column Design Column Loads Wood Column Design 27 35-24 UMIH Suite H_SANTA ANA_R0.xls, Calculation Index 800 N Tustin Ave Unit #H1/23/2025 GRAVITY LOADS 2.00 psf 2.25 psf 4.20 psf 1.50 psf 9.95 psf 10.00 psf 3.00 psf 2.25 psf 3.15 psf 3.00 psf 1.60 psf 13.00 psf 100.00 psf 2.10 psf 3.00 psf 3.00 psf 8.00 psf 20.00 psf 10.00 psf 2.81 psf 1.58 psf 0.50 psf 3.00 psf 18.00 psf 3.00 psf 1.05 psf 2.81 psf 3.00 psf 10.00 psf Insulation Fiber Glass Rigid Wall Wood Studs 2x6 @ 16" O.C. DF-Larch EXTERIOR WALL INTERIOR WALL Drywall Finish INTERIOR WALL LOAD Drywall Finish Sheathing 15/32" Plywood Wall Wood Studs 2x4 @ 16" O.C. DF-Larch Insulation Fiber Glass Loose EXTERIOR WALL LOAD Framing 2x12 @ 12" O.C. DF-Larch Sheathing 3/4" T&G ROOF LIVE LOAD TOTAL ROOF DEAD LOAD TOTAL OPEN DECK DEAD LOAD DEAD LOAD ROOF LOADS Roofing Shingles Asphalt (1/4 in) DECK DEAD LOAD TOTAL Sheathing 3/4" T&G Flooring Hardwood (1 in) CEILING DEAD LOAD TOTAL Miscellaneous Framing 2x 8 @ 16" O.C. DF-Larch CEILING LIVE LOAD TOTAL Drywall Finish CEILING LOADS Wall Plaster (1 in) on Metal Lath DEAD LOAD Sheathing 15/32" Plywood Drywall Finish Framing 2x12 @ 16" O.C. DF-Larch Drywall Finish DECK LIVE LOAD TOTAL Miscellaneous 35-24 UMIH Suite H_SANTA ANA_R0.xls, Gravity Loads Page 1 800 N Tustin Ave Unit #H1/23/2025 BUILDING WEIGHT DESIGN CRITERIA Code Used : 2022 CBC Concrete F'c : 2,500 psi Building Code : 2021 IBC Steel Fy : 60,000 psi LACity Requirement : Yes v SOILS REPORT NO SOILS REPORT Bearing Capacity : 1,500 psf SEISMIC DESIGN PARAMETERS Short Period, Fa :1.2 0.2 sec Fig 1613.5(1) Latitude : 33.752258 Long Period, Fv :1.5 1.0 sec Fig 1613.5(2) Longitude :-117.834959 Response Spectral : 129.40% 0.2 sec Fig 1613.5(3) Site Class : D Response Spectral : 46.10% 1.0 sec Fig 1613.5(4) BUILDING SUMMARY Level Height Elevation Unit Weight psf Wall Weight ft Dead Live Type psf ROOF 15.00 15.00 9.95 10.00 Exterior 18.00 Interior 10.00 BUILDING WEIGHT ROOF Area Type L (ft) W (ft) H (ft) Area (ft^2) Dead Load (psf) Weight (kips) Roof 6,510.8 9.95 64.78 Ext. Wall 62.00 24.00 7.50 18.00 11.61 Int. Wall 124.00 48.00 7.50 10.00 12.90 TOTAL ROOF AREA / LOAD 6,510.8 89.29 35-24 UMIH Suite H_SANTA ANA_R0.xls, Building Weight Page 2 800 N Tustin Ave Unit #H1/23/2025 27.5 Directional Procedure, Part 2: Enclosed Simple Diaphragm Buildings With H ≤ 160 Ft T-27.6-2 (psf) X oof Exp adjust factor T-27.6-2 = 1 0.00 Ph =21.80 Ph = 25.20 P0 =21.80 P0 =25.20 62 24 Example will work for V =110, 115 and 120 MPH only. Wind Normal to Ridge Wind Parallel to Ridge Roof Height h =15 feet Exposure C Roof Pitch =0.00 :12 Topography factor Kzt =1.00 26.8.2, Figure 26.8-1 Building & Structure Risk Category = IBC T-1604.5 Wind Speed V = 110 mph Fig. 26.5-1A, MRI = 700 yrs Wind Normal to Ridge, L/B = 2.583 use 2.0 Wind Parallel to Ridge, L/B = 0.39 use 0.5 Since .2 ≤ L/B ≤ 5.0 = Yes Since .2 ≤ L/B ≤ 5.0 = Yes and h ≤ 60 = Yes and h ≤ 60 = Yes Building meet Class I condition ? Yes Building meet Class I condition ? Yes  Since .5 ≤ L/B ≤ 2.0 = No Since .5 ≤ L/B ≤ 2.0 = No and 60 ≤h ≤1 60 = No and 60 ≤h ≤1 60 = No Fundamental period =0.500 sec Fundamental period =0.500 sec More than h/75 sec. NG More than h/75 sec. NG Building meet Class II condition ? No Building meet Class II condition ? No From T-27.6-1, V = 110 MPH Exp C, L/B =2.0 and 15 FT. HT From T-27.6-1, V = 110 MPH Exp C, L/B =0.5 and 15 FT. HT Ph =21.80 Kzt Ph =25.20 Kzt Po =21.80 Kzt Po =25.20 Kzt T-27.6-2 V =110 Exp C, h =15 Roof slope =0:12 Zone 1 =-23.5 Adjust factor T-27.6-2, = 1.00 Design roof pressure for zone 1 = -23.50 PSF Wind Base Shear = 7.85 kips Wind Base Shear = 23.44 kips II, standard == 35-24 UMIH Suite H_SANTA ANA_R0.xls, Wind Analysis MWFR<160ft Page 3 800 N Tustin Ave Unit #H1/23/2025                                    !"##$      %&'()*+,-.(/'01.,6778 9 : :;#!7<:=5 ??!<##<6:"@@!6?A;<;@<< #7#A"7G"#G@!H77H?#<!<I5  M.)P/&,05  !"@G(L5 SST"  &(4X'CP& O&4)(1F01.,@#;A Y Z[ M  \  ]7#^7AG@ Y Z[ M  \  ]@7^@<<?  "M        9  _  "M        9  @7?< 8M  M [9   7#_ 8M  M [9   @7@@A6-.(/'01.,X'CP& O&4)(1F01.,_  M [ [ @#  M     7#_  M     @77;?<      \7#^7;#6      \@7^7<A@ Y a [    @#  M     a7G<  M   [    6  ["       \^@#;A     "  [ [ M  \7#^@?6A $  M"       \#b     c  <7  ^@< $  M    9  \7#^7AG@     "  [ [ M  \@7^7A;! $  M"       \#b     c  <7  ^7G $  M    9  \@7^7<A< $  M    9  \a^@@A6 ‚ƒƒ„…†‡ˆ‰‡Š‡‹Œ ŒŽ ‘’“”•–— •˜“ˆ ™Š‡š‡ˆ“™™ ™ Page 4 800 N Tustin Ave Unit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age 5 800 N Tustin Ave Unit #H1/23/2025 IBC2021 (1613), ASCE 7-16 CHAPTER 11, 12, 13 SEISMIC DESIGN CRITERIA Response Spectral Acc. (0.2 sec) Ss =1.294 g Figure 22-1,22-3,22-5,22-6 Response Spectral Acc.( 1.0 sec) S1 =0.461 g Figure 22-2,22-4,22-5,22-6 Soil Site Class Table 20-3-1, Default = D Site Coefficient Fa = 1.200 Table 11.4-1 Site Coefficient Fv =1.540 Table 11.4-2 Max Considered Earthquake Acc. SMS =Fa.Ss = 1.553g (11.4-1) Max Considered Earthquake Acc. SM1 =Fv.S1 = 0.710g (11.4-2) @ 5% Damped Design SDS =2/3(SMS)= 1.035g (11.4-3) SD1 =2/3(SM1)= 0.473g (11.4-4) Building Risk Categories Table 1604.5 Design Category Consideration:with dist. between seismic resisting system >40ft Seismic Design Category for 0.1sec D Table 11.6-1 Seismic Design Category for 1.0sec D Table 11.6-2 S1 < .75g NA Section 11.6 Since Ta < .8Ts (see below), SDC = D Control (exception of Section 11.6 does not apply) IBC, Seismic Design Category D IRC, Seismic Design Category = D2 12.8 Equivalent lateral force procedure Seismic Force Resisting Systems Ct = 0.02 x =0.75 T-12.8-2 Building ht. Hn =35 ft ited Building Height (ft) =65 Cu = 1.400 for SD1 of 0.473g Table 12.8-1 Approx Fundamental period, Ta = Ct(hn)x = 0.288 12.8-7 TL =6.000 Sec Calculated T shall not exceed ≤Cu.Ta = 0.403 Use T =0.403 sec. 0.8Ts = 0.8(SD1/SDS)= 0.366 Is structure Regular & ≤ 5 stories ? 12.8.1.3 Response Spectral Acc.( 0.2 sec) Ss =1.294g Fa = 1.20 @ 5% Damped Design SDS =⅔(Fa.Ss)= 1.035g (11.4-3) Response Modification Coef. R =6.5 Table-12.2-1 Over Strength Factor 2.5 foot note g Importance factor I =1 T 1.5-2 Seismic Base Shear V =C s W SDS (12.8-2) R/I SD1 (12.8-3) (R/I).T SD1TL (12.8-4) T2(R/I) Cs shall not be less than =0.044SDS.I≥.01 = 0.046 (12.8-5) Min Cs =0.5S1I/R N/A For S1 ≥ 0.6g (12.8-6) Use Cs =0.159 Design base shear V =0.159 W Control 12.14 Simplified Seismic base shear @ 5% Damped Design SDS =1.035 SDC = D Limitations:P F =1.2 R = 6.5 V =FSDS(W)= 0.191 W (12.14-11) R A. BEARING WALL SYSTEMS < Ta Cs ==0.159 or need not to exceed, Cs == 0.181 For T≤ TL or Cs =N/A For T > TL For three story building T-12.1 T-12.2 T-R301.2.2.1.1 35-24 UMIH Suite H_SANTA ANA_R0.xls, Seismic Analysis-2021 IBC Page 6 800 N Tustin Ave Unit #H1/23/2025 LATERAL FORCE DISTRIBUTION SEISMIC BASE SHEAR Importance Factor, I ASCE7-16 Table 11.5-1 I = 1.00 EQ Acc. @ 5% Damped Design ASCE7-16 EQ 11.4-3 SDS = 1.04 Vult = 2021 IBC SHEET = 0.159 W Vwork = Vult / 1.4 = 0.114 W Working Stress Level Vwork = 0.114 * 89.3 kips = 10.2 kips Seismic Base Shear p = 1.30 ==> Vwork = 13.2 kips Seismic Base Shear WIND BASE SHEAR Vult = MWFR < 160 ft = 23.4 kips Vwork = Vult * 0.6 = 14.1 kips WIND BASE SHEAR GOVERNS DESIGN BASE SHEAR =14.1 kips BASE SHEAR VERTICAL DISTRIBUTION Floor Height Floor Weight wx*hx Fx % Fx Story V Fx Type hx Area wx wx*hx (V-Ft)Fx%Ft+Fi Fl Area ft ft^2 kips kips-ft (wx*hx)kips kips psf ROOF 15.00 6,511 89.29 1,339 100.0% 14.06 14.06 2.16 Total 89.29 1,339 100.0% 14.06 DIAPHRAGM FORCE DISTRIBUTION Floor Story V Fpx Min Max Fpx Type wpx wi Ft+Fi V*wpx/w Fpx1 Fpx2 Design kips kips kips kips kips kips kips ROOF 83.49 83.49 14.06 14.06 17.29 34.57 17.29 1 Fpx min = 0.2*SDs*I*wpx (for Flexible Diaphragm)ASCE7-16 12.10.1.1 2 Fpx max = 0.4*SDs*I*wpx (for Flexible Diaphragm)ASCE7-16 12.10.1.1 SHEARWALL DESIGN FORCES Level Fl. Area Wall Ht. Stry Shear Base2 Shear ft2 ft kips Shear % psf ROOF 6,511 15.00 14.06 100.0% 2.16 1 Redundancy Factor Used Per ASCE7-16 12.3.4.2 Weight 35-24 UMIH Suite H_SANTA ANA_R0.xls, Lateral Force Distribution Page 7 800 N Tustin Ave Unit #H1/23/2025 TABLES REFERENCED IN SHEARWALL DESIGN SPREADSHEET Table 2306.4.1 Allowable Shear (plf) for Wood Shearwall Panels For Wind or Seismic Loadin (plf)(plf) 1 1 15/32" 10d @6'' @16'' 3/8'' dia Lag Screw @32''OC 5/8'' dia A.B. @48''OC 340 255 2 1 15/32" 10d @4'' @8'' 3/8'' dia Lag Screw @16''OC 5/8'' dia A.B. @32''OC 510 380 3 1 15/32" 10d @3'' @12'' 3/8'' dia Lag Screw @12''OC 5/8'' dia A.B. @24''OC 665 500 4 1 15/32" 10d @2'' @8'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @16''OC 870 650 5 2 15/32" 10d @4'' @8'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @16''OC 1,020 765 6 2 15/32" 10d @3'' @4'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @12''OC 1,370 1,030 7 2 15/32" 10 @2'' @4''3/8'' dia Lag Screw @4''O 5/8'' dia A.B. @16''OC 1,740 1,305 NOTES: 1. 2. 5. NAILS SHALL BE PLACED NOT LESS THAN 1/2" INCH FROM PANEL EDGES. 8. 9. 10. V_allow (100%) A35/LTP 4 Simpson Sill Plate @ Framed Floor Anchor @ Foundation V_allow (75%)Mark # sides Sheathing Edge Nailing 4. WHERE PLYWOOD APPLIES ON BOTH FACES OF A WALL AND NAIL SPACING IS LESS THAN 6" INCHES ON CENTER ON EITHER SIDE. PANEL JOINTS SHALL HAVE MIN 3x (VERTICAL STUDS & BLOCKING) AND NAILS SHALL BE STAGGERED. OFFSET PANEL JOINTS TO FALL ON DIFFERENT FRAMING MEMBER WHERE PLYWOOD IS PLACED AT BOTH FACES. 6. FOR HOLD-DOWNS AT THE END OF THE SHEAR WALL, SEE PLANS AND SCHEDULE. PROVIDE 3"x3"x1/4" WASHER PLATE AT ALL SILL PLATE ANCHOR BOLTS AND AT ALL HOLD-DOWN BOLTS CONNECTED TO VERTICAL POSTS. ALL SHEATHING TO BE DOUGLAS FIR-LARCH STRUCT. I. ALL FIELD NAILING TO INTERMEDIATE FRAMING TO BE AT 12" O.C. 3. FRAMING AT ADJOINING PANEL EDGES SHALL BE 3" (INCH) NOMINAL OR THICKER (i.e. MIN 3x VERTICAL STUDS AND BLOCKING) NAILS SHALL BE STAGGERED IN TWO LINES ALONG PANEL EDGES WHERE NAILS ARE SPACED 2" INCHES ON CENTER OR WHEN 10d COMMON NAILS SPACED 3" O.C. PENETRATE FRAMING MORE THAN 1 5/8". SIMPSON SDS 3/8"x7" WOOD SCREWS. TYP. USE |2"x4|4" SDS INTO NAILER AT STEEL BEAMS. 11. WHERE 2-2x SILL PLATES ARE USED, SCREW LOWER PLATE TO FRAMING BELOW. DRILL HOLE IN UPPER SILL PLATE FOR SCREW HEAD SO THAT UPPER PLATE SITS FLAT ON LOW SILL PLATE. 7. USE WELDED STUD BOLTS OF SAME SIZE & SPACING AS OF SILL PLATE ANCHOR BOLTS, WHERE STEEL BEAM OCCURS UNDER SHEAR WALL. PROVIDE DOUBLE PARALLAM BLOCKING TO ACCOMODATE 2 ROWS OF SIMPSON SDS SCREWS. FOUNDATION SILL PLATE SHALL BE 3x. U.N.O. 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in SW Design Page 8 800 N Tustin Ave Unit #H1/23/2025 TABLES REFERENCED IN SHEARWALL DESIGN SPREADSHEET (HOLDOWN) HD Post Type 75% Full Used Size HDU2 2,306 3,075 2,306 4x4 HDU4 3,424 4,565 3,424 4x4 HDU5 4,253 5,670 4,253 4x4 HDU8 5,903 7,870 5,903 4x6 HDU11 7,151 9,535 7,151 4x6 HDU14 10,793 14,390 10,793 4x8 NOTES: 1. USE THREADED ROD @ EXISTING FOOTING ONLY. SEE DETAIL 16/S4 LARR# 25279. 2. USE SSTB @ NEW FOOTING ONLY PER LARR# 25248. 3. PROVIDE MIN. POST SIZE AS INDICATED, INCREASE SIZE TO MATCH WALL THICKNESS. 4. ALL HOLDOWN TO BE DOUGLAS FIR-LARCH No. 1. Max Uplift Force (lbs) Holdown Capcit 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in SW Design Page 9 800 N Tustin Ave Unit #H1/23/2025 SHEARWALL DESCRIPTION T3 C3 T4 C4 AT ROOF LEVEL Total Shearwall Length ft = Sum (b1 + b2 + ..) Total Shear (V_Roof) lbs = Shear Trib Width * Line Trib Length (L) * Roof Unit Shear (psf) Unit Shear (v_Roof) plf = V_Roof / Sum(b1 + b2 + ..) SW-1 Dead Load lbs = Roof_Dead_Laod + Ceiling_Dead_Load SW-1 Uplift Force T1 lbs = ( Upward Force ) - ( Downward Force ) = (v_Roof * H_2nd Fl) - (0.6 * SW-1 Dead Load /2) Drag Force at Open lbs = V_Roof / Line Trib Length (L) * L_Opening v_Roof L_Opening b2b1 L SW-1 V_Roof H_ 1 s t F l o o r SW-2 35-24 UMIH Suite H_SANTA ANA_R0.xls, SW Description 1-Story Page 10 800 N Tustin Ave Unit #H1/23/2025 SHEARWALL DESIGN #REF! #REF! Fl. Type Story Shear Wall Type ROOF 2.16 psf Ext. 15.00 ft A FALSE TRUE TRUE TRUE TRUE TRUE ROOF SW-01 Shearwall Length ft 19.67 Total Shearwall Length ft 19.67 Shear Trib. Width ft 24.0 Line Trib. Length ft 61.5 Line Total Length ft 61.5 Line Total Shear lbs 3,188 Line Unit Shear plf 162 1 v = 340 plf (1-Side 15/32'' Str. I w/ 10d Common Nails @ 6''-6''-12'' O.C.) Drag Length ft 6.0 Drag Force lbs 648 Strap Type MST27 Roof DL Trib. Width ft - - - Ceiling DL Trib. Width ft - - - Wall Height ft - Wall Dead Load plf - Wall Shear Force lbs 3,188 Uplift Force (Demand) lbs (269) Holdown Type HDU4 Uplift Force (Capacity) lbs 3,424 Wall Height LINE 100% Wood Shearwall 10d 35-24 UMIH Suite H_SANTA ANA_R0.xls, Shearwall Line A Page 11 800 N Tustin Ave Unit #H1/23/2025 SHEARWALL DESIGN #REF! #REF! Fl. Type Story Shear Wall Type ROOF 2.16 psf Ext. 15.00 ft 2 FALSE TRUE TRUE TRUE TRUE TRUE ROOF SW-02 Shearwall Length ft 7.42 Total Shearwall Length ft 7.42 Shear Trib. Width ft 24.0 Line Trib. Length ft 31.0 Line Total Length ft 31.0 Line Total Shear lbs 1,607 Line Unit Shear plf 217 x 8 ft / 7.42 ft = 218.9 plf 2 v = 510 plf (1-Side 15/32'' Str. I w/ 10d Common Nails @ 4''-6''-12'' O.C.) Drag Length ft 6.0 Drag Force lbs 648 Strap Type MST27 Roof DL Trib. Width ft 12.0 12.0 - Ceiling DL Trib. Width ft 12.0 12.0 - Wall Height ft - Wall Dead Load plf - Wall Shear Force lbs 1,607 Uplift Force (Demand) lbs 3,283 Holdown Type HDU5 Uplift Force (Capacity) lbs 4,253 Wall Height LINE 100% Wood Shearwall 10d 35-24 UMIH Suite H_SANTA ANA_R0.xls, Shearwall Line 2. Page 12 800 N Tustin Ave Unit #H1/23/2025 TABLES REFERENCED IN BEAM DESIGN SPREADSHEET 2018 NDS Table 4A fb fv E Select Str 1,500 180 1,900,000 No.1&Better 1,200 180 1,800,000 No.1 1,000 180 1,700,000 No.2 900 180 1,600,000 No.3 525 180 1,400,000 Stud 700 180 1,400,000 2018 NDS Table 4D fb fv E Dense Str 1,900 170 1,700,000 Select Str 1,600 170 1,600,000 Dense No. 1 1,550 170 1,700,000 No.1 1,350 170 1,600,000 Dense No. 2 1,000 170 1,400,000 No.2 875 170 1,300,000 Other Material Prllm2.0E 2,900 290 2,000,000 Mcrlm1.8E 2,600 285 1,800,000 Mcrlm1.9E 2,600 285 1,900,000 Steel Fy=36 ksi 23,760 14400 29,000,000 Steel Fy=46 ksi 30,360 18400 29,000,000 Steel Fy=50 ksi 33,000 20000 29,000,000 1. FOR DOUGLAS FIR-LARCH USE 19% MAX. MOISTURE CONTENT LOAD SYMBOLS AND NOTATION D = Dead Load E = Earthquake Load Lr = Roof Live Load W = Wind Load L = Floor Live Load ASCE7-16 2.4 LOAD COMBINATION - ALLOWABLE STRESS DESIGN 1. D 2. D + Lr Load Duration = 1.25 3. D + L Max. (Dead + Live) 4. D + 0.75 (Lr + L) Load Duration = 1.25 5.(1.0 + 0.14SDS)D + 0.7E 6.(1.0 + 0.105SDS)D + 0.525E + 0.75(L + Lr) 7.(0.6 − 0.14SDS)D + 0.7E ASCE7-16 12.4.3.2 TABLE 1604.3 (2022 CBC) DEFLECTION LIMITS Roof Members L D + L Supporting Plaster Ceiling l / 360 l / 240 Supporting Nonplaster Ceiling l / 240 l / 180 Not Supporting Ceiling l / 180 l / 120 Floor Members l / 360 l / 240 Max. (Dead + Live + Lateral) Allowable Stress Increase = 1.2  = 2.5 For Flexible Diaphragm WWPA Design Values for Visually Graded (2"-4") Design Values for Visually Graded (5" & Larger) Douglas Fir-Larch 1 WWPA Douglas Fir-Larch 1 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in Beam Design Page 13 800 N Tustin Ave Unit #H1/23/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 ALLOWABLE STRESSES REPETITIVE MEMBER NO NO NO NO NO NO REPETITIVE FACTOR, Cr 1.00 1.00 1.00 1.00 1.00 1.00 SIZE FACTOR, Cf 0.97 1.00 1.20 1.00 1.00 1.30 BENDING STRESSES, F'b psi 1,308 2,900 1,080 2,900 2,900 1,170 SHEAR STRESSES, F'v psi 170 290 180 290 290 180 MODULUS OF ELASTICITY ksi 1,700 2,000 1,600 2,000 2,000 1,600 UNIFORM DISTRIBUTED LOAD OVER FULL SPAN ROOF TRIB. WIDTH ft 4.00 2.00 16.00 21.00 13.00 CEILING TRIB. WIDTH ft 1.33 - - 7.00 7.00 FLOOR TRIB. WIDTH ft DECK TRIB. WIDTH ft WALL HEIGHT ft 6.00 6.00 3.00 WALL TYPE (EXT, INT)EXT EXT EXT AUTO CALC BEAM WEIGHT TOTAL DEAD LOAD (D plf 39.80 127.90 267.20 TOTAL ROOF LIVE LOAD (L plf 40.00 20.00 160.00 TOTAL FLOOR LIVE LOAD (L plf - - - PARTIALLY DISTRIBUTED LOAD ROOF TRIB. WIDTH ft CEILING TRIB. WIDTH ft FLOOR TRIB. WIDTH ft DECK TRIB. WIDTH ft WALL HEIGHT ft WALL TYPE (EXT, INT) TOTAL DEAD LOAD (D plf - - - TOTAL ROOF LIVE LOAD (L plf - - - TOTAL FLOOR LIVE LOAD (L plf - - - FROM (LEFT SUPPORT) ft LENGTH OF LOAD ft TRIANGULAR DISTRIBUTED LOAD ROOF TRIB. WIDTH ft TOTAL DEAD LOAD (D plf - - - TOTAL ROOF LIVE LOAD (L plf - - - CONCENTRATED LOADS P1 CHILLER CB1 DEAD LOAD (P D ) lbs 0.8 618.2 ROOF LIVE LOAD (P Lr) lbs 620.0 FLOOR LIVE LOAD (P L ) lbs - - LATERAL, P (W or 0.7E) lbs - - DIST. (LEFT SUPPORT) ft 1.00 15.50 P2 CHILLER DEAD LOAD (P D ) lbs 0.8 ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft 6.50 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 14 800 N Tustin Ave Unit #H1/23/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 P3 DEAD LOAD (P D ) lbs ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft P4 DEAD LOAD (P D ) lbs ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft LOAD CASE 1: D MAX. BENDING MOMENT lb-ft 4,784 1,023 1,411 MAX. DEFLECTION in 0.285 0.032 0.007 LEFT REACTION lbs 618 512 868 RIGHT REACTION lbs 617 512 868 LOAD CASE: Lr MAX. BENDING MOMENT lb-ft 4,805 160 845 MAX. DEFLECTION in 0.286 0.005 0.004 LEFT REACTION lbs 620 80 520 RIGHT REACTION lbs 620 80 520 LOAD CASE: L MAX. BENDING MOMENT lb-ft - - - MAX. DEFLECTION in - - - LEFT REACTION lbs - - - RIGHT REACTION lbs - - - LOAD CASE 2: D + Lr Wood Load Duration Factor = 1.25 MAX. BENDING MOMENT lb-ft 7,671 947 1,805 MAX. DEFLECTION in 0.572 0.037 0.011 LEFT REACTION lbs 991 473 1,111 RIGHT REACTION lbs 990 473 1,111 LOAD CASE 3: D + L Wood Load Duration Factor = 1.0 MAX. BENDING MOMENT lb-ft 4,784 1,023 1,411 MAX. DEFLECTION in 0.285 0.032 0.007 LEFT REACTION lbs 618 512 868 RIGHT REACTION lbs 617 512 868 LOAD CASE 4:D + 0.75 (Lr + L)Wood Load Duration Factor = 1.25 MAX. BENDING MOMENT lb-ft 6,710 915 1,636 MAX. DEFLECTION in 0.500 0.036 0.010 LEFT REACTION lbs 1,083 572 1,258 RIGHT REACTION lbs 1,082 572 1,258 LOAD CASE 5:(1.0 + 0.14SDS)D + 0.7E Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 3,423 732 1,010 MAX. DEFLECTION in 0.272 0.030 0.006 LEFT REACTION lbs 590 488 829 RIGHT REACTION lbs 589 488 829 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 15 800 N Tustin Ave Unit #H1/23/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 LOAD CASE 6:(1.0 + 0.105SDS)D + 0.525E + 0.75(L + Lr)Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 5,567 784 1,374 MAX. DEFLECTION in 0.443 0.033 0.009 LEFT REACTION lbs 959 523 1,127 RIGHT REACTION lbs 958 523 1,127 LOAD CASE 7:(0.6 − 0.14SDS)D + 0.7E Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 1,361 291 401 MAX. DEFLECTION in 0.108 0.012 0.003 LEFT REACTION lbs 234 194 329 RIGHT REACTION lbs 234 194 329 CHECK BENDING STRESSES MAX. BENDING MOMENT lb-ft 7,671.0 - 1,023.2 1,804.9 - - SECTION MODULUS, S in3 220.2 114.3 49.9 114.3 114.3 30.7 BENDING STRESS psi 418.0 - 246.0 189.4 - - CHECK BENDING STRESS RATIO 32% OK 0% OK 23% OK 7% OK 0% OK 0% OK CHECK SHEAR STRESSES #VALUE!#VALUE! #VALUE! MAX. SHEAR FORCE lbs 1,083.2 #VALUE!571.60 1,258.40 #VALUE! #VALUE! SECTION AREA, A in2 85.25 49.00 32.38 49.00 49.00 25.38 SHEAR STRESS, fv psi 19.06 #VALUE!26.48 38.52 #VALUE! #VALUE! CHECK SHEAR STRESS RATIO 11% OK #VALUE!15% OK 13% OK #VALUE! #VALUE! CHECK DEFLECTION #VALUE!#VALUE! #VALUE! MOMENT OF INERTIA, I in4 1,706.78 800.33 230.84 800.33 800.33 111.15 MAX. DEFLECTION, DL in 0.285 0.032 0.007 MAX. DEFLECTION, LL in 0.286 #VALUE!0.005 0.004 #VALUE! #VALUE! DEFLECTION LIMITS, LL L / 360 L / 360 L / 360 L / 360 L / 360 L / 360 CHECK DEFLECTION LL < 1.03 OK #VALUE!< 0.27 OK < 0.22 OK #VALUE! #VALUE! MAX. DEFLECTION, DL+LL in 0.572 #VALUE!0.037 0.011 #VALUE! #VALUE! DEFLECTION LIMITS, DL+LL L / 240 L / 240 L / 240 L / 240 L / 240 L / 240 CHECK DEFLECTION (DL+LL)< 1.55 OK #VALUE!< 0.4 OK < 0.33 OK #VALUE! #VALUE! 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 16 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:(N) RB4 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design iLevel Truss Joist Parallam PSL 2.0E 2,900.0 2,900.0 2,900.0 750.0 2,000.0 1,016.54 290.0 2,025.0 45.070 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Point Load : D = 0.750 k @ 1.0 ft, (CHILLER#1) Point Load : D = 0.750 k @ 7.0 ft, (CHILLER#2) Uniform Load : D = 0.0160, Lr = 0.020 ksf, Tributary Width = 4.0 ft, (Roof) Point Load : D = 0.20 k @ 13.0 ft, (TRANSFORMER) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.367: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 13.803 ft 63.89 psi= = 3,425.18 psi 3.5x20Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 362.50 psi== Section used for this span 3.5x20 Maximum Shear Stress Ratio 0.176 : 1 0.000 ft= = 1,258.03 psi Maximum Deflection 0 <360 406 Ratio =0 <240 Max Downward Transient Deflection 0.358 in 1038Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.914 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.314 0.153 0.90 0.945 1.001.00 1.00 15.04 773.7 2,466.1 1.87 261.040.0 0.00.0 1 0.367 0.176 1.25 0.945 1.001.00 1.00 24.46 1,258.0 3,425.2 2.98 362.563.9 0.00.0 1 0.332 0.160 1.25 0.945 1.001.00 1.00 22.09 1,136.1 3,425.2 2.70 362.557.9 0.00.0 1 0.106 0.052 1.60 0.945 1.001.00 1.00 9.03 464.2 4,384.2 1.12 464.024.0 . Page 17 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:(N) RB4 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.9144 15.274 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 3.994 2.849 Max Upward from Load Combinations 3.994 2.849 Max Upward from Load Cases 2.754 1.609 D Only 2.754 1.609 +D+Lr 3.994 2.849 +D+0.750Lr 3.684 2.539 +0.60D 1.653 0.965 Lr Only 1.240 1.240 Page 18 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RB2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design Douglas Fir-Larch No.1 1,350.0 1,350.0 925.0 625.0 1,600.0 580.0 170.0 675.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.0160, Lr = 0.0120 ksf, Tributary Width = 31.0 ft, (ROOF) Point Load : D = 1.320 k @ 10.0 ft, (TJI #1) Point Load : D = 1.320 k @ 14.0 ft, (TJI #2) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.757: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 9.985 ft 97.95 psi= = 1,566.07 psi 6x24Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 212.50 psi== Section used for this span 6x24 Maximum Shear Stress Ratio 0.461 : 1 17.058 ft= = 1,186.16 psi Maximum Deflection 0 <360 677 Ratio =0 <240 Max Downward Transient Deflection 0.115 in 1977Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.337 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.700 0.427 0.90 0.928 1.001.00 1.00 33.30 789.3 1,127.6 5.63 153.065.3 0.00.0 1 0.757 0.461 1.25 0.928 1.001.00 1.00 50.04 1,186.2 1,566.1 8.44 212.597.9 0.00.0 1 0.694 0.423 1.25 0.928 1.001.00 1.00 45.85 1,086.9 1,566.1 7.74 212.589.8 0.00.0 1 0.236 0.144 1.60 0.928 1.001.00 1.00 19.98 473.6 2,004.6 3.38 272.039.2 . Page 19 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RB2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.3367 9.639 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 9.485 10.179 Max Upward from Load Combinations 9.485 10.179 Max Upward from Load Cases 5.951 6.645 D Only 5.951 6.645 +D+Lr 9.485 10.179 +D+0.750Lr 8.601 9.296 +0.60D 3.570 3.987 Lr Only 3.534 3.534 Page 20 800 N Tustin Ave Unit #H1/23/2025 Page 21 800 N Tustin Ave Unit #H1/23/2025 Page 22 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RB3- 5.5X18 GLLM Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design DF/HF 24F-V5 2,400.0 1,600.0 1,450.0 650.0 1,700.0 900.0 215.0 1,100.0 26.840 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity 1,500.0 ksi 790.0 ksi Ebend- yy Eminbend - yy Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Load for Span Number 1 Point Load : D = 6.650, Lr = 3.530 k @ 0.0 ft, (RB2) Uniform Load : D = 0.010, Lr = 0.0120 ksf, Tributary Width = 31.0 ft, (ROOF) Load for Span Number 2 Uniform Load : D = 0.010, Lr = 0.0120 ksf, Tributary Width = 31.0 ft, (ROOF) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.995: 1 Load Combination +D+Lr Span # where maximum occurs Span # 2 Location of maximum on span 0.000 ft 180.80 psi= = 1,881.72 psi 5.5x18Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 268.75 psi== Section used for this span 5.5x18 Maximum Shear Stress Ratio 0.673 : 1 2.503 ft= = 1,871.66 psi Maximum Deflection 1134 >=360 541 Ratio =18512 >=240 Max Downward Transient Deflection 0.382 in 753Ratio =>=360 Max Upward Transient Deflection -0.085 in Ratio = Max Downward Total Deflection 0.532 in Ratio =>=240 Max Upward Total Deflection -0.016 in fb: Actual F'b fv: Actual F'v Span: 2 : Lr Only Span: 1 : Lr Only Span: 2 : +D+Lr Span: 2 : D Only .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCV rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.820 0.585 0.90 1.000 1.001.00 1.00 29.23 1,180.9 1,440.0 7.47 193.5113.2 2 0.872 0.585 0.90 0.941 1.001.00 1.00 29.23 1,180.9 1,354.8 4.67 193.5113.2 0.00.0 1 0.936 0.673 1.25 1.000 1.001.00 1.00 46.32 1,871.7 2,000.0 11.93 268.8180.8 2 0.995 0.673 1.25 0.941 1.001.00 1.00 46.32 1,871.7 1,881.7 9.30 268.8180.8 0.00.0 Page 23 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RB3- 5.5X18 GLLM Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCV rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu 1.00Length = 4.0 ft 1 0.849 0.610 1.25 1.000 1.001.00 1.00 42.05 1,699.0 2,000.0 10.82 268.8163.9 2 0.903 0.610 1.25 0.941 1.001.00 1.00 42.05 1,699.0 1,881.7 8.15 268.8163.9 0.00.0 1 0.277 0.197 1.60 1.000 1.001.00 1.00 17.54 708.5 2,560.0 4.48 344.067.9 2 0.294 0.197 1.60 0.941 1.001.00 1.00 17.54 708.5 2,408.6 2.80 344.067.9 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections Lr OnlyD Only 1 0.1261 0.000 -0.0407 2.369 2 0.5319 13.676 0.0000 2.369 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 23.317 6.475 Max Upward from Load Combinations 23.317 6.475 Max Upward from Load Cases 13.123 3.752 D Only 13.123 2.724 +D+Lr 23.317 6.475 +D+0.750Lr 20.769 5.537 +0.60D 7.874 1.634 Lr Only 10.194 3.752 Page 24 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RTU-Curb Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design Douglas Fir-Larch No.2 875.0 875.0 600.0 625.0 1,300.0 470.0 170.0 425.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.1250 ksf, Tributary Width = 3.0 ft, (Chiller) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.655: 1 Load Combination D Only Span # where maximum occurs Span # 1 Location of maximum on span 3.000 ft 54.18 psi= = 1,023.75 psi 4x8Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination D Only = = = 153.00 psi== Section used for this span 4x8 Maximum Shear Stress Ratio 0.354 : 1 0.000 ft= = 670.12 psi Maximum Deflection 0 <360 932 Ratio =0 <240 Max Downward Transient Deflection 0 in 0Ratio =<360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.077 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v n/a n/a Span: 1 : D Only n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.655 0.354 0.90 1.300 1.001.00 1.00 1.71 670.1 1,023.8 0.92 153.054.2 0.00.0 1 0.221 0.120 1.60 1.300 1.001.00 1.00 1.03 402.1 1,820.0 0.55 272.032.5 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections D Only 1 0.0772 3.022 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 1.141 1.141 Page 25 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RTU-Curb Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from Load Combinations 0.685 0.685 Max Upward from Load Cases 1.141 1.141 D Only 1.141 1.141 +0.60D 0.685 0.685 Page 26 800 N Tustin Ave Unit #H1/23/2025 COLUMN AXIAL CAPACITY WOOD PROPERTIES: Use Douglas Fir-Larch CF =1.1 Kce = 0.30 Buckling about x-axis?YES Species:Cm =1.0 c = 0.80 Check le/d reqmt.OK! E =CT =1.0 Kf = 1.00 F'c =Ct = 1.0 (for bolted or nailed members) E' = Ci =1.0 Fc* = CD =1.0 No. of 1+ Fce/Fc*Column Plies 2c Capacity C01 1 - 2x 4 1.5 3.50 8 64.0 27.4 27.4 558.27 0.597 1.00 0.498 465.79 2.45 kips C02 2 - 2x 4 3.0 3.50 8 32.0 27.4 27.4 558.27 0.597 1.00 0.498 465.79 4.89 kips C03 1 - 2x 6 1.5 5.50 8 64.0 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 6.22 kips C04 2 - 2x 6 3.0 5.50 8 32.0 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 12.43 kips C05 1 - 2x 8 1.5 7.50 8 64.0 12.8 12.8 2,563.48 2.742 2.34 0.910 850.54 9.57 kips C06 2 - 2x 8 3.0 7.25 8 32.0 13.2 13.2 2,395.43 2.562 2.23 0.902 843.35 18.34 kips WOOD PROPERTIES: Use Douglas Fir-Larch CF =1.1 Kce = 0.30 Buckling about x-axis?YES Species:Cm =1.0 c = 0.80 Check le/d reqmt.OK! E =CT =1.0 Kf = 1.00 F'c =Ct = 1.0 (for bolted or nailed members) E' = Ci =1.0 Fc* = CD =1.0 No. of 1+ Fce/Fc*Column Plies 2c Capacity C07 1 - 4x 4 3.5 3.50 8 27.4 27.4 27.4 558.27 0.597 1.00 0.498 465.79 5.71 kips C08 1 - 4x 6 3.5 5.50 8 27.4 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 14.50 kips C09 1 - 4x 8 3.5 7.50 8 27.4 12.8 12.8 2,563.48 2.742 2.34 0.910 850.54 22.33 kips C10 1 - 6x 6 5.5 5.50 8 17.5 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 22.79 kips C11 1 - 6x 8 5.5 7.25 8 17.5 13.2 13.2 2,395.43 2.562 2.23 0.902 843.35 33.63 kips Note: KcE = 0.510 - 0.839(COV)where COV = 0.25 - sawn lumber 0.3 - for visually graded lumber 0.15 - MEL 0.384 - for machine evaluated lumber (MEL)0.11 - MSR (machine stress rated) 0.418 - for roducts w/ COV<=0.11 0.10 - glu-lam le/dx le/dx F'cCOL(le/d) Fce Fce/Fc*CPdxlex,y 1,500 psi 1,700,000 psi 1,650 psi le/dy 935 psi Size dy Stud 1,400,000 psi 850 psi 1,400,000 psi No.1 1,700,000 psi Size le/dyCOL dy dx lex,y F'c(le/d) Fce Fce/Fc* CP 35-24 UMIH Suite H_SANTA ANA_R0.xls, Column Design Page 27 800 N Tustin Ave Unit #H1/23/2025 www.fastructural.com Email : atefg@fastructural.com T: +1 714.519.5027 STRUCTURAL ENGINEERING AND CONSULTING 800 N Tustin St., Santa Ana, CA 92705 Projecct # 35-24 STRUCTURAL CALCULATIONS Date Rev. R0 # Pages 25 7/1/2024 800 N Tustin Ave Unit #H1/23/2025 CALCULATION INDEX PART / TITLE Page 1. Gravity Criteria 1 2. Building Weight 2 3. Wind Analysis 3 4. Seismic Analysis Site Latitude & Longitude 4 Spectral Response Coefficients 5 Seismic Analysis 2012 IBC 6 5. Lateral Force Distribution 7 6. Wood Shearwall Design Shearwall Design Tables 9 Shearwall Description 10 Shearwall Design 11 7. Beam Design Beam Design Tables 13 Simply Supported Beam Design 14 8. Column Design Column Loads Wood Column Design 25 35-24 UMIH Suite H_SANTA ANA_R0.xls, Calculation Index 800 N Tustin Ave Unit #H1/23/2025 GRAVITY LOADS 2.00 psf 2.25 psf 4.20 psf 1.50 psf 9.95 psf 10.00 psf 3.00 psf 2.25 psf 3.15 psf 3.00 psf 1.60 psf 13.00 psf 100.00 psf 2.10 psf 3.00 psf 3.00 psf 8.00 psf 20.00 psf 10.00 psf 2.81 psf 1.58 psf 0.50 psf 3.00 psf 18.00 psf 3.00 psf 1.05 psf 2.81 psf 3.00 psf 10.00 psf Insulation Fiber Glass Rigid Wall Wood Studs 2x6 @ 16" O.C. DF-Larch EXTERIOR WALL INTERIOR WALL Drywall Finish INTERIOR WALL LOAD Drywall Finish Sheathing 15/32" Plywood Wall Wood Studs 2x4 @ 16" O.C. DF-Larch Insulation Fiber Glass Loose EXTERIOR WALL LOAD Framing 2x12 @ 12" O.C. DF-Larch Sheathing 3/4" T&G ROOF LIVE LOAD TOTAL ROOF DEAD LOAD TOTAL OPEN DECK DEAD LOAD DEAD LOAD ROOF LOADS Roofing Shingles Asphalt (1/4 in) DECK DEAD LOAD TOTAL Sheathing 3/4" T&G Flooring Hardwood (1 in) CEILING DEAD LOAD TOTAL Miscellaneous Framing 2x 8 @ 16" O.C. DF-Larch CEILING LIVE LOAD TOTAL Drywall Finish CEILING LOADS Wall Plaster (1 in) on Metal Lath DEAD LOAD Sheathing 15/32" Plywood Drywall Finish Framing 2x12 @ 16" O.C. DF-Larch Drywall Finish DECK LIVE LOAD TOTAL Miscellaneous 35-24 UMIH Suite H_SANTA ANA_R0.xls, Gravity Loads Page 1 800 N Tustin Ave Unit #H1/23/2025 BUILDING WEIGHT DESIGN CRITERIA Code Used : 2022 CBC Concrete F'c : 2,500 psi Building Code : 2021 IBC Steel Fy : 60,000 psi LACity Requirement : Yes v SOILS REPORT NO SOILS REPORT Bearing Capacity : 1,500 psf SEISMIC DESIGN PARAMETERS Short Period, Fa :1.2 0.2 sec Fig 1613.5(1) Latitude : 33.752258 Long Period, Fv :1.5 1.0 sec Fig 1613.5(2) Longitude :-117.834959 Response Spectral : 129.40% 0.2 sec Fig 1613.5(3) Site Class : D Response Spectral : 46.10% 1.0 sec Fig 1613.5(4) BUILDING SUMMARY Level Height Elevation Unit Weight psf Wall Weight ft Dead Live Type psf ROOF 15.00 15.00 9.95 10.00 Exterior 18.00 Interior 10.00 BUILDING WEIGHT ROOF Area Type L (ft) W (ft) H (ft) Area (ft^2) Dead Load (psf) Weight (kips) Roof 6,510.8 9.95 64.78 Ext. Wall 62.00 24.00 7.50 18.00 11.61 Int. Wall 124.00 48.00 7.50 10.00 12.90 TOTAL ROOF AREA / LOAD 6,510.8 89.29 35-24 UMIH Suite H_SANTA ANA_R0.xls, Building Weight Page 2 800 N Tustin Ave Unit #H1/23/2025 27.5 Directional Procedure, Part 2: Enclosed Simple Diaphragm Buildings With H ≤ 160 Ft T-27.6-2 (psf) X oof Exp adjust factor T-27.6-2 = 1 0.00 Ph =21.80 Ph = 25.20 P0 =21.80 P0 =25.20 62 24 Example will work for V =110, 115 and 120 MPH only. Wind Normal to Ridge Wind Parallel to Ridge Roof Height h =15 feet Exposure C Roof Pitch =0.00 :12 Topography factor Kzt =1.00 26.8.2, Figure 26.8-1 Building & Structure Risk Category = IBC T-1604.5 Wind Speed V = 110 mph Fig. 26.5-1A, MRI = 700 yrs Wind Normal to Ridge, L/B = 2.583 use 2.0 Wind Parallel to Ridge, L/B = 0.39 use 0.5 Since .2 ≤ L/B ≤ 5.0 = Yes Since .2 ≤ L/B ≤ 5.0 = Yes and h ≤ 60 = Yes and h ≤ 60 = Yes Building meet Class I condition ? Yes Building meet Class I condition ? Yes  Since .5 ≤ L/B ≤ 2.0 = No Since .5 ≤ L/B ≤ 2.0 = No and 60 ≤h ≤1 60 = No and 60 ≤h ≤1 60 = No Fundamental period =0.500 sec Fundamental period =0.500 sec More than h/75 sec. NG More than h/75 sec. NG Building meet Class II condition ? No Building meet Class II condition ? No From T-27.6-1, V = 110 MPH Exp C, L/B =2.0 and 15 FT. HT From T-27.6-1, V = 110 MPH Exp C, L/B =0.5 and 15 FT. HT Ph =21.80 Kzt Ph =25.20 Kzt Po =21.80 Kzt Po =25.20 Kzt T-27.6-2 V =110 Exp C, h =15 Roof slope =0:12 Zone 1 =-23.5 Adjust factor T-27.6-2, = 1.00 Design roof pressure for zone 1 = -23.50 PSF Wind Base Shear = 7.85 kips Wind Base Shear = 23.44 kips II, standard == 35-24 UMIH Suite H_SANTA ANA_R0.xls, Wind Analysis MWFR<160ft Page 3 800 N Tustin Ave Unit #H1/23/2025                                    !"##$      %&'()*+,-.(/'01.,6778 9 : :;#!7<:=5 ??!<##<6:"@@!6?A;<;@<< #7#A"7G"#G@!H77H?#<!<I5  M.)P/&,05  !"@G(L5 SST"  &(4X'CP& O&4)(1F01.,@#;A Y Z[ M  \  ]7#^7AG@ Y Z[ M  \  ]@7^@<<?  "M        9  _  "M        9  @7?< 8M  M [9   7#_ 8M  M [9   @7@@A6-.(/'01.,X'CP& O&4)(1F01.,_  M [ [ @#  M     7#_  M     @77;?<      \7#^7;#6      \@7^7<A@ Y a [    @#  M     a7G<  M   [    6  ["       \^@#;A     "  [ [ M  \7#^@?6A $  M"       \#b     c  <7  ^@< $  M    9  \7#^7AG@     "  [ [ M  \@7^7A;! $  M"       \#b     c  <7  ^7G $  M    9  \@7^7<A< $  M    9  \a^@@A6 ‚ƒƒ„…†‡ˆ‰‡Š‡‹Œ ŒŽ ‘’“”•–— •˜“ˆ ™Š‡š‡ˆ“™™ ™ Page 4 800 N Tustin Ave Unit #H1/23/2025                 !"#$%&"'()*+,+-./0+.1+-23-045.2.67892:;<;=20/0>5?+/<@-427<251A5?B215>CD26<2-45?21;0-A+850C3-212C82.0C8951F2615825162/5242.8062?0--2?8GHIJ+C.581130C10-1+C.?0C8-56@80-1+11@A2C0-2130C1565/5870-/5+65/587E0-581+??@-+?7;I92A+82-5+/3-212C82.190@/.C0862@12.0--2/52.@30CE0-+C7132?5E5?+33/5?+850CF5890@8?0A3282C82K+A5C+850C+C.42-5E5?+850C0E581+??@-+?7G1@58+65/587+C.+33/5?+65/587672C>5C22-10-0892-21150C+/1;HIJ.021C085C82C.89+8892@120E89515CE0-A+850C-23/+?289210@C.L@.>A2C80E1@?9?0A3282C83-0E21150C+/1G9+45C>2K32-52C?2+C.MC0F/2.>25C892E52/.0E801@61858@82E0-89218+C.+-.0E?+-2-2N@5-2.0E1@?93-0E21150C+/15C5C82-3-285C>+C.+33/75C>892-21@/810E892-230-83-045.2.678951F261582;:12-10E8925CE0-A+850CE-0A+11@A2+///5+65/587+-515C>E-0A1@?9@12;:120E8920@83@80E8951F261582.021C085A3/7+33-04+/67892>042-C5C>6@5/.5C>?0.260.521-2130C156/2E0-6@5/.5C>?0.2+33-04+/+850CE0-8926@5/.5C>1582.21?-562.67/+858@.2O/0C>58@.2/0?+850C5C892-230-8; Page 5 800 N Tustin Ave Unit #H1/23/2025 IBC2021 (1613), ASCE 7-16 CHAPTER 11, 12, 13 SEISMIC DESIGN CRITERIA Response Spectral Acc. (0.2 sec) Ss =1.294 g Figure 22-1,22-3,22-5,22-6 Response Spectral Acc.( 1.0 sec) S1 =0.461 g Figure 22-2,22-4,22-5,22-6 Soil Site Class Table 20-3-1, Default = D Site Coefficient Fa = 1.200 Table 11.4-1 Site Coefficient Fv =1.540 Table 11.4-2 Max Considered Earthquake Acc. SMS =Fa.Ss = 1.553g (11.4-1) Max Considered Earthquake Acc. SM1 =Fv.S1 = 0.710g (11.4-2) @ 5% Damped Design SDS =2/3(SMS)= 1.035g (11.4-3) SD1 =2/3(SM1)= 0.473g (11.4-4) Building Risk Categories Table 1604.5 Design Category Consideration:with dist. between seismic resisting system >40ft Seismic Design Category for 0.1sec D Table 11.6-1 Seismic Design Category for 1.0sec D Table 11.6-2 S1 < .75g NA Section 11.6 Since Ta < .8Ts (see below), SDC = D Control (exception of Section 11.6 does not apply) IBC, Seismic Design Category D IRC, Seismic Design Category = D2 12.8 Equivalent lateral force procedure Seismic Force Resisting Systems Ct = 0.02 x =0.75 T-12.8-2 Building ht. Hn =35 ft ited Building Height (ft) =65 Cu = 1.400 for SD1 of 0.473g Table 12.8-1 Approx Fundamental period, Ta = Ct(hn)x = 0.288 12.8-7 TL =6.000 Sec Calculated T shall not exceed ≤Cu.Ta = 0.403 Use T =0.403 sec. 0.8Ts = 0.8(SD1/SDS)= 0.366 Is structure Regular & ≤ 5 stories ? 12.8.1.3 Response Spectral Acc.( 0.2 sec) Ss =1.294g Fa = 1.20 @ 5% Damped Design SDS =⅔(Fa.Ss)= 1.035g (11.4-3) Response Modification Coef. R =6.5 Table-12.2-1 Over Strength Factor 2.5 foot note g Importance factor I =1 T 1.5-2 Seismic Base Shear V =C s W SDS (12.8-2) R/I SD1 (12.8-3) (R/I).T SD1TL (12.8-4) T2(R/I) Cs shall not be less than =0.044SDS.I≥.01 = 0.046 (12.8-5) Min Cs =0.5S1I/R N/A For S1 ≥ 0.6g (12.8-6) Use Cs =0.159 Design base shear V =0.159 W Control 12.14 Simplified Seismic base shear @ 5% Damped Design SDS =1.035 SDC = D Limitations:P F =1.2 R = 6.5 V =FSDS(W)= 0.191 W (12.14-11) R A. BEARING WALL SYSTEMS < Ta Cs ==0.159 or need not to exceed, Cs == 0.181 For T≤ TL or Cs =N/A For T > TL For three story building T-12.1 T-12.2 T-R301.2.2.1.1 35-24 UMIH Suite H_SANTA ANA_R0.xls, Seismic Analysis-2021 IBC Page 6 800 N Tustin Ave Unit #H1/23/2025 LATERAL FORCE DISTRIBUTION SEISMIC BASE SHEAR Importance Factor, I ASCE7-16 Table 11.5-1 I = 1.00 EQ Acc. @ 5% Damped Design ASCE7-16 EQ 11.4-3 SDS = 1.04 Vult = 2021 IBC SHEET = 0.159 W Vwork = Vult / 1.4 = 0.114 W Working Stress Level Vwork = 0.114 * 89.3 kips = 10.2 kips Seismic Base Shear p = 1.30 ==> Vwork = 13.2 kips Seismic Base Shear WIND BASE SHEAR Vult = MWFR < 160 ft = 23.4 kips Vwork = Vult * 0.6 = 14.1 kips WIND BASE SHEAR GOVERNS DESIGN BASE SHEAR =14.1 kips BASE SHEAR VERTICAL DISTRIBUTION Floor Height Floor Weight wx*hx Fx % Fx Story V Fx Type hx Area wx wx*hx (V-Ft)Fx%Ft+Fi Fl Area ft ft^2 kips kips-ft (wx*hx)kips kips psf ROOF 15.00 6,511 89.29 1,339 100.0% 14.06 14.06 2.16 Total 89.29 1,339 100.0% 14.06 DIAPHRAGM FORCE DISTRIBUTION Floor Story V Fpx Min Max Fpx Type wpx wi Ft+Fi V*wpx/w Fpx1 Fpx2 Design kips kips kips kips kips kips kips ROOF 83.49 83.49 14.06 14.06 17.29 34.57 17.29 1 Fpx min = 0.2*SDs*I*wpx (for Flexible Diaphragm)ASCE7-16 12.10.1.1 2 Fpx max = 0.4*SDs*I*wpx (for Flexible Diaphragm)ASCE7-16 12.10.1.1 SHEARWALL DESIGN FORCES Level Fl. Area Wall Ht. Stry Shear Base2 Shear ft2 ft kips Shear % psf ROOF 6,511 15.00 14.06 100.0% 2.16 1 Redundancy Factor Used Per ASCE7-16 12.3.4.2 Weight 35-24 UMIH Suite H_SANTA ANA_R0.xls, Lateral Force Distribution Page 7 800 N Tustin Ave Unit #H1/23/2025 TABLES REFERENCED IN SHEARWALL DESIGN SPREADSHEET Table 2306.4.1 Allowable Shear (plf) for Wood Shearwall Panels For Wind or Seismic Loadin (plf)(plf) 1 1 15/32" 10d @6'' @16'' 3/8'' dia Lag Screw @32''OC 5/8'' dia A.B. @48''OC 340 255 2 1 15/32" 10d @4'' @8'' 3/8'' dia Lag Screw @16''OC 5/8'' dia A.B. @32''OC 510 380 3 1 15/32" 10d @3'' @12'' 3/8'' dia Lag Screw @12''OC 5/8'' dia A.B. @24''OC 665 500 4 1 15/32" 10d @2'' @8'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @16''OC 870 650 5 2 15/32" 10d @4'' @8'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @16''OC 1,020 765 6 2 15/32" 10d @3'' @4'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @12''OC 1,370 1,030 7 2 15/32" 10 @2'' @4''3/8'' dia Lag Screw @4''O 5/8'' dia A.B. @16''OC 1,740 1,305 NOTES: 1. 2. 5. NAILS SHALL BE PLACED NOT LESS THAN 1/2" INCH FROM PANEL EDGES. 8. 9. 10. V_allow (100%) A35/LTP 4 Simpson Sill Plate @ Framed Floor Anchor @ Foundation V_allow (75%)Mark # sides Sheathing Edge Nailing 4. WHERE PLYWOOD APPLIES ON BOTH FACES OF A WALL AND NAIL SPACING IS LESS THAN 6" INCHES ON CENTER ON EITHER SIDE. PANEL JOINTS SHALL HAVE MIN 3x (VERTICAL STUDS & BLOCKING) AND NAILS SHALL BE STAGGERED. OFFSET PANEL JOINTS TO FALL ON DIFFERENT FRAMING MEMBER WHERE PLYWOOD IS PLACED AT BOTH FACES. 6. FOR HOLD-DOWNS AT THE END OF THE SHEAR WALL, SEE PLANS AND SCHEDULE. PROVIDE 3"x3"x1/4" WASHER PLATE AT ALL SILL PLATE ANCHOR BOLTS AND AT ALL HOLD-DOWN BOLTS CONNECTED TO VERTICAL POSTS. ALL SHEATHING TO BE DOUGLAS FIR-LARCH STRUCT. I. ALL FIELD NAILING TO INTERMEDIATE FRAMING TO BE AT 12" O.C. 3. FRAMING AT ADJOINING PANEL EDGES SHALL BE 3" (INCH) NOMINAL OR THICKER (i.e. MIN 3x VERTICAL STUDS AND BLOCKING) NAILS SHALL BE STAGGERED IN TWO LINES ALONG PANEL EDGES WHERE NAILS ARE SPACED 2" INCHES ON CENTER OR WHEN 10d COMMON NAILS SPACED 3" O.C. PENETRATE FRAMING MORE THAN 1 5/8". SIMPSON SDS 3/8"x7" WOOD SCREWS. TYP. USE |2"x4|4" SDS INTO NAILER AT STEEL BEAMS. 11. WHERE 2-2x SILL PLATES ARE USED, SCREW LOWER PLATE TO FRAMING BELOW. DRILL HOLE IN UPPER SILL PLATE FOR SCREW HEAD SO THAT UPPER PLATE SITS FLAT ON LOW SILL PLATE. 7. USE WELDED STUD BOLTS OF SAME SIZE & SPACING AS OF SILL PLATE ANCHOR BOLTS, WHERE STEEL BEAM OCCURS UNDER SHEAR WALL. PROVIDE DOUBLE PARALLAM BLOCKING TO ACCOMODATE 2 ROWS OF SIMPSON SDS SCREWS. FOUNDATION SILL PLATE SHALL BE 3x. U.N.O. 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in SW Design Page 8 800 N Tustin Ave Unit #H1/23/2025 TABLES REFERENCED IN SHEARWALL DESIGN SPREADSHEET (HOLDOWN) HD Post Type 75% Full Used Size HDU2 2,306 3,075 2,306 4x4 HDU4 3,424 4,565 3,424 4x4 HDU5 4,253 5,670 4,253 4x4 HDU8 5,903 7,870 5,903 4x6 HDU11 7,151 9,535 7,151 4x6 HDU14 10,793 14,390 10,793 4x8 NOTES: 1. USE THREADED ROD @ EXISTING FOOTING ONLY. SEE DETAIL 16/S4 LARR# 25279. 2. USE SSTB @ NEW FOOTING ONLY PER LARR# 25248. 3. PROVIDE MIN. POST SIZE AS INDICATED, INCREASE SIZE TO MATCH WALL THICKNESS. 4. ALL HOLDOWN TO BE DOUGLAS FIR-LARCH No. 1. Max Uplift Force (lbs) Holdown Capcit 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in SW Design Page 9 800 N Tustin Ave Unit #H1/23/2025 SHEARWALL DESCRIPTION T3 C3 T4 C4 AT ROOF LEVEL Total Shearwall Length ft = Sum (b1 + b2 + ..) Total Shear (V_Roof) lbs = Shear Trib Width * Line Trib Length (L) * Roof Unit Shear (psf) Unit Shear (v_Roof) plf = V_Roof / Sum(b1 + b2 + ..) SW-1 Dead Load lbs = Roof_Dead_Laod + Ceiling_Dead_Load SW-1 Uplift Force T1 lbs = ( Upward Force ) - ( Downward Force ) = (v_Roof * H_2nd Fl) - (0.6 * SW-1 Dead Load /2) Drag Force at Open lbs = V_Roof / Line Trib Length (L) * L_Opening v_Roof L_Opening b2b1 L SW-1 V_Roof H_ 1 s t F l o o r SW-2 35-24 UMIH Suite H_SANTA ANA_R0.xls, SW Description 1-Story Page 10 800 N Tustin Ave Unit #H1/23/2025 SHEARWALL DESIGN #REF! #REF! Fl. Type Story Shear Wall Type ROOF 2.16 psf Ext. 15.00 ft A FALSE TRUE TRUE TRUE TRUE TRUE ROOF SW-01 Shearwall Length ft 19.67 Total Shearwall Length ft 19.67 Shear Trib. Width ft 24.0 Line Trib. Length ft 61.5 Line Total Length ft 61.5 Line Total Shear lbs 3,188 Line Unit Shear plf 162 1 v = 340 plf (1-Side 15/32'' Str. I w/ 10d Common Nails @ 6''-6''-12'' O.C.) Drag Length ft 6.0 Drag Force lbs 648 Strap Type MST27 Roof DL Trib. Width ft - - - Ceiling DL Trib. Width ft - - - Wall Height ft - Wall Dead Load plf - Wall Shear Force lbs 3,188 Uplift Force (Demand) lbs (269) Holdown Type HDU4 Uplift Force (Capacity) lbs 3,424 Wall Height LINE 100% Wood Shearwall 10d 35-24 UMIH Suite H_SANTA ANA_R0.xls, Shearwall Line A Page 11 800 N Tustin Ave Unit #H1/23/2025 SHEARWALL DESIGN #REF! #REF! Fl. Type Story Shear Wall Type ROOF 2.16 psf Ext. 15.00 ft 2 FALSE TRUE TRUE TRUE TRUE TRUE ROOF SW-02 Shearwall Length ft 7.42 Total Shearwall Length ft 7.42 Shear Trib. Width ft 24.0 Line Trib. Length ft 31.0 Line Total Length ft 31.0 Line Total Shear lbs 1,607 Line Unit Shear plf 217 x 8 ft / 7.42 ft = 218.9 plf 2 v = 510 plf (1-Side 15/32'' Str. I w/ 10d Common Nails @ 4''-6''-12'' O.C.) Drag Length ft 6.0 Drag Force lbs 648 Strap Type MST27 Roof DL Trib. Width ft 12.0 12.0 - Ceiling DL Trib. Width ft 12.0 12.0 - Wall Height ft - Wall Dead Load plf - Wall Shear Force lbs 1,607 Uplift Force (Demand) lbs 3,283 Holdown Type HDU5 Uplift Force (Capacity) lbs 4,253 Wall Height LINE 100% Wood Shearwall 10d 35-24 UMIH Suite H_SANTA ANA_R0.xls, Shearwall Line 2. Page 12 800 N Tustin Ave Unit #H1/23/2025 TABLES REFERENCED IN BEAM DESIGN SPREADSHEET 2018 NDS Table 4A fb fv E Select Str 1,500 180 1,900,000 No.1&Better 1,200 180 1,800,000 No.1 1,000 180 1,700,000 No.2 900 180 1,600,000 No.3 525 180 1,400,000 Stud 700 180 1,400,000 2018 NDS Table 4D fb fv E Dense Str 1,900 170 1,700,000 Select Str 1,600 170 1,600,000 Dense No. 1 1,550 170 1,700,000 No.1 1,350 170 1,600,000 Dense No. 2 1,000 170 1,400,000 No.2 875 170 1,300,000 Other Material Prllm2.0E 2,900 290 2,000,000 Mcrlm1.8E 2,600 285 1,800,000 Mcrlm1.9E 2,600 285 1,900,000 Steel Fy=36 ksi 23,760 14400 29,000,000 Steel Fy=46 ksi 30,360 18400 29,000,000 Steel Fy=50 ksi 33,000 20000 29,000,000 1. FOR DOUGLAS FIR-LARCH USE 19% MAX. MOISTURE CONTENT LOAD SYMBOLS AND NOTATION D = Dead Load E = Earthquake Load Lr = Roof Live Load W = Wind Load L = Floor Live Load ASCE7-16 2.4 LOAD COMBINATION - ALLOWABLE STRESS DESIGN 1. D 2. D + Lr Load Duration = 1.25 3. D + L Max. (Dead + Live) 4. D + 0.75 (Lr + L) Load Duration = 1.25 5.(1.0 + 0.14SDS)D + 0.7E 6.(1.0 + 0.105SDS)D + 0.525E + 0.75(L + Lr) 7.(0.6 − 0.14SDS)D + 0.7E ASCE7-16 12.4.3.2 TABLE 1604.3 (2022 CBC) DEFLECTION LIMITS Roof Members L D + L Supporting Plaster Ceiling l / 360 l / 240 Supporting Nonplaster Ceiling l / 240 l / 180 Not Supporting Ceiling l / 180 l / 120 Floor Members l / 360 l / 240 Max. (Dead + Live + Lateral) Allowable Stress Increase = 1.2  = 2.5 For Flexible Diaphragm WWPA Design Values for Visually Graded (2"-4") Design Values for Visually Graded (5" & Larger) Douglas Fir-Larch 1 WWPA Douglas Fir-Larch 1 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in Beam Design Page 13 800 N Tustin Ave Unit #H1/23/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 ALLOWABLE STRESSES REPETITIVE MEMBER NO NO NO NO NO NO REPETITIVE FACTOR, Cr 1.00 1.00 1.00 1.00 1.00 1.00 SIZE FACTOR, Cf 0.97 1.00 1.20 1.00 1.00 1.30 BENDING STRESSES, F'b psi 1,308 2,900 1,080 2,900 2,900 1,170 SHEAR STRESSES, F'v psi 170 290 180 290 290 180 MODULUS OF ELASTICITY ksi 1,700 2,000 1,600 2,000 2,000 1,600 UNIFORM DISTRIBUTED LOAD OVER FULL SPAN ROOF TRIB. WIDTH ft 4.00 2.00 16.00 21.00 13.00 CEILING TRIB. WIDTH ft 1.33 - - 7.00 7.00 FLOOR TRIB. WIDTH ft DECK TRIB. WIDTH ft WALL HEIGHT ft 6.00 6.00 3.00 WALL TYPE (EXT, INT)EXT EXT EXT AUTO CALC BEAM WEIGHT TOTAL DEAD LOAD (D plf 39.80 127.90 267.20 TOTAL ROOF LIVE LOAD (L plf 40.00 20.00 160.00 TOTAL FLOOR LIVE LOAD (L plf - - - PARTIALLY DISTRIBUTED LOAD ROOF TRIB. WIDTH ft CEILING TRIB. WIDTH ft FLOOR TRIB. WIDTH ft DECK TRIB. WIDTH ft WALL HEIGHT ft WALL TYPE (EXT, INT) TOTAL DEAD LOAD (D plf - - - TOTAL ROOF LIVE LOAD (L plf - - - TOTAL FLOOR LIVE LOAD (L plf - - - FROM (LEFT SUPPORT) ft LENGTH OF LOAD ft TRIANGULAR DISTRIBUTED LOAD ROOF TRIB. WIDTH ft TOTAL DEAD LOAD (D plf - - - TOTAL ROOF LIVE LOAD (L plf - - - CONCENTRATED LOADS P1 CHILLER CB1 DEAD LOAD (P D ) lbs 0.8 618.2 ROOF LIVE LOAD (P Lr) lbs 620.0 FLOOR LIVE LOAD (P L ) lbs - - LATERAL, P (W or 0.7E) lbs - - DIST. (LEFT SUPPORT) ft 1.00 15.50 P2 CHILLER DEAD LOAD (P D ) lbs 0.8 ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft 6.50 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 14 800 N Tustin Ave Unit #H1/23/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 P3 DEAD LOAD (P D ) lbs ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft P4 DEAD LOAD (P D ) lbs ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft LOAD CASE 1: D MAX. BENDING MOMENT lb-ft 4,784 1,023 1,411 MAX. DEFLECTION in 0.285 0.032 0.007 LEFT REACTION lbs 618 512 868 RIGHT REACTION lbs 617 512 868 LOAD CASE: Lr MAX. BENDING MOMENT lb-ft 4,805 160 845 MAX. DEFLECTION in 0.286 0.005 0.004 LEFT REACTION lbs 620 80 520 RIGHT REACTION lbs 620 80 520 LOAD CASE: L MAX. BENDING MOMENT lb-ft - - - MAX. DEFLECTION in - - - LEFT REACTION lbs - - - RIGHT REACTION lbs - - - LOAD CASE 2: D + Lr Wood Load Duration Factor = 1.25 MAX. BENDING MOMENT lb-ft 7,671 947 1,805 MAX. DEFLECTION in 0.572 0.037 0.011 LEFT REACTION lbs 991 473 1,111 RIGHT REACTION lbs 990 473 1,111 LOAD CASE 3:D + L Wood Load Duration Factor = 1.0 MAX. BENDING MOMENT lb-ft 4,784 1,023 1,411 MAX. DEFLECTION in 0.285 0.032 0.007 LEFT REACTION lbs 618 512 868 RIGHT REACTION lbs 617 512 868 LOAD CASE 4: D + 0.75 (Lr + L)Wood Load Duration Factor = 1.25 MAX. BENDING MOMENT lb-ft 6,710 915 1,636 MAX. DEFLECTION in 0.500 0.036 0.010 LEFT REACTION lbs 1,083 572 1,258 RIGHT REACTION lbs 1,082 572 1,258 LOAD CASE 5:(1.0 + 0.14SDS)D + 0.7E Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 3,423 732 1,010 MAX. DEFLECTION in 0.272 0.030 0.006 LEFT REACTION lbs 590 488 829 RIGHT REACTION lbs 589 488 829 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 15 800 N Tustin Ave Unit #H1/23/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 LOAD CASE 6:(1.0 + 0.105SDS)D + 0.525E + 0.75(L + Lr)Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 5,567 784 1,374 MAX. DEFLECTION in 0.443 0.033 0.009 LEFT REACTION lbs 959 523 1,127 RIGHT REACTION lbs 958 523 1,127 LOAD CASE 7:(0.6 − 0.14SDS)D + 0.7E Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 1,361 291 401 MAX. DEFLECTION in 0.108 0.012 0.003 LEFT REACTION lbs 234 194 329 RIGHT REACTION lbs 234 194 329 CHECK BENDING STRESSES MAX. BENDING MOMENT lb-ft 7,671.0 - 1,023.2 1,804.9 - - SECTION MODULUS, S in3 220.2 114.3 49.9 114.3 114.3 30.7 BENDING STRESS psi 418.0 - 246.0 189.4 - - CHECK BENDING STRESS RATIO 32% OK 0% OK 23% OK 7% OK 0% OK 0% OK CHECK SHEAR STRESSES #VALUE!#VALUE! #VALUE! MAX. SHEAR FORCE lbs 1,083.2 #VALUE!571.60 1,258.40 #VALUE! #VALUE! SECTION AREA, A in2 85.25 49.00 32.38 49.00 49.00 25.38 SHEAR STRESS, fv psi 19.06 #VALUE!26.48 38.52 #VALUE! #VALUE! CHECK SHEAR STRESS RATIO 11% OK #VALUE!15% OK 13% OK #VALUE! #VALUE! CHECK DEFLECTION #VALUE!#VALUE! #VALUE! MOMENT OF INERTIA, I in4 1,706.78 800.33 230.84 800.33 800.33 111.15 MAX. DEFLECTION, DL in 0.285 0.032 0.007 MAX. DEFLECTION, LL in 0.286 #VALUE!0.005 0.004 #VALUE! #VALUE! DEFLECTION LIMITS, LL L / 360 L / 360 L / 360 L / 360 L / 360 L / 360 CHECK DEFLECTION LL < 1.03 OK #VALUE!< 0.27 OK < 0.22 OK #VALUE! #VALUE! MAX. DEFLECTION, DL+LL in 0.572 #VALUE!0.037 0.011 #VALUE! #VALUE! DEFLECTION LIMITS, DL+LL L / 240 L / 240 L / 240 L / 240 L / 240 L / 240 CHECK DEFLECTION (DL+LL)< 1.55 OK #VALUE!< 0.4 OK < 0.33 OK #VALUE! #VALUE! 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 16 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:TJI REACRION Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design Douglas Fir-Larch No.2 875.0 875.0 600.0 625.0 1,300.0 470.0 170.0 425.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Point Load : D = 0.750 k @ 1.0 ft, (CHILLER#1) Point Load : D = 0.750 k @ 6.50 ft, (CHILLER#2) .DESIGN SUMMARY Design N.G. Maximum Bending Stress Ratio 1.160: 1 Load Combination D Only Span # where maximum occurs Span # 1 Location of maximum on span 6.562 ft 30.45 psi= = 708.75 psi 3x14Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination D Only = = = 153.00 psi== Section used for this span 3x14 Maximum Shear Stress Ratio 0.199 : 1 0.000 ft= = 821.85 psi Maximum Deflection 0 <360 326 Ratio =0 <240 Max Downward Transient Deflection 0 in 0Ratio =<360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 1.138 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v n/a n/a Span: 1 : D Only n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 1.160 0.199 0.90 0.900 1.001.00 1.00 5.01 821.9 708.8 0.67 153.030.5 0.00.0 1 0.391 0.067 1.60 0.900 1.001.00 1.00 3.01 493.1 1,260.0 0.40 272.018.3 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections D Only 1 1.1381 13.916 0.0000 0.000 . Page 17 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:TJI REACRION Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 1.430 0.293 Max Upward from Load Combinations 0.858 0.176 Max Upward from Load Cases 1.430 0.293 D Only 1.430 0.293 +0.60D 0.858 0.176 Page 18 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RB2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design Douglas Fir-Larch No.1 1,350.0 1,350.0 925.0 625.0 1,600.0 580.0 170.0 675.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.0160, Lr = 0.0120 ksf, Tributary Width = 31.0 ft, (ROOF) Point Load : D = 1.320 k @ 10.0 ft, (TJI #1) Point Load : D = 1.320 k @ 14.0 ft, (TJI #2) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.757: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 9.985 ft 97.95 psi= = 1,566.07 psi 6x24Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 212.50 psi== Section used for this span 6x24 Maximum Shear Stress Ratio 0.461 : 1 17.058 ft= = 1,186.16 psi Maximum Deflection 0 <360 677 Ratio =0 <240 Max Downward Transient Deflection 0.115 in 1977Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.337 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.700 0.427 0.90 0.928 1.001.00 1.00 33.30 789.3 1,127.6 5.63 153.065.3 0.00.0 1 0.757 0.461 1.25 0.928 1.001.00 1.00 50.04 1,186.2 1,566.1 8.44 212.597.9 0.00.0 1 0.694 0.423 1.25 0.928 1.001.00 1.00 45.85 1,086.9 1,566.1 7.74 212.589.8 0.00.0 1 0.236 0.144 1.60 0.928 1.001.00 1.00 19.98 473.6 2,004.6 3.38 272.039.2 . Page 19 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RB2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.3367 9.639 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 9.485 10.179 Max Upward from Load Combinations 9.485 10.179 Max Upward from Load Cases 5.951 6.645 D Only 5.951 6.645 +D+Lr 9.485 10.179 +D+0.750Lr 8.601 9.296 +0.60D 3.570 3.987 Lr Only 3.534 3.534 Page 20 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RB3- 5.5X18 GLLM Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design DF/HF 24F-V5 2,400.0 1,600.0 1,450.0 650.0 1,700.0 900.0 215.0 1,100.0 26.840 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity 1,500.0 ksi 790.0 ksi Ebend- yy Eminbend - yy Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Load for Span Number 1 Point Load : D = 6.650, Lr = 3.530 k @ 0.0 ft, (RB2) Uniform Load : D = 0.010, Lr = 0.0120 ksf, Tributary Width = 31.0 ft, (ROOF) Load for Span Number 2 Uniform Load : D = 0.010, Lr = 0.0120 ksf, Tributary Width = 31.0 ft, (ROOF) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.995: 1 Load Combination +D+Lr Span # where maximum occurs Span # 2 Location of maximum on span 0.000 ft 180.80 psi= = 1,881.72 psi 5.5x18Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 268.75 psi== Section used for this span 5.5x18 Maximum Shear Stress Ratio 0.673 : 1 2.503 ft= = 1,871.66 psi Maximum Deflection 1134 >=360 541 Ratio =18512 >=240 Max Downward Transient Deflection 0.382 in 753Ratio =>=360 Max Upward Transient Deflection -0.085 in Ratio = Max Downward Total Deflection 0.532 in Ratio =>=240 Max Upward Total Deflection -0.016 in fb: Actual F'b fv: Actual F'v Span: 2 : Lr Only Span: 1 : Lr Only Span: 2 : +D+Lr Span: 2 : D Only .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCV rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.820 0.585 0.90 1.000 1.001.00 1.00 29.23 1,180.9 1,440.0 7.47 193.5113.2 2 0.872 0.585 0.90 0.941 1.001.00 1.00 29.23 1,180.9 1,354.8 4.67 193.5113.2 0.00.0 1 0.936 0.673 1.25 1.000 1.001.00 1.00 46.32 1,871.7 2,000.0 11.93 268.8180.8 2 0.995 0.673 1.25 0.941 1.001.00 1.00 46.32 1,871.7 1,881.7 9.30 268.8180.8 0.00.0 Page 21 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RB3- 5.5X18 GLLM Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCV rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu 1.00Length = 4.0 ft 1 0.849 0.610 1.25 1.000 1.001.00 1.00 42.05 1,699.0 2,000.0 10.82 268.8163.9 2 0.903 0.610 1.25 0.941 1.001.00 1.00 42.05 1,699.0 1,881.7 8.15 268.8163.9 0.00.0 1 0.277 0.197 1.60 1.000 1.001.00 1.00 17.54 708.5 2,560.0 4.48 344.067.9 2 0.294 0.197 1.60 0.941 1.001.00 1.00 17.54 708.5 2,408.6 2.80 344.067.9 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections Lr OnlyD Only 1 0.1261 0.000 -0.0407 2.369 2 0.5319 13.676 0.0000 2.369 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 23.317 6.475 Max Upward from Load Combinations 23.317 6.475 Max Upward from Load Cases 13.123 3.752 D Only 13.123 2.724 +D+Lr 23.317 6.475 +D+0.750Lr 20.769 5.537 +0.60D 7.874 1.634 Lr Only 10.194 3.752 Page 22 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RTU-Curb Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design Douglas Fir-Larch No.2 875.0 875.0 600.0 625.0 1,300.0 470.0 170.0 425.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.1250 ksf, Tributary Width = 3.0 ft, (Chiller) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.655: 1 Load Combination D Only Span # where maximum occurs Span # 1 Location of maximum on span 3.000 ft 54.18 psi= = 1,023.75 psi 4x8Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination D Only = = = 153.00 psi== Section used for this span 4x8 Maximum Shear Stress Ratio 0.354 : 1 0.000 ft= = 670.12 psi Maximum Deflection 0 <360 932 Ratio =0 <240 Max Downward Transient Deflection 0 in 0Ratio =<360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.077 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v n/a n/a Span: 1 : D Only n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.655 0.354 0.90 1.300 1.001.00 1.00 1.71 670.1 1,023.8 0.92 153.054.2 0.00.0 1 0.221 0.120 1.60 1.300 1.001.00 1.00 1.03 402.1 1,820.0 0.55 272.032.5 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections D Only 1 0.0772 3.022 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 1.141 1.141 Page 23 800 N Tustin Ave Unit #H1/23/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RTU-Curb Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from Load Combinations 0.685 0.685 Max Upward from Load Cases 1.141 1.141 D Only 1.141 1.141 +0.60D 0.685 0.685 Page 24 800 N Tustin Ave Unit #H1/23/2025 COLUMN AXIAL CAPACITY WOOD PROPERTIES: Use Douglas Fir-Larch CF =1.1 Kce = 0.30 Buckling about x-axis?YES Species:Cm =1.0 c = 0.80 Check le/d reqmt.OK! E =CT =1.0 Kf = 1.00 F'c =Ct = 1.0 (for bolted or nailed members) E' = Ci =1.0 Fc* = CD =1.0 No. of 1+ Fce/Fc*Column Plies 2c Capacity C01 1 - 2x 4 1.5 3.50 8 64.0 27.4 27.4 558.27 0.597 1.00 0.498 465.79 2.45 kips C02 2 - 2x 4 3.0 3.50 8 32.0 27.4 27.4 558.27 0.597 1.00 0.498 465.79 4.89 kips C03 1 - 2x 6 1.5 5.50 8 64.0 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 6.22 kips C04 2 - 2x 6 3.0 5.50 8 32.0 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 12.43 kips C05 1 - 2x 8 1.5 7.50 8 64.0 12.8 12.8 2,563.48 2.742 2.34 0.910 850.54 9.57 kips C06 2 - 2x 8 3.0 7.25 8 32.0 13.2 13.2 2,395.43 2.562 2.23 0.902 843.35 18.34 kips WOOD PROPERTIES: Use Douglas Fir-Larch CF =1.1 Kce = 0.30 Buckling about x-axis?YES Species:Cm =1.0 c = 0.80 Check le/d reqmt.OK! E =CT =1.0 Kf = 1.00 F'c =Ct = 1.0 (for bolted or nailed members) E' = Ci =1.0 Fc* = CD =1.0 No. of 1+ Fce/Fc*Column Plies 2c Capacity C07 1 - 4x 4 3.5 3.50 8 27.4 27.4 27.4 558.27 0.597 1.00 0.498 465.79 5.71 kips C08 1 - 4x 6 3.5 5.50 8 27.4 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 14.50 kips C09 1 - 4x 8 3.5 7.50 8 27.4 12.8 12.8 2,563.48 2.742 2.34 0.910 850.54 22.33 kips C10 1 - 6x 6 5.5 5.50 8 17.5 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 22.79 kips C11 1 - 6x 8 5.5 7.25 8 17.5 13.2 13.2 2,395.43 2.562 2.23 0.902 843.35 33.63 kips Note: KcE = 0.510 - 0.839(COV)where COV = 0.25 - sawn lumber 0.3 - for visually graded lumber 0.15 - MEL 0.384 - for machine evaluated lumber (MEL)0.11 - MSR (machine stress rated) 0.418 - for roducts w/ COV<=0.11 0.10 - glu-lam le/dx le/dx F'cCOL(le/d) Fce Fce/Fc*CPdxlex,y 1,500 psi 1,700,000 psi 1,650 psi le/dy 935 psi Size dy Stud 1,400,000 psi 850 psi 1,400,000 psi No.1 1,700,000 psi Size le/dyCOL dy dx lex,y F'c(le/d) Fce Fce/Fc* CP 35-24 UMIH Suite H_SANTA ANA_R0.xls, Column Design Page 25 800 N Tustin Ave Unit #H1/23/2025 SYMBOLS LEGENDABBREVIATIONS -#- 1P SINGLE POLE 1PH SINGLE-PHASE 2/C TWO-CONDUCTOR 3/C THREE-CONDUCTOR 3PH THREE-PHASE 4/C FOUR-CONDUCTOR -A- A/E ARCHITECT/ENGINEER AC ALTERNATING CURRENT ACC ACCESSIBLE ADA AMERICANS DISABILITIES ACT ADDL ADDITIONAL ADDM ADDENDUM AH AMPERE HOUR AHJ AUTHORITY HAVING JURISDICTION AMP AMPERE ANN ANNUNCIATOR ANT ANTENNA APPD APPROVED APPX APPENDIX ARCH ARCHITECT ATS AUTOMATIC TRANSFER SWITCH AUTO AUTOMATIC AUX AUXILIARY AV AUDIO VISUAL AVG AVERAGE AWG AMERICAN WIRE GAUGE -B- BAS BUILDING AUTOMATION SYSTEM BAT BATTERY BC BUILDING CODE BFF BELOW FINISH FLOOR BKGD BACKGROUND BLDG BUILDING BLW BELOW BRKR BREAKER BRZ BRONZE BSMT BASEMENT BSTR BOOSTER BTWN BETWEEN BX INTERLOCKED ARMORED CABLE -C- CAB CABINET CAP CAPACITOR CATW CATWALK CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CD CONSTRUCTION DOCUMENT CERT CERTIFY CF CONTRACTOR FURNISHED CG COMMON GROUND CHK CHECK CKT CIRCUIT CKT BRKR CIRCUIT BREAKER CL CENTER LINE / CLOSE CLG CEILING CLO CLOSET CLR CLEAR C CONDUIT CO CONDUIT ONLY COAX COAXIAL CABLE COL COLUMN COM COMMON COMPR COMPRESSOR COMM COMMUNICATION CONC CONCRETE CONST CONSTRUCTION CORR CORRIDOR CP CONTROL PANEL CSI CONSTRUCTION SPECIFICATION INSTITUTE CT CURRENT TRANSFORMER CTRL CONTROL CATV CABLE TELEVISION -D- DC DIRECT CURRENT DEF DEFINITION DEG DEGREE DEMO DEMOLITION DET DETAIL DGTL DIGITAL DIA DIAMETER DIAG DIAGRAM DIM DIMENSION DIR DIRECTION DISC DISCONNECT DISCH DISCHARGE DISTR PNL DISTRIBUTION PANEL DIV DIVISION DMR DIMMER DS DISCONNECT SWITCH DWG DRAWING DX DUPLEX -E- EA EACH EL ELEVATION ELEC ELECTRIC EMER EMERGENCY EMR ELEVATOR MACHINE ROOM EMS ENERGY MANAGEMENT SYSTEM EMT ELECTRICAL METALLIC TUBING ENGR ENGINEER EQ EQUAL EQUIP EQUIPMENT EQUIV EQUIVALENT ESR ELECTRICAL SERVICE REQUIREMENT ETR EXISTING TO BE RELOCATED EX EXAMPLE EXH FN EXHAUST FAN EXIST EXISTING EXT EXTERNAL EXT LT EXIT LIGHT -F- F FAHRENHEIT FA FIRE ALARM FC FOOTCANDLE FDR FEEDER FLA FULL LOAD AMPS FLEX FLEXIBLE FLMT FLUSH MOUNT FLR FLOOR FLUOR FLUORESCENT FR FIRE RATING FREQ FREQUENCY FT FOOT FU FUSE FU SW FUSED SWITCH FUT FUTURE -G- G GROUND GC GENERAL CONTRACTOR GEN GENERATOR GFCI GROUND FAULT CIRCUIT INTERRUPTER GFR GROUND FAULT RELAY GRD OUT GROUNDED OUTLET -H- HP HORSEPOWER HZ HERTZ -J- JB JUNCTION BOX -L- LED LIGHT EMITTING DIODE LM LUMEN LT LIGHT LTG LIGHTING LTG PNL LIGHTING PANEL LV LOW VOLTAGE -M- MAX MAXIMUM MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MECH MECHANICAL MIN MINIMUM -N- NEUT NEUTRAL NTS NOT TO SCALE -P- P POLE PB PULL BOX PH PHASE PNL PANEL PWR POWER -R- R REMOVE RE RELOCATED EXISTING REC RECESSED RECPT RECEPTACLE REQD REQUIRED RM ROOM -S- SD SMOKE DETECTOR SPEC SPECIFICATION SPKR SPEAKER SWBD SWITCHBOARD SWGR SWITCHGEAR -T- TC TIME CLOCK TEL TELEPHONE TELCOM TELECOMMUNICATIONS THRU THROUGH TV TELEVISION TVSS TRANSIENT VOLTAGE SURGE SUPRESSOR TYP TYPICAL -U- UC UNDERCOUNTER UG UNDERGROUND UL UNDERWRITERS LABORATORIES UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY UGPS UNDERGROUND PULL SECTION -V- V VOLTAGE VA VOLT AMPERE VD VOLTAGE DROP VFD VARIABLE FREQUENCY DRIVE VIF VERIFY IN FIELD -W- W WATT OR WIRE W/WITH W/O WITHOUT WP WEATHERPROOF WR WEATHER RESISTANT -X- XFER TRANSFER XFMR TRANSFORMER GENERAL NOTES SHEET INDEX SCOPE OF WORK TENANT IMPROVEMENT FOR THE UNITED MEDICAL IMAGING CENTER. ELECTRICAL SUBMITTAL FOR ENERGY AND POWER REQUIREMENTS. NEW 400A, 277/480V, 3PH, 4W ELECTRICAL SERVICE FROM SOUTHERN CALIFORNIA EDISON (SCE). 1.GREEN INSULATED COPPER GROUNDING CONDUCTOR SHALL BE INSTALLED IN ALL BRANCH CIRCUITS AND FEEDERS. 2.ALL LIGHTING CONTROL DEVICES SHALL BE CALIFORNIA ELECTRICAL CODE CERTIFIED. 3.PROJECT SPECIFICATIONS ARE AN INTEGRAL PART OF THESE DRAWINGS. 4.UNLESS LISTED OTHERWISE, THE AMPACITY OF 600V OR LESS CONDUCTOR SHALL BASED ON THE TERMINALS NOT TO EXCEED 60°C(140°F) FOR CONDUCTOR SIZE 14 THROUGH 1AWG OR 75°C(167°F) FOR CONDUCTOR SIZES OVER 1AWG. 5.A SINGLE RECEPTACLES INSTALLED ON AN INDIVIDUAL BRANCH CIRCUIT SHALL HAVE AN AMPERE RATING OF NOT LESS THAN THAT OF THE BRANCH CIRCUIT. INDICATE THE RECEPTACLES RATING. 6.MINIMUM SIZE OF CONDUIT SHALL BE 3/4". MINIMUM SIZE OF NEUTRAL CONDUCTOR SHALL BE #10 AWG, U.O.N. MINIMUM SIZE OF CONDUCTOR SHALL BE #12 AWG, U.O.N. MINIMUM CONDUCTOR SIZE AT 120 VOLTS AND OVER 100FT CIRCUIT LENGTH SHALL BE #10 AWG, U.O.N. MINIMUM CONDUCTOR SIZE AT 277 VOLTS AND OVER 200FT. CIRCUIT LENGTH SHALL BE #10AWG U.O.N. 7.PROVIDE DEDICATED NEUTRALS FOR ALL BRANCH CIRCUITRY. 8.THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE OF THE WORK AND THOROUGHLY FAMILIARIZE HIMSELF WITH THE WORKING CONDITION AND THE EXACT NATURE AND EXTENT OF THE WORK TO BE PERFORMED. ELECTRICAL CONTRACTOR IS TO TAKE INTO CONSIDERATION SPECIAL OR UNUSUAL FEATURES PECULIAR TO THIS JOB. 9.MAINTAIN CLEARANCES PER AHJ REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT INSTALLED. 10.OBTAIN AND PAY FOR ALL ELECTRICAL PERMITS, INSPECTION FEES, ETC. 11.CONDUIT STUBS SHALL BE TERMINATED IN ACCESSIBLE LOCATIONS, SECURELY CAPPED AND IDENTIFIED BY VISIBLE MARKER. 12.INSTALL APPROVED GROUNDING BUSHING AT EACH TERMINATION OF RIGID CONDUIT, AND AS OTHERWISE REQUIRED BY CODE. 13.PROVIDE A MINIMUM OF 12" SEPARATION BETWEEN POWER AND TELEPHONE CONDUITS WHERE THEY ARE INSTALLED IN THE SAME TRENCH OR CROSS, U.O.N. 14.CONDUITS SHALL BE CLEAN OF WATER DEBRIS AND OTHER FOREIGN MATERIAL PRIOR TO PULLING CABLES. 15.ALL CONDUITS FOR FUTURE USE SHALL HAVE PULL ROPE LEFT IN PLACE. 16.THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND MARKING THE CORRECT PHASING OF THE BRANCH CIRCUIT OF THE ELECTRICAL PANELS AND BRANCH CIRCUITS. 17.ALL ELECTRICAL OUTLETS READILY ACCESSIBLE LOCATED IN THE BATHROOMS AND KITCHEN SHALL BE EQUIPPED WITH GROUND FAULT CIRCUIT INTERRUPTIVE DEVICE U.O.N. 18.ALL COLORS AND FINISHES OF ELECTRICAL EQUIPMENT AND LIGHTING FIXTURES TO BE VERIFIED WITH OWNER AND/OR ARCHITECT PRIOR TO ORDERING. 19.ELECTRICAL CONTRACTOR TO SIZE ALL J-BOXES AS PER TABLE 370-16A. ALL J-BOXES TO BE SQUARE 4"X 2-1/8" MINIMUM. ALL J-BOXES TO BE READILY ACCESSIBLE. 20.ALL PANELBOARDS, SWITCHBOARDS, ETC. SHALL BE RATED AT 75 DEGREES CELSIUS. 21.REFER TO ARCHITECTURAL OR SPACE PLANNING DRAWINGS FOR EXACT LOCATION OF LIGHTING FIXTURES, FURNITURE AND OTHER EQUIPMENT. IN CASE OF ANY DISCREPANCY BETWEEN THE ARCHITECTURAL OR ELECTRICAL DRAWINGS, THE FORMER TAKES PRECEDENCE. ELECTRICAL CONTRACTOR TO INFORM THE ENGINEER IMMEDIATELY. 22.FUSES SPECIFIED FOR MOTORS AND AIR CONDITIONING EQUIPMENT 600A AND UNDER SHALL BE TIME DELAY DUAL ELEMENT TYPE FRN-R (250V) AND FRS-R (600V) CLASS "L" U.O.N. 23.FUSES SPECIFIED IN SWITCHBOARDS 600A AND UNDER SHALL BE FAST ACTING TYPE KTN-R (250V) AND KTS-R (600V) CLASS RKI. FOR 601A AND ABOVE USE TYPE KTU (600V) CLASS "L" U.O.N. 24.WHERE VERIFICATION OF EXISTING CONDITIONS REQUIRE SIGNIFICANT CONSUMPTION OF TIME AND LABOR, AN ASSUMPTION WAS MADE BASED ON THE EXISTING DRAWINGS SUBMITTED BY THE CLIENT. ELECTRICAL CONTRACTOR IS TO VERIFY THIS INFORMATION IN FIELD AND PERFORM ACCORDING TO EXISTING CONDITIONS. 25.ALL ELECTRICAL MATERIALS SHALL BEAR THE UNDERWRITERS (OR EQUIVALENT TESTING AGENCY) LABEL. ELECTRICAL EQUIPMENT SHALL BE LISTED BY A CITY OF TUSTIN RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT. 26.UNLESS INFORMED OTHERWISE IN WRITING, THIS PROJECT HAS BEEN DETERMINED TO REQUIRE THE LOCAL CITY AUTHORITIES PLAN CHECK APPROVAL AND VALID PERMIT IN ACCORDANCE WITH THE LAW. ALL DESIGN WORK INDICATED ON PLANS AND SPECIFICATIONS IS SUBJECT TO REVIEW AND CHANGES BY SAID PLAN CHECK AUTHORITIES. 27.DO NOT ORDER ANY EQUIPMENT OR PERFORM ANY WORK OVER $500 IN TOTAL VALUE ON THE JOB UNTIL THE COMPLETION OF THE PLAN CHECK APPROVAL PROCESS AND OBTAINING OF ALL REQUIRED PERMITS. INSTALLATION OF ANY EQUIPMENT WITHOUT VALID PERMITS, WHEN REQUIRED, IS A VIOLATION OF THE CODE. 28.UNDER THE STATE OF CALIFORNIA CONTRACTORS STATE LICENSE BOARD REGULATIONS, ALL CONTRACTORS ARE REQUIRED TO ADHERE TO THE LOCAL CODES AND LAWS WITHOUT EXCEPTION. 29.ELECTRICAL CONTRACTOR TO OBTAIN ARCHITECTURAL APPROVAL OF ALL LIGHTING FIXTURES SPECIFIED FOR THE PROJECT PRIOR TO ORDERING. 30.ELECTRICAL CONTRACTOR SHALL PROVIDE CLEARANCES FOR ALL ELECTRICAL EQUIPMENT PER TABLE 110.26 (A) (1) CEC 2019. 31.PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION ON RECEPTACLE(S) LOCATED IN THE FOLLOWING AREAS: A.KITCHEN, BATHROOM, GARAGES, OUTDOORS, CRAWL SPACES, AND UNFINISHED BASEMENTS OF DWELLING UNITS. B.WITHIN 6 FEET OF LAUNDRY, UTILITY AND WET BAR SINK IN DWELLING UNITS. C.OUTDOOR SPACES. 36.THESE ELECTRICAL PLAN ARE SAID TO BE FINAL WHEN STAMPED AND APPROVED BY CITY OF TUSTIN BUILDING & SAFETY DEPARTMENT. PLAN CHECK REVISIONS (IF ANY) WILL BE ISSUED AT A LATER DATE AS AN ADDENDUM. 37.BONDING OF PIPING SYSTEMS IN ACCORDANCE WITH NEC ART. 250.90 SHALL INCLUDE BONDING OF ALL WATER, GAS, FIRE SPRINKLER, COMPRESSED AIR AND/OR ANY OTHER METALLIC PIPING. 38.THE WORK SHALL COMPLY WITH AND BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING LEGALLY CONSTITUTED AUTHORITIES AND CODES HAVING JURISDICTION. A.2022 CALIFORNIA ELECTRICAL CODE (CEC). B.2022 CALIFORNIA BUILDING CODE (CBC). C.2020 NATIONAL ELECTRICAL CODE (NEC). D.2022 CALIFORNIA MECHANICAL CODE (CMC). E.2022 CALIFORNIA PLUMBING CODE (CPC). F.2022 CALIFORNIA ENERGY CODE (CENC). 40.(A) ALL EXPOSED CONDUITS (NOT SUBJECT TO THE MOISTURE) SHALL BE ELECTRIC METALLIC TUBING (EMT). (B) EXPOSED RACEWAYS SHALL BE RIGID STEEL CONDUIT (RSC). (C). ALL VIBRATING MOTORIZED EQUIPMENT FINAL CONNECTION SHALL BE PROVIDED WITH LIQUID TIGHT FLEXIBLE CONDUIT. LENGTH SHALL NOT EXCEED 6-FT. 41.CONDUCTOR SIZING SHALL BE IN ACCORDANCE WITH ARTICLE 110.14(C) AND ARTICLE 310.15. 42.NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT. 43.120 VOLT SMOKE DETECTORS AND COMBINATION SMOKE & CO DETECTORS SHALL BE FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR WITH ALL REQUIRED LABOR, MATERIALS, CONDUITS, WIRING, BOXES AND 120 VOLT POWER FROM DEDICATED LOCK-ON CIRCUIT BREAKER. 44.ALL 125V, 15 AND 20 AMPERE RECEPTACLE AS REQUIRED IN CEC SECTION 210.52 IN DWELLING UNITS SHALL BE TAMPER-RESISTANCE. 45.FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE HOLDERS. 46.OBTAIN APPROVAL AND PERMIT VIA SEPARATE SUBMITTAL FOR ANY ELECTRICAL SUBSYSTEM WITH LOW VOLTAGE POWER SUPPLY OF MORE THAT 50VA AND/ OR 25V. (SECURITY SYSTEM, TELE/DATA, AUDIO/VISUAL AND HVAC DDS CONTROL, ETC.) 47.LOW VOLTAGE COMMUNICATION SYSTEMS SUCH AS TELEPHONE, CABLE TV, FIRE ALARM, SECURITY SYSTEMS ARE NOT PART OF THIS SCOPE OF WORK. CONTRACTOR SHALL COORDINATE WITH EACH SYSTEM INSTALLER AND PROVIDE REQUIRED CONDUITS WITH PULL WIRE AND 120 VOLT POWER. 48.ELECTRICAL CONTRACTOR IS TO COMPLY WITH THE LATEST ADA REQUIREMENTS RELATED TO THE HEIGHT OF THE OUTLETS, SWITCHES AND OTHER EQUIPMENT (NOT TO EXCEED 48" TO CENTER AND NOT BELOW 15" TO BOTTOM OF OUTLET BOX U.O.N.). 49.ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE WEATHERPROOF. ALL OUTDOOR RECEPTACLES SHALL BE GFCI PROTECTED AND PROVIDED WITH EXTRA-DUTY RATED "WEATHERPROOF-WHILE-IN-USE"COVER. RECEPTACLES WITHIN 6' OF SINK SHALL BE GFCI TYPE RECEPTACLE. 50.PROVIDE ALL EQUIPMENT, MATERIAL, LABOR, SUPERVISION, COSTS, AND SERVICES REQUIRED TO INSTALL COMPLETE AND WORKING SYSTEMS INCLUDING ITEMS REQUIRED BUT NOT NORMALLY SHOWN, SUCH AS LAMPS, HANGERS, BRACKETS, CLAMPS, COUPLINGS, BOXES, CONNECTORS AND HARDWARE EVEN THOUGH EACH AND EVERY ITEM IS NOT SPECIFICALLY SPECIFIED OR SHOWN. 51.THE CONTRACTOR SHALL EXAMINE THE COMPLETE SET OF CONTRACT DOCUMENTS FOR ALL TRADES, AS ISSUED BY THE ARCHITECT AND REVIEW DIMENSIONS, SPACE REQUIREMENTS AND POINT OF CONNECTIONS TO ALL EQUIPMENT. MAKE ANY MINOR ADJUSTMENTS NECESSARY TO AVOID CONFLICTS WITH THE BUILDING STRUCTURE AND THE WORK OF OTHER TRADES. 52.REFER TO THE ARCHITECTURAL DRAWINGS FOR THE LOCATIONS OF ALL FIRE RATED PARTITIONS, BUILDING EXPANSION JOINTS AND MOUNTING HEIGHTS OF EQUIPMENT. 53.ALL CONDUIT PENETRATIONS THROUGH WALL MUST BE SEALED, SLEEVED, AND PROPERLY SUPPORTED ON EACH SIDE OF THE WALL. 54.COORDINATE CONDUIT ROUTE IN FIELD WITH OTHER TRADES, EQUIPMENT, AND OWNER. VERIFY EXACT LOCATION AND MOUNTING HEIGHTS WITH ARCHITECT PRIOR TO INSTALLATION. 55.THE DRAWINGS INDICATE, IN A DIAGRAMMATIC MANNER, THE DESIRED LOCATIONS AND ARRANGEMENT OF THE COMPONENTS OF THE ELECTRICAL WORK. DETERMINE EXACT CONDUIT ROUTING, CONDUIT BENDS, AUXILIARY JUNCTION BOXES, SUPPORTS, AND UNDEFINED CONSTRUCTION DETAILS, AS A JOB CONDITION TO BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODE REQUIREMENTS. DO NOT SCALE THE ELECTRICAL DRAWINGS FOR LOCATIONS OF ANY ELECTRICAL, ARCHITECTURAL, STRUCTURAL, CIVIL, OR MECHANICAL ITEMS OR FEATURES, REFER TO ARCHITECTURAL AND STRUCTURAL DIMENSIONAL DRAWINGS. 56.ALL CONDUCTORS SHALL BE COPPER TYPE THWN INSULATION. 57.FOR EQUIPMENT REQUIRING SPECIAL RECEPTACLE, PROVIDE RECEPTACLE WITH NEMA CONFIGURATION TO MATCH EQUIPMENT PLUG. VERIFY WITH EQUIPMENT MANUFACTURER. 58.WHERE MULTI-HOMERUNS ARE INDICATED ON DRAWINGS INDICATING THE SAME PANEL BOARD CIRCUIT NUMBER, PROVIDE JUNCTION BOX ABOVE ACCESSIBLE CEILING AND ROUTE ONE SET OF WIRES TO CIRCUIT BREAKERS. 59.ALL GROUNDING ELECTRODES THAT ARE PRESENT AT EACH BUILDING OR STRUCTURE SHALL BE BONDED TOGETHER. 60.FOR SMALL AC MOTORS NOT HAVING BUILT-IN THERMAL OVERLOAD PROTECTION, PROVIDE MANUAL MOTOR STARTERS WITH OVERLOAD HEATER ELEMENTS SIZED TO THE NAMEPLATE CURRENT RATING OF THE MOTOR. SMALL AC MOTORS WITH BUILT-IN THERMAL OVERLOAD PROTECTION, PROVIDE ELEMENTS SIZED TO THE NAMEPLATE CURRENT RATING OF THE MOTOR. SMALL AC MOTORS WITH BUILT-IN THERMAL OVERLOAD PROTECTION, PROVIDE A HORSEPOWER RATED TOGGLE TYPE DISCONNECT SWITCH. 61.ALL PANELBOARDS SHALL BE MARKED WITH IDENTIFYING NAMEPLATES TO INDICATE THE DESIGNATIONS USED ON THESE DRAWINGS. PROVIDE NEW TYPEWRITTEN PANELBOARD SCHEDULE, CORRECTLY FILLED OUT BASED ON FINAL AS-BUILT RECORD DRAWING CONDITION, FOR EVERY PANELBOARD. 62.OUTLETS SHALL BE INSTALLED AT 15" TO BOTTOM ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED ON THE ARCHITECTURAL DRAWINGS OR LOCATED AT MILLWORK. VERIFY EXACT MOUNTING HEIGHT OF ALL OUTLETS WITH ARCHITECT PRIOR TO INSTALLATION. 63.VERIFY THE EXACT LOCATION OF MECHANICAL AND PLUMBING EQUIPMENT AND OTHER EQUIPMENT REQUIRING ELECTRICAL CONNECTION, PRIOR TO ROUGH IN. REFER TO MECHANICAL AND PLUMBING DRAWINGS. WHERE INDICTED ON MECHANICAL AND PLUMBING DRAWINGS AS PART OF THE DRAWING PACKAGE AND NOT COVERED IN THIS PLAN, PROVIDE NECESSARY POWER, CONDUIT AND CONTROL WIRING (IF LOW VOLTAGE, PROVIDE TRANSFORMERS AS REQUIRED) INCLUDING CONDUIT AND CONTROL WIRING BETWEEN INDOOR AND OUTDOOR UNITS. COORDINATE EXACT POWER REQUIREMENTS INCLUDING BREAKER, DISCONNECT AND FEEDER SIZES WITH EQUIPMENT SUBMITTALS PRIOR TO INSTALLATION. 64.VERIFY ACTUAL MOTOR AND APPLIANCE RATINGS AND LOADS WITH EQUIPMENT SUBMITTALS AND EQUIPMENT MANUFACTURER IN ORDER TO PROVIDE CORRECTLY SIZED BREAKERS, FEEDERS, DISCONNECTS AND OUTLETS. SUBMIT TO ARCHITECT ANY NECESSARY REVISIONS NECESSARY PRIOR TO INSTALLATION. ALL CHANGES SHALL BE SHOWN ON RECORD DRAWINGS. 65.ELECTRICAL OUTLETS AND LIGHTING CIRCUITS SHALL BE PROPERLY IDENTIFIED. OUTLETS SHALL BE LABELED ON BACKSIDE OF COVER-PLATES WITH THE ELECTRICAL, PANEL/CIRCUIT SUPPLYING THE OUTLETS. CIRCUITS IN CONDUITS SHALL BE IDENTIFIED BY CIRCUIT NUMBER, VOLTAGE AND PANEL. 66.PROVIDE FIRE RATED BOX FOR ALL RECESSED JUNCTION BOXES AND PANELS LOCATED IN FIRE RATED WALLS AND CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF FIRE RATED WALLS AND CEILINGS. NO.TITLE SCALE E0.01 GENERAL NOTES SHEET INDEX AND SYMBOLS LIST NO SCALE E0.02 ELECTRICAL SPECIFICATIONS NO SCALE E0.03 TITLE 24 INDOOR NO SCALE E0.04 TITLE 24 OUTDOOR NO SCALE E2.01 SINGLE LINE DIAGRAM NO SCALE E4.01 ELECTRICAL SITE PLAN NO SCALE E5.01 POWER PLAN 1/16" = 1'-0" E5.02 MECHANICAL POWER PLAN 1/4" = 1'-0" E5.03 ROOF POWER PLAN 1/4" = 1'-0" E6.01 LIGHTING PLAN 1/4" = 1'-0" E7.01 EGRESS PHOTOMETRIC CALCULATIONS 1/4" = 1'-0" E7.01 EGRESS PHOTOMETRIC CALCULATIONS 1/4" = 1'-0" POWER OUTLETS FLOOR WALL CEILING DUPLEX QUADRUPLEX DUPLEX - VOICE - DATA GFCI DUPLEX SIMPLEX EMERGENCY DUPLEX EMERGENCY QUADRUPLEX EMERGENCY SIMPLEX DUPLEX-VOICE DUPLEX-DATA QUAD-VOICE QUAD-VOICE-DATA QUAD-DATA JUNCTION BOX POKE THRU SPLIT WIRE SPECIAL OUTLET MULTI OUTLET SURFACE RACEWAY WIRING 3/4" CONDUIT WITH 2#12 WIRES, UON. GROUND WIRE NOT SHOWN. 3/4" CONDUIT WITH 3#12 WIRES, UON. GROUND WIRE NOT SHOWN. 3/4" CONDUIT WITH 4#12 WIRES, UON. GROUND WIRE NOT SHOWN. CONDUIT HOMERUN TO PANEL BOARD 1LA WITH CIRCUIT 1,3,5 CAPPED CONDUIT CONDUIT RUN UNDERGROUND OR UNDER THE FLOOR SLAB CONDUIT TURNING DOWN CONDUIT TURNING UP CONDUIT BREAK LIGHTING FLOOR WALL CEILING RECESSED DOWNLIGHT 1X4 SURFACE MOUNTED LIGHT 2X4 SURFACE MOUNTED LIGHT 4FT WALL MOUNTED LIGHT 1X4 EMERGENCY LIGHT 2X4 EMERGENCY LIGHT 2X4 RECESSED LIGHT EXIT SIGN 1 FACE EXIT SIGN 1 FACE LEFT ARROW ANNOTATION TITLE MARK DETAIL OR PLAN NUMBER - 1 DETAIL OR PLAN REFE LOCATION FOUND IN E-201 DETAIL REFERENCE DETAIL NUMBER - 1 DETAIL FOUND IN E-501 SECTION MARK A2T SECTION NUMBER - 1 SECTION FOUND IN E-501 SHEET KEYNOTE REVISION CLOUD (DELTA 1) DETAIL BOUNDARY B DETAIL NUMBER - 2 LP4:12 PANEL:CIRCUIT A1 LP4:12 LIGHTING FIXTURE TYPE PANEL:CIRCUIT SWITCHES/CONTROLS FLOOR WALL CEILING LIGHT SWITCH - TIME OPERATED LIGHT SWITCH - SINGLE POLE SUBSCRIPT INDICATES CONTROLLING SWITCH LEG. LIGHT SWITCH - THREE WAY LIGHT SWITCH - KEY OPERATED LIGHT SWITCH - WITH PILOT LIGHT SWITCH - WITH THERMAL OVERLOAD DIMMER SWITCH SUBSCRIPT INDICATES CONTROLLING SWITCH LEG. VACANCY SENSOR SWITCH SUBSCRIPT INDICATES CONTROLLING SWITCH LEG. OCCUPANCY SENSOR PHOTOCELL OCCUPANCY SENSOR POWER PACK OVERRIDE SWITCH POWER DISTRIBUTION BOARD 480/277V OR 208/120V RECESSED PANEL 480/277V OR 208/120V SURFACE MOUNTED PANEL TRANSFORMER DISCONNECT SWITCH SWITCH - MOTOR RATED FUSED DISCONNECT SWITCH MAGNETIC MOTOR STARTER - NEMA SIZE 1 INDICATED STARTER - DISCONNECT SWITCH MOTOR VARIABLE FREQUENCY DRIVE PULL BOX MANHOLE FIRE ALARM DEVICES CARBON MONOXIDE SENSOR SMOKE DETECTOR COMBINATION SMOKE DETECTOR AND CARBON MONOXIDE SENSOR SINGLE LINE DIAGRAM CIRCUIT BREAKER SWITCH SWITCHGEAR BUSWAY GROUND FAULT RELAY DIGITAL METER U.O.N. TRANSFORMER - DELTA WYE-GROUNDED GENERATOR PANEL 2000 = AMPACITY 3-NO, 4-SINGLE, 5-DOUBLE = NEUTRAL (+) = ADDITIONAL INFO AS REQUIRED J J J A 1LA-1,3,5 OS OS PC PP OR T M PB MH GFR M G XXXXX XXXXX XXXXX XXXXX 2000-5+ CO SD SC FIRE ALARM NOTES 1.THE CONTRACTOR (LIFE SAFETY VENDOR) SHALL BE RESPONSIBLE FOR SUBMITTING COMPLETE FIRE ALARM PLANS, REQUIRED CONNECTION DIAGRAMS, WIRING DIAGRAMS, BATTERY CALCULATIONS AND WORST CASE VOLTAGE DROP CALCULATIONS TO THE CITY FIRE DEPARTMENT FOR REVIEW AND OBTAIN APPROVAL FROM THE CITY PRIOR TO INSTALLING THE SYSTEM. 2.AN APPROVED MANUAL AND AUTOMATIC FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH CFC, SECTION 907 AND CALIFORNIA BUILDING CODE. 3.VARIANCE FOR THE FIRE ALARM SYSTEM SHALL BE SEPARATE. ELECTRICAL CONTRACTOR TO PAY SEPARATE FEE FOR VARIANCE/MODIFICATION UPON PLAN CHECK RESUBMITTAL. ELECTRICAL PRE-DEMOLITION NOTES 1.PRIOR TO COMMENCEMENT OF DEMOLITION WORK, CONTRACTOR SHALL UNDERTAKE ELECTRICAL SURVEY TO TRACE ALL EXISTING BRANCH CIRCUITS/FEEDERS. CONTRACTOR SHALL CLEARLY IDENTIFY ALL CIRCUITS/FEEDERS THAT SERVE EXISTING TO REMAIN DEVICES/EQUIPMENT/FIXTURES/ETC. WITHIN OR OUTSIDE THE DEMISED AREA TO BE DEMOLISHED. THIS SHALL INCLUDE CIRCUITS THAT PASS THROUGH AND/OR FEED THE SPACE AND EXTEND OUTSIDE THE DEMISED AREA ON AND OFF THE FLOOR (E.G. ABOVE AND BELOW). 2.EXISTING TO REMAIN CIRCUITS WILL BE CLEARLY IDENTIFIED AT THE RESPECTIVE ELECTRICAL PANEL AS "TO REMAIN" WITH THE LOAD SERVED INDICATED. A SCHEDULE FOR EACH PANEL THE ACTIVE LOADS FEEDING OUTSIDE THE DEMISED PREMISES SHALL BE FURNISHED TO CLIENT/ENGINEER PRIOR TO COMMENCEMENT OF DEMOLITION (SEE NOTE 5). 3.THE ASSOCIATED CONDUIT FOR EXISTING TO REMAIN ACTIVE CIRCUITS SHALL BE CLEARLY IDENTIFIED IN THE ELECTRICAL CLOSET AND FOR A MINIMUM OF 24" OUTSIDE THE ELECTRICAL CLOSET PRIOR TO ANY DEMOLITION WORK. AFTER CEILING DEMO, THE ENTIRE LENGTH OF THE CIRCUIT CONDUIT SHALL BE CLEARLY MARKED. 4.THE METHOD OF INDICATING EXISTING TO REMAIN DEVICES/CIRCUITS/WIREWAYS, ETC. SHALL BE AGREED BETWEEN LL/CLIENT REPRESENTATIVE/EC AND DEMOLITION CONTRACTOR, PRIOR TO COMMENCEMENT OF DEMO. 5.THE EC SHALL BE RESPONSIBLE TO INDICATE ALL CIRCUITS TO REMAIN ON AN EXISTING FLOOR PLAN, (PROVIDED BY ARCHITECT/CLIENT REP). THE MARK-UP SHALL INDICATE POINT OF ORIGIN (EG. PANEL), CONDUIT ROUTE AND LOAD SERVED. DEMOLITION NOTES 1.PRIOR TO SUBMISSION OF THE BID, THIS CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS TO DETERMINE THEIR IMPACT ON THE EXECUTION OF WORK IN THIS CONTRACT. 2.THE DEMOLITION WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, ANY AND ALL MATERIALS, CONNECTIONS, EXTENSIONS, CUTTING, REPAIRING AND OTHER ELECTRICAL WORK, TEMPORARY OR PERMANENT, THAT MAY BE REQUIRED TO MAINTAIN SERVICE THROUGH THE COMPLETION OF THIS PROJECT. COORDINATE THE EXTENT OF THE DEMOLITION WORK WITH THE ARCHITECT. 3.EXISTING FEEDERS AND BRANCH CIRCUITING PASSING THROUGH THE AREA OF DEMOLITION AND SERVING OCCUPIED ADJACENT AREAS AND/OR INTERFERING WITH THE NEW WORK SHALL BE TRACED AND RELOCATED BY THIS CONTRACTOR. ALL NECESSARY SHUTDOWNS REQUIRED TO PERFORM THIS WORK SHALL BE COORDINATED WITH THE BUILDING MANAGEMENT. 4.WIRING, CONDUITS, AND SUPPORTS FOR FEEDERS AND BRANCH CIRCUITING SHALL BE REMOVED TO THEIR PANEL OF ORIGIN. 5.MAINTAIN THE CONTINUITY OF EXISTING BRANCH CIRCUITING SERVING REMAINING ELECTRICAL DEVICES OUTSIDE THE SCOPE OF WORK WHERE PORTIONS OF EXISTING BRANCH CIRCUITING ARE BEING REMOVED. 6.IDENTIFY AS SPARE ANY PROTECTIVE DEVICE IN EXISTING PANELS THAT ARE MADE SPARE DUE TO DEMOLITION. PANEL DIRECTORIES SHALL BE UPDATED ACCORDINGLY. 7.UNLESS OTHERWISE NOTED, REMOVE ALL POWER AND COMMUNICATIONS OUTLETS AND DEVICES COMPLETE WITH WIRING, RACEWAYS AND BACK BOXES IN AREA OF DEMOLITION. 8.ALL LIGHTING FIXTURES, SWITCHES AND ASSOCIATED WIRING AND CONDUIT IN AREA OF DEMOLITION SHALL BE REMOVED UNLESS OTHERWISE NOTED. 9.EXISTING BASE BUILDING FIRE ALARM SYSTEM DEVICES ARE TO REMAIN AND KEPT OPERATIONAL DURING ALL STAGES OF THE PROJECT. ALL DEVICES SHALL BE PROPERLY PROTECTED. POWER NOTES 1.REFER TO ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL DEVICES (I.E. RECEPTACLES, DATA/TELEPHONE OUTLETS, SECURITY DEVICES, PANELS, SPEAKER/STROBE, ETC. 2.ELECTRICAL CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF CIRCUITING IN AREAS WHICH ARE CONNECTED TO EXISTING ELECTRICAL DEVICES AND ELECTRICAL SERVICES STILL IN USE. 3.PROVIDE TIE BARS ON ALL SINGLE POLE CIRCUIT BREAKERS SERVING MULTI-WIRE BRANCH CIRCUITS IN COMPLIANCE WITH CEC ARTICLE 210.4(B). EXISTING CIRCUIT BREAKERS REQUIRING TIE HANDLES SHALL BE REPLACED WITH NEW TRIP FREE HANDLE BREAKERS. NEW BREAKERS SHALL MATCH BASE BUILDING STANDARDS, SHALL BE FROM SAME MANUFACTURER OF EXISTING BREAKERS THAT ARE TO REMAIN IN PANEL, AND SHALL BE COMPATIBLE WITH PANELBOARD. CONTRACTOR SHALL COORDINATE REQUIREMENTS IN FIELD WITH EXISTING EQUIPMENT. 4.ALL TELEPHONE/DATA CONDUIT STUB-UPS, WHERE GYPBOARD CEILINGS OCCUR, SHALL RUN INTO ACCESSIBLE CEILING AREAS. 5.ALL MECHANICAL EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE HVAC CONTRACTOR, WIRED BY THE ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL WIRE MECHANICAL EQUIPMENT AS PER AN APPROVED MANUFACTURER'S WIRING DIAGRAM. ALL CONTROL WIRING BY THE HVAC CONTRACTOR. 6.CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHES FOR ALL MECHANICAL EQUIPMENT THAT IS NOT FACTORY SUPPLIED UNLESS OTHERWISE NOTED ON MECHANICAL DRAWINGS. CONTRACTOR SHALL COORDINATE SIZE WITH MECHANICAL EQUIPMENT SPECIFICATIONS AND MECHANICAL CONTRACTOR. LIGHTING NOTES 1.REFER TO ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATION, QUANTITIES, TYPES, AND MOUNTING HEIGHTS OF LIGHT FIXTURES, EXIT SIGNS, SWITCHES, DIMMERS, ETC. 2.PRIOR TO ORDERING LIGHTING FIXTURES, COORDINATE WITH ARCHITECTURAL AND ENGINEERING INFORMATION, OBTAIN CLARIFICATION OF ANY QUESTIONS PRIOR TO PROCEEDING. 3.ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ALL NEW LIGHT FIXTURES AS INDICATED AND INSTALL NEW SWITCHES, DIMMERS, ETC. FOR CONTROL OF LIGHT FIXTURES AS SHOWN ON ARCHITECTURAL DRAWINGS. VERIFY AND COORDINATE SWITCHING CONTROL WITH ARCHITECT/CLIENT REPRESENTATIVES. 4.ALL JUNCTION OR OUTLET BOXES SHALL BE ACCESSIBLE. WHERE UNOBSTRUCTED ACCESS TO A BOX OR OUTLET IS NOT POSSIBLE, PROVIDE ACCESS PANEL. COORDINATE WITH THE ARCHITECT AND OBTAIN APPROVAL FROM ARCHITECT PRIOR TO INSTALLATION OF JUNCTION OR OUTLET BOXES. 5.WHERE MULTIPLE SWITCHES ARE GROUPED TOGETHER AT ONE LOCATION, THEY SHALL BE MOUNTED IN A SINGLE OUTLET BOX WITH A COMMON FACEPLATE. BUTTED OUTLET BOXES AND SWITCHPLATES ARE NOT PERMITTED. PROVIDE DIVIDER FOR SEPARATION OF SERVICE. 6.SUPPORT CEILING MOUNTED FIXTURES DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT FIXTURES FROM PIPING, EQUIPMENT, OR SOLELY FROM THE SUSPENDED CEILING. SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L GE N E R A L N O T E S S H E E T I N D E X AN D S Y M B O L S L I S T E0.01 1 1 SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI N EER ELECTRICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 1.01 GENERAL REQUIREMENTS PART 1 GENERAL A.ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE CALIFORNIA ELECTRICAL CODE, THE CALIFORNIA BUILDING CODE, CITY AMENDMENTS, BUILDING MANAGEMENT AND ALL AUTHORITIES HAVING JURISDICTION (AHJ). APPLICABLE NATIONAL, STATE AND LOCAL CODES, LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY PORTION OF THIS WORK SHALL BE INCORPORATED INTO AND MADE A PART OF THESE SPECIFICATIONS. B.IF A CONFLICT OCCURS IN THE SPECIFICATIONS AND/OR ON THE DRAWINGS, THE MORE STRINGENT SITUATION SHALL APPLY. C.ALL MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE OF THIS WORK. FINAL ACCEPTANCE SHALL BE DEFINED AS THE TIME AT WHICH THE ELECTRICAL WORK IS TAKEN OVER AND ACCEPTED BY THE OWNER. ENGAGE THE SERVICES OF VARIOUS MANUFACTURERS SUPPLYING THE EQUIPMENT FOR THE PROPER STARTUP, TRAINING AND OPERATION OF ALL SYSTEMS INSTALLED. INSTRUCT THE OWNERS PERSONNEL IN THE PROPER OPERATION AND SERVICING OF THE EQUIPMENT. D.ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE CAREFULLY THE EXISTING AREAS AFFECTED BY THIS WORK TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND WITH DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE AND LATER CLAIMS WILL NOT BE RECOGNIZED FOR EXTRA LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD SUCH AN EXAMINATION BEEN UNDERTAKEN. E.DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF ALL DEVICES INCLUDING DIMENSIONS AND ELEVATIONS. WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID CONFLICTS. F.ALTHOUGH NOT SPECIFICALLY MENTIONED HEREIN OR SHOWN ON THE DRAWINGS, ANY EQUIPMENT, MATERIALS, ACCESSORIES, OR LABOR REQUIRED FOR PROPER AND COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHALL BE FURNISHED AND INSTALLED AS PART OF THE ORIGINAL BID. G.THIS CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING THE LATEST COPY OF THE BUILDING RULES AND REGULATIONS. BASE BUILDING SYSTEM INTERRUPTIONS ARE TO BE PERFORMED OUTSIDE OF NORMAL BUSINESS HOURS. COORDINATE WITH BUILDING OWNER FOR ANY SERVICE INTERRUPTION OF EXISTING SYSTEMS AND GIVE NOTICE AS REQUIRED BY BUILDING RULES AND REGULATIONS. H.ANY DAMAGE TO EXISTING PARTITIONS, FLOORS, CEILINGS OR ANY PART OF THE BUILDING OR EQUIPMENT HOUSED THEREIN CAUSED BY THE WORK OF THE CONTRACTOR SHALL BE REPAIRED AT NO ADDITIONAL EXPENSE TO THE OWNER. I.ALL NEW MATERIALS REQUIRED SHALL CONFORM WITH THE STANDARDS OF THE UNDERWRITERS LABORATORIES, INC. (UL) IN EVERY CASE WHERE SUCH A STANDARD EXISTS. J.DURING THE PROJECT DURATION, THE BUILDING MANAGEMENT OFFICE AND ITS DESIGNATED REPRESENTATIVE SHALL BE ABLE TO INSPECT THE WORK IN PROGRESS. ANY WORK WHICH THE BUILDING MANAGEMENT DEEMS UNACCEPTABLE SHALL BE REMOVED AND REPLACED AT THE EXPENSE OF CONTRACTOR/TENANT. K.ALL EQUIPMENT INSTALLED OR CONNECTED INTO THE BUILDING RISERS, SYSTEMS AND INFRASTRUCTURE SHALL BE APPROVED IN ADVANCE BY THE BUILDING PRIOR TO INSTALLATION. 1.02 SCOPE OF WORK A.PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR COMPLETE, SAFE INSTALLATION OF ALL ELECTRICAL WORK. THE SCOPE OF WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: 1.INSTALLATION OF LIGHTING FIXTURES AND LAMPS INCLUDING EXIT AND EMERGENCY LIGHTING. 2.INSTALLATION OF RECEPTACLES, VOICE/DATA, OUTLETS, ETC. 3.INSTALLATION OF NEW RACEWAY AND CONDUCTORS FOR LIGHTING AND POWER. 4.INSTALLATION OF LIGHTING CONTROL SYSTEM COMPLETE WITH DEVICES, CONTROLLERS, SENSORS, WIRING AND CODE MANDATED ACCEPTANCE TESTING. 5.ADDITION OR MODIFICATION OF EXISTING ELECTRICAL DISTRIBUTION EQUIPMENT. 6.INSTALLATION OF MECHANICAL EQUIPMENT FEEDERS AND FINAL CONNECTIONS TO MECHANICAL EQUIPMENT. 7.GROUNDING OF ALL EQUIPMENT AS REQUIRED BY CODE AND AS SPECIFIED. 8.MODIFICATION OF EXISTING FIRE ALARM SYSTEM. 9.TEMPORARY LIGHTING AND POWER DURING CONSTRUCTION. 10.CUTTING, CHANNELING, CORING, AND CHASING REQUIRED TO ACCOMMODATE ELECTRIC INSTALLATION AND ROUGH PATCHING. 11.DEMOLITION AND REMOVAL OF ELECTRICAL EQUIPMENT AS REQUIRED INCLUDING ALL CONDUCTORS AND CONDUIT BACK TO THEIR SOURCE. 12.MAINTENANCE AND PROPER OPERATION OF EXISTING BASE BUILDING SYSTEMS WITHIN THE CONTRACT AREA IN ACCORDANCE WITH THE REQUIREMENTS OF BUILDING MANAGEMENT. 13.PROVISION OF SECURITY SYSTEM INFRASTRUCTURE AS DETAILED. 14.PROVISION OF AUDIO VISUAL SYSTEM INFRASTRUCTURE AS DETAILED. 15.RECEIPT AND INSTALLATION OF DEVICES, EQUIPMENT, SYSTEMS, SUPPLIED BY OTHERS AS DETAILED. 16.COORDINATION WITH OTHER TRADES. 1.03 SUBSTITUTIONS 1.04 SHOP DRAWINGS A.SHOP DRAWINGS SUBMISSION SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: 1.DISTRIBUTION EQUIPMENT (PANELS, SWITCHES, ETC.) 2.OVERCURRENT PROTECTIVE DEVICES (FUSES AND BREAKERS) 3.LIGHTING FIXTURES 4.WIRING DEVICES 5.FIRE ALARM EQUIPMENT, WIRING SCHEMATIC AND SEQUENCE OF OPERATION 6.FLOOR BOXES/ POKE THRU DEVICES 7.GROUNDING EQUIPMENT/DEVICES 8.CONDUIT, RACEWAYS, WIREWAYS 9.WIRING 10.LIGHTING CONTROL SYSTEMS AND DEVICES 11.TESTING AND COMMISSIONING SCHEDULE 12.TRANSFORMERS 13.UNINTERRUPTIBLE POWER SUPPLIES (UPS) 14.EMERGENCY LIGHTING INVERTERS 1.05 QUALITY ASSURANCE A.NO SUBSTITUTE MATERIAL OR MANUFACTURER OF EQUIPMENT SHALL BE PERMITTED WITHOUT A FORMAL WRITTEN SUBMITTAL TO THE ENGINEER WHICH INCLUDES ALL DIMENSIONAL, PERFORMANCE AND MATERIAL SPECIFICATIONS. B.ANY CHANGES IN LAYOUT, MECHANICAL CHARACTERISTICS, STRUCTURAL REQUIREMENTS, OR DESIGN DUE TO THE USE OF A SUBSTITUTION SHALL BE SUBMITTED TO THE ENGINEER AS PART OF THIS PROPOSAL. THE CONTRACTOR TAKES FULL RESPONSIBILITY FOR THE SUBSTITUTION AND ALL CHANGES RESULTING FROM SUBSTITUTION. C.ALL ITEMS SHALL BE SUBMITTED FOR REVIEW IN CONJUNCTION WITH THE SUBMITTAL OF THE ALTERNATE. ANY SUBSTITUTION MUST BE SUBMITTED WITH AN EXPLANATION WHY SUBSTITUTION IS BEING UTILIZED. IF THE SUBSTITUTED ITEM DEVIATES FROM THE SPECIFIED ITEM, THOSE DEVIATIONS ARE TO BE IDENTIFIED ON A LINE BY LINE BASIS. IF THE SUBSTITUTION IS BEING UTILIZED FOR FINANCIAL REASONS, THE ASSOCIATED CREDIT MUST BE SIMULTANEOUSLY SUBMITTED. D.ALL SUBSTITUTED EQUIPMENT SHALL CONFORM TO SPACE REQUIREMENTS AND PERFORMANCE REQUIREMENTS SHOWN ON CONTRACT DOCUMENTS. E.CONTRACTOR SHALL SUBMIT BID BASED ON SPECIFIED ITEMS AND SHALL SUPPLY, AS AN ALTERNATE PRICE, ANY SUBSTITUTIONS. A.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, AND MARKED FOR INTENDED USE. B.COMPLY WITH NFPA 70. A.COORDINATE CHASES, SLOTS, INSERTS, SLEEVES, AND OPENINGS WITH GENERAL CONSTRUCTION WORK AND ARRANGE IN BUILDING STRUCTURE DURING PROGRESS OF CONSTRUCTION TO FACILITATE THE ELECTRICAL INSTALLATIONS THAT FOLLOW. B.SET INSERTS AND SLEEVES IN POURED-IN-PLACE CONCRETE, MASONRY WORK, AND OTHER STRUCTURAL COMPONENTS AS THEY ARE CONSTRUCTED. C.SEQUENCE, COORDINATE, AND INTEGRATE INSTALLING ELECTRICAL MATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. COORDINATE INSTALLING LARGE EQUIPMENT REQUIRING POSITIONING BEFORE CLOSING IN THE BUILDING. D.COORDINATE LOCATION OF ACCESS PANELS AND DOORS FOR ELECTRICAL ITEMS THAT ARE CONCEALED BY FINISHED SURFACES. ACCESS DOORS AND PANELS ARE SPECIFIED BY THE ARCHITECT. E.WHERE ELECTRICAL IDENTIFICATION DEVICES ARE APPLIED TO FIELD-FINISHED SURFACES, COORDINATE INSTALLATION OF IDENTIFICATION DEVICES WITH COMPLETION OF FINISHED SURFACE. F.WHERE ELECTRICAL IDENTIFICATION MARKINGS AND DEVICES WILL BE CONCEALED BY ACOUSTICAL CEILINGS AND SIMILAR FINISHES, COORDINATE INSTALLATION OF THESE ITEMS BEFORE CEILING INSTALLATION. 1.07 AS-BUILT DRAWINGS A.CONTRACTOR SHALL MAINTAIN RECORD DRAWING PRINTS ON JOB SITE AND RECORD, AT TIME OF OCCURRENCE, DEVIATIONS FROM CONTRACT DOCUMENTS. B.AT THE COMPLETION OF WORK AND BEFORE FINAL ACCEPTANCE, PROVIDE AS-BUILT DRAWINGS OF THE INSTALLATION, IN AUTO-CAD. AN ELECTRONIC COPY (AUTOCAD FORMAT) OF ALL DRAWINGS WILL BE PROVIDED TO THE ELECTRICAL CONTRACTOR BY THE CONSULTANT AT NO COST. THE DRAWINGS WILL REFLECT THE BID AND/OR CONSTRUCTION SET OF DRAWINGS. C.INCORPORATE ALL CHANGES AND DEVIATIONS FROM BID DRAWINGS, UTILIZING NORMAL RECOGNIZED DRAFTING PROCEDURES THAT MATCH THE ORIGINAL DRAFTING METHODOLOGY. D.ALL MAIN BRANCH CONDUIT RUNS, JUNCTION BOX LOCATIONS, CONDUIT RUNS FOR ALL FLOOR OUTLETS, ETC., MUST BE REFLECTED ON THE DRAWINGS. E.REMOVE ALL ELECTRICAL ENGINEER'S DRAWING DIRECTIVE NOTES TO CONTRACTOR. F.CLEARLY INDICATE THE WORDS “AS-BUILT” IN THE TITLE BLOCK COLUMN OF THE DRAWINGS AS WELL AS THE ELECTRICAL CONTRACTOR'S NAME AND ADDRESS. G.WHEN FOUND ACCEPTABLE BY THE CONSULTANT, SUBMIT THREE (3) SETS OF PRINTS TOGETHER WITH THE CAD DISK FOR PRESENTATION TO THE LANDLORD AND TENANT. 1.06 COORDINATION 1.12 LOCATIONS OF OUTLETS A.REFER TO DESIGN CONSULTANT'S/ARCHITECT'S DRAWINGS FOR EXACT LOCATIONS OF ALL LIGHTING FIXTURES AND WIRING DEVICES. B.CHANGE LOCATION OF OUTLETS AT NO COST OR CREDIT, PROVIDING DISTANCE DOES NOT EXCEED (10'-0") AND INFORMATION IS GIVEN PRIOR TO INSTALLATION. C.ALL OUTLETS TO BE MARKED ON JOB SITE FOR APPROVAL BY DESIGN CONSULTANT/ARCHITECT PRIOR TO INSTALLATION. 1.13 PLYWOOD A.PLYWOOD BACKBOARDS SHALL BE 3/4” THICK, OF HIGHEST QUALITY FIRE RETARDANT FIR. B.PRIME AND PAINT BACKBOARDS WITH FIRE RETARDANT PAINT COLOR AS SELECTED BY THE DESIGN CONSULTANT/ARCHITECT. 1.15 NOISE AND VIBRATION A.ELECTRICAL EQUIPMENT IS TO OPERATE WITHOUT OBJECTIONABLE NOISE OR VIBRATION. IF, IN THE OPINION OF THE LANDLORD, ARCHITECT OR CONSULTANT, THE EQUIPMENT OPERATES WITH EXCESSIVE NOISE OR VIBRATION, THEN THE EQUIPMENT MUST BE REPLACED OR NOISE OR VIBRATION ELIMINATED. B.CONNECTIONS TO NOISE-PRODUCING AND VIBRATING EQUIPMENT MUST BE MADE WITH LIQUID-TIGHT FLEXIBLE CONDUIT AND ASSOCIATED CONNECTORS. THIS INCLUDES TRANSFORMERS, DIMMING EQUIPMENT RACKS, AND MOTORS. USE A MINIMUM OF 3 FT OF FLEXIBLE CABLE WITH SLACK AT EACH DEVICE. C.VIBRATION ISOLATORS ARE TO BE PROVIDED WHERE INDICATED OR REQUIRED. TRANSFORMERS TO BE ISOLATED FROM THE STRUCTURE, WITH SPRING AND RUBBER ISOLATORS WHEN WALL MOUNTED OR SUSPENDED AND 1/2" HIGH DENSITY NEOPRENE SANDWICH PADS (TYPE MWP) WHEN FLOOR MOUNTED. 1.16 TENANT'S EQUIPMENT A.WHERE SPECIFIED, INSTALL ALL EQUIPMENT PROVIDED BY THE TENANT. RECEIVE, STORE AND INSTALL EQUIPMENT AND ACCEPT FULL RESPONSIBILITY FOR ITS CORRECT OPERATION. PROVIDE CONDUIT, WIRE, BOXES, SWITCHES, OUTLETS, DEVICES, FLEX CONNECTIONS, ETC., AS REQUIRED. 1.17 INTERRUPTION OF SERVICES A.INTERRUPTION OF ELECTRICAL SERVICE TO ANY PART OF THE BUILDING SHALL OCCUR ONLY BY PRE-ARRANGEMENT WITH AND AT TIMES SUITABLE TO THE LANDLORD. B.INTERRUPTIONS SHALL ONLY OCCUR DURING PREMIUM TIME PERIODS; ALL ALLOWANCES FOR THIS SHALL BE INCLUDED IN THE PRICE SUBMITTED. 1.18 ENGINEERS FINAL INSPECTION A.FINAL INSPECTION IS IMPERATIVE. PRIOR TO CLOSING OF CEILINGS, THIS CONTRACTOR SHALL CONTACT AMA CONSULTING ENGINEERS. (310-846-4666) AND THE LANDLORD'S REPRESENTATIVE TO PERFORM A FINAL INSPECTION. WHEN CEILING TILES HAVE BEEN INSTALLED IT WILL BE NECESSARY FOR THE CONTRACTOR TO REMOVE PORTIONS FOR INSPECTION. 1.19 COMPLETION OF CONTRACT A.ALL EQUIPMENT MUST BE CLEANED AND TESTED BEFORE FINAL ACCEPTANCE BY THE CONSULTANT. B.DEFECTS AND DEFICIENCIES WHICH ORIGINATE OR BECOME EVIDENT DURING THE WARRANTY PERIOD MUST BE REPAIRED OR REPLACED, AT NO COST. C.IF, DURING THE WARRANTY PERIOD, TRANSFORMERS, BALLASTS, DRIVERS OR OTHER NOISE AND VIBRATION PRODUCING EQUIPMENT ARE CONSIDERED BY THE CONSULTANT TO EXCEED ACCEPTABLE STANDARDS, THEN THEY MUST BE REPLACED WITHOUT DELAY OR ADDITIONAL COST TO THE TENANT. ALL WORK RELATING TO THE REPLACEMENT OF DEFECTIVE ITEMS, MUST BE CARRIED OUT AFTER NORMAL WORKING HOURS AND AT A TIME WHICH IS ACCEPTABLE TO THE TENANT. 1.09 MATERIALS AND EQUIPMENT A.ALL MATERIALS AND EQUIPMENT SHALL BE NEW, CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY AND MANUFACTURED TO THE STANDARDS SPECIFIED. PART 2 PRODUCT/APPLICATION 2.02 WIRE AND CABLE A.CONDUCTORS, NO. 10 AWG AND SMALLER: SOLID COPPER. B.CONDUCTORS, LARGER THAN NO. 10 AWG: STRANDED COPPER. C.INSULATION: THERMOPLASTIC, RATED AT 75 DEG C MINIMUM. D.MULTICONDUCTOR CABLE: COMPLY WITH NEMA WC 70 FOR METAL-CLAD CABLE, TYPE MC WITH GROUND WIRE. E.FACTORY-FABRICATED CONNECTORS AND SPLICES OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE INDICATED. F.FEEDERS: COPPER. SOLID FOR NO. 10 AWG AND SMALLER; STRANDED FOR NO. 8 AWG AND LARGER. G.BRANCH CIRCUITS: COPPER. SOLID FOR NO. 10 AWG AND SMALLER; STRANDED FOR NO. 8 AWG AND LARGER. H.METAL-CLAD CABLE (TYPE MC) MAY BE USED FOR COMPLETELY CONCEALED BRANCH CIRCUITRY FROM J-BOX TO OUTLETS OR LIGHTS AND WHERE PERMITTED BY CODE AND ONLY IN TENANT SPACE. HOMERUNS FROM J-BOX TO PANELBOARD SHALL BE EMT. I.METAL-CLAD CABLE MAY NOT BE USED FOR UPS-SUPPORTED WIRING OR FOR EMERGENCY WIRING. 2.03 SUPPORTING DEVICES A.MATERIAL: COLD-FORMED STEEL, WITH CORROSION-RESISTANT COATING ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. B.METAL ITEMS FOR USE OUTDOORS OR IN DAMP LOCATIONS: HOT-DIP GALVANIZED STEEL. C.SLOTTED-STEEL CHANNEL SUPPORTS: FLANGE EDGES TURNED TOWARD WEB, AND 9/16-INCH DIAMETER SLOTTED HOLES AT A MAXIMUM OF 2 INCHES O.C., IN WEBS. CHANNEL THICKNESS: SELECTED TO SUIT STRUCTURAL LOADING. D.FITTINGS AND ACCESSORIES: PRODUCTS OF THE SAME MANUFACTURER AS CHANNEL SUPPORTS. E.RACEWAY AND CABLE SUPPORTS: MANUFACTURED CLEVIS HANGERS, RISER CLAMPS, STRAPS, THREADED C-CLAMPS WITH RETAINERS, CEILING TRAPEZE HANGERS, WALL BRACKETS, AND SPRING-STEEL CLAMPS OR CLICK-TYPE HANGERS. F.PIPE SLEEVES: ASTM A 53, TYPE E, GRADE A, SCHEDULE 40, GALVANIZED STEEL, PLAIN ENDS. G.CABLE SUPPORTS FOR VERTICAL CONDUIT: FACTORY-FABRICATED ASSEMBLY CONSISTING OF THREADED BODY AND INSULATING WEDGING PLUG FOR NON-ARMORED ELECTRICAL CABLES IN RISER CONDUITS. PLUGS HAVE NUMBER AND SIZE OF CONDUCTOR GRIPPING HOLES AS REQUIRED TO SUIT INDIVIDUAL RISERS. BODY CONSTRUCTED OF MALLEABLE-IRON CASTING WITH HOT-DIP GALVANIZED FINISH. H.EXPANSION ANCHORS: CARBON-STEEL WEDGE OR SLEEVE TYPE. I.TOGGLE BOLTS: ALL-STEEL SPRINGHEAD TYPE. J.POWDER-DRIVEN THREADED STUDS: HEAT-TREATED STEEL. K.EXCEPT FOR BRANCH CIRCUITRY INSTALL ALL CONDUIT IN HUNG CEILING SPACE ON ACCEPTABLE HANGERS AND INSERTS. CONDUIT OR MC CABLE FOR BRANCH CIRCUITRY SHALL BE SUPPORTED BY CLAMPS OR PIPE STRAPS SECURED TO THE CEILING SUPPORT SYSTEM, FROM STRUCTURAL MEMBERS OR FROM THE DECK. SUPPORT FROM CEILING TEES, CROSS TEES OR SUPPORT WIRES IS PROHIBITED. L.SPACING OF SUPPORTS SHALL BE PER THE NEC/CEC. M.INSERTS ARE TO BE OF A LEAD SHIELD TYPE. N.HANGERS MUST NOT BE WELDED TO STRUCTURAL STEEL MEMBERS AND BURNING OF HOLES IN STRUCTURAL STEEL IS PROHIBITED. O.SLEEVES ARE TO BE OF A TYPE SUITABLE FOR THE APPLICATION AND BE SEALED AND MADE WATERTIGHT. SLEEVES THROUGH CONCRETE SHALL BE SCHEDULE 40 STEEL PIPE, SIZED FOR FREE PASSAGE OF CONDUIT AND INSTALLED FLUSH WITH UNDERSIZE OF CONCRETE SLAB AND EXTEND 4" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. 2.04 PULLBOXES, JUNCTION BOXES AND OUTLET BOXES A.PULLBOXES, JUNCTION BOXES AND OUTLET BOXES SHALL BE MANUFACTURED FROM GALVANIZED INDUSTRY STANDARD GAUGE SHEET STEEL. B.PROVIDE PULL BOXES AND JUNCTION BOXES IN LONG STRAIGHT RUNS OF RACEWAY TO ASSURE THAT CABLES ARE NOT DAMAGED WHEN THEY ARE PULLED, TO FULFILL REQUIREMENTS AS TO THE NUMBER OF BENDS PERMITTED IN RACEWAY BETWEEN CABLE ACCESS POINTS, THE ACCESSIBILITY OF CABLE JOINTS AND SPLICES, AND THE APPLICATION OF CABLE SUPPORTS. C.PULLBOXES AND JUNCTION BOXES SHALL BE SIZED SO THAT THE MINIMUM BENDING RADIUS CRITERIA SPECIFIED FOR THE WIRES AND CABLE ARE MAINTAINED. D.SWITCH RECEPTACLE AND WALL OUTLET BOXES SHALL BE A NOMINAL 4" SQUARE, 1-1/2" OR 2-1/8" DEEP AS REQUIRED BY CODE WITH A RAISED COVER, UNLESS OTHERWISE INDICATED ON THE DRAWING. E.PROVIDE BLANK COVERPLATES FOR BOXES WITHOUT WIRING DEVICES. F.DO NOT INSTALL OUTLET BOXES BACK TO BACK IN PARTITIONS. STAGGER TO PREVENT SOUND TRANSFER. G.TWO OR MORE OUTLET BOXES THAT OCCUR AT THE SAME LOCATION SHALL BE GANGED TOGETHER IN THE SAME COVERPLATE UNLESS OTHERWISE NOTED. H.LIGHTING FIXTURE BOXES SHALL BE 4" OCTAGON TYPE, DEPTH AS REQUIRED WITH 3/8" FIXTURE STUD. FOR SUSPENDED CEILING WORK, PROVIDE A 4" OCTAGON BOX WITH REMOVABLE BACKPLATE WHERE REQUIRED. I.PULL/JUNCTION BOX BARRIERS SHALL BE PROVIDED WHERE REQUIRED BY CODE. J.INSTALL JUNCTION AND PULLBOXES IN INCONSPICUOUS LOCATIONS. K.A MINIMUM OF ONE PULLBOX SHALL BE INSTALLED FOR EVERY 100 FT OF CONDUITS. (NOTE: EACH 90 DEGREE BEND SHALL EQUATE TO 30' LENGTH OF CONDUIT). L.NO MORE THAN TWO (2) 90 DEGREE BENDS SHALL BE INSTALLED BETWEEN AND TWO ADJACENT PULLBOXES. M.ALL EQUIPMENT, DEVICE BOXES, JUNCTION BOXES, PULLBOXES AND OUTLET BOXES SHALL BE INSTALLED TO ALLOW ACCESS TO THE BOX. N.OUTLET BOXES SHALL BE PROVIDED FOR ALL LOW VOLTAGE DEVICES (I.E. TELEPHONE/DATA, SECURITY, FIRE ALARM, ETC.). COORDINATE BOX SIZE AND DEPTH WITH RESPECTIVE VENDOR. 2.05 WIRING DEVICES A.WIRING DEVICES SHALL BE SPECIFICATION GRADE, DECORATIVE STYLE, UNLESS OTHERWISE NOTED. B.DEVICES GANGED TOGETHER IN MULTI-GANG BOX SHALL BE MOUNTED UNDER A SINGLE COVERPLATE. C.DEVICE COLORS SHALL BE AS APPROVED BY ARCHITECT. DEVICE AND FACEPLATE SHALL MATCH. D.LINE VOLTAGE SWITCHES SHALL BE 120/277 VOLTS, RATED AT 20 AMPERES, QUIET OPERATION ROCKER TYPE, DECORA STYLE. E.RECEPTACLES 1.PROVIDE SPECIFICATION GRADE 20A. 120 VOLT, "U" GROUND RECEPTACLES, WITH MATCHING COVERPLATES. RECEPTACLES SHALL BE OF THE “DECORATOR STYLE”. 2.REFER TO NOTES AND DETAILS FOR SPECIALITY RECEPTACLE COLORS AND MARKINGS. 3.RECEPTACLES TO HAVE CIRCUIT NUMBER IDENTIFIED ON THE WALL PLATE AND FURTHER IDENTIFIED WITH THE EXACT LOCATION LISTED IN THE PANEL DIRECTORY. 4.RECEPTACLES CONTROLLED FOR COMPLIANCE WITH TITLE 24 SHALL BE LABELED WITH NEMA APPROVED MARKINGS. 2.06 DISCONNECT SWITCHES A.INDOOR DISCONNECT SWITCHES SHALL BE "QUICK-MAKE, QUICK-BREAK," HEAVY DUTY TYPE IN NEMA 1 ENCLOSURES. PROVIDE ALL FUSES WHERE NOTED. B.OUTDOOR DISCONNECT SWITCHES SHALL BE SIMILAR TO INDOOR, EXCEPT LISTED FOR OUTDOOR APPLICATIONS (NEMA 3R OR 4, AS REQUIRED). C.FUSED DISCONNECT SWITCHES SHALL BE PROVIDED WITH FUSE CLIPS TO ACCEPT SPECIFIED FUSES. 2.07 FUSES A.FUSES SHALL BE CURRENT LIMITING TYPE WITH A UL LISTED INTERRUPTING CAPACITY OF 200,000 RMS. B.FUSES RATED 601 AMPS AND LARGER SHALL BE CURRENT-LIMITING, TIME-DELAY, UL CLASS L FUSES. C.FUSES RATED 600 AMPS AND BELOW SHALL BE CUREENT-LIMITING, DUAL-ELEMENT, TTIME-DELAY UL CLASS RK-1 FOR NON-MOTOR CIRCUITS AND UL CLASS RK-5 FOR MOTOR CIRCUITS. D.ALL FUSES SHALL BE OF THE SAME MANUFACTURER. 2.09 PANELBOARDS A.PANELBOARD BOXES SHALL BE MADE OF SHEET STEEL "BENT-UP" OR RIVETED OR BOLTED TOGETHER WITH EXTERIOR ANGLE IRON FRAME. BOX SHALL BE OF SUFFICIENT SIZE TO ALLOW A GUTTER AT LEAST 6" IN WIDTH ENTIRELY SURROUNDING EACH SECTION OF BOARD. PANELBOARDS SHALL BE SURFACE OR FLUSH TYPE AS NOTED ON THE DRAWINGS. PANEL BOX AND COVER SHALL BE GIVEN TWO COATS OF GRAY ENAMEL PAINT. B.PROVIDE CODE GAUGE STEEL DOORS FOR ALL PANELBOARD BOXES. FRONT COVER SHALL BE A "DOOR WITHIN A DOOR" TYPE. THE OUTER DOOR (TRIM) SHALL ALLOW ACCESS TO ENTIRE PANELBOARD BOX INCLUDING GUTTER SPACES. OUTER DOOR (TRIM) SHALL BE ATTACHED DIRECTLY TO BOX BY A FULL-LENGTH PIANO-HINGE. THE INNER DOOR SHALL ALLOW ACCESS TO CIRCUIT BREAKERS ONLY. PROVIDE LOCK AND SET OF KEYS FOR INNER DOOR PER PANELBOARD. C.PROVIDE A COPPER EQUIPMENT GROUND BAR IN EACH PANEL, AND A COPPER ISOLATED GROUND BAR AS NOTED. D.PANELS SHALL BE PROVIDED WITH NEUTRAL BARS SIZED AT 200% OF THE PHASE BUS BARS. E.ALL MAIN BREAKERS SHALL BE SEPARATELY MOUNTED ON TOP OR BOTTOM OF PANEL TO SUIT CABLE ENTRY. F.ALL FLOOR MOUNTED DISTRIBUTION EQUIPMENT, INCLUDING PANELBOARDS AND/OR DISTRIBUTION PANELBOARDS SHALL BE INSTALLED ON A 4” HIGH CONCRETE BASE TO EXTEND 2” ON ALL SIDES WITH CHAMFERED CORNERS. ALL CONCRETE WORK TO BE INCLUDED, IN THIS DIVISION. G.A TYPEWRITTEN LIST OF CIRCUITS SHOWING CLEARLY THE LOADS SUPPLIED BY EACH CIRCUIT SHALL BE INSTALLED ON THE INSIDE OF EACH PANEL BOARD DOOR. THIS LIST SHALL BE MOUNTED IN A STEEL FRAME UNDER A PLASTIC WINDOW. EACH PANEL SHALL BE EXTERNALLY TAGGED WITH PERMANENT LAMACOID PLATE INDICATING PANEL DESIGNATION AND VOLTAGE. PANEL DIRECTORY SHALL BE SUBMITTED TO ENGINEER FOR REVIEW AND APPROVAL PRIOR TO INSTALLING IN PANELBOARD. LOAD DESCRIPTION SHALL INCLUDE COLUMN GRID LINES, ROOM NUMBERS, OR OTHER INFORMATION TO CLEARLY DISTINGUISH LOAD LOCATION. H.PHASE LEGS OF ALL PANELS SHALL BE BALANCED AT SUPPLY POINT TO WITHIN 10% AFTER ALL CIRCUITS ARE WIRED AND LOADS CONNECTED. 2.12 LIGHT FIXTURES A.LIGHT FIXTURE MOUNTING HARDWARE SHALL MATCH AND BE COORDINATED WITH THE NEW CEILING SYSTEM TYPE. ALL FIXTURES SHALL BE EQUIPPED WITH "EARTHQUAKE" CLIPS. B.LIGHT FIXTURES SHALL BE INSTALLED WITH SEISMIC BRACING WHERE REQUIRED. C.FIXTURES SHALL BE FREE OF LIGHT LEAKS BELOW CEILING. D.REFER TO ARCHITECTURAL DRAWINGS FOR ALL LIGHTING FIXTURE SPECIFICATIONS. E.FIXTURES SHALL BE COMPLETE WITH NEW LAMPS, BALLASTS, DRIVERS, ACCESSORIES AND MOUNTING APPURTENANCES. F.ALL LIGHT FIXTURES SHALL BE U.L. APPROVED. G.CONTRACTOR SHALL AIM AND ADJUST ALL LIGHT FIXTURES IN PRESENCE OF LIGHTING CONSULTANT. 2.13 GROUNDING A.PROVIDE SUPPLEMENTARY GROUND BONDING WHERE METALLIC CONDUITS TERMINATE AT METAL CLAD EQUIPMENT (OR AT THE METAL PULL BOX OF EQUIPMENT) FOR WHICH A GROUND BUS IS SPECIFIED WITH A BUSHING OF THE GROUNDING TYPE CONNECTED INDIVIDUALLY TO GROUND BUS. B.GROUND ALL EQUIPMENT IN ACCORDANCE WITH LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. PROVIDE SEPARATE GREEN INSULATED GROUND CONDUCTOR IN EVERY CONDUIT TO ALL DEVICES, LIGHTING FIXTURES AND FEEDERS (PANELBOARDS, DISCONNECT SWITCHES, ETC.). C.ALL GROUND WIRES SHALL BE SUITABLY PROTECTED FROM MECHANICAL INJURY. D.SPECIALTY GROUNDING AS DETAILED ON THE DESIGN DRAWINGS OR REQUESTED AS ELECTRICAL CONTRACTOR SCOPE BY OTHER CONSULTANTS DOCUMENTS. 2.14 MOTORS AND APPARATUS FURNISHED BY OTHERS A.INSTALL ALL WIRING IN CONDUITS. CONNECT CONDUIT TO MOTOR CONDUIT TERMINAL BOXES WITH 18" TO 24" OF FLEXIBLE CONDUIT FROM END OF CONDUIT TO MOTOR TERMINAL BOX. B.PROVIDE CONNECTIONS TO ALL "EXISTING TO BE RELOCATED" AS WELL AS NEW MOTORS, CONTROLLERS, DISCONNECTS, ACTUATING AND CONTROL DEVICES. CONDUCTORS TO MOTORS TO BE THE SAME AS TO CONTROLLERS EXCEPT AS NOTED. C.ASCERTAIN EXACT LOCATIONS OF CONTROLLERS AND CONTROL SERVICES PRIOR TO INSTALLATION AND PULLING WIRING. D.COORDINATE WITH ALL OTHER TRADES AND PROVIDE ALL WIRING, CONDUIT, JUNCTION BOXES, DISCONNECTS, CONNECTIONS AND TERMINATIONS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER WIRING AND NECESSARY ELECTRICAL ADJUSTMENTS AS REQUIRED BY THE EQUIPMENT SPECIFICATION. E.CONFIRM ELECTRICAL REQUIREMENTS AND EXACT LOCATIONS OF ALL MECHANICAL EQUIPMENT PRIOR TO INSTALLATION. 2.15 LIGHTING CONTROL SYSTEMS A.MANUFACTURER OF CONTROL SYSTEM MUST VERIFY TYPE, QUANTITIES, PLACEMENT OF DEVICES TO MEET DESIGN INTENT AND TITLE 24 CODE COMPLIANCE, AND PROVIDE SHOP DRAWINGS FOR APPROVAL. THIRD PARTY TAKE-OFFS OR LAYOUTS WILL NOT BE ACCEPTED. B.OCCUPANCY AND DAYLIGHT SENSORS QUANTITY AND LOCATIONS SHOWN ON DRAWINGS ARE FOR INTENT ONLY. PROVIDE APPROPRIATE QUANTITY AND LOCATION OF DEVICES FOR ADEQUATE COVERAGE. C.CONTRACTOR SHALL COORDINATE APPROPRIATE INTERFACE DEVICES REQUIRED TO MATCH THE LIGHT FIXTURE LAMP AND CONTROL TECHNOLOGY PER LIGHT MANUFACTURER'S RECOMMENDATIONS. D.LIGHTING CONTROL SWITCHES SHALL CONTAIN THE EXACT QUANTITY OF PUSH BUTTONS TO CONTROL THE QUANTITY OF ZONES IN THE ROOM OR AREA BEING CONTROLLED. CONTROL SWITCHES WITH BUTTONS THAT DO NOT PERFORM ANY ACTION WILL NOT BE ACCEPTED. E.LOCATE COMBINATION OCCUPANCY SENSOR AND SWITCH DEVICES SO OCCUPANCY SENSOR CAN OPERATE CORRECTLY. IF THE ROUGHED-IN SWITCH LOCATION DOES NOT PROVIDE FOR PROPER OPERATION, THEN A STANDALONE OCCUPANCY SENSORS SHALL BE PROVIDED INSTEAD. F.ALL OCCUPANCY SENSORS ON THIS PROJECT SHALL BE SET WITH THE SIMILAR DELAY SET TIME. G.ALL WIRING FOR LIGHTING CONTROL DEVICES SHALL BE INSTALLED IN CONDUIT. H.LIGHTING CONTROL DEVICES SHALL BE PROGRAMMED TO MATCH SEQUENCE OF OPERATIONS DESCRIBED ON THE DRAWINGS PRIOR TO ELECTRICAL ENGINEER'S VISIT TO PERFORM FINAL PUNCH. I.COLOR OF ALL LIGHTING CONTROL DEVICES SHALL BE APPROVED BY ARCHITECT. 2.16 EMERGENCY LIGHTING INVERTERS - NOT USED. 2.17 ELECTRICAL IDENTIFICATION A.USE A SINGLE TYPE OF IDENTIFICATION PRODUCT FOR EACH APPLICATION. USE COLORS PRESCRIBED BY ANSI A13.1, NFPA 70, AND THESE SPECIFICATIONS. B.RACEWAY AND CABLE LABELS: COMPLY WITH ANSI A13.1, TABLE 3, FOR MINIMUM SIZE OF LETTERS FOR LEGEND AND MINIMUM LENGTH OF COLOR FIELD FOR EACH RACEWAY AND CABLE SIZE. C.COLORED ADHESIVE MARKING TAPE FOR RACEWAYS, WIRES, AND CABLES: SELF-ADHESIVE VINYL TAPE, NOT LESS THAN 1 INCH WIDE BY 3 MILS THICK. D.TAPE MARKERS FOR WIRE: VINYL OR VINYL-CLOTH, SELF-ADHESIVE, WRAPAROUND TYPE WITH PREPRINTED NUMBERS AND LETTERS. E.COLOR-CODING CABLE TIES: TYPE 6/6 NYLON, SELF-LOCKING TYPE. COLORS TO SUIT CODING SCHEME. F.ENGRAVED-PLASTIC LABELS, SIGNS, AND INSTRUCTION PLATES: ENGRAVING STOCK, MELAMINE PLASTIC LAMINATE PUNCHED OR DRILLED FOR MECHANICAL FASTENERS 1/16-INCH MINIMUM THICKNESS FOR SIGNS UP TO 20 SQ. IN. AND 1/8-INCH MINIMUM THICKNESS FOR LARGER SIZES. ENGRAVED LEGEND IN BLACK LETTERS ON WHITE BACKGROUND. G.INTERIOR WARNING AND CAUTION SIGNS: COMPLY WITH 29 CFR, CHAPTER XVII, PART 1910.145. PREPRINTED, ALUMINUM, BAKED-ENAMEL-FINISH SIGNS, PUNCHED OR DRILLED FOR MECHANICAL FASTENERS, WITH COLORS, LEGEND, AND SIZE APPROPRIATE TO THE APPLICATION. H.EXTERIOR WARNING AND CAUTION SIGNS: COMPLY WITH 29 CFR, CHAPTER XVII, PART 1910.145. WEATHER-RESISTANT, NON-FADING, PREPRINTED, CELLULOSE-ACETATE BUTYRATE SIGNS WITH 0.0396-INCH (1-MM), GALVANIZED-STEEL BACKING, WITH COLORS, LEGEND, AND SIZE APPROPRIATE TO THE APPLICATION. 1/4-INCH GROMMETS IN CORNERS FOR MOUNTING. I.FASTENERS FOR NAMEPLATES AND SIGNS: SELF-TAPPING, STAINLESS-STEEL SCREWS OR NO. 10/32 STAINLESS-STEEL MACHINE SCREWS WITH NUTS AND FLAT AND LOCK WASHERS. 2.18 ACCEPTABLE MANUFACTURERS: A.RECEPTACLES: HUBBELL, LEVITON, PASS & SEYMOUR. B.LIGHT SWITCHES: HUBBELL, LEVITON, PASS & SEYMOUR. C.LINE VOLTAGE DIMMER SWITCHES: LUTRON, LEVITON. D.RACEWAYS: NATIONAL WIRE PRODUCTS, TRIANGLE OR REPUBLIC. E.WIRE/CABLE: SOUTHWIRE, GENERAL CABLE, CERRO. F.METAL CLAD CABLE: AFC, SOUTHWIRE. G.FITTINGS, COUPLINGS, BUSHINGS, CONNECTORS: OZ GEDNEY, BURNDY, NEPCO, THOMAS AND BETTS. H.DISCONNECT SWITCHES: EATON, GE, SQUARE "D" OR SIEMENS. I.FUSES: BUSSMAN, MERSEN. J.CIRCUIT BREAKERS: EATON, GE, SQUARE "D" OR SIEMENS. K.PANELBOARDS: EATON, GE, SQUARE "D" OR SIEMENS. MATCH BUILDING STANDARD. L.TRANSFORMERS: EATON, GE, SQUARE D, OR SIEMENS. MATCH BUILDING STANDARD. M.EXIT SIGNS: LITHONIA LIGHTING OR MATCH BUILDING STANDARD. N.LIGHTING CONTROL: nLIGHT OR MATCH BUILDING STANDARD. O.FLOOR BOXES POKE-THRU'S: HUBBELL, WIREMOLD. P.WIREWAYS: HUBBELL, WIREMOLD. Q.INVERTERS: LITHONIA LIGHTING, MYERS POWER PRODUCTS. R.TENANT SUBMETERING: EMON DMON CORPORATION OR MATCH BUILDING STANDARDS. PART 3 EXECUTION 3.01 GENERAL A.PERFORM THE WORK AT SUCH TIME AND IN SUCH MANNER AS TO MINIMIZE INTERFERENCE WITH BUILDING'S NORMAL OPERATION. NOTIFY BUILDING MANAGEMENT REPRESENTATIVES IN ADVANCE EACH TIME A SERVICE OUTAGE OR INTERRUPTION WILL BE REQUIRED FOR THE PERFORMANCE OF SOME PHASE OF THE WORK. SCHEDULE SUCH SERVICE OUTAGE OR INTERRUPTION, ONLY AFTER HAVING RECEIVED APPROVAL OF DATE, HOUR, AND TIME INTERVAL REQUIRED THEREOF. SCHEDULE OF WORK AS DIRECTED SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE. B.OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE RESISTANCE RATED WALLS, PARTITIONS, FLOORS, OR CEILINGS SHALL BE FIRE STOPPED USING APPROVED METHODS. SEALANT SHALL BE RATED FOR 3 HOURS. TELECOMMUNICATION CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING FIRE STOPPING IN 'IT' CONDUITS/SLEEVES/PENETRATIONS AFTER 'IT' WIRES ARE PULLED. C.PROVIDE 277/480 VOLT DANGER LABELING AT ALL EQUIPMENT AND JUNCTION/PULL BOXES PER CODE. D.MAINTAIN GROUND CONTINUITY THROUGHOUT ALL SYSTEMS. E.MAINTAIN CONTINUITY AND PROTECT ALL EXISTING CIRCUITS TO REMAIN SERVING EQUIPMENT WITHIN BASE BUILDING CORE AREAS OR OTHER TENANT AREAS AFFECTED BY THE ALTERATION WORK. CONTRACTOR SHALL BE RESPONSIBLE TO TRACE ALL EXISTING CIRCUITS TO REMAIN ORIGINATING FROM PANELBOARDS, AND SUBMIT FINDINGS TO ENGINEER FOR CLARIFICATION PRIOR TO THE START OF ANY PANELBOARD WORK. WHENEVER IT IS REQUIRED THAT AN EXISTING CIRCUIT BE MODIFIED, REVISED, DISCONNECTED OR REMOVED IT SHALL BE UNDERSTOOD THAT THE CIRCUIT SHALL BE RECONNECTED AND SERVICE RE-ESTABLISHED IN THE REMAINING PORTION OF THE CIRCUIT AFFECTED BY THE ALTERNATION. F.PRIOR TO ANY CHASING, CHOPPING, OR CORE DRILLING BEING PERFORMED, THE CONTRACTOR SHALL FIELD INVESTIGATE CONDITIONS AND COORDINATE WITH ALL APPROPRIATE TRADES TO ENSURE THAT WORK WILL BE IN HARMONY WITH OTHER WORK AND NOT AFFECTED ANY EXISTING BUILDING SYSTEMS. X-RAY SLABS IF REQUIRED. THIS WORK MUST BE APPROVED BY BUILDING MANAGEMENT PRIOR TO PROCEEDING. ALL CORING/CHASING WILL BE DONE ON OVERTIME. 3.02 ELECTRICAL EQUIPMENT INSTALLATION A.HEADROOM MAINTENANCE: IF MOUNTING HEIGHTS OR OTHER LOCATION CRITERIA ARE NOT INDICATED, ARRANGE AND INSTALL COMPONENTS AND EQUIPMENT TO PROVIDE THE MAXIMUM POSSIBLE HEADROOM. B.MATERIALS AND COMPONENTS: INSTALL LEVEL, PLUMB, AND PARALLEL AND PERPENDICULAR TO OTHER BUILDING SYSTEMS AND COMPONENTS, UNLESS OTHERWISE INDICATED. C.EQUIPMENT: INSTALL TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR REPLACEMENT OF COMPONENTS. CONNECT FOR EASE OF DISCONNECTING, WITH MINIMUM INTERFERENCE WITH OTHER INSTALLATIONS. D.RIGHT OF WAY: GIVE TO RACEWAYS AND PIPING SYSTEMS INSTALLED AT A REQUIRED SLOPE. 3.03 RACEWAY APPLICATION A.USE THE FOLLOWING RACEWAYS FOR OUTDOOR INSTALLATIONS: 1.EXPOSED: RMC. 2.CONCEALED: RMC. 3.CONNECTION TO VIBRATING EQUIPMENT: LFMC. 4.BOXES AND ENCLOSURES: NEMA 250, TYPE 3R OR TYPE 4. B.USE THE FOLLOWING RACEWAYS FOR INDOOR INSTALLATIONS: 1.EXPOSED: EMT. 2.CONCEALED: EMT OR MC CABLE IF INSTALLED PER SPECIFICATIONS. 3.CONNECTION TO VIBRATING EQUIPMENT: FMC; EXCEPT IN WET OR DAMP LOCATIONS, USE LFMC. 4.DAMP OR WET LOCATIONS: RMC. 5.OUTSIDE TENANT SPACE: EMT C.BOXES AND ENCLOSURES: NEMA 250, TYPE 1, UNLESS OTHERWISE INDICATED. 3.04 RACEWAY AND CABLE INSTALLATION A.CONCEAL RACEWAYS AND CABLES, UNLESS OTHERWISE INDICATED, WITHIN FINISHED WALLS, CEILINGS, AND FLOORS. B.INSTALL RACEWAYS AND CABLES AT LEAST 6 INCHES AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES. LOCATE HORIZONTAL RACEWAY RUNS ABOVE WATER AND STEAM PIPING. C.USE TEMPORARY RACEWAY CAPS TO PREVENT FOREIGN MATTER FROM ENTERING. D.MAKE CONDUIT BENDS AND OFFSETS SO ID IS NOT REDUCED. KEEP LEGS OF BENDS IN THE SAME PLANE AND STRAIGHT LEGS OF OFFSETS PARALLEL, UNLESS OTHERWISE INDICATED. E.USE RACEWAY AND CABLE FITTINGS COMPATIBLE WITH RACEWAYS AND CABLES AND SUITABLE FOR USE AND LOCATION. F.INSTALL RACEWAYS EMBEDDED IN SLABS IN MIDDLE THIRD OF SLAB THICKNESS WHERE PRACTICAL, AND LEAVE AT LEAST 1-INCH CONCRETE COVER. OBTAIN STRUCTURAL ENGINEER'S APPROVAL PRIOR TO INSTALLATION. G.SECURE RACEWAYS TO REINFORCING RODS TO PREVENT SAGGING OR SHIFTING DURING CONCRETE PLACEMENT. H.SPACE RACEWAYS LATERALLY TO PREVENT VOIDS IN CONCRETE. I.INSTALL CONDUIT LARGER THAN 1-INCH TRADE SIZE PARALLEL TO OR AT RIGHT ANGLES TO MAIN REINFORCEMENT. WHERE CONDUIT IS AT RIGHT ANGLES TO REINFORCEMENT, PLACE CONDUIT CLOSE TO SLAB SUPPORT. J.TRANSITION FROM NONMETALLIC TUBING TO SCHEDULE 80 NONMETALLIC CONDUIT, RIGID STEEL CONDUIT, OR IMC BEFORE RISING ABOVE FLOOR. K.MAKE BENDS IN EXPOSED PARALLEL OR BANKED RUNS FROM SAME CENTERLINE TO MAKE BENDS PARALLEL. USE FACTORY ELBOWS ONLY WHERE ELBOWS CAN BE INSTALLED PARALLEL; OTHERWISE, PROVIDE FIELD BENDS FOR EXPOSED PARALLEL RACEWAYS. L.INSTALL PULL WIRES IN EMPTY RACEWAYS. USE NO. 14 AWG ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN 200-LB TENSILE STRENGTH. LEAVE AT LEAST 12 INCHES OF SLACK AT EACH END OF THE PULL WIRE. M.INSTALL TELEPHONE AND SIGNAL SYSTEM RACEWAYS, 2-INCH TRADE SIZE AND SMALLER, IN MAXIMUM LENGTHS OF 100 FEET AND WITH A MAXIMUM OF TWO 90-DEGREE BENDS OR EQUIVALENT. SEPARATE LENGTHS WITH PULL OR JUNCTION BOXES WHERE NECESSARY TO COMPLY WITH THESE REQUIREMENTS, IN ADDITION TO REQUIREMENTS ABOVE. N.CONNECT MOTORS AND EQUIPMENT SUBJECT TO VIBRATION, NOISE TRANSMISSION, OR MOVEMENT WITH A MAXIMUM OF 72-INCH FLEXIBLE CONDUIT. INSTALL LFMC IN WET OR DAMP LOCATIONS. INSTALL SEPARATE GROUND CONDUCTOR ACROSS FLEXIBLE CONNECTIONS. O.SET FLOOR BOXES LEVEL AND TRIM AFTER INSTALLATION TO FIT FLUSH TO FINISHED FLOOR SURFACE. 3.05 WIRING A.FEEDERS: TYPE THHN/THWN INSULATED CONDUCTORS IN RACEWAY. B.UNDERGROUND FEEDERS AND BRANCH CIRCUITS: TYPE THWN OR SINGLE-WIRE, TYPE UF INSULATED CONDUCTORS IN RACEWAY. C.BRANCH CIRCUITS: TYPE THWN OR THHN/THWN INSULATED CONDUCTORS IN RACEWAY WHERE EXPOSED. METAL-CLAD CABLE SHALL BE PERMITTED WHERE PERMITTED BY AUTHORITIES HAVING JURISDICTION AND WHEN APPROVED BY LANDLORD RULES AND REGULATIONS. METAL-CLAD CABLE SHALL NOT BE INSTALLED WITHIN ELECTRIC CLOSETS OR DIRECTLY INTO PANELBOARDS. D.REMOTE-CONTROL SIGNALING AND POWER-LIMITED CIRCUITS: TYPE THHN/THWN INSULATED CONDUCTORS IN RACEWAY FOR CLASSES 1, 2, AND 3, UNLESS OTHERWISE INDICATED. E.MULTI-WIRE BRANCH CIRCUITS SHALL BE PROVIDED WITH A MEANS TO DISCONNECT SIMULTANEOUSLY ALL UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE BRANCH CIRCUIT ORIGINATES. F.WIRE CONNECTORS AND SPLICES: UNITS OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS SUITABLE FOR SERVICE INDICATED. G.METAL CLAD (TYPE MC) FOR CONCEALED BRANCH CIRCUITRY IN TENANT SPACE ONLY MAYBE USED WHEN APPROVED BY BUILDING MANAGEMENT AND WHERE PERMITTED BY CODE. H.EMT SHALL BE USED OUTSIDE TENANT SPACE AND IN BUILDING CLOSETS. I.METAL CLAD (TYPE MC) SHALL NOT BE INSTALLED INTO PANELBOARDS. J.ALL CONDUCTORS SHALL BE SOFT 98% MINIMUM CONDUCTIVITY PROPERLY REFINED COPPER, TYPE THHN/THWN INSULATED RATED AT 600V, UNLESS OTHERWISE NOTED. K.THE MINIMUM WIRE SIZE FOR BRANCH CIRCUITS SHALL BE NO. 12 AWG EXCEPT 120 VOLT CIRCUITS OVER 100' IN LENGTH SHALL BE NO. 10 AWG. L.ALL FEEDER CONDUCTORS SHALL BE SIZED FOR MAXIMUM 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL ALSO BE SIZED FOR 2.5% VOLTAGE DROP. M.TAG ALL FEEDERS IN ALL PULL BOXES, GUTTER SPACES, AND WIREWAYS THROUGH WHICH THEY PASS. N.TERMINATE STRANDED CONDUCTORS NO. 8 AWG AND LARGER, AT SWITCHBOARDS, TRANSFORMERS, UPS SYSTEMS WITH COMPRESSION TYPE CONNECTORS. TERMINATE WITH MECHANICAL LUGS AT PANELBOARDS. O.JOIN OR TAP STRANDED CONDUCTORS (NO. 6 AWG AND LARGER) WITH PRESSURE INDENT TYPE CONNECTORS BURNDY, NEPCO, OR O.Z./GEDNEY WITH COMPOSITION INSULATING COVERS. P.SPLICES IN BRANCH WIRING (NO. 8 AWG AND SMALLER) SHALL BE TWISTED AND MADE MECHANICALLY TIGHT; THEN SECURED WITH PIGTAIL CONNECTORS, CRIMP TYPE CONNECTORS SHALL NOT BE USED. UTILIZE UL LISTED, "SILICON FILLED" PIGTAIL CONNECTORS WHERE LOCATED IN WET ENVIRONMENTS OR OUTDOORS. Q.SUPPORT CONDUCTORS IN VERTICAL RACEWAYS IN ACCORDANCE WITH THE NEC/NYCEC BASED ON CONDUCTOR SIZE AND VERTICAL DISTANCE. R.WALL MOUNTED DEVICES SHALL BE FED VERTICALLY. HORIZONTAL RUNS THROUGH PARTITIONS SHALL NOT BE PERMITTED, EXCEPT IN LOW HEIGHT PARTITIONS OR WHERE NOTED ON DRAWINGS. S.INSTALL WIRING AT OUTLETS WITH AT LEAST 12 INCHES OF SLACK CONDUCTOR AT EACH OUTLET. T.CONNECT OUTLET AND COMPONENT CONNECTIONS TO WIRING SYSTEMS AND TO GROUND. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A. 3.06 SUPPORTS A.DAMP LOCATIONS AND OUTDOORS: HOT-DIP GALVANIZED MATERIALS OR NONMETALLIC, U-CHANNEL SYSTEM COMPONENTS. B.DRY LOCATIONS: STEEL MATERIALS. C.SUPPORT CLAMPS FOR PVC RACEWAYS: CLICK-TYPE CLAMP SYSTEM. D.SELECTION OF SUPPORTS: COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. E.STRENGTH OF SUPPORTS: ADEQUATE TO CARRY PRESENT AND FUTURE LOADS, TIMES A SAFETY FACTOR OF AT LEAST FOUR; MINIMUM OF 200-LB DESIGN LOAD. F.INSTALL SUPPORT DEVICES TO SECURELY AND PERMANENTLY FASTEN AND SUPPORT ELECTRICAL COMPONENTS. G.INSTALL INDIVIDUAL AND MULTIPLE RACEWAY HANGERS AND RISER CLAMPS TO SUPPORT RACEWAYS. PROVIDE U-BOLTS, CLAMPS, ATTACHMENTS, AND OTHER HARDWARE NECESSARY FOR HANGER ASSEMBLIES AND FOR SECURING HANGER RODS AND CONDUITS. H.SUPPORT PARALLEL RUNS OF HORIZONTAL RACEWAYS TOGETHER ON TRAPEZE- OR BRACKET-TYPE HANGERS. I.SIZE SUPPORTS FOR MULTIPLE RACEWAY INSTALLATIONS SO CAPACITY CAN BE INCREASED BY A 25 PERCENT MINIMUM IN THE FUTURE. J.SUPPORT INDIVIDUAL HORIZONTAL RACEWAYS WITH SEPARATE, MALLEABLE-IRON PIPE HANGERS OR CLAMPS. K.INSTALL 1/4-INCH DIAMETER OR LARGER THREADED STEEL HANGER RODS, UNLESS OTHERWISE INDICATED. L.SPRING-STEEL FASTENERS SPECIFICALLY DESIGNED FOR SUPPORTING SINGLE CONDUITS OR TUBING MAY BE USED INSTEAD OF MALLEABLE-IRON HANGERS FOR 1-1/2-INCH (AND SMALLER RACEWAYS SERVING LIGHTING AND RECEPTACLE BRANCH CIRCUITS ABOVE SUSPENDED CEILINGS AND FOR FASTENING RACEWAYS TO SLOTTED CHANNEL AND ANGLE SUPPORTS. M.ARRANGE SUPPORTS IN VERTICAL RUNS SO THE WEIGHT OF RACEWAYS AND ENCLOSED CONDUCTORS IS CARRIED ENTIRELY BY RACEWAY SUPPORTS, WITH NO WEIGHT LOAD ON RACEWAY TERMINALS. N.SEPARATELY SUPPORT CAST BOXES THAT ARE THREADED TO RACEWAYS AND USED FOR FIXTURE SUPPORT. SUPPORT SHEET-METAL BOXES DIRECTLY FROM THE BUILDING STRUCTURE OR BY BAR HANGERS. IF BAR HANGERS ARE USED, ATTACH BAR TO RACEWAYS ON OPPOSITE SIDES OF THE BOX AND SUPPORT THE RACEWAY WITH AN APPROVED FASTENER NOT MORE THAN 24 INCHES FROM THE BOX. O.INSTALL METAL CHANNEL RACKS FOR MOUNTING CABINETS, PANELBOARDS, DISCONNECT SWITCHES, CONTROL ENCLOSURES, PULL AND JUNCTION BOXES, TRANSFORMERS, AND OTHER DEVICES UNLESS COMPONENTS ARE MOUNTED DIRECTLY TO STRUCTURAL ELEMENTS OF ADEQUATE STRENGTH. P.INSTALL SLEEVES FOR CABLE AND RACEWAY PENETRATIONS OF CONCRETE SLABS AND WALLS UNLESS CORE-DRILLED HOLES ARE USED. INSTALL SLEEVES FOR CABLE AND RACEWAY PENETRATIONS OF MASONRY AND FIRE-RATED GYPSUM WALLS AND OF ALL OTHER FIRE-RATED FLOOR AND WALL ASSEMBLIES. INSTALL SLEEVES DURING ERECTION OF CONCRETE AND MASONRY WALLS. Q.SECURELY FASTEN ELECTRICAL ITEMS AND THEIR SUPPORTS TO THE BUILDING STRUCTURE, UNLESS OTHERWISE INDICATED. PERFORM FASTENING ACCORDING TO THE FOLLOWING UNLESS OTHER FASTENING METHODS ARE INDICATED: 1.WOOD: FASTEN WITH WOOD SCREWS OR SCREW-TYPE NAILS. 2.MASONRY: TOGGLE BOLTS ON HOLLOW MASONRY UNITS AND EXPANSION BOLTS ON SOLID MASONRY UNITS. 3.NEW CONCRETE: CONCRETE INSERTS WITH MACHINE SCREWS AND BOLTS. 4.EXISTING CONCRETE: EXPANSION BOLTS. 5.INSTEAD OF EXPANSION BOLTS, THREADED STUDS DRIVEN BY A POWDER CHARGE AND PROVIDED WITH LOCK WASHERS MAY BE USED IN EXISTING CONCRETE. 6.STEEL: WELDED THREADED STUDS OR SPRING-TENSION CLAMPS ON STEEL. 7.FIELD WELDING: COMPLY WITH AWS D1.1. 8.WELDING TO STEEL STRUCTURE MAY BE USED ONLY FOR THREADED STUDS, NOT FOR CONDUITS, PIPE STRAPS, OR OTHER ITEMS. 9.LIGHT STEEL: SHEET-METAL SCREWS. 10.FASTENERS: SELECT SO THE LOAD APPLIED TO EACH FASTENER DOES NOT EXCEED 25 PERCENT OF ITS PROOF-TEST LOAD. 3.07 CUTTING, PATCHING AND FIRESTOPPING A.ALL CUTTING AND PATCHING REQUIRED TO THE EXISTING BUILDING STRUCTURE FOR THE WORK SHALL BE INCLUDED UNDER THIS CONTRACT AND BE ACCEPTABLE TO THE LANDLORD. OBTAIN WRITTEN APPROVAL FROM LANDLORD BEFORE ANY CUTTING IS CARRIED OUT. B.WHERE CONDUITS PASS THROUGH FIRE RATED WALLS OR FLOORS, PROVIDE FIRE STOPPING MATERIAL LISTED WITH, AND BEAR LABEL OF CSA AND ULC, AND MAINTAIN SAME FIRE RATING OF BUILDING COMPONENT PENETRATION. C.APPLY FIRESTOPPING TO CABLE AND RACEWAY PENETRATIONS OF FIRE-RATED FLOOR AND WALL ASSEMBLIES TO ACHIEVE FIRE-RESISTANCE RATING OF THE ASSEMBLY. D.CUT, CHANNEL, CHASE, AND DRILL FLOORS, WALLS, PARTITIONS, CEILINGS, AND OTHER SURFACES REQUIRED TO PERMIT ELECTRICAL INSTALLATIONS. PERFORM CUTTING BY SKILLED MECHANICS OF TRADES INVOLVED. E.REPAIR AND REFINISH DISTURBED FINISH MATERIALS AND OTHER SURFACES TO MATCH ADJACENT UNDISTURBED SURFACES. INSTALL NEW FIREPROOFING WHERE EXISTING FIRESTOPPING HAS BEEN DISTURBED. REPAIR AND REFINISH MATERIALS AND OTHER SURFACES BY SKILLED MECHANICS OF TRADES INVOLVED. 3.08 ELECTRICAL FURNITURE SYSTEMS A.THE ELECTRIFIED FURNITURE VENDOR WILL SUPPLY ALL RECEPTACLES, FURNITURE TASK LIGHTING FIXTURES, WIRING HARNESSES, CONNECTORS AND FITTINGS TO THE ELECTRICAL CONTRACTOR FOR THE COMPLETE WIRING INSTALLATION. ALL WIRING AND COMPONENTS SHALL BE INSTALLED AS DIRECTED BY VENDOR. B.ELECTRICAL CONTRACTOR SHALL FURNISH AN 18" MAXIMUM LIQUID TIGHT FLEXIBLE CONDUIT CONNECTIONS WITH REQUIRED PHASE CONDUCTORS, NEUTRAL CONDUCTORS AND GROUND CONDUCTORS AS INDICATED FROM WALL OR FLOOR OUTLET. C.THE FURNITURE VENDOR SHALL CHALK THE FURNITURE SYSTEM OUTLINE ON THE FLOOR FOR COORDINATION OF POWER AND COMMUNICATION IN-FEED LOCATIONS. IN-FEED LOCATIONS INDICATED ON PLAN DOCUMENTS ARE FOR CLARITY PURPOSES. IN-FEED LOCATIONS AND QUANTITY SHALL BE APPROVED IN FIELD BY ARCHITECT AND FURNITURE SYSTEM VENDOR PRIOR TO INSTALLATION. 1.08 OPERATION AND MAINTENANCE MANUALS A.PROVIDE 2 (TWO) SETS OF OPERATION AND MAINTENANCE MANUALS SUBMITTED IN HARD COVER 3-RING BINDERS. INCLUDE THE FOLLOWING INFORMATION IN THE OPERATIONS AND MAINTENANCE MANUALS: 1.NAMES AND ADDRESS OF LOCAL SUPPLIERS FOR THE ITEMS INCLUDED. 2.TECHNICAL DATA, PRODUCT DATA, SUPPLEMENTED BY BULLETINS, COMPONENT ILLUSTRATIONS, EXPLODED VIEWS, TECHNICAL DESCRIPTIONS OF ITEMS, AND PARTS LISTS. ADVERTISING OR SALES LITERATURE IS NOT ACCEPTABLE. 3.THE CONSULTANTS REVIEWED SHOP DRAWINGS. 4.CERTIFICATE(S) OF ACCEPTANCE FROM THE AUTHORITIES INSPECTION DEPARTMENT. 5.VERIFICATION REPORTS AND CERTIFICATE(S) FOR ANY NEW FIRE ALARM COMPONENTS OR TIE-INS AND ANY BASE BUILDING TIE-INS FOR MISCELLANEOUS SYSTEMS (I.E. SECURITY, LIGHTING CONTROL, DIGITAL METERING). 6.LOAD BALANCE REPORT. 7.WRITTEN GUARANTEE. 8.LIST OF EACH FIXTURE TYPE IDENTIFYING TYPE OF LAMP, WATTAGE AND MANUFACTURER'S CONTACT INFO. B.REVIEW INFORMATION PROVIDED IN THE MAINTENANCE INSTRUCTIONS AND MANUALS WITH THE TENANT'S OPERATING PERSONNEL AND LANDLORD'S OPERATING PERSONNEL WHERE BASE BUILDING SYSTEMS ARE REVISED, TO ENSURE A COMPLETE UNDERSTANDING OF THE ELECTRICAL EQUIPMENT AND SYSTEMS AND THEIR OPERATION. 1.10 CONTRACT DOCUMENTS A.THE DRAWINGS FOR THE ELECTRICAL WORK ARE DIAGRAMMATIC PERFORMANCE DRAWINGS ONLY, INTENDED TO CONVEY THE SCOPE OF WORK AND INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE SIZE AND LOCATION OF ELECTRICAL EQUIPMENT. THE DRAWINGS DO NOT INTEND TO SHOW ARCHITECTURAL, INTERIOR DESIGN, MECHANICAL, STRUCTURAL OR BASE BUILDING DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR A THOROUGH KNOWLEDGE OF SAME BEFORE PROCEEDING WITH THE WORK. B.DO NOT SCALE OR MEASURE DRAWINGS, BUT OBTAIN INFORMATION REGARDING ACCURATE DIMENSIONS FROM THE DIMENSIONS SHOWN ON THE DESIGN CONSULTANT/ARCHITECT'S DRAWINGS, OR BY SITE MEASUREMENTS. C.ANY DISCREPANCIES BETWEEN DRAWINGS AND/OR SPECIFICATIONS AND EXISTING CONDITIONS, MUST BE REFERRED TO THE DESIGN CONSULTANT/ARCHITECT BEFORE ANY WORK AFFECTED IS BEGUN. D.COOPERATE AND COORDINATE WITH OTHER CONTRACTORS IN LAYING OUT OF WORK SO AS NOT TO CONFLICT WITH THE WORK OF OTHER CONTRACTORS. CARRY OUT WORK PROMPTLY AS PER CONSTRUCTION SCHEDULE AND COORDINATE WITH WORK OF OTHER CONTRACTORS. E.MAKE, AT NO ADDITIONAL COST, ANY CHANGES OR ADDITIONS TO MATERIALS AND EQUIPMENT NECESSARY TO ACCOMMODATE STRUCTURAL CONDITIONS (OFFSETS AROUND BEAMS, COLUMN, ETC.) 2.08 CIRCUIT BREAKERS A.FOR PANELBOARD APPLICATIONS, CIRCUIT BREAKERS SHALL BE BOLTED TO THE PANELBOARD BUS BARS. WHERE CIRCUIT BREAKERS ARE INSTALLED IN EXISTING PANELBOARD BREAKERS SHALL BE OF THE SAME MANUFACTURER AND INTERRUPTING RATING. BREAKERS SHALL BE COMPATIBLE WITH EXISTING PANELBOARD. B.CIRCUIT BREAKERS SHALL BE "THERMAL MAGNETIC" TYPE, QUICK-MAKE, QUICK- BREAK, TRIP-FREE WITH NON-WELDING CONTACTS COMPENSATED FOR AMBIENT TEMPERATURES AND SHALL HAVE A MINIMUM SHORT CIRCUIT RATING OF 10,000 AMPERES SYMMETRICAL FOR 120/280V PANELS AND 14,000 AMPERES SYMMETRICAL FOR 277/480V PANELS OR HIGHER WHERE NOTED. C.MULTI-WIRE BRANCH CIRCUITS SUPPLYING POWER TO MORE THAN ONE DEVICE OR EQUIPMENT SHALL BE PROVIDED WITH A MEANS TO DISCONNECT SIMULTANEOUSLY ALL UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE BRANCH CIRCUIT ORIGINATES. CONTRACTOR SHALL COORDINATE WITH LOCAL AHJ THE MEANS REQUIRED TO MEET NYCEC/NEC SECTIONS 210.4(B). CONTRACTOR SHALL REMOVE AND REPLACE ALL EXISTING CIRCUIT BREAKERS THAT CAN NOT BE RETROFITTED WITH TIE BARS AS REQUIRED TO COMPLY WITH REQUIREMENT. D.TANDEM BREAKERS MAY NOT BE UTILIZED. E.PROVIDE BREAKER LOCKS FOR ALL NEW AND EXISTING BREAKERS SERVING EXIT LIGHTS, EMERGENCY LIGHTING AND EMERGENCY BATTERY PACKS. F.WHERE INDICATED TO BE LSI TYPE, CIRCUIT BREAKERS SHALL BE SOLID-STATE ELECTRONIC TRIP WITH FIELD-ADJUSTABLE LONG-TIME AND SHORT-TIME PICKUP LEVELS, LONG-TIME AND SHORT-TIME TIME ADJUSTMENTS, INSTANTANEOUS TRIP. PROVIDE ADJUSTABLE GROUND FAULT PICKUP AND TIME DELAY WHERE INDICATED. 2.01 RACEWAYS A.EMT: ANSI C80.3, ZINC-COATED STEEL, WITH SET-SCREW OR COMPRESSION FITTINGS. ELECTRIC METALLIC TUBING SHALL BE INDUSTRY STANDARD THIN WALL CONDUIT, HOT DIPPED GALVANIZED STEEL (1/2" MIN, 4" MAX). B.FMC: ZINC-COATED STEEL. THE FLEXIBLE METALLIC CONDUIT SHALL BE OF THE GROUNDING TYPE. IT SHALL CONSIST OF GALVANIZED STEEL TAPE FORMED INTO AN INDUSTRY STANDARD INTERLOCKING COIL (1/2" MIN). C.RMC: ANSI C80.1, HOT-DIPPED GALVANIZED STEEL WITH THREADED FITTINGS. RIGID METAL CONDUIT SHALL BE INDUSTRY STANDARD STEEL CONDUIT (1/2" MIN, 4" MAX). D.RACEWAY FITTINGS: SPECIFICALLY DESIGNED FOR THE RACEWAY TYPE WITH WHICH USED. E.FOR ALL SIZES OF CONDUIT LARGER THAN 1-1/2", USE STANDARD ELBOW. F.CONDUIT SHALL BE SECURELY FASTENED IN PLACE AND HANGERS, SUPPORTS OR FASTENINGS SHALL BE PROVIDED AT EACH ELBOW AND AT EACH END OF EACH STRAIGHT RUN TERMINATED AT A BOX OR CABINET. G.PROVIDE EXPANSION FITTINGS IN EACH CONDUIT RUN WHEREVER IT CROSSES AN EXPANSION JOINT AND WHEREVER THE CONDUIT LENGTH EXCEEDS 200 FEET. H.UNLESS OTHERWISE INDICATED OR SPECIFIED, ALL WIRING SHALL BE INSTALLED CONCEALED. I.FEEDERS AND BRANCH CIRCUITRY ABOVE HUNG CEILING AND IN PARTITIONS SHALL BE RUN IN ELECTRICAL METALLIC TUBING (EMT) UNLESS OTHERWISE NOTED. REFER TO WIRING SECTION BELOW FOR SITUATIONS WHERE MAC CABLE MAY BE ACCEPTABLE. J.FINAL CONNECTIONS TO MOTORS, LIGHT FIXTURES, TRANSFORMERS, AND EQUIPMENT SUBJECT TO VIBRATION WILL BE DONE WITH FLEXIBLE METALLIC CONDUIT. LENGTH SHALL NOT EXCEED 6 FEET. K.ALL CONDUIT IN MECHANICAL ROOMS, ELECTRICAL CLOSETS AND WHERE CONCEALED IN CONCRETE OR INSTALLED OUTDOORS SHALL BE EMT. L.ALL CONDUITS INSTALLED IN CONCRETE OR OUTDOORS SHALL BE PROVIDED WITH WEATHERPROOF CONNECTORS. M.ALL METAL CONDUIT TERMINATING IN A METAL ENCLOSURE SHALL HAVE AN INSULATED BUSHING. PROVIDE "GROUNDING" TYPE BUSHING WHERE REQUIRED. N.WHERE CONDUITS ARE RUN IN THE CEILING SPACE OF THE FLOOR BELOW, THEY SHALL BE CONTINUOUS AND HAVE NO JUNCTION OR PULL BOXES UNLESS PRIOR APPROVAL IS GIVEN BY BUILDING MANAGEMENT/CLIENT. O.INSTALL CONDUITS TO CONSERVE HEADROOM, PARALLEL AND PERPENDICULAR TO BUILDING LINES. DO NOT CLIP CONDUITS TO CEILING HANGER. P.WALL COMMUNICATIONS CONDUIT SHALL BE REAMED AND INSTALLED COMPLETE WITH INSULATED BUSHINGS AT EACH END. 2.10 TRANSFORMERS - NOT USED. 1.11 INTENT A.IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS THAT THE CONTRACTOR PROVIDE COMPLETE AND OPERATIONAL SYSTEMS AS REQUIRED. WHERE DIFFERENCES OCCUR, THE MAXIMUM CONDITION SHALL GOVERN. B.ANY MISCELLANEOUS ITEMS, HARDWARE, DEVICES, WIRING, ETC., NOT SPECIFICALLY DESCRIBED, BUT REQUIRED FOR THE OPERATION OF THE SYSTEM, MUST BE PROVIDED AND INCLUDED AS PART OF THE BID. 2.11 TENANT SUB-METERING - NOT USED. 1.14 ACCESS DOORS A.WHEREVER ANY BASE BUILDING EQUIPMENT REQUIRES ACCESSIBILITY, MAINTENANCE OR ADJUSTMENT, PROVIDE ACCESS DOORS APPROVED BY DESIGN CONSULTANT/ARCHITECT AND LANDLORD. B.ACCESS DOORS SHALL BE FINISHED TO MATCH ADJACENT SURFACES. C.IN ALL DRYWALL CEILING AREAS, CONTRACTOR SHALL REMOVE AND RELOCATE ALL EXISTING JUNCTION BOXES TO ACCESSIBLE CEILING SPACE. D.PROVIDE ACCESS PANELS FOR ALL NEW AND EXISTING DEVICES AS REQUIRED. G. FOR TEMPORARY POWER, FURNISH AND INSTALL WIRING FOR ADEQUATE LIGHT AND SMALL TOOLS POWER FOR THE PROJECT. THIS SHALL INCLUDE STRINGERS, LAMPS, OUTLETS, BREAKERS, AND FUSING, AS IT IS NECESSARY. ALL TEMPORARY WIRING SHALL BE REMOVED FROM SPACE AT COMPLETION OF PROJECT. H. FURNISH AND INSTALL A MINIMUM 1" EMPTY CONDUIT FOR ALL WALL MOUNTED LOW VOLTAGE EQUIPMENT JUNCTION BOXES. CONDUIT SHALL BE STUBBED 6" ABOVE HUNG CEILING AND TURNED TOWARDS TERMINATION CLOSET ABOVE ACCESSIBLE CEILING AREA. I. COORDINATE WITH THE BUILDING OWNER FOR ANY SERVICE INTERRUPTION OF EXISTING SYSTEMS AND GIVE NOTICE AS REQUIRED BY BUILDING RULES AND REGULATIONS OR A MINIMUM OF FIVE (5) DAYS PRIOR TO ANY WORK, WHICHEVER IS MORE STRINGENT. CONTRACTOR IS TO PERFORM WORK ON PREMIUM TIME SO AS TO NOT DISTURB EXISTING TENANTS ON OTHER FLOORS. J. WHEN USING TEMPORARY LIGHTING, THE CONTRACTOR SHALL CLEARLY LABEL PANELS AND BREAKERS USED FOR LIGHTING. LOCATION OF PANELS TO BE SHOWN ON FLOOR PLAN POSTED AT ENTRANCE TO WORK AREA. PROPER TEMPORARY LIGHTING AND POWER MUST BE INSTALLED AND MAINTAINED IN ALL WORK AREAS. CONNECTIONS TO EXISTING STAIRWELL AND EXIT LIGHT SYSTEMS ARE NOT PERMITTED. K. THE CONTRACTOR SHALL CUT BACK TO THE FLOOR, WALL OR CEILING, REMOVE WIRING AND PLUG BOTH ENDS OF CONCEALED CONDUITS MADE OBSOLETE BY THIS ALTERNATION. EXPOSED CONDUITS, WIREWAYS, OUTLET BOXES, PULL BOXES, HANGERS, ETC. MADE OBSOLETE BY THE ALTERNATION WORK SHALL BE REMOVED, UNLESS OTHERWISE NOTED. L. IT IS POSSIBLE THAT THERE WILL BE CERTAIN REMOVALS AND RELOCATIONS OF THE EXISTING ELECTRICAL INSTALLATION NECESSARY FOR THE SATISFACTORY PERFORMANCE OF THE WORK. THESE CHANGES CANNOT BE COMPLETELY DETAILED ON THE DRAWINGS, BUT MUST BE CONSIDERED BY THE CONTRACTOR WHILE REVIEWING THE EXISTING CONDITIONS AT THE SITE AND PREPARING THE PROPOSAL. SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com EL E C T R I C A L S P E C I F I C A T I O N S E0.02 SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI NE ER ELECTR ICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com TI T L E 2 4 I N D O O R E0.03 SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI NE ER ELECTR ICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 PA R T N E R S 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com TI T L E 2 4 O U T D O O R E0.04 SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI NE ER ELECTR ICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 PA R T N E R S 800 N Tustin Ave Unit #H1/23/2025 1.MAXIMUM AVAILABE FAULT CURRENT FROM SCE UTILITY COMPANY IS: 30,000 AIC. AFC = 30,000 + MOTOR CONTRIBUTION = 30,000 + (6 X 70) = 30,420 A 2.ALL EQUIPMENT BUSSING AND GROUNDING ELECTRODE SHALL BE COPPER AND ALL WIRES SHALL BE COPPER, THWN/THHN UNLESS NOTED OTHERWISE. 3.THE MAIN SWITCHBOARD AND PANEL BOARDS SHALL BE BY ONE MANUFACTURER ONLY. 4.ALL FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE HOLDER. 5.MAIN SWITCHGEAR CIRCUIT BREAKERS TO BE FULLY RATED FOR THE FAULT CURRENT AVAILABLE. 6.ALL CIRCUIT BREAKER SHALL BE LABELLED TO CLEARLY INDICATE AREA BEING SERVED. 7.UNDERGROUND CONDUIT SHALL BE MINIMUM OF PVC SCHEDULE 40. REFER TO 2022 CEC TABLE 300.5 FOR THE MINIMUM COVER REQUIREMENTS OF DIRECT BURIAL CABLE. 8.ALL METAL PIPING & STRUCTURES INCLUDING GAS PIPING THAT IS LIKELY TO BE ENERGIZED SHALL BE BONDED TO THE SERVICE GROUNDING POINT AS DESCRIBED IN CEC SECTION 250.104. FIELD VERIFY & PROVIDE BONDING JUMPERS AS REQUIRED. 9.ALL TERMINATIONS AND CIRCUIT BREAKERS SHALL BE RATED FOR 75 DEGREES CENTIGRADE. 10.ALL ELECTRICAL EQUIPMENT, PANELS, FEEDERS, ETC. ARE NEW UNLESS NOTED OTHERWISE. 11.ALL THE ELECTRICAL SERVICES AND REQUIREMENTS ARE SUBJECT TO THE APPROVAL BY THE UTILITY COMPANY AND THE DEPARTMENT OF BUILDING AND SAFETY. VERIFY EXACT REQUIREMENTS PRIOR TO ROUGH-INS. 12.ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH SCE SERVICE PLANNER FOR THE PRIMARY ELECTRICAL SERVICE PRIOR TO ANY WORK. 13.FEEDER LENGTH IS FOR CALCULATION ONLY NOT FOR BIDDING PURPOSES. 14.THE MAIN SERVICE SHALL BE TESTED BY A THIRD PARTY NRTL TESTING LABORATORY AND SHALL BE CERTIFIED FOR SERVICE GROUND FAULT PROTECTION. THE MAIN SERVICE SHALL NOT BE ENERGIZED PRIOR TO BUILDING INSPECTORS' RECEIPT OF THE THIRD PARTY TESTING REPORT. REFERENCE NOTES: GENERAL NOTES 1.3/4"C - 1#6 CU G.. 2.TRANSFORMER PRIMARY DISCONNECTING MEANS SHALL BE LOCKABLE IN ACCORDANCE WITH CEC 110.25 AND IT'S LOCATION SHALL BE FIELD MARKED ON THE TRANSFORMER PER CEC 450.14. 3.PROVIDE SURGE PROTECTION DEVICE FOR THE MAIN SWITCHBOARD. 4.PROVIDE EMON-DMON TYPE ELECTRICAL METER IN THE ELECTRICAL CLOSET NEXT TO MAIN SWITCHBOARD TO MEASURE THE ELECTRICAL USAGE OF PANEL 'LA'. - MAIN SWITCHBOARD 'MSB' 400A, 277/480V, 3PH, 4W, 42KAIC INCOMING UNDERGROUND SERVICE CONDUCTOR FROM SCE TRASFORMER M 400A 3P 125A 3P 70A 3P 1- 1 / 2 " C - 3 # 1 C U + 1 # 6 C U G . L= 4 0 ' , % V D = 0 . 2 4 % SCE METER G N 1"C., 1#3/0 CU TO BUILDING STEEL 1"C., 1#3/0 CU UFER GROUND 1"C., 1#3/0 TO COLD WATER PIPING WITHIN 5FT OF ENTRANCE TO BUILDING 400A BUS (N) XFMR 'TLA' 45KVA 480-120/208V 3PH, 4W %Z = 3.9% PANEL 'LA' 150A MCB 1 Isc = 3.1kA AFC = 30,420A SEE GENERAL NOTE 1 1 4 MRI CHILLER @ ROOF 60AS 60AF 3P 60A 3P 3 MRI MAIN DISC. PANEL (MDP) 200AS 125AF 3P Isc=18.9kA 1- 1 / 4 " C - 3 # 4 C U + 1 # 8 C U G . L= 6 0 ' , % V D = 0 . 3 5 % 2 2" C - 4 # 1 / 0 C U + 1 # 6 C U G . L= 1 0 ' , % V D = 0 . 1 4 % 125A 3P 1- 1 / 2 " C - 3 # 1 C U + 1 # 1 C U G . L= 7 0 ' , % V D = 0 . 4 2 % 2 CT SCAN 200AS 125AF 3P 1" C - 3 # 6 C U + 1 # 1 0 C U G . L= 5 0 ' , % V D = 0 . 3 4 % Isc=14.8kA Isc=9.3kA Isc=11.2kA SPD 30A 3P 3 5 10KAIC M 4 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L 1 SI N G L E L I N E D I A G R A M E2.01 1 PA R T N E R S SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI N EER ELECTRICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com PA N E L S C H E D U L E S E3.01 SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI NE ER ELECTR ICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 PA R T N E R S 800 N Tustin Ave Unit #H1/23/2025 T U S T I N A V E N U E CL FRUIT STREETCL 20 7 9 1 14 8 2 H FG E D C B A I J K L M 8 14 8 1 2 (N) 6'X8'-6" SCE TRANSFORMER PAD (N) MAIN SWITCHBOARD 'MSB' 400A, 277/480V, 3PH, 4W, 42KAIC (2) 4" CONDUITS FROM TRANSFORMER PAD TO MAIN SWITCHBOARD 'MSB' (E)METER FOR SUITE "H" TO BE REMOVED COORDINATE WITH SCE SCOPE OF WORK SUITE H REFERENCE NOTES:- 1.- SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L 1 EL E C T R I C A L S I T E P L A N E4.01 GENERAL NOTES 1.ELECTRICAL CONTRACTOR TO CHECK ALL FEASIBLE ROUTING OF CONDUITS AND WIRES AT THE JOB SITE INCLUDING LOCATIONS OF ALL ADDITIONAL EQUIPMENT FOR A COMPLETE FUNCTIONAL CODE COMPLIANT ELECTRICAL SYSTEM. 2.CONTRACTOR SHALL VISIT SITE AND DETERMINE ALL CONDITIONS AFFECTING ELECTRICAL WORK AND INCLUDE COSTS THEREFORE IN THIS CONTRACT PRICE. 3.CONTACT UTILITY COMPANIES AND PROVIDE ALL SERVICES, WORK, INSTALLATION AND COORDINATION REQUIRED FOR THEIR USE. 4.CONDUITS STUBS SHALL BE TERMINATED IN ACCESSIBLE LOCATIONS, SECURELY CAPPED, AND LOCATED BY AN APPROVED VISIBLE MARKER. 5.INSTALL APPROVED GROUNDING BUSHING AT EACH TERMINATION OF RIGID CONDUIT. 6.ALL WORK REQUIRED FOR THE UTILITY SERVICES SHALL CONFORM TO THE REQUIREMENTS AND STANDARDS OF THE SERVING UTILITY COMPANIES. 7.LOCATION AND ROUTING OF ALL EXPOSED EQUIPMENT, PIPING, DUCTWORK, AND CONDUIT SHALL BE APPROVED BY THE ARCHITECT PRIOR TO START OF ANY WORK. 8.ALL UNDERGROUND ELECTRICAL CONDUITS SHALL BE PVC SCH. 40 MINIMUM. 9.ALL EXTERIOR CONDUITS SHALL BE INSTALLED AT LEAST 24" BELOW GRADE OR SHALL MEET THE REQUIREMENTS BASED ON 2022 CEC TABLE 300.5 10.CONDUIT RUNS ARE DIAGRAMMATIC ONLY. 11.REFER TO 2022 CEC TABLE 300.5 FOR THE MINIMUM COVER REQUIREMENTS OF DIRECT BURIAL CABLE. PROVIDE 24" BURIAL DEPTH OF UNDERGROUND CABLES FOR CONDUITS AND CONDUCTORS AND PROVIDE ALL REQUIRED COVER MATERIALS FOR THE DIRECT BURIED CONDUCTOR AND THE TOP SURFACE OF FINISH GRADE, CONCRETE OR SIMILAR COVER. 12.OBSERVE CLEAN ELECTRICAL INSTALLATION ALL THROUGHOUT THE SPACE. Scale: 1/16"=1'-0" ELECTRICAL SITE PLAN 1 PA R T N E R S SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI N EER ELECTRICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 ENTRY PROPOSED NEW CANOPY AT THE ENTRY +18" +18" +18"+18" +18" +60 +18" +18" +18" +18" +18" +18" +18" +18" +18" +18" +18" RF SHIELD MAGNET ROOM SIDE MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G NE C MAGNET ROOM SIDE RF SHIELD MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G FEC 41 52 A B 3 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGINGROOM 103 OPERATORS 104 MRI 105 EQUIPMENT 108 STORAGE +18" +18" MSB:2 PANEL 'LA' (N) MAIN SWITCHBOARD 'MSB' 400A, 277/480V, 3PH, 4W, 42KAIC 2 5 +42"5 J 6 LA:32 LA:11 1 LA:15,17 3 LA:7,9 LA:13 LA:1 LA:3 J 5 LA:30 4 1 11 11 3 3 5 5 LA:5 7 7 7 9 9 15 13 13 11 11 17 17 15 MSB:1 8 8 J LA:25 XFMR 'TLA' 11 REFERENCE NOTES:- SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L 1 PO W E R P L A N E5.01 GENERAL NOTES 1.ALL WORK SHALL COMPLY WITH 2022 CALIFORNIA ELECTRIC CODE. 2.REFER TO DRAWING E0.01 FOR GENERAL NOTES. 3.ALL BREAKERS FEEDING MULTIPLE CIRCUIT HOMERUNS SHALL BE PROVIDED WITH UL LISTED HANDLE TIES ON SINGLE POLE BREAKERS SERVING MULTI WIRE BRANCH CIRCUITS IN COMPLIANCE WITH CEC 210.4B. HANDLE TIE SHALL BE SQUARE D CATALOG NUMBER QO1HT. 4.RECEPTACLES GANGED TOGETHER SHALL BE MOUNTED UNDER SINGLE COVER PLATE. 5.COORDINATE EXACT LOCATION OF RECEPTACLES WITH ARCHITECT. SCALING OF ENGINEERING DOCUMENTS FOR LOCATIONS OF DEVICES SHALL NOT BE PERMITTED. 6.PROVIDE TELE/DATA BOXES AND AN EMPTY CONDUIT SYSTEM. TELE/DATA CABLING BY OTHERS. INSTALL PULL STRING IN EACH EMPTY CONDUIT. 7.REFER TO THE MECHANICAL AND PLUMBING DRAWINGS FOR EXACT LOCATION OF ALL EQUIPMENT. 8.REFER TO ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL DEVICES (I.E. RECEPTACLES, DATA/TELEPHONE OUTLETS, SECURITY DEVICES, PANELS, SPEAKER/STROBE, ETC.) MAXIMUM 48" AFF TO TOP OF DEVICE AND MINIMUM 15" AFF TO BOTTOM OF DEVICE. 9.NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT. 10.ALL TELEPHONE/DATA CONDUIT STUB-UPS, WHERE GYPBOARD CEILINGS OCCUR, SHALL RUN INTO ACCESSIBLE CEILING AREAS. 11.ANY DISCREPANCIES SHALL BE DIRECTED TO ARCHITECT PRIOR TO BIDDING. WHERE DISCREPANCIES CANNOT BE RESOLVED PRIOR TO SUBMITTING BIDS, CONTRACTOR SHALL PROCEED BASED ON MORE COSTLY OR RESTRICTIVE INTERPRETATIONS. 12.DO NOT INSTALL OUTLETS BACK TO BACK ON THE SAME PARTITION. WHERE OUTLETS MUST BE LOCATED IN THE SAME STUD CAVITY ON OPPOSITE SIDES OF THE PARTITION, INSTALL A VERTICAL AND HORIZONTAL STUD, AS REQUIRED, SEPARATING SUCH OUTLETS. 13.ALL SLAB CORING LOCATIONS SHALL BE FIELD VERIFIED FOR ANY OBSTRUCTIONS BELOW THE SLAB. LOCATIONS SHALL BE X-RAYED WITH ALL REBAR AND ELECTRICAL LINES INDICATED. 14.NO EQUIPMENT, J-BOXES, ETC. REQUIRING ACCESS SHALL BE LOCATED IN HARD CEILING AREAS UNLESS ACCESS PANEL IS PROVIDED, COORDINATE WITH ARCHITECT. 15.ALL WIRING IN OPEN AREAS TO BE RUN NEATLY IN CONDUIT. 16.ALL THE NEW AND EXISTING DATA OUTLETS SHALL BE PROVIDED WITH A NEW CONDUIT STUBBED UP TO THE ACCESSIBLE LOCATION AND PROVIDE WIRING TO THE NEW DATA ROOM LOCATION. 17.ALL DEDICATED 120V RECEPTACLE OUTLET SHALL HAVE SEPARATE CIRCUIT AND RECEPTACLE SHALL BE NEMA 5-20R. 18.ALL FEEDER WIRES SHALL BE COPPER (CU), UNLESS NOTED OTHERWISE. 19.FOR 15A, 20A, 25 AND 30 AMPERE BRANCH CIRCUIT, THE EQUIPMENT GROUNDING CONDUCTORS SHALL BE THE SAME AWG AS THE UNGROUNDED CONDUCTOR. (CEC 250.122 (A)(B)). 20.ALL ELECTRICAL OUTLETS LOCATED ABOVE COUNTERTOP INCLUDING BATHROOM COUNTERTOP SHALL BE GFCI DUPLEX OUTLET. GFCI OUTLET SHALL BE SELF-TEST, SELF-DIAGNOSTIC TYPE HUBBELL AUTOGUARD SERIES OR EQUAL. 21.ALL THE BRANCH CIRCUITS SHALL BE (1)3/4"C. - 2#12 CU+1#12CU G. UNLESS OTHERWISE NOTED. 22.PROVIDE 3/4" C.O. FOR HVAC CONTROLS. E.C. AND HVAC CONTRACTOR SHALL COORDINATE WITH VENDOR FOR EXACT LOW VOLTAGE REQUIREMENTS SERVING HVAC EQUIPMENT. 23.ALL CIRCUITS SHOWN ENTERING MRI ROOM SHALL BE PROTECTED WITH RF FILTER. SCALE: POWER PLAN - SUITE H 11/4" = 1'-0" 1.MAIN DISCONNECT PANEL (MDP) FOR MRI EQUIPMENT PROVIDED BY GE INSTALLED BY ELECTRICAL CONTRACTOR. VERIFY EXACT LOCATION IN FIELD. 2.RF FILTER PANEL FOR POWER AND LIGHTING IN THE MRI ROOM. VERIFY EXACT LOCATION IN FIELD. 3.FOR CONNECTION TO FAUCET AND SOAP DISPENSER. VERIFY EXACT LOCATION IN FIELD. 4.FOR CONNECTION TO TV. VERIFY EXACT LOCATION IN FIELD. 5.FOR CONNECTION TO VIRTUAL WINDOW. VERIFY EXACT POWER SUPPLY LOCATION IN FIELD. INSTALL PER MANUFACTURER'S RECOMMENDATION AND GUIDELINES. ROUTE ELECTRICAL CONNECTION THROUGH RF FILTER. 6.FOR CONNECTION TO HAND DRYER. VERIFY EXACT LOCATION IN FIELD. 7.TRANSFORMER PRIMARY DISCONNECTING MEANS SHALL BE LOCKABLE IN ACCORDANCE WITH CEC 110.25 AND IT'S LOCATION SHALL BE FIELD MARKED ON THE TRANSFORMER PER CEC 450.14. 8.REFER TO SINGLE LINE DIAGRAM ON SHEET E2.01 FOR FEEDER AND DISCONNECT SIZE. 9.FOR CONNECTION TO LED SIGN. VERIFY EXACT LOCATION IN FIELD. SIGN LIGHTING SHALL BE CONTROLLED VIA PHOTOCELL AND ASTRONOMICAL TIME-CLOCK. 10.TRANSFORMER IS LOCATED IN THE ACCESSIBLE CEILING AND SHALL BE SUPPORTED FROM THE CEILING. REFER TO DETAIL 2/E5.01. 11.PROVIDE EMON-DMON TYPE ELECTRICAL METER IN THE ELECTRICAL CLOSET NEXT TO MAIN SWITCHBOARD TO MEASURE THE ELECTRICAL USAGE OF PANEL 'LA'. 9 10 Scale: NONE CEILING MOUNT TRANSFORMER SUPPORT DETAIL 1 1 1 1 1 1 ANGLE IRON SUPPORT (SIZE AS REQUIRED) TRANSFORMER BASE CHANNEL THREADED STEEL ROD (SIZE AS REQUIRED TO SUPPORT LOAD) SUPPORT FROM STRUCTURE ABOVE. PROVIDE MISCELLANEOUS STEEL AS REQUIRED TO CONNECT TO STRUCTURE. COORDINATE DETAIL WITH STRUCTURAL ENGINEER. SUBMIT LOADS IMPOSED. PRIMARY FLEXIBLE METAL CONDUIT WITH GROUND (24" MIN, 36" MAX) RIGID PRIMARY CONDUIT VIBRATION ISOLATION 7'-6" AFF (MIN) SECONDARY FLEXIBLE METAL CONDUIT WITH GROUND (24" MIN, 36" MAX) NUT, LOCK NUT, BOLT AND LOCK WASHERS AS REQUIRED TRAPEZE MOUNTED TRANSFORMER. PROVIDE METAL CHANNEL SUPPORT AS REQUIRED. RIGID SECONDARY CONDUIT GROUND BUSHING WITH GROUND CONNECTOR (SIZE PER CODE) 1 PA R T N E R S SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI N EER ELECTRICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 EXISTING ELECTRICAL ROOM NEW ELECTRICAL CLOSET ENTRY (E) COLUMN TO REMAIN (E) OPENING TO BE INFILLED WITH SOLID WALL CABINET NEW PAIR 4'-0" X 8'-0" DOORS (MAGNET ACCESS) proposed new electrical transformer PROPOSED NEW CANOPY AT THE ENTRY LOCKER ACCESS DOOR RF SHIELD MAGNET ROOM SIDE MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G NE C MAGNET ROOM SIDE RF SHIELD MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G 41 52 A B 3 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGINGROOM 103 OPERATORS 104 MRI 105 EQUIPMENT 108 STORAGE FC 1A FC 1B FC 2B FC 2A EF 1 EF 2 m LA:28 m 2 1 LA:14,16 m 2 1 LA:22,24 m 2 1 LA:18,20 m 2 1 LA:10,12 m 2 IWH-1 LA:34,36 m LA:26 1 2 3 REFERENCE NOTES:- SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com ME C H A N I C A L P O W E R P L A N E5.02 GENERAL NOTES 1.ALL WORK SHALL COMPLY WITH 2022 CALIFORNIA ELECTRIC CODE. 2.REFER TO DRAWING E0.01 FOR GENERAL NOTES. 3.ALL BREAKERS FEEDING MULTIPLE CIRCUIT HOMERUNS SHALL BE PROVIDED WITH UL LISTED HANDLE TIES ON SINGLE POLE BREAKERS SERVING MULTI WIRE BRANCH CIRCUITS IN COMPLIANCE WITH CEC 210.4B. HANDLE TIE SHALL BE SQUARE D CATALOG NUMBER QO1HT. 4.RECEPTACLES GANGED TOGETHER SHALL BE MOUNTED UNDER SINGLE COVER PLATE. 5.COORDINATE EXACT LOCATION OF RECEPTACLES WITH ARCHITECT. SCALING OF ENGINEERING DOCUMENTS FOR LOCATIONS OF DEVICES SHALL NOT BE PERMITTED. 6.PROVIDE TELE/DATA BOXES AND AN EMPTY CONDUIT SYSTEM. TELE/DATA CABLING BY OTHERS. INSTALL PULL STRING IN EACH EMPTY CONDUIT. 7.REFER TO THE MECHANICAL AND PLUMBING DRAWINGS FOR EXACT LOCATION OF ALL EQUIPMENT. 8.REFER TO ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL DEVICES (I.E. RECEPTACLES, DATA/TELEPHONE OUTLETS, SECURITY DEVICES, PANELS, SPEAKER/STROBE, ETC.) MAXIMUM 48" AFF TO TOP OF DEVICE AND MINIMUM 15" AFF TO BOTTOM OF DEVICE. 9.NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT. 10.ALL TELEPHONE/DATA CONDUIT STUB-UPS, WHERE GYPBOARD CEILINGS OCCUR, SHALL RUN INTO ACCESSIBLE CEILING AREAS. 11.ANY DISCREPANCIES SHALL BE DIRECTED TO ARCHITECT PRIOR TO BIDDING. WHERE DISCREPANCIES CANNOT BE RESOLVED PRIOR TO SUBMITTING BIDS, CONTRACTOR SHALL PROCEED BASED ON MORE COSTLY OR RESTRICTIVE INTERPRETATIONS. 12.DO NOT INSTALL OUTLETS BACK TO BACK ON THE SAME PARTITION. WHERE OUTLETS MUST BE LOCATED IN THE SAME STUD CAVITY ON OPPOSITE SIDES OF THE PARTITION, INSTALL A VERTICAL AND HORIZONTAL STUD, AS REQUIRED, SEPARATING SUCH OUTLETS. 13.ALL SLAB CORING LOCATIONS SHALL BE FIELD VERIFIED FOR ANY OBSTRUCTIONS BELOW THE SLAB. LOCATIONS SHALL BE X-RAYED WITH ALL REBAR AND ELECTRICAL LINES INDICATED. 14.NO EQUIPMENT, J-BOXES, ETC. REQUIRING ACCESS SHALL BE LOCATED IN HARD CEILING AREAS UNLESS ACCESS PANEL IS PROVIDED, COORDINATE WITH ARCHITECT. 15.ALL WIRING IN OPEN AREAS TO BE RUN NEATLY IN CONDUIT. 16.ALL THE NEW AND EXISTING DATA OUTLETS SHALL BE PROVIDED WITH A NEW CONDUIT STUBBED UP TO THE ACCESSIBLE LOCATION AND PROVIDE WIRING TO THE NEW DATA ROOM LOCATION. 17.ALL DEDICATED 120V RECEPTACLE OUTLET SHALL HAVE SEPARATE CIRCUIT AND RECEPTACLE SHALL BE NEMA 5-20R. 18.ALL FEEDER WIRES SHALL BE COPPER (CU), UNLESS NOTED OTHERWISE. 19.FOR 15A, 20A, 25 AND 30 AMPERE BRANCH CIRCUIT, THE EQUIPMENT GROUNDING CONDUCTORS SHALL BE THE SAME AWG AS THE UNGROUNDED CONDUCTOR. (CEC 250.122 (A)(B)). 20.ALL ELECTRICAL OUTLETS LOCATED ABOVE COUNTERTOP INCLUDING BATHROOM COUNTERTOP SHALL BE GFCI DUPLEX OUTLET. GFCI OUTLET SHALL BE SELF-TEST, SELF-DIAGNOSTIC TYPE HUBBELL AUTOGUARD SERIES OR EQUAL. 21.ALL THE BRANCH CIRCUITS SHALL BE (1)3/4"C. - 2#12 CU+1#12CU G. UNLESS OTHERWISE NOTED. 22.PROVIDE 3/4" C.O. FOR HVAC CONTROLS. E.C. AND HVAC CONTRACTOR SHALL COORDINATE WITH VENDOR FOR EXACT LOW VOLTAGE REQUIREMENTS SERVING HVAC EQUIPMENT. 23.ALL CIRCUITS SHOWN ENTERING MRI ROOM SHALL BE PROTECTED WITH RF FILTER. SCALE: MECHANICAL POWER PLAN - SUITE H 11/4" = 1'-0" 1.PROVIDE 1/2" CONDUIT TO THE CONTROL UNIT. WIRING PER MANUFACTURER'S RECOMMENDATION. 2.PROVIDE 3/4"C - 2#10 CU + 1#10 CU G. 3.EMERGENCY EXHAUST FAN SWITCH. COORDINATE CONNECTION REQUIREMENTS WITH MRI MANUFACTURER AND EXACT LOCATION IN FIELD. SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI NE ER ELECTR ICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 PA R T N E R S 800 N Tustin Ave Unit #H1/23/2025 E - HVAC 41 52 A B 3 HASKRIS OPC15 CHILLER 1,200 LBS. 320 lb. 140 lb. 120 lb. 140 lb. MSB:3 4 19WP LA:19 CH 1 3 LA:31,33 1 5 LA:6,8 1 2 LA:27,29 1 5 LA:2,4 1 5 HP 4 HP 3 HP 2 HP 1 60AS 40AF 2P 30AS 25AF 2P 30AS 25AF 2P 30AS 20AF 2P 1 REFERENCE NOTES:- SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 10 - 2 8 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L 1 RO O F P O W E R P L A N E5.03 GENERAL NOTES 1.VERIFY WITH THE MECHANICAL DRAWINGS FOR THE EXACT LOCATION OF HVAC EQUIPMENT. 2.VERIFY WITH THE PLUMBING DRAWINGS FOR THE EXACT LOCATION OF PLUMBING EQUIPMENT. 3.LOCATION AND ROUTING OF ALL EXPOSED EQUIPMENT, PIPING, DUCTWORK, AND CONDUIT SHALL BE APPROVED BY THE ARCHITECT PRIOR TO START OF ANY WORK. 4.ALL FEEDER WIRES SHALL BE COPPER (CU), UNLESS NOTED OTHERWISE. 5.PROVIDE GFCI, WEATHERPROOF RECEPTACLE ON THE ROOF AS SHOWN. 6.PROVIDE UNISTRUT FOR THE DISCONNECT SWITCHES AS REQUIRED. 7.PROVIDE 3'-0" CLEARANCE IN FRONT OF ALL DISCONNECT SWITCHES. 8.ALL THE BRANCH CIRCUITS SHALL BE (1)3/4"C. - 2#12 CU+1#12CU G. UNLESS OTHERWISE NOTED. 9.CONDUIT RUNS ARE DIAGRAMMATIC ONLY. ELECTRICAL CONTRACTOR SHALL VERIFY FEASIBLE CONDUIT ROUTING. 10.OBSERVE CLEAN ELECTRICAL INSTALLATION ALL THROUGHOUT THE SPACE. 11.ALL ELECTRICAL EQUIPMENT ON ROOF SHALL BE WEATHERPROOF, NEMA-3R OR BETTER. 12.ALL HVAC CONTROLS SHALL BE PROVIDED AND PROGRAMMED BY THE MECHANICAL CONTRACTOR ELECTRICAL CONTRACTOR TO PROVIDE ALL REQUIRED CONDUIT AND WIRES UP TO THE CONTROL BOX COORDINATE WITH MECHANICAL DRAWINGS FOR THE CONTROLS AND INTERCONNECTION AS REQUIRED BY ALL TRADES. 13.THE MOTOR OVERLOAD PROTECTION SHALL BE PERMITTED AS A SEPARATE FIELD INSTALLED DEVICE OR INTEGRAL WITH THE MOTOR ASSEMBLY. USE THE MOTOR NAMEPLATE FULL LOAD CURRENT TO SELECT THE OVERLOAD PROTECTION. 14.THE SMOKE DETECTORS AS PART OF THE REQUIRED AUTOMATIC SHUT DOWN FOR THE HVAC UNITS SHALL BE MONITORED BY THE REQUIRED FIRE ALARM SYSTEM. 15.REFER TO MECHANICAL DRAWINGS CONTROL DIAGRAM FOR ALL TIME SWITCHES, RELAYS, STARTERS, THERMOSTATS, CONDUIT FOR LINE/LOW VOLTAGE AS REQUIRED. 16.DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED AND FUSED WITH CURRENT LIMITING/TIME DELAY FUSES, SIZED PER MANUFACTURERS RECOMMENDATION. SWITCHES SHALL HAVE "RK-5" FUSE REJECTION CLIPS. SCALE: ROOF POWER PLAN - SUITE H 11/4" = 1'-0" 1.PROVIDE 1/2" CONDUIT TO THE CONTROL UNIT. WIRING PER MANUFACTURER'S RECOMMENDATION. 2.PROVIDE 3/4"C - 2#8 CU + 1#10 CU G. 3.REFER TO SINGLE LINE DIAGRAM ON SHEET E2.01 FOR FEEDER AND DISCONNECT SIZE. 4.VERIFY EXACT CHILLER ELECTRICAL SPECIFICATION WITH MANUFACTURER PRIOR TO INSTALLATION INCLUDING THE DISCONNECT AND BREAKER SIZE. 5.PROVIDE 3/4"C - 2#10 CU + 1#10 CU G. 1 1 1 PA R T N E R S SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI N EER ELECTRICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 EXISTING ELECTRICAL ROOM NEW ELECTRICAL CLOSET ENTRY (E) COLUMN TO REMAIN (E) OPENING TO BE INFILLED WITH SOLID WALL CABINET NEW PAIR 4'-0" X 8'-0" DOORS (MAGNET ACCESS) proposed new electrical transformer PROPOSED NEW CANOPY AT THE ENTRY LOCKER ACCESS DOOR RF SHIELD MAGNET ROOM SIDE MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G NE C MAGNET ROOM SIDE RF SHIELD MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G 41 52 A B 3 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGINGROOM 103 OPERATORS 104 MRI 105 EQUIPMENT 108 STORAGE osS D a OS J EX 21 F3 21c F3 21c F3 21c F3 21c F3 21c F3 21c F1 21d EM F1 21d F1 21d F1 21d F1 21x F1 21x F1 21x F1 21x F1 21x F1 21a EX 21 J F4 21b F4 21b F4 21b F4 21b F3 21a 2 F4 21b F4 21b F4 21c F4 21b F4 21b F4 21c F3 21a F3 21a F3 21a F3 21a F3 21a F4 21b F4 21b F4 21b F4 21b F4 21b 3 LA:21 F1 21a F1 21a F1 21a EM EM EM EM D os a D osF2 21 F2 21 D x D abc osS 2 1 (TYP) OS D cd F2 21 4 (TYP) 5 6 F5 23 S LA:23 S b 7 8 (TYP) F5 23b LA:23 9 F1 21 F1 21 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com LI G H T I N G P L A N E6.01 REFERENCE NOTES:-GENERAL NOTES 1.ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH 2022 CEC AND CENC CODE. 2.ALL HOMERUNS SHALL BE INSTALLED IN CONDUIT THROUGHOUT. 3.GENERAL CONTRACTOR TO VERIFY EXIT SIGN LOCATION AND COUNTS WITH FIRE INSPECTOR. 4.ALL LIGHT FIXTURES SHALL BE CONNECTED TO THE LIGHTING CONTROL SYSTEM VIA LOW VOLTAGE CONTROL WIRING UNLESS OTHERWISE NOTED. 5.EACH COMPONENT OF THE LIGHTING CONTROL SYSTEM SHALL BE ADDRESSABLE AND CAPABLE OF BEING INDEPENDENTLY CONTROLLED AND CONFIGURED THROUGH THE SYSTEM. PROVIDE THE REQUIRED RELAY PACKS AND DIMMING MODULES TO CONTROL ALL LIGHTING LOAD TYPES. 6.PROVIDE THE REQUIRED RELAY PACKS AND DIMMING MODULES TO CONTROL ALL LIGHTING LOAD TYPES. 7.ON NORMAL POWER FAILURE ALL LIGHTS CONNECTED TO EMERGENCY CIRCUITS SHALL AUTOMATICALLY COME UP TO FULL BRIGHTNESS AND REMAIN ON. 8.PROVIDE OCCUPANCY SENSOR, WALL OR CEILING MOUNTED AS SHOWN ON THIS PLAN WITH TYPE AND MODEL THAT CAN ACCOMMODATE THE SPACE REQUIREMENT FOR THE ROOM OR AREA. 9.DAYLIGHT PHOTOSENSOR AND DIMMING LEVEL SETTINGS SHALL BE COMMISSIONED AND ESTABLISHED IN THE FIELD AFTER FURNITURE AND FINAL FINISHES ARE INSTALLED AND LIGHTING IS OPERATIONAL. 10.CONTRACTOR SHALL PROVIDE SHOP DRAWING PREPARED BY THE LIGHTING CONTROLS MANUFACTURER. SHOP DRAWINGS PREPARED BY THIRD PARTY OTHER THAN MANUFACTURER ARE NOT ACCEPTABLE. 11.REFER TO ARCHITECTURAL AND/OR INTERIOR DESIGNER DRAWING FOR LIGHTING FIXTURE SCHEDULE. 12.LIGHTING SPECIFICATIONS SHALL BE COORDINATED WITH THE ARCHITECT PRIOR TO PURCHASING. 13.ALL THE BRANCH CIRCUITS SHALL BE (1)3/4"C. - 2#12 CU+1#12CU GRD. UNLESS OTHERWISE NOTED. 14.COORDINATE EXACT SWITCH LOCATION AND MOUNTING HEIGHTS WITH ARCHITECT/OWNER. 15.COORDINATE EXACT LOCATIONS OF LIGHTS AND LIGHTING CONTROL DEVICES WITH ARCHITECT 16.PRIMARY DAYLIGHT AREA/CONTROL ZONE DESIGNATED BY "PDZ" AND SECONDARY DAYLIGHT AREA/CONTROL ZONE DESIGNATED BY "SDZ" 17.PROVIDE EMERGENCY LIGHTING INVERTER WITH MINIMUM OF 120-MINUTES RUN TIME AS INDICATED ON THE PLAN. IN THE EVENT OF LOSS OF NORMAL POWER THE EMERGENCY LIGHTING CONTROL UNIT SHALL BYPASS THE LOCAL SWITCH/DIMMER FORCING THE FIXTURE TO "ON" POSITION. 18.MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1-FOOT CANDLE AT THE WALKING SURFACE, 2022 CBC, SECTION 1006. 19.WHERE MULTIPLE SWITCHES ARE INDICATED, SWITCHES SHALL BE GANGED UNDER A COMMON WALL PLATE. 20.LIGHTING CONTROLS DEVICES SHOWN FOR REFERENCE ONLY, COORDINATE WITH LIGHTING CONTROLS MANUFACTURER FOR EXACT EQUIPMENT AND DEVICE LAYOUT PRIOR TO ORDERING OF EQUIPMENT. PROVIDE ADDITIONAL EQUIPMENT AS NECESSARY TO ACHIEVE AN OPERATIONAL SYSTEM THAT MEETS ALL OF THE DESIGN REQUIREMENTS AND COMPLYING WITH LATEST CALIFORNIA ENERGY CODE (2022). LIGHTING CONTROL MANUFACTURER SHALL SUBMIT COMPLETE SHOP DRAWING SHOWING PREFERRED LOCATION AND QUANTITY OF SENSORS REQUIRED FOR OPTIMUM SYSTEM PERFORMANCE. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. 21. LOWER CASE LETTER INDICATES THE SWITCHING DESIGNATION. 22.DAYLIGHT PHOTOSENSOR AND DIMMING LEVEL SETTINGS SHALL BE COMMISSIONING AND ESTABLISHED IN THE FIELD AFTER FURNITURE AND FINAL FINISHES ARE INSTALLED AND ALL LIGHTING IS OPERATIONAL. 23.PHOTOSENSORS SHALL BE SELECTED SPECIFIC TO EACH SPACE, COVERAGE AREA AND BE CAPABLE OF DETECTING THE DESIGN MAINTAINED LIGHTING LEVEL IN EACH SPACE. SCALE: LIGHTING PLAN - SUITE H 11/4" = 1'-0" 1.EXIT SIGN SHALL BE FED FROM UNSWITCHED CIRCUIT AND SHALL BE PROVIDED WITH 90 MINUTE BATTERY BACK-UP. 2.LIGHT FIXTURES TO BE CONTROLLED BY A TIME CLOCK SUCH THAT IT SHUTS THE LIGHTS OFF WHEN THE SPACE IS TYPICALLY UNOCCUPIED. 3.RF FILTER PANEL FOR POWER AND LIGHTING IN THE MRI ROOM. VERIFY EXACT LOCATION IN FIELD. 4.HATCH INDICATES EMERGENCY LIGHTING FIXTURE. PROVIDE EMERGENCY BATTERY PACK MINIMUM OF 90-MINUTES AS INDICATED ON THE LIGHTING FIXTURE SCHEDULE. 5.LIGHT SWITCH FOR MRI ROOM. VERIFY EXACT LOCATION IN FIELD. 6.LIGHT SWITCH FOR CT SCAN ROOM. VERIFY EXACT LOCATION IN FIELD. 7.MANUAL ON/OFF SWITCH FOR EXTERIOR LIGHT FIXTURE. 8.LIGHT SWITCH LOCATION IS SHOWN FOR REFERENCE ONLY. VERIFY EXACT LOCATIONS IN FIELD WITH ARCHITECT/OWNER. 9.EXTERIOR LIGHT FIXTURE SHALL BE CONTROLLED VIA PHOTOCELL AND ASTRONOMICAL TIME-CLOCK. LIGHTING FIXTURE SCHEDULE LIGHTING CONTROL LEGENDSNOTES: 1.ALL FIXTURES SHALL BE COORDINATED WITH THE ARCHITECT AND WITH THE OWNER PRIOR TO PURCHASING. 2.ALL FIXTURE SHALL BE UL LISTED AND/OR ETL LISTED. 3.ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING FIXTURE LOCATIONS, MOUNTING REQUIREMENTS INCLUDING MOUNTING CLIPS, HARDWARE, ETC AS REQUIRED FOR A COMPLETE INSTALLATION AND U.L. LABELING OF THE FIXTURE PRIOR TO ORDERING. 4.VERIFY ALL LIGHTING FIXTURE CONNECTED CIRCUIT VOLTAGE PRIOR TO ORDERING. 5.ALL LIGHTS WITH "EXTERNAL" POWER SUPPLIES OR LED DRIVERS (SUCH AS TAPE LIGHTS OR LED STRIPS) SHALL ONLY BE CONNECTED TO LISTED AND CLASS 2 POWER SUPPLIES. "RECOGNIZED" COMPONENTS OR "CLASS 1" POWER SUPPLIES / LED DRIVERS ARE NOT ACCEPTABLE. COMBINATION SWITCH/ WALL OCCUPANCY SENSOR WITH TWO POLE FOR TWO ZONE CONTROL. MANUAL ON/OFF WALL SWITCH. COMBINATION DIMMER SWITCH/ WALL OCCUPANCY SENSOR. 1 ZONE CONTROL WALL DIMMER SWITCH. 2 ZONE CONTROL WALL DIMMER SWITCH CONTROLLING THE ZONES INDICATED. 4 ZONE CONTROL WALL DIMMER SWITCH CONTROLLING THE ZONES INDICATED. CEILING MOUNTED OCCUPANCY SENSOR CONTROLLING THE ZONES INDICATED. CEILING MOUNTED PHOTOCELL SENSOR WITH AUTOMATIC DAYLIGHT DIMMING CONTROLLING THE ZONES INDICATED. a* - PRIMARY SIDELIT DAYLIGHT CONTROL ZONE a** - SECONDARY SIDELIT DAYLIGHT CONTROL ZONE OS ab abcd ab a*a** OS PC D D D D S S OS TYPE MANUFACTURER MOUNTING LAMP TYPE WATTAGE VOLT MODEL DESCRIPTION F1 COOPER LIGHTING RECESSED LED 20.9 120 METALUX 22CZ-LD5-29-L940-CD1-U 2X2 RECESSED LED TROFFER, 2900 LUMENS, 4000K, 0-10V. PROVIDE 90 MINUTE BATTERY BACK UP (EL14W) FOR EM FIXTURES F2 COOPER LIGHTING RECESSED LED 14.5 120 HALO COMMERCIAL FRAME: HC6-15-D010 LED MODULE: HM6-0525-940 6" RECESSED LED DOWNLIGHT. 1500 LUMENTS, 4000K, 0-10V. PROVIDE 90 MINUTE BATTERY BACK UP (IEM14) FOR EM FIXTURES F3 KENALL SURFACE LED 14 24 MRIAUC-T-TBD-14L40K-24VDC SURFACE MOUNTED LED. 1100 LUMENTS, 4000K, 0-10V. POWER SUPPLY: MRIPSF-120, DIMMING FILTER: MRIFD-1A SERIES F4 KENALL RECESSED LED 13 24 MRIDL6-R-TBD-13L-40K9-W-RIMRI6-24V-DIM1 6" RECESSED LED DOWNLIGHT. 1300 LUMENTS, 4000K, 0-10V. POWER SUPPLY: MRIPSF-240, DIMMING FILTER: MRIFD-1A SERIES F5 COOPER LIGHTING WALL LED 20.1 120 IST-SA1-A-740-U-T4FT-GM-BPC WALL MOUNTED LED FIXTURE, BUILT IN PHOTOCELL FOR EXTERIOR FIXTURE EX LITHONIA LIGHTING CEILING LED 5 120 EDGR-W-1-R-EL OR PER BUILDING STANDARD EXIT SIGN, PROVIDE 90 MINUTE BATTERY BACK UP SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI NE ER ELECTR ICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 PA R T N E R S 800 N Tustin Ave Unit #H1/23/2025 EXISTING ELECTRICAL ROOM NEW ELECTRICAL CLOSET ENTRY (E) COLUMN TO REMAIN (E) OPENING TO BE INFILLED WITH SOLID WALL CABINET NEW PAIR 4'-0" X 8'-0" DOORS (MAGNET ACCESS) proposed new electrical transformer PROPOSED NEW CANOPY AT THE ENTRY LOCKER ACCESS DOOR RF SHIELD MAGNET ROOM SIDE MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G NE C MAGNET ROOM SIDE RF SHIELD MIN CLOSET DEPTH 30 0 m m C A B L E S T O R A G E , E I T H E R S I D E Keep out of 50G 41 52 A B 3 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGINGROOM 103 OPERATORS 104 MRI 105 EQUIPMENT 108 STORAGE 0.7 0.7 0.8 0.8 0.7 0.8 0.9 1.0 1.0 0.8 1.0 1.2 1.3 1.3 0.9 1.2 1.5 1.7 1.7 1.3 1.7 1.7 1.8 1.8 1.5 0.6 2.0 2.0 2.0 2.0 1.0 1.3 1.6 1.9 2.1 2.1 2.0 2.0 2.2 2.2 2.1 0.8 1.0 1.4 1.8 2.2 2.3 2.3 2.2 2.2 2.4 2.4 1.0 1.4 1.9 2.3 2.4 2.3 2.2 2.2 2.4 2.4 2.0 2.1 2.1 2.0 2.1 2.2 2.3 2.2 1.5 1.4 1.1 1.1 0.7 0.7 2.5 2.5 1.6 1.5 1.3 1.2 2.0 1.8 1.6 1.3 1.2 2.3 2.3 2.1 1.8 1.5 1.3 2.3 2.3 2.0 1.8 1.5 2.1 2.3 2.2 2.2 2.0 1.8 1.8 2.0 2.2 2.3 2.3 2.1 1.5 1.8 2.0 2.3 2.3 1.3 1.6 1.8 2.1 2.3 2.2 1.1 1.4 1.6 1.9 2.0 1.9 1.2 1.4 1.5 1.6 1.61.0 1.0 2.4 2.4 F1 @ 9'F1 @ 9' F1 @ 9' F1 @ 9' F1 @ 9' SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com EG R E S S P H O T O M E T R I C CA L C U L A T I O N S E7.01 SCALE: EGRESS PHOTOMETRIC PLAN - SUITE H 11/4" = 1'-0" Statistics Description Symbol Avg Max Min Max/Min Avg/Min CT SCAN 1.8 fc 2.4 fc 1.0 fc 2.4:1 1.8:1 RECEPTION 1.3 fc 2.0 fc 0.6 fc 3.3:1 2.2:1 CORRIDOR / OPERATOR 1.9 fc 2.5 fc 0.7 fc 3.6:1 2.7:1 Schedule Symbol Label QTY Manufacturer Catalog Description LLF Input Power F1 5 COOPER LIGHTING SOLUTIONS - METALUX (FORMERLY EATON) 22CZ2-34HE-RDP-UNV-L940-CD1-U 2'X2' TROFFER LED MODULE,SMOOTH LENS WITH INSERT, 90CRI 0.7 25.8 F2 0 COOPER LIGHTING SOLUTIONS - HALO COMMERCIAL (FORMERLY EATON) HC620D010-HM60525940-61MDW HALO COMMERCIAL 6" ROUND, NEW CONSTRUCTION FRAME, WITH 6" MEDIUM DISTRIBUTION, WHITE TRIM 0.7 20 SA URABH JAGD ISH PANDY AREG I STERED PROF E SS IONAL ENGI NE ER ELECTR ICALSTATE OF CALIFORNIA E-23194 EXP. 6-30- 46 PA R T N E R S 800 N Tustin Ave Unit #H1/23/2025 DUCTWORK SYMBOLS DUCT SUPPORT NOTES: MECHANICAL SHEETS LEGEND AND ABBREVIATIONS CODE SECTIONS DUCT MATERIAL SCHEDULE ²² ² ²³ ½ DUCT INSULATION SCHEDULE VERTICAL RECTANGULAR DUCT SUPPORT SCHEDULE MISCELLANEOUS EQUIPMENT SCHEDULE OUTDOOR UNITINDOOR UNIT SPLIT SYSTEM HEATPUMP UNIT SCHEDULES EXHAUST FAN SCHEDULES PIPING MATERIALS SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 11 - 1 2 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L DS/MH 1550 LE G E N D S & E Q U I P . S C H . M0.0 AJE 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 AIR CONDITIONING SPECIFICATIONS COORDINATION NOTES: GENERAL NOTES AND REQUIREMENTS SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com DS/MH 1550 ME C H S P E C S M0.1 AJE 800 N Tustin Ave Unit #H1/23/2025 (E) COLUMN TO REMAIN 3 B A 2 514 ACCESS DOOR EXISTING ELECTRICAL ROOM NEW 800 AMP E - HVAC (E ) G L B 5- 1 / 2 " X 1 8 " HASKRIS OPC15 CHILLER 1,200 LBS. (E) 22" TJI AT 48" O.C. 3 B A 2 514 Xref .\XSP.dwg MECHANICAL HVAC NOTES SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 2 7 0 5 TE N A N T I M P R O V E M E N T O R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 11 - 1 2 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L DS/MH 1550 ME C H . 1 s t F L O O R P L A N M2.0 AJE 101 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGING ROOM 103 OPERATORS 104 MRI 105 EQUIPMENT 108 STORAGE 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com DS/MH 1550 ME C H . D E T A I L S M3.0 AJE 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com DS/MH 1550 ME C H . E Q U I P . S P E C S . M3.1 AJE 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 11 - 1 2 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L DS/MH 1550 ME C H . E Q U I P . S P E C S . M3.2 AJE 1 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 11 - 1 2 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L DS/MH 1550 T- 2 4 C O M P L I A N C E F O R M S M4.0 AJE 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 11 - 1 2 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L DS/MH 1550 T- 2 4 C O M P L I A N C E F O R M S M4.1 AJE 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 11 - 1 2 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L DS/MH 1550 T- 2 4 C O M P L I A N C E F O R M S M4.2 AJE 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 PLUMBING FIXTURE SCHEDULES PLUMBING SYMBOLS LEGEND GENERAL NOTES PLUMBING SHEETS ”” ”” CODE SECTIONS 2022 BUILDING ENERGY EFFICIENCY STANDARDS: PLUMBING FIXTURE FLOW RATES [2022 CGBC Table 5.303.2.3] ² ³ PIPING MATERIALS REQUIREMENTS OF WATER-CONSERVING FIXTURES AND FITTINGS PLUMBING SYSTEM MANDATORY MEASURES (CEC) GENERAL NOTES: ELECTRIC WATER HEATER SCHEDULE SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com DS/MH 1550 PL M B G L E G E N D S & E Q U I P . P1.0 AJE 800 N Tustin Ave Unit #H1/23/2025 GENERAL NOTES: INSTALLATION NOTES: EXISTING ELECTRICAL ROOM NEW 800 AMP ENTRY (E) COLUMN TO REMAIN 3 B A 2 514 PROPOSED NEW CANOPY AT THE ENTRY ACCESS DOOR NE C SHELVES Xref .\XSP.dwg E - HVAC (E ) G L B 5- 1 / 2 " X 1 8 " HASKRIS OPC15 CHILLER 1,200 LBS. (E) 22" TJI AT 48" O.C. 32 514 Xref .\XSP.dwg SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 2 7 0 5 TE N A N T I M P R O V E M E N T O R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com 11 - 1 2 - 2 0 2 4 PL A N C H E C K R E S U B M I T T A L DS/MH 1550 PL M B G F L O O R P L A N S P2.0 AJE 101 LOBBY/RECEPTION 102 CT SCAN 106 RESTROOM 107 CHANGING ROOM 103 OPERATORS 104 MRI 105 EQUIPMENT 108 STORAGE 1 1 di g i t a l s t a m p a n d s i g n a t u r e , d a t e 1 1 - 1 3 - 2 0 2 4 800 N Tustin Ave Unit #H1/23/2025 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E de b s @ s h p a r t n e r s . n e t ma r c o h @ s h p a r t n e r s . n e t (7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S ww w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 PL A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A I N H E A L T H C A R E 00 N . T U S T I N A E N U E SA N T A A N A C A 2 7 0 5 TE N A N T I M P R E M E N T R Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H Mechanical . Electrical . Plumbing 225 E Broadway, Suite 101A Glendale, CA 91205 # 213.820.3683 Hestrada@elogicsce.com DS/MH 1550 PL U M B I N G D E T A I L S P3.0 AJE 800 N Tustin Ave Unit #H1/23/2025 800 N Tustin Ave Unit #H1/23/2025 YES NO INSTRUCTIONS: ORAN GE COUNTY FI RE AUTHORI TY Plan Submittal Criteria COMMERCIAL projects, MULTIFAMILY RESIDENTIAL projects and RESIDENTIAL TRACT developments · Fill in the project/business address and provide a brief description of the scope of work and type of business operation that will take place. · Answer questions 1 through 10, read and initial items 11 and 12, then complete and sign the certification section. · If you answer: - “YES” to any part of questions 1 through 10, submit the type of plan indicated in italics to OCFA. · In some cases, other plan types not indicated herein may also be necessary depending on specific conditions or operations. · Visit www.ocfa.org for submittal information and locations. If you need assistance in filling out this form or have questions regarding requirements for review, please contact OCFA at 714-573-6108 or visit us at 1 Fire Authority Road, Irvine, CA 92602. Address Suite City Project Scope/Business Description 1. Construction of a new building, a new story, or increase the footprint of an existing building? Changes to roadways, curbs, or drive aisles? Addition, relocation, or modification of fire hydrants or fences/gates? Construction within 300 feet of an active or proposed oil well? Fire Master Plan (PR145) 2. Property is adjacent to a wildland area or non-irrigated native vegetation? Fire Master Plan (PR145); a Fuel Modification Plan may also be required. (PR120, PR124) 3. Located in or < 100’ from a Division of Oil, Gas, and Geothermal Resources (DOGGR) field boundary, < 300’ from an oil/gas seep, or < 1000’ from a landfill? Methane Work Plan. (PR170) 4. Installation/modification/repair of underground piping, backflow preventers, or fire department connections serving private fire hydrant/sprinkler/standpipe systems? Underground Plan. (PR470, PR475) 5. Drinking/dining/recreation/meetings/training/religious functions or other gatherings in a room > 750 sq.ft. (> 1,000 sq.ft. for training/adulteducation) or > 49 people? Healthcare/outpatient services for > 5 people who may be unable to immediately evacuate without assistance? Education for children (academic tutoring for ages 5+ is exempt unless classified as an E occupancy by the Building Official)? Adult/child daycare? 24-hour care/supervision? Incarceration or restraint? Hotel/apartment or residential facility with 3+ units and 3+ stories (3-story townhouses/rowhouses where an independent direct exit to grade is provided for dwelling are exempt)? Congregate housing/dormitories with 17+ people? High-rise structure (55+ feet to highest occupied floor level)? Architectural Plan (PR200-PR285) 6. Installation/modification of locks delaying or preventing occupants from leaving a space or requiring use of a card, button, or similar action to open a door in the direction of exit travel? Architectural, Sprinkler, and/or Alarm Plan depending on the occupancy and type of device installed (PR200-PR280, PR420-PR425, PR500-PR520) 7. Installation/modification/use of spray booths; dust collection; dry cleaning; industrial ovens/drying equipment; industrial/commercial refrigeration systems; compressed gasses; tanks for cryogenic or flammable/combustible liquids; vapor recovery; smoke control; battery back-up/charging systems (> 50 gal. electrolyte, > 1,000 lb. lithium ion); welding/brazing/soldering, open flame torches, cutting/grinding; or other similar operations? Special Equipment Plan (PR315, PR340-PR382) 8. Storage/use/research with flammable/combustible liquids or other chemicals? Motor vehicle/aircraft maintenance/repair? Cabinetry/woodworking/finishing facility? Chem Class & floor plan (full architectural plan if H occupancy); Special Equipment Plans may be necessary. (PR315-PR360, PR232-PR240) 9. Storage or merchandizing areas in excess of 500 sq. ft. where items are located higher than 12’ (6’ for high-hazard commodities, plastic, rubber, foam, etc.)? High-piled Storage Plan (PR330) 10. Cooking under a Type I commercial hood; installation or modification of a fire extinguishing system located in a commercial cooking hood? Hood & Duct Extinguishing System, not just the hood mechanical plan. (PR335) Initial each of the following two items indicating that you have read and understand the statement: 11. *Sprinklers/Alarms: Consult Building/Fire Codes and ordinances to determine sprinkler/alarm requirements; if a system is required, plans shall be submitted for OCFA review. Existing buildings undergoing remodel must be evaluated by a licensed Initials contractor to determine if modification is needed; if so, contractor shall submit plans prior to making modifications. 12. Fire Hazard Severity Zone: Consult maps available at building department or on OCFA website to determine if your site is located in a FHSZ. Buildings in a FHSZ may be subject to special construction requirements detailed in CBC Chapter 7A or CRC R327— Initials the building department will determine specific requirements. I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name Signature Phone Number ( ) Date / / Building Department: If you have verified that all of the questions have been answered accurately as “NO”, and the project does not otherwise require OCFA review of sprinkler or alarm plans*, then you may accept this signed form as a written release that OCFA review is not required. Should you still require that the applicant have plans approved by OCFA, please initial here or attach an OCFA referral form and have the applicant submit the form along with the appropriate plans and fees for OCFA review. 10-08-14 EE COM 800 N Tustin Ave Unit #H1/23/2025 O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Referral Form Required for OCFA to review plans upon the request of the Building Department when the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”. City / County Official Requesting Review: City / County Reference #: Date: __________________________________ City / County: _____________________________________ E-Mail: __________________________________ Contact Name: _____________________________________ Phone #: _________________________________ Title: _____________________________________ ** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. ** Reason(s) for Review: Please describe why OCFA Plan Review is or may be required by the City/County : OCFA COMMENTS:  No further action required on this specific plan type, based on information provided on: ____/______/______.  Project to be taken in for OCFA Review. Other: Name: _________________________________________ Contact #: ______________________________________ Date: _________________________________ OCFA Authorization Updated: 06/02/2020 rs 800 N Tustin Ave Unit #H1/23/2025 PLUMBING M0.0 M0.1 M3.0 M3.1 ELECTRICAL MECHANICAL MECHANICAL EQUIPMENT SPECIFICATIONS MECHANICAL DETAILS LEGEND & EQUIPMENT SCHEDULES A2.1 FLOOR PLAN A6.1 A4.1 WALL DETAILS ARCHITECTURAL A1.1 G.1 GENERAL NOTES ACCESSIBILITY DETAILS TITLE SHEET VICINITY MAP ABBREVIATIONS PROJECT DATA SHEET INDEX TI T L E S H E E T G.1 MH G.3 G.4 G.2 DETAIL SECTION REFERENCE FIRE EXTINGUISHER CABINET EXTINGUISHER W/ FIRE EXTINGUISHER WALL-MOUNTED FIRE KEYNOTE INDICATOR DELTA NUMBER REVISION CLOUD & X FE FEC ELEVATION REFERENCE SHEET NUMBER ELEVATION VIEW ELEVATION REFERENCE SHEET NUMBER 1 2 3 4 X XXX X XXX SYMBOLS LEGEND ALIGN ROOM NAME ROOM NUMBER101 OFFICE DETAIL REFERENCEXX XXX SECTION REFERENCE SHEET NUMBER SHEET NUMBER SHEET NUMBER XX XXX NEW DOOR EXISTING DOOR ###DOOR NUMBER (REFER TO DOOR SCHEDULE) NO SCALE N TYPE NUMBER WALL MATERIAL TYPE TYPE NUMBER FLOOR MATERIAL TYPE XX XXX Quarry TileQ.T. West With Water Closet Wood Without Waterproof Wainscot Weight Vertical Vestibule Unfinished Unless Otherwise Noted Urinal Tread Towel Bar Top of Curb Telephone Terrazzo Tongue and Groove Thick Top of Concrete Top of Panel Top of Reveal Top of Deep Recess Top of Mullion Top of Wall Top of Pavement Toilet Paper Dispenser Television Top of Wall Typical W. W/ W.C. WD. W/O WP WSCT. WT. VERT. VEST. UNF. U.O.N. UR. TRD. T.B. T.C. TEL. TER. T. & G. THK. T.O.C. T.O.P. T.O.R. T.O.RC. T.O.M. T.O.W. T.P. T.P.D. T.V. T.W. TYP. South Solid Core Seat Cover Dispenser Schedule Soap Dispenser Section Shelf Shower Sheet Similar Sanitary Napkin Disp. Sanitary Napkin Recept. Specification Square Stainless Steel Service Sink Station Standard Steel Storage Structural Suspended Symmetrical S. S.C. S.C.D. SCHED. S.D. SECT. SH. SHR. SHT. SIM. S.N.D. S.N.R. SPEC. SQ. S.ST. S.SK. STA. STD. STL. STOR. STRL. SUSP. SYS. Riser Radius Roof Drain Reference Refrigerator Register Reinforced Required Resilient Room Rough Opening Redwood Rain Water Leader R. RAD. R.D. REF. REFR. RGTR. REINF. REQ. RESIL. RM. R.O. RWD. R.W.L. Pre-cast Plate Plastic Laminate Plaster Plywood Pair Point Paper Towel Dispenser Combination Paper Towel Partition Paper Towel Receptacle Panel Joint PRCST. PL. P.LAM. PLAS. PLYWD. PR. PT. P.T.D P.T.D/R PTN. P.T.R. P.J. Overall Obscure On Center Outside Diameter (Dim.) Office Opening Opposite O.A. OBS. O.C. O.D. OFF. OPNG. OPP. North Not In Contract Number Nominal Not To Scale N. N.I.C. NO. NOM. N.T.S. Maximum Medicine Mechanical Membrane Metal Manufacturer Manhole Minimum Mirror Miscellaneous Masonry Opening Mounted Mullion MAX. M.C. MECH. MEMB. MET. MFR. MH. MIN. MIR. MISC. M.O. MTD. MUL. Laboratory Laminate Lavatory Locker Light LAB. LAM. LAV. LKR. LT. Janitor Joint Kitchen Knock Out Jan. JT. KIT. K.O. Inside Diameter (Dim.) Insulation Interior I.D. INSUL. INT. Hose Bibb Hollow Core Hardwood Hardware Hollow Metal Horizontal Hour Height H.B. H.C. HDWD. HDWE. H.M. HORIZ. HR. HGT. Gauge Galvanized Grab Bar Glass Ground Grade Gypsum GA. GALV. G.B. GL. GND. GR. GYP. Fire Alarm Flat Bar Floor Drain Foundation Fire Extinguisher Fire Extinguisher Cab Fire Hose Cabinet Finish Floor Flashing Fluorescent Face of Concrete Face of Finish Face of Mullion Face of Stud Fireproof Full Size Foot or Feet Footing Furring Future F.A. F.B. F.D. FDN. F.E. F.E.C. F.H.C. FIN. FL. FLASH. FLUOR. F.O.C. F.O.F. F.O.M. F.O.S. FPRF. F.S. FT. FTG. FURR. FUT. East Each Expansion Joint Elevation Electrical Elevator Emergency Enclosure Electrical Panelboard Equal Equipment Electric Water Cooler Existing Exposed Expansion Exterior E. EA. E.J. EL. ELEC. ELEV. EMER. ENCL. E.P. EQ. EQPT. E.W.C. EXST. EXPO. EXP. EXT. Double Department Drinking Fountain Detail Diameter Dimension Dispenser Down Door Opening Door Drawer Downspout Dry Standpipe Drawing DBL. DEPT. D.F. DET. DIA. DIM. DISP. DN. D.O. DR. DWR. DS. D.S.P. DWG Cabinet Catch Basin Cement Ceramic Cast Iron Corner Guard Ceiling Caulking Closet Clear Cased Opening Column Center of Mullion Concrete Connection Construction Continuous Center of Reveal Corridor Countersunk Counter Center CAB. C.B. CEM. CER. C.I. C.G. CLG. CLKG. CLO. CLR. C.O. COL. C.O.M. CONC. CONN. CONSTR. CONT. C.O.R. CORR. CTSK. CNTR. CTR. Board Bituminous Building Block Blocking Beam Bottom of Concrete Bottom of Mullion Bottom of Panel Bottom of Reveal Bottom BD. BITUM. BLDG. BLK. BLKG. BM. B.O.C. B.O.M. B.O.P. B.O.R. BOT. Acoustical Area Drain Adjustable Aggregate Aluminum Approximate Architectural Asbestos Asphalt ACOUS A.D. ADJ. AGGR. AL. APPROX. ARCH. ASB. ASPH. And At Angle ~ # LC & @ (E) Pound or Number Diameter or Round Existing Centerline P 1 C 1 PL 1 X EQUIPMENT TAG TYPE NUMBER MISC. MATERIAL TYPE PROJECT TEAM PROJECT SCOPE: TENANT OCCUPANCY: EXISTING OCCUPANCY: BUILDING CODES: TENANT- LESSEE UNITED MEDICAL IMAGING OF SANTA ANA 800 N. TUSTIN AVE., SUITE M SANTA ANA, CA 92705 CONTACT: NASSER HIEKALI PHONE: (818) 632-7778 EMAIL: NHIEKALI@UMIH.COM GENERAL CONTRACTOR TBD M MEDICAL OFFICE P1.0 P2.0 PLUMBING DETAILS PLUMBING FLOOR PLANS E0.01 GENERAL NOTES, SHEET INDEX AND SYMBOLS LIST DS/MH 23-16 ACCESSIBILITY DETAILS A6.2 RCP DETAILS EXTERIOR ELEVATIONS LANDLORD A6.3 MILLWORK DETAILS DOOR/WINDOW SCHEDULES PROPOSED OCCUPANCY: B BUSINESS GROUP (MEDICAL OFFICE) A7.1 SITE PLAN 18 SHEETS 9 SHEETS 3 SHEETS 11 SHEETS OCCUPANT LOAD: TABLE 1006.2.1 - MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE 100 FEET NO POINT OF TRAVEL DISTANCE EXCEEDS 100 FEET REQUIREMENT BUSINESS AREA - TABLE 1004.5 TOTAL OCCUPANT 9 OCCUPANTS < THAN 49 EXIT REQUIRED : 1 EXIT PROVIDED : 1 USE SF (NET) OCC. LOAD OCCS. 1,294 SF 150 9 SHEET PA / PM: JOB NO.: DRAWN BY: CAUTION: 24"x36" RE M A R K S DA T E d e b s @ s h p a r t n e r s . n e t m a r c o h @ s h p a r t n e r s . n e t ( 7 1 4 ) 3 9 0 . 8 6 0 0 ar c h i t e c t u r e a n d p l a n n i n g PA R T N E R S w w w . s h p a r t n e r s . n e t 07 - 0 3 - 2 0 2 4 P L A N C H E C K S U B M I T T A L UN I T E D M E D I C A L I M A G I N G H E A L T H C A R E 80 0 N . T U S T I N A V E N U E , SA N T A A N A , C A 9 2 7 0 5 TE N A N T I M P R O V E M E N T F O R : Un i t e d M e d i c a l I m a g i n g H e a l t h c a r e SU I T E - H 10 - 2 8 - 2 0 2 4 P L A N C H E C K R E S U B M I T T A L P3.0 A2.0 DEMOLITION PLAN TYPE OF PROCEDURES: THERE ARE NO SURGICAL, SEDATED OR ANY OSHPD 3 REQUIREMENTS. M2.0 MECHANICAL 1ST FLOOR PLAN A2.2 REFLECTED CEILING PLAN BUILDING DEPARTMENT: CITY OF SANTA ANA 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA PLUMBING CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA GREEN BUILDING CODE 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA FIRE CODE MECHANICAL SPECIFICATIONS PLUMBING LEGENDS & EQUIPMENT A.P.N. NUMBER:400-202-03 TYPE OF CONSTRUCTION: V-B (EXISTING) NON-SPRINKLERED NO. OF STORIES: ONE STORY SLAB ON GRADE TOTAL SQUARE FOOTAGE: EXISTING FLOOR AREA 1,245 SF PROPOSED ADDITION 49 SF TOTAL FLOOR AREA 1,294 SF UMIH PLUMBING FIXTURE CALCULATIONS: TABLE 422.1 USE OFFICE 1,294 SF 200 7 OCCUPANTSOCC. LOAD TOTAL PLUMBING FIXTURES REQUIRED: PER UPC SECTIION 422.2 EXCEPTION 3 TOTAL OCCUPANT LOAD OF LESS THAN 50 - ONE UNISEX TOILET ROOM REQUIRED TOTAL PLUMBING FIXTURES PROVIDED: ONE UNISEX TOILET ROOM FLOOR AREA 1 UNITED MEDICAL IMAGING HEALTHCARE 800 N. TUSTIN AVENUE SANTA ANA, CA 92705 TENANT IMPROVEMENT FOR: United Medical Imaging Healthcare S & A MANAGEMENT LLC 129 WEST WILSON SUITE 100 COSTA MESA, CALIFORNIA 92627 CONTACT: RYAN CHASE PHONE: (949) 722-7400 EMAIL: RYANLYLECHASE@GMAIL.COM ELECTRICAL ENGINEER PLUMBING ENGINEER ARCHITECT CONSULTANTS SH PARTNERS, INC 7052 EVENINGSONG DRIVE HUNTINGTON BEACH, CA 92648 ARCHITECT: DEBRA L SANDS, AIA PHONE: (714) 553-2849 EMAIL: DEBS@SHPARTNERS.NET CONTACT: MARCO HANAWI PHONE: (714) 390-8600 EMAIL: MARCOH@SHPARTNERS.NET ENERGYLOGICS, INC. 225 E BROADWAY SUITE 101A, GLENDALE CA 91205 ENERGYLOGICS, INC. 225 E BROADWAY SUITE 101A, GLENDALE CA 91205 MECHANICAL ENGINEER ENERGYLOGICS, INC. 225 E BROADWAY SUITE 101A, GLENDALE CA 91205 CONTACT: HENRY ESTRADA PH: (213) 820-3683 EMAIL: HESTRADA@ELOGICSCE.COM CONTACT: HENRY ESTRADA PH: (213) 820-3683 EMAIL: HESTRADA@ELOGICSCE.COM CONTACT: SAURABH PANDYA PH: (562) 541-4729 EMAIL: ZONING:P - PROFESSIONAL EXIT REQ'D EXIT PROVIDED 1 SUITE - H A2.3 FINISH FLOOR PLAN STRUCTURAL 7 SHEETS 1 A6.4 MISCELLANEOUS DETAILS S-1.0 FOUNDATION PLAN S-1.1 ROOF FRAMING PLAN S-2.0 FOUNDATION DETAILS M3.2 MECHANICAL EQUIPMENT SPECIFICATIONS E0.02 TITLE 24 INDOORE0.03 ELECTRICAL SPECIFICATIONS E2.01 SINGLE LINE DIAGRAM E3.01 PANEL SCHEDULES E6.01 LIGHTING PLAN E5.01 POWER PLAN E7.01 EGRESS PHOTOMETRIC CALCULATIONS M4.0 T-24 COMPLIANCE FORMS M4.1 T-24 COMPLIANCE FORMS S-3.0 ROOF FRAMING DETAILS CONTACT: JEFF BEDDOW PHONE: (949) 722-7400 EMAIL: JEFF.SAPROPERTIES@GMAIL.COM SPANDYA@ELOGICSCE.COM SA N T A A N A FW Y CO S T A ME SA F W Y 17TH STREET E. FRUIT STREET 4TH STREET N. T U S T I N A V E . CA B R I L L O P A R K D R . E. 1ST STREET W. 1ST STREET 5 PROJECT LOCATION 55 A1.2 LINE OF SIGHT A3.1 ROOF PLAN A5.1 INTERIOR ELEVATIONS S-4.0 DETAILS TITLE 24 OUTDOORE0.04 E5.02 MECHANICAL POWER PLAN E5.03 ROOF POWER PLAN S-0 GENERAL NOTES S-0.1 GENERAL NOTES INTERIOR TI TO CREATE NEW IMAGING AND LOBBY ROOMS FOR A NEW PROPOSED MEDICAL OFFICE, NEW ROOF EQUIPMENT W/ SCREENING, NEW EXTERIOR NON-BEARING WALLS, NEW CANVAS CANOPY OVER TWO SEPARATE DOORS, AND A 49 SQ. FT. ADDITION PLAN CHECK NO: 101120961 - BUILDING DEPARTMENT 20184073 - ELECTRICAL 30147809 - PLUMBING 40139552 - MECHANICAL 1 1 1 1 1 1 1 1 1 1 M4.2 T-24 COMPLIANCE FORMS 1 1 1 1 1 E4.01 ELECTRICAL SITE PLAN 1 1 1 1 1 - DELETED 1 1 1 1 1 2 st r u c t u r a l r e v i s i o n s 02 - 1 1 - 2 0 2 5 2 2 Revision to 101123214 (issued on 1/23/25) APPROVALS: BLDG- CSG 800 N Tustin Ave Unit #H5/1/2025 3 B A 2 5142.2 S-1.1 RO O F F R A M I N G P L A N XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 R-1 10-28-2024 R-2 02-11-2025 800 N Tustin Ave Unit #H5/1/2025 1 2 DO NOT cut or notch flange. DO NOT cut holes in cantilever reinforcement. 13"11"87 8"61 2"3" 4"2"13"11"87 8"61 2"3"4" ROUND HOLE SIZE 2" TJIDEPTH 360 360 117 8" 117 8" Table A - End Support Minimum distance from edge of hole to inside face of nearest end support Table B - Intermediate or Cantilever Support SQUARE OR RECTANGULAR HOLE SIZE Minimum distance from edge of hole to inside face of nearest intermediate or cantilever support Rectangular holes based on measurement of longest side. S-3.0 RO O F F R A M I N G DE T A I L S XXX1:XXXXXXXXXXAAABBB Project Name Rev.Desciption Date Drawing Title Project ID D A T E Drawing No. 35-24 80 0 N T U S T I N S T . , SA N T A A N A , C A 9 2 7 0 5 UM I H S A N T A A N A R-0 07-01-2024 R-1 10-28-2024 R-2 02-11-2025 800 N Tustin Ave Unit #H5/1/2025 www.fastructural.com Email : atefg@fastructural.com T: +1 714.519.5027 STRUCTURAL ENGINEERING AND CONSULTING 800 N Tustin St., Santa Ana, CA 92705 Projecct # 35-24 STRUCTURAL CALCULATIONS Date Rev. R2 # Pages 31 2/11/2025 800 N Tustin Ave Unit #H5/1/2025 CALCULATION INDEX PART / TITLE Page 1. Gravity Criteria 1 2. Building Weight 2 3. Wind Analysis 3 4. Seismic Analysis Site Latitude & Longitude 4 Spectral Response Coefficients 5 Seismic Analysis 2012 IBC 6 AN Lateral Force Distribution 7 6. Wood Shearwall Design Shearwall Design Tables 9 Shearwall Description 10 Shearwall Design 11 7. Beam Design Beam Design Tables 12 Simply Supported Beam Design 13 Cantilever Beam Design (EnerCalc) 17 8. Column Design Column Loads Wood Column Design 31 35-24 UMIH Suite H_SANTA ANA_R0.xls, Calculation Index 800 N Tustin Ave Unit #H5/1/2025 GRAVITY LOADS 2.00 psf 2.25 psf 4.20 psf 1.50 psf 9.95 psf 10.00 psf 3.00 psf 2.25 psf 3.15 psf 3.00 psf 1.60 psf 13.00 psf 100.00 psf 2.10 psf 3.00 psf 3.00 psf 8.00 psf 20.00 psf 10.00 psf 2.81 psf 1.58 psf 0.50 psf 3.00 psf 18.00 psf 3.00 psf 1.05 psf 2.81 psf 3.00 psf 10.00 psf Insulation Fiber Glass Rigid Wall Wood Studs 2x6 @ 16" O.C. DF-Larch EXTERIOR WALL INTERIOR WALL Drywall Finish INTERIOR WALL LOAD Drywall Finish Sheathing 15/32" Plywood Wall Wood Studs 2x4 @ 16" O.C. DF-Larch Insulation Fiber Glass Loose EXTERIOR WALL LOAD Framing 2x12 @ 12" O.C. DF-Larch Sheathing 3/4" T&G ROOF LIVE LOAD TOTAL ROOF DEAD LOAD TOTAL OPEN DECK DEAD LOAD DEAD LOAD ROOF LOADS Roofing Shingles Asphalt (1/4 in) DECK DEAD LOAD TOTAL Sheathing 3/4" T&G Flooring Hardwood (1 in) CEILING DEAD LOAD TOTAL Miscellaneous Framing 2x 8 @ 16" O.C. DF-Larch CEILING LIVE LOAD TOTAL Drywall Finish CEILING LOADS Wall Plaster (1 in) on Metal Lath DEAD LOAD Sheathing 15/32" Plywood Drywall Finish Framing 2x12 @ 16" O.C. DF-Larch Drywall Finish DECK LIVE LOAD TOTAL Miscellaneous 35-24 UMIH Suite H_SANTA ANA_R0.xls, Gravity Loads Page 1 800 N Tustin Ave Unit #H5/1/2025 BUILDING WEIGHT DESIGN CRITERIA Code Used : 2022 CBC Concrete F'c : 2,500 psi Building Code : 2021 IBC Steel Fy : 60,000 psi LACity Requirement : Yes v SOILS REPORT NO SOILS REPORT Bearing Capacity : 1,500 psf SEISMIC DESIGN PARAMETERS Short Period, Fa :1.2 0.2 sec Fig 1613.5(1) Latitude : 33.752258 Long Period, Fv :1.5 1.0 sec Fig 1613.5(2) Longitude :-117.834959 Response Spectral : 129.40% 0.2 sec Fig 1613.5(3) Site Class : D Response Spectral : 46.10% 1.0 sec Fig 1613.5(4) BUILDING SUMMARY Level Height Elevation Unit Weight psf Wall Weight ft Dead Live Type psf ROOF 15.00 15.00 9.95 10.00 Exterior 18.00 Interior 10.00 BUILDING WEIGHT ROOF Area Type L (ft) W (ft) H (ft) Area (ft^2) Dead Load (psf) Weight (kips) Roof 6,510.8 9.95 64.78 Ext. Wall 62.00 24.00 7.50 18.00 11.61 Int. Wall 124.00 48.00 7.50 10.00 12.90 TOTAL ROOF AREA / LOAD 6,510.8 89.29 35-24 UMIH Suite H_SANTA ANA_R0.xls, Building Weight Page 2 800 N Tustin Ave Unit #H5/1/2025 27.5 Directional Procedure, Part 2: Enclosed Simple Diaphragm Buildings With H ≤ 160 Ft T-27.6-2 (psf) X oof Exp adjust factor T-27.6-2 = 1 0.00 Ph =21.80 Ph = 25.20 P0 =21.80 P0 =25.20 62 24 Example will work for V =110, 115 and 120 MPH only. Wind Normal to Ridge Wind Parallel to Ridge Roof Height h =15 feet Exposure C Roof Pitch =0.00 :12 Topography factor Kzt =1.00 26.8.2, Figure 26.8-1 Building & Structure Risk Category = IBC T-1604.5 Wind Speed V = 110 mph Fig. 26.5-1A, MRI = 700 yrs Wind Normal to Ridge, L/B = 2.583 use 2.0 Wind Parallel to Ridge, L/B = 0.39 use 0.5 Since .2 ≤ L/B ≤ 5.0 = Yes Since .2 ≤ L/B ≤ 5.0 = Yes and h ≤ 60 = Yes and h ≤ 60 = Yes Building meet Class I condition ? Yes Building meet Class I condition ? Yes  Since .5 ≤ L/B ≤ 2.0 = No Since .5 ≤ L/B ≤ 2.0 = No and 60 ≤h ≤1 60 = No and 60 ≤h ≤1 60 = No Fundamental period =0.500 sec Fundamental period =0.500 sec More than h/75 sec. NG More than h/75 sec. NG Building meet Class II condition ? No Building meet Class II condition ? No From T-27.6-1, V = 110 MPH Exp C, L/B =2.0 and 15 FT. HT From T-27.6-1, V = 110 MPH Exp C, L/B =0.5 and 15 FT. HT Ph =21.80 Kzt Ph =25.20 Kzt Po =21.80 Kzt Po =25.20 Kzt T-27.6-2 V =110 Exp C, h =15 Roof slope =0:12 Zone 1 =-23.5 Adjust factor T-27.6-2, = 1.00 Design roof pressure for zone 1 = -23.50 PSF Wind Base Shear = 7.85 kips Wind Base Shear = 23.44 kips II, standard == 35-24 UMIH Suite H_SANTA ANA_R0.xls, Wind Analysis MWFR<160ft Page 3 800 N Tustin Ave Unit #H5/1/2025                                    !"##$      %&'()*+,-.(/'01.,6778 9 : :;#!7<:=5 ??!<##<6:"@@!6?A;<;@<< #7#A"7G"#G@!H77H?#<!<I5  M.)P/&,05  !"@G(L5 SST"  &(4X'CP& O&4)(1F01.,@#;A Y Z[ M  \  ]7#^7AG@ Y Z[ M  \  ]@7^@<<?  "M        9  _  "M        9  @7?< 8M  M [9   7#_ 8M  M [9   @7@@A6-.(/'01.,X'CP& O&4)(1F01.,_  M [ [ @#  M     7#_  M     @77;?<      \7#^7;#6      \@7^7<A@ Y a [    @#  M     a7G<  M   [    6  ["       \^@#;A     "  [ [ M  \7#^@?6A $  M"       \#b     c  <7  ^@< $  M    9  \7#^7AG@     "  [ [ M  \@7^7A;! $  M"       \#b     c  <7  ^7G $  M    9  \@7^7<A< $  M    9  \a^@@A6 ‚ƒƒ„…†‡ˆ‰‡Š‡‹Œ ŒŽ ‘’“”•–— •˜“ˆ ™Š‡š‡ˆ“™™ ™ Page 4 800 N Tustin Ave Unit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age 5 800 N Tustin Ave Unit #H5/1/2025 IBC2021 (1613), ASCE 7-16 CHAPTER 11, 12, 13 SEISMIC DESIGN CRITERIA Response Spectral Acc. (0.2 sec) Ss =1.294 g Figure 22-1,22-3,22-5,22-6 Response Spectral Acc.( 1.0 sec) S1 =0.461 g Figure 22-2,22-4,22-5,22-6 Soil Site Class Table 20-3-1, Default = D Site Coefficient Fa = 1.200 Table 11.4-1 Site Coefficient Fv =1.540 Table 11.4-2 Max Considered Earthquake Acc. SMS =Fa.Ss = 1.553g (11.4-1) Max Considered Earthquake Acc. SM1 =Fv.S1 = 0.710g (11.4-2) @ 5% Damped Design SDS =2/3(SMS)= 1.035g (11.4-3) SD1 =2/3(SM1)= 0.473g (11.4-4) Building Risk Categories Table 1604.5 Design Category Consideration:with dist. between seismic resisting system >40ft Seismic Design Category for 0.1sec D Table 11.6-1 Seismic Design Category for 1.0sec D Table 11.6-2 S1 < .75g NA Section 11.6 Since Ta < .8Ts (see below), SDC = D Control (exception of Section 11.6 does not apply) IBC, Seismic Design Category D IRC, Seismic Design Category = D2 12.8 Equivalent lateral force procedure Seismic Force Resisting Systems Ct = 0.02 x =0.75 T-12.8-2 Building ht. Hn =35 ft ited Building Height (ft) =65 Cu = 1.400 for SD1 of 0.473g Table 12.8-1 Approx Fundamental period, Ta = Ct(hn)x = 0.288 12.8-7 TL =6.000 Sec Calculated T shall not exceed ≤Cu.Ta = 0.403 Use T =0.403 sec. 0.8Ts = 0.8(SD1/SDS)= 0.366 Is structure Regular & ≤ 5 stories ? 12.8.1.3 Response Spectral Acc.( 0.2 sec) Ss =1.294g Fa = 1.20 @ 5% Damped Design SDS =⅔(Fa.Ss)= 1.035g (11.4-3) Response Modification Coef. R =6.5 Table-12.2-1 Over Strength Factor 2.5 foot note g Importance factor I =1 T 1.5-2 Seismic Base Shear V =C s W SDS (12.8-2) R/I SD1 (12.8-3) (R/I).T SD1TL (12.8-4) T2(R/I) Cs shall not be less than =0.044SDS.I≥.01 = 0.046 (12.8-5) Min Cs =0.5S1I/R N/A For S1 ≥ 0.6g (12.8-6) Use Cs =0.159 Design base shear V =0.159 W Control 12.14 Simplified Seismic base shear @ 5% Damped Design SDS =1.035 SDC = D Limitations:P F =1.2 R = 6.5 V =FSDS(W)= 0.191 W (12.14-11) R A. BEARING WALL SYSTEMS < Ta Cs ==0.159 or need not to exceed, Cs == 0.181 For T≤ TL or Cs =N/A For T > TL For three story building T-12.1 T-12.2 T-R301.2.2.1.1 35-24 UMIH Suite H_SANTA ANA_R0.xls, Seismic Analysis-2021 IBC Page 6 800 N Tustin Ave Unit #H5/1/2025 LATERAL FORCE DISTRIBUTION SEISMIC BASE SHEAR Importance Factor, I ASCE7-16 Table 11.5-1 I = 1.00 EQ Acc. @ 5% Damped Design ASCE7-16 EQ 11.4-3 SDS = 1.04 Vult = 2021 IBC SHEET = 0.159 W Vwork = Vult / 1.4 = 0.114 W Working Stress Level Vwork = 0.114 * 89.3 kips = 10.2 kips Seismic Base Shear p = 1.30 ==> Vwork = 13.2 kips Seismic Base Shear WIND BASE SHEAR Vult = MWFR < 160 ft = 23.4 kips Vwork = Vult * 0.6 = 14.1 kips WIND BASE SHEAR GOVERNS DESIGN BASE SHEAR =14.1 kips BASE SHEAR VERTICAL DISTRIBUTION Floor Height Floor Weight wx*hx Fx % Fx Story V Fx Type hx Area wx wx*hx (V-Ft)Fx%Ft+Fi Fl Area ft ft^2 kips kips-ft (wx*hx)kips kips psf ROOF 15.00 6,511 89.29 1,339 100.0% 14.06 14.06 2.16 Total 89.29 1,339 100.0% 14.06 DIAPHRAGM FORCE DISTRIBUTION Floor Story V Fpx Min Max Fpx Type wpx wi Ft+Fi V*wpx/w Fpx1 Fpx2 Design kips kips kips kips kips kips kips ROOF 83.49 83.49 14.06 14.06 17.29 34.57 17.29 1 Fpx min = 0.2*SDs*I*wpx (for Flexible Diaphragm)ASCE7-16 12.10.1.1 2 Fpx max = 0.4*SDs*I*wpx (for Flexible Diaphragm)ASCE7-16 12.10.1.1 SHEARWALL DESIGN FORCES Level Fl. Area Wall Ht. Stry Shear Base2 Shear ft2 ft kips Shear % psf ROOF 6,511 15.00 14.06 100.0% 2.16 1 Redundancy Factor Used Per ASCE7-16 12.3.4.2 Weight 35-24 UMIH Suite H_SANTA ANA_R0.xls, Lateral Force Distribution Page 7 800 N Tustin Ave Unit #H5/1/2025 TABLES REFERENCED IN SHEARWALL DESIGN SPREADSHEET Table 2306.4.1 Allowable Shear (plf) for Wood Shearwall Panels For Wind or Seismic Loadin (plf)(plf) 1 1 15/32" 10d @6'' @16'' 3/8'' dia Lag Screw @32''OC 5/8'' dia A.B. @48''OC 340 255 2 1 15/32" 10d @4'' @8'' 3/8'' dia Lag Screw @16''OC 5/8'' dia A.B. @32''OC 510 380 3 1 15/32" 10d @3'' @12'' 3/8'' dia Lag Screw @12''OC 5/8'' dia A.B. @24''OC 665 500 4 1 15/32" 10d @2'' @8'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @16''OC 870 650 5 2 15/32" 10d @4'' @8'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @16''OC 1,020 765 6 2 15/32" 10d @3'' @4'' 3/8'' dia Lag Screw @9''OC 5/8'' dia A.B. @12''OC 1,370 1,030 7 2 15/32" 10 @2'' @4''3/8'' dia Lag Screw @4''O 5/8'' dia A.B. @16''OC 1,740 1,305 NOTES: 1. 2. 5. NAILS SHALL BE PLACED NOT LESS THAN 1/2" INCH FROM PANEL EDGES. 8. 9. 10. V_allow (100%) A35/LTP 4 Simpson Sill Plate @ Framed Floor Anchor @ Foundation V_allow (75%)Mark # sides Sheathing Edge Nailing 4. WHERE PLYWOOD APPLIES ON BOTH FACES OF A WALL AND NAIL SPACING IS LESS THAN 6" INCHES ON CENTER ON EITHER SIDE. PANEL JOINTS SHALL HAVE MIN 3x (VERTICAL STUDS & BLOCKING) AND NAILS SHALL BE STAGGERED. OFFSET PANEL JOINTS TO FALL ON DIFFERENT FRAMING MEMBER WHERE PLYWOOD IS PLACED AT BOTH FACES. 6. FOR HOLD-DOWNS AT THE END OF THE SHEAR WALL, SEE PLANS AND SCHEDULE. PROVIDE 3"x3"x1/4" WASHER PLATE AT ALL SILL PLATE ANCHOR BOLTS AND AT ALL HOLD-DOWN BOLTS CONNECTED TO VERTICAL POSTS. ALL SHEATHING TO BE DOUGLAS FIR-LARCH STRUCT. I. ALL FIELD NAILING TO INTERMEDIATE FRAMING TO BE AT 12" O.C. 3. FRAMING AT ADJOINING PANEL EDGES SHALL BE 3" (INCH) NOMINAL OR THICKER (i.e. MIN 3x VERTICAL STUDS AND BLOCKING) NAILS SHALL BE STAGGERED IN TWO LINES ALONG PANEL EDGES WHERE NAILS ARE SPACED 2" INCHES ON CENTER OR WHEN 10d COMMON NAILS SPACED 3" O.C. PENETRATE FRAMING MORE THAN 1 5/8". SIMPSON SDS 3/8"x7" WOOD SCREWS. TYP. USE |2"x4|4" SDS INTO NAILER AT STEEL BEAMS. 11. WHERE 2-2x SILL PLATES ARE USED, SCREW LOWER PLATE TO FRAMING BELOW. DRILL HOLE IN UPPER SILL PLATE FOR SCREW HEAD SO THAT UPPER PLATE SITS FLAT ON LOW SILL PLATE. 7. USE WELDED STUD BOLTS OF SAME SIZE & SPACING AS OF SILL PLATE ANCHOR BOLTS, WHERE STEEL BEAM OCCURS UNDER SHEAR WALL. PROVIDE DOUBLE PARALLAM BLOCKING TO ACCOMODATE 2 ROWS OF SIMPSON SDS SCREWS. FOUNDATION SILL PLATE SHALL BE 3x. U.N.O. 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in SW Design Page 8 800 N Tustin Ave Unit #H5/1/2025 TABLES REFERENCED IN SHEARWALL DESIGN SPREADSHEET (HOLDOWN) HD Post Type 75% Full Used Size HDU2 2,306 3,075 2,306 4x4 HDU4 3,424 4,565 3,424 4x4 HDU5 4,253 5,670 4,253 4x4 HDU8 5,903 7,870 5,903 4x6 HDU11 7,151 9,535 7,151 4x6 HDU14 10,793 14,390 10,793 4x8 NOTES: 1. USE THREADED ROD @ EXISTING FOOTING ONLY. SEE DETAIL 16/S4 LARR# 25279. 2. USE SSTB @ NEW FOOTING ONLY PER LARR# 25248. 3. PROVIDE MIN. POST SIZE AS INDICATED, INCREASE SIZE TO MATCH WALL THICKNESS. 4. ALL HOLDOWN TO BE DOUGLAS FIR-LARCH No. 1. Max Uplift Force (lbs) Holdown Capcit 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in SW Design Page 9 800 N Tustin Ave Unit #H5/1/2025 SHEARWALL DESCRIPTION T3 C3 T4 C4 AT ROOF LEVEL Total Shearwall Length ft = Sum (b1 + b2 + ..) Total Shear (V_Roof) lbs = Shear Trib Width * Line Trib Length (L) * Roof Unit Shear (psf) Unit Shear (v_Roof) plf = V_Roof / Sum(b1 + b2 + ..) SW-1 Dead Load lbs = Roof_Dead_Laod + Ceiling_Dead_Load SW-1 Uplift Force T1 lbs = ( Upward Force ) - ( Downward Force ) = (v_Roof * H_2nd Fl) - (0.6 * SW-1 Dead Load /2) Drag Force at Open lbs = V_Roof / Line Trib Length (L) * L_Opening v_Roof L_Opening b2b1 L SW-1 V_Roof H_ 1 s t F l o o r SW-2 35-24 UMIH Suite H_SANTA ANA_R0.xls, SW Description 1-Story Page 10 800 N Tustin Ave Unit #H5/1/2025 SHEARWALL DESIGN #REF! #REF! Fl. Type Story Shear Wall Type ROOF 2.16 psf Ext. 15.00 ft A FALSE TRUE TRUE TRUE TRUE TRUE ROOF SW-01 Shearwall Length ft 19.67 Total Shearwall Length ft 19.67 Shear Trib. Width ft 24.0 Line Trib. Length ft 61.5 Line Total Length ft 61.5 Line Total Shear lbs 3,188 Line Unit Shear plf 162 1 v = 340 plf (1-Side 15/32'' Str. I w/ 10d Common Nails @ 6''-6''-12'' O.C.) Drag Length ft 6.0 Drag Force lbs 648 Strap Type MST27 Roof DL Trib. Width ft - - - Ceiling DL Trib. Width ft - - - Wall Height ft - Wall Dead Load plf - Wall Shear Force lbs 3,188 Uplift Force (Demand) lbs (269) Holdown Type HDU4 Uplift Force (Capacity) lbs 3,424 Wall Height LINE 100% Wood Shearwall 10d 35-24 UMIH Suite H_SANTA ANA_R0.xls, Shearwall Line A Page 11 800 N Tustin Ave Unit #H5/1/2025 SHEARWALL DESIGN #REF! #REF! Fl. Type Story Shear Wall Type ROOF 2.16 psf Ext. 15.00 ft 2 FALSE TRUE TRUE TRUE TRUE TRUE ROOF SW-02 Shearwall Length ft 7.42 Total Shearwall Length ft 7.42 Shear Trib. Width ft 24.0 Line Trib. Length ft 31.0 Line Total Length ft 31.0 Line Total Shear lbs 1,607 Line Unit Shear plf 217 x 8 ft / 7.42 ft = 218.9 plf 2 v = 510 plf (1-Side 15/32'' Str. I w/ 10d Common Nails @ 4''-6''-12'' O.C.) Drag Length ft 6.0 Drag Force lbs 648 Strap Type MST27 Roof DL Trib. Width ft 12.0 12.0 - Ceiling DL Trib. Width ft 12.0 12.0 - Wall Height ft - Wall Dead Load plf - Wall Shear Force lbs 1,607 Uplift Force (Demand) lbs 3,283 Holdown Type HDU5 Uplift Force (Capacity) lbs 4,253 Wall Height LINE 100% Wood Shearwall 10d 35-24 UMIH Suite H_SANTA ANA_R0.xls, Shearwall Line 2. Page 12 800 N Tustin Ave Unit #H5/1/2025 TABLES REFERENCED IN BEAM DESIGN SPREADSHEET 2018 NDS Table 4A fb fv E Select Str 1,500 180 1,900,000 No.1&Better 1,200 180 1,800,000 No.1 1,000 180 1,700,000 No.2 900 180 1,600,000 No.3 525 180 1,400,000 Stud 700 180 1,400,000 2018 NDS Table 4D fb fv E Dense Str 1,900 170 1,700,000 Select Str 1,600 170 1,600,000 Dense No. 1 1,550 170 1,700,000 No.1 1,350 170 1,600,000 Dense No. 2 1,000 170 1,400,000 No.2 875 170 1,300,000 Other Material Prllm2.0E 2,900 290 2,000,000 Mcrlm1.8E 2,600 285 1,800,000 Mcrlm1.9E 2,600 285 1,900,000 Steel Fy=36 ksi 23,760 14400 29,000,000 Steel Fy=46 ksi 30,360 18400 29,000,000 Steel Fy=50 ksi 33,000 20000 29,000,000 1. FOR DOUGLAS FIR-LARCH USE 19% MAX. MOISTURE CONTENT LOAD SYMBOLS AND NOTATION D = Dead Load E = Earthquake Load Lr = Roof Live Load W = Wind Load L = Floor Live Load ASCE7-16 2.4 LOAD COMBINATION - ALLOWABLE STRESS DESIGN 1. D 2. D + Lr Load Duration = 1.25 3. D + L Max. (Dead + Live) 4. D + 0.75 (Lr + L) Load Duration = 1.25 5.(1.0 + 0.14SDS)D + 0.7E 6.(1.0 + 0.105SDS)D + 0.525E + 0.75(L + Lr) 7.(0.6 − 0.14SDS)D + 0.7E ASCE7-16 12.4.3.2 TABLE 1604.3 (2022 CBC) DEFLECTION LIMITS Roof Members L D + L Supporting Plaster Ceiling l / 360 l / 240 Supporting Nonplaster Ceiling l / 240 l / 180 Not Supporting Ceiling l / 180 l / 120 Floor Members l / 360 l / 240 Max. (Dead + Live + Lateral) Allowable Stress Increase = 1.2  = 2.5 For Flexible Diaphragm WWPA Design Values for Visually Graded (2"-4") Design Values for Visually Graded (5" & Larger) Douglas Fir-Larch 1 WWPA Douglas Fir-Larch 1 35-24 UMIH Suite H_SANTA ANA_R0.xls, Tables Refrenced in Beam Design Page 13 800 N Tustin Ave Unit #H5/1/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 ALLOWABLE STRESSES REPETITIVE MEMBER NO NO NO NO NO NO REPETITIVE FACTOR, Cr 1.00 1.00 1.00 1.00 1.00 1.00 SIZE FACTOR, Cf 0.97 1.00 1.20 1.00 1.00 1.30 BENDING STRESSES, F'b psi 1,308 2,900 1,080 2,900 2,900 1,170 SHEAR STRESSES, F'v psi 170 290 180 290 290 180 MODULUS OF ELASTICITY ksi 1,700 2,000 1,600 2,000 2,000 1,600 UNIFORM DISTRIBUTED LOAD OVER FULL SPAN ROOF TRIB. WIDTH ft 4.00 2.00 16.00 21.00 13.00 CEILING TRIB. WIDTH ft 1.33 - - 7.00 7.00 FLOOR TRIB. WIDTH ft DECK TRIB. WIDTH ft WALL HEIGHT ft 6.00 6.00 3.00 WALL TYPE (EXT, INT)EXT EXT EXT AUTO CALC BEAM WEIGHT TOTAL DEAD LOAD (D plf 39.80 127.90 267.20 TOTAL ROOF LIVE LOAD (L plf 40.00 20.00 160.00 TOTAL FLOOR LIVE LOAD (L plf - - - PARTIALLY DISTRIBUTED LOAD ROOF TRIB. WIDTH ft CEILING TRIB. WIDTH ft FLOOR TRIB. WIDTH ft DECK TRIB. WIDTH ft WALL HEIGHT ft WALL TYPE (EXT, INT) TOTAL DEAD LOAD (D plf - - - TOTAL ROOF LIVE LOAD (L plf - - - TOTAL FLOOR LIVE LOAD (L plf - - - FROM (LEFT SUPPORT) ft LENGTH OF LOAD ft TRIANGULAR DISTRIBUTED LOAD ROOF TRIB. WIDTH ft TOTAL DEAD LOAD (D plf - - - TOTAL ROOF LIVE LOAD (L plf - - - CONCENTRATED LOADS P1 CHILLER CB1 DEAD LOAD (P D ) lbs 0.8 618.2 ROOF LIVE LOAD (P Lr) lbs 620.0 FLOOR LIVE LOAD (P L ) lbs - - LATERAL, P (W or 0.7E) lbs - - DIST. (LEFT SUPPORT) ft 1.00 15.50 P2 CHILLER DEAD LOAD (P D ) lbs 0.8 ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft 6.50 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 14 800 N Tustin Ave Unit #H5/1/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 P3 DEAD LOAD (P D ) lbs ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft P4 DEAD LOAD (P D ) lbs ROOF LIVE LOAD (P Lr) lbs FLOOR LIVE LOAD (P L ) lbs LATERAL, P (W or 0.7E) lbs DIST. (LEFT SUPPORT) ft LOAD CASE 1: D MAX. BENDING MOMENT lb-ft 4,784 1,023 1,411 MAX. DEFLECTION in 0.285 0.032 0.007 LEFT REACTION lbs 618 512 868 RIGHT REACTION lbs 617 512 868 LOAD CASE: Lr MAX. BENDING MOMENT lb-ft 4,805 160 845 MAX. DEFLECTION in 0.286 0.005 0.004 LEFT REACTION lbs 620 80 520 RIGHT REACTION lbs 620 80 520 LOAD CASE: L MAX. BENDING MOMENT lb-ft - - - MAX. DEFLECTION in - - - LEFT REACTION lbs - - - RIGHT REACTION lbs - - - LOAD CASE 2: D + Lr Wood Load Duration Factor = 1.25 MAX. BENDING MOMENT lb-ft 7,671 947 1,805 MAX. DEFLECTION in 0.572 0.037 0.011 LEFT REACTION lbs 991 473 1,111 RIGHT REACTION lbs 990 473 1,111 LOAD CASE 3: D + L Wood Load Duration Factor = 1.0 MAX. BENDING MOMENT lb-ft 4,784 1,023 1,411 MAX. DEFLECTION in 0.285 0.032 0.007 LEFT REACTION lbs 618 512 868 RIGHT REACTION lbs 617 512 868 LOAD CASE 4: D + 0.75 (Lr + L)Wood Load Duration Factor = 1.25 MAX. BENDING MOMENT lb-ft 6,710 915 1,636 MAX. DEFLECTION in 0.500 0.036 0.010 LEFT REACTION lbs 1,083 572 1,258 RIGHT REACTION lbs 1,082 572 1,258 LOAD CASE 5:(1.0 + 0.14SDS)D + 0.7E Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 3,423 732 1,010 MAX. DEFLECTION in 0.272 0.030 0.006 LEFT REACTION lbs 590 488 829 RIGHT REACTION lbs 589 488 829 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 15 800 N Tustin Ave Unit #H5/1/2025 SIMPLY SUPPORTED BEAM DESIGN FALSE TRUE FALSE FALSE TRUE TRUE TJI CB2 HDR1 HDR2 HDR3 HDR4 SPAN ft 31.00 8.00 6.50 MATERIAL (WOOD, STEEL)WOOD DF-L WOOD Prllm WOOD DF-L WOOD Prllm WOOD Prllm WOOD DF-L BEAM SECTION in 6x16 3.5x14 4x10 3.5x14 3.5x14 4x 8 GRADE No.1 Prllm2.0E No.2 Prllm2.0E Prllm2.0E No.2 LOAD CASE 6:(1.0 + 0.105SDS)D + 0.525E + 0.75(L + Lr)Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 5,567 784 1,374 MAX. DEFLECTION in 0.443 0.033 0.009 LEFT REACTION lbs 959 523 1,127 RIGHT REACTION lbs 958 523 1,127 LOAD CASE 7:(0.6 − 0.14SDS)D + 0.7E Wood Load Duration Factor = 1.6 MAX. BENDING MOMENT lb-ft 1,361 291 401 MAX. DEFLECTION in 0.108 0.012 0.003 LEFT REACTION lbs 234 194 329 RIGHT REACTION lbs 234 194 329 CHECK BENDING STRESSES MAX. BENDING MOMENT lb-ft 7,671.0 - 1,023.2 1,804.9 - - SECTION MODULUS, S in3 220.2 114.3 49.9 114.3 114.3 30.7 BENDING STRESS psi 418.0 - 246.0 189.4 - - CHECK BENDING STRESS RATIO 32% OK 0% OK 23% OK 7% OK 0% OK 0% OK CHECK SHEAR STRESSES #VALUE!#VALUE! #VALUE! MAX. SHEAR FORCE lbs 1,083.2 #VALUE!571.60 1,258.40 #VALUE! #VALUE! SECTION AREA, A in2 85.25 49.00 32.38 49.00 49.00 25.38 SHEAR STRESS, fv psi 19.06 #VALUE!26.48 38.52 #VALUE! #VALUE! CHECK SHEAR STRESS RATIO 11% OK #VALUE!15% OK 13% OK #VALUE! #VALUE! CHECK DEFLECTION #VALUE!#VALUE! #VALUE! MOMENT OF INERTIA, I in4 1,706.78 800.33 230.84 800.33 800.33 111.15 MAX. DEFLECTION, DL in 0.285 0.032 0.007 MAX. DEFLECTION, LL in 0.286 #VALUE!0.005 0.004 #VALUE! #VALUE! DEFLECTION LIMITS, LL L / 360 L / 360 L / 360 L / 360 L / 360 L / 360 CHECK DEFLECTION LL < 1.03 OK #VALUE!< 0.27 OK < 0.22 OK #VALUE! #VALUE! MAX. DEFLECTION, DL+LL in 0.572 #VALUE!0.037 0.011 #VALUE! #VALUE! DEFLECTION LIMITS, DL+LL L / 240 L / 240 L / 240 L / 240 L / 240 L / 240 CHECK DEFLECTION (DL+LL)< 1.55 OK #VALUE!< 0.4 OK < 0.33 OK #VALUE! #VALUE! 35-24 UMIH Suite H_SANTA ANA_R0.xls, Roof Beam Design 1 Page 16 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:(N) RB4-R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design iLevel Truss Joist Parallam PSL 2.0E 2,900.0 2,900.0 2,900.0 750.0 2,000.0 1,016.54 290.0 2,025.0 45.070 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.0160, Lr = 0.0120 ksf, Tributary Width = 4.0 ft, (Roof) Point Load : D = 0.20 k @ 13.0 ft, (TRANSFORMER) Uniform Load : D = 0.060 ksf, Extent = 1.0 -->> 7.0 ft, Tributary Width = 2.0 ft, (RTU (Chiller)) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.247: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 13.002 ft 37.06 psi= = 3,425.18 psi 3.5x20Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination D Only = = = 261.00 psi== Section used for this span 3.5x20 Maximum Shear Stress Ratio 0.142 : 1 0.000 ft= = 847.11 psi Maximum Deflection 0 <360 662 Ratio =0 <240 Max Downward Transient Deflection 0.154 in 2226Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.516 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.243 0.142 0.90 0.945 1.001.00 1.00 11.64 598.4 2,466.1 1.73 261.037.1 0.00.0 1 0.247 0.138 1.25 0.945 1.001.00 1.00 16.47 847.1 3,425.2 2.33 362.550.0 0.00.0 1 0.229 0.129 1.25 0.945 1.001.00 1.00 15.26 784.9 3,425.2 2.18 362.546.8 0.00.0 1 0.082 0.048 1.60 0.945 1.001.00 1.00 6.98 359.0 4,384.2 1.04 464.022.2 . Page 17 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:(N) RB4-R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.5164 14.042 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 2.636 2.100 Max Upward from Load Combinations 2.636 2.100 Max Upward from Load Cases 1.952 1.416 D Only 1.952 1.416 +D+Lr 2.636 2.100 +D+0.750Lr 2.465 1.929 +0.60D 1.171 0.850 Lr Only 0.684 0.684 Page 18 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:(N) RB4A-R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design iLevel Truss Joist Parallam PSL 2.0E 2,900.0 2,900.0 2,900.0 750.0 2,000.0 1,016.54 290.0 2,025.0 45.070 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Point Load : D = 0.20 k @ 13.0 ft, (TRANSFORMER) Uniform Load : D = 0.060 ksf, Extent = 1.0 -->> 7.0 ft, Tributary Width = 2.0 ft, (RTU (Chiller)) Uniform Load : D = 0.0160, Lr = 0.0120 ksf, Tributary Width = 4.0 ft, (ROOF) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.183: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 11.825 ft 32.14 psi= = 3,425.18 psi 3.5x20Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination D Only = = = 261.00 psi== Section used for this span 3.5x20 Maximum Shear Stress Ratio 0.123 : 1 0.000 ft= = 626.62 psi Maximum Deflection 0 <360 1054 Ratio =0 <240 Max Downward Transient Deflection 0.077 in 3729Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.273 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.182 0.123 0.90 0.945 1.001.00 1.00 8.73 449.0 2,466.1 1.50 261.032.1 0.00.0 1 0.183 0.118 1.25 0.945 1.001.00 1.00 12.18 626.6 3,425.2 2.00 362.542.8 0.00.0 1 0.170 0.111 1.25 0.945 1.001.00 1.00 11.32 582.2 3,425.2 1.87 362.540.1 0.00.0 1 0.061 0.042 1.60 0.945 1.001.00 1.00 5.24 269.4 4,384.2 0.90 464.019.3 . Page 19 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:(N) RB4A-R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.2732 11.912 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 2.299 1.835 Max Upward from Load Combinations 2.299 1.835 Max Upward from Load Cases 1.723 1.259 D Only 1.723 1.259 +D+Lr 2.299 1.835 +D+0.750Lr 2.155 1.691 +0.60D 1.034 0.756 Lr Only 0.576 0.576 Page 20 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:Header3 (EXISTING) R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design Douglas Fir-Larch No.2 875.0 875.0 600.0 625.0 1,300.0 470.0 170.0 425.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-22 / IBC 2024 (L<=100psf) .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight NOT internally calculated and added Point Load : D = 1.260, Lr = 0.580 k @ 3.0 ft, (PSL) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.631: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 3.007 ft 53.28 psi= = 1,312.50 psi 4x10Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 212.50 psi== Section used for this span 4x10 Maximum Shear Stress Ratio 0.251 : 1 0.000 ft= = 828.26 psi Maximum Deflection 0 <360 917 Ratio =0 <240 Max Downward Transient Deflection 0.033 in 2911Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.105 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.600 0.238 0.90 1.200 1.001.00 1.00 2.36 567.2 945.0 0.79 153.036.5 0.00.0 1 0.631 0.251 1.25 1.200 1.001.00 1.00 3.44 828.3 1,312.5 1.15 212.553.3 0.00.0 1 0.581 0.231 1.25 1.200 1.001.00 1.00 3.17 763.0 1,312.5 1.06 212.549.1 0.00.0 1 0.203 0.080 1.60 1.200 1.001.00 1.00 1.42 340.3 1,680.0 0.47 272.021.9 . Page 21 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:Header3 (EXISTING) R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.1046 3.737 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 1.150 0.690 Max Upward from Load Combinations 1.150 0.690 Max Upward from Load Cases 0.788 0.473 D Only 0.788 0.473 +D+Lr 1.150 0.690 +D+0.750Lr 1.059 0.636 +0.60D 0.473 0.284 Lr Only 0.363 0.218 Page 22 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:RB2_R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design Douglas Fir-Larch No.1 1,350.0 1,350.0 925.0 625.0 1,600.0 580.0 170.0 675.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.0160, Lr = 0.0120 ksf, Tributary Width = 13.0 ft, (ROOF) Point Load : D = 1.720, Lr = 0.580 k @ 5.0 ft, (RB4A) Point Load : D = 1.950, Lr = 0.680 k @ 10.50 ft, (RB4) Uniform Load : D = 0.0160, Lr = 0.0120 ksf, Extent = 12.0 -->> 19.0 ft, Tributary Width = 15.0 ft, (ROOF) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.615: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 10.471 ft 76.65 psi= = 1,566.07 psi 6x24Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 212.50 psi== Section used for this span 6x24 Maximum Shear Stress Ratio 0.361 : 1 17.058 ft= = 963.78 psi Maximum Deflection 0 <360 842 Ratio =0 <240 Max Downward Transient Deflection 0.093 in 2446Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.271 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.563 0.321 0.90 0.928 1.001.00 1.00 26.77 634.7 1,127.6 4.23 153.049.1 0.00.0 1 0.615 0.361 1.25 0.928 1.001.00 1.00 40.66 963.8 1,566.1 6.60 212.576.6 0.00.0 1 0.563 0.328 1.25 0.928 1.001.00 1.00 37.19 881.5 1,566.1 6.01 212.569.7 0.00.0 1 0.190 0.108 1.60 0.928 1.001.00 1.00 16.06 380.8 2,004.6 2.54 272.029.5 . Page 23 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:RB2_R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.2706 9.639 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 7.137 8.181 Max Upward from Load Combinations 7.137 8.181 Max Upward from Load Cases 4.691 5.143 D Only 4.691 5.143 +D+Lr 7.137 8.181 +D+0.750Lr 6.526 7.422 +0.60D 2.815 3.086 Lr Only 2.446 3.038 Page 24 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:RB3- 5.5X18 GLLM_R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design DF/HF 24F-V5 2,400.0 1,600.0 1,450.0 650.0 1,700.0 900.0 215.0 1,100.0 26.840 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity 1,500.0 ksi 790.0 ksi Ebend- yy Eminbend - yy Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Load for Span Number 1 Point Load : D = 5.140, Lr = 3.040 k @ 0.0 ft, (RB2) Uniform Load : D = 0.010, Lr = 0.0120 ksf, Tributary Width = 31.0 ft, (ROOF) Load for Span Number 2 Uniform Load : D = 0.010, Lr = 0.0120 ksf, Tributary Width = 31.0 ft, (ROOF) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.823: 1 Load Combination +D+Lr Span # where maximum occurs Span # 2 Location of maximum on span 0.000 ft 150.50 psi= = 1,881.72 psi 5.5x18Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 268.75 psi== Section used for this span 5.5x18 Maximum Shear Stress Ratio 0.560 : 1 2.503 ft= = 1,548.43 psi Maximum Deflection 852 >=360 451 Ratio =1330 >=240 Max Downward Transient Deflection 0.409 in 704Ratio =>=360 Max Upward Transient Deflection -0.112 in Ratio = Max Downward Total Deflection 0.637 in Ratio =>=240 Max Upward Total Deflection -0.072 in fb: Actual F'b fv: Actual F'v Span: 2 : Lr Only Span: 1 : Lr Only Span: 2 : +D+Lr Span: 1 : +D+Lr .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCV rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.651 0.467 0.90 1.000 1.001.00 1.00 23.19 936.9 1,440.0 5.96 193.590.3 2 0.692 0.467 0.90 0.941 1.001.00 1.00 23.19 936.9 1,354.8 4.42 193.590.3 0.00.0 1 0.774 0.560 1.25 1.000 1.001.00 1.00 38.32 1,548.4 2,000.0 9.93 268.8150.5 2 0.823 0.560 1.25 0.941 1.001.00 1.00 38.32 1,548.4 1,881.7 8.97 268.8150.5 0.00.0 Page 25 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA STRUCTURAL (c) ENERCALC INC 1983-2023 DESCRIPTION:RB3- 5.5X18 GLLM_R2 Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: R1.ec6 Project Title: Engineer: Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCV rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu 1.00Length = 4.0 ft 1 0.698 0.504 1.25 1.000 1.001.00 1.00 34.54 1,395.5 2,000.0 8.94 268.8135.5 2 0.742 0.504 1.25 0.941 1.001.00 1.00 34.54 1,395.5 1,881.7 7.83 268.8135.5 0.00.0 1 0.220 0.158 1.60 1.000 1.001.00 1.00 13.91 562.1 2,560.0 3.58 344.054.2 2 0.233 0.158 1.60 0.941 1.001.00 1.00 13.91 562.1 2,408.6 2.65 344.054.2 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections Lr Only10.0000 0.000 -0.1124 0.000 2 0.6373 13.274 0.0000 0.000 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 20.984 6.809 Max Upward from Load Combinations 20.984 6.809 Max Upward from Load Cases 11.361 3.833 D Only 11.361 2.975 +D+Lr 20.984 6.809 +D+0.750Lr 18.578 5.850 +0.60D 6.817 1.785 Lr Only 9.623 3.833 Page 26 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RTU-Curb Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: CODE REFERENCES Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design Douglas Fir-Larch No.2 875.0 875.0 600.0 625.0 1,300.0 470.0 170.0 425.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2021 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.1250 ksf, Tributary Width = 3.0 ft, (Chiller) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.655: 1 Load Combination D Only Span # where maximum occurs Span # 1 Location of maximum on span 3.000 ft 54.18 psi= = 1,023.75 psi 4x8Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination D Only = = = 153.00 psi== Section used for this span 4x8 Maximum Shear Stress Ratio 0.354 : 1 0.000 ft= = 670.12 psi Maximum Deflection 0 <360 932 Ratio =0 <240 Max Downward Transient Deflection 0 in 0Ratio =<360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.077 in Ratio =>=240 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v n/a n/a Span: 1 : D Only n/a .Maximum Forces & Stresses for Load Combinations Span #C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1 0.655 0.354 0.90 1.300 1.001.00 1.00 1.71 670.1 1,023.8 0.92 153.054.2 0.00.0 1 0.221 0.120 1.60 1.300 1.001.00 1.00 1.03 402.1 1,820.0 0.55 272.032.5 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections D Only 1 0.0772 3.022 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 1.141 1.141 Page 27 800 N Tustin Ave Unit #H5/1/2025 Wood Beam LIC# : KW-06018875, Build:20.23.08.30 FA Trinity Engineering (c) ENERCALC INC 1983-2023 DESCRIPTION:RTU-Curb Fa Structural Engineering Email : atefg@fastructural.com Address : 15041 Genoa Cir Huntington Beach CA 92647 Phone :+1 714.519.5027 Project File: 35-24.ec6 Project Title: Engineer: Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from Load Combinations 0.685 0.685 Max Upward from Load Cases 1.141 1.141 D Only 1.141 1.141 +0.60D 0.685 0.685 Page 28 800 N Tustin Ave Unit #H5/1/2025 Page 29 800 N Tustin Ave Unit #H5/1/2025 Page 30 800 N Tustin Ave Unit #H5/1/2025 COLUMN AXIAL CAPACITY WOOD PROPERTIES: Use Douglas Fir-Larch CF =1.1 Kce = 0.30 Buckling about x-axis?YES Species:Cm =1.0 c = 0.80 Check le/d reqmt.OK! E =CT =1.0 Kf = 1.00 F'c =Ct = 1.0 (for bolted or nailed members) E' = Ci =1.0 Fc* = CD =1.0 No. of 1+ Fce/Fc*Column Plies 2c Capacity C01 1 - 2x 4 1.5 3.50 8 64.0 27.4 27.4 558.27 0.597 1.00 0.498 465.79 2.45 kips C02 2 - 2x 4 3.0 3.50 8 32.0 27.4 27.4 558.27 0.597 1.00 0.498 465.79 4.89 kips C03 1 - 2x 6 1.5 5.50 8 64.0 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 6.22 kips C04 2 - 2x 6 3.0 5.50 8 32.0 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 12.43 kips C05 1 - 2x 8 1.5 7.50 8 64.0 12.8 12.8 2,563.48 2.742 2.34 0.910 850.54 9.57 kips C06 2 - 2x 8 3.0 7.25 8 32.0 13.2 13.2 2,395.43 2.562 2.23 0.902 843.35 18.34 kips WOOD PROPERTIES: Use Douglas Fir-Larch CF =1.1 Kce = 0.30 Buckling about x-axis?YES Species:Cm =1.0 c = 0.80 Check le/d reqmt.OK! E =CT =1.0 Kf = 1.00 F'c =Ct = 1.0 (for bolted or nailed members) E' = Ci =1.0 Fc* = CD =1.0 No. of 1+ Fce/Fc*Column Plies 2c Capacity C07 1 - 4x 4 3.5 3.50 8 27.4 27.4 27.4 558.27 0.597 1.00 0.498 465.79 5.71 kips C08 1 - 4x 6 3.5 5.50 8 27.4 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 14.50 kips C09 1 - 4x 8 3.5 7.50 8 27.4 12.8 12.8 2,563.48 2.742 2.34 0.910 850.54 22.33 kips C10 1 - 6x 6 5.5 5.50 8 17.5 17.5 17.5 1,378.58 1.474 1.55 0.806 753.41 22.79 kips C11 1 - 6x 8 5.5 7.25 8 17.5 13.2 13.2 2,395.43 2.562 2.23 0.902 843.35 33.63 kips Note: KcE = 0.510 - 0.839(COV)where COV = 0.25 - sawn lumber 0.3 - for visually graded lumber 0.15 - MEL 0.384 - for machine evaluated lumber (MEL)0.11 - MSR (machine stress rated) 0.418 - for roducts w/ COV<=0.11 0.10 - glu-lam le/dx le/dx F'cCOL(le/d) Fce Fce/Fc*CPdxlex,y 1,500 psi 1,700,000 psi 1,650 psi le/dy 935 psi Size dy Stud 1,400,000 psi 850 psi 1,400,000 psi No.1 1,700,000 psi Size le/dyCOL dy dx lex,y F'c(le/d) Fce Fce/Fc* CP 35-24 UMIH Suite H_SANTA ANA_R0.xls, Column Design Page 31 800 N Tustin Ave Unit #H5/1/2025