HomeMy WebLinkAbout5514 W Rhonda Ave - Plan518 Lake Cleveland Street
Burley,ID 83318
1-208-994-1680
1002094
08/09/2024
Structure:Single Story Residence
Address: 5514 Rhonda Avenue
Santa Ana, California 92703, Orange County
Codes & Standards:
Jurisdiction:City of Santa Ana
Solar Array Components Adequate¹
Solar Array Anchorage to Roof Adequate
Roof Structure Adequate
Note:
1) Only includes items listed in Table 1.
Respectfully,
Professional Engineering Team
PV Letters
To whom it may concern,
This structural report shall state the structural adequacy of the existing building structure to support the solar
array installation proposed in Permit Drawings by Illumine-i (Project: 5514 Rhonda Avenue, Santa Ana,
California 92703, dated 08/08/2024, Rev A).
Based upon our analysis of the proposed installation to the existing structure, we have determined the
adequacy of the following components to be as follows:
This analysis will be affected if any conditions throughout the report or associated permit drawings are not
also represented on-site. Contractor shall notify the engineer of record of any discrepancies and receive
written approval from the engineer of record before proceeding with installation. If there are any questions or
further assistance required, please call.
Project Information:
Structural Report for Solar Array Installation
PV Letters Project #:
Issued Date:
Design Requirements:2022 CRC (ASCE 7-16), 2022 CBC, 2022 CEBC
trevor@pvletters.com
Project Name: 5514 Rhonda Avenue, Santa Ana, California 92703
5514 W Rhonda
Ave11/27/2024
Project Name: 5514 Rhonda Avenue, Santa Ana, California 92703
Issued Date: 08/09/2024
Solar Array Installation Page | 2
Page #:
2
3
4
5
1) INTRODUCTION
Source
SEG Solar Inc.
SnapNrack
SnapNrack
Note:
1) All components are verified to withstand design criteria either based upon
referenced rating letters or by calculations provided in this report.
YUKON SERIES
BLACK DIAMOND
HALF CELL 400-
415W
Solar Panels Spec Sheet by SEG SOLAR, document
ID: SEG_DS_2023-02_Rev01_EN
SpeedSeal foot
(Framing Mount)
Roof Attachment
System
Report # 2019-13746.004 – SnapNrack
Ultra Rail SpeedSeal Foot Pre-
Production, by PZSE, Inc. - Structural
Engineers, dated 3/9/2020
SnapNrack UR-40 Rail System
Report # 2017-03227.11 – Engineering
Certification and Span Tables for the
SnapNrack Ultra Rail Solar
Photovoltaic Racking System, by PZSE,
Inc. - Structural Engineers, dated
2/26/2020
4) CALCULATIONS
Table 1 – List of Solar Panel Array Components
Component Description Rating Letter Info
The solar panel array shall be installed on the existing single story residence. The structure is wood
framed. The roof structure is composed of 2x4 rafters spaced at 2'-0" on center. Original building drawings
are unavailable; however, site information was obtained during a site visit by Next Phase Electric.
The solar panel array is composed of components shown in Table 1.
3.2) Limitations
TABLE OF CONTENTS
1) INTRODUCTION
Table 1 – List of Solar Panel Array Components
2) DESIGN CRITERIA
3) DISCLAIMERS
3.1) Assumptions
5514 W Rhonda
Ave11/27/2024
Project Name: 5514 Rhonda Avenue, Santa Ana, California 92703
Issued Date: 08/09/2024
Solar Array Installation Page | 3
Wood Framing: 5 psf 0 psf
Solar Array: 3 psf 1.0
1.0
Asphalt Shingles: 2 psf 1.0
1/2" Plywood: 1.6 psf 1.0
0 psf
20 psf
115 mph
89.1 mph
II
B
0.18
II
1.0
D(default)
DSeismic Design Category:
Seismic Importance Factor, IE:
Mapped Spectral Response
Acceleration Parameters:SS: 1.339, S1: 0.477
Design Spectral Response
Acceleration Parameters:SDS: 1.071, SD1: 0.58
Site Class (Assumed):
Risk Category:
Slope Factor, Cs:
Flat Roof Snow Load, pf:
Live Loads
Roof Live Load:
Wind Loads
Basic Design Wind Speed, V:
Allowable Stress Design Wind
Speed, Vasd:
Risk Category:
Exposure Category:
GCpi (+/-):
Seismic Loads
Thermal Factor, Ct:
2) DESIGN CRITERIA
Code & Standards:
Dead Loads Snow Loads
Ground Snow Load, pg:
Snow Exposure Factor, Ce:
Snow Importance Factor, Is:
2022 CRC (ASCE 7-16), 2022 CBC, 2022 CEBC
5514 W Rhonda
Ave11/27/2024
Project Name: 5514 Rhonda Avenue, Santa Ana, California 92703
Issued Date: 08/09/2024
Solar Array Installation Page | 4
Wall Framing No. 2 Douglas Fir Larch
2. All solar panel array components listed in Table 1 shall be designed and installed per the
manufacturer’s approved installation specifications.
3. The existing building structure was properly constructed and maintained in good condition.
3.2 LIMITATIONS
1. Waterproofing around the roof penetrations is the responsibility of others.
2. No allowance has been made in this report for any existing deficiency in design, material,
construction, or lack of maintenance for the existing structure or proposed equipment.
3. Any miscellaneous items not explicitly listed in this report have not been designed or
detailed by PV Letters. It is recommended that material of suitable size and strength be
obtained from a reputable manufacturer for miscellaneous items.
4. The referenced permit plans are schematic representations of the installation of proposed
equipment to the existing structure. The contractor shall be responsible for field verifying
existing conditions, proper fit, and clearances in the field.
5. Construction documents depicting the required modifications for installation are obtainable
from PV Letters, but are beyond the scope of this report.
3) DISCLAIMERS
3.1 ASSUMPTIONS
1. Wood framing meets the following specifications in accordance with the ANSI/AWC
“National Design Specification” (2018 Edition).
Roof Framing No. 2 Douglas Fir Larch
5514 W Rhonda
Ave11/27/2024
Project Name: 5514 Rhonda Avenue, Santa Ana, California 92703
Issued Date: 08/09/2024
Solar Array Installation Calculations: Page | 1
l.Component & Cladding Wind Calculations
Site Data
Basic Design Wind Speed, V: 115 mph
Exposure Category: B
Risk Category: II
Topo Factor, Kzt: 1.00
Building Data
Mean Roof Height, h: 15 ft
Building Type: Enclosed
Roof Type: Hip
Roof Slope: 18 °
Least Horizontal Building Length: 17 ft
Largest Horizontal Building Length: 50 ft
Estimated Building Area: 3000 ft2
Roof dimension, 'a' per ASCE7: 3 ft
Wind Data
Velocity Pressure Coef, Kz: 0.700
Wind Directionality Factor, Kd: 0.85
Ground Elevation Factor, Ke: 1.0
Velocity Pressure @ Height, qh: 19.9 psf
Effective Wind Area, A: 20.0 ft2
Component & Cladding Wind Pressures
Positive Pressure for Effective Area, A = 20 SF*
Roof Zone (GCp) (GCpi, +/-)
Max Positive
Pressure (psf)
All Zones 0.58 0.18 15.15
*Positive notation indicates wind pressure acting downwards on roof
Negative Pressure for Effective Area, A = 20 SF*
Roof Zone (GCp) (GCpi, +/-)
Max Negative
Pressure (psf)
1 -1.80 0.18 -39.49
2r -2.15 0.18 -46.38
2e & 3 -2.32 0.18 -49.90
*Negative notation indicates wind pressure acting away from roof
*Wind calculations according to ASCE 7-16*
5514 W Rhonda
Ave11/27/2024
Project Name: 5514 Rhonda Avenue, Santa Ana, California 92703
Issued Date: 08/09/2024
Solar Array Installation Calculations: Page | 2
ll.Wind Forces on Solar Panel System
Panel Data
Short Length of Panel: 45 in
Long Length of Panel: 68 in
Quantity of Panels: 30
*Panel Pressure
Panel Location
(Roof Zone)
Eff. Wind Area, A
(ft2)
γa,
Fig. 29.4-8 γE, uplift
γE,
others
Positive
Pressure (psf)
Uplift Pressure
(psf)
Service Uplift
Pressure (psf)
1 21.0 0.751 1.5 1.0 11.25 -43.93 -26.36
2r 21.0 0.751 1.5 1.0 11.25 -51.84 -31.11
2e & 3 21.0 0.751 1.5 1.0 11.25 -55.77 -33.47
*Panel pressures only calculated for roof zones where solar panels are present.
Attachment Data
Connection # 1:Connection # 2:
Max CNX Spacing: 4.00 ft Max CNX Spacing: 4.00 ft
Panel Attachments, Withdrawal
CNX #
Attach. Location
(Roof Zone)
Trib. Wind
Area, A γa
γE,
uplift
Uplift Pressure
(psf)
Withdrawal
Force (lbs)
Service
Withdrawal
Force (lbs)
1 2e & 3 11.3 0.8 1.5 -64.89 -733.1 -439.9
Applied Load: -439.88 lbs
Allowable Load: -802.00 lbs
Safe
Note:
*Wind calculations according to ASCE 7-16*
1) The system is safe since the allowable capacity is greater than the service withdrawal force.
2) See the rating letter info on page 2 in Table-1 for additional information on attachments capacity.
Attachments are along..(x)..of panel:Short Side
Attachments are
along..(x)..of panel:Long Side
5514 W Rhonda
Ave11/27/2024
Project Name: 5514 Rhonda Avenue, Santa Ana, California 92703
Issued Date: 08/09/2024
Solar Array Installation Calculations: Page | 3
III.Gravity Loads
Roof Dead Loads Roof Dead Loads with Panels
Asphalt Shingles:2 psf Solar Array 3 psf
1/2" Plywood:1.6 psf psf
psf
psf
psf
psf
Total Existing Dead Load:3.6 psf Total New Dead Load:6.6 psf
Roof Live Loads Roof Live Loads with Panels
16.0 psf 0 psf
Snow Loads Snow Loads with Panels
Ground Snow Load, pg:0 psf Thermal Factor, Ct:1.0
Snow Exposure Factor, Ce:1.0 Flat Roof Snow Load, pf:0.0 psf
Snow Importance Factor, Is:1.0 Slope Factor, Cs:1.0
Thermal Factor, Ct:1.0 Sloped Roof Snow Load, ps:0.0 psf
Flat Roof Snow Load, pf:0 psf
Slope Factor, Cs:1.0
Sloped Roof Snow Load, ps:0 psf
Gravity Load Comparison
Factored Load Combinations Exist. Weight (psf) New Weight (psf)
1.4 DL:5.0 9.2
1.2 DL + 1.6 Lr:29.9 7.9
1.2 DL + 1.6 S:4.3 7.9
Maximum Factored Gravity Loads:29.9 9.2
% Increase in Factored Weight:-69.1%
Roof Live Load @ Location w/
Solar Array:
Per Section 503.3 of the 2022 CEBC, any existing gravity load-carrying structural element for which an alteration
causes an increase in design dead, live, or snow load, including drift effects, of more than 5% shall be replaced or
altered as needed to carry the gravity loads by the CBC for new structures.
Since there is no increase of gravity load greater than 5%, the existing structure is adequate for the alteration.
Existing Design Roof Live Load
(reduced for sloped roof):
5514 W Rhonda
Ave11/27/2024
Project Name: 5514 Rhonda Avenue, Santa Ana, California 92703
Issued Date: 08/09/2024
Solar Array Installation Calculations: Page | 4
IV.Seismic Loads
Seismic Weight
Existing Roof Dead Load:8.6 psf
Roof Dead Load @ Panel Locations:11.6 psf
Quantity of Pre-Existing Panels:0
% of Roof w/ Solar Panels:21.0%
Equiv. Seismic Weight Increase:7.3%
Per Section 503.4 of the 2022 CEBC, any existing lateral load-carrying element whose demand-capacity ratio
with the alteration considered is not more than 10% greater than its demand-capacity ratio with the alteration
ignored shall be permitted to remain unaltered.
Since there is no increase of seismic weight greater than 10%, the existing lateral load-carrying elements are
adequate for the alteration.
5514 W Rhonda
Ave11/27/2024
Expedited Permit Process for PV Systems - Micro-Inverter1
Expedited Permit Process for PV Systems
Micro-Inverter
The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro-
cess provides a means to differentiate systems that can be permitted quickly and easily
due to their similarity with the majority of small-scale PV systems. Those systems with
unique characteristics may be handled with small additions to this Expedited Permit
Process or may require much more information, depending on the uniqueness of the
installation.
The following pages contain forms for the Micro-Inverter to use with the Expedited Per-
mit Process. The Standard String, AC Module, and Supply-Side Connection forms
are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic-
tions that have adopted the Expedited Permit Process for PV Systems, these forms can
be filled out electronically and submitted in either printed form and via email. An elec-
tronic format is used so that the supplied information is standardized and legible for the
local jurisdiction.
5514 W Rhonda
Ave11/27/2024
Expedited Permit Process for PV Systems — Micro-Inverter 2
Expedited Permit Process for Small-Scale PV Systems
Micro-Inverter
The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations
are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential
systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been
suggested to provide as a path to permit approval.
Required Information for Permit:
1.Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it
should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings
with a 3’ perimeter space at ridge and sides may not need separate fire service review.
2.Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects,
required signs, and ac connection to building (see supplied standard electrical diagram).
3.Specification sheets and installation manuals (if available) for all manufactured components including, but not
limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system.
Step 1: Structural Review of PV Array Mounting System
Is the array to be mounted on a defined, permitted roof structure? l Yes l No
If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1.
Roof Information:
1.Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________
____________________________________________________________________________________________________
If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…).
2.Does the roof have a single roof covering?l Yes l No
If No, submit completed worksheet for roof structure WKS1.
3.Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________
Mounting System Information:
1.Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap
beneath the module frames? l Yes l No
If No, provide details of structural attachment certified by a design professional.
2.For manufactured mounting systems, fill out information on the mounting system below:
a.Mounting System Manufacturer ___________Product Name and Model#________________________________
b.Total Weight of PV Modules and Rails ___________lbs
c.Total Number of Attachment Points____________
d.Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1)
e.Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for
maximum spacing allowed based on maximum design wind speed)
f.Total Surface Area of PV Modules (square feet)_________________ ft2
g.Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2
If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1.
Step 2: Electrical Review of PV System (Calculations for Electrical Diagram)
In order for a PV system to be considered for an expedited permit process, the following must apply:
1.PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems.
2.The PV array is composed of 4 series strings or less per inverter.
3.The total inverter capacity has a continuous ac power output 13,440 Watts or less
4.The ac interconnection point is on the load side of service disconnecting means (690.64(B)).
5.One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV
system. Interactive PDF diagrams are available at www.solarabcs.org/permitting.
Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant
understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively
communicate, provide an alternative diagram with appropriate detail.
5514 W Rhonda
Ave11/27/2024
E
x
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
3
Micro-Inverter Site Plan
5514 W Rhonda
Ave11/27/2024
E
x
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
4
Micro-Inverter Electrical Diagram
Contractor Name,
Address and Phone:One-Line Standard Electrical Diagram
for Micro-Inverter PV Systems
Site Name:
Site Address:
System AC Size:
SIZE FSCM NO DWG NO REV
E1.1a
SCALE NTS Date: SHEET
Drawn By:
Checked By:
DESCRIPTION OR CONDUCTOR TYPE
USE-2 or PV WIRE
GEC EGC X ALL THAT APPLY
EXTERIOR CABLE LISTED W/ INV.
THWN-2 or XHHW-2 or RHW-2
GEC EGC X ALL THAT APPLY
NO DC GEC IF 690.35 SYSTEM
THWN-2 or XHHW-2 or RHW-2
GEC EGC X ALL THAT APPLY
TAG
1
2
3
4
5
CONDUIT AND CONDUCTOR SCHEDULE
COND.
GAUGE
MFG
MFG
NUMBER OF
CONDUCTORS
MFG Cable
MFG Cable
CONDUIT
TYPE
N/A
N/A
N/A
SAME
SAME
CONDUIT
SIZE
N/A
N/A
N/A
SAME
SAME
DESCRIPTION
PV DC or AC MODULE
DC/AC INVERTER (MICRO)
J-BOX (IF USED)
PV ARRAY
AC COMB. PANEL (IF USED)
GEN METER (IF USED)
AC DISCONNECT (IF USED)
SERVICE PANEL
TAG
1
2
3
4
5
6
7
8
PART NUMBER NOTES
FOR UNUSED MODULES
PUT "N/A” in BLANK ABOVE
1
1
3
2
3
EQUIPMENT SCHEDULE
2
_____
MICRO-INVERTERS
IN BRANCH-
CIRCUIT
MOD
____
DC
AC
MOD
____
DC
AC
MOD
____
DC
AC
MOD
____
DC
AC
MOD
____
DC
AC
MOD
____
DC
AC
J-BOX
4
AC DISCO
M
BUILDING
GROUNDING
ELECTRODE
G
M
UTILITY
SERVICE
MAIN SERVICE PANEL
MAIN
OCPD
INVERTER
OCPD
6
7
8
5
4 5
G
SEE GUIDE APPENDIX D FOR
INFORMATION ON MODULE AND
ARRAY GROUNDING
AC COMBINER
PANEL
G
____
MICRO-INVERTERS
IN BRANCH-
CIRCUIT
5514 W Rhonda
Ave11/27/2024
E
x
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
5
Contractor Name,
Address and Phone:Notes for One-Line Standard Electrical
Diagram for Single-Phase PV Systems
Site Name:
Site Address:
System AC Size:
SIZE FSCM NO DWG NO REV
E1.2a
SCALE NTS Date: SHEET
Drawn By:
Checked By:
MAX POWER-POINT CURRENT (IMP)
MAX POWER-POINT VOLTAGE (VMP)
OPEN-CIRCUIT VOLTAGE (VOC)
SHORT-CIRCUIT CURRENT (ISC)
MAX SERIES FUSE (OCPD)
MAXIMUM POWER (PMAX)
MAX VOLTAGE (TYP 600VDC)
VOC TEMP COEFF (mV/oC or %/oC )
IF COEFF SUPPLIED, CIRCLE UNITS
MODULE MAKE
MODULE MODEL
PV MODULE RATINGS @ STC (Guide Section 5)
MAX DC VOLT RATING
MAX POWER @ 40oC
NOMINAL AC VOLTAGE
MAX AC CURRENT
MAX OCPD RATING
INVERTER MAKE
INVERTER MODEL
INVERTER RATINGS (Guide Section 4)
1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THEREQUIREMENT? YES NO N/A
2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A
3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT
4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9)
5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAREXCEPTION IN 690.64(B)(2)(a)? YES NO
NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):
1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC
2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC
2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES),
a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE.b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE.
NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E):
OCPD = OVERCURRENT PROTECTION DEVICE
NATIONAL ELECTRICAL CODE®REFERENCES
SHOWN AS (NEC XXX.XX)
NOTES FOR ALL DRAWINGS:
SIGNS–SEE GUIDE SECTION 7
SIGN FOR DC DISCONNECT
SIGN FOR INVERTER OCPD AND AC
DISCONNECT (IF USED)
No sign necessary since 690.51
marking on PV module covers
needed information
AC OUTPUT CURRENT
NOMINAL AC VOLTAGE
SOLAR PV SYSTEM
AC POINT OF CONNECTION
THIS PANEL FED BY MULTIPLE
SOURCES (UTILITY AND SOLAR)
Notes for Micro-Inverter Electrical Diagram 5514 W Rhonda
Ave11/27/2024
PV-1
COVER SHEET
VICINITY MAP
METER NUMBER: 222013-507784
AHJ
CA-CITY OF SANTA ANA
UTILITY
SOUTHERN CALIFORNIA EDISON CO
5514 RHONDA AVENUE, SANTA ANA, CA 92703
NEW PHOTOVOLTAIC SYSTEM 12.150kW DC / 9.750kW AC / 11.012kW CEC AC
CODES AND STANDARDS
CALIFORNIA ADMINISTRATIVE CODE
ELECTRIC CODE: CEC 2022
FIRE CODE: CFC 2022
BUILDING CODE: CBC 2022
RESIDENTIAL CODE: CRC 2022
WIND SPEED:110 MPH
SNOW LOAD: 0 PSF
SCOPE OF WORK
(N) 12.150kW DC / 9.750kW AC / 11.012kW CEC AC ROOF MOUNT
PV SYSTEM
(30) SEG SOLAR SEG-405-BMD-HV (405W) MODULE
(30) ENPHASE IQ8M-72-M-US (240V) MICROINVERTER
(1) ENPHASE IQ COMBINER 4
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
1025263
LICENSE NO
C-10
CLASSIFICATION
ECLE
T
IR
C
AHSEPTXEN
T NIA
ROFIETA
OF C LA
S
I
RO
R
C
ONT
CLA
TCA
ELECTR I
SED
NEC
L
I
VICTOR ISAAC NUNEZ
SHEET CATALOG
PV-1 COVER SHEET
PV-1.1 GENERAL NOTES
PV-2 SITE PLAN
PV-3 MOUNTING DETAILS-1
PV-3.1 MOUNTING DETAILS-2
PV-3.2 STRUCTURAL DETAILS
PV-4 SINGLE LINE DIAGRAM
PV-4.1 ELECTRICAL CALCULATIONS
PV-4.2 EQUIPMENT ELEVATION VIEW
PV-5 PLACARDS
PV-5.1 PROPOSED EQUIPMENT LAYOUT
SS SPEC SHEETS
Structural Only 10/18/2024
5514 W Rhonda
Ave11/27/2024
PV-1.1
GENERAL NOTES
NOTES:
1. MODULES ARE LISTED UNDER UL 1703 / UL 61730 AND CONFORM TO THE STANDARDS.
2. INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS.
3. DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM. ACTUAL SITE CONDITIONS MAY VARY.
4. WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT SHALL BE MAINTAINED IN ACCORDANCE WITH CEC 110.26.
5. ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL / SERVICE EQUIPMENT.
6. ALL CONDUCTORS SHALL BE 600V, 90°C STANDARD COPPER UNLESS OTHERWISE NOTED.
7. WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.
8. THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM UTILITY IS RECEIVED.
9. ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG
POINTS OF BUILDING CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREES, WIRES OR SIGNS.
10. PV ARRAY COMBINER / JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING.
11. RACKING SYSTEM SHALL BE LISTED TO UL 2703.
12. FIRE RATING OF EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED WITH ADDITION OF PHOTOVOLTAIC SYSTEM.
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
Structural Only 10/18/2024
5514 W Rhonda
Ave11/27/2024
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
5514 RHONA AVE SANTAN ANA CA 92703
CARLEY RAYMOND
661-878-7576 09/09/2024
craymond@nextphaseelect.com
NEXT PHASE ELECTRIC
1025263
5514 W Rhonda
Ave11/27/2024
TO: CITY OF SANTA ANA
RE: 5514 RHONDA AVE SANTA ANA, CA 92703
DATE: 09/6/2024
To whom it may concern:
This is to inform you that my contract with ____________________________ is void and cancelled as
they went out of business. I will be moving forward with Next Phase Electric Contractor License
#1025263 for my home improvement contract. I approve of cancelling the existing permit and
approving Next Phase Electric to proceed with my project.
Thanks, and best regards,
__________________________________
Name
__________________________________
Signature
AMERICAN SOLAR ADVANTAGE
Zoho Sign Document ID: 30204908-LWMACE5NKSG6SLHUM3VBJ-93XT7LE-NACEN-7V1E_SK
5514 W Rhonda
Ave11/27/2024
Generated on Sep 6, 2024 22:15 P DT
Document ID :30204908-LWMAC E5NKSG6SLHUM3V BJ-93XT7LE-NAC EN-7V 1E_SK
Document Name :LETTER OF C A NCELLATION TO A HJ H TRIN H
Sent by :Carley Raym ond <c raym ond@nextphaseel ect.com >
Organiz ation :N ext P hase Elec tri c
Sent on :Sep 6, 2024 08:21 PDT Signers :1
Completed on :Sep 6, 2024 22:15 PDT Receives a copy :0
Sign order :Sequential Approvers :0
N o. of documents :1
Summary
Recipients
Certificate of Completion
Signer
H IEP TRIN H
al ex.luong.0712@ gmai l.com
Emailed on :Sep 6, 2024 08:21 P DT Accessed from :172.58.114.117
Viewed on :Sep 6, 2024 22:13 P DT Device used :Mobi le
Terms agreed on :Sep 6, 2024 22:13 PDT Authentication type :None
Signed on :Sep 6, 2024 22:15 P DT
Signature
5514 W Rhonda
Ave11/27/2024
Legal Disclosure
ELECTRONIC RECORD AND SIGNATURE DISCLOSURE
Please read the fol lowing i nform ati on c arefully. By c li c king the 'I agree' button, you agree that you have r evi ewed the
followi ng term s and condi ti ons and c onsent to transact busi ness el ectronical ly usi ng Zoho Si gn electronic signatur e
system . If you do not agree to these terms, do not cl ick the 'I agree' button.
Electr onic docume nts
Please note that Next Phase El ectric ("we", "us" or "Company") wi ll send all docum ents el ectronical ly to you to the
em ail addr ess that you have given us during the c ourse of the busi ness rel ati onship unl ess you tel l us otherwise in
acc ordance wi th the procedure explai ned herei n. Onc e you si gn a doc ument el ectronical ly, we wil l send a P DF version
of the docum ent to you.
Re quest for pape r copie s
You have the ri ght to request paper c opies of these doc um ents sent to you elec troni cal ly from
j abel@ nextphaseel ec t.com . A lternati vely, you also have the ability to download and print these docum ents sent to you
el ectronical ly, and r e-upl oad a sc anned c opy of the pr inted and physical ly si gned doc um ents. If you, however, wish to
request paper copi es of these docum ents sent to you el ectronically, you c an write back to the sender.
Withdr awing y our consent
A t any point i n tim e during the course of our business relationship, you have the ri ght to withdraw your consent to
rec eive docum ents i n el ectronic format. If you wish to withdr aw your consent, you can decl ine to si gn a docum ent that
we have sent to you and send an em ail to jabel @nextphaseelect.com informi ng us that you wi sh to recei ve doc uments
onl y i n paper form at. Upon request from you, we wil l stop sending doc um ents using Zoho Sign el ectronic si gnature
system .
To advise Ne xt Phase Electr ic of your ne w email address
If you need to change the emai l address that you use to recei ve noti c es and discl osures from us, write to us at
j abel@ nextphaseel ec t.com
Sy stem requir eme nts
C om patibl e wi th recent ver si ons of popular browsers suc h as Chrom e, Fi refox, Safar i, and Internet Explorer. Zoho Sign
i s also avai lable on i OS and A ndroid devi ces.
5514 W Rhonda
Ave11/27/2024
MODULE SPEC SHEET
SS
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
5514 W Rhonda
Ave11/27/2024
MICROINVERTER SPEC SHEET
SS
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
5514 W Rhonda
Ave11/27/2024
SS
COMBINER BOX SPEC SHEET
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
5514 W Rhonda
Ave11/27/2024
MOUNT SPEC SHEET
SS
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
5514 W Rhonda
Ave11/27/2024
RAIL SPEC SHEET
SS
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
5514 W Rhonda
Ave11/27/2024
5514 W Rhonda
Ave11/27/2024
5514 W Rhonda
Ave11/27/2024
t. (415) 805.7000
38 Fountain Square Plaza
Cincinnati, OH 45263
dividendfinance.com
All lending is originated by Fifth Third Bank, National Association. Member FDIC. Equal Housing Lender.
For solar and certain home improvement loans, Fifth Third Bank does business under the trade name Dividend.
October 29, 2024
To whom it may concern,
Dividend Solar Finance LLC, the loan provider for Hiep Trinh, authorizes Next Phase Electric to complete the
interconnection process for the solar system located at 5514 Rhonda Avenue. The original installer, American Solar
Advnatage, is out of business and unable to complete this interconnection for the customer.
This letter serves as confirmation that Next Phase Electric is completing the approval and interconnection process
for this solar system. This process includes obtaining permits, completing inspections, and submitting
interconnection paperwork. The system and electrical work was completed at its current state by American Solar
Advantage, Next Phase Electric will complete remediation if needed for inspections.
Hiep Trinh
5514 Rhonda Avenue
Santa Ana, CA 92703
Regards,
The Dividend Team
5514 W Rhonda
Ave11/27/2024
MSPACCB
JB
C C
C C C C C C C B
B
B
BBBBBBB
A
A
A
A
A
A
A
A
A
A
A
SCALE:1/16" = 1'-0"
PV-2
SITE PLAN
(N) UTILITY METER WITH MAIN SERVICE
PANEL (EXTERIOR) (UNDER PATIO)
SCOPE OF WORK
(N) 12.150kW DC / 9.750kW AC / 11.012kW CEC AC ROOF MOUNT
PV SYSTEM
(30) SEG SOLAR SEG-405-BMD-HV (405W) MODULE
(30) ENPHASE IQ8M-72-M-US (240V) MICROINVERTER
(1) ENPHASE IQ COMBINER 4
TOTAL ARRAY AREA = 630.44 SQ.FT
TOTAL ROOF AREA = 3002 SQ.FT
% ARRAY AREA IN ROOF = 21%
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
(N) ENPHASE IQ COMBINER 4 (EXTERIOR)
(UNDER PATIO)
(N) AC DISCONNECT (EXTERIOR)
(UNDER PATIO)
(N) CONDUIT RUN
(N) JUNCTION BOX NEMA 4X RATED
(N) (30) SEG SOLAR SEG-405-BMD-HV (405W)
MODULES WITH ENPHASE IQ8M-72-M-US (240V)
MICROINVERTER UNDER EACH MODULE
(N) PHOTOVOLTAIC ARRAY ON MP-01
(N) PHOTOVOLTAIC
ARRAY ON MP-03
(N) PHOTOVOLTAIC
ARRAY ON MP-02
(N) PHOTOVOLTAIC ARRAY ON MP-04
(N) PHOTOVOLTAIC ARRAY ON MP-05
RHONDA AVENUE
DR
I
V
E
W
A
Y
114'-11"
126'
66'-1"
26'-1"
7'-3"
5'-5"
67'-9"
(E) DETACHED STRUCTURE
(E) RESIDENCE
(E) GATE
(E) FENCE
LEGEND
JB
SETBACK
PROPERTY LINE
FENCE AND GATE LINE
JUNCTION BOX
VENT & ATTIC FAN
(ROOF OBSTRUCTION)
AC AC DISCONNECT
CB COMBINER BOX
MSP UTILITY METER WITH
MAIN SERVICE PANEL
STRING CONFIGURATION
BRANCH DETAILS
A 11 MICROINVERTERS
B 10 MICROINVERTERS
C 9 MICROINVERTERS
(E) GATE
RAPID SHUTDOWN COMPLIANT SYSTEM
27'-2"
Structural Only 10/18/2024
5514 W Rhonda
Ave11/27/2024
(N) ENPHASE IQ COMBINER 4
(EXTERIOR) (UNDER PATIO)
(E) UTILITY METER WITH
MAIN SERVICE PANEL
(EXTERIOR) (UNDER PATIO)
M
ENPHASE
(N) AC DISCONNECT
(EXTERIOR) (UNDER PATIO)
SOUTH EXTERIOR WALL ELEVATION BACKYARD
(E) GRADE
(N) EMT AC CONDUIT FROM ROOF
(E) WINDOW
(E) WINDOW
BACKYARD
PV-4.2
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
DIMENSIONS OF THE EQUIPMENT:
(H X W X D)
COMBINER BOX: 19.5" X 14.75" X 6.63"
AC DISCONNECT: 19.25" X 9.13" X 7.38"
SOUTH EXTERIOR WALL ELEVATION
SCALE:1/2" = 1'-0"
4'-9"3'-9"4'
6"
1'
EQUIPMENT ELEVATION VIEW
5514 W Rhonda
Ave11/27/2024
MSPACCB
PV-5.1
PROPOSED EQUIPMENT LAYOUT
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
**THIS SHEET FOR FIELD USE ONLY, NOT REQUIRED FOR PERMITTING**
NAME:
SIGNATURE:DATE:
MICROINVERTER STICKERS
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
(N) UTILITY METER WITH MAIN SERVICE
PANEL (EXTERIOR) (UNDER PATIO)
(N) ENPHASE IQ COMBINER 4
(EXTERIOR) (UNDER PATIO)
(N) AC DISCONNECT (EXTERIOR)
(UNDER PATIO)
(N) PV ARRAY
RAPID SHUTDOWN COMPLIANT SYSTEM
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
C1
C2
C3
C4
C5
C6
C7
C8
C9
5514 W Rhonda
Ave11/27/2024
PV-3
MOUNTING DETAILS-1
WIND SPEED: 110 MPH AND SNOW LOAD: 0 PSF
S.NO AZIMUTH PITCH NO. OF
MODULES
ARRAY AREA
(SQ.FT)ROOF TYPE ATTACHMENT ATTACHMENT
QUANTITY
ROOF
EXPOSURE FRAME TYPE FRAME
SIZE
FRAME
SPACING
MAX
ATTACHMENT
SPACING
MAX
OVER
HANG
MP-01 180°18°9 189.13 COMPOSITION
SHINGLE
SNAPNRACK
SPEEDSEAL FOOT 20 ATTIC RAFTERS 2" X 4"24" O.C.4'-0"1'-6"
MP-02 0°18°6 126.08 COMPOSITION
SHINGLE
SNAPNRACK
SPEEDSEAL FOOT 12 ATTIC RAFTERS 2" X 4"24" O.C.4'-0"1'-6"
MP-03 90°18°4 84.05 COMPOSITION
SHINGLE
SNAPNRACK
SPEEDSEAL FOOT 10 ATTIC RAFTERS 2" X 4"24" O.C.4'-0"1'-6"
MP-04 270°18°7 147.1 COMPOSITION
SHINGLE
SNAPNRACK
SPEEDSEAL FOOT 20 ATTIC RAFTERS 2" X 4"24" O.C.4'-0"1'-6"
MP-05 90°18°4 84.05 COMPOSITION
SHINGLE
SNAPNRACK
SPEEDSEAL FOOT 12 ATTIC RAFTERS 2" X 4"24" O.C.4'-0"1'-6"
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
Structural Only 10/18/2024
5514 W Rhonda
Ave11/27/2024
C C
C C C C C C C B
B
B
BBBBBBB
A
A
A
A
A
A
A
A
A
A
A
SCALE:1/8" = 1'-0"
PV-3.1
MOUNTING DETAILS-2
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
NOTE: PENETRATIONS ARE NON-STAGGERED
8'-8"
31'-10"
8'-10"
2'-6"5'-4"3'-2"
2'-3"7'-1"3'-1"
8'
12'-10"
9'-11"
9'-5"
22'-4"10'-4"
8'-4"
5'-4"
2'-1"
9'-2"
14'-11"
6'
1'-7"5'-4"2"
13'-10"26'-1"13'-3"
2'-1"
8'-11"
3'-3"
4'
1'-6"
1'-6"
3'3'
3'
3'
1'-6"
1'-6"
3'
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
(N) ARRAY MP-01
(N) ARRAY MP-02
(N) ARRAY MP-03
(N) ARRAY MP-04
(N) ARRAY MP-05
(N) ALUMINUM RAILS
(E) 2" X 4" RAFTERS
@ 24" O.C. SPACING
LEGEND
SETBACK
RAIL
ATTACHMENT
VENT & ATTIC FAN
(ROOF OBSTRUCTION)
ROOF FRAME
MODULE
3'
3'
Structural Only 10/18/2024
5514 W Rhonda
Ave11/27/2024
PV-3.2
STRUCTURAL DETAILS
STRUCTURAL NOTES
1. ALL SOLAR PANEL COMPONENTS SHALL BE INSTALLED PER
THE MANUFACTURER'S APPROVED INSTALLATION
SPECIFICATIONS.
2. THE EXISTING BUILDING'S STRUCTURE SHALL BE VERIFIED AS
PROPERLY CONSTRUCTED AND MAINTAINED IN GOOD
CONDITION. NO ALLOWANCE HAS BEEN MADE FOR ANY
EXISTING DEFICIENCY IN DESIGN, MATERIAL,
CONSTRUCTION, OR LACK OF MAINTENANCE FOR THE
EXISTING STRUCTURE OR PROPOSED EQUIPMENT.
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS,
PROPER FIT, AND CLEARANCES IN THE FIELD.
3. IF ANY CONDITION THROUGHOUT THE ASSOCIATED REPORT
OR PERMIT DRAWINGS IS NOT REPRESENTED ON-SITE,
CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD
(EOR) OF ANY DISCREPANCIES AND RECEIVE WRITTEN
APPROVAL FROM THE EOR BEFORE PROCEEDING WITH
INSTALLATION.
4. MISCELLANEOUS ITEMS NOT EXPLICITLY NAMED & SHOWN IN
THESE DRAWINGS HAVE NOT BEEN DESIGNED. IT IS
RECOMMENDED THAT MATERIAL OF SUITABLE SIZE &
STRENGTH BE OBTAINED FROM A REPUTABLE
MANUFACTURER FOR MISCELLANEOUS ITEMS.
5. CONTRACTOR SHALL BE RESPONSIBLE TO COMPLETE, SEAL,
& WATERPROOF ROOFTOP PENETRATIONS FOR SOLAR
RACKING.
6. CONTRACTOR TO PROVIDE MINIMUM 1/4" GAP BETWEEN ALL
SOLAR PANELS.
7. PROJECT WINDSPEED IS BASIC WIND SPEED PER CODE
UNLESS NOTED OTHERWISE.
DEAD LOAD CALCULATIONS
BOM QUANTITY LBS/UNIT TOTAL
WEIGHT (LBS)
MODULES 30 47.39 1421.7
MID-CLAMP 44 0.17 7.48
END-CLAMP 32 0.3 9.6
RAIL LENGTH 264 0.42 110.88
SPLICE BAR 10 0.52 5.2
SNAPNRACK
SPEEDSEAL FOOT 74 0.45 33.3
MICROINVERTER 30 2.43 72.9
TOTAL WEIGHT OF THE SYSTEM (LBS)1661.06
TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)630.44
WEIGHT PER SQ. FT.(LBS)2.63
WEIGHT PER PENETRATION (LBS)22.44
SCALE: NTS
(N) STAINLESS STEEL 5/16" LAG BOLT MIN.
2.5" EMBEDMENT PILOT HOLE REQUIRED
(E) 2" X 4" RAFTERS @ 24" O.C. SPACING
(N) SNAPNRACK ULTRA RAIL UR-40
(E) ROOF DECKING(N) SNAPNRACK SPEEDSEAL FOOT
(E) COMPOSITION SHINGLE ROOF MEMBRANE
(N) SNAPNRACK SPEEDSEAL FOOT
(E) 2" X 4" RAFTERS @ 24"
O.C. SPACING
(N) SOLAR MODULE
6" MAX
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
Structural Only 10/18/2024
5514 W Rhonda
Ave11/27/2024
MSPACCB
5514 RHONDA AVENUE, SANTA ANA, CA 92703
PV-5
PLACARDS
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS PHOTOVOLTAIC
SYSTEM ARE UNGROUNDED AND MAY BE
ENERGIZED
LABEL LOCATION
PV COMBINER BOX
[To be used when inverter is ungrounded]
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
WARNING
LABEL LOCATION
AC DISCONNECT,
POINT OF INTERCONNECTION
PER CODE: CEC 690.13
SOLAR DISCONNECT
LABEL LOCATION
AC DISCONNECT, POINT OF INTERCONNECTION
PER CODE: CEC 690.13(B)
!
!
SYSTEM UTILIZES MICROINVERTERS LOCATED UNDER EACH SOLAR MODULE
LABEL LOCATION
POINT OF INTERCONNECTION
PER CODE: CEC 705.12(B)(3-4) AND 690.59
WARNING
DUAL POWER SOURCE SECOND
SOURCE IS PHOTOVOLTAIC
SYSTEM
!
LABEL LOCATION
POINT OF INTERCONNECTION
PER CODE: CEC 705.12(B)(3)(2)
WARNING
POWER SOURCE OUTPUT
CONNECTION
DO NOT RELOCATE THIS
OVER-CURRENT DEVICE
RATED AC OPERATING CURRENT
AC NOMINAL OPERATING VOLTAGE
40.50
240
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
AMPS AC
VAC
LABEL LOCATION
AC DISCONNECT, POINT OF INTERCONNECTION
PER CODE: CEC 690.54
LABEL LOCATION
CONDUIT, PV COMBINER BOX
PER CODE: CEC 690.31(D)(2)
WARNING:PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION
PV COMBINER BOX, JUNCTION BOX (ROOF),
AC DISCONNECT
WARNING-ELECTRIC SHOCK HAZARD
NO USER SERVICEABLE PARTS INSIDE
CONTACT AUTHORIZED SERVICE
PROVIDE FOR ASSISTANCE
NOTES
1.PLACARDS SHALL MEET THE REQUIREMENTS
OF ARTICLES 690 AND 705, UNLESS
OTHERWISE SPECIFIED PER LOCAL AHJ
REQUIREMENTS.
2.PLACARDS SHALL MEET THE REQUIREMENTS
OF SECTION 110.21(B) AS REQUIRED AND
SHALL COMPLY WITH ANSI Z535.4-2011,
PRODUCT SAFETY SIGNS AND LABELS.
3.PLACARDS SHALL BE PERMANENTLY AFFIXED
TO THE EQUIPMENT OR WIRING METHOD.
4.PLACARDS SHALL BE SUFFICIENT
DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED AND SHALL NOT BE
HANDWRITTEN.
5.PLACARDS SHALL NOT COVER EXISTING
MANUFACTURER LABELS.
6.WARNING SIGNAGE TEXT SHALL BE MINIMUM
3/8" TALL.
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED
AS SHOWN
!!CAUTION:MULTIPLE SOURCES
OF POWER
LABEL LOCATION
SERVICE PANEL
PER CODE: CEC 705.10
LABEL LOCATION
AC DISCONNECT, PV COMBINER BOX
PER CODE: CEC 690.56(C)(2)
RAPID SHUTDOWN
SWITCH FOR SOLAR PV
SYSTEM
LABEL LOCATION
AC DISCONNECT,
POINT OF INTERCONNECTION
PER CODE: CEC 690.56(C)
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRICPV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
(N) UTILITY METER WITH MAIN SERVICE
PANEL (EXTERIOR) (UNDER PATIO)
(N) ENPHASE IQ COMBINER 4
(EXTERIOR) (UNDER PATIO)
(N) AC DISCONNECT (EXTERIOR)
(UNDER PATIO)
(N) PV ARRAY
RAPID SHUTDOWN
COMPLIANT SYSTEM
5514 W Rhonda
Ave11/27/2024
ENPHASE IQ COMBINER
WITH IQ GATEWAY
X-IQ-AM1-240-4,
120/240V, NEMA 3R,
INSTALL
20A 2P PV BREAKER
15A 2P GATEWAY
BREAKER (ONLY FOR
SOLAR, NO LOADS
TO BE ADDED)
15A/2P
20A/2P
20A/2P
20A/2P
(3)
(1)
(N) ENPHASE IQ
COMBINER 4
33
(ROOF EQUIPMENT)(GROUND LEVEL EQUIPMENT)
(EXTERIOR)
(N) 60A AC
DISCONNECT
AC DISCONNECT
NON FUSED 60A,
120/240V, 2P,
VISIBLE,
LOCKABLE, LOAD
BREAK RATED,
ACCESSIBLE 24/7,
NEMA 3R
(1) BRANCH OF (11) MICROINVERTER
(1) BRANCH OF (10) MICROINVERTER
(1) BRANCH OF (9) MICROINVERTER
(N) JUNCTION
BOX
NEMA 4X RATED
JUNCTION BOX
(N) (30) SEG SOLAR SEG-405-BMD-HV (405W) MODULE WITH
(N) (30) ENPHASE IQ8M-72-M-US (240V) MICROINVERTER
21
(N) ENPHASE IQ8M-72-M-US (240V)
MICROINVERTER PER MODULE
(N) SURGE PROTECTIVE DEVICE
M
METER: SOUTHERN
CALIFORNIA EDISON CO
222013-507784
(N) 120/240V 1PH 60HZ
(N) 225A END FED
MAIN SERVICE PANEL
(N
)
2
0
0
A
M
A
I
N
BR
E
A
K
E
R
PV BREAKER AT THE
OPPOSITE END OF
BUSBAR
(N) 60A 2P
PV BREAKER
UTILITY
GRID
(N) GROUNDING ELECTRODE, MIN
5/8" x 8' LONG Cu GROUND ROD
INSTALLED IN ACCORDANCE
WITH CEC 250.53
4
(OVER HEAD
SERVICE)
(2) 2/0 AWG THHN/THWN-2, Cu
(1) 2/0 AWG THHN/THWN-2, Cu
(UNDER PATIO)(EXTERIOR)
(UNDER PATIO)
(EXTERIOR)
(UNDER PATIO)
PV-4
MICROINVERTER SPECIFICATIONS
MODEL ENPHASE IQ8M-72-M-US (240V)
POWER RATING 325W
MAX OUTPUT CURRENT 1.35A
CEC WEIGHTED EFFICIENCY 97.5%
MAX NO OF MICRO
INVERTERS/BRANCH 11
MAX DC VOLTAGE 60V
MODULE SPECIFICATIONS
MODEL SEG SOLAR SEG-405-BMD-HV
(405W)
MODULE POWER @ STC 405W
OPEN CIRCUIT VOLTAGE:Voc 37.22V
MAX POWER VOLTAGE:Vmp 30.93V
SHORT CIRCUIT CURRENT:Isc 13.7A
MAX POWER CURRENT:Imp 13.1A
TEMPERATURE COEFFICIENT:Voc -0.27%/°C
MODULE DIMENSIONS: L x W x H 67.79" x 44.64" x 1.18"
SINGLE LINE DIAGRAM
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
1025263
LICENSE NO
C-10
CLASSIFICATION
ECLE
T
IR
C
AHSEPTXEN
T NIA
ROFIETA
OF C LA
S
I
RO
R
C
ONT
CLA
TCA
ELECTR I
SED
NEC
L
I
VICTOR ISAAC NUNEZ
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND
1 NONE (2) 12 AWG ENPHASE Q CABLE
PER BRANCH CIRCUIT NONE (1) 12 AWG THHN/THWN-2, Cu, EGC
2 3/4" EMT (6) 10 AWG THHN/THWN-2, Cu NONE (1) 12 AWG THHN/THWN-2, Cu, EGC
3 3/4" EMT (2) 6 AWG THHN/THWN-2, Cu (1) 6 AWG THHN/THWN-2, Cu (1) 10 AWG THHN/THWN-2, Cu, EGC
4 NONE (1) 6 AWG BARE COPPER, GEC
CONDUCTOR SCHEDULE
NOTE:
1. MICROINVERTERS ARE RAPID SHUTDOWN COMPLIANT AS PER CEC 690.12.
2. KNIFE BLADE AC DISCONNECT SHALL BE INSTALLED WITH PV SYSTEM.
3. REPLACE EXISTING MAIN SERVICE PANEL WITH NEW 225A / 200A MAIN SERVICE PANEL.
4. SURGE PROTECTION SHALL BE INSTALLED WITH THE NEW MAIN SERVICE PANEL IN ACCORDANCE WITH CEC 230.67
5. THE MAIN PANEL IS UNDERGROUND SERVICE WITH 2/0 AWG THHN/THWN-2, Cu PER CEC 310.12.
5514 W Rhonda
Ave11/27/2024
PV-4.1
ELECTRICAL CALCULATIONS
ALLOWABLE BACKFEED:
MAIN PANEL RATING = 225A
MAIN BREAKER RATING = 200A
120% RULE: = (MAIN PANEL RATING * 1.2) - MAIN BREAKER RATING
= (225A * 1.2) - 200A
= 270A - 200A
= 70A
ALLOWABLE BACKFEED = 70A
INVERTER OVERCURRENT PROTECTION:
INVERTER OVERCURRENT PROTECTION = (MICROINVERTER O/P CURRENT *
# OF MICROINVERTERS) * CONTINUOUS LOAD (1.25)
= (1.35 * 30) * 1.25
= 40.50 * 1.25
= 50.62A
PV OVERCURRENT PROTECTION = 60A ≥ 50.62A
ALLOWABLE BACKFEED 70A ≥ 60A PV OVERCURRENT PROTECTION
THE DESIGNED INTERCONNECTION MEETS THE 705.12(B)(3)(2) REQUIREMENTS.
OCPD CALCULATION
AMBIENT TEMPERATURE @ 32°C
WIRE SIZE CALCULATIONS
= 61.1A
= 50.62A
= 26.32A
= 18.56A
= 23.5A
= 18.56A
TAG 1: (AC)
REQUIRED CONDUCTOR AMPACITY (1.35 * 11 * 1.25)
CORRECTED AMPACITY CALCULATION (0.94 * 1 * 25)
18.56A < 23.5A (#12 AWG ENPHASE Q CABLE)
TAG 2: (AC)
REQUIRED CONDUCTOR AMPACITY (1.35 * 11 * 1.25)
CORRECTED AMPACITY CALCULATION (0.94 * 0.8 * 35)
18.56A < 26.32A (3/4" EMT, #10 AWG THHN/THWN-2, Cu)
TAG 3: (AC)
REQUIRED CONDUCTOR AMPACITY (1.35 * 30 * 1.25)
CORRECTED AMPACITY CALCULATION (0.94 * 1 * 65)
50.62A < 61.1A (3/4" EMT, #6 AWG THHN/THWN-2, Cu)
ELECTRICAL NOTES
1.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER
CEC 310.10(D).
2.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET
LOCATIONS PER CEC 310.10(C).
3.MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%.
4.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED.
5.BREAKER/FUSE SIZES PER CEC 240.
6.AC EQUIPMENT GROUNDING CONDUCTOR SIZED PER CEC 250.122.
7.AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON CEC 310.15(B)(1).
8.MAX. SYSTEM VOLTAGE COEFFICIENT IS FROM MODULE MANUFACTURER OR CEC 690.7
WHEN MANUFACTURER COEFFICIENT UNAVAILABLE.
9.CONDUCTORS ARE SIZED PER CEC TABLE 310.16.
10. CONDUIT SHALL BE INSTALLED MINIMUM 7/8" FROM ROOF SURFACE.
AC WIRE SIZING CALCULATIONS BASED ON FOLLOWING EQUATIONS
REQUIRED CONDUCTOR AMPACITY:
INVERTER OUTPUT CURRENT * #OF INVERTERS = MAX CURRENT PER 690.8(A)(1)(e) * 125%
= MAX CURRENT PER 690.8(B)(1)
CORRECTED AMPACITY CALCULATIONS:
DERATED CONDUCTOR AMPACITY PER 690.8(B)(2) = AMPACITY * TEMPERATURE DERATE
FACTOR * CONDUIT FILL DERATE
DERATED CONDUCTOR AMPACITY CHECK : MAX CURRENT PER 690.8(B)(1) <
DERATED CONDUCTOR AMPACITY
LICENSE TYPE: C-10
NEXT PHASE ELECTRIC
APN: 09920301
PHONE NUMBER: (661) 878-7576
ADDRESS: 5409 ALDRIN COURT,
BAKERSFIELD, CA 93313
ADDRESS: 5514 RHONDA AVENUE,
SANTA ANA, CA 92703
COORDINATES: 33.750842, -117.941808
CONTRACTOR INFORMATION
NAME: HIEP TRINH
CUSTOMER INFORMATION
PROJECT ID AUR-1002094
DATE 10/3/2024
CREATED BY SSB
SIGNATURE
LICENSE NUMBER: 1025263
12.150kW DC / 9.750kW AC / 11.012kW
CEC AC ROOF MOUNT PV SYSTEM
5514 W Rhonda
Ave11/27/2024
Generated on N ov 19, 2024 17:10 PST
Document ID :30204908-Y9U4LCQJI-4C FU0Y_QJ1V9GYHMWUNTNA 0P N_CBAB0UK
Document Name :LETTER OF C A NCELLATION TO A HJ H TRIN H 2
Sent by :Carley Raym ond <c raym ond@nextphaseel ect.com >
Organiz ation :N ext P hase Elec tri c
Sent on :Nov 19, 2024 16:03 P ST Signers :1
Completed on :Nov 19, 2024 17:10 P ST Receives a copy :0
Sign order :Sequential Approvers :0
N o. of documents :1 Witnesses :0
Summary
Recipients
Certificate of Completion
Signer
H IEP TRIN H
al ex.luong.0712@ gmai l.com
Emailed on :Nov 19, 2024 16:03 PST Accessed from :172.58.115.196
Viewed on :N ov 19, 2024 17:09 PST Device used :Mobi le
Terms agreed on :Nov 19, 2024 17:09 P ST Authentication type :None
Signed on :Nov 19, 2024 17:10 PST
Signature
5514 W Rhonda
Ave11/27/2024
Legal Disclosure
ELECTRONIC RECORD AND SIGNATURE DISCLOSURE
Please read the fol lowing i nform ati on c arefully. By c li c king the 'I agree' button, you agree that you have r evi ewed the
followi ng term s and condi ti ons and c onsent to transact busi ness el ectronical ly usi ng Zoho Si gn electronic signatur e
system . If you do not agree to these terms, do not cl ick the 'I agree' button.
Electr onic docume nts
Please note that Next Phase El ectric ("we", "us" or "Company") wi ll send all docum ents el ectronical ly to you to the
em ail addr ess that you have given us during the c ourse of the busi ness rel ati onship unl ess you tel l us otherwise in
acc ordance wi th the procedure explai ned herei n. Onc e you si gn a doc ument el ectronical ly, we wil l send a P DF version
of the docum ent to you.
Re quest for pape r copie s
You have the ri ght to request paper c opies of these doc um ents sent to you elec troni cal ly from
j abel@ nextphaseel ec t.com . A lternati vely, you also have the ability to download and print these docum ents sent to you
el ectronical ly, and r e-upl oad a sc anned c opy of the pr inted and physical ly si gned doc um ents. If you, however, wish to
request paper copi es of these docum ents sent to you el ectronically, you c an write back to the sender.
Withdr awing y our consent
A t any point i n tim e during the course of our business relationship, you have the ri ght to withdraw your consent to
rec eive docum ents i n el ectronic format. If you wish to withdr aw your consent, you can decl ine to si gn a docum ent that
we have sent to you and send an em ail to jabel @nextphaseelect.com informi ng us that you wi sh to recei ve doc uments
onl y i n paper form at. Upon request from you, we wil l stop sending doc um ents using Zoho Sign el ectronic si gnature
system .
To advise Ne xt Phase Electr ic of your ne w email address
If you need to change the emai l address that you use to recei ve noti c es and discl osures from us, write to us at
j abel@ nextphaseel ec t.com
Sy stem requir eme nts
C om patibl e wi th recent ver si ons of popular browsers suc h as Chrom e, Fi refox, Safar i, and Internet Explorer. Zoho Sign
i s also avai lable on i OS and A ndroid devi ces.
5514 W Rhonda
Ave11/27/2024
TO: CITY OF SANTA ANA
RE: 5514 RHONDA AVE SANTA ANA, CA 92703
DATE: 11/19/2024
To whom it may concern:
This is to inform you that my contract with ____________________________ is void and cancelled as
they went out of business. I will be moving forward with Next Phase Electric Contractor License
#1025263 for my home improvement contract. I approve of cancelling any existing permits and
approving Next Phase Electric to proceed with my project to install solar panels, pull permits and
finish inspections.
Thanks, and Best regards,
__________________________________
Name
__________________________________
Signature
AMERICAN SOLAR ADVANTAGE
Zoho Sign Document ID: 30204908-Y9U4LCQJI-4CFU0Y_QJ1V9GYHMWUNTNA0PN_CBAB0UK
5514 W Rhonda
Ave11/27/2024