Loading...
HomeMy WebLinkAbout2704 W Camden Pl - Plan***The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. Bldg#: 101120682 Elec#: 20183879 Approvals: Elec: M Smith 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 Minda Herman (Aug 23, 2024 11:59 PDT) Minda Herman 08/23/2024 2704 W Camden Pl 9/26/2024 Expedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 2704 W Camden Pl 9/26/2024 Expedited Permit Process for PV Systems — Micro-Inverter 2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 2704 W Camden Pl 9/26/2024 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Micro-Inverter Site Plan             2704 W Camden Pl 9/26/2024 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Micro-Inverter Electrical Diagram Contractor Name, Address and Phone:One-Line Standard Electrical Diagram for Micro-Inverter PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.1a SCALE NTS Date: SHEET Drawn By: Checked By: DESCRIPTION OR CONDUCTOR TYPE USE-2 or PV WIRE GEC EGC X ALL THAT APPLY EXTERIOR CABLE LISTED W/ INV. THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY NO DC GEC IF 690.35 SYSTEM THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY TAG 1 2 3 4 5 CONDUIT AND CONDUCTOR SCHEDULE COND. GAUGE MFG MFG NUMBER OF CONDUCTORS MFG Cable MFG Cable CONDUIT TYPE N/A N/A N/A SAME SAME CONDUIT SIZE N/A N/A N/A SAME SAME DESCRIPTION PV DC or AC MODULE DC/AC INVERTER (MICRO) J-BOX (IF USED) PV ARRAY AC COMB. PANEL (IF USED) GEN METER (IF USED) AC DISCONNECT (IF USED) SERVICE PANEL TAG 1 2 3 4 5 6 7 8 PART NUMBER NOTES FOR UNUSED MODULES PUT "N/A” in BLANK ABOVE 1 1 3 2 3 EQUIPMENT SCHEDULE 2 _____ MICRO-INVERTERS IN BRANCH- CIRCUIT MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC J-BOX 4 AC DISCO M BUILDING GROUNDING ELECTRODE G M UTILITY SERVICE MAIN SERVICE PANEL MAIN OCPD INVERTER OCPD 6 7 8 5 4 5 G SEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDING AC COMBINER PANEL G ____ MICRO-INVERTERS IN BRANCH- CIRCUIT 2704 W Camden Pl 9/26/2024 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Contractor Name, Address and Phone:Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.2a SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC 2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE.b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE®REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) No sign necessary since 690.51 marking on PV module covers needed information AC OUTPUT CURRENT NOMINAL AC VOLTAGE SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Notes for Micro-Inverter Electrical Diagram 2704 W Camden Pl 9/26/2024 Empower Solar 1300 E. Shaw Ave #173 Fresno, CA, 93710800-306-6953 CSLB#1057693 - C10 To Whom It May Concern: I, Scott Forster, am the license holder for Empower Solar, contractor license C-10 #1057693 and certify to the accuracy of this authorization form. I authorize the following Empower employee(s) to apply for, sign, file and authorize cancellations of all documents necessary to obtain/cancel any business license and/or permit for Empower Solar.  Brendan Blankenship Name: Scott Forster Signature: Date: 02/1/2023 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 1724178104-Minda Herman -Santa Ana-HO Auth Letter 1 Final Audit Report 2024-08-23 Created:2024-08-23 By:Empower Home (mandy@mpwrsolar.com) Status:Signed Transaction ID:CBJCHBCAABAA2N88CwzSWSwuBUmQeXK5osvekFBYKD72 "1724178104-Minda Herman -Santa Ana-HO Auth Letter 1" Hist ory Document created by Empower Home (mandy@mpwrsolar.com) 2024-08-23 - 6:01:54 PM GMT Document emailed to aqua_obelisk@sbcglobal.net for signature 2024-08-23 - 6:01:59 PM GMT Email viewed by aqua_obelisk@sbcglobal.net 2024-08-23 - 6:58:42 PM GMT Signer aqua_obelisk@sbcglobal.net entered name at signing as Minda Herman 2024-08-23 - 6:59:34 PM GMT Document e-signed by Minda Herman (aqua_obelisk@sbcglobal.net) Signature Date: 2024-08-23 - 6:59:36 PM GMT - Time Source: server Agreement completed. 2024-08-23 - 6:59:36 PM GMT 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : UNIRAC 1411 Broadway Blvd, NE Albuquerque, NM 87102 RE: Solar Array Installation at 2704 W Camden Pl, Santa Ana, CA 92704, USA To Whom it May Concern, CODE REFERENCES: BUILDING CODE: 2022 CALIFORNIA BUILDING CODE 2021 INTERNATIONAL BUILDING CODE ASCE 7-16 SCOPE OF WORK: DESIGN PARAMETERS RISK CATEGORY : DESIGN WIND SPEED : mph WIND EXPOSURE : GROUND SNOW LOAD : psf SEISMIC DESIGN CATEGORY : EXISTING ROOF STRUCTURE ROOF : 2x6 Rafters @ 24" O.C. ROOF MATERIAL : W Tile CONNECTION TO ROOF STRUCTURE MOUNTING CONNECTION : Minda Herman PE 08-08-2024 Roof structural framing plan has been reviewed for additional loading due to installation of the roof mounted solar PV addition. The structural review that follows, including plans and calculations, only apply to the section of the roof that is directly supporting the solar PV system and its supporting elements. 08 August 2024 Per your request, we have reviewed the existing structure at the above referenced site. The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof per layout plan. (2) 1/4" SS LAG SCREWS w/ MIN. 2.5" EMBEDMENT INTO (E) 2x FRAMING MEMBER @ MAX. 48" O.C. ALONG RAILS (2) RAILS PER ROW OF PANELS, EVENLY SPACED. PANEL LENGTH PERPENDICULAR TO RAIL NOT TO EXCEED 74" II 95 B 0 *null Page 1 2704 W Camden Pl 9/26/2024 OBSERVED CONDITIONS: CONCLUSIONS: LIMITATIONS: Praneet R Erusu, P.E. Principal Engineer Erusu Consultants US Inc. The observed roof framing is described below. If field conditions differ, the contractor shall notify the engineer prior to starting construction. The roof framing is supported by 2x6 Rafters @ 24" O.C are spanning between load bearing walls. The maximum allowed clear span of rafter is 14ft, to be verified in field by the contractor. Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. In the area of the solar array, other live loads will not be present or will be greatly reduced (2022 CBC, Section 1607.14.4). The gravity loads and the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Therefore, the requirements of Section 503.3 of the 2022 CEBC are met and the structure is permitted to remain unaltered. The solar array will be flush-mounted (no more than 10" above the roof surface) and parallel to the roof surface. Thus, we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case. Regarding seismic loads, we conclude that any additional forces will be small. Conservatively neglecting the weight of existing wall materials, the installation of the solar panels represents an increase in the total weight (and resulting seismic load) of 1.2%. Because the increase in lateral forces is less than 10%, this addition meets the requirements of the exception in Section 503.4 of the 2022 CEBC. Thus the existing lateral force resisting system is permitted to remain unaltered. Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work performed must be in accordance with accepted industry-wide methods and applicable safety standards. Existing Roof and structural members are assumed to be in good and serviceable condition. The contractor must notify Erusu Consultants US Inc. should any damage, deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found. The use of solar panel support span tables provided by others are allowed only where the building type, site conditions, site-specific design parameters, and solar panel configuration match the description of the span tables. The design of the solar panel racking (mounts, rails,etc.), and electrical engineering is the responsibility of others. Waterproofing around the roof penetrations is the responsibility of others. Erusu Consultants US Inc. assumes no responsibility for improper installation of the solar array. 08 Aug 2024 EXP : 30 Sep 2025 Page 2 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Address : Site Plan: Minda Herman PE 08-08-2024 2704 W Camden Pl, Santa Ana, CA 92704, USA Page 3 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Roof Dead Load Roof Slope = : Angle = degrees Roof Live Load Roof Live Load = psf (Refer ASCE 7-16, Table 4.3-1) Roof Live Load with PV Array = psf 2022 CBC, Section 1607.14.4 (Ceiling load and MEP is assumed to be not supported by rafter) 3.16 1/2" Gypsum Ceiling Minda Herman PE 08-08-2024 DL = Increase due to Roof Slope Plan Projected Material Weight (psf) 12.65 1.16 3.16 0.53Insulation 0.5 1.05 2.32 1.50 21.32 1/2" Plywood 1.1 1.05 Framing 3 1.05 W Tile 12 1.05 4 12 18 Material Material Weight (psf) PV Array 3 1.05 2.2 1.05 MEP & Misc. 1.5 20 0 Page 4 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Minda Herman PE 08-08-2024 Summary of Gravity Loads Dead Load, D = psf Roof Live Load, Lr = psf Gravity Load Comparison (D + Lr)/Cd = psf (Cd = 0.9 for D, 1.15 for S, 1.25 for Lr) Max Loading = psf Proposed to Current Loading Ratio = Existing With PV Array 21.32 24.48 39.69 27.20 20.00 0.00 Existing With PV Array O.K. Gravity Loading with PV Array is not stressing the current framing system by more that 5% of the original configuration. Per Section 503.3 of 2022 California Existing Building Code the structure is allowed to remain unaltered for gravity loading 39.69 27.20 69%< 105% Page 5 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Wind Load Calculation Wind Loads - ASCE 7-16 Chapter 26 & 29 Width of the Building, B = ft (Approximate) V = mph Exposure = Average height of building, z = ft - avg (Approximate) ft (Refer ASCE 7-16, Table 26.11-1) α =Zg =ft (Refer ASCE 7-16, Table 26.11-1) Kh & Kz =2.01(z/Zg)^(2/α) = Kzt =(Refer ASCE 7-16, Equation 26.8-1) Kd =(Refer ASCE 7-16, Table 26.6.1) Ke =(Refer ASCE 7-16, Table 26.9-1) qh ='.00256 KzKztKdKeV² =psf (Refer ASCE 7-16, Section 26.10-1) Building Classification = Solar Panel Components and Cladding p C&C = qh(GCp)(ϒe)(ϒa)ASCE 7-16 Chapter 29.4.4 Module Length =in Module Width =in Area of Module =ft2 Roof Pitch =: Slope =degrees Gable Roof = ϒe= ϒa= (Refer ASCE 7-16, Figure 29.4-8) Minda Herman PE 08-08-2024 1200 zmin = 30 7 1 47.2 1 0.85 11.29 4.0 41.1 95 B 15 0.57 Enclosed 0.8 21.1 74 7° < θ ≤ 20° 1.5 12 18 Page 6 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Minda Herman PE 08-08-2024 Zone 1 Uplift External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf Zone 2 Uplift External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf All Zone Downward External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf Maximum Uplift Wind Pressure, p = psf Minimum Downward Wind Pressure, p =psf Wind Load Tributary Width =in (Max Spacing of fastners along Rails) Tributary Length =in (Half Panel Length) Tributary Area =ft2 Max Wind Downward (Wd) =lbs Max Wind Uplift (Wu) =lbs Dead Load Loads from Solar panel (Dead) PV Array Load =psf Tributary Area =ft2 Axial Load (Pd) =lbs Eccentricity (e) =in Distance between anchors (w) = in Moment due to eccentricity (Pd*e) =lbs-in Tensile load, D1 = (Pd/2 + Pd*e/w) = lbs Compressive load, D2 = (Pd*e/w - Pd/2) = lbs223.0 3.0 -260.0 6.20 0.95 229.4 -2.6 48 37 12.33 37.00 -35.21 -2 -27.088 -35.21 16.0 0.5 6.8 12.33 197.33 -434.3 Page 7 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Minda Herman PE 08-08-2024 Load Combinations [D1+0.6Wu] = lbs [D1+0.6Wd] = lbs [D2+0.6Wu] = lbs [D2+0.6Wd] = lbs [0.6D1+0.6Wu] = lbs [0.6D1+0.6Wd] = lbs [0.6D2+0.6Wu] = lbs [0.6D2+0.6Wd] = lbs Max pull out load on screw = lbs (Demand) Lag Screw / Bolt Connection Check (ASD) Lag Screw/Bolt Size = Cd =(Refer NDS Table 2.3.2) Embedment = in Grade of Wood = #2 (or better) G = Capacity = lb/in (Refer NDS Table 12.2A) Number of Screws in Tension = Prying Coefficient = Capacity of Fasteners = lb (Capacity) Demand (lb) Capacity (lb) DCR 520.6 1286 0.40 0.5 225 2 1.4 1286 1/4 1.6 2.5 (Measured from top of the framing member to tapered tip of lag screw, embeddment in sheathing and tapered tip of screw is not included ) DF -416.6 -37.6 -126.8 252.2 520.6 -520.6 -141.6 -37.6 341.4 Page 8 2704 W Camden Pl 9/26/2024 Wood Beam LIC# : KW-06014559, Build:20.24.06.04 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2023 DESCRIPTION:2x6 Rafters @ 24" o.c. (Wind Condition_Downward) (Strength Check) Project File: 2x6 joist @ 24 o.c_copy.ec6 Project Title: Engineer: Project ID: Project Descr: CODE REFERENCES Calculations per NDS 2018, IBC 2021, ASCE 7-16 Load Combination Set : ASCE 7-16 Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.2 900.0 900.0 1,350.0 625.0 1,600.0 580.0 180.0 575.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-16 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight NOT internally calculated and added Load for Span Number 1 Uniform Load : D = 0.010, Lr = 0.020, W = 0.0160 ksf, Tributary Width = 2.0 ft, (Existing Roof Load) Load for Span Number 2 Uniform Load : D = 0.010 ksf, Tributary Width = 2.0 ft, (Existing Roof Dead Load) Point Load : D = 0.0370, W = 0.1970 k @ 1.750 ft, (Solar Panel Load) Point Load : D = 0.0370, W = 0.1970 k @ 5.70 ft, (Solar Panel Load) Uniform Load : Lr = 0.020, W = 0.0160 ksf, Extent = 0.0 -->> 0.750 ft, Tributary Width = 2.0 ft, (Existing Wind & Roof Live Load) Uniform Load : Lr = 0.020, W = 0.0160 ksf, Extent = 12.60 -->> 14.0 ft, Tributary Width = 2.0 ft, (Existing Wind & Roof Live Load) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.827: 1 Load Combination +D+0.60W Span # where maximum occurs Span # 2 Location of maximum on span 5.709 ft 67.90 psi= = 2,152.80 psi 2x6Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+0.60W = = = 288.00 psi== Section used for this span 2x6 Maximum Shear Stress Ratio 0.236 : 1 2.000 ft= = 1,781.14 psi Maximum Deflection 128 >=128 152 Ratio =92 >=91 Max Downward Transient Deflection 0.768 in 218 Ratio =>=128 Max Upward Transient Deflection -0.371 in Ratio = Max Downward Total Deflection 1.104 in Ratio =>=91 Max Upward Total Deflection -0.513 in fb: Actual F'b fv: Actual F'v Span: 2 : W Only Span: 1 : W Only Span: 2 : +D+0.60W Span: 1 : +D+0.60W .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1.00Length = 2.0 ft 1 0.052 0.213 0.90 1.300 1.151.00 1.00 0.04 63.5 1,211.0 0.19 162.01.00 34.41.00 1.00Length = 14.0 ft 2 0.806 0.213 0.90 1.300 1.151.00 1.00 0.61 975.7 1,211.0 0.19 162.01.00 34.41.00 1.00+D+Lr 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 Page 9 2704 W Camden Pl 9/26/2024 Wood Beam LIC# : KW-06014559, Build:20.24.06.04 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2023 DESCRIPTION:2x6 Rafters @ 24" o.c. (Wind Condition_Downward) (Strength Check) Project File: 2x6 joist @ 24 o.c_copy.ec6 Project Title: Engineer: Project ID: Project Descr: Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu 1.00Length = 2.0 ft 1 0.113 0.171 1.25 1.300 1.151.00 1.00 0.12 190.4 1,681.9 0.21 225.01.00 38.41.00 1.00Length = 14.0 ft 2 0.561 0.171 1.25 1.300 1.151.00 1.00 0.60 944.3 1,681.9 0.21 225.01.00 38.41.00 1.00+D+0.750Lr 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.094 0.166 1.25 1.300 1.151.00 1.00 0.10 158.7 1,681.9 0.21 225.01.00 37.41.00 1.00Length = 14.0 ft 2 0.566 0.166 1.25 1.300 1.151.00 1.00 0.60 951.7 1,681.9 0.21 225.01.00 37.41.00 1.00+D+0.60W 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.058 0.236 1.60 1.300 1.151.00 1.00 0.08 124.4 2,152.8 0.37 288.01.00 67.91.00 1.00Length = 14.0 ft 2 0.827 0.236 1.60 1.300 1.151.00 1.00 1.12 1,781.1 2,152.8 0.37 288.01.00 67.91.00 1.00+D+0.750Lr+0.450W 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.095 0.217 1.60 1.300 1.151.00 1.00 0.13 204.4 2,152.8 0.34 288.01.00 62.51.00 1.00Length = 14.0 ft 2 0.720 0.217 1.60 1.300 1.151.00 1.00 0.98 1,549.6 2,152.8 0.34 288.01.00 62.51.00 1.00+D+0.450W 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.051 0.207 1.60 1.300 1.151.00 1.00 0.07 109.2 2,152.8 0.33 288.01.00 59.51.00 1.00Length = 14.0 ft 2 0.733 0.207 1.60 1.300 1.151.00 1.00 1.00 1,579.0 2,152.8 0.33 288.01.00 59.51.00 1.00+0.60D+0.60W 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.046 0.188 1.60 1.300 1.151.00 1.00 0.06 99.0 2,152.8 0.30 288.01.00 54.11.00 1.00Length = 14.0 ft 2 0.647 0.188 1.60 1.300 1.151.00 1.00 0.88 1,392.1 2,152.8 0.30 288.01.00 54.11.00 1.00+0.60D 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.018 0.072 1.60 1.300 1.151.00 1.00 0.02 38.1 2,152.8 0.11 288.01.00 20.71.00 1.00Length = 14.0 ft 2 0.272 0.072 1.60 1.300 1.151.00 1.00 0.37 585.4 2,152.8 0.11 288.01.00 20.71.00 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+0.60W10.0000 0.000 -0.5129 0.000 +D+0.60W 2 1.1045 6.804 0.0000 0.000 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 0.498 0.258 Max Upward from Load Combinations 0.498 0.258 Max Upward from Load Cases 0.383 0.157 D Only 0.237 0.157 +D+Lr 0.355 0.205 +D+0.750Lr 0.325 0.193 +D+0.60W 0.467 0.243 +D+0.750Lr+0.450W 0.498 0.258 +D+0.450W 0.410 0.221 +0.60D+0.60W 0.372 0.180 +0.60D 0.142 0.094 Lr Only 0.118 0.048 W Only 0.383 0.143 Page 10 2704 W Camden Pl 9/26/2024 Wood Beam LIC# : KW-06014559, Build:20.24.06.04 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2023 DESCRIPTION:2x6 Rafters @ 24" o.c. (Wind Condition_Uplift) (Strength Check) Project File: 2x6 joist @ 24 o.c_copy.ec6 Project Title: Engineer: Project ID: Project Descr: CODE REFERENCES Calculations per NDS 2018, IBC 2021, ASCE 7-16 Load Combination Set : ASCE 7-16 Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.2 900.0 900.0 1,350.0 625.0 1,600.0 580.0 180.0 575.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-16 .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight NOT internally calculated and added Load for Span Number 1 Uniform Load : D = 0.010, Lr = 0.020, W = -0.0350 ksf, Tributary Width = 2.0 ft, (Existing Roof Load) Load for Span Number 2 Uniform Load : D = 0.010 ksf, Tributary Width = 2.0 ft, (Existing Roof Dead Load) Point Load : D = 0.0370, W = -0.4340 k @ 1.750 ft, (Solar Panel Load) Point Load : D = 0.0370, W = -0.4340 k @ 5.70 ft, (Solar Panel Load) Uniform Load : Lr = 0.020, W = -0.0350 ksf, Extent = 0.0 -->> 0.750 ft, Tributary Width = 2.0 ft, (Existing Wind & Roof Live Load) Uniform Load : Lr = 0.020, W = -0.0350 ksf, Extent = 12.60 -->> 14.0 ft, Tributary Width = 2.0 ft, (Existing Wind & Roof Live Load) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.806: 1 Load Combination D Only Span # where maximum occurs Span # 2 Location of maximum on span 6.179 ft 34.43 psi= = 1,210.95 psi 2x6Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination D Only = = = 162.00 psi== Section used for this span 2x6 Maximum Shear Stress Ratio 0.213 : 1 2.000 ft= = 975.72 psi Maximum Deflection 99 >=58 150 Ratio =164 >=120 Max Downward Transient Deflection 0.819 in 58 Ratio =>=58 Max Upward Transient Deflection -1.692 in Ratio = Max Downward Total Deflection 0.317 in Ratio =>=120 Max Upward Total Deflection -0.290 in fb: Actual F'b fv: Actual F'v Span: 1 : W Only Span: 2 : W Only Span: 1 : +0.60D+0.60W Span: 1 : D Only .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1.00Length = 2.0 ft 1 0.052 0.213 0.90 1.300 1.151.00 1.00 0.04 63.5 1,211.0 0.19 162.01.00 34.41.00 1.00Length = 14.0 ft 2 0.806 0.213 0.90 1.300 1.151.00 1.00 0.61 975.7 1,211.0 0.19 162.01.00 34.41.00 1.00+D+Lr 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 Page 11 2704 W Camden Pl 9/26/2024 Wood Beam LIC# : KW-06014559, Build:20.24.06.04 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2023 DESCRIPTION:2x6 Rafters @ 24" o.c. (Wind Condition_Uplift) (Strength Check) Project File: 2x6 joist @ 24 o.c_copy.ec6 Project Title: Engineer: Project ID: Project Descr: Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu 1.00Length = 2.0 ft 1 0.113 0.171 1.25 1.300 1.151.00 1.00 0.12 190.4 1,681.9 0.21 225.01.00 38.41.00 1.00Length = 14.0 ft 2 0.561 0.171 1.25 1.300 1.151.00 1.00 0.60 944.3 1,681.9 0.21 225.01.00 38.41.00 1.00+D+0.750Lr 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.094 0.166 1.25 1.300 1.151.00 1.00 0.10 158.7 1,681.9 0.21 225.01.00 37.41.00 1.00Length = 14.0 ft 2 0.566 0.166 1.25 1.300 1.151.00 1.00 0.60 951.7 1,681.9 0.21 225.01.00 37.41.00 1.00+D+0.60W 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.032 0.136 1.60 1.300 1.151.00 1.00 0.04 69.8 2,152.8 0.22 288.01.00 39.31.00 1.00Length = 14.0 ft 2 0.376 0.144 1.60 1.300 1.151.00 1.00 0.51 809.2 2,152.8 0.23 288.01.00 41.41.00 1.00+D+0.750Lr+0.450W 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.027 0.057 1.60 1.300 1.151.00 1.00 0.04 58.7 2,152.8 0.09 288.01.00 16.51.00 1.00Length = 14.0 ft 2 0.183 0.078 1.60 1.300 1.151.00 1.00 0.25 393.2 2,152.8 0.12 288.01.00 22.61.00 1.00+D+0.450W 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.017 0.072 1.60 1.300 1.151.00 1.00 0.02 36.5 2,152.8 0.11 288.01.00 20.91.00 1.00Length = 14.0 ft 2 0.169 0.082 1.60 1.300 1.151.00 1.00 0.23 363.8 2,152.8 0.13 288.01.00 23.61.00 1.00+0.60D+0.60W 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.044 0.184 1.60 1.300 1.151.00 1.00 0.06 95.2 2,152.8 0.29 288.01.00 53.11.00 1.00Length = 14.0 ft 2 0.557 0.185 1.60 1.300 1.151.00 1.00 0.76 1,198.2 2,152.8 0.29 288.01.00 53.21.00 1.00+0.60D 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 2.0 ft 1 0.018 0.072 1.60 1.300 1.151.00 1.00 0.02 38.1 2,152.8 0.11 288.01.00 20.71.00 1.00Length = 14.0 ft 2 0.272 0.072 1.60 1.300 1.151.00 1.00 0.37 585.4 2,152.8 0.11 288.01.00 20.71.00 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections W Only 1 0.8185 0.000 0.0000 0.000 W Only20.0000 0.000 -1.6920 6.570 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 0.355 0.205 Max Upward from Load Combinations 0.355 0.205 Max Upward from Load Cases 0.237 0.157 Max Downward from all Load Conditio -0.843 -0.315 Max Downward from Load Combinations -0.364 -0.095 Max Downward from Load Cases (Resis -0.843 -0.315 D Only 0.237 0.157 +D+Lr 0.355 0.205 +D+0.750Lr 0.325 0.193 +D+0.60W -0.269 -0.032 +D+0.750Lr+0.450W -0.054 0.051 +D+0.450W -0.142 0.015 +0.60D+0.60W -0.364 -0.095 +0.60D 0.142 0.094 Lr Only 0.118 0.048 W Only -0.843 -0.315 Page 12 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Seismic Ground Motion Values Minda Herman PE 08-08-2024 Page 13 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Seismic Design Force Seismic Loads - ASCE 7-16 Chapter 13 Seismic Force Component Amplification Factor, ap= (Refer ASCE 7-16, Table 13.6 -1) Overstrength Factor, Ωo = (Refer ASCE 7-16, Table 13.6 -1) Component Importance Factor, Ip= SDS = Average roof height of structure,h =ft z/h =z/h should not exceed 1 Frame Weight Wp = psf Seismic Design Force on Solar framing structure Horizontal Seismic Design Load, Fp Max Fp =1.6 x SDS x Ip X Wp =psf Min Fp =0.3 x SDS x Ip X Wp =psf Horizontal Seismic Design Load Fp =psf Vertical Seismic Design Load Fv =psf Seismic Coefficients for Mechanical and Electrical components = Component Response Modification Factor, Rp= 1.50 Minda Herman PE 08-08-2024 12 Other mechanical or electrical components. (Refer ASCE 7-16, Table 13.6 -1) Height in structure at point of attachment, z = 15 ft 1.00 2.00 1.04 1.00 FP = ((0.4 x ap x SDS x Wp)/ (Rp / Ip)) x ((1+2(z/h)) =2.63 psf 15 1 2.63 5.27 0.99 3.16 0.66 Page 14 2704 W Camden Pl 9/26/2024 Project : Project Number: By : Date : Minda Herman PE 08-08-2024 Check for Increase in overall seismic loads Module Area =ft2 Number of Modules = Total Array Area =ft2 Array Load = psf Number of Existing Modules = Existing Array Area =ft2 Total Array Wt. = lb Total Roof Area =ft2 DL of Roof = psf Total Wt. of Roof = lb Increase in Seismic Wt. = < 10% Conservatively the Wt. of the Walls tributary to the roof is not included. Seismic weight increase is less than 10% and no seismic retrofit or evaluation of existing lateral system is required per Section 503.4 of 2022 CEBC. 21.1 10 211.21 2379 3.00 633.63 0 0.00 21.32 50713 1.2% Page 15 2704 W Camden Pl 9/26/2024 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024 2704 W Camden Pl 9/26/2024