HomeMy WebLinkAbout2309 N Spurgeon St - PlanGENERAL NOTES
PHOTOVOLTAIC NOTES
AERIAL VIEW
VICINITY MAP
PV-0
COVER PAGE
PROJECT DESCRIPTION:SCOPE:SCOPE:
DATE:11/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
SOLAR MODULES:
NEW
SYSTEM SIZE:
DC STC: 6.56 kW
AC CEC: 5.93 kW
INVERTERS OUTPUT: AC: 11.40 kW
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703.
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS.
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER OUTAGE.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE
PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED.
8. INVERTER IS EQUIPPED W/ INTEGRATED GFDI, THUS PROVIDING GROUND FAULT PROTECTION.
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED.
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT.
11. CONDUITS SHOULD BE PAINTED TO MATCH EXISTING ROOF AND WALL COLORS.
12. ALL WORK SHALL BE IN ACCORD WITH THE 2022 CBC, 2022 CEC AND 2022 NEC WITH SPECIAL EMPHASIS ON ARTICLE 690.
13. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING MEANS AS PER 230.82(6).
14. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING AND BONDING BETWEEN AC AND DC SYSTEMS
SIZED AS PER SEC 250.122
15. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122.
16. PER ART NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER.
SHEET INDEX
PV-2
PV-3
PV-4
D-1
D-2
D-3
D-4
D-5
D-6
D-7
SITE PLAN
THREE LINE DIAGRAM
DESCRIPTION
PV-0 COVER PAGE
PV-1
NOTES:
ALL ELECTRICAL WORK TO BE INSTALLED BY A QUALIFIED AND LICENSED
ELECTRICAL CONTRACTOR.
ALL SOLAR MODULES SHALL BE UL LISTED 1703 & CEC APPROVED. ALL
INVERTERS SHALL BE UL LISTED 1741 CERTIFIED & CEC APPROVED. ALL
ELECTRICAL COMPONENTS AND MATERIALS SHALL BE LISTED FOR IT'S
PURPOSE AND INSTALLED IN A WORKMAN LIKE MANNER. ALL OUTDOOR
EQUIPMENT SHALL MEET APPROPRIATE NEMA STANDARDS.
THE ELECTRICAL CONTRACTOR IS ADVISED THAT ALL DRAWINGS AND
COMPONENT MANUALS ARE TO BE UNDERSTOOD PRIOR TO INSTALLATION.
THE CONTRACTOR IS ADVISED TO HAVE ALL SWITCHES IN THE OFF POSITION
AND FUSES REMOVED PRIOR TO INSTALLATION OF FUSE-BEARING
COMPONENTS.
THIS SYSTEM IS INTENDED TO BE OPERATED IN PARALLEL WITH THE UTILITY
SERVICE PROVIDER. ANTI-ISLANDING PROTECTION IS A REQUIREMENT OF UL
1741 AND IS INTENDED TO PREVENT THE OPERATION OF THE PV SYSTEM
WHEN THE UTILITY GRID IS NOT OPERATIONAL.
PERMISSION TO OPERATE THE SYSTEM IS NOT AUTHORIZED UNTIL FINAL
INSPECTIONS AND APPROVALS ARE OBTAINED FROM THE LOCAL AUTHORITY
HAVING JURISDICTION AND THE LOCAL UTILITY SERVICE PROVIDER.
THE METHOD OF ATTACHMENT CREATES A UNIFIED STRUCTURE TO MEET
DEAD LOAD, WIND LOAD, AND SEISMIC REQUIREMENTS. SOLAR MODULES
WILL BE SECURED TO THE EXISTING ROOF AS SPECIFIED ON THE
STRUCTURAL SHEETS. EXISTING ROOF EQUIPMENT WILL NOT BE EFFECTED
BY THE PV SYSTEM. ALL STRUCTURAL DESIGN AND INSTALLATION
COMPONENTS ARE THE RESPONSIBILITY OF OTHERS AND OUTSIDE THE
SCOPE OF THIS DOCUMENT.
ALL FASTENERS SHALL BE CORROSION RESISTANT APPROPRIATE FOR SITE
CONDITIONS. CONNECTORS SHALL BE TORQUED PER DEVICE LISTING OR
ENGINEERING RECOMMENDATIONS.
ALL ROOFING REPAIR MUST MAINTAIN EXISTING CLASS AND TYPE OF ROOF
AND ALL WORK SHALL BE IN ACCORDANCE WITH THE ROOF IN
MANUFACTURER'S INSTALLATION REQUIREMENTS.
EXISTING:
MSP BUS:
MAIN BREAKER:
1P, 3W, 120/240V
200A
200A
ELECTRICAL INFORMATION
THE FOLLOWING PLANS INCLUDES INSTALLATION OF TWO TESLA POWERWALL 3 LITIUM-ION AC BATTERIES.
EACH BATTERY IS SINGLE ASSEMBLY WITH INVERTER. THESE BATTERIES WILL BE INSTALLED OUTSIDE TO
EXISTING STUDS AND HAVE A CAPACITY OF 13.5 KWH. WITH TOTAL CAPACITY OF 27.0 KWH
POWERWALL 3 MOUNTING DETAILS
LOAD CALCULATION BSP
SYSTEM CONFIGURATION
(2) 11.5 kW TESLA POWERWALL 3 1707000-xx-y (120/240V)
(ALL-IN-ONE SOLAR & BATTERY SYSTEM (DC-COUPLED SOLAR))
APPLICABLE CODES
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA RESIDENTIAL CODE
2022 NATIONAL ELECTRICAL CODE
2022 CALIFORNIA FIRE CODE
ALL OTHER ORDINANCE ADOPTED BY THE
LOCAL GOVERNING AGENCIES
EQUIPMENT ELEVATION
INVERTER & ESS:
POWERWALL 3 MOUNTING DETAILS
POWERWALL 3 MOUNTING DETAILS
NOTE: SMOKE ALARMS AND CARBON MONOXIDE ALARMS SHALL
BE PROVIDED FOR THE DWELLING PER CRC R314 AND R315.
TESLA GATEWAY DATA SHEET
(19) JA SOLAR 395W (JAM54S31-395/MR)EXISTING
EXISTING
NEW
INVERTER:
(1) TIGO 11.4KW (TSI-11.4K-US) (120/240V)
SOLAR MODULES: (16) SOLAREVER 410W (SE-182*91-410M-108)
INVERTER:
(1) ABB 3.6KW (PVI-3.6-OUTD-S-US-Z-A) (120/240V)
INVERTER & ESS DATA SHEET
EXISTING
SYSTEM SIZE:
DC STC: 7.51 kW
AC CEC: 6.73 kW
INVERTERS OUTPUT: AC: 3.60 kW
NEW
NEW
ELECTRICAL CALCULATION
ATTACHMENT LAYOUT
STRUCTURAL DETAIL
CODE REQUIRED SIGNAGE
PV-5
PV-6
BATTERY REQUIRED SIGNAGEPV-7
PV-8
MODULE DATA SHEET
RACKING DATA SHEET
ATTACHMENT DATA SHEET
GROUNDING SPECS
RACKING CERTIFICATION
RACKING DETAILS
INVERTER DATA SHEET
OPTIMIZER DATA SHEET
D-8
D-9
D-10
D-11
D-12
D-13
D-14
D-15
RSD DEVICE DATA SHEETD-16
BLDG#101121197
ELEC#20184262
APPROVALS
ELEC - MSmith
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:09/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
ROOF PLAN
PV-1
SCALE
0 5 20ft10
ELECTRICAL EQUIPMENT INFORMATION
#Quantity Description
- 19 (E)JA SOLAR 395W (JAM54S31-395/MR) Modules
- 19 (E) TIGO TS4-A-O Optimizers
-16 (N)Solarever 410W (SE-182*91-410M-108) Modules
-16 (N) TIGO TS4-A-O Optimizers
1 1 (N) Junction-Box
2 1 (E) ABB 3.6KW (PVI-3.6-OUTD-S-US-Z-A) (120/240V) Inverter
3 1 (E)30A Non-Fused AC Disconnect (120/240V)
4 1 (N) TIGO 11.4KW (TSI-11.4K-US) (120/240V) Inverter
5 1 (N)60A Non-Fused AC Disconnect (120/240V)
6 2 (N) 11.5 kW TESLA POWERWALL 3 1707000-xx-y (120/240V)
(All-In-One Solar & Battery System (DC-Coupled Solar)) (Page D-1)
7 2 (N)60A Non-Fused AC Disconnect (120/240V)
8 1 (N) Tesla Backup Gateway 2 (120/240V) (Page D-2)
9 1 (N)200A Back-up Load Panel (120/240V)
10 1 (E)200A Main Service Panel (120/240V)
Pu
b
l
i
c
S
i
d
e
w
a
l
k
N
S
p
u
r
g
e
o
n
S
t
Driveway
98'
62'
Existing Solar System
Existing Solar System
Gate
Gate
[2]
[3]
[4]
[5]
[8]
[9]
[6]
[7]
[10]
Solar Array 1
5 Solarever 410W
5 TIGO Optimizers
Pitch: 20 Deg
Orientation: 270 Deg
[1]
Solar Array 2
7 Solarever 410W
7 TIGO Optimizers
Pitch: 20 Deg
Orientation: 270 Deg
Solar Array 3
4 Solarever 410W
4 TIGO Optimizers
Pitch: 20 Deg
Orientation: 90 Deg
A A
A
A
A
A
A
A
B
B
B
B
B
B
B
B
STRING CONFIGURATION
A 8 MODULES
B 8 MODULES
FIRE SETBACK (36'' TYP)
FIRE SETBACK (18'' TYP)
Roof access is not located in areas that
require placement of ground ladders over
exterior wall openings CRC R331.4.1.
PROPERTY LINE
ROOF ACCESS
ROOF ACCESS
(N) Number of modules 16
(E) Number of modules 19
Module area (sq.ft)21
Total Module area (sq.ft)735
Total area of roof (sq.ft)2300
Total area of array
covered in the roof (%)32.0
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-8
RACKING DETAILS
2309 N Spurgeon
St12/11/2024
ATTACHMENT LAYOUT
SCOPE:SCOPE:
DATE:09/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
PV-4
SOLAR ARRAY MOUNTING RAIL TYPE: UNIRAC STANDARD RAIL
SOLAR ARRAY ATTACHMENT TYPE: UNIRAC FLASHLOC
ATTACHMENT SPACING: 72'' MAX
FRAMING: TRUSSES 2'' x 4'' @ 24'' O.C
FINISHED ROOF SURFACE IS ONE LAYER OF COMPOSITION SHINGLE.
WIND SPEED: 110 mph FOR EXPOSURE C
SNOW LOAD: 0 psf
72''
24''
2309 N Spurgeon
St12/11/2024
STRUCTURAL DETAIL
SCOPE:SCOPE:
DATE:09/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
PV-5
WEIGHT LOAD CALCULATION
MODULE WEIGHT(LBS):45
NUMBER OF MODULES:16
OPTIMIZER WEIGHT(LBS):1.08
NUMBER OF OPTIMIZERS:16
TOTAL WEIGHT OF MODULES(LBS):720
SOLAR RACKING WEIGHT(LBS):144
TOTAL RSD WEIGHT(LBS):17
TOTAL SYSTEM WEIGHT(LBS):881
NUMBER OF ATTACHMENTS:34
LOADING PER ATTACHMENT(LBS):25.9
SOLAR ARRAY DEAD LOAD(LBS/FT2):2.66
TOTAL SOLAR AREA(SQFT):331
TOTAL ROOF AREA(SQFT):2300
TOTAL AREA OF ARRAY COVERED IN THE ROOF (%)14.4
MID-CLAMP AND
END-CLAMP ANATOMY
ROOF FRAMING DETAILS
MODULE TO MODULE
& MODULE TO RAIL
T-BOLT
GROUNDING LUG
RAIL TO RAIL
UNIVERSAL AF
END CLAMP
15 8"
UNIVERSAL AF
MID CLAMP
11 2"
13 16"11 4"
30mm to 46mm
MODULE FRAME 30mm to 46mm
MODULE FRAME
1 2"
UNIVERSAL
MID CLAMP
UNIVERSAL
END CLAMP
BONDING SPLICE BAR
1 1 2"
15 16"
4"
5/16"-18 TYPE F THREAD
CUTTING SCREWS INCLUDED
ATTACHMENT DETAIL- UNIRAC FLASHLOC
NOTE:ROOF ATTACHMENTS WILL HAVE A
MINIMUM OF 2.5" EMBEDMENT IN RAFTER.
NOTE:STANDOFF LAG BOLTS ARE
STAINLESS STEEL (SS)
SCALE:NTS
6" MAX
UNIRAC STANDARD
RAIL-168"
PV MODULES
GROUNDING & END/MID
CLAMP
SS SERRATED T-BOLT
SS SERRATED FLANGE NUT
FLASHLOC BASE
5/16" x 4" SS LAG BOLT
W/ SS EPDM BONDED WASHER
WITH MIN
2 1/2" THREAD EMBEDMENT
5/16" X 3.5" LAG SCREW
1 BOLT PER PENETRATION
MODULE
LOAD BEARING WALL SCALE:NTS
20o
2''x4'' TRUSSES @24'' O.C.
2''x6'' BLOCKING
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:09/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
EQUIPMENT ELEVATION
PV-8
Tesla Powerwall 3
BATTERY
DISCONNECT
Min 3'
BACKUP LOADS
PANEL TESLA GATEWAY
SOLAR INVERTER
SOLAR DISCONNECT
SERVICE POINT &
UTILITY METERING
(E) SOLAR INVERTER
(E) SOLAR DISCONNECT
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:11/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
PV-2
THREE LINE DIAGRAM
NOTE: Photovoltaic system is rapid shut down ready
1 2 9
INV
G N L2 L1
EXISTING CONDUIT
EXISTING ABB 3.6KW
(PVI-3.6-OUTD-S-US-Z-A)
INVERTER
EXISTING
3/4'' EMT CONDUIT
(3) THWN-2, #10 (L1, L2, N)
(1) #8, EGC CU
1 2 10
TESLA
POWERWALL
3
L1
L2
N
GG
-
+
-
+
TESLA
BATTERY
TESLA
POWERWALL
3
L1
L2
N
GG
-
+
-
+
TESLA
BATTERY
NEW
3/4'' EMT CONDUIT
(3) THWN-2, #6 (L1, L2, N)
(1) #8, EGC CU
L1
L2
G
L1
L2
G
N N
8
NEW
3/4'' EMT CONDUIT
(3) THWN-2, #6 (L1, L2, N)
(1) #8, EGC CU
L1
L2
G
L1
L2
G
N N
N
G
L2L1
L2
L1
CTRL
L2
L1
L1
L1
L2
L1
L2
L1
L2
L1
L1
L1
L2
L2
L2
N
G
L2
N
G
NEW 60A
BREAKER
NOTE: AFCI PROTECTION IS REQUIRED
FOR CIRCUITS RELOCATED MORE
THAN 6 FT. PER SECT. 210.12(B).
NEW WIRING
2'' EMT CONDUIT
(3) THWN-2, #3/0 (L1, L2, N)
(1) #4, EGC CU
NEW 200A
OCPD
L2
L1
L2
L1
L1
L2
G
L1
L2
G
N N
1 2 8
INV
G N L2 L1
EXISTING SOLAR SYSTEM
(19) JA SOLAR 395W MODULES
TIGO 11.4KW
(TSI-11.4K-US)
INVERTER
1 2 8
L1
L2
G
L1
L2
G
N N
1
2
6
4
7
5
8
9
9
10
11
INSTALL 2P
20A CB(PV)
FURTHEST FROM
MAIN FEEDER CB
8' Minimum Embedment Rod at 6'
From Equipment Ground Conductor Unless
Existing Ground is UFER.
N
G
M
L1
L1
N L2
N L2
N
L2
L1
L1
L2
EXISTING 200A
CENTER FEED OCPD
TO UTILITY GRID
NEW 2P 200A
12
NOTE: 705.12.(B)(3)(3)
connection method will be used.
A
B
ELECTRICAL EQUIPMENT INFORMATION
#Quantity Description
-19 (E) JA SOLAR 395W (JAM54S31-395/MR) Modules
1 16 (N) Solarever 410W (SE-182*91-410M-108) Modules
2 16 (N) TIGO TS4-A-O Optimizers
3 1 (N) Junction-Box
4 1 (E) ABB 3.6KW (PVI-3.6-OUTD-S-US-Z-A) (120/240V) Inverter
5 1 (E) 30A Non-Fused AC Disconnect (120/240V)
6 1 (N) TIGO 11.4KW (TSI-11.4K-US) (120/240V) Inverter
7 1 (N) 60A Non-Fused AC Disconnect (120/240V)
8 2 (N) 11.5 kW TESLA POWERWALL 3 1707000-xx-y (120/240V)
(All-In-One Solar & Battery System (DC-Coupled Solar)) (Page D-1)
9 2 (N) 60A Non-Fused AC Disconnect (120/240V)
10 1 (N) Tesla Backup Gateway 2 (120/240V) (Page D-2)
11 1 (N) 200A Back-up Load Panel (120/240V)
12 1 (E) 200A Main Service Panel (120/240V)
3
J/B
C C
STRINGS A,B
(8) SOLAREVER 410W MODULES
(8) TIGO TS4-A-O OPTIMIZERS STRING CALCULATION
Number of
Modules
Module
VOC Coefficient Total Inp.
Voltage
Max Inp.
Voltage
8 37.12 1.12 332.6V <=600V
[1]
[2]
[5]
EXISTING ABB RAPID
SHUTDOWN DEVICE
SEE PAGE D-16
[6]
Rerouted circuits will be 10 x #8 wires, and 33 x #10 wires
Multiple conduit will be used 1 x 1 1/4'' EMT and 3 x 1'' EMT Conduits
[7]
2309 N Spurgeon
St12/11/2024
1.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER CEC 310.10(D).
2.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER CEC310.10(C).
3.MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%.
4.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED. 5.BREAKER/FUSE SIZES CONFORMS TO CEC
240.6 CODE SECTION.
6.AC GROUNDING ELECTRODE CONDUCTOR SIZED PER CEC 250.66.
7.AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON CEC 690.31(A).
8.AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON CEC 310.15(B)(2).
9.MAX. SYSTEM VOLTAGE CORRECTION IS PER CEC 690.7.
10.CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE CEC 310.15(B)(16).
SCOPE:SCOPE:
DATE:11/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
PV-3
ELECTRICAL CALCULATION
WIRE SIZE CALCULATION
WIRE TAG#WIRE TYPE
AND SIZE
QUANTITY OF
WIRES
GROUNDING
SIZE
WIRE
AMPACITY TEMPERATURE CONDUIT TYPE ABOVE ROOF TEMP. DERATE
FACTOR ADJUSTING FACTOR
CORRECTED
CONDUCTOR
AMP
CURRENT
AMP
A PV WIRE #10 2 #6, BARE CU 40 A 90°Free in the air >3.5 - 12''0.71 1 N/A 28.4 18.8
B THWN-2 #10
2x(DC+,DC-)4 #8, EGC CU 40 A 90°3/4'' EMT >3.5 - 12''0.71 0.8 4 Thru 6 Wires 22.7 18.8
C THWN-2 #6
(L1,L2,N)3 #8, EGC CU 75 A 90°3/4'' EMT ALONG THE
WALL 0.91 1 N/A 68.3 60.0
NEW PV SYSTEM OUTPUT CALCULATION
1 TIGO 11.4KW (TSI-11.4K-US)97.5 %
16
Solarever 410W (SE-182*91-410M-108)410.0 W
Pmax (PTC Rating)380.0 W
1 Inverter Output 11400 W
Max DC Output 16 * 410.0 6.56 KW
Max AC Output 16 * 380.0 * 0.975 5.93 KW
Inverters Output:1 * 11400.0 11.40 KW
WIRE AMPACITY DC
#RSD
AMP
CONSIDER
CONTINUOUS
COEFFICIENT
CURRENT
AMP
A 15 1.25 18.8
B 15 1.25 18.8
WIRE AMPACITY AC
#
INVERTER
MAX
OUTPUT
CURRENT
QUANTITY
CONSIDER
CONTINUOUS
COEFFICIENT
CURRENT
AMP
C 48.0 1 1.25 60.0
EXISTING PV SYSTEM OUTPUT CALCULATION
1 ABB 3.6KW (PVI-3.6-OUTD-S-US-Z-A)96.0 %
19
JA SOLAR 395W (JAM54S31-395/MR)395.0 W
Pmax (PTC Rating)368.7 W
1 Inverter Output 3600 W
Max DC Output 19 * 395.0 7.51 KW
Max AC Output 19 * 368.7 * 0.960 6.73 KW
Inverters Output:1 * 3600.0 3.60 KW
PANEL SCHEDULE
BREAKER
AMP PHOLES AMOUNT DESCRIPTION TYPE
20 1 1 Light Single
20 1 1 Bedroom Light Single
20 1 4 Kitchen Light Multi Wire Circuit
20 1 4 Kitchen Plug Multi Wire Circuit
30 2 1 Dryer -
40 2 1 AC Unit -
30 2 1 AC Unit -
20 1 1 El. Plugs Multi Wire Circuit
20 1 1 Washer Multi Wire Circuit
20 1 1 Garage Multi Wire Circuit
15 1 2 1st Floor Lights Multi Wire Circuit
20 1 2 1st Floor Plugs Multi Wire Circuit
50 2 1 EV Charger -
20 1 1 Bathroom+Bedroom Switch Multi Wire Circuit
50 2 1 SPA -
[3]
Note: All multi-wire circuits to be bundled with a single neutral.
[4]
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:11/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
PV-6
CODE REQUIRED SIGNAGE
CAUTION
MULTIPLE SOURCES OF POWER
PHOTOVOLTAIC ARRAY
14
METER
MAIN SERVICE
PANEL
7
9
12
13
AC
DISCONNECT
* if applicable
7
SUB-PANEL
* if applicable
7
9
81110
7
9
6
PV SUB-PANEL
* if applicable
81110
INVERTER
*if applicable
3
INTEGRATED
DC DISCONNECT
4 5
J BOX
1 2
8
10
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT
DOWN PV SYSTEM AND
REDUCE SHOCK
HAZARD IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
1
(TO BE LOCATED ON
SUB-PANEL ONLY
WHEN SUB-PANEL IS
DEDICATED FOR PV ONLY)
PV SUB-PANEL ONLY
CAUTION
AUTHORIZED SOLAR
PERSONNAL ONLY!
WARNING!
ELECTRIC SHOCK HAZARD.
IF GROUND FAULT IS INDICATED,
NORMALLY GROUNDED
CONDUCTORS MAY BE
UNGROUNDED AND ENERGIZED.
RAPID SHUT DOWN SWITCH
FOR SOLAR PV SYSTEM
705.12 (D)(3)
CAUTION
DUAL POWER SOURCE SECOND
SOURCE IS PHOTOVOLTAIC SYSTEM
AC DISCONNECT
AC PHOTOVOLTAIC POWER SOURCE
RATED AC OUTPUT CURRENT: 48.0 A MAX
NOMINAL AC OPERATING VOLTAGE: 240 Vac
THIS PANEL FED BY
MULTIPLE SOURCES
(UTILITY & SOLAR)
WARNING!
ELECTRIC SHOCK HAZARD.
TERMINALS ON BOTH THE LINE AND
LOAD SIDES MAY BE ENERGIZED IN
THE OPEN POSITION.
ALL SIGNAGE/LABELS SHALL BE IN THE FOLLOWING FORMAT:
1. WHITE LETTERING ON A RED BACKGROUND AND WEATHER RESISTANT
2. MINIMUM 3/8" LETTER HEIGHT
3. ALL LETTERS SHALL BE CAPITALIZED
4. ARIAL OR SIMILAR FONT, NON-BOLD
5. SHALL BE IN ACCORDANCE WITH APPROPRIATE SECTIONS,
TABLES AND ARTICLES OF THE NEC, IFC.
(STICKER TO BE LOCATED ON CONDUIT WITH DC CURRENT EVERY 4'
HORIZONTALLY OR 10' VERTICALLY AND 1' FROM EACH SIDE OF A BEND)
WARNING: PHOTOVOLTAIC POWER SOURCE2
14
3 4
5
6 7
(STICKER LOCATED
INSIDE PANEL
NEXT TO SOLAR BREAKER)
(STICKER LOCATED INSIDE PANEL
BELOW PV BREAKER)
PV LOAD CENTER SIZED FOR PV
BREAKERS ONLY OR RENDERED UNABLE
TO ACCEPT ANY ADDITIONAL LOADS.
SOLAR
WARNING
INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE
9
10
11
8
(STICKER LOCATED
ON THE PV SUB PANEL)
12 13
15
TRI POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
THIRD SOURCE IS ENERGY STORAGE SYSTEM
15
PLAQUES SHALL BE METAL OR PLASTIC, WITH ENGRAVED OR MACHINE PRINTED
LETTERS, OR ELECTRO-PHOTO PLATING, IN A CONTRASTING COLOR TO THE
PLAQUE. PLAQUE SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH
POP-RIVETS OR SCREWS.
DC DISCONNECT
DC PHOTOVOLTAIC POWER SOURCE
RATED MAX POWER POINT CURRENT- 13.08 AMPS
RATED MAX POWER POINT VOLTAGE- 31.35 VOLTS
MAXIMUM SYSTEM VOLTAGE- 41.57 VOLTS
SHORT CIRCUIT CURRENT- 11.26 AMPS
N
S
p
u
r
g
e
o
n
S
t
TESLA BATTERY
BATTERY DISCONNECT
SERVICE POINT
& UTILITY METERING
SOLAR INVERTER
SOLAR DISCONNECT
SOLAR INVERTER
SOLAR DISCONNECT
CEC 705.10
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:09/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
PV-7
1
2
3
WARNING!
THIS EQUIPMENT FED BY MULTIPLE SOURCES.
TOTAL RATING OF ALL OVERCURRENT DEVICES,
EXCLUDING MAIN SUPPLY OVERCURRENT DEVICES
SHALL NOT EXCEED AMPACITY OF BUSBAR.
REQ'D BY: NEC 705.12(B)(2)(3)(b)
LABEL LOCATION:
BATTERY BREAKERS
REQ'D BY: NEC 705.12(B)(2)(3)(b)
LABEL LOCATION:
PV BREAKERS
4 FIRST SOURCE IS UTILITY ELECTRICAL GRID
SECOND SOURCE IS AC BATTERY
THIRD SOURCE IS PV INVERTER
CAUTION-TRI POWER SOURCE
REQ'D BY: NEC 705.10
LABEL LOCATION:
SUB PANEL OR BACKUP LOADS PANEL, BATTERY,
INVERTER OUTPUT PANEL, MAIN SERVICE PANEL,
METER/MAIN, AND PV AC DISCONNECT
5 NOMINAL ESS VOLTAGE:
MAX SHORT-CIRCUIT CURRENT:
ASSOCIATED CLEARING TIME:
DATE CALCULATION WAS PERFORMED:
WARNING ARC FLASH & SHOCK HAZARD
240V
48.0A
60ms
09/19/2024
LABEL LOCATION:
BATTERY DISCONNECT
6 DO NOT ADD
LOADS
REQ'D BY: NEC 705.10
LABEL LOCATION:
SUB PANEL OR BACKUP LOADS PANEL, BATTERY,
INVERTER OUTPUT PANEL, MAIN SERVICE PANEL,
METER/MAIN, AND PV AC DISCONNECT
PLACARDS NOTES
1. CEC ARTICLES 690 AND 705 AND CRC SECTION R331 MARKINGS SHOW HEREON
2. ALL MARKINGS SHALL CONSIST OF THE FOLLOWING:
A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR MACHINE PRINTED LETTERS OR
B. RED BACKGROUND COLOR WITH WHITE TEXT AND LINE WORK
C. ARIAL FONT.
3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN THE LOCATIONS SPECIFIED.
4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT USING POP-RIVETS OR SCREWS.
5. THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT WHERE IT IS INSTALLED.
6. WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD APPLIED LABELS, WARNINGS AND MARKINGS
SHOULD COMPLY WITH ANSI Z535.4 [NEC 110.21(8) FIELD MARKING].
7. ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY ADHERED. VINYL SIGNS SHALL BE
WEATHER RESISTANT [IFC 605.11.1.3]
BATTERY DISCONNECT
DO NOT RELOCATE
THIS OVERCURRENT
DEVICE
PV SOLAR BREAKER
DO NOT RELOCATE
THIS OVERCURRENT
DEVICE
CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED AS SHOWN.
BATTERY SYSTEM RATED AC OUTPUT CURRENT
PV SYSTEM RATED AC OUTPUT CURRENT
PV SYSTEM RATED AC OUTPUT VOLTAGE
PV SYSTEM POWER PHASE
48.0A
64.0A
240V
SINGLE
MAIN SERVICE
PANEL
2309 NORTH SPURGEON STREET, SANTA ANA, CA 92706
(STICKER LOCATED ON THE ESS DISCONNECT)
AC DISCONNECT
ENERGY STORAGE
SYSTEM
INVERTER
STORAGE
BATTERY
BATTERY
DISCONNECT
TESLA
GATEWAY
TESLA BATTERY
BATTERY DISCONNECT
REQ'D BY: NEC 705.12(B)(3)
BATTERY
DISCONNECT
INVERTER
STORAGE
BATTERY
SOLAR
INVERTER
SOLAR
PANELS
SOLAR
DISCONNECT
SOLAR
INVERTER
SOLAR
PANELS
SOLAR
DISCONNECT
BACKUP
LOADS PANEL
N Spurgeon St
SERVICE POINT
& UTILITY METERING
SOLAR INVERTER
SOLAR DISCONNECT
SOLAR INVERTER
SOLAR DISCONNECT
BACK-UP LOADS PANEL
TESLA GATEWAY
PHOTOVOLTAIC
ARRAY ON ROOF
PHOTOVOLTAIC
ARRAY ON ROOF
PHOTOVOLTAIC
ARRAY ON ROOF
BATTERY
REQUIRED SIGNAGE
2309 N Spurgeon
St12/11/2024
D-1
SCOPE:SCOPE:
DATE:09/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
MODULE DATA SHEET
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-10
TESLA GATEWAY
DATA SHEET
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-11
POWERWALL 3
MOUNTING DETAILS
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-12
POWERWALL 3
MOUNTING DETAILS
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-13
POWERWALL 3
MOUNTING DETAILS
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-14
SYSTEM CONFIGURATION
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-15
LOAD CALCULATION
Standard Method for Dwelling Service Calculations
Worksheet for the EVITP Step 7: Article 220.60 – Noncoincident Loads
2309 NORTH SPURGEON STREET, SANTA ANA, CA 92706 Air conditioning
Step 1: Section 220.12 – Lighting load for listed occupancies.32 A x 240 V x 1 =7,680 VA
2,614 Sq.ft x 3 VA =7,842 VA 24 A x 240 V x 1 =5,760 VA
Step 2 : Section 220.52 – Small Appliance and Laundry load.0 A x 240 V x 1 =0 VA
2,614 Sq.ft x 3 VA =7,842 VA Other Loads
2 Appliances Circuits x 1,500 VA =3,000 VA 0 A x 240 V x 1 =0 VA
1 Laundry Circuit x 1,500 VA =1,500 VA 0 A x 240 V x 1 =0 VA
General Lighting Load =12,342 VA 0 A x 240 V x 1 =0 VA
Step 3: Table 220.42 Apply demand factors to the general lighting load.Total Load =13,440 VA
First 3,000 VA at 100%=3,000 VA Step 8: 220.50 – 25% of largest motor FLA.*
Remainder at 35%9,342 x 0.35 =3270 VA 50 A x 240 V x 25%=3,000 VA
Net Load =6270 VA Step 9: 220.14(A) Other Loads – EVSE
Step 4: 220.53 – Demand Factor – Appliance Loads – Dwelling Units.50 A x 240 V x 1 =12,000 VA
Disposal =1,300 VA Sum of Calculated Loads
Dishwasher =1,300 VA Lighting, Sm. Appliance, Laundry (Step 3)=6,270 VA
Refrigerator =1,300 VA Fastened in Place Appliances (Step 4)=3,675 VA
Microwave =1,000 VA Clothes Dryer (Step 5)=5,000 VA
=0 VA Cooking Equipment (Step 6)=0 VA
=0 VA Noncoincedent Heat – A/C (Step 7)=13,440 VA
=0 VA 25% of Largest Motor (Step 8)=3,000 VA
=0 VA Other Loads – (Step 9)=12,000 VA
=0 VA Total Calculated Load =43,385 VA
Total =4,900 VA Step 10: Table 310.15 (B)(6) – Size the service and conductors.
75% of total; four or more appliances =3,675 VA 43,385 VA/240V =180.770 A
Step 5: 220.54 – Clothes Dryer – The greater of 5 kW or nameplate value.Conductor Size CU AL
5,000 kW Electric Dryer =5,000 VA Step 10: Table 310.15 (B)(6) – Size the service and conductors.
Step 6: Table 220.55 - Household cooking Equipment GEC Size CU AL
Oven =0 VA * Remember that although the voltages shown in the tables in
Article 430 indicate that motors are rated for 115,230 and 460 Volts,
Section 220.5(A) requires nominal voltages of 120, 240 and 480
Volts to be used for load calculations.
Range =0 VA
=0 VA
Total =0 VA
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:11/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-16
RSD DEVICE
DATA SHEET
[6]
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:09/19/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-2
INVERTER DATA SHEET
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-3
OPTIMIZER
DATA SHEET
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-4
RACKING DATA SHEET
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-5
GROUNDING SPECS
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-6
ATTACHMENT DATA SHEET
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-7
RACKING
CERTIFICATION
2309 N Spurgeon
St12/11/2024
SCOPE:SCOPE:
DATE:08/29/2024
SCALE:AS NOTED PAPER SIZE:17"x11"
CUSTOMER INFORMATION
BUILDING INFO:
OMAR NASSER
NAME: DOUG RISK
ADDRESS: 2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
CITY OF SANTA ANA
UTILITY: SCE
COMPANY NAME: TREEPUBLIC
LICENSE:# 996593
ADDRESS: 3521 JACK NORTHROP AVE,
HAWTHORNE CA 90250
PHONE: (800) 701-8073
6.56 KW DC Roof Mounted
PV Electrical System
16 - Solarever 410W PV Modules
1 - Tigo 11.4KW Inverter
2 - Tesla Powerwall 3 Battery
TWO STORY BUILDING
ROOF TYPE: COMPOSITION SHINGLE
ROOF STRUCTURE:
2''X4'' TRUSSES 24'' O/C
CONSTRUCTION TYPE:V-B
OCCUPANCY GROUP: R3
FIRE SPRINKLERS: NO
MOUNTING SYSTEM:
IRONRIDGE RACKING
PARCEL NUMBER: 00307232
LOT AREA: 6,000 SQFT
LIVING AREA: 2,614 SQFT
D-9
INVERTER & ESS
DATA SHEET
2309 N Spurgeon
St12/11/2024
State of Florida
County of Broward
This foregoing instrument was acknowledged before me by means of online notarization,
this 06/05/2024 by Omar Nasser.
Beverly Y Wimberly
___ Personally Known OR ___ Produced Identification
Type of Identification Produced California DL
2309 N Spurgeon
St12/11/2024
Address | City, St Zip Code
SANTA ANA CITY PERMIT STAFF
A
2309 N. Spurgeon St, Santa Ana, CA
92706. Please remove Solgen Construction, LLC as my contractor and replace with TreePublic
as my new contractor. Please contact me if you have any questions.
TreePublic License # 996593
3521 Jack Northrop Ave.
Hawthorne, CA 90250
800-701-8073
SINCERELY,
CAMILLE PEDROZA
714 -390 -6922
October 11 , 2 0 2 4
Contractor Info:
I Camille Pedroza residing at: 2309 North Spurgeon st, Santa Ana, CA, 92706
Hereby authorize Treepublic Solar to install solar panels at my residence and pull any necessary
Permits on my behalf.
Please feel free to contact me if any additional information or documentation is required.
2309 N Spurgeon
St12/11/2024
Address | City, St Zip Code
September 20, 2024
SANTA ANA CITY PERMIT STAFF
EVELYN LAROCCA
This letter is to change contractors on my solar project at 2309 N. Spurgeon St, Santa Ana, CA
92706. Please remove Solgen Construction, LLC as my contractor and replace with TreePublic
as my new contractor. Please contact me if you have any questions.
New Contractor Info:
TreePublic License # 996593
3521 Jack Northrop Ave.
Hawthorne, CA 90250
800-701-8073
SINCERELY,
CAMILLE PEDROZA
714 -390 -6922
2309 N Spurgeon
St12/11/2024
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
2309 N Spurgeon Str, Santa Ana, CA,
Treepublic Solar
996593
x
x
x
x
x
x
x
x
x
x
Robert Hayrapetyan
818-926-9307
permits@treepublic.com
10.04.24
2309 N Spurgeon
St12/11/2024
treepublic
Attn.: To Whom It May Concern
re job:DOUG RISK
2309 NORTH SPURGEON
STREET, SANTA ANA, CA 92706
Design Criteria:
Code:2022 CBC
ASCE 7-16
Live Load:20 psf
Ult Wind Speed:110 mph
Exposure Cat:C
Ground Snow:0 psf Min Roof Snow:NA
AHZ Consulting Engineers Inc.
Professional Engineer
projects@ahzengineers.com
10/8/2024
The following calculations are for the structural engineering design of the photovoltaic panels and are valid
only for the structural info referenced in the stamped plan set. The verification of such info is the
responsibility of others.
After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads.
All mounting equipment shall be designed and installed per manufacturer's approved installation
specifications.
www.ahzengineers.com
2309 N Spurgeon
St12/11/2024
Job Code: DOUG RISK
2 of 6
Roof Properties:
Roof Type =
Roof Pitch (deg) =
Mean Roof Height (ft) =
Attachment Trib Width (ft) =
Attachment Spacing (ft) =
Framing Type =
Framing Size =
Framing OC Spacing (in.) =
Section Thickness, b (in.) =
Section Depth, d (in.) =
Section Modulus, Sx (in.^3) =
Moment of Inertia, Ix (in.^4) =
Framing Span (ft) =
Deflection Limit D+L (in.) =
Deflection Limit S or W (in.) =
Framing Upgrade =
Sister Size =
Wood Species =
Wood Fb (psi) =
Wood Fv (psi) =
Wood E (psi) =
CD (Wind) =
CD (Snow) =
CM = Ct = CL = Ci =
CF =
Cfu =
Cr =
F'b_wind (psi) =
F'b_snow (psi) =
F'v_wind (psi) =
F'v_snow (psi) =
M_allowable_wind (lb-ft) =
M_allowable_snow (lb-ft) =
V_allowable_wind (lbs) =
V_allowable_snow (lbs) =
E' (psi) =
725
1600000
456
1008
207
634
1785
288
1.15
2484
1.5
1.00
1.0
1.6
1.15
180
1600000
DF #2
900
Adequate
NA
0.93
7
1.4
3.1
5.4
1.5
3.5
2x4
24
6
Truss
13
3.25
Shingle
20
Roof 1
www.ahzengineers.com
2309 N Spurgeon
St12/11/2024
Job Code: DOUG RISK
3 of 6
Load Calculation:
Panels Dead Load (psf) =
Roofing Weight (psf) =
Decking Weight (psf) =
Framing Weight (psf) =
Misc. Additional Weight (psf) =
Existing Dead Load (psf) =
Total Dead Load (psf) =
Ultimate Wind Speed (mph) =
Directionality Factor, kd =
Topographic Factor, kzt =
Velocity Press Exp Factor, kz =
Ground Elevation Factor, ke =
Velocity Pressure, qz (psf) =
Array Edge Factor, γE =
Solar Equalization Factor, γa =
External Pressure Up, GCp_1 =
External Pressure Up, GCp_2 =
External Pressure Up, GCp_3 =
External Pressure Down, GCp =
Design Pressure Up, p_1 (psf) =
Design Pressure Up, p_2 (psf) =
Design Pressure Up, p_3 (psf) =
Design Pressure Down, p (psf) =
Hardware Checks:
Ref. Widthrawal Value, W (lb/in) =
(CM = Ct = Ceg = 1.0) CD =
Adjusted Widthrawal Value, W' (lb/in) =
Lag Penetration, p (in.) =
Allowable Widthrawal Force, W'p (lbs) =
Applied Uplift Force (lbs) =
1064
-516
426
2.5
266
1.6
Lag Screw Checks:
Roof 1
16.0
-50.8
-60.6
0.6
-39.1
-2.6
-3.1
1.25
0.70
-2
0.85
1.00
22.4
110
0.85
1.0
Roof 1
Wind Load Calculations:
6.6
9.6
0.6
1.0
3.0
2.0
Dead Load Calculations:
3.0
Roof 1
www.ahzengineers.com
2309 N Spurgeon
St12/11/2024
Job Code: DOUG RISK
4 of 6
Uplift DCR =
Ref. Lateral Value, Z (lbs) =
(CM = Ct = CΔ = Ceg = 1.0) CD =
Adjusted Lateral Value, Z' (lbs) =
Applied Laeral Force (lbs) =
Angle of Resultant Force, α (deg) =
Adjusted Interaction Lateral Value, Z'α (lbs) =
Lateral DCR =
Roof Framing Checks:
LC1: D+S
Applied Moment (lb-ft) =
Applied Shear (lbs) =
Allowable Moment (lb-ft) =
Allowable Shear (lbs) =
Moment DCR =
Shear DCR =
LC2: D+0.6W
Applied Moment (lb-ft) =
Applied Shear (lbs) =
Allowable Moment (lb-ft) =
Allowable Shear (lbs) =
Moment DCR =
Shear DCR =
LC3: D+0.75(S+0.6W)
Applied Moment (lb-ft) =
Applied Shear (lbs) =
Allowable Moment (lb-ft) =
Allowable Shear (lbs) =
Moment DCR =
Shear DCR =
LC4: 0.6D+0.6W
Applied Moment (lb-ft) =
Applied Shear (lbs) =
Allowable Moment (lb-ft) =
Allowable Shear (lbs) =
Moment DCR =
Shear DCR =
0.50
0.39
634
1008
320
395
0.52
0.24
634
1008
327
245
0.62
0.29
634
1008
391
292
0.29
0.14
456
725
105
Force Checks:
Roof 1
134
1059
0.02
20
88
0.9
243
0.49
270
www.ahzengineers.com
2309 N Spurgeon
St12/11/2024
Job Code: DOUG RISK
5 of 6
LC1: D+L
Deflection (in.) =
Deflection Limit (in.) =
Deflection DCR =
LC2: S
Deflection (in.) =
Deflection Limit (in.) =
Deflection DCR =
LC3: W (Down)
Deflection (in.) =
Deflection Limit (in.) =
Deflection DCR =
LC4: W (Up)
Deflection (in.) =
Deflection Limit (in.) =
Deflection DCR =
Seismic Check:
Wall Weight (psf) =
Tributary Wall Area (ft2) =
Total Wall Weight (lbs) =
Roof Weight (psf) =
Roof Area (ft2) =
Total Roof Weight (lbs) =
Total Existing Weight (lbs) =
Total Additional PV Weight (lbs) =
(Existing W + Additional W)/(Existing W) =103%
The increase in weight as a result of the solar system is less than 10% of the existing structure and
therefore no further seismic analysis is required.
Limits of Scope of Work and Liability:
Additional PV Weight:
1030
Weight Increase:
1000
17000
7
2400
15844
32844
0.22
Existing Weight:
17
-0.20
0.93
0.93
0.09
0.00
0.08
0.00
0.93
1.4
0.06
Deflection Checks (Service Level):
Roof 1
0.08
www.ahzengineers.com
2309 N Spurgeon
St12/11/2024
Job Code: DOUG RISK
6 of 6
Existing structure is assumed to have been designed and constructed following appropriate codes at
time of erection, and assumed to have appropriate permits. The calculations produced are only for the
roof framing supporting the proposed PV installation referenced in the stamped planset and were
completed according to generally recognized structural analysis standards and procedures, professional
engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or
were not observable during time of inspection are not included in this scope of work. All PV modules,
racking, and mounting equipment shall be designed and installed per manufacturer's approved
installation specifications. The Engineer of Record and the engineering consulting firm assume no
responsibility for misuse or improper installation. This analysis is not stamped for water leakage.
Framing was determined based on information in provided plans and/or photos, along with engineering
judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and
spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the
Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that
there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter
(where applicable) and notify the Engineer of Record of any concerns prior to starting construction.
www.ahzengineers.com
2309 N Spurgeon
St12/11/2024