HomeMy WebLinkAbout1730 W Carlton Pl - Plan0 PV SYSTEM AS INDICATED May 30, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW COVER PAGE 1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY 2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED 3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED 4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER. 5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED. 6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY. 7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE COORDINATED WITH OTHER TRADES. 8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT. 9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE. 10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS. OWNER SCOPE PROJECT ADDRESS PROJECT DATA GENERAL NOTES VICINITY MAP SHEET INDEX 0 COVER PAGE PHOTOVOLTAIC NOTES SATELLITE VIEW BUILDING INFORMATION: SINGLE LINE DIAGRAM CODE REQUIRED SIGNAGE 3 4 ATTACHMENT LAYOUT5 6 7 INVERTER DATA SHEET D1 MODULE DATA SHEET RACKING DATA SHEET RACKING CERTIFICATE ATTACHMENT DATA SHEET ELECTRICAL INFORMATION MAIN SERVICE PANEL BUSBAR RATING MAIN SERVICE BREAKER RATING 1ɸ, 3W, 120/240V ROOF PLAN MODULE MAP RACKING INFORMATION Main Service Panel Solar Module Micro Inverter / Optimizer EMT / FMT / PVC / RMC type conduit/ Romex NM Cable/ FNMT (Fluid non-metalic tube) 36'' SetbackInverter Utility Meter Production Meter PV Load Center IQ Combiner Box Junction Box Sunpower PV Supervisor 18'' Setback EV Outlet CONSTRUCTION TYPE: V-B ROOF TYPE AHJ APN LOT AREA LIVING AREA MSP UM PM INV PV PVS6 IQ J/B EV ENRIQUE MORAN NOVOA 14 1 SOLAR EDGE ENERGY HUB SE3800H-US (240V) SOLAR EDGE ENERGY BANK BATTERY 10kWh1 1730 W CARLTON PL SANTA ANA, CA 92704 SSP Service Sub Panel COMPOSITION SHINGLE 1,423 SQFT 40831309 CITY OF SANTA ANA WIRE SIZE CALCULATIONS INVERTER MAP D2 D3 D4 D5 D6 GROUNDING SPECSD7 ROOF MOUNT INSTALLATION OF DC PHOTOVOLTAIC SYSTEM 5.53 KW DC 5.53 KW 5.12 KW AC NEW UPGRADED ALL OTHER ORDINANCE ADOPTED BY THE LOCAL GOVERNING AGENCIES THE INSTALLATION OF SOLAR ARRAYS AND PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITH THE FOLLOWING CODES: 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA RESIDENTIAL CODE 2022 CALIFORNIA FIRE CODE 2022 CALIFORNIA PLUMBING CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE 2022 CALIFORNIA HISTORICAL CODE 2022 CALIFORNIA EXISTING BUILDING CODE 2022 CALIFORNIA REFERENCED STANDARDS CODE 2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE 1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703. 2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS 3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED. 4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER OUTAGE. 5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS. 6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE. 7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED. 8 .INVERTER IS EQUIPPED W/ INTEGRATED GFCI, THUS PROVIDING GROUND FAULT PROTECTION 9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED 10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT. 11. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING MEANS AS PER 230.82(6) 12. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER CEC 250.122 13. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122. 14. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS OPTIMIZER DATA SHEET 1 2 6,098 SQFT 1.1 SITE PLAN Battery BackupBB Auto TransformerAT Solar Edge Meter EnclosureSEM Distribution PanelDP Rapid Shutdown ControllerRSC Rapid Shutdown BoxRSB Itron MeterIM UNIT INDEX CODE REFERENCES IRONRIDGE RACKING RAFTERS 2"X4" @ 24" O.C OCCUPANCY: R ONE STORY BUILDING 200A 200A CANADIAN SOLAR 395W CS6R-395MS (don't delete this note) AC DisconnectACD Visible Lockable Labeled DisconnectVLLD D8 BATTERY DATA SHEET BATTERY MOUNTING DETAILSD9 Bldg# 101120685 Elec# 20183887 APPROVAL: ELEC - MSmith The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 16, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW ROOF AREA CALCULATIONS FIRE SPRINKLERS - NO TOTAL ROOF AREA (SQ.FT.) - 2075 SOLAR AREA (SQ.FT.) - 294 % OF COVERED AREA - 14.2% PHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT5.53 KW DC 14 Canadian Solar 395W Modules (CS6R-395MS) ROOF PLAN 36'' Setback 18'' Setback PV 0.0 N 0° S 180° E 90° W 270° SCALE 1" = 10' MSP INV ACD J/B SolarEdge Energy Bank Battery Solar Array 1 4 Canadian 395W Modules 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Gate Solar Array 2 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg W CARLTON PL Fence DC Disconnect 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW SITE PLAN PV 1.0 N 0° S 180° E 90° W 270° SCALE 1" = 15' PROPERTY LINE 60' 95' 30' 10' 19' 25' W CARLTON PL Public Sidewalk Driveway MSP INV ACD SolarEdge Energy Bank Battery Gate Fence DC Disconnect 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW STRUCTURAL STAMPROOF PITCH ROOFING TYPE ATTACHMENT TYPE FRAMING TYPE FRAMING SIZE PENETRATION PATTERN 18° RACKING TYPE MAX PENETRATION SPACING ROOFING LAYERS WIND SPEED 95 MPH SNOW LOAD 0 PSF EXPOSURE C LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE SEALED WITH CHEM LINK SEALANT OR EQUIVALENT. MODULE WEIGHT (LBS) # OF MODULES TOTAL MODULE WEIGHT (LBS) RACK WEIGHT (LBS) TOTAL SYSTEM WEIGHT (LBS) # OF STANDOFFS LOADING PER STANDOFF (LBS) TOTAL MODULE AREA (SQ.FT.) LOADING (PSF) WEIGHT LOAD CALCULATION INDEX ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER SURFACE IS FACED WITH FELT PAPER TOTAL ROOF AREA (Sq. FT) % OF COVERED AREA PV MODULE MODEL # OPTIMIZERS WEIGHT (LBS) 14 Roof 1 Layer Comp Shingle Ironridge XR10 Rafter Stacked 48"2"X4" @ 24" O.C 3 1 2 4 ITEM NO. 1 DESCRIPTION 2 3 4 BOLT LAG 5/16 X 4.75" ASSY, FLASHING ASSY, CAPFOOT WASHER, EPDM BACKED Qty in Kit 4 4 4 4 5/16" X 4.75" Flash Foot 2 MIN 2.5" EMBEDMENT RACKING RAIL ATTACHMENT ROOF FRAMING 34 294 2075 658 132 21 811 23.8 2.76 14.2 2''X6'' Blocking 2''X4'' Support 2''X4'' Purlin 2''X6'' Collar Tie SOLAR MODULE ROOF ASCE 7-16 Max 3.5'' 47.0 CS6R-395MS ATTACHMENT LAYOUT S 1.0 48"24" 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW ITEM DESCRIPTION QTY# PV MODULE MAIN SERVICE PANEL MAIN SERVICE PANEL & UTILITY METER BUSBAR RATING BREAKER RATING 1 ITEM DESCRIPTION QTY# PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3 1 1 1 4 3 1 4 6 MAIN SERVICE PANEL 120/240V 1P,3W 2 EXISTING GROUNDING SYSTEM UTILITY 2 3 INVERTER PEAK PWR TRACKING VOLTAGE INVERTER EFFICIENCY ENCLOSURE : MAXIMUM INPUT CURRENT MAXIMUM OUTPUT CURRENT MAXIMUM INPUT POWER MAXIMUM OUTPUT POWER 4 1 5700W 380 V 99.0 % NEMA 3R 10.5 A 16.0 A 7,600 W 3,800 W SOLAREDGE ENERGY HUB SE3800H-US (240V) SOLAREDGE POWER OPTIMIZER RATED DC INPUT POWER MAXIMUM INPUT VOLTAGE MPPT RANGE MAXIMUM SHORT CIRCUIT CURRENT (Isc) MAXIMUM OUTPUT CURRENT OPTIMIZER WEIGHT MAXIMUM POWER PER STRING 5 S440 440W 60 Vdc 8 to 60 Vdc 14.5 Adc 15 Adc 1.5 Lbs 14POWER OPTIMIZER 30AAC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE, BLADE TYPE, NEMA 3R, 120/240V 16 NEW UPGRADED NEW 2 1 33 200A 200A 200A FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3 14 Canadian Solar 395W CS6R-395MS Voc = 36.6V Vmp = 30.6V Isc = 13.77A Imp = 12.91A String: (14) Modules, (14) Optimizers SINGLE LINE DIAGRAM (2)#10 AWG (10-12 AWG), 600V insulated (1)#24 AWG (16-24 AWG), 600V insulated or CAT6 1" EMT TYPE Conduit BATTERY BACKUP BATTERY BACKUP SYSTEMS SOLAR EDGE ENERGY BANK 10kWh, BAT-10K1P 17 EXTERIOR KNIFE SWITCH TYPE DISCONNECT INSTALL 2P 20A CB(PV) AT OPPOSITE END OF BUS FROM MAIN FEEDER CB (N)200A 7 8 DC DISCONNECT DC DISCONNECT LOCKABLE, BLADE TYPE, NEMA 3R, 600V 1830A E 1.0 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW FROM PV MODULES TO JBOX FROM JBOX TO INVERTER (2)1 (1) #6 AWG BARE CU EGC, 2 #10 AWG CU EGC, (3) 3 (1) #10 AWG CU EGC, MAXIMUM INVERTER OUTPUT CURRENT (A) TEMPERATURE FACTOR TEMPERATURE ADJUSTMENT (A) OUTPUT CALCULATIONS PV SYSTEM MAX DC OUTPUT PV SYSTEM MAX AC OUTPUT MAXIMUM POWER (W) PEAK PWR TRACKING VOLTAGE (V) CONSIDER CONTINUOUS COEFFICIENT SHORT CIRCUIT CURRENT (A) ADJUSTED CONDUCTOR AMPACITY (A) 1.25 1.25 1.25 0.91 (2) (1) Pmax (PTC Rating) 16.0 380 1 99.0 % 16.0 * 1.25 / 0.91 22.0 #10 AWG THWN-2 SOLAR EDGE ENERGY HUB SE3800H-US (240V) 16.0 * 1.25 20.0 1 1/2'' (TEMP - 39 + 22 = 61C)0.58 RACEWAY HEIGHT FROM ROOF ADJST. FACTOR (1 thru 3 WIRES)1.0 FREE IN THE AIR, 3/4'' EMT TYPE CONDUIT BETWEEN ARRAYS 3/4'' EMT TYPE CONDUIT 1'' EMT TYPE CONDUIT MAIN SERVICE PANEL RATING BUSBAR RATING MAIN BREAKER PV BACKFEED BREAKER SIZE 120% RULE: MAX ALLOWED FEED 20A */*1.25 *1.2514 395 380 22.7 / /22.7 0.58 1.0 39.1 #10 AWG THWN-2 WIRE CHART WIRE CHART *14 395 5.53 KW * *14 369.1 0.99 5.12 KW CONSIDER CONTINUOUS COEFFICIENT CONSIDER CONTINUOUS COEFFICIENT 200A 200A 240A 200A ''MB'' + 20A "SOLAR" = 220A ≤ 240A MAX FROM INVERTER TO MAIN SERVICE PANEL CONSIDER CONTINUOUS (A) MAX NUMBER OF MODULES IN STRING 14 #10 AWG PV-WIRE 14 CS6R-395MS 395 W 369.1 W 395 WIRE SIZE CALCULATIONS E 1.1 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 16, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW JB B O X WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL CEC 110.27(C) In v e r t e r / P V L o a d WARNING THE DISCONNECTION OF THE GROUNDING CONDUCTOR(S) MAY RESULT IN OVERVOLTAGE ON THE EQUIPMENT CEC 690.31(E) CEC 690.54 AC D i s c o n n e c t CEC 690.54 WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) PM M E T E R Ma i n / S u b P a n e l CEC 690.54 CEC 690.13 (E), CEC 705.12(B)(C-D) & CEC 690.59 CEC 690.15 (B) & CEC 690.33(D)(2) CEC 690.13(B) SINGLE 120-VOLT SUPPLY DO NOT CONNECT MULTIWIRE BRANCH CIRCUIT! CEC 710.15(C) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL CEC 110.27(C) WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) CEC 705.12 (B)(3)(2) LABELING REQUIREMENTS FOR ARTICLE 690 CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether in the open (off) or closed (on) position and be permanently marked “PV SYSTEM DISCONNECT” or equivalent. Additional markings shall be permitted based upon the specific system configuration. CEC 690.13(E) Type of Disconnect. The PV system disconnecting means shall simultaneously disconnect the PV system conductors that are not solidly grounded from all conductors of other wiring systems. The PV system disconnecting means or its remote operating device or the enclosure providing access to the disconnecting means shall be capable of being locked in accordance with 110.25. CEC 690.15(B) An isolating device shall not be required to have an interrupting rating. Where an isolating device is not rated for interrupting the circuit current, it shall be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting." An isolating device shall not be required to simultaneously disconnect all current-carrying conductors of a circuit. CEC 690.31(B)(1) PV system dc circuit conductors shall be identified at all termination, connection, and splice points by color coding, marking tape, tagging, or other approved means. CEC 690.31(D)(2) Unless located and arranged so the purpose is evident, the following wiring methods and enclosures that contain PV system dc circuit conductors shall be marked with the wording PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT by means of permanently affixed labels or other approved permanent marking. CEC 690.31(D)(2) PV system dc circuit labels shall appear on every section of the wiring system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft). Labels required in this section shall be suitable for the environment where they are installed. CEC 690.31(E) Solidly-grounded bipolar PV systems shall be clearly marked with a permanent, legible warning notice indicating that the disconnection of the grounded conductor(s) may result in overvoltage on the equipment. CEC 690.33(D)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting”. CEC 690.6 Alternating-current (AC) modules and systems: The PV source circuit, conductors, and inverters shall be considered as internal components of an ac module or ac module system. CEC 690.53 A permanent readily visible label indicating the highest maximum dc voltage in a PV system, calculated in accordance with 690.7, shall be provided by the installer. CEC 690.54 All interactive system(s) points of interconnection with other sources shall be marked at an accessible location at the disconnecting means as a power source and with the rated ac output current and the nominal operating ac voltage. CEC 690.55 The PV system output circuit conductors shall be marked to indicate polarity where connected to energy storage systems. CEC 690.56(A) Plaques or directories shall be installed in accordance with 705.10. CEC 690.56(C)(2) A rapid shutdown switch shall have a label located on or no more than 1 meter (3 ft) from the switch. CEC 690.59 PV systems connected to other sources shall be installed in accordance with Parts I and II of Article 705 and Article 712. SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH ON THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY CFC 1205.4.1(1) & CEC 690.56(C) CEC 690.56(C)(2) CEC 690.31(D)(2) CEC 690.31(D)(2)CO N D U I T RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT WARNING RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC SYSTEM DISCONNECT WARNING CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED WARNING POWER SOURCE OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE. WARNING DO NOT DISCONNECT UNDER LOAD RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM WARNING: PHOTOVOLTAIC POWER SOURCE WARNING PHOTOVOLTAIC POWER SOURCE DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW FOR SOLAR PHOTOVOLTAIC SYSTEMS THAT SHUT DOWN THE ARRAY AND THE CONDUCTORS LEAVING THE ARRAY, A LABEL SHALL BE PROVIDED. THE FIRST TWO LINES OF THE LABEL SHALL BE UPPERCASE CHARACTERS WITH A MINIMUM HEIGHT OF 3/8 INCH (10 MM) IN BLACK ON A YELLOW BACKGROUND. THE REMAINING CHARACTERS SHALL BE UPPERCASE WITH A MINIMUM HEIGHT OF 3/16 INCH (5 MM) IN BLACK ON A WHITE BACKGROUND. [CFC 1205.4.1(1)] 240 Vac 240 Vac 240 Vac CEC 690.13(B) AC DISCONNECT PHOTOVOLTAIC 16.0 A 16.0 A 16.0 A CEC 705.10 CAUTION MULTIPLE SOURCES OF POWER CEC 705.10 CAUTION MULTIPLE SOURCES OF POWER CEC 690.53 MAXIMUM SYSTEM VOLTAGE RATED SHORT CIRCUIT CURRENT N/AMAX RATED AC OPERATING VOLTAGE N/ARATED AC OPERATING VOLTAGE MAX RATED AC OPERATING CURRENT RATED AC OPERATING CURRENT N/A N/A N/A N/A CAUTION N 0° S 180° E 90° W 270° POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: CEC 705.10 & CEC 690.56(B) Permanent directory or plaque providing location of service disconnecting means and photovoltaic system disconnecting means, if not located at the same location. (Plaques shall be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a contrasting color to the plaque. Plaques shall be permanently attached to the equipment or in the required location using an approved method that is suitable to withstand the environment to which it is exposed. Plaques and signage shall meet legibility, defacement, exposure and adhesion requirements of Underwriters Laboratories marking and labeling system 969(UL969). Plaques will have red background & white lettering. CODE REQUIRED SIGNAGE DC D i s c o n n e c t CEC 690.13(B) DC DISCONNECT PHOTOVOLTAIC WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B)CEC 690.53 OF PV SYSTEM MAXIMUM DC VOLTAGE PV 2.0 W CARLTON PL SOLAR INVERTER PV SYSTEM DISCONNECT FOR UTILITY OPERATION SERVICE POINT & UTILITY METERING SOLAR ARRAY ON THE ROOF SOLAREDGE ENERGY BANK BATTERY SOLAR ARRAY ON THE ROOF DC DISCONNECT 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW [FOR INSTALLER USE ONLY] PHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 5.53 KW DC 14 Canadian Solar 395W Modules (CS6R-395MS)MODULE MAP PV 2.1 Solar Array 1 4 Canadian 395W Modules 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Solar Array 2 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW INVERTERPHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 5.53 KW DC [FOR INSTALLER USE ONLY] 14 Canadian Solar 395W Modules (CS6R-395MS) INVERTER MAP PV 3.0 Solar Array 1 4 Canadian 395W Modules 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Solar Array 2 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Canadian 395W Modules 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW MODULE DATA SHEET PV 3.1 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW INVERTER DATA SHEET PV 4.0 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW OPTIMIZER DATA SHEET PV 4.1 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW RACKING DATA SHEET PV 5.0 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW ATTACHMENT DATA SHEET PV 5.1 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW GROUNDING SPECS PV 6.0 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW BATTERY DATA SHEET PV 6.1 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED September 3, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.53KW PV SYSTEM AC SIZE 5.12KW BATTERY MOUNTING DETAILS BATTERY SIDE ELEVATION BATTERY FRONT ELEVATION 2 LAG SREWS MOUNTING BRACKET 16''/40.5cm 24''/61cm BATTERY (N)BATTERY MOUNTING BRACKET & SCREWS (E) STUD WALL 31.1'' 46.4'' MIN 8"/20CM SIDE CLEARANCE PV 6.2 1730 W Carlton Pl 9/23/2024 •• ••• •• CLEAN ENERGY SOLUTIONS To whom it may concern, Clean Energy Solutions 417 W. Allen Ave Suite #105 San Dimas CA, 91773 800)994-1134 This letter authorizes Bernard Albosta to pull permits/ business license on behalf of Clean Energy Solutions. If you have any question, please call us at 800) 994-1134 Sincerely, David Gomez CEO A notary public or other officer comple�ng this cerlificate verifies only the Identity of the individual who signed lhe document 10 which lhis certificate is attached, and nol the lruthlulness accuracy, or validily of lhat document. State of California County of / f)S �lc.J Subscribe�nd sworn to (or affirmed)beore me on thisl_day of ?:(� ,20 1-!J by � Q-y\<k (-,ol\Jv+;. proved to me on the basis of satisfactory evidence to be the person( who app ared before me. Signature (Nolary Seat) ' @ ANDRE ROBINSONI , r. COMM # 2433203 � :;; NOTARY PUBLIC· CAUFORNIA !'? I LOS ANGELES COUNTY Ilily Com! Ell)ltS JANUARY ll. 2027 q • 0 1730 W Carlton Pl 9/23/2024 1730 W Carlton Pl 9/23/2024 1730 W CARLTON PL., SANTA ANA, CA 92704 NOVOA, ENRIQUE MORAN CLEAN ENERGY SOLUTIONS, INC 1055 WEST 7TH STR., 33RD FLR, LOS ANGELES, CA 90017 800-994-1134 Design Criteria 1- Code: CALIFORNIA BLDG CODE 2022 / ASCE 7-16 2 - Wind: 110 MPH, Exposure: C 3 - Wood Species: DF-L No. 2 (SG = 0.5 ) Notice: Use restrictions of these calculations. The attached Calculations are valid only when bearing original signature hereon. Contractor/Client to verify existing dimensions/conditions prior to construction & solar racking is installed per manufacturer span requirements. The use of these calculations is solely intended for the above mentioned project. 1-844-PV ELITE | info@yoursolarplans.com 3000 E. Birch Street Suite 201 | Brea CA 92821 5/30/2024 Structural Calculations for SOLAR POWER SYSTEM CONNECTION CHECK AT: Job: 1730 W Carlton Pl 9/23/2024 ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes. Roof Slope =18 ° Roof Shape Hip Tributary Width s =4.00 ft Tributary Length l =2.83 ft Effective Area Ae =11.30 f 2 Height of Structure h =15 ft Wind Speed V =110 mph Exposure Categor C Building Width B =30 ft Building Length L =50 ft Zone Width a =3 ft Elevation Height zg =51 ft Wind Directionality Kd =0.85 Topography Factor Kt =1.00 Ground Elevation Factor Ke =1.00 Velocity Pressure Exposure Coefficient Kz =0.85 Velocity Pressure qz = 0.00256KzKztKdKeV2 =22.31 psf Solar Array Pressure Equalization a =0.79 Array Edge Factor E =1.50 Zone GCp p = qz(GCp)(E)(a) 3 2.59 -68.88 3r - - 3e - - 2 - - 2r 2.38 -63.37 2e 2.59 -68.88 2n - - 1 1.80 -47.84 1' - - 1730 W Carlton Pl 9/23/2024 LAG SCREW ANALYSIS Loads Wind Pressures qz =-68.88 psf Solar Panel Load QD =3 psf Panel Length l =5.650 ft Panel Width b 3.7167 ft Attachment Spacing s =4 ft Portrait Tributary Area At =11.30 ft2 Wind Load PW = qz * At =-778 lbs Dead Load PD = QD * At =33.9 lbs Uplift Pa = 0.6 PD + 0.6 Pw =-447 lbs Landscape Tributary Area At = b * s =7.4333 ft2 Wind Load PW = qz * At =-512 lbs Dead Load PD = QD * At =22.3 lbs Uplift Pa = 0.6 PD + 0.6 Pw =-294 lbs Lag Screw Specific Gravity of Lumber SG =0.50 (Douglas Fir-Larch) Diameter of Lag Screw D =5/16 in Withdraw Design /in 1800*SG3/2*D3/4 =266 lbs/in Depth of Embedment lp =2.50 in Total Nominal Withdrawal Value W = W * l p =665 lbs Load Duration Factor CD =1.6 Withdrawal Design Value W' = W * C D =1064 lbs Demand Capacity Ratio DCR = Pa / W'=0.42 < 1 OK 1730 W Carlton Pl 9/23/2024 ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check Roof Slope =18 ° Roof Shape Hip Tributary Width s =2.00 ft Tributary Length L =17.00 ft Effective Area A = L ( MAX [ s , L/3] )=96 f 2 Height of Structure h =15 ft Wind Speed V =110 mph Exposure Categor C Building Width B =30 ft Building Length L =50 ft Zone Width a =3 ft Elevation Height zg =51 ft Wind Directionality Kd =0.85 Topography Factor Kt =1.00 Ground Elevation Factor Ke =1.00 Velocity Pressure Exposure Coefficient Kz =0.85 Velocity Pressure qz = 0.00256KzKztKdKeV2 =22.31 psf Internal Pressure Coefficient (GCpi)=-0.18 Zone GCp p = qz [(GCp) - (Gcpi)] 3 2.05 -49.86 3r - - 3e - - 2 - - 2r 1.34 -34.02 2e 2.05 -49.86 2n - - 1 1.04 -27.14 1' - - 1730 W Carlton Pl 9/23/2024 Beam/ Top Chord Check Lumber: Moment Demand # of Attachment per Rafter NA =Span :Orientation Lenght (ft) : Dead Load Roof Material:QD =psf Live Load QLr =psf Wind Load p = psf Snow Load QS =psf Rafter Spacing s = in Wind Load, Portrait Portrait UL = Wind Load, Landscape Landscape UW = Linear Dead Load wd =plf Live Load wLr = plf Start ft Start ft End ft End ft Snow Load ws = plf Start ft Start ft End ft End ft Ma, Moment D lb-ft D+Lr lb-ft D+S lb-ft 0.6D+0.6W lb-ft D+0.45W+0.75Lr lb-ft D+0.45W+0.75S lb-ft Moment Capacity Framing Member Size Lumber Grade : DF-L No. 2 CM = 1 Ct = 1 Cr= CF = fb =psi Cfu =Ci = Breadth b = in Depth d = in Section Modulus Sx = bd2 / 6 =in3 Bending Stress Capacity Fb = CM * Ct * Cr * CF * fb =psi Table 4.3.1 NDS 2015 Deflection Limit E = ksi I =in4 Transient Deflection in Transient Deflection Allowed > [OKAY] Total Deflection in Total Deflection Allowed > [OKAY] -49.86 DF-L No. 2 2 j lj (ft)pd,j (lbs) pw,j (lbs) ps,j (lbs) Portrait 1 7.5 33.9 -563 0.0 11.7 33.9 -563 0 0.0 0 0.0 0.0 0 0.0 0.0 8.00 8.00 0.00 0.00 1.00 Portrait 0 0.0 0.0 10.00 1 2 3 4 Eave 2 0.0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0 0.0Portrait0 0.0 0.0 0 0.0 20 40 0.0 0.0 0.0 0.0 0 0.0Portrait0 0.022.3 -371 0 0 0.0 0 6.8 0 0 0.0 Portrait 6.8 0.0Portrait0 0.0 0.0 AT (ft2) 11.3 7.4333 pd (lbs) 33.9 -563 pw (lbs) ps (lbs) 0 12.45 2x4 1.15 1.5 17.00 12.45 17.00 900 1.50 3.50 188 286 188 423 251 251 DCR 0.9 1397 psi D 737 psi 0.53 3.06 1553 CD Fb' = CD * Fb ASD Load Ma / Sx 1.15 1785 psi D+S 737 psi 0.41 OKAY OKAY 1.25 1941 psi D+Lr 1122 psi 0.58 OKAY 1.6 2484 psi 0.380 253 120 1600 5.36 0.6D+0.6W 1657 psi 0.67 OKAY 1.0 1 20 0.00 24 HINGL 0.319 301 180 1.6 2484 psi D+0.45W+0.75S 985 psi 0.40 OKAY 1.6 2484 psi D+0.45W+0.75L 985 psi 0.40 OKAY 𝑴𝒙 𝑹𝒊𝒙 𝑳𝒊 𝑷𝒋𝒙 𝒍𝒋 𝒘𝒅𝒙𝟐 𝟐 ‐300.0 ‐200.0 ‐100.0 0.0 100.0 200.0 300.0 400.0 500.0 0.000 5.000 10.000 15.000 20.000 1730 W Carlton Pl 9/23/2024 EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2022 Part 10 Chapter 5 Section 502.5) PV System Weight Module Model CS Panel Weight W panel = 49.4 lbs Number of Panels NPV = 14 Total PV System Weight W PV = W panel * NPV =691.6 lbs Existing Roof Weight Roof Weight QD =10.0 psf Building Length Lbuild =50 ft Building Width W build =30 ft Roof Area Abuild =1500 ft2 Building Perimeter Pbuild =160 ft Wall Height ht =8 ft Wall weight Qwall =15 psf Interior wall weight Qint =10 psf Roof Load W floor = Abuild * QD =15000 lbs Wall Load wall = ht /2 * Qwall * Pbuild + Abuild * Qint /=17100 lbs Total Story Weight W build = W floor + W wall =32100 lbs Percentage Weight Increas WPV / Wbuild = 2.15% < 10% OKAY 1730 W Carlton Pl 9/23/2024 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1. Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2. Will the PV system be installed on a roof having only one roofing layer with no overlays? 3. Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4. Will the PV system weigh maximum 4 pounds per square feet or less? 5. Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6. Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7. Will the PV system be installed without using any ballast system or counter-weight system? 8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10. Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions 998787 09/03/24 mluna@cleanenergysolar.org 8009941134 Bernard Albosta 1730 W Carlton Pl 9/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW 1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY 2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED 3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED 4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER. 5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED. 6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY. 7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE COORDINATED WITH OTHER TRADES. 8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT. 9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE. 10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS. OWNER SCOPE PROJECT ADDRESS PROJECT DATA GENERAL NOTES VICINITY MAP SHEET INDEX PHOTOVOLTAIC NOTES SATELLITE VIEW BUILDING INFORMATION: ELECTRICAL INFORMATION MAIN SERVICE PANEL BUSBAR RATING MAIN SERVICE BREAKER RATING 1ɸ, 3W, 120/240V RACKING INFORMATION Main Service Panel Solar Module Micro Inverter / Optimizer EMT / FMT / PVC / RMC type conduit/ Romex NM Cable/ FNMT (Fluid non-metalic tube) 36'' SetbackInverter Utility Meter Production Meter PV Load Center IQ Combiner Box Junction Box Sunpower PV Supervisor 18'' Setback EV Outlet CONSTRUCTION TYPE: V-B ROOF TYPE AHJ APN LOT AREA LIVING AREA MSP UM PM INV PV PVS6 IQ J/B EV ENRIQUE MORAN NOVOA 14 1 SOLAR EDGE ENERGY HUB SE3800H-US (240V) SOLAR EDGE ENERGY BANK BATTERY 10kWh1 1730 W CARLTON PL SANTA ANA, CA 92704 SSP Service Sub Panel COMPOSITION SHINGLE 1,423 SQFT 40831309 CITY OF SANTA ANA SITE PLAN ROOF MOUNT INSTALLATION OF DC PHOTOVOLTAIC SYSTEM 5.60 KW DC 5.60 KW 5.18 KW AC NEW UPGRADED ALL OTHER ORDINANCE ADOPTED BY THE LOCAL GOVERNING AGENCIES THE INSTALLATION OF SOLAR ARRAYS AND PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITH THE FOLLOWING CODES: 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA RESIDENTIAL CODE 2022 CALIFORNIA FIRE CODE 2022 CALIFORNIA PLUMBING CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE 2022 CALIFORNIA HISTORICAL CODE 2022 CALIFORNIA EXISTING BUILDING CODE 2022 CALIFORNIA REFERENCED STANDARDS CODE 2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE 1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703. 2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS 3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED. 4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER OUTAGE. 5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS. 6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE. 7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED. 8 .INVERTER IS EQUIPPED W/ INTEGRATED GFCI, THUS PROVIDING GROUND FAULT PROTECTION 9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED 10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT. 11. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING MEANS AS PER 230.82(6) 12. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER CEC 250.122 13. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122. 14. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS 6,098 SQFT Battery BackupBB Auto TransformerAT Solar Edge Meter EnclosureSEM Distribution PanelDP Rapid Shutdown ControllerRSC Rapid Shutdown BoxRSB Itron MeterIM UNIT INDEX CODE REFERENCES IRONRIDGE RACKING RAFTERS 2"X4" @ 24" O.C OCCUPANCY: R ONE STORY BUILDING 200A 200A LONGI SOLAR 400W LR5-54HABB-400M (don't delete this note) AC DisconnectACD Visible Lockable Labeled DisconnectVLLD 0 TITLE SHEET SINGLE LINE DIAGRAM CODE REQUIRED SIGNAGE E 1.1 PV 2.0 ATTACHMENT LAYOUTS 1.0 PV 2.1 PV 3.0 INVERTER DATA SHEET MODULE DATA SHEET RACKING SPECIFICATIONS ATTACHMENT SPECIFICATIONS ROOF PLAN MODULE MAP WIRE SIZE CALCULATIONS INVERTER MAP GROUNDING SPECIFICATIONS OPTIMIZER DATA SHEET PV 0.0 E 1.0 SITE PLANPV 1.0 PV 3.1 PV 4.0 PV 4.1 PV 5.0 PV 5.1 PV 6.0 PV 6.1 BATTERY DATA SHEET PV 6.2 BATTERY MOUNTING DETAILS 0 COVER PAGE 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW ROOF AREA CALCULATIONS FIRE SPRINKLERS - NO TOTAL ROOF AREA (SQ.FT.) - 2075 SOLAR AREA (SQ.FT.) - 294 % OF COVERED AREA - 14.2% PHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT5.60 KW DC 14 Longi Solar 400W Modules (LR5-54HABB-400M) ROOF PLAN 36'' Setback 18'' Setback PV 0.0 N 0° S 180° E 90° W 270° SCALE 1" = 10' MSP INV ACD J/B SolarEdge Energy Bank Battery Solar Array 1 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Gate Solar Array 2 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg W CARLTON PL Fence 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW SITE PLAN PV 1.0 N 0° S 180° E 90° W 270° SCALE 1" = 15' PROPERTY LINE 60' 95' 30' 10' 19' 25' W CARLTON PL Public Sidewalk Driveway MSP INV ACD SolarEdge Energy Bank Battery Gate Fence 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW STRUCTURAL STAMPROOF PITCH ROOFING TYPE ATTACHMENT TYPE FRAMING TYPE FRAMING SIZE PENETRATION PATTERN 18° RACKING TYPE MAX PENETRATION SPACING ROOFING LAYERS WIND SPEED 95 MPH SNOW LOAD 0 PSF EXPOSURE C LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE SEALED WITH CHEM LINK SEALANT OR EQUIVALENT. MODULE WEIGHT (LBS) # OF MODULES TOTAL MODULE WEIGHT (LBS) RACK WEIGHT (LBS) TOTAL SYSTEM WEIGHT (LBS) # OF STANDOFFS LOADING PER STANDOFF (LBS) TOTAL MODULE AREA (SQ.FT.) LOADING (PSF) WEIGHT LOAD CALCULATION INDEX ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER SURFACE IS FACED WITH FELT PAPER TOTAL ROOF AREA (Sq. FT) % OF COVERED AREA PV MODULE MODEL # OPTIMIZERS WEIGHT (LBS) 14 Roof 1 Layer Comp Shingle Ironridge XR10 Rafter Stacked 48"2"X4" @ 24" O.C 3 1 2 4 ITEM NO. 1 DESCRIPTION 2 3 4 BOLT LAG 5/16 X 4.75" ASSY, FLASHING ASSY, CAPFOOT WASHER, EPDM BACKED Qty in Kit 4 4 4 4 5/16" X 4.75" Flash Foot 2 MIN 2.5" EMBEDMENT RACKING RAIL ATTACHMENT ROOF FRAMING 34 294 2075 694 139 21 854 25.1 2.91 14.2 2''X6'' Blocking 2''X4'' Support 2''X4'' Purlin 2''X6'' Collar Tie SOLAR MODULE ROOF ASCE 7-16 Max 3.5'' 49.6 LR5-54HABB-400M ATTACHMENT LAYOUT S 1.0 48"24" 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW ITEM DESCRIPTION QTY# PV MODULE MAIN SERVICE PANEL MAIN SERVICE PANEL & UTILITY METER BUSBAR RATING BREAKER RATING 1 ITEM DESCRIPTION QTY# PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3 1 1 1 4 3 1 4 6 MAIN SERVICE PANEL 120/240V 1P,3W 2 EXISTING GROUNDING SYSTEM UTILITY 2 3 INVERTER PEAK PWR TRACKING VOLTAGE INVERTER EFFICIENCY ENCLOSURE : MAXIMUM INPUT CURRENT MAXIMUM OUTPUT CURRENT MAXIMUM INPUT POWER MAXIMUM OUTPUT POWER 4 1 5700W 380 V 99.0 % NEMA 3R 10.5 A 16.0 A 7,600 W 3,800 W SOLAREDGE ENERGY HUB SE3800H-US (240V) SOLAREDGE POWER OPTIMIZER RATED DC INPUT POWER MAXIMUM INPUT VOLTAGE MPPT RANGE MAXIMUM SHORT CIRCUIT CURRENT (Isc) MAXIMUM OUTPUT CURRENT OPTIMIZER WEIGHT MAXIMUM POWER PER STRING 5 S440 440W 60 Vdc 8 to 60 Vdc 14.5 Adc 15 Adc 1.5 Lbs 14POWER OPTIMIZER 30AAC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE, BLADE TYPE, NEMA 3R, 120/240V 16 NEW UPGRADED NEW 2 1 33 200A 200A 200A FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3 14 LONGI SOLAR 400W LR5-54HABB-400M Voc = 37.05V Vmp = 30.94V Isc = 13.72A Imp = 12.93A String: (14) Modules, (14) Optimizers SINGLE LINE DIAGRAM (2)#10 AWG (10-12 AWG), 600V insulated (1)#24 AWG (16-24 AWG), 600V insulated or CAT6 1" EMT TYPE Conduit BATTERY BACKUP BATTERY BACKUP SYSTEMS SOLAR EDGE ENERGY BANK 10kWh, BAT-10K1P 17 EXTERIOR KNIFE SWITCH TYPE DISCONNECT INSTALL 2P 20A CB(PV) AT OPPOSITE END OF BUS FROM MAIN FEEDER CB (N)200A 7 E 1.0 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW FROM PV MODULES TO JBOX FROM JBOX TO INVERTER (2)1 (1) #6 AWG BARE CU EGC, 2 #10 AWG CU EGC, (3) 3 (1) #10 AWG CU EGC, MAXIMUM INVERTER OUTPUT CURRENT (A) TEMPERATURE FACTOR TEMPERATURE ADJUSTMENT (A) OUTPUT CALCULATIONS PV SYSTEM MAX DC OUTPUT PV SYSTEM MAX AC OUTPUT MAXIMUM POWER (W) PEAK PWR TRACKING VOLTAGE (V) CONSIDER CONTINUOUS COEFFICIENT SHORT CIRCUIT CURRENT (A) ADJUSTED CONDUCTOR AMPACITY (A) 1.25 1.25 1.25 0.91 (2) (1) Pmax (PTC Rating) 16.0 380 1 99.0 % 16.0 * 1.25 / 0.91 22.0 #10 AWG THWN-2 SOLAR EDGE ENERGY HUB SE3800H-US (240V) 16.0 * 1.25 20.0 1 1/2'' (TEMP - 39 + 22 = 61C)0.58 RACEWAY HEIGHT FROM ROOF ADJST. FACTOR (1 thru 3 WIRES)1.0 FREE IN THE AIR, 3/4'' EMT TYPE CONDUIT BETWEEN ARRAYS 3/4'' EMT TYPE CONDUIT 1'' EMT TYPE CONDUIT MAIN SERVICE PANEL RATING BUSBAR RATING MAIN BREAKER PV BACKFEED BREAKER SIZE 120% RULE: MAX ALLOWED FEED 20A */*1.25 *1.2514400380 23.0 //23.0 0.58 1.0 39.7 #10 AWG THWN-2 WIRE CHART WIRE CHART *14 400 5.60 KW **14 373.7 0.99 5.18 KW CONSIDER CONTINUOUS COEFFICIENT CONSIDER CONTINUOUS COEFFICIENT 200A 200A 240A 200A ''MB'' + 20A "SOLAR" = 220A ≤ 240A MAX FROM INVERTER TO MAIN SERVICE PANEL CONSIDER CONTINUOUS (A) MAX NUMBER OF MODULES IN STRING 14 #10 AWG PV-WIRE 14 400 LR5-54HABB-400M 400 W 373.7 W WIRE SIZE CALCULATIONS E 1.1 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW JB B O X WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL CEC 110.27(C) In v e r t e r / P V L o a d WARNING THE DISCONNECTION OF THE GROUNDING CONDUCTOR(S) MAY RESULT IN OVERVOLTAGE ON THE EQUIPMENT CEC 690.31(E) CEC 690.54 AC D i s c o n n e c t CEC 690.54 WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) PM M E T E R Ma i n / S u b P a n e l CEC 690.54 CEC 690.13 (E), CEC 705.12(B)(C-D) & CEC 690.59 CEC 690.15 (B) & CEC 690.33(D)(2) CEC 690.13(B) SINGLE 120-VOLT SUPPLY DO NOT CONNECT MULTIWIRE BRANCH CIRCUIT! CEC 710.15(C) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL CEC 110.27(C) WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) CEC 705.12 (B)(3)(2) LABELING REQUIREMENTS FOR ARTICLE 690 CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether in the open (off) or closed (on) position and be permanently marked “PV SYSTEM DISCONNECT” or equivalent. Additional markings shall be permitted based upon the specific system configuration. CEC 690.13(E) Type of Disconnect. The PV system disconnecting means shall simultaneously disconnect the PV system conductors that are not solidly grounded from all conductors of other wiring systems. The PV system disconnecting means or its remote operating device or the enclosure providing access to the disconnecting means shall be capable of being locked in accordance with 110.25. CEC 690.15(B) An isolating device shall not be required to have an interrupting rating. Where an isolating device is not rated for interrupting the circuit current, it shall be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting." An isolating device shall not be required to simultaneously disconnect all current-carrying conductors of a circuit. CEC 690.31(B)(1) PV system dc circuit conductors shall be identified at all termination, connection, and splice points by color coding, marking tape, tagging, or other approved means. CEC 690.31(D)(2) Unless located and arranged so the purpose is evident, the following wiring methods and enclosures that contain PV system dc circuit conductors shall be marked with the wording PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT by means of permanently affixed labels or other approved permanent marking. CEC 690.31(D)(2) PV system dc circuit labels shall appear on every section of the wiring system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft). Labels required in this section shall be suitable for the environment where they are installed. CEC 690.31(E) Solidly-grounded bipolar PV systems shall be clearly marked with a permanent, legible warning notice indicating that the disconnection of the grounded conductor(s) may result in overvoltage on the equipment. CEC 690.33(D)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting”. CEC 690.6 Alternating-current (AC) modules and systems: The PV source circuit, conductors, and inverters shall be considered as internal components of an ac module or ac module system. CEC 690.53 A permanent readily visible label indicating the highest maximum dc voltage in a PV system, calculated in accordance with 690.7, shall be provided by the installer. CEC 690.54 All interactive system(s) points of interconnection with other sources shall be marked at an accessible location at the disconnecting means as a power source and with the rated ac output current and the nominal operating ac voltage. CEC 690.55 The PV system output circuit conductors shall be marked to indicate polarity where connected to energy storage systems. CEC 690.56(A) Plaques or directories shall be installed in accordance with 705.10. CEC 690.56(C)(2) A rapid shutdown switch shall have a label located on or no more than 1 meter (3 ft) from the switch. CEC 690.59 PV systems connected to other sources shall be installed in accordance with Parts I and II of Article 705 and Article 712. SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH ON THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY CFC 1205.4.1(1) & CEC 690.56(C) CEC 690.56(C)(2) CEC 690.31(D)(2) CEC 690.31(D)(2)CO N D U I T RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT WARNING RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC SYSTEM DISCONNECT WARNING CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED WARNING POWER SOURCE OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE. WARNING DO NOT DISCONNECT UNDER LOAD RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM WARNING: PHOTOVOLTAIC POWER SOURCE WARNING PHOTOVOLTAIC POWER SOURCE DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW FOR SOLAR PHOTOVOLTAIC SYSTEMS THAT SHUT DOWN THE ARRAY AND THE CONDUCTORS LEAVING THE ARRAY, A LABEL SHALL BE PROVIDED. THE FIRST TWO LINES OF THE LABEL SHALL BE UPPERCASE CHARACTERS WITH A MINIMUM HEIGHT OF 3/8 INCH (10 MM) IN BLACK ON A YELLOW BACKGROUND. THE REMAINING CHARACTERS SHALL BE UPPERCASE WITH A MINIMUM HEIGHT OF 3/16 INCH (5 MM) IN BLACK ON A WHITE BACKGROUND. [CFC 1205.4.1(1)] 240 Vac 240 Vac 240 Vac CEC 690.13(B) AC DISCONNECT PHOTOVOLTAIC 16.0 A 16.0 A 16.0 A CEC 705.10 CAUTION MULTIPLE SOURCES OF POWER CEC 705.10 CAUTION MULTIPLE SOURCES OF POWER CEC 690.53 MAXIMUM SYSTEM VOLTAGE RATED SHORT CIRCUIT CURRENT N/AMAX RATED AC OPERATING VOLTAGE N/ARATED AC OPERATING VOLTAGE MAX RATED AC OPERATING CURRENT RATED AC OPERATING CURRENT N/A N/A N/A N/A CAUTION N 0° S 180° E 90° W 270° POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: CEC 705.10 & CEC 690.56(B) Permanent directory or plaque providing location of service disconnecting means and photovoltaic system disconnecting means, if not located at the same location. (Plaques shall be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a contrasting color to the plaque. Plaques shall be permanently attached to the equipment or in the required location using an approved method that is suitable to withstand the environment to which it is exposed. Plaques and signage shall meet legibility, defacement, exposure and adhesion requirements of Underwriters Laboratories marking and labeling system 969(UL969). Plaques will have red background & white lettering. CODE REQUIRED SIGNAGE DC D i s c o n n e c t CEC 690.13(B) DC DISCONNECT PHOTOVOLTAIC WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B)CEC 690.53 OF PV SYSTEM MAXIMUM DC VOLTAGE PV 2.0 W CARLTON PL SOLAR INVERTER PV SYSTEM DISCONNECT FOR UTILITY OPERATION SERVICE POINT & UTILITY METERING SOLAR ARRAY ON THE ROOF SOLAREDGE ENERGY BANK BATTERY SOLAR ARRAY ON THE ROOF 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW [FOR INSTALLER USE ONLY] PHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 5.60 KW DC 14 Longi Solar 400W Modules (LR5-54HABB-400M) MODULE MAP PV 2.1 Solar Array 1 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Solar Array 2 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW INVERTERPHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 5.60 KW DC [FOR INSTALLER USE ONLY] 14 Longi Solar 400W Modules (LR5-54HABB-400M) INVERTER MAP PV 3.0 Solar Array 1 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Solar Array 2 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW MODULE DATA SHEET PV 3.1 1730 W Carlton Pl 10/23/2024 PCC-13 Rev. 06-17-2019 White-Plan Check Yellow-Applicant REVISION /SUPPLEMENTAL PLAN CHECK REQUEST PCC-13 CBC 2022 Rev 6-17-2024 Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org Project Address: _________________________________________ Suite #_______________________________ New Plan Check No.____________________________________________________________________________ Original Plan Check No.:__________________________________ Permit Issuance Date:____________________ Original Plan Checker: __________________________________________________________________________ Amount Paid: $__________________________________________ Misc. Receipt #: ________________________ Processed by: ___________________________________________ Date: ________________________________ Plan Checker Approval: ___________________________________ Date: ________________________________ Additional Hours:________________________________________ @ $269.90 = $ _________________________ Print Name:_____________________________________________ Signature: ____________________________ Representing: ________________________________________________________________________________ Contact Person: ________________________________________ Telephone: ( ) ________________________ E-mail (Strongly Recommended): _________________________________________________________________ PLANS PREPARED BY AN ARCHITECT OR ENGINEER MUST BE SIGNED BY THE PROFESSIONAL WHO PREPARES THEM. PLEASE WRITE A BRIEF DESCRIPTION OF THE REVISION/SUPPLEMENT AND IF POSSIBLE AREA OF WORK. ALL REVISIONS ARE TO BE CLOUDED AND PROPERLY IDENTIFIED: (i.e. Deltas,Sheet Numbers, etc.). Electrical, Plumbing and/or Mechanical plans – stamped job set shall accompany revised plans. ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ Telephone: ( ) ____________________________________ Fax: ( ) __________________________________ 1730 West Carlton Place Santa Ana, CA 92704 09/20/2024 Smith, Mark $212.19 OPS 4682 web_issue 09/20/2024 Melissa Luna Clean Energy Solutions 800 994-1134 Melissa Luna 800 994-1134 mluna@cleanenergysolar.org 101120685 The battery location has been changed. (Pages PV 0.0, PV1.0, PV2.0) The DC Disconnect has been removed. (Pages PV0.0, PV1.0, E1.0, PV2.0) The module type has been changed. (Pages 0-PV 3.1) 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW 1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY 2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED 3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED 4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER. 5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED. 6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY. 7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE COORDINATED WITH OTHER TRADES. 8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT. 9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE. 10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS. OWNER SCOPE PROJECT ADDRESS PROJECT DATA GENERAL NOTES VICINITY MAP SHEET INDEX PHOTOVOLTAIC NOTES SATELLITE VIEW BUILDING INFORMATION: ELECTRICAL INFORMATION MAIN SERVICE PANEL BUSBAR RATING MAIN SERVICE BREAKER RATING 1ɸ, 3W, 120/240V RACKING INFORMATION Main Service Panel Solar Module Micro Inverter / Optimizer EMT / FMT / PVC / RMC type conduit/ Romex NM Cable/ FNMT (Fluid non-metalic tube) 36'' SetbackInverter Utility Meter Production Meter PV Load Center IQ Combiner Box Junction Box Sunpower PV Supervisor 18'' Setback EV Outlet CONSTRUCTION TYPE: V-B ROOF TYPE AHJ APN LOT AREA LIVING AREA MSP UM PM INV PV PVS6 IQ J/B EV ENRIQUE MORAN NOVOA 14 1 SOLAR EDGE ENERGY HUB SE3800H-US (240V) SOLAR EDGE ENERGY BANK BATTERY 10kWh1 1730 W CARLTON PL SANTA ANA, CA 92704 SSP Service Sub Panel COMPOSITION SHINGLE 1,423 SQFT 40831309 CITY OF SANTA ANA ROOF MOUNT INSTALLATION OF DC PHOTOVOLTAIC SYSTEM 5.60 KW DC 5.60 KW 5.18 KW AC NEW UPGRADED ALL OTHER ORDINANCE ADOPTED BY THE LOCAL GOVERNING AGENCIES THE INSTALLATION OF SOLAR ARRAYS AND PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITH THE FOLLOWING CODES: 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA RESIDENTIAL CODE 2022 CALIFORNIA FIRE CODE 2022 CALIFORNIA PLUMBING CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE 2022 CALIFORNIA HISTORICAL CODE 2022 CALIFORNIA EXISTING BUILDING CODE 2022 CALIFORNIA REFERENCED STANDARDS CODE 2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE 1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703. 2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS 3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED. 4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER OUTAGE. 5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS. 6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE. 7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED. 8 .INVERTER IS EQUIPPED W/ INTEGRATED GFCI, THUS PROVIDING GROUND FAULT PROTECTION 9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED 10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT. 11. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING MEANS AS PER 230.82(6) 12. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER CEC 250.122 13. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122. 14. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS 6,098 SQFT Battery BackupBB Auto TransformerAT Solar Edge Meter EnclosureSEM Distribution PanelDP Rapid Shutdown ControllerRSC Rapid Shutdown BoxRSB Itron MeterIM UNIT INDEX CODE REFERENCES IRONRIDGE RACKING RAFTERS 2"X4" @ 24" O.C OCCUPANCY: R ONE STORY BUILDING 200A 200A LONGI SOLAR 400W LR5-54HABB-400M (don't delete this note) AC DisconnectACD Visible Lockable Labeled DisconnectVLLD 0 TITLE SHEET SINGLE LINE DIAGRAM CODE REQUIRED SIGNAGE E 1.1 PV 2.0 ATTACHMENT LAYOUTS 1.0 PV 2.1 PV 3.0 INVERTER DATA SHEET MODULE DATA SHEET RACKING SPECIFICATIONS ATTACHMENT SPECIFICATIONS ROOF PLAN MODULE MAP WIRE SIZE CALCULATIONS INVERTER MAP GROUNDING SPECIFICATIONS OPTIMIZER DATA SHEET PV 0.0 E 1.0 SITE PLANPV 1.0 PV 3.1 PV 4.0 PV 4.1 PV 5.0 PV 5.1 PV 6.0 PV 6.1 BATTERY DATA SHEET PV 6.2 BATTERY MOUNTING DETAILS 0 COVER PAGE ***The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. *** Bldg#: 101121042 Elec#: 20184140 Rev to: Bldg#: 101120685 Elec: 20183887 Approvals: Elec: M Smith 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW ROOF AREA CALCULATIONS FIRE SPRINKLERS - NO TOTAL ROOF AREA (SQ.FT.) - 2075 SOLAR AREA (SQ.FT.) - 294 % OF COVERED AREA - 14.2% PHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT5.60 KW DC 14 Longi Solar 400W Modules (LR5-54HABB-400M) ROOF PLAN 36'' Setback 18'' Setback PV 0.0 N 0° S 180° E 90° W 270° SCALE 1" = 10' MSP INV ACD J/B SolarEdge Energy Bank Battery Solar Array 1 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Gate Solar Array 2 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg W CARLTON PL Fence 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW SITE PLAN PV 1.0 N 0° S 180° E 90° W 270° SCALE 1" = 15' PROPERTY LINE 60' 95' 30' 10' 19' 25' W CARLTON PL Public Sidewalk Driveway MSP INV ACD SolarEdge Energy Bank Battery Gate Fence 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW STRUCTURAL STAMPROOF PITCH ROOFING TYPE ATTACHMENT TYPE FRAMING TYPE FRAMING SIZE PENETRATION PATTERN 18° RACKING TYPE MAX PENETRATION SPACING ROOFING LAYERS WIND SPEED 95 MPH SNOW LOAD 0 PSF EXPOSURE C LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE SEALED WITH CHEM LINK SEALANT OR EQUIVALENT. MODULE WEIGHT (LBS) # OF MODULES TOTAL MODULE WEIGHT (LBS) RACK WEIGHT (LBS) TOTAL SYSTEM WEIGHT (LBS) # OF STANDOFFS LOADING PER STANDOFF (LBS) TOTAL MODULE AREA (SQ.FT.) LOADING (PSF) WEIGHT LOAD CALCULATION INDEX ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER SURFACE IS FACED WITH FELT PAPER TOTAL ROOF AREA (Sq. FT) % OF COVERED AREA PV MODULE MODEL # OPTIMIZERS WEIGHT (LBS) 14 Roof 1 Layer Comp Shingle Ironridge XR10 Rafter Stacked 48"2"X4" @ 24" O.C 3 1 2 4 ITEM NO. 1 DESCRIPTION 2 3 4 BOLT LAG 5/16 X 4.75" ASSY, FLASHING ASSY, CAPFOOT WASHER, EPDM BACKED Qty in Kit 4 4 4 4 5/16" X 4.75" Flash Foot 2 MIN 2.5" EMBEDMENT RACKING RAIL ATTACHMENT ROOF FRAMING 34 294 2075 694 139 21 854 25.1 2.91 14.2 2''X6'' Blocking 2''X4'' Support 2''X4'' Purlin 2''X6'' Collar Tie SOLAR MODULE ROOF ASCE 7-16 Max 3.5'' 49.6 LR5-54HABB-400M ATTACHMENT LAYOUT S 1.0 48"24" 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW ITEM DESCRIPTION QTY# PV MODULE MAIN SERVICE PANEL MAIN SERVICE PANEL & UTILITY METER BUSBAR RATING BREAKER RATING 1 ITEM DESCRIPTION QTY# PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3 1 1 1 4 3 1 4 6 MAIN SERVICE PANEL 120/240V 1P,3W 2 EXISTING GROUNDING SYSTEM UTILITY 2 3 INVERTER PEAK PWR TRACKING VOLTAGE INVERTER EFFICIENCY ENCLOSURE : MAXIMUM INPUT CURRENT MAXIMUM OUTPUT CURRENT MAXIMUM INPUT POWER MAXIMUM OUTPUT POWER 4 1 5700W 380 V 99.0 % NEMA 3R 10.5 A 16.0 A 7,600 W 3,800 W SOLAREDGE ENERGY HUB SE3800H-US (240V) SOLAREDGE POWER OPTIMIZER RATED DC INPUT POWER MAXIMUM INPUT VOLTAGE MPPT RANGE MAXIMUM SHORT CIRCUIT CURRENT (Isc) MAXIMUM OUTPUT CURRENT OPTIMIZER WEIGHT MAXIMUM POWER PER STRING 5 S440 440W 60 Vdc 8 to 60 Vdc 14.5 Adc 15 Adc 1.5 Lbs 14POWER OPTIMIZER 30AAC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE, BLADE TYPE, NEMA 3R, 120/240V 16 NEW UPGRADED NEW 2 1 33 200A 200A 200A FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3 14 LONGI SOLAR 400W LR5-54HABB-400M Voc = 37.05V Vmp = 30.94V Isc = 13.72A Imp = 12.93A String: (14) Modules, (14) Optimizers SINGLE LINE DIAGRAM (2)#10 AWG (10-12 AWG), 600V insulated (1)#24 AWG (16-24 AWG), 600V insulated or CAT6 1" EMT TYPE Conduit BATTERY BACKUP BATTERY BACKUP SYSTEMS SOLAR EDGE ENERGY BANK 10kWh, BAT-10K1P 17 EXTERIOR KNIFE SWITCH TYPE DISCONNECT INSTALL 2P 20A CB(PV) AT OPPOSITE END OF BUS FROM MAIN FEEDER CB (N)200A 7 E 1.0 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW FROM PV MODULES TO JBOX FROM JBOX TO INVERTER (2)1 (1) #6 AWG BARE CU EGC, 2 #10 AWG CU EGC, (3) 3 (1) #10 AWG CU EGC, MAXIMUM INVERTER OUTPUT CURRENT (A) TEMPERATURE FACTOR TEMPERATURE ADJUSTMENT (A) OUTPUT CALCULATIONS PV SYSTEM MAX DC OUTPUT PV SYSTEM MAX AC OUTPUT MAXIMUM POWER (W) PEAK PWR TRACKING VOLTAGE (V) CONSIDER CONTINUOUS COEFFICIENT SHORT CIRCUIT CURRENT (A) ADJUSTED CONDUCTOR AMPACITY (A) 1.25 1.25 1.25 0.91 (2) (1) Pmax (PTC Rating) 16.0 380 1 99.0 % 16.0 * 1.25 / 0.91 22.0 #10 AWG THWN-2 SOLAR EDGE ENERGY HUB SE3800H-US (240V) 16.0 * 1.25 20.0 1 1/2'' (TEMP - 39 + 22 = 61C)0.58 RACEWAY HEIGHT FROM ROOF ADJST. FACTOR (1 thru 3 WIRES)1.0 FREE IN THE AIR, 3/4'' EMT TYPE CONDUIT BETWEEN ARRAYS 3/4'' EMT TYPE CONDUIT 1'' EMT TYPE CONDUIT MAIN SERVICE PANEL RATING BUSBAR RATING MAIN BREAKER PV BACKFEED BREAKER SIZE 120% RULE: MAX ALLOWED FEED 20A */*1.25 *1.2514400380 23.0 //23.0 0.58 1.0 39.7 #10 AWG THWN-2 WIRE CHART WIRE CHART *14 400 5.60 KW **14 373.7 0.99 5.18 KW CONSIDER CONTINUOUS COEFFICIENT CONSIDER CONTINUOUS COEFFICIENT 200A 200A 240A 200A ''MB'' + 20A "SOLAR" = 220A ≤ 240A MAX FROM INVERTER TO MAIN SERVICE PANEL CONSIDER CONTINUOUS (A) MAX NUMBER OF MODULES IN STRING 14 #10 AWG PV-WIRE 14 400 LR5-54HABB-400M 400 W 373.7 W WIRE SIZE CALCULATIONS E 1.1 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW JB B O X WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL CEC 110.27(C) In v e r t e r / P V L o a d WARNING THE DISCONNECTION OF THE GROUNDING CONDUCTOR(S) MAY RESULT IN OVERVOLTAGE ON THE EQUIPMENT CEC 690.31(E) CEC 690.54 AC D i s c o n n e c t CEC 690.54 WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) PM M E T E R Ma i n / S u b P a n e l CEC 690.54 CEC 690.13 (E), CEC 705.12(B)(C-D) & CEC 690.59 CEC 690.15 (B) & CEC 690.33(D)(2) CEC 690.13(B) SINGLE 120-VOLT SUPPLY DO NOT CONNECT MULTIWIRE BRANCH CIRCUIT! CEC 710.15(C) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL CEC 110.27(C) WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) CEC 705.12 (B)(3)(2) LABELING REQUIREMENTS FOR ARTICLE 690 CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether in the open (off) or closed (on) position and be permanently marked “PV SYSTEM DISCONNECT” or equivalent. Additional markings shall be permitted based upon the specific system configuration. CEC 690.13(E) Type of Disconnect. The PV system disconnecting means shall simultaneously disconnect the PV system conductors that are not solidly grounded from all conductors of other wiring systems. The PV system disconnecting means or its remote operating device or the enclosure providing access to the disconnecting means shall be capable of being locked in accordance with 110.25. CEC 690.15(B) An isolating device shall not be required to have an interrupting rating. Where an isolating device is not rated for interrupting the circuit current, it shall be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting." An isolating device shall not be required to simultaneously disconnect all current-carrying conductors of a circuit. CEC 690.31(B)(1) PV system dc circuit conductors shall be identified at all termination, connection, and splice points by color coding, marking tape, tagging, or other approved means. CEC 690.31(D)(2) Unless located and arranged so the purpose is evident, the following wiring methods and enclosures that contain PV system dc circuit conductors shall be marked with the wording PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT by means of permanently affixed labels or other approved permanent marking. CEC 690.31(D)(2) PV system dc circuit labels shall appear on every section of the wiring system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft). Labels required in this section shall be suitable for the environment where they are installed. CEC 690.31(E) Solidly-grounded bipolar PV systems shall be clearly marked with a permanent, legible warning notice indicating that the disconnection of the grounded conductor(s) may result in overvoltage on the equipment. CEC 690.33(D)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting”. CEC 690.6 Alternating-current (AC) modules and systems: The PV source circuit, conductors, and inverters shall be considered as internal components of an ac module or ac module system. CEC 690.53 A permanent readily visible label indicating the highest maximum dc voltage in a PV system, calculated in accordance with 690.7, shall be provided by the installer. CEC 690.54 All interactive system(s) points of interconnection with other sources shall be marked at an accessible location at the disconnecting means as a power source and with the rated ac output current and the nominal operating ac voltage. CEC 690.55 The PV system output circuit conductors shall be marked to indicate polarity where connected to energy storage systems. CEC 690.56(A) Plaques or directories shall be installed in accordance with 705.10. CEC 690.56(C)(2) A rapid shutdown switch shall have a label located on or no more than 1 meter (3 ft) from the switch. CEC 690.59 PV systems connected to other sources shall be installed in accordance with Parts I and II of Article 705 and Article 712. SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH ON THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY CFC 1205.4.1(1) & CEC 690.56(C) CEC 690.56(C)(2) CEC 690.31(D)(2) CEC 690.31(D)(2)CO N D U I T RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT WARNING RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT RATED AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC SYSTEM DISCONNECT WARNING CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED WARNING POWER SOURCE OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE. WARNING DO NOT DISCONNECT UNDER LOAD RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM WARNING: PHOTOVOLTAIC POWER SOURCE WARNING PHOTOVOLTAIC POWER SOURCE DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW FOR SOLAR PHOTOVOLTAIC SYSTEMS THAT SHUT DOWN THE ARRAY AND THE CONDUCTORS LEAVING THE ARRAY, A LABEL SHALL BE PROVIDED. THE FIRST TWO LINES OF THE LABEL SHALL BE UPPERCASE CHARACTERS WITH A MINIMUM HEIGHT OF 3/8 INCH (10 MM) IN BLACK ON A YELLOW BACKGROUND. THE REMAINING CHARACTERS SHALL BE UPPERCASE WITH A MINIMUM HEIGHT OF 3/16 INCH (5 MM) IN BLACK ON A WHITE BACKGROUND. [CFC 1205.4.1(1)] 240 Vac 240 Vac 240 Vac CEC 690.13(B) AC DISCONNECT PHOTOVOLTAIC 16.0 A 16.0 A 16.0 A CEC 705.10 CAUTION MULTIPLE SOURCES OF POWER CEC 705.10 CAUTION MULTIPLE SOURCES OF POWER CEC 690.53 MAXIMUM SYSTEM VOLTAGE RATED SHORT CIRCUIT CURRENT N/AMAX RATED AC OPERATING VOLTAGE N/ARATED AC OPERATING VOLTAGE MAX RATED AC OPERATING CURRENT RATED AC OPERATING CURRENT N/A N/A N/A N/A CAUTION N 0° S 180° E 90° W 270° POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: CEC 705.10 & CEC 690.56(B) Permanent directory or plaque providing location of service disconnecting means and photovoltaic system disconnecting means, if not located at the same location. (Plaques shall be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a contrasting color to the plaque. Plaques shall be permanently attached to the equipment or in the required location using an approved method that is suitable to withstand the environment to which it is exposed. Plaques and signage shall meet legibility, defacement, exposure and adhesion requirements of Underwriters Laboratories marking and labeling system 969(UL969). Plaques will have red background & white lettering. CODE REQUIRED SIGNAGE DC D i s c o n n e c t CEC 690.13(B) DC DISCONNECT PHOTOVOLTAIC WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B)CEC 690.53 OF PV SYSTEM MAXIMUM DC VOLTAGE PV 2.0 W CARLTON PL SOLAR INVERTER PV SYSTEM DISCONNECT FOR UTILITY OPERATION SERVICE POINT & UTILITY METERING SOLAR ARRAY ON THE ROOF SOLAREDGE ENERGY BANK BATTERY SOLAR ARRAY ON THE ROOF 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW [FOR INSTALLER USE ONLY] PHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 5.60 KW DC 14 Longi Solar 400W Modules (LR5-54HABB-400M) MODULE MAP PV 2.1 Solar Array 1 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Solar Array 2 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW INVERTERPHOTOVOLTAIC SYSTEM 1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V) Solar Edge S440 Power Optimizers14 5.60 KW DC [FOR INSTALLER USE ONLY] 14 Longi Solar 400W Modules (LR5-54HABB-400M) INVERTER MAP PV 3.0 Solar Array 1 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 270 Deg Solar Array 2 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 90 Deg Solar Array 3 4 Longi Solar 400W 4 S440 Optimizers Tilt: 18 Deg Azimuth: 0 Deg Solar Array 4 3 Longi Solar 400W 3 S440 Optimizers Tilt: 18 Deg Azimuth: 180 Deg 1730 W Carlton Pl 10/23/2024 PV SYSTEM AS INDICATED October 1, 2024 ENRIQUE MORAN NOVOA 1730 W CARLTON PL SANTA ANA, CA 92704 Clean Energy Solutions Inc. Address: 1055 West 7th Street 33rd Floor, Los Angeles, CA 90017 Phone Number: (800) 994 1134 Lic# 998787 Class C-10 CONTRACTOR Designed By: Intersolar CAD www.intersolarcad.com PV SYSTEM DC SIZE 5.60KW PV SYSTEM AC SIZE 5.18KW MODULE DATA SHEET PV 3.1 1730 W Carlton Pl 10/23/2024