HomeMy WebLinkAbout1730 W Carlton Pl - Plan0
PV SYSTEM
AS INDICATED
May 30, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
COVER PAGE
1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE
COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY
2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED
3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED
4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER.
5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED.
6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY
AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL
INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY.
7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE
COORDINATED WITH OTHER TRADES.
8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS
RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT.
9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE
WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE.
10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS.
OWNER
SCOPE
PROJECT
ADDRESS
PROJECT DATA GENERAL NOTES VICINITY MAP
SHEET INDEX
0 COVER PAGE
PHOTOVOLTAIC NOTES
SATELLITE VIEW
BUILDING
INFORMATION:
SINGLE LINE DIAGRAM
CODE REQUIRED SIGNAGE
3
4
ATTACHMENT LAYOUT5
6
7
INVERTER DATA SHEET
D1 MODULE DATA SHEET
RACKING DATA SHEET
RACKING CERTIFICATE
ATTACHMENT DATA SHEET
ELECTRICAL
INFORMATION
MAIN SERVICE PANEL
BUSBAR RATING
MAIN SERVICE
BREAKER RATING
1ɸ, 3W, 120/240V
ROOF PLAN
MODULE MAP
RACKING
INFORMATION
Main Service Panel
Solar Module
Micro Inverter /
Optimizer
EMT / FMT / PVC
/ RMC type conduit/
Romex NM Cable/
FNMT (Fluid non-metalic tube)
36'' SetbackInverter
Utility Meter
Production Meter
PV Load Center
IQ Combiner Box
Junction Box
Sunpower PV Supervisor
18'' Setback
EV Outlet
CONSTRUCTION TYPE: V-B
ROOF
TYPE
AHJ
APN
LOT AREA
LIVING AREA
MSP
UM
PM
INV
PV
PVS6
IQ
J/B
EV
ENRIQUE MORAN NOVOA
14
1 SOLAR EDGE ENERGY HUB SE3800H-US (240V)
SOLAR EDGE ENERGY BANK BATTERY 10kWh1
1730 W CARLTON PL
SANTA ANA, CA 92704
SSP Service Sub Panel
COMPOSITION SHINGLE
1,423 SQFT
40831309
CITY OF SANTA ANA
WIRE SIZE CALCULATIONS
INVERTER MAP
D2
D3
D4
D5
D6
GROUNDING SPECSD7
ROOF MOUNT INSTALLATION OF
DC PHOTOVOLTAIC SYSTEM
5.53 KW DC
5.53 KW
5.12 KW AC
NEW UPGRADED
ALL OTHER ORDINANCE ADOPTED BY THE
LOCAL GOVERNING AGENCIES
THE INSTALLATION OF SOLAR ARRAYS AND
PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY
WITH THE FOLLOWING CODES:
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA RESIDENTIAL CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
2022 CALIFORNIA HISTORICAL CODE
2022 CALIFORNIA EXISTING BUILDING CODE
2022 CALIFORNIA REFERENCED STANDARDS CODE
2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703.
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER
OUTAGE.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE
ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED.
8 .INVERTER IS EQUIPPED W/ INTEGRATED GFCI, THUS PROVIDING GROUND FAULT PROTECTION
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT.
11. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING
MEANS AS PER 230.82(6)
12. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING
AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER CEC 250.122
13. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122.
14. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS
OPTIMIZER DATA SHEET
1
2
6,098 SQFT 1.1 SITE PLAN
Battery BackupBB
Auto TransformerAT
Solar Edge Meter EnclosureSEM
Distribution PanelDP
Rapid Shutdown ControllerRSC
Rapid Shutdown BoxRSB
Itron MeterIM
UNIT INDEX
CODE REFERENCES
IRONRIDGE RACKING
RAFTERS 2"X4" @ 24" O.C
OCCUPANCY: R
ONE STORY BUILDING
200A
200A
CANADIAN SOLAR 395W
CS6R-395MS
(don't delete this note)
AC DisconnectACD
Visible Lockable
Labeled DisconnectVLLD
D8 BATTERY DATA SHEET
BATTERY MOUNTING DETAILSD9
Bldg# 101120685
Elec# 20183887
APPROVAL:
ELEC - MSmith
The scope of the plans is for the installation of the solar
photovoltaic system only and the approval is subject to
compliance with all applicable city and state codes and
regulations regarding construction. The approval of the
plans does not constitute any certification of the accuracy,
completeness, or building permit status of the existing
buildings and structures as shown.
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 16, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
ROOF AREA CALCULATIONS
FIRE SPRINKLERS - NO
TOTAL ROOF AREA (SQ.FT.) - 2075
SOLAR AREA (SQ.FT.) - 294
% OF COVERED AREA - 14.2%
PHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER
THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT5.53 KW DC
14 Canadian Solar 395W Modules (CS6R-395MS)
ROOF PLAN
36'' Setback
18'' Setback
PV 0.0
N
0°
S
180°
E
90°
W
270°
SCALE
1" = 10'
MSP
INV
ACD
J/B
SolarEdge
Energy Bank Battery
Solar Array 1
4 Canadian 395W Modules
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Gate
Solar Array 2
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg Solar Array 3
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
W CARLTON PL
Fence
DC Disconnect
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
SITE PLAN
PV 1.0
N
0°
S
180°
E
90°
W
270°
SCALE
1" = 15'
PROPERTY LINE
60'
95'
30'
10'
19'
25'
W CARLTON PL
Public Sidewalk
Driveway
MSP
INV
ACD
SolarEdge
Energy Bank Battery
Gate
Fence
DC Disconnect
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
STRUCTURAL STAMPROOF
PITCH
ROOFING
TYPE
ATTACHMENT
TYPE
FRAMING
TYPE
FRAMING
SIZE
PENETRATION
PATTERN
18°
RACKING
TYPE
MAX
PENETRATION
SPACING
ROOFING
LAYERS
WIND SPEED 95 MPH
SNOW LOAD 0 PSF
EXPOSURE C
LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE
SEALED WITH CHEM LINK SEALANT OR EQUIVALENT.
MODULE WEIGHT (LBS)
# OF MODULES
TOTAL MODULE WEIGHT (LBS)
RACK WEIGHT (LBS)
TOTAL SYSTEM WEIGHT (LBS)
# OF STANDOFFS
LOADING PER STANDOFF (LBS)
TOTAL MODULE AREA (SQ.FT.)
LOADING (PSF)
WEIGHT LOAD CALCULATION INDEX
ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER
SURFACE IS FACED WITH FELT PAPER
TOTAL ROOF AREA (Sq. FT)
% OF COVERED AREA
PV MODULE MODEL #
OPTIMIZERS WEIGHT (LBS)
14
Roof 1 Layer Comp Shingle Ironridge XR10 Rafter Stacked 48"2"X4" @ 24" O.C
3
1
2
4
ITEM NO.
1
DESCRIPTION
2
3
4
BOLT LAG 5/16 X 4.75"
ASSY, FLASHING
ASSY, CAPFOOT
WASHER, EPDM BACKED
Qty in Kit
4
4
4
4
5/16" X 4.75"
Flash Foot 2
MIN 2.5" EMBEDMENT
RACKING RAIL
ATTACHMENT
ROOF FRAMING
34
294
2075
658
132
21
811
23.8
2.76
14.2
2''X6'' Blocking
2''X4'' Support
2''X4'' Purlin
2''X6'' Collar Tie
SOLAR MODULE
ROOF
ASCE 7-16
Max 3.5''
47.0
CS6R-395MS
ATTACHMENT
LAYOUT
S 1.0
48"24"
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
ITEM DESCRIPTION QTY#
PV MODULE
MAIN SERVICE PANEL
MAIN SERVICE PANEL
& UTILITY METER
BUSBAR RATING
BREAKER RATING
1
ITEM DESCRIPTION QTY#
PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3
1
1
1
4
3
1
4
6
MAIN
SERVICE
PANEL
120/240V
1P,3W
2
EXISTING
GROUNDING SYSTEM
UTILITY
2
3
INVERTER
PEAK PWR TRACKING VOLTAGE
INVERTER EFFICIENCY
ENCLOSURE :
MAXIMUM INPUT CURRENT
MAXIMUM OUTPUT CURRENT
MAXIMUM INPUT POWER
MAXIMUM OUTPUT POWER
4 1
5700W
380 V
99.0 %
NEMA 3R
10.5 A
16.0 A
7,600 W
3,800 W
SOLAREDGE ENERGY HUB SE3800H-US (240V)
SOLAREDGE POWER OPTIMIZER
RATED DC INPUT POWER
MAXIMUM INPUT VOLTAGE
MPPT RANGE
MAXIMUM SHORT CIRCUIT CURRENT (Isc)
MAXIMUM OUTPUT CURRENT
OPTIMIZER WEIGHT
MAXIMUM POWER PER STRING
5
S440
440W
60 Vdc
8 to 60 Vdc
14.5 Adc
15 Adc
1.5 Lbs
14POWER OPTIMIZER
30AAC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE,
BLADE TYPE, NEMA 3R, 120/240V 16
NEW UPGRADED
NEW
2
1
33
200A
200A
200A
FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3
14
Canadian Solar 395W
CS6R-395MS
Voc = 36.6V
Vmp = 30.6V
Isc = 13.77A
Imp = 12.91A
String: (14) Modules, (14) Optimizers
SINGLE LINE
DIAGRAM
(2)#10 AWG (10-12 AWG), 600V insulated
(1)#24 AWG (16-24 AWG), 600V insulated or CAT6
1" EMT TYPE Conduit
BATTERY BACKUP BATTERY BACKUP SYSTEMS
SOLAR EDGE ENERGY BANK 10kWh, BAT-10K1P 17
EXTERIOR KNIFE SWITCH TYPE DISCONNECT
INSTALL 2P
20A CB(PV) AT
OPPOSITE END
OF BUS FROM
MAIN FEEDER CB
(N)200A
7
8
DC DISCONNECT DC DISCONNECT LOCKABLE,
BLADE TYPE, NEMA 3R, 600V 1830A
E 1.0
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
FROM PV MODULES TO JBOX
FROM JBOX TO INVERTER
(2)1
(1) #6 AWG BARE CU EGC,
2
#10 AWG CU EGC,
(3)
3
(1) #10 AWG CU EGC,
MAXIMUM INVERTER OUTPUT CURRENT (A)
TEMPERATURE FACTOR
TEMPERATURE ADJUSTMENT (A)
OUTPUT CALCULATIONS
PV SYSTEM MAX DC OUTPUT
PV SYSTEM MAX AC OUTPUT
MAXIMUM POWER (W)
PEAK PWR TRACKING VOLTAGE (V)
CONSIDER CONTINUOUS COEFFICIENT
SHORT CIRCUIT CURRENT (A)
ADJUSTED CONDUCTOR AMPACITY (A)
1.25
1.25
1.25
0.91
(2)
(1)
Pmax (PTC Rating)
16.0
380
1 99.0 %
16.0 * 1.25 / 0.91 22.0
#10 AWG THWN-2
SOLAR EDGE ENERGY HUB SE3800H-US (240V)
16.0 * 1.25 20.0
1 1/2''
(TEMP - 39 + 22 = 61C)0.58
RACEWAY HEIGHT FROM ROOF
ADJST. FACTOR (1 thru 3 WIRES)1.0
FREE IN THE AIR, 3/4'' EMT TYPE CONDUIT BETWEEN ARRAYS
3/4'' EMT TYPE CONDUIT
1'' EMT TYPE CONDUIT
MAIN SERVICE PANEL RATING
BUSBAR RATING
MAIN BREAKER
PV BACKFEED BREAKER SIZE
120% RULE:
MAX ALLOWED FEED
20A
*/*1.25 *1.2514 395 380 22.7
/ /22.7 0.58 1.0 39.1
#10 AWG THWN-2
WIRE CHART WIRE CHART
*14 395 5.53 KW
* *14 369.1 0.99 5.12 KW
CONSIDER CONTINUOUS COEFFICIENT
CONSIDER CONTINUOUS COEFFICIENT
200A
200A
240A
200A ''MB'' + 20A "SOLAR" = 220A ≤ 240A MAX
FROM INVERTER TO MAIN SERVICE PANEL
CONSIDER CONTINUOUS (A)
MAX NUMBER OF MODULES IN STRING 14
#10 AWG PV-WIRE
14
CS6R-395MS 395 W
369.1 W
395
WIRE SIZE
CALCULATIONS
E 1.1
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 16, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
JB
B
O
X
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
CEC 110.27(C)
In
v
e
r
t
e
r
/
P
V
L
o
a
d
WARNING
THE DISCONNECTION OF THE
GROUNDING CONDUCTOR(S)
MAY RESULT IN OVERVOLTAGE
ON THE EQUIPMENT
CEC 690.31(E)
CEC 690.54
AC
D
i
s
c
o
n
n
e
c
t
CEC 690.54
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
PM
M
E
T
E
R
Ma
i
n
/
S
u
b
P
a
n
e
l
CEC 690.54
CEC 690.13 (E), CEC 705.12(B)(C-D) & CEC 690.59
CEC 690.15 (B) & CEC 690.33(D)(2)
CEC 690.13(B)
SINGLE 120-VOLT SUPPLY
DO NOT CONNECT
MULTIWIRE BRANCH CIRCUIT!
CEC 710.15(C)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
CEC 110.27(C)
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
CEC 705.12 (B)(3)(2)
LABELING REQUIREMENTS FOR ARTICLE 690
CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether
in the open (off) or closed (on) position and be permanently marked “PV SYSTEM
DISCONNECT” or equivalent. Additional markings shall be permitted based upon
the specific system configuration.
CEC 690.13(E) Type of Disconnect. The PV system disconnecting means shall
simultaneously disconnect the PV system conductors that are not solidly grounded
from all conductors of other wiring systems. The PV system disconnecting means or
its remote operating device or the enclosure providing access to the disconnecting
means shall be capable of being locked in accordance with 110.25.
CEC 690.15(B) An isolating device shall not be required to have an interrupting
rating. Where an isolating device is not rated for interrupting the circuit current, it shall
be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting." An
isolating device shall not be required to simultaneously disconnect all current-carrying
conductors of a circuit.
CEC 690.31(B)(1) PV system dc circuit conductors shall be identified at all
termination, connection, and splice points by color coding, marking tape, tagging, or
other approved means.
CEC 690.31(D)(2) Unless located and arranged so the purpose is evident, the following wiring
methods and enclosures that contain PV system dc circuit conductors shall be marked with the
wording PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT by means of
permanently affixed labels or other approved permanent marking.
CEC 690.31(D)(2) PV system dc circuit labels shall appear on every section of the wiring
system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between
labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft).
Labels required in this section shall be suitable for the environment where they are installed.
CEC 690.31(E) Solidly-grounded bipolar PV systems shall be clearly marked with a
permanent, legible warning notice indicating that the disconnection of the grounded
conductor(s) may result in overvoltage on the equipment.
CEC 690.33(D)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a
tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting”.
CEC 690.6 Alternating-current (AC) modules and systems: The PV source circuit, conductors,
and inverters shall be considered as internal components of an ac module or ac module
system.
CEC 690.53 A permanent readily visible label indicating the highest
maximum dc voltage in a PV system, calculated in accordance with 690.7,
shall be provided by the installer.
CEC 690.54 All interactive system(s) points of interconnection with other
sources shall be marked at an accessible location at the disconnecting
means as a power source and with the rated ac output current and the
nominal operating ac voltage.
CEC 690.55 The PV system output circuit conductors shall be marked to
indicate polarity where connected to energy storage systems.
CEC 690.56(A) Plaques or directories shall be installed in accordance with
705.10.
CEC 690.56(C)(2) A rapid shutdown switch shall have a label located on
or no more than 1 meter (3 ft) from the switch.
CEC 690.59 PV systems connected to other sources shall be installed in
accordance with Parts I and II of Article 705 and Article 712.
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH ON THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
CFC 1205.4.1(1) & CEC 690.56(C)
CEC 690.56(C)(2)
CEC 690.31(D)(2)
CEC 690.31(D)(2)CO
N
D
U
I
T
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
WARNING
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT WARNING
CAUTION
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
WARNING
POWER SOURCE OUTPUT
CONNECTION. DO NOT
RELOCATE THIS
OVERCURRENT DEVICE.
WARNING
DO NOT DISCONNECT
UNDER LOAD
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING
PHOTOVOLTAIC POWER SOURCE
DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW
FOR SOLAR PHOTOVOLTAIC SYSTEMS THAT SHUT
DOWN THE ARRAY AND THE CONDUCTORS LEAVING
THE ARRAY, A LABEL SHALL BE PROVIDED. THE
FIRST TWO LINES OF THE LABEL SHALL BE
UPPERCASE CHARACTERS WITH A MINIMUM
HEIGHT OF 3/8 INCH (10 MM) IN BLACK ON A
YELLOW BACKGROUND. THE REMAINING
CHARACTERS SHALL BE UPPERCASE WITH A
MINIMUM HEIGHT OF 3/16 INCH (5 MM) IN BLACK ON
A WHITE BACKGROUND. [CFC 1205.4.1(1)]
240 Vac
240 Vac
240 Vac
CEC 690.13(B)
AC DISCONNECT
PHOTOVOLTAIC
16.0 A
16.0 A
16.0 A
CEC 705.10
CAUTION
MULTIPLE SOURCES OF POWER
CEC 705.10
CAUTION
MULTIPLE SOURCES OF POWER
CEC 690.53
MAXIMUM SYSTEM VOLTAGE
RATED SHORT CIRCUIT CURRENT
N/AMAX RATED AC OPERATING VOLTAGE
N/ARATED AC OPERATING VOLTAGE
MAX RATED AC OPERATING CURRENT
RATED AC OPERATING CURRENT
N/A
N/A
N/A
N/A
CAUTION
N
0°
S
180°
E
90°
W
270°
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
CEC 705.10 & CEC 690.56(B)
Permanent directory or plaque providing location of service disconnecting means and
photovoltaic system disconnecting means, if not located at the same location. (Plaques shall
be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a
contrasting color to the plaque. Plaques shall be permanently attached to the equipment or in the
required location using an approved method that is suitable to withstand the environment to which it
is exposed. Plaques and signage shall meet legibility, defacement, exposure and adhesion
requirements of Underwriters Laboratories marking and labeling system 969(UL969).
Plaques will have red background & white lettering.
CODE REQUIRED
SIGNAGE
DC
D
i
s
c
o
n
n
e
c
t
CEC 690.13(B)
DC DISCONNECT
PHOTOVOLTAIC
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)CEC 690.53
OF PV SYSTEM
MAXIMUM DC VOLTAGE
PV 2.0
W CARLTON PL
SOLAR INVERTER
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
SERVICE POINT &
UTILITY METERING
SOLAR ARRAY
ON THE ROOF
SOLAREDGE ENERGY
BANK BATTERY
SOLAR ARRAY
ON THE ROOF
DC DISCONNECT
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
[FOR INSTALLER USE ONLY]
PHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
5.53 KW DC
14 Canadian Solar 395W Modules (CS6R-395MS)MODULE MAP
PV 2.1
Solar Array 1
4 Canadian 395W Modules
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Solar Array 2
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
Solar Array 3
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
INVERTERPHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
5.53 KW DC
[FOR INSTALLER USE ONLY]
14 Canadian Solar 395W Modules (CS6R-395MS)
INVERTER MAP
PV 3.0
Solar Array 1
4 Canadian 395W Modules
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Solar Array 2
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
Solar Array 3
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Canadian 395W Modules
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
MODULE
DATA SHEET
PV 3.1
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
INVERTER
DATA SHEET
PV 4.0
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
OPTIMIZER
DATA SHEET
PV 4.1
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
RACKING
DATA SHEET
PV 5.0
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
ATTACHMENT
DATA SHEET
PV 5.1
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
GROUNDING
SPECS
PV 6.0
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
BATTERY
DATA SHEET
PV 6.1
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
September 3, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.53KW
PV SYSTEM AC SIZE 5.12KW
BATTERY
MOUNTING
DETAILS
BATTERY SIDE ELEVATION BATTERY FRONT ELEVATION
2 LAG SREWS
MOUNTING
BRACKET
16''/40.5cm
24''/61cm
BATTERY
(N)BATTERY
MOUNTING BRACKET
& SCREWS
(E) STUD WALL
31.1''
46.4''
MIN 8"/20CM
SIDE CLEARANCE
PV 6.2
1730 W Carlton Pl
9/23/2024
•• ••• ••
CLEAN ENERGY
SOLUTIONS
To whom it may concern,
Clean Energy Solutions
417 W. Allen Ave Suite #105
San Dimas CA, 91773
800)994-1134
This letter authorizes Bernard Albosta to pull permits/ business license on behalf of Clean Energy Solutions.
If you have any question, please call us at 800) 994-1134
Sincerely,
David Gomez
CEO
A notary public or other officer comple�ng this
cerlificate verifies only the Identity of the
individual who signed lhe document 10 which lhis
certificate is attached, and nol the lruthlulness
accuracy, or validily of lhat document.
State of California County of / f)S �lc.J
Subscribe�nd sworn to (or affirmed)beore me
on thisl_day of ?:(� ,20 1-!J
by � Q-y\<k (-,ol\Jv+;.
proved to me on the basis of satisfactory evidence
to be the person( who app ared before me.
Signature (Nolary Seat)
'
@
ANDRE ROBINSONI , r. COMM # 2433203 �
:;; NOTARY PUBLIC· CAUFORNIA !'? I LOS ANGELES COUNTY Ilily Com! Ell)ltS JANUARY ll. 2027
q • 0
1730 W Carlton Pl
9/23/2024
1730 W Carlton Pl
9/23/2024
1730 W CARLTON PL.,
SANTA ANA, CA 92704
NOVOA, ENRIQUE MORAN
CLEAN ENERGY SOLUTIONS, INC
1055 WEST 7TH STR.,
33RD FLR,
LOS ANGELES, CA 90017
800-994-1134
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2022 / ASCE 7-16
2 - Wind: 110 MPH, Exposure: C
3 - Wood Species: DF-L No. 2 (SG = 0.5 )
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon.
Contractor/Client to verify existing dimensions/conditions prior to construction
& solar racking is installed per manufacturer span requirements.
The use of these calculations is solely intended for the above mentioned project.
1-844-PV ELITE | info@yoursolarplans.com
3000 E. Birch Street Suite 201 | Brea CA 92821
5/30/2024
Structural Calculations for
SOLAR POWER SYSTEM CONNECTION CHECK AT:
Job:
1730 W Carlton Pl
9/23/2024
ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes.
Roof Slope =18 °
Roof Shape Hip
Tributary Width s =4.00 ft
Tributary Length l =2.83 ft
Effective Area Ae =11.30 f 2
Height of Structure h =15 ft
Wind Speed V =110 mph
Exposure Categor C
Building Width B =30 ft
Building Length L =50 ft
Zone Width a =3 ft
Elevation Height zg =51 ft
Wind Directionality Kd =0.85
Topography Factor Kt =1.00
Ground Elevation Factor Ke =1.00
Velocity Pressure Exposure Coefficient Kz =0.85
Velocity Pressure qz = 0.00256KzKztKdKeV2 =22.31 psf
Solar Array Pressure Equalization a =0.79
Array Edge Factor E =1.50
Zone GCp p = qz(GCp)(E)(a)
3 2.59 -68.88
3r - -
3e - -
2 - -
2r 2.38 -63.37
2e 2.59 -68.88
2n - -
1 1.80 -47.84
1' - -
1730 W Carlton Pl
9/23/2024
LAG SCREW ANALYSIS
Loads
Wind Pressures qz =-68.88 psf
Solar Panel Load QD =3 psf
Panel Length l =5.650 ft
Panel Width b 3.7167 ft
Attachment Spacing s =4 ft
Portrait
Tributary Area At =11.30 ft2
Wind Load PW = qz * At =-778 lbs
Dead Load PD = QD * At =33.9 lbs
Uplift Pa = 0.6 PD + 0.6 Pw =-447 lbs
Landscape
Tributary Area At = b * s =7.4333 ft2
Wind Load PW = qz * At =-512 lbs
Dead Load PD = QD * At =22.3 lbs
Uplift Pa = 0.6 PD + 0.6 Pw =-294 lbs
Lag Screw
Specific Gravity of Lumber SG =0.50 (Douglas Fir-Larch)
Diameter of Lag Screw D =5/16 in
Withdraw Design /in 1800*SG3/2*D3/4 =266 lbs/in
Depth of Embedment lp =2.50 in
Total Nominal Withdrawal Value W = W * l p =665 lbs
Load Duration Factor CD =1.6
Withdrawal Design Value W' = W * C D =1064 lbs
Demand Capacity Ratio DCR = Pa / W'=0.42 < 1 OK
1730 W Carlton Pl
9/23/2024
ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check
Roof Slope =18 °
Roof Shape Hip
Tributary Width s =2.00 ft
Tributary Length L =17.00 ft
Effective Area A = L ( MAX [ s , L/3] )=96 f 2
Height of Structure h =15 ft
Wind Speed V =110 mph
Exposure Categor C
Building Width B =30 ft
Building Length L =50 ft
Zone Width a =3 ft
Elevation Height zg =51 ft
Wind Directionality Kd =0.85
Topography Factor Kt =1.00
Ground Elevation Factor Ke =1.00
Velocity Pressure Exposure Coefficient Kz =0.85
Velocity Pressure qz = 0.00256KzKztKdKeV2 =22.31 psf
Internal Pressure Coefficient (GCpi)=-0.18
Zone GCp p = qz [(GCp) - (Gcpi)]
3 2.05 -49.86
3r - -
3e - -
2 - -
2r 1.34 -34.02
2e 2.05 -49.86
2n - -
1 1.04 -27.14
1' - -
1730 W Carlton Pl
9/23/2024
Beam/ Top Chord Check Lumber:
Moment Demand
# of Attachment per Rafter NA =Span :Orientation
Lenght (ft) :
Dead Load Roof Material:QD =psf
Live Load QLr =psf
Wind Load p = psf
Snow Load QS =psf
Rafter Spacing s = in
Wind Load, Portrait Portrait UL =
Wind Load, Landscape Landscape UW =
Linear Dead Load wd =plf
Live Load wLr = plf Start ft Start ft
End ft End ft
Snow Load ws = plf Start ft Start ft
End ft End ft
Ma, Moment
D lb-ft
D+Lr lb-ft
D+S lb-ft
0.6D+0.6W lb-ft
D+0.45W+0.75Lr lb-ft
D+0.45W+0.75S lb-ft
Moment Capacity Framing Member Size Lumber Grade : DF-L No. 2
CM = 1 Ct = 1 Cr= CF = fb =psi Cfu =Ci =
Breadth b = in
Depth d = in
Section Modulus Sx = bd2 / 6 =in3
Bending Stress Capacity Fb
= CM * Ct * Cr * CF * fb =psi Table 4.3.1 NDS 2015
Deflection Limit E = ksi I =in4
Transient Deflection in
Transient Deflection Allowed > [OKAY]
Total Deflection in
Total Deflection Allowed > [OKAY]
-49.86
DF-L No. 2
2 j lj (ft)pd,j (lbs) pw,j (lbs) ps,j (lbs)
Portrait 1 7.5 33.9 -563 0.0
11.7 33.9 -563
0 0.0
0 0.0 0.0 0 0.0
0.0
8.00 8.00 0.00 0.00 1.00
Portrait 0 0.0 0.0
10.00
1 2 3 4 Eave
2
0.0
0.0 0.0 0.0
0.0
0 0.0 0.0 0.0 0.0
0 0.0 0.0 0.0
0.0
0 0.0 0.0 0 0.0Portrait0 0.0 0.0 0
0.0
20
40
0.0 0.0 0.0 0.0
0 0.0Portrait0
0.022.3 -371 0
0
0.0
0
6.8
0
0
0.0
Portrait
6.8
0.0Portrait0 0.0 0.0
AT (ft2)
11.3
7.4333
pd (lbs)
33.9 -563
pw (lbs) ps (lbs)
0
12.45
2x4
1.15 1.5
17.00
12.45
17.00
900
1.50
3.50
188
286
188
423
251
251
DCR
0.9 1397 psi D 737 psi 0.53
3.06
1553
CD Fb' = CD * Fb ASD Load Ma / Sx
1.15 1785 psi D+S 737 psi 0.41 OKAY
OKAY
1.25 1941 psi D+Lr 1122 psi 0.58 OKAY
1.6 2484 psi
0.380
253 120
1600 5.36
0.6D+0.6W 1657 psi 0.67 OKAY
1.0 1
20
0.00
24
HINGL
0.319
301 180
1.6 2484 psi D+0.45W+0.75S 985 psi 0.40 OKAY
1.6 2484 psi D+0.45W+0.75L 985 psi 0.40 OKAY
𝑴𝒙 𝑹𝒊𝒙 𝑳𝒊 𝑷𝒋𝒙 𝒍𝒋
𝒘𝒅𝒙𝟐
𝟐
‐300.0
‐200.0
‐100.0
0.0
100.0
200.0
300.0
400.0
500.0
0.000 5.000 10.000 15.000 20.000
1730 W Carlton Pl
9/23/2024
EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2022 Part 10 Chapter 5 Section 502.5)
PV System Weight
Module Model CS
Panel Weight W panel = 49.4 lbs
Number of Panels NPV = 14
Total PV System Weight W PV = W panel * NPV =691.6 lbs
Existing Roof Weight
Roof Weight QD =10.0 psf
Building Length Lbuild =50 ft
Building Width W build =30 ft
Roof Area Abuild =1500 ft2
Building Perimeter Pbuild =160 ft
Wall Height ht =8 ft
Wall weight Qwall =15 psf
Interior wall weight Qint =10 psf
Roof Load W floor = Abuild * QD =15000 lbs
Wall Load wall = ht /2 * Qwall * Pbuild + Abuild * Qint /=17100 lbs
Total Story Weight W build = W floor + W wall =32100 lbs
Percentage Weight Increas WPV / Wbuild = 2.15% < 10% OKAY
1730 W Carlton Pl
9/23/2024
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
1730 W CARLTON PL SANTA ANA, CA 92704
Clean Energy Solutions
998787
09/03/24
mluna@cleanenergysolar.org
8009941134
Bernard Albosta
1730 W Carlton Pl
9/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE
COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY
2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED
3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED
4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER.
5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED.
6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY
AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL
INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY.
7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE
COORDINATED WITH OTHER TRADES.
8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS
RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT.
9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE
WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE.
10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS.
OWNER
SCOPE
PROJECT
ADDRESS
PROJECT DATA GENERAL NOTES VICINITY MAP
SHEET INDEX
PHOTOVOLTAIC NOTES
SATELLITE VIEW
BUILDING
INFORMATION:
ELECTRICAL
INFORMATION
MAIN SERVICE PANEL
BUSBAR RATING
MAIN SERVICE
BREAKER RATING
1ɸ, 3W, 120/240V
RACKING
INFORMATION
Main Service Panel
Solar Module
Micro Inverter /
Optimizer
EMT / FMT / PVC
/ RMC type conduit/
Romex NM Cable/
FNMT (Fluid non-metalic tube)
36'' SetbackInverter
Utility Meter
Production Meter
PV Load Center
IQ Combiner Box
Junction Box
Sunpower PV Supervisor
18'' Setback
EV Outlet
CONSTRUCTION TYPE: V-B
ROOF
TYPE
AHJ
APN
LOT AREA
LIVING AREA
MSP
UM
PM
INV
PV
PVS6
IQ
J/B
EV
ENRIQUE MORAN NOVOA
14
1 SOLAR EDGE ENERGY HUB SE3800H-US (240V)
SOLAR EDGE ENERGY BANK BATTERY 10kWh1
1730 W CARLTON PL
SANTA ANA, CA 92704
SSP Service Sub Panel
COMPOSITION SHINGLE
1,423 SQFT
40831309
CITY OF SANTA ANA
SITE PLAN
ROOF MOUNT INSTALLATION OF
DC PHOTOVOLTAIC SYSTEM
5.60 KW DC
5.60 KW
5.18 KW AC
NEW UPGRADED
ALL OTHER ORDINANCE ADOPTED BY THE
LOCAL GOVERNING AGENCIES
THE INSTALLATION OF SOLAR ARRAYS AND
PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY
WITH THE FOLLOWING CODES:
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA RESIDENTIAL CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
2022 CALIFORNIA HISTORICAL CODE
2022 CALIFORNIA EXISTING BUILDING CODE
2022 CALIFORNIA REFERENCED STANDARDS CODE
2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703.
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER
OUTAGE.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE
ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED.
8 .INVERTER IS EQUIPPED W/ INTEGRATED GFCI, THUS PROVIDING GROUND FAULT PROTECTION
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT.
11. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING
MEANS AS PER 230.82(6)
12. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING
AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER CEC 250.122
13. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122.
14. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS
6,098 SQFT
Battery BackupBB
Auto TransformerAT
Solar Edge Meter EnclosureSEM
Distribution PanelDP
Rapid Shutdown ControllerRSC
Rapid Shutdown BoxRSB
Itron MeterIM
UNIT INDEX
CODE REFERENCES
IRONRIDGE RACKING
RAFTERS 2"X4" @ 24" O.C
OCCUPANCY: R
ONE STORY BUILDING
200A
200A
LONGI SOLAR 400W
LR5-54HABB-400M
(don't delete this note)
AC DisconnectACD
Visible Lockable
Labeled DisconnectVLLD
0 TITLE SHEET
SINGLE LINE DIAGRAM
CODE REQUIRED SIGNAGE
E 1.1
PV 2.0
ATTACHMENT LAYOUTS 1.0
PV 2.1
PV 3.0
INVERTER DATA SHEET
MODULE DATA SHEET
RACKING SPECIFICATIONS
ATTACHMENT SPECIFICATIONS
ROOF PLAN
MODULE MAP
WIRE SIZE CALCULATIONS
INVERTER MAP
GROUNDING SPECIFICATIONS
OPTIMIZER DATA SHEET
PV 0.0
E 1.0
SITE PLANPV 1.0
PV 3.1
PV 4.0
PV 4.1
PV 5.0
PV 5.1
PV 6.0
PV 6.1 BATTERY DATA SHEET
PV 6.2 BATTERY MOUNTING DETAILS
0
COVER PAGE 1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
ROOF AREA CALCULATIONS
FIRE SPRINKLERS - NO
TOTAL ROOF AREA (SQ.FT.) - 2075
SOLAR AREA (SQ.FT.) - 294
% OF COVERED AREA - 14.2%
PHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER
THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT5.60 KW DC
14 Longi Solar 400W Modules (LR5-54HABB-400M)
ROOF PLAN
36'' Setback
18'' Setback
PV 0.0
N
0°
S
180°
E
90°
W
270°
SCALE
1" = 10'
MSP
INV
ACD
J/B
SolarEdge
Energy Bank Battery
Solar Array 1
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Gate
Solar Array 2
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg Solar Array 3
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
W CARLTON PL
Fence
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
SITE PLAN
PV 1.0
N
0°
S
180°
E
90°
W
270°
SCALE
1" = 15'
PROPERTY LINE
60'
95'
30'
10'
19'
25'
W CARLTON PL
Public Sidewalk
Driveway
MSP
INV
ACD
SolarEdge
Energy Bank Battery
Gate
Fence
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
STRUCTURAL STAMPROOF
PITCH
ROOFING
TYPE
ATTACHMENT
TYPE
FRAMING
TYPE
FRAMING
SIZE
PENETRATION
PATTERN
18°
RACKING
TYPE
MAX
PENETRATION
SPACING
ROOFING
LAYERS
WIND SPEED 95 MPH
SNOW LOAD 0 PSF
EXPOSURE C
LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE
SEALED WITH CHEM LINK SEALANT OR EQUIVALENT.
MODULE WEIGHT (LBS)
# OF MODULES
TOTAL MODULE WEIGHT (LBS)
RACK WEIGHT (LBS)
TOTAL SYSTEM WEIGHT (LBS)
# OF STANDOFFS
LOADING PER STANDOFF (LBS)
TOTAL MODULE AREA (SQ.FT.)
LOADING (PSF)
WEIGHT LOAD CALCULATION INDEX
ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER
SURFACE IS FACED WITH FELT PAPER
TOTAL ROOF AREA (Sq. FT)
% OF COVERED AREA
PV MODULE MODEL #
OPTIMIZERS WEIGHT (LBS)
14
Roof 1 Layer Comp Shingle Ironridge XR10 Rafter Stacked 48"2"X4" @ 24" O.C
3
1
2
4
ITEM NO.
1
DESCRIPTION
2
3
4
BOLT LAG 5/16 X 4.75"
ASSY, FLASHING
ASSY, CAPFOOT
WASHER, EPDM BACKED
Qty in Kit
4
4
4
4
5/16" X 4.75"
Flash Foot 2
MIN 2.5" EMBEDMENT
RACKING RAIL
ATTACHMENT
ROOF FRAMING
34
294
2075
694
139
21
854
25.1
2.91
14.2
2''X6'' Blocking
2''X4'' Support
2''X4'' Purlin
2''X6'' Collar Tie
SOLAR MODULE
ROOF
ASCE 7-16
Max 3.5''
49.6
LR5-54HABB-400M
ATTACHMENT
LAYOUT
S 1.0
48"24"
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
ITEM DESCRIPTION QTY#
PV MODULE
MAIN SERVICE PANEL
MAIN SERVICE PANEL
& UTILITY METER
BUSBAR RATING
BREAKER RATING
1
ITEM DESCRIPTION QTY#
PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3
1
1
1
4
3
1
4
6
MAIN
SERVICE
PANEL
120/240V
1P,3W
2
EXISTING
GROUNDING SYSTEM
UTILITY
2
3
INVERTER
PEAK PWR TRACKING VOLTAGE
INVERTER EFFICIENCY
ENCLOSURE :
MAXIMUM INPUT CURRENT
MAXIMUM OUTPUT CURRENT
MAXIMUM INPUT POWER
MAXIMUM OUTPUT POWER
4 1
5700W
380 V
99.0 %
NEMA 3R
10.5 A
16.0 A
7,600 W
3,800 W
SOLAREDGE ENERGY HUB SE3800H-US (240V)
SOLAREDGE POWER OPTIMIZER
RATED DC INPUT POWER
MAXIMUM INPUT VOLTAGE
MPPT RANGE
MAXIMUM SHORT CIRCUIT CURRENT (Isc)
MAXIMUM OUTPUT CURRENT
OPTIMIZER WEIGHT
MAXIMUM POWER PER STRING
5
S440
440W
60 Vdc
8 to 60 Vdc
14.5 Adc
15 Adc
1.5 Lbs
14POWER OPTIMIZER
30AAC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE,
BLADE TYPE, NEMA 3R, 120/240V 16
NEW UPGRADED
NEW
2
1
33
200A
200A
200A
FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3
14
LONGI SOLAR 400W
LR5-54HABB-400M
Voc = 37.05V
Vmp = 30.94V
Isc = 13.72A
Imp = 12.93A
String: (14) Modules, (14) Optimizers
SINGLE LINE
DIAGRAM
(2)#10 AWG (10-12 AWG), 600V insulated
(1)#24 AWG (16-24 AWG), 600V insulated or CAT6
1" EMT TYPE Conduit
BATTERY BACKUP BATTERY BACKUP SYSTEMS
SOLAR EDGE ENERGY BANK 10kWh, BAT-10K1P 17
EXTERIOR KNIFE SWITCH TYPE DISCONNECT
INSTALL 2P
20A CB(PV) AT
OPPOSITE END
OF BUS FROM
MAIN FEEDER CB
(N)200A
7
E 1.0
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
FROM PV MODULES TO JBOX
FROM JBOX TO INVERTER
(2)1
(1) #6 AWG BARE CU EGC,
2
#10 AWG CU EGC,
(3)
3
(1) #10 AWG CU EGC,
MAXIMUM INVERTER OUTPUT CURRENT (A)
TEMPERATURE FACTOR
TEMPERATURE ADJUSTMENT (A)
OUTPUT CALCULATIONS
PV SYSTEM MAX DC OUTPUT
PV SYSTEM MAX AC OUTPUT
MAXIMUM POWER (W)
PEAK PWR TRACKING VOLTAGE (V)
CONSIDER CONTINUOUS COEFFICIENT
SHORT CIRCUIT CURRENT (A)
ADJUSTED CONDUCTOR AMPACITY (A)
1.25
1.25
1.25
0.91
(2)
(1)
Pmax (PTC Rating)
16.0
380
1 99.0 %
16.0 * 1.25 / 0.91 22.0
#10 AWG THWN-2
SOLAR EDGE ENERGY HUB SE3800H-US (240V)
16.0 * 1.25 20.0
1 1/2''
(TEMP - 39 + 22 = 61C)0.58
RACEWAY HEIGHT FROM ROOF
ADJST. FACTOR (1 thru 3 WIRES)1.0
FREE IN THE AIR, 3/4'' EMT TYPE CONDUIT BETWEEN ARRAYS
3/4'' EMT TYPE CONDUIT
1'' EMT TYPE CONDUIT
MAIN SERVICE PANEL RATING
BUSBAR RATING
MAIN BREAKER
PV BACKFEED BREAKER SIZE
120% RULE:
MAX ALLOWED FEED
20A
*/*1.25 *1.2514400380 23.0
//23.0 0.58 1.0 39.7
#10 AWG THWN-2
WIRE CHART WIRE CHART
*14 400 5.60 KW
**14 373.7 0.99 5.18 KW
CONSIDER CONTINUOUS COEFFICIENT
CONSIDER CONTINUOUS COEFFICIENT
200A
200A
240A
200A ''MB'' + 20A "SOLAR" = 220A ≤ 240A MAX
FROM INVERTER TO MAIN SERVICE PANEL
CONSIDER CONTINUOUS (A)
MAX NUMBER OF MODULES IN STRING 14
#10 AWG PV-WIRE
14
400
LR5-54HABB-400M 400 W
373.7 W
WIRE SIZE
CALCULATIONS
E 1.1
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
JB
B
O
X
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
CEC 110.27(C)
In
v
e
r
t
e
r
/
P
V
L
o
a
d
WARNING
THE DISCONNECTION OF THE
GROUNDING CONDUCTOR(S)
MAY RESULT IN OVERVOLTAGE
ON THE EQUIPMENT
CEC 690.31(E)
CEC 690.54
AC
D
i
s
c
o
n
n
e
c
t
CEC 690.54
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
PM
M
E
T
E
R
Ma
i
n
/
S
u
b
P
a
n
e
l
CEC 690.54
CEC 690.13 (E), CEC 705.12(B)(C-D) & CEC 690.59
CEC 690.15 (B) & CEC 690.33(D)(2)
CEC 690.13(B)
SINGLE 120-VOLT SUPPLY
DO NOT CONNECT
MULTIWIRE BRANCH CIRCUIT!
CEC 710.15(C)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
CEC 110.27(C)
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
CEC 705.12 (B)(3)(2)
LABELING REQUIREMENTS FOR ARTICLE 690
CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether
in the open (off) or closed (on) position and be permanently marked “PV SYSTEM
DISCONNECT” or equivalent. Additional markings shall be permitted based upon
the specific system configuration.
CEC 690.13(E) Type of Disconnect. The PV system disconnecting means shall
simultaneously disconnect the PV system conductors that are not solidly grounded
from all conductors of other wiring systems. The PV system disconnecting means or
its remote operating device or the enclosure providing access to the disconnecting
means shall be capable of being locked in accordance with 110.25.
CEC 690.15(B) An isolating device shall not be required to have an interrupting
rating. Where an isolating device is not rated for interrupting the circuit current, it shall
be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting." An
isolating device shall not be required to simultaneously disconnect all current-carrying
conductors of a circuit.
CEC 690.31(B)(1) PV system dc circuit conductors shall be identified at all
termination, connection, and splice points by color coding, marking tape, tagging, or
other approved means.
CEC 690.31(D)(2) Unless located and arranged so the purpose is evident, the following wiring
methods and enclosures that contain PV system dc circuit conductors shall be marked with the
wording PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT by means of
permanently affixed labels or other approved permanent marking.
CEC 690.31(D)(2) PV system dc circuit labels shall appear on every section of the wiring
system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between
labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft).
Labels required in this section shall be suitable for the environment where they are installed.
CEC 690.31(E) Solidly-grounded bipolar PV systems shall be clearly marked with a
permanent, legible warning notice indicating that the disconnection of the grounded
conductor(s) may result in overvoltage on the equipment.
CEC 690.33(D)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a
tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting”.
CEC 690.6 Alternating-current (AC) modules and systems: The PV source circuit, conductors,
and inverters shall be considered as internal components of an ac module or ac module
system.
CEC 690.53 A permanent readily visible label indicating the highest
maximum dc voltage in a PV system, calculated in accordance with 690.7,
shall be provided by the installer.
CEC 690.54 All interactive system(s) points of interconnection with other
sources shall be marked at an accessible location at the disconnecting
means as a power source and with the rated ac output current and the
nominal operating ac voltage.
CEC 690.55 The PV system output circuit conductors shall be marked to
indicate polarity where connected to energy storage systems.
CEC 690.56(A) Plaques or directories shall be installed in accordance with
705.10.
CEC 690.56(C)(2) A rapid shutdown switch shall have a label located on
or no more than 1 meter (3 ft) from the switch.
CEC 690.59 PV systems connected to other sources shall be installed in
accordance with Parts I and II of Article 705 and Article 712.
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH ON THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
CFC 1205.4.1(1) & CEC 690.56(C)
CEC 690.56(C)(2)
CEC 690.31(D)(2)
CEC 690.31(D)(2)CO
N
D
U
I
T
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
WARNING
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT WARNING
CAUTION
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
WARNING
POWER SOURCE OUTPUT
CONNECTION. DO NOT
RELOCATE THIS
OVERCURRENT DEVICE.
WARNING
DO NOT DISCONNECT
UNDER LOAD
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING
PHOTOVOLTAIC POWER SOURCE
DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW
FOR SOLAR PHOTOVOLTAIC SYSTEMS THAT SHUT
DOWN THE ARRAY AND THE CONDUCTORS LEAVING
THE ARRAY, A LABEL SHALL BE PROVIDED. THE
FIRST TWO LINES OF THE LABEL SHALL BE
UPPERCASE CHARACTERS WITH A MINIMUM
HEIGHT OF 3/8 INCH (10 MM) IN BLACK ON A
YELLOW BACKGROUND. THE REMAINING
CHARACTERS SHALL BE UPPERCASE WITH A
MINIMUM HEIGHT OF 3/16 INCH (5 MM) IN BLACK ON
A WHITE BACKGROUND. [CFC 1205.4.1(1)]
240 Vac
240 Vac
240 Vac
CEC 690.13(B)
AC DISCONNECT
PHOTOVOLTAIC
16.0 A
16.0 A
16.0 A
CEC 705.10
CAUTION
MULTIPLE SOURCES OF POWER
CEC 705.10
CAUTION
MULTIPLE SOURCES OF POWER
CEC 690.53
MAXIMUM SYSTEM VOLTAGE
RATED SHORT CIRCUIT CURRENT
N/AMAX RATED AC OPERATING VOLTAGE
N/ARATED AC OPERATING VOLTAGE
MAX RATED AC OPERATING CURRENT
RATED AC OPERATING CURRENT
N/A
N/A
N/A
N/A
CAUTION
N
0°
S
180°
E
90°
W
270°
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
CEC 705.10 & CEC 690.56(B)
Permanent directory or plaque providing location of service disconnecting means and
photovoltaic system disconnecting means, if not located at the same location. (Plaques shall
be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a
contrasting color to the plaque. Plaques shall be permanently attached to the equipment or in the
required location using an approved method that is suitable to withstand the environment to which it
is exposed. Plaques and signage shall meet legibility, defacement, exposure and adhesion
requirements of Underwriters Laboratories marking and labeling system 969(UL969).
Plaques will have red background & white lettering.
CODE REQUIRED
SIGNAGE
DC
D
i
s
c
o
n
n
e
c
t
CEC 690.13(B)
DC DISCONNECT
PHOTOVOLTAIC
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)CEC 690.53
OF PV SYSTEM
MAXIMUM DC VOLTAGE
PV 2.0
W CARLTON PL
SOLAR INVERTER
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
SERVICE POINT &
UTILITY METERING
SOLAR ARRAY
ON THE ROOF
SOLAREDGE ENERGY
BANK BATTERY
SOLAR ARRAY
ON THE ROOF
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
[FOR INSTALLER USE ONLY]
PHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
5.60 KW DC
14 Longi Solar 400W Modules (LR5-54HABB-400M)
MODULE MAP
PV 2.1
Solar Array 1
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Solar Array 2
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
Solar Array 3
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
INVERTERPHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
5.60 KW DC
[FOR INSTALLER USE ONLY]
14 Longi Solar 400W Modules (LR5-54HABB-400M)
INVERTER MAP
PV 3.0
Solar Array 1
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Solar Array 2
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
Solar Array 3
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
MODULE
DATA SHEET
PV 3.1
1730 W Carlton Pl
10/23/2024
PCC-13 Rev. 06-17-2019 White-Plan Check Yellow-Applicant
REVISION /SUPPLEMENTAL
PLAN CHECK REQUEST
PCC-13 CBC 2022 Rev 6-17-2024
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
Project Address: _________________________________________ Suite #_______________________________
New Plan Check No.____________________________________________________________________________
Original Plan Check No.:__________________________________ Permit Issuance Date:____________________
Original Plan Checker: __________________________________________________________________________
Amount Paid: $__________________________________________ Misc. Receipt #: ________________________
Processed by: ___________________________________________ Date: ________________________________
Plan Checker Approval: ___________________________________ Date: ________________________________
Additional Hours:________________________________________ @ $269.90 = $ _________________________
Print Name:_____________________________________________ Signature: ____________________________
Representing: ________________________________________________________________________________
Contact Person: ________________________________________ Telephone: ( ) ________________________
E-mail (Strongly Recommended): _________________________________________________________________
PLANS PREPARED BY AN ARCHITECT OR ENGINEER MUST BE SIGNED BY THE PROFESSIONAL WHO PREPARES THEM.
PLEASE WRITE A BRIEF DESCRIPTION OF THE REVISION/SUPPLEMENT AND IF POSSIBLE AREA OF WORK.
ALL REVISIONS ARE TO BE CLOUDED AND PROPERLY IDENTIFIED: (i.e. Deltas,Sheet Numbers, etc.).
Electrical, Plumbing and/or Mechanical plans – stamped job set shall accompany revised plans.
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
Telephone: ( ) ____________________________________ Fax: ( ) __________________________________
1730 West Carlton Place Santa Ana, CA 92704
09/20/2024
Smith, Mark
$212.19 OPS 4682
web_issue 09/20/2024
Melissa Luna
Clean Energy Solutions
800 994-1134
Melissa Luna 800 994-1134
mluna@cleanenergysolar.org
101120685
The battery location has been changed. (Pages PV 0.0, PV1.0, PV2.0)
The DC Disconnect has been removed. (Pages PV0.0, PV1.0, E1.0, PV2.0)
The module type has been changed. (Pages 0-PV 3.1)
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE
COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY
2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED
3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED
4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER.
5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED.
6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY
AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL
INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY.
7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE
COORDINATED WITH OTHER TRADES.
8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS
RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT.
9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE
WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE.
10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS.
OWNER
SCOPE
PROJECT
ADDRESS
PROJECT DATA GENERAL NOTES VICINITY MAP
SHEET INDEX
PHOTOVOLTAIC NOTES
SATELLITE VIEW
BUILDING
INFORMATION:
ELECTRICAL
INFORMATION
MAIN SERVICE PANEL
BUSBAR RATING
MAIN SERVICE
BREAKER RATING
1ɸ, 3W, 120/240V
RACKING
INFORMATION
Main Service Panel
Solar Module
Micro Inverter /
Optimizer
EMT / FMT / PVC
/ RMC type conduit/
Romex NM Cable/
FNMT (Fluid non-metalic tube)
36'' SetbackInverter
Utility Meter
Production Meter
PV Load Center
IQ Combiner Box
Junction Box
Sunpower PV Supervisor
18'' Setback
EV Outlet
CONSTRUCTION TYPE: V-B
ROOF
TYPE
AHJ
APN
LOT AREA
LIVING AREA
MSP
UM
PM
INV
PV
PVS6
IQ
J/B
EV
ENRIQUE MORAN NOVOA
14
1 SOLAR EDGE ENERGY HUB SE3800H-US (240V)
SOLAR EDGE ENERGY BANK BATTERY 10kWh1
1730 W CARLTON PL
SANTA ANA, CA 92704
SSP Service Sub Panel
COMPOSITION SHINGLE
1,423 SQFT
40831309
CITY OF SANTA ANA
ROOF MOUNT INSTALLATION OF
DC PHOTOVOLTAIC SYSTEM
5.60 KW DC
5.60 KW
5.18 KW AC
NEW UPGRADED
ALL OTHER ORDINANCE ADOPTED BY THE
LOCAL GOVERNING AGENCIES
THE INSTALLATION OF SOLAR ARRAYS AND
PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY
WITH THE FOLLOWING CODES:
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA RESIDENTIAL CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
2022 CALIFORNIA HISTORICAL CODE
2022 CALIFORNIA EXISTING BUILDING CODE
2022 CALIFORNIA REFERENCED STANDARDS CODE
2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703.
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER
OUTAGE.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE
ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED.
8 .INVERTER IS EQUIPPED W/ INTEGRATED GFCI, THUS PROVIDING GROUND FAULT PROTECTION
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT.
11. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING
MEANS AS PER 230.82(6)
12. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING
AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER CEC 250.122
13. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122.
14. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS
6,098 SQFT
Battery BackupBB
Auto TransformerAT
Solar Edge Meter EnclosureSEM
Distribution PanelDP
Rapid Shutdown ControllerRSC
Rapid Shutdown BoxRSB
Itron MeterIM
UNIT INDEX
CODE REFERENCES
IRONRIDGE RACKING
RAFTERS 2"X4" @ 24" O.C
OCCUPANCY: R
ONE STORY BUILDING
200A
200A
LONGI SOLAR 400W
LR5-54HABB-400M
(don't delete this note)
AC DisconnectACD
Visible Lockable
Labeled DisconnectVLLD
0 TITLE SHEET
SINGLE LINE DIAGRAM
CODE REQUIRED SIGNAGE
E 1.1
PV 2.0
ATTACHMENT LAYOUTS 1.0
PV 2.1
PV 3.0
INVERTER DATA SHEET
MODULE DATA SHEET
RACKING SPECIFICATIONS
ATTACHMENT SPECIFICATIONS
ROOF PLAN
MODULE MAP
WIRE SIZE CALCULATIONS
INVERTER MAP
GROUNDING SPECIFICATIONS
OPTIMIZER DATA SHEET
PV 0.0
E 1.0
SITE PLANPV 1.0
PV 3.1
PV 4.0
PV 4.1
PV 5.0
PV 5.1
PV 6.0
PV 6.1 BATTERY DATA SHEET
PV 6.2 BATTERY MOUNTING DETAILS
0
COVER PAGE
***The scope of the plans is for the installation of the
solar photovoltaic system only and the approval is
subject to compliance with all applicable city and state
codes and regulations regarding construction. The
approval of the plans does not constitute any
certification of the accuracy, completeness, or building
permit status of the existing buildings and structures as
shown. ***
Bldg#: 101121042
Elec#: 20184140
Rev to:
Bldg#: 101120685
Elec: 20183887
Approvals:
Elec: M Smith
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
ROOF AREA CALCULATIONS
FIRE SPRINKLERS - NO
TOTAL ROOF AREA (SQ.FT.) - 2075
SOLAR AREA (SQ.FT.) - 294
% OF COVERED AREA - 14.2%
PHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER
THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT5.60 KW DC
14 Longi Solar 400W Modules (LR5-54HABB-400M)
ROOF PLAN
36'' Setback
18'' Setback
PV 0.0
N
0°
S
180°
E
90°
W
270°
SCALE
1" = 10'
MSP
INV
ACD
J/B
SolarEdge
Energy Bank Battery
Solar Array 1
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Gate
Solar Array 2
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg Solar Array 3
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
W CARLTON PL
Fence
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
SITE PLAN
PV 1.0
N
0°
S
180°
E
90°
W
270°
SCALE
1" = 15'
PROPERTY LINE
60'
95'
30'
10'
19'
25'
W CARLTON PL
Public Sidewalk
Driveway
MSP
INV
ACD
SolarEdge
Energy Bank Battery
Gate
Fence
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
STRUCTURAL STAMPROOF
PITCH
ROOFING
TYPE
ATTACHMENT
TYPE
FRAMING
TYPE
FRAMING
SIZE
PENETRATION
PATTERN
18°
RACKING
TYPE
MAX
PENETRATION
SPACING
ROOFING
LAYERS
WIND SPEED 95 MPH
SNOW LOAD 0 PSF
EXPOSURE C
LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE
SEALED WITH CHEM LINK SEALANT OR EQUIVALENT.
MODULE WEIGHT (LBS)
# OF MODULES
TOTAL MODULE WEIGHT (LBS)
RACK WEIGHT (LBS)
TOTAL SYSTEM WEIGHT (LBS)
# OF STANDOFFS
LOADING PER STANDOFF (LBS)
TOTAL MODULE AREA (SQ.FT.)
LOADING (PSF)
WEIGHT LOAD CALCULATION INDEX
ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER
SURFACE IS FACED WITH FELT PAPER
TOTAL ROOF AREA (Sq. FT)
% OF COVERED AREA
PV MODULE MODEL #
OPTIMIZERS WEIGHT (LBS)
14
Roof 1 Layer Comp Shingle Ironridge XR10 Rafter Stacked 48"2"X4" @ 24" O.C
3
1
2
4
ITEM NO.
1
DESCRIPTION
2
3
4
BOLT LAG 5/16 X 4.75"
ASSY, FLASHING
ASSY, CAPFOOT
WASHER, EPDM BACKED
Qty in Kit
4
4
4
4
5/16" X 4.75"
Flash Foot 2
MIN 2.5" EMBEDMENT
RACKING RAIL
ATTACHMENT
ROOF FRAMING
34
294
2075
694
139
21
854
25.1
2.91
14.2
2''X6'' Blocking
2''X4'' Support
2''X4'' Purlin
2''X6'' Collar Tie
SOLAR MODULE
ROOF
ASCE 7-16
Max 3.5''
49.6
LR5-54HABB-400M
ATTACHMENT
LAYOUT
S 1.0
48"24"
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
ITEM DESCRIPTION QTY#
PV MODULE
MAIN SERVICE PANEL
MAIN SERVICE PANEL
& UTILITY METER
BUSBAR RATING
BREAKER RATING
1
ITEM DESCRIPTION QTY#
PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3
1
1
1
4
3
1
4
6
MAIN
SERVICE
PANEL
120/240V
1P,3W
2
EXISTING
GROUNDING SYSTEM
UTILITY
2
3
INVERTER
PEAK PWR TRACKING VOLTAGE
INVERTER EFFICIENCY
ENCLOSURE :
MAXIMUM INPUT CURRENT
MAXIMUM OUTPUT CURRENT
MAXIMUM INPUT POWER
MAXIMUM OUTPUT POWER
4 1
5700W
380 V
99.0 %
NEMA 3R
10.5 A
16.0 A
7,600 W
3,800 W
SOLAREDGE ENERGY HUB SE3800H-US (240V)
SOLAREDGE POWER OPTIMIZER
RATED DC INPUT POWER
MAXIMUM INPUT VOLTAGE
MPPT RANGE
MAXIMUM SHORT CIRCUIT CURRENT (Isc)
MAXIMUM OUTPUT CURRENT
OPTIMIZER WEIGHT
MAXIMUM POWER PER STRING
5
S440
440W
60 Vdc
8 to 60 Vdc
14.5 Adc
15 Adc
1.5 Lbs
14POWER OPTIMIZER
30AAC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE,
BLADE TYPE, NEMA 3R, 120/240V 16
NEW UPGRADED
NEW
2
1
33
200A
200A
200A
FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3
14
LONGI SOLAR 400W
LR5-54HABB-400M
Voc = 37.05V
Vmp = 30.94V
Isc = 13.72A
Imp = 12.93A
String: (14) Modules, (14) Optimizers
SINGLE LINE
DIAGRAM
(2)#10 AWG (10-12 AWG), 600V insulated
(1)#24 AWG (16-24 AWG), 600V insulated or CAT6
1" EMT TYPE Conduit
BATTERY BACKUP BATTERY BACKUP SYSTEMS
SOLAR EDGE ENERGY BANK 10kWh, BAT-10K1P 17
EXTERIOR KNIFE SWITCH TYPE DISCONNECT
INSTALL 2P
20A CB(PV) AT
OPPOSITE END
OF BUS FROM
MAIN FEEDER CB
(N)200A
7
E 1.0
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
FROM PV MODULES TO JBOX
FROM JBOX TO INVERTER
(2)1
(1) #6 AWG BARE CU EGC,
2
#10 AWG CU EGC,
(3)
3
(1) #10 AWG CU EGC,
MAXIMUM INVERTER OUTPUT CURRENT (A)
TEMPERATURE FACTOR
TEMPERATURE ADJUSTMENT (A)
OUTPUT CALCULATIONS
PV SYSTEM MAX DC OUTPUT
PV SYSTEM MAX AC OUTPUT
MAXIMUM POWER (W)
PEAK PWR TRACKING VOLTAGE (V)
CONSIDER CONTINUOUS COEFFICIENT
SHORT CIRCUIT CURRENT (A)
ADJUSTED CONDUCTOR AMPACITY (A)
1.25
1.25
1.25
0.91
(2)
(1)
Pmax (PTC Rating)
16.0
380
1 99.0 %
16.0 * 1.25 / 0.91 22.0
#10 AWG THWN-2
SOLAR EDGE ENERGY HUB SE3800H-US (240V)
16.0 * 1.25 20.0
1 1/2''
(TEMP - 39 + 22 = 61C)0.58
RACEWAY HEIGHT FROM ROOF
ADJST. FACTOR (1 thru 3 WIRES)1.0
FREE IN THE AIR, 3/4'' EMT TYPE CONDUIT BETWEEN ARRAYS
3/4'' EMT TYPE CONDUIT
1'' EMT TYPE CONDUIT
MAIN SERVICE PANEL RATING
BUSBAR RATING
MAIN BREAKER
PV BACKFEED BREAKER SIZE
120% RULE:
MAX ALLOWED FEED
20A
*/*1.25 *1.2514400380 23.0
//23.0 0.58 1.0 39.7
#10 AWG THWN-2
WIRE CHART WIRE CHART
*14 400 5.60 KW
**14 373.7 0.99 5.18 KW
CONSIDER CONTINUOUS COEFFICIENT
CONSIDER CONTINUOUS COEFFICIENT
200A
200A
240A
200A ''MB'' + 20A "SOLAR" = 220A ≤ 240A MAX
FROM INVERTER TO MAIN SERVICE PANEL
CONSIDER CONTINUOUS (A)
MAX NUMBER OF MODULES IN STRING 14
#10 AWG PV-WIRE
14
400
LR5-54HABB-400M 400 W
373.7 W
WIRE SIZE
CALCULATIONS
E 1.1
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
JB
B
O
X
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
CEC 110.27(C)
In
v
e
r
t
e
r
/
P
V
L
o
a
d
WARNING
THE DISCONNECTION OF THE
GROUNDING CONDUCTOR(S)
MAY RESULT IN OVERVOLTAGE
ON THE EQUIPMENT
CEC 690.31(E)
CEC 690.54
AC
D
i
s
c
o
n
n
e
c
t
CEC 690.54
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
PM
M
E
T
E
R
Ma
i
n
/
S
u
b
P
a
n
e
l
CEC 690.54
CEC 690.13 (E), CEC 705.12(B)(C-D) & CEC 690.59
CEC 690.15 (B) & CEC 690.33(D)(2)
CEC 690.13(B)
SINGLE 120-VOLT SUPPLY
DO NOT CONNECT
MULTIWIRE BRANCH CIRCUIT!
CEC 710.15(C)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
CEC 110.27(C)
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
CEC 705.12 (B)(3)(2)
LABELING REQUIREMENTS FOR ARTICLE 690
CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether
in the open (off) or closed (on) position and be permanently marked “PV SYSTEM
DISCONNECT” or equivalent. Additional markings shall be permitted based upon
the specific system configuration.
CEC 690.13(E) Type of Disconnect. The PV system disconnecting means shall
simultaneously disconnect the PV system conductors that are not solidly grounded
from all conductors of other wiring systems. The PV system disconnecting means or
its remote operating device or the enclosure providing access to the disconnecting
means shall be capable of being locked in accordance with 110.25.
CEC 690.15(B) An isolating device shall not be required to have an interrupting
rating. Where an isolating device is not rated for interrupting the circuit current, it shall
be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting." An
isolating device shall not be required to simultaneously disconnect all current-carrying
conductors of a circuit.
CEC 690.31(B)(1) PV system dc circuit conductors shall be identified at all
termination, connection, and splice points by color coding, marking tape, tagging, or
other approved means.
CEC 690.31(D)(2) Unless located and arranged so the purpose is evident, the following wiring
methods and enclosures that contain PV system dc circuit conductors shall be marked with the
wording PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT by means of
permanently affixed labels or other approved permanent marking.
CEC 690.31(D)(2) PV system dc circuit labels shall appear on every section of the wiring
system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between
labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft).
Labels required in this section shall be suitable for the environment where they are installed.
CEC 690.31(E) Solidly-grounded bipolar PV systems shall be clearly marked with a
permanent, legible warning notice indicating that the disconnection of the grounded
conductor(s) may result in overvoltage on the equipment.
CEC 690.33(D)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a
tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting”.
CEC 690.6 Alternating-current (AC) modules and systems: The PV source circuit, conductors,
and inverters shall be considered as internal components of an ac module or ac module
system.
CEC 690.53 A permanent readily visible label indicating the highest
maximum dc voltage in a PV system, calculated in accordance with 690.7,
shall be provided by the installer.
CEC 690.54 All interactive system(s) points of interconnection with other
sources shall be marked at an accessible location at the disconnecting
means as a power source and with the rated ac output current and the
nominal operating ac voltage.
CEC 690.55 The PV system output circuit conductors shall be marked to
indicate polarity where connected to energy storage systems.
CEC 690.56(A) Plaques or directories shall be installed in accordance with
705.10.
CEC 690.56(C)(2) A rapid shutdown switch shall have a label located on
or no more than 1 meter (3 ft) from the switch.
CEC 690.59 PV systems connected to other sources shall be installed in
accordance with Parts I and II of Article 705 and Article 712.
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH ON THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
CFC 1205.4.1(1) & CEC 690.56(C)
CEC 690.56(C)(2)
CEC 690.31(D)(2)
CEC 690.31(D)(2)CO
N
D
U
I
T
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
WARNING
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT WARNING
CAUTION
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
WARNING
POWER SOURCE OUTPUT
CONNECTION. DO NOT
RELOCATE THIS
OVERCURRENT DEVICE.
WARNING
DO NOT DISCONNECT
UNDER LOAD
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING
PHOTOVOLTAIC POWER SOURCE
DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW
FOR SOLAR PHOTOVOLTAIC SYSTEMS THAT SHUT
DOWN THE ARRAY AND THE CONDUCTORS LEAVING
THE ARRAY, A LABEL SHALL BE PROVIDED. THE
FIRST TWO LINES OF THE LABEL SHALL BE
UPPERCASE CHARACTERS WITH A MINIMUM
HEIGHT OF 3/8 INCH (10 MM) IN BLACK ON A
YELLOW BACKGROUND. THE REMAINING
CHARACTERS SHALL BE UPPERCASE WITH A
MINIMUM HEIGHT OF 3/16 INCH (5 MM) IN BLACK ON
A WHITE BACKGROUND. [CFC 1205.4.1(1)]
240 Vac
240 Vac
240 Vac
CEC 690.13(B)
AC DISCONNECT
PHOTOVOLTAIC
16.0 A
16.0 A
16.0 A
CEC 705.10
CAUTION
MULTIPLE SOURCES OF POWER
CEC 705.10
CAUTION
MULTIPLE SOURCES OF POWER
CEC 690.53
MAXIMUM SYSTEM VOLTAGE
RATED SHORT CIRCUIT CURRENT
N/AMAX RATED AC OPERATING VOLTAGE
N/ARATED AC OPERATING VOLTAGE
MAX RATED AC OPERATING CURRENT
RATED AC OPERATING CURRENT
N/A
N/A
N/A
N/A
CAUTION
N
0°
S
180°
E
90°
W
270°
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
CEC 705.10 & CEC 690.56(B)
Permanent directory or plaque providing location of service disconnecting means and
photovoltaic system disconnecting means, if not located at the same location. (Plaques shall
be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a
contrasting color to the plaque. Plaques shall be permanently attached to the equipment or in the
required location using an approved method that is suitable to withstand the environment to which it
is exposed. Plaques and signage shall meet legibility, defacement, exposure and adhesion
requirements of Underwriters Laboratories marking and labeling system 969(UL969).
Plaques will have red background & white lettering.
CODE REQUIRED
SIGNAGE
DC
D
i
s
c
o
n
n
e
c
t
CEC 690.13(B)
DC DISCONNECT
PHOTOVOLTAIC
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)CEC 690.53
OF PV SYSTEM
MAXIMUM DC VOLTAGE
PV 2.0
W CARLTON PL
SOLAR INVERTER
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
SERVICE POINT &
UTILITY METERING
SOLAR ARRAY
ON THE ROOF
SOLAREDGE ENERGY
BANK BATTERY
SOLAR ARRAY
ON THE ROOF
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
[FOR INSTALLER USE ONLY]
PHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
5.60 KW DC
14 Longi Solar 400W Modules (LR5-54HABB-400M)
MODULE MAP
PV 2.1
Solar Array 1
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Solar Array 2
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
Solar Array 3
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
INVERTERPHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 3.8 Kw Inverter SE3800H-US (240V)
Solar Edge S440 Power Optimizers14
5.60 KW DC
[FOR INSTALLER USE ONLY]
14 Longi Solar 400W Modules (LR5-54HABB-400M)
INVERTER MAP
PV 3.0
Solar Array 1
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 270 Deg
Solar Array 2
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
Solar Array 3
4 Longi Solar 400W
4 S440 Optimizers
Tilt: 18 Deg
Azimuth: 0 Deg
Solar Array 4
3 Longi Solar 400W
3 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
1730 W Carlton Pl
10/23/2024
PV SYSTEM
AS INDICATED
October 1, 2024
ENRIQUE MORAN NOVOA
1730 W CARLTON PL
SANTA ANA, CA 92704
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Intersolar CAD
www.intersolarcad.com
PV SYSTEM DC SIZE 5.60KW
PV SYSTEM AC SIZE 5.18KW
MODULE
DATA SHEET
PV 3.1
1730 W Carlton Pl
10/23/2024