HomeMy WebLinkAbout5313 W Henderson Pl - PlanPAGE
REV: A3 10/29/2024
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N) NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
SURGE PROTECTOR TO BE INSTALLED PER MANUFACTURER
AND PANEL BOARD SPECS.
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-3.0 LAYOUT
PV-3.1 MOUNTING DETAIL
PV-3.2 MOUNTING DETAIL
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL CALCS
PV-4.2 BACKUP LOAD CALCS
PV-4.3 PANEL SCHEDULE
PV-5.0 SIGNAGE
PV-5.1 SIGNAGE
LTD: LR5-54HABB-400M
TESLA: POWERWALL 3 1707000-XX-Y
WITH STANDOFF TO FRAMING: SNR-DC-01249 [FLAT, FLUSH
MOUNT ( ROLLED COMP/ MEMBRANE/ FOAM) 1 LAG
OMNIBASE]; ULTRA RAIL, ATTACHMENT DETAIL, UMBRELLA L
FOOT TO FRAMING, SNR-DC-00339
1707000-XX-Y, 27 kWh
(MCI) ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE
PANEL WITH 50 AMP MAIN BREAKER TO BE REPLACED WITH
NEW 125 AMP MAIN PANEL WITH 125 AMP MAIN BREAKER
AND 225 AMP BUSBAR.
MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A).
MODULES, ARE CLASS A FIRE RATED.
CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30
SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE
ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
The scope of the plans is for the installation of the solar photovoltaic system only
and the approval is subject to compliance with all applicable city and state codes
and regulations regarding construction. The approval of the plans does not
constitute any certification of the accuracy, completeness, or building permit
status of the existing buildings and structures as shown.
Bldg#: 101121650
Elec#: 20184540
Approvals:
Elec: M Smith
5313 W Henderson
Pl2/5/2025
PAGE
REV: A3 10/29/2024
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
PL
PL
PL
PL PL
PL
PL
PL
PLPL
SITE PLAN
PV-2.0
#SSTAMPSP
#ESTAMPSP
NOTES:
RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
TOTAL ROOF SURFACE AREA: 2538 SQFT.
TOTAL PV ARRAY AREA: 441.4 SQ FT.
PERCENTAGE PV COVERAGE:
(TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
AREA) * 100 = 17.4%
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN
ACCORDANCE WITH R328.4. ESS UNITS SHALL BE SEPARATED FROM
EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT WHERE SMALLER
SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE
BASED ON LARGE/SCALE FIRE TESTING.
POWERWALL ENERGY
STORAGE SYSTEM (ESS)
BG BACKUP GATEWAY
GP GENERATION PANEL
ELECTRIC VEHICLE
SUPPLY EQUPMENTEV
MAIN PANEL
INVERTER(S)
AC DISCONNECT(S)
DC DISCONNECT(S)
SUNRUN METER
DEDICATED PV METER
SERVICE ENTRANCE
INTERIOR EQUIPMENT
SHOWN AS DASHED
SE
MP
SM
PM
INV
AC
DC
SUB-PANELSP
CB IQ COMBINER BOX
METER ADAPTERMA
GROUNDING
ELECTRODE
ENERGY STORAGE
SYSTEM
BP BACKUP LOADS PANEL
BI BACKUP INTERFACE 1 COMMUNICATION
WIRESAM
MD MICROGRID
INTERCONNECT DEVICE
ACREL METER
SOLAREDGE METERSEMPV LOAD CENTERLC
LEGEND
SCALE: NTS
NOTE: NOT ALL ITEMS IN LEGEND
WILL APPEAR IN SITE PLAN
RAIL
STANDOFFS &
FOOTINGS
SOLAR
MODULES
SITE PLAN - SCALE = 0'-0 3/64" = 1'-0"
(E) RESIDENCE
(N) ARRAY AR-01
(N) ARRAY AR-02
FIRE SETBACKS
(18" TYP)
ROOF PATHWAYS
(3' TYP)
SE
MP
AC
INV INV
W HENDERSON PL
GP
RSD
MD
ROOF PATHWAYS
(3' TYP)
AC
(E) FENCE
(E) GATE (TYP.)
EXTERNAL RAPID
SHUTDOWN SWITCH
RSD
A A A A A A A A
B B B B B B B
C C C C C C
(E) DETACHED
STRUCTURE
(E) PATIO
ARRAY
PITCH
PV AREA
(SQFT)
AR-01 6° 126.1
AR-02 18° 315.3179°
TRUE
AZIM
MAG
AZIM
167°179°
167°
NOTE: ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE
INSTALLED MODULE PER NEC 690.12
AC AC
10/29/2024
5313 W Henderson
Pl2/5/2025
PAGE
REV: A3 10/29/2024
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
#SSTAMP
DESIGN CRITERIA
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED:
96 MPH 3-SEC GUST.
FASTENERS:
(1) 5/16" DIA S.S. LAG SCREW: 2.5"
MIN EMBEDMENT INTO FRAMING
PV-3.0
LAYOUT
SOLAR MODULE
SNAPNRACK
RACKING
4"
MODULE ELEVATION DETAIL - SCALE: NTS
INSTALLERS SHALL NOTIFY ENGINEER OF ANY
POTENTIAL STRUCTURAL ISSUES OBSERVED
PRIOR TO PROCEEDING W/ INSTALLATION.
* IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12" BOUNDARY REGION OF
ANY ROOF PLANE EDGES (EXCEPT VALLEYS), THEN ATTACHMENTS
NEED TO BE ADDED AND OVERHANG REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS FOLLOWS:
** ALLOWABLE ATTACHMENT SPACING INDICATED ON PLANS TO BE
REDUCED BY 50%.
** ALLOWABLE OVERHANG INDICATED ON PLANS TO BE 1/5TH OF
ALLOWABLE ATTACHMENT SPACING INDICATED ON PLANS.
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION
Name Type Height Type Max
Span
OC
Spacing Detail Max Landscape
OC Spacing
Max Landscape
Overhang
Max Portrait
OC Spacing
Max Portrait
Overhang Configuration
AR-01
FLAT, ROLLED COMP
[FLUSH MOUNT] -
OMNIBASE 1 LAG - UR
1-Story 2X6 RAFTERS 7'-1" 24"
ULTRA RAIL, ATTACHMENT DETAIL,
OMNIBASE WITH STANDOFF TO FRAMING:
SNR-DC-01249 [FLAT, FLUSH MOUNT (
ROLLED COMP/ MEMBRANE/ FOAM) 1 LAG
OMNIBASE]
6'-0" 2'-4" 6'-0" 2'-3" STACKED
AR-02 COMP SHINGLE - UR -
UMBRELLA L FOOT 1-Story 2X4 PRE-FABRICATED TRUSSES 7'-7" 24"
ULTRA RAIL, ATTACHMENT DETAIL,
UMBRELLA L FOOT TO FRAMING,
SNR-DC-00339
6'-0" 2'-4" 6'-0" 2'-3" STACKED
SEE SITE PLAN FOR NORTH ARROW
D1 - AR-01 - SCALE: 1/8" = 1'-0"
AZIM: 179°
PITCH: 6°
D2 - AR-02 - SCALE: 1/8" = 1'-0"
AZIM: 179°
PITCH: 18°
SOLAR MODULE
SNAPNRACK RACKING AND
STANDOFF
MODULE ELEVATION DETAIL - SCALE: NTS
7"
6' TYP
30'-2"
11'-4"
8"20'-6"
1'-6"
1'-2"
6' TYP
22'-8"
5'-8"
3'3'-4"
1'-6"
1'
FASTENERS:
(1) 5/16" DIA S.S. UMBRELLA
SCREW: 2.5" MIN EMBEDMENT
INTO FRAMING
10/29/2024
5313 W Henderson
Pl2/5/2025
PAGE
REV: A3 10/29/2024
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
#SSTAMP
PV-3.1
MOUNTING DETAIL
DESCRIPTION:
UR-40 RAIL | UR-60 RAIL
FOR USE WITH SNAPNRACK ULTRA SERIES RAILS
15 8"
11 2"
11 2"
21 4"
SNAPNRACK ULTRA RAIL STANDARD STANDOFF
ON OMNIBASE FOR MOUNTING TO VARIOUS
ROOF TYPES
REFER TO SNAPNRACK ENGINEERING CHARTS
FOR APPLICABLE RAIL SPANS. "BIN" NUMBER ON
CHART SHOULD MATCH "BIN" NUMBER ON THIS
DRAWING
5 16"Ø S.S. LAG SCREW MUST EMBED A MIN. OF
21 2" INTO STRUCTURAL MEMBER
REFER TO SNAPNRACK INSTALLATION MANUAL
FOR 5 16"Ø HARDWARE TORQUE SPECIFICATIONS
SNAPNRACK OMNIBASE CAN MOUNT IN ANY
ORIENTATION ON THE ROOF
RAILS CAN MOUNT ON ANY SIDE OF THE
STANDOFF POST
FOR LEVELING DETAILS, REFER TO SNAPNRACK
DETAIL DRAWING "SNR-DC-00334 ULTRA RAIL,
COMPONENT DETAIL, LEVELING SPACER ON
STANDOFF" AND "SNR-DC-00447 ULTRA RAIL,
COMPONENT DETAIL, UR LEVELING SPACER"
*A POURED SEALANT-STYLE FLASHING MAY BE
USED WHEN INSTALLED PER THE
MANUFACTURER'S SPECIFICATIONS
INSTALLED
ATTACHMENT DETAIL
SNAPNRACK OMNIBASE
EXPLODED
SNAPNRACK, OMNIBASE
SNAPNRACK STANDOFF,
LENGTH VARIES
SNAPNRACK, UR STANDOFF
CLAMP ASSEMBLY. VARIES
FOR FLUSH AND TILT APPLICATIONS
MODULE HEIGHT OFF ROOF, RANGE:
UR-40: 73 4" - 87 8"
UR-60: 83 8" - 91 2"
(SHOWN FOR 7" STANDOFF,
ADJUST PER STANDOFF LENGTH)
OMNIBASE, TOP
BASE HEIGHT:
.70
4.00
3.00
7" STANDOFF SHOWN,
LENGTH VARIES
SNAPNRACK, ULTRA RAIL
(UR-40 SHOWN)
SNAPNRACK, ULTRA RAIL
(UR-40 SHOWN)
STRUCTURAL MEMBER,
WOOD RAFTER, TYP.
ROOF DECKING, TYP.
*FLASH STANDOFF APPROPRIATELY.
1"Ø VENT PIPE FLASHING SHOWN,
VARIES BY APPLICATION
SNAPNRACK RUBBER RAIN COLLAR
FOR 1"Ø CONE FLASHINGS
5 16"Ø S.S. LAG SCREW WITH
S.S. FLAT WASHER. CHOOSE
LENGTH FOR PROPER EMBEDMENT
5 16"Ø S.S. LAG SCREW WITH
S.S. FLAT WASHER. CHOOSE
LENGTH FOR PROPER EMBEDMENT
STRUCTURAL MEMBER,
WOOD RAFTER, TYP.
ROOF DECKING, TYP.
(1) 5/16" Ø S.S. LAG SCREW:
2.5" MIN EMBEDMENT INTO
FRAMING
SNR-DC-01249_UR_OMNI_STANDOFF TO RAFTER
10/29/2024
5313 W Henderson
Pl2/5/2025
CONDUIT SCHEDULE
TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT
1 Inverter Input (2) 10 AWG (PV WIRE)N/A 6 AWG (BARE) Open Air
2 Inverter Input (2) 10 AWG
THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4 EMT
2a Inverter Input (4) 10 AWG
THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4 EMT
3 Inverter Output (2) 6 AWG
THHN/THWN-2
(1) 6 AWG
THHN/THWN-2 8 AWG THHN/THWN-2 3/4 EMT
4 Backup gateway/
Generation panel Output
(2) 1 AWG
THHN/THWN-2
(1) 1 AWG
THHN/THWN-2 6 AWG THHN/THWN-2 1-1/4 EMT
5 Backup load Output
(4) 6 AWG
THHN/THWN-2
(4) 6 AWG
THHN/THWN-2 8 AWG THHN/THWN-2
1-1/4 EMT
(4) 6 AWG
THHN/THWN-2
(2) 6 AWG
THHN/THWN-2 8 AWG THHN/THWN-2
PAGE
REV: B 1/29/2025
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
NEW125A
MAIN BREAKER
END FED
NEW 125A
MAIN PANEL
225A BUS
NEW 200A
BACKUP GATEWAY
1841000-X1-Y
4
J-BOX
LONGI GREEN
ENERGY TECHNOLOGY CO LTD
LR5-54HABB-400M
STRING 1 OF 7 MODULES
3 MODULE LEVEL
RAPID SHUTDOWN DEVICES
LONGI GREEN
ENERGY TECHNOLOGY CO LTD
LR5-54HABB-400M
STRING 2 OF 8 MODULES
3 MODULE LEVEL
RAPID SHUTDOWN DEVICES
1
1
2a
J-BOX
LONGI GREEN
ENERGY TECHNOLOGY CO LTD
LR5-54HABB-400M
STRING 1 OF 6 MODULES
2 MODULE LEVEL
RAPID SHUTDOWN DEVICES
12
POINT OF INTERCONNECTION:705.12(B)(3)(2), GATEWAY
BREAKER AT OPPOSITE END OF BUSBAR
METER
NUMBER: 222013-570957
REPLACE EXISTING 50 MAIN
PANEL WITH NEW 125A MAIN PANEL 125A MAIN BREAKER
AND 225A BUS BAR
EQUIPMENT CHARACTERISTICS
INCLUDED IN SPEC SHEETS
NOTE: TOTAL PV BACKFEED
= 120A USED FOR INTERCONNECTION CALCULATIONS
M
125A
(N) IMO PE69-3020,
DISCONNECT
SWITCH, 3P, 16A
RSD
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT
3
RSD
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT
3
NEW 225 A GENERATION
AND BACKUP LOAD PANEL
(N) (2) 60A (PV+ESS)
BREAKER
4 60A
60A
FACILITY
GROUND
(E)
RELOCATED
BACKUP
LOADS
5
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A , 2P
120/240VAC
3
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A , 2P
120/240VAC
3
PV-4.0
ELECTRICAL
#ESTAMP
MODULE CHARACTERISTICS
LONGI GREEN ENERGY
TECHNOLOGY CO LTD:
LR5-54HABB-400M
400 W
OPEN CIRCUIT VOLTAGE 37.05 V
MAX POWER VOLTAGE 30.94 V
SHORT CIRCUIT CURRENT 13.72 A
GENERAL NOTES:
GROUND - UFER, TWO GROUNDS RODS OR
COLD WATER GAS BOND
IF THE RELOCATED LOADS EXTEND MORE
THAN 6 FEET, AFCI PROTECTION APPLIES
PER 2019 CEC 210.12
ANY MULTIWIRE BRANCH CIRCUITS
RELOCATED ARE TO BE IDENTIFIED,
GROUPED, AND EQUIPPED WITH A
2-POLE OCPD BREAKER PER CEC
210.4(B,D).
INSTALL THE BACKED UP LOAD CONDUCTORS AND THE GATEWAY BREAKER
CONDUCTORS IN TWO SEPARATE CONDUITS.
B
5313 W Henderson
Pl2/5/2025
PAGE
REV: A3 10/29/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
PV-4.1
ELECTRICAL CALCS
ELECTRICAL CALCS
SYSTEM INFORMATION
8.4 KW DC PHOTOVOLTAIC SYSTEM
(15) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
(6) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
SYSTEM OCPD SIZE
(COMBINED MAX CURRENT) X (CONTINUOUS LOAD) =
96 A X 1.25 = 120 A → 125 A OVERCURRENT PROTECTION
GATEWAY SYSTEM AC WIRE SIZING
MAX AC OUTPUT CURRENT = 125 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 145A = 131.95A
TERMINAL RATING[110.14(C)] =
1 AWG, 75°C RATED = 130A
130A < 131.95A TERMINAL RATING GOVERNS CONDUCTOR SIZING
125A < 130A 1 AWG AMPACITY OK
THEREFORE 1 AWG IS SUFFICIENT.
ALLOWABLE BACKFEED
ALLOWABLE BACKFEED = (MAIN PANEL RATING) X 1.2 - (MAIN BREAKER RATING) =
225A X 1.2 - 125A = 145A
125A ≤ 145A → INTERCONNECTION MEETS 705.12(B)(3)(2) REQUIREMENTS.
INVERTER INFORMATION
6.0 KW DC PHOTOVOLTAIC SYSTEM
(15) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS LOAD)[690.8(B)(1)]=
13.72 A X 1.25 X 1.25= 21.44A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 0.8 X 40A = 29.12A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
29.12A < 35A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
21.44A < 29.12A 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG,75°C RATED = 65A
65A < 68.25A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] + VOC} X
(# MODULES / STRING) =
{[(-0.26 %/°C X 37.05 V) / 100] X [-2 °C - 25 °C] + 37.05 V} X 8 = 317 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 13.72 A X 2 = 34.3A
INVERTER INFORMATION
2.4 KW DC PHOTOVOLTAIC SYSTEM
(6) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3
1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS
LOAD)[690.8(B)(1)]=
13.72 A X 1.25 X 1.25= 21.44A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, RATED = 35A
35A < 36.4A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
21.44A < 35A 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG,75°C RATED = 65A
65A < 68.25A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] + VOC} X
(# MODULES / STRING) =
{[(-0.26 %/°C X 37.05 V) / 100] X [-2 °C - 25 °C] + 37.05 V} X 6 = 238 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 13.72 A X 1 = 17.15A
5313 W Henderson
Pl2/5/2025
BACKUP LOADS
LOAD BREAKER RATING
(AMPS)LABEL DEMAND
LOAD
1 20A-1P KITCHEN 1500 VA
2 20A-1P KITCHEN 1500 VA
3 20A-2P OTHER 3840 VA
5 15A-1P ROOMS 1500 VA
6 15A-1P ROOMS 1500 VA
7 30A-2P DRYER 5760 VA
PAGE
REV: A3 10/29/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
BACKUP LOAD CALCS
ALL BACKED UP LOADS ABOVE IN THE BACKED UP LOADS PANEL ARE RELOCATED FROM THE MAIN SERVICE
PANEL.
BACKED UP LOADS CALCULATION:
(5760 VA)/ 240V = 24 A PER CEC 2022 ARTICLE 690.10 OR NEC 2020 ARTICLE 710.15.
THE MAXIMUM CURRENT FOR ALL LARGE APPLIANCES LOADS IS 40A.
(MAX LOADS OUTPUT) X (CONTINUOUS LOADS) =
24 A X 1.25 = 30A
BACKED UP LOADS PANEL BREAKER = 125A
30 A < 125A.
THEREFORE, THE AMPERAGE OF THE BACKED UP LOADS IS LESS THAN THAT OF THE OCPD.
AC WIRE SIZING FOR BACKUP LOADS PANEL
MAX AC OUTPUT CURRENT = (MAX LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
24 A X 1.25 = 30 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
30A < 35A 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
PV-4.2
BACKUP LOAD
CALCS
5313 W Henderson
Pl2/5/2025
PAGE
REV: A3 10/29/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
(N) GATEWAY
FEEDER BREAKER
MAIN BREAKER
125
NEW PV+ESS
BREAKER60
FUTURE BACKUP LOAD
PANEL
30
LIGHTS /RECEPTABLES
15
15
20
ROOMS
LIGHTS /RECEPTABLES
DRYER
NEW 225/125A
MAIN PANEL
PANEL SCHEDULE
PANEL SCHEDULE
PV-4.3
12
5
20KITCHEN
NEW PV+ESS
BREAKER60
20 OTHER
5313 W Henderson
Pl2/5/2025
PAGE
REV: A3 10/29/2024
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.0
#ESTAMP
ENERGY STORAGE SYSTEM
DISCONNECT
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
POWER SOURCE OUTPUT CONNECTION
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
CEC 2022: 705.12(B)(3)(2)
NOTES AND SPECIFICATIONS:
SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE CEC 2022
ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY
SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.
SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING
EFFECTIVE WORDS, COLORS AND SYMBOLS.
LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR
WIRING METHOD AND SHALL NOT BE HAND WRITTEN.
LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED.
SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT
SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
DO NOT COVER EXISTING MANUFACTURER LABELS.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
4"
3"
ELECTRICAL SHOCK HAZARD
WARNING
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S),
AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC
2022: 690.13(B)
!
INVERTER 1
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:
690.31(D)(2)CAUTION
5313 W HENDERSON PL, SANTA ANA, CA, 92704
SOLAR PANELS ON ROOF
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
MULTIPLE SOURCES OF POWER
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC
2022: 705.12(C)
ENERGY STORAGE SYSTEM
PREMISES WIRING MAY REMAIN
ENERGIZED AFTER LOSS OF
UTILITY POWER
CAUTION!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C)
AC DISCONNECT
INVERTER & ENERGY STORAGE
(EXT)
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
INVERTER 2
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
BACKUP GATEWAY
GENERATION AND BACKUP LOADS PANEL
SERVICE ENTRANCE AND
GATEWAY FEEDER BREAKER
RAPID SHUTDOWN SWITCH
5313 W Henderson
Pl2/5/2025
PAGE
REV: A3 10/29/2024
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.1
#ESTAMP
LABEL LOCATION:
BACKUP LOAD PANEL
NO ADDITIONAL
LOADS TO BE
ADDED
ENERGY STORAGE SYSTEM DISCONNECT
NOMINAL ESS VOLTAGE VAC
LABEL LOCATION:
MAIN PANEL.
120 240
CEC 2022 - PW3
PER CODE(S): CEC 2022: NEC 706.15(C)
5313 W Henderson
Pl2/5/2025
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 1 of 8 GFT-OP-11a (22-August-2019)
Test Verification of Conformity
Verification Number: 104514208CRT-001VOC
Applicant Name & Address:
Tesla Inc.
3500 Deer Creek Road, Palo Alto, CA 94304
Product Description:
Energy Storage System Grid Support Utility Interactive & Standalone Inverter
Ratings & Principle
Characteristics:
See Appendix 2
Models/Type References:
1707000- followed by two numbers; followed by -; followed by one letter.
Brand Names:
Tesla
Relevant Standard(s) /
Specification(s):
See Appendix 1
Verification Issuing Office Name
& Address:
Intertek Testing Services NA, Inc.
3933 US Route 11, Cortland, NY 13045 USA
Date of Tests:
9/15/2022 to 4/23/2024
Test Report Number(s): 104514208CRT-001, 104514208CRT-001RRF, 104514208CRT-001TRS,
104514208CRT-010, 104514208CRT-012
Additional information in Appendix.
Signature
Name: Mukund Rana
Position: Sr. Staff Engineer
Date: 10th May 2024
On the basis of the tests undertaken, the samples of the below product have been found to comply with the
requirements of the referenced standards at the time the tests were carried out. This verification is part of the full
test report and should be read in conjunction with it.
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 2 of 8 GFT-OP-11a (22-August-2019)
Appendix 1: Relevant Standard(s)/Specification(s)
Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources
[UL 1741:2021 Ed.3]
Grid Support Utility Interactive Equipment - Supplement SA to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers
and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement
SA)]
Grid Support Utility Interactive Inverters and Converters Based Upon IEEE 1547:2018 & IEEE 1547.1:2020 -
Supplement SB to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers and Interconnection System Equipment for
use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement SB)]
Energy Storage Systems and Equipment [ANSI/UL 9540:2020 Ed.2+R:09Apr2021]
Photovoltaic (PV) DC Arc-Fault Circuit Protection [UL 1699B:2018 Ed.1+R:18May2021]
Software in Programmable Components [UL 1998:2013 Ed.3+R:24Sep2018]
Tests For Safety-related Controls Employing Solid-state Devices [UL 991:2004 Ed.3+R:09Jun2010]
Batteries for Use in Stationary, Vehicle Auxiliary Power and Light Electric Rail (LER) Applications [ANSI/UL 1973:2018
Ed.2]
IEEE 1547:2018 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with
Associated Electric Power Systems Interfaces
IEEE 1547a:2020 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with
Associated Electric Power Systems Interfaces
Amendment 1: To Provide More Flexibility for Adoption of Abnormal Operating Performance Category III
IEEE 1547.1:2020 - IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy
Resources with Electric Power Systems and Associated Interfaces
Source requirements document UL 1741 (SRD) v2.0 – HECO
Electric Rule No.21-2020 Generating Facility Interconnections
Default New England Bulk System Area Settings Requirement
PRC-024-3 Frequency and Voltage Protection Settings for Generating Resources
GOVERNMENT OF PUERTO RICO PUBLIC SERVICE REGULATORY BOARD PUERTO RICO ENERGY BUREAU, Generating
Facility and Microgrid Interconnection Regulation (“Regulation”), July 2021
Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1]
Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2]
Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2]
Safety Functions Incorporating Electronic Technology [CSA C22.2#0.8:2019 Ed.4]
5313 W Henderson
Pl2/5/2025
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 3 of 8 GFT-OP-11a (22-August-2019)
Appendix 2: Ratings & Principle Characteristics:
➢ Ratings:
Models 1707000-xx-y
Rated AC Output Power (W) 11500, 10000, 7680, 5750
Rated AC Input Power (W) Charging 5000
Max. Cont. Output Power (W) 11500, 10000, 7680, 5750
Max. Continuous Output PV to AC
Power Off-Grid (W) 15400
Max. Cont. Input Power (W) Charging 5000
AC Input / Output Voltage
(VL-L) 240
AC Output Frequency
(Hz) 60
Max. Cont. Output Current (A) 48, 4 1.6, 32, 24
Max. Cont. Input Current (A) Charging 20.83
Apparent Power rating (VA) 11500, 10000, 7680, 5750
Apparent Power rating (VA) Charging 5000
Normal Category A, B
Abnormal Category II, III
➢ Communication Protocol: IEEE 2030.5 protocol
➢ PCH board MD5 Firmware checksum: c5773b136a9ef9be9057302a67258482
➢ TACO board MD5 Firmware checksum: dcq8OiBXbQWYnK9UhCAjvl02/py2MZymmwAQYOn8jSc=
➢ Grid Support Function Parameters:
Tesla used the parameters in the Result reporting form “104514208CRT-001RRF” during the testing of the grid
support functions according to UL1741 SB. The parameters that have “blank” as their value are not applicable.
➢ UL 1998 and CSA C22.2#0.8 Evaluation:
ECU / Board Rev Software version Checksum UL1998, CSA C22.2#0.8
Compliant*
Date of evaluation
HVP / -E V2 51705DB5 Yes Apr-19-2024
PWS / -3F V2 34204954 Yes Apr-19-2024
PWS / -1F V2 B3C1375B Yes Apr-19-2024
PWS / -D V2 43FEF523 Yes Apr-19-2024
*Note: Below safety functions were evaluated during the UL1998 and UL 991 evaluation.
• List of all UL1998 and UL 991 functions are as follow:
o Overcharge
o Over-discharge
o Over Temperature
o Over current
o Relay weld, Isolation Monitoring Interruption, PV RSD (UL 1741)
o AFCI (UL 1699B)
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 4 of 8 GFT-OP-11a (22-August-2019)
5313 W Henderson
Pl2/5/2025
!
"
#$
$% &
!
" '() *$
' *
" +
'
,(-./)0
1'
*
#1
$
1'
#
2
$"
+)
$"
+
%
#$% &
!
1'
)+
!
%
#
'
)
#2*
$"
+1
*
$"
+
3
#
43
5
)6
57...*
57...&*
5#+#
&8
!
97
'"
*
"
1
""
%
5
#
!
)+
9
*
7
'
:$"
-
# ;.<2=><2?
0
(
1
"
+
"
+
#
"
'
"
'
+
+
+
,22
E
F
'"
"G
H
*8 '
"
+
.
Sep 16, 2020
5 .>-2=&>2?
0
.&2=2?
%!
"
1
+
&2@9=2@?
2@9=2@?
+
/%-;
#
#
#'A3B1$% &
0 )
0%&
71C$><;;>>&<
$".+ *#.
*
#
8
# ="?&.-2"=/)?=&.;2*#?
" 'D
'+#/)
*#/
*
#
# .2=.>2?
*
#
8 .>2=&;.<><2?
*
#
# &.<2=<.>>2?
++
)
" '
)
"
++
7
%
#
% 0
% +
+)3D
%/)0
!
%/)0
1:
!'
+
D
'+
D
)
:
+
D
)
#
)
!
)
= +
)
#
?
%!
0
%!
+
5313 W Henderson
Pl2/5/2025
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 5 of 8 GFT-OP-11a (22-August-2019)
Appendix 3: List of Tested Grid protection / Support Function:
Table 3A: Test List -1
Grid protection / Support
Function Tested
Test Standards Sections and Source Requirement Documents
IEEE 1547-
2018
IEEE 1547.1-
2020
UL 1741SB -
2021 CA Rule 21:2020
UL 1741 SRD
V2.0
(HECO):2020
OPERATIONAL TEMPERATURE -- 5.3.3.1 SB4.3.5.3 -- Same as 1547-
2018
PROTECTION FROM
ELECTROMAGNETIC
INTERFERENCE (EMI) TEST
4.11.1 5.8.1 SB4.3.5.8.1 -- Same as 1547-
2018
SURGE WITHSTAND
PERFORMANCE TEST 4.11.2 5.8.2 SB4.3.5.8.2 -- Same as 1547-
2018
PARALLELING DEVICE 4.11.3 5.8.3 -- -- Same as 1547-
2018
OVERVOLTAGE TRIP 6.4.1 5.4.2 SB4.3.5.4.2 Electric Rule No.
21 Table Hh.1
Same as 1547-
2018
UNDERVOLTAGE TRIP 6.4.1 5.4.3 SB4.3.5.4.3 Electric Rule No.
21 Table Hh.1
Same as 1547-
2018
OVERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2
SB4.3.5.5.1
&
SB4.3.5.5.2
Electric Rule No.
21 Table Hh.2
Same as 1547-
2018
UNDERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2
SB4.3.5.5.1
&
SB4.3.5.5.2
Electric Rule No.
21 Table Hh.2
Same as 1547-
2018
LOW VOLTAGE RIDE-THROUGH 6.4.2.3 &
6.4.2.5 5.4.4 SB4.3.5.4.4 Electric Rule No.
21 Table Hh.1
Same as 1547-
2018
HIGH VOLTAGE RIDE-THROUGH 6.4.2.4 5.4.7 SB4.3.5.4.7 Electric Rule No.
21 Table Hh.1
Same as 1547-
2018
LOW FREQUENCY RIDE-THROUGH 6.5.2.3 5.5.3 SB4.3.5.5.3 Electric Rule No.
21 Table Hh.2
SRD-UL-1741-SA-
V2.0 (HECO) Part
II B
HIGH FREQUENCY RIDE-
THROUGH 6.5.2.4 5.5.4 SB4.3.5.5.4 Electric Rule No.
21 Table Hh.2
SRD-UL-1741-SA-
V2.0 (HECO) Part
II B
RATE OF CHANGE OF FREQUENCY 6.5.2.5 5.5.5 -- -- Same as 1547-
2018
ANTI-ISLANDING PROTECTION -
WITH GRID SUPPORT FUNCTIONS
ENABLED
8.1 5.10.2 SB4.3.5.10.2 Electric Rule No.
21 Hh.1a
According to UL
1741 SA-V2.0
(HECO)
TEST FOR VOLTAGE PHASE-ANGLE
CHANGE RIDE-THOUGH
(VARIATION 1)
6.5.2.6 5.5.6.1 SB4.3.5.5.6 -- Same as 1547-
2018
ENTER SERVICE 4.10 5.6 -- -- Same as 1547-
2018
SYNCHRONIZATION CONTROL
FUNCTION TEST FOR EQUIPMENT
WITH NO SYNCHRONIZING
DISABLE CAPABILITY (VARIATION
3)
6.3 5.7.4 -- -- Same as 1547-
2018
LIMITATION OF DC INJECTION
FOR INVERTERS 7.1 5.9 -- Electric Rule No.
21 Hh.2h
Same as 1547-
2018
OPEN PHASE 6.2.2 5.11 -- -- Same as 1547-
2018
CURRENT DISTORTION 7.3 5.12 -- Electric Rule No. Same as 1547-
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 6 of 8 GFT-OP-11a (22-August-2019)
Grid protection / Support
Function Tested
Test Standards Sections and Source Requirement Documents
IEEE 1547-
2018
IEEE 1547.1-
2020
UL 1741SB -
2021 CA Rule 21:2020
UL 1741 SRD
V2.0
(HECO):2020
21 Hh.2g 2018
LIMIT ACTIVE POWER 4.6.2 5.13 -- Electric Rule No.
21 Hh.8
Same as 1547-
2018
CONSTANT POWER FACTOR 5.3.2 5.14.3 SB4.3.5.14.3 Electric Rule No.
21 Hh.2i
Same as 1547-
2018
VOLTAGE-REACTIVE POWER
(VOLT-VAR) MODE FIXED VREF 5.3.3 5.14.4 SB4.3.5.14.4 Electric Rule No.
21 Hh.2J
Same as 1547-
2018
VOLTAGE-REACTIVE POWER
(VOLT-VAR) MODE (VREF TEST) 5.3.3 5.14.5 SB4.3.5.14.5 -- Same as 1547-
2018
ACTIVE POWER-REACTIVE POWER
MODE (WATT-VAR) 5.3.4 5.14.7 SB4.3.5.14.7 -- Same as 1547-
2018
CONSTANT REACTIVE POWER
(VAR) MODE 5.3.5 5.14.8 SB4.3.5.14.8 -- Same as 1547-
2018
VOLTAGE-ACTIVE POWER (VOLT-
WATT) MODE 5.4 5.14.9 SB4.3.5.14.9 Electric Rule No.
21 Hh.2.m
Same as 1547-
2018
TEST FOR FREQUENCY -DROOP
(FREQUENCY-POWER OR
FREQUENCY-WATT) CAPABILITY —
ABOVE NOMINAL FREQUENCY
6.5.2.7 5.15.2 SB4.3.5.15.2 Electric Rule No.
21 Hh.2.l
SRD-UL-1741-SA-
V2.0 (HECO) Part
II C
TEST FOR FREQUENCY -DROOP
(FREQUENCY-POWER OR
FREQUENCY-WATT) CAPABILITY —
BELOW NOMINAL FREQUENCY
6.5.2.7 5.15.3 SB4.3.5.15.3 Electric Rule No.
21 Hh.2.l
SRD-UL-1741-SA-
V2.0 (HECO) Part
II C
PRIORITIZATION OF DER
RESPONSES 4.7 5.16 SB4.3.5.16 -- Same as 1547-
2018
LOAD REJECTION OVERVOLTAGE
(LROV) 7.4 5.17.2 SB4.3.5.17.2 -- Same as 1547-
2018
FAULT CURRENT TESTS FOR
INVERTERS 6.2.1 5.18.1 -- -- Same as 1547-
2018
PERSISTENCE OF DER PARAMETER
SETTINGS -- 5.19 -- -- Same as 1547-
2018
NORMAL RAMP RATE -- -- -- Electric Rule No.
21 Hh.2k --
NAMEPLATE DATA TEST 10.3 6.4 -- -- Same as 1547-
2018
MONITORING INFORMATION
TEST 10.5 6.6 SB4.3.6.6 -- Same as 1547-
2018
MANAGEMENT INFORMATION
TEST 10.6 6.7 SB4.3.6.7 -- Same as 1547-
2018
5313 W Henderson
Pl2/5/2025
5313 W Henderson
Pl2/5/2025
Powerwall 3
Power Everything
2024
—
Powerwall 3 is a fully integrated solar and battery system, designed to accelerate the transition to sustainable energy. Customers
can receive whole home backup, cost savings, and energy independence by producing and consuming their own energy while
participating in grid services. Once installed, customers can manage their system using the Tesla App to customize system
behavior to meet their energy goals.
Powerwall 3 achieves this by supporting up to 20 kW DC of solar and providing 11.5 kW AC of continuous power per unit. It has
the ability to start heavy loads up to 185 A LRA, meaning a single unit can support the power needs of most homes. Powerwall 3
is designed for mass production,fast and efcient installations,easy system expansion,and simple connection to any electrical
service.
22024Powerwall 3 Datasheet
Solar Technical
Specications
Maximum Solar STC Input 20 kW
Withstand Voltage 600 V DC
PV DC Input Voltage Range 60 — 550 V DC
PV DC MPPT Voltage Range 60 — 480 V DC
MPPTs 6
Maximum Current per MPPT (Imp)13 A 5
Maximum Short Circuit Current per MPPT (Isc)15 A 5
Powerwall 3 Technical Specifications
1 Typical solar shifting use case.
2 Values provided for 25°C (77°F), at beginning of life. 3.3 kW charge/discharge power.
3 Tested using CEC weighted efciency methodology.
4 The customer is expected to provide internet connectivity for Powerwall 3;cellular should not be used as the primary mode of
connectivity. Cellular connectivity subject to network operator service coverage and signal strength.
5 Where the DC input current exceeds the MPPT rating,a jumper can be used to combine two MPPTs into a single input to
intake DC current up to 26 A IMP / 30 A ISC.
Battery Technical
Specications
Nominal Battery Energy 13.5 kWh AC 2
Maximum Continuous Discharge Power 11.5 kW AC
Maximum Continuous Charge Power 5 kW AC
Output Power Factor Rating 0 -1 (Grid Code congurable)
Maximum Continuous Current 48 A
Maximum Output Fault Current 10 kA
Load Start Capability (1 s)185 A LRA
Power Scalability Up to 4 Powerwall 3 units supported
System Technical
Specications
Model Number 1707000-xx-y
Nominal Grid Voltage (Input &Output)120/240 VAC
Grid Type Split phase
Frequency 60 Hz
Overcurrent Protection Device 60 A
Solar to Battery to Home/Grid Efciency 89% 1,2
Solar to Home/Grid Efciency 97.5% 3
Supported Islanding Devices Gateway 3, Backup Switch, Backup Gateway 2
Connectivity Wi-Fi (2.4 and 5 GHz), Dual-port switched Ethernet,
Cellular (LTE/4G 4)
Hardware Interface Dry contact relay,Rapid Shutdown (RSD)certied switch
and 2-pin connector, RS-485 for meters
AC Metering Revenue Grade (+/- 0.5%)
Protections Integrated arc fault circuit interrupter (AFCI), Isolation
Monitor Interrupter (IMI),PV Rapid Shutdown (RSD)using
Tesla Mid-Circuit Interrupters
Customer Interface Tesla Mobile App
Warranty 10 years
5313 W Henderson
Pl2/5/2025
5313 W Henderson
Pl2/5/2025
!"#!$
%$&
'
(
)( *+ ,-
((* ,
. ) ./
( *
00+&1&2!!
%
.
.3(
4
/
*4
.
.3 #!5$
/
.(
/(
671
.(
.3 %$&
..
*8
./)(
..
4
*.
((
(.
%. .3*8
/
-)
/(
(
(..
.3
*
.3
.
( *
"(
3
.3 !"$
9
$:222$&
(-.-
$: 222$&88
-8(
-
.
*
:;#2615--<72715.=
3 2#!5--<;2#&5.=
8 ;1215--<&2715.=
3
..3 >
&2;152-<&15()/2.=!2!!?!2!:5.@<2!6?12#5--@=$: 222$:!=
&2;152-<&15()/2.=$: 222$:!=
12!652-< 15()/2.=!2!:5.@<62&75--@=$6=
12!652-< 15()/2.=!2!?!2!&5.@<:2&?:2:5--@=$#222$ =
12#152-<1!5()/2.=!2! 5.@<#2#75--@=$&=
.3
.88.3
(
3*!!:!#AB%$&B&!!!$
.
(
:$
(
-
+
-
.
.
.
.
.
)
/
.
.
)
/
-
.
.
3
)
(
*
(
)
(
*
/
8
/
8
/
8
8
(
.
Feb 3, 2020
:
!!761;!: ;: ;:
,
3
4
3 <)=2::5,3< 2#15()<==
.
)( *C
. */3.%D
//
.
)( *
.
)(
//
.
--8
(/.
88 .#1 $+8
.
E8
*
-
(.(.3+
.(
-8.4
,.4.
/
(/.
.3
.A
8 '
-2-
./-
.3
44428#14
..32
23'
$
3(
.$
(
.
$/
/"C
'
-8(
.
(
.
E
'*-
(/
C
%
*/
C
E
-8 ../-
.C
.
3(
..
(
.
'
.
(
.< /.
(
3
(8
=
.'.-
.
((
.'.-
.
(/(
(
*/(
.
/8
/
*(.38
.
.
(4
. *
. *:6-.
5313 W Henderson
Pl2/5/2025
32024Powerwall 3 Datasheet
Mechanical
Specications
Dimensions 1099 x 609 x 193 mm (43.25 x 24 x 7.6 in)
Weight 130 kg (287 lb)
Mounting Options Floor or wall mount
Powerwall 3 Technical Specifications
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F) 6
Operating Humidity (RH)Up to 100%, condensing
Storage Temperature –20°C to 30°C (–4°F to 86°F), up to 95% RH, non-
condensing, State of Energy (SOE): 25% initial
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
Enclosure Rating NEMA 3R
Ingress Rating IP67 (Battery & Power Electronics)
IP45 (Wiring Compartment)
Pollution Rating PD3
Operating Noise @ 1 m < 50 db(A) typical
<62 db(A)maximum
Compliance
Information
Certications UL 1642, UL 1699B, UL 1741, UL 1741 SA, UL 1741 SB, UL
1741 PCS, UL 3741, UL 1973, UL 1998, UL 9540, IEEE 1547-
2018, IEEE 1547.1, UN 38.3
Grid Connection United States
Emissions FCC Part 15 Class B
Environmental RoHS Directive 2011/65/EU
Seismic AC156, IEEE 693-2005 (high)
Fire Testing Meets the unit level performance criteria
of UL 9540A
6 Performance may be de-rated at operating temperatures above 40°C (104°F).
609 mm 193
mm
1099 mm
42024Powerwall 3 Datasheet
Electrical
Specications
Model MCI-1 MCI-2
Nominal Input DC Current Rating (IMP)13 A 13 A
Maximum Input Short Circuit Current (ISC)19 A 17 A
Maximum System Voltage (PVHCS)600 V DC 1000 V DC 7
Solar Shutdown Device Technical Specifications
Environmental
Specications
Operating Temperature -40°C to 50°C
(-40°F to 122°F)
-45°C to 70°C
(-49°F to 158°F)
Storage Temperature –30°C to 70°C
(–22°F to 158°F)
–30°C to 70°C
(–22°F to 158°F)
Enclosure Rating NEMA 4X /IP65 NEMA 4X /IP65
RSD Module
Performance
Maximum Number of Devices per String 5 5
Control Power Line Excitation Power Line Excitation
Passive State Normally Open Normally Open
Maximum Power Consumption 7 W 7 W
Warranty 25 years 25 years
—
The Solar Shutdown Device is a Mid-Circuit Interrupter (MCI)and is part of the PV system rapid shutdown (RSD)function in
accordance with Article 690 of the applicable NEC. When paired with Powerwall 3, solar array shutdown is initiated by any loss
of AC power.
Mechanical
Specications
Electrical Connections MC4 Connector MC4 Connector
Housing Plastic Plastic
Dimensions 125 x 150 x 22 mm
(5 x 6 x 1 in)
173 x 45 x 22 mm
(6.8 x 1.8 x 1 in)
Weight 350 g (0.77 lb) 120 g (0.26 lb)
Mounting Options ZEP Home Run Clip
M4 Screw (#10)
M8 Bolt (5/16")
Nail / Wood screw
Wire Clip
Compliance
Information
Certications UL 1741 PVRSE, UL 3741,
PVRSA (Photovoltaic Rapid Shutdown Array)
RSD Initiation Method External System Shutdown Switch or
Powerwall 3 Enable Switch
7 Maximum System Voltage is limited by Powerwall to 600 V DC.
UL 3741 PV Hazard Control
(and PVRSA)Compatibility See Powerwall 3 Installation Manual
5313 W Henderson
Pl2/5/2025
52024Powerwall 3 Datasheet
Gateway 3
8 Only Eaton CSR or BWH main breakers are 25 kA rated.
Performance
Specications
Model Number 1841000-01-y
Nominal Grid Voltage 120/240 V AC
Grid Conguration Split phase
Grid Frequency 60 Hz
Continuous Current
Rating
200 A
Maximum Supply Short
Circuit Current
22 kA with Square D or
Eaton main breaker
25 kA with Eaton main
breaker 8
IEC Protective Class Class I
Overvoltage Category Category IV
Mechanical
Specications
Dimensions 660 x 411 x 149 mm
(26 x 16 x 6 in)
Weight 16.3 kg (36 lb)
Mounting options Wall mount
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
Operating Humidity (RH)Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
Enclosure Type NEMA 3R
Compliance
Information
Certications UL 67, UL 869A, UL 916, UL 1741 PCS,
CSA 22.2 107.1, CSA 22.2 29
Emissions FCC Part 15, ICES 003
—
Tesla Gateway 3 controls connection to the grid in a Powerwall system, automatically detecting outages and providing seamless
transition to backup power. It provides energy monitoring that is used by Powerwall for solar self-consumption, time-based
control, and backup operation.
411 mm
660
mm
149
mm
AC Meter Revenue accurate (+/- 0.5%)
Communication CAN
User Interface Tesla App
Backup Transition Automatic disconnect for
seamless backup
Overcurrent
Protection Device
100–200 A
Service entrance rated
Eaton CSR, BWH, or BW, or
Square D QOM breakers
Internal Panelboard 200 A
8-space/16 circuit breakers
Eaton BR, Siemens QP, or
Square D HOM breakers rated
to 10–125A
Warranty 10 years
62024Powerwall 3 Datasheet
Backup Switch
9 Breaker maximum supply short circuit current rating must be equal to or greater than the available fault current.
Performance
Specications
Model Number 1624171-xx-y
Continuous Load Rating 200 A, 120/240 V split phase
Maximum Supply Short Circuit Current 22 kA with breaker 9
Communication CAN
AC Meter Revenue accurate (+/- 0.5%)
Expected Service Life 21 years
Warranty 10 years
Mechanical
Specications
Dimensions 176 x 205 x 74 mm (6.9 x 8.1 x 2.9 in)
Weight 2.8 lb
Meter and Socket Compatibility ANSI Type 2S, ringless or ring type
External Service Interface Contactor manual override 10
Reset button
Conduit Compatibility 1/2-inch NPT
Environmental
Specications
Operating Temperature –40°C to 50°C (–40°F to 122°F)
Storage Temperature –40°C to 85°C (–40°F to 185°F)
Enclosure Rating NEMA 3R
Pollution Rating PD3
Compliance
Information
Safety Standards USA: UL 414, UL 414 SB, UL 2735, UL 916, CA Prop 65
Emissions FCC, ICES
10 Manually overrides the contactor position during a service event.
—
The Tesla Backup Switch controls connection to the grid in a Powerwall system, and can be easily installed behind the utility
meter or in a standalone meter panel downstream of the utility meter.
The Backup Switch automatically detects grid outages, providing a seamless transition to backup power. It communicates
directly with Powerwall, allowing home energy usage monitoring from any mobile device with the Tesla app.
204.86
74
176 mm
205 mm
74 mm
5313 W Henderson
Pl2/5/2025
72024Powerwall 3 Datasheet
Backup Gateway 2
Performance
Specications
Model Number 1232100-xx-y
AC Voltage (Nominal)120/240 V
Feed-in Type Split phase
Grid Frequency 60 Hz
Current Rating 200 A
Maximum Supply Short
Circuit Current
10 kA 11
Overcurrent Protection
Device
100 - 200 A, Service
entrance rated 9
Overvoltage Category Category IV
Internal Primary
AC Meter
Revenue accurate
(+/- 0.2%)
Internal Auxiliary
AC Meter
Revenue accurate
(+/- 2%)
Primary Connectivity Ethernet, Wi-Fi
Secondary Connectivity Cellular (3G, LTE/4G) 12
Mechanical
Specications
Dimensions 660 x 411 x 149 mm
(26 x 16 x 6 in)
Weight 20.4 kg (45 lb)
Mounting options Wall mount,
Semi-Bush mount
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
Operating Humidity (RH)Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
Enclosure Type NEMA 3R
Compliance
Information
Certications UL 67, UL 869A, UL 916, UL 1741 PCS,
CSA 22.2 0.19, CSA 22.2 205
Emissions FCC Part 15, ICES 003
411 mm
660 mm
149
mm
11 When protected by Class J fuses, Backup Gateway 2 is
suitable for use in circuits capable of delivering not more
than 22kA symmetrical amperes.
12 Cellular connectivity subject to network operator service
coverage and signal strength.
—
Backup Gateway 2 controls connection to the grid when paired with Powerwall 3, automatically detecting outages and providing
seamless transition to backup power. Backup Gateway 2 also provides energy metering for solar self-consumption, time-based
control, and backup operation.
In this system conguration,Powerwall 3 acts as the Site Controller,with the Backup Gateway 2 Site Controller disabled.
User Interface Tesla App
Operating Modes Support for solar self-
consumption, time-based
control, and backup
Backup Transition Automatic disconnect for
seamless backup
Modularity Supports up to 10 AC-
coupled Powerwalls
Optional Internal
Panelboard
200 A 6-space / 12 circuit
breakers
Siemens QP or Square D
HOM breakers rated 10 -
80A or Eaton BR breakers
rated 10 - 125A
Warranty 10 years
82024Powerwall 3 Datasheet
Powerwall 3 Example System Configurations
Powerwall 3 with Backup Switch
Whole Home Backup
Powerwall 3 with Gateway 3
Whole Home Backup
Powerwall 3 with Backup Gateway 2
Partial Home Backup
5313 W Henderson
Pl2/5/2025
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 7 of 8 GFT-OP-11a (22-August-2019)
Table 3B: Test List -2
Test Description
CSA
C22.2#107.1:2016
Ed. 4 CSA C22.3#9:2020 Ed 2
Screw Tightening Torque Test 3.6.3 --
Impedance Test 105.1/10.5.2 --
Continuity Test 4.1 --
Output Power Factor 4.2 --
Voltage Harmonics for stand alone 15.3.2.1 --
Frequency 10.5.4 --
Stand-alone inverter dc output short-circuits current contribution 10.5.5 --
Normal ramp rate -- 7.2.3.4.2 / 8.3.12.2.3
Flicker -- 7.2.2 / 8.3.13
Test for constant reactive power (var) mode 7.2.3.3.3 / 8.3.12.2.2
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 8 of 8 GFT-OP-11a (22-August-2019)
Appendix 4: Revision Summary
Date /
Project Engineer Comments
15-Feb-2023 Dipesh Patel Original issue date
8-Mar-2023 /
G104200718
Dipesh Patel Added UL 1699B, UL 1998 and UL 991 standards
24-Mar-2023/
G104200718
Dipesh Patel Added UL 1973 standard.
Added normal and abnormal category in ratings table.
18-Apr-2023 /
G104200718
Dipesh Patel Added additional factory settable nameplate ratings rated output active
power (W): 9600, 7680, 5750; Max. Continuous output power (W):
9600, 7680, 5750; Max. Cont. Output Current (A): 40, 32, 24; Apparent
Power rating (VA): 9600, 7680, 5750
Added Puerto Rico Interconnection regulation as it refers to UL 1741
and IEEE 1547-2018.
1-May-2024 /
G104514208
Mukund Rana
A) Added standards.
Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1]
Interconnection of Distributed Energy Resources and Electricity Supply
Systems [CSA C22.3#9:2020 Ed.2]
Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2]
Interconnection of Distributed Energy Resources and Electricity Supply
Systems [CSA C22.3#9:2020 Ed.2]
B) Update CSA C22.2#0.8 standard
C) added Table 3B: Test List -2
5313 W Henderson
Pl2/5/2025
Service Voltage
240
Section 220.82 Dwelling Unit
Part #1 - Section 220.82(B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
15.63 3750
Part #2 - Section 220.82(B)(3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500
1500
1500
1000
600
1000
1600
5760
3840
Amps Box B (VA)
76.25 18300
Total VA from Parts #1 and #2 combined:Box A + Box B =22050
Total VA 22050
First 10000 VA @ 100%10000 Remaining VA @ 40%
Remaining VA =12050 12050 x 40% =4820 VA
Adding First 10000 VA, if possible 10000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:14820 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:61.75 Amps
Part #3 - Section 220.82(C) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:0 VA
100% of all the Heating or A/C loads in Amps:0.00 A
VA Volts Amps
Parts #1 & #2 14820 240 61.75
Part #3 0 240 0.00
Total VA for all Parts:14,820
Totals Service/Feeder Load 61.75
Dedicated circuit Dedicated circuit
Article 220 - Dedicated Backup Panel Calculation Job Code
5313 W Henderson Pl
Santa Ana, CA 92704
109R-313VALA
Building Square Footage VA (watts)Amps
House 1250.00 3750 15.63
Total for Part #1:
Laundry
Appliance Circuit - 1
Appliance Circuit - 2
Dishwasher
Disposal
Refrigerator
Microwave
Dryer
OTHER
Totals for Part #2:
Totals from all Parts
5313 W Henderson
Pl2/5/2025
Section 220.82 Dwelling Unit
Part #1 - Section 220.82 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
15.63 3750
Part #2 - Section 220.82
Size in VA Size in VA
1500 N/A
3000 N/A
1000 N/A
600 N/A
1000 N/A
1600 N/A
5760 N/A
3840 N/A
N/A N/A
N/A Amps Box B (VA)
N/A 76.25 18300
Total VA from Parts #1 and #2 combined:Box A + Box B =22050
Total VA 22050
First 10,000 VA @ 100%10000 Remaining VA @ 40%
Remaining VA =12050 12050 x 40% =4820 VA
Adding First 10,000 VA 10000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:14820 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:61.75 Amps
Part #3 - Section 220.82 (C) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:0 VA
100% of all the Heating or A/C loads in Amps:0.00 A
VA Volts Amps
Parts #1 & #2 14820 240 61.75
Part #3 0 240 0.00
Total VA for all Parts:14,820
Totals Service/Feeder Load 61.75
#ESTAMP
Laundry
Appliance Circuit(s)
Dishwasher(s)
Disposal(s)
Dedicated circuit
House
Square Footage
1250
Article 220 - Service/Feeder calculation for (address):
5313 W Henderson Pl
Santa Ana, CA 92704
Building VA (watts)
3750
Amps
15.625
Job Code
109R-313VALA
Totals from all Parts
Dedicated circuit
Total for Part #1:
Refrigerator(s)
Microwave(s)
Totals for Part #2:
Dryer
OTHER
5313 W Henderson
Pl2/5/2025
Bus Rating:225
Main Rating:125
0%0%
Not Fed by other panels
Feeds: Panel 2 61.75
0.00
61.75
Bus Rating:225
Main Rating:125
100%100%
Itemized House and 240V Loads for Panel: (VA)
1500 1500
1500 1000
600 1000
1600 5760
3840
Fed by: Panel 1
61.75
61.75
Load Calc: (This Panel)
Appliance Circuit - 2 Dishwasher
Disposal Refrigerator
Microwave Dryer
OTHER
Panel 2 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Laundry Appliance Circuit - 1
Panel 1 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Load Calc: (This Panel)
Total Load Calc:
Total Load Calc:
5313 W Henderson
Pl2/5/2025
STRUCTURAL CERTIFICATION REPORT
Roof-mounted Solar Panels
October 16, 2024
To: Sunrun Re: Maria Valadez
1800 Ashton Blvd 5313 W Henderson Pl
Lehi, UT 84043 Santa Ana, CA 92704
AHJ: Santa Ana (City), CA
Sunrun proposes to install new roof-mounted solar panels at this residence and asked Right Angle Engineering to review
the existing structure for suitability. This letter summarizes the methods that were used to survey, evaluate, and certify
the existing roof framing and the attachment of the new solar panels to it.
STRUCTURAL DESIGN
Building Code:California Residential Code 2022
Design Standards:ASCE 7-16
Snow:Ground: pg= 0.0 psf | Flat Roof: pf= 0.0 psf | Sloped Roof: ps= 0.0 psf
Wind:Ultimate Wind Speed = 96.0 mph | Exposure = C
Seismic:Risk Category = 2 | Seismic Design Category = A | Site Class = D
STRUCTURE
Field Technicians from Sunrun visited the site and observed the existing structure :
Array Name Panel Quantity Roof Framing Material Pitch
Array 1 6 2x6 Rafter| 24" o.c.Rolled Shingle Roof 6°
Array 2 15 Pre-Manufactured Truss
(2x4) Truss| 24" o.c.Rolled Shingle Roof 18°
ANCHORAGE
The solar panel anchorage shall be installed according to the manufacturer's most current installation manual. The
attachment configuration should match the certified building plans. The solar panels should be mounted parallel (max 5
inches) to the roof surface.
Array Name Connection Type Fastener Max Anchorage Spacing
Array 1 OmniBase Tilt Mount
5/16” lag screw (2.5"
embedment) into roof
substructure
72"
Array 2 OmniBase Tilt Mount
5/16” lag screw (2.5"
embedment) into roof
substructure
72"
Installation Instructions
Solar panels and the equipment shall be installed per the manufacturer's installation specifications. Improper installation
will void this certification. If deviations from the approved structural plans occur, Right Angle Engineering must be
notified. Prior to installation, the installer should:
Confirm that the existing structure matches the information provided in the site survey, the approved installation
plans and this certification.
Identify discrepancies between this certification and the approved installation plans. If found, then this
certification shall govern.
Identify structural elements that are dangerous (cracked, broken, excessive sag, signs of overstress, rot, decay,
fire, water). If found, installation shall cease until those elements are adequately abated and made to comply with
the referenced building code.
Verify that both the existing structure and the solar addition has been permitted through the AHJ.
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 1 of 9
5313 W Henderson
Pl2/5/2025
STRUCTURAL CERTIFICATION
I certify the addition of solar panels on the roof of this structure does not cause the structure to become unsafe or make
it generally less compliant with the life-safety requirements of the referenced building code. Based on the evaluation
methods described below, for the loads that exist at this site, the existing framing will safely support the new solar
panels if they are installed and attached correctly. Electrical design is not included in this certification.
Array Name Certification Method Retrofits
Array 1 Stress analysis California Residential code 324.4.1 None required
Array 2 Stress analysis California Residential code 324.4.1 None required
Regards,
10/16/2024
Robert D. Smythe, P.E.
Right Angle Engineering
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 2 of 9
5313 W Henderson
Pl2/5/2025
Job Details
Roof Snow Load - ASCE 7-16
Ground Snow Load (pg)
Section 7.2 0.0 psf
Exposure Factor (Ce)
Table 7.3-1 0.9
Thermal Factor (Ct)
Table 7.3-2 1.1
Importance Factor (Is)
Table 1.5-2 1
Flat Roof Snow Load (pƒ)
Equation 7.3-1 0.0 psf
Non-Slippery Surface Slope Factor
(Cs) Figure 7.4-1 1
Slippery Surface Slope Factor (Cs)
Figure 7.4-1 1
Roof Snow Load
Equation 7.4-1 0.0 psf
Reduced Snow Load (Slippery
Surface)
Equation 7.4-1
0.0 psf
Design Criteria
Wind Speed (Vult)
Local Design Criteria 96.0mph
Exposure Category C
Risk Category 2
Mean Roof Height 20 ft
Roof Type Gable Roof
Building Type Enclosed
Roof Live Load
Existing Roof Live Load
ASCE 7-16 Table 4.3-1 20 psf
1Roof Dead Load
Rolled Shingle Roof 1.5 psf No Drywall 0.0 psf
5/8" Plywood Sheathing 2.0 psf Solar Panel Array 2.74 psf
Roof Framing 1.57 psf Dead Load Without Panels 6.27 psf
Insulation 1.2 psf
1Roof Dead Load is taken from the worst case scenario dead load from all arrays of the job in order to provide a more
conservative evaluation.
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 3 of 9
5313 W Henderson
Pl2/5/2025
Array 1
Array Details
Roof Framing 2x6 Rafter DF No.2
Spacing 24.0"
Beam Span 6.0'
Roof Pitch 6°
Solar Rails UR-40
Panel Quantity 6
Panel Array Area 129.81 ft²
Panel Orientation Portrait
Lag Screw Embedment 2.5"
Roof Attachment Type OmniBase Tilt Mount
5/16” lag screw
Shear Capacity
NDS 190.0 lbs
Pullout Capacity
NDS 665.0 lbs
Velocity Pressure
Equation 26.10-1 (Kz=0.9, Kht=1,
Kd=0.85, Ke=1.0)
15.61 psf
GCP Zones 1'/1 2 3
GCp
Figure 30.3-(2A-5B)-1.56 -2.12 -2.84
Design Pressure Up [psf]
Equation 29.4-7 ga=0.53 gE=1.0,-16 -17.7 -23.7
Factored Design Pressure
Up [psf]
ASD LC (.6D + .6W)
-8.0 -9.0 -12.6
Exposed Design Pressure
Up [psf]
ga=0.53 gE=1.5,
-19.5 -26.5 -35.5
Design Pressure Down
[psf]16 16 16
Tributary Area [ft2]83.5 74.3 52.9
Maximum Connection
Spacing [in]320 285 203
Maximum Rail Span [in]80 80 78
Maximum Rail Cantilever
[in]24 24 24
Design Connection
Spacing [in]
*Adjusted
72 72 72
Design Connection
Spacing (exposed) [in]72 72 72
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 4 of 9
5313 W Henderson
Pl2/5/2025
Design Ratio
Member ID Axial Momentz Sheary Combined Slenderness Deflection Status
1 0.0 0.047 0.052 0.042 0.044 0.009 Pass
2 0.001 0.047 0.046 0.047 0.044 0.029 Pass
Member Design Capacity (LRFD)
Member ID FI
b(ksi)FI
t(ksi)FI
v(ksi)FI
c(ksi)FI
cp(ksi)EI(ksi)Emin
I(ksi)
1 2.324 1.292 0.311 2.566 0.939 1600.0 1041.216
2 2.324 1.292 0.311 2.566 0.939 1600.0 1041.216
Node Coordinates
ID X Coordinate Y Coordinate
1 0.000 0.000
2 6.000 0.631
3 -1.500 -0.158
Members
ID Node A Node B Section Node A Fixity Node B Fixity Length
1 1 2 1 FFFFFF FFFFFF 6.033
2 3 1 1 FFFFFF FFFFFF 1.508
Supports
ID Node ID Restraint Code
1 2 RFFRRR
2 1 FFFFFR
Materials
ID Name Young's Modulus Density Poisson's Ratio
1 NDS - Table 4A - DOUGLAS FIR-LARCH - No.2- 2in & wider 1600.000 33.308 0.400
Sections
ID Name Depth Width Shear Area Z Shear Area Y Torsion Radius
1 1.5 x 5.5 6.000 1.500 7.502 7.500 1.495
ID Centroid Y Centroid Z Area Y-Axis Mol Z-Axis Mol Torsion Constant
1 0.750 3.000 9.000 1.688 27.000 5.687
Point Loads
ID Load Group Member Position %Y Magnitude
1 Solar-Snow 1 8.333%0.000
2 Solar 1 8.333%-0.032
Member Distributed Loads
ID Load Group Start Position End Position Member Y Magnitude
1 Dead Load 0.000%100.000%2 -0.013
2 Dead Load 0.000%100.000%1 -0.013
3 Roof Live Load 0.000%66.667%2 -0.040
4 Roof Live Load 95.371%100.000%1 -0.040
5 Snow Load 0.000%66.667%2 0.000
6 Snow Load 95.371%100.000%1 0.000
Load Combinations
ID Name Dead Load Factor Snow Load Factor Solar Factor Solar-Snow Factor
Roof Live Load
Factor
1 1. 1.4D 1.4 0 1.4 0 0
2 3. 1.2D + 1.6Lr 1.2 0 1.2 0 1.6
3 3. 1.2D + 1.6S 1.2 1.6 1.2 1.6 0
4 4. service loads A 0 1 0 1 0
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 5 of 9
5313 W Henderson
Pl2/5/2025
5 5. service loads B 0 0 0 0 1
Internal Member Forces and Moments
Member Axial Force (Min/Max)
Shear Force Y
(Min/Max)
Shear Force Z
(Min/Max)
Torsion (Min/Max)
Bending Moment Y
(Min/Max)
Bending Moment Z
(Min/Max)
1 -0.006 / 0.010 -0.053 / 0.097 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.081 / 0.042
2 -0.009 / 0.000 -0.087 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.081 / 0.000
Member Displacement Span Check
Member Length Max Relative Displacement Span Method 1
1 6.033 0.004 L/20133
2 1.508 0.006 L/3137
Member Stresses
Member
Axial Stress
(Min/Max)
Torsion Stress
(Min/Max)
Shear Stress Y
(Min/Max)
Shear Stress Z
(Min/Max)
Top Bending Moment
Z (Min/Max)
Bottom Bending
Moment Z (Min/Max)
1 -0.001 / 0.001 0.000 / 0.000 -0.009 / 0.016 -0.000 / -0.000 -0.108 / 0.056 -0.056 / 0.108
2 -0.001 / 0.000 0.000 / 0.000 -0.014 / 0.000 0.000 / 0.000 -0.108 / 0.000 0.000 / 0.108
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 6 of 9
5313 W Henderson
Pl2/5/2025
Array 2
Array Details
Roof Framing
Pre-Manufactured
Truss (2x4) Non
Standard DF No.2
Spacing 24.0"
Beam Span 12.5'
Roof Pitch 18°
Solar Rails UR-40
Panel Quantity 15
Panel Array Area 324.53 ft²
Panel Orientation Portrait
Lag Screw Embedment 2.5"
Roof Attachment Type OmniBase Tilt Mount
5/16” lag screw
Shear Capacity
NDS 190.0 lbs
Pullout Capacity
NDS 665.0 lbs
Velocity Pressure
Equation 26.10-1 (Kz=0.9, Kht=1,
Kd=0.85, Ke=1.0)
15.61 psf
GCP Zones 1/2e 2n/2r
/3e 3r
GCp
Figure 30.3-(2A-5B)-1.93 -2.52 -3.0
Design Pressure Up [psf]
Equation 29.4-7 ga=0.53 gE=1.0,-16.0 -21.0 -24.9
Factored Design Pressure
Up [psf]
ASD LC (.6D + .6W)
-8.1 -11.0 -13.4
Exposed Design Pressure
Up [psf]
ga=0.53 gE=1.5,
-24.0 -31.4 -37.4
Design Pressure Down
[psf]16 16 16
Tributary Area [ft2]82.6 60.4 49.7
Maximum Connection
Spacing [in]317 232 191
Maximum Rail Span [in]80 80 77
Maximum Rail Cantilever
[in]24 24 24
Design Connection
Spacing [in]
*Adjusted
72 72 72
Design Connection
Spacing (exposed) [in]72 72 72
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 7 of 9
5313 W Henderson
Pl2/5/2025
Design Ratio
Member ID Axial Momentz Sheary Combined Slenderness Deflection Status
1 0.004 0.569 0.14 0.568 0.035 0.04 Pass
2 0.003 0.084 0.066 0.087 0.035 0.142 Pass
Member Design Capacity (LRFD)
Member ID FI
b(ksi)FI
t(ksi)FI
v(ksi)FI
c(ksi)FI
cp(ksi)EI(ksi)Emin
I(ksi)
1 2.681 1.49 0.311 2.683 0.939 1600.0 1041.216
2 2.681 1.49 0.311 2.683 0.939 1600.0 1041.216
Node Coordinates
ID X Coordinate Y Coordinate
1 0.000 0.000
2 12.500 4.061
3 -1.500 -0.487
Members
ID Node A Node B Section Node A Fixity Node B Fixity Length
1 1 2 1 FFFFFF FFFFFF 13.143
2 3 1 1 FFFFFF FFFFFF 1.577
Supports
ID Node ID Restraint Code
1 2 RFFRRR
2 1 FFFFFR
Materials
ID Name Young's Modulus Density Poisson's Ratio
1 NDS - Table 4A - DOUGLAS FIR-LARCH - No.2- 2in & wider 1600.000 33.308 0.400
Sections
ID Name Depth Width Shear Area Z Shear Area Y Torsion Radius
1 1.5 x 3.5 4.000 1.500 5.000 5.000 1.463
ID Centroid Y Centroid Z Area Y-Axis Mol Z-Axis Mol Torsion Constant
1 0.750 2.000 6.000 1.125 8.000 3.437
Point Loads
ID Load Group Member Position %Y Magnitude
1 Solar-Snow 1 5.333%0.000
2 Solar 1 5.333%-0.033
3 Solar-Snow 1 52.936%0.000
4 Solar 1 52.936%-0.033
Member Distributed Loads
ID Load Group Start Position End Position Member Y Magnitude
1 Dead Load 0.000%100.000%2 -0.013
2 Dead Load 0.000%100.000%1 -0.013
3 Roof Live Load 0.000%77.778%2 -0.032
4 Roof Live Load 92.539%100.000%1 -0.032
5 Snow Load 0.000%77.778%2 0.000
6 Snow Load 92.539%100.000%1 0.000
Load Combinations
ID Name Dead Load Factor Snow Load Factor Solar Factor Solar-Snow Factor
Roof Live Load
Factor
1 1. 1.4D 1.4 0 1.4 0 0
2 3. 1.2D + 1.6Lr 1.2 0 1.2 0 1.6
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 8 of 9
5313 W Henderson
Pl2/5/2025
3 3. 1.2D + 1.6S 1.2 1.6 1.2 1.6 0
4 4. service loads A 0 1 0 1 0
5 5. service loads B 0 0 0 0 1
Internal Member Forces and Moments
Member Axial Force (Min/Max)
Shear Force Y
(Min/Max)
Shear Force Z
(Min/Max)
Torsion (Min/Max)
Bending Moment Y
(Min/Max)
Bending Moment Z
(Min/Max)
1 -0.043 / 0.056 -0.134 / 0.174 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.021 / 0.508
2 -0.027 / 0.000 -0.082 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.075 / 0.000
Member Displacement Span Check
Member Length Max Relative Displacement Span Method 1
1 13.143 0.035 L/4506
2 1.577 0.030 L/633
Member Stresses
Member
Axial Stress
(Min/Max)
Torsion Stress
(Min/Max)
Shear Stress Y
(Min/Max)
Shear Stress Z
(Min/Max)
Top Bending Moment
Z (Min/Max)
Bottom Bending
Moment Z (Min/Max)
1 -0.007 / 0.009 0.000 / 0.000 -0.034 / 0.044 -0.000 / -0.000 -0.062 / 1.525 -1.525 / 0.062
2 -0.004 / 0.000 0.000 / 0.000 -0.021 / 0.000 -0.000 / -0.000 -0.226 / 0.000 0.000 / 0.226
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 9 of 9
5313 W Henderson
Pl2/5/2025
City of Santa Ana,
SIGNATURE:___________________ DATE:__________
717 17th Street, Ste. 200 | Denver, CO 80202
I, Maria Valdez , grant authorization to SUNRUN SOLAR to install Rooftop Mounted Solar
on my residence located at 5313 w henderson pl , SANTA ANA, CA, 92704.
Docusign Envelope ID: 8D9C8E98-4991-4B64-8953-FA7B4C1C80F2
11/4/2024
5313 W Henderson
Pl2/5/2025
Certificate Of Completion
Envelope Id: 8D9C8E9849914B648953FA7B4C1C80F2 Status: Completed
Subject: Complete with Docusign: 109R-313VALA.unsignedauthorizationdoc.pdf
Source Envelope:
Document Pages: 1 Signatures: 1 Envelope Originator:
Certificate Pages: 5 Initials: 0 Stephanie Phillips
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
225 Bush Street, Suite 1400
San Francisco, CA 94104
stephanie.phillips@sunrun.com
IP Address: 12.133.93.10
Record Tracking
Status: Original
11/4/2024 1:03:11 PM
Holder: Stephanie Phillips
stephanie.phillips@sunrun.com
Location: DocuSign
Signer Events Signature Timestamp
Maria Valadez
juanitapham2@gmail.com
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 71.136.238.250
Signed using mobile
Sent: 11/4/2024 1:04:34 PM
Viewed: 11/4/2024 6:48:59 PM
Signed: 11/4/2024 6:49:04 PM
Electronic Record and Signature Disclosure:
Accepted: 11/4/2024 6:48:59 PM
ID: 5ac9e216-7206-435a-80aa-52ee366fcead
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 11/4/2024 1:04:34 PM
Certified Delivered Security Checked 11/4/2024 6:48:59 PM
Signing Complete Security Checked 11/4/2024 6:49:04 PM
Completed Security Checked 11/4/2024 6:49:04 PM
Payment Events Status Timestamps
Electronic Record and Signature Disclosure
5313 W Henderson
Pl2/5/2025
CONSUMER DISCLOSURE
From time to time, Sunrun Inc. (we, us or Company) may be required by law to provide to you
certain written notices or disclosures. Described below are the terms and conditions for providing
to you such notices and disclosures electronically through the DocuSign, Inc. (DocuSign)
electronic signing system. PLEASE READ THE INFORMATION BELOW CAREFULLY
AND THOROUGHLY, AND IF YOU CAN ACCESS THIS INFORMATION
ELECTRONICALLY TO YOUR SATISFACTION AND AGREE TO THESE TERMS AND
CONDITIONS, PLEASE CONFIRM YOUR AGREEMENT BY CLICKING THE 'I AGREE'
BUTTON AT THE BOTTOM OF THIS DOCUMENT.
Getting paper copies
At any time, you may request from us a paper copy of any record provided or made available
electronically to you by us. You will have the ability to download and print documents we send
to you through the DocuSign system during and immediately after signing session and, if you
elect to create a DocuSign signer account, you may access them for thirty (30) days after such
documents are first sent to you. After such time, if you wish for us to send you paper copies of
any such documents from our office to you, please request delivery of such paper copies from us
by following the procedure described below.
Withdrawing your consent
If you decide to receive notices and disclosures from us electronically, you may at any time
change your mind and tell us that thereafter you want to receive required notices and disclosures
only in paper format. How you must inform us of your decision to receive future notices and
disclosure in paper format and withdraw your consent to receive notices and disclosures
electronically is described below.
Consequences of changing your mind
If you elect to receive required notices and disclosures only in paper format, it will slow the
speed at which we can complete certain steps in transactions with you and delivering services to
you because we will need first to send the required notices or disclosures to you in paper format,
and then wait until we receive back from you your acknowledgment of your receipt of such
paper notices or disclosures. To indicate to us that you are changing your mind, you must
withdraw your consent using the DocuSign ‘Withdraw Consent’ form on the signing page of a
DocuSign envelope instead of signing it. This will indicate to us that you have withdrawn your
consent to receive required notices and disclosures electronically from us and you will no longer
be able to use the DocuSign system to receive required notices and consents electronically from
us or to sign electronically documents from us.
All notices and disclosures will be sent to you electronically
Unless you tell us otherwise in accordance with the procedures described herein, we will provide
electronically to you through the DocuSign system all required notices, disclosures,
authorizations, acknowledgements, and other documents that are required to be provided or made
available to you during the course of our relationship with you. To reduce the chance of you
inadvertently not receiving any notice or disclosure, we prefer to provide all of the required
notices and disclosures to you by the same method and to the same address that you have given
us. Thus, you can receive all the disclosures and notices electronically or in paper format through
the paper mail delivery system. If you do not agree with this process, please let us know as
described below. Please also see the paragraph immediately above that describes the
consequences of your electing not to receive delivery of the notices and disclosures
electronically from us.
Electronic Record and Signature Disclosure created on: 8/7/2013 10:17:58 AM
Parties agreed to: Maria Valadez 5313 W Henderson
Pl2/5/2025
How to contact Sunrun Inc.:
You may contact us to let us know of your changes as to how we may contact you electronically,
to request paper copies of certain information from us, and to withdraw your prior consent to
receive notices and disclosures electronically as follows:
To contact us by email send messages to: customercare@sunrun.com
You may also contact us in writing at 45 Fremont Street, 32nd Floor, San Francisco, CA 94105
or by phone at 1-855-478-6786.
To advise Sunrun Inc. of your new e-mail address
To let us know of a change in your e-mail address where we should send notices and disclosures
electronically to you, you must send an email message to us at customercare@sunrun.com and in
the body of such request you must state: your previous e-mail address, your new e-mail
address. We do not require any other information from you to change your email address.
In addition, you must notify DocuSign, Inc. at 1-866-219-4318 to arrange for your new email
address to be reflected in your DocuSign account by following the process for changing e-mail in
the DocuSign system.
To request paper copies from Sunrun Inc.
To request delivery from us of paper copies of the notices and disclosures previously provided
by us to you electronically, you must contact us by (a) sending us an e-mail to
customercare@sunrun.com, (b) writing to us at Sunrun Inc, 45 Fremont Street, 32nd Floor, San
Francisco, CA 94105, or (c) calling us at 1-855-478-6786, and in connection with your request
you must state your e-mail address, full name, US Postal address, and telephone number.
To withdraw your consent with Sunrun Inc.
To inform us that you no longer want to receive future notices and disclosures in electronic
format you may:
i. decline to sign a document from within your DocuSign session, and on the subsequent
page, select the check-box indicating you wish to withdraw your consent, or you may;
ii. contact us by (a) sending us an email to customercare@sunrun.com, (b) writing to us
at Sunrun Inc., 45 Fremont Street, 32nd Floor, San Francisco, CA 94105, or (c) calling us
at 1-855-478-6786, and in connection with your request you must state your e-mail, full
name, US Postal Address, and telephone number. We do not need any other information
from you to withdraw consent.. The consequences of your withdrawing consent for
online documents will be that transactions may take a longer time to process..
Required hardware and software
Operating
Systems: Windows® 2000, Windows® XP, Windows Vista®; Mac OS® X
5313 W Henderson
Pl2/5/2025
Browsers:
Final release versions of Internet Explorer® 6.0 or above (Windows only);
Mozilla Firefox 2.0 or above (Windows and Mac); Safari™ 3.0 or above
(Mac only)
PDF Reader: Acrobat® or similar software may be required to view and print PDF files
Screen
Resolution: 800 x 600 minimum
Enabled Security
Settings: Allow per session cookies
** These minimum requirements are subject to change. If these requirements change, you will be
asked to re-accept the disclosure. Pre-release (e.g. beta) versions of operating systems and
browsers are not supported.
Notices
Any notice or other communication to be made hereunder, even if otherwise required to be in
writing under other provisions of this Consent or any other documents or agreements that have
been provided to you in connection with this Consent, may alternatively be made in an electronic
record transmitted electronically to the electronic addresses provided by you. Any notice or other
communication made in electronic form will have the same legal effect and enforceability as if
made in non-electronic form.
Acknowledging your access and consent to receive materials electronically
To confirm to us that you can access this information electronically, which will be similar to
other electronic notices and disclosures that we will provide to you, please verify that you were
able to read this electronic disclosure and that you also were able to print on paper or
electronically save this page for your future reference and access or that you were able to e-mail
this disclosure and consent to an address where you will be able to print on paper or save it for
your future reference and access. Further, if you consent to receiving notices and disclosures
exclusively in electronic format on the terms and conditions described above, please let us know
by clicking the ‘I agree’ button below.
By checking the ‘I agree’ box, I confirm that:
I can access and read and have accessed, read and understood the terms of this
ELECTRONIC CONSENT TO ELECTRONIC RECEIPT OF ELECTRONIC
CONSUMER DISCLOSURES document; and
I can print on paper the disclosure or save or send the disclosure to a place where I can
print it, for future reference and access; and
Until or unless I notify Sunrun Inc. as described above, I consent to receive from
exclusively through electronic means all notices, disclosures, authorizations,
acknowledgements, and other documents that are required to be provided or made
available to me by Sunrun Inc. during the course of my relationship with you.
Entire Agreement Provision
This agreement and the consumer disclosure statement executed by the customer in conjunction
with and simultaneously with its review and acceptance of the terms set forth herein constitute
5313 W Henderson
Pl2/5/2025
the entire agreement between the parties with respect to the subject matter hereof and supersede
any prior understandings, agreements, or representations by or between the parties, written or
oral, to the extent they relate in any way to the subject matter hereof.
5313 W Henderson
Pl2/5/2025
5313 W Henderson
Pl2/5/2025
Rev: 8/29/19
SOL-01 CBC 2016
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
caitlyn hernandez
3854005019
oc_permits@sunrun.com
11.20.24
5313 W Henderson
Pl2/5/2025
PAGE
REV: C2 3/11/2025
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
GILBERT CORREIA, C10, C46
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N) NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
SURGE PROTECTOR TO BE INSTALLED PER MANUFACTURER
AND PANEL BOARD SPECS.
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-3.0 LAYOUT
PV-3.1 MOUNTING DETAIL
PV-3.2 MOUNTING DETAIL
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL CALCS
PV-4.2 PANEL SCHEDULE
PV-5.0 SIGNAGE
PV-5.1 SIGNAGE
LTD: LR5-54HABB-400M
WITH STANDOFF TO FRAMING: SNR-DC-01249 [FLAT, FLUSH
MOUNT ( ROLLED COMP/ MEMBRANE/ FOAM) 1 LAG
OMNIBASE]; ULTRA RAIL, ATTACHMENT DETAIL, UMBRELLA L
FOOT TO FRAMING, SNR-DC-00339
1707000-XX-Y, (1) EXPANSION 1807000-XX-Y
(MCI) ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE
PANEL WITH 50 AMP MAIN BREAKER TO BE REPLACED WITH
NEW 125 AMP MAIN PANEL WITH 125 AMP MAIN BREAKER
AND 225 AMP BUSBAR.
MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A).
MODULES, ARE CLASS A FIRE RATED.
CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30
SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE
ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
D
WARNING: POWER SOURCE OUTPUT CONNECTION -- DO NOT
RELOCATE THIS OVERCURRENT DEVICE.
Revision to 20184540 (issued on 2/4/25)
Rev 1 #20185409
APPROVALS:
ELECT - M. Smith
5313 W Henderson
Pl3/27/2025
PAGE
REV: C2 3/11/2025
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
GILBERT CORREIA, C10, C46
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
PL
PL
PL
PL PL
PL
PL
PL
PLPL
SITE PLAN
PV-2.0
#SSTAMPSP
#ESTAMPSP
NOTES:
RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
TOTAL ROOF SURFACE AREA: 2538 SQFT.
TOTAL PV ARRAY AREA: 441.4 SQ FT.
PERCENTAGE PV COVERAGE:
(TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
AREA) * 100 = 17.4%
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN
ACCORDANCE WITH R328.4. ESS UNITS SHALL BE SEPARATED FROM
EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT WHERE SMALLER
SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE
BASED ON LARGE/SCALE FIRE TESTING.
POWERWALL ENERGY
STORAGE SYSTEM (ESS)
BG BACKUP GATEWAY
GP GENERATION PANEL
ELECTRIC VEHICLE
SUPPLY EQUPMENTEV
MAIN PANEL
INVERTER(S)
AC DISCONNECT(S)
DC DISCONNECT(S)
SUNRUN METER
DEDICATED PV METER
SERVICE ENTRANCE
INTERIOR EQUIPMENT
SHOWN AS DASHED
SE
MP
SM
PM
INV
AC
DC
SUB-PANELSP
CB IQ COMBINER BOX
METER ADAPTERMA
GROUNDING
ELECTRODE
ENERGY STORAGE
SYSTEM
BP BACKUP LOADS PANEL
BI BACKUP INTERFACE 1 COMMUNICATION
WIRESAM
MD MICROGRID
INTERCONNECT DEVICE
ACREL METER
SOLAREDGE METERSEMPV LOAD CENTERLC
LEGEND
SCALE: NTS
NOTE: NOT ALL ITEMS IN LEGEND
WILL APPEAR IN SITE PLAN
RAIL
STANDOFFS &
FOOTINGS
SOLAR
MODULES
SITE PLAN - SCALE = 0'-0 3/64" = 1'-0"
(E) RESIDENCE
(N) ARRAY AR-01
(N) ARRAY AR-02
FIRE SETBACKS
(18" TYP)
ROOF PATHWAYS
(3' TYP)
SE
MP
INV
W HENDERSON PL
MD
ROOF PATHWAYS
(3' TYP)
AC
(E) FENCE
(E) GATE (TYP.)
EXTERNAL RAPID
SHUTDOWN SWITCH
RSD
A A A A A A A A
B B B B B B B
C C C C C C
(E) DETACHED
STRUCTURE
(E) PATIO
ARRAY
PITCH
PV AREA
(SQFT)
AR-01 6° 126.1
AR-02 18° 315.3179°
TRUE
AZIM
MAG
AZIM
167°179°
167°
NOTE: ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE
INSTALLED MODULE PER NEC 690.12
RSD D
I V IL
REGISTERED PROFESSIONAL ENGINEER
STATE OF C ALIFORNIA
ROBERT SMYTHEC56136
EXP. 12/31/26
5313 W Henderson
Pl3/27/2025
PAGE
REV: C2 3/11/2025
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
GILBERT CORREIA, C10, C46
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
NEW125A
MAIN BREAKER
END FED
NEW 125A
MAIN PANEL
225A BUS
J-BOX
LONGI GREEN
ENERGY TECHNOLOGY CO LTD
LR5-54HABB-400M
STRING 1 OF 7 MODULES
3 MODULE LEVEL
RAPID SHUTDOWN DEVICES
LONGI GREEN
ENERGY TECHNOLOGY CO LTD
LR5-54HABB-400M
STRING 2 OF 8 MODULES
3 MODULE LEVEL
RAPID SHUTDOWN DEVICES
1
1
2
POINT OF INTERCONNECTION:705.12(B)(3)(2),
METER NUMBER: 222013-570957
REPLACE EXISTING 50 MAIN
PANEL WITH NEW 125A MAIN PANEL 125A MAIN BREAKER
AND 225A BUS BAR
EQUIPMENT CHARACTERISTICS
INCLUDED IN SPEC SHEETS
NOTE: TOTAL PV BACKFEED
= 60A USED FOR INTERCONNECTION CALCULATIONS
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT
3
FACILITY
GROUND
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A , 2P
120/240VAC
3
1
LONGI GREEN
ENERGY TECHNOLOGY CO LTD:
LR5-54HABB-400M
STRING 1 OF 6 MODULES
2 MODULE LEVEL
RAPID SHUTDOWN DEVICES
(N) IMO PE69-3020,
DISCONNECT
SWITCH, 3P, 16A
UL 9540
FACTORY
WIRING
ASSEMBLY
(1 ) TESLA
POWERWALL 3
EXPANSION PACK
1807000-XX-Y
60A
M
TESLA
BACKUP
SWITCH
CONDUIT SCHEDULE
TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT
1 Inverter Input (2) 10 AWG (PV WIRE)N/A 6 AWG (BARE)Open Air
2 Inverter Input (6) 10 AWG
THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4" EMT
3 Inverter Output (2) 6 AWG
THHN/THWN-2
(1) 6 AWG
THHN/THWN-2 8 AWG THHN/THWN-2 3/4" EMT
PV-4.0
ELECTRICAL
#ESTAMP
MODULE CHARACTERISTICS
LONGI GREEN ENERGY
TECHNOLOGY CO LTD:
LR5-54HABB-400M
400 W
OPEN CIRCUIT VOLTAGE 37.05 V
MAX POWER VOLTAGE 30.94 V
SHORT CIRCUIT CURRENT 13.72 A
GENERAL NOTES:
GROUND - UFER, TWO GROUNDS RODS OR
COLD WATER GAS BOND
IF THE RELOCATED LOADS EXTEND MORE
THAN 6 FEET, AFCI PROTECTION APPLIES
PER 2019 CEC 210.12
ANY MULTIWIRE BRANCH CIRCUITS
RELOCATED ARE TO BE IDENTIFIED,
GROUPED, AND EQUIPPED WITH A
2-POLE OCPD BREAKER PER CEC
210.4(B,D).
D
D
5313 W Henderson
Pl3/27/2025
BACKUP LOADS
LOAD BREAKER RATING
(AMPS)LABEL DEMAND
LOAD
1 20A-1P KITCHEN 1500 VA
2 20A-1P KITCHEN 1500 VA
3 20A-2P OTHER 3840 VA
5 15A-1P ROOMS 1500 VA
6 15A-1P ROOMS 1500 VA
7 30A-2P DRYER 5760 VA
PV-4.1
ELECTRICAL CALCS
ELECTRICAL CALCS
SYSTEM INFORMATION
8.4 KW DC PHOTOVOLTAIC SYSTEM
(21) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
ALLOWABLE BACKFEED
ALLOWABLE BACKFEED = (MAIN PANEL RATING) X 1.2 - (MAIN BREAKER RATING) =
225A X 1.2 - 125A = 145A
60A ≤ 145A → INTERCONNECTION MEETS 705.12(B)(3)(2) REQUIREMENTS.
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS LOAD)[690.8(B)(1)]=
13.72 A X 1.25 X 1.25= 21.44A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 0.8 X 40A = 29.12A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
29.12A < 35A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
21.44A < 29.12A 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG,75°C RATED = 65A
65A < 68.25A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] + VOC} X
(# MODULES / STRING) =
{[(-0.26 %/°C X 37.05 V) / 100] X [-2 °C - 25 °C] + 37.05 V} X 8 = 317 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 13.72 A X 3 = 51.45A
PAGE
REV: C2 3/11/2025
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
D
5313 W Henderson
Pl3/27/2025
LIGHTS /RECEPTABLES
ROOMS
LIGHTS /RECEPTABLES
PANEL SCHEDULE
PANEL SCHEDULE
PV-4.2
KITCHEN
PAGE
REV: C2 3/11/2025
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
MAIN BREAKER
125
NEW 225/125A
MAIN PANEL
60
PV + ESS
BREAKER
30
15
15
20
20
DRYER
20 OTHER
D
5313 W Henderson
Pl3/27/2025
PAGE
REV: C2 3/11/2025
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
GILBERT CORREIA, C10, C46
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
SIGNAGE
PV-5.0
#ESTAMP
ENERGY STORAGE SYSTEM
DISCONNECT
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
POWER SOURCE OUTPUT CONNECTION
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
CEC 2022: 705.12(B)(3)(2)
NOTES AND SPECIFICATIONS:
SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE CEC 2022
ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY
SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.
SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING
EFFECTIVE WORDS, COLORS AND SYMBOLS.
LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR
WIRING METHOD AND SHALL NOT BE HAND WRITTEN.
LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED.
SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT
SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
DO NOT COVER EXISTING MANUFACTURER LABELS.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
4"
3"
ELECTRICAL SHOCK HAZARD
WARNING
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S),
AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC
2022: 690.13(B)
!
INVERTER 1
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:
690.31(D)(2)CAUTION
5313 W HENDERSON PL, SANTA ANA, CA, 92704
SOLAR PANELS ON ROOF
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
MULTIPLE SOURCES OF POWER
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC
2022: 705.12(C)
ENERGY STORAGE SYSTEM
PREMISES WIRING MAY REMAIN
ENERGIZED AFTER LOSS OF
UTILITY POWER
CAUTION!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C)
AC DISCONNECT
INVERTER & ENERGY STORAGE
(EXT)
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
MAXIMUM SYSTEM VOLTAGE:
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
EXPANSION ENERGY
STORAGE (EXT)
SERVICE ENTRANCE WITH TESLA
BACKUP SWITCH
RAPID SHUTDOWN SWITCH
D
5313 W Henderson
Pl3/27/2025