HomeMy WebLinkAbout2307 N Towner St - Plan0
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
COVER PAGE
1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE
COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY
2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED
3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED
4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER.
5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED.
6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY
AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL
INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY.
7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE
COORDINATED WITH OTHER TRADES.
8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS
RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT.
9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE
WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE.
10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS.
OWNER
SCOPE
PROJECT
ADDRESS
PROJECT DATA GENERAL NOTES VICINITY MAP
SHEET INDEX
PHOTOVOLTAIC NOTES
SATELLITE VIEW
BUILDING
INFORMATION:
ELECTRICAL
INFORMATION
MAIN SERVICE PANEL
BUSBAR RATING
MAIN SERVICE
BREAKER RATING
1ɸ, 3W, 120/240V
RACKING
INFORMATION
Main Service Panel
Solar Module
Micro Inverter /
Optimizer
EMT / FMT / PVC
/ RMC type conduit/
Romex NM Cable/
FNMT (Fluid non-metalic tube)
36'' SetbackInverter
Utility Meter
Production Meter
PV Load Center
IQ Combiner Box
Junction Box
Sunpower PV Supervisor
18'' Setback
EV Outlet
CONSTRUCTION TYPE: V-B
ROOF
TYPE
AHJ
APN
LOT AREA
LIVING AREA
MSP
UM
PM
INV
PV
PVS6
IQ
J/B
EV
DAVID VANDERVOORT
18
18 ENPHASE IQ8PLUS-72-2-US
2307 N TOWNER ST,
SANTA ANA, CA 92706
AC DisconnectACD
SSP Service Sub Panel
M CONCRETE TILE
2,741 SQFT
00121406
CITY OF SANTA ANA
ROOF MOUNT INSTALLATION OF
DC PHOTOVOLTAIC SYSTEM
7.20 KW DC
7.20 KW
6.49 KW AC
NEW UPGRADED
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703.
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER
OUTAGE.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE
ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED.
8 .INVERTER IS EQUIPPED W/ INTEGRATED GFCI, THUS PROVIDING GROUND FAULT PROTECTION
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT.
11. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING
MEANS AS PER 230.82(6)
12. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING
AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER SEC 250.122
13. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122.
14. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS
ALL OTHER ORDINANCE ADOPTED BY THE
LOCAL GOVERNING AGENCIES
THE INSTALLATION OF SOLAR ARRAYS AND
PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY
WITH THE FOLLOWING CODES:
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA RESIDENTIAL CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
2022 CALIFORNIA HISTORICAL CODE
2022 CALIFORNIA EXISTING BUILDING CODE
2022 CALIFORNIA REFERENCED STANDARDS CODE
2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE
10,496 SQFT
Battery BackupBB
Auto TransformerAT
Solar Edge Meter EnclosureSEM
Distribution PanelDP
Rapid Shutdown Controller RSC
Rapid Shutdown Box RSB
Itron MeterIM
UNIT INDEX
CODE REFERENCES
ECOFASTEN CLICKFIT
2"X4" @ 24" O.CFRAMING
OCCUPANCY: R
ONE STORY BUILDING
175A
225A
HANWHA 400W
Q.PEAK DUO BLK ML-G10+ 400
(don't delete this note)
0 COVER PAGE
SINGLE LINE DIAGRAM
CODE REQUIRED SIGNAGE
3
4
ATTACHMENT LAYOUT5
INVERTER DATA SHEET
D1 MODULE DATA SHEET
RACKING DATA SHEET
ROOF PLAN
WIRE SIZE CALCULATIONS
D2
D3
D4
D5
GROUNDING SPECS
IQ COMBINER BOX DATA SHEET
1
2
1.1 SITE PLAN
D6
SURVEY PHOTO
D7
1 TESLA POWERWALL 2 AC BATTERY
WITH TESLA BACKUP GATEWAY
D8
BATTERY DATA SHEET
ATTACHMENT DATA SHEET
ATTACHMENT DATA SHEETD5.1
IRONRIDGE ROOF MOUNT
GROUNDING SPECS
D4.1 RACKING DATA SHEET
D6.1
D9
3.1 PANEL SCHEDULES
3.2 GENERATION PANEL LOAD CALCULATIONS
NEW PV SYSTEM SIZE
EXISTING PV SYSTEM SIZE
TOTAL PV SYSTEM SIZE
7.20 KW AC
10.26 KW AC
17.46 KW AC
Signed 08/09/2023
The scope of the plans is for the installation of the solar photovoltaic
system only and the approval is subject to compliance with all
applicable city and state codes and regulations regarding construction.
The approval of the plans does not constitute any certification of the
accuracy, completeness, or building permit status of the existing
buildings and structures as shown.
Bldg# 101114193
Elec# 20178963 MSmith
Issued 10/17/23
2307 N Towner St -
2017896310/18/2023
1.1
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
SITE PLAN
N
0°
S
180°
E
90°
W
270°
SCALE
20ft1050
POOL
130'
80'
48'
5'
23'
64'
Driveway
N
T
o
w
n
e
r
S
t
Pu
b
l
i
c
S
i
d
e
w
a
l
k
Gate
Gate
MSP
PROPERTY LINE
ACD
IQ
TESLA BACKUP GATEWAY
GENERATION PANEL
TESLA POWERWALL AC II BATTERY
NOTE: Meter Spot is approved for the same location.
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
1
ROOF PLAN
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
ROOF AREA CALCULATIONS
FIRE SPRINKLERS - NO
TOTAL ROOF AREA (SQ.FT.) - 4,610
SOLAR AREA (SQ.FT.) - (E)760+(N)378=1,138
% OF COVERED AREA - 24.7%
PHOTOVOLTAIC SYSTEM
18 Enphase Energy Microinverters
(IQ8PLUS-72-2-US)
FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER
THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT7.20 KW DC
18 Hanwha 400W Modules (Q.PEAK DUO BLK ML-G10+ 400)
N
0°
S
180°
E
90°
W
270°
SCALE
0 51 10ft
18'' fire setback
18''
f
i
r
e
s
e
t
b
a
c
k
18''
f
i
r
e
s
e
t
b
a
c
k
18''
f
i
r
e
s
e
t
b
a
c
k
MSP
J/B
N
T
o
w
n
e
r
S
t
Existing Solar System
Existing Solar System
Solar Array 3
11 Hanwha Q.Cell 400W
11 IQ8+ Microinverters
Pitch: 20 Deg
Azimuth: 180 Deg
Solar Array 2
3 Hanwha Q.Cell 400W
3 IQ8+ Microinverters
Pitch: 20 Deg
Azimuth: 180 Deg
Gate
Gate
TESLA BACKUP GATEWAY
GENERATION PANEL
TESLA POWERWALL AC II BATTERY
ACD
IQ
a a
a
b
b
b
bb b
b bb bb
18''
f
i
r
e
s
e
t
b
a
c
k
18
'
'
f
i
r
e
s
e
t
b
a
c
k
a
a
a
a
Solar Array 1
4 Hanwha Q.Cell 400W
4 IQ8+ Microinverters
Pitch: 20 Deg
Azimuth: 270 Deg
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
2
SINGLE LINE
DIAGRAM
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
ITEM DESCRIPTION QTY#
PV MODULE
MAIN SERVICE PANEL
MAIN SERVICE PANEL
& UTILITY METER
BUSBAR RATING
BREAKER RATING
1
ITEM DESCRIPTION QTY#
PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3
1
1
M
MAIN
SERVICE
PANEL
120/240V
1P,3W
2
EXISTING
GROUNDING SYSTEM
UTILITY
2
3
INVERTER
PEAK PWR TRACKING VOLTAGE
CEC EFFICIENCY
PROTECTION RATING:
MAXIMUM INPUT CURRENT
MAXIMUM OUTPUT CURRENT
MAXIMUM INPUT POWER
MAXIMUM CONTINUOUS OUTPUT POWER
4 18
Enphase Energy Microinverters (IQ8PLUS-72-2-US)
29-45 V
97.0 %
NEMA 6
15.0 A
1.21 A
235-440 W
290 W
IQ COMBINER
INSTALL 15A PV 2-POLE C/B
INSTALL 20A PV 2-POLE C/B
0
1
8 1
15A PV 2-POLE C/B
(2)#14 AWG THWN-2 (L1+L2)
(1)#14 AWG-NEUTRAL
IQ GATEWAY
INFORMATION
ENPHASE IQ COMBINER BOX WITH ENPHASE IQ GATEWAY
120/240V, NEMA 3R MODEL# X-IQ-AM1-240-(4/4C)
30AAC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE,
BLADE TYPE, NEMA 3R, 120/240V 16
NEW UPGRADED
PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN
AND COMPLIANT WITH NEC 690.12
1175A
225A
FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3
18
HANWHA 400W
Q.PEAK DUO BLK
ML-G10+ 400
Voc = 45.30V
Vmp =37.13V
Isc = 11.14A
Imp = 10.77A
1
4
3
1
8
15A
2 3
20A
10
CT
R
L
100A
TESLA
BACKUP GATEWAY
NEMA3R, 100A MAX
(3) #3 AWG TWHN-2
(1) #8 AWG EGC/GEC
1 1/4" EMT TYPE CONDUIT
TESLA POWERWALL
AC II BATTERY
(3) #10 AWG TWHN-2
(1)#8 AWG EGC/GEC
7
20A
Branch a : (7) Modules, (7) Microinverters
GENERATION PANEL
120/240V 1P/3W10 125A 1GENERATION PANEL
13.5 kWh POWERWALL 2 AC
120/240V 1P/3W7 1TESLA BATTERY
(N) 175A
30A
EXISTING ABB
PVI-3.8-OUTD-US
INVERTER
EXISTING (19) TRINASOLAR
TSM-270PD05. 18 270W MODULES
EXISTING ABB
PVI-3.8-OUTD-US
INVERTER
EXISTING (19) TRINASOLAR
TSM-270PD05. 18 270W MODULES
6
3
100A
INSTALL 2P
30A CB(PV)
EXISTING
(2)#10 AWG THWN-2
(1)#8 AWG BARE CU EGC
3/4'' EMT TYPE CONDUIT
EXISTING
(2)#10 AWG PV-WIRE
(1) #6 AWG BARE CU EGC
EXISTING
(2)#10 AWG THWN-2
(1)#8 AWG BARE CU EGC
3/4'' EMT TYPE CONDUIT
Branch b : (11) Modules, (11) Microinverters
20A
225A
NEW
Existing PV system is NOT RS compliant.
20A
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
97%
0.97
1.21
1.21
18 IQ8PLUS-72-2-US (CEC)
FROM JBOX TO IQ COMBINER BOX
FROM IQ COMBINER BOX TO GENERATION PANEL
1 1/2''
TEMP. DERATE FACTOR (TEMP - 39 + 22 = 61C)0.58
RACEWAY HEIGHT FROM ROOF
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
3
WIRE SIZE
CALCULATIONSFROM PV MODULES TO JBOX
#12 AWG Q-CABLE, PV WIRE(4)1
(1) #6 AWG BARE CU EGC
2
#8 AWG CU EGC,
(3)
3
(1) #8 AWG CU EGC,
MAXIMUM INVERTER OUTPUT CURRENT
WALL TEMPERATURE FACTOR
OUTPUT CALCULATIONS
PV SYSTEM MAX DC OUTPUT
PV SYSTEM MAX AC OUTPUT
1.25
0.91
(4)
(1)
18
Pmax (PTC Rating)
3/4'' EMT TYPE CONDUIT
3/4'' EMT TYPE CONDUIT
#10 AWG THWN-2
WIRE CHART WIRE CHART
a b
2 BRANCH CIRCUITS
INVERTER OUTPUT MAX CURRENT
COEFFICIENT 1.25
BRANCH CIRCUIT CURRENT a: 7 BREAKER SIZE PER BRANCH CRCT
20A
0.8ADJST. FACTOR (4 thru 6 WIRES)
* *1.257 1.21 10.6A
ADJUSTED CONDUCTOR AMPACITY
/ /16.6 0.58 0.8 35.8A
NUMBER OF MICROINVERTERS
7.20KW
6.49KW
MAIN SERVICE PANEL RATING
BUSBAR RATING
MAIN BREAKER
PV BACKFEED BREAKER SIZE
120% RULE:
MAX ALLOWED FEED
30A
175A
225A
270A
175A''MB'' + (N)30A "SOLAR"+(E)30A "SOLAR"= 235A
≤ 270A MAX
WIRE CHART
QTY
CONSIDER CONTINUOUS COEFFICIENT
CONSIDER CONTINUOUS (A)1.25* *18 1.21 27.2
*1.25 / 0.91*18 1.21 29.9
#10 AWG THWN-2
TEMPERATURE ADJUSTMENT (A)
18
18
18
400W
* 400
371.5W
* 371.5 *
Q.PEAK DUO BLK ML-G10+ 400
117
BRANCH CIRCUIT CURRENT b: 11 BREAKER SIZE PER BRANCH CRCT
20A* *1.2511 1.21 16.6A
a) The feeder and OCPD supplying the backup loads panel must have an ampacity greater than the backup loads
calculation.
b) Utility power must be able to supply 100% of the backup loads.
c)Any one load cannot exceed the sustained power output rating of the non-utility backup source(s). CEC 702.4(B)(1)
The ampacity of relocated load conductors must be adjusted for ambient temperature and number of current-carrying
conductors in a conduit. CEC 310.15(A, B, C(1))
a) Conductors routed on the exterior will need to be adjusted for a maximum ambient temperature of 96°F-104°F.
CEC 310.15(B)(1)
b) More than 9 current-carrying conductors in a 24in. or longer conduit will generally require an increase in wire
gauge due to reduced ampacity. CEC 310.15(C)(1)
c) The adjusted conductor ampacity must be equal to or greater than the circuit ampacity (OCPD). CEC 240.4
Arc-fault circuit-interrupter (AFCI) protection must be provided for relocated circuits when the extending raceway(s) is
greater than 6 feet. This applies to all dwelling unit 120-volt 15A and 20A branch circuits except those supplying
outlets and devices exclusively in bathrooms, garages, attics, crawl spaces, and outdoors. CEC 210.12(A)
A Surge-Protective Device is required for this new service panel.
The 2022 California Electrical Code (CEC) requires all dwelling units to have an SPD installed for any new or replaced
service. These shall be of SPD Type 1 or Type 2. CEC Section 230.67, Article 242
Multi-wire circuits must be preserved. When multi-wire circuits are relocated, they must be grouped, tagged, and
otherwise identified as to the two ungrounded and single grounded (neutral) conductors. 2-pole circuit breakers are
required for each relocated multi-wire circuit. CEC 210.4(B,D)
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
11.14 A
CODE REQUIRED
SIGNAGE
4
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
60 Hz
290 W
N/A
CAUTION
NEC 705.10(B) & NEC 690.56(B)
Permanent directory or plaque providing location of service disconnecting means and
photovoltaic system disconnecting means, if not located at the same location. (Plaques shall
be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a
contrasting color to the plaque. Plaques shall be permanently attached to the equipmenq or in the
required location using an approved method that is suitable to withstand the environment to which it
is exposed. Plaques and signage shall meet legibility, defacemet, exposure and adhesion
requirements of Underwriters Laboratories marking and labeling system 969(UL969).
Plaques will have red background & white lettering.
N
0°
S
180°
E
90°
W
270°
CONTACT EXO ENERGY SOLAR (888) 463-9667
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
JB
B
O
X
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
NEC 110.27(C) & OSHA 1910.145(f)(7)
DC
D
i
s
c
o
n
n
e
c
t
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B)
DC VOLTAGE IS ALWAYS PRESENT
WHEN SOLAR MODULES
ARE EXPOSED TO SUNLIGHT NEC 690.53
NEC 690.13(B)
In
v
e
r
t
e
r
/
P
V
L
o
a
d
WARNING
THE DISCONNECTION OF THE
GROUNDING CONDUCTOR(S)
MAY RESULT IN OVERVOLTAGE
ON THE EQUIPMENT
NEC 690.31(I)
NEC 690.54
AC
D
i
s
c
o
n
n
e
c
t
NEC 690.54
NEC 690.52
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B)
PM
M
E
T
E
R
NEC 705.12(D)(3) & NEC 690.59
Ma
i
n
/
S
u
b
P
a
n
e
l
NEC 690.54
NEC 690.13 (F), NEC 705.12(B)(3-4) & NEC 690.59
NEC 705.12(D)(3) & NEC 690.59
NEC 690.15 (C) & NEC 690.33(E)(2)
NEC 690.13(B)
SINGLE 120-VOLT SUPPLY
DO NOT CONNECT
MULTIWIRE BRANCH CIRCUIT
NEC 710.15(C) & 692.9 (C)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
NEC 110.27(C) & OSHA 1910.145(f)(7)
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B)
NEC 705.12 (B)(2)(c)
LABELING REQUIREMENTS FOR ARTICLE 690
NEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether
in the open (off) or closed (on) position and be permanently marked “PV SYSTEM
DISCONNECT” or equivalent. Additional markings shall be permitted based upon
the specific system configuration. For PV system disconnecting means where the
line and load terminals may be energized in the open position, the device shall be
marked with the following words or equivalent.
NEC 690.13(F) Type of Disconnect. A dc PV system disconnecting means shall be
marked for use in PV systems or be suitable for backfeed operation.
NEC 690.15(C) An isolating device shall be rated to open the maximum circuit
current under load or be marked “Do Not Disconnect Under Load” or “Not for
Current Interrupting.”
NEC 690.31(B)(1) PV system circuit conductors shall be identified at all accessible
points of termination, connection and splices. The means of identification shall be
permitted by separate color coding, marking tape, tagging or other approved means.
NEC 690.31(G)(1) Where circuits are embedded in build up, laminate or membrane
roofing materials not covered by PV modules and associated equipment, the location
of the circuits shall be clearly marked.
NEC 690.31(G)(4) PV dc system circuit labels shall appear on every section of the wiring
system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between
labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft).
Labels required in this section shall be suitable for the environment where they are installed.
NEC 690.31(I) Solidly-grounded bipolar PV systems shall be clearly marked with a permanent,
legible warning notice indicating that the disconnection of the grounded conductor(s) may
result in overvoltage on the equipment.
NEC 690.33(E)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a
tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting.”
NEC 690.52 Alternating-current modules shall be marked with identification of terminals or
leads and with identification of the following ratings.
NEC 690.53A permanent label for the dc PV power source indicating items (1) through (3)
shall be provided by the installer at dc PV system disconnecting means and at each dc
equipment disconnecting means required by 690.15. Where a disconnecting means has more
than one dc PV power source, the values in 690.53 (1) through (3) shall be specified for each
source.
NEC 690.54 All interactive system(s) points of interconnection with other
sources shall be marked as an accessible location at the disconnecting
means as a power source and with the rated ac output current and the
nominal operating ac voltage.
NEC 690.55 The PV system output circuit conductors shall be marked to
indicate polarity where connected to energy storage systems.
NEC 690.56(B)Plaques or directories shall be installed in accordance with
705.10.
NEC 690.56(C)(3) A rapid shutdown switch shall have a label located on
or no more than 1 meter (3 ft) from the switch that includes the following
wording.
NEC 690.56(C)(1)(a-b) The type of PV system shall be labeled as described
in a) or b):
NEC 690.59 PV systems connected to other sources shall be installed in
accordance with Parts I and II of Article 705.
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH ON THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
IFC 605.11.3.1(1) & 690.56(C)(1)(a)
NEC 690.56(C)(3)
NEC 690.31(G)(3)(4)
NEC 690.31(G)(1)CO
N
D
U
I
T
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
MAXIMUM VOLTAGE
MAXIMUM CIRCUIT CURRENT
MAX RATED OUTPUT CURRENT OF
THE CHARGE CONTROLLER
OR DC-TO-DC CONVERTER
(IF INSTALLED)
DC DISCONNECT
PHOTOVOLTAIC
WARNING WARNING DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT NOMINAL OPERATING AC VOLTAGE
NOMINAL OPERATING AC FREQUENCY
MAXIMUM AC POWER
MAXIMUM AC CURRENT
MAX OVERCURRENT DEVICE RATING
FOR AC MODULE PROTECTION
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT WARNING DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT WARNING
CAUTION
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
WARNING
POWER SOURCE OUTPUT
CONNECTION. DO NOT
RELOCATE THIS
OVERCURRENT DEVICE.
WARNING
DO NOT DISCONNECT
UNDER LOAD
RAPID SHUT DOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING
PHOTOVOLTAIC POWER SOURCE
DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW
WARNING
FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY
AND CONDUCTORS LEAVING THE ARRAY: SIGH TO
BE LOCATED ON OR NO MORE THAN 3 FT AWAY
FROM SERVICE DISCONNECTING MEANS TO WHICH
THE PV SYSTEMS ARE CONNECTED AND SHALL
INDICATE THE LOCATION OF ALL IDENTIFIED RAPID
SHUTDOWN SWITCHES IF NOT AT THE SAME
LOCATION. [CEC 690.56(C)(1)(A)]
50.74 V
240 Vac
240 Vac
240 Vac
240 Vac
NEC 690.13(B)
AC DISCONNECT
PHOTOVOLTAIC
30 A
21.78 A
21.78 A
21.78 A
21.78 A
MAIN PANEL
TESLA BATTERY
GENERATION PANEL
N
T
o
w
n
e
r
S
t
PV DISCONNECT
NOT RS COMPLIANT
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
ATTACHMENT
LAYOUT
5
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
STRUCTURAL STAMPROOF
PITCH
ROOFING
TYPE
ATTACHMENT
TYPE
FRAMING
TYPE
FRAMING
SIZE
PENETRATION
PATTERN
20°
RACKING
TYPE
MAX
PENETRATION
SPACING
ROOFING
LAYERS
WIND SPEED 110 MPH EXPOSURE C
LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE
SEALED WITH CHEM LINK SEALANT OR EQUIVALENT.
MODULE WEIGHT (LBS)
# OF MODULES
TOTAL MODULE WEIGHT (LBS)
RACK WEIGHT (LBS)
TOTAL SYSTEM WEIGHT (LBS)
# OF STANDOFFS
LOADING PER STANDOFF (LBS)
TOTAL MODULE AREA (SQ.FT.)
LOADING (PSF)
WEIGHT LOAD CALCULATION INDEX
ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER
SURFACE IS FACED WITH FELT PAPER
TOTAL ROOF AREA (Sq. FT)
% OF COVERED AREA
PV MODULE MODEL #
MICROINVERTER WEIGHT (LBS)
18
Roof 1 1 Layer M Concrete Tile EcoFasten Truss Stacked 48"2"X4" @ 24" O.C
2''X6'' Blocking
SOLAR MODULE
ROOF 1,2
ASCE 7-16
Max 3.5''
48.5
Q.PEAK DUO BLK ML-G10+ 400
47
378
4610
873
175
43
1090
23.2
2.88
8.2
20°Roof 2 1 Layer Comp Shingle Ironridge XR10 Truss Stacked 48"2"X4" @ 24" O.C
PART TABLE
P/N DESCRIPTION
004085M FLASHLOC COMP KIT MILL, 20 PACK
004085D FLASHLOC COMP KIT DARK, 20 PACK
SS LAG BOLT
W/ SS EPDM BONDED WASHER
SS SERRATED T-BOLT
SS SERRATED FLANGE NUT
FLASHLOC BASE
MILL OR DARK
33
21 4"
31 2"
67 8"
Unirac Flashloc Kit
MIN 2.5" EMBEDMENT
RACKING RAIL
ATTACHMENT
ROOF FRAMING
5/16" X 4.0"
Ecofasten Universal Tile Hook
ATTACHMENT DETAILS
ROOF SHEETING
WATERPROOF
MEMBRAIN ROOF TILE
ECOFASTEN RAIL
5/16"x4.0" LAG BOLT
WITH 2 1/2"MIN
THREAS PENETRATION
ECOFASTEN'S CLICKFIT
UNIVERSAL TILE HOOK
TILE HOOK FLASHING
TILE HOOK ADDENDUMSOLAR MODULE
48''24''
Roof 2
Roof 2
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
D1
MODULE
DATA SHEET
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
INVERTER
DATA SHEET
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D2
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
IQ COMBINER
BOX DATA SHEET
D3
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D4.1
RACKING
DATA SHEET
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D4
RACKING
DATA SHEET
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D5.1
ATTACHMENT
DATA SHEET
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D5
ATTACHMENT
DATA SHEET
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D6.1
GROUNDING
SPECS
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D6
GROUNDING
SPECS
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D7
BATTERY
DATA SHEET
Signed 08/09/2023
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D8
SURVEY PHOTO 2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
D9
SURVEY PHOTO 2307 N Towner St -
2017896310/18/2023
3.1
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
PANEL
SCHEDULES
GENERATION PANEL SCHEDULE
1 2
3 4 15A
5 6 15A
7 8 20A
9 N/A / A/C 30A/30A 10 20A
11 A/C / N/A 30A/30A 12 20A
13 Old Solar/Batt 20A/30A 14 20A
15 Batt/Old Solar 30A/20A 16 20A
17 Old Solar/New Solar 20A/30A 18
19 New Solar/Old Solar 30A/20A 20
MAIN SERVICE PANEL SCHEDULE
1
A/C 40A
2 20A/20A
3 4
5
Tesla Gateway 100A
6
Range 50A
7 8
9
30A
10
50A
11 12
13 20A 14 20A
15 16
17 18
Meter 20A
19 20
2307 N Towner St -
2017896310/18/2023
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
3.2
GENERATION
PANEL LOAD
CALCULATIONS
2307 N Towner St -
2017896310/18/2023
76 North Meadowbrook Drive
Scott E. Wyssling, PE Alpine, UT 84004
Coleman D. Larsen, SE, PE office (201) 874-3483
Gregory T. Elvestad, PE swyssling@wysslingconsulting.com
December 14, 2022
Revised May 16, 2023
EXO Energy
1247 Simpson Way
Escondido, CA 92029
Re: Engineering Services
Vandervoort Residence
2307 North Towner Street, Santa Ana CA
7.200 kW System
To Whom It May Concern:
We have received information regarding solar panel installation on the roof of the above referenced
structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
to support the additional loads imposed by the proposed solar system.
A.Site Assessment Information
1.Site visit documentation identifying attic information including size and spacing of framing
for the existing roof structure.
2.Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information will be utilized for approval and construction
of the proposed system.
B.Description of Structure:
Roof Framing: Assumed prefabricated wood trusses at 24” on center. All truss members
are constructed of 2x4 dimensional lumber.
Roof Material: Concrete Tile & Composite Asphalt Shingles
Roof Slope: 20 degrees
Attic Access: Inaccessible
Foundation: Permanent
C.Loading Criteria Used
•Dead Load
o Existing Roofing and framing = 13 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 16 PSF
•Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 psf
•Live Load = 20 psf (reducible) – 0 psf at locations of solar panels
•Ground Snow Load = 0 psf
•Wind Load based on ASCE 7-16
o Ultimate Wind Speed = 95 mph (based on Risk Category II)
o Exposure Category C
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance
with the 2022 California Building Code, including provisions allowing existing structures to not
require strengthening if the new loads do not exceed existing design loads by 105% for gravity
elements and 110% for seismic elements. This analysis indicates that the existing framing will
support the additional panel loading without damage, if installed correctly.
2307 N Towner St -
2017896310/18/2023
Page 2 of 2
D.Solar Panel Anchorage
1.Concrete Tile
i.The solar panels shall be mounted in accordance with the most recent EcoFasten
installation manual. If during solar panel installation, the roof framing members appear
unstable or deflect non-uniformly, our office should be notified before proceeding with the
installation.
ii.The maximum allowable withdrawal force for a 5/16” lag screw is 229 lbs per inch of
penetration as identified in the National D esign Standards (NDS) of timber construction
specifications. Based on two screws with a minimum penetration depth of 2½”, the
allowable capacity per connection is greater than the design withdrawal force (demand).
Considering the variable factors for the existing roof framing and installation tolerances,
the connection using two 5/16” diameter lag screw with a minimum of 2½” embedment will
be adequate and will include a sufficient factor of safety.
iii.Considering the wind speed, roof slopes, size and spacing of framing members, and
condition of the roof, the panel supports shall be placed no greater than 48” on centers.
2.Composite Asphalt Shingles
i.The solar panels shall be mounted in accordance with the most recent Unirac installation
manual. If during solar panel installation, the roof framing members appear unstable or
deflect non-uniformly, our office should be notified before proceeding with the installation.
ii.The maximum allowable withdrawal force for a 5/16” lag screw is 229 lbs per inch of
penetration as identified in the National Design Standards (NDS) of timber construction
specifications. Based on a minimum penetration depth of 2½”, the allowable capacity per
connection is greater than the design withdrawal force (demand). Considering the variable
factors for the existing roof framing and installation tolerances, the connection using one
5/16” diameter lag screw with a minimum of 2½” embedment will be adequate and will
include a sufficient factor of safety.
iii.Considering the wind speed, roof slopes, size and spacing of framing members, and
condition of the roof, the panel supports shall be placed no greater than 48” on center.
Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing
roof system will adequately support the additional loading imposed by the solar system. This evaluation is in
conformance with the 2022 California Building Code, current industry standards, and is based on information
supplied to us at the time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Very truly yours,
Scott E. Wyssling, PE
California License No. 83664
2307 N Towner St -
2017896310/18/2023
Wyssling Consulting
76 N. Meadowbrook Drive
Alpine, UT 84004
(201) 874-3483
swyssling@wysslingconsulting.com
Existing Vandervoort Residence
Roof Dead Load 2307 North Towner Street
2.0 psf Composite Shingle Santa Ana, CA
1.6 psf 1/2" Plywood Sheathing
0.8 psf 2x4 Trusses @ 24 in. o.c.
1.0 psf Ceiling, Mechanical, Electrical
1.6 psf Miscellaneous
7.0 psf TOTAL
Second Floor Dead Load
0 psf Floor Finishes
0 psf 1 1/8" Subfloor Sheathing
0 psf Joists @ 16' o.c.
0 psf Partitions
0 psf Ceiling, Mechanical, Electrical
0 psf Miscellaneous
0 psf TOTAL
Roof Live Load Floor Live Load
20 psf 0 psf
Roof Snow Load
Ground SnowLoad=0 psf (to be divided by cosine of roof angle for horizontal projection ASCE 7 Sec. 7.4)
pf = 0.7 Ce Ct I pg =0 psf Ce = 1, Ct = 1.1 Flat Roof Snow Load (ASCE 7-16 Eq. 7.3-1)
Cs =0.91 ASCE 7-16 Figure 7.4-1
Additional
Roof Dead Load - New Solar Panels
3 psf
Roof Live Load at Solar Panels
0 psf
Roof Snow Load at Solar Panels
0 psf Sloped Roof Snow Load (ASCE 7-16 Eq. 7.4-1)
Total
Total Existing Roof Load = (DLROOF + Max(LLROOF or S)) AreaROOF
124470 lbs
Total New Roof Load = (DLROOF + DLADD + Max(LLROOF or S)) AreaROOF
117848 lbs
Change in Demand = (Total New Roof Load - Existing Roof Load) / Existing Roof Load
-5.32%
2021 IEBC Section 805.2 states:
"Any existing gravity load-carrying structural element for which an alteration causes an increase in design gravity load
of more than 5 percent shall be strengthened, supplemented, replaced or otherwise altered as needed to carry the
increased gravity load required by this code for new structures."
Gravity Loads
Total New Gravity Loads are less than Existing Loads. OK
Signed 5/16/2023
2307 N Towner St -
2017896310/18/2023
Wyssling Consulting
76 N. Meadowbrook Drive
Alpine, UT 84004
(201) 874-3483
swyssling@wysslingconsulting.com
V =95 Basic Wind Speed Vandervoort Residence
Exposure C ASCE 7-16, Section 26.7 2307 North Towner Street
Kz =0.85 Velocity Pressure Coefficient, ASCE 7-16, Figure 26.10-1 Santa Ana, CA
Kzt =1 Topographic Factor, ASCE 7-16, Section 26.8.2
Kd =0.85 Directionality Factor, ASCE 7-16, Section 26.6
Ke =0.995 Ground Elevation Factor, ASCE 7-16, Section 26.9
qh =16.6 psf qh = 0.00256KzKztKdKeV2 (ASCE 7-16 Eq. 26.10-1)
Roof Angle =20 deg
Roof Type Gable
sanchor =48 in Horizontal spacing of roof anchors
Atrib =12.33 sf Panel Area tributary to each roof anchor
GCp External Pressure Coefficient, ASCE 7-16, Figure 30.3-2
Roof Zone Zone 1 2e 2n 2r 3e 3r
-2.00 -2.00 -2.98 -2.98 -2.98 -3.55
ga =0.79 Pressure Equalization Factor, ASCE 7-16 Figure 29.4.-8
gE =1.00 Edge Array Factor, ASCE 29.4.4 edges < 0.5*building height, and panel spacing < 4ft.
pnet = qhGCpgEga =Design Wind Pressure, ASCE 7-16, Equation 29.4-7
Roof Zone 1 2e 2n 2r 3e 3r
-26 psf -26 psf -39 psf -39 psf -39 psf -47 psf Min Pressure = -16 psf
Use 26 psf Use 26 psf Use 39 psf Use 39 psf Use 39 psf Use 47 psf ULTIMATE
x 0.6 =16 psf 16 psf 23 psf 23 psf 23 psf 28 psf ALLOWABLE
Connection to Existing Roof Framing
F.S. =1 Additional Factor of Safety applied to withdrawl force, if desired
Atrib =12.3 ft2
DLpanel =3 psf
Roof Zone 1 2e 2n 2r 3e 3r
Wuplift =26 psf 26 psf 39 psf 39 psf 39 psf 47 psf
Plag = F.S. x Atrib x (0.6D - 0.6W) =Withdrawl force for each roof anchor
Roof Zone 1 2e 2n 2r 3e 3r
-174.9 lbs -174.9 lbs -270.1 lbs -270.1 lbs -270.1 lbs -325.7 lbs
Connection Capacity
db =5/16 in Lag Screw diameter
Dpen =2 1/2 in Lag Screw penetration into existing framing member
No. of Screws 2 Screws per Connection
Species of wood framing
CD =1.6 Load Duration Factor for Wind Loading, NDS Table 2.3.2
Ct =0.7 Temperature Factor, NDS Table 10.3.4
W =205 lb/in Withdrawl Capacity, NDS Equation 11.2-1
W' = CD x Ct x W =229 lb/in Adjusted withdrawl value
Pallow = Dpen x W' =1147 lbs (Using (2) screws per connection)
Roof Zone 1 2e 2n 2r 3e 3r
DEMAND =175 lbs 175 lbs 270 lbs 270 lbs 270 lbs 326 lbs
CAPACITY =1147 lbs 1147 lbs 1147 lbs 1147 lbs 1147 lbs 1147 lbs
up to72in ok up to72in ok up to72in ok up to72in ok up to72in ok up to72in ok
Spruce-Pine-Fir
Wind Uplift
Rooftop Solar Panels Parallel to Roof Surface
ASCE 7-16, Section 29.4.4
This analysis calculates the
capacity of the lag screws
only. For capacity of the
complete mounting system,
please see manufacturer's
recommendations.
Signed 5/16/2023
2307 N Towner St -
2017896310/18/2023
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
2307 N Towner St -
2017896310/18/2023
2307 N Towner St -
2017896310/18/2023
Certificate Of Completion
Envelope Id: 1D151051274C4D8BA89565DE58EBBF7D Status: Completed
Subject: Complete with DocuSign: Revision sheet -22.pdf
Source Envelope:
Document Pages: 1 Signatures: 1 Envelope Originator:
Certificate Pages: 1 Initials: 0 Wesley Calland
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
pto@goexoenergy.com
IP Address: 70.166.84.110
Record Tracking
Status: Original
12/28/2022 10:17:00 AM
Holder: Wesley Calland
pto@goexoenergy.com
Location: DocuSign
Signer Events Signature Timestamp
DAVID VANDERVOORT
david.vandervoort@yahoo.com
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 76.170.1.138
Signed using mobile
Sent: 12/28/2022 10:17:56 AM
Viewed: 12/28/2022 10:27:06 AM
Signed: 12/28/2022 10:27:22 AM
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Justin Romeo
Justinr@goexoenergy.com
Security Level: Email, Account Authentication
(None)
Sent: 12/28/2022 10:17:57 AM
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 12/28/2022 10:17:57 AM
Certified Delivered Security Checked 12/28/2022 10:27:06 AM
Signing Complete Security Checked 12/28/2022 10:27:22 AM
Completed Security Checked 12/28/2022 10:27:22 AM
Payment Events Status Timestamps
2307 N Towner St -
2017896310/18/2023
3.1
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
PANEL
SCHEDULES
GENERATION PANEL SCHEDULE
1 2
3 4 15A
5 6 15A
7 8 20A
9 N/A / A/C 30A/30A 10 20A
11 A/C / N/A 30A/30A 12 20A
13 Old Solar/Batt 20A/30A 14 20A
15 Batt/Old Solar 30A/20A 16 20A
17 Old Solar/New Solar 20A/30A 18
19 New Solar/Old Solar 30A/20A 20
MAIN SERVICE PANEL SCHEDULE
1
A/C 40A
2 20A/20A
3 4
5
Tesla Gateway 100A
6
Range 50A
7 8
9
30A
10
50A
11 12
13 20A 14 20A
15 16
17 18
Meter 20A
19 20
Signed 08/09/2023
REVISION TO:
20178963
Revised
20181798
APPROVALS:
ELEC - MSmith
2307 N Towner St -
201817982/9/2024
PV SYSTEM
AS INDICATED
AUGUST 09, 2023
DAVID VANDERVOORT
2307 N TOWNER ST,
SANTA ANA, CA 92706
Current Insight, LLC
2852 W. Amini Way
South Jordan, UT
84095
EXO ENERGY
Address:
1247 Simpson Way
Escondido, CA 92029
Phone Number:
208-351-4153
CSLB:#1063308
Drafted By:
CONTRACTOR
3.2
GENERATION
PANEL LOAD
CALCULATIONS
Signed 08/09/2023
2307 N Towner St -
201817982/9/2024
CALIFORNIA LICENSE NO. C83664
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA PV-1
AERIAL MAP VICINITY MAP
SCOPE OF WORK
CONTRACTOR
DATE:
DRAWN BY:
REVIEWED BY:
CODE REFERENCE
DESIGN CRITERIA
2307 NORTH TOWNER STREET,
SANTA ANA, CALIFORNIA 92706
(33.767339,-117.879137)
18 MODULES - 7.200 KW DC 6.984 KW AC SYSTEM SIZE
DAVID VANDERVOORT RESIDENCE - 2307 NORTH TOWNER STREET, SANTA ANA, CALIFORNIA 92706
NEW PV ROOFTOP AND BATTERY SYSTEM DESIGN
ABD
1. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND REVIEW ALL MANUFACTURER INSTALLATION DOCUMENTS PRIOR TO INITIATING CONSTRUCTION.
2. ALL COMPONENTS SHALL BE NEW AND LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY AND LISTED FOR THEIR SPECIFIC APPLICATION.
3. OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED OR BETTER.
4. ACCESS TO ELECTRICAL COMPONENTS OVER 150 VOLTS TO GROUND SHALL BE RESTRICTED TO QUALIFIED PERSONNEL.
5. CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING COMMISSIONING, AND ACCEPTANCE WITH
THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED.
6. EACH MODULE TO BE GROUNDED USING THE SUPPLIED CONNECTION POINT PER THE MANUFACTURER'S REQUIREMENTS. ALL PV MODULES, EQUIPMENT, AND METALLIC
COMPONENTS ARE TO BE BONDED. IF THE EXISTING GROUNDING ELECTRODE SYSTEM CANNOT BE VERIFIED OR IS ONLY METALLIC WATER PIPING, IT IS THE CONTRACTOR'S
RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE.
7. DC CONDUCTORS SHALL BE RUN IN EMT AND/OR MC (METAL CLAD CABLE) AND SHALL BE LABELED. ALL DC CONDUCTORS RUN INSIDE OF THE STRUCTURE SHALL BE INSTALLED
A MINIMUM OF 18" BELOW THE ROOF DECK.
8. EXPOSED NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH APPLICABLE NEC.
9. CONFIRM LINE SIDE VOLTAGE AT THE ELECTRIC UTILITY SERVICE PRIOR TO CONNECTING INVERTER. VERIFY SERVICE VOLTAGE IS WITHIN INVERTER VOLTAGE OPERATIONAL
RANGE.
10. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND ANCHOR CONDUIT RUNS AS REQUIRED PER CODE.
11. ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE, AND FOR ROOF-MOUNTED SYSTEMS, WIRING MUST BE
PERMANENTLY AND COMPLETELY HELD OFF OF THE ROOF SURFACE.
12. ALL ROOF PENETRATIONS MUST BE SEALED OR FLASHED.
13. EQUIPMENT MAY BE SUBSTITUTED FOR SIMILAR EQUIPMENT BASED ON AVAILABILITY. SUBSTITUTED EQUIPMENT SHALL COMPLY WITH DESIGN CRITERIA.
14. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND
THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
15. WHENEVER A DISCREPANCY IN THE QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND
INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS TO ENSURE COMPLETE
COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ENGINEERS.
GENERAL NOTES
ATF
SCOTT E. WYSSLING, P.E.
INSTALL 7.200 KW DC ROOF MOUNTED
PV SYSTEM UTILIZING
(18) HANWHA Q.CELL BLK ML-G10+ 400
(18) ENPHASE IQ8PLUS-72-2-US
(1) ENPHASE - X-IQ-AM1-240-4C
(1) 30A PV AC DISCONNECT
(1) 30A ESS AC DISCONNECT
(1) 125 GENERATION PANEL
(1) TESLA BACKUP GATEWAY 2
(1) TESLA POWERWALL AC II BATTERY
ECOFASTEN CLICKFIT RAIL RACKING WITH
(51) ECOFASTEN TILE HOOK FLASHING MOUNTS
NEW 225 A BUSBAR WITH 175 A MAIN BREAKER
INTERCONNECTION METHOD: LOAD SIDE BREAKER
ROOF TYPE: CONCRETE W TILE
NUMBER OF STORIES: 1
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
ASCE 7-16 WIND SPEED: 95 MPH
EXPOSURE CATEGORY C
GROUND SNOW LOAD: 0 PSF
AHJ: SANTA ANA
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA RESIDENTIAL CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
2022 CALIFORNIA HISTORICAL CODE
2022 CALIFORNIA EXISTING BUILDING CODE
2022 CALIFORNIA REFERENCED STANDARDS CODE
2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE
7/26/2024
COVER SHEET
SHEET INDEX
PV-1
PV-3
PV-4
S-1
E-1
E-2
E-3
SITE PHOTOS
PV LABELS
EQUIPMENT INFORMATION
ELECTRICAL DIAGRAM
STRUCTURAL DETAILS
MOUNTING PLAN
SITE PLAN-2
COVER SHEET
PV-5
MANUFACTURER'S SPECSSPECS 1-7
INSTALL CHECKLISTPV-6
E-4 PLACARD
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
REVISIONS
NO.
1
2
DATE
swyssling@wysslingconsulting.com
(201) 874-3483
COMMENTS
PV-2 SITE PLAN-1
E-5 ELEVATION DETAILS
07/26/2024 ESS DISCONNECT LOCATION
Signed 7/26/2024
Elec#: 20183254
Revision to:
Elec# 20178963 & 20181798
Approvals:
M Smith
The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all
applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any
certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown.
2307 N Towner St
8/23/2024
EW
S
N
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
ÀPN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
UM MSPBI GENINVINVCOM
AC
ACB
(E) CONCRETE DRIVEWAY
NO
R
T
H
T
O
W
N
E
R
S
T
R
E
E
T
SWIMMING POOL (TYP.)
FR
O
N
T
O
F
H
O
M
E
PROPERTY LINE
B
BB
GATE
GATE
UTILITY METER
MAIN SERVICE PANEL
AC DISCONNECT
DC DISCONNECT
AC COMBINER PANEL
INVERTER
BACKUP INTERFACE
BATTERY
PRODUCTION METER
SUBPANEL
UNCTION BOX
FIRE PATHWAY
PROPERTY LINE
ATTIC RUN CONDUIT
EXTERNAL CONDUIT
SATELLITE DISH
SITE PLAN LEGEND
MODULE SPEC AND ROOF INFO:
SCALE: 1/16À À 1À-0À
ROOF OBSTRUCTION (TYP.)
CHIMNEY
ROOF VENT (TYP.)
COM
PM
B
B
UM
MSP
INV
DC
BI
AC
SUB
PV MODULE TYPE - HANWHA .CELL BLK ML-G10À 400 (400W)
SOLAR AREA - 380.44 S FT
EXISTING SOLAR AREA - 635.04 S FT
ROOF AREA - 4610 S FT
ROOF COVERAGE -22.03
UTILITY:
GAS METER GM
PV-2
DATE:8/9/2024
SITE PLAN-1
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
I SYSTEM CONTROLLER I
SITE PLAN NOTES:
1. VERIFY ALL OBSTRUCTIONS AND DIMENSIONS IN THE FIELD.
2. PROVIDE RAIL SPLICES AS REUIRED BY MANUFACTURERÀS GUIDELINES.
3. NO SIGNIFICANT SHADING WILL RESULT FROM EXISTING ROOF OBSTRUCTIONS.
4. PV MODULES CANNOT BE INSTALLED OVER OR BLOCK ATTIC, PLUMBING, FURNACE OR
WATER HEATER VENTS
5. AC DISCONNECT SHALL BE VISIBLE-OPEN TYPE, LOCKABLE AND READILY ACCESSIBLE. TO
BE WITHIN 10À OF THE UTILITY METER
6. 3/4À OR GREATER CONDUIT RUN (7/8À ABOVE ROOF SURFACE)
7. ROOF ACCESS POINTS SHALL BE LOCATED IN AREAS THAT DO NOT REUIRE THE
PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND
LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE THE
ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE
LIMBS, WIRES OR SIGNS.
LOAD CENTER LC
127À-11À
81À-11À
125À-4À
82À-5À
3À-9À
36À-11À
7À-1À
17À-11À
2307 N Towner St
8/23/2024
EW
S
N
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
ÀPN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
(E) INVERTER
B
(E) INVERTER
NO
R
T
H
T
O
W
N
E
R
S
T
R
E
E
T
FR
O
N
T
O
F
H
O
M
E
B
BB
18À FIRE PATHWAY (TYP.)
ROOF ACCESS POINT
ROOF OBSTRUCTION (TYP.)
(E) UTILITY METER
(N) BACKUP GATEWAY
(N) BATTERY
(N) MAIN SERVICE PANEL
(N) GENERATION PANEL
(N) AC COMBINER PANEL
ROOF SECTION 1
TILT: 20À
AZIMUTH: 270À
ROOF SECTION 2
TILT: 20À
AZIMUTH: 180À
ROOF SECTION 3
TILT: 20À
AZIMUTH: 180À
(N) AC DISCONNECT
(N) ESS DISCONNECT
(E) PV SYSTEM
CHIMNEY (TYP.)
(N) PV MODULE EUIPPED
W/ 1 MICRO-INVERTER
PER MODULE
AC UM MSPBI GENINVINVCOM
AC
UTILITY METER
MAIN SERVICE PANEL
AC DISCONNECT
DC DISCONNECT
AC COMBINER PANEL
INVERTER
BACKUP INTERFACE
BATTERY
PRODUCTION METER
SUBPANEL
UNCTION BOX
FIRE PATHWAY
PROPERTY LINE
ATTIC RUN CONDUIT
EXTERNAL CONDUIT
SATELLITE DISH
SITE PLAN LEGEND
MODULE SPEC AND ROOF INFO:
SCALE: 3/32À À 1À-0À
ROOF OBSTRUCTION (TYP.)
CHIMNEY
ROOF VENT (TYP.)
COM
PM
B
B
UM
MSP
INV
DC
BI
AC
SUB
PV MODULE TYPE - HANWHA .CELL BLK ML-G10À 400 (400W)
SOLAR AREA - 380.44 S FT
EXISTING SOLAR AREA - 635.04 S FT
ROOF AREA - 4610 S FT
ROOF COVERAGE -22.03
UTILITY:
GAS METER GM
I SYSTEM CONTROLLER I
SITE PLAN NOTES:
1. VERIFY ALL OBSTRUCTIONS AND DIMENSIONS IN THE FIELD.
2. PROVIDE RAIL SPLICES AS REUIRED BY MANUFACTURERÀS
GUIDELINES.
3. NO SIGNIFICANT SHADING WILL RESULT FROM EXISTING ROOF
OBSTRUCTIONS.
4. PV MODULES CANNOT BE INSTALLED OVER OR BLOCK ATTIC,
PLUMBING, FURNACE OR WATER HEATER VENTS
5. AC DISCONNECT SHALL BE VISIBLE-OPEN TYPE, LOCKABLE AND
READILY ACCESSIBLE. TO BE WITHIN 10À OF THE UTILITY METER
6. 3/4À OR GREATER CONDUIT RUN (7/8À ABOVE ROOF SURFACE)
7. ROOF ACCESS POINTS SHALL BE LOCATED IN AREAS THAT DO NOT
REUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS
SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS
OF BUILDING CONSTRUCTION IN LOCATIONS WHERE THE ACCESS
POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS
SUCH AS TREE LIMBS, WIRES OR SIGNS.
LOAD CENTER LC
PV-3
DATE:8/9/2024
SITE PLAN-2
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
2307 N Towner St
8/23/2024
EW
S
N
CALIFORNIA LICENSE NO. C83664
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
UM
MS
P
BI
GE
N
IN
V
IN
V
CO
M
AC
ACB
(E) CONCRETE DRIVEWAY
NO
R
T
H
T
O
W
N
E
R
S
T
R
E
E
T
SWIMMING POOL (TYP.)
FR
O
N
T
O
F
H
O
M
E
PROPERTY LINE
JB
JBJB
GATE
GATE
UTILITY METER
MAIN SERVICE PANEL
AC DISCONNECT
DC DISCONNECT
AC COMBINER PANEL
INVERTER
BACKUP INTERFACE
BATTERY
PRODUCTION METER
SUBPANEL
JUNCTION BOX
FIRE PATHWAY
PROPERTY LINE
ATTIC RUN CONDUIT
EXTERNAL CONDUIT
SATELLITE DISH
SITE PLAN LEGEND
MODULE SPEC AND ROOF INFO:
SCALE: 1/16" = 1'-0"
ROOF OBSTRUCTION (TYP.)
CHIMNEY
ROOF VENT (TYP.)
COM
PM
B
JB
UM
MSP
INV
DC
BI
AC
SUB
PV MODULE TYPE - HANWHA Q.CELL BLK ML-G10+ 400 (400W)
SOLAR AREA - 380.44 SQ FT
EXISTING SOLAR AREA - 635.04 SQ FT
ROOF AREA - 4610.00 SQ FT
ROOF COVERAGE -22.03%
UTILITY:
GAS METER GM
PV-2
DATE:
SCOTT E. WYSSLING, P.E.
7/26/2024
SITE PLAN-1
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
IQ SYSTEM CONTROLLER IQ
SITE PLAN NOTES:
1. VERIFY ALL OBSTRUCTIONS AND DIMENSIONS IN THE FIELD.
2. PROVIDE RAIL SPLICES AS REQUIRED BY MANUFACTURER'S GUIDELINES.
3. NO SIGNIFICANT SHADING WILL RESULT FROM EXISTING ROOF OBSTRUCTIONS.
4. PV MODULES CANNOT BE INSTALLED OVER OR BLOCK ATTIC, PLUMBING, FURNACE OR
WATER HEATER VENTS
5. AC DISCONNECT SHALL BE VISIBLE-OPEN TYPE, LOCKABLE AND READILY ACCESSIBLE. TO
BE WITHIN 10' OF THE UTILITY METER
6. 3/4" OR GREATER CONDUIT RUN (7/8" ABOVE ROOF SURFACE)
7. ROOF ACCESS POINTS SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE
PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND
LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE THE
ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE
LIMBS, WIRES OR SIGNS.
LOAD CENTER LC
127'-11"
81'-11"
125'-4"
82'-5"
3'-9"
36'-11"
7'-1"
17'-11"
Signed 7/26/2024
2307 N Towner St
8/23/2024
EW
S
N
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
ÀPN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
B
NO
R
T
H
T
O
W
N
E
R
S
T
R
E
E
T
FR
O
N
T
O
F
H
O
M
E
B
BB
ROOF OBSTRUCTION (TYP.)
RAIL (TYP.)
MOUNT (TYP.)
SEE TABLE BELOW
SEE TABLE BELOW FOR
ROOF FRAMING SIZE
ROOF SECTION 1
TILT: 20À
AZIMUTH: 270À
ROOF SECTION 2
TILT: 20À
AZIMUTH: 180À
ROOF SECTION 3
TILT: 20À
AZIMUTH: 180À
(E) PV SYSTEM
ROOF FRAMING 24À ON CENTER
48À MAX MOUNT SPACING
CHIMNEY (TYP.)
(N) PV MODULE EUIPPED
W/ 1 MICRO-INVERTER
PER MODULE
AC UM MSPBI GENINVINVCOM
AC
SCALE: 3/32À À 1À-0À
ROOF
FRAMING
FRAMING
SPACING ROOF TYPE MAX MOUNT
SPACING MOUNT MOUNT
TYPE
EMBEDMENT
DEPTH
ROOF SECTION 1 2X4 - TRUSSES 24À CONCRETE W TILE 48À ECOFASTEN TILE
HOOK FLASHING ROOF MOUNT 2-1/2À
ROOF SECTION 2 2X4 - TRUSSES 24À CONCRETE W TILE 48À ECOFASTEN TILE
HOOK FLASHING ROOF MOUNT 2-1/2À
ROOF SECTION 3 2X4 - TRUSSES 24À CONCRETE W TILE 48À ECOFASTEN TILE
HOOK FLASHING ROOF MOUNT 2-1/2À
PROPERTY LINE
ATTIC RUN CONDUIT
EXTERNAL CONDUIT
MOUNTING PLAN
LEGEND
RAIL
MOUNT
ROOF FRAMING
ROOF OBSTRUCTION (TYP.)
CHIMNEY
ROOF VENT (TYP.)
UTILITY METER
MAIN SERVICE PANEL
AC DISCONNECT
DC DISCONNECT
AC COMBINER PANEL
INVERTER
BACKUP INTERFACE
BATTERY
PRODUCTION METER
SUBPANEL
UNCTION BOX
SATELLITE DISH
COM
PM
B
B
UM
MSP
INV
DC
BI
AC
SUB
GAS METER GM
I SYSTEM CONTROLLER I
LOAD CENTER LC
METAL SEAMS
MOUNTING PLAN NOTES:
1. VERIFY ALL OBSTRUCTIONS AND DIMENSIONS IN THE FIELD.
2. PROVIDE RAIL SPLICES AS REUIRED BY MANUFACTURERÀS GUIDELINES.
3. NO SIGNIFICANT SHADING WILL RESULT FROM EXISTING ROOF OBSTRUCTIONS.
4. PV MODULES CANNOT BE INSTALLED OVER OR BLOCK ATTIC, PLUMBING,
FURNACE OR WATER HEATER VENTS
5. ACTUAL ROOF CONDITIONS AND ROOF FRAMING (OR SEAM)LOCATIONS MAY
VARY. INSTALL PER MANUFACTURER(S)INSTALLATION GUIDELINES AND
ENGINEERED SPANS FOR ATTACHMENTS
CANTILEVER NOTES:
1. CANTILEVER (OVERHANG) LENGTHS CAN BE UP TO 33 OF THE
SPAN LENGTH.
2. THE CANTILEVER IS DEFINED AS THE DISTANCE FROM THE
CENTER OF THE MOUNT TO THE EDGE OF THE RAIL
PV-4
DATE:8/9/2024
MOUNTING PLAN
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
2307 N Towner St
8/23/2024
76 North Meadowbrook Drive
Scott E. Wyssling, PE Alpine, UT 84004
Coleman D. Larsen, SE, PE office (201) 874-3483
Gregory T. Elvestad, PE swyssling@wysslingconsulting.com
July 1, 2024
Exo Energy
1358 La Miranda Drive
San Marcos, CA 92071
Re: Engineering Services
Vandervoort Residence
2307 N Towner Street, Santa Ana, CA
7.200 kW System
To Whom It May Concern:
We have received information regarding solar panel installation on the roof of the above referenced
structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
to support the additional loads imposed by the proposed solar system.
A. Site Assessment Information
1. Site visit documentation identifying attic information including size and spacing of framing
for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information will be utilized for approval and construction
of the proposed system.
B. Description of Structure:
Roof Framing: Assumed prefabricated wood trusses at 24” on center. All truss members
are constructed of 2x4 dimensional lumber.
Roof Material: Tile Roofing
Roof Slope: 20 degrees
Attic Access: Inaccessible
Foundation: Permanent
C. Loading Criteria Used
• Dead Load
o Existing Roofing and framing = 13 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 16 PSF
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 psf
• Live Load = 20 psf (reducible) – 0 psf at locations of solar panels
• Ground Snow Load = 0 psf
• Wind Load based on ASCE 7-16
o Ultimate Wind Speed = 95 mph (based on Risk Category II)
o Exposure Category C
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance
with the 2022 California Building Code, including provisions allowing existing structures to not
require strengthening if the new loads do not exceed existing design loads by 105% for gravity
elements and 110% for seismic elements. This analysis indicates that the existing framing will
support the additional panel loading without damage, if installed correctly.
2307 N Towner St
8/23/2024
Page 2 of 2
D. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent Ecofasten installation
manual. If during solar panel installation, the roof framing members appear unstable or deflect non-
uniformly, our office should be notified before proceeding with the installation.
2. The maximum allowable withdrawal force for a 5/16” lag screw is 229 lbs per inch of penetration as
identified in the National Design Standards (NDS) of timber construction specifications. Based on
two screws with a minimum penetration depth of 2-1/2”, the allowable capacity per connection is
greater than the design withdrawal force (demand). Considering the variable factors for the existing
roof framing and installation tolerances, the connection using two 5/16” diameter lag screws with a
minimum of 2-1/2” embedment will be adequate and will include a sufficient factor of safety.
3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of
the roof, the panel supports shall be placed no greater than 48” on center.
Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing
roof system will adequately support the additional loading imposed by the solar system. This evaluation is in
conformance with the 2022 California Building Code, current industry standards, and is based on information
supplied to us at the time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Very truly yours,
Scott E. Wyssling, PE
California License No. 83664
2307 N Towner St
8/23/2024
Wyssling Consulting
76 N. Meadowbrook Drive
Alpine, UT 84004
(201) 874-3483
swyssling@wysslingconsulting.com
Existing Vandervoort Residence
Roof Dead Load 2307 N Towner Street
9.0 psf Clay or Conc Tile Santa Ana, CA
1.6 psf 1/2" Plywood Sheathing
0.8 psf 2x4 Trusses @ 24 in. o.c.
1.0 psf Ceiling, Mechanical, Electrical
0.6 psf Miscellaneous
13.0 psf TOTAL
Second Floor Dead Load
0 psf Floor Finishes
0 psf 1 1/8" Subfloor Sheathing
0 psf Joists @ 16' o.c.
0 psf Partitions
0 psf Ceiling, Mechanical, Electrical
0 psf Miscellaneous
0 psf TOTAL
Roof Live Load Floor Live Load
20 psf 0 psf
Roof Snow Load
Ground SnowLoad=0 psf (to be divided by cosine of roof angle for horizontal projection ASCE 7 Sec. 7.4)
pf = 0.7 Ce Ct I pg =0 psf Ce = 1, Ct = 1.1 Flat Roof Snow Load (ASCE 7-16 Eq. 7.3-1)
Cs =0.91 ASCE 7-16 Figure 7.4-1
Additional
Roof Dead Load - New Solar Panels
3 psf
Roof Live Load at Solar Panels
0 psf
Roof Snow Load at Solar Panels
0 psf Sloped Roof Snow Load (ASCE 7-16 Eq. 7.4-1)
Total
Total Existing Roof Load = (DLROOF + Max(LLROOF or S)) AreaROOF
152130 lbs
Total New Roof Load = (DLROOF + DLADD + Max(LLROOF or S)) AreaROOF
145514 lbs
Change in Demand = (Total New Roof Load - Existing Roof Load) / Existing Roof Load
-4.35%
2021 IEBC Section 805.2 states:
"Any existing gravity load-carrying structural element for which an alteration causes an increase in design gravity load
of more than 5 percent shall be strengthened, supplemented, replaced or otherwise altered as needed to carry the
increased gravity load required by this code for new structures."
Gravity Loads
Total New Gravity Loads are less than Existing Loads. OK
Signed 7/01/2024
2307 N Towner St
8/23/2024
Wyssling Consulting
76 N. Meadowbrook Drive
Alpine, UT 84004
(201) 874-3483
swyssling@wysslingconsulting.com
V =95 Basic Wind Speed Vandervoort Residence
Exposure C ASCE 7-16, Section 26.7 2307 N Towner Street
Kz =0.85 Velocity Pressure Coefficient, ASCE 7-16, Figure 26.10-1 Santa Ana, CA
Kzt =1 Topographic Factor, ASCE 7-16, Section 26.8.2
Kd =0.85 Directionality Factor, ASCE 7-16, Section 26.6
Ke =0.995 Ground Elevation Factor, ASCE 7-16, Section 26.9
qh =16.6 psf qh = 0.00256KzKztKdKeV2 (ASCE 7-16 Eq. 26.10-1)
Roof Angle =20 deg
Roof Type Hip
sanchor =48 in Horizontal spacing of roof anchors
Atrib =12.33 sf Panel Area tributary to each roof anchor
GCp External Pressure Coefficient, ASCE 7-16, Figure 30.3-2
Roof Zone Zone 1 2e 2r Zone 3
-1.30 -1.79 -2.39 -1.79
ga =0.79 Pressure Equalization Factor, ASCE 7-16 Figure 29.4.-8
gE =1.00 Edge Array Factor, ASCE 29.4.4 edges < 0.5*building height, and panel spacing < 4ft.
pnet = qhGCpgEga =Design Wind Pressure, ASCE 7-16, Equation 29.4-7
Roof Zone 1 2e 2r Zone 3
-17 psf -24 psf -31 psf -24 psf Min Pressure = -16 psf
Use 17 psf Use 24 psf Use 31 psf Use 24 psf ULTIMATE
x 0.6 =16 psf 16 psf 19 psf 16 psf ALLOWABLE
Connection to Existing Roof Framing
F.S. =1 Additional Factor of Safety applied to withdrawl force, if desired
Atrib =12.3 ft2
DLpanel =3 psf
Roof Zone 1 2e 2r Zone 3
Wuplift =17 psf 24 psf 31 psf 24 psf
Plag = F.S. x Atrib x (0.6D - 0.6W) =Withdrawl force for each roof anchor
Roof Zone 1 2e 2r Zone 3
-107.0 lbs -154.7 lbs -212.5 lbs -154.7 lbs
Connection Capacity
db =5/16 in Lag Screw diameter
Dpen =2 1/2 in Lag Screw penetration into existing framing member
No. of Screws 2 Screws per Connection
Species of wood framing
CD =1.6 Load Duration Factor for Wind Loading, NDS Table 2.3.2
Ct =0.7 Temperature Factor, NDS Table 10.3.4
W =205 lb/in Withdrawl Capacity, NDS Equation 11.2-1
W' = CD x Ct x W =229 lb/in Adjusted withdrawl value
Pallow = Dpen x W' =1147 lbs (Using (2) screws per connection)
Roof Zone 1 2e 2r Zone 3
DEMAND =107 lbs 155 lbs 213 lbs 155 lbs
CAPACITY =1147 lbs 1147 lbs 1147 lbs 1147 lbs
up to72in ok up to72in ok up to72in ok up to72in ok
Spruce-Pine-Fir
Wind Uplift
Rooftop Solar Panels Parallel to Roof Surface
ASCE 7-16, Section 29.4.4
This analysis calculates the
capacity of the lag screws
only. For capacity of the
complete mounting system,
please see manufacturer's
recommendations.
Signed 7/01/2024
2307 N Towner St
8/23/2024
ROOF MOUNT CROSS SECTION DETAIL
NTS
ROOF FRAMING
SEE TABLE ON SHEET PV-3
PV MODULE
FINISHED ROOF
GROUND END/MID CLAMP
SHEATHING
RAIL
ECOFASTEN CLICKFIT UNIVERSAL TILE
HOOK ROOF MOUNT WITH (2) SCREWS
CONNECTED TO ROOF FRAMING
WATERPROOF BUTYL
(2) 5/16" x 4" LAG SCREWS PROVIDED
BY MANUFACTURER CONNECTED
INTO ROOF FRAMING
EMBEDMENT DEPTH SEE
TABLE ON SHEET PV-3
GENERAL ROOF MOUNT DETAIL
NTS ROOF MOUNT PLAN VIEW DETAIL
NTS
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
CALIFORNIA LICENSE NO. C83664
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
S-1
DATE:
SCOTT E. WYSSLING, P.E.
7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
STRUCTURAL
DETAILS
ECOFASTEN CLICKFIT UNIVERSAL TILE HOOK
FLASHING ROOF MOUNT SEE ROOF MOUNT CROSS
SECTION DETAIL THIS SHEET FOR CONNECTION TO
ROOF FRAMING
ROOF FRAM
I
N
G
SEE TABLE
O
N
S
H
E
E
T
P
V
-
3
FINISHED ROOF
ROOF SHEATHING
PV MODULE
RAIL
3" MIN - 6"
MAX SPACE
FROM ROOF
SURFACE ECOFASTEN CLICKFIT UNIVERSAL TILE
HOOK ROOF MOUNT WITH (2) SCREWS
CONNECTED TO ROOF FRAMING
(2) 5/16" x 4" LAG SCREWS
PROVIDED BY MANUFACTURER
CONNECTED INTO ROOF FRAMING
1.CONTRACTOR IS TO FOLLOW THE PLAN FOR INSTALLING
ROOF MOUNTS.
2.IF THE CONTRACTOR IDENTIFIES THE ROOF FRAMING IS
DIFFERENT FROM WHAT IS IDENTIFIED ON THIS PLAN,
CONTRACTOR SHALL NOTIFY THE ENGINEER BEFORE
PROCEEDING WITH INSTALLATION.
3.CONTRACTOR IS TO LOCATE THE ROOF FRAMING BY
UTILIZING A HAMMER.
4.WHEN THE ROOF FRAMING IS LOCATED, CONTRACTOR IS TO
DRILL A PILOT HOLE TO CONFIRM CENTER OF ROOF FRAMING.
IF THE ROOF FRAMING IS MISSED, AND A NEW PILOT HOLE IS
TO BE DRILLED, CONTRACTOR TO UTILIZE SILICON/CAULK TO
SEAL THE ORIGINAL PILOT HOLE.
5.DIRECT TO DECK MOUNTS ARE ONLY TO BE USED WITH
APPROVED DESIGN BY THE ENGINEER. DIRECT TO DECK
MOUNT INSTALLATION IS NOT A SUBSTITUTION FOR LAG
SCREWS INTO ROOF FRAMING.
6.CONTRACTOR TO FOLLOW MANUFACTURERS
SPECIFICATIONS FOR INSTALLATION AND REQUIRED SCREWS.
MOUNT INSTALLATION NOTES
Signed 7/26/2024
2307 N Towner St
8/23/2024
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
BRANCH CIRCUIT (1):
7 MODULES
(N) ENPHASE IQ COMBINER
X-IQ-AM1-240-4C
(N) 15A-2P
ENVOY
BREAKER
NEW
(2) 20A-2P
1
(N) NEMA 3
JUNCTION BOX
2
BRANCH CIRCUIT (2):
11 MODULES 1 L1
L2
N
G
G
N
ENPHASE IQ8PLUS-72-2-US
MICROINVERTER(S)
(N) NON-FUSED PV
AC DISCONNECT
VISIBLE, LOCKABLE,
LABELED, OPEN
30A, 240V, 2-POLE
3
G
(E) TESLA POWERWALL
AC II BATTERY
(N) 30A-2P
(E) 20A-2P
G
N
3
=
=
=
=
=
=
L1
L2
G AC
DC
EXISTING DC CONVERTER
L1
L2
N
G
(E) INVERTER
(E) DC DISCONNECT
(E) 20A-2P
=
=
=
=
=
=
L1
L2
G
(N) JUNCTION BOX
AC
DC
L1
L2
N
G
(E) INVERTER
(E) DC DISCONNECTEXISTING DC CONVERTER
(N) JUNCTION BOX
(N) 125A GENERATION PANEL
120/240V, 1-PHASE
EXISTING STRING(S)
EXISTING MODULE(S)
EXISTING STRING(S)
EXISTING MODULE(S)
(N) NON-FUSED
ESS DISCONNECT
VISIBLE, LOCKABLE,
LABELED, OPEN
30A, 240V, 2-POLE
(N) 30A-2P
(N) 100A-2P
(N) 175A-2P
(N) 100A-2P
(N) 225A MAIN SERVICE PANEL
(N) 175A / 2P MAIN BREAKER
(E) LOADS
SPD
(N) SURGE
PROTECTION
DEVICE TYPE 1
(N) 20A-2P
G
N
L2
L1
G
N
4
EXISTING GROUNDING
ELECTRODE SYSTEM
POINT OF INTERCONNECTION:
SINGLE BACKFED BREAKER
705.12 (B)(2)(3)(b)
(E) UTILITY METER
(2)#10 AWG PV-WIRE
(1) #6 AWG BARE CU EGC
(2)#10 AWG THWN-2
(1)#8 AWG BARE CU EGC
3/4'' EMT TYPE CONDUIT
(2)#10 AWG THWN-2
(1)#8 AWG BARE CU EGC
3/4'' EMT TYPE CONDUIT
(3) #10 AWG TWHN-2
(1) #8 AWG EGC/GEC
(3) #10 AWG TWHN-2
(1) #8 AWG EGC/GEC
SUPPLY
CONNECTIONS
MAIN LUGS OR
MAIN BREAKER
G
N
(E) TESLA BACKUP GATEWAY 2 200A, NEMA 3R, 120/240V
(E) 100A-2P
4
Existing Module:Trina Solar TSM-270PD05.08
Existing Inverter:PVI-3.8-OUTD-US INVERTER
Existing 2nd Inverter:PVI-3.8-OUTD-US INVERTER
Existing Module QTY:36
Existing Interconnection:LOAD SIDE BREAKER
Existing PV Breaker Amp:
Existing System Output:16 x 2= 32
Existing System size:9.72
PCS SETTING SET
TO 44A
CT's
CONDUCTOR SCHEDULE
CONDUCTORS GROUND CONDUIT
TAG ID WIRES IN CONDUIT WIRE AWG TYPE, MATERIAL AMPACITY SIZE TYPE, MATERIAL
1 3 #12 AWG Q CABLE 20 #6 AWG BARE, CU
2 5 #10 AWG THHN,CU 30 #8 AWG THHN,CU 3/4" CONDUIT
3 4 #10 AWG THHN,CU 30 #8 AWG THHN,CU 3/4" CONDUIT
4 4 #3 AWG THHN,CU 100 #8 AWG THHN,CU 1-1/4" CONDUIT
1. AC DISCONNECT SHALL BE VISIBLE-OPEN TYPE, LOCKABLE AND READILY ACCESSIBLE. TO BE WITHIN 10' OF THE UTILITY METER
2. 3/4" OR GREATER CONDUIT RUN (7/8" ABOVE ROOF SURFACE
3. GAS METER LOCATED IN PROXIMITY OF THE PV INSTALLATION, LOAD CENTER, AND/OR DISCONNECTS. DISCONNECTS SHALL BE
LOCATED IN COMPLIANCE WITH UTILITY AND THE AHJ (AUTHORITY HAVING JURISDICTION).
4. PER NEC REQUIREMENTS GROUNDING CONDUCTORS SMALLER THAN #6 AWG SHALL BE PROTECTED IN A CONDUIT, RACEWAY, OR
ARMORED PROTECTIVE SHEATHING (NEC 250.64).
5. THE WORKING CLEARANCES AROUND THE EXISTING ELECTRICAL EQUIPMENT AS WELL AS THE NEW ELECTRICAL EQUIPMENT WILL BE
MAINTAINED IN ACCORDANCE WITH NEC 110.26.
6. ANY CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT. (NEC 300.6 C1, 310.8 D).
7. ROOM FOR EQUIPMENT WITHIN 5 FEET FROM MSP.
GENERAL NOTES
INTEGRATED BONDING/ GROUNDING
CONDUCTOR NOTES
1. ALL TERMINATIONS AND CONDUCTORS RATED FOR
75°C MINIMUM. 110.14(C)(1)(a)(3).
INTERCONNECTION CALCULATIONS
BUS RATING
MAIN OCPD
ALLOWED PV PER NEC
AMPS
AMPS
AMPS
225A
175A
95A
ITEM UNIT PANEL
E-1
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
ELECTRICAL
DIAGRAM
EXISTING PV SYSTEM IS NOT RS COMPLIANT.
2307 N Towner St
8/23/2024
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
CONDUCTOR CALCULATIONS
MODULE
MANUFACTURER/ MODEL
HANWHA Q.CELL BLK
ML-G10+ 400
PMAX 400 W
VOC 45.3 V
VMP 37.13 V
IMP 10.77 A
ISC 11.14 A
TEMPERATURE COOEFFICIENT OF PMAX -0.034 %/°C
TEMPERATURE COEFFICIENT OF VOC -0.27 %/°C
INVERTER
MANUFACTURER/ MODEL ENPHASE IQ8PLUS-72-2-US
MAX AC OUTPUT 1.21 A
AC OUTPUT VOLTAGE 240 V
MAX DC INPUT VOLTAGE 60 V
MAX INPUT CURRENT 20 A
WEIGHTED CEC EFFICIENCY 97.00%
INVERTER WATTAGE 290 W
TAG 1 (SEE E-1)TAG 2 (SEE E-1)TAG 3 (SEE E-1)TAG 4 (SEE E-1)
UNDER MODULES, NOT IN CONDUIT #10 AWG MAX CURRENT = 30A #10 AWG MAX CURRENT = 30A #3 AWG MAX CURRENT = 100A
#12 AWG MAX CURRENT = 20A
ENPHASE IQ8PLUS-72-2-US MAX OUTPUT = 21.78A
8.47 A FOR CIRCUIT 1 8.47 A FOR CIRCUIT 1 21.78 * 1.25 (SAFETY FACTOR) = 27.225A 21.78 * 1.25 (SAFETY FACTOR) = 27.225A
13.31 A FOR CIRCUIT 2 13.31 A FOR CIRCUIT 2 RECOMMENDED OCPD = 30 TESLA POWERWALL OCPD = 30
EXISITING SYSTEM MAX OUTPUT= 32A
32*1.25(SAFETY FACTOR) = 40
TOTAL OUTPUT CURRENT = 27.225+30+40 = 97.225A
RECOMMENDED OCPD = 100
EQUIPMENT INFORMATION
E-2
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
EQUIPMENT
INFORMATION
2307 N Towner St
8/23/2024
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
THE EQUIPMENT FED BY MULTIPLE SOURCES.
TOTAL RATING OF ALL OVERCURRENT DEVICES,
EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE,
SHALL NOT EXCEED AMPACITY OF BUSBAR
RAPID SHUTDOWN
SWITCH FOR SOLAR PV
SECOND SOURCE IS PHTOVOLTAIC SYSTEM
MAXIMUM AC OPERATING CURRENT:
PHOTOVOLTAIC
WARNING: PHOTOVOLTAIC
POWER SOURCE
PHOTOVOLTAIC AC DISCONNECT
DUAL POWER SOURCE
NOMINAL OPERATING AC VOLTAGE:
DC DISCONNECT
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT
WARNING
ELECTRICAL SHOCK HAZARD
DO NO TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
WARNING!
INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE
WARNING!
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
!
WARNING!
77.78
240
PHOTOVOLTAIC
AC DISCONNECT
!!
LABELING NOTES:
1.LABELING REQUIREMENTS BASED ON THE 2022 CALIFORNIA ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535.
2.MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
3.LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [CEC 110.21]
4.LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC
605.11.1.1]
AT POINT OF INTERCONNECTION,
MARKED AT DISCONNECTING MEANS
[CEC 690.54]
AT POINT OF INTERCONNECTION.
[CEC 705.12(C), 690.59]
EACH PV SYSTEM DISCONNECTING MEANS
SHALL PLAINLY INDICATE WHETHER IN THE
OPEN (OFF) OR CLOSED (ON) POSITION AND
BE PERMANENTLY MARKED [CEC. 690.13(B)]
AT EACH DC DISCONNECTING MEANS
[CEC 690.13(B)]
AT EACH AC DISCONNECTING
MEANS [CEC 690.13(B)]
AT EXPOSED RACEWAYS, CABLE TRAYS,
AND OTHER WIRING METHODS; SPACED
AT MAXIMUM 10FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS,
PARTITIONS, CEILINGS, OR FLOORS
[CEC 690.31(D)(2)]
AT BUILDING OR STRUCTURE MAIN
DISCONNECTING MEANS. [CEC 690.12(E),
CEC 690.13(B)]
A RAPID SHUTDOWN SWITCH SHALL
HAVE A LABEL LOCATED ON OR NO MORE
THAN 3 FT FROM THE SWITCH THAT
INCLUDES THIS WORDING. THE LABEL
SHALL BE REFLECTIVE, WITH ALL
LETTERS CAPITALIZED AND HAVING A
MINIMUM HEIGHT OF 3/8 IN., IN WHITE ON
RED BACKGROUND.[CEC 690.56(C)(2)]
FOR PV SYSTEMS THAT SHUT DOWN THE
ARRAY AND CONDUCTORS LEAVING THE
ARRAY: THE TITLE “SOLAR PV SYSTEM IS
EQUIPPED WITH RAPID SHUTDOWN”
SHALL UTILIZE CAPITALIZED
CHARACTERS WITH A MINIMUM HEIGHT
OF 3/8 IN. IN BLACK ON YELLOW
BACKGROUND, AND THE REMAINING
CHARACTERS SHALL BE CAPITALIZED
WITH A MINIMUM HEIGHT OF 3/16 IN. IN
BLACK ON WHITE BACKGROUND. [CEC
690.56(C)(1)(A)]
A PERMANENT WARNING LABEL SHALL BE
APPLIED TO THE DISTRIBUTION
EQUIPMENT ADJACENT TO THE
BACK-FED BREAKER FROM THE
INVERTER.
[CEC 705.12(B)(3)(2)]
PERMANENT WARNING LABELS SHALL BE
APPLIED TO DISTRIBUTION EQUIPMENT
E-3
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
PV LABELS
PLACE LABEL AT MAIN SERVICE PANELCAUTION: DO NOT INSTALL
ADDITIONAL LOADS IN THIS PANEL
PLACE LABEL AT MAIN SERVICE PANEL
THIS EQUIPMENT FED BY MULTIPLE
SOURCES. TOTAL RATING OF ALL
OVERCURRENT DEVICES, EXCLUDING
MAIN SUPPLY OVERCURRENT
DEVICE, SHALL NOT EXCEED
AMPACITY OF BUSBAR.
WARNING
PHOTOVOLTAIC SYSTEM
COMBINER PANEL
WARNING
DO NOT ADD LOADS
CAUTION AT EXTERNAL LOCATION NEAR METER
AND UTILITY SERVICE DISCONNECT
TRI POWER SOURCE
SECOND SOURCE IS
BATTERY THIRD SOURCE IS
PHOTOVOLTAIC SYSTEM
PLACE LABEL EXTERNAL AT MAIN
SERVICE DISCONNECTENERGY STORAGE SYSTEM
ON SITE LOCATED OUTSIDE
PLACE ESS LABELS AT BATTERY AND/OR
CONTROLLERWARNING
ELECTRIC SHOCK IF A
GROUND FAULT IS
INDICATED, NORMALLY
GROUNDED CONDUCTORS
MAY BE UNGROUNDED AND
ENERGIZED
AT AC COMBINER PANEL. NEC 690.13(B)
ON THE DEAD FRONT BELOW THE TRANSPARENT
BREAKER, POSITION THE COVER FOR THE MAINS
BREAKER.
THE MAXIMUM CURRENT BACKFED BY THIS SYSTEM TO THE MAIN
PANEL MAY BE CONTROLLED ELECTRONICALLY. REFER TO THE
MANUFACTURER'S INSTRUCTIONS FOR MORE INFORMATION.
PC CONTROLLED CURRENT SETTINGS:AMPS44
2307 N Towner St
8/23/2024
UM
MS
P
BG
GE
N
IN
V
IN
V
CO
M
AC
B
NO
R
T
H
T
O
W
N
E
R
S
T
R
E
E
T
JB
JBJB
AC
EW
S
N
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
2307 NORTH TOWNER STREET, SANTA ANA, CALIFORNIA 92706
CAUTION:
LABEL LOCATION: MSP CODE REF: CEC 2022 - 705.10
POWER TO THIS BUILDING IS
ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH
DISCONNECTS AS SHOWN
FR
O
N
T
O
F
H
O
M
E
RSS EQUIPPED SOLAR
ARRAY ON ROOFTOP
AC COMBINER PANEL
AC DISCONNECT
MAIN SERVICE PANEL
UTILITY METER
YOU ARE HERE
INVERTER WITH
DC DISCONNECT
E-4
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
PLACARD
GENERATION PANEL
BACKUP GATEWAY
ESS DISCONNECTBATTERY(EXTERIOR)
EXISTING PV SYSTEM IS NOT RS COMPLIANT.
2307 N Towner St
8/23/2024
TESLA BACKUP
GATEWAY 2125A GENERATION PANEL
TESLA POWERWALL 2 ABB PVI-3.8-OUTD-US INVERTER ABB PVI-3.8-OUTD-US INVERTER
ENPHASE I COMBINER
X-I-AM1-240-4C
30A
ESS DISCONNECT
30A
AC DISCONNECT
TO GENERATION PANEL
FROM ESS
DISCONNECT
METER MAIN
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
ÀPN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
1.EUIPMENT SHALL BE A MINIMUM OF 3À X 3À
ACCESSIBLE WORKSPACE, FLAT, AND CLEAR OF
DEBRIS AND OBSTACLES (TREES, BUSHES,
PLANTS, ETC.)
2.BATTERIES TO BE SEPARATED BY A MINIMUM 3À
BETWEEN EACH UNIT PER UL 9540A REPORT
NOTES
E-5
DATE:8/9/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
ELEVATION
DETAIL
SOUTH EXTERIOR ELEVATION DETAIL
SCALE: NTS
2307 N Towner St
8/23/2024
UM
MS
P
BG
GE
N
IN
V
IN
V
CO
M
AC
B
JB
JBJB
AC
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
PV-6
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
INSTALL
CHECKLIST
2307 N Towner St
8/23/2024
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-1
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
MODULE
SPEC SHEET
2307 N Towner St
8/23/2024
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-2
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
INVERTER
SPEC SHEET
2307 N Towner St
8/23/2024
UM
MS
P
BG
GE
N
IN
V
IN
V
CO
M
AC
AC
B
NO
R
T
H
T
O
W
N
E
R
S
T
R
E
E
T
JB
JBJB
EW
S
N
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
2307 NORTH TOWNER STREET, SANTA ANA, CALIFORNIA 92706
CAUTION:
LABEL LOCATION: MSP CODE REF: CEC 2022 - 705.10
POWER TO THIS BUILDING IS
ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH
DISCONNECTS AS SHOWN
FR
O
N
T
O
F
H
O
M
E
RSS EQUIPPED SOLAR
ARRAY ON ROOFTOP
AC COMBINER PANEL
AC DISCONNECT
MAIN SERVICE PANEL
UTILITY METER
YOU ARE HERE
INVERTER WITH
DC DISCONNECT
E-4
DATE:
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
PLACARD
GENERATION PANEL
BACKUP GATEWAY
ESS DISCONNECT
BATTERY (EXTERIOR)
Existing PV system is NOT RS compliant.
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
APN/PARCEL NO: 00121406
7/01/2024
2307 N Towner St
8/23/2024
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
PV-5
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
SITE PHOTOS
2307 N Towner St
8/23/2024
B
B
BB
AC UM MSPBI GENINVINVCOM
AC
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
ÀPN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
PV-6
DATE:8/9/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
INSTALL
CHECKLIST
2307 N Towner St
8/23/2024
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-1
DATE:
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
MODULE
SPEC SHEET
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
APN/PARCEL NO: 00121406
7/01/2024
2307 N Towner St
8/23/2024
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-2
DATE:
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
INVERTER
SPEC SHEET
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
APN/PARCEL NO: 00121406
7/01/2024
2307 N Towner St
8/23/2024
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-3
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
COMBINER PANEL
SPEC SHEET
2307 N Towner St
8/23/2024
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-4
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
RAIL SPEC
SHEET
2307 N Towner St
8/23/2024
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-4
DATE:
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
RAIL SPEC
SHEET-1
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
APN/PARCEL NO: 00121406
7/01/2024
2307 N Towner St
8/23/2024
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-5
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
MOUNTING
SPEC SHEET
2307 N Towner St
8/23/2024
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-6
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
GROUNDING
SPEC
2307 N Towner St
8/23/2024
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-7
DATE:
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
BATTERY
SPEC SHEET
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
APN/PARCEL NO: 00121406
7/01/2024
2307 N Towner St
8/23/2024
VANDERVOORT, DAVID
2307 NORTH TOWNER STREET
SANTA ANA, CA 92706
PN/PARCEL NO: 00121406
EXO ENERGY
1358 LA MIRADA DRIVE
SAN MARCOS, CA 92071
(208) 351-4153
MICHAEL ESPINOZA
CSLB: 1063308
SPECS-7
DATE:7/26/2024
swyssling@wysslingconsulting.com
(201) 874-3483
DESIGN ENGINEER
SOLAR COMPANY/CLIENT
76 N. MEADOWBROOK DRIVE
ALPINE, UTAH 84004
BATTERY
SPEC SHEET
2307 N Towner St
8/23/2024
PCC-13 Rev. 06-17-2019 White-Plan Check Yellow-Applicant
REVISION /SUPPLEMENTAL
PLAN CHECK REQUEST
PCC-13 CBC 2022 Rev 6-09-2023
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
Project Address: _________________________________________ Suite #_______________________________
New Plan Check No.____________________________________________________________________________
Original Plan Check No.:__________________________________ Permit Issuance Date:____________________
Original Plan Checker: __________________________________________________________________________
Amount Paid: $__________________________________________ Misc. Receipt #: ________________________
Processed by: ___________________________________________ Date: ________________________________
Plan Checker Approval: ___________________________________ Date: ________________________________
Additional Hours:________________________________________ @ $257.88 = $ _________________________
Print Name:_____________________________________________ Signature: ____________________________
Representing: ________________________________________________________________________________
Telephone: ( ) ____________________________________ Fax: ( ) __________________________________
Contact Person: ________________________________________ Telephone: ( ) ________________________
E-mail (Strongly Recommended): _________________________________________________________________
PLANS PREPARED BY AN ARCHITECT OR ENGINEER MUST BE SIGNED BY THE PROFESSIONAL WHO PREPARES THEM.
PLEASE WRITE A BRIEF DESCRIPTION OF THE REVISION/SUPPLEMENT AND IF POSSIBLE AREA OF WORK.
ALL REVISIONS ARE TO BE CLOUDED AND PROPERLY IDENTIFIED: (i.e. Deltas,Sheet Numbers, etc.).
Electrical, Plumbing and/or Mechanical plans – stamped job set shall accompany revised plans.
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
2307 N Towner Street, Santa Ana, CA
Scott E. Wyssling
201 874-3483
Wyssling Consulting
swyssling@wysslingconsulting.com
1. Battery has been relocated for Clearances purposes see PV2, PV3, PV4, and E4.
2. 30A disconnect for the battery has been added see PV1, PV2, PV3, PV4, E1, and E4.
3. 100A main breaker added to the new 125A sub panel. See E1.
4. Structural stamps/calcs are provided.
2307 N Towner St
8/23/2024