HomeMy WebLinkAbout2701 S Poplar St - PlanPAGE
REV: C1 1/14/2025
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N) NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-3.0 LAYOUT
PV-3.1 LAYOUT
PV-3.2 MOUNTING DETAIL
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL
PV-4.2 ELECTRICAL CALCS
PV-4.3 BACKUPLOAD CALCS
PV-4.4 PANEL SCHEDULE
PV-5.0 SIGNAGE
PV-5.1 SIGNAGE
LTD: LR5-54HABB-395M
TESLA: POWERWALL 3 1707000-XX-Y
FOOT TO FRAMING, SNR-DC-00339
1707000-XX-Y WITH INTERGRATED INVERTER: 13.5 kWh
TOTAL ENERGY CAPACITY (IN kWh): 27kWH
EQUIPMENT INSTALLED, SEE PV-4.0 FOR INTERCONNECTION
DETAILS
EXISITNG SOLAR SYSTEM INSTALLED
BACKUP GATEWAY: (1) 200A TESLA POWERWALL CONTROL
PANEL
CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS.
SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A).
MODULES, ARE CLASS A FIRE RATED.
CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30
SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE
ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
Bldg #101122234
Elect #20184913
APPROVALS:
ELECT - CSG
***The scope of the plans is for the installation of the solar photovoltaic
system only and the approval is subject to compliance with all
applicable city and state codes and regulations regarding construction.
The approval of the plans does not constitute any certification of the
accuracy, completeness, or building permit status of the existing
buildings and structures as shown.***
2701 S Poplar St
3/10/2025
/ce/
PAGE
REV: B1 12/10/2024
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
PL PL PL
PL
PLPLPL
PL
SITE PLAN
PV-2.0
#SSTAMPSP
#ESTAMPSP
(E) DETACHED
STRUCTURE
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS
IN ACCORDANCE WITH R328.4. ESS UNITS SHALL BE
SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET
EXCEPT WHERE SMALLER SEPARATION DISTANCES ARE
DOCUMENTED TO BE ADEQUATE BASED ON LARGE/SCALE
FIRE TESTING.
ARRAY
PITCH
PV AREA
(SQFT)
AR-01 17° 63.1
AR-02 17° 84.1
AR-03 17° 252.3270° 258°
90°
TRUE
AZIM
MAG
AZIM
168°180°
78°
SITE PLAN - SCALE = 3/64" = 1'-0"
(E) RESIDENCE (N) ARRAY AR-01
(N) ARRAY AR-02
(N) ARRAY AR-03
FIRE SETBACKS
(18" TYP)
ROOF PATHWAYS
(3' TYP)
SE
MP
GP
(E) PV ARRAY(TYP)
(E) PV EQUIPMENT
S
P
O
P
L
A
R
S
T
(E) FENCE
(E) GATE(TYP)
(E) CHIMNEY
RSD INVAC
MD
POWERWALL ENERGY
STORAGE SYSTEM (ESS)
BG BACKUP GATEWAY
GP GENERATION PANEL
ELECTRIC VEHICLE
SUPPLY EQUPMENTEV
MAIN PANEL
INVERTER(S)
AC DISCONNECT(S)
DC DISCONNECT(S)
SUNRUN METER
DEDICATED PV METER
SERVICE ENTRANCE
INTERIOR EQUIPMENT
SHOWN AS DASHED
SE
MP
SM
PM
INV
AC
DC
SUB-PANELSP
CB IQ COMBINER BOX
METER ADAPTERMA
GROUNDING
ELECTRODE
ENERGY STORAGE
SYSTEM
BP BACKUP LOADS PANEL
BI BACKUP INTERFACE 1 COMMUNICATION
WIRESAM
MD MICROGRID
INTERCONNECT DEVICE
ACREL METER
SOLAREDGE METERSEMPV LOAD CENTERLC
LEGEND
SCALE: NTS
NOTE: NOT ALL ITEMS IN LEGEND
WILL APPEAR IN SITE PLAN
RAIL
STANDOFFS &
FOOTINGS
SOLAR
MODULES
RSD EXTERNAL RAPID
SHUTDOWN SWITCH
AC AC
INVINV
ROOF PATHWAYS
(3' TYP)
"NOTE: ROOFTOP MODULE LEVEL RAPID
SHUTDOWN DEVICE INSTALLED PER CEC
690.12"
NOTES:
RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
TOTAL ROOF SURFACE AREA: 2606 SQFT.
TOTAL PV ARRAY AREA(E+N): 651.5 SQ FT.
PERCENTAGE PV COVERAGE:
(TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
AREA) * 100 (E+N)= 25%
A
A
A
A
A
A
A
A
AA
A
A
B
B
B
B
C C C
Exp. 12/31/2026Digitally Signed On: 12/31/24
2701 S Poplar St
3/10/2025
/ce/
PAGE
REV: B1 12/10/2024
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
#SSTAMP
UR-40 RAIL | UR-60 RAIL
FOR USE WITH SNAPNRACK ULTRA SERIES RAILS
PENETRATION DETAIL
INSTALLED SECTION VIEW
DESCRIPTION:DRAWING NUMBER:SCALE:DESIGNER:
APPROVED BY:
REVISION:
Sunrun South LLC
595 MARKET STREET, 29TH FLOOR ● SAN FRANCISCO, CA 94105 USA
PHONE (415) 580-6900 ● FAX (415) 580-6902
THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY
REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE
WRITTEN CONSENT OF SUNRUN SOUTH LLC.
ULTRA RAIL, ATTACHMENT DETAIL, UMBRELLA
L FOOT TO RAFTERSNR-DC-00339
1 5 7 2019 NEW DETAIL
1 6 18 2019 DRO-00138
B 6 22 2023 DC002707
REV:
ADATE:
DNS
6 22 2023
DRAFTER: M.AFFENTRANGER
E.FERGUSON
M.AFFENTRANGER
Solar Mounting Solutions
MJA
MJA
MJA
BIN:
8
214"
112"
112"
158"
SNAPNRACK ULTRA RAIL UMBRELLA L FOOT WITH UMBRELLA FLASHING
FOR COMPOSTION ROOF MOUNTING
REFER TO SNAPNRACK ENGINEERING CHARTS FOR APPLICABLE RAIL
SPANS. "BIN" NUMBER ON CHART SHOULD MATCH "BIN" NUMBER ON
THIS DRAWING
516"Ø S.S. UMBRELLA LAG SCREW MUST EMBED A MIN. OF 212" INTO
STRUCTURAL MEMBER TO UTILIZE STANDARD SNAPNRACK ENGINEERING.
REACH OUT TO SNAPNRACK IF THIS IS NOT POSSIBLE
REFER TO SNAPNRACK INSTALLATION MANUAL FOR516"Ø HARDWARE
TORQUE SPECIFICATIONS
RAIL CAN BE MOUNTED ON EITHER SIDE OF THE L-FOOT
FOR LEVELING DETAILS, REFER TO SNAPNRACK
DETAIL DRAWING "SNR-DC-00447"
STRUCUTRAL MEMBER,
WOOD RAFTER, TYP.
ROOF DECKING, TYP.
SNAPNRACK5 16"n UMBRELLA
LAG SCREW, S.S.
COMP SHINGLE ROOFING, TYP.
SNAPNRACK
ULTRA RAIL
SNAPNRACK UMBRELLA FLASHING
212" MIN. EMBEDMENT
INTO WOOD MEMBER
MODULE HEIGHT OFF ROOF:
UR-40: 338" - 438"
UR-60: 4" - 5"
SNAPNRACK ULTRA RAIL
UMBRELLA L FOOT
STRUCUTRAL MEMBER,
WOOD RAFTER, TYP.
ROOF DECKING, TYP.
COMP SHINGLE ROOFING, TYP.
SNAPNRACK ULTRA RAIL
UMBRELLA L FOOT WITH
UMBRELLA LAG AND FLASHING
SNAPNRACK
UMBRELLA FLASHING
MOUNTING DETAIL
PV-3.2
Exp. 12/31/2026Digitally Signed On: 12/31/24
2701 S Poplar St
3/10/2025
/ce/
PAGE
REV: B1 12/10/2024
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
#SSTAMP
DESIGN CRITERIA
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED:
96 MPH 3-SEC GUST.
FASTENERS:
(1) 5/16" DIA S.S. UMBRELLA
SCREW: 2.5" MIN EMBEDMENT
INTO FRAMING
PV-3.0
LAYOUT
4"
SOLAR MODULE
SNAPNRACK
RACKING
MODULE ELEVATION DETAIL - SCALE: NTS
INSTALLERS SHALL NOTIFY ENGINEER OF ANY
POTENTIAL STRUCTURAL ISSUES OBSERVED
PRIOR TO PROCEEDING W/ INSTALLATION.
* IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12"
BOUNDARY REGION OF ANY ROOF PLANE
EDGES (EXCEPT VALLEYS), THEN
ATTACHMENTS NEED TO BE ADDED AND
OVERHANG REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS FOLLOWS:
** ALLOWABLE ATTACHMENT SPACING
INDICATED ON PLANS TO BE REDUCED BY 50%.
** ALLOWABLE OVERHANG INDICATED ON
PLANS TO BE 1/5TH OF ALLOWABLE
ATTACHMENT SPACING INDICATED ON PLANS.
D1 - AR-01 - SCALE: 1/8" = 1'-0"
AZIM: 180°
PITCH: 17°
D2 - AR-02 - SCALE: 1/8" = 1'-0"
AZIM: 90°
PITCH: 17°
ROOF INFO ATTACHMENT INFORMATION
Name Type Height Detail Max Landscape
OC Spacing
Max Landscape
Overhang
Max Portrait
OC Spacing
Max Portrait
Overhang Configuration
AR-01 COMP SHINGLE - UR - UMBRELLA L
FOOT 1-Story ULTRA RAIL, ATTACHMENT DETAIL, UMBRELLA L FOOT TO FRAMING,
SNR-DC-00339 6'-0" 2'-4" 6'-0" 2'-3" STAGGERED
AR-02 COMP SHINGLE - UR - UMBRELLA L
FOOT 1-Story ULTRA RAIL, ATTACHMENT DETAIL, UMBRELLA L FOOT TO FRAMING, SNR-DC-00339 6'-0" 2'-4" 6'-0" 2'-3" STAGGERED
5'-8"
3'-5"
8'-2"
3'-9"
11"
13'-11"
37'-4"17'-1"5'-7"
16'-6"7'-6"6'7'-6"15'-3"
EXISTING STRUCTURE IS ASSUMED TO BE A LIGHT-FRAME WOOD
ROOF AND FREE FROM DAMAGE, DETERIORATION, OR
MODIFICATION THAT WOULD COMPROMISE ITS ORIGINAL DESIGN
INTEGRITY. CONTACT ENGINEER OF RECORD IF FOLLOWING
MINIMUM REQUIREMENTS ARE NOT SATISFIED IN COMPLIANCE
WITH THE STATED RACKING DESIGN:
Exp. 12/31/2026Digitally Signed On: 12/31/24
2701 S Poplar St
3/10/2025
/ce/
PAGE
REV: B1 12/10/2024
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
#SSTAMP
DESIGN CRITERIA
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED:
96 MPH 3-SEC GUST.
FASTENERS:
(1) 5/16" DIA S.S. UMBRELLA
SCREW: 2.5" MIN EMBEDMENT
INTO FRAMING
4"
SOLAR MODULE
SNAPNRACK
RACKING
MODULE ELEVATION DETAIL - SCALE: NTS
INSTALLERS SHALL NOTIFY ENGINEER OF ANY
POTENTIAL STRUCTURAL ISSUES OBSERVED
PRIOR TO PROCEEDING W/ INSTALLATION.
* IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12"
BOUNDARY REGION OF ANY ROOF PLANE
EDGES (EXCEPT VALLEYS), THEN
ATTACHMENTS NEED TO BE ADDED AND
OVERHANG REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS FOLLOWS:
** ALLOWABLE ATTACHMENT SPACING
INDICATED ON PLANS TO BE REDUCED BY 50%.
** ALLOWABLE OVERHANG INDICATED ON
PLANS TO BE 1/5TH OF ALLOWABLE
ATTACHMENT SPACING INDICATED ON PLANS.
ROOF INFO ATTACHMENT INFORMATION
Name Type Height Detail Max Landscape
OC Spacing
Max Landscape
Overhang
Max Portrait
OC Spacing
Max Portrait
Overhang Configuration
AR-03 COMP SHINGLE - UR - UMBRELLA L
FOOT 1-Story ULTRA RAIL, ATTACHMENT DETAIL, UMBRELLA L FOOT TO FRAMING, SNR-DC-00339 6'-0" 2'-4" 6'-0" 2'-3" STAGGERED
D3 - AR-03 - SCALE:1/8"=1'-0"
AZIM: 270°
PITCH: 17°
18'-10"
15'-2"
13'-7"8'-11"
1'-7"
1'-6"
PV-3.1
LAYOUT
EXISTING STRUCTURE IS ASSUMED TO BE A LIGHT-FRAME WOOD
ROOF AND FREE FROM DAMAGE, DETERIORATION, OR
MODIFICATION THAT WOULD COMPROMISE ITS ORIGINAL DESIGN
INTEGRITY. CONTACT ENGINEER OF RECORD IF FOLLOWING
MINIMUM REQUIREMENTS ARE NOT SATISFIED IN COMPLIANCE
WITH THE STATED RACKING DESIGN:
Exp. 12/31/2026Digitally Signed On: 12/31/24
2701 S Poplar St
3/10/2025
EXISTING 100A
MAIN BREAKER
END FED
EXISTING 100A
MAIN PANEL
100A BUS
M
100A
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A , 2P
120/240VAC
3
TRL
M
NEW 200A
BACKUP GATEWAY3
1841000-X1-Y
4
NEW 225 A
GENERATION PANEL & BACKUP
LOAD PANEL
(N)(1) 60A PV +ESS BREAKER
(E)20A PV BREAKER
4
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT,
POWER CONTROL
SYSTEM
3
J-BOX
LONGI GREEN ENERGY TECHNOLOGY CO LTD
LR5-54HABB-395M
STRING 1 OF 12 MODULES
4 MODULE LEVEL
RAPID SHUTDOWN DEVICES
12
POINT OF INTERCONNECTION:CEC 705.13 GATEWAY
BREAKER AT OPPOSITE END OF BUSBAR
METER NUMBER: 222013-515499
EQUIPMENT CHARACTERISTICS
INCLUDED IN SPEC SHEETS
NOTE: TOTAL PV BACKFEED(E+N)
= 80A USED FOR INTERCONNECTION CALCULATIONS
Existing Inverter(s)E
ABB: PVI-3.0-OUTD-S-US-A (240 V)
J-BOX
14 Kyocera Solar: KU265-6ZPA
EE
E
E
(E)
AC DISCONNECT
KNIFE DISCONNECT
E
FACILITY
GROUND
5
(N) TESLA REMOTE METER
SOLAR CURRENT
TRANSFORMERS
1 LONGI GREEN ENERGY TECHNOLOGY CO LTD
LR5-54HABB-395M
STRING 1 OF 4 MODULES
2 MODULE LEVEL
RAPID SHUTDOWN DEVICES
UL 9540
FACTORY
WIRING
ASSEMBLY
(1) TESLA
POWERWALL 3
EXPANSION PACK
1807000-xx-y
1 LONGI GREEN ENERGY TECHNOLOGY CO LTD
LR5-54HABB-395M
STRING 2 OF 3 MODULES
1 MODULE LEVEL
RAPID SHUTDOWN DEVICES
PAGE
REV: D 2/27/2025
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
PV-4.0
ELECTRICAL
#ESTAMP
POWER CONTROL SYSTEM (PCS):
SOURCES OF SUPPLY DOES NOT EXCEED THE RATING OF ANY BUSBAR OR CONDUCTOR
SUPPLIED BY THE POWER PRODUCTION SOURCES
MONITORED BY THE PCS SHALL COMPLY WITH ARTICLE 705.12.
WITH 240.6(C).
SETPOINTS:
- 80A - MAXIMUM TOTAL CURRENT ON THE CONTROLLED PANEL
- 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY (120% COMPLIANT)D
2701 S Poplar St
3/10/2025
CONDUIT SCHEDULE
TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT
1 Inverter Input (2) 10 AWG (PV WIRE)N/A 6 AWG (BARE)Open Air
2 Inverter Input (6) 10 AWG
THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4 EMT
3 Inverter Output (2) 6 AWG
THHN/THWN-2
(1) 6 AWG
THHN/THWN-2 8 AWG THHN/THWN-2 3/4 EMT
4 Gateway Output (2) 3 AWG
THHN/THWN-2
(1) 3 AWG
THHN/THWN-2 8 AWG THHN/THWN-2 1 EMT
5 Backup Loads
(13) 12AWG
THHN/THWN-2
(13) 12AWG
THHN/THWN-2 8 AWG THHN/THWN-2
1-1/4 EMT
(2) 10AWG
THHN/THWN-2
(1) 10AWG
THHN/THWN-2 8 AWG THHN/THWN-2
E EXISTING
PAGE
REV: D 2/27/2025
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
#ESTAMP
POWER CONTROL SYSTEM (PCS):
SOURCES OF SUPPLY DOES NOT EXCEED THE RATING OF ANY BUSBAR OR CONDUCTOR
SUPPLIED BY THE POWER PRODUCTION SOURCES
MONITORED BY THE PCS SHALL COMPLY WITH ARTICLE 705.12.
WITH 240.6(C).
SETPOINTS:
- 80A - MAXIMUM TOTAL CURRENT ON THE CONTROLLED PANEL
- 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY (120% COMPLIANT)
INSTALLER MUST CHECK THE CONDITION,
INSTALLABILITY AND CODE COMPLIANCE OF
EXISTING EQUIPMENT.
CITY REQUIRES TWO SOURCES OF GROUND - UFER, TWO GROUNDS RODS OR COLD WATER GAS BOND
INSTALL THE BACKED UP LOAD CONDUCTORS AND THE GATEWAY BREAKER CONDUCTORS IN
TWO SEPARATE CONDUITS
ANY MULTIWIRE BRANCH CIRCUITS RELOCATED ARE TO BE IDENTIFIED, GROUPED, AND EQUIPPED
WITH A 2-POLE OCPD BREAKER PER CEC 210.4(B,D).
IF THE RELOCATED LOADS EXTEND MORE THAN 6 FEET, AFCI PROTECTION APPLIES PER 2019 CEC 210.12
PV-4.1
ELECTRICAL
CONTI
GENERAL NOTES:
COLD WATER GAS BOND
D
D
2701 S Poplar St
3/10/2025
PAGE
REV: B1 12/10/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
SYSTEM INFORMATION
7.505 KW DC PHOTOVOLTAIC SYSTEM
(12) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M, TESLA:
POWERWALL 3 1707000-XX-Y
(7) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M, TESLA:
POWERWALL 3 1707000-XX-Y
SYSTEM OCPD SIZE
(COMBINED MAX CURRENT) X (CONTINUOUS LOAD) =
112 A X 1.25 = 140 A → 70 A OVERCURRENT PROTECTION
GATEWAY SYSTEM AC WIRE SIZING
MAX AC OUTPUT CURRENT = 70 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)(1)] X (CONDUIT
FILL)[TABLE 310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 95A = 86.45A
TERMINAL RATING[110.14(C)] =
4 AWG, 75°C RATED = 85A
85A < 86.45A TERMINAL RATING GOVERNS CONDUCTOR SIZING
70A < 85A 4 AWG AMPACITY OK
THEREFORE 4 AWG IS SUFFICIENT.
ALLOWABLE BACKFEED
MAX ALLOWED TOTAL GENERATION BACKFEED OCPD = MAIN BREAKER RATING =
100A
70A ≤ 100A→ INTERCONNECTION MEETS CEC 705.13 REQUIREMENTS.
INVERTER INFORMATION
4740 KW DC PHOTOVOLTAIC SYSTEM
(12) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M, TESLA:
POWERWALL 3 1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS
LOAD)[690.8(B)(1)]=
14.88A X 1.25 X 1.25 = 23.25A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT
FILL)[TABLE 310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
23.25A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)]
=
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT
FILL)[TABLE 310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG, 75°C RATED = 65A
65A < 68.25A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A → 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT.
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC
TEMP] + VOC} X (# MODULES / STRING) =
{[(-0.26 %/°C X 36.81 V) / 100] X [-2 °C - 25 °C] + 36.81 V} X 12 = 472.72 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 14.88 A X 1 = 18.6A
INVERTER INFORMATION
2765 KW DC PHOTOVOLTAIC SYSTEM
(7) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M, TESLA:
POWERWALL 3 1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS
LOAD)[690.8(B)(1)]=
14.88A X 1.25 X 1.25 = 23.25A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT
FILL)[TABLE 310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
23.25A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)]
=
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT
FILL)[TABLE 310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG, 75°C RATED = 65A
65A < 68.25A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A → 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT.
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC
TEMP] + VOC} X (# MODULES / STRING) =
{[(-0.26 %/°C X 36.81 V) / 100] X [-2 °C - 25 °C] + 36.81 V} X 4 = 157.57 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 14.88 A X 1 = 18.6A PV-4.2
ELECTRICAL CALCS
2701 S Poplar St
3/10/2025
BACKUP LOADS
LOAD BREAKER RATING
(AMPS)LABEL DEMAND
LOAD
1 15A-1P LIGHTING/ RECEPTACLE 1500 W
2 15A-1P LIGHTING/ RECEPTACLE 1500 W
3 20A-1P LIVING ROOM 1500 W
4 20A-1P M BED OUT 1500 W
5 20A-1P LIGHTING/ RECEPTACLE 1500 W
6 20A-1P LIGHTING/ RECEPTACLE 1500 W
7 20A-1P LIGHTING/ RECEPTACLE 1500 W
8 20A-1P LIGHTING/ RECEPTACLE 1500 W
9 20A-1P LIGHTING/ RECEPTACLE 1500 W
10 20A-1P LIGHTING/ RECEPTACLE 1500 W
11 20A-1P LIGHTING/ RECEPTACLE 1500 W
12 20A-1P LIGHTING/ RECEPTACLE 1500 W
13 20A-1P LIGHTING/ RECEPTACLE 1500 W
14 30A-2P AC 4464 W
PAGE
REV: B1 12/10/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
BACKUP LOAD CALCS
ALL BACKED UP LOADS ABOVE IN THE BACKED UP LOADS PANEL ARE RELOCATED FROM THE MAIN SERVICE
PANEL.
BACKED UP LOADS CALCULATION:
(4464 VA)/ 240V = 18.6 A PER CEC 2022 ARTICLE 690.10 OR NEC 2020 ARTICLE 710.15.
THE MAXIMUM CURRENT FOR ALL LARGE APPLIANCES LOADS IS 18.6A.
(MAX LOADS OUTPUT) X (CONTINUOUS LOADS) =
18.6 A X 1.25 = 23.25A
BACKED UP LOADS PANEL BREAKER = 70A
23.25 A < 70A.
THEREFORE, THE AMPERAGE OF THE BACKED UP LOADS IS LESS THAN THAT OF THE OCPD.
AC WIRE SIZING FOR BACKUP LOADS PANEL
MAX AC OUTPUT CURRENT = (MAX LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
18.6 A X 1.25 = 23.25 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
23.25A < 35A 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
PV-4.3
BACKUP LOAD
CALCS
2701 S Poplar St
3/10/2025
PAGE
REV: D 2/27/2025
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
(N) GATEWAY
FEEDER BREAKER
MAIN BREAKER10
0
NEW PV+ESS
BREAKER60
20
20
15
(N) 225A GENERATION
&BACKUPLOADS PANEL
20
20
20
20
20
LIVING ROOM
20
BATHROOM LIGHTS
FUTURE 100/100A
MAIN PANEL
PANEL SCHEDULE
PANEL SCHEDULE
PV-4.4
15
20
20
20
30
MASTER BED OUTLET
BATHROOM OUTELTS
AC UNIT
BEDROOM 2 LIGHTS
BEDROOM 2 OUTLETS
BEDROOM 3 LIGHTS
BEDROOM 3 OUTLETS
GARAGE OUTLETS
REFRIDGERATOR
MASTER BED LIGHTS
KITCHEN LIGHTS
KITCHEN OUTLETS
20
10
0
D
EXISTING PV
BREAKER
D
2701 S Poplar St
3/10/2025
PAGE
REV: B1 12/10/2024
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.0
#ESTAMP
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
POWER SOURCE OUTPUT CONNECTION
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
CEC 2022: 705.12(B)(3)(2)
NOTES AND SPECIFICATIONS:
SIGNS AND LABELS SHALL
MEET THE REQUIREMENTS
OF THE CEC 2022 ARTICLE
110.21(B), UNLESS SPECIFIC
INSTRUCTIONS ARE
REQUIRED BY SECTION 690,
OR IF REQUESTED BY THE
LOCAL AHJ.
SIGNS AND LABELS SHALL
ADEQUATELY WARN OF
HAZARDS USING EFFECTIVE
WORDS, COLORS AND
SYMBOLS.
LABELS SHALL BE
PERMANENTLY AFFIXED TO
THE EQUIPMENT OR WIRING
METHOD AND SHALL NOT BE
HAND WRITTEN.
LABEL SHALL BE OF
SUFFICIENT DURABILITY TO
WITHSTAND THE
ENVIRONMENT INVOLVED.
SIGNS AND LABELS SHALL
COMPLY WITH ANSI
Z535.4-2011, PRODUCT
SAFETY SIGNS AND LABELS,
UNLESS OTHERWISE
SPECIFIED.
DO NOT COVER EXISTING
MANUFACTURER LABELS.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
4"
3"
ELECTRICAL SHOCK HAZARD
WARNING
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S),
AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC
2022: 690.13(B)
!
INVERTER 1
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
WARNING:PHOTOVOLTAIC
POWER SOURCE
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:
690.31(D)(2)
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC
2022: 705.12(C)
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
ENERGY STORAGE SYSTEM
DISCONNECT
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
ENERGY STORAGE SYSTEM
PREMISES WIRING MAY REMAIN
ENERGIZED AFTER LOSS OF
UTILITY POWER
CAUTION!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C)
CAUTION
2701 S POPLAR ST, SANTA ANA, CA, 92704
SOLAR PANELS ON ROOF
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
MULTIPLE SOURCES OF POWER
INVERTER AND ENERGY STORAGE
(EXT)-PCS CONTROLLED
AC DISCONNECT
BACKUP GATEWAY
SERVICE ENTRANCE AND GATEWAY
FEEDER BREAKER
(E) PV EQUIPMENT
GENERATION AND BACKUP LOADS PANEL
RAPID SHUTDOWN SWITCH
(E)PV ARRAY
RAPID SHUTDOWN DISCONNECT LOCATION
(EXISTING SYSTEM AC DISCONNECT)
PV SYSTEM(S) ARE
EQUIPPED WITH RAPID
SHUTDOWN DEVICE(S)
2701 S Poplar St
3/10/2025
PAGE
REV: B1 12/10/2024
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.1
#ESTAMP
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
INVERTER 2
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
WARNING: THIS SENSOR IS PART
OF A POWER CONTROL SYSTEM.
DO NOT REMOVE. REPLACE ONLY
WITH THE SAME TYPE AND RATING.
WARNING: THIS SENSOR IS PART
OF A POWER CONTROL SYSTEM.
DO NOT REMOVE. REPLACE ONLY
WITH THE SAME TYPE AND RATING.
REQUIREMENT: UL 1741, SECTION 206.3
LOCATION: AROUND THE CT WIRE BY CLAMP
SIZE 4.25" X 0.75"
INVERTER 1
LABEL LOCATION:
REQUIREMENT: UL 1741, SECTION 206.1 AND 206.4
LOCATION: MAIN PANEL
SIZE: 4.25" X 1.25"
PCS CONTROLLED CURRENT SETTING: 56 A
THE MAXIMUM OUTPUT CURRENT FROM THIS
SYSTEM IS CONTROLLED ELECTRONICALLY.
REFER TO THE MANUFACTURER'S
INSTRUCTIONS FOR MORE INFORMATION.
LABEL LOCATION:
BACKUP LOAD PANEL
NO ADDITIONAL
LOADS TO BE
ADDED
LABEL LOCATION:
120 240NOMINAL ESS VOLTAGE VAC
MAIN PANEL.
ENERGY STORAGE SYSTEM DISCONNECT
NEC 2020 - PW2
PER CODE(S): NEC 706.15(C)
2701 S Poplar St
3/10/2025
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 1 of 8 GFT-OP-11a (22-August-2019)
Test Verification of Conformity
Verification Number: 104514208CRT-001VOC
Applicant Name & Address:
Tesla Inc.
3500 Deer Creek Road, Palo Alto, CA 94304
Product Description:
Energy Storage System Grid Support Utility Interactive & Standalone Inverter
Ratings & Principle
Characteristics:
See Appendix 2
Models/Type References:
1707000- followed by two numbers; followed by -; followed by one letter.
Brand Names:
Tesla
Relevant Standard(s) /
Specification(s):
See Appendix 1
Verification Issuing Office Name
& Address:
Intertek Testing Services NA, Inc.
3933 US Route 11, Cortland, NY 13045 USA
Date of Tests:
9/15/2022 to 4/23/2024
Test Report Number(s): 104514208CRT-001, 104514208CRT-001RRF, 104514208CRT-001TRS,
104514208CRT-010, 104514208CRT-012
Additional information in Appendix.
Signature
Name: Mukund Rana
Position: Sr. Staff Engineer
Date: 10th May 2024
On the basis of the tests undertaken, the samples of the below product have been found to comply with the
requirements of the referenced standards at the time the tests were carried out. This verification is part of the full
test report and should be read in conjunction with it.
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 2 of 8 GFT-OP-11a (22-August-2019)
Appendix 1: Relevant Standard(s)/Specification(s)
Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources
[UL 1741:2021 Ed.3]
Grid Support Utility Interactive Equipment - Supplement SA to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers
and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement
SA)]
Grid Support Utility Interactive Inverters and Converters Based Upon IEEE 1547:2018 & IEEE 1547.1:2020 -
Supplement SB to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers and Interconnection System Equipment for
use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement SB)]
Energy Storage Systems and Equipment [ANSI/UL 9540:2020 Ed.2+R:09Apr2021]
Photovoltaic (PV) DC Arc-Fault Circuit Protection [UL 1699B:2018 Ed.1+R:18May2021]
Software in Programmable Components [UL 1998:2013 Ed.3+R:24Sep2018]
Tests For Safety-related Controls Employing Solid-state Devices [UL 991:2004 Ed.3+R:09Jun2010]
Batteries for Use in Stationary, Vehicle Auxiliary Power and Light Electric Rail (LER) Applications [ANSI/UL 1973:2018
Ed.2]
IEEE 1547:2018 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with
Associated Electric Power Systems Interfaces
IEEE 1547a:2020 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with
Associated Electric Power Systems Interfaces
Amendment 1: To Provide More Flexibility for Adoption of Abnormal Operating Performance Category III
IEEE 1547.1:2020 - IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy
Resources with Electric Power Systems and Associated Interfaces
Source requirements document UL 1741 (SRD) v2.0 – HECO
Electric Rule No.21-2020 Generating Facility Interconnections
Default New England Bulk System Area Settings Requirement
PRC-024-3 Frequency and Voltage Protection Settings for Generating Resources
GOVERNMENT OF PUERTO RICO PUBLIC SERVICE REGULATORY BOARD PUERTO RICO ENERGY BUREAU, Generating
Facility and Microgrid Interconnection Regulation (“Regulation”), July 2021
Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1]
Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2]
Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2]
Safety Functions Incorporating Electronic Technology [CSA C22.2#0.8:2019 Ed.4]
2701 S Poplar St
3/10/2025
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 3 of 8 GFT-OP-11a (22-August-2019)
Appendix 2: Ratings & Principle Characteristics:
➢ Ratings:
Models 1707000-xx-y
Rated AC Output Power (W) 11500, 10000, 7680, 5750
Rated AC Input Power (W) Charging 5000
Max. Cont. Output Power (W) 11500, 10000, 7680, 5750
Max. Continuous Output PV to AC
Power Off-Grid (W) 15400
Max. Cont. Input Power (W) Charging 5000
AC Input / Output Voltage
(VL-L) 240
AC Output Frequency
(Hz) 60
Max. Cont. Output Current (A) 48, 4 1.6, 32, 24
Max. Cont. Input Current (A) Charging 20.83
Apparent Power rating (VA) 11500, 10000, 7680, 5750
Apparent Power rating (VA) Charging 5000
Normal Category A, B
Abnormal Category II, III
➢ Communication Protocol: IEEE 2030.5 protocol
➢ PCH board MD5 Firmware checksum: c5773b136a9ef9be9057302a67258482
➢ TACO board MD5 Firmware checksum: dcq8OiBXbQWYnK9UhCAjvl02/py2MZymmwAQYOn8jSc=
➢ Grid Support Function Parameters:
Tesla used the parameters in the Result reporting form “104514208CRT-001RRF” during the testing of the grid
support functions according to UL1741 SB. The parameters that have “blank” as their value are not applicable.
➢ UL 1998 and CSA C22.2#0.8 Evaluation:
ECU / Board Rev Software version Checksum UL1998, CSA C22.2#0.8
Compliant*
Date of evaluation
HVP / -E V2 51705DB5 Yes Apr-19-2024
PWS / -3F V2 34204954 Yes Apr-19-2024
PWS / -1F V2 B3C1375B Yes Apr-19-2024
PWS / -D V2 43FEF523 Yes Apr-19-2024
*Note: Below safety functions were evaluated during the UL1998 and UL 991 evaluation.
• List of all UL1998 and UL 991 functions are as follow:
o Overcharge
o Over-discharge
o Over Temperature
o Over current
o Relay weld, Isolation Monitoring Interruption, PV RSD (UL 1741)
o AFCI (UL 1699B)
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 4 of 8 GFT-OP-11a (22-August-2019)
2701 S Poplar St
3/10/2025
!
"
#$
$% &
!
" '() *$
' *
" +
'
,(-./)0
1'
*
#1
$
1'
#
2
$"
+)
$"
+
%
#$% &
!
1'
)+
!
%
#
'
)
#2*
$"
+1
*
$"
+
3
#
43
5
)6
57...*
57...&*
5#+#
&8
!
97
'"
*
"
1
""
%
5
#
!
)+
9
*
7
'
:$"
-
# ;.<2=><2?
0
(
1
"
+
"
+
#
"
'
"
'
+
+
+
,22
E
F
'"
"G
H
*8 '
"
+
.
Sep 16, 2020
5 .>-2=&>2?
0
.&2=2?
%!
"
1
+
&2@9=2@?
2@9=2@?
+
/%-;
#
#
#'A3B1$% &
0 )
0%&
71C$><;;>>&<
$".+ *#.
*
#
8
# ="?&.-2"=/)?=&.;2*#?
" 'D
'+#/)
*#/
*
#
# .2=.>2?
*
#
8 .>2=&;.<><2?
*
#
# &.<2=<.>>2?
++
)
" '
)
"
++
7
%
#
% 0
% +
+)3D
%/)0
!
%/)0
1:
!'
+
D
'+
D
)
:
+
D
)
#
)
!
)
= +
)
#
?
%!
0
%!
+
2701 S Poplar St
3/10/2025
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 5 of 8 GFT-OP-11a (22-August-2019)
Appendix 3: List of Tested Grid protection / Support Function:
Table 3A: Test List -1
Grid protection / Support
Function Tested
Test Standards Sections and Source Requirement Documents
IEEE 1547-
2018
IEEE 1547.1-
2020
UL 1741SB -
2021 CA Rule 21:2020
UL 1741 SRD
V2.0
(HECO):2020
OPERATIONAL TEMPERATURE -- 5.3.3.1 SB4.3.5.3 -- Same as 1547-
2018
PROTECTION FROM
ELECTROMAGNETIC
INTERFERENCE (EMI) TEST
4.11.1 5.8.1 SB4.3.5.8.1 -- Same as 1547-
2018
SURGE WITHSTAND
PERFORMANCE TEST 4.11.2 5.8.2 SB4.3.5.8.2 -- Same as 1547-
2018
PARALLELING DEVICE 4.11.3 5.8.3 -- -- Same as 1547-
2018
OVERVOLTAGE TRIP 6.4.1 5.4.2 SB4.3.5.4.2 Electric Rule No.
21 Table Hh.1
Same as 1547-
2018
UNDERVOLTAGE TRIP 6.4.1 5.4.3 SB4.3.5.4.3 Electric Rule No.
21 Table Hh.1
Same as 1547-
2018
OVERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2
SB4.3.5.5.1
&
SB4.3.5.5.2
Electric Rule No.
21 Table Hh.2
Same as 1547-
2018
UNDERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2
SB4.3.5.5.1
&
SB4.3.5.5.2
Electric Rule No.
21 Table Hh.2
Same as 1547-
2018
LOW VOLTAGE RIDE-THROUGH 6.4.2.3 &
6.4.2.5 5.4.4 SB4.3.5.4.4 Electric Rule No.
21 Table Hh.1
Same as 1547-
2018
HIGH VOLTAGE RIDE-THROUGH 6.4.2.4 5.4.7 SB4.3.5.4.7 Electric Rule No.
21 Table Hh.1
Same as 1547-
2018
LOW FREQUENCY RIDE-THROUGH 6.5.2.3 5.5.3 SB4.3.5.5.3 Electric Rule No.
21 Table Hh.2
SRD-UL-1741-SA-
V2.0 (HECO) Part
II B
HIGH FREQUENCY RIDE-
THROUGH 6.5.2.4 5.5.4 SB4.3.5.5.4 Electric Rule No.
21 Table Hh.2
SRD-UL-1741-SA-
V2.0 (HECO) Part
II B
RATE OF CHANGE OF FREQUENCY 6.5.2.5 5.5.5 -- -- Same as 1547-
2018
ANTI-ISLANDING PROTECTION -
WITH GRID SUPPORT FUNCTIONS
ENABLED
8.1 5.10.2 SB4.3.5.10.2 Electric Rule No.
21 Hh.1a
According to UL
1741 SA-V2.0
(HECO)
TEST FOR VOLTAGE PHASE-ANGLE
CHANGE RIDE-THOUGH
(VARIATION 1)
6.5.2.6 5.5.6.1 SB4.3.5.5.6 -- Same as 1547-
2018
ENTER SERVICE 4.10 5.6 -- -- Same as 1547-
2018
SYNCHRONIZATION CONTROL
FUNCTION TEST FOR EQUIPMENT
WITH NO SYNCHRONIZING
DISABLE CAPABILITY (VARIATION
3)
6.3 5.7.4 -- -- Same as 1547-
2018
LIMITATION OF DC INJECTION
FOR INVERTERS 7.1 5.9 -- Electric Rule No.
21 Hh.2h
Same as 1547-
2018
OPEN PHASE 6.2.2 5.11 -- -- Same as 1547-
2018
CURRENT DISTORTION 7.3 5.12 -- Electric Rule No. Same as 1547-
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 6 of 8 GFT-OP-11a (22-August-2019)
Grid protection / Support
Function Tested
Test Standards Sections and Source Requirement Documents
IEEE 1547-
2018
IEEE 1547.1-
2020
UL 1741SB -
2021 CA Rule 21:2020
UL 1741 SRD
V2.0
(HECO):2020
21 Hh.2g 2018
LIMIT ACTIVE POWER 4.6.2 5.13 -- Electric Rule No.
21 Hh.8
Same as 1547-
2018
CONSTANT POWER FACTOR 5.3.2 5.14.3 SB4.3.5.14.3 Electric Rule No.
21 Hh.2i
Same as 1547-
2018
VOLTAGE-REACTIVE POWER
(VOLT-VAR) MODE FIXED VREF 5.3.3 5.14.4 SB4.3.5.14.4 Electric Rule No.
21 Hh.2J
Same as 1547-
2018
VOLTAGE-REACTIVE POWER
(VOLT-VAR) MODE (VREF TEST) 5.3.3 5.14.5 SB4.3.5.14.5 -- Same as 1547-
2018
ACTIVE POWER-REACTIVE POWER
MODE (WATT-VAR) 5.3.4 5.14.7 SB4.3.5.14.7 -- Same as 1547-
2018
CONSTANT REACTIVE POWER
(VAR) MODE 5.3.5 5.14.8 SB4.3.5.14.8 -- Same as 1547-
2018
VOLTAGE-ACTIVE POWER (VOLT-
WATT) MODE 5.4 5.14.9 SB4.3.5.14.9 Electric Rule No.
21 Hh.2.m
Same as 1547-
2018
TEST FOR FREQUENCY -DROOP
(FREQUENCY-POWER OR
FREQUENCY-WATT) CAPABILITY —
ABOVE NOMINAL FREQUENCY
6.5.2.7 5.15.2 SB4.3.5.15.2 Electric Rule No.
21 Hh.2.l
SRD-UL-1741-SA-
V2.0 (HECO) Part
II C
TEST FOR FREQUENCY -DROOP
(FREQUENCY-POWER OR
FREQUENCY-WATT) CAPABILITY —
BELOW NOMINAL FREQUENCY
6.5.2.7 5.15.3 SB4.3.5.15.3 Electric Rule No.
21 Hh.2.l
SRD-UL-1741-SA-
V2.0 (HECO) Part
II C
PRIORITIZATION OF DER
RESPONSES 4.7 5.16 SB4.3.5.16 -- Same as 1547-
2018
LOAD REJECTION OVERVOLTAGE
(LROV) 7.4 5.17.2 SB4.3.5.17.2 -- Same as 1547-
2018
FAULT CURRENT TESTS FOR
INVERTERS 6.2.1 5.18.1 -- -- Same as 1547-
2018
PERSISTENCE OF DER PARAMETER
SETTINGS -- 5.19 -- -- Same as 1547-
2018
NORMAL RAMP RATE -- -- -- Electric Rule No.
21 Hh.2k --
NAMEPLATE DATA TEST 10.3 6.4 -- -- Same as 1547-
2018
MONITORING INFORMATION
TEST 10.5 6.6 SB4.3.6.6 -- Same as 1547-
2018
MANAGEMENT INFORMATION
TEST 10.6 6.7 SB4.3.6.7 -- Same as 1547-
2018
2701 S Poplar St
3/10/2025
2701 S Poplar St
3/10/2025
Powerwall 3
Power Everything
2024
—
Powerwall 3 is a fully integrated solar and battery system, designed to accelerate the transition to sustainable energy. Customers
can receive whole home backup, cost savings, and energy independence by producing and consuming their own energy while
participating in grid services. Once installed, customers can manage their system using the Tesla App to customize system
behavior to meet their energy goals.
Powerwall 3 achieves this by supporting up to 20 kW DC of solar and providing 11.5 kW AC of continuous power per unit. It has
the ability to start heavy loads up to 185 A LRA, meaning a single unit can support the power needs of most homes. Powerwall 3
is designed for mass production,fast and efcient installations,easy system expansion,and simple connection to any electrical
service.
22024Powerwall 3 Datasheet
Solar Technical
Specications
Maximum Solar STC Input 20 kW
Withstand Voltage 600 V DC
PV DC Input Voltage Range 60 — 550 V DC
PV DC MPPT Voltage Range 60 — 480 V DC
MPPTs 6
Maximum Current per MPPT (Imp)13 A 5
Maximum Short Circuit Current per MPPT (Isc)15 A 5
Powerwall 3 Technical Specifications
1 Typical solar shifting use case.
2 Values provided for 25°C (77°F), at beginning of life. 3.3 kW charge/discharge power.
3 Tested using CEC weighted efciency methodology.
4 The customer is expected to provide internet connectivity for Powerwall 3;cellular should not be used as the primary mode of
connectivity. Cellular connectivity subject to network operator service coverage and signal strength.
5 Where the DC input current exceeds the MPPT rating,a jumper can be used to combine two MPPTs into a single input to
intake DC current up to 26 A IMP / 30 A ISC.
Battery Technical
Specications
Nominal Battery Energy 13.5 kWh AC 2
Maximum Continuous Discharge Power 11.5 kW AC
Maximum Continuous Charge Power 5 kW AC
Output Power Factor Rating 0 -1 (Grid Code congurable)
Maximum Continuous Current 48 A
Maximum Output Fault Current 10 kA
Load Start Capability (1 s)185 A LRA
Power Scalability Up to 4 Powerwall 3 units supported
System Technical
Specications
Model Number 1707000-xx-y
Nominal Grid Voltage (Input &Output)120/240 VAC
Grid Type Split phase
Frequency 60 Hz
Overcurrent Protection Device 60 A
Solar to Battery to Home/Grid Efciency 89% 1,2
Solar to Home/Grid Efciency 97.5% 3
Supported Islanding Devices Gateway 3, Backup Switch, Backup Gateway 2
Connectivity Wi-Fi (2.4 and 5 GHz), Dual-port switched Ethernet,
Cellular (LTE/4G 4)
Hardware Interface Dry contact relay,Rapid Shutdown (RSD)certied switch
and 2-pin connector, RS-485 for meters
AC Metering Revenue Grade (+/- 0.5%)
Protections Integrated arc fault circuit interrupter (AFCI), Isolation
Monitor Interrupter (IMI),PV Rapid Shutdown (RSD)using
Tesla Mid-Circuit Interrupters
Customer Interface Tesla Mobile App
Warranty 10 years
2701 S Poplar St
3/10/2025
2701 S Poplar St
3/10/2025
!"#!$
%$&
'
(
)( *+ ,-
((* ,
. ) ./
( *
00+&1&2!!
%
.
.3(
4
/
*4
.
.3 #!5$
/
.(
/(
671
.(
.3 %$&
..
*8
./)(
..
4
*.
((
(.
%. .3*8
/
-)
/(
(
(..
.3
*
.3
.
( *
"(
3
.3 !"$
9
$:222$&
(-.-
$: 222$&88
-8(
-
.
*
:;#2615--<72715.=
3 2#!5--<;2#&5.=
8 ;1215--<&2715.=
3
..3 >
&2;152-<&15()/2.=!2!!?!2!:5.@<2!6?12#5--@=$: 222$:!=
&2;152-<&15()/2.=$: 222$:!=
12!652-< 15()/2.=!2!:5.@<62&75--@=$6=
12!652-< 15()/2.=!2!?!2!&5.@<:2&?:2:5--@=$#222$ =
12#152-<1!5()/2.=!2! 5.@<#2#75--@=$&=
.3
.88.3
(
3*!!:!#AB%$&B&!!!$
.
(
:$
(
-
+
-
.
.
.
.
.
)
/
.
.
)
/
-
.
.
3
)
(
*
(
)
(
*
/
8
/
8
/
8
8
(
.
Feb 3, 2020
:
!!761;!: ;: ;:
,
3
4
3 <)=2::5,3< 2#15()<==
.
)( *C
. */3.%D
//
.
)( *
.
)(
//
.
--8
(/.
88 .#1 $+8
.
E8
*
-
(.(.3+
.(
-8.4
,.4.
/
(/.
.3
.A
8 '
-2-
./-
.3
44428#14
..32
23'
$
3(
.$
(
.
$/
/"C
'
-8(
.
(
.
E
'*-
(/
C
%
*/
C
E
-8 ../-
.C
.
3(
..
(
.
'
.
(
.< /.
(
3
(8
=
.'.-
.
((
.'.-
.
(/(
(
*/(
.
/8
/
*(.38
.
.
(4
. *
. *:6-.
2701 S Poplar St
3/10/2025
32024Powerwall 3 Datasheet
Mechanical
Specications
Dimensions 1099 x 609 x 193 mm (43.25 x 24 x 7.6 in)
Weight 130 kg (287 lb)
Mounting Options Floor or wall mount
Powerwall 3 Technical Specifications
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F) 6
Operating Humidity (RH)Up to 100%, condensing
Storage Temperature –20°C to 30°C (–4°F to 86°F), up to 95% RH, non-
condensing, State of Energy (SOE): 25% initial
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
Enclosure Rating NEMA 3R
Ingress Rating IP67 (Battery & Power Electronics)
IP45 (Wiring Compartment)
Pollution Rating PD3
Operating Noise @ 1 m < 50 db(A) typical
<62 db(A)maximum
Compliance
Information
Certications UL 1642, UL 1699B, UL 1741, UL 1741 SA, UL 1741 SB, UL
1741 PCS, UL 3741, UL 1973, UL 1998, UL 9540, IEEE 1547-
2018, IEEE 1547.1, UN 38.3
Grid Connection United States
Emissions FCC Part 15 Class B
Environmental RoHS Directive 2011/65/EU
Seismic AC156, IEEE 693-2005 (high)
Fire Testing Meets the unit level performance criteria
of UL 9540A
6 Performance may be de-rated at operating temperatures above 40°C (104°F).
609 mm 193
mm
1099 mm
42024Powerwall 3 Datasheet
Electrical
Specications
Model MCI-1 MCI-2
Nominal Input DC Current Rating (IMP)13 A 13 A
Maximum Input Short Circuit Current (ISC)19 A 17 A
Maximum System Voltage (PVHCS)600 V DC 1000 V DC 7
Solar Shutdown Device Technical Specifications
Environmental
Specications
Operating Temperature -40°C to 50°C
(-40°F to 122°F)
-45°C to 70°C
(-49°F to 158°F)
Storage Temperature –30°C to 70°C
(–22°F to 158°F)
–30°C to 70°C
(–22°F to 158°F)
Enclosure Rating NEMA 4X /IP65 NEMA 4X /IP65
RSD Module
Performance
Maximum Number of Devices per String 5 5
Control Power Line Excitation Power Line Excitation
Passive State Normally Open Normally Open
Maximum Power Consumption 7 W 7 W
Warranty 25 years 25 years
—
The Solar Shutdown Device is a Mid-Circuit Interrupter (MCI)and is part of the PV system rapid shutdown (RSD)function in
accordance with Article 690 of the applicable NEC. When paired with Powerwall 3, solar array shutdown is initiated by any loss
of AC power.
Mechanical
Specications
Electrical Connections MC4 Connector MC4 Connector
Housing Plastic Plastic
Dimensions 125 x 150 x 22 mm
(5 x 6 x 1 in)
173 x 45 x 22 mm
(6.8 x 1.8 x 1 in)
Weight 350 g (0.77 lb) 120 g (0.26 lb)
Mounting Options ZEP Home Run Clip
M4 Screw (#10)
M8 Bolt (5/16")
Nail / Wood screw
Wire Clip
Compliance
Information
Certications UL 1741 PVRSE, UL 3741,
PVRSA (Photovoltaic Rapid Shutdown Array)
RSD Initiation Method External System Shutdown Switch or
Powerwall 3 Enable Switch
7 Maximum System Voltage is limited by Powerwall to 600 V DC.
UL 3741 PV Hazard Control
(and PVRSA)Compatibility See Powerwall 3 Installation Manual
2701 S Poplar St
3/10/2025
52024Powerwall 3 Datasheet
Gateway 3
8 Only Eaton CSR or BWH main breakers are 25 kA rated.
Performance
Specications
Model Number 1841000-01-y
Nominal Grid Voltage 120/240 V AC
Grid Conguration Split phase
Grid Frequency 60 Hz
Continuous Current
Rating
200 A
Maximum Supply Short
Circuit Current
22 kA with Square D or
Eaton main breaker
25 kA with Eaton main
breaker 8
IEC Protective Class Class I
Overvoltage Category Category IV
Mechanical
Specications
Dimensions 660 x 411 x 149 mm
(26 x 16 x 6 in)
Weight 16.3 kg (36 lb)
Mounting options Wall mount
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
Operating Humidity (RH)Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
Enclosure Type NEMA 3R
Compliance
Information
Certications UL 67, UL 869A, UL 916, UL 1741 PCS,
CSA 22.2 107.1, CSA 22.2 29
Emissions FCC Part 15, ICES 003
—
Tesla Gateway 3 controls connection to the grid in a Powerwall system, automatically detecting outages and providing seamless
transition to backup power. It provides energy monitoring that is used by Powerwall for solar self-consumption, time-based
control, and backup operation.
411 mm
660
mm
149
mm
AC Meter Revenue accurate (+/- 0.5%)
Communication CAN
User Interface Tesla App
Backup Transition Automatic disconnect for
seamless backup
Overcurrent
Protection Device
100–200 A
Service entrance rated
Eaton CSR, BWH, or BW, or
Square D QOM breakers
Internal Panelboard 200 A
8-space/16 circuit breakers
Eaton BR, Siemens QP, or
Square D HOM breakers rated
to 10–125A
Warranty 10 years
62024Powerwall 3 Datasheet
Backup Switch
9 Breaker maximum supply short circuit current rating must be equal to or greater than the available fault current.
Performance
Specications
Model Number 1624171-xx-y
Continuous Load Rating 200 A, 120/240 V split phase
Maximum Supply Short Circuit Current 22 kA with breaker 9
Communication CAN
AC Meter Revenue accurate (+/- 0.5%)
Expected Service Life 21 years
Warranty 10 years
Mechanical
Specications
Dimensions 176 x 205 x 74 mm (6.9 x 8.1 x 2.9 in)
Weight 2.8 lb
Meter and Socket Compatibility ANSI Type 2S, ringless or ring type
External Service Interface Contactor manual override 10
Reset button
Conduit Compatibility 1/2-inch NPT
Environmental
Specications
Operating Temperature –40°C to 50°C (–40°F to 122°F)
Storage Temperature –40°C to 85°C (–40°F to 185°F)
Enclosure Rating NEMA 3R
Pollution Rating PD3
Compliance
Information
Safety Standards USA: UL 414, UL 414 SB, UL 2735, UL 916, CA Prop 65
Emissions FCC, ICES
10 Manually overrides the contactor position during a service event.
—
The Tesla Backup Switch controls connection to the grid in a Powerwall system, and can be easily installed behind the utility
meter or in a standalone meter panel downstream of the utility meter.
The Backup Switch automatically detects grid outages, providing a seamless transition to backup power. It communicates
directly with Powerwall, allowing home energy usage monitoring from any mobile device with the Tesla app.
204.86
74
176 mm
205 mm
74 mm
2701 S Poplar St
3/10/2025
72024Powerwall 3 Datasheet
Backup Gateway 2
Performance
Specications
Model Number 1232100-xx-y
AC Voltage (Nominal)120/240 V
Feed-in Type Split phase
Grid Frequency 60 Hz
Current Rating 200 A
Maximum Supply Short
Circuit Current
10 kA 11
Overcurrent Protection
Device
100 - 200 A, Service
entrance rated 9
Overvoltage Category Category IV
Internal Primary
AC Meter
Revenue accurate
(+/- 0.2%)
Internal Auxiliary
AC Meter
Revenue accurate
(+/- 2%)
Primary Connectivity Ethernet, Wi-Fi
Secondary Connectivity Cellular (3G, LTE/4G) 12
Mechanical
Specications
Dimensions 660 x 411 x 149 mm
(26 x 16 x 6 in)
Weight 20.4 kg (45 lb)
Mounting options Wall mount,
Semi-Bush mount
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
Operating Humidity (RH)Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
Enclosure Type NEMA 3R
Compliance
Information
Certications UL 67, UL 869A, UL 916, UL 1741 PCS,
CSA 22.2 0.19, CSA 22.2 205
Emissions FCC Part 15, ICES 003
411 mm
660 mm
149
mm
11 When protected by Class J fuses, Backup Gateway 2 is
suitable for use in circuits capable of delivering not more
than 22kA symmetrical amperes.
12 Cellular connectivity subject to network operator service
coverage and signal strength.
—
Backup Gateway 2 controls connection to the grid when paired with Powerwall 3, automatically detecting outages and providing
seamless transition to backup power. Backup Gateway 2 also provides energy metering for solar self-consumption, time-based
control, and backup operation.
In this system conguration,Powerwall 3 acts as the Site Controller,with the Backup Gateway 2 Site Controller disabled.
User Interface Tesla App
Operating Modes Support for solar self-
consumption, time-based
control, and backup
Backup Transition Automatic disconnect for
seamless backup
Modularity Supports up to 10 AC-
coupled Powerwalls
Optional Internal
Panelboard
200 A 6-space / 12 circuit
breakers
Siemens QP or Square D
HOM breakers rated 10 -
80A or Eaton BR breakers
rated 10 - 125A
Warranty 10 years
82024Powerwall 3 Datasheet
Powerwall 3 Example System Configurations
Powerwall 3 with Backup Switch
Whole Home Backup
Powerwall 3 with Gateway 3
Whole Home Backup
Powerwall 3 with Backup Gateway 2
Partial Home Backup
2701 S Poplar St
3/10/2025
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 7 of 8 GFT-OP-11a (22-August-2019)
Table 3B: Test List -2
Test Description
CSA
C22.2#107.1:2016
Ed. 4 CSA C22.3#9:2020 Ed 2
Screw Tightening Torque Test 3.6.3 --
Impedance Test 105.1/10.5.2 --
Continuity Test 4.1 --
Output Power Factor 4.2 --
Voltage Harmonics for stand alone 15.3.2.1 --
Frequency 10.5.4 --
Stand-alone inverter dc output short-circuits current contribution 10.5.5 --
Normal ramp rate -- 7.2.3.4.2 / 8.3.12.2.3
Flicker -- 7.2.2 / 8.3.13
Test for constant reactive power (var) mode 7.2.3.3.3 / 8.3.12.2.2
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This
Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Intertek Page 8 of 8 GFT-OP-11a (22-August-2019)
Appendix 4: Revision Summary
Date /
Project Engineer Comments
15-Feb-2023 Dipesh Patel Original issue date
8-Mar-2023 /
G104200718
Dipesh Patel Added UL 1699B, UL 1998 and UL 991 standards
24-Mar-2023/
G104200718
Dipesh Patel Added UL 1973 standard.
Added normal and abnormal category in ratings table.
18-Apr-2023 /
G104200718
Dipesh Patel Added additional factory settable nameplate ratings rated output active
power (W): 9600, 7680, 5750; Max. Continuous output power (W):
9600, 7680, 5750; Max. Cont. Output Current (A): 40, 32, 24; Apparent
Power rating (VA): 9600, 7680, 5750
Added Puerto Rico Interconnection regulation as it refers to UL 1741
and IEEE 1547-2018.
1-May-2024 /
G104514208
Mukund Rana
A) Added standards.
Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1]
Interconnection of Distributed Energy Resources and Electricity Supply
Systems [CSA C22.3#9:2020 Ed.2]
Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2]
Interconnection of Distributed Energy Resources and Electricity Supply
Systems [CSA C22.3#9:2020 Ed.2]
B) Update CSA C22.2#0.8 standard
C) added Table 3B: Test List -2
2701 S Poplar St
3/10/2025
Service Voltage
240
Section 220.83 Existing Dwelling Unit
Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
20.4 4896
Part #2 - Section 220.83(B)(2), (3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500
1500
1500
1000
600
1000
1600
Amps Box B (VA)
36.25 8700
Total VA from Parts #1 and #2 combined:Box A + Box B = 13596
Total VA 13596
First 8000 VA @ 100% 8000 Remaining VA @ 40%
Remaining VA = 5596 5596 x 40% = 2238.4 VA
Adding First 8000 VA, if possible 8000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits: 10238.4 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits: 42.66 Amps
Part #3 - Section 220.83(B) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:4,464 VA
100% of all the Heating or A/C loads in Amps:18.60 A
VA Volts Amps
Parts #1 & #2 10238.4 240 42.66
Part #3 4,464 240 18.60
Total VA for all Parts: 14,702
Totals Service/Feeder Load 61.26
Dedicated circuit Dedicated circuit
Article 220 - Dedicated Backup Panel Calculation Job Code
2701 S Poplar St
Santa Ana, CA 92704
109R-701MEN1
Building Square Footage VA (watts)Amps
House 1632.00 4896 20.40
Total for Part #1:
Laundry
Appliance Circuit - 1
Appliance Circuit - 2
Dishwasher
Disposal
Refrigerator
Microwave
Totals for Part #2:
Totals from all Parts
2701 S Poplar St
3/10/2025
Service Voltage
240
Section 220.82 Dwelling Unit
Part #1 - Section 220.82(B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
20.4 4896
Part #2 - Section 220.82(B)(3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500
1500
1500
1000
600
1000
1600
Amps Box B (VA)
36.25 8700
Total VA from Parts #1 and #2 combined:Box A + Box B =13596
Total VA 13596
First 10000 VA @ 100%10000 Remaining VA @ 40%
Remaining VA =3596 3596 x 40% =1438.4 VA
Adding First 10000 VA, if possible 10000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:11438.4 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:47.66 Amps
Part #3 - Section 220.82(C) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:4,464 VA
100% of all the Heating or A/C loads in Amps:18.60 A
VA Volts Amps
Parts #1 & #2 11438.4 240 47.66
Part #3 4,464 240 18.60
Total VA for all Parts:15,902
Totals Service/Feeder Load 66.26
Dedicated circuit Dedicated circuit
Article 220 - Dedicated Backup Panel Calculation Job Code
2701 S Poplar St
Santa Ana, CA 92704
109R-701MEN1
Building Square Footage VA (watts)Amps
House 1632.00 4896 20.40
Total for Part #1:
Laundry
Appliance Circuit - 1
Appliance Circuit - 2
Dishwasher
Disposal
Refrigerator
Microwave
Totals for Part #2:
Totals from all Parts
2701 S Poplar St
3/10/2025
Section 220.83 Existing Dwelling Unit
Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
20.4 4896
Part #2 - Section 220.83 (B)(2),(3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500 N/A
3000 N/A
1000 N/A
600 N/A
1000 N/A
1600 N/A
N/A N/A
N/A N/A
N/A N/A
N/A Amps Box B (VA)
N/A 36.25 8700
Total VA from Parts #1 and #2 combined:Box A + Box B =13596
Total VA 13596
First 8,000 VA @ 100%8000 Remaining VA @ 40%
Remaining VA =5596 5596 x 40% =2238.4 VA
Adding First 8000 VA 8000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:10238.4 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:42.66 Amps
Part #3 - Section 220.83 (B) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:4,464 VA
100% of all the Heating or A/C loads in Amps:18.60 A
VA Volts Amps
Parts #1 & #2 10238.4 240 42.66
Part #3 4,464 240 18.60
Total VA for all Parts:14,702
Totals Service/Feeder Load 61.26
#ESTAMP
Laundry
Appliance Circuit(s)
Dishwasher(s)
Disposal(s)
Dedicated circuit
House
Square Footage
1632
Article 220 - Service/Feeder calculation for (address):
2701 S Poplar St
Santa Ana, CA 92704
Building VA (watts)
4896
Amps
20.4
Job Code
109R-701MEN1
Totals from all Parts
Dedicated circuit
Total for Part #1:
Refrigerator(s)
Microwave(s)
Totals for Part #2:
Dryer
Range
Oven
Pool Equipment
2701 S Poplar St
3/10/2025
Bus Rating:100
Main Rating:100
0%0%
Not Fed by other panels
Feeds: Panel 2 61.26
0.00
61.26
Bus Rating:225
Main Rating:70
100%100%
Itemized House and 240V Loads for Panel: (VA)
1500 1500
1500 1000
600 1000
1600 4464
Fed by: Panel 1
61.26
61.26
Panel 1 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Load Calc: (This Panel)
Total Load Calc:
Panel 2 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Laundry Appliance Circuit - 1
Total Load Calc:
Appliance Circuit - 2 Dishwasher
Disposal Refrigerator
Microwave A/C Unit - 240V
Load Calc: (This Panel)
2701 S Poplar St
3/10/2025
City of Santa Ana,
SIGNATURE:___________________ DATE:__________
717 17th Street, Ste. 200 | Denver, CO 80202
I, Isidro Mendoza, grant authorization to SUNRUN SOLAR to install Rooftop Mounted Solar
on my residence located at 2701 s popular st , SANTA ANA, CA, 92704.
Docusign Envelope ID: 07FB0F4F-DB5E-48FE-BEDB-560D4E23E344
12/20/2024
2701 S Poplar St
3/10/2025
Certificate Of Completion
Envelope Id: 07FB0F4F-DB5E-48FE-BEDB-560D4E23E344 Status: Completed
Subject: Complete with Docusign: Isidro Mendoza.Solar Authorization Letter (1).pdf
Source Envelope:
Document Pages: 1 Signatures: 1 Envelope Originator:
Certificate Pages: 5 Initials: 0 Stephanie Phillips
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
225 Bush Street, Suite 1400
San Francisco, CA 94104
stephanie.phillips@sunrun.com
IP Address: 68.119.159.122
Record Tracking
Status: Original
12/17/2024 3:25:21 PM
Holder: Stephanie Phillips
stephanie.phillips@sunrun.com
Location: DocuSign
Signer Events Signature Timestamp
Isidro Mendoza
isidroamendoza94@gmail.com
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 172.1.155.184
Signed using mobile
Sent: 12/17/2024 3:26:18 PM
Resent: 12/19/2024 1:50:57 PM
Viewed: 12/20/2024 4:38:49 PM
Signed: 12/20/2024 4:39:23 PM
Electronic Record and Signature Disclosure:
Accepted: 8/11/2024 7:38:38 PM
ID: c01db57d-2018-4fbc-819e-0348fc13a4f3
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 12/17/2024 3:26:18 PM
Certified Delivered Security Checked 12/20/2024 4:38:49 PM
Signing Complete Security Checked 12/20/2024 4:39:23 PM
Completed Security Checked 12/20/2024 4:39:23 PM
Payment Events Status Timestamps
Electronic Record and Signature Disclosure
2701 S Poplar St
3/10/2025
CONSUMER DISCLOSURE
From time to time, Sunrun Inc. (we, us or Company) may be required by law to provide to you
certain written notices or disclosures. Described below are the terms and conditions for providing
to you such notices and disclosures electronically through the DocuSign, Inc. (DocuSign)
electronic signing system. PLEASE READ THE INFORMATION BELOW CAREFULLY
AND THOROUGHLY, AND IF YOU CAN ACCESS THIS INFORMATION
ELECTRONICALLY TO YOUR SATISFACTION AND AGREE TO THESE TERMS AND
CONDITIONS, PLEASE CONFIRM YOUR AGREEMENT BY CLICKING THE 'I AGREE'
BUTTON AT THE BOTTOM OF THIS DOCUMENT.
Getting paper copies
At any time, you may request from us a paper copy of any record provided or made available
electronically to you by us. You will have the ability to download and print documents we send
to you through the DocuSign system during and immediately after signing session and, if you
elect to create a DocuSign signer account, you may access them for thirty (30) days after such
documents are first sent to you. After such time, if you wish for us to send you paper copies of
any such documents from our office to you, please request delivery of such paper copies from us
by following the procedure described below.
Withdrawing your consent
If you decide to receive notices and disclosures from us electronically, you may at any time
change your mind and tell us that thereafter you want to receive required notices and disclosures
only in paper format. How you must inform us of your decision to receive future notices and
disclosure in paper format and withdraw your consent to receive notices and disclosures
electronically is described below.
Consequences of changing your mind
If you elect to receive required notices and disclosures only in paper format, it will slow the
speed at which we can complete certain steps in transactions with you and delivering services to
you because we will need first to send the required notices or disclosures to you in paper format,
and then wait until we receive back from you your acknowledgment of your receipt of such
paper notices or disclosures. To indicate to us that you are changing your mind, you must
withdraw your consent using the DocuSign ‘Withdraw Consent’ form on the signing page of a
DocuSign envelope instead of signing it. This will indicate to us that you have withdrawn your
consent to receive required notices and disclosures electronically from us and you will no longer
be able to use the DocuSign system to receive required notices and consents electronically from
us or to sign electronically documents from us.
All notices and disclosures will be sent to you electronically
Unless you tell us otherwise in accordance with the procedures described herein, we will provide
electronically to you through the DocuSign system all required notices, disclosures,
authorizations, acknowledgements, and other documents that are required to be provided or made
available to you during the course of our relationship with you. To reduce the chance of you
inadvertently not receiving any notice or disclosure, we prefer to provide all of the required
notices and disclosures to you by the same method and to the same address that you have given
us. Thus, you can receive all the disclosures and notices electronically or in paper format through
the paper mail delivery system. If you do not agree with this process, please let us know as
described below. Please also see the paragraph immediately above that describes the
consequences of your electing not to receive delivery of the notices and disclosures
electronically from us.
Electronic Record and Signature Disclosure created on: 8/7/2013 10:17:58 AM
Parties agreed to: Isidro Mendoza 2701 S Poplar St
3/10/2025
How to contact Sunrun Inc.:
You may contact us to let us know of your changes as to how we may contact you electronically,
to request paper copies of certain information from us, and to withdraw your prior consent to
receive notices and disclosures electronically as follows:
To contact us by email send messages to: customercare@sunrun.com
You may also contact us in writing at 45 Fremont Street, 32nd Floor, San Francisco, CA 94105
or by phone at 1-855-478-6786.
To advise Sunrun Inc. of your new e-mail address
To let us know of a change in your e-mail address where we should send notices and disclosures
electronically to you, you must send an email message to us at customercare@sunrun.com and in
the body of such request you must state: your previous e-mail address, your new e-mail
address. We do not require any other information from you to change your email address.
In addition, you must notify DocuSign, Inc. at 1-866-219-4318 to arrange for your new email
address to be reflected in your DocuSign account by following the process for changing e-mail in
the DocuSign system.
To request paper copies from Sunrun Inc.
To request delivery from us of paper copies of the notices and disclosures previously provided
by us to you electronically, you must contact us by (a) sending us an e-mail to
customercare@sunrun.com, (b) writing to us at Sunrun Inc, 45 Fremont Street, 32nd Floor, San
Francisco, CA 94105, or (c) calling us at 1-855-478-6786, and in connection with your request
you must state your e-mail address, full name, US Postal address, and telephone number.
To withdraw your consent with Sunrun Inc.
To inform us that you no longer want to receive future notices and disclosures in electronic
format you may:
i. decline to sign a document from within your DocuSign session, and on the subsequent
page, select the check-box indicating you wish to withdraw your consent, or you may;
ii. contact us by (a) sending us an email to customercare@sunrun.com, (b) writing to us
at Sunrun Inc., 45 Fremont Street, 32nd Floor, San Francisco, CA 94105, or (c) calling us
at 1-855-478-6786, and in connection with your request you must state your e-mail, full
name, US Postal Address, and telephone number. We do not need any other information
from you to withdraw consent.. The consequences of your withdrawing consent for
online documents will be that transactions may take a longer time to process..
Required hardware and software
Operating
Systems: Windows® 2000, Windows® XP, Windows Vista®; Mac OS® X
2701 S Poplar St
3/10/2025
Browsers:
Final release versions of Internet Explorer® 6.0 or above (Windows only);
Mozilla Firefox 2.0 or above (Windows and Mac); Safari™ 3.0 or above
(Mac only)
PDF Reader: Acrobat® or similar software may be required to view and print PDF files
Screen
Resolution: 800 x 600 minimum
Enabled Security
Settings: Allow per session cookies
** These minimum requirements are subject to change. If these requirements change, you will be
asked to re-accept the disclosure. Pre-release (e.g. beta) versions of operating systems and
browsers are not supported.
Notices
Any notice or other communication to be made hereunder, even if otherwise required to be in
writing under other provisions of this Consent or any other documents or agreements that have
been provided to you in connection with this Consent, may alternatively be made in an electronic
record transmitted electronically to the electronic addresses provided by you. Any notice or other
communication made in electronic form will have the same legal effect and enforceability as if
made in non-electronic form.
Acknowledging your access and consent to receive materials electronically
To confirm to us that you can access this information electronically, which will be similar to
other electronic notices and disclosures that we will provide to you, please verify that you were
able to read this electronic disclosure and that you also were able to print on paper or
electronically save this page for your future reference and access or that you were able to e-mail
this disclosure and consent to an address where you will be able to print on paper or save it for
your future reference and access. Further, if you consent to receiving notices and disclosures
exclusively in electronic format on the terms and conditions described above, please let us know
by clicking the ‘I agree’ button below.
By checking the ‘I agree’ box, I confirm that:
I can access and read and have accessed, read and understood the terms of this
ELECTRONIC CONSENT TO ELECTRONIC RECEIPT OF ELECTRONIC
CONSUMER DISCLOSURES document; and
I can print on paper the disclosure or save or send the disclosure to a place where I can
print it, for future reference and access; and
Until or unless I notify Sunrun Inc. as described above, I consent to receive from
exclusively through electronic means all notices, disclosures, authorizations,
acknowledgements, and other documents that are required to be provided or made
available to me by Sunrun Inc. during the course of my relationship with you.
Entire Agreement Provision
This agreement and the consumer disclosure statement executed by the customer in conjunction
with and simultaneously with its review and acceptance of the terms set forth herein constitute
2701 S Poplar St
3/10/2025
the entire agreement between the parties with respect to the subject matter hereof and supersede
any prior understandings, agreements, or representations by or between the parties, written or
oral, to the extent they relate in any way to the subject matter hereof.
2701 S Poplar St
3/10/2025
Rev: 8/29/19
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
Print Name:
CA CL #750184 (C10, C46)
SUNRUN
SOL-01 CBC 2016
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
CAITLYN HERNANDEZ
385-400-5019
Caitlyn.hernandez@sunrun.com
2701 s poplar st Santa ana Ca 92704
1.14.25
2701 S Poplar St
3/10/2025
PAGE
REV: C1 1/14/2025
ISIDRO MENDOZA
2701 S POPLAR ST, SANTA ANA,
CA, 92704
PROJECT NUMBER:
109R-701MEN1
SHEET
DESIGNER:
VISHNUMAYA KP
CUSTOMER RESIDENCE:
TEL. (714) 697-7230
APN: 140-273-07
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N)NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-3.0 LAYOUT
PV-3.1 LAYOUT
PV-3.2 MOUNTING DETAIL
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL
PV-4.2 ELECTRICAL CALCS
PV-4.3 BACKUPLOAD CALCS
PV-4.4 PANEL SCHEDULE
PV-5.0 SIGNAGE
PV-5.1 SIGNAGE
LTD: LR5-54HABB-395M
TESLA: POWERWALL 3 1707000-XX-Y
FOOT TO FRAMING, SNR-DC-00339
1707000-XX-Y WITH INTERGRATED INVERTER: 13.5 kWh
TOTAL ENERGY CAPACITY (IN kWh): 27kWH
EQUIPMENT INSTALLED, SEE PV-4.0 FOR INTERCONNECTION
DETAILS
EXISITNG SOLAR SYSTEM INSTALLED
BACKUP GATEWAY: (1) 200A TESLA POWERWALL CONTROL
PANEL
CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS.
SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A).
MODULES, ARE CLASS A FIRE RATED.
CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30
SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE
ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
2701 S Poplar St
3/10/2025