HomeMy WebLinkAbout10180154_1915 W. FIRST C - Plan1,11}Ingn Planning & Building Agency Building and Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www. santa-ana.org ELECTRICAL SIGN REQUIREMENTS Code references are to the 2010 California Electrical Code (CEC) A. All signs require Planning Department approval. B. All electrical signs require electric plancheck and permit. 1. Manufacturer's instructions are required at the time of submittal. C-11: 3-21-2011 2. Submit detailed installation instructions including diagrams to the Building Department for plan review at the time of submittal. Plans must include appropriate items noted by this bulletin. 3. Cash or surety bond in the amount of $200.00 is required at time of issuance for each address. The cash or surety bond will be refunded after all required finals. C. A building permit is also required - except for open or highlight neon lighting. D. Installation Requirements: CONTACT FIELD INSPECTOR PRIOR TO SIGN INSTALLATION. (SEE SECTION G OF THIS BULLETIN) 1. Conductors and equipment shall comply with California Electric Code Article 600. 2. All metal parts of a sign shall be bonded in the manner specified in Article 250. Isolated metal parts are permitted to be bonded by using an external green insulated conductor. Equipment grounding & bonding conductors must be sized by 110.26 and protected from physical damage. Minimum size is 14 AWG. CEC 600.7 3. A listed disconnect switch in the power supply primary, shall be installed within sight of sign or have permanently installed means for locking in an "OFF" position. This is also true for a transformer enclosure. CEC 600.6 4. A listed receptacle or an approved termination device shall be used for each neon electrode. To relieve stress at terminations, tubing shall be supported with listed tube supports in an approved manner within six inches of electrode connection. CEC 600.41 & 600.42 5. Every electric sign of any type shall be listed by an approved testing laboratory and shall be installed in conformance with this listing. That includes "1 of x", "2 of x" labeling for each separate unit of a multi-unit sign. CEC 600.3 6. All "can" letters and transformers housings shall have section labels that are readily visible after installation. CEC 600.4 7. Transformers shall be located where accessible and be securely fastened in place. Page 1 of 2 When not inside the sign, they need a 3 foot high x 3 foot wide x 3 foot deep workspace. Transformers are permitted to be located in attics or canopies provided there is a passageway at least 3 feet high x 2 feet wide with a minimum 12 inch catwalk/walkway from the point of entry. Transformers must be securely fastened and independent of T- bar when above a suspended ceiling. No part of sign may be fed with flexible cord when located above T-bar ceilings. CEC 600.21(E&F) & 400.8 8. Adequate illumination shall be provided for all working spaces about electrical equipment. This applies to attics and canopies when entry is required to service or inspect the equipment. At least one switch is required at entrance. CEC 110.34 & 600.21 9. Doorway to an attic or canopy space shall be minimum 3 feet by 2 feet wide. CEC 600.21(E) E. Open neon outline or highlight lighting. 1. To be treated as a sign by this department. However, Section D-5 & D-6 of this bulletin will not apply. 2. Neon tubing shall be located where not normally exposed to physical damage. Open neon tubing below 9 feet shall be protected from physical damage by an approved shielding method. CEC 600.30 and 1 10.34(E) F. Light-Emitting Diode (LED) Signs 1. Will be treated as a sign by this department. All sign rules in sections A, B, C, D, F, and G will apply as appropriate. 2. LED illumination for signage must be a listed or recognized component. Many LED manufacturers specify particular brands and models of transformers some do not. Manufacturer information to clarify this issue is required on LED sign plans. 3. Unlisted LEDs may not be used in an electrical sign or as permanently installed illumination. 110.3 4. Please have packaging or catalog cut-sheets on hand for inspector to review when LED modules do not bear listing symbols. G. Inspections 1. Contact an Electrical Inspector one (1) workday (minimum) in advance of installation to arrange a site meeting on dav of installation. 2. Call for inspection Monday through Friday, 8:00- 8:30 a.m. at (714) 647-5821. Approved prints and the job card must be on site for inspection. Page 2 of 2 - 133 SIGN COMPONENTS MANUAL (SAM)October 1, 2013 SINO-OPTO USA LLC, DBA LED LIGHTING SERVICES LLC 3575 COMMERCIAL AVE E342085 NORTHBROOK, IL 60062 LED Tube, Cat Nos. LLIT8-48-18W, LLIT8-24-10W 1. These products are suitable for use in dry, or damp locations. 2. The lamp is maintained not less than 2 inches (50.8 mm) from combustible materials such as wood or plastic and parts that are a source of heat or arcing. Spacing from lampholder to sign housing is zero. 3. This LED lamp is not for use with internally shunted bipin lampholders used with fluorescent instant start lamps. SINO-OPTO USA LLC, DBA LED LIGHTING SERVICES LLC 3575 COMMERCIAL AVE E345360 NORTHBROOK, IL 60062 LED Tube, Cat. No. SN-T. 1. These products are suitable for use in dry, or damp locations. 2. The lamp is maintained not less than 2 inches (50.8 mm) from combustible materials such as wood or plastic and parts that are a source of heat or arcing. Spacing from lampholder to sign housing is zero. 3. This LED lamp is not for use with internally shunted bipin lampholders used with fluorescent instant start lamps. LED Tube, Cat. No. LLI-T10DBL. 1. Manufacturer's name, trade name, or trademark. 2. Distinctive catalog or model number. 3. The electrical ratings. 4. When multiple manufactures are involved, then a Factory ID identifying the product to a particular factory shall be provided. 5. Optional - "For Connection with Class 2 Circuits Only." SLOANLED, DIV OF SLOAN CO INC 5725 OLIVAS PARK DR E215393 VENTURA, CA 93003 LED Modules, Cat. Nos. 701261, 701261-PW, 701340, with suffix -R, -O,-Y, -B, -G, -W or -A; Cat. Nos. 701340-PW with suffix - R, -O, -Y, -A, -B, -G or AN; Cat. No. 701340-CM. 1.These products are only suitable for connection to a UL Listed or Recognized Class 2,24 V dc power source for Model 701340 and 7.5 V dc or 5 V dc power source for Model 701261. 2.These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3.The total number of Model 701261 LED Lighting Units are not to exceed a total of 75 units per Class 2 circuit. The total number of Model 701340 LED Lighting Units are not to exceed a total of 40 units per Class 2 circuit. 4.These products are suitable for use in dry, damp and wet locations. 5.These products are not required to be enclosed or protected from weather. Class 2 LEDs, "ThinLED", Model 701228 , with suffix -A, -B, -G, -R, -W or -Y; Cat. No. 701228-18, with suffix -A, -B, -G, -R, -W or -Y. 1. These products are only suitable for connection to a UL Listed or Recognized Class 2, max. 12 V dc power source. . Only Models 701228-A, -R, or -Y are only suitable for connection to UL Listed or Recognized Class 2, max. 7.5 V dc. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3. The total number of these products when interconnected is not to exceed a total of 14 feet or 14 "ThinLED" units per Class 2 circuit. These products are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations. 5. These products are not required to be enclosed or protected from weather. Class 2 power supply, Model LED Outline Lighting Systems "FlexiBRIGHT", Cat. No. 701499-X-Y, where X and Y may be any alphanumeric character. 1. These products are only suitable for connection to a UL Listed or Recognized Class 2,12 volt DC power source or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3. These products are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply per Class 2 circuit. 4. These products are provided with wire soldered on the printed wiring board for connection. 5. These products are suitable for use in dry, damp and wet locations. Class 2 LEDs, Modules designated, "LED STRIPE2 (Border Light)" and "701956-XXXXXX" series, where XXXXXX may be replaced with alphanumeric characters. 1. These products are only suitable for connection to a UL Listed or Recognized Class 2,15 Volt or less DC power source. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3. Class 2 LEDs, "LED STRIPE2 (Border Light)", is rated max. 48 Watts per module. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations. Class 2 LED Module, Cat. No. 701269-xxx=xxicxx-MB Series, where x)0000000<x maybe blank or any alphanumeric characters. 1. These products have been evaluated only for use when connected to the Class 2 output of a Listed or Recognized power source rated 15 VDC or less. 2, These products are suitable for use in dry, damp and wet locations with supply sources rated at 15 V DC or less. 3, These products are not required to be enclosed or protected from the weather in the end product. 4, These products may be secured in the end product with any available means. 5. These products are rated for a maximum of 7.5 watts or less per module. Class 2 LED Border Light, Class 2 "Border Light", Cat. No. 701 189-XXXXXXXXXX series. October 1, 2013 SIGN COMPONENTS MANUAL (SAM)134 1. These products are only suitable for connection to a Class 2 power source, rated 30 Volt DC or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limits and which is rated greater than 30 V DC. 3. These products are each rated max. 100 Watts per unit. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations when rated maximum 30 VDC. 5. These products are not required to be enclosed or protected from the weather in the end product when rated 30 VDC or less. 6. These products may be secured in place in the end product by any means available. 7. When these products are used in applications other than signs or outline lighting, the need to conduct a temperature test shall be considered. LED Strips, Cat. No. 701174,701181 and 701195 with suffix -R, -Y, -A, -B, -W, or -G followed by -1" through -24". 1. These products are only suitable for connection to a UL Listed or Recognized Class 2,24 volt AC power source. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3. These products may be cut into segments through a black mark provided on the printed wiring board. No other cut across the board is permitted. 4. Cat. No. 701174 is rated for 4.2 watts per foot, Cat. No. 701181 is rated for 9.2 watts per foot and Cat. No. 701195 is rated at 1.5 Watts per foot. The total number of feet of each type and inches for the inch unit are not to produce a total wattage of greater than 60 watts per Class 2 circuit. 5, These products are suitable for use in dry, damp and wet locations. 6. These products are not required to be enclosed or protected from weather. Class 2 LED Module, Cat. No. 701946-XXYYYYUZZZ series, where XX, YYYYYY and ZZZ may be replaced with any alphanumeric characters or blank. 1. These products are suitable for use in dry, damp and wet locations and supplied only with a Class 2 power source rated 24 Volt DC or less. 2. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 3. These products are not required to be enclosed or protected from the weather in the end product. 4. These products may be secured in place in the end product by any means available. Class 2 power supply, Model 701285. 1. Power supply is intended to power LEDs in signs. 2. Power supply model is intended for permanent connection only. 3. These units are suitable for use in dry location without a need for an additional enclosure and in damp locations when installed inside a sign that complies with the Exclusion of Water Test in UL 48. 4. If the power supply output wiring is extended longer than the 5 foot leads provided, the spliced connections shall be made inside a Listed junction box suitable for the application included with proper grounding. Class 2 power supply, Cat. Nos. 701349, 701351. 1. Power supply models 701349 and 701351 are intended to power LEDs in signs. 2. Power supply model 701349 and 701351 are intended for permanent connection only. 3. These units are suitable for use in dry location without a need for an additional enclosure and in damp locations when installed inside a sign that complies with the Exclusion of Water Test in UL 48. 5. These power supplies have two outputs. The Class 2 output circuits are not to be conductively connected to each other in the sign by wiring or other type of component. 6. The maximum rated output power for Model 701349 is 42 watts at each Class 2 output. The maximum rated output power for Model 701351 is 60 watts at each Class 2 output. Class 2 power supplies, Models 701507-MOD, 701507-MOD277 (AD060S277/347-SLN). All may be followed by alphanumeric sumx. 1. These power supplies have a maximum of one Class 2 output. The output of these power supplies has been evaluated to Class 2 output requirements for dc circuits. 2. These products with Class 2 outputs are suitable for use in dry, damp and wet locations. 3. In the end product, power supply spacing to other heat producing components shall be minimum 4 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 4. When used in wet locations, each unit shall be provided with Listed (QCRV) 1/2 inch, liquid tight conduit fittings on primary circuit. 5. When used in a cord connected product, the need for conducting a leakage current test shall be considered in the end product. 6. When not marked for Dry and Damp Locations Only the power supply primary bracket shall be provided with min. 3.5 threads and maximum 5 threads tapered for connection to liquid tight conduit fitting. If less than 3.5 threads, the liquid tight shall be provided with watertight fitting Listed (QCRV) 1/2 inch, liquid tight conduit fittings. 7. The suitability of grounding connection shall be determined in the end-use product. Class 2 power supply, Model 701680. 1. The product shall be installed in compliance with the mounting, spacing, casualty, and segregation requirements of the ultimate application. 2. These units are provided with a Class 105(A) insulation system. 3. The suitability of the input and output connections shall be determined in each end use application. 4. These power units are intended for dry or damp location use only. 5. Strain Relief on input lead construction and Impact Tests have not been investigated. 6. The polymeric enclosure of each unit has not been evaluated as ultimate enclosure. The flame class of polymeric enclosure of each unit is V-2, and the necessity of additional fire barriers shall be determined in end product. 7. Multiple power supplies shall be spaced at least 25mm (1 in.) end to end or 102mm (4 in.) in other directions. If lesser spacings are used, then the Temperature Test shall be conducted in the end use product. For reference the maximum enclosure (case) temperature on the power supply was 90°C when tested at 58.4° ambient. Class 2 power supply, Model 701680-MW. 1. These power supplies have been evaluated to Class 2 output requirements for dc circuits with a maximum of one Class 2 output. 135 SIGN COMPONENTS MANUAL (SAM)October 1, 2013 2. The load powered by the Class 2 output of the power supplies rated at max 30 VDC or less are suitable for use in dry, damp and wet locations. 3. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 4. These products are provided *tl t[}e_ following electrical ratings: Input Output Model Vac | A Hz Vdc A 701680-MW 100-240 | 0.55 50/60 12 1.67 5. These products shall be enclosed in the end product. 6. These power supplies are suitable for use in dry and damp locations. Class 2 power supply, Model 701681. 1. The product shall be installed in compliance with the mounting, spacing, casualty, and segregation requirements of the ultimate application. 2. These units are provided with a Class 105(A) insulation system. 3. Input leads are Style 1015, No. 18 AWG, rated VW-1, 600 V, 105°C. Output leads are Style 1430, No. 18 AWG, rated VW-1, 300 V, 105°C. The suitability of the input and output connections shall be determined in each end use application. 4. These power units are intended for dry or damp location use only. 5. Strain Relief and Impact Tests have not been investigated on input lead construction. The suitability of the enclosure as ultimate enclosure shall be determined in the end-use application. 6. The polymeric enclosure of each unit has not been evaluated as ultimate enclosure. The flame class of the polymeric enclosure is V-0 and the necessity of additional fire barriers shall be determined in end product. 7. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. Class 2 power supplies, Model 701495. 1. These power supplies have been evaluated to Class 2 output requirements for dc circuits with a maximum of four Class 2 outputs. 2. These power supplies are only suitable for use in dry, damp and wet locations. 3. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. Class 2 power LED Lighting Strip, 701912-QQXXYYZZZ series, where QQ represents length, XX represents the LED color temperature, YY represents configuration and ZZZ represents the LED drive current. 1. These products are only suitable for connection to a Class 2 power source, rated 24VDC. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limits and which is rated greater than 24VDC. 3. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated class 2. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. These products may be secured in place in the end product by any means available. 7. When these products are used in applications other than signs or outline lighting, the need to conduct a temperature test shall be considered. Class 2 "Dimming Control Knob" potentiometer, Model 701843. 1. These products are only suitable for connection to the output of a UL Listed or Recognized Class 2 power supply rated max 12 VDC. 2. These products are suitable for use in dry and damp locations. 3. These products are suitable for factory wiring only. 4. These products are 1 Kohm potentiometers intended for connection to max 12 VDC Class 2 power supply that drops the voltage to a 0-10 V signal to feed into the PWM dimmer. Class 2 LED Modules, Cat. No. 701960-XXYYYZ Series, where XX, YYY, and Z may be replaced with any alphanumeric character or blank. 1. These products are suitable for use in dry, damp and wet locations and supplied only with a Class 2 power source rated 24 Volt DC or less. 2. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 3. These products are not required to be enclosed or protected from the weather in the end product. 4. These products may be secured in place in the end product by any means available. Class 2 power supplies, Models 701507-60W1-JV and 701507-60W1-CT. 1. These power supplies have been evaluated to Class 2 output requirements for dc circuits with a maximum of one Class 2 output. 2. These products are provided with the following electrical ratings: Output Output Frequency Voltage Current Model Number Input Voltage (V)Input Current (A)(Hz)(Vdc)(mA) 701507-60W1-JV,100-240 0.85 50/60 12 0-500 701507-60W1-CT 3. In the end product, power supply spacing to other heat producing components shall be at least 25.4 mm (1 in) from end to end and 101.6 mm (4 in) from side to side. 4. These products shall be enclosed in the end product. 5. These products are suitable for factory wiring only. 6. These products are intended for use in a dry or damp locations only. 7. The suitability of input/output leads and the wring shall be determined in end product use. SPARTECH PLASTICS E202184 Goo 04 Me 6 . C 1 9 C 5 g.-1 -53. St . S.ANIA. 44/A CA 9-2 T (13 14 ' f . 1 vt re'.·IM.': 0 · -' ' 4i 1 i i p -'*.li iii 1 ' r·.I··•11 /1 ·u· 91 rl 11·' 2 ! 2 K·.· p ]6:.i & ( 8 1 ..... 11·'• t J..e i.er. A: 1;i .Ill, Jir:,0,hef-k i f 1 '1 A·: 4 n...1 12..:.:':2:-Cam--:run: Ill 0 9,bic..11 190 1,i.4 f Irp·,f 2 ppACE 1 BLEFlit. p; ..e ! SPACED > IS'-c,0 MASTEIR 1.or· 10;>i·i*ir .'l»_/ 1 I r -Lut. .mt-nre. Fpr',le:c·· r·t?.1,1110 ' 1·41,•0129 €•r,9,11<-Erl.. 91*re.14'£,-v, tic #·8:,VE::,I J.. .1 -45-8 +791, 1»84#v, .,/1 ; MM»•14/,' 24.u·r.1., A:C'/N 2·1 z..,u,i >/-:1.:i .1. Jll, .,,,,,D€\k,41&1 --2 '/4,f..)'Avil. ili&10&==4- -9=-a---- -- -.... " 1 ..1 03 1 1 .c. A,•lot - .65·1)' 1 : 1·2, P#./Di ' 6Tg,41/ 9,1 l 1 j.7 .'t, i 8,4 1i ..th 1,12 7 .SPA r>rIAtic, 14 13.,1 :,- ' v cA2 2,-1 K..2. 1 ....... . -- - -I--- FU>00 A{3-(liu,11.4 4,, _.. ...._ Ah.::·. go, (T n 1 COUT,2,4- 5- 4 .t' •0' 9-19 v4 4,4- -· 101 Tl di #wA; ==-16=19=»C=r _ij 4 r L.. PE,7/10* 0, 1'. ·401- 1 \ Ilr-*wr e. BY CAFE.._ 1 .: -2 1 4%·wu*0=¢E-i,. Fart'*P<4013 11,1.-- . LA.lper..ppl,1,·1 -) MMW ·to 1 .ECTIOMREQUIRED --FIN >1'-- edc·. C.0*:8 44<.·; u.ls, 919:.,IA..K .7 Cc,£,ve.-»2-R· . 4 *LITTE£ 'R. =0,14 (714) 644 716U ........ 1 .- --- 2=2127 4 3UBJECT TO ITEMS CHNCKED AN DITIONS & IRETAIN PLANS FOR FUT JRE REVIEel#1.%%4541 24*OVAL /P 6™UET 04•1 #; *12: ---_ -/ .Feep,·01.0 £42, vt .IM'f<W-<4 4'eg900>LA..4, 6 JR' + ·°PA·/20 .PIFWA'UD,»11 rA'15>% 117,< 41-rr ·cr,·10··-f<1·,S -2219 .1.-1 :3ELOW: y O INTERIOR Tl 0NLY :th i1 O NO EXTEHOR ALTERATIONSA ATI0NS O ALL MATERIALS TC MATCH EX .1 U lilli. .1-/J .I·':REENINfz Rmn .-,7-0 ;·. 1.:lutfil firll,21··i' 1 ; 3 .:UBMIT LANDSCAPE PLANS 29 \ 24 7 LAiN#*&,bIvisio V ¥R#NSFE*RED $-=Efft?N-fWINSF 4#ET le (1_ .T,W 940- fla·011.10:'IS: G 8 ' 'i·• 1, 1 '. , El CO H AIDIFI 1 IN 1 33' 1 Boost Mobile: ICell Wireless #2 - Santa Ana, CA No Signage Existing - 19.13 sq ft 0-lf - New Sign 1.. - .00*8 L - 152.50" , 3132-t mob F U 33' * 4 ' i 1 39 4 4 0 0/0 4- 51,1 0 5 ly Avetk IA uqi le 6 4 l.5 $ \1.-75=- 11. 13 It sie ekiecr New LED individual channel letters to be installed on building front. Letters are UL listed. 08 SHEET METAL SCREW PAINT SATIN BLACK - r·-I 3/16' WHITE CHEMCAST BLACK f WIDE TRII*CAP ACRYLIC €- - I 3/4"WIDE BLACK SLOAN ..,WHITE /ORANGE · LED MODULES L_J #3630-84 32 BLACK VINYL#3650-12 3/16" WHITE--D CHEIVICA5T ACRYLIC m. El .040 BLACK COIL PRE-COATAL!:!&--4 LETTER RETURN WELD TO.080·ALUM. BACK ----& L.Vk•-1/4• WEEP HOLES 47*#M/mob!)€f 0 6 , LISTED DISCONNECT SWITCH IN PRIMARY. - POWER SUPPLY - JUNCTION BOX r 1/2' CONDUIT WIRE SHIELD WITH LEADS WASHERS -- #10 PLASTIC ANCH WITH #10%1WX SCREW ·MIN. m PER SIGN. cr HARDWARE SUITABLE FOR FIELD CONDMIONS TYPICAL SIDE SECTION DETAIL NO SCALE Thi. 4.-Ine 1. th. property or SIgnal. US Ind .11 rl'h- to Ite w.. for r.production are etrictly r.lerved by SIgnage US P„on.: 203-440-9419 Drawing Date:10/17M3 Signage Approval Landlord Approval Signature & Date: signoge *F.- 203-630-2780 <%)boost mobile™Drawing Number: P El Approved As Noted /1 Il Approved \AUb: slgnigium.corn Drawing by: MV Not Apploved -revise As Noted 2-- V19 15 bu -1-4T 5-r Boost Exterior Illuminated Channel Letters Without Raceway C WHITE LETTER A B SIZE TM 12'16.63"12" B 18"24.930 18" 24" C 11'55/8" 17'27/13" SM TRNSLUCENT VINYL TANGERINE #3630-84 OVERLAY 22'111/4• WHITE PLEX FACE #GP-016-2 1" WIDE BLACK TRIM CAP WITH #8BLACK METAL SCREWS BOOST EXTERIOR CHANNEL LETTERS WITH ACRYLIC FACE & TRIM CAP EDGES GENERAL SPECIFICATIONS: ONE SET OF INDIVIDUAL CHANNEL LETTERS WITH 3/16" THICK WHITE ACRYLIC PLEX FACES WITH TANGERINE #3630-84 TRANSLUCENT VINYL APPLIED TO THE LOGO. LETTERS TO HAVE 1" BLACK TRIM CAP EDGES. TRIM CAP SCREWS #8 PAINTED SATIN BLACK. SIGN BACKS TO BE.090 ALUMINUM AND RETURNS.063 PAINTED SATIN BLACK. CHANNEL LETTERS ILLUMINATED WITH HIGH OUTPUT BRIGHT WHITE LED'S AND REMOTE POWER SUPPLIES. CLIENT TO SUPPLY ONE (1) 20 AMP 120 VOLT CIRCUIT WITHIN 60"OF SIGN INSTALL AREA. /8 SHEET METAL. SCREW P*IT SATIN BLACK - BLACK f WIDE ™1$(AFFA- SLOAN · WHITEE /ORANGEr- LED MODULES \ LISTED SIGN P'- 120 VAC ZA PRIMARY 12VOC SASECONDARY p LISTED DISCONNECT 4-' SWITCH IN PRIMARY. JUNCTION BOX GENERAL NOTES FOR ELECTRICAL SIGNS:3/16 WHITE CHEMCAST ACRYLIC 3/16- WHrre- CHEMCAST ACRYLIC 1. ALL ELECTRICAL SIGNS WIU HAVE WEEP HOLES IN COMPLIANCE WITH U148 Uy CONDUrT WIRE SHIELD WITH LEADS 3/4"WIDE BLACK TRIM CAP - WASHERS 2 ON SIGNS WITH LIFTING CLIPS, REMOVE CUPS AFTER SIGN INSTALLATION AND REPLACE WI™ HARDWARE TO PREVENT WATER FROM ENTERING AT THESE POINTS..040 BLACK COIL PRE-COATALUIA. | "\-3. ALL ELECTRICAL SIGNS ARE TO BE INSTALLED IN COMPLIANCE WI™ U:48, NEC, AND 3M T GERINE TRANSLUCENTVIN LETTER RETURN - -1,5 PLASUC ANCI. WELD TO.DWALUM. BACK £--¥,TH 1,0,1,1-* SCREW #3630-84 HARDWARE 9JTTA/LE WNFER*5194,0 LOCAL CODES.:le WEEP HOLES -FCA FEID CO,DI11919 4. ALL ELECTRICAL SIGNS WILL BE UL USTED AND HAVE A UL LABEL APPUED TO THE SIGN.TYPICAL SIDE SECTION DETAIL NO SCALE 6. ALL WALL PENETRATIONS TO BE WEATHERPROOFED WITH SIUCONE SEALANT. MATERIAL DETAILS FOR LOGO SIGN NO SCALE signage Luti L 0 R R P.0-: 203-440-9419 Drawing Date: 3/112012 F..: 203-630-2780 Drawing Number 8103113 Wa•: •Ign•eou•·Com 6 Drawing by. RL Signage Approval This drawing Is the property of m Signage US and all rights to its L_] Approved use for reproduction are stricuy m reserved by Signage US. · Ll Approved As Noted .-- A 1- 0 15-0 st - 3&.Boost Mobile: ICell Wireless #2 - Santa Ana, CA 2-41 174 .:7914 New Sign Faces - -. 4• boost 1 '1 i boost mobild Old Sign Faces I INAILSICHCCJI] 8'GUNAILS CHCC-NOTAR¥ UULIC STEM: 1 Illi NOTARY ejulio < 1915 SALON !12fdh - :1915 Remove existing "CHCC" vinyl lettering from sign face on each side of monument sign, clean area, and apply new vinyl graphics supplied to existing faces as shown. Sign face areas measure 16"h x 34"w h;, drawing 1 th- Property Of SIgn'gl US ..d /11 right' to lt' u.. for reproduction .re 'trictly r......d by Sign.gl US Phone: 203-440-9419 Drawing Date:10/17Ml Signage Approvil undlord Approval Signature & Date: signoge (80 F..: 203-630-2780 boostmobile-Drawing Number: P Il Approved El Approved As Noted W.b:.Ign.g....com Drawing by: MV O Not Approved -revise As Nied -1 v l\V V 1 9 1 9 9 LLeT- 9- -1 ti l\)2\ /13 lol@019 9 2 01 9-2 9 77 1 1 1 67 \/U t,I Ral- 49= c_ Ci M m P€ Agency ELECTRICAL , PLAN APPROVAL This set of plans and specifications must be kept or,. the job at all tlmesand It Is unlawful to make any. changes or alterations on same without written per-mission from the Department of Building SafetyCity of Santa Ana. The approval of this plan and specifications SHALLNOT tr. held to permit nor be an approval of theviola, Ir any provisions of ANY City Ordinance 1.63 1.09 e00000uit breaker( 1 A local disc 046005\00 .red or or above any power supply ifrorA 509 500-Pwith a2x3 foot accessne>ve.\ 099 b.0eli PERMIT TYPE: .<BLD E-LBG MECH GRADING PERMIT#10\90 \64 / OCC. GROUP _%?Af:*cr761 CONSTR. TYPE CODE EDITION RE) rc) FLOOD ZONE FLOOD ZONE CERTIF. REQ'D YES /146- 1or State Law. -. MICROFILM . =YES hgoh.. Api-1NEEn;2 \ \ \¢5 - RADIANT BARRIER @ ROOF YES /N(f liTY OF SANTA ANA * , ,DEPARTMENT OF BUILDING SAFETY 'RESIDENTIAL DEV. FEE YE< NO SCHOOL DISTRICT YE*., L ty of Santa Ana. CBC & CEC 2410 inimum (4) screws per letter, aximum 24" on center, £ ,netration, #10 sheet metal screws, & , 1 ¥4" drain holes per letter