HomeMy WebLinkAbout10180173_131 E. MEMORY - Plan19 I Planning & Building Agency Building and Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org ELECTRICAL SIGN REQUIREMENTS Code references are to the 2010 California Electrical Code (CEC) A. All signs require Planning Department appreval. B. All electrical signs require electric plancheck and permit. 1. Manufacturer's instructions are required at the time of submittal. C-11: 3-21-2011 2. Submit detailed installation instructions including diagrams to the Building Department for plan review at the time of submittal. Plans must include appropriate items noted by this bulletin. 3. Cash or surety bond in the amount of $200.00 is requited at time of issuance for each address. The cash or surety bond will be refunded after all required finals. C. A building permit is also required - except for open or highlight neon lighting. D. Installation Requirements: CONTACT FIELD INSPECTOR PRIOR TO SIGN INSTALLATION. (SEE SECTION G OF THIS BULLETIN) 1. Conductors and equipment shall comply with California Electric Code Article 600. 2. All metal parts of a sign shall be bonded in the manner specified in Article 250. Isolated metal parts are permitted to be bonded by using an external green insulated conductor. Equipment grounding & bonding conductors must be sized by 110.26 and protected from physical damage. Minimum size is 14 AWG. CEC 600.7 3. A listed disconnect switch in the power supply primary, shall be installed within sight of sign or have permanently installed means for locking in an "OFF" position. This is also true for a transformer enclosure. CEC 600.6 4. A listed receptacle or an approved termination device shall be used for each neon electrode. To relieve stress at terminations, tubing shall be supported with listed tube supports in an approved manner within six inches of electrode connection. CEC 600.41 & 600.42 5. Every electric sign of any type shall be listed by an approved testing laboratory and shall be installed in conformance with this listing. That includes "1 of x", "2 of x" labeling for each separate unit of a multi-unit sign. CEC 600.3 6. All "can" letters and transformers housings shall have section labels that are readily visible after installation. CEC 600.4 7. Transformers shall be located where accessible and be securely fastened in place. Page 1 of 2 __1 When not inside the sign, they need a 3 foot high x 3 foot wide x 3 foot deep workspace. Transformers are permitted to be located in attics or canopies provided there is a passageway at least 3 feet high x 2 feet wide with a minimum 12 inch catwalk/walkway from the point of entry. Transformers must be securely fastened and independent of T- bar when above a suspended ceiling. No part of sign may be fed with flexible cord when located above T-bar ceilings. CEC 600.21(E&F) & 400.8 8. Adequate illumination shall be provided for all working spaces about electrical equipment. This applies to attics and canopies when entry is required to service or inspect the equipment. At least one switch is required at entrance. CEC 110.34 & 600.21 9. Doorway to an attic or canopy space shall be minimum 3 feet by 2 feet wide. CEC 600.21(E) E. Open neon outline or highlight lighting. 1. To be treated as a sign by this department. However, Section D-5 & D-6 of this bulletin will not apply. 2. Neon tubing shall be located where not normally exposed to physical damage. Open neon tubing below 9 feet shall be protected from physical damage by an approved shielding method. CEC 600.30 and 110.34(E) F. Light-Emitting Diode (LED) Signs 1. Will be treated as a sign by this department. All sign rules in sections A, B, C, D, F, and G will apply as appropriate. 2. LED illumination for signage must be a listed or recognized component. Many LED manufacturers specify particular brands and models of transformers some do not. Manufacturer information to clarify this issue is required on LED sign plans. 3. Unlisted LEDs may not be used in an electrical sign or as permanently installed illumination. 110.3 4. Please have packaging or catalog cut-sheets on hand for inspector to review when LED modules do not bear listing symbols. G. Inspections 1. Contact an Electrical Inspector one (1) workday (minimum) in advance of installation to arrange a site meeting on day of installation. 2. Call for inspection Monday through Friday, 8:00- 8:30 a.m. at (714) 647-5821. Approved prints and the job card must be on site for inspection. Page 2 of 2 October 1, 2013 SIGN COMPONENTS MANUAL (SAM)146 1. These power supplies have been evaluated to Class 2 output requirements for dc circuits with a maximum of one Class 2 output. 2. These products are provided with the following electrical ratings: Input Output Output Input Input Current P0wer Voltage (V Output Power Model No.Voltage (V)Freq (HZ) (A) Factor dc) Current (A) (W) LCU 060/12 D 120-240 50/60 0.75 0.95 12 5.0 60 LCU 035/12 0XX 120-240 50/60 0.39 0.95 12 2.92 35 LCU 015/12 D 120-240 50/60 0.35 0.4 12 1.25= 15 3. In the end product, power supply spacing to other heat producing components shall be at least 25.4 mm (1 in) from end to end and 101 6 mm (4 in) from side to side. 4. These products shall be enclosed in suitable electrical enclosure in the end product. 5. These products are suitable for factory wirihg only. 6. The load powered by the Class 2 output of these power supplies at the 12 Vdc rating or less is suitable for use in dry, damp and wet locations. 7. These products have been tested in oven at 50°C ambient, with the following maximum case temperatures, T, For model LCU 060/12 D the Tc = 82°C: for model LCU 035/12 D XX the Tc = 64°C; for model LCU 035/12 D XX the Tc74°C. 8. These products are intended for use in a dry or damp locations only. 9. The suitability of inpuUoutput leads and the wring shall be determiAed in end product use. 10. The metal case of Model LCU=015/12 D is not grounded. The proper grounding means of this product shall comply with the end product requirements. Class 2 LED modules Models P541-CLA, P551-SEL. 1. These products are only suitable for connection to a Class 2 power source rated 14 V DC or less. 2. These products are intended for use only when connected to a power source that complies with Class 2 voltage and energy limited circuit and is rated at 14 V DC or less. 3. When these units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at 14 V DC or less. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. These products may be secured in place in the end product by any means available. TRONICC TECHNOLOGIES E357992 18584 BUDGE PIERREFONDS, QC H9K1 K8 CANADA Sign accessories, Class 2 LED modules, TT-M-01, TT-M-02, TT-M-03, TT-M-04,1-T-8-01. 1. These products were evaluated for connection to a UL Listed or Recognized Component Sign Accessory - UYMR2, Class 2 source. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limiting requirements. 3. When these units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry and damp locations. 5. Consideration for the installation and power supply connection and interconnection is to be determined in the end-use application. TUBE LIGHTING PRODUCTS E348777 1346 PIONEER WAY EL CAJON, CA 92020 Class 2 LED Strip, Model DSH Series. 1. These products are intended for use only when connected to a power sourcei that complies with Class 2 voltage and energy limited circuit and is rated less than 24V DC. 2. When these units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 3. These products are suitable for use'in dry, damp and wet locations. 4. These products do not require an electrical enclosure. 5. These products may be secured in place in the end product by any means available. U S LED LTD E226833 6807 PORTWEST DR HOUSTON, TX 77024 Class 2 LED Module, Model MY-12-K-XX "MegaX" Series, where Y may be replaced by any number from 0 to 99 ind., K may be replaced by W, R, B, Y, G or RO and XX is optional, where it may be replaced by any alphanumeric characters.(0 to 99 ind. or A to Z incl. or combinations). 1.These products are only suitable for connection to a Class 2 power source, rated max 24 Volt DC or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited circuit. 3. These Class 2 LED Modules are each rated 0.77 Watts per unit. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at 12 Volt DC or less. When rated 24 VDC, these products are suitable for dry and damp locations only. 5. These products are not required to be enclosed or protected frorri the weather in the end product. 147 SIGN COMPONENTS MANUAL (SAM)October 1, 2013 LED Accent Module, Mega, Accent or Right Light Series, Model Q ABC-XX-YY-ZZZZ series, where Q may be P, M, AC or blank; AB, XX and YY may be replaced by any alphanumeric characters (0 to 9 incl. or A to ZZ incl. or combinations); C may be blank or may be any alphanumeric characters (0 to 9 incl, or A to Z incl. or combinations); and ZZZZ may be any alphanumeric characters (0 to 9999 incl. or A to ZZZZ incl. or combinations) or blank. 1. These products are only suitable for connection to a Class 2 power source, rated max 24 Volt DC or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited circuit. 3. These Class 2 LED Modules are each rated 0.77 Watts per unit. When units are connected toj a Class 2 circuit, they are not to draw a total wattage of greater than tile secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at 12 Volt DC or less. When rated 24 VDC. these products are suitable for dry and damp locations only. 5. These products are not required to be enclosed or protected from the weather in the end product. LED Accent LED module, Model AC-X-Y-Z-T, where X is the length of the module, Y identifies the operating voltage, Z identifies the color, and T identifies a standard 1. These products are only suitable for connection to a UL Listed or Recognized Class 2, max 30 Vdc only power source. 2. These products have not been evaluated for use when connected to a power source that does. not comply with Class 2 voltage and energy limited supplies. 3. These products are not provided with break points in the printed wiring board. No cuts across the board is permitted. 4. These products are suitable for use in dry, damp, and wet locations. 5. These products are not required to be enclosed or protected from weather. Right Light Series LED module "Right Light';, Models TP-2- 12-z, abc-X-Y-Z and RLS-X-Y-Z, where X may; be any number from 0 to 9, Y may be any number from 00 to 99, and Z may be any alphanumeric character. 1. These products are only suitable for connection to a UL Listed or Recognized Class max. 24 VDC power source. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3. These products are not provided with break points in the printed wiring board. No.cuts across the board are permitted. 4. These products are suitable for use in dry, damp, and wet locations. 5. These products are not required to be enclosed or protected from weather. LED Driver Enclosure, Model Life Extender Box. 1. This product has been evaluated for Dry and Damp Locations only. If used in a wet location, Rain Testing shall be conducted durihg the end product evaluation. Class 2 LED Module, Models EXSA-1-6, EXSA-1-12. 1. These products are intended for use only when connected to a power source that complies with Class 2 voltage and energy limited circuit and is rated less than 24V DC. 2. When these units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 3, These products are suitable for use in dry, damp and wet locations with supply sources rated at 12hVolt DC or less. When rated 24 VDC, these products are suitable for dry and damp locations only. 4. These products do not require an electrical enclosure. The 24Vdc modules require protection from the weather in the end product. as they are not suitable for wet locations. The 12Vdc modules require no such protection. 5. These products may be secured in place in the end product by any means available. Class 2 LED Module, Models Tandem XX and Tandem XX Dual, where XX, a non-safety related designation, may be any alphanumeric character. 1. These products- are intended for use only when connected to a power source that cemplies with Class 2 voltage and energy limited circuit and is rated less than 24V DC. 2. When these units are cohnected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 3. These products are suitable for use in dry, damp and wet locations with supply sources rated at 15 V AC or 30 VDC max. 4. These products do not require an electrical enclosure. 5. These products may be secured in place in the end product by any means available. Class 2 LED Module,"BEV series, designated as Models BE1-W-XY-ZZ series, Where W may be any number from 0 to 9, X may be any number from 0-9, Y may be L or Hand ZZ may be any two digit number between 0-9. 1. These products are only suitable for connection to a UL Listed or Recognized Class 2 power soufce with max. 24 VDC. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3. These products are provided with break poihts in the printed wiring board. No cuts across the board are permitted except where indicated in the installation instructions. 4. These products are suitable for use in dry, damp, and wet locations. 5. These products are not required to be enclosed or protected; from weather. 6. These products may! be secured in place iin the end product by any means available UNILUMIN GROUP CO LTD E330828 BLDG A, 112 YONGFU RD QIAOTOU, FUYONG TOWN BAOAN DISTRICT SHENZHEN, GUANGDONG 518103 CHINA Changing Message Signs, Model P16. 1. Maximum of 2 units when installed in a 15 Amp branch circuit and 3 units for a 20 Amp branch circuit. 2. This product was tested for use at a room ambient temperature of 25°C. Testing was conducted on an open bench positioned in a vertical position facing horizontally. The need for conducting temperature testing in the end product shall be considered where the units are installed in a higher ambient. 3. The suitability of the mounting means shall be determined in the end use. - CHANNEL LETTER LIGHTING INSTALLATION GUIDE E226833 E230624 241793 TIO 1 LED Alwavq the Rinht Chair»1 INSTALLATION GUIDE t 9 1, LED UGHTING WARNING • Installation must only be performed by a licensed electrician. • To prevent death, injury or damage to property this product must be installed in accordance ta Na- tional Electric Code in the US or Canadian Electrical Code (CSA22.1) in Canada. 0 US LED Chanhel Letter modules are only to be used with the 12VDC power supplies listed in this:guide. INSTALLATION INSTRUCTIONS 1. Lay out the modules like neon, only without double-backs, approximately 2-4 per:foot, depending on the mod- ule type (see Figure 1 for spacing modules center-center). Be sure to test your first:letter to make: sure you are satisfied before proceeding. Figure 5: Module spacing Module Sefies ..Approximate , C@htef -. Cdnilr Module Scritis. App**Imde Cente, 1· dehter Right Light -2 Up 4" -:5"Point3 5· Flight Light - a Up 5' - 6"Saver3 5" Tadpole) 6." 3" Quas,3 5• Tadpo163 4" 2 2. For power supply loading, see Page:5 or follow this link: :www.usled.com/channel_letter_loading.htm. 3. Install length of product in letters by fastening mounting clips with VHS tape (supplied) or mechanically through holes in the clip, or both. Add silicone for additional security if desired (see Figure 2). Figure 2: Example lay@ut Z -EDI 1=1 2 L V ausHIG - CLASS 29!RE LED MODULES /4$. R. t Ri- bE=52:==R40el-El».r,:«,_- f t.' 4. Connect separate runs of product within a letter using Quick Connect jumper wires with pre-crimped connec- tors. These wires come in pairs of Blue (negative) and Red (positive). Simply connect one negative tab at the end of any module on one run to a negative tab at the end of any module on the second run. Then repeat pro- cess connecting a positive tab on one run to a positive tab on the other (Figures 3 and 4). See Wiring Diagram, on Page 5 for further details. Figure 3· Example power iump Figurel4: Connecting moduleswith Quck Connect Jumper Wires Na-gative Jumper f ru,-AMS=/1977.25 'ositive Jumper telte Bireib Page 2 Undated 05,19.11 US LED 1 6807 PORTWEST DR I HOUSTON. TX 77024 1 T 866 972 9191 1 F 713 972 9393 1 Info@usled. com 1 www.usled.com CHANNEL LETTER I l 13 (/1 f 1.4 flf.) M (Hj i i }*. 1..,f l) !.lut']1jjl1(, INSTALLATION INSTRUCTIONS (cont) 5. The 36" Quick Connect jumper wires with class. 2 wire should be used to connect modules from letter to letter, 'while: the 5-Foot Whip is to be used to connect a run of modules to a power supply (See Wiring Diagram on Page 5). Although jumps can b.e made from letter Lo letter and then h·om the final letter to the: fewer supply. the preferred method is to run each letter to the power supply. The secondary wires on the power supplies are color coordinated to match (Blue for negative atnd Red for positive or Black for negative and Yellow for positive on older products). All runs through a wall must either be in a conduit or "pass-thru" or be made with class,2 wire·. See Figure 5 for an example installation. Figure,5: Example layout, SECONDAR'i WIRING Wl FLE,<lai. OR CLASS LWIPE MCUT CONDI:11 CONDUIT 7 1 PRIMAR·f WIRING 1--•- 1 4,·.NSFCHMER ····iN CHA /1/¢t Ll'R CHANNEL CrR CHANNEL UR rOP VIEW OF 901RING EXAMPLE FOR 8EHIND WALLOR AN RACEWAY .040 ALUM. RETURNS-7 .040 ALUM. RETURNS -r= BUSHING P' TRIM --- / f BUSHING - 4OMB" PLEX --- • i- TRANSFORMER SECONDARY Fl WIRINGi ...TRANSFORMER 1- TRIM - 91 1 CAN -TRANSFORMER bSECONDARY WIRING BUSHING -- ·--- W* FLEX]BLE CONDUIT OR CLASS 2<WIRE -PRIMARY WIOUT CONDurr WIRING3/16" PLEX·--I - PASS-THRU 7"X 7" RACEWAY LED MODUI.ES APPLIED --·# W/DOUBLE·SIDED TAPE OR MECHANICALLY FASTENED LED MODULES APPLIED 2 WI DOUBLE·SIDED TARE OR MECHANICALLY FASTENED Limit the total number of modules per run to 1/3 of the total power Supply load. This will increase your load: bal- ance and light uniformity. FOr example: using the Quasar (QZR-6-12-W) on a 60W power supply, you would limit the total number of modules on each run to 26 (or 13: feet) and connect at the midpoint. 6. Repair and seal any unused openings in the rain enclosure. Openings greater than 1/2i inch diameter require a metal patch secured by screws er rivets and caulked with hon-hardening caulk. Smaller openings may be sealed with non-hardening caulk. 7. Attach channel letter face(s). 8. Energize sign. ULED Page 3 Uadaria 0519.1 1 US LED 1 6007 PORTWEST DR I HOUSTON, rx 77024 I r 886 972 gigi i F 713 972 9393 1 Info@usled com www.usled.cornAlwavs the Riaht Chnice!1 .b:An' 12.,0- .My F ·; CHANNEL LETTER Right Light Series Tadpole Series MegaWhite Series Feet·/12W Feet·/ 6OW -Feet / 1.?W Feat /,603% , ' ' . .. -- . Feet /.12W Feet /.BOW1.Model Number· ·Min Max· •Min· 'Max' ;Model Number ' i'Min ' Max ' Min _. Mar M»de'l Numtrer' ' Min·, Max·, · Min · ·· Max-· RLS-2-12-RX 15527 TP-2-12-RX 1 4 4 20 OZR-6-12-W 2 8 7 -11 P SVR-2-12-RX 2 10 9 52 TP-2-12-0 1 4 4 20 RLS-3-12-RX 2 8 7 R TPL-2-12-G 2 8 7 41 P SVR-3-12-RX 3 15 14 78 TPL-2-12-8 2 8 7 41 RES-2-12-0 2 6 6 '33 TP3-2-12-W 1.5 6 5 30 RLS-3-12-0 2 10 9 50 TP]-2-12-6W 1 4 3 20 RLS-2-12-Y 2 6 6 33 RLS-2-12-G 2 11 10 55 RLS-2-12-8 2 11 10 55 PI-3-3-12-W 2 6 5 30 PLO-3-12-W 4 10: 10 50 SV3-3-12-W 2 9 8 45 WIRING DIAGRAM Output (+129) -f?.3!!5.9..(.Ef.?j...... Rosi#ke fRed) 5·Foo;Wn,0 7, 48¥u tal'Ae)Netiati·.42 (Bilm)12\ZDC Power Supply. 12W or 60W Q.utput Input: 120V for PSA-12-12. P 3A-12-60 1209-2,77V Cor PSA-12-€0/ Posilive )Red)*11@110.'FR (Blue) Channel Leiter./1 2 1 -u,---r.& 22·ru.jel gemej/'11.-6/ ' CE-ELOe-'mvERCE* Jumpert'Ara,3$28'Nife 26.ave(Red)Noga'i·.e ABI,in) •im. 1 .·L,/,/NISNE**11@ _p EJ®101**@liE -67:&:2-332/6-17 Channel Letier #2 lili ,,5 .'Iii, •11 Vh, j 'f:.Ilivemud)"1;1/1..!IB . 1 ===T -c&.al-f-4316_lei-(Culemar.®119- -'r>=-SE»'TE E ]529*KE=ellE>-2=*&. .-1-1- . Elijoi@ Page 4 U,daial 05 19:11 US LEO 1 6807 PORTWEST DR HOUS'TON. EX 77024 1 T 866972 9191 1 F 713 972 9393 1 mfolusted com ' www. usled.connAlwavs the Riaht Choice!E-:73 7. Tri--TWITY.F·-75,0=-9-rp"•-•77•-=·.e.-:-r--m-·-·· =-·..... .. S= iL Ir 11 INSTALLANON GUIDE LEI) LIGHTING TROUBLESHOOTING 1Symptpin 3.'.·.···. .''Podsible.Cause . Ai single module not lighting Malfunction on module Leave malfunctioning medi.lie in place. Mount replacement module alongside in.i using iumper wires, cormect the positive tab to the pc tive tab of any mocule on the r.in. Do likewise with the negative tab. LEDs nicker A. Underloaded or overloaded A. Adjust loads' on power sources to be within recommended limit&. B. Malfunctioning power sburce B. Replace power source. Entire product run is not lighting A. Bari wife connections A. Restofe connection. B. If only one run of product on' power B. Check power source and replace if appropriate. souice, malkincricning powei source C. Shon D. Overload C. Search wir,ng for a short circuit between the red and blue;wires. Replace bao wiring or userelectrical tape to insulate the bad wire(s). D. Adjust loads on power sources to be within recommended limits T Page.5 Uoda[ea 05.19.11 US LED 1 6807 PORTWEST DR 1 HOUSTGN. TX 77024 1 T 866 972 9191 1 F 713 972 9393 1 frio@usled,com www.usled.comAlwavq the Richt Choice! 11 1 APPROVED PLANNING DIVISION [Gk Memory Lane Santa Ana CA MASTER\. D._78/5-//1.05- ....Metro signs, Inc. 31' -- -IWF 2675 Skypark Dr. Un,t 302BACK SOUTH ELEVolON 88#1 Torrance, CA 90505-4' high Letters-S'95 Lic 984884 626-818-4329< -- PLANNER_tg--9=9-DAT#LOr-JTRANSFERREciBY 1,\1 31'13€ 1-1*&,nhmed clwmil latt, wai*.LANNING I CTION REQUIRED: ' P--·•-, ...M .Ala/#*A'INI18" I©GE[E[E ®@108[2 'tpGH------FINAL .NONE 1 . aosIMP#ive**mi k I___*••mk IAME- tr-0· R\N CHAKIA LETTERS WIED 1 r.f MA ORF 10' 14 CURRY HOUSE b 21 NS 3!TIONS -Vi 1 1, 1/lillil YPICAL UL CHANNEL LETTER NSIALLATION METHOD13-6, h THMEi-oNbug wai *f *010*4 0% 2 WA< i 964 1 6 LETTER STYLE.CURR HOUSE -7-/ RESERVOR GRU4GIE IRM BLACK RETIRN BLACK BUE COLOR RED#27934--Ave**m IT Japanese Clrry &__ tr-4 InN CHANE- LETTERS W/LED Charter ITC * TRM BLACK - RETLRN BLACK EACE COLOR WHTE W/BLACK TRIM le[CURRY '3 2 7 8 5\9 LISTED 1 CHANVEL LErnER 6 EXIS™ALL 2 PLASTIc FACE 7 12V CABLES 3 #10 scREws 8 f*4.5 W SCREWS & ANCHORS . 4 +ED LIGHTS 9 12VPOWER MIT 5 TRN CAP 10 TANSFORIER BCK Wl DISCON€CT SVETCH ALL WORK S DONE N 2010 CALIFORNA BLLDING AND 2010 ELECTRICAL CODE 10 1 90194/A)\-52)»L 16\ 6- Meah-opi LE \Sjisconnect for the monument sign(s)musti or the dedicated circuit breaker(s)ridually lockable in the off position. Jo-6is to any power supply in attic or aboveg shall be immediately from a ladder or a 2 x 3 foot access door & passage with a . ..,·,11<way.CEC 600-Agency ' City of Santa Ana. CBC & CEC 2010 Minimum (4) screws per letter, maximum 24" on center, 2" penetration, #10 sheet metal screws, & (2)_4. drain holes py letter retpaA" -be indi, ceillrr 12-incn wc....of Santa Ana Planning & Buiiwit. - - C\W ELECTRICAL + PLAN APPROVAL 4 j This sat of plans and speclficatlong must be kept on the job at all times and It Is unlawful to make any i changes or alteratlons on same without written per- 1 mission from the Department of Building Safely City of Santa Ana. The approval of this plan and speclficatlons SHALL NOT,@&.tpld to permit nor be an approval of the vioiane:Cor any provisions of ANY City Ordinance or State Law. „ Approv by42(-tt ' CITY OF SANTA ANA| DEPARTMENT OF BUILDING SAFETY 1 Il - PERMIT TYPE:(BELE PLBG | MECH GRADING f PERMIT#1(3 1 5tb 1 /7-6 / OCC. GROUP..cab \ JA soc-)4- CONSTR. TYPE_---I..---* CODE EDITION-620\/0 FLOOD ZONE- FLOOD ZONE CERTIE REQ'D YES<\ MICROFILM YES -48/ RADIANT BARRIER @ ROOF YENO RESIDENTIAL DEV. FEE YES»C-i SCHOOL DISTRICT YES NO I M- faS--22.242*636i;*444*775 162- \O- 6 \A GB