HomeMy WebLinkAbout1410 N Parsons Pl - 20181873 – DL- need V1 & V3 - 20181873 - PlanCOORDINATES:
33.757323, -117.932011
KINGSTON RESIDENCE
NEW PHOTOVOLTAIC SYSTEM
PROJECT - 3.555 kW DC /
3.800 kW AC
SHEET #
T-1
T-2
PV-1
PV-2
PV-3
E-1
E1.1
E-2
S-1
S-2
S-3
S-4
S-5
SHEET NAME
COVER SHEET
PLAN NOTES
SITE PLAN LAYOUT
ATTACHMENT DETAILS
MOUNTING DETAILS
ELECTRICAL CALCULATION
ELECTRICAL DIAGRAM
WARNING LABELS
SPEC SHEET
SPEC SHEET
SPEC SHEET
SPEC SHEET
SPEC SHEET
SHEET
CONTRACTOR
SOLGEN CONSTRUCTION LLC.
1410 N PARSONS PL,
SANTA ANA,
CA 92703
APN:10046201
DATE:11/2/2023
KINGSTON
RESIDENCE
License#: C-10 1053344
ADDRESS: 2072 N MAIN ST
FL 2, LOGAN
UT 84341-1993
CSLB#: 1053344
DESIGNER: OAV
CORE ENERGY GROUP.
T-1
TYPE OF
INTERCONNECTION: BACKFEED BREAKER IN THE MSP
SCOPE OF WORK
SYSTEM SIZE:STC: 9 X 395W = 3.555kW
PTC: 9 X 368.7W = 3.318kW
(9) JA SOLAR JAM54S31-395/MR (395W) MODULES
(1)TIGO EI TSI-3.8K-US INVERTER
(9)TIGO TS4-A-O PV OPTIMIZERS
(1)60A KNIFE AC DISCONNECT
(1)100A PV LOAD CENTER
MSP UPGRADE:NO
MAIN BREAKER DERATE: NO
RACKING & MOUNTING
PV ATTACHMENT TYPE: UNIRAC FLASHLOC FOR COMP SHINGLE ROOF
RACKING TYPE: EVEREST CROSSRAIL- ROOF
MOUNT RACKING HARDWARE
PROJECT INFORMATION
PROPERTY OWNER
NAME:ROBERT KINGSTON
PHONE:-
CONTRACTOR
NAME:SOLGEN CONSTRUCTION
PHONE:(559)442-9887
DESIGN SPECIFICATIONS
OCCUPANCY: R-3
CONSTRUCTION TYPE: SINGLE FAMILY RESIDENCE
ZONING: RESIDENTIAL
GROUND SNOW LOAD: 0 PSF
WIND EXPOSURE: C
WIND SPEED: 110 MPH
APPLICABLE CODES & STANDARDS
2022 CALIFORNIA RESIDENTIAL CODE (CRC)
2022 CALIFORNIA BUILDING CODE (CBC)
2022 CALIFORNIA MECHANICAL CODE (CMC)
2022 CALIFORNIA ELECTRICAL CODE (CEC)
2022 CALIFORNIA PLUMBING CODE (CPC)
2022 CALIFORNIA ENERGY CODE (ENERGY)
2022 CALIFORNIA GREEN BUILDING CODE (CALGREEN)
2020 NATIONAL ELECTRICAL CODE (NEC)
2022 CALIFORNIA FIRE CODE (CFC)
AERIAL VIEW
EXISTING PV SYSTEM :
DC SYSTEM SIZE:- 2.000 kW
AC SYSTEM SIZE:- 1.800 kW
COMBINED PV SYSTEM :
DC SYSTEM SIZE:- 5.555 kW
AC SYSTEM SIZE:- 5.600 kW
Signed: 11/08/2023
Structural
Only
The scope of the plans is for the installation of the
solar photovoltaic system only and the approval is
subject to compliance with all applicable city and
state codes and regulations regarding construction.
The approval of the plans does not constitute any
certification of the accuracy, completeness, or
building permit status of the existing buildings and
structures as shown.
Bldg# 101117607
Elec# 20181641 MSmith
Issued 12/12/23
1410 N Parsons Pl -
2018164112/13/2023
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.T-21.1.PROJECT NOTES:1.2. THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE 2022 CALIFORNIAELECTRICAL CODE (CEC) ARTICLE 690, ALL MANUFACTURER’S LISTING ANDINSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIEDBY THE AUTHORITY HAVING JURISDICTION’S (AHJ) APPLICABLE CODES.1.3. THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED ANDPV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION1.4. GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE ISINTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH 2022 CEC690.41(B)1.5. ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVEINVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED ANDLISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY 2022 CEC 690.4 PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.6. MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMPCOEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATEDACCORDING TO 2022 CEC 690.7.1.7. ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, ANDSOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAICPOWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATIONPER 690.4 (D). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONSFROM LISTING OR LABELING [ 2022 CEC 110.3].1.8. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDINGCODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALLPLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE CECAND AHJ.1.9.SCOPE OF WORK:1.10. PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN ANDSPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT.PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTINGONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THEEXTERIOR ROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMSDETAILED IN THIS DOCUMENT.1.11.WORK INCLUDES:1.12. PV ROOF ATTACHMENTS - UNIRAC FLASHLOC FOR COMP SHINGLE ROOF1.13. PV RACKING SYSTEM INSTALLATION - EVEREST CROSSRAIL ROOF MOUNTRACKING HARDWARE1.14. PV MODULE AND INVERTER INSTALLATION - JA SOLAR JAM54S31-395/MR (395W)MODULES / TIGO EI TSI-3.8K-US INVERTER1.15. PV EQUIPMENT GROUNDING1.16. PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.17. PV LOAD CENTERS (IF INCLUDED)1.18. PV METERING/MONITORING (IF INCLUDED)1.19. PV DISCONNECTS1.20. PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.21. PV FINAL COMMISSIONING1.22. (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.23. SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE1.24.SITE NOTES:1.25. A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHAREGULATIONS.1.26. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THISSYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGEBATTERY.1.27. THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING,MECHANICAL, OR BUILDING ROOF VENTS.1.28. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING ANDPROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION2022 CEC 110.26.1.29. ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED INACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'SINSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECTTHE BUILDING OR STRUCTURE.1.30.EQUIPMENT LOCATIONS:1.31. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY 2022 CEC110.26.1.32. WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOREXPECTED OPERATING TEMPERATURE AS SPECIFIED BY 2022 CEC 690.31 (A),(C)AND CEC TABLES 310.15 (B)(2)(A) AND 310.15 (B)(3)(C)1.33. JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULESACCORDING TO 2022 CEC 690.34.1.34. ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THEINVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT .1.35. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIEDPERSONNEL ACCORDING TO 2022 CEC APPLICABLE CODES.1.36. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOROUTDOOR USAGE WHEN APPROPRIATE.1.37.STRUCTURAL NOTES:1.38. RACKING SYSTEM1.39. PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANTINSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEENMODULES, AND RAILS MUST ALSO EXTEND1.40. A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY,ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.1.41. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'SSPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED SEALEDPER LOCAL REQUIREMENTS.1.42. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED ANDSEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSEDCONTRACTOR.1.43. ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THANTHE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.1.44. WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BESTAGGERED AMONGST THE ROOF FRAMING MEMBERS.1.45.WIRING & CONDUIT NOTES:1.46. ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIRPURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUMCODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.1.47. CONDUCTORS SIZED ACCORDING TO 2022 CEC 690.8, 2022 CEC 690.7.1.48. VOLTAGE DROP LIMITED TO 1.5%.1.49. DC WIRING LIMITED TO MODULE FOOTPRINT. OPTIMIZER WIRINGSYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITHSUITABLE WIRING CLIPS.1.50. AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1-BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASEPHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTIONNEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THEPHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [2022 CEC 110.151.51.GROUNDING NOTES:1.52. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIRPURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALLBE RATED FOR SUCH USE.1.53. PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO 2022 CEC 690.43 ANDMINIMUM 2022 CEC TABLE 250.122.1.54. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURESCONSIDERED GROUNDED IN ACCORDING WITH 2022 CEC 250.134 AND 2022250.136(A).1.55. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TOCEC 690.45 AND INVERTER MANUFACTURER'S INSTRUCTIONS.1.56. EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS ASSHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THEAHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BEINSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THEMANUFACTURERS' INSTALLATION REQUIREMENTS.1.57. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCHTHAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDINGCONDUCTOR TO ANOTHER MODULE.1.58. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BECOLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [2022 CEC250.119]1.59. THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC 690.47 ANDCEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, ORINADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TOCEC 250, CEC 690.47 AND AHJ.1.60. GROUND-FAULT DETECTION SHALL COMPLY WITH CEC 690.41 IN GENERALAND CEC 690.41 (A)(1) SPECIFICALLY.1.61.DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:1.62. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THESWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARECONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THEUPPER TERMINALS).1.63. DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BELOCKABLE, AND BE A VISIBLE-BREAK SWITCH1.64. RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 1 FT OF PVARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLEDCONDUCTORS ≤30V AND ≤240VA [CEC 690.12(B)]. LOCATION OF LABELACCORDING TO AHJ1.65. ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC 690.8,690.9, AND 240.1.66. EQUIPMENT THAT IS LISTED, LABELED, OR BOTH SHALL BE INSTALLED ANDUSED IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTINGOR LABELING. CEC 110.3(B).1.67. IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUITPROTECTION ACCORDING TO CEC 690.11 AND UL1699B.1.68.ELECTRICAL INTERCONNECTION NOTES:1.69. THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAYNOT EXCEED 120% OF BUSBAR RATING.1.70. WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PVDEDICATED BACKFFED BREAKERS MUST BE LOCATED OPPOSITE END OFTHE BUS FROM THE UTILITY SOURCE OCPD.1.71. AT MULTIPLE PV OUTPUT COMBINER PANEL, TOTAL RATING OF ALLOVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR.HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED.1.72. SUPPLY SIDE TAP INTERCONNECTION WITH SERVICE ENTRANCECONDUCTORS.1.73. BACKFEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT ISEXEMPT FROM ADDITIONAL FASTENING.Signed: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
1'-6"1'-6"N3'3'3'3'SCALE: 1/16" = 1'-0"PV SYSTEM SITE PLANPV SYSTEM SIZE:3.555 kW DC LEGENDCONSTRUCTION NOTESNEW SOLAR PANELS1410 N PARSONS PLSHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.PV-1ACDAC DISCONNECTROOF OBSTRUCTIONS(E) SERVICE DROPDRIVEWAY(9) JA SOLAR JAM54S31-395/MR (395W)MODULES WITHA TIGO TS4-A-O OPTIMIZER ATTACHED TO THEBACK OF EACH MODULES MOUNTED ONCOMP SHINGLE ROOFMMETER MAIN COMBOINV STRING INVERTERRoof Azimuth: 270°Roof Tilt: 16°Roof Section 1PROPERTY LINE PROPERTY LINE(E) SOLAR SYSTEMMPV INTERCONNECTION POINT.LOCATION OF METER MAIN COMBO,AC DISCONNECT, PV LOAD CENTER &STRING INVERTER MOUNTED ONEXTERIOR WALL OF A SINGLE FAMILYRESIDENCEINVPROPERTY LINE
CAL-FIRE ROOF LADDERACCESS POINTPROPERTY LINE
PROPERTY LINECAL-FIRE ROOF LADDERACCESS POINTLOCATION OF "RAPID SHUTDOWN" ACDISCONNECT NEC 690.121. SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ONRESIDENTIAL STRUCTURE.2. THIS PROJECT HAS BEEN DESIGNED IN COMPLIANCEWITH THE CBC SECTION 1609 TO WITHSTAND A BASICWIND SPEED OF 110 MPH (3 SECOND GUST), WINDEXPOSURE C.3. THE ROOF MEMBERS ARE 2 "X 4" TRUSSES AT 24" ONCENTER. CONNECTION TO STRUCTURE SHALL NOT BEWITHIN 11" OF NAILING PLATES.4. THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOTOBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDINGROOF VENTS.5. ALL CONDUCTORS AND CONDUITS MOUNTED ON ROOFSHALL BE MINIMUM 7/8" ABOVE ROOF SURFACE(INCLUDING CABLES UNDERNEATH MODULES ANDRACKING).6. ROOF ACCESS POINTS SHALL BE PROVIDED PER THEFOLLOWING (CRC R324.6, CBC 3111.3.4)6.1. LOCATED IN AREAS NOT REQUIRING PLACEMENT OFGROUND LADDERS OVER OPENINGS SUCH ASDOORS OR WINDOWS.6.2. LOCATED AT STRONG POINTS OF CONSTRUCTION INLOCATIONS WHERE ACCESS POINT DOES NOTCONFLICT WITH OVERHEAD OBSTRUCTIONS SUCHAS: TREES, WIRES, OR SIGNS.7. SETBACKS AT RIDGES CAN BE REDUCED TO 18 INCHES INCOMPLIANCE 2022 CFC/2021 IFC 1205.2.1.2TOTAL PLAN VIEW AREA = 2203.08 SQFTTOTAL PV AREA FOR NEW SYSTEM= 9(67.79 IN)(44.64 IN)/(144 IN^2) = 189.13 SQFT=(189.13 SQFT/ 2203.08 SQFT)100 = 8.58%TOTAL PV AREA FOR EXISTING SYSTEM=8(64.57 IN)(39.29IN)/(144 IN^2) = 140.94 SQFT=(140.94SQFT/ 2203.08 SQFT)100 =6.39%TOTAL PV AREA FOR NEW AND EXISTING SYSTEM.(140.94+ 189.13 ) SQFT/ 2203.08 SQFT = 14.98%TOTAL PV AREA POPULATES 14.98% OF TOTAL PLANVIEW AREA AND IS WITHIN THE 33% REQUIREMENT.PROPERTY LINEPROPERTY LINEPROPERTY LINEACDACDWALKWAYLCLOCATION OF EXISTING ACDISCONNECT & LOAD CENTERLCPV LOAD CENTERLC(E) STRUCTURE ON PROPERTYCAL-FIRE ROOF LADDERACCESS POINTW SUNSWEPT AVESigned: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
6'6'6'6'6'N
SCALE: 3/16" = 1'-0"PV SYSTEM MOUNTING DETAILSEXISTING COMP SHINGLE ROOFUNIRAC FLASHLOC FOR COMPSHINGLE @ 72" O.C. MAXPROPOSED EVERESTCROSSRAIL RACKINGPROPOSED JA SOLARJAM54S31-395/MR (395W) PVSOLAR MODULESEXISTING 2 "X 4" ROOFTRUSSES @ 24"O.C.SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.PV-2Roof Azimuth: 270°Roof Tilt: 16°Roof Section 1(E) SOLAR SYSTEM(E) SERVICE DROPSigned: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
ROOF SLOPE 910106217PV-3D52011121413151822PV-3D431542524238262D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALESHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.1. ROOF MATERIAL: COMP SHINGLE2. ROOF STRUCTURE: TRUSSES3. ATTACHMENT TYPE: UNIRAC FLASHLOC4. MODULE MANUFACTURER: JA SOLAR5. MODULE MODEL: JAM54S31-395/MR (395W)6. MODULE LENGTH: 67.79''7. MODULE WIDTH: 44.64"8. MODULE WEIGHT: 42.99 LBS.9. SEE SHEET S-1 FOR DIMENSION(S)10. MIN. FIRE OFFSET: 18"11. TRUSSES SPACING: 24" O.C.12. TRUSSES SIZE: 2 "X 4" NOMINAL13. LAG BOLT DIAMETER: 5/16 IN.14. LAG BOLT EMBEDMENT: 2.5 IN.15. TOTAL # OF ATTACHMENTS: 1416. TOTAL AREA: 189.13 SQ. FT.17. TOTAL WEIGHT: 386.91 LBS.18. WEIGHT PER ATTACHMENT: 27.64 LBS.19. DISTRIBUTED LOAD: 2.05 PSF20. MAX. HORIZONTAL STANDOFF: 72 IN.21. MAX. VERTICAL STANDOFF:LANDSCAPE: 26 IN., PORTRAIT: 43 IN.22. STANDOFF STAGGERING: YES23. RAIL MANUFACTURER AND MODEL(OR EQUIV.):EVEREST CROSSRAIL24. RAIL WEIGHT: 0.436 PLF.25. MAX. TRUSSES SPAN: 12 FT.26. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.PV-3Signed: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS:2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.E-1Conduit and Conductor Schedule~(75°C Copper Column)TagDescriptionWire Gauge# of ConductorsConduit TypeConduit Size1PV WIRES10 AWG2(1-V+,1-V-)N/A - Free AirN/A - Free Air1Bare Copper Ground (EGC/GEC)6 AWG1N/A - Free AirN/A - Free Air2THWN-210 AWG2(1-V+,1-V-)EMT3/4"2THWN-2 - Ground8 AWG1EMT3/4"Inverter RatingsInverter Make/ModelTIGO EITSI-3.8K-USMax DC Volt Rating600VMax Continuous OutputPower3800WMax Nominal Voltage240VMax AC Current16AMax OCPD Rating20ADESIGN TEMPERATURESASHRAE EXTREME LOW2°CASHRAE 2% HIGH30°CPV Module Ratings @ STCModule Make/Model JA SOLARJAM54S31-395/MR (395W)MODULEMax Power-Point Current (Imp)12.81AMax Power-Point Voltage (Vmp)30.84VOpen-Circuit Voltage (Voc)36.98VShort-Circuit Current (Isc)13.70AMax Series Fuse (OCPD)25ANominal Maximum Power at STC(Pmax)395WMaximum System Voltage1500VVoc Temperature Coefficient-0.275%/°C3THWN-210 AWG3(1-L1,1-L2,1-N)EMT3/4"3THWN-2 - Ground8 AWG1EMT3/4"SYSTEM SUMMARYBRANCH #1MODULE SHORT CIRCUITCURRENTNO. OF MODULES PERSTRINGARRAY STC POWERARRAY PTC POWERMAX AC CURRENTMAX AC POWERDERATED (CEC) AC POWER3555W3318W16A3800W3218.46W13.70A94THWN-28 AWG3(1-L1,1-L2,1-N)EMT3/4"4THWN-2 - Ground8 AWG1EMT3/4"1410 N Parsons Pl -2018164112/13/2023
TIGOEI INVERTERPV INPUTBATTERYAC GRIDMPPT2+-GL1L2NGG(N) TIGO TSI-3.8K-USINVERTER(N) TIGO CCAKIT+RA485LAN-E-STOPBUTTON3(N) 9 JA SOLAR JAM54S31-395/MR (395W) WITH TIGOTS4-A-O OPTIMIZER ATTACHED TO THE BACK OF EACHMODULEG1(N) JUNCTION BOXWITH IRREVERSIBLEGROUND SPLICE2========PV CIRCUIT 1: 9 MODULES/SERIESMPPT1BACKFEEDBREAKERMPOINT OF DELIVERY ANDINTERCONNECTION200AN(E) GROUNDINGELECTRODE OR(UFER)EXISTING240V/200AMAIN SERVICE PANELSINGLE PHASE40AAC DISCONNECTTO BE LOCATEDWITHIN 10' OFMETER(N) VISIBLE LOCKABLE2 POLE 60A'KNIFE' AC DISCONNECT4NOTE: IN BETWEEN EACH ARRAY THE EMT IS USED AS THEGROUNDING / BONDING, GROUND CLAMPS ARE AT EACHEND OF THE EMT CONDUIT WITH THE WIRE THEN FREEAIR'D TO THE GROUND CLAMP ON THE RACKING RAIL20A15AN(N) 100A PV LOADCENTER4AC DISCONNECTTO BE LOCATEDWITHIN 10' OFMETER(E) JUNCTION BOX WITHIRREVRESIBLE GROUNDSPLICE(E) 8 HYUNDAI M250ORG (250W) MODULES WITHAN ENPHASE M215-IG MICRO-INVERTERATTACHED TO THE BACK OF EVERY MODULE.ROOF TOPGROUND LEVEL -HOUSE EXTERIOREXISTING WIRE8PV CIRCUIT 1: 8 MODULES/PARALLEL1215AN(E) 100A PV LOADCENTER(E) VISIBLELOCKABLE2 POLE 30A'KNIFE' AC DISCONNECTEXISTING WIRE(E) PV SYSTEM IS RSD COMPLIANTEXISTING WIREEXISTING WIREROOF TOPGROUND LEVEL -HOUSE EXTERIORSHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS:2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.E-1.1METER # 222012785226MAIN SERVICE PANEL240/120V 1Ø, 3WMAIN BUSS: 200AMAX BREAKER SIZE:(200A X 1.2) - 200A = 40.0A1410 N Parsons Pl -2018164112/13/2023
1.NOT ALL PLACARDS SHOWN MAY BE REQUIRED BY LOCAL AHJ. CONTRACTOR TO VERIFY PLACARDREQUIREMENTS WITH LOCAL AHJ BEFORE INSTALLATION.2.ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE3.ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC, ENGRAVED OR MACHINEPRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTCHED BY POPRIVETS OR SCREWS OR OTHER APPROVED METHOD.4.DIRECTORY PLACARD MARKING CONTENT AND FORMAT: RED BACKGROUND, WHITE LETTERING,MINIMUM 3/8" LETTER HIEGHT, ALL CAPITAL LETTERS, ARIAL OR SIMILAR FONT, NON BOLD, REFLECTIVEWEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT.PERMANENT SIGNAGE NOTES:WARNING!DO NOT RELOCATE THISOVERCURRENT DEVICEPOWER SOURCE OUTPUT CONNECTIONLABEL LOCATION:ADJACENT TO PV BREAKER (IF APPLICABLE).PER CODE(S): CEC 2022: 705.12(B)(3)(2)!DO NOT ADD LOADSPHOTOVOLTAIC SYSTEMCOMBINER PANELWARNINGLABEL LOCATION:PHOTOVOLTAIC AC COMBINER (IFAPPLICABLE).PER CODE(S): CEC 2022: 705.12(B)(3)(3)SOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNSOLAR ELECTRICPV PANELSTURN RAPID SHUTDOWNSWITCH TO THE "OFF"POSITION TO SHUT DOWNPV SYSTEM AND REDUCESHOCK HAZARD IN THEARRAY.LABEL LOCATION:ON OR NO MORE THAT 3 M (10 FT) FROM THE SERVICEDISCONNECTING MEANS TO WHICH THE PV SYSTEMSARE CONNECTED.ELECTRICAL SHOCK HAZARDWARNING!LABEL LOCATION:INVERTER(S), AC DISCONNECT(S), ACCOMBINER PANEL (IF APPLICABLE).PER CODE(S): CEC 2022: 690.13(B)& 706.15(C)(4)TERMINALS ON LINE AND LOADSIDES MAY BE ENERGIZED INTHE OPEN POSITIONRAPID SHUTDOWN SWITCHFOR SOLAR PV SYSTEMLABEL LOCATION:UTILITY SERVICE ENTRANCE/METER, INVERTER/DCDISCONNECT IF REQUIRED BY LOCAL AHJ, OROTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.PER CODE(S): CEC 2022: 690.56(C)(2),CFC 2022: 1204.5.3POWER TO THIS BUILDING ISALSO SUPPLIED FROM THEFOLLOWING SOURCES WITHDISCONNECTS AS SHOWNCAUTION:MAXIMUM AC OPERATING CURRENT:NOMINAL OPERATING AC VOLTAGE:16.00 AMPS240.0 VACPHOTOVOLTAIC AC DISCONNECTLABEL LOCATION:AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OFINTERCONNECTION.PER CODE(S): CEC 2022: 690.54SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS:2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.E-2LOCATION OF EXISTING ACDISCONNECT & PV LOADCENTERWARNING!THIS EQUIPMENT FED BY MULTIPLESOURCES. TOTAL RATING OF ALLOVERCURRENT DEVICES, EXCLUDINGMAIN SUPPLY OVERCURRENTDEVICE, SHALL NOT EXCEEDAMPACITY OF BUSBAR.PV INTERCONNECTION POINT.LOCATION OF METER MAIN COMBO, ACDISCONNECT, PV LOAD CENTER & STRINGINVERTER.1410 N PARSONS PL(N) SOLAR PANELS & OPTIMIZERON ROOF(E) PV SYSTEM IS RSD COMPLIANT(E) SOLAR PANELS &MICRO-INVERTERS ON ROOFW SUNSWEPT AVE PHOTOVOLTAIC SYSTEMDC DISCONNECTOPERATING VOLTAGE: 443.76 VDCOPERATING CURRENT: 12.81 AMPSMAX SYSTEM VOLTAGE: 501.44VDCSHORT CIRCUIT CURRENT: 13.70 AMPSLABEL LOCATION: INVERTERPER CODE(S): CEC 2022: 690.531410 N Parsons Pl -2018164112/13/2023
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-1Signed: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-2Signed: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-3Signed: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-4Signed: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:11/2/2023KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-5Signed: 11/08/2023Structural Only1410 N Parsons Pl -2018164112/13/2023
11/08/2023
RE: Structural Certification for Installation of Residential Solar
ROBERT KINGSTON:1410 N PARSONS PL, SANTA ANA, CA, 92703
Attn: To Whom It May Concern
Design Criteria
Code 2022 California Building Code (ASCE 7‐16)
Risk category II Wind Load (component and Cladding)
Roof Dead Load Dr 10 psf V 110 mph
PV Dead Load DPV 3 psf Exposure C
Roof Live Load Lr 20 psf
Ground Snow S 0 psf
If you have any questions on the above, please do not hesitate to call.
Sincerely,
Eugene Munyanziza, P.E. Signed 11/08/2023
EV Engineering, LLC
projects@evengineersnet.com
http://www.evengineersnet.com
Exp: 06/30/2024
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the
PV system to existing roof framing. From the field observation report, the roof is made of Composition shingle
roofing over roof plywood supported by 2X4 Trusses at 24 inches. The slope of the roof was approximated to be
16 degrees.
After review of the field observation data and based on our structural capacity calculation, the existing roof
framing has been determined to be adequate to support the imposed loads without structural upgrades.
Contractor shall verify that existing framing is consistent with the described above before install. Should they
find any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity
calculations were done in accordance with applicable building codes.
projects@evengineersnet.com
http://www.evengineersnet.com
1410 N Parsons Pl -
2018164112/13/2023
Structural Letter for PV Installation
Date: 11/08/2023
Job Address:1410 N PARSONS PL
SANTA ANA, CA, 92703
Job Name:ROBERT KINGSTON
Job Number:231108RK
Scope of Work
Table of Content
Sheet
2 Cover
3 Attachment Uplift checks
4 Roof Framing Check
5 Seismic Check and Scope of work
Engineering Calculations Summary
Code 2022 California Building Code (ASCE 7‐16)
Risk category II
Roof Dead Load Dr 10 psf
PV Dead Load DPV 3 psf
Roof Live Load Lr 20 psf
Ground Snow S 0 psf
Wind Load (component and Cladding)
V 110 mph
Exposure C
References
NDS for Wood Construction
Sincerely,
Signed 11/08/2023
Eugene Munyanziza, P.E.
EV Engineering, LLC
projects@evengineersnet.com
http://www.evengineersnet.com Exp: 06/30/2024
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV
system to existing roof framing. All PV mounting equipment shall be designed and installed per manufacturer's
approved installation specifications.
projects@evengineersnet.com
http://www.evengineersnet.com
1410 N Parsons Pl -
2018164112/13/2023
Wind Load Cont.
110 mph ASCE 7‐16 Figure 26.5‐1B
C
1.0 ASCE 7‐16 Sec 26.8.2
0.93 ASCE 7‐16 Table 26.10‐1
0.85 ASCE 7‐16 Table 26.6‐1
1.00 ASCE 7‐16 Table 26.9‐1
24.39 psf
16.0 Degrees
1.5 Conservatively assuming all exposed
0.8 conservatively assuming 10 ft2 effective area
Uplift (W)Zone(1,2e) Zone(2r, 2n) Zone(3e) Zone(3r)
Fig. 30‐3‐2 GCp=‐1.1 ‐2 ‐2 ‐2.4
Eq. 29.4‐7 P=qh(GCp)(γE)(γa)=‐32.19 ‐58.53 ‐58.53 ‐70.23
GCp=0.5 Figure 30.3‐2
P=qh(GCp)(γE)(γa)=8.05 Equation 29.4‐7
Rafter Attachments: 0.6D+0.6W (CD=1.6)
Connection Check
Attachment max. spacing= 6 ft
5/16" Lag Screw Withdrawal Value= 266 lbs/in Table 12.2A ‐ NDS
2.5 in DFL Assumed
Prying Coefficient 1.4
Allowable Capacity= 760 lbs
Zone Trib Width Area (ft) Uplift (lbs) Down (lbs)
Zone(1,2e)6 16.5 191.6 182.3
Zone(2r, 2n)6 16.5 335.0 182.3
Zone(3e)6 16.5 335.0 182.3
Zone(3r)6 16.5 398.8 182.3
Conservative Max=398.8 < 760
CONNECTION IS OK
Risk Category =
KZ =
Kd =
Ke =
2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw.
Embedment in sheading or other material does not count.
II
V=
Exposure =
1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift
governs
γE=
γa=
KZt =
qh= 0.00256KzKztKdKeV2=
Pitch =
Lag Screw Penetration
projects@evengineersnet.com
http://www.evengineersnet.com
1410 N Parsons Pl -
2018164112/13/2023
Vertical Load Resisting System Design
Roof Framing Trusses
Snow Load Fully Exposed
pg= 0 psf
Ct =1.1
Ce =0.9 Is =1.0
pf = 0 psf
pfmin. = 0.0 psf
ps = 0 psf Conservatively (Cs=1) 0 plf
Max Length, L = 8.0 ft (Rafter maximum Allowable Horizontal Span)
Tributary Width, WT =24 in
Dr =10psf 20 plf
PvDL =3 psf 18 plf
Load Case: DL+0.75(0.6W+S)
0.75(Pnet+Ps)+ Ppvcos(θ)+PDL=45 plf
Mdown=241 lb‐ft
Mallowable = Sx x Fb' (wind)= 456 lb‐ft > 241 lb‐ft OK
Load Case: DL+S
Ps+ Ppvcos(θ)+PDL=38 plf
Mdown=203 lb‐ft
Mallowable = Sx x Fb' (wind)= 456 lb‐ft > 203 lb‐ft OK
Load Case: DL+0.6W
Pnet+ Ppvcos(θ)+PDL=47.7 plf
Max Moment, Mu=254 lb‐ft
Mallowable = Sx x Fb' (wind)= 634 lb‐ft > 254 lb‐ft OK
Pv max Shear= 182.3 lbs
Shear, Vu=wL/2+Pv Point Load =334 lbs
Max Shear, Vu=wL/2+Pv Point Load =334 lb
Member Capacity
DF‐L No.2
2X4 CL CF Ci Cr KF φλ
Fb =900 psi 1.0 1.5 1.0 1.15 2.54 0.85 0.8 1553 psi
Fv =180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi
E = 1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psi
Emin =580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi
Depth, d = 3.5 in
Width, b = 1.5 in
Cross‐Sectonal Area, A = 5.25
in2
Moment of Inertia, Ixx =5.35938 in4
Section Modulus, Sxx =3.0625 in
Allowable Moment, Mall = Fb'Sxx =396.2 lb‐ft DCR=Mu/Mall =0.53 < 1 Satisfactory
Allowable Shear, Vall = 2/3Fv'A =630.0 lb DCR=Vu/Vall =0.53 < 1 Satisfactory
Design Value Adjusted Value
projects@evengineersnet.com
http://www.evengineersnet.com
1410 N Parsons Pl -
2018164112/13/2023
Siesmic Loads Check
Roof Dead Load 10 psf
% or Roof with Pv 15%
Dpv and Racking 3 psf
Average Total Dead Load 10.4 psf
Increase in Dead Load 1.8%OK
Limits of Scope of Work and Liability
The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and
therefore no further seismic analysis is required.
We have based our structural capacity determination on information in pictures and a drawing set titled PV plans ‐
ROBERT KINGSTON. The analysis was according to applicable building codes, professional engineering and design
experience, opinions and judgments. The calculations produced for this Structure's assessment are only for the
proposed solar panel installation referenced in the stamped plan set and were made according to generally
recognized structural analysis standards and procedures.
projects@evengineersnet.com
http://www.evengineersnet.com
1410 N Parsons Pl -
2018164112/13/2023
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
1053344
Solgen Construction, LLC
Cole Farmer
Permits@CoreEnergyGroup.com
559-462-6009
1410 N Parsons Pl, Santa Ana, CA 92703
12/04/2023
1410 N Parsons Pl -
2018164112/13/2023
To whom it may concern,
This letter serves to confirm I have chosen to have my system installed by Solgen
Construction LLC. You have my express permission to move forward with the solar
permit applied for by Solgen Construction LLC for my property at 1410 N Parsons Pl.
Santa Ana, CA 92703.
Thank you,
Robert Kingston
DocuSign Envelope ID: FE0CED3B-30A4-4C85-8F71-3D39C8C9B05D
12/2/2023
1410 N Parsons Pl -
2018164112/13/2023
DocuSign Envelope ID: FE0CED3B-30A4-4C85-8F71-3D39C8C9B05D
1410 N Parsons Pl -
2018164112/13/2023
Certificate Of Completion
Envelope Id: FE0CED3B30A44C858F713D39C8C9B05D Status: Completed
Subject: Complete with DocuSign: Robert Kingston Authorization Letter
Source Envelope:
Document Pages: 2 Signatures: 1 Envelope Originator:
Certificate Pages: 5 Initials: 0 Core Energy Group
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
727 Eagle Pass
North Salt Lake, UT 84054
proposals@coreenergygroup.com
IP Address: 173.170.204.103
Record Tracking
Status: Original
11/8/2023 12:41:24 PM
Holder: Core Energy Group
proposals@coreenergygroup.com
Location: DocuSign
Signer Events Signature Timestamp
Robert Kingston
Robinrsorell@yahoo.com
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 76.32.190.69
Signed using mobile
Sent: 11/8/2023 12:44:35 PM
Resent: 11/17/2023 3:20:24 PM
Resent: 11/17/2023 3:20:52 PM
Viewed: 11/17/2023 4:05:43 PM
Signed: 12/2/2023 11:42:56 AM
Electronic Record and Signature Disclosure:
Accepted: 11/17/2023 4:05:43 PM
ID: 0ee0705d-ed37-402b-b73f-8c6e53edb82b
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Core Permits
permits@coreenergygroup.com
Mr.
Security Level: Email, Account Authentication
(None)
Sent: 12/2/2023 11:42:57 AM
Viewed: 12/4/2023 8:32:32 AM
Electronic Record and Signature Disclosure:
Accepted: 8/15/2023 3:05:32 PM
ID: 66ba5d5d-5f22-4bdb-a9d4-a0896bad0286
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 11/8/2023 12:44:35 PM
Envelope Updated Security Checked 11/17/2023 3:20:24 PM
Envelope Updated Security Checked 11/17/2023 3:20:24 PM
Certified Delivered Security Checked 11/17/2023 4:05:43 PM
1410 N Parsons Pl -
2018164112/13/2023
Envelope Summary Events Status Timestamps
Signing Complete Security Checked 12/2/2023 11:42:56 AM
Completed Security Checked 12/2/2023 11:42:57 AM
Payment Events Status Timestamps
Electronic Record and Signature Disclosure
1410 N Parsons Pl -
2018164112/13/2023
ELECTRONIC RECORD AND SIGNATURE DISCLOSURE
From time to time, Solgen Construction LLC (we, us or Company) may be required by law to
provide to you certain written notices or disclosures. Described below are the terms and
conditions for providing to you such notices and disclosures electronically through the DocuSign
system. Please read the information below carefully and thoroughly, and if you can access this
information electronically to your satisfaction and agree to this Electronic Record and Signature
Disclosure (ERSD), please confirm your agreement by selecting the check-box next to ‘I agree to
use electronic records and signatures’ before clicking ‘CONTINUE’ within the DocuSign
system.
Getting paper copies
At any time, you may request from us a paper copy of any record provided or made available
electronically to you by us. You will have the ability to download and print documents we send
to you through the DocuSign system during and immediately after the signing session and, if you
elect to create a DocuSign account, you may access the documents for a limited period of time
(usually 30 days) after such documents are first sent to you. After such time, if you wish for us to
send you paper copies of any such documents from our office to you, you will be charged a
$0.00 per-page fee. You may request delivery of such paper copies from us by following the
procedure described below.
Withdrawing your consent
If you decide to receive notices and disclosures from us electronically, you may at any time
change your mind and tell us that thereafter you want to receive required notices and disclosures
only in paper format. How you must inform us of your decision to receive future notices and
disclosure in paper format and withdraw your consent to receive notices and disclosures
electronically is described below.
Consequences of changing your mind
If you elect to receive required notices and disclosures only in paper format, it will slow the
speed at which we can complete certain steps in transactions with you and delivering services to
you because we will need first to send the required notices or disclosures to you in paper format,
and then wait until we receive back from you your acknowledgment of your receipt of such
paper notices or disclosures. Further, you will no longer be able to use the DocuSign system to
receive required notices and consents electronically from us or to sign electronically documents
from us.
All notices and disclosures will be sent to you electronically
Electronic Record and Signature Disclosure created on: 2/16/2023 3:39:07 PM
Parties agreed to: Robert Kingston, Core Permits 1410 N Parsons Pl -
2018164112/13/2023
Unless you tell us otherwise in accordance with the procedures described herein, we will provide
electronically to you through the DocuSign system all required notices, disclosures,
authorizations, acknowledgements, and other documents that are required to be provided or made
available to you during the course of our relationship with you. To reduce the chance of you
inadvertently not receiving any notice or disclosure, we prefer to provide all of the required
notices and disclosures to you by the same method and to the same address that you have given
us. Thus, you can receive all the disclosures and notices electronically or in paper format through
the paper mail delivery system. If you do not agree with this process, please let us know as
described below. Please also see the paragraph immediately above that describes the
consequences of your electing not to receive delivery of the notices and disclosures
electronically from us.
How to contact Solgen Construction LLC:
You may contact us to let us know of your changes as to how we may contact you electronically,
to request paper copies of certain information from us, and to withdraw your prior consent to
receive notices and disclosures electronically as follows:
To contact us by email send messages to: proposals@solgen.co
To advise Solgen Construction LLC of your new email address
To let us know of a change in your email address where we should send notices and disclosures
electronically to you, you must send an email message to us at proposals@solgen.co and in the
body of such request you must state: your previous email address, your new email address. We
do not require any other information from you to change your email address.
If you created a DocuSign account, you may update it with your new email address through your
account preferences.
To request paper copies from Solgen Construction LLC
To request delivery from us of paper copies of the notices and disclosures previously provided
by us to you electronically, you must send us an email to proposals@solgen.co and in the body
of such request you must state your email address, full name, mailing address, and telephone
number. We will bill you for any fees at that time, if any.
To withdraw your consent with Solgen Construction LLC
To inform us that you no longer wish to receive future notices and disclosures in electronic
format you may:
1410 N Parsons Pl -
2018164112/13/2023
i. decline to sign a document from within your signing session, and on the subsequent page,
select the check-box indicating you wish to withdraw your consent, or you may;
ii. send us an email to proposals@solgen.co and in the body of such request you must state your
email, full name, mailing address, and telephone number. We do not need any other information
from you to withdraw consent.. The consequences of your withdrawing consent for online
documents will be that transactions may take a longer time to process..
Required hardware and software
The minimum system requirements for using the DocuSign system may change over time. The
current system requirements are found here: https://support.docusign.com/guides/signer-guide-
signing-system-requirements.
Acknowledging your access and consent to receive and sign documents electronically
To confirm to us that you can access this information electronically, which will be similar to
other electronic notices and disclosures that we will provide to you, please confirm that you have
read this ERSD, and (i) that you are able to print on paper or electronically save this ERSD for
your future reference and access; or (ii) that you are able to email this ERSD to an email address
where you will be able to print on paper or save it for your future reference and access. Further,
if you consent to receiving notices and disclosures exclusively in electronic format as described
herein, then select the check-box next to ‘I agree to use electronic records and signatures’ before
clicking ‘CONTINUE’ within the DocuSign system.
By selecting the check-box next to ‘I agree to use electronic records and signatures’, you confirm
that:
You can access and read this Electronic Record and Signature Disclosure; and
You can print on paper this Electronic Record and Signature Disclosure, or save or send
this Electronic Record and Disclosure to a location where you can print it, for future
reference and access; and
Until or unless you notify Solgen Construction LLC as described above, you consent to
receive exclusively through electronic means all notices, disclosures, authorizations,
acknowledgements, and other documents that are required to be provided or made
available to you by Solgen Construction LLC during the course of your relationship with
Solgen Construction LLC.
1410 N Parsons Pl -
2018164112/13/2023
COORDINATES:
33.757323, -117.932011
KINGSTON RESIDENCE
NEW PHOTOVOLTAIC SYSTEM
PROJECT - 3.160 kW DC /
3.072 kW AC
SHEET #
T-1
T-2
PV-1
PV-2
PV-3
E-1
E1.1
E-2
S-1
S-2
S-3
S-4
SHEET NAME
COVER SHEET
PLAN NOTES
SITE PLAN LAYOUT
ATTACHMENT DETAILS
MOUNTING DETAILS
ELECTRICAL CALCULATION
ELECTRICAL DIAGRAM
WARNING LABELS
SPEC SHEET
SPEC SHEET
SPEC SHEET
SPEC SHEET
SHEET
CONTRACTOR
SOLGEN CONSTRUCTION LLC.
1410 N PARSONS PL,
SANTA ANA,
CA 92703
APN:10046201
DATE:1/3/2024
KINGSTON
RESIDENCE
License#: C-10 1053344
ADDRESS: 2072 N MAIN ST
FL 2, LOGAN
UT 84341-1993
CSLB#: 1053344
DESIGNER: OAV
CORE ENERGY GROUP.
T-1
TYPE OF
INTERCONNECTION: BACKFEED BREAKER IN THE SSP
SCOPE OF WORK
SYSTEM SIZE:STC: 8 X 395W = 3.160kW
PTC: 8 X 368.7W = 2.950kW
(8) JA SOLAR JAM54S31-395/MR (395W) MODULES
(4)AP SYSTEM DS3-L MICROINVERTERS
(1)125A SUB SERVICE PANEL
(1)60A KNIFE AC DISCONNECT
(1)100A PV LOAD CENTER
MSP UPGRADE:NO
MAIN BREAKER DERATE: NO
RACKING & MOUNTING
PV ATTACHMENT TYPE: UNIRAC FLASHLOC FOR COMP SHINGLE ROOF
RACKING TYPE: EVEREST CROSSRAIL- ROOF
MOUNT RACKING HARDWARE
PROJECT INFORMATION
PROPERTY OWNER
NAME:ROBERT KINGSTON
PHONE:-
CONTRACTOR
NAME:SOLGEN CONSTRUCTION
PHONE:(559)442-9887
DESIGN SPECIFICATIONS
OCCUPANCY: R-3
CONSTRUCTION TYPE: SINGLE FAMILY RESIDENCE
ZONING: RESIDENTIAL
GROUND SNOW LOAD: 0 PSF
WIND EXPOSURE: C
WIND SPEED: 110 MPH
APPLICABLE CODES & STANDARDS
2022 CALIFORNIA RESIDENTIAL CODE (CRC)
2022 CALIFORNIA BUILDING CODE (CBC)
2022 CALIFORNIA MECHANICAL CODE (CMC)
2022 CALIFORNIA ELECTRICAL CODE (CEC)
2022 CALIFORNIA PLUMBING CODE (CPC)
2022 CALIFORNIA ENERGY CODE (ENERGY)
2022 CALIFORNIA GREEN BUILDING CODE (CALGREEN)
2020 NATIONAL ELECTRICAL CODE (NEC)
2022 CALIFORNIA FIRE CODE (CFC)
AERIAL VIEW
EXISTING PV SYSTEM :
DC SYSTEM SIZE:- 2.000 kW
AC SYSTEM SIZE:- 1.800 kW
COMBINED PV SYSTEM :
DC SYSTEM SIZE:- 5.16 kW
AC SYSTEM SIZE:- 5.072 kW
Exp: 06/30/2024
The scope of the plans is for the installation of the solar
photovoltaic system only and the approval is subject to
compliance with all applicable city and state codes and
regulations regarding construction. The approval of the plans
does not constitute any certification of the accuracy,
completeness, or building permit status of the existing
buildings and structures as shown.
Bldg#: 101117952
Elec#: 20181873
Rev:
Bldg#: 101117607
Elect#: 20181641
Approvals:
Elec: MSmith
1410 N Parsons Pl -
20181873 - DL4/10/2024
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.T-21.1.PROJECT NOTES:1.2. THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE 2022 CALIFORNIAELECTRICAL CODE (CEC) ARTICLE 690, ALL MANUFACTURER’S LISTING ANDINSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIEDBY THE AUTHORITY HAVING JURISDICTION’S (AHJ) APPLICABLE CODES.1.3. THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED ANDPV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION1.4. GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE ISINTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH 2022 CEC690.41(B)1.5. ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVEINVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED ANDLISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY 2022 CEC 690.4 PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.6. MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMPCOEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATEDACCORDING TO 2022 CEC 690.7.1.7. ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, ANDSOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAICPOWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATIONPER 690.4 (D). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONSFROM LISTING OR LABELING [ 2022 CEC 110.3].1.8. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDINGCODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALLPLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE CECAND AHJ.1.9.SCOPE OF WORK:1.10. PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN ANDSPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT.PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTINGONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THEEXTERIOR ROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMSDETAILED IN THIS DOCUMENT.1.11.WORK INCLUDES:1.12. PV ROOF ATTACHMENTS - UNIRAC FLASHLOC FOR COMP SHINGLE ROOF1.13. PV RACKING SYSTEM INSTALLATION - EVEREST CROSSRAIL ROOF MOUNTRACKING HARDWARE1.14. PV MODULE AND INVERTER INSTALLATION - JA SOLAR JAM54S31-395/MR (395W)MODULES / AP SYSTEM DS3-L MICROINVERTER1.15. PV EQUIPMENT GROUNDING1.16. PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.17. PV LOAD CENTERS (IF INCLUDED)1.18. PV METERING/MONITORING (IF INCLUDED)1.19. PV DISCONNECTS1.20. PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.21. PV FINAL COMMISSIONING1.22. (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.23. SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE1.24.SITE NOTES:1.25. A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHAREGULATIONS.1.26. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THISSYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGEBATTERY.1.27. THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING,MECHANICAL, OR BUILDING ROOF VENTS.1.28. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING ANDPROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION2022 CEC 110.26.1.29. ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED INACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'SINSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECTTHE BUILDING OR STRUCTURE.1.30.EQUIPMENT LOCATIONS:1.31. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY 2022 CEC110.26.1.32. WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOREXPECTED OPERATING TEMPERATURE AS SPECIFIED BY 2022 CEC 690.31 (A),(C)AND CEC TABLES 310.15 (B)(2)(A) AND 310.15 (B)(3)(C)1.33. JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULESACCORDING TO 2022 CEC 690.34.1.34. ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THEINVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT .1.35. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIEDPERSONNEL ACCORDING TO 2022 CEC APPLICABLE CODES.1.36. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOROUTDOOR USAGE WHEN APPROPRIATE.1.37.STRUCTURAL NOTES:1.38. RACKING SYSTEM1.39. PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANTINSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEENMODULES, AND RAILS MUST ALSO EXTEND1.40. A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY,ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.1.41. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'SSPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED SEALEDPER LOCAL REQUIREMENTS.1.42. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED ANDSEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSEDCONTRACTOR.1.43. ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THANTHE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.1.44. WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BESTAGGERED AMONGST THE ROOF FRAMING MEMBERS.1.45.WIRING & CONDUIT NOTES:1.46. ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIRPURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUMCODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.1.47. CONDUCTORS SIZED ACCORDING TO 2022 CEC 690.8, 2022 CEC 690.7.1.48. VOLTAGE DROP LIMITED TO 1.5%.1.49. DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTERS WIRINGSYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITHSUITABLE WIRING CLIPS.1.50. AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1-BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASEPHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTIONNEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THEPHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [2022 CEC 110.151.51.GROUNDING NOTES:1.52. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIRPURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALLBE RATED FOR SUCH USE.1.53. PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO 2022 CEC 690.43 ANDMINIMUM 2022 CEC TABLE 250.122.1.54. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURESCONSIDERED GROUNDED IN ACCORDING WITH 2022 CEC 250.134 AND 2022250.136(A).1.55. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TOCEC 690.45 AND MICROINVERTER MANUFACTURER'S INSTRUCTIONS.1.56. EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS ASSHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THEAHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BEINSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THEMANUFACTURERS' INSTALLATION REQUIREMENTS.1.57. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCHTHAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDINGCONDUCTOR TO ANOTHER MODULE.1.58. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BECOLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [2022 CEC250.119]1.59. THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC 690.47 ANDCEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, ORINADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TOCEC 250, CEC 690.47 AND AHJ.1.60. GROUND-FAULT DETECTION SHALL COMPLY WITH CEC 690.41 IN GENERALAND CEC 690.41 (A)(1) SPECIFICALLY.1.61.DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:1.62. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THESWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARECONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THEUPPER TERMINALS).1.63. DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BELOCKABLE, AND BE A VISIBLE-BREAK SWITCH1.64. RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 1 FT OF PVARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLEDCONDUCTORS ≤30V AND ≤240VA [CEC 690.12(B)]. LOCATION OF LABELACCORDING TO AHJ1.65. ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC 690.8,690.9, AND 240.1.66. EQUIPMENT THAT IS LISTED, LABELED, OR BOTH SHALL BE INSTALLED ANDUSED IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTINGOR LABELING. CEC 110.3(B).1.67. IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUITPROTECTION ACCORDING TO CEC 690.11 AND UL1699B.1.68.ELECTRICAL INTERCONNECTION NOTES:1.69. THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAYNOT EXCEED 120% OF BUSBAR RATING.1.70. WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PVDEDICATED BACKFFED BREAKERS MUST BE LOCATED OPPOSITE END OFTHE BUS FROM THE UTILITY SOURCE OCPD.1.71. AT MULTIPLE PV OUTPUT COMBINER PANEL, TOTAL RATING OF ALLOVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR.HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED.1.72. SUPPLY SIDE TAP INTERCONNECTION WITH SERVICE ENTRANCECONDUCTORS.1.73. BACKFEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT ISEXEMPT FROM ADDITIONAL FASTENING.Exp: 06/30/20241410 N Parsons Pl -20181873 - DL4/10/2024
1'-6"N3'3'SCALE: 1/16" = 1'-0"PV SYSTEM SITE PLANPV SYSTEM SIZE:3.16 kW DC LEGENDCONSTRUCTION NOTESNEW SOLAR PANELS1410 N PARSONS PLSHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.PV-1ACDAC DISCONNECTROOF OBSTRUCTIONSSSPSUB SERVICE PANEL(E) SERVICE DROPDRIVEWAY(8) JA SOLAR JAM54S31-395/MR (395W)MODULES WITH (4) AP SYSTEM DS3-LMICRO-INVERTERS MOUNTED ON THEBACK OF THE MODULE IN PAIR OF TWOON COMP SHINGLE ROOFMMETER MAIN COMBORoof Azimuth: 90°Roof Tilt: 16°Roof Section 1PROPERTY LINE PROPERTY LINE(E) SOLAR SYSTEMMPV INTERCONNECTION POINT.LOCATION OF SUB SERVICE PANEL,METER MAIN COMBO, PV LOAD CENTER& AC DISCONNECT MOUNTED ONEXTERIOR WALL OF A SINGLE FAMILYRESIDENCEPROPERTY LINE
CAL-FIRE ROOF LADDERACCESS POINTPROPERTY LINE
PROPERTY LINELOCATION OF "RAPID SHUTDOWN" ACDISCONNECT NEC 690.121. SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ONRESIDENTIAL STRUCTURE.2. THIS PROJECT HAS BEEN DESIGNED IN COMPLIANCEWITH THE CBC SECTION 1609 TO WITHSTAND A BASICWIND SPEED OF 110 MPH (3 SECOND GUST), WINDEXPOSURE C.3. THE ROOF MEMBERS ARE 2 "X 4" TRUSSES AT 24" ONCENTER. CONNECTION TO STRUCTURE SHALL NOT BEWITHIN 11" OF NAILING PLATES.4. THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOTOBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDINGROOF VENTS.5. ALL CONDUCTORS AND CONDUITS MOUNTED ON ROOFSHALL BE MINIMUM 7/8" ABOVE ROOF SURFACE(INCLUDING CABLES UNDERNEATH MODULES ANDRACKING).6. ROOF ACCESS POINTS SHALL BE PROVIDED PER THEFOLLOWING (CRC R324.6, CBC 3111.3.4)6.1. LOCATED IN AREAS NOT REQUIRING PLACEMENT OFGROUND LADDERS OVER OPENINGS SUCH ASDOORS OR WINDOWS.6.2. LOCATED AT STRONG POINTS OF CONSTRUCTION INLOCATIONS WHERE ACCESS POINT DOES NOTCONFLICT WITH OVERHEAD OBSTRUCTIONS SUCHAS: TREES, WIRES, OR SIGNS.7. SETBACKS AT RIDGES CAN BE REDUCED TO 18 INCHES INCOMPLIANCE 2022 CFC/2021 IFC 1205.2.1.2TOTAL PLAN VIEW AREA = 2203.08 SQFTTOTAL PV AREA FOR NEW SYSTEM= 8(67.79 IN)(44.64 IN)/(144 IN^2) = 168.12 SQFT=(168.12 SQFT/ 2203.08 SQFT)100 = 7.63%TOTAL PV AREA FOR EXISTING SYSTEM=8(64.57 IN)(39.29IN)/(144 IN^2) = 140.94 SQFT=(140.94SQFT/ 2203.08 SQFT)100 =6.39%TOTAL PV AREA FOR NEW AND EXISTING SYSTEM.(140.94+ 168.12 ) SQFT/ 2203.08 SQFT = 14.02%TOTAL PV AREA POPULATES 14.02% OF TOTAL PLANVIEW AREA AND IS WITHIN THE 33% REQUIREMENT.PROPERTY LINEPROPERTY LINEPROPERTY LINEACDWALKWAYLOCATION OF EXISTING ACDISCONNECT, PV PRODUCTIONMETER & LOAD CENTERLCPV LOAD CENTERLC(E) STRUCTURE ONPROPERTYCAL-FIRE ROOF LADDERACCESS POINTW SUNSWEPT AVEPM PV PRODUCTION METERPMACDSSPCAL-FIRE ROOF LADDERACCESS POINTExp: 06/30/20241410 N Parsons Pl -20181873 - DL4/10/2024
N6'6'SCALE: 3/16" = 1'-0"PV SYSTEM MOUNTING DETAILSEXISTING COMP SHINGLE ROOFUNIRAC FLASHLOC FOR COMPSHINGLE @ 72" O.C. MAXPROPOSED EVERESTCROSSRAIL RACKINGPROPOSED JA SOLARJAM54S31-395/MR (395W) PVSOLAR MODULESEXISTING 2 "X 4" ROOFTRUSSES @ 24"O.C.SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.PV-2Roof Azimuth: 90°Roof Tilt: 16°Roof Section 1Exp: 06/30/20241410 N Parsons Pl -20181873 - DL4/10/2024
ROOF SLOPE 910106217PV-3D52011121413151822PV-3D431542524238262D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALESHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.1. ROOF MATERIAL: COMP SHINGLE2. ROOF STRUCTURE: TRUSSES3. ATTACHMENT TYPE: UNIRAC FLASHLOC4. MODULE MANUFACTURER: JA SOLAR5. MODULE MODEL: JAM54S31-395/MR (395W)6. MODULE LENGTH: 67.79''7. MODULE WIDTH: 44.64"8. MODULE WEIGHT: 42.99 LBS.9. SEE SHEET S-1 FOR DIMENSION(S)10. MIN. FIRE OFFSET: 18"11. TRUSSES SPACING: 24" O.C.12. TRUSSES SIZE: 2 "X 4" NOMINAL13. LAG BOLT DIAMETER: 5/16 IN.14. LAG BOLT EMBEDMENT: 2.5 IN.15. TOTAL # OF ATTACHMENTS: 1616. TOTAL AREA: 168.12 SQ. FT.17. TOTAL WEIGHT: 343.92 LBS.18. WEIGHT PER ATTACHMENT: 21.50 LBS.19. DISTRIBUTED LOAD: 2.05 PSF20. MAX. HORIZONTAL STANDOFF: 72 IN.21. MAX. VERTICAL STANDOFF:LANDSCAPE: 26 IN., PORTRAIT: 43 IN.22. STANDOFF STAGGERING: YES23. RAIL MANUFACTURER AND MODEL(OR EQUIV.):EVEREST CROSSRAIL24. RAIL WEIGHT: 0.436 PLF.25. MAX. TRUSSES SPAN: 12 FT.26. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.PV-3Exp: 06/30/20241410 N Parsons Pl -20181873 - DL4/10/2024
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS:2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.E-1Conduit and Conductor ScheduleTagDescriptionWire Gauge# of ConductorsConduit TypeConduit Size1AP SYSTEM'S AC BUS CABLE12 AWG1N/A - Free AirN/A - Free Air1Bare Copper Ground (EGC/GEC)6 AWG1N/A - Free AirN/A - Free Air2THWN-2 (CU)10 AWG2EMT3/4"2THWN-2 - Ground (CU)8 AWG1EMT3/4"Inverter RatingsInverter Make/ModelAP SYSTEMDS3-LMax DC Volt Rating60VMax Continuous OutputPower768WMax Nominal Voltage240VMax AC Current3.2AMax OCPD Rating20ADESIGN TEMPERATURESASHRAE EXTREME LOW2°CASHRAE 2% HIGH30°CPV Module Ratings @ STCModule Make/Model JA SOLARJAM54S31-395/MR (395W)MODULEMax Power-Point Current (Imp)12.81AMax Power-Point Voltage (Vmp)30.84VOpen-Circuit Voltage (Voc)36.98VShort-Circuit Current (Isc)13.70AMax Series Fuse (OCPD)25ANominal Maximum Power at STC(Pmax)395WMaximum System Voltage1500VVoc Temperature Coefficient-0.275%/°C3THWN-2 (CU)8 AWG3EMT3/4"3THWN-2 - Ground (CU)8 AWG1EMT3/4"4THWN-2 (AL)1 AWG3EMT1-1/4"4THWN-2 - Ground (AL)6 AWG1EMT1-1/4"SYSTEM SUMMARYBRANCH #1INVERTERS PER BRANCH4MAX AC CURRENT12.8AMAX AC OUTPUT POWER3072WARRAY STC POWER3160WARRAY PTC POWER2949.6WMAX AC CURRENT12.8AMAX AC POWER3072WDERATED (CEC) AC POWER2846.36W1410 N Parsons Pl -20181873 - DL4/10/2024
(N) (8) JA SOLAR JAM54S31-395/MR (395W) WITH (4) AP SYSTEM DS3-L 2 IN 1 MICRO-INVERTERSATTACHED TO THE BACK OF MODULES1121PV CIRCUIT 1: 8 MODULES/PARALLEL [(4) AP SYSTEM DS3-L 2 IN 1]8720A15AN2(N) JUNCTION BOXWITH IRREVERSIBLEGROUND SPLICENOTE: IN BETWEEN EACH ARRAY THE EMT IS USED AS THEGROUNDING / BONDING, GROUND CLAMPS ARE AT EACHEND OF THE EMT CONDUIT WITH THE WIRE THEN FREEAIR'D TO THE GROUND CLAMP ON THE RACKING RAIL(N) 100A PV LOADCENTER3(N) VISIBLELOCKABLE2 POLE 60A'KNIFE' ACDISCONNECTACDISCONNECTTO BE LOCATEDWITHIN 10' OFMETER340ABACKFEEDBREAKER(N) 240V/125ASUB SERVICE PANELSINGLE PHASENMPOINT OF DELIVERY ANDINTERCONNECTIONN(E) GROUNDINGELECTRODE OR(UFER)EXISTING240V/100AMAIN SERVICE PANELSINGLE PHASEROOF TOPGROUND LEVEL -HOUSE EXTERIORAC DISCONNECTTO BE LOCATEDWITHIN 10' OFMETER(E) JUNCTION BOX WITHIRREVRESIBLE GROUNDSPLICE(E) 8 HYUNDAI M250ORG (250W) MODULES WITHAN ENPHASE M215-IG MICRO-INVERTERATTACHED TO THE BACK OF EVERY MODULE.ROOF TOPGROUND LEVEL -HOUSE EXTERIOREXISTING WIRE8PV CIRCUIT 1: 8 MODULES/PARALLEL12(E) VISIBLELOCKABLE2 POLE 30A'KNIFE' AC DISCONNECTEXISTING WIRE(E) PV SYSTEM IS RSD COMPLIANTEXISTING WIREEXISTING WIRE100A4ALL EXISTING LOADS ARERELOCATED FROM MAINSERVICE PANEL TO NEWSUB SERVICE PANELM (E) PVPRODUCTIONMETERN100ASHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS:2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.E-1.1METER # 222012785226NOTE:TOTAL AMPERAGE RATING OFALL OVERCURRENT DEVICES SUMMEDUP IN THE MAIN PANEL EXCLUDINGMAIN SUPPLY OVERCURRENT DEVICE,SHALL NOT EXCEED AMPACITY OF BUSBAR CEC 2022 705.12(B)(3)(3)SUB SERVICE PANEL240/120V 1Ø, 3WMAIN BUSS: 125AMAX BREAKER SIZE:(125A X 1.2) - 100A = 50A1410 N Parsons Pl -20181873 - DL4/10/2024
N
1.NOT ALL PLACARDS SHOWN MAY BE REQUIRED BY LOCAL AHJ. CONTRACTOR TO VERIFY PLACARDREQUIREMENTS WITH LOCAL AHJ BEFORE INSTALLATION.2.ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE3.ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC, ENGRAVED OR MACHINEPRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTCHED BY POPRIVETS OR SCREWS OR OTHER APPROVED METHOD.4.DIRECTORY PLACARD MARKING CONTENT AND FORMAT: RED BACKGROUND, WHITE LETTERING,MINIMUM 3/8" LETTER HIEGHT, ALL CAPITAL LETTERS, ARIAL OR SIMILAR FONT, NON BOLD, REFLECTIVEWEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT.PERMANENT SIGNAGE NOTES:WARNING!DO NOT RELOCATE THISOVERCURRENT DEVICEPOWER SOURCE OUTPUT CONNECTIONLABEL LOCATION:ADJACENT TO PV BREAKER (IF APPLICABLE).PER CODE(S): CEC 2022: 705.12(B)(3)(2)!DO NOT ADD LOADSPHOTOVOLTAIC SYSTEMCOMBINER PANELWARNINGLABEL LOCATION:PHOTOVOLTAIC AC COMBINER (IFAPPLICABLE).PER CODE(S): CEC 2022: 705.12(B)(3)(3)SOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNSOLAR ELECTRICPV PANELSTURN RAPID SHUTDOWNSWITCH TO THE "OFF"POSITION TO SHUT DOWNPV SYSTEM AND REDUCESHOCK HAZARD IN THEARRAY.LABEL LOCATION:ON OR NO MORE THAT 3 M (10 FT) FROM THE SERVICEDISCONNECTING MEANS TO WHICH THE PV SYSTEMSARE CONNECTED.ELECTRICAL SHOCK HAZARDWARNING!LABEL LOCATION:INVERTER(S), AC DISCONNECT(S), ACCOMBINER PANEL (IF APPLICABLE).PER CODE(S): CEC 2022: 690.13(B)& 706.15(C)(4)TERMINALS ON LINE AND LOADSIDES MAY BE ENERGIZED INTHE OPEN POSITIONRAPID SHUTDOWN SWITCHFOR SOLAR PV SYSTEMLABEL LOCATION:UTILITY SERVICE ENTRANCE/METER, INVERTER/DCDISCONNECT IF REQUIRED BY LOCAL AHJ, OROTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.PER CODE(S): CEC 2022: 690.56(C)(2),CFC 2022: 1204.5.3POWER TO THIS BUILDING ISALSO SUPPLIED FROM THEFOLLOWING SOURCES WITHDISCONNECTS AS SHOWNCAUTION:MAXIMUM AC OPERATING CURRENT:NOMINAL OPERATING AC VOLTAGE:12.8 AMPS240.0 VACPHOTOVOLTAIC AC DISCONNECTLABEL LOCATION:AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OFINTERCONNECTION.PER CODE(S): CEC 2022: 690.54SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS:2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.E-2LOCATION OF EXISTING ACDISCONNECT & PVPRODUCTION METERWARNING!THIS EQUIPMENT FED BY MULTIPLESOURCES. TOTAL RATING OF ALLOVERCURRENT DEVICES, EXCLUDINGMAIN SUPPLY OVERCURRENTDEVICE, SHALL NOT EXCEEDAMPACITY OF BUSBAR.PV INTERCONNECTION POINT.LOCATION OF SUB SERVICE PANEL, METER MAINCOMBO, PV LOAD CENETER & AC DISCONNECT1410 N PARSONS PL(N) SOLAR PANELS ANDMICROINVERTERS ON ROOF(E) PV SYSTEM IS RSD COMPLIANT(E) SOLAR PANELS &MICRO-INVERTERS ON ROOFW SUNSWEPT AVEMAXIMUM AC OPERATING CURRENT(NEW AND EXISTING SYSTEM):NOMINAL OPERATING AC VOLTAGE:20 AMPS240.0 VACPHOTOVOLTAIC AC DISCONNECTLABEL LOCATION:AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OFINTERCONNECTION.PER CODE(S): CEC 2022: 690.541410 N Parsons Pl -20181873 - DL4/10/2024
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:3/14/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.E-1Conduit and Conductor ScheduleTagDescriptionWire Gauge# of ConductorsConduit TypeConduit Size1 AP SYSTEM'S AC BUS CABLE 12 AWG1 N/A - Free Air N/A - Free Air1Bare Copper Ground (EGC/GEC)6 AWG1 N/A - Free Air N/A - Free Air2THWN-2 (CU)10 AWG2EMT3/4"2THWN-2 - Ground (CU)8 AWG1EMT3/4"Inverter RatingsInverter Make/ModelAP SYSTEMINC. DS3-L[240V] [SI1-SB]Max DC Volt Rating60VMax Continuous OutputPower768WMax Nominal Voltage240VMax AC Current3.2AMax OCPD Rating20ADESIGN TEMPERATURESASHRAE EXTREME LOW2°CASHRAE 2% HIGH30°CPV Module Ratings @ STCModule Make/Model JA SOLARJAM54S31-395/MR (395W)MODULEMax Power-Point Current (Imp)12.81AMax Power-Point Voltage (Vmp)30.84VOpen-Circuit Voltage (Voc)36.98VShort-Circuit Current (Isc)13.70AMax Series Fuse (OCPD)25ANominal Maximum Power at STC(Pmax)395WMaximum System Voltage1500VVoc Temperature Coefficient-0.275%/°C3THWN-2 (CU)8 AWG3EMT3/4"3THWN-2 - Ground (CU)8 AWG1EMT3/4"4THWN-2 (AL)1 AWG3EMT1-1/4"4THWN-2 - Ground (AL)4 AWG1EMT1-1/4"SYSTEM SUMMARYBRANCH #1INVERTERS PER BRANCH4MAX AC CURRENT12.8AMAX AC OUTPUT POWER3072WARRAY STC POWER3160WARRAY PTC POWER2949.6WMAX AC CURRENT12.8AMAX AC POWER3072WDERATED (CEC) AC POWER2846.36W1410 N Parsons Pl -20181873 - DL4/10/2024
(N) (8) JA SOLAR JAM54S31-395/MR (395W) WITH (4) AP SYSTEM INC. DS3-L [240V] [SI1-SB] 2 IN 1MICRO-INVERTERS ATTACHED TO THE BACK OF MODULES1121PV CIRCUIT 1: 8 MODULES/PARALLEL [(4) AP SYSTEM DS3-L 2 IN 1]8720A15AN2(N) JUNCTION BOXWITH IRREVERSIBLEGROUND SPLICENOTE: IN BETWEEN EACH ARRAY THE EMT IS USED AS THEGROUNDING / BONDING, GROUND CLAMPS ARE AT EACHEND OF THE EMT CONDUIT WITH THE WIRE THEN FREEAIR'D TO THE GROUND CLAMP ON THE RACKING RAIL(N) 100A PV LOADCENTER3(N) VISIBLELOCKABLE2 POLE SQUARED DU222RB 60A'KNIFE' ACDISCONNECTACDISCONNECTTO BE LOCATEDWITHIN 10' OFMETER3ROOF TOPGROUND LEVEL -HOUSE EXTERIORAC DISCONNECTTO BE LOCATEDWITHIN 10' OFMETER(E) JUNCTION BOX WITHIRREVRESIBLE GROUNDSPLICE(E) 8 HYUNDAI M250ORG (250W) MODULES WITHAN ENPHASE M215-IG MICRO-INVERTERATTACHED TO THE BACK OF EVERY MODULE.ROOF TOPGROUND LEVEL -HOUSE EXTERIOREXISTING WIRE8PV CIRCUIT 1: 8 MODULES/PARALLEL12(E) VISIBLELOCKABLE2 POLE 30A'KNIFE' AC DISCONNECTEXISTING WIRE(E) PV SYSTEM IS RSD COMPLIANTEXISTING WIREEXISTING WIREM (E) PVPRODUCTIONMETERN100A40ABACKFEEDBREAKER(N) 240V/125ASUB SERVICE PANELSINGLE PHASEMPOINT OF DELIVERY ANDINTERCONNECTION100AN(E) GROUNDINGELECTRODE OR(UFER)EXISTING240V/100AMAIN SERVICE PANELSINGLE PHASEN4ALL EXISTING LOADSRELOCATED FROM MAINSERVICE PANEL TO NEWSUB SERVICE PANEL15A/1P15A/2P15A/1P20A/2P20A/2P20A20A20A/2P20A/2P(E)QUAD BREAKER20A/20ASHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:3/14/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS:2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.E-1.1METER # 222012785226NOTE:TOTAL AMPERAGE RATING OFALL OVERCURRENT DEVICES SUMMEDUP IN THE MAIN PANEL EXCLUDINGMAIN SUPPLY OVERCURRENT DEVICE,SHALL NOT EXCEED AMPACITY OF BUSBAR CEC 2022 705.12(B)(3)(3)SUB SERVICE PANEL240/120V 1Ø, 3WMAIN BUSS: 125AMAX BREAKER SIZE:(125A X 1.2) - 100A = 50APANEL SCHEDULE OF 125ANEW SUB SERVICE PANEL1KITCHEN OUTLETS20A2SPARE ROOM20A3OUTLETS20A4LIGHTS20A520A620A7815A9KITCHEN/ HALLWAYSPAREHEATERSR.NODESCRIPTIONBREAKER SIZEREFRIGERATOR15A15ALIGHTS20AUPSTAIRS101410 N Parsons Pl -20181873 - DL4/10/2024
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-1Exp: 06/30/2024Structural Only1410 N Parsons Pl -20181873 - DL4/10/2024
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-2Exp: 06/30/2024Structural Only1410 N Parsons Pl -20181873 - DL4/10/2024
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-3Exp: 06/30/2024Structural Only1410 N Parsons Pl -20181873 - DL4/10/2024
SHEETCONTRACTORSOLGEN CONSTRUCTION LLC.1410 N PARSONS PL, SANTA ANA, CA 92703APN:10046201DATE:1/3/2024KINGSTONRESIDENCELicense#: C-10 1053344ADDRESS: 2072 N MAIN ST FL 2, LOGAN UT 84341-1993 CSLB#: 1053344DESIGNER: OAVCORE ENERGY GROUP.S-4Exp: 06/30/2024Structural Only1410 N Parsons Pl -20181873 - DL4/10/2024