HomeMy WebLinkAbout1414 S Shelton St - 101121213 & 20184273 & 20184973 - PlanPAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
LTD: LR5-54HABB-400M
TESLA: POWERWALL 3 1707000-XX-Y
SNR-DC-00335 [FLAT, TILT KIT (ROLLED COMP/ MEMBRANE/
FOAM) 1 LAG OMNIBASE]
1707000-XX-Y
MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A).
MODULES, ARE CLASS A FIRE RATED.
CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30
SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE
ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N)NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-2.1 ELEVATION DETAIL
VIEW
PV-3.0 LAYOUT
PV-3.1 MOUNTING DETAIL
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL CALCS
PV-4.2 BACKUP LOAD CALCS
PV-4.3 PANEL SCHEDULE
PV-5.0 SIGNAGE
PV-5.1 SIGNAGE
NOTE: CEC 2022: 705.12(B)(3)(3): THIS EQUIPMENT FED BY
MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT
DEVICES EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE
SHALL NOT EXCEED AMPACITY OF BUSBAR.
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46PLPLPLPLPLPLPLPLPLPLPLPLPLPL
SITE PLAN
PV-2.0
#SSTAMPSP
#ESTAMPSP
SITE PLAN - SCALE = 1/16" = 1'-0"
ARRAY
PITCH
PV AREA
(SQFT)
AR-01 3° 189.2
TRUE
AZIM
MAG
AZIM
168°180°
POWERWALL ENERGY
STORAGE SYSTEM (ESS)
BG BACKUP GATEWAY
GP GENERATION PANEL
ELECTRIC VEHICLE
SUPPLY EQUPMENTEV
MAIN PANEL
INVERTER(S)
AC DISCONNECT(S)
DC DISCONNECT(S)
SUNRUN METER
DEDICATED PV METER
SERVICE ENTRANCE
INTERIOR EQUIPMENT
SHOWN AS DASHED
SE
MP
SM
PM
INV
AC
DC
SUB-PANELSP
CB IQ COMBINER BOX
METER ADAPTERMA
GROUNDING
ELECTRODE
ENERGY STORAGE
SYSTEM
BP BACKUP LOADS PANEL
BI BACKUP INTERFACE 1 COMMUNICATION
WIRESAM
MD MICROGRID
INTERCONNECT DEVICE
ACREL METER
SOLAREDGE METERSEMPV LOAD CENTERLC
LEGEND
SCALE: NTS
NOTE: NOT ALL ITEMS IN LEGEND
WILL APPEAR IN SITE PLAN
RAIL
STANDOFFS &
FOOTINGS
SOLAR
MODULES
NOTES:
RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
TOTAL ROOF SURFACE AREA: 2223 SQFT.
TOTAL PV ARRAY AREA (E+N): 489.06 SQ FT.
PERCENTAGE PV COVERAGE (E+N):
(TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
AREA) * 100 = 22%
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4.
ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT
WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED
ON LARGE/SCALE FIRE TESTING.
(N) ARRAY AR-01
SE
MP
INV
(E) PV ARRAY
(E) PV EQUIPMENT
MD RSD
INV
AC
BPAC
INV
AC
(E) FENCE
(E) GATE (TYP.)
(E) DETACHED
STORAGE SHED
(NO ELECTRICAL)S SHELTON STA A A A A A
B B B
(E) FLAT ROOF STRUCTURE CONNECTED
STRUCTURALLY TO RESIDENCE
(E) RESIDENCE
3'-8"4'-6"
3'-3"
4'-1"
21'-9"22'-7"
5'-1"
29'-4"
39'-1"
5'-4"
54'-3"
42'-9"
33'-4"
4'-4"3'-6"
B
Signed 10/15/2024
1414 S Shelton St
12/2/2024
EXTERIOR WEST WALL
PAGE
REV: B 10/14/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
ESS ELEVATION
VIEW
PV-2.1
ESS ELEVATION VIEW
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4.
ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT WHERE SMALLER
SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON LARGE/SCALE FIRE TESTING.
SITE PLAN - SCALE = 3/32" = 1'-0"
AC DISCONNECT
INVERTER + ESS
BACKUP LOAD PANEL
BACKUP GATEWAY
RAPID SHUTDOWN
SWITCH
(E) AC DISCONNECT
(E) INVERTER
MSP Signed 10/15/2024
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
D1 - AR-01 - SCALE: 0.010417
AZIM:180°
PITCH: 3°
#SSTAMP
DESIGN CRITERIA
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED:
96 MPH 3-SEC GUST.
FASTENERS:
(1) 5/16" DIA S.S. LAG SCREW: 2.5"
MIN EMBEDMENT INTO FRAMING
PV-3.0
LAYOUT
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION
Name Type Height Type
Max
Span
OC
Spacing Detail Max Landscape
OC Spacing
Max Landscape
Overhang
Max Portrait
OC Spacing
Max Portrait
Overhang Configuration
AR-01
FLAT, ROLLED COMP
[TILT KIT] - OMNIBASE 1
LAG - UR
1-Story 2X8 RAFTERS 15'-2" 16"
ULTRA RAIL, SYSTEM DETAIL, FIXED TILT:
SNR-DC-00335 [FLAT, TILT KIT (ROLLED
COMP/ MEMBRANE/ FOAM) 1 LAG
OMNIBASE]
5'-4"2'-1"5'-4"2'-1"STACKED
SEE SITE PLAN FOR NORTH ARROW
INSTALLERS SHALL NOTIFY ENGINEER OF ANY
POTENTIAL STRUCTURAL ISSUES OBSERVED
PRIOR TO PROCEEDING W/ INSTALLATION.
NOTES TO INSTALLER:
LOCATION OF RAFTERS AND PENETRATIONS
* IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12"
BOUNDARY REGION OF ANY ROOF PLANE
EDGES (EXCEPT VALLEYS), THEN
ATTACHMENTS NEED TO BE ADDED AND
OVERHANG REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS FOLLOWS:
** ALLOWABLE ATTACHMENT SPACING
INDICATED ON PLANS TO BE REDUCED BY 50%.
** ALLOWABLE OVERHANG INDICATED ON
PLANS TO BE 1/5TH OF ALLOWABLE
ATTACHMENT SPACING INDICATED ON PLANS.
MODULE ELEVATION DETAIL - SCALE: NTS
2'-2"
1'-2"10°10°
ROOF PITCH, SEE NOTES MODULE PITCH, SEE NOTES
10"22'-8"10'-7"
1'-2"
13'-2"
2'-11"
5'-4" TYP 2'-2"
Signed 10/15/2024
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
MOUNTING DETAIL
PV-3.1
THE SNAPNRACK FIXED TILT IS A SIMPLE
SOLUTION FOR INSTALLATIONS
REQUIRING MODULE TILT BEYOND THE
EXISTING ROOF SLOPE. IT IS DESIGNED
FOR TILT ANGLES FROM 0°-30° ABOVE
THE HORIZONTAL UTILIZING FIXED
STANDOFF HEIGHTS
THE SNAPNRACK FIXED TILT IS
COMPATIBLE WITH THE VARIOUS
SNAPNRACK ROOF ATTACHMENTS
SHOWN. REFER TO SPECIFIC
"ATTACHMENT DETAIL"
REFER TO SNAPNRACK ENGINEERING
CHARTS FOR APPLICABLE RAIL SPANS.
"BIN" NUMBER ON CHART SHOULD MATCH
"BIN" NUMBER ON THIS DRAWING
REFER TO THE SNAPNRACK INSTALLATION
MANUAL FOR 5 16"Ø HARDWARE TORQUE
SPECIFICATIONS
FOR ADDITIONAL SYSTEM
REQUIREMENTS, INCLUDING MODULE
OVERHANG, SEE "SNR-DC-00329 ULTRA
RAIL, SYSTEM OVERVIEW, TYPICAL"
FOR LEVELING REQUIREMENTS SEE
"SNR-DC-00334 ULTRA RAIL, COMPONENT
DETAIL, LEVELING SPACER ON STANDOFF"
SNAPNRACK OMNIBASE CAN MOUNT IN
ANY ORIENTATION ON THE ROOF
RAILS CAN MOUNT ON ANY SIDE OF THE
STANDOFF POST
FOR "ROOF PITCH" GREATER THAN 7°,
"TILT ANGLE" MUST BE IN SAME
DIRECTION AS "ROOF PITCH"
UR-40 RAIL | UR-60 RAIL
FOR USE WITH SNAPNRACK ULTRA SERIES RAILS
21 4"
11 2"
11 2"
15 8"
FIXED TILT, INSTALLED
ALLOWABLE ANGLES
A
DETAIL A
FIXED TILT, FRONT LEG
(RAIL HIDDEN)
B
DETAIL B
FIXED TILT, REAR LEG
TILT ANGLE, RELATIVE
TO HORIZONTAL
(30° MAX)
METAL ROOF BASE:
BIN 10
DETAIL: SNR-DC-00352
DETAIL: SNR-DC-00353
1-HOLE BASE:
BIN 10
DETAIL: SNR-DC-00348
DETAIL: SNR-DC-00349
4-HOLE BASE:
BIN 11
DETAIL: SNR-DC-00350
DETAIL: SNR-DC-00357
DETAIL: SNR-DC-00358
DETAIL: SNR-DC-00359
*COMPATIBLE ROOF ATTACHMENTS FOR FIXED TILT
PV MODULE, TYP.
SNAPNRACK
ULTRA RAIL
ROOF DECKING,
(ROOFING MATERIAL
NOT SHOWN)
STRUCTURAL MEMBER,
WOOD RAFTER SHOWN
PV MODULE, TYP.SNAPNRACK
MODULE CLAMPS
ROOF PITCH, VARIES
TILT ABOVE
ROOF SURFACE
(5°-30°)
OMNIBASE
BIN 10
DETAIL: SNR-DC-01249
DETAIL: SNR-DC-01250
DETAIL: SNR-DC-01251
DETAIL: SNR-DC-01252
DETAIL: SNR-DC-01253
DETAIL: SNR-DC-01254
SNAPNRACK FIXED
TILT, REAR LEG
(LENGTH VARIES)
SNAPNRACK FIXED
TILT, FRONT LEG
(LENGTH VARIES)
SNAPNRACK FIXED
TILT, REAR LEG
(LENGTH VARIES)
SNAPNRACK FIXED
TILT, FRONT LEG
(LENGTH VARIES)
SNAPNRACK AP 90 L FOOT
WITH UR MOUNT HARDWARE
5 16"-18 BOLT WITH
SERRATED FLANGE NUT, S.S.
SNAPNRACK
STANDOFF CLAMP
SNAPNRACK STANDARD
STANDOFF, LENGTH VARIES:
5-1 2" OR 10"
SNAPNRACK ROOF ATTACHMENT - COMPATIBLE
WITH ATTACHMENTS SHOWN ABOVE. REFER TO
SPECIFIC SNAPNRACK "ATTACHMENT DETAIL"
SNAPNRACK STANDARD
STANDOFF, LENGTH VARIES:
10", 14" OR 23"
Signed 10/15/2024
1414 S Shelton St
12/2/2024
PAGE
REV: C 10/25/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
BACKUP LOADS
LOAD BREAKER RATING
(AMPS)LABEL DEMAND
LOAD
1 20A-1P LIGHTS & RECEPTABLES 1500 VA
2 20A-1P LIGHTS & RECEPTABLES 1500 VA
3 20A-1P LIGHTS & RECEPTABLES 1500 VA
4 20A-1P LIGHTS & RECEPTABLES 1500 VA
5 20A-1P BED 1500 VA
6 20A-1P KITCHEN 1500 VA
7 20A-1P DISPOSAL 1500 VA
8 20A-1P FRIDGE 1500 VA
9 30A-2P 240V GARAGE OUTLET 5760 VA
PV-4.2
#ESTAMP
BACKUP LOAD
CALCS
BACKUP LOAD CALCS
ALL BACKED UP LOADS ABOVE IN THE BACKED UP LOADS PANEL ARE RELOCATED FROM THE MAIN SERVICE
PANEL.
BACKED UP LOADS CALCULATION:
(5760 VA)/ 240V = 24 A PER CEC 2022 ARTICLE 690.10 OR NEC 2020 ARTICLE 710.15.
THE MAXIMUM CURRENT FOR ALL LARGE APPLIANCES LOADS IS 24A.
(MAX LOADS OUTPUT) X (CONTINUOUS LOADS) =
24 A X 1.25 = 30 A
BACKED UP LOADS PANEL BREAKER = 150A
100 A < 150A.
THEREFORE, THE AMPERAGE OF THE BACKED UP LOADS IS LESS THAN THAT OF THE OCPD.
AC WIRE SIZING FOR BACKUP LOADS PANEL
MAX AC OUTPUT CURRENT = (MAX LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
24 A X 1.25 = 30 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
30A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
C
1414 S Shelton St
12/2/2024
PAGE
REV: C 10/25/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
CONDUIT SCHEDULE
TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT
1 Inverter Input (2) 10 AWG (PV WIRE)N/A (1) 6 AWG (BARE)Open Air
2 Inverter Input (2) 10 AWG THHN/THWN-2 N/A (1) 8 AWG THHN/THWN-2 3/4 EMT
3 Inverter Output (2) 6 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2 3/4 EMT
4 Panel Feeder (2) 1/0 AWG THHN/THWN-2 (1) 1/0 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2 1 1/2 EMT
5 Backup Load
(8) 10 AWG THHN/THWN-2 (8) 10 AWG THHN/THWN-2
(1) 8 AWG THHN/THWN-2 1 1/4 EMT
(2) 10 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2
E EXISTING
EXISTING 200A
MAIN BREAKER
END FED
EXISTING 200A
MAIN PANEL
200A BUS
M
150A
CTRL
M
NEW 200A
BACKUP GATEWAY
(2) - 60A PV +ESS BREAKER
(1) (E) 20A PV BREAKER
IN (N) INTERNAL
PANELBOARD
4
A
A
NEW 225 A
BACK UP LOADS PANEL
WITH 150 A MAIN BREAKER
RELOCATED (E) LOADS
4
(N) IMO PE69-3020,
DISCONNECT
SWITCH, 3P, 16A
RSD
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT
3
J-BOX
LONGI GREEN ENERGY TECHNOLOGY CO LTD:
LR5-54HABB-400M
STRING 1 OF 6 MODULES
2 MODULE LEVEL
RAPID SHUTDOWN DEVICES
12
RSD
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT
3 J-BOX
LONGI GREEN ENERGY TECHNOLOGY CO LTD:
LR5-54HABB-400M
STRING 1 OF 3 MODULES
1 MODULE LEVEL
RAPID SHUTDOWN DEVICES
12
POINT OF INTERCONNECTION CEC 2022:705.12(B)(3)(3), LOAD
BREAKER AT OPPOSITE END OF BUSBAR
METER
NUMBER: 222013-458849
EQUIPMENT CHARACTERISTICS
INCLUDED IN SPEC SHEETS
NOTE: TOTAL PV BACKFEED (E+N)
= 140A USED FOR INTERCONNECTION CALCULATIONS
Existing Inverter(s)E
SolarEdge Technologies: SE3800H-USMN
J-BOX
14 JA SOLAR: JAM54S31-395/MR
12
E20A OCPD
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB, 60A , 2P
120/240VAC
3
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB, 60A , 2P
120/240VAC
3
E
(E) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU324RB
3R, 30A , 2P
120/240VAC
E
60A
60A
5
FACILITY
GROUND
PV-4.0
ELECTRICAL
#ESTAMP
GENERAL NOTES:
GROUNDS RODS OR COLD WATER GAS BOND
BREAKER CONDUCTORS IN TWO SEPARATE CONDUITS.
CONDUCTOR SIZINGS ARE SUBJECT TO CHANGE AT TIME OF
INSTALlATION IF THE BACKUP LOADS ARE RELOCATED MORE THAN
2' FROM THEIR CURRENT INTERCONNECTION POINT TO COMPLY
WITH CEC 310.15(C)(1).
MODULE CHARACTERISTICS
LONGI GREEN ENERGY
TECHNOLOGY CO LTD:
LR5-54HABB-400M
400 W
OPEN CIRCUIT VOLTAGE 37.05 V
MAX POWER VOLTAGE 30.94 V
SHORT CIRCUIT CURRENT 13.72 A
C
C
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
PV-4.1
ELECTRICAL CALCS
#ESTAMP
ELECTRICAL CALCS
SYSTEM INFORMATION
3.6 KW DC PHOTOVOLTAIC SYSTEM
(6) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
(3) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
SYSTEM OCPD SIZE
(COMBINED MAX CURRENT) X (CONTINUOUS LOAD) =
112 A X 1.25 = 140 A → 140 A OVERCURRENT PROTECTIO
ALLOWABLE BACKFEED
MAX ALLOWED TOTAL GENERATION BACKFEED OCPD = MAIN BREAKER RATING =
200A
LOADS IN MAIN PANEL: 00A LOADS + 150A GATEWAY BREAKER = 150A ≤ 200A
INTERCONNECTION MEETS CEC 2022: 705.12(B)(3)(3) REQUIREMENTS.
GATEWAY SYSTEM AC WIRE SIZING
MAX AC OUTPUT CURRENT = 150 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 170A = 154.7A
TERMINAL RATING[110.14(C)] =
1/0AWG, 75°C RATED = 150A
150A < 154.7A TERMINAL RATING GOVERNS CONDUCTOR SIZING
150A < 150A 1/0 AWG AMPACITY OK
THEREFORE 1/0 AWG IS SUFFICIENT.
INVERTER INFORMATION
2400 KW DC PHOTOVOLTAIC SYSTEM
(6) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS LOAD)[690.8(B)(1)]=
13.72A X 1.25 X 1.25 = 21.43A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
21.43A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG, 75°C RATED = 65A
65A < 68.25A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A → 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT.
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] + VOC} X (# MODULES /
STRING) =
{[(-0.26 %/°C X 37.05 V) / 100] X [-2 °C - 25 °C] + 37.05 V} X 6 = 238 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 13.72A X 1 = 17.15
INVERTER INFORMATION
1200 KW DC PHOTOVOLTAIC SYSTEM
(3) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3
1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS
LOAD)[690.8(B)(1)]=
13.72A X 1.25 X 1.25 = 21.43A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
21.43A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG, 75°C RATED = 65A
65A < 68.25A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A → 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT.
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] +
VOC} X (# MODULES / STRING) =
{[(-0.26 %/°C X 37.05 V) / 100] X [-2 °C - 25 °C] + 37.05 V} X 0 = 119 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 13.72 A X 1 = 17.15A
1414 S Shelton St
12/2/2024
#ESTAMP
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20200
PANEL
SCHEDULE
PAGE
REV: C 10/25/24
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN/TMK #: APN: 013-051-21
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
PV-4.3
PANEL SCHEDULE
225/200A FUTURE
MAIN PANEL
150(N) GATEWAY
FEEDER
BREAKER
MAIN BREAKER
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20
150
225/150A FUTURE
BACKUP LOAD PANEL
MAIN BREAKER
240 V GARAGE OUTLET30
20LIGHTING & RECEPTABLES
LIGHTING & RECEPTABLES 202020LIGHTING & RECEPTABLES
LIGHTING & RECEPTABLES 2020BED
KITCHEN
2020DISPOSAL
FRIDGE
FUTURE 200A BACKUP
GATEWAY
602
4
6
8
10
12
14
16
18
20
NEW PV+ESS
BREAKER60
20NEW PV+ESS
BREAKER
EXISTNG PV
BREAKER
1
3
5
7
9
11
13
15
17
19
C
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.0
#ESTAMP
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48.00 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
POWER SOURCE OUTPUT CONNECTION
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
CEC 2022: 705.12(B)(3)(2)
NOTES AND SPECIFICATIONS:
SIGNS AND LABELS SHALL MEET THE
REQUIREMENTS OF THE CEC 2022
ARTICLE 110.21(B), UNLESS SPECIFIC
INSTRUCTIONS ARE REQUIRED BY
SECTION 690, OR IF REQUESTED BY
THE LOCAL AHJ.
SIGNS AND LABELS SHALL
ADEQUATELY WARN OF HAZARDS
USING EFFECTIVE WORDS, COLORS
AND SYMBOLS.
LABELS SHALL BE PERMANENTLY
AFFIXED TO THE EQUIPMENT OR
WIRING METHOD AND SHALL NOT BE
HAND WRITTEN.
LABEL SHALL BE OF SUFFICIENT
DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED.
SIGNS AND LABELS SHALL COMPLY
WITH ANSI Z535.4-2011, PRODUCT
SAFETY SIGNS AND LABELS, UNLESS
OTHERWISE SPECIFIED.
DO NOT COVER EXISTING
MANUFACTURER LABELS.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
4"
3"
ELECTRICAL SHOCK HAZARD
WARNING
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S),
AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC
2022: 690.13(B)
!
INVERTER 1
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
PER CODE(S): NEC 2020: 705.10, 710.10. CEC 2022: 705.10, 710.10
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:
690.31(D)(2)
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC
2022: 705.12(C)
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
ENERGY STORAGE SYSTEM
DISCONNECT
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
THIS EQUIPMENT FED BY
MULTIPLE SOURCES. TOTAL
RATING OF ALL OVERCURRENT
DEVICES EXCLUDING MAIN
SUPPLY OVERCURRENT DEVICE
SHALL NOT EXCEED AMPACITY OF
BUSBAR
WARNING!
LABEL LOCATION:
PV LOAD CENTER (IF APPLICABLE) AND
ANY PANEL THAT UTILIZES "THE SUM
OF BREAKERS RULE".
PER CODE(S): NEC 2020: 705.12 (B)(3)(3),
CEC 2022: 705.12 (B)(3)(3)
ENERGY STORAGE SYSTEM
PREMISES WIRING MAY REMAIN
ENERGIZED AFTER LOSS OF
UTILITY POWER
CAUTION!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C)
CAUTION
1414 S SHELTON ST, SANTA ANA, CA, 92707
SOLAR PANELS
ON ROOF
AC DISCONNECT
INVERTER + ESS (EXT)
BACKUP GATEWAY
AND PV BREAKER
DISCONNECT BACKUP LOADS PANEL
RAPID SHUTDOWN SWITCH
SERVICE ENTRANCE AND
GATEWAY FEEDER
BREAKER
MULTIPLE SOURCES OF POWER
(E) PV EQUIPMENT
(E) PV ARRAY
PV SYSTEM(S) ARE EQUIPPED WITH
RAPID SHUTDOWN DEVICE(S)
RAPID SHUTDOWN DISCONNECT LOCATION
(EXISTING SYSTEM AC DISCONNECT)
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48.00 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.1
#ESTAMP
LABEL LOCATION:
BACKUP LOAD PANEL
NO ADDITIONAL
LOADS TO BE
ADDED
ONLY THIS
INVERTER HAS
RAPID SHUT DOWN
ENERGY STORAGE SYSTEM DISCONNECT
NOMINAL ESS VOLTAGE VAC
LABEL LOCATION:
MAIN PANEL.
120 240
NEC 2020 - PW3
PER CODE(S): NEC 706.15(C)
1414 S Shelton St
12/2/2024
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 1 of 8 GFT-OP-11a (22-August-2019) Test Verification of Conformity Verification Number: 104514208CRT-001VOC Applicant Name & Address: Tesla Inc. 3500 Deer Creek Road, Palo Alto, CA 94304 Product Description: Energy Storage System Grid Support Utility Interactive & Standalone Inverter Ratings & Principle Characteristics: See Appendix 2 Models/Type References: 1707000- followed by two numbers; followed by -; followed by one letter. Brand Names: Tesla Relevant Standard(s) / Specification(s): See Appendix 1 Verification Issuing Office Name & Address: Intertek Testing Services NA, Inc. 3933 US Route 11, Cortland, NY 13045 USA Date of Tests: 9/15/2022 to 4/23/2024 Test Report Number(s): 104514208CRT-001, 104514208CRT-001RRF, 104514208CRT-001TRS, 104514208CRT-010, 104514208CRT-012 Additional information in Appendix. Signature Name: Mukund Rana Position: Sr. Staff Engineer Date: 10th May 2024 On the basis of the tests undertaken, the samples of the below product have been found to comply with the requirements of the referenced standards at the time the tests were carried out. This verification is part of the full test report and should be read in conjunction with it. This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 2 of 8 GFT-OP-11a (22-August-2019) Appendix 1: Relevant Standard(s)/Specification(s) Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3] Grid Support Utility Interactive Equipment - Supplement SA to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement SA)] Grid Support Utility Interactive Inverters and Converters Based Upon IEEE 1547:2018 & IEEE 1547.1:2020 - Supplement SB to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement SB)] Energy Storage Systems and Equipment [ANSI/UL 9540:2020 Ed.2+R:09Apr2021] Photovoltaic (PV) DC Arc-Fault Circuit Protection [UL 1699B:2018 Ed.1+R:18May2021] Software in Programmable Components [UL 1998:2013 Ed.3+R:24Sep2018] Tests For Safety-related Controls Employing Solid-state Devices [UL 991:2004 Ed.3+R:09Jun2010] Batteries for Use in Stationary, Vehicle Auxiliary Power and Light Electric Rail (LER) Applications [ANSI/UL 1973:2018 Ed.2] IEEE 1547:2018 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces IEEE 1547a:2020 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces Amendment 1: To Provide More Flexibility for Adoption of Abnormal Operating Performance Category III IEEE 1547.1:2020 - IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated Interfaces Source requirements document UL 1741 (SRD) v2.0 – HECO Electric Rule No.21-2020 Generating Facility Interconnections Default New England Bulk System Area Settings Requirement PRC-024-3 Frequency and Voltage Protection Settings for Generating Resources GOVERNMENT OF PUERTO RICO PUBLIC SERVICE REGULATORY BOARD PUERTO RICO ENERGY BUREAU, Generating Facility and Microgrid Interconnection Regulation (“Regulation”), July 2021 Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2] Safety Functions Incorporating Electronic Technology [CSA C22.2#0.8:2019 Ed.4] 1414 S Shelton St12/2/2024
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 3 of 8 GFT-OP-11a (22-August-2019) Appendix 2: Ratings & Principle Characteristics: ➢ Ratings: Models 1707000-xx-y Rated AC Output Power (W) 11500, 10000, 7680, 5750 Rated AC Input Power (W) Charging 5000 Max. Cont. Output Power (W) 11500, 10000, 7680, 5750 Max. Continuous Output PV to AC Power Off-Grid (W) 15400 Max. Cont. Input Power (W) Charging 5000 AC Input / Output Voltage (VL-L) 240 AC Output Frequency (Hz) 60 Max. Cont. Output Current (A) 48, 41.6, 32, 24 Max. Cont. Input Current (A) Charging 20.83 Apparent Power rating (VA) 11500, 10000, 7680, 5750 Apparent Power rating (VA) Charging 5000 Normal Category A, B Abnormal Category II, III ➢ Communication Protocol: IEEE 2030.5 protocol ➢ PCH board MD5 Firmware checksum: c5773b136a9ef9be9057302a67258482 ➢ TACO board MD5 Firmware checksum: dcq8OiBXbQWYnK9UhCAjvl02/py2MZymmwAQYOn8jSc= ➢ Grid Support Function Parameters: Tesla used the parameters in the Result reporting form “104514208CRT-001RRF” during the testing of the grid support functions according to UL1741 SB. The parameters that have “blank” as their value are not applicable. ➢ UL 1998 and CSA C22.2#0.8 Evaluation: ECU / Board Rev Software version Checksum UL1998, CSA C22.2#0.8 Compliant* Date of evaluation HVP / -E V2 51705DB5 Yes Apr-19-2024 PWS / -3F V2 34204954 Yes Apr-19-2024 PWS / -1F V2 B3C1375B Yes Apr-19-2024 PWS / -D V2 43FEF523 Yes Apr-19-2024 *Note: Below safety functions were evaluated during the UL1998 and UL 991 evaluation. • List of all UL1998 and UL 991 functions are as follow: o Overcharge o Over-discharge o Over Temperature o Over current o Relay weld, Isolation Monitoring Interruption, PV RSD (UL 1741) o AFCI (UL 1699B) This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 4 of 8 GFT-OP-11a (22-August-2019) 1414 S Shelton St12/2/2024
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 5 of 8 GFT-OP-11a (22-August-2019) Appendix 3: List of Tested Grid protection / Support Function: Table 3A: Test List -1 Grid protection / Support Function Tested Test Standards Sections and Source Requirement Documents IEEE 1547-2018 IEEE 1547.1-2020 UL 1741SB - 2021 CA Rule 21:2020 UL 1741 SRD V2.0 (HECO):2020 OPERATIONAL TEMPERATURE -- 5.3.3.1 SB4.3.5.3 -- Same as 1547-2018 PROTECTION FROM ELECTROMAGNETIC INTERFERENCE (EMI) TEST 4.11.1 5.8.1 SB4.3.5.8.1 -- Same as 1547-2018 SURGE WITHSTAND PERFORMANCE TEST 4.11.2 5.8.2 SB4.3.5.8.2 -- Same as 1547-2018 PARALLELING DEVICE 4.11.3 5.8.3 -- -- Same as 1547-2018 OVERVOLTAGE TRIP 6.4.1 5.4.2 SB4.3.5.4.2 Electric Rule No. 21 Table Hh.1 Same as 1547-2018 UNDERVOLTAGE TRIP 6.4.1 5.4.3 SB4.3.5.4.3 Electric Rule No. 21 Table Hh.1 Same as 1547-2018 OVERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2 SB4.3.5.5.1 & SB4.3.5.5.2 Electric Rule No. 21 Table Hh.2 Same as 1547-2018 UNDERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2 SB4.3.5.5.1 & SB4.3.5.5.2 Electric Rule No. 21 Table Hh.2 Same as 1547-2018 LOW VOLTAGE RIDE-THROUGH 6.4.2.3 & 6.4.2.5 5.4.4 SB4.3.5.4.4 Electric Rule No. 21 Table Hh.1 Same as 1547-2018 HIGH VOLTAGE RIDE-THROUGH 6.4.2.4 5.4.7 SB4.3.5.4.7 Electric Rule No. 21 Table Hh.1 Same as 1547-2018 LOW FREQUENCY RIDE-THROUGH 6.5.2.3 5.5.3 SB4.3.5.5.3 Electric Rule No. 21 Table Hh.2 SRD-UL-1741-SA-V2.0 (HECO) Part II B HIGH FREQUENCY RIDE-THROUGH 6.5.2.4 5.5.4 SB4.3.5.5.4 Electric Rule No. 21 Table Hh.2 SRD-UL-1741-SA-V2.0 (HECO) Part II B RATE OF CHANGE OF FREQUENCY 6.5.2.5 5.5.5 -- -- Same as 1547-2018 ANTI-ISLANDING PROTECTION - WITH GRID SUPPORT FUNCTIONS ENABLED 8.1 5.10.2 SB4.3.5.10.2 Electric Rule No. 21 Hh.1a According to UL 1741 SA-V2.0 (HECO) TEST FOR VOLTAGE PHASE-ANGLE CHANGE RIDE-THOUGH (VARIATION 1) 6.5.2.6 5.5.6.1 SB4.3.5.5.6 -- Same as 1547-2018 ENTER SERVICE 4.10 5.6 -- -- Same as 1547-2018 SYNCHRONIZATION CONTROL FUNCTION TEST FOR EQUIPMENT WITH NO SYNCHRONIZING DISABLE CAPABILITY (VARIATION 3) 6.3 5.7.4 -- -- Same as 1547-2018 LIMITATION OF DC INJECTION FOR INVERTERS 7.1 5.9 -- Electric Rule No. 21 Hh.2h Same as 1547-2018 OPEN PHASE 6.2.2 5.11 -- -- Same as 1547-2018 CURRENT DISTORTION 7.3 5.12 -- Electric Rule No. Same as 1547- This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 6 of 8 GFT-OP-11a (22-August-2019) Grid protection / Support Function Tested Test Standards Sections and Source Requirement Documents IEEE 1547-2018 IEEE 1547.1-2020 UL 1741SB - 2021 CA Rule 21:2020 UL 1741 SRD V2.0 (HECO):2020 21 Hh.2g 2018 LIMIT ACTIVE POWER 4.6.2 5.13 -- Electric Rule No. 21 Hh.8 Same as 1547-2018 CONSTANT POWER FACTOR 5.3.2 5.14.3 SB4.3.5.14.3 Electric Rule No. 21 Hh.2i Same as 1547-2018 VOLTAGE-REACTIVE POWER (VOLT-VAR) MODE FIXED VREF 5.3.3 5.14.4 SB4.3.5.14.4 Electric Rule No. 21 Hh.2J Same as 1547-2018 VOLTAGE-REACTIVE POWER (VOLT-VAR) MODE (VREF TEST) 5.3.3 5.14.5 SB4.3.5.14.5 -- Same as 1547-2018 ACTIVE POWER-REACTIVE POWER MODE (WATT-VAR) 5.3.4 5.14.7 SB4.3.5.14.7 -- Same as 1547-2018 CONSTANT REACTIVE POWER (VAR) MODE 5.3.5 5.14.8 SB4.3.5.14.8 -- Same as 1547-2018 VOLTAGE-ACTIVE POWER (VOLT-WATT) MODE 5.4 5.14.9 SB4.3.5.14.9 Electric Rule No. 21 Hh.2.m Same as 1547-2018 TEST FOR FREQUENCY-DROOP (FREQUENCY-POWER OR FREQUENCY-WATT) CAPABILITY—ABOVE NOMINAL FREQUENCY 6.5.2.7 5.15.2 SB4.3.5.15.2 Electric Rule No. 21 Hh.2.l SRD-UL-1741-SA-V2.0 (HECO) Part II C TEST FOR FREQUENCY-DROOP (FREQUENCY-POWER OR FREQUENCY-WATT) CAPABILITY—BELOW NOMINAL FREQUENCY 6.5.2.7 5.15.3 SB4.3.5.15.3 Electric Rule No. 21 Hh.2.l SRD-UL-1741-SA-V2.0 (HECO) Part II C PRIORITIZATION OF DER RESPONSES 4.7 5.16 SB4.3.5.16 -- Same as 1547-2018 LOAD REJECTION OVERVOLTAGE (LROV) 7.4 5.17.2 SB4.3.5.17.2 -- Same as 1547-2018 FAULT CURRENT TESTS FOR INVERTERS 6.2.1 5.18.1 -- -- Same as 1547-2018 PERSISTENCE OF DER PARAMETER SETTINGS -- 5.19 -- -- Same as 1547-2018 NORMAL RAMP RATE -- -- -- Electric Rule No. 21 Hh.2k -- NAMEPLATE DATA TEST 10.3 6.4 -- -- Same as 1547-2018 MONITORING INFORMATION TEST 10.5 6.6 SB4.3.6.6 -- Same as 1547-2018 MANAGEMENT INFORMATION TEST 10.6 6.7 SB4.3.6.7 -- Same as 1547-2018 1414 S Shelton St12/2/2024
1414 S Shelton St
12/2/2024
Powerwall 3
Power Everything
2024
—
Powerwall 3 is a fully integrated solar and battery system, designed to accelerate the transition to sustainable energy. Customers
can receive whole home backup, cost savings, and energy independence by producing and consuming their own energy while
participating in grid services. Once installed, customers can manage their system using the Tesla App to customize system
behavior to meet their energy goals.
Powerwall 3 achieves this by supporting up to 20 kW DC of solar and providing 11.5 kW AC of continuous power per unit. It has
the ability to start heavy loads up to 185 A LRA, meaning a single unit can support the power needs of most homes. Powerwall 3
isdesignedformassproduction,fastandefcientinstallations,easysystemexpansion,andsimpleconnectiontoanyelectrical
service.
22024Powerwall 3 Datasheet
Solar Technical
Specications
Maximum Solar STC Input 20 kW
WithstandVoltage 600 V DC
PVDCInputVoltageRange 60 — 550 V DC
PVDCMPPTVoltageRange 60 — 480 V DC
MPPTs 6
Maximum Current per MPPT (Imp)13 A 5
Maximum Short Circuit Current per MPPT (Isc)15 A 5
Powerwall3 Technical Specifications
1 Typical solar shifting use case.
2 Values provided for 25°C (77°F), at beginning of life. 3.3 kW charge/discharge power.
3 TestedusingCECweightedefciencymethodology.
4 ThecustomerisexpectedtoprovideinternetconnectivityforPowerwall3;cellularshouldnotbeusedastheprimarymodeof
connectivity. Cellular connectivity subject to network operator service coverage and signal strength.
5 WheretheDCinputcurrentexceedstheMPPTrating,ajumpercanbeusedtocombinetwoMPPTsintoasingleinputto
intake DC current up to 26 A IMP / 30 A ISC.
Battery Technical
Specications
Nominal Battery Energy 13.5 kWh AC 2
MaximumContinuousDischargePower 11.5 kW AC
MaximumContinuousChargePower 5 kW AC
OutputPowerFactorRating 0-1(GridCodecongurable)
MaximumContinuousCurrent 48 A
Maximum Output Fault Current 10 kA
LoadStartCapability(1s)185 A LRA
PowerScalability Up to 4 Powerwall 3 units supported
SystemTechnical
Specications
ModelNumber 1707000-xx-y
NominalGridVoltage(Input&Output)120/240 VAC
GridType Split phase
Frequency 60 Hz
OvercurrentProtectionDevice 60 A
SolartoBatterytoHome/GridEfciency 89% 1,2
SolartoHome/GridEfciency 97.5% 3
SupportedIslandingDevices Gateway 3, Backup Switch, Backup Gateway 2
Connectivity Wi-Fi (2.4 and 5 GHz), Dual-port switched Ethernet,
Cellular (LTE/4G 4)
HardwareInterface Drycontactrelay,RapidShutdown(RSD)certiedswitch
and 2-pin connector, RS-485 for meters
AC Metering Revenue Grade (+/- 0.5%)
Protections Integrated arc fault circuit interrupter (AFCI), Isolation
MonitorInterrupter(IMI),PVRapidShutdown(RSD)using
TeslaMid-CircuitInterrupters
CustomerInterface TeslaMobileApp
Warranty 10 years
1414 S Shelton St
12/2/2024
1414 S Shelton St
12/2/2024
!"#!$%$&
'
(
)( *+ ,-
((* ,
. ) ./
( *
00+&1&2!!%
. .3(
4
/
*4
.
.3#!5$
/
.(
/(
671.(
.3%$&..
*8
./)(
..
4
*.
((
(.
%. .3*8
/
-)
/(
(
(..
.3 *
.3
.
( *"(
3
.3 !"$
9
$:222$&
(-.-$: 222$&88
-8(
-
.
* :;#2615--<72715.=
3 2#!5--<;2#&5.=
8 ;1215--<&2715.=3
..3 >
&2;152-<&15()/2.=!2!!?!2!:5.@<2!6?12#5--@=$: 222$:!=&2;152-<&15()/2.=$: 222$:!=12!652-< 15()/2.=!2!:5.@<62&75--@=$6=12!652-< 15()/2.=!2!?!2!&5.@<:2&?:2:5--@=$#222$ =12#152-<1!5()/2.=!2! 5.@<#2#75--@=$&=
.3
.88.3
(
3*!!:!#AB%$&B&!!!$.
(
:$(
-
+-
.
.. .
.
)
/
.. )
/
-..3
)( *
(
)( */
8 /8
/
88(
.Feb 3, 2020:!!761;!: ;: ;:
,
3
4
3 <)=2::5,3< 2#15()<==
.
)( *C
. */3.%D//
.
)( *
.
)(
//
.
--8
(/.
88 .#1$+8
.
E8
*
-
(.(.3+
.(
-8.4,.4.
/
(/.
.3
.A
8 '
-2-
./-
.3 44428#14
..32
23'$
3(
.$
(
.$/
/"C
'
-8(
.
(
.E
'*-
(/
C
%
*/
C
E
-8 ../-
.C
.
3(
..
(
.
'
.
(
.< /.
(
3
(8
=.'.-
.
((
.'.-
.
(/(
(
*/(
.
/8
/
*(.38
..
(4
. *
. *:6-. 1414 S Shelton St12/2/2024
32024Powerwall 3 Datasheet
Mechanical
Specications
Dimensions 1099x609x193mm(43.25x24x7.6in)
Weight 130 kg (287 lb)
MountingOptions Floor or wall mount
Powerwall3 Technical Specifications
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F) 6
OperatingHumidity(RH)Up to 100%, condensing
Storage Temperature –20°C to 30°C (–4°F to 86°F), up to 95% RH, non-
condensing, State of Energy (SOE): 25% initial
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
EnclosureRating NEMA3R
IngressRating IP67 (Battery & Power Electronics)
IP45 (Wiring Compartment)
PollutionRating PD3
OperatingNoise@1m < 50 db(A) typical
<62db(A)maximum
Compliance
Information
Certications UL 1642, UL 1699B, UL 1741, UL 1741 SA, UL 1741 SB, UL
1741 PCS, UL 3741, UL 1973, UL 1998, UL 9540, IEEE 1547-
2018, IEEE 1547.1, UN 38.3
GridConnection United States
Emissions FCC Part 15 Class B
Environmental RoHS Directive 2011/65/EU
Seismic AC156, IEEE 693-2005 (high)
FireTesting Meetstheunitlevelperformancecriteria
of UL 9540A
6 Performance may be de-rated at operating temperatures above 40°C (104°F).
609 mm 193
mm
1099 mm
42024Powerwall 3 Datasheet
Electrical
Specications
Model MCI-1 MCI-2
NominalInputDCCurrentRating(IMP)13 A 13 A
Maximum Input Short Circuit Current (ISC)19 A 17 A
MaximumSystemVoltage(PVHCS)600 V DC 1000 V DC
7
Solar Shutdown Device Technical Specifications
Environmental
Specications
Operating Temperature -40°C to 50°C
(-40°F to 122°F)
-45°C to 70°C
(-49°F to 158°F)
Storage Temperature –30°C to 70°C
(–22°F to 158°F)
–30°C to 70°C
(–22°F to 158°F)
EnclosureRating NEMA4X/IP65NEMA4X/IP65
RSDModule
Performance
MaximumNumberofDevicesperString 5 5
Control PowerLineExcitation PowerLineExcitation
PassiveState Normally Open Normally Open
MaximumPowerConsumption 7 W 7 W
Warranty 25 years 25 years
—
TheSolarShutdownDeviceisaMid-CircuitInterrupter(MCI)andispartofthePVsystemrapidshutdown(RSD)functionin
accordance with Article 690 of the applicable NEC. When paired with Powerwall 3, solar array shutdown is initiated by any loss
of AC power.
Mechanical
Specications
ElectricalConnections MC4Connector MC4Connector
Housing Plastic Plastic
Dimensions 125x150x22mm
(5x6x1in)
173x45x22mm
(6.8x1.8x1in)
Weight 350 g (0.77 lb) 120 g (0.26 lb)
MountingOptions ZEP Home Run Clip
M4Screw(#10)
M8Bolt(5/16")
Nail / Wood screw
Wire Clip
Compliance
Information
Certications UL 1741 PVRSE, UL 3741,
PVRSA (Photovoltaic Rapid Shutdown Array)
RSDInitiationMethod ExternalSystemShutdownSwitchor
Powerwall 3 Enable Switch
7MaximumSystemVoltageislimitedbyPowerwallto600VDC.
UL3741PVHazardControl
(andPVRSA)Compatibility SeePowerwall3InstallationManual
1414 S Shelton St
12/2/2024
52024Powerwall 3 Datasheet
Gateway 3
8 Only Eaton CSR or BWH main breakers are 25 kA rated.
Performance
Specications
ModelNumber 1841000-01-y
NominalGridVoltage 120/240 V AC
GridConguration Split phase
GridFrequency 60 Hz
ContinuousCurrent
Rating
200 A
Maximum Supply Short
Circuit Current
22 kA with Square D or
Eaton main breaker
25 kA with Eaton main
breaker 8
IECProtectiveClass Class I
Overvoltage Category Category IV
Mechanical
Specications
Dimensions 660x411x149mm
(26x16x6in)
Weight 16.3 kg (36 lb)
Mountingoptions Wall mount
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
OperatingHumidity(RH)Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
EnclosureType NEMA3R
Compliance
Information
Certications UL 67, UL 869A, UL 916, UL 1741 PCS,
CSA 22.2 107.1, CSA 22.2 29
Emissions FCC Part 15, ICES 003
—
Tesla Gateway 3 controls connection to the grid in a Powerwall system, automatically detecting outages and providing seamless
transition to backup power. It provides energy monitoring that is used by Powerwall for solar self-consumption, time-based
control, and backup operation.
411 mm
660
mm
149
mm
AC Meter Revenue accurate (+/- 0.5%)
Communication CAN
UserInterface Tesla App
BackupTransition Automatic disconnect for
seamless backup
Overcurrent
ProtectionDevice
100–200 A
Service entrance rated
Eaton CSR, BWH, or BW, or
SquareDQOMbreakers
InternalPanelboard 200 A
8-space/16 circuit breakers
Eaton BR, Siemens QP, or
SquareDHOMbreakersrated
to 10–125A
Warranty 10 years
62024Powerwall 3 Datasheet
Backup Switch
9Breakermaximumsupplyshortcircuitcurrentratingmustbeequaltoorgreaterthantheavailablefaultcurrent.
Performance
Specications
ModelNumber 1624171-xx-y
ContinuousLoadRating 200 A, 120/240 V split phase
Maximum Supply Short Circuit Current 22 kA with breaker 9
Communication CAN
AC Meter Revenue accurate (+/- 0.5%)
ExpectedServiceLife 21 years
Warranty 10 years
Mechanical
Specications
Dimensions 176x205x74mm(6.9x8.1x2.9in)
Weight 2.8 lb
MeterandSocketCompatibility ANSI Type 2S, ringless or ring type
External Service Interface Contactor manual override 10
Reset button
ConduitCompatibility 1/2-inch NPT
Environmental
Specications
Operating Temperature –40°C to 50°C (–40°F to 122°F)
Storage Temperature –40°C to 85°C (–40°F to 185°F)
EnclosureRating NEMA3R
PollutionRating PD3
Compliance
Information
SafetyStandards USA: UL 414, UL 414 SB, UL 2735, UL 916, CA Prop 65
Emissions FCC, ICES
10Manuallyoverridesthecontactorpositionduringaserviceevent.
—
The Tesla Backup Switch controls connection to the grid in a Powerwall system, and can be easily installed behind the utility
meter or in a standalone meter panel downstream of the utility meter.
The Backup Switch automatically detects grid outages, providing a seamless transition to backup power. It communicates
directly with Powerwall, allowing home energy usage monitoring from any mobile device with the Tesla app.
204.86
74
176 mm
205 mm
74 mm
1414 S Shelton St
12/2/2024
72024Powerwall 3 Datasheet
Backup Gateway 2
Performance
Specications
ModelNumber 1232100-xx-y
ACVoltage(Nominal)120/240 V
Feed-inType Split phase
GridFrequency 60 Hz
CurrentRating 200 A
Maximum Supply Short
Circuit Current
10 kA 11
Overcurrent Protection
Device
100 - 200 A, Service
entrance rated 9
Overvoltage Category Category IV
Internal Primary
AC Meter
Revenue accurate
(+/- 0.2%)
Internal Auxiliary
AC Meter
Revenue accurate
(+/- 2%)
Primary Connectivity Ethernet, Wi-Fi
SecondaryConnectivity Cellular (3G, LTE/4G) 12
Mechanical
Specications
Dimensions 660x411x149mm
(26x16x6in)
Weight 20.4 kg (45 lb)
Mountingoptions Wall mount,
Semi-Đushmount
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
OperatingHumidity(RH)Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
EnclosureType NEMA3R
Compliance
Information
Certications UL 67, UL 869A, UL 916, UL 1741 PCS,
CSA 22.2 0.19, CSA 22.2 205
Emissions FCC Part 15, ICES 003
411 mm
660 mm
149
mm
11 When protected by Class J fuses, Backup Gateway 2 is
suitable for use in circuits capable of delivering not more
than 22kA symmetrical amperes.
12 Cellular connectivity subject to network operator service
coverage and signal strength.
—
Backup Gateway 2 controls connection to the grid when paired with Powerwall 3, automatically detecting outages and providing
seamless transition to backup power. Backup Gateway 2 also provides energy metering for solar self-consumption, time-based
control, and backup operation.
Inthissystemconguration,Powerwall3actsastheSiteController,withtheBackupGateway2SiteControllerdisabled.
UserInterface Tesla App
OperatingModes Support for solar self-
consumption, time-based
control, and backup
BackupTransition Automatic disconnect for
seamless backup
Modularity Supports up to 10 AC-
coupled Powerwalls
Optional Internal
Panelboard
200 A 6-space / 12 circuit
breakers
Siemens QP or Square D
HOMbreakersrated10-
80A or Eaton BR breakers
rated 10 - 125A
Warranty 10 years
82024Powerwall 3 Datasheet
Powerwall3 Example System Configurations
Powerwall 3 with Backup Switch
Whole Home Backup
Powerwall 3 with Gateway 3
Whole Home Backup
Powerwall 3 with Backup Gateway 2
Partial Home Backup
1414 S Shelton St
12/2/2024
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 7 of 8 GFT-OP-11a (22-August-2019) Table 3B: Test List -2 Test Description CSA C22.2#107.1:2016 Ed. 4 CSA C22.3#9:2020 Ed 2 Screw Tightening Torque Test 3.6.3 -- Impedance Test 105.1/10.5.2 -- Continuity Test 4.1 -- Output Power Factor 4.2 -- Voltage Harmonics for stand alone 15.3.2.1 -- Frequency 10.5.4 -- Stand-alone inverter dc output short-circuits current contribution 10.5.5 -- Normal ramp rate -- 7.2.3.4.2 / 8.3.12.2.3 Flicker -- 7.2.2 / 8.3.13 Test for constant reactive power (var) mode 7.2.3.3.3 / 8.3.12.2.2 This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 8 of 8 GFT-OP-11a (22-August-2019) Appendix 4: Revision Summary Date / Project Engineer Comments 15-Feb-2023 Dipesh Patel Original issue date 8-Mar-2023 / G104200718 Dipesh Patel Added UL 1699B, UL 1998 and UL 991 standards 24-Mar-2023/ G104200718 Dipesh Patel Added UL 1973 standard. Added normal and abnormal category in ratings table. 18-Apr-2023 / G104200718 Dipesh Patel Added additional factory settable nameplate ratings rated output active power (W): 9600, 7680, 5750; Max. Continuous output power (W): 9600, 7680, 5750; Max. Cont. Output Current (A): 40, 32, 24; Apparent Power rating (VA): 9600, 7680, 5750 Added Puerto Rico Interconnection regulation as it refers to UL 1741 and IEEE 1547-2018. 1-May-2024 / G104514208 Mukund Rana A) Added standards. Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] B) Update CSA C22.2#0.8 standard C) added Table 3B: Test List -2 1414 S Shelton St12/2/2024
Service Voltage
240
Section 220.83 Existing Dwelling Unit
Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
19.1 4584
Part #2 - Section 220.83(B)(2), (3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500
1500
1500
1000
600
1000
1600
5760
Amps Box B (VA)
60.25 14460
Total VA from Parts #1 and #2 combined:Box A + Box B =19044
Total VA 19044
First 8000 VA @ 100%8000 Remaining VA @ 40%
Remaining VA =11044 11044 x 40% =4417.6 VA
Adding First 8000 VA, if possible 8000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:12417.6 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:51.74 Amps
Part #3 - Section 220.83(B) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:0 VA
100% of all the Heating or A/C loads in Amps:0.00 A
VA Volts Amps
Parts #1 & #2 12417.6 240 51.74
Part #3 0 240 0.00
Total VA for all Parts:12,418
Totals Service/Feeder Load 51.74
Microwave
EV Charger
Totals for Part #2:
Totals from all Parts
Dishwasher
Disposal
Refrigerator
Laundry
Appliance Circuit - 1
Appliance Circuit - 2
Dedicated circuit Dedicated circuit
Article 220 - Dedicated Backup Panel Calculation Job Code
1414 S Shelton St Santa Ana CA USA 92707 109R-414SER1
Building Square Footage VA (watts)Amps
House 1528.00 4584 19.10
Total for Part #1:
1414 S Shelton St
12/2/2024
Section 220.83 Existing Dwelling Unit
Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
19.1 4584
Part #2 - Section 220.83 (B)(2),(3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500 N/A
3000 N/A
1000 N/A
600 N/A
1000 N/A
1600 N/A
5760 N/A
N/A N/A
N/A N/A
N/A Amps Box B (VA)
N/A 60.25 14460
Total VA from Parts #1 and #2 combined:Box A + Box B =19044
Total VA 19044
First 8,000 VA @ 100%8000 Remaining VA @ 40%
Remaining VA =11044 11044 x 40% =4417.6 VA
Adding First 8000 VA 8000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:12417.6 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:51.74 Amps
Part #3 - Section 220.83 (B) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:0 VA
100% of all the Heating or A/C loads in Amps:0.00 A
VA Volts Amps
Parts #1 & #2 12417.6 240 51.74
Part #3 0 240 0.00
Total VA for all Parts:12,418
Totals Service/Feeder Load 51.74
#ESTAMP
Refrigerator(s)
Microwave(s)
Totals for Part #2:
EV Charger
Amps
19.1
Job Code
109R-414SER1
Totals from all Parts
Dedicated circuit
Total for Part #1:
House
Square Footage
1528
Article 220 - Service/Feeder calculation for (address):
1414 S Shelton St Santa Ana CA USA 92707
Building VA (watts)
4584
Laundry
Appliance Circuit(s)
Dishwasher(s)
Disposal(s)
Dedicated circuit
1414 S Shelton St
12/2/2024
Bus Rating:200
Main Rating:200
0%0%
Not Fed by other panels
Feeds: Panel 2 51.74
0.00
51.74
Bus Rating:225
Main Rating:150
100%100%
Itemized House and 240V Loads for Panel: (VA)
1500 1500
1500 1000
600 1000
1600 5760
Fed by: Panel 1
51.74
51.74
Panel 1 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Load Calc: (This Panel)
Total Load Calc:
Panel 2 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Laundry Appliance Circuit - 1
Load Calc: (This Panel)
Total Load Calc:
Appliance Circuit - 2 Dishwasher
Disposal Refrigerator
Microwave EV Charger
1414 S Shelton St
12/2/2024
1414 S Shelton St
12/2/2024
10/3/2024
RE: Structural Certification for Installation of Residential Solar
FELIPE SERRANO:1414 S SHELTON ST, SANTA ANA, CA, 92707
Code 2022 California Building Code (ASCE 7-16)
Risk category II Wind Load (component and Cladding)
Roof Dead Load Dr 10 psf V 96 mph
PV Dead Load DPV 3 psf Exposure B
Roof Live Load Lr 20 psf
Ground Snow S 0 psf
If you have any questions on the above, please do not hesitate to call.
Sincerely,
Eugene Munyanziza, P.E.
EV Engineering, LLC
projects@evengineersnet.com Signed: 10/3/2024
http://www.evengineersnet.com
Exp: 06/30/2026
Attn: To Whom It May Concern
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the
PV system to existing roof framing. From the field observation report, the roof is made of Flat Rolled
Composition shingle roofing over roof plywood supported by 2X8 Rafters at 16 inches. The slope of the roof
was approximated to be 3 degrees.
After review and based on our structural capacity calculation, the existing roof framing has been determined to
be adequate to support the imposed loads without structural upgrades.
I certify that the PV module assembly including all attachments supporting it have been reviewed to be in
accordance with manufacturer's specifications. Capacity Calculations were done in accordance with applicable
building codes.
Design Criteria
projects@evengineersnet.com
http://www.evengineersnet.com
1414 S Shelton St
12/2/2024
Wind Load Cont.
96 mph ASCE 7-16 Figure 26.5-1B
B
1.0 ASCE 7-16 Sec 26.8.2
0.57 ASCE 7-16 Table 26.10-1
0.85 ASCE 7-16 Table 26.6-1
1.00 ASCE 7-16 Table 26.9-1
11.40 psf
3.0 Degrees
1.5
0.8
Uplift (W)Zone(1)Zone(2r)Zone(2e)Zone(3)
Fig. 30-3-2 GCp=-1.3 -1.8 -1.8 -1.95
Eq. 29.4-7 P=qh(GCp)(γE)(γa)=-17.79 -24.63 -24.63 -26.69
GCp=0.7 Figure 30.3-2
P=qh(GCp)(γE)(γa)=5.16 Equation 29.4-7
Rafter Attachments: 0.6D+0.6W (CD=1.6)
Connection Check
Attachement max. spacing=5.3 ft
5/16" Lag Screw Withdrawal Value=266 lbs/in Table 12.2A - NDS
2.5 in DFL#2 Assumed
Prying Coefficient 1.4
Allowable Capacity=760 lbs
Zone Trib Width Area (ft)Uplift (lbs)Down (lbs)
Zone(1)5.3 15.1 101.3 123.0
Zone(2r)5.3 8.6 76.9 123.0
Zone(2e)5.3 8.6 76.9 123.0
Zone(3)5 8.6 82.6 123.0
Conservative Max=101.3 <760
CONNECTION IS OK
2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw.
Embedment in sheading or other material does not count.
II
V=
Exposure =
1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift
governs
γE=
γa=
KZt =
qh= 0.00256KzKztKdKeV2=
Pitch =
Lag Screw Penetration
Risk Category =
KZ =
Kd =
Ke =
projects@evengineersnet.com
http://www.evengineersnet.com
1414 S Shelton St
12/2/2024
Vertical Load Resisting System Design
Roof Framing Rafters
Snow Load Fully Exposed
pg=0 psf Ct =1.1
Ce =0.9 Is =1.0 ps = 0 psf
pf = 0 psf pfmin. = 0.0 psf 0 plf
Max Length, L =15.2 ft
Tributary Width, WT =16 in
RLL =20 psf 13.32 plf
Dr =10 psf 13.33 plf
PvDL =3 psf 4 plf
Load Case: DL w=17 plf
M=443 lb-ft
Mallowable = Sx x Fb'=1224 lb-ft >443 lb-ft OK
Load Case: DL+RLL DL+Lr=27 plf
Mdown=681 lb-ft
Mallowable = Sx x Fb'=1700 lb-ft >681 lb-ft OK
Load Case: DL+S DL+S=17 plf
Mdown=443 lb-ft
Mallowable = Sx x Fb'=1632 lb-ft >443 lb-ft OK
Load Case: DL+0.6W w=21.5 plf
Mu=549 lb-ft
Mallowable = Sx x Fb' (wind)=2176 lb-ft >549 lb-ft OK
Load Case: 0.6DL+0.6W w=15.0 plf
Mu=382 lb-ft
Mallowable = Sx x Fb' (wind)=2176 lb-ft >382 lb-ft OK
DL+0.45W+0.75(RLL or S)21 plf
Mdown=530 lb-ft
Mallowable = Sx x Fb'=2176 lb-ft >530 lb-ft OK
Member Capacity
DF-L No.2
2X8 CL CF Ci Cr
Fb =900 psi 1.0 1.2 1.0 1.15 1242 psi
Fv =180 psi N/A N/A 1.0 N/A 180 psi
E =1600000 psi N/A N/A 1.0 N/A 1600000 psi
Emin =580000 psi N/A N/A 1.0 N/A 580000 psi
Depth, d =7.25 in
Width, b =1.5 in
Cross-Sectonal Area, A =10.875 in2
Moment of Inertia, Ixx =47.6348 in4
Section Modulus, Sxx =13.1406 in3
Allowable Moment, Mall = Fb'Sxx =1360.1 lb-ft DCR=Mu/Mall =0.40 < 1 Satisfactory
Allowable Shear, Vall = 2/3Fv'A =1305.0 lb DCR=Vu/Vall =0.11 < 1 Satisfactory
Design Value Adjusted Value
projects@evengineersnet.com
http://www.evengineersnet.com
1414 S Shelton St
12/2/2024
Siesmic Loads Check
Roof Dead Load 10 psf
% or Roof with Pv 22.0%
Dpv and Racking 3 psf
Average Total Dead Load 10.7 psf
Increase in Dead Load 3.0%OK
Limits of Scope of Work and Liability
The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and
therefore no further seismic analysis is required.
We have based our structural capacity determination on information in pictures and a drawing set titled PV plans
-FELIPE SERRANO. The analysis was according to applicable building codes, professional engineering and design
experience, opinions and judgments. The calculations produced for this structure's assessment are only for the
proposed solar panel installation referenced in the stamped plan set and were made according to generally
recognized structural analysis standards and procedures.
projects@evengineersnet.com
http://www.evengineersnet.com
1414 S Shelton St
12/2/2024
Rev: 8/29/19
SOL-01 CBC 2016
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Signature:
Date:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
Print Name: caitlyn hernandez
Phone Number: 3854005019
Email Address: oc_permits@sunrun.com
1414 S Shelton St
12/2/2024
City of Santa Ana,
SIGNATURE:___________________ DATE:__________
717 17th Street, Ste. 200 | Denver, CO 80202
I, Felipe Serrano, grant authorization to SUNRUN SOLAR to install Rooftop Mounted Solar
on my residence located at 1414 s shelton st , SANTA ANA, CA, 92704.
Docusign Envelope ID: 4AEF63B2-5746-41FF-97A7-BE122D5FA46A
10/4/2024
1414 S Shelton St
12/2/2024
Certificate Of Completion
Envelope Id: 4AEF63B2574641FF97A7BE122D5FA46A Status: Completed
Subject: SUNRUN URGENT NEEDED FOR PERMITS Complete with Docusign: -Solar Authorization Letter.pdf
Source Envelope:
Document Pages: 1 Signatures: 1 Envelope Originator:
Certificate Pages: 5 Initials: 0 Bobby Cautela
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
225 Bush Street, Suite 1400
San Francisco, CA 94104
robert.cautela@sunrun.com
IP Address: 174.65.135.37
Record Tracking
Status: Original
10/4/2024 4:09:03 PM
Holder: Bobby Cautela
robert.cautela@sunrun.com
Location: DocuSign
Signer Events Signature Timestamp
Felipe Serrano
mikeaserrano17@yahoo.com
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 104.34.211.107
Signed using mobile
Sent: 10/4/2024 4:09:48 PM
Viewed: 10/4/2024 5:37:03 PM
Signed: 10/4/2024 5:37:16 PM
Electronic Record and Signature Disclosure:
Accepted: 10/22/2022 2:24:20 PM
ID: 3c3106f2-7176-4d5b-b82b-035b929142e4
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 10/4/2024 4:09:48 PM
Certified Delivered Security Checked 10/4/2024 5:37:03 PM
Signing Complete Security Checked 10/4/2024 5:37:16 PM
Completed Security Checked 10/4/2024 5:37:16 PM
Payment Events Status Timestamps
Electronic Record and Signature Disclosure
1414 S Shelton St
12/2/2024
CONSUMER DISCLOSURE
From time to time, Sunrun Inc. (we, us or Company) may be required by law to provide to you
certain written notices or disclosures. Described below are the terms and conditions for providing
to you such notices and disclosures electronically through the DocuSign, Inc. (DocuSign)
electronic signing system. PLEASE READ THE INFORMATION BELOW CAREFULLY
AND THOROUGHLY, AND IF YOU CAN ACCESS THIS INFORMATION
ELECTRONICALLY TO YOUR SATISFACTION AND AGREE TO THESE TERMS AND
CONDITIONS, PLEASE CONFIRM YOUR AGREEMENT BY CLICKING THE 'I AGREE'
BUTTON AT THE BOTTOM OF THIS DOCUMENT.
Getting paper copies
At any time, you may request from us a paper copy of any record provided or made available
electronically to you by us. You will have the ability to download and print documents we send
to you through the DocuSign system during and immediately after signing session and, if you
elect to create a DocuSign signer account, you may access them for thirty (30) days after such
documents are first sent to you. After such time, if you wish for us to send you paper copies of
any such documents from our office to you, please request delivery of such paper copies from us
by following the procedure described below.
Withdrawing your consent
If you decide to receive notices and disclosures from us electronically, you may at any time
change your mind and tell us that thereafter you want to receive required notices and disclosures
only in paper format. How you must inform us of your decision to receive future notices and
disclosure in paper format and withdraw your consent to receive notices and disclosures
electronically is described below.
Consequences of changing your mind
If you elect to receive required notices and disclosures only in paper format, it will slow the
speed at which we can complete certain steps in transactions with you and delivering services to
you because we will need first to send the required notices or disclosures to you in paper format,
and then wait until we receive back from you your acknowledgment of your receipt of such
paper notices or disclosures. To indicate to us that you are changing your mind, you must
withdraw your consent using the DocuSign ‘Withdraw Consent’ form on the signing page of a
DocuSign envelope instead of signing it. This will indicate to us that you have withdrawn your
consent to receive required notices and disclosures electronically from us and you will no longer
be able to use the DocuSign system to receive required notices and consents electronically from
us or to sign electronically documents from us.
All notices and disclosures will be sent to you electronically
Unless you tell us otherwise in accordance with the procedures described herein, we will provide
electronically to you through the DocuSign system all required notices, disclosures,
authorizations, acknowledgements, and other documents that are required to be provided or made
available to you during the course of our relationship with you. To reduce the chance of you
inadvertently not receiving any notice or disclosure, we prefer to provide all of the required
notices and disclosures to you by the same method and to the same address that you have given
us. Thus, you can receive all the disclosures and notices electronically or in paper format through
the paper mail delivery system. If you do not agree with this process, please let us know as
described below. Please also see the paragraph immediately above that describes the
consequences of your electing not to receive delivery of the notices and disclosures
electronically from us.
Electronic Record and Signature Disclosure created on: 8/7/2013 10:17:58 AM
Parties agreed to: Felipe Serrano 1414 S Shelton St
12/2/2024
How to contact Sunrun Inc.:
You may contact us to let us know of your changes as to how we may contact you electronically,
to request paper copies of certain information from us, and to withdraw your prior consent to
receive notices and disclosures electronically as follows:
To contact us by email send messages to: customercare@sunrun.com
You may also contact us in writing at 45 Fremont Street, 32nd Floor, San Francisco, CA 94105
or by phone at 1-855-478-6786.
To advise Sunrun Inc. of your new e-mail address
To let us know of a change in your e-mail address where we should send notices and disclosures
electronically to you, you must send an email message to us at customercare@sunrun.com and in
the body of such request you must state: your previous e-mail address, your new e-mail
address. We do not require any other information from you to change your email address.
In addition, you must notify DocuSign, Inc. at 1-866-219-4318 to arrange for your new email
address to be reflected in your DocuSign account by following the process for changing e-mail in
the DocuSign system.
To request paper copies from Sunrun Inc.
To request delivery from us of paper copies of the notices and disclosures previously provided
by us to you electronically, you must contact us by (a) sending us an e-mail to
customercare@sunrun.com, (b) writing to us at Sunrun Inc, 45 Fremont Street, 32nd Floor, San
Francisco, CA 94105, or (c) calling us at 1-855-478-6786, and in connection with your request
you must state your e-mail address, full name, US Postal address, and telephone number.
To withdraw your consent with Sunrun Inc.
To inform us that you no longer want to receive future notices and disclosures in electronic
format you may:
i. decline to sign a document from within your DocuSign session, and on the subsequent
page, select the check-box indicating you wish to withdraw your consent, or you may;
ii. contact us by (a) sending us an email to customercare@sunrun.com, (b) writing to us
at Sunrun Inc., 45 Fremont Street, 32nd Floor, San Francisco, CA 94105, or (c) calling us
at 1-855-478-6786, and in connection with your request you must state your e-mail, full
name, US Postal Address, and telephone number. We do not need any other information
from you to withdraw consent.. The consequences of your withdrawing consent for
online documents will be that transactions may take a longer time to process..
Required hardware and software
Operating
Systems: Windows® 2000, Windows® XP, Windows Vista®; Mac OS® X
1414 S Shelton St
12/2/2024
Browsers:
Final release versions of Internet Explorer® 6.0 or above (Windows only);
Mozilla Firefox 2.0 or above (Windows and Mac); Safari™ 3.0 or above
(Mac only)
PDF Reader: Acrobat® or similar software may be required to view and print PDF files
Screen
Resolution: 800 x 600 minimum
Enabled Security
Settings: Allow per session cookies
** These minimum requirements are subject to change. If these requirements change, you will be
asked to re-accept the disclosure. Pre-release (e.g. beta) versions of operating systems and
browsers are not supported.
Notices
Any notice or other communication to be made hereunder, even if otherwise required to be in
writing under other provisions of this Consent or any other documents or agreements that have
been provided to you in connection with this Consent, may alternatively be made in an electronic
record transmitted electronically to the electronic addresses provided by you. Any notice or other
communication made in electronic form will have the same legal effect and enforceability as if
made in non-electronic form.
Acknowledging your access and consent to receive materials electronically
To confirm to us that you can access this information electronically, which will be similar to
other electronic notices and disclosures that we will provide to you, please verify that you were
able to read this electronic disclosure and that you also were able to print on paper or
electronically save this page for your future reference and access or that you were able to e-mail
this disclosure and consent to an address where you will be able to print on paper or save it for
your future reference and access. Further, if you consent to receiving notices and disclosures
exclusively in electronic format on the terms and conditions described above, please let us know
by clicking the ‘I agree’ button below.
By checking the ‘I agree’ box, I confirm that:
I can access and read and have accessed, read and understood the terms of this
ELECTRONIC CONSENT TO ELECTRONIC RECEIPT OF ELECTRONIC
CONSUMER DISCLOSURES document; and
I can print on paper the disclosure or save or send the disclosure to a place where I can
print it, for future reference and access; and
Until or unless I notify Sunrun Inc. as described above, I consent to receive from
exclusively through electronic means all notices, disclosures, authorizations,
acknowledgements, and other documents that are required to be provided or made
available to me by Sunrun Inc. during the course of my relationship with you.
Entire Agreement Provision
This agreement and the consumer disclosure statement executed by the customer in conjunction
with and simultaneously with its review and acceptance of the terms set forth herein constitute
1414 S Shelton St
12/2/2024
the entire agreement between the parties with respect to the subject matter hereof and supersede
any prior understandings, agreements, or representations by or between the parties, written or
oral, to the extent they relate in any way to the subject matter hereof.
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
LTD: LR5-54HABB-400M
TESLA: POWERWALL 3 1707000-XX-Y
SNR-DC-00335 [FLAT, TILT KIT (ROLLED COMP/ MEMBRANE/
FOAM) 1 LAG OMNIBASE]
1707000-XX-Y
MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A).
MODULES, ARE CLASS A FIRE RATED.
CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30
SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE
ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N) NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-2.1 ELEVATION DETAIL
VIEW
PV-3.0 LAYOUT
PV-3.1 MOUNTING DETAIL
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL CALCS
PV-4.2 BACKUP LOAD CALCS
PV-4.3 PANEL SCHEDULE
PV-5.0 SIGNAGE
PV-5.1 SIGNAGE
NOTE: CEC 2022: 705.12(B)(3)(3): THIS EQUIPMENT FED BY
MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT
DEVICES EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE
SHALL NOT EXCEED AMPACITY OF BUSBAR.
***The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to
compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does
not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and
structures as shown. ***
Bldg#: 101121213
Elect#: 20184273
Approvals:
Elec: M Smith
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46PLPLPLPLPLPLPLPLPLPLPLPLPLPL
SITE PLAN
PV-2.0
#SSTAMPSP
#ESTAMPSP
SITE PLAN - SCALE = 1/16" = 1'-0"
ARRAY
PITCH
PV AREA
(SQFT)
AR-01 3° 189.2
TRUE
AZIM
MAG
AZIM
168°180°
POWERWALL ENERGY
STORAGE SYSTEM (ESS)
BG BACKUP GATEWAY
GP GENERATION PANEL
ELECTRIC VEHICLE
SUPPLY EQUPMENTEV
MAIN PANEL
INVERTER(S)
AC DISCONNECT(S)
DC DISCONNECT(S)
SUNRUN METER
DEDICATED PV METER
SERVICE ENTRANCE
INTERIOR EQUIPMENT
SHOWN AS DASHED
SE
MP
SM
PM
INV
AC
DC
SUB-PANELSP
CB IQ COMBINER BOX
METER ADAPTERMA
GROUNDING
ELECTRODE
ENERGY STORAGE
SYSTEM
BP BACKUP LOADS PANEL
BI BACKUP INTERFACE 1 COMMUNICATION
WIRESAM
MD MICROGRID
INTERCONNECT DEVICE
ACREL METER
SOLAREDGE METERSEMPV LOAD CENTERLC
LEGEND
SCALE: NTS
NOTE: NOT ALL ITEMS IN LEGEND
WILL APPEAR IN SITE PLAN
RAIL
STANDOFFS &
FOOTINGS
SOLAR
MODULES
NOTES:
RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
TOTAL ROOF SURFACE AREA: 2223 SQFT.
TOTAL PV ARRAY AREA (E+N): 489.06 SQ FT.
PERCENTAGE PV COVERAGE (E+N):
(TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
AREA) * 100 = 22%
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4.
ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT
WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED
ON LARGE/SCALE FIRE TESTING.
(N) ARRAY AR-01
SE
MP
INV
(E) PV ARRAY
(E) PV EQUIPMENT
MD RSD
INV
AC
BPAC
INV
AC
(E) FENCE
(E) GATE (TYP.)
(E) DETACHED
STORAGE SHED
(NO ELECTRICAL)S SHELTON STA A A A A A
B B B
(E) FLAT ROOF STRUCTURE CONNECTED
STRUCTURALLY TO RESIDENCE
(E) RESIDENCE
3'-8"4'-6"
3'-3"
4'-1"
21'-9"22'-7"
5'-1"
29'-4"
39'-1"
5'-4"
54'-3"
42'-9"
33'-4"
4'-4"3'-6"
B
Signed 10/15/2024
1414 S Shelton St
12/2/2024
EXTERIOR WEST WALL
PAGE
REV: B 10/14/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
ESS ELEVATION
VIEW
PV-2.1
ESS ELEVATION VIEW
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4.
ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT WHERE SMALLER
SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON LARGE/SCALE FIRE TESTING.
SITE PLAN - SCALE = 3/32" = 1'-0"
AC DISCONNECT
INVERTER + ESS
BACKUP LOAD PANEL
BACKUP GATEWAY
RAPID SHUTDOWN
SWITCH
(E) AC DISCONNECT
(E) INVERTER
MSP Signed 10/15/2024
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
D1 - AR-01 - SCALE: 0.010417
AZIM:180°
PITCH: 3°
#SSTAMP
DESIGN CRITERIA
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED:
96 MPH 3-SEC GUST.
FASTENERS:
(1) 5/16" DIA S.S. LAG SCREW: 2.5"
MIN EMBEDMENT INTO FRAMING
PV-3.0
LAYOUT
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION
Name Type Height Type
Max
Span
OC
Spacing Detail Max Landscape
OC Spacing
Max Landscape
Overhang
Max Portrait
OC Spacing
Max Portrait
Overhang Configuration
AR-01
FLAT, ROLLED COMP
[TILT KIT] - OMNIBASE 1
LAG - UR
1-Story 2X8 RAFTERS 15'-2" 16"
ULTRA RAIL, SYSTEM DETAIL, FIXED TILT:
SNR-DC-00335 [FLAT, TILT KIT (ROLLED
COMP/ MEMBRANE/ FOAM) 1 LAG
OMNIBASE]
5'-4"2'-1"5'-4"2'-1"STACKED
SEE SITE PLAN FOR NORTH ARROW
INSTALLERS SHALL NOTIFY ENGINEER OF ANY
POTENTIAL STRUCTURAL ISSUES OBSERVED
PRIOR TO PROCEEDING W/ INSTALLATION.
NOTES TO INSTALLER:
LOCATION OF RAFTERS AND PENETRATIONS
* IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12"
BOUNDARY REGION OF ANY ROOF PLANE
EDGES (EXCEPT VALLEYS), THEN
ATTACHMENTS NEED TO BE ADDED AND
OVERHANG REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS FOLLOWS:
** ALLOWABLE ATTACHMENT SPACING
INDICATED ON PLANS TO BE REDUCED BY 50%.
** ALLOWABLE OVERHANG INDICATED ON
PLANS TO BE 1/5TH OF ALLOWABLE
ATTACHMENT SPACING INDICATED ON PLANS.
MODULE ELEVATION DETAIL - SCALE: NTS
2'-2"
1'-2"10°10°
ROOF PITCH, SEE NOTES MODULE PITCH, SEE NOTES
10"22'-8"10'-7"
1'-2"
13'-2"
2'-11"
5'-4" TYP 2'-2"
Signed 10/15/2024
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
MOUNTING DETAIL
PV-3.1
THE SNAPNRACK FIXED TILT IS A SIMPLE
SOLUTION FOR INSTALLATIONS
REQUIRING MODULE TILT BEYOND THE
EXISTING ROOF SLOPE. IT IS DESIGNED
FOR TILT ANGLES FROM 0°-30° ABOVE
THE HORIZONTAL UTILIZING FIXED
STANDOFF HEIGHTS
THE SNAPNRACK FIXED TILT IS
COMPATIBLE WITH THE VARIOUS
SNAPNRACK ROOF ATTACHMENTS
SHOWN. REFER TO SPECIFIC
"ATTACHMENT DETAIL"
REFER TO SNAPNRACK ENGINEERING
CHARTS FOR APPLICABLE RAIL SPANS.
"BIN" NUMBER ON CHART SHOULD MATCH
"BIN" NUMBER ON THIS DRAWING
REFER TO THE SNAPNRACK INSTALLATION
MANUAL FOR 5 16"Ø HARDWARE TORQUE
SPECIFICATIONS
FOR ADDITIONAL SYSTEM
REQUIREMENTS, INCLUDING MODULE
OVERHANG, SEE "SNR-DC-00329 ULTRA
RAIL, SYSTEM OVERVIEW, TYPICAL"
FOR LEVELING REQUIREMENTS SEE
"SNR-DC-00334 ULTRA RAIL, COMPONENT
DETAIL, LEVELING SPACER ON STANDOFF"
SNAPNRACK OMNIBASE CAN MOUNT IN
ANY ORIENTATION ON THE ROOF
RAILS CAN MOUNT ON ANY SIDE OF THE
STANDOFF POST
FOR "ROOF PITCH" GREATER THAN 7°,
"TILT ANGLE" MUST BE IN SAME
DIRECTION AS "ROOF PITCH"
UR-40 RAIL | UR-60 RAIL
FOR USE WITH SNAPNRACK ULTRA SERIES RAILS
21 4"
11 2"
11 2"
15 8"
FIXED TILT, INSTALLED
ALLOWABLE ANGLES
A
DETAIL A
FIXED TILT, FRONT LEG
(RAIL HIDDEN)
B
DETAIL B
FIXED TILT, REAR LEG
TILT ANGLE, RELATIVE
TO HORIZONTAL
(30° MAX)
METAL ROOF BASE:
BIN 10
DETAIL: SNR-DC-00352
DETAIL: SNR-DC-00353
1-HOLE BASE:
BIN 10
DETAIL: SNR-DC-00348
DETAIL: SNR-DC-00349
4-HOLE BASE:
BIN 11
DETAIL: SNR-DC-00350
DETAIL: SNR-DC-00357
DETAIL: SNR-DC-00358
DETAIL: SNR-DC-00359
*COMPATIBLE ROOF ATTACHMENTS FOR FIXED TILT
PV MODULE, TYP.
SNAPNRACK
ULTRA RAIL
ROOF DECKING,
(ROOFING MATERIAL
NOT SHOWN)
STRUCTURAL MEMBER,
WOOD RAFTER SHOWN
PV MODULE, TYP.SNAPNRACK
MODULE CLAMPS
ROOF PITCH, VARIES
TILT ABOVE
ROOF SURFACE
(5°-30°)
OMNIBASE
BIN 10
DETAIL: SNR-DC-01249
DETAIL: SNR-DC-01250
DETAIL: SNR-DC-01251
DETAIL: SNR-DC-01252
DETAIL: SNR-DC-01253
DETAIL: SNR-DC-01254
SNAPNRACK FIXED
TILT, REAR LEG
(LENGTH VARIES)
SNAPNRACK FIXED
TILT, FRONT LEG
(LENGTH VARIES)
SNAPNRACK FIXED
TILT, REAR LEG
(LENGTH VARIES)
SNAPNRACK FIXED
TILT, FRONT LEG
(LENGTH VARIES)
SNAPNRACK AP 90 L FOOT
WITH UR MOUNT HARDWARE
5 16"-18 BOLT WITH
SERRATED FLANGE NUT, S.S.
SNAPNRACK
STANDOFF CLAMP
SNAPNRACK STANDARD
STANDOFF, LENGTH VARIES:
5-1 2" OR 10"
SNAPNRACK ROOF ATTACHMENT - COMPATIBLE
WITH ATTACHMENTS SHOWN ABOVE. REFER TO
SPECIFIC SNAPNRACK "ATTACHMENT DETAIL"
SNAPNRACK STANDARD
STANDOFF, LENGTH VARIES:
10", 14" OR 23"
Signed 10/15/2024
1414 S Shelton St
12/2/2024
PAGE
REV: C 10/25/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
BACKUP LOADS
LOAD BREAKER RATING
(AMPS)LABEL DEMAND
LOAD
1 20A-1P LIGHTS & RECEPTABLES 1500 VA
2 20A-1P LIGHTS & RECEPTABLES 1500 VA
3 20A-1P LIGHTS & RECEPTABLES 1500 VA
4 20A-1P LIGHTS & RECEPTABLES 1500 VA
5 20A-1P BED 1500 VA
6 20A-1P KITCHEN 1500 VA
7 20A-1P DISPOSAL 1500 VA
8 20A-1P FRIDGE 1500 VA
9 30A-2P 240V GARAGE OUTLET 5760 VA
PV-4.2
#ESTAMP
BACKUP LOAD
CALCS
BACKUP LOAD CALCS
ALL BACKED UP LOADS ABOVE IN THE BACKED UP LOADS PANEL ARE RELOCATED FROM THE MAIN SERVICE
PANEL.
BACKED UP LOADS CALCULATION:
(5760 VA)/ 240V = 24 A PER CEC 2022 ARTICLE 690.10 OR NEC 2020 ARTICLE 710.15.
THE MAXIMUM CURRENT FOR ALL LARGE APPLIANCES LOADS IS 24A.
(MAX LOADS OUTPUT) X (CONTINUOUS LOADS) =
24 A X 1.25 = 30 A
BACKED UP LOADS PANEL BREAKER = 150A
100 A < 150A.
THEREFORE, THE AMPERAGE OF THE BACKED UP LOADS IS LESS THAN THAT OF THE OCPD.
AC WIRE SIZING FOR BACKUP LOADS PANEL
MAX AC OUTPUT CURRENT = (MAX LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
24 A X 1.25 = 30 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
30A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
C
1414 S Shelton St
12/2/2024
PAGE
REV: C 10/25/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
CONDUIT SCHEDULE
TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT
1 Inverter Input (2) 10 AWG (PV WIRE)N/A (1) 6 AWG (BARE)Open Air
2 Inverter Input (2) 10 AWG THHN/THWN-2 N/A (1) 8 AWG THHN/THWN-2 3/4 EMT
3 Inverter Output (2) 6 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2 3/4 EMT
4 Panel Feeder (2) 1/0 AWG THHN/THWN-2 (1) 1/0 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2 1 1/2 EMT
5 Backup Load
(8) 10 AWG THHN/THWN-2 (8) 10 AWG THHN/THWN-2
(1) 8 AWG THHN/THWN-2 1 1/4 EMT
(2) 10 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2
E EXISTING
EXISTING 200A
MAIN BREAKER
END FED
EXISTING 200A
MAIN PANEL
200A BUS
M
150A
CTRL
M
NEW 200A
BACKUP GATEWAY
(2) - 60A PV +ESS BREAKER
(1) (E) 20A PV BREAKER
IN (N) INTERNAL
PANELBOARD
4
A
A
NEW 225 A
BACK UP LOADS PANEL
WITH 150 A MAIN BREAKER
RELOCATED (E) LOADS
4
(N) IMO PE69-3020,
DISCONNECT
SWITCH, 3P, 16A
RSD
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT
3
J-BOX
LONGI GREEN ENERGY TECHNOLOGY CO LTD:
LR5-54HABB-400M
STRING 1 OF 6 MODULES
2 MODULE LEVEL
RAPID SHUTDOWN DEVICES
12
RSD
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT
3 J-BOX
LONGI GREEN ENERGY TECHNOLOGY CO LTD:
LR5-54HABB-400M
STRING 1 OF 3 MODULES
1 MODULE LEVEL
RAPID SHUTDOWN DEVICES
12
POINT OF INTERCONNECTION CEC 2022:705.12(B)(3)(3), LOAD
BREAKER AT OPPOSITE END OF BUSBAR
METER
NUMBER: 222013-458849
EQUIPMENT CHARACTERISTICS
INCLUDED IN SPEC SHEETS
NOTE: TOTAL PV BACKFEED (E+N)
= 140A USED FOR INTERCONNECTION CALCULATIONS
Existing Inverter(s)E
SolarEdge Technologies: SE3800H-USMN
J-BOX
14 JA SOLAR: JAM54S31-395/MR
12
E20A OCPD
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB, 60A , 2P
120/240VAC
3
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB, 60A , 2P
120/240VAC
3
E
(E) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU324RB
3R, 30A , 2P
120/240VAC
E
60A
60A
5
FACILITY
GROUND
PV-4.0
ELECTRICAL
#ESTAMP
GENERAL NOTES:
GROUNDS RODS OR COLD WATER GAS BOND
BREAKER CONDUCTORS IN TWO SEPARATE CONDUITS.
CONDUCTOR SIZINGS ARE SUBJECT TO CHANGE AT TIME OF
INSTALlATION IF THE BACKUP LOADS ARE RELOCATED MORE THAN
2' FROM THEIR CURRENT INTERCONNECTION POINT TO COMPLY
WITH CEC 310.15(C)(1).
MODULE CHARACTERISTICS
LONGI GREEN ENERGY
TECHNOLOGY CO LTD:
LR5-54HABB-400M
400 W
OPEN CIRCUIT VOLTAGE 37.05 V
MAX POWER VOLTAGE 30.94 V
SHORT CIRCUIT CURRENT 13.72 A
C
C
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
PV-4.1
ELECTRICAL CALCS
#ESTAMP
ELECTRICAL CALCS
SYSTEM INFORMATION
3.6 KW DC PHOTOVOLTAIC SYSTEM
(6) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
(3) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
SYSTEM OCPD SIZE
(COMBINED MAX CURRENT) X (CONTINUOUS LOAD) =
112 A X 1.25 = 140 A → 140 A OVERCURRENT PROTECTIO
ALLOWABLE BACKFEED
MAX ALLOWED TOTAL GENERATION BACKFEED OCPD = MAIN BREAKER RATING =
200A
LOADS IN MAIN PANEL: 00A LOADS + 150A GATEWAY BREAKER = 150A ≤ 200A
INTERCONNECTION MEETS CEC 2022: 705.12(B)(3)(3) REQUIREMENTS.
GATEWAY SYSTEM AC WIRE SIZING
MAX AC OUTPUT CURRENT = 150 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 170A = 154.7A
TERMINAL RATING[110.14(C)] =
1/0AWG, 75°C RATED = 150A
150A < 154.7A TERMINAL RATING GOVERNS CONDUCTOR SIZING
150A < 150A 1/0 AWG AMPACITY OK
THEREFORE 1/0 AWG IS SUFFICIENT.
INVERTER INFORMATION
2400 KW DC PHOTOVOLTAIC SYSTEM
(6) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS LOAD)[690.8(B)(1)]=
13.72A X 1.25 X 1.25 = 21.43A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
21.43A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG, 75°C RATED = 65A
65A < 68.25A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A → 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT.
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] + VOC} X (# MODULES /
STRING) =
{[(-0.26 %/°C X 37.05 V) / 100] X [-2 °C - 25 °C] + 37.05 V} X 6 = 238 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 13.72A X 1 = 17.15
INVERTER INFORMATION
1200 KW DC PHOTOVOLTAIC SYSTEM
(3) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3
1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS
LOAD)[690.8(B)(1)]=
13.72A X 1.25 X 1.25 = 21.43A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
21.43A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG, 75°C RATED = 65A
65A < 68.25A → TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A → 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT.
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] +
VOC} X (# MODULES / STRING) =
{[(-0.26 %/°C X 37.05 V) / 100] X [-2 °C - 25 °C] + 37.05 V} X 0 = 119 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 13.72 A X 1 = 17.15A
1414 S Shelton St
12/2/2024
#ESTAMP
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20200
PANEL
SCHEDULE
PAGE
REV: C 10/25/24
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN/TMK #: APN: 013-051-21
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
PV-4.3
PANEL SCHEDULE
225/200A FUTURE
MAIN PANEL
150(N) GATEWAY
FEEDER
BREAKER
MAIN BREAKER
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20
150
225/150A FUTURE
BACKUP LOAD PANEL
MAIN BREAKER
240 V GARAGE OUTLET30
20LIGHTING & RECEPTABLES
LIGHTING & RECEPTABLES 202020LIGHTING & RECEPTABLES
LIGHTING & RECEPTABLES 2020BED
KITCHEN
2020DISPOSAL
FRIDGE
FUTURE 200A BACKUP
GATEWAY
602
4
6
8
10
12
14
16
18
20
NEW PV+ESS
BREAKER60
20NEW PV+ESS
BREAKER
EXISTNG PV
BREAKER
1
3
5
7
9
11
13
15
17
19
C
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.0
#ESTAMP
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48.00 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
POWER SOURCE OUTPUT CONNECTION
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
CEC 2022: 705.12(B)(3)(2)
NOTES AND SPECIFICATIONS:
SIGNS AND LABELS SHALL MEET THE
REQUIREMENTS OF THE CEC 2022
ARTICLE 110.21(B), UNLESS SPECIFIC
INSTRUCTIONS ARE REQUIRED BY
SECTION 690, OR IF REQUESTED BY
THE LOCAL AHJ.
SIGNS AND LABELS SHALL
ADEQUATELY WARN OF HAZARDS
USING EFFECTIVE WORDS, COLORS
AND SYMBOLS.
LABELS SHALL BE PERMANENTLY
AFFIXED TO THE EQUIPMENT OR
WIRING METHOD AND SHALL NOT BE
HAND WRITTEN.
LABEL SHALL BE OF SUFFICIENT
DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED.
SIGNS AND LABELS SHALL COMPLY
WITH ANSI Z535.4-2011, PRODUCT
SAFETY SIGNS AND LABELS, UNLESS
OTHERWISE SPECIFIED.
DO NOT COVER EXISTING
MANUFACTURER LABELS.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
4"
3"
ELECTRICAL SHOCK HAZARD
WARNING
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S),
AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC
2022: 690.13(B)
!
INVERTER 1
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
PER CODE(S): NEC 2020: 705.10, 710.10. CEC 2022: 705.10, 710.10
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:
690.31(D)(2)
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC
2022: 705.12(C)
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
ENERGY STORAGE SYSTEM
DISCONNECT
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
THIS EQUIPMENT FED BY
MULTIPLE SOURCES. TOTAL
RATING OF ALL OVERCURRENT
DEVICES EXCLUDING MAIN
SUPPLY OVERCURRENT DEVICE
SHALL NOT EXCEED AMPACITY OF
BUSBAR
WARNING!
LABEL LOCATION:
PV LOAD CENTER (IF APPLICABLE) AND
ANY PANEL THAT UTILIZES "THE SUM
OF BREAKERS RULE".
PER CODE(S): NEC 2020: 705.12 (B)(3)(3),
CEC 2022: 705.12 (B)(3)(3)
ENERGY STORAGE SYSTEM
PREMISES WIRING MAY REMAIN
ENERGIZED AFTER LOSS OF
UTILITY POWER
CAUTION!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C)
CAUTION
1414 S SHELTON ST, SANTA ANA, CA, 92707
SOLAR PANELS
ON ROOF
AC DISCONNECT
INVERTER + ESS (EXT)
BACKUP GATEWAY
AND PV BREAKER
DISCONNECT BACKUP LOADS PANEL
RAPID SHUTDOWN SWITCH
SERVICE ENTRANCE AND
GATEWAY FEEDER
BREAKER
MULTIPLE SOURCES OF POWER
(E) PV EQUIPMENT
(E) PV ARRAY
PV SYSTEM(S) ARE EQUIPPED WITH
RAPID SHUTDOWN DEVICE(S)
RAPID SHUTDOWN DISCONNECT LOCATION
(EXISTING SYSTEM AC DISCONNECT)
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48.00 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
1414 S Shelton St
12/2/2024
PAGE
REV: B 10/14/2024
FELIPE SERRANO
1414 S SHELTON ST, SANTA
ANA, CA, 92707
PROJECT NUMBER:
109R-414SER1
SHEET
DESIGNER:
ARUN MOHAN
CUSTOMER RESIDENCE:
TEL. (714) 299-7123
APN: 013-051-21
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.1
#ESTAMP
LABEL LOCATION:
BACKUP LOAD PANEL
NO ADDITIONAL
LOADS TO BE
ADDED
ONLY THIS
INVERTER HAS
RAPID SHUT DOWN
ENERGY STORAGE SYSTEM DISCONNECT
NOMINAL ESS VOLTAGE VAC
LABEL LOCATION:
MAIN PANEL.
120 240
NEC 2020 - PW3
PER CODE(S): NEC 706.15(C)
1414 S Shelton St
12/2/2024
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 1 of 8 GFT-OP-11a (22-August-2019) Test Verification of Conformity Verification Number: 104514208CRT-001VOC Applicant Name & Address: Tesla Inc. 3500 Deer Creek Road, Palo Alto, CA 94304 Product Description: Energy Storage System Grid Support Utility Interactive & Standalone Inverter Ratings & Principle Characteristics: See Appendix 2 Models/Type References: 1707000- followed by two numbers; followed by -; followed by one letter. Brand Names: Tesla Relevant Standard(s) / Specification(s): See Appendix 1 Verification Issuing Office Name & Address: Intertek Testing Services NA, Inc. 3933 US Route 11, Cortland, NY 13045 USA Date of Tests: 9/15/2022 to 4/23/2024 Test Report Number(s): 104514208CRT-001, 104514208CRT-001RRF, 104514208CRT-001TRS, 104514208CRT-010, 104514208CRT-012 Additional information in Appendix. Signature Name: Mukund Rana Position: Sr. Staff Engineer Date: 10th May 2024 On the basis of the tests undertaken, the samples of the below product have been found to comply with the requirements of the referenced standards at the time the tests were carried out. This verification is part of the full test report and should be read in conjunction with it. This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 2 of 8 GFT-OP-11a (22-August-2019) Appendix 1: Relevant Standard(s)/Specification(s) Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3] Grid Support Utility Interactive Equipment - Supplement SA to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement SA)] Grid Support Utility Interactive Inverters and Converters Based Upon IEEE 1547:2018 & IEEE 1547.1:2020 - Supplement SB to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement SB)] Energy Storage Systems and Equipment [ANSI/UL 9540:2020 Ed.2+R:09Apr2021] Photovoltaic (PV) DC Arc-Fault Circuit Protection [UL 1699B:2018 Ed.1+R:18May2021] Software in Programmable Components [UL 1998:2013 Ed.3+R:24Sep2018] Tests For Safety-related Controls Employing Solid-state Devices [UL 991:2004 Ed.3+R:09Jun2010] Batteries for Use in Stationary, Vehicle Auxiliary Power and Light Electric Rail (LER) Applications [ANSI/UL 1973:2018 Ed.2] IEEE 1547:2018 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces IEEE 1547a:2020 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces Amendment 1: To Provide More Flexibility for Adoption of Abnormal Operating Performance Category III IEEE 1547.1:2020 - IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated Interfaces Source requirements document UL 1741 (SRD) v2.0 – HECO Electric Rule No.21-2020 Generating Facility Interconnections Default New England Bulk System Area Settings Requirement PRC-024-3 Frequency and Voltage Protection Settings for Generating Resources GOVERNMENT OF PUERTO RICO PUBLIC SERVICE REGULATORY BOARD PUERTO RICO ENERGY BUREAU, Generating Facility and Microgrid Interconnection Regulation (“Regulation”), July 2021 Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2] Safety Functions Incorporating Electronic Technology [CSA C22.2#0.8:2019 Ed.4] 1414 S Shelton St12/2/2024
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 3 of 8 GFT-OP-11a (22-August-2019) Appendix 2: Ratings & Principle Characteristics: ➢ Ratings: Models 1707000-xx-y Rated AC Output Power (W) 11500, 10000, 7680, 5750 Rated AC Input Power (W) Charging 5000 Max. Cont. Output Power (W) 11500, 10000, 7680, 5750 Max. Continuous Output PV to AC Power Off-Grid (W) 15400 Max. Cont. Input Power (W) Charging 5000 AC Input / Output Voltage (VL-L) 240 AC Output Frequency (Hz) 60 Max. Cont. Output Current (A) 48, 41.6, 32, 24 Max. Cont. Input Current (A) Charging 20.83 Apparent Power rating (VA) 11500, 10000, 7680, 5750 Apparent Power rating (VA) Charging 5000 Normal Category A, B Abnormal Category II, III ➢ Communication Protocol: IEEE 2030.5 protocol ➢ PCH board MD5 Firmware checksum: c5773b136a9ef9be9057302a67258482 ➢ TACO board MD5 Firmware checksum: dcq8OiBXbQWYnK9UhCAjvl02/py2MZymmwAQYOn8jSc= ➢ Grid Support Function Parameters: Tesla used the parameters in the Result reporting form “104514208CRT-001RRF” during the testing of the grid support functions according to UL1741 SB. The parameters that have “blank” as their value are not applicable. ➢ UL 1998 and CSA C22.2#0.8 Evaluation: ECU / Board Rev Software version Checksum UL1998, CSA C22.2#0.8 Compliant* Date of evaluation HVP / -E V2 51705DB5 Yes Apr-19-2024 PWS / -3F V2 34204954 Yes Apr-19-2024 PWS / -1F V2 B3C1375B Yes Apr-19-2024 PWS / -D V2 43FEF523 Yes Apr-19-2024 *Note: Below safety functions were evaluated during the UL1998 and UL 991 evaluation. • List of all UL1998 and UL 991 functions are as follow: o Overcharge o Over-discharge o Over Temperature o Over current o Relay weld, Isolation Monitoring Interruption, PV RSD (UL 1741) o AFCI (UL 1699B) This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 4 of 8 GFT-OP-11a (22-August-2019) 1414 S Shelton St12/2/2024
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 5 of 8 GFT-OP-11a (22-August-2019) Appendix 3: List of Tested Grid protection / Support Function: Table 3A: Test List -1 Grid protection / Support Function Tested Test Standards Sections and Source Requirement Documents IEEE 1547-2018 IEEE 1547.1-2020 UL 1741SB - 2021 CA Rule 21:2020 UL 1741 SRD V2.0 (HECO):2020 OPERATIONAL TEMPERATURE -- 5.3.3.1 SB4.3.5.3 -- Same as 1547-2018 PROTECTION FROM ELECTROMAGNETIC INTERFERENCE (EMI) TEST 4.11.1 5.8.1 SB4.3.5.8.1 -- Same as 1547-2018 SURGE WITHSTAND PERFORMANCE TEST 4.11.2 5.8.2 SB4.3.5.8.2 -- Same as 1547-2018 PARALLELING DEVICE 4.11.3 5.8.3 -- -- Same as 1547-2018 OVERVOLTAGE TRIP 6.4.1 5.4.2 SB4.3.5.4.2 Electric Rule No. 21 Table Hh.1 Same as 1547-2018 UNDERVOLTAGE TRIP 6.4.1 5.4.3 SB4.3.5.4.3 Electric Rule No. 21 Table Hh.1 Same as 1547-2018 OVERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2 SB4.3.5.5.1 & SB4.3.5.5.2 Electric Rule No. 21 Table Hh.2 Same as 1547-2018 UNDERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2 SB4.3.5.5.1 & SB4.3.5.5.2 Electric Rule No. 21 Table Hh.2 Same as 1547-2018 LOW VOLTAGE RIDE-THROUGH 6.4.2.3 & 6.4.2.5 5.4.4 SB4.3.5.4.4 Electric Rule No. 21 Table Hh.1 Same as 1547-2018 HIGH VOLTAGE RIDE-THROUGH 6.4.2.4 5.4.7 SB4.3.5.4.7 Electric Rule No. 21 Table Hh.1 Same as 1547-2018 LOW FREQUENCY RIDE-THROUGH 6.5.2.3 5.5.3 SB4.3.5.5.3 Electric Rule No. 21 Table Hh.2 SRD-UL-1741-SA-V2.0 (HECO) Part II B HIGH FREQUENCY RIDE-THROUGH 6.5.2.4 5.5.4 SB4.3.5.5.4 Electric Rule No. 21 Table Hh.2 SRD-UL-1741-SA-V2.0 (HECO) Part II B RATE OF CHANGE OF FREQUENCY 6.5.2.5 5.5.5 -- -- Same as 1547-2018 ANTI-ISLANDING PROTECTION - WITH GRID SUPPORT FUNCTIONS ENABLED 8.1 5.10.2 SB4.3.5.10.2 Electric Rule No. 21 Hh.1a According to UL 1741 SA-V2.0 (HECO) TEST FOR VOLTAGE PHASE-ANGLE CHANGE RIDE-THOUGH (VARIATION 1) 6.5.2.6 5.5.6.1 SB4.3.5.5.6 -- Same as 1547-2018 ENTER SERVICE 4.10 5.6 -- -- Same as 1547-2018 SYNCHRONIZATION CONTROL FUNCTION TEST FOR EQUIPMENT WITH NO SYNCHRONIZING DISABLE CAPABILITY (VARIATION 3) 6.3 5.7.4 -- -- Same as 1547-2018 LIMITATION OF DC INJECTION FOR INVERTERS 7.1 5.9 -- Electric Rule No. 21 Hh.2h Same as 1547-2018 OPEN PHASE 6.2.2 5.11 -- -- Same as 1547-2018 CURRENT DISTORTION 7.3 5.12 -- Electric Rule No. Same as 1547- This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 6 of 8 GFT-OP-11a (22-August-2019) Grid protection / Support Function Tested Test Standards Sections and Source Requirement Documents IEEE 1547-2018 IEEE 1547.1-2020 UL 1741SB - 2021 CA Rule 21:2020 UL 1741 SRD V2.0 (HECO):2020 21 Hh.2g 2018 LIMIT ACTIVE POWER 4.6.2 5.13 -- Electric Rule No. 21 Hh.8 Same as 1547-2018 CONSTANT POWER FACTOR 5.3.2 5.14.3 SB4.3.5.14.3 Electric Rule No. 21 Hh.2i Same as 1547-2018 VOLTAGE-REACTIVE POWER (VOLT-VAR) MODE FIXED VREF 5.3.3 5.14.4 SB4.3.5.14.4 Electric Rule No. 21 Hh.2J Same as 1547-2018 VOLTAGE-REACTIVE POWER (VOLT-VAR) MODE (VREF TEST) 5.3.3 5.14.5 SB4.3.5.14.5 -- Same as 1547-2018 ACTIVE POWER-REACTIVE POWER MODE (WATT-VAR) 5.3.4 5.14.7 SB4.3.5.14.7 -- Same as 1547-2018 CONSTANT REACTIVE POWER (VAR) MODE 5.3.5 5.14.8 SB4.3.5.14.8 -- Same as 1547-2018 VOLTAGE-ACTIVE POWER (VOLT-WATT) MODE 5.4 5.14.9 SB4.3.5.14.9 Electric Rule No. 21 Hh.2.m Same as 1547-2018 TEST FOR FREQUENCY-DROOP (FREQUENCY-POWER OR FREQUENCY-WATT) CAPABILITY—ABOVE NOMINAL FREQUENCY 6.5.2.7 5.15.2 SB4.3.5.15.2 Electric Rule No. 21 Hh.2.l SRD-UL-1741-SA-V2.0 (HECO) Part II C TEST FOR FREQUENCY-DROOP (FREQUENCY-POWER OR FREQUENCY-WATT) CAPABILITY—BELOW NOMINAL FREQUENCY 6.5.2.7 5.15.3 SB4.3.5.15.3 Electric Rule No. 21 Hh.2.l SRD-UL-1741-SA-V2.0 (HECO) Part II C PRIORITIZATION OF DER RESPONSES 4.7 5.16 SB4.3.5.16 -- Same as 1547-2018 LOAD REJECTION OVERVOLTAGE (LROV) 7.4 5.17.2 SB4.3.5.17.2 -- Same as 1547-2018 FAULT CURRENT TESTS FOR INVERTERS 6.2.1 5.18.1 -- -- Same as 1547-2018 PERSISTENCE OF DER PARAMETER SETTINGS -- 5.19 -- -- Same as 1547-2018 NORMAL RAMP RATE -- -- -- Electric Rule No. 21 Hh.2k -- NAMEPLATE DATA TEST 10.3 6.4 -- -- Same as 1547-2018 MONITORING INFORMATION TEST 10.5 6.6 SB4.3.6.6 -- Same as 1547-2018 MANAGEMENT INFORMATION TEST 10.6 6.7 SB4.3.6.7 -- Same as 1547-2018 1414 S Shelton St12/2/2024
1414 S Shelton St
12/2/2024
Powerwall 3
Power Everything
2024
—
Powerwall 3 is a fully integrated solar and battery system, designed to accelerate the transition to sustainable energy. Customers
can receive whole home backup, cost savings, and energy independence by producing and consuming their own energy while
participating in grid services. Once installed, customers can manage their system using the Tesla App to customize system
behavior to meet their energy goals.
Powerwall 3 achieves this by supporting up to 20 kW DC of solar and providing 11.5 kW AC of continuous power per unit. It has
the ability to start heavy loads up to 185 A LRA, meaning a single unit can support the power needs of most homes. Powerwall 3
isdesignedformassproduction,fastandefcientinstallations,easysystemexpansion,andsimpleconnectiontoanyelectrical
service.
22024Powerwall 3 Datasheet
Solar Technical
Specications
Maximum Solar STC Input 20 kW
WithstandVoltage 600 V DC
PVDCInputVoltageRange 60 — 550 V DC
PVDCMPPTVoltageRange 60 — 480 V DC
MPPTs 6
Maximum Current per MPPT (Imp)13 A 5
Maximum Short Circuit Current per MPPT (Isc)15 A 5
Powerwall3 Technical Specifications
1 Typical solar shifting use case.
2 Values provided for 25°C (77°F), at beginning of life. 3.3 kW charge/discharge power.
3 TestedusingCECweightedefciencymethodology.
4 ThecustomerisexpectedtoprovideinternetconnectivityforPowerwall3;cellularshouldnotbeusedastheprimarymodeof
connectivity. Cellular connectivity subject to network operator service coverage and signal strength.
5 WheretheDCinputcurrentexceedstheMPPTrating,ajumpercanbeusedtocombinetwoMPPTsintoasingleinputto
intake DC current up to 26 A IMP / 30 A ISC.
Battery Technical
Specications
Nominal Battery Energy 13.5 kWh AC 2
MaximumContinuousDischargePower 11.5 kW AC
MaximumContinuousChargePower 5 kW AC
OutputPowerFactorRating 0-1(GridCodecongurable)
MaximumContinuousCurrent 48 A
Maximum Output Fault Current 10 kA
LoadStartCapability(1s)185 A LRA
PowerScalability Up to 4 Powerwall 3 units supported
SystemTechnical
Specications
ModelNumber 1707000-xx-y
NominalGridVoltage(Input&Output)120/240 VAC
GridType Split phase
Frequency 60 Hz
OvercurrentProtectionDevice 60 A
SolartoBatterytoHome/GridEfciency 89% 1,2
SolartoHome/GridEfciency 97.5% 3
SupportedIslandingDevices Gateway 3, Backup Switch, Backup Gateway 2
Connectivity Wi-Fi (2.4 and 5 GHz), Dual-port switched Ethernet,
Cellular (LTE/4G 4)
HardwareInterface Drycontactrelay,RapidShutdown(RSD)certiedswitch
and 2-pin connector, RS-485 for meters
AC Metering Revenue Grade (+/- 0.5%)
Protections Integrated arc fault circuit interrupter (AFCI), Isolation
MonitorInterrupter(IMI),PVRapidShutdown(RSD)using
TeslaMid-CircuitInterrupters
CustomerInterface TeslaMobileApp
Warranty 10 years
1414 S Shelton St
12/2/2024
1414 S Shelton St
12/2/2024
!"#!$%$&
'
(
)( *+ ,-
((* ,
. ) ./
( *
00+&1&2!!%
. .3(
4
/
*4
.
.3#!5$
/
.(
/(
671.(
.3%$&..
*8
./)(
..
4
*.
((
(.
%. .3*8
/
-)
/(
(
(..
.3 *
.3
.
( *"(
3
.3 !"$
9
$:222$&
(-.-$: 222$&88
-8(
-
.
* :;#2615--<72715.=
3 2#!5--<;2#&5.=
8 ;1215--<&2715.=3
..3 >
&2;152-<&15()/2.=!2!!?!2!:5.@<2!6?12#5--@=$: 222$:!=&2;152-<&15()/2.=$: 222$:!=12!652-< 15()/2.=!2!:5.@<62&75--@=$6=12!652-< 15()/2.=!2!?!2!&5.@<:2&?:2:5--@=$#222$ =12#152-<1!5()/2.=!2! 5.@<#2#75--@=$&=
.3
.88.3
(
3*!!:!#AB%$&B&!!!$.
(
:$(
-
+-
.
.. .
.
)
/
.. )
/
-..3
)( *
(
)( */
8 /8
/
88(
.Feb 3, 2020:!!761;!: ;: ;:
,
3
4
3 <)=2::5,3< 2#15()<==
.
)( *C
. */3.%D//
.
)( *
.
)(
//
.
--8
(/.
88 .#1$+8
.
E8
*
-
(.(.3+
.(
-8.4,.4.
/
(/.
.3
.A
8 '
-2-
./-
.3 44428#14
..32
23'$
3(
.$
(
.$/
/"C
'
-8(
.
(
.E
'*-
(/
C
%
*/
C
E
-8 ../-
.C
.
3(
..
(
.
'
.
(
.< /.
(
3
(8
=.'.-
.
((
.'.-
.
(/(
(
*/(
.
/8
/
*(.38
..
(4
. *
. *:6-. 1414 S Shelton St12/2/2024
32024Powerwall 3 Datasheet
Mechanical
Specications
Dimensions 1099x609x193mm(43.25x24x7.6in)
Weight 130 kg (287 lb)
MountingOptions Floor or wall mount
Powerwall3 Technical Specifications
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F) 6
OperatingHumidity(RH)Up to 100%, condensing
Storage Temperature –20°C to 30°C (–4°F to 86°F), up to 95% RH, non-
condensing, State of Energy (SOE): 25% initial
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
EnclosureRating NEMA3R
IngressRating IP67 (Battery & Power Electronics)
IP45 (Wiring Compartment)
PollutionRating PD3
OperatingNoise@1m < 50 db(A) typical
<62db(A)maximum
Compliance
Information
Certications UL 1642, UL 1699B, UL 1741, UL 1741 SA, UL 1741 SB, UL
1741 PCS, UL 3741, UL 1973, UL 1998, UL 9540, IEEE 1547-
2018, IEEE 1547.1, UN 38.3
GridConnection United States
Emissions FCC Part 15 Class B
Environmental RoHS Directive 2011/65/EU
Seismic AC156, IEEE 693-2005 (high)
FireTesting Meetstheunitlevelperformancecriteria
of UL 9540A
6 Performance may be de-rated at operating temperatures above 40°C (104°F).
609 mm 193
mm
1099 mm
42024Powerwall 3 Datasheet
Electrical
Specications
Model MCI-1 MCI-2
NominalInputDCCurrentRating(IMP)13 A 13 A
Maximum Input Short Circuit Current (ISC)19 A 17 A
MaximumSystemVoltage(PVHCS)600 V DC 1000 V DC
7
Solar Shutdown Device Technical Specifications
Environmental
Specications
Operating Temperature -40°C to 50°C
(-40°F to 122°F)
-45°C to 70°C
(-49°F to 158°F)
Storage Temperature –30°C to 70°C
(–22°F to 158°F)
–30°C to 70°C
(–22°F to 158°F)
EnclosureRating NEMA4X/IP65NEMA4X/IP65
RSDModule
Performance
MaximumNumberofDevicesperString 5 5
Control PowerLineExcitation PowerLineExcitation
PassiveState Normally Open Normally Open
MaximumPowerConsumption 7 W 7 W
Warranty 25 years 25 years
—
TheSolarShutdownDeviceisaMid-CircuitInterrupter(MCI)andispartofthePVsystemrapidshutdown(RSD)functionin
accordance with Article 690 of the applicable NEC. When paired with Powerwall 3, solar array shutdown is initiated by any loss
of AC power.
Mechanical
Specications
ElectricalConnections MC4Connector MC4Connector
Housing Plastic Plastic
Dimensions 125x150x22mm
(5x6x1in)
173x45x22mm
(6.8x1.8x1in)
Weight 350 g (0.77 lb) 120 g (0.26 lb)
MountingOptions ZEP Home Run Clip
M4Screw(#10)
M8Bolt(5/16")
Nail / Wood screw
Wire Clip
Compliance
Information
Certications UL 1741 PVRSE, UL 3741,
PVRSA (Photovoltaic Rapid Shutdown Array)
RSDInitiationMethod ExternalSystemShutdownSwitchor
Powerwall 3 Enable Switch
7MaximumSystemVoltageislimitedbyPowerwallto600VDC.
UL3741PVHazardControl
(andPVRSA)Compatibility SeePowerwall3InstallationManual
1414 S Shelton St
12/2/2024
52024Powerwall 3 Datasheet
Gateway 3
8 Only Eaton CSR or BWH main breakers are 25 kA rated.
Performance
Specications
ModelNumber 1841000-01-y
NominalGridVoltage 120/240 V AC
GridConguration Split phase
GridFrequency 60 Hz
ContinuousCurrent
Rating
200 A
Maximum Supply Short
Circuit Current
22 kA with Square D or
Eaton main breaker
25 kA with Eaton main
breaker 8
IECProtectiveClass Class I
Overvoltage Category Category IV
Mechanical
Specications
Dimensions 660x411x149mm
(26x16x6in)
Weight 16.3 kg (36 lb)
Mountingoptions Wall mount
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
OperatingHumidity(RH)Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
EnclosureType NEMA3R
Compliance
Information
Certications UL 67, UL 869A, UL 916, UL 1741 PCS,
CSA 22.2 107.1, CSA 22.2 29
Emissions FCC Part 15, ICES 003
—
Tesla Gateway 3 controls connection to the grid in a Powerwall system, automatically detecting outages and providing seamless
transition to backup power. It provides energy monitoring that is used by Powerwall for solar self-consumption, time-based
control, and backup operation.
411 mm
660
mm
149
mm
AC Meter Revenue accurate (+/- 0.5%)
Communication CAN
UserInterface Tesla App
BackupTransition Automatic disconnect for
seamless backup
Overcurrent
ProtectionDevice
100–200 A
Service entrance rated
Eaton CSR, BWH, or BW, or
SquareDQOMbreakers
InternalPanelboard 200 A
8-space/16 circuit breakers
Eaton BR, Siemens QP, or
SquareDHOMbreakersrated
to 10–125A
Warranty 10 years
62024Powerwall 3 Datasheet
Backup Switch
9Breakermaximumsupplyshortcircuitcurrentratingmustbeequaltoorgreaterthantheavailablefaultcurrent.
Performance
Specications
ModelNumber 1624171-xx-y
ContinuousLoadRating 200 A, 120/240 V split phase
Maximum Supply Short Circuit Current 22 kA with breaker 9
Communication CAN
AC Meter Revenue accurate (+/- 0.5%)
ExpectedServiceLife 21 years
Warranty 10 years
Mechanical
Specications
Dimensions 176x205x74mm(6.9x8.1x2.9in)
Weight 2.8 lb
MeterandSocketCompatibility ANSI Type 2S, ringless or ring type
External Service Interface Contactor manual override 10
Reset button
ConduitCompatibility 1/2-inch NPT
Environmental
Specications
Operating Temperature –40°C to 50°C (–40°F to 122°F)
Storage Temperature –40°C to 85°C (–40°F to 185°F)
EnclosureRating NEMA3R
PollutionRating PD3
Compliance
Information
SafetyStandards USA: UL 414, UL 414 SB, UL 2735, UL 916, CA Prop 65
Emissions FCC, ICES
10Manuallyoverridesthecontactorpositionduringaserviceevent.
—
The Tesla Backup Switch controls connection to the grid in a Powerwall system, and can be easily installed behind the utility
meter or in a standalone meter panel downstream of the utility meter.
The Backup Switch automatically detects grid outages, providing a seamless transition to backup power. It communicates
directly with Powerwall, allowing home energy usage monitoring from any mobile device with the Tesla app.
204.86
74
176 mm
205 mm
74 mm
1414 S Shelton St
12/2/2024
72024Powerwall 3 Datasheet
Backup Gateway 2
Performance
Specications
ModelNumber 1232100-xx-y
ACVoltage(Nominal)120/240 V
Feed-inType Split phase
GridFrequency 60 Hz
CurrentRating 200 A
Maximum Supply Short
Circuit Current
10 kA 11
Overcurrent Protection
Device
100 - 200 A, Service
entrance rated 9
Overvoltage Category Category IV
Internal Primary
AC Meter
Revenue accurate
(+/- 0.2%)
Internal Auxiliary
AC Meter
Revenue accurate
(+/- 2%)
Primary Connectivity Ethernet, Wi-Fi
SecondaryConnectivity Cellular (3G, LTE/4G) 12
Mechanical
Specications
Dimensions 660x411x149mm
(26x16x6in)
Weight 20.4 kg (45 lb)
Mountingoptions Wall mount,
Semi-Đushmount
Environmental
Specications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
OperatingHumidity(RH)Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
EnclosureType NEMA3R
Compliance
Information
Certications UL 67, UL 869A, UL 916, UL 1741 PCS,
CSA 22.2 0.19, CSA 22.2 205
Emissions FCC Part 15, ICES 003
411 mm
660 mm
149
mm
11 When protected by Class J fuses, Backup Gateway 2 is
suitable for use in circuits capable of delivering not more
than 22kA symmetrical amperes.
12 Cellular connectivity subject to network operator service
coverage and signal strength.
—
Backup Gateway 2 controls connection to the grid when paired with Powerwall 3, automatically detecting outages and providing
seamless transition to backup power. Backup Gateway 2 also provides energy metering for solar self-consumption, time-based
control, and backup operation.
Inthissystemconguration,Powerwall3actsastheSiteController,withtheBackupGateway2SiteControllerdisabled.
UserInterface Tesla App
OperatingModes Support for solar self-
consumption, time-based
control, and backup
BackupTransition Automatic disconnect for
seamless backup
Modularity Supports up to 10 AC-
coupled Powerwalls
Optional Internal
Panelboard
200 A 6-space / 12 circuit
breakers
Siemens QP or Square D
HOMbreakersrated10-
80A or Eaton BR breakers
rated 10 - 125A
Warranty 10 years
82024Powerwall 3 Datasheet
Powerwall3 Example System Configurations
Powerwall 3 with Backup Switch
Whole Home Backup
Powerwall 3 with Gateway 3
Whole Home Backup
Powerwall 3 with Backup Gateway 2
Partial Home Backup
1414 S Shelton St
12/2/2024
This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 7 of 8 GFT-OP-11a (22-August-2019) Table 3B: Test List -2 Test Description CSA C22.2#107.1:2016 Ed. 4 CSA C22.3#9:2020 Ed 2 Screw Tightening Torque Test 3.6.3 -- Impedance Test 105.1/10.5.2 -- Continuity Test 4.1 -- Output Power Factor 4.2 -- Voltage Harmonics for stand alone 15.3.2.1 -- Frequency 10.5.4 -- Stand-alone inverter dc output short-circuits current contribution 10.5.5 -- Normal ramp rate -- 7.2.3.4.2 / 8.3.12.2.3 Flicker -- 7.2.2 / 8.3.13 Test for constant reactive power (var) mode 7.2.3.3.3 / 8.3.12.2.2 This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 8 of 8 GFT-OP-11a (22-August-2019) Appendix 4: Revision Summary Date / Project Engineer Comments 15-Feb-2023 Dipesh Patel Original issue date 8-Mar-2023 / G104200718 Dipesh Patel Added UL 1699B, UL 1998 and UL 991 standards 24-Mar-2023/ G104200718 Dipesh Patel Added UL 1973 standard. Added normal and abnormal category in ratings table. 18-Apr-2023 / G104200718 Dipesh Patel Added additional factory settable nameplate ratings rated output active power (W): 9600, 7680, 5750; Max. Continuous output power (W): 9600, 7680, 5750; Max. Cont. Output Current (A): 40, 32, 24; Apparent Power rating (VA): 9600, 7680, 5750 Added Puerto Rico Interconnection regulation as it refers to UL 1741 and IEEE 1547-2018. 1-May-2024 / G104514208 Mukund Rana A) Added standards. Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] B) Update CSA C22.2#0.8 standard C) added Table 3B: Test List -2 1414 S Shelton St12/2/2024
Service Voltage
240
Section 220.83 Existing Dwelling Unit
Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
19.1 4584
Part #2 - Section 220.83(B)(2), (3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500
1500
1500
1000
600
1000
1600
5760
Amps Box B (VA)
60.25 14460
Total VA from Parts #1 and #2 combined:Box A + Box B =19044
Total VA 19044
First 8000 VA @ 100%8000 Remaining VA @ 40%
Remaining VA =11044 11044 x 40% =4417.6 VA
Adding First 8000 VA, if possible 8000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:12417.6 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:51.74 Amps
Part #3 - Section 220.83(B) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:0 VA
100% of all the Heating or A/C loads in Amps:0.00 A
VA Volts Amps
Parts #1 & #2 12417.6 240 51.74
Part #3 0 240 0.00
Total VA for all Parts:12,418
Totals Service/Feeder Load 51.74
Microwave
EV Charger
Totals for Part #2:
Totals from all Parts
Dishwasher
Disposal
Refrigerator
Laundry
Appliance Circuit - 1
Appliance Circuit - 2
Dedicated circuit Dedicated circuit
Article 220 - Dedicated Backup Panel Calculation Job Code
1414 S Shelton St Santa Ana CA USA 92707 109R-414SER1
Building Square Footage VA (watts)Amps
House 1528.00 4584 19.10
Total for Part #1:
1414 S Shelton St
12/2/2024
Section 220.83 Existing Dwelling Unit
Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
19.1 4584
Part #2 - Section 220.83 (B)(2),(3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500 N/A
3000 N/A
1000 N/A
600 N/A
1000 N/A
1600 N/A
5760 N/A
N/A N/A
N/A N/A
N/A Amps Box B (VA)
N/A 60.25 14460
Total VA from Parts #1 and #2 combined:Box A + Box B =19044
Total VA 19044
First 8,000 VA @ 100%8000 Remaining VA @ 40%
Remaining VA =11044 11044 x 40% =4417.6 VA
Adding First 8000 VA 8000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:12417.6 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:51.74 Amps
Part #3 - Section 220.83 (B) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:0 VA
100% of all the Heating or A/C loads in Amps:0.00 A
VA Volts Amps
Parts #1 & #2 12417.6 240 51.74
Part #3 0 240 0.00
Total VA for all Parts:12,418
Totals Service/Feeder Load 51.74
#ESTAMP
Refrigerator(s)
Microwave(s)
Totals for Part #2:
EV Charger
Amps
19.1
Job Code
109R-414SER1
Totals from all Parts
Dedicated circuit
Total for Part #1:
House
Square Footage
1528
Article 220 - Service/Feeder calculation for (address):
1414 S Shelton St Santa Ana CA USA 92707
Building VA (watts)
4584
Laundry
Appliance Circuit(s)
Dishwasher(s)
Disposal(s)
Dedicated circuit
1414 S Shelton St
12/2/2024
Bus Rating:200
Main Rating:200
0%0%
Not Fed by other panels
Feeds: Panel 2 51.74
0.00
51.74
Bus Rating:225
Main Rating:150
100%100%
Itemized House and 240V Loads for Panel: (VA)
1500 1500
1500 1000
600 1000
1600 5760
Fed by: Panel 1
51.74
51.74
Panel 1 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Load Calc: (This Panel)
Total Load Calc:
Panel 2 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Laundry Appliance Circuit - 1
Load Calc: (This Panel)
Total Load Calc:
Appliance Circuit - 2 Dishwasher
Disposal Refrigerator
Microwave EV Charger
1414 S Shelton St
12/2/2024
1414 S Shelton St
12/2/2024
10/3/2024
RE: Structural Certification for Installation of Residential Solar
FELIPE SERRANO:1414 S SHELTON ST, SANTA ANA, CA, 92707
Code 2022 California Building Code (ASCE 7-16)
Risk category II Wind Load (component and Cladding)
Roof Dead Load Dr 10 psf V 96 mph
PV Dead Load DPV 3 psf Exposure B
Roof Live Load Lr 20 psf
Ground Snow S 0 psf
If you have any questions on the above, please do not hesitate to call.
Sincerely,
Eugene Munyanziza, P.E.
EV Engineering, LLC
projects@evengineersnet.com Signed: 10/3/2024
http://www.evengineersnet.com
Exp: 06/30/2026
Attn: To Whom It May Concern
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the
PV system to existing roof framing. From the field observation report, the roof is made of Flat Rolled
Composition shingle roofing over roof plywood supported by 2X8 Rafters at 16 inches. The slope of the roof
was approximated to be 3 degrees.
After review and based on our structural capacity calculation, the existing roof framing has been determined to
be adequate to support the imposed loads without structural upgrades.
I certify that the PV module assembly including all attachments supporting it have been reviewed to be in
accordance with manufacturer's specifications. Capacity Calculations were done in accordance with applicable
building codes.
Design Criteria
projects@evengineersnet.com
http://www.evengineersnet.com
1414 S Shelton St
12/2/2024
Wind Load Cont.
96 mph ASCE 7-16 Figure 26.5-1B
B
1.0 ASCE 7-16 Sec 26.8.2
0.57 ASCE 7-16 Table 26.10-1
0.85 ASCE 7-16 Table 26.6-1
1.00 ASCE 7-16 Table 26.9-1
11.40 psf
3.0 Degrees
1.5
0.8
Uplift (W)Zone(1)Zone(2r)Zone(2e)Zone(3)
Fig. 30-3-2 GCp=-1.3 -1.8 -1.8 -1.95
Eq. 29.4-7 P=qh(GCp)(γE)(γa)=-17.79 -24.63 -24.63 -26.69
GCp=0.7 Figure 30.3-2
P=qh(GCp)(γE)(γa)=5.16 Equation 29.4-7
Rafter Attachments: 0.6D+0.6W (CD=1.6)
Connection Check
Attachement max. spacing=5.3 ft
5/16" Lag Screw Withdrawal Value=266 lbs/in Table 12.2A - NDS
2.5 in DFL#2 Assumed
Prying Coefficient 1.4
Allowable Capacity=760 lbs
Zone Trib Width Area (ft)Uplift (lbs)Down (lbs)
Zone(1)5.3 15.1 101.3 123.0
Zone(2r)5.3 8.6 76.9 123.0
Zone(2e)5.3 8.6 76.9 123.0
Zone(3)5 8.6 82.6 123.0
Conservative Max=101.3 <760
CONNECTION IS OK
2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw.
Embedment in sheading or other material does not count.
II
V=
Exposure =
1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift
governs
γE=
γa=
KZt =
qh= 0.00256KzKztKdKeV2=
Pitch =
Lag Screw Penetration
Risk Category =
KZ =
Kd =
Ke =
projects@evengineersnet.com
http://www.evengineersnet.com
1414 S Shelton St
12/2/2024
Vertical Load Resisting System Design
Roof Framing Rafters
Snow Load Fully Exposed
pg=0 psf Ct =1.1
Ce =0.9 Is =1.0 ps = 0 psf
pf = 0 psf pfmin. = 0.0 psf 0 plf
Max Length, L =15.2 ft
Tributary Width, WT =16 in
RLL =20 psf 13.32 plf
Dr =10 psf 13.33 plf
PvDL =3 psf 4 plf
Load Case: DL w=17 plf
M=443 lb-ft
Mallowable = Sx x Fb'=1224 lb-ft >443 lb-ft OK
Load Case: DL+RLL DL+Lr=27 plf
Mdown=681 lb-ft
Mallowable = Sx x Fb'=1700 lb-ft >681 lb-ft OK
Load Case: DL+S DL+S=17 plf
Mdown=443 lb-ft
Mallowable = Sx x Fb'=1632 lb-ft >443 lb-ft OK
Load Case: DL+0.6W w=21.5 plf
Mu=549 lb-ft
Mallowable = Sx x Fb' (wind)=2176 lb-ft >549 lb-ft OK
Load Case: 0.6DL+0.6W w=15.0 plf
Mu=382 lb-ft
Mallowable = Sx x Fb' (wind)=2176 lb-ft >382 lb-ft OK
DL+0.45W+0.75(RLL or S)21 plf
Mdown=530 lb-ft
Mallowable = Sx x Fb'=2176 lb-ft >530 lb-ft OK
Member Capacity
DF-L No.2
2X8 CL CF Ci Cr
Fb =900 psi 1.0 1.2 1.0 1.15 1242 psi
Fv =180 psi N/A N/A 1.0 N/A 180 psi
E =1600000 psi N/A N/A 1.0 N/A 1600000 psi
Emin =580000 psi N/A N/A 1.0 N/A 580000 psi
Depth, d =7.25 in
Width, b =1.5 in
Cross-Sectonal Area, A =10.875 in2
Moment of Inertia, Ixx =47.6348 in4
Section Modulus, Sxx =13.1406 in3
Allowable Moment, Mall = Fb'Sxx =1360.1 lb-ft DCR=Mu/Mall =0.40 < 1 Satisfactory
Allowable Shear, Vall = 2/3Fv'A =1305.0 lb DCR=Vu/Vall =0.11 < 1 Satisfactory
Design Value Adjusted Value
projects@evengineersnet.com
http://www.evengineersnet.com
1414 S Shelton St
12/2/2024
Siesmic Loads Check
Roof Dead Load 10 psf
% or Roof with Pv 22.0%
Dpv and Racking 3 psf
Average Total Dead Load 10.7 psf
Increase in Dead Load 3.0%OK
Limits of Scope of Work and Liability
The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and
therefore no further seismic analysis is required.
We have based our structural capacity determination on information in pictures and a drawing set titled PV plans
-FELIPE SERRANO. The analysis was according to applicable building codes, professional engineering and design
experience, opinions and judgments. The calculations produced for this structure's assessment are only for the
proposed solar panel installation referenced in the stamped plan set and were made according to generally
recognized structural analysis standards and procedures.
projects@evengineersnet.com
http://www.evengineersnet.com
1414 S Shelton St
12/2/2024
Rev: 8/29/19
SOL-01 CBC 2016
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Signature:
Date:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
Print Name: caitlyn hernandez
Phone Number: 3854005019
Email Address: oc_permits@sunrun.com
1414 S Shelton St
12/2/2024
Wc614287601American Zurich10/01/241414 S Shelton St12/2/2024
CITY OF SANTA ANA
DEVELOPMENT FEES WORKSHEET -- ELECTRICAL PERMIT
APP FOR ELECTRICAL 06-10-2019 APP-02 CEC2016
Project Address: Contractor:
Tenant Name: Address:
Building Owner: City: St.: Zip:
Address: Contractor License No.:
City: St.: Zip: Contractor Email:
Phone: Phone:
Contact Person: Contact E-Mail Strongly Recommended PLEASE PRINT:
Contact Phone:
NEW BUILDING OCCUPANCY CHANGE
ELECTRICAL ITEM Count $ EACH ELECTRICAL ITEM Count $ EACH
125 Volt Receptacle Outlets 1.51 LOW VOLTAGE SYSTEMS – EACH: phone, data outlet,
speaker, thermostat, door holder, doorbell, pull station, smoke
detector, alarm device, card reader, etc. (circle items) Light Switches, Occupancy Sensors 1.64
Light Fixtures 1.09 COMMERCIAL:
Air Conditioners, Heat Pumps 100.70 FIRST 10 devices or outlets 35.21
Factory-Wired Units (Solid Hook-Ups) 25.76 Additional devices, each 3.33
Dedicated Circuits (15 or 20 AMP Receptacles) 25.76 Each control panel, power supply
annunciator, switch or aux equip. 16.77 Time Clock, Photo-Cell, Time Switch 12.57
Track-Light, Cable Tray, Special
Raceway, Plugmold, Under-Floor
Duct, Plug-In Busway, Surface Duct,
Etc. (Each 100 Feet or any fraction thereof)
25.76
RESIDENTIAL:
Single Dwelling unit 38.16
Each add’l dwelling unit (2 to 20) 33.57
Each add’l unit (over 20) 20.49
SERVICE METERS & PANELS: Service Meter, Reset Meter,
Subpanel, Switchboard, Motor Control Center, Transfer Switch,
Busduct, or other Distribution Equipment changes or modifications.
(circle items as needed)
MISCELLANEOUS
Light Standard (Pole) with 1
Fixture 25.77
Additional Fixtures – same pole 0.00
Power Pole (Temporary) 107.11
Use this column if a Service All others
here Additional distribution poles 25.77
Under 400 amperes 55.37 Swimming Pool, Spa, Fountain 125.84
400 amperes to 1199 amperes 150.97 Above ground spa 54.37
1200 amperes and over 251.56 Demolition 50.36
POWER APPARATUS: Motor, Transformer, Welder, Industrial
Equipment, Oven, Rectifier, Generator, Surge Arrestor, Water
Heater, Photovoltaic Panel, or other Power Equipment changes or
modifications. (circle items as needed) Per HP, kW, or kVA
SIGNS & neon/LED decorative
lighting ($200 refundable sign bond)
78.08
NEW or TOTAL REWIRE for SINGLE FAMILY DWELLINGS
SFD Per square foot .15
0 to 1 3.70 Garage Per square foot .15
Over 1 to 10 24.20 SUBTOTAL $
Over 10 to 50 48.02 P/C 65% of SUBTOTAL $
Over 50 to 100 109.06 MIN. FEE – (Nonresidential) $ 76.26
Over 100 to 500 156.70 ISSUANCE & General Plan
Surcharge $ 57.20 + 22.95 = $80.15
Over 500 195.74 TOTAL $
OFFICE USE ONLY
BLDG PMT RECEIPT BY DATE
OCCUPANCY TYPE P/CPAID
1414 S Shelton St
12/2/2024
City of Santa Ana,
SIGNATURE:___________________ DATE:__________
717 17th Street, Ste. 200 | Denver, CO 80202
I, Felipe Serrano, grant authorization to SUNRUN SOLAR to install Rooftop Mounted Solar
on my residence located at 1414 s shelton st , SANTA ANA, CA, 92704.
Docusign Envelope ID: 4AEF63B2-5746-41FF-97A7-BE122D5FA46A
10/4/2024
1414 S Shelton St
12/2/2024
Certificate Of Completion
Envelope Id: 4AEF63B2574641FF97A7BE122D5FA46A Status: Completed
Subject: SUNRUN URGENT NEEDED FOR PERMITS Complete with Docusign: -Solar Authorization Letter.pdf
Source Envelope:
Document Pages: 1 Signatures: 1 Envelope Originator:
Certificate Pages: 5 Initials: 0 Bobby Cautela
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
225 Bush Street, Suite 1400
San Francisco, CA 94104
robert.cautela@sunrun.com
IP Address: 174.65.135.37
Record Tracking
Status: Original
10/4/2024 4:09:03 PM
Holder: Bobby Cautela
robert.cautela@sunrun.com
Location: DocuSign
Signer Events Signature Timestamp
Felipe Serrano
mikeaserrano17@yahoo.com
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 104.34.211.107
Signed using mobile
Sent: 10/4/2024 4:09:48 PM
Viewed: 10/4/2024 5:37:03 PM
Signed: 10/4/2024 5:37:16 PM
Electronic Record and Signature Disclosure:
Accepted: 10/22/2022 2:24:20 PM
ID: 3c3106f2-7176-4d5b-b82b-035b929142e4
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 10/4/2024 4:09:48 PM
Certified Delivered Security Checked 10/4/2024 5:37:03 PM
Signing Complete Security Checked 10/4/2024 5:37:16 PM
Completed Security Checked 10/4/2024 5:37:16 PM
Payment Events Status Timestamps
Electronic Record and Signature Disclosure
1414 S Shelton St
12/2/2024
CONSUMER DISCLOSURE
From time to time, Sunrun Inc. (we, us or Company) may be required by law to provide to you
certain written notices or disclosures. Described below are the terms and conditions for providing
to you such notices and disclosures electronically through the DocuSign, Inc. (DocuSign)
electronic signing system. PLEASE READ THE INFORMATION BELOW CAREFULLY
AND THOROUGHLY, AND IF YOU CAN ACCESS THIS INFORMATION
ELECTRONICALLY TO YOUR SATISFACTION AND AGREE TO THESE TERMS AND
CONDITIONS, PLEASE CONFIRM YOUR AGREEMENT BY CLICKING THE 'I AGREE'
BUTTON AT THE BOTTOM OF THIS DOCUMENT.
Getting paper copies
At any time, you may request from us a paper copy of any record provided or made available
electronically to you by us. You will have the ability to download and print documents we send
to you through the DocuSign system during and immediately after signing session and, if you
elect to create a DocuSign signer account, you may access them for thirty (30) days after such
documents are first sent to you. After such time, if you wish for us to send you paper copies of
any such documents from our office to you, please request delivery of such paper copies from us
by following the procedure described below.
Withdrawing your consent
If you decide to receive notices and disclosures from us electronically, you may at any time
change your mind and tell us that thereafter you want to receive required notices and disclosures
only in paper format. How you must inform us of your decision to receive future notices and
disclosure in paper format and withdraw your consent to receive notices and disclosures
electronically is described below.
Consequences of changing your mind
If you elect to receive required notices and disclosures only in paper format, it will slow the
speed at which we can complete certain steps in transactions with you and delivering services to
you because we will need first to send the required notices or disclosures to you in paper format,
and then wait until we receive back from you your acknowledgment of your receipt of such
paper notices or disclosures. To indicate to us that you are changing your mind, you must
withdraw your consent using the DocuSign ‘Withdraw Consent’ form on the signing page of a
DocuSign envelope instead of signing it. This will indicate to us that you have withdrawn your
consent to receive required notices and disclosures electronically from us and you will no longer
be able to use the DocuSign system to receive required notices and consents electronically from
us or to sign electronically documents from us.
All notices and disclosures will be sent to you electronically
Unless you tell us otherwise in accordance with the procedures described herein, we will provide
electronically to you through the DocuSign system all required notices, disclosures,
authorizations, acknowledgements, and other documents that are required to be provided or made
available to you during the course of our relationship with you. To reduce the chance of you
inadvertently not receiving any notice or disclosure, we prefer to provide all of the required
notices and disclosures to you by the same method and to the same address that you have given
us. Thus, you can receive all the disclosures and notices electronically or in paper format through
the paper mail delivery system. If you do not agree with this process, please let us know as
described below. Please also see the paragraph immediately above that describes the
consequences of your electing not to receive delivery of the notices and disclosures
electronically from us.
Electronic Record and Signature Disclosure created on: 8/7/2013 10:17:58 AM
Parties agreed to: Felipe Serrano 1414 S Shelton St
12/2/2024
How to contact Sunrun Inc.:
You may contact us to let us know of your changes as to how we may contact you electronically,
to request paper copies of certain information from us, and to withdraw your prior consent to
receive notices and disclosures electronically as follows:
To contact us by email send messages to: customercare@sunrun.com
You may also contact us in writing at 45 Fremont Street, 32nd Floor, San Francisco, CA 94105
or by phone at 1-855-478-6786.
To advise Sunrun Inc. of your new e-mail address
To let us know of a change in your e-mail address where we should send notices and disclosures
electronically to you, you must send an email message to us at customercare@sunrun.com and in
the body of such request you must state: your previous e-mail address, your new e-mail
address. We do not require any other information from you to change your email address.
In addition, you must notify DocuSign, Inc. at 1-866-219-4318 to arrange for your new email
address to be reflected in your DocuSign account by following the process for changing e-mail in
the DocuSign system.
To request paper copies from Sunrun Inc.
To request delivery from us of paper copies of the notices and disclosures previously provided
by us to you electronically, you must contact us by (a) sending us an e-mail to
customercare@sunrun.com, (b) writing to us at Sunrun Inc, 45 Fremont Street, 32nd Floor, San
Francisco, CA 94105, or (c) calling us at 1-855-478-6786, and in connection with your request
you must state your e-mail address, full name, US Postal address, and telephone number.
To withdraw your consent with Sunrun Inc.
To inform us that you no longer want to receive future notices and disclosures in electronic
format you may:
i. decline to sign a document from within your DocuSign session, and on the subsequent
page, select the check-box indicating you wish to withdraw your consent, or you may;
ii. contact us by (a) sending us an email to customercare@sunrun.com, (b) writing to us
at Sunrun Inc., 45 Fremont Street, 32nd Floor, San Francisco, CA 94105, or (c) calling us
at 1-855-478-6786, and in connection with your request you must state your e-mail, full
name, US Postal Address, and telephone number. We do not need any other information
from you to withdraw consent.. The consequences of your withdrawing consent for
online documents will be that transactions may take a longer time to process..
Required hardware and software
Operating
Systems: Windows® 2000, Windows® XP, Windows Vista®; Mac OS® X
1414 S Shelton St
12/2/2024
Browsers:
Final release versions of Internet Explorer® 6.0 or above (Windows only);
Mozilla Firefox 2.0 or above (Windows and Mac); Safari™ 3.0 or above
(Mac only)
PDF Reader: Acrobat® or similar software may be required to view and print PDF files
Screen
Resolution: 800 x 600 minimum
Enabled Security
Settings: Allow per session cookies
** These minimum requirements are subject to change. If these requirements change, you will be
asked to re-accept the disclosure. Pre-release (e.g. beta) versions of operating systems and
browsers are not supported.
Notices
Any notice or other communication to be made hereunder, even if otherwise required to be in
writing under other provisions of this Consent or any other documents or agreements that have
been provided to you in connection with this Consent, may alternatively be made in an electronic
record transmitted electronically to the electronic addresses provided by you. Any notice or other
communication made in electronic form will have the same legal effect and enforceability as if
made in non-electronic form.
Acknowledging your access and consent to receive materials electronically
To confirm to us that you can access this information electronically, which will be similar to
other electronic notices and disclosures that we will provide to you, please verify that you were
able to read this electronic disclosure and that you also were able to print on paper or
electronically save this page for your future reference and access or that you were able to e-mail
this disclosure and consent to an address where you will be able to print on paper or save it for
your future reference and access. Further, if you consent to receiving notices and disclosures
exclusively in electronic format on the terms and conditions described above, please let us know
by clicking the ‘I agree’ button below.
By checking the ‘I agree’ box, I confirm that:
I can access and read and have accessed, read and understood the terms of this
ELECTRONIC CONSENT TO ELECTRONIC RECEIPT OF ELECTRONIC
CONSUMER DISCLOSURES document; and
I can print on paper the disclosure or save or send the disclosure to a place where I can
print it, for future reference and access; and
Until or unless I notify Sunrun Inc. as described above, I consent to receive from
exclusively through electronic means all notices, disclosures, authorizations,
acknowledgements, and other documents that are required to be provided or made
available to me by Sunrun Inc. during the course of my relationship with you.
Entire Agreement Provision
This agreement and the consumer disclosure statement executed by the customer in conjunction
with and simultaneously with its review and acceptance of the terms set forth herein constitute
1414 S Shelton St
12/2/2024
the entire agreement between the parties with respect to the subject matter hereof and supersede
any prior understandings, agreements, or representations by or between the parties, written or
oral, to the extent they relate in any way to the subject matter hereof.
1414 S Shelton St
12/2/2024