Loading...
HomeMy WebLinkAbout2140 S Broadway - REV 1- 20185638 - PlanPAGE REV: I 2/14/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA, CA, 92707 PROJECT NUMBER: 109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024.02.28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603 FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 COVER SHEET SCOPE OF WORK GENERAL NOTES PV-1.0 VICINITY MAP #SSTAMPCS #ESTAMPCS ABBREVIATIONS A AMPERE AC ALTERNATING CURRENT AFC ARC FAULT CIRCUIT INTERUPTER AZIM AZIMUTH COMP COMPOSITION DC DIRECT CURRENT (E)EXISTING ESS ENERGY STORAGE SYSTEM MSP MAIN SERVICE PANEL (N) NEW PRE-FAB PRE-FABRICATED PSF POUNDS PER SQUARE FOOT PV PHOTOVOLTAIC RSD RAPID SHUTDOWN DEVICE TL TRANSFORMERLESS V VOLTS W WATTS SHEET INDEX • EXISTING SYSTEM SIZE: 3975W DC, 3225W AC • MODULES: (7) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M • INVERTERS: (1) TESLA: POWERWALL 3 1707000-XX-Y, • RACKING: UR - SPEEDSEAL DECKFOOT TO FRAMING - SNR-DC-00449 • ENERGY STORAGE SYSTEM: (1) TESLA: POWERWALL 3 1707000-XX-Y, (1) EXPANSION 1807000-XX-Y • RAPID SHUTDOWN: (3) TESLA MID CIRCUIT INTERRUPTER (MCI) ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE • POWER CONTROLLED SYSTEM (PCS) ENABLED EQUIPMENT INSTALLED, SEE PV-4.0 FOR INTERCONNECTION DETAILS PAGE # DESCRIPTION PV-1.0 COVER SHEET PV-2.0 SITE PLAN PV-2.1 ESS ELEVATION VIEW PV-3.0 LAYOUT PV-3.1 MOUNTING DETAIL PV-4.0 ELECTRICAL PV-4.1 ELECTRICAL CALCS PV-4.2 BACKUP LOAD CALCS PV-4.3 PANEL SCHEDULE PV-5.0 SIGNAGE PV-5.1 SIGNAGE • ALL WORK SHALL COMPLY WITH 2022 CRC/CBC/CEBC, 7-16 ASCE & 2018 NDS, MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS. • PHOTOVOLTAIC SYSTEM WILL COMPLY WITH CEC 2022. • ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH CEC 2022. • PHOTOVOLTAIC SYSTEM IS FUNCTIONALLY GROUNDED. NO CONDUCTORS ARE SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A). • MODULES CONFORM TO AND ARE LISTED UNDER UL 61730. • INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741. • RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. • SNAPNRACK RACKING SYSTEMS, IN COMBINATION WITH TYPE I, OR TYPE II MODULES, ARE CLASS A FIRE RATED. • RAPID SHUTDOWN SYSTEM IN COMPLIANCE WITH CEC 2022 690.12(B)(1) WHERE CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30 SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS • CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(D). • ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. • 14.79 AMPS MODULE SHORT CIRCUIT CURRENT. • 23.11 AMPS DERATED SHORT CIRCUIT CURRENT [690.8 (A)(1) & 690.8 (B)]. • ENERGY STORAGE SYSTEM CONFORMS TO AND IS LISTED UNDER UL 9540. • ENERGY STORAGE SYSTEM LIVE PARTS ARE NOT ACCESSIBLE DURING ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20 AND EXCEPTION 1 CEC 706.20 (B). • ADDITIONAL DISCONNECTING MEANS SHALL BE INSTALLED WHERE THE CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER 706.15(D). • LISTED, COMBINATION TYPE AFCI SHALL BE INSTALLED WHERE BACKED UP CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D). • ALL PASS-THROUGH CONDUCTORS MUST COMPLY WITH CEC 312.8 • THE CAPACITY OF THE STANDALONE SYSTEM SUPPLY SHALL BE EQUAL TO OR GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A) • NEW SYSTEM SIZE: 2765W DC, 11500W AC • COMBINED SYSTEM SIZE: 6740W DC, 14725W AC NEW 200A PV LOAD CENTER TO BE INSTALLED I Bldg #101122013 & Elect #20184760 APPROVALS: ELECT - M. Smith **The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. ** 2140 S Broadway 3/21/2025 PAGE REV: I 2/14/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA, CA, 92707 PROJECT NUMBER: 109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024.02.28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603 FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 PV-2.1 GATE EXTERIOR SOUTH WALL ACD DOOR SITE PLAN - SCALE = NTS ESS ELEVATION VIEW ESS ELEVATION VIEW EXPACKPW3 ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4. ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON LARGE/SCALE FIRE TESTING. WINDOW 3' MIN WINDOW GATE 3' MIN I I V I LREGISTERED PR O F E SSIONAL E N G I NEERS T ATE OF C A L IFORNIAROBER T SMYT H EC56136 EXP. 12/31/26 2140 S Broadway 3/21/2025 PAGE REV: I 2/14/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA, CA, 92707 PROJECT NUMBER: 109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024.02.28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603 FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46PLPLPLPLPLPLPLPLPLPL SITE PLAN PV-2.0 #SSTAMPSP #ESTAMPSP ARRAY PITCH PV AREA (SQFT) AR-01 21° 147.2 TRUE AZIM MAG AZIM 77°89° NOTES: ·RESIDENCE DOES NOT CONTAIN ACTIVE FIRE SPRINKLERS. ARRAY DETAILS: ·TOTAL ROOF SURFACE AREA: 1837 SQFT. ·TOTAL PV ARRAY AREA(E+N): 422.51 SQ FT. ·PERCENTAGE PV COVERAGE: (TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE AREA)(E+N) * 100 = 23% ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4. ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON LARGE/SCALE FIRE TESTING. SITE PLAN - SCALE = 3/64" = 1'-0" POWERWALL ENERGY STORAGE SYSTEM (ESS) BG BACKUP GATEWAY GP GENERATION PANEL ELECTRIC VEHICLE SUPPLY EQUPMENTEV MAIN PANEL INVERTER(S) AC DISCONNECT(S) DC DISCONNECT(S) SUNRUN METER DEDICATED PV METER SERVICE ENTRANCE INTERIOR EQUIPMENT SHOWN AS DASHED SE MP SM PM INV AC DC SUB-PANELSP CB IQ COMBINER BOX METER ADAPTERMA GROUNDING ELECTRODE ENERGY STORAGE SYSTEM BP BACKUP LOADS PANEL BI BACKUP INTERFACE 1 COMMUNICATION WIRESAM MD MICROGRID INTERCONNECT DEVICE ACREL METER SOLAREDGE METERSEMPV LOAD CENTERLC LEGEND SCALE: NTS NOTE: NOT ALL ITEMS IN LEGEND WILL APPEAR IN SITE PLAN RAIL STANDOFFS & FOOTINGS SOLAR MODULES EXTERNAL RAPID SHUTDOWN SWITCH RSD MD (E) RESIDENCE (N) ARRAY AR-01 FIRE SETBACKS (18" TYP) ROOF PATHWAYS (3' TYP) SE MP (E) PV ARRAY(TYP) (E) PV EQUIPMENT S BROADWAYROOF PATHWAYS (3' TYP) ACPM INVAC (E) GATE(TYP) (E) FENCE(TYP) (E) DETACHED GARAGE STRUCTURE (TYP.) (E) DETACHED SHED STRUCTURE (TYP.) (E) CHIMNEY AAAABBB125'-9" 50'-2" 125'-9" 50'-10" 20'-6" 4'-5" 2'-9" 1'-7" 3'-8" 5' 2'-6" 10'-3" 20'-7" 13'-7" 8'-9" (E) DETACHED EQUIPMENT AWNING STRUCTURE (TYP.)(E) ROOF PLANE ATTACHED TO STRUCTURE (E) DETACHED GARAGE STRUCTURE ROOF PLANE ATTACHED TO GARAGE STRUCTURE (TYP.) SP (E) SUBPANEL LC I I I V I LREGISTERED PR O F E SSIONAL E N G I NEERS T ATE OF C A L IFORNIAROBER T SMYT H EC56136 EXP. 12/31/26 2140 S Broadway 3/21/2025 PAGE REV: A 9/24/2024 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA,  CA, 92707 PROJECT NUMBER:   109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024 02 28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 #SSTAMP DESIGN CRITERIA MAX DISTRIBUTED LOAD: 3 PSF SNOW LOAD: 0 PSF WIND SPEED:  96 MPH 3-SEC GUST. FASTENERS: (2) #14 S.S. SEALING WASHER  WOOD SCREWS: 1.5" MIN  EMBEDMENT INTO FRAMING (2) #14 S.S. SEALING WASHER  WOOD SCREWS FULLY  PENETRATING THROUGH WOOD  DECK PV-3.0 LAYOUT SOLAR MODULE SNAPNRACK  RACKING 6" MODULE ELEVATION DETAIL - SCALE: NTS INSTALLERS SHALL NOTIFY ENGINEER OF ANY  POTENTIAL STRUCTURAL ISSUES OBSERVED  PRIOR TO PROCEEDING W/ INSTALLATION. * IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12"  BOUNDARY REGION OF ANY ROOF PLANE  EDGES (EXCEPT VALLEYS), THEN  ATTACHMENTS NEED TO BE ADDED AND  OVERHANG REDUCED WITHIN THE 12"  BOUNDARY REGION ONLY AS FOLLOWS: ** ALLOWABLE ATTACHMENT SPACING  INDICATED ON PLANS TO BE REDUCED BY 50%. ** ALLOWABLE OVERHANG INDICATED ON  PLANS TO BE 1/5TH OF ALLOWABLE  ATTACHMENT SPACING INDICATED ON PLANS. D1 - AR-01 - SCALE: 1/8" = 1'-0" AZIM:89° PITCH: 21°   6' TYP 7'-7" 11'-4" 18'-10"10'8'-2" 1'-1" ROOF INFO FRAMING INFO ATTACHMENT INFORMATION Name Type Height Type Max  Span OC  Spacing Detail Max Landscape  OC Spacing Max Landscape  Overhang Max Portrait  OC Spacing Max Portrait  Overhang Configuration AR-01 COMP SHINGLE  SPEEDSEAL DECKFOOT 1-Story 2X4 RAFTERS 9'-2"24"UR - SPEEDSEAL DECKFOOT TO FRAMING -  SNR-DC-00449 6'-0"2'-4"6'-0" 2'-3"STACKED 09/24/2024 2140 S Broadway 3/21/2025 SNAPNRACK UR SPEEDSEAL DECKFOOT FOR COMPOSTION ROOF MOUNTING ONTO WOOD RAFTER 5 16"-18 X 13 REFER TO SNAPNRACK ENGINEERING CHARTS FOR APPLICABLE RAIL SPANS. "BIN" NUMBER ON CHART SHOULD MATCH "BIN" NUMBER ON THIS DRAWING (X2) #14 FULLY THREADED WOOD SCREWS, S.S. MUST PENETRATE A MIN. OF 112" INTO STRUCTURAL MEMBER. (X2) #14 FULLY THREADED WOOD SCREWS, S.S. MUST EMBED FULLY INTO WOOD DECK REFER TO SNAPNRACK INSTALLATION MANUAL FOR 5 HARDWARE TORQUE SPECIFICATIONS 16" RAIL CAN MOUNT ON EITHER SIDE OF SPEEDSEAL DECKFOOT. SPEEDSEAL DECKFOOT CAN MOUNT UP, DOWN, OR ACROSS THE SLOPE OF THE ROOF FOR ADDITIONAL LEVELING DETAILS, REFER TO SNAPNRACK DETAIL DRAWING "SNR-DC-00447 ULTRA RAIL, COMPONENT DETAIL, ULTRA RAIL LEVELING SPACER" SNAPNRACK, ULTRA RAIL MODULE HEIGHT, MAX: UR-40 = 438" UR-60 = 5" SCREW HEIGHT OFF ROOF: 9 16" MINIMUM RAFTER PENETRATION: 11 2" ROOF DECKING MINIMUM DECK THICKNESS: PLYWOOD: 15 32" OSB: 7 11 11 2" 21 15 8" UR-40 RAIL | UR-60 RAIL FOR USE WITH SNAPNRACK ULTRA SERIES RAILS Sunrun South LLC 595 MARKET STREET, 29TH FLOOR  SAN FRANCISCO, CA 94105 USA PHONE (415) 580-6900  FAX (415) 580-6902 Solar Mounting SolutionsTHE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF SUNRUN SOUTH LLC. DESIGNER: APPROVED BY: M.AFFENTRANGER DRAFTER: M.AFFENTRANGER W.ARBUCKLE SCALE: DATE: DNS 4/5/2021 DRAWING NUMBER: SNR-DC-00449 4" 2" ATTACHMENT DETAIL ROOF DECKING WOOD RAFTER, TYP. (STRUCTURAL MEMBER) (2X) #14 FULLY THREADED WOOD SCREW. S.S. INTO STRUCTURAL MEMBER. SIZE LENGTH APPROPRIATELY INSTALLATION OVERVIEW DESCRIPTION: ULTRA RAIL, ATTACHMENT DETAIL, UR SPEEDSEAL DECKFOOT TO RAFTER 16" COMP SHINGLE ROOFING, TYP. STRUCTURAL MEMBER (RAFTER) COMP SHINGLE ROOFING, TYP. COIL SPRING FOR 3 BIN: 4" BOLT, SERRATED FLANGE, S.S. 8" BOLT, S.S. (OPTIONAL) SNAPNRACK, SPEEDSEAL DECKFOOT BASE, SEALING SNAPNRACK, UR MOUNT THRU SNAPNRACK, UR MOUNT TAPPED TOP EXPLODED (2X) #14 FULLY THREADED WOOD SCREW. S.S. MUST EMBED FULLY INTO WOOD DECK 5.200 N/A REVISION: 1 1/13/2021 NEW DETAIL 2 4/5/2021 2PC CLAMP MJA MJA 3.860 REV: 2 PAGE REV: A 09/24/24 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA,  CA, 92707 PROJECT NUMBER:   109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 CA CL #750184 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 MOUNTING DETAIL PV-3.1 GILBERT CORREIA, C10, C46 APN: 015-082-22 09/24/2024 2140 S Broadway 3/21/2025 PAGE REV: I 2/14/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA, CA, 92707 PROJECT NUMBER: 109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024.02.28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603 FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 CONDUIT SCHEDULE TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT 1 Inverter Input (2) 10 AWG (PV WIRE)N/A 6 AWG (BARE)Open Air 2 Inverter Input (2) 10 AWG THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4 EMT 3 Inverter Output (2) 6 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2 8 AWG THHN/THWN-2 3/4 EMT 4 PV Load Center Output (2) 3 AWG THHN/THWN-2 (1) 3 AWG THHN/THWN-2 8 AWG THHN/THWN-2 1 EMT E EXISTING EXISTING 100A MAIN BREAKER END FED EXISTING 125A MAIN PANEL 125A BUS (N) LOCKABLE BLADE TYPE AC DISCONNECT SQUARE D DU222RB 3R, 60A , 2P 120/240VAC 3 A A EXISTING 100A SUB PANEL WITH 100A MAIN BREAKER (E) LOADS E TESLA POWERWALL 3 1707000-XX-Y TESLA: POWERWALL 3 1707000-XX-Y 11500 WATT INVERTER LOAD RATED DC DISCONNECT WITH AFCI RAPID SHUTDOWN COMPLIANT, POWER CONTROL SYSTEM 3 J-BOX LONGi Green Energy Technology Co Ltd LR5-54HABB-395M STRING 1 OF 7 MODULES 3 MODULE LEVEL RAPID SHUTDOWN DEVICES 12 POINT OF INTERCONNECTION:705.13, GATEWAY FEEDER BREAKER AT OPPOSITE END OF BUSBAR METER NUMBER: 222013-165258 EQUIPMENT CHARACTERISTICS INCLUDED IN SPEC SHEETS NOTE: TOTAL PV BACKFEED(E+N) = 80A USED FOR INTERCONNECTION CALCULATIONS J-BOX (15) HANWHA Q-CELLS: Q.PRO-G4 265 MODULES AND MICRO-INVERTER PAIRS (15) ENPHASE ENERGY: M215-60-2LL-S2X-IG EE E 20A OCPD M Existing Production Meter E Existing Knife Disconnect 30A Rated E Existing Combiner Panel XA Rated E E (N) TESLA REMOTE METER SOLAR CURRENT TRANSFORMERS M TESLA BACKUP SWITCH NEW 200A PV LOAD CENTER (N) (1) - 60A (ESS+PV)BREAKER (E) 20A PV BREAKER 4100AOCPD 100AOCPD UL 9540 FACTORY WIRING ASSEMBLY (1 ) TESLA POWERWALL 3 EXPANSION PACK 1807000-XX-Y PV-4.0 ELECTRICAL #ESTAMP MODULE CHARACTERISTICS LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M 395 W OPEN CIRCUIT VOLTAGE 36.81 V MAX POWER VOLTAGE 30.7 V SHORT CIRCUIT CURRENT 14.79 A GENERAL NOTES: • CITY REQUIRES TWO SOURCES OF GROUND - UFER, TWO GROUNDS RODS OR COLD WATER GAS BOND POWER CONTROL SYSTEM (PCS): • A PCS IS INSTALLED IN ACCORDANCE WITH NEC 705.13 • THE PCS SHALL LIMIT GENERATION SOURCE OUTPUT SUCH THAT CURRENT FROM ALL SOURCES OF SUPPLY DOES NOT EXCEED THE RATING OF ANY BUSBAR OR CONDUCTOR SUPPLIED BY THE POWER PRODUCTION SOURCES • ANY BUSBAR OR CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECT NOT MONITORED BY THE PCS SHALL COMPLY WITH ARTICLE 705.12. • ACCESS TO PCS CONTROLS IS RESTRICTED TO QUALIFIED PERSONS IN ACCORDANCE WITH 240.6(C). • ENERGY STORAGE SYSTEM: TESLA: POWERWALL 3 1707000-XX-Y • ENABLE PCS SETPOINTS: - 100A - MAXIMUM TOTAL CURRENT ON THE CONTROLLED PANEL - 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY (120% COMPLIANT) INSTALL THE BACKED UP LOAD CONDUCTORS AND THE GATEWAY BREAKER CONDUCTORS IN TWO SEPARATE CONDUITS. I 2140 S Broadway 3/21/2025 PAGE REV: I 2/14/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA, CA, 92707 PROJECT NUMBER: 109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024.02.28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603 FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 PV-4.1 ELECTRICAL CALCS #ESTAMP SYSTEM INFORMATION 2.765 KW DC PHOTOVOLTAIC SYSTEM (7) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M, TESLA: POWERWALL 3 1707000-XX-Y SYSTEM OCPD SIZE   (COMBINED MAX CURRENT) X (CONTINUOUS LOAD) =      96 A X 1.25 = 120A → 100A OVERCURRENT PROTECTION UTILIZING PCS ALLOWABLE BACKFEED MAX ALLOWED TOTAL GENERATION BACKFEED OCPD = MAIN BREAKER RATING = 100A 100A ≤ 100A→ INTERCONNECTION MEETS 705.13 REQUIREMENTS. GATEWAY SYSTEM AC WIRE SIZING MAX AC OUTPUT CURRENT = 100 A ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] = 0.91 X 1 X 115A = 104.65A TERMINAL RATING[110.14(C)] = 3 AWG, 75°C RATED = 100A 100A < 104.65A → TERMINAL RATING GOVERNS CONDUCTOR SIZING 100A ≤ 100A → 3 AWG AMPACITY OK THEREFORE 3 AWG IS SUFFICIENT. INVERTER INFORMATION 2765 KW DC PHOTOVOLTAIC SYSTEM (7) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M, TESLA: POWERWALL 3 1707000-XX-Y INVERTER OVERCURRENT PROTECTION (INVERTER MAX CURRENT) X (CONTINUOUS LOAD) = 48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER DC WIRE SIZING MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS LOAD)[690.8(B)(1)]= 15A X 1.25 = 18.75A ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] = 0.91 X 1 X 40A = 36.4A TERMINAL RATING[110.14(C)] = 10 AWG, 75°C RATED = 35A 35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING 18.75A < 35A → 10 AWG AMPACITY OK THEREFORE 10 AWG IS SUFFICIENT. AC WIRE SIZING MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] = 48 A X 1.25 = 60 A ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] = 0.91 X 1 X 75A = 68.25A TERMINAL RATING[110.14(C)] = 6 AWG, 75°C RATED = 65A 65A < 68.25A → TERMINAL RATING GOVERNS CONDUCTOR SIZING 60A < 65A → 6 AWG AMPACITY OK THEREFORE 6 AWG IS SUFFICIENT. SYSTEM CHARACTERISTICS MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] + VOC} X (# MODULES / STRING) = {[(-0.26 %/°C X 36.81 V) / 100] X [-2 °C - 25 °C] + 36.81 V} X 7 = 276.5 V SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS) 1.25 X 14.79 A X 1 = 18.48A I 2140 S Broadway 3/21/2025 BACKUP LOADS LOAD BREAKER RATING  (AMPS)LABEL DEMAND LOAD(VA) 1 100A-2P SUB PANEL 19200 W 2 30A-2P DRYER 5760 W BACKUP LOAD CALCS PV-4.2 BACKUP LOAD  CALCS #ESTAMP PAGE REV: A 9/24/2024 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA,  CA, 92707 PROJECT NUMBER:   109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 GILBERT CORREIA, C10, C46 CA CL #750184 (415) 580-6920 ex3 Template_version_v5_2024 02 28 ALL BACKED UP LOADS ABOVE IN THE BACKED UP LOADS PANEL ARE RELOCATED FROM THE MAIN SERVICE PANEL. BACKED UP LOADS CALCULATION: (5760 VA)/ 240V = 24 A PER CEC 2022 ARTICLE 690.10 OR NEC 2020 ARTICLE 710.15. THE MAXIMUM CURRENT FOR ALL SMALL APPLIANCES LOADS IS 24A. (MAX LOADS OUTPUT) X (CONTINUOUS LOADS) =  24 A X 1.25 = 30A BACKED UP LOADS PANEL BREAKER = 70A 30 A < 70A. THEREFORE, THE AMPERAGE OF THE BACKED UP LOADS IS LESS THAN THAT OF THE OCPD. AC WIRE SIZING FOR BACKED UP LOADS PANEL: MAX AC OUTPUT CURRENT = (MAX LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] = 30 A X 1.25 = 38A ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X  (CONDUCTOR AMPACITY)[TABLE 310.16] = 0.91 X 1 X 55A = 50.05A TERMINAL RATING[110.14(C)] = 8 AWG, 75°C RATED = 50A 50A < 50.05A   TERMINAL RATING GOVERNS CONDUCTOR SIZING. 38A ≤ 50A   8 AWG AMPACITY OK THEREFORE 8 AWG IS SUFFICIENT.   AC WIRE SIZING FOR BACKED UP LOADS PANEL: MAX AC OUTPUT CURRENT = (MAX LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] = 12.5 A X 1.25 = 15.625A ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X  (CONDUCTOR AMPACITY)[TABLE 310.16] = 0.91 X 1 X 40A = 36.4A TERMINAL RATING[110.14(C)] = 12 AWG, 75°C RATED = 35A 35A < 36.4A   TERMINAL RATING GOVERNS CONDUCTOR SIZING. 15.625A < 35A   12 AWG AMPACITY OK THEREFORE 12 AWG IS SUFFICIENT.      2140 S Broadway 3/21/2025 PV-4.3 #ESTAMP PANEL SCHEDULE PAGE REV: I 2/14/2025 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603 FAX 949.215.7778 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA, CA, 92707 PROJECT NUMBER: 109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 GILBERT CORREIA, C10, C46 CA CL #750184 (415) 580-6920 ex3 FUTURE 125/100A MAIN PANEL 30100100 DRYER SUB PANEL PANEL SCHEDULE (E) 100/100A SUBPANEL 10020202020201515BEDROOM LIGHTS BEDROOM 1 OUTLET BEDROOM 2 OUTLET BEDROOM 3 OUTLET REFRIGERATOR BATHROOM PLUGS BATHROOM LIGHTS MAIN BREAKER EXISTING 125/100A MAIN PANEL 30100100 DRYER SUB PANEL 20(E) PV BREAKER 60ESS +PV BREAKER 20(E) PV BREAKER (N) 200A PV LOAD CENTER 100PV LOAD CENTER FEEDER BREAKER I 2140 S Broadway 3/21/2025 PAGE REV: I 2/14/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA, CA, 92707 PROJECT NUMBER: 109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024.02.28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603 FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 ( N) TESLAR EMOTE METERS OLAR CURRENTT RANSFORMERS SIGNAGE PV-5.0 #ESTAMP ENERGY STORAGE SYSTEM CAUTION! LABEL LOCATION: INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C) LABEL LOCATION: ENERGY STORAGE SYSTEM DISCONNECT PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C) LABEL LOCATION: AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF INTERCONNECTION. PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54 PV SYSTEM DISCONNECT WARNING! DO NOT RELOCATE THIS OVERCURRENT DEVICE LABEL LOCATION: ADJACENT TO PV BREAKER AND ESS OCPD (IF APPLICABLE). PER CODE(S): NEC 2020: 705.12(B)(3)(2), CEC 2022: 705.12(B)(3)(2) NOTES AND SPECIFICATIONS: ·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE CEC 2022 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ. ·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE WORDS, COLORS AND SYMBOLS. ·LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HAND WRITTEN. ·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. ·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED. ·DO NOT COVER EXISTING MANUFACTURER LABELS. SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS LABEL LOCATION: ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED. PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C) 4" 3" ELECTRICAL SHOCK HAZARD WARNING LABEL LOCATION: INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): NEC 2020: 690.13(B), CEC 2022: 690.13(B) ! LABEL LOCATION: INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT, AT EACH TURN, ABOVE AND BELOW PENETRATIONS, ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS. PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022: 690.31(D)(2)CAUTION: 2140 S BROADWAY, SANTA ANA, CA, 92707 PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10 MULTIPLE SOURCES OF POWER LABEL LOCATION: INSTALLED WITHIN 3' OF RAPID SHUT DOWN SWITCH PER CODE(S): NEC 2020: 690.56(C)(2), CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3 WARNING! SOURCES: UTILITY GRID, BATTERY AND PV SOLAR ELECTRIC SYSTEM THREE POWER SUPPLY LABEL LOCATION: UTILITY SERVICE METER AND MAIN SERVICE PANEL. PER CODE(S): NEC 2020: 705.12(C), CEC 2022: 705.12(C) INVERTER 1 PHOTOVOLTAIC DC DISCONNECT MAXIMUM SYSTEM VOLTAGE:VDC550 LABEL LOCATION: INVERTER(S), DC DISCONNECT(S). PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53 SOLAR PANELS ON ROOF SERVICE ENTRANCE AND TESLA BACKUP SWITCH INVERTER + BATTERY AND EXPACK (EXT)- PCS CONTROLLED AC DISCONNECT (E) PV EQUIPMENT RAPID SHUTDOWN DISCONNECT LOCATION (EXISTING SYSTEM AC DISCONNECT) (E) PV ARRAY (TYP.) PV SYSTEM(S) ARE EQUIPPED WITH RAPID SHUTDOWN DEVICE(S) (E) SUB PANEL (N) LOAD CENTER I 2140 S Broadway 3/21/2025 PAGE REV: A 9/24/2024 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA,  CA, 92707 PROJECT NUMBER:   109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024 02 28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 SIGNAGE PV-5.1 #ESTAMP WARNING: THIS SENSOR IS PART  OF A POWER CONTROL SYSTEM.  DO NOT REMOVE. REPLACE ONLY  WITH THE SAME TYPE AND RATING. WARNING: THIS SENSOR IS PART  OF A POWER CONTROL SYSTEM.  DO NOT REMOVE. REPLACE ONLY  WITH THE SAME TYPE AND RATING. REQUIREMENT: UL 1741, SECTION 206.3 LOCATION: AROUND THE CT WIRE  BY CLAMP SIZE 4.25" X 0.75" INVERTER 1 LABEL LOCATION: REQUIREMENT: UL 1741, SECTION 206.1 AND 206.4 LOCATION: MAIN PANEL SIZE: 4.25" X 1.25" PCS CONTROLLED CURRENT SETTING:  36A   THE MAXIMUM OUTPUT CURRENT FROM THIS SYSTEM IS CONTROLLED ELECTRONICALLY. REFER TO THE MANUFACTURER'S INSTRUCTIONS FOR MORE INFORMATION. ENERGY STORAGE SYSTEM DISCONNECT NOMINAL ESS VOLTAGE VAC LABEL LOCATION: MAIN PANEL. 120 240 NEC 2020 - PW3 PER CODE(S): NEC 706.15(C) LABEL LOCATION: BACKED UP LOADS PANEL NO ADDITIONAL  LOADS TO BE  ADDED 2140 S Broadway 3/21/2025 2140 S Broadway3/21/2025 Service Voltage 240 Section 220.83 Existing Dwelling Unit Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft: Amps Box A (VA) 14.03 3366 Part #2 - Section 220.83(B)(2), (3)a, b, c, d - Appliances and Dedicated Circuits: Size in VA Size in VA 1500 1500 1500 1000 600 1000 1600 5760 Amps Box B (VA) 60.25 14460 Total VA from Parts #1 and #2 combined:Box A + Box B =17826 Total VA 17826 First 8000 VA @ 100%8000 Remaining VA @ 40% Remaining VA =9826 9826 x 40% =3930.4 VA Adding First 8000 VA, if possible 8000 VA Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:11930.4 VA Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:49.71 Amps Part #3 - Section 220.83(B) Heating and A/C loads: *Combine the larger loads of either the Heating or the A/C loads togther 100% of all the Heating or A/C loads in VA:0 VA 100% of all the Heating or A/C loads in Amps:0.00 A VA Volts Amps Parts #1 & #2 11930.4 240 49.71 Part #3 0 240 0.00 Total VA for all Parts:11,930 Totals Service/Feeder Load 49.71 Microwave Dryer Totals for Part #2: Totals from all Parts Dishwasher Disposal Refrigerator Laundry Appliance Circuit - 1 Appliance Circuit - 2 Dedicated circuit Dedicated circuit Article 220 - Dedicated Backup Panel Calculation Job Code 2140 S Broadway Santa Ana, CA 92707 109R-140TOLE Building Square Footage VA (watts)Amps House 1122.00 3366 14.03 Total for Part #1: 2140 S Broadway 3/21/2025 Section 220.83 Existing Dwelling Unit Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft: Amps Box A (VA) 14.03 3366 Part #2 - Section 220.83 (B)(2),(3)a, b, c, d - Appliances and Dedicated Circuits: Size in VA Size in VA 1500 N/A 3000 N/A 1000 N/A 600 N/A 1000 N/A 1600 N/A 5760 N/A N/A N/A N/A N/A N/A Amps Box B (VA) N/A 60.25 14460 Total VA from Parts #1 and #2 combined:Box A + Box B =17826 Total VA 17826 First 8,000 VA @ 100%8000 Remaining VA @ 40% Remaining VA =9826 9826 x 40% =3930.4 VA Adding First 8000 VA 8000 VA Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:11930.4 VA Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:49.71 Amps Part #3 - Section 220.83 (B) Heating and A/C loads: *Combine the larger loads of either the Heating or the A/C loads togther 100% of all the Heating or A/C loads in VA:0 VA 100% of all the Heating or A/C loads in Amps:0.00 A VA Volts Amps Parts #1 & #2 11930.4 240 49.71 Part #3 0 240 0.00 Total VA for all Parts:11,930 Totals Service/Feeder Load 49.71 #ESTAMP Refrigerator(s) Microwave(s) Totals for Part #2:Pool Equipment Dryer Range Oven Cooktop Amps 14.025 Job Code 109R-140TOLE Totals from all Parts Dedicated circuit Total for Part #1: Water Heater House Square Footage 1122 Article 220 - Service/Feeder calculation for (address): 2140 S Broadway Santa Ana, CA 92707 Building VA (watts) 3366 Laundry Appliance Circuit(s) Dishwasher(s) Disposal(s) Dedicated circuit 2140 S Broadway 3/21/2025 Bus Rating:125 Main Rating:100 0%0% Not Fed by other panels Feeds: Panel 2 49.71 0.00 49.71 Bus Rating:225 Main Rating:100 100%100% Itemized House and 240V Loads for Panel: (VA) 1500 1500 1500 1000 600 1000 1600 5760 Fed by: Panel 1 49.71 49.71 Panel 1 of 2 Panel % of Sq.Ft:Panel % of 100% VA: Load Calc: (This Panel) Total Load Calc: Panel 2 of 2 Panel % of Sq.Ft:Panel % of 100% VA: Laundry Appliance Circuit - 1 Load Calc: (This Panel) Total Load Calc: Appliance Circuit - 2 Dishwasher Disposal Refrigerator Microwave Dryer 2140 S Broadway 3/21/2025 City of Santa Ana, SIGNATURE:___________________ DATE:__________ 717 17th Street, Ste. 200 | Denver, CO 80202  I, Miguel Toledo, grant authorization to SUNRUN SOLAR to install Rooftop Mounted Solar on my residence located at 2140 s Broadway , SANTA ANA, CA, 92707. Docusign Envelope ID: B47231CB-9AD7-49FD-9D10-BD4C7209D56D 9/26/2024 2140 S Broadway 3/21/2025 Certificate Of Completion Envelope Id: B47231CB9AD749FD9D10BD4C7209D56D Status: Completed Subject: Complete with Docusign: Solar Authorization Letter 140TOLE.pdf Source Envelope: Document Pages: 1 Signatures: 1 Envelope Originator: Certificate Pages: 5 Initials: 0 Courtney Ashley Tijing AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 225 Bush Street, Suite 1400 San Francisco, CA 94104 courtneyashley.tijing@sunrun.com IP Address: 99.145.234.107 Record Tracking Status: Original 9/26/2024 3:39:21 PM Holder: Courtney Ashley Tijing courtneyashley.tijing@sunrun.com Location: DocuSign Signer Events Signature Timestamp Miguel Toledo migueltoledo51@yahoo.com Security Level: Email, Account Authentication (None) Signature Adoption: Drawn on Device Using IP Address: 76.32.191.144 Signed using mobile Sent: 9/26/2024 3:39:46 PM Viewed: 9/26/2024 3:54:50 PM Signed: 9/26/2024 3:55:06 PM Electronic Record and Signature Disclosure: Accepted: 9/26/2024 3:54:50 PM ID: 5b0c3a40-aa13-45e7-965a-bfdacb85492e In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 9/26/2024 3:39:46 PM Certified Delivered Security Checked 9/26/2024 3:54:50 PM Signing Complete Security Checked 9/26/2024 3:55:06 PM Completed Security Checked 9/26/2024 3:55:06 PM Payment Events Status Timestamps Electronic Record and Signature Disclosure 2140 S Broadway 3/21/2025 CONSUMER DISCLOSURE From time to time, Sunrun Inc. (we, us or Company) may be required by law to provide to you certain written notices or disclosures. Described below are the terms and conditions for providing to you such notices and disclosures electronically through the DocuSign, Inc. (DocuSign) electronic signing system. PLEASE READ THE INFORMATION BELOW CAREFULLY AND THOROUGHLY, AND IF YOU CAN ACCESS THIS INFORMATION ELECTRONICALLY TO YOUR SATISFACTION AND AGREE TO THESE TERMS AND CONDITIONS, PLEASE CONFIRM YOUR AGREEMENT BY CLICKING THE 'I AGREE' BUTTON AT THE BOTTOM OF THIS DOCUMENT. Getting paper copies At any time, you may request from us a paper copy of any record provided or made available electronically to you by us. You will have the ability to download and print documents we send to you through the DocuSign system during and immediately after signing session and, if you elect to create a DocuSign signer account, you may access them for thirty (30) days after such documents are first sent to you. After such time, if you wish for us to send you paper copies of any such documents from our office to you, please request delivery of such paper copies from us by following the procedure described below. Withdrawing your consent If you decide to receive notices and disclosures from us electronically, you may at any time change your mind and tell us that thereafter you want to receive required notices and disclosures only in paper format. How you must inform us of your decision to receive future notices and disclosure in paper format and withdraw your consent to receive notices and disclosures electronically is described below. Consequences of changing your mind If you elect to receive required notices and disclosures only in paper format, it will slow the speed at which we can complete certain steps in transactions with you and delivering services to you because we will need first to send the required notices or disclosures to you in paper format, and then wait until we receive back from you your acknowledgment of your receipt of such paper notices or disclosures. To indicate to us that you are changing your mind, you must withdraw your consent using the DocuSign ‘Withdraw Consent’ form on the signing page of a DocuSign envelope instead of signing it. This will indicate to us that you have withdrawn your consent to receive required notices and disclosures electronically from us and you will no longer be able to use the DocuSign system to receive required notices and consents electronically from us or to sign electronically documents from us. All notices and disclosures will be sent to you electronically Unless you tell us otherwise in accordance with the procedures described herein, we will provide electronically to you through the DocuSign system all required notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to you during the course of our relationship with you. To reduce the chance of you inadvertently not receiving any notice or disclosure, we prefer to provide all of the required notices and disclosures to you by the same method and to the same address that you have given us. Thus, you can receive all the disclosures and notices electronically or in paper format through the paper mail delivery system. If you do not agree with this process, please let us know as described below. Please also see the paragraph immediately above that describes the consequences of your electing not to receive delivery of the notices and disclosures electronically from us. Electronic Record and Signature Disclosure created on: 8/7/2013 10:17:58 AM Parties agreed to: Miguel Toledo 2140 S Broadway 3/21/2025 How to contact Sunrun Inc.: You may contact us to let us know of your changes as to how we may contact you electronically, to request paper copies of certain information from us, and to withdraw your prior consent to receive notices and disclosures electronically as follows: To contact us by email send messages to: customercare@sunrun.com You may also contact us in writing at 45 Fremont Street, 32nd Floor, San Francisco, CA 94105 or by phone at 1-855-478-6786. To advise Sunrun Inc. of your new e-mail address To let us know of a change in your e-mail address where we should send notices and disclosures electronically to you, you must send an email message to us at customercare@sunrun.com and in the body of such request you must state: your previous e-mail address, your new e-mail address. We do not require any other information from you to change your email address. In addition, you must notify DocuSign, Inc. at 1-866-219-4318 to arrange for your new email address to be reflected in your DocuSign account by following the process for changing e-mail in the DocuSign system. To request paper copies from Sunrun Inc. To request delivery from us of paper copies of the notices and disclosures previously provided by us to you electronically, you must contact us by (a) sending us an e-mail to customercare@sunrun.com, (b) writing to us at Sunrun Inc, 45 Fremont Street, 32nd Floor, San Francisco, CA 94105, or (c) calling us at 1-855-478-6786, and in connection with your request you must state your e-mail address, full name, US Postal address, and telephone number. To withdraw your consent with Sunrun Inc. To inform us that you no longer want to receive future notices and disclosures in electronic format you may: i. decline to sign a document from within your DocuSign session, and on the subsequent page, select the check-box indicating you wish to withdraw your consent, or you may; ii. contact us by (a) sending us an email to customercare@sunrun.com, (b) writing to us at Sunrun Inc., 45 Fremont Street, 32nd Floor, San Francisco, CA 94105, or (c) calling us at 1-855-478-6786, and in connection with your request you must state your e-mail, full name, US Postal Address, and telephone number. We do not need any other information from you to withdraw consent.. The consequences of your withdrawing consent for online documents will be that transactions may take a longer time to process.. Required hardware and software Operating Systems: Windows® 2000, Windows® XP, Windows Vista®; Mac OS® X 2140 S Broadway 3/21/2025 Browsers: Final release versions of Internet Explorer® 6.0 or above (Windows only); Mozilla Firefox 2.0 or above (Windows and Mac); Safari™ 3.0 or above (Mac only) PDF Reader: Acrobat® or similar software may be required to view and print PDF files Screen Resolution: 800 x 600 minimum Enabled Security Settings: Allow per session cookies ** These minimum requirements are subject to change. If these requirements change, you will be asked to re-accept the disclosure. Pre-release (e.g. beta) versions of operating systems and browsers are not supported. Notices Any notice or other communication to be made hereunder, even if otherwise required to be in writing under other provisions of this Consent or any other documents or agreements that have been provided to you in connection with this Consent, may alternatively be made in an electronic record transmitted electronically to the electronic addresses provided by you. Any notice or other communication made in electronic form will have the same legal effect and enforceability as if made in non-electronic form. Acknowledging your access and consent to receive materials electronically To confirm to us that you can access this information electronically, which will be similar to other electronic notices and disclosures that we will provide to you, please verify that you were able to read this electronic disclosure and that you also were able to print on paper or electronically save this page for your future reference and access or that you were able to e-mail this disclosure and consent to an address where you will be able to print on paper or save it for your future reference and access. Further, if you consent to receiving notices and disclosures exclusively in electronic format on the terms and conditions described above, please let us know by clicking the ‘I agree’ button below. By checking the ‘I agree’ box, I confirm that:  I can access and read and have accessed, read and understood the terms of this ELECTRONIC CONSENT TO ELECTRONIC RECEIPT OF ELECTRONIC CONSUMER DISCLOSURES document; and  I can print on paper the disclosure or save or send the disclosure to a place where I can print it, for future reference and access; and  Until or unless I notify Sunrun Inc. as described above, I consent to receive from exclusively through electronic means all notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to me by Sunrun Inc. during the course of my relationship with you. Entire Agreement Provision This agreement and the consumer disclosure statement executed by the customer in conjunction with and simultaneously with its review and acceptance of the terms set forth herein constitute 2140 S Broadway 3/21/2025 the entire agreement between the parties with respect to the subject matter hereof and supersede any prior understandings, agreements, or representations by or between the parties, written or oral, to the extent they relate in any way to the subject matter hereof. 2140 S Broadway 3/21/2025 STRUCTURAL CERTIFICATION REPORT Roof-mounted Solar Panels September 24, 2024 To: Sunrun Re: Miguel Toledo 1800 Ashton Blvd 2140 S Broadway Lehi, UT 84043 Santa Ana, CA 92707 AHJ: Santa Ana (City), CA Sunrun proposes to install new roof-mounted solar panels at this residence and asked Right Angle Engineering to review the existing structure for suitability. This letter summarizes the methods that were used to survey, evaluate, and certify the existing roof framing and the attachment of the new solar panels to it. STRUCTURAL DESIGN Building Code:California Residential Code 2022 Design Standards:ASCE 7-16 Snow:Ground: pg= 0.0 psf | Flat Roof: pf= 0.0 psf | Sloped Roof: ps= 0.0 psf Wind:Ultimate Wind Speed = 96.0 mph | Exposure = C Seismic:Risk Category = 2 | Seismic Design Category = A | Site Class = D STRUCTURE Field Technicians from Sunrun visited the site and observed the existing structure : Array Name Panel Quantity Roof Framing Material Pitch Array 1 7 2x4 Rafter| 24" o.c.Asphalt Shingles 21° ANCHORAGE The solar panel anchorage shall be installed according to the manufacturer's most current installation manual. The attachment configuration should match the certified building plans. The solar panels should be mounted parallel (max 5 inches) to the roof surface. Array Name Connection Type Fastener Max Anchorage Spacing Array 1 SpeedSeal Deckfoot (into rafter) (2) #14 SS screws into rafter (2) #14 SS screws into deck (1.5" embedment) into roof substructure 72" Installation Instructions Solar panels and the equipment shall be installed per the manufacturer's installation specifications. Improper installation will void this certification. If deviations from the approved structural plans occur, Right Angle Engineering must be notified. Prior to installation, the installer should: •Confirm that the existing structure matches the information provided in the site survey, the approved installation plans and this certification. •Identify discrepancies between this certification and the approved installation plans. If found, then this certification shall govern. •Identify structural elements that are dangerous (cracked, broken, excessive sag, signs of overstress, rot, decay, fire, water). If found, installation shall cease until those elements are adequately abated and made to comply with the referenced building code. •Verify that both the existing structure and the solar addition has been permitted through the AHJ. 757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 1 of 6 2140 S Broadway 3/21/2025 STRUCTURAL CERTIFICATION I certify the addition of solar panels on the roof of this structure does not cause the structure to become unsafe or make it generally less compliant with the life-safety requirements of the referenced building code. Based on the evaluation methods described below, for the loads that exist at this site, the existing framing will safely support the new solar panels if they are installed and attached correctly. Electrical design is not included in this certification. Array Name Certification Method Retrofits Array 1 Stress analysis California Residential code 324.4.1 None required Regards, 09/24/2024 Robert D. Smythe, P.E. Right Angle Engineering 757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 2 of 6 2140 S Broadway 3/21/2025 Job Details Roof Snow Load - ASCE 7-16 Ground Snow Load (pg) Section 7.2 0.0 psf Exposure Factor (Ce) Table 7.3-1 0.9 Thermal Factor (Ct) Table 7.3-2 1.1 Importance Factor (Is) Table 1.5-2 1 Flat Roof Snow Load (pƒ) Equation 7.3-1 0.0 psf Non-Slippery Surface Slope Factor (Cs) Figure 7.4-1 1 Slippery Surface Slope Factor (Cs) Figure 7.4-1 0.82 Roof Snow Load Equation 7.4-1 0.0 psf Reduced Snow Load (Slippery Surface) Equation 7.4-1 0.0 psf Design Criteria Wind Speed (Vult) Local Design Criteria 96.0mph Exposure Category C Risk Category 2 Mean Roof Height 20 ft Roof Type Gable Roof Building Type Enclosed Roof Live Load Existing Roof Live Load ASCE 7-16 Table 4.3-1 20 psf 1Roof Dead Load Asphalt Shingles 2.0 psf No Drywall 0.0 psf 5/8" Plywood Sheathing 2.0 psf Solar Panel Array 2.74 psf Roof Framing 1.1 psf Dead Load Without Panels 6.3 psf Insulation 1.2 psf 1Roof Dead Load is taken from the worst case scenario dead load from all arrays of the job in order to provide a more conservative evaluation. 757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 3 of 6 2140 S Broadway 3/21/2025 Array 1 Array Details Roof Framing 2x4 Rafter DF No.2 Spacing 24.0" Beam Span 9.5', 9.5' Roof Pitch 21° Solar Rails UR-40 Panel Quantity 7 Panel Array Area 151.45 ft² Panel Orientation Portrait Lag Screw Embedment 1.5" Roof Attachment Type SpeedSeal Deckfoot (into rafter) (2) #14 SS screws into rafter (2) #14 SS screws into deck Shear Capacity SnapnRack testing 460.0 lbs Pullout Capacity SnapnRack testing 829.0 lbs Velocity Pressure Equation 26.10-1 (Kz=0.9, Kht=1, Kd=0.85, Ke=1.0) 15.61 psf GCP Zones 1/2e 2n/2r /3e 3r GCp Figure 30.3-(2A-5B)-1.48 -2.13 -2.4 Design Pressure Up [psf] Equation 29.4-7 ga=0.53 gE=1.0,-16 -17.7 -19.9 Factored Design Pressure Up [psf] ASD LC (.6D + .6W) -8.1 -9.1 -10.4 Exposed Design Pressure Up [psf] ga=0.53 gE=1.5, -18.5 -26.6 -29.9 Design Pressure Down [psf]16 16 16 Tributary Area [ft2]102. 8 91.2 79.5 Maximum Connection Spacing [in]394 350 305 Maximum Rail Span [in]80 80 80 Maximum Rail Cantilever [in]24 24 24 Design Connection Spacing [in] *Adjusted 72 72 72 Design Connection Spacing (exposed) [in]72 72 72 757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 4 of 6 2140 S Broadway 3/21/2025 Design Ratio Member ID Axial Momentz Sheary Combined Slenderness Deflection Status 1 0.007 0.589 0.228 0.588 0.035 0.557 Pass 2 0.003 0.082 0.059 0.085 0.035 0.417 Pass Member Design Capacity (LRFD) Member ID FI b(ksi)FI t(ksi)FI v(ksi)FI c(ksi)FI cp(ksi)EI(ksi)Emin I(ksi) 1 2.681 1.49 0.311 2.683 0.939 1600.0 1041.216 2 2.681 1.49 0.311 2.683 0.939 1600.0 1041.216 Node Coordinates ID X Coordinate Y Coordinate 1 0.000 0.000 2 9.500 3.647 3 19.000 7.293 4 -1.500 -0.576 Members ID Node A Node B Section Node A Fixity Node B Fixity Length 1 1 3 1 FFFFFF FFFFFF 20.352 2 4 1 1 FFFFFF FFFFFF 1.607 Supports ID Node ID Restraint Code 1 2 RFFRRR 2 3 RFFRRR 3 1 FFFFFR Materials ID Name Young's Modulus Density Poisson's Ratio 1 NDS - Table 4A - DOUGLAS FIR-LARCH - No.2- 2in & wider 1600.000 33.308 0.400 Sections ID Name Depth Width Shear Area Z Shear Area Y Torsion Radius 1 1.5 x 3.5 4.000 1.500 5.000 5.000 1.463 ID Centroid Y Centroid Z Area Y-Axis Mol Z-Axis Mol Torsion Constant 1 0.750 2.000 6.000 1.125 8.000 3.437 Point Loads ID Load Group Member Position %Y Magnitude 1 Solar-Snow 1 2.632%0.000 2 Solar 1 2.632%-0.026 3 Solar-Snow 1 33.374%0.000 4 Solar 1 33.374%-0.026 Member Distributed Loads ID Load Group Start Position End Position Member Y Magnitude 1 Dead Load 0.000%100.000%2 -0.013 2 Dead Load 0.000%100.000%1 -0.013 3 Roof Live Load 0.000%66.667%2 -0.032 4 Roof Live Load 58.853%100.000%1 -0.032 5 Snow Load 0.000%66.667%2 0.000 6 Snow Load 58.853%100.000%1 0.000 Load Combinations ID Name Dead Load Factor Snow Load Factor Solar Factor Solar-Snow Factor Roof Live Load Factor 757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 5 of 6 2140 S Broadway 3/21/2025 1 1. 1.4D 1.4 0 1.4 0 0 2 3. 1.2D + 1.6Lr 1.2 0 1.2 0 1.6 3 3. 1.2D + 1.6S 1.2 1.6 1.2 1.6 0 4 4. service loads A 0 1 0 1 0 5 5. service loads B 0 0 0 0 1 Internal Member Forces and Moments Member Axial Force (Min/Max) Shear Force Y (Min/Max) Shear Force Z (Min/Max) Torsion (Min/Max) Bending Moment Y (Min/Max) Bending Moment Z (Min/Max) 1 -0.100 / 0.109 -0.261 / 0.283 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.473 / 0.526 2 -0.028 / 0.000 -0.074 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.073 / 0.000 Member Displacement Span Check Member Length Max Relative Displacement Span Method 1 1 20.352 0.378 L/323 2 1.607 0.089 L/216 Member Stresses Member Axial Stress (Min/Max) Torsion Stress (Min/Max) Shear Stress Y (Min/Max) Shear Stress Z (Min/Max) Top Bending Moment Z (Min/Max) Bottom Bending Moment Z (Min/Max) 1 -0.017 / 0.018 0.000 / 0.000 -0.065 / 0.071 -0.000 / -0.000 -1.419 / 1.578 -1.578 / 1.419 2 -0.005 / 0.000 0.000 / 0.000 -0.019 / 0.000 -0.000 / -0.000 -0.219 / 0.000 0.000 / 0.219 757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 6 of 6 2140 S Broadway 3/21/2025 Rev: 8/29/19 SOL-01 CBC 2016 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1. Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org RESIDENTIAL PHOTOVOLTAIC CHECKLIST SUNRUN CA CL #750184 2140 S Broadway, Santa Ana, CA, 92707 caitlyn h 3854005019 oc_permits@sunrun.com 2140 S Broadway 3/21/2025 PLPLPL PL PLPL PL PL PL PLPAGE REV: J 3/29/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA, CA, 92707 PROJECT NUMBER: 109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024 02 28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603 FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 SITE PLAN PV-2.0 #SSTAMPSP #ESTAMPSP ARRAY PITCH PV AREA (SQFT) AR-01 21° 147.2 TRUE AZIM MAG AZIM 77° 89° NOTES: RESIDENCE DOES NOT CONTAIN ACTIVE FIRE SPRINKLERS. ARRAY DETAILS: TOTAL ROOF SURFACE AREA: 1837 SQFT. TOTAL PV ARRAY AREA(E+N): 422.51 SQ FT. PERCENTAGE PV COVERAGE: (TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE AREA)(E+N) * 100 = 23% ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4. ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON LARGE/SCALE FIRE TESTING. SITE PLAN - SCALE = 0'-0 3/64" = 1'-0" POWERWALL ENERGY STORAGE SYSTEM (ESS) BG BACKUP GATEWAY GP GENERATION PANEL ELECTRIC VEHICLE SUPPLY EQUPMENTEV MAIN PANEL INVERTER(S) AC DISCONNECT(S) DC DISCONNECT(S) SUNRUN METER DEDICATED PV METER SERVICE ENTRANCE INTERIOR EQUIPMENT SHOWN AS DASHED SE MP SM PM INV AC DC SUB-PANEL SP CB IQ COMBINER BOX METER ADAPTERMA GROUNDING ELECTRODE ENERGY STORAGE SYSTEM BP BACKUP LOADS PANEL BI BACKUP INTERFACE 1 COMMUNICATION WIRESAM MD MICROGRID INTERCONNECT DEVICE ACREL METER SOLAREDGE METER SEM PV LOAD CENTER LC LEGEND SCALE: NTS NOTE: NOT ALL ITEMS IN LEGEND WILL APPEAR IN SITE PLAN RAIL STANDOFFS & FOOTINGS SOLAR MODULES EXTERNAL RAPID SHUTDOWN SWITCH RSD MD (E) RESIDENCE (N) ARRAY AR-01 FIRE SETBACKS (18" TYP) ROOF PATHWAYS (3' TYP) SE MP (E) PV ARRAY(TYP) (E) PV EQUIPMENT S BROADWAYROOF PATHWAYS (3' TYP) ACPM INVAC (E) GATE(TYP) (E) FENCE(TYP) (E) DETACHED GARAGE STRUCTURE (TYP.) (E) DETACHED SHED STRUCTURE (TYP.) (E) CHIMNEY AA A A B BB 125'-9" 50'-2" 125'-9" 50'-10" 20'-6" 4'-5" 2'-9" 1'-7" 3'-8" 5' 2'-6" 10'-3" 20'-7" 13'-7" 8'-9" (E) DETACHED EQUIPMENT AWNING STRUCTURE (TYP.)(E) ROOF PLANE ATTACHED TO STRUCTURE (E) DETACHED GARAGE STRUCTURE ROOF PLANE ATTACHED TO GARAGE STRUCTURE (TYP.) SP (E) SUBPANEL LC J J Revision to 20184760 (issued on 3/21/25) Revision 1 #20185638 APPROVALS: ELECT - M. Smith 2140 S Broadway - REV 15/5/2025 PAGE REV: J 3/29/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA,  CA, 92707 PROJECT NUMBER:   109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024 02 28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 PV-2.1 EXTERIOR NORTH WALL ACD  CHIMNEY SITE PLAN - SCALE = NTS ESS ELEVATION VIEW ESS ELEVATION VIEW PW3 W/ EXPACK STACKED ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4.   ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT  WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON  LARGE/SCALE FIRE TESTING. WINDOW 3' MIN WINDOW 3' MIN MAIN SERVICE PANEL WINDOW J I V I LREGISTERED PR O F ESSIONAL E N G I NEERS T ATE OF C A L IFORNIAROBER T SMYT H EC56136 EXP. 12/31/26 2140 S Broadway - REV 15/5/2025 (N) TESLA  REMOTE M ETER SOLAR CU RRENT TRANSFO RMERS PAGE REV: J 3/29/2025 MIGUEL TOLEDO 2140 S BROADWAY, SANTA ANA,  CA, 92707 PROJECT NUMBER:   109R-140TOLE SHEET DESIGNER: AL AMEEN V H CUSTOMER RESIDENCE: TEL. (714) 272-5451 APN: 015-082-22 (415) 580-6920 ex3 Template_version_v5_2024 02 28 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 SIGNAGE PV-5.0 #ESTAMP ENERGY STORAGE SYSTEM PREMISES WIRING MAY REMAIN  ENERGIZED AFTER LOSS OF  UTILITY POWER CAUTION! LABEL LOCATION: INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C) ENERGY STORAGE SYSTEM  DISCONNECT LABEL LOCATION: ENERGY STORAGE SYSTEM DISCONNECT PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C) MAXIMUM AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE:           61.5 AMPS   240     VAC LABEL LOCATION: AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF  INTERCONNECTION. PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54 PV SYSTEM DISCONNECT WARNING! DO NOT RELOCATE THIS  OVERCURRENT DEVICE POWER SOURCE OUTPUT CONNECTION LABEL LOCATION: ADJACENT TO PV BREAKER AND ESS  OCPD (IF APPLICABLE). PER CODE(S): NEC 2020: 705.12(B)(3)(2),  CEC 2022: 705.12(B)(3)(2) NOTES AND SPECIFICATIONS:   SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF  THE CEC 2022 ARTICLE 110.21(B), UNLESS SPECIFIC  INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF  REQUESTED BY THE LOCAL AHJ.  SIGNS AND LABELS SHALL ADEQUATELY WARN OF  HAZARDS USING EFFECTIVE WORDS, COLORS AND  SYMBOLS.  LABELS SHALL BE PERMANENTLY AFFIXED TO THE  EQUIPMENT OR WIRING METHOD AND SHALL NOT BE  HAND WRITTEN.  LABEL SHALL BE OF SUFFICIENT DURABILITY TO  WITHSTAND THE ENVIRONMENT INVOLVED.  SIGNS AND LABELS SHALL COMPLY WITH ANSI  Z535.4-2011, PRODUCT SAFETY SIGNS AND LABELS,  UNLESS OTHERWISE SPECIFIED.  DO NOT COVER EXISTING MANUFACTURER LABELS. SOLAR PV SYSTEM EQUIPPED  WITH RAPID SHUTDOWN SOLAR ELECTRIC  PV PANELS TURN RAPID SHUTDOWN  SWITCH TO THE "OFF"  POSITION TO SHUT DOWN  PV SYSTEM AND REDUCE  SHOCK HAZARD IN THE  ARRAY. LABEL LOCATION: ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE  DISCONNECTING MEANS TO WHICH THE PV SYSTEMS  ARE CONNECTED. PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C) 4" 3" ELECTRICAL SHOCK HAZARD WARNING TERMINALS ON LINE AND LOAD  SIDES MAY BE ENERGIZED IN  THE OPEN POSITION LABEL LOCATION: INVERTER(S),  AC/DC DISCONNECT(S),  AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): NEC 2020: 690.13(B), CEC  2022: 690.13(B) ! WARNING: PHOTOVOLTAIC  POWER SOURCE WARNING: PHOTOVOLTAIC  POWER SOURCE LABEL LOCATION: INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,  AT EACH TURN, ABOVE AND BELOW  PENETRATIONS,  ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS. PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:  690.31(D)(2)CAUTION  2140 S BROADWAY, SANTA ANA, CA, 92707 PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10 MULTIPLE SOURCES OF POWER LABEL LOCATION: INSTALLED WITHIN 3' OF RAPID SHUT DOWN  SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),  CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3 RAPID SHUTDOWN SWITCH  FOR SOLAR PV SYSTEM WARNING! SOURCES: UTILITY GRID,  BATTERY AND PV SOLAR  ELECTRIC SYSTEM THREE POWER SUPPLY LABEL LOCATION: UTILITY SERVICE METER AND MAIN  SERVICE PANEL. PER CODE(S): NEC 2020: 705.12(C), CEC  2022: 705.12(C) INVERTER 1 PHOTOVOLTAIC DC DISCONNECT MAXIMUM SYSTEM VOLTAGE:VDC550 LABEL LOCATION: INVERTER(S), DC DISCONNECT(S). PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53 SOLAR PANELS ON ROOF SERVICE ENTRANCE AND  TESLA BACKUP SWITCH INVERTER + BATTERY AND EXPACK  (EXT)- PCS CONTROLLED AC DISCONNECT (E) PV EQUIPMENT RAPID SHUTDOWN DISCONNECT LOCATION  (EXISTING SYSTEM AC DISCONNECT) (E) PV ARRAY (TYP.) PV SYSTEM(S) ARE EQUIPPED WITH RAPID  SHUTDOWN DEVICE(S) (E) SUB PANEL (N) LOAD CENTER J 2140 S Broadway - REV 15/5/2025