HomeMy WebLinkAbout2140 S Broadway - REV 1- 20185638 - PlanPAGE
REV: I 2/14/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N) NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
• EXISTING SYSTEM SIZE: 3975W DC, 3225W AC
• MODULES: (7) LONGI GREEN ENERGY TECHNOLOGY CO
LTD: LR5-54HABB-395M
• INVERTERS: (1) TESLA: POWERWALL 3 1707000-XX-Y,
• RACKING: UR - SPEEDSEAL DECKFOOT TO FRAMING -
SNR-DC-00449
• ENERGY STORAGE SYSTEM: (1) TESLA: POWERWALL 3
1707000-XX-Y, (1) EXPANSION 1807000-XX-Y
• RAPID SHUTDOWN: (3) TESLA MID CIRCUIT INTERRUPTER
(MCI) ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE
• POWER CONTROLLED SYSTEM (PCS) ENABLED
EQUIPMENT INSTALLED, SEE PV-4.0 FOR INTERCONNECTION
DETAILS
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-2.1 ESS ELEVATION VIEW
PV-3.0 LAYOUT
PV-3.1 MOUNTING DETAIL
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL CALCS
PV-4.2 BACKUP LOAD CALCS
PV-4.3 PANEL SCHEDULE
PV-5.0 SIGNAGE
PV-5.1 SIGNAGE
• ALL WORK SHALL COMPLY WITH 2022 CRC/CBC/CEBC, 7-16 ASCE & 2018 NDS,
MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
• PHOTOVOLTAIC SYSTEM WILL COMPLY WITH CEC 2022.
• ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH CEC 2022.
• PHOTOVOLTAIC SYSTEM IS FUNCTIONALLY GROUNDED. NO CONDUCTORS ARE
SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A).
• MODULES CONFORM TO AND ARE LISTED UNDER UL 61730.
• INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
• RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
• SNAPNRACK RACKING SYSTEMS, IN COMBINATION WITH TYPE I, OR TYPE II
MODULES, ARE CLASS A FIRE RATED.
• RAPID SHUTDOWN SYSTEM IN COMPLIANCE WITH CEC 2022 690.12(B)(1) WHERE
CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30
SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE
ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS
• CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(D).
• ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT.
• 14.79 AMPS MODULE SHORT CIRCUIT CURRENT.
• 23.11 AMPS DERATED SHORT CIRCUIT CURRENT [690.8 (A)(1) & 690.8 (B)].
• ENERGY STORAGE SYSTEM CONFORMS TO AND IS LISTED UNDER UL 9540.
• ENERGY STORAGE SYSTEM LIVE PARTS ARE NOT ACCESSIBLE DURING
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
• ADDITIONAL DISCONNECTING MEANS SHALL BE INSTALLED WHERE THE
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
• LISTED, COMBINATION TYPE AFCI SHALL BE INSTALLED WHERE BACKED UP
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
• ALL PASS-THROUGH CONDUCTORS MUST COMPLY WITH CEC 312.8
• THE CAPACITY OF THE STANDALONE SYSTEM SUPPLY SHALL BE EQUAL TO OR
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
• NEW SYSTEM SIZE: 2765W DC, 11500W AC
• COMBINED SYSTEM SIZE: 6740W DC, 14725W AC
NEW 200A PV LOAD CENTER TO BE INSTALLED
I
Bldg #101122013 & Elect #20184760
APPROVALS:
ELECT - M. Smith
**The scope of the plans is for the installation of the
solar photovoltaic system only and the approval is
subject to compliance with all applicable city and state
codes and regulations regarding construction. The
approval of the plans does not constitute any
certification of the accuracy, completeness, or building
permit status of the existing buildings and structures
as shown. **
2140 S Broadway
3/21/2025
PAGE
REV: I 2/14/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
PV-2.1
GATE
EXTERIOR SOUTH WALL
ACD
DOOR
SITE PLAN - SCALE = NTS
ESS ELEVATION VIEW
ESS ELEVATION VIEW
EXPACKPW3
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4.
ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT
WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON
LARGE/SCALE FIRE TESTING.
WINDOW
3' MIN
WINDOW
GATE
3' MIN
I
I V I LREGISTERED PR O F E SSIONAL E
N
G
I
NEERS
T
ATE OF C A L IFORNIAROBER T SMYT
H
EC56136
EXP. 12/31/26
2140 S Broadway
3/21/2025
PAGE
REV: I 2/14/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46PLPLPLPLPLPLPLPLPLPL
SITE PLAN
PV-2.0
#SSTAMPSP
#ESTAMPSP
ARRAY
PITCH
PV AREA
(SQFT)
AR-01 21° 147.2
TRUE
AZIM
MAG
AZIM
77°89°
NOTES:
·RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
·TOTAL ROOF SURFACE AREA: 1837 SQFT.
·TOTAL PV ARRAY AREA(E+N): 422.51 SQ FT.
·PERCENTAGE PV COVERAGE:
(TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
AREA)(E+N) * 100 = 23%
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS
IN ACCORDANCE WITH R328.4. ESS UNITS SHALL BE
SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET
EXCEPT WHERE SMALLER SEPARATION DISTANCES ARE
DOCUMENTED TO BE ADEQUATE BASED ON LARGE/SCALE
FIRE TESTING.
SITE PLAN - SCALE = 3/64" = 1'-0"
POWERWALL ENERGY
STORAGE SYSTEM (ESS)
BG BACKUP GATEWAY
GP GENERATION PANEL
ELECTRIC VEHICLE
SUPPLY EQUPMENTEV
MAIN PANEL
INVERTER(S)
AC DISCONNECT(S)
DC DISCONNECT(S)
SUNRUN METER
DEDICATED PV METER
SERVICE ENTRANCE
INTERIOR EQUIPMENT
SHOWN AS DASHED
SE
MP
SM
PM
INV
AC
DC
SUB-PANELSP
CB IQ COMBINER BOX
METER ADAPTERMA
GROUNDING
ELECTRODE
ENERGY STORAGE
SYSTEM
BP BACKUP LOADS PANEL
BI BACKUP INTERFACE 1 COMMUNICATION
WIRESAM
MD MICROGRID
INTERCONNECT DEVICE
ACREL METER
SOLAREDGE METERSEMPV LOAD CENTERLC
LEGEND
SCALE: NTS
NOTE: NOT ALL ITEMS IN LEGEND
WILL APPEAR IN SITE PLAN
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
EXTERNAL RAPID
SHUTDOWN SWITCH
RSD
MD
(E) RESIDENCE
(N) ARRAY AR-01
FIRE SETBACKS
(18" TYP)
ROOF PATHWAYS
(3' TYP)
SE
MP
(E) PV ARRAY(TYP)
(E) PV EQUIPMENT
S BROADWAYROOF PATHWAYS
(3' TYP)
ACPM
INVAC
(E) GATE(TYP)
(E) FENCE(TYP)
(E) DETACHED GARAGE
STRUCTURE (TYP.)
(E) DETACHED SHED
STRUCTURE (TYP.)
(E) CHIMNEY
AAAABBB125'-9"
50'-2"
125'-9"
50'-10"
20'-6"
4'-5"
2'-9"
1'-7"
3'-8"
5'
2'-6"
10'-3"
20'-7"
13'-7"
8'-9"
(E) DETACHED
EQUIPMENT AWNING
STRUCTURE (TYP.)(E) ROOF PLANE
ATTACHED TO STRUCTURE
(E) DETACHED GARAGE
STRUCTURE ROOF PLANE
ATTACHED TO GARAGE
STRUCTURE (TYP.)
SP
(E) SUBPANEL
LC
I
I
I V I LREGISTERED PR O F E SSIONAL E
N
G
I
NEERS
T
ATE OF C A L IFORNIAROBER T SMYT
H
EC56136
EXP. 12/31/26
2140 S Broadway
3/21/2025
PAGE
REV: A 9/24/2024
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
#SSTAMP
DESIGN CRITERIA
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED:
96 MPH 3-SEC GUST.
FASTENERS:
(2) #14 S.S. SEALING WASHER
WOOD SCREWS: 1.5" MIN
EMBEDMENT INTO FRAMING
(2) #14 S.S. SEALING WASHER
WOOD SCREWS FULLY
PENETRATING THROUGH WOOD
DECK
PV-3.0
LAYOUT
SOLAR MODULE
SNAPNRACK
RACKING
6"
MODULE ELEVATION DETAIL - SCALE: NTS
INSTALLERS SHALL NOTIFY ENGINEER OF ANY
POTENTIAL STRUCTURAL ISSUES OBSERVED
PRIOR TO PROCEEDING W/ INSTALLATION.
* IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12"
BOUNDARY REGION OF ANY ROOF PLANE
EDGES (EXCEPT VALLEYS), THEN
ATTACHMENTS NEED TO BE ADDED AND
OVERHANG REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS FOLLOWS:
** ALLOWABLE ATTACHMENT SPACING
INDICATED ON PLANS TO BE REDUCED BY 50%.
** ALLOWABLE OVERHANG INDICATED ON
PLANS TO BE 1/5TH OF ALLOWABLE
ATTACHMENT SPACING INDICATED ON PLANS.
D1 - AR-01 - SCALE: 1/8" = 1'-0"
AZIM:89°
PITCH: 21°
6' TYP
7'-7"
11'-4"
18'-10"10'8'-2"
1'-1"
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION
Name Type Height Type
Max
Span
OC
Spacing Detail Max Landscape
OC Spacing
Max Landscape
Overhang
Max Portrait
OC Spacing
Max Portrait
Overhang Configuration
AR-01 COMP SHINGLE
SPEEDSEAL DECKFOOT 1-Story 2X4 RAFTERS 9'-2"24"UR - SPEEDSEAL DECKFOOT TO FRAMING -
SNR-DC-00449 6'-0"2'-4"6'-0" 2'-3"STACKED
09/24/2024
2140 S Broadway
3/21/2025
SNAPNRACK UR SPEEDSEAL DECKFOOT FOR COMPOSTION
ROOF MOUNTING ONTO WOOD RAFTER
5 16"-18 X 13
REFER TO SNAPNRACK ENGINEERING CHARTS FOR APPLICABLE
RAIL SPANS. "BIN" NUMBER ON CHART SHOULD MATCH "BIN"
NUMBER ON THIS DRAWING
(X2) #14 FULLY THREADED WOOD SCREWS, S.S. MUST
PENETRATE A MIN. OF 112" INTO STRUCTURAL MEMBER. (X2)
#14 FULLY THREADED WOOD SCREWS, S.S. MUST EMBED
FULLY INTO WOOD DECK
REFER TO SNAPNRACK INSTALLATION MANUAL FOR 5
HARDWARE TORQUE SPECIFICATIONS
16"
RAIL CAN MOUNT ON EITHER SIDE OF SPEEDSEAL DECKFOOT.
SPEEDSEAL DECKFOOT CAN MOUNT UP, DOWN, OR ACROSS
THE SLOPE OF THE ROOF
FOR ADDITIONAL LEVELING DETAILS, REFER TO SNAPNRACK
DETAIL DRAWING "SNR-DC-00447 ULTRA RAIL, COMPONENT
DETAIL, ULTRA RAIL LEVELING SPACER"
SNAPNRACK, ULTRA RAIL
MODULE HEIGHT, MAX:
UR-40 = 438"
UR-60 = 5"
SCREW HEIGHT
OFF ROOF:
9 16"
MINIMUM RAFTER
PENETRATION:
11 2"
ROOF DECKING
MINIMUM DECK THICKNESS:
PLYWOOD: 15 32"
OSB: 7
11
11 2"
21
15 8"
UR-40 RAIL | UR-60 RAIL
FOR USE WITH SNAPNRACK ULTRA SERIES RAILS
Sunrun South LLC
595 MARKET STREET, 29TH FLOOR SAN FRANCISCO, CA 94105 USA
PHONE (415) 580-6900 FAX (415) 580-6902
Solar Mounting SolutionsTHE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY
REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE
WRITTEN CONSENT OF SUNRUN SOUTH LLC.
DESIGNER:
APPROVED BY:
M.AFFENTRANGER
DRAFTER: M.AFFENTRANGER
W.ARBUCKLE
SCALE:
DATE:
DNS
4/5/2021
DRAWING NUMBER:
SNR-DC-00449
4"
2"
ATTACHMENT DETAIL
ROOF DECKING
WOOD RAFTER, TYP.
(STRUCTURAL MEMBER)
(2X) #14 FULLY THREADED
WOOD SCREW. S.S. INTO
STRUCTURAL MEMBER.
SIZE LENGTH APPROPRIATELY
INSTALLATION OVERVIEW
DESCRIPTION:
ULTRA RAIL, ATTACHMENT DETAIL, UR
SPEEDSEAL DECKFOOT TO RAFTER
16"
COMP SHINGLE ROOFING, TYP.
STRUCTURAL MEMBER (RAFTER)
COMP SHINGLE
ROOFING, TYP.
COIL SPRING FOR 3
BIN:
4" BOLT,
SERRATED FLANGE, S.S.
8"
BOLT, S.S. (OPTIONAL)
SNAPNRACK, SPEEDSEAL
DECKFOOT BASE, SEALING
SNAPNRACK, UR MOUNT
THRU
SNAPNRACK, UR MOUNT
TAPPED
TOP
EXPLODED
(2X) #14 FULLY THREADED
WOOD SCREW. S.S. MUST EMBED
FULLY INTO WOOD DECK
5.200
N/A
REVISION:
1 1/13/2021 NEW DETAIL
2 4/5/2021 2PC CLAMP
MJA
MJA
3.860
REV:
2 PAGE
REV: A 09/24/24
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
CA CL #750184
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MOUNTING DETAIL
PV-3.1
GILBERT CORREIA, C10, C46
APN: 015-082-22
09/24/2024
2140 S Broadway
3/21/2025
PAGE
REV: I 2/14/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
CONDUIT SCHEDULE
TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT
1 Inverter Input (2) 10 AWG (PV WIRE)N/A 6 AWG (BARE)Open Air
2 Inverter Input (2) 10 AWG
THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4 EMT
3 Inverter Output (2) 6 AWG
THHN/THWN-2
(1) 6 AWG
THHN/THWN-2 8 AWG THHN/THWN-2 3/4 EMT
4 PV Load Center Output (2) 3 AWG
THHN/THWN-2
(1) 3 AWG
THHN/THWN-2 8 AWG THHN/THWN-2 1 EMT
E EXISTING
EXISTING 100A
MAIN BREAKER
END FED
EXISTING 125A
MAIN PANEL
125A BUS
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A , 2P
120/240VAC
3
A
A
EXISTING 100A SUB PANEL
WITH 100A MAIN BREAKER
(E) LOADS
E
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN COMPLIANT,
POWER CONTROL SYSTEM
3
J-BOX
LONGi Green Energy Technology Co Ltd
LR5-54HABB-395M
STRING 1 OF 7 MODULES
3 MODULE LEVEL
RAPID SHUTDOWN DEVICES
12
POINT OF INTERCONNECTION:705.13, GATEWAY FEEDER
BREAKER AT OPPOSITE END OF BUSBAR
METER NUMBER: 222013-165258
EQUIPMENT CHARACTERISTICS
INCLUDED IN SPEC SHEETS
NOTE: TOTAL PV BACKFEED(E+N)
= 80A USED FOR INTERCONNECTION CALCULATIONS
J-BOX
(15) HANWHA Q-CELLS:
Q.PRO-G4 265 MODULES
AND MICRO-INVERTER PAIRS
(15) ENPHASE ENERGY:
M215-60-2LL-S2X-IG
EE
E
20A OCPD
M
Existing
Production Meter
E
Existing
Knife Disconnect 30A Rated
E
Existing
Combiner Panel XA Rated
E
E
(N) TESLA
REMOTE METER
SOLAR CURRENT
TRANSFORMERS
M
TESLA
BACKUP
SWITCH
NEW 200A
PV LOAD CENTER
(N) (1) - 60A (ESS+PV)BREAKER
(E) 20A PV BREAKER
4100AOCPD
100AOCPD
UL 9540
FACTORY
WIRING
ASSEMBLY
(1 ) TESLA
POWERWALL 3
EXPANSION PACK 1807000-XX-Y
PV-4.0
ELECTRICAL
#ESTAMP
MODULE CHARACTERISTICS
LONGI GREEN ENERGY
TECHNOLOGY CO LTD:
LR5-54HABB-395M
395 W
OPEN CIRCUIT VOLTAGE 36.81 V
MAX POWER VOLTAGE 30.7 V
SHORT CIRCUIT CURRENT 14.79 A
GENERAL NOTES:
• CITY REQUIRES TWO SOURCES OF GROUND - UFER,
TWO GROUNDS RODS OR COLD WATER GAS BOND
POWER CONTROL SYSTEM (PCS):
• A PCS IS INSTALLED IN ACCORDANCE WITH NEC 705.13
• THE PCS SHALL LIMIT GENERATION SOURCE OUTPUT SUCH THAT
CURRENT FROM ALL SOURCES OF SUPPLY DOES NOT EXCEED THE
RATING OF ANY BUSBAR OR CONDUCTOR SUPPLIED BY THE POWER
PRODUCTION SOURCES
• ANY BUSBAR OR CONDUCTOR ON THE LOAD SIDE OF THE
SERVICE DISCONNECT NOT MONITORED BY THE PCS SHALL
COMPLY WITH ARTICLE 705.12.
• ACCESS TO PCS CONTROLS IS RESTRICTED TO QUALIFIED
PERSONS IN ACCORDANCE WITH 240.6(C).
• ENERGY STORAGE SYSTEM: TESLA: POWERWALL 3 1707000-XX-Y
• ENABLE PCS
SETPOINTS:
- 100A - MAXIMUM TOTAL CURRENT ON THE CONTROLLED
PANEL
- 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY
(120% COMPLIANT)
INSTALL THE BACKED UP LOAD CONDUCTORS AND THE
GATEWAY BREAKER CONDUCTORS IN TWO SEPARATE CONDUITS.
I
2140 S Broadway
3/21/2025
PAGE
REV: I 2/14/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
PV-4.1
ELECTRICAL CALCS
#ESTAMP
SYSTEM INFORMATION
2.765 KW DC PHOTOVOLTAIC SYSTEM
(7) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M, TESLA: POWERWALL 3
1707000-XX-Y
SYSTEM OCPD SIZE
(COMBINED MAX CURRENT) X (CONTINUOUS LOAD) =
96 A X 1.25 = 120A → 100A OVERCURRENT PROTECTION UTILIZING PCS
ALLOWABLE BACKFEED
MAX ALLOWED TOTAL GENERATION BACKFEED OCPD = MAIN BREAKER RATING =
100A
100A ≤ 100A→ INTERCONNECTION MEETS 705.13 REQUIREMENTS.
GATEWAY SYSTEM AC WIRE SIZING
MAX AC OUTPUT CURRENT = 100 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 115A = 104.65A
TERMINAL RATING[110.14(C)] =
3 AWG, 75°C RATED = 100A
100A < 104.65A → TERMINAL RATING GOVERNS CONDUCTOR SIZING
100A ≤ 100A → 3 AWG AMPACITY OK
THEREFORE 3 AWG IS SUFFICIENT.
INVERTER INFORMATION
2765 KW DC PHOTOVOLTAIC SYSTEM
(7) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-395M, TESLA: POWERWALL 3
1707000-XX-Y
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS
LOAD)[690.8(B)(1)]=
15A X 1.25 = 18.75A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
35A < 36.4A → TERMINAL RATING GOVERNS CONDUCTOR SIZING
18.75A < 35A → 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE
310.15(C)(1)] X (CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG, 75°C RATED = 65A
65A < 68.25A → TERMINAL RATING GOVERNS CONDUCTOR SIZING
60A < 65A → 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT.
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP -
STC TEMP] + VOC} X (# MODULES / STRING) =
{[(-0.26 %/°C X 36.81 V) / 100] X [-2 °C - 25 °C] + 36.81 V} X 7 = 276.5 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 14.79 A X 1 = 18.48A
I 2140 S Broadway
3/21/2025
BACKUP LOADS
LOAD BREAKER RATING
(AMPS)LABEL DEMAND LOAD(VA)
1 100A-2P SUB PANEL 19200 W
2 30A-2P DRYER 5760 W
BACKUP LOAD CALCS
PV-4.2
BACKUP LOAD CALCS
#ESTAMP
PAGE
REV: A 9/24/2024
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
Template_version_v5_2024 02 28
ALL BACKED UP LOADS ABOVE IN THE BACKED UP LOADS PANEL ARE RELOCATED FROM THE MAIN SERVICE PANEL.
BACKED UP LOADS CALCULATION:
(5760 VA)/ 240V = 24 A PER CEC 2022 ARTICLE 690.10 OR NEC 2020 ARTICLE 710.15.
THE MAXIMUM CURRENT FOR ALL SMALL APPLIANCES LOADS IS 24A.
(MAX LOADS OUTPUT) X (CONTINUOUS LOADS) =
24 A X 1.25 = 30A
BACKED UP LOADS PANEL BREAKER = 70A
30 A < 70A.
THEREFORE, THE AMPERAGE OF THE BACKED UP LOADS IS LESS THAN THAT OF THE OCPD.
AC WIRE SIZING FOR BACKED UP LOADS PANEL:
MAX AC OUTPUT CURRENT = (MAX LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
30 A X 1.25 = 38A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 55A = 50.05A
TERMINAL RATING[110.14(C)] =
8 AWG, 75°C RATED = 50A
50A < 50.05A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
38A ≤ 50A 8 AWG AMPACITY OK
THEREFORE 8 AWG IS SUFFICIENT.
AC WIRE SIZING FOR BACKED UP LOADS PANEL:
MAX AC OUTPUT CURRENT = (MAX LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
12.5 A X 1.25 = 15.625A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 40A = 36.4A
TERMINAL RATING[110.14(C)] =
12 AWG, 75°C RATED = 35A
35A < 36.4A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
15.625A < 35A 12 AWG AMPACITY OK
THEREFORE 12 AWG IS SUFFICIENT.
2140 S Broadway
3/21/2025
PV-4.3
#ESTAMP
PANEL
SCHEDULE
PAGE
REV: I 2/14/2025
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
FUTURE 125/100A
MAIN PANEL
30100100
DRYER
SUB PANEL
PANEL SCHEDULE
(E) 100/100A
SUBPANEL
10020202020201515BEDROOM LIGHTS
BEDROOM 1 OUTLET
BEDROOM 2 OUTLET
BEDROOM 3 OUTLET
REFRIGERATOR
BATHROOM PLUGS
BATHROOM LIGHTS
MAIN BREAKER
EXISTING 125/100A MAIN
PANEL
30100100
DRYER
SUB PANEL
20(E) PV BREAKER
60ESS +PV
BREAKER
20(E) PV BREAKER
(N) 200A PV LOAD
CENTER 100PV LOAD
CENTER
FEEDER
BREAKER
I
2140 S Broadway
3/21/2025
PAGE
REV: I 2/14/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024.02.28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
( N) TESLAR EMOTE METERS OLAR CURRENTT RANSFORMERS
SIGNAGE
PV-5.0
#ESTAMP
ENERGY STORAGE SYSTEM
CAUTION!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C)
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
CEC 2022: 705.12(B)(3)(2)
NOTES AND SPECIFICATIONS:
·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF
THE CEC 2022 ARTICLE 110.21(B), UNLESS SPECIFIC
INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF
REQUESTED BY THE LOCAL AHJ.
·SIGNS AND LABELS SHALL ADEQUATELY WARN OF
HAZARDS USING EFFECTIVE WORDS, COLORS AND
SYMBOLS.
·LABELS SHALL BE PERMANENTLY AFFIXED TO THE
EQUIPMENT OR WIRING METHOD AND SHALL NOT BE
HAND WRITTEN.
·LABEL SHALL BE OF SUFFICIENT DURABILITY TO
WITHSTAND THE ENVIRONMENT INVOLVED.
·SIGNS AND LABELS SHALL COMPLY WITH ANSI
Z535.4-2011, PRODUCT SAFETY SIGNS AND LABELS,
UNLESS OTHERWISE SPECIFIED.
·DO NOT COVER EXISTING MANUFACTURER LABELS.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
4"
3"
ELECTRICAL SHOCK HAZARD
WARNING
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S),
AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC
2022: 690.13(B)
!
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:
690.31(D)(2)CAUTION:
2140 S BROADWAY, SANTA ANA, CA, 92707
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
MULTIPLE SOURCES OF POWER
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC
2022: 705.12(C)
INVERTER 1
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
SOLAR PANELS ON ROOF
SERVICE ENTRANCE AND
TESLA BACKUP SWITCH
INVERTER + BATTERY AND EXPACK
(EXT)- PCS CONTROLLED
AC DISCONNECT
(E) PV EQUIPMENT
RAPID SHUTDOWN DISCONNECT LOCATION
(EXISTING SYSTEM AC DISCONNECT)
(E) PV ARRAY (TYP.)
PV SYSTEM(S) ARE EQUIPPED WITH RAPID
SHUTDOWN DEVICE(S)
(E) SUB PANEL
(N) LOAD CENTER
I
2140 S Broadway
3/21/2025
PAGE
REV: A 9/24/2024
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.1
#ESTAMP
WARNING: THIS SENSOR IS PART
OF A POWER CONTROL SYSTEM.
DO NOT REMOVE. REPLACE ONLY
WITH THE SAME TYPE AND RATING.
WARNING: THIS SENSOR IS PART
OF A POWER CONTROL SYSTEM.
DO NOT REMOVE. REPLACE ONLY
WITH THE SAME TYPE AND RATING.
REQUIREMENT: UL 1741, SECTION 206.3
LOCATION: AROUND THE CT WIRE BY CLAMP
SIZE 4.25" X 0.75"
INVERTER 1
LABEL LOCATION:
REQUIREMENT: UL 1741, SECTION 206.1 AND 206.4
LOCATION: MAIN PANEL
SIZE: 4.25" X 1.25"
PCS CONTROLLED CURRENT SETTING: 36A
THE MAXIMUM OUTPUT CURRENT FROM THIS
SYSTEM IS CONTROLLED ELECTRONICALLY.
REFER TO THE MANUFACTURER'S
INSTRUCTIONS FOR MORE INFORMATION.
ENERGY STORAGE SYSTEM DISCONNECT
NOMINAL ESS VOLTAGE VAC
LABEL LOCATION:
MAIN PANEL.
120 240
NEC 2020 - PW3
PER CODE(S): NEC 706.15(C)
LABEL LOCATION:
BACKED UP LOADS PANEL
NO ADDITIONAL
LOADS TO BE
ADDED
2140 S Broadway
3/21/2025
2140 S Broadway3/21/2025
Service Voltage
240
Section 220.83 Existing Dwelling Unit
Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
14.03 3366
Part #2 - Section 220.83(B)(2), (3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500
1500
1500
1000
600
1000
1600
5760
Amps Box B (VA)
60.25 14460
Total VA from Parts #1 and #2 combined:Box A + Box B =17826
Total VA 17826
First 8000 VA @ 100%8000 Remaining VA @ 40%
Remaining VA =9826 9826 x 40% =3930.4 VA
Adding First 8000 VA, if possible 8000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:11930.4 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:49.71 Amps
Part #3 - Section 220.83(B) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:0 VA
100% of all the Heating or A/C loads in Amps:0.00 A
VA Volts Amps
Parts #1 & #2 11930.4 240 49.71
Part #3 0 240 0.00
Total VA for all Parts:11,930
Totals Service/Feeder Load 49.71
Microwave
Dryer
Totals for Part #2:
Totals from all Parts
Dishwasher
Disposal
Refrigerator
Laundry
Appliance Circuit - 1
Appliance Circuit - 2
Dedicated circuit Dedicated circuit
Article 220 - Dedicated Backup Panel Calculation Job Code
2140 S Broadway
Santa Ana, CA 92707
109R-140TOLE
Building Square Footage VA (watts)Amps
House 1122.00 3366 14.03
Total for Part #1:
2140 S Broadway
3/21/2025
Section 220.83 Existing Dwelling Unit
Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft:
Amps Box A (VA)
14.03 3366
Part #2 - Section 220.83 (B)(2),(3)a, b, c, d - Appliances and Dedicated Circuits:
Size in VA Size in VA
1500 N/A
3000 N/A
1000 N/A
600 N/A
1000 N/A
1600 N/A
5760 N/A
N/A N/A
N/A N/A
N/A Amps Box B (VA)
N/A 60.25 14460
Total VA from Parts #1 and #2 combined:Box A + Box B =17826
Total VA 17826
First 8,000 VA @ 100%8000 Remaining VA @ 40%
Remaining VA =9826 9826 x 40% =3930.4 VA
Adding First 8000 VA 8000 VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:11930.4 VA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:49.71 Amps
Part #3 - Section 220.83 (B) Heating and A/C loads:
*Combine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:0 VA
100% of all the Heating or A/C loads in Amps:0.00 A
VA Volts Amps
Parts #1 & #2 11930.4 240 49.71
Part #3 0 240 0.00
Total VA for all Parts:11,930
Totals Service/Feeder Load 49.71
#ESTAMP
Refrigerator(s)
Microwave(s)
Totals for Part #2:Pool Equipment
Dryer
Range
Oven
Cooktop
Amps
14.025
Job Code
109R-140TOLE
Totals from all Parts
Dedicated circuit
Total for Part #1:
Water Heater
House
Square Footage
1122
Article 220 - Service/Feeder calculation for (address):
2140 S Broadway
Santa Ana, CA 92707
Building VA (watts)
3366
Laundry
Appliance Circuit(s)
Dishwasher(s)
Disposal(s)
Dedicated circuit
2140 S Broadway
3/21/2025
Bus Rating:125
Main Rating:100
0%0%
Not Fed by other panels
Feeds: Panel 2 49.71
0.00
49.71
Bus Rating:225
Main Rating:100
100%100%
Itemized House and 240V Loads for Panel: (VA)
1500 1500
1500 1000
600 1000
1600 5760
Fed by: Panel 1
49.71
49.71
Panel 1 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Load Calc: (This Panel)
Total Load Calc:
Panel 2 of 2
Panel % of Sq.Ft:Panel % of 100% VA:
Laundry Appliance Circuit - 1
Load Calc: (This Panel)
Total Load Calc:
Appliance Circuit - 2 Dishwasher
Disposal Refrigerator
Microwave Dryer
2140 S Broadway
3/21/2025
City of Santa Ana,
SIGNATURE:___________________ DATE:__________
717 17th Street, Ste. 200 | Denver, CO 80202
I, Miguel Toledo, grant authorization to SUNRUN SOLAR to install Rooftop Mounted Solar
on my residence located at 2140 s Broadway , SANTA ANA, CA, 92707.
Docusign Envelope ID: B47231CB-9AD7-49FD-9D10-BD4C7209D56D
9/26/2024
2140 S Broadway
3/21/2025
Certificate Of Completion
Envelope Id: B47231CB9AD749FD9D10BD4C7209D56D Status: Completed
Subject: Complete with Docusign: Solar Authorization Letter 140TOLE.pdf
Source Envelope:
Document Pages: 1 Signatures: 1 Envelope Originator:
Certificate Pages: 5 Initials: 0 Courtney Ashley Tijing
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
225 Bush Street, Suite 1400
San Francisco, CA 94104
courtneyashley.tijing@sunrun.com
IP Address: 99.145.234.107
Record Tracking
Status: Original
9/26/2024 3:39:21 PM
Holder: Courtney Ashley Tijing
courtneyashley.tijing@sunrun.com
Location: DocuSign
Signer Events Signature Timestamp
Miguel Toledo
migueltoledo51@yahoo.com
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 76.32.191.144
Signed using mobile
Sent: 9/26/2024 3:39:46 PM
Viewed: 9/26/2024 3:54:50 PM
Signed: 9/26/2024 3:55:06 PM
Electronic Record and Signature Disclosure:
Accepted: 9/26/2024 3:54:50 PM
ID: 5b0c3a40-aa13-45e7-965a-bfdacb85492e
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 9/26/2024 3:39:46 PM
Certified Delivered Security Checked 9/26/2024 3:54:50 PM
Signing Complete Security Checked 9/26/2024 3:55:06 PM
Completed Security Checked 9/26/2024 3:55:06 PM
Payment Events Status Timestamps
Electronic Record and Signature Disclosure
2140 S Broadway
3/21/2025
CONSUMER DISCLOSURE
From time to time, Sunrun Inc. (we, us or Company) may be required by law to provide to you
certain written notices or disclosures. Described below are the terms and conditions for providing
to you such notices and disclosures electronically through the DocuSign, Inc. (DocuSign)
electronic signing system. PLEASE READ THE INFORMATION BELOW CAREFULLY
AND THOROUGHLY, AND IF YOU CAN ACCESS THIS INFORMATION
ELECTRONICALLY TO YOUR SATISFACTION AND AGREE TO THESE TERMS AND
CONDITIONS, PLEASE CONFIRM YOUR AGREEMENT BY CLICKING THE 'I AGREE'
BUTTON AT THE BOTTOM OF THIS DOCUMENT.
Getting paper copies
At any time, you may request from us a paper copy of any record provided or made available
electronically to you by us. You will have the ability to download and print documents we send
to you through the DocuSign system during and immediately after signing session and, if you
elect to create a DocuSign signer account, you may access them for thirty (30) days after such
documents are first sent to you. After such time, if you wish for us to send you paper copies of
any such documents from our office to you, please request delivery of such paper copies from us
by following the procedure described below.
Withdrawing your consent
If you decide to receive notices and disclosures from us electronically, you may at any time
change your mind and tell us that thereafter you want to receive required notices and disclosures
only in paper format. How you must inform us of your decision to receive future notices and
disclosure in paper format and withdraw your consent to receive notices and disclosures
electronically is described below.
Consequences of changing your mind
If you elect to receive required notices and disclosures only in paper format, it will slow the
speed at which we can complete certain steps in transactions with you and delivering services to
you because we will need first to send the required notices or disclosures to you in paper format,
and then wait until we receive back from you your acknowledgment of your receipt of such
paper notices or disclosures. To indicate to us that you are changing your mind, you must
withdraw your consent using the DocuSign ‘Withdraw Consent’ form on the signing page of a
DocuSign envelope instead of signing it. This will indicate to us that you have withdrawn your
consent to receive required notices and disclosures electronically from us and you will no longer
be able to use the DocuSign system to receive required notices and consents electronically from
us or to sign electronically documents from us.
All notices and disclosures will be sent to you electronically
Unless you tell us otherwise in accordance with the procedures described herein, we will provide
electronically to you through the DocuSign system all required notices, disclosures,
authorizations, acknowledgements, and other documents that are required to be provided or made
available to you during the course of our relationship with you. To reduce the chance of you
inadvertently not receiving any notice or disclosure, we prefer to provide all of the required
notices and disclosures to you by the same method and to the same address that you have given
us. Thus, you can receive all the disclosures and notices electronically or in paper format through
the paper mail delivery system. If you do not agree with this process, please let us know as
described below. Please also see the paragraph immediately above that describes the
consequences of your electing not to receive delivery of the notices and disclosures
electronically from us.
Electronic Record and Signature Disclosure created on: 8/7/2013 10:17:58 AM
Parties agreed to: Miguel Toledo 2140 S Broadway
3/21/2025
How to contact Sunrun Inc.:
You may contact us to let us know of your changes as to how we may contact you electronically,
to request paper copies of certain information from us, and to withdraw your prior consent to
receive notices and disclosures electronically as follows:
To contact us by email send messages to: customercare@sunrun.com
You may also contact us in writing at 45 Fremont Street, 32nd Floor, San Francisco, CA 94105
or by phone at 1-855-478-6786.
To advise Sunrun Inc. of your new e-mail address
To let us know of a change in your e-mail address where we should send notices and disclosures
electronically to you, you must send an email message to us at customercare@sunrun.com and in
the body of such request you must state: your previous e-mail address, your new e-mail
address. We do not require any other information from you to change your email address.
In addition, you must notify DocuSign, Inc. at 1-866-219-4318 to arrange for your new email
address to be reflected in your DocuSign account by following the process for changing e-mail in
the DocuSign system.
To request paper copies from Sunrun Inc.
To request delivery from us of paper copies of the notices and disclosures previously provided
by us to you electronically, you must contact us by (a) sending us an e-mail to
customercare@sunrun.com, (b) writing to us at Sunrun Inc, 45 Fremont Street, 32nd Floor, San
Francisco, CA 94105, or (c) calling us at 1-855-478-6786, and in connection with your request
you must state your e-mail address, full name, US Postal address, and telephone number.
To withdraw your consent with Sunrun Inc.
To inform us that you no longer want to receive future notices and disclosures in electronic
format you may:
i. decline to sign a document from within your DocuSign session, and on the subsequent
page, select the check-box indicating you wish to withdraw your consent, or you may;
ii. contact us by (a) sending us an email to customercare@sunrun.com, (b) writing to us
at Sunrun Inc., 45 Fremont Street, 32nd Floor, San Francisco, CA 94105, or (c) calling us
at 1-855-478-6786, and in connection with your request you must state your e-mail, full
name, US Postal Address, and telephone number. We do not need any other information
from you to withdraw consent.. The consequences of your withdrawing consent for
online documents will be that transactions may take a longer time to process..
Required hardware and software
Operating
Systems: Windows® 2000, Windows® XP, Windows Vista®; Mac OS® X
2140 S Broadway
3/21/2025
Browsers:
Final release versions of Internet Explorer® 6.0 or above (Windows only);
Mozilla Firefox 2.0 or above (Windows and Mac); Safari™ 3.0 or above
(Mac only)
PDF Reader: Acrobat® or similar software may be required to view and print PDF files
Screen
Resolution: 800 x 600 minimum
Enabled Security
Settings: Allow per session cookies
** These minimum requirements are subject to change. If these requirements change, you will be
asked to re-accept the disclosure. Pre-release (e.g. beta) versions of operating systems and
browsers are not supported.
Notices
Any notice or other communication to be made hereunder, even if otherwise required to be in
writing under other provisions of this Consent or any other documents or agreements that have
been provided to you in connection with this Consent, may alternatively be made in an electronic
record transmitted electronically to the electronic addresses provided by you. Any notice or other
communication made in electronic form will have the same legal effect and enforceability as if
made in non-electronic form.
Acknowledging your access and consent to receive materials electronically
To confirm to us that you can access this information electronically, which will be similar to
other electronic notices and disclosures that we will provide to you, please verify that you were
able to read this electronic disclosure and that you also were able to print on paper or
electronically save this page for your future reference and access or that you were able to e-mail
this disclosure and consent to an address where you will be able to print on paper or save it for
your future reference and access. Further, if you consent to receiving notices and disclosures
exclusively in electronic format on the terms and conditions described above, please let us know
by clicking the ‘I agree’ button below.
By checking the ‘I agree’ box, I confirm that:
I can access and read and have accessed, read and understood the terms of this
ELECTRONIC CONSENT TO ELECTRONIC RECEIPT OF ELECTRONIC
CONSUMER DISCLOSURES document; and
I can print on paper the disclosure or save or send the disclosure to a place where I can
print it, for future reference and access; and
Until or unless I notify Sunrun Inc. as described above, I consent to receive from
exclusively through electronic means all notices, disclosures, authorizations,
acknowledgements, and other documents that are required to be provided or made
available to me by Sunrun Inc. during the course of my relationship with you.
Entire Agreement Provision
This agreement and the consumer disclosure statement executed by the customer in conjunction
with and simultaneously with its review and acceptance of the terms set forth herein constitute
2140 S Broadway
3/21/2025
the entire agreement between the parties with respect to the subject matter hereof and supersede
any prior understandings, agreements, or representations by or between the parties, written or
oral, to the extent they relate in any way to the subject matter hereof.
2140 S Broadway
3/21/2025
STRUCTURAL CERTIFICATION REPORT
Roof-mounted Solar Panels
September 24, 2024
To: Sunrun Re: Miguel Toledo
1800 Ashton Blvd 2140 S Broadway
Lehi, UT 84043 Santa Ana, CA 92707
AHJ: Santa Ana (City), CA
Sunrun proposes to install new roof-mounted solar panels at this residence and asked Right Angle Engineering to review
the existing structure for suitability. This letter summarizes the methods that were used to survey, evaluate, and certify
the existing roof framing and the attachment of the new solar panels to it.
STRUCTURAL DESIGN
Building Code:California Residential Code 2022
Design Standards:ASCE 7-16
Snow:Ground: pg= 0.0 psf | Flat Roof: pf= 0.0 psf | Sloped Roof: ps= 0.0 psf
Wind:Ultimate Wind Speed = 96.0 mph | Exposure = C
Seismic:Risk Category = 2 | Seismic Design Category = A | Site Class = D
STRUCTURE
Field Technicians from Sunrun visited the site and observed the existing structure :
Array Name Panel Quantity Roof Framing Material Pitch
Array 1 7 2x4 Rafter| 24" o.c.Asphalt Shingles 21°
ANCHORAGE
The solar panel anchorage shall be installed according to the manufacturer's most current installation manual. The
attachment configuration should match the certified building plans. The solar panels should be mounted parallel (max 5
inches) to the roof surface.
Array Name Connection Type Fastener Max Anchorage Spacing
Array 1 SpeedSeal Deckfoot (into rafter)
(2) #14 SS screws into rafter
(2) #14 SS screws into deck
(1.5" embedment) into roof
substructure
72"
Installation Instructions
Solar panels and the equipment shall be installed per the manufacturer's installation specifications. Improper installation
will void this certification. If deviations from the approved structural plans occur, Right Angle Engineering must be
notified. Prior to installation, the installer should:
•Confirm that the existing structure matches the information provided in the site survey, the approved installation
plans and this certification.
•Identify discrepancies between this certification and the approved installation plans. If found, then this
certification shall govern.
•Identify structural elements that are dangerous (cracked, broken, excessive sag, signs of overstress, rot, decay,
fire, water). If found, installation shall cease until those elements are adequately abated and made to comply with
the referenced building code.
•Verify that both the existing structure and the solar addition has been permitted through the AHJ.
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 1 of 6
2140 S Broadway
3/21/2025
STRUCTURAL CERTIFICATION
I certify the addition of solar panels on the roof of this structure does not cause the structure to become unsafe or make
it generally less compliant with the life-safety requirements of the referenced building code. Based on the evaluation
methods described below, for the loads that exist at this site, the existing framing will safely support the new solar
panels if they are installed and attached correctly. Electrical design is not included in this certification.
Array Name Certification Method Retrofits
Array 1 Stress analysis California Residential code 324.4.1 None required
Regards,
09/24/2024
Robert D. Smythe, P.E.
Right Angle Engineering
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 2 of 6
2140 S Broadway
3/21/2025
Job Details
Roof Snow Load - ASCE 7-16
Ground Snow Load (pg)
Section 7.2 0.0 psf
Exposure Factor (Ce)
Table 7.3-1 0.9
Thermal Factor (Ct)
Table 7.3-2 1.1
Importance Factor (Is)
Table 1.5-2 1
Flat Roof Snow Load (pƒ)
Equation 7.3-1 0.0 psf
Non-Slippery Surface Slope Factor
(Cs) Figure 7.4-1 1
Slippery Surface Slope Factor (Cs)
Figure 7.4-1 0.82
Roof Snow Load
Equation 7.4-1 0.0 psf
Reduced Snow Load (Slippery
Surface)
Equation 7.4-1
0.0 psf
Design Criteria
Wind Speed (Vult)
Local Design Criteria 96.0mph
Exposure Category C
Risk Category 2
Mean Roof Height 20 ft
Roof Type Gable Roof
Building Type Enclosed
Roof Live Load
Existing Roof Live Load
ASCE 7-16 Table 4.3-1 20 psf
1Roof Dead Load
Asphalt Shingles 2.0 psf No Drywall 0.0 psf
5/8" Plywood Sheathing 2.0 psf Solar Panel Array 2.74 psf
Roof Framing 1.1 psf Dead Load Without Panels 6.3 psf
Insulation 1.2 psf
1Roof Dead Load is taken from the worst case scenario dead load from all arrays of the job in order to provide a more
conservative evaluation.
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 3 of 6
2140 S Broadway
3/21/2025
Array 1
Array Details
Roof Framing 2x4 Rafter DF No.2
Spacing 24.0"
Beam Span 9.5', 9.5'
Roof Pitch 21°
Solar Rails UR-40
Panel Quantity 7
Panel Array Area 151.45 ft²
Panel Orientation Portrait
Lag Screw Embedment 1.5"
Roof Attachment Type
SpeedSeal Deckfoot
(into rafter) (2) #14 SS
screws into rafter (2)
#14 SS screws into
deck
Shear Capacity
SnapnRack testing 460.0 lbs
Pullout Capacity
SnapnRack testing 829.0 lbs
Velocity Pressure
Equation 26.10-1 (Kz=0.9, Kht=1,
Kd=0.85, Ke=1.0)
15.61 psf
GCP Zones 1/2e 2n/2r
/3e 3r
GCp
Figure 30.3-(2A-5B)-1.48 -2.13 -2.4
Design Pressure Up [psf]
Equation 29.4-7 ga=0.53 gE=1.0,-16 -17.7 -19.9
Factored Design Pressure
Up [psf]
ASD LC (.6D + .6W)
-8.1 -9.1 -10.4
Exposed Design Pressure
Up [psf]
ga=0.53 gE=1.5,
-18.5 -26.6 -29.9
Design Pressure Down
[psf]16 16 16
Tributary Area [ft2]102.
8 91.2 79.5
Maximum Connection
Spacing [in]394 350 305
Maximum Rail Span [in]80 80 80
Maximum Rail Cantilever
[in]24 24 24
Design Connection
Spacing [in]
*Adjusted
72 72 72
Design Connection
Spacing (exposed) [in]72 72 72
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 4 of 6
2140 S Broadway
3/21/2025
Design Ratio
Member ID Axial Momentz Sheary Combined Slenderness Deflection Status
1 0.007 0.589 0.228 0.588 0.035 0.557 Pass
2 0.003 0.082 0.059 0.085 0.035 0.417 Pass
Member Design Capacity (LRFD)
Member ID FI
b(ksi)FI
t(ksi)FI
v(ksi)FI
c(ksi)FI
cp(ksi)EI(ksi)Emin
I(ksi)
1 2.681 1.49 0.311 2.683 0.939 1600.0 1041.216
2 2.681 1.49 0.311 2.683 0.939 1600.0 1041.216
Node Coordinates
ID X Coordinate Y Coordinate
1 0.000 0.000
2 9.500 3.647
3 19.000 7.293
4 -1.500 -0.576
Members
ID Node A Node B Section Node A Fixity Node B Fixity Length
1 1 3 1 FFFFFF FFFFFF 20.352
2 4 1 1 FFFFFF FFFFFF 1.607
Supports
ID Node ID Restraint Code
1 2 RFFRRR
2 3 RFFRRR
3 1 FFFFFR
Materials
ID Name Young's Modulus Density Poisson's Ratio
1 NDS - Table 4A - DOUGLAS FIR-LARCH - No.2- 2in & wider 1600.000 33.308 0.400
Sections
ID Name Depth Width Shear Area Z Shear Area Y Torsion Radius
1 1.5 x 3.5 4.000 1.500 5.000 5.000 1.463
ID Centroid Y Centroid Z Area Y-Axis Mol Z-Axis Mol Torsion Constant
1 0.750 2.000 6.000 1.125 8.000 3.437
Point Loads
ID Load Group Member Position %Y Magnitude
1 Solar-Snow 1 2.632%0.000
2 Solar 1 2.632%-0.026
3 Solar-Snow 1 33.374%0.000
4 Solar 1 33.374%-0.026
Member Distributed Loads
ID Load Group Start Position End Position Member Y Magnitude
1 Dead Load 0.000%100.000%2 -0.013
2 Dead Load 0.000%100.000%1 -0.013
3 Roof Live Load 0.000%66.667%2 -0.032
4 Roof Live Load 58.853%100.000%1 -0.032
5 Snow Load 0.000%66.667%2 0.000
6 Snow Load 58.853%100.000%1 0.000
Load Combinations
ID Name Dead Load Factor Snow Load Factor Solar Factor Solar-Snow Factor
Roof Live Load
Factor
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 5 of 6
2140 S Broadway
3/21/2025
1 1. 1.4D 1.4 0 1.4 0 0
2 3. 1.2D + 1.6Lr 1.2 0 1.2 0 1.6
3 3. 1.2D + 1.6S 1.2 1.6 1.2 1.6 0
4 4. service loads A 0 1 0 1 0
5 5. service loads B 0 0 0 0 1
Internal Member Forces and Moments
Member Axial Force (Min/Max)
Shear Force Y
(Min/Max)
Shear Force Z
(Min/Max)
Torsion (Min/Max)
Bending Moment Y
(Min/Max)
Bending Moment Z
(Min/Max)
1 -0.100 / 0.109 -0.261 / 0.283 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.473 / 0.526
2 -0.028 / 0.000 -0.074 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.073 / 0.000
Member Displacement Span Check
Member Length Max Relative Displacement Span Method 1
1 20.352 0.378 L/323
2 1.607 0.089 L/216
Member Stresses
Member
Axial Stress
(Min/Max)
Torsion Stress
(Min/Max)
Shear Stress Y
(Min/Max)
Shear Stress Z
(Min/Max)
Top Bending Moment
Z (Min/Max)
Bottom Bending
Moment Z (Min/Max)
1 -0.017 / 0.018 0.000 / 0.000 -0.065 / 0.071 -0.000 / -0.000 -1.419 / 1.578 -1.578 / 1.419
2 -0.005 / 0.000 0.000 / 0.000 -0.019 / 0.000 -0.000 / -0.000 -0.219 / 0.000 0.000 / 0.219
757 Technology Ave, F31 | Orem, UT 84097 | 925-787-3067 | www.rightangleeng.com | Page 6 of 6
2140 S Broadway
3/21/2025
Rev: 8/29/19
SOL-01 CBC 2016
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
SUNRUN
CA CL #750184
2140 S Broadway, Santa Ana, CA, 92707
caitlyn h
3854005019
oc_permits@sunrun.com
2140 S Broadway
3/21/2025
PLPLPL PL PLPL PL PL PL PLPAGE
REV: J 3/29/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SITE PLAN
PV-2.0
#SSTAMPSP
#ESTAMPSP
ARRAY
PITCH
PV AREA
(SQFT)
AR-01 21° 147.2
TRUE
AZIM
MAG
AZIM
77° 89°
NOTES:
RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
TOTAL ROOF SURFACE AREA: 1837 SQFT.
TOTAL PV ARRAY AREA(E+N): 422.51 SQ FT.
PERCENTAGE PV COVERAGE:
(TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
AREA)(E+N) * 100 = 23%
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS
IN ACCORDANCE WITH R328.4. ESS UNITS SHALL BE
SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET
EXCEPT WHERE SMALLER SEPARATION DISTANCES ARE
DOCUMENTED TO BE ADEQUATE BASED ON LARGE/SCALE
FIRE TESTING.
SITE PLAN - SCALE = 0'-0 3/64" = 1'-0"
POWERWALL ENERGY
STORAGE SYSTEM (ESS)
BG BACKUP GATEWAY
GP GENERATION PANEL
ELECTRIC VEHICLE
SUPPLY EQUPMENTEV
MAIN PANEL
INVERTER(S)
AC DISCONNECT(S)
DC DISCONNECT(S)
SUNRUN METER
DEDICATED PV METER
SERVICE ENTRANCE
INTERIOR EQUIPMENT
SHOWN AS DASHED
SE
MP
SM
PM
INV
AC
DC
SUB-PANEL SP
CB IQ COMBINER BOX
METER ADAPTERMA
GROUNDING
ELECTRODE
ENERGY STORAGE
SYSTEM
BP BACKUP LOADS PANEL
BI BACKUP INTERFACE 1 COMMUNICATION
WIRESAM
MD MICROGRID
INTERCONNECT DEVICE
ACREL METER
SOLAREDGE METER SEM PV LOAD CENTER LC
LEGEND
SCALE: NTS
NOTE: NOT ALL ITEMS IN LEGEND
WILL APPEAR IN SITE PLAN
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
EXTERNAL RAPID
SHUTDOWN SWITCH
RSD
MD
(E) RESIDENCE
(N) ARRAY AR-01
FIRE SETBACKS
(18" TYP)
ROOF PATHWAYS
(3' TYP)
SE
MP
(E) PV ARRAY(TYP)
(E) PV EQUIPMENT
S BROADWAYROOF PATHWAYS
(3' TYP)
ACPM
INVAC
(E) GATE(TYP)
(E) FENCE(TYP)
(E) DETACHED GARAGE
STRUCTURE (TYP.)
(E) DETACHED SHED
STRUCTURE (TYP.)
(E) CHIMNEY
AA A A B BB 125'-9"
50'-2"
125'-9"
50'-10"
20'-6"
4'-5"
2'-9"
1'-7"
3'-8"
5'
2'-6"
10'-3"
20'-7"
13'-7"
8'-9"
(E) DETACHED
EQUIPMENT AWNING
STRUCTURE (TYP.)(E) ROOF PLANE
ATTACHED TO STRUCTURE
(E) DETACHED GARAGE
STRUCTURE ROOF PLANE
ATTACHED TO GARAGE
STRUCTURE (TYP.)
SP
(E) SUBPANEL
LC
J
J
Revision to 20184760 (issued on 3/21/25)
Revision 1 #20185638
APPROVALS:
ELECT - M. Smith
2140 S Broadway -
REV 15/5/2025
PAGE
REV: J 3/29/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
PV-2.1
EXTERIOR NORTH WALL
ACD
CHIMNEY
SITE PLAN - SCALE = NTS
ESS ELEVATION VIEW
ESS ELEVATION VIEW
PW3 W/ EXPACK STACKED
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4.
ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT
WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON
LARGE/SCALE FIRE TESTING.
WINDOW
3' MIN
WINDOW
3' MIN
MAIN SERVICE PANEL
WINDOW
J
I V I LREGISTERED PR O F ESSIONAL E
N
G
I
NEERS
T
ATE OF C A L IFORNIAROBER T SMYT
H
EC56136
EXP. 12/31/26
2140 S Broadway -
REV 15/5/2025
(N) TESLA REMOTE M ETER SOLAR CU RRENT TRANSFO RMERS
PAGE
REV: J 3/29/2025
MIGUEL TOLEDO
2140 S BROADWAY, SANTA ANA,
CA, 92707
PROJECT NUMBER:
109R-140TOLE
SHEET
DESIGNER:
AL AMEEN V H
CUSTOMER RESIDENCE:
TEL. (714) 272-5451
APN: 015-082-22
(415) 580-6920 ex3
Template_version_v5_2024 02 28
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
SIGNAGE
PV-5.0
#ESTAMP
ENERGY STORAGE SYSTEM
PREMISES WIRING MAY REMAIN
ENERGIZED AFTER LOSS OF
UTILITY POWER
CAUTION!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C)
ENERGY STORAGE SYSTEM
DISCONNECT
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
61.5 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
POWER SOURCE OUTPUT CONNECTION
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
CEC 2022: 705.12(B)(3)(2)
NOTES AND SPECIFICATIONS:
SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF
THE CEC 2022 ARTICLE 110.21(B), UNLESS SPECIFIC
INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF
REQUESTED BY THE LOCAL AHJ.
SIGNS AND LABELS SHALL ADEQUATELY WARN OF
HAZARDS USING EFFECTIVE WORDS, COLORS AND
SYMBOLS.
LABELS SHALL BE PERMANENTLY AFFIXED TO THE
EQUIPMENT OR WIRING METHOD AND SHALL NOT BE
HAND WRITTEN.
LABEL SHALL BE OF SUFFICIENT DURABILITY TO
WITHSTAND THE ENVIRONMENT INVOLVED.
SIGNS AND LABELS SHALL COMPLY WITH ANSI
Z535.4-2011, PRODUCT SAFETY SIGNS AND LABELS,
UNLESS OTHERWISE SPECIFIED.
DO NOT COVER EXISTING MANUFACTURER LABELS.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
4"
3"
ELECTRICAL SHOCK HAZARD
WARNING
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S),
AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC
2022: 690.13(B)
!
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:
690.31(D)(2)CAUTION
2140 S BROADWAY, SANTA ANA, CA, 92707
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
MULTIPLE SOURCES OF POWER
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC
2022: 705.12(C)
INVERTER 1
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
SOLAR PANELS ON ROOF
SERVICE ENTRANCE AND
TESLA BACKUP SWITCH
INVERTER + BATTERY AND EXPACK
(EXT)- PCS CONTROLLED
AC DISCONNECT
(E) PV EQUIPMENT
RAPID SHUTDOWN DISCONNECT LOCATION
(EXISTING SYSTEM AC DISCONNECT)
(E) PV ARRAY (TYP.)
PV SYSTEM(S) ARE EQUIPPED WITH RAPID
SHUTDOWN DEVICE(S)
(E) SUB PANEL
(N) LOAD CENTER
J
2140 S Broadway -
REV 15/5/2025