HomeMy WebLinkAbout2614 A Everglade St - 101118489 & 20182273 - PlanE1
SHEET NUMBER:SEMPER SOLARIS1805 JOHN TOWERS AVEEL CAJON, CA 92020C-10 LIC # 978152Lic. Holder Digitally StampedPROJECT FOR: PROPOSED
DRAWN BY:
DATE:
(DC) kW:
PROJECT #:John AlmondEVOLUTION
11/14/2023
85942
8.400KAREN N FLORES & ORLANDO MACIASSANTA ANA CA 92704 2614 S EVERGLADE ST(714) 824-1142 APN - 41406114SOLAR PHOTOVOLTAIC SYSTEM SIZE: 8.400 kW DC PVMAIN LINE: 619-357-4142ABBREVIATIONS
AMPERE
ALTERNATING CURRENT
AUTHORITY HAVING
JURISDICTION
BUILDING
CONCRETE
COMBINER BOX
CALIFORNIA ELECTRICAL
CODE
COPPER
DISTRIBUTION PANEL
DIRECT CURRENT
EQUIPMENT GROUNDING
CONDUCTOR
(EXISTING)
FIELD VERIFIED
GALVANIZED
GROUNDING ELECTRODE
CONDUCTOR
GROUND
HOT DIPPED GALVANIZED
CURRENT
CURRENT AT MAX POWER
INVERTER
SHORT CIRCUIT CURRENT
KILOVOLT AMPERE
KILOWATT
LOAD BEARING WALL
MINIMUM
MAIN CIRCUIT BREAKER
MAIN SERVICE PANEL
(NEW)
NEMA 3R, RAINTIGHT
OUTSIDE RATED
NATIONAL ELECTRICAL
CODE
NOT TO SCALE
ON CENTER
OVERCURRENT PROTECTION
DEVICE
POLES -BREAKER POLES-
PROPERTY LINES
PHOTOVOLTAIC
POLYVINYL CHLORIDE
ROOF RAFTER
SOLID BARE COPPER
SOLAR PLANE
SUBPANEL
SCHEDULE
STAINLESS STEEL
PRACTICAL TESTING
CONDITIONS
SOLAR WATER HEATER
TYPICAL
UNLESS NOTED OTHERWISE
VOLT
VOLTAGE AT MAX POWER
VOLTAGE AT OPEN CIRCUIT
WATT
A
AC
AHJ
BLDG
CONC
CB
CEC
CU
DP
DC
EGC
(E)
FV
GALV
GEC
GND
HDG
I
Imp
INVT
Isc
kVA
kW
LBW
MIN.
MCB
MSP
(N)
N3R
NEC
NTS
OC
OCPD
P
PL
PV
PVC
RR
SBC
SP
SPL
SCH
SS
PTC
SWH
TYP
UNO
V
Vmp
Voc
W
SHEET INDEX
01- E1 COVER SHEET
APPLICABLE CODES AND STANDARDS
VICINITY MAP
N
·2022 CBC
·2022 CRC
·2022 CEC
·2022 CMC
·2022 CPC
·2022 CFC
·2022 CEBC
· 2022 BUILDING ENERGY
EFFICIENCY STANDARDS
· AUTHORITY HAVING
JURISDICTION
· CURRENT LOCAL FIRE
CODE
1. EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, VENTILATIONS INTAKE AIR OPENINGS SHALL NOT BE
COVERED BY THE SOLAR PHOTOVOLTAIC SYSTEM.
2. EQUIPMENT. INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AC PHOTOVOLTAIC
MODULES, SOURCE-CIRCUIT COMBINERS, AND CHARGE CONTROLLERS INTENDED FOR USE IN PHOTOVOLTAIC POWER
SYSTEMS SHALL BE IDENTIFIED AND LISTED FOR THE APPLICATION. [CEC 690.4(B)]
3. ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND NON
ROOF SWITCHES. ROOF SWITCHES TO BE NEMA 4 RATED.
4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH CEC ARTICLE 250.
5. PROTECTION DEVICES FOR PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS ALSO CONNECTED TO SOURCES HAVING
SIGNIFICANTLY HIGHER CURRENT AVAILABILITY (E.G., PARALLEL STRINGS OF MODULES, UTILITY POWER), SHALL BE
PROTECTED AT THE SOURCE FROM OVERCURRENT. [CEC 690.9(A)]
6. PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION THAT
CONTROLS SPECIFIC CONDUCTORS. [CEC 690.12]
7. THE UTILITY INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED
ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL REMAIN
IN THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED.
[CEC 705.40]
8. ALL CONDUCTOR EXPOSED TO WEATHER SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT. [CEC
310.10(D)(1)]
9. THE MODULE CONDUCTORS MUST BE TYPE USE-2 OR LISTED FOR PHOTOVOLTAIC (PV) WIRE. [CEC 690.31(C)]
10. ALL CONDUCTORS SHALL BE MARKED ON EACH END FOR UNIQUE IDENTIFICATION.
11. AN INSULATED GROUNDED CONDUCTOR OF 6 AWG OR SMALLER SHALL BE IDENTIFIED AS A CONTINUOUS WHITE
FINISH. [CEC 200.6]
12. THE OUTPUT OF AN INTERCONNECTED ELECTRICAL POWER SOURCE SHALL BE PERMITTED TO BE CONNECTED TO THE
LOAD SIDE. INTERCONNECTING PROVISIONS FOR OTHER POWER SOURCES SHALL COMPLY WITH 705.12(B)(1)
THROUGH 705.12(B)(3)
13. EACH SOURCE INTERCONNECTION OF ONE OR MORE POWER SOURCES INSTALLED IN ONE SYSTEM SHALL BE MADE AT
A DEDICATED CIRCUIT BREAKER OR FUSIBLE DISCONNECTING MEANS. [CEC 705.12(A)]
14. THE SUM OF THE AMPERE RATING OF THE OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO THE BUSBAR OR
CONDUCTOR SHALL NOT EXCEED 120% OF THE RATING OF BUSBAR OR CONDUCTOR. [CEC 705.12(B)(3)(2)]
15. A CONNECTION AT EITHER END, BUT NOT BOTH ENDS, OF A CENTER-FED PANEL BOARD IN DWELLINGS SHALL BE PERMITTED WHERE
THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE
PROTECTING THE BUSBAR DOES NOT EXCEED 120 PERCENT OF THE CURRENT RATING OF THE BUSBAR. [CEC 705.12(B)(3)(4)]
16. EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUS BAR OR CONDUCTOR
SHALL BE MARKED TO INDICATE THE PRESENCE OF ALL SOURCES. [CEC 705.12(C)]
17. CIRCUIT BREAKER, IF BACKFED, SHALL BE SUITABLE FOR SUCH OPERATION. [CEC 705.12(D)]
18. TO MINIMIZE OVERHEATING OF THE BUSBAR IN PANELBOARD, THE PANELBOARD MAIN CIRCUIT BREAKER AND THE PV
POWER SOURCE CIRCUIT BREAKER SHALL BE PHYSICALLY LOCATED AT THE OPPOSITE END OF THE BUSBAR.
19. ALL THE CEC REQUIRED WARNING SIGNS, MARKINGS, AND LABELS SHALL BE POSTED ON EQUIPMENT AND
DISCONNECTS PRIOR TO ANY INSPECTIONS TO BE PERFORMED BY THE BUILDING DEPARTMENT INSPECTOR.
20. WHERE PV SYSTEM DC CIRCUIT'S RUN INSIDE A BUILDING, THEY SHALL BE CONTAINED IN METAL RACEWAYS TYPE MC
METAL CLAD CABLE OR METAL ENCLOSURES FROM POINT OF PENETRATION OF THE SURFACE OF THE BUILDING TO THE
FIRST READILY ACCESSIBLE DISCONNECTING MEANS. [CEC 690.31(D)]
21. FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR CONNECTOR
THAT ARE IS IN ACCORDANCE WITH CEC 110.14.
22. CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND
OPERATING AT OVER 30V DC OR 15V AC SHALL REQUIRE TOOL TO OPEN AND MARKED "DO NOT DISCONNECT UNDER
LOAD" OR "NOT FOR CURRENT INTERRUPTING". [CEC 690.33(C) & (D)]
23. EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 6AWG SHALL BE PROTECTED FROM PHYSICAL
DAMAGE BY A RACEWAY OR CABLE ARMOR. [CEC 250.120(C)]
24. EQUIPMENT GROUNDING CONDUCTOR FOR PV SYSTEM CIRCUITS SHALL BE SIZED IN ACCORDANCE WITH 250.122.
[CEC 690.45]
25. GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE INSTALLED IN ONE CONTINUOUS LENGTH WITHOUT A SPLICE OR
JOINT. IF NECESSARY, SPLICES OR CONNECTIONS SHALL BE MADE AS PERMITTED. [CEC 250.64(C)]
26. ALL SMOKE ALARMS, CARBON MONOXIDE ALARMS AND AUDIBLE NOTIFICATION DEVICES SHALL BE LISTED AND
LABELED IN ACCORDANCE WITH UL 217 AND UL 2034. THEY WILL BE INSTALLED IN ACCORDANCE WITH NFPA 72 AND
NFPA 720. [CRC 2019 R314 & R315]
27. SMOKE ALARMS AND CARBON MONOXIDE ALARMS WILL BE RETROFITTED INTO THE EXISTING DWELLING. THESE
SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH
FLOOR OF THE HOUSE. CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED OUTSIDE EACH BEDROOM
AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. THESE ALARMS MAY BE SOLELY BATTERY OPERATED IF THE
PHOTOVOLTAIC PROJECT DOES NOT INVOLVE THE REMOVAL OF INTERIOR WALL AND CEILING FINISHES INSIDE THE
HOME, OTHERWISE, THE ALARMS MUST BE HARD WIRED AND INTERCONNECTED.
GENERAL NOTES
*ALL WORK TO COMPLY WITH ABOVE CODES
* OCCUPANCY TYPE: R-3
* CONSTRUCTION TYPE: TYPE V-B
* UNSPRINKLERED
DWELLING INFO
02- E2 SITE PLAN
06- E7 SINGLE LINE DIAGRAM
07- E8 ELECTRICAL NOTES
04- E5 ROOF PLAN
05- E6 ATTACHMENT DETAIL
SCOPE OF WORK:
-
-
-
-
21
-
-
-
(N) INVERTER(S)
(N) SOLAR MODULE(S)
- ENPHASE IQ8M-72-2-US
- SILFAB SIL-400 HC+
21
1 125A ENPHASE IQ COMBINER 4/4C
1 200A/200A NCF
1 BRNSURGE
(N) AC COMBINER(S)
(N) MAIN SERVICE PANEL
MSP IS UPGRADED TO 200A/200A NCF.
(N) SURGE PROTECTION DEVICE
03- E3 PROPERTY PLAN
08- E9 SIGNAGE
09- E9.1 SIGNAGE
10- JHA
The scope of the plans is for the installation of the solar photovoltaic system
only and the approval is subject to compliance with all applicable city and
state codes and regulations regarding construction. The approval of the plans
does not constitute any certification of the accuracy, completeness, or
building permit status of the existing buildings and structures as shown.
Bldg# 101118489
Elec# 20182273
2614 S Everglade
St3/18/2024
A
C
C
E
S
S
P
A
TH
3'ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"GASMSPACCACDEXISTINGDRIVEWAYWORKING CLEARANCE3'E2SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:SITE PLANN1/8" = 1'-0"LEGEND(N) 200A BUS NCF MSP(N) 200A/2P MAIN BREAKER(N) 40A/2P PV BREAKER FEEDING(N) 60A SINGLE VISIBLY OPEN AND LOCKABLEAC DISCONNECT 240V NEMA-3RSERVICE POINT UTILITY METERING.MSPLALADDER ACCESSGAS(E) GAS RISER( ALL NEW EQUIPMENTS TO BE PLACED 3FEET AWAY FROM GAS MAIN )ACC(N) 125A ENPHASE IQ COMBINER 4/4CWITH ENVOY IQ, CELL MODEM, &WIRELESS COMMUNICATIONS KIT(N) 60A SINGLE VISIBLY OPEN AND LOCKABLEAC DISCONNECT 240V NEMA-3R POC FOR(N) 125A ENPHASE IQ COMBINER 4/4CACD21 (N) 400W SILFAB SIL-400 HC+ SOLARMODULES (FLUSH MOUNT)EACH WITH A (N) ENPHASE IQ8M-72-2-USMICRO-INVERTERSANTA ANA CA 927042614 S EVERGLADE STCUSTOMER ADDRESS -ALL EQUIPMENT IS INSTALLED WITHIN A6-INCH WORKING CLEARANCE WITHRESPECT TO MSP.LOAD SIDE INTERCONNECTION.2614 S EvergladeSt3/18/2024
AC
C
E
S
S
PA
TH3'ACCESS PATH18"ACCESS PATH18"ACCE
S
S
PA
TH18"AC
C
E
S
S
PA
TH
18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACC
E
S
S
P
A
T
H18"A
C
C
E
S
S
P
A
T
H
18"ACCESS PATH18"ACCESS PATH18"GASMSPACCACDEXISTINGPOOL
EXISTING
DRIVEWAY
FRONT OF
RESIDENCE EXISTINGHOUSE99'-6"67'-3"99'-6"67'-3"
S EVERGLADE ST22'6'-5"
6'-1"13'-1"E3SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:PROPERTY PLANN3/32" = 1'-0"(N) PROPOSED SOLAR PANEL(E) EXISTING PATIO(E) FENCE(E) PROPERTY LINE(E) GATE2614 S EvergladeSt3/18/2024
A
C
C
E
S
S
P
A
T
H
3'ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PAT
H
18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACCESS PATH18"ACCESS PA
T
H
18"ACCESS PATH18"ACCESS PATH18"GASMSPACCRP1RP2RP3RP4E5SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:ROOF PLANN1/8" = 1'-0"NEW PV CONDUIT TO BE RUN UNDER ATTIC WHENEVER POSSIBLE.ANY PROPOSED CONDUIT RUN SUBJECT TO CHANGE BY INSTALLER.45 ATTACHMENTS INSTALLED @ 72" O.C. MAX. (TYP.)FRONT OF RESIDENCE PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65233.192"X6"24"COMP.SHINGLE90°21°1PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65326.492"X6"24"COMP.SHINGLE180°21°2PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65223.062"X6"24"COMP.SHINGLE180°21°3PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.127.98259.942"X6"24"COMP.SHINGLE270°21°42614 S EvergladeSt3/18/2024
(N) MODULE(E) COMPOSITIONSHINGLE(E) ROOF DECKING(E) RAFTER, SEE E5FOR DETAIL(N) PEGASUSMULTI CLAMP(N) PEGASUS RAIL(N) PEGASUSDOVETAIL T-BOLT(N) PEGASUS L-FOOT(N) 5/16" x 4.5" PEGASUS LAG BOLTMIN 2.5" EMBEDMENT(N) PEGASUS COMPMOUNT FLASHINGE6SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142ATTACHMENT DETAIL2614 S EvergladeSt3/18/2024
LALA GASMSPACCJHASHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142NEAREST URGENT CAREVICINITY MAPDISTANCEADDRESSNAMECONDITIONSNCREW MEMBERCREW LEADCREW MEMBERCREW MEMBERROPE REACHLADDER ACCESSCONESEXCLUSION ZONEJHA LEGENDANCHOR POINTSNTHIS PAGE TO BE COMPLETED BY INSTALLATION CREW2614 S EvergladeSt3/18/2024
(N) 60ASINGLE VISIBLYOPEN & LOCKABLE,AC DISCONNECT240V NEMA-3RGEnphase IQ Gateway(N) 125A ENPHASE IQCOMBINER 4/4C NEMA-3RX-IQ-AM1-240-4/4C[CRD-PCS NEM) 240VREVENUE-GRADEPRODUCTION METERINGFACTORY INSTALLEDenphaseENERGY(N)20A/2P(N)15A/2PEACH WITH ANENPHASE IQ8M-72-2-USMICROINVERTERAC(N)J-BOXG1 BRANCH OFMODULES11SOURCE CIRCUIT #1Isc = 14.85 AENPHASE Q CABLE2-#121-#6 GRNDOPEN AIR(N)20A/2PEACH WITH ANENPHASE IQ8M-72-2-USMICROINVERTERAC(N)J-BOXG1 BRANCH OFMODULES10SOURCE CIRCUIT #2Isc = 13.5 ATHWN-23-#101-#8 GRND3/4" EMT CONDUITTHWN-23-#81-#8 GRND3/4" EMT CONDUITMAIN SERVICE PANEL, 240VGROUNDING ELECTRODE &AUXILIARY GROUNDINGELECTRODE AS NEEDED PERCEC 690.47 (6 FEET APART)LLLLGND
N LOADS (E) A TOP FEDMETER #222013-028556 (N)200200A/2P(N)(N)40A/2PE7SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142 UTILITY COMPANY:MSP VOLTAGE:MSP GROUND:SERV. TYPE:SERVICE INFOSCE120/240UNDERGROUND(N) ROD2% Avg. 1"MINASHRAE AMBIENT TEMPERATURE SPECS° C° CHigh TempEXTREMEDISTANCEABOVE ROOFNO TEMP ADDERPER 310.15(B)(2)312BUSBARMAINBREAKERMAXPV OCP( 200A x 1.2 ) - 200A = 40ACEC705.12(B)(3)(2)INTERCONNECTION METHOD PER 705.12(B)(3)(2):WHERE TWO SOURCES, ONE A PRIMARY POWER SOURCE AND THE OTHERANOTHER POWER SOURCE, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THATCONTAINS LOADS, THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUTCIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTINGTHE BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR.MSP IS UPGRADED TO 200A/200A NCF.(N)BRNSURGE SURGE PROTECTOR - COMPATIBLE WITH EATON, GE,SIEMENS, CROUSE HINDS PANELBOARDS2614 S EvergladeSt3/18/2024
ELECTRICAL NOTES:1)ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH CODE AND THEMANUFACTURER’S INSTALLATION INSTRUCTIONS.2)ALL PV EQUIPMENT SHALL BE LISTED BY A RECOGNIZED TESTED LAB.3)NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM.4)WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION,BREAKER SHALL NOT READ LINE AND LOAD.5)WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THEBREAKER SHALL BE INSTALLED AT THE OPPOSITE END OF THE BUS BAR OF THEMAIN BREAKER.6)WORKING SPACE FOR EQUIPMENT OPERATING AT 1000 VOLTS, NOMINAL, OR LESSTO GROUND AND LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING,OR MAINTENANCE WHILE ENERGIZED SHALL COMPLY WITH [CEC 110.26(A)]7)ALL EXTERIOR CONDUITS, FITTINGS AND BOXES SHALL BE RAIN-TIGHT ANDAPPROVED FOR USE IN WET LOCATIONS PER [CEC 314.15].8)ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLYCONTINUOUS.9)PV EQUIPMENT, SYSTEMS AND ALL ASSOCIATED WIRING AND INTERCONNECTIONSSHALL ONLY BE INSTALLED BY QUALIFIED PERSONS. [CEC 690.4 (C)].10)THE PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED.THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATED COLORCODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS. [CEC690.31(B)(1)]11)ADEQUATE SPACING MUST BE MAINTAINED BETWEEN ANY PLUMBING SEWERVENTS EXTENDING THROUGH THE ROOF AND THE UNDERSIDE OF THEPHOTOVOLTAIC PANELS (6" MINIMUM RECOMMENDED).E8SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142
2614 S EvergladeSt3/18/2024
E9SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142MARKING IS REQUIRED ON ALL INTERIOR ANDEXTERIOR DC PV CONDUIT, RACEWAYS, ENCLOSURES,CABLE ASSEMBLIES, AND JUNCTION BOXES TO ALERTTHE FIRE SERVICE TO AVOID CUTTING THEM. MARKINGSHALL BE PLACED EVERY 10 FEET, AT TURNS ANDABOVE AND/OR BELOW PENETRATIONS, AND AT ALL PVCOMBINER AND JUNCTION BOXES. [CEC 690.31(D)(2)]REFLECTIVE WEATHER RESISTANT MATERIAL SUITABLEFOR THE ENVIRONMENT (DURABLE ADHESIVEMATERIALS MUST MEET THIS REQUIREMENT)MARKING CONTENT AND FORMATPER [ CEC 110.21(B)] WITH REFERENCETO ANSI Z535.4-2011-BACKGROUND PER ANSI Z535.4-2011-LETTERING PER ANSI Z535.4-2011-MINIMUM 3/8” LETTER HEIGHT-ALL CAPITAL LETTERS-ARIAL OR SIMILAR FONT, NON BOLDMARKING PV CIRCUIT11314483213121195PV COMBINER(IF USED)FOR ILLUSTRATION ONLY (NOT ACTUAL MSP)MAIN SERVICE PANELAC DISCONNECT(IF USED)LABEL LEGEND9112344589131314551515CEC 690.56(C)CEC 705.12(C) & CEC 690.59CEC 690.13(B)CEC 690.13(B)CEC 690.54CEC 705.12(B)(3)(2)CEC 110.27(C)CEC 706.15(C)(4)CEC 690.13(B)CEC 705.12(B)(3)(3)CEC 705.12(D)CEC 690.56(C)(2)2614 S EvergladeSt3/18/2024
LALAGASMSPACCCAUTIONPOWER TO THIS SERVICE IS ALSOSUPPLIED FROM THE FOLLOWINGSOURCES WITH DISCONNECTSLOCATED AS SHOWN:PLACARD RIVETED TO THE MAIN SERVICE PANELE9.1SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142NOMINAL OPERATING AC VOLTAGE: BBBBBBBB NOMINAL OPERATING AC FREQUENCY:BBBBBBBB MAXIMUM AC POWER: BBBBBBBB MAXIMUM AC CURRENT: BBBBBBBB MAX OVERCURRENT DEVICE RATINGFOR AC MODULE PROTECTION: BBBBBBBB 240V60.0Hz6825W28.35A40ASOLAR LOAD CENTERNO ADDITIONAL LOADS ALLOWEDNPHOTOVOLTAIC POWER SOURCEOPERATING AC VOLTAGE: BBBBB VMAXIMUM OPERATING AC OUTPUTCURRENT: BBBBBB AMPSLABEL FOR MAIN SERVICE PANEL COVER24035.43PHOTOVOLTAIC AC DISCONNECTRATED AC OUTPUT CURRENT: BBBBB ANOMINAL OPERATING AC VOLTAGE:BBBBB V35.43240PV DISCONNECTAC DISCONNECT(YOU ARE HERE)SERVICE POINT & UTILITYMETERING & PV DISCONNECTSOLAR ARRAYNO RSD THESEMODSSOUTH EVERGLADE STREETSANTA ANA CA 927042614 S EVERGLADE ST2614 S EvergladeSt3/18/2024
E1
SHEET NUMBER:SEMPER SOLARIS1805 JOHN TOWERS AVEEL CAJON, CA 92020C-10 LIC # 978152Lic. Holder Digitally StampedPROJECT FOR: PROPOSED
DRAWN BY:
DATE:
(DC) kW:
PROJECT #:John AlmondEVOLUTION
11/14/2023
85942
8.400KAREN N FLORES & ORLANDO MACIASSANTA ANA CA 92704 2614 S EVERGLADE ST(714) 824-1142 APN - 41406114SOLAR PHOTOVOLTAIC SYSTEM SIZE: 8.400 kW DC PVMAIN LINE: 619-357-4142ABBREVIATIONS
AMPERE
ALTERNATING CURRENT
AUTHORITY HAVING
JURISDICTION
BUILDING
CONCRETE
COMBINER BOX
CALIFORNIA ELECTRICAL
CODE
COPPER
DISTRIBUTION PANEL
DIRECT CURRENT
EQUIPMENT GROUNDING
CONDUCTOR
(EXISTING)
FIELD VERIFIED
GALVANIZED
GROUNDING ELECTRODE
CONDUCTOR
GROUND
HOT DIPPED GALVANIZED
CURRENT
CURRENT AT MAX POWER
INVERTER
SHORT CIRCUIT CURRENT
KILOVOLT AMPERE
KILOWATT
LOAD BEARING WALL
MINIMUM
MAIN CIRCUIT BREAKER
MAIN SERVICE PANEL
(NEW)
NEMA 3R, RAINTIGHT
OUTSIDE RATED
NATIONAL ELECTRICAL
CODE
NOT TO SCALE
ON CENTER
OVERCURRENT PROTECTION
DEVICE
POLES -BREAKER POLES-
PROPERTY LINES
PHOTOVOLTAIC
POLYVINYL CHLORIDE
ROOF RAFTER
SOLID BARE COPPER
SOLAR PLANE
SUBPANEL
SCHEDULE
STAINLESS STEEL
PRACTICAL TESTING
CONDITIONS
SOLAR WATER HEATER
TYPICAL
UNLESS NOTED OTHERWISE
VOLT
VOLTAGE AT MAX POWER
VOLTAGE AT OPEN CIRCUIT
WATT
A
AC
AHJ
BLDG
CONC
CB
CEC
CU
DP
DC
EGC
(E)
FV
GALV
GEC
GND
HDG
I
Imp
INVT
Isc
kVA
kW
LBW
MIN.
MCB
MSP
(N)
N3R
NEC
NTS
OC
OCPD
P
PL
PV
PVC
RR
SBC
SP
SPL
SCH
SS
PTC
SWH
TYP
UNO
V
Vmp
Voc
W
SHEET INDEX
01- E1 COVER SHEET
APPLICABLE CODES AND STANDARDS
VICINITY MAP
N
·2022 CBC
·2022 CRC
·2022 CEC
·2022 CMC
·2022 CPC
·2022 CFC
·2022 CEBC
· 2022 BUILDING ENERGY
EFFICIENCY STANDARDS
· AUTHORITY HAVING
JURISDICTION
· CURRENT LOCAL FIRE
CODE
1. EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, VENTILATIONS INTAKE AIR OPENINGS SHALL NOT BE
COVERED BY THE SOLAR PHOTOVOLTAIC SYSTEM.
2. EQUIPMENT. INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AC PHOTOVOLTAIC
MODULES, SOURCE-CIRCUIT COMBINERS, AND CHARGE CONTROLLERS INTENDED FOR USE IN PHOTOVOLTAIC POWER
SYSTEMS SHALL BE IDENTIFIED AND LISTED FOR THE APPLICATION. [CEC 690.4(B)]
3. ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND NON
ROOF SWITCHES. ROOF SWITCHES TO BE NEMA 4 RATED.
4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH CEC ARTICLE 250.
5. PROTECTION DEVICES FOR PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS ALSO CONNECTED TO SOURCES HAVING
SIGNIFICANTLY HIGHER CURRENT AVAILABILITY (E.G., PARALLEL STRINGS OF MODULES, UTILITY POWER), SHALL BE
PROTECTED AT THE SOURCE FROM OVERCURRENT. [CEC 690.9(A)]
6. PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION THAT
CONTROLS SPECIFIC CONDUCTORS. [CEC 690.12]
7. THE UTILITY INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED
ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL REMAIN
IN THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED.
[CEC 705.40]
8. ALL CONDUCTOR EXPOSED TO WEATHER SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT. [CEC
310.10(D)(1)]
9. THE MODULE CONDUCTORS MUST BE TYPE USE-2 OR LISTED FOR PHOTOVOLTAIC (PV) WIRE. [CEC 690.31(C)]
10. ALL CONDUCTORS SHALL BE MARKED ON EACH END FOR UNIQUE IDENTIFICATION.
11. AN INSULATED GROUNDED CONDUCTOR OF 6 AWG OR SMALLER SHALL BE IDENTIFIED AS A CONTINUOUS WHITE
FINISH. [CEC 200.6]
12. THE OUTPUT OF AN INTERCONNECTED ELECTRICAL POWER SOURCE SHALL BE PERMITTED TO BE CONNECTED TO THE
LOAD SIDE. INTERCONNECTING PROVISIONS FOR OTHER POWER SOURCES SHALL COMPLY WITH 705.12(B)(1)
THROUGH 705.12(B)(3)
13. EACH SOURCE INTERCONNECTION OF ONE OR MORE POWER SOURCES INSTALLED IN ONE SYSTEM SHALL BE MADE AT
A DEDICATED CIRCUIT BREAKER OR FUSIBLE DISCONNECTING MEANS. [CEC 705.12(A)]
14. THE SUM OF THE AMPERE RATING OF THE OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO THE BUSBAR OR
CONDUCTOR SHALL NOT EXCEED 120% OF THE RATING OF BUSBAR OR CONDUCTOR. [CEC 705.12(B)(3)(2)]
15. A CONNECTION AT EITHER END, BUT NOT BOTH ENDS, OF A CENTER-FED PANEL BOARD IN DWELLINGS SHALL BE PERMITTED WHERE
THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE
PROTECTING THE BUSBAR DOES NOT EXCEED 120 PERCENT OF THE CURRENT RATING OF THE BUSBAR. [CEC 705.12(B)(3)(4)]
16. EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUS BAR OR CONDUCTOR
SHALL BE MARKED TO INDICATE THE PRESENCE OF ALL SOURCES. [CEC 705.12(C)]
17. CIRCUIT BREAKER, IF BACKFED, SHALL BE SUITABLE FOR SUCH OPERATION. [CEC 705.12(D)]
18. TO MINIMIZE OVERHEATING OF THE BUSBAR IN PANELBOARD, THE PANELBOARD MAIN CIRCUIT BREAKER AND THE PV
POWER SOURCE CIRCUIT BREAKER SHALL BE PHYSICALLY LOCATED AT THE OPPOSITE END OF THE BUSBAR.
19. ALL THE CEC REQUIRED WARNING SIGNS, MARKINGS, AND LABELS SHALL BE POSTED ON EQUIPMENT AND
DISCONNECTS PRIOR TO ANY INSPECTIONS TO BE PERFORMED BY THE BUILDING DEPARTMENT INSPECTOR.
20. WHERE PV SYSTEM DC CIRCUIT'S RUN INSIDE A BUILDING, THEY SHALL BE CONTAINED IN METAL RACEWAYS TYPE MC
METAL CLAD CABLE OR METAL ENCLOSURES FROM POINT OF PENETRATION OF THE SURFACE OF THE BUILDING TO THE
FIRST READILY ACCESSIBLE DISCONNECTING MEANS. [CEC 690.31(D)]
21. FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR CONNECTOR
THAT ARE IS IN ACCORDANCE WITH CEC 110.14.
22. CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND
OPERATING AT OVER 30V DC OR 15V AC SHALL REQUIRE TOOL TO OPEN AND MARKED "DO NOT DISCONNECT UNDER
LOAD" OR "NOT FOR CURRENT INTERRUPTING". [CEC 690.33(C) & (D)]
23. EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 6AWG SHALL BE PROTECTED FROM PHYSICAL
DAMAGE BY A RACEWAY OR CABLE ARMOR. [CEC 250.120(C)]
24. EQUIPMENT GROUNDING CONDUCTOR FOR PV SYSTEM CIRCUITS SHALL BE SIZED IN ACCORDANCE WITH 250.122.
[CEC 690.45]
25. GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE INSTALLED IN ONE CONTINUOUS LENGTH WITHOUT A SPLICE OR
JOINT. IF NECESSARY, SPLICES OR CONNECTIONS SHALL BE MADE AS PERMITTED. [CEC 250.64(C)]
26. ALL SMOKE ALARMS, CARBON MONOXIDE ALARMS AND AUDIBLE NOTIFICATION DEVICES SHALL BE LISTED AND
LABELED IN ACCORDANCE WITH UL 217 AND UL 2034. THEY WILL BE INSTALLED IN ACCORDANCE WITH NFPA 72 AND
NFPA 720. [CRC 2019 R314 & R315]
27. SMOKE ALARMS AND CARBON MONOXIDE ALARMS WILL BE RETROFITTED INTO THE EXISTING DWELLING. THESE
SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH
FLOOR OF THE HOUSE. CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED OUTSIDE EACH BEDROOM
AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. THESE ALARMS MAY BE SOLELY BATTERY OPERATED IF THE
PHOTOVOLTAIC PROJECT DOES NOT INVOLVE THE REMOVAL OF INTERIOR WALL AND CEILING FINISHES INSIDE THE
HOME, OTHERWISE, THE ALARMS MUST BE HARD WIRED AND INTERCONNECTED.
GENERAL NOTES
*ALL WORK TO COMPLY WITH ABOVE CODES
* OCCUPANCY TYPE: R-3
* CONSTRUCTION TYPE: TYPE V-B
* UNSPRINKLERED
DWELLING INFO
02- E2 SITE PLAN
06- E7 SINGLE LINE DIAGRAM
07- E8 ELECTRICAL NOTES
04- E5 ROOF PLAN
05- E6 ATTACHMENT DETAIL
SCOPE OF WORK:
-
-
-
-
21
-
-
-
(N) INVERTER(S)
(N) SOLAR MODULE(S)
- ENPHASE IQ8M-72-2-US
- SILFAB SIL-400 HC+
21
1 125A ENPHASE IQ COMBINER 4/4C
1 200A/200A NCF
1 BRNSURGE
(N) AC COMBINER(S)
(N) MAIN SERVICE PANEL
MSP IS UPGRADED TO 200A/200A NCF.
(N) SURGE PROTECTION DEVICE
03- E3 PROPERTY PLAN
08- E9 SIGNAGE
09- E9.1 SIGNAGE
10- JHA
The scope of the plans is for the installation of the solar photovoltaic system
only and the approval is subject to compliance with all applicable city and
state codes and regulations regarding construction. The approval of the plans
does not constitute any certification of the accuracy, completeness, or
building permit status of the existing buildings and structures as shown.
Bldg# 101118489
Elec# 20182273
2614 S Everglade
St3/26/2024
A
C
C
E
S
S
P
A
TH
3'ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"GASMSPACCACDEXISTINGDRIVEWAYWORKING CLEARANCE3'E2SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:SITE PLANN1/8" = 1'-0"LEGEND(N) 200A BUS NCF MSP(N) 200A/2P MAIN BREAKER(N) 40A/2P PV BREAKER FEEDING(N) 60A SINGLE VISIBLY OPEN AND LOCKABLEAC DISCONNECT 240V NEMA-3RSERVICE POINT UTILITY METERING.MSPLALADDER ACCESSGAS(E) GAS RISER( ALL NEW EQUIPMENTS TO BE PLACED 3FEET AWAY FROM GAS MAIN )ACC(N) 125A ENPHASE IQ COMBINER 4/4CWITH ENVOY IQ, CELL MODEM, &WIRELESS COMMUNICATIONS KIT(N) 60A SINGLE VISIBLY OPEN AND LOCKABLEAC DISCONNECT 240V NEMA-3R POC FOR(N) 125A ENPHASE IQ COMBINER 4/4CACD21 (N) 400W SILFAB SIL-400 HC+ SOLARMODULES (FLUSH MOUNT)EACH WITH A (N) ENPHASE IQ8M-72-2-USMICRO-INVERTERSANTA ANA CA 927042614 S EVERGLADE STCUSTOMER ADDRESS -ALL EQUIPMENT IS INSTALLED WITHIN A6-INCH WORKING CLEARANCE WITHRESPECT TO MSP.LOAD SIDE INTERCONNECTION.2614 S EvergladeSt3/26/2024
AC
C
E
S
S
PA
TH3'ACCESS PATH18"ACCESS PATH18"ACCE
S
S
PA
TH18"AC
C
E
S
S
PA
TH
18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACC
E
S
S
P
A
T
H18"A
C
C
E
S
S
P
A
T
H
18"ACCESS PATH18"ACCESS PATH18"GASMSPACCACDEXISTINGPOOL
EXISTING
DRIVEWAY
FRONT OF
RESIDENCE EXISTINGHOUSE99'-6"67'-3"99'-6"67'-3"
S EVERGLADE ST22'6'-5"
6'-1"13'-1"E3SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:PROPERTY PLANN3/32" = 1'-0"(N) PROPOSED SOLAR PANEL(E) EXISTING PATIO(E) FENCE(E) PROPERTY LINE(E) GATE2614 S EvergladeSt3/26/2024
A
C
C
E
S
S
P
A
T
H
3'ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PAT
H
18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACCESS PATH18"ACCESS PA
T
H
18"ACCESS PATH18"ACCESS PATH18"GASMSPACCRP1RP2RP3RP4E5SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:ROOF PLANN1/8" = 1'-0"NEW PV CONDUIT TO BE RUN UNDER ATTIC WHENEVER POSSIBLE.ANY PROPOSED CONDUIT RUN SUBJECT TO CHANGE BY INSTALLER.45 ATTACHMENTS INSTALLED @ 72" O.C. MAX. (TYP.)FRONT OF RESIDENCE PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65233.192"X6"24"COMP.SHINGLE90°21°1PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65326.492"X6"24"COMP.SHINGLE180°21°2PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65223.062"X6"24"COMP.SHINGLE180°21°3PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.127.98259.942"X6"24"COMP.SHINGLE270°21°42614 S EvergladeSt3/26/2024
(N) MODULE(E) COMPOSITIONSHINGLE(E) ROOF DECKING(E) RAFTER, SEE E5FOR DETAIL(N) PEGASUSMULTI CLAMP(N) PEGASUS RAIL(N) PEGASUSDOVETAIL T-BOLT(N) PEGASUS L-FOOT(N) 5/16" x 4.5" PEGASUS LAG BOLTMIN 2.5" EMBEDMENT(N) PEGASUS COMPMOUNT FLASHINGE6SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142ATTACHMENT DETAIL2614 S EvergladeSt3/26/2024
LALA GASMSPACCJHASHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142NEAREST URGENT CAREVICINITY MAPDISTANCEADDRESSNAMECONDITIONSNCREW MEMBERCREW LEADCREW MEMBERCREW MEMBERROPE REACHLADDER ACCESSCONESEXCLUSION ZONEJHA LEGENDANCHOR POINTSNTHIS PAGE TO BE COMPLETED BY INSTALLATION CREW2614 S EvergladeSt3/26/2024
(N) 60ASINGLE VISIBLYOPEN & LOCKABLE,AC DISCONNECT240V NEMA-3RGEnphase IQ Gateway(N) 125A ENPHASE IQCOMBINER 4/4C NEMA-3RX-IQ-AM1-240-4/4C[CRD-PCS NEM) 240VREVENUE-GRADEPRODUCTION METERINGFACTORY INSTALLEDenphaseENERGY(N)20A/2P(N)15A/2PEACH WITH ANENPHASE IQ8M-72-2-USMICROINVERTERAC(N)J-BOXG1 BRANCH OFMODULES11SOURCE CIRCUIT #1Isc = 14.85 AENPHASE Q CABLE2-#121-#6 GRNDOPEN AIR(N)20A/2PEACH WITH ANENPHASE IQ8M-72-2-USMICROINVERTERAC(N)J-BOXG1 BRANCH OFMODULES10SOURCE CIRCUIT #2Isc = 13.5 ATHWN-23-#101-#8 GRND3/4" EMT CONDUITTHWN-23-#81-#8 GRND3/4" EMT CONDUITMAIN SERVICE PANEL, 240VGROUNDING ELECTRODE &AUXILIARY GROUNDINGELECTRODE AS NEEDED PERCEC 690.47 (6 FEET APART)LLLLGND
N LOADS (E) A TOP FEDMETER #222013-028556 (N)200200A/2P(N)(N)40A/2PE7SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142 UTILITY COMPANY:MSP VOLTAGE:MSP GROUND:SERV. TYPE:SERVICE INFOSCE120/240UNDERGROUND(N) ROD2% Avg. 1"MINASHRAE AMBIENT TEMPERATURE SPECS° C° CHigh TempEXTREMEDISTANCEABOVE ROOFNO TEMP ADDERPER 310.15(B)(2)312BUSBARMAINBREAKERMAXPV OCP( 200A x 1.2 ) - 200A = 40ACEC705.12(B)(3)(2)INTERCONNECTION METHOD PER 705.12(B)(3)(2):WHERE TWO SOURCES, ONE A PRIMARY POWER SOURCE AND THE OTHERANOTHER POWER SOURCE, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THATCONTAINS LOADS, THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUTCIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTINGTHE BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR.MSP IS UPGRADED TO 200A/200A NCF.(N)BRNSURGE SURGE PROTECTOR - COMPATIBLE WITH EATON, GE,SIEMENS, CROUSE HINDS PANELBOARDS2614 S EvergladeSt3/26/2024
ELECTRICAL NOTES:1)ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH CODE AND THEMANUFACTURER’S INSTALLATION INSTRUCTIONS.2)ALL PV EQUIPMENT SHALL BE LISTED BY A RECOGNIZED TESTED LAB.3)NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM.4)WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION,BREAKER SHALL NOT READ LINE AND LOAD.5)WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THEBREAKER SHALL BE INSTALLED AT THE OPPOSITE END OF THE BUS BAR OF THEMAIN BREAKER.6)WORKING SPACE FOR EQUIPMENT OPERATING AT 1000 VOLTS, NOMINAL, OR LESSTO GROUND AND LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING,OR MAINTENANCE WHILE ENERGIZED SHALL COMPLY WITH [CEC 110.26(A)]7)ALL EXTERIOR CONDUITS, FITTINGS AND BOXES SHALL BE RAIN-TIGHT ANDAPPROVED FOR USE IN WET LOCATIONS PER [CEC 314.15].8)ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLYCONTINUOUS.9)PV EQUIPMENT, SYSTEMS AND ALL ASSOCIATED WIRING AND INTERCONNECTIONSSHALL ONLY BE INSTALLED BY QUALIFIED PERSONS. [CEC 690.4 (C)].10)THE PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED.THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATED COLORCODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS. [CEC690.31(B)(1)]11)ADEQUATE SPACING MUST BE MAINTAINED BETWEEN ANY PLUMBING SEWERVENTS EXTENDING THROUGH THE ROOF AND THE UNDERSIDE OF THEPHOTOVOLTAIC PANELS (6" MINIMUM RECOMMENDED).E8SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142
2614 S EvergladeSt3/26/2024
E9SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142MARKING IS REQUIRED ON ALL INTERIOR ANDEXTERIOR DC PV CONDUIT, RACEWAYS, ENCLOSURES,CABLE ASSEMBLIES, AND JUNCTION BOXES TO ALERTTHE FIRE SERVICE TO AVOID CUTTING THEM. MARKINGSHALL BE PLACED EVERY 10 FEET, AT TURNS ANDABOVE AND/OR BELOW PENETRATIONS, AND AT ALL PVCOMBINER AND JUNCTION BOXES. [CEC 690.31(D)(2)]REFLECTIVE WEATHER RESISTANT MATERIAL SUITABLEFOR THE ENVIRONMENT (DURABLE ADHESIVEMATERIALS MUST MEET THIS REQUIREMENT)MARKING CONTENT AND FORMATPER [ CEC 110.21(B)] WITH REFERENCETO ANSI Z535.4-2011-BACKGROUND PER ANSI Z535.4-2011-LETTERING PER ANSI Z535.4-2011-MINIMUM 3/8” LETTER HEIGHT-ALL CAPITAL LETTERS-ARIAL OR SIMILAR FONT, NON BOLDMARKING PV CIRCUIT11314483213121195PV COMBINER(IF USED)FOR ILLUSTRATION ONLY (NOT ACTUAL MSP)MAIN SERVICE PANELAC DISCONNECT(IF USED)LABEL LEGEND9112344589131314551515CEC 690.56(C)CEC 705.12(C) & CEC 690.59CEC 690.13(B)CEC 690.13(B)CEC 690.54CEC 705.12(B)(3)(2)CEC 110.27(C)CEC 706.15(C)(4)CEC 690.13(B)CEC 705.12(B)(3)(3)CEC 705.12(D)CEC 690.56(C)(2)2614 S EvergladeSt3/26/2024
LALAGASMSPACCCAUTIONPOWER TO THIS SERVICE IS ALSOSUPPLIED FROM THE FOLLOWINGSOURCES WITH DISCONNECTSLOCATED AS SHOWN:PLACARD RIVETED TO THE MAIN SERVICE PANELE9.1SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142NOMINAL OPERATING AC VOLTAGE: BBBBBBBB NOMINAL OPERATING AC FREQUENCY:BBBBBBBB MAXIMUM AC POWER: BBBBBBBB MAXIMUM AC CURRENT: BBBBBBBB MAX OVERCURRENT DEVICE RATINGFOR AC MODULE PROTECTION: BBBBBBBB 240V60.0Hz6825W28.35A40ASOLAR LOAD CENTERNO ADDITIONAL LOADS ALLOWEDNPHOTOVOLTAIC POWER SOURCEOPERATING AC VOLTAGE: BBBBB VMAXIMUM OPERATING AC OUTPUTCURRENT: BBBBBB AMPSLABEL FOR MAIN SERVICE PANEL COVER24035.43PHOTOVOLTAIC AC DISCONNECTRATED AC OUTPUT CURRENT: BBBBB ANOMINAL OPERATING AC VOLTAGE:BBBBB V35.43240PV DISCONNECTAC DISCONNECT(YOU ARE HERE)SERVICE POINT & UTILITYMETERING & PV DISCONNECTSOLAR ARRAYNO RSD THESEMODSSOUTH EVERGLADE STREETSANTA ANA CA 927042614 S EVERGLADE ST2614 S EvergladeSt3/26/2024
E1
SHEET NUMBER:SEMPER SOLARIS1805 JOHN TOWERS AVEEL CAJON, CA 92020C-10 LIC # 978152Lic. Holder Digitally StampedPROJECT FOR: PROPOSED
DRAWN BY:
DATE:
(DC) kW:
PROJECT #:John AlmondEVOLUTION
11/14/2023
85942
8.400KAREN N FLORES & ORLANDO MACIASSANTA ANA CA 92704 2614 S EVERGLADE ST(714) 824-1142 APN - 41406114SOLAR PHOTOVOLTAIC SYSTEM SIZE: 8.400 kW DC PVMAIN LINE: 619-357-4142ABBREVIATIONS
AMPERE
ALTERNATING CURRENT
AUTHORITY HAVING
JURISDICTION
BUILDING
CONCRETE
COMBINER BOX
CALIFORNIA ELECTRICAL
CODE
COPPER
DISTRIBUTION PANEL
DIRECT CURRENT
EQUIPMENT GROUNDING
CONDUCTOR
(EXISTING)
FIELD VERIFIED
GALVANIZED
GROUNDING ELECTRODE
CONDUCTOR
GROUND
HOT DIPPED GALVANIZED
CURRENT
CURRENT AT MAX POWER
INVERTER
SHORT CIRCUIT CURRENT
KILOVOLT AMPERE
KILOWATT
LOAD BEARING WALL
MINIMUM
MAIN CIRCUIT BREAKER
MAIN SERVICE PANEL
(NEW)
NEMA 3R, RAINTIGHT
OUTSIDE RATED
NATIONAL ELECTRICAL
CODE
NOT TO SCALE
ON CENTER
OVERCURRENT PROTECTION
DEVICE
POLES -BREAKER POLES-
PROPERTY LINES
PHOTOVOLTAIC
POLYVINYL CHLORIDE
ROOF RAFTER
SOLID BARE COPPER
SOLAR PLANE
SUBPANEL
SCHEDULE
STAINLESS STEEL
PRACTICAL TESTING
CONDITIONS
SOLAR WATER HEATER
TYPICAL
UNLESS NOTED OTHERWISE
VOLT
VOLTAGE AT MAX POWER
VOLTAGE AT OPEN CIRCUIT
WATT
A
AC
AHJ
BLDG
CONC
CB
CEC
CU
DP
DC
EGC
(E)
FV
GALV
GEC
GND
HDG
I
Imp
INVT
Isc
kVA
kW
LBW
MIN.
MCB
MSP
(N)
N3R
NEC
NTS
OC
OCPD
P
PL
PV
PVC
RR
SBC
SP
SPL
SCH
SS
PTC
SWH
TYP
UNO
V
Vmp
Voc
W
SHEET INDEX
01- E1 COVER SHEET
APPLICABLE CODES AND STANDARDS
VICINITY MAP
N
·2022 CBC
·2022 CRC
·2022 CEC
·2022 CMC
·2022 CPC
·2022 CFC
·2022 CEBC
· 2022 BUILDING ENERGY
EFFICIENCY STANDARDS
· AUTHORITY HAVING
JURISDICTION
· CURRENT LOCAL FIRE
CODE
1. EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, VENTILATIONS INTAKE AIR OPENINGS SHALL NOT BE
COVERED BY THE SOLAR PHOTOVOLTAIC SYSTEM.
2. EQUIPMENT. INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AC PHOTOVOLTAIC
MODULES, SOURCE-CIRCUIT COMBINERS, AND CHARGE CONTROLLERS INTENDED FOR USE IN PHOTOVOLTAIC POWER
SYSTEMS SHALL BE IDENTIFIED AND LISTED FOR THE APPLICATION. [CEC 690.4(B)]
3. ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND NON
ROOF SWITCHES. ROOF SWITCHES TO BE NEMA 4 RATED.
4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH CEC ARTICLE 250.
5. PROTECTION DEVICES FOR PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS ALSO CONNECTED TO SOURCES HAVING
SIGNIFICANTLY HIGHER CURRENT AVAILABILITY (E.G., PARALLEL STRINGS OF MODULES, UTILITY POWER), SHALL BE
PROTECTED AT THE SOURCE FROM OVERCURRENT. [CEC 690.9(A)]
6. PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION THAT
CONTROLS SPECIFIC CONDUCTORS. [CEC 690.12]
7. THE UTILITY INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED
ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL REMAIN
IN THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED.
[CEC 705.40]
8. ALL CONDUCTOR EXPOSED TO WEATHER SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT. [CEC
310.10(D)(1)]
9. THE MODULE CONDUCTORS MUST BE TYPE USE-2 OR LISTED FOR PHOTOVOLTAIC (PV) WIRE. [CEC 690.31(C)]
10. ALL CONDUCTORS SHALL BE MARKED ON EACH END FOR UNIQUE IDENTIFICATION.
11. AN INSULATED GROUNDED CONDUCTOR OF 6 AWG OR SMALLER SHALL BE IDENTIFIED AS A CONTINUOUS WHITE
FINISH. [CEC 200.6]
12. THE OUTPUT OF AN INTERCONNECTED ELECTRICAL POWER SOURCE SHALL BE PERMITTED TO BE CONNECTED TO THE
LOAD SIDE. INTERCONNECTING PROVISIONS FOR OTHER POWER SOURCES SHALL COMPLY WITH 705.12(B)(1)
THROUGH 705.12(B)(3)
13. EACH SOURCE INTERCONNECTION OF ONE OR MORE POWER SOURCES INSTALLED IN ONE SYSTEM SHALL BE MADE AT
A DEDICATED CIRCUIT BREAKER OR FUSIBLE DISCONNECTING MEANS. [CEC 705.12(A)]
14. THE SUM OF THE AMPERE RATING OF THE OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO THE BUSBAR OR
CONDUCTOR SHALL NOT EXCEED 120% OF THE RATING OF BUSBAR OR CONDUCTOR. [CEC 705.12(B)(3)(2)]
15. A CONNECTION AT EITHER END, BUT NOT BOTH ENDS, OF A CENTER-FED PANEL BOARD IN DWELLINGS SHALL BE PERMITTED WHERE
THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE
PROTECTING THE BUSBAR DOES NOT EXCEED 120 PERCENT OF THE CURRENT RATING OF THE BUSBAR. [CEC 705.12(B)(3)(4)]
16. EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUS BAR OR CONDUCTOR
SHALL BE MARKED TO INDICATE THE PRESENCE OF ALL SOURCES. [CEC 705.12(C)]
17. CIRCUIT BREAKER, IF BACKFED, SHALL BE SUITABLE FOR SUCH OPERATION. [CEC 705.12(D)]
18. TO MINIMIZE OVERHEATING OF THE BUSBAR IN PANELBOARD, THE PANELBOARD MAIN CIRCUIT BREAKER AND THE PV
POWER SOURCE CIRCUIT BREAKER SHALL BE PHYSICALLY LOCATED AT THE OPPOSITE END OF THE BUSBAR.
19. ALL THE CEC REQUIRED WARNING SIGNS, MARKINGS, AND LABELS SHALL BE POSTED ON EQUIPMENT AND
DISCONNECTS PRIOR TO ANY INSPECTIONS TO BE PERFORMED BY THE BUILDING DEPARTMENT INSPECTOR.
20. WHERE PV SYSTEM DC CIRCUIT'S RUN INSIDE A BUILDING, THEY SHALL BE CONTAINED IN METAL RACEWAYS TYPE MC
METAL CLAD CABLE OR METAL ENCLOSURES FROM POINT OF PENETRATION OF THE SURFACE OF THE BUILDING TO THE
FIRST READILY ACCESSIBLE DISCONNECTING MEANS. [CEC 690.31(D)]
21. FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR CONNECTOR
THAT ARE IS IN ACCORDANCE WITH CEC 110.14.
22. CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND
OPERATING AT OVER 30V DC OR 15V AC SHALL REQUIRE TOOL TO OPEN AND MARKED "DO NOT DISCONNECT UNDER
LOAD" OR "NOT FOR CURRENT INTERRUPTING". [CEC 690.33(C) & (D)]
23. EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 6AWG SHALL BE PROTECTED FROM PHYSICAL
DAMAGE BY A RACEWAY OR CABLE ARMOR. [CEC 250.120(C)]
24. EQUIPMENT GROUNDING CONDUCTOR FOR PV SYSTEM CIRCUITS SHALL BE SIZED IN ACCORDANCE WITH 250.122.
[CEC 690.45]
25. GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE INSTALLED IN ONE CONTINUOUS LENGTH WITHOUT A SPLICE OR
JOINT. IF NECESSARY, SPLICES OR CONNECTIONS SHALL BE MADE AS PERMITTED. [CEC 250.64(C)]
26. ALL SMOKE ALARMS, CARBON MONOXIDE ALARMS AND AUDIBLE NOTIFICATION DEVICES SHALL BE LISTED AND
LABELED IN ACCORDANCE WITH UL 217 AND UL 2034. THEY WILL BE INSTALLED IN ACCORDANCE WITH NFPA 72 AND
NFPA 720. [CRC 2019 R314 & R315]
27. SMOKE ALARMS AND CARBON MONOXIDE ALARMS WILL BE RETROFITTED INTO THE EXISTING DWELLING. THESE
SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH
FLOOR OF THE HOUSE. CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED OUTSIDE EACH BEDROOM
AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. THESE ALARMS MAY BE SOLELY BATTERY OPERATED IF THE
PHOTOVOLTAIC PROJECT DOES NOT INVOLVE THE REMOVAL OF INTERIOR WALL AND CEILING FINISHES INSIDE THE
HOME, OTHERWISE, THE ALARMS MUST BE HARD WIRED AND INTERCONNECTED.
GENERAL NOTES
*ALL WORK TO COMPLY WITH ABOVE CODES
* OCCUPANCY TYPE: R-3
* CONSTRUCTION TYPE: TYPE V-B
* UNSPRINKLERED
DWELLING INFO
02- E2 SITE PLAN
06- E7 SINGLE LINE DIAGRAM
07- E8 ELECTRICAL NOTES
04- E5 ROOF PLAN
05- E6 ATTACHMENT DETAIL
SCOPE OF WORK:
-
-
-
-
21
-
-
-
(N) INVERTER(S)
(N) SOLAR MODULE(S)
- ENPHASE IQ8M-72-2-US
- SILFAB SIL-400 HC+
21
1 125A ENPHASE IQ COMBINER 4/4C
1 200A/200A NCF
1 BRNSURGE
(N) AC COMBINER(S)
(N) MAIN SERVICE PANEL
MSP IS UPGRADED TO 200A/200A NCF.
(N) SURGE PROTECTION DEVICE
03- E3 PROPERTY PLAN
08- E9 SIGNAGE
09- E9.1 SIGNAGE
10- JHA
The scope of the plans is for the installation of the solar photovoltaic system
only and the approval is subject to compliance with all applicable city and
state codes and regulations regarding construction. The approval of the plans
does not constitute any certification of the accuracy, completeness, or
building permit status of the existing buildings and structures as shown.
Bldg# 101118489
Elec# 20182273
2614 S Everglade
St4/23/2024
A
C
C
E
S
S
P
A
TH
3'ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"GASMSPACCACDEXISTINGDRIVEWAYWORKING CLEARANCE3'E2SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:SITE PLANN1/8" = 1'-0"LEGEND(N) 200A BUS NCF MSP(N) 200A/2P MAIN BREAKER(N) 40A/2P PV BREAKER FEEDING(N) 60A SINGLE VISIBLY OPEN AND LOCKABLEAC DISCONNECT 240V NEMA-3RSERVICE POINT UTILITY METERING.MSPLALADDER ACCESSGAS(E) GAS RISER( ALL NEW EQUIPMENTS TO BE PLACED 3FEET AWAY FROM GAS MAIN )ACC(N) 125A ENPHASE IQ COMBINER 4/4CWITH ENVOY IQ, CELL MODEM, &WIRELESS COMMUNICATIONS KIT(N) 60A SINGLE VISIBLY OPEN AND LOCKABLEAC DISCONNECT 240V NEMA-3R POC FOR(N) 125A ENPHASE IQ COMBINER 4/4CACD21 (N) 400W SILFAB SIL-400 HC+ SOLARMODULES (FLUSH MOUNT)EACH WITH A (N) ENPHASE IQ8M-72-2-USMICRO-INVERTERSANTA ANA CA 927042614 S EVERGLADE STCUSTOMER ADDRESS -ALL EQUIPMENT IS INSTALLED WITHIN A6-INCH WORKING CLEARANCE WITHRESPECT TO MSP.LOAD SIDE INTERCONNECTION.2614 S EvergladeSt4/23/2024
AC
C
E
S
S
PA
TH3'ACCESS PATH18"ACCESS PATH18"ACCE
S
S
PA
TH18"AC
C
E
S
S
PA
TH
18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACC
E
S
S
P
A
T
H18"A
C
C
E
S
S
P
A
T
H
18"ACCESS PATH18"ACCESS PATH18"GASMSPACCACDEXISTINGPOOL
EXISTING
DRIVEWAY
FRONT OF
RESIDENCE EXISTINGHOUSE99'-6"67'-3"99'-6"67'-3"
S EVERGLADE ST22'6'-5"
6'-1"13'-1"E3SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:PROPERTY PLANN3/32" = 1'-0"(N) PROPOSED SOLAR PANEL(E) EXISTING PATIO(E) FENCE(E) PROPERTY LINE(E) GATE2614 S EvergladeSt4/23/2024
A
C
C
E
S
S
P
A
T
H
3'ACCESS PATH18"ACCESS PATH18"ACCESS PATH18"ACCESS PAT
H
18"FIRE SETBACK18"FIRE SETBACK18"ACCESS PATH3'LALAACCESS PATH18"ACCESS PA
T
H
18"ACCESS PATH18"ACCESS PATH18"GASMSPACCRP1RP2RP3RP4E5SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142SCALE:ROOF PLANN1/8" = 1'-0"NEW PV CONDUIT TO BE RUN UNDER ATTIC WHENEVER POSSIBLE.ANY PROPOSED CONDUIT RUN SUBJECT TO CHANGE BY INSTALLER.45 ATTACHMENTS INSTALLED @ 72" O.C. MAX. (TYP.)FRONT OF RESIDENCE PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65233.192"X6"24"COMP.SHINGLE90°21°1PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65326.492"X6"24"COMP.SHINGLE180°21°2PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.106.65223.062"X6"24"COMP.SHINGLE180°21°3PITCHAZIMUTHMATERIALROOF#RAFTER SPECSSP SQ.FTARRAY SQ.FT@O.C.127.98259.942"X6"24"COMP.SHINGLE270°21°42614 S EvergladeSt4/23/2024
(N) MODULE(E) COMPOSITIONSHINGLE(E) ROOF DECKING(E) RAFTER, SEE E5FOR DETAIL(N) PEGASUSMULTI CLAMP(N) PEGASUS RAIL(N) PEGASUSDOVETAIL T-BOLT(N) PEGASUS L-FOOT(N) 5/16" x 4.5" PEGASUS LAG BOLTMIN 2.5" EMBEDMENT(N) PEGASUS COMPMOUNT FLASHINGE6SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142ATTACHMENT DETAIL2614 S EvergladeSt4/23/2024
LALA GASMSPACCJHASHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142NEAREST URGENT CAREVICINITY MAPDISTANCEADDRESSNAMECONDITIONSNCREW MEMBERCREW LEADCREW MEMBERCREW MEMBERROPE REACHLADDER ACCESSCONESEXCLUSION ZONEJHA LEGENDANCHOR POINTSNTHIS PAGE TO BE COMPLETED BY INSTALLATION CREW2614 S EvergladeSt4/23/2024
(N) 60ASINGLE VISIBLYOPEN & LOCKABLE,AC DISCONNECT240V NEMA-3RGEnphase IQ Gateway(N) 125A ENPHASE IQCOMBINER 4/4C NEMA-3RX-IQ-AM1-240-4/4C[CRD-PCS NEM) 240VREVENUE-GRADEPRODUCTION METERINGFACTORY INSTALLEDenphaseENERGY(N)20A/2P(N)15A/2PEACH WITH ANENPHASE IQ8M-72-2-USMICROINVERTERAC(N)J-BOXG1 BRANCH OFMODULES11SOURCE CIRCUIT #1Isc = 14.85 AENPHASE Q CABLE2-#121-#6 GRNDOPEN AIR(N)20A/2PEACH WITH ANENPHASE IQ8M-72-2-USMICROINVERTERAC(N)J-BOXG1 BRANCH OFMODULES10SOURCE CIRCUIT #2Isc = 13.5 ATHWN-23-#101-#8 GRND3/4" EMT CONDUITTHWN-23-#81-#8 GRND3/4" EMT CONDUITMAIN SERVICE PANEL, 240VGROUNDING ELECTRODE &AUXILIARY GROUNDINGELECTRODE AS NEEDED PERCEC 690.47 (6 FEET APART)LLLLGND
N LOADS (E) A TOP FEDMETER #222013-028556 (N)200200A/2P(N)(N)40A/2PE7SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142 UTILITY COMPANY:MSP VOLTAGE:MSP GROUND:SERV. TYPE:SERVICE INFOSCE120/240UNDERGROUND(N) ROD2% Avg. 1"MINASHRAE AMBIENT TEMPERATURE SPECS° C° CHigh TempEXTREMEDISTANCEABOVE ROOFNO TEMP ADDERPER 310.15(B)(2)312BUSBARMAINBREAKERMAXPV OCP( 200A x 1.2 ) - 200A = 40ACEC705.12(B)(3)(2)INTERCONNECTION METHOD PER 705.12(B)(3)(2):WHERE TWO SOURCES, ONE A PRIMARY POWER SOURCE AND THE OTHERANOTHER POWER SOURCE, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THATCONTAINS LOADS, THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUTCIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTINGTHE BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR.MSP IS UPGRADED TO 200A/200A NCF.(N)BRNSURGE SURGE PROTECTOR - COMPATIBLE WITH EATON, GE,SIEMENS, CROUSE HINDS PANELBOARDS2614 S EvergladeSt4/23/2024
ELECTRICAL NOTES:1)ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH CODE AND THEMANUFACTURER’S INSTALLATION INSTRUCTIONS.2)ALL PV EQUIPMENT SHALL BE LISTED BY A RECOGNIZED TESTED LAB.3)NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM.4)WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION,BREAKER SHALL NOT READ LINE AND LOAD.5)WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THEBREAKER SHALL BE INSTALLED AT THE OPPOSITE END OF THE BUS BAR OF THEMAIN BREAKER.6)WORKING SPACE FOR EQUIPMENT OPERATING AT 1000 VOLTS, NOMINAL, OR LESSTO GROUND AND LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING,OR MAINTENANCE WHILE ENERGIZED SHALL COMPLY WITH [CEC 110.26(A)]7)ALL EXTERIOR CONDUITS, FITTINGS AND BOXES SHALL BE RAIN-TIGHT ANDAPPROVED FOR USE IN WET LOCATIONS PER [CEC 314.15].8)ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLYCONTINUOUS.9)PV EQUIPMENT, SYSTEMS AND ALL ASSOCIATED WIRING AND INTERCONNECTIONSSHALL ONLY BE INSTALLED BY QUALIFIED PERSONS. [CEC 690.4 (C)].10)THE PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED.THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATED COLORCODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS. [CEC690.31(B)(1)]11)ADEQUATE SPACING MUST BE MAINTAINED BETWEEN ANY PLUMBING SEWERVENTS EXTENDING THROUGH THE ROOF AND THE UNDERSIDE OF THEPHOTOVOLTAIC PANELS (6" MINIMUM RECOMMENDED).E8SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142
2614 S EvergladeSt4/23/2024
E9SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142MARKING IS REQUIRED ON ALL INTERIOR ANDEXTERIOR DC PV CONDUIT, RACEWAYS, ENCLOSURES,CABLE ASSEMBLIES, AND JUNCTION BOXES TO ALERTTHE FIRE SERVICE TO AVOID CUTTING THEM. MARKINGSHALL BE PLACED EVERY 10 FEET, AT TURNS ANDABOVE AND/OR BELOW PENETRATIONS, AND AT ALL PVCOMBINER AND JUNCTION BOXES. [CEC 690.31(D)(2)]REFLECTIVE WEATHER RESISTANT MATERIAL SUITABLEFOR THE ENVIRONMENT (DURABLE ADHESIVEMATERIALS MUST MEET THIS REQUIREMENT)MARKING CONTENT AND FORMATPER [ CEC 110.21(B)] WITH REFERENCETO ANSI Z535.4-2011-BACKGROUND PER ANSI Z535.4-2011-LETTERING PER ANSI Z535.4-2011-MINIMUM 3/8” LETTER HEIGHT-ALL CAPITAL LETTERS-ARIAL OR SIMILAR FONT, NON BOLDMARKING PV CIRCUIT11314483213121195PV COMBINER(IF USED)FOR ILLUSTRATION ONLY (NOT ACTUAL MSP)MAIN SERVICE PANELAC DISCONNECT(IF USED)LABEL LEGEND9112344589131314551515CEC 690.56(C)CEC 705.12(C) & CEC 690.59CEC 690.13(B)CEC 690.13(B)CEC 690.54CEC 705.12(B)(3)(2)CEC 110.27(C)CEC 706.15(C)(4)CEC 690.13(B)CEC 705.12(B)(3)(3)CEC 705.12(D)CEC 690.56(C)(2)2614 S EvergladeSt4/23/2024
LALAGASMSPACCCAUTIONPOWER TO THIS SERVICE IS ALSOSUPPLIED FROM THE FOLLOWINGSOURCES WITH DISCONNECTSLOCATED AS SHOWN:PLACARD RIVETED TO THE MAIN SERVICE PANELE9.1SHEET NUMBER:SEMPER SOLARIS
1805 JOHN TOWERS AVE
EL CAJON, CA 92020
C-10 LIC # 978152
Lic. Holder Digitally Stamped
PROJECT FOR:PROPOSEDDRAWN BY:DATE:(DC) kW:PROJECT #:John AlmondEVOLUTION11/14/2023859428.400KAREN N FLORES & ORLANDO MACIAS
SANTA ANA CA 92704
2614 S EVERGLADE ST
(714) 824-1142
APN - 41406114
SOLAR PHOTOVOLTAIC
SYSTEM SIZE:
8.400 kW DC PV
MAIN LINE: 619-357-4142NOMINAL OPERATING AC VOLTAGE: BBBBBBBB NOMINAL OPERATING AC FREQUENCY:BBBBBBBB MAXIMUM AC POWER: BBBBBBBB MAXIMUM AC CURRENT: BBBBBBBB MAX OVERCURRENT DEVICE RATINGFOR AC MODULE PROTECTION: BBBBBBBB 240V60.0Hz6825W28.35A40ASOLAR LOAD CENTERNO ADDITIONAL LOADS ALLOWEDNPHOTOVOLTAIC POWER SOURCEOPERATING AC VOLTAGE: BBBBB VMAXIMUM OPERATING AC OUTPUTCURRENT: BBBBBB AMPSLABEL FOR MAIN SERVICE PANEL COVER24035.43PHOTOVOLTAIC AC DISCONNECTRATED AC OUTPUT CURRENT: BBBBB ANOMINAL OPERATING AC VOLTAGE:BBBBB V35.43240PV DISCONNECTAC DISCONNECT(YOU ARE HERE)SERVICE POINT & UTILITYMETERING & PV DISCONNECTSOLAR ARRAYNO RSD THESEMODSSOUTH EVERGLADE STREETSANTA ANA CA 927042614 S EVERGLADE ST2614 S EvergladeSt4/23/2024