HomeMy WebLinkAbout2402 S Manitoba Drive – DL - 101109909 & 20175792 - PlanExpedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 2402 S Manitoba Drive1/23/2024 Expedited Permit Process for PV Systems — Micro-Inverter 2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. x Composition Shingle x M1 Structural Adhesive x Iron Ridge Flashfoot 2.85 68 23.85 28 502.14 0.0147 ✔ ✔ ✔ 2402 S Manitoba Drive1/23/2024 Expedited Permit Process for PV Systems 3Micro-Inverter Site Plan&RQWUDFWRU1DPH$GGUHVVDQG3KRQH%LOODQG7HG¶V6RODU([FHOOHQW'ULYH6DQ'LPDV&$6LWH3ODQIRU6PDOO6FDOH6LQJOH3KDVH396\VWHPV6LWH1DPH-RHDQG-DQH+RPHRZQHU6LWH$GGUHVV6XQQ\VLGH6W)RQWDQD&$6\VWHP$&6L]HN:6RODU$UUD\^/&^DEKt'EKZs^>Ed^ĂƚĞ͗^,dƌĂǁŶLJ͗ŚĞĐŬĞĚLJ͗2402 S Manitoba Drive1/23/2024 Expedited Permit Process for PV Systems 4Micro-Inverter Electrical DiagramContractor Name, Address and Phone:One-Line Standard Electrical Diagramfor Micro-Inverter PV SystemsSite Name: Site Address: System AC Size: SIZEFSCM NODWG NOREVE1.1aSCALENTSDate: SHEETDrawn By:Checked By:DESCRIPTION OR CONDUCTOR TYPEUSE-2 or PV WIRE GEC EGC X ALL THAT APPLYEXTERIOR CABLE LISTED W/ INV.THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLYNO DC GEC IF 690.35 SYSTEMTHWN-2 or XHHW-2 or RHW-2GEC EGC X ALL THAT APPLYTAG12345CONDUIT AND CONDUCTOR SCHEDULECOND.GAUGEMFGMFGNUMBER OFCONDUCTORSMFG CableMFG CableCONDUITTYPEN/AN/AN/ASAME SAMECONDUITSIZEN/AN/AN/ASAMESAMEDESCRIPTION PV DC or AC MODULEDC/AC INVERTER (MICRO)J-BOX (IF USED)PV ARRAYAC COMB. PANEL (IF USED)GEN METER (IF USED)AC DISCONNECT (IF USED)SERVICE PANELTAG12345678PART NUMBERNOTESFOR UNUSED MODULESPUT "N/A” in BLANK ABOVE11323EQUIPMENT SCHEDULE2_____ MICRO-INVERTERS IN BRANCH-CIRCUITMOD____DCACMOD____DCACMOD____DCACMOD____DCACMOD____DCACMOD____DCACJ-BOX4AC DISCOMBUILDINGGROUNDING ELECTRODEGMUTILITY SERVICEMAIN SERVICE PANELMAINOCPDINVERTEROCPD678545GSEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDINGAC COMBINER PANELG____ MICRO-INVERTERS IN BRANCH-CIRCUITQ Cell Q Peak Duo BLK G6 340WIQ7PlusEnphase Combiner 3Q Cell Q Peak Duo BLK G6 340WNEMA60 AMP Square D DisconnectEaton108xxxxxxxxx12412210482Quan Hy2402 S Manitoba Dr Santa Ana7.542/232402 S Manitoba Drive1/23/2024 Expedited Permit Process for PV Systems 5Contractor Name, Address and Phone:Notes for One-Line Standard Electrical Diagram for Single-Phase PV SystemsSite Name: Site Address: System AC Size: SIZEFSCM NODWG NOREVE1.2aSCALENTSDate: SHEETDrawn By:Checked By:MAX POWER-POINT CURRENT (IMP)MAX POWER-POINT VOLTAGE (VMP)OPEN-CIRCUIT VOLTAGE (VOC)SHORT-CIRCUIT CURRENT (ISC)MAX SERIES FUSE (OCPD)MAXIMUM POWER (PMAX)MAX VOLTAGE (TYP 600VDC)VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITSMODULE MAKEMODULE MODELPV MODULE RATINGS @ STC (Guide Section 5)MAX DC VOLT RATINGMAX POWER @ 40oCNOMINAL AC VOLTAGEMAX AC CURRENTMAX OCPD RATINGINVERTER MAKEINVERTER MODELINVERTER RATINGS (Guide Section 4)1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9)5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NONOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE.b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE.NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E):OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE®REFERENCES SHOWN AS (NEC XXX.XX)NOTES FOR ALL DRAWINGS:SIGNS–SEE GUIDE SECTION 7SIGN FOR DC DISCONNECTSIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED)No sign necessary since 690.51 marking on PV module covers needed informationAC OUTPUT CURRENTNOMINAL AC VOLTAGESOLAR PV SYSTEMAC POINT OF CONNECTIONTHIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR)Notes for Micro-Inverter Electrical DiagramHanwhaQ Cell Q Peak Duo 340W34033.9440.6610.5220254.532.27xEnphaseIQ7Plus602082902029031.46240-4065xx1.21xQuan Hy2402 S Manitoba Dr Santa Ana8.028KW2/232402 S Manitoba Drive1/23/2024 Expedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. Expedited Permit Process for PV Systems — Micro-Inverter2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. x Composition Shingle x M1 Structural Adhesive x Iron Ridge Flashfoot 2.85 68 23.85 28 502.14 0.0147 ✔ ✔ ✔ Expedited Permit Process for PV Systems 3Micro-Inverter Site Plan&RQWUDFWRU1DPH$GGUHVVDQG3KRQH%LOODQG7HG¶V6RODU([FHOOHQW'ULYH6DQ'LPDV&$6LWH3ODQIRU6PDOO6FDOH6LQJOH3KDVH396\VWHPV6LWH1DPH-RHDQG-DQH+RPHRZQHU6LWH$GGUHVV6XQQ\VLGH6W)RQWDQD&$6\VWHP$&6L]HN:6RODU$UUD\^/&^DEKt'EKZs^>Ed^ĂƚĞ͗^,dƌĂǁŶLJ͗ŚĞĐŬĞĚLJ͗ Expedited Permit Process for PV Systems 4Micro-Inverter Electrical DiagramContractor Name,Address and Phone:One-Line Standard Electrical Diagramfor Micro-Inverter PV SystemsSite Name:Site Address:System AC Size:SIZEFSCM NODWG NOREVE1.1aSCALENTSDate: SHEETDrawn By:Checked By:DESCRIPTION OR CONDUCTOR TYPEUSE-2 or PV WIRE GEC EGC X ALL THAT APPLYEXTERIOR CABLE LISTED W/ INV.THWN-2 or XHHW-2 or RHW-2GEC EGC X ALL THAT APPLYNO DC GEC IF 690.35 SYSTEMTHWN-2 or XHHW-2 or RHW-2GEC EGC X ALL THAT APPLYTAG12345CONDUIT AND CONDUCTOR SCHEDULECOND.GAUGEMFGMFGNUMBER OFCONDUCTORSMFG CableMFG CableCONDUITTYPEN/AN/AN/ASAMESAMECONDUITSIZEN/AN/AN/ASAMESAMEDESCRIPTIONPV DC or AC MODULEDC/AC INVERTER (MICRO)J-BOX (IF USED)PV ARRAYAC COMB. PANEL (IF USED)GEN METER (IF USED)AC DISCONNECT (IF USED)SERVICE PANELTAG12345678PART NUMBERNOTESFOR UNUSED MODULESPUT "N/A” in BLANK ABOVE11323EQUIPMENT SCHEDULE2_____MICRO-INVERTERSIN BRANCH-CIRCUITMOD____DCACMOD____DCACMOD____DCACMOD____DCACMOD____DCACMOD____DCACJ-BOX4AC DISCOMBUILDINGGROUNDINGELECTRODEGMUTILITYSERVICEMAIN SERVICE PANELMAINOCPDINVERTEROCPD678545GSEE GUIDE APPENDIX D FORINFORMATION ON MODULE ANDARRAY GROUNDINGAC COMBINERPANELG____MICRO-INVERTERSIN BRANCH-CIRCUITQ Cell Q Peak Duo BLK G6 340WIQ7PlusEnphase Combiner 3Q Cell Q Peak Duo BLK G6 340WNEMA60 AMP Square D DisconnectEaton108xxxxxxxxx12412210482Quan Hy2402 S Manitoba Dr Santa Ana7.542/23 Expedited Permit Process for PV Systems 5Contractor Name,Address and Phone:Notes for One-Line Standard ElectricalDiagram for Single-Phase PV SystemsSite Name:Site Address:System AC Size:SIZEFSCM NODWG NOREVE1.2aSCALENTSDate: SHEETDrawn By:Checked By:MAX POWER-POINT CURRENT (IMP)MAX POWER-POINT VOLTAGE (VMP)OPEN-CIRCUIT VOLTAGE (VOC)SHORT-CIRCUIT CURRENT (ISC)MAX SERIES FUSE (OCPD)MAXIMUM POWER (PMAX)MAX VOLTAGE (TYP 600VDC)VOC TEMP COEFF (mV/oC or %/oC )IF COEFF SUPPLIED, CIRCLE UNITSMODULE MAKEMODULE MODELPV MODULE RATINGS @ STC (Guide Section 5)MAX DC VOLT RATINGMAX POWER @ 40oCNOMINAL AC VOLTAGEMAX AC CURRENTMAX OCPD RATINGINVERTER MAKEINVERTER MODELINVERTER RATINGS (Guide Section 4)1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THEREQUIREMENT? YES NO N/A2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THEREQUIREMENT? YES NO N/A3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAXCURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTEROCPD AMPERE RATING. (See Guide Section 9)5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAREXCEPTION IN 690.64(B)(2)(a)? YES NONOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEANEXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHESTMONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT ATLEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF47oC OR LESS (ALL OF UNITED STATES),a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLERFUSE.b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLERFUSE.NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E):OCPD = OVERCURRENT PROTECTION DEVICENATIONAL ELECTRICAL CODE®REFERENCESSHOWN AS (NEC XXX.XX)NOTES FOR ALL DRAWINGS:SIGNS–SEE GUIDE SECTION 7SIGN FOR DC DISCONNECTSIGN FOR INVERTER OCPD AND ACDISCONNECT (IF USED)No sign necessary since 690.51marking on PV module coversneeded informationAC OUTPUT CURRENTNOMINAL AC VOLTAGESOLAR PV SYSTEMAC POINT OF CONNECTIONTHIS PANEL FED BY MULTIPLESOURCES (UTILITY AND SOLAR)Notes for Micro-Inverter Electrical DiagramHanwhaQ Cell Q Peak Duo 340W34033.9440.6610.5220254.532.27xEnphaseIQ7Plus602082902029031.46240-4065xx1.21xQuan Hy2402 S Manitoba Dr Santa Ana8.028KW2/23 To Whom it may concern, I __________________ as the homeowner am allowing BLC BUILDER CONSTRUCTION Inc, DBA SunGrid Solar to install solar panels on my property located at 2402 S Manitoba Dr, Santa Ana, CA, 92704. Signature: __________________ Date: __________________ DocuSign Envelope ID: 030605A3-B30C-4E7C-92D7-9740700BBBD5 QUAN HY 3/15/2022 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2402 S Manitoba Dr Santa Ana CA 92704 BLC BUILDER CONSTRUCTION 1037212 x x x x x x x x x x Andrew Higgins (949)309-2453 ops@gosungrid.com 2/23/22 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2402 S Manitoba Dr Santa Ana CA 92704 BLC BUILDER CONSTRUCTION 1037212 x x x x x x x x x x Andrew Higgins (949)309-2453 ops@gosungrid.com 2/23/22 2402 1/2 SUNGRID 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. Attn.: To Whom It May Concern re job: QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. Design Criteria: Code:2019 CBC ASCE 7-16 Live Load:20 psf Ult Wind Speed:95 mph Exposure Cat:C Ground Snow:0 psf Min Roof Snow: NA AHZ Consulting Engineers Inc. Professional Engineer projects@ahzengineers.com 1/27/2022 The following calculations are for the structural engineering design of the photovoltaic panels and are valid only for the structural info referenced in the stamped plan set. The verification of such info is the responsibility of others. After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads. All mounting equipment shall be designed and installed per manufacturer's approved installation specifications. www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 2 of 6 Roof Properties: Roof Type = Roof Pitch (deg) = Mean Roof Height (ft) = Attachment Trib Width (ft) = Attachment Spacing (ft) = Framing Type = Framing Size = Framing OC Spacing (in.) = Section Thickness, b (in.) = Section Depth, d (in.) = Section Modulus, Sx (in.^3) = Moment of Inertia, Ix (in.^4) = Framing Span (ft) = Deflection Limit D+L (in.) = Deflection Limit S or W (in.) = Attachments Pattern = Framing Upgrade = Sister Size = Wood Species = Wood Fb (psi) = Wood Fv (psi) = Wood E (psi) = C D (Wind) = C D (Snow) = CLS = C M = Ct = CL = Ci = CF = Cfu = Cr = F'b_wind (psi) = F'b_snow (psi) = F'v_wind (psi) = F'v_snow (psi) = M_allowable_wind (lb-ft) = M_allowable_snow (lb-ft) = V_allowable_wind (lbs) = V_allowable_snow (lbs) = 1139 1121 1584 207 1560 1779 288 1.15 2476 1.3 1.00 1.15 1.0 1.6 1.15 180 1600000 DF #2 900 Adequate NA 2.67 Fully Staggered 20 4 7.6 20.8 1.5 5.5 2x6 16 5.33 Rafter 23 2.75 Shingle 30 Roof 1 www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 3 of 6 E' (psi) = Load Calculation: Panels Dead Load (psf) = Roofing Weight (psf) = Decking Weight (psf) = Framing Weight (psf) = Misc. Additional Weight (psf) = Existing Dead Load (psf) = Total Dead Load (psf) = Ultimate Wind Speed (mph) = Directionality Factor, kd = Topographic Factor, kzt = Velocity Press Exp Factor, kz = Ground Elevation Factor, ke = Velocity Pressure, qz (psf) = Array Edge Factor, γE = Solar Equalization Factor, γa = External Pressure Up, GCp_1 = External Pressure Up, GCp_2 = External Pressure Up, GCp_3 = External Pressure Down, GCp = Design Pressure Up, p_1 (psf) = Design Pressure Up, p_2 (psf) = Design Pressure Up, p_3 (psf) = Design Pressure Down, p (psf) = Hardware Checks: Ref. Widthrawal Value, W (lb/in) = (C M = Ct = Ceg = 1.0) C D = Adjusted Widthrawal Value, W' (lb/in) = Lag Penetration, p (in.) = 426 2.5 266 1.6 Lag Screw Checks: Roof 1 16.0 -26.5 -32.3 0.8 -22.0 -1.8 -2.2 1.25 0.64 -1.5 0.93 1.00 18.2 95 0.85 1.0 Roof 1 Wind Load Calculations: 7.4 10.4 1.4 1.0 3.0 2.0 Dead Load Calculations: 3.0 Roof 1 1600000 www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 4 of 6 Allowable Widthrawal Force, W'p (lbs) = Applied Uplift Force (lbs) = Uplift DCR = Ref. Lateral Value, Z (lbs) = (C M = Ct = CΔ = Ceg = 1.0) C D = Adjusted Lateral Value, Z' (lbs) = Applied Laeral Force (lbs) = Angle of Resultant Force, α (deg) = Adjusted Interaction Lateral Value, Z' α (lbs) = Lateral DCR = Roof Framing Checks: LC1: D+S Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC2: D+0.6W Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC3: D+0.75(S+0.6W) Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC4: 0.6D+0.6W Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = 1560 1584 465 93 0.75 0.15 1560 1584 1175 235 0.86 0.17 1560 1584 1335 267 0.62 0.12 1121 1139 139 Force Checks: Roof 1 695 1038 0.02 22 85 0.9 243 0.24 270 1064 -256 www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 5 of 6 Moment DCR = Shear DCR = LC1: D+L Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC2: S Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC3: W (Down) Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC4: W (Up) Deflection (in.) = Deflection Limit (in.) = Deflection DCR = Seismic Check: Wall Weight (psf) = Tributary Wall Area (ft2) = Total Wall Weight (lbs) = Roof Weight (psf) = Roof Area (ft2) = Total Roof Weight (lbs) = Total Existing Weight (lbs) = PV Panel Weight (lbs) = Number of Panels = Total Additional PV Weight (lbs) = (Existing W + Additional W)/(Existing W)-1 = 0% Additional PV Weight: 54 0 0 Weight Increase: 3000 51000 7 2400 17803 68803 0.44 Existing Weight: 17 -1.34 3.07 3.07 0.32 0.00 0.97 0.00 3.07 4.6 0.49 Deflection Checks (Service Level): Roof 1 2.25 0.30 0.06 www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 6 of 6 The increase in weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. Limits of Scope of Work and Liability: Existing structure is assumed to have been designed and constructed following appropriate codes at time of erection, and assumed to have appropriate permits. The calculations produced are only for the roof framing supporting the proposed PV installation referenced in the stamped planset and were completed according to generally recognized structural analysis standards and procedures, professional engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or were not observable during time of inspection are not included in this scope of work. All PV modules, racking, and mounting equipment shall be designed and installed per manufacturer's approved installation specifications. The Engineer of Record and the engineering consulting firm assume no responsibility for misuse or improper installation. This analysis is not stamped for water leakage. Framing was determined based on information in provided plans and/or photos, along with engineering judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any concerns prior to starting construction. www.ahzengineers.com AC MSPCB SITE PLAN-1 PV-1.0 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC SITE PLAN-1 PV-1.0 A SITE PLAN-1 SCALE: 3/32" = 1'-0" ELECTRIC CODE CEC 2019 FIRE CODE CFC 2019 RESIDENTIAL CODE CRC 2019 BUILDING CODE CBC 2019 WIND SPEED 95 MPH SNOW LOAD 0 PSF GENERAL INFORMATION 3' FIRE SETBACK PV-1.0 A1 VICINITY MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 1'-6" FIRE SETBACK (N) AC DISCONNECT(EXTERIOR) PHOTOVOLTAIC ARRAY ON THE ROOF (E) MAIN SERVICE PANEL(EXTERIOR) (N) ENPHASE IQ COMBINER 3 (EXTERIOR) CONDUIT RUN 15' AC TRENCHED CONDUIT RUN INDEX INDEX NO. DESCRIPTION SITE PLAN-1&2 MICRO SERIAL MAP GENERAL NOTES MOUNTING DETAILS STRUCTURAL DETAILS SINGLE LINE DIAGRAM ELECTRICAL CALCULATION WARNING PLACARDS MODULE SPEC SHEET INVERTER SPEC SHEET COMBINER SPEC SHEET RACKING SPEC SHEET MOUNT SPEC SHEET GROUNDING SPEC SHEET INTEGRATED GROUNDING SPEC SHEET FIRE RATING SPEC SHEET PV-1.0&1.1 PV-1.2 PV-2.0 S-1.0 S-1.1 E-1.0 E-1.1 PV-3.0 PD-1.0 PD-1.1 PD-1.2 PD-1.3 PD-1.4 PD-1.5 PD-1.6 PD-1.7 2402 S Manitoba Dr BLDG # 101109909 ELEC # 20175792 ISSUED 03/31/22 2402 1/2 S Manitoba Dr BLDG #101109910 ELEC #20175794 ISSUED 04/06/22 PD-1.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MODULE SPECSHEET PD-1.1 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 INVERTER SPECSHEET PD-1.2 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 COMBINER SPECSHEET PD-1.3 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 RACKING SPECSHEET PD-1.4 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MOUNT SPECSHEET PD-1.5 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 GROUNDING SPECSHEET PD-1.6 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 INTEGRATED GROUNDING SPECSHEET PD-1.7 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 FIRE RATING SPECSHEET AC MSPCB SITE PLAN-2 PV-1.1 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC SITE PLAN-2 PV-1.1 A SITE PLAN-2 SCALE: 1/16" = 1'-0" PHOTOVOLTAIC ARRAY ON THE ROOF CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 PROPERTY LINE DRIVE WAY S MANITOBA DRGATE-1 GATE-2 151'-5"61'133'-9" 28'-5"12'-2"2'-11" 27'-11" 7'-10" TREE MICRO SERIAL MAP PV-1.2 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC MICRO SERIAL MAP PV-1.2 A MICRO SERIAL MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 GENERAL NOTES PV-2.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 GENERAL NOTES 1. MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS. 2. INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS. 3. DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL SITE CONDITION MIGHT VARY. 4. WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH CEC CODES. 5. ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/ SERVICE EQUIPMENT. 6. ALL CONDUCTORS SHALL BE 600V, 75°C STANDARD COPPER UNLESS OTHERWISE NOTED. 7. WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 8. THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND/OR THE UTILITY. 9. ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREES, WIRES OR SIGNS. 10. PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING EQUIPMENT LOCATION: 11. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY CEC CODES. 12. WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY CEC CODES AND CEC TABLES. 13. JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO CEC CODES. 14. ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 15. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO CEC CODES APPLICABLE CODES. 16. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE . STRUCTURAL NOTES: 17. RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 18. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 19. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. 20. ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 21. WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. WIRING & CONDUIT NOTES: 22. ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. 23. CONDUCTORS SIZED ACCORDING TO CEC CODES . 24. DC WIRING LIMITED TO MODULE FOOTPRINT. MICRO INVERTER WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITH SUITABLE WIRING CLIPS. 25. AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [CEC CODES]. INTERCONNECTION NOTES: 26. LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [CEC CODES]. 27. THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120% OF BUSBAR RATING [CEC CODES]. 28. WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PV DEDICATED BACKFFED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [CEC CODES]. 29. AT MULTIPLE PV OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVER CURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVER CURRENT DEVICE MAY BE EXCLUDED ACCORDING TO CEC CODES . 30. FEEDER TAP INTER CONNECTION (LOAD SIDE) ACCORDING TO CEC CODES. 31. SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO CEC CODES WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH CEC CODES . 32. BACK FEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [CEC CODES]. GROUNDING NOTES: 33. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 34. PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO CEC CODES AND MINIMUM CEC TABLE. 35. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORD. 36. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO CEC CODES AND MICRO INVERTER MANUFACTURER'S INSTRUCTIONS. 37. EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 38. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. 39. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [CEC CODES]. 40. THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC CODES AND NEC THROUGH . IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO CEC CODES AND AHJ. 41. GROUND-FAULT DETECTION SHALL COMPLY WITH CEC CODES IN GENERAL AND CEC CODES SPECIFICALLY. 42. DISCONNECTION AND OVER-CURRENT PROTECTION NOTES. 43. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). 44. DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 45. RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 10 FT OF PV ARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLED CONDUCTORS ≤30V AND ≤240VA [CEC CODES]. LOCATION OF LABEL ACCORDING TO AHJ. 46. ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC CODES. 47. MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH CEC CODES. IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO CEC CODES. GENERAL NOTES MOUNTING DETAILS S-1.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 PV-3.0 B MOUNTING DETAILS SCALE: 3/32" = 1'-0" SITE INFORMATION SR.NO AZIMUTH PITCH NO. OF MODULES ARRAY AREA (SQ. FT.)ROOF TYPE ATTACHMENT ROOF EXPOSURE FRAME TYPE FRAME SIZE FRAME SPACING MAX RAIL SPAN OVER HANG MP-01 180° 30° 8 154.5 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-02 270° 30° 8 154.5 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-03 90° 30° 5 96.6 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-04 180° 30° 3 57.9 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-05 270° 30° 2 38.6 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" DEAD LOAD CALCULATIONS BOM QUANTITY LBS/UNIT TOTAL WEIGHT (LBS) MODULES 26 43.9 1141.40 MID-CLAMP 30 0.050 1.50 END-CLAMP 44 0.050 2.20 RAIL LENGTH 191 0.680 129.88 SPLICE BAR 2 0.360 0.72 FLASH FOOT 68 1.35 91.80 MICRO-INVERTER 26 2.38 61.88 TOTAL WEIGHT OF THE SYSTEM (LBS)1429.38 TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)502.14 WEIGHT PER SQ. FT.(LBS)2.85 WEIGHT PER PENETRATION (LBS)21.02 UPLIFT CALCULATIONS UPLIFT 15064.3 LBS PULL OUT STRENGTH 41820 LBS POINT LOADING 17 LBS MODULES DATA HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULE DIMS 68.5"x40.6"x1.26" LAG SCREWS 5/16"x3.5":2.5"MIN EMBEDMENT ALUMINIUM RAILS MINIMUM FIRE ACCESS PATHWAYS PER CEC 2019 RIDGE TO ARRAY: 3'-0" EAVE TO ARRAY : 3'-0" HIP/VALLEY W/ ADJACENT ARRAY: 1'-6" EACH SIDE HIP/VALLEY W/O ADJACENT ARRAY: 0'-0" NOTE: INSTALLER TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY ANY DISCREPANCIES BEFORE PROCEEDING. FIRE SETBACK 2 X 6 RAFTERS @ 1'-4"SPACING ARRAY MP-01 ARRAY MP-02 ARRAY MP-03 ARRAY MP-04 ARRAY MP-05 3'1'-6"5'-4" STRUCTURAL DETAILS S-1.1 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MID-CLAMP & END CLAMP DETAIL GROUNDING DETAILS MID CLAMP ASSEMBLY MODULE FRAME RAIL GROUNDING MID-CLAMP SCALE: NTS MODULE TO MODULE & MODULE TO RAIL GROUNDING RAIL TO RAIL IRON RIDGE RAIL INTERNAL SPLICE SELF-DRILLING SCREW SCALE: NTS T BOLT SCALE: NTS PV MODULE IRONRIDGE RAIL IRONRIDGE STOPPER SLEEVE END CLAMP PV MODULE IRONRIDGE RAIL MID CLAMP SCALE: NTS FLASHFOOT SOLAR MODULE RAIL 6" MAX 2 X 6 RAFTERS@1'-4" SPACING LOAD BEARING WALL ROOF FRAMING DETAIL SCALE: NTS SCALE: NTS ATTACHMENT DETAIL - FLASHFOOT 5/16 HEX-BOLT STAINLESS STEEL 5/16" HANGER BOLT 2.5" EMBEDMENT PILOT HOLE REQUIRED (E)COMPOSITION SHINGLE ROOF IRONRIDGE FLASHFOOT IRONRIDGE XR10 RAIL PV MODULE (E) BUILDING STRUCTURE ELECTRICAL CALCULATION E-1.1 ELECTRICAL CALCULATION CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MODULE SPECIFICATION MODEL HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULE POWER @ STC 340W OPEN CIRCUIT VOLTAGE:Voc 40.66V MAX POWER VOLTAGE:Vmp 33.94V SHORT CIRCUIT VOLTAGE:Isc 10.52A MAX POWER CURRENT:Imp 10.02A MICRO INVERTER SPECIFICATIONS MODEL ENPHASE IQ7PLUS-72-2-US (240V,1PH) POWER RATING 290W MAX OUTPUT CURRENT 1.21A CEC WEIGHTED EFFICIENCY 97% MAX NO OF MICRO INVERTERS/BRANCH 13 MAX DC VOLTAGE 60V ELECTRICAL NOTES: 1. MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%. 2. BREAKER/FUSE SIZES CONFORMS TO CEC 240.6 CODE SECTION. 3. AC GROUNDING ELECTRODE CONDUCTOR SIZED PER CEC 250.66. 4. AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON CEC 690.31(A). 5. AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON CEC 310.15(B)(2). 6. MAX. SYSTEM VOLTAGE CORRECTION IS PER CEC 690.7. 7. CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE CEC 310.15(B)(16). 8. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER CEC 310.10(D). 9. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER CEC 310.10(C). ELECTRICAL CALCULATION AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION TERMINAL RATING CHECK DERATED CONDUCTOR AMPACITY CHECK 1 1.21 X 8 = 9.68 X 1.25 = 12.10A 30 X 0.96 X 1 =28.80A 12.10A <25A 12.10A <28.80A 2 1.21 X 8 = 9.68 X 1.25 = 12.10A 40 X 0.96 X 0.8 =30.72A 12.10A <35A 12.10A <30.72A 1A 1.21 X 10 = 12.10 X 1.25 = 15.13A 30 X 0.96 X 1 =28.80A 15.13A <25A 15.13A <28.80A 2A 1.21 X 10 = 12.10 X 1.25 = 15.13A 40 X 0.96 X 1 =38.40A 15.13A <35A 15.13A <38.40A 3 1.21 X 26 = 31.46 X 1.25 = 39.33A 55 X 0.96 X 1 =52.80A 39.33A <50A 39.33A <52.80A AC MSPCB PV-3.0 POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN WARNING ! CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE RED WITH WHITE LETTERING U.O.N. PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.FASTENERS APPROVED BY THE LOCAL JURISDICTION 2402 S MANITOBA DR, SANTA ANA, CA 92704. WARNING PLACARDS WARNING PLACARDS NOTE:ALL SIGNAGE CANNOT BE HAND WRITTEN CEC 110.21 PHOTOVOLTAIC ARRAY ON THE ROOF WARNING CAUTION: SOLAR CIRCUIT LABEL LOCATION POINT OF INTERCONNECTION (PER CODE: CEC 705.12(2)(b) [ Not Required if Panel board is rated not less than sum of ampere ratings of all overcurrent devices supplying it] WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVER-CURRENT DEVICE WARNING:PHOTOVOLTAIC POWER SOURCE LABEL LOCATION CONDUIT, COMBINER BOX [PER CODE: CEC690.31(G)(3)] WARNING-Electric Shock Hazard No User Serviceable Parts inside Contact authorized service provide for assistance LABEL LOCATION INVERTER, JUNCTION BOXES(ROOF), AC DISCONNECT [PER CODE: CEC 690.13] LABEL LOCATION DISCONNECT, POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] LABEL LOCATION AC DISCONNECT , POINT OF INTERCONNECTION [PER CODE: CEC 690.54] LABEL LOCATION MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT LEAST EVERY 10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL COMBINER/JUNCTION BOXES. (PER CODE: CFC605.11.1.4) LABEL LOCATION POINT OF INTERCONNECTION [PER CODE: CEC705.12(D)(4)] ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] LABEL LOCATION WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE, UL969 AS STANDARD TO WEATHER RATING (UL LISTING OF MARKINGS NOT REQUIRED), MIN 3 8" LETTER HEIGHT ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN THE MAIN SERVICE DISCONNECT,PLACED ON THE OUTSIDE OF THE COVER WHEN DISCONNECT IS OPERATED WITH THE SERVICE PANEL CLOSED. (PWER CODE: CEC690.15 ,690.13(B)) WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM SOLAR DISCONNECT RATED AC OPERATING CURRENT AC NOMINAL OPERATING VOLTAGE 31.46 240 AMPS AC VAC PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN LABEL LOCATION AC DISCONNECT, DC DISCONNECT, POINT OF INTERCONNECTION (PER CODE: CEC690.56(C)(1)(A)) LABEL LOCATION INVERTER,POINT OF INTERCONNECTION [PER CODE: CEC 690.56(C)(3)] RAPID SHUTDOWN SWITCH FOR SOLAR SYSTEM SYSTEM UTILIZES MICRO-INVERTERS LOCATED UNDER SOLAR MODULE (E) MAIN SERVICE PANEL(EXTERIOR) (N) AC DISCONNECT(EXTERIOR) (N) ENPHASE IQ COMBINER 3 (EXTERIOR) Certificate Of Completion Envelope Id: 8E8E8263F6CD4DC78D1F8B88EE88CDB7 Status: Completed Subject: Please DocuSign: SunGrid Solar Plan Set Approval Source Envelope: Document Pages: 18 Signatures: 1 Envelope Originator: Certificate Pages: 2 Initials: 0 SunGrid Solar AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 17280 newhope st unit 18 Fountain Valley, CA 92708 ops@gosungrid.com IP Address: 98.186.153.107 Record Tracking Status: Original 1/27/2022 10:54:13 AM Holder: SunGrid Solar ops@gosungrid.com Location: DocuSign Signer Events Signature Timestamp QUAN HY quanchihy@yahoo.com Security Level: Email, Account Authentication (None) Signature Adoption: Drawn on Device Using IP Address: 76.175.219.199 Signed using mobile Sent: 1/27/2022 10:56:05 AM Viewed: 1/28/2022 6:08:17 PM Signed: 1/28/2022 6:50:46 PM Electronic Record and Signature Disclosure: Not Offered via DocuSign In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp Felicia Gonzalez felicia@gosungrid.com Security Level: Email, Account Authentication (None) Sent: 1/27/2022 10:56:05 AM Electronic Record and Signature Disclosure: Not Offered via DocuSign Andrew Higgins Andrew@gosungrid.com CEO BLC Builder Constructio Security Level: Email, Account Authentication (None) Sent: 1/27/2022 10:56:04 AM Electronic Record and Signature Disclosure: Not Offered via DocuSign Carbon Copy Events Status Timestamp SunGrid Solar ops@gosungrid.com CEO BLC Builder Construction Inc (DBA SunGrid Solar) Security Level: Email, Account Authentication (None) Sent: 1/27/2022 10:56:05 AM Resent: 1/28/2022 6:50:51 PM Electronic Record and Signature Disclosure: Not Offered via DocuSign Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 1/27/2022 10:56:05 AM Certified Delivered Security Checked 1/28/2022 6:08:17 PM Signing Complete Security Checked 1/28/2022 6:50:46 PM Completed Security Checked 1/28/2022 6:50:46 PM Payment Events Status Timestamps Expedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. Expedited Permit Process for PV Systems — Micro-Inverter2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. x Composition Shingle x M1 Structural Adhesive x Iron Ridge Flashfoot 2.85 68 23.85 28 502.14 0.0147 ✔ ✔ ✔ Expedited Permit Process for PV Systems 3Micro-Inverter Site Plan&RQWUDFWRU1DPH$GGUHVVDQG3KRQH%LOODQG7HG¶V6RODU([FHOOHQW'ULYH6DQ'LPDV&$6LWH3ODQIRU6PDOO6FDOH6LQJOH3KDVH396\VWHPV6LWH1DPH-RHDQG-DQH+RPHRZQHU6LWH$GGUHVV6XQQ\VLGH6W)RQWDQD&$6\VWHP$&6L]HN:6RODU$UUD\^/&^DEKt'EKZs^>Ed^ĂƚĞ͗^,dƌĂǁŶLJ͗ŚĞĐŬĞĚLJ͗ Expedited Permit Process for PV Systems 4Micro-Inverter Electrical DiagramContractor Name,Address and Phone:One-Line Standard Electrical Diagramfor Micro-Inverter PV SystemsSite Name:Site Address:System AC Size:SIZEFSCM NODWG NOREVE1.1aSCALENTSDate: SHEETDrawn By:Checked By:DESCRIPTION OR CONDUCTOR TYPEUSE-2 or PV WIRE GEC EGC X ALL THAT APPLYEXTERIOR CABLE LISTED W/ INV.THWN-2 or XHHW-2 or RHW-2GEC EGC X ALL THAT APPLYNO DC GEC IF 690.35 SYSTEMTHWN-2 or XHHW-2 or RHW-2GEC EGC X ALL THAT APPLYTAG12345CONDUIT AND CONDUCTOR SCHEDULECOND.GAUGEMFGMFGNUMBER OFCONDUCTORSMFG CableMFG CableCONDUITTYPEN/AN/AN/ASAMESAMECONDUITSIZEN/AN/AN/ASAMESAMEDESCRIPTIONPV DC or AC MODULEDC/AC INVERTER (MICRO)J-BOX (IF USED)PV ARRAYAC COMB. PANEL (IF USED)GEN METER (IF USED)AC DISCONNECT (IF USED)SERVICE PANELTAG12345678PART NUMBERNOTESFOR UNUSED MODULESPUT "N/A” in BLANK ABOVE11323EQUIPMENT SCHEDULE2_____MICRO-INVERTERSIN BRANCH-CIRCUITMOD____DCACMOD____DCACMOD____DCACMOD____DCACMOD____DCACMOD____DCACJ-BOX4AC DISCOMBUILDINGGROUNDINGELECTRODEGMUTILITYSERVICEMAIN SERVICE PANELMAINOCPDINVERTEROCPD678545GSEE GUIDE APPENDIX D FORINFORMATION ON MODULE ANDARRAY GROUNDINGAC COMBINERPANELG____MICRO-INVERTERSIN BRANCH-CIRCUITQ Cell Q Peak Duo BLK G6 340WIQ7PlusEnphase Combiner 3Q Cell Q Peak Duo BLK G6 340WNEMA60 AMP Square D DisconnectEaton108xxxxxxxxx12412210482Quan Hy2402 S Manitoba Dr Santa Ana7.542/23 Expedited Permit Process for PV Systems 5Contractor Name,Address and Phone:Notes for One-Line Standard ElectricalDiagram for Single-Phase PV SystemsSite Name:Site Address:System AC Size:SIZEFSCM NODWG NOREVE1.2aSCALENTSDate: SHEETDrawn By:Checked By:MAX POWER-POINT CURRENT (IMP)MAX POWER-POINT VOLTAGE (VMP)OPEN-CIRCUIT VOLTAGE (VOC)SHORT-CIRCUIT CURRENT (ISC)MAX SERIES FUSE (OCPD)MAXIMUM POWER (PMAX)MAX VOLTAGE (TYP 600VDC)VOC TEMP COEFF (mV/oC or %/oC )IF COEFF SUPPLIED, CIRCLE UNITSMODULE MAKEMODULE MODELPV MODULE RATINGS @ STC (Guide Section 5)MAX DC VOLT RATINGMAX POWER @ 40oCNOMINAL AC VOLTAGEMAX AC CURRENTMAX OCPD RATINGINVERTER MAKEINVERTER MODELINVERTER RATINGS (Guide Section 4)1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THEREQUIREMENT? YES NO N/A2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THEREQUIREMENT? YES NO N/A3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAXCURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTEROCPD AMPERE RATING. (See Guide Section 9)5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAREXCEPTION IN 690.64(B)(2)(a)? YES NONOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEANEXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHESTMONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT ATLEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF47oC OR LESS (ALL OF UNITED STATES),a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLERFUSE.b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLERFUSE.NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E):OCPD = OVERCURRENT PROTECTION DEVICENATIONAL ELECTRICAL CODE®REFERENCESSHOWN AS (NEC XXX.XX)NOTES FOR ALL DRAWINGS:SIGNS–SEE GUIDE SECTION 7SIGN FOR DC DISCONNECTSIGN FOR INVERTER OCPD AND ACDISCONNECT (IF USED)No sign necessary since 690.51marking on PV module coversneeded informationAC OUTPUT CURRENTNOMINAL AC VOLTAGESOLAR PV SYSTEMAC POINT OF CONNECTIONTHIS PANEL FED BY MULTIPLESOURCES (UTILITY AND SOLAR)Notes for Micro-Inverter Electrical DiagramHanwhaQ Cell Q Peak Duo 340W34033.9440.6610.5220254.532.27xEnphaseIQ7Plus602082902029031.46240-4065xx1.21xQuan Hy2402 S Manitoba Dr Santa Ana8.028KW2/23 To Whom it may concern, I __________________ as the homeowner am allowing BLC BUILDER CONSTRUCTION Inc, DBA SunGrid Solar to install solar panels on my property located at 2402 S Manitoba Dr, Santa Ana, CA, 92704. Signature: __________________ Date: __________________ DocuSign Envelope ID: 030605A3-B30C-4E7C-92D7-9740700BBBD5 QUAN HY 3/15/2022 2402 S Manitoba Drive04/19/22 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2402 S Manitoba Dr Santa Ana CA 92704 BLC BUILDER CONSTRUCTION 1037212 x x x x x x x x x x Andrew Higgins (949)309-2453 ops@gosungrid.com 2/23/22 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2402 S Manitoba Dr Santa Ana CA 92704 BLC BUILDER CONSTRUCTION 1037212 x x x x x x x x x x Andrew Higgins (949)309-2453 ops@gosungrid.com 2/23/22 2402 1/2 SUNGRID 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. Attn.: To Whom It May Concern re job: QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. Design Criteria: Code:2019 CBC ASCE 7-16 Live Load:20 psf Ult Wind Speed:95 mph Exposure Cat:C Ground Snow:0 psf Min Roof Snow: NA AHZ Consulting Engineers Inc. Professional Engineer projects@ahzengineers.com 1/27/2022 The following calculations are for the structural engineering design of the photovoltaic panels and are valid only for the structural info referenced in the stamped plan set. The verification of such info is the responsibility of others. After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads. All mounting equipment shall be designed and installed per manufacturer's approved installation specifications. www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 2 of 6 Roof Properties: Roof Type = Roof Pitch (deg) = Mean Roof Height (ft) = Attachment Trib Width (ft) = Attachment Spacing (ft) = Framing Type = Framing Size = Framing OC Spacing (in.) = Section Thickness, b (in.) = Section Depth, d (in.) = Section Modulus, Sx (in.^3) = Moment of Inertia, Ix (in.^4) = Framing Span (ft) = Deflection Limit D+L (in.) = Deflection Limit S or W (in.) = Attachments Pattern = Framing Upgrade = Sister Size = Wood Species = Wood Fb (psi) = Wood Fv (psi) = Wood E (psi) = C D (Wind) = C D (Snow) = CLS = C M = Ct = CL = Ci = CF = Cfu = Cr = F'b_wind (psi) = F'b_snow (psi) = F'v_wind (psi) = F'v_snow (psi) = M_allowable_wind (lb-ft) = M_allowable_snow (lb-ft) = V_allowable_wind (lbs) = V_allowable_snow (lbs) = 1139 1121 1584 207 1560 1779 288 1.15 2476 1.3 1.00 1.15 1.0 1.6 1.15 180 1600000 DF #2 900 Adequate NA 2.67 Fully Staggered 20 4 7.6 20.8 1.5 5.5 2x6 16 5.33 Rafter 23 2.75 Shingle 30 Roof 1 www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 3 of 6 E' (psi) = Load Calculation: Panels Dead Load (psf) = Roofing Weight (psf) = Decking Weight (psf) = Framing Weight (psf) = Misc. Additional Weight (psf) = Existing Dead Load (psf) = Total Dead Load (psf) = Ultimate Wind Speed (mph) = Directionality Factor, kd = Topographic Factor, kzt = Velocity Press Exp Factor, kz = Ground Elevation Factor, ke = Velocity Pressure, qz (psf) = Array Edge Factor, γE = Solar Equalization Factor, γa = External Pressure Up, GCp_1 = External Pressure Up, GCp_2 = External Pressure Up, GCp_3 = External Pressure Down, GCp = Design Pressure Up, p_1 (psf) = Design Pressure Up, p_2 (psf) = Design Pressure Up, p_3 (psf) = Design Pressure Down, p (psf) = Hardware Checks: Ref. Widthrawal Value, W (lb/in) = (C M = Ct = Ceg = 1.0) C D = Adjusted Widthrawal Value, W' (lb/in) = Lag Penetration, p (in.) = 426 2.5 266 1.6 Lag Screw Checks: Roof 1 16.0 -26.5 -32.3 0.8 -22.0 -1.8 -2.2 1.25 0.64 -1.5 0.93 1.00 18.2 95 0.85 1.0 Roof 1 Wind Load Calculations: 7.4 10.4 1.4 1.0 3.0 2.0 Dead Load Calculations: 3.0 Roof 1 1600000 www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 4 of 6 Allowable Widthrawal Force, W'p (lbs) = Applied Uplift Force (lbs) = Uplift DCR = Ref. Lateral Value, Z (lbs) = (C M = Ct = CΔ = Ceg = 1.0) C D = Adjusted Lateral Value, Z' (lbs) = Applied Laeral Force (lbs) = Angle of Resultant Force, α (deg) = Adjusted Interaction Lateral Value, Z' α (lbs) = Lateral DCR = Roof Framing Checks: LC1: D+S Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC2: D+0.6W Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC3: D+0.75(S+0.6W) Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC4: 0.6D+0.6W Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = 1560 1584 465 93 0.75 0.15 1560 1584 1175 235 0.86 0.17 1560 1584 1335 267 0.62 0.12 1121 1139 139 Force Checks: Roof 1 695 1038 0.02 22 85 0.9 243 0.24 270 1064 -256 www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 5 of 6 Moment DCR = Shear DCR = LC1: D+L Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC2: S Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC3: W (Down) Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC4: W (Up) Deflection (in.) = Deflection Limit (in.) = Deflection DCR = Seismic Check: Wall Weight (psf) = Tributary Wall Area (ft2) = Total Wall Weight (lbs) = Roof Weight (psf) = Roof Area (ft2) = Total Roof Weight (lbs) = Total Existing Weight (lbs) = PV Panel Weight (lbs) = Number of Panels = Total Additional PV Weight (lbs) = (Existing W + Additional W)/(Existing W)-1 = 0% Additional PV Weight: 54 0 0 Weight Increase: 3000 51000 7 2400 17803 68803 0.44 Existing Weight: 17 -1.34 3.07 3.07 0.32 0.00 0.97 0.00 3.07 4.6 0.49 Deflection Checks (Service Level): Roof 1 2.25 0.30 0.06 www.ahzengineers.com Date :1/27/2022 Job Code: QUAN HY 6 of 6 The increase in weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. Limits of Scope of Work and Liability: Existing structure is assumed to have been designed and constructed following appropriate codes at time of erection, and assumed to have appropriate permits. The calculations produced are only for the roof framing supporting the proposed PV installation referenced in the stamped planset and were completed according to generally recognized structural analysis standards and procedures, professional engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or were not observable during time of inspection are not included in this scope of work. All PV modules, racking, and mounting equipment shall be designed and installed per manufacturer's approved installation specifications. The Engineer of Record and the engineering consulting firm assume no responsibility for misuse or improper installation. This analysis is not stamped for water leakage. Framing was determined based on information in provided plans and/or photos, along with engineering judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any concerns prior to starting construction. www.ahzengineers.com AC MSPCB SITE PLAN-1 PV-1.0 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC SITE PLAN-1 PV-1.0 A SITE PLAN-1 SCALE: 3/32" = 1'-0" ELECTRIC CODE CEC 2019 FIRE CODE CFC 2019 RESIDENTIAL CODE CRC 2019 BUILDING CODE CBC 2019 WIND SPEED 95 MPH SNOW LOAD 0 PSF GENERAL INFORMATION 3' FIRE SETBACK PV-1.0 A1 VICINITY MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 1'-6" FIRE SETBACK (N) AC DISCONNECT(EXTERIOR) PHOTOVOLTAIC ARRAY ON THE ROOF (E) MAIN SERVICE PANEL(EXTERIOR) (N) ENPHASE IQ COMBINER 3 (EXTERIOR) CONDUIT RUN 15' AC TRENCHED CONDUIT RUN INDEX INDEX NO. DESCRIPTION SITE PLAN-1&2 MICRO SERIAL MAP GENERAL NOTES MOUNTING DETAILS STRUCTURAL DETAILS SINGLE LINE DIAGRAM ELECTRICAL CALCULATION WARNING PLACARDS MODULE SPEC SHEET INVERTER SPEC SHEET COMBINER SPEC SHEET RACKING SPEC SHEET MOUNT SPEC SHEET GROUNDING SPEC SHEET INTEGRATED GROUNDING SPEC SHEET FIRE RATING SPEC SHEET PV-1.0&1.1 PV-1.2 PV-2.0 S-1.0 S-1.1 E-1.0 E-1.1 PV-3.0 PD-1.0 PD-1.1 PD-1.2 PD-1.3 PD-1.4 PD-1.5 PD-1.6 PD-1.7 2402 S Manitoba Dr BLDG # 101109909 ELEC # 20175792 ISSUED 03/31/22 2402 1/2 S Manitoba Dr BLDG #101109910 ELEC #20175794 ISSUED 04/06/22 PD-1.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MODULE SPECSHEET PD-1.1 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 INVERTER SPECSHEET PD-1.2 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 COMBINER SPECSHEET PD-1.3 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 RACKING SPECSHEET PD-1.4 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MOUNT SPECSHEET PD-1.5 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 GROUNDING SPECSHEET PD-1.6 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 INTEGRATED GROUNDING SPECSHEET PD-1.7 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 FIRE RATING SPECSHEET AC MSPCB SITE PLAN-2 PV-1.1 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC SITE PLAN-2 PV-1.1 A SITE PLAN-2 SCALE: 1/16" = 1'-0" PHOTOVOLTAIC ARRAY ON THE ROOF CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 PROPERTY LINE DRIVE WAY S MANITOBA DRGATE-1 GATE-2 151'-5"61'133'-9" 28'-5"12'-2"2'-11" 27'-11" 7'-10" TREE MICRO SERIAL MAP PV-1.2 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC MICRO SERIAL MAP PV-1.2 A MICRO SERIAL MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 GENERAL NOTES PV-2.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 GENERAL NOTES 1. MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS. 2. INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS. 3. DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL SITE CONDITION MIGHT VARY. 4. WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH CEC CODES. 5. ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/ SERVICE EQUIPMENT. 6. ALL CONDUCTORS SHALL BE 600V, 75°C STANDARD COPPER UNLESS OTHERWISE NOTED. 7. WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 8. THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND/OR THE UTILITY. 9. ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREES, WIRES OR SIGNS. 10. PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING EQUIPMENT LOCATION: 11. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY CEC CODES. 12. WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY CEC CODES AND CEC TABLES. 13. JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO CEC CODES. 14. ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 15. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO CEC CODES APPLICABLE CODES. 16. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE . STRUCTURAL NOTES: 17. RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 18. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 19. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. 20. ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 21. WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. WIRING & CONDUIT NOTES: 22. ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. 23. CONDUCTORS SIZED ACCORDING TO CEC CODES . 24. DC WIRING LIMITED TO MODULE FOOTPRINT. MICRO INVERTER WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITH SUITABLE WIRING CLIPS. 25. AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [CEC CODES]. INTERCONNECTION NOTES: 26. LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [CEC CODES]. 27. THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120% OF BUSBAR RATING [CEC CODES]. 28. WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PV DEDICATED BACKFFED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [CEC CODES]. 29. AT MULTIPLE PV OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVER CURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVER CURRENT DEVICE MAY BE EXCLUDED ACCORDING TO CEC CODES . 30. FEEDER TAP INTER CONNECTION (LOAD SIDE) ACCORDING TO CEC CODES. 31. SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO CEC CODES WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH CEC CODES . 32. BACK FEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [CEC CODES]. GROUNDING NOTES: 33. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 34. PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO CEC CODES AND MINIMUM CEC TABLE. 35. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORD. 36. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO CEC CODES AND MICRO INVERTER MANUFACTURER'S INSTRUCTIONS. 37. EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 38. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. 39. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [CEC CODES]. 40. THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC CODES AND NEC THROUGH . IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO CEC CODES AND AHJ. 41. GROUND-FAULT DETECTION SHALL COMPLY WITH CEC CODES IN GENERAL AND CEC CODES SPECIFICALLY. 42. DISCONNECTION AND OVER-CURRENT PROTECTION NOTES. 43. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). 44. DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 45. RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 10 FT OF PV ARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLED CONDUCTORS ≤30V AND ≤240VA [CEC CODES]. LOCATION OF LABEL ACCORDING TO AHJ. 46. ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC CODES. 47. MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH CEC CODES. IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO CEC CODES. GENERAL NOTES MOUNTING DETAILS S-1.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 PV-3.0 B MOUNTING DETAILS SCALE: 3/32" = 1'-0" SITE INFORMATION SR.NO AZIMUTH PITCH NO. OF MODULES ARRAY AREA (SQ. FT.)ROOF TYPE ATTACHMENT ROOF EXPOSURE FRAME TYPE FRAME SIZE FRAME SPACING MAX RAIL SPAN OVER HANG MP-01 180° 30° 8 154.5 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-02 270° 30° 8 154.5 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-03 90° 30° 5 96.6 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-04 180° 30° 3 57.9 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-05 270° 30° 2 38.6 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" DEAD LOAD CALCULATIONS BOM QUANTITY LBS/UNIT TOTAL WEIGHT (LBS) MODULES 26 43.9 1141.40 MID-CLAMP 30 0.050 1.50 END-CLAMP 44 0.050 2.20 RAIL LENGTH 191 0.680 129.88 SPLICE BAR 2 0.360 0.72 FLASH FOOT 68 1.35 91.80 MICRO-INVERTER 26 2.38 61.88 TOTAL WEIGHT OF THE SYSTEM (LBS)1429.38 TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)502.14 WEIGHT PER SQ. FT.(LBS)2.85 WEIGHT PER PENETRATION (LBS)21.02 UPLIFT CALCULATIONS UPLIFT 15064.3 LBS PULL OUT STRENGTH 41820 LBS POINT LOADING 17 LBS MODULES DATA HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULE DIMS 68.5"x40.6"x1.26" LAG SCREWS 5/16"x3.5":2.5"MIN EMBEDMENT ALUMINIUM RAILS MINIMUM FIRE ACCESS PATHWAYS PER CEC 2019 RIDGE TO ARRAY: 3'-0" EAVE TO ARRAY : 3'-0" HIP/VALLEY W/ ADJACENT ARRAY: 1'-6" EACH SIDE HIP/VALLEY W/O ADJACENT ARRAY: 0'-0" NOTE: INSTALLER TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY ANY DISCREPANCIES BEFORE PROCEEDING. FIRE SETBACK 2 X 6 RAFTERS @ 1'-4"SPACING ARRAY MP-01 ARRAY MP-02 ARRAY MP-03 ARRAY MP-04 ARRAY MP-05 3'1'-6"5'-4" STRUCTURAL DETAILS S-1.1 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MID-CLAMP & END CLAMP DETAIL GROUNDING DETAILS MID CLAMP ASSEMBLY MODULE FRAME RAIL GROUNDING MID-CLAMP SCALE: NTS MODULE TO MODULE & MODULE TO RAIL GROUNDING RAIL TO RAIL IRON RIDGE RAIL INTERNAL SPLICE SELF-DRILLING SCREW SCALE: NTS T BOLT SCALE: NTS PV MODULE IRONRIDGE RAIL IRONRIDGE STOPPER SLEEVE END CLAMP PV MODULE IRONRIDGE RAIL MID CLAMP SCALE: NTS FLASHFOOT SOLAR MODULE RAIL 6" MAX 2 X 6 RAFTERS@1'-4" SPACING LOAD BEARING WALL ROOF FRAMING DETAIL SCALE: NTS SCALE: NTS ATTACHMENT DETAIL - FLASHFOOT 5/16 HEX-BOLT STAINLESS STEEL 5/16" HANGER BOLT 2.5" EMBEDMENT PILOT HOLE REQUIRED (E)COMPOSITION SHINGLE ROOF IRONRIDGE FLASHFOOT IRONRIDGE XR10 RAIL PV MODULE (E) BUILDING STRUCTURE 3 (E)200A MAIN BREAKER M PV BREAKER AT THE OPPOSITE END OF BUSBAR 40A 2P PV BREAKER EXISTING 120/240V 1PH 60HZUTILITYGRID (E)GROUND ELECTRODE (E)200A END FED MAIN PANEL UTILITY:SCE 222012-778830 (N)JUNCTION BOX OR EQUIV (N)(16)ENPHASE IQ7PLUS-72-2-US (240V,1PH) WITH (16)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULES 1 (1) BRANCH OF (8) MICRO-INVERTERS(8 MODULES) (1) BRANCH OF (8) MICRO-INVERTERS(8 MODULES) (N)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W, 340W MODULES 20A AC COMBINER WITH ENPHASE ENVOY-S EN-X-IQ-AM1-240-3 120/240 NEMA 3R INSTALL (3)20A PV 2P BREAKERS(ONLY FOR SOLAR NO LOAD TO BE ADDED) (N)ENPHASE IQ COMBINER 3 15A 2 3 20A (N)60A AC DISCONNECT SQUARE D DU222RB AC DISCONNECT NON FUSED 60A, 120/240V, 2P (N)JUNCTION BOX OR EQUIV (N)(10)ENPHASE IQ7PLUS-72-2-US (240V,1PH) WITH (10)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULES 1A (1) BRANCH OF (10) MICRO-INVERTERS(10 MODULES) (N)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W, 340W MODULES 2A 20A SINGLE LINE DIAGRAM E-1.0 SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 8840W, AC SYSTEM SIZE - 7540W,CEC AC SYSTEM SIZE - 8028W CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 NOTE: 1. MICROINVERTERS ARE UL 1741 RATED 2. EACH MICROINVERTER IS RAPID SHUTDOWN COMPLAINT CONDUIT SCHEDULE TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND 1 NONE (4) 12 ENPHASE Q CABLE PER BRANCH CIRCUIT NONE (1) 6 AWG BARE COPPER 2 3/4"EMT OR EQUIV (4) 10 AWG THHN/THWN-2 NONE (1) 10 AWG THHN/THWN-2 1A NONE (2) 12 ENPHASE Q CABLE PER BRANCH CIRCUIT NONE (1) 6 AWG BARE COPPER 2A 3/4" SCH 40 PVC (BELOW GROUND) 3/4" SCH 80 PVC (ABOVE GROUND) (2) 10 AWG THHN/THWN-2 NONE (1) 10 AWG THHN/THWN-2 3 3/4"EMT OR EQUIV (2) 8 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2 OCPD CALCULATIONS: MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A 120% RULE: (200AX1.2)-200A=40A =>ALLOWABLE BACKFEED IS 40A INVERTER OVERCURRENT PROTECTION= INVERTER O/P I X CONTINUOUS LOAD(1.25)X #OF INVERTERS =1.21x1.25x26=39.33 A =>PV BREAKER = 40A ALLOWABLE BACKFEED 40A =>40A PV BREAKER THE DESIGNED INTERCONNECTION MEETS THE 705.12(B)(2) REQUIREMENTS ELECTRICAL CALCULATION E-1.1 ELECTRICAL CALCULATION CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MODULE SPECIFICATION MODEL HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULE POWER @ STC 340W OPEN CIRCUIT VOLTAGE:Voc 40.66V MAX POWER VOLTAGE:Vmp 33.94V SHORT CIRCUIT VOLTAGE:Isc 10.52A MAX POWER CURRENT:Imp 10.02A MICRO INVERTER SPECIFICATIONS MODEL ENPHASE IQ7PLUS-72-2-US (240V,1PH) POWER RATING 290W MAX OUTPUT CURRENT 1.21A CEC WEIGHTED EFFICIENCY 97% MAX NO OF MICRO INVERTERS/BRANCH 13 MAX DC VOLTAGE 60V ELECTRICAL NOTES: 1. MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%. 2. BREAKER/FUSE SIZES CONFORMS TO CEC 240.6 CODE SECTION. 3. AC GROUNDING ELECTRODE CONDUCTOR SIZED PER CEC 250.66. 4. AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON CEC 690.31(A). 5. AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON CEC 310.15(B)(2). 6. MAX. SYSTEM VOLTAGE CORRECTION IS PER CEC 690.7. 7. CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE CEC 310.15(B)(16). 8. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER CEC 310.10(D). 9. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER CEC 310.10(C). ELECTRICAL CALCULATION AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION TERMINAL RATING CHECK DERATED CONDUCTOR AMPACITY CHECK 1 1.21 X 8 = 9.68 X 1.25 = 12.10A 30 X 0.96 X 1 =28.80A 12.10A <25A 12.10A <28.80A 2 1.21 X 8 = 9.68 X 1.25 = 12.10A 40 X 0.96 X 0.8 =30.72A 12.10A <35A 12.10A <30.72A 1A 1.21 X 10 = 12.10 X 1.25 = 15.13A 30 X 0.96 X 1 =28.80A 15.13A <25A 15.13A <28.80A 2A 1.21 X 10 = 12.10 X 1.25 = 15.13A 40 X 0.96 X 1 =38.40A 15.13A <35A 15.13A <38.40A 3 1.21 X 26 = 31.46 X 1.25 = 39.33A 55 X 0.96 X 1 =52.80A 39.33A <50A 39.33A <52.80A Certificate Of Completion Envelope Id: 8E8E8263F6CD4DC78D1F8B88EE88CDB7 Status: Completed Subject: Please DocuSign: SunGrid Solar Plan Set Approval Source Envelope: Document Pages: 18 Signatures: 1 Envelope Originator: Certificate Pages: 2 Initials: 0 SunGrid Solar AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 17280 newhope st unit 18 Fountain Valley, CA 92708 ops@gosungrid.com IP Address: 98.186.153.107 Record Tracking Status: Original 1/27/2022 10:54:13 AM Holder: SunGrid Solar ops@gosungrid.com Location: DocuSign Signer Events Signature Timestamp QUAN HY quanchihy@yahoo.com Security Level: Email, Account Authentication (None) Signature Adoption: Drawn on Device Using IP Address: 76.175.219.199 Signed using mobile Sent: 1/27/2022 10:56:05 AM Viewed: 1/28/2022 6:08:17 PM Signed: 1/28/2022 6:50:46 PM Electronic Record and Signature Disclosure: Not Offered via DocuSign In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp Felicia Gonzalez felicia@gosungrid.com Security Level: Email, Account Authentication (None) Sent: 1/27/2022 10:56:05 AM Electronic Record and Signature Disclosure: Not Offered via DocuSign Andrew Higgins Andrew@gosungrid.com CEO BLC Builder Constructio Security Level: Email, Account Authentication (None) Sent: 1/27/2022 10:56:04 AM Electronic Record and Signature Disclosure: Not Offered via DocuSign 2402 S Manitoba Drive04/19/22 Carbon Copy Events Status Timestamp SunGrid Solar ops@gosungrid.com CEO BLC Builder Construction Inc (DBA SunGrid Solar) Security Level: Email, Account Authentication (None) Sent: 1/27/2022 10:56:05 AM Resent: 1/28/2022 6:50:51 PM Electronic Record and Signature Disclosure: Not Offered via DocuSign Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 1/27/2022 10:56:05 AM Certified Delivered Security Checked 1/28/2022 6:08:17 PM Signing Complete Security Checked 1/28/2022 6:50:46 PM Completed Security Checked 1/28/2022 6:50:46 PM Payment Events Status Timestamps 2402 S Manitoba Drive04/19/22 Expedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 2402 S Manitoba Drive04/19/22 Expedited Permit Process for PV Systems — Micro-Inverter2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. x Composition Shingle x M1 Structural Adhesive x Iron Ridge Flashfoot 2.85 68 23.85 28 502.14 0.0147 ✔ ✔ ✔ 2402 S Manitoba Drive04/19/22 Expedited Permit Process for PV Systems 3Micro-Inverter Site Plan&RQWUDFWRU1DPH$GGUHVVDQG3KRQH%LOODQG7HG¶V6RODU([FHOOHQW'ULYH6DQ'LPDV&$6LWH3ODQIRU6PDOO6FDOH6LQJOH3KDVH396\VWHPV6LWH1DPH-RHDQG-DQH+RPHRZQHU6LWH$GGUHVV6XQQ\VLGH6W)RQWDQD&$6\VWHP$&6L]HN:6RODU$UUD\^/&^DEKt'EKZs^>Ed^ĂƚĞ͗^,dƌĂǁŶLJ͗ŚĞĐŬĞĚLJ͗2402 S Manitoba Drive04/19/22 Expedited Permit Process for PV Systems 4Micro-Inverter Electrical DiagramContractor Name,Address and Phone:One-Line Standard Electrical Diagramfor Micro-Inverter PV SystemsSite Name:Site Address:System AC Size:SIZEFSCM NODWG NOREVE1.1aSCALENTSDate: SHEETDrawn By:Checked By:DESCRIPTION OR CONDUCTOR TYPEUSE-2 or PV WIRE GEC EGC X ALL THAT APPLYEXTERIOR CABLE LISTED W/ INV.THWN-2 or XHHW-2 or RHW-2GEC EGC X ALL THAT APPLYNO DC GEC IF 690.35 SYSTEMTHWN-2 or XHHW-2 or RHW-2GEC EGC X ALL THAT APPLYTAG12345CONDUIT AND CONDUCTOR SCHEDULECOND.GAUGEMFGMFGNUMBER OFCONDUCTORSMFG CableMFG CableCONDUITTYPEN/AN/AN/ASAMESAMECONDUITSIZEN/AN/AN/ASAMESAMEDESCRIPTIONPV DC or AC MODULEDC/AC INVERTER (MICRO)J-BOX (IF USED)PV ARRAYAC COMB. PANEL (IF USED)GEN METER (IF USED)AC DISCONNECT (IF USED)SERVICE PANELTAG12345678PART NUMBERNOTESFOR UNUSED MODULESPUT "N/A” in BLANK ABOVE11323EQUIPMENT SCHEDULE2_____MICRO-INVERTERSIN BRANCH-CIRCUITMOD____DCACMOD____DCACMOD____DCACMOD____DCACMOD____DCACMOD____DCACJ-BOX4AC DISCOMBUILDINGGROUNDINGELECTRODEGMUTILITYSERVICEMAIN SERVICE PANELMAINOCPDINVERTEROCPD678545GSEE GUIDE APPENDIX D FORINFORMATION ON MODULE ANDARRAY GROUNDINGAC COMBINERPANELG____MICRO-INVERTERSIN BRANCH-CIRCUITQ Cell Q Peak Duo BLK G6 340WIQ7PlusEnphase Combiner 3Q Cell Q Peak Duo BLK G6 340WNEMA60 AMP Square D DisconnectEaton108xxxxxxxxx12412210482Quan Hy2402 S Manitoba Dr Santa Ana7.542/232402 S Manitoba Drive04/19/22 Expedited Permit Process for PV Systems 5Contractor Name,Address and Phone:Notes for One-Line Standard ElectricalDiagram for Single-Phase PV SystemsSite Name:Site Address:System AC Size:SIZEFSCM NODWG NOREVE1.2aSCALENTSDate: SHEETDrawn By:Checked By:MAX POWER-POINT CURRENT (IMP)MAX POWER-POINT VOLTAGE (VMP)OPEN-CIRCUIT VOLTAGE (VOC)SHORT-CIRCUIT CURRENT (ISC)MAX SERIES FUSE (OCPD)MAXIMUM POWER (PMAX)MAX VOLTAGE (TYP 600VDC)VOC TEMP COEFF (mV/oC or %/oC )IF COEFF SUPPLIED, CIRCLE UNITSMODULE MAKEMODULE MODELPV MODULE RATINGS @ STC (Guide Section 5)MAX DC VOLT RATINGMAX POWER @ 40oCNOMINAL AC VOLTAGEMAX AC CURRENTMAX OCPD RATINGINVERTER MAKEINVERTER MODELINVERTER RATINGS (Guide Section 4)1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THEREQUIREMENT? YES NO N/A2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THEREQUIREMENT? YES NO N/A3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAXCURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTEROCPD AMPERE RATING. (See Guide Section 9)5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAREXCEPTION IN 690.64(B)(2)(a)? YES NONOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEANEXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHESTMONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT ATLEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF47oC OR LESS (ALL OF UNITED STATES),a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLERFUSE.b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLERFUSE.NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E):OCPD = OVERCURRENT PROTECTION DEVICENATIONAL ELECTRICAL CODE®REFERENCESSHOWN AS (NEC XXX.XX)NOTES FOR ALL DRAWINGS:SIGNS–SEE GUIDE SECTION 7SIGN FOR DC DISCONNECTSIGN FOR INVERTER OCPD AND ACDISCONNECT (IF USED)No sign necessary since 690.51marking on PV module coversneeded informationAC OUTPUT CURRENTNOMINAL AC VOLTAGESOLAR PV SYSTEMAC POINT OF CONNECTIONTHIS PANEL FED BY MULTIPLESOURCES (UTILITY AND SOLAR)Notes for Micro-Inverter Electrical DiagramHanwhaQ Cell Q Peak Duo 340W34033.9440.6610.5220254.532.27xEnphaseIQ7Plus602082902029031.46240-4065xx1.21xQuan Hy2402 S Manitoba Dr Santa Ana8.028KW2/232402 S Manitoba Drive04/19/22 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2402 S Manitoba Dr Santa Ana CA 92704 BLC BUILDER CONSTRUCTION 1037212 x x x x x x x x x x Andrew Higgins (949)309-2453 ops@gosungrid.com 2/23/22 2402 S Manitoba Drive04/19/22 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2402 S Manitoba Dr Santa Ana CA 92704 BLC BUILDER CONSTRUCTION 1037212 x x x x x x x x x x Andrew Higgins (949)309-2453 ops@gosungrid.com 2/23/22 2402 1/2 2402 S Manitoba Drive04/19/22 SUNGRID 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. Attn.: To Whom It May Concern re job: QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. Design Criteria: Code:2019 CBC ASCE 7-16 Live Load:20 psf Ult Wind Speed:95 mph Exposure Cat:C Ground Snow:0 psf Min Roof Snow: NA AHZ Consulting Engineers Inc. Professional Engineer projects@ahzengineers.com 1/27/2022 The following calculations are for the structural engineering design of the photovoltaic panels and are valid only for the structural info referenced in the stamped plan set. The verification of such info is the responsibility of others. After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads. All mounting equipment shall be designed and installed per manufacturer's approved installation specifications. www.ahzengineers.com 2402 S Manitoba Drive04/19/22 Date :1/27/2022 Job Code: QUAN HY 2 of 6 Roof Properties: Roof Type = Roof Pitch (deg) = Mean Roof Height (ft) = Attachment Trib Width (ft) = Attachment Spacing (ft) = Framing Type = Framing Size = Framing OC Spacing (in.) = Section Thickness, b (in.) = Section Depth, d (in.) = Section Modulus, Sx (in.^3) = Moment of Inertia, Ix (in.^4) = Framing Span (ft) = Deflection Limit D+L (in.) = Deflection Limit S or W (in.) = Attachments Pattern = Framing Upgrade = Sister Size = Wood Species = Wood Fb (psi) = Wood Fv (psi) = Wood E (psi) = C D (Wind) = C D (Snow) = CLS = C M = Ct = CL = Ci = CF = Cfu = Cr = F'b_wind (psi) = F'b_snow (psi) = F'v_wind (psi) = F'v_snow (psi) = M_allowable_wind (lb-ft) = M_allowable_snow (lb-ft) = V_allowable_wind (lbs) = V_allowable_snow (lbs) = 1139 1121 1584 207 1560 1779 288 1.15 2476 1.3 1.00 1.15 1.0 1.6 1.15 180 1600000 DF #2 900 Adequate NA 2.67 Fully Staggered 20 4 7.6 20.8 1.5 5.5 2x6 16 5.33 Rafter 23 2.75 Shingle 30 Roof 1 www.ahzengineers.com 2402 S Manitoba Drive04/19/22 Date :1/27/2022 Job Code: QUAN HY 3 of 6 E' (psi) = Load Calculation: Panels Dead Load (psf) = Roofing Weight (psf) = Decking Weight (psf) = Framing Weight (psf) = Misc. Additional Weight (psf) = Existing Dead Load (psf) = Total Dead Load (psf) = Ultimate Wind Speed (mph) = Directionality Factor, kd = Topographic Factor, kzt = Velocity Press Exp Factor, kz = Ground Elevation Factor, ke = Velocity Pressure, qz (psf) = Array Edge Factor, γE = Solar Equalization Factor, γa = External Pressure Up, GCp_1 = External Pressure Up, GCp_2 = External Pressure Up, GCp_3 = External Pressure Down, GCp = Design Pressure Up, p_1 (psf) = Design Pressure Up, p_2 (psf) = Design Pressure Up, p_3 (psf) = Design Pressure Down, p (psf) = Hardware Checks: Ref. Widthrawal Value, W (lb/in) = (C M = Ct = Ceg = 1.0) C D = Adjusted Widthrawal Value, W' (lb/in) = Lag Penetration, p (in.) = 426 2.5 266 1.6 Lag Screw Checks: Roof 1 16.0 -26.5 -32.3 0.8 -22.0 -1.8 -2.2 1.25 0.64 -1.5 0.93 1.00 18.2 95 0.85 1.0 Roof 1 Wind Load Calculations: 7.4 10.4 1.4 1.0 3.0 2.0 Dead Load Calculations: 3.0 Roof 1 1600000 www.ahzengineers.com 2402 S Manitoba Drive04/19/22 Date :1/27/2022 Job Code: QUAN HY 4 of 6 Allowable Widthrawal Force, W'p (lbs) = Applied Uplift Force (lbs) = Uplift DCR = Ref. Lateral Value, Z (lbs) = (C M = Ct = CΔ = Ceg = 1.0) C D = Adjusted Lateral Value, Z' (lbs) = Applied Laeral Force (lbs) = Angle of Resultant Force, α (deg) = Adjusted Interaction Lateral Value, Z' α (lbs) = Lateral DCR = Roof Framing Checks: LC1: D+S Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC2: D+0.6W Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC3: D+0.75(S+0.6W) Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC4: 0.6D+0.6W Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = 1560 1584 465 93 0.75 0.15 1560 1584 1175 235 0.86 0.17 1560 1584 1335 267 0.62 0.12 1121 1139 139 Force Checks: Roof 1 695 1038 0.02 22 85 0.9 243 0.24 270 1064 -256 www.ahzengineers.com 2402 S Manitoba Drive04/19/22 Date :1/27/2022 Job Code: QUAN HY 5 of 6 Moment DCR = Shear DCR = LC1: D+L Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC2: S Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC3: W (Down) Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC4: W (Up) Deflection (in.) = Deflection Limit (in.) = Deflection DCR = Seismic Check: Wall Weight (psf) = Tributary Wall Area (ft2) = Total Wall Weight (lbs) = Roof Weight (psf) = Roof Area (ft2) = Total Roof Weight (lbs) = Total Existing Weight (lbs) = PV Panel Weight (lbs) = Number of Panels = Total Additional PV Weight (lbs) = (Existing W + Additional W)/(Existing W)-1 = 0% Additional PV Weight: 54 0 0 Weight Increase: 3000 51000 7 2400 17803 68803 0.44 Existing Weight: 17 -1.34 3.07 3.07 0.32 0.00 0.97 0.00 3.07 4.6 0.49 Deflection Checks (Service Level): Roof 1 2.25 0.30 0.06 www.ahzengineers.com 2402 S Manitoba Drive04/19/22 Date :1/27/2022 Job Code: QUAN HY 6 of 6 The increase in weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. Limits of Scope of Work and Liability: Existing structure is assumed to have been designed and constructed following appropriate codes at time of erection, and assumed to have appropriate permits. The calculations produced are only for the roof framing supporting the proposed PV installation referenced in the stamped planset and were completed according to generally recognized structural analysis standards and procedures, professional engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or were not observable during time of inspection are not included in this scope of work. All PV modules, racking, and mounting equipment shall be designed and installed per manufacturer's approved installation specifications. The Engineer of Record and the engineering consulting firm assume no responsibility for misuse or improper installation. This analysis is not stamped for water leakage. Framing was determined based on information in provided plans and/or photos, along with engineering judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any concerns prior to starting construction. www.ahzengineers.com 2402 S Manitoba Drive04/19/22 AC MSPCB SITE PLAN-1 PV-1.0 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC SITE PLAN-1 PV-1.0 A SITE PLAN-1 SCALE: 3/32" = 1'-0" ELECTRIC CODE CEC 2019 FIRE CODE CFC 2019 RESIDENTIAL CODE CRC 2019 BUILDING CODE CBC 2019 WIND SPEED 95 MPH SNOW LOAD 0 PSF GENERAL INFORMATION 3' FIRE SETBACK PV-1.0 A1 VICINITY MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 1'-6" FIRE SETBACK (N) AC DISCONNECT(EXTERIOR) PHOTOVOLTAIC ARRAY ON THE ROOF (E) MAIN SERVICE PANEL(EXTERIOR) (N) ENPHASE IQ COMBINER 3 (EXTERIOR) CONDUIT RUN 15' AC TRENCHED CONDUIT RUN INDEX INDEX NO. DESCRIPTION SITE PLAN-1&2 MICRO SERIAL MAP GENERAL NOTES MOUNTING DETAILS STRUCTURAL DETAILS SINGLE LINE DIAGRAM ELECTRICAL CALCULATION WARNING PLACARDS MODULE SPEC SHEET INVERTER SPEC SHEET COMBINER SPEC SHEET RACKING SPEC SHEET MOUNT SPEC SHEET GROUNDING SPEC SHEET INTEGRATED GROUNDING SPEC SHEET FIRE RATING SPEC SHEET PV-1.0&1.1 PV-1.2 PV-2.0 S-1.0 S-1.1 E-1.0 E-1.1 PV-3.0 PD-1.0 PD-1.1 PD-1.2 PD-1.3 PD-1.4 PD-1.5 PD-1.6 PD-1.7 2402 S Manitoba Dr BLDG # 101109909 ELEC # 20175792 ISSUED 03/31/22 2402 1/2 S Manitoba Dr BLDG #101109910 ELEC #20175794 ISSUED 04/06/22 2402 S Manitoba Drive04/19/22 PD-1.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MODULE SPECSHEET 2402 S Manitoba Drive04/19/22 PD-1.1 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 INVERTER SPECSHEET 2402 S Manitoba Drive04/19/22 PD-1.2 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 COMBINER SPECSHEET 2402 S Manitoba Drive04/19/22 PD-1.3 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 RACKING SPECSHEET 2402 S Manitoba Drive04/19/22 PD-1.4 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MOUNT SPECSHEET 2402 S Manitoba Drive04/19/22 PD-1.5 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 GROUNDING SPECSHEET 2402 S Manitoba Drive04/19/22 PD-1.6 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 INTEGRATED GROUNDING SPECSHEET 2402 S Manitoba Drive04/19/22 PD-1.7 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 FIRE RATING SPECSHEET 2402 S Manitoba Drive04/19/22 AC MSPCB SITE PLAN-2 PV-1.1 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC SITE PLAN-2 PV-1.1 A SITE PLAN-2 SCALE: 1/16" = 1'-0" PHOTOVOLTAIC ARRAY ON THE ROOF CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 PROPERTY LINE DRIVE WAY S MANITOBA DRGATE-1 GATE-2 151'-5"61'133'-9" 28'-5"12'-2"2'-11" 27'-11" 7'-10" TREE 2402 S Manitoba Drive04/19/22 MICRO SERIAL MAP PV-1.2 QUAN HY - 8.840kW DC, 7.540kW AC, 8.028kW CEC AC MICRO SERIAL MAP PV-1.2 A MICRO SERIAL MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 2402 S Manitoba Drive04/19/22 GENERAL NOTES PV-2.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 GENERAL NOTES 1. MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS. 2. INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS. 3. DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL SITE CONDITION MIGHT VARY. 4. WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH CEC CODES. 5. ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/ SERVICE EQUIPMENT. 6. ALL CONDUCTORS SHALL BE 600V, 75°C STANDARD COPPER UNLESS OTHERWISE NOTED. 7. WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 8. THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND/OR THE UTILITY. 9. ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREES, WIRES OR SIGNS. 10. PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING EQUIPMENT LOCATION: 11. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY CEC CODES. 12. WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY CEC CODES AND CEC TABLES. 13. JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO CEC CODES. 14. ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 15. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO CEC CODES APPLICABLE CODES. 16. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE . STRUCTURAL NOTES: 17. RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 18. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 19. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. 20. ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 21. WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. WIRING & CONDUIT NOTES: 22. ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. 23. CONDUCTORS SIZED ACCORDING TO CEC CODES . 24. DC WIRING LIMITED TO MODULE FOOTPRINT. MICRO INVERTER WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITH SUITABLE WIRING CLIPS. 25. AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [CEC CODES]. INTERCONNECTION NOTES: 26. LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [CEC CODES]. 27. THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120% OF BUSBAR RATING [CEC CODES]. 28. WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PV DEDICATED BACKFFED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [CEC CODES]. 29. AT MULTIPLE PV OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVER CURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVER CURRENT DEVICE MAY BE EXCLUDED ACCORDING TO CEC CODES . 30. FEEDER TAP INTER CONNECTION (LOAD SIDE) ACCORDING TO CEC CODES. 31. SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO CEC CODES WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH CEC CODES . 32. BACK FEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [CEC CODES]. GROUNDING NOTES: 33. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 34. PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO CEC CODES AND MINIMUM CEC TABLE. 35. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORD. 36. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO CEC CODES AND MICRO INVERTER MANUFACTURER'S INSTRUCTIONS. 37. EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 38. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. 39. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [CEC CODES]. 40. THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC CODES AND NEC THROUGH . IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO CEC CODES AND AHJ. 41. GROUND-FAULT DETECTION SHALL COMPLY WITH CEC CODES IN GENERAL AND CEC CODES SPECIFICALLY. 42. DISCONNECTION AND OVER-CURRENT PROTECTION NOTES. 43. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). 44. DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 45. RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 10 FT OF PV ARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLED CONDUCTORS ≤30V AND ≤240VA [CEC CODES]. LOCATION OF LABEL ACCORDING TO AHJ. 46. ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC CODES. 47. MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH CEC CODES. IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO CEC CODES. GENERAL NOTES 2402 S Manitoba Drive04/19/22 MOUNTING DETAILS S-1.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 PV-3.0 B MOUNTING DETAILS SCALE: 3/32" = 1'-0" SITE INFORMATION SR.NO AZIMUTH PITCH NO. OF MODULES ARRAY AREA (SQ. FT.)ROOF TYPE ATTACHMENT ROOF EXPOSURE FRAME TYPE FRAME SIZE FRAME SPACING MAX RAIL SPAN OVER HANG MP-01 180° 30° 8 154.5 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-02 270° 30° 8 154.5 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-03 90° 30° 5 96.6 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-04 180° 30° 3 57.9 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" MP-05 270° 30° 2 38.6 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 6 1'-4"5'-4" 2'-0" DEAD LOAD CALCULATIONS BOM QUANTITY LBS/UNIT TOTAL WEIGHT (LBS) MODULES 26 43.9 1141.40 MID-CLAMP 30 0.050 1.50 END-CLAMP 44 0.050 2.20 RAIL LENGTH 191 0.680 129.88 SPLICE BAR 2 0.360 0.72 FLASH FOOT 68 1.35 91.80 MICRO-INVERTER 26 2.38 61.88 TOTAL WEIGHT OF THE SYSTEM (LBS)1429.38 TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)502.14 WEIGHT PER SQ. FT.(LBS)2.85 WEIGHT PER PENETRATION (LBS)21.02 UPLIFT CALCULATIONS UPLIFT 15064.3 LBS PULL OUT STRENGTH 41820 LBS POINT LOADING 17 LBS MODULES DATA HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULE DIMS 68.5"x40.6"x1.26" LAG SCREWS 5/16"x3.5":2.5"MIN EMBEDMENT ALUMINIUM RAILS MINIMUM FIRE ACCESS PATHWAYS PER CEC 2019 RIDGE TO ARRAY: 3'-0" EAVE TO ARRAY : 3'-0" HIP/VALLEY W/ ADJACENT ARRAY: 1'-6" EACH SIDE HIP/VALLEY W/O ADJACENT ARRAY: 0'-0" NOTE: INSTALLER TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY ANY DISCREPANCIES BEFORE PROCEEDING. FIRE SETBACK 2 X 6 RAFTERS @ 1'-4"SPACING ARRAY MP-01 ARRAY MP-02 ARRAY MP-03 ARRAY MP-04 ARRAY MP-05 3'1'-6"5'-4" 2402 S Manitoba Drive04/19/22 STRUCTURAL DETAILS S-1.1 CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MID-CLAMP & END CLAMP DETAIL GROUNDING DETAILS MID CLAMP ASSEMBLY MODULE FRAME RAIL GROUNDING MID-CLAMP SCALE: NTS MODULE TO MODULE & MODULE TO RAIL GROUNDING RAIL TO RAIL IRON RIDGE RAIL INTERNAL SPLICE SELF-DRILLING SCREW SCALE: NTS T BOLT SCALE: NTS PV MODULE IRONRIDGE RAIL IRONRIDGE STOPPER SLEEVE END CLAMP PV MODULE IRONRIDGE RAIL MID CLAMP SCALE: NTS FLASHFOOT SOLAR MODULE RAIL 6" MAX 2 X 6 RAFTERS@1'-4" SPACING LOAD BEARING WALL ROOF FRAMING DETAIL SCALE: NTS SCALE: NTS ATTACHMENT DETAIL - FLASHFOOT 5/16 HEX-BOLT STAINLESS STEEL 5/16" HANGER BOLT 2.5" EMBEDMENT PILOT HOLE REQUIRED (E)COMPOSITION SHINGLE ROOF IRONRIDGE FLASHFOOT IRONRIDGE XR10 RAIL PV MODULE (E) BUILDING STRUCTURE 2402 S Manitoba Drive04/19/22 3 (E)200A MAIN BREAKER M PV BREAKER AT THE OPPOSITE END OF BUSBAR 40A 2P PV BREAKER EXISTING 120/240V 1PH 60HZUTILITYGRID (E)GROUND ELECTRODE (E)200A END FED MAIN PANEL UTILITY:SCE 222012-778830 (N)JUNCTION BOX OR EQUIV (N)(16)ENPHASE IQ7PLUS-72-2-US (240V,1PH) WITH (16)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULES 1 (1) BRANCH OF (8) MICRO-INVERTERS(8 MODULES) (1) BRANCH OF (8) MICRO-INVERTERS(8 MODULES) (N)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W, 340W MODULES 20A AC COMBINER WITH ENPHASE ENVOY-S EN-X-IQ-AM1-240-3 120/240 NEMA 3R INSTALL (3)20A PV 2P BREAKERS(ONLY FOR SOLAR NO LOAD TO BE ADDED) (N)ENPHASE IQ COMBINER 3 15A 2 3 20A (N)60A AC DISCONNECT SQUARE D DU222RB AC DISCONNECT NON FUSED 60A, 120/240V, 2P (N)JUNCTION BOX OR EQUIV (N)(10)ENPHASE IQ7PLUS-72-2-US (240V,1PH) WITH (10)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULES 1A (1) BRANCH OF (10) MICRO-INVERTERS(10 MODULES) (N)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W, 340W MODULES 2A 20A SINGLE LINE DIAGRAM E-1.0 SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 8840W, AC SYSTEM SIZE - 7540W,CEC AC SYSTEM SIZE - 8028W CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 NOTE: 1. MICROINVERTERS ARE UL 1741 RATED 2. EACH MICROINVERTER IS RAPID SHUTDOWN COMPLAINT CONDUIT SCHEDULE TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND 1 NONE (4) 12 ENPHASE Q CABLE PER BRANCH CIRCUIT NONE (1) 6 AWG BARE COPPER 2 3/4"EMT OR EQUIV (4) 10 AWG THHN/THWN-2 NONE (1) 10 AWG THHN/THWN-2 1A NONE (2) 12 ENPHASE Q CABLE PER BRANCH CIRCUIT NONE (1) 6 AWG BARE COPPER 2A 3/4" SCH 40 PVC (BELOW GROUND) 3/4" SCH 80 PVC (ABOVE GROUND) (2) 10 AWG THHN/THWN-2 NONE (1) 10 AWG THHN/THWN-2 3 3/4"EMT OR EQUIV (2) 8 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2 OCPD CALCULATIONS: MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A 120% RULE: (200AX1.2)-200A=40A =>ALLOWABLE BACKFEED IS 40A INVERTER OVERCURRENT PROTECTION= INVERTER O/P I X CONTINUOUS LOAD(1.25)X #OF INVERTERS =1.21x1.25x26=39.33 A =>PV BREAKER = 40A ALLOWABLE BACKFEED 40A =>40A PV BREAKER THE DESIGNED INTERCONNECTION MEETS THE 705.12(B)(2) REQUIREMENTS 2402 S Manitoba Drive04/19/22 ELECTRICAL CALCULATION E-1.1 ELECTRICAL CALCULATION CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 MODULE SPECIFICATION MODEL HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W MODULE POWER @ STC 340W OPEN CIRCUIT VOLTAGE:Voc 40.66V MAX POWER VOLTAGE:Vmp 33.94V SHORT CIRCUIT VOLTAGE:Isc 10.52A MAX POWER CURRENT:Imp 10.02A MICRO INVERTER SPECIFICATIONS MODEL ENPHASE IQ7PLUS-72-2-US (240V,1PH) POWER RATING 290W MAX OUTPUT CURRENT 1.21A CEC WEIGHTED EFFICIENCY 97% MAX NO OF MICRO INVERTERS/BRANCH 13 MAX DC VOLTAGE 60V ELECTRICAL NOTES: 1. MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%. 2. BREAKER/FUSE SIZES CONFORMS TO CEC 240.6 CODE SECTION. 3. AC GROUNDING ELECTRODE CONDUCTOR SIZED PER CEC 250.66. 4. AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON CEC 690.31(A). 5. AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON CEC 310.15(B)(2). 6. MAX. SYSTEM VOLTAGE CORRECTION IS PER CEC 690.7. 7. CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE CEC 310.15(B)(16). 8. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER CEC 310.10(D). 9. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER CEC 310.10(C). ELECTRICAL CALCULATION AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION TERMINAL RATING CHECK DERATED CONDUCTOR AMPACITY CHECK 1 1.21 X 8 = 9.68 X 1.25 = 12.10A 30 X 0.96 X 1 =28.80A 12.10A <25A 12.10A <28.80A 2 1.21 X 8 = 9.68 X 1.25 = 12.10A 40 X 0.96 X 0.8 =30.72A 12.10A <35A 12.10A <30.72A 1A 1.21 X 10 = 12.10 X 1.25 = 15.13A 30 X 0.96 X 1 =28.80A 15.13A <25A 15.13A <28.80A 2A 1.21 X 10 = 12.10 X 1.25 = 15.13A 40 X 0.96 X 1 =38.40A 15.13A <35A 15.13A <38.40A 3 1.21 X 26 = 31.46 X 1.25 = 39.33A 55 X 0.96 X 1 =52.80A 39.33A <50A 39.33A <52.80A 2402 S Manitoba Drive04/19/22 AC MSPCB PV-3.0 POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN WARNING ! CUSTOMER INFORMATION NAME&ADDRESS: 33°42'52.12"N 117°54'10.30"W APN:412-311-09 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: PA/VR PROJECT NUMBER:GOSG-004333 SCALE:AS NOTED PAPER SIZE:17"x11" QUAN HY 2402 S MANITOBA DR, SANTA ANA, CA 92704. ENGINEER OF RECORD DC SYSTEM SIZE : 8840W AC SYSTEM SIZE : 7540W CEC AC SYSTEM SIZE : 8028W MODULES: (26)HANWHA Q CELLS Q.PEAK DUO BLK-G6+ 340W INVERTER: (26)ENPHASE IQ7PLUS-72-2-US (240V,1PH) BRANCH DETAILS: (1)BRANCH OF 10 MICRO INVERTERS(10 MODULES) (2)BRANCH OF 8 MICRO INVERTERS(8 MODULES) DATE:01/27/2022 REV:A 17280 NEWHOPE ST,UNIT 18, FOUNTAIN VALLEY,CA 92708. TEL.NO: 949-309-2453 LIC: #B/C10 - 1037212 ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE RED WITH WHITE LETTERING U.O.N. PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.FASTENERS APPROVED BY THE LOCAL JURISDICTION 2402 S MANITOBA DR, SANTA ANA, CA 92704. WARNING PLACARDS WARNING PLACARDS NOTE:ALL SIGNAGE CANNOT BE HAND WRITTEN CEC 110.21 PHOTOVOLTAIC ARRAY ON THE ROOF WARNING CAUTION: SOLAR CIRCUIT LABEL LOCATION POINT OF INTERCONNECTION (PER CODE: CEC 705.12(2)(b) [ Not Required if Panel board is rated not less than sum of ampere ratings of all overcurrent devices supplying it] WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVER-CURRENT DEVICE WARNING:PHOTOVOLTAIC POWER SOURCE LABEL LOCATION CONDUIT, COMBINER BOX [PER CODE: CEC690.31(G)(3)] WARNING-Electric Shock Hazard No User Serviceable Parts inside Contact authorized service provide for assistance LABEL LOCATION INVERTER, JUNCTION BOXES(ROOF), AC DISCONNECT [PER CODE: CEC 690.13] LABEL LOCATION DISCONNECT, POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] LABEL LOCATION AC DISCONNECT , POINT OF INTERCONNECTION [PER CODE: CEC 690.54] LABEL LOCATION MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT LEAST EVERY 10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL COMBINER/JUNCTION BOXES. (PER CODE: CFC605.11.1.4) LABEL LOCATION POINT OF INTERCONNECTION [PER CODE: CEC705.12(D)(4)] ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] LABEL LOCATION WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE, UL969 AS STANDARD TO WEATHER RATING (UL LISTING OF MARKINGS NOT REQUIRED), MIN 3 8" LETTER HEIGHT ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN THE MAIN SERVICE DISCONNECT,PLACED ON THE OUTSIDE OF THE COVER WHEN DISCONNECT IS OPERATED WITH THE SERVICE PANEL CLOSED. (PWER CODE: CEC690.15 ,690.13(B)) WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM SOLAR DISCONNECT RATED AC OPERATING CURRENT AC NOMINAL OPERATING VOLTAGE 31.46 240 AMPS AC VAC PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN LABEL LOCATION AC DISCONNECT, DC DISCONNECT, POINT OF INTERCONNECTION (PER CODE: CEC690.56(C)(1)(A)) LABEL LOCATION INVERTER,POINT OF INTERCONNECTION [PER CODE: CEC 690.56(C)(3)] RAPID SHUTDOWN SWITCH FOR SOLAR SYSTEM SYSTEM UTILIZES MICRO-INVERTERS LOCATED UNDER SOLAR MODULE (E) MAIN SERVICE PANEL(EXTERIOR) (N) AC DISCONNECT(EXTERIOR) (N) ENPHASE IQ COMBINER 3 (EXTERIOR) 2402 S Manitoba Drive04/19/22