COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N) NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
SURGE PROTECTOR TO BE INSTALLED PER MANUFACTURER
AND PANEL BOARD SPECS.
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-3.0 LAYOUT
PV-3.1 MOUNTING DETAIL
PV-3.2 MOUNTING DETAIL
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL CALCS
PV-4.2 PANEL SCHEDULE
PV-5.0 SIGNAGE
PV-5.1 SIGNAGE
LTD: LR5-54HABB-400M
WITH STANDOFF TO FRAMING: SNR-DC-01249 [FLAT, FLUSH
MOUNT ( ROLLED COMP/ MEMBRANE/ FOAM) 1 LAG
OMNIBASE]; ULTRA RAIL, ATTACHMENT DETAIL, UMBRELLA L
FOOT TO FRAMING, SNR-DC-00339
1707000-XX-Y, (1) EXPANSION 1807000-XX-Y
(MCI) ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE
PANEL WITH 50 AMP MAIN BREAKER TO BE REPLACED WITH
NEW 125 AMP MAIN PANEL WITH 125 AMP MAIN BREAKER
AND 225 AMP BUSBAR.
MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A).
MODULES, ARE CLASS A FIRE RATED.
CONDUCTORS OUTSIDE OF THE ARRAY ARE LIMITED TO LESS THAN 30V IN 30
SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE THE
ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
D
WARNING: POWER SOURCE OUTPUT CONNECTION -- DO NOT
RELOCATE THIS OVERCURRENT DEVICE.
Revision to 20184540 (issued on 2/4/25)
Rev 1 #20185409
APPROVALS:
ELECT - M. Smith
5313 W Henderson
Pl3/27/2025
PAGE
REV: C2 3/11/2025
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
GILBERT CORREIA, C10, C46
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184PLPLPLPLPLPLPLPLPLPL
SITE PLAN
PV-2.0
#SSTAMPSP
#ESTAMPSP
NOTES:
RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
TOTAL ROOF SURFACE AREA: 2538 SQFT.
TOTAL PV ARRAY AREA: 441.4 SQ FT.
PERCENTAGE PV COVERAGE:
(TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
AREA) * 100 = 17.4%
ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN
ACCORDANCE WITH R328.4. ESS UNITS SHALL BE SEPARATED FROM
EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT WHERE SMALLER
SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE
BASED ON LARGE/SCALE FIRE TESTING.
POWERWALL ENERGY
STORAGE SYSTEM (ESS)
BG BACKUP GATEWAY
GP GENERATION PANEL
ELECTRIC VEHICLE
SUPPLY EQUPMENTEV
MAIN PANEL
INVERTER(S)
AC DISCONNECT(S)
DC DISCONNECT(S)
SUNRUN METER
DEDICATED PV METER
SERVICE ENTRANCE
INTERIOR EQUIPMENT
SHOWN AS DASHED
SE
MP
SM
PM
INV
AC
DC
SUB-PANELSP
CB IQ COMBINER BOX
METER ADAPTERMA
GROUNDING
ELECTRODE
ENERGY STORAGE
SYSTEM
BP BACKUP LOADS PANEL
BI BACKUP INTERFACE 1 COMMUNICATION
WIRESAM
MD MICROGRID
INTERCONNECT DEVICE
ACREL METER
SOLAREDGE METERSEMPV LOAD CENTERLC
LEGEND
SCALE: NTS
NOTE: NOT ALL ITEMS IN LEGEND
WILL APPEAR IN SITE PLAN
RAIL
STANDOFFS &
FOOTINGS
SOLAR
MODULES
SITE PLAN - SCALE = 0'-0 3/64" = 1'-0"
(E) RESIDENCE
(N) ARRAY AR-01
(N) ARRAY AR-02
FIRE SETBACKS
(18" TYP)
ROOF PATHWAYS
(3' TYP)
SE
MP
INV
W HENDERSON PL
MD
ROOF PATHWAYS
(3' TYP)
AC
(E) FENCE
(E) GATE (TYP.)
EXTERNAL RAPID
SHUTDOWN SWITCH
RSD
A A A A A A A A
B B B B B B B
C C C C C C
(E) DETACHED
STRUCTURE
(E) PATIO
ARRAY
PITCH
PV AREA
(SQFT)
AR-01 6° 126.1
AR-02 18° 315.3179°
TRUE
AZIM
MAG
AZIM
167°179°
167°
NOTE: ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE
INSTALLED MODULE PER NEC 690.12
RSD D
I V I LREGISTERED PR O F ESSIONAL E
N
G
I
NEERS
T
ATE OF C A L IFORNIAROBER T SMYT
H
EC56136
EXP. 12/31/26
5313 W Henderson
Pl3/27/2025
PAGE
REV: C2 3/11/2025
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
GILBERT CORREIA, C10, C46
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
NEW125A
MAIN BREAKER
END FED
NEW 125A
MAIN PANEL
225A BUS
J-BOX
LONGI GREEN
ENERGY TECHNOLOGY CO LTD
LR5-54HABB-400M
STRING 1 OF 7 MODULES
3 MODULE LEVEL
RAPID SHUTDOWN DEVICES
LONGI GREEN
ENERGY TECHNOLOGY CO LTD
LR5-54HABB-400M
STRING 2 OF 8 MODULES
3 MODULE LEVEL
RAPID SHUTDOWN DEVICES
1
1
2
POINT OF INTERCONNECTION:705.12(B)(3)(2),
METER NUMBER: 222013-570957
REPLACE EXISTING 50 MAIN
PANEL WITH NEW 125A MAIN PANEL 125A MAIN BREAKER
AND 225A BUS BAR
EQUIPMENT CHARACTERISTICS
INCLUDED IN SPEC SHEETS
NOTE: TOTAL PV BACKFEED
= 60A USED FOR INTERCONNECTION CALCULATIONS
TESLA
POWERWALL 3 1707000-XX-Y
TESLA: POWERWALL
3 1707000-XX-Y
11500 WATT
INVERTER
LOAD RATED DC
DISCONNECT WITH
AFCI RAPID
SHUTDOWN
COMPLIANT
3
FACILITY
GROUND
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A , 2P
120/240VAC
3
1
LONGI GREEN
ENERGY TECHNOLOGY CO LTD:
LR5-54HABB-400M
STRING 1 OF 6 MODULES
2 MODULE LEVEL
RAPID SHUTDOWN DEVICES
(N) IMO PE69-3020,
DISCONNECT
SWITCH, 3P, 16A
UL 9540
FACTORY
WIRING
ASSEMBLY
(1 ) TESLA
POWERWALL 3
EXPANSION PACK
1807000-XX-Y
60A
M
TESLA
BACKUP
SWITCH
CONDUIT SCHEDULE
TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT
1 Inverter Input (2) 10 AWG (PV WIRE)N/A 6 AWG (BARE)Open Air
2 Inverter Input (6) 10 AWG
THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4" EMT
3 Inverter Output (2) 6 AWG
THHN/THWN-2
(1) 6 AWG
THHN/THWN-2 8 AWG THHN/THWN-2 3/4" EMT
PV-4.0
ELECTRICAL
#ESTAMP
MODULE CHARACTERISTICS
LONGI GREEN ENERGY
TECHNOLOGY CO LTD:
LR5-54HABB-400M
400 W
OPEN CIRCUIT VOLTAGE 37.05 V
MAX POWER VOLTAGE 30.94 V
SHORT CIRCUIT CURRENT 13.72 A
GENERAL NOTES:
GROUND - UFER, TWO GROUNDS RODS OR
COLD WATER GAS BOND
IF THE RELOCATED LOADS EXTEND MORE
THAN 6 FEET, AFCI PROTECTION APPLIES
PER 2019 CEC 210.12
ANY MULTIWIRE BRANCH CIRCUITS
RELOCATED ARE TO BE IDENTIFIED,
GROUPED, AND EQUIPPED WITH A
2-POLE OCPD BREAKER PER CEC
210.4(B,D).
D
D
5313 W Henderson
Pl3/27/2025
BACKUP LOADS
LOAD BREAKER RATING
(AMPS)LABEL DEMAND
LOAD
1 20A-1P KITCHEN 1500 VA
2 20A-1P KITCHEN 1500 VA
3 20A-2P OTHER 3840 VA
5 15A-1P ROOMS 1500 VA
6 15A-1P ROOMS 1500 VA
7 30A-2P DRYER 5760 VA
PV-4.1
ELECTRICAL CALCS
ELECTRICAL CALCS
SYSTEM INFORMATION
8.4 KW DC PHOTOVOLTAIC SYSTEM
(21) LONGI GREEN ENERGY TECHNOLOGY CO LTD: LR5-54HABB-400M, TESLA: POWERWALL 3 1707000-XX-Y
ALLOWABLE BACKFEED
ALLOWABLE BACKFEED = (MAIN PANEL RATING) X 1.2 - (MAIN BREAKER RATING) =
225A X 1.2 - 125A = 145A
60A ≤ 145A → INTERCONNECTION MEETS 705.12(B)(3)(2) REQUIREMENTS.
INVERTER OVERCURRENT PROTECTION
(INVERTER MAX CURRENT) X (CONTINUOUS LOAD) =
48 A X 1.25 = 60 A → 60 A OVERCURRENT PROTECTION PER MANUFACTURER
DC WIRE SIZING
MAX CIRCUIT CURRENT = (MODULE ISC) X (HIGH IRRADIANCE)[690.8(A)(1)] X (CONTINUOUS LOAD)[690.8(B)(1)]=
13.72 A X 1.25 X 1.25= 21.44A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 0.8 X 40A = 29.12A
TERMINAL RATING[110.14(C)] =
10 AWG, 75°C RATED = 35A
29.12A < 35A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
21.44A < 29.12A 10 AWG AMPACITY OK
THEREFORE 10 AWG IS SUFFICIENT.
AC WIRE SIZING
MAX AC OUTPUT CURRENT = (MAX INVERTER OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] =
48 A X 1.25 = 60 A
ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X
(CONDUCTOR AMPACITY)[TABLE 310.16] =
0.91 X 1 X 75A = 68.25A
TERMINAL RATING[110.14(C)] =
6 AWG,75°C RATED = 65A
65A < 68.25A TERMINAL RATING GOVERNS CONDUCTOR SIZING.
60A < 65A 6 AWG AMPACITY OK
THEREFORE 6 AWG IS SUFFICIENT
SYSTEM CHARACTERISTICS
MAX OPEN CIRCUIT VOLTAGE = {[((TEMP COEF VOC) X (VOC)) / 100] X [LOW TEMP - STC TEMP] + VOC} X
(# MODULES / STRING) =
{[(-0.26 %/°C X 37.05 V) / 100] X [-2 °C - 25 °C] + 37.05 V} X 8 = 317 V
SHORT CIRCUIT CURRENT = 1.25 X (MODULE ISC) X (# STRINGS)
1.25 X 13.72 A X 3 = 51.45A
PAGE
REV: C2 3/11/2025
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
D
5313 W Henderson
Pl3/27/2025
LIGHTS /RECEPTABLES
ROOMS
LIGHTS /RECEPTABLES
PANEL SCHEDULE
PANEL SCHEDULE
PV-4.2
KITCHEN
PAGE
REV: C2 3/11/2025
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
GILBERT CORREIA, C10, C46
CA CL #750184
(415) 580-6920 ex3
MAIN BREAKER
125
NEW 225/125A
MAIN PANEL
60PV + ESS
BREAKER3015152020DRYER20OTHER
D
5313 W Henderson
Pl3/27/2025
PAGE
REV: C2 3/11/2025
MARIA VALADEZ
5313 W HENDERSON PL, SANTA
ANA, CA, 92704
PROJECT NUMBER:
109R-313VALA
SHEET
DESIGNER:
CHIPPY PRINCE
CUSTOMER RESIDENCE:
TEL. (714) 493-3532
APN: 108-392-16
(415) 580-6920 ex3
Template_version_v5_2024 02 28
GILBERT CORREIA, C10, C46
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
SIGNAGE
PV-5.0
#ESTAMP
ENERGY STORAGE SYSTEM
DISCONNECT
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
POWER SOURCE OUTPUT CONNECTION
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
CEC 2022: 705.12(B)(3)(2)
NOTES AND SPECIFICATIONS:
SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE CEC 2022
ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY
SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.
SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING
EFFECTIVE WORDS, COLORS AND SYMBOLS.
LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR
WIRING METHOD AND SHALL NOT BE HAND WRITTEN.
LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED.
SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT
SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
DO NOT COVER EXISTING MANUFACTURER LABELS.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
4"
3"
ELECTRICAL SHOCK HAZARD
WARNING
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S),
AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC
2022: 690.13(B)
!
INVERTER 1
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM SYSTEM VOLTAGE:VDC550
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.31(D)(2), CEC 2022:
690.31(D)(2)CAUTION
5313 W HENDERSON PL, SANTA ANA, CA, 92704
SOLAR PANELS ON ROOF
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
MULTIPLE SOURCES OF POWER
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC
2022: 705.12(C)
ENERGY STORAGE SYSTEM
PREMISES WIRING MAY REMAIN
ENERGIZED AFTER LOSS OF
UTILITY POWER
CAUTION!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 706.15(C), NEC 2020: 706.15(C)
AC DISCONNECT
INVERTER & ENERGY STORAGE
(EXT)
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
48 AMPS
240 VAC
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
PV SYSTEM DISCONNECT
MAXIMUM SYSTEM VOLTAGE:
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
EXPANSION ENERGY
STORAGE (EXT)
SERVICE ENTRANCE WITH TESLA
BACKUP SWITCH
RAPID SHUTDOWN SWITCH
D