Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
10180827_2302 W. HEMLOCK - Plan
CALCULATIONS FOR Job: GLOVER SOLAR PANELS Address: 2302 W. Hemlock Way Santa Ana, CA 92704 INDEX TO CALCULATIONS Sheet 1 2 Itern design loads, wind uplift check attachment check, rail check, lateral cheek Engineering Calculations Performed By: Doug Engineering 20751 Kelvin Lane, Huntington Beach, CA 92646 949-285-5104 For: Verengo Solar Plus 20285 South Western Avenue, Suite 200 Torrance. CA 90501 (877) 403-3479 Project Number VS-6696 16$*3*A, Date:3/5/2014 AimkLd-04¥.ft BASIS FOR DESIGN #*fre 69163 Ti CODE:2013 California Building Code ASCE 7-10 LIVE LOADS ROOF 20.0 psf £ EXP. 06-30-14 j, LATERAL Seismic Design Category: D R 6.5 Seismic Use Group I SDS 1 SS 150 %SD1 0.6 Sl 60% I 1 WIND Exposure C Figure 30.5-1 - Components and Cladding V38 110 mph Table values are multiplied w 1 by X 1<z, 1 1= 1.21 Exposure C a 3 ft Pnet = 1 X i.zt X I X Pne£30 1 roof slope 7-27 degrees 20 sf Zone; 1 Pnet30 = Zone 2 Pne,30 - Zone 3 Pnet30 - Downward for all zones 1 1 -23.5 psf (interior zones) All panels within Zone 1 &2 -38.6 psf (end zones)Use Zone 2 Value -52.6 psf (Corner Zones within a) 13.8 psf 4 r PROJECT: Glover Solar Panels Doug Engineering SHT.1 OF 2 CLIENT:V.S.Civil Engineering DATE 3/5/2014 BY:DM DE JOB NO. VS-6696 DESIGN LOADS Dead Loads Roof Comp. Shingle 3.5 psf 23.5 psfPuplittzl = 5/8" Ply shtg 1.9 Puptiftz2 =38.6 psf Rf Frm'g 2.8 PWLdown =13.8 psf Misc.1.5 Uplift 0,6DL+0.6WL (N) PV System 3.0 Zone 1 0.6*3.0-0.6*23.5 -12.3 pt Zone 2 0.613.0-0.6'38.6 -21.36 psf Total DL 12.7 psf Downward DL+0.6WL LL 20· psf DL+WL =11.3 psf UPIift Check 2x4 trusses @ 24" o.c. Spacing 2.00 ft Trib panel width =6 ft E 1500000 psi Fb -900*1.5*1.15 1553 psi 5 inA4 Mallow#4Wind =1109 ft-lb Spanl 8.58 ft Mallow,2*4LL =867 ft-lb Span2 7.00 ft See below for Wind Uplift loads Span3 0.00 ft due to concentated loads at attachments (Distance Wihd Mmax P =Mmax to Att.Load Trib Load wind(ft- PVDL live(ft- Pts) a b Rl (lb) R2 (lb (psf) W (ft) (lb) lb) (tb) lb) Panel Edge 1.00 1 2.00 2.00 6.58 -266.0 -80.9 -21.4 6.0 -346.9 -532.1 48.7 65.01 2 5.41 5.41 3.17 -73.7 -126.0 -12.3 6.0 -199.8 -399.1 48.7 84.68 Panel Edge 6.41 Panel Edge 11.83 3 12.83 4 16.24 Panel Edge 17.24 Span 1 Uniform DL 8.58 49.9 49.9 5.8 psf 2.0 11.6 pif Span 2 Uniform DL 7.00 40.7 40.7 5.8 psf 2.0 11.6 Reactions at Spanl -289.8 -157.0 Negative values are uplift reactions Reactions at Span2 40.7 40.7 Mmaxwind®rm =603 ft-lb < 1109 ft-It>OK For DL+LL including the PV system weight point loads W=59.4 pif P = Mmax =673 ft-lb < 867 ft-lb OK 107.1 71.3 48.7 Ib PROJECT: Glover Solar Panels Doug Engineering SHT.2 OF 2 CLIENT:V.S.Civil Engineering DATE 3/5/2014 BY:DM DE JOB NO. VS-6696 CHECK SCREW ATTACHMENTS FOR WIND UPLIFT P.m = 346.9 Ib 5/16" Lag with min 2.5"penetration for each attachment Table 11.2A - NDS - Lag Screw Withdrawal Values For 5/16" Lag into .5G wood 266 Ib Allowable. wind load = 1.632.5*266 1064 Ib >347 Ib OK Unirac Selection Load for half a panel = 2.7' UNIRAC =57.78 pif Per the Unirac Manual for 60 pif, the max span for Solar Mount Unirac Rails is 6.5' Use L-Foot SolarMount Rails with a spacing of 72"lo.c. max for attachment points, typ. Table 8. L-Foot SolarMount Series Rail Span SM - SolarMount HD . Sola,Mount Heavy Duty 2 2.5 3 33 4 43 5 16 1 7 7.5 8 8.5 9 93 10 10.5 11 11'.5 ll 12-5 w = DImiblrted lood (pUl 20 25 30 40 50 60 80 100 120 140 160 180 ZoO 220 240 260 290 300 Sri SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM Sri SM SM SM SM SM SM SM SM 91 SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM J SM SM SM SM SM SM SM 91 Sri SM SM SM SIt SMI SM SM SM SM SM SM SM SM SM SM SM HD SM SM SM SM SM SM 5M SM 91 SM HD SM SM SM SM SM SM SM SM HD MD SM SM SM SM SM SM SM HO HD AD SM SM SM SM 91 HD 1-ID MD SM 5M SM SM SM HD HD AD SM SM SM SM 5M HD ·HD HD SM SM SM SM SM FID HD HD SM SM SM SM ,MD HD HD SM SM SM HO WD MD WD SM SM SM H.D MD HD HD SM SM SM HD PD HD SM SM HD HD HD MD SM SM HD MD WD HD SM MD 'HD WD MD SM HD HD HO HD HD -HD HD HO HD RD HD HD LATERAL ANALYSIS DETERMINE ADDITIONAL LOAD COMPARED TO EXISTING FOR LATERAL LOADING 2600 sf Wpanel =Aroofexisting- 25 *Wpanel =iWroofexisting = 9.7*2600 =25220 Ib wallexisting = 15*80*4 =5400 Ib Wrestolarray = 42.1 Ib 1052.5 Ib 266 Ib Wexisting =30620 Ib V = 0.182W rciofexisting =5573 Ib Existing Total Lateral Force roofwpanels =5813 Ib New Total Later Force V:array =1318.5 Ib % increase =5813 5573 *100%-100% = 4.3% increase' which results in less than a 10% increase in the stress of existing lateral resisting elements OK r. AHJ NOTES: 2010 CALIFORNIA ELECTRICAL CODE: NEC 690.64 (B)(7) LOCATE INVERTER OUTPUT AS FAR AS POSSIBLE FROM NORMAL POWER SUPPLY AT SERVICE PANEL. RELOCATION OF EXISTING CIRCUITS MAY BE NEEDED. DO NOT CHANGE PHASING OF MULTIWIRE CIRCUITS. PERMANENT SIGNAGE AT PV SUPPLY CIRCUIT BREAKERS MUST SAY: A 23 72 *S *t ·a y •C p·r.2,% r · MY.4.2 4 tle E- MASTER I.D.__20\L{ - 113.13(k__-_ G.P. l_fL -.-. .L. PLANNER Aul P 3/[ 0/14 -E... 1 TRANSFERRED BY PLANNING INSDECTION 1.EQU}490: .- , ROUGH 0 i :-un L rg , 3 (714) I 4 / r>i A.:v 7 ..''. NAME F> {ria SHEET INDEX EM=1 GENERAL NOTES, SCOPE OF WORK AND AHJ NOTES PV-l A SITE PLAN PV-2 SITE PLAN, ELECTRICAL ROOF PLAN AND EQUIPMENT ELEVATION PV-2A ROOF FRAMING PLAN AND CONSTRUCPON NOTES PV-2B DETAILS EM=2 MATERIALS UST, SINGLE LINE DIAGRAM AND CONDUCTOR TABLE PV-4 SIGNAGE AND PLACARDS, ELECTRICAL CALCULATIONS ABBREVIATIONS PLAN SET LEGEND INVERTER(S) TEn DC DISCONNECT 29 AC DISCONNECT LC LOAD CENTER MSP MAIN SERVICE PANEL SUB PANEL () FINANCE PARTNER METER () UTILITY METER ----- CONDUIT (EXTERIOR RUN) JUNCTION BOX 26- COMBINER BOX . ATTACHMENT POINT O PLUMBING VENT ® GAS VENT |1 Ame AIR VENT SCOPE OF WORK RESIDENTIAL ROOF-MOUNT PHOTOVOLTAIC SYSTEM SYSTEM SIZE:10 811 STC: 25 X 250.00W = 6.25kW 0- 111 4:<tl..45/1 --FOR PTC: 25 X 226.20W = 5.66kW DC LL ME Ni -9,9%'t (25) YINGU Y1250P-29B MODULES <OIL'38" (1) POWER-ONE-PVI-5000 INVERTER Eg * 63 -2. S pod NAME OF UTIUTY: TO 12:§ :npr.! ' CD m Ck: 9 co c'An, SOUTHERN CAUFORNIA EDISON (SCO Z&.59%LUU)1 -EM CD Iti EL FINANCE PARTNER METER: SUNRUN INC.LU 8 .- 3 i 031 > 341.- 1 -* 0 AlTACHMENT TYPE QUICK MOUNT AlTACHMENTS t SPECKLTY WORK (IF APPLICABLE)O ACCON* BJ =_ _-CD NONE ta >, 6 crrY MAIN SERVICE PANEL UPGRADE:0 2 4 NM LEE. 1 3?E--0FROM :10OA BUSS/10OA DISCONNECT b J 9 4%TO :200A BUSS/20OA DISCONNECT 0 4 w > C B K O (1) - CALIFORNIA CODES rn I PROJECT COMPLIES WITH r .JB5 %• 2013 CALIFORNIA BUILDING CODE cv • 2013 CALIFORNIA MECHANICAL CODE • 2013 CALIFORNIA PLUMBING CODE • 2013 CALIFORNIA ENERGY CODE • 2008 CALIFORNIA ENERGY EFFICIENCY STANDARDS b • ALL CITY ORDINANCES • N.E.C. 690 SUBJECT TO A-P·,·.2 CH'EC.·22· :...... ..-p:TiONS BELOW: -·/U iN i Er·.-·. Cj NO E.7 -"2 - 4.p-:.FIONS El ALL W.'· -' : - ./;Ev--8 O SCRECM;N'.0 - ·· . 4 O SUCLA;iT LANG·ou.i·,id .··.J·, ·IS -AY-.int.,0. 16 N,AA) 00(.0.- ynovnic 96[0-·C ISC .... VOC .., VMP .. IMP ..., EMT ... LBW ... (E) .... (N) .... (EXT) . .. SHORT CIRCUIT CURRENT . VOLTAGE OPEN CIRCUIT ..VOLTAGE AT MAXIMUM POWER CURRENT AT MAXIMUM POWER . ELECTRICAL MErALUC TUBING . LOAD BEARING WALL EXISTING NEW - EXTERIOR Ai No. SO-14-01-018 ESIGN BY : N. LIVELY DATE · 02/28/14 GENERAL INSTALLATION NOTES *UNLESS OTIERWISE NOTED ON PLANS OR PER AH, NOTES, THE FOLL.0-G ARE GENERALIZED AND PERTAIN ONLY TO BUILDING PICTICES AS ADOPTED BY VERENGO SOLAR. PER ART. 705.12 (D)(2), THE PV BREAKER SHALL NOT EXCEED 120% OF THE ALLOWABLE BACK FEED OF THE MAIN SERVICE BUSS RATING. PV WIRE SHALL BE USED ON DC RUNS FOR UNGROUNDED/TRANSFORMERLESS INVERTERS. INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK. 14 4, VICINITY MAP -- PROJECT SITE W ROv.'130= A. e HI- 20 La Buena g M MIS - 102010 W San Lole[1400 L ow of dant£ W Chandler Ave 19 pUOLUe!0 S 8 0 CO larl EET TITLE CONDUIT TO MATCH HOME 24, 21612201 AR©griTFOr'a,FUE,MW HEMLOCK WAY 1 1,14- 2. STRUCT(11#:C'8 u 1-1 36i ACCEMED k=nHOPJ 0 00)1 10!Ot'A O Ul/ J *t d d .-I1--VU6,=. . ..r .-h 11[.2 :t!*,e DRIVE WAY inf Spz:!IR't,NOns must M i.1.9.t 4,1 81" ..h at eli 61289 2#15 It M 9'--"r'Ew'fl'? te mek,0 1,9§,134;&;%112; 1 -COOM -23 aL g**1. 151 STORY HOUSE OfI afratlons on frilo E.ij.gl 1.1'NMen Brinission 0 1 Lu 130/ City of EC::2- f.r a,h.(40 :0?61 >4 M '11 0<0 LI, 4'A Z LU- dl :AptI The &00*72:f'* f?# 2•;9 r#re -4 -e..._.·r· .„.. It 1 1 .....' H .41 1-4.1 .44,Me PUM, '31- 1 --050- LU Z M r ';d ba REff-- toi p?-TII rir Arl f€t ftS.2-'CA'..Ef oi *8 villEtion Of any .10 provisiong of ,:.67 0 :4 07218&239 67 62:9 Law.CD 9*9 0 3467 -U =3 fl N 1 This set of plans e r Accepted By -LUZZL ..31 . Ill2 Date=SE--19 W Q.r 0 ir 1-1-1 R =dCITY OF 2 BJ 1 Date Issued , 5,[%:PI w Jinance m V 0 0 SANTA ANA OF SA 0 PERMIT TYPE: ELECT PLBG MECH GRADING 1 |PERMIT# n OCC. GROUP o \.go RA--1 Z R3 0-ti-09 EZ/ZO 3-1-VCAe N .fiD CONS'TR.TYPE_ 1>2 m CODE EDn-ION O>C-© O \3 *0 44 FLOOD ZONE >f / N FLOOD ZONE GERTIE REQ'D YES NO ! MICROFILM 1 RADI*IT BARRIER @ ROOF RESIDENTIAL DEV. FEE SCHOOL DBTRICT SITE PLAN 1 POOL JA 1'-0" 81.0-L *13All 311ll 133HS NV-Id 31ISZE==--4NO- YES NO 1 YEA NO ; YES ,NO A « LE: 3/32" = PV-1 A ..WHIemlbck-*vi 11681@W**lll Service- A . 0 R 13-1 £0 1 PV-2 HOUSE PHOTO /4 1-1 - 0-1 ft-----=x< l- i IEl TO ARRAY TO UTILITY 2 2 ru rb 1 1 1 2 2 1 1 2 2 1 1 GATE N 2 2 1 1 2 2 1 1 2 2 1 DC MSP 011 0 9L0-1.0-t71.-OS 'ON gor *13All 'N · *El NDIS30 4 L/BZ/ZO 31¥C] 11 1 1 1 -FO \ ,71 1 L-J L-----------1 ' MOINING PLAE - 2 3'-7" 1 MOUNTNG PLANE - 1 ROOF PITCH: 20 ARRAY PITCH: 20 ROOF AZIMUTH: 270 ARRAY AZIMUTH: 270 ROOF AREA: 506.51 80 FT ARRAY AREA:215.76 SO FT NO. OF MODULES: 12 %COVERED: 4260% 3'-3" ROOF PITCH: 20 ARRAY PITCH: 20' ROOF AZIMUTH: 90 ARRAY AZIMUTH: 90 ROOF AREA: 545,24 SO FT ARRAY AREA:233.81 SO Fr NO. OF MODULES: 13 %COVERED: 4208% EQUIPMENT ELEVATION SCALE: N.T.S. 1 ELECTRICAL ROOF PLAN SCALE:1/8" = 1'-0" PV-2 Tel: (714) 380-2452 -[t J-9053 / e-Fax: (310)-755-6456 0 1 £ 47 -m "; 1 9-1 MOUNTING PLANE -1 ROOF TYPE: CDCOMPOSITE SHINGLE ROOF Ws 9 f' 10 + p J =t E kMODULE TYPE = YL250-29b CL u.1 7- D ' MODULE WEIGHT = 42.1 LBS CE 5 g B.·-F f.-A 1- - - r MODULE DIMENSIONS = 64.96"X38.980 = 17.58 SF -.1, CO O CO. -ag 9--·-7 i UNIT WEIGHT OF ARRAY = 2.39 PSF b Iii CR %515\111? 346 XTTACHMENT POINTS: •_72' O.C. MAX ,-Z U.1 m.\1 V,go- V 04 toll On€ ·ny choym. ' 'AG'J.Ga 9,= .. 1.99 SH# 3 ' 61 2 0 Viglatio9 Stat{ Law. i \1 \ to035 0 =CN E .EC' 4 1 - U G *At c O - Re - 4-\ -0 1 0 01_1 I 32 r 1 < J g0d d ci 0 CS C m & 1 1 1 0@ -1- -St1 00 | bo W 9>.'9 511 1 52% m W N 1 1 A 85 £ 5 DESIGN R'-7"7'-0=7'-n" 1-L -ON HOr1-1_LJ_1_L1 1 11 1 V IL- / - (EXT.WALL)(SPAN)(SPAN) ' (SPAN)A (SPAN)(EXT,WALL) • REFERENCE PV-2B FOR ATTACHMENT DETAILS • ROOF FRAMING PLAN Exp 06-30.14 h SCALE:1/8" = 1'-0" CD Z 11 < 2 CK z LL 11 - 8 0 2 I 9 05 0- PV-2A 1 PV MODULE 49% 2'm IX PV MODULE- QUICKMOUNT - ATTACHMENTS 4" - COMPOSTTE / ROOF - FLASHING 2-1/2" ALUMN.i 1 00 8RAIL BY UNIRAC 10 8\, 9 .Al A 2-1/2" ALUMN. IMIL BY UNIRAC 5/li6" SS LAG-BOLT<MIN. 2.5" PENETRATION SEALED-W/SIKAF[=ER 1A SCALE: 1'=1'-O' 1QUICK MOUNT DETAIL COMPOSITE ROOF - QUICK MOUNT BLOW-UP DETAIL - r -ALUMN. V BRACKET / W" SS BOLT & NUT QUICK MOUNT - 2-1/20 ALUMN. RAIL BY UNIRAC >:25 -ATTACHMENTS -'Atte - 5/16" SS LAG BOLT MIN. 2.5" PENETRATION SEALED W/SIKAFLEX 1A SCALE: 3"=1'-0" 2 QUICK MOUNT ISO DETAIL PV QUICK MOUNT ...111 i,M ATTACHMENTS CD LL.1 % Cz 9 3 g#\EU.1 9 Ecr 33 iw SCALE: N.T.S. 3 > A -- EXISTING ROOF TILE r CONDUIT ILSCO COPPER g GROUND LUG a g LU - S.S. HEX NUT H, - <9 0 , =2-1 RUBBER U Uwa GROMMET ---S.S. STAR; WASHER 5 -1 0. 01lr2 E % 8 FLASHING U - R +METAL PLATE /flii O 0 3 3 0 > 6 2 r 2 I . r-; 2.-I-=-..-* Zk -SOLID BARE COPPER CONDUCTORC<%--.-%. . 77) 34 ACI- - -,/ - - 50LAR MODULE TYP. CONDUIT PENETRATION DETAIL SCALE: N.T.S. 4 GROUND LUG DETAIL SCALE: 1/2"=11-0" 5 - CONDUIT CONDUIT -7 - UNISTRUTCONDUIT CLAMP - UNISTRUT 0 44CONDUIT CLAMP 1 11- 1. /\ P 1-5/8 X 1-5/8 UNISTRUT CONDUIT HEIGHT - 1 -5/8 X 1 -5/8 ABOVE MOUNANG UNISTRUT PLANE TO ISO VIEW BE 1 5/8"SCALE: N.T.S. .Mrc 69163 54'Wil F 8|'0-|'O-PL-OS . 01\1801' 311ll 133HS ,V-2B CONDUIT CLAMP ASSEMBLY SCALE: 3" = 1'-00 6 CONDUIT TO ROOF ISO DETAIL SCALE: N.T.S. 7 EQUIPMENT QIY DESCRIPTION YINGU ENERGY (CHINA) YINGU Y1250P-29B 250WSOLAR PV 25 VOC= 38.4V VMP= 30.4VMODULE ISC= 8.79A IMP= 8.24A PMAX: 250W PTC RATING: 226.2W KRALOY J-BO* 6x6x6 CSA C22.2 J-BOX 1 #40 CUTOUT, JUNCTION AND PULUBOXES POWER-ONE-PVI-5000=OUTD-US-A (24* MPPT VOLTAGE RANGE: 1 200_600V MAX DC INPUT VOLTAGE:INVERTER 600V AC VOLTAGE RANGE: 211-264 MAX AC OUTPUT CURRENT: 23A CEC EFFICIENCY: 96.5% USTED WITH INVERTER. SEEDC DISCONNECT 1 SPECIFICATION SHEET. 1-210+C SMART METER 120-240 SUNRUN 1 VAC, 3.3V / m COMPATIBLE METER ASYNCHRONOUS AC EATON / CUTI-ER HAMMER DG221 URBDISCONNECT 1 600 VAC, 308, NEMA 3R, UL USE PHOTOVOLTAIC 1 2-POLE PV BREAKER, 240V, 30ABREAKER MAIN SERVICE 1 240V, 200ADISCONNECT NEW UPGRADED MAIN SERVICE PANEL MAIN SERVICE 1 1-PHASE, PU-200 AMP BOTTOMPANELFEED,, 240 VAC, 200A GROUND ROD 1 05/8" X 10'L 8' EMBED. PLACED MIN 6' AWAY FROM EXISTING GROUND ROD CONDUIT 60' 3/4" EMT CONDUIT 11 1 J B 1 1 i lf' 0 0 4 5 flil 5 QIY ,CONDUCTOR INFORMATION (4) #10AWG - PV WIRE IN FREE AIR O) #BAWG - BARE COPPER GND IN FREE AIR (4) #10AWG - THWN-2 DE En (1) #8AWG - THWN-2 GN IN 3/4" EMT -1* bRIC 0_ LU h 1 1 (37 #10AWG - THWN-2 5@Sh (1) #8AWG - THWN-2 GN IN 3/4' EMT % g 3 1- \#8 BARE ARMOR COPPER 0 % Hui-Comly.2. (1) EXISTING GROUNDING S¥STEM 0 & i WCD lu w q M> 9 m O Z>09(\1 LU 06 " 31 10to o M0500 re1.11 g e *t UNGROUNDED SYSTEM -J SYSTEM WIRES TO BE: RED AND BLACK r- 6 N ELI 9 (0 Co- 120% RULE CO le * 02 X 20 200 X 1.2 = 240A 5 J 0.40 0 240 - 200 = 40A MAX BACK FEED g 9 E- > *t 2 0 2'-8-DIRECnONAL UTILITY METER 1 -PHASE, 3 WIRE 120/240V 2 32 R5 0 g0 N ATTACHMENTS 36 QUICK MOUNT ATTACHMENTS 2 12 MODULES IN SERIES RAIL 142' UNIRAC RAIL 1 :ROOF 20:: PITCH MID CLAMPS 42 MID CLAMPS 90.: AZ[MUTH LE 1 1 END CLAMPS 16 END CLAMPS 13 MODULES IN SERIES IDCN MSP / .-4 114 JOBNO. : SO-14-014 All 'N I *El NOIS3(]V I./BE/W · 31¥0 2:ROOF 20. PITCH 270:: AZIMUTH <D 111 0-0 8LC A13 UJ Z | 10 -c=b 1 3-Illl 133HS 11 319NIS PV-3 21®EE E El E 1.-2-1 t GROUND-FAULT DETECTION AND INTERRUPTION; TO BE INSTALLED AT INVERTER PER NEC 2011 690.5 (C) WARNING ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED, NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED DISCONNECTION MEANS; TO BE INSTALLED AT ALL AC AND DC DISCONNECTS RESPECTIVELY PER NEC 2011 690.14(C)(2) SOLAR AC DISCONNECT SOLAR DC DISCONNECT DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSmON; TO BE INSTALLED AT DISCONNECTING MEANS PER NEC 2011 690.17 WARNING ELECTRIC SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION. PHOTOVOLTAIC POWER SOURCE SHALL BE LABELED WITH THE FOLLOWING WARNING AT EACH JUNCTION BOX, COMBINER BOX, DISCONNECT, AND DEVICE WHERE ENERGIZED, UNGROUNDED CIRCUITS MAY BE EXPOSED DURING SERVICE PER NEC690.35(F) WARNING ELECTRIC SHOCK HAZARD. THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED INVERTER OUTPUT CONNECTION TO BE INSTALLED AT MAIN SERVICE PANEL PER NEC 2011 705.12 (D)(7) WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE MARKING SHOULD BE PLACED ON ALL INTERIOR AND EXTERIOR PV CONDUIT, RACEWAYS, ENCLOSURES, AND CABLE ASSEMBLIES, EVERY 10 FEET, AT TURNS AND ABOVE AND/OR BELOW PENETRATIONS AND All PV COMBINER AND JUNCTION BOXES. o SHALL BE REFLECTIVE WEATHER RESISIANT MATERIAL CAUTION: SOLAR CIRCUIT TO BE LOCATED AT MAIN SERVICE PANEL: CAUTION: SOLAR EL-ECTRIC SYSTEM CONNECTED TO BE INSTALLED ON THE FACE OF THE SERVICE METER PANEL PER NEC 2011 705.10 CAUTION: POWER TO THIS BUILDING IS ALSO SUPPUED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN W HEMLOCK WAY AT: 9 METER AND MAIN SERVICE 1--1 %\ /5,/AC DISCONNECT ® DC DISCONNECTINVERTER ® DIRECT-CURRENT PHOTOVOLTAIC POWER SOURCE TO BE INSTALLED AT INVERTER PER NEC 690.53 & 690.54 OPERAnNG CURRENT: 8A OPERAnNG VOLTAGE: 395V SHORT-CIRCUIT CURRENT: 1 OA MAX SYSTEM VOLTAGE: 559V DIRECT--CURRENT PHOTOVOLTAIC POWER SOURCE TO BE INSTALLED AT AC DISCONNECT PER NEC 690.54 AC OUTPUT CURRENT 234 NOMINAL OPERATING VOLTAGE: 240V /= t 0 MARKING CONTENT AND FORMAT 0 RED BACKGROUND o WHITE LETTERING o MINIMUM 3/8' LETTER HEIGHT u ALL CAPITAL LETTERS 0 ARIAL OR SIMILAR FONT, NON-BOLD c] WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT (DURABLE ADHESIVE MATERIALS MUST MEET THIS REQUIREMENT MAX PV VOLTAGE & CURRENT CALC'S: ACCONDUCTOR AMPACITY CALCULATIONS: RECORD LOW TEMP. CC): -5' VOLTAGE CORRECTION PER NEC 690.7: 1.12 MAX PV SYSTEM VOLTAGE (PER NEC 690.7): Vcorrection X Voc X # MODULES IN SERIES 1.12 X 38.40 X 13 = 559.10V MAX PV CURRENT PER NEC 690.8(A)(1): 1.25 X Isc 1.25 ;X 8.79 = 10.99A # OF INVERTERS: 1 EXPECTED WIRE TEMP ¢C): 41 TEMP CORRECnON PER NEC TABLE 310.15(B)(16): 0.87 CIRCUIT CONDUCTOR SIZE: 10 AWG # OF CURRENT CARRYING CONDUCTORS: 3 CONDUIT FILL PER NEC 310.15(B)(3)(a): 1 CIRCUIT CONDUCTOR AMPACITY: 40 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): 1.25 X MAX INVERTER OUTPUT CURRENT= 1.25 X 23.00 = 28.75 A DC CONDUCTORAMPACITY CALCULATIONS: ARRAY TO JUNCTION BOX EXPECTED WIRE TEMP (°C): 41' TEMP CORRECTION PER TABLE 310.15(B)(16): 0.87 # OF CURRENT CARRYING CONDUCTORS: 4 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 0.8 CIRCUIT CONDUCTOR SIZE: 10 AWG CIRCUIT CONDUCTOR AMPACITY: 40 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.80\&B): 1.25 X 1.25 X Isc = 1.25 X 1.25 X 8.79 = 13.73A DERATED AMPACHY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(16) X CONDUIT FIU CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.87 X 0.8 X 40 = 27.84A DERATED Al,PACIP( OF- aRCUIT CaiDUC[ORS PER NEC TABLE 310.15(B)(16): TEMP CORR. PER NEC 310.15(B)(16) X CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.87 X1X40= 34.80 A DC CONDUCTOR AMPACITY CALCULATIONS: FROM JUNCTION BOX TO INVERTER AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT PER NEC 310.15(B)(3)(c): + 22 EXPECTED WIRE TEMP ¢C): 41' + 22° TEMP CORRECTION PER TABLE 310.15(B)(16): 0.58 # OF CURRENT CARRYING CONDUCTORS: 4 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 0.8 CIRCUIT CONDUCTOR SIZE: 10 AWG CIRCUIT CONDUCTOR AMPACITY: 40 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.80&8): 1.25 X 1.25 X Isc 1.25 X 1.25 X 8.79 = 13.73 A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(16) X CONDUIT FIll CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.58 X 0.8 X 40 = 18.56 A€] 91 'Al CO < 1 L YGE 60 CELL SERIES e YL255P-29b YL250P-29b YL245 P-29b YINGMEkE}LAR YL240P-29b YL235P-29b U.S. Soccer Powered by Yingli Solar COMPANY t 3 Yingli Green Energy (NYSE:YGE) is one of the world's largest fully vertically integrated PV manufacturers. With over 4.5 GW of modules installed globally, we are a leading solar energy company built upon proven product reliability and sustainable performance. Founded in 1998, Yingli Green Energy serves customers through our U.S. subsidiary,· Yingli Americas, co-headquartered in New York and San Francisco. We are the first renewable energy company to sponsorthe U.S. National Soccer teams and the FIFA World Cup- PERFORMANCE Industry leading in-house manufacturing of polysilicon, ingots, wafers, cells and modules ensures tight control of our material and production quality. High performance, multicrystalline solar cells deliver a module series efficiency of up to 15.6%, reducing installation costs and maximizing the kWh output per unit area. Tight positive power tolerance of -OW to +5W ensures modules , are delivered at or above rated power, improving system performance through the reduction of module mismatch loss. QUALITY & RELIABILITY Robust, corrosion resistant aluminum frame independently tested to withstand wind and snow loads of up to 50 psf and 113 psf, respectively, ensuring mechanical stability. Manufacturing facility certified to ISO9001 Quality Management System standards. Module packaging optimized to protect product during transportation and minimize on-site waste. WARRANTIES Leading limited power warranty* ensures 91.2% of rated power for 10 years, and 80.7% of rated power for 25 years. 10-year limited product warranty. * In compliance with our warranty terms and conditions. QUALIFICATIONS & CERTIFICATES UL 1703 and ULC 1703, UL Fire Safety Class C, CEC, FSEC, ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007, SA8000 c®us 127, Rj'¥1 12 0 LISTED CE] -(MOTOVOLT/EMODULE} - 44DD NGLISOLAR.COM/US Yingli Americas 1443 94* 0,4.= M 0% fl--AYUIL OU CELL SERIES Powered by YIN[EU ELECT'RICAL PERFORMANCE -2----1.-,i-2-:I 2-4--4 ....= A-, GENERAL CH ARIACT ERISTICS Module type- - - -- -YL.2552-29b YL250P-29b YL245P-29b YL 210P-29b Power outpd Prr- W 255 250 245 240 Powor output tolerances AP=. W -0/+5 Module efficiency r. 5% 15.6 15.3 15.0 14.7 Voltage at P11..mpp V 30.6 30.4 30.2 29.5 Current at P-Impp A 8.32'8.24 8.11 8.14 Open-circuit voltaga Voe V 38.7 38.4 37.8 37.5 Short-circuit currant lie A 8.88 8.79 8.63 8.65 STC· 10COW/in' irradiance. 25•C ccll temperaturc. AM 1.5( spectrum according to EN*090423 Avenge relative :·fficiencyreduccionof 5 0% M 200W/m' a-ccoiding to EN 60904-1 ¥1235P-29b Dimensions (UW/H)64.6 in (1650 mrn) /38.98in (990 mm)/ 157 in (40 mm) 235 Weight 42.1 lbs (19.1 kg) 14:4 29.5 7.97 PACKAGING SPECIFICATIONS 37.0 Number of modules per pallet 26 8:54 34Number of pallets per 53' container Packaging box dimension: (UW/H)67/in (1700 mm} / 45 in {1150 mrn) / 47 in (1190 mm) Power output pm. W 184.7 181.1 177.9 174.3 170.7 Voltage at P-'V./p V 27.9 27.6 27.2 26.6 26.6 Current at Pm„1- A 6.63 6.56 6.54 6.56 6.42 Open-circuit voitage 6 V 35.7 35.4 34.5 34.2 33.8 Short-circuit current L A 7.19 7.12 6.99 7.01 6.92 Box weight 1177 lbs (534 kg) Units: inch (mm) 38.98[(990) 37.24 {946)1.5740) C, ...NOCT: open<ircuit operating cell temperature ar 800W/m' in·adiance, 20°C.ambient temperature, 1 m/s wind: speed 11_0- THERMAL CHARACTERISTICS Nominal operating cetl temperature NOCT •C Temperature coefficient of Pma.V %/ec Temperature coefficient of V.0.. %7.C Temperature coefficient of h. auc 96/'C Temperature coefficient of Vmpp h,pe %2C OPERATING CONDITIONS Max. system voltage Max. series fuse rating Limiting reverse current Operating temperature range Max. static load, front (e.g., snow and wind) Max. static load, back (e.g.. wind) Hailstone impact CONSTRUCTION MATERIALS Front cover (material/type/thickness) Catl (quantity/material/type/dimensions/ area/# of busbars) Encapsulant (material) Frame (material/color) Junction box (protection degree) Cable (typo/longth/gauge/outside diameter) Plug connector (manufacturer/type/protection degree) 46 +/- 2 -0.45 -0.33 0.06 -0.45 600Voc 15A 15A -40 to 194·F{·40 to 90'C) 113 psf{5400 Pa) 50 psf (24CO Pa) 1 in {25 mm) at 51 mph (23 rn/4 Low-iron glass / tempered / 3.2 mm Glass may have anti-reflective coating 60 1 poly,ilicon / multicrystalline / 156 mm x 156 mm / 243.3 cmZ / 2 or 3 Ethylenevinyl acetatei(EVA) Aluminum;alloy / anodized silver or black ZIP65 PV Wire / 43.31 ifi (1100 mm) / 12 AWG / 0.244 in (6.2 mm) Amphenol / H4 / IP68 UF 0 Grounding holae @ 9 r 6-00.236 (61 .0 10256:0316.5.8) 8-4 Drainage:holes 33 1 8-0.12xo.315 (3KS) ,.Er ' -1 - (100) / r \ \ / 1 D; SECTION 8-8 \ 1/ / I 4 1.2692); -./ Warning: Read the Installation and Wser Manual in its entiretybefore handling, installing, and operating Yingli modules. Our Partners 3.94 0.47 (12) 00) The specifications in this datashect are not guaranteed and are subject to change without prior notice. This datasheet ccmplies with EN 50380:2003irequirements. Yingli Green Energy Americas,i Inc. info@yingliamericas.com Tel: +1 (888) 686-8820 YINGLISOLAR.COM/US | NYSE:YGE NILAR © Yingli Green Energy Holding Co. Ctd. | YGE60CelISeries2013_EN_201301_Vol U.S. Soccer Powered by Yingli Solar -1 0% 144.% f 'lf»¢*./ L. , .. 21* 9 vii 011 nv 7344 A MEMBER OFTHE ABB GROUP GENERAL SPECFICATIONS -E@*bl/· 1, 1, Designed for residential and small commercial PV installations, this .1/2' 2., - 4inverter fills a specific niche in the Aurora product line to cater for · those installations producing between 5kW and 20kW.mrmmllmEREEn This inverter has all the usual Aurora benefits, including dual input i section to process two strings with independent MPPT, high speed :lillilill'll'll'll'll"// and precise MPPT algorithm for real-time power tracking and .1 6 energy harvesting, as well as transformerless operation for high b -..--Ii--performance efficiencies of up to 97.1%. D The wide input voltage range makes the inverter suitable to low power installations with reduced string size. This outdoor inverter has been designed as a completely sealed unit to withstand the harshest environmental conditions. gC . r*atuires 24 S.#ch & Aliting#,>. • Each inverter is set on specific grid codes which can be selected in the field • Single phase output • Dual input sections with independent MPPT, allows optimal energy harvesting from two sub-arrays oriented in different directions • Wide input range • High speed and precise MPPT algorithm for real time power tracking and improved energy harvesting • Flat efficiency curves ensure high efficiency at all output levels ensuring consistent and stable performance across the entire input voltage and output power range • Outdoor NEMA 4X rated enclosure for unrestricted use under any environmental conditions • RS-485 communication interface (for connection to laptop or datalogger) • Compatible with PVI-RADIOMODULE for wireless communication with Aurora PVI-DESKTOP • Integrated Arc Fault Detection and Interruption (-A Version) 4- ,%,= , 6--1,1 XL_ Irm..1 -7 4*, 4624%i -#245 2 .1..!t'lititb"t- - - - k >F--'-2.k J 16-- ..24£Ul!0*'4-3..L.·34-w,=L +*ME I *- 14;2221 Nominal Output Power Maximum Output Power Rated Grid ACVoltage .[offaside.(9€1.-,- ..'·. LLI.·2..c.2.:u= ·74....- Numberof Independent MPPT Channels Maximum Usable Power for Each Channel Absolute Maximum Voltage (Vmax) Start-Up Voltage (Vstart] Full Power MPPTVottage Range Operating MPPTVoltage Range Maximum Current (ldcmax) for both MPPT in Parallel Maximum Usable Curient per Channel Maximum Short Circuit Current Limit per Channej Numberof Wire LandingTerminals Per Channel Array Wiring Termination Grid ConnectionType Adjustableyoltage Range (Vmin-Vmax} Grid Frequency _ justable Grid Frequ-ency Rangp Malimum Burrent (lacnkxl- Power Factor Total Harmonic Distortion At Rated Power Contributory Fault Current .. Grid Wiring Termination Type -EMettiE.29*i-. 1-.-)31.--+.1.-1:: _-. -':fiy-F Input ReGUse Poiari#Rrot*#4 Ovepbonage Protection Type PVArray Ground Fault Detection Output Anti-Istanding Protection Over-Voltage Protection Type Maximum ACOCPD Rating **iEf -'-7-7 31 3,- '.'.Frov·---.... Maximum Efficiency CECEfficiency 28!?rM![19-P?ffermance. ..Li,.·-· I ' ', ·.-- - - Stand-by Consumption Nigh! time consumption _,gunica_tj29.-2 -46:-·-u- ' ..2_1. ' . ... User-Interface Remote Monitoring (lxR5485 incl.) Wired Local Monitoring {lxR5485 ineLl Wirejess LoGIMAnitoring Environme'ntal' '- 5000 5000 240 2 4000 600 W 6000 W 6000 V 208 277 208 240 277 r· · '1 ' Al, ..2-¥t . , 2 W 4000 V 600 V 200 (adj. 12.0-350)200 (adj. 120-350,) V 200·530 200-530 V 0.7xVstart-580 O.7*Vstart-580 A 36 36 A 18 18 A 22 22 2Aks · 2 pairs Terminal block, Pressure Clamp, AWG8-AWG¢ . 10/2W Spli 0/3W 10/2W 10/2W Split-0AW 10/2W V 183-228 211-264 244-304 183-228 211-264 244-36 Hz 60 60 Hz 57=60.5 57-60.5 Ans 27 23 20 30 28 24 > 0.995 >0.995 % <2 <2 APAR«;3655>15.63 365/25.81 31.75/22A5 36.25/25.63 365/25.81 31.7*2i45 Terminal block. Pressure Clamp, AWG8- AWG4 Yes ¥bs Varistor, 2 foreach channel Varistor, 2 foreachchannel Pre start-up™Mko and ciynamic GFDI Prc start-up Riso and dynamic GFDI (Requ,reR Floatiag Arrays)(Requires FIQating Arrays) Meets UL 174i/IEE1547 requirements Meets UL 1 741/IEE1547 requirements Varistor, 2 (Li-L,/L,-G)Va,istor, 2(6-6/6-G) A 35 30 25 40 35 30 % 97.1 97.1 % 96 96.5 95.5 95 96.5 96.5 v\,4,<8 <8 WaM; <0.6 <0.6 16 characters x 2 lines LCD display AURORA-UNIVERSAL (opt.1 PVI-USB-RS£185_232 (opt.), PVI-DESKTOP (opt.) PVI-DESKTOP (opt.) with Pi/1 RADIOMODULE (opt.) Ambient Air Operating Temperature Range Ambient Air Storage,Temperature Range Relative Humidity Acoustic Noise Emission Level Maximum Operating Altitude without Derating Me3Ianic'al I&Kifigtions -- . I''i- . . -- Enclosure rating Cooling Dimensions (H x W x D) Weight Shipping Weight Mounting System Conduit Connections DC Switch Rating-(Per Contact) .Mity> '2 Isolation Level 5afetyand EMC 5tandard 5afety Approval Warranty- Standard Warranty Extended Warranty Available Models Standard - With DC Switch - Floating Ar,Gy With DC 5witch, Wiring box and Arc Fault Detector and Interrupter 'All data is sublect [o change wit Nout notice ••Inverter can apply that much current · Breakerwill open 'F (.Cl -13 to +140 (-25 to +60) FF (C)-40 to 176 (-40 to +80) % RH 0-100 condensing db(A)@lm <50 ft(m)6560(2000) NEMA 4X Natural Convection in (mm)41.4 x 12.8 x 8.6 (1052 x lb(kg) <59.5 (27.0) lb(kg) €78 (35.4) Wall bracket Trade Size Kos: Q.ca x 1/21 and (2eax 1-1/4'.3 places side, front, rear) N'Q 25/600 Trans formcrless (Floating Array) UL 1741.IEE1547. IEE1547.1,CSA-C22.2 N. 107.1-01 ,CSA.. years 10 years 15&20 Pvl-5800·oum-05 PV!-5000-OUTD-US-A - --923+140(3570+60) - -- with derating above 122 (50) -40 to 1 76 HO to +80) 0-100 condensing <50 6560 (2000) NEMA 4X Natural Convection 325 x 218) <59.5 (27.0) < 78 (35.4) Wall bracket Trade Size Kos: Oca x 1/21 and (2ca x 1-1/4", 3 places side, front, rear) 25/600 Transformerless (Floating Array) , UL 1998, UL 1699 8. FCC Pa n 15 Class B ,CSA„ 10 15&20 PVI-6000-OWTD-US PVI-6000-OUTD·US-A A.'Ill..."0 '- Elar JITE'#2="I'll""IN . N- ..1 f®Quick Mount er.lib-7 El Your So/ution in Mounting Products Solar •1-|2O . Conduit • HVAC • Custom Composition Mount Specifications - 5/16" - PV - Quick Mount PV ® is an all-in-one waterproof flashing and mount to anchor photovoltaic racking systems, solar thermal panels, air conditioning units, satellite dishes, or anything you may need to secure to a new or existing roof. It is made in the USA of all aluminum and includes stainless steel hardware. It works with all standard racks, installs seamlessly and saves labor by not need- ing to cut away any roofing: will out live galvanized 2 to 1, and is a better low-profile mount. Ice Split Lock Washer SS 5/16" (Not a theft- prevention feature) Fender Washer SS 5/16"xl" - - EPDM Rubber Washer 60 Durometer 5/16"C¤U===GREE*Scaling Washer SS 5/16" - F Hanger Bolt SS 5/16" x 6" -T1 1/4" Machine, 1 3/4" Spacer, 3" Lag Mount & Flashing Aluminum - Mount 1 1/4" x 1 1/4" x 2 1/4" Beveled Block- Flashing .05" thick For standard composition roofs: ESR-2835 . (2) Hex Nuts SS 5/16" flashing is 12" x 12" mount is attached 3" off center Lag pull-out (withdrawal) capacities (lbs) in typical lumber: Lag Bolt Specifications Specific 5/16' shaft 5/16" shaft gravity per 3"per 1" thread depth thread depth Douglas Fir, Larch .50 798 266 Douglas Fin South .46 705 235 Engelmann Spruce, Lodgepole Pine (MSR 1650 f & higher).46 705 235 Hem, Fir .43 636 212 Hem, Fin (North).46 705 235 Southern Pine .55 921 307 Spruce, Pine, Fir .42 615 205 Spruce, Pine, Fir (E of 2 million psi and higher grades of MSR and MEL)..50 798 266 Sources: Uniform Building Code; American Wood Council Notes: 1) Thread must be embedded in a rafter or other structural roof member. 2) Pull-out values incorporate a 1.6 safety factor recommended by the American Wood Council. 3) See IBC for required edge distances. 936 Detroit Ave Suite D, Concord, CA. 94518 Phone: (925) 687-6686 Fax: (925) 687-6689 1 of 4 Email: info@quickmountpv. corn www.quickmountpv.com f 5/16" SS Hex, Nut 19" '1 Beveled Block 1 1/4" x 1 1/4" x 2 1/4" ll 1 1 5/16" Split Lock Washer /(Not a theft-prevention feature) 5/16" x 1" SS Fender Washer- TypicalBlock pivots on flashing 5/16" 60 Durometer L foot,with water-proof seal -EPDM Rubber Washer not, included-;c 0/- 1 5116" SS Hex Nut5/16" SS Sealing Washer- (3 5/16-18 x 6" SS Hanger Bolt: 11/4" Machine, 1 3M" Spacer 3" Lag 7 \\ U E-7 166111/4" 1 1 Compostion/ , Roofing 1 1 11 11 1 i' 1 .U i 1 l A-1 E /4."1 6"1/2" OSB or/ Plywood 4 21/4" W12" RafteM ¥1, Scale 12 U> TITLE:QM-PV-Comp %16" COMMENTS FILE NAME QMSC_EXP_ 3125Scale 1:5 PROPERTY:OF QUICK MOUNT PV · ALL RIGHTS OF DESIGN OR INVENTION ARE RESERVED: DATE 1/07/11 REVISION 5 DRAWN BY F.K. Quick Mount PV Yo_ur 5041.tion_in:Mounting.prodlict5 Solar • 11,0 • Conduit o HVAC · Custom PJOE 4\ -FESE inc 5TI?11(TURAL INGINFIRM January 13, 2014 ..s,04... ,'' a. *ANENNE TH ·8 2/11 44·4:' UniRac 23.2/ 1\99 ta\, 1411 Broadway Boulevard NE I , ImiAlbuquerque, New Mexico 87102-1545 ,1 7 / No. 63878 1 1 3 1/ Exp. 34' 1-': .621 TEL: (505) 242-6411 ..4 STRUCToae, ©FAX: (505) 242-6412 37.-9.cuf>.. Attn.: Engineering Department, Re: Engineering Certification for UniRac's SolarMount Code-Compliant Installation Manual 227.3 PZSE, Inc.-Structural Engineers has reviewed UniRac's "SolarMount Code-Compliant Installation Manual 227.3" published January 2014 and specifically "Part I. Procedure to Determine the Design Wind Load", and "Part II: Procedure to Select Rail Span and Rail Type". The procedures are used to; determine the calculation of the design wind force, load combinations, applied loading and rail selection. All information, data and analysis contained within the Installation Manual are based on, and comply with the'following: 1. Minimum Design Loads for Buildings and other Structures, ASCE/SEI 7-05 and ASCE/SEI 7-10 2. 2012 International Building Code, by International Code Council, Inc. 3. 2013 California Building Code, by California Building Standards Commission 4. 2010 Aluminum Design Manual, by The Aluminum Association- This letter certifies that the structural calculations contained within UniRac's "SolarMount Code-Compliant Installation Manual 227.3 are in compliance with the above Codes. If you have any questions on the above, do not hesitate to call. Sincerely, k Paul Zaeher, SE - President 8137 Sunset Avenue, Suite 120 • Foit Ooks, CA 95628 • 916.961.3960 • 916.961.39651 • WWW.PISE.(014, ma UNBRAC1I(106,2#,45*)422*49,:i.1,7,3,,1..*3?rit, A-:".9.*P.:sild:.?,t'.3,#,1'i;jft·fk;tf '' U,· -f; !, ''.ii *17·&PNFr .,.4/.#5*solARMOUN#Jadli Aidal {Dataiheatil A '11111 •a:.wi '.t]M'*N SolarMount Technical Datasheet Pub 110818-·Itd Vl .0 August 2011 SelarMount Module Connection Hardware 1 Bottom Up Module Clip . 1 2Mid Clamp End Clamp 2 SolarMount Beam Connection Hardware 3 L-Foot -3 SolarMount Beams 4 SolarMount Module Connection Hardware SolarMount Bottom Up Module Clip Part No. 302000C / ' Washer ·Bottom Up Clip material: One of the following extruded aluminum Bottom .ifiut (hidden..se alloys: 6005-T5, 6105-T5, 6061-T6 Up Clip / 1 5te-*) •Ultimate tensile: 381<si, Yield: 35 ksi · Finish: Clear Anodized · Bottom Up Clip weight: -0.031 lbs (149) · Allowable and design loads are valid When components are assembled with SolarMount series beams according to authorized UN[RAC documents · Assemble with one %1,-20 ASTM F593 bolt, one 1/7-20 ASTM F594 serrated flange nut, and one 34" flat washer · Use anti-seize and tighten to 10 ft-lbs of torque »4 ·Resistance factors and safety factofs are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third- party test results from an IAS accredited laboratory Module edge must be fully supported by the beam Beam TA't * NOTE ON WASHER: Install washer on bolt head side of assembly. DO NOT install washer under serrated flange nut A -X L ' 1 ir - 1.24 1.co Applied Load Average Allowable Safety Design Resistance Direction Ultimate Load Factor,Load Factor, lbs (N)lbs (N) FS lbs (N) * Tension, Y+1566 (6967) 686 (3052)2.28 1038 (4615)0.662 Transverse, Xi 1128 (5019)329 (1463)3.43 497 (2213)0.441 Sliding, Zi 66 (292)27 (119)2.44 41 (181)0.619 Dimensions specified in inches uhless noted ¢94 546%%04 .34233*»**3*.· 94·;39"13<4£44: uiy.96%426%*SS'$.2... - *. My# 933'lEt fl¢P1SdjLARMOON¥. Tioh nlidd'I Dataah@et §1 :im UN I RAE A ·,IL· i te/?Zle C'JAUVi,=·· SolarMount Mid Clamp Part No. 302101 C, 3021010, 302103C, 30217048, 3021050,302106D \4 rab©\\glptrt/«f *EV,\ lili-9 32... Beam .,P< Bolt L Mid clamp material: One of the following extruded aluminum alloys: 6005-T5, 6105-T5, 6061-T6 Ultimate tensile: 38ksi, Yield: 35 ksi Finish: Clear or Dark Anodized Mid clamp weight: 0.050 lbs (23g) Allowable and design loads are valid when components are assembled according to authorized UNIRAC documents Values. represent the allowable and design load capacity of a single mid clamp assembly when used with a SolarMount series beam to refain a module in the direction indicated Assemble mid clamp with one Unirac W'-20 T-bolt and one W'-20 ASTM F594 serrated flange nut Use anti-seize and tighten to 10 fi-lbs of torque Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third- party test results from an IAS accredited laboratory Applied Load |Average Allowable Safety Design Resistance 1.00 DISTANCE -Direction Ultimate Load Factor,Load Factor, DEr.VEEN MODULES . £lbs (N)lbs (N) FS lbs (N) ® Y A Tension, Y+2020 (8987) 891 (3963)2.27 1348 (5994)0.667 Transverse, Zi 520 (2313)229 (1017)2.27 346 (1539)0.665 Sliding, XIE 1194 (5312)490 (2179)2.44 741 (3295)0.620 ,- X Dimensioris specified in inches unless noted SolarIViount End Clamp Part No. 302001 C, 302002C, 302002D, 302003C, 302003D, 302004C, 302004D, 302005C, 302005D, 302006C, 3020060,3020070,302008C, 302008D, 302009C, 302009D, 302010C,i302011 C, 302012C /loIt 32*4Clamp Serrated /<·>»·' Flange Nut N Y .X t.5 -- ME'.:NOM ...GE VAR:CS Wlili 1.ID{>U LE · End clamp material: One of the following extruded, aluminum alloys: 6005-T5, 6105-T5, 6061-T6 • Ultimate tensile: 38ksi, Yield: 35 ksi · Finish: Clear or Dark Anodized · End clamp weight: varies based on height: -0.058 lbs (26g) Allowable and design loads are valid when components are assembled according to authorized UNIRAC documents · Values represent the allowable and design load capacity of a, single end clamp assembly when used with a SolarMount series beam to retain a module in the direction indicated Assemble with one Unirac W'-20 T-bolt and one 14"-20 ASTM F594 serrated flange nut Use anti-seize and tighten to 10 ft-lbs of torque Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third- party test results from an IAS accredited laboratory ·, Modules must be installed at least 1.5 in frorn either end of a beam IlllLA.•L_, Dimensions specified-irtifialieslifilessrtifted Applied Load Average Allowable Safety Design Resistance Direction Ultimate Load Factor,Loads Factor, lbs (N)lbs (N) FS lbs (N) 0 Tension, Y+1321 (5876) 529 (2352)2.50 800 (3557)0.605 Transverse, Zi 63 (279)14(61)4.58 21 (92)0.330 Sliding, >79 (349)0.555142 (630)52 (231)2.72 9(95.0.4429434*1313*frt**t?'*<ft'}fii)2 it 'iyE-I':(I€21'-4'*..2 . 3 E.Atir}0.-219?' D _OMPAN p Sola:rMo:unt Beam Connection Hardware SolarMount L-Foot Part No. 304000C, 304000D Ait-,-i44- Bolt L-Foot NE*MSIP' Flange Nu r Y A $X 80 L-Foot material: One of the following extruded alumihum alloys: 6005- T5,6105-T5, 6061-T6 Ultimate tensile: 38ksi, Yield: 35 ksi Finish: Clear or Dark Anodized L-Foot weight: varies based on height: -0:215 lbs (98g) Allowable and design loads are valid when components are assembled with SolarMount series beams according to authorized UNIRAC documents For the beam to L-Foot connection: · Assemble with one ASTM F593 %"-16 hex head screw and one ASTM F594 %"serrated flange nut · Use anti-seize and tighten to 30 ft-lbs of torque Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third-party test results from an IAS accredited laboratory NOTE: Loads are given for the L-Foot to beam connection only; be sure to check load limits for standoff, lag screw, or other attachment method 3X kOT FOR 16 ItARD,·/AAE Ti' x. i / 2.01 - Dimensions specified in inches unless noted Applied Load Average Safety Design Resistance Direction Ultimate Allowable Load Factor,Load Factor, lbs (N).lbs (N)FS lbs (N) ® Sliding, Zi 1766 (7856)755 (3356)2.34 1141 (5077);0.646 Tension, Y+ 1859 (8269)707 (3144)2.63 1069 (4755)0.575 Compression, Y- 3258 (14492)1325 (5893)2.46 2004 (8913) -0.615 Traverse, XE 486 (2162)213 (949)2.28 323 (1436)0.664 BiN me UNIRAC e C UNIRAC8 1 SoLAAM6O*Ted}inidal Dhtashe*E emel S 01 ·*c:Et 3.r=Qh,tt-.=, •.91=X I./4/, 4-4 5/40'J-2*- /.4.r'.#z·l' - *'2-· 14:0*4>S :agr'·ti / 9 .H.4:14<..ir.g, 216*/*0 5*' ·CR'th'I .•//,a/k.kiw/ i-A H Ill 1 dROUP SolarMount Beams, Part No. 310132C, 310132C-B, 310168C, 310168C-B, 310168D 310208C, 31020.BC-B, 310240C, 310240C-B, 3102400, 410144M, 410168M, 410204IVI, 41 0240IV] Properties U nits SolarMount SolarMount HD Bearn Height in 2.5 3.0 Approximate Weight (per line'ar ft) pif 0.811 1.271 Total Cross Sectional Area irf 0.676 1.059 Section Modulus (X-Axis) ire 0.353 0.898 Section Modulus (Y-Axis) in3 0.113 0.221 Moment of Inertia (X-Axis) int 0.464 1.450 Moment of Inertia (Y-Axis) ir,4 0.044 0.267 Radius of Gyration (X-Axis) in 0.289 1.170 Radius of Gyration (Y-Axis) in 0.254 0.502 »di; ' · A·.0·'· 'N . ! ' r ; 4, 4.D .1,1/ : 10..:*w 13: 4;111' .aw f 6'.,i:p.y i C··F f ' 0-. d€.:. t ft'0k:12'».,J®>33%-'ir ·€, b. 9,1 SLOT FOR T-BOLT OR 44" HEX HEAD SCREW 2X SLOT FOR n BOTTOM CLIP SLOT FOR T-BOLT OR 1 1%„HEX HEAD SCREW SLOT FOR n glL- 2.500 BOTrOM CLIP \tll- 1.728 - 8 Y- T Moo 1.316 .0 4 SLOT FOR - 6" HEX BOLT 001 1 SLOT FOR - 3" HEX BOLT p 1.385 .387 -- -1 9 11 V Y Y A A 1-- 1.207 -4 1.875 -- X BX SolarMount Beam SolarMount HD Beam Dimensions specified in inches unless noted i)·#23%;473·'91?93>''81%.:··*,t:,i·71 -,?1'93'9· t.„.'Aje':.L.944(11 A....·,?C ·A,th.. - ·:- .., . .p , ,i.,4-04%1·<·fg. t®,if 1-3.j..·4294:41-1.I-:91--3 65:.:-:=S,+2.,;Ffitff; 9.44 rittit 94 2%8 ZON·iFAN / 11 llc 6tb-_.,-we create smart g 3 5-4··-5., i - I h.7.7,·13;<'520„?3*:¥e4'4441=..-i:- -·P·844*%«*4».+Ou_.7.4 /-:--- :1044.- .:4 - --,-1 1 -,11 I-210+c® St-nartMeter97*.:t SmartSyhch's residential smart metering solution features a communications module that 1 is integrated into the GE I-2 10+c electricity meter. The 1-210+c SmartMeter communicates 1! over an existing cellular network with the SmartSynch Ifansaction Management Systeml-M t'2:22¥2#.p:.Fi; (TMS) or other C 1 2.21 head-end system (such as MV-90),and complies with A NSI C12.19. .wm" . ·,4, protocols for data storage and transmission. \101*07 The I-21;0+c SmartMeter is a single-phase electronic watt-hour meter for use in residential and light commercial service locations. The I-210+c's key features include Time of Use, Demand and Load Profile, Remote Connect/Disconnect, and Cl 2.22/ C 12.21 compatibilit9. The 1-210+c SmariMeter also includes an optional ZigBee® wireless component for in-premise communications and an optional Badger ORION® wireless component for gas and water reads. Functions & Features 9. eSmor}Synch, Inc. 4400 Old Conton Road. Jackson. Mississippi 39211 1-888-362- 1780 www.smortsynch.isom Wireless Communications . GRRS • ZigBee® • Badger ORION® Advanced Metaring Functionality a Remote Disconnect/Reconnect • Flexible Two-Way Data Retrieval • Scheduled & On-Demand Reads • Interval Reads (5,15,30, 60 minutes) • Real-Time Interval Reads • Automated Register, Self-Read & TOU •Demand Resets :• Real-Time Meter Event & Alarm Retrieval •Real-Time Power Outage & Restoration • Service Diagnostics & Tamper Detection • Tilt Detection • Meter Clock Synchronization • SmariMeter Status Display • Automated Meter Registration · Secure & Encrypted Data Transmissions • Bi-Directional Metering • Over-The-Air SmartMeter Module, Firmware Upgrade Supported Meter Forms · Class 20: 3S, 4S • Class 1 00: 1 S • Class 200: 25,12S, 25S · Class 320: 2S • See back page for Supported Forms with Remote Disconnect Hardware Components · Remote Disconnect/Reconnect · Radio Control Module Board; (RCM) • Capaciter Storage Bank (CSB) • GSM/GPRS Modem • ZigBee Transceiver • Badger ORION Receivef e Internal Antenna Operating Ranges Tempetature • Operating: [-40°C, +85°C] • Transmission (GPRS): [-40°C. +85°C] Humidity • 0% to 95% non-condensing Accuracy • Meets ANSI 12.20 for accuracy class 0.5% Regulatory & Industry Specifications • FCC Part 15 Class 8 • ANSI C37.90.1 - 1989: (SWC) • ANSIC12.20 (Class 0.5) - 1998 · PTCRB Ceftified • Nelwork Carrier Certified • Measurement Canada Certified 7. 171...'. ,- . -·f_'_ -i -1' 4 4' A;4 ·Pt,23/'·43€:212'.9'C 4·'24-1 ' --5 '.·:i.Pi·'- . '7»11 3 0229 - 'I '7..2 1-:.-1 'CL 11' /74+JA- '4 - .11'· -'1 **> Hardware Specifications2.1 ' Lii-4 -Snnart f '-- - 11 - - - ,§,4 - .ar. ¥21 Hardware Component -'' Radio Control Module Board (RCM) k..7, Capacitor Storage Bank (CSB) ··,·>' GSM/GPRS Modem 1 i,T ZigBee Transceiver i-fi'·:; Badger ORION Receiver 2'3 Internal Antenna :/Synch'-6 Description 32-bit ARM processor, 256K RAM. 512K flash Supplies peak power fof data transmissions and all functions during power outages - no batteries required GSM modem communicates with head-end using GPRS and SMS services Wireless component for in-premise two-way communications Wireless component for receiving gas and waterfeads Flexible dual frequency GSM antenna for the modem "·-1 Temperature Ranges f i Operating: [-40°C, +85°C] /. 1 Transmission (wireless): [-40°(, +85°C] Support:ed Meter Forms Class 20: 35,4S Class 100: 1 S Class 200: 2S. 12S. 259 Class 320: 2S With Disconnect. Class. 100: 1 S Class 200: 2S, 125, 255 Class 320: 25S 0, 3.9 Humidity Range 9-· 0% to 95% non-condensing Accuracy rt< ' : :.· Meets ANSI 12.20 for accuracy class 0.5% Regulatory & industry,Certitications FCC Part 15 Class B ANSI C37.90.1 - 1989: Surge Withstand Capability [SWC) ANSI C 1 2.20 (Class 0.5) - 1998 PTCRB Certified Measurement Canada,Certified Network Carrier Certified Input/Output Signal or Interface Definition/Values Module Power Input Voltage 120 - 240 VAC Meter Serial Interface 3.3V / Ul compatible asynchronous Integratio.n . The SmartMeter module is a fully integrated, under-the-cover option inside the 1-210+C meter. The I-210+c Smar·IMeter is shipped as one complete unit, ready for field deployment. Version and Compatibility information I-210+c Meter Hardware:Supported meter forms, classes, and types. equipped with battery 1-210+c Meter Firrhware:Latest fully supported SmarIModule:I-210+c GPRS SmartMeter Module SmartSynch TMS:Version 6.0 or higher About SmariSynch: Headquartered in Jackson, Miss.. SmartSynch has been developing successful Smart Grid Inte/ligenee solutions for the utility industry since 2000. The company's clean-tech innovations in the iwo-way delivery of real-lime energy usage data over cellular networks (AT&T, Rogers, etc.), in lieu of private nelwod< build-outs, have to date simplified SmarIMeler deployments for 1 50 major North American utilities, while enabling green-energy initiatives and delivering significantly higher Returns on Resources. Unlike proprietary. closed-architecture solutions, SmariSynch"s Smar[Meters represent future-proof investments in technology. The standards-based IP connectivity enabled in every SmartMeter deployed makes them adaptable and remotely upgradable to support today's sensor and communications needs, as well as tomorrow's opportunities, better thon any alternative. - . ., . ., 1 1,4 1-T--lm--F' - --'-'Eogynclh£*2011.'Siiiarlf/iiahinc.,:iilriclhsresefved.'-- ''1 4- 1 1 1- 1 1 1 -1 - 1 -1 € 1 SCREW: E1276 CAT. NO.: MASS:.052 LBS. · SURFACE AREA: 2.738 IN2 STUFFER SHT: FORM 12 MATERIAL:COPPER, X0C7309 PLATING: SEE CHART MARKING: 0 GBI-408,4-14, CU, DB ® g CELL:ABM TOLERANCES-UNLESS OTHERWISE SPECIFIED 2 PL DEC. 1.015 TRUE C.L t.015 3 PL DEC *.010 ANGLES *1 DRAWN BY: CLH SCALE: 3: 1 DATE: 7/27/2007 SIZE: A REV. DWG. NO. G0977 SHEET 1 OF 1 DESCRIPTION - CORP. 7 1/4-28 UNF - 28 / V.040 MAX X 45° GBL-4DBCat # h H .470 [11.:94] --0.218THRU GBL-4DBT .375*.015 [9.53 *.38] E1276- 1.-11,1 = SCALE 1:11 1.4 1 .213 .190 [5.41][4.84] 111 OPENING MUST-1 SLIP A 0.250 PIN \ 11 1 11 T--7 .825 | [20.96]Ch .185*.005 [4.703:.13]-4-k- 8 -*- 1 / Ill, ;1W - 1,150 . PART NUMBER PLATING MARKING[29.21]' GBL-4DB,4-14, CU, DB @ GG0977A00BBRIGHT DIP G0977A00T EL-TIN GBL-VD.BT,4-14, CU, DB @ G THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS PROPRIETARY TO ILSCO AND MAY NOT BE DISCLOSED WrrHOUT PRIOR WRIITEN'CONSENT .