Loading...
HomeMy WebLinkAbout10181047_2800 N. MAIN #528 - PlanPlanning & Building Agency Building and Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.orq ELECTRICAL SIGN REQUIREMENTS Code references are to the 2010 California Electrical Code (CEC) All signs require Planning Department approval. All electrical signs require electric plancheck and permit. 1. Manufacturer's instructions are required at the time of submittal. C-11: 3-21-2011 2. Submit detailed installation instructions including diagrams to the Building Department for plan review at the time of submittal. Plans must include appropriate items noted by this bulletin. 3. Cash or surety bond in the amount of $200.00 is required at time of issuance for each address. The cash or surety bond will be refunded after all required finals. A building permit is also required - except for open or highlight neon lighting. Installation Requirements: CONTACT FIELD INSPECTOR PRIOR TO SIGN INSTALLATION. (SEE SECTION G OF THIS BULLETIN) 1. Conductors and equipment shall comply with California Electric Code Article 600. 2. All metal parts of a sign shall be bonded in the manner specified in Article 250. Isolated metal parts are permitted to be bonded by using an external green insulated conductor. Equipment grounding & bonding conductors must be sized by 110.26 and protected from physical damage. Minimum size is 14 AWG. CEC 600.7 3. A listed disconnect switch in the power supply primary, shall be installed within sight of sign or have permanently installed means for locking in an "OFF" position. This is also true for a transformer enclosure. CEC 600.6 4. A listed receptacle or an approved termination device shall be used for each neon electrode. To relieve stress at terminations, tubing shall be supported with listed tube supports in an approved manner within six inches of electrode connection. CEC 600.41 & 600.42 5. Every electric sign of any type shall be listed by an approved testing laboratory and shall be installed in conformance with this listing. That includes "1 of x", "2 of x" labeling for each separate unit of a multi-unit sign. CEC 600.3 6. All "can" letters and transformers housings shall have section labels that are readily visible after installation. CEC 600.4 7. Transformers shall be located where accessible and be securely fastened in place. Page 1 of 2 O 0 0 , When not inside the sign, they need a 3 foot high x 3 foot wide x 3 foot deep workspace. Transformers are permitted to be located in attics or canopies provided there is a passageway at least 3 feet high x 2 feet wide with a minimum 12 inch catwalldwalkway from the point of entry. Transformers must be securely fastened and independent of T- bar when above a suspended ceiling. No part of sign mav be fed with flexible cord when located above T-bar ceilings. CEC 600.21(E&F) & 400.8 8. Adequate illumination shall be provided for all working spaces about electrical equipment. This applies to attics and canopies when entry is required to service or inspect the equipment. At least one switch is required at entrance. CEC 110.34 & 600.21 9. Doorway to an attic or canopy space shall be minimum 3 feet by 2 feet wide. CEC 600.21(E) E. Open neon outline or highlight lighting. 1. To be treated as a sign by this department. Howevert Section D-5 & D-6 of this bulletin will not apply. 2. Neon tubing shall be located where not normally exposed to physical damage. Open neon tubing below 9 feet shall be protected from physical damage by an approved shielding method. CEC 600.30 and 1 10.34(E) F. Light-Emitting Diode (LED) Signs 1. Will be treated as a sign by this department. All sign rules in sections A, B, C, D, F, and G will apply as appropriate. 2. LED illumination for signage must be a listed or recognized component. Many LED manufacturers specify particular brands and models of transformers some do not. Manufacturer information to clarify this issue is required on LED sign plans. 3. Unlisted LEDs may not be used in an electrical sign or as permanently installed illumination. 110.3 4. Please have packaging or catalog cut-sheets on hand for inspector to review when LED modules do not bear listing symbols. G. Inspections 1. Contact an Electrical Inspector one (1) workday (minimum) in advance of installation to arrange a site meeting on dav of installation. 2. Call for inspection Monday through Friday, 8:00- 8:30 a.m. at (714) 647-5821. Approved prints and the job card must be on site for inspection. Page 2 of 2 0 13 SIGN COMPONENTS MANUAL (SAM)October 1, 2013 1. These products are only suitable for connection to the provided UL R/C Class 2 DC power source according to the power source's UL conditions of acceptability. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3. These products may be cut to create voids or segments through any portion on the sheet. 4. Suitable for dry and damp locations. 5. These products are required to be enclosed or protected from weather. 6. These products are intended only for factory installation in new signs. Class 2 LED Module, Cat. Nos. 3M™ LED High Efficiency Light Panel 1. These products have been evaluated for use only when connected to a power source that complies with Class 2 or LPS requirements for energy limited power supplies. 2. Suitable for dry and damp locations. 3. These products are required to be enclosed or protected from weather. 4. These products are intended only for factory installation in new signs. 5. Grounding of frame to supply ground is required. Suitability of bonding for grounding connection is to be determined in final application. 6. Suitability of LED panel mounting shall be determined in final application. 7. Suitability of LED power source shall be determined in the final application. Polymeric adhesive systems, Cat Nos. DP-810 and DP-810 Black designated "Scotch-Weld" 1. The use of these adhesive systems shall be employed in applications wherein the limitations specified in Table A are not exceeded. 2. These systems may be used for securement to any combination of surfaces Listed in Table A, provided the use of temperature is no higher than the lowest temperature rating of any element of the combination 3. The materials have been evaluated for adhesive compatibility and stability only. No electrical or flammability tests have been performed on the adhesive by itself. The Engineer must consider the need to investigate the part of other than the properties investigated, in accordance with the applicable UL-end product Standard or requirements outlined in the Standard for Polymeric Materials - Use in Electrical Equipment Evaluations, UL 746C. 4. The suitability for use when exposed to oil, chemicals, refrigerant, soaps, X-rays, ultraviolet light and the like, has not been determined. 5. These systems are suitable for application to smooth flat surfaces. The need for adhesive bond strength test when applied to another surface or configuration shall be determined in the particular end use application. 6. These systems are also suitable where exposed indoors or outdoors to high humidity or occasional exposure to water. The minimum temperature rating is -35°C (-31°F). 7. The adhesive shall be applied in accordance with the manufacturer's instruction. All surfaces shall be clean and dry. The manufacturer's instructions regarding cure time shall be followed. 8. The adhesive bond strength specified in Table A includes a safety factor of four. 9. When considering the use of any adhesive covered by this Report, the strength of the adhesive joint used to position parts shall be capable of withstanding the maximum force that might be applied to the joint in the end application. This is called the bond strength and includes static load as well as wind loading(dynamic load). The minimum square inches of adhesive to use is determined by dividing the maximum load in pounds by the adhesive bond strength specified in Table A. TABLE A Cat. Nos.DP-810, DP-810 Black Thickness: 0.076 mm (0.003 in) Substrate Combination Max. Operating Temp.Adhesive Bond °C (°F)Strength(PSI) Stainless Steel to Stainless Steel 60 1000 Aluminum to Aluminum 60 980 Polycarbonate to Polycarbonate 60 180 Magnesium to Magnesium 60 870 Acrylonitrile Butadiene Styrene to Acrylonitrile 60 310 Butadiene Styrene Cat. Nos.DP-810, DP-810 Black Substrate Combination Stainless Steel to Stainless Steel Aluminum to Aluminum Polycarbonate to Polycarbonate Magnesium to Magnesium Thickness: 0.254 mm (0.010 in) Max. Operating Temp.Adhesive Bond Strength °C (°F)(PS') 60 940 60 900 60 190 60 690 Acrylonitrile Butadiene Styrene to Acrylonitrile 60 430 Butadiene Styrene AA LED SUPPLY CORP E325964 9441 VALLEY BLVD. ROSEMEAD, CA 91770 Class 2 LED modules, Models LS0723*, LS0766*, LS0769x, LS0776*, where that x may be RI G, B or Y indicating LED Color. October 1, 2013 SIGN COMPONENTS MANUAL (SAM) 14 1. These products are only suitable for connection to the output of a UL Listed or R/C Class 2 Power Supply rated ·12VDC. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 requirements. 3. These products are rated per the Table below. When units are connected to a Class 2 circuit, their number is to be limited to draw a total wattage of no greater than the secondary current rating of each Class 2 power supply. Part No.Operating Current per Watts per module Voltage module LS0723x 12Vdc 40mA 0.48W LS0766x 12Vdc 30mA 0.36W 1LS1769x 12Vdc 75mA 0.90W LS0776x 12Vdc 60mA 0.72W 4. These products are suitable for use in dry, damp and wet locations without additional enclosures. Class 2 LED Modules, Model AA-0766EC-XX, where XX can be any alpha characters or blank to represent different light color 1. These products are only suitable for connection to a Class 2 power source rated 12 Volt DC or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited circuit and which is rated greater than 12 V DC. 3. These Class 2 LED modules are each rated as noted in the electrical ratings tables. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at 12 Volts DC or less. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. These products may be secured in place in the end product by any means available. ABC SIGN PRODUCTS E80767 2028 SE FRONTAGE RD FT COLLINS, CO 80525 Lampholder adapter, Type LH. 1. This device is suitable for use in indoor or outdoor extruded aluminum awning frames. 2. This adapter is intended for use only with Listed, single or double contact, recessed lampholders (Cat. No. 530, Kulka) which snap-fit into, and are securely held by, the adapter. The lampholder shall be held securely with or without a lamp in place. 3. This adapter is intended to complete the enclosure housing of insulated live parts only. 4. This device shall be installed in an aluminum extrusion in accordance with the "Installation Instructions" supplied by the manufacturer in the smallest shipping container. -.Sign Face Tensioning System, Model ABC. -1. The suitability of these tensioning systems in combination with any R/C (UYMR2) Flexible Sign Face Material to prevent entrance of water in outdoor sign applications shall be determined in the end product. 2. This product has not be evaluated for use as an electrical enclosure. 3. Tensioning clips shall be spaced as described in the Installation Instructions. 4. When employed in a sign with any frame dimension greater than 6 feet the sign shall be provided with a means to prevent billowing. 5. The mounted assembly of sign face material in these tensioning systems shall comply with the electrical and thermal spacing requirements of UL 48. 6. These clips have been determined to be suitable with any R/C Flexible Sign Face Material of min. 0.020 inches (0.51 mm) thick, suitability for use with a material of lesser thickness shall be determined in the end product. ABLE APPLIED TECHNOLOGIES LTD E329973 BOUNDARY HOUSE BUSINESS CENTER BOSTON MANOR RD LONDON, W7 2QE UNITED KINGDOM Class 2 LED Modules, Models MS-P40XXX-XX Series, where XXX-XX may be any alphanumeric characters. 1. These LED panel of these products are powered by Class 2 power source rated at max. 15 VDC, 5 amps. 2. These products are suitable for use in dry and damp locations. 3. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 4, When provided with a power supply, in the end product the power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 5. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 limits. ACROSENTEC CO LTD E363566 253-9 GOCHUN-DONG UIWANG-SHI , GYEONGGI-DO 437-801 REPUBLIC OF KOREA Class 2 LED Modules, Models ASPCH-@-#-24-$-%-&, ASFCH-@*24-$-%-&, and ASMX-@-A-24-*-!, where @ can be any 2 to 4 alphanumeric code, # can be any 3 to 5 alphanumeric code, $ can be any 2 or 3 alphanumeric code, % can be any 1 to 4 alphanumeric code, & can be any 3 to 9 alphanumeric code, A can be any 3 to 5 alphanumeric code, * can be any 3 to 6 alphanumeric code, ! can be any 2 to 9 alphanumeric code. 1, These products are only suitable for connection to a Class 2 power source rated 27 V DC or less. . ECEIVE1 APR 07 2014 City of Santa Ana naiia=Gi9-EEUKEE---------- :-iliZZJ-/'ll- I.=. 1 -ililitzilil 0. --FOOT LOCKER, INC. -Tl-1 =FFI i Foot lacker MALLKEY-BEAN ZIUIRIZIE'*12 i . .il :F 4- 1 2/.I--+/ U.-'-·-" :.I.- - 4. ' nzy= 44. 7-4g;E=----i * 3.- /95 -/-- .2031 .%/£.= 4 4 2, - -- P-- ize Ur-,g- , 9 . -_.,140.- -·c=t_0 -2-tiflf-4*44.Jels*¢ =7....9, 1 'SVEP ORY N UST OF DRAWINGS- .// 1 Sm=.1 1 1 ./ A . 4 ./. -0 - 89 i 1 Ettlit 1 IN S. A 738 G. 1..... I.....1111/1 D NOTES | SYMBOLS u=: 9. cr..t= -S. 2335 =A=- I /1- ASERE'UU-nONS ==. -Sln**0.-„A,€7: a=of: 44=IST 6*TAAh,KCA€]2703 £54€E. 523 i sro=:c 46579 K.rm. t=7 'E"_ 11 1 COVER SMEET -0 0 ET 4 LANDLORD 'OTES > I .-a.£a -. Gl.0 e· ' :2000*44 ,02 .hl IL 952. -,1443 \9 ft J 04. 0 0 /2*9..kr\90. 4 / O americanneon@sbeglobal.net - attnet Mail Page 1 of 1 Search Mail Search WelZ. Hi, Dennis INBOX CONTACTS CALENDAR EnvironmentaILights. Compose Delete Move Spam Actions . 1%00 N. MAL E>Av,U- Avof A CLA 9 13 Of https://us-mg205.mail.yahoo.com/neo/launch?.partner=sbc&.rand=dk7i95r1 i273o 3/12/2014 ,4Z. DPJ SIGNS 1 1 ./ l li M!.M Foot locker Lexan Back .. White LED 1.ette, Paiedi R. Red w/ Red Ret*rts 1-1- 5 1 -17 11 92Lin mace 2300 21 Uahn St- Sam' Ana. CA 9005 E==1 1 De*ler St &Ret L / i 11 11*44 - 1 E-El -- t. $-0.-0-39.0 on .2/ r 2-07-14 /' Itte: Ul L.ch ./&%**rE -oi==./. 0, ac73 Ccilact Re Naine: 18sant,465793 Tr 31/2- 42 3/4- *. i i ip *er I 1 +P Lockerl LJ Ah:mi,== Welded - r / Stencil Cut am--3 15 Face Pated Kn Ence - 13 Custcme, Sign /Date: - P,ims,y Electric toBUMing by G.C Landord SigVDate. 0=„mect SItd, Plocklekn Ap,ir),91 Date uu Itwer Supply -/ .hmction Box 4 Mipe == 820 St,ul: Bscia 1 --061.* K Fri t.97; 1 -Lk' 20. Sect= Sign Drawing Review A as Noted 0 Resubmit 1 1 u-Ikidsfootlocker.com ITa ZA,» a.. M.0 41- 1/5 % . ELECTRICAL NOT TO SCALE AMPS -1- _VOLTS _29 ¢i »4 574'2-10-14 L 1 18" 1 13' •44 ./ 1 1 1 9-]9-)14 1€00 10131 09/7 )20155 6=6 -y53:A ent sigonoroed or the breaker(s) mu.e cuit ositionA\000 6, Rectfor 0 ted 0 0% 91\ de¢\00 0\0*0lockabl attic or aboverea#A,vid\131 a ladder or he \0't.Anx)..,c>s suf34 fro-0-Ass3g City of Santa Ana. CBC & CEC 2013 Minimum (4) screws per letter, maximum 24" on center, z penetration, #10 sheet metal screws, & (2) 44" drain holes per letter *Iding Ageno,& 80\ \-4 of Santa Ana Planning ELECTRICAL j PLAN APPROVAL ' This set of plans and speclficalions must be kept on the job at all times and It Is unlawful to make any changes or alterations on same without written per- mission from the Department of Building Safety City of Santa Arla. The approval of this plan and specifications SHALL NOT hs held to permit nor be an approval of the. 1 E=*65.,viotat:·a, or any provisions of ANY City Ordinance or State Law.,r Approle b,9 0 1 ·L-b. Er•62 l-1.L€=19-1 \ 41TY OF SANTA ANA , DEPARTMENT OF BUILDING SAFETY i . 1, PERMIT TYPE:BLDELEPLBG MECH -GFUdiNG PERMIT#10\'AOLAFT / OCC. GROUP AX)\669) L. 6 CONSTR. TYPE.. CODE EDITION 90 13 FLOOD ZONE FLOOD ZONE CERTIF. REQ'D YES N MICROFILM YES RADIANT BARRIER @ ROOF YES RESIDENTIAL DEV. FEE YEEK SCHOOL DISTRICT YE*Q NO 0 1 1 any 9