Loading...
HomeMy WebLinkAbout2422 W Marty Ln Unit 2 & 3 - Plan(N) 4 " A B S S E W E R L I N E , MIN . 2 % S L O P E (E ) 4 " S E W E R L I N E TO S T R E E T ( V . I . F . ) (N) WATER LINE: 1" COPPER TYPE "L" OR PVC PIPE, MIN. 18" BELOW GROUND (N) ADU 799 SF 2 BED/2 BATH (N) JADU 431 SF 1 BED/1 BATH (E) WATER METER (E) 100A PANEL CHANGED TO 100A SUB-PANEL (E) GAS METER (E) POWER POLE PROPERTY LINE - 75.00' PR O P E R T Y L I N E - 8 9 . 1 9 ' PR O P E R T Y L I N E - 1 0 8 . 2 1 ' 6'H METAL GATE (E) 6'H WOODEN FENCE (E ) 6 ' H B L O C K W A L L 9'-1"27'-4"4'-0" 19'-7" 30'-3" 7'-0" 35'-5" 25'-0" TO CENTERLINE ℄ W MARTY LN 25'-0" 36'-3" 7'-0" (E) 1-STORY MAIN UNIT 1,248 SF 4 BED/2 BATH 4: 1 2 4: 1 2 (E) GARAGE 353 SF 4:12 4:12 (E) PORCH 23 SF 18" (TYP.) 5'-0" (E) DRIVEWAY AND IMPERVIOUS SURFACE 20'-11"9'-1"18'-0"3'-6"4'-6" 34'-7" 18'-8"17'-3"4'-0" 5'-0"6'-0" 3'-0" 10'-0" 3'-0" 17'-4" 4: 1 2 FRONT YARD LANDSCAPING (PER S.A.M.C. SEC. 41-240) 12" (TYP. @ JADU) FI R E S E P A R A T I O N LI N E PU B L I C U T I L I T Y EA S E M E N T ( 5 ' & 6 ' ) 14 SD-2 1-HR RATED OVERHANG AND WALL 14 SD-2 ADDRESS NUMBER (N ) 2 - G A N G P A N E L , 10 0 A E A C H F O R JA D U A N D M A I N U N I T (N ) A D U 20 0 A P A N E L (N) 1" WATER METER (N) JADU 100A SUB-PANEL 3'-0" (N ) A C (N ) A C 12" (TYP. @ ADU) 3'-0" 2: 1 2 2: 1 2 4:124:12 4:124:12 4: 1 2 4: 1 2 4: 1 2 2 A3 1 A3 14 SD-2 1-HR RATED OVERHANG AND WALL 1-HR RATED OVERHANG AND WALL 14 SD-2 1-HR RATED OVERHANG AND WALL 2'-0" 2'-0" 12" OVERHANG TO BE TRIM TO BE 12" FOR FIRE SEPARATION NEW WATER METER AND SERVICE WILL BE APPROVED UNDER A SEPARATE PERMIT ATTIC VENTILATION CALCULATION TOTAL ATTIC VENTILATION AREA SHALL NOT BE LESS THAN 1/150 OF THE ATTIC SPACE AREA. 1. ADU: ATTIC SPACE = 799 SF ATTIC VENTS REQUIRED = 799/150 = 5.33 SF 2. JADU: ATTIC SPACE = 431 SF ATTIC VENTS REQUIRED = 431/150 = 2.9 SF ===> PROVIDE 6 VENTS ON THE ADU AND 3 VENTS ON THE JADU, OHAGINTM 14" DIAMETER ROOF VENTS (1.07 SF EACH), AS INDICATED ON ROOF PLAN HEREON ===> ALSO PROVIDE 3 VENTS ON THE MAIN HOUSE, OHAGINTM 14" DIAMETER ROOF VENTS (1.07 SF EACH), TO ACCOUNT FOR THE VENT LOSS FROM THE NEW BUILDING ATTACHMENT PROJECT INFORMATION OWNER:TT STARS LLC C/O:TOAN TRAN TEL.:(714) 548 1711 ADD.:MAIN:2422 W MARTY LN JADU: 2422 W MARTY LN, UNIT 2 ADU: 2422 W MARTY LN, UNIT 3 SANTA ANA, CA 92706 (E) MAIN UNIT = 1,248 SF (E) GARAGE = 353 SF (E) PORCH = 23 SF (N) JADU = 431 SF (N) ADU = 799 SF (EXEMPT FROM LOT COVERAGE) LOT COVERAGE = 1,248 + 353 + 431 = 2,032 SF LIVING AREA = 1,248 + 431 + 799 = 2,478 SF LOT SIZE = 7,405 SF % COVERAGE = 2,032/7,405 = 27.4% < 35.0% APN = 399-141-14 ZONE = R1/U OCCUPANCY = MAIN UNIT: R-3/U, ADU: R-3 FLOOD ZONE = X NUMBER OF STORY = 1 TYPE OF CONSTRUCTION = VB (E) UNIT AND ADU FIRE SPRINKLER = NOT EQUIPPED APPLICABLE BUILDING STANDARDS 1. 2022 CALIFORNIA MECHANICAL CODE (CMC) 2. 2022 CALIFORNIA BUILDING CODE (CBC) 3. 2022 CALIFORNIA RESIDENTIAL CODE (CRC) 4. 2022 CALIFORNIA PLUMBING CODE (CPC) 5. 2022 CALIFORNIA ELECTRICAL CODE (CEC) 6. 2022 CALIF. ENERGY EFFICIENCY STANDARD 7. 2022 CALIF. GREEN BUILDING STANDARDS 8. CITY OF SANTA ANA ORDINANCES DRAWING INDEX A1 SITE/ROOF PLAN - GENERAL NOTES A2 ELEVATION - (E) FLOOR PLAN A3 (N) FLOOR PLAN A4 BUILDING SECTION - FIRE RATED LISTING LOAD CALCULATIONS DR-1 DRAINAGE PLAN SN-1 STRUCTURAL GENERAL NOTES S1-2 FOUNDATION PLAN - FRAMING PLAN SD1-2 STRUCTURAL DETAILS T1-3 TITLE 24 PLAN T4-5 GREEN BUILDING STANDARDS CODE SCOPE OF WORK 1. BUILD NEW ATTACHED 799 SF ADU (2 BEDROOM - 2 BATHROOM) 2. BUILD NEW ATTACHED 431 SF JADU (1 BEDROOM - 1 BATHROOM) 3. RELOCATE EXISTING 100A PANEL TO ADU CONSTRUCTION NOTES 1. CONSTRUCTION WORK HOURS ARE 7AM - 7PM, M-F; 9AM - 7PM, SATURDAY; NO SUNDAY OR LEGAL HOLIDAYS. 2. THERE SHALL BE NO TRENCHES OR EXCAVATIONS 5' OR MORE IN DEPTH INTO WHICH A PERSON IS REQUIRED TO DESCEND, OR OBTAIN PERMIT FROM STATE OF CA, DIVISION OF OCCUPATIONAL SAFETY AND HEALTH (CAL/OSHA). THIS PERMIT AND ANY OTHER SAFETY PERMIT SHALL BE OBTAINED PRIOR TO COMMENCE OF ANY WORK. VICINITY MAP ADU PARKING EXEMPTION NOTE PROPOSED ADU IS LOCATED WITHIN ONE-HALF MILE TO OCTA ROUTE 47 ALONG FAIRVIEW ST. AT DOWNIE PL., PURSUANT TO ASSEMBLY BILL 68, NO PARKING IS REQUIRED FOR THE ADU. GENERAL NOTES 1. ALL WORK PERFORMED SHALL COMPLY WITH THESE GENERAL NOTES (UNLESS NOTED OTHERWISE ON THESE PLANS AND SPECIFICATIONS) AND ALL THE FOLLOWING NOTES, DRAWINGS AND SPECIFICATIONS. GENERAL CONTRACTOR SHALL COORDINATE THE INTENT OF GENERAL NOTES WITH MECHANICAL, ELECTRICAL, AND PLUMBING TRADES. 2. THE GENERAL CONTRACTOR OBTAINS AND PAYS FOR ALL REQUIRED PERMITS AND ARRANGES FOR ALL REQUIRED INSPECTIONS. 3. ALL WORK SHALL COMPLY WITH LATEST EDITION OF BUILDING CODES AS ADOPTED BY THE CITY OF SANTA ANA AND ALL OTHER APPLICABLE REGULATIONS. 4. DO NOT SCALE DRAWINGS. CONTRACTOR SHALL VERIFY ALL SITES CONDITIONS, DIMENSIONS AND ELEVATION BEFORE STARTING THE WORK, AND NOTIFY THE DESIGNER OF ANY DISCREPANCY, IN WRITING, PRIOR TO PROCEEDING. 5. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN HEREON OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSES OF REPAIR OR REPLACEMENT IN CONJUNCTION WITH THE PROSECUTION OF SUCH WORK. 6. THE CONTRACTOR SHALL DETERMINE THE LOCATION OF THE UTILITY SERVICES IN THE AREA TO BE EXCAVATED PRIOR TO THE EXCAVATION. 7. THE DISCHARGE OF POLLUTANTS TO ANY STORM DRAINAGE SYSTEM IS PROHIBITED. NO SOLID WASTE, PETROLEUM BYPRODUCTS, SOIL PARTICULATE, CONSTRUCTION WASTE MATERIALS, OR WASTEWATER GENERATED ON CONSTRUCTION SITE OR BY THE CONSTRUCTION ACTIVITIES SHALL BE PLACED, CONVEYED OR DISCHARGED INTO THE STREET, GUTTER OR STORM DRAIN SYSTEM. 8. ALL NEW ROOF MATERIALS, STUCCO AND WINDOWS SHALL MATCH EXISTING COLOR AND STYLE. EMERGENCY EGRESS NOTES 1. MIN. SET CLEAR OPENING OF 5.7 SQUARE FEET. 2. MIN. 5 SQUARE FEET FOR GRADE-FLOOR OPENINGS 3. MIN. SET CLEAR HEIGHT OF 24 INCHES. 4. WINDOW TO BOTTOM OF CLEAR OPENING SHALL BE NO MORE THAN 44 INCHES. STUCCO NOTES 1. A CORROSION RESISTANT WEEP SCREED 2" BELOW PLATE, 6" (2" FOR CONCRETE WALKWAY) ABOVE GRADE THAT ALLOWS TRAPPED WATER TO DRAIN TO THE EXTERIOR OF THE BUILDING IS REQUIRED BELOW THE STUCCO AT THE FOUNDATION PLATE LINE. 2. 7/8" MIN. THICK THREE-COAT APPLICATION (SCRATCH, BROWN AND FINISH) OVER SELF-FURRING GALVANIZED WIRE LATH OVER GRADE D BUILDING PAPER AND WIRE BACKING. 3. EXTERIOR LATH: PROVIDE 2 LAYERS OF GRADE D PAPER OVER SHEATHING OR WOOD STUDS. SETBACK AND PROPERTY LINE NOTE THE OWNER/CONTRACTOR SHALL CONSULT WITH A LAND SURVEYOR TO DETERMINE IF A LOT/BOUNDARY SURVEY IS NEEDED TO VERIFY SETBACKS OF EXISTING AND PROPOSED STRUCTURES WITH RESPECT TO PROPERTY LINES. IN THE EVENT THERE IS DISCREPANCY BETWEEN PROPOSAL AND FIELD MEASUREMENTS OF SETBACK, THE DESIGNER SHALL BE NOTIFIED; AND REVISION SHALL BE SUBMITTED FOR CITY APPROVAL. ELECTRICAL METER RELOCATION NOTE THE CONTRACTOR SHALL CONTACT SOUTHERN CALIFORNIA EDISON (SCE) @ 800-655-4555 TO OBTAIN A NEW METER SPOT APPROVAL AND INSTALLATION INSTRUCTIONS PRIOR TO INSTALLING THE NEW METER SERVICE PANEL. LOCATION AND AMPERAGE OF NEW METER IN THIS PLAN ARE ONLY PROPOSAL AND SUBJECT TO SCE FINAL APPROVAL. SI T E P L A N RO O F P L A N GE N E R A L N O T E S OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U SHEET A1 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 LANDSCAPING LEGEND GRASS OR ACCEPTABLE DRY CLIMATE GROUND COVER POP-UP SPRINKLER NEW 5 GAL. JUNIPER BUSH (TYP. 6) NEW 1 GAL. ENCORE AZALEA (TYP. 10) FRUIT TREES ( VARIETY - MAX. 20' APART) NEW 24" BOX KING PALM OR SIMILAR, TREE SHALL BE DOUBLE-STAKED BUILDING NOTES 1. ALL CONCEALED WORK INSTALLED WITHOUT PERMITS MUST BE EXPOSED FOR INSPECTION TO THE SATISFACTION OF THE BUILDING INSPECTOR. THIS INCLUDES METHODS OF ATTACHMENT AND ALL FOOTINGS, STRUCTURAL MEMBERS, MECHANICAL, ELECTRICAL, PLUMBING AND INSULATION. 2. MECHANICAL, ELECTRICAL AND PLUMBING ARE NOT PART OF THIS PLAN REVIEW AND APPROVAL. MEP ARE SUBJECT TO BUILDING FIELD INSPECTION. FRONT YARD NOTES 1.FRONT YARD LANDSCAPING SHALL COMPLY WITH S.A.M.C. SEC. 41-240. 2.LANDSCAPING AREAS SHALL BE DESIGNED WITH AN AUTOMATIC IRRIGATION SYSTEM WITH POP-UP SPRINKLERS. DRIP, BUBBLER OR OTHER LOW GALLONAGE SYSTEMS MAY BE USED IN BUFFER AREAS AND NARROW STRIPS. 3.FRONT YARD LANDSCAPING, IF NOT PRESENT, SHALL BE RESTORED WITH LIVE VEGETATION (GRASS OR ACCEPTABLE DRY CLIMATE GROUND COVER). 4.FENCE IN FRONT YARD SHALL COMPLY WITH S.A.M.C. SEC. 41-610 AND SHALL NOT EXCEED 3' IN HEIGHT. (N) SITE/ROOF PLAN SCALE: 1/8" = 1'-0" ADU SF / SFD SF RATIO ADU SF / SFD SF RATIO = 799/1,248 = 0.64 THE ADU SF / SFD SF RATIO IS FOR PARK & REC. FEE PURPOSE ONLY. THE APPLICANT IS RESPONSIBLE FOR THE GIVEN "SFR SF" OF THE EXISTING PRIMARY RESIDENCE. BUILDING SAFETY STAFF ARE NOT RESPONSIBLE FOR THE ACCURACY OF THE GIVEN "SFR SF" OF THE EXISTING RESIDENCE. BUILDING DEPARTMENT NOTE FOR NEW BUILDINGS AND ADDITIONS, ALTERATIONS, AND REPAIRS WITHIN ANY TWELVE-MONTH PERIOD EXCEED FIFTY (50%) PERCENT OF THE VALUE OF ANY EXISTING BUILDING OR STRUCTURE, EACH BUILDING OR STRUCTURE SHALL BE MADE TO CONFORM TO THE REQUIREMENTS FOR NEW BUILDINGS OR STRUCTURES AND COMPLY WITH THE BUILDING SECURITY REGULATIONS. SANTA ANA MUNICIPAL CODE CHAPTER 8, DIVISION 3. PLANNING NOTE THE PROPERTY OWNER SHALL BE RESPONSIBLE FOR CONFIRMING ALL EXISTING UTILITY EASEMENTS AND/OR CLEARANCE ON-SITE THAT MAY AFFECT THE PROJECT. HERS SPECIAL FEATURES • INSULATION BELOW ROOF DECK • NORTHWEST ENERGY EFFICIENCY ALLIANCE (NEEA) RATED HEAT PUMP WATER HEATER; SPECIFIC BRAND/MODEL, OR EQUIVALENT, MUST BE INSTALLED HERS INSPECTION FEATURES • QUALITY INSULATION INSTALLATION (QII) • INDOOR AIR QUALITY VENTILATION • VERIFIED HEAT PUMP RATED HEATING CAPACITY (E) 100A PANEL CHANGED TO 100A SUB-PANEL WH BEDROOM 1BEDROOM 2 BEDROOM 3 BEDROOM 4 BATH 1 KITCHEN DINING AREA LIVING AREA GARAGE ATTIC ACCESS 36"48" VINYL WINDOW36"48" VINYL WINDOW 36"48" VINYL WINDOW 36"48" VINYL WINDOW 36"48" VINYL WINDOW 36"12" VINYL WINDOW 30"48" VINYL WINDOW 36"48" VINYL WINDOW 36"48" VINYL WINDOW 36"48" VINYL WINDOW 36"48" VINYL WINDOW 36 " 3 6 " V I N Y L WI N D O W 36 " 3 6 " V I N Y L WI N D O W 36 " 3 6 " V I N Y L W I N D O W 30 " 4 8 " V I N Y L WI N D O W 15'7' GARAGE DOOR W/ AUTO. OPENER PORCH 19'-7" 12'-5" 3'-6" 4'-6" 9'-11" 12'-8"21'-9"10'-4" 49'-10" 30'-3" 19'-7" 18'-8"3'-6"18'-0" 44'-8" 4'-6" WALL HEATER B A T H 2 OHAGINTM ATTIC VENTS 14" DIA., 1.07 SF (TYP.) COOL ROOF REQUIRED, CRRC # 0676-0139, GAFTM CLASS A ASPHALT SHINGLES (ICC# ESR-1475) W/ DOUBLE LAYERS OF 30 LB. UNDERLAYMENT ON RADIANT BARRIER SHEATHING WALL OPENING CALCULATION: WALL AREA = 61.25'x8' = 490 SF WALL OPENING = 3'x3' + 4'x4' + 5'x4' + 3'x6.7' = 65 SF % OPENING = 65/490 = 13.3% < 25% (E) LIGHT BROWN COMPOSITION SHINGLE ROOF 12 4 2422 2422-#2 NEW FASCIA & ROOF TO MATCH EXISTING HOUSE IN COLOR AND SIZE 2422-#3 8'-0" CEILING HEIGHT 8" MIN. STUCCO TO MATCH EXISTING UNIT IN COLOR & TEXTURE 5'W x 3'D EXTERIOR LANDING (3" DROP FROM DOOR THRESHOLD, 2% SLOPE) 5'W x 3'D EXTERIOR LANDING (3" DROP FROM DOOR THRESHOLD, 2% SLOPE) 2'-8" 5'-8" 2'-8" (N) DOUBLE-ROLLED TORCH-DOWN OR BUILT-UP ROOF 12 4 12 4 12 4 FINISH FLOOR FINISH FLOOR FINISH FLOOR FINISH FLOOR FINISH GRADE FINISH GRADE 18" 12" 12" 18" 12'-2" 13'-8" 12'-1" FINISH GRADE FINISH GRADE WALL OPENING CALCULATION: WALL AREA = 44.7'x8' = 358 SF WALL OPENING = 6(3'x4') + 2.5'x6.7' = 88.7 SF % OPENING = 88.7/358 = 24.8% < 25% 44'-8" - (E) UNIT 17'-3" - (N) JADU 34'-7" - (N) ADU 55'-10" - (E) UNIT 27'-4" - (E) UNIT 10'-0" - (N) ADU 4'-7"61'-3" - (N) JADU AND ADU EL E C . PA N E L EL E C . PA N E L AC AC EL E C . PA N E L EL E V A T I O N (E ) F L O O R P L A N SHEET A2 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 (E) FLOOR PLAN SCALE: 3/16" = 1'-0" OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U SOUTH ELEVATION SCALE: 1/8" = 1'-0" NORTH ELEVATION SCALE: 1/8" = 1'-0" EAST ELEVATION SCALE: 1/8" = 1'-0" WEST ELEVATION SCALE: 1/8" = 1'-0" WINDOW NOTE NEW WINDOWS SHALL BE WHITE VINYL WITH NAILING FLANGE, FRAME FINISH FLUSHED WITH STUCCO. WINDOWS AND TRIMS SHALL MATCH BETWEEN (E) UNIT AND (N) ADU. ADDRESS NUMBER NOTE 1. THE ADDRESS NUMBER SHALL BE ARABIC NUMBERS OR ALPHABETICAL LETTERS, NUMBERS SHALL NOT BE SPELLED OUT. 2. EACH CHARACTER SHALL BE NOT LESS THAN 4" IN HEIGHT WITH A STROKE WIDTH OF NOT LESS THAN 0.5". ELEVATION NOTE ALL EXTERIOR FINISHES TO MATCH BETWEEN EXISTING MAIN HOUSE AND NEW ADU, INCLUDING TRIMS, COLORS, ROOFS, WINDOWS, DOORS, SIDING, ETC. S-S JADU 100A SUB-PANEL HOOD VENT THROUGH ROOF, 400 CFM MIN., INSTALLED PER MANU. SPECS. HOOD SHALL COMPLY W/ ASHRAE 62.2(C) LUMINAIRES LOCATED ABOVE BATHTUB OR SHOWER SHALL BE LISTED FOR WET LOCATIONS SMOKE DETECTOR IN LIVING ROOM (WITHIN 20' FROM THE COOK TOP) SHALL BE IONIZED OR PHOTOELECTRIC TYPE WALLS AT SHOWERS SHALL BE TILE/CEMENT PLASTER, MINIMUM 72" ABOVE FLOOR. GRAB BAR REINFORCEMENT, MIN. 2x8 LUMBER, 32"-39.25" ABOVE F.F. (TYP.) SD 40 AMP.ELEC. RANGE TEMP. GLASS EATON 2-POLE SPD OR APPROVED COMPATIBLE (N) 100A SUB-PANEL WH (E) BEDROOM 1 (E) BEDROOM 2 (E) BEDROOM 3 (E) BEDROOM 4 ( E ) B A T H 2 (E) BATH 1 (E) KITCHEN (E) DINING AREA (E) LIVING AREA (E) GARAGE ATTIC ACCESS UL 2034/2075 RATED @ (E) HOUSE CO SD SD SD SD SD UL 217 RATED @ (E) HOUSE (TYP.) SD (E) 36"48" VINYL WINDOW (E) 36"48" VINYL WINDOW (E) 36"48" VINYL WINDOW (E) 36"48" VINYL WINDOW (E) 36"48" VINYL WINDOW (E) 36"12" VINYL WINDOW (E) 30"48" VINYL WINDOW (E) 36"48" VINYL WINDOW (E) 36"48" VINYL WINDOW (E) 36"48" VINYL WINDOW (E) 36"48" VINYL WINDOW ( E ) 3 6 " 3 6 " V I N Y L WI N D O W ( E ) 3 6 " 3 6 " V I N Y L WI N D O W ( E ) 3 6 " 3 6 " V I N Y L W I N D O W ( E ) 3 0 " 4 8 " V I N Y L WI N D O W (E) 15'7' GARAGE DOOR W/ AUTO. OPENER (E) PORCH 21'-9" 49'-10" 30'-3" 19'-7" 18'-8"3'-6"18'-0" 61'-11" 4'-6" WALL HEATER 10'-0" (N) LIVING AREA (N ) B A T H 2 STACKED W/D 2' - 2 " STACKED W/D 30" 1,024 SI 1'-6" 1'-6" 1'-7" (N) BEDROOM 1 (N) BEDROOM 2 (N) BEDROOM (N) LIVING AREA WH (N) KITCHEN (N ) K I T C H E N (N) BATH 1 (N) BATH 15'-0" 11'-3" 2'-6" 5'-7" 16'-11" 17'-3" 9'-4" 9'-2" 7'-0" 61'-3" 2'-6"11'-11" 17'-4" 10'-0" 34'-7" 1' - 6 " 5'-4" 3'-7" 14'-10" (N ) A C CO N D E N S E R O N 3" C O N C R E T E P A D (N ) A C CO N D E N S E R O N 3" C O N C R E T E P A D (N ) 2 - G A N G PA N E L , 1 0 0 A EA C H F O R J A D U AN D M A I N U N I T (N ) A D U 22 5 A R A T E D 20 0 A P A N E L 3" EATON 2-POLE SPD OR APPROVED COMPATIBLE EATON 2-POLE SPD OR APPROVED COMPATIBLE ATTIC ACCESS 22" x 30" ATTIC ACCESS 22" x 30" 3'-0" 3"5'-0" 5'-0" 3'-0" EGRESS WINDOW EGRESS WINDOW EGRESS WINDOW 30" 1,024 SI 30" 1,024 SI 3'-0" 6'-0" 1 A3 2 A3 1 A3 1" GAP BETWEEN 2x4 LUMBER 1" GAP BETWEEN 2x4 LUMBER 40 AMP. 30 AMP. 50 AMP. 30 AMP. $$ S-S DU C T L E S S M I N I SP L I T A C DUCTLESS MINI SPLIT AC DU C T L E S S M I N I SP L I T A C DU C T L E S S M I N I SP L I T A C DU C T L E S S M I N I SP L I T A C SD SD CO SD CO SD SD MAX. 48" MEASURED FROM TOP, MIN. 15" MEASURED FROM BOTTOM OF BOX ABOVE F.F. (TYP.) AFCI (TYP.) AFCI (TYP.) AFCI (TYP.) ELEC. DRYER ELEC. DRYER ELEC. RANGE WR-GFCI WR-GFCI WR-GFCI AFCI (TYP.) GFCI (TYP.) 2'-7" $VS$ 5'-3" 7'-0" $VS$ $D $D $ $4D $3 $$4 $4 $3 $VS $ $D AFCI (TYP.) AFCI (TYP.) 30 AMP. 30 AMP. 50 AMP. $$ AFCI (TYP.) GFCI (TYP.) $ $3 $3 $$3D$3 2'-6" 6'-3" HOOD VENT THROUGH ROOF, 400 CFM MIN., INSTALLED PER MANU. SPECS. HOOD SHALL COMPLY W/ ASHRAE 62.2(C) WH NEEA HPWH NEEA HPWH DOOR SHALL BE TEMPERED AND SWING INWARD (TYP.) NEW WALL, 2x4 STUDS @ 16" O.C. U.N.O. EXISTING STUD WALL WALL LEGEND CARBON MONOXIDE AND SMOKE DETECTOR NOTES SMOKE DETECTOR SHALL BE PROVIDED IN EACH SLEEPING ROOM AND AREA GIVING ACCESS TO THE SLEEPING ROOMS 1. NEW CONSTRUCTION: CO AND SMOKE DETECTORS SHALL RECEIVE THEIR PRIMARY POWER FROM BUILDING WIRING WITH BATTERY BACKUP. 2. EXISTING MAIN HOUSE: BATTERY POWERED UL 2034/2075 RATED CARBON MONOXIDE ALARM AND UL 217 RATED SMOKE ALARMS SHALL BE INSTALLED IN MARKED LOCATIONS. ELECTRICAL NOTES 1.PROVIDE ONE 20 AMP. CIRCUIT FOR BATHROOM OUTLETS. SUCH CIRCUIT SHALL HAVE NO OTHER OUTLETS. 2.PROVIDE 2 DEDICATED GENERAL APPLIANCE CIRCUITS TO THE KITCHEN AREA. 3.ALL INSTALLED LUMINAIRES MUST BE HIGH EFFICACY IN ACCORDANCE WITH TABLE 150.0-A. 4.ALL RECEPTACLES IN BATHROOMS SHALL BE G.F.C.I. 5.SERVICE PANEL/METER UPGRADE OR NEW: OBTAIN LOCATION APPROVAL FROM THE ELECTRICAL PROVIDER. 6.ALL BRANCH CIRCUITS SUPPLYING RECEPTACLE OUTLETS IN KITCHENS, BEDROOMS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, DENS, SUNROOMS, HALLWAYS, CLOSETS AND SIMILAR ROOMS/AREAS SHALL BE PROTECTED BY AN ARC-FAULT CIRCUIT INTERRUPTER (AFCI). 7.NON-HIGH EFFICACY LUMINAIRES SHALL BE SWITCHED ON A SEPARATE CIRCUIT FROM HIGH EFFICACY LUMINAIRES. 8.ELECTRICAL OUTLET BOXES IN OPPOSITE FACES OF SEPARATION WALLS SHALL BE SEPARATED HORIZONTALLY BY 24" . BACK AND SIDES OF BOXES TO BE SEALED WITH 1/8" RESILIENT SEALANT AND BACKED WITH 2" MIN. MINERAL FIBER INSULATION. 9.ALL RECEPTACLE OUTLETS SHALL BE LISTED AS TAMPER-RESISTANT OUTLETS. 10.ALL OUTDOOR LIGHTING MOUNTED TO A RESIDENTIAL BUILDING SHALL BE HIGH EFFICACY LIGHTING OR CONTROLLED BY A PHOTOCELL AND MOTION SENSOR COMBINATION. PLUMBING NOTES 1.BATH FAN SHALL BE CONTROLLED BY HUMIDISTAT WITH ADJUSTMENT BETWEEN A RELATIVE HUMIDITY RANGE 50-80%. 2.SHOWER WALLS ABOVE BATHTUB WITH SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH, NON-ABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 6' ABOVE FLOOR. 3.SHOWER COMPARTMENT SHALL BE MINIMUM 1,024 SQ. IN. AND SHALL BE CAPABLE OF ENCOMPASSING A 30 IN. CIRCLE. 4.PROVIDE A 12"x12" MINIMUM ACCESS PANEL TO BATHTUB TRAP CONNECTION UNLESS PLUMBING IS WITHOUT SLIP JOINTS (CPC 405.2). 5.ALL TOILETS SHALL BE 1.28 GPF, SHOWERHEADS 2.0 GPM, AND FAUCETS 1.2 GPM, KITCHEN FAUCET 1.8 GPM. 6.FOR SHOWERS OR TUB-SHOWERS MAX. TEMPERATURE OF 120 DEGREE TO BE PROVIDED BY THE USE CONTROL VALVE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE. 7.ALL GLAZING IN ALL DOORS, BATH/SHOWER ENCLOSURES MUST BE IDENTIFIED BY A LABEL AS A SAFETY GLAZING. 8.WALL COVERING IN SHOWERS AND TUBS TO BE CEMENT PLASTER OR TILE EQUAL TO 72" ABOVE DRAIN. ENCLOSURES MUST BE OF APPROVED SAFETY GLAZING AND DOORS MUST SWING OUT OF SHOWERS. WINDOWS IN ENCLOSURE WALLS SHALL BE LABELED SAFETY GLAZING WHEN LESS THAN 60" ABOVE THE DRAIN, TYPICAL FOR ALL BATHROOMS. 9.GREEN BOARD GYPSUM OR WATER RESISTANT GYPSUM BOARD SHALL NOT BE USED AS BACKING FOR CEILING FINISH INSIDE BATHROOM DUE TO CONDENSATION OR VAPOR. 10.WATER HEATER: SIZE PER TITLE 24 WITH VENT THROUGH OUTSIDE. PROVIDE P&T RELIEF VALVE ON WATER HEATER. PROVIDE SMITTY PAN WITH DRAIN INSULATION/CLEARANCE PER MANUFACTURER SPECS. WATER HEATER TANK (IF USED) MUST BE ADEQUATELY BRACED TO RESIST SEISMIC FORCES: PROVIDE 2 STRAPS, 1 STRAP AT TOP 1/3 OF TANK AND 1 STRAP AT BOTTOM 1/3 OF THE TANK. 11.PLUMBING VENT TERMINATIONS SHALL BE AT LEAST 10' FROM FRESH AIR INTAKE OR VENTILATION. 12.B-VENTS SHALL TERMINATE AT LEAST 4' FROM FRESH AIR INTAKE OR VENTILATION. NE W FL O O R P L A N SHEET A3 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 (N) FLOOR PLAN SCALE: 1/4" = 1'-0" ELEC. BOX HEIGHT N.T.S. AGING-IN-PLACE NOTES A. REINFORCEMENT FOR GRAB BARS - AT LEAST ONE BATHROOM ON THE ENTRY LEVEL SHALL BE PROVIDED WITH REINFORCEMENT INSTALLED IN ACCORDANCE WITH CRC R327.1. 1) REINFORCEMENT SHALL BE SOLID LUMBER OR OTHER CONSTRUCTION MATERIALS APPROVED BY THE ENFORCING AGENCY. 2) REINFORCEMENT SHALL NOT BE LESS THAN 2 BY 8 INCH NOMINAL LUMBER (1-1/2 INCH BY 7-1/4 INCH ACTUAL DIMENSION) OR OTHER CONSTRUCTION MATERIAL PROVIDING EQUAL HEIGHT AND LOAD CAPACITY. REINFORCEMENT SHALL BE LOCATED BETWEEN 32 INCHES AND 39-1/4 INCHES ABOVE THE FINISHED FLOOR, FLUSH WITH THE WALL FRAMING. 3) WATER CLOSET REINFORCEMENT SHALL BE INSTALLED ON BOTH SIDE WALLS OF THE FIXTURE, OR ONE SIDE WALL AND THE BACK WALL. 4) SHOWER REINFORCEMENT SHALL BE CONTINUOUS WHERE WALL FRAMING IS PROVIDED. 5) BATHTUB AND COMBINATION BATHTUB/SHOWER REINFORCEMENT SHALL BE CONTINUOUS ON EACH END OF THE BATHTUB AND THE BACK WALL. ADDITIONALLY, BACK WALL REINFORCEMENT FOR A LOWER GRAB BAR SHALL BE PROVIDED WITH THE BOTTOM EDGE LOCATED NO MORE THAN 6 INCHES ABOVE THE BATHTUB RIM. 6) WHERE THE WATER CLOSET IS NOT PLACED ADJACENT TO A SIDE WALL CAPABLE OF ACCOMMODATING A GRAB BAR, THE BATHROOM SHALL HAVE PROVISIONS FOR INSTALLATION OF FLOOR-MOUNTED, FOLDAWAY OR SIMILAR ALTERNATE GRAB BAR REINFORCEMENTS APPROVED BY THE ENFORCING AGENCY. 7) REINFORCEMENT SHALL NOT BE REQUIRED IN WALL FRAMING FOR PRE-FABRICATED SHOWER ENCLOSURES AND BATHTUB WALL PANELS WITH INTEGRAL FACTORY- INSTALLED GRAB BARS OR WHEN FACTORY-INSTALLED REINFORCEMENT FOR GRAB BARS IS PROVIDED. 8) SHOWER ENCLOSURES THAT DO NOT PERMIT INSTALLATION OF REINFORCEMENT AND/OR GRAB BARS SHALL BE PERMITTED, PROVIDED REINFORCEMENT FOR INSTALLATION OF FLOOR-MOUNTED GRAB BARS OR AN ALTERNATE METHOD IS APPROVED BY THE ENFORCING AGENCY. 9) BATHTUBS WITH NO SURROUNDING WALLS, OR WHERE WALL PANELS DO NOT PERMIT THE INSTALLATION OF REINFORCEMENT SHALL BE PERMITTED, PROVIDED REINFORCEMENT FOR INSTALLATION OF FLOOR-MOUNTED GRAB BARS ADJACENT TO THE BATHTUB OR AN ALTERNATE METHOD IS APPROVED BY THE ENFORCING AGENCY. 10) REINFORCEMENT OF FLOORS SHALL NOT BE REQUIRED FOR BATHTUBS AND WATER CLOSETS INSTALLED ON CONCRETE SLAB FLOORS. B. DOCUMENTATION FOR GRAB BAR REINFORCEMENT - INFORMATION AND/OR DRAWINGS IDENTIFYING THE LOCATION OF GRAB BAR REINFORCEMENT SHALL BE PLACED IN THE OPERATION AND MAINTENANCE MANUAL IN ACCORDANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS CODE, CHAPTER 4, DIVISION 4.4. (CRC R327.1.1.1) C. ELECTRICAL RECEPTACLE OUTLET, SWITCH AND CONTROL HEIGHTS - ELECTRICAL RECEPTACLE OUTLETS, SWITCHES AND CONTROLS (INCLUDING CONTROLS FOR HEATING, VENTILATION AND AIR CONDITIONING) INTENDED TO BE USED BY OCCUPANTS SHALL BE LOCATED NO MORE THAN 48 INCHES MEASURED FROM THE TOP OF THE OUTLET BOX AND NOT LESS THAN 15 INCHES MEASURED FROM THE BOTTOM OF THE OUTLET BOX ABOVE THE FINISH FLOOR. (CRC R327.1.2). EXCEPTIONS: 1) DEDICATED RECEPTACLE OUTLETS; FLOOR RECEPTACLE OUTLETS; CONTROLS MOUNTED ON CEILING FANS AND CEILING LIGHTS; AND CONTROLS LOCATED ON APPLIANCES. 2) RECEPTACLE OUTLETS REQUIRED BY THE CALIFORNIA ELECTRICAL CODE ON A WALL SPACE WHERE THE DISTANCE BETWEEN THE FINISHED FLOOR AND A BUILT-IN FEATURE ABOVE THE FINISH FLOOR, SUCH AS A WINDOW, IS LESS THAN 15 INCHES. D. DOORBELL BUTTONS - DOORBELL BUTTONS OR CONTROLS, WHEN INSTALLED, SHALL NOT EXCEED 48 INCHES (1219.2 MM) ABOVE EXTERIOR FLOOR OR LANDING, MEASURED FROM THE TOP OF THE DOORBELL BUTTON ASSEMBLY. WHERE DOORBELL BUTTONS INTEGRATED WITH OTHER FEATURES ARE REQUIRED TO BE INSTALLED ABOVE 48 INCHES (1219.2 MM) MEASURED FROM THE EXTERIOR FLOOR OR LANDING, A STANDARD DOORBELL BUTTON OR CONTROL SHALL ALSO BE PROVIDED AT A HEIGHT NOT EXCEEDING 48 INCHES (1219.2 MM) ABOVE EXTERIOR FLOOR OR LANDING, MEASURED FROM THE TOP OF THE DOORBELL BUTTON OR CONTROL. (CRC R327.1.4) WATER HEATER - DRYER - F.A.U. DOOR DETAIL N.T.S. SD LEGEND GFCI RECEPTACLE WR GFCI WEATHER RESISTANT RECEPTACLE TAMPER RESISTANT RECEPTACLE, 120V SINGLE PHASE, 20A, CONTROLLED BY ARC-FAULT CIRCUIT INTERRUPTER (AFCI) 240V DEDICATED OUTLET, AMPERAGE AS INDICATED IN PLAN CEILING-MOUNT RECESS LIGHT OUTDOOR WALL-MOUNT LIGHT FIXTURE W/ PHOTOCELL & MOTION SENSOR $LIGHT SWITCH WITH DIMMER (D) WHERE INDICATED $3 3-WAY LIGHT SWITCH WITH DIMMER (D) WHERE INDICATED $vs VACANCY SENSOR LIGHT SWITCH $W/D WASHER/DRYER DISCONNECT SWITCH, 20A, INSTALL PER MANU. SPECS. EXHAUST FAN (100 CFM MINIMUM) W/ HUMIDITY CONTROL IN-SINK DISPOSAL AIR REGISTER ON CEILING SMOKE DETECTOR CARBON MONOXIDE DETECTOR 4" DRYER VENT W/ DAMPER, TERMINATED 30" ABOVE F.F. ON OUTSIDE WALL 4" SMOOTH SURFACE VENT W/ APPROVED WALL STRAP, TERMINATED ABOVE ROOF THRU. APPROVED FLASHING, 14' LONG MAX., 2 ELBOWS MAX. W/H 240V-50 GAL. WATER HEATER TANK, RHEEMTM MODEL XE50T10H22U W CLOTHES WASHER D CLOTHES DRYER HOSE BIB WITH ANTI-SIPHON VALVE AIR RETURN ON CEILING ROOF-MOUNT ATTIC VENT IAQ FAN (PER TITLE 24), 80 CFM MINIMUM CO 18" 18" PER PLAN 100 SQ. IN. MIN. ON EACH LOUVER @ TOP AND BOTTOM 80" 15" MIN. 48" MAX. F.F. WINDOW SCHEDULE WINDOWS' U-FACTOR = 0.3 AND SHGC = 0.23 A 48"x48" SLIDING GLASS W/D, DUAL GLAZING, VINYL FRAME B 60"x48" SLIDING GLASS W/D, DUAL GLAZING, VINYL FRAME C 36"x36" SLIDING GLASS W/D, DUAL GLAZING, VINYL FRAME D 36"x18" S.L. FROSTED GLASS W/D, DUAL GLAZING, VINYL FRAME, TEMPERED GLASS DOOR SCHEDULE OPAQUE DOORS' U-FACTOR = 0.2 1 30"x80" HOLLOW CORE DOOR 2 28"x80" HOLLOW CORE DOOR 3 36"x80" HOLLOW CORE DOOR 4 36"x80" SOLID CORE ENTRY DOOR W/ TEMPERED GLASS 5 48"x80" CLOSET SLIDING DOOR 6 24"x80" INTERIOR RATED DOOR 7 24"x80" EXTERIOR RATED DOOR DOORS 6 & 7 SHALL HAVE LOUVERS W/ DETAILS AS INDICATED HEREON OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U 1. STC-49 AND 1-HOUR FIRE RATED WALL N.T.S. SOURCE: USG FIRE-RESISTANT ASSEMBLIES TEST NUMBER: UL U305 FOR DOUBLE WALL 5/8" SHEETROCK FIRECODE C CORE GYPSUM BOARD 1" AIR GAP 2x4 WOOD STUD @ 16" O.C. 2 LAYERS OF 5/8" SHEETROCK FIRECODE C CORE GYPSUM BOARD 2. STC-50 AND 1-HOUR FIRE RATED WALL N.T.S. SOURCE: USG FIRE-RESISTANT ASSEMBLIES TEST NUMBER: UL DES U327 AND BBN-760903 5/8" SHEETROCK FIRECODE C CORE GYPSUM BOARD 3" THERMAFIBER SAFB RC-1 CHANNEL OR EQUIVALENT ONE SIDE JOINTS FINISHED 2x4 WOOD STUD @ 16" OR 24" O.C. 5/8" SHEETROCK FIRECODE C CORE GYPSUM BOARD 3'-1" (N) FOUNDATION (PER PLAN) (N) 5" CONC. SLAB O/ VAPOR BARRIER 14 SD-2 8'-0" CEILING HEIGHT 8" MIN. 4x8 RIDGE 7/8" STUCCO OVER SHEARWALL WHERE OCCURS 9 SD-2 7/8" STUCCO (TYP.) WHERE INDICATED 7 SD-1 1 SD-1 6 SD-1 R15 INSULATION 2x4 STUD @ 16" O.C. (TYP.) 13 SD-2 12 4 12" 3 SD-1 5/8" TYP. X DRYWALL TO ROOF SHEATHING GAFTM CLASS A ASPHALT SHINGLES (ICC# ESR-1475) W/ DOUBLE LAYERS OF 30 LB. UNDERLAYMENT ON RADIANT BARRIER SHEATHING 2x6 R.R. @ 24" O.C. R30 INSULATION R15 INSULATION 5/8" TYP. X DRYWALL TO ROOF SHEATHING ON BOTH SIDES 4x6 HEADER D.F. #1 13 SD-2 3'-7"10'-7" (E) FOUNDATION 2x8 C.J. @ 24" O.C. (E) WALL 1" GAP (E) ROOF FRAME (E) RESIDENCE 5 SD-2 6 SD-2 2x4 STUD @ 16" O.C. (TYP.) 16 SD-1 SE C T I O N FI R E R A T E D L I S T I N G LO A D C A L C U L A T I O N S SECTION S-S SCALE: 1/2" = 1'-0" SHEET A4 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U (N) ADU 799 SF (N) JADU 431 SF (E) WATER METER (E) GAS METER (E) POWER POLE PROPERTY LINE - 75.00' PR O P E R T Y L I N E - 8 9 . 1 9 ' PR O P E R T Y L I N E - 1 0 8 . 2 1 ' (E) 6'H WOODEN FENCE (E ) 6 ' H B L O C K W A L L 9'-1"27'-4"4'-0" 19'-7" 30'-3" 7'-0" 35'-5" W MARTY LN 25'-0" 36'-3" 7'-0" (E) 1-STORY MAIN UNIT 1,248 SF (E) GARAGE 353 SF (E) PORCH 23 SF 5'-0" (E) DRIVEWAY AND IMPERVIOUS SURFACE 20'-11"9'-1"18'-0"3'-6"4'-6" 34'-7" 18'-8"17'-3"4'-0" 10'-0" FRONT YARD LANDSCAPING (N) 1" WATER METER 6'-0" i= 0 . 2 5 % F L i=0.25% FL i= 0 . 2 5 % F L 2 1 i=0.25% FL i= 0 . 2 5 % F L 1 2% M I N 2% M I N 2% M I N 2% M I N 2% M I N 2% M I N 2% M I N 2% M I N 2% MIN 2% MIN 2% MIN 2% MIN 2% MIN 2% MIN (10.00 FS) (ASSUMED ELEVATION) 11 . 6 5 F L (E ) (E ) (E ) 11.88 FS 12.18 FS 11.72 FS 12.34 FS 12.55 FS 12.30 FS 12.42 FS 12.42 FS 12.37 FS 12.08 FS12 . 0 0 F L SHEET DR-1 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U DRAINAGE PLAN SCALE: 1/8" = 1'-0" DR A I N A G E P L A N DIG ALERT (811) SHALL BE CONTACTED AND COMPLIANCE WITH EXCAVATION SAFETY IN ACCORDANCE WITH GOVERNMENT CODE 4216 SHALL BE FOLLOWED PRIOR TO ANY EXCAVATION TAKING PLACE TYPICAL GRAVEL BAG DETAIL N.T.S. 1 EROSION CONTROL NOTES 1 INSTALL TYPICAL GRAVEL BAGS PER STD. SE-6, CALIFORNIA STORM WATER BMP HANDBOOK 2 INSTALL 10'x10' MATERIAL STOCKPILE AREA PER STANDARD WM-3 4" PCC 90% COMPACTED SUBGRADE WALKWAY SECTION N.T.S. Pr o j e c t N a m e Date Drawing Title Project Number DesignedDrawn DRAWING NUMBER Checked ANY DISCREPANCIES. DO NOT SCALE DRAWINGS; USE FIGURED DIMENSIONS. CONTRACTOR IS TO NOTIFY THE ENGINEER FOR CLARIFICATION OF OR EXISTING FIELD CONDITIONS AGAINST DRAWINGS. CONTRACTORS ARE TO VERIFY ALL DIMENSIONS ON DRAWINGS CALIFORNIA RELATING TO STRUCTURES AND BUILDINGS. RULES, REGULATIONS AND ORDINANCES OF THE STATE OF THE BEST OF MY KNOWLEDGE, THE SAME COMPLIES WITH THE HAS BEEN PREPARED UNDER MY SUPERVISION AND THAT TO I HEREBY CERTIFY THAT THE ENGINEERING ON THESE PLANS NO. DATE REVISION NE W A T T A C H E D J A D U A N D A D U OW N E R : T T S T A R S L L C 24 2 2 W M A R T Y L N , U N I T 2 & 3 SA N T A A N A , C A 9 2 7 0 6 S-1 Pr o j e c t N a m e Date Drawing Title Project Number DesignedDrawn DRAWING NUMBER Checked ANY DISCREPANCIES. DO NOT SCALE DRAWINGS; USE FIGURED DIMENSIONS. CONTRACTOR IS TO NOTIFY THE ENGINEER FOR CLARIFICATION OF OR EXISTING FIELD CONDITIONS AGAINST DRAWINGS. CONTRACTORS ARE TO VERIFY ALL DIMENSIONS ON DRAWINGS CALIFORNIA RELATING TO STRUCTURES AND BUILDINGS. RULES, REGULATIONS AND ORDINANCES OF THE STATE OF THE BEST OF MY KNOWLEDGE, THE SAME COMPLIES WITH THE HAS BEEN PREPARED UNDER MY SUPERVISION AND THAT TO I HEREBY CERTIFY THAT THE ENGINEERING ON THESE PLANS NO. DATE REVISION NE W A T T A C H E D J A D U A N D A D U OW N E R : T T S T A R S L L C 24 2 2 W M A R T Y L N , U N I T 2 & 3 SA N T A A N A , C A 9 2 7 0 6 S-2 PLASTER CREED N.T.S. EXTERIOR BEARING FOOTING N.T.S. 24 23 20 16 12 08 15 07 04 03 14 10 06 05 02 011309 NON-BEARING INTERIOR WALL N.T.S. SIMPSON HOLDOWN W/ SSTB BOLT N.T.S. 11 18 17 22 21 LANDING DETAIL N.T.S. NEW TO EXISTING FOOTING N.T.S. A36 THREADED HOLDDOWN BOLTS N.T.S. FOOTING INTERSECTION & CORNER N.T.S. SQUARE FOOTING N.T.S. DOWEL CONNECTION N.T.S. SQUARE FOOTING N.T.S. MONO-POUR ONLY #4 DWLS T&B, 6" EMB. INTO (E) FTG., W/ EPOXY, ICC ESR-2508 SPECIAL INSPECTION REQUIRED EXISTING EXISTING FOOTING CONT. REINF. BARS PER PLAN 24"6" NEW NEW FOOTING CONCRETE STEPS AND LANDING N.T.S. INTERIOR BEARING FOOTING N.T.S. MONO-POUR ONLY 19 Pr o j e c t N a m e Date Drawing Title Project Number DesignedDrawn DRAWING NUMBER Checked ANY DISCREPANCIES. DO NOT SCALE DRAWINGS; USE FIGURED DIMENSIONS. CONTRACTOR IS TO NOTIFY THE ENGINEER FOR CLARIFICATION OF OR EXISTING FIELD CONDITIONS AGAINST DRAWINGS. CONTRACTORS ARE TO VERIFY ALL DIMENSIONS ON DRAWINGS CALIFORNIA RELATING TO STRUCTURES AND BUILDINGS. RULES, REGULATIONS AND ORDINANCES OF THE STATE OF THE BEST OF MY KNOWLEDGE, THE SAME COMPLIES WITH THE HAS BEEN PREPARED UNDER MY SUPERVISION AND THAT TO I HEREBY CERTIFY THAT THE ENGINEERING ON THESE PLANS NO. DATE REVISION NE W A T T A C H E D J A D U A N D A D U OW N E R : T T S T A R S L L C 24 2 2 W M A R T Y L N , U N I T 2 & 3 SA N T A A N A , C A 9 2 7 0 6 SD-1 2-2X CEILING JOISTS @ OPENING 2-2X BLKG AROUND EDGES HU2x-2 HANGER PLATE SPLICING N.T.S.24 23 20 16 12 08 19 15 04 03 14 10 06 05 02 011309 11 18 17 22 21 PIPING THRU PLATE FRAMING N.T.S. STUD NOTCHING/BORING LIMITS N.T.S. RIDGE DETAIL N.T.S. POST PER PLAN BM. PER PLAN BEAM TO POST CONNECTION N.T.S. INTERIOR NON-BEARING WALL N.T.S. WALL FRAMING N.T.S. SHEAR TRANSFER N.T.S. RAKE DETAIL N.T.S. DTC CLIP 2x BLKG. @ 24" O.C. 1/2" CLR. DOUBLE PLATES STUD WALL JOIST OR 3 - 16d RAFTER JOISTS PARALLEL TO WALL PER JST JOISTS PERPENDICULAR TO WALL STUD WALL DTC CLIP 1/2" CLR.JST. OR RR DOUBLE PLATES FLUSH BEAM CONNECTION N.T.S. EAVE DETAIL (1-HR FIRE RATED) N.T.S. CALIFORNIA ROOF FRAMING N.T.S. SIMP. STRAP MSTC66 U.O.N. 2X STUDS @ 16" O.C. 2-2X STUDS OR POST PER PLAN DOUBLE TOP PLATES SHEAR WALL WHERE OCCURS SIMPSON END POST CAP PER PLAN DRAG BEAM PER PLAN EAVE DETAIL N.T.S. HRC PER PLAN HIP P E R P L A N HIP P E R P L A N POST PER PLAN RIDGE PER PLAN HIP ROOF DETAIL N.T.S. HIP TO TOP PLATE CONNECTION N.T.S. ATTIC OPENING DETAIL N.T.S. 2X STUDS @ 16" O.C. 2-2X STUDS OR POST PER PLAN BEAM PER PLAN POST PER PLAN SIMP. STRAP ST6236 BENT IN HALF BEAM PER PLAN POST PER PLAN BEAM IN PERPENDICULAR DIRECTION CAP PER PLAN CAP PER PLAN STRAP PLACEMENT DETAIL N.T.S. SIMP. STRAP ST6236 2X STUDS @ 16" O.C. SIMP. STRAP ST6236 BENT IN HALF 2X STUDS @ 16" O.C. IN PERPENDICULAR DIRECTION 03 STRAP PLACEMENT DETAIL N.T.S. CRICKET DETAIL N.T.S. DRAG STRAP PER PLAN WALL PER PLAN DBL. TOP PLATES SIDE STRAP ALTERNATE IF NEEDED RAFTER DRAG DETAIL N.T.S. Pr o j e c t N a m e Date Drawing Title Project Number DesignedDrawn DRAWING NUMBER Checked ANY DISCREPANCIES. DO NOT SCALE DRAWINGS; USE FIGURED DIMENSIONS. CONTRACTOR IS TO NOTIFY THE ENGINEER FOR CLARIFICATION OF OR EXISTING FIELD CONDITIONS AGAINST DRAWINGS. CONTRACTORS ARE TO VERIFY ALL DIMENSIONS ON DRAWINGS CALIFORNIA RELATING TO STRUCTURES AND BUILDINGS. RULES, REGULATIONS AND ORDINANCES OF THE STATE OF THE BEST OF MY KNOWLEDGE, THE SAME COMPLIES WITH THE HAS BEEN PREPARED UNDER MY SUPERVISION AND THAT TO I HEREBY CERTIFY THAT THE ENGINEERING ON THESE PLANS NO. DATE REVISION NE W A T T A C H E D J A D U A N D A D U OW N E R : T T S T A R S L L C 24 2 2 W M A R T Y L N , U N I T 2 & 3 SA N T A A N A , C A 9 2 7 0 6 SD-2 DESIGN CRITERIA: Pr o j e c t N a m e Date Drawing Title Project Number DesignedDrawn DRAWING NUMBER Checked ANY DISCREPANCIES. DO NOT SCALE DRAWINGS; USE FIGURED DIMENSIONS. CONTRACTOR IS TO NOTIFY THE ENGINEER FOR CLARIFICATION OF OR EXISTING FIELD CONDITIONS AGAINST DRAWINGS. CONTRACTORS ARE TO VERIFY ALL DIMENSIONS ON DRAWINGS CALIFORNIA RELATING TO STRUCTURES AND BUILDINGS. RULES, REGULATIONS AND ORDINANCES OF THE STATE OF THE BEST OF MY KNOWLEDGE, THE SAME COMPLIES WITH THE HAS BEEN PREPARED UNDER MY SUPERVISION AND THAT TO I HEREBY CERTIFY THAT THE ENGINEERING ON THESE PLANS NO. DATE REVISION NE W A T T A C H E D J A D U A N D A D U OW N E R : T T S T A R S L L C 24 2 2 W M A R T Y L N , U N I T 2 & 3 SA N T A A N A , C A 9 2 7 0 6 SN-1 JA D U T I T L E 2 4 RE P O R T SHEET T1 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U AD U T I T L E 2 4 RE P O R T SHEET T2 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U AD U T I T L E 2 4 RE P O R T SHEET T3 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U GR E E N B U I L D I N G ST A N D A R D S C O D E SHEET T4 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 CHAPTER 4 RESIDENTIAL MANDATORY MEASURES DIVISION 4.1 PLANNING AND DESIGN DIVISION 4.3 WATER EFFICIENCY AND CONSERVATION 4.406 ENHANCED DURABILITY AND REDUCED MAINTENANCE 4.406.1 RODENT PROOFING. Annular spaces around pipes, electric cables, conduits or other openings in sole/bottom plates at exterior walls shall be protected against the passage of rodents by closing such openings with cement mortar, concrete masonry or a similar method acceptable to the enforcing agency. 4.408 CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING 4.408.1 CONSTRUCTION WASTE MANAGEMENT. Recycle and/or salvage for reuse a minimum of 65 percent of the non-hazardous construction and demolition waste in accordance with either Section 4.408.2, 4.408.3 or 4.408.4, or meet a more stringent local construction and demolition waste management ordinance. Exceptions: 1. Excavated soil and land-clearing debris. 2. Alternate waste reduction methods developed by working with local agencies if diversion or recycle facilities capable of compliance with this item do not exist or are not located reasonably close to the jobsite. 3. The enforcing agency may make exceptions to the requirements of this section when isolated jobsites are located in areas beyond the haul boundaries of the diversion facility. 4.408.2 CONSTRUCTION WASTE MANAGEMENT PLAN. Submit a construction waste management plan in conformance with Items 1 through 5. The construction waste management plan shall be updated as necessary and shall be available during construction for examination by the enforcing agency. 1. Identify the construction and demolition waste materials to be diverted from disposal by recycling, reuse on the project or salvage for future use or sale. 2. Specify if construction and demolition waste materials will be sorted on-site (source separated) or bulk mixed (single stream). 3. Identify diversion facilities where the construction and demolition waste material collected will be taken. 4. Identify construction methods employed to reduce the amount of construction and demolition waste generated. 5. Specify that the amount of construction and demolition waste materials diverted shall be calculated by weight or volume, but not by both. 4.408.3 WASTE MANAGEMENT COMPANY. Utilize a waste management company, approved by the enforcing agency, which can provide verifiable documentation that the percentage of construction and demolition waste material diverted from the landfill complies with Section 4.408.1. Note: The owner or contractor may make the determination if the construction and demolition waste materials will be diverted by a waste management company. 4.408.4 WASTE STREAM REDUCTION ALTERNATIVE [LR]. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed 3.4 lbs./sq.ft. of the building area shall meet the minimum 65% construction waste reduction requirement in Section 4.408.1 4.408.4.1 WASTE STREAM REDUCTION ALTERNATIVE. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed 2 pounds per square foot of the building area, shall meet the minimum 65% construction waste reduction requirement in Section 4.408.1 4.408.5 DOCUMENTATION. Documentation shall be provided to the enforcing agency which demonstrates compliance with Section 4.408.2, items 1 through 5, Section 4.408.3 or Section 4.408.4.. Notes: 1. Sample forms found in "A Guide to the California Green Building Standards Code (Residential)" located at www.hcd.ca.gov/CALGreen.html may be used to assist in documenting compliance with this section. 2. Mixed construction and demolition debris (C & D) processors can be located at the California Department of Resources Recycling and Recovery (CalRecycle). 4.410 BUILDING MAINTENANCE AND OPERATION 4.410.1 OPERATION AND MAINTENANCE MANUAL. At the time of final inspection, a manual, compact disc, web-based reference or other media acceptable to the enforcing agency which includes all of the following shall be placed in the building: 1. Directions to the owner or occupant that the manual shall remain with the building throughout the life cycle of the structure. 2. Operation and maintenance instructions for the following: a. Equipment and appliances, including water-saving devices and systems, HVAC systems, photovoltaic systems, electric vehicle chargers, water-heating systems and other major appliances and equipment. b. Roof and yard drainage, including gutters and downspouts. c. Space conditioning systems, including condensers and air filters. d. Landscape irrigation systems. e. Water reuse systems. 3. Information from local utility, water and waste recovery providers on methods to further reduce resource consumption, including recycle programs and locations. 4. Public transportation and/or carpool options available in the area. 5. Educational material on the positive impacts of an interior relative humidity between 30-60 percent and what methods an occupant may use to maintain the relative humidity level in that range. 6. Information about water-conserving landscape and irrigation design and controllers which conserve water. 7. Instructions for maintaining gutters and downspouts and the importance of diverting water at least 5 feet away from the foundation. 8. Information on required routine maintenance measures, including, but not limited to, caulking, painting, grading around the building, etc. 9. Information about state solar energy and incentive programs available. 10. A copy of all special inspections verifications required by the enforcing agency or this code. 11. Information from the Department of Forestry and Fire Protection on maintenance of defensible space around residential structures. 12. Information and/or drawings identifying the location of grab bar reinforcements. 4.410.2 RECYCLING BY OCCUPANTS. Where 5 or more multifamily dwelling units are constructed on a building site, provide readily accessible area(s) that serves all buildings on the site and are identified for the depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics, organic waster, and metals, or meet a lawfully enacted local recycling ordinance, if more restrictive. Exception: Rural jurisdictions that meet and apply for the exemption in Public Resources Code Section 42649.82 (a)(2)(A) et seq. are note required to comply with the organic waste portion of this section. DIVISION 4.4 MATERIAL CONSERVATION AND RESOURCE EFFICIENCY DIVISION 4.5 ENVIRONMENTAL QUALITY 4.303 INDOOR WATER USE 4.303.1 WATER CONSERVING PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads) shall comply with the sections 4.303.1.1, 4.303.1.2, 4.303.1.3, and 4.303.4.4. Note: All noncompliant plumbing fixtures in any residential real property shall be replaced with water-conserving plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate of occupancy, or final permit approval by the local building department. See Civil Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and other important enactment dates. 4.303.1.1 Water Closets. The effective flush volume of all water closets shall not exceed 1.28 gallons per flush. Tank-type water closets shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Tank-type Toilets. Note: The effective flush volume of dual flush toilets is defined as the composite, average flush volume of two reduced flushes and one full flush. 4.303.1.2 Urinals. The effective flush volume of wall mounted urinals shall not exceed 0.125 gallons per flush. The effective flush volume of all other urinals shall not exceed 0.5 gallons per flush. 4.303.1.3 Showerheads. 4.303.1.3.1 Single Showerhead. Showerheads shall have a maximum flow rate of not more than 1.8 gallons per minute at 80 psi. Showerheads shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Showerheads. 4.303.1.3.2 Multiple showerheads serving one shower. When a shower is served by more than one showerhead, the combined flow rate of all the showerheads and/or other shower outlets controlled by a single valve shall not exceed 1.8 gallons per minute at 80 psi, or the shower shall be designed to only allow one shower outlet to be in operation at a time. Note: A hand-held shower shall be considered a showerhead. 4.303.1.4 Faucets. 4.303.1.4.1 Residential Lavatory Faucets. The maximum flow rate of residential lavatory faucets shall not exceed 1.2 gallons per minute at 60 psi. The minimum flow rate of residential lavatory faucets shall not be less than 0.8 gallons per minute at 20 psi. 4.303.1.4.2 Lavatory Faucets in Common and Public Use Areas. The maximum flow rate of lavatory faucets installed in common and public use areas (outside of dwellings or sleeping units) in residential buildings shall not exceed 0.5 gallons per minute at 60 psi. 4.303.1.4.3 Metering Faucets. Metering faucets when installed in residential buildings shall not deliver more than 0.2 gallons per cycle. 4.303.1.4.4 Kitchen Faucets. The maximum flow rate of kitchen faucets shall not exceed 1.8 gallons per minute at 60 psi. Kitchen faucets may temporarily increase the flow above the maximum rate, but not to exceed 2.2 gallons per minute at 60 psi, and must default to a maximum flow rate of 1.8 gallons per minute at 60 psi. Note: Where complying faucets are unavailable, aerators or other means may be used to achieve reduction. 4.303.1.4.5 Pre-rinse spray valves. When installed, shall meet the requirements in the California Code of Regulations, Title 20 (Appliance Efficiency Regulations), Sections 1605.1 (h)(4) Table H-2, Section 1605.3 (h)(4)(A), and Section 1607 (d)(7) and shall be equipped with an integral automatic shutoff. FOR REFERENCE ONLY: The following table and code section have been reprinted from the California Code of Regulations, Title 20 (Appliance Efficiency Regulations),Section 1605.1 (h)(4) and Section 1605.3 (h)(4)(A). Title 20 Section 1605.3 (h)(4)(A): Commercial prerinse spray values manufactured on or after January 1, 2006, shall have a minimum spray force of not less than 4.0 ounces-force (ozf)[113 grams-force(gf)] 4.303.2 Submeters for multifamily buildings and dwelling units in mixed-used residential/commercial buildings. Submeters shall be installed to measure water usage of individual rental dwelling units in accordance with the California Plumbing Code. 4.303.3 Standards for plumbing fixtures and fittings. Plumbing fixtures and fittings shall be installed in accordance with the California Plumbing Code, and shall meet the applicable standards referenced in Table 1701.1 of the California Plumbing Code. TABLE - MAXIMUM FIXTURE WATER USE FIXTURE TYPE FLOW RATE SHOWER HEADS (RESIDENTIAL)1.8 GMP @ 80 PSI LAVATORY FAUCETS (RESIDENTIAL)MAX. 1.2 GPM @ 60 PSI MIN. 0.8 GPM @ 20 PSI LAVATORY FAUCETS IN COMMON & PUBLIC USE AREAS 0.5 GPM @ 60 PSI KITCHEN FAUCETS 1.8 GPM @ 60 PSI METERING FAUCETS 0.2 GAL/CYCLE WATER CLOSET 1.28 GAL/FLUSH URINALS 0.125 GAL/FLUSH 4.304 OUTDOOR WATER USE 4.304.1 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. Residential developments shall comply with a local water efficient landscape ordinance or the current California Department of Water Resources' Model Water Efficient Landscape Ordinance (MWELO), whichever is more stringent. NOTES: 1. The Model Water Efficient Landscape Ordinance (MWELO) is located in the California Code Regulations, Title 23, Chapter 2.7, Division 2. MWELO and supporting documents, including water budget calculator, are available at: https://www.water.ca.gov/ ABBREVIATION DEFINITIONS: HCD Department of Housing and Community Development BSC California Building Standards Commission DSA-SS Division of the State Architect, Structural Safety OSHPD Office of Statewide Health Planning and Development LR Low Rise HR High Rise AA Additions and Alterations N New NOTE: THIS TABLE COMPILES THE DATA IN SECTION 4.303.1, AND IS INCLUDED AS A CONVENIENCE FOR THE USER. SECTION 4.102 DEFINITIONS 4.102.1 DEFINITIONS The following terms are defined in Chapter 2 (and are included here for reference) FRENCH DRAIN. A trench, hole or other depressed area loosely filled with rock, gravel, fragments of brick or similar pervious material used to collect or channel drainage or runoff water. WATTLES. Wattles are used to reduce sediment in runoff. Wattles are often constructed of natural plant materials such as hay, straw or similar material shaped in the form of tubes and placed on a downflow slope. Wattles are also used for perimeter and inlet controls. 4.106 SITE DEVELOPMENT 4.106.1 GENERAL. Preservation and use of available natural resources shall be accomplished through evaluation and careful planning to minimize negative effects on the site and adjacent areas. Preservation of slopes, management of storm water drainage and erosion controls shall comply with this section. 4.106.2 STORM WATER DRAINAGE AND RETENTION DURING CONSTRUCTION. Projects which disturb less than one acre of soil and are not part of a larger common plan of development which in total disturbs one acre or more, shall manage storm water drainage during construction. In order to manage storm water drainage during construction, one or more of the following measures shall be implemented to prevent flooding of adjacent property, prevent erosion and retain soil runoff on the site. 1. Retention basins of sufficient size shall be utilized to retain storm water on the site. 2. Where storm water is conveyed to a public drainage system, collection point, gutter or similar disposal method, water shall be filtered by use of a barrier system, wattle or other method approved by the enforcing agency. 3. Compliance with a lawfully enacted storm water management ordinance. Note: Refer to the State Water Resources Control Board for projects which disturb one acre or more of soil, or are part of a larger common plan of development which in total disturbs one acre or more of soil. (Website: https://www.waterboards.ca.gov/water_issues/programs/stormwater/construction.html) 4.106.3 GRADING AND PAVING. Construction plans shall indicate how the site grading or drainage system will manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface water include, but are not limited to, the following: 1. Swales 2. Water collection and disposal systems 3. French drains 4. Water retention gardens 5. Other water measures which keep surface water away from buildings and aid in groundwater recharge. Exception: Additions and alterations not altering the drainage path. 4.106.4 Electric vehicle (EV) charging for new construction. New construction shall comply with Sections 4.106.4.1 or 4.106.4.2 to facilitate future installation and use of EV chargers. Electric vehicle supply equipment (EVSE) shall be installed in accordance with the California Electrical Code, Article 625. Exceptions: 1. On a case-by-case basis, where the local enforcing agency has determined EV charging and infrastructure are not feasible based upon one or more of the following conditions: 1.1 Where there is no local utility power supply or the local utility is unable to supply adequate power. 1.2 Where there is evidence suitable to the local enforcing agency substantiating that additional local utility infrastructure design requirements, directly related to the implementation of Section 4.106.4, may adversely impact the construction cost of the project. 2. Accessory Dwelling Units (ADU) and Junior Accessory Dwelling Units (JADU) without additional parking facilities. 4.106.4.1 New one- and two-family dwellings and townhouses with attached private garages. For each dwelling unit, install a listed raceway to accommodate a dedicated 208/240-volt branch circuit. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main service or subpanel and shall terminate into a listed cabinet, box or other enclosure in close proximity to the proposed location of an EV charger. Raceways are required to be continuous at enclosed, inaccessible or concealed areas and spaces. The service panel and/or subpanel shall provide capacity to install a 40-ampere 208/240-volt minimum dedicated branch circuit and space(s) reserved to permit installation of a branch circuit overcurrent protective device. Exemption: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the proposed location of an EV charger at the time of original construction in accordance with the California Electrical Code. 4.106.4.1.1 Identification. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging as "EV CAPABLE". The raceway termination location shall be permanently and visibly marked as "EV CAPABLE". CHAPTER 3 GREEN BUILDING SECTION 301 GENERAL 301.1 SCOPE. Buildings shall be designed to include the green building measures specified as mandatory in the application checklists contained in this code. Voluntary green building measures are also included in the application checklists and may be included in the design and construction of structures covered by this code, but are not required unless adopted by a city, county, or city and county as specified in Section 101.7. 301.1.1 Additions and alterations. [HCD] The mandatory provisions of Chapter 4 shall be applied to additions or alterations of existing residential buildings where the addition or alteration increases the building's conditioned area, volume, or size. The requirements shall apply only to and/or within the specific area of the addition or alteration. The mandatory provision of Section 4.106.4.2 may apply to additions or alterations of existing parking facilities or the addition of new parking facilities serving existing multifamily buildings. See Section 4.106.4.3 for application. Note: Repairs including, but not limited to, resurfacing, restriping and repairing or maintaining existing lighting fixtures are not considered alterations for the purpose of this section. Note: On and after January 1, 2014, residential buildings undergoing permitted alterations, additions, or improvements shall replace noncompliant plumbing fixtures with water-conserving plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate of occupancy or final permit approval by the local building department. See Civil Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and other important enactment dates. 301.2 LOW-RISE AND HIGH-RISE RESIDENTIAL BUILDINGS. [HCD] The provisions of individual sections of CALGreen may apply to either low-rise residential buildings high-rise residential buildings, or both. Individual sections will be designated by banners to indicate where the section applies specifically to low-rise only (LR) or high-rise only (HR). When the section applies to both low-rise and high-rise buildings, no banner will be used. SECTION 302 MIXED OCCUPANCY BUILDINGS 302.1 MIXED OCCUPANCY BUILDINGS. In mixed occupancy buildings, each portion of a building shall comply with the specific green building measures applicable to each specific occupancy. Exceptions: 1. [HCD] Accessory structures and accessory occupancies serving residential buildings shall comply with Chapter 4 and Appendix A4, as applicable. 2. [HCD] For purposes of CALGreen, live/work units, complying with Section 419 of the California Building Code, shall not be considered mixed occupancies. Live/Work units shall comply with Chapter 4 and Appendix A4, as applicable. 4.106.4.2 New multifamily dwellings, hotels and motels and new residential parking facilities. When parking is provided, parking spaces for new multifamily dwellings, hotels and motels shall meet the requirements of Sections 4.106.4.2.1 and 4.106.4.2.2. Calculations for spaces shall be rounded up to the nearest whole number. A parking space served by electric vehicle supply equipment or designed as a future EV charging space shall count as at least one standard automobile parking space only for the purpose of complying with any applicable minimum parking space requirements established by a local jurisdiction. See Vehicle Code Section 22511.2 for further details. 4.106.4.2.1Multifamily development projects with less than 20 dwelling units; and hotels and motels with less than 20 sleeping units or guest rooms. The number of dwelling units, sleeping units or guest rooms shall be based on all buildings on a project site subject to this section. 1.EV Capable. Ten (10) percent of the total number of parking spaces on a building site, provided for all types of parking facilities, shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE. Electrical load calculations shall demonstrate that the electrical panel service capacity and electrical system, including any on-site distribution transformer(s), have sufficient capacity to simultaneously charge all EVs at all required EV spaces at a minimum of 40 amperes. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code. Exceptions: 1.When EV chargers (Level 2 EVSE) are installed in a number equal to or greater than the required number of EV capable spaces. 2.When EV chargers (Level 2 EVSE) are installed in a number less than the required number of EV capable spaces, the number of EV capable spaces required may be reduced by a number equal to the number of EV chargers installed. Notes: a.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating future EV charging. b.There is no requirement for EV spaces to be constructed or available until receptacles for EV charging or EV chargers are installed for use. 2.EV Ready. Twenty-five (25) percent of the total number of parking spaces shall be equipped with low power Level 2 EV charging receptacles. For multifamily parking facilities, no more than one receptacle is required per dwelling unit when more than one parking space is provided for use by a single dwelling unit. Exception: Areas of parking facilities served by parking lifts. 4.106.4.2.2 Multifamily development projects with 20 or more dwelling units, hotels and motels with 20 or more sleeping units or guest rooms. The number of dwelling units, sleeping units or guest rooms shall be based on all buildings on a project site subject to this section. 1.EV Capable. Ten (10) percent of the total number of parking spaces on a building site, provided for all types of parking facilities, shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE. Electrical load calculations shall demonstrate that the electrical panel service capacity and electrical system, including any on-site distribution transformer(s), have sufficient capacity to simultaneously charge all EVs at all required EV spaces at a minimum of 40 amperes. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code. Exception: When EV chargers (Level 2 EVSE) are installed in a number greater than five (5) percent of parking spaces required by Section 4.106.4.2.2, Item 3, the number of EV capable spaces required may be reduced by a number equal to the number of EV chargers installed over the five (5) percent required. Notes: a.Construction documents shall show locations of future EV spaces. b.There is no requirement for EV spaces to be constructed or available until receptacles for EV charging or EV chargers are installed for use. 2.EV Ready. Twenty-five (25) percent of the total number of parking spaces shall be equipped with low power Level 2 EV charging receptacles. For multifamily parking facilities, no more than one receptacle is required per dwelling unit when more than one parking space is provided for use by a single dwelling unit. Exception: Areas of parking facilities served by parking lifts. 3.EV Chargers. Five (5) percent of the total number of parking spaces shall be equipped with Level 2 EVSE. Where common use parking is provided, at least one EV charger shall be located in the common use parking area and shall be available for use by all residents or guests. When low power Level 2 EV charging receptacles or Level 2 EVSE are installed beyond the minimum required, an automatic load management system (ALMS) may be used to reduce the maximum required electrical capacity to each space served by the ALMS. The electrical system and any on-site distribution transformers shall have sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging station (EVCS) served by the ALMS. The branch circuit shall have a minimum capacity of 40 amperes, and installed EVSE shall have a capacity of not less than 30 amperes. ALMS shall not be used to reduce the minimum required electrical capacity to the required EV capable spaces. 4.106.4.2.2.1 Electric vehicle charging stations (EVCS). Electric vehicle charging stations required by Section 4.106.4.2.2, Item 3, shall comply with Section 4.106.4.2.2.1. Exception: Electric vehicle charging stations serving public accommodations, public housing, motels and hotels shall not be required to comply with this section. See California Building Code, Chapter 11B, for applicable requirements. 4.106.4.2.2.1.1 Location. EVCS shall comply with at least one of the following options: 1.The charging space shall be located adjacent to an accessible parking space meeting the requirements of the California Building Code, Chapter 11A, to allow use of the EV charger from the accessible parking space. 2.The charging space shall be located on an accessible route, as defined in the California Building Code, Chapter 2, to the building. Exception: Electric vehicle charging stations designed and constructed in compliance with the California Building Code, Chapter 11B, are not required to comply with Section 4.106.4.2.2.1.1 and Section 4.106.4.2.2.1.2, Item 3. 4.106.4.2.2.1.2 Electric vehicle charging stations (EVCS) dimensions. The charging spaces shall be designed to comply with the following: 1.The minimum length of each EV space shall be 18 feet (5486 mm). 2.The minimum width of each EV space shall be 9 feet (2743 mm). 3.One in every 25 charging spaces, but not less than one, shall also have an 8-foot (2438 mm) wide minimum aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the minimum width of the EV space is 12 feet (3658 mm). a.Surface slope for this EV space and the aisle shall not exceed 1 unit vertical in 48 units horizontal (2.083 percent slope) in any direction. 4.106.4.2.2.1.3 Accessible EV spaces. In addition to the requirements in Sections 4.106.4.2.2.1.1 and 4.106.4.2.2.1.2, all EVSE, when installed, shall comply with the accessibility provisions for EV chargers in the California Building Code, Chapter 11B. EV ready spaces and EVCS in multifamily developments shall comply with California Building Code, Chapter 11A, Section 1109A. 4.106.4.2.3 EV space requirements. 1.Single EV space required. Install a listed raceway capable of accommodating a 208/240-volt dedicated branch circuit. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main service or subpanel and shall terminate into a listed cabinet, box or enclosure in close proximity to the location or the proposed location of the EV space. Construction documents shall identify the raceway termination point, receptacle or charger location, as applicable. The service panel and/ or subpanel shall have a 40-ampere minimum dedicated branch circuit, including branch circuit overcurrent protective device installed, or space(s) reserved to permit installation of a branch circuit overcurrent protective device. Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the location or the proposed location of the EV space, at the time of original construction in accordance with the California Electrical Code. 2.Multiple EV spaces required. Construction documents shall indicate the raceway termination point and the location of installed or future EV spaces, receptacles or EV chargers. Construction documents shall also provide information on amperage of installed or future receptacles or EVSE, raceway method(s), wiring schematics and electrical load calculations. Plan design shall be based upon a 40-ampere minimum branch circuit. Required raceways and related components that are planned to be installed underground, enclosed, inaccessible or in concealed areas and spaces shall be installed at the time of original construction. SECTION 4.501 GENERAL 4.501.1 Scope The provisions of this chapter shall outline means of reducing the quality of air contaminants that are odorous, irritating and/or harmful to the comfort and well being of a building's installers, occupants and neighbors. SECTION 4.502 DEFINITIONS 5.102.1 DEFINITIONS The following terms are defined in Chapter 2 (and are included here for reference) AGRIFIBER PRODUCTS. Agrifiber products include wheatboard, strawboard, panel substrates and door cores, not including furniture, fixtures and equipment (FF&E) not considered base building elements. COMPOSITE WOOD PRODUCTS. Composite wood products include hardwood plywood, particleboard and medium density fiberboard. "Composite wood products" does not include hardboard, structural plywood, structural panels, structural composite lumber, oriented strand board, glued laminated timber, prefabricated wood I-joists or finger-jointed lumber, all as specified in California Code of regulations (CCR), title 17, Section 93120.1. DIRECT-VENT APPLIANCE. A fuel-burning appliance with a sealed combustion system that draws all air for combustion from the outside atmosphere and discharges all flue gases to the outside atmosphere. DISCLAIMER:THIS DOCUMENT IS PROVIDED AND INTENDED TO BE USED AS A MEANS TO INDICATE AREAS OF COMPLIANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS (CALGREEN) CODE. DUE TO THE VARIABLES BETWEEN BUILDING DEPARTMENT JURISDICTIONS, THIS CHECKLIST IS TO BE USED ON AN INDIVIDUAL PROJECT BASIS AND MAY BE MODIFIED BY THE END USER TO MEET THOSE INDIVIDUAL NEEDS. THE END USER ASSUMES ALL RESPONSIBILITY ASSOCIATED WITH THE USE OF THIS DOCUMENT, INCLUDING VERIFICATION WITH THE FULL CODE. Y N/AYN/AYN/AYN/A RESPON. PARTY RESPON. PARTY RESPON. PARTY RESPON. PARTY 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES, SHEET 1 (January 2023)Y = YES N/A =NOT APPLICABLE RESPON. PARTY =RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER, OWNER, CONTRACTOR, INSPECTOR ETC.) 4.201 GENERAL 4.201.1 SCOPE. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards. DIVISION 4.2 ENERGY EFFICIENCY TABLE H-2 STANDARDS FOR COMMERCIAL PRE-RINSE SPRAY VALUES MANUFACTURED ON OR AFTER JANUARY 28, 2019 PRODUCT CLASS [spray force in ounce force (ozf)]MAXIMUM FLOW RATE (gpm) Product Class 1 (≤1.00 Product Class 2 (> 5.0 ozf and ≤1.20 Product Class 3 (> 8.0 ozf)1.28 Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the location or the proposed location of the EV space at the time of original construction in accordance with the California Electrical Code. 4.106.4.2.4 Identification. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code. 4.106.4.2.5 Electric Vehicle Ready Space Signage. Electric vehicle ready spaces shall be identified by signage or pavement markings, in compliance with Caltrans Traffic Operations Policy Directive 13-01 (Zero Emission Vehicle Signs and Pavement Markings) or its successor(s). 4.106.4.3 Electric vehicle charging for additions and alterations of parking facilities serving existing multifamily buildings. When new parking facilities are added, or electrical systems or lighting of existing parking facilities are added or altered and the work requires a building permit, ten (10) percent of the total number of parking spaces added or altered shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE. Notes: 1.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating future EV charging. 2.There is no requirement for EV spaces to be constructed or available until EV chargers are installed for use. x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x x x x x x x x OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U GR E E N B U I L D I N G ST A N D A R D S C O D E SHEET T5 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 MAXIMUM INCREMENTAL REACTIVITY (MIR). The maximum change in weight of ozone formed by adding a compound to the "Base Reactive Organic Gas (ROG) Mixture" per weight of compound added, expressed to hundredths of a gram (g O³/g ROC). Note: MIR values for individual compounds and hydrocarbon solvents are specified in CCR, Title 17, Sections 94700 and 94701. MOISTURE CONTENT. The weight of the water in wood expressed in percentage of the weight of the oven-dry wood. PRODUCT-WEIGHTED MIR (PWMIR). The sum of all weighted-MIR for all ingredients in a product subject to this article. The PWMIR is the total product reactivity expressed to hundredths of a gram of ozone formed per gram of product (excluding container and packaging). Note: PWMIR is calculated according to equations found in CCR, Title 17, Section 94521 (a). REACTIVE ORGANIC COMPOUND (ROC). Any compound that has the potential, once emitted, to contribute to ozone formation in the troposphere. VOC. A volatile organic compound (VOC) broadly defined as a chemical compound based on carbon chains or rings with vapor pressures greater than 0.1 millimeters of mercury at room temperature. These compounds typically contain hydrogen and may contain oxygen, nitrogen and other elements. See CCR Title 17, Section 94508(a). 4.503 FIREPLACES 4.503.1 GENERAL. Any installed gas fireplace shall be a direct-vent sealed-combustion type. Any installed woodstove or pellet stove shall comply with U.S. EPA New Source Performance Standards (NSPS) emission limits as applicable, and shall have a permanent label indicating they are certified to meet the emission limits. Woodstoves, pellet stoves and fireplaces shall also comply with applicable local ordinances. 4.504 POLLUTANT CONTROL 4.504.1 COVERING OF DUCT OPENINGS & PROTECTION OF MECHANICAL EQUIPMENT DURING CONSTRUCTION. At the time of rough installation, during storage on the construction site and until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to reduce the amount of water, dust or debris which may enter the system. 4.504.2 FINISH MATERIAL POLLUTANT CONTROL. Finish materials shall comply with this section. 4.504.2.1 Adhesives, Sealants and Caulks. Adhesives, sealant and caulks used on the project shall meet the requirements of the following standards unless more stringent local or regional air pollution or air quality management district rules apply: 1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable or SCAQMD Rule 1168 VOC limits, as shown in Table 4.504.1 or 4.504.2, as applicable. Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and tricloroethylene), except for aerosol products, as specified in Subsection 2 below. 2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than 1 pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with section 94507. 4.504.2.2 Paints and Coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Suggested Control Measure, as shown in Table 4.504.3, unless more stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table 4.504.3 shall be determined by classifying the coating as a Flat, Nonflat or Nonflat-High Gloss coating, based on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air Resources Board, Suggested Control Measure, and the corresponding Flat, Nonflat or Nonflat-High Gloss VOC limit in Table 4.504.3 shall apply. 4.504.2.3 Aerosol Paints and Coatings. Aerosol paints and coatings shall meet the Product-weighted MIR Limits for ROC in Section 94522(a)(2) and other requirements, including prohibitions on use of certain toxic compounds and ozone depleting substances, in Sections 94522(e)(1) and (f)(1) of California Code of Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation 8, Rule 49. 4.504.2.4 Verification. Verification of compliance with this section shall be provided at the request of the enforcing agency. Documentation may include, but is not limited to, the following: 1. Manufacturer's product specification. 2. Field verification of on-site product containers. CHAPTER 7 INSTALLER & SPECIAL INSPECTOR QUALIFICATIONS 702 QUALIFICATIONS 702.1 INSTALLER TRAINING. HVAC system installers shall be trained and certified in the proper installation of HVAC systems including ducts and equipment by a nationally or regionally recognized training or certification program. Uncertified persons may perform HVAC installations when under the direct supervision and responsibility of a person trained and certified to install HVAC systems or contractor licensed to install HVAC systems. Examples of acceptable HVAC training and certification programs include but are not limited to the following: 1. State certified apprenticeship programs. 2. Public utility training programs. 3. Training programs sponsored by trade, labor or statewide energy consulting or verification organizations. 4. Programs sponsored by manufacturing organizations. 5. Other programs acceptable to the enforcing agency. 702.2 SPECIAL INSPECTION [HCD]. When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition to other certifications or qualifications acceptable to the enforcing agency, the following certifications or education may be considered by the enforcing agency when evaluating the qualifications of a special inspector: 1. Certification by a national or regional green building program or standard publisher. 2. Certification by a statewide energy consulting or verification organization, such as HERS raters, building performance contractors, and home energy auditors. 3. Successful completion of a third party apprentice training program in the appropriate trade. 4. Other programs acceptable to the enforcing agency. Notes: 1. Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code. 2. HERS raters are special inspectors certified by the California Energy Commission (CEC) to rate homes in California according to the Home Energy Rating System (HERS). [BSC] When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a recognized state, national or international association, as determined by the local agency. The area of certification shall be closely related to the primary job function, as determined by the local agency. Note: Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code. 703 VERIFICATIONS 703.1 DOCUMENTATION. Documentation used to show compliance with this code shall include but is not limited to, construction documents, plans, specifications, builder or installer certification, inspection reports, or other methods acceptable to the enforcing agency which demonstrate substantial conformance. When specific documentation or special inspection is necessary to verify compliance, that method of compliance will be specified in the appropriate section or identified applicable checklist. 4.505 INTERIOR MOISTURE CONTROL 4.505.1 General. Buildings shall meet or exceed the provisions of the California Building Standards Code. 4.505.2 CONCRETE SLAB FOUNDATIONS. Concrete slab foundations required to have a vapor retarder by California Building Code, Chapter 19, or concrete slab-on-ground floors required to have a vapor retarder by the California Residential Code, Chapter 5, shall also comply with this section. 4.505.2.1 Capillary break. A capillary break shall be installed in compliance with at least one of the following: 1. A 4-inch (101.6 mm) thick base of 1/2 inch (12.7mm) or larger clean aggregate shall be provided with a vapor barrier in direct contact with concrete and a concrete mix design, which will address bleeding, shrinkage, and curling, shall be used. For additional information, see American Concrete Institute, ACI 302.2R-06. 2. Other equivalent methods approved by the enforcing agency. 3. A slab design specified by a licensed design professional. 4.505.3 MOISTURE CONTENT OF BUILDING MATERIALS. Building materials with visible signs of water damage shall not be installed. Wall and floor framing shall not be enclosed when the framing members exceed 19 percent moisture content. Moisture content shall be verified in compliance with the following: 1. Moisture content shall be determined with either a probe-type or contact-type moisture meter.Equivalent moisture verification methods may be approved by the enforcing agency and shall satisfy requirements found in Section 101.8 of this code. 2. Moisture readings shall be taken at a point 2 feet (610 mm) to 4 feet (1219 mm) from the grade stamped end of each piece verified. 3. At least three random moisture readings shall be performed on wall and floor framing with documentation acceptable to the enforcing agency provided at the time of approval to enclose the wall and floor framing. Insulation products which are visibly wet or have a high moisture content shall be replaced or allowed to dry prior to enclosure in wall or floor cavities. Wet-applied insulation products shall follow the manufacturers' drying recommendations prior to enclosure. 4.506 INDOOR AIR QUALITY AND EXHAUST 4.506.1 Bathroom exhaust fans. Each bathroom shall be mechanically ventilated and shall comply with the following: 1. Fans shall be ENERGY STAR compliant and be ducted to terminate outside the building. 2. Unless functioning as a component of a whole house ventilation system, fans must be controlled by a humidity control. a. Humidity controls shall be capable of adjustment between a relative humidity range less than or equal to 50% to a maximum of 80%. A humidity control may utilize manual or automatic means of adjustment. b. A humidity control may be a separate component to the exhaust fan and is not required to be integral (i.e., built-in) Notes: 1. For the purposes of this section, a bathroom is a room which contains a bathtub, shower or tub/shower combination. 2. Lighting integral to bathroom exhaust fans shall comply with the California Energy Code. 4.507 ENVIRONMENTAL COMFORT 4.507.2 HEATING AND AIR-CONDITIONING SYSTEM DESIGN. Heating and air conditioning systems shall be sized, designed and have their equipment selected using the following methods: 1. The heat loss and heat gain is established according to ANSI/ACCA 2 Manual J - 2011 (Residential Load Calculation), ASHRAE handbooks or other equivalent design software or methods. 2. Duct systems are sized according to ANSI/ACCA 1 Manual D - 2014 (Residential Duct Systems), ASHRAE handbooks or other equivalent design software or methods. 3. Select heating and cooling equipment according to ANSI/ACCA 3 Manual S - 2014 (Residential Equipment Selection), or other equivalent design software or methods. Exception: Use of alternate design temperatures necessary to ensure the system functions are acceptable. TABLE 4.504.1 - ADHESIVE VOC LIMIT1,2 (Less Water and Less Exempt Compounds in Grams per Liter) ARCHITECTURAL APPLICATIONS VOC LIMIT INDOOR CARPET ADHESIVES 50 CARPET PAD ADHESIVES 50 OUTDOOR CARPET ADHESIVES 150 WOOD FLOORING ADHESIVES 100 RUBBER FLOOR ADHESIVES 60 SUBFLOOR ADHESIVES 50 CERAMIC TILE ADHESIVES 65 VCT & ASPHALT TILE ADHESIVES 50 DRYWALL & PANEL ADHESIVES 50 COVE BASE ADHESIVES 50 MULTIPURPOSE CONSTRUCTION ADHESIVE 70 STRUCTURAL GLAZING ADHESIVES 100 SINGLE-PLY ROOF MEMBRANE ADHESIVES 250 OTHER ADHESIVES NOT LISTED 50 SPECIALTY APPLICATIONS PVC WELDING 510 CPVC WELDING 490 ABS WELDING 325 PLASTIC CEMENT WELDING 250 ADHESIVE PRIMER FOR PLASTIC 550 CONTACT ADHESIVE 80 SPECIAL PURPOSE CONTACT ADHESIVE 250 STRUCTURAL WOOD MEMBER ADHESIVE 140 TOP & TRIM ADHESIVE 250 SUBSTRATE SPECIFIC APPLICATIONS METAL TO METAL 30 PLASTIC FOAMS 50 POROUS MATERIAL (EXCEPT WOOD)50 WOOD 30 FIBERGLASS 80 1. IF AN ADHESIVE IS USED TO BOND DISSIMILAR SUBSTRATES TOGETHER, THE ADHESIVE WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED. 2. FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE THE VOC CONTENT SPECIFIED IN THIS TABLE, SEE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT RULE 1168. TABLE 4.504.2 - SEALANT VOC LIMIT (Less Water and Less Exempt Compounds in Grams per Liter) SEALANTS VOC LIMIT ARCHITECTURAL 250 MARINE DECK 760 NONMEMBRANE ROOF 300 ROADWAY 250 SINGLE-PLY ROOF MEMBRANE 450 OTHER 420 SEALANT PRIMERS ARCHITECTURAL NON-POROUS 250 POROUS 775 MODIFIED BITUMINOUS 500 MARINE DECK 760 OTHER 750 TABLE 4.504.5 - FORMALDEHYDE LIMITS1 MAXIMUM FORMALDEHYDE EMISSIONS IN PARTS PER MILLION PRODUCT CURRENT LIMIT HARDWOOD PLYWOOD VENEER CORE 0.05 HARDWOOD PLYWOOD COMPOSITE CORE 0.05 PARTICLE BOARD 0.09 MEDIUM DENSITY FIBERBOARD 0.11 THIN MEDIUM DENSITY FIBERBOARD2 0.13 1. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIF. AIR RESOURCES BOARD, AIR TOXICS CONTROL MEASURE FOR COMPOSITE WOOD AS TESTED IN ACCORDANCE WITH ASTM E 1333. FOR ADDITIONAL INFORMATION, SEE CALIF. CODE OF REGULATIONS, TITLE 17, SECTIONS 93120 THROUGH 93120.12. 2. THIN MEDIUM DENSITY FIBERBOARD HAS A MAXIMUM THICKNESS OF 5/16" (8 MM). TABLE 4.504.3 - VOC CONTENT LIMITS FOR ARCHITECTURAL COATINGS2,3 GRAMS OF VOC PER LITER OF COATING, LESS WATER & LESS EXEMPT COMPOUNDS COATING CATEGORY VOC LIMIT FLAT COATINGS 50 NON-FLAT COATINGS 100 NONFLAT-HIGH GLOSS COATINGS 150 SPECIALTY COATINGS ALUMINUM ROOF COATINGS 400 BASEMENT SPECIALTY COATINGS 400 BITUMINOUS ROOF COATINGS 50 BITUMINOUS ROOF PRIMERS 350 BOND BREAKERS 350 CONCRETE CURING COMPOUNDS 350 CONCRETE/MASONRY SEALERS 100 DRIVEWAY SEALERS 50 DRY FOG COATINGS 150 FAUX FINISHING COATINGS 350 FIRE RESISTIVE COATINGS 350 FLOOR COATINGS 100 FORM-RELEASE COMPOUNDS 250 GRAPHIC ARTS COATINGS (SIGN PAINTS)500 HIGH TEMPERATURE COATINGS 420 INDUSTRIAL MAINTENANCE COATINGS 250 LOW SOLIDS COATINGS1 120 MAGNESITE CEMENT COATINGS 450 MASTIC TEXTURE COATINGS 100 METALLIC PIGMENTED COATINGS 500 MULTICOLOR COATINGS 250 PRETREATMENT WASH PRIMERS 420 PRIMERS, SEALERS, & UNDERCOATERS 100 REACTIVE PENETRATING SEALERS 350 RECYCLED COATINGS 250 ROOF COATINGS 50 RUST PREVENTATIVE COATINGS 250 SHELLACS CLEAR 730 OPAQUE 550 SPECIALTY PRIMERS, SEALERS & UNDERCOATERS 100 STAINS 250 STONE CONSOLIDANTS 450 SWIMMING POOL COATINGS 340 TRAFFIC MARKING COATINGS 100 TUB & TILE REFINISH COATINGS 420 WATERPROOFING MEMBRANES 250 WOOD COATINGS 275 WOOD PRESERVATIVES 350 ZINC-RICH PRIMERS 340 1. GRAMS OF VOC PER LITER OF COATING, INCLUDING WATER & EXEMPT COMPOUNDS 2. THE SPECIFIED LIMITS REMAIN IN EFFECT UNLESS REVISED LIMITS ARE LISTED IN SUBSEQUENT COLUMNS IN THE TABLE. 3. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIFORNIA AIR RESOURCES BOARD, ARCHITECTURAL COATINGS SUGGESTED CONTROL MEASURE, FEB. 1, 2008. MORE INFORMATION IS AVAILABLE FROM THE AIR RESOURCES BOARD. DIVISION 4.5 ENVIRONMENTAL QUALITY (continued) 4.504.3 CARPET SYSTEMS. All carpet installed in the building interior shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx. 4.504.3.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx. 4.504.3.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table 4.504.1. 4.504.4 RESILIENT FLOORING SYSTEMS. Where resilient flooring is installed , at least 80% of floor area receiving resilient flooring shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. hhtps://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx. 4.504.5 COMPOSITE WOOD PRODUCTS. Hardwood plywood, particleboard and medium density fiberboard composite wood products used on the interior or exterior of the buildings shall meet the requirements for formaldehyde as specified in ARB's Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.), by or before the dates specified in those sections, as shown in Table 4.504.5 4.504.5.1 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following: 1. Product certifications and specifications. 2. Chain of custody certifications. 3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see CCR, Title 17, Section 93120, et seq.). 4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered Wood Association, the Australian AS/NZS 2269, European 636 3S standards, and Canadian CSA 0121, CSA 0151, CSA 0153 and CSA 0325 standards. 5. Other methods acceptable to the enforcing agency. DISCLAIMER:THIS DOCUMENT IS PROVIDED AND INTENDED TO BE USED AS A MEANS TO INDICATE AREAS OF COMPLIANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS (CALGREEN) CODE. DUE TO THE VARIABLES BETWEEN BUILDING DEPARTMENT JURISDICTIONS, THIS CHECKLIST IS TO BE USED ON AN INDIVIDUAL PROJECT BASIS AND MAY BE MODIFIED BY THE END USER TO MEET THOSE INDIVIDUAL NEEDS. THE END USER ASSUMES ALL RESPONSIBILITY ASSOCIATED WITH THE USE OF THIS DOCUMENT, INCLUDING VERIFICATION WITH THE FULL CODE. Y N/AYN/AYN/AYN/A RESPON. PARTY RESPON. PARTY RESPON. PARTY RESPON. PARTY 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES, SHEET 2 (January 2023)Y = YES N/A =NOT APPLICABLE RESPON. PARTY =RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER, OWNER, CONTRACTOR, INSPECTOR ETC.) x x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor x Contractor OW N E R TT S T A R S L L C TE L : ( 7 1 4 ) 5 4 8 1 7 1 1 PR O J E C T A D D R E S S MA I N U N I T : 2 4 2 2 W M A R T Y L N JA D U : 2 4 2 2 W M A R T Y L N , U N I T 2 AD U : 2 4 2 2 W M A R T Y L N , U N I T 3 SA N T A A N A , C A 9 2 7 0 6 DATE 2/20/2025 NE W A T T A C H E D 7 9 9 S F A D U AN D A T T A C H E D 4 3 1 S F J A D U O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Submittal Criteria Form Required for Single Family or Duplex Residences (Use Commercial form for lots with 3+ dwelling units or new residential tracts) Complete the Project Information and Questionnaire below, then sign and date the Applicant Certification. Project Information  New Single Family Residence/Duplex  Addition/Remodel  ADU  Other Address: Unit #: City or Unincorporated County Area: ZIP: Scope of Work: Existing Area: Area to be Added: Total Resulting Area: Stories: Area Added in Past 2 Years (excluding this project): Yes No Questionnaire OCFA Plan Type if “Yes” 1.   New – Is this a new single family residence or duplex? *(PR160) Residential Site with Water Availability (PR400-402) Fire Sprinkler 2.   ADU – Is this a new Accessory Dwelling Unit (ADU) on the same property as a house that already has fire sprinklers or a house that will have fire sprinklers added as part of this project? (PR400-402) Fire Sprinkler 3.   Addition – Is this (A) an addition to a currently sprinklered building, or (B) an addition requiring a fire sprinkler retrofit based on a threshold set by local ordinance? (PR400-402) Fire Sprinkler 4.   Distance – Is the most remote portion of the addition, ADU or other detached structure greater than 140-feet from the fire access roadway? *(PR160) Residential Site 5.   Total Area – Will the addition result in a total area of greater than 3,600 square feet (sf) for non- sprinklered buildings, or greater than 6,200 sf for sprinklered buildings, including the area of all enclosed spaces, such as garages, stairs, and detached structures separated by less than 10-feet? *(PR160) Residential Site with Water Availability 6.   Remodel – Is this a remodel of a sprinklered building with a scope of work that includes adding or removing any interior walls? Note: If “Yes”, then project must be evaluated by a C-16 licensed contractor to determine if a fire sprinkler modification is needed. (PR400-402) Fire Sprinkler 7.   Detached Structure – Is this a new detached utility or accessory structure (not an ADU), such as a garage, workshop, game room, pool house, barn, etc., requiring fire sprinklers based on a threshold set by local ordinance? *(PR160) Residential Site (PR400-402) Fire Sprinkler 8.   Gate – Is a gate being installed across a driveway or road that is designated as a fire department access roadway, or a driveway or road that serves more than a single home/duplex? (PR180) Gate 9.   Methane – Is project located in or less than 100’ from a “Division of Oil, Gas, and Geothermal Resources” (DOGGR) field boundary or well (active or abandoned), less than 300-feet from an oil/gas seep, or less than 1000-feet from a landfill? (Note: For projects in Yorba Linda, this requirement only applies to new homes, enclosed accessory structures, addition to existing structure greater than 1000 sf, and ADU’s). *(PR160) Residential Site *(PR172-174) Methane Test/Mitigation Plans 10.   Vegetation – Is the property/structure (A) on the perimeter of a community containing, or adjacent to slopes or hills, or (B) adjacent to an open space or wildland area containing non-irrigated vegetation, or (C) in a State Responsibility Area or Local Responsibility Area “Fire Hazard Severity Zone”, as defined by the State, or (D) near an area that could be affected by a wildfire in the open space. *(PR125) Fuel Modification (PR182) Accessory Structure *OCFA approval required before issuance of a grading/building permit. All other plans types may be deferred submittals. Applicant Certification I certify, under penalty of perjury, under the laws of the State of California, that the information above is true: Print Name:_______________________________________ Signature:___________________________________________ Date:______________ Phone Number:_____________________________________________ Email:_____________________________________________________________ Attention Building Department Staff – After you’ve verified all questions were answered accurately as “No”, then you may accept this signed form as a written release that an OCFA review is not required. If any questions were answered as “Yes”, then the plan type on the right side may be required. ______If all answers are “No” and the Building Department still requires the applicant to have their plans reviewed by OCFA, or if any answers are “Yes” and the Building Department prefers for OCFA to determine if a review is required, please initial this line and provide an explanation on the Plan Referral Form (on the reverse), to be submitted along with the appropriate plans to OCFA for a determination. For questions and submittal information, please visit ocfa.org, or call OCFA at (714) 573-6100 SFR O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Referral Form Required for OCFA to review plans upon the request of the Building Department when the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”. City Official Requesting Review: City Reference #: __________________________ City / County: _____________________________________ Date: __________________________________ Contact Name: _____________________________________ E-Mail: __________________________________ Title: _____________________________________ Phone #: _________________________________ ** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. ** Reason(s) for Review: Please describe why OCFA Plan Review is or may be required by the City/County: OCFA COMMENTS:  No further action required on this specific plan type, based on information provided on: ____/______/______.  Project to be taken in for OCFA Review. Other: Name: _________________________________________ Contact #: ______________________________________ Date: _________________________________ OCFA Authorization Updated: 06/02/2020 rs O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Submittal Criteria Form Required for Single Family or Duplex Residences (Use Commercial form for lots with 3+ dwelling units or new residential tracts) Complete the Project Information and Questionnaire below, then sign and date the Applicant Certification. Project Information  New Single Family Residence/Duplex  Addition/Remodel  ADU  Other Address: Unit #: City or Unincorporated County Area: ZIP: Scope of Work: Existing Area: Area to be Added: Total Resulting Area: Stories: Area Added in Past 2 Years (excluding this project): Yes No Questionnaire OCFA Plan Type if “Yes” 1.   New – Is this a new single family residence or duplex? *(PR160) Residential Site with Water Availability (PR400-402) Fire Sprinkler 2.   ADU – Is this a new Accessory Dwelling Unit (ADU) on the same property as a house that already has fire sprinklers or a house that will have fire sprinklers added as part of this project? (PR400-402) Fire Sprinkler 3.   Addition – Is this (A) an addition to a currently sprinklered building, or (B) an addition requiring a fire sprinkler retrofit based on a threshold set by local ordinance? (PR400-402) Fire Sprinkler 4.   Distance – Is the most remote portion of the addition, ADU or other detached structure greater than 140-feet from the fire access roadway? *(PR160) Residential Site 5.   Total Area – Will the addition result in a total area of greater than 3,600 square feet (sf) for non- sprinklered buildings, or greater than 6,200 sf for sprinklered buildings, including the area of all enclosed spaces, such as garages, stairs, and detached structures separated by less than 10-feet? *(PR160) Residential Site with Water Availability 6.   Remodel – Is this a remodel of a sprinklered building with a scope of work that includes adding or removing any interior walls? Note: If “Yes”, then project must be evaluated by a C-16 licensed contractor to determine if a fire sprinkler modification is needed. (PR400-402) Fire Sprinkler 7.   Detached Structure – Is this a new detached utility or accessory structure (not an ADU), such as a garage, workshop, game room, pool house, barn, etc., requiring fire sprinklers based on a threshold set by local ordinance? *(PR160) Residential Site (PR400-402) Fire Sprinkler 8.   Gate – Is a gate being installed across a driveway or road that is designated as a fire department access roadway, or a driveway or road that serves more than a single home/duplex? (PR180) Gate 9.   Methane – Is project located in or less than 100’ from a “Division of Oil, Gas, and Geothermal Resources” (DOGGR) field boundary or well (active or abandoned), less than 300-feet from an oil/gas seep, or less than 1000-feet from a landfill? (Note: For projects in Yorba Linda, this requirement only applies to new homes, enclosed accessory structures, addition to existing structure greater than 1000 sf, and ADU’s). *(PR160) Residential Site *(PR172-174) Methane Test/Mitigation Plans 10.   Vegetation – Is the property/structure (A) on the perimeter of a community containing, or adjacent to slopes or hills, or (B) adjacent to an open space or wildland area containing non-irrigated vegetation, or (C) in a State Responsibility Area or Local Responsibility Area “Fire Hazard Severity Zone”, as defined by the State, or (D) near an area that could be affected by a wildfire in the open space. *(PR125) Fuel Modification (PR182) Accessory Structure *OCFA approval required before issuance of a grading/building permit. All other plans types may be deferred submittals. Applicant Certification I certify, under penalty of perjury, under the laws of the State of California, that the information above is true: Print Name:_______________________________________ Signature:___________________________________________ Date:______________ Phone Number:_____________________________________________ Email:_____________________________________________________________ Attention Building Department Staff – After you’ve verified all questions were answered accurately as “No”, then you may accept this signed form as a written release that an OCFA review is not required. If any questions were answered as “Yes”, then the plan type on the right side may be required. ______If all answers are “No” and the Building Department still requires the applicant to have their plans reviewed by OCFA, or if any answers are “Yes” and the Building Department prefers for OCFA to determine if a review is required, please initial this line and provide an explanation on the Plan Referral Form (on the reverse), to be submitted along with the appropriate plans to OCFA for a determination. For questions and submittal information, please visit ocfa.org, or call OCFA at (714) 573-6100 SFR O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Referral Form Required for OCFA to review plans upon the request of the Building Department when the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”. City Official Requesting Review: City Reference #: __________________________ City / County: _____________________________________ Date: __________________________________ Contact Name: _____________________________________ E-Mail: __________________________________ Title: _____________________________________ Phone #: _________________________________ ** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. ** Reason(s) for Review: Please describe why OCFA Plan Review is or may be required by the City/County: OCFA COMMENTS:  No further action required on this specific plan type, based on information provided on: ____/______/______.  Project to be taken in for OCFA Review. Other: Name: _________________________________________ Contact #: ______________________________________ Date: _________________________________ OCFA Authorization Updated: 06/02/2020 rs CITY OF SANTA ANA Planning and Building Agency Garden Grove Unified School District Certification of Compliance Payment of School Facility Fees Developer/Applicant Ua o Trml- Address 2 Z Cl b Telephone Number c/ / 7 Project Location Street Address,, OFFICE USE 4&4" Elem. School Int Ach! O. 84roved FOR PERMIT ISSUANCE 11 T S. S L L aster ID: >etif 1&j Aj,� 4.7 city High School ZIP rhomas Map No --------------------------- Number of Square Feet U of Residential Space ! X Total $ 3 U Number of Square Feet of Commercial and Industrial Space X i Total $ The above representations as to square footage are true. Developer/Applicant agrees that if it is later determined that such representations are not true then this certificate shall automatically terminate and the appropriate City/County shall be notified. Applicant is hereby noticed that any party filing a protest regarding the imposition of fees pursuant to Government Code Section 65995 and Education Code Section 17620 must do so within 90 days from the payment of the fee. 11 l 71 z Nate Devel K IApptfc—ant ----------------------------------------------------------------------------------------------------------- Receipt of Payment This certifies that the above -named Developer/Applicant has paid school facility fees in compliance with Government Code Section'(�OriJUA_ 655995 and Education Code Section 17620. onJ These fee have been received from 1 l rkTAl (f w �� Aa�u��`dollars $ Cash Check '---Check No. � Ban � �y Dat Superintend esignee Garden Grove UP(fi School District (714�663-6442 9703.69' (Rev. 6/14) Page 1 of 1 EXISTING ONE & TWO FAMILY DWELLINGS ELECTRICAL SERVICES UNDERGROUND EXCEPTION CEC 2022 ELC-04 All new utility connections are required to be installed below grade by Santa Ana Municipal Code 41- 626(b). There is a standing exception for one and two family dwellings. This exception applies only when the new electrical service is designed to be fed from below grade as well as overhead. This diagram is a typical unit. The utility is able to feed this cabinet from the top or the bottom without interfering with the distribution wiring. All the circuit breakers and branch circuits are contained in the circuit breaker side of this cabinet. Only listed combination overhead and underground feed service boxes may be used to connect to an overhead utility drop. This exception to an underground fed service applies only to existing single family and two family residences. Planning & Building Agency Permits & Plan Check Section 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 Rigid Conduit Service Entrance Conductor Riser Underground Service Lateral METER Rev. 1/21/2020 October 2, 2025 Project No. 17-00.15.47 Albert Luu 8563 Amazon River Cir. Fountain Valley, California Subject: Preliminary Foundation Investigation for Proposed Auxiliary Dwelling Unit (ADU) and Junior Auxiliary Dwelling Unit (JADU) to One-Story Single-Family-Home, 2422 W. Marty Lane, Santa Ana, California Introduction This report presents the results of our preliminary foundation investigation for proposed ADU and JADU to a one-story single-family-home at 2422 W. Marty Lane, Santa Ana, California (see Figure 1). The purpose of the preliminary foundation investigation is to provide preliminary geotechnical design parameters for the foundation of the above-mentioned proposed structures. The proposed structures will be wood-frame one-story-structures that are supported by conventional slabs and perimeter footings. The total area of the proposed one-story ADU and JADU will be about 799 and 431 sqft, respectively. We anticipate that cut and/or fill will be minor (less than 2 feet thick). The sites of the proposed structures are covered by concrete tiles and landscape area. The sites are located in the back yard and side yard of the existing single family residence. The sites are relatively flat areas. The property is bounded to the north by Marty Lane and to the other sides by other residential properties. The overall area is also a relatively flat area. Scope of Work The scope of work for this preliminary foundation investigation consisted of the following: • Field exploration, consisting of drilling and logging of one boring to a depth of 5 feet; • Laboratory testing of selected soil samples considered representative of the subsurface conditions to evaluate the pertinent engineering and physical characteristics of the representative soils; • Engineering analyses of the collected data to develop geotechnical parameters for foundation design of the proposed new structures; and • Preparation of this report presenting our findings, conclusions, and recommendations. 2422 W. Marty Lane October 2, 2025 Page: 2 Field Exploration and Laboratory Testing Field Exploration. The subsurface conditions were explored by drilling one boring by means of a handheld auger. The depth of the boring is about 5 feet below the existing ground surface. The approximate location of the boring is shown on the Boring Location Map in Figure 2. Groundwater was not encountered during our drilling. Details of the field exploration, including the log of the boring, are presented in Appendix A. Laboratory Testing. Soil samples considered representative of the subsurface conditions were tested to obtain or derive relevant physical and engineering soil properties. Laboratory testing included moisture content and insitu density, expansion index and sieve analyses. Moisture content and insitu density test results are shown in the Boring Logs in Appendix A. The remaining laboratory test results are presented in Appendix B. Descriptions of the test methods are also included in Appendix B. Subsurface Soil Conditions The subject site of the proposed ADU is predominantly underlain by silty sand with trace of fine gravel. The consistency of the encountered subsurface soils materials is medium dense with damp moisture content. No groundwater was encountered during our drilling. Conclusions and Recommendations 1. Foundation and Slab Design The proposed development will not have an adverse impact on the existing nearby structures. The proposed site is suitable for the intended use provided all the following recommendations are implemented. The following foundation recommendations were prepared without any information about the maximum and average column loads of the new building. Once the information is available, the following recommendations may be revised to reflect the actual conditions of the proposed building. The foundation criteria given below have been generally observed to be practical in mitigating the potential structural damage due to very low soil expansion. 2422 W. Marty Lane October 2, 2025 Page: 3 Additional expansion index tests need to be performed after completion of pad to verify that the expansion index of the underlying soils is as stated above. If the test results indicate that the underlying soils are not classified as very low expansive soils for the area of the proposed slab-on- grade, the recommendations below should be adjusted accordingly. Other professionals in the design team may have different concerns depending on their own discipline and experience. Therefore, our recommendations should be considered as minimum and should be superseded by more restrictive recommendations of other members of the design team or the governing agencies, if applicable. Footing Design. The following minimum criteria should be adopted for the footing design: a. Allowable Bearing Capacity: qall = 1,500 psf b. Minimum Footing Width: 12 inches c. Minimum Footing Depth: 18 inches d. Minimum Reinforcement: 2 # 5 bars at both the top and bottom in continuous footings Notes: i. Depth of footing is measured from the lowest adjacent grade. ii. Allowable bearing capacity may be increased by one-third for short-term wind or seismic loads. iii. The above-mentioned footing dimensions recommendations should not be considered to preclude more restrictive criteria of regulating agencies or by the structural engineer/architect. iv. The design of the foundation system should be performed by the project structural engineer, incorporating the geotechnical parameters described above. Slab Design. The following recommendations should be incorporated for the slab-on-grade design: a. The minimum thickness of slab-on-grade should be 5 inches. b. The minimum steel reinforcement for slab-on-grade should be # 4 located at mid- height on 18-inch centers both ways (or equivalent). c. A modulus of subgrade reaction of 100 lb/in2/in may be utilized for the slab design d. Moisture barrier (visqueen) of a minimum 10-mil thick should be placed-in below the slab; and located in middle of a minimum of 4 inch thick of sand that is placed underneath the slab in accordance with an equivalent method specified in Section 4.505.2.1 of the California Green Code. Concrete Flatworks. The minimum thickness for concrete flatworks is 4 inches in order to minimize potential for excessive cracks. In addition, construction joints or weakened plane joints should be provided at 6-foot frequent intervals. 2422 W. Marty Lane October 2, 2025 Page: 4 Cement Type. Based on the type of subsurface soils, Type V cement and water-cement ratio of 0.45 or less may be used for concrete in contact with the on-site soils. 2. Seismic Design The most widely used technique for earthquake-resistant design applied to low-rise structures is the California Building Code (CBC). The basic formulas used in the CBC require determination of the site class, which represents the site soil properties at the site of interest. The 2022 CBC seismic zone for use in the seismic design formula is Site Class D. The Seismic Design Maps is included in Appendix C. According to Section 1803.5.12 of 2022 CBC, the potential consequences of liquefaction and soil strength loss are total and differential settlements, lateral soil movement, lateral soil loads on foundation, reduction in foundation soil-bearing capacity and lateral soil reaction and flotation of buried structures. Each and/or combination of these potential consequences of liquefaction and soil strength loss may create significant distresses to the proposed ADU and JADU. The proposed ADU and JADU maybe inhabitable and need major repair/reconstruction. The owner should be solely responsible to repair/reconstruct due to distresses from consequences of liquefaction and soil strength loss. In the case of an earthquake event on any one of several active faults in the nearby area, the site would be subjected to strong ground motion. This hazard is not unique to this site, but is endemic to all areas in Southern California region. 3. Grading and Earthwork Overexcavation/Removals. The upper 24 to 36 inches of the subsurface soil materials under the proposed location of the proposed slabs may consist of uncertified fills, roots, organic and/or be disturbed. Therefore, we recommend that all deleterious materials including concrete are discarded off site and the upper 36 inches of the subsurface materials be removed and replaced with compacted fills. Onsite soils may be reused provided all deleterious materials are removed. The extent of the removal should be within the proposed concrete slabs footprint and 3 feet beyond it, if possible. The removal bottom and compacted fill should be prepared in accordance with the recommendations stated below. Site Preparation. Vegetation, organic soil, roots and other unsuitable material should be removed from the proposed new structure. Fill Compaction. All fill and backfill to be placed in association with site development should be accomplished at slightly over optimum moisture conditions, if any. The minimum relative compaction recommended for fill is 90 percent relative compaction based on maximum dry density performed in accordance with ASTM D-1557. Fill should be compacted by mechanical means in uniform horizontal loose lifts not exceeding 8 inches in thickness. 2422 W. Marty Lane October 2, 2025 Page: 5 Fill Material. The on-site soils can be used for compacted fill. However, during grading operations, soil types other than those analyzed in the geotechnical reports may be encountered by the contractor. The geotechnical consultant should be notified to evaluate the suitability of those soils for use as fill and as finished grade soils. Imported fill materials should be approved by the Geotechnical Engineer prior to importing. Soils exhibiting any expansion potential should not be used as import materials. Both imported and on- site soils to be used as fill materials should be free of debris, organic and cobbles over 6 inches in maximum dimension. Site Drainage. Foundation and slab performance depends greatly on how well runoff waters drain from the site. This is true both during construction and over the entire life of the structure. The ground surface around structures should be graded so that water flows rapidly away from the structures without ponding. The surface gradient needed to achieve this depends on the type of landscaping. In general, we recommend impermeable areas such as paved and concrete flatwork within a minimum distance of 10 feet from a building (measured perpendicular to the face of the wall) should be sloped away at a minimum gradient of 2%. Other areas such as lawn and vegetated areas should have minimum descending gradients of at least 5% within 10 feet of the building (measured perpendicular to the face of the wall). Utility Trenches. Bedding materials should consist of sand having Sand Equivalent not less than 30, which may then be jetted. Existing soils may be utilized for trench backfill provided they are free of organic materials and rocks over 6 inches in dimension. The backfill should be uniformly compacted to at least 90% relative compaction based on maximum density performed in accordance with ASTM D-1557. Excavation. Excavation within 3 feet from the existing building should be limited to 24 inches deep. Otherwise, underpinning of the existing foundations may be warranted. 4. Review of Plans The geotechnical consultant should review the final construction plans and specifications in order to confirm that the general intent of the recommendations contained in this report have been incorporated into the final plans and design documents. Also, the plans will be compared to the preliminary plans used in the preparation of this report in order to evaluate the effect of any major changes with respect to the geotechnical recommendations given in this report. 2422 W. Marty Lane October 2, 2025 Page: 6 5. Geotechnical Observation and Testing The findings, conclusions and recommendations in this report are based upon interpretation of data and data points having limited spacial extent. Verifications and refinement of actual geotechnical conditions during grading is very important. At minimum, geotechnical observation and testing should be conducted by the geotechnical consultant during the following stages of grading and construction: • Upon completion of remedial removals, prior to fill placement, if any • During removal bottom scarification, if any • During fill placement, if any • Upon completion of any footing excavation prior to pouring concrete • During backfilling of any utility trenches • When any unusual conditions are encountered The geotechnical engineering firm providing geotechnical observation/testing shall assume the responsibility of Geotechnical Engineer of Record. If you have any questions regarding this report, please call us. We appreciate the opportunity to be of service. Sincerely, TORO INTERNATIONAL Hantoro Walujono, GE 2164 Principal Attachments: Figure 1: Site Location Map Figure 2: Boring Location Map Appendix A: Boring Logs Appendix B: Laboratory Test Results Appendix C: Seismic Design Maps References: 1. California Building Code (CBC), 2022 2. California Green Code, 2016. EXP. 3/31/27 FIGURE 1 SITE LOCATION MAP 2422 W. MARTY LANE Geotechnical Engineering PROJECT No.17-00.15.47 TORO INTERNATIONAL FIGURE 2 BORING LOCATION MAP 2422 W. MARTY LANE Geotechnical Engineering PROJECT NO. 17-00.15.47 TORO INTERNATIONAL LEGEND Approximate Location of Boring B-1 B-1 B-1 APPENDIX A - BORING LOGS APPENDIX A - Field Exploration Subsurface conditions were explored on September 25, 2025 by drilling one boring to a maximum depth of approximately 5 feet. The borehole was advanced by a handheld auger. The drilled borehole was located in the field by tape measurements from known landmarks. Its location as shown is therefore within the accuracy of such measurements. The field explorations were performed under supervision of our engineer who prepared detailed log of the boring, classified the soil encountered, and obtained soil samples for laboratory testing. The soils were classified based on visual observations during the field investigation and results of the laboratory testing. Soil classifications were conducted in accordance with the Unified Soil Classification System. TORO INTERNATIONAL GEOTECHNICAL ENGINEERING Site Name 2422 W. Marty Lane Site Address 2422 W. Marty Lane, Santa Ana Project Number 17-00.15.47 Date September 25, 2025 Equipment Hollow Stem Flight Auger Drive Weight - Average Drop -Elevation (ft)114 (Assumed) Hole Diameter 4 inches Eng/Geologist HW De p t h , f t El e v , f t Gr a p h i c Lo g Sa m p l e N o . Dr i v e S a m p l e Bl o w s / f t Dr y D e n , p c f Mo i s t u r e , % U. S . C . S . GEOTECHNICAL DESCRIPTION B-1 - - 2.8 SM @ 1': Brown fine silty sand with trace of fine gravel, damp, medium dense S-2 - - 2.4 SM @ 2': same as before except fine to medium grained silty sand -- - 5 109 S-4 - - 4.2 SM @ 4': same as before Total Depth: 5 feet 10 104 15 99 20 94 25 89 30 84 BORING NO. B-1 Sheet 1 of 1 APPENDIX B - LABORATORY TEST RESULTS APPENDIX B - LABORATORY TESTING PROCEDURES AND RESULTS Moisture Content and Dry Density Moisture content was determined for small bulk and relatively undisturbed ring samples. Dry Density was determined for relatively undisturbed ring samples only. The test procedure is in accordance with ASTM 2216-90. The results of moisture content and dry density are presented in the Boring Logs. Expansion Index Expansion Index tests were performed in accordance with ASTM D 4829. The results of the tests are shown in Table B-1. Sieve Analyses Sieve analyses were performed on granular materials in accordance with ASTM D 422. Graphs showing relationship of the various sizes of soil particles versus the percentage passing are shown in Figure B-1. TABLE B-1. EXPANSION INDEX TEST RESULTS Boring Number Depth (feet) Soil Description Expansion Index Expansion Potential B-1 0-5 Brown Silty Sand 14 Very Low Sample Depth Percent Passing (ft) No. 200 Sieve B-1 S-3 3 16.6 SM Project Name: 2422 W. Marty Lane Project No.: 17-00.15.47 Figure: B-1 TORO INTERNATIONAL GRAIN SIZE DISTRIBUTION CURVE ASTM D422 Boring No. Sample No. Soil Type 0 10 20 30 40 50 60 70 80 90 100 0.0010.010.1110100 Particle Diameter in Millimeters Pe r c e n t P a s s i n g b y W e i g h t APPENDIX C ASCE 7 HAZARDS REPORT ASCE Hazards Report Address: 2422 Marty Ln Santa Ana, California 92706 Standard:ASCE/SEI 7-16 Latitude:33.769211 Risk Category:II Longitude:-117.902479 Soil Class:D - Stiff Soil Elevation:108.80421814052751 ft (NAVD 88) Page 1 of 3https://ascehazardtool.org/Wed Oct 01 2025 SS : 1.34 S1 : 0.476 F a : 1 F v : N/A SMS : 1.34 SM1 : N/A SDS : 0.893 SD1 : N/A T L : 8 PGA : 0.568 PGA M : 0.625 F PGA : 1.1 Ie : 1 C v : 1.368 Seismic Site Soil Class: Results: Data Accessed: Date Source: D - Stiff Soil USGS Seismic Design Maps Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8. Wed Oct 01 2025 Page 2 of 3https://ascehazardtool.org/Wed Oct 01 2025 The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE. ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE standard. In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE Hazard Tool. Page 3 of 3https://ascehazardtool.org/Wed Oct 01 2025 STRtJCTURAL CALCULATIONS Date: 06/30/2025 Project Location: Owner: Prepared by: Huilding Code Edition: Concrete: l:oundation: Structural Steel: Pipe Columns: Weiding: Concrete Masonry: Groul: Reinl(n·cing Steel: Wood Framing: Studs, joists, rafters: Beams and posts: G !u lam: Parallam 2.0 PSL: Microllarn LVL: Plywood: TJI: 2422 W. Marty Ln., Santa Ana, CA 90706 Toan Tran (Luan) 1-Story ADU Addition Ben Phan, P.E. (714) 251-4537 11541 Elizabeth Street Garden Grove, CA 92840 2022 California Building Code f c =2,5000 psi @ 28 days Ready-mixed concrete per ASTM C94 Concrete aggregates per ASTM C33 Cement ASMT C150 Type V u.n.o. Minimum allowable soil bearing pressure= 1,500 psf. ASTM A-36, ASTM a-92 ASTM A-53, Grade B Electric arc process by certified welders in approved licensed fabrication shop. ASTM C90, GradeN, fm = 1,500 psi Type M, 1:3:1/4 mix; Cement:Sand:Hydrated Lime or Lime Putty. 1:3:2 mix; Cement:Sand:3/8" pea gravel; f c = 2,000 psi. Deformed bars per ASTM A915; Grade 40 for #4 and smaller; Grade 60 for #5 and larger. WCLIB or WWPA Grading Rules Agency Douglas Fir-Larch #2 Douglas Fir-Larch # 1 24F-V4 or 24F-V8 OF/OF (cantilevered) ICC ESR-1387 ICC ESR-1387 4 or more plies, Structural 1 or CD, CC Structural Panel per PS-1-95 ICC ESR-1153 (TLevel) AU inlonnation shown on plans relative to existing conditions are provided as the best present knowledge but without guarantee of accuracy. Where actual conditions conflict with the plans, they shall be reported to the Engineer so that modifications may be made in writing. Modifications of plans and details shall not be made without written approval of the Engineer. By accepting this calculations or report, the Engineer shall not be held liable for discrepancies not brought up to the attention of the Engineer. The design analysis and calculations were done in accordance with generally accepted engineering principles and practice. l~tj ROOF DEAD LOAD : Compl Shingles Roofing Sheathing/Insulation .2X RR@ 16" OC 2X C.J@ "16" OC Drywall Ceiling MPE Future Solar Panels MISCELLANEOUS 1SLOPE CORRECTION "X:12" MISCELLANEOUS HOOF DEAD LOAD : HOOF SNOW LOAD : HOOF LIVE LOAD : TOTAL. rmOF LOAD: II = 4.00 = = = ROOF TYPE 1 6.0 PSF 1.5 PSF 2.0 PSF 2.0 PSF 2.2 PSF 1.0 PSF 3.0 PSF 1.3 PSF 19.0 PSF 1.05 PSF 0.01 PSF 20.0 PSF §PSF PSF PSF 10.0 PSF 1.~ PSF 2,0 PSF 0.4 PSF 2.2 PSF '-----~1.-=-'0 PSF 17.0 PSF D ~~~ PSF PSF = ~0 PSF RR RR RR CJ CJ CJ CJ CJ FLAT LOAD: Comp. Shingles Roofing Sheathing/Insulation 2X RR@ 16"0C MPE MISCELLANEOUS SUB-TOTAL SLOPE CORRECTION "X:12" MISCELLANEOUS ROOF DEAD LOAD : RO()F SNOW LOAD : ROOF LIVE LOAD : TOTAL ROOF LOAD: Finish .flooring 3/4" subfloorihg 2x12 @16"oc Int. non-brg wall 1/2"gypsum board R19, M/P/E, & others FLOOR DEAD LOAD : FLOOR LIVE LOAD : TOTAL FLOOR LOAD I FIRST FLOOR LOADS DECK DEAD LOAD DECK LIVE LOAD •; GEOTECHNICAL ENGINEER : '--'-='-'-'l::.l==::___:=..:::.::.:::.:::.:~.::.:.:.:::.:..:.:.:::,___j 'BASIC BEARING PRESSURE 1 PADS & CONT. FNDT. = Qa INCREASE FOR WIDTH INCREASE FOR DEPTH 1\11!\X SOIL PRESSURE -Qa , ALLOW PASSIVE PRESSURE = = = ALLOW SOIL FRICTION = 1,500 PSF ISOLATED FOUNDATIONS 0.0 % 0.0 % 1,500.0 PSF 0.01 PCF .__ ___ 0::..;..3.:-J_ EQU/V. FLUID PRESSURE ROOF TYPE 2 3.0 PSF 1.5 PSF 3.0 PSF 0.0 PSF 0.0 PSF 1.0 PSF 0.0 PSF 1.5 PSF 10.0 PSF ~ 1.00 PSF o.oj PSF = = = 10.0 PSF §§i PSF PSF 0 PSF 0.0 PSF 0.0 PSF 0.0 PSF . 0.0 PSF 0.0 PSF o,o PSF '-----:0;:'-.0:::-' PSF 40.0 PSF 40.0 PSF 0 0.0 o.oj PSF PSF PSF PSF PSF '--------'-'0 I PSF O.Oj PCF .__ __ __;;.._"-' Announcement ASCE 7-22 is now available. 2422 Marty Ln, Santa Ana, CA 92706, USA La~t~'tuch;~~ Longitude: 33.7690962, ... 111 .9024494 Gloria Date Design Code Reference Document · Risk Category ·Site Class Type Vaiue Description (Data) 6/30/2025, 11 :43:55 PM ASCE?-22 II Default Map data @2025 Ss 1.53 The MCER spectral response acceleration at 0.2 seconds for Site Class BC, in units of g. · s,1 0.58 The MCER spectral response acceleration at 1 second for Site Class BC, in units of g. SMs = 1.5 x S 08 , the Risk-Targeted Maximum Considered Earthquake (MCER) spectral S1v1s ·J. 78 response acceleration for short periods (of the two-period spectrum) and the user-specified Site Class. SM1 SM 1 = 1.5 x s 01 , the MCER spectral response acceleration for 1 second (of the two-period 1.27 spectrum) and the user-specified Site Class. ,1.19 The design spectral response acceleration for short periods (of the two-period spectrum) and the user-specified Site Class, in units of g. The design spectral response acceleration for 1 second (of the two-period spectrum) and 0 ·84 the user-specified Site Class, in units of g Type Value Description (Data Contd.) SOC D Seismic desiqn cateqorv Latitude 33.7690962. North Longtitude = ···1 "17 .90245 West Occupancy Category II I (Table 1.5-2) Important Factor (I) = 1.00 Shear Panels Timber Frames R 6.50. 1.50 no = 3.00 1.50 cd 4.00 1.50 p= = 1.30 1.00 Use Simplified Alternative Structural Design F = I 1.00 I V (F*Sos)/R V 0.24 Shear Panels DESIGN WIND VELOCITY (V3 5 ) Vrm Occupancy Category lmporiant Factor (I) Exposure Category Adjustment Coefficient (A.) Kzr Ps = = MWFRS Des 110.0 MPH 110.0 MPH II 1.00 (Table 1.5-2) c 1.29 (Figure 28.6-1) 1.00 Ss s1 = Site Class = Fa = Fv = F = v = v Roof Height Wall Height (2ndt floor) = Wall Height (1st floor) = Total Height Mean Roof Height Roof Angle Building Width Building Length = Eave Height Mean Roof Height = 1.530 g 0:580 g D 1.20 1.80 1.00 (F*Sos)/R 0.82 Timber Frames 5.0 0.0 · .. 8.0 13.0 10.5 18.4 34.60 61.25 8.0 10.5. a= 2a = FT FT FT FT FT Edge (a) 3.5 4.2 3.5 6.9 FT FT FT FT FT FT lOAD: Roof weights Roof DL (horiz. Proj.) = Ext. Wall DL = Int. Shear Wall DL = Wall Height (1st floor) = Roof Height = Total height, hn = N-S Length= E-W Length= Roof Area= Tributary Ext. Walls to Roof = Tributary Int. Shear Walls to Roof= Roof Weight = Tributary Ext. Walls to Roof= Tributary Int. Shear Walls to Roof= \f\froof = Total DL (W) = Total Base Shear (V) = Design Base Shear : Period: T=Ct(hn)314 = 0.02*(hn)314 = Vertica~ distributions of seismic forces· r .. -le=~:=E {!b) Area (fe) Fx N-S (lb) ~~-R.ooT ·-56,448 2,119 13,819 1st Floor Fpx N-S (I b) 13,819 Shear E-W 20.0 17.0 7.0 8.0 5.0 13.0 34.6 2,119.3 191.7 34.6 42,444 13,036 969 56,448 56,448 13,819 0.137 sec V= V= N-S 20.0 17.0 7.0 8.0 5.0 13.0 61.3 2,119.3 191.7 61.3 42,444 13,036 1,715 57,194 57,194 13,819 E-W 0.24 13,819 0.2 SosW (lb) Use (lb) 13,819 13,819 Diaphragm E-W 20.0 17.0 7.0 8.0 5.0 13.0 34.6 - 2,119.3 122.5 34.6 42,444 8,330 969 51,743 51,743 N-S 0.24 w 13,819 lbs fx N-S (psf) 6.52 N-S 20.0 17.0 7.0 8.0 5.0 13.0 61.3 - 2,119.3 69.2 61.3 42,444 4,706 1,715 48,864 48,864 fpx N-S (psf) 6.52 psf plf plf ft ft ft sq.ft. ft ft I I I I I I bs. bs. bs. bs. bs bs I L; 56,448 13,819 13,819 ~--·--~.~~~----~--~~--~~~----~-----L----~----~ FxE-W (I b) Fx E-W wx 0.2 SosW Use (I b) fx E-W fpx E-W (I b) (psf) (psf) 13,819 13,819 13,819 13,819 6.52 6.52 13,819 13,819 LongRtudnnal Direction: Shear Wa!ls (Vertical): High Roof Level: ---------------~~~~~~~~--~~~--~~--r---~--.-------~------~~-------. 1 1 to 2 2 2 to 3 3 -----~--~----~~~~~~~~--~~~--~~--r-~~--+--------+------~---------4 fx(psf) 6.52 6.52 6.52 6.52 6.52 -·-------'-'----'--·-l----~~----~------~------r----+-----+------t------4 __ Spacing (ft) 17.25 17.33 Depth (ft) 611.25 61.25 10 -----~~~~--+-~~--r----~~~~~~------+--~--1-----+----~---~ Net D (b, ft) 22.00 22.0 8.0 V5 ,,ismic (lb) 3,445 4,010 565 ______ ___:___:___:_-4-~---+--------+------+-------~-------t-----l-------+------l ! Vwind (lb) 1,961 1,961 1,961 I Vgoverns (!b) 3,445 4,010 1,961 -----v~-~~-J,pi"'rr;)--+--:-15:::::7=---+------+--1::-::8:-:::2---+------+--;:2-;-45:::---+----+--------+-------l t~ Vractoffi~.d(~p_lf~)---l-----1_57-+-----+---18_2-+----~---2_4_5-l-------~--------+------~ ! Vractore/1.0(plf) 157 182 245 ~-----------~----+------r-------r--------+------;-------t-----+----~ i iViin. D (ft) 6.00 10.0 8.0 1 ,----------::7---!------~----+-----~+-------+----:---:----t---------il-----+------·l I f"io (lb-ft) 7,516 14,581 15,692 ·------·----,-:-:::---+-------1----+-------+-----+------+-------t-------~-----l r w~,(plf) 86 86 86 Wwall (plf) 136 136 136 I 0.6*M,~ (lb-ft) 2,402 6,671 4,269 ~---------------+---~---+------l---------l--------+----___:~---------l--------+---------1 I Tie-down (6") I YES YES YES ~---·------·----'-·--'--+-----+------+-------;--------+------t---------t--------+---------j ! Tie-down (lb) 930 833 1,523 Tie-down HDU2&SSTB16 HDU2&SSTB16 HDU2&SSTB16 t= Comp.Po_s_t--~---2--2~x4-.-------.---2---2x-4-.------.----2--2-x-4"--------t--------+---------t D + E/1.4 E = p E 11 p== 1.30 ,_._,......_ ... _.NUMt:al~leiPIOIB~ all (grid line) I.Fabove (lb) LFX (I b) Ftotal v=E/1.4b Shear# Wall Length Sheathing 1 Allowable Shear (I b) (plf) (ft) or 2 sides (plf) >ml;i'ISio~~= 1 -3,445 3,445 157 1 22.0 1 280 ---2 -4,010 4,010 182 1 22.0 1 280 :~ -1,961 1,961 245 1 8.0 1 280 Diaphwagm (horizontal): Roof Level· r·----·----1 1 to 2 2 2 to 3 3 r:~~~-~,( p(~~ 6.52 6.52 6.52 6.52 6.52 17.25 17.33 r--- ___ _Q~pth (ft) 61.25 61.25 10 Area (ft2) 1,057 1,061 fseismic(plf) 56 56 Vwind(plf) 16 16 -· Governs Seis. Seis. f-- Vgoverned(plf) 56 56 r·-Roof Pane! 1/2" CDX 1/2" cox Shear 270 270 ____ Edge Nail 8d.@ 6" 6" 12" 8d@ 6",6",12" ' ' Transverse Direction: Shear Waijls {Vertical): --[ f-____ fxQ)sf) ! --· se:-'cing (ft) r I­ I Depth (ft) - --~--~-t~t C!JE.J!l. I ~ V seismic (I b) --·------- [-Vwind (lb) •N• .. m~-·-• Vgoverns (lb) ! ! i ----··v;;>Verns( pi!-) 1,~ ' ~·--~"l.ll~"'"'"""""""--t.O""" Vtactored(plf) i_ ' Vtoctore/1.0 (plf) ------- i i' I I -- ·-·- Min. D (ft) Mo (lb-ft) Wroof (pif) Vl\vall (plf) r--0.6*MR (lb-ft) - Tie-down (6") ---~~_ie-down (lb) Roof Level A 6.52 34.6 8Jj0 1 '128 1,386 1,386 173 173 '173 8.00 11,086 50 136 3,573 YES 939 A to B B B to C c C to D D 6.52 6.52 6.52 6.52 6.52 6.52 10 14.75 36.6 34.6 17.25 17.25 8.00 10.42 7.00 1,958 2,888 2,058 1,386 1,386 1,386 1,958 2,888 2,058 245 277 294 245 277 294 245 277 294 8.00 10.42 7.00 15,661 23,103 16,467 60 70 80 136 136 136 3,765 6,712 3,176 YES YES YES 1,487 1,573 1,899 --~!:_1~-down --1-HDU2&SSTB16 I~ L HDU2&SSTB16 HDU2&SSTB16 HDU2&SSTB16 --~?mr..:..£~st j_ 2-2x4 D + E/1.4 E = p Eh Ttransve;r:se Shea!' Walls ·---··-~t-"~-· rid line) L:Fabove (lb) -·-""'~~ -- ~ ----. - --- Diap!uarJm (horizontal): ,.._.,....,.,._..~·~--· ·-·~-··-·~--~~-- I ... ~_, ... _!px\!Jsf) -~· r ~ i I L (ft) Depth (ft) Area (fe) f seismic( P If) VwinC:(plf) Governs :~···~~---- '· V governed(p!f) i·~----· i=<.oof Panei Shear i··----· Roof Level· A 6.52 34.6 L:Fx (I b) 1,386 1,958 2,888 2,058 A to B 6.52 10 346 33 20 Seis. 33 1/2" cox 270 l .... _ Edgf::__ N~--8d@ 6",6",12" 2-2x4 2-2x4 2-2x4 p= 1.30 Ftotal v=E/1.4b Shear# Wall Length Sheathing 1 (I b) (plf) (ft) or 2 sides 1,386 173 1 8.0 1 1,958 245 1 8.0 1 2,888 277 1 10.4 1 2,058 294 1 7.0 1 B B to C c Cto D D 6.52 6.52 6.52 6.52 6.52 14.75 36.6 34.6 11.25 17.25 254 631 48 119 40 40 Seis. Seis. 48 119 1/2" cox 1/2" cox 270 270 8d@ 6",6",12" 8d@ 6",6",12" Allowable Shear (plf) 280 280 280 280 7 DESCRIPTION: RR-1 @ 16" OC CODE REFERENCES Project Title: Engineer: Project 10: Project Oeser: ..... --··-·········-···-··-·-·-·-·-----··---------------------------------- Calculations per NOS 2018, IBC 2021, ASCE 7-16 Load Combination Set: ASCE 7-16 IV~~t~Eei3JI __ f'_e:q;;_p~!!!~~-_________________ _ /\nalysis Method : Allowable Stress Design Fb + Load Combination ASCE 7-16 Fb- Fe-Pr/1 Wood Species Douglas Fir-Larch Fe-Perp Wood Grade :· No.2 Fv Ft Beam Bracing : Beam is Fully Braced against lateral-torsional buckling 0(0.019995) Lr(0.02666) .. -------··---·r;-··----------------~----------------~ !. Span = 8.50 ft ! 900.0 psi 900.0 psi 1,350.0 psi 625.0 psi 180.0 psi 575.0 psi E : Modulus of Elasticity Ebend-xx 1 ,600.0 ksi Eminbend-xx 580.0ksi Density 31.210 pcf Repetitive Member Stress Increase f.iJliP~!~d -~-~~~~------·-·-·-Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : 0 == 0.0150, Lr = 0.020 ksf, Tributary Width = 1.333 ft, (Roof Loads) QE;S!GN $liil!IJY!ABX Maximum Bending Stress Ratio Section used for this span fb: Actual F'b Load Combination Location of maxil:num on span Span #where maximum occurs Maximum Deflection Max Downward Transient Deflection Max Upwarcl Transient Deflection Max Downward Total Deflection Max Upwarcl Total Deflection = = = = = 0.413: 1 Maximum Shear Stress Ratio = 0.149: 1 2x6 Section used for this span 2x6 694.22psi fv: Actual = 33.61 psi 1 ,681.88psi F'v = 225.00 psi +D+Lr Load Combination +D+Lr 4.250ft Location of maximum on span = 0.000 ft Span# 1 Span #where maximum occurs = Span# 1 0.095 in Ratio= 1077 >=360 Span: 1 : Lr Only 0 in Ratio = 0 <360 n/a i 0.172 in Ratio = 593 >=180 Span: 1 : +D+Lr i 0 in Ratio= 0 <180 n/a 1 ................................................................................................................................................................................................................................................................................................................................... .1 Maximum Forces & Stresses for load Combinations ·LoaCi-comiiinaHoil ______ l\llax stress Ra 1os Moment Values Shear Values -------- Segment Length Span# M v CD CM Ct CLx CE Cfu c. C r M fb F'b v fv F'v I -·----~---·- D Only 0.0 0.00 0.0 0.0 Length"' 8.50 ft 0.258 0.093 0.90 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.20 312.2 1,211.0 0.08 15.1 162.0 +D+Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length== 8.50 ft 0413 0.149 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.44 694.2 1,681.9 0.18 33.6 225.0 I·D+O 750Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length= 8.50 ft 0.356 0.129 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.38 598.7 1,681.9 0.16 29.0 225.0 +0.600 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length = 8.50 ft 0.087 0.031 1.60 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.12 187.3 2,152.8 0.05 9.1 288.0 DIESCR~IPTION: RR-2@ 16" OC CODE REFERENCES Project Title: Engineer: Project 10: Project Oeser: ----------·····---------------------------------------------- Calculations per NOS 2018, IBC 2021, ASCE 7-16 Lo<Jd Combination Set: ASCE 7-16 i\l~§lt~_!~<l !_ ~~{)Pf!'~rt~-~~---_____ _ Analysis Method : Allowable Stress Design Load Combination ASCE 7-16 Wood Species Wood Grade Douglas Fir-Larch No.2 Fb + Fb- Fe-Prll Fe-Perp Fv Ft 900.0 psi 900.0 psi 1 ,350.0psi 625.0 psi 180.0 psi 575.0 psi E : Modulus of Elasticity Ebend-xx 1 ,600.0 ksi Eminbend-xx 580.0ksi Density 31.210pcf Bearn is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Span= 5.0 ft folfi'j:)'!!_G_'-!_~:~~icJ~.-____ ______________ Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : 0 = 0.0150, Lr = 0.020 ksf, Tributary Width = 1.333 ft, (Roof Loads) [)t; s;q N $' £JMNJABY Maxirnurn Bending Stress Ratio Section used for this span fb: Actual F'b l_oad Combination l_ocation of maximum on span Span #where maximum occurs Maxirnurn Deflection Max Downward Transient Deflection Max Upward Transient Deflection i\llax Downward Total Deflection Max Upward Total Deflection = = = 0.302 1 2x4 585.22psi 1 ,940.63psi +D+Lr 2.500ft Span# 1 0.044 in Ratio= 0 in Ratio= 0.079 in Ratio= 0 in Ratio= Maximum Shear Stress Ratio Section used for this span fv: Actual F'v Load Combination Location of maximum on span Span # where maximum occurs 1364>=360 Span: 1 : Lr Only 0<360 n/a 761>=180 Span: 1 : +D+Lr 0<180 n/a !\ih:mimw1l1 fo1rces & Stresses for load Combinations Li:iadr~(),1,Tiii1-alion --------rvraxstresSRa 1os lllloment 'Values -------- Segment Length Span# M v CD CM ---··-----~---···-· -----------···---·-------· Ct CLx CF Cfu ci C r M fb D Only Lengtr1 '" 5.0 ft 0.185 0.083 0.90 1.00 1.00 1.00 1.500 1.00 1.00 1.15 0.07 258.8 +D+Lr 1.00 1.00 1.00 1.500 1.00 1.00 1.15 Length = 5.0 ft 0.302 0.135 1.25 1.00 1.00 1.00 1.500 1.00 1.00 1.15 0.15 585.2 +D+0.?50Lr 1.00 1.00 1.00 1.500 1.00 1.00 1.15 Length '" 5.0 ft 0.260 0.116 1.25 1.00 1.00 1.00 1.500 1.00 1.00 1.15 0.13 503.6 !-0.60D 1.00 1.00 1.00 1.500 1.00 1.00 1.15 Length 0-' 5.0 ft 0.063 0.028 1.60 1.00 1.00 1.00 1.500 1.00 1.00 1.15 0.04 155.3 = ::: ::: = = F'b 0.0 1,397.3 0.0 1,940.6 0.0 1,940.6 0.0 2,484.0 0.135: 1 2x4 30.40 psi 225.00 psi +D+Lr 0.000 ft Span# 1 i .. I Snear 'Values _______ v fv F'v 0.00 0.0 0.0 0.05 13.4 162.0 0.00 0.0 0.0 0.11 30.4 225.0 0.00 0.0 0.0 0.09 26.2 225.0 0.00 0.0 0.0 0.03 8.1 288.0 DESCRIPTION: CJ-1@ 16" OC CODE REFERENCES Project Title: Engineer: Project ID: Project Oeser: ·. ·f:~'~;~~~~rt~,~c~J NERCALC INC 1983-2023 -·--···---······· -----·········-·--·-·-··----·-----·· --------------------------------- Calculations per NDS 2018, IBC 2021, ASCE 7-16 Load Combination Set: ASCE 7-16 fti~_¥li~!i~i_fn"2P~i!i~~---__________ _ Analysis Method : Allowable Stress Design Load Combination ASCE 7-16 Wood Species Woocl Grade Douglas Fir-Larch No.2 Fb + Fb- Fe-Prll Fe-Perp Fv Ft Elearn Bracing Beam is Fully Braced against lateral-torsional buckling .. ··---····-----·--··--·.,--·---··-·----··--·--·-· r- Span = 16.750 ft 900.0 psi 900.0 psi 1,350.0 psi 625.0 psi 180.0 psi 575.0 psi E : Modulus of Elasticity Ebend-xx 1 ,600.0 ksi Eminbend-xx 580.0ksi Density 31.210pcf Repetitive Member Stress Increase A~pii~(i_!:::l()~_!!~ --·--------------Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.01 0, Lr = 0.010 ksf, Tributary Width = 1.333 ft, (Ceiling Loads) DE:$1Gif1! $ [JlVIJVIA BY ... l'v1aximum Bending Stress Ratio 0.599: 1 Maximum Shear Stress Ratio 0.139: 1 Section used for this span 2x8 Section used for this span 2x8 fb: Actual 929.30psi fv: Actual = 31.32 psi F'b 1 ,552.50psi F'v = 225.00 psi Load Combination +D+Lr Load Combination +D+Lr Location of maximum on span = 8.375ft Location of maximum on span = 16.200 ft Span #where maximum occurs = Span# 1 Span #where maximum occurs = Span# 1 Maximum Deflection 1\ilax Downward Transient Deflection 0.312 in Ratio= 645>=360 Span: 1 : Lr Only 1\ilax Upward Transient Deflection 0 in Ratio= 0<360 n/a 1\ilax Downward Total Deflection 0.678 in Ratio= 296>=180 Span: 1 : +D+Lr IVIax Upward Total Deflection 0 in Ratio= 0<180 n/a Maximum Forces & Stresses for Load Combinations · Eaac0i,bln:illon ______ l\7lax Stress Ratios lllloment 17alues Snear 17alues Segment Length Span# M v --~--· ----~-------~--- CD CM Ct CLx CE Cfu ci cr M fb F'b v fv F'v D Only 0.0 0.00 0.0 0.0 Length == 16. l50 ft 0.449 0.105 0.90 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.55 502.4 1,117.8 0.12 16.9 162.0 HJ+lr 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Len 9th = 16.750 ft 0.599 0.139 1.25 1.00 1.00 1.00 1.200 1.00 1.00 1.15 1.02 929.3 1,552.5 0.23 31.3 225.0 +D+0.750Lr 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.0 0.00 0.0 0.0 l..r:mgth "' 16.750 ft 0.530 0.123 1.25 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.90 822.6 1,552.5 0.20 27.7 225.0 +0.60D 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Len\)tfl = 16.'750 ft 0.152 0.035 1.60 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.33 301.4 1,987.2 0.07 10.2 288.0 DESCRIPTION: CJ-2@ 16" OC CODE REFERENCES Ca:culations per NOS 2018, IBC 2021, ASCE 7-16 Load Combination Set: ASCE 7-16 !lJ:I~t~!·n~UCl'tGie~:e!!i~-~-_____________________ _ Analysis Method : Allowable Stress Design Load Combination ASCE 7-16 Wood Species Wood Grade Douglas Fir-Larch No.2 Project Title: Engineer: Project ID: Project Oeser: Fb + Fb- Fe-Prll Fe-Perp Fv Ft 900.0 psi 900.0 psi 1,350.0 psi 625.0 psi 180.0 psi 575.0 psi E : Modulus of Elasticity Ebend-xx 1 ,600.0ksi Eminbend-xx 580.0ksi Density 31.210pcf Beam Bracing Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase 0(0.01333) Lr{0.01333) 2x6 I· --------------· Span= 9.50 ft t3p~i~~~-ll)_illl]~----------Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.01 0, Lr = 0.010 ksf, Tributary Width = 1.333 ft, (Ceiling Loads) Dg$!(3fll $i!JVJIVIA8Y Maximum Bending Stress Ratio = 0.303 1 Maximum Shear Stress Ratio = 0.099: 1 Section used for this span 2x6 Section used for this span 2x6 fb: Actual = 509.24psi fv: Actual = 22.24 psi F'b 1,681.88psi F'v 225.00 psi Loo;d Cornbination +D+Lr Load Combination +D+Lr Location of maximum on span = 4.750ft Location of maximum on span = 9.049 ft Span# where maximum occurs = Span# 1 Span# where maximum occurs = Span# 1 Maximum Deflection Max Downward Transient Deflection 0.074 in Ratio= 1543 >=360 Span: 1 : Lr Only l\llax Upward Transient Deflection 0 in Ratio= 0<360 n/a Max Downward Total Deflection 0.158 in Ratio= 723>=180 Span: 1 : +D+Lr Max Upward Total Deflection 0 in Ratio= 0<180 n/a Maximum Forrces & Stresses for load Combinations Coacn5c)iTil:lliiatlon _______ Wiax stress Ra!TOs l'illoment Values Sfiear Values --·-------- CLx ci cr fb Segment Length Span# M v CD CM Ct c Cfu M F'b v fv F'v ---... -----··--·-- D Only 0.0 0.00 0.0 0.0 Len(Jlh = 9. 50 ft 0.223 0.073 0.90 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.17 270.6 1,211.0 0.06 11.8 162.0 +D+lr 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length = tl.50 ft 0.303 0.099 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.32 509.2 1,681.9 0.12 22.2 225.0 +U+0.750lr 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length = 9.50 ft 0.267 0.087 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.28 449.6 1,681.9 0.11 19.6 225.0 +0.600 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 length = 9.50 ft 0.075 0.025 1.60 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.10 162.4 2,152.8 0.04 7.1 288.0 t ( DESCRiPTION: HIP-1 -Hip Beam CODE REFERENCES . ·····-------~-------------- Calculations per NOS 2018, IBC 2021, ASCE 7-16 Load Combination Set: ASCE 7-16 !V~~texn<Jll_~w€?PE!.~~~~----·-----·-_ Analysis Method . Allowable Stress Design Load Combination ASCE 7-16 Wood Species Wood Grade Douglas Fir-Larch No.2 Project Title: Engineer: Project ID: Project Oeser: Fb + Fb- Fe-Prll Fe-Perp Fv Ft 900.0 psi 900.0 psi 1,350.0 psi 625.0 psi 180.0 psi 575.0 psi Beam Bracing Beam is Fully Braced against lateral-torsional buckling Span ; 12.250 ft E : Modulus of Elasticity Ebend-xx 1 ,600.0 ksi Eminbend-xx 580.0ksi Density 31.210pcf .-l\:p_fll!i_e_f.i!:_o~~_:;>___________ Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading DI'5SfGN SUMMA BY. Maximum Bending Stress Ratio = 0.861: 1 Maximum Shear Stress Ratio = 0.296: 1 Section used for tl1is span 4x8 Section used for this span 4x8 fb: Actual = 1 ,258.69psi fv: Actual = 66.61 psi F'b = 1 ,462.50psi F'v = 225.00 psi Load Combination +D+Lr Load Combination +D+Lr Location of maximum on span = 6.885ft Location of maximum on span = 11.669 ft Span #where maximum occurs = Span# 1 Span# where maximum occurs = Span# 1 Maximum Deflection Max Downward Transient Deflection 0.268 in Ratio= 549>=360 Span: 1 : Lr Only Max Upward Transient Deflection 0 in Ratio= 0<360 n/a Max Downward Total Deflection 0.484 in Ratio= 303>=180 Span: 1 : +D+Lr Max Upward Total Deflection 0 in Ratio= 0<180 n/a i'tllaJ:imum Forces & Stresses for load Combinations -T.oai:l ·co,:YIG!natlol-i ________ l\lfax::>lress-Rafios l\llomen{ 'Values Shear 'Values ------- Segment Length Span # rv1 v CD CM Ct CLx c Cfu ci C r M fb F'b v fv F'v ---· ----···--·-··------···-··-···------·-----~- D Only 0.0 0.00 0.0 0.0 Length = 12.250 ft 0.534 0.183 0.90 1.00 1.00 1.00 1.300 1.00 1.00 1.00 1.44 562.2 1,053.0 0.50 29.6 162.0 +D+Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.0 0.00 0.0 0.0 Length = 12.250 ft 0.861 0.296 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.00 3.22 1,258.7 1,462.5 1.13 66.6 225.0 +D+0.750Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.0 0.00 0.0 0.0 Length = 12.250 ft 0.742 0.255 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.00 2.77 1,084.6 1,462.5 0.97 57.4 225.0 +0.600 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.0 0.00 0.0 0.0 Lengtll = 12.250 ft 0.180 0.062 1.60 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.86 337.3 1,872.0 0.30 17.7 288.0 Ovewafi Maximum Deflections -··--···· . --~---.. ·----------------~----- Load Combination Span Max. "-" Defl Location in Span Load Combination Max. "+" Defl Location in Span -~rJ~I_I: ··· ···----------------r------o.4842 6.349 0.0000 0.000 jv Project Title: Engineer: Project ID: Project Oeser: [ ~~iood Beam ·· iiE11<W:~6661721f6;-i3uTiCf"'2Do;-;.2""3"'.o"'s"'".3o"'-----'-'-'-'--'-'--'--'-'-''--'--'-'"--'-'~'-"""-"'-=~ DESCRiPTION: HIP-1 -Hip Beam Vertical Reactions Load Combination ~Max Opwa·rali:Om-alrCoa<rC-onditioris Max Upward from Load Combinations Max Upward from Load Cases D Only +D+Lr +D+O.ll'iOLr +0.600 Lr Only Support notation : Far left is #1 Values in KIPS Support 1 Support 2 0.772 1.296 o.772 1.296 ,IL p 0.422 o.721 ·~ L }<:.. 2; -::. 0.350 0.575 .t/ ~~~ :/1 0.772 1.296 0.667 1.116 0.210 0.345 LJ;J~ 1--Jf ~ ~ >P tt 1-r o PIJ]? 0.422 0.721 l7 DESCRIPTION: HIP-2 -Hip Beam CODE REFERENCES Calculations per NOS 2018, IBC 2021, ASCE 7-16 Load Combination Set: ASCE 7-16 i\!ua_~~!<~:!_!r_Q:»_~~ies __ Analysis Method : Allowable Stress Design i_oad Combination ASCE 7-16 Wood Species Wood Grade !3eam Bracing Douglas Fir-Larch No.2 Beam is Fully Braced against lateral-torsional buckling Project Title: Engineer: Project ID: Project Oeser: Fb + Fb- Fe-Prll Fe-Perp Fv Ft 900.0 psi 900.0 psi 1,350.0 psi 625.0 psi 180.0 psi 575.0 psi E : Modulus of Elasticity Ebend-xx 1 ,600.0 ksi Eminbend-xx 580.0ksi Density 31.210pcf Span = 6.50 ft /'l.e_P!!_~I:! L~~~s --------- Beam self weight calculated and added to loading l_oad for Span Number 1 Service loads entered. Load Factors will be applied for calculations. Varying Uniform Load : 0= 0.0150->0.0150, Lr= 0.020->0.020 ksf, Extent= 0.0 --» 6.50 ft, Trib Width= 1.0->4.750 ft, (Roof Loads) D£.:$1QN $1..1}1/JVIARY OO•Ooo ••••••••••••••••••••••••••••••••••••••••••••--••••••••••••••••••••••••••••••••••••••••••••••••••••o••••omoo .. •o•o•o•o•000""'""""""'""'''''"'''"''''''"""'"'"""""'''"'''0"0'"""""''H"""' 1\ilaxirnum Bending Stress Ratio Section used for this span = 0.260 1 Maximum Shear Stress Ratio fb: Actual F'b Load Combination Location of maximum on span , Span #where maximum occurs Maximum Deflection Max Downward Transient Deflection Max Upward Transient Deflection Max Downward Total Deflection IViax Upward Total Deflection = = = = 4x6 380.39psi 1 ,462.50psi +D+Lr 3.582ft Span# 1 0.030 in Ratio= 0 in Ratio= 0.055 in Ratio= 0 in Ratio= Section used for this span fv: Actual F'v Load Combination Location of maximum on span Span# where maximum occurs 2605>=360 0<360 1429>=180 0<180 Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a M<u>imum Forces & Stresses for Load Combinations Co-aa comiJTiiaHoil _______ rvraxstress Ratios llllomenf 'ilalues ----- Segment Length Span # M v CD CM Ct ---~---. -----· ·-···-··--·--·-·------- CLx CE Cfu ci C r M fb D Only Length = 6.50 ft 0.163 0.073 0.90 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.25 171.5 +D+Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.00 Length = 6.50 ft 0.260 0.117 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.56 380.4 +D+0.750Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.00 Length= 6.50 ft 0.224 0.101 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.48 328.2 +0.600 1.00 1.00 1.00 1.300 1.00 1.00 1.00 Length = 6.50 ft 0.055 0.025 1.60 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.15 102.9 = 0.117: 1 4x6 = 26.25 psi = 225.00 psi +D+Lr = 6.049 ft = Span# 1 SFiear 'ilalues F'b v fv F'v 0.0 0.00 0.0 0.0 1,053.0 0.15 11.8 162.0 0.0 0.00 0.0 0.0 1,462.5 0.34 26.3 225.0 0.0 0.00 0.0 0.0 1,462.5 0.29 22.6 225.0 0.0 0.00 0.0 0.0 1,872.0 0.09 7.1 288.0 lt.f Project Title: Engineer: Project 10: Project Oeser: DESCmPTION: HIP-2-Hip Beam Oven'l!i Maximl!.lm Deflections Load Combination Spa-n--~M~ax-.~ .. _~ .. ~D~e~fi~L~o-c-at7io-n~i-n~S-p-an--~L-oa-d~C-om~bi~na~t7io_n ____________ 7M~a-x.~"~+7"~D-ef~I~L-o-ca~t~io-n~in-S~p-a--n +D+L.r 1 0.0546 3.345 0.0000 0.000 V~·rtic3li Reactions Support notation : Far left is #1 Values in KIPS Load Combination --------~--~~~--~----Support 1 Support 2 1Viax Dj)waiccl from·-allToaa-conditions Max Upward from Load Combinations Max Upward from Load Cases D Only +IJ+L.r +D+O. 1'50Lr +0.60D LrOnly 0.269 0.412 0.269 0.412 .Jt:-r A.. ...-r-h o.146 o.228 lJ'L ~ '/ 1 I ~ Jt; -/ "~ v 0.123 0.184 ,___- 0.269 0.412 0.233 0.355 0.074 0.111 0.146 0.228 Project Title: Engineer: Project 10: Project Oeser: DESCRIPTION: CB-1 -Ceiling Beam CODE F?EFERENCES Calculations per NOS 2018, IBC 2021, ASCE 7-16 Load Combination Set: ASCE 7-16 r~~<l~ruaJ_~~"?EIE!~f!i~~-- Analysis Method : Allowable Stress Design Load Combination ASCE 7-16 Wood Species Wood Grade Douglas Fir-Larch No.2 Fb + Fb- Fe-Prll Fe-Perp Fv Ft Beam Bracing Beam is Fully Braced against lateral-torsional buckling 0(0.412) Span = 9.50 ft 900.0 psi 900.0 psi 1,350.0 psi 625.0 psi 180.0 psi 575.0 psi E : Modulus of Elasticity Ebend-xx 1 ,600.0 ksi Eminbend-xx 580.0ksi Density 31.210pcf Service loads entered. Load Factors will be applied for calculations. f3eam self weight calculated and added to loading Uniform Load : D = 0.020, Lr = 0.020 ksf, Tributary Width = 3.0 ft, (Roof Loads) Point Load: D = 0.4120 k@ 4.750 ft, (From HIP-2) Point Load: D = 0.4120 k@ 4.750 ft, (From HIP-2) DES.!GN$VMIVIABX IVlaximum Bending Stress Ratio = 0.671: 1 Maximum Shear Stress Ratio Section used for this span 4x10 Section used for this span fb: Actual = 652.28psi fv: Actual F'b = 972.00psi F'v Load Combination DOnly Load Combination Location of maximum on span = 4.750ft Location of maximum on span Span #where maximum occurs = Span# 1 Span #where maximum occurs fltlaximurn Deflection IVlax Downward Transient Deflection 0.030 in Ratio= 3806>=360 Span: 1 : Lr Only Max Upward Transient Deflection 0 in Ratio= 0<360 nla Max Downward Total Deflection 0.133 in Ratio= 859>=180 Span: 1 : +D+Lr Max Upward Total Deflection 0 in Ratio= 0<180 nla 1\fimdmum IForces & Stresses for load Combinations Lo-aci' c01-fi1i1ilatlcii1·-·---l'iilaX-stress Rabos l'iiloment 'ilalues ----c. C r Segment Length Span# M v CD CM Ct CLx Cp Cfu I M fb ---··---~---·--·---·--·--···-- D Only Length = 9.50 ft 0.671 0.194 0.90 1.00 1.00 1.00 1.200 1.00 1.00 1.00 2.71 652.3 >D+i_r 1.00 1.00 1.00 1.200 1.00 1.00 1.00 Length = 9.£i0 ft 0.604 0.189 1.25 1.00 1.00 1.00 1.200 1.00 1.00 1.00 3.39 815.0 +D+O. 750Lr 1.00 1.00 1.00 1.200 1.00 1.00 1.00 Length= 9.50 ft 0.574 0.177 1.25 1.00 1.00 1.00 1.200 1.00 1.00 1.00 3.22 774.3 +0.60D 1.00 1.00 1.00 1.200 1.00 1.00 1.00 Length "' 9 .l10 ft 0.226 0.066 1.60 1.00 1.00 1.00 1.200 1.00 1.00 1.00 1.63 391.4 = 0.194: 1 4x10 = 31.47 psi = 162.00 psi DOnly = 8.737 ft = Span# 1 Sfiear 'ilalues F'b v fv F'v 0.0 0.00 0.0 0.0 972.0 0.68 31.5 162.0 0.0 0.00 0.0 0.0 1,350.0 0.92 42.6 225.0 0.0 0.00 0.0 0.0 1,350.0 0.86 39.8 225.0 0.0 0.00 0.0 0.0 1,728.0 0.41 18.9 288.0 ly Project Title: Engineer: Project ID: Project Oeser: DESCR!PT!ON: CB-1 -Ceiling Beam Overall Maximum Deflections Load Combination Span Max. "-" Defl Location in Span Load Combination Max. "+" Defl Location in Span +D+Lr 1------~o~.1~3~26~------4·_~78~5~-----------------------------o~.~ooMo~o~-----o~.~ooMo--- V~rtical Reactions ··············-···-·----·-·-· ---·----·--------------- Load Combination ·lvlax lJpwa-rcf froin-aTI-Loaacoriditions 1\/lax Upward from Load Combinations Max Upward from Load Cases D Only +D+L.r +D+O.l50Lr +0.600 l.r Only Support notation : Far left is #1 Values in KIPS Support 1 Support 2 1 . 015 ---,1-.. 0""'1--.=5-------· 1.015 1.015 .. ~ ( 1 ,r---d./. 0. 730 0.730 ~ . -::z_. II 10 l ~ _;,;, 0.730 0.730 1.015 1.015 I{ it 0.944 0.944 A tt oft & I~ [} C4'tJl. 0.438 0.438 ;(. 0.285 0.285 /1 UNIFORM AND POINT LOAD ON CONTINUOUS FOOTING Footing \Nidth (FW) = Footing Depth (FD) = Soil Bearing (SB) = Max. Soil Bearing = Plain Concrete Design: F'c = Tension Fb = Procedures: 12 in 12 in 1,500 psf 1,500 psf 2,500 psi 80 psi Fsoil = ((D-FD)/12*1D)+SB F'soil = Fsoii-(D/12*(150-11 0)) w = W*F'soil/12 1~·=-~ ~}l 8 12 X 15 X 18 1·--· f---- 1 ~-­ f r-- 1 X -~}-+x 24 , X 12 X !----15--1 X ------iL_ 18 I X r-· 21 lx ~------ 1·-~- i l- 1 24 X ---·-'i2 i X 15·l·x I ~-- 18 l X ----+ 21 I X !----.. --·-·-.... ..,. ..... - 24 ix 1-- t­t-- ~-12 15 18 ---· 21 X lx X r-- X 1-.24~ 12 X 15 X i-- 1·-· ---· , ____ _ J r-·- '18 X 2'1 1X ---·--1 I 24 i X ------r· .~.-l X 1_ M = Fb*W*d/\2/12"/6 L = (2*M/w)A1 /2 Pmax = 2*L*w D (") Fsoil (psf) F'soil (psf) 5 1,500 1,483 12 1,500 1,460 12 1,500 1,460 12 1,500 1,460 12 1,500 1,460 12 1,500 1,460 15 1,500 1,450 15 1,500 1,450 15 1,500 1,450 15 1,500 1,450 '15 1,500 1,450 18 1,500 1,440 18 1,500 1,440 18 1,500 1,440 18 1,500 1,440 18 1,500 1,440 21 1,500 1,430 21 1,500 1,430 21 1,500 1,430 21 1,500 1,430 21 1,500 1,430 24 1,500 1,420 24 1,500 1,420 24 1,500 1,420 24 1,500 1,420 24 1,500 1,420 24 1,500 1,420 Soil Density = Concrete Density = Inc. Width (IW) = Inc. Depth (ID) = w {#/ft} M ('#) 1,483 333 1,460 1,920 1,825 2,400 2,190 2,880 2,555 3,360 2,920 3,840 1,450 3,000 1,813 3,750 2,175 4,500 2,538 5,250 2,900 6,000 1,440 4,320 1,800 5,400 2,160 6,480 2,520 7,560 2,880 8,640 1,430 5,880 1,788 7,350 2,145 8,820 2,503 10,290 2,860 11,760 1,420 7,680 1,775 9,600 2,130 11,520 2,485 13,440 2,840 15,360 3,550 19,200 110 pcf 150 pcf 0 psf 0 psf L (ft) Pmax {#} 0.67 1,989 1.62 4,736 1.62 5,919 1.62 7,103 1.62 8,287 1.62 9,471 2.03 5,899 2.03 7,374 2.03 8,849 2.03 10,324 2.03 1~ 2.45 /7,055 2.45 '-..ar818 2.45 10,582 2.45 12,345 2.45 14,109 2.87 8,202 2.87 10,252 2.87 12,302 2.87 14,353 2.87 16,403 3.29 9,340 3.29 11,676 3.29 14,011 3.29 16,346 3.29 18,681 3.29 23,351 Note: For point loads on footings with uniform loads, take the difference between "w" above and the uniform load, then multiply by two and by "L" above for P'max. A ·~ POINT LOAD ON SQUARE PAD FOOTING Footing Depth (FD) = Soil Bearing (SB) = rv1ax. Soil Bearing = 12 in 1500 psf 1500 psf Plain Concrete Design: F'c = Tension Fb = Procedures: 2,500 psi 80 psi Soil Density = Concrete Density = Inc. Width (IW) = Inc. Depth (ID) = Fsoil = ((D-FD)/12*1D)+SB F'soil = Fsoii-(D/12*(150-110)) A= W*L Pmax = F'soii*A 110 pcf 150 pcf 200 psf 200 psf r--\Flf) L (") D (") Fsoil (psf) F'soil (psf) ~ Pmax (#) Reinforce F-·--·--·-+--~~~-=~-4~~~~~~~~--~~~~~~~~~~ 12 12 5 1,383 1,367 1.00 1,367 2-#4 e.w. F--··-=~-~--~--~--~-+----~~----~~------~--~-r~~--~ '12 12 12 1,500 1,460 1.00 1,460 2-#4 e.w. '15 15 12 1,500 1,460 1.56 2,281 3-#4e.w. ~ 21 21 15 1,550 1,500 3.06 4,594 3-#4 e.w. ~__23 ... ~-04 1 24 15 1,550 1,500 4.00 6,000 3-#4 e.w. 1 30 15 1,550 1,500 6.25 9,375 4-#4 e.w. r"'···-w-·--+--18 _ _,_ __ 18 _ _,_ __ 1.;...,6_0_01----1.:...,5_0_0 1---2-.2-5..,_._3...;,-37_5..,_._3--#4-e-.w...,. ··----·----1,___ __ --t------t-------"---+-----'----~-----i---~~--------..;..;..;...:.; 1--~1-·--t---2_1 --;-----1..;:_8_+----1~, 6.:....:0:_:.0.;-__ 1;..!..., 5=-=0:_:.0.;-__ ..:...:3 ·..;:_0~61-----4.!..:., 5-=-9-=-41--..;..3...:.:-#_..:4_..:e:..:... w~. 1 24 24 18 1,600 1,500 4.00 6,000 3-#4 e.w. E-~o----~---3-0---+--..;:_18~-+------1~,6..;:_o~o~----=-1~,5..;:_o~o~----6-=-.2=-=5+---9~,~37=-=5+--4~--=-#4~e-=-.w~. 33 33 18 1,600 1,500 7.56 11,344 4-#4 e.w. 18 __ ~ __ ..:..18~-4---=-12~~-----1~,5:_:.0..;:_0~ __ __;1~,4:_:.6..;:_0t-----2=·=25-+-_..:...;3,=2..;:_85-+-___ 3-_#_4:_:.e_.w~. I 21 21 12 1,500 1,460 3.06 4,471 3-#4 e.w. ·-~~·~· ___ 2_4~-+---12~_,_--~1~,5~0~01----~1~,4~6~01--~4~.0~0~--5~,~84~0~~3-~#~4-e_.w~. '18 18 15 1,550 1,500 2.25 3,375 3-#4 e.w. ~·_2~6--t--~36~--+-~1_8 -t---~1~,6~o--o+-__ 1 ..... ,5 __ o~o+-_9..., ..... oo~_1_3,:...5_oo_,__4-_#~4-e_.w-1. ~ 30 30 21 1,650 1,500 6.25 9,375 4-#5 e.w. l--1~6 ___ ~ __ ..:..36 ___ -4--=2-=-1--t-----=-1~,6.:....:5..:..0+--__ ;_:.1~,5=-=o-=-o+--__ 9=-=·..;:_oo~---1..;:_3,=5..;:_oo~--=-4-~#-=-5~e~.w~. L~~2 42 21 1,650 1,500 12.25 18,375 5-#5 e.w. 36 36 24 1, 700 1,500 9.00 13,500 4-#5 e.w. --------~------,_-..:..-=--~---~~-----~~--~~--~~~--=-~~~ 42 42 24 1, 700 1 ,500 12.25 18,375 5-#5 e.w. ~---4~8~-+--~4~8--~___;2~4~~--~1,~7~00~--~1,~50~0~~1~6~.0~0+-:_:.2~4~,0=-=0~0+-:_:.5~-#~5~e=.~w. 54 54 24 1,700 1,500 20.25 30,375 5-#5 e.w. ·------1-----i-----~----<---+-----'---t--------if----=-~...:...r---------l 60 60 24 1,700 1,500 25.00 37,500 6-#5 e.w. ~~-~--~-~~--~~--+---~~~--~~+-~~~--~~~~~~ • 66 66 24 1,700 1,500 30.25 45,375 6-#5 e.w. t==]·~2---~--..:..7..:...;2_4-~2~-=-4-t----1~,7-0-0+----1~,5~0..:..0+--..........:...36..;:_.=oo~_:_:.5=4~,o..;:_oo~--=-7=-#..:..5=e=.w~. R-7.=8--~--=7..;:_8 __ 4--=2-=-4--t----1~,7=0..:..0+-__ :_:.1~,5.:....:0..:..0+---=-42=.=25~~6..;:_3~,3..;:_75~--=-7~-#..:..5=e=.w~. 84 84 24 1,700 1,500 49.00 73,500 8-#5 e.w. '==~·,.~•~==•rn=J.-.....--~-.J.---J.-...--.......;..-J......_.......;..;...;......L.-_.;....;...;..&__..;;.:..;...;;...;...JI.-,.--....._.1