Loading...
HomeMy WebLinkAbout1560, 1570 Brookhollow Dr & 1540 E Warner Ave - REV 1 - PlanTOTAL ENGINEERING SERVICES, INC. Structural Calculations Project: Prepared for: 1544, 1560, 1570 Brookhollow Drive Santa Ana, CA 2705 Brookhollow Trash Enclosures 1544, 1560, 1570 Brookhollow Drive Santa Ana, CA 2705 Brookhollow Trash Enclosures S T R U C T U R A L E N G I N E E R S TOTAL ENGINEERING SERVICES, INC JOB NO:24-53 SHEET NO: JOB NAME:Brookhollow Trash Enclosures ENGINEER:DA DATE:September '24 ANALYSIS:Vertical Door Loads 3/16"x3" Bar:1.91 plf 18 Ga Panel:2.16 psf 2x2x3/16 HSS:4.32 plf Door Height:8 ft Door Width:3.75 ft Total Bar Length:27.25 ft Total Panel Area: 30 ft2 Bar Weight:7.2 lbs Panel Weight:64.8 lbs HSS Weight:101.52 lbs Door Weight:173.5 lbs Max. Moment:325.3 ft-lbs Company:Date:10/29/2025 Engineer:Page:1/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.0.7947.25 1.Project information Customer company: Customer contact name: Customer e-mail: Comment: Project description: Location: Fastening description: 2. Input Data & Anchor Parameters General Design method:ACI 318-14 Units: Imperial units Anchor Information: Anchor type: Concrete screw Material: Carbon Steel Diameter (inch): 0.500 Nominal Embedment depth (inch): 3.250 Effective Embedment depth, hef (inch): 2.350 Code report: ICC-ES ESR-2713 Anchor category: 1 Anchor ductility: No hmin (inch): 5.00 cac (inch): 3.56 Cmin (inch): 1.75 Smin (inch): 3.00 Base Material Concrete: Normal-weight Concrete thickness, h (inch): 48.00 State: Cracked Compressive strength, f’c (psi): 2500 Ψc,V: 1.0 Reinforcement condition: B tension, B shear Supplemental reinforcement: Not applicable Reinforcement provided at corners: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Ignore 6do requirement: Not applicable Build-up grout pad: No Base Plate Length x Width x Thickness (inch): 4.00 x 24.00 x 0.25 Recommended Anchor Anchor Name: Titen HD® - 1/2"Ø Titen HD, hnom:3.25" (83mm) Code Report: ICC-ES ESR-2713 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Company:Date:10/29/2025 Engineer:Page:2/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.0.7947.25 Load and Geometry Load factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: No Anchors subjected to sustained tension: Not applicable Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: No Strength level loads: Nua [lb]: 0 Vuax [lb]: 0 Vuay [lb]: 174 Mux [ft-lb]: 326 Muy [ft-lb]: 0 Muz [ft-lb]: 0 <Figure 1> 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Company:Date:10/29/2025 Engineer:Page:3/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.0.7947.25 <Figure 2> 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Company:Date:10/29/2025 Engineer:Page:4/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.0.7947.25 Shear load y, Vuay (lb) Anchor Tension load, Nua (lb) 3. Resulting Anchor Forces Shear load combined, √(Vuax)²+(Vuay)² (lb) Shear load x, Vuax (lb) 0.01 0.0 87.087.0 198.82 0.0 87.087.0 0.0 174.0Sum198.8 174.0 Maximum concrete compression strain (‰): 0.01 Maximum concrete compression stress (psi): 25 Resultant tension force (lb): 199 Resultant compression force (lb): 199 Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'Vx (inch): 0.00 Eccentricity of resultant shear forces in y-axis, e'Vy (inch): 0.00 <Figure 3> 4. Steel Strength of Anchor in Tension (Sec. 17.4.1) Nsa (lb)f fNsa (lb) 20130 0.65 13085 5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.4.2) Nb = kclaÖf’chef1.5 (Eq. 17.4.2.2a) kc la f’c (psi)hef (in)Nb (lb) 17.0 1.00 2500 2.350 3062 fNcb = f (ANc / ANco)Yed,NYc,NYcp,NNb (Sec. 17.3.1 & Eq. 17.4.2.1a) ANc (in2)ANco (in2)ca,min (in)Yed,N Yc,N Ycp,N Nb (lb)f fNcb (lb) 49.70 49.70 3.75 1.000 1.00 1.000 3062 0.65 1990 8. Steel Strength of Anchor in Shear (Sec. 17.5.1) Vsa (lb)fgrout f fgroutfVsa (lb) 7455 1.0 0.60 4473 9. Concrete Breakout Strength of Anchor in Shear (Sec. 17.5.2) Shear parallel to edge in x-direction: V by = min|7(le / da)0.2ÖdalaÖf’cca11.5; 9laÖf’cca11.5| (Eq. 17.5.2.2a & Eq. 17.5.2.2b) le (in)da (in)la f’c (psi)ca1 (in)Vby (lb) 2.35 0.500 1.00 2500 3.75 2449 fVcbgx = f (2)(AVc / AVco)Yec,VYed,VYc,VYh,VVby (Sec. 17.3.1, 17.5.2.1(c) & Eq. 17.5.2.1b) AVc (in2)AVco (in2)Yec,V Yed,V Yc,V Yh,V Vby (lb)f fVcbgx (lb) 126.56 63.28 1.000 1.000 1.000 1.000 2449 0.70 6858 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Company:Date:10/29/2025 Engineer:Page:5/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.0.7947.25 10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.5.3) fV cpg = fkcpNcbg = fkcp(A Nc / A Nco)Yec,NYed,NYc,NYcp,NNb (Sec. 17.3.1 & Eq. 17.5.3.1b) kcp ANc (in2)ANco (in2)Yec,N Yed,N Yc,N Ycp,N Nb (lb)f fVcpg (lb) 1.0 99.41 49.70 1.000 1.000 1.000 1.000 3062 0.70 4287 11. Results Interaction of Tensile and Shear Forces (Sec. 17.6.) Tension Factored Load, Nua (lb)Design Strength, øNn (lb)Ratio Status Steel 199 13085 0.02 Pass Concrete breakout 199 1990 0.10 Pass (Governs) Shear Factored Load, Vua (lb)Design Strength, øVn (lb)Ratio Status Steel 87 4473 0.02 Pass || Concrete breakout x-174 6858 0.03 Pass Pryout 174 4287 0.04 Pass (Governs) Interaction check Nua/fNn Vua/fVn Combined Ratio Permissible Status Sec. 17.6..1 0.10 0.00 10.0%1.0 Pass 1/2"Ø Titen HD, hnom:3.25" (83mm) meets the selected design criteria. 12. Warnings - Designer must exercise own judgement to determine if this design is suitable. - Refer to manufacturer’s product literature for hole cleaning and installation instructions. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. * * * * * ** * * * * * * * * 55 F R E E W A Y WARNER AVE. GR A N D A V E . 15 0 6 1504 15 0 2 1500 1530 1532 1516 1518 1522 1526 1524 1520 1538 1536 1544 15 0 8 15 1 0 15 2 8 15 3 4 156 0 155 4 154 8 154 0 157 0 A-2.2 1 18' - 0 " A-2.1 2 1 & 2 1 & 2 --- -1 & 2 TRASH ENCLOSURE @ BLDG. 1570 TRASH & STORAGE ENCLOSURE @ BLDG. 1560 STORAGE ENCLOSURE @ BLDG. 1540 BRO O K H O L L O W D R BRO O K H O L L O W D R BRO O K H O L L O W D R BR O O K H O L L O W D R 74' - 7 " ( F S D ) 245' - 9" (FSD) A-2.0 27' - 8 " ( F S D ) 183 ' - 5 " ( F S D ) 163' - 9 " ( F S D ) 19' - 1 1 " ( F S D ) 64' - 6 " ( F S D ) 32 ' - 0 " ( F S D ) 11' - 2" (FSD ) 12' - 7 " ( F S D ) 12' - 8 " ( F S D ) 4 STORAGE @ 1540: ALLOWABLE AREA: 26,000 SF PROPOSED AREA: 566 SF 536 / 26,000 SF = 0.02 0.02 < 1 (CBC 508.4.2) STORAGE @ 1560: ALLOWABLE AREA: 26,000 SF PROPOSED AREA: 388 SF 371 / 26,000 SF = 0.01 0.01 < 1 (CBC 508.4.2) STORAGE @ 1570: ALLOWABLE AREA: 26,000 SF PROPOSED AREA: 370 SF 318 / 26,000 SF = 0.01 0.01 < 1 (CBC 508.4.2) Aa = (At + (NS x If) S-2 OCCUPANCY: At = 26,000 SF NS = 26,000 SF If = 0 (PER CBC 506.3.3) Aa = (At + (NS x If) Aa = (26,000 + (26,000 x 0) Aa = 26,000 SF PROJECT NUMBER: DATE: ISSUES / REVISIONS SEAL CHECKED BY: DRAWN BY: DATE DESCRIPTIONNO. a r c h i t e c t s 15375 Barranca Pkway . Ste. A-216 Irvine, CA 92618 T: 949.788.9223 F: 949.788.0716 SNIHS Y K S E Expires JANUARY 2027 RTADIVA D CT ET nia r NCE I tat No.C18642 HS ialCfoef I o S CRE L 09/05/24 PC SUBMITTAL A-0.1 A.A D.S 24-09-05 0624 1540 E WARNER AVE, 1560 & 1570 BROOKHOLLOW DRIVE SANTA ANA, CA 92705 BROOKHOLLOW OFFICE PARK STORAGE & TRASH ENCLOSURE OVERALL SITEPLAN 1" = 80'-0" OVERALL SITE PLAN1 ALLOWABLE AREA CALCULATION 1 02/14/25 PC RESUBMITTAL 4 10/01/25 FIELD REVISION LO T 1 LO T 2 LOT3 LO T 4 LOT5 LO T 6 LOT7 LOT9 LOT8 LOT10 LOT11 LOT12 LOT13 LOT14 LOT15 LOT16 LOT17 LOT18 * * * * * ** * * * * * * * * 55 F R E E W A Y WARNER AVE. GR A N D A V E . T T TT T T T T T T T T 15 0 6 1504 15 0 2 1500 1530 1532 1516 1518 1522 1526 1524 1520 1538 1536 1544 15 0 8 15 1 0 15 2 8 15 3 4 156 0 155 4 154 8 154 0 157 0 AREA OF SCOPE 1 2 3 4 18 V. I . F . 9' - 8 " 9' - 8" 27' - 2" 9' - 0" 15' - 6" 3 4 5 6 7 7 8 9 20 ' - 0 " 10 A-2.1.1 4 A-2.1.11 A-2.1.1 3 A-2.1.1 2 191 SF GENERAL MAINTINACE STORAGE 44 SF SUPPLIES 4' - 6 " 69 SF TRASH ENCLOSURE 1' - 2"8' - 4" 12 ' - 4 " 04 12 05 06 1' - 2"10' - 0" MIN. 9" 14 15 8' - 4" 16 24" MIN. CLR. 60 " M I N . C L R . 17 19 0' - 9" (E) 4' - 0" 5' - 0" MIN. 20 5' - 0 " M I N . A-2.1.1 4 A-2.1.11 A-2.1.1 3 A-2.1.1 2 6' - 0"3' - 7" 4' - 4" EQ EQ EQ EQ A-2.1.1 4 A-2.1.11 A-2.1.1 3 A-2.1.1 2 1/ 2 " / 1 ' - 0 " 11 27' - 2" 13 ' - 8 " 13 PROJECT NUMBER: DATE: ISSUES / REVISIONS SEAL CHECKED BY: DRAWN BY: DATE DESCRIPTIONNO. a r c h i t e c t s 15375 Barranca Pkway . Ste. A-216 Irvine, CA 92618 T: 949.788.9223 F: 949.788.0716 SNIHS Y K S E Expires JANUARY 2027 RTADIVA D CT ET nia r NCE I tat No.C18642 HS ialCfoef I o S CRE L 09/05/24 PC SUBMITTAL KEYNOTES A-2.1 Author Checker 24-09-05 0624 1540 E WARNER AVE, 1560 & 1570 BROOKHOLLOW DRIVE SANTA ANA, CA 92705 BROOKHOLLOW OFFICE PARK STORAGE & TRASH ENCLOSURE 1560 ENLCOSURE PLANS 1/4" = 1'-0" TRASH ENCLOSURE @ BLDG 1560 - DEMOLITION PLAN1 1/4" = 1'-0" TRASH/ STORAGE ENCLOSURE @ BLDG 1560 - PROPOSED PLAN2 1 (E) CONC. PAD TO REMAIN 2 (E) TRASH ENCLOSURE TO BE REMOVED 3 LINE OF RIGHT OF WAY 4 LINE OF NEW PERMANENT EASEMENT 5 8" CMU WALL 6 TWO 3 YD. TRASH BINS 7 METAL SWING GATES 8 NEW PARKING STALL 9 NEW DOUBLE STRIPING PER CITY REQ. 10 NEW WHEEL STOP 11 SLOPED CORRUGATED METAL ROOF 12 6"X 6" CONCRETE CURB 13 STRUCTURAL BEAM BELOW 14 PROVIDE LANDSCAPING FOR SCREENING 15 95 GALLON BIN 16 TEMPORARY GOLF CART PARKING 17 PROVIDE LEVEL AREA @ DOOR, NOT TO EXCEED 2% SLOPE 18 REMOVE SECTION OF (E) SIDEWALK & CURB 19 (N) 6" CONCRETE CURB, PAINT RED 20 EXTEND PAVED SIDEWALK TO PROVIDE MIN. 5' WIDTH @ DOOR LANDING KEYPLAN 1/4" = 1'-0" ENCLOSURE @ BLDG. 1560 - REFLECTED CEILING PLAN3 1/4" = 1'-0" TRASH/ STORAGE ENCLOSURE @ BLDG 1560 - ROOF PLAN4 1 02/14/25 PC RESUBMITTAL 2 04/24/25 PC RESUBMITTAL 4 10/01/25 FIELD REVISION NOTES 1.LANDSCAPE TOOLS AND PROPERTY MAINTENANCE EQUIPMENT WILL BE STORED IN THE STORAGE. 4 4 4 4 4 4 LO T 1 LO T 2 LOT3 LO T 4 LOT5 LO T 6 LOT7 LOT9 LOT8 LOT10 LOT11 LOT12 LOT13 LOT14 LOT15 LOT16 LOT17 LOT18 * * * * * ** * * * * * * * * 55 F R E E W A Y WARNER AVE. GR A N D A V E . T T TT T T T T T T T T 15 0 6 1504 15 0 2 1500 1530 1532 1516 1518 1522 1526 1524 1520 1538 1536 1544 15 0 8 15 1 0 15 2 8 15 3 4 156 0 155 4 154 8 154 0 157 0 LOT 1 LOT2LOT3LOT4LOT5LOT6LOT7LOT9LOT8LOT10LOT11 LO T 1 2 LOT13 LO T 1 4 LO T 1 5 LO T 1 6 LOT17LOT18********* * * * * * *55 FREEWAYWARNER AVE. GRA N D A V E . TTTTT T T TT T T T150615041502150015301532151615181522152615241520153815361544 1508 1510 15281534 1560155415481540 1570 AREA OF SCOPE 1 2 3 15 15 15' - 6" 9' - 0 " 10 ' - 2 " 4 5 6 7 A-2.24A-2.2 8 A-2.2 6 A-2.2 7 202 SF STORAGE 61 SF TRASH ENCLOSURE 11 0708 7' - 2" (E) PARKING(E) PARKING 13 1414 9"9" 8" 16 17 60 " M I N . C L R . 24" MIN. CLR.18 6' - 4"8"6' - 4"1' - 6" 4 A-2.24A-2.2 8 A-2.2 6 A-2.2 7 1/ 2 " / 1 ' - 0 " 15' - 6" 20 ' - 6 " 10 12 8' - 0 " 8' - 1 0 " 8910 7' - 0 " 414 7 8 9 10 4 89104 1' - 0 " 7' - 0 " 8' - 0 " 1489104 1' - 0 " 7' - 0 " 8' - 0 " 14 1570 ACCESSIBLE PATH OF TRAVEL, MAX SLOPE 1:20 IN DIRECTION OF TRAVEL & MAX. CROSS SLOPE 1:48 PROJECT NUMBER: DATE: ISSUES / REVISIONS SEAL CHECKED BY: DRAWN BY: DATE DESCRIPTIONNO. a r c h i t e c t s 15375 Barranca Pkway . Ste. A-216 Irvine, CA 92618 T: 949.788.9223 F: 949.788.0716 SNIHS Y K S E Expires JANUARY 2027 RTADIVA D CT ET nia r NCE I tat No.C18642 HS ialCfoef I o S CRE L 09/05/24 PC SUBMITTAL KEYNOTES A-2.2 A.A D.S. 24-09-05 0624 1540 E WARNER AVE, 1560 & 1570 BROOKHOLLOW DRIVE SANTA ANA, CA 92705 BROOKHOLLOW OFFICE PARK STORAGE & TRASH ENCLOSURE 1570 ENCLOSURE PLANS 1/4" = 1'-0" TRASH/ STORAGE ENCLOSURE @ BLDG 1570 - DEMOLITION PLAN1 1/4" = 1'-0" TRASH/ STORAGE ENCLOSURE @ BLDG 1570 - PROPOSED PLAN2 1 (E) CONC. PAVING TO BE REMOVED 2 (E) CONC. CURB TO BE PARTIALLY REMOVED 3 (E) ASPHALT TO BE PARTIALLY REMOVED FOR NEW CONC. PAD 4 8" CMU WALL W/ STUCCO VENEER FINISH 5 (1) 3-YD TRASH BIN 6 NEW CONC. PAD 7 METAL SWING GATES 8 STEEL COLUMN PER STRUCTURAL DRAWINGS 9 PERFORATED SHEET METAL, REVAMP COMPLEX HONEYCOMB RP031, T002-BK08 FINISH 10 SLOPED CORRUGATED METAL ROOF 11 6"X 6" CONCRETE CURB 12 STRUCTURAL BEAM BELOW 13 95 GALLON BIN 14 PROVIDE LANDSCAPING FOR SCREENING 15 (E) CONC. CURB TO REMAIN 16 TEMPORARY GOLF CART PARKING 17 PROVIDE STRIPING PER CITY OF SANTA ANA STANDARDS, SEE DWG 9/A-2.2 FOR EXTENT OF STRIPING 18 PROVIDE LEVEL AREA @ DOOR, NOT TO EXCEED 2% SLOPE KEYPLAN 1/4" = 1'-0" TRASH/ STORAGE ENCLOSURE @ BLDG 1570 - ROOF PLAN3 1/4" = 1'-0" ENCLOSURE @ 1570 - EAST ELEVATION4 1/4" = 1'-0" ENCLOSURE @ 1570 - NORTH ELEVATION6 1/4" = 1'-0" ENCLOSURE @ 1570 - SOUTH ELEVATION7 1/4" = 1'-0" ENCLOSURE @ 1570 - WEST ELEVATION8 1 02/14/25 PC RESUBMITTAL 2 04/24/25 PC RESUBMITTAL 4 10/01/25 FIELD REVISION A 07/22/25 BID CLARIFICATION NOTES 1.LANDSCAPE TOOLS AND PROPERTY MAINTENANCE EQUIPMENT WILL BE STORED IN THE STORAGE. 1/16" = 1'-0" ACCESSIBLE PATH OF TRAVEL DIAGRAM9@ BLDG. 1570 4 4 4 4 1. NOTES: CONTRACTOR TO SUPPLY AND INSTALL ALL NECESSARY HINGES, CANE, BOLTS AND LATCHES, ETC. AS REQUIRED FOR OPERATIONAL GATES. LATCH SHALL POSITIVELY ENGAGE TO PREVENT WIND MOVEMENT. 4 HINGES REQUIRED PER GATE BOLTS AND ANCHORS ATTACHED PER JAMB DETAILS GATE LATCH 3/16" X 3" BAR 20 GA. G.I. SIDING WITH 4" RIBBED PATTERN SPOT WELDED TO FRAME (PAINT) DOUBLE LOCKABLE CANE BOLT PE R D O O R S C H E D U L E PER PLAN A-7.0 4 A-7.0 3 A-7.0 2 1/2" DIA. X 4" TITAN HD BOLT @ 18" O.C. , START @ 6" FROM TOP AND BOTTOM OF GATE PANEL 8" CMU WALL/ W PLASTER FINISH,REFER TO STRUCTURAL DWGS 2x2x3/16" STEEL TUBE FRAME 20 GA. G.I. SIDING WITH 4" RIBBED PATTERN SPOT WELD TO FRAME - PAINT 1X3X1/4" ANGLE W/ FILLET WELDS TO FRAME 3X4X4 BUTT HINGES EA. GATE WELDED TO ADJACENT ANGLE 2X4X1/4" STEEL TUBE, BOLTED TO CMU WALL DRILL 1" DIA. HOLE IN OUTER WALL FOR INSTALLATION OF BOLT, PLUG HOLE AFTER INSTALLATION W/ NEOPRENE PLUG 1/2" DIA. X 4" TITAN HD BOLT @ 18" O.C. , START @ 6" FROM TOP AND BOTTOM OF GATE PANEL 2"5"2" MAX. 1"3" GATE FRAME PIPE SLEEVE TO RECEIVE LOCK ROD 1/4" TYP. 3/4" ROD U-BOLT WELDED TO GATE FOR LOCK 1/2" PLATE W/ SLOTTED HOLE FOR LOCK WELDED TO ROD CENTER LINE OF TUBE DRILL HOLE IN CONC. TO RECEIVE 2" LONG PIPE SLEEVE SET IN NON-SHRINK GROUT (ONE HOLE EACH FOR OPEN AND CLOSED POSITION) 4"3/8" BOTH SIDE PIPE SLEEVE TO RECEIVE 3/4" O.D. ROD HASP FOR LOCK & KEY @ OUTSIDE OF ENCLOSURE YARD 3"3/8" BOTH SIDE PIPE SLEEVE TO RECEIVE 3/4" O.D. ROD 1/ 4 " 2" 3 3 / 4 " 2" 1" 1" 2" 5" 3" 1/2" PLATE W/ SLOT FOR HASP 1/2" THICK PLATE LOCK HOLE 3/4" O.D. ROD PIPE SLEEVE TO RECEIVE 3/4" O.D. ROD HOLLOW METAL FRAME MASONRY ANCHOR @ 24" O.C. SEALANT DOOR, AS SCHEDULED WEATHER STRIPPING ANCHORS (3 - MIN. PER JAMB) 8" CMU WALL EXTERIOR INTERIOR DOOR, SEE SCHEDULE PRE-FINISHED METAL FLASHING MASONRY ANCHOR BOND BEAM 8" CMU WALL EXTERIOR INTERIOR 1 21/ 2 " M A X . METAL THRESHOLD SET IN SEALANT DOOR, AS SCHEDULE HOLLOW METAL FRAME EQ.EQ.W H H W TYPE A TYPE B W H TYPE C PROVIDE 10" KICK PLATE @ DOOR 06 & 08 A. B. C. D. E. F. ALL DOORS SERVING AN OCCUPANT LOAD OF 10 OR MORE SHALL COMPLY WITH CBC SECTION 1003.3.1, 1003.3.1.2, 1003.3.1.3, 1003.3.1.4, 1003.3.1.5 & 11B-404.2.3 ALL HARDWARE TO BE CBC ACCESSIBLE, PER CBC 11B-404.2.7 AND CBC 11B-309.4. WHERE KEY-LOCKING HARDWARE IS USED POST A SIGN ADJACENT TO THE REQUIRED MAIN EXIT DOOR WITH 1" LETTERING STATING "THIS DOOR MUST REMAIN UNLOCKED WHENEVER BUILDING IS OCCUPIED" MAIN EXIT ONLY. MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 5 POUNDS (38N) FOR EXTERIOR AND INTERIOR DOORS, SUCH PULL O R PUSH EFFORT BEING APPLIED AT RIGHT ANGLES TO HINGED DOORS & AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE UTILIZED TO MEET THE ABOVE STANDARDS. WHEN FIRE DOORS ARE REQUIRED, THE MAXIMUM EFFORT TO OPERATE THE DOOR MAY BE INCREASED TO THE MINIMUM ALLOWABLE BY THE APPROPRIATE ADMINISTRATIVE AUTHORITY, NOT TO EXCEED 15 POUNDS (66.72N), PER SECTION 11B-404.2.9 CONTRACTOR TO VERIFY ALL DOOR DIMENSIONS. DOOR OPENING SIZES INDICATED ARE NOMINAL; VERIFY THAT FRAME AND DOOR ASSEMBLY FIT WITHIN OPENING DIMENSIONS. ALL DOORS TO BE PROVIDED WITH SINGLE ACTION LEVER OR PANIC HARDWARE OR REMAIN UNLOCKED DURING BUSINESS HOURS (GROUP B OCCUPANCY). EXTERIOR STORAGE 1 2 CONCRETE SLAB GATE, AS SCHEDULED 1/ 2 " M A X . (E) ASPHALT PROJECT NUMBER: DATE: ISSUES / REVISIONS SEAL CHECKED BY: DRAWN BY: DATE DESCRIPTIONNO. a r c h i t e c t s 15375 Barranca Pkway . Ste. A-216 Irvine, CA 92618 T: 949.788.9223 F: 949.788.0716 SNIHS Y K S E Expires JANUARY 2027 RTADIVA D CT ET nia r NCE I tat No.C18642 HS ialCfoef I o S CRE L 09/05/24 PC SUBMITTAL A-7.0 A.A D.S 24-09-05 0624 1540 E WARNER AVE, 1560 & 1570 BROOKHOLLOW DRIVE SANTA ANA, CA 92705 BROOKHOLLOW OFFICE PARK STORAGE & TRASH ENCLOSURE DOOR SCHEDULE, GATE & DOOR DETAILS N.T.S. TRASH ENCLOSURE1N.T.S. TRASH ENCLOSURE JAMB2 N.T.S. GATE LATCH @ TRASH ENCLOSURE3 N.T.S. CANE BOLT SECTION & ELEVATION4 3" = 1'-0" EXTERIOR DOOR HEAD/JAMB SIM.6 3" = 1'-0" EXTERIOR DOOR HEAD7 3" = 1'-0" DOOR THRESHOLD8 DOOR NUMBER LOCATION W (WIDTH)H (HEIGHT)TYPE DOOR FRAME DETAILS HDWR SET NOTESMATERIALFINISHMATERIALFINISHHEADJAMBTHRESH. ENCLOSURE @ BLDG. 1544 01 RESTROOM 3' - 0"7' - 0"A 7/A-7.0 6/A-7.0 8/A-7.0 01 02 STORAGE 3' - 0"7' - 0"A 7/A-7.0 6/A-7.0 8/A-7.0 02 03 STORAGE 12' - 0"7' - 0"C ENCLOSURE @ BLDG. 1560 04 SUPPLIES 3' - 0"7' - 0"A 7/A-7.0 6/A-7.0 8/A-7.0 02 05 TRASH 8' - 0"7' - 6"B 06 GENERAL MAINTINANCE STORAGE 8' - 0"7' - 6"B 5/A-7.0 03 ENCLOSURE @ BLDG. 1570 07 TRASH 6' - 0"7' - 6"B 08 STORAGE 6' - 0"7' - 6"B 5/A-7.0 03 DOOR SCHEDULE DOOR LEGEND HARDWARE SETSDOOR ABBREV. AL CL CT (E) FF FL FRP GA HC HF HM HML IG ML NR PT PC PG PH PL SC SG ST STN TG WD ALUMINUM CHAIN LINK CLEAR TEMPERED GLASS EXISTING FACTORY FINISH FIRELITE GLASS FIBERGLASS REINFORCED POLYESTER GALVANIZED HOLLOW CORE HOLLOW METAL SLIDING FOLDING HOLLOW METAL HOLLOW METAL KNOCKDOWN INSULATED GLASS METAL KNOCK DOWN NON RATED PAINT POWDER COATED PAINT GRADE WOOD PANIC HARDWARE PLASTIC LAMINATE SOLID CORE SPANDREL GLASS TEMPERED STAIN GRADE WOOD STAINED FINISH (CLEAR SEAL) TEMPERED GLASS WOOD HARDWARE GROUP: 01 RESTROOM, (DOOR 01) DOOR: SINGLE, HM, NON RATED QTY DESCRIPTION MODEL FINISH MANUF. (3 EA) HINGE 3CB1 4.5X4.5 626 IVE (1 EA)CLASSROOM LOCK B561 626 FAL (1 EA) CLOSER 9300 BC 626 NOR (1 SET) SEALS S88 -PEM (1 EA)THRESHOLD (1 EA) SWEEP 309 ANB -PEM (1EA)WEATHER STRIP (1 EA)GASKET PERIM ETER DOOR NOTES 1 02/14/25 PC RESUBMITTAL 2 04/24/25 PC RESUBMITTAL 4 10/01/25 FIELD REVISION HARDWARE GROUP: 03 STORAGE @ 1560 & 1570 (DOOR # 06 & 08) DOOR: MTL. SWING GATE QTY DESCRIPTION MODEL FINISH MANUF. (4 EA) HINGE 3CB1 4.5X4.5 626 IVE (1 EA)STOREROOM LOCK F-5811(Q)626 FAL (1 EA) 10" KICK PLATE (1 EA)FLUSH BOLT (ON LEAF W/O LEVER) HARDWARE GROUP: 02 RESTROOM, (DOOR 02 & 04) DOOR: SINGLE, HM, NON RATED QTY DESCRIPTION MODEL FINISH MANUF. (3 EA) HINGE 3CB1 4.5X4.5 626 IVE (1 EA)STOREROOM LOCK F-5811(Q)626 FAL (1 EA) CLOSER 9300 BC 626 NOR (1 SET) SEALS S88 -PEM (1 EA)THRESHOLD (1 EA) SWEEP 309 ANB -PEM (1EA)WEATHER STRIP (1 EA)GASKET PERIM ETER 3" = 1'-0" THRESHOLD @ STORAGE GATE5 4 4