HomeMy WebLinkAbout10180506_1640 E. 1ST - Plan (2)Planning & Building Agency Building and Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.ora ELECTRICAL SIGN REQUIREMENTS Code references are to the 2010 California Electrical Code (CEC) All signs require Planning Department approval. All electrical signs require electric plancheck and permit. 1. Manufacturer's instructions are required at the time of submittal. C-11: 3-21-2011 2. Submit detailed installation instructions including diagrams to the Building Department for plan review at the time of submittal. Plans must include appropriate items noted by this bulletin. 3. Cash or surety bond in the amount of $200.00 is required at time of issuance for each address. The cash or surety bond will be refunded after all required finals. A building permit is also required - except for open or highlight neon lighting. Installation Requirements: CONTACT FIELD INSPECTOR PRIOR TO SIGN INSTALLATION. (SEE SECTION G OF THIS BULLETIN) 1. Conductors and equipment shall comply with California Electric Code Article 600. 2. All metal parts of a sign shall be bonded in the manner specified in Article 250. Isolated metal parts are permitted to be bonded by using an external green insulated conductor. Equipment grounding & bonding conductors must be sized by 110.26 and protected from physical damage. Minimum size is 14 AWG. CEC 600.7 3. A listed disconnect switch in the power supply primary, shall be installed within sight of sign or have permanently installed means for locking in an "OFF" position. This is also true for a transformer enclosure. CEC 600.6 4. A listed receptacle or an approved termination device shall be used for each neon electrode. To relieve stress at terminations, tubing shall be supported with listed tube supports in an approved manner within six inches of electrode connection. CEC 600.41 & 600.42 5. Every electric sign of any type shall be listed by an approved testing laboratory and shall be installed in conformance with this listing. That includes "1 of x", "2 of x" labeling for each separate unit of a multi-unit sign. CEC 600.3 6. All "can" letters and transformers housings shall have section labels that are readily visible after installation. CEC 600.4 7. Transformers shall be located where accessible and be securely fastened in place. Page 1 of 2 When not inside the sign, they need a 3 foot high x 3 foot wide x 3 foot deep workspace. Transformers are permitted to be located in attics or canopies provided there is a passageway at least 3 feet high x 2 feet wide with a minimum 12 inch catwalldwalkway from the point of entry. Transformers must be securely fastened and independent of T- bar when above a suspended ceiling. No part of sign mav be fed with flexible cord when located above T-bar ceilings. CEC 600.21(E&F) & 400.8 8. Adequate illumination shall be provided for all working spaces about electrical equipment. This applies to attics and canopies when entry is required to service or inspect the equipment. At least one switch is required at entrance. CEC 110.34 & 600.21 ,9. Doorway to an attic or canopy space shall be minimum 3 feet by 2 feet wide. CEC 600.21(E) E. Open neon outline or highlight lighting. 1. To be treated as a sign by this department. However, Section D-5 & D-6 of this bulletin · will not apply. 2. Neon tubing shall be located where not normally exposed to physical damage. Open neon tubing below 9 feet shall be protected from physical damage by an approved shielding method. CEC 600.30 and 1 10.34(E) F. Light-Emitting Diode (LED) Signs 1. Will be treated as a sign by this department. All sign rules in sections A, B, C, D, F, and G will apply as appropriate. 2. LED illumination for signage must be a listed or recognized component. Many LED manufacturers specify particular brands and models of transformers some do not. Manufacturer information to clarify this issue is required on LED sign plans. 3. Unlisted LEDs may not be used in an electrical sign or as permanently installed illumination. 110.3 4. Please have packaging or catalog cut-sheets on hand for inspector to review when LED modules do not bear listing symbols. G. Inspections 1. Contact an Electrical Inspector one (1) workday (minimum) in advance of installation to arrange a site meeting on dav of installation. 2. Call for inspection Monday through Friday, 8:00- 8:30 a.m. at (714) 647-5821. Approved prints and the job card must be on site for inspection. Page 2 of 2 13 SIGN COMPONENTS MANUAL (SAM)October 1, 2013 1. These products are only suitable for connection to the provided UL R/C Class 2 DC power source according to the power source's UL conditions of acceptability. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited supplies. 3. These products may be cut to create voids or segments through any portion on the sheet. 4. Suitable for dry and damp locations. 5. These products are required to be enclosed or protected from weather. 6. These products are intended only for factory installation in new signs. Class 2 LED Module, Cat. Nos. 3M™ LED High Efficiency Light Panel 1. These products have been evaluated for use only when connected to a power source that complies with Class 2 or LPS requirements for energy limited power supplies. 2. Suitable for dry and damp locations. 3. These products are required to be enclosed or protected from weather. 4. These products are intended only for factory installation in new signs. 5. Grounding of frame to supply ground is required. Suitability of bonding for grounding connection is to be determined in final application. 6. Suitability of LED panel mounting shall be determined in final application. 7. Suitability of LED power source shall be determined in the final application. Polymeric adhesive systems, Cat Nos. DP-810 and DP-810 Black designated "Scotch-Weld" 1. The use of these adhesive systems shall be employed in applications wherein the limitations specified in Table A are not exceeded. 2. These systems may be used for securement to any combination of surfaces Listed in Table A, provided the use of temperature is no higher than the lowest temperature rating of any element of the combination 3. The materials have been evaluated for adhesive compatibility and stability only. No electrical or flammability tests have been performed on the adhesive by itself. The Engineer must consider the need to investigate the part of other than the properties investigated, in accordance with the applicable UL-end product Standard or requirements outlined in the Standard for Polymeric Materials - Use in Electrical Equipment Evaluations, UL 746C. 4. The suitability for use when exposed to oil, chemicals, refrigerant, soaps, X-rays, ultraviolet light and the like, has not been determined. 5. These systems are suitable for application to smooth flat surfaces. The need for adhesive bond strength test when applied to another surface or configuration shall be determined in the particular end use application. 6. These systems are also suitable where exposed indoors or outdoors to high humidity or occasional exposure to water. The minimum temperature rating is -35°C (-31°F). 7. The adhesive shall be applied in accordance with the manufacturer's instruction. All surfaces shall be clean and dry. The manufacturer's instructions regarding cure time shall be followed. 8. The adhesive bond strength specified in Table A includes a safety factor of four. 9. When considering the use of any adhesive covered by this Report, the strength of the adhesive joint used to position parts shall be capable of withstanding the maximum force that might be applied to the joint in the end application. This is called the bond strength and includes static load as well as wind loading(dynamic load). The minimum square inches of adhesive to use is determined by dividing the maximum load in pounds by the adhesive bond strength specified in Table A. TABLE A Cat. Nos.DP-810, DP-810 Black Thickness: 0.076 mm (0.003 in) Substrate Combination Max. Operating Temp.Adhesive Bond °C (°F)Strength(PSI) Stainless Steel to Stainless Steel 60 1000 Aluminum to Aluminum 60 980 Polycarbonate to Polycarbonate 60 180 Magnesium to Magnesium 60 870 Acrylonitrile Butadiene Styrene to Acrylonitrile 60 310 Butadiene Styrene Cat. Nos.DP-810, DP-810 Black Thickness: 0.254 mm (0.010 in) Substrate Combination Max. Operating Temp.Adhesive Bond Strength °C (°F)(ps') Stainless Steel to Stainless Steel 60 940 Aluminum to Aluminum 60 900 Polycarbonate to Polycarbonate 60 190 Magnesium to Magnesium 60 690 Acrylonitrile Butadiene Styrene to Acrylonitrile 60 430 Butadiene Styrene AA LED SUPPLY CORP E325964 9441 VALLEY BLVD. ROSEMEAD, CA 91770 Class 2 LED modules, Models LS0723*, LS0766x, LS0769*, LS0776*, where that x may be R, Gi B or Y indicating LED Color. . October 1, 2013 SIGN COMPONENTS MANUAL (SAM) 14 1. These products are only suitable for connection to the output of a UL Listed or R/C Class 2 Power Supply rated 12VDC. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 requirements. 3. These products are rated per the Table below. When units are connected to a Class 2 circuit, their number is to be limited to draw a total wattageof_no_greater than the secondary current rating of each Class 2 power supply. ]Part No. ]LS0723x ]LS0766x jLS1769x iLS0776x Operating Current per Watts per module Voltage module 12Vdc 40mA 0.48W 12Vdc 30mA 0.36W 12Vdc 75mA 0.9ow 12Vdc 60mA 0.72W 4. These products are suitable for use in dr'y, damp and wet locations without additional enclosures. Class 2 LED Modules, Model AA-0766EC-XX, where XX can be any alpha characters or blank to represent different light color 1. These products are only suitable for connection to a Class 2 power source rated 12 Volt DC or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited circuit and which is rated greater than 12V DC. 3. These Class 2 LED modules are each rated as noted in the electrical ratings tables. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply, 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at 12 Volts DC or less. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. These products may be secured in place in the end product by any means available. ABC SIGN PRODUCTS E80767 2028 SE FRONTAGE RD FT COLLINS, CO 80525 Lampholder adapter, Type LH. 1. This device is suitable for use in indoor or outdoor extruded aluminum awning frames. 2. This adapter is intended for use only with Listed, single or double contact, recessed lampholders (Cat. No. 530, Kulka) which snap-fit into, and are securely held by, the adapter. The lampholder shall be held securely with or without a lamp in place. 3. This adapter is intended to complete the enclosure housing of insulated live parts only. 4. This device shall be installed in an aluminum extrusion in accordance with the "Installation Instructions" supplied by the manufacturer in the smallest shipping container. Sign Face Tensioning System, Model ABC. 1. The suitability of these tensioning systems in combination with any R/C (UYMR2) Flexible Sign Face Material to prevent entrance of water in outdoor sign applications shall be determined in the end product. 2. This product has not be evaluated for use as an electrical enclosure. 3. Tensioning clips shall be spaced as described in the Installation Instructions. 4. When employed in a sign with any frame dimension greater than 6 feet the sign shall be provided with a means to prevent billowing. 5. The mounted assembly of sign face material in these tensioning systems shall comply with the electrical and thermal spacing requirements of UL 48 6. These clips have been determined to be suitable with any R/C Flexible Sign Face Material of min. 0.020 inches (0.51 mm) thick, suitability for use with a material of lesser thickness shall be determined in the end product. ABLE APPLIED TECHNOLOGIES LTD E329973 BOUNDARY HOUSE BUSINESS CENTER BOSTON MANOR RD LONDON, W7 2QE UNITED KINGDOM Class 2 LED Modules, Models MS-P40XXX-XX Series, where XXX-XX may be any alphanumeric characters. 1. These LED panel of these products are powered by Class 2 power source rated at max. 15 VDC, 5 amps. 2. These products are suitable for use in dry and damp locations. 3. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 4. When provided with a power supply, in the end product the power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 5. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 limits. ACROSENTEC CO LTD E363566 253-9 GOCHUN-DONG UIWANG-SHI , GYEONGGI-DO 437-801 REPUBLIC OF KOREA Class 2 LED Modules, Models ASPCH-@+24-$-%-&, ASFCH-@-#-24-$-%-&, and ASMX-@-A-24-*-!, where @ can be any 2 to 4 alphanumeric code, # can be any 3 to 5 alphanumeric code, $ can be any 2 or 3 alphanumeric code, % can be any 1 to 4 alphanumeric code, & can be any 3 to 9 alphanumeric code, A can be any 3 to 5 alphanumeric code, * can be any 3 to 6 alphanumeric code, ! can be any 2 to 9 alphanumeric code. 1. These products are only suitable for connection to a Class 2 power source rated 27 V DC or less. 93 SIGN COMPONENTS MANUAL (SAM)October 1, 2013 4. These products may be secured in place in the end product by any means available. Class 2 Low Voltage Connectors, Model LVC2, LVC4, SNAP-KONEK 111, and STICK-KONEK. 1. These devices are not suitable for interrupting the flow of current by connecting or disconnecting. 2. These products are only suitable for connection to a Class 2 power source, Class 2 supply rated max. 15 Volts AC or max. 30 Volts DC or less. 3. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limits. 4. These products are suitable for use in dry, damp and wet locations. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. Modules can be installed to interconnect leads in the field or pre-installed. 7. These products may be secured in place in the end product by mechanical securement or double sided adhesive tape. 8. For Model LVC2 and LVC4, suitable for connecting stranded wires which are 18,20 or 22 AWG with compatible wire guide inserts. 9. For Model SNAP-KONEK Ill, suitable for connecting single conductor per channel either AWM wires 18-24 AWG, or Power- Limited Circuit Cables type CL3P, CL3R, CL3, CL3X, CL2P, CL2R, CL2, CL2X and PLTC. 10. The Model STICK-KONEK base and button are used to join LED strips, LED bars, or LED leads wires. MAGTECH INDUSTRIES CORP 5625-A S ARVILLE ST E314969 LAS VEGAS, NV 89118 Class 2 LED Module, Cat No. LP12060P-08, LP12060P-09, LP12060P-10, LP12060P-11,LP12060P-12, LP24060P-22, LP24060P-23,LP24060P-24. 1. These power supplies have a maximum of one Class 2 output. The output of these power supplies has been evaluated to Class 2 output requirements for dc circuits. 2. These products with Class 2 outputs are suitable for use in dry, damp and wet locations. 3. In the end product, power supply spacing to other heat producing components shall be minimum 4 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 4. When used in wet locations, each unit shall be provided with Listed (QCRV) 1/2 inch, liquid tight conduit fittings on both primary and secondary circuits. MATRIX FRAME E351057 FLEVOWEG 27 2318 BZ LEIDEN, THE NETHERLANDS Class 2 LED Module, "Lightbox CREE XP LEDstrip". 1. These products are suitable for use in Dry and Damp Locations Only and may only be supplied with a Class 2 power source with Current limit rated max. 2.5 Amps or less. 2. These products are only suitable for connection to a Class 2 or LPS power source, rated 24 Volt DC or less. 3. These products shall be mounted in equipment, which provide a suitable overall enclosure. 4. A maximum of 4 Led strips are allowed to be mounted in a row, as detailed in the mounting instructions. 5. These products may only be installed in a metal based enclosure (frame) that is able to transfer the heat that comes from the LEDs over the metal-core Printing Wiring Board into the ambient. MATRIX FRAME FLEVOWEG 27 E358648 2318 BZ LEIDEN, THE NETHERLANDS Class 2 LED driver box, Model A120606. 1. The power supply has been evaluated to Class 2 output requirements for dc circuits with a maximum of one Class 2 output. 2. The Class 2 output of the power supply is suitable for use in dry and damp locations only. 3. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 4. These products shall be enclosed in the end product. 5. These products are suitable for factory wiring only. 6. The load powered by the Class 2 output of the power supply rated at max 30 VDC or less are suitable for use in dry, damp and wet locations. 7. The suitability of strain relief, current leakage, and grounding tests shall be determined in the end-use product. 8. AC input and output connectors are not polarized. Suitability shall be determined in the end use. MAXBRITE LED LIGHTING TECHNOLOGY LLC E313209 1740-B JUNCTION AVE. SAN JOSE, CA 95112 Class 2 LED Illumination Module, Cat. No. OTH-308X 10x18-01 Series, x: indicate the COLOUR: R-Red, Y-Yellow, B-Blue, G- Green, W-White, YO-Yellow Orange. 1. These products are only suitable for connection to a UL Listed or Recognized maximum Class 2, 12 V DC power source. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 circuit limits. 3. Class 2 LED module, OTH-308X10x18-01 Series When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. Each module is rated 0.2A. 4. These products are suitable for use in dry, damp or wet locations. 5. These products are not required to be enclosed or protected from the weather. Class 2 LED Module, PL5050 Polar series, x: indicate the COLOUR; CW-Cool White: PW-Pure White; VWV-Ware White; GL- Golden Yellow; RGB-RGB: Y-Bright Yellow: R-Bright Red, B-Vivid Blue, G-Mega Green, A-Aquamarine. POLAR X Series, TOMORROW'S LIGHT TODAY SIG ECOWHITE 0766EC *A. 0.6 W BLAZER LS-0766 0.5 W RED 0.7 W 4 TRAY 100 modules - 33'TRAY 100 modules - 33' $ 120.00 $150.00 DIMala LS-0723 0.72 W #Al RATAARD PL#¢ar-ON / 0.72 W TRAY 60 modules 0 20;'f,7 RAY 60 modules - 20'TRA $ 150.00 ' $160.00 $10 LE 20 watt DRIVER 40 wa AC INPUT: 100-240 Vac/0.3-0.154 50/60Hz DC OUTPUT: 12VDC /1.67A 4 WE USE "AA LED" BRAND 2 11.1 1 .941.1 LJ ,l=_fU (LP12060P, LP24060P)..1 77.00.2 r. A MANUFACTURERS RECOMMENDED INSTALLATION INSTRUCTIONS FOR SIGNS > All models are recognized under UL Standard for Safety for Electric Sign Components. UL 879. > These power supplies have a single output that complies with Class 2 output requirements. > The maximum rated output power is 60 watts. > Power supply spacing to other heat producing components shall be minimum 4 inches when minimum spacing to sidewails and top of enclosure is kept at minimum 2 inches. > Power supplies can be used in dry, damp and wet locations. > Disclaimer: > All of the above installation methods are recommended by the manufacturer. > All of the above installation shall follow and comply with all local NEC regulations. Option 1 UL listed UL listed junction box / junction box sm,PLTC. s..tr·vi ress:y,0,or sign box AC . . .DCUnit supply 1 - ,load METALLIC ArrING. Ul. LSTED FITTING. UL LSTED AND WATER l'IGHT AND WATER T:CHT IF USED IN WET LOCATIONS IF USEON WCT LOCAT*45 Option 2 Sign Bpx WRE NUTS 0NE :S E"OWN ON,14 COPOL. 9 M. to LEDs. Unit ACconnections - r Option 3 UL listed junction box, classified for outdoor use if used *2 in wet locations:_minumurn size 178*330x1O2H (mm) IHOV•I ONLY) .. CE'OF A ,CC»OUIT - 'i %4 Et Unit 2214#='=4 ' ACk-to Sign boxconnections- -2 4,=, ' € '* f • 1 *#.. 4. ../ I. 60' liD T•O. SUBJA; i i di 11i0FS WHEL EL, AN ' CON,31#(6 6-- SIGN FACE TO STREET 28' STORE FRONT JELOW:ONE SIGN 24 SQFT TWO §IGN 48 SQFT O If 172:R:01 11 0-2 O N 0 EXTF,l'OR Al TERATIONS/MODIFICATIQWS O KiM:. I™" -FO MATCH EXISTING6_ S CREE NIi S JI;ART Lrft r1 dCO 11" 0 L SIGN DIMENSION FOR BOTH SIGNS 916.$.DETAIL: PROPOSED S' DEEP a{ANNEL LETTERS WALL SIGH INTERNAUY iLLUIOUTED BY (12 V LE.O. LIGHT) SIGN FACE: lir Thick acrylk face with 3/1' Bronze trim cap. MATERIAL: Channel letters shall be fabricated by 0.04' thick aluminum and returns wl powder coated finish in Bronze color. AU ELECTRICAL COMPONENTS ARE TO BE U L RXED ..IL W..CAPi-IJL -- ASHYL\C ¥CEf SIGN FACE TO PARKING LOT 1 88 €410,-JOB ADDRES& 1640 E. FIRST ST. 889!gn@sb©global.net SANTA ANA, CA. - TEL: (626) 442-8033 1906 COREEN AVE. FAX: (626) 350-5343 & EL MONTE CA 9173] SCALE:' APPROXED BY:Nic DeAngeloSTATE LIC: #702474 U.L. APPROVED DATE: TRANSFCAMER BCC( wi DISCOMETS SMTCH 12 VTRANSFOAMER WHITE COLOR LE.D. LIGHT -- 3/lr X y SCREW -·4-10 SCREW PER LETTER W RAN HOLD , 10- e 2*FitSt -- - rarmers insurance - Maria Gubrrero C ·FirseSt EZFJ Esl'*S-t-- list.31·E¥1, st·S 1 r 1-648Andrea's 99,3Cent§-&Gifts L./ Caifornia Pollo Rotisserie & Grill ia del Jugall (i) luary - 2 WALLSIGN LOCATION Bari Pasta & Pizza 0 0 9 'J Santa Ana k Daily Deals ..r--11 1 Tacos Y Mariscos ® SinaloA 2 88 €4/9-JOB ADDRESS 1640 E. FIRST ST. 88sign@sbcolobal.net SANTA ANA, CA -TEL: (626) 442-8033 1906 DOREEN AVE. - FAX: (626) 350-5343 S. EL MONTE CA 91733 - SCALE:APPROVED'BY: STATE LIC: #702474 U.L. APPROVED DATE: . i f j disconnedfort .he monument sign(s) is-required or the dedicated circuit breaker(s) mus: .,lockable in the off p ndividua\\100-6 I be immediately from a ladder or chawith a2x3 foot access door & passage with21 (d)(d)ce soo-Agency. , & Buil of sanC\W Ana Planning ELECTRICAL PLAN APPROVAL , « This set of plans and specifications must be kept crl the job at all times and it Is unlawful to make any char,gss or alterations on same without written per- mission from the Department of Building Safety 1 City of Sarita Ana. 1 PERMITTYPE:*LECLEIG MECH GRAVING Ir .PERMIT# joi%;DEC)to / OCC. GROUP ·570 k*99 Llf t. }n.+ CONSTR. TYPE CODE EDITION 520\123 FLOOD ZONE 1 The approval of this plan and speclfications SHALL | NOT be held to permit nor be an approval of thoviolatE¥'6r any provisions of ANY City Ordinance FLOOD ZONE CERTE REQ'D YES CNOor State Law.App dby7 1) 83) )4 MICROFILM YES Ne) RADIANT BARRIER @ROOF YES Ja< dITY OF SANTA ANA RESIDENTIAL DEV. FEE .YE<NO, DEPARTMENT OF BUILDING SAFETY ' . - '' SCHOOL DISTRICT YESM@ e 4*%**2624;24214*2·44211*21*6:£4.6.4461984*4:12=2.' f 't iyE,Ikt*2---- CITY OP SANTA ANA 10190500 OUILOINO PORMIT APPLICATION WORKOH[!(IT •1'LEASE PRINT 3/2/01.mq*LL_1.2-_lt PROJECT ADDRESS:ilotlf) i=z )$ .I null[I: ft RAPIN 0 1 USE OF BUILOING:RESIDGNTIAL COMMURCIAL INDUOIRIAI.OTHIIR iTm:FE™aizliI* 0 MASTOR It)0 NATURE OF WORK: NEW ADD ALTtiR/T.k Ol!MO R(IROOP 14[!PAIR OION Plirl . _ ui, t22!glamaN!81.IERM101 - 1 ST FL. SP BASEMENT: YOWNO 2ND FL. . SP PATIO/UNCL. PA11O:401].111:QQ]l,89E TOTAL OF O™ER FLS: ,SF ReS. Re.MODEC 21-PRO=95-ST..05TMIHIM GARAGE,CARPORT:SF ALTER/1*,1.:Spt'.1JOB DESCRIPTION (non. Mitdontjal pmlocto - rovemoildtof thli application) : ce '0 U 6 009 |6*ZE 1 (RK®NRC®i*123*@CNI:lenim=ED I.LIJ 8.-I'.33 fit tERiliE #40# tj)* *gl® €€ , ILICERSEmiDESI Ef;*£323120 (K® 0 1 @[6*€1(MIREIAO Il 2229 E I , __ _ - 7 - GliRCD[£(, .-= r(3/Ki:23(1Ff*Elija CIRE@ID@5@(2IRR.@&144) -- __ - - €RB (RENP (==;- z ... =, _ -. - ,(<fgHN[9170 -- ... iRIRBQI#(REEKID - - -_ - :-_-_ ; Wbt¥Lk[IRZ, 8 - {EIR€iIZI) YK?@ Otl@) CI@ 9,553<(r)9 Ittvol€g•]213 1'.An 1 ,120-0 -CEEMERk %1 46©Oll® CUES®ZJLA[IZEdle 0 94.3,4[0,,&-/./.1.1 (NE3ZLE]D(i:2 f€)(Eift€28 *Bu-: ·44•/4 (-14.;Af /11%:AUrw, (-31-b6®ECEJU€20 -- BLDG $ $ -1 // - A.n /Ti/\ j \.eq„ INE) ali3 CITY OF SANTA ANA DEVELOPMENT FEES WORKSHEET .- ELECTRICAL PERMIT [pmjectAddms£ - RIZS=5-.=-H Contractor: Dc-Vt l-c,nnj< 2% Sij-)1Tenantfame.--A-' T 444- - -Address: 1 0) 06 Do r ge 4 4 ve. 1 Lfuilding oser: _wi--L-6, A*A/*l B City: 5: El A/le v,4, St.: CA Zip: 9 /733 Lddress:3 6*A-& SPA-l_.1aut 0 0 Contractor License No.: 70 2 4 7 Lt- -city: 56-41- b Ar,j St.:Zip: CA . 4 4 4,0 Contractor Email: 8 8 S '9 M ¢D 566 9'064 1 - 42 Phone:1-14 -334-- 5640.Phone: 62.6 - 44 1 -80 33 Contact Person: p Ad Contact E·Mall Strongly Recommended PLEASE PRINT: Contact Phone:(6ic) 451- 8% 43 NEW BUILDING r-7 OCCUPANCY CHANGE r-1 ELECTRICAL ITEM Count $ EACH 125 Volt Receptacle Outlets 1.25 Light Switches, Occupancy Sensors 1.36 LightFixtures .90 Air Conditioners, Heat Pumps 83.58 FaMory-Wired Units (SoWHook*J 21.39 Dedicated Circuits (15 or 20 AMP Recepfacks)21.39 Time Clock, Photo-Cell, Time Switch 10.43 Track-Light, Cable Tray, Special Raceway, Plugmold, Under-Floor Duct,21.39Plug-In Busway, Surface Duct, Etc. (Each 100 Feetoratly#acton the/804 SERVICE METERS & PANELS: Service Meter, Reset Meter, Subpanel, Switchboard, Motor Control Center, Transfer Switch, Busduct, or other Distribution Equipment changes or modifications. (=te #ams as needed Use this column if a Service - All others here Under 400 amperes 45.96 400 amperes to 1199 amperes 125.31 1200 amperes and over 208.79 POWER APPARATUS: Motor, Transformer, Welder, Industrial Equipment, Oven, Rectifier, Generator, Surge Arrestor, Water Heater, Photovoltaic Panel, or other Power Equipme,il changes or modifications (c,c-n:,sneed,0 Per HP, kW, or kVA 0 to 1 -33·08 Over 1 to 10 20.09 Over 10 to 50 39.86 Over 50 to 100 90.52 Over 100 to 500 130.06 1 Over 500 162.46 1 OFF,UE. L BLDG PMT RECEIPT OCCUPANCY TYPE APP FOR ELECTRICAL 06-24-2013 71-rl. ELECTRICAL ITEM Count $ EACH LOW VOLTAGE SYSTEMS - EACH: phone, data outlet, speaker, thermostat, door holder, doorbell, pull station, smoke detector, alarm device, card reader, etc. (ck-kerns) COMMERCIAL: FIRST 10 devices or outlets 29.22 Additional devices, each 2.76 Each control panel, power supply annunciator, switch or aux equip.13.93 RESIDENTIAL: Single Dwelling unit 31.67 Each add'I dwelling unit (2 to 20)27.86 Each add'I unit (-20 17.01 MISCELLANEOUS Light Standard (Pole) with 1 Fixture 21.39 Additional Fixtures -same pole 0.00 Power Pole (Tenwwy)88.90 Additional distribution poles 21.39 Swimming Pool, Spa, Fountain 104.45 Above ground spa 45.13 Demolition 41.79 SIGNS & neon/LED decorative lighting ($200 reA,Ad,ab s/gn bor,0 64.79 NEW or TOTAL REWIRE for SINGLE#AMILY DWELLI VGS SFD Per square foot .12. Garage Per square foot .12 SUBTOTAL $L P/C 65% of SUBTOTAL V MIN. FEE - Nonresidential) $63.28 -ISSUANCE & GenerN plan sAame $ 49.48 + 19.04 = $66.52 1 TOTAL $ 1SE{ONLY' 8, PEPAID APP-(12 GEC.2013 DATE 1- CITY OF SANTA Planning and Building Agency Planning Division 20 Civic Center Plaza PL.O.j IXG P.O. Box 1988 (M-20) Santa Ana. CA 92702 APPLICATION FOR SIGN& BULDING (714) 647-6804 AGE\(¥ www.santa-ana.org PERMIT AND CHECKLIST Name of Business: 34 4 A-) rl Al · Project Address:UUD E-. f 4-1 4-Zone: Applicant Name (print): DA-J Lon) 6-Phone No.:(?6,3 4*?-643, Mailing Address: 140,6 I),EMV 44' _ ·Fo. EE MW-lp Ch. 6/84 J' Applicant's Signature: )Date: 0 3 1/ U Suite Width: ttl. Elevation Height: 1 Proposed Signage (Quantity and Size): 1. Wall/Canopy:TU)0 U)44 aRAC 6 2. Freestanding:Height: 3. Other Signage: Existing Signage (Quantity and Size): 1. Wall/Canopy: 2. Freestanding:Height: 3. Other Signage: Note: Building Safety Division requires a $200 refundable bond per application. SIGN PROGRAM 94 YES U NO 1st Review Date:Planner: 5IO ·2nd Review:Planner: commenk. 0;**•1/ 60"4-y784£ 1,3T¥ 6( 4,4 P£06RAN, 626 90 -D3 Inspector: Inspector's Comments: SIGN PERMIT NO.2-0 / S - 5 [)1APPROVE U DENY cm\cntr-frm\sign permit - I. r 7/00 Planning & Building Agency Planning Division 20 Civic Center Plaza RO. Box 1988 (M-20) Santa Ana, CA 92702 (714) 667-2700 www.santa-ana.org -- 2 PLANNING DIVISION FEES Sheet 2 of 3 Effective 7/1/2013 MIW[IN,IM# I M•1111•MII 14•I•,22*fal: ADULT ENTERTAINMENT LAND USE PERMIT $1,414.06 $ CERTIFICATE OF COMPLIANCF $1,065.35 $ CHANGE OF ADDRESS REQUEST $1,030.59 $ HISTORIC EXTERIOR MODIFICATION (HEMA) $1,949.49 $ HISTORIC PROPERTY PRESERVATION AGREEMENL...................................... $ 3,935.87 $ (Mills Act Application) HISTORIC RESOURCES COMMISSION ACTION (Historic Designation)... $ 5,015.05 $ HOME OCCUPATION PERMIT $247.92 $ LAND USE CERTIFICATE Category 1 Batch#:24135 - 1/14/2014 ID: CHRISTINA Bazaars, Fiestas, Sidewalk Sales, Outdoor Auctions, Child Office: CTYH Trans#: 3 i of 1 4 - -LAU Care (8-14 children) and Ancilllary Massage Establishments... $ 350.43 MLLL,r• S Ref#: 2001295 Kept?:U1122293 -1/14/2U 14 11:56 AM Category 2 Transaction Total $439.92 Carnival, Circus, Outdoor Music, Concert, Arcade 88 SIGN CORP and ABC Licenqpq $628.41 :4/ O 0 -T '2 T $.WI W & Category 3 Antennas/Dishpq $652.67 I nnil Ile.p Certi!; irnt.p Prn-pc:.9 $439.9' 01116U02- .3.301·Ol!UU-Category 4 -1,A-29 99P h I,- p . ..4 ' . : 16.Exterior Telephones (Pay Phones) ...1. .- .- .101 First Pay Phone $545.77 5 Per Additional Pay Phone (Each) $159.90 $ Category 5 Outdoor Vending Machine (Each) $159.90 $ Category 6 $ Small Collections (Recycling Facilities)............................................. $ 910.39 $ OFF-PREMISE ADVERTISING (SIGN) PERMIT $4,808.29 $ NON-CONFORMING/ZONING VERIFICATION LETTER.................................. $511.65 5 RESIDENTIAL RELOCATION $3,620.45 5 SIGN PERMIT REVIEW (on-premicp) $439.92 $ SIGN PROGRAM REVIEW............................................................................... $ 495.78 $ TEMPORARY SIGN PERMIT $143.47 $ TEMPORARYTRAILER $550.24 4 UNDERGROUND UTILITYWAIVFR $446.22 5 Il:[INNI:lul:(•lgillohal[:!II•)18*fa;2! LANDSCAPE PLAN REVIEW Residential Projprtr $604.46 $ Non-Residential Projertq $1,352.39 $ Per Inspection after 2nd Inspection.......................................................... $ 451.49 5 OTHER $ 5 r=r-"=-7-7----77-7-7.,6.'17- ' .. ..CASE NUMBEIC .AMOUNT ..'Milallilivllliatilll[4•Il)1[6101; CERTIFICATE OF OCCUPANCY $399.79 $ TOTAL $ PROJECTADDRESS DATE f Lh l'. l/APPLICANT <f '/ /,7/5 ·: 2 E' l'PHONE C a -. 1:·i' f/'. (t·.(!/,4:3, BYMAILING ADDRESS '1, 1 WHITE-FINANCE/YELLOW-APLUCANT/PINK-PLANNING 2 rg INSTRUCTION FOR SIGN INSTALLATION 12 V LED WIRE SAME INSTALLATION 1+12 V LED WIRE POWER SOURCE POWER SOURCE 60 W #14 WIRE GOUND 60 W I, 88 44.0,JOB ADDRESS:1640 E. FIRST ST. 883!gn@sbcglobal.net TEL: (626) 442.8033 1906 DOREEN AVE.SANTA ANA, CA. FAX: (626) 350-5343 S. EL MONTE CA 91733 SCALE:APPROVED BY: STATE LIC: #702474 U.L. APPROVED DATE: Fasai Thai ..Afl, 'f.fj 11 t r:- -1, SIGN FACE TO STREET 28' STORE FRONT /LU iC Fasai Thai 11» i 12' mFasai I SIGN DIMENSION FOR BOTH SIGNS DETAIL: PROPOSED $' DEEP O{ANNEL LETTERS WALL SIGN, INTERNALIYILLU€NATED BY (Il V LE.O. LIGHT) SIGN FACE: IThick aer,lic face with 3/4' Broozetrim cap. MATERIAL: Clunnel letters ihill be fabricated by 0.04* thick aluminwn and feturns w; powder coated finish In Bronze color. AU ELECTRICAL COMPONENTS ARE TO BE U L RATED 30'TRM CAP -R ACRYLIC FACE.TRANSFOAMER SCX wl DiscceNECT-3 SwrrcH SIGN FACE TO PARKING LOT 1 1- 01 _12 VJRANSFCAMER C#$•c,„JOB ADDRES& 1640 E. FIRST ST. 8881gn@sb©global.nel SANTA ANA, CA.TEL: (626) 442-8033 1906 DOREEN AVE FAX: (626) 350-5343 i EL MONTE CA 9In3 SCALE:APPROVED BY: Nic DeAngeloSTATE LIC: #702474 U.L. APPROVED DATE: WHITECOIOA L.E.D. LIGHT - - 3/ir X y SCREW 1 -4-10 SCREW PER UETTER W RAN HOLD L 1- 1 m IL--3 C C -,I