Loading...
HomeMy WebLinkAbout10180552_1538 E. WARNER #A - Plan (2)Planning & Building Agency Building and Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org ELECTRICAL SIGN REQUIREMENTS Code references are to the 2010 California Electrical Code (CEC) A. All signs require Planning Department approval. B. All electrical signs require electric plancheck and permit. 1. Manufacturers instructions are required at the time of submittal. C-11: 3-21-2011 2. Submit detailed installation irlstructions including diagrams to the Building Department for plan review at the time of submittal. Plans must include appropriate items noted by this bulletin. 3. Cash or surety bond in the amount of $200.00 is required at time of issuance for each address. The cash or surety bond will be refunded after all required finals. C. A building permit is also required - except for open or highlight neon lighting. D. Installation Requirements: CONTACT FIELD INSPECTOR PRIOR TO SIGN INSTALLATION. (SEE SECTION G OF THIS BULLETIN) 1. Conductors and equipment shall comply with California Electric Code Article 600. 2. All metal parts of a sign shall be bonded in the manner specified in Article 250. Isolated metal parts are permitted to be bonded by using an external green insulated conductor. Equipment grounding & bonding conductors must be sized by 110.26 and protected from physical damage. Minimum size is 14 AWG. CEC 600.7 3. A listed disconnect switch in the power supply primary, shall be installed within sight of sign or have permanently installed means for locking in an "OFF" position. This is also true for a transformer enclosure. CEC 600.6 4. A listed receptacle or an approved termination device shall be used for each neon electrode. To relieve stress at terminations, tubing shall be supported with listed tube supports in an approved manner within six inches of electrode connection. CEC 600.41 & 600.42 5. Every electric sign of any type shall be listed by an approved testing laboratory and shall be installed in conformance with this listing. That includes "1 of x", "2 of x" labeling for each separate unit of a multi-unit sign. CEC 600.3 6. All "can" letters and transformers housings shall have section labels that are readily visible after installation. CEC 600.4 7. Transformers shall be located where accessible and be securely fastened in place. Page 1 of 2 When not inside the sign, they need a 3 foot high x 3 foot wide x 3 foot deep workspace. Transformers are permitted to be located in attics or canopies provided there is a passageway at least 3 feet high x 2 feet wide with a minimum 12 inch catwalk/walkway from the point of entry. Transformers must be securely fastened and independent of T- bar when above a suspended ceiling. No part of sign may be fed with flexible cord when located above T-bar ceilings. CEC 600.21(E&F) & 400.8 8. Adequate illumination shall be provided for all working spaces about electrical equipment. This applies to attics and canopies when entry is required to service or inspect the equipment. At least one switch is required at entrance. CEC 110.34 & 600.21 9. Doorway to an attic or canopy space shall be minimum 3 feet by 2 feet wide. CEC 600.21(E) E. Open neon outline or highlight lighting. 1. To be treated as a sign by this department. However, Section D-5 & D-6 of this bulletin will not apply. 2. Neon tubing shall be located where not normally exposed to physical damage. Open neon tubing below 9 feet shall be protected from physical damage by an approved shielding method. CEC 600.30 and 110.34(E) F. Light-Emitting Diode (LED) Signs 1. Will be treated as a sign by this department. All sign rules in sections A, B, C, D, F, and G will apply as appropriate. 2. LED illumination for signage must be a listed or recognized component. Many LED manufacturers specify particular brands and models of transformers some do not. Manufacturer information to clarify this issue is required on LED sign plans. 3. Unlisted LEDs may not be used in an electrical sign or as permanently installed illumination. 110.3 4. Please have packaging or catalog cut-sheets on hand for inspector to review when LED modules do not bear listing symbols. G. Inspections 1. Contact an Electrical Inspector one (1) workday (minimum) in advance of installation to arrange a site meeting on day of installation. 2. Call for inspection Monday through Friday, 8.00- 8:30 a. m. at (714) 647-5821. Approved prints and the job card must be on site for inspection. Page 2 of 2 137 SIGN COMPONENTS MANUAL (SAM)October 1, 201,3 9. Marking - The following markings or equivalent shall be provided. Markings A and B'below shall be marked anywhere where readily visible during servicing. A. "Do not attempt to repair or service a damaged sign face. Fot servicing of this sign, contact 7 (Blank to be replaced by Applicant's Company name, City and State.) B. "Replace only with , Type ." (Blanks to be replaced by Applicant's Companyname and material type ordesignation.) SS LIGHT CO LTD E346996 7 SINPUNG-DONG PALDAL-GU SUWON-SI, GYEONGGI-DO 442-040 REPUBLIC OF KOREA Class 2 LED Modules, KPL, PPL, DPL, OSPL, CPL, OCPL, SPL40, SPL4, SPL(Wl), KRD, KBD, KGD, KYD, SDL, SDL(Wl), SPL, SPL6. SCPL, ODL, OPL, OPL40, OPL4, OPL6, KSL(Wl), KDL(Wl), CPL(Wl), KP[-4(Wl), JRGB3, KR40, KE340, KG40. CSL(Wl), CSR, CSB, CSG, WSL(Wl). WSR, V\/SB, WSG, WPL(Wl), KOL-le(Wl), KOL-20, KOL-2(4W1), KOR-2(1 KOB-2C, KOG-2Ci GPL, GPL(Wl), GRGBD, GRGB3, GRGB40, JGRGB3, GCS RGB, WGS RGB, WGRGB3. SSL(Wl). SCPL(Wl), SPL40(Wl), JSRGB3, SCSL, SCS[-(Wl), SCS RGB, WSSL, WSSL(Wl), WSS RGB, WSPL(Wl), WSL, GDL, GPL40, GPL40(W), EPL, GCPL, OPCB 5030 6 (3P), OPCB 5030 8 OP), PCB 5030 6 ( 18, PCB 5030 8 (3P), PCB 5030 6 ( 1 P) KP 1, PCB 5030 8 (3P) KP1, PCB 5030 6 (IP) KWL PCB 5030 8 OP) KWL RGB 5030 8 (313, LRGB 5030 10 (3P), PCB 5030 (3P) R, PCB 5030 (3P) B, PCB 5030 (38 G. PCB 4530 - le (214, PCB 4530 Wl - 1C (2P), PCB 4530 R - le (2P), PCB 4530 8 - le (2P), PCB 4530 G - 1C (2P)m PCB 4545 - 2C (3P). PCB 4545 Wl - 2C OP), PCB 4545 R - 20 (3Ph PCB 4545 B - 2C (3P), PCB 4545 G - 2C (3P), GPCB 5030 8(3P), GPCB 5030 8 (3P) W, GRGB 5030 8 (3P), LGRGB 5030 10(3P). SPCB 5030 8 OP), SPCB 5030 8 (3P) W, A/L $18, A/L S30, ALL S60, A/L PP 18, A/L PP30, A/L PP60, A/l S 18 (Wl), A/L SJO (Wl), AIL S60 (Wl), A/L PP18 (Wl), A/L PP30 (Wl), A/L PP6.0 (Wl), A/L. S 18(R), A/L 330(R), A/L 360(R), A/L PP 18(R), A/L PP30(R), A/L PP60(R), AIL 318(B), A/L 330(B), A/L S60(8), A/L PP 1 8(B), A/L PP30(B), A/L PP60(B). A/L 318(G),A/L 330(G),A/L S60(G),A/L PP18(G),A/L PP30(G), A/L PP60(G), A/L RGB S18, A/L RGB S30, A/L RGB S60, A/L RGB P18, A/L RGB P30, A/L RGB PBO, A/L GS18, All- GS30, Al GSBO, A/L GPP18, A/L GPP30, A/L GPP60, All GS18 (Wl). A/L GS30 (Wl), A/L GS60 (Wl). A/L 'GPP18 (Wl), A/L GPP30 (Wl), A/L GPP60 (Wl), A/L GRGB Sl 8, A/L GRGB 830, A/L GRGB S60, At GRGB Pl 8, A/L GRGB P30, A/L GRGB P60, A/L SS18, A/L SS30, A/L SS60, A/L SPP 18, A/L SPP30. A/L SPP60, A/L SS 18 (Wl), A/l SS30 (Wl), A/L SS60 (Wl), A/L SPP18 (Wl), A/L SPP30 (Wl), AIL SPP60 (Wl), WAL PP18, WAL PP30, WAL PP60, WAL PP 18 (Wl), AL PP30 (Wl), WAL PP60 (Wl), WAL PP18(R), WAL PP30(R), WAL PP60(R). WAL PP18(B), WAL PP30(B), WAL PP60(B), WAI- PP 18(G), WAL PP30(G). WAL PP60(G), WAL RGB P18, WAL RGB P30, WAL RGB PBO, WAL GPP18, WAL GPP30, WAL GPP60, WAL GPP 18 (Wl). WAL GPP30 CAM), WAL GPP60 (Wl), WAL GRGB P18, WAL GRGB P30, WAL GRGB P60, WAL SPP18, WAL SPP30, WAL SPP60, WAL SPP18 (VV1). WAL SPP30 (Wl), WAL SPP60 (Wl) 1. These products are only suitable for connection to a Class 2 power source rated 12 Volt DC or less. 2. These products are intended for use only when connected to a power source that complies with Class 2 voltage=and energy limited circuit and is rated greater than 12 V DC. 3. When these units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the' secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at 12 Volts DC or less. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. These products may be secured ih place in the end product by any means available. Marking: Company name or trademark SS LIGHT and product designation. STARTEC CO LTD E350879 310-8 YUHYUN-RI YANGCHON-MYEON GIMPO-SI, GYEONGGI-DO 415-821 REPUBLIC OF KOREA Class 2 LED Module, R03-25KN. 1. These products are only suitable for connection to a Class 2 power source rated 12 Volt DC or less. 2. When these units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 3. These products are suitable for use in dry, damp and wet locations with supply sources rated at 12 Volts DC or less. 4. These products are not required to be enclosed or protected from the weather in the end product. 5. These products may be secured in place in the end product by any means available. SUNSIGNLED OPTO-ELECTRONICS CO LTD E359615 2F BLDG B LAOBING INDUSTRY PARK ZHOUSHI RD SHIYAN TOWN BAOAN DISTRICT 518108 SHENZHEN, CHINA Class 2 powered LED modules, Models IYX225U, IYX324U, IYX220U, IYX3404, IY)(326U, IYX332U, IY)<341 U, MYX112U, MYX120U, MYX 102U, MYX117U, where X and Y niay be replaced by any letter denoting LED color and type respectively. 1. This product is only suitable for connection to a Class 2 power source, rated 12 Volt DC or less. 2. This product has not been evaluated for use when connected to a power source that does not,comply with Class 2 voltage and energy limits and which is rated greater than electrical ratings. 3. This Class 2 LED module is rated as noted in the electrical ratings tables. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. This product is suitable for use in dry, damp and wet locations with supply sources rated at electrical ratings or less. 5. This product is not required to be enclosed or protected from the weather in the end product. 6. This product may be secured in place in the end products by any means available. <h SS Light,New Par@digm 01 LI R ill ny Single Color{White, Red, Green, Blue]-LED Module with dual wires Grounding<Green) A.C Input / 0 0/ Prk /...,lii®. 0 : SMPS A MAX 50PCS D.C ir put + Red 1.Max module qty for direct connection : 100pcs 2.All modules have to be installed within 10meters of SMPS 3.Recommended wire thickness : 1 SQ per 100pcs of 3LED modules 4.Recommended usage of SMPS capacity : 70% of full capacity LED Color-LED Module with 4 wires L--1 1 \ 9 0 0 lili'ilililfill- 1 1 11 111.1- 1,1,111!111..'.1/1 Hill 1 1 lilli .Ill,1 I 911. -11111111" 111111/1'1\\03 1 ,\02 1 •-•12 WIG "WRGIl%3 ) 1 j E ..........\ 11-4/ \ A.C input 1.Max module qty for direct connection : 100pcs 2.Each wire has to be connected to corresponding controller slot 3.All modules have to be installed within 10meters of SMPS 4.Recommended wire thickness : TSQ per 100pcs of 3LED modules 5.Recommended usage of SMPS capacity : 70% of full capacity www.sslight.net L r?,9-4 SSLIGHT Series - White • Life Span : Over 50,000hours *3years warranty * Brightness continuance : Designed to minimize damage of chip from static electricity. Provides constant voltage for same brightness at all times. e Waterproof : Epoxy adherence on LED module to prevent moisture. IP 68 certified.•1 Rank Chip : Use only one rank LED chip for same color of each module. •Other color temperatures for white LED are available by customized order. Common specifications filtGnnecILBIF.- LE[* '19«t· Voltage 1 ':F: I Angle > 44- Waterproof wire to wire | achip DC12V | 120° Lens type:60* 1 | IF 68 Certified KPL One LED module 1 Model , Cdon#r curre: 4.PZL,i 02't' Fl'obrit i ColorTemp KSL | KSL KSL[W]1 White Warrn White 20mA 0.24W Over 6,000mcd 0 8,000-10.000K 20mA 0.24W 5,000mcd O 3.000K • Size : 9 x 12 x hmrn W KSLIWI Two LED module Model Cotors Current f Power , . Brightness , pdarity CotorTemp-Cbnsumotion Consumotion (PerlLEDI KDL KDL KDLIWI White Warm White 40mA 0.48\N Over 6,000mcd x 8,000-10,00]K 40mA 0.48W 5.000mcd x 3,000K ·Size 41*12*7.5mm KOLIWI Three LED module Model Colors Current Power BrightnessConsumption Consumption (Per 1LED! Polarity Color Temp 60mA 0.72W Over 6,000mcd x 8,000-10,000K Warm- 1<PLIW] White 60rnA 0.72W 5.000mcd X 3,000K P-If WPL White 60mA 0.72W Over6,000mcd x 8,000-10,000K 60mA 0.72W 5,000mcd x 3,000K 4 -1 ·Size .68 x 16 x 7.5mm KPL · KPL[WI • Size : 68 x 16x 15mm WPL · WPL[WlWPCIW SS Light Li g h t,New Paradigm ..o It i.jk'h ling Single Color[White, Red, Green, Blue)-LED Module with dual wires Grounding<Green) 42 Input /0 \03\ 10/ MAX 50PCS 11 1 Waterp SIVIPS 3.C OpJ + Red 1.Max module qty fordirect connection : 100pcs 2.All modules have to be installed within 10meters of SMPS 3.Recommended Mre thickness : 1 SQ per 100pcs of 3LED modules 4.Recommended usage of SlvIPS capacity : 70% of full capacity LED Color-LED Module with 4 wires «1 «22 •-•12 11 I'GIWRGI 1111 111]11, Illl !!I 1 .11 il·/11, lilli· ·.I.t [ .,11/ · ·1.11 Ilttir/182!2888*..111111111111 . lili 11Illlllll- *NL 2,I"[MI AC nput 1.Max module qty for direct connection : 100pcs 2.Each wire has to be connected to corresponding controller slot 3.All nlodules have to be installed within 10meters of SMPS 4.Recommended wire thickn ess : T S(1 per TOCpcs of 3LED modules 5.Recommended usage of SMPS capacity : 70% of full capacity www.sslight.net Sign Layout Scale (0.125" = 0'-4.5")(FhmeBrotter wl ;ID Inc Scale (nts) 1538 Flame Broller e ASTER I.D. 1'118+4PS 2.P. 9 prD PLANNER *. ·>erp TRANSFERRED BY 1/iNNING INSPECTION REQU.r./,ne·JF 8485 Artesia Blvd. Unit A. Buena Park, CA 90621 m 714.690.0264(F) 714.690.0274 Description: Internally Illuminated Aluminum ChanneFLetters Face to be 3/16" Red Mex #2793 / Trim Caps & Returns to be Black (Design Layout to Flame Broiler Corporate C.1.) The" to be 1 / 2" Sintra Letters pin mount Installation Illumination w/ 12V Red & While LED - Class 2 Wiring Total of 30 Sq. Ft. / Total length to be 15'-0" / 10% of the leased trontage Materials to be U.L. Listed UL-2161 Compliant / UL-Recognized All penetrations to be made water tight Address: Flame Broiler (Brookhollow - Santa Ana) 1538 Broolmollo Dr. Santa Ana, CA VI .1, 4.I U!,UT-1 P INAL Date:07.23.13 22'-6" - NAME (714) - Rw. 1228!en27'-0"07,2113 Preliminay Layou! RETAIN PLANE FOR FUTURE REViSGONS.-r -ro ITEMS CHECKED AND CONDITIONS. 3:-3-2.l.lu 1 1 142'-0('Leased Frontage) FULL ELEVATION VIEW Project: Brookhollow INTEr.103 -rl ONLYNO E>7110€ ALTERA·TIONS/MODIFICATIONS , ALL MATERiALS TO MATCH EXiSTING 1 SORZE·1!NG REQUIRED 1 SUBMIT LANDSCAPE PLANS ,%---'.-*.-.--I- Scale:See Attached Sheet:1 of 2 JWO: 1307231 --'" %29 1.-F D 9\4 jitu .4,·A. MA f :74 4 Sign Layout Scale (0.125" = 0'-4.5") ISFlate Broller W 15'-0" Installation & Side View 8485 Artesia Blvd. Unit A. Buena Park, CA 90621 m 714.690.0264 /n(F) 714.690.0274 l&; Scale (NTS)Top View 12V / 2 Amp T/F 1 4 1 1 1 lilli Il HI ' 1 L_L_l L_!_IL_-1 I I Il 1 FRONT FACIA Side View (Letters) FR*IT FAC LA 12V / 2 Amp T/F L I·' Al 3/4· PLASCO TRIM CAPS 11 L 0 Aerial Plot Plan Description: Internally Illuminated Aluminum ChannelLetters Face to be 3/16' Red Plex #2793 / Trim Caps & Returns to be Black (Design Layout to Flame Broiler Corporate C.1.) "The' to be 1 / 2" Sintra Letters pin mount Installation Illumination w/ 12V Red & White LED - Class 2 Wiring Total of 30 Sq. Fl/Total length to be 15'-0" / 10% of the leased frontage Materials to be U.L. Listed UL-2161 Compliant / UL-Recognized All penetrations to be made wafer tight MIN. OF 5 1/4" X 3 1/2' ANCHORS OR TOGGLE TO MOUNT LETTER JO FRONT FACADE LED SERIES WIRED ATTACHED W/ 3M VHB TAPE.4. GE SILICONE ----1'r- % t 4 f ' if: :64*:id:: Address: Flame Broiler (Brookhollow - Santa Ana) 1538 Brookhollow Dr. Santa Ana, CA J-BOX: 0.063 ALUMINUMBACK & RETURN- 1 5 Date:07.23.13 CONDUTT Rev, Description 07.23.13 Premmirw,Layoul 3/16'· PLEX FACE POWER SOURCE1----120V INPUT / 12V OUTPUT TRANSFORMER FOR Project: BrookhollowUR RECOGNIZED CLASS 2 EXTERIOR USE W/ 1/4" DRAIN HOLE ELECTROBIT DISCONNECT Scale: See AttachedSWITCHPASS-THRU PENETRATIONS Sheet: 2 of 2 TO BE MADE WATER nGHT AVO: 1307231Proposed future Space -4 ID,1 5' DEEP gn Layout :ale (0.125" = 0'-43 ISID, Inca w ter, Inc. 10'-0"/ 8485 Artesia Blvd. Unit A. Buena Park, CA 90621 m 714.690.0264 evation ( West)Installation (F) 714.690.0274 :ale (nts)Description: 72" Aluminum plate letters Brushed Aluminum Finish FRONT FACIA Pin Mount Installation 1/2"CEEP MIN. OF 3 1/4" X 1" THREADED RODS TO MOUNT LETTER TO FRONT FACADE The Flame Broiler, Inc.5 29 6061 ALUMINUM PLATE 97 BRUSHED FINISH DEEP - Address: Flame Broiler (Brookhollow - Santa Ana) 1538 Brookhollow Dr. Santa Ana, CA Date: 11.08.13 Rev. Description19'.0"1 07.23.13 P,el,minan, Layout 24'-0"11.06.13 Revi/d tayout i 11.00.13 Revised Layout 68'-6" (Leased Frontage) Project: Brookhollow FULL ELEVATION VIEW Scale; See Attached Sheet: 2 of 2 JWO: 1307231 h 18'-6" L khollow 60-usiliESS--PA:*KI Santa Ana, CA • Owner's Association: Brookhollow Office Park Assoc. Site Plan WARNER AVENUE . 15364 11504 L 1 4 1532 15341 [-1500 .A 1544 M 1540 - Lrd* .2&:rii;i:TrifIFIr./11/6. '1538 rJ• 1504 I ,*#- 1 1548 1506 1 , 1554 PROPOSED SIGN LOCATION AND PROPERTY Ul Z LU :I Z 1510 e lol 9 0 5-y 1 -City of Santa Ana. CBC & CEC 2010 , Minimum (4) screws per letter, maximum 24" on center, 2" penetration, #10 sheet metal screws, & 0 44" drain_(loles_per.letter_ 1 5-3 2 E.u/(/A 2 N E K * IS A local disconnect for the monument sign(s)reCPjired or the dedicated circuit break,er(s) mus,dividually lockable in the off position. 600-6ass to any power supply in attic or aboveceng shall be immediately from a ladder orwith a2x3 foot access door & passage with a12-inch walkway. CEC 600-21 (d)(d)City of Santa Ana Planning & Building Agency »3004 €:Lk--3 as nok€-- PEFMT TYPE:(eze·- 1 101 ELECTRICAL 1 PLAN APPROVAL ' This set of plans and specificaions must be kept on the job at al! times and It le unlawful to make any changes or alterations on same without written per- mission from the Department of Building Safety City of Santa Ana. PEFUNT.,)01€0527 - Doc. Gaot; W 00]53&5202 CONSTR. TYPE CODE EDinO24 20\-3 FLOOD ZONE ht .7.0 The approval of this plan and spedficatfons SHALL f -- NOT bs *Did to permit nor be an appmvag of the ;10;any provisions of ANY City Ordinance R.OOD ;a)ME CERTE REQD YES Approvt#i by A t, " 1+RADIANr BARRIER O ROOF YES<5 1dirY OF SANTA ANA DEPARTMENT OF BUILDING SAFETY RESIDernAL DEV. FEE YES NO ;' SCHOOL DESTRET YES NO , 91- , . FFazatmem:f