HomeMy WebLinkAbout10180573_2150 N. TUSTIN - Plan (2)·2itt"'! Planning & Building Agency Building and Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org ELECTRICAL SIGN REQUIREMENTS Code references are to the 2010 California Electrical Code (CEC) All signs require Planning Department approval. All electrical signs require electric plancheck and permit. 1. Manufacturer's instructions are required at the time of submittal C-11: 3-21-2011 2. Submit detailed installation instructions including diagrams to the Building Department for plan review at the time of submittal. Plans must include appropriate items noted by this bulletin. 3. Cash or surety bond in the amount of $200.00 is required at time of issuance for each address. The cash or surety bond will be refunded after all required finals. A building permit is also required - except for open or highlight neon lighting. Installation Requirements: CONTACT FIELD INSPECTOR PRIOR TO SIGN INSTALLATION. (SEE SECTION G OF THIS BULLETIN) 1. Conductors and equipment shall comply with California Electric Code Article 600. 2. All metal parts of a sign shall be bonded in the manner specified in Article 250. Isolated metal parts are permitted to be bonded by using an external green insulated conductor. Equipment grounding & bonding conductors must be sized by 110.26 and protected from physical damage. Minimum Size is 14 AWG. CEC 600.7 3. A listed disconnect switch in the power supply primary, shall be installed within sight of sign or have permanently installed means for locking in an "OFF" position. This is also true for a transformer enclosure. CEC 600.6 4. A listed receptacle or an approved termination device shall be used for each neon electrode. To relieve stress at terminations, tubing shall be supported with listed tube supports in an approved manner within six inches of electrode connection. CEC 600.41 & 600.42 5. Every electric sign of any type shall be listed by an approved testing laboratory and shall be installed in conformance with this listing. That includes 1,1 of x", "2 of x" labeling for each separate unit of a multi-unit sign. CEC 600.3 6. All "can" letters and transformers housings shall have section labels that are readily visible after installation. CEC 600.4 7. Transformers shall be located where accessible and be securely fastened in place. Page 1 of 2 r O 0 CD P When not !inside the sign, they need a 3 foot high x 3 footwide x 3 foot deep workspace. Transformers are permitted to be located in attics or canopies provided there is a passageway at least 3 feet high x 2 feet wide with a minimum- 12 inch catwalk/walkway from the point of entry. Transformers must be securely fastened and independent of T- bar when above a suspended ceiling. No part of sign may be fed with flexible cord when located above T-bar ceilings. CEC 600.21(E&F) & 400.8 8. Adequate illumination shall be provided for all working spaces about electrical equipment. This applies to attics and canopies when entry is required to service or inspect the equipment. At least one switch is required at entrance. CEC 110.34 & 600.21 9. Doorway to an attic or canopy space shall be minimum 3 feet by 2 feet wide. CEC 600.21(E) E. Open neon outline or highlight lighting. 1. To be treated as a sign by this department. However, Section D-5 & D-6 of this bulletin will not apply. 2. Neon tubing shall be located where not normally exposed to physical damage. Open neon tubing below 9 feet shall be proteded from physical damage by an approved shielding method. CEC 600.30 and 110.34(E) F. Light-Emitting Diode (LED) Signs 1. Will be treated as a sign by this department. All sign rules in sections A, B, C, D, F, and G will apply as appropriate. 2. LED illumination for signage must be a listed or recognized component. Many LED manufacturers specify particular brands and models of transformers some do not. Manufacturer information to clarify this issue is required on LED sign plans. 3. Unlisted LEDs may not be used in an electrical sign or as permanently installed illumination. 110.3 4. Please have packaging or catalog cut-sheets on hand for inspector to review when LED modules do not bear listing symbols. G. Inspections 1. Contact an Electrical Inspector one (1) workday (minimum) in advance of installation to - arrange a site meeting on day of installation. 2. Call for inspection Monday through Friday, 8:00- 8:30 a.m. at (714) 647-5821. Approved prints and the job card must be on site for inspection. Page 2 of 2 103 SIGN COMPONENTSi MANUAL (SAM)October 1, 2013 6 These products may be secured in place in the end product by any means available. 7. When these products are used in applications other.than'signs or outline lighting, the need to conduct aitemperature test shall be considered. OPTEK TECHNOLOGY INC E339817 SUITE 130 M S 411 1645 WALLACE DR CARROLLTON, TX 75006 Class 2 LED Strips, Cat. Nos. OVM 12F3x7 Series OVM18F4x7 Series, OPA775, OPA776 and OVQ 12S30x7 Series. 1. These products are only suitable for connection ito a Class 2 power source, rated 12-24 Volts DC. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limits. 3. These Class 2 LED modules are each rated as noted=in the. model list tables. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations'with supply sources rated at rated 12- 21.2 Volts DC. Model OPA776 is suitable for use in dry and damp locations only. 5. These produlcts @re not required to be enclosed or protected from the weather in the end product. ORDER-MATIC ELECTRONICS CORP 320 S BRYANT PL E328326 DEL CITY, OK 73115 Class 2 LED Panel, Cat. No. Model MDMON. 1. These products are required to be enclosed in the end use sign. 2. These products are intended only for factory installation in new signs. 3. Grounding of frame to supply ground is required. Suitability of bonding for grounding connection is to be determined in final application. 4. Suitability of LCD panel mounting shall be determined in final application. 5. In the end product, the LCD panel spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing'to top of enclosure. 6. These products are 0nly suitable, for connection to a circuit from a Class 2 power source. OSRAM SYLVANIA INC 54 CHERRY HILL DR DANVERS, MA 01923 E220096 LED Array Drivers, Models OT3W/3500/120-240V, OT240/120-240/24/CH3, OT96/120-277/24, OT96/120-277/241 OT240/120- 240/24/CH, OT240/120-240/12/CH. OT25W/700€/UNV, OT20VW 1 OV/120-240V, OT17W/700(/UNV, OT1 7VW24V/UNV, OT40W/14000/UNV, OT40/120-277/1050E, OT40/120-277/850E, OT25W/1040C/UNV, OT40W/11 10C/UNV. 1. These power supplies have multiple outputs. Power supply Model OT240/120-240/12/CH has a maximum of four Class 2 outputs. Power supply Models 0T3/120-240/350 and OT240/120-240/24/CH have maximum three Class 2 outputs. Each output of these power supplies have been evaluated to Class 2 output requirements for dc circuits. 2. These products with Class 2 outputs are suitable for use in dry, damp and wet locations. 3. Power supply spacing to other heat producing components shall be minimum 4 inches when minimum spacing to sidewalls and top of enclosure is kept at minimum 2 inches. 4. When not marked for dry and damp locations only, all units shall be provided with liqUid tight fittings on the primary and secondary circuits. 5. Cord connected (not cord and plug) models are suitable only for use in cord connected signs: A) The suitability of the cord length, type, and temperature rating shall be determined in the end use. B) Strain relief testing has been conducted at 20 lbs. The need for additional strain relief shall be determined in the end use. C) Leakage current testing has not been conducted on the cord connected models and shall be conducted in the end use. LED Array Drivers, Models OT25/120/10, OT50/120/10, OT75/120/24. 1. These power supplies have a maximum of one Class 2 output. The ootput of these power supplies has been evaluated to Class 2 output requirements for dc circuits. 2. These products with Class 2 outputs are suitable for use in dry and damp locations only. 3. In the end product, power supply spacing to other heat producing components shall be minimum 4 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 4. When used in a cord connected product, the need for conducting a leakage current test shall be considered in the end product. 5. These lead connected products are suitable for use in commercial application only when marked with 277 V input voltage. OSRAM SYLVANIA INC E258264 54 CHERRY HILL DR DANVERS, MA 01923 Class 2 LED Illumination Module, Cat. Nos. OS-LM01 A-X, OS-LM03A-X, where X may be replaced with any letters of the alphabet A to Z, or any number from 0 to 9, or any combination of letter and numbers representing different LED colors ; LINEAR/LM01 AAN3F/XXX and L#LRE/1 OV/XXX/LNRLT, where X can be any number from 0-9 indicating color temperature. 1. These products are only suitable for connection to a UL Listed or R/C (UYMR2), Component - Sign Accessory. 2. These products have; not been evaluated for use when connected to a power source that does not comply with Class 2 requirements. October 1, 2013 SIGN COMPONENTS MANUAL (SAM)110 Model ' Input Voltage ' Max. Max. Current ,Max. # Max. Total Length (Vdc)Wattr 9 1-:s 7VI05A-W3-XXX 24 5. Suitable for Dry or Damp locations. 6. Class 2 Input Only. LED Strip Class 2, LINEARIight Flex Series - LF05EP 1. These products have been evaluated for use with a suitable Class 2,24 VDC; power source only. 2. These products have been evaluated for use in dry and damp locations. 3. Thermal spacings shall be provided in accordance with Standard UL 48 or the following tests should be considered in the end use application: Normal Temperature, and Dielectric Voltage Withstand Test. 4. The LED strips may be mounted by integral tape or other mechanical means. 5. Installation Instructions indicate that the LED Strips may be cut to size in areas marked by straight edge symbol. Class 2 Power Supply, Models OTl OW/350C/120-240V, OTl OW/12V/120-240V and OT25W/12V/UNV. 1. The electrical ratings are as follows: | Input, 60 Hz |Output, ac I Model IV A V A VA or Pmax | OT25W/12V/UNV ||85-277 || 0.11-0.3 || 12 || 2.0 |1 25 Pmax I OT10W/12V/120-240V ||120-240|| 0175-0.120 | 12 ||0.833|| 10 VA | OT1 OW/350C/120-240V || 120-240 || 0 175-0.120 ||2.3-28|| 0.350 || 10 VA | 2. These power supplies have beenevaluated to Class 2 output requirements for dc circuits with a maximum of one Class 2 output 3. A suitable Fire and Electrical Enclosure shall be provided in the end product. 4. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls: and minimum 2 inches spacing to top of enclosure. 5. These power supplies are only suitable for use in dry and damp locations. Class 2 Power Supply, Model OT60W/12V/UNV. 1. Ihese power supplies have been evaluated to Class 2 output requirements for dc circuits with a ma'ximum of one Class 2 output. 2. Th6 electrical ratings are as follows: Input, 60 Hz Output, DC Model N v A 1 V VA |OT6OW/12V/UNV | 100 - 277 | 0.8 - 0.3 || 12 || 60 3. These power supplies are only suitable for use In dry and damp locations. 4. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. Class 2 LED Module, designated as BA03MA-XXX-YYY and BB03-LA-XXXYYY series, where XXX may be blank or WAF, and YYY may be a combination of any alphanumeric characters. 1. These products are only suitable for connection to a Class 2 power source rated 12 Volt DC or less. 2. These products are intended for use only when connected to a power source that complies with Class 2 voltage and energy limited circuits. 3. When these units are connected to a Class 2 supply circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dfy, damp and wet locations. 5. These products are not required to be enclosed or protected from the weather in the end. product. 6. These products may be secured in place in the end product by any means avajlable. Class 2 LED Module, designated as BX 12BA-VV4F Series. 1. These products afe only suitable for connection to a Class 2,24Vdc power source only. 2. These products are intended for use only when connected to a power source that complies with Class 2 voltage and energy limited circuits. 3. When these units are connected to a Class 2 supply circuit, they are hot to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. These products may besecured in place in the end product by any means available. Class 2 LED Module, designated as BX06BA-V\MF Series. 1. These products are only suitable for connection to a Class 2,24Vdc; power source only. 2. These products are intended for use only when connected to a power source that complies ;with Class 2 voltage and energy limited circuits. 3. When these units are connected to a Class 2 supply circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. These products may be secured in place in the end product by any nieans available. Class 2 LED Strip, LINEARIight Colormix Flex, LF05CA2-RGB3. 1. These products were evaluated for connection to a UL Listed or Recognized Component Sign Accessory - UYMR2, Class 2 source. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limiting requirements. 41 O <I»·77+4- c. 171*J Fon,««_/3 9-e 0 00 0 6 £-c \T?NG- //10[72d-Tzar' 3 --3<14(-> ( Allowable SQ.FL 38.5 SQFT Total SQ.FL 37.5 5Q FT 2-24"H 18' 8-7/E 1]1[2 21©(DEK PROPOSED SIGN TYPE: Face-Lit illuminated channel letters Additional Sign 1 EAR; 5"deepstd .040 coll-white interior,.063 pre-finished white aluminum backs MOUNTING: Flush mounted to building exteriorwith reg. hardware ILLUMINATION: LEDs -Sylvania 71071 White 6500K. Toggle switch, UL Listed, dedicated 20 amp breaker. LETTER FACES: 3/16"thic#2447 Arkema Plexiglas Acrylic with l"std trimcap. SOUTH WATER SIGNS Sales Rep: tA Designer: pnif ..i""11*P."11 li.b'-¥-k*1 f-*-)· / m.,-P: //2.7%/23©l-'3'• 31_fiEA--46 LOGO FACES: 3/16"thk.#2447 Arkema Plexiglas Acrylic with 3M 3630-106 Brilliant Green. PRE-PAINT: Letter returns - pre-painted mil (PMS Gray 4300 Logo returns - pre-painted mil (PMS 3760 Trim caps - pre-painted black(letters) green(logo) BILL OF MATERIALS QTY. 1 NAED DESCRIPTION 3 |71071 L 144/1 2V/865 (CHAIN X1 6500k)LE.D.ILLUMINATION 2 51603/51632 0760W/12V/UNV (120-277) -----,-.LA1 .· U i ,--* 4=£ R :3 =ral- 4 aAPP¢QMRP I 96.48 Wat1s 1 < 1 .PLANNING DIVia;Qos to Match 44 -»0 >1 #t ASTER I.D.322-14.ic? 4fl:Letter Returns PMS 430[ 6}i- i .p, CLe.Zone__-C-4 U @2 1. mIUCAP'NHRET"'&//6 -C -'%,%.2,4fNUE,APla//ASACR,1/Trim & Returns - PM5 376(3 WIEM"*LED, 4.eIAN 1' BACKS m W i N 2 ¤ . ......11 LANNER 10-< -Faces-#2447 Arkema Plexiglas 10|E#51680SP.WO=JM M -J- i'& FASTENREfa 8 Ewith- 3M3630-106 Btimant Green USTED AA ./ Leave As Is: 2 Signage Recomm-61*Nifier¢ED BY DATE LED Retrofit: E]Channel Letters: MLANN 82 R*P@CTION REK:13#2!ional Notes Face Change: U Y Raceway: 3*)UGH Reface ExistliEN]AL A. El N IN etrofit Existing: [1 New Sign: 3Existing Face Color: El White New Face Color:NA#tU Day/Night Size: 0 2' X 8' 0 3' X 5(714) O Other O Other 03*5 [3318' ' 04'X8' O41X 10' New Face Color: E White Existingsign Size: RETAIN PLANE ¢}12><till .Ay,-:.r- .or,-'g·,9 13 Day/Night 31£.-1&4·t:AE}ECT TO i-n.!V· F .3,1, E '·6 ' *'' ' ' ' - %-U Other New Sign Size: 241-=188&,INTER!OP TI P 0 tOO D--" . p · Location: 2150 North Trustin Avenue Santa Ana, CA 92705 MEMBER 11*30 Ill UmULM,iO·i,my LISTED D ALL L..1, - ' ·· O SCREENK« O SUBMFT LAN.- .' - -ONDITIONS: Allowable SQ.FL 38.5 SQ FT Building SQ.FT. 385SQ FT Current SQ.FT. 37.5 SQ FT 1 Opportunityto increase size: I Y [3 N SOUTH WATER =e- SIGNS EXISTING SIGN - . B Sales Rep: tm Designer: 4 29700 pmf, 1 41.1 0 19*4. .4 E C. 2 E Existing Signage: Sign Type:Existing Sign Dimensions: Illumination:Face Color:Sign Condition: j 3 Box Sign: [3 H 31.5"-15" W 167'None: [3 White: I Good: 1 Channel Letters: 11 LED: I Day/Night: [3 Fair: m Location: Other: E]Existing Wall Dimensions:Neon: C]Other: El Poor: 0 2150 North Trustin Avenue H 44"W 33'-0"Fluorescent: [3 Santa Ana. CA 92705 Additional Notes: Customer wants main signage to remain as is.MEMBER 04*8 1 ile!'155,1§[CEr"LISTED . Aerial View SOUTH WATER 141- 1-941 4 .1 1 If€:t 'r a.2!Elum i.11 '11 1 1+4 ::1· 4 1 I r·-r 17 . SIGNS Sales Rep: tm Designer: pmf E E 2 -2 0 C »5 » -3 % Location: 2150 North Tristin Avenue Santa Ana, CA 92705 MEMBER 04*g IRMIP,lip,ER-£1 LISTED -3-\F_jul . - C.er-el 2150 N --ns-4-< n -7-90,6- · eritsignls)\S .- „ onum - 63:it_of-Sania-Anad:EA-CEC-2012 8"1 dpconnect Tor the m Minimum (4) screws per letter,1 l maximum 24" on center, 2" 'p ., 00 (* 0bcple ' penetration, #10 sheet metal screws, & 1.laN r 2)_Mt" drain holes per letter aLe :Esoo,+Oin Grty po\Ner suppty ;11 0 ladder Oressage,tth a _- _- __- _- _- _CP·.24 j ..on / <VI *pa '4 h .-.- - --3 12=4 4>ld)«A -----/1, . re·,··· -8.00 :.>0005 6001 7 rt...,1 ·,0 ,·25,010 020 *140=41*me-9 CAL 80-1-F PERMEr TYPE 220< EE3 PLBG | MECH b#4)NG ELECTRICAL j; PLAN APPROVAL ZfjPERMIT#_ 0 ?C) 59 OCC. GROUP .f20 1 0 62 9-4 6- . ' TWs set of plans and spec!ncations must be kept on CONSTR. TYPE. ' the Job at agS times and it as unlawful to make any 1changes or aNerations on same without wri#an per- CODE EDITION..2-OlD mission from the Department of Building Safety <Cly of Sent*Arm.FLOOD ZONE- .. The appn,val of '8'ls Man and specticatlons SHALL ir NOT*J.19#d to 00;imit nor bo an approval of *r- . ,FLOOD ZONE CERTE REQ'D YES 0I violagentr any provisions of ANY Clay Ordlid.. 1 :1 or State 1* 1 1, ' BACBOFUR YES Nth' -*FAR"4 --- - --- - ..RADIANT BARMIER @ ROOF YES .N€ RESADENTIAL DEV. FEE YES/ NOCITY OF SANTAANADEPARTMENTOF BUILDING SAFETY ( SCHOOL DISTRICT YE+Qp 60,0 1**16%'22..4ib*42·.22-:1426=4.<:,s,k@24.z»G¢ND.1,:.·>»-6f