HomeMy WebLinkAbout10180962_2781 W. MACARTHUR F-2 - Plan (2)Planning & Building Agency Building and Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.ora ELECTRICAL SIGN REQUIREMENTS '1 'Jlf r. . . '.1 Code references are to the 2010 California Electrical Code (CEC) All signs require Planning Department approval. All electrical signs require electric plancheck and permit. 1. Manufacturer's instructions are required at the time of submittal C-11: 3-21-2011 2. Submit detailed installation instructions including diagrams to the Building Department for plan review at the time of submittal. Plans must include appropriate items noted by this bulletin. 3. Cash or surety bond in the amount of $200.00 is required at time of issuance for each address. The cash or surety bond will be refunded after all required finals. A building permit is also required - except for open or highlight neon lighting. Installation Requirements: CONTACT FIELD INSPECTOR PRIOR TO SIGN INSTALLATION. (SEE SECTION G OF THIS BULLETIN) 1. Conductors and equipment shall comply with California Electric Code Article 600. 2. All metal parts of a sign shall be bonded in the manner specified in Article 250. Isolated metal parts are permitted to be bonded by using an external green insulated conductor. Equipment grounding & bonding conductors must be sized by 110.26 and protected from physical damage. Minimum size is 14 AWG. CEC 600.7 3. A listed disconnect switch in the power supply primary, shall be installed within sight of sign or have permanently installed means for locking in an "OFF" position. This is also true for a transformer enclosure. CEC 600.6 4. A listed receptacle or an approved termination device shall be used for each neon electrode. To relieve stress at terminations, tubing shall be supported with listed tube supports in an approved manner within six inches of electrode connection. CEC 600.41 & 600.42 5. Every electric sign of any type shall be listed by an approved testing laboratory and shall be installed in conformance with this listing. That includes "1 of x", "2 of x" labeling for each separate unit of a multi-unit sign. CEC 600.3 6. All "can" letters and transformers housings shall have section labels that are readily visible after installation. CEC 600.4 7. Transformers shall be located where accessible and be securely fastened in place. Page 1 of 2 When not inside the sign, they need a 3 foot high x 3 foot wide x 3 foot deep workspace. Transformers are permitted to be located in attics or canopies provided there is a passageway at least 3 feet high x 2 feet wide with a minimum 12 inch catwalk/walkway from the point of entry. Transformers must be securely fastened and independent of T- bar when above a suspended ceiling. No part of siqn mav be fed with flexible cord when located above T-bar ceilings. CEC 600.21(E&F) & 400.8 8. Adequate illumination shall be provided for all working spaces about electrical equipment. This applies to attics and canopies when entry is required to service or inspect the equipment. At least one switch is required at entrance. CEC 110.34 & 600.21 9. Doorway to an attic or canopy space shall be minimum 3 feet by 2 feet wide. CEC 600.21(E) E. Open neon outline or highlight lighting. 1. To be treated as a sign by this department. However, Section D-5 & D-6 of this bulletin will not apply. 2. Neon tubing shall be located where not normally exposed to physical damage. Open neon tubing below,9 feet shall be protected from physical damage by an approved shielding method. CEC 600.30 and 1 10.34(E) F. Light-Emitting Diode (LED) Signs 1. Will be treated as a sign by this department. All sign rules in sections A, B, C, D, F, and G will apply as appropriate. 2. LEDillumination for signage must be a listed or recognized component. Many LED manufacturers specify particular brands and models of transformers some do not. Manufacturer information to clarify this issue is required on LED sign plans. 3. Unlisted LEDs may not be used in an electrical sign or as permanently installed illumination. 110.3 4. Please have packaging or catalog cut-sheets on hand for inspector to review when LED modules do not bear listing symbols. G. Inspections 1. Contact an Electrical Inspector one (1) workday (minimum) in advance of installation to arrange a site meeting on dav of installation. 2. Call for inspection Monday through Friday, 8:00- 8:30 a.m. at (714) 647-5821. Approved prints and the job card must be on site for inspection. Page 2 of 2 October 1, 2013 SIGN COMPONENTS MANUAL (SAM) 76 7. A temperature test is not required if the LED drivers are spaced at least 1 in. apart end to end or 4 in. apart in other directions. Spacng to plastic shall be 1 inch minimum and to metal may be zero in. The need for a temperature test shall be considered if the LED driver is mounted closer than the referenced spacings. For reference these LED drivers have been tested in a 50 C ambient and maximum case temperature is 73C. JKL COMPONENTS CORP E339601 13343 PAXTON ST PACOIMA, CA 91331 Class 2 LED Modules, designated as ZAF-336-24, ZAF-486-24, ZAF-636-24, ZAF-936-24, ZAF-1236-24, may be followed by additional suffixes for color temperature. 1. These products are only suitable for connection to a Class 2 power source rated 24 Volt DC or less. 2. These products are intended for use only when connected to a power source that complies with Class 2 voltage and energy limited circuit and is rated greater than 24V DC. 3. When these units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at 24 Volts DC or less. 5. These products are not required to be enclosed or protected from the weather in the end product. 6. These products may be secured in place in the end product by any means LED Illumination Modules, ZM-4047-CW, ZM-1957-CW, ZM-1543-R. 1. Each Class 2 LED Modules is only suitable for connection to a Class 2 power source, max. 24 Volt dc or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limits. 3. Class 2 LED modules, rated max. 12 Watts per LED unit or less. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at max. 24 Volt DC or less. 5. These products are not required to be enclosed or protected from the weather in the end product. Class 2 LED Modules, Cat. No. ZWF-XXXX-XX, where XXXX-XX will be replaced with alpha-numeric digits that indicated length and color. 1. These Class 2 LED modules are only suitable for connection to a Class 2 power source, rated 15 Volt or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limits. 3. These Class 2 LED modules are rated max. 2 Watts.per LED module. When these units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at max. 15 Volts or less. 5. These products are not required to be enclosed or protected from the weather in the end product. Class 2 LED Modules, Cat. No. ZWF-337-24CW, ZWF-438-24CW, ZWF-638-24CW, ZWF-939-24CW, ZWF-1239-24CW, ZWF-337-24WW, ZWF-438-24WW, ZWF-638-24VWV, ZWF-939-24VWV, ZWF-1239-24WW 1. Each Class 2 LED Module is only suitable for connection to a Class 2 power source, max. 24 Volt dc or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limits. 3. Class 2 LED modules rated max. 12 Watts per LED unit or less. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations with supply sources rated at max. 24 Volt DC or less. 5. These products are not required to be enclosed or protected from the weather in the end product. JOHNSON WALKER & ASSOCIATES L LC, DBA IMPERIAL PLASTICS MFG E225580 4337 MILL ST NORTH BRANCH, MI 48461 Aluminum Reinforced Sign Face Trim, designated Signatrim. 1. Acceptable for use in dry, damp and wet locations. 2. Water exclusion must be determined in the end product. 3. Minimum 5 cm (2 in.) spacing from heat producing components required. 4. The specified solvents are continuously applied to edge of acrylic or polycarbonate sign face. Additional specified adhesives may be applied for the final bond. Sign Face Generic Material Solvent Final Bond Adhesive Sign Trim Generic Material Methyl Methacrylate (Acrylic)Methylene Chloride Methylene Chloride Cellulose Acetate Butyrate Methyl Methacrylate (Acrylic)Weld-ON #4 Weld-ON # 16 Cellulose Acetate Butyrate Methylene Chloride Polycarbonate Transco Transco Cellulose Acetate Butyrate Channel Bond Channel Bond 5. The suitability of the securement or "fit" of this trip cap shall be determined in the end product. Screws or solvents are considered acceptable for permanent mounting. v JS LED TECHNOLOGY CORP, DBA JS LED POWER INC E308859 1318 MAINE AVE BALDWIN PARK, CA 91706 Class 2 LED Modules, Cat. No. JE-OOABCD-XY-EZ Series, where A, B, C, D, E, Z, X and Y may be any alphanumeric characters, or suffixes may be blank. 77 SIGN COMPONENTS MANUAL (SAM)October 1, 2013 1. These products are only suitable for connection to a Class 2 power source rated 12 Volt AC/DC or less. 2. These products are each rated max. 24 watts per module. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 3. These products are suitable for use in dry, damp and wet locations. 4. These products are not required to be enclosed or protected from the weather in the end product. 5. When these products are used in applications other than signs or outline lighting, the need to conduct a temperature test shall be considered. Class 2 Power Supply, Cat. Nos. MJ-ABCD-WXYZ Series, where AB is 12, and CD-WXYZ is 20-1670,40-3300 or 60-5000. 1. These power supplies have a maximum of one Class 2 outputs. The output of these power supplies have been evaluated to Class 2 output requirements for dc circuits. 2. These products with Class 2 outputs are suitable for use in dry and damp locations only. 3. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls, and minimum 2 inches spacing to top of enclosure. 4. These products have not been subjected to Leakage Current, Strain Relief, and Impact Tests. The need to conduct these tests shall be considered in the product. In addition to these tests, the need to conduct the Mold Stress test on model MJ-1260-500 shall be considered in the end product. 5. These products shall be provided with additional enclosure when used in the end product. Class 2 LEDs, Cat. Nos. Cat. Nos. JE-001X (HS-F504BR4TN), JE-002X (HS-F504BN4TN), JE-003X (HS-F504884TN), JE-0041 JE-005X (HS-F504BY4TN), JE-006X (HS-R483AR4CY or HS-R484CN4CY or HS-R484CB4CY), where X may be replaced with A, B, G, M, R or W. 1 These products are only suitable for connection to a Class 2 power source, rated 15 Volt (DC or AC) or less. 2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage and energy limited circuit. 3. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. 4. These products are suitable for use in dry, damp and wet locations. 5. These products are not required to be enclosed or protected from the weather in the end product. Class 2 LED Controllers, Models HM-12RGB5A3-RC, HM-12RGB5A3-XY Series, where suffix X and Y may be any alphanumeric characters or blank for marketing purpose only. 1. These products are only suitable for connection to the output of a UL Listed or R/C Class 2 Power Supply rated max 24VDC. 2. These products are rated per the Table below. When units are connected to a Class 2 circuit, their ratings are to be limited to draw a total wattage of no greater than the secondary current rating of each Class 2 power supply. {Model Input - Class 2 Output - Class 2 ] HM-12RGB5A3-XY Series 12- 24 Vdc 10-24V 24 W 3. These products are suitable for use in dry, and damp. 4. These products are each rated max. 24 watts. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating of the Class 2 supply. Sign accessories, Class 2 LED power supplies, Model MJ-12100. 1. The output of this component complies with Class 2 requirements in the Standard for Class 2 Power Units, UL 1310. 2. In the end product, power supply spacing to other heat producing components shall be min. 2 inches spacing to sidewalls, and min. 2 inches spacing to top of enclosure. 3, These products shall be enclosed in the end product. 4. These power supplies are suitable for use in dry and damp locations. 5. These devices are intended for factory installation only. 6. This Class 2 power supply is not provided with any grounding. The enclosure must be grounded in the end product. JUSTIN INC E235322 2663 N LEE AVE SOUTH EL MONTE, CA 91733 Class 2 Power Supply, Model 601-12DC, 601-12DCR, 101-24DCR, 02240-12DCR, C2240-24DCR, C2240-12, 62240-12-240, C2240-24, and C2240-24-240. 1. These power supplies have been evaluated for use in LED signs. 2. The power supplies have outputs that individually comply with Class 2 circuit requirements. 3. These units are suitable for use in dry and damp locations without a need for an additional enclosure. 4. The output of this power source shall not be connected to any other power source or provide power to components connected to another power source. 5. These products shall have conductors entering, leaving or residing in the wiring compartment or junction box extending at least 150 mm (6 in) inside. Class 2 Power Supply, Model 601-12DC-LC, 601-12DCR-LC, 101-24DCR-LC, C2240-12DCR-LC, C2240-24DCR-LC, C2240-12- LC, C2240-12-240-LC, C2240-24-LC, and C2240-24-240-LC. 1. These power supplies have been evaluated for use in portable LED signs. 2. The power supplies have outputs that individually comply with Class 2 circuit requirements. 3. These units are suitable for use in dry and damp locations without a need for an additional enclosure. 4. The output of this power source shall not be connected to any other power source or provide power to components connected to another power source. 5. The attachment plug on the end of the power supply cord is not to be removed. KASON INDUSTRIES INC 57 AMLAJACK BLVD NEWNAN, GA 30265 Power supplies with Class 2 output circuits, Model 61815000200. E363080 LED MODULE SERIES ITEM NO.:LS0783 LS0783H-3 4 / e SIZE: • All the size date above is in mm • Tolerance for the size date is 1 0.2mm APPLICATION: • Applicable forhome, shopping mall, office meeting room, hotel, cabinet, and show windows, etc. C€ E 15.8mm 53.8mm Ih 111-1 7.4mn Sheet No. : 01 091.u: E320022 LS0783H-4 ## ¥ 1 ./ 4.. FEATURE: • No UV or IR radiation. • Superthinand flexible • Waterproof IP65 • High Brightness SMD LED • LED QTY: LS0783H-3: 3PCS LS0783H-4:4PCS • 50000 hours long life span • Color Temperature CW: 8000-900OK DW: 6000-6500K WW: 3000-3300K I Low temperature rising, less than 20t . Less than 7% light decay in 6,000 hours testing 0 120° Beaming Angle • Colour: LS0783H-3: G/B/P/WW/DW/CW LS0783H-4: R/Y Absolute Maximum Rating at TA=25t Parameter Symbol Absolute Maximum Rating Unit Voltage VIN DC12V VAC Electrostatic Discharge ESD 2000 V Operating Temperature TOPR -20°045°C °C Storage Temperature TSTG -20°C-60t °C Sheet No.:02 Electrical/Optical Characteristics at TA=25t(VIN=DC12VAC, 50Hz) Colour Voltage Current Power CT/WL Lumin.ous Ra WW DC12V 20mA 0.6W 3000-3300K ------ 64 CW DC12V 20mA 0.6W 8000-9000K ------ 83 R DC12V 20mA 0.6W 620-630nm ------ ------ G DC12V 20mA 0.6W 520-525nm ------ ------ P DC12V 20mA 0.6W 380-760nm ------ ------ Y DC12V 20mA 0.6W 585-595nm ------ ------ Maximum 'Connection 100Pcs 100Pcs 100Pcs 100Pcs 100Pcs 100Pcs illuminated diagram 90° 9oooo., 80%6096 4096 20%0%2096 4096 8096 too·:6 INSTALLATION 50% 1.Please rip PE adhesive tape on the back of the product, then stick to the oblects where you want. 2.Use the screws to fasten it again. MAX 100PCS Power .F EDC12V -1- 0 3.Connect multiple product (max 100 pcs), (The tatal power consumption of products should be less than 80% of driver's power),the connect the driver. • Connect red wire to the positive polarity and black wire to the negative polarity of power supply • Operate on 12 Volt DC Power Supply(constant voltage) • Wire length of powersupplyshould be no more than 3 meters;if more than that,suggest increasing wirediameter Sheet No. : 03 NOTE • Low voltage product, please make sure of the DC12v +2V input voltage • Please don't press the elements on the PCB from any angle by stress • Non-bendable • Please don't install in flammable, explosive orcorrosive circumstances -1)iscount' = ' C 4.4-•------------¥ u ¢4/»7Vile/11.4·5111'14'11:1-9%7"V m1 GO 115 151kth-*m THAU"4;3:- L 'FIRK' 19%\TilR'.V[: 34'nrmfl MASSAGE" L 14861 Moran St. #B Westmister, CA 92683 (714)848-9616 Phone (714)740-5030 Fax Website: www.i2isigns.com Email: info@i2isigns.com COMMENTS: i . - r---[-1 CLIENT:Nuad Thai Massage ADDRESS 2781 W McArthur Blvd. Suite F2 LOCATION:Width 22' DATE:02/5/14 CONCEPT:A1234 SALES: MASTER I.D. ZO/4-//3590 G.P 50 Zone 09-- 11 PI ANNFR 14 TRANSFEF P - TE RR #0 1,1@iZgfQjy gHggETo BE )UGH FINAL NONE X ..:.PPROVED Orr CUSTOMER APPROVAL LAN[U#19 AP<ROW ED?&MTURE TEDASIGNATURE DA This sign is intended to be installed in accordance with the requirements of Article 600 of the National Electrical Code and/or other applicable local codes. This includes proper grounding and bondingofthe sign. Contractors Lic. #917099 SCALE: 1/8" = 1' NOTE: This is an original drawing, created by i2i Signs Corp. It is submitted for your personal use in connection with a project being planned foryou by i2i Signs. It is not PAGE to be show to anyone outside 1 your organization, nor is it to be used, reproduced, copied orOF exhibited in any fashion. Any 2 printed colors on drawing are approximate. ---Discount« THA| 14 14861 Moran St. #B Westmister, CA 92683 (714)848-9616 Phone (714)740-5030 Fax 30"Website: www.i2isigns.comy 1[[!IlgI MASSAG E14 Email: info@i2isigns.com COMMENTS: 14' 1. MANUFACTURE AND INSTALL ONE SET OF ILLUMINATED CHANNEL LETTERS 2. FACES: - COLOR "Nuad" 12"H 1/8 ACRYLIC WHITE W/ RED OUTLINE 70+732-9 - COLOR THAI MASSAGE" 14"H 1 /8 ACRYLIC RED y27 9.3 3. RETURN: -5"DEEP PAINTED BLACK- TRIMP CAP BRONZE 4. ILLUMINATION: WHITE 12 DC LED LIGHT UITS - SPACING: 2.5 UNITS/STROKE INCH 5. LETTERS SHALL BE MOUNTED DIRECTLY ON THE WALL 5'x22' WITH €1 NON-FERROUS FASTENERS 1/4"x 1-1/2"PER LETTER (4) MIN.--1- 6. ALL WIRING AND COMPONENTS TO BE UL APPROVED.42\7. TRANSFORMER TO BE UL LISTED mAM600 WATT AS NEEDED4)DISCON·NECT_SWITCH: - --O 8. ULLISTED 18AWGWIRE RETAIN PLANS FOR FUTURE REVISIONS. 9. EXISTING WALL 5'H x 22'W SUBJECT TO ITEMS CHECKED AND CONDITIONS BELOW: CLIENT:Nuad Thai Massage ADDRESS 2781 W. McArthur Blvd. Suite F2 LOCATION:Width 22' - DATE:02/5/14 CONCEPT:Al 234 SALES: RR O INTERIOR TI ONLY -(4K O NO EXTERIOR ALTERATIONS/MODIFICATIONS O ALL MATERIALS TO MATCH EXISTING O SCREENING REQUIRED O SUBMIT LANDSCAPE PLANS -(t« #*u Wait, 9#J.Water drain hole L vivul I B. ; USTOMER APPROVAL LANOLORD APPHOVAL 0**™44 316/1,4 SIGIWFURE JDATE SIGNATURE DATE DRAWN BY:RR WE HAVE REVIEWED AND APPROVED THE SIGN DETAILED HEREIN TO BE FABRICATED PER THE SPECIFICATIONS SHOWN ON THE DRAWING 37-- This sign is intended to be installed In accordance with the requirements of Article 600 of the National Elect,ical Code and/0, other applicable local codes. This includ es proper grounding and bonding of the sign. Contractors Lic. #917099 SCALE: 1/8"=1' NOTE: This is an original drawing, created by i2i Signs Corp. It is submitted for your personal use in connection with a project being planned for you by i2i Signs. It is not PAGE to be show to anyone outside 2 your organization, nor is it to be used, reproduced, copied orOF exhibited in any fashion. Any 2 printed colors on drawing are approximate. - W 9 1// 1 Li l .ARP-fUR-93«--1-h City of Santa Ana. -CBC- 4-CE_2-013Minimum (4) screws per letter,maximum 24" on center, 2" penetration, #10 sheet metal screws, &(2) 44" drain holes per letterV• ect for the -V ,looeS er**<19 n06 06.4,0.0019,A CPI olsen\» ?\"f3 PERMIT TYPE:CNREE>LBG MECH ?RADING PERMIT#lojec)949/ELECTRICAL j OCC. GROUP 620 63«9PLAN APPROVAL t -CONSTA. TYPFThis set of plans and speclfications must be kipt on CODE EDITION 520,3 the job at all times And It Is unlawful to make anyI changes or alterations on same without written per-FLOOD ZONE . 9f mission from the Department of Building Safety /City of Santa Ana. . The approval of this: plan andepAclflcatiorts SHALL FLOOD ZONE CERTIR REQ'D YES 40NOT ba. beld to permit nor.be'an approval of thoviolation or any provisions of ANY City Ordinance MICROFILM YES lk>or State Law. -'- I'll'812%) )51 RADIANT BARRIER @ ROOF YES NO . 11 RESIDENTIAL DEV. FEE YES 26 Approved CITY OF SANTA ANA DEPARTMENT OF BUILDING SAFETY SCHOOL DISTRICT YES (,60 r 0 ...-9 .f position. or above & passage 00.41 4 en j r'. : ¢f 9 1