10181020_1122 N. CONCORD - Plan (2)
CALCULATIONS FOR Job:TRANG SOLAR PANELS Address: 1122 North Concord Street Santa Ana, CA 92701 FU MASTER I.D. 2 G.P. 21 ERR DR' PLANNEINDEX TO CALCULATIONS Sheet Item TRANSF 1 design loads, wind uplift check 2 attachment check, rail check, lateral check ROUGH PLANNING INSPEC Engineering Calculations Performed By: - Doug Engineering NAME 20751 Kelvin Lane, Huntington Beach, CA 92646 949-285-5104 SUBJECT TO ITEk RETAIN PLANE FO BELOW: For: Verengo Solar Plus ,4, O INTERIOR T? 20285 South Western Avenue, Suite 200 O NO EXTERIO Torrance, CA 90501 O ALL MATER!; O SCREENiNG(877) 403-3479 KOFESSON O SUBMIT LANI Project Number VS-6832 '*diiA/*411 Date:3/31/2014 uct-ov. 2-•02*ele4 CONDITIONS: S BASIS FOR DESIGN #00-'26163 ij li I EXP 06·30·14 1* # CODE:2013 California Building Code V\1 11 ASCE 7-10 N.J>\.Es/52,0 LIVE LOADS '9OFCAL ROOF 20.0 psf LATERAL Seismic Design Category: D R 6.5 Seismic Use Group I SDS 1 SS 150 %SD1 0.6 Sl 60% I 1 WIND Exposure C Figure 30.5-1 - Components and Cladding S 110 mph Table values are multiplied L 1 by X lit 1 1=1.21 Exposure C a 3 ft Pnet-Xx Kzt XIX Pnet30 1 '1 1 roof slope 7-27 degrees Atrb =20 sf Zone 1 Pnet30 = *Zone 2 Pnet30 = Zone 3 Pne,30 = Downward for All-zones -23.5 psf (interior zones)All panels within Zone 1 &2 -38.6 psf (end zones)Use Zone 2 Value -52.6 psf (Corner Zones within a) 13.8 psf I PROJECT: Trang Solar Panels Doug Engineering SHT.1 OF 2 CLIENT:V.S.Civil Engineering DATE 3/31/2014 BY:DM DE JOB NO. VS-6832 DESIGN LOADS Dead Loads Roof Comp. Shingle 3.5 psf Puplittzl =23.5 psf 5/8" Ply shtg 1.9 Pupliftz2 -38.6 psf Rf Frm'g 2.8 PWLdown =13.8 psf Misc.1.5 Uplift 0.6DL+0.6WL (N) PV System 3.0 Zone 1 0.6*3.0-0.6*23.5 -12.3 psf Zone 2 0.6*3.0-0.6*38.6 -21.36 psf Total DL 12.7 psf Downward DL+0.6WL LL 20 psf DL+WL -11.3 psf Unlift Check Existing 2x6 rafters @ 24" o.c. Spacing 2.00 ft Trib panel width =6 ft E 1500000 psi Fb =900*1.3*1.15 1346 psi I 21 inA4 Mallowa,6Wind =1357 ft-lb Spanl 11.17 ft 'VIallow26LL =1060 ft-lb Span2 13.17 ft See below for Wind Uplift loads Span3 3.83 ft due to concentated loads at attachments (Distance Wind Mmax P =Mmax to Att.Load Trib Load wind(ft· PVDL live(ft- Pts) a b Rl (lb) R2 (lb (psf) W (ft) (lb) lb) (lb) lb) Panel,Edge 3.00 1 3.50 3.50 7.67 -82.3 -37.6 -12.3 6.0 -119.9 -288.1 29.2 61.13 2 5.75 5.75 5.42 -58.2 -61.7 -12.3 6.0 -119.9 -334.4 29.2 70.96 Panel Edge 6.25 Panel Edge 17.08 3 18.08 6.91 6.26 -111.9 -123.6 -12.3 6.0 -199.8 -773.5 48.7 188.7 4 21.50 10.33 2.85 -50.9 -184.6 -12.3 6.0 -199.8 -525.3 48.7 128.1 Panel Edge 22.50 Span 1 Uniform DL 11.17 65.0 65.0 5.8 psf 2.0 11.6 pif Span 2 Uniform DL 13.17 76.6 76.6 5.8 psf 2.0 11.6 Reactions at Spanl -75.5 -34.2 Negative values are uplift reactions Reactions at Span2 25.8 -108.0 Mmaxwinduptift =353 ft-lb < 1357 ft-lb OK For DL+LL including the PV system weight point loads W=59.4 pif P = Mmax =1057 ft-lb < 1060 ft-lb OK 181.5 252.4 29.2 Ib A. PROJECT: Trang Solar Panels CLIENT:V.S. BY:DM Doug Engineering Civil Engineering SHT.2 OF DATE DE JOB NO. VS-6832 2 3/31/2014 CHECK SCREW ATTACHMENTS FOR WIND UPLIFT Pwuptilt =119.9 Ib 5/16" Lag with min 2.5" penetration for each attachment Table 11.2A - NDS - Lag Screw Withdrawal Values For 5/16" Lag into .5G wood 266 Ib Allowable wind load = 1.6*2.5*266 1064 Ib >120 Ib OK Unirac Selection Load for half a panel = 2.7' WUNIRAC =57.78 pif Per the Unirac Manual for 60 pif, the max span for Solar Mount Unirac Rails is 6.5' Use L-Foot SolarMount Rails with a spacing of 72" o.c. max for attachment points, typ. Table 8. L-Foot SolarMount Series Rail Span SM - SolarMount HD - SolarMount Heavy Duty (R) 2 15 3 33 4 43 0 7 75 8 9 93 I0 10.5 11.5 I2 12-5 w = £)&01!,uted Load *U) 20 25 30 40 50 FA 80 100 120 140 160 180 200 220 240 260 280 300 SM SM SM SM 91 SM SM SM SM SM SM SM 91 SM SM SM 91 Stl SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM 91 SM SM SM j SM SM SM SM 91 SM SM SM 91 SM SM SM 91 SM j SM SM SM SM 91 SM SM SM 91 SM SM MD SM SM SM SM 91 SM SM SM Sri SM HO SM SM SM SM SM SM SM SM HD HD SM SM SM SM 91 SM SM ID HD HD SM SM SM SM SM HD HI) HD SM SM SM SM 91 HD HD HD SM SM SM SM Sri HD HD SM SM SM SM 91 HD HD SM SM SM SM HD HD SM SM SM HD HD HD SM SM SM HD HD HD SM SM SM HD HD SM SM HO HD HD SM SM HD HD HD SM MD HD HD HD SM HD HD HD HD H D 1-ED HD WD HD HD HD HD HD HD HD LATERAL ANALYSIS DETERMINE ADDITIONAL LOAD COMPARED TO EXISTING FOR LATERAL LOADING Arootexisting= = 22 *Wpanet=2400 sf Wpanel = \Nroofexisting = 9.7*2400 =23280 Ib Wwallexisting = 15*80*4 =4800 Ib Wrestolarray = 42.1 Ib 926.2 Ib 234.08 Ib Wexisting =28080 Ib V = 0.182W Vroofexisting =5111 Ib Existing Total Lateral Force Vrootwpanels =5322 Ib New Total Later Force array =1160.3 Ib % increase =5322 5111 *100%-100% =4.1% increase which results in less than a 10% increase in the stress of existing lateral resisting elements OK AHJ NOTES: CITYOF SANTA ANA SHEETANDEX 1 PLAI%LSET LEGEND SCOPE OF WORK 2010 CALIFORNIA ELECTRICAL CODE: NEC 690.64 (B)(7) LOCATE INVERTER OUTPUT AS FAR AS POSSIBLE FROM NORMAL POWER SUPPLY AT SERVICE PANEL RELOCAnON OF EXISTING CIRCUITS MAY BE NEEDED. DO NOT CHANGE PHASING OF MULDWIRE CIRCUITS. PERMANENT SIGNAGE AT PV SUPPLY CIRCUIT BREAKERS MUST SAY: WARNING! INVERTER OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE. SIGNAGE TO BE LOCATED ADJACENT TO BACKFED BREAKER. 2-61 GENERAL NOTES, SCOPE OF WORK AND AHJ NOTES PV-lA SITE PLAN PV-2 SITE PLAN, ELECTRICAL ROOF PLAN AND EQUIPMENT ELEVATION 22=28 ROOF FRAMING PLAN AND CONSTRUCnON NOTES EM=a DETAILS 2¥=2 MATERIALS UST, SINGLE UNE DIAGRAM AND CONDUCTOR TABLE INV INVERTER(S)E'OFF.¤42 '71*D2 1 .,4.NIi·.. ArrUS?f'plDC] ' DC' DISCONNECT C I q_:3q-3£8_0___, C DISCONNECT LOAD%&2/4 MAIN SERVICE PANEL ._ SUB PANEL FINANCE PARTNER:METER UTILITY METER es J J IR NAE £¥=31 RESIDENTIAL ROOF-MOUNT PHOTOVOLTAIC SYSTEM SYSTEM SIZE: STC: 22 X 250.00W = 5.50kW LL A -2 1 -b PTC: 22 X 226.20W = 4.98kW DC 0530% 1 < . CD W (22) YINGU YL250P-29B MODULES d W 5 3 J (1) POWER-ONE-PVI-5000 INVERTER Cnzu-id)0:0- NAME OF UnUTY: m r=-03 SOUTHERN CALIFORNIA EDISON (SCO Z 9 5 6 kd AA 00LUE e05% 26 FINANCE PARTNER METER: SUNRUN INC.;M Zi Sl 19 f i LEC.ATTACHMENT TYPE: QUICK MOUNT ATTACHMENTS it all SPECIALTY WORK 6 E Rent NONE ;ity 01<C%3 0 0. : -he alMAIN SERVICE PANEL UPGRADE:n C Z M 'whAI/1 % d h SIGNAGE AND PLACARDS,4.· ./.1·'2 rt -- ELECTRICAL CALCULAnONS .- h FROM: UNKNOWN BUSS / DISCONNECT 2'12- CONDUIT (EXTERIOR RUN)TO: 200A BUSS/200A DISCONNECT ECEIVE APR 01 2014 City of Santa Ana ABBREVIATIONS ISC ................SHORT CIRCUIT CURRENT i..4 | JB JUNCTION BOX CB COMBINER BOX • ATTACHMENT POINT O PLUMBING VENT ® GAS VENT || ATTIC AIR VENT CALIFORNIA CODES PROJECT COMPLIES WITH • 2013 CALIFORNIA BUILDING CODE • 2013 CALIFORNIA MECHANICAL CODE • 2013 CALIFORNIA PLUMBING CODE • 2013 CALIFORNIA ENERGY CODE • 2008 CALIFORNIA ENERGY EFFICIENCY STANDARDS • ALL CITY ORDINANCES • N.E.C. 690 VICINITY MAP VOC ..............VOLTAGE OPEN CIRCUIT GENERAL INSTALLATION NOTES EWashington Ave_ - .2 ,&35 -=-; PROJECT SHE ,•32VMP ..............VOLTAGE AT MAXIMUM POWER •UNLESS OTHERWISE NOTED ON PIANS OR PER AMI NOTES. TIE FOLLOWING N ARE GENOWIZED AND PERTAIN ONLY TO BULDING PRACTICES AS ADOPTED BY 21 8 IMP ..............CURRENT AT MAXIMUM POWER VERENGO SOLAR.82 . 60 EMT ..............ELECTRICAL METALLIC TUBING PER ART. 705.12 (D)(2), THE PV BREAKER SHALL .0 1 Soo Wellington Ave - NOT EXCEED 120% OF THE ALLOWABLE BACK FEED LBW ..............LOAD BEARING WALL OF THE MAIN SERVICE BUSS RATING.a , 51_-EXISTING PV WIRE SHALL BE USED ON DC RUNS FOR 2 7 co JOB No. SO-14-03-519 DESIGN BY: F. CARBONELL DATE : 03/31/14 Dds (N) ..............NEW (aT) .............EXTERIOR UNGROUNDED/TRANSFORMERLESS INVERTERS. R Ef INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR 0 TO COMMENCING WORK.vatize Pt 1600 a \ I creens V Mabury.bl Concol C NLyon St. MaoCONDUIT TO MATCH HOME '' | PV- 1 a \Users\fcorbonell\Docurnents\Plons\SO-14-03-519\Trang (Santo Ana) SO-14-03-519.dwg Mar 31. 2014 UR g OD irovision Date Iss 1 6 1 STORY HOUSE - 2 [=-1 & grrrEct § 01)TED ) 6 92 -= DRNE WAY MECH G PERMIT#-inLELCUOCC. GROUB------2-4 Z0- 10 -O 0 ARCHITETURAL STRUCTURAL0 ACCEPTE[ FOR CONSTRUCTION 1LECT8'CBS OA rhihi. 1innullyu SEPARATE PE?MI rS ARE REQUIRED FORELECTRICAL, PLUMBING & MECHANICAL PLANS tThis get of plans and specifications must be kept on the job iat ail times and it E unl awful tc make any changes or iaiterations on same 'Nithc ul written permission from the iCity of Santa Ana. 2 44CONSTR. n'PE----ALA__- The acceptance of this plan and specifications SHALL NOT 4CODE EDITION-- .be held to permit nor be an approval of the violation of any -' provisions of ANY City Ordinance or State Law.FLOOD ZONEE | ul Z\ccepted ByEf-' -0.42=2=\)41 J n FLOOD ZONE CERTIE REQ'D YES NO CITY OF SANIAANA MICROFILM YES NO 4 oae Iss„ga.-__RADIANT BARRIER @ROOF YES NO RESIDENTIAL DEV. FEE YES NO rv-lASCHOO: n:Crro:r•·r YES \ NO /SITE PLAN SCALE:3/32" = 1'-0" LU133HS9LE: C.\Ueere\fcorboneir\Documents\F'long\$0-14-03-519\Trang (Santo Ana) SO-14-03-519.dwg Mar 31, 2014 - 12:04em *GETVAR,17) fcorbonell <REF: 11 N r t 1 PV-2 MOCJIVING PLAE - 1 ROOF PITCH: 10 ARRAY PITCH: 10 ROOF AZIMUTH: 279 ARRAY AZIMUTH: 270 ROOF AREA: 1328,22 SO FT ARRAY AREA:386.76 SOFT NO. OF MODULES: 22 %COVERED: 29.12% 9 1, 0 4.1 I ' 1 4 3 01 f , --I -\1 1-21 J 61 rn Z Ui '1) 6 W, 0 4 URA 1-L-1 m 1 :OR MITS aBING 08Cific- unlaw jithout 1 L- & 1 1 I C)4 , plan,r ¤10 je an i -- 9 623 Ordinf 2 2 1 HOUSEPHOTO 2 2 2 2 6 c:% A (0 8 - 1 0 - gy (YOF I».9 2211 1 TO UTILITY TO ARRAY 222 MSP L- M . 0 1 1 1/ \ 3'-0" 0 Dcl 11 11 6109-£0-t4-OS 'ON gor 1=,INUOC,VJ J Am INJID-jU J L-J L NORTH WALL WEST WALL J N l EQUIPMENT ELEVATION SCALE: N.T.S. 1 ELECTRICAL ROOF PLAN SCALE:1/8" = 1'-0" PV-2 311ll 133HS NV-Id =10061 MOUNTING PLANE -1 ROOF TYPE: 1'-10" (EXT 7 ---- 11'-2" (SPAN) VAULTED 13'-2" V (SPAN) VAULTED ---------1 0 CD 13'-10"COMPOSITE SHINGLE ROOF 0 (SPAN)J * E \I, MODULE TYPE = YI-250-29b 0- LU -38 / MODULE WEIGHT = 42.1 LBS „A rt.1 CE 5*9 1MODULE DIMENSIONS = 64.96")(38.98" = 17.58 SF ,U) o m 1 1 \ UNIT WEIGHT OF ARRAY = 2.39 PSF JMNE I O < 9 4 \ ATTACHMENT POINTS:h• 7r O.C. MA)C 05*.2 1,- - .-1 1 1 1 -L----------L- 1 1 32 1 1 N § --1---------t----------E- 1 1 --1-*------------------4-- FRAMING - 1 1 RANSmON --1---------------------r- POINT ------------------Iit- 1 1 1 1 1 1 -----------t---1-- 1 1 ---- PORTIONS OF ROOF HAVE VAULTED CEIUNG - VERIFY RAFTER SPACING IN - FIELD PRIOR TO INSTAUATION 0 4 @ -1 0 L STt ARE F ' & MB mons m ful to 1- written ind spe, pproval nce or S ;ANTA A 1 1 --1-- 1 \ 11 --1--- -- 1---4---L_-_1-___ I \r-O--7 -4--/- r r 11'-2"8'-2"5'-0" (SPAN)(SPAN) ' (SPAN) 'N 3'-10" DESIGN BY:DATE:( CD Z (SPAN) • REFERENCE PV-2B FOR ATTACHMENT DETAILS • ROOF FRAMING PILAN A \ Exp. 0,3WN /* CNIL/41 SCALE:1/8" = 1'-0" 2 2 - 117 I U --1 9 0: 0- PV-2A j 7LE: C:\User«fcarbonel\Documente\Plans\SO-14-03-519\Trang (Santa Ana) SO-14-03-519.dwg Mar 31, 2014 - 12:04pm KGETVAR,¥¥) fcarbonell <REF: PV MODULE - 2- RAII ALL W/i 5, 2. W - COMPOSITEALUMN. V BRACKET /ROOF WA" SS BOLT & NUT '0, \PV MODULE - - HASHING ATTACHMENTS 252>1 1 1/2" ALUMN. L BY UNIRAC 11 4 - IMN. "L" BRACKET 0-LU h 1- r- -4 1" SS BOLT & NUT CE 529 <3- 2-1/2" ALUMN.928 RAIL BY UNIRAC WKM \QUICK MOUNT AT[ACHMENTS /16" SS LAG BOLT MIN.r '-t COMPOSITE ROOF -PV QUICK MOUNT LU Z (95" PENETRATION SEALED *per.Q- 2-1/2" ALUMN. RAIL ATTACHMENTS |'Flaw n BY UNIRAC ->CE 'n/SIKAFLEX lA P//42=RENGRATION SEALED- W/SIKAFLEX TA > QUICK MOUNT DETAIL SCALE: 10=1'-00 1 QUICK MOUNT BLOW-UP DETAIL SCALE: 3"=1'-0" 2 QUICK MOUNT ISO DETAIL SCALE: N.T.S. 3 Wily' Chl....1¥ 1 t CO E J = 0 UOI 2.1, ", i Z>O n :HMI]RAL *43 A W SDI O, @jill EXISHNG ROOF TILE L 44{ / 4 i" CONDUIT RUBBER GROMMET - ILSCO COPPER GROUND LUG - S.S. HEX NUT S.S. STAR WASHER FLASHING METAL PLATE Elli ¢ae vial®n of ai y IVOTAIC 9kZZ-00€ SOUD BARE COPPER CONDUCTOR SOLAR MODULE TYP. CONDUIT PENETRATION DETAIL SCALE: N.T.S. 4 GROUND LUG DETAIL SCALE: 1/2"=1'-0" 5 - CONDUIT CONDUIT -- UNISTRUT CONDUIT CLAMP - UNISTRUT CONDUIT CLAMP J L 1-5/8 X 1-5/8 UNISTRUT 4-OS 'ON 8Or 311ll 133HS LU 0 0 CONDUIT HEIGHT L 1-5/8 X 1-5/8 ABOVE MOUNnNG UNISTRUT PLANE TO ISO VIEW BE 1 5/8"SCALE: N.T.S. - PV-2BCONDUIT CLAMP ASSEMBLY SCALE: 3" = 1'-O" 6 ; CONDUIT TO ROOF ISO DETAIL SCALE: N.T.S. 7 2 C: \Ueers\fcarbonell\Documents\plans\SO-14-03-519\Trang (Santa Ana) SO-14-03-519.dwg Mar 31, 2014 - 12:04pm $(GETVAR,??) fcarbonell I.- 1 11 'JB 11 Ulll PEQUIPMENT QTY DESCRIPTION QTY CONDUCTOR INFORMATION YINGU ENERGY (CHINA)(4) #10AWG - PV WIRE YINGU YL250P-29B 250W (1) #6AWG - BARE COPPER GNDSOLAR PV 22 VOC= 38.4V VMP= 30.4VMODULE (4) #10AWG - THWN-2ISC= 8.79A IMP= 8.24A PMAX: 250W Pm RAnNG: 226.2W (1) #6AWG - THWN-2 GN IN 3/4» EMT (3) #10AWG - THWN-2 KRALOY J-BOX 6x6x6 CSA C22.2 J-BOX 1 #40 CUTOUT, JUNCRON AND (1) #6AWG - THWN-2 GN IN 3/4" EMT PULLBOXES ) #6 BARE ARMOR COPPER ei (1) EXISTING GROUNDING SYSTEM POWER-ONE-PM-5000-Olm>-US-A (240V) MPPT VOLTAGE RANGE: 200-600V MAX DC INPUT VOLTAGE:INVERTER 1 UNGROUNDED SYSTEM600V AC VOLTAGE RANGE: 211-264 MAX AC OUTPUT CURRENT: 23A SYSTEM WIRES TO BE RED AND BLACK CEC EFFICIENCY: 96.5% DC DISCONNECT 1 USED WITH INVERTER. SEE SPECIACADON SHEET. 1-210+C SMART METER 120-240 SUNRUN 1 VAC, 3.3V / TTL COMPAPBLE METER ASYNCHRONOUS AC DISCONNECT PHOTOVOLTAIC BREAKER MAIN SERVICE DISCONNECT MAIN SERVICE PANEL 1 EATON / CUTLER HAMMER DG221 URB 600 VAC, 30A, NEMA 3R, UL USTED 1 2-POLE PV BREAKER, 240V, 30A 1 240V, 200A NEW UPGRADED MAIN SERVICE PANEL 1 1-PHASE, TOP FEED, 120/240 VAC, 200A 120% RULE 200 X 1.2 =240A 240 - 200 = 40A MAX BACK FEED Bl-DIRECTIONAL UTILITY METER 1 -PHASE, 3 WIRE 120/240V 111 GROUND ROD 1 05/8" X 101 8' EMBED. PLACED MIN 6' AWAY FROM EXISTING GROUND ROD CONDUIT 40' 3/40 EMT CONDUIT ATTACHMENTS 44 QUICK MOUNT ATTACHMENTS 2 El 11 MODULES IN SERIES RAIL 180'UNIRAC RAIL 1 :ROOF 10: PITCH MID CLAMPS 32 MID CLAMPS 270: AZIMUTH END CLAME 24 END CLAMPS 1 __9 11 MODULES T IN SERIES 1 T% MS 000 1:ROOF 10: PITCH 270 : AZIMUTH L<D LE}--39 Le 20-14-OS 'ON 80r 03 : *8 NDIS30 W LE/£0 31VD 311I1133HS 3Nll 319NIS PV-3 2 C:\Ugers\fcarbonell\Docurnente\plans\SO-14-03-519\Trong (Santa Ana) SO-14-03-519.dig Mor 31, 2014 - 12:04$,m KGETVAR,9,) fcarbonell F: E E ®EE E E lei El t Lic.#935263 GROUND-LFAULT DETECTION AND {INTERRUPTION TO BE INSTALLED AT INVERTER PER NEC 2011 690.5 (C) WARNING ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED, NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED fINVERTER OUTPlJT (CONNECRON TO BE INSTALLED AT MAIN SERVICE PANEL LOCATED ADJACENT TO BACKFED BREAKER PER NEC 2011 705.12 (D)(7) WARNING INVERTER OUTPUT CONNECRON DO NOT RELOCATE THIS OVERCURRENT DEVICE MAX PVVOLTAGE & CURRENT CALC'S: RECORD LOW TEMP. CC): -5 VOLTAGE CORRECTION PER NEC 690.7: 1.12 MAX PV SYSTEM VOLTAGE (PER NEC 690.7): Vcorrection X Voc X # MODULES IN SERIES 1.12 X 38.40 X 11 = 473.09V MAX PV CURRENT PER NEC 690.8(A)(1): AC CONDUCFOR AMPACITY(CALCULATIONS: 1 # OF INVERTERS: 1 EXPECTED WIRE TEMP CC): 31' TEMP CORRECnON PER NEC TABLE 310.15(B)(16): 0.96 CIRCUIT CONDUCTOR SIZE: 10 AWG # OF CURRENT CARRYING CONDUCTORS: 3 CONDUIT FIll PER NEC 310.15(B)(3)(a): 1 CIRCUIT CONDUCTOR AMPACITY: 40 A DISCONNECRON MEANS; TO BE INSTALLED AT ALL AC AND DC DISCONNECTS RESPECTIVELY PER NEC 2011 690.14(C)(2) SOLAR AC DISCONNECT SOLAR DC DISCONNECT DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSmON; TO BE INSTALLED AT DISCONNECTING MEANS PER NEC 2011 690.17 WARNING ELECTRIC SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE UNE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSmON. PHOTOVOLTAIC POWER SOURCE SHALL BE LABELED WITH THE FOLLOWING WARNING AT EACH JUNCnON BOX, COMBINER BOX, DISCONNECT, AND DEVICE WHERE ENERGIZED, UNGROUNDED CIRCUITS MAY BE EXPOSED DURING SERVICE PER NEC690.35(F) WARNING ELECTRIC SHOCK HAZARD. THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED DIRECT-CURRENT PHOTOVOLTAIC POWER SOURCE TO BE INSTALLED AT INVERTER PER NEC 690.53 & 690.54 OPERAnNG CURRENT: 8.24A OPERATING VOLTAGE: 334.40V SHORT-CIRCUIT CURRENT: 10.99A MAX SYSTEM VOLTAGE: 473.09V DIRECT--CURRENT PHOTOVOLTAIC POWER SOURCE TO BE INSTALLED AT AC DISCONNECT PER NEC 690.54 MARKING SHOULD BE PLACED ON All INTERIOR AND EXTERIOR PV CONDUIT, RACEWAYS, ENCLOSURES, AND CABLE ASSEMBUES, EVERY 10 FEET, AT TURNS AND ABOVE AND/OR BELOW PENETRATONS AND ALL PV COMBINER AND JUNCTION BOXES. o SHALL BE REFLECTIVE WEATHER RESISTANT MATERIAL CAUTION: SOLAR CIRCUIT TO BE LOCATED AT MAIN SERVICE PANEL: CAUnON: SOLAR ELECTRIC SYSTEM CONNECTED TO BE INSTALLED ON THE FACE OF THE SERVICE METER PANEL PER NEC 2011 705.10 CAUTION: POWER TO THIS BUILDING IS ALSO SUPPUED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN AT: CE] METER AND MAIN SERVICE AC DISCONNECT DC DISCONNECT INVERTER L - MARKING CONTENT AND FORMAT 0 RED BACKGROUND o WHITE LETTERING 0 MINIMUM 3/8" LETTER HEIGHT u ALL CAPITAL LETTERS O ARIAL OR SIMILAR FONT, NON-BOLD 0 WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT (DURABLE ADHESIVE MATERIALS MUST MEET THIS REQUIREMENT REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): 1.25 X MAX INVERTER OUTPUT CURRENT= 1.25 X 23.00 = 28.75 A DERATED AM)ACITY OF aRCUIT ODUC[016 PER l€C TAELE 310.15(B)(16): TEMP CORR. PER NEC 310.15(B)(16) X CONDUR FILL CORR. PER NEC 310.15(B)(3)(0) X CIRCUIT CONDUCTOR AMPACITf = 0.96 X1X40= 30.72 A 3% 49 CONCORD 1.25 X Isc 1.25 X 8.79 = 10.99A DC CONDUCTOR AMPACITY CALCULATIONS: ARRAY TO JUNCTION BOX EXPECTED WIRE TEMP ¢C): 31' TEMP CORRECTION PER TABLE 310.15(B)(16): 0.96 # OF CURRENT CARRYING CONDUCTORS: 4 CONDUIT FILL CORRECnON PER NEC 310.15(B)(3)(a): 0.8 CIRCUIT CONDUCTOR SIZE: 10 AWG CIRCUIT CONDUCTOR AMPACITY: 40 A REQUIRED CIRCUIT CONDUCTOR AMPACHY PER NEC 690.80&8): 1.25 X 1.25 X Isc = 1.25 X 1.25 X 8.79 = 13.73A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(16) X CONDUIT FIU CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.96 X 0.8 X 40 = 30.72A DC CONDUCTOR AMPACITY CALCULATIC FROM JUNCTION BOX TO INVERTER AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT PER NEC 310.15(B)(3)(c): + 22' EXPECTED WIRE TEMP ¢C): 31' + 22' TEMP CORRECTION PER TABLE 310.15(8)(16): 0.76 # OF CURRENT CARRYING CONDUCTORS: 4 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 0.8 CIRCUIT CONDUCTOR SIZE: 10 AWG CIRCUIT CONDUCTOR AMPACITY: 40 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): 1.25 X 1.25 X Isc 1.25 X 1.25 X 8.79 = 13.73 A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(16) X CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.76 X 0.8 X 40 = 24.32 A AC OUTPUT CURRENT 23A PV-4NOMINAL OPERATING VOLTAGE: 240V C.\Users\fcarbonell\Documente\Plans\SO-14-03-519\Trang (Santo Ano) SO-14-03-519.d, g War 31, 2014 - 12:04¢,m KGEIVAR,?i) fcarbonell F: ® ® 0 ® ® 0. bll,NAL,t & NU I tb Lic.#935263 - (VEb 9 1,4,1 \4 -1 L 11- 55 Co M Co R D 1Olt lola YGE 60 YL255P-29b YL250P-29b CELL SERIES YL245P-29b YL240P-29b YL235P-29b YINI ILAR U.S. Soccer Powered by Yingli Solar i r 1 i i Ill COMPANY Yingli Green Energy (NYSE:YGE) is one of the world's largest fully vertically integrated PV manufacturers. With over 4.5 GW of modules installed globally, we are a leading solar energy company built upon proven product reliability and sustainable performance. Founded in 1998, Yingli Green Energy serves customers through our U.S. subsidiary,· Yingli Americas, co-headquartered in New York and San Francisco. We are the first renewable energy company to sponsor the U.S. National· Soccer teams and the FIFA World Cup™. PERFORMANCE Industry leading in-house manufacturing of polysilicon, ingots, wafers, cells and modules ensures tight control of our material and production quality. High performance, multicrystalline solar cells deliver a module series efficiency of up to 15.6%, reducing installation costs and maximizing the kWh output per unit area. Tight positive power tolerance of -OW to +5W ensures modules , are delivered at or above rated power, improving system performance through the reduction of module mismatch loss. ·34*14*3: QUALITY & RELIABILITY Robust, corrosion resistant aluminum frame independently tested to withstand wind and snow loads of up to 50 psf and 113 psf, respectively, ensuring mechanical stability. Manufacturing facility certified to ISO9001 Quality Management System standards. Module packaging optimized to protect product during transportation and minimize on-site waste. SILVER FRAME WARRANTIES Leading limited power warranty* ensures 91.2% of rated power for 10 years, and 80.7% of rated power for 25 years. 10-year limited product warranty. * In compliance with our warranty terms and conditions. QUALIFICATIONS & CERTIFICATES UL 1703 and ULC 1703, UL Fire Safety Class C, CEC, FSEC, ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007, SA8000 c(©us * EER#1 m :, LISTED -2 {PHOTOVOLTAIC MODULE)=3>1.••..6-·-; CZ-3 44DD 0.0 LISOLAR.COM/US Yingli Americas J 1 ':-% £4 th 9: 7 fGE 60 CELL SERIES Powered by YINGLI ELECTRICAL PERFORMANCE Electrical ¤arameters at Standard Test Conditions (ST€) YL255P-29b YL250P-29b Yl.245P-29b YL240P-29b YL235P-29bModule type . Power output P..W 255 250 245 240 235 Power output tolerances M'rnal W -0/+5 Module efficiency :len %15.6 15.3 15.0 .14.7 14.4 Voltage at P...Vmpp V 30.6 30.4 30.2 29.5 29.5 Current at P._Impp A 8.32 8.24 8.11 8.14 7.97 Open·circuit voltage Voc V 38.7 38.4 37.8 37.5 37.0 Short·circuit current 1- A 8.88 8.79 8.63 8.65 8.54 STC: 1000W/m' irradiance, 25°C cell temperature, AM 1.59 spectrum according to EN 60904-3Average relative efficiency reduction of 5.0% at 200W/rn' according to EN 60904-1 GENERAL CHARACTERISTICS Dimensions (L/W/H)64.96 in (1650mrn)/38.98 in(990 mm)/ 157 in (40 mm) Weight 42.1 lbs (19.1 kg) PACKAGING SPECIFICATIONS Number of modules per pallot 26 Number of pallets per 53' container 34 Packaging box dimensions (L/W/H)67 in (1700 mm)/ 45 in (1150 mm) / 47 in (1190 mm) Electrical parameters at Nominal Oceratina Cell Temberature (NOCT) . * Box weight 1177 lbs (534 kg) Power output P,re W 184.7 181.1 177.9 174.3 170.7 Voltage at P-i V.Ip V 27.9 27.6 27.2 26.6 26.6 Units: inch (mm) Current at Pr,„1.p A 6.63 6.56 6.54 6.56 6.42 38.98 (990) Open-circuit voltage Voc V 35.7 35.4 34.5 34.2 33.8 . . 37.24 (946)1.57 40) Short-circuit current 6 A 7.19 7.12 6.99 7.01 6.92 gi NOCT: open-circuit operating cetl temperature at 800W/m' irradiance. 20°C ambient temperature, 1 m/s wind speed THERMAL CHARACTERISTICS Nominal operating cell temperature NOCT *C Temperature coefficient of Pm„V 96/.C Temperature coefficient of V.0., 96/C Temperature coefficient of l.c al. 96/'C Temperature coefficient of Vmpp Ov.w 96/•C OPERATING CONDITIONS Max. system voltage Max. series fuse rating limiting reverse current Operating temperature range Max. static load, front (e.g.. snow and wind) Max- static load. back (e.g.. wind) Hailstone impact - CONSTRUCTION MATERIALS Front cover (material/type/thickness) Cell (quantity/material/type/dimensions/ area/#of busbars) Encapsulant (material) Frame (material/color) Junction box (protection degree) Cable (type/length/gauge/outside diameter) Plug connector (manufacturer/type/protection degree) 1.J' g46 +/. 2 · - -0.45 1 6 -0.33 'LL 6 0.06 Grounding holes e e 1% 9e 6-00.236 (61 - I B : 9 -0.45 M= : 600VDC Mounting holes 4-0.256x0.315 (6-5xe) 15A ,4- 41 15A a Drainage holes B'-'8 5 1 8-0.12x0.315 Oxe) ,-F; ' -40 to 194'F (-40 to 90'C) 113 psf (5400 Pa)(100) 50 psf (2400 Pa) 1 in (25 mm) at 51 mph (23 m/s) Low·iron glass / tempered / 3.2 mm A SECTION B-8 ,1 Glass may have anti-reflective coating -1 60/polysilicon / multicrystalline /156 rnm x 156 mm/243,3 cnn' /20,3 # // 1.26(32) ' ,/ Ethylene vinyl acetate (EVA)---------0 Aluminum alloy / anodized silver or black- . - .-- -. Warning: Read the Installation and User Manual in its entirety 2 IP65 before handling, installing, and operating Yingli modules. PV Wire / 43.31 in (1100 mm) / 12 AWG / 0.244 in (6.2 mrn) Amphenol / H4 / IP68 Our Partners NI 3.94 0.47 (12) (40) The specifications in this datasheet are not guaranteed and are subject to change without prior notice. This datasheet complies with EN 50380:2003 requirements. Yingli Green Energy Americas, Inc. info@yingliamericas.com Tel: +1 (888) 686-8820 YINGLISOLAR.COM/US NYSE:YGE INGIMINSOLAR © Yingli gGreen Energy Holding Co. Ltd. YGE60CelISeries2013_EN.201301_V01 U.S. Soccer Powered by Yingli Solar / 'liA powerane<. ' 1.14 . 1 .-. · D p'·.it LD 12,44,4 m PVQ=5000=TL PVO-6000=TL LF.. 4, 61:' 6- -tb k GENERAL SPECFICATIOI\IS .liu r 'Vt, 1« 7% 3. i. - Designed for residential and small commercial PV installations, this p.lit inverter fills a specific niche in the Aurora product line to cater for 221. those installations producing between 5kW and 20kW. -.9. 1 at_,527'464 ' till'll'll'll'll'll//4.1.11'..i,194,41 -- This inverter has all the usual Aurora benefits, including dual input section to process two strings with independent MPPT, high speed and precise MPPT algorithm for real-time power tracking and energy harvesting, as well as transformerless operation for high performance efficiencies of up to 97.1%. The wide input voltage range makes the inverter suitable to low power installations with reduced string size. This outdoor inverter has been designed as a completely sealed unit to withstand the harshest environmental conditions. 'W- i 5'·f;tj.»2 -'· -2 < ti, . A.,4 te.· if 99:.6574. I44airripiki:f .c: 4915 1 i .... 036 51,1/h & 1%1Rng 80, 6945.3*2:*:fi,F 1.. ...1*231 6 **1,68.4/fiLi FFidatU+Iles 2 C 1· • Each inverter is set on specific grid codes which can be selected in the field • Single phase output • Dual input sections withindependent MPPT, allows optimal energy harvesting from two sub-arrays oriented in different directions • Wide input range • High speed and precise MPPT algorithm for real time power tracking and improved energy harvesting • Flat efficiency curves ensure high efficiencyat all output levels ensuring consistent and stable performance across the entire input voltage and output power range • Outdoor NEMA 4X rated enclosure for unrestricted use under any environmental conditions • RS-485 communication interface (for connection to laptop or datalogger) • Compatible with PVI-RADIOMODULE for wireless communication with Aurora PVI-DESKTOP • Integrated Arc Fault Detection and Interruption (-A Version) 71-/pir U · :4 -42 -44 . : 0 4 9 . G r44 4.-·4·:'3, Nom-nal Output Power W,5000 ' 6000 Maximum Output Power W 5000 6000 Rated Grid AC Voltage V 208 240 277 208 240 .277 i!@*t$.i»j®}1*#&R#*'&9*'r¥*ARMM**%4*r#*h*m®m?.'i·*»!2222£2<1 Numberof Independent MPPTChannels 2 2 Maximum Usable Power for Each Channel .W 4000 4000 AiGoiute MGirnlimOottage (vmax) V 600 600 *#*9 /*fa-91(.Vifa&L ...._.-- . V 200 (adj. 120-350)280 (adflioato 1 Full power MPPTVoltage Range . , opei#fihs¥@LWGge RAge- -------'- ------- ·· - - ·---- ---··.--V . 0.7*Wtart-580 0.7xktart-580 Maximum Current (Idcmax) for both MPPT in Parallel A 36 36 Maximum Usable Current per Channel A 18 18 Maximum Short Circuit Current Limit per Channel A 22 22 Numberof Wire Landing Terminals Per Channel 2 Pairs 2 Pairs Array Wiring Termination Terminal block, Pressure Clamp, AWG8-AWG4 £241@9*1-Al) *202-9*#59*tia&efam 2&468$*1*BE#Tr*C#&*%81#i&*4*3&00kljsel:*12i#imdi#Wfjlj*8223:*bE.61¢221 Grid Connection Type - -1 _8djult*le-Yo#agEREge (Vmin-Vmax) V tl Grid Frequency Hz fd)*t,ble p.*(Freplelfy-Riege. __- __.-- -__-_ Hz Maximum Current (lacmax)AM Power Factor Total Harmonic Distortion At Rated Power % Con®butory Fault Current**A.jAwS 36. Grid WiringTermination Type·,pi21ette<D £91?isl*@Biia[*tiN&2*&§89..9&&(WId'..a,:.fe*d/a Input Reve;A pola my Protection Over-Voltage Protection Type PV Array Ground Fault Detection 0nw Split-0/3W 10/2W 10/2W Split-0/3W 1-42 --_ 33-228 211-264 244-304 183-228 211-264 244-304 - 60 · 60 57-605 57-60.5 27 23 20 30 28 24 > 0.995 >0.995 <2 <2 ?5/25.63 36.5/25.81 31.75/22.45 36.25/25.63 363/25.81 31.75/22.45 Terminal block, Pressure Clamp, AWG8-AWG4 £05£12485,144*4.4$/*0#44 F4549kkNNSI#*&M28 Yes Yes Varistor, 2 for each channel ' Varistor, 2 for each channel -Prisiin-upAiGWid*dlinic-GFbi ---- ----Pre start-up Riso and dynamic GFDI-- .__.*qulies Floigng.Auays) . _.. _(Requires.Flpating Arrap) Output. . .. .- Anti-lslanding Protection Over-Voltage Protection Type Maximum AC OCPD Rating A a Emti@-4.#Ed.*F***t,f.*,,.TIA..LiMIX#tee@*4%&€4;.SLit/,8**#*t Maximum Efficiency % CEC Efficiency % (g##hililiq Paifd;Mibie,#.12403*2€Mt¥,KA..04.&16'.'44%***%'**08 Stand-by Conswl'Ption .WRMS Night time consumption WRMS -t«&#HHi¢ationla*0.--3»*99**43:*0426*W..,4.¢#33.'4:i User-Interface Remote Monitoring (l,RS485 incl.1 Wired Local Monitoring (lxR5485 Inci.) Wireless Local Monitoring ··160.¢6*m.¢61#Lz¢lfi?Ak¥·*ii.¥*%§3:4:41,2?it¢84·Qioff,AN#1*2*bi·?.re*·i.,zv-4, Ambient Air Operating Temperature Range .F (°C) Ambient Air Storage Temperature Range °F (°C) Relative Humidity %RH Acoustic Noise Emission Level db (A)@1 m Maximum Operating Altitude without Derating ft(m) 01,Midhiigal *Sbkk!*i#4*y,«***-.;FPeltte4»9:**2,48%6**F,t Enclosure rating 96iff-9- - 4-I---I-/# - -Dimension; (Hxwxm in (mm) merk-02-(711*fihi> requi;Jnents-- _Megs UL 1 741 /|EE 1 547 reqdiremAts WIistor. 2-(l, 26/6-G)Varistor, 2 (L,-6/L,-G) 35 30 ; 25 40 35 3065€2242.4,44414:-LE<#CLG*,d:ttaliq97.1 97.1 . 96.5 96.596 96.5 i 963 <44*42»014:,A*¢i*-4-8*¥€2024**ST&*.*475*,€<¢ft:.94 38 . <8 < 0.6 ' < 0.6 Isj.·94*22**fmlt#*lg#Knigrk*lit-admidd'WaSgRF'<diwi,agQTAL,ij 16 characters x 2 lines LCD display • AURORA-UNIVERSAL (opt.) PVI-USB-RS485_-232 (opt.), PVI-DESKTOP (opt.) PVI-DESICTOP (opt.} with Pin-RADIOMODULE (opt.) ·, 01*#» %·'-?fak -Ut<:4?*4§*}*92.*d.tek\52?)*0224*le#uNS·N -13 to+140(-25 to+60)-13 to +140 (-25 to +60)Mth.*ratjngitle 12?(59).. .- -40 to 176 HO to +80)-40 to 176 {-40 to +80) 0-100 condensing 0-100 condensing < 50 <50 6560 (2000)6560 (2000) *#A»§*.i.*idk#)3'biL.tt*46:i'f#H#*§7214**32317&Fik/=dit€. NEMA 4X NEMA 4X Natural Convection Natural Convection 41 A x 12.8 x 8.6 (1052 x 325 x 218) Weight Ib (1 Shipping-Weight Ib (1 NGurmr,Bystem Conduit Connections DC Switch Rating-(Per Contact) /V Safet A.7 . ,· 2-, 2% D :;mil-:4: 4 •44:'.- , :- '.'r ''ta '4. '17· €·i ..6?· ;194 4. Isolation Level Safetyand EMCStandard Safety Approval **€#iWJ.12 3%.6.' 1.32·3LW.-,Ij·DENLIntffl3352 Standard Warranty ye: Extended Warranty yeeBil'*R-*H.s"'. f':.1.1,7:0':779(7"·7.r.:,; 1.-1.-:.37?1 1.-2...;Standard - With DC Switch - Floating Array With DC Switch, Wiring box and Arc Fault Detector and Interrupter •All data is 5ubject to change without notice " Inverter can apply that much cument - Breaker will open (g) < 59.5 (27.0) < 78 (35A) Wall bracket Trade Size Kos: (2ea x 1/21 and (2eax 1 -1/4; 3 places side. front, rear) V 25/600 4.23IRY_3fl·252:JA2.69¢22-REE-2 Transformerless (Floating Array) UL 1741, IEE 1547, IEE 1547.1, CSA - C22.2 N. 107.1 ,CSAus · E. 7.Aur •'.,; f-'Or.ts-11 2:'?N-.'·:;9744 iw '·1·7·rep.rgr.*··%-d.....6,· 1 -41-»211.i. 44.i_,4.0.-...Al·U.'Ue,2.2.·=.,·. irs 10irs 15&202 i.·N'.13:f i:I". 2 -:-1 3 -c.:Ct:32t #': 32: 2 23-22f:jti@71.2 PVI-5000-OUTD-US PVI-5000-OUTD-US-A < 59.5 (27.0) < 78 (35A) Wall bracket ---Trid@5126*Bs:ii@,1-F/il------ - and (lea x 1 -1/4'; 3 places side, front, rear) 25/600 2241924*18*ra22*qt?5:li Transformerless (Floating Array) ·01 , UL1998 UL16998, FCC Part 15 Class B ,CSAu, 93 37 #VJELOTII.:35 10 15&20 i . I Un PVI-6000-OUTD-US PVI-6000-OUTD-US-A ,.fiENE:kil,26£'/ALIESS/Diliticis//36212*11(1210 Quick Mount PV Your SO/ution in Mounting Products Solar •H2O . Conduit • HVAC • Custom Composition Mount Specifications - 5/16" - PV - Quick Mount PV ® is an all-in-one waterproof flashing and mount to anchor photovoltaic racking systems, solar thermal panels, air conditioning units, satellite dishes, or anything you may need to secure to a new or existing roof. It is made in the USA of all aluminum and includes stainless steel hardware. It works with all standard racks, installs seamlessly and saves labor by not need- ing to cut away any roofing, will out live galvanized 2 to 1, and is a better low-profile mount. irtrt Split Lock Washer SS 5/16" (Not a theft- prevention feature) Fender Washer SS 5/16" x1" - EPDM Rubber Washer 60 Durometer 5/16" - Sealing Washer SS 5/16"- Hanger Bolt SS 5/16" x E - 1 1/4" Machine, 1 3/4" Spacer, 3" Lag Mount & Flashing Aluminum - Mount 1 1/4" x 1 1/4" x 2 1/4" Beveled Block Flashing .05" thick For standard composition roofs: 9 t.ar -44.-- ESR-2835 . (2) Hex Nuts SS 5/16" flashing is 12" x 12"mount is attached 3" off center 4-1 0 - S-in·Mt,1 . A Lag pull-out (withdrawal) capacities (lbs) in typical lumber: Lag Bolt Specifications Specific 5/16" shaft 5/16" shaft gravity per 3"per 1" thread depth thread depth Douglas Fir, Larch .50 798 266 Douglas Fir, South .46 705 235 Engelmann Spruce, Lodgepole Pine (MSR 1650 f & higher).46 705 235 Hem, Fir .43 636 212 Hem, Fin (North).46 705 235 Southern Pine .55 921 307 Spruce, Pine, Fir .42 615 205 Spruce, Pine, Fir (E of 2 million psi and higher grades of MSR and MEL)..50 798 266 Sources: Uniform Building Code; American Wood Council Notes: 1) Thread must be embedded in a after or other structural roof member. 2) Pull-out values incorporate a 1.6 safety factor recommended by the American Wood Council. 3) See IBC for required edge distances. 1 of 4 936 Detroit Ave Suite D, Concord, CA. 94518 Phone: (925) 687-6686 Fax: (925) 687-6689 Email: info@quickmountpv.com www.quickmountpv.com 5/16" SS Hex Nut 5/16" Split Lock Washer /(Not a theft-prevention feature) 5/16" x 1" SS Fender Washer Block pivots on flashing 5/16" 60 Durometerwith water-proof seal -EPDM Rubber Washer.- 5/16" SS Sealing Washer - Typical L fool..j -/not included ,-5/16" SS Hex Nut Beveled Block 11/4" x 1 1/4" x 21/4" - 5/16-18 x 6" SS Hanger Bolt: 11/4" Machine/ 1 3/4" Spacer12"3" Lag Ile 7 \\ U 1 11M Compostion Roofing 1/2" 0SB or/ Plywood Scale 1:2 2 1/4"12" Rafter' TITLE:QM-PV-Comp 5/16" Scale 1:5 PROPERTY OF QUICK MOUNT PV * ALL RIGHTS OF DESIGN OR INVENTION ARE RESERVED COMMENTS DATE 1/07/11 REVISION 5 DRAWN BY F.K. FILE NAME QMSC_EXP_ 3125 Quick Mount PV* LV_UL Solutic/ljo-Maunting.fro.dilets Solar · 11,0 · Conduit · HVAC · Custom t .... 'JOE L A c>11/1,1 6" 3" 4, STRUCTURAL ENGINEERS January 13,2014 'kp.keHETH ' / No. $3878 4· ·STRUCTUidh.17.k- UniRac 8 4\mt1411 Broadway Boulevard NE & i /Albuquerque, New Mexico 87102-1545 TEL: (505) 242-6411 FAX: (505) 242-6412 Attn.: Engineering Department, Re: Engineering Certification for UniRac's SolarMount Code-Compliant Installation Manual 227.3 PZSE, Inc.-Structural Engineers has reviewed UniRac's "SolarMount Code-Compliant Installation Manual 227.3" published January 2014 and specifically "Part I. Procedure to Determine the Design Wind Load", and "Part II: Procedure to Select Rail Span and Rail Type". The procedures are used to determine the calculation ofthe design wind force, load combinations, applied loading and rail selection. All information, data and analysis contained within the Installation Manual are based on, and comply with the following: 1. Minimum Design Loads for Buildings and other Structures, ASCE/SEI 7-05 and ASCE/SEI 7-10 2. 2012 International Building Code, by International Code Council, Inc. 3. 2013 California Building Code, by California Building Standards Commission 4. 2010 Aluminum Design Manual, by The Aluminum Association This letter certifies that the structural calculations contained within UniRac's "SolarMount Code-Compliant Installation Manual 227.3 are in compliance with the above Codes. If you have any questions on the above, do not hesitate to call. Sincerely, Ai Paul Zacher, SE - President 8137 Sunset Avenue, Suite 120 • Fait Ooks, CA 95628 • 916.961.3960 • 916.961.3965 f • WWW.Plf[.COM J SOLARMOUNT Technical Datasheets ma UNIMAL A rm.;'1 ':'ROUP (OMPANY SolarMount Technical Datasheet Pub 110818-ltd Vl.0 August 2011 SolarMount Module Connection Hardware 1 Bottom Up Module Clip 1 Mid Clamp 2 End Clamp 2 SolarMount Beam Connection Hardware 3 L-Foot 3 SolarMount Beams 4 SolarMount Module Connection Hardware SolarMount Bottom Up Module Clip Part No. 302000C Bottom \Nasher -Bottom Up Clip material: One of the following extruded aluminum Nut (hidden..ge alloys: 6005-T5, 6105-T5, 6061-T6 note$) •Ultimate tensile: 38ksi, Yield: 35 ksi · Finish: Clear Anodized • Bottom Up Clip weight: -0.031 lbs (14g) · Allowable and design loads are valid when components are assembled with SolarMount series beams according to authorized UNIFU\C documents · Assemble with one W'-20 ASTM F593 bolt, one 1,1,1-20 ASTM F594 serrated flange nut, and one 16" flat washer Use anti-seize and tighten to 10 ft-lbs of torque Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third- party test results from an IAS accredited laboratory · Module edge must be fully supported by the beam #A up clip / Beam El * NOTE ON WASHER: Install washer on bolt head side of assembly. DO NOT install washer under serrated flange nut K...I-90. 11.24 Y ;1 A .X· 2 - '·CO Applied Load Average Allowable Safety Design Resistance Direction Ultimate Load Factor,Load Factor, lbs (N)lbs (N)FS lbs (N) 0 Tension, Y+1566 (6967)686 (3052)2.28 1038 (4615)0.662 Transverse, Xi 1128 (5019)329 (1463)3.43 497 (2213)0.441 Sliding, Zt 66 (292)27 (119)2.44 41 (181)0.619 Dimensions specified in inches unless noted e :FUNIRACSOlARMOUNT Technical Datasheets A ·11 1 ·WOU•' ..06'.FAil. SolarMount Mid Clamp Part No. 302101 C, 302101 D, 302103C, 3021040, 302105D, 302106D Mid clamp material: One of the following extruded aluminum alloys: 6005-T5,6105-T5, 6061-T6 Ultimate tensile: 38ksi, Yield: 35 ksi Finish: Clear or Dark Anodized Mid clamp weight: 0.050 lbs (23g) Allowable and design loads are valid when components are assembled according to authorized UNIRAC documents Values represent the allowable and design load capacity of a single mid clamp assembly when used with a SolarMount series beam to retain a module in the direction indicated Assemble mid clamp with one Unirac 14"-20 T-bolt and one 14"-20 ASTM F594 serrated flange nut Use anti-seize and tighten to 10 ft-lbs of torque Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third- party test results from an IAS accredited laboratory Applied Load Average Allowable Safety Design Resistance 1.00 DISTANCE - -Direction Ultimate Load Factor,Load Factor, DEr.VEEN MODULES n .' 11 -.lbs (N)lbs (N)FS lbs (N) 0 Tension, Y+2020 (8987)891 (3963)2.27 1348 (5994)0.667 Transverse, Zi 520 (2313)229 (1017)2.27 346 (1539)0.665 Y .- . ...Sliding, Xi 1194 (5312)490 (2179)2.44 741 (3295)0.620 fX Dimensions specified in inches unless noted SolarMount End Clamp Part No. 302001 C, 302002C, 302002D, 302003C, 3020030,302004C, 302004D, 302005C, 3020050, 302006C, 302006D, 302007D, 302008C, 3020080, 302009C, 302009D, 302010C, 302011 C, 302012C - Bnd Clamp Flange Nut Y A -X • End clamp material: One of the following extruded aluminum alloys: 6005-T5, 6105-T5, 6061-T6 · Ultimate tensile: 38ksi, Yield: 35 ksi • Finish: Clear or Dark Anodized · End clamp weight: varies based on height: -0.058 lbs (269) Allowable and design loads are valid when components are assembled according to authorized UNIRAC documents Values represent the allowable and design load capacity of a single end clamp assembly when used with a SolarMount series beam to retain a module in the direction indicated Assemble with one Unirac 74'-20 T-bolt and one 1/1,1-20 ASTM F594 serrated flange nut Use anti-seize and tighten to 10 ft-lbs of torque Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third- party test results from an IAS accredited laboratory Modules must be installed at least 1.5 in from either end of a beam Me.:PUH d I HEIGHTVults 1-'11 Vi' I '11 MODULE rtito.:d= Dimensions specified-in-inches-unl@anoted Applied Load Average Allowable Safety Design Resistance Direction Ultimate Load Factor,Loads Factor, lbs (N)lbs (N)FS lbs (N) O Tension, Y+1321 (5876)529 (2352)2.50 800 (3557)0.605 Transverse, Zi:63 (279)14 (61)4.58 21 (92)0.330 Sliding, Xi 142 (630)52 (231)2.72 79 (349)0.555 a 1 i 190 U INI I MALSOLARMOUNT Technical Datasheets A I ·]l; 1.201. P COMPAMi SolarMount Beam Connection Hardware SolarMount L-Foot Part No. 304000C, 304000D L-Foot F/ange NuF29;,> Y L-Foot material: One of the following extruded aluminum alloys: 6005- T5, 6105-T5, 6061-T6 Ultimate tensile: 38ksi, Yield: 35 ksi Finish: Clear or Dark Anodized L-Foot weight: varies based on height: -0.215 lbs (98g) Allowable and design loads are valid when components are assembled with SolarMount series beams according to authorized UNIRAC documents For the beam to L-Foot connection: · Assemble with one ASTM F593 %"-16 hex head screw and one ASTM F594 %"serrated flange nut , Use anti-seize and tighten to 30 ft-lbs of torque Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third-party test results from an IAS accredited laboratory NOTE: Loads are given for the L-Foot to beam connection only; be $ X sure to check load limits for standoff, lag screw, or other attachment method 1 1 I lot 3* 9-OT FOR . 16 ARCN,AAE 4 - 2.01 - Dimensions specified in inches unless noted Applied Load Average Safety Design Resistance Direction Ultimate Allowable Load Factor,Load Factor, lbs (N)lbs (N)FS lbs (N) ® Sliding, Zi 1766 (7856)755 (3356)2.34 1141 (5077)0.646 Tension, Y+1859 (8269)707 (3144)2.63 1069 (4755)0.575 Compression, Y- 3258 (14492)1325 (5893)2.46 2004 (8913)0.615 Traverse, Xi 486 (2162)213 (949)2.28 323 (1436)0.664 a e SOLARMOUNT Technical Datasheets ::· UN I RAC SolarMount Beams Part No. 310132C, 310132C-B, 310168C, 310168C-B, 310168D 310208C, 310208C-B, 310240C, 310240C-B, 310240D, 410144M, 410168M, 410204M, 410240M Properties Units SolarMount SolarMount HD Beam Height in 2.5 3.0 Approximate Weight (per linear ft) pif 0.811 1.271 Total Cross Sectional Area ir,2 0.676 1.059 Section Modulus (X-Axis) in3 0.353 0.898 Section Modulus (Y-Axis) ir,3 0.113 0.221 Moment of Inertia (X-Axis) ir,4 0.464 1.450 Moment of Inertia (Y-Axis) in' 0.044 0.267 Radius of Gyration (X-Axis) in 0.289 1.170 Radius of Gyration (Y-Axis) in 0.254 0.502 SLOT FOR T-BOLT OR SLOT FOR T-BOLT ORM" HEX HEAD SCREW 61 rl . 1" HEX HEAD SCREW 2X SLOT FOR -iln rij SLOT FOR -1 BOTTOM CLIP 6_ 2.SOO BOTTOM CLIP \ - 1.728- SLOT FOR - 6" HEX BOLT 1.316301 SLOT FOR - 34" HEX BOLT .750 • • Y Y A A 3.(00 0 \ F 1.385 .387 -M I¥ I b- 1.207 -| -1.875 -- -X -X SolarMount Beam SolarMount HD Beam Dimensions specified in inches unless noted e A.0." iRCUP COA.;PA·,·. 00 t i 1 , :1 fl tk Smart/ 27' we create smart grids™ ; limm I-210+c® SmartMeter SmartSynch's residential smart metering solution features a communications module that is integrated into the GE 1-210+c electricity meter. The I-210+c SmartMeter communicates over an existing cellular network with the SmartSynch Transaction Management System™ (TMS) or other C 12.21 head-end system (such as MV-90) and complies with A NSI (12.19 protocols for data storage and transmission. 23 The 1-210+c SmartMeter is a single-phase electronic watt-hour meter for use in residential and light commercial service locations. The 1-210+c's key features include Time of Use, Demand and Load Profile. Remote Connect/Disconnect, and C12.22/ C 12.21 compatibility. The I-210+c SmartMeter also includes an optional ZigBee® wireless component for in-premise communications and an optional Badger ORION® wireless component for gas and water reads. Functions & Features SmartSynch, Inc. 4400 Old Canton Road Jackson, Mississippi 39211 1-888-362-1780 www.smarlsynch.com Wireless Communications • GPRS • ZigBee® • Badger ORION® Advanced Metering Functionality • Remote Disconnect/Reconnect · Flexible Two-Way Data Retrieval • Scheduled & On-Demand Reads • Interval Reads (5, 15, 30, 60 minutes) • Real-Time Interval Reads • Automated Register, Self-Read & TOU • Demand Resets • Real-Time Meter Event & Alarm Retrieval • Real-Time Power Outage & Restoration • Service Diagnostics & Tamper Detection • Tilt Detection • Meter Clock Synchronization · SmartMeter Status Display • Automated Meter Registration • Secure & Encrypted Data Transmissions • Bi-Directional Metering • Over-The-Air SmartMeter Module Firmware Upgrade Supported Meter Forms • Class 20: 3S, 4S • Class 100: 1 S • Class 200: 2S, 125,25S · Class 320: 2S • See back page for Supported Forms with Remote Disconnect Hardware Components · Remote Disconnect/Reconnect · Radio Control Module Board (RCM) • Capacitor Storage Bank (CSB) • GSM/GPRS Modem • Zig Bee Transceiver • Badger ORION Receiver • Internal Antenna Operating Ranges Temperature • Operating: [-40°C, +85°C] • Transmission (GPRS): [-40°C, +85°C] Humidity • 0% to 95% non-condensing Accuracy · Meets ANSI 12.20 for accuracy class 0.5% Regulatory & Industry Specifications • FCC Part 15 Class B · ANSI C37.90.1 - 1989: (SWC) • ANSI C 12.20 (Class 0.5) - 1998 • PTCRB Certified · Network Carrier Certified • Measurement Canada Certified U 1 'er ·4-' -t:€,-tifir:4#IjaMJambj,tr,2-*--„-*-,1.11.:-7+47 - - .. -*14 a . . 1 1 , ..Er Hardware Specifications ©Aynch® Hardware Component Radio Control Module Board (RCM) Capacitor Storage Bank (CSB) GSM/GPRS Modem ZigBee Transceiver Badger ORION Receiver Internal Antenna Description 32-bit ARM processor, 256K RAM. 512K flash Supplies peak power for data transmissions and all functions during power outages - no batteries required GSM modem communicates with head-end using GPRS and SMS services Wireless component for in-premise iwo-way communications Wireless component for receiving gas and water reads Flexible dual frequency GSM antenna forthe modem Temperature Ranges Operating: [-40°C, +85°C] Transmission (wireless): [-40°C, +85°C] Supported Meter Forms Class 20: 3S, 4S Class 100: 1 S Class 200: 2S. 12S, 25S Class 320: 2S With Disconnect. Class 100: 1 S Class 200: 2S, 12S, 25S Class 320: 25S Humidity Range 0% to 95% non-condensing Accuracy Meets ANSI 12.20 for accuracy class 0.5% Regulatory & Industry Certifications FCC Part 15 Class B ANSI C37.90.1 - 1989: Surge Withstand Capability (SWC) ANSI C 12.20 (Class 0.5) - 1998 PTCRB Certified Measurement Canada Certified Network Carrier Certified Input/Output Signal or Interface Definition/Values Module Power Input Voltage 120 - 240 VAC Meter Serial Interface 3.3V / TTL compatible asynchronous integration The SmartMeter module is a fully integrated, under-the-cover option inside the I-210+c meter. The I-210+c SmartMeter is shipped as one complete unit. ready for field deployment. Version and Compatibility Information 1-210+c Meter Hardware:Supported meter forms, classes, and types, equipped with battery I-210+c Meter Firmware:Latest fully supported SmartModule:I-210+c GPRS SmartMeter Module SmartSynch TMS:Version 6.0 or higher About SmarISynch: Headquartered in Jackson, Miss., SmartSynch has been developing successful Smart Grid intelligence solutions for the utility industry since 2000. The company's clean-tech innovations in the two-way delivery of real-time energy usage data over cellular networks (AT&T. Rogers. etc.). in lieu of private network build-outs, have to date simplified SmartMeter deployments for 150 major North American utilities, while enabling green-energy initiatives and delivering significantly higher Returns on Resources. Unlike proprietary, closed-architecture solutions, SmartSynch's SmartMeters represent future-proof investments in technology. The standards-based IP connectivity enabled in every SmartMeter deployed makes them adaptable and remotely upgradable to support today's sensor and communications needs, as well as tomorrow's opportunities, better than any alternative. Copyright © 2011, SmartSynch Inc., all rights reserved. . 37 21C j. 4 + . I I SCREW: E1276 CAT. NO.: MASS:.052 LBS. · SURFACE AREA: 2.738 IN2 STUFFER SHT: FORM 12 MATERIAL:COPPER, X0C7309 PLATING: SEE CHART MARKING: 0 GBL-4DB, 4-14, CU, DB @ € CELL: ABM TOLERANCES-UNLESS OTHERWISE SPECIFIED DWG. NO. 2 PL DEC. *.015 TRUE C.L *.015 3 PL DEC. f.010 ANGLES *l G0977 DRAWN BY: CLH SCALE: 3:1 SHEET 1 OF 1 DATE: 7/27/2007 SIZE: A REV.DESCRIPTION CORP. /- 1/4-28 UNF- 28 V.040 MAX X 45° 1 11 / 1 -0.218 THRU Cat #: GBL-4DB GBL-4DBT .375*.015 [9.53 *.38] .213 • [5.41] .470 ( 11 1 1 [11.94] OPENING MUST-nSLIP A 0.250 PIN Y E1276 SCALE 1:1 .190 [4.84] 11 1 11 -7-7 .825 .185& .005[20.96] --1 --- [4.70*.13] 1 1 1/1 - -tr-3- lili' 111 • 1.150 PART NUMBER PLATING .MARKING[29.21] G0977A00B BRIGHT DIP 0 GBL-4DB,4-14, CU, DB @ G G0977A00T EL-TIN 0GBI--4DBT,4-14, CU, DB @G THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS PROPRIETARY TO ILSCO AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN CONSENT P .