Loading...
HomeMy WebLinkAbout3220 S Fairview St - PlanNOTES RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK G-001 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R NOTES 1. EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUS BAR OR CONDUCTOR 2. EQUIPMENT. INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AC PHOTOVOLTAIC MODULES, SOURCE-CIRCUIT COMBINERS, AND CHARGE CONTROLLERS INTENDED FOR USE IN PHOTOVOLTAIC POWER SYSTEMS SHALL BE IDENTIFIED AND LISTED FOR THE APPLICATION. (CEC 690.4(B)) 3. ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND NON ROOF SWITCHES. ROOF SWITCHES TO BE NEMA 4 RATED. 4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH CEC ARTICLE 250. 5.PROTECTION DEVICES FOR PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS ALSO CONNECTED TO SOURCES HAVING SIGNIFICANTLY HIGHER CURRENT AVAILABILITY (E.G., PARALLEL STRINGS OF MODULES, UTILITY POWER), SHALL BE PROTECTED AT THE SOURCE FROM OVERCURRENT. [CEC 690.9(A)] 6.PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION THAT CONTROLS SPECIFIC CONDUCTORS. [ CEC 690.12] 7.THE UTILITY INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL REMAIN IN THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED. [CEC 705.41] 8.ALL CONDUCTOR EXPOSED TO WEATHER SHALL BE LISTED & IDENTIFIED FOR USE IN DIRECT SUNLIGHT. [ CEC 310.10(D)(1)] 9.THE MODULE CONDUCTORS MUST BE TYPE USE-2 OR LISTED FOR PHOTOVOLTAIC (PV) WIRE. (CEC 690.31(C)) 10.ALL CONDUCTORS SHALL BE MARKED ON EACH END FOR UNIQUE IDENTIFICATION. 11.AN INSULATED GROUNDED CONDUCTOR OF 6 AWG OR SMALLER SHALL BE IDENTIFIED AS A CONTINUOUS WHITE FINISH. [CEC 200.6] 12.THE OUTPUT OF AN INTERCONNECTED ELECTRICAL POWER SOURCE SHALL BE PERMITTED TO BE CONNECTED TO THE LOAD SIDE. INTERCONNECTING PROVISIONS FOR OTHER POWER SOURCES SHALL COMPLY WITH 705.12(B)(1) THROUGH 705.12(B)(5) 13. EACH SOURCE INTERCONNECTION OF ONE OR MORE POWER SOURCES INSTALLED IN ONE SYSTEM SHALL BE MADE AT A DEDICATED CIRCUIT BREAKER OR FUSIBLE DISCONNECTING MEANS [CEC 705.12(B)(1)] 14.THE SUM OF THE AMPERE RATING OF THE OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO THE BUSBAR OR CONDUCTOR SHALL NOT EXCEED 120% OF THE RATING OF BUSBAR OR CONDUCTOR.[CEC 705.12(B)(3)(2)] 15.A CONNECTION AT EITHER END, BUT NOT BOTH ENDS, OF A CENTER-FED PANEL BOARD IN DWELLINGS SHALL BE PERMITTED WHERE THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR DOES NOT EXCEED 120 PERCENT OF THE CURRENT RATING OF THE BUSBAR. [CEC 705.12(B)(3)(2)] 16.EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUS BAR OR CONDUCTOR SHALL BE MARKED TO INDICATE THE PRESENCE OF ALL SOURCES. [ CEC 705.12(B)(3)] 17.CIRCUIT BREAKER, IF BACKFED, SHALL BE SUITABLE FOR SUCH OPERATION. [ CEC 705.12(B)(4)] 18.TO MINIMIZE OVERHEATING OF THE BUSBAR IN PANELBOARD, THE PANELBOARD MAIN CIRCUIT BREAKER AND THE PV POWER SOURCE CIRCUIT BREAKER SHALL BE PHYSICALLY LOCATED AT THE OPPOSITE END OF THE BUSBAR. 19. ALL THE CEC REQUIRED WARNING SIGNS, MARKINGS, AND LABELS SHALL BE POSTED ON EQUIPMENT AND DISCONNECTS PRIOR TO ANY INSPECTIONS TO BE PERFORMED BY THE BUILDING DEPARTMENT INSPECTOR. 20.WHERE PV SYSTEM DC CIRCUIT'S RUN INSIDE A BUILDING, THEY SHALL BE CONTAINED IN METAL RACEWAYS TYPE MC METAL CLAD CABLE OR METAL ENCLOSURES FROM POINT OF PENETRATION OF THE SURFACE OF THE BUILDING TO THE FIRST READILY ACCESSIBLE DISCONNECTING MEANS. [ CEC 690.31(G)] 21.FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR CONNECTOR THAT ARE IS IN ACCORDANCE WITH CEC 110.14 22.CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND OPERATING AT OVER 30V DC OR 15V AC SHALL REQUIRE TOOL TO OPEN AND MARKED "DO NOT DISCONNECT UNDER LOAD" OR "NOT FOR CURRENT INTERRUPTING". [CEC 690.33(C) & (E)(2)] 23. EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 6AWG SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY A RACEWAY OR CABLE ARMOR. [CEC 690.46 & 250.120(C)] 24. AN EQUIPMENT GROUNDING CONDUCTOR SHALL NOT BE SMALLER THAN 14 AWG. [ CEC 690.45] 25. FINE STRANDED CABLES USED FOR BATTERY TERMINALS, DEVICES, AND CONNECTIONS REQUIRE LUGS AND TERMINALS IS IN ACCORDANCE WITH CEC 110.14 26.GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE INSTALLED IN ONE CONTINUOUS LENGTH WITHOUT A SPLICE OR JOINT. IF NECESSARY,SPLICES OR CONNECTIONS SHALL BE MADE AS PERMITTED. (CEC 250.64 C) 27.ALL SMOKE ALARMS, CARBON MONOXIDE ALARMS AND AUDIBLE NOTIFICATION DEVICES SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL 217 AND UL 2034. THEY WILL BE INSTALLED IN ACCORDANCE WITH NFPA 72 AND NFPA 720. 28.SMOKE ALARMS AND CARBON MONOXIDE ALARMS WILL BE RETROFITTED INTO THE EXISTING DWELLING. THESE SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS,OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE.THESE ALARMS MAY BE SOLELY BATTERY OPERATED IF THE PHOTOVOLTAIC PROJECT DOES NOT INVOLVE THE REMOVAL OF INTERIOR WALL AND CEILING FINISHES INSIDE THE HOME, OTHERWISE, THE ALARMS MUST BE HARD WIRED AND INTERCONNECTED. GROUND FAULT PROTECTION 1.PHOTOVOLTAIC INVERTERS SHALL BE EQUIPPED WITH DC GROUND FAULT PROTECTION. INVERTERS ARE ALSO EQUIPPED WITH ANTI-ISLANDING CIRCUITRY. DISCONNECTING MEANS 1.MEANS SHALL BE PROVIDED TO ISOLATE EACH SOURCE CIRCUIT FROM THE SYSTEM. 2.WHERE A CIRCUIT GROUNDING CONNECTION IS NOT DESIGNED TO BE AUTOMATICALLY INTERRUPTED AS PART OF THE GROUND-FAULT PROTECTION, A SWITCH OR CIRCUIT BREAKER USED AS A DISCONNECTING MEANS SHALL NOT HAVE A POLE ON THE GROUNDED CONDUCTOR. 3.THE GROUNDED CONDUCTOR MAY HAVE A BOLTED OR TERMINAL DISCONNECTING MEANS TO ALLOW MAINTENANCE OR TROUBLESHOOTING BY QUALIFIED PERSONNEL. 4.EQUIPMENT SUCH AS PHOTOVOLTAIC SOURCE CIRCUITS, OVER CURRENT DEVICES, AND BLOCKING DIODES SHALL BE PERMITTED ON THE PHOTOVOLTAIC SIDE OF THE PHOTOVOLTAIC DISCONNECTING MEANS. 5.MEANS SHALL BE PROVIDED TO DISCONNECT INVERTERS FROM ALL UNGROUNDED CONDUCTORS OF ALL SOURCES. IF THE EQUIPMENT IS ENERGIZED FROM MORE THAN ONE SOURCE, THE DISCONNECTING MEANS SHALL BE GROUPED AND IDENTIFIED. 6.A SINGLE DISCONNECTING MEANS SHALL BE PERMITTED FOR THE COMBINED OUTPUT OF ONE OR MORE INVERTERS IN A GRID INTERACTIVE SYSTEM. 7.DISCONNECTING MEANS SHALL BE PROVIDED TO DISCONNECT A FUSE FROM ALL SOURCES OF SUPPLY IF THE FUSE IS ENERGIZED FROM BOTH DIRECTIONS AND IS ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS. SUCH A FUSE IN A PHOTOVOLTAIC SOURCE CIRCUIT SHALL BE CAPABLE OF BEING DISCONNECTED INDEPENDENTLY OF FUSES IN OTHER PHOTOVOLTAIC SOURCE CIRCUITS. DC CONDUCTORS POSITIVE(UNGROUNDED)RED NEGATIVE(UNGROUNDED)BLACK 120/208V OR 240V AC CONDUCTORS PHASE L1 BLACK PHASE L2 RED (SEE NOTE) PHASE L3 BLUE 480/277V AC CONDUCTORS PHASE L1 BROWN PHASE L2 ORANGE PHASE L3 YELLOW NEUTRAL WHITE OR GREY GROUND GREEN OR BARE Cu NOTE:THREE PHASE HIGH LEG MUST BE IN ORANGE COLOR PER NFPA 70. GENERAL CONDUCTOR INSULATION KEY Signed 4/04/2025 COVER PAGE NEW PHOTOVOLTAIC SYSTEM 223.59 KW DC & 187.5 KW AC 3220 S FAIRVIEW ST, SANTA ANA, CA 92704, USA GENERAL NOTES VICINITY MAP SATELLITE VIEW SHEET INDEX COVER PAGET-001 G-001 A-101 SITE PLAN RESOURCE DOCUMENTS 1.1.1 PROJECT NOTES: 1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE CALIFORNIA ELECTRIC CODE (CEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVING JURISDICTION’S (AHJ) APPLICABLE CODES. 1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION 1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS ACCORDANCE WITH CEC 690.41(B) 1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY CEC 690.4: PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY 1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED ACCORDING TO CEC 690.7. 1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS, AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [CEC 110.3]. 1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE CEC AND AHJ. 1.2.1 SCOPE OF WORK: 1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT 1.2.3 INSTALLING CONTRACTOR IS RESPONSIBLE FOR FOLLOWING EQUIPMENT MANUFACTURER'S INSTALLATION AND COMMISSIONING MEANS AND METHODS. 1.3.1 WORK INCLUDES: 1.3.2 PV RACKING SYSTEM INSTALLATION - UNIRAC RMDT RACKING 1.3.3 PV MODULE AND INVERTER INSTALLATION - HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES / SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTERS 1.3.4 PV EQUIPMENT ROOF MOUNT 1.3.5 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX 1.3.6 PV LOAD CENTERS (IF INCLUDED) 1.3.7 PV METERING/MONITORING (IF INCLUDED) 1.3.8 PV DISCONNECTS 1.3.9 PV GROUNDING ELECTRODE & BONDING TO (E) GEC 1.3.10 PV FINAL COMMISSIONING 1.3.11 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV 1.3.12 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE PROJECT INFORMATION PROJECT NAME NAME: ELECTRICAL PLAN ELECTRICAL CALCULATIONS A-102 E-602 R-001-R-006 WAXIE SANTA ANA NOTES PLACARDE-604 CONTRACTOR INFORMATION: CONTRACTOR NAME: PALOMAR SOLAR LTD PROJECT MANAGER: CURTIS WILLIAMSON EMAIL: support@palomarsolar.com RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK T-001 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R WARNING LABELSE-603 ELECTRICAL LINE DIAGRAME-601 SCOPE OF WORK SYSTEM SIZE : STC : 514 X 435W= 223.59 kW DC PTC : 514 X 408W = 209.71 kW DC CEC AC RATING: 204.46 kW AC AC SIZE: 187.5 kW AC (514) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (03) SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTERS AUTHORITIES HAVING JURISDICTION BUILDING : CITY OF SANTA ANA UTILITY : SCE ATTACHMENT TYPE: DESIGN SPECIFICATION OCCUPANCY - GROUP B CONSTRUCTION - TYPE 2 ZONING - CITY OF SANTA ANA GROUND SNOW LOAD - 0 PSF WIND EXPOSURE - B WIND SPEED - 95 MPH RISK CATEGORY - II BUILDING HEIGHT -40 FT APPLICABLE CODES & STANDARDS BUILDING: CBC 2022, CMC 2022 CPC 2022, CEBC 2022 ELECTRICAL: CEC 2022 FIRE: CFC 2022 MSP UPGRADE: NO UNIRAC RMDT RACKING ATTACHMENT PLANA-103-A103.1 Signed 4/04/2025 S-1-S-2 TKJ STRUCTURAL DRAWINGS EXISTING PV SYSTEM AT 3220 S FAIRVIEW ST. HAS BEEN REMOVED UNDER DEMO PERMITS 101122489/20185150 Bldg #101123299 & Elect #20185611 APPROVALS: PLNG - C. Santana BLDG - G. Huang PUBLIC WORKS - Y. Soto ELECT - M. Smith 625'-0" 21 9 ' - 5 " 625'-6" 22 2 ' - 1 " 496'-5" 22 ' - 0 " 30'-11" 87 ' - 6 " 24'-4 " 21'-0" 9' - 8 " 77'-1" 35 ' - 9 " 148'-9"50 ' - 2 " 198'-7" 39'-11" 34'- 1 0 " 12 3 ' - 2 " CB MS G AC D SP 61'-7" 66 ' - 1 0 " 36'-0" 3' - 1 1 " IN V IN V IN V T MS G AC D SP T RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK A-101 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R SITE PLAN 1 SITE PLAN ENLARGED VIEW (E) VISIBLE LOCKABLE LABELED AND FUSED AC DISCONNECT (INSIDE MAIN ELECTRICAL ROOM) LEGEND - VENT, ATTIC FAN (ROOF OBSTRUCTION) - PROPERTY LINE - FIRE SETBACK - SKYLIGHT (ROOF OBSTRUCTION) W ALTON AVE DRIVEWAY S F A I R V I E W S T (N) (50) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (32) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES DRIVEWAY DR I V E W A Y (E) MAIN ELECTRICAL ROOM (E) MAIN BUILDING (E) DETATCHED STRUCTURE 6FT FIRE SETBACKS (E) GATE (N) SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTER (ON ROOF) SEE ENLARGED VIEW (2x) (N) SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTERS (ON ROOF) (TYP) (E) PARKING LOT (N) AC COMBINER PANEL (ON ROOF) (E) MAIN SWITCH GEAR (INSIDE MAIN ELECTRICAL ROOM) (E) SUBPANEL (INSIDE MAIN ELECTRICAL ROOM) - FENCE LINE (E) FENCE N S EW (E) PROPERTY LINE SCALE:1/40" = 1'-0" (E) TRANSFORMER (INSIDE MAIN ELECTRICAL ROOM) NOTE : THE SMA INVERTERS LOCATED NEAREST TO THE ARRAY TO AVOID RSD PER UL 3741. (N) (48) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (30) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (40) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (58) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (32) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (50) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (48) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (48) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (48) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES (N) (30) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES Signed 4/04/2025 45 ' - 4" 25'-1"25'-1"16'-11" 39 ' - 8" 33'-3" 2 2 2 2 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1 1 13 1 1 1 1 1 1 1 1 1 13 2 1 1 1 1 1 1 1 3 21 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 3 2 2 2 2 2 2 3 1 2 2 1 2 22111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 3 2 2 2 2 1 1 2 2 2 3 3 1 3 3 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 2 1 2 2 1 1 11 1 2 2 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1 3 1 3 31 3 3 3 3 1 2 1 1 2 2 2 2 2 2 22 2 1 1 1 1 1 1 1 1 3 31 3 2 2 1 2 2 2 3 1 1 2 1 3 1 2 1 1 2 2 2 2 1 2 2 2 1 2 2 1 3 1 1 1 1 2 2 2 3 3 1 2 1 2 23 3 45 ' - 4" 45 ' - 4" 41'-5" 3 2 1 2 2 2 2221 1 1 1 11 11 2111332 2 1 1 1 13 1 2 2211331 1 1 1 13 11 2 2 2 1 1 1 1 1 1 1 1 1 1 1 22111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 3 2 2 2 2 2 1 3 2 2 2 39 ' - 8" 33'-3" 39 ' - 8" MODULE RMDT RIDGE BAY RMDT VALLEY BAY ~ 8.6" BOTTOM OF MODULE TO BOTTOM OF ADJACENT MODULE (TYP) 1.08" BOTTOM OF MODULE TO BOTTOM OF ADJACENT MODULE (TYP) ~ 7.9" EDGE OF BAY TO BOTTOM OF MODULE (TYP) FRONT VIEW NOT TO SCALE 5. 4 6 " 5º RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK A-103 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R ATTACHMENT PLAN 1 ATTACHMENT PLAN SCALE:1/8" = 1'-0" ATTACHMENT DETAILS ROOF 1 ARRAY 1 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG LEGEND 1 2 -STANDARD CORNER BAY WITH CMU BLOCK COUNT 3 -SUPPLEMENTAL BAY WITH CMU BLOCK COUNT -SUPPLEMENTAL BAY WITH CMU BLOCK COUNT ROOF 1 ARRAY 2 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF 1 ARRAY 3 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF 1 ARRAY 4 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF 1 ARRAY 5 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF 1 ARRAY 6 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG DESIGN CRITERIA NUMBER OF PANELS IN ARRAY = 514 MODULE TYPE = HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES ATTACHMENT= UNIRAC RMDT RACKING ROOF AREA 1 - ARRAY 1 AVERAGE PSF 4.91 PSF TOTAL NUMBER OF MODULES 50 TOTAL KW 21.75 KW TOTAL AREA 1182 SQFT TOTAL WEIGHT ON ROOF 5805 LBS RACKING WEIGHT 462 LBS MODULE WEIGHT 2335 LBS BALLAST WEIGHT 3008 LBS ROOF AREA 1 - ARRAY 2 AVERAGE PSF 4.64 PSF TOTAL NUMBER OF MODULES 50 TOTAL KW 21.75 KW TOTAL AREA 1182 SQFT TOTAL WEIGHT ON ROOF 5485 LBS RACKING WEIGHT 462 LBS MODULE WEIGHT 2335 LBS BALLAST WEIGHT 2688 LBS ROOF AREA 1 - ARRAY 3 AVERAGE PSF 4.92 PSF TOTAL NUMBER OF MODULES 58 TOTAL KW 25.23 KW TOTAL AREA 1367 SQFT TOTAL WEIGHT ON ROOF 6730 LBS RACKING WEIGHT 534 LBS MODULE WEIGHT 2709 LBS BALLAST WEIGHT 3488 LBS ROOF AREA 1 - ARRAY 4 AVERAGE PSF 5.19 PSF TOTAL NUMBER OF MODULES 48 TOTAL KW 20.88 KW TOTAL AREA 1139 SQFT TOTAL WEIGHT ON ROOF 5912 LBS RACKING WEIGHT 438 LBS MODULE WEIGHT 2242 LBS BALLAST WEIGHT 3232 LBS ROOF AREA 1 - ARRAY 5 AVERAGE PSF 5.19 PSF TOTAL NUMBER OF MODULES 48 TOTAL KW 20.88 KW TOTAL AREA 1139 SQFT TOTAL WEIGHT ON ROOF 5912 LBS RACKING WEIGHT 438 LBS MODULE WEIGHT 2242 LBS BALLAST WEIGHT 3232 LBS ROOF AREA 1 - ARRAY 6 AVERAGE PSF 5.72 PSF TOTAL NUMBER OF MODULES 32 TOTAL KW 13.92 KW TOTAL AREA 768 SQFT TOTAL WEIGHT ON ROOF 4395 LBS RACKING WEIGHT 309 LBS MODULE WEIGHT 1494 LBS BALLAST WEIGHT 2592 LBS Signed 4/04/2025 25'-1" 45 ' - 4" 2 2 2 2 2 2 2 2 2 2 2 1 1 2 1 2 2 1 1 11 1 2 2 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 3 3 1 3 1 3 31 3 3 3 3 1 2 1 1 2 2 2 12 25'-1" 45 ' - 4" 2 2 2 2 2 2 2 2 2 2 2 1 1 2 1 2 2 1 1 11 1 2 2 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 3 3 1 3 1 3 31 3 3 3 3 1 2 1 1 2 2 2 12 16'-11" 45 ' - 4" 2 2 1 2 2 2 3 1 1 2 1 3 1 2 1 1 2 2 2 2 1 2 2 2 1 2 2 1 3 1 1 1 1 2 2 2 3 3 1 2 1 2 23 3 2 2 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 2 2 2 2 2 2 2 2 3 3 3 3 25'-1" 28 ' - 4" 2 2 1 1 1 2 2 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 111 1 1 1 2 2 2 2 2 2 1 3 3 28 ' - 4"1 1 1 1 2 2 1 1 3 3 2 1 2 2 2 2 2 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 2 1 33'-3" 1 1 1 1 1 1 1 25'-1" 28 ' - 4" MODULE RMDT RIDGE BAY RMDT VALLEY BAY ~ 8.6" BOTTOM OF MODULE TO BOTTOM OF ADJACENT MODULE (TYP) 1.08" BOTTOM OF MODULE TO BOTTOM OF ADJACENT MODULE (TYP) ~ 7.9" EDGE OF BAY TO BOTTOM OF MODULE (TYP) FRONT VIEW NOT TO SCALE 5. 4 6 " 5º RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK A-103.1 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R ATTACHMENT PLAN 1 ATTACHMENT PLAN SCALE:1/8" = 1'-0" ATTACHMENT DETAILS ROOF 1 ARRAY 7 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG LEGEND 1 2 -STANDARD CORNER BAY WITH CMU BLOCK COUNT 3 -SUPPLEMENTAL BAY WITH CMU BLOCK COUNT -SUPPLEMENTAL BAY WITH CMU BLOCK COUNT ROOF 1 ARRAY 8 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF 1 ARRAY 9 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF 1 ARRAY 10 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF 1 ARRAY 11 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF 1 ARRAY 12 TILT- 5 DEG AZIMUTH - 90 DEG & 270 DEG ROOF AREA 1 - ARRAY 7 AVERAGE PSF 5.72 PSF TOTAL NUMBER OF MODULES 48 TOTAL KW 20.88 KW TOTAL AREA 1139 SQFT TOTAL WEIGHT ON ROOF 5976 LBS RACKING WEIGHT 438 LBS MODULE WEIGHT 2242 LBS BALLAST WEIGHT 3296 LBS ROOF AREA 1 - ARRAY 8 AVERAGE PSF 5.25 PSF TOTAL NUMBER OF MODULES 48 TOTAL KW 20.88 KW TOTAL AREA 1139 SQFT TOTAL WEIGHT ON ROOF 5976 LBS RACKING WEIGHT 438 LBS MODULE WEIGHT 2242 LBS BALLAST WEIGHT 3296 LBS ROOF AREA 1 - ARRAY 9 AVERAGE PSF 5.72 PSF TOTAL NUMBER OF MODULES 32 TOTAL KW 13.92 KW TOTAL AREA 768 SQFT TOTAL WEIGHT ON ROOF 4395 LBS RACKING WEIGHT 309 LBS MODULE WEIGHT 1494 LBS BALLAST WEIGHT 2592 LBS ROOF AREA 1 - ARRAY 10 AVERAGE PSF 5.17 PSF TOTAL NUMBER OF MODULES 30 TOTAL KW 13.05 KW TOTAL AREA 712 SQFT TOTAL WEIGHT ON ROOF 3677 LBS RACKING WEIGHT 292 LBS MODULE WEIGHT 1401 LBS BALLAST WEIGHT 1984 LBS ROOF AREA 1 - ARRAY 12 AVERAGE PSF 4.76 PSF TOTAL NUMBER OF MODULES 40 TOTAL KW 17.40 KW TOTAL AREA 943 SQFT TOTAL WEIGHT ON ROOF 4487 LBS RACKING WEIGHT 379 LBS MODULE WEIGHT 1868 LBS BALLAST WEIGHT 2240 LBS ROOF AREA 1 - ARRAY 11 AVERAGE PSF 4.94 PSF TOTAL NUMBER OF MODULES 30 TOTAL KW 13.05 KW TOTAL AREA 712 SQFT TOTAL WEIGHT ON ROOF 3517 LBS RACKING WEIGHT 292 LBS MODULE WEIGHT 1401 LBS BALLAST WEIGHT 1824 LBS Signed 4/04/2025 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. SPECIFIC NOTES AND DETAILS ON THE STRUCTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN OR NOTED IN ANY PART OF THE WORK THE DETAILS FOR OTHER SIMILAR WORK SHALL APPLY. DETAILS IDENTIFIED AS TYPICAL, SHALL APPLY IN ESTIMATING AND CONSTRUCTION TO EVERY LIKE CONDITION WHETHER OR NOT THE REFERENCE IS REPEATED. THE STRUCTURAL DRAWINGS SHALL NOT BE SCALED. COORDINATE DIMENSIONS WITH ARCHITECTURAL DRAWINGS. COORDINATE ELEVATIONS, SLOPES, AND DRAINAGE REQUIREMENTS WITH THE ARCHITECTURAL DRAWINGS. STANDARDS REFERENCED ON THE STRUCTURAL DRAWINGS REFER TO THE EDITION APPLICABLE UNDER THE CURRENT BUILDING CODE. THE RESPONSIBILITY FOR THE REVIEW AND COORDINATION OF DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF RELATED CONSTRUCTION SHALL BEAR ON THE CONTRACTOR. DISCREPANCIES THAT EXIST SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN A TIMELY MANNER, PRIOR TO THE START OF RELATED CONSTRUCTION. WORK PERFORMED IN CONFLICT WITH THE STRUCTURAL DRAWINGS OR APPLICABLE BUILDING CODE REQUIREMENTS SHALL BE CORRECTED AT THE EXPENSE OF THE CONTRACTOR. DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS SHALL BE VERIFIED BEFORE STARTING RELATED WORK AND THE ENGINEER NOTIFIED OF DISCREPANCIES IN A TIMELY MANNER. SITE CONDITIONS THAT ARE NOT REFLECTED ON THE STRUCTURAL DRAWINGS OR THAT DEVIATE FROM THE MAXIMUM OR MINIMUM DIMENSIONS INDICATED SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN A TIMELY MANNER. SUCH CONDITIONS MAY INCLUDE CONFLICT IN GRADES, ADVERSE SOIL CONDITIONS, GROUND WATER PRESENT, DEEPENED FOOTINGS, UNCOVERED AND UNEXPECTED UTILITY LINES, ETC. MATERIALS AND WORKMANSHIP SHALL CONFORM TO REQUIREMENTS OF APPLICABLE REGULATIONS AND THE BUILDING CODE AS AMENDED AND ADOPTED BY THE BUILDING OFFICIAL. LOADS TO THE BUILDING EXCEEDING THE LOADS INDICATED ON THE PLANS, OR ANY LOADS EXCEEDING 400 POUNDS THAT ARE NOT INDICATED ON THE STRUCTURAL DRAWINGS SHALL BE REPORTED TO THE ENGINEER. GENERAL 1. 2. 3. 4. 5. THE STRUCTURAL DESIGN HAS BEEN PERFORMED IN ACCORDANCE WITH THE 2022 CALIFORNIA BUILDING CODE (CBC) DESIGN LOADS (LIVE LOADS MAY BE REDUCED IN ACCORDANCE WITH THE BUILDING CODE) LL ROOF 20 psf SEISMIC DESIGN DATA : ASCE 7-16 RISK CATEGORY II SEISMIC IMPORTANCE FACTOR Ie 1.0 MAPPED SPECTRAL ACCELERATION SS 1.303 g MAPPED SPECTRAL ACCELERATION S1 0.468 g DESIGN SPECTRAL ACCELERATION SDS 1.042 g SITE CLASS D (DEFAULT) SEISMIC DESIGN CATEGORY D ANALYSIS PROCEDURE USED NONSTRUCTURAL COMPONENTS COMPONENT SEISMIC DESIGN DATA COMPONENT ap Rp SOLAR PV MODULES 1.0 1.5 OTHER ELECTRICAL COMPONENTS 2.5 6.0 WIND DESIGN DATA : ASCE 7-16 BASIC WIND SPEED V 95 mph EXPOSURE CATEGORY B ENCLOSURE CATEGORY ENCLOSED GUST & INTERNAL PRESSURE COEFF GCpi 0.18 DIRECTIONALITY FACTOR Kd 0.85 TOPOGRAPHIC FACTOR Kzt 1.00 BASIS OF DESIGN 1. 2. 3. THE STRUCTURAL DRAWINGS SHOW THE REQUIREMENTS FOR THE COMPLETED STRUCTURE ONLY. TEMPORARY WORKS REQUIRED TO COMPLETE THE CONSTRUCTION PROCESS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE DESIGN OR FIELD VERIFICATION OF TEMPORARY AND ANCILLARY WORK. THE RESPONSIBILITY FOR SAFETY IN AND AROUND THE JOBSITE SHALL BEAR ON THE CONTRACTOR. PROPER AND SAFE METHODS OF CONSTRUCTION SHALL BE EMPLOYED AT ALL TIMES INCLUDING THE STABILIZING OF INCOMPLETE STRUCTURES, FORMWORK, SHORING, RESHORING, FALSEWORK, PLATFORMS, SCAFFOLDING, BARRIERS, WALKWAYS, ETC, AND INCLUDING CONTROL OF THE INTENSITY, DURATION, AND LOCATION OF CONSTRUCTION LOADS. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON A STRUCTURE. LOADS SHALL NOT EXCEED THE DESIGN LIVE LOAD INDICATED. WHERE THE STRUCTURE HAS NOT ATTAINED FINAL DESIGN STRENGTH, ADEQUATE SHORING AND OR BRACING SHALL BE INSTALLED. TEMPORARY WORK AND SITE SAFETY 1.DUE TO THE SCOPE AND NATURE OF THIS PROJECT, STRUCTURAL OBSERVATION IS NOT REQUIRED. STRUCTURAL OBSERVATIONS 1. A. GENERAL: DUE TO THE SCOPE AND NATURE OF THIS PROJECT, SPECIAL INSPECTION IS NOT REQUIRED. SPECIAL INSPECTION PROGRAM 1. 2. 3. 4. 5. A. B. 6. A. B. C. D. 7. A. B. C. 8. 9. A. B. C. 10. STRUT CHANNELS AND FITTINGS SPECIFIED ON CONTRACT DRAWINGS SHALL BE MANUFACTURED BY UNISTRUT CORPORATION. SUBSTITUTIONS FOR PRODUCTS OF ALTERNATIVE MANUFACTURERS SHALL BE APPROVED BY THE ENGINEER. STRUT CHANNEL AND FITTING DESIGNATIONS ON CONTRACT DRAWINGS CORRESPOND TO PRODUCT DESIGNATIONS IN THE UNISTRUT GENERAL ENGINEERING CATALOG. WHERE SUBSTITUTIONS OF STRUT CHANNELS OR FITTINGS ARE REQUESTED, THE CONTRACTOR SHALL PROVIDE DOCUMENTATION DEMONSTRATING THAT THE PROPOSED STRUT CHANNEL OR COMPONENT MEETS OR EXCEEDS THE STRUCTURAL PROPERTIES AND ALLOWABLE DESIGN VALUES OF THE SPECIFIED STRUT CHANNEL OR COMPONENT. ALL STRUT CHANNELS AND COMPONENTS MUST BE SUPPLIED BY A SINGLE MANUFACTURER. CHANNELS AND COMPONENTS SHALL MEET THE REQUIREMENTS OF THE AMERICAN IRON AND STEEL INSTITUTE (AISI) SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS, 2007 EDITION. ALL CHANNEL MEMBERS SHALL BE FABRICATED FROM STRUCTURAL GRADE STEEL CONFORMING TO ONE OF THE FOLLOWING ASTM SPECIFICATIONS: A 1011 SS GR 33 A 653 GR 33 ALL FITTINGS SHALL BE FABRICATED FROM STEEL CONFORMING TO ONE OF THE FOLLOWING ASTM SPECIFICATIONS: A 575 A 576 A36 A 635 ALL STRUT CHANNEL MEMBERS AND COMPONENTS SHALL BE FINISHED WITH ONE OF THE FOLLOWING STANDARDS: ELECTRO-GALVANIZED (EG): ELECTROLYTICALLY ZINC COATED PER ASTM B 633 TYPE III SC 1 PRE-GALVANIZED (PG): ZINC COATED BY HOT-DIPPED PROCESS PRIOR TO ROLL FORMING. THE ZINC WEIGHT SHALL BE G90 CONFORMING TO ASTM A 653 HOT-DIPPED GALVANIZED (HG): ZINC COATED AFTER ALL MANUFACTURING OPERATIONS ARE COMPLETE. COATING SHALL CONFORM TO ASTM A 123 OR A 153 FIELD-CUTTING AND DRILLING OF STRUT CHANNELS SHALL BE MINIMIZED. STRUT CHANNELS WITH FACTORY-PUNCHED HOLES FOR FITTING CONNECTIONS SHALL BE USED WHERE DESIGNATED ON THE CONTRACT DRAWINGS AND WHERE HOLES OR SLOTS ARE ANTICIPATED BY THE CONTRACTOR. WHERE FIELD-CUTTING OR FIELD-DRILLING OF STRUT CHANNELS IS REQUIRED, SURFACES AFFECTED SHALL BE TREATED WITH A HIGH PERFORMANCE GALVANIZING PAINT AFTER FIELD-CUTTING OR FIELD- DRILLING IS PERFORMED. THE FOLLOWING GALVANIZING PRODUCTS ARE ACCEPTABLE: HIGH PERFORMANCE ZINC SPRAY, MANUFACTURED BY CLEARCO, INC. ZRC COLD GALVANIZING COMPOUND, MANUFACTURED BY ZRD WORLDWIDE, INC. SPRAYON SILVER GALVANIZING SPRAY, MANUFACTURED BY KRYLON, INC. ALTERNATE GALVANIZING PRODUCTS SHALL BE APPROVED BY THE ENGINEER PRIOR TO APPLICATION. FIELD-CUTTING OR FIELD-DRILLING OF CONNECTION COMPONENTS IS NOT ALLOWED. STRUT CHANNELS (6) #14 x 1-1/2" WOOD SCREW INTO DF SLEEPER, GALV, TYP UON (E) ROOF FRAMING PER PLAN (N) U-ANCHOR ROOF ATTACHMENT (2) SIMPSON 0.220 x 4" SDWS EXISTING ROOF FRAMING, MIN (2) PER U-ANCHOR, GALV,(N) PTDF SLEEPER PER /1 S-1 3/8" Ø COUPLING NUT, GALV. (N) U-ANCHOR ROOF ATTACHMENT, MIN (2) PER INVERTER (N) UNISTRUT P3300 RAIL w/ SLOTTED HOLES, GALV., w/ 3/8" Ø BOLT, WASHER & NUT, MIN (2) PER INVERTER, TYP. M8-1.25 x 70mm BOLT, MIN (2) PER SUPPORT FOOT, TYP. SECTION VIEW X-X (E) ROOF SHEATHING (E) ROOF FRAMING PER PLAN PLAN VIEW (N) UNISTRUT P3300 RAIL w/ SLOTTED HOLES, GALV., MIN (2) PER INVERTER, TYP. (N) 3/8" Ø BOLT, WASHER & NUT, GALV., TYP. (N) U-ANCHOR ROOF ATTACHMENT, MIN (2) PER INVERTER X X (N) INVERTER PER ELECT. SHEET E600 [WT 185# MAX] 6" MAX 1" MIN, TYP. 6" MAX S-1 2 (E) ROOF FRAMING (N) BLOCK PER SECTION (N) 2 x 8 PRESSURE-TREATED DF SLEEPER 1 1/2"1 1/2" 1 1/2" MIN 1 1/2" MIN 2" MIN, TYP 1" MIN, TYP. AL L I D E A S , D E S I G N S A N D A R R A N G E M E N T S I N D I C A T E D O N T H E S E D R A W I N G S A R E T H E P R O P E R T Y O F T K J S T R U C T U R A L E N G I N E E R I N G , I N C . , A N D A R E IN T E N D E D T O B E U S E D I N C O N N E C T I O N W I T H T H I S S P E C I F I C P R O J E C T O N LY , A N D S H A L L N O T B E U S E D F O R A N Y O T H E R P U R P O S E W H A T S O E V E R W I T H OU T T H E W R I T T E N C O N S E N T O F T H E E N G I N E E R . DRAWN BY WA X I E S A N T A A N A SY S T E M S I Z E : 22 3 . 5 9 k W D C BAJ DATE: 5/ 1 4 / 2 0 2 5 1 1 : 0 0 : 0 4 A M S-1 STRUCTURAL NOTES & DETAILS 5/13/25 32 2 0 S F A I R V I E W S T SA N T A A N A , C A 9 2 7 0 4 24 0 8 7 6-30-25 S 4845 EXP. STRUCTURAL TIMOTHY KYLE JAQUESS STATE OF CALIFORNIA REG ISTEREDPROFESSIONALENGINEER 3" 1'-0" U-Anchor Attachment Detail 2 1 1/2" 1'-0" Equipment Anchorage - Rooftop Inverter 1 242' - 4 3/4"148' - 9" 50' - 2" 123' - 2" 29' - 3 5/8" 411' - 1 3/4" (E) OFFICES (NOT IN SCOPE) 20' - 0"40' - 0" (TYP UNO) (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " 20' - 0" (E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2" ABCD 1 2 98' - 7" (N) INV PER ELECTRICAL; SEE FOR MOUNTING DETAILS (N) INV PER ELECTRICAL; SEE FOR MOUNTING DETAILS /1 S-1 /1 S-1 12'-0" +/- 6" 40'-0" +/- 6" 22'-6" +/- 6" 23'-0" +/- 6"25'-0" +/- 6" 7'-0" MIN 17'-3" +/- 6" 6'-6" +/- 6" LEGEND (E) 2x ROOF SUB-PURLIN PER SCHED TO REMAIN (E) ROOF FRAMING PER SCHED TO REMAIN (N) HANWHA Q CELLS Q.TRON BLK M-G2+ (425W) MODULES (514) TO BE INSTALLED ON BALLASTED UNIRAC RMDT RACKING PER PV DRAWINGS (E) SKYLIGHT AL L I D E A S , D E S I G N S A N D A R R A N G E M E N T S I N D I C A T E D O N T H E S E D R A W I N G S A R E T H E P R O P E R T Y O F T K J S T R U C T U R A L E N G I N E E R I N G , I N C . , A N D A R E IN T E N D E D T O B E U S E D I N C O N N E C T I O N W I T H T H I S S P E C I F I C P R O J E C T O N LY , A N D S H A L L N O T B E U S E D F O R A N Y O T H E R P U R P O S E W H A T S O E V E R W I T H OU T T H E W R I T T E N C O N S E N T O F T H E E N G I N E E R . DRAWN BY WA X I E S A N T A A N A SY S T E M S I Z E : 22 3 . 5 9 k W D C BAJ DATE: 5/ 1 4 / 2 0 2 5 1 1 : 0 0 : 0 4 A M S-2 ROOF FRAMING PLAN 5/13/25 32 2 0 S F A I R V I E W S T SA N T A A N A , C A 9 2 7 0 4 24 0 8 7 1/16" 1'-0" Roof Framing Plan 1 6-30-25 S 4845 EXP. STRUCTURAL TIMOTHY KYLE JAQUESS STATE OF CALIFORNIA REG ISTEREDPROFESSIONALENGINEER CB MS G AC D SP 39 ' - 1 0 " 6' - 0 " IN V IN V IN V T 15'-7" 45 ' - 6 " 23'-9" 45 ' - 6 " 23'-9" 45 ' - 6 " 45 ' - 6 " 23'-9"23'-9" 45 ' - 6 " 15'-7" 45 ' - 6 " 39 ' - 1 0 " 31'-11" MS G AC D SP T RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK A-102 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R ELECTRICAL PLAN 1 ELECTRICAL PLAN SCALE:1"=20'-0" ROOF SECTION ARRAY TILT - 5° ROOF SLOPE-0° AZIMUTH - 90° & 270° MODULE - 514 ROOF-1 (514) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES FOR (03) SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTERS (16) STRINGS OF (22) MODULES CONNECTED IN SERIES (02) STRINGS OF (21) MODULES CONNECTED IN SERIES (06) STRINGS OF (20) MODULES CONNECTED IN SERIES DC SYSTEM SIZE: 223.59 kW DC AC SYSTEM SIZE: 187.5 kW ACCEC AC RATING: 204.46 kW AC - 02 STRINGS OF 21 MODULES (E) MAIN ELECTRICAL ROOM 6FT FIRE SETBACKS (N) SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTER (ON ROOF) SEE ENLARGED VIEW (2x) (N) SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTERS (ON ROOF) (N) AC COMBINER PANEL (ON ROOF) ENLARGED VIEW (E) VISIBLE LOCKABLE LABELED AND FUSED AC DISCONNECT (INSIDE MAIN ELECTRICAL ROOM) (E) MAIN SWITCH GEAR (INSIDE MAIN ELECTRICAL ROOM) (E) SUBPANEL (INSIDE MAIN ELECTRICAL ROOM) ROOF 1 LEGEND - VENT, ATTIC FAN (ROOF OBSTRUCTION) - FIRE SETBACK - SKYLIGHT (ROOF OBSTRUCTION) ARRAY-1 ARRAY SECTION(S) TILT- 5° AZIMUTH - 90° & 270° MODULE - 50 (N) CONDUIT RUN NOTE : THE SMA INVERTERS LOCATED NEAREST TO THE ARRAY TO AVOID RSD PER UL 3741. N S EW - 16 STRINGS OF 22 MODULES (E) TRANSFORMER (INSIDE MAIN ELECTRICAL ROOM) ARRAY 1 - 06 STRINGS OF 20 MODULES ARRAY 2ARRAY 3ARRAY 4ARRAY 5ARRAY 6 ARRAY 7ARRAY 8ARRAY 9 ARRAY 12 ARRAY 11 ARRAY 10 ARRAY-2 TILT- 5° AZIMUTH - 90° & 270° MODULE - 50 ARRAY-3 TILT- 5° AZIMUTH - 90° & 270° MODULE - 58 ARRAY-4 TILT- 5° AZIMUTH - 90° & 270° MODULE - 48 ARRAY-5 TILT- 5° AZIMUTH - 90° & 270° MODULE - 48 ARRAY-6 TILT- 5° AZIMUTH - 90° & 270° MODULE - 32 ARRAY-7 TILT- 5° AZIMUTH - 90° & 270° MODULE - 48 ARRAY-8 TILT- 5° AZIMUTH - 90° & 270° MODULE - 48 ARRAY-9 TILT- 5° AZIMUTH - 90° & 270° MODULE - 32 ARRAY-10 TILT- 5° AZIMUTH - 90° & 270° MODULE - 30 ARRAY-11 TILT- 5° AZIMUTH - 90° & 270° MODULE - 30 ARRAY-12 TILT- 5° AZIMUTH - 90° & 270° MODULE - 40 Signed 4/04/2025 = OUTPUT DC INPUT MPPT 1 (N) SMA SUNNY TRIPOWER CORE1 62-US-41 INVERTER-1 OUTPUT CURRENT: 80A, 480VAC 97.5% CEC WEIGHTED EFFICIENCY NEMA 4X, UL LISTED, INTERNAL GFDI WITH INTEGRATED DC DISCONNECT (INVERTER-1) (ON ROOF) (172) HANWHA Q CELLS Q.TRON BLK M-G2+435 (435W) MODULES MPPT:1 (01) STRING OF 22 MODULES IN SERIES (01) STRING OF 22 MODULES IN SERIES MPPT:2 (01) STRING OF 22 MODULES IN SERIES MPPT:3 (01) STRING OF 20 MODULES IN SERIES MPPT:4 (01) STRING OF 22 MODULES IN SERIES (01) STRING OF 22 MODULES IN SERIES MPPT:5 (01) STRING OF 22 MODULES IN SERIES MPPT:6 (01) STRING OF 20 MODULES IN SERIES DC INPUT MPPT 2 DC INPUT MPPT 3 DC INPUT MPPT 4 DC INPUT MPPT 5 DC INPUT MPPT 61 (N) 400A AC COMBINER PANEL WITH (3) 100A\3P BREAKERS, 277/480V, 3 PHASE, UL LISTED, NEMA 3R (ON ROOF) 100A/3P G L1 L2 L3 N N G 100A/3P 4 7 = OUTPUT DC INPUT MPPT 1 (N) SMA SUNNY TRIPOWER CORE1 62-US-41 INVERTER-2 OUTPUT CURRENT: 80A, 480VAC 97.5% CEC WEIGHTED EFFICIENCY NEMA 4X, UL LISTED, INTERNAL GFDI WITH INTEGRATED DC DISCONNECT (INVERTER-2) (ON ROOF) DC INPUT MPPT 2 DC INPUT MPPT 3 DC INPUT MPPT 4 DC INPUT MPPT 5 DC INPUT MPPT 6 5 100A/3P (E) AC DISCONNECT VISIBLE, LOCKABLE, LABELED 400A AC DISCONNECT WITH (N) (3) 300A FUSES,277/480V, 3 PHASE NEMA 1, UL LISTED (INSIDE MAIN ELECTRICAL ROOM) G L1 L2 N LOAD LINE G L1 L2 L3 L3 GEC G N (E) MAIN SWITCH GEAR 600A RATED, 3-PHASE, 4-W, 277/480V ,WYE, (INSIDE MAIN ELECTRICAL ROOM) (E) MAIN FUSES 600A RATED, 277/480V LINE SIDE INTERCONNECTION AT MAIN SWITCH GEAR PER ART. 705.11 M L2L2L1 (E) BI-DIRECTIONAL UTILITY METER 3-PHASE, 4-W, 277/480 WYE, 600A RATED (INSIDE MAIN ELECTRICAL ROOM) L2 L3L2L1 TO UTILITY TRANSFROMER LINE LOAD N G N (E) SUB PANEL 400A RATED, 3-PHASE, 4-W, 277/480WYE, (INSIDE MAIN ELECTRICAL ROOM) (N) GROUNDING ELECTRODE SYSTEM PER CEC 250.66 (N) BONDING PER CEC 250.102(C)(1) (E) GROUNDING ELECTRODE SYSTEM TO EARTH (E)GROUNDING ELECTRODE SYSTEM (E) BONDING JUMPER (E) MAIN BONDING JUMPER EXISTING GROUNDING ELECTRODE SYSTEM TO EARTH 200A/3P 150A/3P 225A/3P 20A/3P PV MONITORING DISCONNEC A/C GUTTER TRANSFMR T/A LIGHTING PNL LA 8 E (E) LINE SIDE TAP PER CEC 705.11 = OUTPUT DC INPUT MPPT 1 (N) SMA SUNNY TRIPOWER CORE1 62-US-41 INVERTER-3 OUTPUT CURRENT: 80A, 480VAC 97.5% CEC WEIGHTED EFFICIENCY NEMA 4X, UL LISTED, INTERNAL GFDI WITH INTEGRATED DC DISCONNECT (INVERTER-3) (ON ROOF) DC INPUT MPPT 2 DC INPUT MPPT 3 DC INPUT MPPT 4 DC INPUT MPPT 5 DC INPUT MPPT 6 6 (N) # 2 AWG GEC (CU) (171) HANWHA Q CELLS Q.TRON BLK M-G2+435 (435W) MODULES MPPT:1 (01) STRING OF 22 MODULES IN SERIES (01) STRING OF 22 MODULES IN SERIES MPPT:2 (01) STRING OF 20 MODULES IN SERIES MPPT:3 (01) STRING OF 21 MODULES IN SERIES MPPT:4 (01) STRING OF 22 MODULES IN SERIES (01) STRING OF 22 MODULES IN SERIES MPPT:5 (01) STRING OF 22 MODULES IN SERIES MPPT:6 (01) STRING OF 20 MODULES IN SERIES (171) HANWHA Q CELLS Q.TRON BLK M-G2+435 (435W) MODULES MPPT:1 (01) STRING OF 22 MODULES IN SERIES (01) STRING OF 22 MODULES IN SERIES MPPT:2 (01) STRING OF 20 MODULES IN SERIES MPPT:3 (01) STRING OF 21 MODULES IN SERIES MPPT:4 (01) STRING OF 22 MODULES IN SERIES (01) STRING OF 22 MODULES IN SERIES MPPT:5 (01) STRING OF 22 MODULES IN SERIES MPPT:6 (01) STRING OF 20 MODULES IN SERIES 1A 2 2A 3 3A RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK E-601 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R ELECTRICAL LINE DIAGRAM ID PARALLEL FEEDER PHASE CONDUCTOR QTY, SIZE AND TYPE PER CONDUIT NEUTRAL GROUND CONDUCTOR QTY, SIZE AND TYPE PER CONDUIT CONDUIT SIZE CONDUIT TYPE 1 1 8 AWG #10 PV-WIRE/USE-2KV,CU N/A 1 AWG #10 THWN-2,COPPER EGC 1-1/4"EMT 1A 1 8 AWG #10 PV-WIRE/USE-2KV,CU N/A 1 AWG #10 THWN-2,COPPER EGC 1-1/4"EMT 2 1 8 AWG #10 PV-WIRE/USE-2KV,CU N/A 1 AWG #10 THWN-2,COPPER EGC 1-1/4"EMT 2A 1 8 AWG #10 PV-WIRE/USE-2KV,CU N/A 1 AWG #10 THWN-2,COPPER EGC 1-1/4"EMT 3 1 8 AWG #10 PV-WIRE/USE-2KV,CU N/A 1 AWG #10 THWN-2,COPPER EGC 1-1/4"EMT 3A 1 8 AWG #10 PV-WIRE/USE-2KV,CU N/A 1 AWG #10 THWN-2,COPPER EGC 1-1/4"EMT 4 1 3 AWG #2 THWN-2,COPPER 1 AWG #8 THWN-2,COPPER 1 AWG #8 THWN-2,COPPER EGC 1-1/4"EMT 5 1 3 AWG #2 THWN-2,COPPER 1 AWG #8 THWN-2,COPPER 1 AWG #8 THWN-2,COPPER EGC 1-1/4"EMT 6 1 3 AWG #2 THWN-2,COPPER 1 AWG #8 THWN-2,COPPER 1 AWG #8 THWN-2,COPPER EGC 1-1/4"EMT 7 1 3 MCM #350 THWN-2,COPPER 1 AWG #4 THWN-2,COPPER 1 AWG #4 THWN-2,COPPER EGC 2-1/2"EMT 8 1 3 MCM #350 THWN-2,COPPER N/A 1 AWG #2 THWN-2,COPPER EGC 2-1/2"EMT E EXISTING Vmax = Voc + ((TLow - TStc) x (VocCoef x Voc/100)) Vmax = 39.60+ ((2ºC - 25ºC) x (-0.24 x 39.60/100)) Vmax = 39.60 + (-23 x -0.093) Vmax = 41.73 = 1000/41.73 = 23.96 (Maximum Number of Modules in Series) NOTE : THE SMA INVERTERS LOCATED NEAREST TO THE ARRAY TO AVOID RSD PER UL 3741. (514) HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES FOR (03) SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTERS (16) STRINGS OF (22) MODULES CONNECTED IN SERIES (06) STRINGS OF (21) MODULES CONNECTED IN SERIES (02) STRINGS OF (20) MODULES CONNECTED IN SERIES DC SYSTEM SIZE: 223.59 kW DC AC SYSTEM SIZE: 187.5 kW ACCEC AC RATING: 204.46 kW AC Signed 4/04/2025 13.82A ELECTRICALCALCULATIONS RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK E-602 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R PERCENT OF VALUES NUMBER OF CURRENT CARRYING CONDUCTORS IN EMT 0.80 4-6 0.70 7-9 0.50 10-20 0.45 21-30 INVERTER SPECIFICATIONS MANUFACTURER / MODEL #SMA SUNNY TRIPOWER CORE1 STP 62-US-41 (480V) INVERTER NOMINAL AC POWER 62500 W NOMINAL OUTPUT VOLTAGE 480 VAC NOMINAL OUTPUT CURRENT 80 A AMBIENT TEMPERATURE SPECS(°C) RECORD LOW TEMP 2°C AMBIENT TEMP (HIGH TEMP 2%)31°C CONDUIT HEIGHT 7/8" ROOF TOP TEMP 31°C CONDUCTOR TEMPERATURE RATE 90°C SOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL # HANWHA Q CELLS Q.TRON BLK M-G2+ (435W) MODULES VMP 33.14V IMP 13.13A VOC 39.60V ISC TEMP. COEFF. VOC -0.24%/°K PTC RATING 408W MODULE DIMENSION 67.80×44.60×1.18 (In Inch) STC DC WIRE CALCULATION WIRE ID PARALLEL FEEDERS EXPECTED WIRE TEMP (In Celsius) TEMP. CORRECTION PER TABLE 310.15(B)(1) NO. OF CURRENT CARRYING CONDUCTORS CONDUIT FILL CORRECTION PER CEC 310.15(C)(1) CIRCUIT CONDUCTOR SIZE CIRCUIT CONDUCTOR AMPACITY @75°(PER FEEDER SET) CIRCUIT CONDUCTOR AMPACITY @90°(PER FEEDER SET) REQUIRED CIRCUIT CONDUCTOR AMPACITY PER CEC 690.8(A&B) 1.25 X 1.25 X Isc DERATED AMPACITY OF CIRCUIT CONDUCTOR PER CEC TABLE 310.16 TEMP. CORRECTION PER TABLE 310.15(B)(1) X CONDUIT FILL CORRECTION PER CEC 310.15(C)(1) X CIRCUIT CONDUCTOR AMPACITY @90°(PER FEEDER SET) DERATED AMPACITY OF CIRCUIT CONDUCTOR IS GREATER THAN REQUIRED ESTIMATED DISTANCE (FT) EXPECTED VOLTAGE DROP (%) 1 1 31°0.96 8 0.70 #10 AWG 35A 40A 21.55A 26.88A YES 31 0.16 1A 1 31°0.96 8 0.70 #10 AWG 35A 40A 21.55A 26.88A YES 25 0.13 2 1 31°0.96 8 0.70 #10 AWG 35A 40A 21.55A 26.88A YES 191 0.98 2A 1 31°0.96 8 0.70 #10 AWG 35A 40A 21.55A 26.88A YES 185 0.95 3 1 31°0.96 8 0.70 #10 AWG 35A 40A 21.55A 26.88A YES 277 1.42 3A 1 31°0.96 8 0.70 #10 AWG 35A 40A 21.55A 26.88A YES 260 1.33 TOTAL DC VOLTAGE DROP (FOR TAG 3) (%)1.42 AC WIRE CALCULATION WIRE ID PARALLEL FEEDERS EXPECTED WIRE TEMP (In Celsius) TEMP. CORRECTION PER TABLE 310.15(B)(1) NO. OF CURRENT CARRYING CONDUCTORS CONDUIT FILL CORRECTION PER CEC 310.15(C)(1) CIRCUIT CONDUCTOR SIZE CIRCUIT CONDUCTOR AMPACITY @75°(PER FEEDER SET) CIRCUIT CONDUCTOR AMPACITY @90°(PER FEEDER SET) REQUIRED CIRCUIT CONDUCTOR AMPACITY PER CEC 690.8(A)(1)(e) TOTAL INVERTER OUTPUT CURRENT MINIMUM OCPD REQUIRED PER CEC 690.9(B) TOTAL INVERTER OUTPUT CURRENT X 1.25 DERATED AMPACITY OF CIRCUIT CONDUCTOR PER CEC TABLE 310.16 TEMP. CORRECTION PER TABLE 310.15(B)(1) X CONDUIT FILL CORRECTION PER CEC 310.15(C)(1) X CIRCUIT CONDUCTOR AMPACITY @90°(PER FEEDER SET) DERATED AMPACITY OF CIRCUIT CONDUCTOR IS GREATER THAN REQUIRED ESTIMATED DISTANCE (FT) EXPECTED VOLTAGE DROP (%) 4 1 31°0.96 3 1 #2 AWG 115A 130A 80A 100A 124.8A YES 200 1.45 5 1 31°0.96 3 1 #2 AWG 115A 130A 80A 100A 124.8A YES 250 1.81 6 1 31°0.96 3 1 #2 AWG 115A 130A 80A 100A 124.8A YES 50 0.36 7 1 31°0.96 3 1 #350 MCM 310A 350A 240A 300A 336A YES 80 0.27 8 1 31°0.96 3 1 #350 MCM 310A 350A 240A 300A 336A YES 10 0.03 TOTAL AC VOLTAGE DROP( FOR TAG 5,7 & 8) (%)2.11 SMA SUNNY TRIPOWER CORE1 62-US-41 (480V) INVERTER = [(INVERTER OUTPUT POWER X 1.5) / (MODULE WATTAGE)] = [(62500W X 1.5) / (435)] = [(93750W / 435W)] = 215.51 = 215 MODULES PER INVERTER Signed 4/04/2025 WARNING LABELS RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK E-603 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL LOCATION: COMBINER PANEL, AC DISCONNECT, POINT OF INTERCONNECTION PER CODE: CEC 706.15(C)(4), CEC 690.13(B) WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM LABEL LOCATION: MAIN SERVICE DISCONNECT PER CODE: CEC 690.59, 705.12(C) LABEL LOCATION: MAIN SERVICE DISCONNECT, UTILITY METER PER CODE: CEC 690.13(B) POWER SOURCE OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE. WARNING LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: CEC 705.12(B)(3)(2) LABEL LOCATION: AC DISCONNECT PER CODE: CEC 705.12(B)(3)(3) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL WARNING LABEL LOCATION: COMBINER PANEL(S), MAIN SERVICE DISCONNECT PER CODE: CEC 110.27(C), OSHA 1910.145(f)(7) ELECTRICAL SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT LABEL LOCATION: DC DISCONNECT PER CODE: CEC 690.13(B) LABEL LOCATION: AC DISCONNECT PER CODE: CEC 690.13(B) ! ! ! ! ! PHOTOVOLTAIC POWER SOURCE LABEL LOCATION: DC CONDUIT/RACEWAYS PER CODE: CEC 690.31(D)(2) SOLAR PV DC CIRCUIT LABEL LOCATION: DC CONDUIT/RACEWAYS PER CODE: CEC 690.31(D)(2) LABEL LOCATION: AC DISCONNECT/POINT OF INTERCONNECTION PER CODE: CEC 690.54 PHOTOVOLTAIC SYSTEM AC DISCONNECT RATED AC OUTPUT CURRENT:240 A NOMINAL OPERATING AC VOLTAGE:480 V THIS EQUIPMENT FED BY MULTIPLE SOURCES: TOTAL RATING OF ALL OVERCURRENT DEVICES EXCLUDING MAIN POWER SUPPLY SHALL NOT EXCEED AMPACITY OF BUSBAR WARNING! LABEL LOCATION: MAIN SERVICE DISCONNECT PER CODE: CEC 705.12(D), CEC 690.59 CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED ! DO NOT DISCONNECT UNDER LOAD LABEL LOCATION: MAIN SERVICE DISCONNECT PER CODE: CEC 690.15(B) & CEC 690.33(D)(2) LABEL LOCATION: DC DISCONNECT/INVERTER/PV DIST. EQUIPMENT PER CODE: CEC 690.53 MAXIMUM DC VOLTAGE OF PV SYSTEM PV SYSTEM DISCONNECT MAIN PHOTOVOLTAIC SYSTEM DISCONNECT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 INVERTERDC DISCONNECT PV ARRAY 2 5 9 11 1 10 UTILITY METER PV AC DISCONNECT (WHEN PRESENT) MAIN SWITCH INVERTERDC DISCONNECT PV ARRAY 134 AC COMBINER PANEL 3 43 14 1 2 1 5 7 10 INVERTERDC DISCONNECT PV ARRAY 43 GEAR SUB PANEL 13 14 13 14 8 6 12 Signed 4/04/2025 CB MS G AC D SP IN V IN V IN V T RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK E-604 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R PLACARDS CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: PV ARRAYS PV AC DISCONNECT (INSIDE MAIN ELECTRICAL ROOM) MAIN SWITCH GEAR (INSIDE MAIN ELECTRICAL ROOM) N S EW Signed 4/04/2025 RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK R-001 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R RESOURCEDOCUMENT 3220 S. Fairview St. 187.5kW AC solar PV install of 526 QCell panels with 3 SMA inverters Reem Ateek 760 504-0388 01 14 2025 Santa Ana RA RA CITY OF SANTA ANA Planning and Building Agency VIRF GE COGy c4[IF RG�P RANGE COUNTY FIRE AUTHORIT Plan Referral Form Required for OCFA to review plans upon the request of the Building Department the answers on the Plan Submittal Criteria Form (on the reverse) are all "No". City / County Official Requesting Review: City / County Reference #: City/County: Contact Name: Title: Date: E-Mail: Phone #: Approved FOR PERMIT ISSUANCE ** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. ** Reason(s) for Review: Please describe why OCFA Plan Review is or may be required by the City/County: OCFA COMMENTS: ❑ No further action required on this specific plan type, based on information provided on: ❑ Project to be taken in for OCFA Review. Other: Date: OCFA Authorization Updated: 06/02/2020 rs TRANSACTION DETAILS DOCUMENT DETAILS Reference Number 55D0D608-E936-429A-826F-785AEE20F01F Transaction Type Signature Request Sent At 01/14/2025 16:16 EST Executed At 01/14/2025 16:17 EST Identity Method email Distribution Method email Signed Checksum bf4a3505949f262cf614d52d6a89f0a7a8722991e7581f7b245d66c083ab2f35 Signer Sequencing Disabled Document Passcode Disabled Document Name Orange Co Fire Authority Form - 3220 S Fairview St Filename Orange_Co_Fire_Authority_Form_-_3220_S_Fairview_St.pdf Pages 2 pages Content Type application/pdf File Size 865 KB Original Checksum f89455116414004ab1be8c4a9383380392ce922ec4c6bf09940468d82cae3351 SIGNERS SIGNER E-SIGNATURE EVENTS Name Reem Ateek Email documents@palomarsolar.com Components 3 Status signed Multi-factor Digital Fingerprint Checksum b4af6c0be00537cb89640b63e4b31146be775fb711de4661f817965af0afdc67 IP Address 98.185.98.242 Device Microsoft Edge via Windows Typed Signature Signature Reference ID 7885BE9E Viewed At 01/14/2025 16:16 EST Identity Authenticated At 01/14/2025 16:17 EST Signed At 01/14/2025 16:17 EST AUDITS TIMESTAMP AUDIT 01/14/2025 16:16 EST Palomar Solar and Roofing (documents@palomarsolar.com) created document 'Orange_Co_Fire_Authority_Form_-_3220_S_Fairview_St.pdf' on Chrome via Windows from 35.169.110.255. 01/14/2025 16:16 EST Reem Ateek (documents@palomarsolar.com) was emailed a link to sign. 01/14/2025 16:16 EST Reem Ateek (documents@palomarsolar.com) viewed the document on Microsoft Edge via Windows from 98.185.98.242. 01/14/2025 16:17 EST Reem Ateek (documents@palomarsolar.com) authenticated via email on Microsoft Edge via Windows from 98.185.98.242. 01/14/2025 16:17 EST Reem Ateek (documents@palomarsolar.com) signed the document on Microsoft Edge via Windows from 98.185.98.242. SIGNATURE CERTIFICATE REFERENCE NUMBER 55D0D608-E936-429A-826F-785AEE20F01F TKJ Structural Engineering 9820 Willow Creek Rd., Suite 490 San Diego, CA 92131 858.649.1700 www.tkjse.com STRUCTURAL CALCULATIONS V2 For: Waxie Santa Ana PV 3220 S Fairview St Santa Ana, CA 92704 [INSERT STAMP] Date: TKJSE Job No: February 24, 2025 24087 Page 1 of 23 V3 May 14, 2025May 21, 2025 TKJ Structural Engineering 9820 Willow Creek Rd., Suite 490 San Diego, CA 92131 858.649.1700 www.tkjse.com SCOPE AND TABLE OF CONTENTS Project Description: Client: Property: Scope: Table of Contents: Section Title 1 to 1 Table of Contents 2 to 2 Load Takeoffs 3 to 4 Seismic Increase Checks 5 to 8 Gravity Load Checks 9 to 14 Inverter Attachment Anchorage Checks 15 to 23 Palomar Solar The calculations provided herein are the property of TKJ Structural Engineering, Inc., and may be used solely by the Client for the Project located at the Address noted above. Pages 3220 S Fairview St Santa Ana, CA 92704 The project consists of Fully-ballasted rooftop PV modules Framing consists of Glulam Beams. Lateral resistance provided by tilt-up concrete walls. Waxie Santa Ana PV Page 2 of 23 Page 3 of 23 LOAD TAKEOFFS Project: Project No.: Date: DESIGN LOADS DEAD LOADS Notes: * DL of beam member(s) self-weight included in analysis ** Where solar is present, roof live load has been reduced to 50%. psf LL: psf DLL <= DTL <= psf Misc. 1.4 1.9 1.9 10.0 10.0 1.5 1.5 1.0 1.4 8.5 10.5 MEP 1.0 Waterproofing 0.1 0.1 0.1 0.1 GLB 15-1/2 x 3-1/8 2.1 2.1 2.1 2.1 Insulation 0.2 0.2 0.2 0.2 1/2" Plywood 1.5 1.5 1.5 1.5 GLB 31-1/2 x 5-1/8 - 1.0 1.0 1.0 Waxie Santa Ana PV 12/14/2024 24087 Asphalt Shingles 2.0 2.0 2.0 2.0 Roof Joists Beams Walls Seismic L/360 L/240 87.5 89.2 89.2 89.0 89.0 20 20 20 Walls Interior Seismic Exterior Seismic Tilt-Up Concrete 87.5 87.5 87.5 Misc. 1.2 1.2 1.0 1.3 MEP 0.5 0.5 0.5 0.2 Skylights 0.2 0.2 0.2 0.2 Page 4 of 23 Page 5 of 23 SEISMIC INCREASE CHECKS Project: Project #: Prepared By: Date: Page 6 of 23 Waxie Santa Ana PV - Fully Ballasted 24087 BS 02/05/2025 Per Load Takeoffs: Total Seismic Weight of Roof w/o Solar = 10 psf x 53,000 sq-ft = 530 kip Total Seismic Weight of Walls = 89 psf; Wall perimeter = 1104 ft; Wall Height = 30 ft 89 psf x 1104 ft x (30 ft / 2) = 1474 kip Total weight = 2004 kip (N) Solar Weight Total weight of array per UNIRAC = 57.749 kip [(57.749 kip / 2004 kip) *100 ] = 2.88% Seismic Increase < 10%: OK [Seismic Weight Increase: Global]: 50' - 2" 2" 29' - 3 5/8" (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2" (N) INV PER ELECTRICAL; SEE FOR MOUNTING DETAILS/1 S-1 40'-0" +/- 6" 22'-6" +/- 6" 23'-0" +/- 6"25'-0" +/- 6" 7'-0" MIN 17'-3" +/- 6" 6'-6" +/- 6" Project: Project #: Prepared By: Date: Page 7 of 23 [Seismic Weight Increase: Local, Longitudinal]: Per Load Takeoffs: Area of Roof highlighted above = 27215 sq-ft Total Seismic Weight of Roof w/o Solar = 10 psf x 27215 sq-ft = 272 kip Total Seismic Weight of Walls = 89 psf; Wall perimeter above = 441 ft; Wall Height = 30 ft 89 psf x 441 ft x (30 ft / 2) = 713 kip Total weight = 985 kip (N) Solar Weight Weight of arrays in shaded region: Total = 38.43 kip [ (38.43 kip / 985 kip) * 100 ] = 3.9% Seismic Increase < 10%: OK Waxie Santa Ana PV - Fully Ballasted 24087 BS 02/05/2025 50' - 2" 2" 29' - 3 5/8" (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2" (N) INV PER ELECTRICAL; SEE FOR MOUNTING DETAILS/1 S-1 40'-0" +/- 6" 22'-6" +/- 6" 23'-0" +/- 6"25'-0" +/- 6" 7'-0" MIN 17'-3" +/- 6" 6'-6" +/- 6" Project: Project #: Prepared By: Date: Page 8 of 23 [Seismic Weight Increase: Local, Transverse]: Per Load Takeoffs: Area of Roof highlighted above = 36056 sq-ft Total Seismic Weight of Roof w/o Solar = 10 psf x 36056 sq-ft = 360 kip Total Seismic Weight of Walls = 89 psf; Wall perimeter above = 441 ft; Wall Height = 30 ft 89 psf x 441 ft x (30 ft / 2) = 588 kip Total weight = 948 kip (N) Solar Weight Weight of arrays in shaded region: [ Individual Panel Area = 23.541 sq-ft ] 389 Panels, Total Shaded Area = 9158 sq-ft, Average Module Weight = 4.83 psf (Panel, Ballast, Rack) Total Weight: 9158 sq-ft * 4.83 psf = -> -> Total = 44.3 kip [ (44.3 kip) / 948 kip) *100 ] = 4.67% Seismic Increase < 10%: OK Waxie Santa Ana PV - Fully Ballasted 24087 BS 02/05/2025 50' - 2" 2" 29' - 3 5/8" (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2" (N) INV PER ELECTRICAL; SEE FOR MOUNTING DETAILS/1 S-1 40'-0" +/- 6" 22'-6" +/- 6" 23'-0" +/- 6"25'-0" +/- 6" 7'-0" MIN 17'-3" +/- 6" 6'-6" +/- 6" Page 9 of 23 GRAVITY LOAD CHECKS Project: Project #: Prepared By: Date: Page 10 of 23 MEMBERS TO BE CHECKED FOR GRAVITY LOADS: The following pages contain checks of the members shown above under the presumed array loads. Waxie Santa Ana PV - Fully Ballasted 24087 CM 02/24/2025 50' - 2" 2" 29' - 3 5/8" (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2" (N) INV PER ELECTRICAL; SEE FOR MOUNTING DETAILS/1 S-1 40'-0" +/- 6" 22'-6" +/- 6" 23'-0" +/- 6"25'-0" +/- 6" 7'-0" MIN 17'-3" +/- 6" 6'-6" +/- 6" B- 1 B- 2 J-1 Project: Date: Wood Beam Design Beam Label: Geometry Left Overhang= Center Span=Overall Length= Right Overhang= Loads Point Load 1 Point Load 2 Point Load 3 Point Load 4 Start End Start End Start End Start End Beam Self Wt.0.0 0.0 0 0 0 0 0.00 ft 60.50 ft Dist Load 1 0 0 480 480 0 0 0.00 ft 6.50 ft Dist Load 2 166.0 166.0 0 0 0 0 6.50 ft 60.50 ft Dist Load 3 400 400 0 0 0 0 0.00 ft 60.50 ft Dist Load 4 0 0 0 0 0 0 0.00 ft 0.00 ft W=1.0 [1.0 for Wind loading or if not req'd per ASCE 7-16 12.4.3.1] Load Combinations D + L 0.6D +/- (.6W or .7rE) D + (.6W or .7rE)D + 0.75[L + (.6W or .7rE)] Governing Combination: Deflection Criteria ΔLL<=ΔTL<=Kcr=1.5 Beam Member Design b= 5.13 in Fv= d= 31.50 in Fb= Sx=847.55 in3 E= Ix=13348.86 in4 Emin= Shear Design Equation F'v= Fv(CD)(CM)(Ct)(Ci)(CF) fv=VQ / Ib [=3V / 2bd for rectangular sections]Vmax= Vmin= Flexural Design Equation Mmax= F'b= Fb(CD)(CM)(Ct)(CL)(CF)(CV)(Cfu)(Ci)(Cr)(Cc) Mmin= fb= M / Sx RLmax= RLmin= Modification Factors RRmax= CD=0.90 Load Duration Factor [NDS 18 Table 2.3.2]RRmin= CM=1.00 Wet Service Factor [NDS 18 Table 4A, 4D, 5A, 5B] Ct=1.00 Temperature Factor [NDS 18 Table 2.3.3] CL=0.99 Beam Stability Factor [NDS 18 3.3.3]fv=152 psi lu=50 in Effective Unbraced Length [NDS 18 Table 3.3.3]F'v=239 psi CF=1.00 Size Factor [Sawn only. NDS 18 4.3.6]fb=1746 psi CV=0.83 Volume Factor [Manuf or GLB's only. NDS 18 5.3.6]F'b=1772 psi Cfu=1.00 Flat Use Factor [NDS 18 Table 4A, 4D, 5A]ΔLL=0.00 in Ci=1.00 Incising Factor [NDS 18 Table 4.3.8] Cr=1.00 Repetitive Member Factor [=1.15 if s<= 24" o.c.]ΔTL=0.00 in Cc=1.00 Curvature Factor [GLB's only. See NDS 18 5.3.8] 3.22 in 1.08 in OK=L / 186 =L / 117 0.17 in 0.30 in OK=L / 3455 =L / 424 17966 # Design Summary D/C =0.64 OK D/C =0.99 OK 10904 # 2444 # 0 # 13348 # 6542 # 29943 # 2929 # 0 # 32872 # 123329 ft-lbs 6222 ft-lbs 0 ft-lbs 123329 ft-lbs -111870 ft-lbs -23658 ft-lbs 0 ft-lbs -135527 ft-lbs 13626 #2444 #0 #15879 # -16317 # -676 # 0 # -16993 # 1800 ksi 950 ksi Analysis Summary DL LL E or W Combinations 5.125"x31.5" GLB 24F-V4 (1.8E)Strong-way 265 psi 2400 psi D L / 360 L / 180 Section Species & Grade Orientation .7rEh Location DL (plf) LL (plf) or .6W (plf) From Left 0 # 0 # 0 # 0.00 ft 0 # 0 # 0 # 0.00 ft 0 # 0 # 0 # 0.00 ft 0.00 ft 50.00 ft 60.50 ft 7683 # 2253 # 0 # 60.50 ft 10.50 ft .7rEh Location DL LL or .6W From Left Waxie Santa Ana PV 2/24/25 B-1 -1 0 1 Sh e a r Mo m e n t De f l e c t i o n Page 11 of 23 max ballast count @ 166 plf = 280 Project: Date: Wood Beam Design Beam Label: Geometry Left Overhang= Center Span=Overall Length= Right Overhang= Loads Point Load 1 Point Load 2 Point Load 3 Point Load 4 Start End Start End Start End Start End Beam Self Wt.0.0 0.0 0 0 0 0 0.00 ft 29.00 ft Dist Load 1 192 192 0 0 0 0 0.00 ft 12.50 ft Dist Load 2 0.00 0.00 480 480 0 0 12.50 ft 29.00 ft Dist Load 3 400 400 0 0 0 0 0.00 ft 29.00 ft Dist Load 4 0 0 0 0 0 0 0.00 ft 0.00 ft W=1.0 [1.0 for Wind loading or if not req'd per ASCE 7-16 12.4.3.1] Load Combinations D + L 0.6D +/- (.6W or .7rE) D + (.6W or .7rE)D + 0.75[L + (.6W or .7rE)] Governing Combination: Deflection Criteria ΔLL<=ΔTL<=Kcr=1.5 Beam Member Design b= 5.13 in Fv= d= 28.50 in Fb= Sx=693.80 in3 E= Ix=9886.61 in4 Emin= Shear Design Equation F'v= Fv(CD)(CM)(Ct)(Ci)(CF) fv=VQ / Ib [=3V / 2bd for rectangular sections]Vmax= Vmin= Flexural Design Equation Mmax= F'b= Fb(CD)(CM)(Ct)(CL)(CF)(CV)(Cfu)(Ci)(Cr)(Cc) Mmin= fb= M / Sx RLmax= RLmin= Modification Factors RRmax= CD=1.25 Load Duration Factor [NDS 18 Table 2.3.2]RRmin= CM=1.00 Wet Service Factor [NDS 18 Table 4A, 4D, 5A, 5B] Ct=1.00 Temperature Factor [NDS 18 Table 2.3.3] CL=0.98 Beam Stability Factor [NDS 18 3.3.3]fv=123 psi lu=50 in Effective Unbraced Length [NDS 18 Table 3.3.3]F'v=265 psi CF=1.00 Size Factor [Sawn only. NDS 18 4.3.6]fb=1411 psi CV=0.89 Volume Factor [Manuf or GLB's only. NDS 18 5.3.6]F'b=2089 psi Cfu=1.00 Flat Use Factor [NDS 18 Table 4A, 4D, 5A]ΔLL=0.00 in Ci=1.00 Incising Factor [NDS 18 Table 4.3.8] Cr=1.00 Repetitive Member Factor [=1.15 if s<= 24" o.c.]ΔTL=0.00 in Cc=1.00 Curvature Factor [GLB's only. See NDS 18 5.3.8] 0.90 in 0.00 in OK=L / 387 0.26 in 0.00 in OK=L / 1324 3790 # Design Summary D/C =0.46 OK D/C =0.68 OK 7683 # 2253 # 0 # 9936 # 4610 # 6317 # 5667 # 0 # 11984 # 49884 ft-lbs 33449 ft-lbs 0 ft-lbs 81602 ft-lbs 0 ft-lbs 0 ft-lbs 0 ft-lbs 0 ft-lbs 7683 #2253 #0 #9936 # -6317 # -5667 # 0 # -11984 # 1800 ksi 950 ksi Analysis Summary DL LL E or W Combinations 5.125"x28.5" GLB 24F-V4 (1.8E)Strong-way 265 psi 2400 psi D + L L / 240 L / 180 Section Species & Grade Orientation .7rEh Location DL (plf) LL (plf) or .6W (plf) From Left 0 # 0 # 0 # 0.00 ft 0 # 0 # 0 # 0.00 ft 0 # 0 # 0 # 0.00 ft 0.00 ft 29.00 ft 29.00 ft 0 # 0 # 0 # 0.00 ft 0.00 ft .7rEh Location DL LL or .6W From Left Waxie Santa Ana PV 2/24/25 B-2 -1 0 1 Sh e a r Mo m e n t De f l e c t i o n Page 12 of 23 Project:Waxie Santa Ana PV Date:2/24/25 Wood Beam Design Joist Label: Geometry Left Overhang=True Length= Center Span=True Length= Right Overhang=True Length= Joist Spacing=Overall Length= Roof Pitch= Loads Point Load 1 Point Load 2 Point Load 3 Point Load 4 Start End Start End Start End Start End Dist Load 1 8.5 8.5 0 0 0 0 0.00 ft 40.00 ft Dist Load 2 4.80 4.80 0 0 0 0 0.00 ft 40.00 ft Dist Load 3 0 0 0 0 0 0 0.00 ft 0.00 ft Dist Load 4 0 0 0 0 0 0 0.00 ft 0.00 ft Start End Start End Start End Start End Dist Load 1 68 68 0 0 0 0 0.00 ft 40.00 ft Dist Load 2 38 38 0 0 0 0 0.00 ft 40.00 ft Dist Load 3 0 0 0 0 0 0 0.00 ft 0.00 ft Dist Load 4 0 0 0 0 0 0 0.00 ft 0.00 ft W=1.0 [1.0 for Wind loading or if not req'd per ASCE 7-16 12.4.3.1] Load Combinations D + L 0.6D +/- (.6W or .7rE) D + (.6W or .7rE)D + 0.75[L + (.6W or .7rE)] Governing Combination: Deflection Criteria ΔLL<= ΔTL<= Kcr=1.5 Joist Member Design b= 3.13 in Fv= d= 22.50 in Fb= Sx=263.67 in3 E= Ix=2966.31 in4 Emin= 265 psi 2400 psi 1800 ksi 0 #0 #0 #0.00 ft L / 360 L / 240 Section Species & Grade Orientation Strong-way 950 ksi D 0:12 .7rEh Location DL LL or .6W From Left From Left .7rEh Location DL (plf)LL (plf)or .6W (plf)From Left 0 # 0 # 0 # 0.00 ft .7rEh Location DL (psf)LL (psf)or .6W (psf) 3.125"x22.5" GLB 24F-V4 (1.8E) J-1 0 #0 #0 #20.00 ft 0 #0 #0 #0.00 ft 96'' o.c.40.00 ft 0.00 ft 0.00 ft 40.00 ft 40.00 ft 0.00 ft 0.00 ft -0.1 0.9 Sh e a r ( l b s . ) Mo m e n t ( f t - l b s . ) De f l e c t i o n ( i n . ) Page 13 of 23 Project:Waxie Santa Ana PV Date:2/24/25 Wood Beam Design Shear Design Equation F'v=Fv(CD)(CM)(Ct)(Ci)(CF) fv=VQ / Ib [=3V / 2bd for rectangular sections]Vmax= Vmin= Flexural Design Equation Mmax= F'b=Fb(CD)(CM)(Ct)(CL)(CF)(CV)(Cfu)(Ci)(Cr)(Cc)Mmin= fb=M / Sx RLmax= RLmin= Modification Factors RRmax= CD=0.90 Load Duration Factor [NDS 18 Table 2.3.2]RRmin= CM=1.00 Wet Service Factor [NDS 18 Table 4A, 4D, 5A, 5B] Ct=1.00 Temperature Factor [NDS 18 Table 2.3.3] CL=0.78 Beam Stability Factor [NDS 18 3.3.3]fv=45 psi lu=120 in Effective Unbraced Length [NDS 18 Table 3.3.3]F'v=239 psi CF=1.00 Size Factor [Sawn only. NDS 18 4.3.6]fb=968 psi CV=0.93 Volume Factor [Manuf or GLB's only. NDS 18 5.3.6]F'b=1567 psi Cfu=1.00 Flat Use Factor [NDS 18 Table 4A, 4D, 5A] ΔLL= Ci=1.00 Incising Factor [NDS 18 Table 4.3.8] Cr=1.00 Repetitive Member Factor [=1.15 if s<= 24" o.c.] ΔTL= Cc=1.00 Curvature Factor [GLB's only. See NDS 18 5.3.8] 0.0000 in 1.7216 in 0.00 in OK=L / 279 D/C =0.62 OK 0.00 in 0.000 in 0.00 in OK 21278 ft-lbs 0 ft-lbs 0 ft-lbs 21278 ft-lbs 1277 # Design Summary D/C = 0 ft-lbs 0 ft-lbs 0 ft-lbs 0 ft-lbs 2128 # 0 # 0 # 2128 # -2128 # 0 # 0 # -2128 # 2128 # 0 # 0 # 2128 # 1277 # 2128 # 0 # 0 # 2128 # 0.19 OK Analysis Summary DL LL E or W Combinations Page 14 of 23 Page 15 of 23 INVERTER ATTACHMENT ANCHORAGE CHECK Project: Project #: Prepared By: Date: Page 16 of 23 Waxie Santa Ana PV 24087 CM 02/18/2025 EQUIPMENT ANCHORAGE: ROOFTOP INVERTER Equipment Information: Inverter Dimensions (W/H/D) = 24.4 in x 28.8 in x 22.4 in Weight, Wp = 185 lbs Ye = 4.5" Xe = 6" + 12.2" = 18.2"D H Ev, Fv Fp, Fh Wp Xe Ye Seismic Loading: ASCE Ch. 13 SDS = 1.042 g Ip = 1.0 Rp = 2.5 ap =1.0 z/h = 1.0 Fp = (0.4×ap×SDS×Wp)(1+2×z/h)/(Rp/Ip) = 0.4×(1.0)×(1.042)×(185#)×(1+2)/(2.5/1.0) = 93# Ev = 0.2×SDS×Wp = 39# Wind Loading: ASCE Ch. 29 V = 95 mph Exp = C h = 30 ft Kd = 0.85 Kzt = 1.0 Ke = 1.0 qh = 0.00256×Kz×Kzt×Kd×Ke×V2 = 0.00256×(0.85)×(1.0)×(0.85)×(1.0)×(95)^2 = 16.7 psf Fh = 1.9×qh×B×H = 1.9×(16.7 psf)×(24.4")×(28.8") = 155# Fv = 1.5×qh×B×D = 1.5×(16.7)×(24.4")×(22.4") = 96# Load Case: D + 0.7E Lh = 0.7×(93#) = 65.1# Lv = (-185#) + 0.7×(39#) = -157.7# Load Case:0.6D + 0.6W Lh = 0.6×(155#) = 93# Lv = 0.6×(-185#) + 0.6×(96#) = -53.4# Project: Project #: Prepared By: Date: Page 17 of 23 Waxie Santa Ana PV 24087 CM 02/18/2025 EQUIPMENT ANCHORAGE: ROOFTOP INVERTER PLAN VIEW V Xe h Connection: Unistrut to Coupling Nut Bolt Ø = 3/8" Ab = 0.11 in2 Bolt Grade = A307 Fnv = 27 ksi Fnt = 45 ksi Maximum Reactions @ Inverter LC: D + 0.7E: LC: 0.6D + 0.6W: Shear, Lh = 65.1# Lh = 93# Tension, Lv = 158# Lv = 54# Moment from Offset, Me = (158#)(18.2") = 2876 in-lbs Spacing between U-Anchors, h = 15" Loading Per Bolt: V = (93#)/(2 bolts) + (93#)×(18.2")/(15") =160# T = (158#)/(2 bolts) + (2876 in-lbs)/(15") = 271# Coupling Nut Allowable Loads: Shear, Va = Ab×Fnv/2 = 1485# D/C = 160# / 1485# = 0.12, therefore OK Tension, Ta = Ab×Fnt/2 = 2475# D/C = 271# / 2475# = 0.11, therefore OK Resultant, R = √(160#)2 + (271#)2 = 315# D/C = 315# / 1485# = 0.22, therefore OK Project: Project #: Prepared By: Date: Page 18 of 23 Waxie Santa Ana PV 24087 CM 02/18/2025 EQUIPMENT ANCHORAGE: ROOFTOP INVERTER Connection: U-Anchor U2600-SBS Number of U-Anchors per inverter = 2 minimum Max Horizontal Offset, Ye = 4.5" Max Vertical Offset, Xe = 18.2" T VMe Maximum Reactions @ Inverter LC: D + 0.7E: LC: 0.6D + 0.6W: Shear, V = 65.1# V = 93# Tension, T = 158# T = 54# Loading Per Bolt: V = (93#)/(2 bolts) + (93#)×(18.2")/(15") =160# T = (158#)/(2 bolts) + (2876 in-lbs)/(15") = 271# U-Anchor U2600-SBS Bolt Allowable Loading: (per data sheet in 'Reference Documents' section) Shear, Va = 4339# / 3.0 = 1446# D/C = 160# / 1446# = 0.13, therefore OK Tension, Ta = 2713# / 3.0 = 904# D/C = 271# / 904# = 0.31, therefore OK 5 1/2" Connection: #14 Wood Screws Anchor Type = (2) U-Anchor Attachment Number of screws per attachment = (2) 3" screws, (4) 3/4" screws Loading Per Screw: V = (160#)/(6 screws) = 27# T = (271#)/(2 screws) + (160#)×(18.2")/(3.44")(2 screws) = 559# - See following pages for wood screw check 2 1/16" Project: Project #: Prepared By: Date: Page 19 of 23 Waxie Santa Ana PV 24087 CM 02/18/2025 EQUIPMENT ANCHORAGE: ROOFTOP INVERTER 14 x 1" wood screw check (Shear) Dowel Bearing Strength per NDS Table 12.3.3 G = 0.50 Fe = 4650 psi Area of screw = (pi/4)*(0.25^2) = 0.049 in^2 Bearing (Shear) Strength = 228 lbs >> 27 lbs; OK NOTE: 3" Wood screws are able to resist the full demands of tension; additional screws into sheathing are intended to resist shear only. Project: Job No.: Date: WOOD CONNECTION DESIGN: WOOD SCREW CONNECTIONS [2018 NDS CHAPTERS 11 & 12] GENERAL DATA CONNECTION: Connector Type: Single or Double Shear: Connection Exposed to Wet Service?CM=1.00 Connection Exposed to High Temp?Ct=1.00 Connectors in End Grain?Ceg=1.00 Diaphragm Connection?Cdi=1.00 Toe-Nail Connection?Ctn=1.00 CONNECTOR FASTENER PATTERN Size:Dr=in 1 Rows of 1 screws/row = 1 screws CD=1.00 Length: L= in Cg=1.00 Fyb=ksi SIDE MEMBER Material:qm=degrees from horiz.ls= Width:Fes=psi MAIN MEMBER Material:qm=degrees from horiz.p= Width:Fem=psi lm= LOADS SUMMARY D L Lr E W Z' (lbs) D/C 0.25 in 0.01 0.01 0.02 0.02 0.05 2075 1971 857 867 398 3.50 in 3.50 in Yield Mode Im Is II IIIm IIIs IV R (lbs) 18 18 18 18 18 18 0.05379 27 lbs 559 lbs 0 lbs 0 lbs 0 lbs 0 lbs 26 lbs 32 lbs Withdrawal 319 782 0.41 Combined 320 709 0.45 Waxie Santa Ana PV 24087 2/18/25 4.00 in 0.196 4.000 No Rooftop Inverter Anchorage (#14 x 4" Screw) No Wood Screw Single Shear #14 No No No DF-L 46503.50 in 90 80 Shear (RH) Tension (RV) 0 lbs -27 lbs Steel 0 0.250 in 61850 Page 20 of 23 Project: Job No.: Date: WOOD CONNECTION DESIGN: WOOD SCREW CONNECTIONS [2018 NDS CHAPTERS 11 & 12] LOAD COMBINATIONS CONNECTION: LC1 LC2 LC3 LC4 LC5 LC6 LC7 LC8 LC9 LC10 YIELD MODE Im CD nconn D/C LC1 0.90 1 0.00 D=in LC2 1.00 1 0.00 lm=in LC3 1.25 1 0.00 Fem=psi LC4 1.00 1 0.00 Rd=LC5 1.60 1 0.01 Z=lbs LC6 1.60 1 0.01 LC7 1.60 1 0.01 LC8 1.60 1 0.01 LC9 1.60 1 0.01 LC10 1.60 1 0.01 LC6 0.01 YIELD MODE Is CD nconn D/C LC1 0.90 1 0.00 ns=[1 for single shear; 2 for double shear] LC2 1.00 1 0.00 D=in LC3 1.25 1 0.00 ls=in LC4 1.00 1 0.00 Fes=psi LC5 1.60 1 0.01 Rd=LC6 1.60 1 0.01 Z=lbs LC7 1.60 1 0.01 LC8 1.60 1 0.01 LC9 1.60 1 0.01 LC10 1.60 1 0.01 LC6 0.011971 16 1.00 1971 18 1.00 1971 1971 1 14 1.00 1971 16 1.00 1971 18 1.00 1971 2075 2075 1232 R (CM…Ctn) Z' 0 1.00 1109 0 1.00 1232 0 1.00 1540 0 1.00 1232 0.196 0.250 61850 2.46 12 1.00 2075 R (CM…Ctn) 1.00 1.00 1.00 Z' 1167 1297 1621 0 0 0 1297 2075 2075 2075 2075 1.00 1.0018 1.00 1.00 1.00 0.196 3.50 4650 2.46 1297 1.60 1.60 1.00 1.60 1.60 1.60 1.60 16 18 0 16 18 12 14 12 14 16 18 0.6D + 0.6W -5 225 -10 319 6 90.00 90.00 90.00 86.99 -14.27 86.90 -36.95 87.09 18.920.6D + 0.7E Rooftop Inverter Anchorage (#14 x 4" Screw) RH RV R a 0 -27 0 90.00 0 0 0 16 18 D + 0.75L + 0.75Lr D + 0.6W D + 0.7E D + 0.75(0.6W + L + Lr) D + 0.75(0.7E + L) -27 -27 -27 308 24087 2/18/25 D D + L D + Lr 0 0 CD 0.90 1.00 1.25 R'a 27 27 27 Waxie Santa Ana PV 27 309 19 225 17 320 19 18 1.00 1.00 0 16 18 12 14 16 18 Page 21 of 23 Project: Job No.: Date: WOOD CONNECTION DESIGN: WOOD SCREW CONNECTIONS [2018 NDS CHAPTERS 11 & 12] YIELD MODE II CD nconn D/C LC1 0.90 1 0.00 LC2 1.00 1 0.00 LC3 1.25 1 0.00 Re= Fem / Fes =LC4 1.00 1 0.00 Rt= lm / ls =LC5 1.60 1 0.02 k1=LC6 1.60 1 0.02 D=in LC7 1.60 1 0.01 ls=in LC8 1.60 1 0.02 Fes=psi LC9 1.60 1 0.02 Rd=LC10 1.60 1 0.02 Z=lbs LC6 0.02 YIELD MODE IIIm CD nconn D/C LC1 0.90 1 0.00 LC2 1.00 1 0.00 LC3 1.25 1 0.00 LC4 1.00 1 0.00 Re=LC5 1.60 1 0.02 Fyb=ksi LC6 1.60 1 0.02 D=in LC7 1.60 1 0.01 Fem=psi LC8 1.60 1 0.02 lm=in LC9 1.60 1 0.02 k2=LC10 1.60 1 0.02 Rd=LC6 0.02 Z=lbs YIELD MODE IIIs CD nconn D/C LC1 0.90 1 0.00 LC2 1.00 1 0.00 LC3 1.25 1 0.00 LC4 1.00 1 0.00 Re=LC5 1.60 1 0.04 Fyb=ksi LC6 1.60 1 0.05 D=in LC7 1.60 1 0.03 Fem=psi LC8 1.60 1 0.03 ls=in LC9 1.60 1 0.04 k3=LC10 1.60 1 0.05 Rd=LC6 0.05 Z=lbs 249 0 1.00 311 1.00 398 16 1.00 398 1.00 398 12 1.00 398 1.00 398 18 398 398 1.00 Z' 0 1.00 224 5.5751 2.46 249 R 0 0 18 14 18 0.0752 80 0.196 4650 0.25 1.00 249 16 1.00 867 18 1.00 867 18 867 867 12 1.00 867 14 1.00 867 677 0 1.00 542 16 1.00 867 Z' 0 1.00 487 0 1.00 542 0.4805 2.46 542 R (CM…Ctn) 0 1.00 18 1.00 16 1.00 0.0752 80 0.196 4650 3.50 857 18 1.00 857 18 857 857 12 1.00 857 14 1.00 857 669 0 1.00 535 16 1.00 857 Z' 0 1.00 482 0 1.00 535 61850 2.46 535 R (CM…Ctn) 0 1.00 18 1.00 16 1.00 0.0752 14.00 0.4345 0.196 0.250 Waxie Santa Ana PV 24087 2/18/25 (CM…Ctn) Page 22 of 23 Project: Job No.: Date: WOOD CONNECTION DESIGN: WOOD SCREW CONNECTIONS [2018 NDS CHAPTERS 11 & 12] YIELD MODE IV CD nconn D/C LC1 0.90 1 0.00 ns=LC2 1.00 1 0.00 D=in LC3 1.25 1 0.00 Fem=psi LC4 1.00 1 0.00 Fyb=ksi LC5 1.60 1 0.04 Re=LC6 1.60 1 0.05 Rd=LC7 1.60 1 0.03 Z=lbs LC8 1.60 1 0.04 LC9 1.60 1 0.04 LC10 1.60 1 0.05 LC6 0.05 WITHDRAWAL CD nconn D/C W = 2850 G 2D [NDS 18 12.2.2]LC1 0.90 1 -0.06 G =LC2 1.00 1 -0.06 CM 2…Ctn =LC3 1.25 1 -0.04 W =#/in.LC4 1.00 1 -0.06 D =in LC5 1.60 1 0.39 p =in LC6 1.60 1 -0.01 LC7 1.60 1 0.29 LC8 1.60 1 -0.01 LC9 1.60 1 0.41 LC10 1.60 1 0.01 LC9 0.41 COMBINED SHEAR AND WITHDRAWAL a D/C LC1 90.0 0.06 LC2 90.0 0.06 LC3 90.0 0.04 LC4 90.0 0.06 LC5 87.0 0.44 LC6 ####0.04 LC7 86.9 0.32 LC8 ####0.02 LC9 87.1 0.45 LC10 18.9 0.06 LC9 87.1 0.45 18 379 16 1.00 379 18 1.00 379 1.00 379 1 0.196 4650 80 0.0752 2.46 237 16 12 14 0 0 1.00 213 1.00 379 1.00 379 18 1.00 379 1.00 237 1.00 296 1.00 237 24087 2/18/25 Waxie Santa Ana PV (CM…Ctn) Z' 0.5 1.0 139.65 0.196 3.50 T W'p -27 440 -27 489 -27 611 -27 489 308 782 -5 782 782 -10 782 319 782 6 782 319 782 R'a W'p 225 R 0 0 Z' Z'a 27 440 213 440 27 489 237 489 27 611 296 611 27 489 237 489 309 782 379 707 19 782 379 447 225 782 379 705 17 782 379 748 320 782 379 709 19 782 379 344 320 782 379 709 Page 23 of 23 RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK R-002 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R RESOURCEDOCUMENT RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK R-003 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R RESOURCEDOCUMENT RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK R-004 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R RESOURCEDOCUMENT RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK R-005 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R RESOURCEDOCUMENT RE V SHEET TITLE DA T E DE S C R I P T I O N RE V I S I O N S SI G N A T U R E W I T H S E A L PR O J E C T N A M E & A D D R E S S DRAWN DATE DRAWN BY 04/02/2025 VA SHEET NUMBER REVIEWED BY NGK R-006 WA X I E S A N T A A N A 32 2 0 S F A I R V I E W S T , SA N T A A N A , C A 9 2 7 0 4 , US A A. 0 PE R M I T P L A N CONTRACTOR GREENTECH RENEWABLES PALOMAR SOLAR LTD 1526 STERLING COURT ESCONDIDO, CA 92029, USA PHONE NO- (760) 540-0388 LICENCE NO - C10-945152 04 / 0 2 / 2 0 2 5 NO T F O R C O N S T R U C T I O N U N L E S S S I G N E D B Y T H E CO N T R A C T O R O R S E A L E D B Y P R O F E S S I O N A L E N G I N E E R RESOURCEDOCUMENT 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. SPECIFIC NOTES AND DETAILS ON THE STRUCTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN OR NOTED IN ANY PART OF THE WORK THE DETAILS FOR OTHER SIMILAR WORK SHALL APPLY. DETAILS IDENTIFIED AS TYPICAL, SHALL APPLY IN ESTIMATING AND CONSTRUCTION TO EVERY LIKE CONDITION WHETHER OR NOT THE REFERENCE IS REPEATED. THE STRUCTURAL DRAWINGS SHALL NOT BE SCALED. COORDINATE DIMENSIONS WITH ARCHITECTURAL DRAWINGS. COORDINATE ELEVATIONS, SLOPES, AND DRAINAGE REQUIREMENTS WITH THE ARCHITECTURAL DRAWINGS. STANDARDS REFERENCED ON THE STRUCTURAL DRAWINGS REFER TO THE EDITION APPLICABLE UNDER THE CURRENT BUILDING CODE. THE RESPONSIBILITY FOR THE REVIEW AND COORDINATION OF DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF RELATED CONSTRUCTION SHALL BEAR ON THE CONTRACTOR. DISCREPANCIES THAT EXIST SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN A TIMELY MANNER, PRIOR TO THE START OF RELATED CONSTRUCTION. WORK PERFORMED IN CONFLICT WITH THE STRUCTURAL DRAWINGS OR APPLICABLE BUILDING CODE REQUIREMENTS SHALL BE CORRECTED AT THE EXPENSE OF THE CONTRACTOR. DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS SHALL BE VERIFIED BEFORE STARTING RELATED WORK AND THE ENGINEER NOTIFIED OF DISCREPANCIES IN A TIMELY MANNER. SITE CONDITIONS THAT ARE NOT REFLECTED ON THE STRUCTURAL DRAWINGS OR THAT DEVIATE FROM THE MAXIMUM OR MINIMUM DIMENSIONS INDICATED SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN A TIMELY MANNER. SUCH CONDITIONS MAY INCLUDE CONFLICT IN GRADES, ADVERSE SOIL CONDITIONS, GROUND WATER PRESENT, DEEPENED FOOTINGS, UNCOVERED AND UNEXPECTED UTILITY LINES, ETC. MATERIALS AND WORKMANSHIP SHALL CONFORM TO REQUIREMENTS OF APPLICABLE REGULATIONS AND THE BUILDING CODE AS AMENDED AND ADOPTED BY THE BUILDING OFFICIAL. LOADS TO THE BUILDING EXCEEDING THE LOADS INDICATED ON THE PLANS, OR ANY LOADS EXCEEDING 400 POUNDS THAT ARE NOT INDICATED ON THE STRUCTURAL DRAWINGS SHALL BE REPORTED TO THE ENGINEER. GENERAL 1. 2. 3. 4. 5. THE STRUCTURAL DESIGN HAS BEEN PERFORMED IN ACCORDANCE WITH THE 2022 CALIFORNIA BUILDING CODE (CBC) DESIGN LOADS (LIVE LOADS MAY BE REDUCED IN ACCORDANCE WITH THE BUILDING CODE) LL ROOF 20 psf SEISMIC DESIGN DATA : ASCE 7-16 RISK CATEGORY II SEISMIC IMPORTANCE FACTOR Ie 1.0 MAPPED SPECTRAL ACCELERATION SS 1.303 g MAPPED SPECTRAL ACCELERATION S1 0.468 g DESIGN SPECTRAL ACCELERATION SDS 1.042 g SITE CLASS D (DEFAULT) SEISMIC DESIGN CATEGORY D ANALYSIS PROCEDURE USED NONSTRUCTURAL COMPONENTS COMPONENT SEISMIC DESIGN DATA COMPONENT ap Rp SOLAR PV MODULES 1.0 1.5 OTHER ELECTRICAL COMPONENTS 2.5 6.0 WIND DESIGN DATA : ASCE 7-16 BASIC WIND SPEED V 95 mph EXPOSURE CATEGORY B ENCLOSURE CATEGORY ENCLOSED GUST & INTERNAL PRESSURE COEFF GCpi 0.18 DIRECTIONALITY FACTOR Kd 0.85 TOPOGRAPHIC FACTOR Kzt 1.00 BASIS OF DESIGN 1. 2. 3. THE STRUCTURAL DRAWINGS SHOW THE REQUIREMENTS FOR THE COMPLETED STRUCTURE ONLY. TEMPORARY WORKS REQUIRED TO COMPLETE THE CONSTRUCTION PROCESS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE DESIGN OR FIELD VERIFICATION OF TEMPORARY AND ANCILLARY WORK. THE RESPONSIBILITY FOR SAFETY IN AND AROUND THE JOBSITE SHALL BEAR ON THE CONTRACTOR. PROPER AND SAFE METHODS OF CONSTRUCTION SHALL BE EMPLOYED AT ALL TIMES INCLUDING THE STABILIZING OF INCOMPLETE STRUCTURES, FORMWORK, SHORING, RESHORING, FALSEWORK, PLATFORMS, SCAFFOLDING, BARRIERS, WALKWAYS, ETC, AND INCLUDING CONTROL OF THE INTENSITY, DURATION, AND LOCATION OF CONSTRUCTION LOADS. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON A STRUCTURE. LOADS SHALL NOT EXCEED THE DESIGN LIVE LOAD INDICATED. WHERE THE STRUCTURE HAS NOT ATTAINED FINAL DESIGN STRENGTH, ADEQUATE SHORING AND OR BRACING SHALL BE INSTALLED. TEMPORARY WORK AND SITE SAFETY 1.DUE TO THE SCOPE AND NATURE OF THIS PROJECT, STRUCTURAL OBSERVATION IS NOT REQUIRED. STRUCTURAL OBSERVATIONS 1. A. GENERAL: DUE TO THE SCOPE AND NATURE OF THIS PROJECT, SPECIAL INSPECTION IS NOT REQUIRED. SPECIAL INSPECTION PROGRAM 1. 2. 3. 4. 5. A. B. 6. A. B. C. D. 7. A. B. C. 8. 9. A. B. C. 10. STRUT CHANNELS AND FITTINGS SPECIFIED ON CONTRACT DRAWINGS SHALL BE MANUFACTURED BY UNISTRUT CORPORATION. SUBSTITUTIONS FOR PRODUCTS OF ALTERNATIVE MANUFACTURERS SHALL BE APPROVED BY THE ENGINEER. STRUT CHANNEL AND FITTING DESIGNATIONS ON CONTRACT DRAWINGS CORRESPOND TO PRODUCT DESIGNATIONS IN THE UNISTRUT GENERAL ENGINEERING CATALOG. WHERE SUBSTITUTIONS OF STRUT CHANNELS OR FITTINGS ARE REQUESTED, THE CONTRACTOR SHALL PROVIDE DOCUMENTATION DEMONSTRATING THAT THE PROPOSED STRUT CHANNEL OR COMPONENT MEETS OR EXCEEDS THE STRUCTURAL PROPERTIES AND ALLOWABLE DESIGN VALUES OF THE SPECIFIED STRUT CHANNEL OR COMPONENT. ALL STRUT CHANNELS AND COMPONENTS MUST BE SUPPLIED BY A SINGLE MANUFACTURER. CHANNELS AND COMPONENTS SHALL MEET THE REQUIREMENTS OF THE AMERICAN IRON AND STEEL INSTITUTE (AISI) SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS, 2007 EDITION. ALL CHANNEL MEMBERS SHALL BE FABRICATED FROM STRUCTURAL GRADE STEEL CONFORMING TO ONE OF THE FOLLOWING ASTM SPECIFICATIONS: A 1011 SS GR 33 A 653 GR 33 ALL FITTINGS SHALL BE FABRICATED FROM STEEL CONFORMING TO ONE OF THE FOLLOWING ASTM SPECIFICATIONS: A 575 A 576 A36 A 635 ALL STRUT CHANNEL MEMBERS AND COMPONENTS SHALL BE FINISHED WITH ONE OF THE FOLLOWING STANDARDS: ELECTRO-GALVANIZED (EG): ELECTROLYTICALLY ZINC COATED PER ASTM B 633 TYPE III SC 1 PRE-GALVANIZED (PG): ZINC COATED BY HOT-DIPPED PROCESS PRIOR TO ROLL FORMING. THE ZINC WEIGHT SHALL BE G90 CONFORMING TO ASTM A 653 HOT-DIPPED GALVANIZED (HG): ZINC COATED AFTER ALL MANUFACTURING OPERATIONS ARE COMPLETE. COATING SHALL CONFORM TO ASTM A 123 OR A 153 FIELD-CUTTING AND DRILLING OF STRUT CHANNELS SHALL BE MINIMIZED. STRUT CHANNELS WITH FACTORY-PUNCHED HOLES FOR FITTING CONNECTIONS SHALL BE USED WHERE DESIGNATED ON THE CONTRACT DRAWINGS AND WHERE HOLES OR SLOTS ARE ANTICIPATED BY THE CONTRACTOR. WHERE FIELD-CUTTING OR FIELD-DRILLING OF STRUT CHANNELS IS REQUIRED, SURFACES AFFECTED SHALL BE TREATED WITH A HIGH PERFORMANCE GALVANIZING PAINT AFTER FIELD-CUTTING OR FIELD- DRILLING IS PERFORMED. THE FOLLOWING GALVANIZING PRODUCTS ARE ACCEPTABLE: HIGH PERFORMANCE ZINC SPRAY, MANUFACTURED BY CLEARCO, INC. ZRC COLD GALVANIZING COMPOUND, MANUFACTURED BY ZRD WORLDWIDE, INC. SPRAYON SILVER GALVANIZING SPRAY, MANUFACTURED BY KRYLON, INC. ALTERNATE GALVANIZING PRODUCTS SHALL BE APPROVED BY THE ENGINEER PRIOR TO APPLICATION. FIELD-CUTTING OR FIELD-DRILLING OF CONNECTION COMPONENTS IS NOT ALLOWED. STRUT CHANNELS 3/8" Ø COUPLING NUT, GALV. (N) U-ANCHOR ROOF ATTACHMENT, MIN (2) PER INVERTER (N) UNISTRUT P3300 RAIL w/ SLOTTED HOLES, GALV., w/ 3/8" Ø BOLT, WASHER & NUT, MIN (2) PER INVERTER, TYP. M8-1.25 x 70mm BOLT, MIN (2) PER SUPPORT FOOT, TYP. SECTION VIEW X-X (E) ROOF SHEATHING (E) ROOF FRAMING PER PLAN PLAN VIEW (N) UNISTRUT P3300 RAIL w/ SLOTTED HOLES, GALV., MIN (2) PER INVERTER, TYP. (N) 3/8" Ø BOLT, WASHER & NUT, GALV., TYP. (N) U-ANCHOR ROOF ATTACHMENT, MIN (2) PER INVERTER X X (N) INVERTER PER ELECT. SHEET E600 [WT 185# MAX] 6" MAX 1" MIN, TYP. 6" MAX (E) ROOF FRAMING --- - AL L I D E A S , D E S I G N S A N D A R R A N G E M E N T S I N D I C A T E D O N T H E S E D R A W I N G S A R E T H E P R O P E R T Y O F T K J S T R U C T U R A L E N G I N E E R I N G , I N C . , A N D A R E IN T E N D E D T O B E U S E D I N C O N N E C T I O N W I T H T H I S S P E C I F I C P R O J E C T O N LY , A N D S H A L L N O T B E U S E D F O R A N Y O T H E R P U R P O S E W H A T S O E V E R W I T H OU T T H E W R I T T E N C O N S E N T O F T H E E N G I N E E R . DRAWN BY WA X I E S A N T A A N A SY S T E M S I Z E : 22 3 . 5 9 k W D C BAJ DATE: 3/ 1 3 / 2 0 2 5 1 : 2 2 : 3 2 P M S-1 STRUCTURAL NOTES & DETAILS 3/13/25 32 2 0 S F A I R V I E W S T SA N T A A N A , C A 9 2 7 0 4 24 0 8 7 6-30-25 S 4845 EXP. STRUCTURAL TIMOTHY KYLE JAQUESS STATE OF CALIFORNIA REG ISTEREDPROFESSIONALENGINEER 1 1/2" 1'-0" Equipment Anchorage - Rooftop Inverter 1 242' - 4 3/4"148' - 9" 50 ' - 2 " 12 3 ' - 2 " 29' - 3 5 / 8 " 411' - 1 3/4" (E) OFFICES (NOT IN SCOPE) 20' - 0"40' - 0" (TYP UNO) (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 3 1 - 1 / 2 " (E ) G L B 5 - 1 / 8 " x 2 8 - 1 / 2 " 20' - 0" (E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2"(E) GLB 3-1/8" x 22-1/2" ABCD 1 2 98 ' - 7 " (N) INV PER ELECTRICAL; SEE FOR MOUNTING DETAILS (N) INV PER ELECTRICAL; SEE FOR MOUNTING DETAILS /1 S-1 /1 S-1 12 ' - 0 " + / - 6 " 40'-0" +/- 6" 22 ' - 6 " + / - 6 " 23 ' - 0 " + / - 6 " 25'-0" +/- 6" 7' - 0 " M I N 17'-3" +/- 6" LEGEND (E) 2x ROOF SUB-PURLIN PER SCHED TO REMAIN (E) ROOF FRAMING PER SCHED TO REMAIN (N) HANWHA Q CELLS Q.TRON BLK M-G2+ (425W) MODULES (514) TO BE INSTALLED ON BALLASTED UNIRAC RMDT RACKING PER PV DRAWINGS (E) SKYLIGHT AL L I D E A S , D E S I G N S A N D A R R A N G E M E N T S I N D I C A T E D O N T H E S E D R A W I N G S A R E T H E P R O P E R T Y O F T K J S T R U C T U R A L E N G I N E E R I N G , I N C . , A N D A R E IN T E N D E D T O B E U S E D I N C O N N E C T I O N W I T H T H I S S P E C I F I C P R O J E C T O N LY , A N D S H A L L N O T B E U S E D F O R A N Y O T H E R P U R P O S E W H A T S O E V E R W I T H OU T T H E W R I T T E N C O N S E N T O F T H E E N G I N E E R . DRAWN BY WA X I E S A N T A A N A SY S T E M S I Z E : 22 3 . 5 9 k W D C BAJ DATE: 3/ 1 3 / 2 0 2 5 1 : 2 2 : 3 3 P M S-2 ROOF FRAMING PLAN 3/13/25 32 2 0 S F A I R V I E W S T SA N T A A N A , C A 9 2 7 0 4 24 0 8 7 1/16" 1'-0" Roof Framing Plan 1 6-30-25 S 4845 EXP. STRUCTURAL TIMOTHY KYLE JAQUESS STATE OF CALIFORNIA REG ISTEREDPROFESSIONALENGINEER U-BUILDER PROJECT REPORT APPLICATION VERSION: 6.7.2 PROJECT VERSION: 0.0.63 PROJECT TITLE ROOFMOUNT RMDT PROJECT ID A77DF4B6 LAST UPDATED Apr. 1, 2025 ORIGINALLY CREATED Mar. 12, 2025 NAME Waxie ADDRESS 3220 S Fairview St Santa Ana, CA CITY, STATE Santa Ana, CA MODULE QCells Q.TRON BLK M-G2+/AC 435W Designed by goncalogloria84@gmail.com ROOFMOUNT RMDT QCells 514 - Q.TRON BLK M-G2+/AC 435W 12190 ft 223.59 KW 2 NOTE: Installation of the project is intended to happen within the year of project designed in UBuilder. If it's past one year please rerun the design or contact Unirac Engineering Services. Page 1 of 19 INSTALLATION AND DESIGN PLAN Roof Area 1 Page 6 of 43 Roof Area 1 - Array 1 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 8 9 14 448.0 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. NS DIMENSION ~ 39.68 ft EW DIMENSION ~ 33.27 ft Page 7 of 43 2 8 9 12 384.0 3 8 9 10 320.0 4 8 9 12 384.0 5 6 9 14 448.0 6 6 7 12 384.0 7 6 7 9 288.0 8 0 7 11 352.0 Roof Area 1 - Array 2 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. Page 8 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 8 9 13 416.0 2 8 9 9 288.0 3 8 9 9 288.0 4 8 9 9 288.0 5 6 9 11 352.0 6 6 7 13 416.0 7 6 7 9 288.0 8 0 7 11 352.0 Roof Area 1 - Array 3 NS DIMENSION ~ 39.68 ft EW DIMENSION ~ 33.27 ft Page 9 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 10 11 17 544.0 2 10 11 14 448.0 3 10 11 13 416.0 4 10 11 15 480.0 5 6 11 18 576.0 6 6 7 11 352.0 7 6 7 10 320.0 8 0 7 11 352.0 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. NS DIMENSION ~ 39.68 ft EW DIMENSION ~ 41.44 ft Page 10 of 43 Roof Area 1 - Array 4 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. Page 11 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 6 7 13 416.0 2 6 7 7 224.0 3 6 7 13 416.0 4 6 7 14 448.0 5 6 7 10 320.0 6 6 7 13 416.0 7 6 7 10 320.0 8 6 7 10 320.0 9 0 7 11 352.0 NS DIMENSION ~ 45.35 ft EW DIMENSION ~ 25.10 ft Page 12 of 43 Roof Area 1 - Array 5 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. Page 13 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 6 7 13 416.0 2 6 7 7 224.0 3 6 7 13 416.0 4 6 7 14 448.0 5 6 7 10 320.0 6 6 7 13 416.0 7 6 7 10 320.0 8 6 7 10 320.0 9 0 7 11 352.0 NS DIMENSION ~ 45.35 ft EW DIMENSION ~ 25.10 ft Page 14 of 43 Roof Area 1 - Array 6 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. Page 15 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 4 5 9 288.0 2 4 5 9 288.0 3 4 5 9 288.0 4 4 5 9 288.0 5 4 5 9 288.0 6 4 5 11 352.0 7 4 5 11 352.0 8 4 5 5 160.0 9 0 5 9 288.0 NS DIMENSION ~ 45.35 ft EW DIMENSION ~ 16.93 ft Page 16 of 43 Roof Area 1 - Array 7 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. Page 17 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 6 7 13 416.0 2 6 7 7 224.0 3 6 7 13 416.0 4 6 7 14 448.0 5 6 7 10 320.0 6 6 7 13 416.0 7 6 7 10 320.0 8 6 7 10 320.0 9 0 7 13 416.0 NS DIMENSION ~ 45.35 ft EW DIMENSION ~ 25.10 ft Page 18 of 43 Roof Area 1 - Array 8 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. Page 19 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 6 7 13 416.0 2 6 7 7 224.0 3 6 7 13 416.0 4 6 7 14 448.0 5 6 7 10 320.0 6 6 7 13 416.0 7 6 7 10 320.0 8 6 7 10 320.0 9 0 7 13 416.0 NS DIMENSION ~ 45.35 ft EW DIMENSION ~ 25.10 ft Page 20 of 43 Roof Area 1 - Array 9 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. Page 21 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 4 5 9 288.0 2 4 5 9 288.0 3 4 5 9 288.0 4 4 5 9 288.0 5 4 5 9 288.0 6 4 5 11 352.0 7 4 5 11 352.0 8 4 5 5 160.0 9 0 5 9 288.0 Roof Area 1 - Array 10 NS DIMENSION ~ 45.35 ft EW DIMENSION ~ 16.93 ft Page 22 of 43 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 6 7 11 352.0 2 6 7 7 224.0 3 6 7 13 416.0 4 6 7 13 416.0 5 6 7 7 224.0 6 0 7 11 352.0 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. NS DIMENSION ~ 28.33 ft EW DIMENSION ~ 25.10 ft Page 23 of 43 Roof Area 1 - Array 11 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 6 7 11 352.0 2 6 7 8 256.0 3 6 7 10 320.0 4 6 7 9 288.0 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. NS DIMENSION ~ 28.33 ft EW DIMENSION ~ 25.10 ft Page 24 of 43 5 6 7 8 256.0 6 0 7 11 352.0 Roof Area 1 - Array 12 Layout Dimensions ROW MODULES BAYS BALLAST BLOCKS (CMU)BALLAST WEIGHT (LBS) 1 8 9 13 416.0 2 8 9 11 352.0 LEGEND Module 1 Standard corner bay with CMU block count 4 Supplemental bay with CMU block count NOTE Bays in the space beside modules are supplemental bays. You can fit a maximum of 2 blocks in valley bays, and 5 blocks in ridge bays. If the number in these bays is greater, you will need to add an additional supplemental bay. NS DIMENSION ~ 28.33 ft EW DIMENSION ~ 33.27 ft Page 25 of 43 3 8 9 12 384.0 4 8 9 10 320.0 5 8 9 11 352.0 6 0 9 13 416.0 Page 26 of 43 Roof Area 1 - Array 1 AVERAGE PSF 4.91 psf TOTAL NUMBER OF MODULES 50 ROW SPACING 0.3" TOTAL KW 21.75 KW TOTAL AREA 1182 ft TOTAL WEIGHT ON ROOF 5805 lbs RACKING WEIGHT 462 lbs MODULE WEIGHT 2335 lbs BALLAST WEIGHT 3008 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 27 of 43 Roof Area 1 - Array 2 AVERAGE PSF 4.64 psf TOTAL NUMBER OF MODULES 50 ROW SPACING 0.3" TOTAL KW 21.75 KW TOTAL AREA 1182 ft TOTAL WEIGHT ON ROOF 5485 lbs RACKING WEIGHT 462 lbs MODULE WEIGHT 2335 lbs BALLAST WEIGHT 2688 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 28 of 43 Roof Area 1 - Array 3 AVERAGE PSF 4.92 psf TOTAL NUMBER OF MODULES 58 ROW SPACING 0.3" TOTAL KW 25.23 KW TOTAL AREA 1367 ft TOTAL WEIGHT ON ROOF 6730 lbs RACKING WEIGHT 534 lbs MODULE WEIGHT 2709 lbs BALLAST WEIGHT 3488 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 29 of 43 Roof Area 1 - Array 4 AVERAGE PSF 5.19 psf TOTAL NUMBER OF MODULES 48 ROW SPACING 0.3" TOTAL KW 20.88 KW TOTAL AREA 1139 ft TOTAL WEIGHT ON ROOF 5912 lbs RACKING WEIGHT 438 lbs MODULE WEIGHT 2242 lbs BALLAST WEIGHT 3232 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 30 of 43 Roof Area 1 - Array 5 AVERAGE PSF 5.19 psf TOTAL NUMBER OF MODULES 48 ROW SPACING 0.3" TOTAL KW 20.88 KW TOTAL AREA 1139 ft TOTAL WEIGHT ON ROOF 5912 lbs RACKING WEIGHT 438 lbs MODULE WEIGHT 2242 lbs BALLAST WEIGHT 3232 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 31 of 43 Roof Area 1 - Array 6 AVERAGE PSF 5.72 psf TOTAL NUMBER OF MODULES 32 ROW SPACING 0.3" TOTAL KW 13.92 KW TOTAL AREA 768 ft TOTAL WEIGHT ON ROOF 4395 lbs RACKING WEIGHT 309 lbs MODULE WEIGHT 1494 lbs BALLAST WEIGHT 2592 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 32 of 43 Roof Area 1 - Array 7 AVERAGE PSF 5.25 psf TOTAL NUMBER OF MODULES 48 ROW SPACING 0.3" TOTAL KW 20.88 KW TOTAL AREA 1139 ft TOTAL WEIGHT ON ROOF 5976 lbs RACKING WEIGHT 438 lbs MODULE WEIGHT 2242 lbs BALLAST WEIGHT 3296 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 33 of 43 Roof Area 1 - Array 8 AVERAGE PSF 5.25 psf TOTAL NUMBER OF MODULES 48 ROW SPACING 0.3" TOTAL KW 20.88 KW TOTAL AREA 1139 ft TOTAL WEIGHT ON ROOF 5976 lbs RACKING WEIGHT 438 lbs MODULE WEIGHT 2242 lbs BALLAST WEIGHT 3296 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 34 of 43 Roof Area 1 - Array 9 AVERAGE PSF 5.72 psf TOTAL NUMBER OF MODULES 32 ROW SPACING 0.3" TOTAL KW 13.92 KW TOTAL AREA 768 ft TOTAL WEIGHT ON ROOF 4395 lbs RACKING WEIGHT 309 lbs MODULE WEIGHT 1494 lbs BALLAST WEIGHT 2592 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 35 of 43 Roof Area 1 - Array 10 AVERAGE PSF 5.17 psf TOTAL NUMBER OF MODULES 30 ROW SPACING 0.3" TOTAL KW 13.05 KW TOTAL AREA 712 ft TOTAL WEIGHT ON ROOF 3677 lbs RACKING WEIGHT 292 lbs MODULE WEIGHT 1401 lbs BALLAST WEIGHT 1984 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 36 of 43 Roof Area 1 - Array 11 AVERAGE PSF 4.94 psf TOTAL NUMBER OF MODULES 30 ROW SPACING 0.3" TOTAL KW 13.05 KW TOTAL AREA 712 ft TOTAL WEIGHT ON ROOF 3517 lbs RACKING WEIGHT 292 lbs MODULE WEIGHT 1401 lbs BALLAST WEIGHT 1824 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 37 of 43 Roof Area 1 - Array 12 AVERAGE PSF 4.76 psf TOTAL NUMBER OF MODULES 40 ROW SPACING 0.3" TOTAL KW 17.40 KW TOTAL AREA 943 ft TOTAL WEIGHT ON ROOF 4487 lbs RACKING WEIGHT 379 lbs MODULE WEIGHT 1868 lbs BALLAST WEIGHT 2240 lbs 2 MINIMUM SEISMIC SEPARATION (UNATTACHED ARRAYS) * ARRAY TO ARRAY:12.4" TO FIXED OBJECT ON ROOF:24.8" TO ROOF EDGE WITH QUALIFYING PARAPET:24.8" TO ROOF EDGE WITHOUT QUALIFYING PARAPET:49.5" MAX ARRAY (SEISMIC) (FOR UNATTACHED ARRAYS) * MAX NUMBER OF NORTH-SOUTH ROWS:9 MAX NUMBER OF EAST-WEST COLUMNS:11 *See ASCE 7-16 Section 13.6.12 for more details Page 38 of 43 WIND DESIGN DETAIL Terrain Category B Section 26.7 (ASCE 7-16) Basic Wind Speed 95.00 mph Elevation 40.00 ft Risk Category II Table 1.5‐1 (ASCE 7-16) Mean Roof Height 30.0 ft Numerical Coefficient 0.002560 Section C26.10.2 (ASCE 7-16) Topographic Factor, K 1.00 Section 26.8.2 (ASCE 7-16) Wind Directionality Factor, K 0.85 Table 26.6-1 (ASCE 7-16) Ground Elevation Factor, K 0.999 Table 26.9-1 (ASCE 7-16) Velocity Pressure Exposure Coefficient, K 0.70 Table 26.10-1 (ASCE 7-16) Design Life Factor , f 1.0000 Velocity Pressure at Height, Q 13.74 psf Equation 26.10.1 (ASCE 7-16) Design Life Velocity Pressure, Q = Q x f 13.74 psf Equation C26.5-4 (ASCE 7-16) zt d e z 2 c2 h z h c2 Page 39 of 43 CLAMPS LOCATIONS AND MAX MODULE PRESSURES Page 40 of 43 NOTE : 1. SUPPLEMENTAL BAYS ARE PLACED SYMMETRIC TO THE MODULE 2. EDGE CANTILEVER DISTANCE TO CLAMP AT VALLEY BAY (Ve ) = 2.39" APPROX 3. EDGE CANTILEVER DISTANCE TO CLAMP AT SHARED VALLEY BAY (Vm ) = 7.19" APPROX 4. EDGE CANTILEVER DISTANCE TO CLAMP AT RIDGE BAY (Re ) = 2.85" APPROX 5. EDGE CANTILEVER DISTANCE TO CLAMP AT SHARED RIDGE BAY (Rm ) = 10.00" APPROX FACTORED MAX UPWARD PRESSURE ON MODULE : 4.95 psf FACTORED MAX DOWNWARD PRESSURE ON MODULE : 7.19 psf LEGEND Module Primary bay Supplemental bay Ridge bay End Clamp Mid Clamp Page 41 of 43 RMDT U-BUILDER PRODUCT ASSUMPTIONS RMDT – Ballasted Flat Roof Systems Limitations of Responsibility: It is the user’s responsibility to ensure that inputs are correct for your specific project. Unirac is not the solar, electrical, or building engineer of record and is not responsible for the solar, electrical, or building design for this project. Building Assumptions 1. Risk Category I - IV 2. Building Height ≤ 100.00 ft 3. Building Height > 50.00 ft: only where (longest length of building x building height)^0.5 ≤ 100.00 ft 4. Roof Slope ≥ 0° (0:12) and ≤ 3° (5/8:12) for Seismic Design Category C, D, E and F. For low seismic regions Seismic Design Category A and B (provided Array Importance factor = 1.0), Roof Slope ≥ 0° (0:12) and ≤ 7° (1 1/2:12). 5. Roofing Material Types: EDPM, PVC, TPO, or Mineral Cap 6. Surrounding Building Grade: Level Ballast Blocks The installer is responsible for procuring the ballast blocks (Concrete Masonry Units – CMU) and verifying the required minimum weight needed for this design. CMU should comply with ASM standard specification for concrete roof pavers designation (C1491 or C90 with an integral water repellant suitable for the climate it is placed. It is recommended that the blocks are inspected periodically for any signs of degradation. If degradation of the block is observed, the block should immediately be replaced. The CMU ballast block should have nominal dimensions of 4.00" x 8.00" x 16.00". The actual block dimensions are 0.37" less than the nominal dimensions. Ballast blocks should have a weight as specified for the project in the “Inspection” section of this report. Design Parameters 1. Risk Category I to IV 2. Wind Design a. Basic Wind Speed: 110.00 mph - 150.00 mph (ASCE 7-10)/90.00 mph - 180.00 mph (ASCE 7-16/ASCE 7-22) b. Exposure: B or C (ASCE 7-10/ASCE 7-16/ASCE 7-22) c. 25 year Design Life/50 year Design Life for ASCE 7-16/ASCE 7-22 d. Elevation: Insertion of the project at - grade elevation can result in a reduction of wind pressure. If your project is in a special case study region or in an area where wind studies have been performed, please verify with your jurisdiction to ensure that elevation effects have not already been factored into the wind speed. If elevation effects have been included in your wind speed, please select 0.00 ft as the project site elevation. e. Wind Tunnel Testing: Wind tunnel testing coefficients have been utilized for design of the system. 3. Snow Design a. Ground Snow Load: 0 - 80.00 psf(ASCE 7-10/ASCE 7-16/ASCE 7-22) b. Exposure Factor: 0.9 c. Thermal Factor: 1.2 d. Roof Snow Load: Calculation per Section 7.3 (ASCE 7-10/ASCE 7-16/ASCE 7-22) e. Unbalanced/Drifting/Sliding: Results are based on the uniform snow loading and do not consider unbalanced, drifting, and sliding conditions 4. Seismic Design a. Report SEAOC PV1-2012/ASCE 7-16/ASCE 7-22 SECTION 13.6.12 – Structural Seismic Requirements and Commentary for Rooftop Solar Photovoltaic Arrays b. Seismic Site Class: A, B, C, or D (ASCE 7-10/ASCE 7-16/ASCE 7-22) c. Importance Factor Array (lp): 1.0 d. Importance Factor Building (le): 1.0 e. Site Class: D Properties 1. Ridge Bay Weight: 7.70 lbs 2. Valley Bay Weight: 5.60 lbs 3. Module Gaps (N/S) = 0.25" 4. Bays: East and west column bays overhang the module by ~7.90". Testing 1. Coefficient of Friction 2. Wind Tunnel 3. UL 2703 4. Component Testing (Bay and Clamp) Page 42 of 43 Setbacks For the wind tunnel recommendations in U-Builder to apply, the following setbacks should be observed/followed for U-Builder wind design: 1. Modules should be placed a minimum of 3.00 ft from the edge of the building in any direction. 2. If the array is located near an obstruction that is 3.50 ft wide and 3.50 ft high or larger, the nearest module of the array must be located a distance from the obstruction that is greater than or equal to the height of the obstruction. Exception: When using ASCE 7-16/ASCE 7-22 Building Code and using the obstruction feature in the module editor to accurately model the size and location of obstruction. 3. Installations within the setbacks listed above require site specific engineering 4. The setbacks above are for wind. High seismic areas, fire access isles, mechanical equipment, etc., may require larger setbacks than listed above for wind. Site Specific Engineering Conditions listed below are beyond the current capabilities of U-Builder. Site specific engineering is required. 1. Building assumptions and design parameters outside of U-Builder assumptions 2. Risk Category IV projects 3. Wind tunnel testing reduction factors are not permitted by the Authority Having Jurisdiction (AHJ) 4. Seismic designs that fall outside SEAOC PV1-2012/ASCE 7-16/ASCE 7-22 SECTION 13.6.12 recommendations (>3% roof slope, or AHJ’s that require shake table testing or non-linear site-specific response history analysis) 5. Signed and sealed site-specific calculations, layouts, and drawings 6. Building that is not enclosed and categorized as open structures, carport or others Notes: Please contact EngineeringServices@unirac.com for more information. Page 43 of 43