HomeMy WebLinkAbout3101 & 3121 W Adams St - PlanElect #'s 20186072 & 20185854
APPROVALS:
PLNG - C. SantanaELECT - M. Smith
N
N
(ITV OF SAKITA ANA
[E] UTILITY
TRANSFORMER
T
ELECTRICAL NOTES
(N) CHARGEPILOT FM�
METER KIT
[E] UTILITY METER
[E] 400AT 3P MAIN
DISCONNECT
10000
ELECTRICAL DIAGRAM
RACEWAY AND CONDUCTOR SCHEDULE
WIRE
TAG
NO. OF
SETS
RACEWAY
MINIMUM
CONDUCTORS PER SET
PHASE
NEUTRAL
GROUND
1
1 1 /4" C.
(3) #3 AWG THHN/THWN-2 CU
(1) #3 AWG THHN/THWN-2 CU
(1) #8 AWG THHN/THWN-2 CU
❑2
1
2 1 /2" C.
(3) #4/0 AWG THHN/THWN-2 CU
(1) #4/0 AWG THHN/THWN-2 CU
(1) #2 AWG THHN/THWN-2 CU
*ALL CONDUCTORS ARE WITH TERMINATION TEMP RATING OF 75 DEG C AND INSULATION TEMP RATING OF 90 DEG C
*CONDUCTOR AMPACITY BASED ON NEC TABLE 310-16 CALCULATED WITH ADJUSTMENTS FOR AMBIENT TEMPERATURE OR VOLTAGE DROP.
(E) MAIN DISTRIBUTION PANEL
480Y/277V, 3 PHASE, 400A
[N] 100AT rA 11 9 nn AT rr1 A n AT rr-I -1nn AT _ rr1 -7n AT _ rrl -1 C! (-N A7
3P BKR
[N] FUSED DISCONNECT
90AF/10OAS
[N] XFMR 'EV1'
75 IVA
480V-120/208V
3�, 4W
N
PANEL
'EV1'
120/208V
*REFER TO SHEET E-2 FOR THE
ENLARGED EVSE DIAGRAM
LOAD DEMAND
METER NO. 259000-066643
DATE
PEAK DEMAND (KW)
�
o
N
MAY
13
JUNE
14
JULY
14
AUGUST
16
SEPTEMBER
14
OCTOBER
13
NOVEMBER
13
LlvJ i vvmi
3P BKR
L�J
3P
-rum'
BKR
L�J
3P
i uumI
BKR
L�J
3P
i um
BKR
L'-J
3P
i .)vmi
BKR
IF
T O
E X
IF
I S T I N G
IF
B U I L D I
N G
IF
L 0 A D
S
[N] FUSED DISCONNECT
90AF/100AS
[N] XFMR 'EV2'
75 kVA
480V-120/208V
3�, 4W
N
PANEL
'LV2,
120/208V
*REFER TO SHEET E-3 FOR THE
ENLARGED EVSE DIAGRAM
LOAD SUMMARY FOR MAIN SWITCHBOARD
12 MONTH PEAK DEMAND
16 KW
POWER FACTOR
0.9
APPARENT POWER PEAK
17.78 KVA
APPARENT POWER PEAK 125%
22.22 KVA
OPERATING VOLTAGE
480.00 V
EXISTING TOTAL CURRENT g 125%, 480V
46.30 A
APPARENT POWER FROM (N) EVSE g 125%
162.00 KVA
PEAK CURRENT FROM (N) EVSE 480V
194.86 A
TOTAL CURRENT AT MAIN SWITCHBOARD
241.16 A
AVAILABLE REMAINING CURRENT AT MAIN SWITCHBOARD'400A'
158.84 A
1. ALL ELECTRICAL WORKS AND INSTALLATIONS SHALL COMPLY WITH THE PROVISIONS OF THE NATIONAL ELECTRICAL CODE WITH THE RULES AND REGULATIONS OF THE LOCAL AUTHORITIES CONCERNED IN
THE REINFORCEMENT OF THE ELECTRICAL LAWS AND ORDINANCES AND WITH THE REGULATIONS OF THE UTILITY COMPANY CONCERNED.
2. ALL MATERIALS AND EQUIPMENT SHALL BE THE APPROVED TYPE FOR BOTH LOCATION AND PURPOSE INTENDED. THESE SHALL BE FREE OF DEFECTS AND ARE APPROPRIATELY LISTED FOR ITS USE.
3. ALL (N) EQUIPMENT SHALL BE PLACED WITH CONSIDERATION TO EXISTING CONDITIONS AND FEATURES.
4. ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS OTHERWISE NOTED, AND SHALL BE PROPERLY IDENTIFIED.
5. PER NEC 625.42, THE TOTAL LOAD ON THE MAIN DISTRIBUTION PANEL WILL BE LIMITED TO 320A USING THE AUTOMATED LOAD MANAGEMENT SYSTEM AND ASSOCIATED METERING DEVICES.
I gQTidI IfdI V
NAME:
REVOLV (SANTA ANA)
3DDRE ACl
pt�IS rT0VNTA NA,
FORPFRMIT ISSUANC
SHEET CATALOG
S
DESCRIPTION
T-1
COVER PAGE
S-1� TO 2
SITE PLAN
E-4
COND. CALCS
E-5
LOAD CALCS
SS-1 TO 2
SPECS SHEET
C10-614779
BOBBY PENN
MASTER ELECTRICIAN}
REVISION
REV NO.
DESCRIPTION
DATE
Q
UPDATED ADA NOTE
04/20/25
Q
UPDATED THE SITE PLAN TO
05/27/25
INDICATE CORRECT ADDRESS FOR
PROPERTY 3121 AND THE LEGAL
PROPERTY LINES
Q
UPDATED LINE DIAGRAM TO
05/27/25
REFLECT DETAILED GROUNDING
SYSTEM
CITY STAMP
gop-o
COIL
COIL INC.
1307 HAYES ST. SUITE 5
SAN FRANCISCO, CA 94117
CALIFORNIA LICENSE 814779
ELEC DIAGRAM
SCALE: AS NOTED
DESIGNED BY: COIL INC
SHEET NO.
DATE DRAWN: MAY 27 2025
C
C —
PAPER SIZE: 18"x24"
REV C
=Y
G
N
G
G
N
G
("ITV QF gAKITA AnlA
TAG 1
FROM (E) MAIN DISTRIBUTION PANEL TO (N) AC DISCONNECT
CONDUCTOR AND CONDUIT CALCULATIONS
TAG 2
FROM (N) XFMR EV1/EV2 TO (N) PANEL EVl/EV2
TAG3
FROM (I) PANEL EVI/EV2 TO (N) EVCS
CONDUCTOR SIZING:
CONDUCTOR SIZING-
CONDUCTORSIZING:
ADJUSTED AMPACITY =
(CONDUCTOR AMPACITY @ 90 DEG)[PER TABLE 310.15(B)(16)]
ADJUSTED AMPACITY =
(CONDUCTOR AMPACITY @ 90 DEG)[PER TABLE 310.15(B)(16)]
ADJUSTED AMPACITY =
(CONDUCTOR AMPACITY @ 90 DEG)[PER TABLE 310.15(B)(16)]
X (BUNDLING ADJUSTMENT FACTOR)[PER TABLE 310.15(B)(3)(A)1
X (BUNDLING ADJUSTMENT FACTOR)[PER TABLE 310.15(B)(3)(A)1
X (BUNDLING ADJUSTMENT FACTOR)[PER TABLE 310.15(B)(3)(A)]
X (AMBIENT TEMP CORRECTION FACTOR)[PER TABLE 310.15(B)(2)(A)]
X (AMBIENT TEMP CORRECTION FACTOR)[PER TABLE 310.15(B)(2)(A)]
X (AMBIENT TEMP CORRECTION FACTOR)[PER TABLE 310.15(B)(2)(A)]
=
115 AMPS X I X 1
=
260 AMPS X 1 X 1
=
130 AMPS X 0.8 X I
=
115 AMPS
=
260 AMPS
=
104 AMPS
115 AMPS > 100 AMPS
260 AMPS > 230 AMPS
104 AMPS < 115 AMPS
(ALLOWED AMPACITY FOR 75 DEG RATED TERMINALS)
(ALLOWED AMPACITY FOR 75 DEG RATED TERMINALS)
(ALLOWED AMPACITY FOR 75 DEG RATED TERMINALS)
TOTAL AMPACITY =
(ADJUSTED CONDUCTOR AMPACITY) X (NO. OF PARALLEL SETS)
TOTAL AMPACITY =
(ADJUSTED CONDUCTOR AMPACITY) X (NO. OF PARALLEL SETS)
TOTAL AMPACITY =
(ADJUSTED CONDUCTOR AMPACITY) X (NO. OF PARALLEL SETS)
=
100 AMPS X 1
=
230 AMPS X 1
=
104 AMPS X 1
=
100 AMPS
=
230 AMPS
=
104 AMPS
FEEDER CURRENT AND OCPD RATING:
FE®ER CURRENT AND OCPD RATING:
FEEDER CURRENT AND OCPD RATING:
OCPD RATING =
(TOTAL CURRENT) X 125%
OCPD RATING =
(TOTAL CURRENT) X 125%
OCPD RATING =
(TOTAL CURRENT) X 125%
=
80 AMPS X 125%
=
180 AMPS X 125%
=
80 AMPS X 125%
=
100 AT
=
225 AT
=
100 AT
MINIMUM OCPD SIZE =
100 AT
MINIMUM OCPD SIZE =
225 AT
MINIMUM OCPD SIZE =
100 AT
MINIMUM WIRE SIZE =
3 AWG THHN, THWN, THWN-2 COPPER
MINIMUM WIRE SIZE =
4/0 AWG THHN, THWN, THWN-2 COPPER
MINIMUM WIRE SIZE =
2 AWG THHN, THWN, THWN-2 COPPER
MINIMUM GROUNDING COND. =
8 AWG THHN, THWN, THWN-2 COPPER
MINIMUM GROUNDING COND. =
4 AWG THHN, THWN, THWN-2 COPPER
MINIMUM GROUNDING COND. =
8 AWG THHN, THWN, THWN-2 COPPER
VOLTAGE DROP:
VOLTAGE DROP:
VOLTAGEDROP:
CIRCUIT RESISTANCE =
(RESISTANCE PER UNIT LENGTH)[CH9 TABLE 91 X (ONE WAY LENGTH)
CIRCUIT RESISTANCE =
(RESISTANCE PER UNIT LENGTH)[CH9 TABLE 91 X (ONE WAY LENGTH)
CIRCUIT RESISTANCE =
(RESISTANCE PER UNIT LENGTH)[CH9 TABLE 91 X (ONE WAY LENGTH)
X (EFFECTIVE NUMBER OF CONDUCTORS)
X (EFFECTIVE NUMBER OF CONDUCTORS)
X (EFFECTIVE NUMBER OF CONDUCTORS)
=
0.25 OHMS/KFT X 256 FT X 1.73
=
0.062 OHMS/KFT X 20 FT X 1.73
=
0.19 OHMS/KFT X 130 FT X 2.00
=
0.1109 OHMS
=
0.0021 OHM S
=
0.0494 OHMS
VOLTAGE DROP =
(CIRCUIT DISTANCE) X (OPERATING CURRENT)
VOLTAGE DROP =
(CIRCUIT DISTANCE) X (OPERATING CURRENT)
VOLTAGE DROP =
(CIRCUIT DISTANCE) X (OPERATING CURRENT)
=
0.1109 OHMS X 80 AMPS
=
0.0021 OHMS X 180 AMPS
=
0.0494 OHMS X 80 AMPS
=
8.8681 VOLTS
=
0.3866 VOLTS
=
3.9520 VOLTS
VOLTAGE DROP (%) =
1.8475 %
VOLTAGE DROP (%) =
0.1859 %
VOLTAGE DROP (%) =
1.9000 %
CONDUIT SIZING-
CONDUIT SIZING:
CONDUIT SIZING:
CONDUIT TYPE =
PVC-40
CONDUIT TYPE =
PVC-40
CONDUIT TYPE =
PVC-40
CONDUIT TRADE SIZE =
1 1/4 IN
CONDUIT TRADE SIZE =
2 1/2 IN
CONDUIT TRADE SIZE =
1 1/2 IN
AREA OF PHASE CONDUCTORS =
0.2919 IN^2
AREA OF PHASE CONDUCTORS =
0.9711 IN^2
AREA OF PHASE CONDUCTORS =
0.4632 IN^2
AREA OF NEUTRAL CONDUCTOR =
0.0973 IN^2
AREA OF NEUTRAL CONDUCTOR
0.3237 IN^2
AREA OF NEUTRAL CONDUCTOR =
0 IN^2
AREA OF GROUND CONDUCTOR =
0.0366 IN^2
AREA OF GROUND CONDUCTOR =
0.0824 IN^2
AREA OF GROUND CONDUCTOR =
0.0366 IN^2
TOTAL AREA OF CONDUCTORS =
0.4258 IN^2
TOTAL AREA OF CONDUCTORS =
1.3772 IN^2
TOTAL AREA OF CONDUCTORS =
0.4998 IN^2
AREA OF CONDUIT =
1.453 IN^2
AREA OF CONDUIT =
4.695 IN^2
AREA OF CONDUIT =
1.986 IN^2
CONDUIT FILL RATIO =
29.3049 %
CONDUIT FILL RATIO =
29.3333 %
CONDUIT FILL RATIO =
25.1662 %
I a9fflidgG-h d OW Id V4 VW n
NAME:
REVOLV (SANTA ANA)
3D2READ MS rSTOVT#NA,
F(DR2PFRMIT ISSUANC
SHEET CATALOG
lgag11H..
DESCRIPTION
T-1
COVER PAGE
S-1: TO 2
SITE PLAN
IDIAGRAM
E-4
COND. CALCS
E-5
LOAD CALCS
SS-1 TO 2
SPECS SHEET
C10-814779
s
BOBBY PENN
MASTER ELECTRICIAN
REVISION
REV NO.
DESCRIPTION
DATE
Q
UPDATED ADA NOTE
04/20/25
Qz
UPDATED THE SITE PLAN TO
05/27/25
INDICATE CORRECT ADDRESS FOR
PROPERTY 3121 AND THE LEGAL
PROPERTY LINES
Q
UPDATED LINE DIAGRAM TO
05/27/25
REFLECT DETAILED GROUNDING
SYSTEM
CITY STAMP
COIL
�1w I k\0
COIL INC.
1307 HAYES ST. SUITE 5
SAN FRANCISCO, CA 94117
CALIFORNIA LICENSE 814779
CALCULATIONS
SCALE: AS NOTED
DESIGNED BY: COIL INC
SHEET NO.
DATE DRAWN: MAY 27 2025
c -
C
PAPER SIZE: 18"x24"
REV C
=Y
CITY OF SANTA ANA
LOAD CALCULATIONS
(N) PANEL EV1
208Y/120V 3PH 4W 225A MCB
TYPE
DESCRIPTION
BKR
CKT
A PH
B PH
C PH
CKT
BKR
DESCRIPTION
TYPE
C
(N) AUTEL EVCS NO. 1
l00/2P
1
6 0 0 1
67050
0 0
67050
6750
0
67050
6750
67050
6750
0
60 0
6 0
67050
0 0
0
0
0
0
0
o
0
0
SPACE
2
C
LOAD SHARING 80A MAX
'
SPACE
4
C
(N) AUTEL EVCS NO. 2
1 oo!2P
5
SPACE
6
C
LOAD SHARING 80A MAX
7
SPACE
8
C
(N) AUTEL EVCS NO. 3
100/21?
SPACE
10
C
LOAD SHARING 80A MAX
11
SPACE
-
12
-
(N) AUTEL EVCS NO. 4
l00/2P
13
SPACE
-
14
-
LOAD SHARING 80A MAX
15
SPACE
-
16
-
(N) AUTEL EVCS NO. 5
100/2P
17
SPACE
-
18
-
LOAD SHARING 80A MAX
19
SPACE
-
20
-
(N) AUTEL EVCS NO. 6
100/2P
21
SPACE
22
-
LOAD SHARING 80A MAX
23
SPACE
24
-
SPACE
-
25
-
SPACE
-
26
-
SPACE
-
27
SPACE
28
-
SPACE
-
SPACE
30
-
SPACE
-
31
SPACE
-
32
SPACE
-
33
SPACE
-
34
-
SPACE
-
35
SPACE
-
36
-
SPACE
-
37
SPACE
-
i8
-
SPACE
-
39
SPACE
-
40
-
SPACE
-
41
SPACE
-
42
TOTAL DEMAND LOAD (VA)
PHASE DEMAND (AMPS)
TOTAL CURRENT @ 208V
PANEL CURRENT @ 208V
27000
27000
27000
225
225
225
224.8335
AMPS
225.0000
AMPS
LOAD ABBREVIATIONS A:NDDFMANDFACTORS :
C = CONT. LOAD (125%). L = LIGHTINGLOAD (125%)
LM -LARGEST MOTOR (125%), M =MOTOR (100%)
R = RECEPTACLES (100%), N = NON-CONT. LOAD (100%)
AUTEL POWER SHARING
EVSE NO.
BREAKER SIZE (AT)
NETWORK LIMIT (A)
FALLBACK LIMIT (A)
MAX OUTPUT (A)
1
100
103.84
_51.92
80
4
100
51.92
80
2
100
103.84
51.92
80
5
100
51.92
80
3
100
103.84
51.92
80
6
100
51.92
80
(N) PANEL EV2
208Y/120V 3PH 4W 225A MCB
TYPE
DESCRIPTION
BKR
CKT
A PH
B PH
C PH
CKT
BKR
DESCRIPTION
TYPE
C
(N) AUTEL EVCS NO. 7
100/2P
1
67050
0
6750
67050
60 0
6 O 0
67050
6 0 0
67050
6750
0
60
0
6 0 0
67050
00
00
0
0
0
0
0
0
0 Me-
0
SPACE
-
2
C
LOAD SHARING 80A MAX
3
SPACE
4
C
(N) AUTEL EVCS NO. 8
loor2P
5
SPACE
6
6
C
LOAD SHARING 80A MAX
7
SPACE
C
(N) AUTEL EVCS NO.9
100/2P
9
-
SPACE
10
C
LOAD SHARING 80A MAX
I
-
SPACE
12
-
(N) AUTEL EVCS NO. 10
100/2P
13
-
SPACE
14
-
LOAD SHARING 80A MAX
15
16
-
SPACE
-
(N) AUTEL EVCS NO. 11
100f2P
17
-
SPACE
18
-
LOAD SHARING 80A MAX
19
-
SPACE
20
-
(N) AUTEL EVCS NO. 12
100f2P
21
-
SPACE
22
-
LOAD SHARING 80A MAX
23
-
SPACE
24
-
SPACE
25
-
SPACE
26
SPACE
-
27
-
SPACE
28
SPACE
-
29
-
SPACE
30
SPACE
-
31
-
SPACE
32
-
SPACE
-
33
-
SPACE
34
-
SPACE
-
35
-
SPACE
-
36
-
SPACE
-
37
-
SPACE
38
-
SPACE
-
39
40
-
SPACE
SPACE
-
41
-
SPACE
42
TOTAL DEMAND LOAD (VA)
PHASE DEMAND (AMPS)
TOTAL CURRENT @ 208V
PANEL CURRENT @ 208V
27000
27000
27000
225
225
225
224.8335
AMPS
225.0000
AMPS
LOAD ABBREVIATIONS AiN'D DFMAN-D FACTORS:
C = CONT. LOAD (125%), L = LIGHTINGLOAD (125%)
LM = LARGEST MOTOR (125%), M =MOTOR (100%)
R=RECEPTACLES (100%), N =NON-CONT. LOAD (100%)
AUTEL POWER SHARING
EVSE NO.
BREAKER SIZE AT
NETWORK LIMIT A
FALLBACK LIMIT A
MAX OUTPUT (A)-
7
100
103.84
51.92
80
10
100
51.92
80
8
100
103.84
51.92
80
11
100
51.92
80
9
100
103.84
51.92
80
12
100
51.92
80
I bg(b-hd f Ifd
NAME:
REVOLV (SANTA ANA)
3DDRE fArt�IS STTVNTA NA,
F(DWPFRMIT ISSUANC
SHEET CATALOG
S
DESCRIPTION
T-1
COVER PAGE
S-1.TO 2
SITE PLAN
E-4
COND. CALCS
E-5
LOAD CALCS
SS-1 TO 2
SPECS SHEET
C10-614779
s
BOBBY PENN
MASTER ELECTRICIAN}
REVISION
REV NO.
DESCRIPTION
DATE
p
UPDATED ADA NOTE
04/20/25
Qz
UPDATED THE SITE PLAN TO
05/27/25
INDICATE CORRECT ADDRESS FOR
PROPERTY 3121 AND THE LEGAL
PROPERTY LINES
UPDATED LINE DIAGRAM TO
05/27/25
REFLECT DETAILED GROUNDING
SYSTEM
CITY STAMP
////x
C 0 1 L
�1w I k\0
COIL INC.
1307 HAYES ST. SUITE 5
SAN FRANCISCO, CA 94117
CALIFORNIA LICENSE 814779
CALCULATIONS
SCALE: AS NOTED
DESIGNED BY: COIL INC
SHEET NO.
DATE DRAWN: MAY 27 2025
C
C —
PAPER SIZE: 18"x24"
REV C
cY
/AUTEL
MAXICHARGERT"
AC FLOOR -STANDING
SPECIFICATIONS
POWERFUL
Max 2*19.2kW, Simultaneous
Charging of 2 Vehicles
ADVANCED
ISO 15118 Plug & Charge
CONVENIENT
Cable Management System
PROFITABLE
Generate Advertising Revenue
Using 8 Inch High -Definition Screen
SMART
Dynamic Load Balancing
WORKPLACE I COMMERCIAL PARKING I CAR WORKSHOP
2.844.765,0250 WWW.AUTELENERGY.COM AUTELENERGY&AUTEL.COM
For Single Input:
1. Main Breaker
2. PE Bus
3. 100 A Breaker
4. Power Sharing Kit
4
AUTEL L2 EVCS
SPECIFICATIONS
MAXICHARGER AC FLOOR -STANDING
PRODUCT INFORMATION
INPUT/OUTPUT POWER RATING AND CURRENT 2*19.2kW (240V AC*80A)
Output Amperage Adjustable Via Mobile App or DIP Switch, from 6A to 80A On Each Port
INPUT/OUTPUTVOLTAGE
208Vt1596; 240Vt15'X, 60Hz
NETWORKTYPE
LVN+PE, LVL21PE
INPUTCORD
Hardwired
CONNECTOR TYPE
SAE J177Z 25' (7.5m) or 16.4' ('5m)
GROUND FAULT DETECTION
20MA CCID
PROTECTION
Over -Current, Over -Voltage, Under -Voltage, Integrated Surge Protection
CARD READER
Optional: ISO 16693, ISO 14443, NFC
POWER MEASUREMENT ACCURACY
GENERAL CHARACTERISTICS
+/-1.0%from 1%to Full Scale
ENCLOSURE RATING
NEMA 3R
OPERATING ALTITUDE
6561 Ft.
OPERATING TEMPERATURE RANGE
-40F — +131F
STORAGE TEMPERATURE RANGE
-40E—+186F
MOUNTING
Floor Mounted or Wall Mounted
DIMENSIONS (H.W-D)
USERINTERFACE
24.6'x12.6'x6.7' (625nunx320mmx170mm)
STATUS INDICATION
LED/APP/LCD (8 Inch, VXx720 Touch Screen)
USER INTERFACE
Autel Charge APP; Autel Charge Cloud
CONNECTIVITY
Bluetooth, Wi-F7, Ethernet, 4G, RS485
COMMUNICATION PROTOCOLS
OCPP L6J (Can be Upgraded to OCPP 2.0.1 Later)
USER AUTHENTICATION
SOFTWARE UPDATE
APP, RF ID Card, Credit Cards (Optional)
SOFTWARE UPDATE
CERTIFICATIONS & STANDARDS
OTA Updates Via Web Portal
SAFETY & COMPLIANCE
UL 2231-L UL 2231-2, UL2594, NEC Article 625, CSA C22.2, UL 916, ISO 15US Plug&Charge
EMC COMPLIANCE
FCC 15 Class B
CERTIFICATION
Energy Star, OpenADR 2.Ob
WARRANTY
36 Months, Warranty Extension Possible
— cGus
1.844.765.0150 WWW.AUTELENERGY.COM AUTELENERGYCaAUTEL.COM ECEM
Single Input Wiring Connection: 2. Use a flathead screwdriver to set the rotary switch to an appropriate position as per
the table below.
Before connecting L1, L2/N, and PE wires, install the included power sharing kit: put the
four spacers into the four holes respectively and cover with the supplied two double tee
nuts. Insert the four M4 x 26 screws provided and tighten the screws.
Next, connect the wires per the diagram.
L1
Position
Amperage (A)
A IMPORTANT
The supplied double tee nuts, spacers, and M4 x 26 screws are used only for single input
wiring connection. Do not use them for dual inputs wiring connection.
8 40 42
1=161 a Of A ilk I I F, M A 0
r! � n Ili F • ii � � �:� ��11
NAME:
REVOLV (SANTA ANA)
3D2RE AD MS "'0VNT#NA,
F(DR2PFRMIT ISSUANC
SHEET CATALOG
S
DESCRIPTION
T-1
�ateS-1�
COVER PAGE
TO 2
SITE PLAN
E-4
COND. CALCS
E-5
LOAD CALCS
SS-1 TO 2
SPECS SHEET
REVISION
REV NO.
DESCRIPTION
DATE
Q
UPDATED ADA NOTE
04/20/25
Q
UPDATED THE SITE PLAN TO
05/27/25
INDICATE CORRECT ADDRESS FOR
PROPERTY 3121 AND THE LEGAL
PROPERTY LINES
Q
UPDATED LINE DIAGRAM TO
05/27/25
REFLECT DETAILED GROUNDING
SYSTEM
CITY STAMP
COIL
/IIk\0
COIL INC.
1307 HAYES ST. SUITE 5
SAN FRANCISCO, CA 94117
CALIFORNIA LICENSE 814779
SPECS SHEET
SCALE: AS NOTED
DESIGNED BY: COIL INC
SHEET NO.
DATE DRAWN: MAY 27 2025
S c _ I
J
PAPER SIZE: 18"x24"
REV C
CONTROLLER
R1=M1101,,,,,,,,I.tJT10N 121 - R-,[4.
R1Df01,,,,,,,,ILJT10N 121
RevPi Connect S of
RevPi Connect S
CE �A O
Technical Data - `�` mom
Number of digital output channels 1
Article No.: 100362 (8 GB version)
Output type Relay contact, approval up to 30 V switching voltage (e.g. for
Article No.: 100363 (16 GB version)
power supply of a router)
Article No.: 100364 (32 GB version)
Maximum current load of the contact 2 A @ 30 V DC (resistive load!)
Software interface of input and output Via GPIOs and process image. Output is optionally switched by
Housing dimensions (H x W x D) 96 x 45 x 110,5 mm
hardware watchdog.
Housing type DIN rail housing (for DIN rail version EN 50022)
Hardware watchdog functionality Can be disabled by bridging the 4-pole screw -type terminal. Re-
set by toggling a GPIO or alternatively a bit in the process im-
Housing material Polycarbonate
age..
Weight approx 197 g / 224 g (incl. connectors)
Hardware watchdog interval) Trigger after approx. 60 seconds without toggling the reset
it.
Protection class IP20
Compatible modules for system expansion All RevPi 10 modules and RevPi Gate modules can be con -
Power supply 12 ... 24 V DC -15 % /+20 %, reverse -polarity protected
nected via the PiBridge system bus.
Max. power consumption 20 Watt (incl.1 A total USB output current)
All RevPi Con modules can be connected via the ConBridge sys-
tem bus.
Allowable operating temperature -25 ... +55 °C
—
ESD protection 4 kV / 8 kV (according to EN61131-2 and IEC 61000-6-2)
Allowable storage temperature -40 ... +85 °C
-
EMI tests Passed (according to EN61131-2 and IEC 61000-6-2)
Max. relative humidity (at 40 °C) up to 93 % (non -condensing)
Surge/Burst tests Passed (according to EN61131-2 and IEC 61000-6-2)
Interfaces 2 x USB A (Total current draw from both sockets max.1 A) Z
Buffer time RTC min. 24 h
2 x RJ4510/100 Ethernet (using separate MAC addresses)
1 x RS485 screw -type terminal
Optical indicator 6 status LEDs (bi-color), two of them freely programmable
Conformity CE, RoHS
1 x Micro-USB (solely for image transfer to eMMC)
1 x Micro HDMI 2.Oa (4K)
UL certification Yes, UL-File-No. E494534
1 x PiBridge system bus
Note: The device may only be supplied from circuits that com-
1 x ConBridge system bus
ply with Class 2 or Safety Extra Low Voltage (SELV) according
to Class 9.4 of UL 61010-1.
Connectors 1 x 4-pole screw -type terminal for relay contact and signal in-
The average power consumption without USB load varies greatly and depends on the use of the interfaces, the GPU and the
put
CPU. It is usually well below 4 watts without HDMI.
1 x 4-pole screw -type terminal for power supply
z 1 A USB output current (total of both USB outputs) is only available for input voltages >11 V. The bridging time required by EN
61131-2 of voltage dips of at least 10 ms is only guaranteed with a supply voltage of 20.4 to 28.8 V. At 12 V input voltage this
Processor Broadcom BCM2711, quad -core Arm Cortex-A72
time decreases drastically, especially when driving loads by USB ports.
Clock rate 1.5 GHz
Processor cooling Passive with heat sink
RAM 1 GB LPDDR4
Flash memory 8 GB (Article No.: 100362), 16 GB (Article No.: 100363), 32 GB
N100364 )
(Atil(Article o.:
Collins Electrical Company, Inc.
project 249003
purchase order #2490035016
Number of digital input channels 1
Digital input type 24 V control voltage (e.g. for power -good signal of a UPS)
Input thresholds approx. 3.0 V (0 -> 1) resp. 2.3 V (1 -> 0)
Input protection against overvoltage, negative voltages
Errors and omissions excepted.
KUNBUS GmbH, Heerweg 15C, 73770 Denkendorl', Germany 1 Tel: +49 (0) 711 400 91 500 1 Fax: +49 (0) 711 400 91 501 1 V 1.2
Email: info@kunbus.de I Web: www.kunbus.com 1/2
Errors and omissions excepted.
KUNBUS GmbH, Heerweg 15C, 73770 Denkendorf, Germany I Tel: +49 (0) 711 400 91 500 1 Fax: +49 (0) 711 400 91 501 I V 1.2
Email: info@kunbus.de I Web: www.kunbus.com 2/2
E-4
COND. CALCS
E-5
LOAD CALCS
SS-1 TO 2
SPECS SHEET
REVISION
REV NO.
DESCRIPTION
DATE
Q
UPDATED ADA NOTE
04/20/25
Qz
UPDATED THE SITE PLAN TO
05/27/25
INDICATE CORRECT ADDRESS FOR
PROPERTY 3121 AND THE LEGAL
PROPERTY LINES
Q
UPDATED LINE DIAGRAM TO
05/27/25
REFLECT DETAILED GROUNDING
SYSTEM
CITY STAMP
--_z COIL
//III``
COIL INC.
1307 HAYES ST. SUITE 5
SAN FRANCISCO, CA 94117
CALIFORNIA LICENSE 814779
SPECS SHEET
SCALE: AS NOTED
DESIGNED BY: COIL INC
SHEET NO.
DATE DRAWN: MAY 27 2025
SS-2
PAPER SIZE: 18"x24"
REV C