HomeMy WebLinkAbout3080 S Harbor Blvd - PlanProject For: KPRS Inc 2850 Saturn, Suite 120 Brea CA, 92821 McGuff TI Structural Calculations For Santa Ana, CA 3080 S. Harbor Blvd 92704 PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Cover S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH 03/17/2025 Project Description This project entails additions of all of the following structural items 1. New And Replacement RTUs Structural calculations will be provided to verify the adequacy of the (E) roof framing for multiple new RTUs. Calculations will also be provided for the design of seismic anchorage for the new and replacement units. 2. Interior Partitions And Metal Stud Framing Calculations Calculations will be provided for the design of multiple new partial/full height metal stud walls and new metal stud ceiling areas. 4. Generator Enclosure Design Structural calculations will be provided for the design of new generator enclosure for a future generator. PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Description S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH 3. Transformer Support Structural calculations will be provided for the design of new wall mounted transformers and for the anchorage of transformers on grade. 4. Generator Enclosure Design Structural calculations will be provided for the design of new generator enclosure for a future generator. Use ASCE Hazard Tool PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Hazards S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Hazards S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Seismic Parameter Determination Risk Cat:II Site Class:D-Default Ss =1.315 MCE R short period spectral response acceleration S1 =0.472 MCE R spectral response acceleration (T=1.0s) SMS =1.578 Site-modified spectral acceleration value SM1 =0.865 Site-modified spectral acceleration value (ASCE 7-16 §11.4-4) SD1 =0.577 Numeric seismic design value at 1.0s SA (ASCE 7-16 §11.4-5) SDC = D Seismic design category (ASCE 7-16 §11.6-1 & §11.6-2) Fv =1.833 Site amplification factor at 1.0s (ASCE 7-16 §11.4-2) Section 11.4.8 Requirements & Exemptions Exception 1 Criteria:Exception Not Allowed Site Class E ?No Ss ≥ 1.0 ?Yes Fa must be taken as equal to that of Site Class C No Exception 2 Criteria:Exception Not Allowed Site Class D ?Yes S1 ≥ 0.2 ?Yes Ground Motion Hazard Requirments 1. S1 ≥ 0.6 ?No 2. Class E - Ss ≥ 1.0 ?No Exception 3 Criteria:Exception Not Allowed 3. Class D & E - S1 ≥ 0.2 ?Yes Site Class E ?No S1 ≥ 0.2 ?Yes T ≤ Ts ?No Equivalent Static Force Procedure Used For Design ?No No Site Response Analysis Per Section 21.1 Required? Ground Motion Hazard Analysis Per Section 21.2 Required? No Yes Cs determined by Eq. 12.8-2 for values of T ≤ 1.5Ts and taken as 1.5 times the value computed with Eq 12.8-3 or Eq 12.8-4 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Hazards S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Exception 2 Period Calculations SDS =1.052 g Design spectral response acceleration parameter Ts =0.548 s Short-period transition period TL =8 s Long-period transition period T ≤ 1.5Ts ?Yes Ct =0.02 Approximate period parameter (ASCE7-16 Table 12.8-2)TL ≥ T > 1.5Ts ?No x = 0.75 Approximate period parameter (ASCE7-16 Table 12.8-2) T > TL ?No hn =33 ft Structure height Ta =0.275 s Approximate structure period (ASCE7-16 Eq. 12.8-7) Cs =Value per Eq. 12.8-2 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Dead Load Plywood Sheathing 3 Insulation 2 Mechanical 4 Ceiling 2 Sprinklers 1 Miscellaneous 3 Total 15 psf Live Load Roof Live Load 20 Total 20 psf LOADS PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Load Sheet S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Dead Load Metal Studs @ 16"OC 1.1 5/8" Sheathing (Both Sides) 5 7/8" Plaster (Both Sides) 14.9 Total 21.0 psf ENCLOSURE LOADS RTU Framing Calculations PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA - S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Prescriptive Compliance Method For Single RTU - 5% Increase For Gravity Demands (CBC 502.4) Note: The following calculations apply to members supporting HP-1, HP-3, HP-5 Member Parameters L =40 ft Span of member tw =8 ft Tributary width of member DL =15 psf Dead load demand LL =20 psf Live load demand wASD =280 plf Distributed ASD demand New Unit Demand W p =750 lbs Weight of unit L1 =72 in Length of unit (Dimension parallel to span) L2 =48 in Width of unit (Dimension perpendicular to span) Aunit =24 ft 2 Plan area of unit qunit =11.3 psf Design area demand from unit tw,unit =4 ft Tributary width of unit to member wunit =45.0 plf Design distributed demand from unit x1 =28 ft Span location where unit demand starts x2 =34 ft Span location where unit demand ends Moment Diagram PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA HP-1,HP-3,HP-5 S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis 0 10000 20000 30000 40000 50000 60000 70000 0. 0 1. 6 3. 1 4. 7 6. 3 7. 8 9. 4 11 . 0 12 . 5 14 . 1 15 . 7 17 . 3 18 . 8 20 . 4 22 . 0 23 . 5 25 . 1 26 . 7 28 . 2 29 . 8 31 . 4 32 . 9 34 . 5 36 . 1 37 . 6 39 . 2 Mm a x ( l b - f t ) Span Location (ft) Maximum Moment Demand (N) vs (E) (E) Moment 5% Increase (N) Demand BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA HP-1,HP-3,HP-5 S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Shear Diagram Demand Comparison Mmax,E =56.0 k-ft Maximum moment demand from existing loading Vmax,E =5.6 kips Maximum shear demand from existing loading Mmax,N =57.2 k-ft Maximum moment demand from new loading Vmax,N =5.8 kips Maximum shear demand from new loading %Mincrease =2.2%Percent increase in moment %Vincrease =3.7%Percent increase in shear Less than 5% increase, O.K. -8000 -6000 -4000 -2000 0 2000 4000 6000 8000 0. 0 1. 6 3. 1 4. 7 6. 3 7. 8 9. 4 11 . 0 12 . 5 14 . 1 15 . 7 17 . 3 18 . 8 20 . 4 22 . 0 23 . 5 25 . 1 26 . 7 28 . 2 29 . 8 31 . 4 32 . 9 34 . 5 36 . 1 37 . 6 39 . 2 Vm a x ( l b s ) Span Location (ft) Maximum Shear Demand (N) vs (E) (E) Shear 5% Increase (N) Demand BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Roof Framing Calculations HP-6, HP-7, HP-8, HP-9, HP-10 Support Design Lspan,6 =40 ft Span of new member supporting HP-6 Lspan,7 =36 ft Span of new member supporting HP-7 Lspan,8 =40 ft Span of new member supporting HP-8 Lspan,9 =36 ft Span of new member supporting HP-9 Lspan,10 =40 ft Span of new member supporting HP-10 Ldes =40 ft Design length for new member tw,E =8 ft Spacing of (E) roof members Lunit =5 ft Width of unit tw =3.25 ft Tributary width of new reinforcing members DL =15 psf Dead load LL =20 psf Live load W p =1300 lbs Weight of unit L1 =84 in Length of unit (Dimension parallel to span) L2 =60 in Width of unit (Dimension perpendicular to span) Aunit =35 ft 2 Plan area of unit qunit =17.1 psf Design area demand from unit tw,unit =2.5 ft Tributary width of unit to member wunit =42.9 plf Design distributed demand from unit x1 =2.75 ft Span location where unit demand starts x2 =9.75 ft Span location where unit demand ends See Attached Enercalc Report PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Roof Framing S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Wood Beam LIC# : KW-06017366, Build:20.24.12.17 B&J HBK, INC. (c) ENERCALC, LLC 1982-2025 DESCRIPTION:RTU Support Project File: KPRS McGuff TI.ec6 Project Title: Engineer: Project ID: Project Descr: CODE REFERENCES Calculations per NDS 2018, IBC 2018, CBC 2019, SDPWS 2015 Load Combination Set : ASCE 7-22 / IBC 2024 (L<=100psf) Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Allowable Stress Design iLevel Truss Joist MicroLam LVL 2.0 E 2,600.0 2,600.0 2,510.0 750.0 2,000.0 1,016.54 285.0 1,555.0 42.010 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-22 / IBC 2024 (L<=100psf) .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Load for Span Number 1 Uniform Load : D = 0.04290 k/ft, Extent = 2.750 -->> 9.750 ft, Tributary Width = 1.0 ft Uniform Load : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 3.250 ft, (DL + RLL) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.565: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 19.708ft 64.36 psi= = 3,075.64psi 2-1.75x18Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 356.25 psi== Section used for this span 2-1.75x18 Maximum Shear Stress Ratio 0.181 : 1 0.000 ft= = 1,737.93psi Maximum Deflection 433 <240 204 Ratio =0 <180 Max Downward Transient Deflection 1.107 in 0 Ratio = >=240 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 2.342 in Ratio = >=180 Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1.00Length = 40.0 ft 1 0.412 0.139 0.90 0.946 1.001.00 1.00 14.38 913.1 2,214.5 1.50 256.51.00 35.71.00 1.00+D+Lr 0.946 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 40.0 ft 1 0.565 0.181 1.25 0.946 1.001.00 1.00 27.37 1,737.9 3,075.6 2.70 356.31.00 64.41.00 1.00+D+0.750Lr 0.946 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 40.0 ft 1 0.498 0.161 1.25 0.946 1.001.00 1.00 24.12 1,531.7 3,075.6 2.40 356.31.00 57.21.00 1.00+0.60D 0.946 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00 Wood Beam LIC# : KW-06017366, Build:20.24.12.17 B&J HBK, INC. (c) ENERCALC, LLC 1982-2025 DESCRIPTION:RTU Support Project File: KPRS McGuff TI.ec6 Project Title: Engineer: Project ID: Project Descr: Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu 1.00Length = 40.0 ft 1 0.139 0.047 1.60 0.946 1.001.00 1.00 8.63 547.8 3,936.8 0.90 456.01.00 21.41.00 . LocationLoad CombinationMax. LocationLoad CombinationSpan Max. Overall Maximum Deflections "-" Defl in Span in Span"+" Defl +D+Lr1 2.3422 20.000 0.0000 0.000 . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 2.896 2.690 Max Upward from Load Combinations 2.896 2.690 Max Upward from Load Cases 1.596 1.390 D Only 1.596 1.390 +D+Lr 2.896 2.690 +D+0.750Lr 2.571 2.365 +0.60D 0.958 0.834 Lr Only 1.300 1.300 PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA - S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis RTU Anchorage Calculations BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH RTU Anchorage Calculations Type 1 RTU Type 2 RTU W p =750 lbs Weight of unit W p =1300 lbs Weight of unit L1 =72 in Length of unit L1 =84 in Length of unit L2 =48 in Width of unit L2 =60 in Width of unit H =48 in Height of unit H =54 in Height of unit Units:HP-1, HP-3, HP-5 Units:HP-6, HP-7, HP-8, HP-9, HP-10 Type 3 RTU Type 4 RTU W p =125 lbs Weight of unit W p =75 lbs Weight of unit L1 =36.6 in Length of unit L1 =24.4 in Length of unit L2 =13.8 in Width of unit L2 =19.0 in Width of unit H =28 in Height of unit H =24 in Height of unit Units:CU-1, CU-2 Units:EF-1 Anchorage Demands V1 =146 lbs Ultimate shear demand in single anchor for type 1 units T1 =170 lbs Ultimate tensile demand in single anchor for type 1 units V2 =192 lbs Ultimate shear demand in single anchor for type 2 units T2 =183 lbs Ultimate tensile demand in single anchor for type 2 units V3 =43 lbs Ultimate shear demand in single anchor for type 3 units T3 =88 lbs Ultimate tensile demand in single anchor for type 3 units V4 =43 lbs Ultimate shear demand in single anchor for type 4 units T4 =88 lbs Ultimate tensile demand in single anchor for type 4 units Type 2 Anchorage Controls Lag Screw Design See Anchorage Calculations PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA RTU Anchorage S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Non-Structural Seismic Coefficient Per ASCE 7-16 Design Criteria h =1.00 ft Average Roof Height From Ground z =1.00 ft Component Attachment Height ap =2.50 Component Amplification Factor ASCE 7-16 Table 13.5-1 or 13.6-1 Rp =6.00 ASCE 7-16 Table 13.5-1 or 13.6-1 Ω0 =2.00 Overstrength Factor ASCE 7-16 Table 13.5-1 or 13.6-1 SDS =1.052 Short Period Spectral Acceleration ASCE 7-16 §11.4 Ip =1.00 Component Importance Factor ASCE 7-16 §13.1.3 Analysis F ph =Max(0.32, Min(0.53, 1.68))= 0.526 W p (LRFD) F pv = .2S DS W p = 0.210 W p (LRFD) Component Response Modification Factor 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.33 0.35 0.37 0.39 0.40 0.42 0.44 0.46 0.47 0.49 0.51 0.53 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.67 0.70 0.74 0.77 0.81 0.84 0.88 0.91 0.95 0.98 1.02 1.05 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0.10 0.30 0.50 0.70 0.90 1.10 z/ h Seismic Force Seismic Factor Component/Connection Factor Connection to Concrete Factor F Max S I W Min a S I W R z h S I Wp DS p p p DS P P P DS P P= +        03 04 1 2 16. , . , . PROJECT PROJECT NO. ITEM McGuff TI Load Sheet ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 1 ANCHORAGE" Design Wind Load per ASCE 7-16 Building Data Subscripts 1 and 2 refer to direction of wind load Risk Category:II ASCE 7-16 Table 1.5-1 Exposure Category:C ASCE 7-16 §26.7 hr =33 ft Building average roof height B1 =175 ft Building width B2 =130 ft Building width V =95 mph Basic wind speed ASCE 7-16 Fig. 26.5-1A, B, C, or D Rooftop Structure or Equipment Data h =48 in L1 =72 in Af1 =24.0 sf z = 37 ft L2 =48 in Af2 =16.0 sf zg =41 ft Elevation above sea level Ar =24.0 sf Design Wind Load qz = 0.00256 Kz Kzt Kd Ke V2 =21.3 psf ASCE 7-16 Eq. 26.10-1 Kz =1.0266 Velocity pressure exposure coefficient ASCE 7-16 Table 26.10-1 Kzt =1.0 Topographic factor ASCE 7-16 §26.8 Kd =0.9 Wind directionality factor ASCE 7-16 Table 26.6-1 Ke =1.00 Ground elevation factor ASCE 7-16 Table 26.9-1 Fh = qz (G Cr) Af Lateral force ASCE 7-16 Eq. 29.4-2 Fv = qz (G Cr) Ar Vertical force ASCE 7-16 Eq. 29.4-3 Wind Load (G Cr) Fh1 =341 lb x 1.9 = 648 lb Fh2 =512 lb x 1.9 = 972 lb Fv =512 lb x 1.5 = 767 lb PROJECT PROJECT NO. ITEM McGuff TI Load Sheet ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 1 ANCHORAGE" Equipment Anchorage Per ASCE 7-16 (ASD) Unit Geometry Unit Dimensions Unit Connections h =48.0 in Nc =4.0 # of conn. L1 =72.0 in Nsc =4.0 # of effective shear conn. L2 =48.0 in Ntc =2.0 # of effective tension conn. Dimensions to Center of Gravity x1 =39.6 in COG or Include 5% ecc. x2 =26.4 in COG or Include 5% ecc. y =32.0 in COG or 2/3*h Loads W p =750 lb Weight of equipment Fph =0.526 *Wp Horizontal seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fpv =0.210 *Wp Vertical seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fph =395 lb Horizontal seismic force Ref. ASCE 7-16 §13.3.1 Fpv =158 lb Vertical seismic force Ref. ASCE 7-16 §13.3.1 Fwh =972 lb Horizontal wind force Ref. ASCE 7-16 Eq. 29.4-2 Fwv =767 lb Vertical wind force Ref. ASCE 7-16 Eq. 29.4-3 Shear Demand (ASD) Vc =146 lb/conn = MAX(0.7*Fph/Nsc, 0.6*Fwh/Nsc) Tension Demand (ASD) Twh =243 lb/conn = Fwh*(h/2)/MIN(L1, L2)/Ntc Twv =192 lb/conn = Fwv/Nc Tw =435 lb/conn = Twv + Twh Tpv =48 lb/conn = Fpv*(MAX(x1, L1 - x1)/L1)*(MAX(x2, L2 - x2)/L2) Tph1 =88 lb/conn = (Fph*y/L1)/Ntc Tph2 =132 lb/conn = (Fph*y/L2)/Ntc TE =179 lb/conn = Tpv + MAX(Tph1, Tph2) CD =152 lb/conn = W p*(MIN(x1, L1 - x1)/L1)*(MIN(x2, L2 - x2)/L2) Tc =170 lb/conn = MAX(0, 0.7*TE - 0.6*CD, 0.6*Tw - 0.6*CD) PROJECT PROJECT NO. ITEM McGuff TI RTU Unit Anchorage ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 1 ANCHORAGE" Non-Structural Seismic Coefficient Per ASCE 7-16 Design Criteria h =1.00 ft Average Roof Height From Ground z =1.00 ft Component Attachment Height ap =2.50 Component Amplification Factor ASCE 7-16 Table 13.5-1 or 13.6-1 Rp =3.00 ASCE 7-16 Table 13.5-1 or 13.6-1 Ω0 =1.50 Overstrength Factor ASCE 7-16 Table 13.5-1 or 13.6-1 SDS =1.052 Short Period Spectral Acceleration ASCE 7-16 §11.4 Ip =1.00 Component Importance Factor ASCE 7-16 §13.1.3 Analysis F ph =Max(0.32, Min(1.05, 1.68))= 1.052 W p (LRFD) F pv = .2S DS W p = 0.210 W p (LRFD) Component Response Modification Factor 0.35 0.39 0.42 0.46 0.49 0.53 0.56 0.60 0.63 0.67 0.70 0.74 0.77 0.81 0.84 0.88 0.91 0.95 0.98 1.02 1.05 0.53 0.58 0.63 0.68 0.74 0.79 0.84 0.89 0.95 1.00 1.05 1.10 1.16 1.21 1.26 1.32 1.37 1.42 1.47 1.53 1.58 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0.10 0.30 0.50 0.70 0.90 1.10 1.30 1.50 1.70 z/ h Seismic Force Seismic Factor Component/Connection Factor Connection to Concrete Factor F Max S I W Min a S I W R z h S I Wp DS p p p DS P P P DS P P= +        03 04 1 2 16. , . , . PROJECT PROJECT NO. ITEM McGuff TI Load Sheet ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 3 ANCHORAGE" Design Wind Load per ASCE 7-16 Building Data Subscripts 1 and 2 refer to direction of wind load Risk Category:II ASCE 7-16 Table 1.5-1 Exposure Category:C ASCE 7-16 §26.7 hr =33 ft Building average roof height B1 =175 ft Building width B2 =130 ft Building width V =95 mph Basic wind speed ASCE 7-16 Fig. 26.5-1A, B, C, or D Rooftop Structure or Equipment Data h =28 in L1 =36.6 in Af1 =7.1 sf z = 35.333 ft L2 =13.8 in Af2 =2.7 sf zg =41 ft Elevation above sea level Ar =3.5 sf Design Wind Load qz = 0.00256 Kz Kzt Kd Ke V2 =21.1 psf ASCE 7-16 Eq. 26.10-1 Kz =1.0167 Velocity pressure exposure coefficient ASCE 7-16 Table 26.10-1 Kzt =1.0 Topographic factor ASCE 7-16 §26.8 Kd =0.9 Wind directionality factor ASCE 7-16 Table 26.6-1 Ke =1.00 Ground elevation factor ASCE 7-16 Table 26.9-1 Fh = qz (G Cr) Af Lateral force ASCE 7-16 Eq. 29.4-2 Fv = qz (G Cr) Ar Vertical force ASCE 7-16 Eq. 29.4-3 Wind Load (G Cr) Fh1 =57 lb x 1.9 = 108 lb Fh2 =150 lb x 1.9 = 285 lb Fv =74 lb x 1.5 = 111 lb PROJECT PROJECT NO. ITEM McGuff TI Load Sheet ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 3 ANCHORAGE" Equipment Anchorage Per ASCE 7-16 (ASD) Unit Geometry Unit Dimensions Unit Connections h =28.0 in Nc =4.0 # of conn. L1 =36.6 in Nsc =4.0 # of effective shear conn. L2 =13.8 in Ntc =2.0 # of effective tension conn. Dimensions to Center of Gravity x1 =20.1 in COG or Include 5% ecc. x2 =7.6 in COG or Include 5% ecc. y =18.7 in COG or 2/3*h Loads W p =125 lb Weight of equipment Fph =1.052 *Wp Horizontal seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fpv =0.210 *Wp Vertical seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fph =132 lb Horizontal seismic force Ref. ASCE 7-16 §13.3.1 Fpv =26 lb Vertical seismic force Ref. ASCE 7-16 §13.3.1 Fwh =285 lb Horizontal wind force Ref. ASCE 7-16 Eq. 29.4-2 Fwv =111 lb Vertical wind force Ref. ASCE 7-16 Eq. 29.4-3 Shear Demand (ASD) Vc =43 lb/conn = MAX(0.7*Fph/Nsc, 0.6*Fwh/Nsc) Tension Demand (ASD) Twh =145 lb/conn = Fwh*(h/2)/MIN(L1, L2)/Ntc Twv =28 lb/conn = Fwv/Nc Tw =173 lb/conn = Twv + Twh Tpv =8 lb/conn = Fpv*(MAX(x1, L1 - x1)/L1)*(MAX(x2, L2 - x2)/L2) Tph1 =34 lb/conn = (Fph*y/L1)/Ntc Tph2 =89 lb/conn = (Fph*y/L2)/Ntc TE =97 lb/conn = Tpv + MAX(Tph1, Tph2) CD =25 lb/conn = W p*(MIN(x1, L1 - x1)/L1)*(MIN(x2, L2 - x2)/L2) Tc =88 lb/conn = MAX(0, 0.7*TE - 0.6*CD, 0.6*Tw - 0.6*CD) PROJECT PROJECT NO. ITEM McGuff TI RTU Unit Anchorage ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 3 ANCHORAGE" Non-Structural Seismic Coefficient Per ASCE 7-16 Design Criteria h =1.00 ft Average Roof Height From Ground z =1.00 ft Component Attachment Height ap =2.50 Component Amplification Factor ASCE 7-16 Table 13.5-1 or 13.6-1 Rp =6.00 ASCE 7-16 Table 13.5-1 or 13.6-1 Ω0 =2.00 Overstrength Factor ASCE 7-16 Table 13.5-1 or 13.6-1 SDS =1.052 Short Period Spectral Acceleration ASCE 7-16 §11.4 Ip =1.00 Component Importance Factor ASCE 7-16 §13.1.3 Analysis F ph =Max(0.32, Min(0.53, 1.68))= 0.526 W p (LRFD) F pv = .2S DS W p = 0.210 W p (LRFD) Component Response Modification Factor 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.33 0.35 0.37 0.39 0.40 0.42 0.44 0.46 0.47 0.49 0.51 0.53 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.67 0.70 0.74 0.77 0.81 0.84 0.88 0.91 0.95 0.98 1.02 1.05 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0.10 0.30 0.50 0.70 0.90 1.10 z/ h Seismic Force Seismic Factor Component/Connection Factor Connection to Concrete Factor F Max S I W Min a S I W R z h S I Wp DS p p p DS P P P DS P P= +        03 04 1 2 16. , . , . PROJECT PROJECT NO. ITEM McGuff TI Load Sheet ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 4 ANCHORAGE" Design Wind Load per ASCE 7-16 Building Data Subscripts 1 and 2 refer to direction of wind load Risk Category:II ASCE 7-16 Table 1.5-1 Exposure Category:C ASCE 7-16 §26.7 hr =33 ft Building average roof height B1 =175 ft Building width B2 =130 ft Building width V =95 mph Basic wind speed ASCE 7-16 Fig. 26.5-1A, B, C, or D Rooftop Structure or Equipment Data h =24 in L1 =24.4 in Af1 =4.1 sf z = 35 ft L2 =19 in Af2 =3.2 sf zg =41 ft Elevation above sea level Ar =3.2 sf Design Wind Load qz = 0.00256 Kz Kzt Kd Ke V2 =21.1 psf ASCE 7-16 Eq. 26.10-1 Kz =1.0147 Velocity pressure exposure coefficient ASCE 7-16 Table 26.10-1 Kzt =1.0 Topographic factor ASCE 7-16 §26.8 Kd =0.9 Wind directionality factor ASCE 7-16 Table 26.6-1 Ke =1.00 Ground elevation factor ASCE 7-16 Table 26.9-1 Fh = qz (G Cr) Af Lateral force ASCE 7-16 Eq. 29.4-2 Fv = qz (G Cr) Ar Vertical force ASCE 7-16 Eq. 29.4-3 Wind Load (G Cr) Fh1 =67 lb x 1.9 = 127 lb Fh2 =86 lb x 1.9 = 163 lb Fv =68 lb x 1.5 = 102 lb PROJECT PROJECT NO. ITEM McGuff TI Load Sheet ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 4 ANCHORAGE" Equipment Anchorage Per ASCE 7-16 (ASD) Unit Geometry Unit Dimensions Unit Connections h =24.0 in Nc =4.0 # of conn. L1 =24.4 in Nsc =4.0 # of effective shear conn. L2 =19.0 in Ntc =2.0 # of effective tension conn. Dimensions to Center of Gravity x1 =13.4 in COG or Include 5% ecc. x2 =10.5 in COG or Include 5% ecc. y =16.0 in COG or 2/3*h Loads W p =75 lb Weight of equipment Fph =0.526 *Wp Horizontal seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fpv =0.210 *Wp Vertical seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fph =39 lb Horizontal seismic force Ref. ASCE 7-16 §13.3.1 Fpv =16 lb Vertical seismic force Ref. ASCE 7-16 §13.3.1 Fwh =163 lb Horizontal wind force Ref. ASCE 7-16 Eq. 29.4-2 Fwv =102 lb Vertical wind force Ref. ASCE 7-16 Eq. 29.4-3 Shear Demand (ASD) Vc =24 lb/conn = MAX(0.7*Fph/Nsc, 0.6*Fwh/Nsc) Tension Demand (ASD) Twh =51 lb/conn = Fwh*(h/2)/MIN(L1, L2)/Ntc Twv =25 lb/conn = Fwv/Nc Tw =77 lb/conn = Twv + Twh Tpv =5 lb/conn = Fpv*(MAX(x1, L1 - x1)/L1)*(MAX(x2, L2 - x2)/L2) Tph1 =13 lb/conn = (Fph*y/L1)/Ntc Tph2 =17 lb/conn = (Fph*y/L2)/Ntc TE =21 lb/conn = Tpv + MAX(Tph1, Tph2) CD =15 lb/conn = W p*(MIN(x1, L1 - x1)/L1)*(MIN(x2, L2 - x2)/L2) Tc =37 lb/conn = MAX(0, 0.7*TE - 0.6*CD, 0.6*Tw - 0.6*CD) PROJECT PROJECT NO. ITEM McGuff TI RTU Unit Anchorage ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 4 ANCHORAGE" Non-Structural Seismic Coefficient Per ASCE 7-16 Design Criteria h =1.00 ft Average Roof Height From Ground z =1.00 ft Component Attachment Height ap =2.50 Component Amplification Factor ASCE 7-16 Table 13.5-1 or 13.6-1 Rp =6.00 ASCE 7-16 Table 13.5-1 or 13.6-1 Ω0 =2.00 Overstrength Factor ASCE 7-16 Table 13.5-1 or 13.6-1 SDS =1.052 Short Period Spectral Acceleration ASCE 7-16 §11.4 Ip =1.00 Component Importance Factor ASCE 7-16 §13.1.3 Analysis F ph =Max(0.32, Min(0.53, 1.68))= 0.526 W p (LRFD) F pv = .2S DS W p = 0.210 W p (LRFD) Component Response Modification Factor 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.33 0.35 0.37 0.39 0.40 0.42 0.44 0.46 0.47 0.49 0.51 0.53 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.67 0.70 0.74 0.77 0.81 0.84 0.88 0.91 0.95 0.98 1.02 1.05 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0.10 0.30 0.50 0.70 0.90 1.10 z/ h Seismic Force Seismic Factor Component/Connection Factor Connection to Concrete Factor F Max S I W Min a S I W R z h S I Wp DS p p p DS P P P DS P P= +        03 04 1 2 16. , . , . PROJECT PROJECT NO. ITEM McGuff TI Load Sheet ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 2 ANCHORAGE" - CONTROLS DESIGN Design Wind Load per ASCE 7-16 Building Data Subscripts 1 and 2 refer to direction of wind load Risk Category:II ASCE 7-16 Table 1.5-1 Exposure Category:C ASCE 7-16 §26.7 hr =33 ft Building average roof height B1 =175 ft Building width B2 =130 ft Building width V =95 mph Basic wind speed ASCE 7-16 Fig. 26.5-1A, B, C, or D Rooftop Structure or Equipment Data h =54 in L1 =84 in Af1 =31.5 sf z = 37.5 ft L2 =60 in Af2 =22.5 sf zg =41 ft Elevation above sea level Ar =35.0 sf Design Wind Load qz = 0.00256 Kz Kzt Kd Ke V2 =21.4 psf ASCE 7-16 Eq. 26.10-1 Kz =1.0295 Velocity pressure exposure coefficient ASCE 7-16 Table 26.10-1 Kzt =1.0 Topographic factor ASCE 7-16 §26.8 Kd =0.9 Wind directionality factor ASCE 7-16 Table 26.6-1 Ke =1.00 Ground elevation factor ASCE 7-16 Table 26.9-1 Fh = qz (G Cr) Af Lateral force ASCE 7-16 Eq. 29.4-2 Fv = qz (G Cr) Ar Vertical force ASCE 7-16 Eq. 29.4-3 Wind Load (G Cr) Fh1 =481 lb x 1.9 = 914 lb Fh2 =673 lb x 1.9 = 1279 lb Fv =748 lb x 1.5 = 1122 lb PROJECT PROJECT NO. ITEM McGuff TI Load Sheet ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 2 ANCHORAGE" - CONTROLS DESIGN Equipment Anchorage Per ASCE 7-16 (ASD) Unit Geometry Unit Dimensions Unit Connections h =54.0 in Nc =4.0 # of conn. L1 =84.0 in Nsc =4.0 # of effective shear conn. L2 =60.0 in Ntc =2.0 # of effective tension conn. Dimensions to Center of Gravity x1 =46.2 in COG or Include 5% ecc. x2 =33.0 in COG or Include 5% ecc. y =36.0 in COG or 2/3*h Loads W p =1300 lb Weight of equipment Fph =0.526 *Wp Horizontal seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fpv =0.210 *Wp Vertical seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fph =684 lb Horizontal seismic force Ref. ASCE 7-16 §13.3.1 Fpv =273 lb Vertical seismic force Ref. ASCE 7-16 §13.3.1 Fwh =1279 lb Horizontal wind force Ref. ASCE 7-16 Eq. 29.4-2 Fwv =1122 lb Vertical wind force Ref. ASCE 7-16 Eq. 29.4-3 Shear Demand (ASD) Vc =192 lb/conn = MAX(0.7*Fph/Nsc, 0.6*Fwh/Nsc) Tension Demand (ASD) Twh =288 lb/conn = Fwh*(h/2)/MIN(L1, L2)/Ntc Twv =281 lb/conn = Fwv/Nc Tw =568 lb/conn = Twv + Twh Tpv =83 lb/conn = Fpv*(MAX(x1, L1 - x1)/L1)*(MAX(x2, L2 - x2)/L2) Tph1 =147 lb/conn = (Fph*y/L1)/Ntc Tph2 =205 lb/conn = (Fph*y/L2)/Ntc TE =288 lb/conn = Tpv + MAX(Tph1, Tph2) CD =263 lb/conn = W p*(MIN(x1, L1 - x1)/L1)*(MIN(x2, L2 - x2)/L2) Tc =183 lb/conn = MAX(0, 0.7*TE - 0.6*CD, 0.6*Tw - 0.6*CD) PROJECT PROJECT NO. ITEM McGuff TI RTU Unit Anchorage ENGINEER DATE SHEET NO. CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 2 ANCHORAGE" - CONTROLS DESIGN PROJECT PROJECT NO. ITEM McGuff TI RTU Unit Anchorage ENGINEER DATE SHEET NO. CL S24-0254 Wood Lag Screw Design Design Criteria R α Load: 265 lb @ 43.7 °Vector Load from V b and T b Main Member Species:Douglas Fir-Larch Main Member Thickness:7-1/2 in Side Member Thickness:1/4 in G = 0.50 Specific gravity D = 0.5 in Diameter of lag screw L = 4 in Length of lag screw pz =3.44 in Shear penetration pw =2.19 in Withdrawal penetration From Table Z multiplier (Note 3) Z =320 x 0.8594 Ref. NDS-2018 Table 12J - 11K Allowable Lateral Load Capacity Ref. NDS-2018 Table 11.3.1 Z CD CM Ct Cg C∆Ceg Cdi Ctn Z' =275 1.6 1 1 1 1 1 1 1 =440 lb Allowable Withdrawal Load Capacity Ref. NDS-2018 Table 11.3.1 W CD CM Ct Ceg Ctn W' =378 1.6 1 1 1 1 = 605 lb/in W' x pw = 1324 lb Allowable Vector Load Capacity Demand / Capacity Ref. NDS-2018 §12.4.1 Z'α = 645 lb OK Ref. NDS-2018 Eq.12.4-1 Use 1/2'' diameter 4'' long lag screw Douglas Fir-Larch 0.5 4 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH "TYPE 2 ANCHORAGE" - CONTROLS DESIGN PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA - S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Metal Stud Calculations BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Metal Stud Calculations Ceiling Joists: Non-Walkable Ceiling DL =12 psf Dead load from ceiling LL =10 psf Live load demand for uninhabitable attics without storage tw =1.33 ft Spacing of ceiling joists Lmax,1 =15.75 ft Span of joists in first area Lmax,2 =6 ft Span of joists in second area See Attached CFS Designer Reports Ceiling Joists: Walkable Ceiling DL =12 psf Dead load from ceiling LL =20 psf Roof live load demand tw =1.33 ft Spacing of ceiling joists Lmax =12 ft Span of joists See Attached CFS Designer Report Typical Interior Wall Stud - Non-Walkable And Walkable Ceiling H =12 ft Height of wall studs W wall =10 psf Self weight of wall PDL,stud,nw =126 lbs Dead load demand on wall stud from non-walkable ceiling demands PLL,stud,nw =105 lbs Live load demand on wall stud from non-walkable ceiling demands Pmax,nw =231 lbs Total ASD gravity demand on wall stud from non-walkable ceiling stud PDL,stud,w =96 lbs Dead load demand on wall stud from walkable ceiling demands PLL,stud,w =160 lbs Live load demand on wall stud from walkable ceiling demands Pmax,nw =256 lbs Total ASD gravity demand on wall stud from walkable ceiling stud (Controls Wall Stud Design) See Attached CFS Designer Report Typical Headers - 4'-0" & 6'-0" Openings Habv =7.5 ft Height above opening (includes height above header and parapet height) W wall =10 psf Self weight of wall wDL,wall =75 plf Distributed demand from wall self weight wceiling =192 plf Worst case demand from ceiling framing wtotal =267 plf Distributed demand on header from wall and ceiling framing See Attached CFS Designer Report PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Metal Studs S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Metal Studs S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Typical Interior Wall Stud & Header - Full Height Non Bearing Wall H =30 ft Max height of studs W wall =10 psf Self weight of wall Hopng =9 ft Height of wall opening See Attached CFS Designer Report Typical Header - 12'-0" Openings Habv =7.5 ft Height above opening (includes height above header and parapet height) W wall =10 psf Self weight of wall See Attached CFS Designer Report BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Section : 600S162-43 (33 ksi) @ 16 in" o.c. Single C Stud (punched) Maxo =1390.0 ft-lb 1415.7 lbVa =I =2.316 in^4 Total Load - 240 1. DL + LL All spans 2. DL + LL Even spans 3. DL + LL Odd spans Deflection Limits: Load Comb:4. LL All spans 5. LL Even spans 6. LL Odd spans Live Load - 360 Mmax (ft-lb) K-phi (lb-in/in) Lm (in) Ma-dist (ft-lb) Mmax/ Ma min Load Comb. TL Defl Load Comb. LL Defl Load Comb. Joist Flexural and Deflection Span 910 0.0 189.0 1205.1 0.755 1 L/318 1 L/699 4 Support Load (lb) Bearing (in) Pa (lb) Pn (lb) Max Intr. Load Comb. Stiffeners Required Joist Bending and Web Crippling Load Comb. R1 231.0 1.00 259.1 453.4 0.46 1 NO1 R2 231.0 1.00 259.1 453.4 0.46 1 NO1 Support Vmax (lb) Load Comb. Va Factor V/Va M/Ma Intr. Unstiffened Intr. Stiffened Joist Bending and Shear Load Comb. Load Comb. R1 231.0 1 0.16 0.00 0.16 N/A1.000 1 N/A R2 231.0 1 0.16 0.00 0.16 N/A1.000 1 N/A Support Rx(lb)Ry(lb)Simpson Strong-Tie Connector Connector Interaction Anchor Interaction Joist Reaction and Connections 0.00 %R1 0.0 231.0 0.00 %SSC4.25 (4#10) & (3) #10 to A36 steel (Joist Bearing on Support) 0.00 %R2 0.0 231.0 0.00 %SSC4.25 (4#10) & (3) #10 to A36 steel (Joist Bearing on Support) * Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:Non-Walkable Ceiling Joists 1 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Section : 362S162-33 (33 ksi) @ 16 in" o.c. Single C Stud (punched) Maxo =440.9 ft-lb 1023.6 lbVa =I =0.551 in^4 Total Load - 240 1. DL + LL All spans 2. DL + LL Even spans 3. DL + LL Odd spans Deflection Limits: Load Comb:4. LL All spans 5. LL Even spans 6. LL Odd spans Live Load - 360 Mmax (ft-lb) K-phi (lb-in/in) Lm (in) Ma-dist (ft-lb) Mmax/ Ma min Load Comb. TL Defl Load Comb. LL Defl Load Comb. Joist Flexural and Deflection Span 265 0.0 102.0 452.4 0.601 1 L/481 1 L/1059 4 Support Load (lb) Bearing (in) Pa (lb) Pn (lb) Max Intr. Load Comb. Stiffeners Required Joist Bending and Web Crippling Load Comb. R1 124.7 1.00 165.2 289.1 0.39 1 NO1 R2 124.7 1.00 165.2 289.1 0.39 1 NO1 Support Vmax (lb) Load Comb. Va Factor V/Va M/Ma Intr. Unstiffened Intr. Stiffened Joist Bending and Shear Load Comb. Load Comb. R1 124.7 1 0.12 0.00 0.12 N/A1.000 1 N/A R2 124.7 1 0.12 0.00 0.12 N/A1.000 1 N/A Support Rx(lb)Ry(lb)Simpson Strong-Tie Connector Connector Interaction Anchor Interaction Joist Reaction and Connections 0.00 %R1 0.0 124.7 0.00 %SSC4.25 (4#10) & (3) #10 to A36 steel (Joist Bearing on Support) 0.00 %R2 0.0 124.7 0.00 %SSC4.25 (4#10) & (3) #10 to A36 steel (Joist Bearing on Support) * Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:Non-Walkable Ceiling Joists 2 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Section : 600S162-43 (33 ksi) @ 16 in" o.c. Single C Stud (punched) Maxo =1390.0 ft-lb 1415.7 lbVa =I =2.316 in^4 Total Load - 240 1. DL + LL All spans 2. DL + LL Even spans 3. DL + LL Odd spans Deflection Limits: Load Comb:4. LL All spans 5. LL Even spans 6. LL Odd spans Live Load - 360 Mmax (ft-lb) K-phi (lb-in/in) Lm (in) Ma-dist (ft-lb) Mmax/ Ma min Load Comb. TL Defl Load Comb. LL Defl Load Comb. Joist Flexural and Deflection Span 768 0.0 144.0 1205.1 0.637 1 L/494 1 L/791 4 Support Load (lb) Bearing (in) Pa (lb) Pn (lb) Max Intr. Load Comb. Stiffeners Required Joist Bending and Web Crippling Load Comb. R1 256.0 1.00 259.1 453.4 0.51 1 NO1 R2 256.0 1.00 259.1 453.4 0.51 1 NO1 Support Vmax (lb) Load Comb. Va Factor V/Va M/Ma Intr. Unstiffened Intr. Stiffened Joist Bending and Shear Load Comb. Load Comb. R1 256.0 1 0.18 0.00 0.18 N/A1.000 1 N/A R2 256.0 1 0.18 0.00 0.18 N/A1.000 1 N/A Support Rx(lb)Ry(lb)Simpson Strong-Tie Connector Connector Interaction Anchor Interaction Joist Reaction and Connections 0.00 %R1 0.0 256.0 0.00 %SSC4.25 (4#10) & (3) #10 to A36 steel (Joist Bearing on Support) 0.00 %R2 0.0 256.0 0.00 %SSC4.25 (4#10) & (3) #10 to A36 steel (Joist Bearing on Support) * Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:Walkable Ceiling Joists 1 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Design Loads Wall Lateral Pressure : RO Lateral Pressure : Parapet Lateral Pressure : 5 psf 4-Ways 5 psf Lateral element force multiplier Strength : Deflection :1 1.0 Gravity Load at Header:10 psf Single MemberHeader: Cant. Deflection:2 x Cantilever Additional Pt. Load ea. Stud :256 lbs Component(s)Members(s) Flexural Bracing Axial KyLy Axial KtLt Distortional K-Phi(lb-in/in) Distortional Lm Brace Settings Interconnection Spacing Wall Studs 362S162-33(33), Single@16 in o/c 48 in 48 in 0 None48 in N/A Jamb Studs 362S162-33(33), Single 48 in 48 in 0 None48 in N/A Sill 362S162-33(33), Single Full N/A 0 NoneN/A N/A Component(s)Members(s) Axial Load (lb) Max. Moment (ft-lb) Max. Shear (lb) Bottom Reaction (lb) Top or End Reaction (lb) Analysis Results Max KL/r Wall Studs 362S162-33(33), Single@16 in o/c 256.0 43.4 36.6 66.7100.599 Jamb Studs 362S162-33(33), Single 534.0 58.2 58.2 63.2194.299 Sill 362S162-33(33), Single N/A 25.0 N/A 25.028.3N/A Component(s)Members(s) Deflection A + M Interaction V + M Interaction Web Stiffners Design OK Design Results Span Parapet Wall Studs 362S162-33(33), Single@16 in o/c L/944 0.10 No Yes0.523L/804 Jamb Studs 362S162-33(33), Single L/482 0.44 No Yes0.817L/340 Sill 362S162-33(33), Single L/9748 0.06 No Yes0.06NA Support Rx(lb)Ry(lb)Simpson Strong-Tie® Connector Connector Interaction Anchor Interaction Simpson Strong-Tie® Connectors @ Studs 5.99 %R2 66.74 0.00 13.62 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 76.33 %R1 36.60 462.67 46.37 %FCB43.5 Max(6#12-14) & (2) #12-24 SST X or XL to A36 Steel * Reference catalog for connector and anchor requirement notes as well as screw placements requirement www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:4' OPNG Typical Interior Wall Stud - Non-Walkable 2012 NASPEC [AISI S100-2012]Code: Page 1 of 2 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Support Rx(lb)Ry(lb)Simpson Strong-Tie® Connector Connector Interaction Anchor Interaction Simpson Strong-Tie® Connectors @ Jambs 5.66 %R2 63.16 0.00 12.89 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 13.21 %R1 58.19 690.67 22.26 %362T125-33 (33) & (2) .157" SST PDPA/PDPAT-62KP to steel (3/16" to 1/2" thickness) * Reference catalog for connector and anchor requirement notes as well as screw placements requirement Span/Parapet Bracing Length(in.) Design Number of Braces Pn(lb.) SUBH (Min)¹ SUBH (Max)¹ MSUBH (Min)¹ Simpson Strong-Tie® Wall Stud Bridging Connectors @ Studs MSUBH (Max)¹ LSUBH (Min)¹ LSUBH (Max)¹ Top Parapet Span N/A N/A N/A N/AN/A N/AN/A N/A Span 48 3165.7 OK (0.12)OK (0.10)No Soln3 No SolnOK (0.18)OK (0.11) Span/Parapet Bracing Length(in.) Design Number of Braces Pn(lb.) SUBH (Min)¹ SUBH (Max)¹ MSUBH (Min)¹ Simpson Strong-Tie® Wall Stud Bridging Connectors @ Jambs MSUBH (Max)¹ LSUBH (Min)¹ LSUBH (Max)¹ Top Parapet Span N/A N/A N/A N/AN/A N/AN/A N/A Span 48 3165.7 OK (0.16)OK (0.14)No Soln3 No SolnOK (0.24)OK (0.15) 1) Values in parentheses are stress ratios. 2) Bridging connectors are not designed for back-back, box, or built-up sections. 3) Reference Notes: 4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same. 5) If the bracing length is larger than the span length, bridging connectors are not designed. for latest load data, important information, and general notes. www.strongtie.com www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:4' OPNG Typical Interior Wall Stud - Non-Walkable 2012 NASPEC [AISI S100-2012]Code: Page 2 of 2 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Loads have not been modified for strength checks Loads have not been modified for deflection calculations Section Number Section Ixx (in^4) % of Total Ixx Area (in^2) % of Total Area Built-Up Section: 1 362T200-43(33)32.3 %0.343 33.5 %0.649 2 362T200-43(33)32.3 %0.343 33.5 %0.649 3 362S162-43(33)35.3 %0.340 33.1 %0.710 Overall Member Inputs: Span Bracing (in) K-phi (lb-in/in) Flexure Lm (in) Load (lb) KyLy (in) KtLt (in) Axial K-phi (lb-in/in) Lm (in) Span None 0 0 N/A N/A48 N/A N/A R2 Reaction And Point Load Data: R1 Load (lb)534.0534.0 Brng (in)1.001.00 Analysis Summary: Section Defl M/Ma Flexure V/Va Shear & Bending Axial Web Cripling Stiffen Req'd Unstiffened Stiffened P/Pa Combined 362T200-43(33)L/1849 0.395 0.10 0.10 N/A 0.00No 0.395 362T200-43(33)L/1849 0.395 0.10 0.10 N/A 0.00No 0.395 362S162-43(33)L/1849 0.312 0.28 0.28 N/A 0.00No 0.312 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:4'-0" OPNG Typical Header 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Design Loads Wall Lateral Pressure : RO Lateral Pressure : Parapet Lateral Pressure : 5 psf 4-Ways 5 psf Lateral element force multiplier Strength : Deflection :1 1.0 Gravity Load at Header:10 psf Box (lateral combined)Header: Cant. Deflection:2 x Cantilever Additional Pt. Load ea. Stud :256 lbs Back-to-Back Member L/6 Interconnection Spacing per AISI S100 D1.1 Member Span Cantilever Jamb Studs 24.0 in 7.0 in See AISI S100 D1.1 for Add'nl Requirements Component(s)Members(s) Flexural Bracing Axial KyLy Axial KtLt Distortional K-Phi(lb-in/in) Distortional Lm Brace Settings Interconnection Spacing Wall Studs 362S162-33(33), Single@16 in o/c Third-Pt Third-Pt 0 NoneThird-Pt N/A Jamb Studs 362S162-33(33), Back-To-Back Third-Pt Third-Pt 0 NoneThird-Pt 12 in Sill 362T150-33(33), Single Full N/A 0 NoneN/A N/A Component(s)Members(s) Axial Load (lb) Max. Moment (ft-lb) Max. Shear (lb) Bottom Reaction (lb) Top or End Reaction (lb) Analysis Results Max KL/r Wall Studs 362S162-33(33), Single@16 in o/c 256.0 43.4 36.6 66.7100.599 Jamb Studs 362S162-33(33), Back-To-Back 801.0 78.1 78.1 78.1255.499 Sill 362T150-33(33), Single N/A 44.4 N/A 44.477.0N/A Component(s)Members(s) Deflection A + M Interaction V + M Interaction Web Stiffners Design OK Design Results Span Parapet Wall Studs 362S162-33(33), Single@16 in o/c L/944 0.10 No Yes0.523L/804 Jamb Studs 362S162-33(33), Back-To-Back L/718 0.29 No Yes0.503L/496 Sill 362T150-33(33), Single L/1796 0.26 No Yes0.26NA Support Rx(lb)Ry(lb)Simpson Strong-Tie® Connector Connector Interaction Anchor Interaction Simpson Strong-Tie® Connectors @ Studs 5.99 %R2 66.74 0.00 13.62 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 43.39 %R1 36.60 462.67 30.20 %MFCB45.5 Max(9#12-14) & (2) #12-24 SST X or XL to A36 Steel * Reference catalog for connector and anchor requirement notes as well as screw placements requirement www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:6' OPNG Typical Interior Wall Stud - Non-Walkable 2012 NASPEC [AISI S100-2012]Code: Page 1 of 2 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Support Rx(lb)Ry(lb)Simpson Strong-Tie® Connector Connector Interaction Anchor Interaction Simpson Strong-Tie® Connectors @ Jambs 7.00 %R2 78.06 0.00 15.93 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 17.74 %R1 78.14 957.67 20.04 %362T125-33 (33) & (2) .157" SST PDPA/PDPAT-62KP to steel (3/16" to 1/2" thickness) * Reference catalog for connector and anchor requirement notes as well as screw placements requirement Span/Parapet Bracing Length(in.) Design Number of Braces Pn(lb.) SUBH (Min)¹ SUBH (Max)¹ MSUBH (Min)¹ Simpson Strong-Tie® Wall Stud Bridging Connectors @ Studs MSUBH (Max)¹ LSUBH (Min)¹ LSUBH (Max)¹ Top Parapet Span N/A N/A N/A N/AN/A N/AN/A N/A Span 48 3165.7 OK (0.12)OK (0.10)No Soln2 No SolnOK (0.18)OK (0.11) Span/Parapet Bracing Length(in.) Design Number of Braces Pn(lb.) SUBH (Min)¹ SUBH (Max)¹ MSUBH (Min)¹ Simpson Strong-Tie® Wall Stud Bridging Connectors @ Jambs MSUBH (Max)¹ LSUBH (Min)¹ LSUBH (Max)¹ Top Parapet Span N/A N/A N/A N/AN/A N/AN/A N/A Span 48 N/A N/A N/A N/AN/A N/AN/A N/A 1) Values in parentheses are stress ratios. 2) Bridging connectors are not designed for back-back, box, or built-up sections. 3) Reference Notes: 4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same. 5) If the bracing length is larger than the span length, bridging connectors are not designed. for latest load data, important information, and general notes. www.strongtie.com www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:6' OPNG Typical Interior Wall Stud - Non-Walkable 2012 NASPEC [AISI S100-2012]Code: Page 2 of 2 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Loads have not been modified for strength checks Loads have not been modified for deflection calculations Section Number Section Ixx (in^4) % of Total Ixx Area (in^2) % of Total Area Built-Up Section: 1 362S200-54(50)38.2 %0.479 35.7 %1.030 2 362T200-54(50)30.9 %0.431 32.1 %0.832 3 362T200-54(50)30.9 %0.431 32.1 %0.832 Overall Member Inputs: Span Bracing (in) K-phi (lb-in/in) Flexure Lm (in) Load (lb) KyLy (in) KtLt (in) Axial K-phi (lb-in/in) Lm (in) Span 60 0 0 N/A N/A72 N/A N/A R2 Reaction And Point Load Data: R1 Load (lb)801.0801.0 Brng (in)1.001.00 Analysis Summary: Section Defl M/Ma Flexure V/Va Shear & Bending Axial Web Cripling Stiffen Req'd Unstiffened Stiffened P/Pa Combined 362S200-54(50)L/735 0.393 0.30 0.30 N/A 0.00No 0.393 362T200-54(50)L/735 0.518 0.07 0.07 N/A 0.00No 0.518 362T200-54(50)L/735 0.518 0.07 0.07 N/A 0.00No 0.518 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:6'-0" OPNG Typical Header 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Design Loads Wall Lateral Pressure : RO Lateral Pressure : Parapet Lateral Pressure : 5 psf 4-Ways Lateral element force multiplier Strength : Deflection :1 1.0 Gravity Load at Header:10 psf Box (lateral combined)Header: Component(s)Members(s) Flexural Bracing Axial KyLy Axial KtLt Distortional K-Phi(lb-in/in) Distortional Lm Brace Settings Interconnection Spacing Wall Studs 800S162-43(33), Single@16 in o/c 48 in 48 in 0 None48 in N/A Jamb Studs 800S162-43(33), (3) Non-Composite 48 in 48 in 0 None48 in N/A Vertical Header 800S162-54(50), Boxed Full N/A 0 NoneN/A N/A Lateral Header 800T150-54(50), Boxed Full N/A 0 NoneN/A N/A Sill 800T150-54(50), Single Full N/A 0 NoneN/A N/A Component(s)Members(s) Axial Load (lb) Max. Moment (ft-lb) Max. Shear (lb) Bottom Reaction (lb) Top or End Reaction (lb) Analysis Results Max KL/r Wall Studs 800S162-43(33), Single@16 in o/c 0.0 105.0 105.0 105.0826.9N/A Jamb Studs 800S162-43(33), (3) Non-Composite 450.0 412.5 300.0 412.54125.0129 Vertical Header 800S162-54(50), Boxed N/A 450.0 N/A 450.01350.0N/A Lateral Header 800T150-54(50), Boxed N/A 196.9 N/A 196.9666.6N/A Sill 800T150-54(50), Single N/A 309.4 N/A 309.41004.1N/A Component(s)Members(s) Deflection A + M Interaction V + M Interaction Web Stiffners Design OK Design Results Span Parapet Wall Studs 800S162-43(33), Single@16 in o/c L/340 0.10 No Yes0.541L/0 Jamb Studs 800S162-43(33), (3) Non-Composite L/224 0.82 No Yes0.964L/0 Vertical Header 800S162-54(50), Boxed L/1360 0.22 No Yes0.22NA Lateral Header 800T150-54(50), Boxed L/2343 0.16 No Yes0.16NA Sill 800T150-54(50), Single L/774 0.48 No Yes0.48NA Connector Anchor Interaction Simpson Strong-Tie® Connectors @ Studs www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:12' OPNG Full Height Wall 2012 NASPEC [AISI S100-2012]Code: Page 1 of 2 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Support Rx(lb)Ry(lb)Simpson Strong-Tie® Connector Interaction Interaction 9.42 %R2 105.00 0.00 17.21 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 46.25 %R1 105.00 420.00 27.64 %MFCB45.5 Max(9#12-14) & (2) #12-24 SST X or XL to A36 Steel * Reference catalog for connector and anchor requirement notes as well as screw placements requirement Support Rx(lb)Ry(lb)Simpson Strong-Tie® Connector Connector Interaction Anchor Interaction Simpson Strong-Tie® Connectors @ Jambs 37.00 %R2 412.50 0.00 67.62 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 68.12 %R1 300.00 820.00 43.60 %800T125-33 (33) & (2) .157" SST PDPA/PDPAT-62KP to steel (3/16" to 1/2" thickness) * Reference catalog for connector and anchor requirement notes as well as screw placements requirement Span/Parapet Bracing Length(in.) Design Number of Braces Pn(lb.) SUBH (Min)¹ SUBH (Max)¹ MSUBH (Min)¹ Simpson Strong-Tie® Wall Stud Bridging Connectors @ Studs MSUBH (Max)¹ LSUBH (Min)¹ LSUBH (Max)¹ Span 48 4227.4 OK (0.26)OK (0.25)No Soln8 No SolnOK (0.16)OK (0.16) Span/Parapet Bracing Length(in.) Design Number of Braces Pn(lb.) SUBH (Min)¹ SUBH (Max)¹ MSUBH (Min)¹ Simpson Strong-Tie® Wall Stud Bridging Connectors @ Jambs MSUBH (Max)¹ LSUBH (Min)¹ LSUBH (Max)¹ Span 48 N/A N/A N/A N/AN/A N/AN/A N/A 1) Values in parentheses are stress ratios. 2) Bridging connectors are not designed for back-back, box, or built-up sections. 3) Reference Notes: 4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same. 5) If the bracing length is larger than the span length, bridging connectors are not designed. for latest load data, important information, and general notes. www.strongtie.com www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:12' OPNG Full Height Wall 2012 NASPEC [AISI S100-2012]Code: Page 2 of 2 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Section : 800S162-43 (33 ksi) @ 16" o.c. Single C Stud (punched) Maxo =1678.4 ft-lb 1051.2 lbVa =I =4.50 in^4 Loads have not been modified for strength checks Loads have not been modified for deflection calculations Bridging Connectors - Design Method =AISI S100 Span KyLy, KtLt Flexual, Distortional Connector Stress Ratio Axial Span 48.0", 48.0"48.0", 396.0"LSUBH3.25 (Min)0.17 Web Crippling Support Load (lb)(in)Max Int.Stiffener? Bearing Pa M (lb)(ft-lbs) R2 110.00 --Shear Connection w/ clip--NO R1 110.00 --Stud/Track Design, Ref Connectors--NO Gravity Load Type Load (lb) Uniform 13.33plf Code Check Required Interaction NotesAllowed Max. Axial, lbs 440.0(c)20%KΦ=0.00 lb-in/in Max KL/r = 1352204.9(c)Span Max. Shear, lbs 110.0 10%Shear (Punched)1051.2 Max. Moment (MaFy, Ma-dist), ft-lbs 907.5 59%Ma-dist (control),KΦ=0.00 lb-in/in1527.4 Moment Stability, ft-lbs 907.5 57%1605.0 Shear/Moment 0.54 54%Shear 0.0, Moment 907.51.00 Axial/Moment 0.70 70%Axial 238.5(c), Moment 901.11.00 Deflection Span, in 1.340 --meets L/296-- Support Rx(lb)Ry(lb)Simpson Strong-Tie Connector Connector Interaction Anchor Interaction 9.87 %R2 110.0 0.0 18.03 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 49.95 %R1 110.0 440.0 42.93 %800T125-33 (33) & (1) .157" SST PDPA/PDPAT-62KP to steel (3/16" to 1/2" thickness) * Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:Interior Full Height Wall Stud 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA - S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Miscellaneous Calculations BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Transformer Support Calculations Demand H =40 in Max height of unit L1 =36 in Length of unit L2 =24 in Width of unit W p =400 lbs Component weight SDS =1.052 Short period spectral acceleration ap =1 Component amplification factor Fp =0.34 *W p Rp =2.5 Component response modification factor Ω0 =2 Overstrength factor Ip =1 Component importance factor Fp,max =1.68 *W p z = 16.5 ft Elevation above base h = 33 ft Average roof height Fp =134.7 lbs Seismic design force Fp,min =0.32 *W p Fv =84.2 lbs Vertical seismic demand Transformer Anchorage yCOG =26.7 in Unit center of gravity assumed at 2/3H OMu =3591 lb-in Overturning moment demand nanchors=4 Total number of anchors T/C = 74.8 lbs Tension compression demand in each anchor due to lateral seismic demand V =34 lbs Shear demand on each anchor due to lateral seismic demand Fnt =45 ksi Nominal tensile strength of bolt Fnv =27 ksi Nominal shear strength of bolt Dbolt =0.5 in Diameter of bolt Abolt =0.20 in 2 Area of bolt frv =0.2 ksi Required shear stress of connection F'nt =45 ksi Adjusted nominal tensile sress ɸRn =6.6 kips Tensile capacity of bolt with effects from shear included O.K. P1000 Beams L =36 in Span of unistrut supporting transformer nb =2 Number of members supporting unit Pmax,t =564 lbs Maximum gravity demand from unit (acts on min (2) members) Pmax,m =282 lbs Maximum gravity demand on member Mmax =2536 lb-in Maximum flexural demand on section (Worst case demand at midspan) Mall =5070 lb-in Allowable flexural capacity of section per catalog O.K. PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Transformer S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Transformer S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis P1000 Brace Design L1 =36.0 in Horizontal dimension of brace H1 =36.0 in Vertical dimension of brace L =50.9 in Length of brace Pmax =564 lbs Maximum vertical demand on horiz beam w/ additional vertical demand from lateral seismic force ϴb =45.0 degrees Angle of brace Paxial =797 lbs Axial demand on brace from vertical and lateral demands Pall =2380 lbs Axial capacity of section O.K. Anchorage - Concrete Wall Pu =564 lbs Ultimate vertical demand on horiz beam w/ additional vertical demand from lateral seismic force Fseis =134.7 lbs Lateral seismic demand L1 =36.0 in Horizontal dimension of brace H1 =36.0 in Vertical dimension of brace Mmax =20291 lb-in Maximum total moment demand on wall connection nc =4 Number of total anchors nT =2 Number of anchors resisting tensile demands nV =4 Number of anchors resisting shear demand T/Canchor =315.5 lbs Tension/compression demand at anchorage from unit lateral and vertical demands Vanchor =141 lbs Total shear demand at anchorage Ωo =2 Overtstrength factor See Attached Anchorage Calaculations BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 1 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 1 3/13/2025 Specifier's comments: 1 Input data Anchor type and diameter: Kwik Bolt TZ2 - CS 1/2 (1 1/2) hnom1 Item number: 2210254 KB-TZ2 1/2x3 3/4 Specification text: Hilti Æ 1/2 in Kwik Bolt TZ2 - CS with 2 in nominal embedment depth per ICC-ES ESR-4266 , Hammer drill bit installation per MPII, Effective embedment depth: hef,act = 1.500 in., hnom = 2.000 in. Material: Carbon Steel Evaluation Service Report: ESR-4266 Issued I Valid: 10/1/2024 | 12/1/2025 Proof: Design Method ACI 318-19 / Mech Shear edge breakout verification: Row closest to edge (Case 3 only from ACI 318-19 Fig. R.17.7.2.1b) Stand-off installation: Profile: Base material: cracked concrete, 2500, fc' = 2,500 psi; h = 6.000 in. Installation: Hammer drilled hole, Installation condition: Dry Reinforcement: tension: not present, shear: not present; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 2 3/13/2025 Geometry [in.] & Loading [lb, in.lb] www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 3 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 3 3/13/2025 1.1 Design results Case Description Forces [lb] / Moments [in.lb]Seismic Max. Util. Anchor [%] 1 Combination 1 N = 860; Vx = 400; Vy = 0; Mx = 0; My = 0; Mz = 0; no 61 2 Load case/Resulting anchor forces Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor Tension force Shear force Shear force x Shear force y 1 860 400 400 0 3 Tension load Load Nua [lb]Capacity f Nn [lb]Utilization bN = Nua/f Nn Status Steel Strength*860 8,433 11 OK Pullout Strength*N/A N/A N/A N/A Concrete Breakout Failure**860 1,433 61 OK * highest loaded anchor **anchor group (anchors in tension) www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 4 3/13/2025 3.1 Steel Strength Nsa = ESR value refer to ICC-ES ESR-4266 f Nsa ³ Nua ACI 318-19 Table 17.5.2 Variables Ase,N [in.2]futa [psi] 0.10 114,004 Calculations Nsa [lb] 11,244 Results Nsa [lb]f steel f Nsa [lb]Nua [lb] 11,244 0.750 8,433 860 3.2 Concrete Breakout Failure Ncb = (ANc ANc0)y ed,N y c,N y cp,N Nb ACI 318-19 Eq. (17.6.2.1a) f Ncb ³ Nua ACI 318-19 Table 17.5.2 ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANc0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.1.4) y ed,N = 0.7 + 0.3 (ca,min 1.5hef )£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) y cp,N = MAX(ca,min cac , 1.5hef cac )£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b) Nb = kc l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables hef [in.]ca,min [in.]y c,N cac [in.]kc l a f' c [psi] 1.500 18.000 1.000 8.000 24 1.000 2,500 Calculations ANc [in.2]ANc0 [in.2]y ed,N y cp,N Nb [lb] 20.25 20.25 1.000 1.000 2,205 Results Ncb [lb]f concrete f Ncb [lb]Nua [lb] 2,205 0.650 1,433 860 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 5 3/13/2025 4 Shear load Load Vua [lb]Capacity f Vn [lb]Utilization bV = Vua/f Vn Status Steel Strength*400 3,599 12 OK Steel failure (with lever arm)*N/A N/A N/A N/A Pryout Strength**400 1,543 26 OK Concrete edge failure in direction x+**400 5,179 8 OK * highest loaded anchor **anchor group (relevant anchors) 4.1 Steel Strength Vsa = ESR value refer to ICC-ES ESR-4266 f Vsteel ³ Vua ACI 318-19 Table 17.5.2 Variables Ase,V [in.2]futa [psi] 0.10 114,004 Calculations Vsa [lb] 5,537 Results Vsa [lb]f steel f Vsa [lb]Vua [lb] 5,537 0.650 3,599 400 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 6 3/13/2025 4.2 Pryout Strength Vcp = kcp [(ANc ANc0)y ed,N y c,N y cp,N Nb ] ACI 318-19 Eq. (17.7.3.1a) f Vcp ³ Vua ACI 318-19 Table 17.5.2 ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANc0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.1.4) y ed,N = 0.7 + 0.3 (ca,min 1.5hef)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) y cp,N = MAX(ca,min cac , 1.5hef cac )£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b) Nb = kc l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables kcp hef [in.]ca,min [in.]y c,N 1 1.500 18.000 1.000 cac [in.]kc l a f' c [psi] 8.000 24 1.000 2,500 Calculations ANc [in.2]ANc0 [in.2]y ed,N y cp,N Nb [lb] 20.25 20.25 1.000 1.000 2,205 Results Vcp [lb]f concrete f Vcp [lb]Vua [lb] 2,205 0.700 1,543 400 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 7 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 7 3/13/2025 4.3 Concrete edge failure in direction x+ Vcb = (AVc AVc0)y ed,V y c,V y h,V y parallel,V Vb ACI 318-19 Eq. (17.7.2.1a) f Vcb ³ Vua ACI 318-19 Table 17.5.2 AVc see ACI 318-19, Section 17.7.2.1, Fig. R 17.7.2.1(b)* AVc0 = 4.5 c2 a1 ACI 318-19 Eq. (17.7.2.1.3) y ed,V = 0.7 + 0.3(ca2 1.5ca1)£ 1.0 ACI 318-19 Eq. (17.7.2.4.1b) y h,V = √1.5ca1 ha ³ 1.0 ACI 318-19 Eq. (17.7.2.6.1) Vb = (7 (le da)0.2 √da)l a √f' c c1.5 a1 ACI 318-19 Eq. (17.7.2.2.1a) Variables ca1 [in.]ca2 [in.]y c,V ha [in.]le [in.] 12.000 18.000 1.000 6.000 1.500 l a da [in.]f' c [psi]y parallel,V 1.000 0.500 2,500 1.000 Calculations AVc [in.2]AVc0 [in.2]y ed,V y h,V Vb [lb] 216.00 648.00 1.000 1.732 12,816 Results Vcb [lb]f concrete f Vcb [lb]Vua [lb] 7,399 0.700 5,179 400 *Anchor row defined by: Anchor 1; Case 3 controls 5 Combined tension and shear loads, per ACI 318-19 section 17.8 bN bV z Utilization bN,V [%]Status 0.600 0.259 5/3 54 OK bNV = bz N + bz V <= 1 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 8 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 8 3/13/2025 6 Warnings • The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility! • The equations presented in this report are based on imperial units. When inputs are displayed in metric units, the user should be aware that the equations remain in their imperial format. • Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs. • Refer to the manufacturer's product literature for cleaning and installation instructions. • For additional information about ACI 318 strength design provisions, please go to https://viewer.joomag.com/profis-design-guide-us-en-summer-2021/0841849001625154758?short&/ • Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI 318-19, Section 26.7. Fastening meets the design criteria! www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 9 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 9 3/13/2025 7 Installation data Anchor type and diameter: Kwik Bolt TZ2 - CS 1/2 (1 1/2) hnom1 Profile: - Item number: 2210254 KB-TZ2 1/2x3 3/4 Hole diameter in the fixture: - Maximum installation torque: 602 in.lb Plate thickness (input): - Hole diameter in the base material: 0.500 in. Hole depth in the base material: 2.250 in. Drilling method: Hammer drilled Minimum thickness of the base material: 3.500 in. Cleaning: Manual cleaning of the drilled hole according to instructions for use is required. Hilti Æ 1/2 in Kwik Bolt TZ2 - CS with 2 in nominal embedment depth per ICC-ES ESR-4266 , Hammer drill bit installation per MPII 7.1 Recommended accessories Drilling Cleaning Setting • Suitable Rotary Hammer • Properly sized drill bit • Manual blow-out pump • Torque controlled cordless impact tool • Torque wrench • Hammer Coordinates Anchor in. Anchor x y c-x c+x c-y c+y 1 0.000 0.000 18.000 18.000 18.000 18.000 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 10 Company: Address: Phone I Fax: Design: Fastening point: | Transformer Support Wall Anchorage Page: Specifier: E-Mail: Date: 10 3/13/2025 8 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you. PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Transformer S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Concrete Wall Capacity Check H =33 ft Height of concrete wall twall =9.5 in Thickness of concrete wall DLconc =150 pcf Weight of concrete W wall =118.75 psf Self weight of concrete wall tw =3 ft Width of wall being analyzed (Includes 3' of wall that transformer attaches to and 1' on each side) wwall =356 plf Distributed weight of wall (W p *t w ) SDS =1.052 Short period spectral acceleration Ie =1 Importance factor Fp =149.9 plf Out-of-plane wall seismic demand Mmax,E =20406 lb-ft Flexural demand in wall from seismic demands (W p *H 2 /8) Mmax,transformer =1691 lb-ft Flexural demand on wall from new transformer demands Mmax,N =22097 lb-ft Worst case flexural demand in wall (Assume transformer moment acts at midspan) Section Capacity fy =60 ksi Yield strength f'c =3 ksi Concrete strength b = 36 in Width of section dsection =9.5 in Depth of section Dbar =0.75 in Diameter of bar nbar =4.0 Number of bars in section As =1.77 in 2 Area of reinforcing steel crebar =4.75 in Concrete cover d = 4.75 in Distance to reinforcing a = 1.15 in Depth of compression block c = 1.36 in Depth of neutral axis εt =0.007 Strain in tensile reinforcment Tension Controlled Φ = 0.90 Moment capacity factor Φ = 0.75 Shear capacity factor ΦMn =33180 lb-ft Flexural capacity O.K. BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Transformer S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Anchorage - Stud Wall Pu =564 lbs Maximum vertical demand on horiz beam w/ additional vertical demand from lateral seismic force (ASD) Fseis =94.3 lbs Maximum lateral seismic demand (ASD) L1 =36.0 in Horizontal dimension of brace H1 =36.0 in Vertical dimension of brace Mmax =20291 lb-in Maximum total moment demand on wall connection T/C =610.77 lbs Tension compresion demand at top and bottom connection to wall V =282 lbs Shear demand at top and bottom connection nscrews =6 Notal number of screws in top and bottom connections Vscrew =47.0 lbs Maximum shear demand in each screw Tscrew =101.8 lbs Maximum tensile demand in each screw Use:#12 SMS Screws tmin =16 GA Min thickness of connected elements Vn =1182 lbs Nominal shear capacity of screw (3*Value in SSMA Catalog) Tnot =468 lbs Nominal pull-out capacity of screw (3*Value in SSMA Catalog) Tnov =1299 lbs Nominal pull-over capacity of screw (3*Value in SSMA Catalog) DCRlim,ov =0.47 DCR limit for combined shear and pull-over (ASD) DCRov =0.10 O.K.Design DCR of connection DCRlim,ot =0.45 DCR limit for combined shear and pull-out (ASD) DCRot =0.26 O.K.Design DCR of connection Connection O.K. Stud Wall Transformer Support Design Demands Mmax =1690.9 lb-ft Maximum total moment demand on wall Pvert,max =564 lbs Maximum vertical demand on wall Phoriz,max =94 lbs Maximum out of plane lateral demand on wall nstuds =3 Number of studs supporting transformer Mstud =564 Maximum moment demand from transformer support on single stud Pvert,stud =188 Maximum vertical demand from transformer support on single stud Phoriz,stud =31 Maximum lateral demand from transformer support on single stud yfull height =16.5 ft Height at which demands act on full height wall (where occurs) See Attached CFS Designer Reports BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Section : 800S162-54 (50 ksi) @ 12" o.c. Single C Stud (punched) Maxo =3065.9 ft-lb 2091.3 lbVa =I =5.60 in^4 Loads have not been modified for strength checks Loads have not been modified for deflection calculations Bridging Connectors - Design Method =AISI S100 Span KyLy, KtLt Flexual, Distortional Connector Stress Ratio Axial Span 48.0", 48.0"48.0", 396.0"LSUBH3.25 (Min)0.16 Web Crippling Support Load (lb)(in)Max Int.Stiffener? Bearing Pa M (lb)(ft-lbs) P1x 39.00 1.50 NO1347.4 0.281377.7 R2 81.09 1.00 NO0.0 0.07574.6 R1 122.91 1.00 NO0.0 0.11574.6 "*" after support means punched near support Gravity Load Type Load (lb) Uniform 10.00plf P1y 230.00lb @ 16.50ft P1xPoint Loads Load(lb)39.00 16.50Y-Dist.(ft) M1Moments Load(ft-lb)-690.00 16.50Y-Dist.(ft) Code Check Required Interaction NotesAllowed Max. Axial, lbs 560.0(c)19%KΦ=0.00 lb-in/in Max KL/r = 1352972.7(c)Span Max. Shear, lbs 122.9 6%Shear (Punched)2091.3 Max. Moment (MaFy, Ma-dist), ft-lbs 1347.4 49%Ma-dist (control),KΦ=0.00 lb-in/in2734.3 Moment Stability, ft-lbs 1347.4 47%2846.4 Shear/Moment 0.44 44%Shear 40.4, Moment 1347.41.00 Axial/Moment 0.63 63%Axial 395.0(c), Moment 1347.41.00 Deflection Span, in 1.128 --meets L/351-- Support Rx(lb)Ry(lb)Simpson Strong-Tie Connector Connector Interaction Anchor Interaction NAR281.1 0.0 NABy Others & Anchorage Designed by Engineer NAR1122.9 560.0 NABy Others & Anchorage Designed by Engineer * Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:Interior Full Height Wall Stud - Transformer Support 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 Non-Structural Seismic Coefficient Per ASCE 7-16 Design Criteria h =0.00 ft Average Roof Height From Ground z =0.00 ft Component Attachment Height ap =1.00 Component Amplification Factor ASCE 7-16 Table 13.5-1 or 13.6-1 Rp =2.50 ASCE 7-16 Table 13.5-1 or 13.6-1 Ω0 =2.00 Overstrength Factor ASCE 7-16 Table 13.5-1 or 13.6-1 SDS =1.052 Short Period Spectral Acceleration ASCE 7-16 §11.4.4 Ip =1.00 Component Importance Factor ASCE 7-16 §13.1.3 Analysis F ph =Max(0.32, Min(0.17, 1.68))= 0.316 W p (LRFD) F pv = .2S DS W p = 0.210 W p (LRFD) Component Response Modification Factor 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.34 0.35 0.37 0.39 0.40 0.42 0.44 0.45 0.47 0.49 0.50 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.64 0.67 0.71 0.74 0.77 0.81 0.84 0.88 0.91 0.94 0.98 1.01 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0.10 0.30 0.50 0.70 0.90 1.10 z/ h Seismic Force Seismic Factor Component/Connection Factor Connection to Concrete Factor F Max S I W Min a S I W R z h S I Wp DS p p p DS P P P DS P P= +        03 04 1 2 16. , . , . PROJECT PROJECT NO. ITEM McGuff TI Seismic Coefficient ENGINEER DATE SHEET NO. 3/12/2025 CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Design Wind Load Per ASCE 7-16 Building Data Subscripts 1 and 2 refer to direction of wind load Risk Category:II ASCE 7-16 Table 1.5-1 Exposure Category:C ASCE 7-16 §26.7 hr =0 ft Building average roof height B1 =100 ft Building width B2 =100 ft Building width V =95 mph Basic wind speed ASCE 7-16 Fig. 26.5-1A, B, C, or D Rooftop Structure or Equipment Data h =45.8 in L1 =34.8 in Af1 =11.1 sf z = 3.8167 ft L2 =24 in Af2 =7.6 sf Zg =41 ft Elevation above sea level Design Wind Load qz = 0.00256 Kz Kzt Kd Ke V2 =5.0 psf ASCE 7-16 Eq. 26.10-1 Kz =0.8489 Velocity pressure exposure coefficient ASCE 7-16 Table 26.10-1 Kzt =1.0 Topographic factor ASCE 7-16 §26.8 Kd =0.9 Wind directionality factor ASCE 7-16 Table 26.6-1 Ke =1.00 Ground elevation factor ASCE 7-16 Table 26.9-1 G =0.85 Gust effect factor ASCE 7-16 26.11 Cf =1.32 Force coefficient ASCE 7-16 Fig. 29.3-1 Fh = qz (G Cr) Af Lateral force ASCE 7-16 Eq. 29.4-2 Fv = qz (G Cr) Af Vertical force ASCE 7-16 Eq. 29.4-3 Wind Load Rooftop Multiplier Fh1 =38 lb x 1 = 38 lb Fh2 =55 lb x 1 = 55 lb Fv =29 lb x 1.5 = 44 lb Note: Equation 29.5-1 used for buildings with average roof height greater than 60' PROJECT PROJECT NO. ITEM McGuff TI Wind Load ENGINEER DATE SHEET NO. 3/12/2025 CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Equipment Anchorage Per 2022 CBC (LRFD) Unit Geometry Unit Dimensions Unit Connections h =45.8 in Nc =4.0 # of conn. L1 =34.8 in Nsc =4.0 # of effective shear conn. L2 =24.0 in Ntc =2.0 # of effective tension conn. y =30.5 in COG or 2/3*h Dimensions to Center of Gravity x1 =19.1 in COG or Include 5% ecc. x2 =13.2 in COG or Include 5% ecc. Loads W p =1050 lb Weight of equipment Fph =0.316 *Wp Horizontal seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fpv =0.210 *Wp Vertical seismic force coefficient Ref. ASCE 7-16 §13.3.1 Fph =332 lb Horizontal seismic force Ref. ASCE 7-16 §13.3.1 Fpv =221 lb Vertical seismic force Ref. ASCE 7-16 §13.3.1 Fwh =55 lb Horizontal wind force Ref. ASCE 7-16 Eq. 29.4-2 Fwv =44 lb Vertical wind force Ref. ASCE 7-16 Eq. 29.4-3 Shear Vc =166 lb/conn = MAX(Ω0Fph/Nsc, Fwh/Nsc) Tension Twh =26.4 lb/conn = Fwh*(h/2)/MIN(L1, L2)/Ntc Twv =10.9 lb/conn = Fwv/Nc Tw =37.3 lb/conn = Twv + Twh Tpv =66.7 lb/conn = Fpv*(MAX(x1, L1 - x1)/L1)*(MAX(x2, L2 - x2)/L2) Tph1 =145.6 lb/conn = (Fph*y/L1)/Ntc Tph2 =211.1 lb/conn = (Fph*y/L2)/Ntc TE =488.8 lb/conn = Tpv + Ω0*MAX(Tph1, Tph2) CD =212.6 lb/conn = W p*(MIN(x1, L1 - x1)/L1)*(MIN(x2, L2 - x2)/L2) Tc =297.5 lb/conn = MAX(0, TE - 0.9*CD, Tw - 0.9*CD) Notes: 1. Anchors in concrete must be designed in accordance with ACI 318. Ref. ASCE 7-16 §13.4.2 PROJECT PROJECT NO. ITEM McGuff TI Anchorage ENGINEER DATE SHEET NO. 3/12/2025 CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Pad Design Per 2022 CBC (LRFD) Geometry Unit Dimensions Pad Dimensions L = 24.0 in t =5.0 in Concrete thickness W = 34.8 in l' =6.0 in Extent beyond end of Unit C.G. (h) = 30.5 in L' = 36 in = L +2l' Weight = 1050 lbs W' (B) = 46.8 in = W + 2l' FPH =331.8 lbs f'c =3000 psi fy =60 ksi qallowable =500 psf Weight = 731.25 lbs 150 pcf x t x L x W Load Combinations ASD LRFD LC 1 = D + (0.7 x E) LC 1 =(1.2 + 0.2SDS)D + E LC 2 = 0.6D + (0.7 x E) LC 2 =(0.9 - 0.2SDS)D + E Mot =7092 lb-in =(F ph xC.G.)x0.7 Mot =10131 lb-in = (F ph xC.G.) Eccentricity LC 1: e = 3.98 in = M ot /(Weight + Pad) LC 2: e = 6.64 in = M ot /(Weight + Pad)-->Governs B/6: 6 in = min(L'xW')/6 ==>Large Eccentricity =if(B/6 > e, Small Eccentricity, Large Eccentricity) f1 =170.0 psf =if("Small Eccentricity",(P/BH + 6M/BH 2 ),(2P/3B(H/2-e)) Soil O.K.=if(f 1 <q allowable , Soik O.K., Soil Failure) PROJECT PROJECT NO. ITEM McGuff TI Foundation ENGINEER DATE SHEET NO. 3/12/2025 CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT PROJECT NO. ITEM McGuff TI Foundation ENGINEER DATE SHEET NO. 3/12/2025 CL S24-0254 1-Way Shear Mu(E) =10131.0 lb-in =F PH x C.G. LC 1: PU (D) =2512.3 lbs =(1.2+0.2S DS )x(Weight + Pad) LC 2: PU (D) =1228.4 lbs =(0.9-0.2S DS )x(Weight + Pad) LC 1: e = 4.03 in =M u /P u LC 2: e = 8.25 in =M u /P u ==>Large Eccentricity =if(B/6 > e, Small Eccentricity, Large Eccentricity) Note: Conservatively use fmax =216.2 psf =if("Small Eccentricity",(P/BH + 6M/BH 2 ),(2P/3B(H/2-e))fmax as fully uniform load Vu = 0.32 kips =(f max /1000)x(l'xW')/144 ϕVn =5.92 kips =0.75x2xSQRT(f'c )/1000xBx(d-3)Note: Assume critical section @ edge of equipment 1-Way Shear O.K.=if(ϕV n >V u , 1-Way Shear O.K., N.G.) 2-Way Shear Note: Assume critical section @ edge of equipment Acrit = 850 in^2 in2 =(L'xW')-(LxW) Vu = 1.3 K kips =(f max /1000) x (A crit /144) λ =1.0 Light Weight (0.75) or Normal Weight (1.0) β = 0.7 =L/W α =40 bo=118 =(2xW)+(2xL) Vc =0.219 ksi =4λ x sqrt(f'c ) Vc =0.427 ksi =(2+(4/β))λ x SQRT(f'c ) Vc =0.147 ksi =(2+(α x d)/b o )λ x SQRT(f'c ) ϕVn =25.90 kips =0.75 x min(V c ) x b o x d 2-Way Shear O.K.=if(ϕV n >V u , 2-Way Shear O.K., N.G.) BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT PROJECT NO. ITEM McGuff TI Foundation ENGINEER DATE SHEET NO. 3/12/2025 CL S24-0254 Check Flexural Steel Note:Use same critical area as 1-way shear Mu =0.08 k-ft =(f max /1000) x ((B x l')/144) x (l'/(2x12)) As,req =0.01 in2 =(M u x 12)/(0.9 x F y x 0.9d) Verify Tempurature & Shrinkage Steel As(S&T) =0.324 in2 =0.0018Bt ==> Governs As/FT =0.108 in2/ft Note:Use table A.3 Provide:#4 bars As = 0.15 in2/ft [O.K.] @ 16 in o.c. BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 1 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 1 3/13/2025 Specifier's comments: 1 Input data Anchor type and diameter: Kwik Bolt TZ2 - CS 1/2 (1 1/2) hnom1 Item number: 2210254 KB-TZ2 1/2x3 3/4 Specification text: Hilti Æ 1/2 in Kwik Bolt TZ2 - CS with 2 in nominal embedment depth per ICC-ES ESR-4266 , Hammer drill bit installation per MPII, Effective embedment depth: hef,act = 1.500 in., hnom = 2.000 in. Material: Carbon Steel Evaluation Service Report: ESR-4266 Issued I Valid: 10/1/2024 | 12/1/2025 Proof: Design Method ACI 318-19 / Mech Shear edge breakout verification: Row closest to edge (Case 3 only from ACI 318-19 Fig. R.17.7.2.1b) Stand-off installation: Profile: Base material: cracked concrete, 2500, fc' = 2,500 psi; h = 5.000 in. Installation: Hammer drilled hole, Installation condition: Dry Reinforcement: tension: not present, shear: not present; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) Tension load: yes (17.10.5.3 (d)) Shear load: yes (17.10.6.3 (c)) www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 2 3/13/2025 Geometry [in.] & Loading [lb, in.lb] www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 3 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 3 3/13/2025 1.1 Design results Case Description Forces [lb] / Moments [in.lb]Seismic Max. Util. Anchor [%] 1 Combination 1 N = 298; Vx = 166; Vy = 0; Mx = 0; My = 0; Mz = 0; yes 28 2 Load case/Resulting anchor forces Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor Tension force Shear force Shear force x Shear force y 1 298 166 166 0 3 Tension load Load Nua [lb]Capacity f Nn [lb]Utilization bN = Nua/f Nn Status Steel Strength*298 8,433 4 OK Pullout Strength*N/A N/A N/A N/A Concrete Breakout Failure**298 1,075 28 OK * highest loaded anchor **anchor group (anchors in tension) www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 4 3/13/2025 3.1 Steel Strength Nsa = ESR value refer to ICC-ES ESR-4266 f Nsa ³ Nua ACI 318-19 Table 17.5.2 Variables Ase,N [in.2]futa [psi] 0.10 114,004 Calculations Nsa [lb] 11,244 Results Nsa [lb]f steel f nonductile f Nsa [lb]Nua [lb] 11,244 0.750 1.000 8,433 298 3.2 Concrete Breakout Failure Ncb = (ANc ANc0)y ed,N y c,N y cp,N Nb ACI 318-19 Eq. (17.6.2.1a) f Ncb ³ Nua ACI 318-19 Table 17.5.2 ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANc0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.1.4) y ed,N = 0.7 + 0.3 (ca,min 1.5hef )£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) y cp,N = MAX(ca,min cac , 1.5hef cac )£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b) Nb = kc l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables hef [in.]ca,min [in.]y c,N cac [in.]kc l a f' c [psi] 1.500 ∞1.000 8.000 24 1.000 2,500 Calculations ANc [in.2]ANc0 [in.2]y ed,N y cp,N Nb [lb] 20.25 20.25 1.000 1.000 2,205 Results Ncb [lb]f concrete f seismic f nonductile f Ncb [lb]Nua [lb] 2,205 0.650 0.750 1.000 1,075 298 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 5 3/13/2025 4 Shear load Load Vua [lb]Capacity f Vn [lb]Utilization bV = Vua/f Vn Status Steel Strength*166 3,599 5 OK Steel failure (with lever arm)*N/A N/A N/A N/A Pryout Strength**166 1,543 11 OK Concrete edge failure in direction **N/A N/A N/A N/A * highest loaded anchor **anchor group (relevant anchors) When the input edge distance is set to "infinity", edge breakout verification is not performed in that direction 4.1 Steel Strength Vsa,eq = ESR value refer to ICC-ES ESR-4266 f Vsteel ³ Vua ACI 318-19 Table 17.5.2 Variables Ase,V [in.2]futa [psi]aV,seis 0.10 114,004 1.000 Calculations Vsa,eq [lb] 5,537 Results Vsa,eq [lb]f steel f nonductile f Vsa,eq [lb]Vua [lb] 5,537 0.650 1.000 3,599 166 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 6 3/13/2025 4.2 Pryout Strength Vcp = kcp [(ANc ANc0)y ed,N y c,N y cp,N Nb ] ACI 318-19 Eq. (17.7.3.1a) f Vcp ³ Vua ACI 318-19 Table 17.5.2 ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANc0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.1.4) y ed,N = 0.7 + 0.3 (ca,min 1.5hef)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) y cp,N = MAX(ca,min cac , 1.5hef cac )£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b) Nb = kc l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables kcp hef [in.]ca,min [in.]y c,N 1 1.500 ∞1.000 cac [in.]kc l a f' c [psi] 8.000 24 1.000 2,500 Calculations ANc [in.2]ANc0 [in.2]y ed,N y cp,N Nb [lb] 20.25 20.25 1.000 1.000 2,205 Results Vcp [lb]f concrete f seismic f nonductile f Vcp [lb]Vua [lb] 2,205 0.700 1.000 1.000 1,543 166 5 Combined tension and shear loads, per ACI 318-19 section 17.8 bN bV z Utilization bN,V [%]Status 0.277 0.108 5/3 15 OK bNV = bz N + bz V <= 1 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 7 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 7 3/13/2025 6 Warnings • The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility! • The equations presented in this report are based on imperial units. When inputs are displayed in metric units, the user should be aware that the equations remain in their imperial format. • Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs. • Refer to the manufacturer's product literature for cleaning and installation instructions. • For additional information about ACI 318 strength design provisions, please go to https://viewer.joomag.com/profis-design-guide-us-en-summer-2021/0841849001625154758?short&/ • "An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-19, Chapter 17, Section 17.10.5.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, the connection design (tension) shall satisfy the provisions of Section 17.10.5.3 (b), Section 17.10.5.3 (c), or Section 17.10.5.3 (d). The connection design (shear) shall satisfy the provisions of Section 17.10.6.3 (a), Section 17.10.6.3 (b), or Section 17.10.6.3 (c)." • Section 17.10.5.3 (b) / Section 17.10.6.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.10.5.3 (c) / Section 17.10.6.3 (b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the anchors by a non-yielding attachment. Section 17.10.5.3 (d) / Section 17.10.6.3 (c) waive the ductility requirements and require the design strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased by w0. • Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI 318-19, Section 26.7. Fastening meets the design criteria! www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 8 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 8 3/13/2025 7 Installation data Anchor type and diameter: Kwik Bolt TZ2 - CS 1/2 (1 1/2) hnom1 Profile: - Item number: 2210254 KB-TZ2 1/2x3 3/4 Hole diameter in the fixture: - Maximum installation torque: 602 in.lb Plate thickness (input): - Hole diameter in the base material: 0.500 in. Hole depth in the base material: 2.250 in. Drilling method: Hammer drilled Minimum thickness of the base material: 3.500 in. Cleaning: Manual cleaning of the drilled hole according to instructions for use is required. Hilti Æ 1/2 in Kwik Bolt TZ2 - CS with 2 in nominal embedment depth per ICC-ES ESR-4266 , Hammer drill bit installation per MPII 7.1 Recommended accessories Drilling Cleaning Setting • Suitable Rotary Hammer • Properly sized drill bit • Manual blow-out pump • Torque controlled cordless impact tool • Torque wrench • Hammer Coordinates Anchor in. Anchor x y c-x c+x c-y c+y 1 0.000 0.000 ---- www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 9 Company: Address: Phone I Fax: Design: Fastening point: | McGuff TI Floor Mount Transformer Page: Specifier: E-Mail: Date: 9 3/13/2025 8 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you. PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA - S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Generator Pad Calculations BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Generator Calcs S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Generator Footing Calculations Footing Parameters L1,gen =13.7 ft Length of unit L2,gen =4 ft Width of unit Le =6 in Extension of footing beyond unit dimensions L1 = 15 ft Length of footing L2 5.5 ft Width of footing D =1.5 ft Depth of footing Footing Demands xecc =32 in Distance from load application to centerline of footing zecc =0 in Distance from load application to centerline of footing PDL =7145 lbs Dead load demand from generator and tank Fpv =1500 lbs Vertical seismic force from generator and tank Fph =2258 lbs Horizontal seismic force from generator and tank OM =12042 lb-ft Overturning moment demand on footing See Attached Enercalc Report BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH = General Footing LIC# : KW-06017366, Build:20.24.12.17 B&J HBK, INC. (c) ENERCALC, LLC 1982-2025 DESCRIPTION:Generator Footing - Case 1 Project File: KPRS McGuff TI.ec6 Project Title: Engineer: Project ID: Project Descr: Code References Calculations per ACI 318-14, IBC 2018, CBC 2019 Load Combinations Used : ASCE 7-16 General Information Material Properties Soil Design Values 1.50 Analysis Settings 250.0 ksi No ksfAllowable Soil Bearing = = 4.0 60.0 3,644.15 145.0 = 0.30Flexure = 0.90 Shear = Valuesϕ 0.00090 Soil Passive Resistance (for Sliding) 1.0 = Increases based on footing plan dimension Add Pedestal Wt for Soil Pressure No: Use Pedestal wt for stability, mom & shear No: Allowable pressure increase per foot of depth = ksf when max. length or width is greater than = ft : = Add Ftg Wt for Soil Pressure Yes Yes:Use ftg wt for stability, moments & shears when footing base is below ft pcf Increase Bearing By Footing Weight = pcf Min. Overturning Safety Factor = : 1 Increases based on footing Depth0.750 = Soil/Concrete Friction Coeff. Ec : Concrete Elastic Modulus = = Footing base depth below soil surface ft =Allow press. increase per foot of depth ksf = : 11.0Min. Sliding Safety Factor = = Concrete Density = Min Allow % Temp Reinf. ksif'c : Concrete 28 day strength fy : Rebar Yield ksi Min Steel % Bending Reinf. Soil Density =110.0 pcf # Dimensions Width parallel to X-X Axis 15.0 ft Length parallel to Z-Z Axis = 5.50 ft Load location offset from footing center... ex : Prll to X-X Axis 32 in= in= = Pedestal dimensions... px : parallel to X-X Axis in pz : parallel to Z-Z Axis in Height = = in Footing Thickness = 18.0 in= Rebar Centerline to Edge of Concrete... = inat Bottom of footing 3.0 Reinforcing # Bars parallel to X-X Axis Reinforcing Bar Size = 5 Number of Bars = 5.0 Bars parallel to Z-Z Axis Reinforcing Bar Size = 5 Number of Bars = 13.0 Bandwidth Distribution Check (ACI 15.4.4.2) Direction Requiring Closer Separation # Bars required within zone # Bars required on each side of zone Applied Loads 7.145 1.50 D Lr ksf L S P : Column Load OB : Overburden = k W E M-zz V-x = =k V-z k2.258 M-xx = k-ft= k-ft12.042 H = General Footing LIC# : KW-06017366, Build:20.24.12.17 B&J HBK, INC. (c) ENERCALC, LLC 1982-2025 DESCRIPTION:Generator Footing - Case 1 Project File: KPRS McGuff TI.ec6 Project Title: Engineer: Project ID: Project Descr: FAIL Sliding - X-X k k FAIL Sliding - Z-Z k k DESIGN SUMMARY Design N.G. Governing Load CombinationMin. Ratio Item Applied Capacity PASS Soil Bearing ksf ksf FAIL Overturning - X-X k-ft k-ft FAIL Overturning - Z-Z k-ft k-ft FAIL Uplift k k PASS Z Flexure (+X) k-ft/ft k-ft/ft PASS Z Flexure (-X) k-ft/ft k-ft/ft PASS X Flexure (+Z)k-ft/ft k-ft/ft PASS X Flexure (-Z)k-ft/ft k-ft/ft PASS 1-way Shear (+X) psi psi PASS 1-way Shear (-X) psi psi PASS 1-way Shear (+Z) psi psi PASS 1-way Shear (-Z) psi psi PASS 2-way Punching psi psi Top reinforcing mat required (see 'Bending' tab). Hand check required for anchor pullout. Detailed Results Rotation Axis &ZeccXecc Actual Soil Bearing Stress @ Location Actual / Allow Soil Bearing (in)Gross Allowable Bottom, -Z Top, +Z Left, -X Right, +X RatioLoad Combination... X-X, D Only 1.50 n/a0.3030 0.3030 n/a 0.2020.0n/a X-X, +0.60D 1.50 n/a0.1818 0.1818 n/a 0.1210.0n/a X-X, +D+0.70E 1.50 n/a0.1760 0.4551 n/a 0.3034.913n/a X-X, +D+0.5250E 1.50 n/a0.2077 0.4170 n/a 0.2783.722n/a X-X, +0.60D+0.70E 1.50 n/a0.05481 0.3339 n/a 0.2237.977n/a Z-Z, D Only 1.50 0.2139n/a n/a 0.3920 0.261n/a9.027 Z-Z, +0.60D 1.50 0.1283n/a n/a 0.2352 0.157n/a9.027 Z-Z, +D+0.70E 1.50 0.2134n/a n/a 0.4177 0.279n/a9.942 Z-Z, +D+0.5250E 1.50 0.2135n/a n/a 0.4113 0.274n/a9.720 Z-Z, +0.60D+0.70E 1.50 0.1278n/a n/a 0.2609 0.174n/a10.512 Rotation Axis & Overturning Stability Load Combination...StatusOverturning Moment Resisting Moment Stability Ratio X-X, D Only None 0.0 k-ft Infinity OK X-X, +0.60D None 0.0 k-ft Infinity OK X-X, +D+0.70E 10.80 k-ft 72.540 k-ft 6.716 OK X-X, +D+0.5250E 8.10 k-ft 71.818 k-ft 8.866 OK X-X, +0.60D+0.70E 10.80 k-ft 44.679 k-ft 4.137 OK Z-Z, D Only None 211.546 k-ft Infinity OK Z-Z, +0.60D None 126.928 k-ft Infinity OK Z-Z, +D+0.70E None 222.326 k-ft Infinity OK Z-Z, +D+0.5250E None 219.631 k-ft Infinity OK Z-Z, +0.60D+0.70E None 137.708 k-ft Infinity OK Force Application Axis Sliding Stability All units k Load Combination...StatusSliding Force Resisting Force Stability Ratio X-X, D Only 0.0 k 7.598 k No Sliding OK X-X, +0.60D 0.0 k 4.559 k No Sliding OK X-X, +D+0.70E 0.0 k 7.913 k No Sliding OK X-X, +D+0.5250E 0.0 k 7.835 k No Sliding OK X-X, +0.60D+0.70E 0.0 k 4.874 k No Sliding OK Z-Z, D Only 0.0 k 7.598 k No Sliding OK Z-Z, +0.60D 0.0 k 4.559 k No Sliding OK General Footing LIC# : KW-06017366, Build:20.24.12.17 B&J HBK, INC. (c) ENERCALC, LLC 1982-2025 DESCRIPTION:Generator Footing - Case 1 Project File: KPRS McGuff TI.ec6 Project Title: Engineer: Project ID: Project Descr: Force Application Axis Sliding Stability All units k Load Combination...StatusSliding Force Resisting Force Stability Ratio Z-Z, +D+0.70E 1.581 k 7.913 k 5.007 OK Z-Z, +D+0.5250E 1.185 k 7.835 k 6.609 OK Z-Z, +0.60D+0.70E 1.581 k 4.874 k 3.084 OK Flexure Axis & Load Combination in^2 in^2 in^2 k-ft As Req'd Footing Flexure Tension k-ft Actual As StatusMu Side Surface Gvrn. As Phi*Mn X-X, +1.20D 0.3878 +Z Bottom 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +1.20D 0.3878 -Z Bottom 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +0.90D 0.2909 +Z Bottom 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +0.90D 0.2909 -Z Bottom 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +1.20D+E 0.9631 +Z Bottom 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +1.20D+E 0.05183 -Z Top 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +1.20D-E 0.1875 +Z Top 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +1.20D-E 0.8274 -Z Bottom 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +0.90D+E 0.8662 +Z Bottom 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +0.90D+E 0.1488 -Z Top 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +0.90D-E 0.2845 +Z Top 0.1944 ACI 7.6.1.1 0.2651 17.664 OK X-X, +0.90D-E 0.7305 -Z Bottom 0.1944 ACI 7.6.1.1 0.2651 17.664 OK Z-Z, +1.20D 2.277 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D 2.277 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D 1.708 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D 1.708 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D+E 2.676 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D+E 2.675 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D-E 1.879 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D-E 1.879 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D+E 2.107 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D+E 2.106 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D-E 1.310 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D-E 1.309 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK One Way Shear X Vu @ +XLoad Combination... Vu @ -X Vu:Max Vu / Phi*VnPhi Vn Status +1.20D 2.90 3.74 3.74 94.87 0.04psipsipsipsi OK +0.90D 2.18 2.81 2.81 94.87 0.03psipsipsipsi OK +1.20D+E 3.41 4.40 4.40 94.87 0.05psipsipsipsi OK +1.20D-E 2.40 3.09 3.09 94.87 0.03psipsipsipsi OK +0.90D+E 2.69 3.46 3.46 94.87 0.04psipsipsipsi OK +0.90D-E 1.67 2.15 2.15 94.87 0.02psipsipsipsi OK One Way Shear Z Load Combination... Vu @ -Z Vu @ +Z Vu:Max Vu / Phi*VnPhi Vn Status +1.20D 0.85 0.85 3.74 94.87 0.04psipsipsipsi OK +0.90D 0.63 0.63 2.81 94.87 0.03psipsipsipsi OK +1.20D+E 0.22 2.21 4.40 94.87 0.05psipsipsipsi OK +1.20D-E 1.91 0.51 3.09 94.87 0.03psipsipsipsi OK +0.90D+E 0.43 2.00 3.46 94.87 0.04psipsipsipsi OK +0.90D-E 1.70 0.73 2.15 94.87 0.02psipsipsipsi OK Vu / Phi*Vn Two-Way "Punching" Shear All units k StatusVu Phi*VnLoad Combination... +1.20D 9.34 189.74 0.04922 OKpsipsi +0.90D 7.00 189.74 0.03691 OKpsipsi +1.20D+E 10.97 189.74 0.05783 OKpsipsi +1.20D-E 7.70 189.74 0.04061 OKpsipsi +0.90D+E 8.64 189.74 0.04552 OKpsipsi +0.90D-E 5.37 189.74 0.0283 OKpsipsi General Footing LIC# : KW-06017366, Build:20.24.12.17 B&J HBK, INC. (c) ENERCALC, LLC 1982-2025 DESCRIPTION:Generator Footing - Case 2 Project File: KPRS McGuff TI.ec6 Project Title: Engineer: Project ID: Project Descr: Code References Calculations per ACI 318-14, IBC 2018, CBC 2019 Load Combinations Used : ASCE 7-16 General Information Material Properties Soil Design Values 1.50 Analysis Settings 250.0 ksi No ksfAllowable Soil Bearing = = 4.0 60.0 3,644.15 145.0 = 0.30Flexure = 0.90 Shear = Valuesϕ 0.00090 Soil Passive Resistance (for Sliding) 1.0 = Increases based on footing plan dimension Add Pedestal Wt for Soil Pressure No: Use Pedestal wt for stability, mom & shear No: Allowable pressure increase per foot of depth = ksf when max. length or width is greater than = ft : = Add Ftg Wt for Soil Pressure Yes Yes:Use ftg wt for stability, moments & shears when footing base is below ft pcf Increase Bearing By Footing Weight = pcf Min. Overturning Safety Factor = : 1 Increases based on footing Depth0.750 = Soil/Concrete Friction Coeff. Ec : Concrete Elastic Modulus = = Footing base depth below soil surface ft =Allow press. increase per foot of depth ksf = : 11.0Min. Sliding Safety Factor = = Concrete Density = Min Allow % Temp Reinf. ksif'c : Concrete 28 day strength fy : Rebar Yield ksi Min Steel % Bending Reinf. Soil Density =110.0 pcf # Dimensions Width parallel to X-X Axis 15.0 ft Length parallel to Z-Z Axis = 5.50 ft Load location offset from footing center... ex : Prll to X-X Axis 32 in= in= = Pedestal dimensions... px : parallel to X-X Axis in pz : parallel to Z-Z Axis in Height = = in Footing Thickness = 18.0 in= Rebar Centerline to Edge of Concrete... = inat Bottom of footing 3.0 Reinforcing # Bars parallel to X-X Axis Reinforcing Bar Size = 5 Number of Bars = 5.0 Bars parallel to Z-Z Axis Reinforcing Bar Size = 5 Number of Bars = 13.0 Bandwidth Distribution Check (ACI 15.4.4.2) Direction Requiring Closer Separation Bars along Z-Z Axis # Bars required within zone 53.7 % # Bars required on each side of zone 46.3 % Applied Loads 7.145 1.50 D Lr ksf L S P : Column Load OB : Overburden = k W E M-zz V-x = =k2.258 V-z k M-xx = k-ft= k-ft 12.042 H = General Footing LIC# : KW-06017366, Build:20.24.12.17 B&J HBK, INC. (c) ENERCALC, LLC 1982-2025 DESCRIPTION:Generator Footing - Case 2 Project File: KPRS McGuff TI.ec6 Project Title: Engineer: Project ID: Project Descr: PASS 3.056 Sliding - X-X 1.581 k 4.831 k +0.60D+0.70E PASS n/a Sliding - Z-Z 0.0 k 0.0 k No Sliding DESIGN SUMMARY Design OK Governing Load CombinationMin. Ratio Item Applied Capacity PASS 0.3157 Soil Bearing 0.4736 ksf 1.50 ksf +D+0.70E about Z-Z axis PASS n/a Overturning - X-X 0.0 k-ft 0.0 k-ft No Overturning PASS 9.865 Overturning - Z-Z 10.80 k-ft 106.542 k-ft +0.60D+0.70E PASS n/a Uplift 0.0 k 0.0 k No Uplift PASS 0.1763 Z Flexure (+X) 3.307 k-ft/ft 18.760 k-ft/ft +1.20D+E PASS 0.2111 Z Flexure (-X) 3.960 k-ft/ft 18.760 k-ft/ft +1.20D-E PASS 0.02580 X Flexure (+Z)0.4617 k-ft/ft 17.896 k-ft/ft +1.20D+E PASS 0.02580 X Flexure (-Z)0.4617 k-ft/ft 17.896 k-ft/ft +1.20D+E PASS 0.05860 1-way Shear (+X) 5.559 psi 94.868 psi +1.20D+E PASS 0.04090 1-way Shear (-X) 3.880 psi 94.868 psi +1.20D-E PASS 0.01062 1-way Shear (+Z) 1.007 psi 94.868 psi +1.20D+E PASS 0.01062 1-way Shear (-Z) 1.007 psi 94.868 psi +1.20D+E PASS 0.05796 2-way Punching 10.996 psi 189.737 psi +1.20D+E Top reinforcing mat required (see 'Bending' tab). Hand check required for anchor pullout. Detailed Results Rotation Axis &ZeccXecc Actual Soil Bearing Stress @ Location Actual / Allow Soil Bearing (in)Gross Allowable Bottom, -Z Top, +Z Left, -X Right, +X RatioLoad Combination... X-X, D Only 1.50 n/a0.3041 0.3041 n/a 0.2030.0n/a X-X, +0.60D 1.50 n/a0.1825 0.1825 n/a 0.1220.0n/a X-X, +D+0.70E 1.50 n/a0.3168 0.3168 n/a 0.2110.0n/a X-X, +D+0.5250E 1.50 n/a0.3137 0.3137 n/a 0.2090.0n/a X-X, +0.60D+0.70E 1.50 n/a0.1952 0.1952 n/a 0.1300.0n/a Z-Z, D Only 1.50 0.2127n/a n/a 0.3956 0.264n/a9.113 Z-Z, +0.60D 1.50 0.1276n/a n/a 0.2373 0.158n/a9.113 Z-Z, +D+0.70E 1.50 0.1601n/a n/a 0.4736 0.316n/a14.991 Z-Z, +D+0.5250E 1.50 0.1732n/a n/a 0.4541 0.303n/a13.566 Z-Z, +0.60D+0.70E 1.50 0.07504n/a n/a 0.3153 0.210n/a18.654 Rotation Axis & Overturning Stability Load Combination...StatusOverturning Moment Resisting Moment Stability Ratio X-X, D Only None 0.0 k-ft Infinity OK X-X, +0.60D None 0.0 k-ft Infinity OK X-X, +D+0.70E None 0.0 k-ft Infinity OK X-X, +D+0.5250E None 0.0 k-ft Infinity OK X-X, +0.60D+0.70E None 0.0 k-ft Infinity OK Z-Z, D Only None 207.219 k-ft Infinity OK Z-Z, +0.60D None 124.331 k-ft Infinity OK Z-Z, +D+0.70E 10.80 k-ft 174.187 k-ft 16.128 OK Z-Z, +D+0.5250E 8.10 k-ft 172.919 k-ft 21.347 OK Z-Z, +0.60D+0.70E 10.80 k-ft 106.542 k-ft 9.865 OK Force Application Axis Sliding Stability All units k Load Combination...StatusSliding Force Resisting Force Stability Ratio X-X, D Only 0.0 k 7.527 k No Sliding OK X-X, +0.60D 0.0 k 4.516 k No Sliding OK X-X, +D+0.70E 1.581 k 7.842 k 4.961 OK X-X, +D+0.5250E 1.185 k 7.763 k 6.548 OK X-X, +0.60D+0.70E 1.581 k 4.831 k 3.056 OK Z-Z, D Only 0.0 k 7.527 k No Sliding OK Z-Z, +0.60D 0.0 k 4.516 k No Sliding OK General Footing LIC# : KW-06017366, Build:20.24.12.17 B&J HBK, INC. (c) ENERCALC, LLC 1982-2025 DESCRIPTION:Generator Footing - Case 2 Project File: KPRS McGuff TI.ec6 Project Title: Engineer: Project ID: Project Descr: Force Application Axis Sliding Stability All units k Load Combination...StatusSliding Force Resisting Force Stability Ratio Z-Z, +D+0.70E 0.0 k 7.842 k No Sliding OK Z-Z, +D+0.5250E 0.0 k 7.763 k No Sliding OK Z-Z, +0.60D+0.70E 0.0 k 4.831 k No Sliding OK Flexure Axis & Load Combination in^2 in^2 in^2 k-ft As Req'd Footing Flexure Tension k-ft Actual As StatusMu Side Surface Gvrn. As Phi*Mn X-X, +1.20D 0.3930 +Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +1.20D 0.3930 -Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +0.90D 0.2947 +Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +0.90D 0.2947 -Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +1.20D+E 0.4617 +Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +1.20D+E 0.4617 -Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +1.20D-E 0.3242 +Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +1.20D-E 0.3242 -Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +0.90D+E 0.3635 +Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +0.90D+E 0.3635 -Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +0.90D-E 0.2260 +Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK X-X, +0.90D-E 0.2260 -Z Bottom 0.1944 ACI 7.6.1.1 0.2687 17.896 OK Z-Z, +1.20D 2.231 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D 2.230 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D 1.673 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D 1.673 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D+E 0.5021 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D+E 3.307 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D-E 3.960 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +1.20D-E 1.154 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D+E 0.05561 -X Top 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D+E 2.749 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D-E 3.402 -X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK Z-Z, +0.90D-E 0.5966 +X Bottom 0.1944 ACI 7.6.1.1 0.2818 18.760 OK One Way Shear X Vu @ +XLoad Combination... Vu @ -X Vu:Max Vu / Phi*VnPhi Vn Status +1.20D 2.88 3.76 3.76 94.87 0.04psipsipsipsi OK +0.90D 2.16 2.82 2.82 94.87 0.03psipsipsipsi OK +1.20D+E 1.87 5.56 5.56 94.87 0.06psipsipsipsi OK +1.20D-E 3.88 1.97 3.88 94.87 0.04psipsipsipsi OK +0.90D+E 1.15 4.62 4.62 94.87 0.05psipsipsipsi OK +0.90D-E 3.16 1.03 3.16 94.87 0.03psipsipsipsi OK One Way Shear Z Load Combination... Vu @ -Z Vu @ +Z Vu:Max Vu / Phi*VnPhi Vn Status +1.20D 0.86 0.86 3.76 94.87 0.04psipsipsipsi OK +0.90D 0.64 0.64 2.82 94.87 0.03psipsipsipsi OK +1.20D+E 1.01 1.01 5.56 94.87 0.06psipsipsipsi OK +1.20D-E 0.71 0.71 3.88 94.87 0.04psipsipsipsi OK +0.90D+E 0.79 0.79 4.62 94.87 0.05psipsipsipsi OK +0.90D-E 0.49 0.49 3.16 94.87 0.03psipsipsipsi OK Vu / Phi*Vn Two-Way "Punching" Shear All units k StatusVu Phi*VnLoad Combination... +1.20D 9.36 189.74 0.04933 OKpsipsi +0.90D 7.02 189.74 0.037 OKpsipsi +1.20D+E 11.00 189.74 0.05796 OKpsipsi +1.20D-E 7.72 189.74 0.0407 OKpsipsi +0.90D+E 8.66 189.74 0.04562 OKpsipsi +0.90D-E 5.38 189.74 0.02837 OKpsipsi PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA - S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis Generator Enclosure Design BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Design Wind Load per ASCE 7-16 §29.3 Building Data Risk Category:II ASCE 7-16 Table 1.5-1 Exposure Category:C ASCE 7-16 §26.7 Site Elevation:41.2 ft V =95 mph Basic wind speed ASCE 7-16 Fig. 26.5-1A, B, or C Solid Freestanding Wall or Sign Data h =11.00 ft Overall height B =22.25 ft Sign/wall length s =11 ft Sign/wall height Lr =12.75 ft Return corner length Design Wind Load qh = 0.00256 Kz Kzt Kd Ke V2 =16.6 psf ASCE 7-16 Eq. 26.10-1 Kz =0.85 Velocity pressure exposure coefficient ASCE 7-16 Table 26.10-1 Kzt =1.0 Topographic factor ASCE 7-16 §26.8.2 Kd =0.85 Wind directionality factor ASCE 7-16 Table 26.6-1 Ke =1.0 Ground elevation factor ASCE 7-16 Table 26.9-1 G =0.85 Gust effect factor ASCE 7-16 §26.11 β = 1.00 Corner reduction factor ASCE 7-16 Fig. 29.3-1 ε =1.00 Ratio of solid to gross area for wall, sign, or structure F =β qh G Cf As ASCE 7-16 Eq. 29.3-1 Cf qw (psf)Fw (lb)Cf qw (psf)Fw (lb) 1.40 19.8 4846 2.26 25.6 3093 2.26 25.6 3093 1.50 17.0 2061 1.50 17.0 2061 1.15 13.0 1575 1.15 13.0 3.254 0.00 0.0 0 0.00 0.0 0 0.00 0.0 0 5156 0.00 0.0 0 0.00 0.0 0 C f from ASCE 7-16 Fig. 29.3-1 6728.3 Notes: 2s to 3s 3s to 4s 3s to 10s 4s to 5s FTotal 5s to 10s >10s FTotal 1. β applied to Case C 0 to s zone for B/s ≥ 5 2. Reduction of (1.8 - s/h) applied to Case C where s/h > 0.8 s to 2s 2s to 3s Case A and B Case C Case C 0 to s 0 to s s to 2s Figure from ASCE7-10 PROJECT PROJECT NO. ITEM McGuff TI Freestanding Wall Wind Load ENGINEER DATE SHEET NO. 1/8/2025 CL S24-0254 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Generator Enclousre Wall Design Wall Demands H =11 ft Height of wall W p =21 psf Weight of wall SDS =1.05 Short period spectral acceleration Ie =1 Importance factor Fp =8.8 psf Out-of-plane wall seismic demand pwind =25.6 psf Wind demand (See calculations) Wall Stud Design L =11 ft Length of stud tw =1.33 ft Tributary width of stud pmax,ASD =15.36 psf Maximum lateral ASD level demand See Attached CFS Designer Report HSS Member Design H =11 ft Height of post pseis =8.8 psf Seismic demand on post pwind =25.6 psf Wind demand on post (Controls Design) Δlim =1.1 in Deflection limit for canatilver post (2*L/240) See Attached RISA3D Model HSS Post Footing Design See Pole Foundation Calculations HSS Post Anchorage At (E) Wall Footing pwind =25.6 psf Wind demand (See calculations) H =11 ft Height of post tw,post =2.5 ft Trib width for posts at (E) wall footing Mu =7744 lb-ft Moment demand at base of post Vu =704 lbs Shear demand at base of post See Attached Anchorage Calculations PROJECT CLIENT LOCATION ITEM McGuff TI KPRS Inc Santa Ana, CA Enclosure S24-0254 SHEET # ENGINEER DATE JOB # 3/12/2025 C. Landis BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH Section : 362S162-43 (33 ksi) @ 16" o.c. Single C Stud (punched) Maxo =612.0 ft-lb 1739.1 lbVa =I =0.71 in^4 Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations Bridging Connectors - Design Method =AISI S100 Span KyLy, KtLt Flexual, Distortional Connector Stress Ratio Axial Span 60.0", 60.0"60.0", 132.0"LSUBH3.25 (Min)0.54 Web Crippling Support Load (lb)(in)Max Int.Stiffener? Bearing Pa M (lb)(ft-lbs) R2 112.64 --Shear Connection w/ clip--NO R1 112.64 --Stud/Track Design, Ref Connectors--NO Gravity Load Type Load (lb) Uniform 28.00plf Code Check Required Interaction NotesAllowed Max. Axial, lbs 308.0(c)14%KΦ=0.00 lb-in/in Max KL/r = 982169.1(c)Span Max. Shear, lbs 112.6 17%Shear (Punched)675.7 Max. Moment (MaFy, Ma-dist), ft-lbs 309.8 51%MaFy (control),KΦ=0.00 lb-in/in612.0 Moment Stability, ft-lbs 309.8 56%553.1 Shear/Moment 0.51 51%Shear 0.0, Moment 309.81.00 Axial/Moment 0.63 63%Axial 163.9(c), Moment 308.51.00 Deflection Span, in 0.226 --meets L/585-- Support Rx(lb)Ry(lb)Simpson Strong-Tie Connector Connector Interaction Anchor Interaction 10.10 %R2 112.6 0.0 18.47 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 51.15 %R1 112.6 308.0 25.82 %362T125-33 (33) & (1) .157" SST PDPA/PDPAT-62KP to steel (3/16" to 1/2" thickness) * Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:McGuff CFS Designer Model:Exterior Wall Stud 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 03/12/2025 Simpson Strong-Tie® CFS Designer™ 5.2.7.0 <Licensed Company> CLandis SK-1 Mar 12, 2025 at 02:37 PM Generator Enclosure Wall RI… Company Designer Job Number Model Name : : : : <Licensed Company> CLandis Checked By : __________ 3/12/2025 2:39:28 PM RISA-3D Version 22 [ Generator Enclosure Wall RISA Model.r3… Page 1 Node Coordinates Label X [ft] Y [ft] Z [ft] Detach From Diaphragm 1 N1 0 0 0 2 N2 9 0 0 3 N3 13.25 0 0 4 N4 0 11 0 5 N5 9 11 0 6 N6 13.25 11 0 7 N7 -4.25 0 0 8 N8 -4.25 11 0 9 N9 0 8 0 10 N10 9 8 0 11 N11 -10 0 0 12 N12 -10 11 0 13 N13 -14.33 0 0 14 N14 -14.33 11 0 15 N15 -18.66 0 0 16 N16 -18.66 11 0 Hot Rolled Steel Properties Label E [ksi] G [ksi] Nu Therm. Coeff. [1e⁵°F⁻¹] Density [k/ft³] Yield [ksi] Ry Fu [ksi] Rt 1 A992 29000 11154 0.3 0.65 0.49 50 1.1 65 1.1 2 A36 Gr.36 29000 11154 0.3 0.65 0.49 36 1.5 58 1.2 3 A572 Gr.50 29000 11154 0.3 0.65 0.49 50 1.1 65 1.1 4 A500 Gr.B RND 29000 11154 0.3 0.65 0.527 42 1.4 58 1.3 5 A500 Gr.B RECT 29000 11154 0.3 0.65 0.527 46 1.4 58 1.3 6 A500 Gr.C RND 29000 11154 0.3 0.65 0.527 46 1.4 62 1.3 7 A500 Gr.C RECT 29000 11154 0.3 0.65 0.527 50 1.4 62 1.3 8 A53 Gr.B 29000 11154 0.3 0.65 0.49 35 1.6 60 1.2 9 A1085 29000 11154 0.3 0.65 0.49 50 1.4 65 1.3 10 A913 Gr.65 29000 11154 0.3 0.65 0.49 65 1.1 80 1.1 Hot Rolled Steel Section Sets Label Shape Type Design List Material Design Rule Area [in²] Iyy [in⁴] Izz [in⁴] J [in⁴] 1 HSS Post (3.5")HSS3.5X3.5X6 Column Tube A500 Gr.C RECT Typical 4.09 6.49 6.49 11.2 2 HSS Beam (3.5")HSS3.5X3.5X6 Beam Tube A500 Gr.C RECT Typical 4.09 6.49 6.49 11.2 3 HSS Post (4")HSS4X4X8 Column Tube A500 Gr.C RECT Typical 6.02 11.9 11.9 21 4 HSS Beam (4")HSS4X4X4 Beam Tube A500 Gr.C RECT Typical 3.37 7.8 7.8 12.8 5 HR1 HSS5X4X6 Column Tube A500 Gr.C RECT Typical 5.48 12.6 17.9 24.9 6 HR2 HSS5X4X6 Beam Tube A500 Gr.C RECT Typical 5.48 12.6 17.9 24.9 Member Primary Data Label I Node J Node Section/Shape Type Design List Material Design Rule 1 M1 N1 N4 HSS Post (4")Column Tube A500 Gr.C RECT Typical 2 M2 N2 N5 HSS Post (4")Column Tube A500 Gr.C RECT Typical 3 M3 N3 N6 HSS Post (4")Column Tube A500 Gr.C RECT Typical 4 M4 N4 N5 HSS Beam (4")Beam Tube A500 Gr.C RECT Typical 5 M5 N5 N6 HSS Beam (4")Beam Tube A500 Gr.C RECT Typical 6 M6 N8 N4 HSS Beam (4")Beam Tube A500 Gr.C RECT Typical 7 M7 N8 N7 HSS Post (4")Column Tube A500 Gr.C RECT Typical 8 M8 N9 N10 HSS Beam (4")Beam Tube A500 Gr.C RECT Typical 9 M9 N16 N14 HSS Beam (4")Beam Tube A500 Gr.C RECT Typical 10 M10 N14 N12 HSS Beam (4")Beam Tube A500 Gr.C RECT Typical Company Designer Job Number Model Name : : : : <Licensed Company> CLandis Checked By : __________ 3/12/2025 2:39:28 PM RISA-3D Version 22 [ Generator Enclosure Wall RISA Model.r3… Page 2 Member Primary Data (Continued) Label I Node J Node Section/Shape Type Design List Material Design Rule 11 M11 N15 N16 HSS Post (4")Column Tube A500 Gr.C RECT Typical 12 M12 N13 N14 HSS Post (4")Column Tube A500 Gr.C RECT Typical 13 M13 N11 N12 HSS Post (4")Column Tube A500 Gr.C RECT Typical Nodal Loads and Enforced Displacements No Data to Print... Member Point Loads No Data to Print... Member Distributed Loads (BLC 3 : BLC 2 Transient Area Loads) Member LabelDirectionStart Magnitude [k/ft, F, psf, k-ft/ft]End Magnitude [k/ft, F, psf, k-ft/ft]Start Location [(ft, %)]End Location [(ft, %)] 1 M5 Z 0.282 0.282 0 4.25 2 M6 Z 0.282 0.282 0 4.25 3 M4 Z 0.038 0.038 0 9 4 M8 Z 0.038 0.038 0 9 5 M1 Z 0.115 0.115 0 8 6 M2 Z 0.115 0.115 0 8 7 M9 Z 0.282 0.282 0 4.33 8 M10 Z 0.282 0.282 0 4.33 Member Area Loads (BLC 2 : W) Node ANode BNode CNode DDirection Load Direction A Magnitude [psf] B Magnitude [psf] C Magnitude [psf] D Magnitude [psf] Exclude Braces 1 N5 N6 N3 N2 Z B-C 25.6 25.6 25.6 25.6 Yes 2 N8 N4 N1 N7 Z B-C 25.6 25.6 25.6 25.6 Yes 3 N4 N5 N10 N9 Z B-C 25.6 25.6 25.6 25.6 Yes 4 N9 N10 N2 N1 Z A-B 25.6 25.6 25.6 25.6 Yes 5 N16 N12 N11 N15 Z B-C 25.6 25.6 25.6 25.6 Yes Basic Load Cases BLC Description Category Y Gravity Distributed Area(Member) 1 DL DL -1 2 W WL 5 3 BLC 2 Transient Area Loads None 8 Load Combinations Description Solve P-Delta BLC Factor BLC Factor BLC Factor BLC Factor 1 Deflection 1 Yes Y DL 1 2 Deflection 2 Yes Y LL 1 3 Deflection 3 Yes Y DL 1 LL 1 4 ASCE Strength 1 Yes Y DL 1.4 5 ASCE Strength 2 (a)Yes Y DL 1.2 LL 1.6 LLS 1.6 6 ASCE Strength 3 (b) (a)Yes Y DL 1.2 WL 0.5 7 ASCE Strength 3 (b) (b)Yes Y DL 1.2 WL -0.5 8 ASCE Strength 4 (a) (a)Yes Y DL 1.2 WL 1 LL 0.5 LLS 1 9 ASCE Strength 4 (a) (b)Yes Y DL 1.2 WL -1 LL 0.5 LLS 1 10 ASCE Strength 5 (a)Yes Y DL 0.9 WL 1 11 ASCE Strength 5 (b)Yes Y DL 0.9 WL -1 12 Wind Deflection Yes Y DL 1 WL 0.42 Company Designer Job Number Model Name : : : : <Licensed Company> CLandis Checked By : __________ 3/12/2025 2:39:28 PM RISA-3D Version 22 [ Generator Enclosure Wall RISA Model.r3… Page 3 Envelope Node Reactions Node Label X [k] LC Y [k] LC Z [k] LC MX [k-ft] LC MY [k-ft] LC MZ [k-ft] LC 1 N1 max 0.005 4 0.54 4 1.65 11 11.237 9 0.225 8 0 2 2 min 0 2 0 2 -1.65 10 -11.237 8 -0.225 9 -0.014 4 3 N2 max 0 2 0.54 4 1.65 11 11.237 9 0.225 9 0.014 4 4 min -0.005 4 0 2 -1.65 10 -11.237 8 -0.225 8 0 2 5 N3 max 0 2 0.367 4 0.815 9 8.985 9 0.453 9 0.004 4 6 min -0.001 4 0 2 -0.815 8 -8.985 8 -0.453 8 0 2 7 N7 max 0.001 4 0.367 4 0.815 9 8.985 9 0.453 8 0 2 8 min 0 2 0 2 -0.815 8 -8.985 8 -0.453 9 -0.004 4 9 N15 max 0.001 4 0.371 4 0.795 9 8.855 9 0.284 8 0 2 10 min 0 2 0 2 -0.795 8 -8.855 8 -0.284 9 -0.005 4 11 N13 max 0 9 0.425 4 0.85 11 9.223 9 0 9 0 4 12 min 0 2 0 2 -0.85 10 -9.223 8 0 8 0 10 13 N11 max 0 2 0.371 4 0.795 9 8.855 9 0.284 9 0.005 4 14 min -0.001 4 0 2 -0.795 8 -8.855 8 -0.284 8 0 2 15 Totals:max 0 4 2.982 4 7.367 11 16 min 0 2 0 2 -7.367 10 Envelope AISC 15TH (360-16): LRFD Member Steel Code Checks Member Shape Code CheckLoc[ft]LCShear CheckLoc[ft]Dir LCphi*Pnc [k]phi*Pnt [k]phi*Mn y-y [k-ft]phi*Mn z-z [k-ft] Cb Eqn 1 M1 HSS4X4X8 0.391 0 9 0.034 0 z 9 142.203 270.9 28.875 28.875 2.147H1-1b 2 M2 HSS4X4X8 0.391 0 9 0.034 0 z 9 142.203 270.9 28.875 28.875 2.147H1-1b 3 M3 HSS4X4X8 0.312 0 9 0.03 11 z 9 142.203 270.9 28.875 28.875 2.17 H1-1b 4 M4 HSS4X4X4 0.036 4.5 9 0.004 9 z 11 104.91 151.65 17.588 17.588 2.167H1-1b 5 M5 HSS4X4X4 0.041 1.284 9 0.02 4.25 z 9 139.688 151.65 17.588 17.588 2.631H1-1b 6 M6 HSS4X4X4 0.041 2.966 9 0.02 0 z 9 139.688 151.65 17.588 17.588 2.631H1-1b 7 M7 HSS4X4X8 0.312 11 9 0.03 11 z 9 142.203 270.9 28.875 28.875 2.17 H1-1b 8 M8 HSS4X4X4 0.028 4.5 9 0.004 9 z 11 104.91 151.65 17.588 17.588 2.022H1-1b 9 M9 HSS4X4X4 0.048 2.751 9 0.025 0 z 9 139.252 151.65 17.588 17.588 2.071H1-1b 10 M10 HSS4X4X4 0.048 1.579 9 0.025 4.33 z 9 139.252 151.65 17.588 17.588 2.071H1-1b 11 M11 HSS4X4X8 0.308 0 9 0.023 11 z 9 142.203 270.9 28.875 28.875 2.173H1-1b 12 M12 HSS4X4X8 0.321 0 9 0.013 11 z 9 142.203 270.9 28.875 28.875 1 H1-1b 13 M13 HSS4X4X8 0.308 0 9 0.023 11 z 9 142.203 270.9 28.875 28.875 2.173H1-1b Pole Foundation Per 2022 CBC Design Criteria bf =2 ft Diameter or diagonal dimension of footing d =4 ft Depth of footing h =11 ft Height above grade of application of load "P" Af =3.14 ft2 Area of circular footing qn =1500 psf Allowable net soil pressure at depth d S3 =800 psf Allowable lateral soil-bearing pressure at depth d1 Loading W p =386 lb Gravity demand on pole footing MW base =4176 lb ft Moment at finish grade Peq =380 lb Equivalent lateral load at height "h" above grade Footing Design OK Depth dreq = √(4.25*P*h/(S3*b)) =3.33 Ref. 2022 CBC Eq. 18-2 Area Areq = W p/qn =0.26 1Increase for poles per 1806.3.4 PROJECT PROJECT NO. ITEM McGuff TI Pole Foundation ENGINEER DATE SHEET NO. 2/14/2025 C. Landis S24-0154 BRANDOW & JOHNSTON STRUCTURAL & CIVIL ENGINEERS | LOS ANGELES NEWPORT BEACH www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 1 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 1 3/12/2025 Specifier's comments: 1 Input data Anchor type and diameter: Hex Head ASTM F 1554 GR. 36 5/8 Item number: not available Specification text:Æ 5/8 in Hex Head ASTM F 1554 GR. 36 with 8 in nominal embedment depth per Technical data , cast in place installation per MPII, Effective embedment depth: hef = 8.000 in. Material: ASTM F 1554 Evaluation Service Report: Hilti Technical Data Issued I Valid: - | - Proof: Design Method ACI 318-19 / CIP Shear edge breakout verification: Row closest to edge (Case 3 only from ACI 318-19 Fig. R.17.7.2.1b) Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.500 in. Anchor plateR : lx x ly x t = 12.000 in. x 8.000 in. x 0.500 in.; (Recommended plate thickness: not calculated) Profile: Square HSS (AISC), HSS4X4X.25; (L x W x T) = 4.000 in. x 4.000 in. x 0.250 in. Base material: cracked concrete, 2500, fc' = 2,500 psi; h = 12.000 in. Reinforcement: tension: not present, shear: not present; edge reinforcement: none or < No. 4 bar R - The anchor calculation is based on a rigid anchor plate assumption. Geometry [in.] & Loading [lb, ft.lb] www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 2 3/12/2025 1.1 Design results Case Description Forces [lb] / Moments [ft.lb]Seismic Max. Util. Anchor [%] 1 Combination 1 N = 0; Vx = 704; Vy = 0; Mx = 0.000; My = 7,744.000; Mz = 0.000; no 76 2 Load case/Resulting anchor forces Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor Tension force Shear force Shear force x Shear force y 1 4,800 212 205 -52 2 0 212 205 52 3 4,800 156 147 -52 4 0 156 147 52 Max. concrete compressive strain: 0.22 [‰] Max. concrete compressive stress: 975 [psi] Resulting tension force in (x/y)=(-4.500/0.000): 9,600 [lb] Resulting compression force in (x/y)=(5.180/0.000): 9,600 [lb] Anchor forces are calculated based on the assumption of a rigid anchor plate. 3 Tension load Load Nua [lb]Capacity f Nn [lb]Utilization bN = Nua/f Nn Status Steel Strength*4,800 9,831 49 OK Pullout Strength*4,800 6,356 76 OK Concrete Breakout Failure**9,600 15,483 63 OK Concrete Side-Face Blowout, direction **N/A N/A N/A N/A * highest loaded anchor **anchor group (anchors in tension) www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 3 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 3 3/12/2025 3.1 Steel Strength Nsa = Ase,N futa ACI 318-19 Eq. (17.6.1.2) f Nsa ³ Nua ACI 318-19 Table 17.5.2 Variables Ase,N [in.2]futa [psi] 0.23 58,000 Calculations Nsa [lb] 13,108 Results Nsa [lb]f steel f Nsa [lb]Nua [lb] 13,108 0.750 9,831 4,800 3.2 Pullout Strength NpN = y c,p Np ACI 318-19 Eq. (17.6.3.1) Np = 8 Abrg f' c ACI 318-19 Eq. (17.6.3.2.2a) f NpN ³ Nua ACI 318-19 Table 17.5.2 Variables y c,p Abrg [in.2]l a f' c [psi] 1.000 0.45 1.000 2,500 Calculations Np [lb] 9,080 Results Npn [lb]f concrete f Npn [lb]Nua [lb] 9,080 0.700 6,356 4,800 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 4 3/12/2025 3.3 Concrete Breakout Failure Ncbg = (ANc ANc0)y ec,N y ed,N y c,N y cp,N Nb ACI 318-19 Eq. (17.6.2.1b) f Ncbg ³ Nua ACI 318-19 Table 17.5.2 ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANc0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.1.4) y ec,N = (1 1 + 2 e' N 3 hef )£ 1.0 ACI 318-19 Eq. (17.6.2.3.1) y ed,N = 0.7 + 0.3 (ca,min 1.5hef)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) y cp,N = MAX(ca,min cac , 1.5hef cac )£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b) Nb = kc l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables hef [in.]ec1,N [in.]ec2,N [in.]ca,min [in.]y c,N 8.000 0.000 0.000 6.000 1.000 cac [in.]kc l a f' c [psi] -24 1.000 2,500 Calculations ANc [in.2]ANc0 [in.2]y ec1,N y ec2,N y ed,N y cp,N Nb [lb] 552.00 576.00 1.000 1.000 0.850 1.000 27,153 Results Ncbg [lb]f concrete f Ncbg [lb]Nua [lb] 22,118 0.700 15,483 9,600 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 5 3/12/2025 4 Shear load Load Vua [lb]Capacity f Vn [lb]Utilization bV = Vua/f Vn Status Steel Strength*212 5,112 5 OK Steel failure (with lever arm)*N/A N/A N/A N/A Pryout Strength**704 37,159 2 OK Concrete edge failure in direction y+**712 6,029 12 OK * highest loaded anchor **anchor group (relevant anchors) When the input edge distance is set to "infinity", edge breakout verification is not performed in that direction 4.1 Steel Strength Vsa = 0.6 Ase,V futa ACI 318-19 Eq. (17.7.1.2b) f Vsteel ³ Vua ACI 318-19 Table 17.5.2 Variables Ase,V [in.2]futa [psi] 0.23 58,000 Calculations Vsa [lb] 7,865 Results Vsa [lb]f steel f Vsa [lb]Vua [lb] 7,865 0.650 5,112 212 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 6 3/12/2025 4.2 Pryout Strength Vcpg = kcp [(ANc ANc0)y ec,N y ed,N y c,N y cp,N Nb ] ACI 318-19 Eq. (17.7.3.1b) f Vcpg ³ Vua ACI 318-19 Table 17.5.2 ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANc0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.1.4) y ec,N = (1 1 + 2 e' N 3 hef )£ 1.0 ACI 318-19 Eq. (17.6.2.3.1) y ed,N = 0.7 + 0.3 (ca,min 1.5hef)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) y cp,N = MAX(ca,min cac , 1.5hef cac )£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b) Nb = kc l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables kcp hef [in.]ec1,N [in.]ec2,N [in.]ca,min [in.] 2 8.000 0.000 1.750 6.000 y c,N cac [in.]kc l a f' c [psi] 1.000 -24 1.000 2,500 Calculations ANc [in.2]ANc0 [in.2]y ec1,N y ec2,N y ed,N y cp,N Nb [lb] 759.00 576.00 1.000 0.873 0.850 1.000 27,153 Results Vcpg [lb]f concrete f Vcpg [lb]Vua [lb] 53,084 0.700 37,159 704 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 7 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 7 3/12/2025 4.3 Concrete edge failure in direction y+ Vcbg = (AVc AVc0)y ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-19 Eq. (17.7.2.1b) f Vcbg ³ Vua ACI 318-19 Table 17.5.2 AVc see ACI 318-19, Section 17.7.2.1, Fig. R 17.7.2.1(b)* AVc0 = 4.5 c2 a1 ACI 318-19 Eq. (17.7.2.1.3) y ec,V = (1 1 + e' v 1.5ca1 )£ 1.0 ACI 318-19 Eq. (17.7.2.3.1) y ed,V = 0.7 + 0.3(ca2 1.5ca1)£ 1.0 ACI 318-19 Eq. (17.7.2.4.1b) y h,V = √1.5ca1 ha ³ 1.0 ACI 318-19 Eq. (17.7.2.6.1) Vb = (7 (le da)0.2 √da)l a √f' c c1.5 a1 ACI 318-19 Eq. (17.7.2.2.1a) Variables ca1 [in.]ca2 [in.]ecV [in.]y c,V ha [in.] 6.000 -0.661 1.000 12.000 le [in.]l a da [in.]f' c [psi]y parallel,V 5.000 1.000 0.625 2,500 1.000 Calculations AVc [in.2]AVc0 [in.2]y ec,V y ed,V y h,V Vb [lb] 243.00 162.00 0.932 1.000 1.000 6,164 Results Vcbg [lb]f concrete f Vcbg [lb]Vua [lb] 8,613 0.700 6,029 712 *Anchor row defined by: Anchor 3, 4; Case 3 controls When the input edge distance is set to "infinity", edge breakout verification is not performed in that direction 5 Combined tension and shear loads, per ACI 318-19 section 17.8 bN bV z Utilization bN,V [%]Status 0.755 0.118 5/3 66 OK bNV = bz N + bz V <= 1 www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 8 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 8 3/12/2025 6 Warnings • The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility! • The equations presented in this report are based on imperial units. When inputs are displayed in metric units, the user should be aware that the equations remain in their imperial format. • Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs. • For additional information about ACI 318 strength design provisions, please go to https://viewer.joomag.com/profis-design-guide-us-en-summer-2021/0841849001625154758?short&/ Fastening meets the design criteria! www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 9 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 9 3/12/2025 Coordinates Anchor [in.] Anchor x y c-x c+x c-y c+y 1 -4.500 -2.500 ---11.000 2 4.500 -2.500 ---11.000 3 -4.500 2.500 ---6.000 4 4.500 2.500 ---6.000 7 Installation data Anchor type and diameter: Hex Head ASTM F 1554 GR. 36 5/8 Profile: Square HSS (AISC), HSS4X4X.25; (L x W x T) = 4.000 in. x 4.000 in. x 0.250 in. Item number: not available Hole diameter in the fixture: df = 0.687 in. Maximum installation torque: - Plate thickness (input): 0.500 in. Hole diameter in the base material: - in. Recommended plate thickness: not calculated Hole depth in the base material: 8.000 in. Minimum thickness of the base material: 8.922 in. Æ 5/8 in Hex Head ASTM F 1554 GR. 36 with 8 in nominal embedment depth per Technical data , cast in place installation per MPII www.hilti.com Hilti PROFIS Engineering 3.1.11 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 10 Company: Address: Phone I Fax: Design: Fastening point: | McGuff Enclosure Post Anchorage Page: Specifier: E-Mail: Date: 10 3/12/2025 8 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you. HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 CALIFORNIA GREEN NOTES CGN MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 FEC CA CR E NG I NE CENT ERL INE FEC FEC FE C FE C FE C E sc F 1 F 2 F 3 F 4 F 5 F 6 F 7 F 8F 9 F 10 F 11 F 12 ºª\1!|"@·#$ & ¬/% ( )=?¡¿ 23 4 567 8 9' 0 Q WE€R T Y U I O P A S D F G H J KLÑ ZX C V B N M;, :._->< ^[`*]+ ¨´Ç B loqm ay ús C o n tr o l A lt A lt G rC o n tr o l Im prPantP e t s isB loqD e sp lP au saIn te r R eP ág A vP ág In ic io In s er t S u pr F in B loqN u m/-* + In tr o 1 2 3 45 6 78 9 F in A vP ág In ic io R eP ág In s0S u pr. N u mL o ckC a ps S c r oll LockL o ck eth CR CR CR CR CR CA CA CA CA CA CA CA CA CA CACA CA CACA CA CA CA CA CA CA CR CR L L L L L L ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFER TO GENERAL NOTES IA-G1 AND IA-G2 FOR ADDITIONAL INFORMATION. 2. REPLACE SEALANT AT ALL EXTERIOR PANEL JOINTS PARTITION NOTES AREA NOT IN CONTRACT EXISTING PARTITION TO REMAIN, PROTECT IN PLACE. EXISTING DOOR TO REMAIN NEW DOOR, REFER TO DOOR SCHEDULE. EXISTING SIDELIGHT OR GLAZING TO REMAIN. NEW SIDELIGHT OR GLAZING. REFER TO KEYNOTES AND/OR ELEVATIONS FOR ADDITIONAL INFORMATION. WALL TYPE A: 3-5/8" X 16 GA. X 12'-0" HIGH MTL. STUDS @ 16" O.C. W/ (1) LAYER 5/8" GYP. BD. EA. SIDE . PROVIDE BUILDING STANDARD SEMI-RECESSED FIRE EXTINGUISHER CABINET. NEW MILLWORK TO BE CONSTRUCTED. REFER TO ELEVATIONS FOR ADDITIONAL INFORMATION. DOOR TAG, SEE DOOR SCHEDULE, SHEET IA-8.1. PARTITION LEGEND - WALL TYPE B: 3-5/8" X 16 GA. X 12'-0" HIGH MTL. STUDS @ 16" O.C. W/ (1) LAYER 6 MIL VISQUEEN ON INTERIOR SIDE AND (1) LAYER 5/8" GYP. BD. EA SIDE. . WALL TYPE C: 8" X 16 GA. X 12'-0" HIGH MTL. STUDS @ 16" O.C. W/ (1) LAYER 6 MIL VISQUEEN ON INTERIOR SIDE AND (1) LAYER 5/8" GYP. BD. EA SIDE. . WALL TYPE D: 3-5/8" X 16 GA. X 12'-0" HIGH MTL. STUDS @ 16" O.C. W/ (1) LAYER 6 MIL VISQUEEN ON INTERIOR SIDE AND (1) LAYER 5/8" GYP. BD. ON INTERIOR SIDE. . 12'-0" HIGH CHAIN LINK FENCING W/ 12'-0" GATE .X SECURITY CAMERA CARD READER 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR 402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 OFFICE 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH 308 SHIPPING AND RECEIVING 111 RECEIVING 116 DIGITAL PHOTO 123 STORAGE 127 SHIPPING 303 MAINTENANCE 16' - 1" 17 ' - 2 " 8' - 7 " 12 ' - 1 0 " 6' - 0 " 3' - 6 " 2' - 1 1 " 2' - 1 1 " WALK-IN REFRIGERATOR BY OTHERS EXISTING TRASH ENCLOSURE TO REMAIN FUTURE SECURE AREA 3 IA-5.1 116 123 308 11 ' - 5 " 70 ' - 0 " 6' - 0 " 5' - 3 " 70' - 0" B1 B1 B1 B1 B1 304A MEN 304B WOMEN 61' - 8" 22' - 0" 3 3 3 5' - 7"41' - 5"6' - 0" 5' - 3 " 54 ' - 4 " 4 4 4 4 4 4 4 1 2 30 3 304B 304A 5 EQ EQ 3' - 7 " 3' - 7 " 7' - 3"3' - 11" 1 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 2 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 3 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ F1 F1 F1 7 7 12 7 A 11 1 A 101 12 5 103104105106 102 108107 109A 112 113 124 124A 115 122114 126 114A 121 120A120A1120119 118 118A 120A2 40 1 401A 401B405405A 402403404 311311A 111 307 307 127 6 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 6' - 0 " 1' - 1 " NEW 8'-0" HIGH OPENING 6' - 0"5' - 6"6' - 0"5' - 6"6' - 0"17' - 2" 1 BRIGHTPICK AREA TO RECEIVE SELF-LEVELING COMPOUND.1 KEY NOTES 2 3 4 EPOXY FILL ALL GAPS AND CRACKS IN SLAB GREATER THAN 0.2 INCHES IN WIDTH NEW VISION GLAZING IN EXISTING WINDOW FRAMES NEW 16 GA. METAL BACKING PER DETAIL 5 NEW COMBINATION EYEWASH/ SHOWER UNIT. HAWS AXION MSR 8300-8309 6 RELOCATED WINDOW AND FRAME 7 NEW AIR CURTAIN AT COILING DOORS -MARS STD2 (STANDARD 2) SERIES STD2144-3U-0B NOT USED NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 1 PARTITION PLAN IA-1.1 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1 PRESCREEN CORRECTIONS 3/24/25 L L L L L L ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFER TO GENERAL NOTES IA-G1 AND IA-G2 FOR ADDITIONAL INFORMATION. 2. VERIFY EXISTING CONDITIONS AND NOTIFY H. HENDY ASSOCIATES OF ANY DISCREPANCIES. 3. WORK SHALL COMPLY FULLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES. 4. CONTRACTOR SHALL VERIFY CONDITION OF SLAB AND PATCH/REPAIR TO SMOOTH AND LEVEL AS REQUIRED TO RECEIVE FLOOR FINISHES. PATCH AND FILL ALL ABANDONED FLOOR CORES PRIOR TO INSTALLATION OF FINISHES. 5. DEMOLISH PARTITIONS, DOOR ASSEMBLIES AND SIDELIGHTS AS SHOWN ON PLAN. PATCH AND REPAIR ADJACENT CONSTRUCTION AS REQUIRED. EXISTING COLUMN FURRING TO REMAIN. TERMINATE RELATED ELECTRICAL BACK TO POINT OF ORIGIN. 6. AT PARTITIONS BEING DEMOLISHED, ALL EXISTING POWER/TELE-DATA RECEPTACLES TO BE REMOVED. DISCONNECT AND REMOVE ALL HOMERUN CONDUITS AND CONDUCTORS FROM RECEPTACLES BACK TO POINT OF ORIGIN AS REQUIRED. 7. REMOVE ALL FLOORING, BASE, WALLCOVERING, WHITEBOARDS & TACKBOARDS, U.O.N. SCRAPE FLOOR AND CLEAN/PREP FOR NEW FUTURE FLOOR FINISHES. 8. REMOVE EXISTING TENANT AND EGRESS SIGNAGE AND ANY MISC. SCREWS/NAILS IN WALLS. PATCH WALL AND PREP FOR NEW FINISHES. 9. REMOVE/REPLACE ALL OUTLETS THAT DO NOT MEET CODE OR CURRENT BUILDING STANDARD STYLE/FINISH. CONTRACTOR TO VERIFY IN FIELD AND PROVIDE COUNTS AND LOCATIONS. 10. REMOVE EXISTING POWER/TELE/DATA RECEPTACLES AND WALL FEEDS AS INDICATED BY "D", DO NOT BLANK PLATE. REMOVE ALL UNUSED CABLING/CONDUITS IN WALLS, FLOORS, AND ABOVE CEILING IN THEIR ENTIRETY. COORDINATE WITH POWER & SIGNAL PLANS TO REUSE/MODIFY EXISTING WHEN AVAILABLE. REMOVE ALL BLANK PLATES AND ALL ASSOCIATED LOW VOLTAGE CABLING THROUGHOUT WHERE INDICATED. 11. EXISTING WINDOW COVERINGS AT ALL PERIMETER WINDOWS TO REMAIN. CLEAN AND REPAIR FOR LIKE- NEW APPEARANCE. DEMOLITION NOTES EXISTING PARTITION TO REMAIN, PROTECT IN PLACE DEMOLISH EXISTING PARTITION REMOVE EXISTING MILLWORK REMOVE DOOR ASSEMBLY, SAVE FOR POTENTIAL REUSE DEMOLISH SIDELIGHT OR GLAZING. AREA NOT IN CONTRACT LEGEND 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 OFFICE 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH C A B M M M M D D D D FFF C J K J L J 54 ' - 4 " 22 ' - 1 " 28' - 7"41' - 5"6' - 2" 6' - 5 " M M M M M M M M M M M M MM M M M M 1 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 2 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 3 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ NNN P P 6 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ ROUGHEN AND REDUCE EXISTING CONCRETE SURFACE IN THIS AREA TO RECEIVE NEW SELF-LEVELING COMPOUND. GRIND ALL DIFFERENCES IN HEIGHT GREATER THAN .2 INCHES AND FILL ALL GAPS GREATER THAN .2 INCHES. A DEMOLITION PLAN KEY NOTES SAWCUT AND REMOVE EXISTING SLAB TO ACCOMODATE NEW PLUMBING.B EXISTING MILLWORK TO BE REMOVED INCLUDING EXISTING PLUMBING FIXTURES. PROTECT ALL SUPPLY AND DRAIN LINES IN PLACE. C EXISTING WINDOW TO BE REMOVEDD EXISTING COILING DOOR TO BE REMOVEDE EXISTING ONE WAY REFLECTIVE GLAZING TO BE REMOVED. PROTECT EXISTING FRAME AND PREPARE TO RECEIVE NEW GLAZING. F REMOVE DECALS AT WINDOWSG EXISTING DUCTWORK TO BE RELOCATED AWAY FROM PALLET RACK AREA.H EXISTING EXISTING MILLWORK TO BE REMOVEDJ EXISTING PLATFORM TO BE REMOVEDK EXISTING SLAB TO BE SAWCUT AND REMOVED TO ACCOMODATE TRENCHINGL REMOVE ALL CARPET, FLOORING, AND WALLBASE THROUGHOUTM EXISTING WINDOW AND FRAME TO BE REMOVED AND RE-INSTALLED IN NEW WALL.N EXISTING COILING DOOR AND TRACK TO BE REMOVED.P NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 1 DEMOLITION PLAN IA-1.1D MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 FEC CA CR FE C (E ) FEC (E) CR CR CR ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFER TO GENERAL NOTES IA-G1 AND IA-G2 FOR ADDITIONAL INFORMATION. 2. REPLACE SEALANT AT ALL EXTERIOR PANEL JOINTS PARTITION NOTES AREA NOT IN CONTRACT EXISTING PARTITION TO REMAIN, PROTECT IN PLACE. EXISTING DOOR TO REMAIN NEW DOOR, REFER TO DOOR SCHEDULE. EXISTING SIDELIGHT OR GLAZING TO REMAIN. NEW SIDELIGHT OR GLAZING. REFER TO KEYNOTES AND/OR ELEVATIONS FOR ADDITIONAL INFORMATION. WALL TYPE A: 3-5/8" X 16 GA. X 12'-0" HIGH MTL. STUDS @ 16" O.C. W/ (1) LAYER 5/8" GYP. BD. EA. SIDE . PROVIDE BUILDING STANDARD SEMI-RECESSED FIRE EXTINGUISHER CABINET. NEW MILLWORK TO BE CONSTRUCTED. REFER TO ELEVATIONS FOR ADDITIONAL INFORMATION. DOOR TAG, SEE DOOR SCHEDULE, SHEET IA-8.1. PARTITION LEGEND - WALL TYPE B: 3-5/8" X 16 GA. X 12'-0" HIGH MTL. STUDS @ 16" O.C. W/ (1) LAYER 6 MIL VISQUEEN ON INTERIOR SIDE AND (1) LAYER 5/8" GYP. BD. EA SIDE. . WALL TYPE C: 8" X 16 GA. X 12'-0" HIGH MTL. STUDS @ 16" O.C. W/ (1) LAYER 6 MIL VISQUEEN ON INTERIOR SIDE AND (1) LAYER 5/8" GYP. BD. EA SIDE. . WALL TYPE D: 3-5/8" X 16 GA. X 12'-0" HIGH MTL. STUDS @ 16" O.C. W/ (1) LAYER 6 MIL VISQUEEN ON INTERIOR SIDE AND (1) LAYER 5/8" GYP. BD. ON INTERIOR SIDE. . 12'-0" HIGH CHAIN LINK FENCING W/ 12'-0" GATE .X SECURITY CAMERA CARD READER 1 A B C D C.6 C.5 2 3 4 5 6 201 OFFICE 200 EXECUTIVE OFFICE 202 LOUNGE 203 RESTROOM 204 STORAGE 206A VETIBULE 205 STOR 206 OPEN OFFICE 207 OFFICE 208 MEN 209 WOMEN210 JAN 204A STOR 20 4 4 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 2' - 11" 200 200A 203 20 6 A 205 202 210 209 208 206 207 204A 201 5' - 11"5' - 0" 5 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 4 4 4 4 BRIGHTPICK AREA TO RECEIVE SELF-LEVELING COMPOUND.1 KEY NOTES 2 3 4 EPOXY FILL ALL GAPS AND CRACKS IN SLAB GREATER THAN 0.2 INCHES IN WIDTH NEW VISION GLAZING IN EXISTING WINDOW FRAMES NEW 16 GA. METAL BACKING PER DETAIL 5 NEW COMBINATION EYEWASH/ SHOWER UNIT. HAWS AXION MSR 8300-8309 6 RELOCATED WINDOW AND FRAME 7 NEW AIR CURTAIN AT COILING DOORS -MARS STD2 (STANDARD 2) SERIES STD2144-3U-0B NOT USED NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 2 PARTITION PLAN IA-1.2 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFER TO GENERAL NOTES IA-G1 AND IA-G2 FOR ADDITIONAL INFORMATION. 2. VERIFY EXISTING CONDITIONS AND NOTIFY H. HENDY ASSOCIATES OF ANY DISCREPANCIES. 3. WORK SHALL COMPLY FULLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES. 4. CONTRACTOR SHALL VERIFY CONDITION OF SLAB AND PATCH/REPAIR TO SMOOTH AND LEVEL AS REQUIRED TO RECEIVE FLOOR FINISHES. PATCH AND FILL ALL ABANDONED FLOOR CORES PRIOR TO INSTALLATION OF FINISHES. 5. DEMOLISH PARTITIONS, DOOR ASSEMBLIES AND SIDELIGHTS AS SHOWN ON PLAN. PATCH AND REPAIR ADJACENT CONSTRUCTION AS REQUIRED. EXISTING COLUMN FURRING TO REMAIN. TERMINATE RELATED ELECTRICAL BACK TO POINT OF ORIGIN. 6. AT PARTITIONS BEING DEMOLISHED, ALL EXISTING POWER/TELE-DATA RECEPTACLES TO BE REMOVED. DISCONNECT AND REMOVE ALL HOMERUN CONDUITS AND CONDUCTORS FROM RECEPTACLES BACK TO POINT OF ORIGIN AS REQUIRED. 7. REMOVE ALL FLOORING, BASE, WALLCOVERING, WHITEBOARDS & TACKBOARDS, U.O.N. SCRAPE FLOOR AND CLEAN/PREP FOR NEW FUTURE FLOOR FINISHES. 8. REMOVE EXISTING TENANT AND EGRESS SIGNAGE AND ANY MISC. SCREWS/NAILS IN WALLS. PATCH WALL AND PREP FOR NEW FINISHES. 9. REMOVE/REPLACE ALL OUTLETS THAT DO NOT MEET CODE OR CURRENT BUILDING STANDARD STYLE/FINISH. CONTRACTOR TO VERIFY IN FIELD AND PROVIDE COUNTS AND LOCATIONS. 10. REMOVE EXISTING POWER/TELE/DATA RECEPTACLES AND WALL FEEDS AS INDICATED BY "D", DO NOT BLANK PLATE. REMOVE ALL UNUSED CABLING/CONDUITS IN WALLS, FLOORS, AND ABOVE CEILING IN THEIR ENTIRETY. COORDINATE WITH POWER & SIGNAL PLANS TO REUSE/MODIFY EXISTING WHEN AVAILABLE. REMOVE ALL BLANK PLATES AND ALL ASSOCIATED LOW VOLTAGE CABLING THROUGHOUT WHERE INDICATED. 11. EXISTING WINDOW COVERINGS AT ALL PERIMETER WINDOWS TO REMAIN. CLEAN AND REPAIR FOR LIKE- NEW APPEARANCE. DEMOLITION NOTES EXISTING PARTITION TO REMAIN, PROTECT IN PLACE DEMOLISH EXISTING PARTITION REMOVE EXISTING MILLWORK REMOVE DOOR ASSEMBLY, SAVE FOR POTENTIAL REUSE DEMOLISH SIDELIGHT OR GLAZING. AREA NOT IN CONTRACT LEGEND 1 A B C D C.6 C.5 2 3 4 5 6 201 OFFICE 200 EXECUTIVE OFFICE 202 LOUNGE 203 RESTROOM 204 STORAGE 206A VETIBULE 205 STOR 206 OPEN OFFICE 207 OFFICE 208 MEN 209 WOMEN210 JAN J 1' - 2"6' - 0"7"6' - 0" 4" 3' - 4" M M M M M M MM M M MM M M C J 4 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 5 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ ROUGHEN AND REDUCE EXISTING CONCRETE SURFACE IN THIS AREA TO RECEIVE NEW SELF-LEVELING COMPOUND. GRIND ALL DIFFERENCES IN HEIGHT GREATER THAN .2 INCHES AND FILL ALL GAPS GREATER THAN .2 INCHES. A DEMOLITION PLAN KEY NOTES SAWCUT AND REMOVE EXISTING SLAB TO ACCOMODATE NEW PLUMBING.B EXISTING MILLWORK TO BE REMOVED INCLUDING EXISTING PLUMBING FIXTURES. PROTECT ALL SUPPLY AND DRAIN LINES IN PLACE. C EXISTING WINDOW TO BE REMOVEDD EXISTING COILING DOOR TO BE REMOVEDE EXISTING ONE WAY REFLECTIVE GLAZING TO BE REMOVED. PROTECT EXISTING FRAME AND PREPARE TO RECEIVE NEW GLAZING. F REMOVE DECALS AT WINDOWSG EXISTING DUCTWORK TO BE RELOCATED AWAY FROM PALLET RACK AREA.H EXISTING EXISTING MILLWORK TO BE REMOVEDJ EXISTING PLATFORM TO BE REMOVEDK EXISTING SLAB TO BE SAWCUT AND REMOVED TO ACCOMODATE TRENCHINGL REMOVE ALL CARPET, FLOORING, AND WALLBASE THROUGHOUTM EXISTING WINDOW AND FRAME TO BE REMOVED AND RE-INSTALLED IN NEW WALL.N EXISTING COILING DOOR AND TRACK TO BE REMOVED.P NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 2 DEMOLITION PLAN IA-1.2D MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1 A B C D C.6 C.5 2 3 4 5 6 2 2 3 3 3 3 4 5 5 5 5 5 5 5 5 5 5 1 1 5 5 5 16' - 3" 17 ' - 4 " 13 ' - 7 " 2' - 9 " 8' - 1 " 3' - 9"2' - 9" 1' - 8"17' - 7" 2' - 9 " 8' - 1 " 4" 9' - 0"6' - 9"9' - 6" 6" 3' - 10"10" 2' - 9 " 2' - 9" 1' - 5 " 2' - 9 " 12' - 2" 1 1 ALL NOTES ARE TYPICAL THROUGHOUT: 1. PROVIDE 5.17" OF POLYISOCYANURATE RIGID INSUALTION BOARDS WITH A TOTAL INSULATION VALUE OF R30 MIN. OVER ENTIRE ROOF SURFACE. 2. PROVIDE 1/4" DENSDECK PRIME PROTECTION BOARD TO COVER INSULATION. 3.PROVIDE NEW 135 MIL. FLEECE BACKED ADHERED TPO ROOFING AND FLASHING OVER ENTIRE ROOF SURFACE. EXTEND UP PARAPETS TO TERMINATE BENEATH COPING CAPS. ROOF NOTES ROOF KEYNOTES INFILL EXISTING SKYLIGHT OPENING -SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION1 NEW SKYLIGHT. PROVIDE CRICKETS AS REQUIRED FOR DRAINAGE. VELUX DYNAMIC DOME 4896 W/ FACTORY INSULATED ALUMINUM CURB ESR-4108 2 EXISTING SKYLIGHT TO BE REMOVED AND REPLACED. VELUX DYNAMIC DOME 4896 W/ FACTORY INSULATED ALUMINUM CURB ESR-4108 3 EXISTING ROOF LADDER AND HATCH TO REMAIN. PROTECT IN PLACE4 NEW ROOFTOP EQUIPMENT UNIT AND CURB. SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION5 2 2 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 ROOF PLAN IA-1.3 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1 PRESCREEN CORRECTIONS 3/24/25 ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFER TO GENERAL NOTES IA-G1 AND IA-G2 FOR ADDITIONAL INFORMATION. 2.ALL EXISTING ROOFING TO BE REMOVED DOWN TO EXISTING PLYWOOD DECKING. 3.ALL EXISTING FLASHING TO BE REMOVED. 4.EXAMINE EXISTING DECKING TO REMAIN. REPLACE ALL DAMAGED DECKING WITH NEW PLYWOOD TO MATCH EXISTING. 5.PROTECT EXISTING ROOFTOP EQUIPMENT AND EQUIPMENT PADS TO REMAIN. 6.EXAMINE EXISTING CURBS TO REMAIN. REPLACE ALL DAMAGED CURBS. ROOF DEMOLITION NOTES EXISTING ROOF DRAIN AND OVERFLOW TO REMAIN. PROTECT IN PLACE. PREVENT DEBRIS FROM ENTERING PIPING. ROOF DEMOLITION KEYNOTES A EXISTING SKYLIGHT TO BE REMOVED AND REPLACED.B EXISTING ROOF HATCH TO REMAIN. PROTECT IN PLACE. PROVIDE NEW GUARD RAILS AND LADDER EXTENSION PER CALOSHA REQUIREMENTS. C D EXISTING SKYLIGHT AND CURB TO BE REMOVED E EXISTING SPLIT SYSTEM TO BE REMOVED F EXISTING SPLIT SYSTEM TO BE REUSED FOR IT ROOM J EXISTING MECHANICAL UNIT K CUT AND REMOVE EXISTING ROOF SUBSTRATE TO ACCEPT NEW SKYLIGHT ALL NOTES ARE TYPICAL THROUGHOUT: 1. PROVIDE 5.17" OF POLYISOCYANURATE RIGID INSUALTION BOARDS WITH A TOTAL INSULATION VALUE OF R30 MIN. OVER ENTIRE ROOF SURFACE. 2. PROVIDE 1/4" DENSDECK PRIME PROTECTION BOARD TO COVER INSULATION. 3.PROVIDE NEW 135 MIL. FLEECE BACKED ADHERED TPO ROOFING AND FLASHING OVER ENTIRE ROOF SURFACE. EXTEND UP PARAPETS TO TERMINATE BENEATH COPING CAPS. ROOF NOTES 1 A B C D C.6 C.5 2 3 4 5 6 A A A A B B B B B B C D D E E E E F F J J J J J J J J J J 18' - 3"4' - 6" 15 ' - 9 " 8' - 6 " 6' - 1 0 " 8' - 6 " K K NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 ROOF DEMOLITION PLAN IA-1.3D MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 FE C (E ) FEC (E) CR CR CR ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFERENCE GENERAL NOTES ON IA-G1 AND IA-G-2 FOR ADDITIONAL INFORMATION 2. VERIFY EXISTING CONDITIONS AND NOTIFY H. HENDY ASSOCIATES OF ANY DISCREPANCIES. 3. WORK SHALL COMPLY FULLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES. 4. PROVIDE LEVEL-5 FINISH AT ALL GYP. BOARD CEILINGS/SOFFITS, U.O.N. 5.INSTALL R30 BATT INSULATION AND SCRIM AT UNDERSIDE OF EXISTING ROOF DECK. SCRIM COLOR: WHITE. 6.SEE DETAILS 2/ IA-7.1, 3/IA-7.1, AND 4/ IA-7.1 FOR SUSPENDED CEILING DETAILS CEILING NOTES 2 EXISTING 2 X 4 SUSPENDED CEILING GRID TO REMAIN. REPLACE EXISTING ACCOUSTICAL TILES WITH NEW TILES COMPATIBLE WITH EXISTING GRID. SEE NOTE 6.4 FOR ADDITIONAL INFORMATION CEILING HEIGHT EXPOSED CEILING ILLUMINATED EXIT SIGNS, DIRECTIONAL ARROW WHERE INDICATED. TIED TO BUILDING LIFE SAFETY OR BATTERY BACKUP. FOR EMERGENCY LIGHTING, REFER TO ELECTRICAL ENGINEERING PLANS. AREA NOT IN CONTRACT LEGEND X'-X" EXP. EXISTING 2 X 2 SUSPENDED CEILING GRID TO REMAIN. REPLACE EXISTING ACCOUSTICAL TILES WITH NEW TILES COMPATIBLE WITH EXISTING GRID. SEE NOTE 6.4 FOR ADDITIONAL INFORMATION EXISTING 2 X 4 FLOURESCENT FIXTURE. REMOVE AND REPLACE WITH NEW LED FIXTURE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION EXISTING 2 X 2 FLOURESCENT FIXTURE. REMOVE AND REPLACE WITH NEW LED FIXTURE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION NEW 2X4 LED FIXTURE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION EXISTING FLOURESCENT CAN LIGHT. REMOVE AND REPLACE WITH NEW LED FIXTURE EXISTING FLOURESCENT WALL WASHER FIXTURE. REMOVE AND REPLACE WITH NEW LED FIXTURE NEW 2X4 SUSPENDED CEILING SYSTEM TO MATCH EXISTING EXISTING METAL HALIDE HIGH BAY LIGHT FIXTURE. REMOVE AND REPLACE WITH NEW LED HIGH BAY FIXTURE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION EXISTING FLOURESCENT STRIP LIGHT TO REMAIN EXISTING FLOURESCENT FIXTURE TO REMAIN. 1.REMOVE ALL UNUSED WIRES, HANGERS, STRAPS, CLIPS, SCREWS, CABLING, CONDUITS OR ELECTRICAL WIRES AT EXPOSED CEILING CONDITIONS. 2.REMOVE INSULATION AT EXISTING DUCTWORK WHERE OCCURS. CLEAN EXTERIOR OF DUCTWORK AND PREP TO RECEIVE PAINT, U.N.O. 3.COORDINATE EXISTING DRAFT STOPS AT EXPOSED CEILING CONDITIONS WITH ARCHITECT. 4.PROVIDE RIGID DUCTWORK WITH SIDE DUCT MOUNTED SUPPLY DIFFUSERS AT ALL EXPOSED CEILING CONDITIONS, U.N.O. PROVIDE CUT SHEETS TO ARCHITECT FOR APPROVAL PRIOR TO ORDERING AND INSTALLATION. 5.PROVIDE ALUMINUM STRAPS TO MATCH ALUMINUM DUCTWORK FOR COVERING ALL DUCT SEALANT LOCATIONS, U.N.O. 6.ALL VISIBLE PIPING, DUCTS AND CONDUITS IN EXPOSED CEILING CONDITIONS SHALL HAVE 90 DEGREE ANGLES INSTEAD OF SHORTEST DISTANCE PATH. 7.PAINT ALL EXPOSED DUCTWORK, CONDUIT, PIPES, DECKING, SUPPORT BEAMS, ETC., U..N.O. REFER TO FINISH LEGEND FOR PAINT SPECIFICATION. 8.WHERE INSULATION IS REQUIRED BY CODE, PROVIDE BATT INSULATION WITH SCRIM AT UNDERSIDE OF DECK IN ALL EXPOSED CEILING CONDITIONS AT UNDERSIDE OF ROOF. COLOR OF SCRIM SHALL BE SELECTED BY ARCHITECT. 9.EXTEND EXISTING WALLS AND FURRING SURROUNDING EXPOSED CEILING FULL HEIGHT TO UNDERSIDE OF DECK ABOVE AS REQUIRED FOR CONSISTENT APPEARANCE. EXPOSED KICKERS SHALL BE AVOIDED. 10.COORDINATE LIGHT FIXTURE AND EXIT SIGN LOCATIONS IN ALL EXPOSED CEILINGS PRIOR TO ROUGH-IN TO CONFIRM LOCATIONS AND ANY POSSIBLE HEIGHT LIMITATIONS. NOTIFY ARCHITECT OF ANY CONFLICTS. 11.PROVIDE ALLOWANCE FOR MOUNTING LIGHT FIXTURES AND EXIT SIGNS UNDER UNI-STRUT AS NEEDED TO MAINTAIN FIXTURE LOCATIONS AT OBSTRUCTIONS. EXPOSED CEILING NOTES 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR 402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 OFFICE 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH 308 SHIPPING AND RECEIVING 111 RECEIVING 116 DIGITAL PHOTO 123 STORAGE 127 SHIPPING 303 MAINTENANCE +12'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" EXP. EXP. EXP. EXP. P 2 EP 1P 2 WALK-IN REFRIGERATOR BY OTHERS 304A MEN 304B WOMEN 1 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 1 REFLECTED CEILING PLAN IA-2.1 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1 PRESCREEN CORRECTIONS 3/24/25 1 A B C D C.6 C.5 2 3 4 5 6 A B C D C D C D C D C D C D C D C D C D C D C D C D C D C D C D C D C D E F A B GGGG G G G G GG ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFER TO GENERAL NOTES IA-G1 AND IA-G2 FOR ADDITIONAL INFORMATION. 2. VERIFY EXISTING CONDITIONS AND NOTIFY H. HENDY ASSOCIATES OF ANY DISCREPANCIES. 3. WORK SHALL COMPLY FULLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES. 4. CONTRACTOR SHALL VERIFY CONDITION OF SLAB AND PATCH/REPAIR TO SMOOTH AND LEVEL AS REQUIRED TO RECEIVE FLOOR FINISHES. PATCH AND FILL ALL ABANDONED FLOOR CORES PRIOR TO INSTALLATION OF FINISHES. 5. DEMOLISH PARTITIONS, DOOR ASSEMBLIES AND SIDELIGHTS AS SHOWN ON PLAN. PATCH AND REPAIR ADJACENT CONSTRUCTION AS REQUIRED. EXISTING COLUMN FURRING TO REMAIN. TERMINATE RELATED ELECTRICAL BACK TO POINT OF ORIGIN. 6. AT PARTITIONS BEING DEMOLISHED, ALL EXISTING POWER/TELE-DATA RECEPTACLES TO BE REMOVED. DISCONNECT AND REMOVE ALL HOMERUN CONDUITS AND CONDUCTORS FROM RECEPTACLES BACK TO POINT OF ORIGIN AS REQUIRED. 7. REMOVE ALL FLOORING, BASE, WALLCOVERING, WHITEBOARDS & TACKBOARDS, U.O.N. SCRAPE FLOOR AND CLEAN/PREP FOR NEW FUTURE FLOOR FINISHES. 8. REMOVE EXISTING TENANT AND EGRESS SIGNAGE AND ANY MISC. SCREWS/NAILS IN WALLS. PATCH WALL AND PREP FOR NEW FINISHES. 9. REMOVE/REPLACE ALL OUTLETS THAT DO NOT MEET CODE OR CURRENT BUILDING STANDARD STYLE/FINISH. CONTRACTOR TO VERIFY IN FIELD AND PROVIDE COUNTS AND LOCATIONS. 10. REMOVE EXISTING POWER/TELE/DATA RECEPTACLES AND WALL FEEDS AS INDICATED BY "D", DO NOT BLANK PLATE. REMOVE ALL UNUSED CABLING/CONDUITS IN WALLS, FLOORS, AND ABOVE CEILING IN THEIR ENTIRETY. COORDINATE WITH POWER & SIGNAL PLANS TO REUSE/MODIFY EXISTING WHEN AVAILABLE. REMOVE ALL BLANK PLATES AND ALL ASSOCIATED LOW VOLTAGE CABLING THROUGHOUT WHERE INDICATED. 11. EXISTING WINDOW COVERINGS AT ALL PERIMETER WINDOWS TO REMAIN. CLEAN AND REPAIR FOR LIKE- NEW APPEARANCE. DEMOLITION NOTES EXISTING PARTITION TO REMAIN, PROTECT IN PLACE DEMOLISH EXISTING PARTITION REMOVE EXISTING MILLWORK REMOVE DOOR ASSEMBLY, SAVE FOR POTENTIAL REUSE DEMOLISH SIDELIGHT OR GLAZING. AREA NOT IN CONTRACT LEGEND REMOVE ALL UNUSED CABLING AND CONDUIT FROM PLENUM SPACE CEILING DEMOLITOIN KEYNOTES A EXISTING SUSPENDED CEILING TO BE REMOVED. REMOVE LIGHT FIXTURES, HVAC, AND FIRE LIFE-SAFETY APPRERATUS B EXISTING ACOUSTICAL CEILING TILES TO BE REMOVED AND REPLACED. PROTECT EXISTING GRID IN PLACE. REPAIR OR REPLACE ALL DAMAGED GRID. C EXISTING LIGHT FIXTURES TO BE REMOVED AND REPLACED. SEE ELECTRICAL DRAWINGS FOR NEW LIGHT FIXTURE INFORMATION D EXISTING TRAPEEZE STRUCTURE TO BE REMOVED THROUGHOUT.E EXISTING DUCTWORK TO BE RELOCATED AWAY FROM PALLET RACK AREAF EXISTING HIGH-BAY LIGHTING TO BE REMOVED AND REPLACED. SEE ELECTRICAL DRAWINGS FOR NEW LIGHT FIXTURE INFORMATION. G NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 1 DEMOLITION CEILING PLAN IA-2.1D MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFERENCE GENERAL NOTES ON IA-G1 AND IA-G-2 FOR ADDITIONAL INFORMATION 2. VERIFY EXISTING CONDITIONS AND NOTIFY H. HENDY ASSOCIATES OF ANY DISCREPANCIES. 3. WORK SHALL COMPLY FULLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES. 4. PROVIDE LEVEL-5 FINISH AT ALL GYP. BOARD CEILINGS/SOFFITS, U.O.N. 5.INSTALL R30 BATT INSULATION AND SCRIM AT UNDERSIDE OF EXISTING ROOF DECK. SCRIM COLOR: WHITE. 6.SEE DETAILS 2/ IA-7.1, 3/IA-7.1, AND 4/ IA-7.1 FOR SUSPENDED CEILING DETAILS CEILING NOTES 2 EXISTING 2 X 4 SUSPENDED CEILING GRID TO REMAIN. REPLACE EXISTING ACCOUSTICAL TILES WITH NEW TILES COMPATIBLE WITH EXISTING GRID. SEE NOTE 6.4 FOR ADDITIONAL INFORMATION CEILING HEIGHT EXPOSED CEILING ILLUMINATED EXIT SIGNS, DIRECTIONAL ARROW WHERE INDICATED. TIED TO BUILDING LIFE SAFETY OR BATTERY BACKUP. FOR EMERGENCY LIGHTING, REFER TO ELECTRICAL ENGINEERING PLANS. AREA NOT IN CONTRACT LEGEND X'-X" EXP. EXISTING 2 X 2 SUSPENDED CEILING GRID TO REMAIN. REPLACE EXISTING ACCOUSTICAL TILES WITH NEW TILES COMPATIBLE WITH EXISTING GRID. SEE NOTE 6.4 FOR ADDITIONAL INFORMATION EXISTING 2 X 4 FLOURESCENT FIXTURE. REMOVE AND REPLACE WITH NEW LED FIXTURE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION EXISTING 2 X 2 FLOURESCENT FIXTURE. REMOVE AND REPLACE WITH NEW LED FIXTURE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION NEW 2X4 LED FIXTURE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION EXISTING FLOURESCENT CAN LIGHT. REMOVE AND REPLACE WITH NEW LED FIXTURE EXISTING FLOURESCENT WALL WASHER FIXTURE. REMOVE AND REPLACE WITH NEW LED FIXTURE NEW 2X4 SUSPENDED CEILING SYSTEM TO MATCH EXISTING EXISTING METAL HALIDE HIGH BAY LIGHT FIXTURE. REMOVE AND REPLACE WITH NEW LED HIGH BAY FIXTURE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION EXISTING FLOURESCENT STRIP LIGHT TO REMAIN EXISTING FLOURESCENT FIXTURE TO REMAIN. 1.REMOVE ALL UNUSED WIRES, HANGERS, STRAPS, CLIPS, SCREWS, CABLING, CONDUITS OR ELECTRICAL WIRES AT EXPOSED CEILING CONDITIONS. 2.REMOVE INSULATION AT EXISTING DUCTWORK WHERE OCCURS. CLEAN EXTERIOR OF DUCTWORK AND PREP TO RECEIVE PAINT, U.N.O. 3.COORDINATE EXISTING DRAFT STOPS AT EXPOSED CEILING CONDITIONS WITH ARCHITECT. 4.PROVIDE RIGID DUCTWORK WITH SIDE DUCT MOUNTED SUPPLY DIFFUSERS AT ALL EXPOSED CEILING CONDITIONS, U.N.O. PROVIDE CUT SHEETS TO ARCHITECT FOR APPROVAL PRIOR TO ORDERING AND INSTALLATION. 5.PROVIDE ALUMINUM STRAPS TO MATCH ALUMINUM DUCTWORK FOR COVERING ALL DUCT SEALANT LOCATIONS, U.N.O. 6.ALL VISIBLE PIPING, DUCTS AND CONDUITS IN EXPOSED CEILING CONDITIONS SHALL HAVE 90 DEGREE ANGLES INSTEAD OF SHORTEST DISTANCE PATH. 7.PAINT ALL EXPOSED DUCTWORK, CONDUIT, PIPES, DECKING, SUPPORT BEAMS, ETC., U..N.O. REFER TO FINISH LEGEND FOR PAINT SPECIFICATION. 8.WHERE INSULATION IS REQUIRED BY CODE, PROVIDE BATT INSULATION WITH SCRIM AT UNDERSIDE OF DECK IN ALL EXPOSED CEILING CONDITIONS AT UNDERSIDE OF ROOF. COLOR OF SCRIM SHALL BE SELECTED BY ARCHITECT. 9.EXTEND EXISTING WALLS AND FURRING SURROUNDING EXPOSED CEILING FULL HEIGHT TO UNDERSIDE OF DECK ABOVE AS REQUIRED FOR CONSISTENT APPEARANCE. EXPOSED KICKERS SHALL BE AVOIDED. 10.COORDINATE LIGHT FIXTURE AND EXIT SIGN LOCATIONS IN ALL EXPOSED CEILINGS PRIOR TO ROUGH-IN TO CONFIRM LOCATIONS AND ANY POSSIBLE HEIGHT LIMITATIONS. NOTIFY ARCHITECT OF ANY CONFLICTS. 11.PROVIDE ALLOWANCE FOR MOUNTING LIGHT FIXTURES AND EXIT SIGNS UNDER UNI-STRUT AS NEEDED TO MAINTAIN FIXTURE LOCATIONS AT OBSTRUCTIONS. EXPOSED CEILING NOTES 1 A B C D C.6 C.5 2 3 4 5 6 201 OFFICE 200 EXECUTIVE OFFICE 202 LOUNGE 203 RESTROOM 204 STORAGE 206A VETIBULE 205 STOR 206 OPEN OFFICE 207 OFFICE 208 MEN 209 WOMEN 210 JAN +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +8'-0" +8'-0" NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 2 REFLECTED CEILING PLAN IA-2.2 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 ALL NOTES ARE TYPICAL THROUGHOUT: 1. REFER TO GENERAL NOTES IA-G1 AND IA-G2 FOR ADDITIONAL INFORMATION. 2. VERIFY EXISTING CONDITIONS AND NOTIFY H. HENDY ASSOCIATES OF ANY DISCREPANCIES. 3. WORK SHALL COMPLY FULLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES. 4. CONTRACTOR SHALL VERIFY CONDITION OF SLAB AND PATCH/REPAIR TO SMOOTH AND LEVEL AS REQUIRED TO RECEIVE FLOOR FINISHES. PATCH AND FILL ALL ABANDONED FLOOR CORES PRIOR TO INSTALLATION OF FINISHES. 5. DEMOLISH PARTITIONS, DOOR ASSEMBLIES AND SIDELIGHTS AS SHOWN ON PLAN. PATCH AND REPAIR ADJACENT CONSTRUCTION AS REQUIRED. EXISTING COLUMN FURRING TO REMAIN. TERMINATE RELATED ELECTRICAL BACK TO POINT OF ORIGIN. 6. AT PARTITIONS BEING DEMOLISHED, ALL EXISTING POWER/TELE-DATA RECEPTACLES TO BE REMOVED. DISCONNECT AND REMOVE ALL HOMERUN CONDUITS AND CONDUCTORS FROM RECEPTACLES BACK TO POINT OF ORIGIN AS REQUIRED. 7. REMOVE ALL FLOORING, BASE, WALLCOVERING, WHITEBOARDS & TACKBOARDS, U.O.N. SCRAPE FLOOR AND CLEAN/PREP FOR NEW FUTURE FLOOR FINISHES. 8. REMOVE EXISTING TENANT AND EGRESS SIGNAGE AND ANY MISC. SCREWS/NAILS IN WALLS. PATCH WALL AND PREP FOR NEW FINISHES. 9. REMOVE/REPLACE ALL OUTLETS THAT DO NOT MEET CODE OR CURRENT BUILDING STANDARD STYLE/FINISH. CONTRACTOR TO VERIFY IN FIELD AND PROVIDE COUNTS AND LOCATIONS. 10. REMOVE EXISTING POWER/TELE/DATA RECEPTACLES AND WALL FEEDS AS INDICATED BY "D", DO NOT BLANK PLATE. REMOVE ALL UNUSED CABLING/CONDUITS IN WALLS, FLOORS, AND ABOVE CEILING IN THEIR ENTIRETY. COORDINATE WITH POWER & SIGNAL PLANS TO REUSE/MODIFY EXISTING WHEN AVAILABLE. REMOVE ALL BLANK PLATES AND ALL ASSOCIATED LOW VOLTAGE CABLING THROUGHOUT WHERE INDICATED. 11. EXISTING WINDOW COVERINGS AT ALL PERIMETER WINDOWS TO REMAIN. CLEAN AND REPAIR FOR LIKE- NEW APPEARANCE. DEMOLITION NOTES EXISTING PARTITION TO REMAIN, PROTECT IN PLACE DEMOLISH EXISTING PARTITION REMOVE EXISTING MILLWORK REMOVE DOOR ASSEMBLY, SAVE FOR POTENTIAL REUSE DEMOLISH SIDELIGHT OR GLAZING. AREA NOT IN CONTRACT LEGEND 1 A B C D C.6 C.5 2 3 4 5 6 C D C D C D C D C D C D 4 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 5 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ REMOVE ALL UNUSED CABLING AND CONDUIT FROM PLENUM SPACE CEILING DEMOLITOIN KEYNOTES A EXISTING SUSPENDED CEILING TO BE REMOVED. REMOVE LIGHT FIXTURES, HVAC, AND FIRE LIFE-SAFETY APPRERATUS B EXISTING ACOUSTICAL CEILING TILES TO BE REMOVED AND REPLACED. PROTECT EXISTING GRID IN PLACE. REPAIR OR REPLACE ALL DAMAGED GRID. C EXISTING LIGHT FIXTURES TO BE REMOVED AND REPLACED. SEE ELECTRICAL DRAWINGS FOR NEW LIGHT FIXTURE INFORMATION D EXISTING TRAPEEZE STRUCTURE TO BE REMOVED THROUGHOUT.E EXISTING DUCTWORK TO BE RELOCATED AWAY FROM PALLET RACK AREAF EXISTING HIGH-BAY LIGHTING TO BE REMOVED AND REPLACED. SEE ELECTRICAL DRAWINGS FOR NEW LIGHT FIXTURE INFORMATION. G NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 2 DEMOLITION CEILING PLAN IA-2.2D MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 E NG I NE CENT ERL INE FEC FEC FE C FE C FE C E sc F 1 F 2 F 3 F 4 F 5 F 6 F 7 F 8F 9 F 10 F 11 F 12 ºª\1!|"@·#$ &¬/% ( )=?¡¿ 23 4 567 8 9' 0 Q WE€R T Y U I O P A S D F G H J KLÑ ZX C V B N M;, :._->< ^[`*]+¨´Ç B loqm ay ús C o n tr o l A lt A lt G rC o n tr o l Im prPantP e t s isB loqD e sp lP au saIn te r R eP ág A vP ág In ic io In s er t S u pr F in B loqN u m/-* + In tr o 1 2 3 45 6 78 9 F in A vP ág In ic io R eP ág In s0S u pr. N u mL o ckC a ps S c r oll LockL o ck eth CR CR CR CR CR CA CA CA CA CA CA CA CA CA CACA CA CACA CA CA CA CA CR CR L L L L L L 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR 402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 OFFICE 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH 308 SHIPPING AND RECEIVING 111 RECEIVING 116 DIGITAL PHOTO 123 STORAGE 127 SHIPPING 303 MAINTENANCE SC 1 SC 1 B 1 SC 1 B B SC 1 B 1 P 1 EP 1 P 1 SC 1 B 1 P 1 SC 1 B 1 P 1 EP 1 FT 1 WT 1 P 1 FT 1 WT 1 P 1 WALK-IN REFRIGERATOR BY OTHERS EXISTING TRASH ENCLOSURE TO REMAIN SC 1 B 1 EP 1 FUTURE SECURE AREA 3 3 3 2 2 7.4 304A MEN 304B WOMEN 3 3 3 1 ALL NOTES ARE TYPICAL THROUGHOUT: 1. VERIFY EXISTING CONDITIONS AND NOTIFY H. HENDY ASSOCIATES OF ANY DISCREPANCIES. 2. WORK SHALL COMPLY FULLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES. 3. FLOOR FINISHES: ALL FLOORING SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. ADHESIVE MAY VARY DEPENDING ON SUBSTRATE MATERIAL OR SLAB ON GRADE INSTALLATION. FLOORING CONTRACTOR SHALL VERIFY AND INSTALL USING MANUFACTURER'S SPECIFIED ADHESIVES. 4. REFER TO CEILING PLAN FOR ALL FINISH SPECIFICATIONS AS IT REFERS TO EXPOSED CEILINGS, GYP. BOARD CEILINGS AND SOFFITS. FINISH NOTES CHANGE OF MATERIAL. SEE DETAILS . DIRECTION OF PATTERN FINISH CALL-OUT. REFER TO FINISH SCHEDULE ON SHEET IA-8.1 FOR FINISH SPECIFICATIONS. /---- AREA NOT IN CONTRACT LEGEND PROVIDE JOHNSONITE SLIM LINE SLT-XX-A TRANSITION AT ALL CARPET TO VINYL TRANSITIONS. KEYNOTES 1 PAINT ALL CEILING SUPPORT BEAMS, DECKING, CONDUITS, ETC., WHERE VISIBLE AT EXPOSED CEILING AREAS AND ABOVE FLOATING CEILINGS. 2 3 INCH WIDE TRAFFIC TAPE. COLOR: TBD3 WALL FINISHES FLOOR FINISHES BASE FINISHES ITEM:HARD, NON-ABSORBENT FINISH MFR:- STYLE:TO BE DETERMINED BY CLIENT COLOR:- INSTALL:- CONTACT:- GROUT:- ITEM:RUBBER BASE -FIELD MFR:JOHNSONITE STYLE:2 1/2" STRAIGHT @ CARPET, COVED @ HARD SURFACE FLOORING COLOR:BURNT UMBER B -63 INSTALL:PER MFR SPECS, ZERO CUT ALL MATERIALS TIGHT TO WALL SO NO GAPS OCCUR CONTACT: ITEM:GENERAL PAINT (WHITE) MFR:TBD STYLE:FLAT COLOR:TBD INSTALL:MIN. 2 COATS OVER PRIMER CONTACT:TBD ITEM:CEILING PAINT MFR:TBD STYLE:FLAT COLOR:TBD INSTALL:MIN. 2 COATS OVER PRIMER CONTACT:TBD FINISH SPECIFICATIONS SCHEDULE P 1 P 2 FT 1 B 1 ITEM:EPOXY FLOOR MFR:RUST-OELUM STYLE:OVERKRETE EXTRA S COLOR:TBD INSTALL:PER MFR. SPEC. OVER RUST -OLEUM TVB WATER BASED VAPOR BARRIER CONTACT: EF 1 ITEM:EPOXY COVE BASE MFR:RUST -OLEUM STYLE:OVERKRETE CB COLOR:TBD INSTALL:PER MFR. SPEC CONTACT: EB 1 ITEM:EPOXY PAINT MFR:SHERWIN WILLIAMS STYLE:ENDURACAT SEMI-GLOSS PRO INDUSTRIAL WB CATALIZED EPOXY COLOR:TBD INSTALL:MIN. 2 COATS OVER PRIMER CONTACT:TBD EP 1 ITEM:HARD, NON-ABSORBENT FINISH MFR:- STYLE:TO BE DETERMINED BY CLIENT COLOR:- INSTALL:- CONTACT:- GROUT:- WT 1 ITEM:SEALED CONCRETE MFR:WR MEADOWS STYLE:INDUROSHINE COLOR:TBD INSTALL:GRIND PER MFR. SPEC. W/ LIQUI-HARD ULTRA DENSIFIER AND BELLATRIX CONCRETE ENHANCER CONTACT: SC 1 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 1 FINISH PLAN IA-4.1 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1 PRESCREEN CORRECTIONS 3/24/25 FEC #DESCRIPTION MANUFACTURER MODEL #NOTES BOBRICK B-6806-36"WALL MOUNTED GRAB BAR - 36" BOBRICK B-6806-42"WALL MOUNTED GRAB BAR - 42" RESTROOM ACCESSORIES SCHEDULE 1 2 PARTITION MOUNTED TOILET TISSUE DISPENSER, AND TOILET SEAT COVER DISPENSER - SERVES (1) COMPARTMENT BOBRICK B-34793 RECESSED COMBINATION TOILET TISSUE DISPENSER, TOILET SEAT COVER DISPENSER AND SANITARY NAPKIN DISPOSAL - LEFT-HAND SIDE BOBRICK B-3091 4 BOBRICK B-3944RECESSED PAPER TOWEL DISPENSER WITH WASTE RECEPT COUNTERTOP MOUNTED MOTION- SENSOR SOAP DISPENSER ZURN INDUSTRIES SERIO SERIES Z6950-SD HARDWIRED MIRROR: 48" H X 24" W X 1/4" CLEAR TEMPERED GLASS W/ 1/2 BEVELED EDGE - - 5 6 7 SEMI-RECESSED SANITARY NAPKIN/TAMPON VENDOR BOBRICK B-3706348 FLOOR SINK JUST MANUFACTURING B33213-J -9 SCULLERY SINK JUST MANUFACTURING SB130-J -10 EYEWASH SHOWER HAWS AXION MSR 8300-8309 -11 DRINKING FOUNTAIN/ BOTTLE FILLER HAWS 1011HSA.8 CHILLED AND FILTERED WATER12 NOT USED NOT USED A 2 9' - 1"4' - 5"3' - 4"8' - 2" 1 2 2 4 4 5 5 6 7 10 FD 48" 30 " 2 A B C D 1 11 6 7 48" 30 " ø 5' - 0" 1 A B C D 16 ' - 6 " 9" A1 A1 D2 A2 D1 E1 IA-5.1‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ IA-5.1‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 9 12 8' - 1 " 7' - 6 " C2 A1 A1 E1 304A MEN 304B WOMEN 303 MAINTENANCE 2ø 5' - 0" 4 2 1 WT 1 4' - 0 " M I N . 2'-0" MIN. 1 2 7 6 5 WT 1 4' - 0 " M I N . 7 6 5 WT 1 4' - 0 " M I N . 2'-0" MIN. P 1 4 2 1 WT 1 4' - 0 " M I N . 2'-0" MIN. 1 2 7 6 5 WT 1 4' - 0 " M I N . 7 6 5 WT 1 4' - 0 " M I N . 2'-0" MIN. P 1 WALL FINISHES FLOOR FINISHES BASE FINISHES ITEM:HARD, NON-ABSORBENT FINISH MFR:- STYLE:TO BE DETERMINED BY CLIENT COLOR:- INSTALL:- CONTACT:- GROUT:- ITEM:RUBBER BASE -FIELD MFR:JOHNSONITE STYLE:2 1/2" STRAIGHT @ CARPET, COVED @ HARD SURFACE FLOORING COLOR:BURNT UMBER B -63 INSTALL:PER MFR SPECS, ZERO CUT ALL MATERIALS TIGHT TO WALL SO NO GAPS OCCUR CONTACT: ITEM:GENERAL PAINT (WHITE) MFR:TBD STYLE:FLAT COLOR:TBD INSTALL:MIN. 2 COATS OVER PRIMER CONTACT:TBD ITEM:CEILING PAINT MFR:TBD STYLE:FLAT COLOR:TBD INSTALL:MIN. 2 COATS OVER PRIMER CONTACT:TBD FINISH SPECIFICATIONS SCHEDULE P 1 P 2 FT 1 B 1 ITEM:EPOXY FLOOR MFR:RUST-OELUM STYLE:OVERKRETE EXTRA S COLOR:TBD INSTALL:PER MFR. SPEC. OVER RUST -OLEUM TVB WATER BASED VAPOR BARRIER CONTACT: EF 1 ITEM:EPOXY COVE BASE MFR:RUST -OLEUM STYLE:OVERKRETE CB COLOR:TBD INSTALL:PER MFR. SPEC CONTACT: EB 1 ITEM:EPOXY PAINT MFR:SHERWIN WILLIAMS STYLE:ENDURACAT SEMI-GLOSS PRO INDUSTRIAL WB CATALIZED EPOXY COLOR:TBD INSTALL:MIN. 2 COATS OVER PRIMER CONTACT:TBD EP 1 ITEM:HARD, NON-ABSORBENT FINISH MFR:- STYLE:TO BE DETERMINED BY CLIENT COLOR:- INSTALL:- CONTACT:- GROUT:- WT 1 ITEM:SEALED CONCRETE MFR:WR MEADOWS STYLE:INDUROSHINE COLOR:TBD INSTALL:GRIND PER MFR. SPEC. W/ LIQUI-HARD ULTRA DENSIFIER AND BELLATRIX CONCRETE ENHANCER CONTACT: SC 1 FINISH NOTES 1. EXTENTS OF HARD, NON-ABSORBENT FINISHES SHOWN TO CODE MINIMUM. ACTUAL MATERIALS AND EXTENTS OF MATERIALS TO BE DETERMINED BY CLIENT. HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 ENLARGED RESTROOM PLAN(S) & ELEVATIONS IA-5.1 MCGUFF AB/CD SCALE 3/8" = 1'-0"3ENLARGED RESTROOM PLAN ABCD ABCD SCALE 3/8" = 1'-0"2MEN'S RESTROOM -ELEVATION A SCALE 3/8" = 1'-0"1WOMEN'S RESTROOM -ELEVATION A NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 8' - 2 " 5' - 0 " 8' - 2 " 5' - 0 " 5' - 0 " 8' - 2 " 8' - 2 " 5' - 0 " 8' - 0 " 5' - 0 " T 8' - 2 " 5' - 0 " NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 3/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 ELEVATIONS IA-5.2 MCGUFF AB/CD SCALE 3/8" = 1'-0"1WAREHOUSE OFFICE ELEVATIONSCALE 3/8" = 1'-0"2WAREHOUSE OFFICE ELEVATIONSCALE 3/8" = 1'-0"3WAREHOUSE OFFICE ELEVATION SCALE 3/8" = 1'-0"4STORAGE ROOM ELEVATION NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 SCALE 3/8" = 1'-0"5OFFICE ENTRY ELEVATION SCALE 3/8" = 1'-0"6WAREHOUSE WINDOW ELEVATIONS CE I L I N G H T . P E R P L A N CONT. ACCOUSTICAL SEALANT BEAD BASE PER PLAN (1) LAYER 5/8" GYP. BD. EA. SIDE. 1/2" GLASS MAT WATER RESISTANT BACKER PANELS WHERE TILE OCCURS) METAL TRACK W/ POWDER DRIVEN ANCHORS - SET IN CONT. SEALANT BED. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION. BATT INSULATION 6 MIL VISQUEEN. LAP SEAMS 3" AND CONT. TAPE. 5/8" GYP. BD. 6 MIL VISQUEEN. LAP SEAMS 3" AND CONT. TAPE. CLG. JOISTS PER STRUCTURAL DRAWINGS MTL. STUD FRAMING (ESR #3064P) SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION TYPE STUD SIZE STUD GAUGE STUD SPACING GWB LAYERS STC RATING FIRE RATING FIRE RATING TEST NO.NOM. DIM A1 3-5/8"**(1) LAYER GWB. EA SIDE ---4-7/8" A2 6"**(1) LAYER GWB. EA SIDE ---7-1/4" * SEE STRUCTURAL DRAWINGS FOR GUAGE, SPACING, AND ADDITIONAL INFORMATION CLG. JOISTS PER STRUCTURAL DRAWINGS CONT. ACCOUSTICAL SEALANT BEAD BASE PER PLAN (1) LAYER 5/8" GYP. BD. EA. SIDE METAL TRACK W/ POWDER DRIVEN ANCHORS - SEE STRUCTURAL DRAWINGS BATT INSULATION CE I L I N G H T . P E R P L A N TYPE STUD SIZE STUD GAUGE STUD SPACING GWB LAYERS STC RATING FIRE RATING FIRE RATING TEST NO.NOM. DIM B1 3-5/8"**(1) LAYER GWB. EA SIDE ---4-7/8" * SEE STRUCTURAL DRAWINGS FOR GUAGE, SPACING, AND ADDITIONAL INFORMATION METAL STUD FRAMING (ESR #3064P) SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION TYPE STUD SIZE STUD GAUGE STUD SPACING GWB LAYERS STC RATING FIRE RATING FIRE RATING TEST NO.NOM. DIM C1 3-5/8"**(1) LAYER GWB. EA SIDE ---4-7/8" * SEE STRUCTURAL DRAWINGS FOR GUAGE, SPACING, AND ADDITIONAL INFORMATION CLG. JOISTS PER STRUCTURAL DRAWINGS SLOTTED TOP TRACK W/ #10 S.M.S. EA. FLANGE EA. STUD #10 X 1" S.M.S. @ EA. HORIZ. JOIST METAL STUD FRAMING (ESR # 3064P) SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION (1) LAYER 5/8" GYP. BD. EA. SIDE METAL TRACK W/ POWDER DRIVEN ANCHORS -SEE STRUCTURAL DRAWINGS BASE PER PLAN CONT. ACCOUSTICAL SEALANT BEAD CE I L I N G H T . P E R P L A N C2 6"**(1) LAYER GWB. EA SIDE ---7-1/4" CLG. JOISTS PER STRUCTURAL DRAWINGS METAL TRACK W/ POWDER DRIVEN ANCHORS -SEE STRUCTURAL DRAWINGS BATT INSULATION TYPE STUD SIZE STUD GAUGE STUD SPACING GWB LAYERS STC RATING FIRE RATING FIRE RATING TEST NO.NOM. DIM E1 3-5/8"**(1) LAYER GWB. EA SIDE ---4-7/8" * SEE STRUCTURAL DRAWINGS FOR GUAGE, SPACING, AND ADDITIONAL INFORMATION (1) LAYER 5/8" GYP. BD. EA. SIDE METAL. STUD FRAMING (ESR # 3064P) SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION 6 MIL VISQUEEN. LAP SEAMS 3" AND CONT. TAPE. CE I L I N G H T . P E R P L A N TYPE STUD SIZE STUD GAUGE STUD SPACING GWB LAYERS STC RATING FIRE RATING FIRE RATING TEST NO.NOM. DIM D1 3-5/8"**(1) LAYER GWB. ---4-1/4" * SEE STRUCTURAL DRAWINGS FOR GUAGE, SPACING, AND ADDITIONAL INFORMATION CLG. JOIST PER STRUCTURAL DRAWINGS 5/8" GYP. BD. SLOTTED TOP TRACK W/ #10 S.M.S. EA. FLANGE EA. STUD #10 X 1" S.M.S. @ EA. HORIZ. JOIST 3-5/8" MTL. STUD BRACING @ 4'-0" (VERT). POWDER DRIVEN FASTENER (4) #10 X 1" S.M.S. (1) LAYER 5/8" GYP. BD. BATT INSULATION METAL TRACK W/ POWDER DRIVEN ANCHORS -SEE STRUCTURAL DRAWINGS BASE PER PLAN CONT. ACCOUSTICAL SEALANT BEAD METAL STUD FRAMING (ESR #3064P) SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION 6 MIL VISQUEEN. LAP SEAMS 3" AND CONT. TAPE AT WALL TYPE D1 ONLY CE I L I N G H T . P E R P L A N D2 3-5/8"**(1) LAYER GWB. ---4-1/4" 16 GA. MTL. STUD -WHERE BACKING PLATE OCCURS (STUD WIDTH PER PLANS) 6" X 16 GA. MTL. STUD -NOTCH AT EA. VERT. STUD AS SHOWN 6" X 16 GA. SHEET METAL STRAP (3) #10 FLAT HEAD SHEET MTL. SCREWS TO EA. STUD (TYP.) EXTEND BACKING PLATE TYPE 1 ACROSS MIN. THREE (3) STUDS. EXTEND ALL BACKING PLATES TO LAST STUD BEYOND ITEM. DO NOT CUT WALL STUD FLANGES TYPE 1 -USE AT: WALL CABINETS AND BASE CABINETS, HANDRAILS AND GRAB BARS TYPE 2 -USE AT: WALL MOUNTED DOOR STOPS, MARKER AND TACK BOARDS, TOILET ACCESSORIES, MIRRORS SCHEDULED PARTITION ALUMINUM WINDOW FRAME TO MATCH ADJACENT DOOR FRAMES NOTE: NO EXPOSED FASTENERS, TYP. 1 1 / 2 " T Y P EQ EQ RATINGTYPE F1 - FIRE RATING TEST NO.FIRE -9 1/4" RATING STC STC 54(1) LAYER GWB BOTH SIDES8" SIZE STUD GAUGE * STUD * SPACING STUD LAYERS GWB TOP OF SLAB BASE: SEE FINISH SCHEDULE HEAD PLAN SILL METAL TRACK W/ POWDER DRIVEN ANCHORS: HILTI X-U UNIVERSAL KNURLED SHANK FASTENER, AT 24"o.c. W/ 1" EMBED (ICC/ESR #2269) CONTINUOUS ACOUSTICAL SEALANT CEILING PER FINISH SCHEDULE SLIP TRACK, 16 GA. TOP TRACK, W/ #10 S.M.S. EA. FLANGE EA. STUD SOUND ATTENUATION BATT INSULATION METAL STUDS (ESR #3064P) WITH 5/8" TYPE. "x" GYP. BD. BOTH SIDES (# OF LAYERS PER BELOW), 1/2" GLASS MAT WATER-RESISTANT BACKER PANELS WHERE TILE OCCURS) CL G . H T . P E R R E F L E C T E D C E I L I N G P L A N S NOM. DIM (2) #10 WOOD SCREWS X 2" LONG @ 24" O.C. EXISTING ROOF FRAMING (2) 16d END NAILS 2X BLOCKING @ 24" O.C. HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 WALL SECTIONS & DETAILS IA-6.1 MCGUFF AB/CD SCALE 3" = 1'-0"3WALL TYPE ASCALE 3" = 1'-0"7WALL TYPE BSCALE 3" = 1'-0"11WALL TYPE CSCALE 3" = 1'-0"19WALL TYPE E SCALE 3" = 1'-0"15WALL TYPE D SCALE 1 1/2" = 1'-0"2WALL BACKINGSCALE 3" = 1'-0"6WINDOW JAMB -HEAD, SILL SIM. SCALE 3" = 1'-0"9PARTITION TYPE F NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 8" MAX. PERIMETER SEISMIC CLIP ANGLE MOLDING EDGE TRIM SCREWED TO EACH STUDCROSS TEE <10'-0" : TWO 1-5/8" (25GA) METAL STUD <15'-0" : TWO 2-1/2" (25GA) METAL STUD <20'-0" : TWO 3-5/8" (25GA) METAL STUD STUD ORIENTATION Specifications: Ceiling grid classification: Heavy-Duty Manufacturer's catalog number Main runner: Cross runner: Runner splice: Armstrong Prelude XL15__ 16 " 7301 7340 Armstrong Suprafine XL 9__ 16 " 7501 7540 USG DONN DX/DXT 15__ 16 " ZXLA26 ZXLA424 TFS-1 USG DONN DX/DXT 9__ 16 " DXT26 DXT424 TFS-1 SUSPENDED CEILING NOTES (INSTALLATION REQUIREMENTS): COMPLY WITH CBC 2501A.5 AND ASCE 7 Fixture Attachment: Attach all light fixtures and ceiling mounetd air terminals to the ceiling grid runnders to resist a horizontal force equal to the weight of the fixtures. Screws or approved fasteners are requried. Flush or recessed light fixtures and air terminals weighing less than 56 lbs. may be supported directly on the runners of a heavy duty grid system, but in addition, must have a minimum of (2) #12 ga. slack safety wires attached to the fixture at diagonal corners and anchored to the structure above. All 4'x4' fixtures must have slack safety sires at each corner. All flush or recessed light fixtures and air terminals weighing 56 lbs. or more must be independently supported by not less than (4) taut #12 ga. wires, each attached to the fixture and to the structure above regardless of the type of grid system used. Surface Mounted Light Fixtures: Support surface mounted light fixtures by at least two positive devices which surround the ceiling runner and which are each supported from the structure ababove by a #12 ga. wire. Spring clips or clamps that connect only to the runner are not acceptable. Provide additional supports when light fixtures are 8 feet or longer. Pendant Mounted Light Fixtures: Support pendant mounted light fixtures directly from the structure wabove with hanger wires or cables passing through each pendant hanger and capable of supporting (4) times the weight of the fixture. A bracing assembly is required where the pendant hanger penetrates the ceiling. Free Wall: at the perimeter of the ceiling area where main or cross runners are not connected to the adjacent wall, provide interconnection between the runners at the free end to prevent lateral spreading. A metal strut or a #16 ga. wire with a mechanical connection to the runner may be used. Where the perpendicular distance fromt he wall to the first parallel runner is 12" or less, this interlock is not requried. Seismic Bracing: Provide bracing assemblies consisting of a compression strut and (4) #12 ga. splayed bracing wires oriented 90 degress from each other at 12' x 12' on center, 6' maximum from each perimeter wall and at the edge of vertical ceiling offsets. Ceiling areas of 144 SF. or less, surrounded by walls which connect directly to the structure above, do not require bracing assemblies when attached to two adjacent walls. Fastening: Fasten hanger wires with not less than (3) tight turns. Fasten bracing wires with (4) tight turns. Make all tight turns within a distance of 1 1/2". Hanger or bracing wire anchors to the structure should be installed i nsuch a manner that the direction of the anchor aligns as closely as possible with the direction of the wire. Separation: Separate all ceilign hanger and bracing wires at least 6: from all unbraced ducts, pipes, conduit, etc., Field Tests: Whe drilled-in concrete anchors or shot-in anchors are used in reinforced concrete for hanger wires, 1 out of 10 must be field tested for 200 lbs. in tension. When drilled-in anchors are used for bracing wires, 1 out of 2 must be field tested for 400 lbs. in tension. Shot-in anchors for concrete are not permited for bracing wires. Hanger Wires: #12 ga. wires may be used for up to and including 4 ft. by 4 ft. grid spacing and shall be attached to main runners. Perimeter: Provide #12 ga. hanger wires at the ends of all main and cross runners within 8" of the support or within 1/4 th of the length of the end tee, whichever is least, for the perimeter of the ceiling area. Obstructions: Provide trapeze or other supplementary support members at ovstructions to gypical hanger spacing. Provide additional hangers, or braces as requried at all ceiling breakes, soffits or discontinuous areas. Hanger wires that are more than 1 in 6 out of plumb are to have counter-sloping wires. Wall Attachment: Ceiling grid members may be attached to not more than 2 adjacent walls. Ceiling grid members shall be at least 1/2" clear of other walls. If walls run diagonally to ceiling grid system runenrs, one end of main and cross members should be free, and a minimum of 1/2" clear of wall. WHERE THE DISTANCE BETWEEN THE CEILING GRID AND THE SLAB ABOVE IS LESS THAN 8'-0": PROVIDE 3-5/8" (25 GA.) METAL STUD. ATTACH TO MAIN RUNNERS WITH 2" OF FROSS RUNNER WITH (2) #12 SELF-DRILLING, SELF-TAPPING SCREWS AND TO CONCRETE/ STEEL STRUCTURE WITH 3/16" DIA. ANCHOR. IF DISTANCE BETWEEN CEILNIG GRID AND SLAB ABOVE IS 8'-0" OR GREATER: USE THE SCHEDULE BELOW FOR STUD SIZES: METAL STUDS ORIENTED AS SHOWN, CONNECTED EVERY 12" ALONG THEIR LENGTH COMPRESSION STRUT AT 12' O.C. BOTH DIRECTIONS 12" GA. HANGER WIRES AT 48" O.C. ALONG MAIN TEE RUNNERS (4) 12 GA. SPLAYED SEISMIC BRACING WIRES AT 12' O.C. BOTH DIRECTIONS . 45 DEGREE MAX. MAIN TEE RUNNER 2" MAX. CROSS TEE RUNNER AT STEEL BEAM VERTICAL HANGER AT CONCRETE SPLAYED SEISMIC BRACING AT CONCRETE STEEL BEAM (SEE TYPICAL NOTES) #9 VERTICAL HANGER WIRE (200# TEST) w/ (3) TIGHT TURNS MIN. WOOD JOIST/BEAM CEILING CLIP, 13GA. x 3/4" MIN. - HILTI CC-27 (ESR-2184) OR EQUAL 1/4"" DIA. THREADED WOOD SCREW w/ 1 1/4" MIN. EMBEDMENT 45°#12 SPLAYED SEISMIC WIRE (440# TEST) w/ (4) TIGHT TURNS MIN. STEEL STRAP, 1" WIDE x 2" LONG x 12GA. MIN. WOOD JOIST/ BEAM 1/4" DIA. THREADED WOOD SCREW w/ 1 1/4" MIN. EMBEDMENT 5/8" MAX. 5/8" MAX. B CARPET TO CERAMIC TILE CARPET TO RESILIENTA CARPET ALUM. TRANSITION STRIP VCT OR SHEET VINYL CONCRETE FLOOR SLAB W/ CLEAR SEALER D VCT TO CONCRETE VCT TO CERAMIC TILEC 1/ 4 " 1/ 2 " M A X . VCT THREASHOLD CERAMIC TILE CONCRETE FLOOR SLAB W/ CLEAR SEALER CARPET CLEAR ANODIZED ALUMINUM STRIP, SECURE TO SLAB CERAMIC TILE CLEAVAGE MEMBRANE OVER CONC. SLAB EPOXY GROUT, TAPER UP TO MEET CERAMIC TILE FINISH (IF REQUIRED) 1/ 2 " M A X . 1/ 2 " M A X . THRESHOLD VCT CONC. FLOOR SLAB W/ CLEAR SEALER METAL STUD FRAMING. SEE PARTITION PLAN 5/8" TYPE 'X' GYP. BOARD SEMI-RECESSED FIRE EXTINGUISHER CABINET- SEE PARTITION PLAN LEGEND FOR SPEC. SEE PARTITION PLAN FOR LOCATIONS. CABINET FINISH TO BE PAINTED TO MATCH ADJACENT SURFACE, UNO. FACE OF WALL BEYOND 5/8" TYPE 'X' GYP. BOARDA. F . F . T O K N O B . 40 " M A X . 8" M I N . EXISTING CONC. WALL PANEL CONT. SEALANT BEAD TWO PIECE GALV. MTL. REGLET CAP SHEET FLASHING SHEETS CANT BUILT-UP ROOFING 1/4" DENS DECK PROTECTION BOARD 6" POLYISOCYANURATE RIGID INSULATION BOARDS (R-30 MIN.) EXISTING ROOF SUBSTRATE 1. ASPHALT AND MBR UTILITY CEMENT NOT SHOWN FOR CLARITY 2. LEAD FLASHING SHALL BE 2.5 LBS. PER SQUARE FOOT MINIMUM. 3. IT IS ACCEPTABLE TO RUN FIELD MEMBRANE PLY THROUGH DRAIN CENTER AND OMIT TARGET SHEET IF DRAIN SUMP IS SHALLOW ENOUGH TO ALLOW INSTALLATION WITHOUT WRINKLES OR FISHMOUTHS. STEEP SUMPS WILL REQUIRE THE INSTALLATION OF A TARGET PATCH WITHIN DRAINSUMP. 4. USE ASPHALT PRIMER ON LEAD FLANGES WHEN USING MBR UTILITY CEMENT. USE PERMAFLASH PRIMER ON LEAD FLANGES WHEN USING MBR FLASHING CEMENT. 5. EXTEND ALL PLIES TO EDGE OF DRAIN BOWL. NO SEAMS ARE ALLOWED THROUGH THE DRAIN. SHEET LEAD, MIN. 30" x 30" PRIME LEAD WITH PRIMER ON BOTH SIDES, (SEE NOTES) ROLL LEAD DOWN BOWL. (SET IN MBR UTILITY CEMENT OR MBR FLASHING CEMENT) CLAMPING RING DRAIN STRAINER SUMP CORNER CAP SHEET UNDER CLAMPING RING BACKER PLY 4" MIN. 4" MIN. SMOOTH SURFACE PLY BELOW CAP SHEET INSULATION TAPERED TO DRAIN UNDERDECK DRAIN CLAMP (AS REQUIRED) LEAD SHEET RIGID INSULATIONNOTES: 6. ANY CARPENTRY, METAL WORK, OR MASONRY CONSTRUCTION SHOULD BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS AND/OR PROJECT SPECIFICATIONS. THESE COMPONENTS SHOULD BE REVIEWED AND APPROVED BY A LICENSED DESIGN PROFESSIONAL. 7. PLEASE SEE BITUMINOUS FLASHING SPECIFICATIONS FOR A FULL DESCRIPTION OF INSTALLATION INSTRUCTIONS AND REQUIREMENTS WHICH ARE CONSIDERED A PART OF THIS DETAIL. CAP SHEET ROOF ASSEMBLY SEALANT SURFACED FLASHING PLY (SEE NOTE 5.) DRAWBAND FLASHING COLLAR (8" TALL MIN.) STORM COLLAR (INJECT POLYURETHANE SEALANT BETWEEN COLLAR AND PIPE. TIGHTEN DRAWBAND AND TOOL SEALANT BLEEDOUT AROUND PIPE.) FLASHING PLIES (INSTALL MIN. TWO (2) FLASHING PLIES, AND FEATHER EACH PLY 3" MIN.) BITUMINOUS ROOF CEMENT OR POLYUREHANE SEALANT (INSTALL AT BASE OF PENETRATION.) FLASHING COLLAR FLANGE (PRIME BOTH SIDES OF HORIZONTAL FLANGES AND SET IN BED OF BITUMOUS ROOF CEMENT ON FINISHED FIELD PLIES. IF REQUIRED, NAIL TO DECK APPROX 3" O.C. STAGGERED.) MULTIPLE-PLY POLYMER MODIFIED BITUMEN ROOFING FIELD PLIES BASE SHEET (MECHANICALLY ATTACH AS REQUIRED.) PIPE PENETRATION SECURED TO STRUCTURAL FRAMING FIRE SAFING INSULATION REQUIRED AT HOT STACK CONDITION 1. DIMENSIONS SHOWN ARE MINIMUMS AND ARE INTENDED TO BE APPROXIMATE TO ALLOW FOR RESONABLE TOLERANCES DUE TO FIELD CONDITIONS. 2. THIS DETAIL IS SUITABLE FOR FLASHING ROUND PIPES USED TO SUPPORT EQUIPMENT, ELECTRICAL CONDUIT, WATER AND GASE LINES, SHEET METAL FLUES, AND OTHER SIMILAR PENETRATIONS. 3. THE HORIZONTAL FLASHING FLANGES TO BE A MINIMUM OF 4" WIDE. 4. SET METAL FLASHING FLANGES ON FINISHED FIELD PLIES AND STRIP-IN BEFORE SURFACING. 5. SURFACED FLASHING PLY IS RECOMMENDED TO HAVE WHITE OR OTHER LIGHT REFLECTING SURFACE TO MINIMIZE HEAT GAIN AND THERMAL MOVEMENT. FOR AGGREGATE-SURFACE MEMBRANES, EXTEND AGGREGATE COVERAGE TO OUTSIDE OF COLLAR. ROOF ASSEMBLY COUNTERFLASHING SKIRT (SEE NOTE 2.) 3" MIN. 3" MIN. SURFACED FLASHING PLY (SEE NOTE 3.) SHEET METAL COUNTERFLASHING GASKETED SCREW FASTENERS BASE FLASHING MEMBRANE (EXTEND TO TOP OF CURB AND FASTEN 6" O.C. EXTEND ONTO ROOF SURFACE BEYOND TOE OF CANT.) MULTIPLE-PLY POLYMER MODIFIED BITUMEN ROOFING (OPTION: FIELD PLIES MAY BE EXTENDED OR FEATHERED ABOVE HEAD OF CANT.) BASE SHEET (MECHANICALLY ATTACH AS REQUIRED.) FIBER CANT STRIP (SET FIBER CANT IN HOT ASPHALT OR BITUMOUS ROOF CEMENT OVER BASE SHEET.) PRE-FABRICATED 18 GA. GALV. EQUIPMENT CURB 8" HIGH MIN. W/ FACTORY WOOD NAILER AT TOP, PRESERVATIVE TREATED, AND RIGID INSULATION NOTES: 1. DIMENSIONS SHOWN ARE MINIMUMS AND ARE INTENDED TO BE APPROXIMATE AND TO ALLOW FOR REASONABLE TOLERANCES DUE TO FIELD CONDITIONS. 2. COUNTERFLASHING SKIRT IS RECOMMENDED WHEN PRE- MANUFACTGURED FLASHING FLANGE EXTENDS LESS THAN 2" OVER MEMBRANE BASE FLASHING, OR WHEN BASE FLASHING FASTENERS ARE EXPOSED. 3. SURFACED FLASHING PLY IS RECOMMENDED TO HAVE WHITE OR OTHER LIGHT REFLECTING SURFACE TO MINIMIZE HEAT GAIN AND THERMAL MOVEMENT. DETAIL VIEW Approx. 6" O.C. ROOF DECK SHEET METAL CAP 3" MIN.3" MIN. SURFACED FLASHING PLY (SEE NOTE 4.) MEMBRANE BASE FLASHING (FASTEN TO TOP OF CURB AT APPROX. 6" O.C. EXTEND ONTO FIELD OF ROOF BEYOND TOE OF CANT.) MULTIPLE-PLY POLYMER MODIFIED BITUMEN ROOFING (OPTION: FIELD PLIES MAY BE EXTENDED OR FEATHERED ABOVE HEAD OF CANT.) BASE SHEET (MECHANICALLY ATTACH AS REQUIRED.) FIBER CANT, SET CANT OVER BASE SHEET IN HOT ASPHALT OR BITUMOUS ROOF CEMENT WOOD CURB (EXTEND 8" MIN. ABOVE FINISHED ROOF SURFACE. PRESERVATIVE TREATMENT OPTIONAL.) Notes: 1. DIMENSIONS SHOWN ARE MINIMUMS AND ARE INTENDED TO BE APPROXIMATE TO ALLOW FOR REASONABLE TOLERANCES DUE TO FIELD CONDITIONS. 2. ATTACH TOP OF MEMBRANE BASE FLASHING APPROXIMATELY 6" O.C. 3. SURFACE FLASHING PLY IS RECOMMENDED TO HAVE WHITE OR OTHER LIGHT REFLECTING SURFACE TO MINIMIZE HEAT GAIN AND THERMAL MOVEMENT. HIGH-DOMED CAPPED, GASKETED SELF- TAPPING SCREW (FASTEN AT APPROXIMATELY 18" O.C.)MEMBRANE BASE FLASHING (LAP AT TOP FOR DOUBLE LAYER.) HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 DETAILS IA-7.1 MCGUFF AB/CD SCALE 3" = 1'-0"2PERIMETER TRIM SCALE 12" = 1'-0"3ACCOUSTICAL CEILING SUSPENSION SYSTEM SCALE 3" = 1'-0"4SUSPENDED CEILING ATTACHMENT POINTS SCALE 6" = 1'-0"9FLOORING TRANSITIONS SCALE 1 1/2" = 1'-0"10FIRE EXTINGUISHER CABINET SCALE 1 1/2" = 1'-0"16ROOF AT PARAPET SCALE 1 1/2" = 1'-0"14ROOF AT DRAIN SCALE 3" = 1'-0"13B.U.R. PIPE PENETRATION SCALE 3" = 1'-0"19CURB FLASHING SCALE 1 1/2" = 1'-0"17SLEEPER FLASHING NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 DOOR TYPE ELEVATIONS A B C - 11 - 15 - 11 - 15 NOT USED NOT USED 3' - 0 " - 17 - 17 D GROUP H1 (CARD READER ENTRY, SINGLE DOOR) ELECTRIC LOCKSET:BY TENANT VENDOR ELECTRIC HINGE:BY TENANT VENDOR BALL BEARING HINGE:HAGER BB 4-1/2" X 4-1/2" CLOSER: NORTON 1600 SERIES DOOR STOP:QUALITY 331 GROUP H2 (KEYED ENTRY, SINGLE DOOR) ENTRY LOCKSET:BUILDING STANDARD BALL BEARING HINGE:HAGER BB 4-1/2" X 4-1/2" CLOSER: NORTON 1600 SERIES DOOR STOP:QUALITY 331 GROUP H3 (OFFICE) OFFICE LOCKSET SCHLAGE L SERIES, LEVER STANDARD HINGE:HAGER 4-1/2" X 4-1/2" DOOR STOP:QUALITY 331 GROUP H4 (PASSAGE) PASSAGE LATCHSET:SCHLAGE L SERIES, LEVER BALL BEARING HINGE:HAGER BB 4-1/2" X 4-1/2" CLOSER: NORTON 1600 SERIES DOOR STOP:QUALITY 331 GROUP H5 (STORAGE) STOREROOM LOCKSET:SCHLAGE L SERIES, LEVER BALL BEARING HINGE:HAGER BB 4-1/2" X 4-1/2" CLOSER:NORTON 1600 SERIES DOOR STOP:QUALITY 331 HARDWARE SCHEDULE GROUP H6 (PRIVACY) PRIVACY LOCKSET:SCHLAGE L SERIES, LEVER BALL BEARING HINGE:HAGER BB 4-1/2" X 4-1/2" CLOSER:NORTON 1600 SERIES DOOR STOP:QUALITY 331 WALL TYPE PER PLAN METAL TRACK DOUBLE METAL STUD HEADER CONTINUOUS SEALANT -BOTH SIDES HOLLOW METAL DOOR FRAME DOOR -REFER TO DOOR SCHEDULE HEAD FRAME ANCHOR -3 PER JAMB DOOR -REFER TO DOOR SCHEDULE HOLLOW METAL DOOR FRAME CONTINUOUS SEALANT -BOTH SIDES WALL TYPE PER PLAN DOUBLE STUDS AT JAMB VA R I E S P E R W A L L T Y P E JAMB STEEL STUD ANCHORSBASE CLIPS 2" VERIFY VE R I F Y 2" RETAINER CLIP DOOR -REFER TO SCHEDULE VA R I E S P E R W A L L T Y P E VE R I F Y STEEL KNOCK-DOWN FRAME DOUBLE STUDS AT JAMB WALL TYPE PER PLAN VERIFY DOOR -REFER TO SCHEDULE STEEL KNOCK-DOWN FRAME DOUBLE METAL STUD HEADER METAL TRACK WALL TYPE PER PLAN HEAD JAMB 39 " >1/2 W W >1/2 W 39 " W >1/2W NOTES: 1. 15 LBS 2. LENGTH OF PUSH PAD SHALL BE GREATER THAN HALF OF THE WIDTH OF THE ACTIVE DOOR LEAF 3/4" CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE SINGLE CARD READER ON J-BOX ELECTRIFIED MORTISE LOCK 3/4" C. DOOR CONTACTS WIRE PATHWAY IN DOOR TERMINATE CONDUIT IN DOOR FRAME ADJACENT TO ELECTRIC HINGE REQUEST TO EXIT INFRARED SENSOR MOUNTED ON J-BOX (ON OPPOSITE FACE OF WALL) 1/2" C. 1/2" C. TERMINATE CONDUIT IN DOOR FRAME ADJACENT TO ELECTRIC HINGE WIRE PATHWAY IN DOOR PAIR CARD READER ON J-BOX ELECTRIFIED MORTISE LOCK REQUEST TO EXIT INFRARED SENSOR MOUNTED ON J-BOX (ON OPPOSITE FACE OF WALL) 3/4" CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE 1/2" C. 1/2 " C. 3/4" C. DOOR CONTACTS A B AT THIN-SET TILE AT MORTAR BED TILE 2 11/ 4 " 1/ 4 " 2 1 1/ 4 " 1/ 4 " ADJACENT FLOOR ADJACENT FLOOR MARBLE THRESHOLD W/ POLISHED FINISH -FULL DEPTH OF DOOR FRAME. NOTCH AT JAMB DOOR PER SCHEDULE (DOOR BOTTOM WHERE OCCURS) 1/4" WIDE CONT. SEALANT BEAD - BOTH SIDES CERAMIC FLOOR TILE CONC. SLAB MARBLE THRESHOLD W/ POLISHED FINISH -FULL DEPTH OF DOOR FRAME. NOTCH AT JAMB DOOR PER SCHEDULE (DOOR BOTTOM WHERE OCCURS) 1/4" WIDE CONT. SEALANT BEAD - BOTH SIDES CERAMIC FLOOR TILE MORTAR BED SECTION ASTRAGALGUIDE SEAL ROLLING DOOR CHAIN KEEPER PADLOCK BY G.C MAX. 1/4"∅SHANK MID-HOOD SUPPORT; WHEN REQUIRED; SOLID WALL CONSTRUCTION REQ'D.SPRING ADJUSTOR HOOD AUXILIARY HAND CHAIN HOOD BAFFLE PLAN OF OPENING STEEL BRACKET PLATE ABOVE WEATHER STRIPPING GUIDE TRACK PER MFR. ELEVATION OP E N I N G H E I G H T OV E R A L L H E I G H T 2"15" 20 " + / - 2" 5" 8"8" OPENING WIDTH 1/2" CLEAR TEMPERED GLASS BOTTOM CORNER PATCH FINISHED CONCRETE FLOOR TOP PIVOT HARDWARE WITH CORNER PATCH WITH RECESSED, CONCEALED CLOSER EXISTING FLOOR STRUCTURE ABOVE SLOTTED HEAD TRACK (ICC-ESR-3064P) ATTACHED TO STRUCTURE WITH FASTENERS @ 24" O.C. AND 2" FROM EACH END (HILTI-ICC-ESR-2269) - REFER TO DETAIL 25 GAUGE METAL STUDS GANGED TO FORM TOP HEADER 5/8" TYPE 'X' GYP. BD. OVER METAL STUD FRAMING SEISMIC BRACING @ 48" O.C., EACH DIRECTION AS REQUIRED BOTTOM PIVOT ASSEMBLY HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 DOOR SCHEDULE & DETAILS IA-8.1 MCGUFF AB/CD DOOR NUMBER FIRE RATING (MIN) DOOR FRAME HARDWARE COMMENTS TY P E WI D T H HE I G H T MA T E R I A L FI N I S H MA T E R I A L FI N I S H GR O U P PA N I C AC C E S S C O N T R O L 101 - - 6' - 0" 9' - 0" - Y EXISTING DOOR -RETROFIT WITH CARD READER 102 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 103 - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 104 - - 3' - 0" 7' - 0" Y EXISTING DOOR -RETROFIT WITH CARD READER 105 - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 106 - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 107 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 108 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 109 - - 6' - 0" 9' - 0" - EXISTING TO REMAIN 109A - - 6' - 0" 7' - 0" - EXISTING TO REMAIN 111 - - 3' - 0" 9' - 0" Y EXISTING DOOR -RETROFIT WITH CARD READER 111A - C 12' - 0" 14' - 0" MTL MFR MFR MFR MFR - - COOKSON THERMISER MAX MODEL ESD30 112 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 113 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 114 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 114A - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 115 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 116 - A 3' - 0" 8' - 0" WD PT KD PT H4 - - - 118 - - 3' - 0" 8' - 0" - EXISTING DOOR -RETROFIT WITH CARD READER 118A - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 119 - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 120 - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 120A - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 120A1 - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 120A2 - - 3' - 0" 9' - 0" Y EXISTING DOOR -RETROFIT WITH CARD READER 121 - - 3' - 0" 9' - 0" Y EXISTING DOOR -RETROFIT WITH CARD READER 122 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 123 - A 3' - 0" 8' - 0" WD PT KD PT H5 - - - 124 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 124A - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 125 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 126 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 127 - - 3' - 0" 9' - 0" Y EXISTING DOOR -RETROFIT WITH CARD READER 127A - C 12' - 0" 14' - 0" MTL MFR MFR MFR MFR - - COOKSON THERMISER MAX MODEL ESD30 200 - - 3' - 0" 8' - 0" Y EXISTING DOOR -RETROFIT WITH CARD READER 200A - - 3' - 0" 8' - 0" Y - 201 - D 6' - 0" 8' - 0" GLASS TEMPER MFR MFR MFR HERCULITE DOOR AND FRAME 202 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 203 - - 3' - 0" 8' - 0" - - 204 - A 3' - 0" 8' - 0" WD PT KD PT H5 - - EXISTING TO REMAIN 204A - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 205 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 206 - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 206A - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 207 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 208 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 209 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 210 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 303 - A 4' - 0" 8' - 0" WD PT KD PT H4 - - - 304A - A 3' - 0" 8' - 0" WD PT KD PT H6 - - - 304B - A 3' - 0" 8' - 0" WD PT KD PT H6 - - - 307 - - 3' - 0" 9' - 0" Y COOKSON THERMISER MAX MODEL ESD30 307 - - 3' - 0" 7' - 0" - EXISTING DOOR -RETROFIT WITH CARD READER 308 - A 3' - 0" 8' - 0" WD PT KD PT H4 - - - 311 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 311A - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 401 - - 3' - 0" 9' - 0" - EXISTING TO REMAIN 401A - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 401B - - 3' - 0" 7' - 0" - EXISTING TO REMAIN 402 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 403 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 404 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 405 - - 3' - 0" 8' - 0" - EXISTING TO REMAIN 405A - - 3' - 0" 8' - 0" - EXISTING TO REMAIN DOOR SCHEDULE ABBREVIATIONS: AL ALUMINUM ANO ANODIZED FF FACTORY FINISH HM HOLLOW METAL KD KNOCK DOWN MIN MINUTE P PAINT; REFER TO FINISH SCHEDULE FOR COLOR STL STEEL WD WOOD Y YES SCALE 3" = 1'-0"11HOLLOW METAL DOOR FRAMESCALE 3" = 1'-0"15KNOCK DOWN FRAME SCALE 1/2" = 1'-0"9PANIC HARDWARE SCALE 1/2" = 1'-0"10TYPICAL CARD READER CONNECTION SCALE 6" = 1'-0"13MARBLE THRESHOLDSCALE 1/2" = 1'-0"17COILING DOOR NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 NOTE: REFINISH STAIN GRADE DOORS IF DAMAGEDSCALE 3" = 1'-0"19HERCULITE DOOR 19 - INSPECTIONS 1. OCFA FINAL INSPECTION REQUIRED. PLEASE SCHEDULE ALL FIELD INSPECTIONS AT LEAST 72 HOURS IN ADVANCE. INSPECTIONS CANCELED AFTER 1 P.M. ON THE DAY BEFORE THE SCHEDULED DATE WILL BE SUBJECT TO A REINSPECTION FEE. PHASING OF INSPECTIONS MAY REQUIRE ADDITIONAL FEES, ALSO. CALL OCFA INSPECTION SCHEDULING AT (714) 573-6150. 2. BUILDINGS UNDER CONSTRUCTION OR DEMOLITION SHALL CONFORM TO CFC CHAPTER 33. NO SMOKING OR COOKING IS ALLOWED IN STRUCTURES WHERE COMBUSTIBLE MATERIALS ARE EXPOSED OR WITHIN 25' OF COMBUSTIBLE MATERIALS STORAGE AREAS. CUTTING, WELDING, OR OTHER HOT WORK SHALL BE IN CONFORMANCE WITH CFC CHAPTER 35. 3. IN BUILDINGS FOUR OR MORE STORIES IN HEIGHT, STANDPIPES SHALL BE PROVIDED DURING CONSTRUCTION WHEN THE HEIGHT REACHES 40 FEET ABOVE THE LOWEST POINT OF FIRE DEPARTMENT ACCESS. A FIRE DEPARTMENT CONNECTION SHALL BE NO MORE THAN 100 FEET FROM AVAILABLE FIRE DEPARTMENT VEHICLE ACCESS ROADWAYS. A HYDRANT SHALL BE LOCATED ALONG THE ACCESS ROADWAY WITHIN 150 FEET OF THE LOCATION(S) THAT THE FDC CAN BE ACCESSED FROM. FC 3310, 3313 4. ADDRESS NUMBERS SHALL BE PROVIDED FOR ALL NEW AND EXISTING BUILDINGS, BE A MINIMUM OF FOUR INCHES HIGH FOR INDIVIDUAL DWELLING UNITS AND SIX INCHES HIGH FOR ALL OTHER INSTALLATIONS AND STRUCTURES, CONTRAST WITH THEIR BACKGROUND, AND BE PLAINLY VISIBLE FROM THE ROADWAY THE BUILDING IS ADDRESSED ON. TEMPORARY ADDRESS NUMBERS SHALL BE PROVIDED ON CONSTRUCTION FENCING OR THE BUILDING UNTIL PERMANENT NUMBERS CAN BE PROVIDED. CBC 501.2, CFC 505.1 5. LOCATIONS AND CLASSIFICATIONS OF EXTINGUISHERS SHALL BE IN ACCORDANCE WITH CFC 906 AND CCR TITLE 19. AT LEAST ONE EXTINGUISHER SHALL BE PROVIDED DURING CONSTRUCTION ON EACH FLOOR AT EACH STAIRWAY, IN EACH STORAGE AND CONSTRUCTION SHED, IN LOCATIONS WHERE FLAMMABLE OR COMBUSTIBLE LIQUIDS ARE STORED OR USED, OR WHERE SIMILAR HAZARDS ARE PRESENT PER CFC 3315.1. BEFORE FINAL OCCUPANCY, AT LEAST ONE 2A:10B:C EXTINGUISHER SHALL BE PROVIDED SO THAT NO POINT IS MORE THAN 75' TRAVEL DISTANCE FROM THE EXTINGUISHER. EXTINGUISHERS SHALL BE LOCATED ALONG THE PATH OF EGRESS TRAVEL AND IN A READILY VISIBLE AND ACCESSIBLE LOCATION, WITH THE BOTTOM OF THE EXTINGUISHER AT LEAST 4”ABOVE THE FLOOR. ADDITIONAL EXTINGUISHERS MAY BE REQUIRED BY OCFA INSPECTORS DEPENDING ON PROJECT OR SITE CONDITIONS AND FINAL PLACEMENT IS SUBJECT TO THEIR APPROVAL. 6. WALL, FLOOR AND CEILING FINISHES AND MATERIALS SHALL NOT EXCEED THE FLAME SPREAD CLASSIFICATIONS IN CBC TABLE 803.11. DECORATIVE MATERIALS SHALL BE PROPERLY TREATED BY A PRODUCT OR PROCESS APPROVED BY THE STATE FIRE MARSHAL WITH APPROPRIATE DOCUMENTATION PROVIDED TO THE OCFA. SUCH ITEMS SHALL BE APPROVED AND INSPECTED BY THE OCFA PRIOR TO INSTALLATION. 7. KNOX BOXES/KEY CABINETS SHALL BE PROVIDED FOR ALL HIGH-RISE BUILDINGS, POOL ENCLOSURES, GATES IN THE PATH OF FIREFIGHTER TRAVEL TO STRUCTURES, SECURED PARKING LEVELS, DOORS GIVING ACCESS TO ALARM PANELS AND/OR ANNUNCIATORS, AND ANY OTHER STRUCTURES OR AREAS WHERE IMMEDIATE ACCESS IS REQUIRED OR IS UNDULY DIFFICULT. AN OCFA INSPECTOR CAN ASSIST WITH LOCKING GATE KEYS IN KNOX BOXES, CONTACT YOUR LOCAL FIRE STATION TO ARRANGE AN APPOINTMENT TO SECURE MASTER BUILDING KEYS IN THE KNOX BOX. 8. APPROVAL OF THESE PLANS SHALL NOT PERMIT THE VIOLATION OF ANY CODE OR LAW. REQUIREMENTS OR FEATURES NOT IDENTIFIED ON THE PLAN MAY APPLY AND OCFA INSPECTORS MAY REQUIRE ADDITIONAL INFORMATION OR ITEMS FROM THOSE SHOWN ON THE PLAN DEPENDING ON ACTUAL OR ANTICIPATED FIELD CONDITIONS. SUCH CHANGES MAY NECESSITATE SUBMITTAL OF REVISED OR AS- BUILT PLANS TO THE OCFA AND THE CITY/COUNTY WHERE THE PROJECT IS LOCATED. GENERAL REQUIREMENTS 1. THE PROJECT SHALL COMPLY WITH CALIFORNIA BUILDING CODE, CALIFORNIA FIRE CODE, AND OTHER CURRENTLY ADOPTED CODES, STANDARDS, REGULATIONS AND REQUIREMENTS AS ENFORCED BY THE ORANGE COUNTY FIRE AUTHORITY. 2. DUMPSTERS AND TRASH CONTAINERS EXCEEDING 1.5 CUBIC YARDS SHALL NOT BE STORED IN BUILDINGS OR PLACED WITHIN 5 FEET OF COMBUSTIBLE WALLS, OPENINGS OR COMBUSTIBLE ROOF EAVE LINES UNLESS PROTECTED BY AN APPROVED SPRINKLER SYSTEM OR LOCATED IN A TYPE I OR IIA STRUCTURE SEPARATED BY 10 FEET FROM OTHER STRUCTURES. CONTAINERS LARGER THAN 1 CUBIC YARD SHALL BE OF NON-OR LIMITED-COMBUSTIBLE MATERIALS OR SIMILARLY PROTECTED OR SEPARATED. CFC 304.3. 3. EXITS, EXIT SIGNS, FIRE ALARM PANELS, HOSE CABINETS, FIRE EXTINGUISHER LOCATIONS, AND STANDPIPE CONNECTIONS SHALL NOT BE CONCEALED BY CURTAINS, MIRRORS, OR OTHER DECORATIVE MATERIAL. 4. THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF ALL OBSTRUCTIONS AT ALL TIMES. NO STORAGE IS PERMITTED IN AISLES. 5. EXIT DOORS SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT. DOORS SHALL NOT BE PROVIDED WITH THUMB-TURN LOCKS OR DEADBOLTS THAT DO NOT UNLATCH IN TANDEM WITH THE NORMAL OPERATING LEVER. THE OPENING FORCE FOR INTERIOR DOORS WITHOUT CLOSERS SHALL NOT EXCEED 5 POUNDS. THE UNLATCHING AND OPENING FORCE FOR OTHER DOORS, INCLUDING FIRE DOORS, SHALL NOT EXCEED 15 POUNDS. CBC 1010 6. THE EXIT PATH SHALL BE CLEARLY IDENTIFIED WITH EXIT SIGNS CONFORMING TO CBC 1013. ILLUMINATED EXIT SIGNS MUST HAVE 90-MINUTE EMERGENCY POWER BACK-UP. 7. TACTILE SIGNS SHALL BE PROVIDED IN COMMERCIAL BUILDINGS, PUBLIC BUILDINGS/ACCOMMODATIONS, AND PUBLICLY FUNDED HOUSING SUBJECT TO CBC CHAPTERS 11A AND B AND CONFORM TO 1143A OR 11B-703.1, -703.2, -703.3, AND 703.5, BE MOUNTED WITH THE BOTTOM OF THE LOWEST LINE OF BRAILLE CHARACTERS AT LEAST 4 FEET ABOVE THE FLOOR BUT THE BOTTOM OF THE HIGHEST LINE OF RAISED TEXT CHARACTERS NO MORE THAN 5 FEET ABOVE THE FLOOR AND, WHENEVER POSSIBLE, ON THE STRIKE SIDE OF THE DOOR. LETTERING SHALL BE BETWEEN 5/8”AND 2” HIGH. CBC 1013.4 8. STAIRS SERVING 4+ STORIES SHALL HAVE STAIRWELL SIGNS CONFORMING TO CBC 1023.9 AND OCFA GUIDELINE E_02. 9. THE EXIT PATH SHALL BE ILLUMINATED AT ALL TIMES IN ACCORDANCE WITH CBC 1006. EMERGENCY LIGHTING SHALL BE PROVIDED WITH 90-MINUTE BACK-UP. 10. RATED ASSEMBLIES SHALL CONFORM TO APPROVED METHODS AND MATERIALS OF CONSTRUCTION. PENETRATIONS THROUGH RATED WALLS, CEILINGS, OR FLOORS SHALL BE PROTECTED IN AN APPROVED MANNER COMPLYING WITH CBC/CFC CHAPTER 7. 11. RATED DOORS SHALL BE SELF-CLOSING AND LATCHING; SUCH DOORS SHALL NOT BE EQUIPPED WITH DOOR STOPS OR OTHERWISE PROPPED OPEN. RATED DOORS SHALL BE EQUIPPED WITH RATED HARDWARE. CFC 703 PROJECT-SPECIFIC REQUIREMENTS ALARM AND MONITORING SYSTEMS 1. A FIRE ALARM SYSTEM SHALL BE PROVIDED IN COMPLIANCE WITH CBC/CFC 907 AND NFPA 72. A SEPARATE PLAN SUBMITTAL IS REQUIRED FOR APPROVAL PRIOR TO INSTALLATION OR MODIFICATION. 2. AUTOMATIC FIRE SPRINKLER SYSTEM(S) AND ALL CONTROL VALVES, WITH THE EXCEPTION OF THOSE LISTED IN CFC 903.4, SHALL BE MONITORED BY A UL LISTED CENTRAL ALARM STATION. EXTINGUISHING SYSTEMS 3. AN AUTOMATIC FIRE SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT THE BUILDING IN COMPLIANCE WITH CFC 903 AND THE APPLICABLE NFPA SPRINKLER STANDARD. REVIEW AND APPROVAL OF A SPRINKLER PLAN IS REQUIRED PRIOR TO INSTALLATION OR MODIFICATION. HAZARDOUS MATERIALS, EQUIPMENT, AND PROCESSES 4. STORAGE, DISPENSING, OR USE OF ANY HAZARDOUS MATERIALS SHALL COMPLY WITH CBC 414 AND 415 AND CFC REGULATIONS. THE STORAGE AND USE OF HAZARDOUS MATERIALS SHALL BE REVIEWED AND APPROVED BY THE OCFA PRIOR TO SUCH MATERIALS BEING BROUGHT ON SITE. APPROPRIATE HAZARDOUS MATERIALS WARNING SIGNS SHALL BE PROMINENTLY PLACED IN THE VICINITY/ENTRANCES TO AREAS WHERE HAZARDOUS MATERIALS ARE STORED IN QUANTITIES SUFFICIENT TO REQUIRE A CFC PERMIT. 1. ENSURE OUTDOOR SMOKING AREAS ARE A MINIMUM OF 25'-0" FROM BUILDING ENTRIES, OUTDOOR AIR INTAKES AND OPERABLE WINDOWS AS REQUIRED BY CALGREEN SECTION 5.504.7. 2. RECYCLE OR SALVAGE FOR REUSE A MINIMUM OF 65% OF THE NON-HAZARDOUS CONSTRUCTION AND DEMOLITION WASTE PER CALGREEN SECTION 5.408.1 OR COMPLY WITH THE LOCAL ORDINANCE, WHICHEVER IS MORE STRINGENT. GC SHALL PROVIDE DOCUMENTATION OF CONSTRUCTION WASTE MANAGEMENT PLANS AS REQUIRED TO ENFORCING AGENCIES. 3. 3.PROVIDE VERIFICATION THAT UNIVERSAL WASTE ITEMS SUCH AS FLORESCENT LAMPS AND BALLAST AND MERCURY-CONTAINING THERMOSTATS AS WELL AS OTHER CALIFORNIA PROHIBITED UNIVERSAL WASTE MATERIALS ARE DISPOSED OF PROPERLY AND ARE DIVERTED FROM LANDFILLS. 4. ALL WALL AND FLOOR ASSEMBLIES SEPARATING TENANTS OR SEPARATING TENANTS FROM PUBLIC SPACES SHALL HAVE A MINIMUM STC RATING OF 40 AS PER CALGREEN SECTION 5.507.4.3. 5. ALL PLUMBING FIXTURES IN AREA OF WORK SHALL COMPLY WITH CALGREEN SECTION 5.303.3. 6. 6PER CA CIVIL CODE 1101 TO 1105, ALL NON-COMPLIANT PLUMBING FIXTURES WITHIN THE AREA OF WORK SHALL BE REPLACED WITH WATER CONSERVING PLUMBING FIXTURES. BUILDINGS FINALED ON OR AFTER 01/01/1994 ARE EXEMPT. 7. PROVIDE HVAC, REFRIGERATION AND FIRE SUPPRESSION SYSTEMS AND EQUIPMENT THAT DO NOT UTILIZE CFC OR HALONS AS PER CALGREEN SECTION 5.508.1. 8. PER CALGREEN SECTION 5.410.4.2, A WRITTEN PLAN OF PROCEDURES FOR TESTING AND ADJUSTMENT FOR NEW SYSTEMS SERVING THE AREA OF WORK IS REQUIRED TO BE DEVELOPED FOR THE FOLLOWING SYSTEMS: A.HVAC SYSTEMS AND CONTROLS B.INDOOR LIGHTING AND CONTROLS C.WATER HEATING SYSTEMS 9. PERFORM TESTING AND ADJUSTMENT OF REQUIRED SYSTEMS, INCLUDING HVAC BALANCING, AND PROVIDE REPORTS TO BUILDING OWNER AND ENFORCING AGENCIES AS PER CALGREEN SECTION 5.410.4.3 AND 5.410.4.4. 10. DURING CONSTRUCTION, MINIMIZE USE OF PERMANENT HVAC SYSTEMS. IF SYSTEM IS USED DURING CONSTRUCTION, PROTECT RETURN AIR TRUNK WITH AIR FILTERS WITH AN MINIMUM MERV RATING OF 8. REPLACE ALL FILTERS AT COMPLETION OF CONSTRUCTION. 11. ALL DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC, SHEET METAL OR OTHER METHODS TO REDUCE THE AMOUNT OF DUST, WATER AND DEBRIS ENTERING THE SYSTEM FROM THE TIME OF ROUGH INSTALLATION AND DURING STORAGE ON THE CONSTRUCTION SITE UNTIL FINAL START UP. 12. ALL FINISH MATERIALS SHALL COMPLY WITH THE VOC LIMITS LISTED IN CALGREEN SECTIONS 5.504.4.1 TO 5.504.4.4. VERIFICATION OF COMPLIANCE SHALL BE PROVIDED TO ENFORCING AGENCIES AS REQUIRED OR REQUESTED. 13. ALL COMPOSITE WOOD PRODUCTS SHALL COMPLY WITH THE FORMALDEHYDE LIMITS LISTED IN CALGREEN SECTION 5.504.4.5. VERIFICATION OF COMPLIANCE SHALL BE PROVIDED TO ENFORCING AGENCIES AS REQUIRED OR REQUESTED. 14. RESILIENT FLOORING SHALL COMPLY WITH THE REQUIREMENTS OF CALGREEN SECTION 5.504.4.6. VERIFICATION OF COMPLIANCE SHALL BE PROVIDED TO ENFORCING AGENCIES AS REQUIRED OR REQUESTED. 15. PROVIDE THE BUILDING OWNER AN OPERATING AND MAINTENANCE (O&M) MANUAL WITH DETAIL OPERATING AND MAINTENANCE INSTRUCTION AND COPIES OF ALL GUARANTEES AND WARRANTIES FOR EACH INSTALLED SYSTEM. THE O&M INSTRUCTIONS SHALL BE CONSISTENT WITH OSHA REQUIREMENTS IN CR, TITLE 8 SECTION 5142 AND OTHER RELATED REGULATIONS. INCLUDE COPIES OF ALL INSPECTIONS AND REPORTS FROM THE TESTING AND ADJUSTMENT PROCEDURES IN THE O&M MANUAL. 1. ALL WORK SHALL BE IN ACCORDANCE WITH CURRENT APPLICABLE NATIONAL, STATE, AND LOCAL CODES, LAWS AND ORDINANCES, INCLUDING ACCESS REQUIREMENTS. 2. "ARCHITECT" AS USED IN THESE DOCUMENTS REFER TO HENDY, (949) 851-3080. 3. GENERAL CONTRACTOR FOR THE PROJECT SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED BUILDING PERMITS. 4. EXAMINE ALL CONTRACT DOCUMENTS AND FIELD CONDITIONS AND CONFIRM THAT WORK IS BUILDABLE AS SHOWN. IF THERE ARE QUESTIONS OR DISCREPANCIES, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION FROM HENDY BEFORE PROCEEDING WITH WORK IN QUESTION. 5. VERIFY ALL DIMENSIONS ON JOB SITE BEFORE START OF ANY CONSTRUCTION. DO NOT SCALE DRAWINGS. DIMENSIONS SHALL GOVERN. 6. LARGE SCALE DRAWINGS TAKE PRECEDENCE OVER SMALL SCALE DRAWINGS. DETAILS GOVERN OVER PLANS. NOTIFY HENDY OF ANY DISCREPANCIES. 7. "TYPICAL" AS USED IN THESE DOCUMENTS SHALL MEAN THAT THE CONDITION IS THE SAME OR REPRESENTATIVE FOR ALL SIMILAR CONDITIONS THROUGHOUT, U.N.O. 8. "SIMILAR" MEANS COMPARABLE CHARACTERISTICS FOR THE CONDITIONS NOTED. VERIFY DIMENSIONS AND ORIENTATIONS ON PLANS AND ELEVATIONS. 9. DETAILS NOTED "TYPICAL" ARE KEYED ONLY ONCE AND ARE REPRESENTATIVE OF SIMILAR CONDITIONS THROUGHOUT, U.N.O. 10. "ALIGN" AS USED IN THESE DOCUMENTS SHALL MEAN TO ACCURATELY LOCATE FINISH FACES IN THE SAME PLANE. 11. WHERE NOTED "V.I.F." OR "VERIFY IN FIELD”THE DIMENSIONS SHALL BE CONFIRMED IN THE FIELD BY THE GENERAL CONTRACTOR. NOTIFY HENDY OF DISCREPANCIES GREATER THAN 2 INCHES. 12. ALL VERTICAL DIMENSIONS ARE SHOWN FROM FINISH FLOOR, U.N.O. 13. MAKE VERTICAL WORK PLUMB AND MAKE HORIZONTAL WORK LEVEL AND WITH ALIGNMENT AS INDICATED. 14. MAINTAIN MINIMUM HEADROOM CLEARANCE OF 90 INCHES IN ALL OCCUPIED SPACES AND 84 INCHES IN RESTROOMS. 15. ALL WORK NOTED "N.I.C.," "NOT IN CONTRACT," OR BY OTHERS SHALL BE ACCOMPLISHED BY A CONTRACTOR OTHER THAN THE GENERAL CONTRACTOR AND ARE NOT PART OF THE CONSTRUCTION AGREEMENT. THE GENERAL CONTRACTOR SHALL COORDINATE WITH OWNER OR TENANT'S VENDORS AND CONTRACTORS AS REQUIRED BY OWNER, TENANT OR BOTH. 16. BEFORE PROCEEDING WITH EACH COMPONENT OF WORK, EXAMINE SUBSTRATES, AREAS AND CONDITIONS, WITH THE INSTALLER OR APPLICATOR PRESENT FOR COMPLIANCE REQUIREMENTS FOR INSTALLATION TOLERANCES AND OTHER CONDITIONS AFFECTING PERFORMANCE. A.EXAMINE ROUGH IN FOR MECHANICAL AND ELECTRICAL SYSTEMS TO VERIFY ACTUAL LOCATIONS OF CONNECTIONS BEFORE EQUIPMENT AND FIXTURE INSTALLATION. B.EXAMINE WALLS, FLOORS, AND CEILINGS FOR SUITABLE CONDITIONS WHERE PRODUCTS AND SYSTEMS ARE TO BE INSTALLED. C.VERIFY COMPATIBILITY WITH AND SUITABILITY OF SUBSTRATES, INCLUDING COMPATIBILITY WITH EXISTING FINISHES OR PRIMERS. D.PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED. PROCEEDING WITH THE WORK INDICATES ACCEPTANCE OF SURFACES AND CONDITIONS. 17. GENERAL CONTRACTOR SHALL PROVIDE RECORD DOCUMENTS TO BUILDING OWNER/TENANT AND HENDY UPON COMPLETION OF TENANT CONSTRUCTION. 18. WHERE EXISTING CEMENTITIOUS FIREPROOFING IS MISSING OR REMOVED DUE TO CONSTRUCTION, PROVIDE SPRAY APPLIED CEMENTITIOUS FIREPROOFING FOR CONTINUOUS AND CONSISTENT PROTECTION. 19. DELIVER, STORE AND HANDLE PRODUCTS USING MEANS AND METHODS THAT WILL PREVENT DAMAGE, DETERIORATION, AND LOSS, INCLUDING THEFT AND VANDALISM. COMPLY WITH MANUFACTURERS' WRITTEN INSTRUCTIONS. 20. PROVIDE PRODUCTS THAT COMPLY WITH THE CONTRACT DOCUMENTS, ARE UNDAMAGED, AND UNLESS OTHERWISE INDICATED, ARE NEW AT THE TIME OF INSTALLATION. 21. INSTALL ALL MANUFACTURED ITEMS, MATERIALS AND EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS AND WRITTEN INSTRUCTIONS, INCLUDING INSTRUCTIONS FOR TEMPERATURE, HUMIDITY, VENTILATION, AND WEATHER-PROTECTION. 22. VERIFY ALL APPLIANCE AND EQUIPMENT REQUIREMENTS WITH MANUFACTURERS. PROVIDE ALL WALL BACKING, ELECTRICAL AND PLUMBING SUPPLIES, FITTINGS AND CONNECTORS TO SUPPORT OR COMPLETE INSTALLATION. SUPPLY CUT-SHEETS FOR APPROVAL. 23. COORDINATE BACKING WITH MILLWORKER FOR WALL HUNG UNITS AND FEATURES. 24. PROVIDE FINAL PROTECTION AND MAINTAIN CONDITIONS THAT ENSURE INSTALLED WORK IS WITHOUT DAMAGE OR DETERIORATION AT THE TIME OF SUBSTANTIAL COMPLETION. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR TEMPERATURE AND RELATIVE HUMIDITY. 25. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE GENERAL CLEANING OF A JOB AFTER COMPLETION. CLEANING SHALL INCLUDE INTERIOR OF THE BUILDING AND PATH OF TRAVEL TO THE JOB SITE, THE PARKING LOT, ELEVATORS, STAIRS, LOBBIES & CORRIDORS. 26. DIVERT NON-HAZARDOUS CONSTRUCTION, DEMOLITION, AND PACKAGING DEBRIS FROM LANDFILL DISPOSAL. REDIRECT RECYCLABLE, SALVAGEABLE, OR REUSABLE MATERIALS TO APPROPRIATE SITES OR CHARITABLE ORGANIZATIONS, INCLUDING: CARDBOARD, METAL, BRICK, CONCRETE, GLASS, PLASTIC, CLEAN WOOD, GYPSUM WALLBOARD, CARPET, AND INSULATION. 1. DURING BID PROCESS IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO SITE VERIFY ALL CLEARANCES, INCLUDING IN PLENUM AREA. ADVISE IF MECHANICAL EQUIPMENT, MAIN SPRINKLER LINES, OR OTHER EXISTING ITEMS REQUIRE RELOCATION. 2. ANY REQUESTS FOR SUBSTITUTIONS OF ITEMS SPECIFIED SHALL BE SUBMITTED IN WRITING WITH CUT- SHEETS ATTACHED. IT WILL BE CONSIDERED ONLY IF IT HAS A MORE ADVANTAGEOUS DELIVERY DATE, A LOWER PRICE (WITH CREDIT TO THE TENANT) AND WILL BE PROVIDED WITHOUT SACRIFICING QUALITY, APPEARANCE AND FUNCTION. 1. REQUESTS FOR SUBSTITUTIONS OF ITEMS SPECIFIED SHALL BE SUBMITTED IN WRITING WITH CUT- SHEETS ATTACHED. CONSIDERATION WILL ONLY BE GIVEN WITH AN ADVANTAGEOUS DELIVERY DATE, A LOWER PRICE (WITH CREDIT TO THE TENANT) AND WILL BE PROVIDED WITHOUT SACRIFICING QUALITY, APPEARANCE AND FUNCTION. 2. THE GENERAL CONTRACTOR SHALL SUBMIT CONFIRMATION OF DELIVERY DATES FOR ORDERS OF MATERIALS AND EQUIPMENT HAVING LONG LEAD TIMES TO HENDY AT START OF PROJECT CONSTRUCTION. 3. SUBMIT (3) SAMPLES OF ALL MATERIALS TO HENDY FOR APPROVAL PRIOR TO ORDERING OR INSTALLATION. THE CONTRACTOR SHALL BE WHOLLY LIABLE BY FAILING TO DO SO WHETHER ITEMS ARE SPECIFIED CORRECTLY OR INCORRECTLY IN THE CONTRACT DOCUMENTS. SUBMITTALS ITEMS SHALL INCLUDE, BUT ARE NOT LIMITED TO: A.STONEWORK, MILLWORK, METALWORK, DOORS, DOOR HARDWARE, APPLIANCES & EQUIPMENT, FINISH MATERIALS, ACOUSTICAL CEILING TILES, SUSPENSION SYSTEMS, FIXTURES, MECHANICAL DEVICES, AND THE LIKE. B.SUBMITTALS SHALL INCLUDE SHOP DRAWINGS, PRODUCT DATA, SAMPLES AND OTHER ITEMS. C.SHOP DRAWINGS SHALL INCLUDE DETAILED FABRICATION AND INSTALLATION, SETTING DRAWINGS, DIAGRAMMATIC DRAWINGS AND MATERIAL SCHEDULES. LOCATION AND ORIENTATION OF ALL ITEMS SHALL BE CLEARLY INDICATED. BEGIN FABRICATION ONLY AFTER RECEIVING HENDY APPROVAL OF SHOP DRAWINGS. 1. REMOVE AND DISPOSE OF ALL ITEMS SHOWN ON PLANS IN A LEGAL MANNER. RECYCLE AS REQUIRED BY LOCAL MUNICIPALITY. 2. EXAMINE THE SITE AND ALL CONDITIONS AND LIMITATIONS WHETHER OR NOT THEY ARE SPECIFICALLY SHOWN OR MENTIONED IN ANY OF THE CONTRACT DOCUMENTS AND INCLUDE WHATEVER IS NEEDED TO COMPLETE THE WORK IN EVERY PART SHOWN OR DESCRIBED BY THE CONTRACT. 3. CHECK DRAWINGS CAREFULLY AND THOROUGHLY INVESTIGATE EXISTING CONSTRUCTION. FURNISH AND INSTALL SHORING AND BRACING NECESSARY TO POSITIVELY PROTECT THE STRUCTURAL ELEMENTS OF THE BUILDING. REMOVE ALL SHORING AND BRACING WHEN CONSTRUCTION IS SAFELY IN PLACE. 4. ALL CORRIDORS, STAIRWAYS AND RATED LOBBIES THAT ARE PART OF THE PATH OF EGRESS SHALL REMAIN OPERATIONAL AND FREE OF DEBRIS. ALL WORK IN THESE AREAS SHALL BE PERFORMED AFTER REGULAR BUSINESS HOURS. 5. REMOVED MATERIALS NOT DESIGNATED FOR REUSE AND ALL DEBRIS FROM CONSTRUCTION BECOMES THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE SITE IN A TIMELY MANNER. 6. DO NOT ALLOW MATERIALS AND DEBRIS GENERATED BY DEMOLITION ACTIVITIES TO ACCUMULATE. REMOVE DAILY AND DISPOSE OFF SITE IN A LEGAL MANNER. 7. REMOVE ALL DOOR ASSEMBLIES SHOWN DASHED. STOCKPILE UNUSED DOOR ASSEMBLIES FOR REUSE WITHIN THE BUILDING AT THE DISCRETION OF BUILDING MANAGEMENT. IDENTIFY ANY DOOR ASSEMBLIES TO BE REUSED, PROVIDE PROTECTION AND STORE AS DIRECTED. 8. REMOVE ALL WALLS SHOWN DASHED AND ITEMS LOCATED ON WALLS, INCLUDING BUT NOT LIMITED TO ELEC/TELE/DATA OUTLETS, SWITCHES, TIMERS, ETC. 9. ALL EXISTING ELECTRICAL, MECHANICAL AND PLUMBING SYSTEMS NOT REQUIRED FOR PROPOSED CONFIGURATION SHALL BE REMOVED TO THE FURTHEST TERMINATION POINT. ELIMINATE ALL UNUSED WIRING, PLUMBING, DUCTWORK, ETC. COMPLETELY FROM CEILING SPACES OR WALLS. THIS SHALL BE DONE TO THE SATISFACTION OF THE BUILDING INSPECTORS (UNLESS NOTED OTHERWISE). 10. A 24-HOUR FIRE WATCH SHALL BE MAINTAINED DURING ANY WORK THAT COMPROMISES THE RATING AND/OR OBSTRUCTS THE EXITING OF ANY AND ALL CORRIDORS, STAIRWAYS OR RATED LOBBIES. 11. ABANDONED CABLING SHALL BE REMOVED. COORDINATE WITH TENANT REQUIREMENTS FOR PROPOSED WORK AND PROTECT EXISTING CABLING TO REMAIN IN PLACE. 12. EXERCISE THE GREATEST POSSIBLE CARE WHEN REMOVING ITEMS SCHEDULED FOR REUSE. USE ONLY CONTRACTORS SKILLED IN THE APPROPRIATE TRADES. PROVIDE PROTECTION AND STORE AS DIRECTED IN CONTRACT DOCUMENTS. 13. EXISTING ITEMS NOTED TO REMAIN, BUT WHICH REQUIRE REMOVAL TO COMPLETE THE WORK, SHALL BE PROTECTED, CAREFULLY REMOVED AND REPLACED UPON COMPLETION. THE REPLACED WORK SHALL MATCH ITS CONDITION AT THE START OF THE WORK. 14. LEAVE ALL SPACES BROOM CLEAN WITH ALL LEDGES AND CORNERS PROPERLY CLEANED. 15. WHERE CUT OPENINGS ARE OVERSIZED OR AT IMPROPER LOCATION, MATERIAL SHALL BE REPLACED AT NO EXTRA COST TO THE OWNER/TENANT. 16. PROVIDE TEMPORARY SUPPORT OF WORK TO BE CUT. PROTECT IN PLACE CONSTRUCTION DURING CUTTING AND REMOVAL TO PREVENT DAMAGE TO ADJACENT SURFACES. 17. CUT OR DRILL FROM THE EXPOSED OR FINISHED SIDE OF MATERIALS TO REMAIN. 18. DO NOT CUT STRUCTURAL ELEMENTS IN A MANNER THAT COULD CHANGE THEIR LOAD-CARRYING CAPACITY OR LOAD-DEFLECTION RATIO. 19. DO NOT CUT OPERATING ELEMENTS TO REMAIN OR THEIR RELATED COMPONENTS IN A MANNER THAT RESULTS IN REDUCING THEIR CAPACITY TO PERFORM AS INTENDED OR THAT RESULTS IN INCREASED MAINTENANCE OR DECREASED OPERATIONAL LIFE OR SAFETY. 1. IN AREAS WHERE DEMOLITION (REMOVAL OF TILE, CARPETING, PARTITIONS, ETC) CAUSES DIVOTS OR UNEVENNESS IN SLAB, THE CONTRACTOR SHALL PATCH TO LEVEL THE SLAB TO RECEIVE FINISHES. 2. WHERE REQUIRED FOR FLOOR LEVELING, PROVIDE CEMENT-BASED, POLYMER-MODIFIED, SELF-LEVELING PRODUCT THAT CAN BE APPLIED IN UNIFORM THICKNESS FROM 1/8" AND THAT CAN BE FEATHERED AT EDGES TO MATCH ADJACENT FLOOR ELEVATIONS. COMPRESSIVE STRENGTH SHALL NOT BE LESS THAN 4100 PSI AT 29 DAYS. 3. DO NOT PATCH CONSTRUCTION IN A MANNER THAT RESULTS IN VISUAL EVIDENCE OF CUTTING AND PATCHING. REMOVE AND REPLACE CONSTRUCTION THAT HAS BEEN CUT AND PATCHED IN A VISUALLY UNSATISFACTORY MANNER, OR THAT, IN THE ARCHITECT'S OPINION, REDUCES THE BUILDING'S AESTHETIC QUALITIES. 1. COLUMN CENTERLINES (ALSO REFERRED TO AS GRID LINES) ARE SHOWN FOR REFERENCE. 2. DIMENSIONS ARE TO FINISH FACE OF WALL, U.N.O. 3. DOOR OPENINGS WHICH ARE NOT DIMENSIONED SHALL BE LOCATED WITHIN 4 INCHES OF ADJOINING PARTITIONS. 4. HENDY SHALL REVIEW AND APPROVE ALL CHALK LINES PRIOR TO INSTALLATION OF TRACK. HENDY WILL BE NOTIFIED OF ANY DEVIATIONS FROM CONSTRUCTION DIMENSIONS OR CLEARANCE IDENTIFIED ON PLAN OR ANY CONSTRUCTION CONFLICTS. 5. USE 5/8”MOISTURE RESISTANT "GREEN BOARD" GYPSUM BOARD ON ALL WET WALLS. 6. PROVIDE AND INSTALL 16 GAUGE GALVANIZED METAL WALL BACKING AT ALL BUILT-IN MILLWORK LOCATIONS, HANGING WALL EQUIPMENT, ETC. COORDINATE EXACT LOCATIONS. 7. ALL INTERIOR WALLS AND PARTITIONS SHALL BE CONSTRUCTED TO RESIST ALL LOADS TO WHICH THEY ARE SUBJECTED BUT NOT LESS THAN A FORCE OF FIVE POUNDS PER SQUARE FOOT APPLIED PERPENDICULAR TO THE WALLS. 8. ALL INTERIOR PARTITIONS SHALL MEET THE "AWCI RECOMMENDED LEVELS" FOR A LEVEL 4 FINISH, U.N.O. WHERE DEEP TONE PAINT IS SCHEDULED, SKIM COAT FULL SURFACE OF SUBSTRATE TO LEVEL 5 FINISH. 9. PROVIDE A "LEVEL-5" FINISH AT GYP. BD. CEILINGS AND SOFFITS. 10. PROVIDE MINIMUM FURRING AT ALL UNFURRED INTERIOR COLUMNS & RATED WALLS TO 6 INCHES ABOVE CEILING, OR TO STRUCTURE ABOVE AT EXPOSED CEILINGS, U.N.O. 11. PROVIDE GYP. BD. FURRING AT ALL EXPOSED PERIMETER BULKHEAD CONDITIONS AND ABOVE ALL EXPOSED PERIMETER WINDOW HEAD CONDITIONS TO 6 INCHES ABOVE SUSPENDED CEILING, OR TO STRUCTURE AT EXPOSED CEILINGS, U.N.O. 12. PREPARE EXISTING SURFACES FOR FINISHES. ALL SURFACES SHALL BE PROPERLY PREPARED FREE FROM ADHESIVE, BUMPS, CRACKS, ETC. 13. ALL PENETRATIONS AT ONE OR TWO HOUR PARTITIONS AND FLOORS SHALL BE PROTECTED BY FIRE RATED ASSEMBLIES TO MAINTAIN RATING 14. AT STC-RATED ASSEMBLES, SEAL CONSTRUCTION AT PERIMETERS, BEHIND CONTROL JOINTS, AND AT OPENINGS AND PENETRATIONS WITH A CONTINUOUS BEAD OF ACOUSTICAL SEALANT. INSTALL ACOUSTICAL SEALANT AT BOTH FACES OF PARTITIONS AND PERIMETERS AND THROUGH PENETRATIONS. COMPLY WITH ASTM C 919 AND WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS FOR LOCATING EDGE TRIM AND CLOSING OFF SOUND FLANKING PATHS AROUND OR THROUGH ASSEMBLIES INCLUDING SEALING PARTITIONS ABOVE ACOUSTICAL CEILINGS. 15. CONTRACTOR SHALL VERIFY LOCATIONS OF ALL FIRE EXTINGUISHERS. FINAL LOCATION OF FIRE EXTINGUISHERS SHALL BE REVIEWED BY HENDY PRIOR TO INSTALLATION. 16. USE 3-5/8" MINIMUM METAL STUDS AT ALL PLUMBING WALLS. 17. PENETRATIONS OF FIRE-RESISTIVE WALLS AND FLOORS/CEILINGS SHALL BE PROTECTED AS REQUIRED IN CBC 710, 711, 712 AND 713. 18. NOTIFY HENDY WHEN ACCESS PANELS ARE REQUIRED FOR MECHANICAL, ELECTRICAL, OR PLUMBING INSTALLATIONS PER BUILDING CODES. THE STYLE AND LOCATIONS OF REQUIRED ACCESS PANELS SHALL BE COORDINATED WITH ARCHITECT PRIOR TO INSTALLATION. 1. FOR INTERIOR FRAMES, COORDINATE WITH DOOR HARDWARE AND GLAZING 2. AT FIRE RATED ASSEMBLIES PROVIDE FRAME ASSEMBLIES COMPLYING WITH NFPA 80 AND LISTED AND LABELED BY A QUALIFIED TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION FOR FIRE PROTECTION RATINGS AND TEMPERATURE-RISE LIMITS INDICATED. 3. WHERE HOLLOW METAL FRAMES ARE FABRICATED IN SECTIONS BECAUSE OF SHIPPING OR HANDLING LIMITATIONS, FIELD SPLICE AT APPROVED LOCATIONS BY WELDING FACE JOINT CONTINUOUSLY, GRIND, FILL, DRESS, AND MAKE SPLICE SMOOTH, FLUSH AND INVISIBLE ON EXPOSED FACES. 4. CHECK PLUMB, SQUARE, AND TWIST OF FRAMES AS WALLS ARE CONSTRUCTED. SHIM AS NECESSARY TO COMPLY WITH INSTALLATION TOLERANCES. 5. CLEAN EXPOSED FRAME SURFACES PROMPTLY AFTER INSTALLATION, USING CLEANING METHODS RECOMMENDED BY FRAME MANUFACTURER AND ACCORDING TO AAMA 609 AND 610. TOUCH UP MARRED FRAME SURFACES SO TOUCH UP IS NOT VISIBLE FROM A DISTANCE OF 48 INCHES. REMOVE AND REPLACE ALUMINUM FRAMES WITH DAMAGED FINISH THAT CANNOT BE SATISFACTORILY REPAIRED. 1. ALL GLAZING SHALL BE INSTALLED PER CBC CHAPTER 24 2. FIELD MEASURE FOR ALL GLAZING AND MILLWORK CONDITIONS PRIOR TO MANUFACTURING. 3. GLAZING AREAS LARGER THAN A SINGLE PANE OF GLASS SHALL HAVE EQUAL SIZED PANES OF GLASS AS LARGE AS POSSIBLE WITH A MAXIMUM WIDTH OF 5 FEET EACH, U.N.O. 4. UNLESS NOTED OTHERWISE, PROVIDE MINIMUM GLAZING THICKNESS AS FOLLOWS: A.1/4" AT ALL FRAMED SIDELIGHTS AND GLAZING LESS THAN 5' X 9' SUPPORTED ON 3 SIDES OR AS REVIEWED BY STRUCTURAL ENGINEER B.3/8" AT TOP AND BOTTOM FRAMED, BUTT-JOINED CORNERS C.1/2" AT SIDELIGHTS AND GLAZING WITH SEISMIC CLIPS W HERE UNSUPPORTED ON TWO OR MORE SIDES D.5/8" AT SIDELIGHTS AND GLAZING WHERE UNSUPPORTED ON TWO OR MORE SIDES E.5/8" AT FRAMELESS DOOR AND SIDELIGHT CONDITIONS AND WHERE UNSUPPORTED ON TWO OR MORE SIDES WITHOUT SEISMIC CLIPS 5.COORDINATE GLAZING CHANNEL DIMENSIONS TO PROVIDE NECESSARY BITE ON GLASS, MINIMUM EDGE AND FACE CLEARANCES AND ADEQUATE SEALANT THICKNESS, WITH REASONABLE TOLERANCES. 6.CLEAN GLAZING CHANNELS AND OTHER FRAMING MEMBERS RECEIVING GLASS IMMEDIATELY BEFORE GLAZING. REMOVE COATINGS NOT FIRMLY BONDED TO SUBSTRATES. EXAMINE GLAZING UNITS TO LOCATE INTERIOR AND EXTERIOR SURFACES. LABEL OR MARK UNITS AS NEEDED SO THAT EXTERIOR AND INTERIOR SURFACES ARE READILY IDENTIFIABLE. DO NOT USE MATERIALS THAT LEAVE VISIBLE MARKS ON THE COMPLETED WORK. 7.PROVIDE EDGE BLOCKING WHERE INDICATED OR NEEDED TO PREVENT GLASS LITES FROM MOVING SIDEWAYS IN GLAZING CHANNEL, AS RECOMMENDED IN WRITING BY GLASS MANUFACTURER AND ACCORDING TO REQUIREMENTS IN REFERENCE GLAZING PUBLICATIONS. 1. THE CONTRACTOR SHALL FURNISH AND INSTALL REQUIRED DOOR AND FRAME ASSEMBLIES AS SPECIFIED IN THE DRAWINGS, U.N.O. 2. PROVIDE DOORS MADE WITH ADHESIVES AND COMPOSITE WOOD PRODUCTS THAT DO NOT CONTAIN UREA-FORMALDEHYDE RESINS. 3. FINISH DOORS AT FACTORY THAT ARE INDICATED TO RECEIVE TRANSPARENT FINISH. 4. ALL HOLLOW METAL DOOR FRAMES SHALL BE STEEL FRAMES WHETHER OR NOT THEY ARE SHOWN ON APPROVED SET OF DRAWINGS. 5. DOOR SHALL BE INSTALLED IN FRAME WITH 1/8" MAX. TOLERANCE AT HEAD HINGES, AND STRIKE JAMB. 6. THE CONTRACTOR SHALL VERIFY AND COORDINATE THE THICKNESS OF FLOOR FINISH WITH UNDERCUT DIMENSION AT DOOR. 7. EXISTING DOORS, CLOSET DOORS, RESTROOM DOORS, ETC. IN A ONE-HOUR CORRIDOR SHALL BE 20 MINUTE RATED DOORS. 8. A SINGLE LEAF OF A SWINGING DOOR SHALL NOT EXCEED FOUR FEET IN WIDTH. THE MINIMUM CLEAR WIDTH SHALL BE 32 INCHES (CBC 1010.1.1.) 9. EXIT DOORS SHALL SWING IN THE DIRECTION OF EXIT TRAVEL WHEN SERVING ANY HAZARDOUS AREA OR WHEN SERVING AN AREA HAVING AN OCCUPANT LOAD OF 50 OR MORE. (CBC 1010.1.2.1) 10. THE FORCE FOR PUSHING OR PULLING OPEN INTERIOR SWINGING EGRESS DOORS, OTHER THAN FIRE DOORS, SHALL NOT EXCEED 5 POUNDS. FORCES SHALL BE APPLIED TO THE LATCH SIDE OF THE DOOR. (CBC 1010.1.3) 11. ALL DOORS SHALL BE ACCESSIBLE BY DISABLED PERSONS, COMPLYING WITH CBC 1010.1, 1010.2 AND 11B-404. INCLUDING LEVER TYPE HARDWARE. 12. EXIT DOORS SHALL BE OPENABLE FROM INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT. (CBC 1010.2) 13. MAIN EXTERIOR EXIT DOORS WHICH OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS NEED NOT BE SIGNED WHEN APPROVED BY THE BUILDING OFFICIAL. (CBC 1013.1) 14. DOORWAYS SHALL BE LEVEL: 60 INCHES DEEP LEVEL AREA SHALL BE PROVIDED IN THE DIRECTION OF DOOR SWING. 44 INCHES DEEP LEVEL AREA WHEN DOOR SWINGS AWAY FROM APPROACH. (CBC 11B-404.2.4) THE WIDTH OF THE LEVEL AREA SHALL EXTEND 24 INCHES PAST THE STRIKE EDGE ON THE SIDE TO SWINGS ON EXTERIOR DOORS AND 18 INCHES PAST THE STRIKE EDGE ON INTERIOR DOORS. (CBC TABLE 11B-404.2.4.1) 15. THE BOTTOM 10 INCHES OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING SHALL HAVE A SMOOTH UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. WHERE NARROW FRAME DOORS ARE USED, A 10 INCHES HIGH SMOOTH PANEL SHALL BE INSTALLED ON THE PUSH SIDE OF THE DOOR, WHICH WILL ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOT-REST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. (CBC 11B-404.2.10) 16. DOOR ASSEMBLIES OFTEN PROVIDE ACCESSIBILITY, LIFE SAFETY AND SECURITY FUNCTIONS WHICH CAN INCREASE THEIR COMPLEXITY DRAMATICALLY. DOOR INSTALLERS SHALL LOOK AT THE CRITERIA FOR INSPECTING. SEE SECTION 5.2.4 OF NFPA 80. NFPA 80 DOES NOT REQUIRE THE INSPECTIONS TO BE PERFORMED BY THIRD-PARTY INSPECTION, NOR DOES IT REQUIRE PROFESSIONAL CERTIFICATION FOR THE INSPECTORS, ONLY THAT THE INSPECTORS ARE KNOWLEDGEABLE ABOUT THE TYPES OF OPENINGS BEING INSPECTED. 1. ALL LOCKSETS SHALL BE CODED AND/OR KEYED IN ACCORDANCE WITH OWNER'S REQUIREMENTS. CODES AND/OR KEYS SHALL BE DELIVERED TO OWNER PROPERLY TESTED AND/OR TAGGED. THE NUMBER OF MASTER AND PASS KEYS SHALL BE COORDINATED WITH OWNER. 2. HARDWARE SUPPLIER SHALL PROVIDE GRANDMASTER KEY, MASTER KEY, KEY-ALIKE AND/OR KEY- DIFFERENT ALL LOCKS IN ACCORDANCE WITH KEYING SCHEDULE AS PROVIDE BY OWNER. 3. THE ATTACHED HARDWARE SCHEDULE IS INTENDED TO COVER ALL DOORS IN THE PROJECT AND ESTABLISH A TYPE AND STANDARD OF QUALITY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FURNISH AND INSTALL A COMPLETE AND OPERATIONAL SYSTEM OF DOOR FINISH HARDWARE ITEMS ENCOMPASSING ALL OPENINGS WITHIN THE PROJECT AREA. 4. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL HARDWARE AS REQUIRED TO MEET CODE AND FUNCTIONAL REQUIREMENTS. THE OUTLINE HARDWARE SPECIFICATION IS PROVIDED AS A BASIS FOR A COMPLETE SUBMITTAL BY THE DETAILED HARDWARE LIST WHICH INDICATES THE QUANTITY, TYPE, CATALOG NUMBER, MANUFACTURER, AND AND LOCATION OF EACH ARTICLE OF HARDWARE REQUIRED. HARDWARE LIST SHALL BE SUBMITTED NO LATER THAN 30 DAYS BEFORE THE ORDER DATE NECESSARY TO MEET THE PROJECT SCHEDULE. HENDY REVIEW OF THE HARDWARE LIST SHALL NOT REPRESENT CERTIFICATION THAT THE LIST IS COMPLETE AND DOES NOT RELIEVE THE CONTRACTOR FROM PROVIDING A COMPLETE PROJECT. 5. ALL HARDWARE SHALL BE OF LEVER TYPE TO COMPLY WITH ACCESSIBILITY REQUIREMENTS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REPLACE ALL DOOR HARDWARE ITEMS NOT IN COMPLIANCE WITH APPLICABLE ACCESSIBILITY REQUIREMENTS TO THE SATISFACTION OF THE BUILDING AUTHORITY. 6. 6EACH ARTICLE OF HARDWARE SHALL BE INDIVIDUALLY PACKAGED IN ITS ORIGINAL MANUFACTURER'S CONTAINER AND PROPERLY MARKED OR LABELED IN CONFORMANCE WITH THE APPROVED HARDWARE LIST. 7. ALL FASTENERS SHALL MATCH THE HARDWARE MATERIAL AND FINISH. 8. ALL HARDWARE APPLIED TO METAL DOORS OR JAMBS SHALL BE MADE TO TEMPLATE AND SECURED BY MACHINE SCREWS. FURNISH (3) BUTT HINGES FOR DOORS UP TO 7'-0" HIGH AND (1) HINGE FOR EACH ADDITIONAL 2'-6". 9. PROVIDE STANDARD STRIKE PLATE WITH EXTENDED LIP WHERE REQUIRED TO PROTECT TRIM FROM BEING MARRED OR DAMAGED BY THE LATCH BOLT. 10. PROVIDE DUST COVERS AT ALL STRIKE PLATES. 11. LATCHING & LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS, OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP THE OPENING HARDWARE. HARDWARE SHALL BE CENTERED BETWEEN 34 INCHES AND 44 INCHES MAX. ABOVE THE FLOOR (CBC 11B-404) 12. MAIN EXTERIOR DOORS IN A GROUP B OCCUPANCY ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED LOCKING DEVICE PROVIDED. THERE IS A VISIBLE, DURABLE SIGN ON OR ADJACENT TO THE DOOR STATING "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." THE LETTERS SHALL NOT BE LESS THAN 1 INCH ON A CONTRASTING BACKGROUND. THE LOCKING DEVICE MUST BE A TYPE THAT WILL BE READILY DISTINGUISHABLE AS LOCKED. (CBC 1010.2.4(3)) 13. WHERE EGRESS DOORS ARE USED IN PAIRS, APPROVED AUTOMATIC FLUSH BOLTS SHALL BE PERMITTED TO BE USED, PROVIDED THAT THE DOOR LEAF HAVING THE AUTOMATIC FLUSH BOLTS HAS NO DOOR KNOBS OR SURFACE-MOUNTED HARDWARE. (CBC 1010.2.4(4)) 14. MANUALLY OPERATED FLUSH BOLTS OR SURFACE BOLTS ARE PERMITTED WHERE A PAIR OF DOORS SERVES AN OCCUPANT LOAD OF LESS THAN 50 PERSONS IN A GROUP B, F OR S OCCUPANCY. MANUALLY OPERATED EDGE-OR SURFACE-MOUNTED BOLTS ARE PERMITTED THE INACTIVE LEAF. THE INACTIVE LEAF SHALL CONTAIN NO DOOR KNOBS, PANIC BARS OR SIMILAR OPERATING HARDWARE. (CBC 1010.2.4(4)) 15. PANIC & FIRE HARDWARE, WHEN INSTALLED, SHALL COMPLY WITH THE REQUIREMENTS OF CBC 1010.2.9 AS FOLLOWING: A.THE ACTUATING PORTION OF THE RELEASING DEVICE SHALL EXTEND AT LEAST ONE HALF OF THE LEAF WIDTH. B.THE MAXIMUM UNLATCHING FORCE SHALL NOT EXCEED 15 POUNDS (67N) 16. EXIT DOOR HARDWARE SHALL BE OF AN APPROVED TYPE AND TESTED IN ACCORDANCE WITH PROCEDURES ESTABLISHED IN CBC SECTION 715 AND CBC CHAPTER 11B. 17. THRESHOLD HEIGHT AT DOOR WAYS SHALL BE 1/2" HIGH MAXIMUM (CBC 11B-404.2.5). CHANGES IN LEVEL AT DOORWAYS BETWEEN 1/4" AND 1/2" SHALL BE BEVELED WITH SLOPE NO STEEPER THAN 1:2. (CBC 11B-303.3). 1. THE USE OF A CARD READER WILL NOT DELAY EGRESS OF OCCUPANTS LEAVING THE BUILDING. ACCESS- CONTROLLED EGRESS DOORS SHALL FULLY COMPLY WITH CBC 1010.2.11. 2. THE CONTRACTOR SHALL VERIFY AND COORDINATE ELECTRICAL AND SECURITY REQUIREMENTS AT CARD READERS. TENANT'S SECURITY VENDOR SHALL PROVIDE ALL CARD READER EQUIPMENT AND WIRING. CONDUITS AND BOXES SHALL BE PROVIDED BY GENERAL CONTRACTOR. THIS WORK SHALL BE COORDINATED BETWEEN CONTRACTOR AND TENANT'S SECURITY VENDOR. HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 GENERAL NOTES IA-G1 MCGUFF AB/CD ORANGE COUNTY FIRE AUTHORITY CAL GREEN NOTES GENERAL NOTES BIDDING SUBMITTALS DEMOLITION PATCHING & PREPPING FRAMING & DRYWALL DOOR & WINDOW FRAMES GLASS & GLAZING SYSTEMS DOORS DOOR HARDWARE ACCESS CONTROL NONE NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1. IF ANY OUTLETS CANNOT BE INSTALLED AS NOTED OR AS SHOWN ON PLANS DUE TO CONFLICTS WITH STRUCTURAL, MECHANICAL OR ELECTRICAL CONDITIONS, CLARIFY WITH HENDY BEFORE PROCEEDING WITH OUTLETS IN QUESTION OR RELATED OUTLETS IN AREA. 2. ARCHITECTURAL DRAWINGS GOVERN OUTLET LOCATIONS. VERIFY ANY DISCREPANCIES WITH HENDY. 3. CONTRACTOR TO REFER TO ELECTRICAL ENGINEERING DRAWINGS FOR CONDUIT SIZE & DEVICE SPECIFICATIONS, NO DEVICE OR CONDUIT SUBSTITUTIONS OR SIZE REDUCTIONS ARE ACCEPTABLE. 4. FOR CIRCUITING INFORMATION AND PULL BOX LOCATIONS, REFER TO ELECTRICAL ENGINEERING DRAWINGS. 5. ALL NEW CIRCUITS SHALL BE LABELED ON THE PROPER BUILDING ELECTRICAL PANEL DIRECTORIES. 6. PROVIDE ELECTRICAL REQUIREMENTS AS NEEDED FOR MECHANICAL AND PLUMBING EQUIPMENT SEE ENGINEERING DRAWINGS. 7. NON-DIMENSIONED OUTLETS SHALL BE LOCATED AT THE NEAREST STUD. ALL OUTLET DIMENSIONS SHALL BE CENTERLINE U.N.O. ALL OUTLET HEIGHTS NOTED ARE TO THE CENTERLINE OF THE RECEPTACLE, U.N.O. (SEE TYPICAL POWER AND COMMUNICATION LOCATIONS DIAGRAM). 8. WHERE OUTLETS ARE GROUPED TOGETHER, THEY SHALL BE NO MORE THAN 2 INCHES APART. GANG WITH COMMON MOUNTING BRACKET AND/OR FACEPLATE WHENEVER POSSIBLE. 9. PROVIDE CODE REQUIRED PROTECTION AT ALL OUTLETS AND SWITCHES LOCATED IN RATED PARTITIONS. 10. ALL WALL OUTLETS LOCATED IN PRIVATE OFFICES & CONFERENCE ROOMS SHALL HAVE SOUND PADS, SEE TYPICAL WALL OUTLET SPACING DIAGRAM. 11. MARK LOCATIONS OF ALL FLOOR MOUNTED RECEPTACLES AND REVIEW WITH HENDY PRIOR TO PROCEEDING WITH CORING/TRENCHING. 12. SCHEDULE THE CORING OF ANY FLOOR OUTLETS WITH LANDLORD TO PREVENT DISTURBANCE OR DAMAGE TO OTHER TENANT SPACES. 13. CONTRACTOR TO VERIFY WITH LANDLORD IF X-RAY IS REQUIRED PRIOR TO CORE DRILLING. 14. ALL CONDUITS INSTALLED FROM A FLOOR POKE THROUGH FOR VOICE/DATA CABLING SHALL BE RUN TO 6" ABOVE THE SUSPENDED CEILING AT THE NEAREST WALL/COLUMN IN THE DIRECTION OF THE APPROPRIATE MDF/IDF ROOM EXCEPT AS WHERE IMPOSSIBLE DUE TO CEILING RESTRICTIONS/BLOCKAGES. 15. PROVIDE CONDUITS OVER HARD LID CEILING & THRU-RATED WALLS FOR TENANT CABLING, LOCATIONS & SIZES SHALL BE VERIFIED WITH ELECTRICAL ENGINEERING DRAWINGS & TENANT CABLING INSTALLER. 16. CONDUIT ABOVE CEILING SHALL BE SELF-SUPPORTED AND HELD TIGHT TO STRUCTURE A MINIMUM OF 6" ABOVE GRID, COORDINATE WITH LIGHT FIXTURE AND EQUIPMENT REQUIRED CLEARANCES. 17. GENERAL CONTRACTOR SHALL COORDINATE WORK WITH TENANT'S CABLING CONTRACTORS. 18. CABLING SHALL BE PLENUM RATED AND SUPPORTED INDEPENDENT OF THE SUSPENDED CEILING. ALL CABLING SHALL BE PROVIDED AND INSTALLED BY TENANT'S VENDOR. 19. WHERE ELECTRICAL WORK IS SPECIFIED IN CONJUNCTION W ITH MILLWORK, ALL OUTLETS, CONDUITS ND FIXTURES SHALL BE PROVIDED BY GENERAL CONTRACTOR. CUT OUTS FOR SWITCHES, OUTLETS, ETC. SHALL BE PROVIDED BY THE MILLWORK CONTRACTOR AND SHALL BE COORDINATED WITH THE ELECTRICAL CONTRACTOR, U.N.O. 20. FURNITURE SYSTEMS SHALL BE SUPPLIED AND INSTALLED BY TENANT'S VENDOR. ELECTRICAL CONTRACTOR SHALL MAKE FINAL HARDWIRE CONNECTION AND IS RESPONSIBLE FOR ALL REQUIRED PERMITS/INSPECTIONS. 21. ISOLATED GROUND RECEPTACLE SHALL BE ORANGE WITH BUILDING STANDARD COVER PLATES. 22. TELEPHONE DATA CONTRACTOR SHALL COORDINATE DEVICE LOCATION WITH HENDY PRIOR TO INSTALLATION. 1. REFER TO IA-9.1 SHEET FOR RESTROOM PLUMBING REQUIREMENTS. 2. REFER TO MILLWORK ELEVATIONS FOR EXACT PLUMBING LOCATIONS. 3. KITCHEN SINKS SHALL HAVE A LEVER, PUSH TYPE OR ELECTRONICALLY OPERATED FAUCETS, WITH A 5 LBS. MAXIMUM OPENING FORCE. SELF CLOSING FAUCETS SHALL REMAIN OPEN 10 SECONDS MINIMUM. 1. ALL EQUIPMENT IN PLENUM SHALL BE LOCATED AWAY FROM GYP. BD. CEILINGS WHENEVER POSSIBLE. NO ACCESS HATCHES IN GYP. BD. CEILING WITHOUT PRIOR APPROVAL BY ARCHITECT. ACCESS HATCHES SHALL BE A TRIMLESS TYPE. SUBMIT CUT SHEET FOR APPROVAL. 2. PROVIDE AND INSTALL CONDUITS OVER GYP. BD. CEILINGS, THROUGH FULL HEIGHT WALLS AND THROUGH RATED CORRIDORS TO NEAREST ACCESSIBLE CEILING FOR TENANT'S CABLING. CONDUIT SIZE AND LOCATION SHALL BE VERIFIED PRIOR TO INSTALLATION. 3. EXCEPT WHERE RIGID BRACES ARE USED TO LIMIT LATERAL DEFLECTIONS, SPRINKLER HEADS AND OTHER PENETRATIONS SHALL HAVE A 2 INCH OVERSIZE RING SLEEVE OR ADAPTER THROUGH THE CEILING TILE TO ALLOW FOR FREE MOVEMENT OF AT LEAST 1 INCH IN ALL HORIZONTAL DIRECTIONS. ALTERNATIVELY, A SWING JOINT THAT CAN ACCOMMODATE 1 INCH OF CEILING MOVEMENT IN ALL HORIZONTAL DIRECTIONS IS PERMITTED SHALL BE PROVIDED AT THE TOP OF THE SPRINKLER HEAD EXTENSION. 4. INSTALL SUSPENDED CEILING SYSTEMS IN ACCORDANCE WITH CBC CHAPTERS 8 AND 25. 5. SUSPENDED CEILING FRAMING SYSTEMS SHALL BE DESIGNED TO RESIST A LATERAL FORCE OF 20% OF THE WEIGHT OF THE CEILING ASSEMBLY AND ANY LOADS TRIBUTARY TO THE SYSTEM. FOR THE PURPOSES OF DETERMINING THE LATERAL FORCE, A MINIMUM CEILING WEIGHT OF 5 LBS PER SQUARE FOOT SHALL BE USED. WHERE THE CEILING LOADS DO NOT EXCEED 5 LBS PER SQUARE FOOT AND WHERE PARTITIONS ARE NOT CONNECTED TO THE CEILING SYSTEM, THE FOLLOWING BRACING METHOD MAY BE EMPLOYED: a.LATERAL SUPPORT MAY BE PROVIDED BY FOUR WIRES OF MINIMUM NO. 8 GAUGE SPLAYED IN FOUR DIRECTIONS 90 DEGREES APART, AND CONNECTED TO THE MAIN RUNNER WITHIN 2'' OF THE CROSS RUNNER AND TO THE STRUCTURE ABOVE AT AN ANGLE NOT EXCEEDING 45 DEGREES FROM THE PLANE OF THE CEILING. THESE LATERAL SUPPORT POINTS SHALL BE PLACED 12 FT. O.C. IN EACH DIRECTION WITH THE FIRST POINT WITHIN 6 FT. FROM EACH WALL. b.ALLOWANCE SHALL BE MADE FOR LATERAL MOVEMENT OF THE SYSTEM WITH CLEARANCE BETWEEN THE WALL AND THE RUNNERS MAINTAINED AT THE OTHER TWO WALLS. c.VERTICAL SUPPORT SHALL BE PROVIDED AS REQUIRED IN CBC CHAPTER 8 WITH THE ADDED REQUIREMENT THAT DISCONTINUOUS ENDS OF CROSS RUNNERS AND MAIN RUNNERS BE VERTICALLY SUPPORTED WITHIN 8'' OF SUCH DISCONTINUITIES AS MAY OCCUR WHERE THE CEILING IS DISRUPTED BY A WALL. d.A STRUT FASTENED TO THE MAIN RUNNER SHALL EXTEND TO AND FASTENED TO THE STRUCTURAL MEMBERS SUPPORTING THE ROOF OR FLOOR ABOVE AT 12'-0”O.C. IN BOTH DIRECTIONS AND WITHIN 6'-0”FROM WALLS. 6. SUSPENDED ACOUSTICAL CEILING SYSTEM PERIMETER SUPPORTING CLOSURE ANGLE SHALL BE NOT LESS THAN 2 INCHES IN EACH ORTHOGONAL HORIZONTAL DIRECTION. ONE END OF THE CEILING GRID SHALL BE ATTACHED TO THE CLOSURE ANGLE. THE OTHER END IN EACH HORIZONTAL DIRECTION SHALL HAVE A 3/4 INCH CLEARANCE FROM THE WALL AND SHALL REST UPON AND BE FREE TO SLIDE ON A CLOSURE ANGLE. 7. REMOVE AND REPLACE EXISTING CEILING GRID AND TILES AS REQUIRED FOR INSTALLATION OF VAV BOXES, MECHANICAL DUCTS, AND/OR AC UNITS. 1. SPRINKLER HEADS LOCATED IN GYP. BD. CEILINGS SHALL BE FULLY RECESSED AND FACTORY PAINTED TO MATCH CEILING. DISTRIBUTION OF HEADS MUST MEET GOVERNING CODES. 2. SPRINKLER HEADS LOCATED IN SUSPENDED ACOUSTICAL CEILING SYSTEMS SHALL BE SEMI- RECESSED ADJUSTABLE HEADS. DISTRIBUTION OF HEADS MUST MEET GOVERNING CODES. HEADS SHALL BE LOCATED IN CENTER OF CEILING TILE, U.N.O. (EXCEPT AS CODE REQUIRED NEAR SOFFIT). CONFIRM EXISTING SPRINKLER HEAD LOCATIONS. 1. LOCATE RECESSED DOWNLIGHTS, WALL WASHERS, PENDANTS, AND ACCENT LIGHTS IN THE CENTER OF CEILING TILES, U.N.O. 2. LIGHT SENSOR AND LIGHT SWITCH LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION. 3. ALL STROBES SHALL BE LOCATED IN CEILING WHERE ALLOWABLE BY CODE. COLOR SHALL BE APPROVED BY ARCHITECT. 4. THE COLOR AND DESIGN OF LETTERING, ARROWS AND OTHER SYMBOLS ON THE EXIT SIGN SHALL BE IN HIGH CONTRAST WITH THEIR BACKGROUND. WORDS ON THE SIGN SHALL BE IN BLOCK LETTERS 6 INCHES IN HEIGHT WITH A STROKE OF NOT LESS THAN 3/4" INCH. MATCH BUILDING STANDARD, UNLESS NOTED OTHERWISE. 5. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FOOT-CANDLE AT THE WALKING SURFACE LEVEL. 6. THE EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION NOT LESS THAN 90 MINUTES AND SHALL CONSIST OF STORAGE BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR. THE INSTALLATION OF THE EMERGENCY POWER SYSTEM SHALL BE IN ACCORDANCE WITH CBC 2702 AND ILLUMINATE THE FOLLOWING AREAS: A.AISLES AND UNENCLOSED EGRESS STAIRWAYS IN ROOMS AND SPACES THAT REQUIRE TWO OR MORE MEANS OF EGRESS. B.CORRIDORS, EXIT ENCLOSURES AND EXIT PASSAGEWAYS IN BUILDINGS REQUIRED TO HAVE TWO OR MORE EXITS. C.EXTERIOR EGRESS COMPONENTS AT ALL LEVELS OTHER THAN THE LEVEL OF EXIT DISCHARGE UNTIL EXIT DISCHARGE IS ACCOMPLISHED FOR BUILDINGS REQUIRED TO HAVE TWO OR MORE EXITS. D.INTERIOR EXIT DISCHARGE ELEMENTS, AS REQUIRED BY CBC SECTION 1028.1, IN BUILDINGS REQUIRED TO HAVE TWO OR MORE EXITS. E.EXTERIOR LANDINGS FOR EXIT DISCHARGE DOORWAYS IN BUILDINGS REQUIRED TO HAVE TWO OR MORE EXITS. 7. LIGHTING FIXTURES SHALL BE SUPPORTED DIRECTLY BY WIRES TO THE STRUCTURE ABOVE. RECESSED LIGHTING FIXTURES NOT OVER 56 LBS IN WEIGHT AND PENDANT HUNG FIXTURES NOT OVER 20 LBS IN WEIGHT MAY BE SUPPORTED AND ATTACHED DIRECTLY TO THE CEILING SYSTEM RUNNERS BY A POSITIVE ATTACHMENT SUCH AS SCREWS OR BOLTS. THESE REQUIREMENTS ARE BASED ON CURRENT CALIFORNIA BUILDING CODES. OTHER METHODS MAY BE USED PROVIDED THEY ARE SUBSTANTIATED BY DESIGN CALCULATIONS USING THE LOADS SPECIFIED IN CBC CHAPTER 25. 1. ELEVATORS SHALL COMPLY WITH ALL CURRENT CALIFORNIA BUILDING CODE SECTIONS. 2. ELEVATOR SHALL OPERATE AUTOMATICALLY. 3. CAB SHALL BE SELF-LEVELING TO A TOLERANCE OF 1/2" VERTICAL WITH A MAXIMUM GAP BETWEEN PLATFORM SILL AND EDGE OF HOISTWAY OF 1-1/4" HORIZONTAL BETWEEN CAR AND LANDING. 4. CALL BUTTONS SHALL BE CENTERED AT 42 INCHES A.F.F. WITH BUTTONS A MINIMUM OF 3/4" DIA. AND RAISED 1/8". 5. VISUAL INDICATOR TO SHOW EACH CALL REGISTERED AND ANSWERED. 6. VISUAL SIGNALS AT EACH HOISTWAY ENTRANCE SHOWING CAR ARRIVAL AND DIRECTION SHALL BE 2-1/2" AND CENTERLINE AT 6'-0”MINIMUM ABOVE FLOOR AND VISIBLE FROM PROXIMITY OF CALL BUTTON. 7. AUDIBLE INDICATORS ANNOUNCING CAR ARRIVAL AND TRAVEL DIRECTION SHALL SOUND ONCE FOR UP AND TWICE FOR DOWN. 8. BOTH HOISTWAY JAMBS AT EACH FLOOR SHALL HAVE SIGNAGE AT 5'-0" A.F.F. INDICATING FLOOR NUMBER IN RAISED CHARACTERS THAT ARE MINIMUM 2 INCHES HIGH ON CONTRASTING BACKGROUND. PROVIDE 2 INCHES DIA. FIVE POINT STAR TO LEFT OF CHARACTER ON MAIN ENTRY LEVEL. BRAILLE SHALL BE PLACED BELOW CORRESPONDING CHARACTERS. 9. AUTOMATIC DOORS SHALL BE MINIMUM 36" WIDE. 10. CAR SIZE SHALL BE A MINIMUM OF 80”X 54”FOR CENTER OPENING DOORS AND 68”X 54”FOR SIDE-SLIDE OPENING DOORS. 11. CAR CONTROL BUTTONS SHALL BE 48 INCHES A.F.F. FOR FRONT APPROACH OR 54 INCHES A.F.F. FOR SIDE APPROACH WITH EMERGENCY CONTROLS NO LOWER THAN 35" A.F.F. AND ADJACENT TO OR IN BOTTOM OF BUTTON PANEL. 12. EMERGENCY TWO-WAY COMMUNICATION SYSTEM SHALL BE NO MORE THAN 48 INCHES A.F.F. WITH THE HANDSET CORD A MINIMUM OF 29" IN LENGTH. EMERGENCY INTERCOMMUNICATION SHALL NOT REQUIRE VOICE COMMUNICATION. 13. HANDRAIL SHALL BE LOCATED ON ONE WALL, PREFERABLY REAR MOUNTED, AT 32”A.F.F. AND 1-1/2”FROM WALL. 14. DOOR REOPENING DEVICE SHALL BE ACTIVATED WHEN OBSTRUCTION IS SENSED BETWEEN 5"-29" ABOVE THE FLOOR WITHOUT CONTACT AND REMAIN EFFECTIVE FOR A MINIMUM OF 20 SECONDS. 15. DOOR DELAY TIME SHALL BE NOT LESS THAN CALCULATED BY T=D/(1.5 FT/S) WHERE “T”IS TIME IN SECONDS AND “D”IS THE DISTANCE FROM A POINT IN THE LOBBY OR LANDING AREA 60 INCHES DIRECTLY IN FRONT OF THE FARTHEST CALL BUTTON CONTROLLING THE CAR TO CENTERLINE OF ITS HOISTWAY DOOR. 16. MINIMUM ACCEPTABLE TIME FOR THE DOORS TO REMAIN FULL OPEN IS NOT LESS THAN FIVE SECONDS. 17. MINIMUM ILLUMINATION REQUIRED AT CAR CONTROLS THRESHOLD AND LANDING WHEN CAR AND LANDING DOORS ARE OPEN IS 5 FOOTCANDLES. 18. PASSENGER ELEVATOR CAR CONTROL BUTTON SHALL BE ILLUMINATED, HAVE SQUARE SHOULDERS, BE MINIMUM 3/4" IN DIMENSION AND RAISED 1/8". 19. CONTROL BUTTONS SHALL BE DESIGNATED BY 5/8" MINIMUM RAISED CHARACTERS AND STANDARD SYMBOL IMMEDIATELY TO THE LEFT OF THE CONTROL BUTTON. GRADE 2 BRAILLE SHALL BE LOCATED IMMEDIATELY BELOW THE CHARACTER OR SYMBOL. 1. PROVIDE HVAC DISTRIBUTION TO ACCOMMODATE PROPOSED LAYOUT, PEOPLE & EQUIPMENT LOADS AS REQUIRED. 2. VERIFY ALL THERMOSTAT LOCATIONS PRIOR TO INSTALLATION, LOCATIONS SHALL NOT CONFLICT WITH TENANT'S FURNITURE. 3. PROVIDE SEPARATE ZONES WITH THERMOSTATS IN ALL CONFERENCE ROOMS SEATING MORE THAN 6 PEOPLE AND ALL ROOMS WITH EXTERIOR GLAZING ON TWO SIDES. 4. PROVIDE A DEDICATED 24/7 HVAC UNIT IN IDF ROOM. REFER TO MECHANICAL ENGINEERING PLANS FOR MORE INFORMATION. HVAC UNIT SHALL BE OUTSIDE OF ROOM & DUCTED IN. 5. PROVIDE FIRE DAMPERS AT PENETRATIONS TO ALL FIRE RATED PARTITIONS. 6. PROVIDE SOUND BOOTS ON ALL RETURN AIR DUCTS IN FULL HEIGHT WALLS. 7. ALL SUPPLY & RETURN AIR DIFFUSERS SHALL MATCH BUILDING STANDARD. 8. PROVIDE LINEAR DIFFUSERS IN GYPSUM BOARD LOCATIONS. ALL LINEAR DIFFUSERS SHALL BE TRIMLESS TYPE. PROVIDE CUT SHEET FOR REVIEW. 9. WHERE EXPOSED CEILINGS OCCUR, EXISTING VAV BOXES SHALL BE RELOCATED TO NEAREST SUSPENDED ACOUSTICAL CEILING AREA. 1. ADHESIVES, GENERAL: DO NOT USE ADHESIVES THAT CONTAIN UREA FORMALDEHYDE. 2. WOOD GLUE: PROVIDE ALIPHATIC-RESIN, POLYURETHANE, OR RESORCINOL WOOD GLUE RECOMMENDED BY MANUFACTURER FOR GENERAL CARPENTRY USE. VOC CONTENT SHALL NOT EXCEED 30 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24). 3. MULTIPURPOSE CONSTRUCTION ADHESIVE: PROVIDE FORMULATION COMPLYING WITH ASTM D3498 THAT IS RECOMMENDED FOR INDICATED USE BY ADHESIVE MANUFACTURER. VOC CONTENT SHALL NOT EXCEED 70 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24). 4. CONTACT ADHESIVE: PROVIDE PRODUCT RECOMMENDED FOR INDICATED USE BY MANUFACTURER. VOC CONTENT SHALL NOT EXCEED 250 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24). 5. VOC CONTENT OF INTERIOR SEALANTS; PROVIDE SEALANTS AND SEALANT PRIMERS FOR USE INSIDE THE WEATHERPROOFING SYSTEM THAT COMPLY WITH THE FOLLOWING LIMITS FOR VOC CONTENT WHEN CALCULATED ACCORDING TO CFR 40 59, SUBPART D (EPA METHOD 24): A. ARCHITECTURAL SEALANTS: VOC LIMIT NOT MORE THAN 250 G/L. B. SEALANT PRIMERS FOR NON-POROUS SUBSTRATES: NOT MORE 250 G/L. C. SEALANT PRIMERS FOR POROUS SUBSTRATES: NOT MORE THAN 775 G/L. 1. NO FINISH SUBSTITUTIONS MAY BE MADE WITHOUT PRIOR W RITTEN AUTHORIZATION BY HENDY. 2. ALL FINISHES SHALL BE APPLIED IN STRICT ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS, UNLESS NOTED OTHERWISE, AND SHALL CONFORM TO CHAPTER 8 OF THE CALIFORNIA BUILDING CODE. 3. APPLICATION OF CONTROLLED INTERIOR FINISHES SHALL BE IN ACCORDANCE WITH SECTIONS 803 AND 804 OF THE CALIFORNIA BUILDING CODE. 4. MAXIMUM FLAME SPREAD CLASSIFICATION OF FINISH MATERIALS USED ON INTERIOR WALLS AND CEILINGS SHALL NOT EXCEED THAT SET FORTH IN TABLE 803.9 OF THE CALIFORNIA BUILDING CODE. 5. SMOKE DENSITY OF MATERIALS SHALL BE NO GREATER THAN 450 WHEN TESTED IN ACCORDANCE WITH SECTION 803 OF THE CALIFORNIA BUILDING CODE. 1. FIELD VERIFY EXISTING CONDITION OF FLOORS RECEIVING FINISHES. ALL FLOORS SHALL BE CLEAN, DRY, FREE OF DUST, GREASE, WAX, CURING AGENTS, EXCESSIVE ALKALINITY, PAINT, OLD ADHESIVE AND ANY FOREIGN SUBSTANCE THAT WOULD PROHIBIT PROPER BONDING OF ANY FLOOR COVERING MATERIAL. CONTRACTOR SHALL INCLUDE ALL REQUIRED FLOOR PREPARATION IN BID. PROVIDE PRICE TO FLOAT FLOOR WHERE NECESSARY TO ACHIEVE TOLERANCE OF 1/4'' MAX. IN 10'-0'' SPAN. 2. PREPARE ALL FLOORS TO RECEIVE FINISHES. PROVIDE CALCIUM CHLORIDE TESTING IN SEVERAL AREAS OF TENANT FLOOR AREA AND PROVIDE TEST RESULTS TO HENDY. 3. ALL CONCRETE SUBFLOORS SHALL BE TREATED FOR MOISTURE PRIOR TO INSTALLATION OF ANY FLOOR COVERING. RATINGS SHALL BE IN ACCORDANCE WITH THOSE AS CONSIDERED ACCEPTABLE BY THE MANUFACTURER FOR THE SPECIFIED PRODUCTS. PROVIDE CORRECTIVE MEASURES AT SUBFLOORS EXCEEDING THESE MOISTURE RATINGS. 4. SUBMIT SEAMING DIAGRAM WITH FLOORING SUBMITTAL. 5. FLOORING SHALL EXTEND TO BACK WALL WHERE ACCESSIBLE SINK CABINETS OCCUR. 6. FLOORING SHALL MEET ALL CURRENT NON-SLIP STANDARDS AND APPLICABLE CODES AND/OR AUTHORITY'S REQUIREMENTS. PROVIDE NON-SLIP COATINGS AS NECESSARY TO MEET THESE REQUIREMENTS. 7. AFTER CLEANING, THE FLOORING CONTRACTOR SHALL PROVIDE (2) APPLICATIONS OF AN APPROVED NON-SLIP WAX TO ALL RESILIENT TILE FLOOR, WHICH SHALL BE THOROUGHLY MACHINE-BUFFED AND IN CONDITION ACCEPTABLE TO HENDY. 8. ALL VINYL COMPOSITION TILES SHALL BE INSTALLED WITH FULL TILE FROM TRANSITION AT DOOR AND FULL TILE FROM WALL PERPENDICULAR TO DOOR, U.N.O. 9. PROVIDE CORK RUBBER FLOOR TILE MADE WITH ADHESIVES AND BINDERS THAT DO NOT CONTAIN UREA-FORMALDEHYDE RESINS. 10. PROVIDE CORK RUBBER FLOOR TILE WATER-RESISTANT ADHESIVE AS RECOMMENDED BY MANUFACTURER TO SUIT CORK RUBBER FLOORING AND SUBSTRATE CONDITIONS INDICATED. USE ADHESIVES THAT HAVE A VOC CONTENT OF NOT MORE THAN 50 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). 11. PROVIDE SHEET VINYL FLOOR COVERING WATER RESISTANT ADHESIVE RECOMMENDED BY MANUFACTURER TO SUIT SUCH MATERIALS AND SUBSTRATE CONDITIONS. USE ADHESIVES THAT HAVE A VOC CONTENT OF NOT MORE THAN 50 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). 12. PROVIDE STATIC-CONTROL ADHESIVE PRODUCT THAT PRODUCES CONDUCTIVE CONTINUITY OF VCT AND ASPHALT TILE FLOOR COVERING SYSTEM WITH VOC CONTENT OF NOT MORE THAN 50 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). 13. FLOAT FLOOR AT TILE TO CARPET TRANSITIONS, RAMP IN DIRECTION OF CARPET. 14. THE MAXIMUM PILE HEIGHT OF CARPET SHALL BE 1/4 INCH. EXPOSED EDGES OF CARPET SHALL BE FASTENED TO FLOOR SURFACES AND HAVE TRIM ALONG THE ENTIRE LENGTH OF THE EXPOSED EDGE. 15. CARPET SHALL BE INSTALLED IN ACCORDANCE WITH GUIDELINES SET FORTH BY THE CARPET AND RUG INSTITUTE'S CURRENT STANDARD FOR INSTALLATION OF COMMERCIAL TEXTILE FLOOR COVERING MATERIALS. ALL SEAMS MUST BE PROPERLY SEALED USING A CONTINUOUS BEAD OF SEAM ADHESIVE LARGE ENOUGH TO COVER THE PRIMARY BACKING, YARN BUNDLES AND SECONDARY BACKING. 16. PROVIDE CARPET TILE AND CUSHION PRODUCTS PER SPECIFICATION THAT COMPLY WITH TESTING AND PRODUCT REQUIREMENTS OF CARPET AND RUG INSTITUTE'S “GREEN LABEL PLUS”PROGRAM. 17. PROVIDE CARPET ADHESIVES THAT ARE WATER RESISTANT, MILDEW RESISTANT, NON-STAINING, TYPE THAT SUIT PRODUCTS AND SUBFLOOR CONDITIONS INDICATED, THAT COMPLIES WITH FLAMMABILITY REQUIREMENTS FOR INSTALLED CARPET AND THAT IS RECOMMENDED BY THE MANUFACTURER. USE CARPET ADHESIVE WITH VOC CONTENT OF NOT MORE THAN 50 G/L L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). 18. ALL CARPET INSTALLATION SHALL BE ACCOMPLISHED BY A FLOOR COVERING FIRM OR INSTALLER CERTIFIED BY THE FCIB, FCICA OR CFI; AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. 19. PROVIDE TRANSITION STRIPS AS SPECIFIED AT ALL FLOORING TRANSITIONS. SUBMIT TRANSITION SAMPLE TO HENDY FOR REVIEW AND COLOR SELECTION. 20. ALL TRANSITIONS AT DOORS TO OCCUR UNDER CENTERLINE OF DOOR IN CLOSED POSITION, U.N.O. TRANSITIONS AT CASED OPENINGS SHALL BE VERIFIED WITH HENDY. 21. INSTALL WALL FINISH FOR THE FULL HEIGHT OF THE PARTITION WITHOUT BASE. THERE SHALL BE NO UNFINISHED GAPS OF GYP. BD. AT THE BASE. 22. PROVIDE MINIMUM 2" WIDE X LENGTH OF STEP WARNING STRIPE IN CONTRASTING COLOR OF COORDINATING FLOORING AT FIRST AND LAST STAIR TREADS AS REQUIRED BY CODE. 1. PAINT AND WALLCOVERING SUBCONTRACTORS SHALL EXAMINE WALLS PRIOR TO FINISH APPLICATION. BEGINNING WORK IMPLIES ACCEPTANCE OF THEIR CONDITION. 2. ALL EXISTING WALLS SHALL BE PAINTED, U.N.O. 3. PAINT AND PRIMERS SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATION FOR THAT PARTICULAR SURFACE. 4. PROVIDE INTERIOR PAINT PRODUCTS THAT COMPLY WITH THE FOLLOWING LIMITS FOR VOC CONTENT WHEN CALCULATED ACCORDING TO 40 CFR 59M SUBPART D (EPA METHOD 24): A.FLAT PAINTS, COATINGS, TOPCOATS, AND PRIMERS: VOC CONTENT < 50 G/L. B.NON-FLAT PAINTS, COATINGS, AND PRIMERS: VOC CONTENT < 150 G/L. C.FLOOR COATINGS: VOC CONTENT < 100 G/L. 5.RESTRICTED COMPONENTS: PAINTS AND COATINGS SHALL NOT CONTAIN ANY OF THE FOLLOWING: ACROLEIN, ACRYLONITRILE, ANTIMONY, BENZENE, BUTYL BENZYL PHTHALATE, CADMIUM, DI (2- ETHYLHEXYL PHTHALATE, DI-N-BUTYL PHTHALATE, DI-N-OCTYL PHTHALATE, 1,2- DICHLOROBENZENE, DIETHYL PHTHALATE, DIMENTHYL PHTHALATE, ETHYLBENZENE, FORMALDEHYDE, HEXAVALENT CHROMIUM, ISOPHORONE, LEAD, MERCURY. METHYL ETHYL KETONE, METHYL ISOBUTYL KETONE, METHYLENE CHLORIDE, NAPHTHALENE, TOLUENE (METHYLBENZENE), 1,1,1-TRICLOROETHANE, VINYL CHLORIDE. 6.ALL PAINTED WALLS SHALL RECEIVE ONE (1) PRIMER COAT AND TWO (2) COATS OF PAINT, U.N.O. PAINT FINISH SHALL HAVE CONSISTENT COVERAGE, FREE OF ROLLER OR BRUSH MARKS. 7.WHERE PAINT COLORS CHANGE, CORNERS SHALL BE CUT-IN AND FREE OF OVERLAP. 8.ALL GYP. BD. CEILINGS AND SOFFITS SHALL HAVE A LEVEL 5 FINISH AND RECEIVE TWO (2) COATS FLAT PAINT OVER (1) COAT PRIMER, U.N.O. 9.PAINT FINISH ON METAL SURFACES INCLUDING DOOR FRAMES, HANDRAILS, ELEVATOR DOORS, ETC. SHALL BE SEMI-GLOSS, U.N.O. 10.ALL METAL ACCESS DOORS SHALL BE PAINTED TO MATCH ADJACENT WALL OR CEILING FINISH. 11.SUBMIT SEAMING MOCK-UP SAMPLES ON GYP. BD. OF ALL SPECIFIED WALLCOVERINGS TO HENDY FOR APPROVAL PRIOR TO PLACEMENT OF ORDER. 12.ALL SURFACES RECEIVING WALLCOVERING SHALL BE PROPERLY PREPARED PER MANUFACTURER'S SPECIFICATIONS. PRIMER AND ADHESIVE SHALL BE FROM SAME MANUFACTURER OR OTHER APPROVED/ COMPATIBLE PRODUCTS. 13.PROVIDE WALLCOVERING ADHESIVE THAT IS MILDEW RESISTANT AND NON-STAINING FOR USE WITH SPECIFIC WALLCOVERING AND SUBSTRATE APPLICATION, AS RECOMMENDED IN WRITING BY WALLCOVERING MANUFACTURER. USE WALLCOVERING ADHESIVE WITH VOC CONTENT OF NOT MORE THAN 50 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). 14.COORDINATE WALLCOVERING INSTALLATION IN OR ON MILLWORK WITH SUB-CONTRACTORS. 15.WALLCOVERING SHALL BE HUNG IN SEQUENCE AND FROM SAME DYE LOT. 16.POLYOLEFIN WALLCOVERING SHALL RECEIVE SCOTCH GUARD APPLICATION IF NOT FACTORY APPLIED. 17.INSTALL WALLCOVERING PER MANUFACTURER'S SPECIFICATIONS. WALLCOVERING SHALL BE INSTALLED SMOOTH, WITHOUT WRINKLES, BUBBLES OR LOOSE EDGES. ALL PASTE AND BRUSH MARKS SHALL BE REMOVED. WALL COVERING TERMINATIONS SHALL BE CUT STRAIGHT AND SQUARE. WALLCOVERING AT ALL REVEALS SHALL RETURN INTO REVEAL, U.N.O. 18.INSTALL BASE LENGTHS AS LONG AS POSSIBLE. WRAP BASE AROUND CORNER AND CONTINUE A MIN. OF 6 INCHES BEYOND BEFORE SEAMING OR USE PRE-FORMED CORNER PIECES. 19.COORDINATE THE INSTALLATION OF WALL BASE WITH MILLWORK. OMIT BASE WHERE BUILT-IN CABINETS ARE INDICATED. PROVIDE BASE AT BACK WALL INSIDE ACCESSIBLE SINK CABINET. 1. COMPLY WITH TCNA'S "HANDBOOK FOR CERAMIC, GLASS, AND STONE TILE INSTALLATION" METHODS AND WITH PARTS OF ANSI A108 SERIES" SPECIFICATIONS FOR INSTALLATION OF CERAMIC TILE" THAT RE REFERENCE IN TCNA INSTALLATION METHODS. APPLY TO TYPES OF SETTING AND GROUTING MATERIALS USED. 2. EXAMINE TILE SUBSTRATES, AREAS, AND CONDITIONS FOR COMPLIANCE WITH INSTALLATION TOLERANCES AND OTHER CONDITIONS AFFECTING THE WORK. PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED. FILL CRACKS, HOLES, AND DEPRESSIONS IN CONCRETE SUBSTRATES WITH TROWELABLE LEVELING AND PATCHING COMPOUND SPECIFICALLY RECOMMENDED BY TILE MANUFACTURER. SEE ALSO "PATCHING AND PREPPING" NOTES / IA-G1. 3. WHERE TILE FLOOR SLOPES TO DRAIN, PROVIDE WATERPROOFING OVER REINFORCED MORTAR BED, SLOPE 1/4" PER FOOT MAX TOWARD DRAIN. 4. AT WET WALLS AND AREAS SUCH AS SHOWERS, PROVIDE WATERPROOF MEMBRANE COMPLIANT WITH ANSI A118.10 AND AS RECOMMENDED BY THE MANUFACTURER FOR THE APPLICATION INDICATED. INCLUDE REINFORCEMENT AND ACCESSORIES RECOMMENDED BY THE MANUFACTURER. 5. PROVIDE EXPANSION JOINTS AND OTHER SEALANT-FILLED JOINTS, INCLUDING CONTROL JOINT, CONTRACTION, AND ISOLATION JOINTS. CONFIRM JOINT LOCATIONS WITH HENDY PRIOR TO INSTALLATION. DO NOT SAW-CUT JOINTS AFTER INSTALLING TILES. 6. GROUT JOINTS AT TILES SHALL BE 1/8" MAX., U.N.O. GROUT SHALL BE SEALED WITH AQUAMIX "SEALER'S CHOICE" PER MANUFACTURER'S WRITTEN SPECIFICATIONS. 7. PROVIDE CERAMIC TILE ADHESIVE CONTAINING VOC CONTENT OF NOT MORE THAN 50 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). 8. PROVIDE CERAMIC TILE SETTING GROUTING MATERIALS THAT ARE CHEMICAL RESISTANT, WATER- CLEANABLE, TILE-SETTING AND GROUTING EPOXY COMPLIANT WITH ANSI A118.3, WITH A VOC CONTENT OF NOT MORE THAN 65 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). 9. ON COMPLETION OF PLACEMENT AND GROUTING, CLEAN ALL CERAMIC TILE SURFACES SO THEY ARE FREE OF FOREIGN MATTER. 1. FABRICATE CABINETS AND COUNTERTOPS WITH WOOD AND WOOD-BASED PRODUCTS PRODUCED FROM NOT LESS THAN 70% OF WOOD OBTAINED FROM FORESTS CERTIFIED BY AN FSC-ACCREDITED CERTIFICATION BODY TO COMPLY WITH FSC STD-01-001, FSC PRINCIPLES AND CRITERIA FOR FOREST STEWARDSHIP. 2. REVIEW OF SHOP DRAWINGS SHALL BE GENERAL AND/OR FOR AESTHETIC INTERPRETATION, AND EXCEPT WHERE OTHERWISE INDICATED, SHALL NOT BE CONSTRUED AS PERMITTING ANY DEPARTURE FROM CONTRACT OR LEASE REQUIREMENT, RELIEVING THE CONTRACTOR OF RESPONSIBILITY FOR ANY ERROR IN DETAILS OR INSTRUCTIONS PREVIOUSLY FURNISHED BY HENDY. THE CONTRACTOR SHALL CORRECT ERRORS IN AND OMISSIONS FROM THE WORK WITHOUT ADDITIONAL COST TO THE TENANT WHETHER OR NOT WORK WAS INSTALLED AS PER REVIEWED SHOP DRAWINGS. 3. WOOD VENEER CABINETS SHALL CONFORM TO AWI/WIC STANDARDS FOR PREMIUM GRADE MILLWORK. ALL PLASTIC LAMINATE CABINETS SHALL BE CUSTOM GRADE MILLWORK. 4. PROVIDE WOOD STAIN PRODUCTS THAT COMPLY WITH THE FOLLOWING LIMITS FOR VOC CONTENT WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24): A. CLEAR WOOD FINISHES, VARNISHES: VOC CONTENT NOT MORE THAN 350 G/L. B. CLEAR WOOD FINISHES, LACQUERS: VOC CONTENT NOT MORE THAN 550 G/L. C. STAINS: VOC CONTENT NOT MORE THAN 250 G/L. 5. PROVIDE MANUFACTURED WOOD CASEWORK, INCLUDING COUNTERTOPS, MADE WITH ADHESIVES AND COMPOSITE WOOD PRODUCTS THAT DO NOT CONTAIN UREA FORMALDEHYDE. 6. PROVIDE PARTICLE BOARD COMPLIANT WITH ANSI A208.1, GRADE M-2, MADE WITH BINDER CONTAINING NO UREA-FORMALDEHYDE RESIN. 7. PROVIDE MEDIUM-DENSITY FIBERBOARD: PROVIDE PRODUCTS COMPLIANT WITH ANSI A208.2, GRADE 130, MADE WITH BINDER CONTAINING NO UREA FORMALDEHYDE. 8. PLASTIC LAMINATE ADHESIVE AND SEALANT: PROVIDE SINGLE-COMPONENT, MILDEW RESISTANT, NEUTRAL CURING SILICONE/LATEX SEALANT RECOMMENDED BY PLASTIC PANELING MANUFACTURER AND COMPLIANT WITH REQUIREMENTS DIVISION 07 SECTION “JOINT SEALANTS”. VOC CONTENT SHALL NOT EXCEED 250 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24). 9. PROVIDE VENEER-FACED PANEL PRODUCTS (HARDWOOD PLYWOOD) THAT ARE COMPLIANT WITH HPVA-HP-1, MADE WITH ADHESIVE CONTAINING NO UREA FORMALDEHYDE. 10. MILLWORKER SHALL VERIFY SITE CONDITIONS FOR DELIVERY ACCESS PRIOR TO INSTALLATION. 11. MILLWORKER SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON JOB SITE. ALL DISCREPANCIES BETWEEN HENDY'S DRAWINGS AND EXISTING CONDITIONS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF HENDY FOR CLARIFICATION PRIOR TO THE COMMENCEMENT OF WORK. 12. ALL BUILT-IN PLUMBING FIXTURES, ELECTRICAL AND APPLIANCES SHALL BE SUPPLIED AND INSTALLED BY GENERAL CONTRACTOR. CUT-OUTS SHALL BE PERFORMED BY MILLWORKER. GENERAL CONTRACTOR SHALL SUPPLY INFORMATION AND COORDINATE CLEARANCES AND CUTOUTS WITH MILLWORKER. 13. ALL CABINETS SHALL BE CHECKED FOR PROPER MECHANICAL OPERATION. 14. ALL CABINETRY SHALL BE ATTACHED TO WALLS OR STRUCTURE AS REQUIRED FOR STABLE INSTALLATION AND USE. MILLWORKER SHALL COORDINATE BACKING LOCATIONS WITH GENERAL CONTRACTOR AS REQUIRED TO SUPPORT WALL HUNG CABINETS. 15. ALL PAINTED WOOD SURFACES SHALL BE PROPERLY SEALED, SANDED AND PRIMED TO RECEIVE FINAL FINISH COAT. 16. ALL PLASTIC LAMINATE SHEETS SHALL BE PROPERLY BACKED TO PREVENT WARPAGE OF THE SUBSTRATE. 17. ALL MILLWORK SHALL BE FABRICATED OF MINIMUM 3/4" STOCK MATERIAL. 18. ALL MILLWORK SHALL BE SCRIBED TO WALLS, FLOORS AND/OR CEILING WHERE OCCURS. 19. COUNTERTOP AND BASE CABINET SHALL ALIGN TO OUTSIDE END OF CABINET WHERE NO WALL OCCURS, U.N.O.. ALL EXPOSED FACES OF CABINETRY SHALL BE FINISHED. 20. PROVIDE (3) HINGES ON CABINET DOORS EXCEEDING 14 INCHES IN WIDTH. 21. SUBMIT MIN. (3) THREE EACH WOOD, PAINT AND/OR STAIN SAMPLES AND FINISHES FOR APPROVAL BY HENDY PRIOR TO FABRICATION ON 8" X 8" MINIMUM SAMPLES. 22. ALL WOOD VENEER AND PLASTIC LAMINATE DOOR PANELS SHALL BE VERTICAL GRAINED, UNLESS NOTED OTHERWISE. 23. DOOR AND DRAWER EDGES SHALL BE PLASTIC LAMINATE TO MATCH PLASTIC LAMINATE DOOR OR DRAWER FACE. SELF EDGES ON PLASTIC LAMINATE COUNTERTOPS SHALL MATCH COUNTERTOP. HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 GENERAL NOTES IA-G2 MCGUFF AB/CD POWER & COMMUNICATIONS PLUMBING CEILING FIRE SPRINKLERS LIGHT FIXTURES EXISTING ELEVATORS MECHANICAL DEVICES & DISTRIBUTION SEALANTS & ADHESIVES FINISHES FLOOR FINISHES & TRANSITIONS PAINT & WALL FINISHES TILE FINISHES MILLWORK NONE 1.SIGNAGE IDENTIFYING ROOMS OR BUILDING AREAS SHALL BE LOCATED ON THE WALL NEXT TO THE LATCH SIDE OF THE DOOR MAXIMUM 60 INCHES A.F.F. AND MINIMUM 48”A.F.F. 2.POST INTERNATIONAL SYMBOL OF ACCESSIBILITY ON OR ADJACENT TO ALL DISABLED ACCESSIBLE BUILDING ENTRANCES. SIGNAGE NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 ENG INE CENTERLINE Esc F1 F2 F3F4 F5F6 F7 F8 F9 F10F11 F12 ºª\1!|"@·# $ &¬/% ()=?¡¿23 4567 89' 0 Q WE€R T YU I O P A S DF G HJ KLÑ ZX C VB N M;,:._-><^[` *] +¨´ÇB loqmayúsC ontrol A lt A lt Gr C ontrol ImprPantP et s isB loqD esplPausaInterRePágAvPágIn ic ioIns ertSupr F inB loqNum /- *+Intro1 234 56 7 89F inAvPágIn ic ioRePágIns 0 Supr . NumLock Caps S cr oll LockLocketh CR CR CR CR CR CA CACA CA CACA CA CA CACACA CA CACACA CA CA CA CR CR L L L L L L CR CR CR TENANT: MCGUFF MEDICAL PRODUCTS 3080 HARBOR BLVD SANTA ANA, CA 92704 PHONE NUMBER CONTACT: INTERIOR ARCHITECT: H. HENDY ASSOCIATES 4770 CAMPUS DRIVE, SUITE 100 NEWPORT BEACH, CA 92660 (949) 851-3080 CONTACT: CAROLINA WEIDLER/ DAVID KATAOKA ELECTRICAL ENGINEER: SALAS O'BRIEN 8825 RESEARCH DRIVE IRVINE, CA 92618 (949) 753-1553 CONTACT: VICTOR BECCERRA MECHANICAL ENGINEER: KMA CONSULTING 151 KALMUS DRIVE. STE. C COSTA MESA, CA 92626 (714) 66207366 CONTACT: KEITH MATOI STRUCTURAL ENGINEER: BRANDOW AND JOHNSTON 3300 IRVINE AVENUE, STE. 105 NEWPORT BEACH, CA 92660 (949) 862-8510 CONTACT: RYAN BISHOFF GENERAL CONTRACTOR: KPRS CONSTRUCTION 2850 SATURN STREET BREA, CA 92821 (714) 672-0800 CONTACT: TIM LINDEN PLUMBING ENGINEER: KMA CONSULTING 151 KALMUS DRIVE. STE. C COSTA MESA, CA 92626 (714) 66207366 CONTACT: KEITH MATOI PROJECT SHALL CONFORM TO GOVERNING BUILDING CODE: 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA PLUMBING CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA FIRE CODE 2022 CALIFORNIA ENERGY CODE CITY OF SANTA ANA ORDINANCES & AMENDMENTS. CONSTRUCTION TYPE: TYPE VB NUMBER OF STORIES: 2 SPRINKLERS: FULLY SPRINKLERED, FIRE ALARM SYSTEM OCCUPANCY: B, S-1 PROJECT ADDRESS: 3080 HARBOR BLVD SANTA ANA, CA BUILDING AREA: FIRST FLOOR 23,041 SF SECOND FLOOR 7,301 SF AREA OF CONSTRUCTION: FIRST FLOOR 20,865 SF SECOND FLOOR 7,301 SF TOTAL 28,155 SF PROJECT DESCRIPTION: RENOVATION OF FIRST AND SECOND FLOORS OF EXISTING WAREHOUSE/ OFFICE BUILDING. RENOVATION INCLUDES: CONSTRUCTION OF NEW SINGLE OCCUPANT RESTROOMS; CONSTRUCTION OF NEW GENERATOR ENCLOSURE; CONSTRUCTION OF NEW INTERIOR WALLS, DOORS, AND WINDOWS; INSTALLATION OF NEW ELECTRICAL, PLUMBING AND HVAC SYSTEMS; AND UPGRADE OF EXISTING LIGHTING. NOT TO SCALE GRIDLINE DETAIL NUMBER SHEET NUMBER SECTION NUMBER SHEET NUMBER ELEVATION NUMBER SHEET NUMBER DOOR NUMBER KEYNOTE REVISION LETTER/NUMBER ROOM NAME ROOM NUMBER INSIDE CLEAR DIMENSION CENTER TO CENTER DIMENSION ALIGNMENT SYMBOL ELEVATION DATUM POINT 1 4' - 0" 4' - 0" ℄℄ IA-X.X X IA-X.X X IA-X.X X 101 1 1 OFFICE 858 @ AT ADJ.ADJUSTABLE A.F.F.ABOVE FINISH FLOOR BLDG BUILDING BLDG. STD.BUILDING STANDARD CENTER LINE CLG CEILING CLR CLEAR CPT CARPET COL COLUMN D.F.DRINKING FOUNTAIN DN DOWN DTL DETAIL DW DISHWASHER EA.EACH ELEC ELECTRICAL EQ.EQUAL EXIST EXISTING F.F.FINISH FLOOR F. CLG FINISH CEILING F.D.FLOOR DRAIN F.E.FIRE EXTINGUISHER FEC FIRE EXTINGUISHER CABINET F.S.FIRE SPRINKLER G.D.GARBAGE DISPOSAL GYP. BD.GYPSUM BOARD HR HOUR HT HEIGHT MECH MECHANICAL MICRO MICROWAVE MTL METAL N.I.C.NOT IN CONTRACT N.T.S.NOT TO SCALE O.C.ON CENTER OPP OPPOSITE REF REFRIGERATOR REV REVERSED RM ROOM SIM SIMILAR TYP TYPICAL W/WITH WC WALLCOVERING WH WATER HEATER U.N.O.UNLESS NOTED OTHERWISE VCT VINYL COMPOSITION TILE CL +/-APPROXIMATE DIMENSION TOTAL OFFICE (B OCCUPANCY): 17,160 SF TOTAL WAREHOUSE (S-1 OCCUPANCY): 13, 182 SF PARKING RATIOS: WAREHOUSE: 1 PER 1,000 SF WITH 30% GROSS AREA AS OFFICE OFFICE: 3 PER 1,000 WAREHOUSE 13,182 SF/ 1000 = 14 STALLS REQUIRED 30% OF 13,182 = 3,955 SF 3,955 SF /1000 = 4 STALLS REQUIRED OFFICE 17160 SF - 3,955 SF = 13,195 SF 13.195 X 3 = 40 STALLS REQUIRED 14 + 4 + 40 = 58 STALLS REQUIRED 62 STALLS PROVIDED ACCESSIBLE STALLS REQUIRED: ACCESSIBLE: 3 VAN ACCESIBLE: 1 PROVIDED: ACCESSIBLE: 3 VAN ACCESSIBLE: 1 TOTAL OFFICE (B OCCUPANCY): 17,160 SF TOTAL WAREHOUSE (S-1 OCCUPANCY): 13, 182 SF OCCUPANT LOAD FACTORS OFFICE (B OCCUPANCY): 150 WAREHOUSE (S-1 OCCUPANCY) STORAGE: 4000 DISTRIBUTION: 500 OFFICE (B OCCUPANCY) 17,160 SF /150 = 115 OCCUPANTS WAREHOUSE (S-1 OCCUPANCY) STORAGE: 11,009 SF/ 4000 = 3 OCCUPANTS DISTRIBUTION: 2,173 SF/ 500 = 5 OCCUPANTS TOTAL WAREHOUSE OCCUPANTS: 8 OFFICE (B OCCUPANCY) 115 OCCUPANTS 58 MALE 58 FEMALE MALE FEMALE WATER CLOSETS URINALS LAVATORIES WATER CLOSETS LAVATORIES DRINKING FOUNTAINS 2 1 1 4 2 1 WAREHOUSE (S-1 OCCUPANCY) 8 OCCUPANTS 4 MALE 4 FEMALE MALE FEMALE WATER CLOSETS URINALS LAVATORIES WATER CLOSETS LAVATORIES DRINKING FOUNTAINS 1 - 1 1 1 1 PROVIDED FIXTURES MALE FEMALE WATER CLOSETS URINALS LAVATORIES WATER CLOSETS LAVATORIES DRINKING FOUNTAINS 4 - 4 5 5 2 AREA OF WORK ARCHITECTURAL IA-T TITLE SHEET T-1 LEVEL 1 EXITING PLAN T-2 LEVEL 2 EXITING PLAN T-3 ACCESSIBILITY DETAILS CGN CALIFORNIA GREEN NOTES IA-G1 GENERAL NOTES IA-G2 GENERAL NOTES ST-1D SITE DEMOLITION PLAN ST-1 SITE PLAN ST-2 ENLARGED SITE PLANS AND DETAILS ST-3 ENLARGED PLANS, ELEVATIONS, DETAILS ST-4 ENCLOSURE ELEVATIONS IA-1.1D LEVEL 1 DEMOLITION PLAN IA-1.1 LEVEL 1 PARTITION PLAN IA-1.2D LEVEL 2 DEMOLITION PLAN IA-1.2 LEVEL 2 PARTITION PLAN IA-1.3D ROOF DEMOLITION PLAN IA-1.3 ROOF PLAN IA-2.1D LEVEL 1 DEMOLITION CEILING PLAN IA-2.1 LEVEL 1 REFLECTED CEILING PLAN IA-2.2D LEVEL 2 DEMOLITION CEILING PLAN IA-2.2 LEVEL 2 REFLECTED CEILING PLAN IA-4.1 LEVEL 1 FINISH PLAN IA-5.1 ENLARGED RESTROOM PLAN(S) & ELEVATIONS IA-5.2 ELEVATIONS IA-6.1 WALL SECTIONS & DETAILS IA-7.1 DETAILS IA-8.1 DOOR SCHEDULE & DETAILS ELECTRICAL IE-0.01 ELECTRICAL COVER SHEET IE-0.02 TITLE 24 CALCULATIONS IE-0.03 ELECTRICAL SPECIFICATIONS IE-0.04 ELECTRICAL SPECIFICATIONS IE-0.05 LIGHTING FIXTURE SCHEDULE IE-0.06 MECHANICAL AND PLUMBING EQUIPMENT CONNECTIONS IE-0.07 ELECTRICAL DETAILS IE-0.10 SINGLE LINE DIAGRAM IE-0.11 SHORT CIRCUIT CALCULATION IE-0.20 PANEL SCHEDULES IE-0.21 PANEL SCHEDULES IE-0.22 PANEL SCHEDULES IE-0.30 LIGHTING CONTROLS IE-1.0 ELECTRICAL SITE PLAN IED-1.1 OVERALL FIRST FLOOR POWER AND SIGNAL DEMOLITION PLAN IED-1.2 OVERALL SECOND FLOOR POWER AND SIGNAL DEMOLITION PLAN IED-2.1 OVERALL FIRST FLOOR LIGHTING DEMOLITION PLAN IED-2.2 OVERALL SECOND FLOOR LIGHTING DEMOLITION PLAN IE1.1 OVERALL FIRST FLOOR POWER AND SIGNAL PLAN IE1.2 OVERALL SECOND FLOOR POWER AND SIGNAL PLAN IE1.3 ROOF ELECTRICAL PLAN IE-2.1 OVERALL FIRST FLOOR LIGHTING PLAN IE-2.2 OVERALL SECOND FLOOR LIGHTING PLAN MECHANICAL M-0.1 MECHANICAL LEGEND, NOTES, SCHEDULES AND SHEET INDEX M-0.2 MECHANICAL EQUIPMENT SCHEDULES M-2.1 LEVEL 1 -PARTITION FLOOR MECHANICAL PLAN M-3.1 PARTITION MECHANICAL ROOF PLAN M-5.1 MECHANICAL DETAILS M-5.2 TITLE 24 M-5.3 TITLE 24 HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 TITLE SHEET IA-T MCGUFF AB/CD PROJECT TEAM BUILDING SUMMARY VICINITY MAPSYMBOLS ABBREVIATIONS DRAWING INDEX PARKING CALUCULATION RESTROOM FIXTURE CALUCULATION KEY PLANS LEVEL 1 LEVEL 2 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 PLUMBING P-0.1 PLUMBING LEAD SHEET P-0.2 PLUMBING SCHEDULES P-0.3 PLUMBING SPECIFICATIONS P-2.1 LEVEL 1 -PARTITION FLOOR PLUMBING PLAN P-2.2 LEVEL 2 -PARTITION FLOOR PLUMBING PLAN P-3.1 PARTITION MECHANICAL ROOF PLAN P-4.1 LEVEL 1 -PARTITION FLOOR PLUMBING PLAN P-5.1 PLUMBING SCHEDULES P-5.2 TITLE 24 STRUCTURAL S-1 STRUCTURAL DEFERRED SUBMITTALS 1. FIRE SPRINKLERS 2. RACKING FEC FEC FE C FE C FE C Esc F1 F2 F3 F4 F5 F6 F7 F8F9 F10 F11 F12 ºª \1!|"@·#$ & ¬/ % ( ) = ?¡¿23 4 567 8 9' 0 Q WE€R T Y U I O P A S D F G H J KLÑ ZX C V B N M;,:._->< ^[`*]+¨´Ç B loqm ayús C on tr ol A lt A lt G rC on tr ol ImprPantP e t sisB loqD es plP ausaInterRePágAvPág In icio In se rtS upr F in B loqN um /-*+ Intro 1 2 3 45 6 78 9 F in A vPág In icio R ePág Ins0S upr. N umL ock C aps S c ro ll LockL ock eth CR CR CR CR CR CA CACA CA CA CA CA CA CA CACA CA CACA CA CA CA CA CR CR L L L L L L GARRY AVENUE HA R B O R B L V D . 1 ST-2 .. 5 56 .6 .6 6 2 S T A L L S @ 8 ' - 6 " E A . = 1 7 ' - 0 " 5 6' - 3 " . 1 1 3 4 1 3 ST-2 3 ST-2 41010 10 10 2 2 4 2 3 7 4 ST-2 TYP. 4 ST-2 TYP. 23' - 4" 20 ' - 0 " 20' - 0" 40' - 0" 20' - 0" 20' - 0" 40' - 0" 20 ' - 0 " 20 ' - 0 " 20' - 0" 40' - 0" 20' - 0" 8 8 8 8 8 8 8 9 9 10 10 5 2 NEW CONCRETE CURB TO MATCH EXISTING KEYNOTES 1 NEW CONCRETE PAVING TO MATCH EXISTING2 NEW LANDSCAPING: 55.36 SF3 NEW PAINTED STRIPING5 EXISTING PAINTED STRIPING TO REMAIN6 NEW DETECTABLE WARNINGS4 NEW EXTERIOR ENCLOSURE FOR FUTURE GENERATOR7 1 EXISTING RED PAINTED CURBS WITH "FIRE LANE NO PARKING" TEXT TO REMAIN8 NEW RED PAINTED CURBS WITH "FIRE LANE NO PARKING" TEXT TO MATCH EXISTING9 NEW "NO PARKING FIRE LANE" SIGNAGE PER DETAIL 1/-10 SITE LEGEND EXISTING FIRE LANE TO REMAIN EXISTING FIRE HYDRANT TO REMAIN TOTAL OFFICE (B OCCUPANCY): 17,160 SF TOTAL WAREHOUSE (S-1 OCCUPANCY): 13, 182 SF PARKING RATIOS: WAREHOUSE: 1 PER 1,000 SF WITH 30% GROSS AREA AS OFFICE OFFICE: 3 PER 1,000 WAREHOUSE 13,182 SF/ 1000 = 14 STALLS REQUIRED 30% OF 13,182 = 3,955 SF 3,955 SF /1000 = 4 STALLS REQUIRED OFFICE 17160 SF - 3,955 SF = 13,195 SF 13.195 X 3 = 40 STALLS REQUIRED 14 + 4 + 40 = 58 STALLS REQUIRED 64 STALLS PROVIDED ACCESSIBLE STALLS REQUIRED: ACCESSIBLE: 3 VAN ACCESIBLE: 1 PROVIDED: ACCESSIBLE: 3 VAN ACCESSIBLE: 1 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 SITE PLAN ST-1 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1 PRESCREEN CORRECTIONS 3/24/25 2 PLAN CHECK CORRECTIONS 6/11/25 1 1 1 SCALE 1 1/2" = 1'-0"1NO PARKING SIGNAGE PARKING CALUCULATION 2 2 2 L L L L L L GARRY AVENUE HA R B O R B L V D . 5 4 4 3 3 2 1 4 55 6 6 4 1 EXISTING CONCRETE CURB TO BE SAWCUT AND REMOVED KEYNOTES 1 EXISTING PAVING TO BE SAWCUT AND REMOVED2 EXISTING LANDSCAPING TO REMAIN. PROTECT IN PLACE3 EXISTING PAINTED STRIPING TO BE REMOVED4 EXISTING ACCESSIBLE PARKING SYMBOL TO BE REMOVED5 EXISTING ACCESSIBLE PARKING SIGNAGE TO BE REMOVED6 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 SITE DEMOLITION PLAN ST-1D MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 CA CA 9' - 0 " 5' - 0 " 9' - 0 " 8' - 0 " 9' - 0 " 18' - 0" EQ EQ EQ EQ EQ EQ 6' - 5" 6' - 0 " 3' - 5"3' - 0" SL O P E D N 1 : 1 2 M A X . NO PA R K I N G NO PA R K I N G NEW 6" CONCRETE CURB POLE MOUNTED ACCESIBLE STALL SIGNAGE POLE MOUNTED ACCESIBLE STALL SIGNAGE POLE MOUNTED ACCESIBLE STALL SIGNAGE 6d 6d 6d C C C D D D DETECTABLE WARNING TOWED VEHICLES MAY BE RECLAIMED AT OR BY TELEPHONING SECTION 22507.8 CVC UNAUTHORIZED VEHICLES PARKED IN DESIGNATED SPACES NOT DISPLAYING DISTINGUISHING PLACARDS OR LICENSE PLATES ISSUED FOR PERSONS WITH DISABILITIES MAY BE TOWED AWAY AT OWNERS EXPENSE. 6a 5 4 3 2 1 6d 2 4 3 5 1 6a 6a 6b 6c 6b 6c 6d 6" MIN 3' -0" 3'-0" 6' -8" M I N I M U M 1'-0" DIA. 2" 7" 10 " R = 1" 6' -8" M I N I M U M 1'-0" DIA. 2" PLAN 17" 22 " R = 1" PLAN 4" 3' -0" 18 ' -0" M I N . 1'-0" 2' -0" 2' -0" 9'-0"9'-0" 3'-0" 5'-0" Location: Accessible parking spaces serving a particular building shall be located on the shortest accessible route of travel from adjacent parking to an accessible entrance. In buildings with multiple accessible entrances with adjacent parking, accessible parking spaces shall be dispersed and located closest to the accessible entrances. Parking Space Size: 18' minimum length, 9' minimum width, 5' minimum width access aisle (8' at van spaces) with 12" high NO PARKING white letters Van Spaces: 1:8 minimum ratio, 8'-0" minimum wide access aisle located on the passenger side Arrangement: In each parking area, a bumper or curb shall be provided and located to prevent encroachment of cars over the required width of walkways. Accessible parking spaces shall be so located that persons with disabilities are not compelled to wheel or walk behind parked cars other than their own. Ramps shall not encroach into any accessible parking space or the adjacent access aisle. Slope: 2% maximum in any direction within spaces and access aisles Signage: a. At Parking Spaces: 70 square inch minimum reflectorized sign permanently posted immediately adjacent to and visible from each stall or space, consisting of a profile view of a wheelchair with occupant in white on dark blue background. b. Van Spaces: an additional sign stating "Van-Accessible" mounted below the symbol of accessibility. Maintain 80" height. c. Entrance Sign: 17" x 22" minimum sign at each entrance to off-street parking facilities, or immediately adjacent to and visible from each stall or space. Lettering not less than 1" in height, which clearly and conspicuously states the following: "Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards or license plates issued for persons with disabilities may be towed away at Owner's expense. Towed vehicles may be reclaimed at ___________________________ or by telephoning _____________________." d. Pavement Symbol: 36" square symbol outlining a profile view depicting a wheelchair with occupant in white on blue background. The profile view shall be located so that it is visible to a traffic enforcement officer when a vehicle is properly parked in the space AB O V E P A V E M E N T O R GR A D E MI N . AB O V E P A V E M E N T OR G R A D E MI N . 12" HIGH "NO PARKING" TRAFFIC PAINT -WHITE POLE MOUNTED ACCESSIBLE STALL SIGNAGE ACCESSIBLE PAVEMENT SYMBOL PRECAST CONC. WHEELSTOP 4" WIDE TRAFFIC LINE PAINT -BLUE (TYP.) HEIGHT: 98" MINIMUM VERTICAL CLEARANCE IS PROVIDED AT THE PARKING SPACE AND ALONG AT LEAST ONE VEHICLE ACCESS ROUTE TO SUCH SPACES FROM SITE ENTRANCE(S) AND EXIT(S) ACCESSIBLE RESERVED VAN LINE UP BOTTOM OF SYMBOL WITH END OF PARKING STRIPING TRAFFIC PAINT: BLUE (EQUAL TO COLOR NO. 15090 PER FED. STD. 595B) BACKGROUND W/ WHITE INTERNATIONAL SYMBOL OF ACCESSIBILITY AND 2" WIDE BORDER CENTER LINE OF ACCESSIBLE PARKING SPACE AND SYMBOL (2) 3/4" DIA. x 24" LONG REINFORCING BARS EMBEDDED 18" INTO SUBGRADE W/ TOP FLUSH PAVEMENT 4'-0" LONG PRECAST CONCRETE WHEEL STOP w/ 7/8" DIA. HOLES FOR REINFORCING BARS PAVEMENT SYMBOLB PRECAST WHEELSTOPC B C D VAN ACCESSIBLE SIGN AT VAN STALL(S) ONLY WHITE SYMBOL AND 3/4" HIGH BLOCK LETTERS ON BLUE BACKGROUND SLOPE 1/4" TO DRAIN PAVEMENT OR GRADE AS PER SITE PLAN 2" DIA. GALVANIZED STEEL POST EMBED IN CONCRETE FOOTING REFLECTORIZED PORCELAIN SIGN ON STEEL, BEADED TEXT OR EQUAL. 6a CENTERED AT INTERIOR END OF ACCESSIBLE PARKING STALL,6C INSTALLED IN CONSPICUOUS LOCATIONADJACENT TO ACCESSIBLE PARKING ENTRANCE WHITE LETTERS ON BLUE BACKGROUND EQUAL TO COLOR NO. 15090, FEDERAL STD. 595B, MINIMUM 1" HIGH SECURE SIGN TO POST WITH 3/8" DIA. GALVANIZED MACHINE BOLTS AND STRAPS AT TOP & BOTTOM STALL SIGND ENTRY SIGNE LOCATION PER SITE PLAN MIN.MIN. 8'-0" MIN. AT VAN ACCESSIBLE SPACES MIN. PARKING NO TOWING COMPANY AND PHONE NUMBER SHALL BE INCLUDED DURING FABRICATION OF THE SIGN - OBTAIN INFORMATION FROM OWNER 7 6 5 4 3 2 1 8 53 7 Width:4' minimum, 5' minimum at 1A Ramp Slope:1:12 maximum Landings: transitions from ramps to walks, gutters, road surface shall be flush and free of abrupt changes. 1:20 maximum slope within 4' of the top and bottom of the curb ramp. Flared Sides:1:10 maximum slope Level Landing:full width x 4' minimum deep at top Ramp Finish:surfaces of curb ramps and its flared sides shall be stable, firm, and slip-resistant and shall be of a contrasting finish from the adjacent sidewalk -heavy broom finish w/ 1/4" amplitude Detectable Warnings:required at curb ramps which adjoin a vehicular way a. Location: full width of the curb ramp x 36" deep in the direction of travel located so that the edge nearest the curb line is 6" to 8" from the curb line b. Pattern: raised truncated domes with a diameter of nominal 0.9" at the base tapering to 0.45" at the top, a height of nominal 0.2", and a center-to-center spacing of nominal 2.35" aligned on a square grid. Only approved prefabricated surface treatment detectable warning products shall be installed. c. Contrast: 70% minimum contrast in light reflectance between the detectable warning and an adjoining surface, or the detectable warning shall be "safety yellow" (Color No. 33538 per Fed. Std. 595B). The material used to provide visual contrast shall be an integral part of the detectable warning surface. Diagonal Curb Ramps:If diagonal (corner type) curb ramps have returned curbs or other well-defined edges, such edges shall be parallel to the direction of pedestrian flow. The bottom of diagonal curb ramps shall have 48 inches minimum clear space. If diagonal curb ramps are provided at marked crossings, the 48" clear space shall be within the markings. If diagonal curb ramps have flared sides, they shall also have at least a 24" long segment of straight curb located on each side of the curb ramp and within the marked crossing. 6O 6" PAVING AND BASE C DIAGONAL D SECTIOND 4 7 2 3 8 1 4 4 2 6 5 3 4' - 0" 3' - 0"4' - 0" 7 HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 ENLARGED SITE PLANS AND DETAILS ST-2 MCGUFF AB/CD SCALE 1/4" = 1'-0"1ENLARGED ACCESSIBLE PARKING PLAN SCALE 1/8" = 1'-0"2ACCESSIBLE PARKING STALL SCALE 1/4" = 1'-0"3ACCESSIBLE CURB RAMPS NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 M-5.2 MCGUFF AB/CD TITLE 24 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 8 ST-3 12 ST-3 12 ST-3 11 ST-3 11 ST-3 7 ST-3 7 ST-3 14 ST-3 EQ EQ 8 ST-3 12 ST-3 HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 3/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 ENCLOSURE ELEVATIONS ST-4 MCGUFF AB/CD SCALE 3/8" = 1'-0"4ENCLOSURE ELEVATION -SOUTHSCALE 3/8" = 1'-0"12ENCLOSURE ELEVATION -WESTSCALE 3/8" = 1'-0"16ENCLOSURE ELEVATION -NORTH NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3 4 5 6 300' - 0" 5' - 6 " 3' - 1 1 " 1 2 3ST-5 4 5' - 6 " 300' - 2" 3' - 7 " ST-5 3 C DC.6C.5 5' - 6 " 300' - 0" 2' - 6 " A B 5' - 6 " 2' - 6 " HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/16" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 SIGHT LINES ST-5 MCGUFF AB/CD SCALE 1/16" = 1'-0"1SIGHT LINE 1 -FROM HARBOR BLVD. NO. DESCRIPTION DATE 2 PLAN CHECK CORRECTIONS 6/11/25 SCALE 1/16" = 1'-0"2SIGHT LINE 1A -TOWARDS HARBOR BLVD. SCALE 1/16" = 1'-0"3SIGHT LINE 2 -FROM GARRY AVE. SCALE 1/16" = 1'-0"4SIGHT LINE 2A -TOWARDS GARRY AVE. 2 E NG I NE CENT ERL INE FEC FEC FE C FE C FE C E sc F 1 F 2 F 3 F 4 F 5 F 6 F 7 F 8F 9 F 10 F 11 F 12 ºª\1!|"@·#$ & ¬/% ( )=?¡¿ 23 4 567 8 9' 0 Q WE€R T Y U I O P A S D F G H J KLÑ ZX C V B N M;,:._ ->< ^[`*]+¨´Ç B loqm ay ús C o n tr o l A lt A lt G rC o n tr o l Im prPantP e t s isB loqD e sp lP au saIn te r R eP ág A vP ág In ic io In s er t S u pr F in B loqN u m/-* + In tr o 1 2 3 45 6 78 9 F in A vP ág In ic io R eP ág In s0S u pr. N u mL o ckC a ps S c r oll LockL o ck eth CR CR CR CR CR CR CR L L L L L L FEC CR 1 A B C D C.6 C.5 2 3 4 5 6 317 SF 22 101 LOBBY 15 236 SF 16 101A RECEPTION 15 218 SF 2 102 OFFICE 150 44 SF 1 106 JAN 300 154 SF 2 402 OFFICE 150 144 SF 1 403 OFFICE 150 151 SF 2 404 OFFICE 150 436 SF 3 405 OFFICE 150 295 SF 2 408 OFFICE 150 189 SF 2 107 OFFICE 150 216 SF 2 108 OFFICE 150 1223 SF 9 109 OFFICE 150 247 SF 2 112 OFFICE 150 234 SF 2 113 IT 150 243 SF 2 114 OFFICE 150 229 SF 2 115 OFFICE 150 673 SF 45 118 BREAK ROOM 15 350 SF 24 121 LOBBY 15 218 SF 2 122 OFFICE 150 361 SF 3 124 OFFICE 150 488 SF 33 125 CONF. 15 158 SF 1 307 ELECTRICAL 300 464 SF 1 311 PACKAGING 500 42 SF 1 103 MECH 300 256 SF 2 308 WAREHOUSE OFFICE 150 1576 SF 4 111 RECEIVING 500 45 SF 1 116 DIGITAL PHOTO 100 49 SF 1 123 STORAGE 500 5672 SF 12 127 SHIPPING 500 178 SF 1 303 MAINTENANCE 300 WALK-IN REFRIGERATOR BY OTHERS EXISTING TRASH ENCLOSURE TO REMAIN FUTURE SECURE AREA 4451 SF 9 304C WAREHOUSE 500 ELEVATOR 1 1 2 2 2 15 33 11 2 2 3 2 2 45 3 212 1 9 6 6 75 1 12 12 95 1 1 2 300 SF 1 304D FRIDGE 300 1 28 6 12 X .15 = 1.8" REQUIRED 32" PROVIDED 96 X .15 = 14.4" REQUIRED 72" PROVIDED 75 X .15 = 11.25" REQUIRED 32" PROVIDED 6 X .15 = .9" REQUIRED 32" PROVIDED 28 X .15 = 4.2" REQUIRED 32" PROVIDED A A A A B A A 84 ' - 6 " P A T H O F T R A V E L 2 COMMON PATH OF TRAVEL = 93'-0" MA X I M U M P A T H O F T R A V E L = 1 4 3 ' - 2 " M A X I M U M P A T H O F T R A VE L = 1 9 0 ' - 6 " PH PH PH PH 1.IN SPRINKLERED BUILDINGS, MAXIMUM COMMON PATH OF EGRESS TRAVEL SHALL NOT EXCEED (CBC TABLE 1006.2.1): A-3 = 75'-0" B = 100'-0" S-1 = 100'-0" 2.IN SPRINKLERED BUILDINGS, MAXIMUM EXIT ACCESS TRAVEL DISTANCE ALLOWED (CBC TABLE 1017.2): A-3 = 250'-0" B = 300'-0" S-1 = 400'-0" CODE ANALYSIS NOTES MAXIMUM EXIT ACCESS TRAVEL DISTANCE MAXIMUM COMMON PATH OF EGRESS TRAVEL DOOR WITH PANIC HARDWARE ILLUMINATED EXIT SIGN, DIRECTIONAL WHERE INDICATED. TIED TO BUILDING LIFE SAFETY OR BATTERY BACKUP. FOR EMERGENCY LIGHTING, REFER TO ELECTRICAL ENGINEERING LIGHTING PLAN. -(E) INDICATES EXISTING AREA NOT IN CONTRACT FIRE EXTINGUISHER CABINET WITH FIRE EXTINGUISHER CARD READER NUMBER OF OCCUPANTS EXITING IN DIRECTION INDICATED LEGEND SQUARE FOOTAGE OCCUPANT LOAD LOAD FACTOR PH AREA 101 Name LF OL X AREA PROVIDE CODE COMPLIANT TACTILE "EXIT" SIGNAGE. SEE DETAIL S-3 PROVIDE CODE COMPLIANT TACTILE "EXIT ROUTE" SIGNAGE. SEE DETAIL SEE DETAIL S-5 KEYNOTES A B /1 T-3 /1 T-3 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 1 EXITING PLAN T-1 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 FEC CR FE C (E ) FEC (E) CR CR CR 1.IN SPRINKLERED BUILDINGS, MAXIMUM COMMON PATH OF EGRESS TRAVEL SHALL NOT EXCEED (CBC TABLE 1006.2.1): A-3 = 75'-0" B = 100'-0" S-1 = 100'-0" 2.IN SPRINKLERED BUILDINGS, MAXIMUM EXIT ACCESS TRAVEL DISTANCE ALLOWED (CBC TABLE 1017.2): A-3 = 250'-0" B = 300'-0" S-1 = 400'-0" CODE ANALYSIS NOTES MAXIMUM EXIT ACCESS TRAVEL DISTANCE MAXIMUM COMMON PATH OF EGRESS TRAVEL DOOR WITH PANIC HARDWARE ILLUMINATED EXIT SIGN, DIRECTIONAL WHERE INDICATED. TIED TO BUILDING LIFE SAFETY OR BATTERY BACKUP. FOR EMERGENCY LIGHTING, REFER TO ELECTRICAL ENGINEERING LIGHTING PLAN. -(E) INDICATES EXISTING AREA NOT IN CONTRACT FIRE EXTINGUISHER CABINET WITH FIRE EXTINGUISHER CARD READER NUMBER OF OCCUPANTS EXITING IN DIRECTION INDICATED LEGEND SQUARE FOOTAGE OCCUPANT LOAD LOAD FACTOR PH AREA 101 Name LF OL X AREA PROVIDE CODE COMPLIANT TACTILE "EXIT" SIGNAGE. SEE DETAIL S-3 PROVIDE CODE COMPLIANT TACTILE "EXIT ROUTE" SIGNAGE. SEE DETAIL SEE DETAIL S-5 KEYNOTES A B /1 T-3 /1 T-3 1 A B C D C.6 C.5 2 3 4 5 6 379 SF 3 201 OFFICE 150 590 SF 4 200 EXECUTIVE OFFICE 150 647 SF 44 202 LOUNGE 15 223 SF 1 204 STORAGE 300 28 SF 1 205 STOR 300 4440 SF 30 206 OPEN OFFICE 150 212 SF 2 207 OFFICE 150 38 SF 210 JAN 26 SF 1 204A STOR 300 OPEN TO BELOW OPEN TO BELOW 3 23 24 1 1 1 1 2 29 29 2958 58 X .2 = 11.6" REQUIRED 49" PROVIDED 29" X .2 = 5.8" REQUIRED 37" PROVIDED 29 X .15 = 4.2" REQUIRED 32" PROVIDED 29 X .15 = 4.35" REQUIRED 32" PROVIDED 4 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 5 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 LEVEL 2 EXITING PLAN T-2 MCGUFF AB/CD NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 S-1 60 " A . F . F . EXIT 60 " T O FI N I S H E D FL O O R 60 " T O FI N I S H E D FL O O R 60 " T O FI N I S H E D FL O O R 1 1'-0" 1' - 0 " 681 6" 8" 5' -0" A. F . F . PORTABLE ASSISTIVE LISTENING DEVICES AVAILABLE TTY AVAILABLE HERE OCCUPANCY MAXIMUM 1 THROUGH 5 NO ROOF ACCESS STAIR 1 CONFERENCE ROOM 102 ENTRANCE PROVIDE AT EACH GRADE-LEVEL EXTERIOR EXIT DOOR EXIT PROVIDE AT EACH EXIT DOOR THAT LEADS DIRECTLY TO A GRADE-LEVEL EXTERIOR EXIT BY MEANS OF A STAIR OR RAMP WALL MOUNTED SIGN W/ 5/8" HIGH WORDING AND CORRESPONDING GRADE 2 BRAILLE TO BE LOCATED ON LATCH SIDE OF DOOR CLEAR OF DOOR SWING STAIR DOWN EXIT TO EXIT PROVIDE AT EACH EXIT DOOR THROUGH A HORIZONTAL EXIT EXIT ROUTE PROVIDE AT EACH EXIT DOOR LEADING TO AN EXIT ENCLOSURE OR EXIT PASSAGEWAY OR WHERE A VISUAL EXIT SIGN IS REQUIRED TYPICAL MOUNTING LOCATION 5-INCH SIZE BLOCK STYLE LETTERING WITH 3/4-INCH STROKE w/ CORRESPONDING GRADE 2 BRAILLE. CONTRACTOR SHALL OBTAIN ACTUAL NUMBER FROM "MEANS OF EGRESS" PLANS. 1-INCH SIZE BLOCK STYLE LETTERING WITH 1/4-INCH STROKE w/ CORRESPONDING GRADE 2 BRAILLE 1-INCH SIZE BLOCK STYLE LETTERING WITH 1/4-INCH STROKE w/ CORRESPONDING GRADE 2 BRAILLE 5-INCH SIZE BLOCK STYLE LETTERING WITH 3/4-INCH STROKE w/ CORRESPONDING GRADE 2 BRAILLE 1-INCH SIZE BLOCK STYLE LETTERING WITH 1/4-INCH STROKE w/ CORRESPONDING GRADE 2 BRAILLE RESTROOM WALL MOUNTED SIGN MEN DOOR MOUNTED SIGN MEN WOMEN General Requirements: Signs identifying, directing, or giving information about permanent rooms or spaces, or accessible elements and features of a building or site shall comply with the following: Finish and Contrast: characters, symbols and their background shall have an eggshell, matte, or other non-glare finish. Characters and symbols shall contrast with their background, either light characters on a dark background or dark characters on a light background. Proportions: characters on signs shall have a width-to-height ratio of 3:5 and 1:1 and a strok width-to height-ration of between 1:5 and 1:10. Character Height: characters and numerals on signs shall be sided accodring to the viewing distance from which they are to be read. The minimum height is measured using an uppercase X. Lowercase characters are permitted. For signs suspended or projected above the finish floor, the minimum character height shall be 3". Raised Characters and Pictorial Symbol Signs: when raised characters are required or when pictorial symbols are used on such signs, they shall conform to the following requirement: • Character Type: raised 1/32" minimum, sans serif uppercase accompanied by Contracted Grade 2 Braille • Character Size: 5/8" minimum to 2" maximum high • Pictorial Symbols: pictorial symbol signs shall be accompanied by the verbal description placed directly below the pictorial. The outside dimension of the pictorial field shall be a minimum of 6" in height. • Character Placement: characters and Braille shall be in a horizontal format. Braille shall be placed a minimum of 3/8" and a maximum of 1/2" directly below the tactile characters; flush or centered. When tactile text is multi-lined, all Braille shall be placed together below all lines of tactile text. Braille: Contracted Grade 2 Braille shall accompany all wall-mounted signage. Dots shall be 1/10" on centers in each cell with a 2/10" space between cells. Dots shall be raised a minimum of 1/40" above the background. Braille dots shall be domed or rounded. Mounting: • Location: signs shall be installed on the wall adjacent to the latch outside of the door. Where there is no wall space on the latch side, including at double leaf doors, signs shall be placed on the nearest wall, preferablly on the right. Mounting location shall be determined so that a person may approach within 3: of signage without encountering protruding objects or standing within the swing of the door. • Height: 60" above the finish floor to the centerline of the sign. Symbols of Accessibility: shall be the International Symbol of Accessibility, the color of the symbol shall consist of a white figure on a blue background. The blue shall be equal to Color No. 15090 in Federal Standard 595B. Entrance Signs: all building entraces that are accessible to and usable by persons with disabilities shall be identified with a minimum of on International Symbol of Accessibility Accessible Route Signs: additional directional signs, utilizing the symbol, at junctions where the accessible route of travel diverges from the regular circulation path, to be visible to persons along approaching pedestrians ways. Signs shall indicate the direction to accessible building entrances and facilities. Text Telephones: where text telephones are provided, the identification symbol shall be the International TTY symbol Volume Control Telephones: where telephones with volume controls are provided, the identification symbol shall be a telephone hand set with radiating sound waves. Assistive Listening Systems: where assistive listening systems are provided, a sign shall be posted in a prominent place indicating the availability of assistive-listening devices. The sign shall include the International Symbol of Access for Hearing Loss and wording that states "Assistive-Listening System Available". Tactile Floor Level Stairway Signs: shall be located at each floor level landing in all enclosed stairways in buildings two or more stories in height to identify the floor level. At exit discharge level, the sign shall include a raised five pointed star located to the left of the identifying floor level. The ouside diameter of the star shall be the same as the height of the raised characters. Interior Sign Mounting: Drywall: adhesively applied, no visible fasteners Glass: adhesively applied with additional blank plastic backing the same size/ color as the sign adhesively applied to the back side of the glass, no visible fasteners. 9". 5' -0" A . F . F . 6" 6" S-2 DIRECTIONAL 6" 3" S-3 EXIT 6" 3" S-4 EXIT EXIT STAIR DOWN 6" 3" S-5 EXIT ROUTE 6" 3" S-6 TO EXIT 1' - 0" 1' - 0 " S-7 STAIR S-8 MAXIMUM CAPACITY 1' - 0" 1' - 0 " 1' - 0 " S-9 RESTROOM -DOOR MOUNTED 9".EQ EQ S-10 RESTROOM -WALL MOUNTED 8" 1" . 1' - 0" 6" S-11 ASSISTIVE -LISTENING 8" 8"6" S-12 VOLUME CONTROL 10" 8" 6" . 1" . S-13 TEXT TELEPHONE 9" 8" 1" RAD. TYP. S-14 ROOM ID 1 2 3 4 5 6 6 5 3 2 BOTTOM OF LIGHT LINE OF CEILING TOP OF LIGHT TE L E / D A T A O U T L E T S EL E C T R I C A L O U T L E T S W A L L S W I T C H E S TH E R M O S T A T S MA N U A L F I R E AL A R M P U L L 5 L B M A X . F O R C E FI R E FI R E A L A R M BE L L H O R N EX T I N G U I S H E R S MARKERBOARDSCA R D R E A D E R S CLEAR FLOOR SPACE:30" X 48" FOR FORWARD OR PARALLEL APPROACH MAXIMUM HEIGHT:48" (FORWARD) OR 54" (PARALLEL) TO HIGHEST OPERABLE PART OF ALL CONTROLS, DISPENSERS, RECEPTACLES, AND OTHER OPERABLE EQUIPMENT MINIMUM HEIGHT:15" (FORWARD AND PARALLEL) TO LOWEST OPERABLE PART. ELECTRICAL AND COMMUNICATION SYSTEM ERCEPTACLES ON WALLS SHALL BE MOUNTED NO LESS THAN 15" ABOVE THE FLOOR. OPERATION:CONTROLS AND OPERATING MECHANISMS SHALL BE OPENABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PNCHING OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 LBS. ELECTRICAL SWITCHES:THE TOP OF THE GRIP OF THE OPERATING HANDLE OF CONTROLS OR SWITCHES, APPLIANCES OR COOLING, HEATING AND VENTILATING EQUIPMENT SHALL BE 48" ABOVE THE FLOOR. ELECTRICAL RECEPTABLE OUTLETS:THE TOP OF ELECTRICAL RECEPTACLE OUTLETS SHALL BE INSTALLED NOT MORE THAN 48" NOR LESS THAN 15" ABOVE THE FLOOR. 6" 15 " M I N . CL 48 " M A X . 6". 48 " M A X . 48 " M A X . 80 " M I N . 6" . 48 " M A X . 36 " M A X . 60" MIN. MIN. CLEAR WIDTH FOR TWO WHEELCHAIRS 32" MIN. 24 " M A X . 36" MIN. WALL (TYP.) MIN. CLEAR WIDTH FOR SINGLE WHEELCHAIR WALL (TYP.)60 " M I N . 60" MIN. MIN. 60" TURNING DIA. FOR WHEELCHAIR 12" MIN.36" MIN.12" MIN. 60 " M I N . 36 " M I N . WALL (TYP.) WALL (TYP.)T-SHAPED SPACE FOR 180- DEGREE TURNS 30" X 48" CLEAR FLOOR SPACE (FRONT APPROACH) SECTION PLAN ELEVATION TO E C L E A R A N C E ACCESSIBLE FOUNTAIN STANDARD FOUNTAIN Minimum Number: in new construction, where only one drinking fountain area is provided on a floor, there shall be a drinking fountain that is accessible to individuals who use wheelchairs and one accessible to those who have difficulty bending or stooping. This can be accomodated by the use of 'hi-low' fountains. Clearances (Forward approach only): a. Fixture Depth: 17" minimum to 19" maximum b. Knee Space: 27" minimum height, 30" minimum width and 8" minimum depth from the front edge c. Toe Clearance: 9" minimum height and 17" minimum depth from the front edge Alcoves: a. Width: 32" minimum b. Depth: 18" minimum to 24" maximum Controls: a. Force: 5 lb. maximum force b. Location: front mounted or side mounted 6" maximum from front edge Spout: a. Location: 3" maximum from front edge to outlet orifice b. Height: 36" maximum to outlet orifice c. Flow: substantially parallel to the front edge of the drinking fountain, 4" minimum high so as to allow the insertion of a cup or glass under the flow of water 1 2 3 4 5 5 4 3 1 2 9" MAX. 6". MIN. 8". 18" MIN. 3" ST A N D A R D H T . F O U N T A I N 39 " T O 4 0 " T O B U B B L E R AC C E S S I B L E F O U N T A I N 36 " M A X . T O B U B B L E R KN E E C L E A R A N C E 27 " M I N . 4'-0" MIN. 18 " M I N . 18" MIN.14-1/8". SOAP DISPENSERSS.C., ND & TOILET PAPER DISPENSER ROBE HOOKS WATER CLOSET URINAL LAVATORY DRINKING FOUNTAIN TOILET PAPER HOLDERS PAPER TOWEL / TRASH RECEPT./ ETC. PAPER TOWEL DISPENSER GRAB BARS MIRRORS SANITARY NAPKIN DISPOSAL SANITARY NAPKIN DISPENSER SEAT COVER DISPENSER FOLDING UTILITY SHELF HAND DRYER URINAL SCREEN SHOWER STALL MI N . 1' - 7 " MA X . 3' - 4 " MA X . 3' - 4 " 2' - 9 " MA X . 3' - 4 " MA X . 3' - 4 " MA X . 3' - 4 " MA X . 2' - 1 0 " MA X . 3' - 4 " MA X . 3' - 4 " MA X . 3' - 4 " MA X . 3' - 4 " MA X . 3' - 4 " MA X . 3' - 4 " MA X . 3' - 4 " +4 0 " M A X . 2' - 0" . +3 3 " MAX. .12" 19 " M A X . 17 " M I N . VALVE AT WIDE SIDE (TYP.) 3' - 8 " M A X . MA X . 1' - 5 " 2' - 0 " 1' - 6 " 3' - 6 " MI N . 2' - 7 " MA X . 2' - 1 0 " 8" MIN. +9 " M I N . MIN. 1' - 6" MI N . 2' - 3 " TO B U B B L E R 3' - 0 " M A X . MI N . 2' - 3 " TO B U B B L E R 3' - 4 " 1' - 6 " 6' - 0 " 2' - 9 " 1 2 1 22 LOBBY OVERHANGING OBSTRUCTIONS:80" MINIMUM CLEAR ABOVE THE WALKING SURFACE PROTRUDING OBJECTS:OBJECTS PROJECTING FROM WALLS WITH THEIR LEADING EDGES BETWEEN 27" AND 80" ABOVE THE FINISHED FLOOR SHALL PROTRUDE NO MORE THAN 4" INTO WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES. FREE-STANDING OBJECTS MOUNTED ON POSTS OR PYLONS MAY OVERHANG 12" MAXIMUM FROM 27" TO 80" ABOVE THE GROUND OR FINISHED FLOOR. PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING SPACE. 80 " M I N I M U M 4" MAX. 27 " AB O V E UP T O 8 0 " ANY AMMOUNT 27 " . OR B E L O W CA N E D E T E C T I O N A R E A FORWARD REACH SIDE REACH SIDE REACH OVER AN OBSTRUCTION FORWARD REACH OVER AN OBSTRUCTION CLEAR FLOOR AREA WHEELCHAIR TURNING RADIUS 60" MIN. 60 " M I N . 48 " M I N . 30" MIN. 1 2 3 2 4 4 1 3 5 5 6 7 8 6 7 8 9 9 9 8 PA T H O F TR A V E L CROSS SLOPE EXTERIOR INTERIOR CONTINUOUS GRADIENTS/ PASSING SPACES:60" X 60" MIN. LEVEL AREA AT 200' MAX. LEVEL AREAS:42" MIN. PLUS DOOR WIDTH AT A DOOR OR GATE THAT SWINGS TOWARD THE WALK, 48" DEEP AND 12" STRIKE CLEARANCE MIN. AT A DOOR OR GATE THAT SWINGS AWAY FROM THE WALK. CHANGES IN LEVEL:1/4" MAX. MAY BE VERTICAL, 1/2" MAX. BEVELED WITH A SLOP NO GREATER THAN 1:2 MAXIMUM SLOPE:1 VERTICAL TO 20 HORIZONTAL (5%) MAX. IN THE DIRECTION OF TRAVEL GRATINGS:1/2" MAX. OPENING IN THE PREDOMINANT DIRECTION OF TRAVEL CROSS SLOPE:1/4" PER FOOR (2%) MAX. SURFACE TEXTURES:SURFACES SHALL BE STABLE, FIRM, AND SLIP RESISTANT AS FOLLOWS: A. SLOPES LESS THAN 6%: SHALL BE A MEDIUM SALTED FINISH OR SIMILAR, 0.6 MIN. COEFFICEINT OF FRICTION MINIMUM WIDTH:48" CONTINUOUS SURFACE:A CONTINUOUS COMMON SURFACE NOT INTERRUPTED BY STEPS OR BY ABRUPT CHANGES IN LEVEL EXCEEDING 1/2" AT 2:1 SLOPE OR 1/4" VERTICAL SURFACE 36" MIN. POLE OR OBSTRUCTION WHERE OCCURS (MIN. 80" VERT. CLEAR) FA C E O F C U R B W H E R E OC C U R S 4'-0" MIN. DIM PER PLAN 4' - 0 " M I N . DO O R O R G A T E MIN. 1' - 0" 24" MIN. LANDINGS:SLOPE SHALL NOT EXCEED 2" IN ANY DIRECTION 3' - 6 " M I N . 60" MIN. 2 4 3 1 2 3 2 4 MINIMUM NUMBER:5% BUT NEVER LESS THAN ONE MUST BE ACCESSIBLE CLEAR FLOOR SPACE:30" X 48" MINIMUM KNEE CLEARANCE: A. HEIGHT: 27" MINIMUM B. WIDTH: 30" MINIMUM C. DEPTH: 19" MINIMUM WORK SURFACES: A. HEIGHT: 28" TO 34" B. LENGTH: 36" MINIMUM LENGTH, WHERE A SINGLE COUNTER CONTAINS MORE THAN ONE TRANSATION STATION, AT LEAST 5%, BUT NEVER LESS THAN ONE, OF EACH TYPE OF STATION SHALL BE LOCATED AT A SECTION OF THE COUNTER. C. LENGTH: 60" MINIMUM LENGTH AT DINING AND BAR COUNTERS 8 7 6 4 5 2 3 1 4 5 2 45 8 1 3 76APLAN SECTIONB C ELEVATION Location: on one side and the back of the accessible toilet Height: 33" above and parallel to the floor except where a tank-type toilet is used which obstructs placement at 33", the grab bar may be as high as 36". Length: a. Side: 42" minimum long, 24" in front of the water closet and 12" maximum from the rear wall b. Back 36" minimum long, 6" maximum from the side wall Grip Size: 1 1/4" to 1 1/2" diameter or equivalent shape Wall Clearance: 1 1/2" Structural Strength: shall meet bending stress, shear stress, shear force, and tensil force of 250 lbs. point load. Stability: grab bars shall not rotate within their fittings. Adjacent Surface: shall be free of any sharp or abrasive elements. Edges shall have a minimum radius of 1/8" MINIMUM 18 GA. STUD AT 16" O.C. ON EACH END OF STEEL PLATE FASTEN GRAB BAR TO BACKING PLACE WITH 1/4" X 2 1/2" COUNTER-SUNK SELF TAPPING S.M.S AND 1/2" DIA. GALV. SLEEVE SPACERS, TYP. ANCHOR INTO STEEL BACKING PLACE (3 EA.) -SNAP FLANGE COVER FOR CONCEALED MOUNTING . 1 1/4" MIN. TO 1 1/2" MAX. DIAMETER 6" X 16 GA. STEEL BACKING PLATE -ATTACH TO 2 STUDS W/ (2) 1/4" DIA X 1" SELF TAPPING S.M.S. AT EA. STUD (MIN.) WALL FINISH PER SCHEDULE/ ELEVATION PROVIDE BACK TO BACK STUDS WHERE BLOCKING IS CONTINUOUS CLR. 1 1/2" 33 " A . F . F . 1 1/2" TANGENTIAL CLEAR ZONE AROUND GRAB BAR, 3" MAXIMUM HORIZONTAL PROJECTION ZONE DIRECTLY BELOW GRAB BAR AND 18" VERTICAL CLEAR ZONE DIRECTLY ABOVE GRAB BAR 1 1/2"1 1/2" (2) #12 S.M.S. AT EA. STUD METAL STUD (TYP.) 6" X 16 GA. MTL. BACKING PLATE . EQ EQ 6" 1/4" DIA. X 2 1/2" COUNTER-SUNK SELF TAPPING S.M.S. AND 1/2" DIA. GALV. SLEEVE SPAVERS, (TYP.). ANCHOR INTO STEEL BACKING PLATE (3 EA.) HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE As indicated 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 ACCESSIBILITY DETAILS T-3 MCGUFF AB/CD SCALE 1" = 1'-0"1ACCESSIBLE SIGNAGE -GENERAL SCALE 3/16" = 1'-0"3CONTROLS AND MECHANISMSSCALE 1/4" = 1'-0"19WHEELCHAIR CLEARANCES SCALE 1/2" = 1'-0"4ACCESSIBLE HI-LOW DRINKING FOUNTAIN SCALE 1/4" = 1'-0"9MOUNTING HEIGHT SCHEDULE SCALE 1/4" = 1'-0"18OVERHANGING OBJECTS SCALE 1/4" = 1'-0"7SPACE AND REACH RANGE SCALE 1/4" = 1'-0"12ACCESSIBLE WALKS AND SIDEWALKS SCALE 1/2" = 1'-0"17FIXED SEATING/ COUNTERS SCALE 3" = 1'-0"11GRAB BAR MOUNTING NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 SLAB-ON-GRADE WHERE OCCURS 1/2" NEOPRENE FILLER EXP JOINT ALL AROUND AT INT CONDITION SLAB OR FINISH GRADE WHERE OCCURS #5 BARS@12" OC EACH WAY T&B FUTURE GENERATOR (7200# MAX OPERATING WEIGHT) 6 " 1'-0" FUTURE ANCHORAGE FOR FUTURE GENERATOR PER PLAN METAL STUD PER PLAN TYP 2" MIN EDGE DISTANCE CONC CURB (WHERE OCCURS) CONC SLAB-ON-GRADE REINF NOT SHOWN FOR CLARITY (6" MIN) SEE ARCH CONT 362T150-54 W/ #10 SMS EA FLANGE EA STUD 3/8" DIA HILTI KWIK HUS-EZ @ 32" OC MAX W/ 2 1/8" NOMINAL EMBED (STAGGERED) MIN 2" CL MITRE JOINT DETAILa CJP CL HSS PER PLAN CL BUTT JOINT DETAILb AT EQUAL HSS SIZES CL HSS PER PLAN MIN 1/4" CAP PL 1/8 W/ SEAM WELD ALL AROUND 1/4 1/4 AT UNEQUAL HSS SIZES 1/4 TYP HSS PER PLAN CJP CL CJP (ALTERNATE) HSS SPLICE DETAIL (OTHER THAN COLUMN)c HSS PER PLAN NOTE: CONTRACTOR SHALL OBTAIN WRITTEN APPROVAL FROM SEOR PRIOR TO FABRICATION WHERE SPLICE LOCATIONS ARE NOT INDICATED ON PLANS/SECTION. 8" 1' - 0" TYP 1 1/2" TYP 1 1/2" 1/4" 1/4 (4) 5/8" DIA ASTM F1554 GR. 36 ANCHORS W/ 8" MIN EMBED 3/4" THK CL COL & FTG COLUMN PER PLAN 3/4" DIA x 0'-3" WELDED STUDS EACH FACE 3" FROM END OF POST TIES PER SCHEDULE PROVIDE 1 1/2 EXTRA TURNS AT TOP & BOTTOM PER SCHEDULE VERT BARS PER SCHEDULE NOTES: 1. VIBRATE CONCRETE FULL DEPTH 2. NOTIFY STRUCTURAL ENGINEER OF RECORD IF GROUND WATER IS ENCOUNTERED. PER SCHEDULE UNO 12" MIN TYPE DIA DEPTH VERT BARS TIES PF1 6" MIN 12" MAX SECTION A-A A A 24"4'-0"(6) #6 #4@6"OC 1' - 8" NEW CONCRETE SLAB ON GRADE PER PLAN 4" MIN CURB BEYOND WHERE OCCURS PER SEE ARCH (OMIT CURB @ COL LEAVE 1/2" GAP BETWEEN COL & CURB, FILL GAP W/BACKER ROD & SEALANT) (4)#4 SLAB DOWEL TOTAL EACH POLE FTG (24" MIN HORIZ LEG) DIA PER SCHED 3" CLR TYP 24". #4 TIES OR #4 SPIRAL TIES @ REQUIRED SPACING 3" CLR. (1)#5 CONT (2)#5 SLAB EDGE BARS PER . (2)@5 CORNER BARS TYP SPLICE LENGTH AT CORNER POST AT SIDE POST NOTE: FOR ADDITIONAL INFORMATION SEE 6 S1.1.3 12 S1.1.2 HSS PER PLAN WALL STUDS PER PLAN HSS PER PLAN BOTTOM TRACK PER STOP BOTTOM TRACK AT POST. ADD TRACK ACNHOR WITHIN 4" OF HSS 11'-0" MAX CURB WHERE OCCURS(SEE ARCH) OVER SLAB PER PLAN TOP OF SLAB BEYOND BOTTOM OF SLAB BEYOND SLAB TURNDOWN 6 S1.1.3 POST FOOTING 13 S1.1.3 14 S1.1.3 2 S1.1.3 (E)SLAB (E) CONT WALL FTG SLAB PER PLAN (E) CONC WALL (2) CONT #4 BARS #4 DOWEL PER 4 S1.1.2 2 '- 6" MIN 2" SEPARATION (E)SLAB (E) CONT WALL FTG METAL STUD WALL PER PLAN SLAB TURNDOWN PER PLAN SLAB PER PLAN POST PER PLAN 3 S1.1.3 (2) CONT #4 BARS #4 DOWEL PER 4 S1.1.2 BOTTOM OF SLAB BEYOND 2 '- 6" MIN 12 S1.1.2 A WEIGHT #400 MAX P1000 BRACE W/ P2815 ADJUSTABLE BRACE FITTING EA END AELEVATION B TRANSFORMER PER ELEC PROVIDE MIN (4) 1/2" THRU BOLTS TO SUPPORT FRAME PER MFR LAYOUT 1 1 BPLAN P1000 BEAM W/ 1/2" BOLT EA END TYP, ADDITIONAL P1000 AS REQUIRED 3' - 0" MAX (2) P1000 W/ 1/2" HILTI KB-TZ2 W/ 3 1/4" EMBED @1'-0"OC (3) MIN P1000 W/ 1/2" HILTI KB-TZ2 W/ 3 1/4" EMBED @1'-0"OC (3) MIN UNISTRUT P1727 FITTING W/ 1/2" BOLTS EXTEND AS REQUIRED FOR FITTING (E) CONC WALL (E) CONC WALL 3' - 0" MAX WEIGHT #400 MAX 16 GA STUDS (3) STUDS MIN AT EA EQUIP WALL PER PLAN P1000 BRACE W/ P2815 ADJUSTABLE BRACE FITTING EA END AELEVATION B TRANSFORMER PER ELEC PROVIDE MIN (4) 1/2" THRU BOLTS TO SUPPORT FRAME PER MFR LAYOUT 1 1 BPLAN P1000 BEAM W/ 1/2" BOLT EA END TYP, ADDITIONAL P1000 AS REQUIRED 3' - 0" MAX (2) P1000 W/ #12 SMS @6"OC (6) MIN SMS P1000 W/ #12 SMS @6"OC (6) MIN SMS TYPICAL TRACK WALL BACKING T&B, PROVIDE MIN 6" DEEP TRACK AT TOP TYPICAL TRACK WALL BACKING, EXTEND BLOCKING AT LEAST ONE BAY EA SIDE OF ATTACHMENT 3' - 0" MAX UNISTRUT P1727 FITTING W/ 1/2" BOLTS EXTEND AS REQUIRED FOR FITTING FINISH PER ARCH POST PER PLAN (2)#10 SMS @12" OCSTUDS PER PLAN 362S150-54 CONT NESTED STUD #10 SMS @8" OC STAGGERED HSS PER PLAN #10 SMS EACH FLAGE EACH STUD METAL STUD WALL PER PLAN STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 As indicated 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 DETAILS S1.1.3 MCGUFF 01/02/25 SCALE: 1" = 1'-0"S1.1.3 TYPICAL ISOLATED EQUIPMENT PAD 1 DETAIL ID: CON-PDCB-01 SCALE: 1" = 1'-0"S1.1.3 BOTTOM TRACK AT SLAB-ON-GRADE 2 DETAIL ID: MST-EXTS-01m SCALE: 1 1/2" = 1'-0"S1.1.3 TYPICAL HSS-TO-HSS CONNECTION DETAIL 4 DETAIL ID: STL-BEAM-12 SCALE: 1 1/2" = 1'-0"S1.1.3 BASEPLATE DETAIL 3 SCALE: 1" = 1'-0"S1.1.3 TYPICAL POLE FOOTING 6 DETAIL ID: CON-POLE-01a SCALE: 1" = 1'-0"S1.1.3 SLAB TO POLE FOOTING DETAIL 10 SCALE: 3/4" = 1'-0"S1.1.3 SLAB TO POLE FOOTING DETAIL 9 SCALE: 1" = 1'-0"S1.1.3 SLAB @ (E) WALL 7 SCALE: 1" = 1'-0"S1.1.3 ENCLOSURE FOOTING @ (E) WALL 8 DETAIL ID: ECON-FTNG-01 SCALE: 1" = 1'-0"S1.1.3 TRANFORMER SUPPORT AT (E) CONC WALL 16 SCALE: 1" = 1'-0"S1.1.3 TRANFORMER SUPPORT AT METAL STUD WALL 12 SCALE: 1 1/2" = 1'-0"S1.1.3 POST TO STUD CONNECTION 13 DETAIL ID: MST-MISC-07 SCALE: 3" = 1'-0"S1.1.3 TOP TRACK SECTION DETAIL 14 DETAIL ID: MST-MISC-08 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, PROJECT BOUNDARIES AND EXISTING CONDITIONS AT THE SITE PRIOR TO COMMENCEMENT OF WORK AND IMMEDIATELY NOTIFY STRUCTURAL ENGINEER OF RECORD (SEOR) AND ARCHITECT OF RECORD (AOR) OF ANY DISCREPANCY. THE CONTRACTOR SHALL CHECK DETAILS AND DIMENSIONS SHOWN ON THE STRUCTURAL DRAWINGS WITH RE LATED REQUIREMENTS ON OTHER CONTRACT DOCUMENTS. 2. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE STRUCTURAL ENGINEER OF RECORD (SEOR) OF ANY CONFLICTS BETWEEN THE STRUCTURAL DRAWINGS AND OTHER CONSTRUCTION DOCUMENTS OR EXISTING CONDITIONS NOT SHOWN OR DIFFERENT THAN THOSE SHOWN ON CONTRACT DOCUMENT PRIOR TO COMMENCEMENT OF WORK. THE CONTRACTOR SHALL NOT ORDER MATERIAL, FABRICATE ELEMENTS, OR CONSTRUCT ANY PORTION OF STRUCTURE THAT IS IN CONFLICT UNTIL RESOLUTION IS MADE. IN THE EVENT OF CONFLICTS, INCONSISTENCIES AND DISCREPANCIES BETWEEN OR AMONG THE CONTRACT DOCUMENTS THE AOR/SEOR DECIDE WHICH OF THE CONFLICTING REQUIREMENTS WILL GOVERN BASED UPON THE MOST STRINGENT OF THE REQUIREMENTS. THE CONTRACTOR SHALL PERFORM THE WORK CONSISTENT WITH THE AOR/SEOR'S DECISION WITHOUT ADJUSTMENT OF THE CONTRACT SUM OR CONTRACT TIME. 3. ALL DIMENSIONS ON STRUCTURAL DRAWINGS SHALL BE CHECKED BY CONTRACTOR AGAINST ARCHITECTURAL DIMENSIONS. WHERE DIMENSIONS ARE UNCLEAR OR OMITTED, REQUEST CLARIFICATION FROM THE STRUCTURAL ENGINEER OF RECORD (SEOR) AND ARCHITECT OF RECORD (AOR). DO NOT SCALE DRAWINGS. UNLESS NOTED OTHERWISE, PLAN DIMENSIONS INDICATE CENTERLINE OF BEAMS AND COLUMNS. LIGHT-FRAMED WALLS ARE DIMENSIONED TO FACE OF STUDS, AND FOOTINGS ARE CENTERED UNDER THE ELEMENTS THEY SUPPORT. ALL DIMENSIONS RELATED TO EXISTING CONDITIONS SHALL BE FIELD VERIFIED BY THE CONTRACTOR PRIOR TO START OF WORK. 4. SEE ARCHITECTURAL DRAWINGS FOR SIZE AND LOCATION OF DOOR AND WINDOW OPENINGS IN STRUCTURAL WALLS; SIZE AND LOCATION OF FLOOR AND ROOF OPENINGS AND SLAB EDGES; SIZE AND LOCATION OF NON- BEARING WALLS AND OPENINGS; SIZE AND LOCATION OF CONCRETE CURBS, SLOPES, DEPRESSIONS, DRAINS, NON-STRUCTURAL PARTITIONS, CHANGES IN LEVEL, CHAMFERS AND REVEALS, INSERTS FOR FINISH SYSTEMS; EXTERIOR WALL FINISHES; STAIR SIZE, LOCATION, FRAMING AND DETAILS, UNLESS DETAILED ON STRUCTURAL DRAWINGS; DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS. 5. PROJECT SPECIFICATIONS SHALL BE A PART OF THE CONTRACT DOCUMENTS. WHERE DISCREPANCIES OCCUR BETWEEN GENERAL NOTES, PLANS, DETAILS AND SPECIFICATIONS, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN. SPECIFIC NOTES AND DETAILS ON DRAWINGS GOVERN OVER GENERAL NOTES AND TYPICAL DETAILS. NOTIFY THE ARCHITECT OF RECORD (AOR) AND STRUCTURAL ENGINEER OF RECORD (SEOR) IMMEDIATELY WHERE CONFLICT OCCURS BETWEEN DRAWINGS AND SPECIFICATIONS. AOR/SEOR DECIDE WHICH OF THE CONFLICTING REQUIREMENTS WILL GOVERN BASED UPON THE MOST STRINGENT OF THE REQUIREMENTS. 6. REFER TO THE TYPICAL DETAIL SHEETS FOR TYPICAL CONS TRUCTION DETAILS. TYPICAL DETAILS APPLY TO ALL CONSTRUCTION DOCUMENTS AND MAY NOT BE SPECIFICALLY REFERENCED THEREIN. UNLESS SPECIFICALLY NOTED OR SHOWN OTHERWISE, CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING THESE TYPICAL DETAILS PRIOR TO COMMENCEMENT OF WORK. WHERE CONDITIONS REQUIRE M ODIFICATIONS OF A TYPICAL DETAIL, THE CONTRACTOR SHALL SUBMIT MODIFIED DETAIL FOR APPROVAL BY THE STRUCTURAL ENGINEER OF RECORD (SEOR) PRIOR TO FABRICATION AND INSTALLATION. DETAIL OF CONSTRUCTION NOT SHOWN SHALL BE OF SAME NATURE AS THOSE SHOWN FOR SIMILAR CONSTRUCTION. 7. SCHEDULE CONSTRUCTION OPERATIONS IN SEQUENCE REQUIRED TO OBTAIN THE BEST RESULTS, WHERE INSTALLATION OF ONE PART OF THE WORK DEPENDS ON INSTALLATION OF OTHER COMPONENTS, BEFORE OR AFTER ITS OWN INSTALLATION. COORDINATE INSTALLATION OF DIFFERENT COMPONENTS TO ENSURE MAXIMUM PERFORMANCE AND ACCESSIBILITY FOR REQUIRED MAINTENANCE, SERVICE, AND REPAIR. 8. THESE DOCUMENTS SHALL NOT BE CONSTRUED AS STAND-ALONE DOCUMENTS. CONTRACTOR SHALL COORDINATE WITH ALL OTHER CONSULTANTS' WORK. 9. MODIFICATIONS AND SUBSTITUTION REQUESTS FOR MATERIALS SPECIFIED ON STRUCTURAL DRAWINGS MUST BE ACCEPTED IN WRITING BY STRUCTURAL ENGINEER OF RECORD (SEOR) PRIOR TO COMMENCEMENT OF WORK. CURRENT EVALUATION REPORTS AND PRODUCT INFORMATION SHALL BE PROVIDED TO THE STRUCTURAL ENGINEER DEMONSTRATING ADEQUACY OF THE REQUIRED CAPACITY AND PERFORMANCE OF THE MATERIAL TO BE SUBSTITUTED. ARCHITECT OF RECORD (AOR) AND STRUCTURAL ENGINEER OF RECORD (SEOR), AT THEIR DISCRETION, MAKE DETERMINATION AS TO WHETHER OR NOT THE PROPOSED CONTRACTOR'S MODIFICATIONS AND/OR SUBSTITUTIONS IS ACCEPTABLE. 10. CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE AND DO NOT INDICATE THE MEANS AND METHODS OF CONSTRUCTION OR NECESSARY COMPONENTS FOR CONSTRUCTION SAFETY. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN OF TEMPORARY ERECTION AIDS, FORMWORK, SCAFFOLDING, SAFETY MEASURES, SHORING OF ANY PORTION OF WORK DUE TO CONSTRUCTION EQUIPMENT, MACHINERY AND MATERIALS, AND PROTECTION OF ADJACENT PROPERTIES. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS AND METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES. VISITS TO THE SITE BY THE STRUCTURAL ENGINEER OF RECORD (SEOR) AND ARCHITECT OF RECORD (AOR) SHALL NOT CONSTITUTE ACCEPTANCE OF CONSTRUCTION MEANS AND METHODS AND DO NOT IN ANY WAY RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITIES FOR THE ABOVE. CONSTRUCTION MATERIALS AND ERECTION LOADS SHALL BE DISTRIBUTED WHEN PLACED ON THE STRUCTURE SUCH THAT THEY DO NOT EXCEED DESIGN LIVE LOADS OR RESULT IN AN UNBALANCED LOADING CONDITION. CONSTRUCTION LOADS ON ELEVATED SLABS SHALL NOT RESULT IN EXCESSIVE SHORT-TERM OR LONG-TERM DEFLECTIONS. 11. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH THE PERTINENT SECTIONS OF THE LATEST EDITION OF THE "CONSTRUCTION SAFETY ORDERS" ISSUED BY THE STATE OF CALIFORNIA, AND ALL OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) REQUIREMENTS AS THEY APPLY TO THE PROJECT. THE STRUCTURAL ENGINEER OF RECORD (SEOR) AND THE OWNER SHALL NOT BE HELD RESPONSIBLE FOR THE CONTRACTOR'S FAILURE TO COMPLY WITH THESE REQUIREMENTS. 12. ALL STRUCTURAL FRAMING SHALL BE ERECTED PLUMB AND TRUE TO LINE. TEMPORARY BRACING, AS REQUIRED, SHALL BE INSTALLED AND LEFT IN PLACE UNTIL ADEQUATE PORTION OF THE STRUCTURE IS CONSTRUCTED FOR STABILITY. 13. MAXIMUM PERMANENT EQUIPMENT WEIGHTS, POSTED LOAD LIMITS OR OTHER RESTRICTIONS NOTED ON THE STRUCTURAL DRAWINGS SHALL NOT BE EXCEEDED WITHOUT PRIOR WRITTEN APPROVAL BY THE STRUCTURAL ENGINEER OF RECORD (SEOR). UNLESS SPECIFICALLY STATED, THE STRUCTURE IS NOT DESIGNED TO SUPPORT TRAFFIC FROM FORK LIFTS, CRANES OR OTHER HEAVY CONSTRUCTION VEHICLES. ADEQUACY OF THE STRUCTURE TO SUPPORT TEMPORARY LOADS DURING CONSTRUCTION SHALL BE VERIFIED BY A LICENSED SHORING ENGINEER RETAINED BY CONTRACTOR. SHORING SYSTEM SHALL BE DESIGNED AS A COMPLETE SYSTEM THAT INCLUDES BUT NOT LIMITED TO GRAVITY LOADS AND LATERAL LOADS. 14. THESE DRAWINGS SHALL NOT BE USED FOR CONSTRUCTION IF THE STRUCTURAL ENGINEER'S SEAL AND SIGNATURE IS NOT AFFIXED TO THESE DRAWINGS. 15. CONTRACTOR SHALL ESTABLISH AND VERIFY SIZE AND LOCATION OF ALL OPENINGS AND INSERTS BY ALL TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND CONSTRUCTION. PENETRATION THROUGH SLABS AND WALLS SHALL BE IDENTIFIED BY CONTRACTOR AND SUBMITTED TO STRUCTURAL ENGINEER OF RECORD (SEOR) FOR REVIEW AND APPROVAL PRIOR TO PLACEMENT OF CONCRETE OR CMU. CORE DRILLING SHALL ONLY BE PERMITTED WHERE AUTHORIZED IN WRITING BY SEOR PRIOR TO PROCEEDING WITH THE WORK. CORE DRILLS SHALL NOT CUT ANY REINFORCING, UNLESS PERMITTED BY SEOR IN WRITING. INSPECTOR OF RECORD (IOR) SHALL BE PRESENT DURING CORE DRILLING FOR VERIFICATION. THE IOR IS TO DOCUMENT CORES EXAMINED INDICATING AN ABSENCE OF REINFORCING. 16. STRUCTURAL DRAWINGS INDICATE THE APPROXIMATE LOCATION OF EQUIPMENTS AND THEIR SECONDARY FRAMING SUPPORTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WORK BETWEEN SUBCONTRACTORS. IN ORDER TO PROVIDE NECESSARY DIMENSIONS IN A TIMELY MANNER TO ALL PARTIES INVOLVED. SECONDARY FRAMING SUPPORTING EQUIPMENTS SHALL BE PER TYPICAL DETAILS UNLESS SPECIFICALLY NOTED OTHERWISE ON PLANS. 17. SEE MECHANICAL, ELECTRICAL, AND PLUMBING (MEP) DRAWINGS FOR SIZE AND LOCATION OF EQUIPMENT PADS, EQUIPMENT ANCHORAGE TO STRUCTURE, AND EQUIPMENT WEIGHTS; ANCHORAGE AND SEISMIC BRACING OF DUCTWORK, PIPING, ELECTRICAL CONDUITS TO STRUCTURE; ELECTRICAL CONDUIT RUNS, OUTLETS AND BOXES IN CONCRETE SLABS AND WALLS; PIPE SLEEVES, TRENCHES, OPENINGS THROUGH WALLS AND SLABS FOR DUCTWORK, PIPE RUNS, AND ELECTRICAL CONDUIT RUNS. 18. MAKE ALLOWANCE FOR SHIM SPACE AT HEADERS AND JAMBS TO ALLOW FOR SETTLEMENT, DEFELCTION, AND MOVEMENT OF FRAMING. INSTALL WINDOWS, DOORS AND OTHER INSET ITEMS IN WALLS AFTER BUILDING LOADS ARE FULLY APPLIED. 19. STRUCTURAL JOINT DIMENSIONS SHOWN ON STRUCTURAL DRAWINGS (EXPANSION, SEISMIC, SEPARATION, ETC) INDICATE THE MINIMUM CLEAR DISTANCE REQUIRED STRUCTURALLY. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL REQUIREMENTS AND INFORMATION. ALL PIPES, DUCTS, CONDUIT, ETC., CROSSING SUCH JOINTS SHALL HAVE FLEXIBLE LINES WITH ADEQUATE RANGE OF MOTION. 20. REFER TO THE PROJECT SPECIFICATIONS FOR SHOP DRAWING REQUIREMENTS AND SUBMITTALS. SHOP DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER OF RECORD (SEOR) PRIOR TO FABRICATION. ALLOW FOR A REVIEW DURATION OF MINIMUM 10 BUSINESS DAYS. SUBMITTALS SHALL CONSIST OF EITHER ELECTRONIC FILES OR TWO HARD COPIES (ONE SET TO BE KEPT BY THE STRUCTURAL ENGINEER OF RECORD AND ONE REPRODUCIBLE SET TO BE RETURNED TO CONTRACTOR). 1. GOVERNING CODE: ALL WORK SHALL BE IN CONFORMANCE WITH THE 2022 CALIFORNIA BUILDING CODE (CBC 2022), INCLUDING ALL AMENDMENTS AND SUPPLEMENTS BY GOVERNING CODE AUTHORITY, AND OTHER CODES AND STANDARDS REFERENCED IN THE CONTRACT DOCUMENTS. ALL CODES AND STANDARDS REFERENCED IN CONTRACT DOCUMENTS SHALL BE THE LATEST EDITION AS NOTED BY CBC 2022, CHAPTER 35, UNO. 2. GOVERNING CODE AUTHORITY: CITY OF SANTA ANA -BUILDING AND SAFETY DIVISION. 3. GRAVITY DESIGN LOADS: ROOF LIVE LOAD.................................................................................................................................................................20 PSF 4. WIND DESIGN DATA: BASIC DESIGN WIND SPEED...........................................................................................................................................95 MPH WIND EXPOSURE.........................................................................................................................................................................C RISK CATEGORY..........................................................................................................................................................................II BUILDING ENCLOSURE.........................................................................................................................PARTIALLY ENCLOSED INTERNAL PRESSURE COEFFICIENT.................................................................................................................................+0.18 5. EARTHQUAKE DESIGN DATA: SITE LATITUDE...........................................................................................................................................................33.706123 N SITE LONGITUDE...................................................................................................................................................-117.920384 W RISK CATEGORY...........................................................................................................................................................................II SEISMIC IMPORTANCE FACTOR, Ie.......................................................................................................................................1.00 SITE CLASS...................................................................................................................................................................................D SHORT-PERIOD SITE COEFFICIENT, Fa.................................................................................................................................1.2 LONG-PERIOD SITE COEFFICIENT, Fv................................................................................................................................1.833 SITE-SPECIFIC SPECTRAL RESPONSE ACCELERATION, Ss......................................................................................1.315 g SITE-SPECIFIC SPECTRAL RESPONSE ACCELERATION, S1.......................................................................................0.472 g DESIGN SPECTRAL RESPONSE ACCELERATION, SDS.................................................................................................1.052 g DESIGN SPECTRAL RESPONSE ACCELERATION, SD1.................................................................................................0.577 g SEISMIC DESIGN CATEGORY....................................................................................................................................................D SEISMIC BASE......................................................................................................................GROUND LEVEL (DATUM EL 41.2) 6. SEISMIC FORCE-RESISTING SYSTEM (SFRS): NON-STRUCTURAL ELEMENTS 21.REVIEW OF SHOP DRAWINGS AND SUBMITTALS BY THE ARCHITECT OF RECORD (AOR) AND STRUCTURAL ENGINEER OF RECORD (SEOR) IS FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS AND DOES NOT CONSTITUTE AUTHORIZATION TO DEVIATE FROM TERMS AND CONDITIONS OF THE CONTRACT. THE CONTRACTOR WILL REMAIN RESPONSIBLE FOR ALL ERRORS IN DETAILING, FABRICATION, AND FOR CORRECT FITTING OF ALL STRUCTURAL MEMBERS, INCLUDING COORDINATION WITH OTHER TRADES. 22. SHOP DRAWINGS AND SUBMITTALS DO NOT CONSTITUTE CHANGE ORDERS. ANY PROPOSED CHANGES TO THE STRUCTURAL DOCUMENTS MUST BE SUBMITTED IN WRITING AS A REQUEST FOR SUBSTITUTION TO THE ARCHITECT AND SEOR FOR APPROVAL. 23. PREPARE TO-SCALE PROJECT-SPECIFIC SHOP DRAWINGS. SHOP DRAWINGS SHALL BE INDEPENDENTLY PRODUCED BY THE CONTRACTOR AND SHALL NOT BE A COPY OR REPRODUCTION OF THE CONTRACT DOCUMENTS. 24. ALL WORK IS NEW UNLESS INDICATED AS EXISTING (E). 25. IN AN EXISTING STRUCTURE WHERE MODIFICATIONS TO AN EXISTING LOAD-BEARING WALL IS REQUIRED, PROVIDE TEMPORARY BRACING/SHORING UNTIL NEW LOAD-BEARING WALL CONSTRUCTION IS COMPLETED AND LOAD PATH IS RESTORED. GENERAL REQUIREMENTS GENERAL REQUIREMENTS (CONTINUED) STRUCTURAL DESIGN CRITERIA 1. REVIEW OF SHOP DRAWINGS AND SUBMITTALS BY THE AOR AND SEOR IS FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS. 2. SHOP DRAWINGS SHALL BE SUBMITTED TO THE SEOR FOR REVIEW PRIOR TO FABRICATION. THE CONTRACTOR WILL REMAIN RESPONSIBLE FOR ALL ERRORS OF DETAILING, FABRICATION, AND FOR CORRECT FITTING OF ALL STRUCTURAL MEMBERS INCLUDING COORDINATION WITH OTHER TRADES. 3. SHOP DRAWINGS SHALL BE SUBMITTED TO THE SEOR (ALLOW FOR A REVIEW DURATION OF 10 BUSINESS DAYS), AND SHALL CONSIST OF EITHER ELECTRONIC FILES OR ONLY ONE SET FOR OUR RECORDS AND ONE REPRODUCIBLE SET. 4. SEOR WILL RETURN THE ELECTRONIC FILES OR REPRODUCIBLE SET CLEARLY MARKED WITH COMMENTS. ANY REQUIRED RECORD SET COPIES SHALL BE MADE FROM THIS RETURNED SET. 5. REPRODUCTION OF STRUCTURAL PLANS & DETAILS FOR SHOP DRAWINGS IS PROHIBITED. SUBCONTRACTOR/FABRICATOR IS TO PROVIDE INDEPENDENTLY CREATED DRAWINGS BASED ON THE STRUCTURAL PLANS AND DETAILS. 6. SHOP DRAWINGS AND SUBMITTALS DO NOT CONSTITUTE CHANGE ORDERS. ANY PROPOSED CHANGES TO THE STRUCTURAL DOCUMENTS MUST BE SUBMITTED IN WRITING AS A REQUEST FOR SUBSTITUTION TO THE ARCHITECT AND SEOR FOR APPROVAL. 7. EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A MAIN WIND OR SEISMIC FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM OR A WIND-OR SEISMIC-RESISTING COMPONENT LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT. THE CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL CONTAIN ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTION. 8. SUBSTITUTION REQUESTS FOR MATERIALS SPECIFIED ON THE STRUCTURAL DOCUMENTS MAY BE CONSIDERED WITH MATERIALS HAVING EQUIVALENT OR GREATER CAPACITY AND PERFORMANCE. CURRENT EVALUATION REPORTS AND PRODUCT INFORMATION SHALL BE PROVIDED TO THE SEOR DEMONSTRATING EQUIVALENT QUALITIES OF THE MATERIAL TO BE SUBSTITUTED. THE FOLLOWING LIST SUMMARIZES IMPORTANT STRUCTURAL SUBMITTALS FOR THIS PROJECT. REFER TO THE SPECIFICATIONS FOR A COMPLETE LIST AND ADDITIONAL REQUIREMENTS. GENERAL •QUALIFICATION DATA FOR APPROVED INSTALLERS AND FABRICATORS •CERTIFICATES OF CONFORMANCE FOR PREFABRICATED MEMBERS CONCRETE FORMWORK •MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR PROPRIETARY MATERIALS INCLUDING FORM COATINGS, MANUFACTURED FORM SYSTEMS, TIES AND ACCESSORIES •SHOP DRAWINGS FOR FABRICATION AND ERECTION OF FORMWORK AND SHORING CONCRETE REINFORCEMENT •MANUFACTURER'S PRODUCT DATA, SPECIFICATIONS AND INSTALLATION PROCEDURES FOR PROPRIETARY MATERIALS AND REINFORCEMENT •STEEL PRODUCER'S CERTIFICATES OF MILL ANALYSIS, TENSILE AND BEND TESTS •SHOP DRAWINGS FOR FABRICATION, BENDING AND PLACEMENT CAST-IN-PLACE CONCRETE •DESIGN MIX FOR EACH CONCRETE MIX •MATERIAL TEST REPORTS •MATERIAL CERTIFICATES FOR CEMENT, AGGREGATES AND ADMIXTURES •MANUFACTURER'S PRODUCT DATA FOR WATERSTOPS, BONDING AGENTS, VAPOR RETARDERS, JOINT FILLER, CURING MATERIALS AND FLOOR TREATMENTS •SHOP DRAWINGS FOR PROPOSED LOCATIONS OF ADDITIONAL CONSTRUCTION OR CONTROL JOINTS NOT SHOWN ON THE STRUCTURAL PLANS •MINUTES FROM PREINSTALLATION CONFERENCE STRUCTURAL STEEL •MANUFACTURER'S MILL CERTIFICATES •MILL TEST REPORTS •SHOP DRAWINGS FOR FABRICATION AND ASSEMBLY OF MEMBERS •ERECTION PLAN SEQUENCE AND PROCEDURES •WELDING PROCEDURE SPECIFICATIONS (WPS) •TEST REPORTS FOR SHOP AND FIELD WELDED AND BOLTED CONNECTIONS COLD-FORMED METAL FRAMING •SHOP DRAWINGS INDICATING LAYOUT AND DETAILS •ENGINEERING CALCULATIONS ROUGH CARPENTRY •PRODUCT DATA FOR TREATMENTS AND PRESERVATIVES •MATERIAL CERTIFICATES FOR DIMENSION LUMBER PREFABRICATED WOOD PRODUCTS •SHOP DRAWINGS INDICATING LAYOUT & DETAILS •ENGINEERING CALCULATIONS GLUE LAMINATED BEAMS •SHOP DRAWINGS INDICATING LAYOUT •CERTIFICATE OF CONFORMANCE STRUCTURAL SUBMITTALS 1. SEE "AS-BUILT" DRAWINGS FOR EXISTING BUILDING ITEMS NOT SHOWN OR NOTED. 2. FIELD VERIFY ALL CONDITIONS & DIMENSIONS PRIOR TO SHOP DRAWING PRODUCTION AND FABRICATION OF STRUCTURAL ELEMENTS. 3. WHERE ALL OTHER EXISTING CONDITIONS VARY SIGNIFICANTLY FROM THOSE SHOWN ON THESE DRAWINGS, THE STRUCTURAL ENGINEER SHALL BE NOTIFIED PRIOR TO CONTINUED CONSTRUCTION RELATED TO SUBJECT CONDITIONS. 4. SHORE ALL EXISTING CONSTRUCTION AS REQUIRED, INCLUDING WHERE WELDING TO EXISTING STEEL FRAMING. SHORING DESIGN BY OTHERS. 5. ALL EXISTING CONCRETE SURFACES TO BE IN CONTACT WITH NEW CONCRETE SHALL BE ROUGHENED TO 1/4" MINIMUM AMPLITUDE. USE ICC APPROVED BONDING AGENT ON EXISTING CONCRETE PRIOR TO PLACING NEW CONCRETE. 6. VERIFY LOCATION OF EXISTING REBAR BEFORE FABRICATION USING NON-DESTRUCTIVE TESTING. EXISTING REINFORCING SHALL BE AVOIDED WHERE DRILLING FOR POST-INSTALLED ANCHORS OR CONCRETE DOWELS. 7. THE GENERAL CONTRACTOR SHALL COORDINATE THE WEIGHT AND SPECIFIC LOCATION OF ALL MECHANICAL EQUIPMENT WITH THE STRUCTURAL FRAMING. IF THE EQUIPMENT DEVIATES IN WEIGHT OR LOCATION FROM THOSE INDICATED IN THE DRAWINGS, THE STRUCTURAL ENGINEER'S APPROVAL MUST BE OBTAINED PRIOR TO INSTALLATION OF THE UNITS. 8. ALL EXISTING WOOD FRAMING MEMBERS SUPPORTING NEW MECHANICAL UNITS SHALL BE INSPECTED FOR DAMAGE AND DETERIORATION PRIOR TO INSTALLATION OF THE UNITS. NOTIFY THE STRUCTURAL ENGINEER IF DAMAGE OR DETERIORATION IS DISCOVERED. 9. ALL EXISTING (E) WOOD ELEMENTS TO REMAIN SHALL BE FIELD INSPECTED DURING CONSTRUCTION AND TREATED FOR DRYROT REMOVAL / CONTROL. WHERE EXISTING GLUE LAMINATED TIMBER BEAMS TO REMAIN ARE FOUND TO HAVE EXTENSIVE DRYROT DEEPER THAN THE TOP TWO LAMINATIONS (3"), THE STRUCTURAL ENGINEER SHALL BE NOTIFIED PRIOR TO CONTINUED CONSTRUCTION RELATED TO SUBJECT GLUE LAMINATED TIMBER BEAMS . 10. ALL EXISTING CONNECTIONS AT ELEMENTS TO BE REPLACED SHALL BE REPLACED OR RE-ATTACHED TO MATCH EXISTING CONDITIONS. 11. SEE PROJECT REPORTS AND ARCHITECTURAL DRAWINGS FOR HAZARDOUS MATERIALS (LEAD, ASBESTOS, ETC.) ABATEMENT REQUIREMENTS. 12. DO NOT CUT OR DAMAGE EXISTING CONCRETE OR MASONRY REINFORCEMENT EXCEPT AS CLEARLY INDICATED ON STRUCTURAL DRAWINGS. MAINTAIN AT LEAST 2 INCHES CLEAR TO EXISTING REINFORCEMENT, CONDUIT AND OTHER EMBEDDED ITEMS FROM CUTS, CORES, DRILL HOLES, SHOTPINS, ETC. IN AREAS OF WORK, MARK LOCATIONS OF SUCH ITEMS USING NONDESTRUCTIVE METHODS SUCH AS GROUND PENETRATING RADAR OR X- RAY. 1. POST-INSTALLED ANCHORS INCLUDE EXPANSION ANCHORS, SCREW ANCHORS, EPOXY ANCHORS/DOWELS, AND POWDER-ACTUATED FASTENERS. 2. INSTALL POST-INSTALLED ANCHORS PER MANUFACTURER'S RECOMMENDED SPECIFICATIONS. 3. WHEN INSTALLING POWER-INSTALLED ANCHORS IN EXISTING NON-PRESTRESSED REINFORCED CONCRETE, USE CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE REINFORCING BARS OR OTHER EMBEDDED ITEMS SUCH AS ELECTRICAL/TELECOMMUNICATIONS CONDUIT AND GAS LINES. WHEN INSTALLING DRILL-IN ANCHORS INTO PRESTRESSED CONCRETE (PRE OR POST-TENSIONED), LOCATE TENDONS DURING INSTALLATION BY USING A NON-DESTRUCTIVE METHOD PRIOR TO INSTALLATION. EXERCISE EXTREME CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE TENDONS DURING INSTALLATION. MAINTAIN A MINIMUM CLEARANCE OF ONE INCH BETWEEN THE REINFORCEMENT AND THE DRILLED-IN ANCHOR. 4. WHERE SPECIFIED ANCHOR EMBEDMENT DEPTH, SPACING OR EDGE DISTANCE CANNOT BE PROVIDED, NOTIFY THE SEOR AND IOR PRIOR TO INSTALLATION. 5. PATCH ABANDONED HOLES AND SPALLS USING NON-SHRINK GROUT AND REPAIR FINISHES AS REQUIRED. ANCHORS PENETRATING THROUGH WATER PROOFING OR VAPOR MEMBRANES SHALL BE SEALED OR FLASHED. 6. TESTING OF POST-INSTALLED ANCHORS IS REQUIRED UNO. TEST ANCHORS IN ACCORDANCE WITH THE PROVISIONS OF CBC 19010A.5 AND THE FOLLOWING: a. TEST 100% OF ANCHORS AT ALL STRUCTURAL APPLICATIONS UNO. b. TEST 50% OF ANCHORS AT ALL-NON-STRUCTURAL APPLICATIONS SUCH AS EQUIPMENT ANCHORAGE, UNO. c. IF ANY ANCHOR FAILS TESTING, TEST ALL ANCHORS OF THE SAME TYPE NOT PREVIOUSLY TESTED UNTIL TWENTY (20) CONSECUTIVE ANCHORS PASS, THEN RESUME INITIAL TEST FREQUENCY. IF THE ANCHORS ARE USED FOR THE SUPPORT AND BRACING OF NON-STRCTURAL COMPONENTS (PIPE, DUCT, OR CONDUIT), THE TWENTY (20) SHALL BE ONLY THOSE ANCHORS INSTALLED BY THE SAME TRADE. d. ALL POST-INSTALLED ANCHORS ARE TO BE TENSION TESTED WITH THE EXCEPTION THAT TORQUE TESTING IS ALLOWED IF THE ANCHORS ARE SPECIFICALLY DESIGNED AS TORQUE CONTROLLED. e. TENSION TESTS ACCEPTANCE: APPLY PROOF TEST LOADS TO ANCHORS WITHOUT REMOVING NUT IS POSSIBLE. IF NOT, REMOVE NUT AND INSTALL A THREADED COUPLER TO THE SAME TIGHTNESS OF THE ORIGINAL NUT USING A TORQUE WRENCH AND APPLY LOAD. ANCHORS TESTED WITH A HYDRAULIC JACK OR SPRING LOADED DEVICES SHALL MAINTAIN THE TEST LOAD FOR A MINIMUM OF 15 SECONDS AND SHALL EXHIBIT NO DISCERNIBLE MOVEMENT DURING THE TENSION TEST, E.G. AS EVIDENCED BY LOOSENING OF THE WASHER UNDER THE NUT. f. TORQUE TESTS ACCEPTANCE: ANCHORS TESTED WITH A CALIBRATED TORQUE WRENCH MUST ATTAIN THE MANUFACTURER'S RECOMMENDED TORQUE WITHIN 1/2 TURN OF THE NUT. g. TEST EQUIPMENT IS TO BE CALIBRATED BY AN APPROVED TESTING LABORATORY IN ACCORDANCE WITH STANDARD RECOGNIZED PROCEDURES. h. FIELD TESTING SHALL BE DONE IN THE PRESENCE OF THE SPECIAL INSPECTOR OR INSPECTOR OF RECORD. i. TESTING SHOULD OCCUR 24 HOURS MINIMUM AFTER INSTALLATION OF THE SUBJECT ANCHORS. j. INSPECTOR OF RECORDS SHALL REQUEST PROOF TEST VALUES FROM SEOR FOR EACH TYPE OF POST-INSTALLED ANCHORS AT LEAST 48 HOURS PRIOR TO TESTING. 7. INSTALLERS PLACING HORIZONTALLY OR UPWARDLY INCLINED ADHESIVE ANCHORS SHALL BE CERTIFIED BY ACI OR APPROVED EQUIVALENT. 8.RE-USE OF SCREW ANCHORS OR HOLES IS NOT PERMITTED. POST-INSTALLED ANCHOR POWDER ACTUATED FASTENERS (PAF) EXISTING CONDITIONS 1. ALLOWABLE POWDER-ACTUATED FASTENERS (PAF) SHALL BE EITHER ONE OF THE FOLLOWING UNO: HILTI X-U (ICC ESR-2269), SIMPSON POWER-DRIVEN FASTENERS (ICC ESR-2138), DEWALT CSI SPIRAL DRIVE PIN (ICC ESR-2024) 2. INSTALL PER MANUFACTURER'S RECOMMENDED SPECIFICATIONS. 3. PROVIDE 0.08" THICK x 1.1" SQUARE OR 1.425" ROUND WASHERS FOR ALL POWDER-ACTUATED FASTENERS. 4. THE MINIMUM EMBEDMENT OF PAF INTO CONCRETE SHALL BE 1" UNO. 5. THE EMBEDMENT OF PAF INTO STEEL SHALL BE THAT REQUIRED BY PAF MANUFACTURER ICC ESR REPORT. 6. TESTING OF PAF IS NOT REQUIRED. 7. MAINTAIN ALL APPLICABLE EDGE DISTANCE AT CURBS AND SLAB EDGES PER MANUFACTURER'S ICC ESR REPORT. 1. DEMOLITION WORK SHALL BE CONDUCTED IN SUCH A MANNER AS TO NOT DAMAGE EXISTING ELEMENTS THAT ARE TO REMAIN IN THE FINISHED BUILDING. 2. VERIFY EXISTING BUILDING DIMENSIONS AND ELEVATIONS. NOTIFY AOR/SEOR OF ANY DISCREPANCIES BEFORE PROCEEDING WITH WORK. 3. PROVIDE MEASURES NECESSARY TO PROTECT THE EXISTING STRUCTURE DURING DEMOLITION WORK. PROTECTIVE MEASURES SHALL REMAIN IN PLACE UNTIL THE FINAL STRUCTURAL ELEMENTS ARE IN PLACE AND ABLE TO SAFELY CARRY ALL IMPOSED EXISTING BUILDING LOADS. SUCH MEASURES INCLUDE, BUT NOT LIMITED TO, BRACING AND SHORING. 4. EXISTING ELEMENTS OF THE STRUCTURE THAT ARE TO REMAIN IN THE FINISHED BUILDING SHALL BE PROTECTED AS NECESSARY TO MINIMIZE DAMAGE DURING DEMOLITION WORK, ANY SUCH DAMAGE SHALL BE REPAIRED AND/OR REPLACED AT NO ADDED COST. 5. ROUGHEN EXISTING CONCRETE SURFACES AGAINST WHICH FRESH CONCRETE IS TO BE PLACED TO A FULL AMPLITUDE OF 1/4 INCH. 6. EXISTING CONCRETE ELEMENTS THAT ARE TO BE REMOVED BY CHIPPING SHALL BE STARTED WITH A 3/4 INCH DEEP SAW CUT. CORNERS SHALL BE DRILLED TO PREVENT OVER-CUTTING. EXPOSED SAW CUT LINES SHALL BE CLEAN, STRAIGHT AND SMOOTH. 7. EXISTING REINFORCING STEEL TO REMAIN SHALL BE CLEANED TO BARE METAL. 8. DEMOLISHED MATERIAL PLACED ON EXISTING FLOORS SHALL BE SPREAD OUT SUCH THAT IMPOSED LOADS DO NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. PROVIDE ADEQUATE SHORING WHERE OVERLOAD IS ANTICIPATED. DEMOLITION 1. DESIGN, FABRICATION AND ERECTION OF COLD-FORMED STEEL FRAMING SHALL CONFORM TO THE CURRENT CBC ADOPTED EDITION OF THE SPECIFICATIONS AND STANDARD OF THE AMERICAN IRON AND STEEL INSTITUTE (AISI), AS CONTAINED IN THE "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS", INCLUDING ALL APPLICABLE AMENDMENTS. 2. ALL COLD-FORMED STEEL FRAMING SHALL BE ERECTED PLUMB AND TRUE TO LINE. TEMPORARY BRACING SHALL BE INSTALLED AND LEFT IN PLACE UNTIL OTHER MEANS IS PROVIDED TO ADEQUATELY BRACE THE STRUCTURE. ALL COLD-FORMED STEEL FRAMING SHALL BE BRACED AS REQUIRED BY SECTION D3 OF THE AISI SPECIFICATION. 3. COLD-FORMED STEEL GRADES (ASTM A1003): 18 GA (43 MILS) OR THINNER.................................................................................................................GRADE 33 (Fy = 33 KSI) 16 GA (54 MILS) AND THICKER...............................................................................................................GRADE 50 (Fy = 50 KSI) 4. SUBMIT COLD-FORMED STEEL FRAMING SHOP DRAWINGS AND SPECIFICATIONS TO THE SEOR AND AOR FOR REVIEW AND APPROVAL PRIOR TO FABRICATION. 5. COLD-FORMED STEEL STUDS AND TRACKS ARE TO BE ATTACHED WITH SHEET METAL SCREWS (SMS) WITH SIZES CALLED OUT ON THE DETAILS. PENETRATION OF SCREWS THROUGH JOINED MATERIAL SHALL NOT BE LESS THAN 3 EXPOSED THREADS. SCREWS SHALL BE DART SELF DRILLING SCREWS (ICC ESR-1408) OR ITW BUILDEX TEKS (ICC ESR-1976) AND SHALL BE INSTALLED AND TIGHTENED IN ACCORDANCE WITH SCREW MANUFACTURER'S RECOMMENDATIONS. SHEET METAL SCREWS SHALL COMPLY WITH ASTM C1513, SELF-DRILLING AND TAPPING TYPE, WITH PANCAKE FRAMER HEAD TYPE FOR #10 SMS AND HEX WASHER HEAD TYPE FOR #12 AND #14 (1/4"Ø) SMS UNLESS NOTED OTHERWISE. 6. COLD-FORMED STUD MEMBERS SHALL BE UNPUNCHED WHERE USED FOR THE FOLLOWING: HEADERS AND SILLS OF OPENINGS WIDER THAN 3'-0", AND BUILT-UP BOX AND BACK-TO-BACK SECTIONS. PUNCH-OUTS SHALL BE LOCATED IN THE CENTER OF THE WEB WITH A MINIMUM SPACING OF 24"OC, HAVE A MAXIMUM WIDTH OF HALF THE MEMBER DEPTH OR 2 1/2", WHICHEVER IS LESS, AND A MAXIMUM LENGTH OF 4 1/2". THE MINIMUM DISTANCE BETWEEN THE END OF THE MEMBER AND THE NEAR EDGE OF THE PUNCH-OUT SHALL BE 12". 7. WELDING OF LIGHT GAGE STEEL SHALL BE IN ACCORDANCE WITH AMERICAN WELDING SOCIETY (AWS) D1.3. COLD-FORMED STEEL FRAMING STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 12" = 1'-0" 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 GENERAL NOTES S1.0.1 MCGUFF 03/11/25 SHEET LIST - TI Sheet Number Sheet Name S1.0.1 GENERAL NOTES S1.0.2 GENERAL NOTES S1.0.3 GENERAL NOTES S1.1.1 TYPICAL CONCRETE DETAILS S1.1.2 DETAILS S1.1.3 DETAILS S1.1.4 METAL STUD DETAILS S1.1.5 METAL STUD DETAILS S1.1.6 DETAILS S1.2.1 FIRST FLOOR PLAN S1.2.2 ROOF FRAMING PLAN NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 1. THE STRUCTURAL PRODUCT SCHEDULE INDICATES BASIS-OF-DESIGN MANUFACTURERS AND PRODUCTS FOR USE ON THIS PROJECT. WHERE STRUCTURAL PRODUCTS ARE NOT EXPLICITLY NAMED IN THE CONSTRUCTION DOCUMENTS, PROVIDE A LISTED PRODUCT. 2. PRODUCTS SHALL BE INSTALLED PER THE MANUFACTURER’S INSTALLATION INSTRUCTIONS AS AMENDED BY THE REFERENCED PRODUCT ACCEPTANCE REPORTS (ICC, IAPMO, ETC.) FOR THE INTENDED USE. 3. AT CONTRACTOR’S OPTION, SUBSTITUTION REQUESTS MAY BE MADE FOR LIKE PRODUCTS WHICH DEMONSTRATE QUALITIES THAT EQUAL OR EXCEED THOSE OF SPECIFIED PRODUCTS. 25675 22668 25469 SHOTPIN 25897 25741 25808 SCREW ANCHOR TO CONCRETE 25964 26028 - 26035 25960 NA ADHESIVE ANCHOR TO CONCRETE NA 25831 25891 STRUCTURAL PRODUCT SCHEDULE LARR EXPANSION ANCHOR TO CONCRETE ESR-2269 ESR-1799 ESR-2138 ESR-3027 ESR-2713 ESR-2526 ESR-3187 ESR-3814 ESR-4027 ESR-3298 ER-0263 ESR-4057 ESR-4266 ESR-2502 ESR-3037 HILTI LOW-VELOCITY X-U ITW RAMSET POWER-DRIVEN SIMPSON POWDER-ACTUATED HILTI KWIK HUS-EZ, -EZ 1 SIMPSON TITEN HD DEWALT/POWERS WEDGE-BOLT+ HILTI HIT-HY 200 HILTI HIT-RE 500-V3 DEWALT/POWERS AC200+ DEWALT/POWERS PURE110+ SIMPSON AT-XP SIMPSON SET-3G HILTI KWIK BOLT TZ2 DEWALT/POWERS-STUD+ SD2 SIMPSON STRONG-BOLT 2 ICC / IAPMOPRODUCTTYPE PRODUCT SPECIFICATION 25620 26050 FIBER-REINFORCED POLYMER (FRP) SYSTEMS REINFORCEMENT BAR TERMINATOR 25342 25347 24507 REINFORCEMENT BAR COUPLER 02725 25860 WELDED STUD 25815 25893 ESR-2103 ESR-2606 ESR-2495 ESR-2746 ER-0129 ESR-2856 ESR-2907 ESR-2746 ER-0188 FYFE TYFO FIBRWRAP STRUCTURAL TECH V-WRAP DAYTON BAR LOCK L-SERIES HRC 500/510 XTENDER LENTON NELSON SHEAR CONNECTOR STUDS NELSON D2L DEFORMED BAR ANCHOR HRC 555/670 HEADED REINF. BARS LENTON TERMINATOR 1. REINFORCING GRADES FOR CONCRETE OR MASONRY (UNO): A. ALL BARS EXCEPT THOSE TO BE WELDED......................................................................................ASTM A615, GRADE 60 B. TIES AND STIRRUPS ............................................................................................................................ASTM A615, GRADE 60 C. WELDED WIRE FABRIC ..........................................................................................................................................ASTM A1064 D. ALL BARS TO BE WELDED ..................................................................................................................ASTM A706, GRADE 60 NOTE: ALL BARS SHALL BE DEFORMED. 2. MAINTAIN SPECIFIED CONCRETE COVER FROM FACE OF CONCRETE TO EDGE OF ALL REINFORCEMENT AS FOLLOWS (UNO): 3. REINFORCEMENT SHALL BE PLACED IN ACCORDANCE WITH THE LATEST EDITION OF CONCRETE REINFORCING STEEL INSTITUTE (CRSI) "MANUAL OF STANDARD PRACTICE". EACH REINFORCING BAR SHALL BE WIRED TO A CROSS BAR AT A MAXIMUM SPACING OF 24"OC. PROVIDE ALL ACCESSORIES NECESSARY TO SUPPORT REINFORCING IN POSITIONS SHOWN ON THE PLANS. DO NOT USE WOOD OR BRICK TO SUPPORT REINFORCING. 4. SPLICES IN CONTINUOUS REINFORCEMENT AS USED IN WALLS, WALL FOOTINGS, ETC., SHALL HAVE A CLASS "B" LAP (1'-6" MIN) AND THE SPLICES IN ADJACENT BARS SHALL BE NOT LESS THAN 5'-0" APART. VERTICAL WALL BARS SHALL BE SPLICED AT OR NEAR FLOOR LINES. BARS MAY BE WIRED TOGETHER AT SPLICES OR LAPS EXCEPT FOR TOP REINFORCING OF BEAMS AND SLABS OR WHERE SPECIFICALLY DETAILED TO BE SEPARATED. WELDED WIRE FABRIC SHALL BE LAPPED 12" MINIMUM. ADJACENT WELDED WIRE FABRIC (WWF) SHEET SHALL BE LAPPED 12 INCHES MINIMUM. 5. PROVISION FOR LAP SPLICES OR DOWELS SHALL BE PROVIDED ACROSS ALL CONSTRUCTION JOINTS AND SHALL BE THE SAME GRADE, SIZE AND SPACING AS REINFORCING CONTINUING BEYOND UNLESS NOTED OTHERWISE. IN LIEU OF SPLICES OR DOWELS, THE CONTRACTOR MAY SUBMIT FOR SEOR APPROVAL THE LOCATION AND MANUFACTURER DATA OF FORMSAVERS OR COUPLERS PRIOR TO THEIR USE. 6. ALL DOWELS, ANCHOR BOLTS AND OTHER HARDWARE TO BE SET IN CONCRETE SHALL BE TIED IN PLACE PRIOR TO PLACEMENT OF CONCRETE. NO WET SETTING, STABBING, RODDING OR OTHER MOVEMENT OF EMBEDDED ITEMS SHALL BE PERFORMED DURING PLACEMENT OF CONCRETE. 7. BEND REINFORCING BARS COLD. 8. REINFORCING BARS SHALL BE KEPT CLEAN AND FREE OF RUST. 9. DOWELS BETWEEN FOOTING AND WALLS OR COLUMNS SHALL BE THE SAME GRADE, SIZE AND SPACING AS THE MAIN REINFORCING UNO. 10. ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN THE FINAL IN PLACE INSPECTION IS MADE. 11. CHAIRS OR SPACERS FOR REINFORCING SHALL BE PLASTIC WHEN RESTING ON EXPOSED SURFACES. 12. WHERE LONGITUDINAL REINFORCING BARS ARE PLACED IN 2 OR MORE LAYERS, BARS IN THE UPPER LAYERS SHALL BE PLACED DIRECTLY ABOVE BARS IN THE BOTTOM LAYER. 13. ALL BENDS WITHIN STIRRUPS, HOOPS, AND CROSS-TIES SHALL ENGAGE A LONGITUDINAL BAR. PROVIDE #4 SPACER BAR WHERE A LONGITUDINAL BAR IS NOT SPECIFICALLY DETAILED. 14. WELDING OF REINFORCING BARS SHALL BE ASTM A706 AND BE PERFORMED PER AMERICAN WELDING SOCIETY (AWS) D1.4 USING MATCHING FILLER MATERIALS PER AWS TABLE 7.1, MINIMUM E80XX ELECTRODES. 15. THE FOLLOWING REINFORCEMENT SHALL COMPLY WITH ASTM A706: A. VERTICAL REINFORCEMENT AT INTERSECTIONS AND ENDS OF CONCRETE WALLS ENCLOSED IN TIES OR STIRRUPS (BOUNDARY ELEMENTS). B. LONGITUDINAL MOMENT FRAME BEAMS AND COLUMNS REINFORCING BARS. C. WELDED REINFORCING. SPECIFIED CONCRETE COVER FOR CAST-IN-PLACE NON-PRESTRESSED CONCRETE MEMBERS CONCRETE EXPOSURE MEMBER REINFORCEMENT CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND ALL ALL SPECIFIED COVER (IN) 3 EXPOSED TO WEATHER OR IN CONTACT WITH GROUND ALL NO. 6 THROUGH NO. 18 BARS 2 NO. 5 BAR, W31 OR D31 WIRE, AND SMALLER 1 1/2 NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND SLABS, JOISTS, AND WALLS NO. 14 AND NO.18 BARS NO. 11 BAR AND SMALLER 1 1/2 3/4 BEAMS, COLUMNS, PEDESTALS, AND TENSION TIES PRIMARY REINFORCEMENT, STIRRUPS, TIES, SPIRALS, AND HOOPS 1 1/2 SPECIFIED CONCRETE COVER FOR CAST-IN-PLACE PRESTRESSED CONCRETE MEMBERS CONCRETE EXPOSURE MEMBER REINFORCEMENT CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND ALL ALL SPECIFIED COVER (IN) 3 EXPOSED TO WEATHER OR IN CONTACT WITH GROUND ALL 1 ALL 1 1/2 NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND SLABS, JOISTS, AND WALLS ALL PRIMARY REINFORCEMENT 3/4 1 1/2 BEAMS, COLUMNS, PEDESTALS, AND TENSION TIES STIRRUPS, TIES, SPIRALS, AND HOOPS 1 SLABS, JOISTS, AND WALLS ALL OTHER REINFORCING STEEL CONCRETE TYPE MAX AGGREGATE SIZE MIN COMPRESSIVE STRENGTH AT 28 DAYS (f'c) LOCATION MAX W/CM RATIO SLAB-ON-GRADE 4,000 PSI 1"0.45 CONCRETE CURB FOR ROOF TOP AHU 5,000 PSI 3/4"N/A ALL OTHER STRUCTURAL CONCRETE (UNO)3,000 PSI 1"0.50 NORMAL-WEIGHT LIGHT-WEIGHT NORMAL-WEIGHT GRADE BEAM 5,000 PSI FOUNDATIONS (UNO)5,000 PSI NORMAL-WEIGHT 1 1/2"0.50 3/4"0.50NORMAL-WEIGHT 3. STRUCTURAL CONCRETE SHALL CONFORM TO PROJECT SPECIFICATIONS AND THE FOLLOWING REQUIREMENTS: A. MAXIMUM DRY UNIT WEIGHT OF LIGHT-WEIGHT CONCRETE SHALL NOT EXCEED 110 ± 3 PCF (PER ASTM C138). MAXIMUM DRY UNIT WEIGHT OF NORMAL-WEIGHT CONCRETE SHALL NOT EXCEED 150 ± 3 PCF. B. WHEN PLASTICIZER OR WATER REDUCER IS USED, MAXIMUM SLUMP SHALL BE 4" PRIOR TO ADMIXTURE AND 8" INCLUDING ADMIXTURE AT THE POINT OF DISCHARGE. IN THE ABSENCE OF PLASTICIZER AND WATER REDUCER, SLUMP AT THE POINT OF DISCHARGE SHALL NOT EXCEED 4" IN FLATWORK AND 5" ELSEWHERE. C. W/CM INDICATES WATER TO CEMENTITOUS MATERIALS RATIO BASED ON ALL CEMENTITIOUS AND SUPPLEMENTARY CEMENTITIOUS MATERIALS IN THE CONCRETE MIXTURE. THE MAXIMUM WATER-CEMENTITOUS MATERIAL RATIO (W/CM) FOR SLABS-ON-GRADE AND ALL OTHER SLABS RECEIVING ADHERED FLOORING FINISHES SENSITIVE TO MOISTURE SHALL NOT EXCEED 0.45, WATER-CEMENTITOUS MATERIAL RATIO (W/CM) FOR CONCRETE ON METAL DECK WITH WITH VENTED FLUTES MAY BE 0.50, UNO. D. SLABS ON GRADE, TOPPING SLABS, AND ELEVATED CONCRETE FLOORS (INCLUDING CONCRETE ON METAL DECK) SHALL HAVE A MAXIMUM SHRINKAGE RATE OF 0.045% AT 28 DAYS PER ASTM C 157. SUBMIT SHRINKAGE TEST RESULTS AS PART OF CONCRETE MIX DESIGN FOR REVIEW AND APPROVAL BY SEOR. E. MAXIMUM AGGREGATE SIZE SHALL BE AS NOTED IN TABLE ABOVE, BUT NOT LARGER THAN THE LEAST OF ONE- FIFTH THE NARROWEST DIMENSION BETWEEN SIDES OF FORMS, ONE-THIRD THE DEPTH OF SLAB, AND THREE- FOURTH THE MINIMUM SPECIFIED CLEAR SPACING BETWEEN INDIVIDUAL REINFORCING BARS OR TENDONS. F. AGGREGATE GRADATION OF 3/8" MAXIMUM (PEA GRAVEL) SHALL NOT BE USED WHERE FINISHED CONCRETE SURFACE IS EXPOSED TO VIEW. G. FOR CONCRETE EXPOSURE CATEGORIES AND CLASSES REFER TO TABLE 19.3.1.1 OF ACI 318. CONCRETE MIXTURES SHALL CONFORM TO THE MOST RESTRICTIVE REQUIREMENTS OF TABLE 19.3.2.1 OF ACI 318 BASE ON EXPOSURE CLASSES ASSIGNED. H. CURING COMPOUNDS USED ON CONCRETE THAT IS TO RECEIVE FINISHES SHALL BE COMPATIBLE WITH TILE AND ADHESIVES OR GROUTS IN ACCORDANCE WITH MANUFACTURER'S DATA. I. MAXIMUM W/CM LIMITS DO NOT APPLY TO LIGHTWEIGHT CONCRETE. J. AIR CONTENT OF CONCRETE MIXTURE SHALL COMPLY WITH R EQUIREMENTS OF SECTION 19.3.3 OF ACI 318. K. FOR EXPOSURE CLASS S1, S2 OR S3, MINERAL FILLERS DERIVED FROM CARBONATE AGGREGATE ARE PROHIBITED. 4. CONCRETE MIX PROPORTIONING SHALL BE BASED ON FIELD DATA AND/OR LABORATORY TRIAL MIXES AS REQUIRED BY CBC, ACI 318, ACI 214R AND ACI 301. THE CONCRETE SHALL BE WORKABLE AND MEET DURABILITY AND STRENGTH REQUIREMENT OF THE CODE. SUBMIT CONCRETE MIX PROPORTIONING DATA INCLUDING HISTORICAL STRENGTH RECORDS AND/OR LABORATORY TRIAL MIXES FOR EACH TYPE AND COMPRESSIVE STRENGTH PREPARED, SIGNED AND SEALED BY A CALIFORNIA LICENSED CIVIL OR STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL BY AOR/SEOR AND DSA'S LABORATORY ACCEPTANCE PROGRAM (LEA) PRIOR TO CONCRETE PLACEMENT. 5. AGGREGATES IN NORMAL-WEIGHT CONCRETE SHALL BE HARD ROCK AND CONFORM TO ASTM C33. AGGREGATES IN LIGHT-WEIGHT CONCRETE SHALL BE EXPANDED SHALE AND CONFORM TO ASTM C330. FOR CONCRETE IDENTIFIED AS BEING EXPOSED TO WATER IN SERVICE, EVIDENCE SHALL BE SUBMITTED THAT AGGREGATES IN THE CONCRETE MIXTURE ARE NOT ALKALI-SILICA REACTIVE OR ALKALI-CARBONATE REACTIVE. 6. CEMENTITIOUS MATERIALS USED IN CONCRETE MIXTURE SHALL COMPLY WITH TABLE 26.4.1.1.1(a) AND TABLE 19.3.2.1 OF ACI 318. MILL TESTS WITH CERTIFICATES OF COMPLIANCE SHALL BE SUBMITTED. FLY ASH OR OTHER POZZOLANS CONFORMING TO ASTM C618 CLASS F MAY BE USED AS A PARTIAL SUBSTITUTION FOR PORTLAND CEMENT BY WEIGHT IF THE MIX DESIGN IS PROPORTIONED BY FIELD EXPERIENCE OR TRIAL MIXTURES. WHERE CONCRETE IS SUBJECT TO CYCLES OF FREEZING AND THAWING AND APPLICATION OF DEICING CHEMICALS, SUPPLEMENTARY CEMENTITIOUS MATERIALS SHALL NOT EXCEED THE MAXIMUM PERCENTAGES ALLOWED IN TABLE 26.4.2.2(b) AND SECTION 26.4.2.2 OF ACI 318. 7. READY-MIXED CONCRETE SHALL BE BATCHED, MIXED AND DELIVERE D IN CONFORMANCE WITH ASTM C94. 8. ADMIXTURES SHALL CONFORM WITH THE FOLLOWING REQUIREMENTS: WATER REDUCER AND SETTING TIME MODIFICATION IN CONFORMANCE WITH ASTM C494 (TYPE F OR G) SUPERPLASTICIZER IN CONFORMANCE WITH ASTM C1017 (TYPE I OR II). AIR ENTRAINMENT IN CONFORMANCE WITH ASTM C260. INHIBITING CHLORIDE-INDUCED CORROSION IN CONFORMANCE WITH ASTM C1582. 9. CONCRETE SHALL NOT BE DROPPED THROUGH REINFORCING STEEL OR CAUSE SEGREGATION OF AGGREGATES. IN SUCH CASES, HOPPERS AND VERTICAL CHUTES OR TRUNKS SHALL BE USED. CHUTES OR TRUNKS SHALL BE OF VARIABLE LENGTHS SO THAT FREE UNCONFINED FALL OF CONCRETE SHALL NOT EXCEED SIX FEET. A SUFFICIENT NUMBER OF CHUTES OR TRUNKS SHALL BE USED TO ENSURE THE CONCRETE IS KEPT LEVEL AT ALL TIMES. 10. CONSTRUCTION JOINTS SHALL BE CLEANED AND ROUGHENED BY REMOVING THE ENTIRE SURFACE TO EXPOSE CLEAN AGGREGATE SOLIDLY EMBEDDED IN THE MORTAR MATRIX. SEE PLANS AND DETAILS FOR LOCATION AND TYPE OF CONSTRUCTION JOINT. LOCATIONS OF ADDITIONAL CONSTRUCTION JOINTS NOT SHOWN ON THESE PLANS SHALL BE SUBMITTED TO SEOR FOR APPROVAL PRIOR TO CONCRETE PLACEMENT. 11. LEAN CONCRETE, WHERE SPECIFICALLY INDICATED, SHALL CONTAIN 2 SACKS OF CEMENT PER CUBIC YARD OF CONCRETE. 12. DRYPACK OR NON-SHRINK GROUT SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 5000 PSI, AND CONSIST OF MASTERFLOW 713, EUCON NS GROUT, SIKA GROUT 212, OR APPROVED EQUAL. FOR THICK GROUT LAYERS FOLLOW MANUFACTURER'S GUIDELINES TO ATTAIN THE REQUIRED STRENGTH, WHICH MAY INCLUDE THE ADDITION OF PEA FINE AGGREGATES. FOR BASE PLATES LARGER THAN 6 SQUARE FEET, USE HI-FLOW GROUT OR MASTERFLOW 928. 13. DO NOT USE ANY CONCRETE OR GROUT CONTAINING CHLORIDES. WATER USED IN MIX SHALL BE CLEAN AND POTABLE. 14. PRIOR TO ERECTING ANY ELEMENTS THAT LOAD THE FOUNDATION, CONCRETE MUST REACH AN UNCONFINED COMPRESSION STRENGTH OF MINIMUM 75% f'c AS DETERMINED BY TESTING OR PREVIOUSLY DOCUMENTED DATA FOR THE MIX DESIGN USED UNDER SIMILAR CONDITIONS, AND MUST BE ALLOWED TO CURE FOR A MINIMUM OF 3 DAYS. 15. MAINTAIN CONCRETE ABOVE 50 DEGREES FAHRENHEIT AND IN A MOIST CONDITION FOR A MINIMUM OF 7 DAYS AFTER PLACEMENT UNLESS OTHERWISE ACCEPTED BY SEOR. 16. SEE ARCHITECTURAL DRAWINGS FOR WALL OPENING SIZES AND LOCATIONS, WALL OFFSETS, CHAMFERS, KERFS, DRIPS AND FOR EXTENT OF DEPRESSIONS, RAMPS, ETC. 17. PROVIDE SLEEVES FOR ALL PIPES THROUGH CONCRETE WALLS AND FOOTINGS WHERE SHOWN ON THESE DRAWINGS. CORING IS NOT PERMITTED WITHOUT PRIOR APPROVAL BY THE SEOR. 18. EXPOSED CORNERS OF SLABS, BEAMS, WALLS, COLUMNS, ETC. SHALL BE FORMED WITH 3/4" CHAMFER OR 1/2" RADIUS TOOLED EDGE, UNO. 19. SUBMIT SHOP DRAWINGS INDICATING LOCATIONS OF CONCRETE CONSTRUCTION JOINTS TO SEOR FOR REVIEW AND APPROVAL PRIOR TO CONCRETE PLACEMENT. LOCATE CONSTRUCTION JOINTS TO MINIMIZE EFFECTS OF SHRINKAGE AND AT POINTS OF LOW STRESS. HORIZONTAL CONSTRUCTION JOINTS ARE NOT PERMITTED IN BEAMS AND SLABS UNLESS SPECIFICALLY SHOWN ON THE DRAWINGS OR APPROVED BY SEOR PRIOR TO CONCRETE PLACEMENT. 20. PRIOR TO PLACING CONCRETE, REINFORCING BARS (INCLUDING WELDED WIRE REINFORCEMENT), EMBEDDED PLATES, ANCHOR BOLTS, AND OTHER CONCRETE EMBEDMENTS SHALL BE WELL SECURED IN POSITION. 21. CONCRETE PLACEMENT SHALL CONFORM TO ACI 304 AND CONTRACT DOCUMENTS. INTENTIONALLY ROUGHEN ALL PREVIOUSLY HARDENED CONCRETE SURFACES TO A FULL AMPLITUDE OF 1/4-INCH AGAINST WHICH FRESH CONCRETE IS PLACED. 22. CURING COMPOUNDS, SEALERS, HARDENERS, ETC., USED ON CONCRETE THAT RECEIVES A FINISH SHALL BE APPROVED BY THE ARCHITECT BEFORE USE. 1. CONCRETE SHALL BE MIXED, PLACED AND CURED IN ACCORDANCE WITH THE CURRENT CBC ADOPTED EDITION OF ACI 318, ACI 301, AND PROJECT SPECIFICATIONS. 2. STRUCTURAL CONCRETE SHALL MEET THE FOLLOWING DESIGN CRITERIA UNLESS NOTED OTHERWISE: CAST-IN-PLACE CONCRETE CONCRETE OVER METAL DECK, CURBS & PADS 4,000 PSI 3/4"N/ALIGHT-WEIGHT CONCRETE WALLS/ BASEMENT WALLS 4,000 PSI 3/4"0.50NORMAL-WEIGHT CONCRETE PEDESTALS 4,000 PSI 3/4"0.50NORMAL-WEIGHT EXPOSURE CATEGORIES AND CLASSES F0 S0 W2 C1 F0 S0 W0 C0 F0 S0 W1 C1 F0 S0 W0 C0 F0 S0 W1 C0 F0 S0 W0 C0 F0 S0 W0 C0 F0 S0 W0 C0 1. DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO THE CURRENT CBC ADOPTED EDITION OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS" (ANSI/AISC 360) AND AISC "SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS" (ANSI/AISC 341). 2. ALL WORK SHALL BE IN CONFORMANCE WITH ANY AND ALL TESTING, INSPECTION, QUALIFICATION, AND QUALITY ASSURANCE PROVISIONS AS REQUIRED BY THE CALIFORNIA BUILDING CODE AND ANY APPLICABLE STANDARDS (LATEST ADOPTED EDITION OF CURRENT CBC). • ANSI/AISC 360 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS" • ANSI/AISC 341 "SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS" • AWS D1.1 "STRUCTURAL WELDING CODE -STEEL" • AWS D1.8 "STRUCTURAL WELDING CODE -SEISMIC SUPPLEMENT" • RCSC "SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS" • ANSI/AISC 303 " CODE OF STANDARD PRACTICE FOR STEEL BUILDING AND BRIDGES" • ANSI/AISC 358 " PREQUALIFIED CONNECTIONS FOR SPECIAL AND INTERMEDIATE STEEL MOMENT FRAMES FOR SEISMIC APPLICATIONS" CONFORMANCE TO SUPPLEMENTS TO THESE STANDARDS, IF PUBLISHED ON OR BEFORE THE DATE OF PERMIT ISSUANCE, IS ALSO REQUIRED. ALTHOUGH THESE CONTRACT DOCUMENTS INCLUDE GENERAL REFERENCES TO CODES AND STANDARDS, AND REFERENCES TO OR INCLUSIONS OF SPECIFIED PROVISIONS, OMISSIONS OF ANY APPLICABLE CODE, STANDARD, OR PROVISION DOES NOT RELIEVE THE GENERAL CONTRACTOR FROM COMPLIANCE TO THE APPLICABLE REQUIREMENTS. COORDINATION OF QUALITY CONTROL AND QUALITY ASSURANCE IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. 3. STRUCTURAL STEEL MATERIAL SHALL CONFORM TO THE FOLLOWING ASTM STANDARDS, UNO: WIDE FLANGE SECTIONS....................................................................................................................................................ASTM A992 PLATE, ANGLE, CHANNEL & TEES............................................................................................................................ASTM A36 (UNO) PLATES USED IN SFRS..........................................................................................................................................ASTM A572 (50 KSI) SQUARE OR RECTANGULAR HSS....................................................................................................ASTM A500, GRADE C (50 KSI) ROUND HSS..........................................................................................................................................ASTM A500, GRADE C (46 KSI) PIPES........................................................................................................................................................ASTM A53, GRADE B (35 KSI) 4. HEADED STUD ANCHORS (SHEAR CONNECTOR STUDS ) IN CONCRETE SHALL BE NELSON TYPE S3L (ICC ESR-2856) OR AN APPROVED EQUAL, AND SHALL CONFORM TO ASTM A29-12, GRADES 1010 THROUGH 1020, COLD-DRAWN STEEL, WITH A MINIMUM ULTIMATE TENSILE STRENGTH OF 65 KSI. HEADED STUDS WELDING TEST AND INSPECTION SHALL CONFORM TO AWS D1.1, CHAPTER 7. 5. FABRICATOR SHALL BE LICENSED IN CONFORMANCE WITH THE BUILDIND CODE AND IN ACCORDANCE WITH THE AUTHORITY HAVING JURISDICTION. 6. ALL STEEL NOT ENCASED IN CONCRETE, MASONRY, OR FIREPROOFING SHALL BE SHOP PRIMED AND PAINTED PER SPECIFICATIONS, EXCEPT FOR TOP FLANGE OF BEAMS SUPPORTING METAL DECK. ANY ABRASIONS OR UNPAINTED AREAS SHALL BE REPAIRED AFTER ERECTION. 7. ALL STRUCTURAL STEEL AND MISCELLANEOUS STEEL PERMANENTLY EXPOSED TO WEATHER OR GROUND SHALL BE HOT-DIP GALVANIZED AFTER FABRICATION IN ACCORDANCE WITH ASTM A385 UNLESS A WEATHER PROOF COATING IS SPECIFIED BY THE ARCHITECT, UNO. STAINLESS AND WEATHERING STEELS, WHERE SPECIFIED, ARE EXEMPT FROM THIS REQUIREMENT. GALVANIZED SURFACES SHALL BE PROTECTED DURING CONSTRUCTION AND SHALL BE REPAIRED AS NECESSARY. BOLTED CONNECTIONS PERMANENTLY EXPOSED TO WEATHER SHALL USE GALVANIZED HIGH-STRENGTH BOLTS ASTM F3125 GRADE A325 TYPE 1 OR GALVANIZED ASTM F3125 GRADE F1852 TYPE 1. WELDED CONNECTIONS PERMANENTLY EXPOSED TO WEATHER SHALL RECEIVE ZINC RICH TOUCH UP PAINT (COORDINATE WITH AOR). STEEL IN CONTACT WITH TREADED WOOD SHALL BE HOT DIP GALVANIZED, UNO. 8. PROVIDE UPWARD CAMBER FOR ALL BEAMS SPECIFIED TO HAVE CAMBER. AMOUNT MEASURES IN THE FIELD PRIOR TO ERECTION SHALL NOT DEVIATE MORE THAN ALLOWED BY AISC SPECIFICATIONS. BEAMS WITHOUT SPECIFIED CAMBER SHALL BE FABRICATED SO THAT ANY MINOR CAMBER DUE TO ROLLING SHALL BE UPWARD AFTER ERECTION. 9. COMPOSITE STRUCTURAL BEAMS AND GIRDERS ARE DESIGNED FOR UNSHORED CONSTRUCTION UNLESS NOTED OTHERWISE. 10. ALL ARCHITECTURALLY EXPOSED STRUCTURAL STEEL (AESS) SHALL COMPLY WITH AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES" (ANSI/AISC 303), SECTION 10. 11. SEE ARCHITECTURAL DRAWINGS FOR NAILER HOLES, WELDED STUDS OR OTHER ITEMS NOT SHOWN IN STRUCTURAL DRAWINGS. 12. FOR STEEL EMBEDDED IN CONCRETE OR MASONRY WHICH WILL INTERFERE WITH CONTINUOUS REINFORCING BARS, REQUEST CLARIFICATION FROM THE SEOR WHETHER TO PROVIDE HOLES FOR PASSAGE. DO NOT CUT HOLES IN STRUCTURAL STEEL WITHOUT PRIOR APPROVAL OF SEOR. 13. DO NOT CUT HOLES IN STRUCTURAL STEEL WITHOUT WRITTEN APPROVAL OF THE SEOR. 14. PLACE NON-SHRINK OR DRYPACK GROUT UNDER ALL BASE PLATES AND ALLOW TO CURE BEFORE APPLYING ANY LOAD. 15. ALL STRUCTURAL STEEL SHALL BE ERECTED PLUMB AND TRUE TO LINE. TEMPORARY BRACING SHALL BE INSTALLED AND SHALL BE LEFT IN PLACE UNTIL OTHER MEANS IS PROVIDED TO ADEQUATELY BRACE THE STRUCTURE. 16. SUBMIT SHOP DRAWINGS TO AOR AND SEOR FOR REVIEW AND, UPON REQUEST, TO GOVERNING CODE AUTHORITY. INDICATE AN ERECTION SEQUENCE OF WELDING TO MINIMIZE LOCKED-UP STRESSES OR DISTORTION FOR MOMENT- RESISTING STEEL FRAMES. 17. HOURLY FIRE RESISTIVE REQUIREMENTS FOR STRUCTURAL STEEL MEMBERS SHALL BE DETERMINED PER CBC TABLE 601. REFER TO ARCHITECTURAL DRAWINGS FOR BUILDING TYPES OF CONSTRUCTION AND FIREPROOFING MATERIALS. 18. MECHANICAL CONTRACTOR TO VERIFY ALL MECHANICAL UNIT LOCATIONS, SIZES AND OPENINGS. NOTIFY SEOR OF ANY DISCREPANCY PRIOR TO START OF WORK. 19. STEEL FABRICATOR TO LOCATE ALL BEAMS BASED ON INFORMATION FROM MECHANICAL CONTRACTOR AND SUBMIT STEEL BEAM LOCATION TO THE AOR AND SEOR FOR REVIEW AND APPROVAL. 20. REFER TO "HIGH-STRENGTH BOLT" , "WELDING" AND "STEEL IN SEISMIC FORCE RESISTING SYSTEM (SFRS)" FOR RELATED SPECIFIC REQUIREMENTS AND NOTES FOR ADDITIONAL INFORMATION. 21. THE USE OF ROLLED STEEL SECTIONS AND/OR BOLTS MANUFACTURED OUTSIDE OF THE UNITED STATES WILL REQUIRE VERIFICATION THAT THE PRODUCTS COMPLY WITH APPLICABLE ASTM STANDARDS. MILL CERTIFICATES WILL BE REQUIRED FOR ALL STEEL. STEEL GRADES OTHER THAN ASTM A36 WILL REQUIRE TESTING BY AN APPROVED LABORATORY. ALL FOREIGN BOLTS MUST BE APPROVED BY COUNTY OF LOS ANGELES BUILDING AND SAFETY PRIOR TO THEIR USE. STRUCTURAL STEEL 1. SEE "STRUCTURAL STEEL" NOTES FOR ADDITIONAL INFORMATION. 2. JOINT ASSEMBLIES USING HIGH-STRENGTH BOLTS SHALL BE IN ACCORDANCE WITH THE CURRENT CBC ADOPTED EDITION OF THE "AISC (RCSC) SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS". 3. HIGH-STRENGTH BOLTS, NUTS AND WASHERS SHALL CONFORM TO THE "SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS" PREPARED BY RCSC AND AS AMENDED BY CBC SECTION 2204. PROVIDE STANDARD-SIZE HOLES UNLESS NOTED OTHERWISE. 4. ALL BOLTS SHALL BE HIGH-STRENGTH BOLTS, UNLESS NOTED OTHERWISE. 5. BOLTS WITH UPSET THREADS ARE NOT ALLOWED UNLESS NOTED OTHERWISE. 6. BOLTED CONNECTIONS SHALL CONFORM TO THE FOLLOWING ASTM STANDARDS UNO: MACHINE BOLTS (MB)..............................................................................................................................................ASTM A307 HIGH-STRENGTH BOLTS (TYP UNO ON DRAWINGS)......................................ASTM F3125 GRADE A325 (TYPE 1) UNO HIGH-STRENGTH BOLTS (TWIST-OFF-TYPE TENSION-CONTROLLED)................ASTM F3125 GRADE F1852 (TYPE 1) UNO THREADED RODS USED AS ANCHOR BOLTS...........................................................ASTM F1554, GRADE 36 (UNO) THREADED RODS USED IN SFRS...................................ASTM F1554, GRADE 55 (WELDABLE WITH SUPPLEMENT S1) 7. PAINT SHALL NOT BE PERMITTED ON CONTACT SURFACES UNLESS NOTED OTHERWISE. CONTACT SURFACES OF BOLTED PARTS SHALL BE DESCALED AND FREE OF DIRT, OIL, BURRS, PITS, AND OTHER DEFECTS WHICH PREVENT SOLID SEATING OF PARTS. 8. ALL HIGH-STRENGTH BOLTS SHALL BE TIGHTENED TO SNUG-TIGHT CONDITION USING ASTM F3125 GRADE A325 BEARING TYPE BOLTS WITH THREADS INCLUDED IN SHEAR PLANE UNLESS NOTED OTHERWISE. 9. PROVIDE SLIP-CRITICAL CONNECTIONS IN SEISMIC FORCE RESISTANCE SYSTEM (SFRS). SLIP-CRITICAL BOLTS SHALL HAVE CLASS "A" FAYING SURFACES. SLIP-CRITICAL JOINT ASSEMBLIES SHALL BE FULLY PRE- TENSIONED BY TURN-OF-NUT TIGHTENING, TENSION CONTROL CALIBRATED WRENCH TIGHTENING, TWIST- OFF BOLTS CONFORMING TO ASTM F3125 GRADE F1852, OR BY DIRECT TENSION INDICATOR TIGHTENING CONFORMING TO ASTM F959. (a) HIGH-STRENGTH BOLTS: STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 12" = 1'-0" 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 GENERAL NOTES S1.0.2 MCGUFF 03/11/25 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 (a)WHERE APPLICABLE, SEE SECTION 1705A.13 (b)SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK. (c)INSTALLATION OF ALL ADHESIVE ANCHORS IN HORIZONTAL AND UPWARDLY INCLINED POSITIONS SHALL BE PERFORMED BY AN ACI/CRSI CERTIFIED ADHESIVE ANCHOR INSTALLER, EXCEPT WHERE THE DESIGN TENSION ON THE ANCHORS IS LESS THAN 100 LBS AND THOSE ANCHORS ARE CLEARLY NOTED ON THE APPROVED CONSTRUCTION DOCUMENTS OR WHERE THE ANCHORS ARE SHEAR DOWELS ACROSS COLD JOINTS IN SLABS ON GRADE WHERE THE SLAB IS NOT PART OF THE LATERAL FORCE-RESISTING SYSTEM. TABLE 1705.3 OF CBC REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION TYPE CONTINUOUS SPECIAL INSPECTION PERIODIC SPECIAL INSPECTION REFERENCED STANDARD (a) 1. INSPECT AND TEST REINFORCEMENT, INCLUDING PRESTRESSING TENDONS, AND VERIFY PLACEMENT. X ACI 318: CH. 20, 25.2, 25.3, 25.5.1, 26.6.1-26.6.3, 26.13.1, 26.13.3.2, 26.13.3.3 2. REINFORCING BAR WELDING: AWS D1.4 ACI 318: 18.2.8, 25.5.7, 26.6.4,26.13.1.4, 26.13.3.2, 26.13.3.3 a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706.─X b. INSPECT SINGLE PASS FILLET WELDS, MAXIMUM 5/16”; NOT DEFINED IN 2.d OR 2.e X c. INSPECT ALL OTHER WELDS.X 3. INSPECT ANCHORS CAST IN CONCRETE.─X ACI 318: 17.8.2, 26.7.2, 26.8.2, 26.13.1, 26.13.3.3 4. INSPECT AND TEST ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS.(b) ACI 318: 17.8.2.4, 26.7.2, 26.13.1, 26.13.3.2 a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS. X b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a.X 5. VERIFY USE OF REQUIRED DESIGN MIX.ACI 318: CH.19, 26.4, 26.13.3.2 6. PRIOR TO AND DURING CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF THE CONCRETE. X ─ ASTM C31 ASTM C172 ACI 318: 26.4, 26.5, 26.12 7. INSPECT CONCRETE AND SHOTCRETE FOR PROPER APPLICATION TECHNIQUES.X ─ACI 318: 26.5, 26.13, ACI 506: 3.4 8. VERIFY MAINTENANCE OF SPECIFIC CURING TEMPERATURE AND TECHNIQUES.─X ACI 318: 26.5.3–26.5.5, 26.13.3.3 9. INSPECT PRESTRESSED CONCRETE FOR: ACI 318: 26.10.2, 26.13.1, 26.13.3.2 a. APPLICATION OF PRESTRESSING FORCES; AND X ─ b. GROUTING OF BONDED PRESTRESSING TENDONS.X ─ 10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.─X ACI 318: 26.9, 26.13.1, 26.13.3.3 11. FOR PRECAST CONCRETE DIAPHRAGM CONNECTIONS OR REINFORCEMENT AT JOINTS CLASSIFIED AS MODERATE OR HIGH DEFORMABILITY ELEMENTS (MDE OR HDE) IN STRUCTURES ASSIGNED TO SEISMIC DESIGN CATEGORY D, E OR F, INSPECT SUCH CONNECTIONS AND REINFORCEMENT IN THE FIELD FOR: ─X ACI 318: 26.13.1.3 12. INSPECT INSTALLATION TOLERANCES OF PRECAST CONCRETE DIAPHRAGM CONNECTIONS FOR COMPLIANCE WITH ACI 550.5 ─X ACI 318: 26.13.1.3 ─ ─ ─ ─ ─X a. REINFORCEMENT IN SPECIAL MOMENT FRAMES, BOUNDARY ELEMENTS OF SPECIAL STRUCTURAL WALLS AND COUPLING BEAMS. b. ALL OTHER REINFORCEMENT. ─ d. REINFORCING STEEL RESISTING FLEXURAL AND AXIAL FORCES IN INTERMEDIATE AND SPECIAL MOMENT FRAMES, AND BOUNDARY ELEMENTS AND COUPLING BEAMS OF SPECIAL STRUCTURAL WALLS OF CONCRETE AND SHEAR REINFORCEMENT. X ─ e. SHEAR REINFORCEMENT.X ─ ACI 318: 17.8.2, 26.7.2, 26.13.1, 26.1 3.3.2 ─X a. INSTALLATION OF THE EMBEDDED PARTS X ─ b. COMPLETION OF THE CONTINUITY OF REINFORCEMENT ACROSS JOINTS X ─ c. COMPLETION OF CONNECTIONS IN THE FIELD X ─ ACI 550.5 13. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF SHORES AND FORMS FROM BEAMS AND STRUCTURAL ─X ACI 318: 26.10.2, 26.11.2, 26.13.3.3 14. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED ─X ACI 318: 26.11.1.2(b), 26.13.3.3 SPECIAL INSPECTION AND TESTING 1. ALL WORK SHALL BE IN CONFORMANCE WITH ANY AND ALL TESTING, INSPECTION, QUALIFICATION, AND QUALITY ASSURANCE PROVISIONS AS REQUIRED BY THE CALIFORNIA BUILDING CODE AND ANY APPLICABLE STANDARDS (LATEST ADOPTED EDITION OF CURRENT CBC). 2. AN APPROVED TESTING AND INSPECTION AGENCY, RETAINED BY OWNER AND SATISFACTORY TO AOR/SEOR AND GOVERNING CODE AUTHORITY, SHALL PERFORM SPECIAL INSPECTIONS AND TESTS REQUIRED BY THIS CONTRACT AND IN ACCORDANCE WITH APPLICABLE CODE'S REQUIREMENTS. LABORATORIES CONDUCTING ANY SPECIAL INSPECTION, TESTING, OR OBTAINING, HANDLING, PREPARING, PROTECTING, TRANSPORTING OR STORING OF SAMPLES MUST BE ACCEPTED BY THE DSA LABORATORY EVALUATION AND ACCEPTANCE (LEA) PROGRAM. THESE SPECIAL INSPECTIONS AND TESTS ARE IN ADDITION TO THE INSPECTIONS REQUIRED BY CBC SECTION 110. AN APPROVED TESTING AND INSPECTION AGENCY IS A RECOGNIZED AGENCY REGULARLY ENGAGED IN CONDUCTING TESTS AND/OR FURNISHING INSPECTION SERVICES, WHERE SUCH AGENCY HAS BEEN APPROVED BY THE GOVERNING CODE AUTHORITY. 3. THE APPROVED TESTING AND INSPECTION AGENCY SHALL KEEP RECORDS OF ALL SPECIAL INSPECTIONS AND TESTS AND SHALL FURNISH REPORTS OF SPECIAL INSPECTIONS AND TESTS TO THE GOVERNING CODE AUTHORITY AND THE AOR/SEOR. REPORTS SHALL INDICATE WHETHER THE WORK INSPECTED OR TESTED WAS OR WAS NOT COMPLETED IN CONFORMANCE TO APPROVED CONSTRUCTION DOCUMENTS. DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF NOT CORRECTED, THE DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE GOVERNING CODE AUTHORITY AND THE ARCHITECT (STRUCTURAL ENGINEER) PRIOR TO THE COMPLETION OF THAT PHASE OF WORK. A FINAL REPORT DOCUMENTING REQUIRED SPECIAL INSPECTIONS AND TESTS, AND CORRECTION OF DISCREPANCIES, SHALL BE SUBMITTED UPON COMPLETION OF THAT PHASE OF WORK. 4. APPROVED TESTING AND INSPECTION AGENCY SHALL PERFORM SPECIAL INSPECTIONS AND TESTINGS IN ACCORDANCE WITH CBC SECTION 1705 AND WITH THIS SECTION FOR THE FOLLOWING WORK. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL TESTING AND INSPECTION REQUIREMENTS. A. STEEL CONSTRUCTION: PER TABLE 1705.2.1 OF CBC B. CONCRETE CONSTRUCTION: PER ATTACHED TABLE 1705.3 OF CBC 5. STRUCTURAL STEEL: (i)ALL WELDING SHALL BE IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY (AWS) STRUCTURAL WELDING CODE FOR STEEL AWS D1.1. (ii)WELDING PROCEDURE SPECIFICATIONS (WPS) SHALL BE SUB MITTED TO THE ENGINEER FOR APPROVAL, PRIOR TO THE BEGINNING OF WELDING OPERATIONS. THE WPS SHALL INCLUDE THE WELDING PARAMETERS RECOMMENDED BY THE ELECTRODE MANUFACTURER. SEE AWS D1.1 APPENDIX E, FORM E-1. JOINT DETAILS TO SUIT EXISTING CONDITIONS. THE WELDING ELECTRODE MANUFACTURER'S SPECIFICATIONS SHALL BE ATTACHED TO THE WPS. ALL WELDERS AND INSPECTORS SHALL BE INFORMED OF THE WPS AND SHALL RETAIN A COPY. (iii)SEE AWS FOR PREQUALIFIED SMAW WPS'S. (iv)SEE AWS FOR PREQUALIFIED FCAW WPS'S. (v)WELDING TO BE DONE BY WELDERS CERTIFIED BY AWS. (vi)ONLY SHIELDED METAL ARC WELDING (SMAW) WITH LOW HYDROGEN ELECTRODES OR FLUX CORE ARC WELDING (FCAW), EITHER GAS SHIELDED OF SELF SHIELDED, SHALL BE USED. FOR SMAW, THE TYPICAL REQUIREMENTS SHALL BE ACCORDING TO NOTE #3 ABOVE. WELDING PROCEDURES SHALL MEET THE REQUIREMENTS OF AWS D1.1 4.6.2, OR SHALL BE QUALIFIED BY TEST. FOR FCAW, THE TYPICAL REQUIREMENTS SHALL BE ACCORDING TO NOTE #5 ABOVE. THE WELDING PROCEDURE SHALL MEET THE REQUIREMENTS OF AWS D1.1. (vii)INDIVIDUAL WELDS SHALL BE CARRIED CONTINUOUSLY TO COMPLETION BEFORE THE JOINT IS ALLOWED TO COOL BELOW THE MINIMUM SPECIFIED PREHEAT AND INTERPASS TEMPERATURE. (viii) AT ALL COMPLETE PENETRATION WELDS, WELD BEADS SHALL BE PEENED AFTER EACH PASS, WITH THE EXCEPTION OF THE ROOT PASS AND THE SURFACES PASSES, AS FOLLOWS: TURN SLAG GUN 90 DEG. AND MAKE A MINIMUM OF 4 PASSES WITH DULL CHISEL. (ix)PREHEATING IS REQUIRED ON ALL TACK WELDS NOT INCORPORATED INTO FINAL WELDS. SEE AWS D1.1. (x)FOR BEAM FLANGE REINFORCEMENT PLATES, THE ROLLING DIRECTION OF GRAIN SHALL BE INDICATED ON THE PLATE AND INSTALLED SO THAT THE GRAIN DIRECTION IS PARALLEL TO THE LONGITUDINAL AXIS OF THE MEMBER. (xi)FULL TIME VISUAL INSPECTION BY AN AWS QC-1 QUALIFIED INSPECTOR IS REQUIRED FOR ALL WELDING. (xii)100% ULTRASONIC WELD TESTING BY THE INSPECTOR IS RE QUIRED FOR ALL COMPLETE-JOINT-PENETRATION WELDS. (xiii) AMPERAGE, VOLTAGE, POLARITY AND ELECTRODE STICK OUT SHALL BE VERIFIED TO BE IN COMPLIANCE WITH THE ELECTRODE MANUFACTURER'S RECOMMENDATIONS. (xiv) REMOVE BACKUP BARS AND WELD TABS AT ALL FLANGE COMPLETE-JOINT-PENETRATION (CJP) WELDS AT DUCTILE MOMENT FRAME CONNECTIONS. TYPICAL UNLESS NOTED OTHERWISE. 6.COLD-FORMED STEEL FRAMING: PERIODIC SPECIAL INSPECTION IS REQUIRED DURING WELDING OPERATION OF ELEMENTS OF THE SLRS. PERIODIC INSPECTION IS REQUIRED FOR SCREW ATTACHMENT, BOLTING, ANCHORING AND OTHER FASTENING OF COMPONENTS WITHIN THE SFRS, INCLUDING STRUTS, BRACES, AND HOLD-DOWNS. 7.MECHANICAL AND ELECTRICAL COMPONENTS: SPECIAL INSPECTION FOR MECHANICAL AND ELECTRICAL EQUIPMENT AS FOLLOWS: (i) PERIODIC SPECIAL INSPECTION IN REQUIRED DURING THE ANCHORAGE OF ELECTRICAL EQUIPMENT FOR EMERGENCY OR STANDBY POWER SYSTEMS. (ii)PERIODIC SPECIAL INSPECTION IS REQUIRED DURING THE INSTALLATION OF VIBRATION ISOLATION SYSTEM WHERE THE CONSTRUCTION DOCUMENTS REQUIRED A NOMINAL CLEARANCE OF 0.25 INCH OR LESS BETWEEN THE EQUIPMENT AND THE SUPPORT FRAME AND RESTRAINT. MATERIALS AND SYMBOLS LFRS STEEL LATERAL FORCE RESISTING SYSTEM, SEE SHEET S001 AND SPECIFICATIONS SHEET REFERENCE SECTION OR DETAIL FULL HEIGHT SECTION WALL OR FRAME ELEVATION FINISH ELEVATION SHEET REFERENCE NUMBER REFERENCE SHEET REFERENCE NUMBER REFERENCE REFER TO PLANS FOR DATUM NUMBER REFERENCE MATERIALS CONCRETE CONCRETE BLOCK EARTH SYMBOLS STEEL STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 12" = 1'-0" 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 GENERAL NOTES S1.0.3 MCGUFF 03/11/25 ABBREVIATIONS A AB ANCHOR BOLT ADDL ADDITIONAL ADJ ADJACENT AFF ABOVE FINISH FLOOR ALT ALTERNATE ARCH ARCHITECT(URAL) B BLDG BUILDING BLKG BLOCKING BM BEAM BN BOUNDARY NAILING BO BOTTOM OF BOTT, (B) BOTTOM BTWN BETWEEN C C CAMBER CIP CAST IN PLACE CJ CONTROL/CONSTRUCTION JOINT CJP, CP COMPLETE JOINT PENETRATION CL CENTERLINE CLG CEILING CLR CLEAR CMU CONCRETE MASONRY UNIT COL COLUMN CONC CONCRETE CONN CONNECTION CONT CONTINUOUS CTR(D) CENTER(ED) CY CUBIC YARDS D DB BAR DIAMETER DBL DOUBLE DC DEMAND CRITICAL DEMO DEMOLISH, DEMOLITION DIA, DIAM DIAMETER DIAG DIAGONAL DIM DIMENSION DO DITTO DWG DRAWING E EA EACH EF EACH FACE EJ EXPANSION JOINT ELEC ELECTRICAL ELEV ELEVATION, ELEVATOR EMBED EMBEDMENT EN EDGE NAIL EO EDGE OF EQ EQUAL EQUIP EQUIPMENT ES EACH SIDE EW EACH WAY EXIST, (E) EXISTING EXP EXPANSION EXT EXTERIOR F FLR FLOOR FN FIELD NAILING FND FOUNDATION FO FACE OF FS FAR SIDE FT FOOT, FEET FTG FOOTING G GA GAUGE GALV GALVANIZED GC GENERAL CONTRACTOR GLBM, GB GLUED-LAMINATED BEAM GR GRADE GRBM GRADE BEAM H HK HOOK HORIZ HORIZONTAL HS HIGH STRENGTH HSS HOLLOW STRUCTURAL SECTION HT HEIGHT I ID INSIDE DIAMETER IN INCH INT INTERIOR ABBREVIATIONS J JT JOINT K K, KIP(S) KILOPOUND KLF KIPS PER LINEAR FOOT KSF KIPS PER SQUARE FOOT KSI KIPS PER SQUARE INCH L L ANGLE LB, LBS POUND(S) LF LINEAR FEET LFRS LATERAL FORCE RESISTING SYSTEM LLH LONG LEG HORIZONTAL LLV LONG LEG VERTICAL M MAX MAXIMUM MB MACHINE BOLT MECH MECHANICAL MFR MANUFACTURE MIN MINIMUM MW MEDIUM WEIGHT N (N) NEW NDT NON-DESTRUCTIVE TESTING NS NEAR SIDE NTS NOT TO SCALE NW(C) NORMAL WEIGHT (CONCRETE) O OC ON CENTER OD OUTSIDE DIAMETER OH OPPOSITE HAND OPP OPPOSITE P PAF, PDF POWDER DRIVEN/POWER ACTUATED FASTENER PJP, PP PARTIAL JOINT PENETRATION PL PLATE PLF POUND PER LINEAR FOOT PSF POUND PER SQUARE FOOT PSI POUND PER SQUARE INCH PT PRESSURE TREATED WOOD, POST/PRE-TENSIONED R R RADIUS REF REFERENCE REINF REINFORCING REQD REQUIRED S (S)EOR (STRUCTURAL) ENGINEER OF RECORD SC SLIP CRITICAL SCHED SCHEDULE SDS, SMS SELF-DRILLING / SHEET METAL SCREW SFRS SEISMIC FORCE RESISTING SYSTEM SIM SIMILAR SN SILL NAILING SOG SLAB ON GRADE SPECS SPECIFICATIONS SQ SQUARE SS STAINLESS STEEL STD STANDARD STIFF STIFFENER STL STEEL STRUCT STRUCTURAL SYM SYMMETRICAL T T&B TOP & BOTTOM TO TOP OF TYP TYPICAL U UNO UNLESS NOTED OTHERWISE V VERT VERTICAL VIF VERIFY IN FIELD W W/ WITH W/O WITHOUT WF WIDE FLANGE WP WORK POINT WT WEIGHT WWF WELDED WIRE FABRIC NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 FOR STRAIGHT BAR EMBEDMENT USE DEVELOPMENT LENGTH Ld FACE OF CONCRETE FACE OF CONC OR CONSTRUCTION JOINT TYPICAL EMBEDMENT DETAILS (3" CLR AT BOT OF FTG) 2" CLR (3" CLR AT BOT OF FTG) 2" CLR 1 6 MIN SLOPE TYPICAL OFFSET BEND (UNO) LAP SPLICE LENGTH PER SCHEDULE TYPICAL LAP SPLICE DETAIL FACE OF CONCRETE OFFSET BEND WHERE OCCURS/ REQUIRED CONTACT LAP SPLICE NON-CONTACT LAP SPLICE db db Lst 1d b MI N Lst /5 O R 6 " M A X 4db (2 1/2" MIN) 12 d b db db REINF CLEAR COVER AND CLEAR SPACING SPACING CLEARDIM "a" DI M " b " CLEAR COVER= LEAST OF DIM "a" & DIM "b" MINIMUM INSIDE BEND DIAMETER: 6db (3# THRU 8#) 8db (9# THRU 11#) 10db (14# THRU 18#) PE R G E N E R A L N O T E S SP E C I F I E D C L E A R C O V E R (3" CLR AT BOT OF FTG) 2" CLR Ld Ldh Ldt STRAIGHT BAR DEVELOPMENT LENGTH (Ld) SCHEDULE (IN) LONGITUDINAL REINFORCEMENT GRADE LONGITUDINAL REINFORCEMENT CONCRETE STRENGTH (f'c)CONCRETE STRENGTH (f'c) SIZE DIAMETER 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI GRADE 60 (60 KSI) #6 0.750 #7 0.875 #8 1.000 #9 1.128 #10 1.270 #11 1.410 DEVELOPMENT LENGTH SCHEDULE NOTES: 1. THIS SCHEDULE IS BASED ON DEVELOPMENT LENGTH FOR 1.0 x REINFORCEMENT YIELD STRENGTH NOT CONSIDERING THE EFFECT OF CONFINING REINFORCEMENT. 2. FOR HOOKED BARS AND HEADED DEFORMED BARS, CONDITION NOTED IN TABLE FOR SIDE COVER ALSO APPLIES TO HOOKED BARS TERMINATING INSIDE COLUMN CORE WITH SIDE COVER NORMAL TO PLANE OF HOOK ≥2.5 INCHES. 3. FOR HOOKED BARS AND HEADED DEFORMED BARS, WHERE SIDE COVER NORMAL TO PLANE OF HOOK IS LESS THAN 6 db OR WHERE HOOKED BARS TERMINATING INSIDE COLUMN CORE WITH SIDE COVER NORMAL TO PLANE OF HOOK IS LESS THAN 2.5 INCHES, MULTIPLY THE TABULATED DEVELOPMENT LENGTH BY 1.25. 4. HOOKED OR HEADED DEFORMED BAR MAY BE USED WHERE STRAIGHT DEVELOPMENT CAN NOT BE ACHIEVED. 5. db IS NOMINAL DIAMETER OF REINFORCEMENT. 6. FOR LIGHT-WEIGHT CONCRETE, MULTIPLY TABULATED DEVELOPMENT LENGTH FOR STRAIGHT DEVELOPMENT LENGTH AND STANDARD HOOKED LENGTH BY 1.33. 7. TABULATED VALUES ARE FOR UNCOATED OR ZINC-COATED (GALVANIZED) REINFORCEMENT. 8. THESE TABLES DO NOT APPLY TO SPECIAL REINFORCED CONCRETE SHEAR WALLS. 9. TOP BARS AS NOTED IN THE SCHEDULE REFERS TO HORIZONTAL REINFORCING WITH MORE THAN 12" OF CONCRETE PLACED BELOW REINFORCING BAR. 10. HEADED DEFORMED BARS SHALL BE HRC 555 (ICC ESR-2935) OR APPROVED EQUIVALENT. #5 0.625 STANDARD HOOK (90° OR 180°) DEVELOPMENT LENGTH (Ldh) SCHEDULES (IN) LONGITUDINAL REINFORCEMENT GRADE LONGITUDINAL REINFORCEMENT CONCRETE STRENGTH (f'c)CONCRETE STRENGTH (f'c) SIZE DIAMETER 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI GRADE 60 (60 KSI) #6 0.750 #7 0.875 #8 1.000 #9 1.128 #10 1.270 #11 1.410 HEADED DEFORMED BAR DEVELOPMENT LENGTH (Ldt) SCHEDULE (IN) LONGITUDINAL REINFORCEMENT GRADE LONGITUDINAL REINFORCEMENT CONCRETE STRENGTH (f'c)CONCRETE STRENGTH (f'c) SIZE DIAMETER 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI GRADE 60 (60 KSI) #6 0.750 #7 0.875 #8 1.000 #9 1.128 #10 1.270 #11 1.410 #5#5 0.625 0.625 REINFORCEMENT CLEAR SPACING ≥5db AND REINFORCEMENT CLEAR COVER ≥2.5db 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI TOP BARS OTHER BARS 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI CONCRETE STRENGTH (f'c) 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI TOP BARS TOP BARSOTHER BARS OTHER BARS REINFORCEMENT CLEAR SPACING ≥3.0db AND REINFORCEMENT CLEAR COVER ≥1.4db db ≤REINFORCEMENT CLEAR SPACING < 3.0db OR SPECIFIED CLEAR COVER ≤REINFORCEMENT CLEAR COVER < 1.4db LAP SPLICE (Lst) SCHEDULE (IN) LONGITUDINAL REINFORCEMENT GRADE LONGITUDINAL REINFORCEMENT CONCRETE STRENGTH (f'c)CONCRETE STRENGTH (f'c) SIZE DIAMETER 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI GRADE 60 (60 KSI) #6 0.750 #7 0.875 #8 1.000 #9 1.128 #10 1.270 #11 1.410 #5 0.625 REINFORCEMENT CLEAR SPACING ≥5db AND REINFORCEMENT CLEAR COVER ≥2.5db 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI TOP BARS OTHER BARS 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI CONCRETE STRENGTH (f'c) 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI 3,000 PSI 4,000 PSI 5,000 PSI 6,000 PSI 7,000 PSI 8,000 PSI TOP BARS TOP BARSOTHER BARS OTHER BARS REINFORCEMENT CLEAR SPACING ≥2.5db AND REINFORCEMENT CLEAR COVER ≥1.25db db ≤REINFORCEMENT CLEAR SPACING < 2.5db OR REINFORCEMENT CLEAR COVER < 1.25db CENTER-TO-CENTER SPACING OF HOOKED BAR < 6db ; AND, SIDE COVER (NORMAL TO PLANE OF HOOK) ≥6db (SEE NOTES 3 & 4) CENTER-TO-CENTER SPACING OF HOOKED BAR ≥6db ; AND, SIDE COVER (NORMAL TO PLANE OF HOOK) ≥6db (SEE NOTES 3 & 4) CENTER-TO-CENTER SPACING OF 5db ≤HEADED DEFORMED BAR < 6db ; AND, SIDE COVER (NORMAL TO PLANE OF HOOK) ≥6db (SEE NOTES 3 & 4) CENTER-TO-CENTER SPACING OF HEADED DEFORMED BAR ≥6db ; AND, SIDE COVER (NORMAL TO PLANE OF HOOK) ≥6db (SEE NOTES 3 & 4) LAP SPLICE SCHEDULE NOTES: 1. THIS SCHEDULE IS BASED ON LAP SPLICE FOR 1.0 x REINFORCEMENT YIELD STRENGTH NOT CONSIDERING THE EFFECT OF CONFINING REINFORCEMENT. 2. REINFORCEMENT CLEAR COVER FOR STRAIGHT BAR DEVELOPM ENT IS BASED ON THE SMALLER VALUE ON BOTH SIDES. 3. FOR HOOKED BARS AND HEADED DEFORMED BARS, CONDITION NOTED IN TABLE ABOVE FOR SIDE COVER ALSO APPLIES TO HOOKED BARS TERMINATING INSIDE COLUMN CORE WITH SIDE COVER NORMAL TO PLANE OF HOOK ≥2.5 INCHES. 4. FOR HOOKED BARS AND HEADED DEFORMED BARS, WHERE SIDE COVER NORMAL TO PLANE OF HOOK IS LESS THAN 6 db OR WHERE HOOKED BARS TERMINATING INSIDE COLUMN CORE WITH SIDE COVER NORMAL TO PLANE OF HOOK IS LESS THAN 2.5 INCHES, MULTIPLY THE TABULATED DEVELOPMENT LENGTH BY 1.25. 5. MECHANICAL SPLICE TYPE 2 MAY BE USED IN LIEU OF STRAIGHT LAP SPLICE BARS. MECHANICAL SPLICES SHALL BE nVENT (IAMPO ER-0129) OR APPROVED EQUIVALENT AND SHALL COMPLY WITH REQUIREMENTS OF ACI 318. 6. db IS NOMINAL DIAMETER OF REINFORCEMENT. 7. FOR LIGHT-WEIGHT CONCRETE, MULTIPLY TABULATED DEVELOPMENT LENGTH FOR STRAIGHT DEVELOPMENT LENGTH AND STANDARD HOOKED LENGTH BY 1.33. 8. TABULATED VALUES ARE FOR UNCOATED OR ZINC-COATED (GALVANIZED) REINFORCEMENT. 9. THESE TABLES DO NOT APPLY TO SPECIAL REINFORCED CON CRETE SHEAR WALLS. 10. TOP BARS AS NOTED IN THE SCHEDULE REFERS TO HORIZONTAL REINFORCING WITH MORE THAN 12" OF CONCRETE PLACED BELOW REINFORCING BAR. 11. WHERE BARS OF DIFFERENT SIZES ARE LAP SPLICED, SPLICE LENGTH SHALL BE THE LARGER OF THE DEVELOPMENT LENGTH OF THE LARGER BAR AND THE LAP SPLICE LENGTH OF THE SMALLER BAR. 12. LAP SPLICES SHALL NOT BE USED FOR BARS LARGER THAN #11. 13. LAP SPLICES OF BARS IN A BUNDLE SHALL BE BASED ON THE LAP SPLICE LENGTH REQUIRED FOR INDIVIDUAL BARS WITHIN A BUNDLE. INCREASE 20 PERCENT FOR THREE-BAR BUNDLE, AND 33 PERCENT FOR FOUR-BAR BUNDLE. INDIVIDUAL BAR SPLICES WITHIN A BUNDLE SHALL NOT OVERLAP. ENTIRE BUNDLES SHALL NOT BE LAP SPLICED. #4 #4 #4 #4 0.500 22 26 38 43 49 55 18 61 19 23 33 37 42 47 15 53 17 20 29 34 38 43 14 47 16 19 27 31 35 39 13 43 14 17 25 28 32 36 12 40 14 16 23 27 30 34 12 37 17 20 29 33 38 42 14 47 15 18 25 29 33 37 12 41 16 23 26 29 33 36 14 21 24 27 30 33 14 19 22 25 28 31 14 18 21 23 26 29 31 37 54 62 69 78 25 87 27 32 47 53 60 68 22 75 24 29 42 48 54 61 19 67 22 26 38 44 49 55 18 61 20 24 35 40 46 51 16 57 19 23 33 38 43 48 15 53 24 29 42 47 53 60 19 67 21 25 36 41 46 52 17 58 19 22 32 37 42 47 15 52 17 20 30 34 38 43 14 47 16 19 27 31 35 40 13 44 15 18 26 29 33 37 12 41 54 65 94 107 121 136 43 151 47 56 81 93 105 118 37 131 42 50 73 83 94 106 34 117 38 46 67 76 86 96 31 107 35 42 62 70 79 89 28 99 33 40 58 66 74 84 27 93 33 42 50 72 83 93 116 36 43 63 72 81 91 29 101 32 39 56 64 72 81 26 90 30 35 51 59 66 74 24 82 27 33 48 54 61 69 22 76 26 31 45 51 57 64 21 71 12 12 12 12 13 12 12 12 105 0.500 28 34 49 56 63 71 23 79 25 29 43 49 55 62 20 68 22 26 38 44 49 55 18 61 20 24 35 40 45 50 16 56 19 22 32 37 42 47 16 52 18 21 30 35 39 44 16 48 22 26 38 43 49 55 18 61 19 23 33 37 42 47 16 53 20 29 34 38 43 47 19 27 31 35 39 43 17 25 28 32 36 40 16 23 27 30 34 37 40 48 70 80 90 101 32 112 35 42 61 69 78 88 28 97 31 37 54 62 70 79 25 87 29 34 50 57 64 72 23 80 26 32 46 52 59 66 21 74 25 30 43 49 55 62 20 69 31 37 54 62 69 78 25 87 27 32 47 53 60 68 22 75 24 29 42 48 54 61 19 67 22 26 38 44 49 55 18 61 20 24 35 40 46 51 16 57 19 23 33 38 43 48 16 53 70 84 122 139 157 177 56 196 61 73 106 121 136 153 49 170 54 65 95 108 122 137 44 152 50 59 86 99 111 125 40 139 46 55 80 91 103 116 37 129 43 52 75 86 96 108 35 120 43 54 65 94 107 121 151 47 56 81 93 105 118 37 131 42 50 73 83 94 106 34 117 38 46 67 76 86 96 31 107 35 42 62 70 79 89 28 99 33 40 58 66 74 84 27 93 16 16 16 16 17 16 16 16 136 0.500 13 17 21 26 31 37 10 43 12 16 20 24 29 35 9 41 12 15 19 24 28 33 9 39 12 15 19 23 27 33 8 38 11 14 18 21 25 30 8 35 10 13 16 20 24 28 7 33 8 11 14 16 20 23 6 27 8 10 13 15 18 22 6 26 10 12 15 18 21 25 10 12 15 17 21 24 9 11 14 16 19 22 8 10 13 15 18 21 6 6 6 6 8 7 7 7 0.500 10 13 16 19 23 27 7 32 9 12 15 18 22 26 7 30 9 11 14 17 21 25 6 29 9 11 14 17 20 24 6 28 8 10 13 16 19 22 6 26 8 10 12 15 18 21 6 24 8 10 12 14 17 20 8 9 11 14 16 19 7 9 11 13 16 18 7 9 11 13 15 18 7 8 10 12 14 17 6 8 9 11 13 15 6 6 6 6 6 6 6 6 6 6 6 6 STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 As indicated 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 TYPICAL CONCRETE DETAILS S1.1.1 MCGUFF 01/02/25 SCALE: 1" = 1'-0"S1.1.1 TYPICAL REINFORCEMENT DEVELOPMENT LENGTH AND LAP SPLICE SCHEDULES 1 DETAIL ID: CON-RBAR-01 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 TYPICAL ANCHOR INSTALLATION DESIGN AND TEST VALUES BOLT DIAMETER MIN EFFECTIVE EMBEDMENT MIN HOLE DEPTH 3/8" 2" 2 3/4" MIN MEMBER THICKNESS 4" INSTALLATION TORQUE CARBON STEEL 30 FT-LBS 1/2" 2" 2 3/4" 4" 5/8" 3 1/4" 4 1/4" 5" 3/4" 3 3/4" 4 3/4" 6" 3 1/4" 4 1/4" 6" 4" 4 3/4" 6" 4 3/4" 5 3/4" 8" 50 FT-LBS 40 FT-LBS 110 FT-LBS ANCHOR AT WALL OR SLAB 1" MIN HOLE DEPTH USE STEEL PIECE AS TEMPLATE ANCHOR RELOCATION DETAIL RELOCATE HOLE SLIGHTLY 1/4 1/4 OPPOSITE EDGES EDGE OF STEEL PLATE 3" SQx1/4" PLATE NOTES: RELOCATE BOLT IF REQ'D TO CLEAR REINFORCING STEEL. UNLESS NOTED/ REFERENCED ON THE DETAILS/DRAWINGS, POST INSTALLED ANCHORS SHALL BE USED TO REPLACE CAST-IN-PLACE ANCHORS CONC NOTES: 1. ALLOWABLE EXPANSION ANCHOR TYPES: HILTI KB-TZ2 (ICC ESR-4266). 2. UNO INSTALL ANCHORS PER MANUFACTURER'S RECOMMENDED SPECIFICATIONS. 3. THE TABULATED INSTALLATION AND TEST VALUES PERTAIN TO USE IN HARDROCK CONCRETE, LIGHT-WEIGHT CONCRETE AND CONCRETE FILL OVER METAL DECK. CONCRETE FILL OVER METAL DECK SHALL CONSIST OF 20GA MINIMUM METAL DECK WITH EITHER HARD ROCK OR LIGHT WEIGHT CONCRETE. CONCRETE SHALL HAVE A MINIMUM STRENGTH OF 3000 PSI. 4. WHEN INSTALLING DRILLED-IN ANCHORS IN NON-PRESTRESSED REINFORCED CONCRETE, USE CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE REINFORCING BARS OR OTHER EMBEDDED ITEMS SUCH AS ELECTRICAL/TELECOMMUNICATIONS CONDUIT AND GAS LINES. WHEN INSTALLING DRILL-IN ANCHORS INTO PRESTRESSED CONCRETE (PRE OR POST-TENSIONED), LOCATE TENDONS DURING INSTALLATION BY USING A NON- DESTRUCTIVE METHOD PRIOR TO INSTALLATION. EXERCISE EXTREME CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE TENDONS DURING INSTALLATION. MAINTAIN A MINIMUM CLEARANCE OF ONE INCH BETWEEN THE REINFORCEMENT AND THE DRILLED-IN ANCHOR. 5. DRILLED EXPANSION TYPE ANCHOR BOLTS SHALL BE USED ONLY WHERE DETAILED OR FOR ATTACHMENT OF MECH, ELECTRICAL, OR MISC ACCESSORIES OR EQUIPMENT TO THE STRUCTURE. 6. WHERE EDGE DISTANCE AND SPACING IS NOT SHOWN ON DETAILS, REFER ICC ESR REPORT FOR MINIMUM VALUES. WHERE SPECIFIED ANCHOR EMBEDMENT DEPTH, SPACING OR EDGE DISTANCE CANNOT BE PROVIDED, NOTIFY SEOR AND IOR PRIOR TO INSTALLATION. 7. SPECIAL INSPECTION REQUIRED PER CBC TABLE 1705.3. 8. USE STAINLESS STEEL ANCHORS FOR CONDITIONS EXPOSED BUILDING EXTERIOR, MOISTURE, AND WHERE SPECIFIED. INSTALLATION TORQUE STAINLESS STEEL 30 FT-LBS 40 FT-LBS 60 FT-LBS 125 FT-LBS EMBEDMENT REBAR SIZE, ASTM A615 GRADE 60 1/2" 5/8" MIN HOLE DIAM #3 #4 3/4"#5 1"#6 MIN DEPTH DOWEL NOTES: 1. ALLOWABLE EPOXY TYPES: HILTI RE 500 V3 (ICC ESR-3814), HILTI HIT-HY 200 (ICC ESR-3187) 2. UNO INSTALL PER MANUFACTURER'S RECOMMENDED SPECIFICATIONS. HOLE SHALL BE THOROUGHLY CLEANED AND ANCHOR SHALL BE FREE OF ANY MATERIAL THAT SHALL IMPAIR BOND TO CONCRETE. 3. THE TABULATED INSTALLATION AND TEST VALUES PERTAIN TO USE IN HARDROCK CONCRETE WITH A MINIMUM STRENGTH OF 3,000 PSI. 4. WHEN INSTALLING DRILLED-IN ANCHORS IN NON-PRESTRESSED REINFORCED CONCRETE, USE CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE REINFORCING BARS OR OTHER EMBEDDED ITEMS SUCH AS ELECTRICAL/TELECOMMUNICATIONS CONDUIT AND GAS LINES. WHEN INSTALLING DRILL-IN ANCHORS INTO PRESTRESSED CONCRETE (PRE OR POST-TENSIONED), LOCATE TENDONS DURING INSTALLATION BY USING A NON- DESTRUCTIVE METHOD PRIOR TO INSTALLATION. EXERCISE EXTREME CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE TENDONS DURING INSTALLATION. MAINTAIN A MINIMUM CLEARANCE OF ONE INCH BETWEEN THE REINFORCEMENT AND THE DRILLED-IN ANCHOR. 5. DRILLED EPOXY ANCHORS SHALL BE USED ONLY WHERE DETAILED. 6. WHERE SPECIFIED ANCHOR EMBEDMENT DEPTH, SPACING OR EDGE DISTANCE CANNOT BE PROVIDED, NOTIFY SEOR AND IOR PRIOR TO INSTALLATION. 7. SPECIAL INSPECTION REQUIRED PER CBC TABLE 1705.3. 8. INSTALLERS PLACING HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS ADHESIVE ANCHORS SHALL BE CERTIFIED BY ACI OR APPROVED EQUIVALENT. 9. ALL TESTS SHALL BE PERFORMED IN THE PRESENCE OF THE SPECIAL INSPECTOR OR INSPECTOR OF RECORD. 10. FOR LOCATIONS WHERE TENSION TEST VALUES ARE NOT SPECIFIED IN THE DRAWINGS, CONSULT WITH THE SEOR. 11. TESTING OF EPOXY DOWELS AT JOINTS BETWEEN NEW AND EXISTING SLABS-ON-GRADE OR #3 BARS AT CONCRETE CURBS IS NOT REQUIRED. 12. EPOXY DOWELS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. 3" 4" 6" 12" 2.8 KIPS 4.4 KIPS 5.8 KIPS 8.5 KIPS (PER SCHEDULE) MIN DIAM OF HOLE (PER SCHEDULE) MINIMUM DEPTH OF HOLE FACE OF EXISTING CONC SLOPED HOLE WHERE INDICATED NOTES: UNLESS NOTED/ REFERENCED ON THE DETAILS/DRAWINGS, EPOXY ANCHORS SHALL NOT BE USED TO REPLACE CAST-IN-PLACE ANCHORS. (TYP) 22.5° THREADED ROD DIAMETER, ASTM A36 TENSION TEST LOAD MIN HOLE DIAM MIN DEPTH TENSION TEST LOAD #7 #8 #9 1 1/8" 1 1/4" 1 3/8" 16" 18" 21" 5/8" 3/4" 7/8" 1/2" 1" 1 1/4" 8" 10" 11 1/4" 11.7 KIPS 13.8 KIPS 23.0 KIPS 9/16" 11/16" 13/16" 15/16" 3 1/2" 4 1/2" 6" 6 3/4" 2.5 KIPS 4.3 KIPS 5.8 KIPS 9.0 KIPS 1 1/16" 1 5/16" 11.5 KIPS 19.4 KIPS 22.9 KIPS 3/8"7/16" db EPOXY REINF BAR REINF BAR BACK-UP ANGLE 1/8" 60° REINF BAR REINF BAR BACK-UP ANGLE 1" MIN PER SCHED WELD LENGTH 1" MIN SECTION REINF BAR MIN 1/16" STRUCTURAL STEEL STL PL NOTES: 1. WELDING OF REINFORCING STEEL: FIELD WELDING OF REINFORCING SHALL BE PERFORMED BY WELDERS SPECIFICALLY CERTIFIED FOR REINFORCING STEEL. PRIOR TO WELDING, THE CARBON EQUIVALENT (CE) OF STEEL SHALL BE DETERMINED. A CERTIFIED MILL TEST REPORT WILL SATISFY THIS REQUIREMENT. REINFORCING STEEL WHOSE CE CANNOT BE IDENTIFIED OR WHOSE CE EXCEEDS 0.75% SHALL NOT BE WELDED. REINFORCING STEEL SHALL BE PREHEATED ACCORDING TO AWS REQUIREMENTS. IN ADDITION, STEEL WITH CE BETWEEN 0.66% and 0.75% SHALL BE WELDED ONLY WHERE PRIOR QUALIFICATION TESTS VERIFY ACCEPTABLE WELDABILITY. CARBON EQUIVALENCY DETERMINATION IS WAIVED FOR REINFORCING STEEL CONFORMING TO ASTM A706. 2. WELDING OF REBAR PERMITTED WHERE SPECIFICALLY DETAILED PER DRAWINGS. 3. PRIOR APPROVAL BY SEOR REQUIRED WHERE REBAR WELDING IS REQUESTED BY GC. 4. VERIFY WITH THE GOVERNING AGENCY THAT WELDS ARE PREQUALIFIED BEFORE PROCEEDING WITH THE WORK. GC IS RESPONSIBLE FOR REQUIRED TESTS NEEDED FOR QUALIFICATION. 5.#8 BAR & LARGER SHALL BE BUTT WELDED. 6.NO WELDING WITHIN 1" OF BEGINNING OF BAR BEND. LAP WELD SCHEDULE BAR SIZE WELD DIAGRAM WELD LENGTH (EACH SIDE) #3 #4 #5 #6 #7 2" 3 " 3 1/2" 4 1/2" 5" BUTT WELD SECTIONSECTION REBAR TO REBAR REBAR TO REBAR REBAR PARALLEL TO STRUCTURAL STEEL A1 C1 C1 D WELD W/ LOW HYDROGEN ELECTRODES SEE SCHED BELOW (TYP) REBAR PERPENDICULAR TO STRUCTURAL STEEL LOW HYDROGEN ELECTRODES COMPLETE PENETRATION REINF BAR MAX 1/8" CHIP OR GRIND ROOT TO SOUND METAL BEFORE WELDING SECOND SIDE HORIZ OR VERT BAR 1" MIN PER SCHED WELD LENGTH 1" MIN REINF BAR B1 B1 REBAR PARALLEL TO STRUCTURAL STEELA B C D E A1 B1 C1 A1 B1 A1 MIN 1/16" MAX 1/8" 45° #8 #9 #10 5 1/2" 6 1/2" 7" B1 MIN 1" CLR db/3 db/3db db/3 db BUTT WELD 6" MIN, STAGGER OVERLAPS AT ADJACENT TIES CIRCULAR TIE COLUMN AND BEAM TIE ALTERNATE BEAM STIRRUP STANDARD HOOK (TYP) STAGGER 90º AND 135º HOOKS AT ADJACENT TIES 90º BEND 180º BEND135º BEND NOTES: 1. MINIMUM INSIDE BEND DIAMETER: 4db FOR #3 TO #5 6db FOR #6 TO #8 2. CONTINUOUS LONGITUDINAL BAR SHALL BE LOCATED AT INSIDE RADIUS OF ALL HOOKS AND BARS. db db 4 db (2 1/2" MIN) MINIMUM INSIDE BEND DIAMETER 6db(3" M I N ) 6db OR 3" MIN (#3 TO #5) 12db (#6 TO #8) MAX 45° #4@12" OC EDGE OF SLAB A 1 1 FIRST POUR 60'-0" MAX SECOND POUR 60'-0" MAX CONSTRUCTION JOINT B CONTROL JOINT SAWCUT CONTROL JOINT NOTE: SAWCUT SHALL BE PERFORMED AS SOON AS SLAB WILL ACCEPT CUT WITHOUT RAVELING OR 12 HOURS AFTER POUR, WHICHEVER OCCURS FIRST. C CURBS AND DEPRESSIONS D CONC CURB WHERE OCCURS PER ARCH SIZE, LOCATION AND EXTENT OF CURBS, PER ARCH DWGS (WHERE OCCURS) 1'-0" 1' - 0" 2' - 6"1" COVER PER PLANS MIN 8" 1' - 0" 6"6" 1' - 0" 5" MAX CLR 2" CLR 3" 8" EQEQ (U N O ) FINISH GRADE PER CIVIL/ARCH CONT #4 ADDED BAR CONT SHEAR KEY 1 1/2" DEEP (4" MIN) SEE ARCH MIN 1' - 0" MIN 1' - 0" EQ EQ (8" MAX) SEE ARCH STANDARD HOOK SEE FOR BALANCE OF INFO NOT SHOWN NOTE: SIZE, LOCATION AND EXTENT OF CURBS AND DEPRESSIONS PER ARCH DWGS. EQ EQ d/4 d 8 S1.1.2 NOTES: 1.COORDINATE WIDTH, HEIGHT AND LOCATION OF CURBS WITH ARCHITECTURAL DRAWINGS. 2. SLAB-ON-GRADE REINF NOT SHOWN FOR CLARITY. REFER TO PLAN FOR REQUIRED REINFORCING. #4 @12"OC (2)#4 CONT PER PLAN (8" MAX) SEE ARCH 8" UNO 4" MIN EQ EQ ADDED #4 ROUGHEN SURFACE CLR 3" EQEQ LAP 18" MIN SAWCUT AND REMOVE EXISTING SLAB AS REQUIRED FOR INSTALLATION OF UTILITY LINES (E)SOG CONCRETE SLAB SEE NOTE 5 4" MIN SEE NOTE 4 UTILITY LINE AS REQUIRED NOTES: 1. VERIFY IN FIELD ALL (E)INFORMATION. 2. SAW-CUTTING SHALL BE AVOIDED NEAR ANY OF THE (E)PAD FOOTINGS, GRADE BEAMS AND CONT FOOTINGS. 3. WHERE REPLACEMENT OF WATERPROOFING IS REQUIRED BELOW THE SLAB ON GRADE, SAW CUT AN ADDITIONAL WIDTH OF SLAB ON GRADE AS REQUIRED WITHOUT DAMAGING THE EXISTING WATERPROOFING. 4. BACKFILL WITH CONTROLLED COMPACTED FILL OR LEAN CONCRETE AT CONTRACTOR'S OPTION OR PER RECOMMENDATIONS FROM GEOTECHNICAL REPORT IF AVAILABLE. 5. REBAR TO MATCH (E)SIZE AND SPACING IN BOTH DIRECTIONS (#4@18"OC MIN). HOOK BARS WHERE LAP CANNOT BE ACHIEVED. INSTALL REBAR IN EPOXY ADHESIVE PER TYPICAL EPOXY DETAIL. SPECIAL INSPECTION IS NOT REQUIRED UNLESS NOTED ON THE PLANS. 6. FOR ANY SLAB ON GRADE SAW-CUTTING THAT IS NOT SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO THE ARCHITECT SHOWING LOCATION, WIDTH, DEPTH AND LENGTH OF TRENCH PRIOR TO CUTTING THE SLAB. SIZE OF TRENCH WILL BE AS REQ'D BY ELECTRICAL OR PLUMBING. STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 As indicated 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 DETAILS S1.1.2 MCGUFF 11/22/24 RB SCALE: 1" = 1'-0"S1.1.2 TYPICAL HILTI CONCRETE EXPANSION ANCHOR DETAIL 2 DETAIL ID: CON-HILTI-01 SCALE: 1" = 1'-0"S1.1.2 TYPICAL HILTI EPOXY DOWEL ANCHOR DETAIL 4 DETAIL ID: CON-HILTI-03 SCALE: 12" = 1'-0"S1.1.2 TYPICAL WELDED REINFORCING BARS DETAILS 6 DETAIL ID: CON-RBAR-02 SCALE: 1" = 1'-0"S1.1.2 TYPICAL REBAR STIRRUP, TIE AND HOOP BEND DETAILS 7 DETAIL ID: CON-RBAR-03 SCALE: 1" = 1'-0"S1.1.2 TYPICAL SLAB-ON-GRADE DETAILS 12 DETAIL ID: CON-SOGD-03 SCALE: 1" = 1'-0"S1.1.2 TYPICAL CURB-ON-GRADE DETAIL 8 DETAIL ID: CON-PDCB-02 SCALE: 1 1/2" = 1'-0"S1.1.2 TYPICAL TRENCH AT (E) SLAB ON GRADE 14 DETAIL ID: ECON-TRENCH-01 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 OPEN SILL PER SCHEDULE LATERAL BRIDGING WHERE REQUIRED PER TYPICAL DETAIL NOTES: 1. REFER TO S00 SERIES FOR GENERAL NOTES. 2. PROVIDE 16 GA STUDS MINIMUM WHERE EQUIPMENTS, CABINETS, ELECTRICAL PANELS, ETC ARE ATTACHED TO STUDS. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR LOCATIONS. PROVIDE BACKING PER TYPICAL DETAIL. 3. WHERE WALLS HAVE CABINETS / CASEWORK ON BOTH SIDES, USE SPACING 12" OC WHERE 16" OC CALLED OUT. 4. TOP & BOTTOM TRACK SIZE TO MATCH WALL STUDS. TOP & BOTTOM TRACK SHALL BE 1 GAUGE HEAVIER THAN WALL STUDS. 5. AT FULL HT TRACK FOR TYPE "C" JAMB, STOP TRACK 2" FROM FLOOR AND TOP TRACK TO AVOID INTERFERENCE WITH SILL AND TOP TRACK S. 6. REFER TO ARCHITECTURAL SPECIFICATIONS AND DRAWINGS FOR WALL THICKNESSES. 7. CONTRACTOR MAY USE PRO-X HEADERS (IAPMO REPORT # 0286) AT INTERIOR NON-LOAD BEARING CONDITIONS IN LIEU OF THIS DETAIL. FOLLOW ALL REQUIREMENTS AND ATTACH TO JAMB STUDS PER ICC REPORT. 8. INTERIOR STUD WALLS ARE DESIGNED TO LIMIT STUD DEFLECTION TO L/240, WHERE L IS DEFINED AS THE STUD SPAN BETWEEN LATERALLY RESTRAINED POINTS. 9. METAL STUD SIZES ARE IDENTIFIED AS NOTED BELOW: DIAGRAMATIC INTERIOR METAL STUD WALL ELEVATION INTERIOR METAL STUD WALL SCHEDULE STUD DEPTH STUD DESIGNATION 3 5/8"362S162-33 @ 16" OC 8"800S162-43 @ 16" OC 600 S 162 -54 INDICATES SECTION THICKNESS (54 = 16GA) INDICATES FLANGE WIDTH (162 / 100 = 1 5/8") INDICATES MEMBER DEPTH (600 / 100 = 6 INCHES) INDICATES STUD (S) OR TRACK (T) SECTION NOTE: REFER TO ARCHITECTURAL DRAWINGS FOR SPECIFIC INTERIOR WALL LAYOUT AND GEOMETRY. STUD SIZE PER PLAN AND SCHEDULE OPEN HEADER PER SCHEDULE BOTTOM TRACK CONC CURB WHERE OCCURS PER ARCH DWG (E)CONC OR SLAB-ON-GRADE UNDERSIDE OF SLAB PER SCHEDULE STUD HEIGHT 'H' WALL MOUNTED MEP UNIT, ARCH COMPONENT, ETC. PER MECH/ARCH DWGS SEE TYPICAL DETAILS FOR REQUIRED WALL ASSEMBLY AND WEIGHT LIMITATIONS BACKING (T&B) PER TYPICAL DETAIL TYPICAL BOTTOM TRACK AND CONNECTION TO SLAB: CONT XXXT150 BOTTOM TRACK ONE GAUGE HEAVIER THAN VERT STUDS (16 GA MIN) WITH #10 SMS EA FLANGE EA STUD PROVIDE 0.157" DIA HILTI X-U PAF WITH 1" EMBED @ 32" OC MAX STAGGERED (ICC ESR-2269) UNO MAX HEIGHT 'H' 12'-0" 30'-0" INTERIOR WALL OPENING SCHEDULE MAX STUD HEIGHT 'H' 7'-6" MAXIMUM WALL OPENING WIDTH JAMB SIZE HEADER SIZE SILL SIZE 4'-0"362S162-33 (2) 362T200-43 (1) 362S200-43 362T150-33 7'-6"6'-0"(2) 362S162-33 362T150-33 7'-6"12'-0"(3)800S162-43 800T150-54 PUNCHOUT NO CLOSER THAN DEPTH OF HEADER TO CONNECTION (TYP) JAMB PER SCHEDULE PROVIDE 0.157" DIA HILTI X-U PAF WITH 1" EMBED @ 16" OC MAX WHERE WALL MOUNTED UNIT FOR ARCH COMPONENTS OCCURS TOP TRACK PER TYP 1g S1.1.4 S1.1.4 1e NOTE: COORDINATE WALL THICKNESS WITH ARCH. SIZES SHOWN IN SCHEDULE ARE MIN REQUIREMENTS. IT IS PERMITTED TO INCREASE DEPTH OF STUD PROVIDED THAT STUD GAUGE AND SPACING MATCH REQUIREMENTS SHOWN IN SCHEDULE JAMB TYPE a1 a2 a4 (2) 362T200-54 (1) 362S200-54 (2) 800T150-54 (1) 800S162-54 HEADER TYPE c2 c2 c3 SILL TYPE b1 b1 b1 JAMB SECTION CONFIGURATIONa SINGLE-STUD JAMB DOUBLE-STUD JAMB (BACK-TO-BACK) (T&B) 1" MAX 2-12 2-126" AT BOTH ENDS TYP DOUBLE-STUD JAMB (BOXED) TRIPPLE-STUD JAMB (BOXED) (2) #10 SMS @ 12" OC (FULL-HEIGHT) IN LIEU OF WELDING CONN 1 2 3 4 SILL PER SCHEDULE SINGLE SILL SILL-TO-JAMB CONNECTIONb L2x2x14 GA (T&B) x STUD DEPTH W/ (3)#10 SMS EA LEG BACK-TO-BACK JAMB STUDS PER DETAIL BOXED SILL (T+S SECTIONS) SILL PER SCHEDULE WHERE BACK-TO-BACK JAMB OCCURS CAP OPENING SIDE OF JAMB WITH A SECTION OF TRACK (XXXT150-54) EXTEND TRACK 12" PAST TOP AND BOTTOM OF OPENING AND ATTACH TO JAMB W/ (1) #10 SMS @ 6" OC MAX IN EACH LEGEQ EQ 1/2" 1/2" 1" BACK-TO-BACK JAMB STUDS PER DETAIL L2x2x14 GAx STUD DEPTH W/ (3)#10 SMS EA LEG EQ EQ 1/2" 1/2" 1" 1 2 SINGLE HEADER HEADER-TO-JAMB CONNECTIONc L2x2x14 GAx STUD DEPTH W/ (3)#10 SMS EA LEG FULL-HEIGHT JAMB STUD HEADER PER SCHEDULE NESTED HEADER IN-FILL STUDS (1)#10 SMS TYP EACH FLANGE FULL-HEIGHT JAMB STUD HEADER PER SCHEDULE L2x2x14 GA (T&B) x STUD DEPTH W/ (3)#10 SMS EA LEG EQ EQ 1/2" 1/2" 1" WHERE BACK-TO-BACK JAMB OCCURS CAP OPENING SIDE OF JAMB WITH A SECTION OF TRACK (XXXT150-54) EXTEND TRACK 12" PAST TOP AND BOTTOM OF OPENING AND ATTACH TO JAMB W/ (1)#10 SMS @ 6" OC MAX IN EACH LEG IN-FILL STUDS (1)#10 SMS TYP EACH FLANGE HEADER PER SCHEDULE (2)#10 SMS @ 16" OC WHERE BACK-TO-BACK JAMB OCCURS CAP OPENING SIDE OF JAMB WITH A SECTION OF TRACK (XXXT150-54) EXTEND TRACK 12" PAST TOP AND BOTTOM OF OPENING AND ATTACH TO JAMB W/ (1)#10 SMS @ 6" OC MAX IN EACH LEG L2x2x14 GA (T&B) x STUD DEPTH W/ (3)#10 SMS EA LEG EQ EQ 1/2" 1/2" 1" BOXED HEADER (BUILD-UP SECTIONS) (2)#10 SMS @ 16" OC 1 2 3 JAMB TO BOTTOM TRACK CONNECTIONe (3) 0.157" DIA HILTI X-U PAF WITH 1" EMBED INTO CONC (EA SIDE OF JAMB) BENT PL 12GA x4"x4" W/ (4)#10 SMS TO JAMB (EA SIDE OF JAMB) #10 SMS EA FLANGE EA STUD EQ EQ CL 3/4" 3/4" TRIPLE-STUD JAMB (PLAN VIEW) CL DOUBLE-STUD JAMB (PLAN VIEW) EDGE OF SLAB WHERE OCCURS BENT PL 14GA x3"x3" W/ (2) 0.157" DIA HILTI X-U PAF WITH 1" EMBED INTO CONC AND (3)#10 SMS TO JAMB CL SINGLE-STUD JAMB (PLAN VIEW) BENT PL 14GA x3"x3" W/ (2) 0.157" DIA HILTI X-U PAF WITH 1" EMBED INTO CONC AND (3)#10 SMS TO JAMB TYP 2" TYP 2" TYPICAL BOTTOM TRACK ATTACHMENT PER TYPICAL DIAGRAMMATIC INTERIOR WALL ELEVATION TYP 2" TYP 2" TYPICAL BOTTOM TRACK ATTACHMENT PER TYPICAL DIAGRAMMATIC INTERIOR WALL ELEVATION TYP 2" TYP 2" #10 SMS EA FLANGE EA STUD NOTE: BOXED JAMB IS SIMILAR #10 SMS EA FLANGE TYPICAL BOTTOM TRACK ATTACHMENT PER TYPICAL DIAGRAMMATIC INTERIOR WALL ELEVATION 1 2 3 BLOCKING OR CONT JOIST INTERIOR METAL STUD PER ARCH DWGS (2) #10 SMS EACH BLKG OR EACH JOIST TOP TRACK CONNECTION TO UNDERSIDE OF FRMGf NOTE: WHERE (E) BLKG DOES NOT OCCUR ADD 4x4 BLKG BETWEEN (E) JOISTS EQ EQ 1 1 / 2 " CL TYP 1/4" 2 1 / 2 " 2 1/2" TYP CTS-W SLOTTED TRACK WITH DRIFT SLOTS BY CEMCO (ICC ESR-2012) ONE GAUGE HEAVIER THAN VERT STUD (16 GA MIN) CL TYP 1/4" 2 1 / 2 " LOCATION OF SPLICE EQ EQ 1 1 / 2 " CL TYP 1/4" 1/ 2 " 1" 1/ 2 " 2 1 / 2 " SLOTTED TOP TRACK DRIFT / SLIP TOP TRACK SPLICE CONDITION NOTE: WALL FINISH TO STOP 1" BELOW THE BOTTOM OF SLOTTED TRACK TO ALLOW FOR SLOTTED TRACK DEFLECTION. CTS-300 SLOTTED TRACK BY CEMCO (ICC ESR-2012) ONE GAUGE HEAVIER THAN VERT STUD (16 GA MIN) TOP TRACK PROFILEg 2"TYP 3" MAX EA SIDE TYPICAL TOP TRACK ATTACHMENT PER TYPICAL DETAIL f JAMB WHERE OCCURS CENTERLINE OF #10 SMS EA FLANGE EA STUD ONE ADDITIONAL ATTACHMENT EA SIDE OF JAMB (WHERE OCCURS) ATTACHMENT SIZE TO MATCH TYPICAL TOP TRACK ATTACHMENT PER TYPICAL DETAIL f 4" TYP NOTE: WALL FINISH TO STOP 1" BELOW THE BOTTOM OF SLOTTED TRACK TO ALLOW FOR SLOTTED TRACK DEFLECTION. JAMB WHERE OCCURS ONE ADDITIONAL ATTACHMENT EA SIDE OF JAMB (WHERE OCCURS) ATTACHMENT SIZE TO MATCH TYPICAL TOP TRACK ATTACHMENT PER TYPICAL DETAIL f CENTERLINE OF #10 SMS EA FLANGE EA STUD TYPICAL TOP TRACK ATTACHMENT PER TYPICAL DETAIL f CENTERLINE OF #10 SMS EA FLANGE EA STUD (2) ADDED CONNECTION TO UNDERSIDE OF DECK (EA SIDE OF SPLICE) ATTACHMENT SIZE TO MATCH TYPICAL TOP TRACK ATTACHMENT PER TYPICAL DETAIL AD D E D VE R T S T U D AD D E D VE R T S T U D 3" MAX 3" MAX 2"TYP f 1 2 3 STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 As indicated 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 METAL STUD DETAILS S1.1.4 MCGUFF 01/02/25 SCALE: 1/2" = 1'-0"S1.1.4 TYPICAL INTERIOR METAL STUD WALL CONSTRUCTION 1 DETAIL ID: EMST-INTS-01 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 PERPENDICULAR TO JOISTS KICKER SIZE & SPACING PER SECTION (4)#12 SMS SCREWS PARALLEL TO JOISTS KICKER SIZE & SPACING PER SECTION (4)#12 SMS SCREWS 1 1 UNO 1 1 UNO (E) SHEATHING SIMPSON A35 EACH SIDE W/ #6x1/2" PAN HEAD SCREWS TO PLYWOOD 4x BLKG W/ SIMPSON FACEMOUNT HANGER EACH END (E) SHEATHING (E) SUB PURLIN (E) SUB PURLIN NOTCHED TRACK BLOCKING (2) #10 SMS (LOW PROFILE HEAD) INTERIOR STUD PER SCHEDULE & ARCH DWGS (16 GA MIN) FLAT STRAP BLOCKING CONT STRAP 4" x 16 GA 1" TYP 1" TYP EQEQ ATTACHMENT TO BACKING PER MEP/ARCH DWGS EXTEND BLOCKING AT LEAST ONE BAY ON EACH SIDE OF THE ATTACHMENT POINT NOTE: FLAT STRAP BRACING FOR CONDITIONS WHERE MAXIMUM DOWNWARD LOAD AT THE POINT OF ATTACHMENT DOES NOT EXCEED 20 LBS (BETWEEN CONSEQUENT WALL STUDS). ATTACHMENT TO BACKING PER MEP/ARCH DWGS EXTEND BLOCKING AT LEAST ONE BAY ON EACH SIDE OF THE ATTACHMENT POINT 1" TYP 1" TYP EQ EQ NOTE: SINGLE WALL STUDS FOR CONDITIONS WHERE MAXIMUM DOWNWARD LOAD AT THE POINT OF ATTACHMENT DOES NOT EXCEED 100 LBS (BETWEEN CONSEQUENT WALL STUDS). (3)#10 SMS (LOW PROFILE HEAD) @ EACH STUD INTERIOR STUD PER SCHEDULE & ARCH DWGS (16 GA MIN) CONT BACKING 600T150-43 NOTCH T&B FLANGES OVER WALL STUDS NOTCHED TRACK BLOCKING ATTACHMENT TO BACKING PER MEP/ARCH DWGS EXTEND BLOCKING AT LEAST ONE BAY ON EACH SIDE OF THE ATTACHMENT POINT 1" TYP 1" TYP EQ NOTE: DOUBLE WALL STUDS FOR CONDITIONS WHERE MAXIMUM DOWNWARD LOAD AT THE POINT OF ATTACHMENT DOES NOT EXCEED 250 LBS (BETWEEN CONSEQUENT WALL STUDS). WHERE DEMANDS EXCEED 250 LBS SEE PLAN FOR CASE SPECIFIC DETAIL (3)#10 SMS (LOW PROFILE HEAD) @ EACH STUD INTERIOR STUD (16 GA MIN) PER SCHEDULE & ARCH DWGS CONT BACKING 600T150-43 NOTCH T&B FLANGES OVER WALL STUDS A B C MIN 6" FINISH CEILING PER ARCH DWG 1 1 TO 2 (3) #10 SMS EA END ALTERNATE KICKER LOCATION 400S162-54 KICKER @ 4'-0" OC MAX (TYP) WHERE DIM 'a' EXCEEDS 6'-0" PROVIDE (2) 400T150-54 (BACK-TO-BACK) BENT PL 14 GAx4"x4" CONT TRACK (ONE GAUGE HEAVIER THAN WALL STUD) PER TYPICAL INTERIOR METAL STUD WALL DETAIL (E) SHEATHING(E) SHEATHING S1.1.5 10 S1.1.5 10 JOIST PER PLAN FINISH PER ARCH (E) CONCRETE WALL CONT 16 GA LEDGER TRACK W/ HILTI "X-U" FASTENERS FROM CLIP ANGLE TO CONCRETE WALL (EMBED 3/4" MIN PER ESR-2269) & #10 SMS @ EA FLANGE OF EA JOIST NOTE: FOR X-STRAP CONNECTION AT (E) CONC WALL SEE 15 S1.1.5 3' - 6" MAX JOIST PER PLAN JOIST @ WALL W/ (3) #10 SMS EA STUD X-STRAP PER PLAN SECURE ENDS OF STRAPS PER CONT BLOCKING PER . 7 S1.1.5 WALL STUDS PER PLAN (2) BAYS CONT BLOCKING @48"OC PER .7 S1.1.5 11 S1.1.5 X-STRAP PER PLAN JOIST PER PLAN SECURE ENDS OF STRAPS PER CONT 16 GA TRACK @ ENDS OF JOISTS W/#10 SMS AT EACH FLANGE CONT BLOCKING PER .7 S1.1.5 (3)#10 SMS EACH STUD WALL STUDS PER PLAN 3' - 6" MAX 11 S1.1.5 METAL STUD WALL PER PLAN CONT BLOCKING WP 16GA GUSSET PL W/ (6) #10 SMS AT EA CONT BLKG (12) TOTAL 6" MIN 6" MIN 3/4" MIN EDGE DISTANCE TYP 1 1/2" MIN SPACING TYP CONT BLOCKING X-STRAP PER PLAN W/ (2) #10 SMS AT EA CEILING JOIST W/ (6) #10 SMS TO GUSSET NOTE: FOR X-STRAP CONNECTION AT (E) CONCRTE WALL SEE 15 S1.1.5 METAL STUD WALL PER PLAN CONT BLOCKING WP 16GA GUSSET PL W/ (6) #10 SMS AT EA CONT BLKG (12) TOTAL 6" MIN 12" MIN X-STRAP PER PLAN W/ (2) #10 SMS AT EA CEILING JOIST W/ (6) #10 SMS TO GUSSET 1 1/2" MIN SPACING TYP 3/4" MIN EDGE DISTANCE TYP CONT TRACK (E) CONC WALL 16GA CLIP TO BE ATTACHED W/ (2) #10 SMS TO "CRC" & (2)#10 SMS TO STUD (LENGTH SHALL BE 1/4" SHORTER THAN STUD WIDTH AT EA END) WHERE BRACING TERMINATES AT BUILT-UP JAMB OR POST, EXTEND "CRC" INTO PUNCH- OUT ATTACH "CRC" TO JAMB OR POST LATERAL BRACING SPLICE (WHERE OCCURS) PROVIDE: (1)12" LONG "CRC" INVERTED OVER CENTER OF SPLICE W/ (3)# 10 SMS ON EACH SIDE OF SPLICE NOTES: 1. SIMPSON SUBH/MSUBH BRIDGING CONNECTORS MAY BE USED AS ALTERNATES TO 16GA CLIPS AT STUDS. 2. PROVIDE LATERAL BRIDGING WHERE RIGID WALL SHEATHING DOES NOT OCCUR FULL-HEIGHT ON BOTH SIDES (FLANGES) OF STUD WALL. 16GA "CRC" (COLD ROLLED CHANNEL) @4'-0" OC TYPICAL JAMB CORNER OR WALL INTERSECTON 16 GA SOLID BLOCK -FIT SNUG IN EACH STUD BAY 1 1/2"x 1 1/2"x 16 GA 50 ksi SUPPORT CLIP. 5" LONG WITH (2) SMS EACH LEG STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 As indicated 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 METAL STUD DETAILS S1.1.5 MCGUFF 01/02/25 SCALE: 1 1/2" = 1'-0"S1.1.5 TYPICAL METAL STUD KICKER TO (E) ROOF 10 DETAIL ID: MTS-MISC-01 SCALE: 1 1/2" = 1'-0"S1.1.5 TYPICAL WALL BACKING DETAIL 4 DETAIL ID: MTS-MISC-02 SCALE: 1" = 1'-0"S1.1.5 TYPICAL PARTIAL-HEIGHT INTERIOR STUD WALL DETAIL 1 DETAIL ID: MTS-MISC-04 SCALE: 1" = 1'-0"S1.1.5 JOIST TO CONCRETE WALL CONNECTION 8 SCALE: 1" = 1'-0"S1.1.5 JOIST PARALLEL TO WALL CONNECTION 12 SCALE: 1" = 1'-0"S1.1.5 JOIST PERPENDICULAR TO WALL CONNECTION 16 SCALE: 1 1/2" = 1'-0"S1.1.5 TYPICAL FLAT STRAP CONNECTION DETAIL 11 SCALE: 1 1/2" = 1'-0"S1.1.5 FLAT STRAP CONNECTION @ (E) CONC WALL DETAIL 15 SCALE: 1 1/2" = 1'-0"S1.1.5 TYPICAL STUD LATERAL BRIDGING DETAIL 6 DETAIL ID: MTS-MISC-06 SCALE: 1" = 1'-0"S1.1.5 CONTINUOUS WALL BRIDGING 7 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 W1 2 x 1 4 4x6 2x6@16" OC 4x6 4x6 4x6 4x 6 4x6 NOTES: 1. DO NOT DAMAGE (E)JOIST 2. ALL CONNECTIONS USE SIMPSON "LUS" OR "JS" HANGER UNO 3. PROVIDE 4x AT ALL ANCHOR LOCATIONS MECH EQUIP PER MECH DWG EXTENT OF UNIT SIMPSON MSTA 18 EA CORNER SUPPLY AND RETURN OPENING PER MECH SH A P E D # 1 4 x ( 9 1 / 4 " N E T M I N ) SH A P E D # 1 4 x ( 9 1 / 4 " N E T M I N ) PLAN VIEW 4x8 DF#1 SIMPSON CMST16 2 BAYS MIN EA SIDE 4x BLK 4x BLK4x BLK4x BLK PROVIDE 8d@4" OC, AROUND OPENING ALL SIDES (E ) S U B -PU R L I N S @ 2 4 " O C T Y P 4x BLK 4x BLK4x BLK4x BLK 4x8 DF#1 48" SQ MECHANICAL OPENING (E)ROOF JOIST PROVIDE SIMPSON 'U' HANGER TYP EA END CUT AND RE-SUPPORT (E)SUB-PURLIN W/ SIMPSON 'U' HANGER (TYP) LOCATE NEW MEMBER SO THAT IS DOESNT INTERFERE WITH (E)SUB-PURLIN OR HANGER 4x 8 D F # 1 4x 8 D F # 1 2x6 DF#1 SIMPSON CMST16 2 BAYS MIN EA SIDE 4x BLK PROVIDE 8d@4" OC, AROUND OPENING ALL SIDES (E ) S U B -PU R L I N S @ 2 4 " O C T Y P 4x BLK4x BLK 24" SQ MECHANICAL OPENING MAX (E)ROOF JOIST PROVIDE SIMPSON 'U' HANGER TYP EA END CUT AND RE-SUPPORT (E)SUB-PURLIN W/ SIMPSON 'U' HANGER (TYP) LOCATE NEW MEMBER SO THAT IS DOESNT INTERFERE WITH (E)SUB-PURLIN OR HANGER 4x 6 D F # 1 4x 6 D F # 1 2x6 DF#1 (2)2x4 PROVIDE 8d@4" OC, AROUND OPENING ALL SIDES (E ) S U B -PU R L I N S @ 2 4 " O C T Y P 21 1/2" SQ MECHANICAL OPENING MAX (E)ROOF JOIST PROVIDE SIMPSON 'U' HANGER TYP EA END LOCATE NEW MEMBER SO THAT IS DOESNT INTERFERE WITH (E)SUB-PURLIN OR HANGER SI S T E R ( N ) 2 x 4 T O ( E ) 2 x 4 S U B -PU R L I N (E)ROOF JOIST 4x BLK 4x BLK 4x BLK (E)ROOF JOIST SI S T E R ( N ) 2 x 4 T O ( E ) 2 x 4 S U B -PU R L I N (2)2x4 NOTE: FOR LARGER ROOF OPENING SEE & CONDITION A 48" SQ CONDITION B 24" SQ CONDITION A 21 1/2" SQ (E)2x (E)2x (E)2x 2x8 2x8 (E)2x (E)2x (E)2x (E)JOIST DETAIL (E)2x (E)2x (N)2x (N)2x LARGE OPENING (E)EN (TYP) JOIST (E)2x (E)2x SMALL OPENING NOTES: 1. THIS DETAIL SHALL BE USED FOR EXISTING CONSTRUCTION GC. TO COORDINATE DIMENSIONS AND LOCATIONS OF OPENINGS. TYP. U.N.O. 2. FOR OPENINGS AT NEW CONSTRUCTION SEE 3. FOR MECHANICAL EQUIPMENT CURB DETAIL SEE 4. USE OF THIS DETAIL IS SUBJECT TO ARCHITECTS/ENGINEERS APPROVAL UNLESS OPENINGS ARE SHOWN ON PLANS, TYP. (2) 2x TO MATCH (E)2x JOIST x14'-0" MAX. SPAN W/ SIMPSON HU JOIST HANGER EA END EDGE NAIL SHEATHING TO ALL MEMBERS FRAMING EDGE OF OPENING (TYP) SIMPSON U-JOIST HANGERS (TYP)4x T O M A T C H (E ) J O I S T D E P T H EDGE NAIL SHEATHING TO ALL MEMBERS FRAMING EDGE OF OPENING (TYP) (E)FRAMING SPACING (16"± OC TYP AT 32"OC MAX @ ROOF) FIELD VERIFY (TYP) 2x6 W/ SIMPSON U-JOIST HANGER EA END ADDED 2x JOIST WHEN SPAN IS LARGER THAN 14'-0" BUT LESS THAN 18'-0" 2-16d @12"OC A B C C4x T O M A T C H (E ) J O I S T D E P T H (E) JOISTS OR RAFTERS FOR SIZE AND SPACING, SEE FRAMING PLANS 4'-0" MAX C 48" CLR MAX 36" CLR MAX METAL CURB W/ 1/2"DIAx4" LONG LAG BOLTS PER MFR LAYOUT (4 MIN TOTAL) 4x BEAM PER PLAN W/ SIMPSON 'LUS' HANGER EA END SIMPSON BC40 HALF BASE@ 2'-0"OC & WITHIN 6" EACH END (3 MIN EACH SIDE) EACH LONGITUNDINAL SIDE W/ SIMPSON SD10212 SCREWS. FILL ALL HOLES 2x6@12"OC PLATFORM JOIST (PROVIDE 4x OR 4x BLOCK AT UNIT ANCHOR 4x BEAM (RIPPED FOR LEVELING AT EDGE OF PLATFORM 3/4" APA SHEATHING W/ 10d@6"OC EN & 10d@12" OC FN (E)PURLIN SIMPSON A35 CLIP @24"OC NOTE: WHERE (E) ROOFTOP PLATFORM IS BEING REUSED, CONTRACTOR TO VERIFY CONSTRUCTION OF (E) PLATFORM EXCEEDS OR MEETS REQUIREMENTS SHOWN ON THIS DETAIL. REMOVE AND REPLACE (E) PLATFORM AS REQUIRED VERIFY (E)EDGE NAILING NEW SHEATHING TO MATCH (E)1/2" MIN (E) SUB PURLIN 10d@4"OC AROUND PERIMETER (E)SHEATHING NEW 2x AROUND OPENING W/ 3" SIMPSON SDWS STAGGERED @12"OC & 6" FROM EACH END NOTE: 1. MINIMUM SHEATHING SIZE TO BE 2'-0"x2'-0" EF PER PLAN ROOF FLASHING PER ARCH ROOF CURB PER MECHANICAL W/ (4)-1/2" DIA x4" LONG LAG BOLTS PER MFR LAYOUT (1 EACH CORNER MIN) AIR SHAFT (E) EXHAUST (E)SHEATHING MACHINE BOLT PER MECHANICAL (4 MIN) 4x8 PER PLAN METAL CURB W/ 1/2"DIAx4" LONG LAG BOLTS PER MFR LAYOUT (4 MIN TOTAL) CONT 4x BLKG SIMPSON BC40 HALF BASE@ 2'-0"OC & WITHIN 6" EACH END (3 MIN EACH SIDE) EACH LONGITUNDINAL SIDE W/ SIMPSON SD10212 SCREWS. FILL ALL HOLES 4x BEAM (RIPPED FOR LEVELING AT EDGE OF PLATFORM 3/4" APA SHEATHING W/ 10d@6"OC EN & 10d@12" OC FN (E) ROOF SHEATHING (E) JOIST PER PLAN (E) GLB PER PLAN LVL PER PLAN W/ SIMPSON HUCQ412- SDS HANGER EA END (E) SUB PURLIN SIMPSON A35 CLIP @24"OC SIMPSON LTP5 CLIP @24"OC 2x6@12"OC PLATFORM JOIST (PROVIDE 4x OR 4x BLOCK AT UNIT ANCHOR) (E) 6x6 STRUT WHERE OCCURS NOTCH AS REQUIRED STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 As indicated 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 DETAILS S1.1.6 MCGUFF 01/02/25 SCALE: 1/2" = 1'-0"S1.1.6 TYPICAL EQUIPMENT SUPPORT FRAMING 2 DETAIL ID: EMUNIT-FRAME-01 SCALE: 1/2" = 1'-0"S1.1.6 TYPICAL PANAELIZED OPEN FOR MECHANICAL EQUIPMENT 7 DETAIL ID: EWOOD-OPEN-01 SCALE: 1/2" = 1'-0"S1.1.6 TYPICAL ROOF OPENING DETAIL 10 DETAIL ID: EWOOD-ROOF-01 SCALE: 1" = 1'-0"S1.1.6 MECHANICAL PLATFORM SUPPORT DETAIL 3 SCALE: 1" = 1'-0"S1.1.6 SKYLIGHT INFILL DETAIL 8 SCALE: 1" = 1'-0"S1.1.6 EXHAUST FAN ANCHORAGE 11 SCALE: 1" = 1'-0"S1.1.6 ALTERNATE MECHANICAL PLATFORM SUPPORT DETAIL 4 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 1 2 3 4 5 6 A B C C.5 C.6 D (E) TRASH ENCLOSURE (E) STAIRS (E) WF MOMENT FRAME AT (E) MEZZANINE EDGE (E) PRECAST PANELS (E) CONT FOOTING 600S162-43 @16"OC 600S162-43@16"OC 3"x16 GA FLAT STRAP X-BRACE PER 11 S1.1.5 600S162-43@16"OC 600S162-43 @16"OC 3"x16 GA FLAT STRAP X-BRACE PER 11 S1.1.5 15'-0"x5'-6" PAD FOOTING FOR FUTURE EQUIPMENT PER 5" THICK CONCRETE SLAB ON GRADE W/#5@16"OC EA WAY AT MID-DEPTH HSS 4 x 4 x 1 / 2 TYP PF1 6" CURB PER .8 S1.1.2 8 S1.1.3 7 S1.1.3 TYP AT (E) WALL FTG 362S162-43@16"OC 1 S1.1.3 PLAN NOTES: 1. ALL EXISTING INFORMATION IS BASE ON RECORD DRAWINGS CONTRACTOR SHALL NOTIFY SEOR IF CONDITIONS DISCOVERED DURING CONSTRUCTION VARY SIGNFICATNLY ON PLANS 2. VERIFY IN FIELD ALL EXISTING MEMBERS SIZES 3. FOR TYPICAL METAL STUD DETAILS SEE SHEET S1.1.4 & S1.1.5 5. INDICATES METAL STUD WALL PER SEE ARCH FOR ADDITIONAL INFO 6. FOR TYPICAL WALL MOUNTED TRANSFORMER SUPPORT SEE & 7. FOR FLOOR MOUNTED TRANSFORMERS ON GRADE PROVIDE MIN (4) 1/2" DIA HILTI KB-TZ2 EXPANSION ANCHORS W/ 3 1/4" EMBED PER MFR LAYOUT. TRANSFORMER OPERATING WEIGHT NOT TO EXCEED 1050 LBS 8. 1 S1.1.4 16 S1.1.3 12 S1.1.3 HSS 4 x 4 x 1 / 2 TYP PF1 INDICATES POLE FOOTING SIZE PER INDICATES POST SIZE 6 S1.1.3 STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 1/8" = 1'-0" 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 FIRST FLOOR PLAN S1.2.1 MCGUFF 03/11/25 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 1 2 3 4 5 6 A B C C.5 C.6 D (E)30" SSI 446R (E ) 6 . 7 5 x 2 8 . 5 G L B (E ) 6 . 7 5 x 2 7 G L B (E ) 6 . 7 5 x 2 5 . 5 G L B (E ) 6 . 7 5 x 2 4 G L B ( E ) 6 . 7 5 x 3 0 G L B (E ) 6 . 7 5 x 3 1 . 5 G L B (E ) 6 . 7 5 x 3 4 . 5 G L B (E ) 6 . 7 5 x 3 6 G L B ( E ) 6 . 7 5 x 2 8 . 5 G L B (E ) 6 . 7 5 x 2 7 G L B (E ) 6 . 7 5 x 2 5 . 5 G L B (E ) 6 . 7 5 x 2 4 G L B (E)26" SSI 446R (E)24" SSI 435R (E)24" SSI 435R (E ) 3 x 4 @ 2 4 " O C TY P U N O (E ) 3 x 4 @ 2 4 " O C TY P U N O (E ) 6 x 6 (E ) 6 x 6 (E ) 6 x 6 (E ) 6 x 6 (E ) 6 x 6 (E) PANELIZED WOOD ROOF FRAMING (E) CONCRETE PANEL PARAPET TY P A L O N G TH I S L I N E @8'-0"OC TYP THIS BAY (E)30" SSI 446R @8'-0"OC TYP THIS BAY TY P A L O N G TH I S L I N E TY P A L O N G TH I S L I N E @8'-0"OC TYP THIS BAY @8'-0"OC TYP THIS BAY TY P A L O N G TH I S L I N E @8'-0"OC TYP THIS BAY TY P A L O N G TH I S L I N E HP 1 HP 3 HP 5 HP 6 HP 8 HP 10 HP 7 HP 9 CU 1 CU 2 (E) SKYLIGHT INFILL (E) SKYLIGHT OPENEINGS PER 8 S1.1.6 NEW SKYLIGHT OPENINGS PER 7 S1.1.6 PROVIDE NEW ROOFTOP PLATFORM PER 2 S1.1.6 SEE NOTE 3 TYP 1300# 1300# 1300# 1300# 150#150# 1300# 4 S1.1.6 EF 1 75# SEE NOTE 3 TYP 750# PROVIDE EF ANCHORAGE PER 11 S1.1.6 PROVIDE NEW ROOFTOP PLATFORM PER 2 S1.1.6 750# 750# TYP AT NEW LVLS 4 S1.1.6 TYP AT NEW LVLS 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 3 1/2x18 LVL 2.0E 4x 8 4x 8 4x 8 4x 8 4x 8 4x 8 4x 8 4x 8 4x 8 4x 8 4 x 8 4x 8 4x 8 4x 8 HSS4x4x1/4 HDR LOW HSS4x4x1/4 TYP LOW ROOF PLAN NOTES: 1. ALL EXISTING INFORMATION IS BASED ON RECORD DRAWINGS. CONTRACTOR SHALL NOTIFY SEOR IF CONDITIONS DISCOVERED DURING CONSTRUCTION VARY SIGNIFICANTLY ON PLANS. 2. VERIFY IN FIELD ALL EXISTING MEMBER SIZES. 3, INDICATES REMOVING AND REPLACING (E) RTU CONTRACTOR TO VERIFY THAT THE NEW UNIT OPERATING WEIGHT IS LESS THAN OR EQUAL TO THE (E) RTU. CONTRACTOR SHALL NOTIFY SEOR IF NEW UNIT IS HEAVIER THAN (E). SEE MECH PLAN FOR ADDITIONAL INFORMATION. PROVIDE ANCHORAGE FOR NEW UNITS PER 3 S1.1.6 STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.) 3300 IRVINE AVE. SUITE 245 NEWPORT BEACH, CALIFORNIA 92660 T:(949)862-8500 WWW.BJSCE.COM JOB#: No. 6250 FFOHSIB RYANW. REGISTEREDPROFESSIONALENGINEER STRUCTURALSTATEOFCALIFORNIA DATE: FOR BRANDOW & JOHNSTON ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE 240254 1/8" = 1'-0" 04463.0000.24 3080 S HARBOR BLVD SANTA ANA, CA 92704 ROOF FRAMING PLAN S1.2.2 MCGUFF 03/11/25 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 3/17/2025 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 ELECTRICAL COVER SHEET IE-0.01 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 TITLE 24 CALCULATIONS IE-0.02 PART 1 - GENERAL CONDITIONS 1.01 SUMMARY A.Work Included: All labor, materials, appliances, tools, equipment, facilities, transportation and services necessary for and incidental to performing all operations in connection with furnishing, delivery and installation of the work of this Division, complete, as shown on the drawings and/or specified herein. The work includes, but is not limited to: 1.Examine all divisions for related work required to be included as work under this Division. 2.General provisions and requirements for electrical work. 1.02 REFERENCES A.Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01, apply to these Specifications. B.In addition, the products covered in this Specification, except as noted, shall be designed, manufactured, and tested in accordance with the latest revisions of the applicable standards of: 1.ANS - American National Standards Institute 2.ASTM - American Society for Testing and Materials 3.IEEE - Institute of Electrical and Electronics Engineers 4.NEC - National Electrical Code (NFPA 70) 5.NECA - National Electrical Contractors Association: "Standard of Installation" 6.NEMA - National Electrical Manufacturers Association 7.NFPA - National Fire Protection Association 8.UL - Underwriters Laboratories, Inc. 1.03 SUBMITTALS (ADDITIONAL REQUIREMENTS) A.General: Submit the following in accordance with the Conditions of the Contract and Division 01 Specification Sections, and these Specifications. B.Product Data: Submit product data for each type of product specified. C.Shop Drawings: Submit shop drawings for the following: 1.Switchboards. 2.Transformers. 3.Panelboards. 4.Lighting fixtures, supports, and controls. 1.04 QUALITY ASSURANCE A.Qualifications of Manufacturer: Company specializing in manufacturing products specified in these Specifications with minimum five years documented experience. B.Electrical Component Standard: Components and installation shall comply with NFPA 70, "National Electrical Code." C.NEMA and UL Compliance: Products shall comply with applicable requirements of NEMA and UL standards. Provide products and components listed and labeled by UL. D.NECA Installation Standards: Perform work in accordance with NECA "Standard of Installation." E.Source Quality Control: Quality control testing shall meet applicable Underwriters' Laboratories Inc. Standards. F.Electrical contractor shall perform all work in strict accordance with all local, state, and national governing codes. 1.05 DELIVERY, STORAGE AND HANDLING A.General: Deliver, store, protect, and handle products to the site in accordance with the General and Supplementary Conditions, Division 01 Specification Sections, and these Specifications. B.Store and protect product in accordance with manufacturer's instructions, and in a manner to prevent damage from the elements, personnel, equipment, and moisture. 1.06 PROJECT CONDITIONS OR SITE CONDITIONS A.Verify that field measurements are as shown prior to commencing the work. PART 2 - PRODUCTS 2.01 MATERIALS AND EQUIPMENT A.Materials, equipment, and devices shall, as a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70. 2.02 RACEWAYS A.Metal Conduit and Tubing: 1.Rigid Metal Conduit: Steel, hot-dipped galvanized including the threads, with an outer coating of zinc bichromate, complete with one coupling and one end thread protector, manufactured in accordance with ANSI C80.1 and UL 6. Fittings: threaded, hot-dipped galvanized, manufactured in accordance with ANSI C80.4. a.Where indicated, provide galvanized rigid steel conduit and fittings with polyvinyl chloride (PVC) coating of nominal .020 inch (20 mil ) thickness conforming to NEMA RN-1, Type A, Robroy Industries, or equal. 2.Intermediate Metal Conduit: Hot-dipped galvanized steel including the threads, manufactured in accordance with UL 1242. 3.Electrical Metallic Tubing: Welded, electro-galvanized thin wall steel tubing, manufactured in accordance with ANSI C80.3 and UL 797. Maximum size: 2". Fittings: compression type (indenter or setscrew type not allowed); gland compression type, zinc plated steel body, cadmium plated malleable iron nut, O-Z/Gedney. 4.Flexible Metal Conduit: Hot-dipped galvanized steel interlocking, single strip type manufactured in accordance with UL1. Connectors: squeeze type, malleable iron, cadmium plated, straight and angle connectors for all sizes and twist-in connectors for 1/2" and 3/4" flexible metal conduit. 5.Liquidtight Flexible Conduit: Hot-dipped galvanized steel strip core with extruded liquid-tight polyvinyl jacket. Use O-Z/Gedney Type UAG, or equal. Liquid-tight fittings. ANSI/NEMA FB 1. Connectors: Cadmium plated malleable iron body and nut, cadmium plated steel ferrule, insulated throat, integral cast external ground lug, O-Z/Gedney. B.Nonmetallic Conduits: 1.Rigid Nonmetallic Conduit: NEMA TC 2 and UL 651, Schedule 40. Polyvinyl chloride (PVC) heavy-wall conduit, with tapered sleeve couplings, rated and labeled for use with 90°C rated conductors, manufactured in accordance with ANSI C33.91. Fittings: NEMA TC-3, cemented type, from the same manufacturer as the conduit. 2.PVC and ABS Plastic Fittings: NEMA TC 9-1. Match to conduit type and material. 3.Conduit, Tubing, and Duct Accessories: Types, sizes, and materials complying with manufacturer's published product information. Mate and match accessories with raceway. C.Conduit Bodies: Provide types, shapes, and sizes as required to suit individual applications and NEC requirements. Provide matching gasketed covers secured with corrosion resistant screws. For metallic conduit and tubing, use metallic conduit bodies. Use bodies with threaded hubs for threaded raceways. D.Wireways and Auxiliary Gutters: Provided electrical wireways and gutters shall be of types, sizes, and number of channels as indicated. Fittings and accessories including but not limited to couplings, offsets, elbows, expansion joints, adapters, hold-down straps, and end caps shall match and mate with wireway or gutter as required for complete system. Where specifications are not indicated, select to fulfill wiring requirements compling with applicable provisions of NEC. Use sheet steel wireways with screw-on covers and corrosion resistant hardware. For dry locations coat with rust inhibitor and finish with gray baked enamel. For wet locations use hot-dipped galvanized material finished with gray baked enamel, provide gaskets for covers. E.Surface Raceway: 1.Provide sizes and channels as indicated. Provide fittings that match and mate with raceway. 2.Surface metal raceway: Construct of galvanized steel with snap-on covers, with 1/8" mounting screw knockouts in base approximately 8" O.C.. Finish with manufacturer's standard prime coating suitable for painting. Provide raceways of types suitable for each application required. Provided by Hoffman Engineering Co., the Wiremold Co., or approved equal. 3.Surface Nonmetallic Raceway: Two-piece construction, manufactured of rigid PVC compound with matte texture and manufacturer's standard color. Raceway and system components shall meet UL 94 requirements for nonflammable, self-extinguishing characteristics. Provided by Hubbell, Inc., Panduit Corp., The Wiremold Co., or approved equal. F.Accessories: 1.General: Reducers, bushings, washers, etc., shall be cadmium plated malleable iron of the shape and dimension best suited for the application. 2.Seals for Walls and Floor Penetrations: Malleable iron body, oversize sleeve, sealing ring, pressure clamp and rings and sealing grommet, hex head cap screws, O-Z/Gedney Type FSK, or equal. 3.Fire Seals: Heat activated intumescent material, elastomeric sealing ring, socket head cap screws, steel pressure discs and flange, O-Z/Gedney Type CFSF, Nelson Flame Seal, or equal. 4.End bells: Hot-dipped galvanized, threaded malleable iron, O-Z/Gedney Type THS, or equal. 5.Bushings 1-1/4" and smaller: High-impact thermo-setting phenolic, 150°C, O-Z/Gedney Type "A", or equal. Bushings 1-1/2" and larger: Hot-dipped galvanized with thermosetting phenolic insulation, 150°C, O-Z/Gedney Type "B", or equal. 6.Locknuts 1-1/2" and smaller: Zinc plated heavy stock steel, O-Z/Gedney, or equal. Locknuts 2" and larger: Cadmium plated malleable iron, O-Z/Gedney, or equal. 7.Hubs: Cadmium plated malleable iron, tapered threads, neoprene "O" ring, insulated throat, O-Z/Gedney, or equal. 8.Expansion Fittings: Hot-dipped galvanized malleable iron with bonding jumpers. Linear: O-Z/Gedney Type AX and TX, or equal. Linear, with deflection: O-Z/Gedney Type AXDX, or equal. 9.Escutcheons: Chrome plated sectional floor and ceiling plates, Crane No. 10, or equal. 2.03 WIRE AND CABLE A.Provide wire and cable suitable for the temperature, conditions, and location where installed, except as otherwise indicated. 1.Conductor: Copper. Provide solid conductor for #10 AWG and smaller. Provide stranded conductors for sizes #8 AWG and larger. a.Use stranded conductors at motors and other applications where subject to vibration, and for control circuits. 2.Minimum Size Conductor: #12 AWG, except as otherwise indicated. a.Control circuits: #14 AWG. 3.Insulation voltage rating: 600 volts. B.Building wire and cable: Single conductor insulated wire. Insulation: ANSI/NFPA 70, Type THHN/THWN, rated 75°C or Type XHHW, rated 90°C. C.Connectors: Provide UL Listed factory fabricated, solderless metal connectors of sizes, ampacity ratings, materials, types and classes for applications and for services indicated. Use connectors with temperature ratings equal to or greater than those of the wires upon which used. D.Pull Cord: 1/8" polypropylene or nylon. 2.04 BOXES AND FITTINGS A.Provide indicated types, sizes, and NEMA enclosure classes. Where not indicated, provide units of types, sizes, and classes appropriate for the use and location. Provide all items complete with covers and accessories required for the intended use. Provide gaskets for units in damp or wet locations. 1.Materials and Finishes: a.Sheet steel: Flat rolled, code gauge, galvanized steel. b.Fasteners for general use: Corrosion resistant screws and hardware, including cadmium and zinc plated items. c.Fasteners for wet or damp locations: Stainless steel screws and hardware. d.Cast metal for boxes, enclosures and covers: Copper-free aluminum except as otherwise indicated. e.Exterior finish: Gray-baked enamel for items exposed in finished locations except as otherwise indicated. f.Painted interior finish: Where indicated, white baked enamel. g.Fittings for boxes, cabinets, and enclosures: Conform to UL 514B. Malleable iron or zinc-plated steel for conduit hubs, bushings and box connectors. B.Metal outlet, device, and small wiring boxes: 1.General: Conform to UL 514A and UL 514B. Boxes shall be of type, shape, size, and depth to suit each location and application. 2.Steel Boxes: NEMA OS 1. Boxes shall be sheet steel with stamped knockouts, threaded screw holes and accessories suitable for each location including mounting brackets and straps, cable clamps, exterior rings and fixture studs. 3.Cast Aluminum Boxes: Copper-free aluminum with gasketed covers, threaded raceway entries, and features and accessories suitable for each location including mounting ears, threaded screw holes for devices and closure plugs. C.Pull and junction boxes: 1.General: Conform to UL 50, for boxes over 100 cubic inches in volume. Boxes shall have bolted-on covers of material same as box, and shall be of the size and shape to suit the application. 2.Steel Boxes: Sheet steel with welded seams. Where necessary to provide a rigid assembly, construct with internal structural steel bracing. 3.Hot-Dip Galvanized Steel Boxes: Sheet steel with welded seams. Where necessary to provide a rigid assembly, construct with internal structural steel bracing. Hot-dip galvanize after fabrication. Cover shall be gasketed. 2.05 WIRING DEVICES A.General: Provide wiring devices, in types, characteristics, grades, colors, and electrical ratings for applications indicated which are UL listed and which comply with NEMA WD 1 and other applicable UL and NEMA standards. Coordinate color selection, prior to ordering materials, with Architect/Engineer. B.Receptacles: UL 498 and NEMA WD 6. Straight blade, two-pole, three-wire grounding type, as indicated below: 1.Duplex: 20Amps, 125V, NEMA 5-20R, Heavy Duty - Hubbell #5362 2.Duplex, GFCI [1]: 20Amps, 125V, NEMA 5-20R, Heavy Duty - Hubbell #GF5362 3.Simplex: 20Amps, 125V, NEMA 5-20R, Heavy Duty - Hubbell #5361 4.Simplex: 20Amps, 250V, NEMA 6-20R, Heavy Duty - Hubbell #5461 5.Simplex, Locking [2]: 20Amps, 125V, NEMA L5-20R, Heavy Duty - Hubbell #2310 Notes: 1.GFCI receptacles shall protect downstream receptacles on same circuit. 2.Provide locking receptacle with black nylon face, except as indicated otherwise. C.Switches: UL20 and NEMA WD 1. Quiet toggle type AC switch. Rating and type as indicated below: 1.Single Pole: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1221 2.Double Pole: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1222 3.Three Way: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1223 4.Single Pole w/Pilot Light [1]: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1221-PL7 5.Single Pole w/Keyed Switch: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1221-L 6.Momentary Contact [2]: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1557 Notes: 1.For switch with pilot light, the light is "ON" when the load is "ON". 2.For momentary contact type switch, operation is three position - two circuit momentary contact and center off. D.Wall Plates: Single and combination, of types, sizes, and with ganging and cutouts as indicated. Provide plates which mate and match with wiring devices to which they are attached, and are from the same manufacturer. Provide metal screws for securing plates to devices with screw heads colored to match finish of plates. Provide wall plate color to match wiring devices except as otherwise indicated. Provide wall plates with engraved legend where indicated. Conform to requirements for electrical identification. 1.Interior Areas: Smooth, high-impact resistant plastic, of the same manufacturer as the device. a.Voice, data, or video communications system outlets: Same as for wiring devices except with 3/8" or 1" rubber grommets as required. b.Surface mounted outlet boxes: Zinc coated sheet steel rounded edges, same size as outlet box. c.Kitchen and food preparation areas: Polished stainless steel type, 0.04 inches thick. 2.Exterior areas: Weatherproof, corrosion-resistant type, die cast aluminum with self-closing gasketed cover. For duplex receptacles, use Hubbell 5206-WO or equal; for wall switches, use Hubbell 7420 or equal; for GFI receptacles, use manufacturer's listed plate. 2.06 GROUNDING AND BONDING A.Materials: All materials shall be copper. Provide types indicated and sizes and ratings required to comply with NEC. Where types, sizes, ratings, and quantities indicated are in excess of NEC requirements, the more stringent requirements and the greater size, rating, and quantity indications govern. B.Wire and cable conductors shall be as follows, except as otherwise indicated: 1.Equipment grounding conductor: Green insulated copper. 2.Grounding electrode conductor: Stranded copper cable. 3.Bare copper conductors: Shall conform to the following: a.Solid Conductors: ASTM B 3. b.Assembly of Stranded Conductors: ASTM B 8. c.Tinned Conductors: ASTM B 33. C.Connector products: 1.General: Listed and labeled as grounding connectors for the materials used. 2.Pressure Connectors: High-conductivity plated units. 3.Bolted Clamps: Heavy-duty units listed for the application. 4.Exothermic Welded Connections: Provided in kit form and selected for the specific types, sizes, and combinations of conductors and other items to be connected. D.Grounding electrodes: 1.Ground Rods: Copper-clad steel with high-strength steel core and electrolytic-grade copper outer sheath, molten-welded to core. Size: 3/4" diameter by 10 feet long. 2.Plate Electrodes: Copper plates, minimum 0.10 inch thick, size as indicated. E.Test (ground) wells: Precast concrete, 12" round x 18" deep open bottom valve box, with cast iron grate cover plate marked "GROUND". 2.07 SUPPORTING DEVICES A.Supports: Individual conduits shall be rigidly supported and clamped with one hole malleable iron conduit clamps, conduit beam clamps, conduit hangers, or wall brackets, as necessary for the type of construction and as indicated. The use of perforated flat steel straps or wire for supporting conduits will not be permitted. B.Support Attachments: Kwik-bolt, sleeve anchors, wedge anchors, toggle bolts, and hollow all anchors, as manufactured by Hilti or Red Head. C.Light steel framing: Light steel framing members for conduit hangers and other supports shall be formed from 12 gauge (minimum) steel, unless otherwise indicated. 1.Finish: Hot-dipped galvanized steel for light steel framing members and fittings and all hardware, such as hanger rods, couplings, bolts, nuts, etc., shall be electro-galvanized, unless otherwise indicated. 2.Acceptable manufacturers: B-Line, Superstrut, Unistrut, or equal. 2.08 ELECTRICAL IDENTIFICATION A.Manufacturers: Brady, Ideal Industries, Markal, Panduit, Thomas & Betts. B.Electrical identification products: 1.Adhesive Marking Labels for Raceway and Metal-clad Cable: Pre-printed, flexible, self-adhesive labels with legend indicating voltage and service (Emergency, Power, Lighting, Air Conditioning, Voice and Data Communications, Control, Fire Alarm and Detection, Public Address (Paging), Electronic Security). 2.Label Size, as follows: a.Raceways 1" and Smaller: 1-1/8" high by 4" long. b.Raceways Larger than 1": 1-1/8" high by 8" long. 3.Color: Black legend on orange background. 4.Colored Adhesive Marking Tape for Raceways, Wires, and Cables: Self-adhesive vinyl tape not less than 3 mils thick by 1" to 2" in width. 5.Pretensioned Flexible Wraparound Colored Plastic Sleeves for Raceway and Cable Identification: Flexible acrylic bands sized to suit the raceway diameter and arranged to stay in place by pre- tensioned gripping action when coiled around the raceway or cable. 6.Underground line marking tape: Permanent, bright-colored, continuous printed, plastic tape compounded for direct burial service not less than 6" wide by 4 mils thick. Printed legend indicative of general type of underground line below. 7.Wire/cable designation tape markers: Vinyl or vinyl-cloth, self-adhesive, wraparound, cable/conductor markers with preprinted numbers and letters 8.Aluminum, wraparound, cable marker bands: Bands cut from 0.014" thick, aluminum sheet, fitted with slots or ears for securing permanently around wire or cable jacket or around groups of conductors. Provide for legend application with stamped letters or numbers. 9.Plasticized card stock tags: Vinyl cloth with preprinted and field printed legends to suit the application. Orange background, except as otherwise indicated, with eyelet for fastener. 10.Aluminum-faced card stock tags: Weather-resistant, 18-point minimum card stock faced on both sides with embossable aluminum sheet, 0.002" thick, and laminated with moisture-resistant acrylic adhesive. Pre-print legend to suit the application, and punch for tie fastener. 11.Brass or aluminum tags: Metal tags with tamped legend, punched for fastener. Dimensions: 2" by 2" by 19 gauge. 12.Engraved, plastic-laminated labels, signs, and instruction plates: Engraving stock melamine plastic laminate, 1/16" minimum thick for signs up to 20 square inches, or 8" in length; 1/8" thick for larger sizes. Engraved legend in white letter on black face and punched for mechanical fasteners. 13.Warning and caution signs for indoor use: Shall be minimum 18 gauge steel, white porcelain enamel finish, with red lettering, punched for fasteners, with colors, legend, and size appropriate to the location. Lettering to read, "Danger - High Voltage", unless otherwise indicated. 14.Exterior metal-backed butyrate warning and caution signs: Weather-resistant, nonfading, preprinted cellulose acetate butyrate signs with 20-gauge, galvanized steel backing, with colors, legend, and size appropriate to the location. Provide 1/4" grommets in corners for mounting. 15.Fasteners for plastic-laminated and metal signs: Self-tapping stainless steel screws or #10-32 stainless steel machine screws with nuts and flat lock washers. 16.Cable ties: Fungus-inert, self-extinguishing, one-piece, self-locking nylon cable ties, 0.18" minimum width, 50 lb minimum tensile strength, and suitable for a temperature range from minus 50°f to 350°f. Provide ties in specified colors when used for color coding. 2.09 SWITCHBOARDS A.Manufacturers: Eaton, General Electric, Siemens or Square D. B.Materials: 1.Main Switchboard: Provide a totally enclosed, dead front, safety type switchboard designed for voltage and service ampacity as indicated on drawings and mounted on 2-1/2" thick concrete pad. 2.Provide a switchboard consisting of the required number of vertical sections bolted together to form one metal enclosed, rigid switchboard with the following features: a.The sides, top and rear covered with removable screw-on code gauge steel plates. b.Include all protective devices and equipment as listed on drawings with necessary interconnections. c.Bus bars mounted on supports of high impact nontracking insulation material braced to withstand mechanical forces exerted during 100,000 AMPS RMS symmetrical short circuit conditions, or as required by serving utility. 3.Chemically clean steel surfaces and treat to aid bonding between paint and metal surfaces. Provide high tensile strength hardware on conductors and suitable protective finish. 4.Provide full length copper ground bus. Secure a ground bus to each vertical section of structures and extend it the entire length of the switchboard. 5.Provide switchboard with adequate lifting means, capable of being rolled or moved into installation position and bolted directly to the floor without the use of floor sills. 6.Use A-B-C type bus arrangement, left-to-right, top-to-bottom and front-to-rear throughout. Switchboard shall be entirely accessible from the front, including cable and bus connections, unless specifically noted otherwise. 7.Provide group mounted, quick-break protective devices with bar connection straps, with device line and load connections accessible from the front. Where "spaces" are scheduled furnish entire bus except device connecting straps. Provide full height wiring gutter covers for quick access to wiring terminals. 8.The switchboard frame work shall be made of formed steel angles securely bolted or riveted together. Adjacent to each switch unit provide a lamacoid plastic name plate engraved with proper circuit designation, screw-on type only. 9.At top of switchboard and supported on the frame, there shall be provided a pull box for termination of the conduits to the board. It shall not be less than 12" in height and shall be built as an integral part of the switchboard. The front of the pull box shall be removable. The entire exterior of the switchboard and pull box enclosures shall be light gray per ANS -61 . 10.Switches shall be quick-make, quick-break of capacity and number of poles indicated. 11.Main busses shall be silver or tin plated copper sized on the basis of a current density to hold temperature rise to 50°c above 40°c ambient. The bus structure shall be braced to withstand the mechanical forces exerted during a fault as shown on the drawings. 12.The switchboard shall bear the label of approval of the underwriter's laboratories and shall be built to NEMA and IEEE standards. Shop drawings of the proposed board shall be furnished to comply with these specifications. 13.Circuit Breakers: a.Resettable, quick-make, quick-break, bolt-in place type, trip-free, with separate trip position from on and off positions. b.Multiple pole breakers with common trip and one operation handle. c.Wire with sequence phasing. 14.Furnish record drawings providing the following information; a.Complete rating. b.Short circuit withstand-ability of bus and lowest rated device. c.Overall outline dimensions including space available for conduits. d.Circuit schedule showing circuit number. e.Device description. f.Feeder circuit identification. g.Conductor ratings and one-line diagram with each circuit device numbered. 15.Provide switchboards meeting U.L. Standard #UL891 and NEMA Standard PB-2. The U.L. label shall appear on all switchboard sections which contain U.L. listed devices. 16.Provide ground fault protection on each main devices, rated 480/277 ground wye, 1000 amps or larger, as follows: a.U.L. listed ground sensor relay system equal to General Electric GSR. Provide ground break components for each system with coordinated ground sensor (CR) and integral test winding. Provide with solid state relay to operate shunt trip circuit on the switch and monitor panel. b.Use time relay with the following features: 1)Continuously adjustable current pick-up settings of 100 to 1200 amperes. 2)Continuously adjustable time delay setting from instantaneous (.03 seconds) to one second. 3)Memory function to recognize and initiate tripping on intermittent ground faults. c.Install panel which: 1)Indicates relay operation. 2)Provides means for testing the system with or without interruption of electrical service. 3)Does not permit the ground fault system to be inadvertently left in an inactive or "off" state. d.Use ground sensor for zero sequence arrangement on the main service entrance devices. 17.Provisions for padlocking the circuit breakers or disconnect in the "on" and "off" positions. 18.Provide full rated bussing (no cascading). 2.10 DISCONNECT (SAFETY) SWITCHES A.Disconnect switches shall be rated 600 volts A.C., NEMA Type HD heavy duty, horsepower-rated, quick-make/quick-break, non-fusible or fusible, Class "R", with the number of poles and ampere rating as shown. Enclosure shall be NEMA Type 1, lockable. Maximum voltage, current and horsepower rating shall be clearly marked on the switch enclosure. Switches equipped with dual-element time-delay fuses shall be permanently labeled with fuse type and rating. 1.For outdoor locations, or shown as "WP" (weatherproof), the enclosure shall be NEMA Type 3R, unless otherwise indicated. 2.11 TRANSFORMERS A.Manufacturers: Eaton, General Electric, International Transformer Company, Siemens or Square D. B.Material and Construction: 1.Dry type, rated as shown. Provide transformer cooled by natural convection of air with: a.Steel enclosure. b.Class H insulation. c.Transformers 25 kVA or Smaller: Insulation temperature rise over 40°C ambient not to exceed 115°C at full load for 185°C insulation system. d.Transformers 30 kVA or Larger: Insulation temperature rise above 40°C ambient not to exceed 150°C at full load for 220°C insulation system. e.Suitable for indoor or outdoor installation as required or indicated on the drawings. f.Compartment located where primary and secondary connections can be made. g.Secure cover plates secured with captive type hardware. h.Transformer coils shall be of the continuous wound construction and shall be impregnated with non-hygroscopic, thermosetting varnish. i.The entire transformer enclosure shall be degreased, cleaned, phosphatized, primed, and finished with a GRAY, baked enamel. j.The maximum temperature of the top of the enclosure shall not exceed 50°C rise above a 40°C ambient. k.The core of the transformer shall be visibly grounded to the enclosure by means of a flexible grounding conductor sized in accordance with applicable NEMA, IEEE, and ANSI standards. l.Provide transformer rated 30 kVA and less with two 5 percent full capacity taps below rated voltage in primary. m.Provide transformers rated greater than 30 kVA with four 2-1/2 percent full capacity taps below and two 2-1/2 percent above rated voltage in primary. 2.The average audible sound level shall not exceed 45 DB for transformers rated at 75 kVA and below, nor 55 DB for transformers rated above 75 kVA, when measured in accordance with NEMA Standard TRI-2.068. 2.12 PANELBOARDS A.Manufacturers: Eaton, Siemens, General Electric, or Square D. B.Materials: 1.Branch circuit panelboards: a.Provide factory assembled, enclosed panelboards in dead front cabinets, with doors, surfaced mounted or recessed as indicated, not less than 20" wide and 5-3/4" deep. Height will depend on the number of breakers and spaces. b.Where a control compartment is indicated, provide an integral compartment with a separate hinged lockable door held with captive screws. c.Provide feeder terminal lugs for both main lugs only and main breakers rated for use with copper or aluminum conductors. d.Provide three phase, 4 wire, solid neutral design with sequence bussing, full capacity neutral and full length copper bussing including areas indicated as space only. Bussing shall be braced for maximum available fault. e.Provide copper neutral bus where neutral bus is indicated. Neutral bus shall be sized for minimum twice the current carrying capacity of line bus. f.Key all door locks alike. Provide a type written directory of circuit index card holder mounted behind the door in framed card slot with plastic see through window. g.Provide full size copper equipment ground bus. h.All breakers shall be bolt-on type molded case. No tie handle is accepted for multi-pole breaker. i.Provide pad lock off devices on all breakers serving appliances, motor operated equipment, HVAC equipment and other circuit as indicated on panel schedules. j.120/208V, 3 Phase, 4 Wire Panelboards: General Electric Co. type NLAB, Square D Co. type NQOB, or Cutler-Hammer type POW-R-LINE1. k.277/480V, 3 Phase, 4 Wire Panelboards: General Electric Co. type NHB, Square D Co. type NEHB, ITE, Inc. type NHB, Sylvania Co. type NH1B or Cutler-Hammer type POW-R-LINE2. l.All equipment shall be listed to meet or exceed the available fault current indicated on drawings. m.Provide main lugs only unless scheduled otherwise. n.Construct in accordance with U.L. and NEMA Standards. 2.Distribution Panelboards: a.Provide circuit breaker type distribution panelboards with fully rated copper bus, lockable molded case breakers for mains and feeders. Provide nameplates for all circuit breakers. b.Busing shall be braced to withstand maximum available fault current indicated on drawings. c.Provide copper neutral bus where indicated. Neutral bus shall be sized for minimum twice the current carrying capacity of line bus. d.Provide full size copper ground bus adequate for number of grounded circuits. e.General Electric Co. type NCP and type CCB, or Square D Co. types HCN and HCM, or Cutler-Hammer type POW-R-LINE3 and POW-R-LINE4B. 3.Circuit breakers: a.Resettable, quick-make, quick-break, bolt-in place type, trip-free, with separate trip position from on and off positions. b.Multiple pole breakers with common trip and one operation handle. c.If handle ties are required, install only handle ties provided by circuit breaker Manufacturer. d.Wire with sequence phasing. e.Circuit breakers shall be rated to meet or exceed the available fault current indicated on drawings. 2.13 OVERCURRENT PROTECTIVE DEVICES A.Manufacturers: 1.Circuit Breakers: a.General Electric b.Square D c.Siemens d.Eaton 2.Fuses: Bussmann only. B.Materials and fabrication: 1.Circuit Breakers: Molded case, quick-make, quick-break, thermal-magnetic, trip-free with individual inverse time tripping mechanism on each pole. Terminal lugs rated for copper and aluminum conductors. Minimum 10,000 amperes interrupting capacity, RMS symmetrical short circuit rating shall be as required. All breakers shall meet or exceed the maximum available fault current as indicated on single line diagram. a.Use magnetic-only circuit breakers for motor applications. b.Provide Class A (5ma sensitivity) breakers where GFI type breakers are required. c.Provide "HACR" type circuit breakers for HVAC loads. Ratings shall be as indicated on the drawings. d.No tie handle on multi-pole circuit breaker is accepted. e.Provide ambient compensated type breaker where the breaker is installed in the ambient in excess of 40°C (104°F). 2.13 OVERCURRENT PROTECTIVE DEVICES 1.Fuses, as follows, unless otherwise indicated: a.Class RK1: 1)250V; LPN-RK, Lowpeak 2)600V; LPS-RK b.Class L: KRP-C, Hi-Cap 2.14 MOTOR CONTROLLERS A.Manual motor controllers: NEMA ICS 6. AC general purpose Class A manually operated, full voltage controller with thermal overload element. Also provide red pilot light, auxiliary contacts: 2 N.O. and 2 N.C., and push button operator. Enclosure: NEMA ICS 6, Type 1 except as otherwise shown. B.Magnetic motor controllers: Provide full voltage, non-reversing, across the line, magnetic controller, except where another type is indicated. 1.Control Circuit: Control circuit shall be 120 volts, except as otherwise indicated. Provide control power transformer integral with controller where no other supply of 120 volt control power is indicated. Provide control power transformer with adequate capacity to operate connected pilot, indicating and control devices, plus 100 percent spare capacity. 2.Combination Controller: a.Circuit Breaker Type: NEMA AB 1. Motor circuit protector; molded-case circuit breaker type with magnetic only trip element calibrated to coordinate with the actual locked rotor current of the connected motor and the controller overload relays. Provide breakers that are factory assembled with the controller, interlocked with unit cover or door, and arranged to disconnect the controller. Provide motor circuit protectors with field adjustable trip elements as specified in "Overcurrent Protective Devices." b.Fuse Type: NEMA KS 1. Enclosed knife switch with externally operable handle. Fuse interrupting rating: 200,000 rms amperes. Fused or non-fused as indicated; quick-make, quick-break switch; factory assembled with controller and arranged to disconnect it. For fused switches, provide rejection-type fuse clips and fuses rated as indicated. Interlock switch with unit cover or door. A.Multispeed motor controllers: Match controller to motor type, application, and to number of speeds. Conform to the requirements for magnetic motor controllers. Provide auxiliary devices as indicated. Provide auxiliary switches, 2 N.O. and 2 N.O., except as otherwise indicated. Provide all required relays factory installed in controller enclosure. 2.15 LIGHTING A.Manufacturers: As indicated herein, and as shown on the Lighting Fixture Schedule. B.Lighting Fixtures, General: 1.Work covered includes manufacturing, equipping, wiring, and assembling of all lighting fixtures. Provide lighting fixtures complete for each and every light outlet in the type, quality, and size of fixture indicated in lighting fixture schedule. 2.The lighting fixtures shown on fixture schedule are marked with the corresponding type letter, indicating thereby the particular type of fixture to be installed on the respective outlets. 3.Include a lighting fixture on every light outlet shown, unless otherwise indicated to be omitted. If the type of lighting fixture is not specifically noted, provide without extra cost to the Owner, a lighting fixture of the same type called for under a similar condition elsewhere on the Contract Drawings. 4.Catalog number on the lighting fixture schedule are for the purpose of indicating the general type, quality, and size of fixtures that will be required. The use of Catalog Numbers for a lighting fixture does not necessarily include all accessories that may be required for a complete and operational installation. 5.All luminaries and other lighting equipment delivered to the job complete, wired and including all supporting means, such as plaster frames, supports, hangers, canopies, sockets, holds, all current or voltage modifiers, such as ballasts, starters, all light control materials; specifically diffusers, louvers, lenses, reflectors and refractors. 6.All lighting fixtures constructed and installed in accordance with local building codes and directives by the NFPA and shall bear the label of approval of the U.L. All materials new and of best grade of approved manufacturing standards. Workmanship of highest order to assure trouble-free operation and durability of equipment. Lighting fixtures constructed by labor agreeable with that employed on the project. 7.Lighting fixtures to be designed for highest relative efficiency and service. Maintenance to be simple and re-lamping possible without use of special tools. 8.Provide all light-sources, lamps and other light-producing media called for and suitable for specified equipment and functions. C.Lighting fixtures: 1.Luminaries to use not less than #16 gauge SF-2 wire. No splice or tap located within a fixture arm, stem or chain. Wire continuous from lamp socket, or from internally mounted ballast or driver, to splice with building wire whether splice box is mounted on fixture or attached to building. 2.Lighting fixture body parts, comprising the lighting fixture housing, reflectors, wire channels, end plates, ballast housing, and similar body parts, to be made of extruded aluminum, galvanized stampings, or bonderized steel, as indicated in the lighting fixture schedule. Wireways to have adequate wiring space, accessible after fixture installation. Housing adequately ventilated where required. All screws and nuts have rust-proof finish. 3.Where recessed lighting fixtures are installed in ceiling finished with acoustical tile or grid system, the lighting fixture shall conform to the patterns indicated on the Architectural Reflected Ceiling Plan. 4.The final installation must present a symmetrical appearance, with all lighting fixtures free of any damage and thoroughly clean. 5.Provide all additional means necessary to support lighting fixtures that would put excessive stress on the ceiling system. 6.Lighting fixtures mounted end-to-end and used as a raceway to be mechanically bonded together to insure continuity of ground. Lighting fixtures used as "feed through" to have wireways of adequate size. 7.All plastic lens of shielding for fluorescent lighting fixtures to be made from 100% virgin acrylic unless otherwise specified. D.Additional Fixture Related Requirements: 1.Recessed lighting fixtures in plaster or drywall ceilings to be furnished with plaster frames. 2.Lighting fixtures recessed in furred ceiling installed so that they can be removed from below the ceiling without damage to the ceiling. 3.Recessed lighting fixtures to be installed with metal bar hangers for attaching to ceiling supports. Lighting fixtures not supported directly from ceiling, provide galvanized steel wire as required for supporting lighting fixture from structure. No wood or other combustible material to be used for supporting fixtures. 4.Provide stems with swivel joints and canopies for all suspended lighting fixtures. Finish of all exposed parts to match that of the associated fixture, unless otherwise noted. Design to conform to Drawings. Wiring to pendant fixtures contained within stems. Wire entry by means of heavy malleable iron hickeys. 5.A canopy to be furnished for each stem and all canopies to match for each fixture type, as shown. 6.Ascertain type of ceiling construction for each fixture and provide suitable frames and fixture accessories to suit. Furnish substantial mounting frames or plaster rings for all recessed and semi-recessed lighting fixtures indicated or required. All frames made of galvanized steel with extra cross members where required to insure maintenance or proper opening dimensions during installation. E.Accessories: 1.Provide manufacturer's standard mounting rings, trim flanges, hanger bars, spacers, supports, plaster frames of nonferrous material or cadmium plated steel. Do not use painted steel plaster frames. DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 ELECTRICAL SPECIFICATIONS IE-0.03 PART 3 - EXECUTION 3.01 INSTALLATION A.General: The electrical installation shall conform to the requirements of NFPA 70, "National Electrical Code," and to the requirements specified herein. B.Wiring Method: The wiring method shall be as follows, except as otherwise noted. 1.Exterior: a.Exposed: Rigid steel conduit. b.Concealed: Rigid steel conduit. 1)In or under slab on grade: Nonmetallic conduit, Schedule 40 PVC. Conduit leaving the slab (including exposed conduit riser) shall be rigid steel conduit. 2)Underground: Rigid nonmetallic conduit. Use Schedule 40 PVC. Provide concrete encasement as indicated. c.Connection to vibrating equipment, including transformers and hydraulic, pneumatic, or electric solenoid or motor-driven equipment: Liquidtight flexible metal conduit, maximum length 18". 2.Interior: a.Exposed: Electrical metallic tubing. 1)Areas where exposed conduit may be subject to physical damage: Rigid metal conduit. 2)Damp or wet locations: Rigid metal conduit. 3)Classified locations: Rigid metal conduit. b.Concealed: Electrical metallic tubing. 1)In or under slab on grade: Nonmetallic conduit, Schedule 40 PVC. Conduit leaving the slab (including exposed conduit riser) shall be rigid steel conduit. 2)In slab, above grade: Rigid nonmetallic conduit Schedule 40 PVC. Maximum size conduit in slab: 1". c.Connection to vibrating equipment, including transformers and hydraulic, pneumatic, or electric solenoid or motor-driven equipment: Flexible metal conduit, maximum length 18". 1)For moist or humid locations or corrosive atmosphere, or where subject to water spray or dripping oil, grease, or water: Liquidtight flexible metal conduit. d.Connection to lighting fixtures located in suspended acoustical or metal ceilings: Flexible metal conduit, maximum length 72". e.Final connections to lighting fixtures which have isolated junction boxes: Flexible metal conduit. 1)Damp locations: Liquidtight flexible conduit. C.Grounding and Bonding: 1.General: Grounding shall be provided in accordance with all applicable codes and regulations and the local authorities having jurisdiction. 2.An equipment grounding conductor shall be provided in all raceway containing phase conductors. 3.The maximum resistance to ground shall not exceed 5 ohms. D.Raceway Installation: 1.General Requirements: Install electrical raceways in accordance with manufacturer's written installation instructions, applicable requirements of NEC, and as follows. a.Minimum size: 3/4" unless otherwise indicated. b.Size conduits as indicated on the drawings and as required by the NEC for the number and sizes of wires to be installed into the conduit. c.Make conduit field cuts square with saw and ream out to full size. Shoulder conduits in couplings. Remove burrs, and swab inside conduits before conductors are pulled in. d.Make all conduit joints mechanically tight, electrically continuous, and watertight. Pitch conduits in a manner to avoid creating moisture traps. e.Install minimum 1/8" polypropylene pull cords from end-to-end in all empty raceways, tagged with the identification of service intended and location of opposite end. Leave at least 24" of pull cord at each end. f.Restore wall, ceiling, and floor penetrations to the requirements of the Authority Having Jurisdiction. g.Communications/Signal System Raceways 2" Trade Size and Smaller: In addition to the above requirements, install raceways 2" and smaller trade size in maximum lengths at 150'-0" and with a maximum of two, 90° bends or equivalent. Install pull or junction boxes where necessary to comply with these requirements. h.Provide code sized green grounding conductor in all conduit. 2.Perform excavating, trenching, backfilling, and compacting as shown, and as specified in Division 02 which prescribes excavation, backfilling and compacting for utilities. Minimum cover for runs below finished grade outside buildings: 24" except where noted. 3.Complete installation of electrical raceways before starting installation of conductors within raceways. a.Protect inside of conduit from dirt and rubbish during construction by capping all openings with plastic caps intended for the purpose. Cap or plug conduits with standard manufactured accessories as soon as the conduits have been permanently installed in place. 4.Install all conduits at elevations and locations to avoid interference with grading or other work, the structure, finished ceilings, walls. Avoid causing cutting of masonry structural members. a.Do not place conduits in close proximity to equipment, systems, and service lines, such as hot water supply and return lines, which could be detrimental to the conduit and its contents. Maintain a minimum 3" separation, except in crossing, which shall be a minimum 1". 1)Minimum separation from uninsulated hot water pipes, steam pipes, heater flues or vents: 6". Avoid running conduit directly under water lines. 2)Elevation of Raceway: Where possible, install horizontal raceway runs above water and steam piping. 5.Conceal conduit, unless indicated otherwise, within finished walls, ceilings, and floors. Keep raceways at least six 6" away from parallel runs of flues and steam or hot water pipes. Install raceway level and square and at proper evaluations. a.To prevent displacement, securely support and hold in place all conduits installed in advance of other work and to be concealed in the building structure. Carefully lay out conduits run within the structure, such as floors, beams, walls, to avoid densities excessive for the construction. Relocate those conduits when excessive densities occur. b.Run conduits embedded in structural slabs in the middle of the slab below the top and above the bottom reinforcing steel. Minimum cover for conduit in concrete floors, walls or roof: 1/3 thickness of slab, but in no case less than 1-1/2" cover except where penetration is made. Do not install conduit larger than 1" in slabs. Tie raceways to reinforcing rods or otherwise secure them to prevent sagging or shifting during concrete placement. Space raceways laterally to prevent voids in the concrete. Where nonmetallic conduit is used, raceways must be converted to Schedule 80 or rigid steel conduit before rising above the floor. c.Where conduit installed in concrete or masonry extends across building construction joints, provide expansion fittings as manufactured by O.Z.; Crouse-Hinds; Appleton; or equal, with approved ground straps and clamps. Expansion fittings installed in concrete shall be water tight, concrete tight, deflection/expansion type. d.Run concealed raceways with a minimum of bends in the shortest practical distance considering the type of building construction and obstructions except as otherwise indicated. This does not apply to conduits in crawl spaces. 6.Install and neatly rack exposed conduits parallel with and perpendicular to building walls. Do not install exposed diagonal conduit runs. a.Run exposed, parallel, or banked raceways together. Make bends in parallel or banked runs from the same center line so that the bends are parallel. Factory elbows may be used in banked runs only where they can be installed parallel. This requires that there be a change in the plane of the run such as from wall to ceiling and that the raceways be of the same size. In other cases provide field bends for parallel raceways. b.Use blockouts for concentrations of conduits in a confined area. c.Route and suspend conduits crossing expansion joints to permit expansion, contraction, and deflection utilizing approved fittings to prevent damage to the building, conduits, and supporting devices. d.Install exposed raceways parallel and perpendicular to nearby surfaces of structural members and follow the surface contours as much as practical. e.Provide conduit bodies for exposed conduit runs at junctions, bends or offsets where required. Do not use elbows or bends around outside corners of beams, walls or equipment. Make conduit body covers accessible. 7.Concrete Wall or Stab Penetrations: All core drilling, sleeves, blockouts or other penetrations must be approved by the Structural Engineer prior to installation. a.Space sleeves and core drills to insure a minimum dimension of 3 times the nominal trade diameter of the largest adjacent conduit between sleeves or core drills. b.Use blockouts for concentrations of conduits in a confined area. 8.Join raceways with fittings designed and approved for the purpose and make joints tight. Where joints cannot be made tight, use bonding jumpers to provide electrical continuity of the raceway system. Make raceway terminations tight. Where terminations are subject to vibration, use bonding bushings or wedges to assure electrical continuity. Where subject to vibration or dampness, use insulating bushings to protect conductors. 9.Make bends and offsets so the inside diameter is not effectively reduced. Unless otherwise indicated, keep the legs of a bend in the same plane and the straight legs of offsets parallel. f.Make no bends with a radius less than 12 times the diameter of the cable it contains nor more than 90°. Make field bends with tools designed for conduit bending. Heating of metallic conduit to facilitate bending is not permitted. g.Bends and offsets in 1" and smaller conduits may be done with approved bending devices. Do not install conduits which have had their walls crushed and deformed and their surface finish damaged due to bending. c Run conduits parallel to and at right angles to building lines. d.Where space conditions prohibit the use of standard ells, elbows, and conduits, use cast ferrous alloy fittings of such forms and dimensions as best required for application. 10.Surface Raceway: a.Install a separate green ground conductor in raceway from the junction box supplying the raceway to receptacle of fixture ground terminals. b.Select each surface raceway outlet box to which a lighting fixture is attached to be of sufficient diameter to provide a seat for the fixture canopy. c.Where a surface raceway is used to supply a lighting fixture having central stem suspension with a backplate and a canopy, with or without extension ring, the backplate and canopy will serve as the outlet box and no separate outlet box need be provided. d.Provide surface raceway outlet box, in addition to the backplate and canopy, at the feed-in location of each lighting fixture having end stem suspension. e.Where a surface raceway extension is made from an existing outlet box on which a lighting fixture is installed, provide a backplate slightly smaller than the fixture canopy, and no additional surface mounted outlet box need be installed. f.Surface raceways shall be securely fastened to the mounting surface. Use expansion type anchors in concrete. 11.Do not run conduits exposed on the roof unless approval is obtained from the Owner prior to installation. 12.Other Requirements: a.Connect motors, equipment containing motors, equipment mounted on an isolated foundation, transformers, and other equipment and devices which are subject to vibration and which require adjustment with liquidtight flexible metallic conduit from the device to the conduit serving it. Size the flexible conduit length more than 12 diameters, but less than 18 diameters. Rigidly support the points of attachment on each side of the connection. Use external bonding jumpers on sizes 1-1/2" and above. b.Install escutcheons on all exposed conduits passing through interior floors, walls, or ceilings. Install fire seals on all conduits passing through fire rated partitions. Install wall and floor fire seals on all conduits passing through exterior walls and floors, or use standard galvanized steel pipe sleeves; diameters 12" greater than the outside diameter of the sleeved conduit and fill the annular space with mastic or caulk with lead. c.Fire pump room: All wiring shall be installed in rigid metal, liquidtight flexible metal conduit. d.Raceway for panelboards: 1)All homeruns shown shall be run to the panel indicated independently of all other homeruns. Provide pull points so as not to exceed total bends of 270°. 2)Run a minimum of one 3/4" empty conduit for every three single pole spare circuit breakers, spaces or fraction thereof and not less than two 3/4" conduits from every flush mounted panel to an accessible space above the ceiling and below the floor. e.Make conduit projections from covered areas to areas exposed to the weather watertight by proper flashing. Extend flashing a minimum of 6" in all directions from conduit. f.Cap conduits indicated to be stubbed-out underground using glued on PVC caps intended for this purpose. g.Install a coupling flush with the floor on all conduits stubbed-up through the floor slab. h.Do not penetrate walls with flexible conduit where subject to physical damage. Use recessed box with extension ring for transition from interior to exterior of wall. i.Terminations: 1)Where raceways are terminated with locknuts and bushings, align the raceway to enter squarely and install the locknuts with dished part against the box. Where terminations cannot be made secure with one locknut, use two locknuts, one inside and one outside the box. 2)Where terminating in threaded hubs, screw the raceway or fitting tight into the hub so the end bears against the wire protection shoulder. Where chase nipples are used, align the raceway so the coupling is square to the box, and tighten the chase nipple so no threads are exposed. 3)At switchboards, manholes and floor standing distribution panelboards, provide insulated throat bushings or bell ends on all non-metallic conduit entries and bushings on all metallic conduit entries. 4)Install insulated throat threaded hubs on conduits entering enclosures without threaded hubs. 5)Install end bells on conduits stubbed through slabs and foundations into electrical enclosures. j.Install raceway sealing fittings in accordance with the manufacturer's written instructions. Locate fittings at suitable, approved, accessible locations and fill them with UL Listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a blank cover plate having a finish similar to that of adjacent plates or surfaces. Install raceway sealing fittings at the following points and elsewhere as indicated: 1)Where conduits enter or leave hazardous locations. 2)Where conduits pass from warm locations to cold locations, such as the boundaries of refrigerated spaces and air conditioned spaces. 3)Where required by the NEC. k.Stub-up Connections: Extend conduits through concrete floor for connection to freestanding equipment with an adjustable top or coupling threaded inside for plugs and set flush with the finished floor. Extend conductors to equipment with rigid steel conduit; flexible metal conduit may be used 6" above the floor. Where equipment connections are not made under this contract, install screwdriver operated threaded flush plugs flush with floor. 1)Protect stub-ups from damage where conduits rise from floor slabs. Arrange so that curved portion of bends is not visible above the finished slab. l.Flexible Connections: Use short length (maximum of 6'-0") of flexible conduit for recessed and semi-recessed lighting fixtures, for equipment subject to vibration, noise transmission, or movement; and for all motors. Use liquidtight flexible conduit in wet locations. Install separate ground conductor across flexible connections. m.PVC Coated Rigid Steel Conduit: 1)Do not store conduit in direct sunlight. 2)Use pipe straps, no pipe wrenches or channel wrenches, when tightening connections to avoid damaging PVC coating. 3)Patch all gouges or cuts in the PVC coating after installing conduit. Use manufacturer's recommended patching paste. Build up area to be patched to full mil thickness of coating and feather out paste on sides of damaged area a minimum of 1/2" to provide a completely bonded seal. 4)Field bend conduit with shoes for a mechanical bender sized for the next larger size conduit. 5)Bends used in or below concrete slabs shall be, rigid steel type elbows, use for all stub-ups with flush floor coupling at transitions. n.Use raceway fittings that are of types compatible with the associated raceway and suitable for the use and location. For intermediate steel conduit, use threaded rigid steel conduit fittings except as otherwise indicated. I.Underground Duct Banks: 1.Exercise care in excavating, trenching and working near existing utilities. Trenching and backfill: a.Contractor shall trench underground duct path and manhole location with utmost care in order to avoid existing underground facilities. Trench size shall be kept to a minimum. No oversized trench shall be made unnecessarily. b.All trench excavations by the Contractor shall be backfilled by same in accordance with this specification. c.All material excavated during underground electrical work is not pre-qualified for backfill. d.All fill must be placed in layers not exceeding 8" in depth and hand tamped or machine compacted to at least 95% of its maximum dry density as computed by the ASTM method of performing a compaction test (D-1557-70). G.Lighting: 1.Inspect Architectural drawings and specifications, including ceiling alternates, to determine ceiling material to be installed. 2.Inspect Architectural reflected ceiling plans. 3.Inspect installed ceiling components for defects affecting the quality and execution of work. 4.Preparation: b.Verify ceiling material and alignment. c.Lay out exact locations of fixtures in accordance with reflected ceiling plans, fixtures' and switches' outlet boxes and supports. d.Provide outlet boxes and conduit. e.Provide appropriate hardware and fixture accessories to support from ceiling system. 5.Installation: a.Installation of all lighting fixtures done by experienced electrician. Lighting fixtures not installed where finished coat of paint has been applied to ceiling and walls until paint is thoroughly dry. Verify ceiling type with architectural plan and provide all necessary framing and mounting hardware. b.Contractor to be responsible for proper coordination of all lighting fixture locations. Provide support for all lighting fixtures mounted on or recessed in hung ceiling. Confer with Ceiling Contractor and other trades to coordinate lighting systems. c.Lighting fixtures to be rigidly mounted to fixture stud in outlet boxes. Malleable iron hickeys or extension pieces provided where required. d.Provide suitable coverplate or canopy for each lighting fixture outlet box where the lighting fixture does not provide a suitable cover. e.Lighting fixtures located on exterior of building installed with cadmium plated brass screws and gasketed. f.Lighting fixture to be installed in suspended T-Bar ceiling shall be attached to the ceiling grid with an attachment device with a capacity capable to resist a force equal to the weight of the light fixture acting in any direction. Lighting fixtures shall be supported directly from the structure above by hangers capable of supporting the weight of the fixture with #12 galvanized steel wire from all 4 corners. g.Verify all ceiling heights and clearances if mounting height is not indicated on plans or in lighting fixture schedule, or if lighting fixture is relocated because of a conflict with another trade. A mounting height for the lighting fixture is to be submitted for review. h.Each lighting fixture completely wired in an approved manner with #14 AWG copper stranded wire, 600 volt, with type SF-2 insulation; recessed lay-in lighting fixtures furnished with 7'-0" #14 SF wire and 6'-0" Greenfield, when installed in an air plenum. i.Circuit wiring running through the lighting fixtures to be #12 AWG with type SF insulation. No joints in the wires other than those absolutely required. Provide wires of sufficient length for making approved connections at the light outlets and at the lampholders or ballasts. j.Joints and splices within lighting fixtures to be either soldered and taped with plastic electrician's tape or secured by wire nuts or indent type lug fasteners. k.Protect the lighting fixtures from damage during their unloading or removal, storage or installation, any broken fixtures, lenses, etc., must be replaced with new parts, without any additional expense to the Owner, undue delay or inconvenience. l.Upon completion of the installation of the lighting fixtures and lighting equipment, they must be in first-class operating order and in perfect condition as to finish, etc. Check for proper operation and appearance, alignment of fixtures and proper placement of lenses, louvers, lamps and other light-controlling or modifying appurtenances. m.Where special lighting effects, flood or spotlighting is involved, perform final adjustment under the direct supervision of Architect. n.Cleaning: Immediately prior to occupancy, damp clean all lenses, lighting fixture trims, reflectors, clean lamps or install new lamps as directed, with lenses and fixtures free of labels. o.Use of Lighting Fixtures: As soon as any portion of lighting fixture work is ready for operation, the Owner shall have the right to operate under the supervision of the Contractor. This shall in no way be interpreted to mean the acceptance of such part of the installation or relieve the Contractor of his responsibility for the complete work or any part thereof. p.Color and type of finish of all lighting fixtures as approved by the Architect. q.Install fixtures and accessories in accordance with manufacturer's recommendations and industry standard practice. r.Coordinate work of this section with that of other trades. s.Provide lighting fixtures, lamps, switches, and control systems, and wiring. t.If designation omitted on drawings, provide same type fixture employed in rooms of similar usage (contact this engineer for final direction). u.Provide spacers for fixtures mounted on low density ceiling material. v.Provide plaster frames for recessed fixtures in plaster ceilings. w.Install fixtures in fiber decking and formboard so outlet boxes and openings will not be sight exposed. x.Prepare fixtures and trim required to be painted. y.Outlet boxes locations on drawings are diagrammatic only. Position outlet boxes to coincide with suspension hangers and knock-outs. z.Install in accordance with manufacturer's instructions, submittal data, and details on drawings. 6.Adjustment and cleaning: a.Adjust lamp positions for desired effects. 1)Align fixtures with building walls and tile joints. b.Cleaning: 1)Remove dirt, grease, and foreign materials from fixtures. 2)Remove fingerprints, smudges, and dirt from fixtures' lenses and lamps. 3.02 FIELD QUALITY CONTROL A.Examine surfaces to which conduits are to be secured for: 1.Defects which will adversely affect the execution and quality of work. 2.Deviations from allowable tolerances for the building material. B.Do not start work until defects and deviations are corrected. 3.03 CLEANING A.Upon completion of installations of raceways, inspect interiors of raceways; clear all blockages and remove burrs, dirt, and construction debris. 3.04 PROTECTION OF FINISHED WORK A.Protect inside of conduit from dirt and rubbish during construction by capping all openings with plastic caps intended for the purpose. B.Protect stub-ups from damage where conduits rise from floor slabs. Arrange so curved portion of bends is not visible above the finished slab. 3.05 GROUNDING A.Electrically ground metallic cabinets, boxes, and enclosures. Where wiring to item includes a grounding conductor, provide a grounding terminal in the interior of the cabinet, box, or enclosure. 3.06 CLEANING AND FINISH REPAIR A.Upon completion of installation, inspect components. Remove burrs, dirt, and construction debris and repair damaged finish including chips, scratches, abrasions and weld marks. Clean surfaces to be painted. B.Galvanized finish: Repair damage using a zinc-rich paint recommended by the manufacturer. C.Painted finish: Repair damage using matching corrosion-inhibiting touch-up coating. e.All compacted fill will be under continuous inspection by the Inspector. Compaction tests will be arranged for by the Inspector in cooperation with the Contractor. i.Puddling or water-flooding for settling backfill will not be permitted except in landscaped areas. The addition of water shall be limited to achieving optimum moisture content for tamp procedures. f.Where Contractor trenches crosses any finished road (paved or gravel), he shall be responsible for restoring the road to its original condition. Repaving shall be with the same surrounding material and to a quality equal or exceeding its surround. g.Do not backfill for a period of at least 24 hours after pouring concrete. Upon receipt of the Inspector's approval proceed with backfill. Backfill with 1 sack slump concrete and repair of surface to be completed within 24 hours of approval. Provide wet sand backfill in landscape areas. h.Survey slope of trenches and ducts between terminations to provide drainage. No pockets shall be permitted. 2.Underground Duct with Concrete Encasement: a.Underground ductbanks lines shall be constructed of individual conduits encased in concrete. Conduit shall be of PVC Schedule 40. The kind of conduit used shall not be mixed in any one duct bank. PVC ducts shall not be smaller than 2" in diameter unless otherwise indicated. The concrete encasement surrounding the bank shall be rectangular in cross-section and shall provide at least 3" of concrete outer encasement for ducts. Conduit shall be separated by a minimum concrete thickness of 2". b.The top of the concrete envelope shall not be less than 30" below grade, except that under roads and pavement it shall be not less than 36" below grade. c.Ductbanks shall have a continuous slope downward toward manholes with a pitch of not less than 1-1/2" in 100'-0". Except at conduit risers, changes in direction of runs exceeding a total of 10°, either vertically or horizontally, shall be accomplished by long sweep bends having a minimum radius of curvature of 25'-0". Sweep bends may be made of one or more curved or straight sections or combinations thereof. Manufactured bends shall have a minimum radius of 24" for use with conduits of less than 3" in diameter and a minimum radius of 48" for ducts of 3" in diameter and larger. d.PVC conduits shall terminate in end-bells where duct lines enter pullboxes or manholes. Separators shall be of precast concrete, high-impact polystyrene, steel, or any combination of these. The joints of the conduits shall be staggered by rows and layers so as to provide a duct line having maximum strength. e.During construction, partially completed duct lines shall be protected from the entrance of debris such as mud, sand, concrete and dirt by means of suitable conduit. As each section of a duct line is completed, a testing mandrel not less than 12" long with a diameter 1/4" less than the size of the conduit shall be drawn through each conduit, after which a brush having the diameter of the duct and having stiff bristles shall be drawn through the conduit until it is clear of all particles of earth, sand, or gravel. Conduit plugs shall then be immediately installed. f.Locate spacers no greater than 5'-0" center to center, along entire length of ductbank. g.Duct couplings may be placed side by side horizontally, but staggered at least 6" vertically. h.Make conduit joints in accordance with manufacturer's recommendations. In the absence of specific recommendations, make the joints as follows: 1)Brush a plastic solvent cement on the inside of the coupling and on the outside of the duct ends. 2)Slip duct and fitting together with a quick one-quarter turn to set the joints. i.Follow ductbank sections on the drawings for size, arrangement and spacing of ducts. j Secure ducts and spacers to prevent movement during placement of concrete. k.At connection to existing manhole, dowel the concrete encasement with one #4 reinforcing bar 36" long per duct. (Minimum of two required.) l.Provide a #2/0 soft bare copper ground conductor throughout the continuous length of ductbanks containing conductors having more than 150 volts to ground. m.Concrete; in accordance with the following: 1)Provide #4 rebar dowels at each concrete joint/pour transition. A minimum of 8'-0" long #4 rebar dowel, one per conduit in ductbank. 2)Provide rebar and tie-downs to prevent conduits from floating to top of concrete during curing. 3)Make ductbank construction monolithic top to bottom and side to side. 4)Do not exceed the outside dimension of the completed ductbank by more than 1" in the vertical or 4" in the horizontal from dimensions indicated. 5)Use plastic film to retain moisture for proper curing. n.Ductbank concrete may be poured without forming, provided trench walls are firm and will not cave in during installation. Unless noted otherwise, encase the raceway on all sides with a minimum of 3" of concrete. o.Where conduits are stubbed out for future connection, stop concrete 12" from end of conduit. Provide a waterproof cap on the end of the conduit. p.The top of the concrete ductbank shall be as shown on the drawings, or as otherwise required by code and as required to coordinate with other underground obstructions. 3.Connections to Existing Ducts: Where connections to existing duct lines are indicated, excavate the lines to the maximum depth necessary. Cut off the lines and remove loose concrete from the conduits before installing new concrete encased ducts. Provide a reinforced concrete collar, poured monolithically with the new duct line, to take the shear at the joint of the duct lines. Remove existing cables which constitute interference with the work. 4.Connection to Existing Handholes and Manholes: For duct line connections to existing structures, break the structure wall out to the dimensions required and preserve steel in the structure wall. Cut steel and band out to tie into the reinforcing of the duct line encasement. Chip out the structure wall to form a key for the duct line encasement. 5.Connections to Existing Concrete Pads: For duct line connections to concrete pads break an opening in the pad out to the dimensions required and preserve steel in pad. Cut the steel and bend out to tie into the reinforcing of the duct line encasement. Chip out the opening in the pad to form a key for the duct line encasement. 6.Removal of Ducts: Where duct lines are removed from existing manholes, close openings and waterproof manhole. Chip out the wall opening to provide a key for the new section of wall. 7.Precast pullboxes shall be of sizes required. F.Installation of boxes and fittings: 1.Outlet boxes and Fittings: Install outlet and device boxes and associated covers and fittings of materials and NEMA types suitable for each locations and in conformance with the following requirements, except as otherwise indicated: a.Interior dry locations: NEMA type 1, sheet steel. 1)In dry walls for single and two gang outlets provide 4S and 4D boxes, for 3 or more outlets use masonry boxes. 2)In block and masonry walls provide masonry boxes of depths required for wall thickness. 3)In poured concrete and plastered walls provide 4S and 4D boxes for single gang outlets and 2G and 3G-5075 boxes for multiple ganged outlets. 4)In concrete ceilings provide OCR rings. In other ceilings provide 40 and 40D boxes. Omit covers if standard canopy and device plates entirely cover the ceiling opening. b.Locations exposed to weather or dampness: Cast metal, NEMA type 3R. c.Wet locations: NEMA type 4 enclosures. 1)In exposed work, exterior of buildings, in wet location, and flush in non-waterproofed walls below grade provide FS and FD boxes. d.Corrosive locations: NEMA type 4X enclosures. e.Hazardous (Classified) locations: Cast metal, UL 886, NEMA type listed and labeled for the location and class of hazard indicated. 2.Pull and Junction Boxes: Install pull and junction boxes of materials and NEMA types as follows, except as otherwise indicated: a.Interior dry locations: NEMA type 1, sheet steel. b.Locations exposed to weather or dampness: NEMA type 3R, sheet steel. c.Wet locations: NEMA type 4 enclosures. d.Corrosive locations: NEMA type 4X enclosures. e.Hazardous (Classified) locations: Cast metal, UL 886, NEMA type listed and labeled for the location and class of hazard indicated. 3.Floor Boxes: In slabs on grade and wet locations: Use NEMA type 4 boxes. At other locations in slabs, use concrete-tight NEMA 1 boxes. a.Provide floor boxes with quantity of gangs as required for power, communication or control as indicated. Use boxes with barriers where required. Provide carpet flanges in carpeted areas. 4.Hinged Door Enclosures: NEMA type 12, except as indicated. 5.Hinged Door Enclosures Outdoors: NEMA type 3R, with drip hood, factory tailored to individual units. 6.Hinged Door Enclosures in Corrosive Locations: NEMA type 4X metal enclosure. 7.Cabinets: Flush mounted, NEMA type 1, except as otherwise indicated. DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 ELECTRICAL SPECIFICATIONS IE-0.04 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 LIGHTING FIXTURE SCHEDULE IE-0.05 · · · DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 MECHANICAL AND PLUMBING EQUIPMENT CONNECTIONS IE-0.06 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 ELECTRICAL DETAILS IE-0.07 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 § § § SINGLE LINE DIAGRAM IE-0.10 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 SHORT CIRCUIT CALCULATION IE-0.11 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 PANEL SCHEDULES IE-0.20 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 PANEL SCHEDULES IE-0.21 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 PANEL SCHEDULES IE-0.22 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 LIGHTING CONTROLS IE-0.30 · · · · · · · · · · · EscF1F2F3F4F5F6F7F8F9F10F11F12ºª\1!|"@·#$&¬/%()=?¡¿23456789'0 QWE€RTYUIOP ASDFGHJKLÑ ZXCVBNM;,:._->< ^[`*]+¨´Ç BloqmayúsControlAltAlt GrControl ImprPantPet sisBloqDesplPausaInterRePágAvPágInicioInsertSuprFinBloqNum/-*+ Intro 123456789 FinAvPág InicioRePág Ins0Supr. NumLockCapsScrollLockLocketh LL LL LL GARRY AVENUE HA R B O R B L V D . DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 ELECTRICAL SITE PLAN IE-1.0 EscF1F2F3F4F5F6F7F8F9F10F11F12 ºª\1!|"@·#$&¬/%()=?¡¿23456789'0 QWE€RTYUIOP ASDFGHJKL Ñ Z XCVBNM;, :._->< ^[`*]+¨´Ç Bloqmayús ControlAltAlt GrControl ImprPantPet sisBloqDesplPausaInter RePágAvPág Inicio InsertSuprFin BloqNum/-* + Intro 123456 789 FinAvPág InicioRePág Ins0Supr. NumLockCapsScrollLockLock eth LL LL LL 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR 402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 OFFICE 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH 308 WAREHOUSE OFFICE 111 RECEIVING 116 DIGITAL PHOTO 123 STORAGE 127 SHIPPING 303 MAINTENANCE WALK-IN REFRIGERATOR BY OTHERS EXISTING TRASH ENCLOSURE TO REMAIN FUTURE SECURE AREA 304A MEN 304B WOMEN NEW 8'-0" HIGH OPENING SERVER EQUIPMENT RACK (BY OTHERS) 113 IT 5 B DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 OVERALL FIRST FLOOR POWER AND SIGNAL PLAN IE-1.1 1 A B C D C.6 C.5 2 3 4 5 6 201 OFFICE 200 EXECUTIVE OFFICE 202 LOUNGE 203 RESTROOM 204 STORAGE 206A VETIBULE 205 STOR 206 OPEN OFFICE 207 OFFICE 208 MEN 209 WOMEN210 JAN 204A STOR 1 A B C D C.6 C.5 2 3 4 5 6 201 OFFICE 200 EXECUTIVE OFFICE 202 LOUNGE 203 RESTROOM 204 STORAGE 206A VETIBULE 205 STOR 206 OPEN OFFICE 207 OFFICE 208 MEN 209 WOMEN210 JAN 204A STOR DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 OVERALL SECOND FLOOR POWER AND SIGNAL PLAN IE-1.2 1 A B C D C.6 C.5 2 3 4 5 6 1 1 1 A B C D C.6 C.5 2 3 4 5 6 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 ROOF ELECTRICAL PLAN IE-1.3 EscF1F2F3F4F5F6F7F8F9F10F11F12 ºª\1!|"@·#$&¬/%()=?¡¿ 23456789'0 QWE€RTYUIOP ASDFGHJKLÑ ZXCVBNM;, :._ ->< ^[`*]+¨´Ç Bloqmayús ControlAltAlt GrControl ImprPantPet sisBloqDesplPausaInter RePág AvPág Inicio Insert SuprFin BloqNum/-* + Intro 1234 56 789 FinAvPág InicioRePág Ins0Supr. NumLockCapsScrollLockLock eth LL LL LL 1 A B C D C.6 C.5 2 3 4 5 6 WALK-IN REFRIGERATOR BY OTHERS EXISTING TRASH ENCLOSURE TO REMAIN FUTURE SECURE AREA NEW 8'-0" HIGH OPENING 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR 402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 OFFICE 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH 308 WAREHOUSE OFFICE 111 RECEIVING 116 DIGITAL PHOTO 123 STORAGE 127 SHIPPING 303 MAINTENANCE +12'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" WALK-IN REFRIGERATOR BY OTHERS 304A MEN 304B WOMEN DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 OVERALL FIRST FLOOR LIGHTING PLAN IE-2.1 1 A B C D C.6 C.5 2 3 4 5 6 201 OFFICE 200 EXECUTIVE OFFICE 202 LOUNGE 203 RESTROOM 204 STORAGE 206A VETIBULE 205 STOR 206 OPEN OFFICE 207 OFFICE 208 MEN 209 WOMEN 210 JAN +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +9'-0" +8'-0" +8'-0" 1 A B C D C.6 C.5 2 3 4 5 6 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 OVERALL SECOND FLOOR LIGHTING PLAN IE-2.2 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 OFFICE 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 OVERALL FIRST FLOOR POWER AND SIGNAL DEMOLITION PLAN IED-1.1 1 A B C D C.6 C.5 2 3 4 5 6 201 OFFICE 200 EXECUTIVE OFFICE 202 LOUNGE 203 RESTROOM 204 STORAGE 206A VETIBULE 205 STOR 206 OPEN OFFICE 207 OFFICE 208 MEN 209 WOMEN210 JAN DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 OVERALL SECOND FLOOR POWER AND SIGNAL DEMOLITION PLAN IED-1.2 1 A B C D C.6 C.5 2 3 4 5 6 DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 OVERALL FIRST FLOOR LIGHTING DEMOLITION PLAN IED-2.1 1 A B C D C.6 C.5 2 3 4 5 6 4 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ 5 IA-5.2‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒‒ DISCLAIMER This plan is for illustrative purposes only and shall not be used for construction or procurement of furniture. Existing conditions and access compliance have not been field verified; Hendy is not responsible for any conditions that differ from plan or that are out of compliance as a result. Furniture dealer shall verify that the final layout of furniture meets clearances required for egress as required by the authority having jurisdiction. NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE salasobrien.com Project No.: Irvine 8825 Research Drive Irvine, CA 92618 949.753.1553 2491-60812-00 1/8" = 1'-0" 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF AB/CD NO.DESCRIPTION DATE PLAN CHECK SUBMITTAL 03/17/25 PLAN CHECK RE-SUBMITTAL 06/06/251 OVERALL SECOND FLOOR LIGHTING DEMOLITION PLAN IED-2.2 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 SCHEDULES AND SHEET INDEX M-0.1 MCGUFF AB/CD MECHANICAL LEGEND, NOTES, NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 SCHEDULES M-0.2 MCGUFF AB/CD MECHANICAL EQUIPMENT NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR 402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 Room 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH 308 WAREHOUSE OFFICE 111 RECEIVING 116 DIGITAL PHOTO 123 STORAGE 127 SHIPPING 303 MAINTENANCE WALK-IN REFRIGERATOR BY OTHERS EXISTING TRASH ENCLOSURE TO REMAIN FUTURE SECURE AREA 304C MEN 304D WOMEN 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MECHANICAL PLAN M-2.1 MCGUFF AB/CD LEVEL 1 - PARTITION FLOOR NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1 A B C D C.6 C.5 2 3 4 5 6 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MECHANICAL ROOF PLAN M-3.1 MCGUFF AB/CD PARTITION NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 M-5.1 MCGUFF AB/CD MECHANICAL DETAILS NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 M-5.2 MCGUFF AB/CD TITLE 24 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 M-5.3 MCGUFF AB/CD TITLE 24 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 Keith Matoi 06-11-2025 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 M-5.4 MCGUFF AB/CD EXISTING OFFICE TITLE 24 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 M-5.5 MCGUFF AB/CD TITLE 24 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 Keith Matoi 06-11-2025 1 A B C D C.6 C.5 2 3 4 5 6 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MECHANICAL ROOF PLAN M-3.1 MCGUFF AB/CD PARTITION NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 PLUMBING ROOF PLAN P-3.1 NO. DESCRIPTION DATE PLAN CHECK SUBMITTAL 3/17/25 1 PRESCREEN CORRECTIONS 3/24/25 1 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 P-0.1 MCGUFF AB/CD PLUMBING LEAD SHEET NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 P-0.2 MCGUFF AB/CD PLUMBING SCHEDULES NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 PRIME AND WRAP ALL PIPE AND FITTINGS WITH 3M SCOTCHRAP 50 (10 MIL) PVC PIPE WRAP AND 3M PIPE PRIMER PER MANUFACTURER'S DIRECTIONS, OR INSTALL IN 8 MIL POLYETHYLENE ENCASEMENT IN ACCORDANCE WITH ANSI/AWWA STANDARD C105/A215-82 . BED AND BACKFILL WITH CLEAN ALKALIZED SAND . ALL COMPRESSED AIR PIPING IN THE METREX LAB SHALL BE OIL-FREE MEDICAL GRADE PIPING. 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 P-0.3 MCGUFF AB/CD PLUMBING SPECIFICATIONS NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1 A B C D C.6 C.5 2 3 4 5 6 101 LOBBY 101A RECEPTION 102 OFFICE 105 MEN 106 JAN 401 SOUTH STAIR 402 OFFICE 403 OFFICE 404 OFFICE 405 OFFICE 408 OFFICE 107 OFFICE 108 OFFICE 109 Room 112 OFFICE 113 IT 114 OFFICE 115 OFFICE 118 BREAK ROOM 121 LOBBY 119 MEN 120 WOMEN 120A NORTH STAIR 126 HALLWAY 122 OFFICE 124 OFFICE 125 CONF. 307 ELECTRICAL 311 PACKAGING 104 WOMEN 103 MECH 308 WAREHOUSE OFFICE 111 RECEIVING 116 DIGITAL PHOTO 123 STORAGE 127 SHIPPING 303 MAINTENANCE WALK-IN REFRIGERATOR BY OTHERS EXISTING TRASH ENCLOSURE TO REMAIN FUTURE SECURE AREA 3.9 3.9 304C MEN 304D WOMEN 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 PLUMBING PLAN P-2.1 MCGUFF AB/CD LEVEL 1 - PARTITION FLOOR NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 DN 1 A B C D C.6 C.5 2 3 4 5 6 201 OFFICE 200 EXECUTIVE OFFICE 202 LOUNGE 203 RESTROOM 204 STORAGE 206A VETIBULE 205 STOR 206 OPEN OFFICE 207 OFFICE 208 MEN 209 WOMEN210 JAN 204A STOR A B C D C.6 C.5 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 PLUMBING PLAN P-2.2 MCGUFF AB/CD LEVEL 2 - PARTITION FLOOR NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1 A B C D C.6 C.5 2 3 4 5 6 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 PLUMBING ROOF PLAN M-3.1 MCGUFF AB/CD PARTITION NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1 A B 2 3 303 MAINTENANCE WALK-IN REFRIGERATOR BY OTHERS EXISTING TRASH ENCLOSURE TO REMAIN FUTURE SECURE AREA 3.9 304C MEN 304D WOMEN 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 RESTROOM PLAN P-4.1 MCGUFF AB/CD PLUMBING ENLARGED NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 P-5.1 MCGUFF AB/CD PLUMBING DETAILS NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 2022 CALIFORNIA PLUMBING CODE - SECTION 906.0 - VENT TEMINATION 906.2 906.1 CLEARANCE - EACH VENT SHALL TERMINATE NOT LESS THAN 10 FEET FROM OR LESS THAN 3 FEET ABOVE, ANY OPENABLE WINDOW, DOOR, OPENING, AIR INTAKE OR VENT SHAFT, OR NOT LESS THAN 3 FEET IN EVERY DIRECTION FROM A LOT LINE, ALLEY AND STREET EXCEPTED. ROOF TERMINATION - EACH VENT PIPE OR STACK SHALL EXTEND THROUGH IT FLASHING AND SHALL TERMINATE VERTICALLY NOT LESS THAN 6 INCHES ABOVE THE ROOF NOR LESS THAN 1 FOOT FROM A VERTICAL SURFACE. 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 P-5.2 MCGUFF AB/CD PLUMBING TITLE 24 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 Keith Matoi 06-11-2025 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 P-6.1 MCGUFF AB/CD WASTE & VENT RISER DIAGRAM NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 P-6.1 MCGUFF AB/CD WASTE & VENT RISER DIAGRAM NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 YES NO INSTRUCTIONS: ORAN GE COUNTY FI RE AUTHORI TY Plan Submittal Criteria COMMERCIAL projects, MULTIFAMILY RESIDENTIAL projects and RESIDENTIAL TRACT developments · Fill in the project/business address and provide a brief description of the scope of work and type of business operation that will take place. · Answer questions 1 through 10, read and initial items 11 and 12, then complete and sign the certification section. · If you answer: - “YES” to any part of questions 1 through 10, submit the type of plan indicated in italics to OCFA. · In some cases, other plan types not indicated herein may also be necessary depending on specific conditions or operations. · Visit www.ocfa.org for submittal information and locations. If you need assistance in filling out this form or have questions regarding requirements for review, please contact OCFA at 714-573-6108 or visit us at 1 Fire Authority Road, Irvine, CA 92602. Address Suite City Project Scope/Business Description 1. Construction of a new building, a new story, or increase the footprint of an existing building? Changes to roadways, curbs, or drive aisles? Addition, relocation, or modification of fire hydrants or fences/gates? Construction within 300 feet of an active or proposed oil well? Fire Master Plan (PR145) 2. Property is adjacent to a wildland area or non-irrigated native vegetation? Fire Master Plan (PR145); a Fuel Modification Plan may also be required. (PR120, PR124) 3. Located in or < 100’ from a Division of Oil, Gas, and Geothermal Resources (DOGGR) field boundary, < 300’ from an oil/gas seep, or < 1000’ from a landfill? Methane Work Plan. (PR170) 4. Installation/modification/repair of underground piping, backflow preventers, or fire department connections serving private fire hydrant/sprinkler/standpipe systems? Underground Plan. (PR470, PR475) 5. Drinking/dining/recreation/meetings/training/religious functions or other gatherings in a room > 750 sq.ft. (> 1,000 sq.ft. for training/adulteducation) or > 49 people? Healthcare/outpatient services for > 5 people who may be unable to immediately evacuate without assistance? Education for children (academic tutoring for ages 5+ is exempt unless classified as an E occupancy by the Building Official)? Adult/child daycare? 24-hour care/supervision? Incarceration or restraint? Hotel/apartment or residential facility with 3+ units and 3+ stories (3-story townhouses/rowhouses where an independent direct exit to grade is provided for dwelling are exempt)? Congregate housing/dormitories with 17+ people? High-rise structure (55+ feet to highest occupied floor level)? Architectural Plan (PR200-PR285) 6. Installation/modification of locks delaying or preventing occupants from leaving a space or requiring use of a card, button, or similar action to open a door in the direction of exit travel? Architectural, Sprinkler, and/or Alarm Plan depending on the occupancy and type of device installed (PR200-PR280, PR420-PR425, PR500-PR520) 7. Installation/modification/use of spray booths; dust collection; dry cleaning; industrial ovens/drying equipment; industrial/commercial refrigeration systems; compressed gasses; tanks for cryogenic or flammable/combustible liquids; vapor recovery; smoke control; battery back-up/charging systems (> 50 gal. electrolyte, > 1,000 lb. lithium ion); welding/brazing/soldering, open flame torches, cutting/grinding; or other similar operations? Special Equipment Plan (PR315, PR340-PR382) 8. Storage/use/research with flammable/combustible liquids or other chemicals? Motor vehicle/aircraft maintenance/repair? Cabinetry/woodworking/finishing facility? Chem Class & floor plan (full architectural plan if H occupancy); Special Equipment Plans may be necessary. (PR315-PR360, PR232-PR240) 9. Storage or merchandizing areas in excess of 500 sq. ft. where items are located higher than 12’ (6’ for high-hazard commodities, plastic, rubber, foam, etc.)? High-piled Storage Plan (PR330) 10. Cooking under a Type I commercial hood; installation or modification of a fire extinguishing system located in a commercial cooking hood? Hood & Duct Extinguishing System, not just the hood mechanical plan. (PR335) Initial each of the following two items indicating that you have read and understand the statement: 11. *Sprinklers/Alarms: Consult Building/Fire Codes and ordinances to determine sprinkler/alarm requirements; if a system is required, plans shall be submitted for OCFA review. Existing buildings undergoing remodel must be evaluated by a licensed Initials contractor to determine if modification is needed; if so, contractor shall submit plans prior to making modifications. 12. Fire Hazard Severity Zone: Consult maps available at building department or on OCFA website to determine if your site is located in a FHSZ. Buildings in a FHSZ may be subject to special construction requirements detailed in CBC Chapter 7A or CRC R327— Initials the building department will determine specific requirements. I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name Signature Phone Number ( ) Date / / Building Department: If you have verified that all of the questions have been answered accurately as “NO”, and the project does not otherwise require OCFA review of sprinkler or alarm plans*, then you may accept this signed form as a written release that OCFA review is not required. Should you still require that the applicant have plans approved by OCFA, please initial here or attach an OCFA referral form and have the applicant submit the form along with the appropriate plans and fees for OCFA review. 10-08-14 EE COM O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Referral Form Required for OCFA to review plans upon the request of the Building Department when the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”. City / County Official Requesting Review: City / County Reference #: Date: __________________________________ City / County: _____________________________________ E-Mail: __________________________________ Contact Name: _____________________________________ Phone #: _________________________________ Title: _____________________________________ ** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. ** Reason(s) for Review: Please describe why OCFA Plan Review is or may be required by the City/County : OCFA COMMENTS:  No further action required on this specific plan type, based on information provided on: ____/______/______.  Project to be taken in for OCFA Review. Other: Name: _________________________________________ Contact #: ______________________________________ Date: _________________________________ OCFA Authorization Updated: 06/02/2020 rs 1/8" = 1'-0" 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 M-5.2 MCGUFF AB/CD TITLE 24 NORTH HHENDY.COM T (949) 851-3080 4770 Campus Dr., Suite 100 Newport Beach, CA 92660 H ndy ISSUES AND REVISIONS JOB NUMBER SCALE PROJECT TEAM All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written consent of H. Hendy Associates. 2023 H.HendyAssociatesc DATE AS NOTED 04463.0000.24 3080 S. HARBOR BLVD. SANTA ANA, CA 92704 MCGUFF - NO.DESCRIPTION DATE ISSUE FOR CITY / BID 02/17/25 Consulting Mechanical Engineers Costa Mesa, CA 92626 714.662.7355 KMA CONSULTING M 023887 JAMES RAE E. 09-30-2025 PLAN CHECK SUBMITTAL 03/17/25 P.C. CORRECTIONS 06/13/25 P.C. CORRECTIONS 07/31/25