GN-1
1GENERAL NOTES & SPECIFICATIONS2ABBREVIATIONS & SYMBOLS
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
GN-2
3
FIRE DEPARTMENT 2
BATTERY NOTES BATTERY SPECIFICATIONS 1
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
T-1
UNDERGROUND
SOUTHERN CALIFORNIA
SERVICE ALERT OF
800-227-2600
SITE INFORMATION
VICINITY MAP LOCAL MAP
LOCATION MAPS
PROJECT TEAM
DRAWING INDEX
DRIVING DIRECTIONS CODE COMPLIANCEDO NOT SCALE DRAWINGS
PROJECT: 5G NR 1SR CBAND
SITE TYPE: ROOFTOP (INDOOR)
SITE ADDRESS: 2333 NORTH BROADWAY
SANTA ANA, CA 92706
FA NUMBER: 10087174
USID NUMBER: 11698
PACE NUMBER: MRLOS080640/MRLOS079296/
MRLOS078913/MRLOS079909
PTN NUMBER: 3551A0YMVL
SITE NUMBER: CLU3236/CLL03236
SITE NAME: SANTA ANA
SI
SI
PROJECT DESCRIPTION
CONSTRUCTION DRAWINGS
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
Bldg #101123288
APPROVALS:
PLNG - C. Santana
BLDG - CSG
PUBLIC WORKS - Y. Soto
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
A-1
1SITE PLAN 15'30'60'1"=30'-0"
SCALE:
SA
N
T
A
A
N
A
F
W
Y
SECTOR 'B'
210°
SECTOR 'C'
320°
SA
N
T
A
A
N
A
F
W
Y
MA
I
N
S
T
N
B
R
O
A
D
W
A
Y
SECTOR 'A'
120°
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
A-2
1ROOF PLAN 3/32"=1'-0"
SCALE:
SECTOR 'B'
210°
SECTOR 'A'
120°
SECTOR 'C'
320°
2(E) EQUIPMENT PLAN 3/8"=1'-0"
SCALE:
3(N) EQUIPMENT PLAN 3/8"=1'-0"
SCALE:
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
A-3
2(E) ANTENNA PLAN 1/4"=1'-0"
SCALE:1(N) ANTENNA PLAN 1/4"=1'-0"
SCALE:
SECTOR 'B'
210°
SECTOR 'A'
120°
SECTOR 'C'
320°
SECTOR 'B'
210°
SECTOR 'A'
120°
SECTOR 'C'
320°
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
A-4
1ANTENNA/RRUS SCHEDULE
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
A-5
1(E) SOUTHEAST ELEVATION 1/8"=1'-0"
SCALE:
2(N) SOUTHEAST ELEVATION 1/8"=1'-0"
SCALE:
VEROS
VEROS
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
A-6
1(E) SOUTHWEST ELEVATION 1/8"=1'-0"
SCALE:
2(N) SOUTHWEST ELEVATION 1/8"=1'-0"
SCALE:
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
A-7
1ANTENNA SPECIFICATIONS
ERICSSON
ERICSSON
4RRUS SPECIFICATIONS
ERICSSON
3RRUS SPECIFICATIONS
7RRUS BACK TO BACK MOUNT
5DIPLEXER SPECIFICATION8PIPE TO PIPE BRACKET 2ANTENNA SPECIFICATIONS
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
MARATHON
M12V185FT
6-48V BATTERY RACK SPECIFICATIONS9RECTIFIER MODULE SPECIFICATIONS
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
S-1
5RACK ANCHORAGE
3RRUS MOUNT
4SECTION
2ANTENNA MOUNT @ SECTOR 'C'
1ANTENNA MOUNT @ SECTORS 'A' & 'B'
·
·
·
6DIPLEXER MOUNT
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
3300 IRVINE AVENUE, SUITE 300
NEWPORT BEACH, CA 92660
TEL: (949) 861-2201
FAX: (949) 468-0931
4430 E. MIRALOMA AVE. SUITE D
ANAHEIM, CALIFORNIA 92807
E-1
5EQUIPMENT ELECTRICAL AND GROUNDING PLAN
6ANTENNA GROUNDING PLAN
3GROUNDING NOTES 1GROUND BAR
2INSTL OF GRND CONDUCTOR4INTERIOR TWO HOLE LUG
3/8"=1'-0"
SCALE:
1/4"=1'-0"
SCALE:
YES NO
INSTRUCTIONS:
ORAN GE COUNTY FI RE AUTHORI TY
Plan Submittal Criteria
COMMERCIAL projects, MULTIFAMILY RESIDENTIAL projects
and RESIDENTIAL TRACT developments
· Fill in the project/business address and provide a brief description of the scope of work and type of business operation that will take place.
· Answer questions 1 through 10, read and initial items 11 and 12, then complete and sign the certification section.
· If you answer: - “YES” to any part of questions 1 through 10, submit the type of plan indicated in italics to OCFA.
· In some cases, other plan types not indicated herein may also be necessary depending on specific conditions or operations.
· Visit www.ocfa.org for submittal information and locations. If you need assistance in filling out this form or have questions regarding
requirements for review, please contact OCFA at 714-573-6108 or visit us at 1 Fire Authority Road, Irvine, CA 92602.
Address Suite City
Project Scope/Business Description
1. Construction of a new building, a new story, or increase the footprint of an existing building? Changes to roadways,
curbs, or drive aisles? Addition, relocation, or modification of fire hydrants or fences/gates? Construction within
300 feet of an active or proposed oil well? Fire Master Plan (PR145)
2. Property is adjacent to a wildland area or non-irrigated native vegetation?
Fire Master Plan (PR145); a Fuel Modification Plan may also be required. (PR120, PR124)
3. Located in or < 100’ from a Division of Oil, Gas, and Geothermal Resources (DOGGR) field boundary, < 300’ from
an oil/gas seep, or < 1000’ from a landfill? Methane Work Plan. (PR170)
4. Installation/modification/repair of underground piping, backflow preventers, or fire department connections serving
private fire hydrant/sprinkler/standpipe systems? Underground Plan. (PR470, PR475)
5. Drinking/dining/recreation/meetings/training/religious functions or other gatherings in a room > 750 sq.ft. (> 1,000
sq.ft. for training/adulteducation) or > 49 people? Healthcare/outpatient services for > 5 people who may be unable
to immediately evacuate without assistance? Education for children (academic tutoring for ages 5+ is exempt unless
classified as an E occupancy by the Building Official)? Adult/child daycare? 24-hour care/supervision? Incarceration
or restraint? Hotel/apartment or residential facility with 3+ units and 3+ stories (3-story townhouses/rowhouses
where an independent direct exit to grade is provided for dwelling are exempt)? Congregate housing/dormitories
with 17+ people? High-rise structure (55+ feet to highest occupied floor level)? Architectural Plan (PR200-PR285)
6. Installation/modification of locks delaying or preventing occupants from leaving a space or requiring use of a card,
button, or similar action to open a door in the direction of exit travel? Architectural, Sprinkler, and/or Alarm Plan
depending on the occupancy and type of device installed (PR200-PR280, PR420-PR425, PR500-PR520)
7. Installation/modification/use of spray booths; dust collection; dry cleaning; industrial ovens/drying equipment;
industrial/commercial refrigeration systems; compressed gasses; tanks for cryogenic or flammable/combustible
liquids; vapor recovery; smoke control; battery back-up/charging systems (> 50 gal. electrolyte, > 1,000 lb. lithium
ion); welding/brazing/soldering, open flame torches, cutting/grinding; or other similar operations?
Special Equipment Plan (PR315, PR340-PR382)
8. Storage/use/research with flammable/combustible liquids or other chemicals? Motor vehicle/aircraft
maintenance/repair? Cabinetry/woodworking/finishing facility? Chem Class & floor plan (full architectural plan if
H occupancy); Special Equipment Plans may be necessary. (PR315-PR360, PR232-PR240)
9. Storage or merchandizing areas in excess of 500 sq. ft. where items are located higher than 12’ (6’ for high-hazard
commodities, plastic, rubber, foam, etc.)? High-piled Storage Plan (PR330)
10. Cooking under a Type I commercial hood; installation or modification of a fire extinguishing system located in a
commercial cooking hood? Hood & Duct Extinguishing System, not just the hood mechanical plan. (PR335)
Initial each of the following two items indicating that you have read and understand the statement:
11. *Sprinklers/Alarms: Consult Building/Fire Codes and ordinances to determine sprinkler/alarm requirements; if a system is
required, plans shall be submitted for OCFA review. Existing buildings undergoing remodel must be evaluated by a licensed
Initials contractor to determine if modification is needed; if so, contractor shall submit plans prior to making modifications.
12. Fire Hazard Severity Zone: Consult maps available at building department or on OCFA website to determine if your site is located
in a FHSZ. Buildings in a FHSZ may be subject to special construction requirements detailed in CBC Chapter 7A or CRC R327—
Initials the building department will determine specific requirements.
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name Signature
Phone Number ( ) Date / /
Building Department: If you have verified that all of the questions have been answered accurately as “NO”, and the project does not otherwise require OCFA
review of sprinkler or alarm plans*, then you may accept this signed form as a written release that OCFA review is not required. Should you still require that the
applicant have plans approved by OCFA, please initial here or attach an OCFA referral form and have the applicant submit the form along with the
appropriate plans and fees for OCFA review. 10-08-14 EE
COM
O R A N G E C O U N T Y F I R E A U T H O R I T Y
Plan Referral Form
Required for OCFA to review plans upon the request of the Building Department when
the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”.
City / County Official Requesting Review:
City / County Reference #: Date: __________________________________
City / County: _____________________________________ E-Mail: __________________________________
Contact Name: _____________________________________ Phone #: _________________________________
Title: _____________________________________
** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. **
Reason(s) for Review:
Please describe why OCFA Plan Review is or may be required by the City/County :
OCFA COMMENTS:
No further action required on this specific plan type, based
on information provided on: ____/______/______.
Project to be taken in for OCFA Review.
Other:
Name: _________________________________________
Contact #: ______________________________________ Date: _________________________________
OCFA Authorization
Updated: 06/02/2020 rs
4430 E. Miraloma Ave. Suite D Anaheim, California 92807
CLU3236/CLL03236
SANTA ANA
5G NR 1SR CBAND
2333 North Broadway
Santa Ana, CA 92706
Prepared for
STRUCTURAL CALCULATIONS
Structural Analysis
By
February 7, 2022
1452 EDINGER AVE.
TUSTIN, CALIFORNIA 92780
George Gomez, P.E.
C VI
C 92845
EORGE GOME
REGISTERED PROFESSIONALENGINEER
STATE OF CAL IFORNIAIL
ZG
Design Criteria
I. Applicable Codes
-California Building Code (CBC)
-ASCE 7-16
-TIA 222-H
-AISC 360-16
-AISC 341-16
-ACI 318-
II. Scope of Work
This project consists of replacing existing antennas with new antennas. All antennas will be mounted
onto existing antenna mounts. A new equipment cabinet will be anchored to an existing slab on
grade in the equipment room.
New Equipment Cabinet:
1. NEQ. 20326 48V BATTERY RACK
New Antenna Equipment:
1. CCI TPA-65R-BU6DA-K
2. ERICSSON AIR6449 N77D
3. KATHREIN 800-10965K
4. QUINTEL QS6658-3E
5. RRUS 4478 B5
6. RRUS 4415 B25
7. RRUS 4426 B66
8. RRUS 4478 B14
9. RRUS 32 B30
10. RRUS E2 B29
11. RRUS 4478 B12A
III. Structural Assessment
New Battery Cabinet Anchorage to slab 97.0% DCR OK
New Antenna Anchorage to Antenna Mount 7.25% DCR OK
IV. Provisions of Analysis & Disclaimer
Our structural calculations are completed assuming all information provided to us is accurate and
applicable to this site. For the purposes of calculations, we assume an overall structure condition of
“like new” and all members, connections, anchors, and surfaces to be free of corrosion and/or
structural defects. The structure owner and/or contractor shall verify the structure’s condition prior
to installation of any proposed equipment. If actual conditions differ from those described in this
report, the Engineer of record should be notified immediately to complete a revised evaluation.
AT&T
CLU3236/CLL03236
Page 1 of 19
ASCE Hazards Report
Address:
No Address at This Location
Standard:ASCE/SEI 7-16 Latitude:33.76826
Risk Category:II Longitude:-117.86878
Soil Class:D - Default (see
Section 11.4.3)
Elevation:147.32063444523126 ft
(NAVD 88)
Wind
Results:
Wind Speed 95 Vmph
10-year MRI 66 Vmph
25-year MRI 72 Vmph
50-year MRI 76 Vmph
100-year MRI 81 Vmph
Data Source: ASCE/SEI 7-16, Fig. 26.5-1B and Figs. CC.2-1–CC.2-4, and Section 26.5.2
Date Accessed: Fri May 23 2025
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear
interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds
correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability =
0.00143, MRI = 700 years).
Site is not in a hurricane-prone region as defined in ASCE/SEI 7-16 Section 26.2.
Page 1 of 3https://ascehazardtool.org/Fri May 23 2025
AT&T
CLU3236/CLL03236
Page 2 of 19
SS : 1.327
S1 : 0.472
F a : 1.2
F v : N/A
SMS : 1.592
SM1 : N/A
SDS : 1.061
SD1 : N/A
T L : 8
PGA : 0.559
PGA M : 0.67
F PGA : 1.2
Ie : 1
C v : 1.365
Seismic
Site Soil Class:
Results:
Data Accessed:
Date Source:
D - Default (see Section 11.4.3)
USGS Seismic Design Maps
Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8.
Fri May 23 2025
Page 2 of 3https://ascehazardtool.org/Fri May 23 2025
AT&T
CLU3236/CLL03236
Page 3 of 19
AT&T
CLU3236/CLL03236
Page 4 of 19
project by CASA
location date 5/23/2025
client job no. 22-115
(Based on USGS and ASCE 7 Standard)Wind - ASCE 7 Sec 29.5.1
Sds=1.061 g Fh = qh*GCr*Af
Sd1=0.576 g kz = 0
V = 95 MPH
Unit Series: qh = 0.00 psf
Unit height=84 inch GCr = 1.9
Unit width=27.5 inch Af = 13.2 sf
Unit length=22.7 inch Fh = 0 lbs
Unit dead load(Wp)=3276 lbs less than Fp*Omega
Unit live load=0 lbs (INDOORS)
SEISMIC - ASCE 7 Sec 13.3.1
( ASCE EQ. 13.3-1)
Rp=2.5 ( ASCE table 13.6-1)
ap=1 ( ASCE table 13.6-1)
Ip=1.0 ( ASCE sec 13.1.3)
Wp= 3276 lbs 1+2(z/h) = 3
Fp= 1668 lbs omega = 2
Fp-max = 1.6*Sds*I*Wp 5561 lbs Fp * omega need not be greater than Fp-max
Fp-omega 3337
Load Combinations LRFD DL LL Eh or W Ev Sds Total Horiz Total Vert
LC1 (eq. 16-1) 1.4 0 0 0 1 0 4586
LC2 (eq. 16-2) 1.2 1.6 0 0 1 0 3931
LC3 (eq. 16-5) 1.2 0.5 1 695 1 3337 4626
LC4 (eq. 16-7) 0.9 0 1 695 1 3337 3644
LC5 (eq. 16-1) 1.4 0 0 0 -1 0 4586
LC6 (eq. 16-2) 1.2 1.6 0 0 -1 0 3931
LC7 (eq. 16-5) 1.2 0.5 1 -695 -1 3337 3236
LC8 (eq. 16-7) 0.9 0 1 -695 -1 3337 2253
note: Ev=0.2*Sds*D
CLU3236/CLL03236
2333 NORTH BROADWAY
SMARTLINK
Mechanical Unit Anchorage
NEQ.20326 48V BATTERY RACK
𝐹𝑝 =.∗ ∗ ∗
/(1+2*z/h)
AT&T
CLU3236/CLL03236
Page 5 of 19
project by CASA
location date 5/23/2025
client job no. 22-115
CLU3236/CLL03236
2333 NORTH BROADWAY
SMARTLINK
Note: For maximum tension load, consider Ev is in the opposite direction of the gravity.
3337 lbs C.G.
2253 lbs
1127 lbs 1127 lbs
5096 lbs 5096 lbs
Mot=total horizontal*unit height/2
Mot=140146 lb.in
T/C= Mot/ unit width
T/C= 5096 lbs
Vertical Reaction= Total Vertical/2
Vertical Reaction= 1127 lbs
Net omega tension = Vertical Reaction-T/C
Net omega tension =-3970 lbs CHECK ANCHORGE FOR PULLOUT
AT&T
CLU3236/CLL03236
Page 6 of 19
project by CASA
location date 5/23/2025
client job no. 22-115
CLU3236/CLL03236
2333 NORTH BROADWAY
SMARTLINK
Note: for maximum compression load, consider Ev is in the same direction of the gravity
3337 lbs
4626 lbs
2313 lbs 2313 lbs
5096 lbs 5096 lbs
Mot=total horizontal*unit height/2
Mot=140146 lbs-in
T/C= Mot/ unit width
T/C=5096 lbs
Vertical Reaction= Total Vertical/2
Vertical Reaction= 2313 lbs
Net Omega Compression = Vertical Reaction+T/C
Net Omega Compression= 7409 lbs (compression)
Compression Force (lb)= 7409
Shear Force (lb)= 3337 < 3000 (V allow)Fails
Tension Force (lb)= 3970 < 1870 (T allow)Fails
t/T + v/V= 3.24 <Fails(4.2.2, ESR 1917)
Use Four (4) 5/8 inch diameter x 3-1/4 inch embedment Hilti Kwik
Bolt TZ2 expansion anchors, (2) each side of unit (minimum), to
attach unit to new pad on grade, per ESR4266. Fill all holes in
support rails with anchors, typical. See following pages for
anchorage calcs.
AT&T
CLU3236/CLL03236
Page 7 of 19
www.hilti.com
Hilti PROFIS Engineering 3.1.14
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Company:
Address:
Phone I Fax:
Design:
Fastening point:
|
CABINET ANCHORAGE
Page:
Specifier:
E-Mail:
Date:
1
5/23/2025
Specifier's comments:
1 Input data
Anchor type and diameter: Kwik Bolt TZ2 - CS 5/8 (3 1/4) hnom2
Item number: 2210271 KB-TZ2 5/8x4 3/4
Specification text: Hilti Æ 5/8 in Kwik Bolt TZ2 - CS with 3.75 in
nominal embedment depth per ICC-ES
ESR-4266 , Hammer drill bit installation per
MPII,
Effective embedment depth: hef,act = 3.250 in., hnom = 3.750 in.
Material: Carbon Steel
Evaluation Service Report: ESR-4266
Issued I Valid: 10/1/2024 | 12/1/2025
Proof: Design Method ACI 318-19 / Mech
Shear edge breakout verification: Row closest to edge (Case 3 only from ACI 318-19 Fig. R.17.7.2.1b)
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.394 in.
Anchor plateR : lx x ly x t = 22.700 in. x 27.500 in. x 0.394 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 2500, fc' = 2,500 psi; h = 6.000 in.
Installation: Hammer drilled hole, Installation condition: Dry
Reinforcement: tension: not present, shear: not present; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) Tension load: yes (17.10.5.3 (d))
Shear load: yes (17.10.6.3 (c))
R - The anchor calculation is based on a rigid anchor plate assumption.
Geometry [in.] & Loading [lb, in.lb]
AT&T
CLU3236/CLL03236
Page 8 of 19
www.hilti.com
Hilti PROFIS Engineering 3.1.14
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Company:
Address:
Phone I Fax:
Design:
Fastening point:
|
CABINET ANCHORAGE
Page:
Specifier:
E-Mail:
Date:
2
5/23/2025
1.1 Design results
Case Description Forces [lb] / Moments [in.lb]Seismic Max. Util. Anchor [%]
1 Combination 1 N = -2,253; Vx = 3,337; Vy = 0;
Mx = 0; My = 140,146; Mz = 0;
yes 97
2 Load case/Resulting anchor forces
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 2,899 834 834 0
2 0 834 834 0
3 2,899 834 834 0
4 0 834 834 0
Max. concrete compressive strain: 0.07 [‰]
Max. concrete compressive stress: 288 [psi]
Resulting tension force in (x/y)=(-9.350/0.000): 5,798 [lb]
Resulting compression force in (x/y)=(10.673/0.000): 8,051 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [lb]Capacity f Nn [lb]Utilization bN = Nua/f Nn Status
Steel Strength*2,899 13,157 23 OK
Pullout Strength*N/A N/A N/A N/A
Concrete Breakout Failure**5,798 5,998 97 OK
* highest loaded anchor **anchor group (anchors in tension)
AT&T
CLU3236/CLL03236
Page 9 of 19
www.hilti.com
Hilti PROFIS Engineering 3.1.14
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Company:
Address:
Phone I Fax:
Design:
Fastening point:
|
CABINET ANCHORAGE
Page:
Specifier:
E-Mail:
Date:
3
5/23/2025
3.1 Steel Strength
Nsa = ESR value refer to ICC-ES ESR-4266
f Nsa ³ Nua ACI 318-19 Table 17.5.2
Variables
Ase,N [in.2]futa [psi]
0.16 106,704
Calculations
Nsa [lb]
17,542
Results
Nsa [lb]f steel f nonductile f Nsa [lb]Nua [lb]
17,542 0.750 1.000 13,157 2,899
3.2 Concrete Breakout Failure
Ncbg = (ANc
ANc0)y ec,N y ed,N y c,N y cp,N Nb ACI 318-19 Eq. (17.6.2.1b)
f Ncbg ³ Nua ACI 318-19 Table 17.5.2
ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
ANc0 = 9 h2
ef ACI 318-19 Eq. (17.6.2.1.4)
y ec,N = (1
1 + 2 e'
N
3 hef
)£ 1.0 ACI 318-19 Eq. (17.6.2.3.1)
y ed,N = 0.7 + 0.3 (ca,min
1.5hef)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b)
y cp,N = MAX(ca,min
cac
, 1.5hef
cac
)£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b)
Nb = kc l a √f'
c h1.5
ef ACI 318-19 Eq. (17.6.2.2.1)
Variables
hef [in.]ec1,N [in.]ec2,N [in.]ca,min [in.]y c,N
3.250 0.000 0.000 ∞1.000
cac [in.]kc l a f'
c [psi]
11.500 21 1.000 2,500
Calculations
ANc [in.2]ANc0 [in.2]y ec1,N y ec2,N y ed,N y cp,N Nb [lb]
190.13 95.06 1.000 1.000 1.000 1.000 6,152
Results
Ncbg [lb]f concrete f seismic f nonductile f Ncbg [lb]Nua [lb]
12,304 0.650 0.750 1.000 5,998 5,798
AT&T
CLU3236/CLL03236
Page 10 of 19
www.hilti.com
Hilti PROFIS Engineering 3.1.14
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Company:
Address:
Phone I Fax:
Design:
Fastening point:
|
CABINET ANCHORAGE
Page:
Specifier:
E-Mail:
Date:
4
5/23/2025
4 Shear load
Load Vua [lb]Capacity f Vn [lb]Utilization bV = Vua/f Vn Status
Steel Strength*834 6,668 13 OK
Steel failure (with lever arm)*N/A N/A N/A N/A
Pryout Strength**3,337 34,451 10 OK
Concrete edge failure in direction **N/A N/A N/A N/A
* highest loaded anchor **anchor group (relevant anchors)
4.1 Steel Strength
Vsa,eq = ESR value refer to ICC-ES ESR-4266
f Vsteel ³ Vua ACI 318-19 Table 17.5.2
Variables
Ase,V [in.2]futa [psi]aV,seis
0.16 106,704 1.000
Calculations
Vsa,eq [lb]
10,259
Results
Vsa,eq [lb]f steel f nonductile f Vsa,eq [lb]Vua [lb]
10,259 0.650 1.000 6,668 834
AT&T
CLU3236/CLL03236
Page 11 of 19
www.hilti.com
Hilti PROFIS Engineering 3.1.14
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Company:
Address:
Phone I Fax:
Design:
Fastening point:
|
CABINET ANCHORAGE
Page:
Specifier:
E-Mail:
Date:
5
5/23/2025
4.2 Pryout Strength
Vcpg = kcp [(ANc
ANc0)y ec,N y ed,N y c,N y cp,N Nb ] ACI 318-19 Eq. (17.7.3.1b)
f Vcpg ³ Vua ACI 318-19 Table 17.5.2
ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
ANc0 = 9 h2
ef ACI 318-19 Eq. (17.6.2.1.4)
y ec,N = (1
1 + 2 e'
N
3 hef
)£ 1.0 ACI 318-19 Eq. (17.6.2.3.1)
y ed,N = 0.7 + 0.3 (ca,min
1.5hef)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b)
y cp,N = MAX(ca,min
cac
, 1.5hef
cac )£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b)
Nb = kc l a √f'
c h1.5
ef ACI 318-19 Eq. (17.6.2.2.1)
Variables
kcp hef [in.]ec1,N [in.]ec2,N [in.]ca,min [in.]
2 3.250 0.000 0.000 ∞
y c,N cac [in.]kc l a f'
c [psi]
1.000 11.500 21 1.000 2,500
Calculations
ANc [in.2]ANc0 [in.2]y ec1,N y ec2,N y ed,N y cp,N Nb [lb]
380.25 95.06 1.000 1.000 1.000 1.000 6,152
Results
Vcpg [lb]f concrete f seismic f nonductile f Vcpg [lb]Vua [lb]
49,216 0.700 1.000 1.000 34,451 3,337
5 Combined tension and shear loads, per ACI 318-19 section 17.8
bN bV z Utilization bN,V [%]Status
0.967 0.125 1.000 91 OK
bNV = (bN + bV) / 1.2 <= 1
AT&T
CLU3236/CLL03236
Page 12 of 19
www.hilti.com
Hilti PROFIS Engineering 3.1.14
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Company:
Address:
Phone I Fax:
Design:
Fastening point:
|
CABINET ANCHORAGE
Page:
Specifier:
E-Mail:
Date:
6
5/23/2025
6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• The equations presented in this report are based on imperial units. When inputs are displayed in metric units, the user should be aware that the
equations remain in their imperial format.
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to
https://viewer.joomag.com/profis-design-guide-us-en-summer-2021/0841849001625154758?short&/
• "An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-19, Chapter 17, Section
17.10.5.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the
case, the connection design (tension) shall satisfy the provisions of Section 17.10.5.3 (b), Section 17.10.5.3 (c), or Section 17.10.5.3 (d). The
connection design (shear) shall satisfy the provisions of Section 17.10.6.3 (a), Section 17.10.6.3 (b), or Section 17.10.6.3 (c)."
• Section 17.10.5.3 (b) / Section 17.10.6.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile
yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.10.5.3 (c) / Section 17.10.6.3
(b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the
anchors by a non-yielding attachment. Section 17.10.5.3 (d) / Section 17.10.6.3 (c) waive the ductility requirements and require the design
strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased
by w0.
• Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI
318-19, Section 26.7.
Fastening meets the design criteria!
AT&T
CLU3236/CLL03236
Page 13 of 19
www.hilti.com
Hilti PROFIS Engineering 3.1.14
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Company:
Address:
Phone I Fax:
Design:
Fastening point:
|
CABINET ANCHORAGE
Page:
Specifier:
E-Mail:
Date:
7
5/23/2025
Coordinates Anchor [in.]
Anchor x y c-x c+x c-y c+y
1 -9.350 -11.750 ----
2 9.350 -11.750 ----
3 -9.350 11.750 ----
4 9.350 11.750 ----
7 Installation data
Anchor type and diameter: Kwik Bolt TZ2 - CS 5/8 (3 1/4)
hnom2
Profile: no profile Item number: 2210271 KB-TZ2 5/8x4 3/4
Hole diameter in the fixture: df = 0.687 in. Maximum installation torque: 481 in.lb
Plate thickness (input): 0.394 in. Hole diameter in the base material: 0.625 in.
Recommended plate thickness: not calculated Hole depth in the base material: 4.250 in.
Drilling method: Hammer drilled Minimum thickness of the base material: 5.500 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.
Hilti Æ 5/8 in Kwik Bolt TZ2 - CS with 3.75 in nominal embedment depth per ICC-ES ESR-4266 , Hammer drill bit installation per MPII
7.1 Recommended accessories
Drilling Cleaning Setting
• Suitable Rotary Hammer
• Properly sized drill bit
• Manual blow-out pump • Torque controlled cordless impact tool
• Torque wrench
• Hammer
AT&T
CLU3236/CLL03236
Page 14 of 19
www.hilti.com
Hilti PROFIS Engineering 3.1.14
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Company:
Address:
Phone I Fax:
Design:
Fastening point:
|
CABINET ANCHORAGE
Page:
Specifier:
E-Mail:
Date:
8
5/23/2025
8 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.
AT&T
CLU3236/CLL03236
Page 15 of 19
AT&T
CLU3236/CLL03236
Page 16 of 19
project by CASA
location date 5/23/2025
client job no. 22-115
Seismic Ground Motion Values
SDS =1.061 II Table 1.5-1
SD1 =0.576 D § 11.4.3
D Table 11.6-1
Seismic Design Force
Wpequip.(lb)Wpmounts(lb)ap Rp Ip 1+2(z/h)Ω
69.0 50 1.0 2.5 1.0 3.0 1.0
83.6 50 1.0 2.5 1.0 3.0 1.0
108.6 50 1.0 2.5 1.0 3.0 1.0
78.0 50 1.0 2.5 1.0 3.0 1.0
53.0 20 1.0 2.5 1.0 3.0 1.0
46.0 20 1.0 2.5 1.0 3.0 1.0
48.4 20 1.0 2.5 1.0 3.0 1.0
53.0 20 1.0 2.5 1.0 3.0 1.0
53.0 20 1.0 2.5 1.0 3.0 1.0
53.0 20 1.0 2.5 1.0 3.0 1.0
59.4 20 1.0 2.5 1.0 3.0 1.0
1.0 2.5 1.0 3.0 1.0
1.0 2.5 1.0 3.0 1.0
Fp min (lb)Fp (lb)Fp max (lb)ΩFp ELat (lb)+/- EVert (lb)
37.9 60.6 202.0 60.6 60.6 25.3
42.5 68.0 226.8 68.0 68.0 28.3
50.5 80.8 269.2 80.8 80.8 33.7
40.7 65.2 217.3 65.2 65.2 27.2
23.2 37.2 123.9 37.2 37.2 15.5
21.0 33.6 112.0 33.6 33.6 14.0
21.8 34.8 116.1 34.8 34.8 14.5
23.2 37.2 123.9 37.2 37.2 15.5
23.2 37.2 123.9 37.2 37.2 15.5
23.2 37.2 123.9 37.2 37.2 15.5
25.3 40.4 134.8 40.4 40.4 16.8
0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0
Item
CCI TPA-65R-BU6DA-K
ERICSSON AIR6449 N77D
KATHREIN 800-10965K
Item
CCI TPA-65R-BU6DA-K
ERICSSON AIR6449 N77D
RRUS 4478 B12A
QUINTEL QS6658-3E
RRUS-4478 B5
RRUS 4415 B25
RRUS 4426 B66
RRUS-4478 B14
RRUS-32 B30
Seismic Coefficients from Table 13.6-1
KATHREIN 800-10965K
QUINTEL QS6658-3E
Seismic Loads Table
RRUS-4478 B5
CLU3236/CLL03236
2333 NORTH BROADWAY
SMARTLINK
Risk Category
Site Class
SDC
Seismic Demands on Nonstructural Components ASCE 7-16
Wind and Seismic Analysis for Appurtenances per ASCE 7-16 & TIA 222-H
RRUS 4426 B66
RRUS-4478 B14
RRUS-32 B30
RRUS 4478 B12A
0
0
RRUS-E2 B29
RRUS-E2 B29
RRUS 4415 B25
AT&T
CLU3236/CLL03236
Page 17 of 19
project by CASA
location date 5/23/2025
client job no. 22-115
CLU3236/CLL03236
2333 NORTH BROADWAY
SMARTLINK
FA =q z*G h*(EPA)A Wind Force (§2.6.11.2)qz*Gh*Ka*Ca =41.6 lb
Gh Gust effect factor from §2.6.9 Gh =1
(EPA)A =K a*C a*A p
Ka Effective projected area coefficient from §2.6.11.2 Ka =1.0
Ap Effective projected area
qh, qz =0.00256 *K z*K zt*K s*K d*K e*V 2 qz =29.7 psf
Kz Velocity pressure exposure coeff. Defined in §2.6.5.2 Kz =1.17
Kzt Topographic factor defined in §2.6.6.2 Kzt =1.0
Ks Rooftop wind speed-up factor from §2.6.7 Ks =1.1
Kd Wind directionality factor from Table 2-2 Kd =1
Ke Ground elevation factor defined in §2.6.8 Ke =1.0
V Basic wind speed V =95 mph
Ca Net force coeff. From Table 2-9 Ca =1.4 0.017453293
h (in) w (in) t (in)Ap (ft2) @ 0o Ap (ft2) @ 30o Ap (ft2) @ 60o Ap (ft2) @ 90o
71.2 20.7 7.7 10.24 10.77 8.41 3.81
31.0 15.9 8.7 3.42 3.90 3.33 1.87
78.7 20.0 6.9 10.93 11.35 8.73 3.77
72.0 12.0 9.6 6.00 7.60 7.16 4.80
23.0 13.0 6.6 2.08 2.33 1.95 1.05
16.5 13.4 5.9 1.54 1.67 1.35 0.68
15.0 13.2 5.8 1.37 1.49 1.21 0.60
23.0 13.0 6.6 2.08 2.33 1.95 1.05
27.2 12.1 7.0 2.29 2.64 2.29 1.32
20.4 18.5 7.5 2.62 2.80 2.23 1.06
15.0 13.2 7.3 1.38 1.57 1.35 0.76
0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00
FA (lb) @ 60o FA (lb) @ 90o FA Max (lb)
350.3 158.5 448.2
138.8 78.0 162.4
363.5 157.0 472.6
297.9 199.8 316.2
81.2 43.9 96.8
56.3 28.1 69.4
50.2 25.1 61.9
81.2 43.9 96.8
95.2 55.0 109.9
92.8 44.1 116.5
56.0 31.7 65.4
0.0 0.0 0.0
0.0 0.0 0.0
FA (lb) @ 30o
448.2
162.4
472.6
FA (lb) @ 0o
426.1
142.5
57.2
0.0
65.4
0.0
455.0
249.8
Wind Effective Projected Areas
Wind Loads Table
0
RRUS 4426 B66
RRUS-4478 B14
RRUS-E2 B29
RRUS 4478 B12A
96.8
QUINTEL QS6658-3E
Item
Wind and Seismic Analysis for Appurtenances per ASCE 7-16 & TIA 222-H
Design Wind Loads TIA-222-H
*Per §16.6 Wind shall be considered to occur from directions in 30 degree maximum
increments around a mounting system and shall include directions normal and parallel to
the face of mount.
RRUS-4478 B5
61.9
RRUS-32 B30
96.8
316.2
63.9
86.4
ERICSSON AIR6449 N77D
KATHREIN 800-10965K
Item
CCI TPA-65R-BU6DA-K
RRUS-4478 B5
QUINTEL QS6658-3E
69.4
109.1
95.1
86.4
57.0
RRUS 4415 B25
0
CCI TPA-65R-BU6DA-K
ERICSSON AIR6449 N77D
KATHREIN 800-10965K
RRUS 4478 B12A
0
0
116.5
109.9
RRUS 4415 B25
RRUS-4478 B14
RRUS-E2 B29
RRUS-32 B30
RRUS 4426 B66
0.0 0.0
AT&T
CLU3236/CLL03236
Page 18 of 19
project by CASA
location date 5/23/2025
client job no. 22-115
CLU3236/CLL03236
2333 NORTH BROADWAY
SMARTLINK
Wp (lb)
119.0
133.6
158.6
128.0
73.0
66.0
68.4
73.0
73.0
73.0
79.4
0.0
0.0
DL ELat EVert W L
LC1 1.4 0 0 0 0
LC2 1.2 0 0 1 0
LC3 1.2 1 1 0 0
Total Vert Total Horiz Total Vert Total Horiz Total Vert(+Ev)Total Horiz Vertical Horizontal
166.6 0.0 142.8 448.2 168.1 60.6 168.1 448.2
187.0 0.0 160.3 162.4 188.7 68.0 188.7 162.4
222.0 0.0 190.3 472.6 224.0 80.8 224.0 472.6
179.2 0.0 153.6 316.2 180.8 65.2 180.8 316.2
102.2 0.0 87.6 96.8 103.1 37.2 103.1 96.8
92.4 0.0 79.2 69.4 93.2 33.6 93.2 69.4
95.8 0.0 82.1 61.9 96.6 34.8 96.6 61.9
102.2 0.0 87.6 96.8 103.1 37.2 103.1 96.8
102.2 0.0 87.6 109.9 103.1 37.2 103.1 109.9
102.2 0.0 87.6 116.5 103.1 37.2 103.1 116.5
111.2 0.0 95.3 65.4 112.1 40.4 112.1 65.4
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00
0
0
40.4
0.0
0.0
16.8
0.0
0.0
RRUS-4478 B5
0.0
RRUS 4478 B12A
RRUS 4478 B12A
0
ELat (lb)
60.6
80.8
65.2
96.8
LRFD Load Combinations
69.4
KATHREIN 800-10965K
Load Case 1 Load Case 2 Load Case 3 Factored Design Forces (lb)
CCI TPA-65R-BU6DA-K
ERICSSON AIR6449 N77D
QUINTEL QS6658-3E
RRUS 4415 B25
RRUS 4426 B66
RRUS-4478 B14
RRUS-32 B30
RRUS-E2 B29
Factored Loads
RRUS-32 B30 37.2 15.5 109.9
CCI TPA-65R-BU6DA-K
KATHREIN 800-10965K
RRUS 4415 B25
Wind and Seismic Analysis for Appurtenances per ASCE 7-16 & TIA 222-H
Design Loads Summary
65.4
0.0
316.2
162.4
61.9
96.8
Seismic Forces Wind Forces
33.6
RRUS 4426 B66
RRUS-4478 B14
Item FA Max. (lb)
448.2
34.8
37.2
+/- Evert (lb)
25.3
33.7
27.2
15.5
14.0
14.5
15.5
472.6
*Max Wind and Seismic forces will be analyzed in each orthogonal
direction for each component. The worst case appurtenance
loading will be used for the (E) mount structure.
RRUS-E2 B29 37.2 15.5 116.5
37.2
QUINTEL QS6658-3E
RRUS-4478 B5
ERICSSON AIR6449 N77D 68.0 28.3
AT&T
CLU3236/CLL03236
Page 19 of 19
project by CASA
location date 5/23/2025
client job no. 22-115
CLU3236/CLL03236
2333 NORTH BROADWAY
SMARTLINK
Ecc
T1
Fh d
V
Fv T2
Fh (lb) Fv (lb)Ecc (in) d (in)T1 (lb) gov.V (lb) DCR %
448.2 168.1 12 71.2 252.4 84.0 6.19%OK
162.4 188.7 12 31.0 154.2 94.3 5.00%OK
472.6 224.0 12 78.7 270.4 112.0 7.25%OK
316.2 180.8 12 72.0 188.2 90.4 5.40%OK
96.8 103.1 12 23.0 102.2 51.5 3.00%OK
69.4 93.2 12 16.5 102.5 46.6 2.87%OK
61.9 96.6 12 15.0 108.5 48.3 3.00%OK
96.8 103.1 12 23.0 102.2 51.5 3.00%OK
109.9 103.1 12 27.2 100.4 51.5 2.97%OK
116.5 103.1 12 20.4 118.9 51.5 3.25%OK
65.4 112.1 12 15.0 122.4 56.1 3.43%OK
0.0 0.0 12 0.0 #DIV/0!0.0 #DIV/0!#DIV/0!
0.0 0.0 12 0.0 #DIV/0!0.0 #DIV/0!#DIV/0!
FU=60.0 ksi
Bolt Diameter=0.5 in
Max V=0.112 kip
Max T=0.270 kip
Φ (Resistance Factor) =0.75
Ab =0.196 in^2
Fnv =24 ksi (A307)
Fnt =45 ksi (A307)
fv = Vu bolt / Ab =0.6 ksi
Vallow = Φ Fnv Ab =3.5 kip >0.112 kip OK
Tallow = Φ Fnt Ab =6.6 kip >0.270 kip OK
Combined Shear and Tension:
F'nt = 1.3F'nt -(Fnt x fv)/ΦFnv < Fnt =57.7 kip <45 kip =45 kip
Rn = F'nt x Ab =8.836 kip
ΦRn = F'nt x Ab =6.627 kip >0.270 kip OK
QUINTEL QS6658-3E
RRUS-4478 B5
RRUS 4415 B25
RRUS 4426 B66
RRUS-4478 B14
RRUS-32 B30
1/2" ø A-307 U-Bolt @ Top & Bottom
Appurtenance Anchorage
RRUS 4478 B12A
0
0
Wind and Seismic Analysis for Appurtenances per ASCE 7-16 & TIA 222-H
CCI TPA-65R-BU6DA-K
KATHREIN 800-10965K
ERICSSON AIR6449 N77D
RRUS-E2 B29
AT&T
CLU3236/CLL03236
Page 20 of 20