HomeMy WebLinkAbout1621 S Diamond St Unit #2 - Plan (2)4'
17
'
11'
3'57'
12
0
'
12
0
'
57'
16'
DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
PV-1
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971 1/16" = 1'-0"
COVER
SHEET
SITE PLAN
·(08) LONGI LR5-54HPB-400M MODULES
·(08) TIGO TS4-A-F RAPID SHUTDOWN
·(01) GROWATT MIN 6000TL-XH-US (240V) INVERTER
·(01) NON-FUSED AC DISCONNECT
ALL WORK TO COMPLY WITH:
·2022 CALIFORNIA ELECTRICAL CODE
·2022 CALIFORNIA RESIDENTIAL CODE
·2022 CALIFORNIA FIRE CODE
·2022 CALIFORNIA BUILDING CODE
TABLE OF CONTENTS
PV-1 COVER SHEET
PV-2 ROOF PLAN & MODULES
PV-2A STRINGING PAGE
PV-3+ ATTACHMENT DETAILS
PV-4 SINGLE-LINE DIAGRAM
PV-4A ELECTRICAL CALCULATIONS
PV-5 LABELS & PLACARD
PV-6+ EQUIPMENT DATASHEETS
SITE DETAILS
ASHRAE MIN TEMP
ASHRAE 2% HIGH TEMP
BUILDING OCCUPANCY
TYPE OF CONSTRUCTION
SPRINKLERS SYSTEM PER NFPA 13D
# OF STORIES
WIND SPEED (ASCE 7-16)
WIND EXPOSURE
RISK CATEGORY
GROUND SNOW LOAD
SQUARE FOOTAGE
UTILITY
2°C
31°C
R-3
V-B
NO
1
95 MPH
B
II
0 PSF
1500 SQ FT
SCE
VICINITY MAP
GOVERNING CODES
TOTAL PV SIZE: 3.200 KW DC, 2.902 KW CEC AC
SCOPE OF WORK
INSTALL A ROOF-MOUNTED PV SYSTEM:
GENERAL NOTES
·ALL WORK SHALL CONFORM TO APPLICABLE BUILDING,
ELECTRICAL CODE AND ANY LOCALLY ADOPTED ORDINANCES.
·DRAWINGS ARE DIAGRAMMATIC, SITE CONDITIONS SHALL
PREVAIL. IF NO SCALE IS GIVEN, DRAWINGS ARE NOT TO
SCALE. ALL DIMENSIONS SHALL BE VERIFIED BY THE
CONTRACTOR IN THE FIELD UPON COMMENCEMENT OF
CONSTRUCTION.
·ALL CONDUIT AND WIRE RUNS ARE DIAGRAMMATIC, SUBJECT
TO FIELD CONDITIONS ROUTING OF RACEWAYS SHALL BE
FINALIZED BY THE CONTRACTOR. IF THE DISTANCES FOR WIRE
RUNS ARE DIFFERENT THAN AS SHOWN, THE CONTRACTOR
SHALL NOTIFY THE DESIGN TEAM TO VALIDATE THE WIRE SIZE.
·ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A
RECOGNIZED TESTING LABORATORY AND INSTALLED PER THE
LISTING AND MANUFACTURER'S REQUIREMENTS.
·ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE
WITH REQUIRED ACCESS AND WORKING CLEARANCES
PER CEC ARTICLE 110.
·ALL NEW MAIN SERVICE PANELS AND SUBPANELS WILL HAVE
APPROPRIATE FIELD IDENTIFICATION PER CEC 408.4.
·ALL EQUIPMENT WILL BE INSTALLED WHERE IT IS NOT EXPOSED
TO PHYSICAL DAMAGE PER CEC 110.27(B)
PR
O
P
E
R
T
Y
L
I
N
E
S DIAMOND ST
FRONT OF HOUSE
W
P
O
M
O
N
A
S
T
10"5'-7"
18
"
F
I
R
E
S
E
T
B
A
C
K
18
"
F
I
R
E
S
E
T
B
A
C
K
8'
-
5
"
18
'
-
8
"
8'
-
5
"
9'-0"11'-2"9'-8"
1'
-
6
"
5"
JB
PV-2
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971 1/14" = 1'-0"
ROOF PLAN
& MODULES
PV ROOF COVERAGE
(E) PV
AREA
[SQ FT]
(N) PV
AREA
[SQ FT]
TOTAL PV
AREA [SQ FT]
TOTAL
ROOF AREA
[SQ FT]
PERCENTAGE
COVERED BY
PV
0 160.26 160.26 937.17 17%
ROOF DESCRIPTION
ROOF ROOF
TILT AZIMUTH ROOF MATERIAL RAFTER
SIZE
RAFTER
SPACING
MAX
RAFTER
SPAN
#1 18° 180°COMP SHINGLE 2" X 6"16" O.C. 7'-0"
#2 18° 270°COMP SHINGLE 2" X 6"16" O.C. 7'-0"
LEGEND
JB - JUNCTION BOX
- RAFTER OR TRUSS
- ROOF OBSTRUCTION
- ROOF ATTACHMENT
- 36" FIRE SETBACKS /
PATHWAYS
- ACCESS POINTX
S DIAMOND ST
(08) LONGI LR5-54HPB-400M MODULES WITH
(08)TIGO TS4-A-F RAPID SHUTDOWN
(N) IRONRIDGE XR10 RAIL
(16) IRONRIDGE FLASHFOOT 2 ATTACHMENTS
WITH MAX 64" O.C. SPAN
(N) EMT CONDUIT
ROOF #1
(E) MAIN SERVICE PANEL
(RAPID SHUTDOWN INITIATION DEVICE)
(E) UTILITY METER
(N) GROWATT MIN 6000TL-XH-US INVERTER
(INTEGRATED DC DISCONNECT)
X
W
P
O
M
O
N
A
S
T
X
(N) NON-FUSED AC DISCONNECT
X
ROOF #2
(E) ADU SUBPANEL (E) MAIN HOUSE SUBPANEL
1. PRIOR TO COMMENCEMENT OF WORK, THE CONTRACTOR SHALL VERIFY THE FRAMI
SIZES, SPACINGS, AND SPANS NOTED IN THE STAMPED PLANS AND ACCOMPANYING
CALCULATIONS AND NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPANCIES PRIOR
TO STARTING CONSTRUCTION.
2. THESE PLANS ARE STAMPED FOR STRUCTURAL CODE COMPLIANCE OF THE RO
FRAMING SUPPORTING THE PROPOSED PV INSTALLATION REFERENCED ONLY. THESE
PLANS ARE NOT STAMPED FOR WATER LEAKAGE. PV MODULES, RACKING, AND
ATTACHMENT COMPONENTS MUST FOLLOW MANUFACTURER GUIDELINES AND
REQUIREMENTS.
3. PLEASE SEE THE ACCOMPANYING STRUCTURAL CALCULATIONS REPORT FOR DETAI
REGARDING CALCULATIONS AS WELL AS LIMITS OF SCOPE OF WORK AND LIABILITY.
DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
JB
PV-2A
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971 1/4" = 1'-0"
STRINGING
PAGE
S DIAMOND ST
W
P
O
M
O
N
A
S
T
A A
B
B
DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
PV MODULE
(E) COMP SHINGLE
IRONRIDGE FLASHFOOT 2 IRONRIDGE XR 10 RAIL
(E) COMP SHINGLE
IRONRIDGE XR 10 RAIL
PV MODULE
5/16"X3"
304 STAINLESS STEEL
COMPRESSION WASHER BLACK 4 3/4" X 5/16" WITH 2.5" MIN LAG
SCREW EMBEDMENT
SEE BELOW FOR ENLARGED VIEW
IRONRIDGE FLASHFOOT 2
MID/END CLAMP
6" MAX
PV-3
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971
ATTACHMENT
DETAILS
NTS DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
(N) GROWATT MIN 6000TL-XH-US
INVERTER, WITH INTEGRATED
LOCKABLE DISCONNET,
(240V) [SI1-SB]
42(N) NON-FUSED AC
DISCONNECT,
SQUARE D DU222RB
60A, 240V, NEMA 3R
3
(N) 08 - LONGI LR5-54HPB-400M MODULES
STRING 1: 03 MODULES
STRING 2: 05 MODULES
03
05
1
(N) JBOX,
NEMA 3R
(N) 08 - TIGO TS4-A-F RAPID SHUTDOWN
(E) ADU SUBPANEL,
125A, 240V, NEMA 3R
705.12(B)(3)(2)
40A/2P
E
(E) MAIN SERVICE PANEL,
200A, 240V, NEMA 3R
705.12(B)(3)(2)
(E) GROUNDING
ELECTRODE
100A/2P
M
100A/2P
M
UTILITY
(E) MAIN BREAKER 100A
(RAPID SHUTDOWN INITIATION DEVICE)
(E) HOUSE SUBPANEL,
125A, 240V, NEMA 3R
705.12(B)(3)(3)
E
UTILITY METER
#----
1Ø, 3W, 240V
PV-4
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971
SINGLE-LINE
DIAGRAM
NTS
THE MAIN BREAKER IN THE MAIN SERVICE PANEL WILL
INITIATE RAPID SHUTDOWN AND MEET THE
REQUIREMENTS OUTLINED IN CEC 690.12.
THE PV BREAKER(S) LAND IN A PANEL THAT MEETS THE PV
DISCONNECT REQUIREMENTS OUTLINED IN CEC 690.13.
THIS PANEL IS READILY ACCESSIBLE, AND THE PANEL
ENCLOSURE IS LOCKABLE.
THE SOLAR MODULE CONNECTORS MEET THE ISOLATING
DEVICE REQUIREMENTS OUTLINED IN CEC 690.15 AND
690.33.
*CODE COMPLIANT WIRE/CONDUIT SUBSITUTIONS MAY BE MADE TO THE ABOVE TABLE.
*SEE THE NEXT PAGE FOR ELECTRICAL CALCULATIONS AND ADDITIONAL ELECTRICAL NOTES.
ID UNGROUNDED
CONDUCTORS NEUTRAL CONDUCTOR EQUIPMENT
GND CONDUCTOR CONDUIT
1 (2) 10 AWG, PV WIRE, CU N/A (1) 6 AWG, SOLID BARE, CU FREE AIR
2 (4) 10 AWG, THWN-2, CU N/A (1) 10 AWG, THWN-2, CU 0.75" EMT
3 (2) 8 AWG, THWN-2, CU (1) 8 AWG, THWN-2, CU (1) 10 AWG, THWN-2, CU 0.75" EMT
4 (2) 8 AWG, THWN-2, CU (1) 8 AWG, THWN-2, CU (1) 10 AWG, THWN-2, CU 0.75" EMT
DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
PV-4A
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971
ELECTRICAL
CALCULATIONS
NTS
INVERTER OUTPUT CALCULATIONS & 705.12 COMPLIANCE
ELECTRICAL NOTES (APPLICABILITY BASED ON SCOPE OF WORK)
ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH NEC ARTICLE 250. A SUPPLEMENTAL
GROUND ROD WILL BE DRIVEN IN ACCORDANCE WITH CEC 250.53(A)(3) IF THE EXISTING GROUND ROD HAS A RESISTANCE TO
EARTH THAT IS GREATER THAN 25 OHMS.
IF ANY EXISTING LOAD CONDUCTORS ARE EXTENDED BY MORE THAN 6', AFCI PROTECTION WILL BE PROVIDED PER CEC
210.12(D).
PER CEC 690.47(A) PV SYSTEMS THAT ARE NOT SOLIDLY GROUNDED, THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
OUTPUT OF THE PV SYSTEMS SHALL BE PERMITTED TO BE THE CONNECTION TO GROUND FOR GROUND-FAULT PROTECTION
AND EQUIPMENT GROUNDING OF THE PV ARRAY.
THE ESS CIRCUIT BREAKER SHALL BE SECURED IN PLACE BY AN ADDITIONAL FASTENER PER CEC 408.36(D).
NO SINGLE BACK-UP LOAD WILL BE LARGER THAN THE MAXIMUM CONTINUOUS OUTPUT OF THE ESS PER CEC 710.15(A).
AS-BUILT CHANGES TO THE ABOVE WIRING ARE PERMISSIBLE AS LONG AS SUBSITUTIONS ARE CODE COMPLIANT. FOR EXAMPLE,
APPROPRIATELY SIZED NM-B MAY BE USED FOR MICROINVERTER OUTPUT CIRCUITS IF INSTALLED IN ACCORDANCE WITH CEC
ARTICLE 334, OR MC CABLE MAY BE USED FOR DC SOLAR STRINGS IF INSTALLED IN ACCORDANCE WITH CEC ARTICLE 330.
ALL OUTDOOR EQUIPMENT SHALL BE RAINTIGHT & HOLD A MINIMUM NEMA 3R RATING, INCLUDING ALL ROOF MOUNTED
TRANSITION BOXES AND SWITCHES. CONDUCTORS EXPOSED TO WET CONDITIONS SHALL BE SUITABLE FOR USE IN WET
CONDITIONS PER CEC 310.10(C).
ALL TERMINAL TEMPERATURES OF EQUIPMENT WILL BE VERIFIED TO BE RATED FOR 75°C, OR THE WIRE WILL NEED TO BE
RESIZED USING THE 60°C TERMINAL TEMPERATURE RATINGS FOR 100A OR LESS.
ALL NM-B SHALL BE INSTALLED AND PROTECTED PER CEC 334, AND ALL SER CABLE SHALL BE INSTALLED AND PROTECTED PER
CEC 338.
ALL ROOFTOP RACEWAYS AND CABLES EXPOSED TO DIRECT SUNLIGHT WILL BE INSTALLED >7/8" ABOVE THE ROOF.
x
ID STARTING
LOCATION FINAL LOCATION UNGROUNDED
CONDUCTORS
NEUTRAL
CONDUCTOR
EQUIPMENT
GND CONDUCTOR
CONTROL
WIRE
TERM.
TEMP.
# OF
CCC ASHARE 2% HIGH TEMP.CCC
ADJUSTMENT
AMBIENT TEMP
CORR.90°C RATING DERATED AMP.
TERM.
TEMP.
RATING
OCPD CONDUIT CONDUIT
FILL LENGTH LOAD VOLTAGE VOLTAGE
DROP
1 STRING JUNCTION BOX (2) 10 AWG, PV WIRE,
CU N/A (1) 6 AWG, SOLID
BARE, CU -- 75°C 2 31°C 20.0A N/A FREE AIR N/A 8FT 10.4A 86.22V 0.25%
2 JUNCTION BOX INVERTER (4) 10 AWG, THWN-2,
CU N/A (1) 10 AWG, THWN-2,
CU -- 75°C 4 31°C 35.0A N/A 0.75" EMT 19.09% 18FT 10.4A 86.22V 0.56%
3 INVERTER NON-FUSED AC
DISCONNECT
(2) 8 AWG, THWN-2,
CU
(1) 8 AWG, THWN-2,
CU
(1) 10 AWG, THWN-2,
CU -- 75°C 2 31°C 50.0A 40A 0.75" EMT 23.86% 25FT 25.0A 240V 0.41%
4 NON-FUSED AC
DISCONNECT ADU SUBPANEL (2) 8 AWG, THWN-2,
CU
(1) 8 AWG, THWN-2,
CU
(1) 10 AWG, THWN-2,
CU -- 75°C 2 31°C 50.0A 40A 0.75" EMT 23.86% 5FT 25.0A 240V 0.08%
x =
x x =
x 0.96 40.0Ax =1
N/AN/A N/A N/A
1 55.0A
INVERTER
OUTPUT CIRCUIT INVERTER OR ESS
# OF
INVERTERS /
ESS
CONTINUOUS
OUTPUT
125% SAFETY
FACTOR
TOTAL
BACKFEED
MINIMUM
BREAKER
SIZE
#1 GROWATT 6KW 1 25.00A 125% 31.25A 40A
PANEL 705.12 COMPLIANCE BUSBAR
OCPD
PROTECTING
PANEL
BUSBAR X
120%
MAX
GENERATION
BACKFEED
MSP 705.12(B)(3)(2)200A 200A 240A 40A
ADU SUBPANEL 705.12(B)(3)(2)125A N/A N/A N/A
HOUSE SUBPANEL 705.12(B)(3)(3)125A N/A N/A N/A
38.4A
52.8A
x x =1 55.0A
0.96
0.96 52.8A
DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
PV-5
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971
LABELS &
PLACARDS
NTS
-THE LABELS/PLACARD SHALL BE PERMANENTLY AFFIXED TO THE
EQUIPMENT OR WIRING METHOD.
-ALL WARNING & HAZARD LABELS SHALL BE INSTALLED PER CEC
110.21(B).
-IF THERE IS EXISTING PV OR ESS, LABELS FOR EXISTING PV SYSTEMS
WILL BE TRANSFERRED OR REPLACED ON NEW EQUIPMENT.
WARNING
THIS EQUIPMENT FED BY MULTIPLE SOURCES.
TOTAL RATING OF ALL OVERCURRENT DEVICES,
EXCLUDING MAIN SUPPLY OVERCURRENT DEVICES
SHALL NOT EXCEED AMPACITY OF BUSBAR.
LOCATED AT ANY PANEL THAT MEETS CEC 705.12(B)(3)(3)
9
WARNING
INVERTER OUTPUT CONNECTION DO NOT
RELOCATE THIS OVERCURRENT DEVICE
LOCATED AT POINT OF INTERCONNECTION.
CEC 705.12(B)(3)(2)
1
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
LOCATED AT PV DISCONNECT
CEC 690.13(B)
!3
5
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
LOCATED AT MAIN SERVICE DISCONNECT.
CEC 690.56(C)(2)
4 RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
LOCATED AT MAIN SERVICE PANEL.
CEC 690.56(C)
2 PHOTOVOLTAIC AC DISCONNECT
MAXIMUM AC OPERATING CURRENT:
LOCATED AT PV DISCONNECT.
CEC 690.56(B), 609.54, 705.20
240V
25.0A
NOMINAL OPERATING AC VOLTAGE:
INSTALLED PER CEC 705.10
6
TWO POWER SOURCES
SOURCES: UTILITY GRID & SOLAR
WARNING!!
8 WARNING: PHOTOVOLTAIC
POWER SOURCE
LOCATED AT DC SOLAR CIRCUIT; CEC 690.31(D)(2)
7 PHOTOVOLTAIC SYSTEM DC DISCONNECT
OPERATING VOLTAGE
LOCATED AT PV DISCONNECT.
CEC 690.56(B), 609.54, 705.20
OPERATING CURRENT
MAX SYSTEM VOLTAGE
SHORT CIRCUIT CURRENT 13.7A
143.7V
10.4A
184.5V
CAUTION
MULTIPLE SOURCES OF POWER WITH
DISCONNECTS LOCATED AS SHOWN:
LOCATED AT MAIN SERVICE PANEL. CEC 690.56(B), 690.4(D), 705.10
1621 S DIAMOND ST
PV MODULES
MAIN SERVICE DISCONNECT
(RAPID SHUTDOWN
INITIATION DEVICE)
INVERTER
FR
O
N
T
O
F
H
O
U
S
E
PV DISCONNECT
DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
PV-6
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971
EQUIPMENT
DATASHEET
NTS DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
PV-7
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971
EQUIPMENT
DATASHEET
NTS DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
PV-8
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971
EQUIPMENT
DATASHEET
NTS DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
1621 S DIAMOND ST
UNIT 2 SANTA ANA, CA 92704
DIAMOND ADU PV-9
DATE: 11/10/2025 REV B
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
HUY THIEU NGUYEN
C10 #833971
EQUIPMENT
DATASHEET
NTSSTARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
1621 S DIAMOND ST
UNIT 2 SANTA ANA, CA 92704
DIAMOND ADU PV-10
DATE: 11/10/2025 REV B
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
HUY THIEU NGUYEN
C10 #833971
EQUIPMENT
DATASHEET
NTSSTARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
PV-11
DATE: 01/13/2026 REV E
AHJ:
APN: 40824215
SANTA ANA CITYSCALE:
SHEET SIZE: 11" x 17"
TEMPLATE V2.0
PREPARED BY:
HIGH LINE DESIGNS
SCOTT TOYAMA
STARS CONSTRUCTION SERVICES INC
6022 WESTERN AVE
BUENA PARK, CA 90621
714.262.3929
HUY THIEU NGUYEN
C10 #833971
EQUIPMENT
DATASHEET
NTS DIAMOND ADU
1621 S DIAMOND ST, UNIT 2
SANTA ANA, CA 92704
Exp.03/31/2026
For Structural Only