HomeMy WebLinkAbout6 E Hutton Center Dr #A-REV 1 - PlanCONTRACTOR
SHEET DESCRIPTION:
COVER PAGE
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
WESTSIDE CONTRACTORS - NEW EV CHARGING SYSTEM
6 HUTTON CENTRE DRIVE, UNIT A, SANTA ANA, CA 92707
Know what's below.
CALL before you dig.
CALL AT LEAST TWO WORKING
DAYS BEFORE YOU DIG
USA
Nor t h
DIG ALERT
CONTRACTOR SHALL VERIFY ALL PLANS & EXISTING LOCATIONS,
CONDITIONS ON THE JOB SITE & SHALL IMMEDIATELY NOTIFY THE
ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR WORK.
SATELLITE VIEW:
VICINITY VIEW:
SYSTEM INFORMATION
MANUFACTURER EVO CHARGE
PRODUCT EVSE, iEVSE, iEVS PLUS
CONNECTOR SAE J1772
LEVEL AC LEVEL 2
MOUNTING WALL OR PEDESTAL
MAX OUTPUT 32A;7.68KW MAX OUTPUT
SCOPE OF WORK:
INSTALL AND ELECTRICALLY CONNECT EVSE
INFRASTRUCTURE AS SHOWN. CONTRACTOR
TO PROVIDE AND INSTALL THE WIRING
DEVICES INCLUDING ALL REQUIRED
ASSOCIATED ITEMS FOR A COMPLETE AND
OPERATIONAL SYSTEM INCLUDING THE
REQUIRED TESTING SPEED IN THE
ELECTRICAL SPEC PACKAGE. CONTRACTOR
SHALL ALSO PROVIDE THE REQUIRED SAW
CUTTING, TRENCHING, BACKFILLING AND
FINISHING OF THE AFFECTED LOT SURFACE
AND RESTORE TO ORIGINAL CONDITION.
PROVIDE AND INSTALL ALL ITEMS SHOWN ON
THE DRAWINGS AND AS SPECIFIED UNLESS
OTHERWISE NOTED AS NOT IN CONTRACT OR
EXISTING TO REMAIN.
TOTAL NUMBER OF EV CHARGERS: 8
UTILITY:
MS-EV RATING:
MS EXISTING OR NEW:
SANTA ANA
225A
EXISTING
METER NO:
BUILDING TYPE: MULTIFAMILY APT COMPLEX
CHARGING KW CAPACITY: 6.656KW
SYSTEM VOLTAGE: 208
SINGLE OR THREE PHASE: THREE PHASE
EVSE LOCATION: PARKING GARAGE
PROJECT INFORMATION:
APPLICABLE CODES:
2020 NATIONAL ELECTRICAL CODE
2022 BUILDING ENERGY EFFICIENCY STANDARDS
2022 CALIFORNIA BUILDING CODE (11B-228.3.1)
2022 CALIFORNIA ELECTRICAL CODE
THIS PROJECT IS EXEMPT FROM ACCESSIBLE
EV STALLS BECAUSE ALL EV STALLS WILL BE
ASSIGNED TO INDIVIDUAL TENANT
GENERAL CONSTRUCTION NOTES:
a. THE JOB SHALL BE MAINTAINED IN A CLEAN, ORDERLY CONDITION FREE OF DEBRIS
AND LITTER SHALL NOT BE UNREASONABLY ENCUMBERED WITH ANY MATERIALS OR
EQUIPMENT AND SHALL BE CLEANED AT THE END OF EACH WORKING DAY.
b. CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. THE
OWNER'S REPRESENTATIVE SHALL BE NOTIFIED OF ANY DISCREPANCIES OF
INCONSISTENCIES.
c. IT SHALL BE CONTRACTORS RESPONSIBILITY TO DESIGN AND PROVIDE ACCURATE
SHORING AND BACKING REQUIRED FOR THE PROTECTION OF LIFE AND PROPERTY
DURING INSTALLATION.
d. ELECTRICAL EQUIPMENT AND APPARATUS INCLUDING BUT NOT LIMITED TO,
SWITCHBOARDS, MOTORS AND CONTROL CENTERS, PANEL BOARDS AND
TRANSFORMERS MUST BE SEISMIC-CERTIFIED AND ANCHORED ACCORDING TO
EQUIPMENT MANUFACTURER'S INSTALLATION INSTRUCTIONS (CEC 110.3 (B), CBC
1613.1, AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) 7-10, CHAPTER 13 SEISMIC
DESIGN REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
e. DUST SHALL BE CONTROLLED AT ALL THE TIMES. WASTE WATER GENERATED DURING
CONSTRUCTION SHALL NOT BE DISCHARGED INTO THE STORM DRAIN SYSTEM. THIS
INCLUDES WASTE FROM PAINTING, SAW CUTTING, CONCRETE WORK, ETC. THE
CONTRACTOR SHALL MAKE ARRANGEMENTS TO ELIMINATE DISCHARGES INTO THE
STORM DRAIN SYSTEM AND, IF NECESSARY, PROVIDE AN AREA FOR ON-SITE WASHING
ACTIVITIES DURING CONSTRUCTION. MATERIALS THAT COULD CONTAMINATE STORM
RUNOFF SHALL BE STORED IN AREAS THAT ARE DESIGNED TO PREVENT EXPOSURE TO
RAINFALL AND NOT ALLOW STORM WATER TO RUN ON TO THE AREA
f. CONSTRUCTION MATERIAL SHALL BE SPECIFIED AND REQUIRED BY THE LATEST
EDITION OF THE BUILDING CODE CURRENTLY ADOPTED BY THE AHJ INCLUDING
ANY/ALL LOCALLY ENFORCED CODES AND AUTHORITIES.ALL MATERIALS AND
EQUIPMENT SHALL BE INSTALLED, APPLIED AND CONNECTED AS DIRECTED BY THE
MANUFACTURERS LATEST WRITTEN SPECIFICATIONS EXPECT WHERE OTHERWISE
NOTED. MATERIALS NOTED ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER THESE
SPECIFICATIONS.
SITE
SITE
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-01
THE PROJECT IS NOT IN THE FEMA DESIGNATED FLOOD ZONE (ZONE A OR E)
Bldg# 101121211
Elec# 20184271
APPROVALS:
PLNG - CSantana
BLDG - CSG Consultants
ELEC - CSG Consultants
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
SITE PLAN
DRAWN DATE 20.06.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, SANTA ANA, CA 92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SITE PLAN:
NOTE: THE HIGH FORWARD REACH SHALL
BE 48 INCHES (1219.2 MM) MAXIMUM AND
THE LOW FORWARD REACH SHALL BE 15
INCHES (381 MM) MINIMUM ABOVE THE
FINISH FLOOR OR GROUND. THE
CONTRACTOR NEED TO PROVIDE DURING
THE INSTALLATION
REACH RANGES:
LEGEND:
MSP - EV
PULL
PNL - EV
N
G
(N) TRANSFORMER
(N)TRANSFORMER
G
M
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
- SAFETY BOLLARD
- CONDUIT
- PARKING SIGN
- MAIN SERVICE PANEL (EV)
- PULL SECTION
- EV PANEL
- EV TRANSFORMER
- DISCONNECT
- METER
- GAS METER
- EV CHARGING STALL
- EV SINGLE PORT
WALL MOUNTED
- EV SINGLE PORT
PEDESTAL MOUNTED
- 2 EV SINGLE PORT
PEDESTAL MOUNTED
- ADA STALL
ELECTRIC
VEHICLE
CHARGING
STATION
PARKING ONLY
WHILE CHARGING
EV PANEL
SAFETY BOLLARD
SAFETY BOLLARD:
PARKING SIGN
EV-02
SCALE: 1/32" = 1'-0"
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
LEVEL 01 FLOOR PLAN
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
ENLARGED PLAN:
NOTE: THE HIGH FORWARD REACH SHALL
BE 48 INCHES (1219.2 MM) MAXIMUM AND
THE LOW FORWARD REACH SHALL BE 15
INCHES (381 MM) MINIMUM ABOVE THE
FINISH FLOOR OR GROUND. THE
CONTRACTOR NEED TO PROVIDE DURING
THE INSTALLATION
REACH RANGES:
LEGEND:
MSP - EV
PULL
PNL - EV
N
G
(N) TRANSFORMER
(N)TRANSFORMER
G
M
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
- SAFETY BOLLARD
- CONDUIT
- PARKING SIGN
- MAIN SERVICE PANEL (EV)
- PULL SECTION
- EV PANEL
- EV TRANSFORMER
- DISCONNECT
- METER
- GAS METER
- EV CHARGING STALL
- EV SINGLE PORT
WALL MOUNTED
- EV SINGLE PORT
PEDESTAL MOUNTED
- 2 EV SINGLE PORT
PEDESTAL MOUNTED
- ADA STALL
ELECTRIC
VEHICLE
CHARGING
STATION
PARKING ONLY
WHILE CHARGING
EV PANEL
SAFETY BOLLARD
SAFETY BOLLARD:
PARKING SIGN
SCALE: 3/16" = 1'-0"
LEVEL 1
CHARGER TOATAL CHARGERS
EV1 - EV4 4 CHARGERS
120121 122 123 124 125 126 127 128 129 130 131 202 203 204 205 206 207 1B
1D 1B
1D
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
201
200
199
198
197
196
195
194
253
193
192
191
190
189
188
187
186
185
184
183
182
181
180
179
178
177
176
175
174
173
172
171
170
169
164 163165 166 167 168
119
118
117
116
115
114
113
112
111
110
109
108
107
106
105
104
103
102
101
100
99
98
97
96
95
94
93
92
91
908988 8786878483828180 7978777675
1B
71 #
1B
WALKWAY
ST
A
R
I
R
W
E
L
L
/
1
D
ST
A
R
I
R
W
E
L
L
/
1
C
ST
A
R
I
R
W
E
L
L
/
1
B
10'-3"
STAIRWAY
NOTE: WALL COLLARS ARE USED AS PHYSICAL BARRIERS
FOR PROTECTING WALL MOUNTED CHARGER'S AGAINST
ACCIDENTAL DAMAGE.
NOTE:THE ELECTRIC VEHICLE CHARGING STATIONS WILL
NOT BE USED AS COMMON CHARGING AREA'S AS PER
11B-228.3.2
NOTE: THE ELECTRIC VEHICLE CHARGING STATIONS ARE
DESIGNATED FOR SPECIFIC TENANT US E ONLY.
NOTE: PLEASE VERIFY EV CHARGER LOCATIONS IN FIELD.
NOTE: THE WALL MOUNTED UNITS ARE POSITIVELY ATTACHED TO
THE STRUCTURE AS REQUIRED BY ASCE 7-16 13.1.4
HUTTON CENTRE DR
(E) 600A MAIN SERVICE PANEL
120/208V, 3PH 4W
(E) "PANEL EV" 200A
120/208V, 3PH 4W
(E) BIKE ROOM AT GROUND
FLOOR
(N) EVO CHARGE, LEVEL 2 CHARGER
PARKING GARAGE: 8 CHARGER'S
PARKING GARAGE ENTRANCE
SCALE: NTS
SHEET NOTES:
1 ATTACH LABEL 01, 02, AND 03 TO
THE FRONT OF (E)PANEL "EV"
2 ATTACH LABEL 03 ADJACENT TO
BREAKER ASSOCIATED WITH (E)PANEL
"EV"
1
2
EV-03
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
PANEL SCHEDULE
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
TOTAL FEEDER AMPS: 23.71A
EV CHARGING LOAD PART OF AUTOMATIC LOAD MANAGEMENT SYSTEM
MAXLOAD OF LOAD MAXIMUM SYSTEM IS 23.71A PER NEC 625.41-625.43
NOTE: AS PER 210.4(B) ALL EV(S) BREAKER/2 POLE WILL DISCONNECT
SIMULTANEOUSLY.
210.0(B): DISCONNECTING MEANS ON MULTI-BRANCH CIRCUITS: EACH
MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT
WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT
THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES.
EV CHARGING LOAD PART OF AUTOMATIC LOAD MANAGEMENT SYSTEM. MAX LOAD OF LOAD
MANAGEMENT SYSTEM IS 23.71A PER NEC 625.42
CHARGIE LOAD MANAGEMENT IS CERTIFIED ENERGY MANAGEMENT EQUIPMENT.
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
(E) PANEL EV: 200A-120/208V-THREE PHASE-4W
CIRCUIT NAME POLES OCPD
RATING
EV
CHARGER'S
CONNECTED
LOAD A B C C B A CONNECTED
LOAD
EV
CHARGER'S POLES OCPD
RATING NAME CIRCUIT
1 LEVEL 2 EV CHARGER 1,2 2 40A 2 6,656
3,328 3,328
6,656 2 2 40A LEVEL 2 EV CHARGER 5,6 2
3 3,328 3,328 4
5 LEVEL 2 EV CHARGER 3,4 2 40A 2 6,656
3,328 3,328
6,656 2 2 40A LEVEL 2 EV CHARGER 7,8 6
7 3,328 3,328 8
9 GATEWAY 1 20A 180 180 10
(LOAD MANAGED) CONNECTED LOAD (VA) 6,656 3,508 3,328 3,328 3,328 6,656
DEMAND LOAD (VA) 8,320 4,340 4,160 4,160 4,160 8,320
TOTAL CONNECTED (VA)26,804
TOTAL DEMAND (VA) :33,460
TOTAL DEMAND (A)92.88
NOTE: CHARGER SETTING WILL BE SET AT 32A PER 40A
BRANCH CIRCUIT.
NOTE: WALL COLLARS ARE USED AS PHYSICAL BARRIERS
FOR PROTECTING WALL MOUNTED CHARGER'S AGAINST
ACCIDENTAL DAMAGE.
NOTE: THE WALL MOUNTED UNITS ARE POSITIVELY ATTACHED TO
THE STRUCTURE AS REQUIRED BY ASCE 7-16 13.1.4
NOTE: THE ELECTRIC VEHICLE CHARGING STATIONS ARE
DESIGNATED FOR SPECIFIC TENANT US E ONLY.
NOTE:THE ELECTRIC VEHICLE CHARGING STATIONS WILL
NOT BE USED AS COMMON CHARGING AREA'S AS PER
11B-228.3.2
EV CHARGING LOAD PART OF AUTOMATIC LOAD MANAGEMENT SYSTEM. MAX
LOAD OF LOAD MANAGEMENT SYSTEM IS 92.88A PER NEC 625.42
LOAD MANAGEMENT IS CERTIFIED BY CHARGIE ENERGY MANAGEMENT
EQUIPMENT.
TOTAL FEEDER AMPS: 92.88A
EV CHARGING LOAD PART OF AUTOMATIC LOAD MANAGEMENT SYSTEM
MAXLOAD OF LOAD MAXIMUM SYSTEM IS 92.88A PER NEC 625.41-625.43
EV-04
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
PANEL SCHEDULE 1
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310)307-5166
JOHNNY HUSTON
LIC: #1086808
PANEL CBP1(NEW)
480/277 VOLTS 3 PHASE 4 WIRE
MAIN: 175A BUS:225A
DISCPRIPTION
VOLT AMPS LT
G
RE
C
MIS
C BRK CIR
C CIRC BR
K
MIS
C
RE
C
LT
G
VOLT AMPS
DISCPRIPTION
Ø A Ø B Ø C Ø A Ø B Ø C
CT-1 22160 1
100
1 2 SPACE
(2)30HP MOTORS 22160 -3 4 SPACE
-22160 -5 6 SPACE
CT-1 3047 1
20
7 8 SPACE
(2)30HP MOTORS 3047 -9 10 SPACE
-3047 -11 12 SPACE
SPACE 13 14 SPACE
SPACE 15 16 SPACE
SPACE 17 18 SPACE
SPACE 19 20 SPACE
SPACE 21 22 SPACE
SPACE 23 24 SPACE
SPACE 25 26 SPACE
SPACE 27 28 SPACE
SPACE 29 30 SPACE
SPACE 31 32 SPACE
SPACE 33 34 SPACE
SPACE 35 36 SPACE
(E) TRANSFORMER
T-1 5000 1
30
37 38 SPACE
15 KVA 5000 -39 40 SPACE
-5000 -41 42 SPACE
Ø A = 30207 VA Ø B = 30207 VA Ø C = 30207 VA LCL = (N/A) LARGEST MOTOR (LM) = (N/A)
TOTAL (Ø A + Ø B + Ø C) = 90621 VA + 25% LCL + 25% LARGEST MOTOR = 90621 VA OR 109.0 AMPS
HIGH PHASE = 90621 VA + 25% LCL + 25% LARGEST MOTOR = 90621 VA OR 109.0 AMPS
PANEL CBP2(NEW)
480/277 VOLTS 3 PHASE 4 WIRE
MAIN: 400A BUS:400A
DISCPRIPTION
VOLT AMPS LT
G
RE
C
MIS
C BRK CIR
C CIRC BR
K
MIS
C
RE
C
LT
G
VOLT AMPS
DISCPRIPTION
Ø A Ø B Ø C Ø A Ø B Ø C
CWP-1 12742 1
90
1 2
90
1 18838 CHP-1
(45 FLA)12742 -3 4 -18838 (68 FLA)
-12742 -5 6 -18838 -
CWP-2 12742 1
60
7 8
90
1 18838 CHP-1
(45 FLA)12742 -9 10 -18838 (68 FLA)
-12742 -11 12 -18838 -
CWP-3 12742 1
60
13 14
15
1 821 EF - 1
(45 FLA)12742 -15 16 -821 (1-1/2HP)
-12742 -17 18 -821 -
SPACE 19 20 SPACE
SPACE 21 22 SPACE
SPACE 23 24 SPACE
SPACE 25 26 SPACE
SPACE 27 28 SPACE
SPACE 29 30 SPACE
SPACE 31 32 SPACE
SPACE 33 34 SPACE
SPACE 35 36 SPACE
SPACE 37 38 SPACE
SPACE 39 40 SPACE
SPACE 41 42 SPACE
Ø A = 76719 VA Ø B = 76719 VA Ø C = 76719 VA LCL = (N/A) LARGEST MOTOR (LM) = (N/A)
TOTAL (Ø A + Ø B + Ø C) = 230157 VA + 25% LCL + 25% LARGEST MOTOR = 230157 VA OR 276.8 AMPS
HIGH PHASE = 230157 VA + 25% LCL + 25% LARGEST MOTOR = 230157 VA OR 276.8 AMPS
PANEL AL (REVISED)
208/120 VOLTS 3 PHASE 4 WIRE
MAIN: 60A BUS:100A
DISCPRIPTION
VOLT AMPS LT
G
RE
C
MI
SC
BR
K
CI
RC CIRC BR
K
MI
SC
RE
C
LT
G
VOLT AMPS
DISCPRIPTION
Ø A Ø B Ø C Ø A Ø B Ø C
1ST FLOOR CHEMICAL ROOM LGTS 20/1 1 2 20/1 4 720 CHILLER ROOM RECEIPTACLES
DEDICATED RECEPTACLES 20/1 3 4 20/1 20 180 CHILLER RM/STORAGE LIGHTS
SHOP LIGHTS 20/1 5 6 20/1 CHILLER TOWER RECEIPTACLES
(6)CONTROL
VALVES(CV-1,2,3,4,5,6)756 20/1 7 8 20/1 IRRIGATION CONTROL
1ST FLOOR CHEMICAL RM
REC/LGTS 20/1 9 10 20/1 IRRIGATION CONTROL
-20/1 11 12 20/1 667 EF-2(1/4 HP)
ENGINEER ROOM 20/1 13 14 20/1 SPARE
SPACE 20/1 15 16 20/1 SPARE
SPACE 20/1 17 18 20/1 INDICATOR LIGHTS SEC DESK
SPACE 20/1 19 20 20/1 DEDICATED RECEIPTACLES
SPACE 20/1 21 22 20/1 SAUD FILTER PUMP CT 1&2
EMS POWER 500 20/1 23 24 20/1 240 2 CONTROL VALVES (CV-7,8)
REFRIGERANT MONITORING SYS 20/1 25 26 20/1 SPACE
SPACE 20/1 27 28 20/1 SPACE
SPACE 20/1 29 30 20/1 SPACE
SPACE 20/1 31 32 20/1 SPACE
SPACE 20/1 33 34 20/1 SPACE
SPACE 20/1 35 36 20/1 SPACE
(E) TRANSFORMER T-1 5000 20/1 37 38 20/1 SPACE
15 KVA 5000 20/1 39 40 20/1 SPACE
-5000 20/1 41 42 20/1 SPACE
Ø A = 1476 VA Ø B = 1080 VA Ø C = 1407 VA LCL = 1080 LARGEST MOTOR (LM) = (N/A)
TOTAL (Ø A + Ø B + Ø C) = 3963 VA + 25% LCL + 25% LARGEST MOTOR = 4233 VA OR 11.7 AMPS
HIGH PHASE = 1476 VA + 25% LCL + 25% LARGEST MOTOR = 1476 VA OR 12.3 AMPS
EV-05
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
SINGLE LINE DIAGRAM
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SINGLE LINE DIAGRAM:
NOTE:
EQUIPMENT WITH SERIES RATING APPLIED WILL BE FIELD
MARKED "CAUTION SERIES RATED SYSTEM 225 AMPS
AVAILABLE. IDENTIFIED REPLACEMENT COMPONENT
REQUIRED." (PER SECTION 110.22)
NOTE:
SERIES RATED SYSTEMS ARE PERMITTED TO BE
SELECTED UNDER ENGINEERING SUPERVISION FOR
EXISTING INSTALLATIONS IN ACCORDANCE WITH NEC
240.86(A)
VOLTAGE DROP: COPPER WIRE
3% OF 240 = 7.2 VOLTS
3% OF 208 = 6.24 VOLTS
#8 AWG @240V =7.2V
@150FT UPSIZE BRANCH CIRCUIT
#8 AWG @208V =6.24V
@125FT UPSIZE BRANCH CIRCUIT
#6 AWG @240V =7.2V
@230FT UPSIZE BRANCH CIRCUIT
#6 AWG @208V =6.24V
@200FT UPSIZE BRANCH CIRCUIT
#4 AWG @240V =7.2V
@350FT UPSIZE BRANCH CIRCUIT
#4 AWG @208V =6.24V
@320FT UPSIZE BRANCH CIRCUIT
LOAD CONTROLLER NOTE:
LOAD CONTROLLER CONTROLS THE TIME OF USAGE FOR SCE
AND IT ALSO ACTS AS THE COMMUNICATION SYSTEM BETWEEN
ALL THE CHARGERS.
IT ALSO HAS THE ONLINE PORTAL FOR THE PAYMENT SYSTEM
FOR THE CLINETS TO MAKE SURE THAT THE USER IS BEING
CHARGED FOR THE ELECTRICITY.
CONDUIT CONTENTS: (2X) HOTS, (1X) E.G.C. (#8 AWG)
(PER UNIT)
CONDUIT TYPES: 1" EMT TO J-BOX/1/2" EMT TO EACH UNIT.
EV CHARGER:40A,NEMA 4, UL LISTED
(N)RACEWAY WITH 2 CURRENT-CARRYING
CONDUCTORS(PER RUN)
40A #8 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
40A #6 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
CONDUCTOR AMPERAGE RATING:
55* 0.91*0.80= 40.1A @ 240 MAX.
FEEDER- (MAX. OPERATING CURRENT)
32A* 1.25= 40.0A @ 240V PEAK
ELECTRICAL DETAILS
NO OF CHARGING UNITS 8
NO OF CHARGING PORTS 8
ELECTRICAL RATING PER PORT 32A
MAXIMUM CAPACITY PER PORT 32A
MS-EV RATING 225
VOLTAGE 208V
PHASE THREE PHASE
EXISTING METER
LADWP LOAD CALCULATIONS
TOTAL EXISTING LOAD KW
EV DEMAND LOAD 8.545KW
UNIT METERS @24%293.532KW
TOTAL LOAD KW
NEW EV BREAKER
REQUIRED BREAKER 40A
BUILDING USAGE
TOTAL EXISTING LOAD KW
CHARGERS CONNECTED TO SYSTEM
EV DEMAND LOADS 8.545KW
CHARGER LOAD FOR BRANCH CIRCUTS
TOTAL EV CHARGER DEMAND AMP 23.71A
GATEWAY
#2 10AWG CONDUCTORS & #1 10AWG
GROUND IN 3/4" EMT CONDUIT
(TO ETHERNET)
IR COMMUNICATION
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
SINGLE LINE DIAGRAM:
NOTE:
EQUIPMENT WITH SERIES RATING APPLIED WILL BE FIELD
MARKED "CAUTION SERIES RATED SYSTEM 200 AMPS
AVAILABLE. IDENTIFIED REPLACEMENT COMPONENT
REQUIRED." (PER SECTION 110.22)
NOTE:
SERIES RATED SYSTEMS ARE PERMITTED TO BE
SELECTED UNDER ENGINEERING SUPERVISION FOR
EXISTING INSTALLATIONS IN ACCORDANCE WITH NEC
240.86(A)
VOLTAGE DROP: COPPER WIRE
3% OF 240 = 7.2 VOLTS
3% OF 208 = 6.24 VOLTS
#8 AWG @240V =7.2V
@150FT UPSIZE BRANCH CIRCUIT
#8 AWG @208V =6.24V
@125FT UPSIZE BRANCH CIRCUIT
#6 AWG @240V =7.2V
@230FT UPSIZE BRANCH CIRCUIT
#6 AWG @208V =6.24V
@200FT UPSIZE BRANCH CIRCUIT
#4 AWG @240V =7.2V
@350FT UPSIZE BRANCH CIRCUIT
#4 AWG @208V =6.24V
@320FT UPSIZE BRANCH CIRCUIT
LOAD CONTROLLER NOTE:
LOAD CONTROLLER CONTROLS THE TIME OF USAGE FOR SMUD
AND IT ALSO ACTS AS THE COMMUNICATION SYSTEM BETWEEN
ALL THE CHARGERS.
IT ALSO HAS THE ONLINE PORTAL FOR THE PAYMENT SYSTEM
FOR THE CLINETS TO MAKE SURE THAT THE USER IS BEING
CHARGED FOR THE ELECTRICITY.
CONDUIT CONTENTS: (2X) HOTS, (1X) E.G.C. (#8 AWG)
(PER UNIT)
CONDUIT TYPES: 1" EMT TO J-BOX/1/2" EMT TO EACH UNIT.
EV CHARGER:40A,NEMA 4, UL LISTED
(N)RACEWAY WITH 2 CURRENT-CARRYING
CONDUCTORS(PER RUN)
40A #8 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
40A #6 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
CONDUCTOR AMPERAGE RATING:
55* 0.91*0.80= 40.1A @ 240 MAX.
FEEDER- (MAX. OPERATING CURRENT)
32A* 1.25= 40.0A @ 240V PEAK
LOAD CALCULATION:
EXISTING HIGH DEMAND (108KW) X 1.25 = 135.0 KW
NEW ELEVATOR (15 HP) = 16.8 KW
NEW PANEL "HB" CONNECTED LOAD = 46.4 KW
+25% OF LARGEST MOTOR = 4.2 KW
EV PANEL = 92.88 KW
TOTAL = 295.28 KW
NOTE: CHARGER SETTING WILL BE SET AT 32A PER 40A
BRANCH CIRCUIT.
NOTE: WALL COLLARS ARE USED AS PHYSICAL BARRIERS
FOR PROTECTING WALL MOUNTED CHARGER'S AGAINST
ACCIDENTAL DAMAGE.
NOTE: EV CHARGER'S ARE CONNECTED TO EV PANEL
(SEE LOAD CALC IN PAGE EV-05)15
EV-06
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
NOTES
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SINGLE LINE NOTES:
1. ALL CONDUCTORS SHALL BE COPPER AS FOLLOWS:
#12AWG AND SMALLER - SOLID, TW
#10AWG AND LARGER - STRANDED, THHN OR THWN
ALL CONDUCTORS SIZES ARE BASED ON 75°C TEMPERATURE
RATINS (NEC.2020 TABLE 310.16)
2. ALL NEW CIRCUIT BREAKERS, FUSIBLE SWITCHES IN MAIN
SWITCHBOARD OR PANEL BOARDS SHALL BE SERIES RATED TO
MATCH EXISTING AIC RATING OR APPROVED EQUAL OR 65kAIC,
UNLESS NOTED OTHERWISE.
3. MOTOR CIRCUIT PROTECTORS SHALL NOT BE A PART OF SERIES
COMBINATION INTERRUPTING RATINGS.
4. SERIES COMBINATION AIC RATINGS SHALL NOT BE USED WHEN
THE SECONDARY EQUIPMENT IN THE SERIES IS SUBJECT TO A
TOTAL CONNECTED FULL LOAD MOTOR CURRENT OF MORE THAN
1% OF ITS AIC RATINGS.
5. EQUIPMENT ENCLOSURES SHALL BE CLEARLY MARKED
"CAUTION-SERIES RATED SYSTEM - 65KAMPS AVAILABLE,
IDENTIFIED REPLACEMENT COMPONENTS REQUIRED". IN
COMPLIANCE WITH 2022 CEC (NEC 2020) SECTION 110-22 END
USE EQUIPMENT SHALL ALSO BE MARKED WITH THE HIGHER
SERIES COMBINATION INTERRUPTING RATINGS AS PER 2022 CEC
SECTION 240-89(C). NO EXCEPTION.
6. FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE
HOLDERS.
7. ELECTRICAL EQUIPMENT SHALL BE LISTED BY THE CITY, WHERE
THE PROJECT IS LOCATED, RECOGNIZED ELECTRICAL TESTING
LABORATORY OR APPROVED BY THE DEPARTMENT.
8. NO PIPING, NO DUCTS OF EQUIPMENT FOREIGN TO ELECTRICAL
EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE
DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT.
9. ALL ITEMS SHOWN ARE EXISTING U.O.N.
10. ALL FEEDER LENGTHS SHOWN ARE FOR VOLTAGE DROP AND
SHORT CIRCUIT CALCULATIONS ONLY.
11. MAXIMUM AVAILABLE FAULT CURRENT AT MAIN SERVICE
ENTRANCE IS ASSUMED TO BE 42KAIC U.O.N.
12. IN MAIN SWITCHBOARD BUS BRACING AND A.I.C. RATINGS OF
ALL DEVICES SHALL BE 42,000 MIN. U.O.N.
13. CIRCUIT BREAKERS IN ALL MAIN SWITCHBOARDS AND PANELS
SHALL BE FROM THE SAME MANUFACTURER AND ENTIRE SYSTEM.
14. ALL REMAINING SPACES IN MAIN SWITCHBOARDS AND PANELS
SHALL BE BUSSED.
15. ALL SUBPANELS SHALL BE RATED 42,000 AIC U.O.N.
16. SUBMIT SHOP DRAWINGS OF MAIN SWITCHBOARD TO SERVING
UTILITY COMPANY AND OBTAIN THERE APPROVAL PRIOR TO
RELEASING SHOP DRAWINGS TO MANUFACTURER. VERIFY TYPE
OF REQUIRED METER SOCKETS (IF NECESSARY).
17. ALL SECTIONS OF MAIN SWITCHBOARD SHALL HAVE THE
HORIZONTAL AND VERTICAL BUSS BARS RATED FOR THE
AMPERE RATING SHOWN ON SINGLE LINE DIAGRAMS.
REDUCTION OF AMPERE RATING OF BUSS BARS THROUGHOUT
THE SECTIONS OF MAIN SWITCHBOARDS IS NOT ACCEPTABLE.
18. NOTIFY SWITCHBOARD PANEL BOARDS MANUFACTURERS OF
FEEDER TERMINATIONS (TOP OR BOTTOM) PRIOR TO
SUBMITTING SHOP DRAWINGS.
19. PROVIDE A METALLIC CARD HOLDER ON INSIDE OF DOOR OF
EACH PANEL BOARD FOR INDEX CARD AND ACCURATE
TYPEWRITTEN PANEL SCHEDULE BE PUT BEHIND HEAVY PLASTIC
COVER INTO EACH PANEL. ROOM NUMBERS SHALL NOT BE THE
ONES ON THE PLANS BUT THE ONES DESIGNATED BY THE
ARCHITECT AND/OR OWNER.
20. PROVIDE TWO (2) KEYS WITH EACH PANEL BOARD. ALL PANELS
BOARDS LOCKS SHALL BE KEYED ALIKE.
21. WHERE TWO OF THREE POLE BREAKERS OCCUR IN LIGHTING
PANELS THE MULTI-POLE BREAKERS SHALL HAVE A COMMON
TRIP "QUICKLAG" TYPE UNITS. SINGLE POLE BREAKERS WITH
TIE-BAR BETWEEN HANDLES WILL NOT BE ACCEPTABLE.
22. PROVIDE BLACK ON WHITE LAMINATED PLASTIC NAMEPLATE
ENGRAVED IN MIN 14" HIGH LETTERS, ATTACHED NAMEPLATES TO
EQUIPMENT, SWITCHBOARD(S), DISTRIBUTION BOARD(S), PANEL
BOARDS AND DISCONNECTS ETC, WITH RIVETS, BOLTS, OR
SHEET METAL SCREWS. CEMENT ATTACHMENTS ARE NOT
ACCEPTABLE.
23. TIME SWITCHES, CONTACTORS, RELAYS, ETCH SHOWN TO BE
FURNISHED WITH PANEL BOARDS SHALL BE LOCATED IN
BARRIERED COMPARTMENTS BEHIND SEPARATE DOORS,
MAINTAIN 2" OF SOLD TRIP BETWEEN DOORS. IF NECESSARY,
INSTALL SWITCHES, CONTACTORS, RELAYS, ETCH IN SEPARATE
WEATHERPROOF CABINETS WITH HINGED LOCKABLE DOORS.
PROVIDE SCREW-ON TYPE NAMEPLATES, FULLY COMPLY WITH
LATEST HANDICAP STANDARDS.
DEMOLITION NOTES:
1. THE DRAWINGS SHOW THE WORK TO BE IN PLACE AT THE
COMPLETION OF INSTALLATION. MAKE NECESSARY ALTERATIONS
TO COORDINATE AND CONNECT THE EXISTING ELECTRICAL WORK
WITH THE NEW SUCH THAT, WHEN THE WORK IS DONE, THE
ENTIRE ELECTRICAL INSTALLATION, EXISTING AND NEW, IS IN
COMPLETE OPERATING CONDITION.
2. UNLESS SPECIFICALLY NOTED ON THE CONTRARY, ALL EXISTING
LIGHTING FIXTURES, SWITCHES, CONTROLS AND OTHER
MATERIALS OR EQUIPMENTS WHICH ARE REPLACED BY NEW AND
ARE NOT INDICATED TO BE REUSED SHALL BE RETURNED TO THE
OWNER OR BE DISPOSED AS DIRECTED BY THE OWNER.
3. EXISTING MATERIAL TO REMAIN UPON COMPLETION IS INDICATED
ON DRAWINGS AS EXISTING, FEEDERS (CONDUIT AND WIRES)
ARE EXISTING TO THEIR RESPECTIVE SOURCE. ALTHOUGH NOT
INDICATED ON THE DRAWINGS. TEMPORARY REMOVAL OR
RE-ROUTE CONDUITS AND REPLACE EXISTING WIRES WITH NEW
DURING CONSTRUCTION WORK MAYBE REQUIRED.
4. PROVIDE AND INSTALL NEW COVER PLATES FOR ALL REMOVED
OUTLETS, SWITCHES, LIGHT FIXTURES, AND OTHER ELECTRICAL
DEVICES WHEN THE OUTLET BOX IS TO REMAIN.
5. REMOVE ALL EXISTING ABANDONED FEEDERS (CONDUITS AND
WIRES) BACK TO PANEL BOARDS. LABEL NEW PANEL DIRECTORY
AS "SPARE".
6. MAINTAIN CONTINUITY OF ALL ELECTRICAL SYSTEMS, EQUIPMENT,
ETC., FED BY ABANDONED OUTLET. THEY SHOULD BE IN
OPERATION AFTER THE WORK IS DONE. MAINTAINING
CONTINUITY SHALL CONSIST OF RE-ROUTING OF CONDUIT AND
WIRING, AS REQUIRED TO SUIT THE EXISTING CONDITIONS.
7. (E) J-BOX DENOTES APPROXIMATE LOCATION OF EXISTING BOXES
IN ACCESSIBLE CEILING SPACE. ALL CONDUIT SHOWN FROM
J-BOX IS NEW UNLESS SHOWN OTHERWISE AS EXISTING.
8. EXISTING LOADS SHOWN ON PANEL SCHEDULES ARE BASED ON
ASSUMPTIONS MADE BY FIELD VISIT, ELECTRICAL BILLS OR
PUBLIC RESOURCES. NOTIFY ENGINEER IMMEDIATELY IF LOADS
EXCEED 16AMPS ON ANY 20A/1P CIRCUIT. NO EXCEPTION.
9. CAREFULLY REVIEW ARCHITECT'S DEMO DRAWINGS FOR
LOCATION OF WALLS BEING REMOVED UNDER THE SCOPE OF THIS
WORK AND REMOVE ALL FEEDERS (CONDUITS AND WIRES) BACK
TO THE LAST DEVICE LEFT IN SERVICE. DON NOT LEAVE
ABANDONED.
10. CAREFULLY REVIEW ARCHITECT'S DEMO DRAWINGS FOR EXISTING
FLOOR BOXES BEING REMOVED UNDER THIS SCOPE OF WORK.
REMOVE FLOOR BOXES AND FEEDERS (CONDUITS AND WIRES)
BACK TO LAST DEVICE LEFT IN SERVICE. DO NOT LEAVE
ABANDONED.
STRIPING AND MARKINGS:
1. ACCESS AISLES SHALL BE MARKED WITH PAINTED BORDERLINES
AROUND THEIR PERIMETER
2. THE AREA WITHIN THE BORDERLINES SHALL BE MARKED WITH
HATCHED LINES A MINIMUM OF 36 INCHES ON CENTER
3. THE COLOR OF THE BORDERLINES, HATCHED LINES, AND LETTERS
SHALL CONTRAST WITH THAT OF THE SURFACE OF THE ACCESS
AISLE
4. THE COLOR OF ALL STRIPING AND MARKINGS SHALL NOT BE THE
BLUE COLOR USED FOR IDENTIFICATION OF ACCESSIBLE PARKING
SPACES PER 11B-502.3.3
5. THE WORDS "NO PARKING" SHALL BE PAINTED WITHIN EACH
ACCESS AISLE IN LETTERS A MINIMUM OF 12 INCHES IN HEIGHT
AND LOCATED TO BE VISIBLE FROM THE ADJACENT VEHICULAR
WAY
6. THE WORDS "EV CHARGING ONLY" SHALL BE PAINTED AT THE
LOWER END OF EACH EV SPACE IN LETTERS A MINIMUM OF 12
INCHES IN HEIGHT. THE CENTERLINE OF THE TEXT SHALL BE 6
INCHES MAXIMUM FROM THE CENTERLINE OF THE VEHICLE SPACE
AND ITS LOWER CORNER AT, OR LOWER SIDE ALIGNED WITH, THE
END OF THE PARKING SPACE. (11B-812.8.9)
GROUNDING:
1. ALL SERVICES SUPPLYING THE BUILDING SHALL HAVE THE SAME
GROUNDING ELECTRODE SYSTEM.
2. REMOVAL OF A GRID INTERACTIVE INVERTER OR OTHER
EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION
BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE
PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED
CONDUCTOR.
3. GROUND BOND CONDUCTOR SHALL NOT BE SPLICED.
4. USE EQUAL OR APPROVED "LAY IN LUG" ILSCO, UL-467 RATED FOR
GROUNDING AND BONDING. HIGH STRENGTH COPPER ALLOY W/
SS SCREW (AS NECESSARY)
CONDUCTORS:
1. ALL CONDUCTORS SHALL BE COPPER UNLESS OTHERWISE NOTED.
2. ALL PROPOSED CONDUCTORS RATED FOR 90°C., HOWEVER
EQUIPMENT RATINGS SHALL BE ASSUMED TO BE 75°C FOR ALL
BUILDING FEEDERS AND THEREFORE TERMINATIONS PRIOR TO
CONNECTION. INTERMEDIATE JUNCTION BOX MAY BE REQUIRED
TO CHANGE FROM 90°C TO 75°C WIRING. MATERIAL SHALL BE
COPPER AND 90°C RATED, SUITABLE FOR SUN EXPOSURE AND WET
LOCATIONS. FIELD APPLIED COATINGS ARE NOT ACCEPTABLE.
3. ALL WIRE INSULATION TYPE SHALL BE EV WIRE FOR AC EV
CIRCUIT RUNS.
4. EACH EV MODULE HAS A POSITIVE AND NEGATIVE EV WIRE
"SUNLIGHT RESISTANT" QUICK CONNECT PLUG IN LEAD. VERIFY
COMPATIBLE EXTENSION WIRE PRIOR TO INSTALLATION.
5. ALL INTER-MODULE SERIES CONNECTIONS TO BE TIE STRAPPED
(W/ BLACK UV RESISTANT TIE
625.41 OVERCURRENT PROTECTION: OVERCURRENT PROTECTION
FOR FEEDERS AND BRANCH CIRCUITS SUPPLYING EQUIPMENT SHALL
BE SIZED FOR CONTINUOUS DUTY AND SHALL HAVE A RATING OF NOT
LESS THAN 125 PERCENT OF THE MAXIMUM LOAD OF THE EQUIPMENT.
WHERE NONCONTINUOUS LOADS ARE SUPPLIED FROM THE SAME
FEEDER, THE OVER-CURRENT DEVICE SHALL HAVE A RATING OF NOT
LESS THAN THE SUM OF THE NON-CONTINUOUS LOADS
PLUS 125 PERCENT OF THE CONTINUOUS LOADS.
625.42 RATING: THE EQUIPMENT SHALL HAVE SUFFICIENT RATING
TO SUPPLY THE LOAD SERVED. ELECTRIC VEHICLE CHARGING LOADS
SHALL BE CONSIDERED TO BE CONTINUOUS LOADS FOR THE
PURPOSES OF THIS ARTICLE.
WHERE AN AUTOMATIC LOAD MANAGEMENT SYSTEM IS USED, THE
MAXIMUM EQUIPMENT LOAD ON A SERVICE AND FEEDER SHALL BE THE
MAXIMUM LOAD PERMITTED BY THE AUTOMATIC LOAD MANAGEMENT
SYSTEM.
625.43 DISCONNECTING: MEANS FOR EQUIPMENT RATED MORE
THAN 60 AMPERES OR MORE THAN 150 VOLTS TO GROUND, THE
DISCONNECTING MEANS SHALL BE PROVIDED
AND INSTALLED IN A READILY ACCESSIBLE LOCATION. THE
DISCONNECTING MEANS SHALL BE LOCKABLE OPEN IN ACCORDANCE
WITH 110.25.
WIRING METHODS:
1. FOR UNDERGROUND AND EXPOSED UP TO +5'-0" OR DAMP
LOCATION, THE CONDUIT SHALL BE RIGID STEEL GALVANIZED
IMC. NO RUNNING THREADS ARE PERMITTED.
2. GALVANIZED EMT SHALL BE USED IN DRY CONCEALED
LOCATIONS AN EXPOSED ABOVE +5-0". EMT CONNECTORS
SHALL BE WATERTIGHT COMPRESSION TYPE.
3. GALVANIZED FLEXIBLE CONDUIT SHALL BE USED ONLY FOR
MOTOR AND FIXTURE CONNECTIONS IN LENGTHS NOT TO
EXCEED 66'
4. CONDUITS PENETRATING THE ROOF SHALL BE FLASHED AND
COUNTER FLASHED.
5. INSTALL FITTINGS, SPECIAL DEVICES AND MATERIAL, WHICH
MAY BE REQUIRED FOR THE PROPER INSTALLATION OF THE
CONDUIT SYSTEM.
NOTE:
110.27(B)PREVENT PHYSICAL DAMAGE:IN
LOCATIONS WHERE ELECTRICAL EQUIPMENT IS
LIKELY TO BE EXPOSED TO PHYSICAL DAMAGE,
ENCLOSURES OR GAURDS SHALL BE SO
ARRANGED AND OF SUCH STRENGTH AS TO
PREVENT SUCH DAMAGE.
DEDICATED ELECTRICAL SPACE: WIDTH AND
DEPTH OF EQUIPMENT EXTENDING FROM THE
FLOOR TO 1.8M (6FT) ABOVE EQUIPMENT OR TO
STRUCTURAL CEILING
NOTE:
NEW SERVICES IS LOCATED OUTDOORS IN THE
PARKING SPACES THAT ARE BELOW THE
RESIDENTIAL
UNITS
ACCESSIBLE ROUTES AND ACCESS AISLES:
1. ACCESS AISLES SHALL BE LEVEL WITH THE EV SPACE SERVED,
AND SLOPES/CROSS -SLOPES SHALL NOT EXCEED 1:48
2. ADA COMPLIANT EV SPACES SHALL BE LOACTED ON AN
ACCESSIBLE ROUTE TO AN ACESSIBLE BUILDING ENTRANCE.
(11B-206.4 & 11B-812.5)
3. EVCS SHALL BE DESIGNED SO ACCESSIBLE ROUTES ARE NOT
OBSTRUCTED BY CABLES OR OTHER ELEMENTS. (11B-812.5.5)
4. PROVIDE CURBS, WHEEL STOPS, BOLLARDS, OR OTHER
BARRIERS TO PREVENT ENCROACHMENT OF VEHICLE OVER THE
REQUIRED CLEAR WIDTH OF ACCESSIBLE ROUTES. (11B-812.5.3)
NOTE:
"ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR
CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY
ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFTY
HEALTH ADMINISTRATION."
IMPORTANT BID NOTES:
1. DUE TO THE SMALL SCALE OF DRAWINGS,
IT IS NOT ALWAYS POSSIBLE TO SHOW
ALL DEVICES WHICH MAYBE REQUIRED.
CONTRACTOR SHALL BE RESPONSIBLE TO
VERIFY ALL EXISTING CONDITIONS
BEFORE SUBMITTING HIS/HER BID. NO
ADDITIONAL COMPENSATION WILL BE
MADE FOR EXTRA DUE TO CONTRACTOR'S
FAILURE TO VISIT THE JOB SITE AND/OR
FAILURE TO DETERMINE ALL EXISTING
CONDITIONS BEFORE SUBMITTING
HIS/HER BID.
2. REFER TO COMPLETE ARCHITECTURAL
AND ELECTRICAL DRAWINGS FOR
ADDITIONAL NOTES, SPECIFICATIONS,
DETAILS, CONTROLS, ETC. REPORT TO
ARCHITECTURE'S CLARIFICATION IN BASE
BID. THIS REQUIREMENT WILL BE
STRICTLY ENFORCED. NO CHANGE
ORDERS WILL BE ALLOWED IF THE
CONTRACTOR FAILS TO PERFORM THIS
SIGNAGE REQUIREMENTS AND NOTES:
1. ACCESSIBLE SIGNAGE IS NOT REQUIRED
WHERE A TOTAL OF FOUR OF FEWER EV
SPACES ARE PROVIDED.
2. FIVE TO TWENTY-FIVE TOTAL EV SPACES
ARE PROVIDED:
A - ONE VAN ACCESSIBLE EV SPACE
SHALL BE IDENTIFIED BY IS A
SIGNAGE
B - ACCESSIBLE SIGNAGE IS NOT
REQUIRED AT THE STANDARD
ACCESSIBLE EV SPACES
3. TWENTY-SIX OR MORE EV SPACES ARE
PROVIDED
4. ALL REQUIRED VAN ACCESSIBLE AND
STANDARD ACCESSIBLE EV SPACES SHALL
BE IDENTIFIED BY ISA SIGNAGE
5. IDENTIFICATION SIGNS SHALL BE
REFLECTORIZED WITH MINIMUM AREA OF
70 SQUARE INCHES. (11B-812.8.7)
6. THE IDENTIFICATION SIGN SHALL BE
VISIBLE FROM THE EV SPACE IT SERVES
7. SIGNS IDENTIFYING VAN ACCESSIBLE EV
SPACES SHALL CONTAIN THE WORDS "VAN
ACCESSIBLE"
8. IDENTIFICATION SIGNS SHALL BE
PERMANENTLY POSTED EITHER
IMMEDIATELY ADJACENT TO THE VEHICLE
SPACE OF WITHIN THE PROJECTED
VEHICLE SPACE WIDTH AT THE FRONT END
OF VEHICLE SPACE. (11B-812.8.7)
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-07
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
PLACARD
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CAUTION
SERVICE 2SERVICE 1
DEDICATED TO EV ONLY
OTHER LOADS MUST
NOT BE CONNECTED
LABEL 01 LOCATION:
TO BE PLACED IN DEDICATED EV SUB PANEL
& NEXT TO THE EV BREAKER IN THE
DISTRIBUTION PANEL
SIZE: 4" X 2" QTY:1
LABEL 02 LOCATION:
TO BE PLACED IN DEDICATED EV SUB PANEL
& NEXT TO THE EV BREAKER IN THE
DISTRIBUTION PANEL
SIZE: 4" X 2" QTY:1
6 Hutton Centre Drive, Unit A,
Santa Ana, CA 92707
208V 225A 3Ø 4W
WARNING PLACARDS:
PNL EV 1
LABEL 03 LOCATION:
TO BE PLACED ON THE CIRCUITS ON MSP - EV
SIZE: 1'6" X 1" QTY:1
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-08
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
SPEC SHEET 1
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-09
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
SPEC SHEET 2
DRAWN DATE 21.05.2024
DRAWN BY CAMERON
REVIEWED BY SHELDON
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-10
6 E Hutton Center Dr
#A12/9/2024
z^EK
,16758&7,216
25$1*( &2817< ),5( $87+25,7<
3ODQ6XEPLWWDO&ULWHULD
&200(5&,$/SURMHFWV08/7,)$0,/<5(6,'(17,$/SURMHFWV
DQG5(6,'(17,$/75$&7GHYHORSPHQWV
)LOOLQWKHSURMHFWEXVLQHVVDGGUHVVDQGSURYLGHDEULHIGHVFULSWLRQRIWKHVFRSHRIZRUNDQGW\SHRIEXVLQHVVRSHUDWLRQWKDWZLOOWDNHSODFH
$QVZHUTXHVWLRQVWKURXJKUHDGDQGLQLWLDOLWHPVDQGWKHQFRPSOHWHDQGVLJQWKHFHUWLILFDWLRQVHFWLRQ
,I\RXDQVZHU³<(6´WRDQ\SDUWRITXHVWLRQVWKURXJKVXEPLWWKHW\SHRISODQLQGLFDWHGLQLWDOLFVWR2&)$
,QVRPHFDVHVRWKHUSODQW\SHVQRWLQGLFDWHGKHUHLQPD\DOVREHQHFHVVDU\GHSHQGLQJRQVSHFLILFFRQGLWLRQVRURSHUDWLRQV
9LVLWZZZRFIDRUJIRUVXEPLWWDOLQIRUPDWLRQDQGORFDWLRQV,I\RXQHHGDVVLVWDQFHLQILOOLQJRXWWKLVIRUPRUKDYHTXHVWLRQVUHJDUGLQJ
UHTXLUHPHQWVIRUUHYLHZSOHDVHFRQWDFW2&)$DWRUYLVLWXVDW)LUH$XWKRULW\5RDG,UYLQH&$
$GGUHVV6XLWH&LW\
3URMHFW6FRSH%XVLQHVV'HVFULSWLRQ
&RQVWUXFWLRQRIDQHZEXLOGLQJDQHZVWRU\RULQFUHDVHWKHIRRWSULQWRIDQH[LVWLQJEXLOGLQJ" &KDQJHVWRURDGZD\V
FXUEVRU GULYH DLVOHV" $GGLWLRQ UHORFDWLRQRU PRGLILFDWLRQ RI ILUH K\GUDQWV RUIHQFHVJDWHV" &RQVWUXFWLRQ ZLWKLQ
IHHWRIDQDFWLYHRUSURSRVHGRLOZHOO")LUH0DVWHU3ODQ35
3URSHUW\LVDGMDFHQWWRDZLOGODQGDUHDRUQRQLUULJDWHGQDWLYHYHJHWDWLRQ"
)LUH0DVWHU3ODQ35D)XHO0RGLILFDWLRQ3ODQPD\DOVREHUHTXLUHG3535
/RFDWHGLQRU¶IURPD'LYLVLRQRI2LO*DVDQG*HRWKHUPDO5HVRXUFHV'2**5ILHOGERXQGDU\¶IURP
DQRLOJDVVHHSRU¶IURPDODQGILOO"0HWKDQH:RUN3ODQ35
,QVWDOODWLRQPRGLILFDWLRQUHSDLURIXQGHUJURXQGSLSLQJEDFNIORZSUHYHQWHUVRUILUHGHSDUWPHQWFRQQHFWLRQVVHUYLQJ
SULYDWHILUHK\GUDQWVSULQNOHUVWDQGSLSHV\VWHPV"8QGHUJURXQG3ODQ3535
'ULQNLQJGLQLQJUHFUHDWLRQPHHWLQJVWUDLQLQJUHOLJLRXVIXQFWLRQVRURWKHUJDWKHULQJVLQDURRP!VTIW!
VTIWIRUWUDLQLQJDGXOWHGXFDWLRQRU!SHRSOH"+HDOWKFDUHRXWSDWLHQWVHUYLFHVIRU!SHRSOHZKRPD\EHXQDEOH
WRLPPHGLDWHO\HYDFXDWHZLWKRXWDVVLVWDQFH"(GXFDWLRQIRUFKLOGUHQDFDGHPLFWXWRULQJIRUDJHVLVH[HPSWXQOHVV
FODVVLILHGDVDQ(RFFXSDQF\E\WKH%XLOGLQJ2IILFLDO"$GXOWFKLOGGD\FDUH"KRXUFDUHVXSHUYLVLRQ",QFDUFHUDWLRQ
RU UHVWUDLQW" +RWHODSDUWPHQW RU UHVLGHQWLDO IDFLOLW\ ZLWK XQLWV DQG VWRULHV VWRU\ WRZQKRXVHVURZKRXVHV
ZKHUHDQLQGHSHQGHQWGLUHFWH[LWWRJUDGHLVSURYLGHGIRUGZHOOLQJDUHH[HPSW"&RQJUHJDWHKRXVLQJGRUPLWRULHV
ZLWKSHRSOH" +LJKULVHVWUXFWXUHIHHWWRKLJKHVWRFFXSLHGIORRUOHYHO"$UFKLWHFWXUDO3ODQ3535
,QVWDOODWLRQPRGLILFDWLRQRIORFNVGHOD\LQJRUSUHYHQWLQJRFFXSDQWVIURPOHDYLQJDVSDFHRUUHTXLULQJXVHRIDFDUG
EXWWRQ RU VLPLODU DFWLRQ WR RSHQ D GRRU LQ WKH GLUHFWLRQ RI H[LW WUDYHO"$UFKLWHFWXUDO 6SULQNOHU DQGRU $ODUP 3ODQ
GHSHQGLQJRQWKHRFFXSDQF\DQGW\SHRIGHYLFHLQVWDOOHG353535353535
,QVWDOODWLRQPRGLILFDWLRQXVH RI VSUD\ ERRWKV GXVW FROOHFWLRQ GU\ FOHDQLQJ LQGXVWULDO RYHQVGU\LQJ HTXLSPHQW
LQGXVWULDOFRPPHUFLDO UHIULJHUDWLRQ V\VWHPV FRPSUHVVHG JDVVHV WDQNV IRU FU\RJHQLF RU IODPPDEOHFRPEXVWLEOH
OLTXLGVYDSRUUHFRYHU\VPRNHFRQWUROEDWWHU\EDFNXSFKDUJLQJV\VWHPV!JDOHOHFWURO\WH!OEOLWKLXP
LRQZHOGLQJEUD]LQJVROGHULQJRSHQIODPHWRUFKHVFXWWLQJJULQGLQJRURWKHUVLPLODURSHUDWLRQV"
6SHFLDO(TXLSPHQW3ODQ353535
6WRUDJHXVHUHVHDUFK ZLWK IODPPDEOHFRPEXVWLEOH OLTXLGV RU RWKHU FKHPLFDOV" 0RWRU YHKLFOHDLUFUDIW
PDLQWHQDQFHUHSDLU"&DELQHWU\ZRRGZRUNLQJILQLVKLQJ IDFLOLW\"&KHP &ODVV IORRU SODQ IXOO DUFKLWHFWXUDO SODQ LI
+RFFXSDQF\6SHFLDO(TXLSPHQW3ODQVPD\EHQHFHVVDU\35353535
6WRUDJHRUPHUFKDQGL]LQJDUHDVLQH[FHVVRIVTIWZKHUHLWHPVDUHORFDWHGKLJKHUWKDQ¶¶IRUKLJKKD]DUG
FRPPRGLWLHVSODVWLFUXEEHUIRDPHWF"+LJKSLOHG6WRUDJH3ODQ35
&RRNLQJXQGHUD7\SH,FRPPHUFLDOKRRGLQVWDOODWLRQRUPRGLILFDWLRQRIDILUHH[WLQJXLVKLQJV\VWHPORFDWHGLQD
FRPPHUFLDOFRRNLQJKRRG"+RRG 'XFW([WLQJXLVKLQJ6\VWHPQRWMXVWWKHKRRGPHFKDQLFDOSODQ35
,QLWLDOHDFKRIWKHIROORZLQJWZRLWHPVLQGLFDWLQJWKDW\RXKDYHUHDGDQGXQGHUVWDQGWKHVWDWHPHQW
6SULQNOHUV$ODUPV &RQVXOW %XLOGLQJ)LUH &RGHV DQG RUGLQDQFHV WR GHWHUPLQH VSULQNOHUDODUP UHTXLUHPHQWV LI D V\VWHP LV
UHTXLUHGSODQVVKDOOEHVXEPLWWHGIRU2&)$UHYLHZ([LVWLQJEXLOGLQJVXQGHUJRLQJUHPRGHOPXVWEHHYDOXDWHGE\DOLFHQVHG
/ŶŝƚŝĂůƐFRQWUDFWRUWRGHWHUPLQHLIPRGLILFDWLRQLVQHHGHGLIVRFRQWUDFWRUVKDOOVXEPLWSODQVSULRUWRPDNLQJPRGLILFDWLRQV
)LUH+D]DUG6HYHULW\=RQH&RQVXOWPDSVDYDLODEOHDWEXLOGLQJGHSDUWPHQWRURQ2&)$ZHEVLWHWRGHWHUPLQHLI\RXUVLWHLVORFDWHG
LQD)+6=%XLOGLQJVLQD)+6=PD\EHVXEMHFWWRVSHFLDOFRQVWUXFWLRQUHTXLUHPHQWVGHWDLOHGLQ&%&&KDSWHU$RU&5&5²
/ŶŝƚŝĂůƐWKHEXLOGLQJGHSDUWPHQWZLOOGHWHUPLQHVSHFLILFUHTXLUHPHQWV
,FHUWLI\XQGHUSHQDOW\RISHUMXU\XQGHUWKHODZVRIWKH6WDWHRI&DOLIRUQLDWKDWWKHDERYHLVWUXH
3ULQW1DPH6LJQDWXUH
3KRQH1XPEHU;'DWHͬ
%XLOGLQJ'HSDUWPHQW,I\RXKDYHYHULILHGWKDWDOORIWKHTXHVWLRQVKDYHEHHQDQVZHUHGDFFXUDWHO\DV³12´DQGWKHSURMHFWGRHVQRWRWKHUZLVHUHTXLUH2&)$
UHYLHZRIVSULQNOHURUDODUPSODQV
WKHQ\RXPD\DFFHSWWKLVVLJQHGIRUPDVDZULWWHQUHOHDVHWKDW2&)$UHYLHZLVQRWUHTXLUHG6KRXOG\RXVWLOOUHTXLUHWKDWWKH
DSSOLFDQWKDYHSODQVDSSURYHGE\2&)$SOHDVHLQLWLDOKHUH RUDWWDFKDQ2&)$UHIHUUDOIRUPDQGKDYHWKHDSSOLFDQWVXEPLWWKHIRUPDORQJZLWKWKH
DSSURSULDWHSODQVDQGIHHVIRU2&)$UHYLHZϭϬͲϬϴͲϭϰ
KD
6 Hutton Centre Dr, Santa Ana, CA, 92707
✔
INSTALL 8 ELECTRIC VEHICLE CHARGING STATIONS.
✔
✔
✔
✔
✔
✔
✔
✔
✔
CASSANDRA GDOVIN
408 516-3310 10 04 2024
Santa Ana
CG
CG
6 E Hutton Center Dr
#A12/9/2024
O R A N G E C O U N T Y F I R E A U T H O R I T Y
Plan Referral Form
Required for OCFA to review plans upon the request of the Building Department when
the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”.
City / County Official Requesting Review:
City / County Reference #: Date: __________________________________
City / County: _____________________________________ E-Mail: __________________________________
Contact Name: _____________________________________ Phone #: _________________________________
Title: _____________________________________
** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. **
Reason(s) for Review:
Please describe why OCFA Plan Review is or may be required by the City/County :
OCFA COMMENTS:
No further action required on this specific plan type, based
on information provided on: ____/______/______.
Project to be taken in for OCFA Review.
Other:
Name: _________________________________________
Contact #: ______________________________________ Date: _________________________________
Updated: 06/02/2020 rs
6 E Hutton Center Dr
#A12/9/2024
6 E Hutton Center Dr
#A12/9/2024
CONTRACTOR
SHEET DESCRIPTION:
COVER PAGE
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
WESTSIDE CONTRACTORS - NEW EV CHARGING SYSTEM
6 HUTTON CENTRE DRIVE, UNIT A, SANTA ANA, CA 92707
Know what's below.
CALL before you dig.
CALL AT LEAST TWO WORKING
DAYS BEFORE YOU DIG
USA
Nor t h
DIG ALERT
CONTRACTOR SHALL VERIFY ALL PLANS & EXISTING LOCATIONS,
CONDITIONS ON THE JOB SITE & SHALL IMMEDIATELY NOTIFY THE
ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR WORK.
SATELLITE VIEW:
VICINITY VIEW:
SYSTEM INFORMATION
MANUFACTURER EVO CHARGE
PRODUCT EVSE, iEVSE, iEVS PLUS
CONNECTOR SAE J1772
LEVEL AC LEVEL 2
MOUNTING WALL OR PEDESTAL
MAX OUTPUT 32A;7.68KW MAX OUTPUT
SCOPE OF WORK:
INSTALL AND ELECTRICALLY CONNECT EVSE
INFRASTRUCTURE AS SHOWN. CONTRACTOR
TO PROVIDE AND INSTALL THE WIRING
DEVICES INCLUDING ALL REQUIRED
ASSOCIATED ITEMS FOR A COMPLETE AND
OPERATIONAL SYSTEM INCLUDING THE
REQUIRED TESTING SPEED IN THE
ELECTRICAL SPEC PACKAGE. CONTRACTOR
SHALL ALSO PROVIDE THE REQUIRED SAW
CUTTING, TRENCHING, BACKFILLING AND
FINISHING OF THE AFFECTED LOT SURFACE
AND RESTORE TO ORIGINAL CONDITION.
PROVIDE AND INSTALL ALL ITEMS SHOWN ON
THE DRAWINGS AND AS SPECIFIED UNLESS
OTHERWISE NOTED AS NOT IN CONTRACT OR
EXISTING TO REMAIN.
TOTAL NUMBER OF EV CHARGERS: 8
UTILITY:
MS-EV RATING:
MS EXISTING OR NEW:
SANTA ANA
METER NO:
BUILDING TYPE:
CHARGING KW CAPACITY: 6.656KW
SYSTEM VOLTAGE: 208
SINGLE OR THREE PHASE: THREE PHASE
EVSE LOCATION: PARKING GARAGE
PROJECT INFORMATION:
APPLICABLE CODES:
2020 NATIONAL ELECTRICAL CODE
2022 BUILDING ENERGY EFFICIENCY STANDARDS
2022 CALIFORNIA BUILDING CODE (11B-228.3.1)
2022 CALIFORNIA ELECTRICAL CODE
GENERAL CONSTRUCTION NOTES:
a. THE JOB SHALL BE MAINTAINED IN A CLEAN, ORDERLY CONDITION FREE OF DEBRIS
AND LITTER SHALL NOT BE UNREASONABLY ENCUMBERED WITH ANY MATERIALS OR
EQUIPMENT AND SHALL BE CLEANED AT THE END OF EACH WORKING DAY.
b. CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. THE
OWNER'S REPRESENTATIVE SHALL BE NOTIFIED OF ANY DISCREPANCIES OF
INCONSISTENCIES.
c. IT SHALL BE CONTRACTORS RESPONSIBILITY TO DESIGN AND PROVIDE ACCURATE
SHORING AND BACKING REQUIRED FOR THE PROTECTION OF LIFE AND PROPERTY
DURING INSTALLATION.
d. ELECTRICAL EQUIPMENT AND APPARATUS INCLUDING BUT NOT LIMITED TO,
SWITCHBOARDS, MOTORS AND CONTROL CENTERS, PANEL BOARDS AND
TRANSFORMERS MUST BE SEISMIC-CERTIFIED AND ANCHORED ACCORDING TO
EQUIPMENT MANUFACTURER'S INSTALLATION INSTRUCTIONS (CEC 110.3 (B), CBC
1613.1, AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) 7-10, CHAPTER 13 SEISMIC
DESIGN REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
e. DUST SHALL BE CONTROLLED AT ALL THE TIMES. WASTE WATER GENERATED DURING
CONSTRUCTION SHALL NOT BE DISCHARGED INTO THE STORM DRAIN SYSTEM. THIS
INCLUDES WASTE FROM PAINTING, SAW CUTTING, CONCRETE WORK, ETC. THE
CONTRACTOR SHALL MAKE ARRANGEMENTS TO ELIMINATE DISCHARGES INTO THE
STORM DRAIN SYSTEM AND, IF NECESSARY, PROVIDE AN AREA FOR ON-SITE WASHING
ACTIVITIES DURING CONSTRUCTION. MATERIALS THAT COULD CONTAMINATE STORM
RUNOFF SHALL BE STORED IN AREAS THAT ARE DESIGNED TO PREVENT EXPOSURE TO
RAINFALL AND NOT ALLOW STORM WATER TO RUN ON TO THE AREA
f. CONSTRUCTION MATERIAL SHALL BE SPECIFIED AND REQUIRED BY THE LATEST
EDITION OF THE BUILDING CODE CURRENTLY ADOPTED BY THE AHJ INCLUDING
ANY/ALL LOCALLY ENFORCED CODES AND AUTHORITIES.ALL MATERIALS AND
EQUIPMENT SHALL BE INSTALLED, APPLIED AND CONNECTED AS DIRECTED BY THE
MANUFACTURERS LATEST WRITTEN SPECIFICATIONS EXPECT WHERE OTHERWISE
NOTED. MATERIALS NOTED ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER THESE
SPECIFICATIONS.
SITE
SITE
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-01
THE PROJECT IS NOT IN THE FEMA DESIGNATED FLOOD ZONE (ZONE A OR E)
02.05.2025
DOTSON
VG
COMMERCIAL OFFICE BUILDING
SCE 259000-72808
EV1: EXISTING | EV2: NEW
(E) EV1: 200A | (N) EV2: 100A
VAHE GULAGIAN
02/10/2025
Revision to 101121211 & 20184271 (issued on
12/03/2025)
Rev 1 #'s 101123394 & 20185654
APPROVALS:
PLNG - C. Santana
BLDG - CSG
PUBLIC WORKS - Y. Soto
ELECT - CSG
CONTRACTOR
SHEET DESCRIPTION:
SITE PLAN
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, SANTA ANA, CA 92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SITE PLAN:
NOTE: THE HIGH FORWARD REACH SHALL
BE 48 INCHES (1219.2 MM) MAXIMUM AND
THE LOW FORWARD REACH SHALL BE 15
INCHES (381 MM) MINIMUM ABOVE THE
FINISH FLOOR OR GROUND. THE
CONTRACTOR NEED TO PROVIDE DURING
THE INSTALLATION
REACH RANGES:
EV-02
SCALE: 1/32" = 1'-0"
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
02.05.2025
DOTSON
VG
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
LEVEL 01 FLOOR PLAN
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
ENLARGED PLAN:
NOTE: THE HIGH FORWARD REACH SHALL
BE 48 INCHES (1219.2 MM) MAXIMUM AND
THE LOW FORWARD REACH SHALL BE 15
INCHES (381 MM) MINIMUM ABOVE THE
FINISH FLOOR OR GROUND. THE
CONTRACTOR NEED TO PROVIDE DURING
THE INSTALLATION
REACH RANGES:
SC 0"EV1 - EV4 4 CHARGERS
10'-3"
EV-03
02.05.2025
DOTSON
VG
SCALE: 1" = 10'-0"
STAIR
RES.
STAIR
R
C
C
C
C
C
C
C
C
C C C C C C C C C C C C C C C
NO
PARK M M
OFFICEELEC.
R
R
R
C
C
C
C
C
C
23'-0"
8'
-
0
"
17'-0"
19'-0"
9'
-
0
"
8'-0"
17
'
-
0
"
23
'
-
0
"
EV EV EV EV EV EV EV
EV
C
H
A
R
G
I
N
G
ON
L
Y
EV
C
H
A
R
G
I
N
G
ON
L
Y
NO
P
A
R
K
I
N
G
RES.
RES.
RES.
R
R
R
R
R
RES.
RES.
RES.
RES.
RES.
RES.
C
C
C
C
C
STORAGE
RES.
(E) CHARGEPOINT DUAL
PORT CHARGERS
ACCESSIBLE PATH
OF TRAVEL TO
FRONT ENTRANCES
AS PER 11B-812.5
VAHE GULAGIAN
02/10/2025
NOTE: THE WALL MOUNTED UNITS ARE POSITIVELY ATTACHED TO
THE STRUCTURE AS REQUIRED BY ASCE 7-16 13.1.4
NOTE: WALL COLLARS ARE USED AS PHYSICAL BARRIERS
FOR PROTECTING WALL MOUNTED CHARGER'S AGAINST
ACCIDENTAL DAMAGE.
EV CHARGING ONLY MARKING
ISA MARKING - ACCESSIBLE
SPACE TO BE STRIPED
SINGLE CHARGIE EV STATION -
WALL MOUNTED WITH COLLAR
PROTECTION
SINGLE CHARGIE EV STATION -
COLUMN MOUNTED WITH
BOLLARD PROTECTION
EXISISTING CHARGEPOINT EV
STATION - DUAL PORT
(E) BIKE ROOM AT GROUND LEVEL
(E) 600A MAIN SERVICE PANEL 120/208V, 3PH, 4W
(E) PANEL "EV" 200A, 120/208V, 3PH, 4W
(N) EVOCHARGE LEVEL 2 CHARGER,
WALL MOUNTED WITH COLLAR
(N) EVOCHARGE LEVEL 2 CHARGER,
COLUMN MOUNTED WITH BOLLARD
9'
-
0
"
9'
-
0
"
RE
S
.
EV CHARGING
ONLY
EV CHARGING
ONLYNO PARKING
SHEET NOTES:
1 ATTACH LABEL 01, 02, AND 03 TO
THE FRONT OF (E)PANEL "EV"
2 ATTACH LABEL 03 ADJACENT TO
BREAKER ASSOCIATED WITH (E)PANEL
"EV"
DETAILED VIEW 1.
MARKINGS STATING "EV CHARGING ONLY" IN LETTERS
12 INCHES HIGH. CENTERED IN THE STALL, WITH TEXT
ON THE SPACE'S EDGE AS PER CBC 11B-812.9
INTERNATIONAL SYMBOL OF ACCESSIBILITY - 36" X 36"
"NO PARKING" PAINTED WITHIN THE ACCESS AISLE IN
WHITE LETTERS, 12 INCHES HIGH. VISIBLE FROM THE
ADJACENT VEHICULAR WAY
ACCESS AISLE MARKED IN BLUE PAINTED BORDERLINE
AROUND THEIR PERIMETER. HATCHING 36" ON CENTER
IN BLUE.
VAN ACCESSIBLE SPACE = 9'-0" WITH AN 8'-0" WIDE
ACCESS AISLE AS PER CBC 1109A.8.6.
SPACE MEASUREMENTS ARE TO BE MEASURED FROM
THE MIDPOINT OF THE LINES. ALL LINES ARE TO BE
STRIPED WITH A MINIMUM THICKNESS OF 4".
STANDARD ACCESSIBLE SPACE = 9'-0"
WITH AN 8'-0" WIDE ACCESS AISLE.
ENTRANCE
EXIT
EXIT
9'-0"
18'-0"
18'-0"
8'-0"
9'-0"
5'-0"
6 HUTTON CENTRE DR, SANTA ANA, CA, 92707
STANDARD ACCESSIBLE PARKING
SIGNAGE TO BE USED:
VAN ACCESSIBLE PARKING
SIGNAGE TO BE USED:
ACCESSIBILITY SIGNAGE AND SURFACE MARKINGS REQUIRED ON
ACCESSIBLE EV SPACES AS PER CBC 1109A.8.8. THESE SIGNS WILL BE
SECURED TO THE WALL A MINIMUM OF 60 INCHES FROM THE PARKING
SURFACE TO THE BOTTOM EDGE OF THE SIGN.
ACCESSIBLE SPACE SIGNAGE WALL MOUNTED.
CONTRACTOR
SHEET DESCRIPTION:
COVER PAGE
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
WESTSIDE CONTRACTORS - NEW EV CHARGING SYSTEM
6 HUTTON CENTRE DRIVE, UNIT A, SANTA ANA, CA 92707
Know what's below.
CALL before you dig.
CALL AT LEAST TWO WORKING
DAYS BEFORE YOU DIG
USA
Nor t h
DIG ALERT
CONTRACTOR SHALL VERIFY ALL PLANS & EXISTING LOCATIONS,
CONDITIONS ON THE JOB SITE & SHALL IMMEDIATELY NOTIFY THE
ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR WORK.
SATELLITE VIEW:
VICINITY VIEW:
SYSTEM INFORMATION
MANUFACTURER EVO CHARGE
PRODUCT EVSE, iEVSE, iEVS PLUS
CONNECTOR SAE J1772
LEVEL AC LEVEL 2
MOUNTING WALL OR PEDESTAL
MAX OUTPUT 32A;7.68KW MAX OUTPUT
SCOPE OF WORK:
INSTALL AND ELECTRICALLY CONNECT EVSE
INFRASTRUCTURE AS SHOWN. CONTRACTOR
TO PROVIDE AND INSTALL THE WIRING
DEVICES INCLUDING ALL REQUIRED
ASSOCIATED ITEMS FOR A COMPLETE AND
OPERATIONAL SYSTEM INCLUDING THE
REQUIRED TESTING SPEED IN THE
ELECTRICAL SPEC PACKAGE. CONTRACTOR
SHALL ALSO PROVIDE THE REQUIRED SAW
CUTTING, TRENCHING, BACKFILLING AND
FINISHING OF THE AFFECTED LOT SURFACE
AND RESTORE TO ORIGINAL CONDITION.
PROVIDE AND INSTALL ALL ITEMS SHOWN ON
THE DRAWINGS AND AS SPECIFIED UNLESS
OTHERWISE NOTED AS NOT IN CONTRACT OR
EXISTING TO REMAIN.
TOTAL NUMBER OF EV CHARGERS: 8
UTILITY:
MS-EV RATING:
MS EXISTING OR NEW:
SANTA ANA
METER NO:
BUILDING TYPE:
CHARGING KW CAPACITY: 6.656KW
SYSTEM VOLTAGE: 208
SINGLE OR THREE PHASE: THREE PHASE
EVSE LOCATION: PARKING GARAGE
PROJECT INFORMATION:
APPLICABLE CODES:
2020 NATIONAL ELECTRICAL CODE
2022 BUILDING ENERGY EFFICIENCY STANDARDS
2022 CALIFORNIA BUILDING CODE (11B-228.3.1)
2022 CALIFORNIA ELECTRICAL CODE
GENERAL CONSTRUCTION NOTES:
a. THE JOB SHALL BE MAINTAINED IN A CLEAN, ORDERLY CONDITION FREE OF DEBRIS
AND LITTER SHALL NOT BE UNREASONABLY ENCUMBERED WITH ANY MATERIALS OR
EQUIPMENT AND SHALL BE CLEANED AT THE END OF EACH WORKING DAY.
b. CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. THE
OWNER'S REPRESENTATIVE SHALL BE NOTIFIED OF ANY DISCREPANCIES OF
INCONSISTENCIES.
c. IT SHALL BE CONTRACTORS RESPONSIBILITY TO DESIGN AND PROVIDE ACCURATE
SHORING AND BACKING REQUIRED FOR THE PROTECTION OF LIFE AND PROPERTY
DURING INSTALLATION.
d. ELECTRICAL EQUIPMENT AND APPARATUS INCLUDING BUT NOT LIMITED TO,
SWITCHBOARDS, MOTORS AND CONTROL CENTERS, PANEL BOARDS AND
TRANSFORMERS MUST BE SEISMIC-CERTIFIED AND ANCHORED ACCORDING TO
EQUIPMENT MANUFACTURER'S INSTALLATION INSTRUCTIONS (CEC 110.3 (B), CBC
1613.1, AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) 7-10, CHAPTER 13 SEISMIC
DESIGN REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
e. DUST SHALL BE CONTROLLED AT ALL THE TIMES. WASTE WATER GENERATED DURING
CONSTRUCTION SHALL NOT BE DISCHARGED INTO THE STORM DRAIN SYSTEM. THIS
INCLUDES WASTE FROM PAINTING, SAW CUTTING, CONCRETE WORK, ETC. THE
CONTRACTOR SHALL MAKE ARRANGEMENTS TO ELIMINATE DISCHARGES INTO THE
STORM DRAIN SYSTEM AND, IF NECESSARY, PROVIDE AN AREA FOR ON-SITE WASHING
ACTIVITIES DURING CONSTRUCTION. MATERIALS THAT COULD CONTAMINATE STORM
RUNOFF SHALL BE STORED IN AREAS THAT ARE DESIGNED TO PREVENT EXPOSURE TO
RAINFALL AND NOT ALLOW STORM WATER TO RUN ON TO THE AREA
f. CONSTRUCTION MATERIAL SHALL BE SPECIFIED AND REQUIRED BY THE LATEST
EDITION OF THE BUILDING CODE CURRENTLY ADOPTED BY THE AHJ INCLUDING
ANY/ALL LOCALLY ENFORCED CODES AND AUTHORITIES.ALL MATERIALS AND
EQUIPMENT SHALL BE INSTALLED, APPLIED AND CONNECTED AS DIRECTED BY THE
MANUFACTURERS LATEST WRITTEN SPECIFICATIONS EXPECT WHERE OTHERWISE
NOTED. MATERIALS NOTED ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER THESE
SPECIFICATIONS.
SITE
SITE
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-01
THE PROJECT IS NOT IN THE FEMA DESIGNATED FLOOD ZONE (ZONE A OR E)
02.05.2025
DOTSON
VG
COMMERCIAL OFFICE BUILDING
SCE 259000-72808
EV1: EXISTING | EV2: NEW
(E) EV1: 200A | (N) EV2: 100A
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
SITE PLAN
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, SANTA ANA, CA 92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SITE PLAN:
NOTE: THE HIGH FORWARD REACH SHALL
BE 48 INCHES (1219.2 MM) MAXIMUM AND
THE LOW FORWARD REACH SHALL BE 15
INCHES (381 MM) MINIMUM ABOVE THE
FINISH FLOOR OR GROUND. THE
CONTRACTOR NEED TO PROVIDE DURING
THE INSTALLATION
REACH RANGES:
EV-02
SCALE: 1/32" = 1'-0"
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
02.05.2025
DOTSON
VG
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
LEVEL 01 FLOOR PLAN
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
ENLARGED PLAN:
NOTE: THE HIGH FORWARD REACH SHALL
BE 48 INCHES (1219.2 MM) MAXIMUM AND
THE LOW FORWARD REACH SHALL BE 15
INCHES (381 MM) MINIMUM ABOVE THE
FINISH FLOOR OR GROUND. THE
CONTRACTOR NEED TO PROVIDE DURING
THE INSTALLATION
REACH RANGES:
SC 0"EV1 - EV4 4 CHARGERS
10'-3"
EV-03
02.05.2025
DOTSON
VG
SCALE: 1" = 10'-0"
STAIR
RES.
STAIR
R
C
C
C
C
C
C
C
C
C C C C C C C C C C C C C C C
NO
PARK M M
OFFICEELEC.
R
R
R
C
C
C
C
C
C
23'-0"
8'
-
0
"
17'-0"
19'-0"
9'
-
0
"
8'-0"
17
'
-
0
"
23
'
-
0
"
EV EV EV EV EV EV EV
EV
C
H
A
R
G
I
N
G
ON
L
Y
EV
C
H
A
R
G
I
N
G
ON
L
Y
NO
P
A
R
K
I
N
G
RES.
RES.
RES.
R
R
R
R
R
RES.
RES.
RES.
RES.
RES.
RES.
C
C
C
C
C
STORAGE
RES.
(E) CHARGEPOINT DUAL
PORT CHARGERS
ACCESSIBLE PATH
OF TRAVEL TO
FRONT ENTRANCES
AS PER 11B-812.5
VAHE GULAGIAN
02/10/2025
NOTE: THE WALL MOUNTED UNITS ARE POSITIVELY ATTACHED TO
THE STRUCTURE AS REQUIRED BY ASCE 7-16 13.1.4
NOTE: WALL COLLARS ARE USED AS PHYSICAL BARRIERS
FOR PROTECTING WALL MOUNTED CHARGER'S AGAINST
ACCIDENTAL DAMAGE.
EV CHARGING ONLY MARKING
ISA MARKING - ACCESSIBLE
SPACE TO BE STRIPED
SINGLE CHARGIE EV STATION -
WALL MOUNTED WITH COLLAR
PROTECTION
SINGLE CHARGIE EV STATION -
COLUMN MOUNTED WITH
BOLLARD PROTECTION
EXISISTING CHARGEPOINT EV
STATION - DUAL PORT
(E) BIKE ROOM AT GROUND LEVEL
(E) 600A MAIN SERVICE PANEL 120/208V, 3PH, 4W
(E) PANEL "EV" 200A, 120/208V, 3PH, 4W
(N) EVOCHARGE LEVEL 2 CHARGER,
WALL MOUNTED WITH COLLAR
(N) EVOCHARGE LEVEL 2 CHARGER,
COLUMN MOUNTED WITH BOLLARD
9'
-
0
"
9'
-
0
"
RE
S
.
EV CHARGING
ONLY
EV CHARGING
ONLYNO PARKING
SHEET NOTES:
1 ATTACH LABEL 01, 02, AND 03 TO
THE FRONT OF (E)PANEL "EV"
2 ATTACH LABEL 03 ADJACENT TO
BREAKER ASSOCIATED WITH (E)PANEL
"EV"
DETAILED VIEW 1.
MARKINGS STATING "EV CHARGING ONLY" IN LETTERS
12 INCHES HIGH. CENTERED IN THE STALL, WITH TEXT
ON THE SPACE'S EDGE AS PER CBC 11B-812.9
INTERNATIONAL SYMBOL OF ACCESSIBILITY - 36" X 36"
"NO PARKING" PAINTED WITHIN THE ACCESS AISLE IN
WHITE LETTERS, 12 INCHES HIGH. VISIBLE FROM THE
ADJACENT VEHICULAR WAY
ACCESS AISLE MARKED IN BLUE PAINTED BORDERLINE
AROUND THEIR PERIMETER. HATCHING 36" ON CENTER
IN BLUE.
VAN ACCESSIBLE SPACE = 9'-0" WITH AN 8'-0" WIDE
ACCESS AISLE AS PER CBC 1109A.8.6.
SPACE MEASUREMENTS ARE TO BE MEASURED FROM
THE MIDPOINT OF THE LINES. ALL LINES ARE TO BE
STRIPED WITH A MINIMUM THICKNESS OF 4".
STANDARD ACCESSIBLE SPACE = 9'-0"
WITH AN 8'-0" WIDE ACCESS AISLE.
ENTRANCE
EXIT
EXIT
9'-0"
18'-0"
18'-0"
8'-0"
9'-0"
5'-0"
6 HUTTON CENTRE DR, SANTA ANA, CA, 92707
STANDARD ACCESSIBLE PARKING
SIGNAGE TO BE USED:
VAN ACCESSIBLE PARKING
SIGNAGE TO BE USED:
ACCESSIBILITY SIGNAGE AND SURFACE MARKINGS REQUIRED ON
ACCESSIBLE EV SPACES AS PER CBC 1109A.8.8. THESE SIGNS WILL BE
SECURED TO THE WALL A MINIMUM OF 60 INCHES FROM THE PARKING
SURFACE TO THE BOTTOM EDGE OF THE SIGN.
ACCESSIBLE SPACE SIGNAGE WALL MOUNTED.
CONTRACTOR
SHEET DESCRIPTION:
PANEL SCHEDULE
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
D
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-04
02.05.2025
DOTSON
VG
NECT
210.0(B): DISCONNECTING MEANS ON MULTI-BRANCH CIRCUITS: EACH
MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT
WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT
THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES.
X LOAD OF LOAD
ENT.
TOTAL FEEDER AMPS: 23.71A
T SYSTEM
5.41-625.43
NOTE: CHARGER SETTING WILL BE SET AT 32A PER 40A
BRANCH CIRCUIT.
NOTE: WALL COLLARS ARE USED AS PHYSICAL BARRIERS
FOR PROTECTING WALL MOUNTED CHARGER'S AGAINST
ACCIDENTAL DAMAGE.
NOTE: THE WALL MOUNTED UNITS ARE POSITIVELY ATTACHED TO
THE STRUCTURE AS REQUIRED BY ASCE 7-16 13.1.4
EV CHARGING LOAD PART OF AUTOMATIC LOAD MANAGEMENT SYSTEM.
LOAD MANAGEMENT IS CERTIFIED BY CHARGIE ENERGY MANAGEMENT
EQUIPMENT.
UPSTREAM TRANSFORMER LOAD CALCULATION:
EV1+EV2 HIGHEST PHASE COMBINED LOAD: 19.344 kVA
ADJUSTED TOTAL CONNECTED LOAD: 58.032 kVA
LOAD ON TRANSFORMER (100% LOADED) = 58.032 kVA < 75 kVA CAPACITY
UPSTREAM 100A DISCONNECT LOAD CALC:
ADJUSTED DEMAND TOTAL LOAD = 58.032*1.25 = 72.54 kVA
(E) 100A MAIN DISCONNECT CAPACITY: 100A*sqrt(3)*208V = 83.14 kVA
LOAD: 72.54 kVA < 83.14 kVA CAPACITY
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
SINGLE LINE DIAGRAM
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SINGLE LINE DIAGRAM:
NOTE:
EQUIPMENT WITH SERIES RATING APPLIED WILL BE FIELD
MARKED "CAUTION SERIES RATED SYSTEM 225 AMPS
AVAILABLE. IDENTIFIED REPLACEMENT COMPONENT
REQUIRED." (PER SECTION 110.22)
NOTE:
SERIES RATED SYSTEMS ARE PERMITTED TO BE
SELECTED UNDER ENGINEERING SUPERVISION FOR
EXISTING INSTALLATIONS IN ACCORDANCE WITH NEC
240.86(A)
VOLTAGE DROP: COPPER WIRE
3% OF 240 = 7.2 VOLTS
3% OF 208 = 6.24 VOLTS
#8 AWG @240V =7.2V
@150FT UPSIZE BRANCH CIRCUIT
#8 AWG @208V =6.24V
@125FT UPSIZE BRANCH CIRCUIT
#6 AWG @240V =7.2V
@230FT UPSIZE BRANCH CIRCUIT
#6 AWG @208V =6.24V
@200FT UPSIZE BRANCH CIRCUIT
#4 AWG @240V =7.2V
@350FT UPSIZE BRANCH CIRCUIT
#4 AWG @208V =6.24V
@320FT UPSIZE BRANCH CIRCUIT
LOAD CONTROLLER NOTE:
LOAD CONTROLLER CONTROLS THE TIME OF USAGE FOR SCE
AND IT ALSO ACTS AS THE COMMUNICATION SYSTEM BETWEEN
ALL THE CHARGERS.
IT ALSO HAS THE ONLINE PORTAL FOR THE PAYMENT SYSTEM
FOR THE CLINETS TO MAKE SURE THAT THE USER IS BEING
CHARGED FOR THE ELECTRICITY.
CONDUIT CONTENTS: (2X) HOTS, (1X) E.G.C. (#8 AWG)
(PER UNIT)
CONDUIT TYPES: 1" EMT TO J-BOX/1/2" EMT TO EACH UNIT.
EV CHARGER:40A,NEMA 4, UL LISTED
(N)RACEWAY WITH 2 CURRENT-CARRYING
CONDUCTORS(PER RUN)
40A #8 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
40A #6 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
CONDUCTOR AMPERAGE RATING:
55* 0.91*0.80= 40.1A @ 240 MAX.
FEEDER- (MAX. OPERATING CURRENT)
32A* 1.25= 40.0A @ 240V PEAK
ELECTRICAL DETAILS
NO OF CHARGING UNITS 8
NO OF CHARGING PORTS 8
PHASE THREE PHASE
EXISTING METER
LADWP LOAD CALCULATIONS
TOTAL EXISTING LOAD KW
EV DEMAND LOAD 8.545KW
UNIT METERS @24%293.532KW
TOTAL LOAD KW
NEW EV BREAKER
REQUIRED BREAKER
BUILDING USAGE
TOTAL EXISTING LOAD KW
CHARGERS CONNECTED TO SYSTEM
DEMAND LOADS 8.545KW
CHARGER LOAD FOR BRANCH CIRCUTS
TOTAL EV CHARGER DEMAND AMP 23.71A
GATEWAY
#2 10AWG CONDUCTORS & #1 10AWG
GROUND IN 3/4" EMT CONDUIT
(TO ETHERNET)
IR COMMUNICATION
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
SINGLE LINE DIAGRAM:
NOTE:
EQUIPMENT WITH SERIES RATING APPLIED WILL BE FIELD
MARKED "CAUTION SERIES RATED SYSTEM 200 AMPS
AVAILABLE. IDENTIFIED REPLACEMENT COMPONENT
REQUIRED." (PER SECTION 110.22)
NOTE:
SERIES RATED SYSTEMS ARE PERMITTED TO BE
SELECTED UNDER ENGINEERING SUPERVISION FOR
EXISTING INSTALLATIONS IN ACCORDANCE WITH NEC
240.86(A)
VOLTAGE DROP: COPPER WIRE
3% OF 240 = 7.2 VOLTS
3% OF 208 = 6.24 VOLTS
#8 AWG @240V =7.2V
@150FT UPSIZE BRANCH CIRCUIT
#8 AWG @208V =6.24V
@125FT UPSIZE BRANCH CIRCUIT
#6 AWG @240V =7.2V
@230FT UPSIZE BRANCH CIRCUIT
#6 AWG @208V =6.24V
@200FT UPSIZE BRANCH CIRCUIT
#4 AWG @240V =7.2V
@350FT UPSIZE BRANCH CIRCUIT
#4 AWG @208V =6.24V
@320FT UPSIZE BRANCH CIRCUIT
LOAD CONTROLLER NOTE:
LOAD CONTROLLER CONTROLS THE TIME OF USAGE FOR SMUD
AND IT ALSO ACTS AS THE COMMUNICATION SYSTEM BETWEEN
ALL THE CHARGERS.
IT ALSO HAS THE ONLINE PORTAL FOR THE PAYMENT SYSTEM
FOR THE CLINETS TO MAKE SURE THAT THE USER IS BEING
CHARGED FOR THE ELECTRICITY.
CONDUIT CONTENTS: (2X) HOTS, (1X) E.G.C. (#8 AWG)
(PER UNIT)
CONDUIT TYPES: 1" EMT TO J-BOX/1/2" EMT TO EACH UNIT.
EV CHARGER:40A,NEMA 4, UL LISTED
(N)RACEWAY WITH 2 CURRENT-CARRYING
CONDUCTORS(PER RUN)
40A #8 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
40A #6 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
CONDUCTOR AMPERAGE RATING:
55* 0.91*0.80= 40.1A @ 240 MAX.
FEEDER- (MAX. OPERATING CURRENT)
32A* 1.25= 40.0A @ 240V PEAK
LOAD CALCULATION:
EXISTING HIGH DEMAND (108KW) X 1.25 = 135.0 KW
NEW ELEVATOR (15 HP)= 16.8 KW
NEW PANEL "HB" CONNECTED LOAD = 46.4 KW
+25% OF LARGEST MOTOR = 4.2 KW
EV PANEL = 92.88 KW
TOTAL = 295.28 KW
NOTE: EV CHARGER'S ARE CONNECTED TO EV PANEL
(SEE LOAD CALC IN PAGE EV-05)15
EV-06
02.05.2025
DOTSON
VG
40A
VAHE GULAGIAN
02/10/2025
(N) 2"C - 4#4/0 + 1#4G.
<10 Ft. Feeders
(N)2"C - 4#4/0 + 1#4G.
<10 Ft. Feeders
CONTRACTOR
SHEET DESCRIPTION:
NOTES
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SINGLE LINE NOTES:
1. ALL CONDUCTORS SHALL BE COPPER AS FOLLOWS:
#12AWG AND SMALLER - SOLID, TW
#10AWG AND LARGER - STRANDED, THHN OR THWN
ALL CONDUCTORS SIZES ARE BASED ON 75°C TEMPERATURE
RATINS (NEC.2020 TABLE 310.16)
2. ALL NEW CIRCUIT BREAKERS, FUSIBLE SWITCHES IN MAIN
SWITCHBOARD OR PANEL BOARDS SHALL BE SERIES RATED TO
MATCH EXISTING AIC RATING OR APPROVED EQUAL OR 65kAIC,
UNLESS NOTED OTHERWISE.
3. MOTOR CIRCUIT PROTECTORS SHALL NOT BE A PART OF SERIES
COMBINATION INTERRUPTING RATINGS.
4. SERIES COMBINATION AIC RATINGS SHALL NOT BE USED WHEN
THE SECONDARY EQUIPMENT IN THE SERIES IS SUBJECT TO A
TOTAL CONNECTED FULL LOAD MOTOR CURRENT OF MORE THAN
1% OF ITS AIC RATINGS.
5. EQUIPMENT ENCLOSURES SHALL BE CLEARLY MARKED
"CAUTION-SERIES RATED SYSTEM - 65KAMPS AVAILABLE,
IDENTIFIED REPLACEMENT COMPONENTS REQUIRED". IN
COMPLIANCE WITH 2022 CEC (NEC 2020) SECTION 110-22 END
USE EQUIPMENT SHALL ALSO BE MARKED WITH THE HIGHER
SERIES COMBINATION INTERRUPTING RATINGS AS PER 2022 CEC
SECTION 240-89(C). NO EXCEPTION.
6. FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE
HOLDERS.
7. ELECTRICAL EQUIPMENT SHALL BE LISTED BY THE CITY, WHERE
THE PROJECT IS LOCATED, RECOGNIZED ELECTRICAL TESTING
LABORATORY OR APPROVED BY THE DEPARTMENT.
8. NO PIPING, NO DUCTS OF EQUIPMENT FOREIGN TO ELECTRICAL
EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE
DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT.
9. ALL ITEMS SHOWN ARE EXISTING U.O.N.
10. ALL FEEDER LENGTHS SHOWN ARE FOR VOLTAGE DROP AND
SHORT CIRCUIT CALCULATIONS ONLY.
11. MAXIMUM AVAILABLE FAULT CURRENT AT MAIN SERVICE
ENTRANCE IS ASSUMED TO BE 42KAIC U.O.N.
12. IN MAIN SWITCHBOARD BUS BRACING AND A.I.C. RATINGS OF
ALL DEVICES SHALL BE 42,000 MIN. U.O.N.
13. CIRCUIT BREAKERS IN ALL MAIN SWITCHBOARDS AND PANELS
SHALL BE FROM THE SAME MANUFACTURER AND ENTIRE SYSTEM.
14. ALL REMAINING SPACES IN MAIN SWITCHBOARDS AND PANELS
SHALL BE BUSSED.
15. ALL SUBPANELS SHALL BE RATED 42,000 AIC U.O.N.
16. SUBMIT SHOP DRAWINGS OF MAIN SWITCHBOARD TO SERVING
UTILITY COMPANY AND OBTAIN THERE APPROVAL PRIOR TO
RELEASING SHOP DRAWINGS TO MANUFACTURER. VERIFY TYPE
OF REQUIRED METER SOCKETS (IF NECESSARY).
17. ALL SECTIONS OF MAIN SWITCHBOARD SHALL HAVE THE
HORIZONTAL AND VERTICAL BUSS BARS RATED FOR THE
AMPERE RATING SHOWN ON SINGLE LINE DIAGRAMS.
REDUCTION OF AMPERE RATING OF BUSS BARS THROUGHOUT
THE SECTIONS OF MAIN SWITCHBOARDS IS NOT ACCEPTABLE.
18. NOTIFY SWITCHBOARD PANEL BOARDS MANUFACTURERS OF
FEEDER TERMINATIONS (TOP OR BOTTOM) PRIOR TO
SUBMITTING SHOP DRAWINGS.
19. PROVIDE A METALLIC CARD HOLDER ON INSIDE OF DOOR OF
EACH PANEL BOARD FOR INDEX CARD AND ACCURATE
TYPEWRITTEN PANEL SCHEDULE BE PUT BEHIND HEAVY PLASTIC
COVER INTO EACH PANEL. ROOM NUMBERS SHALL NOT BE THE
ONES ON THE PLANS BUT THE ONES DESIGNATED BY THE
ARCHITECT AND/OR OWNER.
20. PROVIDE TWO (2) KEYS WITH EACH PANEL BOARD. ALL PANELS
BOARDS LOCKS SHALL BE KEYED ALIKE.
21. WHERE TWO OF THREE POLE BREAKERS OCCUR IN LIGHTING
PANELS THE MULTI-POLE BREAKERS SHALL HAVE A COMMON
TRIP "QUICKLAG" TYPE UNITS. SINGLE POLE BREAKERS WITH
TIE-BAR BETWEEN HANDLES WILL NOT BE ACCEPTABLE.
22. PROVIDE BLACK ON WHITE LAMINATED PLASTIC NAMEPLATE
ENGRAVED IN MIN 14" HIGH LETTERS, ATTACHED NAMEPLATES TO
EQUIPMENT, SWITCHBOARD(S), DISTRIBUTION BOARD(S), PANEL
BOARDS AND DISCONNECTS ETC, WITH RIVETS, BOLTS, OR
SHEET METAL SCREWS. CEMENT ATTACHMENTS ARE NOT
ACCEPTABLE.
23. TIME SWITCHES, CONTACTORS, RELAYS, ETCH SHOWN TO BE
FURNISHED WITH PANEL BOARDS SHALL BE LOCATED IN
BARRIERED COMPARTMENTS BEHIND SEPARATE DOORS,
MAINTAIN 2" OF SOLD TRIP BETWEEN DOORS. IF NECESSARY,
INSTALL SWITCHES, CONTACTORS, RELAYS, ETCH IN SEPARATE
WEATHERPROOF CABINETS WITH HINGED LOCKABLE DOORS.
PROVIDE SCREW-ON TYPE NAMEPLATES, FULLY COMPLY WITH
LATEST HANDICAP STANDARDS.
DEMOLITION NOTES:
1. THE DRAWINGS SHOW THE WORK TO BE IN PLACE AT THE
COMPLETION OF INSTALLATION. MAKE NECESSARY ALTERATIONS
TO COORDINATE AND CONNECT THE EXISTING ELECTRICAL WORK
WITH THE NEW SUCH THAT, WHEN THE WORK IS DONE, THE
ENTIRE ELECTRICAL INSTALLATION, EXISTING AND NEW, IS IN
COMPLETE OPERATING CONDITION.
2. UNLESS SPECIFICALLY NOTED ON THE CONTRARY, ALL EXISTING
LIGHTING FIXTURES, SWITCHES, CONTROLS AND OTHER
MATERIALS OR EQUIPMENTS WHICH ARE REPLACED BY NEW AND
ARE NOT INDICATED TO BE REUSED SHALL BE RETURNED TO THE
OWNER OR BE DISPOSED AS DIRECTED BY THE OWNER.
3. EXISTING MATERIAL TO REMAIN UPON COMPLETION IS INDICATED
ON DRAWINGS AS EXISTING, FEEDERS (CONDUIT AND WIRES)
ARE EXISTING TO THEIR RESPECTIVE SOURCE. ALTHOUGH NOT
INDICATED ON THE DRAWINGS. TEMPORARY REMOVAL OR
RE-ROUTE CONDUITS AND REPLACE EXISTING WIRES WITH NEW
DURING CONSTRUCTION WORK MAYBE REQUIRED.
4. PROVIDE AND INSTALL NEW COVER PLATES FOR ALL REMOVED
OUTLETS, SWITCHES, LIGHT FIXTURES, AND OTHER ELECTRICAL
DEVICES WHEN THE OUTLET BOX IS TO REMAIN.
5. REMOVE ALL EXISTING ABANDONED FEEDERS (CONDUITS AND
WIRES) BACK TO PANEL BOARDS. LABEL NEW PANEL DIRECTORY
AS "SPARE".
6. MAINTAIN CONTINUITY OF ALL ELECTRICAL SYSTEMS, EQUIPMENT,
ETC., FED BY ABANDONED OUTLET. THEY SHOULD BE IN
OPERATION AFTER THE WORK IS DONE. MAINTAINING
CONTINUITY SHALL CONSIST OF RE-ROUTING OF CONDUIT AND
WIRING, AS REQUIRED TO SUIT THE EXISTING CONDITIONS.
7. (E) J-BOX DENOTES APPROXIMATE LOCATION OF EXISTING BOXES
IN ACCESSIBLE CEILING SPACE. ALL CONDUIT SHOWN FROM
J-BOX IS NEW UNLESS SHOWN OTHERWISE AS EXISTING.
8. EXISTING LOADS SHOWN ON PANEL SCHEDULES ARE BASED ON
ASSUMPTIONS MADE BY FIELD VISIT, ELECTRICAL BILLS OR
PUBLIC RESOURCES. NOTIFY ENGINEER IMMEDIATELY IF LOADS
EXCEED 16AMPS ON ANY 20A/1P CIRCUIT. NO EXCEPTION.
9. CAREFULLY REVIEW ARCHITECT'S DEMO DRAWINGS FOR
LOCATION OF WALLS BEING REMOVED UNDER THE SCOPE OF THIS
WORK AND REMOVE ALL FEEDERS (CONDUITS AND WIRES) BACK
TO THE LAST DEVICE LEFT IN SERVICE. DON NOT LEAVE
ABANDONED.
10. CAREFULLY REVIEW ARCHITECT'S DEMO DRAWINGS FOR EXISTING
FLOOR BOXES BEING REMOVED UNDER THIS SCOPE OF WORK.
REMOVE FLOOR BOXES AND FEEDERS (CONDUITS AND WIRES)
BACK TO LAST DEVICE LEFT IN SERVICE. DO NOT LEAVE
ABANDONED.
STRIPING AND MARKINGS:
1. ACCESS AISLES SHALL BE MARKED WITH PAINTED BORDERLINES
AROUND THEIR PERIMETER
2. THE AREA WITHIN THE BORDERLINES SHALL BE MARKED WITH
HATCHED LINES A MINIMUM OF 36 INCHES ON CENTER
3. THE COLOR OF THE BORDERLINES, HATCHED LINES, AND LETTERS
SHALL CONTRAST WITH THAT OF THE SURFACE OF THE ACCESS
AISLE
4. THE COLOR OF ALL STRIPING AND MARKINGS SHALL NOT BE THE
BLUE COLOR USED FOR IDENTIFICATION OF ACCESSIBLE PARKING
SPACES PER 11B-502.3.3
5. THE WORDS "NO PARKING" SHALL BE PAINTED WITHIN EACH
ACCESS AISLE IN LETTERS A MINIMUM OF 12 INCHES IN HEIGHT
AND LOCATED TO BE VISIBLE FROM THE ADJACENT VEHICULAR
WAY
6. THE WORDS "EV CHARGING ONLY" SHALL BE PAINTED AT THE
LOWER END OF EACH EV SPACE IN LETTERS A MINIMUM OF 12
INCHES IN HEIGHT. THE CENTERLINE OF THE TEXT SHALL BE 6
INCHES MAXIMUM FROM THE CENTERLINE OF THE VEHICLE SPACE
AND ITS LOWER CORNER AT, OR LOWER SIDE ALIGNED WITH, THE
END OF THE PARKING SPACE. (11B-812.8.9)
GROUNDING:
1. ALL SERVICES SUPPLYING THE BUILDING SHALL HAVE THE SAME
GROUNDING ELECTRODE SYSTEM.
2. REMOVAL OF A GRID INTERACTIVE INVERTER OR OTHER
EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION
BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE
PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED
CONDUCTOR.
3. GROUND BOND CONDUCTOR SHALL NOT BE SPLICED.
4. USE EQUAL OR APPROVED "LAY IN LUG" ILSCO, UL-467 RATED FOR
GROUNDING AND BONDING. HIGH STRENGTH COPPER ALLOY W/
SS SCREW (AS NECESSARY)
CONDUCTORS:
1. ALL CONDUCTORS SHALL BE COPPER UNLESS OTHERWISE NOTED.
2. ALL PROPOSED CONDUCTORS RATED FOR 90°C., HOWEVER
EQUIPMENT RATINGS SHALL BE ASSUMED TO BE 75°C FOR ALL
BUILDING FEEDERS AND THEREFORE TERMINATIONS PRIOR TO
CONNECTION. INTERMEDIATE JUNCTION BOX MAY BE REQUIRED
TO CHANGE FROM 90°C TO 75°C WIRING. MATERIAL SHALL BE
COPPER AND 90°C RATED, SUITABLE FOR SUN EXPOSURE AND WET
LOCATIONS. FIELD APPLIED COATINGS ARE NOT ACCEPTABLE.
3. ALL WIRE INSULATION TYPE SHALL BE EV WIRE FOR AC EV
CIRCUIT RUNS.
4. EACH EV MODULE HAS A POSITIVE AND NEGATIVE EV WIRE
"SUNLIGHT RESISTANT" QUICK CONNECT PLUG IN LEAD. VERIFY
COMPATIBLE EXTENSION WIRE PRIOR TO INSTALLATION.
5. ALL INTER-MODULE SERIES CONNECTIONS TO BE TIE STRAPPED
(W/ BLACK UV RESISTANT TIE
625.41 OVERCURRENT PROTECTION: OVERCURRENT PROTECTION
FOR FEEDERS AND BRANCH CIRCUITS SUPPLYING EQUIPMENT SHALL
BE SIZED FOR CONTINUOUS DUTY AND SHALL HAVE A RATING OF NOT
LESS THAN 125 PERCENT OF THE MAXIMUM LOAD OF THE EQUIPMENT.
WHERE NONCONTINUOUS LOADS ARE SUPPLIED FROM THE SAME
FEEDER, THE OVER-CURRENT DEVICE SHALL HAVE A RATING OF NOT
LESS THAN THE SUM OF THE NON-CONTINUOUS LOADS
PLUS 125 PERCENT OF THE CONTINUOUS LOADS.
625.42 RATING: THE EQUIPMENT SHALL HAVE SUFFICIENT RATING
TO SUPPLY THE LOAD SERVED. ELECTRIC VEHICLE CHARGING LOADS
SHALL BE CONSIDERED TO BE CONTINUOUS LOADS FOR THE
PURPOSES OF THIS ARTICLE.
WHERE AN AUTOMATIC LOAD MANAGEMENT SYSTEM IS USED, THE
MAXIMUM EQUIPMENT LOAD ON A SERVICE AND FEEDER SHALL BE THE
MAXIMUM LOAD PERMITTED BY THE AUTOMATIC LOAD MANAGEMENT
SYSTEM.
625.43 DISCONNECTING: MEANS FOR EQUIPMENT RATED MORE
THAN 60 AMPERES OR MORE THAN 150 VOLTS TO GROUND, THE
DISCONNECTING MEANS SHALL BE PROVIDED
AND INSTALLED IN A READILY ACCESSIBLE LOCATION. THE
DISCONNECTING MEANS SHALL BE LOCKABLE OPEN IN ACCORDANCE
WITH 110.25.
WIRING METHODS:
1. FOR UNDERGROUND AND EXPOSED UP TO +5'-0" OR DAMP
LOCATION, THE CONDUIT SHALL BE RIGID STEEL GALVANIZED
IMC. NO RUNNING THREADS ARE PERMITTED.
2. GALVANIZED EMT SHALL BE USED IN DRY CONCEALED
LOCATIONS AN EXPOSED ABOVE +5-0". EMT CONNECTORS
SHALL BE WATERTIGHT COMPRESSION TYPE.
3. GALVANIZED FLEXIBLE CONDUIT SHALL BE USED ONLY FOR
MOTOR AND FIXTURE CONNECTIONS IN LENGTHS NOT TO
EXCEED 66'
4. CONDUITS PENETRATING THE ROOF SHALL BE FLASHED AND
COUNTER FLASHED.
5. INSTALL FITTINGS, SPECIAL DEVICES AND MATERIAL, WHICH
MAY BE REQUIRED FOR THE PROPER INSTALLATION OF THE
CONDUIT SYSTEM.
NOTE:
110.27(B)PREVENT PHYSICAL DAMAGE:IN
LOCATIONS WHERE ELECTRICAL EQUIPMENT IS
LIKELY TO BE EXPOSED TO PHYSICAL DAMAGE,
ENCLOSURES OR GAURDS SHALL BE SO
ARRANGED AND OF SUCH STRENGTH AS TO
PREVENT SUCH DAMAGE.
DEDICATED ELECTRICAL SPACE: WIDTH AND
DEPTH OF EQUIPMENT EXTENDING FROM THE
FLOOR TO 1.8M (6FT) ABOVE EQUIPMENT OR TO
STRUCTURAL CEILING
NOTE:
NEW SERVICES IS LOCATED OUTDOORS IN THE
PARKING SPACES THAT ARE BELOW THE
RESIDENTIAL
UNITS
ACCESSIBLE ROUTES AND ACCESS AISLES:
1. ACCESS AISLES SHALL BE LEVEL WITH THE EV SPACE SERVED,
AND SLOPES/CROSS -SLOPES SHALL NOT EXCEED 1:48
2. ADA COMPLIANT EV SPACES SHALL BE LOACTED ON AN
ACCESSIBLE ROUTE TO AN ACESSIBLE BUILDING ENTRANCE.
(11B-206.4 & 11B-812.5)
3. EVCS SHALL BE DESIGNED SO ACCESSIBLE ROUTES ARE NOT
OBSTRUCTED BY CABLES OR OTHER ELEMENTS. (11B-812.5.5)
4. PROVIDE CURBS, WHEEL STOPS, BOLLARDS, OR OTHER
BARRIERS TO PREVENT ENCROACHMENT OF VEHICLE OVER THE
REQUIRED CLEAR WIDTH OF ACCESSIBLE ROUTES. (11B-812.5.3)
NOTE:
"ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR
CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY
ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFTY
HEALTH ADMINISTRATION."
IMPORTANT BID NOTES:
1. DUE TO THE SMALL SCALE OF DRAWINGS,
IT IS NOT ALWAYS POSSIBLE TO SHOW
ALL DEVICES WHICH MAYBE REQUIRED.
CONTRACTOR SHALL BE RESPONSIBLE TO
VERIFY ALL EXISTING CONDITIONS
BEFORE SUBMITTING HIS/HER BID. NO
ADDITIONAL COMPENSATION WILL BE
MADE FOR EXTRA DUE TO CONTRACTOR'S
FAILURE TO VISIT THE JOB SITE AND/OR
FAILURE TO DETERMINE ALL EXISTING
CONDITIONS BEFORE SUBMITTING
HIS/HER BID.
2. REFER TO COMPLETE ARCHITECTURAL
AND ELECTRICAL DRAWINGS FOR
ADDITIONAL NOTES, SPECIFICATIONS,
DETAILS, CONTROLS, ETC. REPORT TO
ARCHITECTURE'S CLARIFICATION IN BASE
BID. THIS REQUIREMENT WILL BE
STRICTLY ENFORCED. NO CHANGE
ORDERS WILL BE ALLOWED IF THE
CONTRACTOR FAILS TO PERFORM THIS
SIGNAGE REQUIREMENTS AND NOTES:
1. ACCESSIBLE SIGNAGE IS NOT REQUIRED
WHERE A TOTAL OF FOUR OF FEWER EV
SPACES ARE PROVIDED.
2. FIVE TO TWENTY-FIVE TOTAL EV SPACES
ARE PROVIDED:
A - ONE VAN ACCESSIBLE EV SPACE
SHALL BE IDENTIFIED BY IS A
SIGNAGE
B - ACCESSIBLE SIGNAGE IS NOT
REQUIRED AT THE STANDARD
ACCESSIBLE EV SPACES
3. TWENTY-SIX OR MORE EV SPACES ARE
PROVIDED
4. ALL REQUIRED VAN ACCESSIBLE AND
STANDARD ACCESSIBLE EV SPACES SHALL
BE IDENTIFIED BY ISA SIGNAGE
5. IDENTIFICATION SIGNS SHALL BE
REFLECTORIZED WITH MINIMUM AREA OF
70 SQUARE INCHES. (11B-812.8.7)
6. THE IDENTIFICATION SIGN SHALL BE
VISIBLE FROM THE EV SPACE IT SERVES
7. SIGNS IDENTIFYING VAN ACCESSIBLE EV
SPACES SHALL CONTAIN THE WORDS "VAN
ACCESSIBLE"
8. IDENTIFICATION SIGNS SHALL BE
PERMANENTLY POSTED EITHER
IMMEDIATELY ADJACENT TO THE VEHICLE
SPACE OF WITHIN THE PROJECTED
VEHICLE SPACE WIDTH AT THE FRONT END
OF VEHICLE SPACE. (11B-812.8.7)
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-07
02.05.2025
DOTSON
VG
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
PLACARD
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CAUTION
SERVICE 2SERVICE 1
DEDICATED TO EV ONLY
OTHER LOADS MUST
NOT BE CONNECTED
LABEL 01 LOCATION:
TO BE PLACED IN DEDICATED EV SUB PANEL
& NEXT TO THE EV BREAKER IN THE
DISTRIBUTION PANEL
SIZE: 4" X 2" QTY:1
LABEL 02 LOCATION:
TO BE PLACED IN DEDICATED EV SUB PANEL
& NEXT TO THE EV BREAKER IN THE
DISTRIBUTION PANEL
SIZE: 4" X 2" QTY:1
6 Hutton Centre Drive, Unit A,
Santa Ana, CA 92707
208V 225A 3Ø 4W
WARNING PLACARDS:
PNL EV 1
LABEL 03 LOCATION:
TO BE PLACED ON THE CIRCUITS ON MSP - EV
SIZE: 1'6" X 1" QTY:1
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-08
02.05.2025
DOTSON
VG
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
PANEL SCHEDULE
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
D
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-04
02.05.2025
DOTSON
VG
NECT
210.0(B): DISCONNECTING MEANS ON MULTI-BRANCH CIRCUITS: EACH
MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT
WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT
THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES.
X LOAD OF LOAD
ENT.
TOTAL FEEDER AMPS: 23.71A
T SYSTEM
5.41-625.43
NOTE: CHARGER SETTING WILL BE SET AT 32A PER 40A
BRANCH CIRCUIT.
NOTE: WALL COLLARS ARE USED AS PHYSICAL BARRIERS
FOR PROTECTING WALL MOUNTED CHARGER'S AGAINST
ACCIDENTAL DAMAGE.
NOTE: THE WALL MOUNTED UNITS ARE POSITIVELY ATTACHED TO
THE STRUCTURE AS REQUIRED BY ASCE 7-16 13.1.4
EV CHARGING LOAD PART OF AUTOMATIC LOAD MANAGEMENT SYSTEM.
LOAD MANAGEMENT IS CERTIFIED BY CHARGIE ENERGY MANAGEMENT
EQUIPMENT.
UPSTREAM TRANSFORMER LOAD CALCULATION:
EV1+EV2 HIGHEST PHASE COMBINED LOAD: 19.344 kVA
ADJUSTED TOTAL CONNECTED LOAD: 58.032 kVA
LOAD ON TRANSFORMER (100% LOADED) = 58.032 kVA < 75 kVA CAPACITY
UPSTREAM 100A DISCONNECT LOAD CALC:
ADJUSTED DEMAND TOTAL LOAD = 58.032*1.25 = 72.54 kVA
(E) 100A MAIN DISCONNECT CAPACITY: 100A*sqrt(3)*208V = 83.14 kVA
LOAD: 72.54 kVA < 83.14 kVA CAPACITY
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
SINGLE LINE DIAGRAM
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SINGLE LINE DIAGRAM:
NOTE:
EQUIPMENT WITH SERIES RATING APPLIED WILL BE FIELD
MARKED "CAUTION SERIES RATED SYSTEM 225 AMPS
AVAILABLE. IDENTIFIED REPLACEMENT COMPONENT
REQUIRED." (PER SECTION 110.22)
NOTE:
SERIES RATED SYSTEMS ARE PERMITTED TO BE
SELECTED UNDER ENGINEERING SUPERVISION FOR
EXISTING INSTALLATIONS IN ACCORDANCE WITH NEC
240.86(A)
VOLTAGE DROP: COPPER WIRE
3% OF 240 = 7.2 VOLTS
3% OF 208 = 6.24 VOLTS
#8 AWG @240V =7.2V
@150FT UPSIZE BRANCH CIRCUIT
#8 AWG @208V =6.24V
@125FT UPSIZE BRANCH CIRCUIT
#6 AWG @240V =7.2V
@230FT UPSIZE BRANCH CIRCUIT
#6 AWG @208V =6.24V
@200FT UPSIZE BRANCH CIRCUIT
#4 AWG @240V =7.2V
@350FT UPSIZE BRANCH CIRCUIT
#4 AWG @208V =6.24V
@320FT UPSIZE BRANCH CIRCUIT
LOAD CONTROLLER NOTE:
LOAD CONTROLLER CONTROLS THE TIME OF USAGE FOR SCE
AND IT ALSO ACTS AS THE COMMUNICATION SYSTEM BETWEEN
ALL THE CHARGERS.
IT ALSO HAS THE ONLINE PORTAL FOR THE PAYMENT SYSTEM
FOR THE CLINETS TO MAKE SURE THAT THE USER IS BEING
CHARGED FOR THE ELECTRICITY.
CONDUIT CONTENTS: (2X) HOTS, (1X) E.G.C. (#8 AWG)
(PER UNIT)
CONDUIT TYPES: 1" EMT TO J-BOX/1/2" EMT TO EACH UNIT.
EV CHARGER:40A,NEMA 4, UL LISTED
(N)RACEWAY WITH 2 CURRENT-CARRYING
CONDUCTORS(PER RUN)
40A #8 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
40A #6 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
CONDUCTOR AMPERAGE RATING:
55* 0.91*0.80= 40.1A @ 240 MAX.
FEEDER- (MAX. OPERATING CURRENT)
32A* 1.25= 40.0A @ 240V PEAK
ELECTRICAL DETAILS
NO OF CHARGING UNITS 8
NO OF CHARGING PORTS 8
PHASE THREE PHASE
EXISTING METER
LADWP LOAD CALCULATIONS
TOTAL EXISTING LOAD KW
EV DEMAND LOAD 8.545KW
UNIT METERS @24%293.532KW
TOTAL LOAD KW
NEW EV BREAKER
REQUIRED BREAKER
BUILDING USAGE
TOTAL EXISTING LOAD KW
CHARGERS CONNECTED TO SYSTEM
DEMAND LOADS 8.545KW
CHARGER LOAD FOR BRANCH CIRCUTS
TOTAL EV CHARGER DEMAND AMP 23.71A
GATEWAY
#2 10AWG CONDUCTORS & #1 10AWG
GROUND IN 3/4" EMT CONDUIT
(TO ETHERNET)
IR COMMUNICATION
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE
ELECTRIC VEHICLE
CHARGE STATION
HIGH POWER
POWER
CHARGING
POWER FAULT
CHARGING FAULT
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
SINGLE LINE DIAGRAM:
NOTE:
EQUIPMENT WITH SERIES RATING APPLIED WILL BE FIELD
MARKED "CAUTION SERIES RATED SYSTEM 200 AMPS
AVAILABLE. IDENTIFIED REPLACEMENT COMPONENT
REQUIRED." (PER SECTION 110.22)
NOTE:
SERIES RATED SYSTEMS ARE PERMITTED TO BE
SELECTED UNDER ENGINEERING SUPERVISION FOR
EXISTING INSTALLATIONS IN ACCORDANCE WITH NEC
240.86(A)
VOLTAGE DROP: COPPER WIRE
3% OF 240 = 7.2 VOLTS
3% OF 208 = 6.24 VOLTS
#8 AWG @240V =7.2V
@150FT UPSIZE BRANCH CIRCUIT
#8 AWG @208V =6.24V
@125FT UPSIZE BRANCH CIRCUIT
#6 AWG @240V =7.2V
@230FT UPSIZE BRANCH CIRCUIT
#6 AWG @208V =6.24V
@200FT UPSIZE BRANCH CIRCUIT
#4 AWG @240V =7.2V
@350FT UPSIZE BRANCH CIRCUIT
#4 AWG @208V =6.24V
@320FT UPSIZE BRANCH CIRCUIT
LOAD CONTROLLER NOTE:
LOAD CONTROLLER CONTROLS THE TIME OF USAGE FOR SMUD
AND IT ALSO ACTS AS THE COMMUNICATION SYSTEM BETWEEN
ALL THE CHARGERS.
IT ALSO HAS THE ONLINE PORTAL FOR THE PAYMENT SYSTEM
FOR THE CLINETS TO MAKE SURE THAT THE USER IS BEING
CHARGED FOR THE ELECTRICITY.
CONDUIT CONTENTS: (2X) HOTS, (1X) E.G.C. (#8 AWG)
(PER UNIT)
CONDUIT TYPES: 1" EMT TO J-BOX/1/2" EMT TO EACH UNIT.
EV CHARGER:40A,NEMA 4, UL LISTED
(N)RACEWAY WITH 2 CURRENT-CARRYING
CONDUCTORS(PER RUN)
40A #8 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
40A #6 THWN-2 AWG 90°C * 0.91(102°F)
CORR. FACTOR * 0.80 FILL FACTOR
CONDUCTOR AMPERAGE RATING:
55* 0.91*0.80= 40.1A @ 240 MAX.
FEEDER- (MAX. OPERATING CURRENT)
32A* 1.25= 40.0A @ 240V PEAK
LOAD CALCULATION:
EXISTING HIGH DEMAND (108KW) X 1.25 = 135.0 KW
NEW ELEVATOR (15 HP)= 16.8 KW
NEW PANEL "HB" CONNECTED LOAD = 46.4 KW
+25% OF LARGEST MOTOR = 4.2 KW
EV PANEL = 92.88 KW
TOTAL = 295.28 KW
NOTE: EV CHARGER'S ARE CONNECTED TO EV PANEL
(SEE LOAD CALC IN PAGE EV-05)15
EV-06
02.05.2025
DOTSON
VG
40A
VAHE GULAGIAN
02/10/2025
(N) 2"C - 4#4/0 + 1#4G.
<10 Ft. Feeders
(N)2"C - 4#4/0 + 1#4G.
<10 Ft. Feeders
CONTRACTOR
SHEET DESCRIPTION:
NOTES
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
SINGLE LINE NOTES:
1. ALL CONDUCTORS SHALL BE COPPER AS FOLLOWS:
#12AWG AND SMALLER - SOLID, TW
#10AWG AND LARGER - STRANDED, THHN OR THWN
ALL CONDUCTORS SIZES ARE BASED ON 75°C TEMPERATURE
RATINS (NEC.2020 TABLE 310.16)
2. ALL NEW CIRCUIT BREAKERS, FUSIBLE SWITCHES IN MAIN
SWITCHBOARD OR PANEL BOARDS SHALL BE SERIES RATED TO
MATCH EXISTING AIC RATING OR APPROVED EQUAL OR 65kAIC,
UNLESS NOTED OTHERWISE.
3. MOTOR CIRCUIT PROTECTORS SHALL NOT BE A PART OF SERIES
COMBINATION INTERRUPTING RATINGS.
4. SERIES COMBINATION AIC RATINGS SHALL NOT BE USED WHEN
THE SECONDARY EQUIPMENT IN THE SERIES IS SUBJECT TO A
TOTAL CONNECTED FULL LOAD MOTOR CURRENT OF MORE THAN
1% OF ITS AIC RATINGS.
5. EQUIPMENT ENCLOSURES SHALL BE CLEARLY MARKED
"CAUTION-SERIES RATED SYSTEM - 65KAMPS AVAILABLE,
IDENTIFIED REPLACEMENT COMPONENTS REQUIRED". IN
COMPLIANCE WITH 2022 CEC (NEC 2020) SECTION 110-22 END
USE EQUIPMENT SHALL ALSO BE MARKED WITH THE HIGHER
SERIES COMBINATION INTERRUPTING RATINGS AS PER 2022 CEC
SECTION 240-89(C). NO EXCEPTION.
6. FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE
HOLDERS.
7. ELECTRICAL EQUIPMENT SHALL BE LISTED BY THE CITY, WHERE
THE PROJECT IS LOCATED, RECOGNIZED ELECTRICAL TESTING
LABORATORY OR APPROVED BY THE DEPARTMENT.
8. NO PIPING, NO DUCTS OF EQUIPMENT FOREIGN TO ELECTRICAL
EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE
DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT.
9. ALL ITEMS SHOWN ARE EXISTING U.O.N.
10. ALL FEEDER LENGTHS SHOWN ARE FOR VOLTAGE DROP AND
SHORT CIRCUIT CALCULATIONS ONLY.
11. MAXIMUM AVAILABLE FAULT CURRENT AT MAIN SERVICE
ENTRANCE IS ASSUMED TO BE 42KAIC U.O.N.
12. IN MAIN SWITCHBOARD BUS BRACING AND A.I.C. RATINGS OF
ALL DEVICES SHALL BE 42,000 MIN. U.O.N.
13. CIRCUIT BREAKERS IN ALL MAIN SWITCHBOARDS AND PANELS
SHALL BE FROM THE SAME MANUFACTURER AND ENTIRE SYSTEM.
14. ALL REMAINING SPACES IN MAIN SWITCHBOARDS AND PANELS
SHALL BE BUSSED.
15. ALL SUBPANELS SHALL BE RATED 42,000 AIC U.O.N.
16. SUBMIT SHOP DRAWINGS OF MAIN SWITCHBOARD TO SERVING
UTILITY COMPANY AND OBTAIN THERE APPROVAL PRIOR TO
RELEASING SHOP DRAWINGS TO MANUFACTURER. VERIFY TYPE
OF REQUIRED METER SOCKETS (IF NECESSARY).
17. ALL SECTIONS OF MAIN SWITCHBOARD SHALL HAVE THE
HORIZONTAL AND VERTICAL BUSS BARS RATED FOR THE
AMPERE RATING SHOWN ON SINGLE LINE DIAGRAMS.
REDUCTION OF AMPERE RATING OF BUSS BARS THROUGHOUT
THE SECTIONS OF MAIN SWITCHBOARDS IS NOT ACCEPTABLE.
18. NOTIFY SWITCHBOARD PANEL BOARDS MANUFACTURERS OF
FEEDER TERMINATIONS (TOP OR BOTTOM) PRIOR TO
SUBMITTING SHOP DRAWINGS.
19. PROVIDE A METALLIC CARD HOLDER ON INSIDE OF DOOR OF
EACH PANEL BOARD FOR INDEX CARD AND ACCURATE
TYPEWRITTEN PANEL SCHEDULE BE PUT BEHIND HEAVY PLASTIC
COVER INTO EACH PANEL. ROOM NUMBERS SHALL NOT BE THE
ONES ON THE PLANS BUT THE ONES DESIGNATED BY THE
ARCHITECT AND/OR OWNER.
20. PROVIDE TWO (2) KEYS WITH EACH PANEL BOARD. ALL PANELS
BOARDS LOCKS SHALL BE KEYED ALIKE.
21. WHERE TWO OF THREE POLE BREAKERS OCCUR IN LIGHTING
PANELS THE MULTI-POLE BREAKERS SHALL HAVE A COMMON
TRIP "QUICKLAG" TYPE UNITS. SINGLE POLE BREAKERS WITH
TIE-BAR BETWEEN HANDLES WILL NOT BE ACCEPTABLE.
22. PROVIDE BLACK ON WHITE LAMINATED PLASTIC NAMEPLATE
ENGRAVED IN MIN 14" HIGH LETTERS, ATTACHED NAMEPLATES TO
EQUIPMENT, SWITCHBOARD(S), DISTRIBUTION BOARD(S), PANEL
BOARDS AND DISCONNECTS ETC, WITH RIVETS, BOLTS, OR
SHEET METAL SCREWS. CEMENT ATTACHMENTS ARE NOT
ACCEPTABLE.
23. TIME SWITCHES, CONTACTORS, RELAYS, ETCH SHOWN TO BE
FURNISHED WITH PANEL BOARDS SHALL BE LOCATED IN
BARRIERED COMPARTMENTS BEHIND SEPARATE DOORS,
MAINTAIN 2" OF SOLD TRIP BETWEEN DOORS. IF NECESSARY,
INSTALL SWITCHES, CONTACTORS, RELAYS, ETCH IN SEPARATE
WEATHERPROOF CABINETS WITH HINGED LOCKABLE DOORS.
PROVIDE SCREW-ON TYPE NAMEPLATES, FULLY COMPLY WITH
LATEST HANDICAP STANDARDS.
DEMOLITION NOTES:
1. THE DRAWINGS SHOW THE WORK TO BE IN PLACE AT THE
COMPLETION OF INSTALLATION. MAKE NECESSARY ALTERATIONS
TO COORDINATE AND CONNECT THE EXISTING ELECTRICAL WORK
WITH THE NEW SUCH THAT, WHEN THE WORK IS DONE, THE
ENTIRE ELECTRICAL INSTALLATION, EXISTING AND NEW, IS IN
COMPLETE OPERATING CONDITION.
2. UNLESS SPECIFICALLY NOTED ON THE CONTRARY, ALL EXISTING
LIGHTING FIXTURES, SWITCHES, CONTROLS AND OTHER
MATERIALS OR EQUIPMENTS WHICH ARE REPLACED BY NEW AND
ARE NOT INDICATED TO BE REUSED SHALL BE RETURNED TO THE
OWNER OR BE DISPOSED AS DIRECTED BY THE OWNER.
3. EXISTING MATERIAL TO REMAIN UPON COMPLETION IS INDICATED
ON DRAWINGS AS EXISTING, FEEDERS (CONDUIT AND WIRES)
ARE EXISTING TO THEIR RESPECTIVE SOURCE. ALTHOUGH NOT
INDICATED ON THE DRAWINGS. TEMPORARY REMOVAL OR
RE-ROUTE CONDUITS AND REPLACE EXISTING WIRES WITH NEW
DURING CONSTRUCTION WORK MAYBE REQUIRED.
4. PROVIDE AND INSTALL NEW COVER PLATES FOR ALL REMOVED
OUTLETS, SWITCHES, LIGHT FIXTURES, AND OTHER ELECTRICAL
DEVICES WHEN THE OUTLET BOX IS TO REMAIN.
5. REMOVE ALL EXISTING ABANDONED FEEDERS (CONDUITS AND
WIRES) BACK TO PANEL BOARDS. LABEL NEW PANEL DIRECTORY
AS "SPARE".
6. MAINTAIN CONTINUITY OF ALL ELECTRICAL SYSTEMS, EQUIPMENT,
ETC., FED BY ABANDONED OUTLET. THEY SHOULD BE IN
OPERATION AFTER THE WORK IS DONE. MAINTAINING
CONTINUITY SHALL CONSIST OF RE-ROUTING OF CONDUIT AND
WIRING, AS REQUIRED TO SUIT THE EXISTING CONDITIONS.
7. (E) J-BOX DENOTES APPROXIMATE LOCATION OF EXISTING BOXES
IN ACCESSIBLE CEILING SPACE. ALL CONDUIT SHOWN FROM
J-BOX IS NEW UNLESS SHOWN OTHERWISE AS EXISTING.
8. EXISTING LOADS SHOWN ON PANEL SCHEDULES ARE BASED ON
ASSUMPTIONS MADE BY FIELD VISIT, ELECTRICAL BILLS OR
PUBLIC RESOURCES. NOTIFY ENGINEER IMMEDIATELY IF LOADS
EXCEED 16AMPS ON ANY 20A/1P CIRCUIT. NO EXCEPTION.
9. CAREFULLY REVIEW ARCHITECT'S DEMO DRAWINGS FOR
LOCATION OF WALLS BEING REMOVED UNDER THE SCOPE OF THIS
WORK AND REMOVE ALL FEEDERS (CONDUITS AND WIRES) BACK
TO THE LAST DEVICE LEFT IN SERVICE. DON NOT LEAVE
ABANDONED.
10. CAREFULLY REVIEW ARCHITECT'S DEMO DRAWINGS FOR EXISTING
FLOOR BOXES BEING REMOVED UNDER THIS SCOPE OF WORK.
REMOVE FLOOR BOXES AND FEEDERS (CONDUITS AND WIRES)
BACK TO LAST DEVICE LEFT IN SERVICE. DO NOT LEAVE
ABANDONED.
STRIPING AND MARKINGS:
1. ACCESS AISLES SHALL BE MARKED WITH PAINTED BORDERLINES
AROUND THEIR PERIMETER
2. THE AREA WITHIN THE BORDERLINES SHALL BE MARKED WITH
HATCHED LINES A MINIMUM OF 36 INCHES ON CENTER
3. THE COLOR OF THE BORDERLINES, HATCHED LINES, AND LETTERS
SHALL CONTRAST WITH THAT OF THE SURFACE OF THE ACCESS
AISLE
4. THE COLOR OF ALL STRIPING AND MARKINGS SHALL NOT BE THE
BLUE COLOR USED FOR IDENTIFICATION OF ACCESSIBLE PARKING
SPACES PER 11B-502.3.3
5. THE WORDS "NO PARKING" SHALL BE PAINTED WITHIN EACH
ACCESS AISLE IN LETTERS A MINIMUM OF 12 INCHES IN HEIGHT
AND LOCATED TO BE VISIBLE FROM THE ADJACENT VEHICULAR
WAY
6. THE WORDS "EV CHARGING ONLY" SHALL BE PAINTED AT THE
LOWER END OF EACH EV SPACE IN LETTERS A MINIMUM OF 12
INCHES IN HEIGHT. THE CENTERLINE OF THE TEXT SHALL BE 6
INCHES MAXIMUM FROM THE CENTERLINE OF THE VEHICLE SPACE
AND ITS LOWER CORNER AT, OR LOWER SIDE ALIGNED WITH, THE
END OF THE PARKING SPACE. (11B-812.8.9)
GROUNDING:
1. ALL SERVICES SUPPLYING THE BUILDING SHALL HAVE THE SAME
GROUNDING ELECTRODE SYSTEM.
2. REMOVAL OF A GRID INTERACTIVE INVERTER OR OTHER
EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION
BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE
PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED
CONDUCTOR.
3. GROUND BOND CONDUCTOR SHALL NOT BE SPLICED.
4. USE EQUAL OR APPROVED "LAY IN LUG" ILSCO, UL-467 RATED FOR
GROUNDING AND BONDING. HIGH STRENGTH COPPER ALLOY W/
SS SCREW (AS NECESSARY)
CONDUCTORS:
1. ALL CONDUCTORS SHALL BE COPPER UNLESS OTHERWISE NOTED.
2. ALL PROPOSED CONDUCTORS RATED FOR 90°C., HOWEVER
EQUIPMENT RATINGS SHALL BE ASSUMED TO BE 75°C FOR ALL
BUILDING FEEDERS AND THEREFORE TERMINATIONS PRIOR TO
CONNECTION. INTERMEDIATE JUNCTION BOX MAY BE REQUIRED
TO CHANGE FROM 90°C TO 75°C WIRING. MATERIAL SHALL BE
COPPER AND 90°C RATED, SUITABLE FOR SUN EXPOSURE AND WET
LOCATIONS. FIELD APPLIED COATINGS ARE NOT ACCEPTABLE.
3. ALL WIRE INSULATION TYPE SHALL BE EV WIRE FOR AC EV
CIRCUIT RUNS.
4. EACH EV MODULE HAS A POSITIVE AND NEGATIVE EV WIRE
"SUNLIGHT RESISTANT" QUICK CONNECT PLUG IN LEAD. VERIFY
COMPATIBLE EXTENSION WIRE PRIOR TO INSTALLATION.
5. ALL INTER-MODULE SERIES CONNECTIONS TO BE TIE STRAPPED
(W/ BLACK UV RESISTANT TIE
625.41 OVERCURRENT PROTECTION: OVERCURRENT PROTECTION
FOR FEEDERS AND BRANCH CIRCUITS SUPPLYING EQUIPMENT SHALL
BE SIZED FOR CONTINUOUS DUTY AND SHALL HAVE A RATING OF NOT
LESS THAN 125 PERCENT OF THE MAXIMUM LOAD OF THE EQUIPMENT.
WHERE NONCONTINUOUS LOADS ARE SUPPLIED FROM THE SAME
FEEDER, THE OVER-CURRENT DEVICE SHALL HAVE A RATING OF NOT
LESS THAN THE SUM OF THE NON-CONTINUOUS LOADS
PLUS 125 PERCENT OF THE CONTINUOUS LOADS.
625.42 RATING: THE EQUIPMENT SHALL HAVE SUFFICIENT RATING
TO SUPPLY THE LOAD SERVED. ELECTRIC VEHICLE CHARGING LOADS
SHALL BE CONSIDERED TO BE CONTINUOUS LOADS FOR THE
PURPOSES OF THIS ARTICLE.
WHERE AN AUTOMATIC LOAD MANAGEMENT SYSTEM IS USED, THE
MAXIMUM EQUIPMENT LOAD ON A SERVICE AND FEEDER SHALL BE THE
MAXIMUM LOAD PERMITTED BY THE AUTOMATIC LOAD MANAGEMENT
SYSTEM.
625.43 DISCONNECTING: MEANS FOR EQUIPMENT RATED MORE
THAN 60 AMPERES OR MORE THAN 150 VOLTS TO GROUND, THE
DISCONNECTING MEANS SHALL BE PROVIDED
AND INSTALLED IN A READILY ACCESSIBLE LOCATION. THE
DISCONNECTING MEANS SHALL BE LOCKABLE OPEN IN ACCORDANCE
WITH 110.25.
WIRING METHODS:
1. FOR UNDERGROUND AND EXPOSED UP TO +5'-0" OR DAMP
LOCATION, THE CONDUIT SHALL BE RIGID STEEL GALVANIZED
IMC. NO RUNNING THREADS ARE PERMITTED.
2. GALVANIZED EMT SHALL BE USED IN DRY CONCEALED
LOCATIONS AN EXPOSED ABOVE +5-0". EMT CONNECTORS
SHALL BE WATERTIGHT COMPRESSION TYPE.
3. GALVANIZED FLEXIBLE CONDUIT SHALL BE USED ONLY FOR
MOTOR AND FIXTURE CONNECTIONS IN LENGTHS NOT TO
EXCEED 66'
4. CONDUITS PENETRATING THE ROOF SHALL BE FLASHED AND
COUNTER FLASHED.
5. INSTALL FITTINGS, SPECIAL DEVICES AND MATERIAL, WHICH
MAY BE REQUIRED FOR THE PROPER INSTALLATION OF THE
CONDUIT SYSTEM.
NOTE:
110.27(B)PREVENT PHYSICAL DAMAGE:IN
LOCATIONS WHERE ELECTRICAL EQUIPMENT IS
LIKELY TO BE EXPOSED TO PHYSICAL DAMAGE,
ENCLOSURES OR GAURDS SHALL BE SO
ARRANGED AND OF SUCH STRENGTH AS TO
PREVENT SUCH DAMAGE.
DEDICATED ELECTRICAL SPACE: WIDTH AND
DEPTH OF EQUIPMENT EXTENDING FROM THE
FLOOR TO 1.8M (6FT) ABOVE EQUIPMENT OR TO
STRUCTURAL CEILING
NOTE:
NEW SERVICES IS LOCATED OUTDOORS IN THE
PARKING SPACES THAT ARE BELOW THE
RESIDENTIAL
UNITS
ACCESSIBLE ROUTES AND ACCESS AISLES:
1. ACCESS AISLES SHALL BE LEVEL WITH THE EV SPACE SERVED,
AND SLOPES/CROSS -SLOPES SHALL NOT EXCEED 1:48
2. ADA COMPLIANT EV SPACES SHALL BE LOACTED ON AN
ACCESSIBLE ROUTE TO AN ACESSIBLE BUILDING ENTRANCE.
(11B-206.4 & 11B-812.5)
3. EVCS SHALL BE DESIGNED SO ACCESSIBLE ROUTES ARE NOT
OBSTRUCTED BY CABLES OR OTHER ELEMENTS. (11B-812.5.5)
4. PROVIDE CURBS, WHEEL STOPS, BOLLARDS, OR OTHER
BARRIERS TO PREVENT ENCROACHMENT OF VEHICLE OVER THE
REQUIRED CLEAR WIDTH OF ACCESSIBLE ROUTES. (11B-812.5.3)
NOTE:
"ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR
CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY
ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFTY
HEALTH ADMINISTRATION."
IMPORTANT BID NOTES:
1. DUE TO THE SMALL SCALE OF DRAWINGS,
IT IS NOT ALWAYS POSSIBLE TO SHOW
ALL DEVICES WHICH MAYBE REQUIRED.
CONTRACTOR SHALL BE RESPONSIBLE TO
VERIFY ALL EXISTING CONDITIONS
BEFORE SUBMITTING HIS/HER BID. NO
ADDITIONAL COMPENSATION WILL BE
MADE FOR EXTRA DUE TO CONTRACTOR'S
FAILURE TO VISIT THE JOB SITE AND/OR
FAILURE TO DETERMINE ALL EXISTING
CONDITIONS BEFORE SUBMITTING
HIS/HER BID.
2. REFER TO COMPLETE ARCHITECTURAL
AND ELECTRICAL DRAWINGS FOR
ADDITIONAL NOTES, SPECIFICATIONS,
DETAILS, CONTROLS, ETC. REPORT TO
ARCHITECTURE'S CLARIFICATION IN BASE
BID. THIS REQUIREMENT WILL BE
STRICTLY ENFORCED. NO CHANGE
ORDERS WILL BE ALLOWED IF THE
CONTRACTOR FAILS TO PERFORM THIS
SIGNAGE REQUIREMENTS AND NOTES:
1. ACCESSIBLE SIGNAGE IS NOT REQUIRED
WHERE A TOTAL OF FOUR OF FEWER EV
SPACES ARE PROVIDED.
2. FIVE TO TWENTY-FIVE TOTAL EV SPACES
ARE PROVIDED:
A - ONE VAN ACCESSIBLE EV SPACE
SHALL BE IDENTIFIED BY IS A
SIGNAGE
B - ACCESSIBLE SIGNAGE IS NOT
REQUIRED AT THE STANDARD
ACCESSIBLE EV SPACES
3. TWENTY-SIX OR MORE EV SPACES ARE
PROVIDED
4. ALL REQUIRED VAN ACCESSIBLE AND
STANDARD ACCESSIBLE EV SPACES SHALL
BE IDENTIFIED BY ISA SIGNAGE
5. IDENTIFICATION SIGNS SHALL BE
REFLECTORIZED WITH MINIMUM AREA OF
70 SQUARE INCHES. (11B-812.8.7)
6. THE IDENTIFICATION SIGN SHALL BE
VISIBLE FROM THE EV SPACE IT SERVES
7. SIGNS IDENTIFYING VAN ACCESSIBLE EV
SPACES SHALL CONTAIN THE WORDS "VAN
ACCESSIBLE"
8. IDENTIFICATION SIGNS SHALL BE
PERMANENTLY POSTED EITHER
IMMEDIATELY ADJACENT TO THE VEHICLE
SPACE OF WITHIN THE PROJECTED
VEHICLE SPACE WIDTH AT THE FRONT END
OF VEHICLE SPACE. (11B-812.8.7)
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-07
02.05.2025
DOTSON
VG
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
PLACARD
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CAUTION
SERVICE 2SERVICE 1
DEDICATED TO EV ONLY
OTHER LOADS MUST
NOT BE CONNECTED
LABEL 01 LOCATION:
TO BE PLACED IN DEDICATED EV SUB PANEL
& NEXT TO THE EV BREAKER IN THE
DISTRIBUTION PANEL
SIZE: 4" X 2" QTY:1
LABEL 02 LOCATION:
TO BE PLACED IN DEDICATED EV SUB PANEL
& NEXT TO THE EV BREAKER IN THE
DISTRIBUTION PANEL
SIZE: 4" X 2" QTY:1
6 Hutton Centre Drive, Unit A,
Santa Ana, CA 92707
208V 225A 3Ø 4W
WARNING PLACARDS:
PNL EV 1
LABEL 03 LOCATION:
TO BE PLACED ON THE CIRCUITS ON MSP - EV
SIZE: 1'6" X 1" QTY:1
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-08
02.05.2025
DOTSON
VG
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
SPEC SHEET 1
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-09
02.05.2025
DOTSON
VG
Software Features
Model TL-SG2008P / TL-SG2210MP TL-SG2008 V3 / TL-SG2210P V3.20 / TL-SG2428P
SDN Support
• Support Omada Hardware Controller (OC200/
OC300), Software Controller, Cloud-Based
Controller
• Automatic Device Discovery
• Batch Configuration
• Batch Firmware Upgrading
• Intelligent Network Monitoring
• Abnormal Event Warnings
• Unified Configuration
• Reboot Schedule
• ZTP (Zero-Touch Provisioning)*
L2+ Features
• DHCP Relay
- DHCP VLAN Relay
• DHCP L2 Relay
• 16 IP Interfaces
- Support IPv4/IPv6 Interface
• Static Routing
- 32 IPv4/IPv6 Static Routes
• DHCP Server
• DHCP Relay
- DHCP Interface Relay
- DHCP VLAN Relay
• DHCP L2 Relay
• Static ARP
• Proxy ARP
• Gratuitous ARP
L2 Features
• Link Aggregation
- Static link aggregation
- 802.3ad LACP
- Up to 8 aggregation groups and up to 8 ports
per group
• Spanning Tree Protocol
- 802.1D STP
- 802.1w RSTP
- 802.1s MSTP
- STP Security: TC Protect, BPDU Filter/Protect,
Root Protect
• Loopback Detection
• Flow Control
- 802.3x Flow Control
• Mirroring
- Port Mirroring
- CPU Mirroring
- One-to-One
- Many-to-One
- Flow-Based
- Ingress/Egress/Both
• Device Link Detect Protocol (DLDP)
• 802.1ab LLDP/ LLDP-MED
L2 Multicast
• 511 IPv4, IPv6 shared multicast groups
• IGMP Snooping
- IGMP v1/v2/v3 Snooping
- Fast Leave
- IGMP Snooping Querier
- Static Group Config
• Multicast VLAN Registration (MVR)
• Multicast Filtering
• MLD Snooping
- MLD v1/v2 Snooping
- Fast Leave
- MLD Snooping Querier
- Static Group Config
• Limited IP Multicast (256 profiles and 16 entries
per profile)
VLAN
• VLAN Group
- Max. 4K VLAN Groups
• 802.1Q tag VLAN
• MAC VLAN
• Protocol VLAN
• GVRP
• Voice VLAN
QoS
• 802.1p CoS/DSCP priority
• 8 priority queues
• Priority Schedule Mode
- SP (Strict Priority)
- WRR (Weighted Round Robin)
• Queue Weight Config
• Bandwidth Control
- Port/Flow based Rating Limit
• Smoother Performance
• Storm Control
- Multiple Control Modes(kbps/ratio)
- Broadcast/Multicast/Unknown-Unicast Control
Hardware Features & Performance
Product Picture
Model TL-SG2210MP
General Interface 8 10/100/1000Mbps RJ45 Ports
2 Gigabit SFP Slots
PoE
PoE Standard 802.3af/at
PoE Ports 8, up to 30W
PoE Power Budget 150 W
Performance
Switching Capacity 20 Gbps
Packet Forwarding Rate 14.88 Mpps
MAC Address Table 8K
Packet Buffer 4.1 Mbit
Number of IP Interfaces 1
Number of Static
Routers --
Jumbo Frame 9 KB
Physical &
Environmet
Power Supply 100-240V AC, 50/60Hz
Max Power
Consumption
12.2 W (110 V/60 Hz) (no PD connected)
173.9 W (110 V/60 Hz) (with 150 W PD
connected)
Max Heat Dissipation
41.63 BTU/h (110 V/60 Hz) (no PD
connected)
539.35 BTU/h (110 V/60 Hz) (with 150 W
PD connected)
Dimensions (W x D x H) 11.6 x 7.1 x 1.7 in (294 x 180 x 44 mm)
Fan Quantity 1
Installation Rackmount/Desktop
Operating Temperature 0 °C to 50 °C (32 °F to 122 °F)
Storage Temperature -40 °C to 70 °C (-40 °F to 158 °F)
Operation Humidity 10% to 90% RH, non-condensing
Storage Humidity 5% to 90% RH, non-condensing
Certification CE, FCC, RoHS
TL-SG2008P
8 10/100/1000Mbps RJ45
ports
802.3af/at
4, up to 30W
62 W
16 Gbps
11.9 Mpps
1
--
9 KB
53.5 VDC/1.31A Ext. Adapter
7.9 W (220 V/50Hz) (no PD
connected)
69.7W (220 V/50Hz) (w/ 62 W PD
connected)
26.95 BTU/h (220 V/50Hz) (no PD
connected)
237.82 BTU/h (220 V/50Hz) (w/
62 W PD connected)
8.2 x 4.9 x 1.0 in (209 x 126 x 25 mm)
Fanless
Desktop/Wall-mounting
0 °C to 40 °C (32 °F to 104 °F)
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
SPEC SHEET 2
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-10
FOR REFERENCE ONLY
MOUNTING FEET SHOWN AS INSTALLED
SECTION A-A
SECTION B-B
AA
B
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
STANDARD ENCLOSURE
DESCRIPTION
ALL DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE SPECIFIED
DO NOT SCALE
CUSTOMERDATE DWG
AH16148
0.03 0.010
SCALE
11/23/16AJC
DRAWN BY
AH161481, 3R, 4, 4X, 12
COLOR:
NEMA 250: TYPE
UNLESS SPECIFIED
TOLERANCES
PART NUMBER
.XX .XXX
AH16148
SPECIAL REQUIREMENTS
MATERIAL: POLYCARBONATE
THIS DRAWING IS THE SOLE AND EXCLUSIVE
PROPERTY OF ROBROY ENCLOSURES.
NO PART OF THIS DRAWING MAY BE
REPRODUCED, DISTRIBUTED, OR PUBLICALLY
DISPLAYED IN ANY FORM OR BY ANY MEANS
WITHOUT THE EXPRESS WRITTEN
PERMISSION OF ROBROY ENCLOSURES.
ALL RIGHTS RESERVED
UNDER THE COPYRIGHT LAWS.
COPYRIGHT ROBROY ENCLOSURES
STANDARD P/N:
CUSTOMER DWG:COLOR STANDARD:
IEC 60529:IP66
AT
N/A
PANTONE 7541 C
2020
Robroy Enclosures
500 Maple Street
Belding, Michigan 48809
Phone: 616-794-0700
Fax: 616-749-3378
ASSEMBLY:
1. (1) ACCESSORY KIT (WPPCACCKIT) SHALL BE PACKAGED LOOSELY INSIDE ENCLOSURE
HARDWARE INCLUDED:
-(4) #1/4-20 x 1/2 FLAT HEAD PHILLIPS MACHINE SCREW (RMSC1/4-20X.5FLPH)
-(4) #10-32 x 5/8 PAN HEAD PHILLIPS MACHINE SCREW (RMSC10/32X5/8SS)
-(4) #10-32 x 3/8 PAN HEAD SCREW (RMSC10/32X3/8ZN)
-(4) #10 WASHER (RMWAS10ZN)
2. (1) STYROFOAM SHEET SHALL BE PLACED ON TOP OF COVER INSIDE CARTON
REVISION HISTORY
REV DESCRIPTION DATE ENG
A PER ECR17972; REMOVED MTL. FROM INNER
GASKET SEALING LIP 09/22/20 AA
--- -
--- -
--- -
--- -
13.63
18.03
11.63
17.41
15.41
16.79
18.88
9.86
1.20
16.68
9.40
14.79
12.25
13.93
0.14 TYP
14.00
0.188 TYP
0.44
15.93
14.2516.00
9.07
A Features - S920 Series
Specifications
Ceiling Mount 802.11ax Wi-Fi 6 AP
Model EAP610
Name AX1800 Ceiling Mount Dual-Band Wi-Fi 6 Access Point
Main Design
LAN Interfaces 1x Gigabit Ethernet Port
Wi-Fi Standards IEEE 802.11 a/b/g/n/ac/ax
Maximum Data Rate 574 Mbps (2.4 GHz)
+1201 Mbps (5 GHz)
Wireless Client Capacity 250+
Antennas 2.4 GHz: 2x 4 dBi
5 GHz: 2x 5 dBi
Transmit Power CE: < 20 dBm (2.4 GHz, EIRP); < 23 dBm (5 GHz, band 1&band 2, EIRP); < 30 dBm (5 GHz, band 3, EIRP);
FCC: < 25 dBm (2.4 GHz); < 25 dBm (5 GHz)
Centralized
Management
Omada Software
Controller •
Omada Hardware
Controller •
Omada APP •
Security
Captive Portal
Authentication •
Access Control •
Maximum number of MAC
Filter 4000
Wireless Isolation
between Clients •
VLAN •
Rogue AP Detection •
Wireless Encryption WPA-Personal/Enterprise, WPA2-Personal/Enterprise, WPA3-Personal/Enterprise
802.1X Support •
Wireless
Function
Multiple SSIDs 16 (8 on each band)
Enable/Disable Wireless
Radio •
Enable/Disable SSID
Broadcast •
Guest Network •
Automatic Channel
Assignment •
Transmit Power Control Adjust transmit Power on dBm
QoS (WMM)•
Seamless Roaming •
Mesh •
Beamforming •
MU-MIMO •
Rate Limit Based on SSID/Client
Load Balance •
Airtime Fairness •
Band Steering •
RADIUS Accounting •
MAC Authentication •
Reboot Schedule •
Wireless Schedule •
Wireless Statistics •
Static IP/Dynamic IP •
Ceiling Mount 802.11ax Wi-Fi 6 AP
Model EAP610
Support Data
Rates
802.11ax 8 Mbps to 1201 Mbps (MCS0-MCS11, NSS = 1 to 2 HE20/40/80)
802.11ac 6.5 Mbps to 1083.3 Mbps (MCS0-MCS11, NSS = 1 to 2 VHT20/40/80)
802.11n 6.5 Mbps to 300 Mbps (MCS0-MCS15, HT20/40)
802.11g 6, 9, 12, 18, 24, 36, 48 ,54 Mbps
802.11b 1, 2, 5.5, 11 Mbps
802.11a 6, 9, 12, 18, 24, 36, 48 ,54 Mbps
Management
LED ON/OFF Control •
Management MAC
Access Control •
Web-based Management •
SNMP v1, v2c, v3
SSH •
Restore & Backup •
Firmware update via Web •
NTP •
System Log •
Email Alerts •
Physical &
Environment
Power Supply V1 & V3: 48V Passive PoE or 802.3at PoE or 12V/1A DC
V2: 48V Passive PoE or 802.3at PoE or 12V/1.5A DC
Maximum Power
Consumption
V1:
EU: 12.8 W (For PoE); 10.8 W (for DC)
US: 13.9 W (For PoE); 11.8 W (for DC)
V2:
EU: 13.7 W (For PoE); 12.3 W (for DC)
US: 14.2 W (For PoE); 12.8 W (for DC)
V3:
EU: 10.6W (For PoE); 9.6W (for DC)
US: 10.9W (For PoE); 9.8W (for DC)
Reset •
Mounting Ceiling / Wall mouting (Kits included) / Junction Box mouting
Certifications CE, FCC, RoHS, IC
Dimensions (W x D x H) 160 x 160 x 33.6 mm
Environment
Operating Temperature: 0 °C–40 °C (32 °F–104 °F);
Storage Temperature: -40 °C–70 °C (-40 °F–158 °F);
Operating Humidity: 10%–90% non-condensing;
Storage Humidity: 5%–90% non-condensing;
Antenna Radiation Patterns
Ceiling Mount AP
EAP610
Elevation-0°Elevation-90°Azimuth Mapped 3D
2.45 GHz
5.25 GHz
5.5 GHz
5.75 GHz
02.05.2025
DOTSON
VG
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
SPEC SHEET 1
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-09
02.05.2025
DOTSON
VG
Software Features
Model TL-SG2008P / TL-SG2210MP TL-SG2008 V3 / TL-SG2210P V3.20 / TL-SG2428P
SDN Support
• Support Omada Hardware Controller (OC200/
OC300), Software Controller, Cloud-Based
Controller
• Automatic Device Discovery
• Batch Configuration
• Batch Firmware Upgrading
• Intelligent Network Monitoring
• Abnormal Event Warnings
• Unified Configuration
• Reboot Schedule
• ZTP (Zero-Touch Provisioning)*
L2+ Features
• DHCP Relay
- DHCP VLAN Relay
• DHCP L2 Relay
• 16 IP Interfaces
- Support IPv4/IPv6 Interface
• Static Routing
- 32 IPv4/IPv6 Static Routes
• DHCP Server
• DHCP Relay
- DHCP Interface Relay
- DHCP VLAN Relay
• DHCP L2 Relay
• Static ARP
• Proxy ARP
• Gratuitous ARP
L2 Features
• Link Aggregation
- Static link aggregation
- 802.3ad LACP
- Up to 8 aggregation groups and up to 8 ports
per group
• Spanning Tree Protocol
- 802.1D STP
- 802.1w RSTP
- 802.1s MSTP
- STP Security: TC Protect, BPDU Filter/Protect,
Root Protect
• Loopback Detection
• Flow Control
- 802.3x Flow Control
• Mirroring
- Port Mirroring
- CPU Mirroring
- One-to-One
- Many-to-One
- Flow-Based
- Ingress/Egress/Both
• Device Link Detect Protocol (DLDP)
• 802.1ab LLDP/ LLDP-MED
L2 Multicast
• 511 IPv4, IPv6 shared multicast groups
• IGMP Snooping
- IGMP v1/v2/v3 Snooping
- Fast Leave
- IGMP Snooping Querier
- Static Group Config
• Multicast VLAN Registration (MVR)
• Multicast Filtering
• MLD Snooping
- MLD v1/v2 Snooping
- Fast Leave
- MLD Snooping Querier
- Static Group Config
• Limited IP Multicast (256 profiles and 16 entries
per profile)
VLAN
• VLAN Group
- Max. 4K VLAN Groups
• 802.1Q tag VLAN
• MAC VLAN
• Protocol VLAN
• GVRP
• Voice VLAN
QoS
• 802.1p CoS/DSCP priority
• 8 priority queues
• Priority Schedule Mode
- SP (Strict Priority)
- WRR (Weighted Round Robin)
• Queue Weight Config
• Bandwidth Control
- Port/Flow based Rating Limit
• Smoother Performance
• Storm Control
- Multiple Control Modes(kbps/ratio)
- Broadcast/Multicast/Unknown-Unicast Control
Hardware Features & Performance
Product Picture
Model TL-SG2210MP
General Interface 8 10/100/1000Mbps RJ45 Ports
2 Gigabit SFP Slots
PoE
PoE Standard 802.3af/at
PoE Ports 8, up to 30W
PoE Power Budget 150 W
Performance
Switching Capacity 20 Gbps
Packet Forwarding Rate 14.88 Mpps
MAC Address Table 8K
Packet Buffer 4.1 Mbit
Number of IP Interfaces 1
Number of Static
Routers --
Jumbo Frame 9 KB
Physical &
Environmet
Power Supply 100-240V AC, 50/60Hz
Max Power
Consumption
12.2 W (110 V/60 Hz) (no PD connected)
173.9 W (110 V/60 Hz) (with 150 W PD
connected)
Max Heat Dissipation
41.63 BTU/h (110 V/60 Hz) (no PD
connected)
539.35 BTU/h (110 V/60 Hz) (with 150 W
PD connected)
Dimensions (W x D x H) 11.6 x 7.1 x 1.7 in (294 x 180 x 44 mm)
Fan Quantity 1
Installation Rackmount/Desktop
Operating Temperature 0 °C to 50 °C (32 °F to 122 °F)
Storage Temperature -40 °C to 70 °C (-40 °F to 158 °F)
Operation Humidity 10% to 90% RH, non-condensing
Storage Humidity 5% to 90% RH, non-condensing
Certification CE, FCC, RoHS
TL-SG2008P
8 10/100/1000Mbps RJ45
ports
802.3af/at
4, up to 30W
62 W
16 Gbps
11.9 Mpps
1
--
9 KB
53.5 VDC/1.31A Ext. Adapter
7.9 W (220 V/50Hz) (no PD
connected)
69.7W (220 V/50Hz) (w/ 62 W PD
connected)
26.95 BTU/h (220 V/50Hz) (no PD
connected)
237.82 BTU/h (220 V/50Hz) (w/
62 W PD connected)
8.2 x 4.9 x 1.0 in (209 x 126 x 25 mm)
Fanless
Desktop/Wall-mounting
0 °C to 40 °C (32 °F to 104 °F)
VAHE GULAGIAN
02/10/2025
CONTRACTOR
SHEET DESCRIPTION:
SPEC SHEET 2
DRAWN DATE
DRAWN BY
REVIEWED BY
REVISIONS
REV DESCRIPTION DATE
SHEET INDEX
UTILITY : SANTA ANA
PROJECT INFORMATION
AHJ : LOS ANGELES
ADDRESS : 6 HUTTON CENTRE
DRIVE, UNIT A, SANTA ANA, CA
92707
NAME : WESTSIDE CONTRACTORS
APN : ----
SYSTEM INFORMATION:
(8)EVO CHARGE
CHARGING STATIONS
SIGNATURE WITH SEAL
CHARGIE LLC
3947 Landmark St,
Culver City, CA 90232
(310) 307-5166
JOHNNY HUSTON
LIC: #1086808
EV-10
FOR REFERENCE ONLY
MOUNTING FEET SHOWN AS INSTALLED
SECTION A-A
SECTION B-B
AA
B
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
STANDARD ENCLOSURE
DESCRIPTION
ALL DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE SPECIFIED
DO NOT SCALE
CUSTOMERDATE DWG
AH16148
0.03 0.010
SCALE
11/23/16AJC
DRAWN BY
AH161481, 3R, 4, 4X, 12
COLOR:
NEMA 250: TYPE
UNLESS SPECIFIED
TOLERANCES
PART NUMBER
.XX .XXX
AH16148
SPECIAL REQUIREMENTS
MATERIAL: POLYCARBONATE
THIS DRAWING IS THE SOLE AND EXCLUSIVE
PROPERTY OF ROBROY ENCLOSURES.
NO PART OF THIS DRAWING MAY BE
REPRODUCED, DISTRIBUTED, OR PUBLICALLY
DISPLAYED IN ANY FORM OR BY ANY MEANS
WITHOUT THE EXPRESS WRITTEN
PERMISSION OF ROBROY ENCLOSURES.
ALL RIGHTS RESERVED
UNDER THE COPYRIGHT LAWS.
COPYRIGHT ROBROY ENCLOSURES
STANDARD P/N:
CUSTOMER DWG:COLOR STANDARD:
IEC 60529:IP66
AT
N/A
PANTONE 7541 C
2020
Robroy Enclosures
500 Maple Street
Belding, Michigan 48809
Phone: 616-794-0700
Fax: 616-749-3378
ASSEMBLY:
1. (1) ACCESSORY KIT (WPPCACCKIT) SHALL BE PACKAGED LOOSELY INSIDE ENCLOSURE
HARDWARE INCLUDED:
-(4) #1/4-20 x 1/2 FLAT HEAD PHILLIPS MACHINE SCREW (RMSC1/4-20X.5FLPH)
-(4) #10-32 x 5/8 PAN HEAD PHILLIPS MACHINE SCREW (RMSC10/32X5/8SS)
-(4) #10-32 x 3/8 PAN HEAD SCREW (RMSC10/32X3/8ZN)
-(4) #10 WASHER (RMWAS10ZN)
2. (1) STYROFOAM SHEET SHALL BE PLACED ON TOP OF COVER INSIDE CARTON
REVISION HISTORY
REV DESCRIPTION DATE ENG
A PER ECR17972; REMOVED MTL. FROM INNER
GASKET SEALING LIP 09/22/20 AA
--- -
--- -
--- -
--- -
13.63
18.03
11.63
17.41
15.41
16.79
18.88
9.86
1.20
16.68
9.40
14.79
12.25
13.93
0.14 TYP
14.00
0.188 TYP
0.44
15.93
14.2516.00
9.07
A Features - S920 Series
Specifications
Ceiling Mount 802.11ax Wi-Fi 6 AP
Model EAP610
Name AX1800 Ceiling Mount Dual-Band Wi-Fi 6 Access Point
Main Design
LAN Interfaces 1x Gigabit Ethernet Port
Wi-Fi Standards IEEE 802.11 a/b/g/n/ac/ax
Maximum Data Rate 574 Mbps (2.4 GHz)
+1201 Mbps (5 GHz)
Wireless Client Capacity 250+
Antennas 2.4 GHz: 2x 4 dBi
5 GHz: 2x 5 dBi
Transmit Power CE: < 20 dBm (2.4 GHz, EIRP); < 23 dBm (5 GHz, band 1&band 2, EIRP); < 30 dBm (5 GHz, band 3, EIRP);
FCC: < 25 dBm (2.4 GHz); < 25 dBm (5 GHz)
Centralized
Management
Omada Software
Controller •
Omada Hardware
Controller •
Omada APP •
Security
Captive Portal
Authentication •
Access Control •
Maximum number of MAC
Filter 4000
Wireless Isolation
between Clients •
VLAN •
Rogue AP Detection •
Wireless Encryption WPA-Personal/Enterprise, WPA2-Personal/Enterprise, WPA3-Personal/Enterprise
802.1X Support •
Wireless
Function
Multiple SSIDs 16 (8 on each band)
Enable/Disable Wireless
Radio •
Enable/Disable SSID
Broadcast •
Guest Network •
Automatic Channel
Assignment •
Transmit Power Control Adjust transmit Power on dBm
QoS (WMM)•
Seamless Roaming •
Mesh •
Beamforming •
MU-MIMO •
Rate Limit Based on SSID/Client
Load Balance •
Airtime Fairness •
Band Steering •
RADIUS Accounting •
MAC Authentication •
Reboot Schedule •
Wireless Schedule •
Wireless Statistics •
Static IP/Dynamic IP •
Ceiling Mount 802.11ax Wi-Fi 6 AP
Model EAP610
Support Data
Rates
802.11ax 8 Mbps to 1201 Mbps (MCS0-MCS11, NSS = 1 to 2 HE20/40/80)
802.11ac 6.5 Mbps to 1083.3 Mbps (MCS0-MCS11, NSS = 1 to 2 VHT20/40/80)
802.11n 6.5 Mbps to 300 Mbps (MCS0-MCS15, HT20/40)
802.11g 6, 9, 12, 18, 24, 36, 48 ,54 Mbps
802.11b 1, 2, 5.5, 11 Mbps
802.11a 6, 9, 12, 18, 24, 36, 48 ,54 Mbps
Management
LED ON/OFF Control •
Management MAC
Access Control •
Web-based Management •
SNMP v1, v2c, v3
SSH •
Restore & Backup •
Firmware update via Web •
NTP •
System Log •
Email Alerts •
Physical &
Environment
Power Supply V1 & V3: 48V Passive PoE or 802.3at PoE or 12V/1A DC
V2: 48V Passive PoE or 802.3at PoE or 12V/1.5A DC
Maximum Power
Consumption
V1:
EU: 12.8 W (For PoE); 10.8 W (for DC)
US: 13.9 W (For PoE); 11.8 W (for DC)
V2:
EU: 13.7 W (For PoE); 12.3 W (for DC)
US: 14.2 W (For PoE); 12.8 W (for DC)
V3:
EU: 10.6W (For PoE); 9.6W (for DC)
US: 10.9W (For PoE); 9.8W (for DC)
Reset •
Mounting Ceiling / Wall mouting (Kits included) / Junction Box mouting
Certifications CE, FCC, RoHS, IC
Dimensions (W x D x H) 160 x 160 x 33.6 mm
Environment
Operating Temperature: 0 °C–40 °C (32 °F–104 °F);
Storage Temperature: -40 °C–70 °C (-40 °F–158 °F);
Operating Humidity: 10%–90% non-condensing;
Storage Humidity: 5%–90% non-condensing;
Antenna Radiation Patterns
Ceiling Mount AP
EAP610
Elevation-0°Elevation-90°Azimuth Mapped 3D
2.45 GHz
5.25 GHz
5.5 GHz
5.75 GHz
02.05.2025
DOTSON
VG
VAHE GULAGIAN
02/10/2025