HomeMy WebLinkAbout1925 W Deerfield Rd - PlanSCOPE OF WORK GENERAL NOTES VICINITY MAPABBREVIATIONS A AMPERE AC ALTERNATING CURRENT AFC ARC FAULT CIRCUIT INTERUPTER AZIM AZIMUTH COMP COMPOSITION DC DIRECT CURRENT (E)EXISTING ESS ENERGY STORAGE SYSTEM MSP MAIN SERVICE PANEL (N)NEW PRE-FAB PRE-FABRICATED PSF POUNDS PER SQUARE FOOT PV PHOTOVOLTAIC RSD RAPID SHUTDOWN DEVICE TL TRANSFORMERLESS V VOLTS W WATTS SHEET INDEX PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA  PR-3004737100 SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-1.0 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 COVER SHEETREV NAME DATE COMMENTS ALL MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS. CEC 2022. CEC 2022. COMPLIES WITH 690.41(A) ARRAY ARE LIMITED TO LESS THAN 30V IN 30 SECONDS AND CEC 2022 690.12(B)(2)(2) WHERE CONDUCTORS INSIDE  THE ARRAY BOUNDARY IS LIMITED TO LESS THAN 80V IN 30 SECONDS 14.29 AMPS MODULE SHORT CIRCUIT CURRENT. 22.33 AMPS DERATED SHORT CIRCUIT CURRENT [690.8 (a)(1) & 690.8 (b)]. VOLTAGE IN ACCORDANCE WITH CEC 706.20 AND EXCEPTION 1 CEC 706.20 (B).  THROUGH A WALL OR PARTITION PER 706.15(D).  THAN 6FT AND DOES NOT INCLUDE ANY ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D). BY THE SINGLE LARGEST UTILIZATION EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A) (MCI) ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE 1707000-XX-Y, 13.5 KWH. TOTAL ENERGY CAPACITY (IN kWh):13.5kWH PANEL SNR-DC-01507 INSTALLED, SEE PV-4.0 FOR INTERCONNECTION DETAILS PAGE # DESCRIPTION PV-1.0 COVER SHEET PV-2.0 SITE PLAN PV-3.0 LAYOUT PV-3.1 MOUNTING DETAIL PV-4.0 ELECTRICAL PV-4.1 ELECTRICAL CALCS PV-4.2 BACKUP LOAD CALCS PV-4.3 PANEL SCHEDULE PV-5.0 SIGNAGE PV-5.1 SIGNAGE 2 PLPL PL PL PL PL PL PL PL PL PL PL PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA  PR-3004737100 SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-2.0 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 SITE PLAN MAIN PANEL SERVICE ENTRANCE SE MP SUB-PANELSP LEGEND SCALE: NTS NOTE: NOT ALL ITEMS IN LEGEND  WILL APPEAR IN SITE PLAN ENERGY STORAGE  SYSTEM (ESS) GP GENERATION PANEL INVERTER(S) AC DISCONNECT(S) DC DISCONNECT(S) INTERIOR EQUIPMENT  SHOWN AS DASHEDINV AC DC METER ADAPTERMA BATTERY BP BACKUP LOADS PANEL MD MICROGRID  INTERCONNECT DEVICE PV LOAD CENTERLC METER ADAPTER  CONTROLLER APB FRANKLIN  APBOX CB IQ COMBINER BOX MAC RDS REMOTE DISCONNECT  SWITCH RAIL STANDOFFS &  FOOTINGS SOLAR  MODULES ESS SHALL BE INSTALLED 3FT FROM DOORS AND  WINDOWS IN ACCORDANCE WITH R328.4. ESS  UNITS SHALL BE SEPARATED FROM EACH OTHER  BY NOT LESS THAN 3 FEET EXCEPT WHERE  SMALLER SEPARATION DISTANCES ARE  DOCUMENTED TO BE ADEQUATE BASED ON  LARGE/SCALE FIRE TESTING. NOTE: ROOFTOP MODULE LEVEL RAPID  SHUTDOWN DEVICE INSTALLED PER CEC  690.12 SITE PLAN - SCALE = 1/16" = 1'-0" (E) GATE (E) CHIMNEY INV ACMP SE RDS BP MD A A A A A AAAAAA A A W DEERFIELD RD (E) RESIDENCE (N) ARRAY AR-01 ROOF PATHWAYS  (3' TYP) ROOF PATHWAYS  (3' TYP) FIRE SETBACKS  (18" TYP) (E) FENCE NOTES:  RESIDENCE DOES NOT CONTAIN ACTIVE FIRE  SPRINKLERS. ARRAY DETAILS:  TOTAL ROOF SURFACE AREA: 3338 SQ FT.  TOTAL PV ARRAY AREA: 272.9 SQ FT.  PERCENTAGE PV COVERAGE: (TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE  AREA) * 100 = 8.2% PITCH PV AREA  (SQFT) AR-01 23°272.87 TRUE  AZIM MAG  AZIM 167°179° Signed: 12/22/2025 DESIGN CRITERIA MAX DISTRIBUTED LOAD: 3 PSF SNOW LOAD: 0 PSF WIND SPEED:  96 MPH 3-SEC GUST. FASTENERS: (2) DECK ANCHORS FULLY  PENETRATING THROUGH WOOD  DECK PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA  PR-3004737100 SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-3.0 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 LAYOUT SOLAR MODULE SNAPNRACK  RACKING MODULE ELEVATION DETAIL - SCALE: NTS 4.5" ROOF INFO ATTACHMENT INFORMATION Name Type Height Detail Max Landscape  OC Spacing Max Landscape  Overhang Max Portrait  OC Spacing Max Portrait  Overhang Configuration AR-01 COMP SHINGLE - UR - ULTRAFOOT  [DECKANCHOR]2-Story ULTRAFOOT [ANCHOR] RAIL TO DECK SNR-DC-01507 4'-10" 0'-6" 4'-10" 0'-6" STAGGERED INSTALLERS SHALL NOTIFY ENGINEER OF ANY  POTENTIAL STRUCTURAL ISSUES OBSERVED  PRIOR TO PROCEEDING W/ INSTALLATION. ATTACHMENTS FOR THIS INSTALLATION ARE DESIGNED FOR A STANDARD  WOOD FRAMED ROOF STRUCTURE FREE FROM DAMAGE, DETERIORATION,  OR MODIFICATION THAT WOULD COMPROMISE ITS ORIGINAL DESIGN  INTEGRITY.  INSTALLERS SHALL OBSERVE THE FRAMING FOR  CONFORMANCE TO THE BELOW REQUIREMENTS AND NOTIFY THE ENGINEER  OF ANY POTENTIAL STRUCTURAL ISSUES FOR GUIDANCE PRIOR TO  PROCEEDING WITH INSTALLATION.  :  MINIMUM 2x WOOD FRAMING (NOMINAL) FREE FROM DAMAGE,  DETERIORATION, OR MODIFICATION ⅱ:  FRAMING SPACING AT 24"" O.C. MAX ⅲ: FASTENER SHALL BE EMBEDDED INTO COMPETENT MATERIAL D1 - AR-01 - SCALE: 3/16" = 1'-0" AZIM:179° PITCH:23° 22'-7" 17'-1" 20'-1"4'-8" 1'-10" 4'-11" IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12" (48" FOR  TILT KITS) BOUNDARY REGION OF ANY ROOF PLANE  EDGES (EXCEPT VALLEYS), THEN ATTACHMENTS NEED TO BE ADDED AND  OVERHANG REDUCED WITHIN THE 12" (48" FOR TILT  KITS) BOUNDARY REGION ONLY AS FOLLOWS: PLANS TO BE REDUCED BY 50%. 1/5TH OF ALLOWABLE ATTACHMENT SPACING  INDICATED ON PLANS. 20'-1"4'-8" 1'-10" Signed: 12/22/2025 FOR SNAPNRACK ENGINEERING TO APPLY, THE EMBEDMENT CRITERIA SHOWN  HEREIN MUST BE MET (IF CRITERIA CANNOT BE MET OR SPANS ARE NOT  SUFFICIENT, CONTACT SNAPNRACKFOR SUPPORT): REFER TO SNAPNRACK INSTALLATION MANUAL FOR 5 16"Ø HARDWARE TORQUE  SPECIFICATIONS. REFER TO MANUFACTURER SPECIFICATIONS FOR OTHER FASTENER  TORQUE REQUIREMENTS.  FOR DECK MOUNT ATTACHMENT: MINIMUM 3 8" SHEATHING REQUIRED. FASTENER  MUST EMBED INTO COMPETENT MATERIAL. REFER TO ATTACHMENT INFORMATION TABLE ON LAYOUT PAGE FOR LOAD PATH  (INSTALL TYPE).  EXPLODED BUTYL PAD 5 16" -18 X 1", SS BOLT, WIDE FLANGE,  RECESSED ULTRA RAIL SPRING  ULTRAFOOT BASE ANCHOR ULTRAFOOT FLIP CLAMP THRU ULTRAFOOT FLIP CLAMP TAPPED TOP .374" .217" RAFTER ATTACHMENT DETAIL SECTION VIEW ROOF DECKING, TYP. ROOF RAFTER, TYP.  FASTENER HEIGHT OFF ROOF: 5/16"  MODULE HEIGHT MAX: UR-40 = 4 1/2" UR-45 = 4 1/2" UR-60 = 5 1/8"  MIN 2 1/2" EMBEDMENT (X1) 5 16"  S.S. LAG  SCREW SNAPNRACK, ULTRA RAIL ULTRAFOOT ANCHOR FASTENER CONFIGURATIONS (X2) DECKANCHORS  INTO WOOD DECK (X1) LAG INTO RAFTER DECK ATTACHMENT DETAIL SECTION VIEW COMP SHINGLE ROOFING, TYP ROOF DECKING, TYP SNAPNRACK, ULTRA RAIL  FASTENER HEIGHT OFF ROOF: 5/16"  MODULE HEIGHT, MAX: UR-40 = 4 1/2" UR-45 = 4 1/2" UR-60 = 5 1/8" (X2) DECK  ANCHOR INTO WOOD DECK MINIMUM 3/8" SCREW  EMBEDMENT INTO DECKING PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-3.1 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 MOUNTING DETAIL DESIGNER: APPROVED BY: M.AFFENTRANGER DRAFTER: H.WULFEKOETTER M.AFFENTRANGER SCALE: DATE: NTS 8/26/2024 DRAWING NUMBER: SNR-DC-01507 Solar Mounting Solutions Sunrun South LLC 595 MARKET STREET, 29TH FLOOR  SAN FRANCISCO, CA 94105 USA PHONE (415) 580-6900  FAX (415) 580-6902 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF SUNRUN SOUTH LLC. Signed: 12/22/2025 FACILITY  GROUND 120/240 VAC SINGLE PHASE SERVICE  EXISTING 225A MAIN BREAKER  -END FED EXISTING 225A MAIN PANEL 225A  BUS (E) FACILITY  LOADS M   125A  NEW 200A BACKUP GATEWAY 3  (1841000-X1-Y) (N) INTERNAL PANELBOARD WITH(1) 60A PV+ESS BREAKER 4 A A NEW 225 A BACKUP LOADS PANEL WITH  125 A MAIN BREAKER RELOCATED (E) LOADS 4 60A (N) IMO PE69-3020,  DISCONNECT  SWITCH, 3P, 16A INVERTER: TESLA POWERWALL 3 1707000-XX-Y, ENERGY STORAGE: TESLA:POWERWALL 3 1707000-XX-Y 11500 WATT INVERTER LOAD RATED DC DISCONNECT WITH AFCI RAPID SHUTDOWN COMPLIANT, POWER CONTROL SYSTEM 3 J-BOX 12 222012-776623 CHARACTERISTICS INCLUDED IN SPEC SHEETS INTERCONNECTION CALCULATIONS (N)TESLA REMOTE METER SITE  CURRENT TRANSFORMER 13 SILFAB SIL-440QD STRING 1 WITH 13 MODULES WITH 5 MCI COUNT , MODULE  LEVEL RAPID SHUTDOWN  DEVICES (N) LOCKABLE BLADE TYPE AC DISCONNECT SQUARE D DU222RB 3R, 60A, 2P 120/240VAC 3 5 CONDUIT SCHEDULE TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT 1 Inverter Input (2) 10 AWG  (PV WIRE)N/A 6 AWG  (BARE)Open Air 2 Inverter Input (2) 10 AWG  THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4 EMT 3 Inverter Output (2) 6 AWG  THHN/THWN-2 (1) 6 AWG  THHN/THWN-2 8 AWG THHN/THWN-2 3/4 EMT 4 Backup Panel Feeder (2) 1 AWG  THHN/THWN-2 (1) 1 AWG  THHN/THWN-2 6 AWG THHN/THWN-2 1 1/4 EMT 5 Backup loads (22) 10 AWG  THHN/THWN-2 (22) 10 AWG  THHN/THWN-2 8 AWG THHN/THWN-2 2 EMT(2) 10 AWG  THHN/THWN-2 (1) 10 AWG  THHN/THWN-2 8 AWG THHN/THWN-2 (4) 8 AWG  THHN/THWN-2 (2) 8 AWG  THHN/THWN-2 8 AWG THHN/THWN-2 PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA  PR-3004737100 SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-4.0 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 ELECTRICAL MODULE CHARACTERISTICS SILFAB: SIL-440QD 440 W OPEN CIRCUIT VOLTAGE 38.97 V MAX POWER VOLTAGE 33.41 V SHORT CIRCUIT CURRENT 14.29 A INSTALLER MUST CHECK THE CONDITION,  INSTALLABILITY AND CODE COMPLIANCE OF  EXISTING EQUIPMENT. POWER CONTROL SYSTEM (PCS):  DOES NOT EXCEED THE RATING OF ANY BUSBAR OR CONDUCTOR SUPPLIED BY THE POWER PRODUCTION  SOURCES SHALL COMPLY WITH ARTICLE 705.12.           - 180A - MAXIMUM TOTAL CURRENT ON THE CONTROLLED PANEL           - 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY (120% COMPLIANT) General Notes: COLD WATER GAS BOND INTERCONNECTION DEVICE BREAKER CONDUCTORS IN TWO SEPARATE  CONDUITS. IF THE RELOCATED LOADS EXTEND MORE THAN 6 FEET, AFCI PROTECTION  APPLIES PER 2019 CEC 210.12 ANY MULTIWIRE BRANCH CIRCUITS RELOCATED ARE TO BE IDENTIFIED,  GROUPED, AND EQUIPPED WITH A 2-POLE OCPD BREAKER PER CEC  210.4(B,D). INVERTER CALCULATIONS EACH INVERTER HAS THE FOLLOWING VALUES WHICH ARE CALCULATED FOLLOWING THESE FORMULAS: INVERTER X: {[((TEMP COEF VOC) X (VOC)) / 100] X (LOW TEMP - STC TEMP) + VOC} * (#  MODULES / STRING) INVERTER POWERWALL 3 1707000-XX-Y ALLOWABLE BACKFEED:    MAX ALLOWED TOTAL GENERATION BACKFEED OCPD =    MAIN BREAKER RATING = 225 A    125 A ≤ 225 A   INTERCONNECTION    MEETS CEC 2022 705.13 REQUIREMENTSWIRE CALCULATIONS WIRE AMPACITY CALCULATED FROM CEC 310.16/310.17 AS APPROPRIATE WITH AMBIENT TEMPERATURE  CALCULATIONS FROM CEC 310.15(B)(1) AND RACEWAY FILL ADJUSTMENTS FROM CEC 310.15(C)(1). CONDUIT  ON THE ROOF SHALL BE INSTALLED NO LESS THAN 1" ABOVE THE ROOF DECK. PV CIRCUIT CONDUCTOR  AMPACITY IS CONSTRAINED USING THE 75°C COLUMN WITH THE CONTINUOUS DUTY UPRATING OR THE 90°C  COLUMN WITH THE RELEVANT AMBIENT TEMPERATURE AND RACEWAY FILL ADJUSTMENTS WITHOUT THE  CONTINUOUS DUTY UPRATING PER 690.8(B), WHICHEVER IS THE LOWER VALUE WILL GOVERN CONDUCTOR  SIZING. NON-PV CIRCUIT CONDUCTORS USE THE AMPACITY IN THE 75°C COLUMN OR THE 90°C COLUMN WITH  THE RELEVANT AMBIENT TEMPERATURE AND RACEWAY FILL ADJUSTMENTS, WHICHEVER IS LESS (110.14(C) &  310.15(A)(2)). THE RATING OF THE CONDUCTOR AFTER ADJUSTMENTS SHALL BE GREATER THAN, OR EQUAL  TO, THE CONTINUOUS DUTY UPRATED CURRENT.  CALC EX: WIRE AMPACITY X AMBIENT TEMP. CORR. FACTOR X CONDUIT FILL ADJ. FACTOR >= OUTPUT  CURRENT PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA  PR-3004737100 SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-4.1 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 ELECTRICAL CALCS BACKUP LOADS LOAD BREAKER RATING  (AMPS)LABEL DEMAND  LOAD 1 15A-1P SEC 1440 W 2 20A-1P SEC 1500 W 3 20A-1P GDO 1500 W 4 20A-1P KIT 1500 W 5 20A-1P DW 1500 W 6 20A-1P KIT 1500 W 7 20A-1P MICRO 1500 W 8 20A-1P GD 1500 W 9 20A-1P REFRI 1500 W 10 20A-1P LAUNDRY 1500 W 11 20A-1P GFI 1500 W 12 20A-1P HOOD 1500 W 13 20A-1P D/R 1500 W 14 20A-1P SPA 1500 W 15 20A-1P GFI 1500 W 16 20A-1P FAU 1920 W 17 20A-1P FAU 1920 W 18 20A-1P GFI  1500 W 19 20A-1P LIGHTS/RECEPTABLES 1500 W 20 20A-1P GFI 1500 W 21 20A-1P REFRI 1500 W 22 20A-2P LIGHTS/RECEPTABLES 86    W 23 40A-2P RANGE 86    W 24 40A-2P AC 86    W 25 30A-2P OVEN 5760 W ELECTRICAL CALCULATIONS FOR BACKED UP LOADS ALL BACKED UP LOADS ABOVE IN THE BACKED UP LOADS PANEL ARE RELOCATED FROM THE MAIN SERVICE PANEL. BACKED UP LOADS CALCULATION: (7680 VA)/ 240V = 32 A PER CEC 2022 ARTICLE 690.10 OR NEC 2020 ARTICLE 710.15. THE MAXIMUM CURRENT FOR ALL SMALL APPLIANCES LOADS IS 32 A. (MAX LOADS OUTPUT) X (CONTINUOUS LOADS) =  32A X 1.25 = 40 A; BACKED UP LOADS PANEL BREAKER = 125 A 40 A < 125 A. THEREFORE, THE AMPERAGE OF THE BACKED UP LOADS IS LESS THAN THAT OF THE OCPD. AC WIRE SIZING FOR BACKED UP LOADS PANEL: MAX AC OUTPUT CURRENT = (MAX BACKUP LOADS OUTPUT) X (CONTINUOUS LOAD)[210.19(A)(1)] = 32A X 1.25 = 40A ADJUSTED CONDUCTOR AMPACITY = (HIGH TEMP)[TABLE 310.15(B)(1)] X (CONDUIT FILL)[TABLE 310.15(C)(1)] X  (CONDUCTOR AMPACITY)[TABLE 310.16] = 0.91 X 0.45 X 55A =22.5225A TERMINAL RATING[110.14(C)] = 8 AWG, , 75°C RATED = 50A 40A < 50A → TERMINAL RATING GOVERNS CONDUCTOR SIZING. 22.5225A < 40A → 8AWG AMPACITY OK THEREFORE 8 AWG IS SUFFICIENT. CONDUIT LENGTH OF THE BACKED UP LOADS CONDUIT.      PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-4.2 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 BACKUP LOAD CALCS 12 5 (N)  GATEWAY  FEEDER  BREAKER EXISTING 225/225A MAIN  PANEL WITH 225 A BUSBAR (N) GATEWAY 3 60 (N) PV+ESS  BREAKER 22 5 MAIN  BREAKER (N) 225A/125A BACKUP  LOADS PANEL  125 MAIN  BREAKER SEC SEC15 20 GDO20 20 AC-2 40 70 10 0 AC-2 SUBFEEDER SUBFEEDER 40 3 0 30 4 0 40 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 RANGE RANGE OVEN KIT DW KIT MICRO GD REFRI LAUNDRY GFI HOOD D/R SPA GFI FAU FAU GFI LIGHTS/RECEPTABLES GFI REFRI LIGHTS/RECEPTABLES PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA  PR-3004737100 SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-4.3 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 PANEL SCHEDULE This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 1 of 8 GFT-OP-11a (22-August-2019) Test Verification of Conformity Verification Number: 104514208CRT-001VOC Applicant Name & Address: Tesla Inc. 3500 Deer Creek Road, Palo Alto, CA 94304 Product Description: Energy Storage System Grid Support Utility Interactive & Standalone Inverter Ratings & Principle Characteristics: See Appendix 2 Models/Type References: 1707000- followed by two numbers; followed by -; followed by one letter. Brand Names: Tesla Relevant Standard(s) / Specification(s): See Appendix 1 Verification Issuing Office Name & Address: Intertek Testing Services NA, Inc. 3933 US Route 11, Cortland, NY 13045 USA Date of Tests: 9/15/2022 to 4/23/2024 Test Report Number(s): 104514208CRT-001, 104514208CRT-001RRF, 104514208CRT-001TRS, 104514208CRT-010, 104514208CRT-012 Additional information in Appendix. Signature Name: Mukund Rana Position: Sr. Staff Engineer Date: 10th May 2024 On the basis of the tests undertaken, the samples of the below product have been found to comply with the requirements of the referenced standards at the time the tests were carried out. This verification is part of the full test report and should be read in conjunction with it. This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 2 of 8 GFT-OP-11a (22-August-2019) Appendix 1: Relevant Standard(s)/Specification(s) Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3] Grid Support Utility Interactive Equipment - Supplement SA to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement SA)] Grid Support Utility Interactive Inverters and Converters Based Upon IEEE 1547:2018 & IEEE 1547.1:2020 - Supplement SB to UL 1741:2021 Ed.3 - Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2021 Ed.3 (Supplement SB)] Energy Storage Systems and Equipment [ANSI/UL 9540:2020 Ed.2+R:09Apr2021] Photovoltaic (PV) DC Arc-Fault Circuit Protection [UL 1699B:2018 Ed.1+R:18May2021] Software in Programmable Components [UL 1998:2013 Ed.3+R:24Sep2018] Tests For Safety-related Controls Employing Solid-state Devices [UL 991:2004 Ed.3+R:09Jun2010] Batteries for Use in Stationary, Vehicle Auxiliary Power and Light Electric Rail (LER) Applications [ANSI/UL 1973:2018 Ed.2] IEEE 1547:2018 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces IEEE 1547a:2020 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces Amendment 1: To Provide More Flexibility for Adoption of Abnormal Operating Performance Category III IEEE 1547.1:2020 - IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated Interfaces Source requirements document UL 1741 (SRD) v2.0 – HECO Electric Rule No.21-2020 Generating Facility Interconnections Default New England Bulk System Area Settings Requirement PRC-024-3 Frequency and Voltage Protection Settings for Generating Resources GOVERNMENT OF PUERTO RICO PUBLIC SERVICE REGULATORY BOARD PUERTO RICO ENERGY BUREAU, Generating Facility and Microgrid Interconnection Regulation (“Regulation”), July 2021 Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2] Safety Functions Incorporating Electronic Technology [CSA C22.2#0.8:2019 Ed.4] This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 3 of 8 GFT-OP-11a (22-August-2019) Appendix 2: Ratings & Principle Characteristics: ➢ Ratings: Models 1707000-xx-y Rated AC Output Power (W) 11500, 10000, 7680, 5750 Rated AC Input Power (W) Charging 5000 Max. Cont. Output Power (W) 11500, 10000, 7680, 5750 Max. Continuous Output PV to AC Power Off-Grid (W) 15400 Max. Cont. Input Power (W) Charging 5000 AC Input / Output Voltage (VL-L) 240 AC Output Frequency (Hz) 60 Max. Cont. Output Current (A) 48, 4 1.6, 32, 24 Max. Cont. Input Current (A) Charging 20.83 Apparent Power rating (VA) 11500, 10000, 7680, 5750 Apparent Power rating (VA) Charging 5000 Normal Category A, B Abnormal Category II, III ➢ Communication Protocol: IEEE 2030.5 protocol ➢ PCH board MD5 Firmware checksum: c5773b136a9ef9be9057302a67258482 ➢ TACO board MD5 Firmware checksum: dcq8OiBXbQWYnK9UhCAjvl02/py2MZymmwAQYOn8jSc= ➢ Grid Support Function Parameters: Tesla used the parameters in the Result reporting form “104514208CRT-001RRF” during the testing of the grid support functions according to UL1741 SB. The parameters that have “blank” as their value are not applicable. ➢ UL 1998 and CSA C22.2#0.8 Evaluation: ECU / Board Rev Software version Checksum UL1998, CSA C22.2#0.8 Compliant* Date of evaluation HVP / -E V2 51705DB5 Yes Apr-19-2024 PWS / -3F V2 34204954 Yes Apr-19-2024 PWS / -1F V2 B3C1375B Yes Apr-19-2024 PWS / -D V2 43FEF523 Yes Apr-19-2024 *Note: Below safety functions were evaluated during the UL1998 and UL 991 evaluation. • List of all UL1998 and UL 991 functions are as follow: o Overcharge o Over-discharge o Over Temperature o Over current o Relay weld, Isolation Monitoring Interruption, PV RSD (UL 1741) o AFCI (UL 1699B) This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 4 of 8 GFT-OP-11a (22-August-2019) SIL-440 QD • Improved Shade Tolerance • Improved Low-Light Performance • Increased Performance in High Temperatures • Enhanced Durability • Reduced Degradation Rate • 25-Year Product Warranty/ 30-Year Performance Warranty N E X T- G E N E R A T I O N N -T Y P E C E L L T E C H N O L O G Y S I L FA BS O L A R . CO M NTC SIL-440 QD MECHANICAL PROPERTIES / COMPONENTS METRIC IMPERIAL Module weight 21 kg ± 0.2 kg 46.3 lbs ± 0.4 lbs Dimensions (H x L x D) 1721 mm x 1133 mm x 35 mm 67.8 in x 44.6 in x 1.37 in Maximum surface load (wind/snow)* 4000 Pa rear load / 5400 Pa front load 83.5 lb/2 rear load / 112.8 lb/2 front load Hail impact resistance ø 25 mm at 83 km/h ø 1 in at 51.6 mph Cells 108 Half cells - N-Type Silicon solar cell 182 mm x 91 mm 108 Half cells - N-Type Silicon solar cell 7.16 in x 3.58 in Glass 3.2 mm high transmittance, tempered, antireflective coating 0.126 in high transmittance, tempered, antireflective coating Cables and connectors (refer to installation manual) 1350 mm, ø 5.7 mm, MC4 from Staubli 53.1 in, ø 0.22 in (12 AWG), MC4 from Staubli Backsheet High durability, superior hydrolysis and UV resistance, multi-layer dielectric film, fluorine-free PV backsheet Frame Anodized aluminum (Black) Junction Box UL 3730 Certified, IEC 62790 Certified, IP68 rated, 3 diodes TEMPERATURE RATINGS Temperature Coe icient Isc 0.04 %/°C Temperature Coe icient Voc -0.24 %/°C Temperature Coe icient Pmax -0.29 %/°C NOCT (± 2 °C) 45 °C Operating temperature -40/+85 °C WARRANTIES Module product workmanship warranty 25 years** Linear power performance guarantee 30 years ≥ 98% end 1st yr ≥ 94.7% end 12th yr ≥ 90.8% end 25th yr ≥ 89.3% end 30th yr SHIPPING SPECS Modules Per Pallet: 26 or 26 (California) Pallets Per Truck 32 or 30 (California) Modules Per Truck 832 or 780 (California) CERTIFICATIONS Product UL 61215, UL 61730, CSA C22.2#61730, IEC 61215, IEC 61730, IEC 61701 (Salt Mist Corrosion), IEC 62716 (Ammonia Corrosion), CEC Listed, UL Fire Rating: Type 2 Factory ISO9001:2015 * Warning. Read the Safety and Installation Manual for mounting specifications and before handling, installing and operating modules. ** 12 year extendable to 25 years subject to registration and conditions outlined under “Warranty” at silfabsolar.com. PAN files generated from 3rd party performance data are available for download at: silfabsolar.com/downloads. ELECTRICAL SPECIFICATIONS 440 Test Conditions STC NOCT Module Power (Pmax) Wp 440 328.0 Maximum power voltage (Vpmax) V 33.41 31.17 Maximum power current (Ipmax) A 13.17 10.52 Open circuit voltage (Voc) V 38.97 36.64 Short circuit current (Isc) A 14.22 11.44 Module e iciency % 22.6% Maximum system voltage (VDC) V 1000 Series fuse rating A 25 Power Tolerance Wp 0 to +10 Measurement conditions: STC 1000 W/m • AM 1.5 • Temperature 25 °C • NOCT 800 W/m • AM 1.5 • Measurement uncertainty ≤ 3% Sun simulator calibration reference modules from Fraunhofer Institute. Electrical characteristics may vary by ±5% and power by 0 to +10 W. 44 . 6 " [ 1 1 3 3 m m ] 11.8" [300.5mm]44.1" [1120mm]11.8" [300.5mm] Ø0 . 1 7 " [ Ø 4 . 2 m m ] ( x 2 ) Gr o u n d i n g H o l e Mounting Hole (x4) Drainage Hole (x8) 43 " [ 1 0 9 3 m m ] 2.4" [60mm]8" [200mm] 53.15" [1350mm] Cable Length 1.4" [35mm] 1. 4 " [ 3 5 m m ] 0.06" [1.5mm] 67.8" [1721mm] 1. 4 " [ 3 5 m m ] 0.5" [12mm] 0. 3 " [ 7 m m ] 0. 6 " [ 1 5 m m ] Si d e Ba c k V i e w Pr o f i l e 1770 Port Drive Burlington WA 98233 USA T +1 360.569.4733 info@silfabsolar.com S I L FA BS O L A R . C O M 7149 Logistics Lane Fort Mill SC 29715 USA T +1 839.400.4338 240 Courtneypark Drive East Mississauga ON L5T 2Y3 Canada T +1 905.255.2501 F +1 905.696.0267 Sales & Customer Support T +1.833.998.6642 Silfab - SIL-440-QD-20250702 No reproduction of any kind is allowed without permission. Data and information is subject to modifications without notice. © Silfab Solar Inc., 2022. Silfab Solar® is a registered trademark of Silfab Solar Inc. SILFAB SOLAR INC. PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA  PR-3004737100 SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-5.0 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 SIGNAGE NOMINAL ESS VOLTAGE VAC LABEL LOCATION: ENERGY STORAGE SYSTEM PER CODE(S): CEC 2022: 706.15(C) 120 240 ENERGY STORAGE SYSTEM DISCONNECT ENERGY STORAGE SYSTEM PREMISES WIRING MAY REMAIN  ENERGIZED AFTER LOSS OF  UTILITY POWER CAUTION! LABEL LOCATION: INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): CEC 2022: 706.15(C) MAXIMUM AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE:           48 AMPS   240     VAC LABEL LOCATION: AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF  INTERCONNECTION. PER CODE(S): CEC 2022: 690.54 PV SYSTEM DISCONNECT WARNING! DO NOT RELOCATE THIS  OVERCURRENT DEVICE POWER SOURCE OUTPUT CONNECTION LABEL LOCATION: ADJACENT TO PV BREAKER AND ESS  OCPD (IF APPLICABLE). PER CODE(S): CEC 2022: 705.12(B)(3)(2) NOTES AND SPECIFICATIONS:   SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE CEC 2022 ARTICLE  110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR  IF REQUESTED BY THE LOCAL AHJ.  SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE  WORDS, COLORS AND SYMBOLS.  LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING  METHOD AND SHALL NOT BE HAND WRITTEN.  LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT  INVOLVED.  SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY  SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.  DO NOT COVER EXISTING MANUFACTURER LABELS. SOLAR PV SYSTEM EQUIPPED  WITH RAPID SHUTDOWN SOLAR  ELECTRIC PV  PANELS LABEL LOCATION: ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE  DISCONNECTING MEANS TO WHICH THE PV SYSTEMS  ARE CONNECTED. TURN RAPID SHUTDOWN  SWITCH TO THE "OFF"  POSITION TO SHUT DOWN PV  SYSTEM AND REDUCE SHOCK  HAZARD IN THE ARRAY. 4" 3" PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C) ELECTRICAL SHOCK HAZARD WARNING TERMINALS ON LINE AND LOAD  SIDES MAY BE ENERGIZED IN  THE OPEN POSITION LABEL LOCATION: INVERTER(S),  AC/DC DISCONNECT(S),  AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): CEC 2022: 690.13(B) ! INVERTER 1 PHOTOVOLTAIC DC DISCONNECT MAXIMUM SYSTEM VOLTAGE:VDC550 LABEL LOCATION: INVERTER(S), DC DISCONNECT(S). PER CODE(S): CEC 2022: 690.53 WARNING: PHOTOVOLTAIC  POWER SOURCE WARNING: PHOTOVOLTAIC  POWER SOURCE LABEL LOCATION: INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,  AT EACH TURN, ABOVE AND BELOW  PENETRATIONS,  ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS. PER CODE(S): CEC 2022: 690.31(D)(2) LABEL LOCATION: INSTALLED WITHIN 3' OF RAPID SHUT DOWN  SWITCH PER CODE(S): CEC 2022: 690.56(C)(2), IFC  2018: 1204.5.3 RAPID SHUTDOWN SWITCH  FOR SOLAR PV SYSTEM WARNING! SOURCES: UTILITY GRID,  BATTERY AND PV SOLAR  ELECTRIC SYSTEM THREE POWER SUPPLY LABEL LOCATION: UTILITY SERVICE METER AND MAIN  SERVICE PANEL. PER CODE(S): CEC 2022: 705.12(C) INVERTER 1 LABEL LOCATION: REQUIREMENT: UL 1741, SECTION 206.1 AND 206.4 LOCATION: MAIN PANEL SIZE: 4.25" X 1.25" PCS CONTROLLED CURRENT SETTING:  180 A  THE MAXIMUM OUTPUT CURRENT FROM THIS SYSTEM IS CONTROLLED ELECTRONICALLY. REFER TO THE MANUFACTURER'S INSTRUCTIONS FOR MORE INFORMATION. WARNING: THIS SENSOR IS PART  OF A POWER CONTROL SYSTEM.  DO NOT REMOVE. REPLACE ONLY  WITH THE SAME TYPE AND RATING. WARNING: THIS SENSOR IS PART  OF A POWER CONTROL SYSTEM.  DO NOT REMOVE. REPLACE ONLY  WITH THE SAME TYPE AND RATING. REQUIREMENT: UL 1741, SECTION 206.3 LOCATION: AROUND THE CT WIRE  BY CLAMP SIZE 4.25" X 0.75" PAGE REV: A 12/22/2025 TED YAMADA 1925 W DEERFIELD RD, SANTA  ANA, CA, 92704 PROJECT NUMBER:   109R-925YAMA  PR-3004737100 SHEET DESIGNER: MEGHA S CUSTOMER RESIDENCE: TEL. (714) 550-6636 APN: 412-531-54 (415) 580-6920 ex3 PV-5.1 #ESTAMP#SSTAMP 2500 WHITE RD. SUITE A, IRVINE CA 92614 PHONE 805.540.7603   FAX 949.215.7778 CA CL #750184 GILBERT CORREIA, C10, C46 SIGNAGE 2 CAUTION: LABELING FORMAT LABELS SHALL BE RED PLASTIC MATERIAL WITH ENGRAVED WHITE LETTERS  MADE OF DURABLE ADHESIVE, WEATHER RESISTANT MATERIAL SUITABLE FOR  THE ENVIRONMENT. LETTERS SHALL BE MINIMUM 3/8" IN SIZE. MULTIPLE SOURCES OF POWER PER CODE(S): CEC 2022: 705.10, 710.10 1925 W DEERFIELD RD, SANTA ANA, CA, 92704 MAIN SERVICE ENTRANCE WITH GATEWAY FEEDER  BREAKER REMOTE DISCONNECT SWITCH GATEWAY WITH PV+ESS BREAKER (EXT) BACKUP LOADS PANEL (EXT) SOLAR PANELS  ON ROOF INVERTER & ENERGY STORAGE(EXT) AC DISCONNECT (EXT)                                   !  "  # $ $% &   !  " '() *$ ' *  " +  '  ,(-./)0    1'      * #1  $       1'  #    2 $" +)   $" +  %   #$% &  ! 1' )+  !  %     #    ' )      #2* $" +1   *   $" +      3 # 43  5 )6 57...*  57...&*  5#+# &8 ! 9 7 '" *      "   1  " "  %    5  # !     )+  9  *    7 ' :$" -  # ;.<2=><2? 0      (  1                           "    +             "     +           #    "    '        "   '   +          +       +               ,22  E  F  '"  "G         H *8 '  "   +    . Sep 16, 2020  5 .>-2=&>2? 0  .&2=2? %!  "   1    +    &2@9=2@? 2@9=2@?    +  /%-;  #  #   #'A3B1$% & 0  )  0%& 71C$><;;>>&< $".+ *#.  * # 8 # =" ?&.-2"=/)?=&.;2*#?   " 'D  '+#/)  *#/  * #  # .2=.>2?  * # 8 .>2=&;.<><2?  * #  # &.<2=<.>>2? ++ )  " ' )  " ++   7   %   # %  0    %  + +)3D %/)0  !   %/)0    1: !' + D  '+ D ) :  + D   ) #   )      !   )   = +  ) #   ? %!  0    %!  +  This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 5 of 8 GFT-OP-11a (22-August-2019) Appendix 3: List of Tested Grid protection / Support Function: Table 3A: Test List -1 Grid protection / Support Function Tested Test Standards Sections and Source Requirement Documents IEEE 1547- 2018 IEEE 1547.1- 2020 UL 1741SB - 2021 CA Rule 21:2020 UL 1741 SRD V2.0 (HECO):2020 OPERATIONAL TEMPERATURE -- 5.3.3.1 SB4.3.5.3 -- Same as 1547- 2018 PROTECTION FROM ELECTROMAGNETIC INTERFERENCE (EMI) TEST 4.11.1 5.8.1 SB4.3.5.8.1 -- Same as 1547- 2018 SURGE WITHSTAND PERFORMANCE TEST 4.11.2 5.8.2 SB4.3.5.8.2 -- Same as 1547- 2018 PARALLELING DEVICE 4.11.3 5.8.3 -- -- Same as 1547- 2018 OVERVOLTAGE TRIP 6.4.1 5.4.2 SB4.3.5.4.2 Electric Rule No. 21 Table Hh.1 Same as 1547- 2018 UNDERVOLTAGE TRIP 6.4.1 5.4.3 SB4.3.5.4.3 Electric Rule No. 21 Table Hh.1 Same as 1547- 2018 OVERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2 SB4.3.5.5.1 & SB4.3.5.5.2 Electric Rule No. 21 Table Hh.2 Same as 1547- 2018 UNDERFREQUENCY TRIP 6.5.1 5.5.1 & 5.5.2 SB4.3.5.5.1 & SB4.3.5.5.2 Electric Rule No. 21 Table Hh.2 Same as 1547- 2018 LOW VOLTAGE RIDE-THROUGH 6.4.2.3 & 6.4.2.5 5.4.4 SB4.3.5.4.4 Electric Rule No. 21 Table Hh.1 Same as 1547- 2018 HIGH VOLTAGE RIDE-THROUGH 6.4.2.4 5.4.7 SB4.3.5.4.7 Electric Rule No. 21 Table Hh.1 Same as 1547- 2018 LOW FREQUENCY RIDE-THROUGH 6.5.2.3 5.5.3 SB4.3.5.5.3 Electric Rule No. 21 Table Hh.2 SRD-UL-1741-SA- V2.0 (HECO) Part II B HIGH FREQUENCY RIDE- THROUGH 6.5.2.4 5.5.4 SB4.3.5.5.4 Electric Rule No. 21 Table Hh.2 SRD-UL-1741-SA- V2.0 (HECO) Part II B RATE OF CHANGE OF FREQUENCY 6.5.2.5 5.5.5 -- -- Same as 1547- 2018 ANTI-ISLANDING PROTECTION - WITH GRID SUPPORT FUNCTIONS ENABLED 8.1 5.10.2 SB4.3.5.10.2 Electric Rule No. 21 Hh.1a According to UL 1741 SA-V2.0 (HECO) TEST FOR VOLTAGE PHASE-ANGLE CHANGE RIDE-THOUGH (VARIATION 1) 6.5.2.6 5.5.6.1 SB4.3.5.5.6 -- Same as 1547- 2018 ENTER SERVICE 4.10 5.6 -- -- Same as 1547- 2018 SYNCHRONIZATION CONTROL FUNCTION TEST FOR EQUIPMENT WITH NO SYNCHRONIZING DISABLE CAPABILITY (VARIATION 3) 6.3 5.7.4 -- -- Same as 1547- 2018 LIMITATION OF DC INJECTION FOR INVERTERS 7.1 5.9 -- Electric Rule No. 21 Hh.2h Same as 1547- 2018 OPEN PHASE 6.2.2 5.11 -- -- Same as 1547- 2018 CURRENT DISTORTION 7.3 5.12 -- Electric Rule No. Same as 1547- This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 6 of 8 GFT-OP-11a (22-August-2019) Grid protection / Support Function Tested Test Standards Sections and Source Requirement Documents IEEE 1547- 2018 IEEE 1547.1- 2020 UL 1741SB - 2021 CA Rule 21:2020 UL 1741 SRD V2.0 (HECO):2020 21 Hh.2g 2018 LIMIT ACTIVE POWER 4.6.2 5.13 -- Electric Rule No. 21 Hh.8 Same as 1547- 2018 CONSTANT POWER FACTOR 5.3.2 5.14.3 SB4.3.5.14.3 Electric Rule No. 21 Hh.2i Same as 1547- 2018 VOLTAGE-REACTIVE POWER (VOLT-VAR) MODE FIXED VREF 5.3.3 5.14.4 SB4.3.5.14.4 Electric Rule No. 21 Hh.2J Same as 1547- 2018 VOLTAGE-REACTIVE POWER (VOLT-VAR) MODE (VREF TEST) 5.3.3 5.14.5 SB4.3.5.14.5 -- Same as 1547- 2018 ACTIVE POWER-REACTIVE POWER MODE (WATT-VAR) 5.3.4 5.14.7 SB4.3.5.14.7 -- Same as 1547- 2018 CONSTANT REACTIVE POWER (VAR) MODE 5.3.5 5.14.8 SB4.3.5.14.8 -- Same as 1547- 2018 VOLTAGE-ACTIVE POWER (VOLT- WATT) MODE 5.4 5.14.9 SB4.3.5.14.9 Electric Rule No. 21 Hh.2.m Same as 1547- 2018 TEST FOR FREQUENCY -DROOP (FREQUENCY-POWER OR FREQUENCY-WATT) CAPABILITY — ABOVE NOMINAL FREQUENCY 6.5.2.7 5.15.2 SB4.3.5.15.2 Electric Rule No. 21 Hh.2.l SRD-UL-1741-SA- V2.0 (HECO) Part II C TEST FOR FREQUENCY -DROOP (FREQUENCY-POWER OR FREQUENCY-WATT) CAPABILITY — BELOW NOMINAL FREQUENCY 6.5.2.7 5.15.3 SB4.3.5.15.3 Electric Rule No. 21 Hh.2.l SRD-UL-1741-SA- V2.0 (HECO) Part II C PRIORITIZATION OF DER RESPONSES 4.7 5.16 SB4.3.5.16 -- Same as 1547- 2018 LOAD REJECTION OVERVOLTAGE (LROV) 7.4 5.17.2 SB4.3.5.17.2 -- Same as 1547- 2018 FAULT CURRENT TESTS FOR INVERTERS 6.2.1 5.18.1 -- -- Same as 1547- 2018 PERSISTENCE OF DER PARAMETER SETTINGS -- 5.19 -- -- Same as 1547- 2018 NORMAL RAMP RATE -- -- -- Electric Rule No. 21 Hh.2k -- NAMEPLATE DATA TEST 10.3 6.4 -- -- Same as 1547- 2018 MONITORING INFORMATION TEST 10.5 6.6 SB4.3.6.6 -- Same as 1547- 2018 MANAGEMENT INFORMATION TEST 10.6 6.7 SB4.3.6.7 -- Same as 1547- 2018 CITY OF SANTA ANA Planning and Building Agency POWERWALL Backup Gateway The Backup Gateway for Tesla Powerwall provides energy management and monitoring for solar self -consumption, time -based control, and backup. The Backup Gateway controls connection to the grid, automatically detecting outages and providing a seamless transition to backup power. When equipped with a circuit breaker, the Backup Gateway can be installed at the service entrance. The Backup Gateway communicates directly with Powerwall, allowing you to monitor energy use and manage backup energy reserves from any mobile device with the Tesla app. PERFORMANCE SPECIFICATIONS AC Voltage (Nominal) 230 V, 120/240 V Feed -In Type Single & Split Phase Grid Frequency 50 and 60 Hz Disconnect Current 200 A Maximum Input Short Circuit Current 10 kA Overcurrent Protection Device' 100-200 A: Service Entrance Rated Overvoltage Category Category IV AC Meter Revenue grade (+/- 1 %) Connectivity Ethernet, Cellular (3G)2, Wi-Fi User Interface Tesla App Operating Modes Support for solar self -consumption, time -based control, and backup Backup Operation Automatic disconnect for seamless backup transition Modularity Supports up to 10 AC -coupled Powerwalls Warranty 10 years Circrnt oreaker ecuired for nstallatio^ at 3eivice entrance. 'CellLlaf --onnecuvity Sublet t to se-v C2 ccve'a3E find ai0l:al sueriq]' , COMPLIANCE INFORMATION Certifications UL 1642, UL 1741, IEC 62109-1, CSA C22.2.107.1 Grid Connection Worldwide Compatibility Emissions FCC Part 15 Class B, ICES 003, IEC 61000-6-3. EN 55024, EN 301489-1, EN 301489-7, EN 301489-17 Environmental RoHS Directive 2011/65/EU, WEEE Directive 2012/19/EU, Battery Directive 2006/66/EC REACH Regulation Seismic AC156, IEEE 693-2005 (high) MECHANICAL SPECIFICATIONS Dimensions 740 mm x 378 min x 129 mm (29.1 inx149inx51 in) Weight 16.4 kg (36 Ibs) Mounting options Wall mount 378 mm 129 mm (14.9 in) (5.1 in) 740 mm (29.1 in) ENVIRONMENTAL SPECIFICATIONS Operating Temperature Operating Humidity (RH) Maximurn Elevation Environment Enclosure Type Ingress Rating -20'C to 50'C (-4`F to 122°F) Up to 100%, condensing 3000 m (9843 ft) Indoor and outdoor rated NEMA 3R IP44 .4 Approved FOR PERMIT ISSUANCE Master ID: Date: TSSLn Powerwall 3 Power Everything 2024 — Powerwall 3 is a fully integrated solar and battery system, designed to accelerate the transition to sustainable energy. Customers can receive whole home backup, cost savings, and energy independence by producing and consuming their own energy while participating in grid services. Once installed, customers can manage their system using the Tesla App to customize system behavior to meet their energy goals. Powerwall 3 achieves this by supporting up to 20 kW DC of solar and providing 11.5 kW AC of continuous power per unit. It has the ability to start heavy loads up to 185 A LRA, meaning a single unit can support the power needs of most homes. Powerwall 3 is designed for mass production,fast and ef𿿿cient installations,easy system expansion,and simple connection to any electrical service. 22024Powerwall 3 Datasheet Solar Technical Speci￿cations Maximum Solar STC Input 20 kW Withstand Voltage 600 V DC PV DC Input Voltage Range 60 — 550 V DC PV DC MPPT Voltage Range 60 — 480 V DC MPPTs 6 Maximum Current per MPPT (Imp)13 A 5 Maximum Short Circuit Current per MPPT (Isc)15 A 5 Powerwall 3 Technical Specifications 1 Typical solar shifting use case. 2 Values provided for 25°C (77°F), at beginning of life. 3.3 kW charge/discharge power. 3 Tested using CEC weighted ef𿿿ciency methodology. 4 The customer is expected to provide internet connectivity for Powerwall 3;cellular should not be used as the primary mode of connectivity. Cellular connectivity subject to network operator service coverage and signal strength. 5 Where the DC input current exceeds the MPPT rating,a jumper can be used to combine two MPPTs into a single input to intake DC current up to 26 A IMP / 30 A ISC. Battery Technical Speci￿cations Nominal Battery Energy 13.5 kWh AC 2 Maximum Continuous Discharge Power 11.5 kW AC Maximum Continuous Charge Power 5 kW AC Output Power Factor Rating 0 -1 (Grid Code con𿿿gurable) Maximum Continuous Current 48 A Maximum Output Fault Current 10 kA Load Start Capability (1 s)185 A LRA Power Scalability Up to 4 Powerwall 3 units supported System Technical Speci￿cations Model Number 1707000-xx-y Nominal Grid Voltage (Input &Output)120/240 VAC Grid Type Split phase Frequency 60 Hz Overcurrent Protection Device 60 A Solar to Battery to Home/Grid Ef￿ciency 89% 1,2 Solar to Home/Grid Ef￿ciency 97.5% 3 Supported Islanding Devices Gateway 3, Backup Switch, Backup Gateway 2 Connectivity Wi-Fi (2.4 and 5 GHz), Dual-port switched Ethernet, Cellular (LTE/4G 4) Hardware Interface Dry contact relay,Rapid Shutdown (RSD)certi𿿿ed switch and 2-pin connector, RS-485 for meters AC Metering Revenue Grade (+/- 0.5%) Protections Integrated arc fault circuit interrupter (AFCI), Isolation Monitor Interrupter (IMI),PV Rapid Shutdown (RSD)using Tesla Mid-Circuit Interrupters Customer Interface Tesla Mobile App Warranty 10 years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eb 3, 2020 : !!761;!: ;: ;:  , 3 4 3 <) =2::5,3< 2#15()<==  . )( *C . */3.%D //  . )( *  . )( //    . --8  (/. 88  .#1 $+  8  . E8 *  - ( .(.3+  .( -8. 4   ,.4.   / (/.     .3 .A 8 '  -2- ./- .3 44428#14 ..3 2 23' $  3( .$  (  . $ / /"C   ' -8( .  (  . E '*- (/ C % */ C  E -8 ../- .C  .  3( . .  (  .   '  .  (  .< / . ( 3 ( 8 = .'.- . ( (   .'.- . (/( (  */( . / 8 / *(.38  . .    (4  . *   . *:6-.  32024Powerwall 3 Datasheet Mechanical Speci￿cations Dimensions 1099 x 609 x 193 mm (43.25 x 24 x 7.6 in) Weight 130 kg (287 lb) Mounting Options Floor or wall mount Powerwall 3 Technical Specifications Environmental Speci￿cations Operating Temperature –20°C to 50°C (–4°F to 122°F) 6 Operating Humidity (RH)Up to 100%, condensing Storage Temperature –20°C to 30°C (–4°F to 86°F), up to 95% RH, non- condensing, State of Energy (SOE): 25% initial Maximum Elevation 3000 m (9843 ft) Environment Indoor and outdoor rated Enclosure Rating NEMA 3R Ingress Rating IP67 (Battery & Power Electronics) IP45 (Wiring Compartment) Pollution Rating PD3 Operating Noise @ 1 m < 50 db(A) typical <62 db(A)maximum Compliance Information Certi￿cations UL 1642, UL 1699B, UL 1741, UL 1741 SA, UL 1741 SB, UL 1741 PCS, UL 3741, UL 1973, UL 1998, UL 9540, IEEE 1547- 2018, IEEE 1547.1, UN 38.3 Grid Connection United States Emissions FCC Part 15 Class B Environmental RoHS Directive 2011/65/EU Seismic AC156, IEEE 693-2005 (high) Fire Testing Meets the unit level performance criteria of UL 9540A 6 Performance may be de-rated at operating temperatures above 40°C (104°F). 609 mm 193 mm 1099 mm 42024Powerwall 3 Datasheet Electrical Speci￿cations Model MCI-1 MCI-2 Nominal Input DC Current Rating (IMP)13 A 13 A Maximum Input Short Circuit Current (ISC)19 A 17 A Maximum System Voltage (PVHCS)600 V DC 1000 V DC 7 Solar Shutdown Device Technical Specifications Environmental Speci￿cations Operating Temperature -40°C to 50°C (-40°F to 122°F) -45°C to 70°C (-49°F to 158°F) Storage Temperature –30°C to 70°C (–22°F to 158°F) –30°C to 70°C (–22°F to 158°F) Enclosure Rating NEMA 4X /IP65 NEMA 4X /IP65 RSD Module Performance Maximum Number of Devices per String 5 5 Control Power Line Excitation Power Line Excitation Passive State Normally Open Normally Open Maximum Power Consumption 7 W 7 W Warranty 25 years 25 years — The Solar Shutdown Device is a Mid-Circuit Interrupter (MCI)and is part of the PV system rapid shutdown (RSD)function in accordance with Article 690 of the applicable NEC. When paired with Powerwall 3, solar array shutdown is initiated by any loss of AC power. Mechanical Speci￿cations Electrical Connections MC4 Connector MC4 Connector Housing Plastic Plastic Dimensions 125 x 150 x 22 mm (5 x 6 x 1 in) 173 x 45 x 22 mm (6.8 x 1.8 x 1 in) Weight 350 g (0.77 lb) 120 g (0.26 lb) Mounting Options ZEP Home Run Clip M4 Screw (#10) M8 Bolt (5/16") Nail / Wood screw Wire Clip Compliance Information Certi￿cations UL 1741 PVRSE, UL 3741, PVRSA (Photovoltaic Rapid Shutdown Array) RSD Initiation Method External System Shutdown Switch or Powerwall 3 Enable Switch 7 Maximum System Voltage is limited by Powerwall to 600 V DC. UL 3741 PV Hazard Control (and PVRSA)Compatibility See Powerwall 3 Installation Manual 52024Powerwall 3 Datasheet Gateway 3 8 Only Eaton CSR or BWH main breakers are 25 kA rated. Performance Speci￿cations Model Number 1841000-01-y Nominal Grid Voltage 120/240 V AC Grid Con￿guration Split phase Grid Frequency 60 Hz Continuous Current Rating 200 A Maximum Supply Short Circuit Current 22 kA with Square D or Eaton main breaker 25 kA with Eaton main breaker 8 IEC Protective Class Class I Overvoltage Category Category IV Mechanical Speci￿cations Dimensions 660 x 411 x 149 mm (26 x 16 x 6 in) Weight 16.3 kg (36 lb) Mounting options Wall mount Environmental Speci￿cations Operating Temperature –20°C to 50°C (–4°F to 122°F) Operating Humidity (RH)Up to 100%, condensing Maximum Elevation 3000 m (9843 ft) Environment Indoor and outdoor rated Enclosure Type NEMA 3R Compliance Information Certi￿cations UL 67, UL 869A, UL 916, UL 1741 PCS, CSA 22.2 107.1, CSA 22.2 29 Emissions FCC Part 15, ICES 003 — Tesla Gateway 3 controls connection to the grid in a Powerwall system, automatically detecting outages and providing seamless transition to backup power. It provides energy monitoring that is used by Powerwall for solar self-consumption, time-based control, and backup operation. 411 mm 660 mm 149 mm AC Meter Revenue accurate (+/- 0.5%) Communication CAN User Interface Tesla App Backup Transition Automatic disconnect for seamless backup Overcurrent Protection Device 100–200 A Service entrance rated Eaton CSR, BWH, or BW, or Square D QOM breakers Internal Panelboard 200 A 8-space/16 circuit breakers Eaton BR, Siemens QP, or Square D HOM breakers rated to 10–125A Warranty 10 years 62024Powerwall 3 Datasheet Backup Switch 9 Breaker maximum supply short circuit current rating must be equal to or greater than the available fault current. Performance Speci￿cations Model Number 1624171-xx-y Continuous Load Rating 200 A, 120/240 V split phase Maximum Supply Short Circuit Current 22 kA with breaker 9 Communication CAN AC Meter Revenue accurate (+/- 0.5%) Expected Service Life 21 years Warranty 10 years Mechanical Speci￿cations Dimensions 176 x 205 x 74 mm (6.9 x 8.1 x 2.9 in) Weight 2.8 lb Meter and Socket Compatibility ANSI Type 2S, ringless or ring type External Service Interface Contactor manual override 10 Reset button Conduit Compatibility 1/2-inch NPT Environmental Speci￿cations Operating Temperature –40°C to 50°C (–40°F to 122°F) Storage Temperature –40°C to 85°C (–40°F to 185°F) Enclosure Rating NEMA 3R Pollution Rating PD3 Compliance Information Safety Standards USA: UL 414, UL 414 SB, UL 2735, UL 916, CA Prop 65 Emissions FCC, ICES 10 Manually overrides the contactor position during a service event. — The Tesla Backup Switch controls connection to the grid in a Powerwall system, and can be easily installed behind the utility meter or in a standalone meter panel downstream of the utility meter. The Backup Switch automatically detects grid outages, providing a seamless transition to backup power. It communicates directly with Powerwall, allowing home energy usage monitoring from any mobile device with the Tesla app. 204.86 74 176 mm 205 mm 74 mm 72024Powerwall 3 Datasheet Backup Gateway 2 Performance Speci￿cations Model Number 1232100-xx-y AC Voltage (Nominal)120/240 V Feed-in Type Split phase Grid Frequency 60 Hz Current Rating 200 A Maximum Supply Short Circuit Current 10 kA 11 Overcurrent Protection Device 100 - 200 A, Service entrance rated 9 Overvoltage Category Category IV Internal Primary AC Meter Revenue accurate (+/- 0.2%) Internal Auxiliary AC Meter Revenue accurate (+/- 2%) Primary Connectivity Ethernet, Wi-Fi Secondary Connectivity Cellular (3G, LTE/4G) 12 Mechanical Speci￿cations Dimensions 660 x 411 x 149 mm (26 x 16 x 6 in) Weight 20.4 kg (45 lb) Mounting options Wall mount, Semi-Bush mount Environmental Speci￿cations Operating Temperature –20°C to 50°C (–4°F to 122°F) Operating Humidity (RH)Up to 100%, condensing Maximum Elevation 3000 m (9843 ft) Environment Indoor and outdoor rated Enclosure Type NEMA 3R Compliance Information Certi￿cations UL 67, UL 869A, UL 916, UL 1741 PCS, CSA 22.2 0.19, CSA 22.2 205 Emissions FCC Part 15, ICES 003 411 mm 660 mm 149 mm 11 When protected by Class J fuses, Backup Gateway 2 is suitable for use in circuits capable of delivering not more than 22kA symmetrical amperes. 12 Cellular connectivity subject to network operator service coverage and signal strength. — Backup Gateway 2 controls connection to the grid when paired with Powerwall 3, automatically detecting outages and providing seamless transition to backup power. Backup Gateway 2 also provides energy metering for solar self-consumption, time-based control, and backup operation. In this system con𿿿guration,Powerwall 3 acts as the Site Controller,with the Backup Gateway 2 Site Controller disabled. User Interface Tesla App Operating Modes Support for solar self- consumption, time-based control, and backup Backup Transition Automatic disconnect for seamless backup Modularity Supports up to 10 AC- coupled Powerwalls Optional Internal Panelboard 200 A 6-space / 12 circuit breakers Siemens QP or Square D HOM breakers rated 10 - 80A or Eaton BR breakers rated 10 - 125A Warranty 10 years 82024Powerwall 3 Datasheet Powerwall 3 Example System Configurations Powerwall 3 with Backup Switch Whole Home Backup Powerwall 3 with Gateway 3 Whole Home Backup Powerwall 3 with Backup Gateway 2 Partial Home Backup This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 7 of 8 GFT-OP-11a (22-August-2019) Table 3B: Test List -2 Test Description CSA C22.2#107.1:2016 Ed. 4 CSA C22.3#9:2020 Ed 2 Screw Tightening Torque Test 3.6.3 -- Impedance Test 105.1/10.5.2 -- Continuity Test 4.1 -- Output Power Factor 4.2 -- Voltage Harmonics for stand alone 15.3.2.1 -- Frequency 10.5.4 -- Stand-alone inverter dc output short-circuits current contribution 10.5.5 -- Normal ramp rate -- 7.2.3.4.2 / 8.3.12.2.3 Flicker -- 7.2.2 / 8.3.13 Test for constant reactive power (var) mode 7.2.3.3.3 / 8.3.12.2.2 This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Page 8 of 8 GFT-OP-11a (22-August-2019) Appendix 4: Revision Summary Date / Project Engineer Comments 15-Feb-2023 Dipesh Patel Original issue date 8-Mar-2023 / G104200718 Dipesh Patel Added UL 1699B, UL 1998 and UL 991 standards 24-Mar-2023/ G104200718 Dipesh Patel Added UL 1973 standard. Added normal and abnormal category in ratings table. 18-Apr-2023 / G104200718 Dipesh Patel Added additional factory settable nameplate ratings rated output active power (W): 9600, 7680, 5750; Max. Continuous output power (W): 9600, 7680, 5750; Max. Cont. Output Current (A): 40, 32, 24; Apparent Power rating (VA): 9600, 7680, 5750 Added Puerto Rico Interconnection regulation as it refers to UL 1741 and IEEE 1547-2018. 1-May-2024 / G104514208 Mukund Rana A) Added standards. Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4+U1] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] Photovoltaic Rapid Shutdown Systems [CSA C22.2#330:2023 Ed.2] Interconnection of Distributed Energy Resources and Electricity Supply Systems [CSA C22.3#9:2020 Ed.2] B) Update CSA C22.2#0.8 standard C) added Table 3B: Test List -2 sunrun Jan 5, 2026 RE: Authorized Employees: Caitlyn Hernandez To Whom It May Concern: CITY OF SANTA ANA Planning and Building Agency may, lS. Approved FOR PERMIT ISSUANCE Master ID: Date: This letter authorizes Caitlyn Hernandez to sign their name on behalf of Sunrun Installation Services, Inc (California CSLB C-10 License #: 750184) in regards to signatory required for obtaining a city or county business license, and any signatures required for applying and obtaining a building permit. If you have any questions in relation to this matter, please contact Sunrun Installation Services, Inc at (559) 455-7302. Effective Date: Jan 5, 2026 Expiration Date: ec 31, 2 26 f Gil ert Correia Email: gilbert.correia@sunrun.com Manager, Field Efficiency & Quality Responsible Managing Employee, CSLB C-10 License #: 750184 California Jurat with Affiant Statement A notary public or other officer completing this certificate verifies only the identity of the individual who signed the document, to which this certificate is attached, and not the truthfulness, accuracy, or validity of that document. State of California County of �?a � Subscribed and sworn to (or affirmed) before me on this day of7:�AnQQ,64, 20 :-I 0 by Gilbert Correia, proved to me on the basis of satisfactory evidence to be the person who appeared before me. a, ABIGAIL CISNEROS d' Notary Public - California W Fresno County Commission k 2533296 `•��"' My Comm. Expires Oct 21, 2029 Signature: Place Notary Seal Above Notary Public 600 California St, . Suite 1800 1 San Francisco. CA 94108 Article 220 - Service/Feeder calculation for (address):Job Code 1925 W Deerfield Rd Santa Ana CA USA 92704 109R-925YAMA Section 220.83 Existing Dwelling Unit Part #1 - Section 220.83(B)(1) General Lighting/Receptacles @ 3 VA per sq ft: Building Square Footage VA (watts)Amps House 3759 11277 46.99 Amps Box A (VA) 46.99 11277Total for Part #1: Part #2 - Section 220.83(B)(2),(4) a, b, c, d - Appliances and Dedicated Circuits: Dedicated Circuit Size in VA Dedicated Circuit Size in VA Oven 5760 N/A Range 7680 N/A Disposal 600 N/A Dishwasher 1000 N/A Microwave 1600 N/A Refrigerator 1000 N/A Laundry 1500 N/A Appliance Circuit(s)3000 N/A N/A N/A N/A Amps Box B (VA) N/A 92.25 22140Total for Part #2: Total VA from Parts #1 and #2 combined:Box A + Box B = 33417 Total VA 33417 First 8000 VA @ 100% 8000 Remaining VA @ 40% Remaining VA = 25417 25417 x 40% = 10166.8 VA Adding First 8,000 VA 8000 VA 18166.8 VA 75.7 Amps Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits: Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits: Part #3 - Section 220.83(B) Heating and A/C loads: 100% of all the Heating or A/C loads in VA: 11520 VA 100% of all the Heating or A/C loads in Amps: 48 A *Combine the larger loads of either the Heating or the A/C loads togther Totals from all Parts#EStamp VA Volts Amps Parts #1 & #2 18166.8 240 75.7 Part #3 11520 240 48 Total VA for all Parts: 29686.8 Totals Service/Feeder Load 123.7 #EStamp Panel 1 of 1 Bus Rating: 225 Main Rating: 125 Panel % of Sq.Ft: 100%Panel % of 100% VA: 100% A/C Unit - 240V 7680 Dishwasher 1000 Air Handler/FAU - 120V 1920 Microwave 1600 Air Handler/FAU - 120V 1920 Refrigerator 1000 Oven 5760 laundry 1500 Range 7680 Appliance Circuit 1 1500 Disposal 600 Appliance Circuit 2 1500 Itemized House and 240V Loads for Panel: (VA) Fed by: Panel 1 Load Calc: (This Panel) 123.7 Total Load Calc: 113.81 Article 220 - Service/Feeder calculation for (address):Job Code 1925 W Deerfield Rd Santa Ana CA USA 92704 109R-925YAMA Section 220.83 Existing Dwelling Unit Part #1 - Section 220.83(B)(1) General Lighting/Receptacles @ 3 VA per sq ft: Building Square Footage VA (watts)Amps House 3759 11277 46.99 Amps Box A (VA) 46.99 11277Total for Part #1: Part #2 - Section 220.83(B)(2),(4) a, b, c, d - Appliances and Dedicated Circuits: Dedicated Circuit Size in VA Dedicated Circuit Size in VA Unknown 2-Pole Load 32640 N/A Oven 5760 N/A Range 7680 N/A Disposal 600 N/A Dishwasher 1000 N/A Microwave 1600 N/A Refrigerator 1000 N/A Laundry 1500 N/A Appliance Circuit(s)3000 N/A N/A Amps Box B (VA) N/A 228.25 54780Total for Part #2: Total VA from Parts #1 and #2 combined:Box A + Box B = 66057 Total VA 66057 First 8000 VA @ 100% 8000 Remaining VA @ 40% Remaining VA = 58057 58057 x 40% = 23222.8 VA Adding First 8,000 VA 8000 VA 31222.8 VA 130.09 Amps Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits: Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits: Part #3 - Section 220.83(B) Heating and A/C loads: 100% of all the Heating or A/C loads in VA: 19200 VA 100% of all the Heating or A/C loads in Amps: 80 A *Combine the larger loads of either the Heating or the A/C loads togther Totals from all Parts#EStamp VA Volts Amps Parts #1 & #2 31222.8 240 130.09 Part #3 19200 240 80 Total VA for all Parts: 50422.8 Totals Service/Feeder Load 210.09 #EStamp Panel 1 of 2 Bus Rating: 225 Main Rating: 225 Panel % of Sq.Ft: 0%Panel % of 100% VA: 49.41% A/C Unit - 240V 7680 Unknown 2-Pole Load 19200 Unknown 2-Pole Load 13440 Itemized House and 240V Loads for Panel: (VA) Not Fed by other panels Feeds: Panel 2 113.81 Load Calc: (This Panel) 96.28 Total Load Calc: 210.09 Panel 2 of 2 Bus Rating: 225 Main Rating: 125 Panel % of Sq.Ft: 100%Panel % of 100% VA: 50.59% A/C Unit - 240V 7680 Dishwasher 1000 Air Handler/FAU - 120V 1920 Microwave 1600 Air Handler/FAU - 120V 1920 Refrigerator 1000 Oven 5760 laundry 1500 Range 7680 Appliance Circuit 1 1500 Disposal 600 Appliance Circuit 2 1500 Itemized House and 240V Loads for Panel: (VA) Fed by: Panel 1 Load Calc: (This Panel) 113.81 Total Load Calc: 113.81 12/22/2025 RE: Structural Certification for Installation of Residential Solar TED YAMADA:1925 W DEERFIELD RD, SANTA ANA, CA, 92704 Attn: To Whom It May Concern Design Criteria Code 2022 California Building Code (ASCE 7-16) Risk category II Wind Load (component and Cladding) Roof Dead Load Dr 10 psf V 96 mph PV Dead Load DPV 3 psf Exposure C Roof Live Load Lr 20 psf Ground Snow S 0 psf If you have any questions on the above, please do not hesitate to call. Sincerely, Eugene Munyanziza, P.E. EV Engineering, LLC projects@evengineersnet.com Signed 12/22/2025 http://www.evengineersnet.com Exp: 06/30/2026 Structural evalution were done in accordance with applicable building codes and considering design criteria below: This Letter is for a structural evaluation of the existing structure at the address above. The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels as well as the attachment of solar panel to the existing framing. After review, we concluded that the existing structure is adequate to support the proposed solar panel installation. Gravity load increase did not exceed 5% and therefore, this install meets the prescriptive compliance requirements of the applicable IEBC. projects@evengineersnet.com http://www.evengineersnet.com Wind (Uplift Check) DCR check= 0.84 CONNECTION PASS Vertical Load Resisting System Design Gravity Load Check Roof Dead Load Roof Dead Load 10.0 psf PV Dead Load 3.0 psf Roof Live Load 20 psf PV Roof Live Load 0 psf Snow Load 0 psf IEBC Check Existing With PV Roof Dead Load (D) 10.0 13.0 psf Roof Live Load (Lr) 18.4 0.0 psf Roof Snow Load (S) 0.0 0.0 psf Cs= 1 0.78 Existing With PV (D + Lr) = 22.7 14.4 psf (D + S) = 8.7 11.3 psf Maximum Gravity Load 22.7 14.4 psf Load Increase (%)-36.4% OK IBC Provision 2018 Siesmic Loads Check Roof Dead Load 10 psf % or Roof with Pv 8.2% Dpv and Racking 3 psf Average Total Dead Load 10.2 psf Increase in Dead Load 1.2%OK Limits of Scope of Work and Liability *The requirements of Section 806.2 of the 2018 IEBC are met and the structure is permitted to remain unaltered. The Existing structure is assumed to have been designed and constructed following appropriate codes and to have appropriate permits. The analysis was according to applicable building codes, professional engineering and design experience, opinions and judgments. This evalution produced for this structure's assessment is only for the proposed solar panel installation referenced in the stamped plan set and were made according to generally recognized structural analysis standards and procedures. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and spans. Contractor shall also verify that there is framing damage or deficiencies. If observed, the EOR must be notified before install. The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. projects@evengineersnet.com http://www.evengineersnet.com Rev: 8/29/19 SOL-01 CBC 2016 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org RESIDENTIAL PHOTOVOLTAIC CHECKLIST 1925 W Deerfield Rd Santa Ana CA USA 92704 sunrun 750184 caitlyn hernandez 3854005019 oc_permit@sunrun.com 1.21.26