HomeMy WebLinkAbout502 & 516 E Alton Ave - PlanE-0.1 NOTES & SYMBOLS ABBREVIATIONS SYMBOLSGENERAL NOTES COPYRIGHT LEWIS ROSS ASSOCIATES FILE NAME: SHEET NUMBER: DESCRIPTION: PROJECT NAME: DRAWN BY: SCALE: DATE: PROJECT NO.: CLIENT: PROJECT NO. PROJECT: AS SHOWN OST ALUMINUM PRECISION PRODUCTS 04-14-2025 24-121 NEC ELECTRIC INC. 24-121 ALUMINUM PRECISION PRODUCT ADDRESS: 502 E. ALTON AVE. 516 E. ALTON AVE. SANTA ANA, CA 92707 17015 SO. BROADWAY ST. GARDENA, CA 90248 REV DESCRIPTION DATE 9401 RESEDA BLVD. SUITE 200 NORTHRIDGE, CA 91324 PHONE: (818) 886-2190 FAX: (818) 886-2131 PLAN CHECK 11-13-2024- Lewis Ross Dropbox\Projects\2020\20-180 17806 Lassen\LRA Drawings PLAN CHECK CORRECTIONS 01-16-20251 CORRECTIONS 04-14-20252 SCOPE OF WORK ELECTRICAL SHEET INDEX SHEET NO.DESCRIPTION E-0.1 NOTES & SYMBOLS E-0.2 SITE PLAN E-0.3 SINGLE LINE DIAGRAM E-0.4 PANEL SCHEDULES E-2.0 502 BUILDING ELECTRICAL POWER PLAN E-2.1 516 BUILDING ELECTRICAL POWER PLAN E-6.0 SCE APPROVED CONSTRUCTION DRAWINGS 2 Elect #'s 20185340-41 APPROVALS: PLNG - V. Estrada ELECT - M. Smith 22' 7' 17'9' 3' 6' 192' 209' 217' 220' 516 E. ALTON AVE. BUILDING TWO N.I.C. EXISTING BUILDING 516 E. ALTON AVE. BUILDING 3 N.I.C. EXISTING BUILDING 516 E. ALTON AVE. EXISTING BUILDING 502 E. ALTON AVE. EXISTING BUILDING 528 E. ALTON AVE. N.I.C. EXISTING1 1679884E 45'Class C4 EX: 1- POLE 45' CLASS 4 WOOD POLE CO: 1-5" (33") 1679884E TO P5539669 45° SWEEP 12.5' RADIUS RISER TO BE PLACED ON THE N/W QUADRANT 16 79 88 4E CO:P5539669 2 PME 48"X72" PAD CO: 1- S SB 4'X6' W/2'-6"X4' BOX FOR PMH-5 *STRUCTURE FOR FUTURE USE. CUSTOMER/CONTRACTOR TO INSTALL DIAMOND PLATE LID WITH SCE ON TOP AND SECURE WITH PENTA HEAD BOLTS. GRADE RINGS MAY BE REQUIRED IN ORDER TO MAINTAIN MINIMUM CONDUIT DEPTH AND ALIGNMENT. 3 CO:P5539670 SLAB BOX 10'X12' CONCRETE CO: 1- S SB 10'X12' W/TUB 5'X8'6"X5' 10'X12' CONCRETE SLAB BOX LID WITH 5'X8'6"X5' CONCRETE BOX. GRADE RINGS MAY BE REQUIRED IN ORDER TO MAINTAIN MINIMUM CONDUIT DEPTHS AND ALIGNMENT. 90° SWEEP 12.5' RADIUS CO: 1-5" (15') P5539669 TO 95539670 1679885E 45 EX: 350 AERIAL SERVICE CABLE REMAIN IN PLACE UNTIL NEXT WORK ORDER PHASE 1679884E 45 3/250/12 480 3P 3W 13X6 RACK CO: 7-4" (61') P5539670 TO SWITCHGEAR CO: 7-4" (50') P5539670 TO SWITCHGEAR 502 E ALTON AVE NEW 4000A PANEL 277/480 3P 4W EXISTING MAINTENANCE BUILDING 502 E. ALTON AVE BUILDING "B" MS PB 1 2 4 3 5 "MS1" 600 AMP MAIN SERVICE 45' 7' 9' 3' 6' CONCRETE ENVELOPE 7'-0" LONG, 4" GRC., CONCRETE-FILLED POSTFINISHED FLOOR 36 " 1 COPYRIGHT LEWIS ROSS ASSOCIATES FILE NAME: SHEET NUMBER: DESCRIPTION: PROJECT NAME: DRAWN BY: SCALE: DATE: PROJECT NO.: CLIENT: PROJECT NO. PROJECT: AS SHOWN OST ALUMINUM PRECISION PRODUCTS 04-14-2025 24-121 NEC ELECTRIC INC. 24-121 ALUMINUM PRECISION PRODUCT ADDRESS: 502 E. ALTON AVE. 516 E. ALTON AVE. SANTA ANA, CA 92707 17015 SO. BROADWAY ST. GARDENA, CA 90248 REV DESCRIPTION DATE 9401 RESEDA BLVD. SUITE 200 NORTHRIDGE, CA 91324 PHONE: (818) 886-2190 FAX: (818) 886-2131 PLAN CHECK 11-13-2024- Lewis Ross Dropbox\Projects\2020\20-180 17806 Lassen\LRA Drawings PLAN CHECK CORRECTIONS 01-16-20251 CORRECTIONS 04-14-20252 E-0.2 SITE PLAN SITE PLAN 1" = 30'-0"2 ENLARGED VIEW AT MAIN SERVICE 1/8"=1'-0" 3 DETAIL "A" BARRIER POSTS AT MAIN SERVICE 3/8"=1'-0" FEEDER AND STRUCTURE SCHEDULE 1 NEW 3" PVC SCH. 40 WITH 4#3/0 AND 1#6 THWN CU 2 NEW 200A/3P, SERVICE RATED DISCONNECT. NEMA 3R-RAINTIGHT 3 NEW TWO 4" PVC SCH. 40 WITH 4#350 MCM AND 1#1 THWN CU EACH 4 NEW TWO 3" EMT WITH 4#350 MCM 1#1 THWN CU EACH 5 NEW 600A/3P, SERVICE RATED DISCONNECT. NEMA 3R-RAINTIGHT M 'M''1' PROPOSED NEW "MS-502" 4000 AMP MAIN SERVICE 480Y277V, 3PH, 4-WIRE NEMA-3R, RAINTIGHT 100,000 AIC MCC T NEW "MS1" 600 AMP DISTRIBUTION PANEL 480Y277V, 3PH, 4-WIRE NEMA-1 INDOOR 42,000 AIC MINIMUM T 600A BUS 4000 AMP BUS 400A 3P 200A 3P 400A 3P 200A 3P 600A 3P 200A 3P 200A 3P 200A 3P 600A 3P 1 2 3 4 5 6 7 8 9 10 12 10 2 1 4 7 2 6 4000A UGPS W/LUGS 4000A 3P 100K ISC GFP 3/4" - 1#3/0 CU TO C.W. PIPE AND TO GROUND RODS CABLE TRENCH PROPOSED 10'X12' CUSTOMER SLAB BOX ONE 5" PROPOSED 5'X11' SWITCH PAD ONE 5" PVC SCH. 40 TO SCE SERVICE POINT PRESS #9 A PRESS #9 B 200A 480Y 277V 3PH, 4W MAINT. BUILDING PRESS 7 800A 480V 3PH, 3W A PRESS #6B PRESS #6A PRESS #5B SEE MS1 357.1A 456.2A 96.0A 226.0A 90.1A 522.2A 100.3A 124.0A 116.3A 318.52A UTILITY COMPANY CONTRIBUTION TO THE AVAILABLE FAULT CURRENT WILL NOT EXCEED 54,400 AMPS 1735.8 KW X 1.25 2,169.75 KVA (PEAK DEMAND BRANCH # 1 - #11) CEC 220.87 2,169.75 KVA 480 3V =2613 AMPS 397.7 AMPS (BRANCH #12) 3,010.7 AMPS NEW 16"X16"X4" (MINIMUM) PULL BOX SEE ABOVE 3/4" -1#3/0 CU TO C.W. PIPE AND TO GROUND RODS (AT 516 BUILDING ) NEW 600/3P SERVICE RATED DISCONNECT WITH (3) 600 AF. NEMA 3R 8 C 9 10 9 11 1 2 3 4 600 A 3P MAIN 42K ISC 50 A 3P 42K ISC 400 A 3P 42K ISC 70 A 3P 42K ISC 200 A 3P 42K ISC 7 37.5 KVA 15 KVA HEAT TREAT OVEN 4A OFFICE 47.1A 48.8A 175.0A 211.6 KW X 1.25 264.5 KVA (PEAK DEMAND) 264.5 KVA/480 3 V = 318.52 AMPS PNL LA2 #4 CU 100AMP 14 3P 200AMP 3P 15 #4 CU T 25 KVA #4 CU 14 PNL HA1 PNL LA1 PNL LB PNL HA T 75 KVA #4 CU PNL HA2 502B PNL 502A HA 600A 3P PNL 502B HB 07 150A 3P PRESS #5A 12 100A 3P 200 AMP 75A85A PNL 502A OVEN 2 200A 3P L=145' VD=.35% L=155' VD=.5% L=65' VD=.21% L=145' VD=.40% L=150' VD=.36% L=170' VD=.44% L=130' VD=.46% L=175' VD=.50% L=180' VD=.64% L=185' VD=.62% L=190' VD=.62% L=220' VD=.62% 11 200AMP 3P 2 PNL B1 100AMP 3P #4 CU PNL LB1 200AMP 3P 2"C-4#3/0 THHN CU (EMT ) 1#4 GRD (EMT) LOAD CALCULATION LOAD CALCULATION MS-502 MS1 L-15' 28,471 A 26,406 A 4000 AMP SERVICE IS ADEQUATE MS1 IS ADEQUATE AIC =44,000 L-10' 37,840 A 23,798 A 42,340 A 17,123 A 17,129 A 23,774 A B 15,285 A 33,818 A 15,868 A 14,656 A 14,656 A 10,959 A 28,471 A 8 PB 50AMP 3P 70AMP 3P 16 17 (N)(N)(E) (N) (N) (N) (E)(E) (E) (E) (E) (E)(E)(E)(E) (N) (N) (E) (E) (N) (N) (E) (E) (E) (E) (E) (E) (E) (N)(N) 1"C-3#2 THHN CU. 1#8 CU GRD T-LB1 75 KVA 480V-120/208V, 3Ø, 4W 150AMP 3P PNL LB2 125AMP 3P (E) 1 COPYRIGHT LEWIS ROSS ASSOCIATES FILE NAME: SHEET NUMBER: DESCRIPTION: PROJECT NAME: DRAWN BY: SCALE: DATE: PROJECT NO.: CLIENT: PROJECT NO. PROJECT: AS SHOWN OST ALUMINUM PRECISION PRODUCTS 04-14-2025 24-121 NEC ELECTRIC INC. 24-121 ALUMINUM PRECISION PRODUCT ADDRESS: 502 E. ALTON AVE. 516 E. ALTON AVE. SANTA ANA, CA 92707 17015 SO. BROADWAY ST. GARDENA, CA 90248 REV DESCRIPTION DATE 9401 RESEDA BLVD. SUITE 200 NORTHRIDGE, CA 91324 PHONE: (818) 886-2190 FAX: (818) 886-2131 PLAN CHECK 11-13-2024- Lewis Ross Dropbox\Projects\2020\20-180 17806 Lassen\LRA Drawings PLAN CHECK CORRECTIONS 01-16-20251 CORRECTIONS 04-14-20252 E-0.3 SINGLE LINE DIAGRAM SINGLE LINE DIAGRAM N.T.S. FEEDER SCHEDULE TAG FEEDER 1 3 1/2" EMT WITH 3#500 MCM AND 1#3 THHN CU 2 2 1/2" EMT WITH 3#3/0 AND 1#6 THHN CU 3 THREE 3 1/2" EMT WITH 3#400 MCM AND 1#2/0 THHN CU EACH (TRIPLE PARALLEL RUN) 4 3" PVC SCH. 40 WITH 4#3/0 AND 1#6 THWN CU 5 THREE 3" EMT WITH 3#300 MCM AND 1#1/0 THHN CU EACH(TRIPLE PARALLEL RUN) 6 TWO 4" PVC SCH. 40 WITH 4#350 MCM AND 1#1 THWN CU EACH (PARALLEL RUN) 7 TWO 3" EMT WITH 3#350 MCM AND 1#1 THHN CU EACH (PARALLEL RUN) 8 TWO 3" EMT WITH 4#350 MCM THWN CU EACH AND 1#1 THHN CU 9 1 1/2" EMT WITH 3#4 AND 1#8 THHN CU 10 4" EMT WITH 3#600 MCM AND 1#2/0 THHN CU 11 2" EMT WITH 3#3/0 AND 1#6 THHN CU 12 2"-3#1/0, 1#6 THHN CU 13 2"-4#3/0, 1#6 THHN CU 14 1 1/4"C EMT 4#2 THHN CU, 1#8 GRD CU 15 2" EMT 4#3/0 THHN CU, 1#1 THHN CU 16 1"C 4#8 THHN CU EMT, 1#8 THHN CU 17 1 1/4"C 4#4 THHN CU EMT, 1#8 THHN CU TABLE OF APPROXIMATE AVAILABLE FAULT CURRENTS NODE LOCATION AAFC A PANEL "M"15,285A B MCC-1 33,818A C MS1 28,471A PANEL "M" TO BE BRACED/RATED FOR 22,000 AIC MINIMUM. MCC-1 TO BE BRACED/RATED FOR 35,000 AIC MINIMUM. MS1 TO BE BRACED/RATED FOR 42,000 AIC MINIMUM. REFERENCE NOTES CHANGE EXISTING 800AMP BREAKER TO A 3 POLE, 600AMP, 100 KAIC BREAKER.ITEMS MARKED (N) OR SHOWN DARK ARE NEW. ITEMS SHOWN LIGHTS OR MARKED (E) ARE EXISTING. FAULT CURRENT IS 54,400 AIC. 2 CHANGING THE TRIP PLUG TO 600AMP. 2 ALL LOADS ARE EXISTING AND IN OPERATION. FED FROM THE EXISTING 1600A OVERHEAD SERVICE. BUILDING GROUND TO BE BONDED TO THE ECG OF THE THE FEEDER ONLY. THE GROUND FAULT PROTECTION SYSTEM SHALL BE PERFORMANCE TESTED WHEN FIRST INSTALLED ON SITE. THIS TESTING SHALL BE CONDUCTED BY A QUALIFIED PERSON(S) USING A TEST PROCESS OF PRIMARY CURRENT INJECTION, IN ACCORDANCE WITH INSTRUCTIONS THAT SHALL BE PROVIDED WITH THE EQUIPMENT. A WRITTEN RECORD OF THIS TESTING SHALL BE MADE AND SHALL BE AVAILABLE TO THE AUTHORITY HAVING JURISDICTION. CEC 230.95(C) 2 2 2 2 COPYRIGHT LEWIS ROSS ASSOCIATES FILE NAME: SHEET NUMBER: DESCRIPTION: PROJECT NAME: DRAWN BY: SCALE: DATE: PROJECT NO.: CLIENT: PROJECT NO. PROJECT: AS SHOWN OST ALUMINUM PRECISION PRODUCTS 04-14-2025 24-121 NEC ELECTRIC INC. 24-121 ALUMINUM PRECISION PRODUCT ADDRESS: 502 E. ALTON AVE. 516 E. ALTON AVE. SANTA ANA, CA 92707 17015 SO. BROADWAY ST. GARDENA, CA 90248 REV DESCRIPTION DATE 9401 RESEDA BLVD. SUITE 200 NORTHRIDGE, CA 91324 PHONE: (818) 886-2190 FAX: (818) 886-2131 PLAN CHECK 11-13-2024- Lewis Ross Dropbox\Projects\2020\20-180 17806 Lassen\LRA Drawings PLAN CHECK CORRECTIONS 01-16-20251 CORRECTIONS 04-14-20252 E-0.4 PANEL SCHEDULES PANEL SCHEDULE HA EXISTING (TO BE MODIFIED) VOLTAGE:277/480 V SOURCE:MAIN SERVICE SINGLE PANEL PHASE:3 Ø PANEL LOCATION:DOUBLE PANEL WIRES:4 W BRACING:42,000 AIC SURFACE AMPERAGE:400 A M.L.O.M.C.B RECESSED NO T E IDENTIFICATION OT H E R RE C . LT G . LOAD (WATTS)AMP CB PO L E CIR. NO. CIR. NO.PO L E AMP CB LOAD (WATTS) LT G . RE C . OT H E R IDENTIFICATION NO T E ØA ØB ØC ØA ØB ØC E OUTSIDE DUST COLLECTOR 8300 60 3 1 2 3 30 4980 1 MAX SYSTEM BOX E8300344980 8300 5 6 4980 E PRESS 5,6,9 COOLING TOWER 4980 30 3 7 8 3 20 2214 1 OVEN EXHAUST FAN E49809102214 4980 11 12 2214 E COOLING TOWER PRESS #5 4100 20 3 13 14 3 30 3960 1 ETCH LINE EXHAUST FAN E410015163960 4100 17 18 3960 E SPACE 19 20 3 30 4200 1 WELDER 30AMPS PLUGS EESPACE21224200 E TRANSFORMER A12, 25 KVA, 1PH 1 7200 60 2 23 24 4200 7200 25 26 3 30 3800 1 TUMBLER MACHINE E E TRANSFORMER A40, 10 KVA, 1PH 1 4000 30 2 27 28 3800 4000 29 30 3800 E TRANSFORMER A26, 15 KVA, 1PH 1 5000 40 2 31 32 3 40 4100 1 TRANSFORMER 5A 15KVA 3PH E500033344100 E SPACE 35 36 4100 E SPACE 37 38 3 100 11,000 1 GATTER 100 DISCONNECT E E TRANSFORMER A4, 25 K.V.A, 1PH 1 7400 60 2 39 40 11,000 7400 41 42 11,000 SUBTOTAL WATTS 0 0 0 29580 33780 35980 0 0 34254 34254 34254 0 0 0 SUBTOTAL WATTS REC:10000W @100% + 21900W @50% =20950 TOTAL WATTS ØA 63834 MAX. CONN. PHASE AMPS 84.478 LCL:0W @125% =0 TOTAL WATTS ØB 68034 TOTAL CONNECTED KVA 202.102 LML:25954W @100% + 33000W @25% =34204 TOTAL WATTS ØC 70234 TOTAL DEMAND KVA 199.402 (REC+LCL+LML) + REMAINDER @100% =199402 TOTAL AMPS 239.843 N = NEW E = EXISTING PANEL SCHEDULE HA1 EXISTING (TO BE MODIFIED) VOLTAGE:277/480 V SOURCE:PANEL HA SINGLE PANEL PHASE:3 Ø PANEL LOCATION:SHOP DOUBLE PANEL WIRES:4 W BRACING:42,000 AIC SURFACE AMPERAGE:200 A M.L.O.M.C.B RECESSED NO T E IDENTIFICATION OT H E R RE C . LT G . LOAD (WATTS)AMP CB PO L E CIR. NO. CIR. NO.PO L E AMP CB LOAD (WATTS) LT G . RE C . OT H E R IDENTIFICATION NO T E ØA ØB ØC ØA ØB ØC E BAND SAW #1 1 5813 30 3 1 2 3 30 3183 1 BAND SAW #2 E5813343183 5813 5 6 3183 E GRINDER #1 1 2076 20 3 7 8 3 20 1965 1 GRINDER #3 E20769101965 2076 11 12 1965 E GRINDER #2 1 2076 20 3 13 14 3 20 1965 1 GRINDER #4 E207615161965 2076 17 18 1965 E COMPRESSOR COOLER TOWER 1 1052 20 3 19 20 3 20 1052 1 COMPRESSOR COOLER TOWER E105221221052 1052 23 24 1052 E WET DUST COLLECTOR 1 1855 20 3 25 26 3 20 2463 1 AIR DRYER COMPRESSOR E185527282463 1855 29 30 2463 E SPACE 31 32 3 20 2159 1 TUMBLER EESPACE33342159 E SPACE 35 36 2159 E SPACE 37 38 SPACE E E SPACE 39 40 SPACE E E SPACE 41 42 SPACE E SUBTOTAL WATTS 0 0 0 12872 12872 12872 0 0 12787 12787 12787 0 0 0 SUBTOTAL WATTS REC:0W @100%0 TOTAL WATTS ØA 25659 MAX. CONN. PHASE AMPS 30.863 LCL:0W @125% =0 TOTAL WATTS ØB 25659 TOTAL CONNECTED KVA 76.977 LML:25659W @100% + 17439W @25% =30019 TOTAL WATTS ØC 25659 TOTAL DEMAND KVA 81.337 (REC+LCL+LML) + REMAINDER @100% =81337 TOTAL AMPS 97.833 N = NEW E = EXISTING PANEL SCHEDULE LA3 EXISTING (TO BE MODIFIED) VOLTAGE:120/208 V SOURCE:MAIN SERVICE SINGLE PANEL PHASE:3 Ø PANEL LOCATION:DOUBLE PANEL WIRES:4 W BRACING:10,000 AIC SURFACE AMPERAGE:250 A M.L.O.M.C.B RECESSED NO T E IDENTIFICATION OT H E R RE C . LT G . LOAD (WATTS)AMP CB PO L E CIR. NO. CIR. NO.PO L E AMP CB LOAD (WATTS) LT G . RE C . OT H E R IDENTIFICATION NO T E ØA ØB ØC ØA ØB ØC E A/C 1 2870 40 2 1 2 2 40 2870 1 A/C E 2870 3 4 2870 E EXISTING CIRCUIT 4 600 20 1 5 6 2 30 2100 1 A/C E E PRINTER ROOM RECEPTACLES & LIGHT 5 900 20 1 7 8 2100 E LIGHT BREAK ROOM 1 720 20 1 9 10 1 20 400 1 HENDRY OFFICE LIGHT E E EXISTING CIRCUIT 1 600 20 1 11 12 1 20 1080 6 KITCHEN AREA OFFICE RECEPTACLES E E EXISTING CIRCUIT 1 600 20 1 13 14 1 20 1200 1 EM LIGHT SNACK MACHINE E E EXISTING CIRCUIT 1 600 20 1 15 16 1 20 600 1 OFFICE COMPUTER & EXIT LIGHT E E MICROWAVE & COMPUTER 1 1500 20 1 17 18 1 20 200 1 ALARM E E LIGHTS & ROOF OFFICE RECEPTACLES 1 1200 20 1 19 20 1 20 220 1 LADIES ROOM LIGHT & PRINTER AREA E E QC BENCH RECEPTACLES 6 1080 20 1 21 22 1 20 1440 8 OFFICE RECEPTACLES E E OFFICE COPY RECEPTACLES 1 1200 20 1 23 24 1 20 600 1 EXISTING CIRCUIT E E LIGHTS & TIME CLOCK 1 1300 20 1 25 26 1 20 600 1 EXISTING CIRCUIT E E EXISTING CIRCUIT 1 600 20 1 27 28 1 20 800 1 QUALITY CONTROL WEST FAN E E LUNCH ROOM REFRIGERATOR 1 1200 20 1 29 30 1 20 540 3 QUALITY CONTROL EAST FAN RECEPTACLES E E TWO LIGHT OVEN OFFICE 1 600 20 1 31 32 1 20 SPARE E E SPARE 20 1 33 34 1 20 SPARE E E SPARE 20 1 35 36 1 20 SPARE E E SPARE 20 1 37 38 1 20 SPARE E E SPARE 20 1 39 40 1 20 SPARE E E SPARE 20 1 41 42 1 20 SPARE E SUBTOTAL WATTS 0 0 0 7470 5870 5100 0 0 6990 6110 4520 0 0 0 SUBTOTAL WATTS REC:10000W @100% + 3040W @50% =11520 TOTAL WATTS ØA 14460 MAX. CONN. PHASE AMPS 40.137 LCL:5040W @125% =6300 TOTAL WATTS ØB 11980 TOTAL CONNECTED KVA 36.060 LML:10140W @100% + 5740W @25% =11575 TOTAL WATTS ØC 9620 TOTAL DEMAND KVA 37.235 (REC+LCL+LML) + REMAINDER @100% =37235 TOTAL AMPS 103.354 N = NEW E = EXISTING SCHEDULE KEY LA3 HA1 HA PANEL SCHEDULE LB1 EXISTING (TO BE MODIFIED) VOLTAGE:120/208 V SOURCE:TRANSFORMER B SINGLE PANEL PHASE:3 Ø PANEL LOCATION:SHOP DOUBLE PANEL WIRES:4 W BRACING:10,000 AIC SURFACE AMPERAGE:200 A M.L.O.M.C.B 200A RECESSED NO T E IDENTIFICATION OT H E R RE C . LT G . LOAD (WATTS)AMP CB PO L E CIR. NO. CIR. NO.PO L E AMP CB LOAD (WATTS) LT G . RE C . OT H E R IDENTIFICATION NO T E ØA ØB ØC ØA ØB ØC E SHIPPING 1 1200 20 1 1 2 1 20 1600 1 HIGH BAY LIGHTS / PLUGS E E LIGHT 1 1200 20 1 3 4 1 20 1600 1 HIGH BAY LIGHTS / PLUGS E E RECEPTACLES 1 1200 20 1 5 6 1 20 720 4 RECEPTACLES E E HIGH BAY LIGHTS 1 1600 20 1 7 8 1 20 1080 6 RECEPTACLES E E E/W INVERE 1 600 20 1 9 10 1 20 1080 6 RECEPTACLES E E OUTSIDE LIGHTS 1 300 20 1 11 12 1 20 1300 6 RECEPTACLES E E SPACE 13 14 1 20 1200 4 RECEPTACLES E E SPACE 15 16 SPACE E E SPACE 17 18 SPACE E E SPACE 19 20 1 20 900 1 WEST SIDE WALL REC.E E SPACE 21 22 SPACE E E SPACE 23 24 SPACE E E SPACE 25 26 SPACE E E SPACE 27 28 SPACE E E SPACE 29 30 SPACE E E SPACE 31 32 SPACE E E SPACE 33 34 SPACE E E SPACE 35 36 SPACE E E SPACE 37 38 SPACE E E SPACE 39 40 SPACE E E SPACE 41 42 SPACE E E PANEL BL2 1 5580 150 3 43 44 5400 45 46 5040 47 48 SUBTOTAL WATTS 1 0 0 8380 7200 6540 0 0 4780 2680 2020 0 0 0 SUBTOTAL WATTS REC:3300W @100%3300 TOTAL WATTS ØA 13160 MAX. CONN. PHASE AMPS 36.529 LCL:6300W @125% =7875 TOTAL WATTS ØB 9880 TOTAL CONNECTED KVA 31.600 LML:11560W @100% + 16740W @25% =15745 TOTAL WATTS ØC 8560 TOTAL DEMAND KVA 37.360 (REC+LCL+LML) + REMAINDER @100% =37360 TOTAL AMPS 103.701 N = NEW E = EXISTING PANEL SCHEDULE B1 EXISTING (TO BE MODIFIED) VOLTAGE:277/480 V SOURCE:HB SINGLE PANEL PHASE:3 Ø PANEL LOCATION:SHOP DOUBLE PANEL WIRES:3 W BRACING:42,000 AIC SURFACE AMPERAGE:200 A M.L.O.M.C.B RECESSED NO T E IDENTIFICATION OT H E R RE C . LT G . LOAD (WATTS)AMP CB PO L E CIR. NO. CIR. NO.PO L E AMP CB LOAD (WATTS) LT G . RE C . OT H E R IDENTIFICATION NO T E ØA ØB ØC ØA ØB ØC E WELDER PLUG 1 4980 30 3 1 2 3 30 1680 1 EXHAUST FAN E4980341680 4980 5 6 1680 E WELDER PLUG 1 4760 30 3 7 8 3 30 2100 1 GAS BLOWER E47609102100 4760 11 12 2100 E WELDER PLUG 1 4760 30 3 13 14 3 30 1800 1 OVEN #4 E476015161800 4760 17 18 1800 E DEBURR MACHINE 1 4560 30 3 19 20 SPACE E 4560 21 22 SPACE E 4560 23 24 SPACE E E PNL LB1 1 13160 100 3 25 26 SPACE E E 9880 27 28 SPACE E E 8560 29 30 SPACE E SUBTOTAL WATTS 0 0 0 32220 28940 27620 0 0 5580 5580 5580 0 0 0 SUBTOTAL WATTS REC:0W @100%0 TOTAL WATTS ØA 37800 MAX. CONN. PHASE AMPS 45.466 LCL:0W @125% =0 TOTAL WATTS ØB 34520 TOTAL CONNECTED KVA 105.520 LML:37800W @100% + 39480W @25% =47670 TOTAL WATTS ØC 33200 TOTAL DEMAND KVA 115.390 (REC+LCL+LML) + REMAINDER @100% =115390 TOTAL AMPS 138.793 N = NEW E = EXISTING LB1B1 PANEL SCHEDULE HB EXISTING (TO BE MODIFIED) VOLTAGE:277/480 V SOURCE:MAIN SERVICE SINGLE PANEL PHASE:3 Ø PANEL LOCATION:SHOP DOUBLE PANEL WIRES:4 W BRACING:65,000 AIC SURFACE AMPERAGE:600 A M.L.O.M.C.B RECESSED NO T E IDENTIFICATION OT H E R RE C . LT G . LOAD (WATTS)AMP CB PO L E CIR. NO. CIR. NO.PO L E AMP CB LOAD (WATTS) LT G . RE C . OT H E R IDENTIFICATION NO T E ØA ØB ØC ØA ØB ØC E EXHAUST 1 2700 20 3 1 2 3 20 680 1 EXHAUST FAN E270034680 2700 5 6 680 E OVEN #6 1 4100 20 3 7 8 3 20 2100 1 GAS BLOWER #7 E41009102100 4100 11 12 2100 E GAS BLOWER #6 1 2100 20 3 13 14 3 20 4100 1 OVEN #7 E210015164100 2100 17 18 4100 E EXHAUST FAN OVER THE DOOR 1 500 20 3 19 20 3 20 4100 1 OVEN #9 E50021224100 500 23 24 4100 E OVEN #5 1 4100 20 3 25 26 3 20 650 1 OIL PUMP E41002728650 4100 29 30 650 E GASS BLOWER 5 1 2100 20 3 31 32 3 30 2100 1 GAS BLOWER #9 E210033342100 2100 35 36 2100 E 75 KVA TRANSFORMER 1 14500 80 3 37 38 3 100 37800 1 PANEL 508 B1 E14500394034520 14500 41 42 33200 E PRESS 5 B 1 6920 125 3 43 44 3 200 16100 1 COMPRESSOR E6920454616100 6920 47 48 16100 SUBTOTAL WATTS 1 0 0 37020 37020 37020 0 0 67630 64350 63030 0 0 1 SUBTOTAL WATTS REC:0W @100%0 TOTAL WATTS ØA 104650 MAX. CONN. PHASE AMPS 125.874 LCL:0W @125% =0 TOTAL WATTS ØB 101370 TOTAL CONNECTED KVA 306.070 LML:104650W @100% + 113400W @25% =133000 TOTAL WATTS ØC 100050 TOTAL DEMAND KVA 334.420 (REC+LCL+LML) + REMAINDER @100% =334420 TOTAL AMPS 402.245 N = NEW E = EXISTING HB PANEL SCHEDULE LA1 EXISTING (TO BE MODIFIED) VOLTAGE:120/208 V SOURCE:SINGLE PANEL PHASE:3 Ø PANEL LOCATION:DOUBLE PANEL WIRES:4 W BRACING:10,000 AIC SURFACE AMPERAGE:100 A M.L.O.M.C.B RECESSED NO T E IDENTIFICATION OT H E R RE C . LT G . LOAD (WATTS)AMP CB PO L E CIR. NO. CIR. NO.PO L E AMP CB LOAD (WATTS) LT G . RE C . OT H E R IDENTIFICATION NO T E ØA ØB ØC ØA ØB ØC E SPACE 1 2 1 20 670 1 WEST EXTERIOR PLUG + R.O. WATER STATION E E SPACE 3 4 1 20 300 1 TANK ALERT (WEST EXTERIOR)E E SPACE 5 6 1 20 280 1 WEST EXTERIOR LIGHTS + PLUGS +TANK E E SPACE 7 8 1 20 600 1 WEST EXTERIOR PLUG E E SPACE 9 10 1 20 600 1 WEST EXTERIOR TANK PLUG E E SPACE 11 12 1 20 600 1 HOLDING TANK #1 & EXTERIOR WASTE WATER TANK E E SPACE 13 14 1 20 1200 1 SOUTH PLUG & CRANE E E SPACE 15 16 1 20 1600 1 TANK EQUIPMENT POWER E E SPACE 17 18 1 20 400 1 INTERIOR WEST SIDE LIGHTS E E PRODUCE LIGHT 1 1100 20 1 19 20 1 20 860 1 WEST PLUGS & HEATER E E LIGHTS 1 800 20 1 21 22 1 20 960 1 WEST PLUGS & TANK EQUIPMENTS E E SPACE 20 1 23 24 1 20 480 1 SOUTH SIDE LIGHTS E E LIGHTS 1 800 20 1 25 26 SPACE E E LIGHTS 1 600 20 1 27 28 SPACE E E PRODUCE LIGHT 1 1100 20 1 29 30 SPACE E E SPACE 31 32 1 20 300 1 TUMBLER ROOM PLUGS/ LIGHTS E E SPACE 33 34 1 20 200 1 FIRE SPRINKLER CONTROLS E E SPACE 35 36 SPACE E E SPACE 37 38 SPACE E E SPACE 39 40 SPACE E E SPACE 41 42 SPACE E SUBTOTAL WATTS 0 0 0 1900 1400 1100 0 0 3630 3660 1760 0 0 0 SUBTOTAL WATTS REC:4170W @100%4170 TOTAL WATTS ØA 5530 MAX. CONN. PHASE AMPS 15.350 LCL:5580W @125% =6975 TOTAL WATTS ØB 5060 TOTAL CONNECTED KVA 13.450 LML:3700W @100% + 1600W @25% =4100 TOTAL WATTS ØC 2860 TOTAL DEMAND KVA 15.245 (REC+LCL+LML) + REMAINDER @100% =15245 TOTAL AMPS 42.316 N = NEW E = EXISTING LA1 LB2 PANEL SCHEDULE LB2 EXISTING (TO BE MODIFIED) VOLTAGE:120/208 V SOURCE:PANEL B1 SINGLE PANEL PHASE:3 Ø PANEL LOCATION:OFFICE AREA DOUBLE PANEL WIRES:4 W BRACING:10,000 SURFACE AMPERAGE:125 A M.L.O.M.C.B RECESSED NO T E IDENTIFICATION OT H E R RE C . LT G . LOAD (WATTS)AMP CB PO L E CIR. NO. CIR. NO.PO L E AMP CB LOAD (WATTS) LT G . RE C . OT H E R IDENTIFICATION NO T E ØA ØB ØC ØA ØB ØC OFFICE RECS.7 1260 20 1 1 2 1 20 720 4 OFFICE RECS. OFFICE RECS.5 900 20 1 3 4 1 20 1080 6 OFFICE RECS. OFFICE RECS.6 1080 20 1 5 6 1 20 540 3 OFFICE RECS. OFFICE RECS.4 720 20 1 7 8 1 20 1080 6 OFFICE RECS. OFFICE RECS.3 540 20 1 9 10 1 20 900 5 OFFICE RECS. OFFICE RECS.6 1080 20 1 11 12 1 20 1260 7 OFFICE RECS. OFFICE RECS.7 1260 20 1 13 14 1 20 540 3 OFFICE RECS. OFFICE RECS.5 900 20 1 15 16 1 20 1080 6 OFFICE RECS. SPACE 17 18 1 20 1080 6 OFFICE RECS. SPACE 19 20 SPACE SPACE 21 22 SPACE SPACE 23 24 SPACE SPACE 25 26 SPACE SPACE 27 28 SPACE SPACE 29 30 SPACE SUBTOTAL WATTS 0 0 0 3240 2340 2160 0 0 2340 3060 2880 0 0 0 SUBTOTAL WATTS REC:10000W @100% + 6020W @50% =13010 TOTAL WATTS ØA 5580 MAX. CONN. PHASE AMPS 15.489 LCL:0W @125% =0 TOTAL WATTS ØB 5400 TOTAL CONNECTED KVA 16.020 LML:0W @100% + 0W @25% =0 TOTAL WATTS ØC 5040 TOTAL DEMAND KVA 13.010 (REC+LCL+LML) + REMAINDER @100% =13010 TOTAL AMPS 36.112 E - EXISTING 1 - EXISTING TO BE REUSED N - NEW X - TIEBAR BREAKER 2 2 A/C 12 A/C 13 A/C 14 A/C 15 A/C 16 DRIVEWAY 8 71917 18 20 200A DISTRIBUTION SECTION. SEE TABLE 3 37 21 23 1 2 3 21 22 6 5 4 10 8 11 T T T 9 EXISTING 400 AMP BUSWAY "B" 480V, 3PH, 3W SEE TABLE 2 2 4 6 10 12 16 18 19 20 22 24 26 37 40 46 44 15 19 21 23 25 277049161431 61 26 24 27 28 1 7 3 2 62 4 27 MS-502 #1039 53 PRESS 6 PRESS 5 50 51 52 49 PRESS 7 MS-502 # 9 MS-502 # 8 55 57 58 40 36 18 20 26 38 B 38A 12 8 28 4 6 10 14 J-BOX 17 24 5 7 EXISTING 1000 AMP BUSWAY "A" SEE TABLE 1 J 0 SPARE 3 9 11 42 EXISTING 1600 AMP SERVICE TO BE REMOVED T 20 19 21 23 2 13 56 BUSWAY "A" 54 PRESS 9 MS-502 # 4 MS-502 # 5 59 OVEN 9 53 43 800A MCC FOR PRESS #7 MS-502 # 7 T PB PB 8 TO MS-1 6 TO MS HB 7 10 72 12 2 2 6A 6B 5A 5B HA 1 COPYRIGHT LEWIS ROSS ASSOCIATES FILE NAME: SHEET NUMBER: DESCRIPTION: PROJECT NAME: DRAWN BY: SCALE: DATE: PROJECT NO.: CLIENT: PROJECT NO. PROJECT: AS SHOWN OST ALUMINUM PRECISION PRODUCTS 04-14-2025 24-121 NEC ELECTRIC INC. 24-121 ALUMINUM PRECISION PRODUCT ADDRESS: 502 E. ALTON AVE. 516 E. ALTON AVE. SANTA ANA, CA 92707 17015 SO. BROADWAY ST. GARDENA, CA 90248 REV DESCRIPTION DATE 9401 RESEDA BLVD. SUITE 200 NORTHRIDGE, CA 91324 PHONE: (818) 886-2190 FAX: (818) 886-2131 PLAN CHECK 11-13-2024- Lewis Ross Dropbox\Projects\2020\20-180 17806 Lassen\LRA Drawings PLAN CHECK CORRECTIONS 01-16-20251 CORRECTIONS 04-14-20252 E-2.0 502 BUILDING ELECTRICAL POWER PLAN 502 BUILDING ELECTRICAL POWER PLAN 1/8"=1'-0" TABLE 1 - BUSWAY "A" EQUIPMENT SCHEDULE TAG DESCRIPTION VOLTS PHASE HP AMPS REMARKS 41 MINE PRESS 480 3 5 7.6 42 ROLIER MACHINE 480 3 1.5 2.76 43 EXHAUST FAN 480 3 1.5 2.76 48 J-BOX ----NO LOAD 49 PRESS 7 480 3 --DISCONNECT SWITCH ONLY 50 OVEN 7 480 3 -15 51 OVEN 6 480 3 -15 52 OVEN 5 480 3 -15 53 BUILDING 3 SHOP 480 3 --DISCONNECT SWITCH ONLY 54 PRESS 9 GAS BURNER 480 3 -1.1 55 DISCONNECT PLUG 480 3 -30 56 XFMR T12 480 3 -31 15 KVA 57 PANEL 2A 120 208 3 -30 13.0A AT 480V 58 PANEL 2B 120 208 3 -30 13.0A AT 480V 59 OVEN 9 480 3 -15 60 NOT USED ---- 61 COMPRESSOR 480 3 150 177 62 OVEN 480 3 -118 TOTAL CONNECTED LOAD AT BUSWAY "A" IS 456.2 AMPS TABLE 2 - BUSWAY "B" EQUIPMENT SCHEDULE TAG DESCRIPTION VOLTS PHASE HP AMPS REMARKS 2 TRANSFORMER 480 3 -30.1 25 KVA 3 D.S FOR OVEN 480 3 --DISCONNECT SWITCH ONLY 4 EXHAUST FAN ON ROOF 480 3 1.5 30 5 CONTROL SLAVE #1 480 3 -7.5 5KV 6 MASTER OVEN CONTROL 480 3 -7.5 5KV 7 CONTROL SLAVE-1 480 3 -5 8 TRANSFORMER 480 3 -18.4 15 KVA 9 TRANSFORMER 480 3 --25 KVA (FEEDS AC-12 &13) 10 TRANSFORMER 480 3 --15 KVA (FEEDS AC-14,15 & 16) 11 TRANSFORMER 480 3 -30.7 25 KVA 17 GRINDER #3 480 3 -4.5 18 GRINDER #4 480 3 -4.5 19 SPARE DISCONNECT 480 3 --SPARE 20 DISCONNECT ON GUTTER 480 3 -50.7 SEE TABLE 3 BELOW 21 TUMBLER 480 3 -7.6 22 DISCONNECT PLUG 480 3 -30 23 SPARE DISCONNECT 480 3 --SPARE 24 EXHAUST FAN PLUG 480 3 5 6.7 26 DUST COLLECTOR 480 3 40 46 27 COOLING TOWER #5 480 3 1.5 2.26 28 COOLING TOWER 480 3 1.5 2.26 37 BAND SAW 480 3 15 23.5 TOTAL CONNECTED LOAD AT BUSWAY "B" IS 357.1 AMPS TABLE 3 - DISTRIBUTION SECTION EQUIPMENT SCHEDULE TAG DESCRIPTION VOLTS PHASE HP AMPS REMARKS 71 GREENDER 1 480 3 -6.1 72 GREENDER 2 480 3 -6.1 73 GREENDER 1 & 2 VAC.480 3 -11 74 BANDSAW 3 480 3 7.5 11.5 75 BANDSAW 4 480 3 3 11.5 76 WET DUST COLLECTOR 480 3 3 4.5 77 XFMR (NOT IN USE)480 3 --15 KVA SPARE 78 NOT IN USE 480 3 --SPARE BREAKER TOTAL CONNECTED LOAD AT 200AMP DISTRIBUTION SECTION IS 50.7 AMPS SUB FEED REFERENCE NOTES AFTER ENERGIZATION OF MAIN SERVICE "MS" AND COMPLETED SWITCH OVER, REMOVE EXISTING BUSWAY "A" & "B" AND DISCONNECT AND REMOVE EXISTING OVERHEAD 1600AMP SERVICE. 1. #1 BUSWAY #1 23 #21 BUSWAY #1 22 21 20 24 ON ROOF #30 BUSWAY #1 #26 BUSWAY #1 #22 BUSWAY #1 #12 BUSWAY #1 T T T T J DP16 #3 #1 BUSWAY #1 EXISTING METER/MAIN SECTION AND SERVICE RISER TO BE REMOVED REMOVE EXISTING 4" 0VHD CONDUIT AND 6#350 MCM FEEDERS 1 J #8 BUSWAY #1 31 J 33 #9 BUSWAY #1 3 2 4 5 J J 6 J #4 BUSWAY #1 400A 10 9 8 7 J #13 BUSWAY #1 27 28 #31 BUSWAY #1 J T 7JJ 37 36 DP16 OVEN 4A #0 BUSWAY #1 JJ 14 13 #18 BUSWAY #1 #16 BUSWAY #1 16 15 MINIMUM 16"X16"X4" P.B. PB NEW 600A SERVICE RATED MAIN DISCONNECT NEW DISTRIBUTION PANEL "DP16" #10 BUSWAY #1 17 18 32 12 35 J #7 BUSWAY #1 NEW 4" TO 600A PANEL DP16 DP16 #2 EXISTING 400A BUSWAY "C" 1357922132317253112P/L271921 2468103414161820X34242602830 "HA" 1 COPYRIGHT LEWIS ROSS ASSOCIATES FILE NAME: SHEET NUMBER: DESCRIPTION: PROJECT NAME: DRAWN BY: SCALE: DATE: PROJECT NO.: CLIENT: PROJECT NO. PROJECT: AS SHOWN OST ALUMINUM PRECISION PRODUCTS 04-14-2025 24-121 NEC ELECTRIC INC. 24-121 ALUMINUM PRECISION PRODUCT ADDRESS: 502 E. ALTON AVE. 516 E. ALTON AVE. SANTA ANA, CA 92707 17015 SO. BROADWAY ST. GARDENA, CA 90248 REV DESCRIPTION DATE 9401 RESEDA BLVD. SUITE 200 NORTHRIDGE, CA 91324 PHONE: (818) 886-2190 FAX: (818) 886-2131 PLAN CHECK 11-13-2024- Lewis Ross Dropbox\Projects\2020\20-180 17806 Lassen\LRA Drawings PLAN CHECK CORRECTIONS 01-16-20251 CORRECTIONS 04-14-20252 E-2.1 516 BUILDING ELECTRICAL POWER PLAN 516 BUILDING ELECTRICAL POWER PLAN 1/8"=1'-0" BUILDING 516 EQUIPMENT SCHEDULE - BUSWAY "C" TAG DESCRIPTION VOLTS PHASE HP AMPS REMARKS 1 HYDRO-TEI BIG DRILLING WITH 45 KVA 480-230V XFMR 230 3 15 52.5 2 ARCHDALE MACHINE 460 3 8 17.5 3 20" LATHE 460 3 -14 4 WELDING MACHINE 460 3 -30 5 BAND SAW 460 3 2 2.7 6 GHARJIN 460 3 -9 7 WINDOW FREE LATHE 460 3 35.7 15 8 SANDER TABLE 460 3 2 2.7 9 DISPOSAL MACHINE 460 3 2 2.7 10 OUTSIDE DRYER 460 3 -10 12 FREEZER #1A 230 3 1/15 0.3 15 KVA XFMR 13 OUTSIDE CLEAN TANK "A"460 3 -24 14 OUTSIDE CLEAN TANK "B"460 3 -24 15 OVEN "3A"460 3 -15 16 OVEN "1A"460 3 -15 17 BAND SAW 460 3 7.5 11.5 18 GRINDER MACHINE 460 3 5 7.6 20 AIR CONDITIONER 460 3 -9 16A MAX FUSE ON ROOF 21 DRYER BOX 460 3 -20 22 DRYER BOX 460 3 -20 23 SANDER BOX 460 3 -12 24 NOT USED ---- 27 DUST COLLECTOR 460 3 20 27 28 COOLING TOWER 460 3 3 4.8 29 HYDRAULIC PUMP 460 3 2.5 4.25 30 SPARE J-BOX. NOT IN USE 460 3 --SPARE 31 460 3 --SPARE 32 SPARE WIRES IN CEILING NOT IN USE.460 3 --SPARE 33 SPARE J-BOX. NOT IN USE 460 3 --SPARE 34 SPARE WIRES IN CEILING NOT IN USE.460 3 --SPARE 35 460 3 --SPARE 36 SPARE J-BOX. NOT IN USE 460 3 --SPARE 37 SPARE DISCONNECT 460 3 --SPARE 1 1 COPYRIGHT LEWIS ROSS ASSOCIATES FILE NAME: SHEET NUMBER: DESCRIPTION: PROJECT NAME: DRAWN BY: SCALE: DATE: PROJECT NO.: CLIENT: PROJECT NO. PROJECT: AS SHOWN OST ALUMINUM PRECISION PRODUCTS 04-14-2025 24-121 NEC ELECTRIC INC. 24-121 ALUMINUM PRECISION PRODUCT ADDRESS: 502 E. ALTON AVE. 516 E. ALTON AVE. SANTA ANA, CA 92707 17015 SO. BROADWAY ST. GARDENA, CA 90248 REV DESCRIPTION DATE 9401 RESEDA BLVD. SUITE 200 NORTHRIDGE, CA 91324 PHONE: (818) 886-2190 FAX: (818) 886-2131 PLAN CHECK 11-13-2024- Lewis Ross Dropbox\Projects\2020\20-180 17806 Lassen\LRA Drawings PLAN CHECK CORRECTIONS 01-16-20251 CORRECTIONS 04-14-20252 E-6.0 SCE APPROVED CONSTRUCTION DRAWINGS SCE APPROVED CONSTRUCTION DRAWINGS N.T.S.