HomeMy WebLinkAbout2219 N Spurgeon St - Plan (2)PAGE
REV: G 5/28/2025
GILBERT VAN DER MARLIERE
2219 N SPURGEON ST, SANTA
ANA, CA, 92706
PROJECT NUMBER:
109R-219VAND
SHEET
DESIGNER:
CODY ZEMKE
CUSTOMER RESIDENCE:
TEL. (714) 381-7691
APN: 003-120-24
(415) 580-6920 ex3
Template_version_v5_2024.07.26
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
COVER SHEET
SCOPE OF WORK GENERAL NOTES
PV-1.0
VICINITY MAP
#SSTAMPCS
#ESTAMPCS
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT
(E)EXISTING
ESS ENERGY STORAGE SYSTEM
MSP MAIN SERVICE PANEL
(N)NEW
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS
V VOLTS
W WATTS
SHEET INDEX
• EXISTING SOLAR SYSTEM INSTALLED.
• ALL WORK SHALL COMPLY WITH 2022 CRC/CBC/CEBC, MUNICIPAL CODE, AND
ALL MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS.
• ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH 2022 CEC.
• CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(D).
• 12.5 AMPS DERATED SHORT CIRCUIT CURRENT [690.8 (A)(1) & 690.8 (B)].
• ENERGY STORAGE SYSTEM CONFORMS TO AND IS LISTED UNDER UL 9540.
• ENERGY STORAGE SYSTEM LIVE PARTS ARE NOT ACCESSIBLE DURING
ROUTINE MAINTENANCE. SYSTEM VOLTAGE IN ACCORDANCE WITH CEC 706.20
AND EXCEPTION 1 CEC 706.20 (B).
• ADDITIONAL DISCONNECTING MEANS SHALL BE INSTALLED WHERE THE
CIRCUITS FROM THESE TERMINALS PASS THROUGH A WALL OR PARTITION PER
706.15(D).
• LISTED, COMBINATION TYPE AFCI SHALL BE INSTALLED WHERE BACKED UP
CIRCUIT WIRING IS EXTENDED MORE THAN 6FT AND DOES NOT INCLUDE ANY
ADDITIONAL OUTLETS OR DEVICES PER CEC 210.12(D).
• ALL PASS-THROUGH CONDUCTORS MUST COMPLY WITH CEC 312.8
• THE CAPACITY OF THE STANDALONE SYSTEM SUPPLY SHALL BE EQUAL TO OR
GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION
EQUIPMENT CONNECTED TO THE SYSTEM PER CEC ARTICLE 710.15(A)
PAGE #DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-2.1 ESS ELEVATION VIEW
PV-2.2 GARAGE FLOOR PLAN
PV-4.0 ELECTRICAL
PV-4.1 ELECTRICAL CALCS
PV-4.2 BACKUP LOAD CALCS
PV-4.3 PANEL SCHEDULE
PV-5.0 SIGNAGE
(1) RESIDIO HEAT SENSOR
• BACKUP GATEWAY: (1) 200A TESLA POWERWALL CONTROL
PANEL
• POWER CONTROLLED SYSTEM (PCS) ENABLED
EQUIPMENT INSTALLED, SEE PV-4.0 FOR INTERCONNECTION
DETAILS
• ENERGY STORAGE SYSTEM: (3) TESLA: POWERWALL 3
1707000-XX-Y 13.5KWH, 5KW INVERTER OUTPUT ,
LITHIUM-ION BATTERY (WEIGHT; 287LB EACH )
G
Revision to 20184381 (issued on 1/24/25)
Rev 1 #20185838
APPROVALS:ELECT - M. Smith
PAGE
REV: G 5/28/2025
GILBERT VAN DER MARLIERE
2219 N SPURGEON ST, SANTA
ANA, CA, 92706
PROJECT NUMBER:
109R-219VAND
SHEET
DESIGNER:
CODY ZEMKE
CUSTOMER RESIDENCE:
TEL. (714) 381-7691
APN: 003-120-24
(415) 580-6920 ex3
Template_version_v5_2024.07.26
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
ESS ELEVATION VIEW
PV-2.1
#SSTAMPSP
#ESTAMPSP
SITE PLAN - SCALE = NTS
INTERIOR EAST WALL - GARAGE
G
3' MIN 3' MIN
ACD
RESIDIO HEAT SENSOR
ESS INTERIOR INSTALLATION WILL COMPLY WITH SMOKE AND HEAT MONITORING REQUIREMENTS FOR 2022 CFC 1207.11.6
ESS INTERIOR INSTALLATION LOCATION WILL COMPLY WITH IMPACT PROTECTION REQUIREMENTS FOR 2022 CFC 1207.11.7.3
ACD ACD
POWREWALL 3 POWERWALL 3 POWERWALL 3
ESS ELEVATION VIEW
PAGE
REV: G 5/28/2025
GILBERT VAN DER MARLIERE
2219 N SPURGEON ST, SANTA
ANA, CA, 92706
PROJECT NUMBER:
109R-219VAND
SHEET
DESIGNER:
CODY ZEMKE
CUSTOMER RESIDENCE:
TEL. (714) 381-7691
APN: 003-120-24
(415) 580-6920 ex3
Template_version_v5_2024.07.26
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
GARAGE FLOOR PLAN
PV-2.2
#SSTAMPSP
#ESTAMPSP
SITE PLAN - SCALE = NTS
AC AC AC
GARAGE FLOOR PLANINTERIOR DOOR
RESIDIO HEAT
SENSOR
G
9"
NOTE: GARAGE WALL BATTERY MOUNTED ON IS NOT
SEPARATING THE GARAGE FROM HABITABLE SPACE
NOTE: ESS DOES NOT EMIT FLAMMABLE GASSES AND
THEREFORE DOES NOT REQUIRE ADDITIONAL
VENTILATION
NOTE: GARAGE WALL BATTERY MOUNTED ON IS
SEPERATING THE GARAGE FROM EXTERIOR SPACE
NOTE: ESS INTERIOR INSTALLABLE SHALL COMPLY WITH
SMOKE AND HEAT MONITORING REQUIREMENTS FOR
2022 CFC 1207.11.6
NOTE: ESS INTERIOR INSTALLABLE SHALL COMPLY WITH
IMPACT PROTECTION REQUIREMENTS FOR 2022 CFC
1207.11.7.3
20'
20'
9"
PAGE
REV: G 5/28/2025
GILBERT VAN DER MARLIERE
2219 N SPURGEON ST, SANTA
ANA, CA, 92706
PROJECT NUMBER:
109R-219VAND
SHEET
DESIGNER:
CODY ZEMKE
CUSTOMER RESIDENCE:
TEL. (714) 381-7691
APN: 003-120-24
(415) 580-6920 ex3
Template_version_v5_2024.07.26
2500 WHITE RD. SUITE A, IRVINE CA 92614
PHONE 805.540.7603
FAX 949.215.7778
CA CL #750184
GILBERT CORREIA, C10, C46
2
(N) 225A
BACKUP
LOAD PANEL(E) BACKUP
LOADS
(N) 100A
MAIN BREAKER
M
CTRL(N) 200A BACKUP
GATEWAY
1
2
FACILITY
GROUND
RELOCATED
(E) FACILITY
LOADS EXISTING
200A MAIN
PANEL
M METER #:
SCE
120/240 VAC
SINGLE PHASE
SERVICEUTILITY
GRID
(N) 100A GATEWAY
FEEDER BREAKER AT
OPPOSITE END OF
BUSBAR
(N) SITE CURRENT
TRANSFORMERSNEURIO
METER EXISTING
200A MAIN
BREAKER
(END FED)
+
-
(N) IMO PE69-3020,
DISCONNECT
SWITCH, 3P, 16A
RSD
+
-
TESLA: POWERWALL 3
1707000-XX-Y
POWER CONTROL SYSTEM
RSD
ENERGY STORAGE SYSTEM
TESLA: POWERWALL 3
1707000-XX-Y
ENERGY STORAGE SYSTEM
POWER CONTROL SYSTEM
1
+
-
POWER CONTROL SYSTEM
RSD
ENERGY STORAGE SYSTEM
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A,2P
120/240VAC
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A,2P
120/240VAC
(N) LOCKABLE
BLADE TYPE
AC DISCONNECT
SQUARE D
DU222RB
3R, 60A,2P
120/240VAC 1
111
1
TESLA: POWERWALL 3
1707000-XX-Y
200A GATEWAY
INTERNAL
PANELBOARD
1
(1) SOLAR PV CURRENT
TRANSFORMER
(E) 35A
PV BREAKER AT
OPPOSITE END
OF BUSBAR
E
JUNCTION BOX
OR EQUIVALENT
SE6000H-USRGM
LOAD RATED DC DISCONNECT
WITH AFCI, RAPID SHUTDOWN
COMPLIANT
6000 WATT INVERTER
E HANWHA Q-CELLS: Q.PEAK G4.1 305
(20) MODULES
EXISTING SYSTEM
PV MODULESE
(N) (3) 60A ESS
BREAKERS AT
OPPOSITE END
OF BUSBAR
2
CONDUIT SCHEDULE
# CONDUIT CONDUCTOR NEUTRAL GROUND
1 3/4" EMT OR EQUIV.(2) 6 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2
2 1" EMT OR EQUIV.(2) 3 AWG THHN/THWN-2 (1) 3 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2
E EXISTING
PV-4.0
ELECTRICAL
#ESTAMP
GENERAL NOTES:
• CITY REQUIRES TWO SOURCES OF GROUND - UFER, TWO GROUNDS RODS OR
COLD WATER GAS BOND
• IF THE RELOCATED LOADS EXTEND MORE THAN 6 FEET, AFCI PROTECTION
APPLIES PER 2019 CEC 210.12
• ANY MULTIWIRE BRANCH CIRCUITS RELOCATED ARE TO BE IDENTIFIED,
GROUPED, AND EQUIPPED WITH A 2-POLE OCPD BREAKER PER CEC 210.4(B,D).
• INSTALL THE BACKED UP LOAD CONDUCTORS AND THE GATEWAY BREAKER
CONDUCTORS IN TWO SEPARATE CONDUITS.
POWER CONTROL SYSTEM (PCS):
• A PCS IS INSTALLED IN ACCORDANCE WITH NEC 705.13
• THE PCS SHALL LIMIT GENERATION SOURCE OUTPUT SUCH THAT CURRENT FROM ALL
SOURCES OF SUPPLY DOES NOT EXCEED THE RATING OF ANY BUSBAR OR CONDUCTOR
SUPPLIED BY THE POWER PRODUCTION SOURCES
• ANY BUSBAR OR CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECT NOT
MONITORED BY THE PCS SHALL COMPLY WITH ARTICLE 705.12.
• ACCESS TO PCS CONTROLS IS RESTRICTED TO QUALIFIED PERSONS IN ACCORDANCE
WITH 240.6(C).
• INVERTER 1: (E) SOLAREDGE TECHNOLOGIES: SE6000H-USRGM 6000 WATT INVERTER
• DO NOT ENABLE PCS
• ENERGY STORAGE SYSTEM: TESLA: POWERWALL
• ENABLE PCS
SETPOINTS:
- 80A - MAXIMUM TOTAL CURRENT ON THE CONTROLLED PANEL
- 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY (120% COMPLIANT)
F