HomeMy WebLinkAbout1009 W River Ln Unit # 2 - PlanExpedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. Expedited Permit Process for PV Systems — Micro-Inverter 2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Micro-Inverter Site Plan             E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Micro-Inverter Electrical Diagram Contractor Name, Address and Phone:One-Line Standard Electrical Diagram for Micro-Inverter PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.1a SCALE NTS Date: SHEET Drawn By: Checked By: DESCRIPTION OR CONDUCTOR TYPE USE-2 or PV WIRE GEC EGC X ALL THAT APPLY EXTERIOR CABLE LISTED W/ INV. THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY NO DC GEC IF 690.35 SYSTEM THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY TAG 1 2 3 4 5 CONDUIT AND CONDUCTOR SCHEDULE COND. GAUGE MFG MFG NUMBER OF CONDUCTORS MFG Cable MFG Cable CONDUIT TYPE N/A N/A N/A SAME SAME CONDUIT SIZE N/A N/A N/A SAME SAME DESCRIPTION PV DC or AC MODULE DC/AC INVERTER (MICRO) J-BOX (IF USED) PV ARRAY AC COMB. PANEL (IF USED) GEN METER (IF USED) AC DISCONNECT (IF USED) SERVICE PANEL TAG 1 2 3 4 5 6 7 8 PART NUMBER NOTES FOR UNUSED MODULES PUT "N/A” in BLANK ABOVE 1 1 3 2 3 EQUIPMENT SCHEDULE 2 _____ MICRO-INVERTERS IN BRANCH- CIRCUIT MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC J-BOX 4 AC DISCO M BUILDING GROUNDING ELECTRODE G M UTILITY SERVICE MAIN SERVICE PANEL MAIN OCPD INVERTER OCPD 6 7 8 5 4 5 G SEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDING AC COMBINER PANEL G ____ MICRO-INVERTERS IN BRANCH- CIRCUIT E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Contractor Name, Address and Phone:Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.2a SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC 2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE.b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE®REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) No sign necessary since 690.51 marking on PV module covers needed information AC OUTPUT CURRENT NOMINAL AC VOLTAGE SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Notes for Micro-Inverter Electrical Diagram Letter of authorization I, Monika Stamp, customer of record at authorize EVERGREEN SOLAR AND HOME BATTERY INC State License number: 1102899 to get the City Permits and complete the Solar installation on my Behalf .Project address 1009 W River Ln Unit #2 Santa Ana, CA 92706 Customer : Monika Stamp Date : 02/24/26 Signature 02/14/2026 RE: Structural Certification for Installation of Residential Solar Monika Stamp:1009 W River Ln Unit #2, Santa Ana, CA 92706 Attn: To Whom It May Concern Design Criteria Code 2025 California Residential Code (ASCE 7-22) Risk category II Wind Load (component and Cladding) Roof Dead Load Dr 10 psf V 95 mph PV Dead Load DPV 3 psf Exposure B Roof Live Load Lr 20 psf Ground Snow S 4 psf If you have any questions on the above, please do not hesitate to call. Sincerely, Eugene Munyanziza, P.E.Signed 02/14/2026 EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2026 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. From the field observation report, the roof is made of Composition shingle roofing over roof plywood supported by 2X10 Rafters at 12 inches. The slope of the roof was approximated to be 18 degrees. After review of the field observation data and based on our structural capacity calculation, the existing roof framing has been determined to be adequate to support the imposed loads without structural upgrades. Contractor shall verify that existing framing is consistent with the described above before install. Should they find any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity calculations were done in accordance with applicable building codes. projects@evengineersnet.com http://www.evengineersnet.com Structural Letter for PV Installation Date:02/14/2026 Job Address:1009 W River Ln Unit #2 Santa Ana, CA 92706 Job Name:Monika Stamp Job Number:021426MS Scope of Work Table of Content Sheet 2 Cover 3 Attachment Uplift checks 4 Roof Framing Check 5 Seismic Check and Scope of work Engineering Calculations Summary Code 2025 California Residential Code (ASCE 7-22) Risk category II Roof Dead Load Dr 10 psf PV Dead Load DPV 3 psf Roof Live Load Lr 20 psf Ground Snow S 4 psf Wind Load (component and Cladding) V 95 mph Exposure B References NDS for Wood Construction Sincerely, Signed 02/14/2026 Eugene Munyanziza, P.E. EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2026 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. All PV mounting equipment shall be designed and installed per manufacturer's approved installation specifications. projects@evengineersnet.com http://www.evengineersnet.com Wind Load Cont. 95 mph ASCE 7-22 Figure 26.5-1B B 1.0 ASCE 7-22 Sec 26.8.2 0.65 ASCE 7-22 Table 26.10-1 0.85 ASCE 7-22 Table 26.6-1 1.00 ASCE 7-22 Table 26.9-1 12.69 psf 18.0 Degrees 1.5 Conservatively assuming all exposed 0.8 conservatively assuming 10 ft2 effective area Uplift (W)Zone(1,2e)Zone(2r, 2n)Zone(3e)Zone(3r) Fig. 30-3-2 GCp=-1.1 -2 -2 -2.4 Eq. 29.4-7 P=qh(GCp)(γE)(γa)=-16.75 -30.46 -30.46 -36.55 GCp=0.5 Figure 30.3-2 P=qh(GCp)(γE)(γa)=4.19 Equation 29.4-7 Rafter Attachments: 0.6D+0.6W (CD=1.6) Connection Check Attachment max. spacing=6 ft 5/16" Lag Screw Withdrawal Value=266 lbs/in Table 12.2A - NDS 2.5 in DFL Assumed Prying Coefficient 1.4 Allowable Capacity=760 lbs Zone Trib Width Area (ft)Uplift (lbs)Down (lbs) Zone(1,2e)6 16.5 107.6 118.6 Zone(2r, 2n)6 16.5 182.2 118.6 Zone(3e)6 16.5 182.2 118.6 Zone(3r)6 16.5 215.4 118.6 Conservative Max=215.4 <760 CONNECTION IS OK Risk Category = KZ = Kd = Ke = II V= Exposure = 1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift governs γE= γa= KZt = qh= 0.00256KzKztKdKeV2= Pitch = Lag Screw Penetration projects@evengineersnet.com http://www.evengineersnet.com Vertical Load Resisting System Design Roof Framing Rafters Snow Load Fully Exposed pg=4 psf Ct =1.1 Ce =0.9 Is =1.0 pf = 3 psf pfmin. = 2.5 psf ps = 3 psf Conservatively (Cs=1)2.52 plf Max Length, L =12 ft (Rafter maximum Allowable Horizontal Span) Tributary Width, WT =12 in Dr =10 psf 10 plf PvDL =3 psf 18 plf Load Case: DL+0.75(0.6W+0.7S) 0.75(Pnet+Ps)+ Ppvcos(θ)+PDL=29 plf Mdown=460 lb-ft Mallowable = Sx x Fb' (wind)=2334 lb-ft >460 lb-ft OK Load Case: DL+0.7S Ps+ Ppvcos(θ)+PDL=25 plf Mdown=402 lb-ft Mallowable = Sx x Fb' (wind)=2334 lb-ft >402 lb-ft OK Load Case: DL+0.6W Pnet+ Ppvcos(θ)+PDL=30.5 plf Max Moment, Mu=488 lb-ft Mallowable = Sx x Fb' (wind)=3247 lb-ft >488 lb-ft OK Pv max Shear=118.6 lbs Shear, Vu=wL/2+Pv Point Load =287 lbs Max Shear, Vu=wL/2+Pv Point Load =287 lb Member Capacity DF-L No.2 2X10 CL CF Ci Cr KF φ λ Fb =900 psi 1.0 1.1 1.0 1.15 2.54 0.85 0.8 1139 psi Fv =180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi E =1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psi Emin =580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi Depth, d =9.25 in Width, b =1.5 in Cross-Sectonal Area, A =13.875 in2 Moment of Inertia, Ixx =98.9316 in4 Section Modulus, Sxx =21.3906 in3 Allowable Moment, Mall = Fb'Sxx =2029.4 lb-ft DCR=Mu/Mall =0.20 < 1 Satisfactory Allowable Shear, Vall = 2/3Fv'A =1665.0 lb DCR=Vu/Vall =0.17 < 1 Satisfactory Design Value Adjusted Value projects@evengineersnet.com http://www.evengineersnet.com Siesmic Loads Check Roof Dead Load 10 psf % or Roof with Pv 13% Dpv and Racking 3 psf Average Total Dead Load 10.4 psf Increase in Dead Load 1.6%OK Limits of Scope of Work and Liability The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. We have based our structural capacity determination on information in pictures and a drawing set titled PV plans - Monika Stamp. The analysis was according to applicable building codes, professional engineering and design experience, opinions and judgments. The calculations produced for this Structure's assessment are only for the proposed solar panel installation referenced in the stamped plan set and were made according to generally recognized structural analysis standards and procedures. projects@evengineersnet.com http://www.evengineersnet.com 01/31/2026 RE: Structural Certification for Installation of Residential Solar Monika Stamp:1009 W River Ln, Santa Ana, CA 92706 Attn: To Whom It May Concern Design Criteria Code 2025 California Residential Code (ASCE 7-22) Risk category II Wind Load (component and Cladding) Roof Dead Load Dr 10 psf V 95 mph PV Dead Load DPV 3 psf Exposure B Roof Live Load Lr 20 psf Ground Snow S 4 psf If you have any questions on the above, please do not hesitate to call. Sincerely, Eugene Munyanziza, P.E.Signed 01/31/2026 EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2026 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. From the field observation report, the roof is made of Composition shingle roofing over roof plywood supported by 2X10 Rafters at 12 inches. The slope of the roof was approximated to be 18 degrees. After review of the field observation data and based on our structural capacity calculation, the existing roof framing has been determined to be adequate to support the imposed loads without structural upgrades. Contractor shall verify that existing framing is consistent with the described above before install. Should they find any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity calculations were done in accordance with applicable building codes. projects@evengineersnet.com http://www.evengineersnet.com Structural Letter for PV Installation Date:01/31/2026 Job Address:1009 W River Ln Santa Ana, CA 92706 Job Name:Monika Stamp Job Number:013126MS Scope of Work Table of Content Sheet 2 Cover 3 Attachment Uplift checks 4 Roof Framing Check 5 Seismic Check and Scope of work Engineering Calculations Summary Code 2025 California Residential Code (ASCE 7-22) Risk category II Roof Dead Load Dr 10 psf PV Dead Load DPV 3 psf Roof Live Load Lr 20 psf Ground Snow S 4 psf Wind Load (component and Cladding) V 95 mph Exposure B References NDS for Wood Construction Sincerely, Signed 01/31/2026 Eugene Munyanziza, P.E. EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2026 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. All PV mounting equipment shall be designed and installed per manufacturer's approved installation specifications. projects@evengineersnet.com http://www.evengineersnet.com Wind Load Cont. 95 mph ASCE 7-22 Figure 26.5-1B B 1.0 ASCE 7-22 Sec 26.8.2 0.65 ASCE 7-22 Table 26.10-1 0.85 ASCE 7-22 Table 26.6-1 1.00 ASCE 7-22 Table 26.9-1 12.69 psf 18.0 Degrees 1.5 Conservatively assuming all exposed 0.8 conservatively assuming 10 ft2 effective area Uplift (W)Zone(1,2e)Zone(2r, 2n)Zone(3e)Zone(3r) Fig. 30-3-2 GCp=-1.1 -2 -2 -2.4 Eq. 29.4-7 P=qh(GCp)(γE)(γa)=-16.75 -30.46 -30.46 -36.55 GCp=0.5 Figure 30.3-2 P=qh(GCp)(γE)(γa)=4.19 Equation 29.4-7 Rafter Attachments: 0.6D+0.6W (CD=1.6) Connection Check Attachment max. spacing=6 ft 5/16" Lag Screw Withdrawal Value=266 lbs/in Table 12.2A - NDS 2.5 in DFL Assumed Prying Coefficient 1.4 Allowable Capacity=760 lbs Zone Trib Width Area (ft)Uplift (lbs)Down (lbs) Zone(1,2e)6 16.5 107.6 118.6 Zone(2r, 2n)6 16.5 182.2 118.6 Zone(3e)6 16.5 182.2 118.6 Zone(3r)6 16.5 215.4 118.6 Conservative Max=215.4 <760 CONNECTION IS OK II V= Exposure = 1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift governs γE= γa= KZt = qh= 0.00256KzKztKdKeV2= Pitch = Lag Screw Penetration Risk Category = KZ = Kd = Ke = projects@evengineersnet.com http://www.evengineersnet.com Vertical Load Resisting System Design Roof Framing Rafters Snow Load Fully Exposed pg=4 psf Ct =1.1 Ce =0.9 Is =1.0 pf = 3 psf pfmin. = 2.5 psf ps = 3 psf Conservatively (Cs=1)2.52 plf Max Length, L =12 ft (Rafter maximum Allowable Horizontal Span) Tributary Width, WT =12 in Dr =10 psf 10 plf PvDL =3 psf 18 plf Load Case: DL+0.75(0.6W+0.7S) 0.75(Pnet+Ps)+ Ppvcos(θ)+PDL=29 plf Mdown=460 lb-ft Mallowable = Sx x Fb' (wind)=2334 lb-ft >460 lb-ft OK Load Case: DL+0.7S Ps+ Ppvcos(θ)+PDL=25 plf Mdown=402 lb-ft Mallowable = Sx x Fb' (wind)=2334 lb-ft >402 lb-ft OK Load Case: DL+0.6W Pnet+ Ppvcos(θ)+PDL=30.5 plf Max Moment, Mu=488 lb-ft Mallowable = Sx x Fb' (wind)=3247 lb-ft >488 lb-ft OK Pv max Shear=118.6 lbs Shear, Vu=wL/2+Pv Point Load =287 lbs Max Shear, Vu=wL/2+Pv Point Load =287 lb Member Capacity DF-L No.2 2X10 CL CF Ci Cr KF φ λ Fb =900 psi 1.0 1.1 1.0 1.15 2.54 0.85 0.8 1139 psi Fv =180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi E =1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psi Emin =580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi Depth, d =9.25 in Width, b =1.5 in Cross-Sectonal Area, A =13.875 in2 Moment of Inertia, Ixx =98.9316 in4 Section Modulus, Sxx =21.3906 in3 Allowable Moment, Mall = Fb'Sxx =2029.4 lb-ft DCR=Mu/Mall =0.20 < 1 Satisfactory Allowable Shear, Vall = 2/3Fv'A =1665.0 lb DCR=Vu/Vall =0.17 < 1 Satisfactory Design Value Adjusted Value projects@evengineersnet.com http://www.evengineersnet.com Siesmic Loads Check Roof Dead Load 10 psf % or Roof with Pv 13% Dpv and Racking 3 psf Average Total Dead Load 10.4 psf Increase in Dead Load 1.6%OK Limits of Scope of Work and Liability The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. We have based our structural capacity determination on information in pictures and a drawing set titled PV plans - Monika Stamp. The analysis was according to applicable building codes, professional engineering and design experience, opinions and judgments. The calculations produced for this Structure's assessment are only for the proposed solar panel installation referenced in the stamped plan set and were made according to generally recognized structural analysis standards and procedures. projects@evengineersnet.com http://www.evengineersnet.com Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE EXISTING 100A 100A 7 7 REC460AA PURE-RX IQ8X-80-M-US COVER PROJECT NOTES PROJECT MAP (N.T.S.) 1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703. 2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS 3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED. 4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER OUTAGE. 5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS. 6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE. 7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED. 8 .INVERTER IS EQUIPPED W/ INTEGRATED GFDI, THUS PROVIDING GROUND FAULT PROTECTION 9. ALL CONDUCTORS SHALL BE COPPER AND 75 DEG RATED 10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT. 11. CONDUITS SHOULD BE PAINTED TO MATCH EXISTING ROOF AND WALL COLORS 12.ALL WORK SHALL BE IN ACCORD WITH THE 2022 CBC, 2022 CEC 13. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING MEANS AS PER 230.82(6) 14. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING AND BONDING BETWEEN AC AND DC SYSTEMS AS PER CEC 250.122 15. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122. 16. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS GENERAL NOTES: THIS INSTALLATION SHALL COMPLY WITH THE FOLLOWING CODES: 2025 California Administrative Code (CAC) 2025 California Building Code (CBC) 2025 California Residential Code (CRC) 2025 California Electrical Code (CEC) 2025 California Mechanical Code (CMC) 2025 California Plumbing Code (CPC) 2025 California Energy Code (CEnC) 2025 California Wildland-Urban Interface Code (CWUI) 2025 California Historical Building Code (CHBC) 2025 California Fire Code (CFC) 2025 California Existing Building Code (CEBC) 2025 California Green Building Standards Code (CALGreen) 2025 California Reference Standards Code code summary additional notes space (if needed) N FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER THE ROOF AT 3 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT project description DC SOLAR PHOTOVOLTAIC SYSTEM MAIN SERVICE PANEL CONDUCTORS TYPE CONDUITS TYPE ON ROOF CONDUITS TYPE FROM EQUIPMENT ROOF TYPE ROOF RAFTERS additional system info AC SOLAR SYSTEM SIZE NUMBER OF SOLAR MODULES NUMBER OF INVERTERS SOLAR PANEL MODEL NUMBER INVERTERS MODEL NUMBER ADDITIONAL DC OPTIMIZER MAIN SERVICE PANEL BUS MAIN SERVICE PANEL MAIN C/B NUMBER OF ROOF STORY PROPERTY DETAILS APN LIVING AREA PROPERTY TYPE OCCUPANCY GROUP 1 THWN-2 EMT EMT 00123105 976 sqft RESIDENTIAL R-3 20ATOTAL PV SIZE 2x10" 12" O/C SHINGLE IRONRIDGEMOUNTING SYSTEM N/A 3.22KW 2.68KW AHJ City of Santa Ana CONSTRUCTION TYPE V-B SIGNED ON: Structural Only 02/14/2026 Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE COMBINER BOX PAGE 9 Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE SOLAR RACKING PAGE 10 SIGNED ON: Structural Only 02/14/2026 Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE SOLAR ATTACHMENT PAGE 11 SIGNED ON: Structural Only 02/14/2026 Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE SOLAR GROUNDING PAGE 12 SIGNED ON: Structural Only 02/14/2026 Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE certifications PAGE 13 SIGNED ON: Structural Only 02/14/2026 REC460AA PURE-RX IQ8X-80-M-US IQ8X-80-M-US REC460AA PURE-RX 7 REC460AA PURE-RX (E) DRIVEWAY (E) PROPERTY LINE 3' 3' 3'3' 3' ARRAY 1 ARRAY 2 MSP (N)PCB (E)SSP garage (E) Pool main house ADU Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE EXISTING 100A 100A 7 IQ8X-80-M-US 2x10" 12" O/C SHINGLE ARRAY #2 PITCH AZIMUTH PANEL MODEL ADDITIONAL EQUIPMENT 18 DEG 180 DEG 5 5 ARRAY #1 PITCH AZIMUTH PANEL MODEL ADDITIONAL EQUIPMENT 2 2 18 DEG 0 DEG PV PANEL PLOT PLAN Scale: 3/32" = 1'-0" PV-1 PLOT PLAN Site Plan N ROOF COVERAGE TOTAL ROOF AREA (SQ.FT.) -1103 SOLAR AREA (SQ.FT.) - 148 % OF COVERED AREA - 13.4% 3' working clearance in front of equipment is required by CEC 110.26 EQUIPMENT INFORMATION <LEGEND> NEWPV COMBINER BOX-<PCB> SERVICE SUB PANEL-<SSP>EXISTING FIRE SETBACK'S ROOF TYPE RAFTER SIZE BUS MAIN BREAKERMAIN SERVICE PANEL-<MSP> INVERTER W River Ln JBOX SIGNED ON: Structural Only 02/14/2026 Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE 7 PV-2.1 STRINGING LAYOUT and fire pathwayN B.CIRCUIT #1 36" fire pathway Roof access points shall be located in areas that do not require the placement of ground ladders over openings such as window or doors, and located at strong points of building construction in locations where the access point does not conflict with overhead obstructions such as tree limbs, wires, or signs. Roof access point Roof access point Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE EXISTING 100A BREAKER #4 FACILITY GROUND AMP NON CENTER MAIN BREAKER MAIN SERVICE PANEL 120/240V, SINGLE PHASE SERVICE MAIN PANEL BUS MAIN BREAKER UTILITY METER 8' minimum embedment rod at 6' from equipment ground conductor unless existing ground is UFER. 100A 100A 100A 100A EXISTING EXISTING ENPHASE IQ COMBINER 5 SOLAR-ONLY SUB PANEL 125A BUS, 120/240 VAC ENVOY MONITORING SYSTEM 15A BREAKER 20A 2P PV BREAKER 3/4" EMT CONDUIT (3)#10 AWG THWN-2 Conductors (1)#8 AWG THWN-2 Ground J BOX NEMA 3R WIRES EXPOSED TO FREE AIR UNDER ARRAY Enphase Q-Cable (2) #12 AWG Conductors (1) #6 AWG Bare Copper Ground BRANCH #1 3/4" EMT CONDUIT (2) #10 AWG THWN-2 Conductors (1) #8 AWG THWN-2 Ground existing SERVICE SUB PANEL SINGLE PHASE 120/240V 125A BUS NEMA 3R (N) 2 POLE PV BREAKER installed in slot furthest from main input 20A EXISTING 1 1/4" PVC CONDUIT (3) #3 AWG THWN-2 Conductors (1) #8 AWG THWN-2 Ground IQ8X-80-M-US REC460AA PURE-RX 7 PV-2.2 SINGLE LINE DIAGRAM NOTE:Equipment is "New" unless otherwise noted. All PV system wires shall be protected against physical damage NOTE:Terminations shall be rated 75 degree NOTE:MINIMAL CONDUCTOR HEIGHT TO BE 7/8" ABOVE THE ROOF SURFACE ADDITIONAL NOTES PV PANEL AND EQUIPMENT MODEL NUMBER,QUANTITY B.CIRCUIT #1 ROOF ATTACHMENT ROOF SURFACE per attachment detail PV MODULE 4''X12'' Blocking 2" ROOF SUPPORT RAFTERS .2x10" 12" O/C Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE RAFTER 3/8" X 3/4" SS Hex Bolt 3/8" SS Flat Washer 1 Layer of 5/16"SS Lag Bolt Min 2.5" Embed into framing Member Threaded Fast Jack BaseRAFTERS .2x10" 12" O/C SHINGLE PV-3 ARRAY LAYOUT & DETAILS ARRAY LAYOUT Scale:1/8" = 1'-0" N ARRAY MOUNTING CROSS SECTION ROOF ATTACHMENT NOTE: Footing placement is estimated. Exact footing placement tbd by installers at time of install. 18° Roof Attachment fast jack on 12" O.C. Rafters PV Railing 72" Max Rail Span 12" Max Rail Cantilever THE HEIGHT OF PV MODULE FROM ROOF DECK SHALL BE 6" SIGNED ON: Structural Only 02/14/2026 NOTE: 1. PRIOR TO COMMENCEMENT OF WORK, THE CONTRACTOR SHALL VERIFY THE FRAMING SIZES, SPACINGS, AND SPANS NOTED IN THE STAMPED PLANS AND ACCOMPANYING CALCULATIONS AND NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPANCIES PRIOR TO STARTING CONSTRUCTION. 2. THESE PLANS ARE STAMPED FOR STRUCTURAL CODE COMPLIANCE OF THE ROOF FRAMING SUPPORTING THE PROPOSED PV INSTALLATION REFERENCED ONLY. THESE PLANS ARE NOT STAMPED FOR WATER LEAKAGE. PV MODULES, RACKING, AND ATTACHMENT COMPONENTS MUST FOLLOW MANUFACTURER GUIDELINES AND REQUIREMENTS. 3. PLEASE SEE THE ACCOMPANYING STRUCTURAL CALCULATIONS REPORT FOR DETAILS REGARDING CALCULATIONS AS WELL AS LIMITS OF SCOPE OF WORK AND LIABILITY. MAXIMUM RATED AC OUTPUT CURRENT:11.06A MAXIMUM OPERATING AC VOLTAGE:240V PHOTOVOLTAIC POINT OF INTERCONNECTION WARNING: DUAL POWER SOURCE. SECOND SOURCE IS PHOTOVOLTAIC SYSTEM Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE PV-4 CODE REQUIRED PV SIGNAGE N CAUTION MULTIPLE SOURCES OF POWER MAIN SERVICE PANEL YOU ARE HERE SERVICE SUB PANEL W River Ln The marking shall comply with 110.21(B). 1. MATERIAL USED FOR THE SIGNAGE SHALL BE REFLECTIVE, WEATHER RESISTANT AND SUITABLE FOR THE ENVIRONMENT. 2. ALL SIGNAGE SHALL HAVE ALL CAPITAL LETTERS WITH MINIMUM 38" LETTER HEIGHT, WHITE ON RED BACKGROUND. 3. MAIN SERVICE DISCONNECT MARKING SHALL BE PLACED ADJACENT TO MAIN SERVICE DISCONNECT IN A LOCATION CLEARLY VISIBLE FROM THE LOCATION WHERE THE LEVER IS OPERATED. 4. MARKING IS REQUIRED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES, AND JUNCTION BOXES TO ALERT THE FIRE SERVICE TO AVOID CUTTING THEM. MARKINGS SHALL BE PLACED EVERY 10', AT TURNS AND ABOVE AND/OR BELOW PENETRATIONS, AND AT ALL DC COMBINER AND JUNCTION BOXES. 5. DO NOT USE SCREWS FOR SIGNAGE ATTACHMENT. USE ONLY APPROVED ADHESIVE. SIGNAGE LOCATIONS: ·MAIN SERVICE PANEL ·INDOOR/OUTDOOR SUB PANEL NEC 705.12(B)(2)(3)(b) SOURCE BREAKER DO NOT RELOCATE THIS OVERCURRENT DEVICE RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM SIGNAGE LOCATIONS: ·MAIN SERVICE PANEL ·INDOOR/OUTDOOR SUB PANEL ·INDOOR OUTDOOR LOAD CENTER SIGNAGE LOCATIONS: ·SHALL BE LOCATED ON OR NO MORE THAN 1M(3 FEET) FROM THE SWITCH SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH ON THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY SIGNAGE LOCATIONS: ·SHALL BE LOCATED ON OR NO MORE THAN 1 M (3 FT) FROM THE SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED. CAUTION:SOLAR CIRCUIT SIGNAGE LOCATIONS: ·EVERY 10" OF CONDUIT AND AT EVERY BEND DO NOT ADD NEW LOADS SIGNAGE LOCATIONS: ·PV PANEL ·MAIN SERVICE PANEL WHEN-705.12(b)(2)(3)(c) SIGNAGE LOCATIONS: ·MAIN SERVICE PANEL SOLAR COMBINER PANEL Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE PAGE 6 STICKER MAP installer use only PV SUPERVISOR STICKER N Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE SOLAR MODULE DATASHEET PAGE 7 Monika Stamp EVERGREEN SOLAR AND HOME BATTERY INC Address:11278 LOS ALAMITOS BLVD, SUITE 707,LOS ALAMITOS, CA 90720 Phone: (562) 666-7174 State License number: 1102899 Expire Date: 03/31/25 License Class: C-46 Email: bryan@evergreen-solar.net Workers Comp: ACCREDITED SURETY AND CASUALTY COMPANY INC Policy Number:1AUICA160143417700 Expire Date: 03/20/2024 License holder-Bryan Amburgey 1009 W River Ln Unit #2 Santa Ana, CA 92706 Date: JANUARY 15, 2026 Project Information PV-1 SHEET INDEX PV-2.1 PV-2.2 PV-3 PV-4 From Page 6 Plot Plan Stringing Single line diagram Array Layout Signage Additional Information Data sheets, Certifications... DC SIZE AC SIZE 3.22KW 2.68KW SYSTEM SIZE INVERTER DATASHEET PAGE 8 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 1009 W River Ln, Santa Ana, CA 92706 EVERGREEN SOLAR AND HOME BATTERY INC 1102899 Sona Hovsepyan (833) 219-1020 02/07/2026 ankyesayan@gmail.com