HomeMy WebLinkAbout2210 3%4 N Grand Ave WCC01 - Plan2C3
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
EXISTING EQUIPMENT PLAN
SCALE: 3/8" = 1'-0"
EXISTING & NEW
EQUIPMENT PLANS
NEW EQUIPMENT PLAN
SCALE: 3/8" = 1'-0"
10
"
6'
-
6
"
8"
1'
-
0
"
1'
-
0
"
8"
5"
5"
1'-4"
7'-5"
(E) 59'-0" MONOPINE
(E) T-MOBILE
EQUIPMENT PAD
(E) WROUGHT
IRON FENCE
(E) T-MOBILE
UTILITY H-FRAME (TYP)
(E) STORM DRAIN
(E) TOWER FOUNDATION PAD
(E) GRAVEL SURFACE
(E) T-MOBILE
CIENA BOX
(E) T-MOBILE
SERVICE LIGHT (TYP)
(E) T-MOBILE
TELCO BOX
(E) T-MOBILE
PPC CABINET
(E) CABLE TRAY
(BY OTHERS)
(E) T-MOBILE
PURCELL CABINET
(E) T-MOBILE
FIBER CABINET
(E) T-MOBILE
GPS ANTENNA
(E)
T-MOBILE
RBS 6131
CABINET
(E)
T-MOBILE
BTS CABINET
(E)
T-MOBILE
6160
RADIO
CABINET
(E)
T-MOBILE
B160
BATTERY
CABINET
(E) ACCESS GATE
(E) CMU WALL
10' SETBACK FROM
BATTERY CABINET
(E) PARKING
(TYP)
NORTH
10
"
6'
-
6
"
8"
1'
-
0
"
1'
-
0
"
8"
5"
5"
1'-4"
7'-5"
(E) 59'-0" MONOPINE
(E) T-MOBILE
EQUIPMENT PAD
(E) WROUGHT
IRON FENCE
(E) T-MOBILE
UTILITY H-FRAME (TYP)
(E) STORM DRAIN
(E) TOWER FOUNDATION PAD
(E) GRAVEL SURFACE
(E) T-MOBILE
CIENA BOX
(E) T-MOBILE
SERVICE LIGHT (TYP)
(E) T-MOBILE
TELCO BOX
(E) T-MOBILE
PPC CABINET
(E) CABLE TRAY
(BY OTHERS)
(E) T-MOBILE
PURCELL CABINET
(E) T-MOBILE
FIBER CABINET
(E) T-MOBILE
GPS ANTENNA
(E)
T-MOBILE
RBS 6131
CABINET
(E)
T-MOBILE
BTS CABINET
(E)
T-MOBILE
6160
RADIO
CABINET
(E)
T-MOBILE
B160
BATTERY
CABINET
(E) ACCESS GATE
(E) CMU WALL
10' SETBACK FROM
BATTERY CABINET
(E) PARKING
(TYP)
NORTH
NOTE:
THE POWER DESIGN FOR ANY AC ELECTRICAL POWER
CHANGES IS TO BE PERFORMED BY OTHERS AND IS SHOWN
HERE FOR REFERENCE PURPOSES ONLY. T-MOBILE IS
SOLELY RESPONSIBLE FOR THE ELECTRICAL POWER DESIGN.NOTE:
ESS IS COMPLIANT WITH CFC 1207.5.1
FOR SIZE AND SEPARATION.
BATTERY LOADING IN EXISTING BATTERY CABINET:
·(12) EXISTING LEAD-ACID BATTERIES = 12 * (123 lb) = 1476 lb
·(8) NEW LITHIUM-ION BATTERIES = 8 * (91 lb) = 728 lb
·THE PROPOSED LOADING IS 49% OF THE EXISTING
LOADING THEREFORE THE EXISTING BATTERY CABINET IS
ADEQUATE
NOTES:
·REMOVE THE (12) EXISTING VALVE-REGULATED
LEAD-ACID BATTERIES IN THE EXISTING B160 BATTERY
CABINET.
·INSTALL (8) NEW ERICSSON 6624 LITHIUM-ION BATTERIES
IN THE EXISTING B160 BATTERY CABINET.
EXISTING T-MOBILE
VALVE-REGULATED
LEAD-ACID (VRLA)
BATTERIES TO BE
REPLACED (12 TOTAL)
(P) ERICSSON 6624
LITHIUM-ION BATTERIES
(8 TOTAL)
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------
2C4
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
BATTERY SPECS
NOTES:
1.BATTERY TERMINALS - ELECTRICAL CONNECTION BETWEEN CELLS ON SEPARATE
LEVELS OR RACKS SHALL NOT PUT MECHANICAL STRAIN ON THE BATTERY TERMINALS.
2.VENTS - EACH VENT CELL SHALL BE EQUIPPED WITH A FLAME ARRESTOR.
3.SEALED CELLS - WHERE A BATTERY IS CONSTRUCTED SUCH THAT EXCESSIVE
ACCUMULATION OF PRESSURE COULD OCCUR WITHIN THE CELL DURING OPERATION, A
PRESSURE RELIEF VENT SHALL BE PROVIDED.
4.VENTILATION - PROVISION APPROPRIATE TO THE BATTERY'S TECHNOLOGY SHALL BE
MADE FOR SUFFICIENT DIFFUSION AND VENTILATION AND GASSES FROM THE BATTERY,
IF PRESENT, TO PREVENT THE ACCUMULATION OF AN EXPLOSIVE MIXTURE.
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------
2C5
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
ESS DETAILS
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------
2C5A
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
ESS DETAILS
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------
2C5B
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
ESS DETAILS
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------
2C6
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
ESS DETAILS
6624
6624
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------
2C7
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
ESS DETAILS
6624
6624
6624
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------
2E1
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
PANEL SCHEDULE &
ONE-LINE DIAGRAM
PANEL SCHEDULE
NOT TO SCALE
PANEL SCHEDULE, TABLE 1207.1.3 & BATTERY CALCULATIONS
NOT TO SCALE
ESS IS LOCATED OUTDOORS ON AN
EQUIPMENT PAD. ESS IS NOT
LOCATED IN A HABITABLE AREA.
NOTES
·DISCONNECTS (CBS) INSIDE THE B160 CABINET
PER INDIVIDUAL BATTERY STRING - ALL ARE
EXISTING AND TO BE RE-USED.
·ESS IS DC, NOT AC, THEREFORE IT SHOULD NOT BE
INCLUDED IN THE MAINS LOAD CALCULATION.
ESS/B160 IS CHARGED BY THE 6160 ALREADY IN
THE LOAD TABLE.
OVERVIEW OF BMS OPERATION
IN BATTERY ENERGY STORAGE SYSTEMS, ONE OF THE MOST IMPORTANT HAZARD
BARRIERS HELPING TO ENSURE SAFETY IS THE BATTERY MANAGEMENT SYSTEM
(BMS). THE BMS PROVIDES PRIMARY THERMAL RUNAWAY PROTECTION BY
ENSURING THAT THE BATTERY SYSTEM OPERATES WITHIN A SAFE RANGE OF
PARAMETERS SUCH AS ITS STATE OF CHARGE AND TEMPERATURE.
IN A UL 9540 LISTED BATTERY ENERGY STORAGE SYSTEM, THE BMS MONITORS,
CONTROLS AND OPTIMIZES THE PERFORMANCE OF BATTERY MODULES AND
DISCONNECTS THEM FROM THE SYSTEM IN THE EVENT OF ABNORMAL CONDITIONS.
THE BMS ALSO PROVIDES CHARGE AND DISCHARGE MANAGEMENT OF THE
BATTERIES.
IN CASE OF UNDERVOLTAGE OR OVERVOLTAGE, OVER-TEMPERATURE, OR
OVERCURRENT CONDITIONS, THE BMS WILL ALARM AND THEN LIMIT THE CHARGE
AND DISCHARGE CURRENT OR POWER.
UNDER EMERGENCY CONDITIONS, THE BMS WILL CEASE OPERATIONS AND
ELECTRICALLY DISCONNECT THE BATTERY.
***NEW BATTERIES ARE TO BE INSTALLED IN THE EXISTING BATTERY CABINET. EXISTING CABINET IS NOT BEING REMOVED FOR THIS SCOPE.***
ONE-LINE DIAGRAM
NOT TO SCALE
BATTERY CABINET IS LOCATED ON AN OUTDOOR PAD AND IS IN COMPLIANCE WITH CEC 706.1(6)
LABELING EXAMPLE ON ESS INTERNAL DISCONNECT IN ESS
DC ONE-LINE DIAGRAM
ELECTRICAL NOTES:
1. ALL NEW CONDUCTORS TO BE INSTALLED SHALL BE
COPPER. ALL CONDUCTORS SHALL BE THHW, THWN, THWN-2,
XHHW, OR XHHW-2 UNLESS NOTED OTHERWISE.
2. CONTRACTOR IS TO FIELD VERIFY ALL EXISTING ITEMS
SHOWN ON THE ELECTRICAL ONE-LINE DIAGRAM AND NOTIFY
THE ENGINEER OF ANY DISCREPANCIES.
3. ALL GROUNDING AND BONDING PER THE CEG.
4. THE POWER DESIGN FOR ANY ELECTRICAL POWER CHANGE
IS TO BE PERFORMED BY OTHERS AND IS SHOWN HERE FOR
REFERENCE PURPOSES ONLY. T-MOBILE IS SOLELY
RESPONSIBLE FOR THE ELECTRICAL; POWER DESIGN SOW.
5. THE E6160AC SUPPORTS AN EXTERNAL BATTERY CABINET
TO SUPPLY BACKUP DC POWER DURING AN AC MAINS
OUTAGE TO THE RECTIFIERS. THE BATTERY CABLE
TERMINALS AND BREAKERS ARE LOCATED AS SHOWN IN
FIGURE 4. EACH BREAKER IS RATED AT 300A. FOR COPPER
WIRES THAT SUPPORT THIS MUCH CURRENT, IT MUST HAVE
A DIAMETER OF AT LEAST 11.684 MM. IT IS BEST TO LOCATE
THE TWO CABINETS ADJACENT TO EACH OTHER TO MINIMIZE
CABLE LENGTH.
NOTE:
THE SECOND 300A BREAKER CONNECTION BETWEEN E6160AC AND B160 SHOULD BE
INSTALLED. THIS IS TO PREVENT BATTERY BREAKERS FROM TRIPPING DURING A COLD
START SCENARIO WHERE INITIAL CURRENT DRAW MAY TRIP THE BATTERY BREAKER AND
REQUIRE FIELD VISIT TO RESET BREAKER.
(E) 6160
RADIO
CABINET
(E)
2P
100A
(E) 120/240, DISTRIBUTION PANEL
(E)
2P
60A
(E)
1P
20A
(E)
1P
20A
(E)
1P
15A
(E) 120/240, 1Ø, 3W, 200A
(E)PPC CABINET NEAR EQUIPMENT AREA
(E) CONDUIT/
CONDUCTORS
(E) SMARTMETER
(E)
(E)
M
(E) 200A, 240V
POWER SOURCE
(E) CONDUIT/
CONDUCTORS
SU
R
G
E
P
R
O
T
E
C
T
O
R
TE
L
C
O
F
A
N
LI
G
H
T
GF
I
(E) B160
BATTERY
CABINET
(E) 1-1/2" CONDUIT
(2#1 + 1#2 GND) FOR 6160 AND
(1#8 + 1#10 GND) FOR B160 (E)
BTS
CABINET
(E) RBS
6131
CABINET
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------
2G1
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MDS
FIN
PROJECT INFORMATION:
LA23642A
2210 3/4 NORTH GRAND AVENUE
SANTA ANA, CA 92705
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 10/09/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ADDRESS JDX COMMENTS203/24/26
WIRE SIZE BURNDY LUG
TYPE HS TYPE 2-YA-2 TYPE XA TYPE YA-2 TYPE GY
#6 AWG GREEN INSULATED
#2 AWG SOLID TINNED
#2 AWG STRANDED
#2/0 AWG STRANDED
#4/0 AWG STRANDED
TYPE VV TYPE VN TYPE NC TYPE SS TYPE GR
YA6C-2TC38
YA3C-2TC38
YA2C-2TC38
YA26-2TC38
YA28-2N
BURNDY GROUND LUG W/
LONG BARREL
(SEE CHART)
NUT
(TYP)
LOCK WASHER
(TYP)TYPE VS
BURNDY TWO HOLE LUG W/
LONG BARREL
(SEE CHART)
BARE WIRE TO BE
NO-OX AT BOTH ENDS
STRANDED (GREEN INSULATED) ONLY FOR #6 AWG
(SEE CHART)
TYPE VB TYPE PT TYPE GT²
BOLT SIZE
1/2" - 16 NC S 2 BOLT
3/8" - 16 NC S 2 BOLT
3/8" - 16 NC S 2 BOLT
3/8" - 16 NC S 2 BOLT
3/8" - 16 NC S 2 BOLT
HEAT SHRINK
(CLEAR)
GROUNDING
CONDUCTOR
GROUND BAR BOLT
(SEE CHART)
(TYP)
STAINLESS STEEL BOLT
(TYP)
2-HOLE CRIMP/
COMPRESSION
CONNECTOR
STAINLESS STEEL
FLAT WASHER
(TYP)
GROUND
BAR
STAINLESS STEEL
BELLVILLE WASHER
(TYP)
STAINLESS STEEL
FLAT WASHER
(TYP)
STAINLESS STEEL NUT
(TYP)
STAINLESS STEEL BOLT
STAINLESS STEEL
FLAT WASHER
DRAGON TOOTH WASHER
(TYP)STEEL
3/8-11x1" TAMPER
RESISTANT BOLT
(TYP)
INSULATORS
SEE NOTE 2.
(TYP)
WALL BRACKET
(TYP)
2-HOLE CRIMP/
COMPRESSION
CONNECTOR
STAINLESS STEEL
BELLVILLE WASHER
(TYP)
STAINLESS STEEL
FLAT WASHER
(TYP)
STAINLESS STEEL NUT
(TYP)
STAINLESS STEEL
SELF-DRILLING
METAL SCREW
(TYP)
UNIVERSAL COPPER
GROUND BAR (4"x20")
LOCK WASHER
P/N M10
(TYP)
TW0-HOLE
COMPRESSION LUG
2-HOLE CRIMP/
COMPRESSION
CONNECTOR
DRAGON TOOTH
WASHER
(TYP)
METALLIC OBJECT
STAINLESS STEEL
FLAT WASHER
(TYP)
NOTE: MINIMUM OF
3 THREADS TO BE
VISIBLE
(TYP)
2 HOLE LONG
BARREL TINNED
SOLID COPPER
LUG
(TYP)
S/S NUT
(TYP)
S/S SPLIT
WASHER
(TYP)
S/S FLAT
WASHER
(TYP)
TIN COATED SOLID
COPPER BUS BAR
CHERRY INSULATOR
INSTALLED IF REQUIRED
S/S FLAT
WASHER
(TYP)
S/S BOLT
(TYP)
NOTE:
1. ERICO EXOTHERMIC "MOLD TYPES" SHOWN HERE ARE EXAMPLES. CONSULT WITH CONSTRUCTION MANAGER
FOR SPECIFIC MOLDS TO BE USED FOR THIS PROJECT.
2. MOLD TYPE ONLY TO BE USED BELOW GRADE WHEN CONNECTING GROUND RING TO GROUND ROD.
CADWELD GROUNDING CONNECTIONS
NOT TO SCALE
SIGNAGE
NOT TO SCALE
NOTES:
1. ALL GROUNDING LUGS ARE TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. ALL
HARDWARE BOLTS, NUTS, LOCK WASHERS SHALL BE STAINLESS STEEL. ALL HARDWARE
ARE TO BE AS FOLLOWS: BOLT, FLAT WASHER,GROUND BAR, GROUND LUG, FLAT WASHER
AND NUT.
MECHANICAL LUG CONNECTION
NOT TO SCALE
LUG DETAIL
NOT TO SCALE
SINGLE CONNECTOR AT METALLIC/STEEL OBJECTS
SINGLE CONNECTOR AT STEEL OBJECTS
SINGLE CONNECTOR AT GROUND BARS
HARDWARE DETAIL (EXTERIOR CONNECTIONS)
NOT TO SCALE
NOTES:
1. DOWN LEAD (HOME RUN) CONDUCTORS ARE NOT TO BE INSTALLED ON CROWN CASTLE
USA INC. TOWER, PER THE GROUNDING DOWN CONDUCTOR POLICY QAS-STD-10091. NO
MODIFICATION OR DRILLING TO TOWER STEEL IS ALLOWED IN ANY FORM OR FASHION,
CAD-WELDING ON THE TOWER AND/OR IN THE AIR IS NOT PERMITTED.
2. OMIT INSULATOR WHEN MOUNTING TO TOWER STEEL OR PLATFORM STEEL
USE INSULATORS WHEN ATTACHING TO BUILDINGS OR SHELTERS.
GROUND BAR DETAIL
NOT TO SCALE
GROUNDING DETAILS
03/24/26
s<s<.J-b.J-b,,.a=,,.a=--------