HomeMy WebLinkAbout1610 E St Andrew Pl #240 - Plan
April 9, 2025
This form grants the following Renault and Moran Construction, LLC dba RAM Construction employees
authorization to act on behalf of Matthew Renault and RAM Construction for the purpose of securing
permits and calling inspections for construction with General B License #1038156:
Steve Tartaglini, Jason Downing, Matthew Lang, Vanessa Cerna, Adam Martinez, Chad Lessman, Robert Bellucci,
Joselyn Lopez, Jerome Thormann, Alex Norfleet, Luke Slater, Gary D’Aiello, Ariel Rios, Jason Muir, Kenneth Cobb,
Saul Hernandez, Lopan Deitner, Melisa Tatarevic, Joe Piane, Michael Ramirez, Arthur Bernabeo, Nick Vaters,
Mason Tartaglini, Nichole Haeberle, Caroline Coffer, Mark Martin, Raul Carrasco.
Please allow this letter to grant access to pay fees, pull permits, submit permits and other governmental
actions required on behalf of RAM Construction to complete contracted construction projects.
Thank you
Matthew Renault, Principal
License#1038156
Please See Attached For
(CA Civil Code Section 1189)
Renault and Moran Construction LLC
20 Executive Park Suite 250, Irvine, CA 92614
949. 418.7688
License #1038156
CITY OF SANTA ANA
Planning and Building Agency
Certificate of Acknowledgment
California
A notary public or other officer completing this certificate verifies only the
identity of the individual who signed the document to which this certificate
is attached, and not the truthfulness, accuracy, or validity of that document.
State of California
County of Orange
Approved
FOR PERMIT ISSUANCE
Master ID:
Date:
On efore me, Steve Ober 1 angler, AVoimry Pu b l i c
personally appeared /" r a ITh e wy0 n r'1 n o� U
who proved to me on the basis of satisfactory evidence to be the personO whose name( is/tnr
subscribed to the within instrument and acknowledged to me that he/pep executed the same in
his/4eer7� authorized capacity(ye!s), and that by his/iterft4eir signature(i) on the instrument the
person(}, or the entity upon behalf of which the persono acted, executed the instrument.
I certify under PENALTY OF PERJURY under the laws of the
State of California that the foregoing paragraph is true and correct.
my hand and official seal.
iME OBERLANDER
COMM.02446998 =
Notary Public - California 7°
Z Orange County o
m
Mv Comm. res .June 9, 2027
Signature of Notary Public (Seal)
Optional Section
Note: Cabfo nia state law does not require this section io be completed either in full or in part. Howcz)er, any
information below may prevent the accidental or fraudulent misuse of this certificate with a docuruent for
which the certificate etas riot originally intended for.
This Certificate Is Attached To A Document (Titled/For The Purpose Of) C e-ffer Avlh,9 rt 2' )'O
Ftr''1 p I D y e e'.r fo Ad on Fe L l� o -t 9 AA 6 -,1 s4rvG f1 d ✓! "t d l Ov`1 p l a7C
Z
The Attached Document Has A Date Of a ►
�Co"160co' Pilo' Z
Additional Information:
Cahforniallotarized
YES NO
INSTRUCTIONS:
ORAN GE COUNTY FI RE AUTHORI TY
Plan Submittal Criteria
COMMERCIAL projects, MULTIFAMILY RESIDENTIAL projects
and RESIDENTIAL TRACT developments
· Fill in the project/business address and provide a brief description of the scope of work and type of business operation that will take place.
· Answer questions 1 through 10, read and initial items 11 and 12, then complete and sign the certification section.
· If you answer: - “YES” to any part of questions 1 through 10, submit the type of plan indicated in italics to OCFA.
· In some cases, other plan types not indicated herein may also be necessary depending on specific conditions or operations.
· Visit www.ocfa.org for submittal information and locations. If you need assistance in filling out this form or have questions regarding
requirements for review, please contact OCFA at 714-573-6108 or visit us at 1 Fire Authority Road, Irvine, CA 92602.
Address Suite City
Project Scope/Business Description
1. Construction of a new building, a new story, or increase the footprint of an existing building? Changes to roadways,
curbs, or drive aisles? Addition, relocation, or modification of fire hydrants or fences/gates? Construction within
300 feet of an active or proposed oil well? Fire Master Plan (PR145)
2. Property is adjacent to a wildland area or non-irrigated native vegetation?
Fire Master Plan (PR145); a Fuel Modification Plan may also be required. (PR120, PR124)
3. Located in or < 100’ from a Division of Oil, Gas, and Geothermal Resources (DOGGR) field boundary, < 300’ from
an oil/gas seep, or < 1000’ from a landfill? Methane Work Plan. (PR170)
4. Installation/modification/repair of underground piping, backflow preventers, or fire department connections serving
private fire hydrant/sprinkler/standpipe systems? Underground Plan. (PR470, PR475)
5. Drinking/dining/recreation/meetings/training/religious functions or other gatherings in a room > 750 sq.ft. (> 1,000
sq.ft. for training/adulteducation) or > 49 people? Healthcare/outpatient services for > 5 people who may be unable
to immediately evacuate without assistance? Education for children (academic tutoring for ages 5+ is exempt unless
classified as an E occupancy by the Building Official)? Adult/child daycare? 24-hour care/supervision? Incarceration
or restraint? Hotel/apartment or residential facility with 3+ units and 3+ stories (3-story townhouses/rowhouses
where an independent direct exit to grade is provided for dwelling are exempt)? Congregate housing/dormitories
with 17+ people? High-rise structure (55+ feet to highest occupied floor level)? Architectural Plan (PR200-PR285)
6. Installation/modification of locks delaying or preventing occupants from leaving a space or requiring use of a card,
button, or similar action to open a door in the direction of exit travel? Architectural, Sprinkler, and/or Alarm Plan
depending on the occupancy and type of device installed (PR200-PR280, PR420-PR425, PR500-PR520)
7. Installation/modification/use of spray booths; dust collection; dry cleaning; industrial ovens/drying equipment;
industrial/commercial refrigeration systems; compressed gasses; tanks for cryogenic or flammable/combustible
liquids; vapor recovery; smoke control; battery back-up/charging systems (> 50 gal. electrolyte, > 1,000 lb. lithium
ion); welding/brazing/soldering, open flame torches, cutting/grinding; or other similar operations?
Special Equipment Plan (PR315, PR340-PR382)
8. Storage/use/research with flammable/combustible liquids or other chemicals? Motor vehicle/aircraft
maintenance/repair? Cabinetry/woodworking/finishing facility? Chem Class & floor plan (full architectural plan if
H occupancy); Special Equipment Plans may be necessary. (PR315-PR360, PR232-PR240)
9. Storage or merchandizing areas in excess of 500 sq. ft. where items are located higher than 12’ (6’ for high-hazard
commodities, plastic, rubber, foam, etc.)? High-piled Storage Plan (PR330)
10. Cooking under a Type I commercial hood; installation or modification of a fire extinguishing system located in a
commercial cooking hood? Hood & Duct Extinguishing System, not just the hood mechanical plan. (PR335)
Initial each of the following two items indicating that you have read and understand the statement:
11. *Sprinklers/Alarms: Consult Building/Fire Codes and ordinances to determine sprinkler/alarm requirements; if a system is
required, plans shall be submitted for OCFA review. Existing buildings undergoing remodel must be evaluated by a licensed
Initials contractor to determine if modification is needed; if so, contractor shall submit plans prior to making modifications.
12. Fire Hazard Severity Zone: Consult maps available at building department or on OCFA website to determine if your site is located
in a FHSZ. Buildings in a FHSZ may be subject to special construction requirements detailed in CBC Chapter 7A or CRC R327—
Initials the building department will determine specific requirements.
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name Signature
Phone Number ( ) Date / /
Building Department: If you have verified that all of the questions have been answered accurately as “NO”, and the project does not otherwise require OCFA
review of sprinkler or alarm plans*, then you may accept this signed form as a written release that OCFA review is not required. Should you still require that the
applicant have plans approved by OCFA, please initial here or attach an OCFA referral form and have the applicant submit the form along with the
appropriate plans and fees for OCFA review. 10-08-14 EE
COM
O R A N G E C O U N T Y F I R E A U T H O R I T Y
Plan Referral Form
Required for OCFA to review plans upon the request of the Building Department when
the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”.
City / County Official Requesting Review:
City / County Reference #: Date: __________________________________
City / County: _____________________________________ E-Mail: __________________________________
Contact Name: _____________________________________ Phone #: _________________________________
Title: _____________________________________
** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. **
Reason(s) for Review:
Please describe why OCFA Plan Review is or may be required by the City/County :
OCFA COMMENTS:
No further action required on this specific plan type, based
on information provided on: ____/______/______.
Project to be taken in for OCFA Review.
Other:
Name: _________________________________________
Contact #: ______________________________________ Date: _________________________________
OCFA Authorization
Updated: 06/02/2020 rs
&
<
@
(E)
#
Ø
AB
ABV
A/C
A.C.
ACT
ACOUS
ADJ
ADA
AFF
ALT
ALUM
ANOD
A.P.
APPROX
ARCH
ASPH
AV
BATT
BD
BITUM
BLDG
BLK
BLKG
BM
BOT
BR
BSMT
B.U.R.
CAB
CARP
CATV
C.B.
CCTV
CEM
CER
CFM
CL
CLG
CLO
CLR
CMU
CNTR
COL
CONC
CONN
CONST
CONT
CONTR
CORR
C.T.
CTSK
C.W.
(D)
D
DATA
DBL
DEMO
DET
DIA
DIM
DISP
DN
D.O.
DR
DS
D.S.P.
DW
DWG
DWR
(E)
EA
EJ
ELEC
ELEV
EMER
ENCL
EPO
E.O.S.
EQ
EQUIP
EXIST
EXP
EXPO
EXT
F.A.
F.D.
FDN
FEC
FF
F.G.
FHC
FIN
FLR
FLUOR
F.O.C.
F.O.F.
F.O.M.
F.O.S.
FPRF
FR
FS
FT
FTG
FURN
FURR
GA
GALV
GC
GFI
GL
GND
GR
GWB
GYP
H
H.B.
H.C.
HDWR
HDWD
HM
HORIZ
HR
HT
HVAC
H.W.
AND
ANGLE
AT
EXISTING
NUMBER
DIAMETER OR ROUND
PERPENDICULAR
ANCHOR BOLT
ABOVE
AIR CONDITIONING
ASPHALT CONCRETE
ACOUSTICAL CEILING TILE
ACOUSTICAL
ADJACENT
AMERICANS WITH DISABILITIES ACT
ABOVE FINISH FLOOR
ALTER OR ALTERNATE
ALUMINUM
ANODIZED
ACCESS PANEL
APPROXIMATE
ARCHITECTURAL
ASPHALT
AUDIO VISUAL
BATT INSULATION
BOARD
BITUMINOUS
BUILDING
BLOCK
BLOCKING
BEAM
BOTTOM
BEDROOM
BASEMENT
BUILT UP ROOFING
CABINET
CARPET
CABLE TELEVISION
CATCH BASIN
CLOSED CIRCUIT TELEVISION
CEMENT
CERAMIC
CUBIC FEET PER MINUTE
CENTER LINE
CEILING
CLOSET
CLEAR
CONCRETE MASONRY UNIT
CENTER
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
CONTRACTOR
CORRIDOR
CERAMIC TILE
COUNTERSUNK
COLD WATER
DEMOLISH
DEEP, DEPTH
DATA COMMUNICATIONS
DOUBLE
DEMOLISH / DEMOLITION
DETAIL
DIAMETER
DIMENSION
DISPENSER
DOWN
DOOR OPENING
DOOR
DOWNSPOUT
DRY STANDPIPE
DISHWASHER
DRAWING
DRAWER
EXISTING
EACH
EXPANSION JOINT
ELECTRICAL
ELEVATION
EMERGENCY
ENCLOSURE
EMERGENCY POWER OFF
EDGE OF SLAB
EQUAL
EQUIPMENT
EXISTING
EXPANSION
EXPOSED
EXTERIOR
FIRE ALARM
FIRE DRAIN
FOUNDATION
FIRE EXTINGUISHER CABINET
FINISHED FACE
FINISH GRADE
FIRE HOSE CABINET
FINISH
FLOOR
FLUORESCENT
FACE OF CONCRETE
FACE OF FINISH
FACE OF MASONRY
FACE OF STUD
FIREPROOF
FRAME
FULL SIZE
FOOT, FEET
FOOTING
FURNITURE
FURRING, FURRED
GAUGE
GALVANIZED
GENERAL CONTRACTOR
GROUND FAULT INTERRUPT
GLASS, GLAZING
GROUND
GRADE
GYPSUM WALL BOARD
GYPSUM
HIGH
HOSE BIB
HOLLOW CORE
HARDWARE
HARDWOOD
HOLLOW METAL
HORIZONTAL
HOUR
HEIGHT
HEATING, VENTILATION, AND
AIR CONDITIONING
HOT WATER
I.D.
INCL
INFO
INSUL
INT
JAN
JST
JT
KIT
LAM
LAV
L.F.
L.H.
L.R.
LT
LVR
MATL
MAX
MDF
MECH
MFR
MIN
MIR
MISC
M.O.
M.R.
MTD
MTL
MUL
(N)
NA
NIC
NO
NOM
N.S.
N.T.S.
O/
OC
O.D.
O.F.D.
O.H.
OVHD
OPNG
OPP
P.D.
PG
P.L.
P-LAM
PLAS
PLMG
PLYWD
PR
PSF
PT
PTD
PTN
(R)
R
RAD
RCP
R.D.
REF
REFR
REINF
REP
REQD
RESIL
REV
RFG
R.H.
RM
ROM
R.O.
S.C.
SCHED
SDT
S.E.D.
S.M.D.
S.P.D.
S.R.D
S.V.D.
SECT
SEP
SF
SGL
SHR
SHT
SIM
SLDG
SPEC
SQ
S.S.
STD
STL
STRUCT
SUSP
SW
SYM
T
T&G
TBD
TELE
TEMP
TER
THK
THR
T.O.C.
T.O.D.
T.O.P.
T.O.S.
T.S.
T.O.W.
TYP
UON
VCT
VERT
VEST
VIF
VOL
W/
W.C.
WD
W.H.
W/O
WP
WPM
W.S.P.
WT
INSIDE DIAMETER
INCLUDING
INFORMATION
INSULATION
INTERIOR
JANITOR
JOIST
JOINT
KITCHEN
LAMINATE
LAVATORY
LINEAL FOOT
LEFT HAND
LIVING ROOM
LIGHT
LOUVER
MATERIAL
MAXIMUM
MEDIUM DENSITY FIBER BOARD
MECHANICAL
MANUFACTURER
MINIMUM
MIRROR
MISCELLANEOUS
MASONRY OPENING
MOISTURE RESISTANT
MOUNTED
METAL
MULLION
NEW
NOT APPLICABLE
NOT IN CONTRACT
NUMBER
NOMINAL
NO SCALE
NOT TO SCALE
OVER
ON CENTER
OUTSIDE DIAMETER
OVERFLOW DRAIN
OVERHAND
OVERHEAD
OPENING
OPPOSITE
PLANTER DRAIN
PAINT GRADE
PROPERTY LINE
PLASTIC LAMINATE
PLASTER
PLUMBING
PLYWOOD
PAIR
POUNDS PER SQUARE FOOT
PAINT
PAINTED
PARTITION
RELOCATED
RISER
RADIUS
REFLECTED CEILING PLAN
ROOF DRAIN
REFERNCE
REFRIDGERATOR
REINFORCED
REPRESENTATIVE
REQUIRED
RESILIENT
REVISED
ROOFING
RIGHT HAND
ROOM
ROUGH ORDER OF MAGNITUDE
ROUGH OPENING
SOLID CORE
SCHEDULE
STATIC DISSIPATIVE TILE
SEE ELECTRICAL DRAWINGS
SEE MECHANICAL DRAWINGS
SEE PLUMBING DRAWINGS
SEE SECURITY DRAWINGS
SEE AUDIO-VISUAL DRAWINGS
SECTION
SEPARATION
SQUARE FOOT / FEET
SINGLE
SHOWER
SHEET
SIMILAR
SLIDING
SPECIFICATION
SQUARE
STAINLESS STEEL
STANDARD
STEEL
STRUCTURAL
SUSPENDED
SWITCH
SYMMETRICAL
TREAD
TONGUE AND GROVE
TO BE DETERMINED
TELECOMMUNICATIONS
TEMPERATURE/TEMPERED
TERRAZZO
THICK
THRESHOLD
TOP OF CURB
TOP OF DRAIN
TOP OF PAVEMENT
TOP OF SLAB
TOP OF STEEL
TOP OF WALL
TYPICAL
UNLESS OTHERWISE NOTED
VINYL COMPOSITION TILE
VERTICAL
VESTIBULE
VERIFY IN FIELD
VOLUME
WITH
WATER CLOSET
WOOD
WATER HEATER
WITHOUT
WATERPROOF
WATERPROOF MEMBRANE
WET STANDPIPE
WEIGHT
BUILDING GRID LINES
WINDOW SYMBOL
ROOM NO.
REFERENCE LETTER
DOOR SYMBOL
REVISION NO.
REVISION CLOUD
MATCH LINE
DETAIL NO.
1/A3.2
ROOM NAME
ROOM NO.
ROOM LABEL
SECTION
SECTION NO.
SHEET NO.
AREA REFERENCE
DETAIL NO.
SHEET NO.
DETAIL
EXTERIOR ELEVATION
ELEVATION NO.
SHEET NO.
DIMENSION STRING
INTERIOR ELEVATION
ELEVATION NO.
(TYPICAL)
SHEET NO.CEILING
WORK POINT OR
CONTROL POINT
NORTH ARROW
AR
C
H
I
T
E
C
T
U
R
A
L
N
O
R
T
H
TRUE NORTH
1"
A101
1 Ref
1
Re
f
1 Ref
1
Re
f
1t
0
0
101
ROOM NO.
REFERENCE NO.
A101
1
SIM
1
A101
SIM
A101
1
Ref
1Re
f 1 Re
f
1
Ref
A.F.F.
1t
1'-0"
SHEET NO.
1
Room name
101
N
MISC. SYMBOLS
(D)
(R)
(E)
(N)
INDICATES ITEM TO BE DEMOLISHED
INDICATES ITEM TO BE REMOVED
AND RELOCATED
INDICATES ITEM EXISTING TO
REMAIN
INDICATES NEW ITEM
TYPE
HEIGHT
KEYNOTE
A00.00
CSI DIVISION
SEQUENCED NUMBER
ROOM NAME
ROOM NO.
Room name
101
EXITING + OCCUPANCY
ROOM LABEL
### SF
OCCUPANT LOAD
OCC 1/#
ROOM AREA
CALCULATED ROOM OCC LOAD
OCCUPANT LOAD FACTOR PER CBC
OCCUPANCY PER CBC
PROJECT
LOCATION
HATCHED AREA NOT IN SCOPEAREA OF INTERIOR
ALTERATIONS
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO.CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
2
:
0
4
:
4
4
P
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
G0.01
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
PROJECT INFORMATION
COLLECTORS
-
ABBREVIATIONS
PROJECT INFORMATIONPROJECT TEAM
VICINITY MAP
1610 E ST. ANDREW PLACE, SUITE 240
SANTA ANA, CA 92705
III-B
YES, FULLY SPRINKLERED NFPA 13
2 , AREA OF WORK ON LEVEL 2
LEVEL 02: 25,523 SF
EXISTING USE: B-OFFICE
PROPOSED USE: B-OFFICE
UNSEPERATED
UNLIMITED FLOOR AREA WITH PRIMARY OCCUPANCY "B"
(PER 507.5)
INTERIOR TENANT IMPROVEMENT INCLUDING: NEW NON-
STRUCTURAL INTERIOR PARTITION; DOORS AND FINISHES.
MEP ENGINEERING DRAWINGS TO BE SUBMITTED UNDER
SEPARATE PERMIT
SD (SPECIAL DEVELOPMENT)
31' MAX.
LOCATION:
BUILDING CONSTRUCTION TYPE
FIRE SPRINKLER SYSTEM
# OF FLOORS IN BUILDING:
TOTAL AREA OF WORK :
SEPERATION:
ALLOWABLE FLOOR AREA:
SCOPE OF PROJECT:
ZONING DESIGNATION:
BUILDING HEIGHT:
CODES & REGULATIONS:
2025 CALIFORNIA BUILDING CODE
2025 CALIFORNIA MECHANICAL CODE
2025 CALIFORNIA ELECTRICAL CODE
2025 CALIFORNIA PLUMBING CODE
2025 CALIFORNIA FIRE CODE
2025 CALIFORNIA ENERGY CODE
2025 NFPA 72 (FIRE ALARMS)
2025 NFPA 13 (SPRINKLERS)
03/15/11 ADA REGULATION FOR TITLE III,
CODE OF FEDERAL REGULATIONS (CBC 2025 CH. 11)
03/15/11 ADA REGULATION FOR TITLE II,
FEDERAL REGISTER (CBC 2025 CH. 11)
TENANT
BEN STEEN
COLLECTORS UNIVERSE, INC
1610 E ST. ANDREW PLACE
SANTA ANA, CA 92705
T (949) 525-0773
E bsteen@collectors.com
ARCHITECT
KEITH MULLER, AIA
FORMM
101 N PACIFIC COAST HWY, SUITE 301
EL SEGUNDO , CA 90245
T (619) 204-2036
E keith@formmstudio.com
MECHANICAL AND PLUMBING ENGINEER
JORDAN PONIACHIK
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
T (858) 228-4150
E Jiponiachik@enginova.com
ELECTRICAL ENGINEER
CHRISTIAN RUBIO
ENGINOVA
1044 PIONEER WAY, SUITE E
EL CAJON, CA 92020
T (619) 334-6020
E crubio@enginova.com
CONTRACTOR
STEVE TARTAGLINI
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
T (949) 418-7688
E startaglini@ramconstruction-us.com
BUILDING OWNER
DRAWBRIDGE PACIFIC CENTER, LLC
THREE EMBARCADERO CENTER, #2310
SAN FRANCISCO, CA 94111
T (415) 391-8300
E info@drawbridgerealty.com
PROPERTY MANAGMENT
CHRISTINA BOWREN
JONES LANG LASALLE
1600 E ST ANDREW PLACE SUITE 130
SANTA ANA, CA 92705
T (949) 235-3437
E christina.bowren@jll.com
PROJECT MANAGER
KIEFER SHAFFER
SAVILLS
520 NEWPORT CENTER DR 8TH FLOOR
NEWPORT BEACH, CA 92660
T (714) 306-4290
E kshaffer@savills.us
SCOPE OF WORK DIAGRAM
SYMBOLS DEFERRED SUBMITTALS
1. FIRE ALARM
2. FIRE SPRINKLERS
SHEET INDEX
SHEET
NUM. SHEET NAME IS
S
U
E
F
O
R
1
0
0
%
D
D
IS
S
U
E
F
O
R
P
E
R
M
I
T
RE
V
I
S
I
O
N
1
00 GENERAL
G0.01 PROJECT INFORMATION ⬛ ⬛ ⬛
G0.02 GENERAL NOTES - COMMERCIAL TI ⬛
G0.03 GREEN BUILDING NOTES - COMMERCIAL ⬛
G0.04 EXITING AND OCCUPANCY ⬛ ⬛ ⬛
G0.11 ACCESSIBILITY COMPLIANCE DIAGRAMS ⬛
G0.12 ACCESSIBILITY COMPLIANCE DIAGRAMS ⬛
G0.13 ACCESSIBILITY COMPLIANCE DIAGRAMS ⬛
G0.14 ACCESSIBILITY COMPLIANCE DIAGRAMS ⬛
G0.20 EXISTING SITE PLAN / ACCESSIBLE PATH OF TRAVEL DIAGRAM ⬛
G0.21 EXISTING SITE ENLARGEMENTS ⬛
G0.22 EXISTING SITE DETAILS ⬛
G0.23 EXISTING SITE SURVEY ⬛
G0.24 EXISTING SITE SURVEY ⬛
G0.25 EXISTING SITE SURVEY ⬛
G0.30 EXISTING RESTROOM PLAN - WEST - FOR REFERENCE ONLY ⬛
G0.31 EXISTING ENLARGED RESTROOM PLANS - WEST - FOR REFERENCE ONLY ⬛
G0.32 EXISTING RESTROOM ADA REQUIREMENTS - FOR REFERENCE ONLY ⬛
G0.33 EXISTING DETAILS - MILLWORK - FOR REFERENCE ONLY ⬛
02 ARCHITECTURE
AD2.11 LEVEL 02 - DEMOLITION PLAN ⬛ ⬛
AD2.12 LEVEL 02 - PLAN, REFLECTED CEILING DEMOLITION ⬛ ⬛
A2.21 LEVEL 02 - CONSTRUCTION PLAN ⬛ ⬛
A2.22 LEVEL 02 - REFLECTED CEILING PLAN ⬛ ⬛
A2.23 LEVEL 02 - POWER-DATA PLAN ⬛ ⬛
A2.24 LEVEL 02 - FINISH PLAN ⬛ ⬛
A2.30 ROOF PLAN ⬛ ⬛
A6.00 DOOR SCHEDULE & SPECIFICATIONS ⬛ ⬛
A6.01 SPECIFICATIONS ⬛ ⬛
A7.00 TYP. INTERIOR FRAMING DETAILS ⬛
A7.01 TYP. INTERIOR FRAMING DETAILS ⬛
A7.02 PARTITION DETAILS ⬛
A7.11 DOOR & GLAZING DETAILS ⬛
A7.20 CEILING DETAILS ⬛
A7.40 FINISH WALL, FLOOR & MISCELLANEOUS DETAILS ⬛
03 STRUCTURAL
S0.1. GENERAL NOTES ⬛ ⬛
S0.2. ABBREVIATIONS ⬛
S2.0. PARTIAL MEZZAINE FRAMING PLAN ⬛
S7.0. WOOD FRAMING DETAILS AND SECTIONS ⬛
04 MECHANICAL
M001 MECHANICAL LEGEND, NOTES AND SYMBOLS ⬛ ⬛
M002 MECHANICA NOTES ⬛ ⬛
M010 MECHANICAL SCHEDULES ⬛ ⬛
M020 MECHANICAL ENERGY CODE COMPLIANCE ⬛ ⬛
M120 MECHANICAL SECOND FLOOR OEVERALL PLAN ⬛ ⬛
M220 MECHANICAL SECOND FLOOR DEMOLITION PLAN ⬛ ⬛
M320 MECHANICAL SECOND FLOOR PLAN ⬛ ⬛
M330 MECHANICAL ROOF PLAN ⬛ ⬛
M420 MECHANICAL SECOND FLOOR PIPING PLAN ⬛ ⬛
M520 MECHANICAL SECOND FLOOR ZONING PLAN ⬛ ⬛
M620 MECHANICAL REFLECTED CEILING PLAN ⬛ ⬛
M910 MECHANICAL DETAILS ⬛ ⬛
05 ELECTRICAL
E001. COVER SHEET ⬛ ⬛
E002. LIGHTING SCHEDULE ⬛ ⬛
E003. TITLE 24 FORMS ⬛ ⬛
E101. DEMOLITION PLAN - LEVEL 2 ⬛ ⬛
E201. LIGHTING PLAN - LEVEL 2 ⬛ ⬛
E301. POWER PLAN - LEVEL 2 ⬛ ⬛
E501. EMERGENCY EGRESS PLAN - LEVEL 2 ⬛ ⬛
E701. LIGHTING CONTROL DETAILS ⬛ ⬛
E801. SINGLE LINE DIAGRAM ⬛ ⬛
E901. PANEL SCHEDULES ⬛ ⬛
06 PLUMBING
P001 PLUMBING LEGEND, NOTES, SCHEDULES AND SYMBOLS ⬛
P002 PLUMBING NOTES AND SCHEDULES ⬛
P420 PLUMBING SECOND FLOOR PLUMBING PLAN ⬛
P910 PLUMBING DETAILS ⬛
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
2026-0130 ISSUE FOR PERMIT
A 2026-0306 REVISION 1
A
A
A
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
1
5
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.02
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
GENERAL NOTES -COMMERCIAL
TI
COLLECTORS
-
DIVISION 1 - GENERAL CONDITIONS
1.1 SCOPE OF WORK
A. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE EXTENT, NATURE,
AND SCOPE OF WORK DESCRIBED IN THE CONTRACT DOCUMENTS. THE GENERAL
CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY TO
EXECUTE ALL WORK SHOWN ON THESE DRAWINGS EXCEPT WHERE NOTED AS NOT IN
CONTRACT (NIC). HE SHALL BE RESPONSIBLE FOR COORDINATING HIS WORK WITH THAT OF
ALL OTHER TRADES INCLUDING THOSE OPERATING UNDER SEPARATE CONTRACTS WITH THE
LANDLORD AND/OR TENANT. ALL WORK SHALL BE PERFORMED BY SKILLED AND QUALIFIED
WORKMEN IN ACCORDANCE WITH THE BEST PRACTICES OF THE TRADES INVOLVED.
B. THE DRAWINGS SHALL BE RECOGNIZED AS DIAGRAMMATIC IN NATURE AND NOT
COMPLETELY DESCRIPTIVE OF ALL REQUIREMENTS FOR CONSTRUCTION. WHATEVER WORK
THAT MAY BE SPECIFIED AND NOT DRAWN OR DRAWN AND NOT SPECIFIED SHALL BE
EXECUTED AS FULLY AS IF DESCRIBED IN BOTH THESE WAYS. SHOULD ANY WORKMANSHIP
OR MATERIAL BE NECESSARY THAT IS NOT EITHER DIRECTLY OR INDIRECTLY NOTED IN
THESE SPECIFICATIONS OR SHOWN ON THE DRAWINGS BUT IS NEVERTHELESS NECESSARY
FOR PROPERLY CARRYING OUT THE OBVIOUS INTENTION THEREOF; CONTRACTOR SHALL
UNDERSTAND IT TO BE IMPLIED AND SHALL PROVIDE FOR THE SAME AS FULLY AS IF IT WERE
PARTICULARLY DESCRIBED OR DELINEATED.
C. THE GENERAL CONTRACTOR SHALL REVIEW ALL CONSTRUCTION DOCUMENTS AND
VERIFY ALL GOVERNING DIMENSIONS AT THE BUILDING. HE SHALL EXAMINE ALL ADJOINING
WORK OR AREAS UPON WHICH THE PERFORMANCE OF HIS WORK IS IN ANY WAY
DEPENDENT. ANY VARIATIONS OR DISCREPANCIES SHALL BE REPORTED, WITH ALL DUE
EXPEDIENCY, TO ARCHITECT PRIOR TO THE FABRICATION OR ERECTION OF THE WORK IN
QUESTION.
D. ALL WORK IS TO BE PERFORMED IN STRICT ACCORDANCE WITH RULES AND
REGULATIONS OF GOVERNMENTAL AGENCIES AND SHALL CONFORM TO ALL CITY, COUNTY,
STATE AND FEDERAL CODES AND ORDINANCES. ALL FEES, TAXES, AND PERMIT
APPLICATIONS WITH THE APPROPRIATE GOVERNMENTAL AGENCIES SHALL BE THE
RESPONSIBILITY OF THE GENERAL CONTRACTOR UNLESS OTHERWISE NOTED.
1.2 THESE GENERAL CONDITIONS SHALL APPLY TO ALL WORK SHOWN HEREIN, AND SHALL
EXTEND TO ANY CHANGES, EXTRAS, OR ADDITIONS AGREED TO DURING THE COURSE OF
WORK.
1.3 THE AIA STANDARD DOCUMENT A201 ENTITLED "GENERAL CONDITIONS OF THE
CONTRACT FOR CONSTRUCTION" IS MADE PART OF THE GENERAL CONDITIONS.
1.4 USE OF DRAWINGS:
DO NOT SCALE DRAWINGS, DIMENSIONS SHALL GOVERN. LARGE SCALE DETAILS SHALL
GOVERN OVER PLANS AND ELEVATIONS. DIMENSIONS ARE FROM FACE OF FINISH TO FACE
OF FINISH UNLESS OTHERWISE NOTED.
1.5 CONSTRUCTION SCHEDULE:
WITHIN ONE WEEK OF THE AWARD OF THE CONTRACT THE GENERAL CONTRACTOR
SHALL SUBMIT A DETAILED CONSTRUCTION SCHEDULE TO THE ARCHITECT FOR REVIEW.
SCHEDULE SHALL INCLUDE THE ORDER AND ANTICIPATED DELIVERY DATES OF ALL LONG
LEAD TIME MATERIALS. CONTRACTOR SHALL UPDATE THE SCHEDULE NO LESS THAN
WEEKLY THROUGHOUT THE COURSE OF CONSTRUCTION.
1.6 CONSTRUCTION MEETINGS:
CONTRACTORS SHALL BE RESPONSIBLE FOR KEEPING DETAILED WEEKLY MINUTES OF
CONSTRUCTION MEETINGS.
1.7 SITE VISITS:
BIDDERS ARE INSTRUCTED TO VISIT AND INSPECT THE PREMISES PRIOR TO SUBMITTING
THEIR PROPOSALS AND TO FAMILIARIZE THEMSELVES WITH THE CONDITIONS UNDER WHICH
THE WORK WILL BE PERFORMED. NO SUBSEQUENT EXTRAS OR ADDITIONS WILL BE
ALLOWED ON ANY CLAIM FOR LACK OF KNOWLEDGE OF CONDITIONS OR CIRCUMSTANCES
ABOUT WHICH THE BIDDER COULD HAVE INFORMED HIMSELF.
1.8 LIMITATIONS AND EXCLUSIONS:
BIDDER SHALL MAKE KNOWN TO ARCHITECT ANY LIMITATIONS, EXCLUSIONS, OR
MODIFICATIONS TO THE PROJECT DURING THE BID PERIOD OF THE PROJECT. ALL
LIMITATIONS, EXCLUSIONS, OR MODIFICATIONS SHALL BE ITEMIZED IN THE BID PROPOSAL,
OR THEY WILL BE PRESUMED INCLUDED; IN WHICH CASE NO ADDITIONAL MONIES WILL BE
ALLOCATED.
1.9 INSURANCE:
ALL CONTRACTORS INVOLVED IN THIS PROJECT SHALL CARRY PROPERTY DAMAGE AND
PUBLIC LIABILITY INSURANCE AS REQUIRED BY GOVERNMENTAL AGENCIES HAVING
JURISDICTION OVER THE PROJECT AND SHALL COMPLY WITH STATUTORY REQUIREMENTS
FOR DISABILITY AND WORKMEN'S COMPENSATION. CONTRACTORS SHALL COMPLY WITH ALL
RULES AND REGULATIONS DICTATED BY THE LANDLORD. INSURANCE SHALL PROTECT
LANDLORD, TENANT, ARCHITECT AND ANY OTHER ENTITIES REQUESTED TO BE FREE FROM
LIABILITY DUE TO CONTRACTOR'S NEGLIGENCE. A PROPERLY EXECUTED CERTIFICATE OF
INSURANCE, AIA DOCUMENT #G705, SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO THE
COMMENCEMENT OF ANY WORK.
1.10 SUBMITTALS AND SHOP DRAWINGS:
A. THE GENERAL CONTRACTOR SHALL SUBMIT THREE (3) SAMPLES AND / OR SCHEDULES
OF EACH OF THE VARIOUS MATERIALS, HARDWARE, EQUIPMENT, AND FINISHES TO
ARCHITECT FOR REVIEW AND COMMENT. SUBMITTALS INCLUDE, BUT ARE NOT LIMITED TO,
DOORS, HARDWARE, LIGHTING, PLUMBING, ELECTRICAL, MECHANICAL, FINISHES, AND
SPECIALTY EQUIPMENT.
B. THE GENERAL CONTRACTOR SHALL SUBMIT TO ARCHITECT FOR REVIEW AND
COMMENT THREE (3) PRINTS OF ALL FABRICATION, ERECTION, OR INSTALLATION SHOP
DRAWINGS. SHOP DRAWINGS INCLUDE, BUT ARE NOT LIMITED TO, MILLWORK, STRUCTURAL,
LIFE SAFETY, AND HVAC.
C. CONTRACTORS SHALL NOT COMMENCE ANY PORTION OF THE WORK REQUIRING
SUBMISSION OF A SHOP DRAWINGS, PRODUCT DATUM, OR SAMPLE UNTIL THE SUBMITTAL
HAS BEEN REVIEWED BY THE ARCHITECT AND / OR THE APPROPRIATE CONSULTANT.
ARCHITECT SHALL HAVE FIVE (5) BUSINESS DAYS PER REVIEW. INCOMPLETE SUBMITTALS
WILL DELAY REVIEW. DOORS, HARDWARE, AND FRAMES ARE CONSIDERED A SINGLE REVIEW
PACKAGE.
1.11 SUBSTITUTIONS:
THERE SHALL BE NO SUBSTITUTION OF MATERIALS SPECIFIED BY THE ARCHITECT.
WHERE THE TERM "OR EQUAL" IS USED THE ARCHITECT ALONE SHALL DETERMINE EQUALITY
BASED UPON INFORMATION SUBMITTED BY THE CONTRACTOR.
1.12 MANUFACTURER’S INSTRUCTIONS:
A. UNLESS OTHERWISE SPECIFIED, INSTALLATION OF WORK SHALL COMPLY WITH
MANUFACTURER’S PRINTED INSTRUCTIONS AND RECOMMENDATIONS. CONTRACTOR SHALL
OBTAIN AND DISTRIBUTE COPIES OF SUCH INSTRUMENTS TO PARTIES INVOLVED IN
INSTALLATION; AND MAINTAIN ONE SET OF COMPLETE INSTRUCTIONS AT THE JOBSITE
DURING INSTALLATION AND UNTIL COMPLETION.
B. CONTRACTOR SHALL HANDLE, INSTALL, CONNECT, CLEAN, CONDITION, AND ADJUST
PRODUCTS IN STRICT ACCORDANCE WITH MANUFACTURER’S INSTRUCTIONS.
C. CONTRACTOR SHALL PERFORM WORK IN STRICT ACCORDANCE WITH
MANUFACTURER’S INSTRUCTIONS. DO NO OMIT ANY PREPARATORY SET OR INSTALLATION
PROCEDURE, UNLESS SPECIFICALLY MODIFIED OR EXEMPTED BY THE CONTRACT
DOCUMENTS.
1.13 OVER – STOCK:
GENERAL CONTRACTOR TO CONSULT TENANT AND LANDLORD REGARDING OVER-STOCK
MATERIALS FOR FUTURE MAINTENANCE. SUCH ITEMS MAY INCLUDE: CARPET, CARPET
ACCESSORIES, DOOR HARDWARE, CEILING TILE, AND PAINT. UNLESS OTHERWISE NOTED,
PROVIDE OVER – STOCK AS FOLLOWS: CEILING TILE – ONE (1) CASE, CARPET TILE – TWO (2)
CASES PER EACH TYPE SPECIFIED, BROADLOOM CARPET – TO BE DETERMINED.
1.14 BUILDING REGULATIONS:
THE GENERAL CONTRACTOR SHALL COMPLY WITH THE RULES AND REGULATIONS OF THE
BUILDING LANDLORD, AND SHALL COORDINATE THE USE OF ELEVATORS AND LOADING
DOCKS PRIOR TO COMMENCEMENT OF WORK WITH SAME.
1.15 BUILDING PROTECTION:
GREAT CARE SHALL BE EXERCISED TO ASSURE THAT THE BUILDING AND TENANT AREAS
SHALL BE PROTECTED FROM DAMAGE THAT COULD OCCUR BECAUSE OF THIS WORK.
CONTRACTORS SHALL PROVIDE PROTECTION FOR EXISTING AREAS AND NEW WORK AREAS.
ANY DAMAGE DUE TO THE CONTRACTOR’S WORK SHALL BE REPAIRED OR REPLACED AT THE
CONTRACTOR'S SOLE EXPENSE. CONTRACTOR SHALL PROVIDE DUST PROOF BARRICADES
AROUND ALL AREAS OF NEW WORK AS NECESSARY TO PROTECT ADJACENT TENANT AREAS
FROM DAMAGE.
1.16 CUTTING AND DRILLING:
CUTTING, CHASING, DRILLING OR DEMOLITION OF WALLS, SLABS, ETC. REQUIRING THE
USE OF JACK HAMMERS OR OTHER HEAVY HAND OR POWER TOOLS SHALL BE PERFORMED
OUTSIDE REGULAR BUSINESS HOURS ON AN OVERTIME BASIS UNLESS THE LANDLORD AND
ANY AFFECTED TENANT EXPRESSLY PERMIT IT.
1.17 HAZARDOUS MATERIALS
REPORT ANY HAZARDOUS MATERIALS TO THE LANDLORD AND ARCHITECT IMMEDIATELY.
1.18 CLEAN-UP
THE GENERAL CONTRACTOR SHALL AT ALL TIMES KEEP THE PREMISES FREE OF
ACCUMULATION OF WASTE MATERIALS OR RUBBISH CAUSED BY HIS OPERATIONS OR BY
THOSE OF OTHER CONTRACTORS UNDER SEPARATE CONTRACT. CONTRACTOR SHALL
CONFINE HIS OPERATIONS FOR REMOVAL TO SUCH METHODS AS MAY BE AGREEABLE WITH
THE LANDLORD. PREMISES TO BE SWEPT CLEAN ON A DAILY BASIS.
1.19 PUNCH-LIST:
UPON COMPLETION OF THE WORK THE GENERAL CONTRACTOR SHALL PREPARE A
"PUNCH-LIST" OF PENDING CORRECTIONS AND UNSATISFACTORY AND/OR INCOMPLETE
WORK FOR REVIEW AND AMENDMENT BY THE ARCHITECT. RELEASE OF FINAL PAYMENT WILL
BE CONTINGENT ON THE COMPLETION OF THESE ITEMS UNDER THE TERMS OF THE OWNER-
CONTRACTOR AGREEMENT.
1.20 GUARANTEE:
ALL WORK AND MATERIALS SHALL BE GUARANTEED AGAINST DEFECTS IN DESIGN,
WORKMANSHIP AND MATERIALS FOR A PERIOD OF AT LEAST (1) ONE YEAR FROM DATE OF
FINAL ACCEPTANCE AND PAYMENT. ALL DEFECTS OCCURRING IN THE GUARANTEE PERIOD
SHALL BE CORRECTED AT NO COST TO THE TENANT.
1.21 AS BUILT DRAWINGS:
DURING THE COURSE OF CONSTRUCTION, ACTUAL LOCATIONS OF ALL RUNS OF
MECHANICAL AND ELECTRICAL WORK SHALL BE INDICATED TO SCALE IN RED INK ON THE
DRAWINGS, INCLUDING CONCEALED DEVIATIONS FROM THE DRAWINGS. UPON COMPLETION
OF THE PROJECT, INCLUDING THE PUNCH-LIST, THIS DRAWING SET SHALL BE TRANSFERRED
TO ELECTRONIC CAD DRAWINGS. THE CAD DRAWINGS SHALL BE MARKED "AS BUILT SET" AND
RETURNED TO ARCHITECT AND TENANT ON COMPACT DISK. THE ARCHITECT SHALL, WITHIN
FIVE WORKING DAYS OF THE RECEIPT OF THIS SET, GRANT APPROVAL FOR FINAL PAYMENT
TO THE CONTRACTOR OR SHOW REASONABLE CAUSE WHY SUCH APPROVAL IS DENIED.
1.22 SUBSTANTIAL COMPLETION
THE FOLLOWING ARE REQUIRED FOR SUBSTANTIAL COMPLETION:
A. FINAL CLEANING BY A PROFESSIONAL SERVICE
B. AS-BUILT DRAWINGS ON COMPACT DISK
C. A BINDER WITH OPERATION, MAINTENANCE DATA, AND WARRANTIES FOR ALL
INSTALLED SYSTEMS.
D. SPECIFIED QUANTITIES OF MAINTENANCE AND OVER STOCK MATERIALS
E. HVAC BALANCE REPORT
DIVISION 2 - DEMOLITION
2.1 DESCRIPTION OF WORK
PERFORM ALL WORK OF A DEMOLITION NATURE THAT MAY BE REQUIRED OR NECESSARY
TO A FULL AND COMPLETE EXECUTION OF THE WORK, WHETHER OR NOT SHOWN OR
SPECIFIED. EXACT EXTENT OF DEMOLITION MAY NOT BE FULLY INDICATED BY THE
DRAWINGS.
2.2 SALVAGED COMPONENTS:
A. WHERE SHOWN ON DRAWINGS, SALVAGE CONSTRUCTION MATERIALS AND
EQUIPMENT (E.G., LIGHT FIXTURES, DOORS, FRAMES, HARDWARE, ETC.) SUITABLE FOR
REUSE. SALVAGED COMPONENTS SHALL BE CLEANED AND REPAIRED BEFORE REUSING.
B. COORDINATE SALVAGE AND STORAGE OF BUILDING STANDARD CONSTRUCTION
MATERIALS AND EQUIPMENT NOT NECESSARY FOR NEW TENANT CONSTRUCTION WITH
LANDLORD.
2.3 PATCH AND REPAIR:
A. EXISTING CONSTRUCTION WHERE AFFECTED BY DEMOLITION WORK SHALL BE
PROPERLY REMEMBERED, ALIGNED, AND REPAIRED TO LEAVE NO EVIDENCE OF
REMODELING WORK. AREAS AFFECTED OUTSIDE OF TENANT SPACE BY DEMOLITION AND
NEW CONSTRUCTION TO BE REPAIRED SO AS TO LEAVE NO EVIDENCE OF DAMAGE.
INTEGRITY OF NON-TENANT SPACE TO BE MAINTAINED.
B. GENERAL CONTRACTOR SHALL REPAIR ANY FIRE PROOFING DAMAGED DURING THE
COURSE OF DEMOLITION OR CONSTRUCTION SO AS TO MAINTAIN THE ORIGINAL FIRE
RATING.
DIVISION 3 - CONCRETE
A. GENERAL CONTRACTOR TO FURNISH AND INSTALL ALL CONCRETE WORK IN
ACCORDANCE WITH THE “AMERICAN CONCRETE INSTITUTE” (ACI) BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE STANDARD 318-83.
B. CONTRACTOR TO CHECK AND LEVEL CONCRETE FLOOR SURFACE TO A TOLERANCE
NOT EXCEEDING ¼” IN A 10’ - 0” DIAMETER WHEN MEASURED WITH A 10’ - 0” STRAIGHT EDGE.
CONTRACTOR SHALL PATCH AND REPAIR IMPERFECTIONS IN EXISTING CONCRETE SLAB AT
ARCHITECT’S DISCRETION OR AS REQUIRED PRIOR TO INSTALLING FLOOR FINISH PER
MANUFACTURER’S RECOMMENDATIONS. FLOOR SHALL BE LEVEL TO ¼” IN 10’ - 0” DIAMETER
ON A NON-CUMULATIVE BASIS ON ALL AREAS TO RECEIVE STONE OR TILE FLOORING.
DIVISION 6 - WOODWORK AND CABINETRY
6.1 CARPENTRY:
A. GENERAL CONTRACTOR TO FURNISH AND INSTALL ALL WOOD BLOCKING AND OTHER
REINFORCING WHERE INDICATED ON THE DRAWINGS OR WHERE REQUIRED FOR
ADEQUATE SUPPORT OF NEW WORK.
B. ALL WOOD BLOCKING SHALL BE STAMPED "FIRE-RETARDANT" TREATED IN
ACCORDANCE WITH GOVERNING ORDINANCES AND BUILDING CODES.
C. ALL RAISED PLATFORMS MUST BE CONSTRUCTED FROM NON- COMBUSTABLE
MATERIALS.
6.2 ARCHITECTURAL WOODWORK AND CABINETRY:
A. THIS CONTRACTOR TO FURNISH AND INSTALL ALL CUSTOM ARCHITECTURAL
WOODWORK INCLUDING, BUT NOT LIMITED TO:
1. STANDING OR RUNNING TRIM
2. WOOD CABINETS AND HARDWARE
3. DOORS AND HARDWARE
4. WOOD FRAMES
5. SHELVING AND HARDWARE
B. QUALITY AND WORKMANSHIP: ALL MATERIALS AND WORKMANSHIP SHALL BE IN STRICT
ACCORDANCE WITH THE AWS PREMIUM GRADE AS CERTIFIED BY THE WOODWORK INSTITUTE
C. MATERIALS AND FINISHES:
1. MATERIALS AND FINISHES SHALL BE SPECIFIED ON THE DRAWINGS. SAMPLES SHALL
BE SUBMITTED TO ARCHITECT FOR REVIEW AS SPECIFIED IN DIVISION 1 OF THESE
SPECIFICATIONS.
2. WOOD VENEERS TO RECEIVE TRANSPARENT FINISH TO BE PLAIN SLICED AND BOOK
AND END MATCHED, UNLESS OTHERWISE NOTED.
3. MELAMINE COLOR, WHERE SPECIFIED, SHALL BE WHITE AT PLASTIC LAMINATE
MILLWORK AND BLACK AT WOOD VENEER MILLWORK, UNLESS OTHERWISE NOTED.
4. PROVIDE GROMMETS IN COUNTERTOPS ABOVE EACH WALL MOUNTED OUTLET.
GROMMETS TO BE MOCKETT & COMPANY SG SERIES, 1 3/4" HOLE, COLOR BLACK.
5. MILLWORK CABINETS CONSTRUCTION TO BE FLUSH OVERLAY TYPE WITH EUROPEAN
(INVISIBLE) SELF - CLOSING , 170 DEGREE OPENING, HEAVY - DUTY HINGES AND 100 POUND
RATED, FULL EXTENSION SIDE MOUNTED DRAWER SLIDES, UNLESS OTHERWISE NOTED.
JOINTS BETWEEN DOORS AND DRAWERS TO BE 3/32" MAXIMUM WIDTH AND CONSISTENT
THROUGHOUT.
6. SCRIBE COUNTERTOPS AN D SPLASHES TO ADJACENT SURFACES.
7. PROVIDE 1/2" X 1/2" REVEAL WHERE CABINETS MEET ANOTHER SURFACE. REVEAL
COLOR TO MATCH CABINET, UON.
8. MAXIMUM UNSUPPORTED CABINET SHELF WIDTH TO BE 3'-0".
D. SHOP DRAWINGS: CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ARCHITECT’S
REVIEW AS SPECIFIED IN DIVISION 1 OF THESE SPECIFICATIONS.
DIVISION 8 - DOOR, WINDOWS AND GLASS:
8.1
A. THE GENERAL CONTRACTOR SHALL FURNISH AND INSTALL DOORS, FRAMES AND
HARDWARE WHERE SPECIFIED AND DETAILED ON THE DRAWINGS. NEW MATERIALS AND
INSTALLATION OF SAME SHALL MATCH EXISTING WORK EXCEPT WHERE OTHERWISE NOTED.
B. HARDWARE SHALL MATCH EXISTING EXCEPT WHERE SPECIFIED OTHERWISE ON
DRAWINGS. CONTRACTOR TO SUBMIT A FINISH HARDWARE SCHEDULE FOR ARCHITECT'S
REVIEW AND APPROVAL PRIOR TO ORDERING MATERIALS.
C. PROVIDE ¼” MAXIMUM UNDERCUT AT ALL NEW DOORS.
8.2 GLASS AND BORROWED LIGHT PARTITIONS:
A. THE GENERAL CONTRACTOR SHALL FURNISH AND INSTALL ALL GLASS WORK WITH
FRAMES AND HARDWARE AS SPECIFIED AND DETAILED ON THE DRAWINGS. GLASS WORK
EXCEPT WHERE DETAILED OR NOTED OTHERWISE SHALL MATCH EXISTING WORK.
B. ALL GLASS WITHIN 12” OF A DOOR, IN A DOOR, OR WITHIN 18” OF THE FINISHED
FLOOR SHALL BE TEMPERED OR LAMINATED SAFETY GLASS AND LABELED AS SUCH
CLEARLY.
C. SUBMIT SHOP DRAWINGS OF ALL GLASS FRAMING AND GLAZING WORK ALONG WITH
MATERIAL SAMPLES TO ARCHITECT FOR REVIEW PRIOR TO PROCEEDING WITH FABRICATION
WORK.
D. INSTALL TEMPERED GLASS WITH MANUFACTURER’S SEAL LOCATED AT THE LOWER
CORNER OF THE LITE. CONCEAL TONG MARKS, IF ANY.
E. ALL FIRE RATED SAFETY GLAZING SHALL BE “FIRE LITE” FIRE RATED CERAMIC GLASS
AS MANUFACTURED BY TECHNICAL GLASS PRODUCTS, UNLESS OTHERWISE NOTED.
REFER TO DRAWINGS FOR GLASS LITE FIRE RATING.
F. EACH PANE OF SAFETY GLAZING INSTALLED IN HAZARDOUS LOCATIONS SHALL BE
IDENTIFIED BY A MANUFACTURER'S DESIGNATION SPECIFYING WHO APPLIED THE
DESIGNATION, THE MANUFACTURER OR INSTALLER AND THE SAFETY GLAZING
STANDARD. LOCATIONS SPECIFIED IN CBC SECTION 2406.4.1 THROUGH 2406.4.7 SHALL
BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS REQUIRING SAFETY GLAZING
MATERIALS.
DIVISION 9 - FINISHES
9.1 DRYWALL PARTITIONS:
A. THE GENERAL CONTRACTOR SHALL FURNISH AND INSTALL ALL NEW PARTITION,
SOFFIT, AND CEILING CONSTRUCTION WHERE INDICATED ON THE DRAWINGS. NEW
CONSTRUCTION SHALL MATCH THAT OF EXISTING ADJACENT CONDITIONS, IF APPLICABLE,
EXCEPT WHERE NOTED OTHERWISE ON THE DRAWINGS.
B. ALL NEW PARTITION CONSTRUCTION SHALL BE IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS AND SPECIFICATIONS, AND SHALL CONFORM TO
BUILDING STANDARD SPECIFICATIONS WHERE APPLICABLE.
C. THE GENERAL CONTRACTOR SHALL LOCATE AND DESIGNATE ALL NEW AND
REMAINING PARTITIONS AS NOTED ON THE DRAWINGS FOR REVIEW BY ARCHITECT ON SITE
PRIOR TO COMMENCEMENT OF DEMOLITION OR NEW WORK.
D. PARTITIONS SHALL BE PLUMB AND DIMENSIONS SHALL BE WITHIN 1/8” IN 20’ - 0” ALONG
LENGTH OF PARTITIONS. CONTRACTOR SHALL NOT ADJUST DIMENSIONS MARKED “CLEAR”
OR “HOLD” WITHOUT REVIEW BY ARCHITECT.
E. PROVIDE WATER RESISTANT GYPSUM WALL BOARD AT TOILET ROOM PARTITIONS AND
OTHER WET AREAS. PROVIDE TYPE “X” GYPSUM BOARD AT FIRE - RATED ASSEMBLIES.
F. INSTALL GYPSUM WALL BOARD WITH LONG DIMENSIONS PERPENDICULAR TO
FRAMING.
G. NEW AND EXISTING GYPSUM WALL BOARD SHALL BE TAPED AND SANDED WITH NO
VISIBLE JOINTS. SURFACES ARE TO BE FREE OF IMPERFECTIONS AND SHALL HAVE SMOOTH
LEVEL 4 SURFACE READY TO RECEIVE SCHEDULED FINISH. WHERE DEEP TONE PAINT IS
SCHEDULED, SKIM COAT FULL SURFACE OF SUBSTRATE TO LEVEL 5 FINISH. REFERENCE USG
STANDARDS.
H. ALL PENETRATIONS THROUGH FIRE RATED PARTITIONS TO BE PROPERLY FIRE
STOPPED PER CODE.
9.2 CEILINGS SYSTEMS:
A. PATCH AND REPAIR: GENERAL CONTRACTOR TO PATCH AND REPAIR EXISTING CEILING
SYSTEM WHERE AFFECTED BY DEMOLITION OR NEW CONSTRUCTION SO AS TO LEAVE NO
EVIDENCE OF REMODELING WORK.
B. GYPSUM CEILINGS:
1. CEILING SUPPORT SYSTEM SHALL LIMIT DEFLECTION OF
FINISHED CEILING TO LESS THAN 1/260 OF SPAN.
2. ATTACHMENT DEVICES SHALL BE AN APPROVED TYPE,
CAPABLE OF CARRYING FIVE TIMES THE CEILING LOAD OR 100
POUNDS, WHICHEVER IS GREATER.
3. HANGERS SHALL BE PLUMB OR COUNTERSPLAYED AND
SHALL NOT PRESS AGAINST PIPE OR DUCT INSULATION.
4. CARRYING CHANNELS AND MAIN RUNNERS SHALL BE LEVEL
TO WITHIN 1/8 INCHES IN 10'-0".
5. SUSPENSION SYSTEM SHALL NOT BE VISIBLE FROM EYE
LEVEL OF A PERSON STANDING ON THE FLOOR.
C. LAY IN PANEL CEILINGS:
1. SPACE MAIN RUNNERS 4'-0" ON CENTER. LEVEL AND SQUARE TO ADJACENT WALLS
2. SPACE CROSS RUNNERS AT 2'-0" ON CENTER
3. PROVIDE COMPRESSION STRUTS AT SEISMIC WIRE LOCATIONS. COMPRESSION STRUTS
SHALL NOT REPLACE HANGER WIRES.
9.3 RESILIENT BASE:
A. RESILIENT BASE TO BE STRAIGHT AT CARPETING AND COVE AT HARD SURFACE
FLOORING.
B. RESILIENT BASE TO BE INSTALLED IN CONTINUOUS RUNS FROM
120'-0" ROLLS. NO JOINTS SHALL BE WITHIN 12” OF A CORNER.
9.4 CARPET TILE:
A. STORE CARPET TILE AT LEAST 3 DAYS PRIOR TO INSTALLATION IN AREA OF
INSTALLATION TO ACHIEVE TEMPERATURE STABILITY.
1. FOLLOW CRI 104 STANDARD FOR ROOM TEMPERATURE AND HUMIDITY CONDITIONS.
2. MAINTAIN RECOMMENDED CONDITIONS AT LEAST 72 HOURS PRIOR TO INSTALLATION
AND AFTER COMPLETION.
3. DO NOT STACK CARPET TILE BOXES MORE THAN 6 CARTONS HIGH TO AVOID
POTENTIAL CRUSHING.
B. SEQUENCE CARPET TILE INSTALLATION WITH OTHER WORK TO MINIMIZE POSSIBILITY
OF DAMAGE AND SOILING DURING REMAINDER OF CONSTRUCTION PERIOD.
C. CONSISTENCY OF COLOR SHALL BE SUCH THAT ANY TILE SHALL BE
INTERCHANGEABLE WITH ANY OTHER TILE, WITHIN A DYE LOT, WITH NO VISUAL DIFFERENCE.
D. ADHESIVES, IF REQUIRED, TO BE PER MANUFACTURER'S GUIDELINES.
E. SUBFLOOR MUST BE CLEANED, FREE OF DUST, DIRT, GREASE, WAX, PAINT, CURING OR
PARTING AGENTS, OR ANY OTHER SUBSTANCE THAT MAY AFFECT THE BOND. CONCRETE
FLOORS MUST BE LEVEL, FULLY CURED, FREE OF EXCESSIVE MOISTURE EMISSIONS AND
ALKALI. CONCRETE FLOORS WITH A MOISTURE EMISSION RATE EXCEEDING 3.0 lbs / 1,000 SQ.
FT. IN A 24 HOUR PERIOD REQUIRE CORRECTIVE MEASURES.
9.5 BROADLOOM CARPET:
A. FACE YARNS SHALL BE OF SAME DYE BATCH, AND FINISH MATERIAL SHALL BE OF ONE
MILL RUN.
B. WHERE SPECIFIED PROVIDE STANDARD CUSHION: NOVA “CONTRACT” BY LEGGETT &
PLATT, OR EQUAL. WEIGHT: 6.5 POUNDS PER CUBIC FOOT. THICKNESS: 5/16”.
C. TACKLESS CARPET STRIPPING SHALL BE WATER RESISTANT PLYWOOD STRIPS, 3/8” OR
9/32” THICK, AS REQUIRED TO MATCH CUSHION / CARPET THICKNESS, WITH ANGULAR PINS
PROTRUDING FROM TOP FOR GRIPPING AND HOLDING STRETCHED CARPET.
D. SUBFLOOR MUST BE CLEANED, FREE OF DUST, DIRT, GREASE, WAX, PAINT, CURING OR
PARTING AGENTS, OR ANY OTHER SUBSTANCE THAT MAY AFFECT THE BOND. CONCRETE
FLOORS MUST BE LEVEL, FULLY CURED, FREE OF EXCESSIVE MOISTURE EMISSIONS AND
ALKALI. CONCRETE FLOORS WITH A MOISTURE EMISSION RATE EXCEEDING 3.0 lbs / 1,000 SQ.
FT. IN A 24 HOUR PERIOD REQUIRE CORRECTIVE MEASURES.
9.6 PAINTING AND DECORATING
A. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL MATERIALS
AND LABOR AS NECESSARY TO PROVIDE PAINTING AND DECORATING WORK AS SPECIFIED
AND INDICATED ON THE DRAWINGS.
B. ALL WALLS, DRYWALL CEILINGS, DOORS, FRAMES AND WOODWORK SHALL BE FREE
FROM DEFECTS AND BE FILLED AND SANDED SMOOTH PRIOR TO RECEIVING PAINTED
AND/OR NATURAL FINISHES. NEW WORK SHALL BE PRIMED AND PAINTED WITH NOT LESS
THAN ONE PRIME AND TWO FINISH COATS. PREVIOUSLY FINISHED WORK SHALL RECEIVE
NOT LESS THAN TWO FINISH COATS.
C. PAINTING SYSTEM NEW CONSTRUCTION:
1. DRYWALL - 1ST COAT - BENJAMIN MOORE (BM) LATEX QUICK DRY PRIME SEALER II
(201).
a. DRYWALL CEILINGS 2ND & 3RD COAT - "BM" REGAL WALL SATIN LATEX FLAT (215).
REFER TO FINISH PLAN FOR PAINT COLORS.
B. DRYWALL WALLS 2ND & 3RD COAT - "BM" REGAL AQUAPEARL LATEX (310) OR
EGGSHELL. REFER TO FINISH PLAN FOR PAINT COLORS.
C. DRYWALL WALLS 2ND & 3RD COAT IN BATHROOMS, KITCHENS, JANITOR CLOSETS,
ETC. SEMI GLOSS FINISH. REFER TO FINISH PLAN FOR PAINT COLORS.
d. OTHER FINISH COATS AS NOTED ON PLAN.
e. EXISTING CONSTRUCTION ONLY, 2ND & 3RD COAT AS REQUIRED, OR NOTED.
2. MISCELLANEOUS WOOD TRIM - 1ST COAT - BENJAMIN MOORE ALKYD ENAMEL
UNDERBODY (217).
a. 2ND & 3RD COAT - AS NOTED.
B. EXISTING CONSTRUCTION ONLY, 2ND & 3RD COAT AS REQUIRED, OR NOTED.
3. MISCELLANEOUS METAL TRIM - 1ST COAT - BENJAMIN MOORE IRONCLAD RETARDO
RUST INHIBITIVE PAINT (163).
a. 2ND & 3RD COAT - "BM" SATIN IMPERVO (235) OR ALKYD DULAMEL (207) FOR SEMI-
GLOSS FINISH.
B. OTHER FINISH COATS AS NOTED ON PLAN.
C. EXISTING CONSTRUCTION ONLY, 2ND & 3RD COAT AS REQUIRED.
NOTE: IF OTHER PAINT MANUFACTURER IS USED, FOLLOW SAME PRODUCT
SPECIFICATIONS AS SHOWN FOR "BM".
D. UNLESS OTHERWISE NOTED, PREPARE AND PAINT ALL EXPOSED ITEMS INCLUDING
COLUMNS, PANEL BOXES, CONDUIT, SURFACE RACEWAYS, DRAPERY POCKETS, ETC. NOT
PRE-FINISHED TO MATCH ADJACENT PARTITION OR CEILING COLOR.
E. FINISH VERTICAL EDGES OF PAINT GRADE DOORS TO MATCH FACES. SEAL TOP AND
BOTTOM EDGES.
F. PAINT ASTRAGALS AT FIRE RATED DOORS TO MATCH DOOR.
G. ALL SHOP PAINTED WOOD DOORS TO BE PAINTED TO AWI-OP4 SPECIFICATION FOR
SOLID COLORS AND AWI TO VIF-4 FOR CLEAR FINISHES.
9.7 WALL COVERING:
INSTALL WALL COVERING USING MANUFACTURER’S RECOMMENDED ADHESIVE. WALL
COVERING SHALL BE CONTINUOUS BEHIND COUNTERTOPS, CHAIR RAILS, ETC. SEAMS SHALL
BE TIGHT, NEAT, AND NOT LESS THAN 12” FROM CORNERS. DO NOT END WALL COVERING AT
AN OUTSIDE CORNER.
9.8 RESILIENT FLOORING:
THE CONTRACTOR SHALL WAX ALL NEW AND, WHERE OCCURS, EXISTING RESILIENT
FLOORS, UON.
DIVISION 10 - SPECIALTIES
(NOT USED)
DIVISION 11 – EQUIPMENT
PROVIDE ELECTRICAL AND WATER SYSTEMS REQUIRED FOR A COMPLETE AND
OPERATIONAL INSTALLATION OF ALL APPLIANCES AS SHOWN OR SPECIFIED ON THE
DRAWINGS.
DIVISION 12 – FURNISHINGS
A. FURNITURE IS BY TENANT UNLESS OTHERWISE NOTED. REFER TO POWER AND
SIGNAL PLAN FOR ELECTRICAL REQUIREMENTS.
B. CONTRACTOR SHALL COORDINATE HIS WORK WITH THAT OF THE TENANT’S
FURNITURE VENDOR TO INCLUDE FLOOR CORE LOCATIONS, BASE POWER, AND DATA IN
FEED LOCATIONS.
DIVISION 13 - SPECIAL CONSTRUCTION
(NOT USED)
DIVISION 14 - CONVEYING SYSTEM
(NOT USED)
DIVISION 15 - MECHANICAL
15.1 SCOPE OF WORK
CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR REQUIRED TO PROVIDE A
COMPLETE AND OPERATIONAL HEATING, AIR CONDITIONING, VENTILATION, PLUMBING, FIRE
PROTECTION, AND LIFE SAFETY SYSTEM. CONTRACTOR SHALL VISIT THE PROJECT SITE TO
DETERMINE THE EXACT LOCATIONS AND ELEVATIONS OF EXISTING DUCTWORK, PIPING AND
FIRE PROTECTION EQUIPMENT. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL
OF EXISTING WORK AS NECESSARY TO ACCOMMODATE NEW WORK.
15.2 ENGINEERING DESIGN DOCUMENTS
CONTRACTOR SHALL PREPARE OR CAUSE TO HAVE PREPARED A COMPLETE SET OF
MECHANICAL AND PLUMBING ENGINEERING DRAWINGS AND SPECIFICATIONS.
CONTRACTORS SHALL SUBMIT DRAWINGS AND SPECIFICATIONS TO ARCHITECT FOR REVIEW
AND APPROVAL PRIOR TO COMMENCING WITH NEW WORK. CONTRACTOR SHALL PROVIDE
WET STAMPED AND SIGNED DRAWINGS FOR BUILDING DEPARTMENT PERMIT SUBMISSION.
15.3 ORDINANCES, REGULATIONS AND BUILDING CODES
ALL WORK SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE ORDINANCES,
REGULATIONS AND BUILDING CODES. CONTRACTOR SHALL BE RESPONSIBLE FOR
OBTAINING ALL PERMITS TO PERFORM THIS WORK.
DIVISION 16 - ELECTRICAL
16.1 SCOPE OF WORK
CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR REQUIRED TO PROVIDE A
COMPLETE OPERATIONAL ELECTRICAL SYSTEM. CONTRACTOR SHALL VISIT THE PROJECT
SITE AND VERIFY ALL ELECTRICAL CONDITIONS TO DETERMINE THE EXTENT OF NEW WORK
AND DEMOLITION INVOLVED. CONTRACTOR SHALL REMOVE AND TERMINATE ALL EXISTING
ELECTRICAL, TELEPHONE AND OTHER DEVISES NOT OTHERWISE INDICATED TO REMAIN.
(REFER TO ENGINEER'S DOCUMENTS, IF APPLICABLE.)
16.2 ENGINEERING DESIGN DOCUMENTS
CONTRACTOR SHALL PREPARE OR CAUSE TO HAVE PREPARED A COMPLETE SET OF
ELECTRICAL ENGINEERING DRAWINGS AND SPECIFICATIONS. CONTRACTORS SHALL SUBMIT
DRAWINGS AND SPECIFICATIONS TO ARCHITECT FOR REVIEW AND APPROVAL PRIOR TO
COMMENCING WITH NEW WORK. CONTRACTOR SHALL PROVIDE WET STAMPED AND SIGNED
DRAWINGS FOR BUILDING DEPARTMENT PERMIT SUBMISSION.
16.3 ORDINANCE, REGULATIONS & BUILDING CODES
ALL WORK SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE ORDINANCES,
REGULATIONS AND BUILDING CODES. CONTRACTOR SHALL BE RESPONSIBLE FOR
OBTAINING ALL PERMITS TO PERFORM THIS WORK.
16.5 TELEPHONE/DATA SYSTEMS COORDINATION
CONTRACTOR SHALL COORDINATE HIS WORK WITH THE TENANT'S TELEPHONE AND
COMMUNICATIONS VENDOR PRIOR TO COMMENCING WITH NEW WORK.
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
1
6
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.03
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
GREEN BUILDING NOTES -
COMMERCIAL
COLLECTORS
-
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SEE PLUMBING
SEE PLUMBING
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
G0.03
N/A
G0.03
SEE MECH
SEE MECH
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SEE MECH
G0.03
N/A
N/A
N/A
N/A
SEE MECH
N/A
SEE MECH
SEE MECH
SEE MECH
SEE MECH
SEE MECH
G0.02
G0.02
G0.02
G0.02
G0.02
G0.03, SEE MECH
G0.02
G0.02
G0.02
G0.03, SEE MECH
G0.03, SEE MECH
1CAL GREEN CHECKLIST
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
FEC
CR
FE
C
FEC
FE
C
DIRECTION OF EGRESS TRAVEL
PATH OF EGRESS TRAVEL
COMMON PATH OF EGRESS TRAVEL (MAX. 100' PER 1006.2.1)
EXIT ACCESS TRAVEL DISTANCE (MAX. 300' PER 1017.2)
DIRECTION OF OCCUPANT LOAD
0
0
INDIVIDUAL OCCUPANCY LOAD
ACCUMULATED OCCUPANCY LOAD
FIRE EXTINGUISHER CABINET
EXIT SIGN
CONTROLLED ACCESS (CARD READER)
AREA NOT IN CONTRACT (N.I.C.)
OFFICE, B - CONCENTRATED (50 OLF)
PH INDICATES PANIC HARDWARE
STORAGE, S-1 ACCESSORY OCCUPANCY
OFFICE, B - STANDARD (150 OLF)
CHAPTER 3 OCCUPANCY CLASSIFICATION AND USE
OCCUPANCY CLASSIFICATION PRIMARY: B - OFFICE
ACCESSORY: A-3 - ASSEMBLY
ACCESSORY: S-1 - STORAGE
S 304
S 303
S 311
2025 CBC
S (SECTION)
T (TABLE)
CHAPTER 4 SPECIAL DETAILED REQUIREMENTS
BASED ON OCCUPANCY AND USE
N.A.
CHAPTER 5 GENERAL BUILDING HEIGHTS AND AREAS
FLOOR AREA
LEVEL 01 (AREA OF WORK):
BUILDING HEIGHT
BUILDING HEIGHT
NO. OF STORIES
ALLOWABLE AREA
FRONTAGE INCREASES
UNLIMITED AREA BUILDING
MIXED USE AND OCCUPANCY
25,523 SF
31'-0" MAX.
2
N.A.
UNLIMITED
N.A.
T 504.3
T 504.4
T 506.2
S 506.3
S 507
S 508
CHAPTER 6 TYPES OF CONSTRUCTION
TYPE OF CONSTRUCTION
FIRE-RESISTENCE RATING FOR BUILDING ELEMENTS
PRIMARY STRUCTURAL FRAME:
BEARING WALL, EXTERIOR:
BEARING WALL, INTERIOR:
NON-BEARING WALLS AND PARTITIONS, EXTERIOR:
NON-BEARING WALLS AND PARTITIONS, INTERIOR:
FLOOR CONSTRUCTION:
ROOF CONSTRUCTION:
IIIB
RATING (HOURS)
0
2
0
SEE BELOW
0
0
0
S 602
T 601
T 601
T 601
T 705.5
T 601
T 601
T 601
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES
FIRE RESISTENCE-RATED CONSTRUCTION
STRUCTURAL MEMBERS:
EXTERIOR WALLS:
FIRE RESISTENCE RATING FOR EXTERIOR WALLS
BASED ON FIRE SEPARATION DISTANCE:
EXTERIOR WALL OPENINGS:
FIRE WALLS:
RATING (HOURS)
N.A.
N.A.
0
FIRE SEP. X>30
N.A.
N.A.
S 704
S 705
T 705.5
T 705.8
S 706
CHAPTER 8 INTERIOR FINISHES
INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT
PASSAGEWAYS:
CORRIDORS AND ENCLOSURE FOR EXIT ACCESS
STAIRWAYS AND RAMPS:
ROOMS AND ENCLOSED SPACES:
A-3
CLASS
B
B
C
T 803.13
B
CLASS
B
C
C
2025 CBC
S (SECTION)
T (TABLE)
2025 CBC
S (SECTION)
T (TABLE)
CHAPTER 9 FIRE PROTECTION AND LIFE SAFETY SYSTEMS
AUTOMATIC FIRE SPRINKLER SYSTEM:
STANDPIPE SYSTEMS:
PORTABLE FIRE EXTINGUISHERS:
FIRE ALARM AND DETECTION SYSTEM
EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM:
S 903
S 905
T 906.3
S 907
S 907.2.2
YES, PROVIDED
N.A.
YES, PROVIDED
>500 OCCUPANTS
YES, PROVIDED
CHAPTER 10 MEANS OF EGRESS
MAXIMUM FLOOR AREA ALLOWANCE PER OCCUPANT
A-ASSEMBLY, UNCONCENTRATED:
B-OFFICE:
B-OFFICE, CONCENTRATED BUSINESS USE:
S-STORAGE:
MEANS OF EGRESS SIZING
STAIRWAYS:
OTHER MEANS OF EGRESS (INLC. DOORS):
NUMBER OF EXITS AND EXIT ACCESS STAIRWAYS
MAXIUMUM TRAVEL DISTANCES
EXIT ACCESS
COMMON PATH OF EGRESS
DEAD END CORRIDOR
T 1004.5
S 1005.3.1
S 1005.3.2
S 1006
T 1017.2
T 1006.2.1
S 1020.5
OLF
15, NET
150, GROSS
50, GROSS
300, GROSS
FACTOR
0.20"/OCC
0.15"/OCC
2
A-3
250'
75'
20'
B
300'
100'
50'
S-1
250'
100'
50'
8544 SF
171 OCC
B.1:50
OPEN OFFICE
200
109 SF
1 OCC
S1 1:300
(E) ELEC
201
311 SF
21 OCC
B 1:15
CONF
202
132 SF
1 OCC
B 1:150
OFFICE
203
135 SF
1 OCC
B 1:150
OFFICE
204
135 SF
1 OCC
B 1:150
OFFICE
205
135 SF
1 OCC
S1 1:300
STORAGE
206
133 SF
1 OCC
S1 1:300
STORAGE
207
134 SF
1 OCC
S1 1:300
STORAGE
208
134 SF
1 OCC
S1 1:300
STORAGE
209
MTRL
CONVEYOR
204 SF
14 OCC
B 1:15
CONF
210
189 SF
1 OCC
S1 1:300
MDF
211
125 SF
1 OCC
B 1:150
OFFICE
212
82 SF
1 OCC
S1 1:300
(E) ELEC
214
7322 SF
49 OCC
B 1:150
OFFICE GROWTH
213
(E) STAIRS
EXIT #1
EXIT
ROUTE
1/3 DIAG
O
N
A
L
=
9
0' - 5"
271' -
1
"
TOT
AL DIAGO
N
AL DISTA
N
CE
156' - 10" > 90' - 5"
156' -
1
0
" EX
IT DI
STAN
CE
REQUIRED
PROVIDED 36"
24"
REQUIRED
PROVIDED 36"
24"
158
158
A102
A102
(E) ELEV
(E) STAIRS
A103
156'
113'
123'109'
102'
EXIT WIDTH COMPLIANCE
(OCC LOAD X 0.15 = REQUIRED)
PER CBC 1005.3.2
EXIT WIDTH COMPLIANCE
(OCC LOAD X 0.15 = REQUIRED)
PER CBC 1005.3.2
REQUIRED
PROVIDED 44"
32"
EXIT STAIR WIDTH COMPLIANCE
(OCC LOAD X 0.2 = REQUIRED)
PER CBC 1005.3.1
REQUIRED
PROVIDED 44"
32"
EXIT STAIR WIDTH COMPLIANCE
(OCC LOAD X 0.2 = REQUIRED)
PER CBC 1005.3.1
EXIT
ROUTE
104'
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
1
8
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
G0.04
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
EXITING AND OCCUPANCY
COLLECTORS
-
LEGENDPLUMBING FIXTURE CALCULATIONSCBC CODE ANALYSIS
PER TABLE 422.1, 2022 CALIFORNIA PLUMBING CODE
DRINKING FOUNTAINS
+ WATER DISPENSERS
KEYNOTES
1. PER CBC TABLE 508.3, WHERE A-3 OCCUPANCY IS ACCESSORY TO PRIMARY B-OCCUPANCY
NO SEPARATION IS REQUIRED.
2. PROVIDE TACTILE EXIT SIGNAGE PER CBC 1013.4 AND 11B-703 WHERE NEW EXITS, EXIT
ACCESS, ETC OCCUR. VERIFY IN FIELD WHERE EXISTING. SEE SHEET A7.50 FOR EXIT
SIGNAGE DETAILS.
A-3 / ASSEMBLY OCCUPANCY
515 SF/ 30 =
50% WOMEN =
50% MEN =
18 OCCS
9
9
B / OFFICE OCCUPANCY
23,608 SF/ 150 =
50% WOMEN =
50% MEN =
158 OCCS
79
79
OCC FIX (M) REQ.(F) PROV. (GN) PROV.
A-3
WC
UR
LAV
1
1
1
B
WC
UR
LAV
2
1
1
TOTAL
WC
UR
LAV
3
2
2
6
-
4
-
-
-
(F) REQ.
1
-
1
4
-
2
5
-
3
(M) PROV.
3
3
3
0 REQUIRED 1 PROVIDED
SHEET NOTES
1/16" = 1'-0"1LEVEL 02 - PLAN, EXITING DIAGRAM
NUM NAME SF FACTOR OCCs
200 OPEN OFFICE Not Placed 150 SF
200 OPEN OFFICE 8544 SF 50 SF 171.0
201 (E) ELEC 109 SF 300 SF 1.0
202 CONF 311 SF 15 SF 21.0
203 OFFICE 132 SF 150 SF 1.0
204 OFFICE 135 SF 150 SF 1.0
205 OFFICE 135 SF 150 SF 1.0
206 STORAGE 135 SF 300 SF 1.0
207 STORAGE 133 SF 300 SF 1.0
208 STORAGE 134 SF 300 SF 1.0
209 STORAGE 134 SF 300 SF 1.0
210 CONF 204 SF 15 SF 14.0
211 MDF 189 SF 300 SF 1.0
212 OFFICE 125 SF 150 SF 1.0
213 OFFICE GROWTH 7322 SF 150 SF 49.0
214 (E) ELEC 82 SF 300 SF 1.0
17825 SF 266.0
TOTAL OCCUPANCY: 315
TOTAL REQUIRED EXIT: 2
TOTAL PROVIDED EXIT: 2
A102 "EXIT" SIGN TO BE PROVIDED PER SECTION 1013.4. REFER TO DETAIL 4/A7.40 FOR
VISUAL CHARACTER, RAISED CHARACTER AND BRAILLE GRAPHIC REQUIREMENTS
A103 PROVIDE EVACUATION MAP
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
A 2026-0306 REVISION 1
AAA
GRAB BAR,
42" MIN.
60" X 60"
LEVEL AND CLEAR
60" MIN. DIA.
CL
E
A
R
32
"
M
I
N
.
24" MIN
GRAB BAR,
36" MIN.
CLEAR
44" MIN.
30" X 48"
CLEAR SPACE
CLEAR
34" MIN.
FLOOR MOUNTED W.C.
59" MIN.
54" MIIN.
FLUSH
LEVER ON
WIDE SIDE
60" MIN
60
"
M
I
N
.
17
"
-
1
8
"
WALL HUNG W.C.
56" MIN.
OUTSWING DOOR
18" MIN
INSWING DOOR
36" MIN W/
CL
GRAB BAR, 48" MIN.
GRAB BAR, 36" MIN.
30"x48" CLEAR FLOOR SPACE
60" MIN. DIA.
17" - 18"
1' - 6"
2'
-
0
"
M
I
N
.
FLUSH LEVER
ON WIDE SIDE
60" MIN.
CL
2' - 8"
6"
M
A
X
.
3'
-
0
"
M
I
N
.
G
R
A
B
B
A
R
1' - 0" MAX.
2' - 0" MIN.
3' - 6" MIN. GRAB BAR
5' - 0" MIN.
5'
-
0
"
M
I
N
.
2' - 10" MIN.
WHEN DOOR SWINGS IN
3' - 0" MIN.
3'
-
6
"
M
I
N
.
18
"
M
A
X
17
"
M
I
N
FLUSH LEVER
ON WIDE SIDE
CL
NOTE:
WHERE SIX OR MORE STALLS
ARE PROVIDED WITHIN A
MULTIPLE-ACCOMADATION
TOILET ROOM, AT LEAST ONE
SHALL BE A STANDARD SIDE-
TRANSFER TOILET STALL
(WHEELCHAIR ACCESSIBLE),
AND AT LEAST ONE
ADDITIONAL STALL SHALL BE
36" WIDE WITH AN OUTWARD
SWINGING SELF CLOSING
DOOR PARALLEL GRAB-BARS
(FOR SEMI-AMBULATORY
USE).
CL
17"-19"
1'
-
0
"
M
A
X
.
3'
-
6
"
M
I
N
.
G
R
A
B
B
A
R
5'
-
0
"
M
I
N
.
35"-37"
MI
N
.
3'
-
8
"
NOTES:
17" MAXIMUM RIM HEIGHT ABOVE FLOOR.
13 1/2" MINIMUM PROJECTION FROM WALL.
44" MAXIMUM HEIGHT OF FLUSH VALVE ABOVE FLOOR.
30"x48" MINIMUM CLEAR ACCESS IN FRONT OF FIXTURE (ONE FIXTURE
ONLY REQUIRED))
13 1/2" MIN.
17
"
M
A
X
.
4'
-
0
"
2' - 6"
9"
M
I
N
.
URINAL DIVIDER
IF X >/= 24"
3' - 0" CLR
X
IF X < 24"
2 - 6" CLR
CLEAR
FLOOR
SPACE
( c ) REMOVABLE IN-TUB SEAT
FORWARD APPROACH
4'
-
0
"
M
I
N
.
LENGTH OF TUB
SE
A
T
CLEAR
FLOOR
SPACE
( a ) REMOVABLE IN-TUB SEAT
PARALLEL APPROACH
2'
-
6
"
M
I
N
.
LENGTH OF TUB
SE
A
T
CLEAR
FLOOR
SPACE
( b ) PERMANENT SEAT
PARALLEL APPROACH
2'
-
6
"
M
I
N
.
LENGHT OF TUB
SE
A
T
12" MIN.
CLEAR
FLOOR
SPACE
( d ) PERMANENT SEAT
FORWARD APPROACH
48
"
M
I
N
.
LENGHT OF TUB
SE
A
T
12" MIN.
4' - 6" MIN.
MAX.
1' - 0"3' - 6" MIN.
TO
P
O
F
B
A
R
33
"
-
3
6
"
3' - 0" MIN.
12" MIN.
6" MAX.
TO
P
O
F
B
A
R
33
"
-
3
6
"
4' - 6" MIN.
MAX.
1' - 0"3' - 6" MIN.
TO
P
O
F
B
A
R
33
"
-
3
6
"
3' - 0" MIN.
12" MIN.
6" MAX.
TO
P
O
F
B
A
R
33
"
-
3
6
"
7"-9"
7"-9"
2' - 0" MIN.2' - 0" MIN.
FLOOR MOUNTED W.C.
WALL HUNG W.C.
2' - 0" MIN 2' - 0" MIN.
CL
CL
FL
U
S
H
V
A
L
V
E
C
O
N
T
R
O
L
44
"
M
A
X
17
"
-
1
9
"
17
"
-
1
9
"
19
"
M
I
N
.
19
"
M
I
N
.
RESTROOMWOMENMEN
WALL MOUNTED SIGNAGE TO BE LOCATED ON
LATCH SIDE OF DOOR. CLEAR OF DOOR
SWING.
NOTE:
1. RAISED LETTERING 1/32" TYP.
2. RAISED GRADE 2 BRAILLE
MARKING PER 2019 CBC
UNISEX RESTROOM
WOMENS RESTROOM
MENS RESTROOM58
"
-
6
0
"
A
.
F
.
F
.
58
"
-
6
0
"
A
.
F
.
F
.
58
"
-
6
0
"
A
.
F
.
F
.
DOOR MOUNTED SIGNAGE WALL MOUNTED SIGNAGE
1' - 0"
1' - 0"
1'
-
0
"
1'
-
0
"
48
"
M
I
N
CL
CL
CL
ALL GENDER RESTROOM58
"
-
6
0
"
A
.
F
.
F
.
1'
-
0
"
CL
THIS IMAGE REPRESENTS THE DOOR SYMBOL
REQUIRED BY CBC 11B-216.8 TO IDENTIFY AN ALL
GENDER/UNISEX SINGLE-USER TOILET FACILITY.
THE SYMBOL MUST COMPLY WITH THE
REQUIREMENTS OF CBC 11B-703.7.2.6.3. NO
PICTOGRAM, TEXT, OR BRAILLE IS REQUIRED ON
THE SYMBOL.
60
"
M
A
X
TO
P
O
F
B
A
R
33
"
-
3
6
"
19" MIN.
27" MAX.
27" MAX.
39
"
-
4
1
"
30
"
M
I
N
.
3'
-
0
"
M
I
N
.
C
L
R
.
15" - 16"
5' - 0" CLR.
22" - 23"
2 1/2" MAX.14
"
-
1
5
"
4'
-
0
"
M
A
X
60" HOSE
HAND HELD
SPRAYER
SINGLE LEVER
CONTROL VALVE
SOAP DISH 18"-24" TO
SEAT BACK. 40" MAX
HEIGHT.
FOLDING
SHOWER SEAT
MAX. 6" FROM
WALL WHEN
FOLDED1/2" BEVELLED
LIP MAX.
SL
O
P
E
1/
4
"
/
F
T
.
MA
X
.
ELEVATION
PLAN
19" MIN.
19" MIN.
27" MAXCL
3"
M
A
X
.
MA
X
.
1
1
/
2
"
1'
-
6
"
33
"
-
3
6
"
6" MAX.3' - 0" MIN. GRAB BAR
1'
-
0
"
M
A
X
.
3'
-
6
"
M
I
N
.
G
R
A
B
B
A
R
2'
-
0
"
M
I
N
.
18" MAX
17" MIN 3' - 6" MIN.
5' - 0" MIN.
2' - 8" MIN.4'
-
0
"
M
I
N
.
5'
-
0
"
M
I
N
.
2' - 0" MIN.
FLUSH
LEVER ON
WIDE SIDE
5' - 0" MIN.
MAX
4"
MIN
1' - 0"
MIN
2' - 0"
CL
1½"
1¼" MIN.
TO
2" MAX.
THE STRUCTURAL STRENGTH OF GRAB BARS SHALL MEET THE FOLLOWING
SPECIFICATIONS:
A. BENDING STRESS AND SHEAR STRSS INDUCED IN A GRAB BAR BY THE
APPLICATION OF A 250-POUND POINT LOAD SHALL BE LESS THAN THE
ALLOWABLE SHEAR STRESS FOR THE MATERIAL OF THE GRAB BAR, AND
ITS MOUNTING BRACKET OR OTHER SUPPORT IS CONSIDERED TO BE FULLY
RESTRAINED, THEN DIRECT AND TORSIONAL SHEAR STRESSES SHALL NOT
EXCEED THE ALLOWABLE SHEAR STRESS.
B. SHEAR FORCE INDUCED IN FASTENER OR MOUNTING DEVICE FROM THE
APPLICATION OF A 250-POUND POINT LOAD SHALL BE LESS THAN THE
ALLOWABLE LATERAL LOAD OF EITHER THE FASTENER OR MOUNTING
DEVICE OR THE SUPPORTING STRUCTURE, WHICHEVER IS THE SMALLER
ALLOWABLE LOAD.
C. TENSILE FORCE INDUCED IN A FASTENER BY A DIRECT TENSION FORCE OF
A 250-POUND POINT LOAD, PLUS THE MAXIMUM MOMENT FROM THE
APPLICATION OF A 250-POUND POINT LOAD, SHALL BE LESS THAN THE
ALLOWABLE WITHDRAWAL LOAD BETWEEN THE FASTENER AND
SUPPORTING STRUCTURE.
D. GRAB BARS SHALL NOT ROTATE WITHIN THIER FITTINGS. EDGES SHALL
HAVE MINIMUM RADIUS OF 1/8". GRAB BARS AND ADJACENT SURFACE
SHALL BE FREE OF ABRASIVE ELEMENTS.
STRUCTURAL STRENGTH OF
GRAB BARS SHALL MEET THE
REQUIREMENTS OF CBC SECTION 11B-609
PROVIDE BACKING AT GRAB
BARS AS REQUIRED.
33
"
-
3
6
"
T
O
P
O
F
B
A
R
(G) GRAB BAR @ TOILET (H) GRAB BAR (I)TOILET TISSUE HOLDER
(A)COMBINATION T.P./SEAT COVER
DISPENSER
(B)COMBINATION WASTE/TOWEL UNITS (C)SANITARY NAPKIN VENDOR
(J)TOWEL BAR (K)CLOTHES HOOK
(D)OUTLETS (E) SWITCHES
(F)MIRROR
NOTE:
MOUNTING HEIGHT FROM FINISHED
FLOOR TO HIGHEST OPERABLE
CONTROL, TYPICAL.
1-1/2" CLR.
3'
-
4
"
M
A
X
.
4'
-
0
"
M
A
X
48
"
M
A
X
.
18
"
M
A
X
,
1
5
"
M
I
N
.
4'
-
0
"
M
A
X
.
3'
-
4
"
3'
-
4
"
M
A
X
.
2'
-
9
1
/
2
"
3'
-
4
"
M
A
X
.
19
"
M
I
N
.
7"-9"
TO
P
O
F
B
A
R
33
"
-
3
6
"
TO
P
O
F
B
A
R
33
"
-
3
6
"
2' - 0" MIN.1' - 0" MAX.
17
"
-
1
9
"
17
"
-
1
9
"
33
"
-
3
6
"
TO
P
O
F
B
A
R
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
2
1
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
G0.11
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
ACCESSIBILITY COMPLIANCE
DIAGRAMS
COLLECTORS
-
1/4" = 1'-0"18ADA MULTIPLE ACCOMODATION TOILET FACILITY
1/2" = 1'-0"2ADA SINGLE OCC. TOILET
1/2" = 1'-0"14ADA STALL SIDE ENTRY
1/2" = 1'-0"19ADA SEMI-AMBUL. STALL
1/2" = 1'-0"20ADA URINALS
1/4" = 1'-0"15ADA TUB FLOOR SPACE
1/2" = 1'-0"16ADA TOILET MOUNTING HT / GRAB BAR LOCATIONS
1" = 1'-0"10ADA RESTROOM SIGNS
1/2" = 1'-0"8ADA ROLL-IN SHOWER
1/2" = 1'-0"4ADA STALL FRONT ENTRY
1 : 1 12DETAIL AT GRAB BAR
1/2" = 1'-0"1ADA RESTROOM ACCESSORY MOUNTING HEIGHTS
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
30"X48" CLEAR
FLOOR SPACE
MIRROR
INSULATE TRAP AND
HOT WATER PIPES TO
PREVENT CONTACT
LINE OF REQUIRED
CLEARANCE
1'
-
6
"
M
I
N
.
25" MAX.
17" MIN.
25" MAX DEPTH
17" MIN DEPTH
11" MIN.6" MAX.
9"
M
I
N
.
2'
-
3
"
M
I
N
.
2'
-
5
"
M
I
N
.
2'
-
1
0
"
M
A
X
.
3'
-
4
"
M
A
X
.
19" MAX
6"
M
A
X
NOTE: ALCOVE DEPTH (X) GREATER
THAN 24", THEN ALCOVE WIDTH (Y)
MUST BE A MINIMUM OF 36"
MI
N
.
1'
-
6
"
MIN.
1' - 6"
CLR.
2' - 6" MIN.
MIN.
1' - 6"
4'
-
0
"
M
I
N
.
19" MAX
17" MIN
36
"
M
A
X
.
FO
R
S
T
A
N
D
I
N
G
P
E
R
S
O
N
S
38
"
-
4
3
"
18
"
-
1
9
"
15
"
M
I
N
.
5"
M
A
X
.
34
"
M
A
X
.
SPACECLEARREQUIRED
6" MIN
17" MIN.
8"
MIN.
34
"
M
A
X
.
29
"
M
I
N
.
27
"
M
I
N
.
9"
M
I
N
.
INSULATED TRAP AND
HOT WATER PIPES
3/4"
PULL SIDE
PANIC HARDWARE
(WHERE REQUIRED)
CLEAR LEVEL LANDING
PUSH SIDE
CLEAR LEVEL LANDING
PROVIDE 12" MIN. IF DOOR
IS EQUIPPED WITH BOTH A
LATCH AND A CLOSER
*NOTE: 2% MAX SLOPE AT
EXTERIOR LANDINGS ONLY
4'
-
0
"
5'
-
0
"
1' - 0"
2' - 8"
1' - 6" MIN.CLEAR@INT.DOORS
2' - 0" MIN. CLEAR@ EXT. DOOR
PUSH SIDE
PULL SIDE
22" MIN.
36" MIN.
60
"
M
I
N
.
44
"
M
I
N
.
*
* NOTE: 48" MINIMUM IF
DOOR HAS BOTH A
LATCH AND A CLOSER
NOTE: ALL DOORS IN ALCOVES SHALL COMPLY WITH THE CLEARANCES FOR FRONT APPROACHES
24" MIN.
FOR LATCH
APPROACH
FOR HINGE
APPROACH
TEXT: "VAN ACCESSIBLE"
TEXT: "PHYSICALLY
DISABLED PERSON
ONLY"
2" GALVANIZED STEEL POST
NOTE: WHERE A WALL OCCURS AT THE WALKWAY END OF THE PARKING
SPACE, SIGN MAY BE CENTERED ON THE WALL AT A MINIMUM HEIGHT OF
3'-0" FROM THE PARKING SPACE FINISH GRADE, GROUND OR SIDEWALK
(WHICHEVER IS HIGHEST) INSTEAD OF ON POST.
LOWEST POINT OF ADJACENT
FINISHED GRADE
HIGHEST POINT OF ADJACENT
FINISHED GRADE
12" CONCRETE BASE
12"x 18"x 1/8" REFLECTORIZED
SIGN W/ THE "INTERNATIONAL
SYMBOL OF ACCESSIBILITY" AND
LETTERING, IN WHITE ON DARK
BACKGROUND, SILK-SCREENED
ON ALUMINUM OR GALVANIZED
METAL PER THE CURRENT
EDITIONS OF THE C.B.C. AND
A.D.A.G.
VAN-ACCESSIBILITY SIGN,
WHERE APPLICABLE
1'
-
8
"
M
I
N
.
BOTTOM OF SIGN
6'
-
8
"
M
I
N
.
FOR ADDITIONAL INFORMATION SEE NOTE #3/REF.2
TEXT: UNAUTHORIZED VEHICLES
PARKED IN DESIGNATED ACCESSIBLE
SPACES NOT DISPLAYING
DISTINGUISHING PLACARDS OR SPECIAL
LICENSE PLATES ISSUED FOR PERSONS
WITH DISABILITIES WILL BE TOWED
AWAY AT THE OWNERS EXPENSE.
TOW-AWAY SIGNAGE,
INCLUDE TOWING COMPANY
CONTACT INFORMATION
(T
O
H
I
G
H
E
S
T
O
P
E
R
A
B
L
E
PA
R
T
)
30"x48"
CLEAR AREA
ELEVATION PLAN
PRALLEL APPROACH
4'
-
0
"
2'
-
3
"
M
I
N
.
C
L
R
.
2' - 6" MIN.
MA
X
.
10
"
EDGE OF COUNTER
30"x48" CLEAR AREA
PLAN
FORWARD APPROACH
20
"
M
A
X
.
24
"
M
A
X
.
NO
PARKING
CARVAN
21
6
"
M
I
N
.
108" MIN.144" MIN.
PERPENDICULAR PARKING
NO
PARKING
CARVAN
108" MIN.
144" MIN.
ANGLED PARKING
216" MIN.
216" MIN.
PARKING SPACE IDENTIFICATION SIGNS SHALL INCLUDE THE INTERNATIONAL SYMBOL OF
ACCESSIBILITY COMPLYING WITH SECTION 11B-703.7.2.1 SIGNS IDENTIFYING VAN PARKING
SPACES SHALL CONTAIN ADDITIONAL LANGUAGE OR AN ADDITIONAL SIGN WITH DESIGNATION
"VAN ACCESSIBLE". SIGNS SHALL BE 60 INCHES MINIMUM ABOVE THE FINISH FLOOR OR GROUND
SURFACE MEASURED TO THE BOTTOM OF THE SIGN. WHEN SIGNS ARE LOCATED WITHIN AN
ACCESSIBLE ROUTE SHALL BE A MINIMUM OF 80 INCHES ABOVE THE FINISH FLOOR OR GROUND
SURFACE MEASURED TO THE BOTTOM OF THE SIGN. (11B-502.6)
PARKING IDENTIFICATION SIGNS SHALL BE REFLECTORIZED WITH A MINIMUM OF 70 SQUARE
INCHES (11B-502.6.1)
ADDITIONAL LANGUAGE OR AN ADDITIONAL SIGN BELOW THE INTERNATIONAL SYMBOL OF
ACCESSIBILITY SHALL STATE "MINIMUM FINE $250." (11B-502.6.2)
A PARKING SPACE IDENTIFICATION SIGN SHALL BE VISIBLE FROM EACH PARKING SPACE. SIGNS
SHALL BE PERMANENTLY POSTED EITHER IMMEDIATELY ADJACENT TO THE PARKING SPACE OR
WITHIN THE PROJECTED PARKING SPACE WIDTH AT THE HEAD END OF THE PARKING SPACE.
SIGNS MAY ALSO BE PERMANENTLY POSTED ON A WALL AT THE INTERIOR END OF THE PARKING
SPACE (11B-502.6.3)
AN ADDITIONAL SIGN SHALL BE POSTED IN A CONSPICUOUS PLACE AT EACH ENTRANCE TO OFF
STREET PARKING FACILITIES, OR IMMEDIATELY ADJACENT TO ON-SITE ACCESSIBLE PARKING
AND VISIBLE FROM EACH PARKING SPACE. THE SIGN SHALL NOT BE LESS THAN 17 INCHES WIDE
BY 22 INCHES HIGH. THE SIGN SHALL CLEARLY STATE IN LETTERS WITH A MINIMUM HEIGHT OF 1
INCH THE FOLLOWING (11B-502.8):
"UNAUTHORIZED VEHICLES PARKING IN DESIGNATED ACCESSIBLE SPACES NOT DISPLAYING
DISTINGUISHING PLACARDS OR SPECIAL LICENSE PLATES ISSUED FOR PERSONS WITH
DISABILITIES WILL BE TOWED AWAY AT THE OWNER'S EXPENSE. TOWED VEHICLES MAY BE
RECLAIMED AT ______________________ OR BY TELEPHONING _______________.
VEHICLE PARKING SPACES
NO
PARKI
NG
PERPENDICULAR PARKING
NO
PARKING
ANGLED PARKING
OF PARKING SPACE
FULL REQUIRED LENGTH
OF PARKING SPACE
FULL REQUIRED LENGTH
PARKING SPACE ACCESS AISLE
OF
P
A
R
K
I
N
G
S
P
A
C
E
FU
L
L
R
E
Q
U
I
R
E
D
L
E
N
G
H
T
60" MIN.
ACCESS AISLE
ACCESS AISLE
60" MIN.
NO
PARKING
PERPENDICULAR PARKING
NO
PARKING
ANGLED PARKING
ANGLED AND PERPENDICULAR PARKING IDENTIFICATION
IDENTIFICATION SIGN
ACCESS AISLE
60" MIN.
WHITE LETTERING,
12 INCHES MIN HEIGHT
ACCESS AISLE
BLUE BORDER
HATCHED LINES AT
36 INCHES ON
CENTER MAX.
INTERNATIONAL SYMBOL
OF ACCESSIBILITY 36
INCHES BY 36 INCHES
MIN.
IDENTIFICATION SIGN
HATCHED LINES AT
36 INCHES ON
CENTER MAX.
INTERNATIONAL
SYMBOL OF
ACCESSIBILITY 36
INCHES BY 36
INCHES MIN.
BLUE BORDER
WHITE LETTERING,
12 INCHES MIN
HEIGHT
CURB LINE
AREA TO BE
MARKED
60
"
M
I
N
.
PASSENGER DROP-OFF AND LOADING ZONE ACCESS ASILE
SIGNS AND SYMBOLS
30
"
M
I
N
.
ELEVATION
PLAN
8" MIN.
9"
M
I
N
.
11" MIN.
27
"
M
I
N
.
ELEVATION @ LAVATORY
8" MIN.
9"
M
I
N
.
11" MIN.
27
"
M
I
N
.
29
"
M
I
N
.
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
2
2
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
G0.12
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
ACCESSIBILITY COMPLIANCE
DIAGRAMS
COLLECTORS
-
1/2" = 1'-0"17ADA LAV. CLEARANCE
1/2" = 1'-0"13ADA FOUNTAINS
1 : 1 15UNDERSINK CLEARANCES
1/2" = 1'-0"16ADA DOOR CLEARANCES
1/4" = 1'-0"12H.C. STALL SIGNAGE
1/2" = 1'-0"4ADA TELEPHONE
12" = 1'-0"3PARKING REQUIREMENTS
1/2" = 1'-0"1ADA KNEE CLEARANCES1
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
5' - 6" MIN.
4'
-
0
"
M
I
N
.
REAR ACCESS
FRONT ACCESS
NOTE: EACH INDIVIDUAL SEATING POSTION HAS
AN EGRESS ROUTE WHICH DOES NOT CROSS
THROUGH OTHER SEATING POSTIONS.
5' - 6" MIN.
5'
-
0
"
M
I
N
.
SIDE ACCESS SIDE ACCESS
T-SHAPE 180° TURNS CLEAR WIDTH FOR TWO WHEEL CHAIRS TO
PASS PARALLEL THROUGH CORRIDOR
MAX. SIDE REACH OVER AN
OBSTRUCTION
NOTE: MAXIMUM DEPTH OF OBSTRUCTION ALLOWED IS 25".
WHEN DEPTH OF OBSTRUCTION IS BETWEEN 20" AND 25", THE
MAXIMUM FORWARD REACH HEIGHT FROM THE FLOOR
SURFACE IS 44". WHEN DEPTH OF OBSTRUCTION IS LESS THAN
20", THE MINIMUM CLEAR HEIGHT BENEATH THE OBSTRUCTION
IS 27". WHEN DEPTH OF OBSTRUCTION IS GREATER THAN 20",
THE CLEAR HEIGHT BELOW THE OBSTRUCTION IS 30" MIN. TO
ALLOW FOR CLEARANCE OF A WHEELCHAIR ARM REST UNDER
THE OBSTRUCTION.
X=DEPTH OF OBSTRUCTION
Y=MAXIMUM REACH HEIGHT
Z=MIN. CLEAR SPACE BELOW OBSTRUCTION
Y
Z
X
90° TURNS
TURNS AROUND AN
OBSTRUCTION
MAX. SIDE REACH OVER AN
OBSTRUCTION
CLEAR FLOOR SPACE WHEELCHAIR TURNING SPACE
NOTE: DIMENSIONS APPLY WHEN X<48"
*CORRIDORS WITH OCCUPANCY OF 9 OR LESS **CORRIDORS WITH OCCUPANCY OF 10 OR MORE
44" MIN** 44" MIN** 44" MIN** 44" MIN**
44
"
M
I
N
*
*
X
5' - 0"
4' - 0"
2'
-
6
"
5' - 0"
34
"
M
A
X
.
44
"
M
A
X
.
3' - 6" MIN.3' - 6" MIN.
4'
-
0
"
M
I
N
.
3' - 0"4' - 0"3' - 0"
3'
-
0
"
M
I
N
.
3'
-
0
"
M
I
N
.
3' - 0" MIN.5' - 0" MIN.
>10" - 24" MAX.
34
"
M
A
X
.
46
"
M
A
X
.
6'
-
8
"
M
I
N
.
≥
8
0
"
M
I
N
.
HI
G
H
E
R
T
H
A
N
2
7
"
4" MAX.
27
"
80
"
M
I
N
27
"
O
R
B
E
L
O
W
REQ'D CLR
WIDTH
(WALKING PARALLEL TO A WALL)
HATCH INDICATES CANE DETECTION AREA
NOTE: PROTRUDING OBJECTS
MAY NOT REDUCE THE
REQUIRED CLEAR WIDTH OF AN
ACCESSIBLE ROUTE OR
MANUEVERING SPACE.
ANY AMOUNT
HI
G
H
E
R
T
H
A
N
2
7
"
12" MAX
POST OR PYLON
2" MIN. 4" MAX. STRIP WIDTH
NOTE:
WARNING STRIPS MUST BE CLEARLY CONTRASTING
COLOR FROM ADJOINING SURFACES. THE STRIP
MUST BE MADE OF A MATERIAL THAT IS AT LEAST
AS SLIP RESISTANT AS THE OTHER TREADS OF THE
STAIR. (PAINTED STRIPS ARE ACCEPTABLE)
INTERIOR STAIRS:
UPPER APPROACH AND
LOWER TREADS MUST BE MARKED
1" MAX FROM
EDGE OF TREAD
EXTERIOR STAIRS:
UPPER APPROACH
AND ALL TREADS
MUST BE MARKED
ROUNDED OR
BEVELED
NOSING, TYPICAL
SOLID RISER,
TYPICAL 1-1/4" MAX
30° MAX
(A) (B)
1-1/4" MAX
30° MAX
(C)
1/2" RADIUS MAX
(D) ROUNDED NOSING (E) BEVELED NOSING
1/2" BEVEL MAX
1. THE REQUIRED MINIMUM HANDRAIL EXTENSION AT EACH BOTTOM
RISER IS 12" + THE DEPTH OF ON TREAD.
2. 12" MINIMUM HANDRAIL EXTENSION REQUIRED AT EACH TOP RISER.
3. 42" GUARDRAIL REQUIRED AT STAIRWAYS WITH 30" OR MORE ABOVE
GRADE OR FLOOR BELOW.
4. OPENINGS IN GUARDRAILS AND HANDRAILS SHALL NOT ALLOW A 4"
SPHERE TO PASS THROUGH.
3'
-
2
"
M
A
X
.
2'
-
3
"
M
A
X
.
MIN.
1' - 0"
TREAD+12"
1' - 11"
MIN.
1' - 0"
2'
-
3
"
M
A
X
.
3'
-
2
"
M
A
X
.
11"
7"
NOTE:
1. MOUNTING HEIGHT IS 34"-38" TO TOP OF GRIPPING SURFACE ABOVE
STAIR NOSINGS.
2. SURFACE OF HANDRAIL SHALL BE SMOOTH WITH NO SHARP EDGES.
3. EDGES OF HANDRAILS HAVE A MINIMUM RADIUS OF 1/8".
34
"
-
3
8
"
A
B
O
V
E
ST
A
I
R
N
O
S
I
N
G
1 1/4" - 1 1/2"1 1/2" CLR.
1
1
/
2
"
M
I
N
.
MIN. 2" HIGH CURB FOR RAMPS AND
LANDINGS WITH DROP-OFFS
ALLOWABLE RAMP LENGTHS
SLOPE
1:12
1:16
1:20
%
8.33%
6.25%
5.00%
MAX. RISE
30"
30"
30"
MAX. HORIZ. PROJECTION
30'-0"
40'-0"
50'-0"
72" MIN. CLEAR LEVEL LANDING AT
BOTTOM OF RAMP. (60"x60" MIN REQ'D
WHEN RAMP CHANGES DIRECTION AT
LANDING)
60"x60" MIN. CLEAR LEVEL
LANDING AT TOP OF RAMP
NOTE:
IF A RAMP HAS A RISE >6" OR A
HORIZONTAL PROJECTION >72", THEN IT
SHALL HAVE HANDRAILS ON BOTH SIDES
LEVEL LANDING
LEVEL LANDING
RAMP HORIZONTAL PROJECTION
RISE
1:12 SLOPE MAX
RE
Q
'
D
W
I
D
T
H
O
F
R
A
M
P
3'
-
2
"
M
A
X
.
2'
-
3
"
M
A
X
.
1' - 0"
1' - 0"
2'
-
3
"
M
A
X
.
3'
-
2
"
M
A
X
.
2"
6' - 0" MIN.
1' - 0"
5' - 0"
2"
3" + 1"
WHEEL
GUIDE
GUIDE RAIL TO BE CENTERED AT 3" PLUS OR
MINUS 1" ABOVE THE RAMP SURFACE
GUIDE CURB
WHEEL GUIDE
+/
-
1
"
3"
@
L
A
N
D
I
N
G
60
"
M
I
N
RAMP HANDRAILS
(A) HANDRAIL
1 1/4" - 1 1/2"
34
"
-
3
8
"
A
B
O
V
E
ST
A
I
R
N
O
S
I
N
G
O
R
RA
M
P
1 1/2" CLR.
1
1
/
2
"
M
I
N
.
112
MAX. SLOPE = 1:12
3'
-
0
"
3'
-
0
"
3
6
"
1
12
MAX. SLOPE = 1:12
3'
-
0
"
3'
-
0
"
3
6
"
TOP LANDING TO BE AT
LEAST 60" LONG
BOTTOM LANDING TO
BE AT LEAST 72"
LONG
TOP LANDING TO BE AT
LEAST 60" LONG
BOTTOM LANDING TO BE AT
LEAST 72" LONG
1' - 0"
1' - 0"
1' - 0"
1' - 0"
1 1/2" DIAMETER PAINTED STEEL
HANDRAIL MOUNTED 1 1/2" FROM WALL
ON CODE COMPLIANT HANDRAIL
BRACKETS. HANDRAIL MAY NOT
ROTATE AND MUST BE SECURE.
1 1/2" DIAMETER
PAINTED STEEL
HANDRAIL WITH
PAINTED STEEL
POSTS FOR
SUPPORT,
RAMP SECTION AT WALL MOUNTED RAILINGS
RAMP SECTION AT FREESTANDING RAILING
HANDRAIL
EXTENSIONS MAY BE
ROTATED PERP. TO
THE PATH OF RAMP
IF THEY BECOME AN
OBSTRUCTION.
RETURN HAND RAIL ENDS (TYP.)
RETURN HAND RAIL ENDS (TYP.)
3" + 1"
WHEEL
GUIDE
2'
-
0
"
M
A
X
.
D
E
P
T
H
FO
R
M
I
N
C
L
E
A
R
A
N
C
E
SI
D
E
R
E
A
C
H
R
A
N
G
E
FO
R
W
A
R
D
RE
A
C
H
R
A
N
G
E
3' - 0" MIN.
2' - 8" MIN.
10" MAX.2' - 6"
4'
-
0
"
15
"
M
I
N
.
4'
-
0
"
M
A
X
10"2' - 6"
4' - 0"
2'
-
6
"
4' - 0"
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
2
5
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
G0.13
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
ACCESSIBILITY COMPLIANCE
DIAGRAMS
COLLECTORS
-
1/2" = 1'-0"13ADA WHEELCHAIR SEATING
3/16" = 1'-0"5ADA TURN AROUND OBSTRUCTIONS/REACH RANGES
12" = 1'-0"1ADA PROTRUDING OBJECTS / OVERHEAD HAZARDS
12" = 1'-0"2ADA WARNING STRIPING
NTS 6ADA STAIR TREADS
1/2" = 1'-0"7ADA HANDRAIL
1 1/2" = 1'-0"3ADA STAIR HANDRAILS
1/4" = 1'-0"4ADA RAMPS
1 1/2" = 1'-0"10ADA RAMP HANDRAILS
1/2" = 1'-0"12ADA RAMP AND RAILING DETAILS
1/2" = 1'-0"16ADA REACH ANGLES
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
MI
N
.
1'
-
0
"
X
LANDING
LANDING
DOWN
X
MI
N
.
1'
-
0
"
NOTE: INNER HANDRAIL AT LANDINGS OF
STAIRS THAT DOUBLE BACK OR
IMMEDIATELY TURN SHALL BE
CONTINIOUS AND SHALL NOT EXTEND
INTO LANDING OR ACCESSIBLE ROUTE
OF TRAVEL
INNER
HANDRAIL
X = EXTENSION OF HANDRAIL
SHALL BE EQUAL TO THE TREAD
WIDTH PLUS 12 INCHES MINIMUM
DOWN
MI
N
.
1'
-
0
"
X
LANDING
LANDING
DOWN
X
DOWN
MIN.
1' - 0"
DO
W
N
MI
N
.
1'
-
0
"
X
ACCESSIBLE ROUTE OF TRAVEL
LANDING
DOWN
MI
N
.
1'
-
0
"
DOWN
MI
N
.
1'
-
0
"
INNER
HANDRAIL
GUARDRAIL
MAY BE
REQUIRED
MI
N
.
1'
-
0
"
X
LANDING
DOWN
MI
N
.
1'
-
0
"
DOWN
GUARDRAIL
MAY BE
REQUIRED
X
DOWN
LANDING
* NOTE: PROVIDE THIS ADDITIONAL
SPACE IF DOOR IS EQUIPPED WITH
BOTH A LATCH AND A CLOSER
( a ) DOORS AT ADJACENT WALLS
48" MIN.
18
"
M
I
N
.
18
"
M
I
N
.
48" MIN.
( b ) DOORS AT OPPOSITE WALLS
18
"
M
I
N
.
( a ) DOOR IN SERIES
48" MIN.
12
"
M
I
N
.
*
( b ) BOTH DOORS OPEN OUT
12
"
M
I
N
.
*
48" MIN.
12
"
M
I
N
.
*
SLOPE = Y : X
WHERE X IS A
LEVEL PLANE
TOP OF RAMP
STREETWALK
MEASUREMENT OF CURB RAMP SLOPES
X
Y
48" MIN.
2%
MAX.
8.33%
MAX.
TOP OF RAMP
RETAINING
CURB IF
NECCESSARY
SECTION B-B
DEPRESS ENTIRE SIDEWALK AS
REQUIRED
2%
MAX.
2%
MAX.
8.33%
MAX.
48" MIN.
RETAINING
CURB IF
NECCESSARY
SECTION A-A
SECTION C-C
60" MIN.
72" MIN.SEE NOTE 2
SEE NOTE 1SWINGS ONTO LANDING60" MIN. WHEN NO DOOR
SEE NOTE 2
60" MIN.
72" MIN.
AS REQUIRED
5'-0" MIN.
TOP PLATFORM
INTERMEDIATE LEVEL PLATFORM
INTERMEDIATE TURNING PLATFORM
60" MIN.
72" MIN.SEE NOTE 2
SEE NOTE 1
SWINGS ONTO LANDING60" MIN. WHEN NO DOOR
SEE NOTE 2
60" MIN.
AS REQUIRED
TOP PLATFORM
INTERMEDIATE LEVEL PLATFORM
BOTTOM LEVEL PLATFORM
SEE NOTE 1
SWINGS ONTO LANDING60" MIN. WHEN NO DOOR
SEE NOTE 2
60" MIN.
AS REQUIRED
TOP PLATFORM
60" MIN.
72" MIN.
NOTE 1: WHEN DOOR SWINGS ONTO LANDING - 42" MIN. PLUS DOOR WIDTH. NOTE 2: MAXIMUM HORIZONTAL DISTANCES OF EACH RAMP AND RUN VARY.
AS REQUIRED
RAMP WITH INTERMEDIATE SWITCH BACK PLATFORMRAMP WITH TURNING PLATFORMSTRAIGHT RAMP RUN
24" MIN. EXTERIOR AND
18" MIN INTERIOR
BEYOND THE STRIKE
EDGE OF A GATE OR
DOOR ON THE SIE
TOWARD WHICH IS
SWINGS
DO
O
R
W
I
D
T
H
P
L
U
S
4
2
"
60" MIN.
RAMP LANDING AT DOORWAY
FRONT EDGE OF SIDE WALK
CURB
1/2", BEVELED AT 45°
WALL OR OTHER
OBSTRUCTION
A
10%
MAX.
8.
3
3
%
MA
X
.
2%
MA
X
.
10%
MAX.
4'
-
0
"
M
I
N
.
4' - 0" MIN.
A
C
C
48
"
M
I
N
.
8.33%
MAX.
48" MIN.
RETAINING CURB IF
NECESSARY AT EDGE
OF SIDEWALK
2%
MA
X
.
NOTE: TRUNCATED DOMES TO FULL WIDTH AND DEPTH OF CURB RAMP,
EXCEPT FLARED SIDES
DETECTABLE WARNING TO
EXTEND FULL WIDTH AND
36" IN THE DIRECTION OF
TRAVEL OF CURB RAMP,
EXCLUDING FLARED SIDES
BENCH: SIDE ELEVATION
CBC 11B-903
1'
-
4
"
3"1 1/2"
2"
20 - 24".
1'
-
6
"
BENCH: PLAN
CBC 11B-903
BENCH LEGS BOLTED
TO FLOOR
2"
M
A
X
.
30" MIN.
48
"
M
I
N
.
48" MIN.
LOCKERS: PLAN
CBC 11B-222 and 11B-803
10"
30" MIN
NOTE: ACCESSIBLE ('ADA') LOCKER LOCATIONS NOTED
ON FURNITURE PLAN TO BE COORDINATED WITH
FUTURE TENANT VENDOR.
SH
E
L
F
15
"
M
I
N
LOCKERS: ELEVATION
CBC 11B-222 and 11B-803
5 TIER
ADA
SH
E
L
F
48
"
M
A
X
TO
L
A
T
C
H
15
"
M
I
N
-
4
8
"
M
A
X
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
2
6
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
G0.14
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
ACCESSIBILITY COMPLIANCE
DIAGRAMS
COLLECTORS
-
1/4" = 1'-0"1ADA STAIR HANDRAIL
1/4" = 1'-0"9ADA VESTIBULE CLEARANCES
1/2" = 1'-0"7ADA CURB SECTIONS
NTS 4ADA RAMP DIMENSIONS
1/4" = 1'-0"3ADA CURB CUT
1/2" = 1'-0"17ADA LOCKER REQUIREMENTS
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
2
7
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.20
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING SITE PLAN /
ACCESSIBLE PATH OF TRAVEL
DIAGRAM
COLLECTORS
-
ACCESSIBLE PATH OF
TRAVEL FROM ACCESSIBLE
PARKING STALLS
YA
R
D
D
I
S
T
A
N
C
E
65
.
4
'
N
O
R
T
H
YARD DISTANCE
71.2' WEST
32
.
7
'
F
S
D
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
2
8
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.21
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING SITE ENLARGEMENTS
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
2
9
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.22
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING SITE DETAILS
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
3
2
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.23
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING SITE SURVEY
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
3
5
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.24
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING SITE SURVEY
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
3
9
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.25
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING SITE SURVEY
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
4
0
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.30
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING RESTROOM PLAN -
WEST -FOR REFERENCE ONLY
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
4
2
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.31
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING ENLARGED RESTROOM
PLANS -WEST -FOR REFERENCE
ONLY
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
4
4
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.32
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING RESTROOM ADA
REQUIREMENTS -FOR
REFERENCE ONLY
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
4
5
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
G0.33
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EXISTING DETAILS -MILLWORK -
FOR REFERENCE ONLY
COLLECTORS
-
FOR REFERENCE ONLY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
FB
1
(E)
(E
)
(E)(E)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E)
(E)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E)
(E)
(E)
(E
)
(E)
(E)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E)(E)
(E)(E)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E)(E)
FE
C
FEC
(E
)
(E
)
(E
)
(E
)
(E)
(E
)
(E
)
(E
)
(E)
(E
)
J
J
(E)
(E)(E)
(E
)
J
J
(E
)
(E)(E)
(E
)
(E)
(E
)
(E)
(E
)
(E)
(E
)
JJJJJJ
J
(E)(E)
(E
)
(E
)
FE
C
J
J
J
J
J
J
J
J
A A
2
2
4
4
5
5
A.9 A.9
C C
D D
3
3
1
1
E E
F F
G G
E.2 E.2
B.2 B.2
OPEN OFFICE
200
STORAGE
213
A107
A107
A107
A107
A107
A107
A108
A108
1. REFER TO G0.01 FOR SYMBOL LEGEND.
2. REFER TO G0.03 FOR GENERAL NOTES.
3. ALL DIMENSIONS ARE FROM FACE OF FINISH TO FACE OF FINISH, UON.
4. REMOVE ALL ABANDONED POWER AND SIGNAL CABLING BACK TO SOURCE AND SAFE OFF.
5. REMOVE FLOORING FINISHES AND WALL FINISHES THROUGHOUT AREA OF WORK, UON.
A. EXISTING WALL PROTECTION AND CORNER GUARDS TO REMAIN UNLESS OTHERWISE
NOTED.
6. PROVIDE PROTECTION FOR EXISTING FINISHES TO REMAIN.
7. GC SHALL PATCH AND REPAIR AREAS WHERE DEMOLITION OR DAMAGE OCCURRED.
REFINISH DISTURBED AREAS TO MATCH ADJACENT CONDITION. EXTEND PATCH TO
NEAREST NATURAL BREAK POINT.
8. GC TO PATCH AND REPAIR DAMAGED FIRE PROOFING ON STRUCTURAL AND FIRE RATED
ASSEMBLIES. MATCH EXISTING FIRE RATING.
9. REMOVE OR COVER ALL EXISTING PERIMETER WINDOW BLINDS PRIOR TO
COMMENCEMENT OF DEMOLITION. CLEAN AND UNCOVER OR REINSTALL AT COMPLETION
OF CONSTRUCTION.
10. CONSULT WITH LANDLORD REGARDING SALVAGE AND REUSE OF BUILDING STANDARD
ELEMENTS NOT REQUIRED FOR NEW CONSTRUCTION.
11. ANY DEMOLITION DRAWINGS AND NOTES ARE PROVIDED FOR CONVENIENCE AND
INFORMATION ONLY AND ARE NOT INTENDED TO REPRESENT THE COMPREHENSIVE STATE
OF THE BUILDING(S). VERIFY THE EXISTING STATE OF THE BUILDING(S) FINISHES AND
BUILDING SYSTEMS.
12. CONTRACTOR TO COORDINATE AND VERIFY ALL DEMOLITION WITH ALL ALTERATION
PLANS.
13. FOLLOWING DEMOLITION, ALL EXISTING DIMENSIONS AND CONDITIONS ARE TO BE
CHECKED BY THE CONTRACTOR FOR CONFORMANCE WITH THE REQUIREMENTS OF THE
NEW CONSTRUCTION. ANY INCONSISTENCIES OR UNFORESEEN CONDITIONS ARE TO BE
SUBMITTED TO THE ARCHITECT FOR REVIEW PRIOR TO THE COMMENCEMENT OF WORK.
14. CONTRACTOR TO REMOVE ALL DEMOLISHED MATERIALS AND ITEMS FROM THE SITE IN
ACCORDANCE WITH ALL APPLICABLE AGENCY CODES AND REGULATIONS.
15. CONTRACTOR SHALL TAKE SPECIAL CARE TO PRESERVE THOSE ELEMENTS THAT ARE TO
REMAIN. ANY ITEMS THAT ARE TO BE RE-USED MUST BE STORED AND PROTECTED AS
REQUIRED FOR RE-USE.
16. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO ENSURE THE SAFETY OF
THE EXISTING STRUCTURE.
17. CONTRACTOR SHALL PROVIDE, ERECT AND MAINTAIN ALL TEMPORARY BARRIERS AND
GUARDS, AND ALL TEMPORARY SHORING AND BRACING AS REQUIRED BY ALL CITY AND
STATE REGULATIONS.
18. WHERE SCHEDULED TO BE DEMOLISHED, EXISTING FLOOR BOXES TO BE SAFED OFF AND
CAPPED WITH A FLUSH TO FLOOR PLATE OR MANUFACTURER RECOMMENDED CAP AND
COVERED WITH SCHEDULED FLOOR FINISH. WHERE BOXES OCCUR AT EXPOSED
CONCRETE, BOX TO BE REMOVED AND PATCHED BACK WITH CONCRETE.
19. WHERE EXISTING POWER/DATA WALL OUTLETS ARE TO BE DEMOLISHED, WALL IS TO BE
PATCHED, REPAIRED, AND PREPPED ACCORDINGLY.
DEMOLISHED CONSTRUCTION
EXISTING CONSTRUCTION
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
1
5
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
AD2.11
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
LEVEL 02 -DEMOLITION PLAN
COLLECTORS
-
KEYNOTES
3/32" = 1'-0"1LEVEL 02 - PLAN, DEMO
A107 DEMO EXISTING DOOR AT THIS LOCATION
A108 EXISTING FLOOR FINISHES TO REMAIN AND VERIFY CONDITIONS IN FIELD
LEGEND
SHEET NOTES
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
1. REFER TO G0.01 FOR SYMBOL LEGEND.
2. REFER TO G0.03 FOR GENERAL NOTES.
3. ALL DIMENSIONS ARE FROM FACE OF FINISH TO FACE OF FINISH, UON.
4. REMOVE ALL ABANDONED POWER AND SIGNAL CABLING BACK TO SOURCE AND SAFE OFF.
5. REMOVE FLOORING FINISHES AND WALL FINISHES THROUGHOUT AREA OF WORK, UON.
A. EXISTING WALL PROTECTION AND CORNER GUARDS TO REMAIN UNLESS OTHERWISE
NOTED.
6. PROVIDE PROTECTION FOR EXISTING FINISHES TO REMAIN.
7. GC SHALL PATCH AND REPAIR AREAS WHERE DEMOLITION OR DAMAGE OCCURRED.
REFINISH DISTURBED AREAS TO MATCH ADJACENT CONDITION. EXTEND PATCH TO
NEAREST NATURAL BREAK POINT.
8. GC TO PATCH AND REPAIR DAMAGED FIRE PROOFING ON STRUCTURAL AND FIRE RATED
ASSEMBLIES. MATCH EXISTING FIRE RATING.
9. REMOVE OR COVER ALL EXISTING PERIMETER WINDOW BLINDS PRIOR TO
COMMENCEMENT OF DEMOLITION. CLEAN AND UNCOVER OR REINSTALL AT COMPLETION
OF CONSTRUCTION.
10. CONSULT WITH LANDLORD REGARDING SALVAGE AND REUSE OF BUILDING STANDARD
ELEMENTS NOT REQUIRED FOR NEW CONSTRUCTION.
11. ANY DEMOLITION DRAWINGS AND NOTES ARE PROVIDED FOR CONVENIENCE AND
INFORMATION ONLY AND ARE NOT INTENDED TO REPRESENT THE COMPREHENSIVE STATE
OF THE BUILDING(S). VERIFY THE EXISTING STATE OF THE BUILDING(S) FINISHES AND
BUILDING SYSTEMS.
12. CONTRACTOR TO COORDINATE AND VERIFY ALL DEMOLITION WITH ALL ALTERATION
PLANS.
13. FOLLOWING DEMOLITION, ALL EXISTING DIMENSIONS AND CONDITIONS ARE TO BE
CHECKED BY THE CONTRACTOR FOR CONFORMANCE WITH THE REQUIREMENTS OF THE
NEW CONSTRUCTION. ANY INCONSISTENCIES OR UNFORESEEN CONDITIONS ARE TO BE
SUBMITTED TO THE ARCHITECT FOR REVIEW PRIOR TO THE COMMENCEMENT OF WORK.
14. CONTRACTOR TO REMOVE ALL DEMOLISHED MATERIALS AND ITEMS FROM THE SITE IN
ACCORDANCE WITH ALL APPLICABLE AGENCY CODES AND REGULATIONS.
15. CONTRACTOR SHALL TAKE SPECIAL CARE TO PRESERVE THOSE ELEMENTS THAT ARE TO
REMAIN. ANY ITEMS THAT ARE TO BE RE-USED MUST BE STORED AND PROTECTED AS
REQUIRED FOR RE-USE.
16. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO ENSURE THE SAFETY OF
THE EXISTING STRUCTURE.
17. CONTRACTOR SHALL PROVIDE, ERECT AND MAINTAIN ALL TEMPORARY BARRIERS AND
GUARDS, AND ALL TEMPORARY SHORING AND BRACING AS REQUIRED BY ALL CITY AND
STATE REGULATIONS.
18. WHERE SCHEDULED TO BE DEMOLISHED, EXISTING FLOOR BOXES TO BE SAFED OFF AND
CAPPED WITH A FLUSH TO FLOOR PLATE OR MANUFACTURER RECOMMENDED CAP AND
COVERED WITH SCHEDULED FLOOR FINISH. WHERE BOXES OCCUR AT EXPOSED
CONCRETE, BOX TO BE REMOVED AND PATCHED BACK WITH CONCRETE.
19. WHERE EXISTING POWER/DATA WALL OUTLETS ARE TO BE DEMOLISHED, WALL IS TO BE
PATCHED, REPAIRED, AND PREPPED ACCORDINGLY.
DEMOLISHED CONSTRUCTION
EXISTING CONSTRUCTION
A A
2
2
4
4
5
5
A.9 A.9
C C
D D
3
3
1
1
E E
F F
G G
E.2 E.2
B.2 B.2
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
1
6
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
AD2.12
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
LEVEL 02 -PLAN, REFLECTED
CEILING DEMOLITION
COLLECTORS
-
KEYNOTES
LEGEND
SHEET NOTES
3/32" = 1'-0"1LEVEL 02 - PLAN, REFLECTED CEILING DEMOLITION
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
FE
C
FEC
FE
C
1. REFER TO G0.01 FOR SYMBOL LEGEND.
2. REFER TO G0.03 FOR GENERAL NOTES.
3. SEE A7.00 AND A7.01 FOR TYPICAL INTERIOR FRAMING DETAILS.
4. LOCATE NEW PARTITIONS ON CENTER LINE OF MULLION OR ALIGNED WITH COLUMN OR
WALL, UON. SEE TYPICAL PARTITION DETAILS ON SHEET A7.02.
5. ALL PARTITIONS SHALL BE TYPE W01A, UON.
6. ALL GLAZING SHALL BE TYPE G01, UON. PROVIDE GLAZING SEALANT COLOR SAMPLE FOR
ARCHITECT’S REVIEW. GLAZING STOP COLOR TO MATCH FRAME.
7. REPAIR OR REPLACE DAMAGED OR MISSING GYPSUM BOARD ON EXISTING PARTITIONS AND
COLUMNS TO REMAIN. MATCH EXISTING PARTITION TYPE AND FINISHES.
8. PROVIDE BACKING AS NEEDED TO SUPPORT WALL HUNG ITEMS INCLUDING, BUT NOT
LIMITED TO, SIGNAGE, RESTROOM ACCESSORIES, GRAB BARS, EQUIPMENT, AND FURNITURE.
9. GC SHALL FIELD CUT MILLWORK AS NECESSARY TO ALLOW ACCESS TO WALL POWER AND
SIGNAL LOCATIONS. FIELD VERIFY CONDITIONS.
10. ALL SIGNAGE IS BY TENANT’S VENDOR.
11. PER CBC 703.7: FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND
SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS OR
PENETRATIONS SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
STENCILING. SUCH IDENTIFICATION SHALL:
A. BE LOCATED IN ACCESSIBLE CONCEALED FLOOR, FLOOR-CEILING OR ATTIC
SPACES.
B. BE LOCATED WITHIN 15 FEET OF THE END OF EACH WALL AND AT INTERVALS NOT
EXCEEDING 30 FEET (914 MM) MEASURED HORIZONTALLY ALONG THE WALL OR
PARTITION; AND
C. INCLUDE LETTERING NOT LESS THAN 3 INCH IN HEIGHT WITH A MINIMUM 3/8-INCH
STROKE IN CONTRASTING COLOR INCORPORATING THE SUGGESTED WORDING: “FIRE
AND/OR SMOKE BARRIER--PROTECT ALL.
12. NO HAZARDOUS MATERIALS ARE TO BE STORED IN THE BUILDING.
13. WINDOW COVERINGS: PROVIDE ALLOWANCE TO CLEAN, REPAIR AND REPLACE AS NEEDED.
DOOR TAG
WALL TAG
STOREFRONT / CURTAIN WALL TAG
XX
CHANGE IN ELEVATION LEVEL
101
APPLIANCE, PLUMBING, AND EQUIPMENT TAGS
1i
1i
EXISTING CONSTRUCTION
1 HR RATED PARTITION
NEW CONSTRUCTION
A A
2
2
4
4
5
5
A.9 A.9
C C
D D
3
3
1
1
E E
F F
G G
E.2 E.2
B.2 B.2
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
MTRL
CONVEYOR
CONFERENCE
210
MDF
211
OFFICE
212
AL
I
G
N
(E) ELEC
214
W40
W40W40
W40
213
OFFICE GROWTH
213
203(E)204(E)
201(E)
205(E)206(E)207(E)208(E)209(E)
210(E)
211(E)
212(E)
214(E)
200(E)
202(E)
215(E)
(E) STAIRS
W01A
216
W24
W24
W24
W24
W24
W24
W24
W24
W24
W24
A109
A109
A109
A109
A109
W24W24
W24
W24
W24 W24
W24
W24
W10
5' - 5"
W24
W24
W24
W24
W24
W24
A109
A109
A109
A109
65' - 1"
15' - 7 3/4"
ALIGN
217
W10A
W24
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
4
8
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
A2.21
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
LEVEL 02 -CONSTRUCTION PLAN
COLLECTORS
-
KEYNOTES
LEGEND
SHEET NOTES
MARK DESCRIPTION DETAIL #
W01A 3 5/8" MTL STUD PARTITION; FULL HEIGHT TO UNDERSIDE OF DECK; (1)
LAYER 5/8" GYP BOTH SIDES; ACOUSTICAL
1/A7.02
W10 (1) LAYER 5/8" GYP ON ONE SIDE 3/A7.02
W10A 3 5/8" MTL STUD FURRING; FULL HEIGHT TO UNDERSIDE OF DECK; (1)
LAYER 5/8" GYP ONE SIDE
4/A7.02
W24 (1) LAYER 5/8" GYP; (1) LAYER METAL GRID MESH ONE SIDE 2/A7.02
W30A 6" C-H STUD SHAFT WALL: ACOUSTICAL; 1 HR RATED (UL145,U469) 1/A6.00
W40 CHAIN LINK FENCING: 11.5 GA BY 1" MINI MESH CHAIN LINK FENCE
FABRIC W/ 1-5/8" POSTS. POST TO UNDERSIDE OF CEILING.
PER MFR REC
WALL SCHEDULE
A109 VERIFY EXISTING WALLS IN FIELD AND EXTEND TO DECK AS REQUIRED TO MATCH
WALL TYPE W01A
3/32" = 1'-0"1LEVEL 02 - PLAN, CONSTRUCTION
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
OCC
WAP
CAM
1
CAM
2
SP
PP
1
A A
2
2
4
4
5
5
A.9 A.9
C C
D D
3
3
1
1
E E
F F
G G
E.2 E.2
B.2 B.2
(E)F1A
(E)F1A(E)F1A
(E)F1A(E)F1A
(E)F1A(E)F1A
(E)F1A(E)F1A
(E)F1A(E)F1A
(E)F1A(E)F1A
(E)F1A
(E)F1A
(E)F1A(E)F1A
(E)F1A
(E)F1A (E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A
(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A
(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A
(E)F1A (E)F1A (E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A
(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A
(E)F1A (E)F1A (E)F1A
(E)F1A(E)F1A(E)F1A
(E)F1A (E)F1A
(E)F1A
(E)F1A (E)F1A
(E)F1A
(E)F1A(E)F1A
(E)F1A
(E)F1A (E)F1A
(E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A (E)F1A
(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A(E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A (E)F1A(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A
(E)F1A(E)F1A(E)F1A
(E)F1A(E)F1A(E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A
(E)F1A (E)F1A
(E)F1A
(E)F1A(E)F1A(E)F1A(E)F1A
(E)F1A
(E)F1A (E)F1A
(E)F1A (E)F1A
(E)F1A (E)F1A
(E)F1A
F1A F1A F1A
F1A
F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A
(E)F1A (E)F1A
(E)F1A (E)F1A
(E)F1A (E)F1A (E)F1A (E)F1A (E)F1A
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
STORAGE
213
(E) ELEC
214
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
210
OFFICE
212
MDF
211
(E)
F1A F1A F1A
A110
A110
A110
(E)
A110
MTRL
CONVEYOR
(E)
A.F.F.
ACT-1
9' - 0"
(E) STAIRS
F2
F2 F2
F2
F2
F2
(E)
F2
52' - 0 1/16"
1. REFER TO G0.01 FOR SYMBOL LEGEND.
2. REFER TO G0.03 FOR GENERAL NOTES.
3. REFER TO A7.20 FOR TYPICAL CEILING DETAILS.
4. REFER TO A2.14 FOR GYPSUM BOARD CEILING FINISHES.
5. REFER TO A6.11 FOR LIGHTING FIXTURE SPECIFICATIONS.
6. REFER TO ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION.
7. SEE DETAIL 1/A7.40 FOR TYPICAL LIGHT SWITCH MOUNTING HEIGHT. REFER TO ELEC DWGS
FOR LIGHT SWITCH LOCATIONS.
8. SUSPENDED CEILING GRID, LIGHT FIXTURES, AND OTHER CEILING DEVICES ARE NEW,UNO.
9. ALL ITEMS ARE BUILDING STANDARD, UON. REFER TO BUILDING CONSTRUCTION GUIDELINES
FOR SPECIFICATIONS.
10. ACOUSTIC CEILING TILE GRID SYSTEM HEIGHT TO EXISTING, UNO.
11. ACOUSTIC CEILING TILE AND GRID SPECIFICATION TO MATCH EXISTING, UNO.
12. ALL DIMENSIONS FOR LIGHT FIXTURES ARE TO FIXTURE CENTER LINE, UON.
13. CEILING GRILLES AND DIFFUSERS TO BE WHITE IN COLOR, UON.
14. GANG ALL SWITCH PLATE COVERS WHERE PRACTICAL.
15. CENTER LIGHT FIXTURES AND SPRINKLER HEADS IN 2 x 2 AND 2 x 4 CEILING TILES
RESPECTIVELY, UON.
16. LOCATION OF ALL NEW DRYWALL CEILING RELATED ITEMS INCLUDING, BUT NOT LIMITED TO,
STROBES, SMOKE DETECTORS, SPRINKLERS, ACCESS PANELS, AIR GRILLES, LIGHTS, ETC. TO
BE ALIGNED WHERE ADJACENT. FINAL LOCATIONS TO BE REVIEWED AND APPROVED BY
ARCHITECT PRIOR TO BEGINNING OF WORK.
17. PROVIDE CONCEALED TYPE SPRINKLER HEADS AT DRYWALL CEILINGS. CAPS TO BE WHITE,
UON.
18. PROVIDE DIMMABLE WALL WASHERS AND DOWN LIGHTS IN CONFERENCE ROOMS, UON.
19. PROVIDE IN-CEILING SUPPORT FOR CEILING MOUNTED / RECESSED AV EQUIPMENT.
CONTRACTOR TO VERIFY REQUIREMENTS WITH AV VENDOR.
20. CENTER CEILING GRIDS IN ROOMS WITH DISCONTINUOUS GRID, UON.
21. REFER TO A2.15 FOR AV EQUIPMENT INFORMATION.
22. AT OPEN CEILINGS: PATCH (E) FIREPROOFING AND PAINT UNDERSIDE OF ALL EXPOSED DECK
/ FIREPROOFED DECK / ITEMS INCLUDING PIPES, SPRINKLER LINES AND CONDUIT. REFER TO
REFLECTED CEILING PLANS FINISH TAGS AND A1.16 FINISH PLANS FOR ADDITIONAL
INFORMATION.
23. AT OPEN CEILINGS: ALL EXPOSED DUCTWORK TO BE GALVANIZED HARD DUCT WITH CLEAR
JOINT SEALER AND PAINTED AS SCHEDULED. ALL EXPOSED DUCTS TO BE HUNG WITH
STRAPS. NO. 8 GAUGE GALVANIZED STEEL WIRE IS NOT ACCEPTABLE. NO FLEX DUCT TO BE
INSTALLED IN EXPOSED AREAS. NO DUCTS IN EXPOSED AREAS TO RECEIVE INSULATION
WRAP. RUN NEW DUCT AS TIGHT AS POSSIBLE TO UNDERSIDE OF (E) BEAMS AND DECK.
24. AT OPEN CEILINGS: ALL EXPOSED CONDUIT, SPRINKLER LINES AND HVAC DUCT TO RUN
PERPENDICULAR TO OFFICE AND EXTERIOR WALLS. GANG EXPOSED CONDUIT RUNS TIGHT
TO ONE ANOTHER AND ALIGNED W/ DUCT RUNS OR CABLE TRAY RUNS TO PROVIDE AN
ALIGNED AND COLLECTED GROUPING APPEARANCE. RUN CONDUIT AS TIGHT AS POSSIBLE
TO UNDERSIDE OF (E) BEAMS.
25. ALL DRYWALL ACCESS PANELS TO INCLUDE A DRYWALL PANEL SYSTEM.
26. ALL J-BOXES LOCATED IN EXPOSED CEIILINGS ARE TO BE COORDINATED IN FIELD W/
ARCHITECT.
27. COORDINATE FIXTURES IN FIELD WITH EXISTING DUCTWORK. ARCHITECT TO APPROVE.
28. ALL WALL MOUNTED THERMOSTATS, OCCUPANCY SENSORS, CO2 SENSORS, ETC, TO BE
GANGED WITH LIGHT SWITCHES IN ENCLOSED ROOMS. ALL WALL MOUNTED THERMOSTATS,
OCCUPANCY SENSORS, CO2 SENSORS, ETC, TO BE GANGED IN OPEN SPACES, WHERE
POSSIBLE FINAL LOCATIONS TO BE REVIEWED AND APPROVED BY ARCHITECT.
29. AT OPEN TO DECK CONDITIONS, PAINT TO BE APPLIED TO DECK AND WALLS, MEP/IT/SECURITY
INFRASTRUCTURE, ETC, DOWN TO DATUM AT 9'-6" AFF.
30. CEILING GRID SUSPENSION SYSTEM TO BE ARMSTRONG SILHOUETTE TO MATCH EXISTING.
ASTM CLASS TO BE HD-HEAVY DUTY. SYSTEM TO BE INSTALLED IN ACCORDANCE WITH ASTM
C635, ASTM C636, AND ASTM E580 SECTION 5.
31. FOR CEILING AREAS EXCEEDING 2,500 SF, A SEISMIC SEPARATION JOINT OR FULL HEIGHT
PARTITION THAT BREAKS THE CEILING UP INTO AREAS NOT EXCEEDING 2,500 SF SHALL BE
PROVIDED UNLESS STRUCTURAL ANALYSES ARE PERFORMED OF THE CEILING BRACING
SYSTEM FOR THE PRESCRIBED SEISMIC FORCES THAT DEMONSTRATE CEILING SYSTEM
PENETRATIONS AND CLOSURE ANGLES PROVIDE SUFFICIENT CLEARANCE TO ACCOMMODATE
THE ANTICIPATED LATERAL DISPLACEMENT. EACH AREA SHALL BE PROVIDED WITH CLOSURE
ANGLES.
32. WHERE NEW PARTITIONS ARE SCHEDULED TO BE INSTALLED AT EXISTING CEILINGS, AS MUCH
OF EXISTING CEILING AS POSSIBLE TO BE SALVAGED AND CEILING TO BE PATCHED BACK
WITH NEW WHERE REQUIRED.
33. SPRINKLER HEADS TO BE EXPOSED AT ACT CEILINGS AND WHERE OPEN TO DECK CEILING
CONDITIONS OCCUR. SPRINKLER HEADS TO BE RECESSED WITH DROP DOWN CAPS TO
MATCH CEILING COLOR AT SPECIALTY AND GYPSUM BOARD CEILINGS.
EXISTING 2X2 ACOUSTIC CEILING TILE
OPEN TO DECK
OCCUPANCY SENSOR - MOUNT VARIES (S.E.D.)
WIRELESS ACCESS POINT - MOUNT VARIES (S.E.D.)
SECURITY CAMERA - MOUNT VARIES (S.R.D.)
SPEAKER - MOUNT VARIES (S.V.D.)
AV CAMERA - MOUNT VARIES (S.V.D.)
EXIT SIGN - MOUNT VARIES (SEE PLAN)
ACT-1 - NEW 2X2 ACOUSTIC CEILING TILE (MATCH EXISTING)
EXISTING 2X4 ACOUSTIC CEILING TILE
ACT-2 - NEW 2X4 ACOUSTIC CEILING TILE (MATCH EXISTING)
POWER POLE - (S.E.D)
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
5
2
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
A2.22
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
LEVEL 02 -REFLECTED CEILING
PLAN
COLLECTORS
-
3/32" = 1'-0"1LEVEL 02 - PLAN, REFLECTED CEILING PLAN KEYNOTES
SHEET NOTES
A110 (E) LIGHT FIXTURES TO SHIFT WITHIN CEILING GRID WHERE IN CONFLICT WITH (N)
POWER POLES, TYPICAL
LEGEND
TYPE DESCRIPTION
ACT-1 2x2 ACOUSTIC CEILING TILE; GRID AND TILE TO MATCH EXISTING
ACT-2 2X4 ACOUSTIC CEILING TILE; GRID AND TILE TO MATCH EXISTING
CEILING SCHEDULE
09/30/27
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
FB
1
FB
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
PP
1
(E)
(E
)
(E)(E)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E)
(E)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
+66"
(E
)
(E
)
(E)
(E)
(E)
(E
)
(E)
(E)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E)(E)
(E)(E)
(E
)
(E
)
(E
)
CR
CR
CR
CR
+66"
(E
)
(E
)
(E
)
(E)(E)
CR
CR
FE
C
FEC
(E
)
(E
)
(E
)
(E
)
(E)
(E
)
(E
)
(E
)
(E)
(E
)
J
J
(E)
(E)(E)
(E
)
J
J
(E
)
(E)(E)
(E
)
(E)
(E
)
(E)
(E
)
(E)
(E
)
JJJJJJ
J
(E)(E)
(E
)
(E
)
FE
C
J
J
J
J
J
J
J
J
CR
CR CR CR CR
CR
CR
FB
1
PP
1
J
T
AV
TV
CR
CA
1
RS
CP
1
SU
1
A A
2
2
4
4
5
5
A.9 A.9
C C
D D
3
3
1
1
E E
F F
G G
E.2 E.2
B.2 B.2
OFFICE
203
OFFICE
204 OFFICE
205 STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
202
OFFICE
212
MDF
211
CONFERENCE
210
MTRL
CONVEYOR
(E) ELEC
201
(E) ELEC
214
EQ122
EQ122
EQ122
EQ122
+6
6
"
+6
6
"
A101
EQ202
EQ202
OPEN OFFICE
200
(E) STAIRS
+1
8
"
+1
8
"
+6
6
"
+1
8
"
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
(E
)
A101
BF-1
1. REFER TO G0.01 FOR SYMBOL LEGEND.
2. REFER TO G0.03 FOR GENERAL NOTES.
3. REFER TO DETAIL 1/A7.40 FOR TYPICAL DEVICE MOUNTING HEIGHTS.
4. REFER TO ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION.
5. SEE ELECTRICAL DRAWINGS FOR WALL SWITCH LOCATIONS.
6. TELE / DATA CABLING PROVIDED BY TENANT UNDER SEPARATE CONTRACT. VERIFY OUTLET
AND CONDUIT REQUIREMENTS WITH TENANT’S VENDOR. GC TO PROVIDE CONDUIT, BACK BOX,
AND TAGGED PULL STRINGS
7. FURNITURE IS SHOWN FOR REFERENCE ONLY AND IS NOT IN CONTRACT. GC TO VERIFY
FURNITURE POWER AND SIGNAL REQUIREMENTS AND LOCATIONS WITH FURNITURE VENDOR
PRIOR TO BEGINNING WORK. GC TO CUT FURNITURE WHIPS TO APPROPRIATE LENGTHS AND
TO CONNECT WHIPS TO FURNITURE POWER IN FEEDS.
8. COVER PLATES, SWITCHES, AND OUTLETS TO BE WHITE IN COLOR, UON. AT MILLWORK,
SPECIALTY FINISH AND ACCENT WALL LOCATIONS, CONFIRM COLOR W/ ARCHITECT.
9. GC TO LAYOUT FLOOR CORE LOCATIONS FOR ARCHITECT’S REVIEW ON SITE PRIOR TO
BEGINNING WORK.
10. MOUNT ALL DATA / ELECTRICAL RECEPTACLES AND LIGHITING/EQUIPMENT SWITCHES ABOVE
WORK SURFACES AND ABOVE COUNTER TOPS HORIZONTALLY.
11. ALL OUTLES AT WET LOCATIONS TO BE GFI DEVICES.
12. PROVIDE OUTLET BOX WITH 3/4" CONDUIT STUBBED TO PLENUM 6" ABOVE CEILING AT WALL
MOUNTED DATA OUTLETS IN FULL HEIGHT OR ACOUSTICAL PARTITIONS.
13. PROVIDE CONDUIT FROM FLOOR DATA RISER CLOSET TO TENANT'S TERMINAL BOARD
LOCATION. SIZE AND ROUTING TO BE COORDINATED WITH TENANT'S CABLING VENDOR.
14. OFFSET ALL WALL MOUNTED OUTLETS SHOWN BACK TO BACK ON PLAN TO AVOID BACK TO
BACK INSTALLATION. OUTLETS IN ACOUSTICALLY TREATED WALLS SHALL BE LOCATED IN
SEPARATE STUD BAYS OR ACOUSTICALLY SEALED.
15. LOCATE WALL OUTLETS AT DIMENSION NOTED OR ON STUD WITHIN 12" OF LOCATION SHOWN
ON DOCUMENT IF NOT NOTED. FURNITURE VENDOR TO PROVIDE FURNITURE POWER
LOCATIONS COORDINATED WITH FINAL FURNITURE LAYOUT.
16. HORIZONTAL DIMENSION ARE TO THE CENTER LINE OF SINGLE OUTLETS AND THE MID-POINT
OF MULTI - GANG DEVICES.
17. MAINTAIN 3" CLEAR AT FLOOR OUTLETS ADJACENT TO WALL UON.
18. WHERE FLOOR MONUMENTS ARE SHOWN NEXT TO EACH OTHER, LOCATE THEM AS CLOSE
TOGETHER AS PRACTICAL.
19. ARCHITECTURAL DRAWINGS OVER-RIDE ENGINEERING DOCUMENTS FOR THE LOCATIONS OF
OUTLETS.
20. PROVIDE ABOVE CEILING POWER FOR EQUIPMENT LOCATED AT CEILING. REFER TO A2.13 FOR
LOCATIONS.
21. AV EQUIPMENT PROVIDED AND INSTALLED BY TENANT’S VENDOR. GC TO PROVIDE
ASSOCIATED POWER, SIGNAL, AND CONDUIT. GC TO VERIFY REQUIREMENTS WITH AV
VENDOR.
22. SECURITY CAMERAS AND CARD READERS BY TENANT’S SECURITY VENDOR. GC TO PROVIDE
ASSOCIATED POWER, SIGNAL, AND CONDUIT. VERIFY REQUIREMENTS AND LOCATIONS WITH
TENANT’S SECURITY VENDOR PRIOR TO COMPLETING WORK.
23. S.E.D. FOR EQUIPMENT DISCONNECT LOCATIONS.
WALL J-BOX - TELE/DATA
WALL DATA OUTLET
WALL DUPLEX, DEDICATED
WALL QUAD, DEDICATED
WALL J-BOX - AUDIO VISUAL
WALL J-BOX - CABLE TV
WALL J-BOX - CARD READER
WALL J-BOX - POWER
POWER POLE
-LEGRAND, WIREMOLD - 25 DTP-4BK / 25 DTC-4BK, BLACK FINISH
FLUSH FLOOR BOX
-S.E.D., S.V.D. FOR ADDITIONAL INFORMATION
COMPRESSED AIR
-S.P.D. FOR ADDITIONAL INFORMATION
WALL J-BOX - ROOM SCHEDULER
WALL QUAD
WALL DUPLEX
EXISTING WALL DUPLEX
(E)
CEILING POWER
-HUBBELL HBLC40123TT, S.E.D. FOR ADDITIONAL INFORMATION
STUB UP
-S.E.D., S.V.D. FOR ADDITIONAL INFORMATION
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
5
5
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
A2.23
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
LEVEL 02 -POWER-DATA PLAN
COLLECTORS
-
3/32" = 1'-0"1LEVEL 02 - PLAN, POWER - DATA
A101 TYPICAL EQUIPMENT AT ALL WORKSTATIONS GROUPINGS
SHEET NOTES
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
FE
C
FEC
FE
C
A A
2
2
4
4
5
5
A.9 A.9
C C
D D
3
3
1
1
E E
F F
G G
E.2 E.2
B.2 B.2
(E) ELEC
201
OPEN OFFICE
200
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
210
MDF
211
OFFICE
212
(E) ELEC
214
STORAGE
213
CPT-01
CPT-01
CPT-01 CPT-01 CPT-01 CPT-01 CPT-01 CPT-01 CPT-01 CPT-01
CPT-01
CPT-01
(E) STAIRS
A108
A108
MTRL
CONVEYOR
FLOOR MATERIAL TRANSITION
CASEWORK FINISH TAG
FLOOR FINISH TAG
WALL FINISH TAG
X-0
X-0
X-0
CARPET TILE
STATIC CONTROL FLOORING
1. REFER TO G0.01 FOR SYMBOL LEGEND.
2. REFER TO G0.03 FOR GENERAL NOTES.
3. ALL PARTITIONS TO RECEIVE PT-01, UON.
4. ALL WALLS TO RECEIVE RB-01 WALL BASE, UON.
5. ALL FLOORS TO RECEIVE CON-01, UON.
6. GYPSUM BOARD CEILINGS AND SOFFITS TO RECEIVE PT-01, UON. SEE RCP FOR FINISH
CALLOUTS.
7. REPAIR AND TOUCH UP FINISHES AT EXISTING PERIMETER WINDOW SILLS.
8. PAINT EXISTING PAINT GRADE DOORS AND FRAMES TO MATCH ADJACENT PARTITION,
UON.
9. INSTALL RESILIENT BASE IN CONTINUOUS STRIPS FROM 120’ - 0” ROLLS. NO JOINTS TO BE
WITHIN 12”OF A CORNER. STRAIGHT BASE AT CARPET. COVE BASE AT HARD SURFACE
FLOORING.
10. PROVIDE REDUCER STRIP WHERE CARPET MEETS VINYL OR CONCRETE FLOOR. PROVIDE
SAMPLE COLOR TO BE APPROVED BY ARCHITECT. SEE DETAILS FOR SPECIFICATION.
11. TRANSITION OF DIFFERING FLOORING MATERIAL TO OCCUR AT CENTER LINE OF DOOR,
TYPICAL.
12. CARPET IS TACKLESS OVER PAD INSTALLATION.
13. ALL INTERIOR FINISH MATERIALS AS PART OF TENANT IMPROVEMENT MUST MEET FLAME
SPREADS OF LESS THAN:
A. CLASS A - 25 (UNSPRINKLERED AREAS ABOVE CEILING)
B. CLASS B - 75 (INTERIOR EXIT STAIRWAYS, RAMPS, EXIT PASSAGEWAYS)
C. CLASS C - 200 (OTHER ROOMS AND ENCLOSED SPACES)
14. AT CON-01 CONTRACTOR TO CARRY ALLOWANCE TO PATCH AND REPAIR WHERE
DAMAGED; GOUGES LARGER THAN 1/4" TO BE FILLED AND CONCRETE TO BE GROUND
FLUSH WHERE CRACKS OCCUR.
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
5
8
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
A2.24
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
LEVEL 02 -FINISH PLAN
COLLECTORS
-
3/32" = 1'-0"1LEVEL 02 - PLAN, FINISH PLAN
LEGEND
SHEET NOTES
A108 EXISTING FLOOR FINISHES TO REMAIN AND VERIFY CONDITIONS IN FIELDA108 EXISTING FLOOR FINISHES TO REMAIN AND VERIFY CONDITIONS IN FIELD
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
A A
2 4 5
A.9 A.9
C C
D D
31
E E
F F
G G
E.2 E.2
B.2 B.2
A104
FOR REFERENCE ONLY. REFER
TO MECHANICAL DRAWING
EXISTING MECHANICAL
SCREENING TO REMAIN
EXISTING MECHANICAL
SCREENING TO REMAIN
17' - 0"
8'
-
0
"
A113
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
3
:
5
9
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
3/32" = 1'-0"23008.00
A2.30
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
ROOF PLAN
COLLECTORS
-
KEYNOTES
3/32" = 1'-0"1ROOF PLAN - WEST
A104 SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION
A113 NEW PROPOSED ROOFTOP CONDENSER (38L X 12W X 55 H). REFER TO MECHANICAL
DRAWINGS FOR ADDITIONAL INFORMATION
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
1. DOUBLE DOOR W/ CARD READER
(7) PAIR BUTT HINGES
(1) PAIR ELECTRIC HINGE
(2) ELECTRIC LEVER LOCKSET
(1) CARD READER
(2) CLOSERS
(1) ASTRAGAL
(1) COORDINATOR
(2) AUTOMATIC DOORBOTTOM
1. ALL DOORS TO COMPLY WITH ADA ACCESS REQUIREMENTS, UON. REFER TO DETAILS ON
THIS SHEET.
2. WOOD DOORS SHALL BE WDMA PREMIUM GRADE. ALL DOORS SHALL BE 5-PLY
CONSTRUCTION AS MANUFACTURED BY ALGOMA HARDWOODS, EGGERS INDUSTRIES, OR
MARSHFIELD DOOR. 7-PLY DOORS ARE NOT ACCEPTABLE. ANY SUBSTITUTIONS TO THE
THREE LISTED MANUFACTURES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT
PRIOR TO BID.
3. ALL STAIN GRADE DOORS SHALL BE FACTORY FINISHED WITH MFR’S STANDARD UV CURED
FINISH. SEE DOOR FINISH TYPES FOR ADDITIONAL INFORMATION.
4. HINGES SHALL BE BY HAGER, MCKINNEY, OR STANLEY. ALL OPENINGS WITH CLOSERS AND
ALL RATED OPENINGS SHALL HAVE BALL BEARING HINGES. DOORS GREATER THEN 36” IN
WIDTH SHALL HAVE HEAVYWEIGHT HINGES. ONE HINGE SHALL BE PROVIDED FOR EACH 30”
OF DOOR HEIGHT.
5. LOCKS SHALL MATCH BUILDING STANDARD, WHERE APPLICABLE. VERIFY LOCKING
HARDWARE OF ALL EXISTING DOORS TO MATCH WHERE APPLICABLE.
6. CLOSERS SHALL BE BY LCN. ALL CORRIDOR DOORS SHALL HAVE 4010/4110 MODEL
CLOSERS WITH INDICATED FINISH. INTERIOR DOORS SHALL HAVE 1461 MODEL CLOSERS
WITH INDICATED FINISH. CONCEALED CLOSERS TO BE 3130 SERIES, WHERE OCCUR.
7. FLUSH BOLTS AND COORDINATORS SHALL BE BY IVES OR DOOR CONTROLS
INTERNATIONAL.
8. FLAT GOODS SHALL BE BY IVES, HAGER, OR ROCKWOOD.
9. SMOKE GASKET, THRESHOLDS, ASTRAGALS, DOOR BOTTOMS, ETC. SHALL BE BY PEMKO
OR NATIONAL GUARD PRODUCTS
10. PROVIDE FLOOR STOP AT ALL LOCATIONS WHERE DOOR WILL STRIKE PARTITION. PROVIDE
RISERS AND DOOR MATES AS NECESSARY.
11. RIGHT HAND LEAF OF PAIR DOORS TO BE ACTIVE, UON.
12. MOUNT CLOSER ON PULL SIDE OF DOOR, UON.
13. FIELD MEASURE FLOOR TO CEILING DOORS FOR PROPER FIT.
14. CONNECT ELECTROMAGNETIC HOLDERS TO BUILDING LIFE SAFETY SYSTEM.
15. PROTECT PREFINISHED SURFACES AND REPAIR ANY DAMAGE.
16. SUBMIT DOOR AND HARDWARE SCHEDULE WITH PROPOSED ITEMS TO ARCHITECT FOR
REVIEW BEFORE ORDERING ITEMS.
17. ALL HDWR TO HAVE FINISH: 626 SATIN CHROME, UON. VERIFY IN FIELD TO MATCH EXISTING.
18. PROVIDE APPROPRIATE SMOKE SEALS AND ‘S’ LABEL ASSEMBLIES AT ALL RATED DOORS.
19. COORDINATE WITH SECURITY VENDOR ON ALL DOORS REQUIRING CARD READERS OR
OTHER EXITING / SECURITY DEVICES.
20. ALL RATED DOORS WITH GLASS TO HAVE CLEAR ‘FIRELITE’ GLASS WITH RATING TO MATCH
DOOR.
21. LEVER TYPE TO BE: SCHLAGE, SPARTA, UON. VERIFY IN FIELD TO MATCH EXISTING.
22. ANY FIRE DOORS THAT ARE TO BE DEMOLISHED AND REPLACED TO REMAIN UNTIL (N)
DOORS ARE READY FOR INSTALLATION.
23. KEYING BY LANDLORD, UON.
24. PAINT EXISTING PAINT GRADE DOORS AND FRAMES TO MATCH ADJACENT PARTITION, UON.
25. PROVIDE A 10" SMOOTH SURFACE ON THE BOTTOM OF ALL ACCESSABLE DOORS, PER CBC
11B-404.2.10
26. EACH PANE OF SAFETY GLAZING INSTALLED IN HAZARDOUS LOCATIONS SHALL BE
IDENTIFIED BY A MANUFACTURER'S DESIGNATION SPECIFYING WHO APPLIED THE
DESIGNATION, THE MANUFACTURER OR INSTALLER AND THE SAFETY GLAZING STANDARD.
THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE
PURPOSED OF SAFETY GLAZING IN: (CBC 2406)
A. FIXED OR OPERABLE PANELS ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED
EDGE OF THE GLAZING IS WITHIN 24 INCHES ARC OF EITHER VERTICAL EDGE OF THE
DOOR IN A CLOSED POSITION AND WHERE THE BOTTOM EXPOSED EDGE OF THE
GLAZING IS LESS THAN 60 INCHES ABOVE THE WALKING SURFACE.
B. SWINGING DOORS
C. IF APPLICABLE, GUARDS AND RAILINGS REGARDLESS OF AREA OR HEIGHT ABOVE A
WALKING SURFACE. INCLUDE COMPLETE INSTALLATION AND ANCHORAGE DETAILS
FROM THE MANUFACTURER OR STRUCTURAL ENGINEER. (CBC 2407)
D. DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS,
BATHTUBS, AND SHOWERS.
E. THE NOMINAL THICKNESS OF THE GLASS SHALL BE 1/4" INCHES.
27. CONTRACTOR TO VERIFY EXISTING LOCK CYLINDERS THROUGHOUT PROJECT TO
ACCOMMODATE NEW TENANT KEYING SYSTEM. TO BE REPLACED AS REQUIRED.
28. CONTRACTOR TO VERIFY EXISTING EXTERIOR DOOR EGRESS HARDWARE IS FUNCTIONAL.
TO BE REPLACED AS REQUIRED.
LE
V
E
L
A
R
E
A
MA
X
S
l
o
p
e
1
:
4
8
4'-0"
3'
-
8
"
PU
S
H
S
I
D
E
DOOR CLEARANCES
5'
-
0
"
PU
L
L
SI
D
E
4'
-
0
"
* REQD FIRE DOORS, MAX EFFORT = 15 LBS
* 1/2 " MAX. THRESHOLD. 1/4" = 1/2" MAX SLOPE =
* 10" KICK PLATE OR SMOOTH FULL WIDTH
DOOR
SECTION @ DOOR / THRESHOLD
THRESHOLD
SEC. 11B-404.2.5 CBC
2'-0" MIN. CLR. @ EXTERIOR
1'-6" MIN. CLR. @ INTERIOR
LC
MIN.
32"
CLR.
* MAX EFFORT FOR INTERIOR DOORS = 5 LBS
* MAX EFFORT FOR EXTERIOR DOOR = 5 LBS
* OPERABLE WITHOUT GRASPING
HARDWARE
PUSH SIDE
SEC. 11B-404.2.9 CBC
SEC. 11B-404.2.10 CBC
1
2
12"
PROVIDE THIS ADDITIONAL SPACE
WHEN BOTH A LATCH AND CLOSER
ARE PRESENT.
34
"
-
4
0
"
HA
R
D
W
A
R
E
HE
I
G
H
T
* 4" FOR SOLID GLASS DOORS 30 BEVEL ALL
SURFACES.
AUTOMATIC DOORS:WHEN AN AUTOMATIC DOOR OPERATOR IS UTILIZED TO OPERATE A PAIR
OF DOORS, AT LEAST ONE OF THE DOORS SHALL PROVIDE A CLEAR, UNOBSTRUCTED
OPENING WIDTH OF 32” WITH THE DOOR POSITIONED AT AN ANGLE OF 90 DEGREES FROM ITS
CLOSED POSITION.
FLOOR LEVEL AT DOORS:REGARDLESS OF THE OCCUPANT LOAD, THERE SHALL BE A FLOOR
OF LANDING ON EACH SIDE OF A DOOR.
THRESHOLDS:THE FLOOR OR LANDING SHALL NOT BE MORE THAN 1/2” LOWER THAN THE
THRESHOLD OF THE DOORWAY. CHANGE IN LEVEL BETWEEN 1/4” AND 1/2” SHALL BE BEVELED
WITH A SLOPE NO GREATER THAN 1 UNIT VERTICAL TO 2 UNITS HORIZONTAL. CHANGE IN
LEVEL GREATER THAN 1/2” SHALL BE ACCOMPLISHED BY MEANS OF A RAMP.
MANEUVERING CLEARANCES AT DOORS:MIN MANEUVERING CLEARANCES AT DOORS SHALL
BE AS SHOWN IN FIGURE 11B-404.2.4.1 AND 11B-404.2.4.1 (2016 CBC). THE FLOOR OR GROUND
AREA WITHIN THE REQUIRED CLEARANCES SHALL BE LEVEL AND CLEAR.
THE LEVEL AREA SHALL HAVE A LENGTH IN THE DIRECTION OF DOOR SWING OF AT LEAST
60” AND THE LENGTH OPPOSITE THE DIRECTION OF DOOR SWING OF 48” AS MEASURED AT
RIGHT ANGLES TO THE PLANE OF THE DOOR IN ITS CLOSED POSITION.
THE WIDTH OF THE LEVEL AREA ON THE SIDE TO WHICH THE DOOR SWINGS SHALL
EXTEND 24” PAST THE STRIKE EDGE OF THE DOOR FOR EXTERIOR DOORS AND 18” PAST THE
STRIKE EDGE FOR INTERIOR DOORS.
THE SPACE BETWEEN TWO CONSECUTIVE DOOR OPENINGS IN A VESTIBULE, SERVING
OTHER THAN A REQUIRED EXIT STAIRWAY SHALL PROVIDE A MINIMUM OF 48” OF CLEAR
SPACE FROM ANY DOOR OPENING INTO SUCH VESTIBULE WHEN THE DOOR IS POSITIONED AT
AND ANGLE OF 90 DEGREES FROM ITS CLOSED POSITION. DOORS IN A SERIES SHALL SWING
EITHER IN THE SAME DIRECTION OR AWAY FROM THE SPACE BETWEEN THE DOORS.
CLOSER-EFFORT TO OPERATE DOORS:MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT
EXCEED 5 LBS. FOR EXTERIOR AND INTERIOR DOORS, SUCH PULL OR PUSH EFFORT BEING
APPLIED AT RIGHT ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF SLIDING OR
FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE
UTILIZED TO MEET THE ABOVE STANDARDS. WHEN FIRE DOORS ARE REQUIRED, THE
MAXIMUM EFFORT TO OPERATE THE DOOR MAY BE INCREASED TO THE MINIMUM ALLOWABLE
BY THE APPROPRIATE ADMINISTRATIVE AUTHORITY, NOT TO EXCEED 15 LBS.
DOOR CLOSER:IF THE DOOR HAS A CLOSER, THEN THE SWEEP PERIOD OF THE CLOSER
SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 70 DEGREES, THE DOOR WILL
TAKE AT LEAST 3 SECONDS TO MOVE TO A POINT 3” FROM THE LATCH, MEASURED TO THE
LANDING EDGE OF THE DOOR. THE MINIMUM ALLOWABLE DISTANCE FROM THE FINISHED
FLOOR TO THE BOTTOM OF THE DOOR CLOSER WILL BE 78 INCHES. THE DOOR WILL TAKE AT
LEAST 5 SECONDS TO MOVE FROM A POINT 90 DEGREES OPEN POSITION TO THE 12 DEGREE
POSITION
DOOR HARDWARE: HAND-ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED
BETWEEN 34” AND 44” ABOVE THE FLOOR. LATCHING AND LOCKING DOORS THAT ARE HAND-
ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL SHALL BE OPERABLE WITH A SINGLE
EFFORT BY LEVER-TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS OR OTHER
HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP
THE OPENING HARDWARE. LOCKED EXIT DOORS SHALL OPERATE AS ABOVE IN EGRESS
DIRECTION.
RECESSED DOORS: WHERE THE PLANE OF THE DOORWAY IS OFFSET 8” OR MORE FROM ANY
OBSTRUCTION WITHIN 18” MEASURED LATERALLY ON THE LATCH SIDE, THE DOOR SHALL BE
PROVIDED WITH MANEUVERING CLEARANCE FOR FRONT APPROACH.
SMOOTH SURFACE:THE BOTTOM 10” OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING SHALL
HAVE A SMOOTH, UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A
WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. WHERE
NARROW FRAME DOORS ARE USED, A 10” HIGH SMOOTH PANEL SHALL BE INSTALLED ON THE
PUSH SIDE OF THE DOOR, WHICH WILL ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR
FOOTREST WITHOUT CREATING A TRAP OR A HAZARDOUS CONDITION.
EXIT DOORS:ALL EXIT DOORS TO SWING IN THE DIRECTION OF TRAVEL AND BE OPERABLE
WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE.
1
SEE SCHED
SE
E
S
C
H
E
D
U
L
E
SIM
SIM
1
A7.11
2
A7.11
2
SEE SCHED
CE
I
L
I
N
G
W
H
E
R
E
O
C
C
U
R
S
SE
E
S
C
H
E
D
U
L
E
3
SEE SCHED
SIM
SIM
1
A7.11
2
A7.11
SE
E
S
C
H
E
D
U
L
E
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
0
0
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
A6.00
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
DOOR SCHEDULE &
SPECIFICATIONS
COLLECTORS
-
DOOR NOTES ACCESSIBILITY REQUIREMENTS
DOOR FINISH TYPES
CL: CLEAR VENEER
PT: PAINTED PT-X, SEE FINISH SCHEDULE
GL: CLEAR TEMPERED GLASS
FM: FILM PATTERN (SEE ELEVATIONS)
ST: STAINED TO MATCH ARCHITECT'S SAMPLE
ME: MATCH EXISTING
RE: REFINISHED
DOOR CONSTRUCTION TYPES
WD: SOLID CORE, WOOD VENEER
WD/GL: SOLID CORE, WOOD VENEER W/ TEMPERED GLASS LITE
PG: SOLID CORE, PAINT GRADE
PG/GL: SOLID CORE, PAINT GRADE W/ TEMPERED GLASS LITE
GL: TEMPERED GLAZING
HM: HOLLOW METAL
MTL/GL: METAL W/ TEMPERED GLASS LITE
ME: MATCH EXISTING
FRAME FINISH TYPES
CL: CLEAR ANODIZED FACTORY FINISH
BK: BLACK ANODIZED FACTORY FINISH
PT: PAINTED - FACTORY FINISH TO MATCH ARCH SAMPLE PT-X
ST: STAINED TO MATCH ARCHITECT'S SAMPLE
ME: MATCH EXISTING
FRAME CONSTRUCTION TYPES
AL: ALUMINUM
HM: HOLLOW METAL, FULLY WELDED
WD: WOOD
ME: MATCH EXISTING
DOOR SCHEDULE
DOOR HARDWARE SCHEDULE
DO
O
R
N
U
M
EL
E
V
.
T
Y
P
E
HD
W
R
G
R
O
U
P
ROOM DOOR FRAME
FI
R
E
R
A
T
I
N
G
PA
N
I
C
H
D
W
R
CTRL'D
ACCESS S.R.D. COMMENTSNUM NAME
SIZE
CONST.
TYPE
FINISH
TYPE
CONST.
TYPE
FINISH
TYPEWIDTH HEIGHT THICK
200(E) (E) 2 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR Y Y PROVIDE CARD READER / PANIC BAR
201(E) (E) 1 201 (E) ELEC 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - Y PROVIDE CARD READER
202(E) (E) (E) 202 CONF 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
203(E) (E) (E) 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
204(E) (E) (E) 204 OFFICE 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
205(E) (E) (E) 205 OFFICE 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
206(E) (E) (E) 206 STORAGE 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
207(E) (E) (E) 207 STORAGE 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
208(E) (E) (E) 208 STORAGE 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
209(E) (E) (E) 209 STORAGE 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
210(E) (E) (E) 210 CONF 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
211(E) (E) 1 211 MDF 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - Y PROVIDE CARD READER
212(E) (E) (E) 212 OFFICE 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - -
213 2 3 213 OFFICE GROWTH 4' - 0" 8' - 0" 1 1/2" MTL MTL - - NR Y Y PROVIDE 'MUSHROOM BUTTON' EMERGENCY RELEASE ON ROOM INTERIOR. ACCESS CONTROLLED SWING DOOR WITH 4'-0" CLR
OPENING. REQUIRED CARD READER
214(E) (E) 1 214 (E) ELEC 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR - Y PROVIDE CARD READER
215(E) (E) 2 3' - 0" 7' - 10 1/2" 1 1/2" (E) (E) (E) (E) NR Y Y PROVIDE CARD READER / PANIC BAR
216 1 4 6' - 0" 7' - 10 1/2" 1 1/2" HM ME PT PT NR Y Y PROVIDE CARD READER / PANIC BAR
217 3 2 213 OFFICE GROWTH 3' - 0" 7' - 10 1/2" 1 1/2" HM ME PT PT NR Y Y PROVIDE CARD READER / PANIC BAR
EL02 1 1 8' - 0" 7' - 10 1/2" 1 1/2" HM PT HM PT 45
MIN
- CR
DOOR SCHEDULE NOTES:
• (E) DOORS TO REMAIN IN CURRENT LOCATION AND RECEIVE NEW HARDWARE OR SECURITY UPGRADES PER SCHEDULE.
• ALL OTHER SCHEDULED DOORS, FRAMES AND HARDWARE TO BE NEW.
• SEE SECURITY DRAWINGS FOR ADDITIONAL INFORMATION.
DOOR ELEVATION LEGEND
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
0
4
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
23008.00
A6.01
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
SPECIFICATIONS
COLLECTORS
-
SPECIFICATIONS - EQUIPMENT
TYPE DESCRIPTION LOCATION MANUFACTURER MODEL NUMBER SPECIALTY POWER COMPRESSED AIR
RESPONSIBI
LITY NOTES
EQ122 ZEBRA PRINTER OPEN OFFICE ZEBRA BY OWNER 110v, 4A N/A O.F.O.I
EQ202 TV MONITOR VARIES, SEE PLAN S.V.D. S.V.D. N/A N/A O.F.O.I
SPECIFICATIONS - LIGHTING FIXTURES
TYPE DESCRIPTION MANUFACTURER MODEL NUMBER MOUNTING HEIGHT NOTES
(E)F1A 2X4 TROFFER EXISTING EXISTING
(E)F20 EXISTING EXIT SIGN EXISTING EXISTING
F1A 2X4 TROFFER NEW NEW
F2 <varies> <varies> <varies>
SCHEDULE - INTERIOR FINISH
TYPE DESCRIPTION MANUFACTURER PRODUCT COLOR FINISH SIZE NOTES
SDT-01 RESILIENT FLOOR ARMSTRONG AMALGAM (4113V) 51915 CHARCOAL 20 INCH X 20 INCH X 5MM THICK GLUE DOWN
ACT-01 ACOUSTIC CEILING TILE ARMSTRONG TO MATCH EXISTING TO MATCH EXISTING TO MATCH EXISTING AS INCICATED ON RCP
TS-03 FLOOR TRANSITION STRIP JOHNSONITE SLT-XX-A SERIES VCT TO CARPET
CPT-01 CARPET TILE BENTLEY MILL REDUX 402270 - 18X36 TILE, STACKED INSTALLATION
RB-01 RESILIENT WALLBASE TARKETT 4" HIGH SILVER GREY 55 - 4" HIGH PROVIDE STRAIGHT AT CARPET AND COVE AT HARD FLOORING SURFACES
PT-01 PAINT - GENERAL BENJAMIN MOORE ATRIUM WHITE OC-145 EGGSHELL
SPECIFICATIONS - PLUMBING FIXTURE
TYPE DESCRIPTION MANUFACTURER MODEL NUMBER MATERIAL/ FINISH COMMENTS
BF-1 BOTTLE FILLER ELKAY
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
MIN 18 GA STUDS AT WALL
MOUNTED ARCHITECTURAL
MILLWORK / ATTACHED. SEE
DETAIL 6 OR 10/A6.01.
LARGE ABOVE
CEILING
OPENING
LARGE BELOW
CEILING
OPENING
BELOW CEILING
OPENING
ABOVE
CEILING
OPENING
DOOR
OPENING DOUBLE DOOR
OPENING
CEILING
LINE
TOP TRACK
BOTTOM TRACK TYP
FLOOR
LINE
UNDERSIDE OF CONCRETE SLAB
.
SEE SHEET NOTE 6
10' - 0" MAX4'-6" MAX
DOUBLE STUDS
DOUBLE
STUDS
4' - 6" MAX 4' - 6" MAX 10' - 0" MAX 10' - 0" MAX
LARGE BELOW CEILING
OPENING
BELOW CEILING
OPENING
DOOR
OPENING DOUBLE DOOR
OPENING
BOTTOM TRACK TYP
10' - 0" MAX4' - 6" MAX
DOUBLE STUDS
(FULL HEIGHT)
DOUBLE
STUDS
(FULL HT)
4' - 6" MAX 10' - 0" MAX
PROVIDE DIAGONAL BRACING AT TOP OF TRACK AT MAX
48" OC BETWEEN FULL HT STUDS
DOUBLE STUDS
(FULL HEIGHT)
22
A7.00
10
A7.00
14
A7.00
23
A7.00
10
A7.00
14
A7.00
15
A7.00
11
A7.00
23
A7.00
23
A7.00
14
A7.00
10
A7.00
10
A7.00
14
A7.00
14
A7.0023
A7.00
23
A7.00
11
A7.00
15
A7.00
22
A7.00
16 GA MIN. MTL TRACK
(2) #10 SCREWS, TOP / BTM @ 4" O.C.
DOUBLE 16 MIN. GA MTL STUDS.
CLIP ANGLE - 18 GA x 1 1/2" x 1 1/2" x
3" for 3 5/8" STUDS AND 5" FOR 6"
STUDS AT EACH SIDE.
(2) #10 SCREWS AT 12" OC TOP / BTM
AT EACH SIDE.
TOP TRACK
11
'
-
0
"
M
A
X
20 GA MIN MTL TRACK
CLIP ANGLE - 18 GA x 1
1/2" x 1 1/2" x 3" FOR 3
5/8" STUDS AND 5" for 6"
STUDS AT EACH SIDE.
2'
-
0
"
M
A
X
.
TOP TRACK
CLIP ANGLE - 18 GA x 1 1/2" x 1 1/2" x 3" FOR 3
5/8" STUDS AND 5" FOR 6" STUDS AT EACH
SIDE.
MTL SILL TRACK BELOW.
(2) #10 SCREWS AT EACH SIDE.
18 GA MTL TRACK AT FLOOR.
DOUBLE18 GA MTL STUDS AT BOTH JAMBS
AT OPENINGS LESS THEN10'-0" WIDE.
MTL TRACK (ES). MATCH GA WITH JAMB STUDS.
NOTE: IF 3 5/8" STUD WALL; USE (3) 16GA STUDS @ JAMB, TYP.
DOUBLE 20 GA MTL STUDS AT BOTH
JAMBS AT OPENINGS LESS THEN 4'-6"
WIDE.
MTL TRACK (ES). MATCH GA WITH JAMB STUDS.
MTL TRACK AT FLOOR.
METAL STUDS SIZE AND SPACING
PER PLAN AND WALL SECTIONS
INTERIOR WALLS
FASTENERS AT 16" OC STAGGERED
WITH (2) EACH MAX. 4" FROM DOOR
AND WINDOW JAMB OR TRACK ENDS.
TYP. USE HILTI XDNI w/1 1/2" EMBED
PROVIDE #12x2" LONG SMS AT
RAISED ACCESS FLOOR OR .177"ø
HILTI XDNI 1 1/2" EMBED TO
CONCRETE SLAB.
TRACK
#10 SCREW AT EACH FLANGE TYP.
>10"
STUD PUNCH-OUT
TOP TRACK
5 EQSPACES12"
1"
1"
(6) #10 SCREWS EACH SIDE
TOP TRACK
PERPENDICULA
R TO METAL
DECK
5/
8
"
5/
8
"
10# PAN HEAD SELF TAPPING
SCREWS, (2) PER FLUTE
ATTACH TO (2) DECK FLUTES 6" X
16 GA PLATE WITH MIN. (4) #10 SMS
METAL DECK
HOLD STUD 1/2" MIN BELOW TRACK
FILL VOIDS BETWEEN MTL DECK
FLUTES AND PLATE W/ INSULATION
AT FIRE RATED PARTITIONS
CONT. DEFLECTION TRACK
(SLOTTED TRACK SYSTEM)
(2) 10# SMS AT EACH FLUTE
CONT. 20 GA. X 1 1/4" DEEP RELIEF
CHANNEL - ANCHOR TO STEEL PLATE
W/ #8 PAN HEAD SELF TAPPING SCREWS
AT 24" O.C. AND 6" FROM ENDS.
METAL DECK
HOLD STUD 1/2" MIN BELOW TRACK
FILL VOIDS BETWEEN MTL DECK FLUTES
AND PLATE W/ INSULATION AT FIRE
RATED PARTITIONS
CONT. DEFLECTION TRACK
(SLOTTED TRACK SYSTEM)
TOP TRACK
PARALLEL TO
METAL DECK
#10 SCREW AT EACH FLANGE
TYP.
#10 SCREW AT EACH FLANGE TYP.
HITLI XDNI PDF w/1 1/2"
EMBED @ 16" O.C. TYP.
STRUCTURAL SLAB
CONT. TRACK 2 1/2" FLANGE SLOTTED
SLIP TRACK W/ #10 SMS EA
FLANGE EA SIDE ALLOW
FOR VERTICAL MOVEMENT
1/
2
"
M
I
N
.
1"
M
A
X
.
16 GA MTL. TRACK
2'
-
0
"
-
8
'
-
0
"
M
A
X
.
TOP TRACK
WALL STUD 3 5/8" OR 6"
(1) #10 SMS EA. SIDE ,
EA. STUD
16 GA HEADER STUD w/(1)
#10 SMS EA. SIDE @ 16"O.C.
PROVIDE MTL TRACK IF FLAT
TOP NEEDED FOR DRYWALL
ATTACHMENT.
OPENING HEAD HT.
2 ROWS #10 SMS @ 4" O.C.
20 GA MTL SILL TRACK
(1) #10 SMS MIN. @ EA. SIDE,
@EA. STUD
OPENING
SILL HT.
OP
E
N
I
N
G
WALL STUD
3-5/8" OR 6"
18 GA MTL. TRACK w/ (1) #10
SMS MIN. @ EA SIDE @ EA.
STUD
18 GA SILL STUD w/
(2) ROWS #10 SMS @ 4" O.C.
OPENING
SILL HT.
MTL. TRACK IF NEEDED FOR
DRYWALL ATTACHMENT
OP
E
N
I
N
G
WALL STUD 3-5/8" OR 6"
NOTE:
WHEN WORK OCCURS
ADJACENT TO AN HABITATED
SPACE, REPLACE PDP AT THE
TOP & BOTTOM TRACKS WIH
A 3/16" SHANK X 1" HILTI KWIK
CON II CONCRETE SCREW
(ICC ER-5259).
#8 SMS @ EA FLANGE TYP.
TRACK TO MATCH
GA OF STUD
0.145" SHANK PDP @ 24" O.C.
TYP. AT BOTTOM TRACK TO
STRUCTURE EXCEPT AS
NOTED OTHERWISE AT 1/--AT
CONDITION WITH TRACK
BACKING AND FLOOR
CABINETS WHEN NOTED.
10
"
M
A
X
1"
STUD PUNCH-
OUT. DO NO
LOCATE
PUNCH-OUT
W/IN 10" OF
END OF STUD.
#8 WAFERHEAD
SCREW TYP.
MIN.
3"
1"
-
1
1
/
4
"
5/8" DEFLECTION GAP
DO NOT ATTACH FINISH
TO SLIP TRACK
USE (2)- .145" SHANK PDP
@ 6" STUDS AND
GREATER @ 24" OC.
USE 1- .145" SHANK PDP
@24" O.C. FOR STUDS
LESS THAN 6"
NOTE:
FOR ADDITIONAL FRAMING
REQ'S AT THE TOP TRACK
SEE SPECIAL
ATTACHMENT DETAILS ON
THIS SHEET AND
PARTITION REQ'S FOR
SOUND AND FIRE
PROTECTION.
2-1/2"-8"
VARIES
1/2"
1/2
"
1 1/2"
18 GA TOP TRACK BY
SLIPTRACK (ICC
ESR-1042). THIS TRACK
TYPE MAY NOT BE USED
FOR EXTERIOR
APPLICATIONS UNLESS
SPECIFICALLY DETAILED
GAUGE
STUD
SIZE l (in )s (in )4 3
STUD PROPERTIES
LAYERS OF GYP. BD. (NOTE 6)
20 GA
18 GA
25 GA
2 LAYERS
3 5/8"
3 5/8"
3 5/8"
3 5/8"
0.616
0.756
0.215
0.479
0.334
0.400
0.09
0.254
19' - 1"
20' - 5"
14' - 4"
17' - 6"
1. HEIGHT INDICATES MAX. STUD SPAN BETWEEN FLOOR TO STRUCTURE ABOVE OR TO BRACED
CEILING
2. WALL DEFLECTION LIMIT = L/240, IF BRITTLE FINISHES ARE TO BE PROPOSED CHECK HIGHER
DEFLECTION LIMITS AND/OR PRODUCT MFR. CRITERIA.
3. STUDS DO NOT CONSIDER CASEWORK OR EQUIPMENT
4. ALL LOCATION ON BUILDING FLOOR RELATIVE TO TOTAL NUMBER OF FLOORS IN BUILDING.
5. STUDS Fy = 33ksi U.N.O., FLANGE = 1 3/8" EXCEPT FLANGE = 1 1/4" FOR 25 GA.
6. OUT OF PLANE FORCES BASED ON ASCE 7, CHAPTER 13 SEISMIC FORCES. WALL HEIGHT PROVIDED
IN TABLE SATIFIES SSMA RECOMMENDED WALL HEIGHT DUE TO DEFLECTION CRITERIA.
7. WEIGHTS INCLUDE LAYERS OF GYP. BD. + INSULATION:
2 LAYERS = 6.8PSF + WEIGHT OF STUD
3 LAYERS = 9.3PSF + WEIGHT OF STUD
4 LAYERS = 11.8PSF + WEIGHT OF STUD
16 GA(50KSI)
MAX. STUD HEIGHT BASED ON OUT-OF-PLANE FORCES
WALL LOCATION (NOTE 4)
LOWER 1/3 MIDDLE 1/3 UPPER 1/3
3 LAYERS4 LAYERS2 LAYERS 4 LAYERS2 LAYERS 4 LAYERS3 LAYERS 3 LAYERS
19' - 1"
20' - 5"
14' - 4"
17' - 6"
19' - 1"
20' - 5"
14' - 4"
17' - 6"
19' - 1"
20' - 5"
14' - 4"
17' - 6"
19' - 1"
20' - 5"
14' - 4"
17' - 6"
12' - 5"
14' - 3"
19' - 1"
20' - 5"
14' - 4"
17' - 6"
12' - 5" 12' - 5"
20 GA
18 GA
25 GA 6"
2.042
2.518
0.778
1.582
0.67
0.809
0.259
0.51
28' - 4"
30' - 4"
19' - 9"
16 GA(50KSI)
19' - 9" 19' - 9"
26' - 0"6"
6"
6"
26' - 0"26' - 0"
28' - 4" 28' - 4"
30' - 4" 30' - 4"
28' - 4"
30' - 4"
19' - 9" 19' - 9"
26' - 0"26' - 0"
28' - 4"
30' - 4"
28' - 4"
30' - 4"
19' - 9"
26' - 0"
NOTES
13' - 10"
14' - 5" 14' - 5"
13' - 10"
12' - 11"
12' - 5"
14' - 0"
19' - 5"
22' - 1"
23' - 6"
16' - 11"
20' - 1"
21' - 7"
14' - 0"
19' - 5"
22' - 1"
23' - 6"
14' - 5"
13' - 10"
12' - 11"
14' - 0"
UPPER
1/3H
MIDDLE
1/3H
LOWER
1/3H
H
FLR
FLR
FLR
SAMPLE BUILDING SECTION
FLR
FLR
FLR
FOR ADDITIONAL
FRAMING REQ'S AT TOP
TRACK SEE
ATTACHMENT DETAILS
ON THIS SHEET.
MIN.
3"
1"
1"
M
A
X
1/
2
"
M
I
N
-1/2" MIN. BETWEEN GYP
BOARD FASTENER AND
LEG OF TOP TRACK
FOR ALTERNATE SLIP
TRACK DETAIL AT INT.
PARTITIONS SEE
9/A7.00
16 GA TOP TRACK W/ 2"
FLANGE
GYP BOARD FASTENER
TO ATTACH TO LOWER
TRACK ONLY.
LOWER TRACK GA TO
MATCH STUD GA.
LOWER TRACK FLANGE
SHALL BE 2-1/2"
USE (2)- .145" SHANK
PDP @ 6" STUDS AND
GREATER @ 24" OC.
USE 1- .145" SHANK
PDP @24" O.C. FOR
STUDS LESS THAN 6"
1. SEE ADDITIONAL DETAILS AND CONSTRUCTION NOTES FOR ADDITIONAL
METAL STUD REQUIREMENTS AT INTERIOR PARTITIONS.
2. ALL METAL STUDS AND JOISTS SHOWN ARE SSMA OR EQUIVALENT (ICC-ESR
3064P).
3. ALL TRACK SHALL MATCH GAUGE OF TYPICAL METAL STUD NOTED IN
SCHEDULE UON.
4. ALL STUD SPACING IS 16” OC UON.
5. ALL STUDS SHALL BE “C” STUDS WITH 1 3/8” FLANGE UON.
6. USE THREE (3) STUDS MIN AT THE INTERSECTION OF ALL EXTERIOR AND / OR
INTERIOR WALLS.
7. ENDS OF STUDS SHOULD SEAT FIRMLY IN THE RUNNER TRACK WHICH MUST
HAVE FULL BEARING ON THE STRUCTURE.
8. ATTACH EACH RUNNER TRACK LEG TO EACH STUD FLANGE WITH ONE (1) #
10-16 SCREW, 5/8” LONG.
9. NO NOTCHING OR COPING OF STUDS IS ALLOWED UNLESS SPECIFICALLY
DETAILED.
10. ALL BRACING SHALL BE INSTALLED AT THE TIME THE WALL IS ERECTED.
FAILURE TO INSTALL BRACING AT THIS TIME MAY COMPROMISE THE
STRUCTURAL INTEGRITY.
11. USE #10-16, 5/8” OR #8-18, 5/8” LONG, LOW PROFILE PAN HEAD SHEET METAL
SCREWS (SMS) FOR ALL STEEL TO STEEL CONNECTIONS EXCEPT AS NOTED
ON PLANS AND DETAILS.
12. A 3/4” MIN CLEARANCE MUST BE MAINTAINED FROM ALL EDGES OF THE
STEEL MEMEBERS IN LOCATING SCREWS. A 3/4” MIN OC SPACING MUST BE
MAINTAINED BETWEEN ADJACENT SCREWS.
13. ALL SCREW RECOMMENDATIONS ARE BASED ON WHICH OUTLINES THE
PROPOSED AISI SPECIFICATION PROVISIONS FOR SCREW CONNECTIONS,
AND ALLOWABLE SCREW SHEAR STRENGTH VALUES PUBLISHED BY
BUILDEX, COMPASS, AND GRABBER.
14. FOR ATTACHMENT OF 3/8” TO 3/4” PLYWOOD TO STEEL STUDS AND JOISTS,
USE 1-15/16” #10-16 BUGLE HEAD PILOT POINT SCREWS.
15. FOR ATTACHMENT OF SINGLE-LAYER ½” OR 5/8” GYP OR SHEATHING TO
STEEL STUDS AND JOISTS, USE #10-16 SCREWS, 1” LONG BUGLE HEAD
SCREWS.
16. ALL CONNECTIONS SHALL BE COMPLETE AS PER THE PLANS AND
SPECIFICATIONS AT THE TIME OF INSTALLATION. FAILURE TO PROMPTLY
COMPLETE CONNECTIONS MAY COMPROMISE THE STRUCTURAL INTEGRITY.
17. SPLICING OF RUNNER TRACK TO BE ACCOMPLISHED BY SCREW
ATTACHMENT OF A STUDY SECTION BETWEEN VERTICAL STUDS TO THE
RUNNER TRACK USING #10-16, 5/8” LONG LOW PROFILE SCREWS.
18. SEE 1998 CBS TABLE 25A-G, 25A-H, FOR ATTACHMENT OF SINGLE AND
DOUBLE PLY GYPSUM SHEATHING TO METAL STUDS.
19. FOR FUTURE PARTITION WALLS, CONTRACTOR SHALL SUPPORT (E) GYP
CEILING.
20. Fy = 33ksi,U.N.O
3/8" = 1'-0"4FRAMING ELEVATION
1/4" = 1'-0"14DBL DR/LARGE OPENING HEAD
1/4" = 1'-0"10DOOR OPENING HEADER
1/4" = 1'-0"23LARGE OPENING BOX JAMB
1/4" = 1'-0"22DR OPENING BOX JAMB STUDS
1/4" = 1'-0"19TYPICAL STUD CONNECTION
1/4" = 1'-0"17TYP TOP TRACK SPLICE
3" = 1'-0"21BRACING PER UL 2079 HW-D-0418
1" = 1'-0"13METAL STUD - TYP NON BEARING WALL BELOW STRUCTURAL SLAB
1/4" = 1'-0"18DR. OPENING HDR. W/ 2' - 8' HEAD WALL
1/4" = 1'-0"15WINDOW SILL OPENING <4'-6"
1/4" = 1'-0"11WINDOW SILL OPENING >4'-6"
3" = 1'-0"6BOTTOM TRACK CONNECTION
3" = 1'-0"9TOP (SLIP) TRACK CONNECTION
12" = 1'-0"3STUD HEIGHT CHART
3" = 1'-0"5TOP TRACK CONNECTION N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
0
7
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
A7.00
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
TYP. INTERIOR FRAMING
DETAILS
COLLECTORS
-
2SPECIFIC NOTES FOR MTL STUD WALLS
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
EXISTING WINDOW FRAME.
CONTINOUS BLACK
NEOPRENE STRIP 1/2"
COMPRESSED TO 1/4"
LINE OF SILL, WHERE OCCURS.
SCHEDULED PARTITION
METAL STUD AGAINST SILL.
FIRE TREATED WOOD BLOCKING
ON TOP OF SILL, WHERE OCCURS
USG 200-A METAL TRIM TAPE,
OR EQUAL
CLOSED CELL NEOPRENE TAPE
INTERIOR
EXTERIOR
EXISTING EXTERIOR WINDOW.
NOTE: FLEXIBLE FIRE CAULKING REQUIRED AT ALL JOINTS AT
SCHEDULED RATED PARTITOINS. ACOUSTICAL SEALANT REQUIRED
WHERE GYP MEETS WALL BELOW SILL AT ALL WALLS WITH
ACOUSTICAL BATTING.
ACOUSTICAL BATTING
WHERE OCCURS.
WALL HUNG ITEM OR CABINET
(MAX. LOAD TO BRACING PLATE =
20 LBS. PER STUD)
EXTEND BACKING ONE
STUD BAY BEYOND
EDGE OF CABINET OR
EQUIP.
NOTES:
1. LENGTH, HEIGHT, AND LOCATION TO SUIT ITEMS BEING FASTENED. SEE
ANCHORAGE DETAIL OF SPECIFIC ITEMS FOR ADDITIONAL INFORMATION.
2. ATTACH TO MIN (3) STUDS.
3. USE MIN #12 SELF TAPPING SCREWS WHEN ATTACHING ITEMS.
4. USE DOUBLE STUDS WHEN STUD IS SUPPORTING MORE THE (2) BACKING
PLATES OR AS CALLED OUT ON PLAN PER SPECIFIC ITEMS.
(3) #10 SHEET METAL
SCREWS TYP @ EA. STUD
NOTCH BACKING TRACK FLANGE AT
STUDS TYP. DO NOT CUT FLANGES
BETWEEN SUPPORTING STUDS.
PARTITION WALL STUD @
16" O.C. MAX. SEE A6.10
FOR SCHEDULE
6" X 16" GA.
PLATE. ATTACH
TO MIN. 3 STUDS
SPLICE, (3) #10 @
EA. END OF STRIP
@ EA. STUD
9
3 5/8
6
STUD SIZE MAX. WALL HT
Hw (ft)
MIN. GAUGE OF STUD
LOADING SCENARIO
12
16
9
12
16
20
18
18
16
18
18
18
18
18
18
18
A A+B C
SEE NOTE 4
SEE NOTE 4SEE NOTE 4SEE NOTE 4
1820
18
1. STUDS ARE SPACED 16" O.C. TYP.
2. IF MILLWORK IS ON BOTH SIDES OF THE WALL, PROVIDE TWICE THE QUANTITY OF STUDS AND TOP/BOTTOM ANCHORAGE
3. FOR FULL HT. WALLS, IF GYP. BD. IS NOT INSTALLED ON BOTH SIDES OF PARTITION WALLS, LATERAL BRACING IS REQUIRED @ 48" O.C.
4. NO MIN. GAUGE IS AVAILABLE FOR 3 5/8" STUDS. 6" MIN. IS REQUIRED, SEE TABLE FOR MIN. GA.
NOTES:
LOADING:A = OVERHEAD GROSS WEIGHT OF CABINET AND CONTENTS = 37plf
a1+a2 = WHERE CABINETS ON EACH SIDE OF PARTITION, GROSS WEIGHT OF CABINET AND CONTENTS = A
B = BASE CABINET GROSS WEIGHT OF CABINET AND CONTENTS = 77plf
A+B = SUPPORTING OVERHEAD AND/OR BASE CABINET, GROSS WEIGHT = 114plf
C = FULL HT. CABINET OR EQUIPMENT, GROSS WEIGHT OF CABINET AND CONTENTS = 285plf
Hw Hw Hw Hw
a1 a2A A
B
C
12-18" MAX 12-18" MAX 12-18" MAX 12-18" MAX
24-36" MAX
CONDITION 1 - FULL HEIGHT PARTITION
CLG.
CONDITION 2 - PARTIAL HEIGHT OR OFFSET PARTITION
(SEE RULE 1-4 FOR SPACING REQUIREMENTS ABOVE)
CLG.
RULE 1 - BRACE WALL EVERY 4'-0"
4' - 0" 4' - 0"
BRACE, TYP.
WALL, TYP.
RULE 2 - OMIT BRACING AT PERPENDICULAR WALL
BRACE, TYP.
WALL, TYP.
4' - 0"4' - 0"
PERPENDICULA
R WALL
RULE 3 - BRACING AT OPENING OR WALL END WITHIN 2'-0"
2' - 0"2' - 0"
RULE 4 - OMIT BRACE WHERE PERPENDICULAR WALL IS WITHIN 2'-0"
2' - 0"
ELEVATION VIEW
PLAN VIEW
SIM TYP
SEE WALL SCHEDULE FOR STUD
SIZING.
3/4"1"3/4"3"
EQ EQ
3/
4
"
.
3/
4
"
.
EQ
1"
EQ
3"
2"4' - 0" MAX SPACING
10"
TYP.
FROM
END OF
WALL
LINE OF STUD FRAMING
1/2" X 3 1/2" EXPANSION
ANCHOR BOLT w/2"
EMBED
3" X 3" 1/4" STEEL TUBE
1/4" STEEL PLATE
SHOP WELDED TO
TUBE
LINE OF STUD
FRAMING
1"
1 1/2" 1 1/2"
#12 SMS AT 16" OC TYP OF (4) ROWS
MTL STUD TYP
SELF-DRILLING SCREWS FLAT HEAD
#10 AT 12" FIELD
#10 AT 6"EDGE1/2" CDX PLYWOOD
#10 AT 12" FIELD
#10 AT 12" EDGES1/2" GYPSUM BOARD
SHEATHING
SHEATHING FASTENER SCHEDULE
SHEATHING TYP
SHEATHING FASTENERS TYP.
TRACK
TRACK
TRACK PIN, TYP.
SHEATING FASTENERS
TRACK
OUTER SHEATHING
INNER SHEATHING
THIS STUD REQUIRED IF INNER
SHEATHING IS INSTALLED
TRACK
TRACK PIN, TYP.
#12 SMS@ 16" OC (1) row.
AT INTERSECTION
AT CORNER
WALL HUNG ITEM OR CABINET
(MAX. LOAD TO BRACING PLATE =
80 LBS. PER STUD)
EXTEND BACKING ONE
STUD BAY BEYOND
EDGE OF CABINET OR
EQUIP.
NOTES:
1. LENGTH, HEIGHT, AND LOCATION TO SUIT ITEMS BEING FASTENED. SEE
ANCHORAGE DETAIL OF SPECIFIC ITEMS FOR ADDITIONAL INFORMATION.
2. ATTACH TO MIN (3) STUDS.
3. USE MIN #12 SELF TAPPING SCREWS WHEN ATTACHING ITEMS.
4. USE DOUBLE STUDS WHEN STUD IS SUPPORTING MORE THE (2) BACKING
PLATES OR AS CALLED OUT ON PLAN PER SPECIFIC ITEMS.
(3) #10 SHEET METAL
SCREWS TYP @ EA. STUD
PARTITION WALL STUD @
16" O.C. MAX. SEE A6.10
FOR SCHEDULE
6" X 1/2" PLYWOOD.
ATTACH TO MIN. 3
STUDS. COORD
HEIGHT OF BACKING
W/ ARCHITECT
SPLICE, (3) #10 SMS
EA. END OF STRIP
@ EA. STUD
1'-0" MAX
(2) 3/8" DIA. EMBED 2"
FOR SINGLE STUD
(2) 5/8" DIA. EMBED 4"
FOR BACK-TO-BACK STUD
* INSTALL (1) BOLT FOR FLUTE
ON BACK SIDE OF BRACE
PARTITION
WALL BRACE
30 - 60
L3XL3X16GA
1'-2" MIN. LENGTH
EQ EQ
(2) 3/8" DIA. EMBED 2"
FOR SINGLE STUD
(2) 5/8" DIA. EMBED 4"
FOR BACK-TO-BACK STUD
30 - 60
1 1/2" TYP MIN
WEB OF BRACE
L3XL3X16GA
8" MIN.
LENGTH
PARTITION
WALL BRACE
PERPENDICULAR TO
DECKING
PARALLEL TO DECKING
NOTES: -STEEL DECK MIN. GAUGE = 20GA
-ASSUMED 3000 PSI LWC IN DECK
EQ EQ
(2) 3/8" DIA. EMBED 2"
FOR SINGLE STUD
(2) 5/8" DIA. EMBED 4"
FOR DOUBLE STUD
30 - 60
1-1/2"
TYP MINWEB OF BRACE
L3XL3X16GA
8"MIN. LENGTH
PARTITION
WALL BRACE
-
-4" MIN FOR 3/8"
DIA. ANCHOR
-6" MIN FOR 1/2"
DIA. ANCHOR
(2) #10 SMS @ 6" O.C.
WHERE THRU BOLT PENETRATES BTWN TOP &
BOTTOM FLUTE, EXTEND PLATE TO ENGAGE BOLT
OF ADJ. FLUTE
4" MIN.
HSS 3X3 @ 4'-0" O.C. MAX
HT. OF APPLIED LOAD =
5'-0"
1/2" THRU BOLT
1/4" THICK BASE
PLATE
HSS BETWEEN
FLUTES
HSS ALIGNS
@ FLUTE
MIN.
2"
2"
2
"
3/4" CLR MIN. 3/4" CLR MIN.
A A
A-A
A A
4"
6"
30 - 60
STRUCTURE ABOVE
SEE DTL 16/A-6.01 SCHEDULE FOR TOP
CONNECTION DETAIL, THIS SHEET
DIAGONAL BRACE: SEE SCHED.
WHERE BRACE <6'-0" PROVIDE
362S137-43. WHERE 6'-0"<BRACE<8'-0"
PROVIDE BACK TO BACK 362S137-54 -
FASTEN WITH #8 SMS @ 6" O.C.
STAGGERED. STOP ONE STUD 6" FROM
EA. END.
SEE DTL 16/A-6.01 SCHEDULE
FOR BOTTOM CONNECTION
L4X4X16 GAX0'-4" MIN.
4- #10 SMS TO TOP TRACK
-
3/4" MIN EDGE DIST +/-3/4" MIN
SPACING BTWN SCREWS, TYP
H-
W
A
L
L
H
-
B
R
A
C
E
6'-5"
MAX.
PARTIAL
WALL
HEIGHT
(H-WALL)
MAX.
(H-BRACE)
3'-5"
3'-1"
REFERENCE 8/A6.01 FOR 'A' + 'B' WALL CONDITION DESCRIPTION
NOTES:
1. WALL STUD IS 18 GA MIN.
2. APPLICABLE FOR 3-5/8" STUD AND 6" STUD, BRACE TO MATCH STUD SIZE
3. (2) 18 GA, BACK-TO-BACK BRACE SEE 7/-FOR SECTION DETAILS
9
12
16
MIN.
GAUGE
18
18
SEE NT. 3
MAX.
SPACIN
G OF
BRACE
5'-4"
5'-4"
6'-0"
SMS
CONNECTIONS
AT BRACE
ENDS
BOTTOM TOP
(6) #10
(6) #10
(8) #10
(4) #10
(4) #10
(8) #10
WALL
CONDITION OR
ACOUSTICAL
WEIGHT
LIMITATIONS
A OR MAX 4
LAYERS OF GYP.
A OR MAX 4
LAYERS OF GYP.
A+B OR MAX 3
LAYERS OF GYP.
WALL DIAGONAL BRACING
HSS 3X3 @ 3'-0" O.C. MAX HT. OF
APPLIED LOAD = 4'-0"
3/8" SIMPSON STRONG BOLT 2
X 2.25"
1/4" THICK BASE PLATEA A
A-A
MI
N
.
4"
2
1
/
4
"
(E) CONC
SLAB
6"
MIN
4 1/2"
6"
3/16"
4"
3
"
ALT LOCATION &
CONNECTION. IF HSS
ALIGNS W/ (E) JOIST
PROVIDE 2 ROWS OF WD
BLKG TO SANDWICH THE
HSS COL. AND CONTINUE
MIN (3) BAYS EA SIDE OF
TUBE
ALT LOCATION: CONNECT
HSS TO (E) JOISE WHERE
CANTILEVERED WALL IS
PERPENDICULAR TO JOIST
DIRECTION.
(N) 3X BLKG ALIGNED
W/ HSS COL. WHERE
CANTILEVERED WALL
PARALLEL TO JOIST
DIRECTION.
HSS 3X3 @ 4' O.C.
MAX HT. OF APPLIED
LOAD = 5'-0"
PENETRATE HSS
THRU (E)
SHEATHING TO
ATTACH TO BLKG
(N) 3X BLKG EA. SIDE
OF HSS FOR MIN (3)
BAYS
(E) FLR JOISTS
SIMPSON A35 CLIPS EA.
SIDE 3X W/ HSS TYP. EA.
END OF BLKG
(2) 3/4" THRU BOLT
4X6 BLOCKING (FLAT)
W/ SIMPSON A34 OR
EQ. @ EA. SIDE @ EA.
END
JOIST, TYP.
-(6) #14X3" WOOD SCREWS FOR
SINGLE STUD
-(8)#14X3" WOOD SCREWS FOR
SINGLE STUD
(5) 8d NAILS
BRACING PERP. TO JOIST ABOVE
4X6 BLOCKING EA. SIDE W/
SIMPSON A34 OR EQ. @ EA. SIDE
@ EA. END WITHIN 12" BRACE
4X12 BLOCKING (FLAT) W/
SIMPSON A34 OR EQ. @ EA.
SIDE @ EA. END
BRACE ALIGNS W/ JOIST, 10 DEG.
MAX. HORIZ. SKEW
BRACE DOES NOT ALIGN W/ JOIST
30-60°
30-60°
L 3X3X16GA 8" MIN.
L 3X3X16GA 8" MIN.
30-60°
JOIST BEYOND
6" = 1'-0"24WALL AT EXTERIOR MULLION
1" = 1'-0"6TYP BACKING FOR SM ITEMS (FLAT STRAP/PLATE)
1/4" = 1'-0"4METAL STUD - TYP. CABINETRY STUD SUPPORT REQS.
1/4" = 1'-0"3METAL STUD - PARTITION ATTACHMENT & BRACING DETAILS
12" = 1'-0"19WALL - PART HT - PLATE ATTACHMENT
1/4" = 1'-0"23METAL STUD WALL INTERSECT.
1" = 1'-0"10TYP BACKING FOR SM ITEMS (PLYWD)
1" = 1'-0"17METAL STUD - BRACING TO CONC DECK
1" = 1'-0"13METAL STUD - BRACING TO CONC SLAB
6" = 1'-0"7METAL STUD - BACK TO BACK STUDS
1" = 1'-0"18PARTIAL HEIGHT WALL @ METAL DECK
1" = 1'-0"15WALL - DIAGONAL BRACING
1/4" = 1'-0"16METAL STUD - DIAGONAL BRACING SCHEDULE
1" = 1'-0"14PARTIAL HEIGHT WALL @ CONC SLAB
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
1
0
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
A7.01
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
TYP. INTERIOR FRAMING
DETAILS
COLLECTORS
-
1" = 1'-0"22PARTIAL HEIGHT WALL @ WD FRAMING
1" = 1'-0"21METAL STUD - BRACING TO WD JOIST ABOVE
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
METAL STUDS. SEE SHEET A6.00 FOR
STUD GAUGE AND SPACING TABLE.
5/8" TYPE "X" GYPSUM BOARD
ACOUSTICAL SEALANT
SLAB /STRUCTURE
SCHEDULED CEILING, WHERE OCCURS
ACOUSTICAL SEALANT, WHERE SCHEDULED
TOP TRACK
FULL WIDTH UNFACED SOUND ATTENUATION
BLANKET FULL HEIGHT OF PARTITION, WHERE
SCHEDULED.
BOTTOM TRACK W01A
EXISTING WALL OR COLUMN
5/8" TYPE "X" GYPSUM BOARD
SLAB / STRUCTURE
SCHEDULED CEILING, WHERE OCCURS
SLAB / STRUCTURE
WIRE SECURITY MESH, S.R.D.
SECURE SIDE
W24
5/8" TYPE "X" GYPSUM BOARD
SLAB / STRUCTURE
SCHEDULED CEILING, WHERE OCCURS
EXISTING WALL
W10
SLAB / STRUCTURE
3" = 1'-0"1PARTITION - FULL HEIGHT N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
1
1
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
3" = 1'-0"23008.00
A7.02
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
PARTITION DETAILS
COLLECTORS
-
3" = 1'-0"2GYP BD W/ WIRE MESH LAMINATED O/ EXISTING - FULL HEIGHT
3" = 1'-0"3FURRING - FULL HEIGHT
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
SIDE WALL, WHERE
OCCURS
SCHEDULED DOOR
SCHEDULED FRAME, VERIFY THROAT
WIDTH WITH SCHEDULED WALL
4"
T
Y
P
SCHEDULED PARTITION
SCHEDULED CEILING,
WHERE OCCURS
SCHEDULED PARTITION
SCHEDULED FINISH
FLOOR
SCHEDULED
DOOR
SCHEDULED FRAME
SIDE WALL WHERE
OCCURS.
SCHEDULED DOOR
SCHEDULED FRAME VERIFY
THROAT WIDTH WITH
SCHEDULED WALL.
PARTITION AS
SCHEDULED.
ASTRAGAL AT RATED
CONDITIIONS
3" = 1'-0"2DR - ALUM FRM - JAMB
3" = 1'-0"1DR - ALUM FRM - HEAD / SILL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
1
1
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
3" = 1'-0"23008.00
A7.11
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
DOOR & GLAZING DETAILS
COLLECTORS
-
3" = 1'-0"3DR - ALUM FRM - JAMB @ DOUBLE ASTRAGAL
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1205 100% DD SET
2025-1218 PERMIT SET
2. WHERE CLG LOADS ARE LESS THAN 5 PSF AND NOT SUPPORTING
INTERIOR PARTITIONS, CLG BRACING SHALL BE PROVIDED BY (4) 12 GA
WIRES SECURED TO THE MAIN RUNNER WITHIN 2 INCHES OF THE CROSS
RUNNER INTERSECTION AND SPLAYED 90° FROM EACH OTHER AT AN ANGLE
NOT EXCEEDING 45° FROM THE PLANE OF THE CEILING. THESE HORIZONTAL
RESTRAINT POINTS SHALL BE PLACED 12’-0” OC IN BOTH DIRECTIONS AND
MAX 6’-0” FROM 1ST ROW OF BRACES TO ANY WALL. THE ATTACHMENT OF
THE RESTRAINT WIRES TO THE STRUCTURE ABV SHALL BE ADEQUATE FOR
LOAD IMPOSED. (ASTMC 635, ASTMC 636, ASTMC 1395, CISCA ACOUSTICAL
CEILINGS-USE AND PRACTICE, CISCA - CEILING SYSTEMS HANDBOOK.)
5. VERTICAL COMPRESSION STRUTS SHALL BE INSTALLED AT EA CROSS
RUNNER INTERSECTION WHERE LATERAL SUPPORT WIRES ARE INSTALLED.
WHERE THE DISTANCE BETWEEN THE CLG GRID AND THE SLAB ABV IS LESS
THAN 8’-0”, PROVIDE ONE 3 5/8” 25 GA METAL STUD WITH POWER DRIVEN PIN
#3330 ICBO #1147 TO SLAB ABV. SCREW WITH #6 DRYWALL SCREW TO CLG
MAIN “T” RUNNER AT SPLAYED CORNERS. IF DISTANCE BETWEEN CLG GRID
AND SLAB ABV IS 8’-0” OR GREATER, THEN USE THE SCHEDULE BELOW FOR
STUD SIZES:
3. LIGHT FIXTURES WEIGHING LESS THAN 56 LBS SHALL BE SUPPORTED
DIRECTLY BY A MIN OF (2) 12 GA HANGER WIRES (MAY BE SLACK) LOCATED
AT OPPOSITE CORNERS OF THE FIXTURE AND ATTACHED TO THE
STRUCTURE ABV. (ASTMC 635, ASTMC 636, ASTMC 1395, CISCA ACOUSTICAL
CEILINGS-USE AND PRACTICE, CISCA - CEILING SYSTEMS HANDBOOK)
4.DISCONTINUOUS ENDS OF CROSS RUNNERS AND MAIN RUNNERS SHALL BE
VERTICALLY SUPPORTED WITHIN 8” OF SUCH ENDS.
1. SUPPORT MAIN RUNNERS AND CROSS “T” ALONG FULL HEIGHT
PARTITION AT 8’-0” OC AND HOLD 5/8” CLR AT ADJ WALLS.
LATERAL SUPPORT OF SUSPENDED CEILING
CROSS "T" RUNNER
2" MAX
45° MAX TYP
8"
MAX
.PERIMETER HANGER
WIRES AT ALL
RUNNERS AND "T'S"
ADJ TO WALLS
MAIN "T" RUNNER
STRUCTURAL STRUT
12 GA HANGER WIRES AT 48" OC
ALONG MAIN "T" RUNNERS.
METAL STUDS MUST BE
ORIENTED AS SHOWN AND
CONNECT EVERY 12" ALONG
THEIR LENGTH.
<10'-0" : (2) 1-5/8" (25 GA) METAL STUD
<15'-0" : (2) 2-1/2" (25 GA) METAL STUD
<20'-0" : (2) 3-5/8" (25 GA) METAL STUD
6. 2 INCH OVERSIZED RING, SLEEVE OR ADAPTER REQUIRED AT SPRINKLER
PIPE PENETRATIONS OF THE NEW SUSPENDED CEILING TILE TO
ACCOMMODATE FREE MOVEMENT OF UP TO 1 INCH BY SPRINKLER PIPING.
CBC SECT. 2506.2.1 AND ASCE 7-05 SECT. 13.5.6.2.2 ITEM E.
12 GA VERTICAL
WIRE HANGER.
CLIP ON END OF
VERTICAL BRACE
FOR SNAPPING AND
LOCKING MAIN
RUNNER.
12 GA BRACE
WIRES. WIRES AT
45° IN (4)
DIRECTIONS. WIRE
TIED TO GRID.
UNDERSIDE OF
CONCRETE SLAB.
HEAVY DUTY
COMPRESSION
SPRING FOR
ADJUSTMENT
(INSIDE VERTICAL
BRACE).
SECTION
SELF TAPPING
DRIVE SCREW #8 x
1/2".
SPRING CLIP - .035
SPRING STEEL.
CEILING
GRID MAIN
RUNNER
ANGLE CLIP-PINNED TO CLG
STRUCTURE AND BOLTED TO
VERTICAL COMPRESSION
BRACE.
VERTICAL COMPRESSION
BRACE MADE FROM .055
STEEL TUBING.
60°
45° MAX
45°
MAX 60°
NO 12 GA LATERAL SUPPORT WIRE WITHIN 3” OF EACH CORNER OF LIGHT FIXTURE. PLAY
WIRE AS SHOWN AND FASTEN TO (E) STRUCTURE. MIN OF (3) WIRE TURNS EACH
CONNECTION POINT. WIRE SUPPORT BY ACOUSTICAL CLG CONTRACTOR. SEE CURRENT
ASTMC 635, ASTMC 636, ASTMC 1395, CISCA ACOUSTICAL CEILINGS - USE AND PRACTICE,
CISCA - CEILINGS HANDBOOK.
FIXTURES WEIGHT 20 LBS OR MORE: CONNECT (2) 12 GA FIXTURE SUPPORT WIRES AT
DIAGONAL CORNERS OF EACH FIXTURE. MIN OF (3) WIRE TURNS EACH CONNECTIONS
POINT. FIXTURE SUPPORT WIRES SUPPLIED AND HUNG BY “T” BAR CONTRACTOR. MAX
FIXTURE WEIGHT 55 LBS.
45°MAIN
RUNNER
CROSS "T"
NOTCHLESS AT
LIGHT EDGES
RECESSED
FLUORESCENT
FIXTURE
12 GA VERTICAL CABLE WIRED AT 48" OC,
CONTINUOUS UP TO STRUCTURE
SET OF 4-WAY LATERAL BRACING WIRES &
COMPRESSION STRUT AS SCHEDULED.
PARTITION AS SCHEDULED
8"
1"
METAL CROSS RUNNER AS
SCHEDULED
METAL MAIN RUNNER AS
SCHEDULED
SCHEDULED ACOUSTIC CEILING TILE
PARTITION AS SCHEDULED
MIN. 3/4" X 3/4" X 16 GA METAL ANGLE SPACER
WHERE CROSS RUNNER IS MORE THAN 12"
FROM END.
ATTACHED END FREE/UNATTACHED END
8" MAX
ARMSTRONG BERC2 SEISMIC CEILING GRID SYSTEM
7/8" X 7/8" METAL EDGE MOULDING AT BOTH
FIXED AND FREE/UNATTACHED END WITH
MIN. #10 SELF TAPPING SM CREWS @ 16" OC
SCREW TIGHTENED END THROUGH WEB OF GRID
RESTRICTING SEPARATION FROM WALL MOULDING.
3/4 " SPACE BETWEEN GRID
AND WALL AT FREE END.
7/8" X 7/8" METAL EDGE MOULDING AT BOTH FIXED
AND FREE/ UNATTACHED END WITH MIN. #10 SELF
TAPPING SM CREWS @ 16" OC
FREE/UNATTACHED
CONDITION
BERC2 ANGLE CLIP
SCREW LOOSE IN SLOT TO ALLOW MOVEMENT
BETWEEN GRAD AND EDGE MOULDING.
MOULDING SECURED TO WALL.
12 GA VERTICAL CABLE WIRED AT 48"
OC, CONTINUOUS UP TO STRUCTURE.
REFER TO DETAIL #3 AND 4 THIS SHEET
FOR ADDITIONAL INFORMATION
3/4" SPACE BETWEEN
END OF GRID AND WALL
AT FREE/UNATTACHED
SIDE.
MIN. 3/4" X 3/4" X 16 GA METAL ANGLE
SPACER WHERE CROSS RUNNER IS
MORE THAN 12" FROM END.
7/8" X 7/8" METAL EDGE MOULDING AT BOTH
FIXED AND FREE/UNATTACHED END WITH
MIN. #10 SELF TAPPING SM SCREWS @ 16 OC
8" MAX.
7/8"
BERC2 ANGLE CLIP
SCREW TIGHTENED END THROUGH WEB
OF GRID RESTRICTING SEPARATION
FROM WALL MOULDING AT SECURED END.
ATTACHED CONDITION
ARMSTRONG BERC2 SEISMIC CEILING GRID SYSTEM
STRUCTURAL CONCRETE FILL
STEEL DECK
5/16" MIN. DRILL-IN EXPANSION
ANCHOR.
MAX
3/4"
45°
STEEL STRAP 1" WIDE X 12 GA.
MIN.
4 TIGHT TURNS IN 1.5"
SPLAYED BRACE WIRE
STRUCTURAL CONCRETE FILL
STEEL DECK
SHOT-IN ANCHOR 3/4" MIN.
PENETRATION
CLG. CLIP 13 GA. X 3/4" WIDE
MIN.
3 TIGHT TURNS IN 1.5"
VERTICAL HANGER WIRE
MAX
3/4"
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
1
2
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
3" = 1'-0"23008.00
A7.20
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
CEILING DETAILS
COLLECTORS
-
3" = 1'-0"2SUSPENDED CEILING DETAIL
3" = 1'-0"3COMPRESSION STRUT DETAIL
3" = 1'-0"4LIGHT FIXTURE BRACING
3" = 1'-0"5CLG SEISMIC TRIM DETAIL ARMSTRONG BERC2
3" = 1'-0"6CLG SEISMIC TRIM DETAIL ARMSTRONG BERC2 AXO
3" = 1'-0"7CLG - CONNECTION TO DECK
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
ELECTRICAL AND
TELE/DATA OUTLETS (TYP)
SCHEDULED HARDWARE
THERMOSTAT
(OPERABLE)
LIGHT SWITCHES (GANG
MULTIPLE SWITCHES.)
NOTE:ALL DEVICE
LOCATIONS SHOWN
BELOW ARE
DIMENSIONED WITH
RESPECT TO THE
STRIKE SIDE DOOR
JAMB. WHERE
SIDELIGHT OCCUS,
SHIFT ALL DEVICES
TO INDICATED
DISTANCES WITH
RESPECT TO
SIDELIGHT JAMB.
REFERENCE
ARCHITECTURAL
THEN ELECTRICAL
DRAWINGS AT
EACH DOOR TO
DETERMINE IF
SWITCHES ARE
LOCATED ON DOOR
WALL OR SIDE
WALL. NOTIFY
ARCHITECT PRIOR
TO INSTALLATION
WHERE LOCATION
IS NOT CLEAR. ALL
DEVICES SHALL
ALIGN VERTICALLY
WHERE POSSIBLE
AT INDICATED
SWITCH LOCATION.
SIDELIGHT, WHERE
APPLICABLE. ADJUST
DEVICES IN RELATION
TO SIDELIGHT JAMB.
SIDELIGHT, WHERE APPLICABLE.
SCHEDULED CEILING
THERMOSTAT (NON-
OPERABLE)
4'
-
3
"
MA
X
3'
-
6
"
MI
N
6'
-
8
"
5'
-
0
"
3'
-
2
"
(
T
Y
P
)
1'
-
6
"
STROBE (VERIFY WITH ALL
APPLICABLE CODES.)
MIN
2"
10"
4'
-
0
"
M
A
X
1'
-
0
"
EMERGENCY EXIT PLAN
SITE ADDRESS
CITY, STATE ZIP
1' - 0"
# FLOOR
ALARM LOOKS LIKE:
STROBE LIGHT
ALARM SOUNDS LIKE:
WHOOP WHOOP
YOU ARE HERE
EXIT ROUTE
EXTINGUISHER
ALARM PULL
STAIRS
ELEVATOR
IN EMERGENCY DIAL: 911
IN CASE OF FIRE, USE STAIRS FOR EXIT.
DO NOT USE ELEVATOR.
EVACUATION MAP TO BE
PROVIDED BY FLOOR;
SYMBOLS AND
INFORMATION
REFERENCED TO THE
LEFT TO BE INCLUDED
AS REQURIED
4
1
/
2
"
8"
ROUTE
1"
T
Y
P
.
1/
2
"
M
I
N
.
3/
8
"
M
I
N
,
1
/
2
"
M
A
X
#2 BRAILLE SIGNAGE
EXIT
RAISED LETTERING
3"
M
I
N
6" ±
EXIT
1/
2
"
M
I
N
.
3/
8
"
M
I
N
,
1
/
2
"
M
A
X
MI
N
.
1"
#2 BRAILLE SIGNAGE
RAISED LETTERING
4"
8" ±
ROOM NAME
NUMBER
3/
8
"
3/
4
"
T
Y
P
.
1/
2
"
M
I
N
.
3/
8
"
M
I
N
,
1
/
2
"
M
A
X
#2 BRAILLE SIGNAGE
FL EL
TRANSITION
POINT
SCHEDULED CARPET TILE
TS-03 EXTRUDED RESILIENT
REDUCER STRIP, CONTINUOUS.
CENTER BELOW DOOR THICKNESS
WHEN PRESENT.
SCHEDULED RESILIENT FLOOR
TILE
1/2" = 1'-0"1TYP. MOUNTING HEIGHTS N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
3/
5
/
2
0
2
6
1
1
:
5
4
:
1
3
A
M
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
C
o
l
l
e
c
t
o
r
s
-
s
n
a
1
6
1
0
p
h
4
/
s
n
a
1
6
1
0
p
h
4
_
RV
T
2
6
.
r
v
t
As indicated23008.00
A7.40
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
FINISH WALL, FLOOR &
MISCELLANEOUS DETAILS
COLLECTORS
-
3" = 1'-0"4ROOM NAME1
3" = 1'-0"6EXIT SIGN1
3" = 1'-0"5EXIT ROUTE SIGN
3" = 1'-0"3EMERGENCY EXIT PLAN SIGN
6" = 1'-0"2FINISH FLOOR TRANSITION AT CARPET AND RESILIENT FLOORING
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
2025-1218 PERMIT SET
1 2 3 4 5
A
A.9
B.2
C
D
E
E.2
F
G
1.SEE SHEETS S0.1 & S0.2 FOR GENERAL NOTES AND ABBREVIATIONS.
2.SEE SHEETS S7.0 FOR WOOD DETAILS AND SECTIONS.
3.VERIFY ALL DIMENSIONS AND FRAMING SIZES IN FIELD PRIOR TO CONSTRUCTION.
4.REMOVE AND REPLACE (E) WATERPROOFING AS REQUIRED.
ROOF FRAMING PLAN NOTES & KEYNOTES:
INDICATES (E) 3/4" PLYWOOD W/ 1 1/2" ELASTIZELL TOPPING, V.I.F.5.
INDICATES (E) STEEL BEAM W/ SIZE PER PLAN, V.I.F.
INDICATES (E) 18" TJI/60C @ 16" O.C., V.I.F.
7
6.
INDICATES (E) Wx COLUMN, V.I.F.8.
INDICATES (E) HSS COLUMN, V.I.F.9.
(E) W30x116(E) W30x116
(E) W33x152(E) W33x152
(E) W30x108(E) W30x108
(E) W30x108(E) W30x108
(E) W33x152(E) W33x152
(E) W33x118
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E) W16x31
(E) W16x31
(E) W27x84 (E) W30x132
(E) W30x108
(E) W27x84 (E) W27x84 (E) W30x108
(E) W30x108
(E) W27x84 (E) W30x108
(E) W27x84 (E) W30x108(E) W27x84
N.I.C.
N.I.C.
N.I.C.
N.I.C.
(E) W30x108
1 PARTIAL MEZZANINE FRAMING PLAN
3/32" = 1'-0"
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO.CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
As indicated24026.2
sna1610ph4 - PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
COLLECTORS
-
Δ DATE REASON FOR ISSUE BY
2025-1218 PLAN CHECK BM
ISSUE RECORD
3852 W. 157th Street
Lawndale, CA 90260
PHONE: 562-673-0056
www.ardmorestructural.com
PARTIAL MEZZANINE
FRAMING PLAN
S2.0
GENERAL NOTES
S0.1
YourSpreadsheets
Address line 1 and line 2
Telephone line 1 and Fax
A GROUND BEAM GB2 REVISED.D
B
REMOVED GB32. ADDED NEW
REINFORCEMENT TO GB4 AND
GB12. ADDED NEW GB48.
D
C NEW LINKS ADDED TO GB23.DFLOOR = 50 PSF + 15 PSF PARTITIONS
BM
1.THE CONTRACTOR SHALL VERIFY ALL DIMENSION PRIOR TO STARTING CONSTRUCTION. THE DESIGN TEAM
SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES.
2.ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL DRAWINGS AND SPECIFICATIONS PRIOR TO THE
START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER
PRIOR TO THE START OF CONSTRUCTION SO THAT CLARIFICATION CAN BE PROVIDED. ANY WORK PERFORMED
IN CONFLICT WITH THE CONTRACT DOCUMENTS OR CODE REQUIREMENTS SHALL BE CORRECTED BY THE
CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE OWNER OR ENGINEER.
3.MATERIALS AND WORKMANSHIP TO CONFORM WITH PART TWO OF THE 2024 EDITION OF THE CALIFORNIA
BUILDING CODE, WITH CITY OF PICO RIVERA AMENDMENTS AND THE REQUIREMENTS OF THE CONTRACT
DOCUMENTS.
4.NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.
WHERE NOT DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
5.REFERENCE TO CODES, RULES, REGULATIONS, STANDARDS, MANUFACTURER’S INSTRUCTIONS OR
REQUIREMENTS OF REGULATORY AGENCIES IS TO THE LATEST PRINTED EDITION OF EACH IN EFFECT AT THE
DATE OF SUBMISSION OF BID UNLESS THE DOCUMENT DATE IS SHOWN.
6.DETAILS ON SHEETS TITLED “TYPICAL DETAILS” APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. SUCH DETAILS ARE NOT NOTED AT EACH
LOCATION THAT THEY OCCUR.
7.DO NOT SCALE THE DRAWINGS.
8.THE CONTRACT STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE. THE CONTRACTOR SHALL
PROVIDE MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES
INCLUDE, BUT MAY NOT BE LIMITED TO, BRACING AND SHORING FOR LOADS DURING CONSTRUCTION.
OBSERVATION VISITS TO THE SITE BY THE ENGINEER WILL NOT INCLUDE OBSERVATION OF THE ABOVE NOTED
ITEMS.
9.INFORMATION SHOWN ON THE DRAWINGS RELATED TO EXISTING CONDITIONS REPRESENTS THE PRESENT
KNOWLEDGE, BUT WITHOUT GUARANTEE OF ACCURACY. REPORT CONDITIONS THAT CONFLICT WITH THE
CONTRACT DOCUMENTS TO THE OWNER. DO NOT DEVIATE FROM THE CONTRACT DOCUMENTS WITHOUT
WRITTEN DIRECTION FROM THE OWNER.
10.THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR PROVIDING A SAFE PLACE TO WORK AND MEETING
THE REQUIREMENTS OF ALL APPLICABLE JURISDICTIONS. EXECUTE WORK TO ENSURE THE SAFETY OF
PERSONS AND ADJACENT PROPERTY AGAINST DAMAGE BY FALLING DEBRIS AND OTHER HAZARDS IN
CONNECTION WITH THIS WORK.
11.REFER TO ARCHITECTURAL DRAWINGS FOR SIZE AND LOCATION OF FLOOR, ROOF AND WALL OPENINGS NOT
SHOWN ON THE STRUCTURAL DRAWINGS. COORDINATE THE SIZE AND LOCATION OF OPENINGS ASSOCIATED
WITH, BUT NOT LIMITED TO, ELECTRICAL, MECHANICAL AND PLUMBING TRADES. SUBMIT FINAL SIZING AND
LOCATION REQUIREMENTS OF OPENINGS TO THE OWNER FOR REVIEW.
12.CONSTRUCTION MATERIAL SHALL BE SPREAD OUT IF PLACED ON FRAMED ROOF OR FLOOR. LOAD SHALL NOT
EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. PROVIDE ADEQUATE SHORING AND/OR BRACING WHERE
STRUCTURE HAS NOT ATTAINED DESIGN STRENGTH.
I. GENERAL
General Structural Notes
1.VERSA-LAM TO COMPLY WITH ESR-1040. PARALLAM PSL AND MICROLLAMS LVL TO COMPLY WITH ESR-1387.
2.MICROLAMS LVL TO BE MAUFACTURED BY TRUS JOIST WITH THE FOLLOWING PROPERTIES:
Fb = 2600 PSI
Fv = 285 PSI
E = 1.9 E6 PSI
3.NOTCH OR BORE MEMBERS ONLY WHERE APPROVED BY THE MANUFACTURER OR WHERE SPECIFICALLY
DETAILED ON THE STRUCTURAL DRAWINGS.
IX. ENGINEERED WOOD PRODUCTS
280
D
(E) W27x84
1.SHOP DRAWINGS, CALCULATIONS, SAMPLES, ETC. FOR THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE
ARCHITECT FOR REVIEW A MINIMUM OF 15 WORKING DAYS PRIOR TO FABRICATION OF WORK:
A.CONCRETE MIX DESIGN SHALL BE STAMPED AND SIGNED BY SUPPLIER'S PROFESSIONAL ENGINEER.
B.STEEL REINFORCEMENT
XI. SUBMITTALS
ANY SUBSTITUTIONS TO THE PRODUCTS SPECIFIED
1.GRAVITY LOADS:
A. DEADLOADS: VARY BASED ON ACTUAL BUILDING AND EQUIPMENT OPERATING WEIGHTS.
B. LIVE LOADS:
ROOF = 20 PSF (REDUCIBLE)
C. SNOW LOADS:
Pg = ZERO
XII. DESIGN CRITERIA
II
IX. ENGINEERED WOOD PRODUCTS
SANTA ANA
I V.
FLOOR: 50 PSF + 15 PSF PARTITIONS
1 2 3 4 5
A
A.9
B.2
C
D
E
E.2
F
G
1.SEE SHEETS S0.1 & S0.2 FOR GENERAL NOTES AND ABBREVIATIONS.
2.SEE SHEETS S7.0 FOR WOOD DETAILS AND SECTIONS.
3.VERIFY ALL DIMENSIONS AND FRAMING SIZES IN FIELD PRIOR TO CONSTRUCTION.
4.REMOVE AND REPLACE (E) WATERPROOFING AS REQUIRED.
ROOF FRAMING PLAN NOTES & KEYNOTES:
INDICATES (E) 3/4" PLYWOOD W/ 1 1/2" ELASTIZELL TOPPING, V.I.F.5.
INDICATES (E) STEEL BEAM W/ SIZE PER PLAN, V.I.F.
INDICATES (E) 18" TJI/60C @ 16" O.C., V.I.F.
7
6.
INDICATES (E) Wx COLUMN, V.I.F.8.
INDICATES (E) HSS COLUMN, V.I.F.9.
(E) W30x116(E) W30x116
(E) W33x152(E) W33x152
(E) W30x108(E) W30x108
(E) W30x108(E) W30x108
(E) W33x152(E) W33x152
(E) W33x118
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E) W16x31
(E) W16x31
(E) W27x84 (E) W30x132
(E) W30x108
(E) W27x84 (E) W27x84 (E) W30x108
(E) W30x108
(E) W27x84 (E) W30x108
(E) W27x84 (E) W30x108(E) W27x84
N.I.C.
N.I.C.
N.I.C.
N.I.C.
(E) W30x108
1 PARTIAL MEZZANINE FRAMING PLAN
3/32" = 1'-0"
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO.CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
As indicated24026.2
sna1610ph4 - PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
COLLECTORS
-
Δ DATE REASON FOR ISSUE BY
2025-1218 PLAN CHECK BM
ISSUE RECORD
3852 W. 157th Street
Lawndale, CA 90260
PHONE: 562-673-0056
www.ardmorestructural.com
PARTIAL MEZZANINE
FRAMING PLAN
S2.0S0.2
ABBREVIATIONS
YourSpreadsheets
Address line 1 and line 2
Telephone line 1 and Fax
A GROUND BEAM GB2 REVISED.D
B
REMOVED GB32. ADDED NEW
REINFORCEMENT TO GB4 AND
GB12. ADDED NEW GB48.
D
C NEW LINKS ADDED TO GB23.D
BM
(E)
(N)
#
&
@
A.A.
A.B.
ABV
ADD'L
ADH
ADJ
AGGR
AL
ALT
ANSI
APPROX
ARCH
ASTM
A.C.
BTWN
BLDG
BLKG
BM or BMS
B.N.
B.O. FTG
BOT
B.P.
BRG
B.S.
BSMT
C
CANT
C.I.P.
C.J.
CL
CLG
CLR
CMU
COL
CONC
CONN
CONST
CONT
CP
CSK
CTR
d
DBL
DEMO
DET or DETS DETAIL or DETAILS
DEMOLITION
DOUBLE
PENNY (NAIL SIZE)
CENTER
COUNTERSINK
COMPLETE PENETRATION
CONTINUOUS
CONSTRUCTION
CONNECTION
CONCRETE
COLUMN
CONCRETE MASONRY UNIT
CLEAR
CEILING
CENTERLINE
CONSTRUCTION JOINT
CAST IN PLACE
CANTILEVER
CHANNEL
BASEMENT
BOTH SIDES
BEARING
BASE PLATE
BOTTOM
BOTTOM OF FOOTING
BOUNDARY NAILING
BEAM or BEAMS
BLOCKING
BUILDING
BETWEEN
ASPHALT CONCRETE
TESTING and MATERIALS
AMERICAN SOCIETY for
ARCHITECTURAL
APPROXIMATE
STANDARDS INSTITUTE
AMERICAN NATIONAL
ALTERNATE
ALUMINUM
AGGREGATE
ADJACENT
ADHESIVE
ADDITIONAL
ABOVE
ANCHOR BOLT
ADHESIVE ANCHOR
AT
AND
NUMBER
NEW
EXISTING DIAG
DIA or Ø
DIM or DIMS
DIST
DK or DKG
DN
DO
DWG or DWGS
DWL or DWLS
EA
E.D.
E.F.
E.J.
EL
ELEC
ELEV
EMBED
E.N.
E.O. SLAB
EQ
EQUIP
E.S.
EV
E.W.
EXCAV
EXP
EXT
FDN
F.F.
FIN
FLR or FLRS
F.N.
F.O.
F.O. CONC
F.O. STUD(S)
FPRF
F.R.O.
FRP
F.S.
FT
FTG or FTGS
GA
GALV
GL
GLB
GRND
GR
GYP BD
HD
H.D.G.HOT DIPPED GALVANIZED
HOLDOWN
GYPSUM BOARD
GRADE
GROUND
GLU-LAM BEAM
GLASS or GLAZING
GALVANIZED
GAUGE
FOOTING or FOOTINGS
FOOT AND FEET
FAR SIDE
PLASTIC
FIBERGLASS REINFORCED
FOR REFERENCE ONLY
FIREPROOFING
FACE OF STUD(S)
FACE OF CONCRETE
FACE OF
FIELD NAILING
FLOOR or FLOORS
FINISH
FAR FACE
FOUNDATION
EXTERIOR
EXPANSION
EXCAVATE or EXCAVATION
EACH WAY
EVERY
EACH SIDE
EQUIPMENT
EQUAL
EDGE OF SLAB
EDGE NAILING
EMBEDMENT
ELEVATOR
ELECTRICAL
ELEVATION
EXPANSION JOINT
EACH FACE
EDGE DISTANCE
EACH
DOWEL or DOWELS
DRAWING or DRAWINGS
DITTO
DOWN
DECK or DECKING
DISTANCE
DIMENSION or DIMENSIONS
DIAMETER
DIAGONAL HDR
HK or HKS
HORIZ or (H)
H.P.
H.S.B.
HSS
HT
I.D.
INFO
JST or JSTS
JT
K.O.
L
LARR
Ld
Ldh
LEV
LLBB
LLH
LLV
LOC
LONGIT
L.P.
s
LSL
LSH
LSV
LT
LVL
L.W.C.
MAX
M.B.
MECH
M.E.P.
MEZZ
M.F.
MFR
MIN
MISC
MTD
MTL
N
N.F.
N.I.C.
NO. or #
NOM DIA
N.S.
N.T.S.
N.W.C.NORMAL WEIGHT CONCRETE
NOT TO SCALE
NEAR SIDE
NOMINAL DIAMETER
NUMBER
NOT IN CONTRACT
NEAR FACE
NORTH
METAL
MOUNTED
MISCELLANEOUS
MINIMUM
MANUFACTURER
MOMENT FRAME
MEZZANINE
PLUMBING
MECHANICAL, ELECTRICAL,
MECHANICAL
MACHINE BOLT
MAXIMUM
LIGHT WEIGHT CONCRETE
VENEER LUMBER
MICROLLAM LAMINATED
LIGHT
LONG SIDE VERTICAL
LONG SIDE HORIZONTAL
STRAND LUMBER
TIMBERSTRAND LAMINATED
LAP SPLICE LENGTH
LOW POINT
LONGITUDINAL
LOCATION
LONG LEG VERTICAL
LONG LEG HORIZONTAL
LONG LEG BACK TO BACK
LEVEL
HOOK DEVELOPMENT LENGTH
DEVELOPMENT LENGTH
LOS ANGELES RESEARCH REPORT
ANGLE
KNOCK-OUT
JOINT
JOIST or JOISTS
INFORMATION
INSIDE DIAMETER
HEIGHT
HOLLOW STRUCTURAL SECTION
HIGH STRENGTH BOLTS
HIGH POINT
HORIZONTAL
HOOK or HOOKS
HEADER O/
O.C.
O.D.
O.H.
OPNG
OPP
OWJ
OWSG
OWSJ
P.A.F.
PARL
PB
PC or PCS
PERP
PL
PLF
PLYWD
P.P.
PR
PRCST
PSF
PSL
PT
P-T
P.T.
PTN
R or RAD
REBAR
REF
REINF
REQ'D
REV
RFG
R.O.
RSJ
S.A.D.
SCHED
S.D.S.
SECT
S.E.D.
SHT
SHTG
SIM
SL
S.M.D.
S.M.S.
S.O.G.SLAB ON GRADE
SHEET METAL SCREW
DOCUMENTS
SEE MECHANICAL
SLOPE
SIMILAR
SHEATHING
SHEET
DOCUMENTS
SEE ELECTRICAL
SECTION
SELF DRILLING SCREW
SCHEDULE
DOCUMENTS
SEE ARCHITECTURAL
ROLLED STEEL JOIST
ROUGH OPENING
ROOFING
REVISE OR REVISION
REQUIRED
REINFORCING
REINFORCED or
REFERENCE
REINFORCING BAR
RADIUS
PARTITION
PRESSURE TREATED
POST TENSIONED
POINT
PARALLAM STRAND LUMBER
POUNDS PER SQUARE FOOT
PRECAST
PAIR
PLYWOOD
PARTIAL PENETRATION
POUNDS PER LINEAR FOOT
PLATE
PERPENDICULAR
PIECE or PIECES
POST BELOW
PARALLEL
POWDER ACTUATED FASTENER
OPEN WEB STEEL JOIST
OPEN WEB STEEL GIRDER
OPEN WEB JOIST
OPPOSITE
OPENING
OPPOSITE HAND
OUTSIDE DIAMETER (DIM)
ON CENTER
OVER SPEC
SQ
S.S.
STAG
STD
STIFF
STIR
S.N.
STL
STRUC
S.E.O.R.
SUBST
SUSP
SYM
TMPD
T&B
T&G
THK
THRD
THRU
T.N.
T.O.
T.O. B.P.
T.O. CONC
T.O. STL
T.O. SLAB
TRANS
TR
TS
TSG
TYP
U.O.N.
URM
VENT.
VERT or (V)
V.I.F.
W/
W/O
W or WF
WD
W.P.
WT
WWF
X HVY
XX HVY
X STR
XX STR DOUBLE EXTRA STRONG
EXTRA STRONG
DOUBLE EXTRA HVY
EXTRA HEAVY
WELDED WIRE FABRIC
WEIGHT
WORK POINT
WOOD
WIDE FLANGE
WITHOUT
WITH
VERIFY IN FIELD
VERTICAL
VENTILATE
UNREINFORCED MASONRY
UNLESS OTHERWISE NOTED
TYPICAL
TAPERED STEEL GIRDER
TUBE STEEL
TREAD
TRANSVERSE
TOP OF STRUCTURAL SLAB
TOP OF STEEL
TOP OF CONCRETE
TOP OF BASE PLATE
TOP OF
TOE NAIL
THROUGH
THREADED
THICK
TONGUE AND GROOVE
TOP AND BOTTOM
TEMPERED
SYMMETRICAL
SUSPENDED
SUBSTITUTE
OF RECORD
STRUCTURAL ENGINEER
STRUCTURAL
STEEL
STITCH NAILING
STIRRUP or STIRRUPS
STIFFENER
STANDARD
STAGGER or STAGGERED
STAINLESS STEEL
SQUARE
SPECIFICATIONS
SPECIFICATION or
ABBREVIATIONS
1 2 3 4 5
A
A.9
B.2
C
D
E
E.2
F
G
1.SEE SHEETS S0.1 & S0.2 FOR GENERAL NOTES AND ABBREVIATIONS.
2.SEE SHEETS S7.0 FOR WOOD DETAILS AND SECTIONS.
3.VERIFY ALL DIMENSIONS AND FRAMING SIZES IN FIELD PRIOR TO CONSTRUCTION.
4.REMOVE AND REPLACE (E) WATERPROOFING AS REQUIRED.
ROOF FRAMING PLAN NOTES & KEYNOTES:
INDICATES (E) 3/4" PLYWOOD W/ 1 1/2" ELASTIZELL TOPPING, V.I.F.5.
INDICATES (E) STEEL BEAM W/ SIZE PER PLAN, V.I.F.
INDICATES (E) 18" TJI/60C @ 16" O.C., V.I.F.
7
6.
INDICATES (E) Wx COLUMN, V.I.F.8.
INDICATES (E) HSS COLUMN, V.I.F.9.
(E) W30x116(E) W30x116
(E) W33x152(E) W33x152
(E) W30x108(E) W30x108
(E) W30x108(E) W30x108
(E) W33x152(E) W33x152
(E) W33x118
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E) W16x31
(E) W16x31
(E) W27x84 (E) W30x132
(E) W30x108
(E) W27x84 (E) W27x84 (E) W30x108
(E) W30x108
(E) W27x84 (E) W30x108
(E) W27x84 (E) W30x108(E) W27x84
N.I.C.
N.I.C.
N.I.C.
N.I.C.
(E) W30x108
1 PARTIAL MEZZANINE FRAMING PLAN
3/32" = 1'-0"
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO.CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
As indicated24026.2
sna1610ph4 - PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
COLLECTORS
-
Δ DATE REASON FOR ISSUE BY
2025-1218 PLAN CHECK BM
ISSUE RECORD
3852 W. 157th Street
Lawndale, CA 90260
PHONE: 562-673-0056
www.ardmorestructural.com
PARTIAL MEZZANINE
FRAMING PLAN
S2.0
11.INDICATES ORIENTATION OF PROPOSED STORAGE, SEE ZONES
BELOW, CONTACT SEOR BEFORE REPOSITIONING
10.INDICATES 1-3/4x14 LVL @ 16" O.C., SEE 1/S7.0
INDICATES AREA INTENDED TO STORE 36"x48" MAIL/WIP HAMPERS,
MAX WEIGHT OF 150 LBS PER HAMPER W/ ORIENTATION PER PLAN
3'-0" MIN
TYP
12.
13.
INDICATES AREA INTENDED TO STORE 40"x48" MATERIAL PALLETS,
MAX WEIGHT OF 665 LBS PER PALLET W/ ORIENTATION PER PLAN,
DO NOT STACK PALLETS
14.
INDICATES AREA INTENDED TO STORE 18"x48" STORAGE RACKS,
MAX WEIGHT OF 614 LBS PER RACK W/ ORIENTATION PER PLAN
3
S7.0
TYP @
LVL
YourSpreadsheets
Address line 1 and line 2
Telephone line 1 and Fax
A GROUND BEAM GB2 REVISED.D
B
REMOVED GB32. ADDED NEW
REINFORCEMENT TO GB4 AND
GB12. ADDED NEW GB48.
D
C NEW LINKS ADDED TO GB23.D
BM
1 2 3 4 5
A
A.9
B.2
C
D
E
E.2
F
G
1.SEE SHEETS S0.1 & S0.2 FOR GENERAL NOTES AND ABBREVIATIONS.
2.SEE SHEETS S7.0 FOR WOOD DETAILS AND SECTIONS.
3.VERIFY ALL DIMENSIONS AND FRAMING SIZES IN FIELD PRIOR TO CONSTRUCTION.
4.REMOVE AND REPLACE (E) WATERPROOFING AS REQUIRED.
ROOF FRAMING PLAN NOTES & KEYNOTES:
INDICATES (E) 3/4" PLYWOOD W/ 1 1/2" ELASTIZELL TOPPING, V.I.F.5.
INDICATES (E) STEEL BEAM W/ SIZE PER PLAN, V.I.F.
INDICATES (E) 18" TJI/60C @ 16" O.C., V.I.F.
7
6.
INDICATES (E) Wx COLUMN, V.I.F.8.
INDICATES (E) HSS COLUMN, V.I.F.9.
(E) W30x116(E) W30x116
(E) W33x152(E) W33x152
(E) W30x108(E) W30x108
(E) W30x108(E) W30x108
(E) W33x152(E) W33x152
(E) W33x118
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E
)
W
3
3
x
2
4
1
(E) W16x31
(E) W16x31
(E) W27x84 (E) W30x132
(E) W30x108
(E) W27x84 (E) W27x84 (E) W30x108
(E) W30x108
(E) W27x84 (E) W30x108
(E) W27x84 (E) W30x108(E) W27x84
N.I.C.
N.I.C.
N.I.C.
N.I.C.
(E) W30x108
1 PARTIAL MEZZANINE FRAMING PLAN
3/32" = 1'-0"
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO.CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
As indicated24026.2
sna1610ph4 - PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
COLLECTORS
-
Δ DATE REASON FOR ISSUE BY
2025-1218 PLAN CHECK BM
ISSUE RECORD
3852 W. 157th Street
Lawndale, CA 90260
PHONE: 562-673-0056
www.ardmorestructural.com
PARTIAL MEZZANINE
FRAMING PLAN
S2.0
BM
S7.0
WOOD FRAMING
DETAILS & SECTIONS
YourSpreadsheets
Address line 1 and line 2
Telephone line 1 and Fax
A GROUND BEAM GB2 REVISED.D
B
REMOVED GB32. ADDED NEW
REINFORCEMENT TO GB4 AND
GB12. ADDED NEW GB48.
D
C NEW LINKS ADDED TO GB23.D
1
FLOOR
STRENGHTENING AT RACK STORAGE
1"=1'-0"
3
FLOOR STRENGTHENING
AT RACK STORAGE - END SUPPORT
N.T.S.
CL (E)
TJI, TYP16" MAX, VIF
CL LVLEQ EQ
(E) TOPPING O/
(E) PLYWOOD
PER PLAN, VIF
(E) 18" TJI PER
PLAN, VIF, TYP
LVL PER PLAN @ 16" O.C. W/
SIMPSON 'A35' EA SIDE @ 24" O.C.
STAGGERED W/ 8d INTO LVL & (6)
PH612I SCREWS INTO (E) SHTG, FILL
ALL HOLES, TYP EA JOIST BAY
REMOVE & REPLACE
(E) DRYWALL
SECTION A-A
(E) TOPPING O/ (E)
PLYWOOD PER PLAN, VIF
ALIGN, TYP
CLIP PER 1/-, TYP
LVL PER PLAN W/
SIMPSON 'U14' HANGER
(E) TJI BEYOND, VIF, TYP
(E) STEEL BEAM W/ 4x
NAILER PER PLAN
4x10 FULL-DEPTH WEB
FILLER W/ (2) 3/4" THRU BOLTS
EA PIECE, TYP EXTENT OF LVLS
PER PLAN, RIP WEB FILLER AS
REQ'D, TYP EA SIDE OF STEEL
BEAM
1-1/2" MIN
TYP TYP
2" MIN
STRUCTURAL CALCULATIONS FOR PLAN CHECK
FLOOR STRENGTHENING
COLLECTOR’S UNIVERSE PHASE 04 TI
1601 E. ST. ANDREWS PLACE
SANTA ANA, CA 90705
ASE PROJECT NO. 24026.1
4 PAGES
December 18, 2025
YourSpreadsheets
Address line 1 and line 2
Telephone line 1 and Fax
A GROUND BEAM GB2 REVISED.D
B
REMOVED GB32. ADDED NEW
REINFORCEMENT TO GB4 AND
GB12. ADDED NEW GB48.
D
C NEW LINKS ADDED TO GB23.D
Job:Collector's Universe TI Designed By:BM
Subject:Mass Takeoff Checked By:
Job Number:24026 Date:11/19/2024
2nd Floor
Flooring 2.0 psf
1.5" concrete topping 18.8 psf
3/4" plywood 3.5 psf
20" TJI at 16" o.c.3.0 psf
2 layers 5/8" drywall 5.5 psf
MEP 3.0 psf
Lights 1.0 psf
T-bar ceiling 3.0 psf
Misc.2.2 psf
2nd Floor DL =42.0 psf
2nd Floor LL =65.0 psf
Page 1 of 4
Page 2 of 4
JOIST
Series 60C NA=Not Applicable (not deep enough for web stiffener)
Depth 18.00 WS=Web Stiffener required
BG=Bearing too narrow or too wide
JOIST RESISTIVE VERT. EI K
WT. MOMENT SHEAR x 10 6 NAILS NAILS
(plf) (ft-lb) (lb) (psi) REQ'D. REQ'D.
NO YES NO YES NO YES NO YES NO YES
4.8 16130 2535 1829 5.3 1255 1885 1685 2320 4 - 16d 3130 3765 3675 4305 BG BG 4 - 16d
LVL = Microllam LVL QUICK CALC
WIDTH THICKNESS MATERIAL E SP = Southern Pine Uniform Live 101.53 plf TOTAL UNIFORM (full-length only)
(in) (in)x 10 6 LSL = Timberstrand LSL Uniform Dead 56.667 plf 158.2 plf
(psi) MSR = Machine Stress Rated Concentrated Live 0 lb TOTAL CONCENTRATED (@ midspan only)
SS = Solid Sawn Concentrated Dead 0 lb 0 lb
3.50 1.750 LVL 2.00 #VALUE! = no value in database Span 24 ft
Duration Factor 100%
Repetitive Member? Yes 104%
NET THICKNESS MATERIAL CRUSH Reaction 1898 lb Compare 1898 (DOL-adjusted value) to table above
DEPTH (in) CAP. OSB = Performance Plus OSB Shear 1898 lb 75%
(in) (psi) PLY = Plywood Moment 11390 ft-lb 68%
AE = A/E OSB Live Deflection 0.488 in L/590
14.50 0.4375 AE #VALUE! = no value in database Total Deflection 0.760 in L/379
VALID FOR:• Simple spans (distance between points of zero moment)
• Uniform loads, full-length
ROUT ROUT ROUT ROUT FLANGE GLUE • Concentrated load at midspan
CAP. DEPTH TIP WIDTH ANGLE BEARING SHEAR • Input load combination only, at input duration
(lb/in) (in) (in) (degrees) STRESS (psi)DEFLECTION:Calculated according to NER-200
(psi)SHEAR:Conservative. Actual shear at bottom-bearing ends is calculated at
inside face of support, which may be less than span (defined above).
SS = Solid Sawn
THICKNESS MATERIAL FIELD- PLANT- INTER- SKEW HEIGHT OSB = OSB
(in) INSTALLED INSTALLED MEDIATE WIDTH (in) END INT. M=L = Microllam LVL
WIDTH WIDTH WIDTH (in) BRNG. BRNG. T=S = Timberstrand LSL
(in) (in) (in) NA = Not Applicable (not deep enough for web stiffener)
1 1/2 SS, M=L, T=S 3 1/2 3 1/2 #VALUE!5 1/2 #VALUE!4 - 16d 4 - 16d #VALUE! = no value in database
NAILS REQ'D
END REACTION (lb)
1-3/4"
Bearing Lgth.
3-1/2"
Bearing Lgth.
BASIC PROPERTIES REACTION PROPERTIES
7"
Bearing Lgth.
INTERMEDIATE REACTION (lb)
5-1/4"
Web Stiffeners
Bearing Lgth. Bearing Lgth.
3-1/2"
WEB STIFFENER
WEB PROPERTIES
ROUT PROPERTIES
FLANGE PROPERTIES
Web Stiffeners Web Stiffeners Web Stiffeners Web Stiffeners
Page 3 of 4
Wood Beam
LIC# : KW-06020694, Build:20.25.09.04 ARDMORE STRUCTURAL ENGINEERING (c) ENERCALC, LLC 1982-2025
DESCRIPTION:LVL at mid-tributary of (E) TJIs
Project File: Collector's Universe Phase 04 TI.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Referenced Design Standard(s) : NDS 2018
Load Combination Set : IBC 2018
Code References
Governing Code : IBC 2021
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Allowable Stress Design
iLevel Truss Joist
MicroLam LVL 2.0 E
2600
2600
2510
750
2000
1016.535
285
1555 42.01
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :IBC 2018
1.75x14
Span = 24.0 ft
1 2
L(0.0682)
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Uniform Load : L = 0.06820 , Tributary Width = 1.0 ft, ((E)LL and WIP Racks)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio Maximum Shear Stress Ratio
1.75x14
0.176
Section used for this span1.75x14
: 10.447 =: 1
Load Combination
+D+L +D+L
Span # where maximum occurs Span # 1
Location of maximum on span 12.000 ft
50.10 psi=
2,546.06 psi
Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination
=
=
=
285.00 psi==
0.000 ft=
=
1,138.78 psi
Maximum Deflection
450
>=360
407
Ratio =0 >=240
Max Downward Transient Deflection 0.640 in
0
Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.707 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : L Only
n/a
Span: 1 : +D+L
n/a
NDS2018 NDS2018
Page 4 of 4
ELECTRICAL SHEET LIST
SHEET NUMBER SHEET NAME
E001 COVER SHEET
E002 LIGHTING SCHEDULE
E003 TITLE 24 FORMS
E101 DEMOLITION PLAN - LEVEL 2
E201 LIGHTING PLAN - LEVEL 2
E301 POWER PLAN - LEVEL 2
E501 EMERGENCY EGRESS PLAN - LEVEL 2
E701 LIGHTING CONTROL DETAILS
E801 SINGLE LINE DIAGRAM
E901 PANEL SCHEDULES
SIGNAL LEGEND
FLUSH MOUNTED TELEVISION OUTLET MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.O.N
WIRELESS ACCESS POINT
FLUSH MOUNTED TELECOM OUTLET MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.O.N. PROVIDE 1"C. TO ACCESSIBLE CEILING SPACE
WITH PULL STRING, U.O.N.
SURFACE MOUNTED TELECOM OUTLET MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.ON. PROVIDE 1"C. TO ACCESSIBLE CEILING
SPACE WITH PULL STRING, U.O.N.
CEILING MOUNTED TELECOM OUTLET
PUSH BUTTON
BUZZER
BELL
WALL MOUNTED SPEAKER
CEILING MOUNTED SPEAKER
TV
FLUSH FLOOR BOX WITH TELECOM OUTLET
FIRE RATED POKE THRU WITH TELECOM OUTLET
FLUSH MOUNTED WALL PHONE OUTLET MOUNTED AT +44" AFF TO
TOP OF BOX U.O.N
WAP
B
B
S
S
SECURITY LEGEND
ELECTRIC DOOR STRIKE
DOOR CONTACT
REMOTE DOOR RELEASE
ELECTRONIC LOCK
VIBRATION DETECTOR
CARD READER
KEYPAD
GLASS BREAK
MOTION SENSOR
DOOR BREACH ALARM
PANIC BUTTON / DURESS ALARM
REQUEST TO EXIT
ELECTRONIC HOLD OPEN
ELECTRONIC PANIC HARDWARE
ELECTRONIC MAGNETIC LOCK
VIDEO CAMERA
A
CR
KP
ALARM CONTACT
GB
MS
ES
DC
DR
EL
VD
DA
PB
REX
EHO
EPH
EML
CONTROL LEGEND
SURFACE MOUNTED SPST SWITCH MOUNTED AT +48" AFF TO TOP
OF BOX U.O.N
FLUSH MOUNTED SINGLE POLE STANDARD TOGGLE SWITCH
MOUNTED AT +48" AFF TO TOP OF BOX U.O.N. LETTERING INDICATES
QUANTITY OF SWITCHES AND DEVICES TO BE CONTROLLED.
XX
D = DIMMING SWITCH
K = KEYED SWITCH
P = PILOT LIGHT SWITCH
R = MOMENTARY CONTACT SWITCH
T = TIMER SWITCH
3 = THREE WAY SWITCH
FLUSH INFRARED WALL OCCUPANCY SENSOR SINGLE BUTTON
MOUNTED AT +48" AFF TO TOP OF BOX U.O.NOC
FLUSH INFRARED WALL OCCUPANCY SENSOR DUAL BUTTON
MOUNTED AT +48" AFF TO TOP OF BOX U.O.NOCab
SURFACE INFRARED WALL OCCUPANCY SENSOR SINGLE BUTTON
MOUNTED AT +48" AFF TO TOP OF BOX U.O.N
SURFACE INFRARED WALL OCCUPANCY SENSOR DUAL BUTTON
MOUNTED AT +48" AFF TO TOP OF BOX U.O.N
ab
OC
OC
XX U = ULTRA SONIC OCCUPANCY SENSOR
DT = DUAL TECHNOLOGY OCCUPANCY SENSOROC
CEILING MOUNTED INFRARED OCCUPANCY SENSOROC
FLUSH MOUNTED OVERRIDE SWITCH STATION MOUNTED AT +48"
AFF TO TOP OF BOX U.O.N. BUTTON CONFIGURATION AS NOTED
PER FLOOR PLAN
SURFACE MOUNTED OVERRIDE SWITCH STATION MOUNTED AT +
48" AFF TO TOP OF BOX U.O.N. BUTTON CONFIGURATION AS
NOTED PER FLOOR PLAN
PHOTOCELL MOUNTED AND ORIENTATED AS NOTED ON FLOOR
PLAN
O
O
PC
DL CEILING MOUNTED DAY LIGHT SENSOR
S
S
S
ABBREVIATIONS AND DESCRIPTIONS
A / AMP AMPERE
ABV ABOVE
ADA AMERICAN WITH DISABILITIES ACT
AF AMPERE FRAME, AMPERE FUSE
AFF / A.F.F.ABOVE FINISH FLOOR
AFG, A.F.G.ABOVE FINISH GRADE
AWG AMERICAN WIRE GAUGE
AIC / A.I.C.AMPERE INTERRUPTING CAPACITY
AS AMPERE SWITCH
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AVG AVERAGE
BKR BREAKER
BLDG BUILDING
BR BRANCH
C CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CBC CALIFORNIA BUILDING CODE
CEC CALIFORNIA ELECTRIC CODE
CFC CALIFORNIA FIRE CODE
CIRC / CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CO / C.O. CONDUIT ONLY
COMM COMMUNICATIONS
CSFM CALIFORNIA STATE FIRE MARSHALL
CT CONTROL TRANSFORMER
CONN CONNECTED
CPT CONTROL POWER TRANSFORMER
CTR CENTER
DET DETAIL
DIST DISTRIBUTION
DP DISTRIBUTION PANEL
(D) DEMOLISH
DISC DISCONNECT
DWG DRAWING
DIA DIAMETER
DIM DIMENSION
EMT ELECTRICAL METALLIC TUBING
EP EXPLOSION PROOF
EM EMERGENCY
EQP EQUIPMENT
(E) EXISTING
ELEC ELECTRICAL
EMS EMERGENCY MANAGEMENT CONTROL SYSTEM
ENT ELECTRICAL NON-METALLIC TUBING
EPO / E.P.O EMERGENCY POWER OFF
EF EXHAUST FAN
EG EQUIPMENT GROUND
EOL END OF LINE RESISTOR
FACP FIRE ALARM CONTROL PANEL
FL FLOOR
FATC FIRE ALARM TERMINAL CABINET
FA FIRE ALARM
FLA FULL LOAD AMPS
FT / 'FEET
FIN FINISH
G / GND GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GEC GROUNDING ELECTRODE CONDUCTOR
H / HGT HEIGHT
HOA HAND OFF AUTO
HP HORSEPOWER
HACR HEATING AIR CONDITIONING REFRIGERATION
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HPS HIGH PRESSURE SODIUM
HID HIGH INTENSITY DISCHARGE
IC INTERCOM
IDF INTERMEDIATE DISTRIBUTION FRAME
IN / "INCHES
IMC INTERMEDIATE METAL CONDUIT
IP INTERNET PROTOCOL
IG ISOLATED GROUND
JB / JBOX JUNCTION BOX
KAIC KILOAMPERE INTERRUPTING CAPACITY
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
KWH KILOWATT HOUR
LTG / LTS LIGHTING
LV LOW VOLTAGE
LF LINEAR FEET
KCMIL / MCM THOUSAND CIRCULAR MILS
MAX MAXIMUM
MDF MAIN DISTRIBUTION FRAME
MECH MECHANICAL
MH MANHOLE
MTD MOUNTED
MTG MOUNTING
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT CIRCUIT PROTECTION
MCA MINIMUM CIRCUIT AMPERES
M.H. METAL HALIDE
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
M METER
MV MERCURY VAPOR
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO. / #NUMBER
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MFR ASSOCIATION
NF NON-FUSED
NL NIGHT LIGHT
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISH, CONTRACTOR INSTALLED
P POLE
PB PULL BOX
PF POWER FACTOR
PA PUBLIC ADDRESS
PH /ø PHASE
PNL PANEL
PRIMARY OVER 600 VOLTS
PC PHOTOCELL
PDU POWER DISTRIBUTION UNIT
PROVIDE FURNISH, INSTALL AND/OR CONNECT
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
REQD REQUIRED
REQT(S) REQUIREMENT(S)
RM ROOM
RMS ROOT MEAN SQUARE
RGS RIGID GALVANIZED STEEL CONDUIT
RECEPT RECEPTACLE
SHT SHEET
SW SWITCH
SWBD SWITCHBOARD
STC SIGNAL TERMINAL CABINET
SCC SHORT CIRCUIT CURRENT
SFD SMOKE FIRE DAMPER
SECONDARY 600 VOLTS AND LESS
SQ SQUARE
TEL TELEPHONE
TYP TYPICAL
TC TIMECLOCK
TEL/DAT TELEPHONE AND DATA
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
UL UNDERWRITERS LABORATORIES
UON / U.O.N. UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTAGE
VA VOLT AMPERES
VD VOLTAGE DROP
VAV VARIABLE AIR VOLUME
W WATTAGE OR WIRE
WP WEATHERPROOF
WAP WIRELESS ACCESS POINT
XFMR TRANSFORMER
X / (X) EXISTING
XL / (XL) EXISTING TO BE RELOCATED
XR / (XR) EXISTING TO BE REMOVED
XN / (XN) EXISTING NEW LOCATION
%Z PERCENTAGE IMPEDANCE
WT WEIGHT
WH WATER HEATER
VFD VARIABLE FREQUENCY DRIVE
UGPS UNDERGROUND PULL SECTION
TEMP TEMPERATURE OR TEMPORARY
SWGR METAL CLAD SWITCHGEAR
SPEC SPECIFICATIONS
REC RECESSED
REFRIG REFRIGERATOR
QTY QUANTITY
PWR POWER
N / NEUT NEUTRAL
LBS POUNDS
KS KNEE SPACE
HR HOUR OR HOME RUN
HZ HERTZ
GC GENERAL CONTRACTOR
GALV GALVANIZED
EC ELECTRICAL CONTRACTOR
CU COPPER
CCTV CLOSED CIRCUIT TELEVISION
AL ALUMINUM
AC ALTERNATING CURRENT
A/C AIR CONDITIONING
DC DIRECT CURRENT
EA EACH
EXO DISCONNECT SWITCH
SINGLE LINE LEGEND
ELECTRONIC METERING UNIT
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
DRAWOUT CIRCUIT BREAKER
AMP FRAME
AMP TRIP
POLE CONFIGURATION
ELECTRONIC TRIP FUNCTIONS
FUSE
TRANSFORMER
100AF
100AT
3
LSIG
100AS
100AF
3
CIRCUIT BREAKER
100AF
100AT
3
LSIG
GROUNDING ELECTRODE
100AF
100AT
3
LSIG
C
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
COIL
SHUNT TRIPST
SOLID STATESS
XXXX
PANEL
HL1
TRANSIENT VOLTAGE SURGE SUPPRESSIONTVSS
M
+
-
PHOTOVOLTAIC PANEL (PV PANEL)
AMP FRAME
AMP TRIP
POLE CONFIGURATION
ELECTRONIC TRIP FUNCTIONS
FUSED SWITCH
AMP SWITCH
AMP FUSE
POLE CONFIGURATION
ENCLOSED CIRCUIT BREAKER
AMP FRAME
AMP TRIP
POLE CONFIGURATION
ELECTRONIC TRIP FUNCTIONS
+
-
+
-
FEEDER TAG
AUTOMATIC TRANSFER SWITCH
PACKAGE ENGINE GENERATOR
PANEL BOARD
STRINGER INVERTER
EQUIPMENT LEGEND
LIGHT FIXTURE DESIGNATIONF1
HL1-13
(R1)
LIGHTING BRANCH CIRCUIT
RELAY DESIGNATION IN LIGHTING IN CONTROL PANEL
M
HEAVY DUTY NON-FUSED DISCONNECT
HEAVY DUTY FUSED DISCONNECT
MOTOR STARTER, HOA, AUX CONTACTS, CPT, PILOT LIGHTS
COMBINATION MOTOR STARTER, HOA, AUX CONTACTS, CPT,
PILOT
LIGHTS, WITH FUSED DISCONNECT SWITCH
MECHANICAL EQUIPMENT TAG
MOTOR RATED SWITCH
SURFACE MOUNTED PANEL BOARD OR ELECTRICAL CABINET
DISTRIBUTION SWITCHBOARD OR PANEL BOARD
FLUSH MOUNTED PANEL BOARD OR ELECTRICAL CABINET
VARIABLE FREQUENCY DRIVE. CONFIRM INTEGRAL
DISCONNECTING
MEANS WITH MECHANICAL
AHU
1
F
VFD
T TRANSFORMER
EMERGENCY POWER OFF BUTTONEPO
SFD SMOKE FIRE DAMPER
MOTOR
S
S
FLUSH MOUNTED HALF HOT DUPLEX RECEPTACLE MOUNTED AT
+15" AFF TO BOTTOM OF BOX U.O.N
XX
HALF SHADED WIRING INDICATES
CONTROLLED
RECEPTACLE PER TITLE 24 SECTION 130.5(d)
POWER LEGEND
FLUSH MOUNTED DUPLEX RECEPTACLE MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.O.N
FLUSH MOUNTED QUAD RECEPTACLE MOUNTING HEIGHT TO
BOTTOM OF BOX PER ARCHITECT ELEVATION
SURFACED MOUNTED DUPLEX RECEPTACLE MOUNTED AT +15" AFF
TO BOTTOM OF BOX U.O.N
SURFACE MOUNTED QUAD RECEPTACLE MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.O.N
FLUSH MOUNTED SINGLE RECEPTACLE MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.O.N
SURFACE MOUNTED SINGLE RECEPTACLE MOUNTED AT +15" AFF
TO BOTTOM OF BOX U.O.N
CEILING MOUNTED DUPLEX RECEPTACLE
CEILING MOUNTED QUAD RECEPTACLE
FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE
FLUSH FLOOR BOX WITH QUAD RECEPTACLE
FLUSH FLOOR BOX WITH COMBINATION DUPLEX RECEPTACLE AND
DATA OUTLET
FLUSH FLOOR BOX WITH COMBINATION QUAD RECEPTACLE AND
DATA OUTLET
FIRE RATED POKE THRU WITH DUPLEX RECEPTACLE
FIRE RATED POKE THRU WITH QUAD RECEPTACLE
FIRE RATED POKE THRU WITH DUPLEX RECEPTACLE AND DATA
OUTLET
FIRE RATED POKE THRU WITH QUAD RECEPTACLE AND DATA
OUTLET
XX
FLUSH MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLE
MOUNTED AT +15" AFF TO BOTTOM OF BOX U.O.N
SURFACE MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLE
MOUNTED AT +15" AFF TO BOTTOM OF BOX U.O.N
FLUSH MOUNTED JUNCTION BOX MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.O.N
SURFACE MOUNTED JUNCTION BOX MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.O.N
FLUSH FLOOR MOUNTED JUNCTION BOX
CEILING MOUNTED JUNCTION BOX
J
GFCI
IG
S
H
AC
GROUND FAULT CIRCUIT INTERRUPTER
ISOLATED GROUND
SURGE SUPPRESSOR
HORIZONTAL MOUNTED
MOUNT ABOVE COUNTER PER
ARCHITECT ELEVATION
PROVIDED WITH INTREGRAL USB
PORTS
RECEPTACLE CONTROLLED PER TITLE
24 202 SECTION 130.5(d)
CLOCK TYPE
=
=
=
=
CEILING MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLE
FLOOR MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLE
=
=RC
=C
FLUSH MOUNTED DUPLEX RECEPTACLE MOUNTING HEIGHT TO
BOTTOM OF BOX PER ARCHITECT ELEVATION
SURFACED MOUNTED DUPLEX RECEPTACLE MOUNTED AT
COUNTER LEVEL PER ARCHITECT ELEVATION
SURFACE MOUNTED QUAD RECEPTACLE MOUNTING TO BOTTOM
OF BOX PER ARCHITECT ELEVATION
FLUSH MOUNTED QUAD RECEPTACLE MOUNTED AT +15" AFF TO
BOTTOM OF BOX U.O.N
=USB
RECEPTACLE POWER PACK MOUNTED IN ACCESSIBLE CEILING
SPACE FOR AUTOMATIC CONTROL OF RECEPTACLE DEVICE
J
J
J
RC
XX-XXX
XX-XXX
XX-XXX
XX-XXX
W
1. CONTRACTOR TO OBTAIN PERMISSION FOR ACCESS TO THE SITE FROM THE
OWNER OR DESIGNATED OWNER REPRESENTATIVE TO VISIT THE SITE INCLUDING
ALL AREAS OF WORK PRIOR TO BID. CONTRACTOR TO BE FAMILIARIZED WITH
EXISTING CONDITIONS, VERIFY SAID CONDITIONS, DIMENSIONS, AND ROUTINGS
PRIOR TO START OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO OWNER /
ARCHITECT / ENGINEER WITHIN 48 HOURS OF DISCREPANCIES FOUND.
2. CONTRACTOR SHALL CONFIRM ACCURACY OF PANEL BOARD INFORMATION PRIOR
TO START OF WORK. REPORT ANY DISCREPANCIES TO OWNER / ARCHITECT /
ENGINEER WITHIN 48 HOURS OF DISCREPANCIES FOUND.
3. ALL WORK SHOWN IS NEW UNLESS OTHERWISE NOTED.
4. ALL AREAS OUTSIDE THE SCOPE OF WORK SHALL BE PROTECTED IN PLACE AND
REMAIN INTACT, U.O.N.
5. CONTRACTOR TO COORDINATE WITH OWNER ANY SHUTDOWN OF ELECTRICAL
EQUIPMENT WITH 7 DAYS NOTIFICATION. CONTRACTOR TO INCLUDE OFF HOURS IN
PRICING FOR THIS WORK.
6. ALL ELECTRICAL MATERIAL AND EQUIPMENT SHALL BE NEW BEARING A UL LISTING
OR ACCEPTABLE NRTL LISTING FROM THE LOCAL AREA JURISDICTION.
7. CONTRACTOR SHALL COMPLY WITH THE CURRENT VERSION OF THE CALIFORNIA
ELECTRICAL CODE 202 , STATE, LOCAL CODES, ORDINANCES, AND REGULATIONS.
8. WORK SHALL BE PERFORMED IN A SAFE MANNER AND NOT DISTURB OR AFFECT
EXISTING BUILDING UTILITIES, OCCUPANTS, OR FINISHES WITHOUT PRIOR NOTICE
AND APPROVAL FROM OWNER.
9. ALL CONDUIT RUN SHALL BE FIELD COORDINATED, LOCATE CONDUITS CLEAR OF
OTHER TRADES, DOOR ACCESS, OR OTHER OBSTRUCTIONS. COORDINATE
CONDUIT RUNS WITH OTHER TRADES PRIOR TO COMMENCEMENT OF WORK.
10. RUN ALL CONDUITS CONCEALED IN CEILING AND WALL SPACES, U.O.N. TO BE
SURFACE MOUNTED. ALL CONDUIT PATHWAYS MUST MAINTAIN 6 INCHES CLEAR OF
SOURCES OF HEAT, SUPPORT CONDUITS FROM STRUCTURE.
11. ALL BRANCH CIRCUITS TO BE PROVIDED WITH SEPARATE GREEN GROUND
INSULATED CONDUCTOR.
12. ALL BRANCH CIRCUITS TO BE PROVIDED WITH SEPARATE WHITE NEUTRAL
INSULATED CONDUCTOR. SHARED NEUTRAL IS ACCEPTABLE IF COMMON HANDLE
TIE CIRCUIT BREAKERS ARE UTILIZED TO SIMULTANEOUSLY DISCONNECT ALL
UNGROUNDED CONDUCTORS PER NEC 210.4(B).
13. PROVIDE IDENTIFICATION TAGS FOR ALL WIRING, INSTALL TAGS AT END OF RUNS,
INTERMEDIATE PULL BOXES, JUNCTION BOXES, CABINETS, ETC.
14. BRANCH CIRCUIT VOLTAGE DROP NOT TO EXCEED 3% FROM PANEL BOARD
SOURCE.
15. LABEL ALL CIRCUIT BREAKERS IN ALL ELECTRICAL DISTRIBUTION PANELS AND
SWITCHBOARDS. PROVIDE TYPE WRITTEN CIRCUIT DIRECTORY CARDS FOR ANY
PANEL BOARD HAVING CIRCUIT MODIFICATIONS.
16. PROVIDE P-TOUCH LABELS ON ALL NEW OUTLETS, RACKS, PLUG MOLD, AND
SWITCHES.
17. ALL CONDUITS PENETRATING ELECTRICAL/MECHANICAL SPACES OF RATED
WALLS SHALL BE SEALED AND FIRE STOPPED.
18. ALL ELECTRICAL PENETRATIONS INTO COOLER OR FREEZER UNITS SHALL BE
SEALED PER CEC SECTION 300-7.
19. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL
BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THE
ELECTRICAL EQUIPMENT PER CEC 110.26(E) (1).
20. THE ENGINEER OF RECORD TAKES NO EXCEPTION TO THE USE OF MC CABLE
WHERE ALLOWED BY CEC SECTION 330 AND PROVIDED MC CABLE IS ACCEPTABLE
BY BUILDING OWNERSHIP.
21. CONTRACTOR SHALL REVIEW THE ARCHITECTURAL PLANS FOR NOTES OR
DIRECTIVES THAT CONCERN ELECTRICAL INSTALLATIONS AND DETAILS.
22. CONDUIT/WIRING IS NOT PERMITTED TO BE INSTALLED ON THE ROOF OF A
BUILDING AND WIRING ON THE EXTERIOR OF A BUILDING REQUIRES APPROVAL BY
THE BUILDING OFFICIAL.
GENERAL PROJECT NOTES
PHOTOVOLTAIC LEGEND
DC TO AC STRING INVERTER
POTENTIAL INDUCED DEGRATION (PID) ENERGY BALANCER CABINET
PHOTOVOLTAIC MODULE PANEL (PV PANEL)
PHOTOVOLTAIC ARRAY (PV ARRAY)
STRING NUMBER DESIGNATION
INVERTER NUMBER DESIGNATIONS#.#
PID
WIRING LEGEND
RACEWAY EXPOSED
RACEWAY TURNED UP
RACEWAY TURNED DOWN
RACEWAY CAPPED AND STUBBED.PROVIDE PERMANENT GROUND
MARKER FOR UNDERGROUND INSTALLATIONS
BRANCH CIRCUIT RACEWAY HOME RUN BACK TO ELECTRICAL
EQUIPMENT AS NOTED
BRANCH CIRCUIT RACEWAY WITH 3#12, 1#12N, 1#12GND, 3/4"C.
MAXIMUM THREE BRANCH CIRCUITS PER HOME RUN, U.O.N.
BRANCH CIRCUIT RACEWAY WITH 3#10, 1#10N, 1#10GND, 3/4"C.
MAXIMUM THREE BRANCH CIRCUITS PER HOME RUN, U.O.N.
CABLE TRAY
POINT OF CONNECTION TO EQUIPMENT
SURFACE MOUNTED WIRE MOLD RACEWAY SYSTEM.
X = 1, 2 OR 3 CHANNEL RACEWAY
BRANCH CIRCUIT RACEWAY TO BE DEMOLISH
BRANCH CIRCUIT RACEWAY CONCEALED IN WALL OR CEILING
BRANCH CIRCUIT RACEWAY CONCEALED IN FLOOR OR
UNDERGROUND
L1-1
#10
WMX
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO.CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
3
6
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
23008.00
E001
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
COVER SHEET
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
NOTE:
1.) ON/OFF TIME TO BE DETERMINED BY FACILITY OPERATORS.
EXISTING LIGHTING CONTROL PANEL 'LCP'
RELAY SOURCE
PANEL CIRCUIT INPUT
VOLTAGE
OVERRIDE
ZONE CONTROLLER LOCATION CONTROLLED ZONE ON/OFF TIME PHOTOCELL NOTES
1 2LA 1 277 R1, R2 2ND FLR ELEC RM OPEN OFFICE 200 YES YES 1
4
2
3
5
6 SPARE - - - - - - - -
7 - - - - - - - -
8 - - - - - - - -
2LA 3 277 R3 2ND FLR ELEC RM OPEN OFFICE 200 YES NO 1
2LA 5 277 R4 2ND FLR ELEC RM OPEN OFFICE 200 YES 1
2LA 4 277 R5 2ND FLR ELEC RM OPEN OFFICE 200 YES 1
2LA 7 277 R6 2ND FLR ELEC RM STORAGE 213 YES 1
NO
NO
NO
SPARE
SPARE
LIGHT FIXTURE SCHEDULE NOTES:
1. QUANTITY COLUMN SHOWN IS FOR REFERENCE ONLY. CONTRACTOR TO CONFIRM COUNTS PRIOR TO ORDER.
2. CONTRACTOR TO VERIFY DIMMING COMPATIBILTY OF ALL FIXTURE TYPES WITH OWNER SELECTED DIMMING CONTROLS.
3. CONTRACTOR TO PROVIDE ALL REMOTE POWER SUPPLIES AND MOUNTING ACCESSORIES REQUIRED TO INSTALL A COMPLETE AND OPERATIONAL SYSTEM.
4. VERIFY ALL MOUNTING HEIGHTS AND FIXTURE LENGTHS WITH ARCHITECTURAL ELEVATIONS PRIOR TO ORDERING.
5. ALL LINEAR FIXTURES TO BE SEAMLESS WITH FULLY ILLUMINATED SECTIONS AND MATCH PATTTERN PER ARCHITECTURAL PLANS.
6. BATTERY PACKS IN EMERGENCY LIGHT FIXTURES TO BE TITLE 20 COMPLIANT.
LIGHTING FIXTURE SCHEDULE
CALLOUT
FIXTURE
IMAGE DESCRIPTION INPUT WATTS LAMP FIXTURE LUMENS EGRESS LUMENS COLOR TEMP CRI MANUFACTURER MODEL MOUNTING VOLTS DIMMING QTY
F1A EXISTING LED 2'X4' TROFFER FIXTURE 47 VA LED 6000 lm 0 lm 3500 K 80 LITHONIA 2BLT4 RECESSED 277 V 0-10V 189
F1AE EXISTING LED 2'X4' TROFFER FIXTURE,
PROVIDED WITH 10W EMERGENCY BATTERY
BACKUP.
47 VA LED 6000 lm 1275 lm 3500 K 80 LITHONIA 2BLT4
SERIES
RECESSED 277 V 0-10V 26
X1 LED EXIT SIGN, MATCH EXISTING BUILDING
STANDARD, PROVIDE 90 MINUTE EMERGENCY
BATTERY BACKUP.
5 VA LED 0 lm 0 lm 0 K - LITHONIA EDG SERIES UNIVERSAL 277 V NONE 3
X2 LED EXIT SIGN, MATCH EXISTING BUILDING
STANDARD, PROVIDE 90 MINUTE EMERGENCY
BATTERY BACKUP.
5 VA LED 0 lm 0 lm 0 K - LITHONIA EDG SERIES UNIVERSAL 277 V NONE 2
Grand total: 220 220
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
3
7
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
12" = 1'-0"23008.00
E002
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
LIGHTING SCHEDULE
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
1 LIGHTING FIXTURE SCHEDULE
SCALE: NONE
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
3
7
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
23008.00
E003
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
TITLE 24 FORMS
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
1 TITLE 24 FORMS
SCALE: NONE
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
FE
C
FEC
FE
C
OC
OC
O
O
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
210
MDF
211
OFFICE
212
(E) WOMENS
X
(E) MENS
X
(E) SHOWER
X
(E) SHOWER
X
(E) ELEC
X
(E) JAN
X
(E) ELEC
214
(E) ELEC
201
MTRL
CONVEYOR
X
OPEN OFFICE
200
XR
2PA-9
F1A
XL
F1A
XL
F1A
XL
F1A
XL
F1A
XL
F1A
XL
F1A
XL
XR
X
T-250
25
0
2L
A
2P
C
2P
D
T-2PC
1
2
3
3 3
3
3
2L
B
2P
B
2P
A
33
33
F1A
X
5
F1A
X
F1AE
X
R1
F1A
X
R2
F1A
X
R3
F1AE
X
R3
F1A
X
R3
F1A
X
R3
F1AE
X
R4
F1A
X
R4
F1A
X
R4
F1AE
X
R4
F1A
X
R5
F1A
X
R5
F1A
X
R1
F1A
X
R2
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R2
F1A
X
R1
F1AE
X
R1
F1A
X
R2
F1A
X
R3
F1AE
X
R3
F1A
X
R3
F1A
X
R3
F1AE
X
R4
F1A
X
R4
F1A
X
R4
F1AE
X
R4
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R2
F1A
X
R1
F1A
X
R1
F1A
X
R2
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R5
F1A
X
R5
F1AE
X
R1
F1A
X
R2
F1A
X
R3
F1AE
X
R3
F1A
X
R3
F1A
X
R3
F1AE
X
R4
F1A
X
R4
F1A
X
R4
F1AE
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R2
F1A
X
R1
F1A
X
R1
F1A
X
R2
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1AE
X
R1
F1A
X
R2
F1A
X
R3
F1AE
X
R3
F1A
X
R3
F1A
X
R3
F1AE
X
R4
F1A
X
R4
F1A
X
R4
F1AE
X
R4
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R3
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R4
F1A
X
R6
F1AE
X
R5
F1A
X
R5
F1A
X
R6
F1A
X
R6
F1AE
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1AE
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1AE
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1A
X
R6
F1AE
X
R6
F1A
X
R6
F1A
X
R5
F1AE
X
R5
F1AE
X
R6
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R6
F1AE
X
R5
F1A
X
R5
F1A
X
R5
F1AE
X
R5
F1AE
X
R6
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R6
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R6
F1AE
X
R5
F1A
X
R5
F1A
X
R5
F1AE
X
R5
F1AE
X
R6
F1A
X
R5
F1A
X
R5
F1A
X
R5
F1A
X
R6
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
XF1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
X
R5
6 6 6 6
6 6 6 6
6 6 6 6
6 6 6 6
6 6 6 6
6 6 6 6
6 6 6 6
6
6
X
R6
X
R1,2,3,4,5
X1
2LA-4
X
X1
2LA-7
X
11
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
3
9
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
3/32" = 1'-0"23008.00
E101
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
DEMOLITION PLAN -LEVEL 2
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
1. EXISTING LIGHT FIXTURES AND CONTROL DEVICES TO BE REMOVED IN THIS AREA,
RECEPTACLES MARKED WITH (X) ARE TO REMAIN, RECEPTACLES MARKED WITH (XR)
ARE TO BE REMOVED. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL DEMOLITIONS
SCOPE OF WORK.
2. EXISTING AREA TO REMAIN. NOT IN SCOPE OF WORK.
3. APPROXIMATE LOCATION OF EXISTING ELECTRICAL EQUIPMENT TO REMAIN.
4. NOT USED.
5. EXISTING CONTROL DEVICE TO BE REMOVED. DISCONNECT EXISTING LIGHT FIXTURE(S)
IN AREA FROM EXISTING AREA CONTROLS.
6. EXISTING LIGHT FIXTURE BE DISCONNECTED FROM EXISTING LIGHTING BRANCH
CIRCUIT AND RELAY.
3/32" = 1'-0"
DEMOLITION PLAN - LEVEL 2 1
GENERAL NOTES
1. ALL ELECTRICAL DEVICES ARE EXISTING TO REMAIN, U.O.N.
2. DEMOLISH CONDUIT AND CONDUCTORS BACK TO SOURCE PANEL OR NEAREST
EXISTING TO REMAIN JUNCTION BOX SERVING OTHER NOT IN SCOPE AREAS.
3. CONTRACTOR TO FIELD VERIFY BRANCH CIRCUITRY PRIOR TO COMMENCEMENT OF
WORK.
4. CONTRACTOR TO MAINTAIN CIRCUITRY CONTINUITY TO EXISTING SPACE OUTSIDE THIS
SCOPE OF WORK.
5. SEE ARCHITECTURAL SHEETS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
6. ELECTRICAL CONTRACTOR TO MAKE EXISTING ELECTRICAL SYSTEM SAFE FOR DEMO
CONTRACTOR. ELECTRICAL CONTRACTOR TO IDENTIFY CONDUIT SYSTEMS THAT ARE
TO REMAIN AND CAREFULLY WALK WITH DEMO CONTRACTOR EXPLAINING WHAT NEEDS
TO STAY. IT IS THE DEMO CONTRACTOR AND GENERAL CONTRACTORS RESPONSIBILITY
TO SET THIS MEETING UP AND MAKE SURE THAT THE COMMUNICATION ON WHAT STAYS
IS CRYSTAL CLEAR. ITEMS THAT STAY (FEEDERS TO PANELS ETC) SHOULD BE CLEARLY
MARKED ON SITE WITH RED PAINT. ANYTHING MARKED RED SHALL NOT BE DEMO OR
REMOVED.
SHEET KEYNOTES#
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
FE
C
FEC
FE
C
OC
OC
O
O
OC
OC
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
210
MDF
211
OFFICE
212
(E) WOMENS
X
(E) MENS
X
(E) SHOWER
X
(E) SHOWER
X
(E) ELEC
X
(E) JAN
X
(E) ELEC
214
(E) ELEC
201
MTRL
CONVEYOR
X
OPEN OFFICE
200
2LA
F1A
2LA-2
XN
F1A
2LA-2
XN
F1A
2LA-2
XN
F1A
2LA-2
XN
F1AE
2LA-1
X
R1
F1A
2LA-1
X
R2
F1A
2LA-3
X
R3
F1AE
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1AE
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1AE
2LA-5
X
R4F1A
2LA-1
X
R1
F1A
2LA-1
X
R2
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1A
2LA-1
X
R1
F1A
2LA-1
X
R2
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1AE
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1AE
2LA-5
X
R4
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1AE
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-1
X
R2
F1AE
2LA-1
X
R1
F1A
2LA-1
X
R1
F1A
2LA-1
X
R2
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1A
2LA-4
X
R5
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-1
X
R2
F1A
2LA-1
X
R1
F1AE
2LA-1
X
R1
F1A
2LA-1
X
R2
F1A
2LA-3
X
R3
F1AE
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1AE
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1AE
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-1
X
R2
F1A
2LA-1
X
R1
F1A
2LA-1
X
R1
F1A
2LA-1
X
R2
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1AE
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1AE
2LA-5
X
R4
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-1
X
R2
F1AE
2LA-1
X
R1
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-3
X
R3
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-5
X
R4
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-5
X
R4
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-2
X
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-2
XN
F1A
X
3
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
1
2
1 2
1 2
1 2
4
X
X
R1,2,3,4,5
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1A
2LA-7
X
R6
F1AE
2LA-3
X
R3
5 5 5 5
5 5 5 5
5 5 5 5
5 5 5 5
5 5 5 5
5 5 5 5
5 5 5 5
5
5
D
LCP 6
7
8
X1
2LA-7
X
X1
2LA-4
X
X2
2LA-7
X1
2LA-7
X2
2LA-7
F1A
2LA-3
XN
R3
F1A
2LA-3
XN
R3
F1A
2LA-3
R3
11
9 9 9
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
4
0
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
3/32" = 1'-0"23008.00
E201
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
LIGHTING PLAN -LEVEL 2
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
3/32" = 1'-0"
LIGHTING PLAN - LEVEL 2 1
1. CONTRACTOR TO MAINTAIN CIRCUITRY CONTINUITY TO EXISTING SPACE OUTSIDE THIS
SCOPE OF WORK.
2. SEE SHEET E002 FOR LIGHTING FIXTURE SCHEDULE.
3. SEE SHEET E501 FOR EGRESS PHOTOMETRIC CALCULATIONS.
4. SEE SHEET E701 FOR ADDITIONAL REQUIREMENTS.
5. SEE ARCHITECTURAL SHEETS FOR ADDITIONAL REQUIREMENTS.
6. PROVIDE DUAL-TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR FOR RESTROOM
AREAS.
7. DO NOT SWITCH EXIT SIGNS UNITS OR LIGHT FIXTURES LABELED "NL" (ON
CONTINUOUSLY).
8. PARTIAL "OFF" OCCUPANCY SENSOR IN CORRIDORS AND STAIRWELLS. OCCUPANCY
SENSOR TO REDUCE THE LIGHT POWER DENSITY BY 50% WHEN THE SPACE BECOMES
UN-OCCUPIED.
GENERAL NOTES
1. PRIMARY SIDE LIT DAY LIGHTING BOUNDARY ZONE.
2. SECONDARY SIDE LIT DAY LIGHTING BOUNDARY ZONE.
3. APPROXIMATE LOCATION OF EXISTING ELECTRICAL EQUIPMENT.
4. INTERCEPT AND EXTEND EXISTING LIGHTING CONTROLS IN AREA TO EXISTING LIGHT
FIXTURE AS SHOWN.
5. INTERCEPT AND EXTEND EXISTING LIGHTING BRANCH CIRCUIT AND CONTROLS TO
EXISTING LIGHT FIXTURES IN AREA AS SHOWN.
6. APPROXIMATE LOCATION OF EXISTING LIGHTING CONTROL PANEL.
7. EXISTING OVERRIDE SWITCH FOR CONTROL OF 'OPEN OFFICE 200'
8. EXISTING OVERRIDE SWITCH FOR CONTROL OF 'GROWTH 213'
9. INTERCEPT AND EXTEND EXISTING LIGHTING BRANCH CIRCUIT AND CONTROLS TO
NEW/RELOCATED LIGHT FIXTURES IN AREA AS SHOWN.
SHEET KEYNOTES#
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
FE
C
FEC
FE
C
CR
CR
CR
CR
CR
CR
CR
J J
CRCRCRCRCR
F
F
F
F
JJ JJ JJ JJ JJ JJ
JJ JJ J J J JJ J
J JJJ JJ J J J JJ J
J JJJ JJ J J J JJ J
J JJJ JJ J J J JJ J
J JJJ JJ J J J JJ J
J JJJ JJ J J J JJ J
J
J
CR
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
210
MDF
211
OFFICE
212
(E) WOMENS
X
(E) MENS
X
(E) SHOWER
X
(E) SHOWER
X
(E) ELEC
X
(E) JAN
X
(E) ELEC
214
(E) ELEC
201
MTRL
CONVEYOR
X
OPEN OFFICE
200
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
210
MDF
211
OFFICE
212
(E) WOMENS
X
(E) MENS
X
(E) SHOWER
X
(E) SHOWER
X
(E) ELEC
X
(E) JAN
X
(E) ELEC
214
(E) ELEC
201
MTRL
CONVEYOR
X
OPEN OFFICE
200
2L
A
T-250
25
0
2P
C
2P
D
T-2PC
1
1
1
1
1
1
X
2PA-5
X
2PA-5
X
2PA-5
X
2PA-5
X
2PA-5
X
2PA-7
X
2PA-7
X
2PA-7
X
2PA-7
X
2PA-7
X
2PA-9
X
2PA-9
X
2PA-9
X
2PA-9
2P
A
2P
B
11
2L
B
1
3
X
2PA-40
X
2PA-40
X
2PA-38
X
2PA-38
X
2PA-38
X
2PA-42
X
2PA-42
X
2PA-42
X
2PA-42 2PA -24
X
2PA-8
X
2PA-8
X
2PA-8
X
2PA-8
3
2PA -11
X
2PA -11
X
2PA -11
X
2PA-13
X
2PA-13
X
2PA-13
X
2PA-13
X
2PA-21
X
2PA-21
X
2PA-21
X
2PA-21
X
2PA-21
X
2PA-21
2PA-2
2PA-4
4
5
6
CU-1-1
CU-1-2
FC-1-1
FC-1-2
9
9
2PA-21,23
3/4"C,2#8,#8N,#8G
7 8
2PA-25,27
3/4"C,2#8,#8N,#8G
78 10
11
10
2PA -25,27
2PA -21,23
2PA-24
2PB-11
2PB-1,3
2PB-9
2PB-5,7
2PB-13,15
2PB-21
2PB-17,19
2PB-23
2PB-25,27
2PB-33
2PB-29,31
2PB-35
2PB-2,4 2PB-10 2PB-6,8
2PB-12
2PB-14,16
2PB-22
2PB-18,20
2PB-24
2PB-30,32
2PB-26,28
2PB-34
2PB-36
2PC-5,72PC-1,3
2PC-9
2PC-11
2PC-13,15
2PC-21
2PC-17,19
2PC-23
2PC-25,27
2PC-33
2PC-29,31
2PC-35
2PC-45
2PC-37,39
2PC-41,43
2PC-47
2PC-61,63
2PC-71
2PC-65,67
2PC-69 2PC-16
2PC-12,14
2PC-18
2PC-8,10
2PC-24,26
2PC-28
2PC-20,22
2PC-30
2PC-32,34
2PC-40
2PC-36,38
2PC-42
2PC-44,46
2PC-52
2PC-48,50
2PC-54
2PD-23
2PD-17,19
2PD-13,15 2PD-21
2PD-11
2PD-5,7
2PD-9
2PD-1,3
2PC-66
2PC-60,62
2PC-64
2PC-56,58
2PD-6
2PD-2,292PD-42PD-25,27
2PD-12,14
2PD-18
2PD-162PD-8,10
2PD-28
2PD-24,26
2PD-30
2PD-20,22
2PA-29
GFCI
WP
12
2 TYP.
2 TYP.
2 TYP.
2 TYP.
2 TYP.
2 TYP.
2 TYP.
11
2PA-22
13
2PA -22
13
2PB-40
11
14
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
4
1
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
3/32" = 1'-0"23008.00
E301
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
POWER PLAN -LEVEL 2
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
3/32" = 1'-0"
POWER PLAN - LEVEL 2 1
1. SEE ARCHITECTURAL SHEETS FOR ADDITIONAL REQUIREMENTS.
2. COORDINATE WITH TENANT IT PERSONNEL FOR DEVICE LOCATIONS PRIOR TO ROUGH
IN.
3. SEE MECHANICAL AND PLUMBING DRAWINGS FOR ADDITIONAL REQUIREMENTS.
4. DATA DEVICE LOCATIONS TO BE MOUNTED ADJACENT TO POWER WIRE DEVICE AT SAME
ELEVATION, U.O.N.
5. PROVIDE RING AND STRING FROM DATA DEVICE LOCATION TO ACCESSIBLE CEILING
SPACE.
6. CONTRACTOR TO PROVIDE P-TOUCH LABELS ON ALL TENANT WIRING DEVICES
INCLUDING PANEL NAME AND CIRCUIT DESIGNATION.
7. ALL WIRING DEVICES 15 TO 20 AMPERE INSTALLED IN KITCHENS OR WITHIN 6' OF SINK
OUTSIDE EDGES SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
(GFCI) PER CEC 210.8(B).
8. PROVIDE #10 CONDUCTOR SERVING MODULAR FURNITURE SYSTEMS AND MODULAR
FURNITURE EQUIPMENT..
9. SEE ARCHITECTURALLY DRAWINGS FOR DIMENSIONED LOCATIONS OF POKE THRU
DEVICES PRIOR TO ROUGH IN.
10. CONTRACTOR TO MAINTAIN CIRCUITRY CONTINUITY TO EXISTING SPACE OUTSIDE THIS
SCOPE OF WORK.
GENERAL NOTES
1. APPROXIMATE LOCATION OF EXISTING ELECTRICAL EQUIPMENT TO REMAIN.
2. PROVIDE NEW TWO CHANNEL POWER POLE FOR POWER AND DATA, POWER POLE TO
MATCH EXISTING BUILDING STANDARDS. PROVIDE #10 CONDUCTORS TO POWER
POLES AND MODULAR FURNITURE EQUIPMENT. VERIFY WITH ARCHITECT FOR EXACT
LOCATIONS PRIOR TO ROUGH IN.
3. EXISTING AREA TO REMAIN NO NEW SCOPE OF WORK.
4. INTERCEPT AND EXTEND EXISTING CONVENIENCE RECEPTACLE BRANCH CIRCUIT FOR
CONNECTION TO NEW DUPLEX RECEPTACLE.
5. PROVIDE RECESSED DUAL-GANG OUTLET FOR TV. VERIFY HEIGHT WITH ARCHITECT
PRIOR TO ROUGH-IN.
6. PROVIDE COMBINATION POWER/DATA/AV POKE THRU DEVICE (MANUFACTURER
WIREMOLD SERIES 6AT). PROVIDE 1-1/2"C.O. WITH PULL STRING FOR A/V FROM TV
WALL JUNCTION BOX, DOWN WALL VOID SPACE, AND INTO POKE-THRU DEVICE.
COVER PLATE FINISH BY ARCHITECT PRIOR TO ROUGH IN. PROVIDE ALL NECESSARY
COMPONENTS FOR A COMPLETE INSTALLATION.
7. APPROXIMATE LOCATION OF NEW MECHANICAL UNIT SHOWN THROUGH FROM ROOF
FOR REFERENCE. SEE MECHANICAL SHEETS FOR ADDITIONAL REQUIREMENTS.
8. PROVIDE 60 AMP, 250V, 1-PHASE, HEAVY DUTY, NEMA 3R, FUSED DISCONNECT SWITCH
WITH 40 AMP FUSES. COORDINATE FINAL FUSE TYPE AND SIZE WITH EQUIPMENT
NAMEPLATE PRIOR TO ROUGH IN.
9. PROVIDE 3/4" C.O. FOR LINE VOLTAGE CONTROL WIRES TO FAN COIL UNIT. LINE
VOLTAGE CONTROL WIRES TO BE PROVIDED AND INSTALLED BY MECHANICAL
CONTRACTOR.
10. PROVIDE 60 AMP, 250V, 1-PHASE, NEMA 1, FUSED DISCONNECT SWITCH WITH 40 AMP
FUSES. COORDINATE FINAL FUSE TYPE AND SIZE WITH EQUIPMENT NAMEPLATE PRIOR
TO ROUGH IN.
11. PROVIDE 3/4" C.O. FOR LINE VOLTAGE CONTROL WIRES TO ROOFTOP CONDENSING
UNIT. LINE VOLTAGE CONTROL WIRES TO BE PROVIDED AND INSTALLED BY
MECHANICAL CONTRACTOR.
12. ELECTRICAL CONTRACTOR TO PROVIDE STANCHION MOUNTED WEATHER RESISTANT,
GFCI AND EXTRA DUTY LISTED WORK RECEPTACLE WITHIN 25'-0" OF EQUIPMENT ON
ROOF.
13. APPROXIMATE LOCATION OF NEW CONDENSATE PUMP. COORDINATE EXACT POINT
OF CONNECTION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
14. APPROXIMATE LOCATION OF NEW DRINKING FOUNTAIN. PROVIDE GFCI CIRCUIT
BREAKER. SEE ELECTRICAL PANEL SCHEDULE. COORDINATE EXACT POINT OF
CONNECTION WITH PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.
SHEET KEYNOTES#
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
1.2
1.7
1.2
1.7
1.2
1.7
1.1
1.5
1.0
1.3
0.8
1.0
0.7
0.9
0.6
0.8
0.6
0.7
0.6
0.7
0.7
0.8
0.7
0.9
0.9
1.1
1.0
1.3
1.2
1.6
1.3
1.8
1.3
1.8
1.3
1.8
1.2
1.6
1.0
1.4
1.7
2.1
2.4
2.5
2.2
1.8
0.9
1.1
1.4
1.6
1.8
1.8
1.7
1.4
0.8
1.0
1.1
0.8
0.8
0.9
0.3
0.3
0.7
0.8
0.9
0.4
0.4
0.8
0.8
0.9
0.5
0.5
0.8
0.9
1.0
0.7
0.6
1.0
1.1
1.2
0.9
0.7
1.1
1.3
1.5
1.2
1.0
0.7
0.7
0.7
0.7
0.8
1.0
1.4
1.9
2.7
3.5
0.6
0.6
0.7
0.8
1.0
1.4
2.0
2.9
3.8
4.3
4.2
0.8
0.7
0.7
0.8
0.9
1.1
1.4
1.9
2.6
3.4
0.7
0.6
0.7
0.8
1.0
1.4
2.0
2.8
3.6
4.1
4.0
0.8
0.8
0.8
0.7
0.7
0.9
0.9
0.9
0.8
0.8
1.0
1.0
1.1
0.9
0.9
1.1
1.2
1.3
1.1
1.0
1.2
1.4
1.6
1.4
1.2
1.4
1.6
2.0
1.8
1.4
1.6
1.9
2.4
2.2
1.7
1.7
2.1
2.7
2.5
1.8
1.7
2.1
2.8
2.7
1.9
1.7
2.1
2.7
2.5
1.8
1.6
1.9
2.4
2.2
1.6
1.4
1.6
1.9
1.8
1.4
1.2
1.4
1.6
1.4
1.1
1.1
1.2
1.3
1.1
0.9
1.0
1.0
1.1
0.9
0.8
0.9
0.9
1.0
0.8
0.7
0.9
0.9
1.0
0.8
0.7
0.9
1.0
1.1
0.9
0.8
1.0
1.1
1.2
1.1
0.9
1.2
1.3
1.5
1.3
1.1
1.3
1.6
1.9
1.7
1.3
1.5
1.8
2.3
2.1
1.6
1.6
2.0
2.7
2.5
1.7
1.6
2.1
2.8
2.6
1.8
1.6
2.0
2.7
2.4
1.7
1.5
1.8
2.3
2.1
1.5
1.3
1.5
1.9
1.6
1.2
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
210
MDF
211
OFFICE
212
(E) WOMENS
X
(E) MENS
X
(E) SHOWER
X
(E) SHOWER
X
(E) ELEC
X
(E) JAN
X
(E) ELEC
214
(E) ELEC
201
MTRL
CONVEYOR
X
OPEN OFFICE
200
11
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
4
1
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
3/32" = 1'-0"23008.00
E501
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
EMERGENCY EGRESS PLAN -
LEVEL 2
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
3/32" = 1'-0"
EMERGENCY EGRESS PLAN - LEVEL 2 1
AVERAGE FOOT-CANDLES
MAXIMUM FOOT-CANDLES
MINIMUM FOOT-CANDLES
MINIMUM TO MAXIMUM FC RATIO
MAXIMUM TO MINIMUM FC RATIO
AVEREGE TO MINIMUM FC RATIO
EGRESS PHOTOMETRIC
SCHEDULE
1.41
4.3
0.3
0.07
14.54
4.77
1. VALUE SHOWN FOR EGRESS POINT BY POINT ARE IN FOOT-CANDLE MEASUREMENTS.
2. DO NOT SWITCH EXIT SIGNS UNITS (ON CONTINUOUSLY).
3. THE MEANS OF EGRESS SHALL BE ILLUMINATED AT ALL TIMES BUILDING SPACE IS
SERVED, IN ACCORDANCE WITH CA. BUILDING CODE, SECTION 1006 AND 1011.5.
4. MEANS OF EGRESS ILLUMINATION LEVEL SHALL BE NOT LESS THAN 1-FOOT CANDLE AT
THE WALKING SURFACE AND EQUIPPED WITH MINIMUM 90 MINUTE BATTERY BACKUP
WHERE REQUIRED.
5. ADDITIONAL ILLUMINATION EXIT SIGNS MAY BE REQUIRED BY FIRE DEPARTMENT TO
ADEQUATELY INDICATE PATH OF EGRESS.
GENERAL NOTES
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
1 2
3 4
ON
OFF
1 2
3 4
ON
OFF
1 2
3 4
ON
OFF
PRODUCT LEGEND
PRODUCT NUMBER DESCRIPTION
NWSX PDT LV DX WH 1 CHANNEL ON/OFF TOGGLE, DIMMING WITH INTEGRSL DUAL TECHNOLOGY
OCCUPANCY SENSOR
NPODM DX WH 1 CHANNEL ON/OFF TOGGLE, RAISE/LOWER DIMMING
NPODM 2P DX WH 2 CHANNEL ON/OFF TOGGLE, RAISE/LOWER DIMMING
NPODM 4P DX WH 4 CHANNEL ON/OFF TOGGLE, RAISE/LOWER DIMMING
NOPD GFX WH SCENE CONTROLLER WITH 16 CHANNEL DIMMING CONTROL
NCM ADCX DZ AUTOMATIC DIMMING CONTROL PHOTOCELL - SEILING MOUNT, LOW VOLTAGE DUAL
ZONE (NO WIRES)
NCM 10 STANDARD RANGE 360 DEGREE SENSOR-CEILING MOUNT, LOW VOLTAGE, PIR
OCCUPANCY SENSOR
NCM PDT 10 STANDARD RANGE 360 DEGREE SENSOR-CEILING MOUNT, LOW VOLTAGE, DUAL
TECHNOLOGY (PDT)
NPP16 PL T24 16 AMP RELAY PACK FOR PLUG LOAD CONTROL; CHASE NIPPLE MOUNTING
NPP16 D 16 AMP RELAY PACK FOR 0-10V DIMMING CONTROL; CHASE NIPPLE MOUNTING
NPP16 D ER 16 AMP RELAY PACK FOR 0-10V DIMMING CONTROL WITH UL 924 EM SHUNT; CHASE
NIPPLE MOUNTING
NSP5 PCD 2W 120/277V, 5 AMP RELAY PACK FOR 2 WIRE INCANDESCENT DIMMING CONTROL
NSP5 PCD ELV 120 120/277V, 5 AMP RELAY PACK FOR ELECTRIC LOW VOLTAGE DIMMING CONTROL
NSP5 PCD MLV 120/277V, 5 AMP RELAY PACK FOR MAGNETIC LOW VOLTAGE DIMMING CONTROL
LIGHT FIXTURE
CAT 5
NLITE ENABLE LIGHT FIXTURE
(EMERGENCY)
CAT 5
CAT 5CAT 5
CAT 5
CAT 5
CAT 5
CAT 5
CAT 5
NCM ADCX DZ NCM PDT 9
NPODM 4P
DX WM
NLITE ENABLE LIGHT FIXTURE
(EMERGENCY)
PRIMARY DAYLIT
ZONE
SECONDARY DAYLIT
ZONE
NPODM 4P
DX WM
NPP16 D
J
B
O
X
NEUTRAL (WHITE)
LINE (BLACK/ORANGE)
J
B
O
X
NPP16 D H N
277V LTG BRANCH CKT
0-
1
0
V
D
I
M
M
I
N
G
(
V
I
O
L
E
T
)
0-
1
0
V
D
I
M
M
I
N
G
(
G
R
E
Y
)
LO
A
D
(
B
L
U
E
)
0-
1
0
V
D
I
M
M
I
N
G
(
V
I
O
L
E
T
)
0-
1
0
V
D
I
M
M
I
N
G
(
G
R
E
Y
)
LO
A
D
(
B
L
U
E
)
0-
1
0
V
D
I
M
M
I
N
G
(
V
I
O
L
E
T
)
0-
1
0
V
D
I
M
M
I
N
G
(
G
R
E
Y
)
LO
A
D
(
B
L
U
E
)
NPODM 4P
DX WM
OR
NWSX PDT
LV DX WH
CAT 5
CAT 5
CAT 5
CAT 5
CAT 5
CAT 5
CAT 5
CAT 5
PRIMARY DAYLIT
ZONE
SECONDARY DAYLIT
ZONE
NLITE ENABLE LIGHT
FIXTURE
NLITE ENABLE LIGHT
FIXTURE
NLITE ENABLE LIGHT
FIXTURE
NLITE ENABLE LIGHT
FIXTURE
NLITE ENABLE LIGHT
FIXTURE
NLITE ENABLE LIGHT
FIXTURE
H N
277V LTG BRANCH CKT
NCM PDT 9NCM ADCX DZ
H N
277V LTG BRANCH CKT
NPP16 D
J BOX
FROM LINE (BLACK/ORANGE)
FROM BUILDING NEUTRAL (WHITE)
TO LOAD (BLUE)
CAT 5
CAT 5
CAT 5
CAT 5
NPODM
DX WM
NPODM
DX WM
NCM 10
NLITE ENABLE LIGHT FIXTURE
(EMERGENCY)
TO 0-10V DIMMING BALLAST (GREY)
TO 0-10V DIMMING BALLAST (VIOLET)
LARGE OPEN OFFICE AREA DIAGRAM PRIVATE OFFICES / CONFERENCE ROOMS / SUPPORT SPACES HALLWAY DIAGRAM
ON/OFF
ON/OFF
GENERAL NOTES:
1. ALL LIGHTING CONTROL PRODUCT ARE SPECIFIED AROUND ACUITY BRANDS CONTROLS, U.O.N. OR EQUAL CONTROL
MANUFACTURERS ARE AVAILABLE. CONTRACTOR TO PROVIDE ALL COMPONENTS NECESSARY FOR A COMPLETE AND
OPERATIONAL SYSTEM.
2. SEE LIGHTING FLOOR PLAN FOR FIXTURE TYPES, CONTROL DEVICE LOCATIONS, AND ADDITIONAL REQUIREMENTS.
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
4
2
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
12" = 1'-0"23008.00
E701
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
LIGHTING CONTROL DETAILS
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
SCALE: 12" = 1'-0"
LIGHTING CONTROL DETAILS1
4000 AF
4000 AT
3P
M
EXISTING SCE CONDUIT AND
CONDUCTORS
SCE EXISTING
12KV CIRCUIT
EXISITNG SCE
PADMOUNT
TRANSFORMER
UGPS
4000A
EXISTING
SWITCHBOARD 'MS2' 4000A, 480/277V, 3Ø, 4W
NG
UGPS
4000A
EXISTING
SWITCHBOARD 'MS1' 2000A, 480/277V, 3Ø, 4W
TO EXISTING
SWITCHBOARD 'MSB1'
EXISTING
FEEDER
EXISTING SCE CONDUIT AND
CONDUCTORS
NG
2000 AF
2000 AT
3P
LSIG
SPARE
EXISTING
FEEDER
2000 AF
2000 AT
3P
LSIG
EXISTING
SWITCHBOARD 'MSB' 2000A, 480/277V, 3Ø, 4W
EXISTING
FEEDER
1200 AF
1000 AT
3P
EXISTING
FEEDER
ATS-3/EDB3
SPARE
2000 AF
2000 AT
3P
M
2000 AF
2000 AT
3P
LSIG
EXISTING
FEEDER
ATS-UPS
SPARE
400 AF
200 AT
3P
EXISTING
FEEDER
800 AF
800 AT
3P
600 AF
600 AT
3P
EXISTING
PANEL
2LB
400 AF
400 AT
3P
EXISTING
FEEDER
EXISTING
PANEL
1LA
EXISTING
DISTRIBUTION BOARD 'DPA' 800A, 480/277V, 3Ø, 4W
400 AF
400 AT
3P
EXISTING
FEEDER
SPARE
100 AF
100 AT
3P
EXISTING
FEEDER
EXISTING
PANEL
2LA
175 AF
175 AT
3P
EXISTING
FEEDER
200 AF
200 AT
3P
EXISTING
FEEDER
EXISTING
PANEL
WLA
100 AF
100 AT
3P
EXISTING
PANEL
EV1
200 AF
200 AT
3P
EXISTING
FEEDER
EXISTING
PANEL
WLB
EXISTING
XFMR 'T-1'
150KVA
480-208Y/120V
NEMA 1EXISTING
EXISITNG
FEEDER
EXISTING
FEEDER
EXISTING
FEEDER
EXISTING
FEEDER
EXISTING
WIREWAY
EXISTING
PANEL
2PA
EXISTING
FEEDER
EXISTING
PANEL
2PB
EXISTING
PANEL
1PA
EXISTING
FEEDER
EXISTING
PANEL
1PB
200 AF
200 AT
3P
F
200 AF
200 AT
3P
F
EXISTING
FEEDER
EXISTING
FEEDER
EXISTING
XFMR 'T-1PF'
75 KVA
480-208Y/120V
NEMA 1EXISTING
EXISITNG
FEEDER
EXISTING
FEEDER
EXISTING
XFMR 'T-1PC'
---KVA
480-208Y/120V
NEMA 1EXISTING
EXISTING
FEEDER
EXISTING
PANEL
1PC
EXISTING
FEEDER
EXISTING
PANEL
EW1PB
(1PD)
EXISTING
FEEDER
EXISTING
PANEL
1PE
EXISTING
XFMR 'T-2PC'
75KVA
480-208Y/120V
NEMA 1EXISTING
EXISITNG
FEEDER
EXISTING
FEEDER
EXISTING
PANEL
2PC
EXISTING
PANEL
2PD
EXISITNG
FEEDER
EXISTING
EXISTING
PANEL
1PF
EXISTING
FEEDER
EXISTING
PANEL
1PG
UPS
EXISITNG
FEEDER
EXISTING
PANEL
UPS
EXISTING
FEEDER
EXISTING
FEEDER
EXISTING
XFMR 'T-EV1'
75 KVA
480-208Y/120V
NEMA 1EXISTING
EXISTING
FEEDER
1 1
2
2 2
22
EXISTING
PANEL
250
EXISTING
FEEDER
EXISTING
XFMR 'T-250'
15 KVA
480-208Y/120V
NEMA 1EXISTING
EXISTING
FEEDER
2
3
3
3
3
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
4
2
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
NONE23008.00
E801
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
SINGLE LINE DIAGRAM
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
1. ALL ELECTRICAL DEVICE SHOWN ARE EXISTING TO REMAIN.
2. ALL ELECTRICAL FEEDER CONDUIT AND CONDUCTORS ARE EXISTING TO REMAIN.
3. ELECTRICAL PANELS ARE EXISTING TO REMAIN WITH MODIFIED LOADS.
GENERAL NOTES
1. EXISTING BREAKER WITH EXISTING LOAD TO REMAIN.
2. EXISTING BREAKER WITH REVISED LOAD PER TENANT IMPROVEMENT.
3. PROVIDE NEW CIRCUIT BREAKER. NEW CIRCUIT BREAKER TO MATCH EXISTING
MANUFACTURER AND AIC VALUES.
4. PROVIDE GROUND-FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKER.
SHEET KEYNOTES#
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
SCALE:NONE
SINGLE LINE DIAGRAM1
VOLTAGE DROP SCHEDULE
DEVICE
FEEDER BRANCH CIRCUIT TOTAL
VOLTAGE
DROP
VOLTAGE
DROP WIRE SIZE
MAX
VOLTAGE
DROP
CIRCUIT
NUMBER WIRE SIZE
MSB 0.00% 0.00%
1LA 0.04% 600kcmil 0.04%
T-1 0.05% 250kcmil 0.05%
2PA 1.21% 4/0 2.75% 11 #12 3.96%
2PB 1.30% #1 1.73% 36 #10 3.03%
DPA 0.04% (3)300kcmil 0.04%
2LA 0.31% #1 2.68% 7 #12 2.99%
T-250 0.00% 0.00%
250 0.00% #1 0.00%
2LB 0.00% 0.00%
T-2PC 0.47% 1/0 0.47%
2PC 0.37% #1 !!! 3.42% !!! 66 #10 3.79%
2PD 0.45% #1 !!! 3.68% !!! 6 #10 4.13%
EXISTING 1315150 VA 100.00% 1315150 VA
KITCHEN EQUIPMENT 0 VA 0.00% 0 VA
NONCONTINUOUS 0 VA 0.00% 0 VA
HEATING 0 VA 0.00% 0 VA
CONTINUOUS 0 VA 0.00% 0 VA TOTAL ESTIMATED DEMAND
AMPS:1633 A
RECEPTACLES 33420 VA 64.96% 21710 VA TOTAL EST. DEMAND:1357.5 kVA
OTHER MOTORS 8112 VA 100.00% 8112 VA TOTAL CONN. AMPS:1644 A
LARGEST MOTOR 0 VA 0.00% 0 VA TOTAL CONN. LOAD:1367 kVA
LIGHTING 10036 VA 125.00% 12545 VA
LOAD CLASSIFICATION CONNECTED
LOAD
DEMAND
FACTOR
ESTIMATED
DEMAND SWITCHBOARD TOTALS
466.9 kVA 457.1 kVA 442.8 kVA
5 1LA 46.6 48.7 42.1 400 A 3 3-1/2"C, 3-600kcmil, 600kcmil N, #2G
4 (X) PANEL 2LB 33.3 33.3 33.3 0 A 3 1/2"C, 3#12, #12N, #12G
3 (X) UPS 99.8 99.8 99.8 0 A 3 1/2"C, 3#12, #12N, #12G
2 (X) DIST. BOARD EDB3 166.3 166.3 166.3 0 A 3 1/2"C, 3#12, #12N, #12G
1 DPA 120.9 109.0 101.3 800 A 3 (3)3"C, 3-300kcmil, 300kcmil N, 1/0G
CKT CIRCUIT DESCRIPTION A B C BREAKER... POLES WIRE SIZE
NOTE EXISTING
FED FROM NEUTRAL LUGS Standard
MOUNTING FLOOR BUS AMPS 2,000 MAIN BKR MCB 2000A
ROOM VOLTS 480Y/277 Wye 3P 4W AIC 50000
MSB
EXISTING 321100 VA 100.00% 321100 VA
KITCHEN EQUIPMENT 0 VA 0.00% 0 VA
NONCONTINUOUS 0 VA 0.00% 0 VA
HEATING 0 VA 0.00% 0 VA
CONTINUOUS 0 VA 0.00% 0 VA TOTAL ESTIMATED DEMAND
AMPS:401 A
RECEPTACLES 0 VA 0.00% 0 VA TOTAL EST. DEMAND:333.6 kVA
OTHER MOTORS 0 VA 0.00% 0 VA TOTAL CONN. AMPS:398 A
LARGEST MOTOR 0 VA 0.00% 0 VA TOTAL CONN. LOAD:331 kVA
LIGHTING 10036 VA 125.00% 12545 VA
LOAD CLASSIFICATION CONNECTED
LOAD
DEMAND
FACTOR
ESTIMATED
DEMAND SWITCHBOARD TOTALS
120.9 kVA 109.0 kVA 101.3 kVA
10 BUSSED SPACE -- -- -- -- 3 1/2"C, 3#12, #12N, #12G
9 BUSSED SPACE -- -- -- -- 3 1/2"C, 3#12, #12N, #12G
8 BUSSED SPACE -- -- -- -- 3 1/2"C, 3#12, #12N, #12G
7 BUSSED SPACE -- -- -- -- 3 1/2"C, 3#12, #12N, #12G
6 SPARE 0.0 0.0 0.0 0 A 3 1/2"C, 3#12, #12N, #12G
5 (X) T-1PC 37.0 34.8 36.0 0 A 3 1/2"C, 3#12, #12N, #12G
4 (X) PANEL WLA 28.7 21.4 13.2 0 A 3 1/2"C, 3#12, #12N, #12G
3 (X) T-EV1 16.6 16.6 16.6 0 A 3 1/2"C, 3#12, #12N, #12G
2 (X) PANEL WLB 33.3 33.3 33.3 0 A 3 1/2"C, 3#12, #12N, #12G
1 2LA 5.3 2.9 2.2 100 A 3 1-1/2"C, 3#1, #1N, #8G
CKT CIRCUIT DESCRIPTION A B C BREAKER... POLES WIRE SIZE
NOTE EXISTING
FED FROM MSB NEUTRAL LUGS Standard
MOUNTING FLOOR BUS AMPS 800 MAIN BKR MLO
ROOM VOLTS 480Y/277 Wye 3P 4W AIC 42000
DPA
MAIN ELEC RM MAIN ELEC RM
E19124
Exp. 06/30/26REGISTEREDPROFESSIONALENGINEER
STATEOF CALIFORNIA
RYANW.BERTALAN
ELE C T R I CAL
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
1
0
:
5
1
:
4
3
A
M
C:
\
U
s
e
r
s
\
r
w
i
l
s
o
n
\
D
o
c
u
m
e
n
t
s
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4.
M
E
P
2
6
_
r
w
i
l
s
o
n
9
Y
V
9
U
.
r
v
t
23008.00
E901
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
PANEL SCHEDULES
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
1 PANEL SCHEDULES
SCALE: NONE
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
BALANCED THREE PHASE AMPS 165 A 151 A
TOTAL KVA 137.38 kVA 125.67 kVA
EXISTING 95.85 kVA 95.85 kVA 100.00%
RECEPTACLES 33.42 kVA 21.71 kVA 64.96%KITCHEN EQUIP Not Computed Not Computed 0.00%
OTHER MOTORS 8.11 kVA 8112 VA 100.00%NONCONTINUOUS Not Computed Not Computed 0.00%
LARGEST MOTOR Not Computed Not Computed 0.00%HEATING 0.00 kVA 0.00 kVA 0.00%
LIGHTING Not Computed Not Computed 0.00%CONTINUOUS Not Computed Not Computed 0.00%
CONN. KVA CALC. KVA CONN. KVA CALC. KVA
TOTAL CONNECTED AMPS BY...170.56 178.27 152.07 170.56 178.27 152.07
TOTAL CONNECTED KVA BY...46.56 48.70 42.12 46.56 48.70 42.12
41 -- BUSSED SPACE -- 18.06 -- -- 42
39 -- BUSSED SPACE -- 21.66 -- -- 40
37 -- BUSSED SPACE -- 19.35 T-1 250 A 38
35 0 A (X) SITE LTG 3.30 0.00 SPARE 0 A 36
33 0 A (X) SITE LTG 3.30 0.00 SPARE 0 A 34
31 0 A (X) SITE LTG 3.30 0.00 SPARE 0 A 32
29 0 A (X) SITE LTG 3.30 2.00 -- -- 30
27 0 A (X) SITE LTG 3.30 2.00 -- -- 28
25 0 A (X) SITE LTG 3.30 2.00 (X) FC-4 0 A 26
23 -- -- 4.15 2.00 -- -- 24
21 -- -- 4.15 2.00 -- -- 22
19 0 A (X) HP-90 4.15 2.00 (X) CU-4 0 A 20
17 0 A SPARE 0.00 2.00 -- -- 18
15 0 A (X) LTG 3.30 2.00 -- -- 16
13 0 A (X) LTG 2.20 2.00 (X) FC-3 0 A 14
11 0 A (X) LTG 1.01 2.00 -- -- 12
9 0 A (X) LTG 0.63 2.00 -- -- 10
7 0 A (X) LTG 2.78 2.00 (X) CU-3 0 A 8
5 0 A (X) LTG 2.30 2.00 (X) EXT WALLPACK LTG 0 A 6
3 0 A (X) LTG 2.36 2.00 (X) EXT WALLPACK LTG 0 A 4
1 0 A (X) LTG 1.48 2.00 (X) EXT WALLPACK LTG 0 A 2
CKT
#
Ratin
g CIRCUIT DESCRIPTION A B C A B C CIRCUIT DESCRIPTION Ratin
g
CKT
#
KVA LOAD KVA LOAD
NOTE:EXISTING
FED FROM:MSB NEUTRAL:100%LUGS:Standard
MOUNTING:SURFACE BUS AMPS:400 MAIN BKR:MLO
LOCATION: VOLTS:480Y/277 Wye A.I.C. RATING:42000
1LA
BALANCED THREE PHASE AMPS 12 A 15 A
TOTAL KVA 10.34 kVA 12.85 kVA
EXISTING 0.30 kVA 0.30 kVA 100.00%
RECEPTACLES Not Computed Not Computed 0.00%KITCHEN EQUIP Not Computed Not Computed 0.00%
OTHER MOTORS Not Computed Not Computed 0.00%NONCONTINUOUS Not Computed Not Computed 0.00%
LARGEST MOTOR Not Computed Not Computed 0.00%HEATING 0.00 kVA 0.00 kVA 0.00%
LIGHTING 10.04 kVA 12.55 kVA 125.00%CONTINUOUS Not Computed Not Computed 0.00%
CONN. KVA CALC. KVA CONN. KVA CALC. KVA
TOTAL CONNECTED AMPS BY...19.49 10.79 7.83 19.49 10.79 7.83
TOTAL CONNECTED KVA BY...5.29 2.88 2.17 5.29 2.88 2.17
41 -- BUSSED SPACE -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- -- BUSSED SPACE -- 30
27 -- BUSSED SPACE -- -- BUSSED SPACE -- 28
25 -- BUSSED SPACE -- -- BUSSED SPACE -- 26
23 -- BUSSED SPACE -- -- BUSSED SPACE -- 24
21 -- BUSSED SPACE -- -- BUSSED SPACE -- 22
19 -- BUSSED SPACE -- -- BUSSED SPACE -- 20
17 -- -- 0.10 -- BUSSED SPACE -- 18
15 -- -- 0.10 0.00 SPARE 20 A 16
13 0 A (X) SUBMETER 0.10 0.00 SPARE 20 A 14
11 0 A SPARE 0.00 0.00 SPARE 20 A 12
9 0 A SPARE 0.00 0.00 SPARE 20 A 10
7 20 A (X) GROWTH 213 LTG 2.84 0.00 SPARE 20 A 8
5 20 A (X) OPEN OFFICE 200 LTG 2.07 0.00 SPARE 20 A 6
3 20 A (X) OPEN OFFICE 200 LTG 2.21 0.57 (X) OPEN OFFICE 200 LTG 20 A 4
1 20 A (X) OPEN OFFICE 200 LTG 0.94 1.41 (X) OFFICE 201-212 LTG 20 A 2
CKT
#
Ratin
g CIRCUIT DESCRIPTION A B C A B C CIRCUIT DESCRIPTION Ratin
g
CKT
#
KVA LOAD KVA LOAD
NOTE:EXISTING
FED FROM:DPA NEUTRAL:100%LUGS:Standard
MOUNTING:SURFACE BUS AMPS:100 MAIN BKR:MLO
LOCATION:(E) ELEC 201 VOLTS:480Y/277 Wye A.I.C. RATING:14000
2LA
BALANCED THREE PHASE AMPS 164 A 131 A
TOTAL KVA 59.07 kVA 47.36 kVA
EXISTING 17.54 kVA 17.54 kVA 100.00%
RECEPTACLES 33.42 kVA 21.71 kVA 64.96%KITCHEN EQUIP Not Computed Not Computed 0.00%
OTHER MOTORS 8.11 kVA 8112 VA 100.00%NONCONTINUOUS Not Computed Not Computed 0.00%
LARGEST MOTOR Not Computed Not Computed 0.00%HEATING 0.00 kVA 0.00 kVA 0.00%
LIGHTING Not Computed Not Computed 0.00%CONTINUOUS Not Computed Not Computed 0.00%
CONN. KVA CALC. KVA CONN. KVA CALC. KVA
TOTAL CONNECTED AMPS BY...162.92 182.12 150.53 162.92 182.12 150.53
TOTAL CONNECTED KVA BY...19.35 21.66 18.06 19.35 21.66 18.06
41 0 A SPARE 0.00 0.72 (X) CONFERNECE 210 REC 0 A 42
39 0 A SPARE 0.00 0.72 (X) OFFICE 229 REC 0 A 40
37 0 A (X) OFFICE 237 REC 0.72 0.72 (X) OFFICE 230 REC 0 A 38
35 0 A (X) OFFICE 238 REC 0.72 0.72 (X) OFFICE 231 REC 0 A 36
33 0 A (X) MEETING RM 239 REC 1.08 0.72 (X) OFFICE 232 REC 0 A 34
31 0 A SPARE 0.00 0.72 (X) OFFICE 233 REC 0 A 32
29 20 A ROOFTOP REC 0.18 0.72 (X) OFFICE 234 REC 0 A 30
27 -- -- 2.03 0.72 (X) OFFICE 235 REC 0 A 28
25 40 A CU-1-1, FC-1-1 2.03 0.72 (X) OFFICE 236 REC 0 A 26
23 -- -- 2.03 0.36 CONFERENCE 210 REC 20 A 24
21 40 A CU-1-2, FC-1-2 2.03 0.36 MDF 211 CDP-1 20 A 22
19 -- -- 0.10 0.00 SPARE 0 A 20
17 -- -- 0.10 0.00 SPARE 0 A 18
15 0 A (X) SUBMETER 0.10 0.00 SPARE 0 A 16
13 0 A (X) OPEN OFFICE 220 REC 0.72 0.00 SPARE 0 A 14
11 20 A REC 0.54 0.00 SPARE 0 A 12
9 0 A (X) OPEN OFFICE 220 REC 0.90 0.72 (X) OFFICE 225 REC 0 A 10
7 0 A (X) OPEN OFFICE 220 REC 0.90 0.72 (X) OFFICE 226 REC 0 A 8
5 0 A (X) OPEN OFFICE 220 REC 0.72 0.00 SPARE 0 A 6
3 0 A (X) ELEC RM 245 REC 1.00 0.54 OPEN OFFICE 200 REC 20 A 4
1 0 A (X) ELEC RM 245 REC 1.00 0.54 OPEN OFFICE 200 REC 20 A 2
CKT
#
Ratin
g CIRCUIT DESCRIPTION A B C A B C CIRCUIT DESCRIPTION Ratin
g
CKT
#
KVA LOAD KVA LOAD
NOTE:EXISTING
FED FROM:T-1 NEUTRAL:100%LUGS:Feed Through
MOUNTING:SURFACE BUS AMPS:225 MAIN BKR:MLO
LOCATION:(E) ELEC 201 VOLTS:208Y/120 Wye A.I.C. RATING:10,000
2PA
BALANCED THREE PHASE AMPS 90 A 61 A
TOTAL KVA 32.46 kVA 22.01 kVA
EXISTING 1.56 kVA 1.56 kVA 100.00%
RECEPTACLES 30.90 kVA 20.45 kVA 66.18%KITCHEN EQUIP Not Computed Not Computed 0.00%
OTHER MOTORS Not Computed Not Computed 0.00%NONCONTINUOUS Not Computed Not Computed 0.00%
LARGEST MOTOR Not Computed Not Computed 0.00%HEATING 0.00 kVA 0.00 kVA 0.00%
LIGHTING Not Computed Not Computed 0.00%CONTINUOUS Not Computed Not Computed 0.00%
CONN. KVA CALC. KVA CONN. KVA CALC. KVA
TOTAL CONNECTED AMPS BY...87.20 89.85 94.15 87.20 89.85 94.15
TOTAL CONNECTED KVA BY...10.46 10.74 11.26 10.46 10.74 11.26
41 0 A SPARE 0.00 0.70 (X) EF-1 0 A 42
39 0 A SPARE 0.00 0.18 DRINKING FOUNTAIN REC 20 A 40
37 0 A SPARE 0.00 0.86 (X) EF-2 0 A 38
35 20 A OPEN OFFICE 200 REC 0.96 0.96 OPEN OFFICE 200 REC 20 A 36
33 20 A OPEN OFFICE 200 REC 0.96 0.96 OPEN OFFICE 200 REC 20 A 34
31 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 32
29 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 30
27 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 28
25 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 26
23 20 A OPEN OFFICE 200 REC 0.96 0.96 OPEN OFFICE 200 REC 20 A 24
21 20 A OPEN OFFICE 200 REC 0.96 0.96 OPEN OFFICE 200 REC 20 A 22
19 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 20
17 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 18
15 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 16
13 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 14
11 20 A OPEN OFFICE 200 REC 0.96 0.96 OPEN OFFICE 200 REC 20 A 12
9 20 A OPEN OFFICE 200 REC 0.96 0.96 OPEN OFFICE 200 REC 20 A 10
7 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 8
5 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 6
3 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 4
1 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 2
CKT
#
Ratin
g CIRCUIT DESCRIPTION A B C A B C CIRCUIT DESCRIPTION Ratin
g
CKT
#
KVA LOAD KVA LOAD
NOTE:EXISTING
FED FROM:2PA NEUTRAL:100%LUGS:Standard
MOUNTING:SURFACE BUS AMPS:100 MAIN BKR:MLO
LOCATION:(E) ELEC 201 VOLTS:208Y/120 Wye A.I.C. RATING:10000
2PB
MAIN ELEC RM
1. ALL ELECTRICAL DEVICE SHOWN ARE EXISTING TO REMAIN.
2. ALL ELECTRICAL FEEDER CONDUIT AND CONDUCTORS ARE EXISTING TO REMAIN.
3. ELECTRICAL PANELS ARE EXISTING TO REMAIN WITH MODIFIED LOADS.
GENERAL NOTES
1. EXISTING BREAKER WITH EXISTING LOAD TO REMAIN.
2. EXISTING BREAKER WITH REVISED LOAD PER TENANT IMPROVEMENT.
3. PROVIDE NEW CIRCUIT BREAKER. NEW CIRCUIT BREAKER TO MATCH EXISTING
MANUFACTURER AND AIC VALUES.
4. PROVIDE GROUND-FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKER.
SHEET KEYNOTES#
1 1
2
1
3
1
2
1
1
2
BALANCED THREE PHASE AMPS 206 A 166 A
TOTAL KVA 171.14 kVA 137.74 kVA
EXISTING 94.34 kVA 94.34 kVA 100.00%
RECEPTACLES 76.80 kVA 43.40 kVA 56.51%KITCHEN EQUIP Not Computed Not Computed 0.00%
OTHER MOTORS Not Computed Not Computed 0.00%NONCONTINUOUS Not Computed Not Computed 0.00%
LARGEST MOTOR Not Computed Not Computed 0.00%HEATING 0.00 kVA 0.00 kVA 0.00%
LIGHTING Not Computed Not Computed 0.00%CONTINUOUS Not Computed Not Computed 0.00%
CONN. KVA CALC. KVA CONN. KVA CALC. KVA
TOTAL CONNECTED AMPS BY...204.78 215.25 199.28 204.78 215.25 199.28
TOTAL CONNECTED KVA BY...56.52 59.42 55.20 56.52 59.42 55.20
41 -- BUSSED SPACE -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- -- BUSSED SPACE -- 30
27 -- BUSSED SPACE -- -- BUSSED SPACE -- 28
25 -- BUSSED SPACE -- -- BUSSED SPACE -- 26
23 -- -- 6.80 -- BUSSED SPACE -- 24
21 -- -- 6.80 -- BUSSED SPACE -- 22
19 0 A (X) CU-1 6.80 -- BUSSED SPACE -- 20
17 -- -- 6.80 -- BUSSED SPACE -- 18
15 -- -- 6.80 -- BUSSED SPACE -- 16
13 0 A (X) HP-120B 6.80 -- BUSSED SPACE -- 14
11 -- -- 6.80 0.50 -- -- 12
9 -- -- 6.80 0.50 -- -- 10
7 0 A (X) HP-120A 6.80 0.50 (X) SUBMETER 0 A 8
5 -- -- 5.50 28.80 -- -- 6
3 -- -- 5.50 33.02 -- -- 4
1 0 A (X) HP-90B 5.50 30.12 T-2PC 125 A 2
CKT
#
Ratin
g CIRCUIT DESCRIPTION A B C A B C CIRCUIT DESCRIPTION Ratin
g
CKT
#
KVA LOAD KVA LOAD
NOTE:
FED FROM: NEUTRAL:100%LUGS:Standard
MOUNTING:SURFACE BUS AMPS:100 MAIN BKR:MLO
LOCATION:(E) ELEC 201 VOLTS:480Y/277 Wye A.I.C. RATING:14000
2LB
BALANCED THREE PHASE AMPS 255 A 162 A
TOTAL KVA 91.94 kVA 58.54 kVA
EXISTING 15.14 kVA 15.14 kVA 100.00%
RECEPTACLES 76.80 kVA 43.40 kVA 56.51%KITCHEN EQUIP Not Computed Not Computed 0.00%
OTHER MOTORS Not Computed Not Computed 0.00%NONCONTINUOUS Not Computed Not Computed 0.00%
LARGEST MOTOR Not Computed Not Computed 0.00%HEATING 0.00 kVA 0.00 kVA 0.00%
LIGHTING Not Computed Not Computed 0.00%CONTINUOUS Not Computed Not Computed 0.00%
CONN. KVA CALC. KVA CONN. KVA CALC. KVA
TOTAL CONNECTED AMPS BY...252.69 276.86 240.00 252.69 276.86 240.00
TOTAL CONNECTED KVA BY...30.12 33.02 28.80 30.12 33.02 28.80
83 84
81 82
79 80
77 78
75 76
73 74
71 20 A OPEN OFFICE 200 REC 0.96 2.40 (X) LOAD 0 A 72
69 20 A OPEN OFFICE 200 REC 0.96 6.12 (X) LOAD 0 A 70
67 20 A OPEN OFFICE 200 POWER POLE 0.80 6.12 (X) LOAD 0 A 68
65 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 66
63 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 64
61 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 62
59 0 A SPARE 0.00 0.80 OPEN OFFICE 200 POWER POLE 20 A 60
57 0 A (X) LOAD 0.50 0.80 OPEN OFFICE 200 POWER POLE 20 A 58
55 0 A SPARE 0.00 0.80 OPEN OFFICE 200 POWER POLE 20 A 56
53 0 A SPARE 0.00 0.96 OPEN OFFICE 200 REC 20 A 54
51 0 A SPARE 0.00 0.96 OPEN OFFICE 200 REC 20 A 52
49 0 A SPARE 0.00 0.80 OPEN OFFICE 200 POWER POLE 20 A 50
47 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 48
45 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 46
43 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 44
41 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 42
39 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 40
37 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 38
35 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 36
33 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 34
31 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 32
29 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 30
27 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 28
25 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 26
23 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 24
21 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 22
19 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 20
17 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 18
15 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 16
13 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 14
11 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 12
9 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 10
7 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 8
5 20 A OPEN OFFICE 200 POWER POLE 0.80 8.80 -- -- 6
3 20 A OPEN OFFICE 200 POWER POLE 0.80 8.80 -- -- 4
1 20 A OPEN OFFICE 200 POWER POLE 0.80 8.00 2PD 100 A 2
CKT
#
Ratin
g CIRCUIT DESCRIPTION A B C A B C CIRCUIT DESCRIPTION Ratin
g
CKT
#
KVA LOAD KVA LOAD
NOTE:
FED FROM:T-2PC NEUTRAL:100%LUGS:Standard
MOUNTING:SURFACE BUS AMPS:100 MAIN BKR:MLO
LOCATION:(E) ELEC 214 VOLTS:208Y/120 Wye A.I.C. RATING:10000
2PC
BALANCED THREE PHASE AMPS 71 A 49 A
TOTAL KVA 25.60 kVA 17.80 kVA
EXISTING Not Computed Not Computed 0.00%
RECEPTACLES 25.60 kVA 17.80 kVA 69.53%KITCHEN EQUIP Not Computed Not Computed 0.00%
OTHER MOTORS Not Computed Not Computed 0.00%NONCONTINUOUS Not Computed Not Computed 0.00%
LARGEST MOTOR Not Computed Not Computed 0.00%HEATING 0.00 kVA 0.00 kVA 0.00%
LIGHTING Not Computed Not Computed 0.00%CONTINUOUS Not Computed Not Computed 0.00%
CONN. KVA CALC. KVA CONN. KVA CALC. KVA
TOTAL CONNECTED AMPS BY...66.67 74.36 74.36 66.67 74.36 74.36
TOTAL CONNECTED KVA BY...8.00 8.80 8.80 8.00 8.80 8.80
29 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 30
27 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 28
25 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 26
23 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 24
21 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 22
19 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 20
17 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 18
15 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 16
13 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 14
11 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 12
9 20 A OPEN OFFICE 200 REC 0.96 0.80 OPEN OFFICE 200 POWER POLE 20 A 10
7 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 8
5 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 6
3 20 A OPEN OFFICE 200 POWER POLE 0.80 0.96 OPEN OFFICE 200 REC 20 A 4
1 20 A OPEN OFFICE 200 POWER POLE 0.80 0.80 OPEN OFFICE 200 POWER POLE 20 A 2
CKT
#
Ratin
g CIRCUIT DESCRIPTION A B C A B C CIRCUIT DESCRIPTION Ratin
g
CKT
#
KVA LOAD KVA LOAD
NOTE:
FED FROM:2PC NEUTRAL:100%LUGS:Standard
MOUNTING:SURFACE BUS AMPS:100 MAIN BKR:MLO
LOCATION:(E) ELEC 214 VOLTS:208Y/120 Wye A.I.C. RATING:10000
2PD
1 2
1
1
2
1
2
1
2
1
3
2
3
2
3
1
2 2
22
11
3
1
4
MECHANICAL SHEET LIST
SHEET NUMBER SHEET NAME
M001 MECHANICAL LEGEND, NOTES AND SYMBOLS
M002 MECHANICAL NOTES
M010 MECHANICAL SCHEDULES
M020 MECHANICAL ENERGY CODE COMPLIANCE
M120 MECHANICAL SECOND FLOOR OVERALL PLAN
M220 MECHANICAL SECOND FLOOR DEMOLITION PLAN
M320 MECHANICAL SECOND FLOOR PLAN
M330 MECHANICAL ROOF PLAN
M420 MECHANICAL SECOND FLOOR PIPING PLAN
M520 MECHANICAL SECOND FLOOR ZONING PLAN
M620 MECHANICAL REFLECTED CEILING PLAN
M910 MECHANICAL DETAILS EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO.CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
5
:
4
8
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
23008.00
M001
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL LEGEND, NOTES
AND SYMBOLS
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
DOUBLE LINE
SYMBOL
SINGLE LINE
SYMBOL DESCRIPTION
AB
B
R
SYMBOL
MECHANICAL LEGEND
BFV
CV
BV
PRV
BV
DESCRIPTION
GV
CD
CWS
CWR
20x1220x12 DUCT DIMENSION
∅-ROUND DUCT
DUCT TRANSITION
FIRE DAMPERFD
FIRE SMOKE DAMPERFSD
SQUARE ELBOW
W/TURNING VANES
RADIUS ELBOW
SUPPLY AIR DUCT UP
SUPPLY AIR DUCT DOWN
RETURN AIR DUCT UP
RETURN AIR DUCT DOWN
DUCT CAP
SUPPLY / OUTSIDE AIR
RETURN / TRANSFER AIR
EXHAUST AIR
SA
SA
SUPPLY AIR DUCT BELOWSA
RETURN AIR DUCT BELOW
RA
RA
EXHAUST AIR DUCT UP
EXHAUST AIR DUCT DOWN
EXHAUST AIR DUCT BELOW
EA
EA
EA
EA
RA
CIRCULAR DIFFUSER
DUCT MOUNTED GRILL
RECTANGULAR DUCT TO
ROUND DUCT TRANSITION
ROUND DUCT UPEA
ROUND DUCT DOWN
FLEX DUCT
SUPPLY AIR TAKEOFF
LINEAR DIFFUSER
VAV BOX
HEAT RECOVERY UNIT
WALL MOUNTED
THERMOSTAT
WALL MOUNTED
HUMIDISTAT
SMOKE DETECTOR
MANUAL VOLUME
DAMPERMD
ACTUATOR VALVE
VAV
HRU
T
H
SD
AUTOMATIC AIR VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
BALANCING VALVE
GLOBE VALVE
PRESSURE REDUCING VALVE
BOTTOM OF PIPE TAKEOFF
TOP OF PIPE TAKEOFF
PIPE DOWN
PIPE UP
G NATURAL GAS PIPINGWALL MOUNTED SWITCHS
CONDENSATE DRAIN PIPING
CHILLED WATER RETURN PIPING
CHILLED WATER SUPPLY PIPING
HHWS HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
HHWS
HHWR
G
AIR FLOW DIRECTION.
DOUBLE & SINGLE POINT OF CONNECTION
POINT OF DISCONNECT
POC
WALL MOUNTED
CARBONDIOXIDE SENSORCO2
T
H
SD
S
CO2
FAN COILFC
BFV
CV
BV
PRV
BV
GV
AIR FLOW DIRECTION
DUCT TRANSITION
FD
FSD
RADIUS ELBOW
SUPPLY AIR DUCT UP
SUPPLY AIR DUCT DOWN
RETURN AIR DUCT UP
RETURN AIR DUCT DOWN
DUCT CAP
SA
SA
SUPPLY AIR DUCT BELOWSA
RETURN AIR DUCT BELOW
RA
RA
EXHAUST AIR DUCT UP
EXHAUST AIR DUCT DOWN
EXHAUST AIR DUCT BELOW
EA
EA
EA
SA
OA
RA
TA
EA
RA
ROUND DUCT UPEA
ROUND DUCT DOWN
FLEX DUCT
SUPPLY AIR TAKEOFF
MD
ACTUATOR VALVE
VAV
HRU
T
H
SD
AUTOMATIC AIR VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
BALANCING VALVE
GLOBE VALVE
PRESSURE REDUCING VALVE
BOTTOM OF PIPE TAKEOFF
TOP OF PIPE TAKEOFF
PIPE DOWN
PIPE UP
NATURAL GAS PIPINGS
CD CONDENSATE DRAIN PIPING
CWR CHILLED WATER RETURN PIPING
CWS CHILLED WATER SUPPLY PIPING
HEATING HOT WATER SUPPLY
HHWR HEATING HOT WATER RETURN
POINT OF CONNECTION
POINT OF DISCONNECTPOD
CO2
H
S
FC
DIFFERENTIAL PRESSURE
GAUGEDPdP
FAN
CIRCULATION PUMPCP
PIPING OR EQUIPMENT TO BE
REMOVED (DEMO PATTERN)
NOT IN SCOPE PATTERN
AREA OF WORK PATTERN
MECHANICAL GENERAL NOTES
1. THE CONTRACTOR SHALL VISIT THE SITE INCLUDING ALL AREAS INDICATED ON THE
DRAWINGS, TO THOROUGHLY FAMILIARIZE HIMSELF/HERSELF WITH THE EXISTING
CONDITIONS. CONTRACTOR SHALL VERIFY SAID CONDITIONS AND DIMENSIONS AT
JOB SITE PRIOR TO START OF CONSTRUCTION. PRIOR TO INSPECTION OF THE
EXISTING FACILITY, THE CONTRACTOR SHALL RECEIVE PERMISSION FOR ACCESS
FROM THE OWNER OR THE DESIGNATED REPRESENTATIVE. IF DISCREPANCIES ARE
DISCOVERED, THE ENGINEER SHALL BE NOTIFED IMMEDIATELY FOR CLARIFICATION.
CONTACT THE ENGINEER TO CLARIFY ANY UNCLEAR DRAWING ITEMS PRIOR TO
CONSTRUCTION. PRIOR TO SITE ACCESS, THE CONTRACTOR SHALL BE PROPERLY
IDENTIFIED.
2. THE CONTRACTOR SHALL PERFORM ALL WORK REQUIRED IN ACCORDANCE WITH ALL
LOCAL, STATE AND FEDERAL CODES, REGULATIONS AND ORDINANCES, AND IN
ACCORDANCE WITH ALL OWNER DESIGN AND CONSTRUCTION STANDARDS.
3. IF THE CONTRACTOR DETERMINES AT ANY TIME THAT THE REQUIREMENTS OF
THESE CONSTRUCTION DOCUMENTS ARE IN CONFLICT WITH, OR IN VIOLATION OF
APPLICABLE LAWS, CODES, REGULATIONS OR ORDINANCES, HE/SHE SHALL NOT
PROCEED WITH ANY WORK IN QUESTION, EXCEPT AT HIS/HER OWN RISK, UNTIL THE
ENGINEER HAS BEEN NOTIFIED AND A DETERMINATION MADE (IN WRITING). WHERE
COMPLETED OR PARTIALLY COMPLETED WORK IS DISCOVERED TO BE IN VIOLATION
OF APPLICABLE LAWS, CODES, REGULATIONS OR ORDINANCES, THE CONTRACTOR
SHALL BE REQUIRED TO REMOVE THAT WORK FROM THE PROJECT AND REPLACE
SUCH WORK WITH ALL NEW COMPLYING WORK AT NO ADDTIIONAL COST TO THE
OWNER, THE ARCHITECT OR THE ENGINEER.
4. ALL DRAWINGS AND SPECIFICATIONS ARE TO BE CONSIDERED PART OF THE
CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
REVIEW AND COORDINATION OF ALL DRAWINGS AND SPECIFICATIONS PRIOR TO
PERFORMING ANY WORK, INCLUDING ARCHITECTURAL, STRUCTURAL, MECHANICAL,
PLUMING AND ELECTRICAL DOCUMENTS.
5. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES AND OTHER
CONTRACTORS.
6. ABBREVIATIONS & SYMBOLS USED ON THE DRAWINGS ARE THOSE IN COMMON USE.
THE ENGINEER SHALL DEFINE THE INTENT OF ANY IN QUESTION.
7. ANY ITEM EXPOSED DURING DEMOLITION AND/OR NEW WORK THAT IS NOT BEING
REUSED, SHALL BE REMOVED AND SCRAPPED-OUT. ITEMS MAY INCLUDE ITEMS
PREVIOUSLY NOT REMOVED. ITEMS REMOVED SHALL BE SCRAPPED-OUT
IMMEDIATELY AND NOT STOCKPILED ON SITE.
8. ALL PENETRATIONS OF PIPING OR DUCTWORK THROUGH FIRE/SMOKE-RATED
ASSEMBLIES SHALL BE SEALED WITH UL APPROVED RESILIENT FIRE-RETARDANT
SEALANT.
9. ALTHOUGH EQUIPMENT AND PIPING INDICATED ON THE DRAWINGS HAVE BEEN
DRAWN TO SCALE, AND ARE GENERALLY DIMENSIONALLY ACCURATE, THE
CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND NOT SCALE THE
DRAWINGS. THIS IS ESPECIALLY TRUE REGARDING EXISTING EQUIPMENT OR PIPING
TO REMAIN.
10. ALL MATERIAL AND EQUIPMENT REMOVED BY DEMOLITION SHALL BE REMOVED FROM
THE SITE ON A DAILY BASIS (NO STOCK PILING).
11. HANDLE, STORE AND INSTALL ALL NEW EQUIPMENT, DUCTWORK, AND PIPING PER
MANUFACTURERS INSTRUCTIONS AND PER 2022 CALIFORNIA GREEN BUILDING CODE.
12. ALL ITEMS NOTED TO BE REMOVED AND REUSED (RELOCATED) SHALL BE HANDLED
WITH PROPER CARE AND STORED IN A SAFE PLACE TO PREVENT DAMAGE, OR THEY
WILL BE REPLACED AT THE CONTRACTOR'S EXPENSE.
13. ALL SAFETY MEASURES WHILE ON SITE ARE THE DIRECT RESPONSIBILITY OF THE
CONTRACTOR. THIS INCLUDES THE USE OF LADDERS, SCAFFOLDING, TOOLS,
EQUIPMENT, TRENCHING, ETC.
14. ALL DUST, NOISE AND ODORS SHALL BE CONTROLLED BY THE CONTRACTOR PER
OWNERS' REQUIREMENTS AND PER 2022 CALIFORNIA GREEN BUILDING CODE.
15. LEGAL EXITS SHALL NOT BE BLOCKED AT ANY TIME WITH MATERIALS OR EQUIPMENT,
TEMPORARILY OR PERMANENTLY.
16. ALL USE OF FLEXIBLE DUCT SHALL BE LIMITED TO FIVE (5) FEET IN TOTAL LENGTH
PER SECTION 603.4.1 OF THE 2022 CMC. ALL FLEXIBLE DUCT SHALL BE ADEQUATELY
SECURED TO BRANCH DUCTWORK AND THE AIR TERMINAL DEVICE WHICH IT SERVES
(I.E. SEALED, STRAPPED, BANDED, MECHANICALLY-SECURED, ETC.). ALL FLEXIBLE
DUCTWORK SHALL HAVE A MINIMUM R-VALUE RATING OF R-8.
17. ALL BRANCH DUCTWORK SHALL BE PROVIDED WITH BALANCE (VOLUME) DAMPERS
WHETHER INDICATED OR NOT, FOR SYSTEM SHUT-OFF AND BALANCING.
18. ALL BRANCH PIPING SHALL BE PROVIDED WITH ISOLATION VALVES WHETHER
INDICATED OR NOT, FOR SYSTEM SHUT-OFF AND BALANCING.
19. IN GENERAL, ALL PIPING AND DUCTWORK SHALL BE RUN CONCEALED ABOVE
SUSPENDED CEILINGS, IN SHAFTS OR IN SOFFITS UNLESS NOTED OR INDICATED
OTHERWISE.
20. PROVIDE ALL REQUIRED SLEEVES OR OPENINGS WHERE PIPES OR DUCTS PASS
THROUGH FOUNDATIONS, FLOOR SLABS, WALLS, ROOFS, ETC.
21. ACCESS SHALL BE PROVIDED AT ALL DAMPERS, VALVES AND EQUIPMENT. PROVIDE
ACCESS DOORS AS REQUIRED. EACH ACCESS DOOR SHALL BE A MINIMUM OF 24”x24”
UNLESS INDICATED OTHERWISE, AND SHALL BE FIRE-RATED IF REQUIRED TO
MAINTAIN THE FIRE-RATING OF THE ASSEMBLY IN WHICH THE ACCESS DOOR IS
INSTALLED.
22. AN AIR BALANCE TEST SHALL BE REQUIRED IN ORDER TO VERIFY THE MINIMUM
VOLUME OF OUTSIDE AIR HAS BEEN PROVIDED TO COMPLY WITH THE CALIFORNIA
TITLE 24 CALCULATIONS PRIOR TO THE APPROVAL/COMPLETION OF PROJECT
CONSTRUCTION.
23. AIR HANDLING DUCT SYSTEMS, EXCEPT GREASE EXHAUST DUCT SYSTEMS, SHALL BE
CONSTRUCTED, INSTALLED, AND INSULATED AS REQUIRED IN 2022 CALIFORNIA
MECHANICAL CODE, CHAPTER 6.
24. IF APPLICABLE, PRIOR TO FINAL APPROVAL OF THE MECHANICAL PERMIT A SMOKE
DETECTOR SHUT-OFF TEST SHALL BE REQUIRED.
25. PROVIDE PERMANENT IDENTIFICATION ON EACH EQUIPMENT AND THE AREA SERVED
WHEN MORE THAN ONE HVAC SYSTEM IS INSTALLED ON THE ROOF OF A BUILDING
OR WITHIN A BUILDING PER 2022 CALIFORNIA MECHANICAL CODE, SECTION 303.7.
26. ALL EXHAUST AIR FANS SHALL BE EQUIPPED WITH BACK-DRAFT DAMPERS.
27. ROOF ACCESS LADDER SHALL COMPLY WITH CURRENT CODE OF CALIFORNIA
MECHANICAL CODE SECTION 304.
28. INSULATION MATERIAL SHALL MEET THE CALIFORNIA QUALITY STANDARD PER
SECTION 110.8 CALIFORNIA ENERGY EFFICIENCY STANDARDS.
29. ALL PIPING AND DUCTWORK SHALL BE INSULATED CONSISTENT WITH THE
REQUIREMENTS OF SECTIONS 120.3, 120.4, AND 120.7 CALIFORNIA ENERGY
EFFICIENCY STANDARDS AND CHAPTER 6 OF CMC.
30. ALL HVAC SYSTEMS SHALL MEET THE CONTROL REQUIREMENTS PER SECTION 110.2
AND 120.2 CALIFORNIA ENERGY EFFICIENCY STANDARDS.
31. ALL HVAC EQUIPMENT AND APPLICANCES SHALL MEET THE REQUIREMENTS PER
SECTION 110.1 -110.3, 110.5, 1201. -120.4 CALIFORNIA ENERGY EFFICIENCY
STANDARDS.
32. SYSTEM PIPING AND COMPONENTS SHALL BE TESTED WITH A PRESSURE OF NOT
LESS THAN ONE AND ONE-HALFT TIMES THE OPERATING PRESSURE BUT NOT LESS
THAN 100 PSI (689 kPa). PIPING SHALL BE TESTED WITH WATER OR AIR EXCEPT THAT
PLASTIC PIPE SHALL NOT BE TESTED WITH AIR. TEST PRESSURES SHALL BE HELD
FOR A PERIOD OF NOT LESS THAN 30 MINUTES WITH NO PERCEPTIBLE DROP IN
PRESSURE. THESE TESTS SHALL BE MADE INTHE PRESENCE OF THE AUTHORITY
HAVING JURISDICTION.
SCOPE OF WORK
MECHANICAL HVAC RENOVATION OF AN EXISITING COMMERCIAL OFFICE SPACE.
BUILDING HVAC IS IN THE FORM OF EXISTING ROOFTOP AHU'S WITH VAV'S AND ADDITION
OF TWO (2) DUCTLESS HEAT PUMP SPLIT-SYSTEM. THE DUCTWORK AND THERMOSTATS
ARE REROUTED TO REFLECT THE CURRENT RENOVATION.
MECHANICAL ANCHORAGE
ALL MECHANICAL AND PLUMBING COMPONENTS SHALL BE ANCHORED AND INSTALLED
PER THE DETAILS IN/ON THE CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS
PROVIDED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET
THE FORCE AND DISPLACEMENT REQUIREMENT PRESCRIBED IN THE 2022 CBC,
SECTIONS 1615A.1.12 THROUGH 1615A.1.22, AND ASCE 7-05, CHAPTER 6 & 13.
1. ALL PERMANENT EQUIPMENT AND COMPONENTS.
2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANTENTLY ATTACHED (I.E.
HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS GAS OR WATER.
3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8
HOURS AND HEAVIER THAN 400 POUNDS (PROVIDE TEMPORARY ATTACHMENTS).
THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND PLUMBING COMPONENTS
SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE. THESE COMPONENTS SHALL BE
PROVIDED WITH FLEXIBLE CONNECTORS BETWEEN THE COMPONENT AND THE
ASSOCIATED DUCTWORK OR PIPING.
1. COMPONENTS WEIGHING LESS THAN 400 POUNDS WITH A CENTER OF MASS
LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL.
2. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED
SYSTEMS (I.E. DUCTWORK OR PIPING), LESS THAN 5 POUNDS PER FOOT (THOSE
COMPONENTS THAT ARE SUPPORTED FROM A ROOF, A FLOOR OR FROM A WALL).
FOR THOSE ELEMENTS/COMPONENTS THAT DO NOT REQUIRE SPECIFIC DETAILS IN/ON
THE CONSTRUCTION DOCUMENTS, THE INSTALLATION SHALL BE SUBJECT TO APPROVAL
BY THE STRUCTURAL ENGINEER OF RECORD. THE PROJECT INSPECTOR WILL VERIFY
THAT ALL COMPONENTS AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH
THESE REQUIREMENTS.
PIPING AND DUCTWORK DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH
THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05, SECTIONS 13.3, 13.6.5.6,
13.6.7 AND 13.6.8, AND THE 2022 CBC, SECTIONS 1615A1.20, 1615A1.21 AND 1615A1.22.
HVAC REFRIGERANT QUANTITIES
UNIT MARK AND
NUMBER
REFRIGERANT TYPE
AND GROUP
REFRIGERANT
QUANTITY (LB)
PER CIRCUIT
FC/CU-1 R-32 (GROUP A2L)9
FC/CU-2 R-32 (GROUP A2L)9
TOTAL AMOUNT OF GROUP A1 REFRIGERANTS:18
TOTAL AMOUNT OF ANY OTHER TYPE OF REFRIGERANTS:0
THIS TABLE IDENTIFIES THE TOTAL AMOUNT OF REFRIGERANT CHARGE IN ANY NEW HVAC
UNITS SHOWN ON THE MECHANICAL PLANS. ANY EXISTING EQUIPMENT SHALL BE
MEASURED WITH AN ESTIMATION OF 3 LBS OF GROUP A1 REFRIGERANT PER 12,000 BTUH
(OR 1-TON) OF COOLING.
A HAZARDOUS MATERIALS PERMIT IS REQUIRED FOR REFRIGERATION SYSTEMS THAT
EXCEED 220 LBS FOR GROUP A1 REFRIGERANT OF 30 LBS OF ANY OTHER GROUP PER
2022 CFC SECTIONS 105.6.42 AND 605.
FOR A HAZARDOUS MATERIALS PERMIT PLEASE CONTACT THE LOCAL FIRE DEPARTMENT
TECHNICAL SERVICES. FOR CITY OF SAN DIEGO CONTACT SDFD AT 619-533-4477 TO MAKE
AN APOINTMENT.
SCHEDULE RESPONSIBILITIES
ITEM
FU
R
N
I
S
H
BY
IN
S
T
A
L
L
BY
PO
W
E
R
BY
CO
N
T
R
O
L
WI
R
I
N
G
B
Y
1 MAGNETIC MOTOR STARTERS:
A AUTOMATIC CONTROLLED, WITH OR WITHOUT
HOA SWITCHES.
E E E DDC
B MANUALLY CONTROLLED.E E E N/A
C MANUALLY CONTROLLED FURNISHED AS
FACTORY WIRED UNIT EQUIPMENT.
M M E E
D SPECIAL DUTY TYPE (PART WINDING, MULTI
SPEED, ETC.).
M SEE
NOTE 1
E SEE
NOTE 1
E ADJUSTABLE FREQUENCY DRIVES WITH OR
WITHOUT MANUAL BYPASS.
M E E DDC
SEE
NOTE 2
F DOMESTIC BOOSTER PUMP. MOTOR CONTROLS.M M E DDC
2 LINE VOLTAGE CONTACTORS.E E E DDC
3 CONTROL RELAY TRANSFORMERS (OTHER THAN
STARTERS).
DDC DDC E DDC
4 CONTROL INSTRUMENTATION PANEL. DDC NI E DDC
5 AUTOMATIC CONTROL VALVES, AUTOMATIC
DAMPERS AND DAMPER OPERATORS, SOLENOID
VALVES, INSERTION TEMPERATURE AND PRESSURE
SENSORS INCLUDING WELLS.
DDC M E DDC
6 CONTROL INTERLOCK WIRING BETWEEN CHILLERS,
PUMPS, COOLING TOWERS, FANS, AND AIR
HANDLING UNITS AND OTHER MISCELLANEOUS
MECHANICAL EQUIPMENT.
DDC DDC E DDC
7 DUCT SMOKE DETECTORS.E M E E
8 DAMPERS.
A CONTROL DAMPERS.M M N/A DDC
B SMOKE DAMPERS AND COMBINATION
FIRE/SMOKE DAMPERS,
M M E E
9 AIRFLOW STATIONS AND TRANSMITTER.M M E DDC
10 AIR TERMINAL DEVICES (I.E., VAV AND FAN POWERED
BOXES.)
M M E DDC
11 INTELLIGENT DEVICES AND CONTROL UNITS
PROVIDED WITH PACKAGED MECHANICAL
EQUIPMENT SUCH AS: LARGE VAV AND CONSTANT
PACKAGE UNIT BOILERS AND CHILLERS.
M M E NI
12 INTELLIGENT DEVICES AND CONTROL UNITS NOT
PROVIDED BY EQUIPMENT MANUFACTURER SUCH AS:
AIR HANDLING UNITS, HEAT PUMPS, AC UNITS (SMALL
< 20 TONS>, AIR TERMINAL UNITS (VAV BOXES).
DDC DDC E DDC
13 INTELLIGENT DEVICES AND CONTROL UNITS
PROVIDED WITH ELECTRICAL SYSTEM SUCH AS:
OCCUPANCY / MOTION SENSORS, LIGHTING
CONTROL PANELS, SWITCHES AND DIMMERS,
SWITCH MULTIPLEXING CONTROL UNITS, DOOR
ENTRY CONTROL UNITS.
E E E DDC
14 GATEWAYS FOR PROPRIETARY NON-BACNET
EQUIPMENT.
M M E DDC
15 COMMUNICATIONS NETWORK DEVICES SUCH AS
ROUTERS, BRIDGES AND REPEATERS.
DDC DDC DDC DDC
ABBREVIATIONS
DDC DDC CONTRACTOR (CONTROLS CONTRACTOR)
M MECHANICAL CONTRACTOR
E ELECTRICAL CONTRACTOR
N/A NOT APPLICABLE
NOTES:
1 MAGNETIC MOTORS STARTERS (SPECIAL DUTY TYPE) SHALL BE SET IN PLACE UNDER
ELECTRICAL DIVISION EXCEPT WHEN PART OF FACTORY WIRED EQUIPMENT, IN WHICH
CASE THEY SHALL BE SET IN PLACE UNDER MECHANICAL DIVISION.
2 WHERE ARE REMOTE MOTOR DISCONNECT IS REQUIRED IN ADDITION TO THE ONE
PROVIDED INTEGRAL TO A VARIABLE FREQUENCY DRIVE (VFD), CONTROLS
CONTRACTOR SHALL PROVIDE THE NECESSARY CONTROL INTERLOCK BETWEEN
DISCONNECTS.
SHEET
TYPE DESCRIPTION
0
LEAD SHEETS
LEGEND, NOTES AND SYMBOLS
1 ENERGY CODES | SITE PLAN
2 DEMOLITION PLANS
3
NEW PLANS
MECH PLAN
4 PIPING
5 ZONING
6 REFLECTED CEILING
7 ENLARGED PLAN
8 DIAGRAMS
9 DETAILS
M 3 1 1
DISCIPLINE DESIGNATION
SERIES TYPE
BUILDING LEVEL
BUILDING AREA / SEQUENCE
NUMBER
MECHANICAL FLOOR...
SHEET TITLE
SHEET NUMBER NOMENCLATURE
APPLICABLE CODES
APPLICABLE CODES, STANDARDS, GUIDELINES AND AHJS
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA GREEN BUILDING CODE
2022 CALIFORNIA BUILDING ENERGY EFFICIENCY STANDARDS
CURRENT EDITION NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
CURRENT EDITION AMERICANS WITH DISABILITIES ACT (ADA)
CALIFORNIA ENERGY CODE NOTE
THIS PROJECT IS THE RENOVATION OF AN EXISTING FLOOR WITH VARIABLE AIR
VOLUME TERMINAL UNITS. THE ENVELOPE HAS NOT BEEN CHANGED OR REVISED
OTHER THAN BEING PAINTED. PRESCRIPTIVE REQUIREMENTS HAVE BEEN SET TO THE
DEFAULT U-VALUE AND SHGC VALUES FOR EXISTING GLAZING.
AB
B
R
DESCRIPTION SYMBOL
AB
B
R
TAG DESCRIPTIONS
MECHANICAL ABBREVIATION
ABBR DESCRIPTION ABBR DESCRIPTION ABBR DESCRIPTION ABBR DESCRIPTION
ACT ACTUAL DOAS DEDICATED OUTDOOR AIR SYSTEM KWH KILOWATTS PER HOUR S WALL MOUNTED SWITCH
AF AIR FILTER DP DEW POINT \ DIFFERENTIAL
PRESSURE L LENGTH SA SUPPLY AIR
AF AIR FOIL (FAN BLADE) (E)EXISTING LAT LEAVING AIR TEMPERATURE SAF SUPPLY AIR FAN
AFF ABOVE FINISHED FLOOR ELEC ELETRICAL (POWER)LBS POUNDS SAV SUPPLY AIR VALVE
AHJ AUTHORITY HAVING JURISDICTION EA EXHAUST AIR LEF LABORATORY EXHAUST FAN SEER SEASONAL ENERGY EFFICIENCY
RATIO
AHU AIR HANDLING UNIT EAT ENTERING AIR TEMPERATURE LWT LEAVING WATER TEMPERATURE SUP SUPPLY
AMB AMBIENT EAV EXHAUST AIR VALVE MAX MAXIMUM T THERMOSTAT
AP ACCESS PANEL EER ENERGY EFFICIENCY RATIO MERV MIN. EFFICIENCY REPORTING
VALUE TOF TOP OF FOOTING
APD AIR PRESSURE DROP EF EXHAUST FAN MCA MIN. CIRCUIT AMPACITY TOD TOP OF DUCT
AS AIR SEPARATOR EFF EFFICIENCY MFS MAXIMUM FUSE SIZE TOP TOP OF PIPE
AT AIR TERMINAL ESP EXTERNAL STATIC PRESSURE MOCP MAX. OVER-CURRENT PROTECTION TSP TOTAL STATIC PRESSURE
AV AIR VALVE ET EXPANSION TANK MC MECHANICAL CONTRACTOR TYP TYPICAL
B BOILER EWT ENTERING WATER TEMPERATURE MD MECHANICAL DAMPER U UPBLAST
BD BALANCING DAMPER EXH EXHAUST MIN MINIMUM UNO UNLESS NOTED OTHERWISE
BDD BACKDRAFT DAMPER (F)FUTURE MS MECHANICAL SENSOR VAV VARIABLE AIR VOLUME
BDR BELT DRIVE (FAN)F FAHREINHEIT (TEMPERATURE)MUA MAKE-UP AIR VD VOLUME DAMPER
BI BACKWARD INCLINED (FAN BLADE)FC FAN COIL (N)NEW VFD VARIABLE FREQUENCY DRIVE
BHP BRAKE HORSEPOWER FD FIRE DAMPER NA NOT APPLICABLE V/PH/HZ VOLTS. PHASE, HERTZ
BMS BUILDING MANAGEMENT SYSTEM FF FINISHED FLOOR NIC NOT IN CONTRACT VTR VENT THROUGH ROOF
BOF BOTTOM OF FOOTING FFU FAN FILTER UNIT NC NORMALLY CLOSED VRF VARIABLE REFRIGERANT FLOW
BOD BOTTOM OF DUCT FG FINISHED GRADE NG NATURAL GAS W WALL MOUNTED
BOP BOTTOM OF PIPE FHD FEET OF HEAD OA OUTSIDE AIR W WIDTH
BTU BRITISH THERMAL UNIT FLA FULL LOAD AMPS P PUMP W WATER
BTUH BRITISH THERMAL UNIT PER HOUR FPM FEET PER MINUTE PG PRESSURE GAUGE W WATTS
BFV BUTTERFLY VALVE FPS FEET PER SECOND PH PHASE (ELECTRICAL)WB WET BULB (TEMPERATURE)
BV BALL VALVE FSD FIRE SMOKE DAMPER POC POINT OF CONNECTION WC WATER COLUMN (INCHES)
C CENTRIFUGAL FT FOOT (FEET)POD POINT OF DISCONNECTION WPD WATER PRESSURE DROP
CH CHILLER FW FIRE WATER PRV PRESSURE REDUCING VALVE WSHP WATER-SOURCE HEAT PUMP
CAV CONSTANT AIR VOLUME G GAS (NATURAL)PSIA POUNDS PER SQUARE INCH (ABS)WT WEIGHT
CC COOLING COIL GA GAUGE PSIG POUNDS PER SQUARE INCH
(GAUGE)W/ WITH
CFH CUBIC PER FEET PER HOUR GPH GALLONS PER HOUR QTY QUANTITY W/O WITHOUT
CFMD COOLING FLOW MEASURING
DEVICE GPM GALLONS PER MINUTE R ROOF MOUNTED
CFM CUBIC FEET PER HOUR H HEIGHT RA RETURN AIR
CFSD COMBINATION FIRE/SMOKE
DAMPER HEPA HIGH-EFFICIENCY PARTICULATE
AIR FILTER RAF RETURN AIR FAN
CD CONDENSATE HC HEATING COIL RAV RETURN AIR VALVE
CLG CEILING HP HORSEPOWER RH REHEAT COIL
CT COOLING TOWER HRB HEAT RECOVERY BOX RLA RUNNING (RATED) LOAD AMPS
CU AIR-COOLED SPLIT-SYSTEM OR
VRF CONDENSER HRU HEAR RECOVERY UNIT RLFA RELIEF AIR
CV CONTROL VALVE IL INLINE RPM REVOLUTIONS PER MINUTE
(D)DEMOLISHED IN INCH RET RETURN
DB DRY BULB (TEMPERATURE)KW KILOWATTS RTU ROOFTOP UNIT
1
M710
HP
1
SD-1
300
MECHANICAL
KEYNOTE
DIFFUSER TYPE
CFM
EQUIPMENT TYPE
UNIT NUMBER
DETAIL NUMBER
SHEET NUMBER
1
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
5
:
4
9
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
23008.00
M002
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL NOTES
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
AIR ECONOMIZER SHUT OFF
DEVICE
TYPE2
CL
I
M
A
T
E
ZO
N
E
S
REQUIRED HIGH LIMIT (ECONOMIZER OFF WHEN):
EQUATION3 DESCRIPTION
FIXED DRY
BULB
7 OUTDOOR AIR TEMPERATURE EXCEEDS 69°F
10 OUTDOOR AIR TEMPERATURE EXCEEDS 73°F
DIFFERENTIAL
DRY BULB
7 TOA > TRA -
6°F
OUTDOOR AIR TEMPERATURE EXCEEDS
RETURN AIR TEMPERATURE MINUS 6°F
10 TOA > TRA -
2°F
OUTDOOR AIR TEMPERATURE EXCEEDS
RETURN AIR TEMPERATURE MINUS 2°F
FIXED
ENTHALPY4+
FIXED DRY
BULB
ALL
ZONES
hOA > 28
BTU/LB4 OR
TOA > 75°F
OUTDOOR AIR ENTHALPY EXCEEDS 28 BTU/LB
OF DRY AIR4 OR OUTDOOR AIR
TEMPERATURE EXCEEDS 75°F
1. THIS TABLE IS BASED ON TABLE 140.4-B "AIR ECONOMIZER HIGH LIMIT SHUT OFF
CONTROL REQUIREMENTS" OF THE 2022 CEC.
2. ONLY THE HIGH LIMIT CONTROL DEVICES LISTED ARE ALLOWED TO BE USED AND AT
THE SET POINTS LISTED. OTHERS SUCH AS DEW POINT, FIXED ENTHALPY, ELECTRONIC
ENTHALPY, AND DIFFERENTIAL ENTHALPY CONTROLS MAY NOT BE USED IN ANY CLIMATE
ZONE FOR COMPLIANCE WITH SECTION 140.4(e)1 UNLESS APPROVAL FOR USE IS
PROVIDED BY THE ENERGY COMMISSION EXECUTIVE DIRECTOR.
3. DEVICES WITH SELECTABLE (RATHER THAN ADJUSTABLE) SET POINTS SHALL BE
CAPABLE OF BEING SET TO WITHIN 2°F AND 2 BTU/LB OF THE SET POINT LISTED.
4. AT ALTITUDES SUBSTANTIALLY DIFFERENT THAN SEA LEVEL, THE FIXED ENTHALPY
LIMIT VALUE SHALL BE SET TO THE ENTHALPY VALUE AT 75°F AND 50% RELATIVE
HUMIDITY. AS AN EXAMPLE, AT APPROXIMATELY 6,000 FOOT ELEVATION, THE FIXED
ENTHALPY LIMIT IS APPROXIMATELY 30.7 BTU/LB.
TOA > 73°F
TOA > 69°F
DRAWBANDS USED WITH
i.DRAWBANDS SHALL BE EITHER STAINLESS-STEEL WORM DRIVE HOSE CLAMS
OR UV-RESISTANT NYLON DUCT TIES.
ii.DRAWBANDS SHALL HAVE A MINIMUM TENSILE STRENGTH OF 150 POUNDS.
iii.DRAWBANDS SHALL BE TIGHTENED AS RECOMMENDED BY THE MANUFACTURER
WITH AN ADJUSTABLE TENSIONING TOOL.
*THIS TABLE IS BASED ON SECTIONS FROM THE 2022 CALIFORNIA ENERGY CODE.
REQUIRED CONTROLS FOR SPACE
CONDITIONING SYSTEMS*
1
WHERE USED TO CONTROL BOTH COMFORT HEATING AND COMFORT COOLING, THE
THERMOSTATIC CONTROLS SHALL MEET ITEMS 120.2(b)1 & 120.2(b)2 OF THE 2016
CEC AND SHALL BE CAPABLE OF PROVIDING A TEMPERATURE RANGE OR DEAD
BAND OF AT LEAST 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLING
ENERGY TO THE ZONE IS SHUT OFF OR REDUCED TO A MINIMUM. COMPLIANT WITH
SECTION 120.2(b)3.
2
THERMOSTATIC CONTROLS FOR ALL SINGLE ONE, AIR CONDITIONERS AND HEAT
PUMPS SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 110.2(c)A AND
REFERENCE JOINT APPENDIX JA5 OR, IF EQUIPPED WITH DDC TO THE ZONE LEVEL,
WITH THE AUTOMATIC DEMAND SHED CONTROLS OF SECTION 120.2(h). COMPLIANT
WITH SECTION 120.2(b)4
3
THE CONTROL SHALL BE CAPABLE OF AUTOMATICALLY SHUTTING OFF THE SYSTEM
DURING PERIODS OF NONUSE AND SHALL COMPLY WITH SECTION 120.2(e)1 AND
SHALL HAVE:
A AN AUTOMATIC TIME SWITCH CONTROL DEVICE COMPLYING WITH SECTION
110.9(c) OF THE 2022 CALIFORNIA ENERGY CODE, WITH AN ACCESSIBLE
MANUAL OVERRIDE THAT ALLOWS OPERATION OF THE SYSTEM FOR UP TO 4
HOURS; OR
B AN OCCUPANCY SENSOR; OR
C A 4-HOUR TIMER THAT CAN BE MANUALLY OPERATED.
>EXCEPTION TO SECTION 120.2(e)1: MECHANICAL SYSTEMS SERVING RETAIL
STORES AND ASSOCIATED MALLS, RESTAURANTS, GROCERY STORES,
CHURCHES AND THEATERS EQUIPPED WITH 7-DAY PROGRAMMABLE TIMERS.
4
MULTIPURPOSE ROOM LESS THAN 1,000 FT², CLASS ROOMS GREATER THAN 750 FT²
AND CONFERENCE, CONVENTION, AUDITORIUM AND MEETING CENTER ROOMS
GREATER THAN 750 FT² THAT DO NOT HAVE PROCESSES OR OPERATIONS THAT
GENERATE DUSTS, FUMES, VAPORS OR GASSES SHALL COMPLY WITH SECTION
120.2(e)3 OF THE 2022 CALIFORNIA ENERGY CODE AND SHALL BE EQUIPPED WITH
OCCUPANT SENSOR(S) TO ACCOMPLISH THE FOLLOWING DURING UNOCCUPIED
PERIODS:
A
AUTOMATICALLY SET UP THE OPERATING COOLING TEMPERATURE SET POINT
BY 2°F OR MORE AND SET BACK THE OPERATING HEATING TEMPERATURE
SET POINT BY 2°F OR MORE; AND
B
AUTOMATICALLY RESET THE MINIMUM REQUIRED VENTILATION RATE WITH
AND OCCUPIED SENSOR VENTILATION CONTROL DEVICE ACCORDING TO
SECTION 120.1(c)5 OF THE 2022 CALIFORNIA ENERGY CODE.
5
HOTEL AND MOTEL GUEST ROOMS SHALL HAVE CAPTIVE CARD KEY CONTROLS,
OCCUPANCY SENSING CONTROLS OR AUTOMATIC CONTROLS SUCH THAT, NO
LONGER THAN 30 MINUTES AFTER THE GUEST ROOM HAS BEEN VACATED, SET
POINTS ARE SET UP AT LEAST +5°F (+3°C) IN COOLING MODE AND SET DOWN AT
LEAST -5°F (-3°C) IN HEATING MODE. COMPLIANT WITH SECTION 120.2(e)4 OF THE
CALIFORNIA ENERGY CODE.
*THIS TABLE IS BASED ON SECTIONS FROM THE 2022 CALIFORNIA ENERGY CODE
REQUIRED NONRESIDENTIAL
MECHANICAL SYSTEM ACCEPTANCE
NONRESIDENTIAL, HIGH-RISE RESIDENTIAL AND HOTEL/MOTEL BUILDING SHALL COMPLY
WITH THE APPLICABLE REQUIREMENTS OF SECTIONS 120.5(a) THROUGH 120.5(b)
A.
BEFORE AN OCCUPANCY PERMIT IS GRANTED, THE FOLLOWING EQUIPMENT AND
SYSTEMS SHALL BE CERTIFIED AS MEETING THE ACCEPTANCE REQUIREMENTS FOR
CODE COMPLIANCE, AS SPECIFIED BY THE REFERENCE NONRESIDENTIAL APPENDIX
NA7. A CERTIFICATE OF ACCEPTANCE SHALL BE SUBMITTED TO THE
ENFORCEMENT AGENCY THAT CERTIFIES THAT THE EQUIPMENT AND SYSTEMS
MEET THE ACCEPTANCE REQUIREMENTS:
1.OUTDOOR AIR VENTILATION SYSTEMS SHALL BE TESTED IN ACCORDANCE
WITH NA7.5.1.
2.CONSTANT VOLUME, SINGLE ZONE UNITARY AIR CONDITIONING AND HEAT
PUMP UNIT CONTROLS SHALL BE TESTED IN ACCORDANCE WITH NA7.5.2.
3.DUCT SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH NA7.5.3 WHERE
EITHER:
a.THEY ARE NEW DUCT SYSTEMS THAT MEET THE CRITERIA OF SECTIONS
140.4(k)1, 140.4(1)2 AND 140.4(1)3 OR
b.THEY ARE PART OF A SYSTEM THAT MEETS THE CRITERIA OR SECTION
141.0(b)2D
4.
AIR ECONOMIZERS SHALL BE TESTED IN ACCORDANCE WITH NA7.5.4.
EXCEPTION: AIR ECONOMIZERS INSTALLED BY THE HVAC SYSTEMS
MANUFACTURER AND CERTIFIED TO THE COMMISSION AS BEING FACTORY
CALIBRATED AND TESTED ARE EXEMPT FROM THE FUNCTIONAL TESTING
SECTION OF THE AIR ECONOMIZER CONTROLS ACCEPTANCE TEST AS
DESCRIBED IN NA7.5.4.2.
5.DEMAND CONTROL VENTILATION SYSTEMS REQUIRED BY SECTION 120.1(c)3
SHALL BE TESTED IN ACCORDANCE WITH NA7.5.5.
6.SUPPLY FAN VARIABLE FLOW CONTROL SHALL BE TESTED IN ACCORDANCE
WITH NA7.5.6.
7.HYDRONIC SYSTEM VARIABLE FLOW CONTROLS SHALL BE TESTED IN
ACCORDANCE WITH NA7.5.7 AND NA7.5.9.
8.
BOILER OR CHILLERS THAT REQUIRE ISOLATION CONTROLS AS SPECIFIED BY
SECTION 140.4(k)2 OR 140.4(k)3 SHALL BE TESTED IN ACCORDANCE WITH
NA7.5.7.
9.HYDRONIC SYSTEMS WITH SUPPLY WATER TEMPERATURE RESET CONTROLS
SHALL BE TESTED IN ACCORDANCE WITH NA7.5.8
10.AUTOMATIC DEMAND SHED CONTROLS SHALL BE TESTED IN ACCORDANCE
WITH NA7.5.10
11.FAULT DETECTION AND DIAGNOSTICS (FDD) FOR AIR HANDLING UNITS AND
ZONE TERMINAL UNITS SHALL BE TESTED IN ACCORDANCE WITH NA7.5.12
12.AUTOMATIC FAULT DETECTION AND DIAGNOSTICS (FDD) FOR AIR HANDLING
UNITS AND ZONE TERMINAL UNITS SHALL BE TESTED IN ACCORDANCE WITH
NA7.5.12.
13.DISTRIBUTED ENERGY STORAGE DX AC SYSTEMS SHALL BE TESTED IN
ACCORDANCE WITH NA7.5.13
14.THERMAL ENERGY STORAGE (TES) SYSTEMS SHALL BE TESTED IN
ACCORDANCE WITH NA7.5.14
15.SUPPLY AIR TEMPERATURE RESET CONTROLS SHALL BE TESTED IN
ACCORDANCE WITH NA7.5.15
16.WATER-COOLED CHILLERS SERVED BY COOLING TOWERS WITH CONDENSER
WATER RESET CONTROLS SHALL BE TESTED IN ACCORDANCE WITH NA7.5.16
17.WHEN AN ENERGY MANAGEMENT CONTROL SYSTEM IS INSTALLED, IT SHALL
FUNCTIONALLY MEET AL THE APPLICABLE REQUIREMENTS OF PART 6.
B.
WHEN CERTIFICATION IS REQUIRED BY TITLE-24, PART 1, SECTION 10-103.2, THE
ACCEPTANCE TESTING SPECIFIED BY SECTION 120.59a) SHALL BE PERFORMED BY A
CERTIFIED MECHANICAL ACCEPTANCE TEST TECHNICIAN (CMATT). IF THE CMATT IS
OPERATING AS AN EMPLOYEE, THE CMATT SHALL BE EMPLOYED BY A CERTIFIED
MECHANICAL ACCEPTANCE TEST EMPLOYER. THE CMATT SHALL DISCLOSE ON THE
CERTIFICATE OF ACCEPTANCE A VALID CMATT CERTIFICATION IDENTIFICATION
NUMBER ISSUED BY AN APPROVED ACCEPTANCE TEST TECHNICIAN CERTIFICATION
PROVIDER. THE CMATT SHALL COMPLETE ALL CERTIFICATE OF ACCEPTANCE
DOCUMENTATION IN ACCORDANCE WITH THE APPLICABLE REQUIREMENTS IN
SECTION 10-103(a)4.
*THIS TABLE IS BASED ON SECTIONS FROM THE 2022 CALIFORNIA ENERGY CODE
VENTILATION REQUIREMENTS
1 THE OUTDOOR AIR-VENTILATION RATE AND AIR-DISTRIBUTION ASSUMPTIONS THAT
ARE MADE IN THE DESIGN OF THE VENTILATING SYSTEM SHALL BE CLEARLY
IDENTIFIED ON THE PLANS REQUIRED BY SECTION 10-103 OF TITLE 24, PART I.
COMPLIANT WITH SECTION 120.1(a)2 OF THE 2022 CALIFORNIA ENERGY CODE.
2 NATURALLY VENTILATED SPACES SHALL BE PERMANENTLY OPEN TO AND WITHIN 20
FEET OF OPERABLE WALL OR ROOF OPENINGS TO THE OUTDOORS, THE OPERABLE
AREA OF WHICH IS NOT LESS THAN 5 PERCENT OF THE CONDITIONED FLOOR AREA
OF THE NATURALLY VENTILATED SPACE. WHERE OPENINGS ARE COVERED WITH
LOUVERS OR OTHERWISE OBSTRUCTED, OPERABLE ARE SHALL BE BASED ON THE
FREE UNOBSTRUCTED AREA THROUGH THE OPENING. COMPLIANT WITH SECTION
120.1(b)1A OF THE 2022 CALIFORNIA ENERGY CODE.
3 15 CFM PER PERSON TIMES THE EXPECTED NUMBER OF OCCUPANTS. FOR
MEETING THE REQUIREMENT IN SECTION 120.1(B)2B FOR SPACES WITHOUT FIXED
SEATING, THE EXPECTED NUMBER OF OCCUPANTS SHALL BE EITHER THE
EXPECTED NUMBER SPECIFIED BY THE BUILDING DESIGNER OR ONE HALF OF THE
MAXIMUM OCCUPANT LOAD ASSUMED FOR EGRESS PURPOSES IN THE CALIFORNIA
BUILDING CODE, WHICHEVER IS GREATER. FOR SPACES WITH FIXED SEATING, THE
EXPECTED NUMBER OF OCCUPANTS SHALL BE DETER-MINED IN ACCORDANCE WITH
THE CALIFORNIA BUILDING CODE. COMPLIANT WITH SECTION 120.1(b)1B OF THE
2022 CALIFORNIA ENERGY CODE.
>EXCEPTION TO SECTION 120.1(b)2: TRANSFER AIR. THE RATE OF OUTDOOR
AIR REQUIRED BY SECTION 120.1(B)2 MAY BE PROVIDED WITH AIR
TRANSFERRED FROM OTHER VENTILATED SPACES IF:
A NONE OF THE SPACES FROM WHICH AIR IS TRANSFERRED HAVE ANY
UNUSUAL SOURCES OF INDOOR AIR CONTAMINANTS; AND
B THE OUTDOOR AIR THAT IS SUPPLIED TO ALL SPACES COMBINED IS
SUFFICIENT TO MEET THE REQUIREMENTS OF SECTION 120.1(B)2 FOR
EACH SPACE INDIVIDUALLY.
4 THE MINIMUM RATE OF OUTDOOR AIR REQUIRED BY SECTION 120.1(b)2 SHALL BE
SUPPLIED TO EACH SPACE AT ALL TIMES WHEN THE SPACE IS USUALLY OCCUPIED.
COMPLIANT WITH SECTION 120.1(c)1 OF THE 2022 CALIFORNIA ENERGY CODE.
>
EXCEPTION 1 TO SECTION 120.1(c)1: DEMAND CONTROL VENTILATION. IN
INTERMITTENTLY OCCUPIED SPACES THAT DO NOT HAVE PROCESSES OR
OPERATIONS THAT GENERATE DUSTS, FUMES, MISTS, VAPORS OR GASSES
AND ARE NOT PROVIDED WITH LOCAL EXHAUST VENTILATION (SUCH AS
INDOOR OPERATION OF INTERNAL COMBUSTION ENGINES OR AREAS
DESIGNATED FOR UN-VENTED FOOD SERVICE PREPARATION), THE RATE OF
OUTDOOR AIR MAY BE REDUCED IF THE VENTILATION SYSTEM SERVING THE
SPACE IS CONTROLLED BY A DEMAND CONTROL VENTILATION DEVICE
COMPLYING WITH SECTION 120.1(C)4 OR BY AN OCCUPANT SENSOR
VENTILATION CONTROL DEVICE COMPLYING WITH SECTIONS 120.1(c)5.
5 HVAC SYSTEMS WITH THE FOLLOWING CHARACTERISTICS SHALL HAVE DEMAND
VENTILATION CONTROLS COMPLYING WITH SECTIONS 120.1(c)3 AND 120.1(c)4 OF
THE 2022 CALIFORNIA ENERGY CODE:
A THEY HAVE AN AIR ECONOMIZER; AND
B THEY SERVE A SPACE WITH A DESIGN OCCUPANT DENSITY, OR A MAXIMUM
OCCUPANCY LOAD FACTOR FOR EGRESS PURPOSES IN THE CBC, GREATER
THAN OR EQUAL TO 25 PEOPLE PER 1,000 SQFT (40 SQFT OR LESS PER
PERSON); AND
C THEY ARE EITHER:
i SINGLE ZONE SYSTEMS WITH ANY CONTROLS; OR
ii MULTIPLE ZONE SYSTEMS WITH DIRECT DIGITAL CONTROLS (DDC) TO
THE ZONE LEVEL.
>EXCEPTION 1 TO SECTION 120.1(c)3: CLASSROOMS, CALL CENTERS, OFFICE
SPACES SERVED BY MULTIPLE ZONE SYS-TEMS THAT ARE CONTINUOUSLY
OCCUPIED DURING NORMAL BUSINESS HOURS WITH OCCUPANT DENSITY
GREATER THAN 25 PEOPLE PER 1,000 SQUARE FEET AS SPECIFIED BY
SECTION 120.1(B)2B, HEALTHCARE FACILITIES AND MEDICAL BUILD-INGS, AND
PUBLIC AREAS OF SOCIAL SERVICES BUILDINGS ARE NOT REQUIRED TO HAVE
DEMAND CONTROL VENTILATION.
>EXCEPTION 4 TO SECTION 120.1(C)3: SPACES WITH AN AREA OF LESS THAN
150 SQUARE FEET, OR A DESIGN OCCU-PANCY OF LESS THAN 10 PEOPLE AS
SPECIFIED BY SECTION 120.1(B)2B.
>EXCEPTION 5 TO SECTION 120.1(C)3: SPACES WITH AN AREA OF LESS THAN
1,500 SQUARE FEET COMPLYING WITH SECTION 120.1(C)5.
6 DEMAND CONTROL VENTILATION DEVICES MUST COMPLY WITH SECTION 120.1(c)4
OF THE 2022 CALIFORNIA ENERGY CODE AND THE FOLLOWING:
A FOR EACH SYSTEM WITH DEMAND CONTROL VENTILATION, CO/2 SENSORS
SHALL BE INSTALLED IN EACH ROOM THAT MEETS THE CRITERIA OF SECTION
120.1(c)3 WITH NO LESS THAN ONE SENSOR PER 10,000 SQFT OF FLOOR
SPACE. WHEN A ZONE OR A SPACE IS SERVED BY MORE THAN ONE SENSOR, A
SIGNAL FROM ANY SENSOR INDICATING THAT CO/2 IS NEAR OR AT THE SE
TPOINT WITHIN A SPACE SHALL TRIGGER AN INCREASE IN VENTILATION TO
THE SPACE;
B CO/2 SENSORS SHALL BE LOCATED IN THE ROOM BETWEEN 3 FEET AND 6
FEET ABOVE THE FLOOR OR AT THE ANTICIPATED HEIGHT OF THE
OCCUPANTS HEADS;
C DEMAND VENTILATION CONTROLS SHALL MAINTAIN CO/2 CONCENTRATIONS
LESS THAN OR EQUAL TO 600 PPM PLUS THE OUTDOOR AIR CO/2
CONCENTRATION IN ALL ROOMS WITH CO/2 SENSORS;
D OUTDOOR AIR CO/2 CONCENTRATION SHALL BE DETERMINED BY ONE OF THE
FOLLOWING:
I CO/2 CONCENTRATION SHALL BE ASSUMED TO BE 400 PPM WITHOUT
ANY DIRECT MEASUREMENT; OR
II CO/2 CONCENTRATION SHALL BE DYNAMICALLY MEASURED USING A
CO2 SENSOR LOCATED WITHIN 4 FEET OF THE OUTDOOR AIR INTAKE.
7 DESIGN AND CONTROL REQUIREMENTS FOR QUANTITIES OF OUTDOOR AIR.
ALL MECHANICAL VENTILATION AND SPACE-CONDITIONING SYSTEMS SHALL BE
DESIGNED WITH AND HAVE INSTALLED DUCTWORK, DAMPERS AND CONTROLS TO
ALLOW OUTSIDE AIR RATES TO BE OPERATED AT THE LARGEST OF (1) THE MINIMUM
LEVELS SPECIFIED IN SECTION 120.1(b)1; OR (2) THE RATE REQUIRED FOR MAKE-UP
OF EXHAUST SYSTEMS THAT ARE REQUIRED FOR AN EXEMPT OR COVERED
PROCESS, FOR CONTROL OF ODORS, OR FOR THE REMOVAL OF CONTAMINANTS
WITHIN THE SPACE. COMPLIANT WITH SECTION 120.1(e)1 OF THE 2016 CALIFORNIA
ENERGY CODE.
*THIS TABLE IS BASED ON SECTIONS FROM THE 2022 CALIFORNIA ENERGY CODE
CONTROL REQUIREMENTS1
FLEXIBLE DUCT
MINIMUM VENTILATION RATES*
TYPE OF USE
CFM PER SQUARE
FOOT OF CONDITIONED
FLOOR AREA
AUTO REPAIR WORKSHOPS 1.5
BARBER SHOPS 0.4
BARS, COCKTAIL LOUNGES AND CASINOS 0.2
BEAUTY SHOPS 0.4
COIN-OPERATED DRY CLEANING 0.3
COMMERCIAL DRY CLEANING 0.45
HIGH-RISE RESIDENTIAL
VENTILATION RATES SPECIFIED
BY THE CALIFORNIA BUILDING
CODE
HOTEL GUEST ROOMS <500 FT²30 CFM / GUEST ROOM
HOTEL GUEST ROOMS >500 FT²0.15
RETAIL STORES 0.2
ALL OTHERS 0.15
*THIS TABLE IS BASED ON TABLE 120.1-A "MINIMUM VENTILATION RATES" OF THE 2022
CEC
DUCTWORK INSULATION
ALL MECHANICAL AND PLUMBING COMPONENTS SHALL BE ANCHORED AND INSTALLED
PER THE DETAILS IN/ON THE CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS
PROVIDED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO
MEET THE FORCE AND DISPLACEMENT REQUIREMENT PRESCRIBED IN THE 2022 CBC,
SECTIONS 1615A.1.12 THROUGH 1615A.1.22, AND ASCE 7-05, CHAPTER 6 & 13.
1. THE INSTALLED THICKNESS OF DUCT INSULATION USED TO DETERMINE ITS R-
VALVE SHALL BE DETERMINED AS FOLLOWS:
A. FOR DUCT BOARD, DUCT LINER AND FACTORY-MADE RIGID DUCTS NOT
NORMALLY SUBJECTED TO COMPRESSION, THE NOMINAL INSULATION
THICKNESS SHALL BE USED.
B. FOR DUCT WRAP, INSTALLED THICKNESS SHALL BE ASSUMED TO BE 75
PERCENT (25 PERCENT COMPRESSION) OF NORMAL THICKNESS .
C. FOR FACTORY-MADE FLEXIBLE AIR DUCTS, THE INSTALLED THICKNESS SHALL
BE DETERMINED BY DIVIDING THE DIFFERENCE BETWEEN THE ACTUAL
OUTSIDE DIAMETER AND NOMINAL INSIDE DIAMETER BY TWO.
2. INSULATED FLEXIBLE DUCT PRODUCTS INSTALLED TO MEET THIS REQUIREMENT
MUST INCLUDE LABELS, IN MAXIMUM INTERVALS OF 3 FEET, SHOWING THE
THERMAL PERFORMANCE R-VALUE FOR THE DUCT INSULATION ITSELF
(EXCLUDING AIR FILMS, VAPOR RETARDER OR OTHER DUCT COMPONENTS),
BASED ON THE TEST IN SECTION 120.4(c) AND THE INSTALLED THICKNESS
DETERMINED BY SECTION 120.4(d)3.
3. PROTECTION OF INSULATION. INSULATION SHALL BE PROTECTED FROM DAMAGE,
INCLUDING THAT DUE TO SUNLIGHT, MOISTURE, EQUIPMENT MAINTENANCE AND
WIND, BUT NOT LIMITED TO THE FOLLOWING:
A. INSULATION EXPOSED TO WEATHER SHALL BE SUITABLE FOR OUTDOOR
SERVICE, E.G., PROTECTED BY ALUMINUM, SHEET METAL, PAINTED CANVAS
OR PLASTIC COVER. CELLULAR FOAM INSULATION SHALL BE PROTECTED AS
ABOVE OR PAINTED WITH A COATING THAT IS WATER RETARDANT AND
PROVIDES SHIELDING FROM SOLAR RADIATION THAT CAN CAUSE
DEGRADATION OF THE MATERIAL.
*THIS TABLE IS BASED ON SECTIONS FROM THE 2022 CALIFORNIA ENERGY CODE.
PIPE INSULATION THICKNESS
FLUID
TEMPERATURE
RANGE, (°F)
CONDUCTIVITY RANGE
(IN BTU-INCH PER HOUR PER
SQUARE FOOT PER °F)
INSULATION MEAN
RATING TEMPERATURE
(°F)
NOMINAL PIPE DIAMETER (IN INCHES)
<1 1 TO <1.5 1.5 TO <4 4 TO <8 8< AND
LARGER
INSULATION THICKNESS REQUIRED (IN INCHES)
SPACE HEATING, HOT WATER SYSTEMS (STEAM, STEAM CONDENSATE AND HOT WATER) AND SERVICE WATER HEATING SYSTEMS (RECIRCULATING SECTIONS, ALL PIPING IN
ELECTRIC TAPE SYSTEMS, AND THE FIRST 8 FEET OF PIPING FROM THE STORAGE TANK FOR NON-RECIRUCLATING SYSTEMS)
>350 0.32 -0.34 250 4.5 5.0 5.0 5.0 5.0
251 -350 0.29 -0.32 200 3.0 4.0 4.5 4.5 4.5
201 -250 0.27 -0.30 150 2.5 2.5 2.5 3.0 3.0
141 -200 0.25 -0.29 125 1.5 1.5 2.0 2.0 2.0
105 -140 0.22 -0.28 100 1.0 1.5 1.5 1.5 1.5
SPACE COOLING SYSTEMS (CHILLED WATER, REFRIGERANT AND BRINE)
40 -60 0.21 -0.27 75 NONRES
(0.5)
RES
(0.75)1.0 1.0 1.0
<40 0.20 -0.26 50 1.0 1.5 1.5 1.5 1.5
NOTES:
1. INSULATION CONDUCTIVITY SHALL BE DETERMINED IN ACCORDANCE WITH ASTM C335 AT THE MEAN TEMPERATURE LISTED IN THE TABLE, AND SHALL BE ROUNDED TO THE
NEAREST 1/100 BTU-INCH PER HOUR PER SQUARE FOOT PER °F.
2. THIS TABLE IS BASED ON TABLE 120.3-A "PIPE INSULATION THICKNESS" OF THE 2022 CEC.
NONRES
(0.5)
RES
(0.75)
AIR DISTRIBUTION DUCT SYSTEMS
REQUIREMENTS
PORTION OF SUPPLY AIR AND RETURN AIR DUCTS CONVEYING HEATED OR COOLED AIR
LOCATED IN ONE OR MORE OF THE FOLLOWING SPACES SHALL BE INSULATED TO A
MINIMUM INSTALLED LEVEL OF R-8:
1.OUTDOORS; OR
2.IN A SPACE BETWEEN THE ROOF AND AN INSULATED CEILING; OR
3.IN A SPACE DIRECTLY UNDER A ROOF WITH FIXED VENTS OR OPENINGS TO THE
OUTSIDE OR UNCONDITIONED SPACES; OR
4.IN AN UNCONDITIONED CRAWLSPACE; OR
5.IN OTHER UNCONDITIONED SPACES.
PORTIONS OF SUPPLY AIR DUCTS THAT ARE NOT IN ONE OF THESE SPACES, INCLUDING
DUCTS BURIED IN CONCRETE SLAB, SHALL BE INSULATED TO A MINIMUM INSTALLED
LEVEL OR R-4.2 (OR ANY HIGHER LEVEL REQUIRED BY CMC SECTION 605.0) OR BE
ENCLOSED IN DIRECTLY CONDITIONED SPACE.
*THIS TABLE IS BASED ON SECTIONS FROM THE 2022 CALIFORNIA ENERGY CODE
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
HANGER ROD SIZES
PIPE AND TUBE SIZE (INCHES) ROD SIZES (INCHES)
1/2 - 4 3/8
5 - 8 1/2
10 - 12 5/8
*THIS TABLE IS BASED ON TABLE 313.6 "HANGER ROD SIZES" OF THE 2022 CALIFORNIA
MECHANICAL CODE.
ELECTRICAL CONNECTION
EQUIPMENT MARK DISCONNECT TYPE CONTROL / POWER
RELAY
BUILDING MANAGEMENT
SYSTEM CONTROLLERS NONE (RECEPTACLE) NO
BOILER FUSED DISCONNECT NO
CHILLER
(AIR-COOLED /
WATER-COOLED)
FUSED DISCONNECT NO
COOLING TOWER FAN(S)
COMBINATION MOTOR
STARTER
DISCONNECT
NO
COOLING TOWER FAN(S) -
PACKAGED SYSTEM FUSED DISCONNECT NO
COOLING TOWER SPRAY
PUMP(S)
COMBINATION MOTOR
STARTER
DISCONNECT
NO
AIR HANDLER FUSED DISCONNECT NO
PACKAGED UNIT
(HEAT
PUMP/GAS-ELECTRIC)
FUSED DISCONNECT NO
FAN (AC MOTOR)
115V MOTOR-RATED SWITCH NO
FAN (AC MOTOR)
208V - 460V
COMBINATION MOTOR
STARTER
DISCONNECT
NO
FAN (AC MOTOR)
208V - 460V
VFD
INTEGRAL DISCONNECT NO
FAN (EC MOTOR)
COMBINATION MOTOR
STARTER
DISCONNECT
NO
SPLIT SYSTEM CONDENSER FUSED DISCONNECT NO
SPLIT SYSTEM
FAN-COIL
(POWERED BY CU)
NONE NO
SPLIT SYSTEM FAN-COIL
(SEPARATELY POWERED)FUSED DISCONNECT NO
PUMP (AC MOTOR)
208V - 460V (SINGLE PHASE)
COMBINATION MOTOR
STARTER
DISCONNECT
NO
PUMP (AC MOTOR)
208V - 460V (THREE PHASE)
VFD
INTEGRAL DISCONNECT NO
PUMP (EC MOTOR)
COMBINATION MOTOR
STARTER
DISCONNECT
NO
PUMP (115V CIRCULATOR) NONE (RECEPTACLE) NO
HEPA FILTER BREAKER SIZED FOR MOCP NO
AIR/VENTURI VALVE
(SAV/EAV)
120V J-BOX W/ 24V
TRANSFORMER NO
VAV TERMINAL 120V J-BOX W/ 24V
TRANSFORMER NO
ELECTRONIC DAMPERS 120V J-BOX W/ 24V
TRANSFORMER NO
HYDRONIC CONTROL
VALVES
120V J-BOX W/ 24V
TRANSFORMER NO
COMBINATION FIRE-SMOKE
DAMPER
BREAKER DISCONNECT
120V
J-BOX AT UNIT
YES
DUCT SMOKE DETECTOR
BREAKER DISCONNECT
120V
J-BOX AT UNIT
YES
WATER HEATER NONE (RECEPTACLE) NO
AIR COMPRESSOR / VACUUM
PUMP FUSED DISCONNECT NO
DI WATER SKID FUSED DISCONNECT NO
SCHEDULE
CONTRACTOR SCOPE &
EQUIPMENT / MATERIAL
PRODUCT SUBMITTAL (S)
CLOSE-OUT PACKAGE (CO)
AIR DISTRIBUTION DEVICES S
DUCTWORK MATERIALS S
DUCTWORK INSULATION S
HVAC SPLIT-SYSTEMS S
FIRE DAMPERS / FIRE-SMOKE DAMPERS / SMOKE DAMPERS S
SUPPLY AND/OR EXHAUST FANS S
HYDRONIC PUMPS S
HYDRONIC ACCESSORIES AND SPECIALTIES S
PIPING - REFRIGERANT S
PIPING - HYDRONIC S
PIPING INSULATION S
PIPING VALVES S
HANGERS AND SEISMIC - HVAC S
HANGERS AND SEISMIC - PLUMBING S
SHOP DRAWINGS - SHEET METAL S
SHOP DRAWINGS - PRESSURIZED PIPING S
BUILDING AUTOMATION SYSTEM - HARDWARE S
BUILDING AUTOMATION SYSTEM - WIRING DIAGRAMS S
BUILDING AUTOMATION SYSTEM - SEQUENCE OF
OPERATIONS S
LOCAL CONTROLS - CONTROLLERS S
LOCAL CONTROLS - INSTRUMENTS AND SENSORS S
PLUMBING - EQUIPMENT S
PLUMBING - FIXTURES S
PLUMBING - VALVES S
PLUMBING - PIPE MATERIALS S
PLUMBING - INSULATION S
PLUMBING - MISC S
BUILDING AUTOMATION SYSTEM - GRAPHICS CO
CONTRACTOR RED-LINES FOR AS-BUILT RECORDS CO
TEST, ADJUST, AND BALANCE - AIR CO
TEST, ADJUST, AND BALANCE - HYDRONIC CO
SUBMITTALS FOR THIS PROJECT SHALL BE PROVIDED IN A SINGLE ELECTRONIC
DOCUMENT WITH:
1. A TABLE OF CONTENTS.
2. USE OF HIGHLIGHTING, SCOPE BOXES, OR CHECK MARKS FOR SPECIFIED EQUIPMENT
ON THIS PROJECT.
3. LABELED PAGES FOR REFERENCE TO DEVICES, EQUIPMENT, OR INSTRUMENTS IN THE
CONTRACT DOCUMENTS.
ENGINOVA WILL REJECT A PROGRESSIVE SUBMITTAL APPROACH.
THE CONTRACTOR MAY SUBSTITUTE MATERIALS OR METHODS TO PERFORM THE SCOPE
OF WORK, HOWEVER, IT IS AT THE APPROVAL OF ENGINOVA. CONTRACTOR BID AND
PRICING SHALL REFLECT THE DRAWINGS WITHOUT SUBSTITUTE OF MATERIALS OR
METHODS. FOR DRAWING CONFLICTS OR ISSUES, REQUESTS FOR INFORMATION (RFI) OR
AN ALLOWANCE MAY BE GIVEN UNTIL FINAL DIRECTION IS PROVIDED. VALUE
ENGINEERING (VE) OR ALTERNATES MAY BE GIVEN TO ANALYZE DIFFERENTIAL COSTS,
BUT SHALL NOT BE A PART OF THE BASE BID.
BUILDING AUTOMATION POINTS LIST CO
SUBMITTALS REQUIRED
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
5
:
5
0
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
23008.00
M010
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL SCHEDULES
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
AIR-COOLED SPLIT-SYSTEM FAN-COIL SCHEDULE
MARK MANUFACTURER MODEL SERVICE AIRFLOW
(CFM)
OUTSIDE
AIR
(CFM)
FILTER
COOLING HEATING ELECTRICAL
SMOKE
DETECTOR
VIBRATION
ISOLATION
DIMENSIONS
NOTESCAPACITY
(BTUH)
SENSIBLE
(BTUH)
EAT
(°F)
LAT
(°F)
EER/
SEER
HEATING
TYPE
CAPACITY
(BTUH)
HSPF
/COP
EMERG
PWR
(Y/N)
FLA /
RLA
(A)
MCA
(A)
MOCP
(A)
LENGTH
(IN)
WIDTH
(IN)
HEIGHT
(IN)
WEIGHT
(LBS)
FC-1-1 LG KNSAP361A MDF 211 1095
N/A
(UNOCCUPI
ED)
- 34,000 27,200 80 / 67 55 / 54
SEE CU
SCHED
ULE
LOCK-OUT
HEATING N/A N/A
NO
18.4 23 30 NO N/A 47 11 14 37 FAN COIL TO BE LOCKED IN COOLING MODE. INDOOR
UNIT POWERS OUTDOOR UNIT.
FC-1-2 LG KNSAP361A MDF 211 1095 (UNOCCUPI
ED)- 34,000 27,200 80 / 67 55 / 54
SEE CU
SCHED
ULE
LOCK-OUT
HEATING N/A N/A
NO
18.4 23 30 NO N/A 47 11 14 37 FAN COIL TO BE LOCKED IN COOLING MODE. INDOOR
UNIT POWERS OUTDOOR UNIT.
CONDENSING UNIT SCHEDULE
MARK MANUFACTURER MODEL SERVICE
COOLING HEATING ELECTRICAL DIMENSIONS
NOTESCAPACITY
(BTUH)EER2/SEER2 HEATING
TYPE
CAPACITY
(BTUH/HR)HSPF V / Ph / Hz FLA/RLA MCA MOCP LENGTH
(IN)
WIDTH
(IN)
HEIGHT
(IN)
WEIGHT
(LB.)
CU-1-1 LG KUSAP361A MDF 211 34,000 10/20 NO HEATING N/A N/A 208 / 1 / 60 18.4 23 30 38 13 55 207
OUTDOOR UNIT TO POWER INDOOR UNIT. PROVIDE WITH
5,000 HOUR SALT SPRAY COIL COATING. PROVIDE BACNET
GATEWAY FOR BMS INTERGRATION FOR MONITORING
ONLY.
CU-1-2 LG KUSAP361A MDF 211 34,000 10/20 NO HEATING N/A N/A 208 / 1 / 60 18.4 23 30 38 13 55 207
OUTDOOR UNIT TO POWER INDOOR UNIT. PROVIDE WITH
5,000 HOUR SALT SPRAY COIL COATING. PROVIDE BACNET
GATEWAY FOR BMS INTERGRATION FOR MONITORING
ONLY.
EXISTING VAV TERMINAL SCHEDULE
MARK MANUFACTURER MODEL SERVICE INLET SIZE
(IN)
AIR HEATING
WEIGHT
(LBS)NOTESMINIMUM
DEAD BAND
FLOW (CFM)
HEATING
FLOW
(CFM)
COOLING
FLOW (CFM)
EAT
(°F)
LAT
(°F)
NUMBER OF
ROWS
HEAT
CAPACITY
(BTUH)
GPM EWT (°F) LWT (°F)
(E)VAV-2-1 EXISTING EXISTING STORAGE 208/209 8 75 125 360 55 85 EXISTING 4,212 0.3 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-2 EXISTING EXISTING OPEN OFFICE 200 8 70 115 320 55 85 EXISTING 3,726 0.2 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-3 EXISTING EXISTING CONFERENCE 210/OFFICE 212 8 90 155 440 55 85 EXISTING 5,022 0.3 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-4 EXISTING EXISTING OPEN OFFICE 200 8 75 125 360 55 85 EXISTING 4,212 0.3 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-5 EXISTING EXISTING OPEN OFFICE 200 8 85 150 420 55 85 EXISTING 4,860 0.3 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-6 EXISTING EXISTING OPEN OFFICE 200 10 160 280 800 55 85 EXISTING 9,072 0.6 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-7 EXISTING EXISTING OFFICE GROWTH 213 8 60 105 300 55 85 EXISTING 3,402 0.2 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-8 EXISTING EXISTING OFFICE GROWTH 213 10 180 315 900 55 85 EXISTING 10,206 0.7 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-9 EXISTING EXISTING OFFICE GROWTH 213 8 70 125 350 55 85 EXISTING 4,050 0.3 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-10 EXISTING EXISTING OFFICE GROWTH 213 10 195 335 960 55 85 EXISTING 11,016 0.7 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-11 EXISTING EXISTING OPEN OFFICE 200 10 160 280 800 55 85 EXISTING 9,072 0.6 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-12 EXISTING EXISTING OPEN OFFICE 200 10 120 210 600 55 85 EXISTING 6,804 0.5 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-13 EXISTING EXISTING OPEN OFFICE 200 12 250 440 1250 55 85 EXISTING 14,256 1.0 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-14 EXISTING EXISTING OPEN OFFICE 200 12 350 615 1750 55 85 EXISTING 19,926 1.3 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-15 EXISTING EXISTING OPEN OFFICE 200 10 130 230 650 55 85 EXISTING 7,452 0.5 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-16 EXISTING EXISTING OPEN OFFICE 200 10 190 335 950 55 85 EXISTING 10,854 0.7 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-17 EXISTING EXISTING OPEN OFFICE 200 12 190 560 1600 55 85 EXISTING 18,144 1.2 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-2-18 EXISTING EXISTING OPEN OFFICE 200 12 240 420 1200 55 85 EXISTING 13,608 0.9 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-120A-
1 EXISTING EXISTING OPEN OFFICE 200 10 195 400 970 55 85 EXISTING 11,016 0.7 180 150 EXISTING EXISTING TO REMAIN.
(E)VAV-120A-
2 EXISTING EXISTING OPEN OFFICE 200 12 100 490 1400 55 85 EXISTING 15,876 1.1 180 150 EXISTING EXISTING TO REMAIN.
PLUMBING EQUIPMENT SCHEDULE
MARK EQUIPMENT
NAME MANUFACTURER MODEL V/PH/HZ FLA OR
WATTS
MOTOR
(HP)
CONTROL
INTEGRATION
(Y/N)
OPERATIONAL
WEIGHT (LBS)DESCRIPTION
CDP-1 CONDENSATE
PUMP LITTLE GIANT EC-1K-DV 0.18 - - NO 1.7 MINI CONDENSATE PUMP. 1.8 GPH AT 1'
HEAD.
AIR DISTRIBUTION DEVICE SCHEDULE
MARK MANUFACTURER MODEL
DIMENSIONS
INSTALLATION PAINT/FINISH MATERIAL NOTESFACE SIZE NECK
SIZE
RG-1 TITUS PAR 24"x24" MATCH DUCT T-GRID MATCH CEILING STEEL MATCH EXISTING BUILDING STANARDS AS CLOSELY AS POSSIBLE.
SD-1 TITUS PCS 24"x24" MATCH DUCT T-GRID MATCH CEILING STEEL MATCH EXISTING BUILDING STANARDS AS CLOSELY AS POSSIBLE.
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
5
:
5
8
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
23008.00
M020
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL ENERGY CODE
COMPLIANCE
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T T
T
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
MTRL
CONVEYOR
CONFERENCE
210
MDF
211
OFFICE
212
AL
I
G
N
(E) ELEC
214
OFFICE GROWTH
213
(E) STAIRS
ALIGN
A
2
B
4 5
6 7 8
A.9
C
D
9
109.7
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
M220
1
M320
1
M420
1
M520
1
M620
1
11
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
6
:
0
2
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
1/16" = 1'-0"23008.00
M120
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL SECOND FLOOR
OVERALL PLAN
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
1/16" = 1'-0"
MECHANICAL SECOND FLOOR OVERALL PLAN 1
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
MTRL
CONVEYOR
CONFERENCE
210
MDF
211
OFFICE
212
AL
I
G
N
(E) ELEC
214
OFFICE GROWTH
213
(E) STAIRS
ALIGN
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
RELOCATE (E)VAV-2-2
THERMOSTAT PER M520
RELOCATE (E)VAV-2-1
THERMOSTAT PER M520
RELOCATE (E)VAV-2-12
THERMOSTAT PER M520
(R)VAV-2-3
(E)VAV-2-1
(E)VAV-2-2
(E)VAV-2-8
11
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
6
:
0
5
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
3/32" = 1'-0"23008.00
M220
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL SECOND FLOOR
DEMOLITION PLAN
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
3/32" = 1'-0"
MECHANICAL SECOND FLOOR DEMOLITION PLAN 1
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T T
T
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
MTRL
CONVEYOR
CONFERENCE
210
MDF
211
OFFICE
212
AL
I
G
N
(E) ELEC
214
OFFICE GROWTH
213
(E) STAIRS
ALIGN
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
POC OF 12"RA
TO (E)32"x16"RA
POC OF 12"RA
TO (E)32"x16"RA
1-1
FC
1-2
FC
(E)VAV-2-1
(E)VAV-2-2
(E)VAV-2-12
(E
)
1
0
"
S
A
(E
)
1
0
"
S
A
(E
)
1
0
"
S
A
(E)10"SA(E)8"SA
(E)10"SA
(E
)
1
0
"
S
A
(E)12"SA(E)8"SA
(E)60"x16"RA
(E
)
6
0
"
x
1
6
"
R
A
(E)52"x16"SA
(E
)
5
2
"
x
1
6
"
S
A
(E)34"x16"RA
(E
)
3
4
"
x
1
6
"
R
A
(E
)
4
8
"
x
1
6
"
R
A
14
"
S
A
12"SA
8"
S
A
(E)8"SA
(E)8"SA
POC OF 14"SA TO (E)VAV PLENUM
POC OF 8"SA TO (E)52"x16"SA 8"
S
A
8"
S
A
(E)8"SA
POC OF 8"SA TO (E)8"SA
POC OF 8"SA TO (R)VAV PLENUM
POC OF 8"SA
TO (E)8"SA
(E)10"SA
(E)24"SA
(E
)
1
4
"
S
A
(E
)
1
2
"
S
A
(E)10"SA
(E)16"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA (E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E
)
1
4
"
S
A
(E)14"SA
(E)12"SA
(E)18"SA
(E)16"SA
(E)10"SA
(E
)
1
8
"
x
1
4
"
S
A
(E)12"SA
(E
)
1
0
"
S
A
(E)12"SA (E)12"SA
(E)16"RA (E)16"RA
(E)18"SA(E)16"SA
(E
)
1
4
"
S
A
(E
)
1
2
"
S
A
(E
)
1
2
"
S
A
(E
)
1
0
"
S
A
(E
)
1
8
"
S
A
(E)16"SA(E)12"SA
(E)18"SA(E)10"SA
(E)10"SA
(E)10"SA
(E
)
1
8
"
R
A
(E)16"RA
(E)12"RA
(E)8"RA
(E)8"RA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA(E)12"SA
(E)12"SA
(E)16"RA
(E
)
2
4
"
S
A
(E
)
1
8
"
S
A
(E)10"SA
(E)10"SA
(E
)
1
6
"
S
A
(E)10"SA
(E)10"SA
(E)8"RA (E)12"RA
(E
)
1
4
"
R
A
(E)12"SA
(E)14"RA
(E)14"RA
(E)18"RA
(E
)
1
8
"
R
A
(E)14"RA
(E)14"RA
(E)24"RA
(E)8"RA (E)8"RA (E)8"RA (E)8"RA
(E)10"SA
(E)12"SA
(E)10"SA (E)10"SA
(E)10"SA
(E
)
1
0
"
S
A
(E
)
1
6
"
S
A
(E)12"SA
(E)16"SA
(E)12"SA
(E)14"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E
)
1
4
"
S
A
(E
)
1
2
"
S
A
(E
)
1
0
"
S
A
(E)12"SA
(E)12"SA
(E)12"SA
(E)8"SA
(E
)
1
0
"
S
A
(E)18"SA (E)12"SA
(E)14"RA
(E)14"RA
(E)12"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)10"SA
(E)12"SA
(E)12"SA
(E
)
1
0
"
S
A
(E)10"SA
(E
)
1
6
"
S
A
(E)10"S
A
(E
)
1
4
"
S
A
(E
)
2
4
"
S
A
(E)10"SA
(E)8"SA
(E
)
1
8
"
S
A
(E
)
1
2
"
S
A
(E)8"SA
(E)10"SA
(E
)
1
2
"
S
A
(E)8"SA
(E)10"SA (E)12"SA
(E)16"SA
(E)10"SA
(E)14"SA
(E)14"SA (E)10"SA
(E)14"RA
(E)14"RA
(E
)
1
8
"
R
A
(E
)
1
8
"
R
A
(E)12"RA
(E
)
1
0
"
S
A
(E
)
8
"
S
A
(E)10"SA
(E)10"SA
(E)10"SA
(E
)
1
0
"
S
A
(E
)
1
4
"
S
A
(E)14"SA
(E)12"SA
(E
)
1
4
"
R
A
(E)10"TA
(E)8"SA
(E)8"SA
(E)10"SA
(E)10"SA
(E)14"SA (E)12"SA
(E)12"SA
(E)12"SA
12
"
R
A
12
"
R
A
(E)12"RA
(E
)
8
"
S
A
(E)8"SA
(E)8"SA
(E
)
1
2
"
R
A
(E
)
1
2
"
R
A
(E)8"RA
(E)10"RA
(E
)
1
8
"
R
A
(E
)
1
4
"
R
A
8"SA
(E
)
8
"
R
A
(E
)
1
0
"
S
A
(E)10"SA
(E)10"SA (E)12"SA
(E)8"EA
(E)VAV-120A-2
(E)VAV-120A-1
(E)VAV-2-15
(E)VAV-2-16
(E)VAV-2-13
(E)VAV-2-14
(E)VAV-2-5
(E)VAV-2-17
(E)VAV-2-4
(E)VAV-2-6
(E)VAV-2-7
(E)VAV-2-8
(E)VAV-2-9
(E)VAV-2-18
(E)VAV-2-10
(E)VAV-2-11
(E)8"SA
(R)VAV-2-3
(E)22"RA
(E)10
"
R
A
(E
)
1
8
"
R
A
11
3/32" = 1'-0"
MECHANICAL SECOND FLOOR PLAN 1
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
6
:
0
9
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
3/32" = 1'-0"23008.00
M320
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL SECOND FLOOR
PLAN
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
A
2
B
4 5
6 7 8
A.9
C
D
9
109.7
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
1-2
CU
1-1
CU
REFRIGERANT
DN TO 2ND FL
11
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
6
:
0
9
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
1/16" = 1'-0"23008.00
M330
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL ROOF PLAN
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
1/16" = 1'-0"
MECHANICAL ROOF PLAN 1
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
MTRL
CONVEYOR
CONFERENCE
210
MDF
211
OFFICE
212
AL
I
G
N
(E) ELEC
214
OFFICE GROWTH
213
(E) STAIRS
ALIGN
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
REFRIGERANT
UP TO ROOF
1-1
FC
1-2
FC
11
3/32" = 1'-0"
MECHANICAL SECOND FLOOR PIPING PLAN 1
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
6
:
1
1
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
3/32" = 1'-0"23008.00
M420
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL SECOND FLOOR
PIPING PLAN
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T T
T
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
MTRL
CONVEYOR
CONFERENCE
210
MDF
211
OFFICE
212
AL
I
G
N
(E) ELEC
214
OFFICE GROWTH
213
(E) STAIRS
ALIGN
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
RELOCATED THERMOSTAT
FOR (E)VAV-2-2RELOCATED
THERMOSTAT FOR
(E)VAV-2-1
RELOCATED THERMOSTAT
FOR (E)VAV-2-12
ZONE 2-11
VAV 2-11
AHU-2-WE
ZONE 2-10
VAV 2-10
AHU-2-WE
ZONE 2-9
VAV 2-9
AHU-2-WE
ZONE 2-8
VAV 2-8
AHU-2-WE
ZONE 2-7
VAV 2-7
AHU-2-WE
ZONE 2-6
VAV 2-6
AHU-2-WE
ZONE 2-17
VAV 2-17
AHU-2-WE
ZONE 2-4
VAV 2-4
AHU-2-WE
ZONE 2-5
VAV 2-5
AHU-2-WE
ZONE 2-5
VAV 2-5
AHU-2-WE
ZONE 2-3
VAV 2-3
AHU-2-WE
ZONE 2-3
VAV 2-3
AHU-2-WE
ZONE 2-2
VAV 2-2
AHU-2-WE
ZONE 2-1
VAV 2-1
AHU-2-WE
ZONE 2-13
VAV 2-13
AHU-2-WE
ZONE 2-12
VAV 2-12
AHU-2-WE
ZONE 2-21
HP-120C
ZONE 2-22
HP-60
ZONE 2-15
VAV 2-15
AHU-2-WE
ZONE 2-20
VAV 120A-1
HP 120A
ZONE 2-19
VAV 120A-2
HP 120A
ZONE 2-16
VAV 2-16
AHU-2-WE
ZONE 2-18
VAV 120A-1
HP 120A
ZONE 2-23
FC-1/CU-1
FC-2/CU-2
11
3/32" = 1'-0"
MECHANICAL SECOND FLOOR ZONING PLAN 1
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
6
:
1
2
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
3/32" = 1'-0"23008.00
M520
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL SECOND FLOOR
ZONING PLAN
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
STORAGE
213
(E) ELEC
214
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
CONFERENCE
210
OFFICE
212
MDF
211
(E)
(E)
MTRL
CONVEYOR
(E)
(E) STAIRS
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
700
700
320
320
320 320
(E)VAV-120A-2
(E)VAV-120A-1
485
485
1200
400
400
450
250
250
250
250
250
250
250
250
250
250
250
215 215
215
320 320
?
830 840
840
840
320
320320
320
320
235
235
235
235
235
400 400
400
400
420
400 400
(E)VAV-2-16
(E)VAV-2-15
(E)VAV-2-17
(E)VAV-2-5
800
800
320
320
320
350
(E)VAV-2-11
(E)VAV-2-10
(E)VAV-2-9
(E)VAV-2-18
(E)VAV-2-6
540
540
540
225 225
SD-1
225
225
(E)VAV-2-8
(E)VAV-2-7
150
150
400
400 400
RG-1
900
RG-1
800
(E)VAV-2-14
(E)VAV-2-13
(E)VAV-2-1
(E)VAV-2-2
1100
1100
250
250
250
250 250
250 250
250
250
250250
250
450
(E)VAV-2-12
180
180
(E)VAV-2-4
(E)VAV-2-3
250
1000
SD-1
200
SD-1
200
SD-1
200
120120200200200200200
600600
100100
150150150150
150
1100
SD-1
100
100
SD-1
200
200
11
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
6
:
1
7
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
3/32" = 1'-0"23008.00
M620
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL REFLECTED
CEILING PLAN
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
3/32" = 1'-0"
MECHANICAL REFLECTED CEILING PLAN 1
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
AH-10
BV-1
AH-9
BFV-1
EQUIPMENT IDENTIFICATION AND TAGGING
1. PERMANENT LABELS SHALL BE AFFIXED TO ALL EQUIPMENT, WHETHER LOCATED INDOOR OR OUTDOOR. EQUIPMENT LABELING
REQUIREMENTS SHALL NOT BE MET THROUGH HAND-WRITTEN MARKER ON THE ENCLOSURE ITSELF OR ON TAPE.
2. MECHANICAL EQUIPMENT SHALL BE IDENTIFIED WITH AN EMBOSSED/ENGRAVED LABEL THAT IS PERMANENTLY ADHERED TO THE
ENCLOSURE OF THE UNIT IN AN EASILY OBSERVABLE LOCATION. IF LOCATED OUTDOORS IT SHALL BE ON THE NORTH OR EAST
FACES OF THE ENCLOSURE, IF POSSIBLE.
3. THE TEXT SHALL BE OF WHITE COLOR AND THE LABEL SHALL BE OF A COLOR WHICH MATCHES THE TYPICAL SERVICE.
3.1. EQUIPMENT: BLACK
3.2. WARNING LABELS AND SIGNS: RED
3.3. CHILLED WATER: GREEN
3.4. CONDENSER WATER PIPING: GREEN
3.5. HEATING WATER: YELLOW (WITH BLACK TEXT) OR RED
3.6. REFRIGERANT: PURPLE
3.7. SUPPLY AIR: BLUE
3.8. RETURN AIR: PURPLE OR MAGENTA
3.9. EXHAUST AIR: GREEN
3.10.OUTSIDE AIR: CYAN OR LIGHT BLUE
4. GENERALLY, LOCATE LABELS:
4.1. NEAR POINTS WHERE UTILITIES ENTER INTO AND EXIT FROM CONCEALED SPACES AND AT MAXIMUM INTERVALS OF 50 FEET
IN EACH SPACE WHERE DUCTS ARE EXPOSED OR CONCEALED BY REMOVABLE CEILING SYSTEM. REDUCE INTERVALS TO 25 FEET
IN AREAS OF CONGESTED CEILING SPACE.
4.2. NEAR EACH VALVE AND CONTROL DEVICE.
4.3. NEAR EACH BRANCH CONNECTION, EXCLUDING SHORT TAKEOFFS FOR FIXTURES AND TERMINAL UNITS. WHERE FLOW
PATTERN IS NOT OBVIOUS, MARK EACH PIPE AT BRANCH.
4.4. NEAR PENETRATIONS AND ON BOTH SIDES OF THROUGH WALLS, FLOORS, CEILINGS, AND INACCESSIBLE ENCLOSURES.
4.5. AT ACCESS DOORS, MANHOLES, AND SIMILAR ACCESS POINTS THAT PERMIT VIEW OF CONCEALED PIPING.
4.6. NEAR MAJOR EQUIPMENT ITEMS AND OTHER POINTS OF ORIGINATION AND TERMINATION.
5. PROVIDE FLOW DIRECTION ARROWS INTEGRAL WITH DUCT OR PIPE SYSTEMS SERVICE LETTERING, ACCOMMODATE BOTH
DIRECTIONS OR AS SEPARATE UNIT ON EACH LABEL TO INDICATE FLOW DIRECTION.
6. LABEL DIMENSION FOR EQUIPMENT MAY VARY IN SIZE, BUT SHALL BE READABLE FROM A DISTANCE OF 10 FEET.
7. ADHESIVE AND LABELS ON EQUIPMENT WHICH MAY BE HOT MUST BE ABLE TO WITHSTAND 180ºF.
8. PIPE AND PIPE INSULATION LABELS SHALL BE OF THE SELF-ADHESIVE PRINTED PLASTIC TYPE.
9. IF THIS PERMIT IS A TENANT IMPROVEMENT WITH EXISTING EQUIPMENT ALREADY IN PLACE AND/OR THERE IS A BUILDING
AUTOMATION SYSTEM, THE INSTALLING CONTRACTOR SHALL COORDINATE WITH THE BUILDING OWNER FOR THE NEXT
CHRONOLOGICAL EQUIPMENT TAG TO USE IF DIFFERING FROM THESE CONTRACT DRAWINGS.
CONTRACTOR SHALL FURNISH AND INSTALL REPLACEMENT FILTER AND
CONFIRM DAMPER ACTUATOR IS ADJUSTED AND CONTROLLING PROPERLY.
MIN. 1.5 DUCT
DIAMETERS
COLD AIR
LOW LOSS FITTING
SEE 6/MP5.1 FOR
REFERENCE
SUPPLY AIR DUCT
SLIP AND DRIVE
CLEAT CONNECTION
SOUND ATTENUATOR
OR PLENUM WITH
1" THICK DUCT LINER
5/16" DIA. STEEL ROD
VARIABLE AIR VOLUME
(VAV) AIR VALVE
FLEXIBLE COUPLING
TRANSFORMER BOX
CONTROL BOX
SUSPEND ELBOW WITH TIE
DRAW BANDS SNUG,
WITHOUT CRUSHING
FLEXIBLE DUCT
DIFFUSER
CEILING
STRUCTURE
PROVIDE DURABLE
ELBOW SUPPORT
RIGID DUCT
FLEXIBLE DUCT MAXIMUM
LENGTH 5 FT (OVERALL)
1D
M
I
N
I
M
U
M
;
3
D
P
R
E
F
E
R
R
E
D
NOTES:
1. ROUND NECK CEILING DIFFUSER SHOWN. PROVIDE SQUARE TO ROUND ADAPTER (8" MIN. HEIGHT) FOR
SQUARE NECK DIFFUSERS.
2. ROUND NECK SIZE AS INDICATED ON DRAWINGS.
3. RETURN AND EXHAUST REGISTERS INSTALLED SIMILARLY.
4. FOR HARD CEILINGS PROVIDE SURFACE MOUNTED TYPE CEILING DIFFUSERS WITH OPPOSED BLADE
DAMPERS.
5. SEE SPECIFICATION FOR AIR DISTRIBUTION TYPE.
6. WHERE FACTORY INSTALLED SHEET METAL FITTING ENDS ARE PROVIDED, ATTACH TO BRANCH DUCT
WITH SHEET METAL SCREWS AND DUCT SEALER.
7. WHEN LENGTH OF STRAIGHT DUCT UPSTREAM OF DIFFUSER IS LESS THAN 3D, PROVIDE AN EQUALIZING
GRID.
L = 1/4 * W (6" MINIMUM)
MANUAL VOLUME
BALANCING DAMPER
MAIN DUCT
DUCT BRANCH WITH
LOW-LOSS FITTING
45º
L
W
MAIN TRUNK DUCT
BRANCH DUCT
TYP.FOR 90°
45°
90° BRANCH TAKE OFF "Y" BRANCH TAKE OFF
MAIN TRUNK DUCT
BRANCH DUCT
TYP. FOR 45°
30° ELBOW 2 PCS 45° ELBOW 3 PCS 60° ELBOW 4 PCS 90° ELBOW 5 PCS
15°
15°11 1/4°
22 1/2°
11 1/4°
10°
20°
20°
10°
11 1/2°
22 1/4°
22 1/2°
22 1/4°
11 1/2"
D D MIN D D MIN D D MIN D D MIN
12" CLEARANCE FOR
REAR AND SIDES 30"
SERVICE ACCESS
CLEARANCE
ANCHOR DETAIL (TYP. 4)
CONDENSER UNIT
(2) #10X\" PLATED
TEK SCREW
16 GA.
GALVANIZED
CORNER BRACE
ANCHOR BOLT, SEE
STRUCTURAL
DWGS.
BUILDER TO SUPPLY
"DUROGRID"
HOUSEKEEPING PAD
LIQUID AND VAPOR
FRONT VIEW RIGHT VIEWLEFT VIEW
CEILING
FLOOR
TYPICAL FANCOIL
INDOOR UNIT
REFRIGERANT LINE SET TO
OUTDOOR UNIT. REFER TO
PLANS FOR ROUTING.
KNOCKOUT FOR LEFT OR RIGHT
SIDE REFRIGERANT, DRAIN,
POWER AND SIGNAL LINES
MOUNT TO WALL PER MFG.
RECOMMENDATIONS. PROVIDE
FANCOIL WITH MFG. MOUNTING
KIT.
(E) WALL
MI
N
6
'
-
0
"
MI
N
.
6
"
SCHEDULED DOOR & FRAME
FIRE/LIFE SAFETY DEVICE, TYP.
THERMOSTAT (WHERE OCCURS)
MAXIMUM 4'-0"
TYPICAL ELECTRICAL SWITCH
OCCUPANCY SENSOR, CARD
READER
ELECTRICAL AND TEL/DATA OUTLETS.
SEE PLAN FOR LOCATIONS.
3/16" MACHINE BOLT
SPIRAL GALV. SHEET METAL
DUCT AND FITTINGS.
CONNECT STRAP TO
ROOF FRAMING MEMBER
GALVANIZED SHEET METAL STRAP.
PROVIDE SEISMIC RESTRAINTS PER
LATEST EDITION, SMACNA "GUIDELINES
FOR SEISMIC RESTRAINTS OF
MECHANICAL SYSTEMS & PLUMBING
PIPING SYSTEMS."
NOTE:
WOOD CURB AT LEAST 8" HIGH ABOVE THE ROOF DECK.
CANT STRIP
MULTIPLE PIPE EXITING AWAY
FROM THE DIRECT WEATHER SIDE
OF THE CURB. SLOPE PIPES AWAY
FROM THE HOOD.
26. GA COUNTER-FLASHING
CAP SHEET BASE FLASHING FULLY
ADHERED TO THE STRIPPING PLY,
INSTALLED TO THE TOP OF THE CURB
AND 6" BEYOND THE TOE OF THE CANT.
STRIPPING/BACKER PLY FULLY
ADHERED AND EXTENDING A MIN. OF 3"
BEYOND THE TOE OF THE CANT.
CAP SHEET SURFACING
FULLY ADHERED TO THE
BASE/INTER-PLIES
BASE/INTER-PLY INSTALLED
OVER THE INSULATION/COVER
BOARD OR ROOF SUBSTRATE
INSULATE VOID IN COLD
CLIMATE
6"
3"
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
M
ICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
0
6
:
1
7
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
As indicated23008.00
M910
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
MECHANICAL DETAILS
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
SCALE:N.T.S.1 EQUIPMENT IDENTIFICATION AND TAGGING
SCALE:N.T.S.2 EXISTING RELOCATED VAV BOX DETAIL
SCALE:N.T.S.3 DIFFUSER WITH FLEXIBLE DUCT CONNECTION
SCALE:N.T.S.4 RECTANGULAR DUCT TAKE-OFF
SCALE:N.T.S.5 ROUND DUCT TAKE-OFF
SCALE:N.T.S.6 ROOFTOP CONDENSER UNIT
SCALE:N.T.S.7 WALL MOUNTED DX SPLIT SYSTEM
SCALE:N.T.S.8 THERMOSTAT MOUNTING
SCALE:N.T.S.9 DUCT HANGER EXPOSED ROUND - ISO
SCALE:N.T.S.10 SHEET METAL HOOD FLASHING
PLUMBING GENERAL NOTES
1. CONTRACTOR SHALL FIELD VEFIRY EXACT SIZE, MATERIAL AND POC OF ALL
EXISTING PIPING PRIOR TO THE COMMENCEMENT OF WORK.
2. ALL PIPING AND EQUIPMENT SHALL COMPLY WITH THE LATEST IAPMO STANDARDS
& ALL APPLICABLE BUILDING CODES, LOCAL OR OTHERWISE.
3. WASTE PIPING SHALL BE PITCHED AT A MINIMUM OF 1/4" INCH PER FOOT WHERE
POSSIBLE.PIPING GREATER THAN 4 INCHES IN DIAMETER ONLY, MAY BE PITCHED
AT A MINIMUM OF 1/8" PER FOOT, AS REQUIRED, BY THE APROVAL OF THE
ADMINSITRATIVE AUTHORITY.
4. ALL EQUIPMENT GIVING OFF WASTE OR CONDENSATE ARE REQUIRED TO DRAIN
INTO FLOOR SINKS OR OTHER APPROVED P-TRAPS.
5. WALL HUNG FIXTURES SHALL BE SECURELY ATTACHED TO WOOD BLOCKING
SECURELY FRAMED IN.
6. WATER HAMMER ARRESTORS SHALL BE PROVIDED AT EACH FIXTURE, APPLIANCE,
OR EQUIPMENT WITH QUICK CLOSING HOT AND COLD WATER CONNECTIONS.
7. HOT WATER PIPING SHALL BE INSULATED WITH FIBERGLASS PIPE INSULATION WITH
A VAPOR BARRIER, AS REQUIRED FOR LOCAL WEATHER CONDITIONS. INSULATION
OF DOMESTIC HOT WATER PIPING SHALL BE IN ACCORDANCE WITH SECTION
609.11.1 AND SECTION 609.11.2. 609.11.1 INSULATION REQUIREMENTS. DOMESTIC
HOT WATER PIPING SHALL BE INSULATED. 609.11.2 PIPE INSULATION WALL
THICKNESS. HOT WATER PIPE INSULATION SHALL HAVE A MINIMUM WALL
THICKNESS OF NOT LESS THAN THE DIAMETER OF THE PIPE FOR A PIPE UP TO 2
INCHES (50 MM) IN DIAMETER. INSULATION WALL THICKNESS SHALL BE NOT LESS
THAN 2 INCHES (51 MM ) FOR A PIPE 2 INCHES (50 MM) OR MORE IN DIAMETER.
EXCEPTIONS:
A. PIPING THAT PENETRATES FRAMING MEMBERS SHALL NOT BE REQUIRED TO
HAVE PIPE INSULATION FOR THE DISTANCE OF THE FRAMING PENETRATION.
B. HOT WATER PIPING BETWEEN THE FIXTURE CONTROL VALVE OR SUPPLY STOP
AND THE FIXTURE OR APPLIANCE SHALL NOT BE REQUIRED TO BE INSULATED.
8. THE EXACT LOCATION OF ALL ACCESS PANELS SERVING TRAP PRIMERS, SHUT-OFF
VALVES, OR SIMILAR PLUMBING DEVICES, SHALL BE APPROVED BY THE ARCHITECT
PRIOR TO INSTALLATION.
9. ALL NEW PIPING SHALL BE PRESSURE TESTED TO THE APPROVAL OF THE
ADMINISTRATIVE AUTHORITY AND MINIMUM STANDARDS AS FOLLOWS:
SANITARY PIPING: MIN. WATER PRESSURE 5 PSI FOR 15 MINUTES.
WATER PIPING: MIN. WATER PRESSURE 120 PSI FOR 15 MINUTES.
10. COLD & HOT WATER PIPING TO FIXTURES SHALL BE THOROUGHLY FLUSHED AND
RINSED PRIOR TO PLACING IN SERVICE.
11. JANITORIAL SINK FAUCETS SHALL BE PROTECTED WITH AN APPROVED BACKFLOW
PREVENTION DEVICES.CONNECTIONS BETWEEN COPPER OR BRASS PIPING WITH
FERROUS MATERIALS SHALL BE MADE WITH APPROVED DIELECTRIC COUPLINGS.
12. CONNECTIONS BETWEEN COPPER OR BRASS PIPING WITH FERROUS MATERIALS
SHALL BE MADE WITH APPROVED DIELECTRIC COUPLINGS.
13. ALL ROOF PENETRATIONS SHALL BE FLASHED AND COUNTER FLASHED TO ENSURE
A DURABLE WATERPROOF MEMBRANE.
14. ALL PIPING SHALL BE SUPPORTED AT THE MINIMUM INTERVALS SHOWN BELOW:
SIZE SUPPORT SPACING
1/2" 6 FT
3/4"8 FT
1"8 FT
1-1/4"10 FT
LARGER SIZES 10 FT
15. ALL FLOOR, WALL OR GROUND CLEAN-OUTS SHALL BE INSTALLED IN WITH
SUFFICIENT SPACE FOR SERVICE AND IN COMPLETE ACCORDANCE WITH THE
LOCAL BUILDING CODE REQUIREMENTS
16. ALL FLOOR MOUNTED SANITARY CLEAN-OUTS SHALL HAVE SKID-RESISTANT COVER
PLATES.
17. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, THE DRAWINGS ARE
ESSENTIALLY DIAGRAMMATIC AND, ALTHOUGH SIZE AND LOCATION OF EQUIPMENT
IS DRAWN TO SCALE WHEREVER POSSIBLE, THE CONTRACTOR SHALL MAKE USE
OF ALL DATA IN ALL OF THE CONTRACT DOCUMENTS, AND VERIFY THIS
INFORMATION AT THE BUILDING SITE.
18. DRAWINGS INDICATE REQUIRED SIZE AND TERMINATION OF PIPES AND DUCTWORK,
AND SUGGEST PROPER ROUTES OF PIPING TO CONFORM TO THE STRUCTURE, TO
AVOID OBSTRUCTIONS AND TO PRESERVE CLEARANCE. HOWEVER, IT IS NOT THE
INTENTION TO INDICATE ALL NECESSARY OFFSETS AND IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE PIPING AND DUCTWORK IN
SUCH A MANNER AS TO CONFORM TO THE STRUCTURE, AVOID OBSTRUCTIONS,
PRESERVE HEADROOM, KEEP OPENINGS & PASSAGEWAYS CLEAR, & MAKE ALL
EQUIPMENT REQUIRING INSPECTION, MAINTENANCE OR REPAIR, ACCESSIBLE
WITHOUT FURTHER INSTRUCTIONS OR EXTRA COST TO THE OWNER.
19. CROSS CONNECTION PROTECTION SHALL BE PROVIDED AT ALL POTABLE WATER
SUPPLIED APPLIANCES OR EQUIPMENT.
PLUMBING NOTES
1. INSULATION MATERIAL SHALL MEET THE CALIFORNIA QUALITY STANDARD PER
SECTION 110.8 ENERGY EFFICIENCY STANDARDS (E.E.S.).
2. ALL PIPING SHALL BE INSULATED CONSISTENT WITH THE REQUIREMENTS OF
SECTIONS 120.3, 120.4 AND 120.7 TITLE 24 ENERGY STANDARDS AND CHAPTER 6
CMC.
3. EACH FIXTURE TRAP SHALL HAVE A PROTECTING VENT SO LOCATED THAT THE
DEVELOPED LENGTH OF THE TRAP ARM FROM THE TRAP WEIR TO THE INNER EDGE
OF THE VENT SHALL BE WITHIN THE DISTANCE GIVEN IN TABLE 1002.2 CPC, BUT IN
NO CASE LESS THAN TWO TIMES THE DIAMETER OF THE TRAP ARM.
4. EACH PLUMBING FIXTURE THAT CONNECTS TO THE SANITARY SEWER SYSTEM
SHALL BE PROPERLY TRAPPED AND VENTED IN ACCORDANCE WITH THE 2022 CPC.
5. BUILDING DRAIN AND VENT PIPING MATERIALS SHALL COMPLY WITH SECTIONS 701.0
AND 903.0 OF THE CALIFORNIA PLUMBING CODE.
6. EACH VENT SHALL RISE VERTICALLY TO A POINT OF NOT LESS THAN SIX (6) INCHES
ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE BEING SERVED BEFORE
OFFSETTING HORIZONTALLY OR BEFORE BEING CONNECTED TO ANY OTHER VENT.
7. WATER HEATER (IH-1) IS A LISTED NON-STORAGE, INSTANTANEOUS HEATER HAVING
AN INSIDE DIAMETER OF NOT MORE THAN 3 INCHES.
8. LAVATORY FAUCETS IN RESTROOMS SHALL BE THE SELF CLOSING TYPE AND SHALL
NOT EXCEED A WATER FLOW OF 0.20 GALLONS PER CYCLE.
9. EACH SHOWERHEAD SHALL NOT EXCEED A WATER FLOW OF 1.8 GPM.
10. EACH KITCHEN FAUCET SHALL NOT EXCEED A WATER FLOW OF 1.8 GPM.
GM
1%
SYMBOL ABBR SYMBOL
PLUMBING LEGEND
BFV
CV
BV
PRV
BV
DESCRIPTION DESCRIPTIONABBR
S
S
V
CW
HW
HWR
G
N2
H2
CO2
LN2
LV
CD
CWS
CWR
DI
GV
AV
SOV
MV
MV
P&TRV
TP
BP
FC
WHA
HB
FDC
PG
GM
GR
SYMBOL DESCRIPTIONABBR
WCO
FS
FCO
FD
AD/DD
IWR
RD/OD
POC
POD
VTR
ACTUATOR VALVE
AUTOMATIC AIR VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
BALANCING VALVE
GLOBE VALVE
PRESSURE REDUCING VALVE
BOTTOM OF PIPE TAKEOFF
TOP OF PIPE TAKEOFF
PIPE DOWN
PIPE UP
G NATURAL GAS PIPING
S SANITARY OR WASTE PIPING
ABOVE GRADE OR FLOOR SLAB
S SANITARY OR WASTE PIPING
BELOW GRADE OR FLOOR SLAB
V WASTE VENT PIPING
CW DOMESTIC COLD WATER PIPING
HW DOMESTIC HOT WATER PIPING
(14O° F MAXIMUM)
HWR DOMESTIC HOT WATER
RECIRCULATING PIPING
N2
H2
CO2
LN2
LAB HYDROGEN PIPING
CARBON DIOXIDE PIPING
LIQUID NITROGEN PIPING
LAB NITROGEN PIPING
LV LAB VACUUM PIPING
CD CONDENSATE DRAIN PIPING
CWR CHILLED WATER RETURN PIPING
CWS CHILLED WATER SUPPLY PIPING
DI DEIONIZED WATER PIPING
IW INDUSTRIAL WASTE PIPING
ABOVE GRADE OR FLOOR SLAB
AW ACID WASTE PIPING ABOVE
GRADE OR FLOOR SLAB
AV ACID VENT PIPING
MPG MEDIUM PRESSURE GAS
HHWS HEATING HOT WATER SUPPLY
HHWR HEATING HOT WATER RETURN
IW
AW
AV
MPG
HHWS
HHWR
TG TRIPLE GASTG
CA COMPRESSED AIRCA
DIRECTION OF FLOW
UNION
REDUCER OR INCREASER
GATE VALVE
MIXING VALVE
GAS COCK VALVE
TRAP PRIMER VALVE
BACKFLOW PREVENTER
STRAINER
PIPE CAP
FLEXIBLE PIPE CONNECTION
WATER HAMMER ARRESTOR
HOSE BIBB
SHUT-OFF VALVE ON RISER OR
DROP
PRESSURE GAUGE
GAS METER
GAS REGULATOR
THERMOMETER
WALL CLEANOUT
FLOOR DRAIN
FLOOR SINK
INDIRECT WASTE RECEPTOR
AREA DRAIN OR DECK DRAIN
POINT OF CONNECTION
POINT OF DISCONNECT
VENT THRU ROOF
PIPING SLOPE
GM
1%
S
S
V
CW
HW
HWR
G
N2
H2
CO2
LN2
LV
CD
CWS
CWR
DI
HB
PG
GM
GR
WCO
FS
FCO
FD
AD/DD
IWR
RD/OD
POC
POD
VTR
BOTTOM OF PIPE TAKEOFF
TOP OF PIPE TAKEOFF
PIPE DOWN
PIPE UP
G
S
S
V
CW
HW
HWR
N2
H2
CO2
LN2
LV
CD
CWR
CWS
DI
IW
AW
AV
MPG
HHWS
HHWR
IW
AW
AV
MPG
HHWS
HHWR
TG TG
CA CA
DIRECTION OF FLOW
PRESSURE & TEMPERATURE
RELIEF VALVE
HOSE BIBB
FIRE DEPARTMENT
CONNECTION
PRESSURE GAUGE
GAS METER
GAS REGULATOR
THERMOMETER
WALL CLEANOUT
FLOOR CLEANOUT OR CLEANOUT
TO GRADE
FLOOR DRAIN
FLOOR SINK
INDIRECT WASTE RECEPTOR
ROOF DRAIN & OVERFLOW ROOF
DRAIN
AREA DRAIN OR DECK DRAIN
POINT OF CONNECTION
POINT OF DISCONNECT
PIPING OR EQUIPMENT TO BE
REMOVED (DEMO PATTERN)
VENT THRU ROOF
PIPING SLOPE
NOT IN SCOPE PATTERN
AREA OF WORK PATTERN
WATER CALCULATION
PRESSURE ANALYSIS (PSIG)
TOTAL FIXTURE UNITS (FLUSH TANK)
TOTAL DEMAND (GPM)
MAXIMUM STREET MAIN PRESSURE
MINIMUM STREET MAIN PRESSURE
PRESSURE LOSS THROUGH WATER METER
PRESSURE LOSS THROUGH BACKFLOW PREVENTER
OTHER PRESSURE LOSSES (WATER SOFTENER, ETC.)
FALL-OFF THROUGH PRESSURE REDUCING VALVE AT TOTAL DEMAND
PRV INLET PRESSURE / DESIGN PRESSURE
PRV OUTLET PRESSURE OR
DESIGN PRESSURE
PRESSURE REQUIRED AT
FIXURE/EQUIPMENT
DIFFERENCE IN ELEVATION LONGEST PIPE RUN + 30%
DEVELOPED LENGTH X 1.3
ALLOWABLE PRESSURE (PSI) =
ALLOWABLE PRESSURE DROP PER 100 FT. (PSI) =
*WATER SYSTEM DESIGNED BASED ON 2022 CPC APPENDIX A
65
30
35
1492
17.1
1.1
87
70
99
29
92
7
10
0
5
PIPE SIZE SCHEDULE
ALLOWABLE FRICTION LOSS. POUNDS PER SQUARE INCH
PER 100 FT LENGTH
SIZE
(IN.)
GPM FTFU's FVFU'S VELOCITY (FPS)
CW HW CW HW CW CW HW
*PIPE SIZE BASED ON CALIFORNIA PLUMBING CODE 2022 EDITION. MAXIMUM VELOCITY 8
FPS FOR COLD WATER AND 5 FPS FOR HOT WATER.
COPPER PIPE
1.5
1/2"1.21
3/4"
1"
1 1/4"
1 1/2"
2"
2 1/2"
3"
3 1/2"
4"
3.15
6.25
11.6
18.2
36.5
64.9
119
154
221
1.21
3.15
6.25
11.6
18.2
36.5
64.9
115
142
185
1.21
4
7.5
15
26
70
200
475
661
1,090
1
4
7.5
15
26
70
200
455
592
844
0
0
1.25
2.25
4
22
92
352
584
1,090
1.58
1.98
2.39
2.74
3.04
3.75
4.41
5.13
5.48
6.07
1.58
1.98
2.39
2.74
3.04
3.75
4.41
5
5
5
SHEET NUMBER NOMENCLATURE
SHEET
TYPE DESCRIPTION
0 LEAD SHEETS LEGEND, NOTES, SYMBOLS AND SCHEDULES
1 SITE PLAN
2
DEMOLITION PLANS
WASTE AND VENT
3 WATER AND GAS
4
NEW PLANS
WASTE AND VENT
5 WATER AND GAS
6 LAB GAS
7 ENLARGED PLAN
8 DIAGRAMS
9 DETAILS
P 4 1 1
DISCIPLINE DESIGNATION
SERIES TYPE
BUILDING LEVEL
BUILDING AREA / SEQUENCE
NUMBER
PLUMBING WASTE AND VENT...
SHEET TITLE
APPLICABLE CODES
APPLICABLE CODES, STANDARDS, GUIDELINES AND AHJS
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA GREEN BUILDING CODE
2022 CALIFORNIA BUILDING ENERGY EFFICIENCY STANDARDS
CURRENT EDITION NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
CURRENT EDITION AMERICANS WITH DISABILITIES ACT (ADA)
RESIDENTIAL & NON-RESIDENTIAL
MAXIMUM FIXTURE FLOW RATES
FIXTURE TYPE MAXIMUM FLOW RATE
WATER CLOSETS 1.28 GALLONS/FLUSH
URINALS (WALL MOUNTED)0.125 GALLONS/FLUSH
URINALS (FLOOR MOUNTED)0.5 GALLONS/FLUSH
SHOWERHEADS 1.8 GPM @60 PSI
NON-RESIDENTIAL LAVATORY FAUCETS 0.5 GPM @60 PSI
NON-RESIDENTIAL METERING FAUCETS 0.2 GALLONS/CYCLE
RESIDENTIAL LAVATORY FAUCETS 1.2 GPM @60 PSI
KITCHEN FAUCETS 1.8 GPM @60 PSI
MANDATORY MEASURES
PLUMBING SHEET LIST
SHEET NUMBER SHEET NAME
P001 PLUMBING LEGEND, NOTES, SCHEDULES AND SYMBOLS
P002 PLUMBING NOTES AND SCHEDULES
P420 PLUMBING SECOND FLOOR PLUMBING PLAN
P910 PLUMBING DETAILS
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
MICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO.CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
4
2
:
2
8
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
23008.00
P001
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
PLUMBING LEGEND, NOTES,
SCHEDULES AND SYMBOLS
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
1
1
P410
WH
1
PLUMBING KEYNOTE
EQUIPMENT TYPE
UNIT NUMBER
DETAIL NUMBER
SHEET NUMBER
PLUMBING ABBREVIATION
ABBR DESCRIPTION ABBR DESCRIPTION ABBR DESCRIPTION ABBR DESCRIPTION
ACL ABOVE CEILING FCO FLOOR CLEANOUT L LAVATORY (R)RELOCATED
AFF ABOVE FINISHED FLOOR FD FLOOR DRAIN L LENGTH SP SAMPLING PORT
ARCH ARCHITECT OR ARCHITECTURAL FF FINISHED FLOOR LBS POUNDS SS SCULLERY SINK
BOP BOTTOM OF PIPE FFE FINISHED FLOOR ELEVATION MAX MAXIMUM TB TEA BREWER
B/F BELOW FLOOR FG FINISHED GRADE MBH BRITISH THERMAL UNITS PER
HOUR x1000 TP TRAP PRIMER
B/G BELOW GRADE FPM FEET PER MINUTE MIN MINIMUM TYP TYPICAL
BLDG BUILDING FPS FEET PER SECOND MFR MANUFACTURER UG UNDERGROUND
BR BROILER FR FRYER MS MOP SINK UR URINAL
BS BAR SINK FS FLOOR SINK (N)NEW W WIDTH
BTUH BRITISH THERMAL UNITS PER
HOUR FT FOOT (FEET)NA NOT APPLICABLE WC WATER CLOSET
BV BALANCING VALVE GCO GRADE CLEANOUT NIPC NOT IN PLUMBING CONTRACT WCO WALL CLEANOUT
CAR CARBONATOR GD GRIDDLE NC NORMALLY CLOSED WF WATER FILTER
CM COFFEE MAKER GI GREASE INTERCEPTOR OFCI OWNER FURNISHED CONTRACTOR
INSTALLED WH WATER HEATER
COV CONVENTIONAL OVER GPF GALLONS PER FLUSH PG PRESSURE GAUGE WHA WATER HAMMER ARRESTER
CONN CONNECTION GPH GALLONS PER HOUR PH PATIO HEATER WT WEIGHT
CP CIRCULATING PUMP GPM GALLONS PER MINUTE PH PHASE (ELECTRICAL)W/ WITH
(D)DEMOLITION GR GAS REGULATOR POC POINT OF CONNECTION W/O WITHOUT
DF DRINKING FOUTAIN H HEIGHT PRV PRESSURE REDUCING VALVE
DW DISH WASHER HB HOSE BIB PS PREP SINK
DWGS DRAWINGS HP HOT PLATE PSIA POUNDS PER SQUARE INCH (ABS)
(E)EXISTING HS HAND SINK PSIG POUNDS PER SQUARE INCH
(GAUGE)
ET EXPANSION TANK IE INVERT ELEVATION PZ PIZZA OVEN
(F)FUTURE IM ICE MAKER QTY QUANTITY
F FAHREINHEIT (TEMPERATURE)JD JUICE DESPENSER R ROOF MOUNTED
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
MICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
4
2
:
2
9
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
23008.00
P002
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
PLUMBING NOTES AND
SCHEDULES
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
PIPING MATERIAL SCHEDULE
SERVICE MATERIAL STANDARD SIZE FITTINGS JOINING METHOD HORIZONTAL HANGER
INTERVAL HANGER SIZE VERTICAL SUPPORT
INTERVAL VALVE INSULATION
TYPE
INSULATION
THICKNESS INSULATION VALUE
VENT ABOVE GRADE INSIDE BUILDING PVC DWV SCH.40 SOLID
CORE
ASTM D1785
ASTM D2665
ASTM F794 OR F1866
ALL GLUED GLUED
PIPE < 4'-0" LENGTH: EVERY
OTHER JOINT
PIPE 4'-0" LENGTH: EACH JOINT
1/2" - 4": 3/8"
5" - 8": 1/2"
10" - 12": 5/8"
BASE & EACH FLOOR
NO GREATER THAN 10'-0"N/A N/A N/A -
CONDENSATE PIPING ABOVE GRADE INSIDE
BUILDING
SEAMLESS TYPE "M"
COPPER ASTM B75 - WROT COPPER - 6'-0"1/2" - 4": 3/8"
5" - 8": 1/2"
BASE & EACH FLOOR
NO GREATER THAN 10'-0"-CLOSED CELL
ELASTOMERIC N/A -
SEWER & WASTE BELOW GRADE INSIDE
BUILDING
PVC DWV SCH.40 SOLID
CORE
ASTM D1785
ASTM D2665
ASTM F794 OR F1866
ALL GLUED GLUED N/A N/A N/A N/A N/A N/A -
DOMESTIC COLD WATER PIPING
ABOVE GRADE
INSIDE BUILDING
SEAMLESS TYPE L COPPER ASTM B88
1/2" - 1-1/2"
------------------
2" - 6"
WROT COPPER LEAD-FREE SOLDER
6'-0"
--------------
10'-0"
1/2" - 4": 3/8"
5" - 8": 1/2"
BASE & EACH FLOOR
NO GREATER THAN 10'-0"
FULL PORT BALL
SWEAT x SWEAT
----------------------
BUTTERFLY
150 PSI FLANGE
N/A N/A -
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
PLUMBING EQUIPMENT SCHEDULE
MARK EQUIPMENT
NAME MANUFACTURER MODEL V/PH/HZ FLA OR
WATTS
MOTOR
(HP)
CONTROL
INTEGRATION
(Y/N)
OPERATIONAL
WEIGHT (LBS)DESCRIPTION
CDP-1 CONDENSATE
PUMP LITTLE GIANT EC-1K-DV 0.18 - - NO 1.7 MINI CONDENSATE PUMP. 1.8 GPH AT 1'
HEAD.
PLUMBING FIXTURE SCHEDULE
ITEM FIXTURE MIN. BRANCH SIZE DESCRIPTIONCW HW V SW
BF-1 BOTTLE FILLER 3/4" - 1-1/4" 2" ELKAY LBWD00WHC BOTTLE FILLER. 115/60/1 FLA: 1A. REMOTE CHILLER 115/60/1.
OPEN OFFICE
200
(E) ELEC
201
CONFERENCE
202
OFFICE
203
OFFICE
204
OFFICE
205
STORAGE
206
STORAGE
207
STORAGE
208
STORAGE
209
MTRL
CONVEYOR
CONFERENCE
210
MDF
211
OFFICE
212
AL
I
G
N
(E) ELEC
214
OFFICE GROWTH
213
(E) STAIRS
ALIGN
A
2
B
4 5
A.9
C
D
31
E
F
G
F.8
E.8
E.2
D.2
C.5
B.8
B.2
A.2
D.5
B.5
A.5
3/4"CW
POC 2"S TO (E)S POC 3/4"CW TO (E)CW
POC 1-1/2"V TO (E)V
1 1/2"V
2"S
BF-1
11
FC 1-2
FC 1-1
3/4"CD
2%
3/4"CD DN TO MOP SINK
(6 TONS)
(E)MS-1
1
CDP
1
CDP
CO
CHECK VALVE
(TYP. OF 2)
3/32" = 1'-0"
PLUMBING SECOND FLOOR PLUMBING PLAN 1
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
MICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
4
2
:
3
0
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
3/32" = 1'-0"23008.00
P420
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
PLUMBING SECOND FLOOR
PLUMBING PLAN
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
SPACE FILLED WITH FIRE-PROOF
PACKING. PACKING SHALL BE AN
APPROVED MATERIAL CAPABLE
OF MAINTAINING ITS INTEGRITY
WHEN SUBJECTED TO TEST
TEMPERATURE PRESCRIBED IN
U.B.C. STD. NO. 43-1 FOR SPECIFIC
WALL OR PARTITION #1479584 &
ASTM-E-814 FIRE TEST
STANDARDS. SEE SPECS.
CAULK ALL AROUND
BOTH SIDES (TYP.)
PIPE
BARE PIPE
WALL
NOTE:
SEE ARCHITECTURAL DETAILS FOR EXACT PENETRATION REQUIREMENTS
EXP. 03/26
N
A
O
E
M
T
R
TS
A
FEFOLCAI
AEHC INC
E
T
RE
SI
G
D
NO. M 3 5 8 0 7
ERFOP ISSO
R
R
IAL
N
E
EN
E
NGI
AL
MICHAEL A .CARLOMAGNO
N
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED
WITHOUT WRITTEN CONSENT OF ARCHITECT. COPYRIGHTED.
PROJECT NO. CHECKED BY
SHEET NO.
SCALE @ ARCH E1
SHEET NAME
CLIENT NAME
ARCHITECT'S STAMP
PROJECT TEAM
KEY PLAN
MEP ENGINEER
CONTRACTOR
12
/
1
8
/
2
0
2
5
2
:
4
2
:
3
0
P
M
C:
\
L
o
c
a
l
R
e
v
i
t
\
2
0
2
6
\
2
5
0
2
1
9
C
o
l
l
e
c
t
o
r
s
P
h
a
s
e
4
.
M
E
P
2
6
_b
h
e
r
m
a
n
S
H
E
6
7
.
r
v
t
N.T.S.23008.00
P910
sna1610ph4 -PHASE 4
1610 E ST ANDREW PL, SUITE 240
SANTA ANA, CA 92705
Approver
PLUMBING DETAILS
COLLECTORS
ENGINOVA
13125 DANIELSON STREET, SUITE 101
POWAY, CA 92064
858-228-4150
-
RAM CONSTRUCTION
20 EXECUTIVE PARK, SUITE 250
IRVINE, CA 92614
949-418-7688
ISSUE RECORD
∆ DATE REASON FOR ISSUE BY
SCALE:N.T.S.1 PIPE PENETRATION THRU WALL
SCALE:
CDP
1
1%
T-BAR CEILING
2 MINI CONDENSATE PUMP
N.T.S.
CHECK VALVE
CLEANOUT
WYE PIPE FITTING
FLEXIBLE PIPING FROM
CONDENSATE PUMP TO
GRAVITY DRAIN
CONDENSATE FROM
WALL MOUNTED
MECHANICAL UNIT
PUMP
RESERVOIR ASSEMBLY
RIGIDLY SECURED
GRAVITY CONDENSATE
DRAIN PIPE
PUMP POWER FROM WALL
MOUNTED FAN COIL
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
This document is used to demonstrate compliance for mechanical systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive
path outlined in 140.4, or 141.0(b)2 for alterations.
Project Name: Collectors Universe Report Page: (Page 1 of 11)
Project Address: 1610 E St Andrew Pl, Suite 240 Date Prepared: 12/12/2025
A. GENERAL INFORMATION
01 Project Location (city)Santa Ana 04 Total Conditioned Floor Area 384
02 Climate Zone 8 05 Total Unconditioned Floor Area 0
03 Occupancy Types Within Project:06 # of Stories (Habitable Above Grade)1
● All Other Occupancies
B. PROJECT SCOPE
This table Includes mechanical systems or components that are within the scope of the permit application and are demonstrating compliance using the prescriptive path outlined in
140.4, 170.2(b) or 141.0(b)2 and 180.2(b)2 for alterations.
01 02 03
Air System(s)Wet System Components Dry System Components
Heating Air System Water Economizer Air Economizer
Cooling Air System Pumps Electric Resistance Heat
Mechanical Controls System Piping Fan Systems
Mechanical Controls (existing to remain, altered
or new)Cooling Towers Ductwork (existing to remain, altered or new)
Chillers Ventilation
Boilers Zonal Systems/ Terminal Boxes
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 2 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
C. COMPLIANCE RESULTS
Table C will indicate if the project data input into the compliance document is compliant with mechanical requirements. This table is not editable by the user. If this table says "DOES
NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D., or the table indicated as not compliant for guidance.
01
AND
02
AND
03
AND
04
AND
05
AND
06
AND
07
AND
08 09
System
Summary
110.1,
110.2,
140.4,
170.2(c)
Pumps
140.4(k),
170.2(c)4I
Fans/
Economizers
140.4(c),
140.4(e),
170.2(c)
System
Controls
110.2, 120.2,
140.4(f),
170.2(c)
Ventilation
120.1, 160.2
Terminal Box
Controls
140.4(d),
170.2(c)4B
Distribution
120.3,
140.4(l),
160.2, 160.3
Cooling Towers
110.2(e)2 Compliance Results
(See Table F)(See Table G)(See Table H)(See Table I)(See Table J)(See Table K)(See Table L)(See Table M)
Yes AND AND Yes AND Yes AND Yes AND AND AND COMPLIES
Mandatory Measures Compliance (See Table Q for Details)COMPLIES
D. EXCEPTIONAL CONDITIONS
This table is auto-filled with uneditable comments because of selections made or data entered in tables throughout the form.
E. ADDITIONAL REMARKS
This table includes remarks made by the permit applicant to the Authority Having Jurisdiction.
F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS)
Space Conditioning System Information
01 02 03 04 05 06
System Name Quantity System Serving System Status Space Type Utilizing Recovered Heat
FC-1/CU-1 1 Single zone New/ Addition
FC-2/CU-2 1 Single zone New/ Addition
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 3 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS)
Dry System Equipment Sizing (includes air conditioners, condensers, heat pumps, VRF, furnaces and unit heaters and DOAS systems)
01 02 03 04 05 06 07 08 09 10 11
Name or Item
Tag
Equipment Category per
Tables 110.2, 140.4(a)2 and
170.2(c)3aii
Equipment Type per Tables 110.2 and
Title 20
Smallest Size
Available1
140.4(a) and
170.2(c)1
Equipment Sizing per Mechanical Schedule (kBtu/h)
140.4(a&b), 170.2(c)1 & 170.2(c)2
Heating Output2,3 Cooling Output2,3 Load Calculations3,4
Per Design
(kBtu/h)
Rated
(kBtu/h)
Supp.
Heating
Output
(kBtu/h)
Sensible
Per Design
(kBtu/h)
Rated
(kBtu/h)
Total
Heating
Load
(kBtu/h)
Total
Sensible
Cooling
Load
(kBtu/h)
FC-1/CU-1 Unitary AC/ Condensers AC, air cooled, split (3 phase)NA: Load
Controls 0 0 0 13.43 27 0 44.28
FC-2/CU-2 Unitary AC/ Condensers AC, air cooled, split (3 phase)NA: Load
Controls 0 0 0 13.43 27 0 44.28
1FOOTNOTES: Equipment shall be the smallest size, within the available options of the desired equipment line, necessary to meet the design heating and cooling loads of the building per
140.4(a) and 170.2(c)1. Healthcare facilities are excepted.
2It is common practice to show rated output capacity on the equipment schedule. Sensible cooling output comes from specification sheet tables.
3 If equipment is heating only, leave cooling output and load blank. If equipment is cooling only, leave heating output and load blank.
4 Authority Having Jurisdiction may ask for load calculations used for compliance per 140.4(b) and 170.2(c).
Dry System Equipment Efficiency (other than Package Terminal Air Conditioners (PTAC) and Package Terminal Heat Pumps (PTHP), DX-DOAS and Dual Fuel Heat Pumps)
01 02 03 04 05 06 07 08 09
Name or Item
Tag
Size Category
(Btu/h)
Heating Mode Cooling Mode
Rating
Condition
( °F)
Efficiency Unit
Minimum
Efficiency
Required per
Tables 110.2 /
Title 20
Design Efficiency Efficiency Unit
Minimum
Efficiency
Required per
Tables 110.2 /
Title 20
Design Efficiency
FC-1/CU-1 <65,000 SEER2 14.3 20
FC-2/CU-2 <65,000 SEER2 14.3 20
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 4 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
G. PUMPS
This section does not apply to this project.
H. FAN SYSTEMS & AIR ECONOMIZERS
This table is used to demonstrate compliance with prescriptive requirements found in 140.4(c), 140.4(e), 140.4(m), 170.2(c)3, and 170.2(c)4A for fan systems. Fan systems serving only
process loads are exempt from these requirements and do not need to be included in Table H.
System
Name FC-1/CU-1 Quantit
y 1 Fan System
Status New System
Zoning
all other
systems
Serving
Dwelling
Units
Not
Serving
Dwelling
Units
Fan
System
Airflow
(cfm)
0 Site
Elevation 115 Economizer
NA: Special
OA
filtration
01 02 03 04 05 06 07 08 09 10 11
Fan
Name
or Item
Tag
Fan Type Qty Component Airflow through
Component (%)
Water
Gauge
(w.g)
Allowance Design
Compone
nt
Allowance
Fan
Allowance
(watt/cfm)
3
Design Electrical Input Power
Method
Motor
Nameplate
Horsepower
Design
Electrical
Input
Power (kW)
SF Supply 1
Base Allowance for system serving
spaces <=6 floors away 100 0
MERV 13-16 Filter upstream of
thermal conditioning equipment 100 0
Hydronic/DX cooling coil or heat
pump coil 100 0
Manufacturer provided 0
Supply Fan Base
Allowance (kW)
Exhuast/Return/Relief/Transfer Fan Base
Allowance(kW)
Fan System
Allowance (kW)3 1 Fan System Electrical
Output (kW)0
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 5 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
H. FAN SYSTEMS & AIR ECONOMIZERS
System
Name FC-2/CU-2 Quantit
y 1 Fan System
Status New System
Zoning
all other
systems
Serving
Dwelling
Units
Not
Serving
Dwelling
Units
Fan
System
Airflow
(cfm)
0 Site
Elevation 115 Economizer
NA: Special
OA
filtration
01 02 03 04 05 06 07 08 09 10 11
Fan
Name
or Item
Tag
Fan Type Qty Component Airflow through
Component (%)
Water
Gauge
(w.g)
Allowance Design
Compone
nt
Allowance
Fan
Allowance
(watt/cfm)
3
Design Electrical Input Power
Method
Motor
Nameplate
Horsepower
Design
Electrical
Input
Power (kW)
SF Supply 1
Base Allowance for system serving
spaces <=6 floors away 100 0
MERV 13-16 Filter upstream of
thermal conditioning equipment 100 0
Hydronic/DX cooling coil or heat
pump coil 100 0
Manufacturer provided 0
Supply Fan Base
Allowance (kW)
Exhuast/Return/Relief/Transfer Fan Base
Allowance(kW)
Fan System
Allowance (kW)3 1 Fan System Electrical
Output (kW)0
1 FOOTNOTES: Fans serving spaces with design background noise goals below NC35
2 Low-turndown single-zone VAV fan system must be capable of and configured to reduce airflow to 50 percent of
design airflow and use no more than 30 percent of the design wattage at that airflow. No more than 10 percent of the
design load served by the equipment shall have fixed loads.
3 Fan system allowance includes fan system base allowance.
4 Filter pressure loss can only be counted once per fan system.
5 Complex Fan System means a fan system that combines a single cabinet fan system with other supply fans, exhaust
fans, or both.
6 Computer room economizers must meet requirements of 140.9(a) and will be documented on the NRCC-PRC-E
document..
H. EXHAUST AIR HEAT RECOVERY 140.4(q), 170.2(c)4O
01 02 03 04 05 06 07 08 09 10 11
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 6 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
H. EXHAUST AIR HEAT RECOVERY 140.4(q), 170.2(c)4O
Fan System
Name Qty
Hours of
Operation per
Year
Design Supply
Airflow Rate
Outdoor
Airflow
% Outdoor Air
at Full Design
Airflow
Exemptions to
Exhaust Air
Heat Recovery
Requirement
per 140.4(q) &
170.2(c)4O
Exhaust Air
Heat Recovery
140.4(q) &
170.2(c)4O
Type Of Heat
Recovery Rating
Required
Recovery Ratio
Energy
Recovery
Bypass
Fan Energy Index (FEI)
01 02 03
Name or Item Tag FEI Exception FEI
FC-1/CU-1 None Applies 1
FC-2/CU-2 None Applies 1
I. SYSTEM CONTROLS
This table is used to demonstrate compliance with mandatory controls in 110.2 and 120.2 and prescriptive controls in 140.4(f) and (n), 170.2(c)4D 170.2(c)4L or requirements in
141.0(b)2E 180.2(b)2 for altered space conditioning systems.
01 02 03 04 05 06 07 08 09
System Name System
Zoning
Conditioned
Floor Area
Being Served
(ft2)
Thermostats
110.2(b) & (c)1, 120.2(a)
160.3(a)2A or 141.0(b)2E &
180.2(b)2
Shut-Off
Controls
120.2(e) &
160.3(a)2D
Isolation
Zone
Controls
120.2(g) &
160.3(a)2F
Demand Response
110.12 120.2(b) &
160.3(a)2B
Supply Air
Temp. Reset
140.4(f) &
170.2(c)4D
Window Interlocks per
140.4(n) & 170.2(c)4D
FC-1/CU-1 Single zone <= 25,000 ft2 Setback Auto Timer
Switch 4 Hour Timer EMCS
NA: Would
increase
energy use
Provided
FC-2/CU-2 Single zone <= 25,000 ft2 Setback Auto Timer
Switch 4 Hour Timer EMCS
NA: Would
increase
energy use
Provided
1FOOTNOTES: Gravity gas wall heaters, gravity floor heaters, gravity room heaters, non-central electric heaters, fireplaces or decorative gas appliances, wood stoves are not required to
have setback thermostats.
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 7 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
J. VENTILATION AND INDOOR AIR QUALITY
This table is used to demonstrate compliance with mandatory ventilation requirements in 120.1 120.2(e)3B 140.4(p) and 140.4(q) for all nonresidential and hotel/motel and
d:t24refnolink/]160.2, 160.3(a)3D, 170.2(a)4N, 170.2(a)4O for high-rise residential occupancies. For alterations, only ventilation systems being altered within the scope of the permit
application need to be documented in this table. In lieu of this table, the required outdoor ventilation rates and airflows may be shown on the plans or the calculations can be presented
in a spreadsheet.
01 Check the box if the project is showing ventilation calculations on the plans, or attaching the calculations instead of completing this table.
02 Check this box if the project included Nonresidential, Hotel/Motel Spaces or Multifamily Common Use Spaces
03 Check the box if the project is using natural ventilation in any nonresidential or hotel/motel spaces to meet required ventilation rates per 120.1(c)2.
Nonresidential and Hotel/ Motel Multifamily Common Use Ventilation Systems
04 05 06 07
System Name FC-1/CU-1 System Design OA CFM
Airflow1 0 System Design
Transfer Air CFM 0
Air Filtration per 120.1(c) 141.0(b)2 and
160.2(c)212
Provided
08 09 10 11 12 13 14 15 16
Space Name
or Item Tag
Mechanical Ventilation Required per 120.1(c)33 & 160.2(c)3 Exh. Vent per 120.1(c)4 &
160.2(c)4 DCV or Sensor Controls per 120.1(d)3,
120.1(d)5, and 120.1(e)36 160.2(c)5D
160.2(c)5E 160.2(c)5DOccupancy Type4
Conditioned
Floor Area
(ft2)
# of Shower
heads/
toilets
# of
people5
Required
Min OA
CFM
Required
Min CFM
Provided per Design
CFM
Zone 2-23 Janitor closet 192 0 192 0
DCV NA: Not required per
§120.1(d)3
Occ Sensor NA: Not required
space type
17 Total System Required Min OA CFM 0 18 Ventilation for this System Complies?Yes
04 05 06 07
System Name FC-2/CU-2 System Design OA CFM
Airflow1 0 System Design
Transfer Air CFM 0
Air Filtration per 120.1(c) 141.0(b)2 and
160.2(c)212
Provided
08 09 10 11 12 13 14 15 16
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 8 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
J. VENTILATION AND INDOOR AIR QUALITY
Space Name
or Item Tag
Mechanical Ventilation Required per 120.1(c)33 & 160.2(c)3 Exh. Vent per 120.1(c)4 &
160.2(c)4 DCV or Sensor Controls per 120.1(d)3,
120.1(d)5, and 120.1(e)36 160.2(c)5D
160.2(c)5E 160.2(c)5DOccupancy Type4
Conditioned
Floor Area
(ft2)
# of Shower
heads/
toilets
# of
people5
Required
Min OA
CFM
Required
Min CFM
Provided per Design
CFM
Zone 2-23 Janitor closet 192 0 192 0
DCV NA: Not required per
§120.1(d)3
Occ Sensor NA: Not required
space type
17 Total System Required Min OA CFM 0 18 Ventilation for this System Complies?Yes
1 FOOTNOTES: System CFM should include both mechanical and natural ventilation for the zone/system
2 Air filtration requirements apply to the following three system types per 120.1(c)1A: space conditioning systems utilizing ducts to supply air to occupiable space; supply-only ventilation
systems providing outside air to occupiable space; supply side of balanced ventilation systems including heat recovery and energy recovery ventilation systems providing outside air to
occupiable space.
3 Uniform Mechanical Code may have more stringent ventilation requirements; the most stringent code requirement takes precedence.
4 See Standards Tables 120.1-A and 120.1-B.
5 For lecture halls with fixed seating, the expected number of occupants shall be determined in accordance with the California Building Code.
6 120.2(e)3 requires systems serving rooms that are required by 130.1(c) to have lighting occupancy sensing controls to also have occupancy sensing zone controls for ventilation.
Examples of spaces which require lighting occupancy sensors include offices 250ft2 or smaller, multipurpose rooms less than 1,000 ft2, classrooms, conference rooms, restrooms, aisles
and open areas in warehouses, library book stack aisles, corridors, stairwells, parking garages, and loading and unloading zones, unless excepted by 130.1(c).
K. TERMINAL BOX CONTROLS
This section does not apply to this project.
L. DISTRIBUTION (DUCTWORK and PIPING)
This section does not apply to this project.
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 9 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
M. COOLING TOWERS
This section does not apply to this project.
N. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION
Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
These documents must be provided to the building inspector during construction and can be found online at
https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCI/
Form/Title
NRCI-MCH-01-E - Must be submitted for all buildings
O. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE
Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
These documents must be provided to the building inspector during construction and can be found online at
https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCA/
Form/Title Systems/Spaces To Be Field
Verified
NRCA-MCH-02-A - Outdoor Air must be submitted for all newly installed HVAC units. Note: MCH-02-A can be performed in conjunction with MCH-07-A
Supply Fan VFD Acceptance (if applicable) since testing activities overlap.
FC-1/CU-1; FC-1/CU-1;
NRCA-MCH-03-A - Constant Volume Single Zone HVAC NOTE: This form does not automatically move to "Yes'. If Constant Volume Single Zone HVAC
Systems are included in the scope, permit applicant should move this form to "Yes".
FC-1/CU-1; FC-1/CU-1;
NRCA-MCH-11-A Automatic Demand Shed Controls FC-1/CU-1; FC-1/CU-1;
NRCA-MCH-16-A Supply Air Temperature Reset Controls FC-1/CU-1; FC-1/CU-1;
NRCA-MCH-18-A Energy Management Control Systems FC-1/CU-1; FC-1/CU-1;
P. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION
There are no NRCV forms required for this project.
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 10 of 11)
Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
Q. MANDATORY MEASURES DOCUMENTATION LOCATION
This table is used to indicate where mandatory measures are documented in the plan set or construction documentation.
01 02
Compliance with Mandatory Measures documented through MCH
Mandatory Measures Note Block Yes Plan sheet or construction document location
M-Sheets
STATE OF CALIFORNIA
Mechanical Systems CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Collectors Universe Report Page: (Page 11 of 11)
Project Address: 1610 E St Andrew Pl, Suite 240 Date Prepared: 12/12/2025
Generated Date/Time:Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-9765-1225-2541
Report Generated: 2025-12-12 13:47:18
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:Documentation Author Signature:
Company:
CGK Consulting Group, Inc.
Signature Date:
Address:CEA/ HERS Certification Identification (if applicable):
City/State/Zip:Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1.The information provided on this Certificate of Compliance is true and correct.
2.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer)
3.The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements
of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations,
plans and specifications submitted to the enforcement agency for approval with this building permit application.
5.I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable
inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name:
Michael Carlomagno
Responsible Designer Signature:
Company:
Enginova
Date Signed:
2025-12-12
Address:
13125 Danielson St
License:
M35807
City/State/Zip:
Poway CA 92064
Phone:
858-228-4150