1387 Calle Avanzado. San Clemente, CA 92673 949-391-6824
April 21st, 2026
City of Santa Ana
Planning and Building Agency
RE: Project Address 2500 3/4 S FAIRVIEW ST., SANTA ANA, CA 92704
(ATT project ID’s: 12844670 - CLL01580 - WSLOS0068803)
All supplementary documents were prepared based on the available provided data by the
client. The supplementary documents:
- Mount Analysis Report by TEP, August 8, 2025.
- Structural Analysis Report by TEP, November 18, 2025.
Were found to be in general conformance to the design for the project.
If you have any questions regarding the information contained in this letter, or if we can be
of further assistance, please contact us at (949-246-1809, jon@msquaredwireless.com).
Respectfully,
M Squared Wireless
Loyall A. Wharton
Civil Engineer
License C50547
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
YES NO
INSTRUCTIONS:
ORAN GE COUNTY FI RE AUTHORI TY
Plan Submittal Criteria
COMMERCIAL projects, MULTIFAMILY RESIDENTIAL projects
and RESIDENTIAL TRACT developments
· Fill in the project/business address and provide a brief description of the scope of work and type of business operation that will take place.
· Answer questions 1 through 10, read and initial items 11 and 12, then complete and sign the certification section.
· If you answer: - “YES” to any part of questions 1 through 10, submit the type of plan indicated in italics to OCFA.
· In some cases, other plan types not indicated herein may also be necessary depending on specific conditions or operations.
· Visit www.ocfa.org for submittal information and locations. If you need assistance in filling out this form or have questions regarding
requirements for review, please contact OCFA at 714-573-6108 or visit us at 1 Fire Authority Road, Irvine, CA 92602.
Address Suite City
Project Scope/Business Description
1. Construction of a new building, a new story, or increase the footprint of an existing building? Changes to roadways,
curbs, or drive aisles? Addition, relocation, or modification of fire hydrants or fences/gates? Construction within
300 feet of an active or proposed oil well? Fire Master Plan (PR145)
2. Property is adjacent to a wildland area or non-irrigated native vegetation?
Fire Master Plan (PR145); a Fuel Modification Plan may also be required. (PR120, PR124)
3. Located in or < 100’ from a Division of Oil, Gas, and Geothermal Resources (DOGGR) field boundary, < 300’ from
an oil/gas seep, or < 1000’ from a landfill? Methane Work Plan. (PR170)
4. Installation/modification/repair of underground piping, backflow preventers, or fire department connections serving
private fire hydrant/sprinkler/standpipe systems? Underground Plan. (PR470, PR475)
5. Drinking/dining/recreation/meetings/training/religious functions or other gatherings in a room > 750 sq.ft. (> 1,000
sq.ft. for training/adulteducation) or > 49 people? Healthcare/outpatient services for > 5 people who may be unable
to immediately evacuate without assistance? Education for children (academic tutoring for ages 5+ is exempt unless
classified as an E occupancy by the Building Official)? Adult/child daycare? 24-hour care/supervision? Incarceration
or restraint? Hotel/apartment or residential facility with 3+ units and 3+ stories (3-story townhouses/rowhouses
where an independent direct exit to grade is provided for dwelling are exempt)? Congregate housing/dormitories
with 17+ people? High-rise structure (55+ feet to highest occupied floor level)? Architectural Plan (PR200-PR285)
6. Installation/modification of locks delaying or preventing occupants from leaving a space or requiring use of a card,
button, or similar action to open a door in the direction of exit travel? Architectural, Sprinkler, and/or Alarm Plan
depending on the occupancy and type of device installed (PR200-PR280, PR420-PR425, PR500-PR520)
7. Installation/modification/use of spray booths; dust collection; dry cleaning; industrial ovens/drying equipment;
industrial/commercial refrigeration systems; compressed gasses; tanks for cryogenic or flammable/combustible
liquids; vapor recovery; smoke control; battery back-up/charging systems (> 50 gal. electrolyte, > 1,000 lb. lithium
ion); welding/brazing/soldering, open flame torches, cutting/grinding; or other similar operations?
Special Equipment Plan (PR315, PR340-PR382)
8. Storage/use/research with flammable/combustible liquids or other chemicals? Motor vehicle/aircraft
maintenance/repair? Cabinetry/woodworking/finishing facility? Chem Class & floor plan (full architectural plan if
H occupancy); Special Equipment Plans may be necessary. (PR315-PR360, PR232-PR240)
9. Storage or merchandizing areas in excess of 500 sq. ft. where items are located higher than 12’ (6’ for high-hazard
commodities, plastic, rubber, foam, etc.)? High-piled Storage Plan (PR330)
10. Cooking under a Type I commercial hood; installation or modification of a fire extinguishing system located in a
commercial cooking hood? Hood & Duct Extinguishing System, not just the hood mechanical plan. (PR335)
Initial each of the following two items indicating that you have read and understand the statement:
11. *Sprinklers/Alarms: Consult Building/Fire Codes and ordinances to determine sprinkler/alarm requirements; if a system is
required, plans shall be submitted for OCFA review. Existing buildings undergoing remodel must be evaluated by a licensed
Initials contractor to determine if modification is needed; if so, contractor shall submit plans prior to making modifications.
12. Fire Hazard Severity Zone: Consult maps available at building department or on OCFA website to determine if your site is located
in a FHSZ. Buildings in a FHSZ may be subject to special construction requirements detailed in CBC Chapter 7A or CRC R327—
Initials the building department will determine specific requirements.
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name Signature
Phone Number ( ) Date / /
Building Department: If you have verified that all of the questions have been answered accurately as “NO”, and the project does not otherwise require OCFA
review of sprinkler or alarm plans*, then you may accept this signed form as a written release that OCFA review is not required. Should you still require that the
applicant have plans approved by OCFA, please initial here or attach an OCFA referral form and have the applicant submit the form along with the
appropriate plans and fees for OCFA review. 10-08-14 EE
COM
O R A N G E C O U N T Y F I R E A U T H O R I T Y
Plan Referral Form
Required for OCFA to review plans upon the request of the Building Department when
the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”.
City / County Official Requesting Review:
City / County Reference #: Date: __________________________________
City / County: _____________________________________ E-Mail: __________________________________
Contact Name: _____________________________________ Phone #: _________________________________
Title: _____________________________________
** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. **
Reason(s) for Review:
Please describe why OCFA Plan Review is or may be required by the City/County :
OCFA COMMENTS:
No further action required on this specific plan type, based
on information provided on: ____/______/______.
Project to be taken in for OCFA Review.
Other:
Name: _________________________________________
Contact #: ______________________________________ Date: _________________________________
OCFA Authorization
Updated: 06/02/2020 rs
SHEET
NO.DESCRIPTION
G-2 GROUNDING DETAILS
SHEET
NO.DESCRIPTION
T-1 TITLE SHEET
GN-1 GENERAL NOTES
A-1.1 SITE PLAN
A-1.2 ENLARGED SITE PLAN
A-2 EQUIPMENT LAYOUTS
A-3.1 EXISTING ANTENNA PLAN
A-3.2 NEW ANTENNA PLANS
A-4 ELEVATIONS
A-5 ELEVATIONS
D-1 DETAILS
G-1 GROUNDING PLAN
APPROVED APPROVED
AS NOTED
REVISE &
RESUBMIT
OWNER REPRESENTATIVE DATE
SITE ACQUISITION DATE
CONSTRUCTION MANAGER DATE
ZONING DATE
RF ENGINEER DATE
APPROVAL BLOCK
TITLE SHEET
mobility corp.
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
T-1
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
SI
CALL CALIFORNIA ONE CALL
(800) 422-4133
CALL 3 WORKING DAYS
BEFORE YOU DIG!
SITE INFORMATION
SITE ADDRESS:2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
LATITUDE (NAD 83):33.7134472
33° 42' 48.40992" N
LONGITUDE (NAD 83):-117.9098583
117° 54' 35.48988" W
GROUND ELEVATION:±43' AMSL
JURISDICTION:CITY OF SANTA ANA
PROPERTY OWNER:DONALD P. JOHNSON
160 EMERALD BAY
LAGUNA BEACH, CA 92780
TOWER OWNER:AT&T TOWERS
PARCEL/MAP NUMBER:414-101-05
STRUCTURE TYPE:MONOEUCALYPTUS
STRUCTURE HEIGHT:60'-0" A.G.L.
ZONING CLASSIFICATION:C4 - COMMERCIAL
OCCUPANCY:U
CONSTRUCTION TYPE:V-B
POWER SUPPLIER:SCE
PROJECT TEAM
VICINITY MAP
DIRECTIONS
CODE COMPLIANCE
ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN ACCORDANCE WITH THE CURRENT EDITIONS OF THE FOLLOWING
CODES AS ADOPTED BY THE LOCAL GOVERNING AUTHORITIES. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK NOT
CONFORMING TO THE LATEST EDITIONS OF THE FOLLOWING CODES.
·2025 CALIFORNIA BUILDING CODE (CBC)
·2025 CALIFORNIA TITLE 24, PART 10
·2025 CALIFORNIA FIRE CODE (CFC)
·2025 CALIFORNIA ENERGY CODE
·2025 CALIFORNIA ELECTRICAL CODE
·2025 CALIFORNIA MECHANICAL CODE (CMC)
·ANSI EIA/TIA-222-I
·CITY/COUNTY ORDINANCES
DIRECTIONS FROM AT&T OFFICE (1452 EDINGER AVE., TUSTIN, CA 92780):
1.HEAD SOUTHEAST ON INDUSTRIAL DR.
2.TURN RIGHT ONTO RED HILL AVE.
3.TURN RIGHT ONTO WARNER AVE.
4.CONTINUE ON E WARNER AVE.
5.TURN LEFT ONTO S FAIRVIEW ST.
6.TURN RIGHT.
7.DESTINATION WILL BE ON THE RIGHT.
DRAWING INDEX
SCOPE OF WORK
NE
N
E
SESW
W
NW
S
DRAWING SCALE
THESE DRAWINGS ARE SCALED TO FULL SIZE AT 22"x34" AND HALF SIZE AT 11"x17". CONTRACTOR
SHALL VERIFY ALL PLANS AND EXISTING DIMENSIONS AND CONFITIONS ON THE JOB SITE AND SHALL
IMMEDIATELY NOTIFY THE DESIGNER / ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK OR MATERIAL ORDERS OR BE RESPONSIBLE FOR THE SAME.
CONTRACTOR SHALL USE BEST MANAGEMENT PRACTICE TO PREVENT STORM WATER POLLUTION
DURING CONSTRUCTION.
THIS PROJECT CONSISTS OF THE MODIFICATIONS OF AN EXISTING AT&T MOBILITY UNMANNED
TELECOMMUNICATIONS FACILITY. THE SCOPE WILL CONSIST OF THE FOLLOWING:
ANTENNA AREA:
·RELOCATE (3) AIR6449 B77D (BOTTOM)
·INSTALL (3) AIR6419 B77G (TOP) WITH (3) NEW 2 7/8" OD MAST PIPES
·REMOVE ALL MDT BRACKETS
·ROTATE COLLAR - SET ARMS TO 100, 220, 340 TO ELIMINATE SKEW
·RELOCATE ALL ANTENNAS TO ACHIEVE PROPOSED EDGE TO EDGE SEPARATIONS
EQUIPMENT AREA:
·REUSE (1) EXISTING NETSURE 512 OUTDOOR PDU
·INSTALL (1) NETSURE 512 OD RETROFIT KIT W/-58V
·INSTALL (5) C48/58-2000 P3 CONVERTERS
·INSTALL (2) R48-2000 E3 RECTIFIERS
·INSTALL (3) 50A DC BREAKERS
EXISTING ANTENNAS:12 EXISTING RRUS:15
REMOVED ANTENNAS:0 REMOVED RRUS:0
PROPOSED ANTENNAS:3 PROPOSED RRUS:0
TOTAL ANTENNAS:15 TOTAL RRUS:15
CLL01580 - FAIRVIEW BUSINESS PARK
FA NUMBER:
IWM ID:
IWM SITE ID:
USID:
PACE NUMBER:
12844670
WSLOS0068803
SICA009891
195375
MRLOS115828
2500 & 2500 3/4 S FAIIRVIEW ST., SANTA ANA, CA 92704
APPLICANT:AT&T MOBILITY
1452 EDINGER AVE.
TUSTIN, CA 92780
A/E:M SQUARED WIRELESS
1387 CALLE AVANZADO
SAN CLEMENTE, CA 92673
CONTACT: JON MAXWELL
PHONE: (949) 391-6824
PROJECT MANAGEMENT FIRM:ERICSSON
KARIANNE KERR
PHONE: (360) 513-1204
EMAIL: karianne.kerr@ericsson.com
RF ENGINEER:AT&T MOBILITY
CONTACT: ATHAR ALI
PHONE: (469) 534-2496
EMAIL: aa250e@att.com
SITE ACQ MANAGER:M SQUARED WIRELESS
FELICIA PHILLIPS
PHONE: (714) 791-6643
EMAIL: felicia@msquaredwireless.com
NOTE:
NO NEW AC POWER WORK PROPOSED UNDER THIS PROJECT.
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
GN-1
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
GENERAL CONSTRUCTION NOTES:
1.FOR THE PURPOSE OF CONSTRUCTION DRAWINGS, THE FOLLOWING DEFINITIONS SHALL
APPLY:
GENERAL CONTRACTOR - GENERAL CONTRACTOR
SUBCONTRACTOR - CONTRACTOR (CONSTRUCTION)
OWNER - AT&T
2.ALL SITE WORK SHALL BE COMPLETED AS INDICATED ON THE DRAWINGS AND AT&T PROJECT
SPECIFICATIONS.
3.GENERAL CONTRACTOR AND SUBCONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE
HIMSELF WITH ALL CONDITIONS AFFECTING THE NEW WORK AND SHALL MAKE PROVISIONS.
GENERAL CONTRACTOR AND SUBCONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING
HIMSELF WITH ALL CONTRACT DOCUMENTS, FIELD CONDITIONS, DIMENSIONS, AND
CONFIRMING THAT THE WORK MAY BE ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING
WITH CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER PRIOR TO THE COMMENCEMENT OF WORK.
4.ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL
APPLICABLE CODES, REGULATIONS, AND ORDINANCES. GENERAL CONTRACTOR SHALL ISSUE
ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAT&T, ORDINANCES, RULES,
REGULATIONS, AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE
PERFORMANCE OF WORK.
5.ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY
COMPANY SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES, AND
APPLICABLE REGULATIONS.
6.UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT,
APPURTENANCES, AND LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED
ON THE DRAWINGS.
7.PLANS ARE NOT TO BE SCALED. THESE PLANS ARE INTENDED TO BE A DIAGRAMMATIC
OUTLINE ONLY UNLESS OTHERWISE NOTED. DIMENSIONS SHOWN ARE TO FINISH SURFACES
UNLESS OTHERWISE NOTED. SPACING BETWEEN EQUIPMENT IS THE MINIMUM REQUIRED
CLEARANCE. THEREFORE, IT IS CRITICAL TO FIELD VERIFY DIMENSIONS, SHOULD THERE BE
ANY QUESTIONS REGARDING THE CONTRACT DOCUMENTS, THE SUBCONTRACTOR SHALL BE
RESPONSIBLE FOR OBTAINING A CLARIFICATION FROM THE ARCHITECT/ENGINEER PRIOR TO
PROCEEDING WITH THE WORK. DETAILS ARE INTENDED TO SHOWN DESIGN INTENT.
MODIFICATIONS MAY BE REQUIRED TO SUIT JOB DIMENSIONS OR CONDITIONS AND SUCH
MODIFICATIONS SHALL BE INCLUDED AS PART OF WORK AND PREPARED BY THE
ARCHITECT/ENGINEER PRIOR TO PROCEEDING WITH WORK.
8.THE SUBCONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE.
9.IF THE SPECIFIED EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THESE DRAWINGS. THE
SUBCONTRACTOR SHALL PROPOSE AN ALTERNATIVE SPACE FOR APPROVAL BY THE
ARCHITECT/ENGINEER PRIOR TO PROCEEDING.
10.GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF WORK AREA, ADJACENT
AREAS AND BUILDING OCCUPANTS THAT ARE LIKELY TO BE AFFECTED BY THE WORK UNDER
THIS CONTRACT. WORK SHALL CONFORM TO ALL OSHA REQUIREMENTS AND THE LOCAL
JURISDICTION.
11.GENERAL CONTRACTOR SHALL COORDINATE WORK AND SCHEDULE WORK ACTIVITIES WITH
OTHER DISCIPLINES.
12.ERECTION SHALL BE DONE IN A WORKMANLIKE MANNER BY COMPETENT EXPERIENCED
WORKMAN IN ACCORDANCE WITH APPLICABLE CODES AND THE BEST ACCEPTED PRACTICE.
ALL MEMBERS SHALL BE LAID PLUMB AND TRUE AS INDICATED ON THE DRAWINGS.
13.SEAL PENETRATIONS THROUGH FIRE RATED AREAS WITH UL LISTED MATERIALS APPROVED BY
LOCAL JURISDICTION. SUBCONTRACTOR SHALL KEEP AREA CLEAN, HAZARD FREE, AND
DISPOSE OF ALL DEBRIS.
14.WORK PREVIOUSLY COMPLETED IS REPRESENTED BY LIGHT SHADED LINES AND NOTES. THE
SCOPE OF WORK FOR THIS PROJECT IS REPRESENTED BY DARK SHADED LINES AND NOTES.
SUBCONTRACTOR SHALL NOTIFY THE GENERAL CONTRACTOR OF ANY EXISTING CONDITIONS
THAT DEVIATE FROM THE DRAWINGS PRIOR TO THE BEGINNING CONSTRUCTION.
15.SUBCONTRACTOR SHALL PROVIDE WRITTEN NOTICE TO THE CONSTRUCTION MANAGER 48
HOURS PRIOR TO COMMENCEMENT OF WORK.
16.THE SUBCONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS,
LANDSCAPING AND STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT
SUBCONTRACTOR'S EXPENSE TO THE SATISFACTION OF THE OWNER.
17.THE SUBCONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF
CONSTRUCTION.
18.GENERAL CONTRACTOR SHALL COORDINATE AND MAINTAIN ACCESS FOR ALL TRADES AND
SUBCONTRACTORS TO THE SITE AND/OR BUILDING.
19.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SECURITY OF THE SITE FOR THE
DURATION OF CONSTRUCTION UNTIL JOB COMPLETION.
20.THE GENERAL CONTRACTOR SHALL MAINTAIN IN GOOD CONDITION ONE COMPLETE SET OF
PLANS WITH ALL REVISIONS, ADDENDA, AND CHANGE ORDERS ON THE PREMISES AT ALL
TIMES.
21.THE GENERAL CONTRACTOR AND SUBCONTRACTOR SHALL PROVIDE PORTABLE FIRE
EXTINGUISHERS WITH A RATING OF NOT LESS THAN 2-A OT 2-A:10-B:C AND SHALL BE WITHIN 25
FEET OF TRAVEL DISTANCE TO ALL PORTIONS OF WHERE THE WORK IS BEING COMPLETED
DURING CONSTRUCTION.
22.ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES SHALL BE
PROTECTED AT ALL TIMES, AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE
WORK, SHALL BE RELOCATED AS DIRECTED BY THE ARCHITECT/ENGINEER. EXTREME CAUTION
SHOULD BE USED BY THE SUBCONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND
OR NEAR UTILITIES. SUBCONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR THE WORKING
CREW. THIS SHALL INCLUDE BUT NOT BE LIMITED TO A) FALL PROTECTION, B) CONFINED
SPACE, C) ELECTRICAL SAFETY, D) TRENCHING & EXCAVATION.
23.ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES, WHICH
INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED, CAPPED, PLUGGED OR
OTHERWISE DISCONNECTED AT POINTS WHICH WILL NOT INTERFERE WITH THE EXECUTION OF
THE WORK, AS DIRECTED BY THE RESPONSIBLE ARCHITECT/ENGINEER, AND SUBJECT TO THE
APPROVAL OF THE OWNER AND/OR LOCAL UTILITIES.
24.THE AREAS OF THE OWNER'S PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY
THE TOWER, EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND
STABILIZED TO PREVENT EROSION.
25.SUBCONTRACTOR SHALL MINIMIZE DISTURBANCE TO THE EXISTING SITE DURING
CONSTRUCTION. EROSION CONTROL MEASURES, IF REQUIRED DURING CONSTRUCTION,
SHALL BE IN CONFORMANCE WITH THE FEDERAL AND LOCAL JURISDICTION FOR EROSION AND
SEDIMENT CONTROL.
26.NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUNDING. FROZEN
MATERIALS, SNOW OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.
27.THE SUBGRADE SHALL BE BROUGHT TO A SMOOTH UNIFORM GRADE AND COMPACTED TO 95
PERCENT STANDARD PROCTOR DENSITY UNDER PAVEMENT AND STRUCTURES AND 80
PERCENT STANDARD PROCTOR DENSITY IN OPEN SPACE. ALL TRENCHES IN PUBLIC RIGHT OF
WAY SHALL BE BACKFILLED WITH FLOWABLE FILL OR OTHER MATERIAL PRE-APPROVED BY
THE LOCAL JURISDICTION.
28.ALL NECESSARY RUBBISH, STUMPS, DEBRIS, STICKS, STONES, AND OTHER REFUSE SHALL BE
REMOVED FROM THE SITE AND DISPOSED OF IN A LAWFUL MANNER.
29.ALL BROCHURES, OPERATING AND MAINTENANCE MANUALS, CATALOGS, SHOP DRAWINGS,
AND OTHER DOCUMENTS SHALL BE TURNED OVER TO THE GENERAL CONTRACTOR AT
COMPLETION OF CONSTRUCTION AND PRIOR TO PAYMENT.
30.SUBCONTRACTOR SHALL SUBMIT A COMPLETE SET OF AS-BUILT REDLINES TO THE GENERAL
CONTRACTOR UPON COMPLETION OF PROJECT AND PRIOR TO FINAL PAYMENT.
31.SUBCONTRACTOR SHALL LEAVE PREMISES IN A CLEAN CONDITION.
32.THE NEW FACILITY WILL BE UNMANNED AND DOES NOT REQUIRE POTABLE WATER OR SEWER
SERVICE, AND IS NOT FOR HUMAN HABITAT (NO HANDICAP ACCESS REQUIRED).
33.OCCUPANCY IS LIMITED TO PERIODIC MAINTENANCE AND INSPECTION, APPROXIMATELY 2
TIMES PER MONTH, BY AT&T TECHNICIANS.
34.NO OUTDOOR STORAGE OR SOLID WASTE CONTAINERS ARE PROPOSED .
35.ALL MATERIAL SHALL BE FURNISHED AND WORK SHALL BE PERFORMED IN ACCORDANCE WITH
THE LATEST REVISION AT&T MOBILITY GROUNDING STANDARD "TECHNICAL SPECIFICATION
FOR CONSTRUCTION OF GSM/GPRS WIRELESS SITES" AND "TECHNICAL SPECIFICATION FOR
FACILITY GROUNDING". IN CASE OF A CONFLICT BETWEEN THE CONSTRUCTION SPECIFICATION
AND THE DRAWINGS, THE DRAWINGS SHALL GOVERN.
36.SUBCONTRACTORS SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS AND INSPECTIONS
REQUIRED FOR CONSTRUCTION. IF SUBCONTRACTOR CANNOT OBTAIN A PERMIT, THEY MUST
NOTIFY THE GENERAL CONTRACTOR IMMEDIATELY.
37.SUBCONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE SITE ON A DAILY BASIS.
38.INFORMATION SHOWN ON THESE DRAWINGS WAS OBTAINED FROM SITE VISITS AND/OR
DRAWINGS PROVIDED BY THE SITE OWNER. CONTRACTORS SHALL NOTIFY THE ENGINEER OF
ANY DISCREPANCIES PRIOR TO ORDERING MATERIAL OR PROCEEDING WITH CONSTRUCTION.
39.NO WHITE STROBIC LIGHTS ARE PERMITTED. LIGHTING IF REQUIRED, WILL MEET FAA
STANDARDS AND REQUIREMENTS.
40.ALL COAXIAL CABLE INSTALLATIONS TO FOLLOW MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS.
41.NO NOISE, SMOKE, DUST, OR VIBRATIONS WILL RESULT FROM THIS FACILITY.
(DELETE THIS NOTE IF THE SITE WILL HAVE A GENERATOR).
42.NO ADDITIONAL PARKING TO BE PROPOSED . EXISTING ACCESS AND PARKING TO REMAIN.
(REVISE THIS NOTE ACCORDING TO THE SITE CONFIGURATION).
43.NO LANDSCAPING IS NEW AT THIS SITE, UNLESS NOTED OTHERWISE.
(REVISE THIS NOTE ACCORDING TO THE SITE CONFIGURATION).
44.CONTRACTOR SHALL ASSESS & REPAIR ANY DAMAGED AND/ OR MISSING CABLE TRAY
COVERS, SLEEPERS, AND/ OR COVER CLAMPS.
45.CONTRACTOR SHALL ASSESS AND REPLACE ANY MISSING OR DAMAGED COLOR CODED,
CONTINUOUS, PHOTO-LUMINESCENT/REFLECTIVE MARKING ON ALL EXISTING CABLE TRAY.
46.CONTRACTOR SHALL ASSESS AND REPLACE ANY MISSING OR DAMAGED ANTENNA
"TRANSMITTER" LABELS & ENSURE MARKING ARE AFFIXED TO ANY EXISTING & NEW ANTENNA.
ANTENNA MOUNT OR CONSPICUOUS LOCATION NEAR THE ANTENNA.
47.THE PROPOSED MODIFICATIONS WILL NOT RESULT IN AN INCREASE IN THE HEIGHT OF THE
EXISTING STRUCTURE.
48.THE PROPOSED MODIFICATIONS WILL NOT REQUIRE THE EXTENSION OF THE SITE BOUNDARY.
49.THE PROPOSED MODIFICATIONS WILL NOT INCREASE NOISE LEVELS AT THE FACILITY BY SIX
DECIBELS OR MORE OR TWO LEVELS THAT EXCEED STATE AND LOCAL CRITERIA.
50.THE OPERATION OF THE REPLACEMENT ANTENNAS WILL NOT INCREASE RADIO FREQUENCY
EMISSIONS AT THE FACILITY TO A LEVEL AT OR ABOVE THE FEDERAL COMMUNICATIONS
COMMISSION SAFETY STANDARD.
51.THE PROPOSED MODIFICATION WILL NOT CAUSE A CHANGE OR ALTERATION IN THE PHYSICAL
OR ENVIRONMENTAL CHARACTERISTICS OF THE SITE.
GENERAL NOTES
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
A-1.1
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
SITE PLAN 1
A-1.1
1,2
A-4
NE
N
E
SESW
W
NW
S
SITE PLANNOTE:
THESE DRAWINGS HAVE BEEN CREATED UTILIZING
AS-BUILTS PROVIDED BY AT&T AND WITHOUT A
SURVEY OR SITE MEASUREMENTS. PLEASE VERIFY
ALL DIMENSIONS, LENGTHS, PROPERTY LINES,
CONDUIT RUNS, ETC. PRIOR TO CONSTRUCTION.
"B"
S
E
C
T
O
R
@
220
°
"A" SECTO
R
@
100°
"C
"
S
E
C
T
O
R
@
34
0
°
1,2
A-5
SEE ENLARGED SITE PLAN
1
A-1.2
APN: 414-101-05
S
F
A
I
R
V
I
E
W
S
T
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
PARKING
AREA
EXISTING
PARKING
AREA
EXISTING
PARKING
AREA
FL
O
O
D
C
O
N
T
R
O
L
C
A
N
A
L
1
A-1.2
1,2
A-4
NE
N
E
SESW
W
NW
S
ENLARGED SITE PLANNOTE:
THESE DRAWINGS HAVE BEEN CREATED UTILIZING
AS-BUILTS PROVIDED BY AT&T AND WITHOUT A
SURVEY OR SITE MEASUREMENTS. PLEASE VERIFY
ALL DIMENSIONS, LENGTHS, PROPERTY LINES,
CONDUIT RUNS, ETC. PRIOR TO CONSTRUCTION.
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
A-1.2
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
ENLARGED SITE PLAN
"B"
S
E
C
T
O
R
@
220
°
"A" SECTO
R
@
100°
"C
"
S
E
C
T
O
R
@
34
0
°
1,2
A-5
LOCATION OF EXISTING AND
NEW AT&T ANTENNA AREA
1
A-3.1
1
A-3.2
LOCATION OF EXISTING AND
NEW AT&T GROUND
EQUIPMENT AREA
1,2
A-2
APN: 414-101-05
PR
O
P
E
R
T
Y
L
I
N
E
PROPERTY LINE
EXISTING
BUILDING
EXISTING
PARKING
AREA
EXISTING
BUILDING
EXISTING
BUILDING
(E) TRANSFORMER
(E) ELECTRICAL VAULT
(E) WALL
(E) FENCE, TYP.
(E) TREE, TYP.
FL
O
O
D
C
O
N
T
R
O
L
C
A
N
A
L
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
A-2
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
EXISTING EQUIPMENT LAYOUT 2
A-2
1
NE
N
ESE
SW W NW
S
EQUIPMENT LAYOUTS
NEW EQUIPMENT LAYOUT
NE
N
ESE
SW W NW
S
(E) AT&T POWER PLANT
WITH EXISTING EQUIPMENT:
(1) POWER CONTROLLER TO REMAIN
(11) RECTIFIERS TO REMAIN
(12) PYL12V185FT BATTERIES TO REMAIN
(E) AT&T FIBER WINDER BOX
(E) AT&T CIENA
(E) ELECTRIC METER
(E) AT&T DC12 SURGE
PROTECTORS TO REMAIN,
(3 TOTAL)
(E) ACCESS DOOR
(E) AT&T GENERATOR INTERFACE
(E) AT&T TELCO CABINET
(E) AT&T AC PANEL
(E) AT&T GPS ANTENNA
(E) AT&T PURCELL CABINET WITH EQUIPMENT:
(1) EXISTING FLEXIHAUL
(1) EXISTING FUSE PANEL
(2) EXISTING EQUIPMENT
TO REMAIN
(E) AT&T H-FRAME
(E) AT&T PURCELL CABINET WITH
EXISTING EQUIPMENT LISTED ABOVE
EQUIPMENT LIST INSIDE EXISTING PURCELL
CABINET:
(1) EXISTING SPOOL BOX
(1) EXISTING SAU-02 01
(2) EXISTING GPS
(3) EXISTING GROUNDING OVP
(1) EXISTING ROUTER
(3) EXISTING 6630 BBU
(2) EXISTING 6601 BBU
(1) EXISTING R503 BBU
(1) EXISTING DUW 3001
(1) EXISTING HEAT SINK
(E) AT&T BATTERY CABINET WITH:
(16) PYL12V185FT BATTERIES TO REMAIN
±8'-8"
EXISTING AT&T EQUIPMENT AREA
±1
1
'
-
6
"
EX
I
S
T
I
N
G
A
T
&
T
E
Q
U
I
P
M
E
N
T
A
R
E
A
(E) AT&T POWER PLANT
WITH EXISTING EQUIPMENT:
(1) POWER CONTROLLER
(11) RECTIFIERS
(12) PYL12V185FT BATTERIES
INSTALL NEW EQUIPMENT:
(1) RETROFIT KIT W/ -58V TO CONVERT
POWER TO -58V
(5) C48/58 DC UP CONVERTERS
(2) R48 2000 E3 RECTIFIERS
(3) 50A DC BREAKERS
(E) AT&T FIBER WINDER BOX
(E) AT&T CIENA
(E) ELECTRIC METER
(E) AT&T DC12 SURGE
PROTECTORS,
(3 TOTAL)
(E) ACCESS DOOR
(E) AT&T GENERATOR INTERFACE
(E) AT&T TELCO CABINET
(E) AT&T AC PANEL
(E) AT&T GPS ANTENNA
(E) AT&T PURCELL CABINET WITH EQUIPMENT:
(1) EXISTING FLEXIHAUL
(1) EXISTING FUSE PANEL
(2) EXISTING EQUIPMENT
(E) AT&T H-FRAME
(E) AT&T PURCELL CABINET WITH
EXISTING EQUIPMENT LISTED ABOVE
(E) AT&T BATTERY CABINET WITH:
(16) PYL12V185FT BATTERIES
±8'-8"
EXISTING AT&T EQUIPMENT AREA
±1
1
'
-
6
"
EX
I
S
T
I
N
G
A
T
&
T
E
Q
U
I
P
M
E
N
T
A
R
E
A
3,4
D-1
(E) W.I. TOPPER(E) W.I. TOPPER
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
A-3.1
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
EXISTING ANTENNA PLAN 1
A-3.1
NE
N
E
SESW
W
NW
S
EXISTING ANTENNA PLAN
ANTENNA RF SCHEDULE
(E) AT&T DC9 SURGE
PROTECTORS TO REMAIN,
(3 TOTAL)
RFDS ID 34994
RFDS REV PRE-CONSTRUCTION
RFDS DATE 01/31/2025
NOTES:
1.GENERAL CONTRACTOR TO REMOVE
EXISTING ANTENNA SKEW (IF ANY).
2.EXISTING ANTENNAS/EQUIPMENT BY
OTHERS NOT SHOWN FOR CLARITY.
3.EXISTING MONOEUCALYPTUS
BRANCHES NOT SHOWN FOR
CLARITY.
(E) MONOEUCALYPTUS, TYP.
A1
A2
A3
A4
B1
B2
B3
B4
C4
C3
C2
C1
(E) AT&T AIR6449 B77D
ANTENNA TO BE MOVED DOWN
AND RELOCATED
(1 PER SECTOR, 3 TOTAL)
2'-7
"
EXISTING RF SCHEDULE
SECTOR ANTENNA MODEL NUMBER AZIMUTH RAD
CENTER RRU MODEL NUMBER SURGE PROTECTION
MODEL NUMBER
A1 NNH4-65C-R6-V3 100°55'-0"8843 B2/B66A / 4449 B5/B12
DC9-48-60-24-8C-EV
A2 AIR6449 B77D 100°57'-9"INTEGRATED
A3 80010966 100°55'-0"4478 B14
A4 QS8658-3 100°55'-0"RRUS-E2 B29 / RRUS-32 B30
B1 NNH4-65C-R6-V3 220°55'-0"8843 B2/B66A / 4449 B5/B12
DC9-48-60-24-8C-EV
B2 AIR6449 B77D 220°57'-9"INTEGRATED
B3 80010966 220°55'-0"4478 B14
B4 QS8658-3 220°55'-0"RRUS-E2 B29 / RRUS-32 B30
C1 NNH4-65C-R6-V3 340°55'-0"8843 B2/B66A / 4449 B5/B12
DC9-48-60-24-8C-EV
C2 AIR6449 B77D 340°57'-9"INTEGRATED
C3 80010966 340°55'-0"4478 B14
C4 QS8658-3 340°55'-0"RRUS-E2 B29 / RRUS-32 B30
(E) AT&T PIPE MAST TO BE
REMOVED AND REPLACED,
(1 PER SECTOR, 3 TOTAL)
"B"
S
E
C
T
O
R
@
220
°
"A" SECTO
R
@
100°
"C
"
S
E
C
T
O
R
@
34
0
°
1'-3
"
3'-1
0
"
(E) AT&T NNH4-65C-R6-V3
ANTENNA TO BE RELOCATED
(1 PER SECTOR, 3 TOTAL)
(E) AT&T 80010966 ANTENNA
TO BE RELOCATED
(1 PER SECTOR, 3 TOTAL)
(E) AT&T QS8658-3E ANTENNA
TO BE RELOCATED
(1 PER SECTOR, 3 TOTAL)(E) AT&T RRUS-32 B30 RRU
TO BE RELOCATED
(1 PER SECTOR, 3 TOTAL)
(E) AT&T RRUS-E2 B29 RRU
TO BE RELOCATED
(1 PER SECTOR, 3 TOTAL)
(E) AT&T 4478 B14 RRU
TO BE RELOCATED
(1 PER SECTOR, 3 TOTAL)
(E) AT&T 8843 B2/B66A RRU
TO BE RELOCATED
(1 PER SECTOR, 3 TOTAL)
(E) AT&T 4449 B5/B12 RRU
TO BE RELOCATED
(1 PER SECTOR, 3 TOTAL)
2'
-
6
"
1'
-
5
"
3'
-
8
"
3'-9"
1'-5"
2'-7"
ROTATE EXISTING SECTOR
MOUNTS TO REMOVE ANTENNA
SKEWS (TYP. FOR ALL SECTORS)
NOTES:
1.ROTATE COLLAR COUNTER
CLOCKWISE ARMS ORIENTATED TO
AZ AS DESIGNED 100, 220, 340
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
A-3.2
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
NEW ANTENNA PLAN 1
A-3.2
NE
N
E
SESW
W
NW
S
NEW ANTENNA PLANS
ANTENNA RF SCHEDULE
NOTES:
1.GENERAL CONTRACTOR TO REMOVE
EXISTING ANTENNA SKEW (IF ANY).
2.EXISTING ANTENNAS/EQUIPMENT BY
OTHERS NOT SHOWN FOR CLARITY.
3.EXISTING MONOEUCALYPTUS
BRANCHES NOT SHOWN FOR
CLARITY.
RFDS ID 34994
RFDS REV PRE-CONSTRUCTION
RFDS DATE 01/31/2025
NEW AT&T ANTENNA
STACKED ABOVE
(1 PER SECTOR, 3 TOTAL)
1,2
D-1
NEW AT&T 2-7/8" O.D. x 10'-0"
LONG PIPE MAST
(1 PER SECTOR, 3 TOTAL)
1'-0"
CLR.
(E) AT&T DC9 SURGE
PROTECTORS, (3 TOTAL)
(E) MONOEUCALYPTUS, TYP.
A1
A2
A3
A4
B1
B2
B3
B4
C4
C3
C2
C1
(E) AT&T AIR6449 B77D
ANTENNA MOVED DOWN AND
RELOCATED,
(1 PER SECTOR, 3 TOTAL)
2'-0
"
TYP
.
FINAL RF SCHEDULE
SECTOR ANTENNA MODEL NUMBER AZIMUTH RAD
CENTER RRU MODEL NUMBER SURGE PROTECTION
MODEL NUMBER
A1 NNH4-65C-R6-V3 100°55'-0"8843 B2/B66A / 4449 B5/B12
DC9-48-60-24-8C-EV
A2 AIR6419 B77G
AIR6449 B77D 100°±57'-10"
±54'-0"
INTEGRATED
INTEGRATED
A3 80010966 100°55'-0"4478 B14
A4 QS8658-3 100°55'-0"RRUS-E2 B29 / RRUS-32 B30
B1 NNH4-65C-R6-V3 220°55'-0"8843 B2/B66A / 4449 B5/B12
DC9-48-60-24-8C-EV
B2 AIR6419 B77G
AIR6449 B77D 220°±57'-10"
±54'-0"
INTEGRATED
INTEGRATED
B3 80010966 220°55'-0"4478 B14
B4 QS8658-3 220°55'-0"RRUS-E2 B29 / RRUS-32 B30
C1 NNH4-65C-R6-V3 340°55'-0"8843 B2/B66A / 4449 B5/B12
DC9-48-60-24-8C-EV
C2 AIR6419 B77G
AIR6449 B77D 340°±57'-10"
±54'-0"
INTEGRATED
INTEGRATED
C3 80010966 340°55'-0"4478 B14
C4 QS8658-3 340°55'-0"RRUS-E2 B29 / RRUS-32 B30
"B"
S
E
C
T
O
R
@
220
°
"A" SECTO
R
@
100°
"C
"
S
E
C
T
O
R
@
34
0
°
2'-0
"
TYP
.
2'-0
"
TYP
.
(E) AT&T NNH4-65C-R6-V3
ANTENNA RELOCATED,
(1 PER SECTOR, 3 TOTAL)
(E) AT&T 80010966 ANTENNA
RELOCATED
(1 PER SECTOR, 3 TOTAL)
(E) AT&T QS8658-3E ANTENNA
RELOCATED
(1 PER SECTOR, 3 TOTAL)
(E) AT&T RRUS-32 B30 RRU RELOCATED,
(1 PER SECTOR, 3 TOTAL)
(E) AT&T RRUS-E2 B29 RRU RELOCATED,
(1 PER SECTOR, 3 TOTAL)
(E) AT&T 4478 B14 RRU RELOCATED,
(1 PER SECTOR, 3 TOTAL)
(E) AT&T 8843 B2/B66A RRU RELOCATED,
(1 PER SECTOR, 3 TOTAL)
(E) AT&T 4449 B5/B12 RRU RELOCATED,
(1 PER SECTOR, 3 TOTAL)
ROTATED EXISTING SECTOR
MOUNTS TO REMOVE ANTENNA
SKEWS (TYP. FOR ALL SECTORS)
NOTES:
1.ROTATE COLLAR COUNTER
CLOCKWISE ARMS ORIENTATED TO
AZ AS DESIGNED 100, 220, 340
TEP MA RECOMMENDATIONS
1)IF THE LOAD DIFFERS FROM THAT DESCRIBED IN TABLE 2 (PER DETAIL 5/D-1) ARE FOUND
TO BE INVALID, ANOTHER STRUCTURAL ANALYSIS SHOULD BE PERFORMED.
2)THE MOUNT AND ITS CONNECTION HAVE SUFFICIENT CAPACITY TO CARRY THE PROPOSED
LOADING CONFIGURATION. IN ORDER FOR THE RESULTS OF THIS ANALYSIS TO BE VALID,
THE MOUNT MODIFICATIONS LISTED BELOW MUST BE COMPLETED:
(3)SITEPRO P30120, 2.5 SCH.40 X 10'-0" MOUNT PIPES (CONMAT ITEM NO. ANT.16008)
(6)SITEPRO FCX45-U UNIVERSAL CROSSOVER PLATE KITS (CONMAT ITEM NO. ANT.56006)
CROSSOVER PLATE KITS
(2 PER SECTOR, 6 TOTAL)
6
D-1
ERICSSONERICSSON
ERICSSONERICSSON
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
A-4
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
2
A-4
1
ELEVATIONS
NEW NORTH ELEVATION
GROUND LEVEL
0'-0" A.G.L.
EXISTING NORTH ELEVATION
EXISTING AT&T ANTENNAS
AND EQUIPMENT. SEE
EXISTING ANTENNA PLAN.
1
A-3.1
EXISTING AND NEW AT&T
ANTENNAS AND EQUIPMENT.
SEE NEW ANTENNA PLANS.
1
A-3.2
GROUND LEVEL
0'-0" A.G.L.
EXISTING AT&T ANTENNA RAD CENTER
55'-0" A.G.L.
TOP OF EXISTING AT&T ANTENNAS
59'-0" A.G.L.
EXISTING AT&T ANTENNA RAD CENTER
57'-9" A.G.L.
TOP OF EXISTING & NEW AT&T ANTENNAS
59'-0" A.G.L.
NEW AT&T ANTENNA RAD CENTER
54'-0" A.G.L.
NEW AT&T ANTENNA RAD CENTER
±57'-10" A.G.L.
(E) MONOEUCALYPTUS
(E) BUILDING
EXISTING AT&T ANTENNA RAD CENTER
55'-0" A.G.L.
TOP OF EXISTING MONOEUCALYPTUS
60'-0" A.G.L.
(E) MONOEUCALYPTUS
(E) BUILDING
TOP OF EXISTING MONOEUCALYPTUS
60'-0" A.G.L.
ERICSSONERICSSON
ERICSSONERICSSON
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
A-5
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
2
A-5
1
ELEVATIONS
NEW SOUTH ELEVATION
EXISTING SOUTH ELEVATION
GROUND LEVEL
0'-0" A.G.L.
GROUND LEVEL
0'-0" A.G.L.
(E) MONOEUCALYPTUS
EXISTING AT&T ANTENNAS
AND EQUIPMENT. SEE
EXISTING ANTENNA PLAN.
1
A-3.1
(E) POWER POLE
(E) BUILDING (BEHIND)
EXISTING AND NEW AT&T
ANTENNAS AND EQUIPMENT.
SEE NEW ANTENNA PLANS.
1
A-3.2
EXISTING AT&T ANTENNA RAD CENTER
55'-0" A.G.L.
TOP OF EXISTING AT&T ANTENNAS
59'-0" A.G.L.
EXISTING AT&T ANTENNA RAD CENTER
57'-9" A.G.L.
TOP OF EXISTING MONOEUCALYPTUS
60'-0" A.G.L.
(E) MONOEUCALYPTUS
(E) POWER POLE
(E) BUILDING (BEHIND)
TOP OF EXISTING & NEW AT&T ANTENNAS
59'-0" A.G.L.
NEW AT&T ANTENNA RAD CENTER
54'-0" A.G.L.
NEW AT&T ANTENNA RAD CENTER
±57'-10" A.G.L.
EXISTING AT&T ANTENNA RAD CENTER
55'-0" A.G.L.
TOP OF EXISTING MONOEUCALYPTUS
60'-0" A.G.L.
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
D-1
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
D-1
64
1 2 3
5
CROSSOVER PLATE KIT
7.
9
"
16
"
±
16.1"
TOP
16.1"
MANUFACTURER: ERICSSON
MODEL: AIR6419 B77G C BAND
WEIGHT: 78.55 LBS W/ MTG BRACKETS
FREQUENCY:REFER TO RF DATA SHEET
7.9"
28
.
3
"
FRONT SIDE
ANTENNA PIPE MOUNT
MOUNTING BRACKET BY
MANURACTURER
PART # SXK 109 2064/1
MOUNTING BRACKET
AIR ANTENNA DETAIL ANTENNA MOUNTING ELEVATION
12
"
M
I
N
.
SE
P
A
R
A
T
I
O
N
NEW AIR ANTENNA PER
DETAIL 1/D-1
EXISTING AIR ANTENNA
(RELOCATED)
EXISTING ANTENNA PIPE MOUNT
TO BE REMOVED AND REPLACED
WITH 2-7/8" O.D. x 10'-0" LONG PIPE
TABLE 2 PER MA
CONVERTER DETAIL
RECTIFIER DETAIL
NEQ. 15930 1R482000E3
RECTIFIER, NETSURETM 512 & 721, HIGH
EFFICIENCY,
-48 VDC, 40 A/2000 W, 120/208/240 VAC,
SINGLE PHASE INPUT,
DIMENSIONS (HxWxD): 1.7" x 3.3" x 9.9"
WEIGHT: 2.49 LBS.
NEW CROSSOVER PLATE KIT TYP.
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
G-1
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
ANTENNA GROUNDING PLAN (TYP. PER SECTOR)1
G-1
NE
N
E
SESW
W
NW
S
GROUNDING PLAN
COMPRESSION TYPE CONNECTION
GROUNDING WIRE
CADWELD TYPE CONNECTION
GROUND BUS BAR
GROUNDING SYMBOLS:
@ 55' RRU MOUNT CENTER LINE
(E) ANTENNA GROUND BAR
TYP. (TO BE VERIFIED IN FIELD)
(N) AWG 2 INSULATED COPPER GROUND
WIRE FROM (N) ANTENNAS TO (E)
ANTENNA GROUND BAR, TYP.
mobility corp.
SHEET TITLE
SHEET NUMBER
DRAWN BY:
CHECKED BY:JM
SD
1452 EDINGER AVE.
TUSTIN, CA 92780
PROJECT NO:
AT&T SITE NO:CLL01580
12844670
90% CD'S FOR REVIEW
EXPIRATION DATE: 06/30/2027
DATE SIGNED: 04/21/2026
APPLICANT:
CLL01580
FAIRVIEW BUSINESS PARK
2500 & 2500 3/4 S FAIIRVIEW ST.
SANTA ANA, CA 92704
SD04/09/2025A
ENGINEER:
G-2
PLANS PREPARED BY:
95% CD'S FOR REVIEW DS11/04/2025B
100% CD'S FOR SUBMITTAL DS12/02/20250
100% CD'S REV - CODE DS04/21/20261
G-2
9
ANTENNA PIPE MOUNT GROUNDING DETAIL 1 CABLE GROUND KIT DETAIL TYPICAL GROUND LUG CONNECTION DETAIL 2 3
4 5 6GROUNDING WIRE CONNECTION ANTENNA GROUNDING BAR CONN. DETAIL ANTENNA (12") GROUND BAR DETAIL
TYPICAL CADWELD TYPES COAX GROUND KIT 7 8RRU GROUNDING DETAIL
TEP is a family of companies licensed to provide different services in different jurisdictions. Depending on the jurisdiction , professional engineering and land
surveying services are provided by TEP OpCo LLC, a Delaware limited liability company, TEP Engineering, PLLC, a North Carolina professional limited liability
company, or M&H Engineering, PLLC, a New York professional limited liability company. General contractor services are provide d by TEPDB OpCo LLC, a
Delaware limited liability company. We acquire the requisite licenses in each state. Additional information can be obtained from the company.
November 8, 2025
Jon Maxwell 326 Tryon Road • Raleigh • NC 27603
M Squared Wireless (919) 661-6351 •StructuresRAL@tepgroup.net
1387 Calle Avanzado
San Clemente, CA 92673
(949) 391-6824
Subject: Appurtenance Mount Analysis
Carrier Designation: AT&T Mobility Reconfiguration
Site Number: CLL01580
Site Name: Fairview Business Park
FA Location Code: 12844670
IWM Job Number: WSLOS0068803
Engineering Firm Designation: TEP Project Number: 353924.1184084
Site Data: 2500-2520 S. Fairview Street
Santa Ana, Orange County, CA 92704
Latitude 33° 42' 48.41'', Longitude -117° 54' 35.49''
60.0± Foot - Monoeucalyptus Tower
55.0 Foot Mount Height - T-Arm
Dear Jon Maxwell,
TEP is pleased to submit this “Appurtenance Mount Analysis” to determine the structural integrity of the
antenna mount on the above-mentioned tower.
The purpose of the analysis is to determine acceptability of the mount's stress level. Based on our analysis we
have determined the stress level for the mount structure, under the following load case, to be:
LC1: Existing + Proposed + Reserved Loading Sufficient Capacity*
Note: See Table 2 for the existing, proposed, and reserved loading
*Sufficient upon completion of the changes listed in the “Recommendations” section of this report
The analysis has been performed in accordance with the ANSI/TIA-222-H Structural Standard for Antenna
Supporting Structures, Antennas, and Small Wind Turbine Support Structures, the 2022 California Building Code,
and the AT&T Mount Technical Guidance – Revision 25.
All equipment proposed in this report shall be installed in accordance with the appurtenances listed in Table 2 for
the determined available structural capacity to be effective.
We at TEP appreciate the opportunity of providing our continuing professional services to you and M Squared
Wireless. If you have any questions or need further assistance on this or any other projects, please give us a call.
Respectfully submitted by:
Adam M. Amortnont, P.E., S.E.
Mount Capacity
36.8%
2500 & 2520 3/4 S Fairview St.,
November 8, 2025
T-Arm Mount Analysis Fairview Business Park (12844670)
TEP Project Number 353924.1184084 Page 2
ANALYSIS CRITERIA
Table 1 - Mount Analysis Parameters
Ultimate
Wind Speed
(MPH)
Ice
Thickness
(in)
Ice Wind
Speed
(MPH)
Exposure
Category
Risk
Category
Topo
Procedure Kzt Ss Value Maintenance
Loads1,2
95 0.0 30 B II Method 2 1.0 1.305
Lm = 250 lbs
Lv = 250 lbs
Notes:
1) Maintenance loads applied per ANSI/TIA-222-H Chapter 16. Worst case positions are included in the RISA-3D Output.
2) Maintenance loads do not govern the structural capacity of the mount.
Table 2 - Existing, Proposed, and Reserved Antenna Loading Configuration
Existing/
Proposed
Mount
Level
(ft)
Ant
CL
(ft)
Qty Antenna Model Mount
Type
Owner/
Tenant
Final
Loading
Config.
55.0
57.7 3 Ericsson AIR6419 B77G1
(3) T-Arm Mounts AT&T 55.0
3 Commscope NNH4-65C-R6-V3
3 Kathrein 80010866
3 Quintel QS8658-3E
3 Ericsson 8843 B2/B66A
3 Ericsson 4449 B5/B12
3 Ericsson 4478 B14
3 Ericsson RRUS E2 B29
3 Ericsson RRUS-32 B30
3 Raycap DC9-48-60-24-8C-EV
53.0 3 Ericsson AIR6449 B77D1
Notes:
1) Antennas are to be vertically stacked in the same position (typical of 2 antennas per sector, 6 total).
ANALYSIS RESULTS
Table 3 - Mount Component Stresses vs. Capacity
Notes Component % Capacity Pass / Fail
- Face Horizontals 28.7 Pass
- Support Horizontals 25.2 Pass
- Mount Pipes 36.8 Pass
- Stabilizer Arms 1.5 Pass
1 Connection Bolts 20.0 Pass
1 Connection Plates 14.3 Pass
Structure Rating (max from all components) = 36.8%
Notes:
1) See additional documentation in “Appendix B - Additional Calculations” for calculations supporting the % capacity listed.
November 8, 2025
T-Arm Mount Analysis Fairview Business Park (12844670)
TEP Project Number 353924.1184084 Page 3
Table 4 - Documents Provided
Document Remarks Source
Previous Mount Analysis GPD Group Inc., dated September 28, 2021
GPD# 2021723.21.195375.01 M Squared
Previous Structural
Analysis
GPD Group Inc., dated September 28, 2021
GPD# 2021723.21.195375.01 M Squared
Scoping form AT&T Mobility, dated September 26, 2025
RFDS ID: RFDS-34994 M Squared
Preliminary Construction
Drawings
M Squared
Project No. 12844670 M Squared
Correspondence Correspondence from M Squared Wireless Solutions in reference to
the existing, proposed, and reserved loading. M Squared
RECOMMENDATIONS
1) If the load differs from that described in Table 2 of this report or the provisions of this analysis
are found to be invalid, another structural analysis should be performed.
2) The mount and its connection have sufficient capacity to carry the proposed loading
configuration.
In order for the results of this analysis to be valid, the mount modifications listed below must be
completed:
a) (3) SitePro P30120, 2.5 Sch.40 x 10’-0” Mount Pipes (CONMAT Item No. ANT.16008)
b) (6) SitePro FCX45-U Universal Crossover Plate Kits (CONMAT Item No. ANT.56006)
ANALYSIS ASSUMPTIONS
1) The mount was built in accordance with the manufacturer’s specifications.
2) The mount has been maintained in accordance with the manufacturer’s specification.
3) The configuration of antennas, transmission cables, mounts and other appurtenances are as
specified in Table 2. All mount components have been assumed to be in sufficient condition to
carry their full design capacity for this analysis.
4) Serviceability with respect to antenna twist, tilt, roll, or lateral translation, is not checked and is
left to the carrier or tower owner to ensure conformance.
5) TEP did not analyze the collar mount connection to the pole and assumes it to have sufficient
structural capacity to transfer the applied forces from the mount to the tower.
6) All material grades used for this analysis, unless verified by mount manufacturer design, were
assumed per AISC Table 2-4, 15th Edition. See RISA 3-D output for confirmation on grades used
in this analysis.
This analysis may be affected if any assumptions are not valid or have been made in error. TEP should
be notified to determine the effect on the structural integrity of the mount.
November 8, 2025
T-Arm Mount Analysis Fairview Business Park (12844670)
TEP Project Number 353924.1184084 Page 4
APPENDIX A
RISA-3D OUTPUT
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)SK-1
Nov 08, 2025 at 02:15 PM
T-Arm Mount.r3d
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)SK-2
Nov 08, 2025 at 02:16 PM
T-Arm Mount.r3d
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)SK-3
Nov 08, 2025 at 02:16 PM
T-Arm Mount.r3d
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)SK-4
Nov 08, 2025 at 02:16 PM
T-Arm Mount.r3d
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)SK-5
Nov 08, 2025 at 02:16 PM
T-Arm Mount.r3d
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)SK-6
Nov 08, 2025 at 02:16 PM
T-Arm Mount.r3d
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 1
Model Settings
Number of Reported Sections 5
Number of Internal Sections 100
Member Area Load Mesh Size (in2)144
Consider Shear Deformation Yes
Consider Torsional Warping Yes
Approximate Mesh Size (in)24
Transfer Forces Between Intersecting Wood Walls Yes
Increase Wood Wall Nailing Capacity for Wind Loads Yes
Include P-Delta for Walls Yes
Optimize Masonry and Wood Walls Yes
Maximum Number of Iterations 3
Single No
Multiple (Optimum)Yes
Maximum No
Global Axis corresponding to vertical direction Y
Convert Existing Data Yes
Default Global Plane for z-axis XZ
Plate Local Axis Orientation Nodal
Hot Rolled Steel AISC 15th (360-16): LRFD
Stiffness Adjustment No
Notional Annex None
Connections None
Cold Formed Steel None
Stiffness Adjustment Yes (Iterative)
Wood None
Temperature < 100F
Concrete None
Masonry None
Aluminum None
Structure Type Building
Stiffness Adjustment No
Stainless None
Stiffness Adjustment Yes (Iterative)
Compression Stress Block Rectangular Stress Block
Analyze using Cracked Sections Yes
Leave room for horizontal rebar splices (2*d bar spacing)Yes
List forces which were ignored for design in the Detail Report Yes
Column Min Steel 1
Column Max Steel 8
Rebar Material Spec ASTM A615
Warn if beam-column framing arrangement is not understood No
Number of Shear Regions 4
Region 2 & 3 Spacing Increase Increment (in)4
Code ASCE 7-16
Risk Category I or II
Drift Cat Other
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 2
Model Settings (Continued)
Base Elevation (ft)
Include the weight of the structure in base shear calcs Yes
S1 (g)1
SD1 (g)1
SDS (g)1
TL (sec)5
T Z (sec)
T X (sec)
CtZ 0.02
CtX 0.02
CtExp. Z 0.75
CtExp. X 0.75
R Z 3
R X 3
Ω0Z 1
Ω0X 1
CdZ 4
CdX 4
ρ Z 1
ρ X 1
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 3
Hot Rolled Steel Properties
Label E [ksi] G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹] Density [k/ft³] Yield [ksi]Ry Fu [ksi]Rt
1 A992 29000 11154 0.3 0.65 0.49 50 1.1 65 1.1
2 A36 Gr.36 29000 11154 0.3 0.65 0.49 36 1.5 58 1.2
3 A572 Gr.50 29000 11154 0.3 0.65 0.49 50 1.1 65 1.1
4 A500 Gr.B RND 29000 11154 0.3 0.65 0.527 42 1.4 58 1.3
5 A500 Gr.B Rect 29000 11154 0.3 0.65 0.527 46 1.4 58 1.3
6 A53 Gr.B 29000 11154 0.3 0.65 0.49 35 1.6 60 1.2
7 A1085 29000 11154 0.3 0.65 0.49 50 1.4 65 1.3
Hot Rolled Steel Section Sets
Label Shape Type Design List Material Design Rule Area [in²] Iyy [in⁴]Izz [in⁴] J [in⁴]
1 Mount Pipes 2.5 PIPE_2.5 None None A53 Gr.B Typical 1.61 1.45 1.45 2.89
2 Mount Pipe 2.0 PIPE_2.0 None None A53 Gr.B Typical 1.02 0.627 0.627 1.25
3 Support Horizontals HSS4X4X4 None None A500 Gr.B Rect Typical 3.37 7.8 7.8 12.8
4 Support Verticals PIPE_4.0 None None A53 Gr.B Typical 2.96 6.82 6.82 13.6
5 Face Horizontals PIPE_3.0 None None A53 Gr.B Typical 2.07 2.85 2.85 5.69
6 Stabiliizer Arm PIPE_2.0 None None A53 Gr.B Typical 1.02 0.627 0.627 1.25
Material Take-Off
Material Size Pieces Length[ft]Weight[K]
1 General Members
2 RIGID 33 5.4 0
3 Total General 33 5.4 0
4
5 Hot Rolled Steel
6 A500 Gr.B Rect HSS4X4X4 6 18 0.222
7 A53 Gr.B PIPE_2.0 15 113.2 0.393
8 A53 Gr.B PIPE_2.5 3 30 0.164
9 A53 Gr.B PIPE_3.0 6 78 0.549
10 A53 Gr.B PIPE_4.0 6 9 0.091
11 Total HR Steel 36 248.2 1.419
Node Boundary Conditions
Node Label X [k/in]Y [k/in]Z [k/in]X Rot [k-ft/rad]Y Rot [k-ft/rad]Z Rot [k-ft/rad]
1 S1 Reaction Reaction Reaction Reaction Reaction Reaction
2 N13 Reaction Reaction Reaction Reaction Reaction Reaction
3 N48 Reaction Reaction Reaction Reaction Reaction Reaction
4 N59 Reaction Reaction Reaction Reaction Reaction Reaction
5 N93 Reaction Reaction Reaction Reaction Reaction Reaction
6 N104 Reaction Reaction Reaction Reaction Reaction Reaction
Node Coordinates
Label X [ft]Y [ft]Z [ft]Detach From Diaphragm
1 S1 1.319078 -1.5 -1.02606
2 N2 4.652411 -1.5 -1.02606
3 N3 4.319078 -1.5 -1.02606
4 N4 4.319078 -0.75 -1.02606
5 N5 4.319078 -2.25 -1.02606
6 N6 4.652411 -1.5 -7.52606
7 N7 4.652411 -1.5 5.47394
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 4
Node Coordinates (Continued)
Label X [ft]Y [ft]Z [ft]Detach From Diaphragm
8 N8 4.652411 -1.5 -7.02606
9 N12 4.777411 4.75 -7.02606
10 N16 4.777411 -5.25 -7.02606
11 N11 4.777411 -1.5 -7.02606
12 N13 1.319078 2.25 -1.02606
13 N14 4.652411 2.25 -1.02606
14 N15 4.319078 2.25 -1.02606
15 N16A 4.319078 3 -1.02606
16 N17 4.319078 1.5 -1.02606
17 N18 4.652411 2.25 -7.52606
18 N19 4.652411 2.25 5.47394
19 N20 4.652411 2.25 -7.02606
20 N21 4.777411 2.25 -7.02606
21 N124A 2.819078 2.25 -1.02606
22 N139 -0.680922 -1.5 -1.02606
23 N147 2.819078 0.25 -1.15114
24 N148 2.819078 4.25 -1.15114
25 N145 2.819078 2.25 -1.15114
26 N48 -1.680922 -1.5 -2.758111
27 N49 -3.347589 -1.5 -5.644863
28 N50 -3.180922 -1.5 -5.356187
29 N51 -3.180922 -0.75 -5.356187
30 N52 -3.180922 -2.25 -5.356187
31 N53 -8.976754 -1.5 -2.394863
32 N54 2.281576 -1.5 -8.894863
33 N59 -1.680922 2.25 -2.758111
34 N60 -3.347589 2.25 -5.644863
35 N61 -3.180922 2.25 -5.356187
36 N62 -3.180922 3 -5.356187
37 N63 -3.180922 1.5 -5.356187
38 N64 -8.976754 2.25 -2.394863
39 N65 2.281576 2.25 -8.894863
40 N88 -2.430922 2.25 -4.057149
41 N90 -2.539244 0.25 -3.99461
42 N91 -2.539244 4.25 -3.99461
43 N92 -2.539244 2.25 -3.99461
44 N93 -1.680922 -1.5 0.70599
45 N94 -3.347589 -1.5 3.592742
46 N95 -3.180922 -1.5 3.304067
47 N96 -3.180922 -0.75 3.304067
48 N97 -3.180922 -2.25 3.304067
49 N98 2.281576 -1.5 6.842742
50 N99 -8.976754 -1.5 0.342742
51 N104 -1.680922 2.25 0.70599
52 N105 -3.347589 2.25 3.592742
53 N106 -3.180922 2.25 3.304067
54 N107 -3.180922 3 3.304067
55 N108 -3.180922 1.5 3.304067
56 N109 2.281576 2.25 6.842742
57 N110 -8.976754 2.25 0.342742
58 N133 -2.430922 2.25 2.005028
59 N135 -2.3226 0.25 2.067568
60 N136A -2.3226 4.25 2.067568
61 N137 -2.3226 2.25 2.067568
62 N128A 4.652411 2.25 -4.52606
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 5
Node Coordinates (Continued)
Label X [ft]Y [ft]Z [ft]Detach From Diaphragm
63 N129A -6.378678 2.25 -3.894863
64 N130A -0.3165 2.25 5.342742
65 N131 4.652411 2.25 2.47394
66 N132 -0.3165 2.25 -7.394863
67 N133A -6.378678 2.25 1.842742
68 N68 4.652411 -1.5 -3.02606
69 N69 4.777411 5.375 -3.02606
70 N70 4.777411 -4.625 -3.02606
71 N71 4.777411 -1.5 -3.02606
72 N72 4.652411 2.25 -3.02606
73 N73 4.777411 2.25 -3.02606
74 N74 4.652411 -1.5 -0.27606
75 N75 4.777411 4.75 -0.27606
76 N76 4.777411 -5.25 -0.27606
77 N77 4.777411 -1.5 -0.27606
78 N78 4.652411 2.25 -0.27606
79 N79 4.777411 2.25 -0.27606
80 N80 4.652411 -1.5 4.97394
81 N81 4.777411 2.75 4.97394
82 N82 4.777411 -5.25 4.97394
83 N83 4.777411 -1.5 4.97394
84 N84 4.652411 2.25 4.97394
85 N85 4.777411 2.25 4.97394
86 N86 -8.543878 -1.5 -2.644784
87 N87 -8.60641 4.75 -2.753093
88 N88A -8.60641 -5.25 -2.753093
89 N89 -8.60641 -1.5 -2.753093
90 N90A -8.543878 2.25 -2.644784
91 N91A -8.60641 2.25 -2.753093
92 N92A -5.079777 -1.5 -4.644784
93 N93A -5.142309 5.375 -4.753093
94 N94A -5.142309 -4.625 -4.753093
95 N95A -5.142309 -1.5 -4.753093
96 N96A -5.079777 2.25 -4.644784
97 N97A -5.142309 2.25 -4.753093
98 N98A -2.698207 -1.5 -6.019784
99 N99A -2.760739 4.75 -6.128093
100 N100 -2.760739 -5.25 -6.128093
101 N101 -2.760739 -1.5 -6.128093
102 N102 -2.698207 2.25 -6.019784
103 N103 -2.760739 2.25 -6.128093
104 N104A 1.848427 -1.5 -8.644784
105 N105A 1.785894 2.75 -8.753093
106 N106A 1.785894 -5.25 -8.753093
107 N107A 1.785894 -1.5 -8.753093
108 N108A 1.848427 2.25 -8.644784
109 N109A 1.785894 2.25 -8.753093
110 N110A 1.848584 -1.5 6.592753
111 N111 1.785999 4.75 6.701153
112 N112 1.785999 -5.25 6.701153
113 N113 1.785999 -1.5 6.701153
114 N114 1.848584 2.25 6.592753
115 N115 1.785999 2.25 6.701153
116 N116 -1.615518 -1.5 4.592753
117 N117 -1.678102 5.375 4.701153
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 6
Node Coordinates (Continued)
Label X [ft]Y [ft]Z [ft]Detach From Diaphragm
118 N118 -1.678102 -4.625 4.701153
119 N119 -1.678102 -1.5 4.701153
120 N120 -1.615518 2.25 4.592753
121 N121 -1.678102 2.25 4.701153
122 N122 -3.997088 -1.5 3.217753
123 N123 -4.059672 4.75 3.326153
124 N124 -4.059672 -5.25 3.326153
125 N125 -4.059672 -1.5 3.326153
126 N126 -3.997088 2.25 3.217753
127 N127 -4.059672 2.25 3.326153
128 N128 -8.543721 -1.5 0.592753
129 N129 -8.606306 2.75 0.701153
130 N130 -8.606306 -5.25 0.701153
131 N131A -8.606306 -1.5 0.701153
132 N132A -8.543721 2.25 0.592753
133 N133B -8.606306 2.25 0.701153
Member Primary Data
Label I Node J Node Section/Shape Type Design List Material Design Rule
1 FF-BH1 N6 N7 Face Horizontals None None A53 Gr.B Typical
2 FF-BH2 N98 N99 Face Horizontals None None A53 Gr.B Typical
3 FF-BH3 N53 N54 Face Horizontals None None A53 Gr.B Typical
4 FF-TH1 N18 N19 Face Horizontals None None A53 Gr.B Typical
5 FF-TH2 N109 N110 Face Horizontals None None A53 Gr.B Typical
6 FF-TH3 N64 N65 Face Horizontals None None A53 Gr.B Typical
7 MP-1 N12 N16 Mount Pipe 2.0 None None A53 Gr.B Typical
8 MP-3 N75 N76 Mount Pipe 2.0 None None A53 Gr.B Typical
9 MP-4 N81 N82 Mount Pipe 2.0 None None A53 Gr.B Typical
10 MP-5 N111 N112 Mount Pipe 2.0 None None A53 Gr.B Typical
11 MP-7 N123 N124 Mount Pipe 2.0 None None A53 Gr.B Typical
12 MP-8 N129 N130 Mount Pipe 2.0 None None A53 Gr.B Typical
13 MP-9 N87 N88A Mount Pipe 2.0 None None A53 Gr.B Typical
14 MP-11 N99A N100 Mount Pipe 2.0 None None A53 Gr.B Typical
15 MP-12 N105A N106A Mount Pipe 2.0 None None A53 Gr.B Typical
16 RRU-1 N148 N147 Mount Pipe 2.0 None None A53 Gr.B Typical
17 RRU-2 N136A N135 Mount Pipe 2.0 None None A53 Gr.B Typical
18 RRU-3 N91 N90 Mount Pipe 2.0 None None A53 Gr.B Typical
19 MP-2 N69 N70 Mount Pipes 2.5 None None A53 Gr.B Typical
20 MP-6 N117 N118 Mount Pipes 2.5 None None A53 Gr.B Typical
21 MP-10 N93A N94A Mount Pipes 2.5 None None A53 Gr.B Typical
22 M6 N11 N8 RIGID None None RIGID Typical
23 M8 N3 N2 RIGID None None RIGID Typical
24 M10 N15 N14 RIGID None None RIGID Typical
25 M11 N21 N20 RIGID None None RIGID Typical
26 M33 N50 N49 RIGID None None RIGID Typical
27 M34 N61 N60 RIGID None None RIGID Typical
28 M38 N71 N68 RIGID None None RIGID Typical
29 M39 N73 N72 RIGID None None RIGID Typical
30 M41 N77 N74 RIGID None None RIGID Typical
31 M42 N88 N92 RIGID None None RIGID Typical
32 M42A N79 N78 RIGID None None RIGID Typical
33 M44 N83 N80 RIGID None None RIGID Typical
34 M45 N85 N84 RIGID None None RIGID Typical
35 M47 N89 N86 RIGID None None RIGID Typical
36 M48 N91A N90A RIGID None None RIGID Typical
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 7
Member Primary Data (Continued)
Label I Node J Node Section/Shape Type Design List Material Design Rule
37 M50 N95A N92A RIGID None None RIGID Typical
38 M51 N97A N96A RIGID None None RIGID Typical
39 M53 N101 N98A RIGID None None RIGID Typical
40 M54 N103 N102 RIGID None None RIGID Typical
41 M55 N95 N94 RIGID None None RIGID Typical
42 M56 N106 N105 RIGID None None RIGID Typical
43 M56A N107A N104A RIGID None None RIGID Typical
44 M57 N109A N108A RIGID None None RIGID Typical
45 M59 N113 N110A RIGID None None RIGID Typical
46 M60 N115 N114 RIGID None None RIGID Typical
47 M62 N119 N116 RIGID None None RIGID Typical
48 M63 N121 N120 RIGID None None RIGID Typical
49 M64 N133 N137 RIGID None None RIGID Typical
50 M65 N125 N122 RIGID None None RIGID Typical
51 M66 N127 N126 RIGID None None RIGID Typical
52 M68 N131A N128 RIGID None None RIGID Typical
53 M69 N133B N132A RIGID None None RIGID Typical
54 M74 N124A N145 RIGID None None RIGID Typical
55 SA-1 N131 N130A Stabiliizer Arm None None A53 Gr.B Typical
56 SA-2 N133A N129A Stabiliizer Arm None None A53 Gr.B Typical
57 SA-3 N128A N132 Stabiliizer Arm None None A53 Gr.B Typical
58 SA1-BH S1 N3 Support Horizontals None None A500 Gr.B Rect Typical
59 SA1-TH N13 N15 Support Horizontals None None A500 Gr.B Rect Typical
60 SA2-BH N93 N95 Support Horizontals None None A500 Gr.B Rect Typical
61 SA2-TH N104 N106 Support Horizontals None None A500 Gr.B Rect Typical
62 SA3-BH N48 N50 Support Horizontals None None A500 Gr.B Rect Typical
63 SA3-TH N59 N61 Support Horizontals None None A500 Gr.B Rect Typical
64 SA1-BV N4 N5 Support Verticals None None A53 Gr.B Typical
65 SA1-TV N16A N17 Support Verticals None None A53 Gr.B Typical
66 SA2-BV N96 N97 Support Verticals None None A53 Gr.B Typical
67 SA2-TV N107 N108 Support Verticals None None A53 Gr.B Typical
68 SA3-BV N51 N52 Support Verticals None None A53 Gr.B Typical
69 SA3-TV N62 N63 Support Verticals None None A53 Gr.B Typical
Member Advanced Data
Label I Release J Release Col-Wall Vert Release Physical Deflection Ratio Options Seismic DR
1 FF-BH1 Yes ** NA **None
2 FF-BH2 Yes ** NA **None
3 FF-BH3 Yes ** NA **None
4 FF-TH1 Yes ** NA **None
5 FF-TH2 Yes ** NA **None
6 FF-TH3 Yes ** NA **None
7 MP-1 Yes ** NA **None
8 MP-3 Yes ** NA **None
9 MP-4 Yes ** NA **None
10 MP-5 Yes ** NA **None
11 MP-7 Yes ** NA **None
12 MP-8 Yes ** NA **None
13 MP-9 Yes ** NA **None
14 MP-11 Yes ** NA **None
15 MP-12 Yes ** NA **None
16 RRU-1 Yes ** NA **None
17 RRU-2 Yes ** NA **None
18 RRU-3 Yes ** NA **None
19 MP-2 Yes ** NA **None
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 8
Member Advanced Data (Continued)
Label I Release J Release Col-Wall Vert Release Physical Deflection Ratio Options Seismic DR
20 MP-6 Yes ** NA **None
21 MP-10 Yes ** NA **None
22 M6 Yes ** NA **None
23 M8 Yes ** NA **None
24 M10 Yes ** NA **None
25 M11 Yes ** NA **None
26 M33 Yes ** NA **None
27 M34 Yes ** NA **None
28 M38 Yes ** NA **None
29 M39 Yes ** NA **None
30 M41 Yes ** NA **None
31 M42 Yes ** NA **None
32 M42A Yes ** NA **None
33 M44 Yes ** NA **None
34 M45 Yes ** NA **None
35 M47 Yes ** NA **None
36 M48 Yes ** NA **None
37 M50 Yes ** NA **None
38 M51 Yes ** NA **None
39 M53 Yes ** NA **None
40 M54 Yes ** NA **None
41 M55 Yes ** NA **None
42 M56 Yes ** NA **None
43 M56A Yes ** NA **None
44 M57 Yes ** NA **None
45 M59 Yes ** NA **None
46 M60 Yes ** NA **None
47 M62 Yes ** NA **None
48 M63 Yes ** NA **None
49 M64 Yes ** NA **None
50 M65 Yes ** NA **None
51 M66 Yes ** NA **None
52 M68 Yes ** NA **None
53 M69 Yes ** NA **None
54 M74 Yes ** NA **None
55 SA-1 BenPIN BenPIN Yes ** NA **None
56 SA-2 BenPIN BenPIN Yes ** NA **None
57 SA-3 BenPIN BenPIN Yes ** NA **None
58 SA1-BH Yes ** NA **None
59 SA1-TH Yes ** NA **None
60 SA2-BH Yes ** NA **None
61 SA2-TH Yes ** NA **None
62 SA3-BH Yes ** NA **None
63 SA3-TH Yes ** NA **None
64 SA1-BV Yes ** NA **None
65 SA1-TV Yes ** NA **None
66 SA2-BV Yes ** NA **None
67 SA2-TV Yes ** NA **None
68 SA3-BV Yes ** NA **None
69 SA3-TV Yes ** NA **None
Hot Rolled Steel Design Parameters
Label Shape Length [ft]Lb y-y [ft]Lb z-z [ft]K y-y K z-z Channel Conn. a [ft] Function
1 FF-BH1 Face Horizontals 13 6.25 6.25 2.1 2.1 N/A N/A Lateral
2 FF-BH2 Face Horizontals 13 6.25 6.25 2.1 2.1 N/A N/A Lateral
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 9
Hot Rolled Steel Design Parameters (Continued)
Label Shape Length [ft]Lb y-y [ft]Lb z-z [ft]K y-y K z-z Channel Conn. a [ft] Function
3 FF-BH3 Face Horizontals 13 6.25 6.25 2.1 2.1 N/A N/A Lateral
4 FF-TH1 Face Horizontals 13 6.25 6.25 2.1 2.1 N/A N/A Lateral
5 FF-TH2 Face Horizontals 13 6.25 6.25 2.1 2.1 N/A N/A Lateral
6 FF-TH3 Face Horizontals 13 6.25 6.25 2.1 2.1 N/A N/A Lateral
7 MP-1 Mount Pipe 2.0 10 Segment Segment 2.1 2.1 N/A N/A Lateral
8 MP-3 Mount Pipe 2.0 10 Segment Segment 2.1 2.1 N/A N/A Lateral
9 MP-4 Mount Pipe 2.0 8 Segment Segment 2.1 2.1 N/A N/A Lateral
10 MP-5 Mount Pipe 2.0 10 Segment Segment 2.1 2.1 N/A N/A Lateral
11 MP-7 Mount Pipe 2.0 10 Segment Segment 2.1 2.1 N/A N/A Lateral
12 MP-8 Mount Pipe 2.0 8 Segment Segment 2.1 2.1 N/A N/A Lateral
13 MP-9 Mount Pipe 2.0 10 Segment Segment 2.1 2.1 N/A N/A Lateral
14 MP-11 Mount Pipe 2.0 10 Segment Segment 2.1 2.1 N/A N/A Lateral
15 MP-12 Mount Pipe 2.0 8 Segment Segment 2.1 2.1 N/A N/A Lateral
16 RRU-1 Mount Pipe 2.0 4 Segment Segment 2.1 2.1 N/A N/A Lateral
17 RRU-2 Mount Pipe 2.0 4 Segment Segment 2.1 2.1 N/A N/A Lateral
18 RRU-3 Mount Pipe 2.0 4 Segment Segment 2.1 2.1 N/A N/A Lateral
19 MP-2 Mount Pipes 2.5 10 Segment Segment 2.1 2.1 N/A N/A Lateral
20 MP-6 Mount Pipes 2.5 10 Segment Segment 2.1 2.1 N/A N/A Lateral
21 MP-10 Mount Pipes 2.5 10 Segment Segment 2.1 2.1 N/A N/A Lateral
22 SA-1 Stabiliizer Arm 5.738 1 1 N/A N/A Lateral
23 SA-2 Stabiliizer Arm 5.738 1 1 N/A N/A Lateral
24 SA-3 Stabiliizer Arm 5.738 1 1 N/A N/A Lateral
25 SA1-BH Support Horizontals 3 2.1 2.1 N/A N/A Lateral
26 SA1-TH Support Horizontals 3 2.1 2.1 N/A N/A Lateral
27 SA2-BH Support Horizontals 3 2.1 2.1 N/A N/A Lateral
28 SA2-TH Support Horizontals 3 2.1 2.1 N/A N/A Lateral
29 SA3-BH Support Horizontals 3 2.1 2.1 N/A N/A Lateral
30 SA3-TH Support Horizontals 3 2.1 2.1 N/A N/A Lateral
31 SA1-BV Support Verticals 1.5 2.1 2.1 N/A N/A Lateral
32 SA1-TV Support Verticals 1.5 2.1 2.1 N/A N/A Lateral
33 SA2-BV Support Verticals 1.5 2.1 2.1 N/A N/A Lateral
34 SA2-TV Support Verticals 1.5 2.1 2.1 N/A N/A Lateral
35 SA3-BV Support Verticals 1.5 2.1 2.1 N/A N/A Lateral
36 SA3-TV Support Verticals 1.5 2.1 2.1 N/A N/A Lateral
Basic Load Cases
BLC Description Category X Gravity Y Gravity Z Gravity Nodal Point Distributed
1 Dead None -1 51
2 0 Wind - No Ice None 51 36
3 30 Wind - No Ice None 102 72
4 45 Wind - No Ice None 102 72
5 60 Wind - No Ice None 102 72
6 90 Wind - No Ice None 51 36
7 120 Wind - No Ice None 102 72
8 135 Wind - No Ice None 102 72
9 150 Wind - No Ice None 102 72
10 180 Wind - No Ice None 51 36
11 210 Wind - No Ice None 102 72
12 225 Wind - No Ice None 102 72
13 240 Wind - No Ice None 102 72
14 270 Wind - No Ice None 51 36
15 300 Wind - No Ice None 102 72
16 315 Wind - No Ice None 102 72
17 330 Wind - No Ice None 102 72
18 Ice Weight None 51 36
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 10
Basic Load Cases (Continued)
BLC Description Category X Gravity Y Gravity Z Gravity Nodal Point Distributed
19 0 Wind - Ice None 51 36
20 30 Wind - Ice None 102 72
21 45 Wind - Ice None 102 72
22 60 Wind - Ice None 102 72
23 90 Wind - Ice None 51 36
24 120 Wind - Ice None 102 72
25 135 Wind - Ice None 102 72
26 150 Wind - Ice None 102 72
27 180 Wind - Ice None 51 36
28 210 Wind - Ice None 102 72
29 225 Wind - Ice None 102 72
30 240 Wind - Ice None 102 72
31 270 Wind - Ice None 51 36
32 300 Wind - Ice None 102 72
33 315 Wind - Ice None 102 72
34 330 Wind - Ice None 102 72
35 Lm None 1
36 Lv None 1
37 Seismic Load X ELX -1 51
38 Seismic Load Z ELZ -1 51
Load Combinations
Description Solve P-Delta BLC Factor BLC Factor BLC Factor
1 1.4D Yes Y 1 1.4
2 0.9D+1.0 0-Wind Yes Y 1 0.9 2 1
3 0.9D+1.0 30-Wind Yes Y 1 0.9 3 1
4 0.9D+1.0 45-Wind Yes Y 1 0.9 4 1
5 0.9D+1.0 60-Wind Yes Y 1 0.9 5 1
6 0.9D+1.0 90-Wind Yes Y 1 0.9 6 1
7 0.9D+1.0 120-Wind Yes Y 1 0.9 7 1
8 0.9D+1.0 135-Wind Yes Y 1 0.9 8 1
9 0.9D+1.0 150-Wind Yes Y 1 0.9 9 1
10 0.9D+1.0 180-Wind Yes Y 1 0.9 10 1
11 0.9D+1.0 210-Wind Yes Y 1 0.9 11 1
12 0.9D+1.0 225-Wind Yes Y 1 0.9 12 1
13 0.9D+1.0 240-Wind Yes Y 1 0.9 13 1
14 0.9D+1.0 270-Wind Yes Y 1 0.9 14 1
15 0.9D+1.0 300-Wind Yes Y 1 0.9 15 1
16 0.9D+1.0 315-Wind Yes Y 1 0.9 16 1
17 0.9D+1.0 330-Wind Yes Y 1 0.9 17 1
18 1.2D+1.0 0-Wind Yes Y 1 1.2 2 1
19 1.2D+1.0 30-Wind Yes Y 1 1.2 3 1
20 1.2D+1.0 45-Wind Yes Y 1 1.2 4 1
21 1.2D+1.0 60-Wind Yes Y 1 1.2 5 1
22 1.2D+1.0 90-Wind Yes Y 1 1.2 6 1
23 1.2D+1.0 120-Wind Yes Y 1 1.2 7 1
24 1.2D+1.0 135-Wind Yes Y 1 1.2 8 1
25 1.2D+1.0 150-Wind Yes Y 1 1.2 9 1
26 1.2D+1.0 180-Wind Yes Y 1 1.2 10 1
27 1.2D+1.0 210-Wind Yes Y 1 1.2 11 1
28 1.2D+1.0 225-Wind Yes Y 1 1.2 12 1
29 1.2D+1.0 240-Wind Yes Y 1 1.2 13 1
30 1.2D+1.0 270-Wind Yes Y 1 1.2 14 1
31 1.2D+1.0 300-Wind Yes Y 1 1.2 15 1
32 1.2D+1.0 315-Wind Yes Y 1 1.2 16 1
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 11
Load Combinations (Continued)
Description Solve P-Delta BLC Factor BLC Factor BLC Factor
33 1.2D+1.0 330-Wind Yes Y 1 1.2 17 1
34 1.2D+1.0Di+1.0 0-Wind Ice Y 1 1.2 18 1 19 1
35 1.2D+1.0Di+1.0 30-Wind Ice Y 1 1.2 18 1 20 1
36 1.2D+1.0Di+1.0 45-Wind Ice Y 1 1.2 18 1 21 1
37 1.2D+1.0Di+1.0 60-Wind Ice Y 1 1.2 18 1 22 1
38 1.2D+1.0Di+1.0 90-Wind Ice Y 1 1.2 18 1 23 1
39 1.2D+1.0Di+1.0 120-Wind Ice Y 1 1.2 18 1 24 1
40 1.2D+1.0Di+1.0 135-Wind Ice Y 1 1.2 18 1 25 1
41 1.2D+1.0Di+1.0 150-Wind Ice Y 1 1.2 18 1 26 1
42 1.2D+1.0Di+1.0 180-Wind Ice Y 1 1.2 18 1 27 1
43 1.2D+1.0Di+1.0 210-Wind Ice Y 1 1.2 18 1 28 1
44 1.2D+1.0Di+1.0 225-Wind Ice Y 1 1.2 18 1 29 1
45 1.2D+1.0Di+1.0 240-Wind Ice Y 1 1.2 18 1 30 1
46 1.2D+1.0Di+1.0 270-Wind Ice Y 1 1.2 18 1 31 1
47 1.2D+1.0Di+1.0 300-Wind Ice Y 1 1.2 18 1 32 1
48 1.2D+1.0Di+1.0 315-Wind Ice Y 1 1.2 18 1 33 1
49 1.2D+1.0Di+1.0 330-Wind Ice Y 1 1.2 18 1 34 1
50 1.2D+1.5Lv Yes Y 36 1.5 1 1.2
51 1.2D+1.5Lm+1.0 0-Wind Yes Y 1 1.2 2 0.1 35 1.5
52 1.2D+1.5Lm+1.0 30-Wind Yes Y 1 1.2 3 0.1 35 1.5
53 1.2D+1.5Lm+1.0 45-Wind Yes Y 1 1.2 4 0.1 35 1.5
54 1.2D+1.5Lm+1.0 60-Wind Yes Y 1 1.2 5 0.1 35 1.5
55 1.2D+1.5Lm+1.0 90-Wind Yes Y 1 1.2 6 0.1 35 1.5
56 1.2D+1.5Lm+1.0 120-Wind Yes Y 1 1.2 7 0.1 35 1.5
57 1.2D+1.5Lm+1.0 135-Wind Yes Y 1 1.2 8 0.1 35 1.5
58 1.2D+1.5Lm+1.0 150-Wind Yes Y 1 1.2 9 0.1 35 1.5
59 1.2D+1.5Lm+1.0 180-Wind Yes Y 1 1.2 10 0.1 35 1.5
60 1.2D+1.5Lm+1.0 210-Wind Yes Y 1 1.2 11 0.1 35 1.5
61 1.2D+1.5Lm+1.0 225-Wind Yes Y 1 1.2 12 0.1 35 1.5
62 1.2D+1.5Lm+1.0 240-Wind Yes Y 1 1.2 13 0.1 35 1.5
63 1.2D+1.5Lm+1.0 270-Wind Yes Y 1 1.2 14 0.1 35 1.5
64 1.2D+1.5Lm+1.0 300-Wind Yes Y 1 1.2 15 0.1 35 1.5
65 1.2D+1.5Lm+1.0 315-Wind Yes Y 1 1.2 16 0.1 35 1.5
66 1.2D+1.5Lm+1.0 330-Wind Yes Y 1 1.2 17 0.1 35 1.5
67 (1.2+0.2Sds)D+1.0 0 Seismic Yes Y 1 1.409 ELX 0.522
68 (1.2+0.2Sds)D+1.0 30 Seismic Yes Y 1 1.409 ELX 0.452 ELZ 0.261
69 (1.2+0.2Sds)D+1.0 45 Seismic Yes Y 1 1.409 ELX 0.369 ELZ 0.369
70 (1.2+0.2Sds)D+1.0 60 Seismic Yes Y 1 1.409 ELX 0.261 ELZ 0.452
71 (1.2+0.2Sds)D+1.0 90 Seismic Yes Y 1 1.409 ELZ 0.522
72 (1.2+0.2Sds)D+1.0 120 Seismic Yes Y 1 1.409 ELX -0.261 ELZ 0.452
73 (1.2+0.2Sds)D+1.0 135 Seismic Yes Y 1 1.409 ELX -0.369 ELZ 0.369
74 (1.2+0.2Sds)D+1.0 150 Seismic Yes Y 1 1.409 ELX -0.452 ELZ 0.261
75 (1.2+0.2Sds)D+1.0 180 Seismic Yes Y 1 1.409 ELX -0.522
76 (1.2+0.2Sds)D+1.0 210 Seismic Yes Y 1 1.409 ELX -0.452 ELZ -0.261
77 (1.2+0.2Sds)D+1.0 225 Seismic Yes Y 1 1.409 ELX -0.369 ELZ -0.369
78 (1.2+0.2Sds)D+1.0 240 Seismic Yes Y 1 1.409 ELX -0.261 ELZ -0.452
79 (1.2+0.2Sds)D+1.0 270 Seismic Yes Y 1 1.409 ELZ -0.522
80 (1.2+0.2Sds)D+1.0 300 Seismic Yes Y 1 1.409 ELX 0.261 ELZ -0.452
81 (1.2+0.2Sds)D+1.0 315 Seismic Yes Y 1 1.409 ELX 0.369 ELZ -0.369
82 (1.2+0.2Sds)D+1.0 330 Seismic Yes Y 1 1.409 ELX 0.452 ELZ -0.261
83 (0.9-0.2Sds)*DL+1.0 0 Seismic Yes Y 1 0.691 ELX 0.522
84 (0.9-0.2Sds)*DL+1.0 30 Seismic Yes Y 1 0.691 ELX 0.452 ELZ 0.261
85 (0.9-0.2Sds)*DL+1.0 Seismic Yes Y 1 0.691 ELX 0.369 ELZ 0.369
86 (0.9-0.2Sds)*DL+1.0 60 Seismic Yes Y 1 0.691 ELX 0.261 ELZ 0.452
87 (0.9-0.2Sds)*DL+1.0 90 Seismic Yes Y 1 0.691 ELZ 0.522
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 12
Load Combinations (Continued)
Description Solve P-Delta BLC Factor BLC Factor BLC Factor
88 (0.9-0.2Sds)*DL+1.0 120 Seismic Yes Y 1 0.691 ELX -0.261 ELZ 0.452
89 (0.9-0.2Sds)*DL+1.0 135 Seismic Yes Y 1 0.691 ELX -0.369 ELZ 0.369
90 (0.9-0.2Sds)*DL+1.0 150 Seismic Yes Y 1 0.691 ELX -0.452 ELZ 0.261
91 (0.9-0.2Sds)*DL+1.0 180 Seismic Yes Y 1 0.691 ELX -0.522
92 (0.9-0.2Sds)*DL+1.0 210 Seismic Yes Y 1 0.691 ELX -0.452 ELZ -0.261
93 (0.9-0.2Sds)*DL+1.0 225 Seismic Yes Y 1 0.691 ELX -0.369 ELZ -0.369
94 (0.9-0.2Sds)*DL+1.0 240 Seismic Yes Y 1 0.691 ELX -0.261 ELZ -0.452
95 (0.9-0.2Sds)*DL+1.0 270 Seismic Yes Y 1 0.691 ELZ -0.522
96 (0.9-0.2Sds)*DL+1.0 300 Seismic Yes Y 1 0.691 ELX 0.261 ELZ -0.452
97 (0.9-0.2Sds)*DL+1.0 315 Seismic Yes Y 1 0.691 ELX 0.369 ELZ -0.369
98 (0.9-0.2Sds)*DL+1.0 330 Seismic Yes Y 1 0.691 ELX 0.452 ELZ -0.261
Node Loads and Enforced Displacements (BLC 35 : Lm)
Node Label L, D, M Direction Magnitude [(k, k-ft), (in, rad), (k*s²/ft, k*s²*ft)]
1 N11 L Y -0.25
Node Loads and Enforced Displacements (BLC 36 : Lv)
Node Label L, D, M Direction Magnitude [(k, k-ft), (in, rad), (k*s²/ft, k*s²*ft)]
1 N6 L Y -0.25
Envelope Node Reactions
Node Label X [k]LC Y [k]LC Z [k]LC MX [k-ft] LC MY [k-ft] LC MZ [k-ft] LC
1 S1 max 0.887 18 0.965 59 0.285 7 0.49 50 1.684 31 2.507 59
2 min -0.366 10 0.418 83 -0.608 62 0.036 85 -0.983 7 1.109 83
3 N13 max 0.555 2 1.004 51 0.615 23 0.488 50 0.853 15 2.536 51
4 min -0.873 26 0.439 91 -0.283 13 0.038 83 -1.619 23 1.157 94
5 N48 max 0.271 3 0.925 70 0.443 6 2.012 69 1.68 26 -0.589 94
6 min -0.798 27 0.418 94 -0.738 30 0.94 93 -0.983 2 -1.296 70
7 N59 max 0.842 19 0.968 78 0.715 22 2.026 79 0.855 10 -0.618 92
8 min -0.399 11 0.439 86 -0.565 14 0.971 87 -1.629 18 -1.297 68
9 N93 max 0.494 33 0.925 80 0.921 22 -0.98 88 1.693 21 -0.517 87
10 min -0.486 9 0.418 88 -0.321 14 -2.128 80 -0.995 13 -1.098 79
11 N104 max 0.476 17 0.968 72 0.492 6 -1.029 86 0.876 5 -0.522 98
12 min -0.569 25 0.439 96 -0.96 30 -2.129 77 -1.652 29 -1.116 74
13 Totals:max 3.349 18 5.535 73 3.231 6
14 min -3.226 10 2.716 97 -3.231 30
Envelope AISC 15TH (360-16): LRFD Member Steel Code Checks
Member Shape Code CheckLoc[ft]LCShear CheckLoc[ft]DirLCphi*Pnc [k]phi*Pnt [k]phi*Mn y-y [k-ft]phi*Mn z-z [k-ft] Cb Eqn
1 MP-1 PIPE_2.0 0.368 6.25 50 0.038 2.5 56 15.275 32.13 1.872 1.872 1 H1-1b
2 FF-BH3 PIPE_3.0 0.287 6.5 29 0.11 6.5 21 25.929 65.205 5.749 5.749 1 H1-1b
3 FF-BH1 PIPE_3.0 0.284 6.5 18 0.11 6.5 26 25.929 65.205 5.749 5.749 1 H1-1b
4 FF-BH2 PIPE_3.0 0.283 6.5 23 0.11 6.5 31 25.929 65.205 5.749 5.749 1 H1-1b
5 MP-2 PIPE_2.5 0.28 3.125 50 0.041 6.875 50 35.651 50.715 3.596 3.596 1 H1-1b
6 FF-TH3 PIPE_3.0 0.259 6.5 20 0.114 6.5 29 25.929 65.205 5.749 5.749 1 H1-1b
7 FF-TH2 PIPE_3.0 0.255 6.5 31 0.114 6.5 23 25.929 65.205 5.749 5.749 1 H1-1b
8 FF-TH1 PIPE_3.0 0.254 6.5 26 0.114 6.5 18 25.929 65.205 5.749 5.749 1 H1-1b
9 SA1-BH HSS4X4X4 0.252 0 62 0.061 0 y 50 118.166 139.518 16.181 16.181 1.832 H1-1b
10 SA1-THHSS4X4X4 0.239 0 56 0.062 0 y 50 118.166 139.518 16.181 16.181 1.854 H1-1b
11 MP-5 PIPE_2.0 0.236 2.5 76 0.034 2.5 77 23.088 32.13 1.872 1.872 1 H1-1b
Company
Designer
Job Number
Model Name
:
:
:
:
TEP
SVW
TEP No. 353924.1184084
CLL01580 (12844670)
Checked By : SMS
11/8/2025
2:16:59 PM
RISA-3D Version 22 [ T-Arm Mount.r3d ]Page 13
Envelope AISC 15TH (360-16): LRFD Member Steel Code Checks (Continued)
Member Shape Code CheckLoc[ft]LCShear CheckLoc[ft]DirLCphi*Pnc [k]phi*Pnt [k]phi*Mn y-y [k-ft]phi*Mn z-z [k-ft] Cb Eqn
12 MP-9 PIPE_2.0 0.236 2.5 82 0.034 2.5 67 23.088 32.13 1.872 1.872 1 H1-1b
13 SA2-BH HSS4X4X4 0.232 0 68 0.033 0 y 82 118.166 139.518 16.181 16.181 1.833 H1-1b
14 SA3-BH HSS4X4X4 0.232 0 74 0.033 0 y 71 118.166 139.518 16.181 16.181 1.833 H1-1b
15 SA2-THHSS4X4X4 0.231 0 76 0.033 0 y 80 118.166 139.518 16.181 16.181 1.858 H1-1b
16 SA3-THHSS4X4X4 0.231 0 82 0.033 0 y 70 118.166 139.518 16.181 16.181 1.858 H1-1b
17 MP-12 PIPE_2.0 0.228 4.25 81 0.035 0.5 72 15.275 32.13 1.872 1.872 1 H1-1b
18 MP-8 PIPE_2.0 0.228 4.25 76 0.035 0.5 67 15.275 32.13 1.872 1.872 1 H1-1b
19 MP-4 PIPE_2.0 0.228 4.25 71 0.035 0.5 78 15.275 32.13 1.872 1.872 1 H1-1b
20 MP-7 PIPE_2.0 0.215 2.5 31 0.036 2.5 82 23.088 32.13 1.872 1.872 1 H1-1b
21 MP-11 PIPE_2.0 0.213 2.5 19 0.036 2.5 71 23.088 32.13 1.872 1.872 1 H1-1b
22 MP-3 PIPE_2.0 0.196 2.5 18 0.042 6.25 50 23.088 32.13 1.872 1.872 1 H1-1b
23 MP-10 PIPE_2.5 0.19 3.125 67 0.032 3.125 82 35.651 50.715 3.596 3.596 1 H1-1b
24 MP-6 PIPE_2.5 0.19 3.125 78 0.032 3.125 77 35.651 50.715 3.596 3.596 1 H1-1b
25 SA-2 PIPE_2.0 0.015 2.869 26 0.007 5.738 20 21.652 32.13 1.872 1.872 1 H1-1b
26 SA-1 PIPE_2.0 0.014 2.869 21 0.009 5.738 50 21.652 32.13 1.872 1.872 1 H1-1b
27 SA-3 PIPE_2.0 0.014 2.869 31 0.026 5.738 50 21.652 32.13 1.872 1.872 1 H1-1b
28 RRU-2 PIPE_2.0 0.014 2 31 0.003 2 31 26.005 32.13 1.872 1.872 1 H1-1b
29 RRU-3 PIPE_2.0 0.014 2 21 0.003 2 21 26.005 32.13 1.872 1.872 1 H1-1b
30 RRU-1 PIPE_2.0 0.014 2 26 0.003 2 25 26.005 32.13 1.872 1.872 1 H1-1b
31 SA1-BVPIPE_4.0 0 0.75 82 0 0.75 75 90.327 93.24 10.631 10.631 1 H1-1b*
32 SA1-TV PIPE_4.0 0 0.75 81 0 0.75 75 90.327 93.24 10.631 10.631 1 H1-1b*
33 SA2-BVPIPE_4.0 0 0.75 82 0 0.75 80 90.327 93.24 10.631 10.631 1 H1-1b*
34 SA2-TV PIPE_4.0 0 0.75 80 0 0.75 80 90.327 93.24 10.631 10.631 1 H1-1b*
35 SA3-BVPIPE_4.0 0 0.75 79 0 0.75 69 90.327 93.24 10.631 10.631 1 H1-1b*
36 SA3-TV PIPE_4.0 0 0.75 82 0 0.75 69 90.327 93.24 10.631 10.631 1 H1-1b*
November 8, 2025
T-Arm Mount Analysis Fairview Business Park (12844670)
TEP Project Number 353924.1184084 Page 5
APPENDIX B
ADDITIONAL CALCULATIONS
ASCE Hazards Report
Address:
No Address at This Location
Standard:ASCE/SEI 7-16 Latitude:33.713447
Risk Category:II Longitude:-117.909858
Soil Class:D - Default (see
Section 11.4.3)
Elevation:45.17017218691528 ft
(NAVD 88)
Wind
Results:
Wind Speed 95 Vmph
10-year MRI 66 Vmph
25-year MRI 72 Vmph
50-year MRI 76 Vmph
100-year MRI 81 Vmph
Data Source: ASCE/SEI 7-16, Fig. 26.5-1B and Figs. CC.2-1–CC.2-4, and Section 26.5.2
Date Accessed: Fri Nov 07 2025
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear
interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds
correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability =
0.00143, MRI = 700 years).
Site is not in a hurricane-prone region as defined in ASCE/SEI 7-16 Section 26.2.
Page 1 of 3https://ascehazardtool.org/Fri Nov 07 2025
SS : 1.305
S1 : 0.468
F a : 1.2
F v : N/A
SMS : 1.566
SM1 : N/A
SDS : 1.044
SD1 : N/A
T L : 8
PGA : 0.559
PGA M : 0.671
F PGA : 1.2
Ie : 1
C v : 1.361
Seismic
Site Soil Class:
Results:
Data Accessed:
Date Source:
D - Default (see Section 11.4.3)
USGS Seismic Design Maps
Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8.
Fri Nov 07 2025
Page 2 of 3https://ascehazardtool.org/Fri Nov 07 2025
Ice
Results:
Data Source:
Date Accessed:
Ice Thickness: 0 in.
Concurrent Temperature: 25 F
Gust Speed 30 mph
Standard ASCE/SEI 7-16, Figs. 10-2 through 10-8
Fri Nov 07 2025
Ice thicknesses on structures in exposed locations at elevations higher than the surrounding terrain and in valleys
and gorges may exceed the mapped values.
Values provided are equivalent radial ice thicknesses due to freezing rain with concurrent 3-second gust speeds,
for a 500-year mean recurrence interval, and temperatures concurrent with ice thicknesses due to freezing rain.
Thicknesses for ice accretions caused by other sources shall be obtained from local meteorological studies. Ice
thicknesses in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may
exceed the mapped values.
The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any
kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or
has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable
sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or
quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation,
relationship, or sponsorship of such third-party content by or from ASCE.
ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent
professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such
professionals in interpreting and applying the contents of this Tool or the ASCE standard.
In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors,
employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential
damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by
law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data
provided by the ASCE Hazard Tool.
Page 3 of 3https://ascehazardtool.org/Fri Nov 07 2025
CLL01580 (12844670)
TEP No.
Analysis By:SVW 11/8/2025
Checked By:SMS 11/8/2025
Code Revisions:IBC 2021
Tower Type:68.0
Ult. Wind Velocity:95 mph Kzt:1.000 Section 2.6.6
Live Load Velocity:30 mph Kd:0.950
Ice Wind Velocity:30 mph z-Mount:0.833
Base Ice Thickness:0.00 inches z-Antenna:0.845
Mount Centerline:55.0 ft Kiz:1.055 Section 2.6.10
Antenna Centerline:57.8 ft Ice Thickness:0.000 inches - Section 2.6.10
Exposure Category:B Kes-wind:0.95 Annex S (Table S-1)
Topo Procedure:Method 2 Kes-ice:0.85 Annex S (Table S-1)
Risk Category:II Ks:1.000 Section 2.6.7
Ground Elevation:45 ft Ke:0.998 Table 2-6
.
(qzGh)Mount:17.34 (qzGh)Mount:1.82
(qzGh)Antenna:17.59 (qzGh)Antenna:1.85
Seismic Code Revisions:
Seismic Risk Category:
SDS:1.044 Design Short Period Spectral Accel.
Ip:1.0 Importance Factor
Rp:2.0 Response Modification Factor
ρ:1.0
As:1.0 Applification Factor - TIA-222-H Section 2.7.8.1
S1:0.468 Spectral Acceleration at a Period of 1 Second
Cs:0.522 kips/kip TIA-H Sec 2.7.7.1.1
Cs-min:0.046 kips/kip TIA-H Sec 2.7.7.1.1
II
Seismic Input
Seismic Design Force
TIA-222-H
353924.1184084
Wind Calculations:
TIA-222-H
Monoeucalyptus
Wind Inputs:
Without Ice - (psf)With Ice - (psf)
Universal Force Generator | Version 1.15.4 | Contact: RisaUFG@tepgroup.net
CLL01580 (12844670)
TEP No.
Analysis By:
Checked By:
MFR Model Height (in) Width (in) Depth (in)Wt. (lbs)Azimuth°Qty Shape Member Label Loc. 1 Loc. 2 Loc. 3 Front Side Front Side Kₐ
**COMMSCOPE NNH4-65C-R6-V3 96.00 19.60 7.80 125.70 0.00 1 Flat MP-1 0.75 4.75 6.75 11.81 3.86 204.81 66.94 1.0
**ERICSSON AIR 6419 B77G 27.95 15.75 6.68 66.20 0.00 1 Flat MP-2 1.50 3.00 3.32 1.14 57.58 19.77 1.0
ERICSSON AIR 6449 B77D 30.39 15.87 8.07 81.60 0.00 1 Flat MP-2 6.25 7.75 4.02 2.14 62.73 33.39 0.9
KATHREIN 80010966 96.00 20.00 6.90 125.70 0.00 1 Flat MP-3 0.25 7.50 17.36 7.50 271.00 117.06 0.9
QUINTEL TECHNOLOGY QS8658-3E 96.00 12.00 9.60 98.00 0.00 1 Flat MP-4 0.25 5.75 11.47 9.60 178.97 149.84 0.9
ERICSSON RADIO 8843 B2/B66A 14.96 13.19 11.10 75.00 90.00 1 Flat MP-1 4.00 1.64 1.38 25.66 21.60 0.9
ERICSSON RADIO 4449 B5/B12 14.96 13.19 10.43 73.00 90.00 1 Flat MP-1 4.00 1.64 1.30 25.66 20.29 0.9
ERICSSON RADIO 4478 B14 18.10 13.40 8.26 59.40 0.00 1 Flat MP-3 4.00 2.02 1.25 31.55 19.45 0.9
ERICSSON RRUS E2 B29 20.40 18.50 7.50 52.90 90.00 1 Flat MP-4 1.75 3.15 1.29 49.09 20.06 0.9
ERICSSON RRUS 32 B30 27.20 12.05 7.00 52.90 90.00 1 Flat MP-4 1.75 2.73 1.67 42.63 26.04 0.9
RAYCAP DC9-48-60-24-8C-EV 31.40 10.24 10.24 26.20 0.00 1 Round RRU-1 1.00 1.14 1.14 17.86 17.86 0.9
**COMMSCOPE NNH4-65C-R6-V3 96.00 19.60 7.80 125.70 120.00 1 Flat MP-5 0.75 4.75 6.75 11.81 3.86 204.81 66.94 1.0
**ERICSSON AIR 6419 B77G 27.95 15.75 6.68 66.20 120.00 1 Flat MP-6 1.50 3.00 3.32 1.14 57.58 19.77 1.0
ERICSSON AIR 6449 B77D 30.39 15.87 8.07 81.60 120.00 1 Flat MP-6 6.25 7.75 4.02 2.14 62.73 33.39 0.9
KATHREIN 80010966 96.00 20.00 6.90 125.70 120.00 1 Flat MP-7 0.25 7.50 17.36 7.50 271.00 117.06 0.9
QUINTEL TECHNOLOGY QS8658-3E 96.00 12.00 9.60 98.00 120.00 1 Flat MP-8 0.25 5.75 11.47 9.60 178.97 149.84 0.9
ERICSSON RADIO 8843 B2/B66A 14.96 13.19 11.10 75.00 210.00 1 Flat MP-5 4.00 1.64 1.38 25.66 21.60 0.9
ERICSSON RADIO 4449 B5/B12 14.96 13.19 10.43 73.00 210.00 1 Flat MP-5 4.00 1.64 1.30 25.66 20.29 0.9
ERICSSON RADIO 4478 B14 18.10 13.40 8.26 59.40 120.00 1 Flat MP-7 4.00 2.02 1.25 31.55 19.45 0.9
ERICSSON RRUS E2 B29 20.40 18.50 7.50 52.90 210.00 1 Flat MP-8 1.75 3.15 1.29 49.09 20.06 0.9
ERICSSON RRUS 32 B30 27.20 12.05 7.00 52.90 210.00 1 Flat MP-8 1.75 2.73 1.67 42.63 26.04 0.9
RAYCAP DC9-48-60-24-8C-EV 31.40 10.24 10.24 26.20 0.00 1 Round RRU-2 1.00 1.14 1.14 17.86 17.86 0.9
**COMMSCOPE NNH4-65C-R6-V3 96.00 19.60 7.80 125.70 240.00 1 Flat MP-9 0.75 4.75 6.75 11.81 3.86 204.81 66.94 1.0
**ERICSSON AIR 6419 B77G 27.95 15.75 6.68 66.20 240.00 1 Flat MP-10 1.50 3.00 3.32 1.14 57.58 19.77 1.0
ERICSSON AIR 6449 B77D 30.39 15.87 8.07 81.60 240.00 1 Flat MP-10 6.25 7.75 4.02 2.14 62.73 33.39 0.9
KATHREIN 80010966 96.00 20.00 6.90 125.70 240.00 1 Flat MP-11 0.25 7.50 17.36 7.50 271.00 117.06 0.9
QUINTEL TECHNOLOGY QS8658-3E 96.00 12.00 9.60 98.00 240.00 1 Flat MP-12 0.25 5.75 11.47 9.60 178.97 149.84 0.9
ERICSSON RADIO 8843 B2/B66A 14.96 13.19 11.10 75.00 330.00 1 Flat MP-9 4.00 1.64 1.38 25.66 21.60 0.9
ERICSSON RADIO 4449 B5/B12 14.96 13.19 10.43 73.00 330.00 1 Flat MP-9 4.00 1.64 1.30 25.66 20.29 0.9
ERICSSON RADIO 4478 B14 18.10 13.40 8.26 59.40 240.00 1 Flat MP-11 4.00 2.02 1.25 31.55 19.45 0.9
ERICSSON RRUS E2 B29 20.40 18.50 7.50 52.90 330.00 1 Flat MP-12 1.75 3.15 1.29 49.09 20.06 0.9
ERICSSON RRUS 32 B30 27.20 12.05 7.00 52.90 330.00 1 Flat MP-12 1.75 2.73 1.67 42.63 26.04 0.9
RAYCAP DC9-48-60-24-8C-EV 31.40 10.24 10.24 26.20 0.00 1 Round RRU-3 1.00 1.14 1.14 17.86 17.86 0.9
353924.1184084
SVW 11/08/2025
SMS 11/08/2025
Fₐ and CₐAₐ values calculated in accordance with TIA-222-H, unless otherwise noted.
Azimuth is the absolute angle measured clockwise from RISA-3D global X-axis.
** CₐAₐ values are derived per Manufacturer CFD data Distance Along Member (ft)CₐAₐ (ft²)Fₐ (lbs)
Universal Force Generator | Version 1.15.4 | Contact: RisaUFG@tepgroup.net
CLL01580 (12844670)
Analysis By:SVW 11/8/2025
Checked By:SMS 11/8/2025
Member Forces are Calculated in Accordance with TIA-222-H
Member Name Wind Proj. (in) Length (in)Shape θ (°)Perimeter (in)
FF-BH1 3.500 156.00 Round 90.00 11.00
FF-BH2 3.500 156.00 Round -30.00
FF-BH3 3.500 156.00 Round 30.00
FF-TH1 3.500 156.00 Round 90.00
FF-TH2 3.500 156.00 Round -30.00
FF-TH3 3.500 156.00 Round 30.00
MP-1 2.375 120.00 Round
MP-3 2.375 120.00 Round
MP-4 2.375 96.00 Round
MP-5 2.375 120.00 Round
MP-7 2.375 120.00 Round
MP-8 2.375 96.00 Round
MP-9 2.375 120.00 Round
MP-11 2.375 120.00 Round
MP-12 2.375 96.00 Round
RRU-1 2.375 48.00 Round
RRU-2 2.375 48.00 Round
RRU-3 2.375 48.00 Round
MP-2 2.875 120.00 Round
MP-6 2.875 120.00 Round
MP-10 2.875 120.00 Round
SA-1 2.375 68.85 Round 30.00
SA-2 2.375 68.85 Round 90.00
SA-3 2.375 68.85 Round -30.00
SA1-BH 4.000 36.00 Flat 0.00
SA1-TH 4.000 36.00 Flat 0.00
SA2-BH 4.000 36.00 Flat 60.00
SA2-TH 4.000 36.00 Flat 60.00
SA3-BH 4.000 36.00 Flat -60.00
SA3-TH 4.000 36.00 Flat -60.00
SA1-BV 4.500 18.00 Round
SA1-TV 4.500 18.00 Round
SA2-BV 4.500 18.00 Round
SA2-TV 4.500 18.00 Round
SA3-BV 4.500 18.00 Round
SA3-TV 4.500 18.00 Round
353924.1184084
Universal Force Generator | Version 1.15.4 | Contact: RisaUFG@tepgroup.net
CLL01580 (12844670)
TEP No.
Analysis By:
Checked By:
Manufacturer CFD data is curve-fit for analysis using a proprietary TEP method to ensure consideration of worst-case wind direction in 15/30° increments.
The data below is a summary of provided EPA values and derived Wind Forces for applicable AT&T Equipment incorporating TEP Standards.
Make Model 0°10°20°30°40°50°60°70°80°90°100°110°120°130°140°150°160°170°180°
COMMSCOPE NNH4-65C-R6-V3 EPA (ft-2):9.65 11.88 12.5 11.81 10.89 9.64 7.3 6.05 4.39 3.35 3.77 7.57 9.18 11.09 11.06 11.46 11.36 10.57 7.94
Force (Lbs):
ERICSSON AIR 6419 B77D/G EPA (ft-2):
Force (Lbs):
Wind Direction
SVW 11/08/2025
SMS 11/08/2025
Universal Force Generator | Version 1.15.4 | Contact: RisaUFG@tepgroup.net
CLL01580 (12844670)
TEP No.
Analysis By:SVW 11/8/2025
Checked By:SMS 11/8/2025
Moment Bolt Group - Collar Connection
Code Revisions:
Bolt Type:
Bolt Size:0.625 in
# Bolts:4 #VALUE! #VALUE!
Plate Width:8.00 in Bolt Capacity=20.0%PASS
Plate Height:8.00 in Plate Capacity=14.3%PASS
Bolt H Gap:6.00 in
Bolt V Gap:6.00 in
Plate T:0.750 in
Slip Member Ø:N/A in
Bolt Grade:A325N
Fybolt:92.0 ksi Member Shape:Flat
Fubolt:120.0 ksi Plate Fy:36.0 ksi
r:4.2 in Plate Fu:58.0 ksi
J:72.0 in4/in2 Member Height:4.0 in
Abolt:0.3 in2 Member Width:4.0 in
Abolt, Net Tensile:0.2 in2
Pretension:19.0 kips
Capacities:
353924.1184084
ANSI/TIA-222-H
Headed Bolts
Connection Inputs:
Member Properties:Bolt Properties:
November 8, 2025
T-Arm Mount Analysis Fairview Business Park (12844670)
TEP Project Number 353924.1184084 Page 6
APPENDIX C
SUPPLEMENTAL DRAWINGS
PARTS LIST
NET WT.UNIT WT.LENGTHPART DESCRIPTIONPART NO.QTYITEM
8.158.15 4-1/2" FORTRESS CROSSOVER PLATEX-SCX4-FR11
9.452.368 1/8 in1/2" THICK, 5-3/4" CNTER TO CENTER CLAMP HALFDCP42
5.640.707 in5/8'' x 7" HDG HEX BOLT GR5 FULL THREADG580783
1.130.071/8 in5/8" HDG USS FLATWASHERG58FW164
0.210.03 5/8" HDG LOCKWASHERG58LW85
1.040.13 5/8'' HDG HEAVY 2H HEX NUTG58NUT86
DESCRIPTION
DRAWING USAGE CHECKED BY
ENG. APPROVALDRAWN BY
DWG. NO.
CPD NO.
CMFL 1 OF 1
9/14/2021 FCX45-U
HEAVY-DUTY UNIVERSAL CROSSOVER KIT
CUSTOMER FCX45-U
CLASS SUB
PART NO.
87 02
PAGE
TOLERANCES ON DIMENSIONS, UNLESS OTHERWISE NOTED ARE:
SAWED, SHEARED AND GAS CUT EDGES (± 0.030")
DRILLED AND GAS CUT HOLES (± 0.030") - NO CONING OF HOLES
LASER CUT EDGES AND HOLES (± 0.010") - NO CONING OF HOLES
BENDS ARE ± 1/2 DEGREE
ALL OTHER MACHINING (± 0.030")
ALL OTHER ASSEMBLY (± 0.060")
TOLERANCE NOTES
PROPRIETARY NOTE:
THE DATA AND TECHNIQUES CONTAINED IN THIS DRAWING ARE PROPRIETARY INFORMATION OF VALMONT
INDUSTRIES AND CONSIDERED A TRADE SECRET. ANY USE OR DISCLOSURE WITHOUT THE CONSENT OF
VALMONT INDUSTRIES IS STRICTLY PROHIBITED.
Engineering
Support Team:
1-888-753-7446
valmont
Locations:
New York, NY
Atlanta, GA
Los Angeles, CA
Plymouth, IN
Salem, OR
Dallas, TX
TOTAL WT. # 25.62
HOT DIP GALVANIZED.
FINISH:
2
2
3 4x2 5 6
34x256
1
4-1/2"Ø MAX.
4-1/2"Ø MAX.
SitePro1.com 888-438-7761
cr
e
a
t
e
d
o
n
:
0
3
/
0
9
/
2
0
2
3
Pxxx: Bulk Pipe
Features:
• Factory cut end, hot-dip galvanized pipe
Construction:
• ASTM A53 Grade B
• Schedule 40 or Schedule 80
Design Criteria:
• ASTM A53 Grade B (Yield Fy = 35 ksi [240 MPa]/
Tensile Fu = 60 ksi [415 MPa])
• Hot dip galvanized in accordance with ASTM A123 requirements
Part #Length OD x Length (in)
Schedule 40
P260 5’-0”2-3/8” x 60”
P263 5’-3”2-3/8” x 63”
P272 6’-0”2-3/8” x 72”
P284 7’-0”2-3/8” x 84”
P296 8’-0”2-3/8” x 96”
P2108 9’-0”2-3/8” x 108”
P2120 10’-0”2-3/8” x 120”
P2126 10’-6”2-3/8” x 126”
P2150 12’-6”2-3/8” x 150”
P2174 14’-6”2-3/8” x 174”
P2252 21’-0”2-3/8” x 252”
P3072 6’-0”2-7/8” x 72”
P3084 7’-0”2-7/8” x 84”
P3096 8’-0”2-7/8” x 96”
P30108 9’-0”2-7/8” x 108”
P30120 10'-0"2-7/8" x 120"
P30126 10’-6”2-7/8” x 126”
P30150 12’-6”2-7/8” x 150”
P30174 14’-6”2-7/8” x 174”
P30252 21’-0”2-7/8” x 252”
P360 5’-0”3-1/2” x 60”
P372 6’-0”3-1/2” x 72”
P384 7’-0”3-1/2” x 84”
P396 8’-0”3-1/2” x 96”
P3150 12’-6”3-1/2” x 150”
P3160 13’-4”3-1/2” x 160”
P3174 14’-6”3-1/2” x 174”
P3216 18’-0”3-1/2” x 216”
P3252 21’-0”3-1/2” x 252”
P472 6’-0”4-1/2” x 72”
P4126 10’-6”4-1/2” x 126”
P4252 21’-0”4-1/2” x 252”
Part #Length OD x Length (in)
Schedule 80
P2252-80 21’2-1/2” x 252”
P30126-80 10’-6”2-7/8” x 126”
P30252-80 21’2-7/8” x 252”
P3252-80 21’3-1/2” x 252”
YES NO
INSTRUCTIONS:
ORAN GE COUNTY FI RE AUTHORI TY
Plan Submittal Criteria
COMMERCIAL projects, MULTIFAMILY RESIDENTIAL projects
and RESIDENTIAL TRACT developments
· Fill in the project/business address and provide a brief description of the scope of work and type of business operation that will take place.
· Answer questions 1 through 10, read and initial items 11 and 12, then complete and sign the certification section.
· If you answer: - “YES” to any part of questions 1 through 10, submit the type of plan indicated in italics to OCFA.
· In some cases, other plan types not indicated herein may also be necessary depending on specific conditions or operations.
· Visit www.ocfa.org for submittal information and locations. If you need assistance in filling out this form or have questions regarding
requirements for review, please contact OCFA at 714-573-6108 or visit us at 1 Fire Authority Road, Irvine, CA 92602.
Address Suite City
Project Scope/Business Description
1. Construction of a new building, a new story, or increase the footprint of an existing building? Changes to roadways,
curbs, or drive aisles? Addition, relocation, or modification of fire hydrants or fences/gates? Construction within
300 feet of an active or proposed oil well? Fire Master Plan (PR145)
2. Property is adjacent to a wildland area or non-irrigated native vegetation?
Fire Master Plan (PR145); a Fuel Modification Plan may also be required. (PR120, PR124)
3. Located in or < 100’ from a Division of Oil, Gas, and Geothermal Resources (DOGGR) field boundary, < 300’ from
an oil/gas seep, or < 1000’ from a landfill? Methane Work Plan. (PR170)
4. Installation/modification/repair of underground piping, backflow preventers, or fire department connections serving
private fire hydrant/sprinkler/standpipe systems? Underground Plan. (PR470, PR475)
5. Drinking/dining/recreation/meetings/training/religious functions or other gatherings in a room > 750 sq.ft. (> 1,000
sq.ft. for training/adulteducation) or > 49 people? Healthcare/outpatient services for > 5 people who may be unable
to immediately evacuate without assistance? Education for children (academic tutoring for ages 5+ is exempt unless
classified as an E occupancy by the Building Official)? Adult/child daycare? 24-hour care/supervision? Incarceration
or restraint? Hotel/apartment or residential facility with 3+ units and 3+ stories (3-story townhouses/rowhouses
where an independent direct exit to grade is provided for dwelling are exempt)? Congregate housing/dormitories
with 17+ people? High-rise structure (55+ feet to highest occupied floor level)? Architectural Plan (PR200-PR285)
6. Installation/modification of locks delaying or preventing occupants from leaving a space or requiring use of a card,
button, or similar action to open a door in the direction of exit travel? Architectural, Sprinkler, and/or Alarm Plan
depending on the occupancy and type of device installed (PR200-PR280, PR420-PR425, PR500-PR520)
7. Installation/modification/use of spray booths; dust collection; dry cleaning; industrial ovens/drying equipment;
industrial/commercial refrigeration systems; compressed gasses; tanks for cryogenic or flammable/combustible
liquids; vapor recovery; smoke control; battery back-up/charging systems (> 50 gal. electrolyte, > 1,000 lb. lithium
ion); welding/brazing/soldering, open flame torches, cutting/grinding; or other similar operations?
Special Equipment Plan (PR315, PR340-PR382)
8. Storage/use/research with flammable/combustible liquids or other chemicals? Motor vehicle/aircraft
maintenance/repair? Cabinetry/woodworking/finishing facility? Chem Class & floor plan (full architectural plan if
H occupancy); Special Equipment Plans may be necessary. (PR315-PR360, PR232-PR240)
9. Storage or merchandizing areas in excess of 500 sq. ft. where items are located higher than 12’ (6’ for high-hazard
commodities, plastic, rubber, foam, etc.)? High-piled Storage Plan (PR330)
10. Cooking under a Type I commercial hood; installation or modification of a fire extinguishing system located in a
commercial cooking hood? Hood & Duct Extinguishing System, not just the hood mechanical plan. (PR335)
Initial each of the following two items indicating that you have read and understand the statement:
11. *Sprinklers/Alarms: Consult Building/Fire Codes and ordinances to determine sprinkler/alarm requirements; if a system is
required, plans shall be submitted for OCFA review. Existing buildings undergoing remodel must be evaluated by a licensed
Initials contractor to determine if modification is needed; if so, contractor shall submit plans prior to making modifications.
12. Fire Hazard Severity Zone: Consult maps available at building department or on OCFA website to determine if your site is located
in a FHSZ. Buildings in a FHSZ may be subject to special construction requirements detailed in CBC Chapter 7A or CRC R327—
Initials the building department will determine specific requirements.
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name Signature
Phone Number ( ) Date / /
Building Department: If you have verified that all of the questions have been answered accurately as “NO”, and the project does not otherwise require OCFA
review of sprinkler or alarm plans*, then you may accept this signed form as a written release that OCFA review is not required. Should you still require that the
applicant have plans approved by OCFA, please initial here or attach an OCFA referral form and have the applicant submit the form along with the
appropriate plans and fees for OCFA review. 10-08-14 EE
COM
O R A N G E C O U N T Y F I R E A U T H O R I T Y
Plan Referral Form
Required for OCFA to review plans upon the request of the Building Department when
the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”.
City / County Official Requesting Review:
City / County Reference #: Date: __________________________________
City / County: _____________________________________ E-Mail: __________________________________
Contact Name: _____________________________________ Phone #: _________________________________
Title: _____________________________________
** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. **
Reason(s) for Review:
Please describe why OCFA Plan Review is or may be required by the City/County :
OCFA COMMENTS:
No further action required on this specific plan type, based
on information provided on: ____/______/______.
Project to be taken in for OCFA Review.
Other:
Name: _________________________________________
Contact #: ______________________________________ Date: _________________________________
OCFA Authorization
Updated: 06/02/2020 rs
PLANS PREPARED FOR:
PROJECT INFORMATION:
SHEET TITLE:
DATE ISSUED FOR:REV
0 11-18-25 STRUCTURAL ANALYSIS
SHEET NUMBER:
TEP #:353924.1184090
REVISION:
November 18, 2025
SEAL:
PLANS PREPARED BY:
TOWER ENGINEERING PROFESSIONALS
326 TRYON ROAD
RALEIGH, NC 27603
OFFICE: (919) 661-6351
www.tepgroup.net
DRAWN BY:
0
CHECKED BY:
2500-2520 S. FAIRVIEW
STREET, SANTA ANA, CA 92704
(ORANGE COUNTY)
ALD
SMS
SEISMIC DESIGN DATA - RISK CATEGORY:II
- SEISMIC IMPORTANCE FACTOR, Ie:1.0
- MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:Ss = 1.305
S1 = 0.468
- SITE CLASS:D
- DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:Sds = 1.044
Sd1 = 0.572
- SEISMIC DESIGN CATEGORY:D
- DESIGN BASE SHEAR:8.009 kips
- RESPONSE MODIFICATION COEFFICIENT, R:1.5
- ANALYSIS METHOD:EQUIVALENT
LATERAL FORCE
PROCEDURE
WIND DESIGN DATA - RISK CATEGORY:II
- EXPOSURE CATEGORY:B
- TOPOGRAPHIC CATEGORY:1
- ULTIMATE WIND SPEED (3-SECOND GUST):95 mph
2500 & 2520 3/4 S Fairview St., Santa Ana, Orange County, CA 92704
TEP is a family of companies licensed to provide different services in different jurisdictions. Depending on the jurisdiction,
professional engineering and land surveying services are provided by TEP OpCo LLC, a Delaware limited liability company,
TEP Engineering, PLLC, a North Carolina professional limited liability company, or M&H Engineering, PLLC, a New York professional limited liability company. General contractor services
are provided by TEPDB OpCo LLC, a Delaware limited liability company. We acquire the requisite licenses in each state. Additional information can be obtained from the company.
November 18, 2025
Jon Maxwell
M Squared Wireless 326 Tryon Road
1387 Calle Avanzado Raleigh, NC 27603
San Clemente, CA 926734 (919) 661-6351
(949) 246-1809 SM-SA@tepgroup.net
Subject: Structural Analysis Report
Carrier Designation: AT&T Mobility Reconfiguration
Carrier Site Number: WSLOS0068803
Carrier Site Name: Fairview Business Park
FA Number: 12844670
Client Designation: Site Number: CLL01580
Site Name: Fairview Business Park
Engineering Firm Designation: TEP Project Number: 353924.1184090
Site Data: 2500-2520 S. Fairview Street, Santa Ana, Orange County, CA 92704
Latitude 33° 42' 48.41'', Longitude -117° 54' 35.49''
58.0 ± Foot - Monoeucalyptus
Dear Jon Maxwell,
TEP is pleased to submit this “Structural Analysis Report” to determine the structural integrity of the above-
mentioned tower.
The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we have
determined the stress level for the tower and foundation structure, under the following load case, to be:
LC1: Existing + Proposed + Reserved Loading Sufficient Capacity
Note: See Table 1 for the existing, proposed, and reserved loading
*Percent capacity based on design reaction comparison as allowed in TIA-222-H, Section 15
The analysis has been performed in accordance with the ANSI/TIA-222-H Structural Standard for Antenna
Supporting Structures, Antennas, and Small Wind Turbine Support Structures and the 2022 California Building
Code
All modifications and equipment proposed in this report shall be installed in accordance with the appurtenances
listed in Table 1 for the determined available structural capacity to be effective.
We at TEP appreciate the opportunity of providing our continuing professional services to you and M Squared
Wireless. If you have any questions or need further assistance on this or any other projects please give us a call.
Structural analysis prepared by: PG / SMS
Respectfully submitted by:
Adam M. Amortnont, P.E., S.E.
Structure Capacity Foundation Capacity
28.5% 33.3%*
2500 & 2520 3/4 S Fairview St., Santa Ana, Orange County, CA 92704
November 18, 2025
58.0 -ft Monoeucalyptus Structural Analysis Fairview Business Park (CLL01580)
TEP Project Number 353924.1184090 Page 2
TABLE OF CONTENTS
1) INTRODUCTION
2) ANALYSIS CRITERIA
Table 1 - Existing, Proposed, and Reserved Antenna and Cable Information
3) ANALYSIS PROCEDURE
Table 2 - Documents Provided
3.1) Analysis Method
3.2) Assumptions
4) ANALYSIS RESULTS
Table 3 - Section Capacity (Summary)
Table 4 - Tower Component Stresses vs. Capacity
4.1) Recommendations
5) APPENDIX A
tnxTower Output
6) APPENDIX B
Additional Calculations
7) APPENDIX C
Seismic Calculations
November 18, 2025
58.0 -ft Monoeucalyptus Structural Analysis Fairview Business Park (CLL01580)
TEP Project Number 353924.1184090 Page 3
1) INTRODUCTION
The tower is a 58.0 ± Foot Monoeucalyptus designed by Larson in July of 2019. The tower was originally designed
for a 3-second gust wind speed of 110 mph and 60 mph under service loads using Structure Class II, Exposure
Category C, and Topographic Category 1 per ANSI/TIA-222-G. All information provided to TEP was assumed to
be accurate and complete.
2) ANALYSIS CRITERIA
TIA-222 Revision: ANSI/TIA-222-H
Type of Analysis: Feasibility Study
Risk Category: II
Wind Speed: 95 mph (Ultimate)
Exposure Category: B
Topographic Procedure: Method 1 (Kzt = 1.0)
Seismic Design Category: D
Seismic Ss: 1.305
Seismic S1: 0.468
Service Wind Speed: 60 mph
Table 1 - Existing, Proposed, and Reserved Antenna and Cable Information
Existing/
Proposed/
Reserved
Mount
Level
(ft)
Ant
CL
(ft)
Qty Antenna Model Mount
Type
Qty
Coax
Coax
Size
Coax
Location
Owner/
Tenant
Proposed 55.0 57.7 3 Ericsson AIR6419 B77G
(3) T-Arm
Mounts
- - - AT&T
Existing 55.0 55.0
3 Kathrein 80010966
9
3
13/16”
3/8" Inside AT&T
3 Commscope NNH4-65C-R6-V3
3 Quintel QS8658-3E
3 Ericsson 8843 B2/B66A
3 Ericsson 4478 B14
3 Ericsson RRUS-32 B30
3 Ericsson RRUS-E2 B29
3 Ericsson 4449 B5/B12
3 Raycap DC9-48-60-24-8C-EV
53.0 3 Ericsson AIR6449 B77D
November 18, 2025
58.0 -ft Monoeucalyptus Structural Analysis Fairview Business Park (CLL01580)
TEP Project Number 353924.1184090 Page 4
3) ANALYSIS PROCEDURE
Table 2 - Documents Provided
Document Remarks Source
Tower and Foundation
Design
Larson, dated July 17, 2019
Job No. UR19272 M Squared
Previous Structural
Analysis
GPD, dated September 28, 2021
Project No. 2021723.21.195375.01 M Squared
Construction Drawings M Square Wireless, dated November 4, 2025
Project No. 12844670 M Squared
Mount Analysis TEP, dated November 8, 2025
TEP No. 353924.1184084 TEP
RF Data Sheet AT&T RFDS-34994, dated September 26, 2025 M Squared
Correspondence Correspondence in reference to the existing, proposed, and reserved
loading. M Squared
3.1) Analysis Method
tnxTower (version 8.3.1.2), a commercially available analysis software package, was used to create a
three-dimensional model of the tower and calculate member stresses for various loading cases.
Selected output from the analysis is included in Appendix A.
3.2) Analysis Assumptions
1) The tower and foundation were built and maintained in accordance with the manufacturer’s
specification.
2) The configuration of existing antennas, transmission cables, mounts and other appurtenances
are as specified in the previous structural analysis.
3) Unless specified by the client or tower mapping, the location of the existing and proposed coax is
assumed by TEP and listed in Table 1.
4) All tower components are in sufficient condition to carry their full design capacity.
5) Serviceability with respect to antenna twist, tilt, roll, or lateral translation, is not checked and is
left to the carrier or tower owner to ensure conformance.
All antenna mounts and mounting hardware are structurally sufficient to carry the full design
capacity requirements of appurtenance wind area and weight as provided by the original
manufacturer specifications. It is the carrier’s responsibility to ensure compliance to the structural
limitations of the existing and/or proposed antenna mounts. TEP did not perform a site visit to
verify the size, condition or capacity of the antenna mounts and did not analyze antennas
supporting mounts as part of this structural analysis report.
This analysis may be affected if any assumptions are not valid or have been made in error. TEP should
be notified to determine the effect on the structural integrity of the tower.
November 18, 2025
58.0 -ft Monoeucalyptus Structural Analysis Fairview Business Park (CLL01580)
TEP Project Number 353924.1184090 Page 5
4) ANALYSIS RESULTS
Table 3 - Section Capacity (Summary)
Section No. Elevation (ft) Component Type Size Critical
Element P (K) ΦPallow (K) %
Capacity Pass / Fail
L1 58 - 16 Pole TP35.15x18x0.2188 1 -15.04 1414.00 25.4 Pass
L2 16 - 1 Pole TP40.837x32.9363x0.25 2 -18.05 1978.24 28.5 Pass
Summary
Pole (L2) 28.5 Pass
RATING = 28.5 Pass
Table 4 - Tower Component Stresses vs. Capacity
Notes Component Elevation
(ft) % Capacity Pass / Fail
1,2,3 Anchor Rods - 26.3 Pass
1,2 Base Plate - 20.1 Pass
1,2,4,5 Base Foundation
(Design Reaction Comparison) - 33.3 Pass
Structure Rating (max from all components) = 33.3%
Notes:
1) Rating per TIA-222-H, Section 15.5
2) See additional documentation in “Appendix B - Additional Calculations” for calculations supporting the % capacity listed.
3) Seismic controls capacity.
4) Foundation capacity is determined by comparing analysis reactions to original design reactions. Design loads were
multiplied by 1.35 for comparison as allowed by TIA-222-H, Section 15.6.2.
5) Although the axial and shear capacity are at 46.3% and 41.1%, respectively, the moment reaction in the governing criteria
for a monopole drilled shaft foundation. Therefore, the overall capacity for this foundation is 33.3%.
4.1) Recommendations
1) If the load differs from that described in Table 1 of this report or the provisions of this analysis are
found to be invalid, another structural analysis should be performed.
2) The tower and its foundation have sufficient capacity to carry the proposed load configuration.
No modifications are required at this time.
3) TEP did not have sufficient information to perform a foundation analysis. If a foundation analysis
is required, please provide TEP with a geotechnical report for this site to determine the
substructure capacity. If this information is not available, TEP recommends a geotechnical
investigation.
November 18, 2025
58.0 -ft Monoeucalyptus Structural Analysis Fairview Business Park (CLL01580)
TEP Project Number 353924.1184090 Page 6
APPENDIX A
TNX TOWER OUTPUT
TEP
326 Tryon Road
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Job: Fairview Business Park (CLL01580)
Project: TEP No. 353924.1184090
Client: M Squared Wireless Drawn by: adare App'd:
Code: TIA-222-H Date: 11/18/25 Scale: NTS
Path:
G:\Shared drives\350001 - 400000\353924\P-499575_L-1184090_CLL01580_FAIRVIEW BUSINESS PARK_ Structural Analysis\TnxTower\Wind and Seismic\FAIRVIEW BUSINESS PARK (CLL01580) CCISeismic 5.0.2 Wind And Seismic Analysis.eri
Dwg No. E-1
58.0 ft
16.0 ft
1.0 ft
REACTIONS - 95 mph WIND
TORQUE 0 kip-ft
12 K
SHEAR
482 kip-ft
MOMENT
18 K
AXIAL
SEISMIC
8 K
SHEAR
369 kip-ft
MOMENT
21 K
AXIAL
ARE FACTORED
ALL REACTIONS
S
e
c
t
i
o
n
1
2
L
e
n
g
t
h
(
f
t
)
4
2
.
0
0
19
.
3
5
N
u
m
b
e
r
o
f
S
i
d
e
s
1
8
18
T
h
i
c
k
n
e
s
s
(
i
n
)
0
.
2
1
8
8
0.
2
5
0
0
S
o
c
k
e
t
L
e
n
g
t
h
(
f
t
)
4
.
3
5
T
o
p
D
i
a
(
i
n
)
1
8
.
0
0
0
0
32
.
9
3
6
3
B
o
t
D
i
a
(
i
n
)
3
5
.
1
5
0
0
40
.
8
3
7
0
G
r
a
d
e
A
5
7
2
-
6
5
W
e
i
g
h
t
(
K
)
2
.
6
1.
9
4.
5
MATERIAL STRENGTH
GRADE GRADEFy FyFu Fu
A572-65 65 ksi 80 ksi
TOWER DESIGN NOTES
1. Tower is located in Orange County, California.
2. Tower designed for Exposure B to the TIA-222-H Standard.
3. Tower designed for a 95 mph basic wind in accordance with the TIA-222-H Standard.
4. Deflections are based upon a 60 mph wind.
5. Tower Risk Category II.
6. Topographic Category 1 with Crest Height of 0.00 ft
7. CCISeismic Note: Seismic loads generated by CCISeismic 5.0.2
8. CCISeismic Note: Seismic calculations are in accordance with TIA-222-H-1
9. TOWER RATING: 28.5%
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
1 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Tower Input Data
The tower is a monopole.
This tower is designed using the TIA-222-H standard.
The following design criteria apply:
Tower is located in Orange County, California.
Tower base elevation above sea level: 46.00 ft.
Basic wind speed of 95 mph.
Risk Category II.
Exposure Category B.
Simplified Topographic Factor Procedure for wind speed-up calculations is used.
Topographic Category: 1.
Crest Height: 0.00 ft.
Deflections calculated using a wind speed of 60 mph.
CCISeismic Note: Seismic loads generated by CCISeismic 5.0.2.
CCISeismic Note: Seismic calculations are in accordance with TIA-222-H-1.
Non-linear (P-delta) analysis was used.
Pressures are calculated at each section.
Stress ratio used in pole design is 1.
Tower analysis based on target reliabilities in accordance with Annex S.
Load Modification Factors used: Kes(Fw) = 0.95, Kes(Ev and Eh) = 1.0.
Maximum demand-capacity ratio is: 1.05.
Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered.
Options
Consider Moments - Legs Assume Legs Pinned Calculate Redundant Bracing Forces
Consider Moments - Horizontals √ Assume Rigid Index Plate Ignore Redundant Members in FEA
Consider Moments - Diagonals √ Use Clear Spans For Wind Area SR Leg Bolts Resist Compression
Use Moment Magnification Use Clear Spans For KL/r All Leg Panels Have Same Allowable
√ Use Code Stress Ratios Retension Guys To Initial Tension Offset Girt At Foundation
√ Use Code Safety Factors - Guys √ Bypass Mast Stability Checks √ Consider Feed Line Torque
Escalate Ice √ Use Azimuth Dish Coefficients Include Angle Block Shear Check
Always Use Max Kz √ Project Wind Area of Appurtenances Use TIA-222-H Bracing Resist. Exemption
Kz In Exposure D Hurricane Region √ Alternative Appurt. EPA Calculation Use TIA-222-H Tension Splice Exemption
Include Bolts In Member Capacity Autocalc Torque Arm Areas Poles
Leg Bolts Are At Top Of Section Add IBC .6D+W Combination √ Include Shear-Torsion Interaction
Secondary Horizontal Braces Leg √ Sort Capacity Reports By Component Always Use Sub-Critical Flow
Use Diamond Inner Bracing (4 Sided) Triangulate Diamond Inner Bracing Use Top Mounted Sockets
SR Members Have Cut Ends Treat Feed Line Bundles As Cylinder √ Pole Without Linear Attachments
SR Members Are Concentric Ignore KL/ry For 60 Deg. Angle Legs Pole With Shroud Or No Appurtenances
Distribute Leg Loads As Uniform Use ASCE 10 X-Brace Ly Rules Outside and Inside Corner Radii Are Known
Use Special Wind Profile
Tapered Pole Section Geometry
Section Elevation
ft
Section
Length
ft
Splice
Length
ft
Number
of
Sides
Top
Diameter
in
Bottom
Diameter
in
Wall
Thickness
in
Bend
Radius
in
Pole Grade
L1 58.00-16.00 42.00 4.35 18 18.0000 35.1500 0.2188 0.8750 A572-65
(65 ksi)
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
2 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Section Elevation
ft
Section
Length
ft
Splice
Length
ft
Number
of
Sides
Top
Diameter
in
Bottom
Diameter
in
Wall
Thickness
in
Bend
Radius
in
Pole Grade
L2 16.00-1.00 19.35 18 32.9363 40.8370 0.2500 1.0000 A572-65
(65 ksi)
Tapered Pole Properties
Section Tip Dia.
in
Area
in2
I
in4
r
in
C
in
I/C
in3
J
in4
It/Q
in2
w
in
w/t
L1 18.2439 12.3457 493.1503 6.3123 9.1440 53.9316 986.9495 6.1740 2.7830 12.722
35.6585 24.2532 3738.8222 12.4006 17.8562 209.3851 7482.5641 12.1289 5.8014 26.521
L2 35.2093 25.9365 3500.8998 11.6036 16.7316 209.2386 7006.4061 12.9707 5.3568 21.427
41.4284 32.2058 6702.6298 14.4084 20.7452 323.0931 13414.0792 16.1060 6.7473 26.989
Tower
Elevation
ft
Gusset
Area
(per face)
ft2
Gusset
Thickness
in
Gusset Grade Adjust. Factor
Af
Adjust.
Factor
Ar
Weight Mult.
Double Angle
Stitch Bolt
Spacing
Diagonals
in
Double Angle
Stitch Bolt
Spacing
Horizontals
in
Double Angle
Stitch Bolt
Spacing
Redundants
in
L1 58.00-16.00 1 1 1
L2 16.00-1.00 1 1 1
Feed Line/Linear Appurtenances - Entered As Round Or Flat
Description Face
or
Leg
Allow
Shield
Exclude
From
Torque
Calculation
Component
Type
Placement
ft
Total
Number
Number
Per Row
Clear
Spacing
in
Width or
Diameter
in
Perimeter
in
Weight
plf
**
Feed Line/Linear Appurtenances - Entered As Area
Description Face
or
Leg
Allow
Shield
Exclude
From
Torque
Calculation
Component
Type
Placement
ft
Total
Number
CAAA
ft2/ft
Weight
plf
***
PWRT-608-S(
13/16'')
C No No Inside Pole 55.00 - 1.00 9 No Ice 0.00 0.62
3/8'' Fiber Cable C No No Inside Pole 55.00 - 1.00 3 No Ice 0.00 0.07
**
Feed Line/Linear Appurtenances Section Areas
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
3 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Tower
Section
Tower
Elevation
ft
Face AR
ft2
AF
ft2
CAAA
In Face
ft2
CAAA
Out Face
ft2
Weight
K
L1 58.00-16.00 A
B
C
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.00
0.00
0.23
L2 16.00-1.00 A
B
C
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.00
0.00
0.09
Feed Line Center of Pressure
Section Elevation
ft
CPX
in
CPZ
in
CPX
Ice
in
CPZ
Ice
in
L1 58.00-16.00 0.0000 0.0000 0.0000 0.0000
L2 16.00-1.00 0.0000 0.0000 0.0000 0.0000
Note: For pole sections, center of pressure calculations do not consider feed line shielding.
User Defined Loads - Seismic
Description Elevation
ft
Offset
From
Centroid
ft
Azimuth
Angle
°
Ev
K
Ehx
K
Ehz
K
Eh
K
CCISeismic Tower Section 1 - 1 57.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic Tower Section 1 - 2 51.00 0.00 0.0000 0.10 0.00 0.00 0.37
CCISeismic Tower Section 1 - 3 41.00 0.00 0.0000 0.12 0.00 0.00 0.33
CCISeismic Tower Section 1 - 4 31.00 0.00 0.0000 0.14 0.00 0.00 0.27
CCISeismic Tower Section 1 - 5 21.00 0.00 0.0000 0.16 0.00 0.00 0.18
CCISeismic Tower Section 2 - 1 15.68 0.00 0.0000 0.18 0.00 0.00 0.14
CCISeismic Tower Section 2 - 2 6.00 0.00 0.0000 0.22 0.00 0.00 0.04
CCISeismic Pine branch 54.00 0.00 0.0000 0.15 0.00 0.00 0.60
CCISeismic Pine branch 45.00 0.00 0.0000 0.30 0.00 0.00 0.92
CCISeismic Pine branch 35.00 0.00 0.0000 0.32 0.00 0.00 0.71
CCISeismic Pine branch 25.00 0.00 0.0000 0.42 0.00 0.00 0.59
CCISeismic ericsson AIR 6419
B77G w/ Mount Pipe
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic ericsson AIR 6419
B77G w/ Mount Pipe
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic ericsson AIR 6419
B77G w/ Mount Pipe
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic ericsson AIR 6449
B77D
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic ericsson AIR 6449
B77D
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic ericsson AIR 6449
B77D
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic kathrein 80010966
w/ Mount Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.12
CCISeismic kathrein 80010966
w/ Mount Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.12
CCISeismic kathrein 80010966
w/ Mount Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.12
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
4 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Description Elevation
ft
Offset
From
Centroid
ft
Azimuth
Angle
°
Ev
K
Ehx
K
Ehz
K
Eh
K
CCISeismic commscope
NNH4-65C-R6-V3 w/ Mount
Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.11
CCISeismic commscope
NNH4-65C-R6-V3 w/ Mount
Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.11
CCISeismic commscope
NNH4-65C-R6-V3 w/ Mount
Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.11
CCISeismic quintel technology
QS8658-3e w/ Mount Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.11
CCISeismic quintel technology
QS8658-3e w/ Mount Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.11
CCISeismic quintel technology
QS8658-3e w/ Mount Pipe
55.00 0.00 0.0000 0.03 0.00 0.00 0.11
CCISeismic ericsson RADIO
4478 B14
55.00 0.00 0.0000 0.01 0.00 0.00 0.05
CCISeismic ericsson RADIO
4478 B14
55.00 0.00 0.0000 0.01 0.00 0.00 0.05
CCISeismic ericsson RADIO
4478 B14
55.00 0.00 0.0000 0.01 0.00 0.00 0.05
CCISeismic ericsson RRUS-32
B30
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic ericsson RRUS-32
B30
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic ericsson RRUS-32
B30
55.00 0.00 0.0000 0.02 0.00 0.00 0.07
CCISeismic ericsson RRUS E2
B29
55.00 0.00 0.0000 0.01 0.00 0.00 0.04
CCISeismic ericsson RRUS E2
B29
55.00 0.00 0.0000 0.01 0.00 0.00 0.04
CCISeismic ericsson RRUS E2
B29
55.00 0.00 0.0000 0.01 0.00 0.00 0.04
CCISeismic ericsson RRUS
4449 B5/B12
55.00 0.00 0.0000 0.01 0.00 0.00 0.06
CCISeismic ericsson RRUS
4449 B5/B12
55.00 0.00 0.0000 0.01 0.00 0.00 0.06
CCISeismic ericsson RRUS
4449 B5/B12
55.00 0.00 0.0000 0.01 0.00 0.00 0.06
CCISeismic ericsson RRUS
8843 B2/B66A
55.00 0.00 0.0000 0.01 0.00 0.00 0.06
CCISeismic ericsson RRUS
8843 B2/B66A
55.00 0.00 0.0000 0.01 0.00 0.00 0.06
CCISeismic ericsson RRUS
8843 B2/B66A
55.00 0.00 0.0000 0.01 0.00 0.00 0.06
CCISeismic raycap
DC9-48-60-24-8C-EV
55.00 0.00 0.0000 0.01 0.00 0.00 0.02
CCISeismic raycap
DC9-48-60-24-8C-EV
55.00 0.00 0.0000 0.01 0.00 0.00 0.02
CCISeismic raycap
DC9-48-60-24-8C-EV
55.00 0.00 0.0000 0.01 0.00 0.00 0.02
CCISeismic mounts 2.4'' Dia x
4-ft Mount Pipe
55.00 0.00 0.0000 0.00 0.00 0.00 0.01
CCISeismic mounts 2.4'' Dia x
4-ft Mount Pipe
55.00 0.00 0.0000 0.00 0.00 0.00 0.01
CCISeismic mounts 2.4'' Dia x
4-ft Mount Pipe
55.00 0.00 0.0000 0.00 0.00 0.00 0.01
CCISeismic stabilizer 2.4'' x 6'
Stabilizer
55.00 0.00 0.0000 0.00 0.00 0.00 0.02
CCISeismic stabilizer 2.4'' x 6' 55.00 0.00 0.0000 0.00 0.00 0.00 0.02
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
5 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Description Elevation
ft
Offset
From
Centroid
ft
Azimuth
Angle
°
Ev
K
Ehx
K
Ehz
K
Eh
K
Stabilizer
CCISeismic stabilizer 2.4'' x 6'
Stabilizer
55.00 0.00 0.0000 0.00 0.00 0.00 0.02
CCISeismic (2) tower mounts
T-Arm Mount [TA 602-3]
55.00 0.00 0.0000 0.32 0.00 0.00 1.29
CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to
54 (47ft to54ft)
51.50 0.00 0.0000 0.01 0.00 0.00 0.03
CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to
54 (37ft to47ft)
43.00 0.00 0.0000 0.01 0.00 0.00 0.03
CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to
54 (27ft to37ft)
33.00 0.00 0.0000 0.01 0.00 0.00 0.02
CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to
54 (17ft to27ft)
23.00 0.00 0.0000 0.01 0.00 0.00 0.01
CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to
54 (7ft to17ft)
13.00 0.00 0.0000 0.01 0.00 0.00 0.01
CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to
54 (0ft to7ft)
4.50 0.00 0.0000 0.01 0.00 0.00 0.00
CCISeismic (3) miscl 3/8'' Fiber
Cable From 0 to 54 (47ft to54ft)
51.50 0.00 0.0000 0.00 0.00 0.00 0.00
CCISeismic (3) miscl 3/8'' Fiber
Cable From 0 to 54 (37ft to47ft)
43.00 0.00 0.0000 0.00 0.00 0.00 0.00
CCISeismic (3) miscl 3/8'' Fiber
Cable From 0 to 54 (27ft to37ft)
33.00 0.00 0.0000 0.00 0.00 0.00 0.00
CCISeismic (3) miscl 3/8'' Fiber
Cable From 0 to 54 (17ft to27ft)
23.00 0.00 0.0000 0.00 0.00 0.00 0.00
CCISeismic (3) miscl 3/8'' Fiber
Cable From 0 to 54 (7ft to17ft)
13.00 0.00 0.0000 0.00 0.00 0.00 0.00
CCISeismic (3) miscl 3/8''
Fiber Cable From 0 to 54 (0ft
to7ft)
4.50 0.00 0.0000 0.00 0.00 0.00 0.00
Discrete Tower Loads
Description Face
or
Leg
Offset
Type
Offsets:
Horz
Lateral
Vert
ft
ft
ft
Azimuth
Adjustment
°
Placement
ft
CAAA
Front
ft2
CAAA
Side
ft2
Weight
K
*Branches*
Pine branch C None 0.0000 58.00 - 50.00 No Ice 52.00 52.00 0.74
Pine branch C None 0.0000 50.00 - 40.00 No Ice 101.00 101.00 1.45
Pine branch C None 0.0000 40.00 - 30.00 No Ice 97.00 97.00 1.55
Pine branch C None 0.0000 30.00 - 20.00 No Ice 157.00 157.00 2.03
******
AIR 6419 B77G w/ Mount
Pipe
A From Leg 4.00
0.00
2.70
0.0000 55.00 No Ice 3.87 2.32 0.08
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
6 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Description Face
or
Leg
Offset
Type
Offsets:
Horz
Lateral
Vert
ft
ft
ft
Azimuth
Adjustment
°
Placement
ft
CAAA
Front
ft2
CAAA
Side
ft2
Weight
K
AIR 6419 B77G w/ Mount
Pipe
B From Leg 4.00
0.00
2.70
0.0000 55.00 No Ice 3.87 2.32 0.08
AIR 6419 B77G w/ Mount
Pipe
A From Leg 4.00
0.00
2.70
0.0000 55.00 No Ice 3.87 2.32 0.08
AIR 6449 B77D A From Leg 4.00
0.00
-2.00
0.0000 55.00 No Ice 4.02 2.14 0.08
AIR 6449 B77D B From Leg 4.00
0.00
-2.00
0.0000 55.00 No Ice 4.02 2.14 0.08
AIR 6449 B77D C From Leg 4.00
0.00
-2.00
0.0000 55.00 No Ice 4.02 2.14 0.08
80010966 w/ Mount Pipe A From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 17.60 9.64 0.15
80010966 w/ Mount Pipe B From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 17.60 9.64 0.15
80010966 w/ Mount Pipe C From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 17.60 9.64 0.15
NNH4-65C-R6-V3 w/ Mount
Pipe
A From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 17.31 10.34 0.13
NNH4-65C-R6-V3 w/ Mount
Pipe
B From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 17.31 10.34 0.13
NNH4-65C-R6-V3 w/ Mount
Pipe
C From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 17.31 10.34 0.13
QS8658-3e w/ Mount Pipe A From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 11.70 11.74 0.13
QS8658-3e w/ Mount Pipe B From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 11.70 11.74 0.13
QS8658-3e w/ Mount Pipe C From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 11.70 11.74 0.13
RADIO 4478 B14 A From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 2.02 1.25 0.06
RADIO 4478 B14 B From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 2.02 1.25 0.06
RADIO 4478 B14 C From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 2.02 1.25 0.06
RRUS-32 B30 A From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 3.31 2.42 0.08
RRUS-32 B30 B From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 3.31 2.42 0.08
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
7 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Description Face
or
Leg
Offset
Type
Offsets:
Horz
Lateral
Vert
ft
ft
ft
Azimuth
Adjustment
°
Placement
ft
CAAA
Front
ft2
CAAA
Side
ft2
Weight
K
RRUS-32 B30 C From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 3.31 2.42 0.08
RRUS E2 B29 A From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 3.15 1.29 0.05
RRUS E2 B29 B From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 3.15 1.29 0.05
RRUS E2 B29 C From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 3.15 1.29 0.05
RRUS 4449 B5/B12 A From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 1.97 1.41 0.07
RRUS 4449 B5/B12 B From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 1.97 1.41 0.07
RRUS 4449 B5/B12 C From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 1.97 1.41 0.07
RRUS 8843 B2/B66A A From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 1.64 1.35 0.07
RRUS 8843 B2/B66A B From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 1.64 1.35 0.07
RRUS 8843 B2/B66A C From Leg 4.00
0.00
0.00
0.0000 55.00 No Ice 1.64 1.35 0.07
DC9-48-60-24-8C-EV A From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 4.78 2.60 0.03
DC9-48-60-24-8C-EV B From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 4.78 2.60 0.03
DC9-48-60-24-8C-EV C From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 4.78 2.60 0.03
2.4'' Dia x 4-ft Mount Pipe A From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 0.87 0.87 0.01
2.4'' Dia x 4-ft Mount Pipe B From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 0.87 0.87 0.01
2.4'' Dia x 4-ft Mount Pipe C From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 0.87 0.87 0.01
2.4'' x 6' Stabilizer A From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 1.44 1.44 0.02
2.4'' x 6' Stabilizer B From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 1.44 1.44 0.02
2.4'' x 6' Stabilizer C From Leg 2.00
0.00
0.00
0.0000 55.00 No Ice 1.44 1.44 0.02
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
8 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Description Face
or
Leg
Offset
Type
Offsets:
Horz
Lateral
Vert
ft
ft
ft
Azimuth
Adjustment
°
Placement
ft
CAAA
Front
ft2
CAAA
Side
ft2
Weight
K
(2) T-Arm Mount [TA 602-3] A None 0.0000 55.00 No Ice 11.59 11.59 0.77
******
Load Combinations
Comb.
No.
Description
1 Dead Only
2 1.2 Dead+1.0 Wind 0 deg - No Ice
3 0.9 Dead+1.0 Wind 0 deg - No Ice
4 1.2 Dead+1.0 Wind 30 deg - No Ice
5 0.9 Dead+1.0 Wind 30 deg - No Ice
6 1.2 Dead+1.0 Wind 60 deg - No Ice
7 0.9 Dead+1.0 Wind 60 deg - No Ice
8 1.2 Dead+1.0 Wind 90 deg - No Ice
9 0.9 Dead+1.0 Wind 90 deg - No Ice
10 1.2 Dead+1.0 Wind 120 deg - No Ice
11 0.9 Dead+1.0 Wind 120 deg - No Ice
12 1.2 Dead+1.0 Wind 150 deg - No Ice
13 0.9 Dead+1.0 Wind 150 deg - No Ice
14 1.2 Dead+1.0 Wind 180 deg - No Ice
15 0.9 Dead+1.0 Wind 180 deg - No Ice
16 1.2 Dead+1.0 Wind 210 deg - No Ice
17 0.9 Dead+1.0 Wind 210 deg - No Ice
18 1.2 Dead+1.0 Wind 240 deg - No Ice
19 0.9 Dead+1.0 Wind 240 deg - No Ice
20 1.2 Dead+1.0 Wind 270 deg - No Ice
21 0.9 Dead+1.0 Wind 270 deg - No Ice
22 1.2 Dead+1.0 Wind 300 deg - No Ice
23 0.9 Dead+1.0 Wind 300 deg - No Ice
24 1.2 Dead+1.0 Wind 330 deg - No Ice
25 0.9 Dead+1.0 Wind 330 deg - No Ice
26 Dead+Wind 0 deg - Service
27 Dead+Wind 30 deg - Service
28 Dead+Wind 60 deg - Service
29 Dead+Wind 90 deg - Service
30 Dead+Wind 120 deg - Service
31 Dead+Wind 150 deg - Service
32 Dead+Wind 180 deg - Service
33 Dead+Wind 210 deg - Service
34 Dead+Wind 240 deg - Service
35 Dead+Wind 270 deg - Service
36 Dead+Wind 300 deg - Service
37 Dead+Wind 330 deg - Service
38 1.2 Dead+1.0 Ev+1.0 Eh 0 deg
39 0.9 Dead-1.0 Ev+1.0 Eh 0 deg
40 1.2 Dead+1.0 Ev+1.0 Eh 30 deg
41 0.9 Dead-1.0 Ev+1.0 Eh 30 deg
42 1.2 Dead+1.0 Ev+1.0 Eh 60 deg
43 0.9 Dead-1.0 Ev+1.0 Eh 60 deg
44 1.2 Dead+1.0 Ev+1.0 Eh 90 deg
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
9 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Comb.
No.
Description
45 0.9 Dead-1.0 Ev+1.0 Eh 90 deg
46 1.2 Dead+1.0 Ev+1.0 Eh 120 deg
47 0.9 Dead-1.0 Ev+1.0 Eh 120 deg
48 1.2 Dead+1.0 Ev+1.0 Eh 150 deg
49 0.9 Dead-1.0 Ev+1.0 Eh 150 deg
50 1.2 Dead+1.0 Ev+1.0 Eh 180 deg
51 0.9 Dead-1.0 Ev+1.0 Eh 180 deg
52 1.2 Dead+1.0 Ev+1.0 Eh 210 deg
53 0.9 Dead-1.0 Ev+1.0 Eh 210 deg
54 1.2 Dead+1.0 Ev+1.0 Eh 240 deg
55 0.9 Dead-1.0 Ev+1.0 Eh 240 deg
56 1.2 Dead+1.0 Ev+1.0 Eh 270 deg
57 0.9 Dead-1.0 Ev+1.0 Eh 270 deg
58 1.2 Dead+1.0 Ev+1.0 Eh 300 deg
59 0.9 Dead-1.0 Ev+1.0 Eh 300 deg
60 1.2 Dead+1.0 Ev+1.0 Eh 330 deg
61 0.9 Dead-1.0 Ev+1.0 Eh 330 deg
Maximum Tower Deflections - Service Wind
Section
No.
Elevation
ft
Horz.
Deflection
in
Gov.
Load
Comb.
Tilt
°
Twist
°
L1 58 - 16 2.419 26 0.3455 0.0013
L2 20.35 - 1 0.301 26 0.1363 0.0002
Critical Deflections and Radius of Curvature - Service Wind
Elevation
ft
Appurtenance Gov.
Load
Comb.
Deflection
in
Tilt
°
Twist
°
Radius of
Curvature
ft
58.00 Pine branch 26 2.419 0.3455 0.0013 42200
57.00 CCISeismic Tower Section 1 - 1 26 2.349 0.3404 0.0013 42200
55.00 AIR 6419 B77G w/ Mount Pipe 26 2.210 0.3303 0.0012 42200
54.00 Pine branch 26 2.141 0.3252 0.0012 42200
51.50 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(47ft to54ft)
26 1.968 0.3125 0.0011 32462
51.00 CCISeismic Tower Section 1 - 2 26 1.934 0.3099 0.0011 30143
50.00 Pine branch 26 1.866 0.3048 0.0010 26375
45.00 Pine branch 26 1.534 0.2789 0.0008 16231
43.00 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(37ft to47ft)
26 1.405 0.2684 0.0008 14067
41.00 CCISeismic Tower Section 1 - 3 26 1.281 0.2577 0.0007 12412
40.00 Pine branch 26 1.220 0.2523 0.0007 11722
35.00 Pine branch 26 0.931 0.2248 0.0005 9174
33.00 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(27ft to37ft)
26 0.825 0.2135 0.0004 8440
31.00 CCISeismic Tower Section 1 - 4 26 0.724 0.2019 0.0004 7815
30.00 Pine branch 26 0.676 0.1961 0.0004 7536
25.00 Pine branch 26 0.460 0.1659 0.0002 6394
23.00 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
26 0.386 0.1534 0.0002 6073
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
10 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Elevation
ft
Appurtenance Gov.
Load
Comb.
Deflection
in
Tilt
°
Twist
°
Radius of
Curvature
ft
(17ft to27ft)
21.00 CCISeismic Tower Section 1 - 5 26 0.321 0.1406 0.0002 5963
20.00 Pine branch 26 0.291 0.1340 0.0002 6029
15.68 CCISeismic Tower Section 2 - 1 26 0.185 0.1050 0.0001 7390
13.00 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(7ft to17ft)
26 0.136 0.0864 0.0001 9037
6.00 CCISeismic Tower Section 2 - 2 32 0.046 0.0364 0.0000 21688
4.50 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(0ft to7ft)
32 0.031 0.0255 0.0000 21688
Maximum Tower Deflections - Design Wind
Section
No.
Elevation
ft
Horz.
Deflection
in
Gov.
Load
Comb.
Tilt
°
Twist
°
L1 58 - 16 6.425 2 0.9150 0.0035
L2 20.35 - 1 0.801 2 0.3628 0.0004
Critical Deflections and Radius of Curvature - Design Wind
Elevation
ft
Appurtenance Gov.
Load
Comb.
Deflection
in
Tilt
°
Twist
°
Radius of
Curvature
ft
58.00 Pine branch 2 6.425 0.9150 0.0036 15909
57.00 CCISeismic Tower Section 1 - 1 2 6.240 0.9017 0.0035 15909
55.00 AIR 6419 B77G w/ Mount Pipe 2 5.870 0.8750 0.0033 15909
54.00 Pine branch 2 5.686 0.8617 0.0032 15909
51.50 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(47ft to54ft)
2 5.229 0.8282 0.0029 12238
51.00 CCISeismic Tower Section 1 - 2 2 5.138 0.8214 0.0028 11364
50.00 Pine branch 2 4.958 0.8080 0.0027 9943
45.00 Pine branch 2 4.075 0.7398 0.0022 6119
43.00 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(37ft to47ft)
2 3.734 0.7120 0.0021 5303
41.00 CCISeismic Tower Section 1 - 3 2 3.403 0.6839 0.0019 4679
40.00 Pine branch 2 3.241 0.6697 0.0018 4419
35.00 Pine branch 2 2.475 0.5971 0.0014 3458
33.00 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(27ft to37ft)
2 2.192 0.5671 0.0012 3181
31.00 CCISeismic Tower Section 1 - 4 2 1.924 0.5366 0.0010 2946
30.00 Pine branch 2 1.797 0.5212 0.0010 2840
25.00 Pine branch 2 1.223 0.4413 0.0007 2410
23.00 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(17ft to27ft)
2 1.028 0.4080 0.0005 2289
21.00 CCISeismic Tower Section 1 - 5 2 0.853 0.3740 0.0005 2248
20.00 Pine branch 2 0.774 0.3567 0.0004 2272
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
11 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Elevation
ft
Appurtenance Gov.
Load
Comb.
Deflection
in
Tilt
°
Twist
°
Radius of
Curvature
ft
15.68 CCISeismic Tower Section 2 - 1 2 0.493 0.2794 0.0003 2785
13.00 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(7ft to17ft)
2 0.362 0.2301 0.0002 3406
6.00 CCISeismic Tower Section 2 - 2 14 0.122 0.0970 0.0001 8174
4.50 CCISeismic (9) commscope
PWRT-608-S( 13/16'') From 0 to 54
(0ft to7ft)
14 0.083 0.0680 0.0000 8174
Compression Checks
Pole Design Data
Section
No.
Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio
Pu
Pn
L1 58 - 16 (1) TP35.15x18x0.2188 42.00 0.00 0.0 23.0199 -15.04 1346.67 0.011
L2 16 - 1 (2) TP40.837x32.9363x0.25 19.35 0.00 0.0 32.2058 -18.05 1884.04 0.010
Pole Bending Design Data
Section
No.
Elevation
ft
Size
Mux
kip-ft
Mnx
kip-ft
Ratio
Mux
Mnx
Muy
kip-ft
Mny
kip-ft
Ratio
Muy
Mny
L1 58 - 16 (1) TP35.15x18x0.2188 255.45 1002.06 0.255 0.00 1002.06 0.000
L2 16 - 1 (2) TP40.837x32.9363x0.25 481.64 1662.84 0.290 0.00 1662.84 0.000
Pole Shear Design Data
Section
No.
Elevation
ft
Size
Actual
Vu
K
Vn
K
Ratio
Vu
Vn
Actual
Tu
kip-ft
Tn
kip-ft
Ratio
Tu
Tn
L1 58 - 16 (1) TP35.15x18x0.2188 11.35 394.14 0.029 0.17 1173.03 0.000
L2 16 - 1 (2) TP40.837x32.9363x0.25 11.95 565.21 0.021 0.17 2008.99 0.000
Pole Interaction Design Data
Section
No.
Elevation
ft
Ratio
Pu
Pn
Ratio
Mux
Mnx
Ratio
Muy
Mny
Ratio
Vu
Vn
Ratio
Tu
Tn
Comb.
Stress
Ratio
Allow.
Stress
Ratio
Criteria
ttnnxxTToowweerr Job
Fairview Business Park (CLL01580)
Page
12 of 12
TEP
326 Tryon Road
Project
TEP No. 353924.1184090
Date
06:58:25 11/18/25
Raleigh, NC 27603
Phone: (919) 661-6351
FAX: (919) 661-6350
Client
M Squared Wireless Designed by
adare
Section
No.
Elevation
ft
Ratio
Pu
Pn
Ratio
Mux
Mnx
Ratio
Muy
Mny
Ratio
Vu
Vn
Ratio
Tu
Tn
Comb.
Stress
Ratio
Allow.
Stress
Ratio
Criteria
L1 58 - 16 (1) 0.011 0.255 0.000 0.029 0.000 0.267 1.050
L2 16 - 1 (2) 0.010 0.290 0.000 0.021 0.000 0.300 1.050
Section Capacity Table
Section
No.
Elevation
ft
Component
Type
Size Critical
Element
P
K
øPallow
K
%
Capacity
Pass
Fail
L1 58 - 16 Pole TP35.15x18x0.2188 1 -15.04 1414.00 25.4 Pass
L2 16 - 1 Pole TP40.837x32.9363x0.25 2 -18.05 1978.24 28.5 Pass
Summary
Pole (L2) 28.5 Pass
RATING = 28.5 Pass
Program Version 8.3.1.2 - 12/11/2024 File:G:/Shared drives/350001 - 400000/353924/P-499575_L-1184090_CLL01580_FAIRVIEW BUSINESS
PARK_ Structural Analysis/TnxTower/Wind and Seismic/FAIRVIEW BUSINESS PARK (CLL01580) CCISeismic 5.0.2 Wind And Seismic Analysis.eri
November 18, 2025
58.0 -ft Monoeucalyptus Structural Analysis Fairview Business Park (CLL01580)
TEP Project Number 353924.1184090 Page 7
APPENDIX B
ADDITIONAL CALCULATIONS
Monopole Base Plate Connection
*TIA-222-H Section 15.5 Applied
#VALUE!
Anchor Rod Data Anchor Rod Summary (units of kips, kip-in)
(8) 2-1/4" ø bolts (A615-75 N; Fy=75 ksi, Fu=100 ksi) on 47.5" BC Pu_t = 58.58 φPn_t = 243.75 Stress Rating
Vu = 1.5 φVn = 149.1 22.9%
Base Plate Data Mu = n/a φMn = n/a Pass
53.5" OD x 2.25" Plate (A36; Fy=36 ksi, Fu=58 ksi)
Base Plate Summary
Stiffener Data Max Stress (ksi):6.84 (Flexural)
N/A Allowable Stress (ksi):32.4
Stress Rating:20.1%Pass
Pole Data
40.837" x 0.25" 18-sided pole (A572-65; Fy=65 ksi, Fu=80 ksi)
18.00
12.00
Adjusted Pole Reactions
Site # CLL01580
Applied Loads
Site Name Fairview Business
TEP # 353924.1184090
Analysis Considerations
Site Info
TIA-222 Revision H
Grout Considered:No
Analysis ResultsConnection Properties
Iar (in) 0
Moment (kip-ft) 482.00
Axial Force (kips) 18.00
Shear Force (kips) 12.00
Moment (kip-ft)
Axial Force (kips)
Shear Force (kips)
0.00
Show image?
Plate Dia.
Shaft Dia.
Pole Shape
Plate Type:
Plate Geometry:
Plate Quantity
Plate Dia. 2
Shaft Dia. 2
Analysis Date: 11/18/2025
FAIRVIEW BUSINESS PARK (CLL01580)
TEP #:
Analysis:PG 11/18/2025
Design Reaction Comparison Tool Check:SMS 11/18/2025
Code Revisions:TIA-222-H Tower Type:Monopole
Design Design*1.35 Analysis Capacity Pass / Fail
1019.95 1376.9325 482 33.3%Pass
27.41 37.0035 18 46.3%Pass
20.62 27.837 12 41.1%Pass
Note 3: Rating per TIA-222-H, Section 15.5
Note 1: Design loads were multiplied by 1.35 for comparison as allowed by TIA-222-H, Section 15.6.2.
Note 2: Although the axial and shear capacity are at 46.3% and 41.1%, respectively, the moment reaction is
the governing criteria for a monopole drilled shaft foundation. Therefore, the overall capacity for this
foundation is 33.3%.
November 18, 2025
58.0 -ft Monoeucalyptus Structural Analysis Fairview Business Park (CLL01580)
TEP Project Number 353924.1184090 Page 8
APPENDIX C
SEISMIC CALCULATIONS
Structure:ASite#: CLL01580
Site Name: Fairview Business
TEP#: 353924.1184090
S
1
L
e
a
v
DS
D1
s
DS
D1
1
Page 1 Analysis Date: 11/17/2025
Site #:
Site Name:
TEP #:
s
u
L
2
avg
4
a
a
s
smax
smax
smin
smin
sc
i i
k
Page 2 Analysis Date: 11/17/2025
Section
Number Length Top Height Mid Height, hx
Section
Weight, wx
wxhx
k Cvx Fxh Fxv
1 - 1 2.00 57.00 56.00 0.0859 15.26 0.0093 0.0748 0.0179
1 - 2 10.00 55.00 50.00 0.4876 74.83 0.0458 0.3666 0.1018
1 - 3 10.00 45.00 40.00 0.5841 67.26 0.0411 0.3296 0.1220
1 - 4 10.00 35.00 30.00 0.6805 54.13 0.0331 0.2652 0.1421
1 - 5 10.00 25.00 20.00 0.7770 36.68 0.0224 0.1797 0.1622
2 - 1 9.35 19.35 14.68 0.8734 27.68 0.0169 0.1356 0.1824
2 - 2 10.00 10.00 5.00 1.0407 8.25 0.0050 0.0404 0.2173
Sum 4.5293 284.09
Tower Section Loads
Page 3 Analysis Date: 11/17/2025
Name hx wx wxhx
k Cvx Fxh Fxv
Pine branch 53.00 0.7400 122.40 0.0749 0.5997 0.1545
Pine branch 44.00 1.4500 188.77 0.1155 0.9249 0.3028
Pine branch 34.00 1.5500 144.82 0.0886 0.7096 0.3236
Pine branch 24.00 2.0300 121.16 0.0741 0.5936 0.4239
ericsson AIR 6419 B77G w/ Mount Pipe 54.00 0.0800 13.55 0.0083 0.0664 0.0167
ericsson AIR 6419 B77G w/ Mount Pipe 54.00 0.0800 13.55 0.0083 0.0664 0.0167
ericsson AIR 6419 B77G w/ Mount Pipe 54.00 0.0800 13.55 0.0083 0.0664 0.0167
ericsson AIR 6449 B77D 54.00 0.0800 13.55 0.0083 0.0664 0.0167
ericsson AIR 6449 B77D 54.00 0.0800 13.55 0.0083 0.0664 0.0167
ericsson AIR 6449 B77D 54.00 0.0800 13.55 0.0083 0.0664 0.0167
kathrein 80010966 w/ Mount Pipe 54.00 0.1500 25.42 0.0155 0.1245 0.0313
kathrein 80010966 w/ Mount Pipe 54.00 0.1500 25.42 0.0155 0.1245 0.0313
kathrein 80010966 w/ Mount Pipe 54.00 0.1500 25.42 0.0155 0.1245 0.0313
commscope NNH4-65C-R6-V3 w/ Mount Pipe 54.00 0.1300 22.03 0.0135 0.1079 0.0271
commscope NNH4-65C-R6-V3 w/ Mount Pipe 54.00 0.1300 22.03 0.0135 0.1079 0.0271
commscope NNH4-65C-R6-V3 w/ Mount Pipe 54.00 0.1300 22.03 0.0135 0.1079 0.0271
quintel technology QS8658-3e w/ Mount Pipe 54.00 0.1300 22.03 0.0135 0.1079 0.0271
quintel technology QS8658-3e w/ Mount Pipe 54.00 0.1300 22.03 0.0135 0.1079 0.0271
quintel technology QS8658-3e w/ Mount Pipe 54.00 0.1300 22.03 0.0135 0.1079 0.0271
ericsson RADIO 4478 B14 54.00 0.0600 10.17 0.0062 0.0498 0.0125
ericsson RADIO 4478 B14 54.00 0.0600 10.17 0.0062 0.0498 0.0125
ericsson RADIO 4478 B14 54.00 0.0600 10.17 0.0062 0.0498 0.0125
ericsson RRUS-32 B30 54.00 0.0800 13.55 0.0083 0.0664 0.0167
ericsson RRUS-32 B30 54.00 0.0800 13.55 0.0083 0.0664 0.0167
ericsson RRUS-32 B30 54.00 0.0800 13.55 0.0083 0.0664 0.0167
ericsson RRUS E2 B29 54.00 0.0500 8.47 0.0052 0.0415 0.0104
ericsson RRUS E2 B29 54.00 0.0500 8.47 0.0052 0.0415 0.0104
ericsson RRUS E2 B29 54.00 0.0500 8.47 0.0052 0.0415 0.0104
ericsson RRUS 4449 B5/B12 54.00 0.0700 11.86 0.0073 0.0581 0.0146
ericsson RRUS 4449 B5/B12 54.00 0.0700 11.86 0.0073 0.0581 0.0146
ericsson RRUS 4449 B5/B12 54.00 0.0700 11.86 0.0073 0.0581 0.0146
ericsson RRUS 8843 B2/B66A 54.00 0.0700 11.86 0.0073 0.0581 0.0146
ericsson RRUS 8843 B2/B66A 54.00 0.0700 11.86 0.0073 0.0581 0.0146
ericsson RRUS 8843 B2/B66A 54.00 0.0700 11.86 0.0073 0.0581 0.0146
raycap DC9-48-60-24-8C-EV 54.00 0.0300 5.08 0.0031 0.0249 0.0063
raycap DC9-48-60-24-8C-EV 54.00 0.0300 5.08 0.0031 0.0249 0.0063
raycap DC9-48-60-24-8C-EV 54.00 0.0300 5.08 0.0031 0.0249 0.0063
mounts 2.4" Dia x 4-ft Mount Pipe 54.00 0.0100 1.69 0.0010 0.0083 0.0021
mounts 2.4" Dia x 4-ft Mount Pipe 54.00 0.0100 1.69 0.0010 0.0083 0.0021
mounts 2.4" Dia x 4-ft Mount Pipe 54.00 0.0100 1.69 0.0010 0.0083 0.0021
stabilizer 2.4" x 6' Stabilizer 54.00 0.0200 3.39 0.0021 0.0166 0.0042
stabilizer 2.4" x 6' Stabilizer 54.00 0.0200 3.39 0.0021 0.0166 0.0042
stabilizer 2.4" x 6' Stabilizer 54.00 0.0200 3.39 0.0021 0.0166 0.0042
(2) tower mounts T-Arm Mount [TA 602-3]54.00 1.5486 262.39 0.1605 1.2856 0.3233
Sum 10.1986 1327.51
Discrete Loads
Page 4 Analysis Date: 11/17/2025
Name Start Height End Height hx wx wxhx
k Cvx Fxh Fxv
(9) commscope PWRT-608-S( 13/16") From 0 to 54 47.00 54.00 50.50 0.0391 6.07 0.0037 0.0297 0.0082
(9) commscope PWRT-608-S( 13/16") From 0 to 54 37.00 47.00 42.00 0.0558 6.84 0.0042 0.0335 0.0117
(9) commscope PWRT-608-S( 13/16") From 0 to 54 27.00 37.00 32.00 0.0558 4.82 0.0029 0.0236 0.0117
(9) commscope PWRT-608-S( 13/16") From 0 to 54 17.00 27.00 22.00 0.0558 2.98 0.0018 0.0146 0.0117
(9) commscope PWRT-608-S( 13/16") From 0 to 54 7.00 17.00 12.00 0.0558 1.37 0.0008 0.0067 0.0117
(9) commscope PWRT-608-S( 13/16") From 0 to 54 0.00 7.00 3.50 0.0391 0.20 0.0001 0.0010 0.0082
(3) miscl 3/8" Fiber Cable From 0 to 54 47.00 54.00 50.50 0.0014 0.22 0.0001 0.0011 0.0003
(3) miscl 3/8" Fiber Cable From 0 to 54 37.00 47.00 42.00 0.0020 0.25 0.0002 0.0012 0.0004
(3) miscl 3/8" Fiber Cable From 0 to 54 27.00 37.00 32.00 0.0020 0.17 0.0001 0.0008 0.0004
(3) miscl 3/8" Fiber Cable From 0 to 54 17.00 27.00 22.00 0.0020 0.11 0.0001 0.0005 0.0004
(3) miscl 3/8" Fiber Cable From 0 to 54 7.00 17.00 12.00 0.0020 0.05 0.0000 0.0002 0.0004
(3) miscl 3/8" Fiber Cable From 0 to 54 0.00 7.00 3.50 0.0014 0.01 0.0000 0.0000 0.0003
Sum 0.3121 23.07
Linear Loads
Page 5 Analysis Date: 11/17/2025
Monopole Base Plate Connection - Seismic
*TIA-222-H Section 15.5 Applied
*1.5 Overstrength Factor Applied
#VALUE!
Anchor Rod Data Anchor Rod Summary (units of kips, kip-in)
(8) 2-1/4" ø bolts (A615-75 N; Fy=75 ksi, Fu=100 ksi) on 47.5" BC Pu_t = 67.23 φPn_t = 243.75 Stress Rating
Vu = 1.5 φVn = 149.1 26.3%
Base Plate Data Mu = n/a φMn = n/a Pass
53.5" OD x 2.25" Plate (A36; Fy=36 ksi, Fu=58 ksi)
Base Plate Summary
Stiffener Data Max Stress (ksi):5.34 (Flexural)
N/A Allowable Stress (ksi):32.4
Stress Rating:15.7%Pass
Pole Data
40.837" x 0.25" 18-sided pole (A572-65; Fy=65 ksi, Fu=80 ksi)
Analysis Results
Axial Force (kips) 21.00
Shear Force (kips) 8.00
Adjusted Pole Reactions
Moment (kip-ft) 0.00
Axial Force (kips) 21.00
Shear Force (kips) 8.00
Connection Properties
Moment (kip-ft) 369.00
TEP # 353924.1184090
Analysis Considerations
TIA-222 Revision H
Grout Considered:No
Iar (in) 0
Applied Loads
Site Info
Site # CLL01580
Site Name Fairview Business Show image?
Plate Dia.
Shaft Dia.
Pole Shape
Plate Type:
Plate Geometry:
Plate Quantity
Plate Dia. 2
Shaft Dia. 2
Analysis Date: 11/18/2025