Design Criteria:
10/31/2025
MASTER ROOFING SOLUTIONS.
Attn.: To Whom It May Concern
re job: PLAN BLDG A1 & BLDG A2
The following calculations are for the structural engineering design of the photovoltaic panels and are valid
only for the structural info referenced in the stamped plan set. The verification of such info is the
responsibility of others.
After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads.
All mounting equipment shall be designed and installed per manufacturer's approved installation
specifications.
Code 2022 California Building Code (ASCE 7-16)
Risk category II Wind Load (component and Cladding)
Dr 10 psf V 95 mph
DPV Exposure C
Lr
Roof Dead Load
PV Dead Load
Roof Live Load
Ground Snow S
3 psf
20 psf
4 psf
Signed-10/31/2025
EXP. 09/30/2026
2 of 5
Roof Properties:
Roof Type =
Roof Pitch (deg) =
Mean Roof Height (ft) =
Attachment Trib Width (ft) =
Attachment Spacing (ft) =
Framing Type =
Framing Size =
Framing OC Spacing (in.) =
Section Thickness, b (in.) =
Section Depth, d (in.) =
Section Modulus, Sx (in.^3) =
Moment of Inertia, Ix (in.^4) =
Framing Span (ft) =
Deflection Limit D+L (in.) =
Deflection Limit S or W (in.) =
Framing Upgrade =
Sister Size =
Wood Species =
Wood Fb (psi) =
Wood Fv (psi) =
Wood E (psi) =
CD (Wind) =
CD (Snow) =
CM = Ct = CL = Ci =
CF =
Cfu =
Cr =
F'b_wind (psi) =
F'b_snow (psi) =
F'v_wind (psi) =
F'v_snow (psi) =
M_allowable_wind (lb-ft) =
M_allowable_snow (lb-ft) =
V_allowable_wind (lbs) =
V_allowable_snow (lbs) =
E' (psi) =
12
2.4
1.60
Adequate
NA
DF #2
900
180
1600000
1.6
1.15
1.0
1.3
1.00
1.15
2153
1547
288
207
1357
975
1584
1139
1600000
1.5
3.4
5.6
20.6
4
Trusses
2x4
24
13
3.25
Comp. Shingle
2,4
Roof
Signed-10/31/2025
EXP. 09/30/2026
3 of 5
Wind Load Cont.
95 mph
C
1.0
0.96
0.83
0.87
ASCE 7-16 Figure 26.5-1B
ASCE 7-16 Sec 26.8.2
ASCE 7-16 Table 26.10-1
ASCE 7-16 Table 26.6-1
ASCE 7-16 Table 26.9-1
25.66 psf
4.0 Degrees
1.5 Conservatively assuming all exposed
0.8 conservatively assuming 10 ft2 effective area
Uplift (W)Zone(1) Zone(2r) Zone(2e)Zone(3)
Fig. 30-3-2 -2.1 -2.6 -2.7 -2.7
Eq. 29.4-7 -48.73 -42.39 -41.42 -39.83
0.3 Figure 30.3-2
GCp=
P=qh(GCp)(γE)(γa)=
GCp=
P=qh(GCp)(γE)(γa)=7.32 Equation 29.4-7
Trusses Attachments: 0.6D+0.6W (CD=1.6)
Connection Check
Attachment max. spacing=4 ft
5/16" x 4 1/2": 2 1/2" LAG SCREW Withdrawal Value=269 lbs/in
2.5 in
Table 12.2A - NDS
DFL Assumed
Prying Coefficient
Allowable Capacity=
Zone Trib Width Area (ft)
1.4
750 lbs Uplift
(lbs)Down (lbs)
Zone(1)4 11.0 85.6
Zone(2r)4 11.0
Zone(2e)4 11.0
Zone(3)4 11.0
85.6
85.6
85.6
Conservative Max=
156.3
227.4
242.8
138.8 <750
CONNECTION IS OK
Risk Category =
V=
Exposure =
KZt =
KZ =
1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift
governs
2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw.
Embedment in sheading or other material does not count.
II
Kd =
Ke =
qh= 0.00256KzKztKdKeV2=
Pitch =
γE=
γa=
Lag Screw Penetration
217.6
4 of 5
Vertical Load Resisting System Design
Roof Framing Trusses
Snow Load Fully Exposed
pg=4 psf Ct =1.1
Ce =0.9 Is =1.0
pf = 3 psf
pfmin. = 3.2 psf
ps = 1 psf Conservatively (Cs=1)5.5 plf
Max Length, L = 8.0 ft (Truss maximum Allowable Horizontal Span)
24 in
10 psf 20 plf
Tributary Width, WT =
Dr =
PvDL =3 psf 12 plf
Load Case: DL+0.75(0.6W+S)
0.75(Pnet+Ps)+ Ppvcos(θ)+PDL=41 plf
Mdown=328 lb-ft
975 lb-ft >258 lb-ft OKMallowable = Sx x Fb' (wind)=
Load Case: DL+S
Ps+ Ppvcos(θ)+PDL=38 plf
Mdown=306 lb-ft
975 lb-ft >281 lb-ft OKMallowable = Sx x Fb' (wind)=
Load Case: DL+0.6W
Pnet+ Ppvcos(θ)+PDL=37.7 plf
Max Moment, Mu=302 lb-ft
Mallowable = Sx x Fb' (wind)=1357 lb-ft >273 lb-ft OK
Pv max Shear=85.6 lbs
247 lbsShear, Vu=wL/2+Pv Point Load =
Max Shear, Vu=wL/2+Pv Point Load = 219 lb
Member Capacity
DF-L No.2
2X4 CL CF Ci Cr KF φ λ
Fb =900 psi 1.0 1.3 1.0 1.15 2.54 0.85 0.8 1346 psi
Fv =180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi
E =1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psi
Emin =580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi
3.5 in
1.5 in
Depth, d =
Width, b =
Cross-Sectonal Area, A =
Moment of Inertia, Ixx =Section Modulus, Sxx =7.5425 in20.7469 in5.25 in4
2
3
848.5 lb-ft SatisfactoryAllowable Moment, Mall = Fb'Sxx =
Allowable Shear, Vall = 2/3Fv'A =990.1 lb
DCR=Mu/Mall =0.34 < 1
DCR=Vu/Vall =0.22 < 1 Satisfactory
Design Value Adjusted Value
5 of 5
Existing structure is assumed to have been designed and constructed following appropriate codes at
time of erection, and assumed to have appropriate permits. The calculations produced are only for the
roof framing supporting the proposed PV installation referenced in the stamped planset and were
completed according to generally recognized structural analysis standards and procedures, professional
engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or
were not observable during time of inspection are not included in this scope of work. All PV modules,
racking, and mounting equipment shall be designed and installed per manufacturer's approved
installation specifications. The Engineer of Record and the engineering consulting firm assume no
responsibility for misuse or improper installation. This analysis is not stamped for water leakage.
Framing was determined based on information in provided plans and/or photos, along with engineering
judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and
spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the
Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that
there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter
(where applicable) and notify the Engineer of Record of any concerns prior to starting construction.
Siesmic Loads Check
Roof Dead Load 10 psf
29.47%
3 psf
8.9 psf
% or Roof with Pv
Dpv and Racking
Average Total Dead Load
Increase in Dead Load 4.1% OK
BLDG. A1
2150 E. FOURTH
BLDG. A2
2160 E. FOURTH
VICINITY MAP
PV COVER
RE
V
I
S
I
O
N
S
RE
V
DE
S
C
R
I
P
T
I
O
N
DA
T
E
M
AC
P
ROOF ACCESS POINTS
SOLAR MODULES. PV MICROINVERTERS MOUNTED ON THE BACK OF EACH MODULE
C
SYMBOLS AND ABBREVIATIONS:
MAIN SERVICE PANEL AND POINT OF INTERCONNECTION
PV SYSTEM AC DISCONNECT
PV SYSTEM COMBINER PANEL
UTILITY PRODUCTION METER
COMPOSITE SHINGLE INSET INTO TILE UNDER ARRAY
SHEET INDEX:
PV COVER COVER SHEET
PV SP 1.0 SITE PLAN
PV SP 1.1 SITE PLAN
PV RL 1.0 PV LAYOUTS
PV RL 1.1 PV LAYOUTS
PV SR 1.0 STRUCTURAL
PV EE 1.0 ELECTRICAL
PV CS 1.0 CUTSHEETS
PV CS 1.1 CUTSHEETS
SOLAR PV PLANS
OLIVE CREST 16
PLAN BLDG A1 & A2
2150 E FOURTH STREET
SANTA ANA, CA
2160 E FOURTH STREET
SANTA ANA, CA
BUILDER / OWNER
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
J. Pasquin
Solar Designer
SCOPE OF WORK
1.SOLELY FOR THE INSTALLATION OF THE ROOFTOP MOUNTED PV SYSTEM(S) ASSOCIATED
WITH OLIVE CREST 16
1.1.PLAN: BLDG A1 & A2
2.BUILDING INFORMATION:
2.1.BUILDING OCCUPANCY GROUP: R2
2.2.CONSTRUCTION TYPE: VA
2.3.NUMBER OF STORIES: 2-STORY
3.PV SYSTEM:
3.1.MICROINVERTER(S):
3.1.1.ENPHASE: IQ8P-3P-72-E-US (@208V)
3.2.SOLAR MODULE TYPE(S):
3.2.1.HYUNDAI: HIN-T440NF(BK)
3.3.SYSTEM SIZE(S):
3.3.1.(45) MODULES 19.800kW DC / 21.375kW AC
GENERAL NOTES:
1.ELECTRICAL
1.1.ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS
DESIGNED AND LISTED FOR SUCH USE. FOR ROOF-MOUNTED SYSTEMS, WIRING
MUST BE PERMANENTLY AND COMPLETELY HELD OFF OF THE ROOF SURFACE.
1.2.SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH ALL RELEVANT CODE.
1.3.SEE *PV EE 1.0 FOR DIAGRAMS, CALCULATIONS, SCHEDULE AND SPECIFICATIONS.
2.STRUCTURAL
2.1.THE SOLAR PANELS ARE TO BE MOUNTED TO THE ROOF FRAMING USING THE L FOOT
SYSTEM BY IRONRIDGE. THE MOUNTING FEET ARE TO BE SPACED AS SHOWN IN THE
DETAILS, AND SHOULD BE STAGGERED, WHERE POSSIBLE, TO ADJACENT FRAMING
MEMBERS TO SPREAD OUT THE ADDITIONAL LOAD.
2.2.UNLESS NOTED OTHERWISE, MOUNTING ANCHORS SHALL BE 5/16" LAG SCREWS
WITH A MINIMUM OF 2 1/2" PENETRATION INTO ROOF FRAMING.
2.3.THE PROPOSED PV SYSTEM ADDS 3.0 psf TO THE ROOF FRAMING SYSTEM.
2.4.ROOF LIVE LOAD = 20 psf TYPICAL, 0 psf UNDER NEW PV SYSTEM.
2.5.GROUND SNOW LOAD = 4 psf
2.6.WIND SPEED = 95 mph
2.7.EXPOSURE CATEGORY = C
GOVERNING CODES:
ALL WORK SHALL CONFORM TO THE FOLLOWING CODES
1.2022 CA BUILDING CODE
2.2022 CA ENERGY CODE
3.2022 CA ELECTRICAL CODE
4.2022 CA FIRE CODE
5.2022 CA GREEN CODE
6.2022 CA MECHANICAL CODE
7.2022 CA PLUMBING CODE
8.2022 CA RESIDENTIAL CODE
9.ANY OTHER LOCAL AMENDMENTS
4
3
4
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
PV SP 1.0
SITE PLAN
J. Pasquin
Solar Designer
2150 E FOURTH STREET SANTA ANA, CA
2160 E FOURTH STREET SANTA ANA, CA
2
2
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
PV SP 1.1
SITE PLAN
J. Pasquin
Solar Designer
4
2150 E FOURTH STREET SANTA ANA, CA
2160 E FOURTH STREET SANTA ANA, CA
SCALE:
3/32" = 1'-0"BUILDING(S) BLDG-A1
LAYOUT 1 LAYOUT 2
4"
/
1
'
-
0
"
4" / 1'-0"4" / 1'-0"
4"
/
1
'
-
0
"
61'-10"
72'-4"
4"
/
1
'
-
0
"
4" / 1'-0"4" / 1'-0"
4"
/
1
'
-
0
"
61'-10"
72'-4"
M
M
M
M
M
M
M
C
AC
M
M
M
M
M
M
M
C
AC
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
PV RL 1.0
PV ROOF LAYOUTS
FIRECODE OFFSET:
RIDGE:18"
RAKE:18"
HIP/VALLEY: 18"
PV SYSTEM WILL CONFORM TO ALL
APPLICABLE GOVERNING CODES AS
OUTLINED ON PV COVER PAGE, NOR
TO BLOCK OR COVER ANY ROOF
PLUMBING OR VENTILATION.
J. Pasquin
Solar Designer
2150 E FOURTH STREET SANTA ANA, CA
4
5
SCALE:
3/32" = 1'-0"BUILDING(S) BLDG-A2
LAYOUT 1 LAYOUT 2
4"
/
1
'
-
0
"
4" / 1'-0"4" / 1'-0"
4"
/
1
'
-
0
"
M
M
M
M
M
M
M
M
C
AC
61'-10"
72'-4"
4"
/
1
'
-
0
"
4" / 1'-0"4" / 1'-0"
4"
/
1
'
-
0
"
M
M
M
M
M
M
M
M
C
AC
61'-10"
72'-4"
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
PV RL 1.1
PV ROOF LAYOUTS
FIRECODE OFFSET:
RIDGE:18"
RAKE:18"
HIP/VALLEY: 18"
PV SYSTEM WILL CONFORM TO ALL
APPLICABLE GOVERNING CODES AS
OUTLINED ON PV COVER PAGE, NOR
TO BLOCK OR COVER ANY ROOF
PLUMBING OR VENTILATION.
J. Pasquin
Solar Designer
2160 E FOURTH STREET SANTA ANA, CA
4
5
MODULES:
HYUNDAI: HIN-T440NF(BK)
MODULE DIMENSIONS:
67.8" x 44.6" x 1.2"
MODULE CLAMPS:
PORTRAIT: 9.84" - 17.72"
LANDSCAPE: 0" - 9.84"
LAG SCREWS:
5/16" x 4 1/2": 2 1/2"
MIN. EMBEDMENT
MAX DISTRIBUTED LOAD:
3 PSF
SNOW LOAD:
4 PSF
WIND SPEED:
95 MPH 3-SEC GUST.
STRUCTURAL NOTES:
INSTALLERS TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY E.O.R. OF ANY DISCREPANCIES BEFORE
PROCEEDING.
PENETRATION SPACING:
STAGGERED/FULLY STAGGERED MAY BE REQUIRED
IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12" BOUNDARY REGION OF ANY ROOF PLANE EDGES (EXCEPT VALLEYS), THEN
ATTACHMENTS NEED TO BE ADDED AND OVERHANG REDUCED WITHIN THE 12" BOUNDARY REGION ONLY AS FOLLOWS:
·ALLOWABLE ATTACHMENT SPACING INDICATED ON PLANS T0 BE REDUCED BY 50%.
·ALLOWABLE OVERHANG INDICATED ON PLANS THE BE 1/5TH OF ALLOWABLE ATTACHMENT SPACING INDICATED ON
PLANS.
WHERE MOUNTS ARE TO BE ANCHORED TO FLAT RAFTERS, MOUNTS SHALL BE INSTALLED WITH ONE OF THE FOLLOWING
OPTIONS.
·OPTION 1: INSTALL ATTACHMENTS ON EVERY FLAT RAFTER UNDER ARRAY WITH REDUCED EMBEDMENT ON FLAT 2x4
MEMBERS. USE 5/16" x 3.5" FULLY-THREADED LAG SCREWS WITH 2.5" EMBEDMENT.
·OPTION 2: BLOCKING MUST BE INSTALLED TO PROCEED WITH ATTACHMENT SPACINGS AS NOTED ON PLANSET.
WHERE MOUNTS ARE TO BE ANCHORED DIRECTLY TO HORIZANTAL TRUSSES. BLOCKING MUST BE INSTALLED TO
PROCEED WITH ATTACHMENT SPACINGS AS NOTED ON PLANSET.
LONGER LAG SCREWS SHALL BE UTILIZED, AS NECESSARY, TO OBTAIN THE MINIMUM SPECIFIED SCREW EMBEDMENT INTO
THE ROOF FRAMING. RIPPERS ON THE ROOF DO NOT QUALIFY AS THE ROOF FRAMING WHERE SOLAR PV MOUNT
EMBEDMENT IS CONCERNED. INSTALLERS SHALL VERIFY SCREW EMBEDMENT REQUIREMENTS ARE MET FOR ALL MOUNTS.
GENERAL NOTES:
*THIS INFORMATION PRESENTED ON THIS PAGE IS MEANT TO ILLUSTRATE GENERAL MATERIALS AND INSTALLATION PRACTICES.
*THE INFORMATION HERE IS SUBJECT TO CHANGE UNIQUE PLANS WILL BE CREATED FOR EACH BUILDING PRIOR TO
CONSTRUCTIONS FOR REVIEW.
DESIGN CRITERIA
STRUCTURAL DETAILS
ROOF INFORMATION ATTACHMENT INFORMATION
TYPE HEIGHT ROOF PITCHES
(X:12)DETAIL MAX PORTRAIT
(OC SPACING)
MAX PORTRAIT
(OVERHANG)
MAX LANDSCAPE
(OC SPACING)
MAX LANDSCAPE
(OVERHANG)CONFIGURATION
COMPOSITE SHINGLE 2-STORY 4, 2 IRONRIDGE L-FOOT 48"L/3 72"L/3 STAGGERED
PORTRAIT:
MAX 48"
SPACING (L)
MAX 10" - 16"
CANTILEVER,
TYP *
MODULE, TYP.
FRAMING, TYP.
UR-40 RAIL, TYP.
CANTILEVER
L/3 OR LESS
MAX 10" - 16"
CANTILEVER,
TYP *
LANDSCAPE:
MAX 72"
SPACING (L)
*DEFER TO MODULE MANUFACTURER
LIMITATIONS WHERE THEIR MAXIMUM
VERTICAL CANTILEVER IS SMALLER.
TYPICAL MOUNT SPACING LAYOUT
NOT TO SCALE1
TRUSS TOP CHORD
PV MODULE
l-foot
COMP. SHINGLE
TRUSS TOP CHORDDECKING
PV MODULE IRONRIDGE RAIL
QMPV L-FOOT ASSEMBLY
SIDE VIEW DETAIL2
LAG BOLT - 5/16" W/ 3" MIN.
EMBEDMENT, SEALED
STRUCTURAL
STRUCTURAL DETAILS TABLE
RACKING
MOUNT DETAILS
PV SR 1.0
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
J. Pasquin
Solar Designer
3
Power Source(s) Output Calc: 705.12(B)(3)(2)Voltage and OCPD Calculations (690.7, 690.9)
ASHRAE 2017 - SANTA ANA CITY
Highest Monthly 2% D.B. Design Temp.: 31 °C
Lowest Min. Mean Extreme D.B.: 2 °C
System Characteristics Conductor Calculations
MODULE:
Max Power @ STC (Watts):
Open Circuit Voltage (Volts):
Max Power Voltage (Volts):
Short Circuit Current (Amps):
HYUNDAI: HiN-T440NF(BK)
440
38.8
32.3
14.39
INVERTER:
AC Operating Voltage (Volts):
Max AC Current (Amps):
Max Panels Per Circuit:
Short Circuit Current (Amps):
Max Power @ 40 C (Watts):
Max DC Voltage (Volts):
ENPHASE: IQ8P-3P-72-E-US (@208V)
12
475
63
25
2.28
208
PV Source Max Circuit Voltage: Module Voc × (1-(ΔT × Voc Coeff)) [art. 690.7(A)]
HYUNDAI: HIN-T440NF(BK): 38.8 V × (1-((25 C – 2 C) × -0.27%)) <= 63 V
Photovoltaic System
DC System Size (Watts)19800
AC System Size (Watts)21375
Total Module Count 45
Main Bus Rating: 400 Amps
Main Service Breaker Rating: 400 Amps
PV Uprated Output Current: 80 Amps
400A + 80A <= 400 x 1.2; 480 <= 480A, OK
General Notes
• Designed according to and all code citations are relevant to the 2022 California Electrical Code.
• Inverter(s) used in this design is/are compliant with 690.12 (Rapid Shutdown). See manufacturer data sheet.
• All inverters installed in California are Rule 21 Utility interactive compliant.
• Array grounding and bonding designed in compliance with 690.47(A).
• Electrical terminations and connectors used in design are listed for use at a minimum of 75°C
Inverter Output Circuit(s): Modules per Circuit × Listed Output Current × 1.25
[art. 690.9(B)]
Circuit #1, 3, & 5 = 8 modules × 2.28 × 1.25 = 23 <= 25 A (OCPD)
System output current w/ continuous duty = 80 A (System OCPD)
Circuit #2, 4, & 6 = 7 modules × 2.28 × 1.25 = 20 <= 20 A (OCPD)
M*
ENCLOSURE WITH ENVOY
(ENV-IQ-AM3-3P)
PV CIRCUIT 2:
(N) 7 HYUNDAI:
HIN-T440NF(BK)
PV MODULES /
PARALLEL, ON ROOF
1 2 7
WI
T
H
I
N
I
N
T
E
R
I
O
R
W
A
L
L
C
A
V
I
T
Y
IN
A
T
T
I
C
(N) MICROINVERTER: ENPHASE: IQ8P-3P-72-E-US
(@208V)
(MOUNTED TO THE BACK OF EACH MODULE)
PV CIRCUIT 1:
(N) 8 HYUNDAI:
HIN-T440NF(BK)
PV MODULES /
PARALLEL, ON ROOF
1 2 8
1
2
(N) NEW EXTERIOR QO327M100 PV LOAD CENTER 120/208V,
100A BUSBAR RATING,
THREE-PHASE,
WITH 80A MAIN DISCONNECT
PV CIRCUIT 4:
(N) 7 HYUNDAI:
HIN-T440NF(BK)
PV MODULES /
PARALLEL, ON ROOF
1 2 7
PV CIRCUIT 3:
(N) 8 HYUNDAI:
HIN-T440NF(BK)
PV MODULES /
PARALLEL, ON ROOF
1 2 8
PV CIRCUIT 6:
(N) 7 HYUNDAI:
HIN-T440NF(BK)
PV MODULES /
PARALLEL, ON ROOF
1 2 7
PV CIRCUIT 5:
(N) 8 HYUNDAI:
HIN-T440NF(BK)
PV MODULES /
PARALLEL, ON ROOF
1 2 8
(N) JUNCTION BOX,
NEMA 3R,
ON ROOF
(N) JUNCTION BOX,
NEMA 3R,
ON ROOF
(N) JUNCTION BOX,
NEMA 3R,
ON ROOF
80A
G N
M
G
N
400A
FACILITY GROUND
L1 L2 N
380A
FUSE
3
N
L1
L2
G
VISIBLE/LOCKABLE 'KNIFE'
AC DISCONNECT
(N) EXTERIOR SQUARE D
VH363NRB, 208V/100A,
FUSED, NEMA3R
RAPID SHUTDOWN
DISCONNECT POINT OF INTERCONNECTION:
SUPPLY SIDE
705.12(B)(3)(2)
BUILDER TO ENSURE
SPD COMPLIANCE
(230.67)
YELLOW PLACARD WITH BLACK
LETTERING TO BE INSTALLED AT
MAIN BILLING METER STATING:
"PHOTOVOLTAIC SYSTEM
CONNECTED"
EXISTING 120/208V
EXTERIOR SERVICE PANEL,
400A BUSBAR RATING,
THREE-PHASE
M M M M
MMMM
L3
L3
25A
20A
25A
20A
25A
20A
2
1
2 2
1
2 2
1
2 2
1
2 2
1
2 2
20A
CONDUIT CONDUCTOR SCHEDULE (UNLESS OTHERWISE SPECIFIED, CONDUCTORS SHALL BE COPPER)
TAG CONDUCTOR NEUTRAL GROUND CONDUIT
1
2
3
Wire ampacity calculated from 310.15(B)(1) & (C)(2) as appropriate with ambient temperature
calculations from 310.15(B)(1) & 310.15(C)(2) and raceway fill adjustments from 310.15(B)(3)(a)
Conduit on the roof shall be installed no less than 1” above the roof deck.
PV Circuit conductor ampacity is constrained using the 75°C column with the continuous duty
uprating or the 90°C column with the relevant ambient temperature and raceway fill adjustments
without the continuous duty uprating per 690.8(B), whichever results with a larger wire size.
Non-PV Circuit conductors use the ampacity in the 75°C column or the 90°C column with the
relevant ambient temperature and raceway fill adjustments, whichever is less (110.14(C) &
310.15(A)(2)). The rating of the conductor after adjustments shall be greater than, or equal to,
the continuous duty uprated current.
More information about conductor calculations can be provided upon request.
Calc. Ex: Wire Ampacity x Ambient Temp. Corr. Factor x Conduit Fill Adj. Factor >= Output Current
(Tag 1 Under Array):
(Tag 2 Attic):
(Tag 3 Exterior):
*"FREE AIR" CONDUIT TO BE PROTECTED BY RUNNING THROUGH WALL CAVITIES*
FREE AIR
FREE AIR
NONE
(1) 8 AWG NM
(1) 10 AWG NM
(1) 6 AWG BARE COPPER
(1) 3 AWG NM
NONE
NONE
(3) 3 AWG NM
(3) 10 AWG NM
(3) 12 AWG Q-CABLE
Inverter Output: 12 AWG rated 40A, 40A >= 20A
Inverter Output: 10 AWG rated 30A, 30A >= 20A
Inverter Output: 3 AWG rated 85A, 85A >= 80A
(15) * (2.28A) * (1.732) * 1.25 = 74.043A ~ 80 A
3-PHASE CURRENT CALCULATION:
NOTE: ROMEX CABLE SHALL NOT BE
ROUTED OUTSIDE THE BUILDING
ENVELOPE IN ANY MANNER,
INCLUDING IN CONDUIT. FIELD
CONDITIONS OR INSTALLATION
CONVENIENCE SHALL NOT JUSTIFY NM
USE OUTSIDE THE STRUCTURE. ALL
EXTERIOR, PV, ESS, ACD, AND
INTERCONNECTION WIRING SHALL
UTILIZE APPROVED OUTDOOR-RATED
CONDUCTORS AND METHODS PER NEC.
NOTE:THE ELECTRICAL SYSTEM
SHOWN IN THIS SINGLE-LINE DIAGRAM
IS APPLICABLE TO BUILDINGS A1 AND
A2.
ELECTRICAL
THREE LINE DIAGRAM
WARNING LABELS
LABEL GUIDE
PV EE 1.0
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
J. Pasquin
Solar Designer
2
2
3
3
3
4
MAXIMUM AC OPERATING CURRENT:59 A
NOMINAL AC OPERATING VOLTAGE:208 VAC
PHOTOVOLTAIC AC DISCONNECT
Warning Labels
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
WARNING
WARNING
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION
POWER SOURCE OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
DUAL POWER SOURCE
SOURCES: UTILITY GRID AND PV SOLAR
ELECTRIC SYSTEM
4"
3"
WARNING
THIS EQUIPMENT FED BY MULTIPLE SOURCES.
TOTAL RATING OF ALL OVERCURRENT DEVICES
EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE
SHALL NOT EXCEED AMPACITY OF BUSBAR
!
!
!
!
LABEL LOCATION:
INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF
APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), CEC 2022: 690.13(B)
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN SERVICE PANEL.
PER CODE(S): NEC 2020: 705.12(C), CEC 2022: 705.12(C)
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2), CEC 2022: 705.12(B)(3)(2)
LABEL LOCATION:
PV LOAD CENTER (IF APPLICABLE) AND ANY PANEL THAT
UTILIZES "THE SUM OF BREAKERS RULE".
PER CODE(S): NEC 2020: 705.12 (B)(3)(3), CEC 2022: 705.12 (B)(3)(3)
LABEL LOCATION:
ON OR NO MORE THAN 1 M (3FT) FROM THE SERVICE DISCONNECTING
MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C)
MAXIMUM SYSTEM VOTAGE:480 VDC
PHOTOVOLTAIC DC DISCONNECT
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): NEC 2020: 690.53, CEC 2022: 690.53
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUTDOWN SWITCH
PER CODE(S): NEC 202: 690.56(C)(2), CEC 2022: 690.56(C)(2), IFC 2018: 1405.5.3
NOTES AND SPECIFICATIONS:
·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE 2022 CEC
ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY
SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.
·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING
EFFECTIVE WORDS, COLORS AND SYMBOLS.
·LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
METHOD AND SHALL NOT BE HAND WRITTEN.
·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED.
·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT
SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
·DO NOT COVER EXISTING MANUFACTURER LABELS.
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, CEC 2022: 690.54
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT, AT EACH TURN, ABOVE AND
BELOW PENETRATIONS, ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): NEC 2020: 690.56(C)(2), CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
(OPTION 1)(OPTION 2)
ELECTRICAL
WARNING LABELS
LABEL GUIDE
PV PL 1.0
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
J. Pasquin
Solar Designer
ROOFTOP ARRAY
WITH MICROINVERTERS
2
4
1
3 5
ROOFTOP
JUNCTION BOX
COMBINER PANEL
(WHEN USED)
VISIBLE/LOCKABLE A/C
DISCONNECT
TYPICAL SOLAR GENERATION INSTALLATION
(NOT ALL DEVICES ARE REQUIRED IN EVERY JURISDICTION)
MAIN SERVICE
DISCONNECT PANEL
*** - value calculated for each
account, for specific value see the
previous warning label page
3 5
INSIDE
PANEL
6 5
M
7
8
3
IF APPLICABLE
HO
U
S
E
E
X
T
E
R
I
O
R
RO
O
F
T
O
P
&
A
T
T
I
C
(
I
F
A
P
P
L
I
C
A
B
L
E
)
1
2
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
PHOTOVOLTAIC AC DISCONNECT
3
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
4
MAXIMUM AC OUTPUT CURRENT: *** A
NOMINAL AC OPERATING VOLTAGE: *** V
SITE PLACARD SHOWING ADDITIONAL POWER SOURCE
AND DISCONNECT LOCATIONS. PLACARD SHALL BE
MOUNTED ON EXTERIOR OF ELECTRICAL PANEL
5
6
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
POWER SOURCE OUTPUT CONNECTION
DO NOT RELOCATE
THIS OVERCURRENT PROTECTION DEVICE
8
7 DUAL POWER SOURCE
SOURCES: UTILITY GRID
AND PV SOLAR ELECTRIC SYSTEM
MAIN BREAKER DE-RATED
DUE TO SOLAR CIRCUITS
***AMPS MAX ALLOWED
DO NOT UPGRADE
WARNING
WARNING
4
CAUTION: MULTIPLE SOURCES OF POWER
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECT LOCATED AS SHOWN
LOT SPECIFIC PLACARDS TO BE PROVIDED WITH INDIVIDUAL TRADE LAYOUTS
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
2160 E FOURTH STREET
LOT SPECIFIC PLACARDS TO BE PROVIDED WITH INDIVIDUAL TRADE LAYOUTS
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
2160 E FOURTH STREET
CAUTION: MULTIPLE SOURCES OF POWER
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECT LOCATED AS SHOWN
CAUTION: MULTIPLE SOURCES OF POWER
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECT LOCATED AS SHOWN
LOT SPECIFIC PLACARDS TO BE PROVIDED WITH INDIVIDUAL TRADE LAYOUTS
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
2150 E FOURTH STREET
LOT SPECIFIC PLACARDS TO BE PROVIDED WITH INDIVIDUAL TRADE LAYOUTS
PER CODE(S): NEC 2020 : 705.10, 710.10, CEC 2022: 705.10, 710.10
2150 E FOURTH STREET
CAUTION: MULTIPLE SOURCES OF POWER
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECT LOCATED AS SHOWN
(OPTION 1)(OPTION 2)
(OPTION 1)(OPTION 2)
2150 E FOURTH STREET
2160 E FOURTH STREET
M
M
M
M
M
M
M
C
AC
M
M
M
M
M
M
M
C
AC
PHOTOVOLTAIC
ARRAY ON ROOF
MAIN
SERVICE
PANEL
IQ
COMBINER
(EXT)
AC
DISCONNECT
(EXT)
PHOTOVOLTAIC
ARRAY ON ROOF
MAIN
SERVICE
PANEL
IQ
COMBINER
(EXT)
AC
DISCONNECT
(EXT)
PHOTOVOLTAIC
ARRAY ON ROOFPHOTOVOLTAIC
ARRAY ON ROOF
M
M
M
M
M
M
M
C
AC
MAIN
SERVICE
PANEL
IQ COMBINER (EXT)
AC
DISCONNECT
(EXT)
M
M
M
M
M
M
M
M
C
AC
MAIN
SERVICE
PANEL
IQ COMBINER (EXT)
AC
DISCONNECT
(EXT)
M
PV CS 1.0
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
CUTSHEETS
MICROINVERTER
COMBINER PANEL
MODULE
J. Pasquin
Solar Designer
PV CS 1.1
HOME DEVELOPER:
WJK DEVELOPMENT
16520 BAKE PKWY
IRVINE, CA 92618
OLIVE CREST 16
SANTA ANA, CA
REV: A
DATE: 3/2/2026
PV SYSTEM PROVIDED BY:
CA LICENSE: 1125771
CUTSHEETS