HomeMy WebLinkAbout2915 3%4 W La Verne Ave WCC01 - PlanYES NO
INSTRUCTIONS:
ORAN GE COUNTY FI RE AUTHORI TY
Plan Submittal Criteria
COMMERCIAL projects, MULTIFAMILY RESIDENTIAL projects
and RESIDENTIAL TRACT developments
·Fill in the project/business address and provide a brief description of the scope of work and type of business operation that will take place.
·Answer questions 1 through 10, read and initial items 11 and 12, then complete and sign the certification section.
·If you answer: - “YES” to any part of questions 1 through 10, submit the type of plan indicated in italics to OCFA.
·In some cases, other plan types not indicated herein may also be necessary depending on specific conditions or operations.
·Visit www.ocfa.org for submittal information and locations. If you need assistance in filling out this form or have questions regarding
requirements for review, please contact OCFA at 714-573-6108 or visit us at 1 Fire Authority Road, Irvine, CA 92602.
Address Suite City
Project Scope/Business Description
1. Construction of a new building, a new story, or increase the footprint of an existing building? Changes to roadways,
curbs, or drive aisles? Addition, relocation, or modification of fire hydrants or fences/gates? Construction within
300 feet of an active or proposed oil well? Fire Master Plan (PR145)
2. Property is adjacent to a wildland area or non-irrigated native vegetation?
Fire Master Plan (PR145); a Fuel Modification Plan may also be required. (PR120, PR124)
3. Located in or < 100’ from a Division of Oil, Gas, and Geothermal Resources (DOGGR) field boundary, < 300’ from
an oil/gas seep, or < 1000’ from a landfill? Methane Work Plan. (PR170)
4. Installation/modification/repair of underground piping, backflow preventers, or fire department connections serving
private fire hydrant/sprinkler/standpipe systems? Underground Plan. (PR470, PR475)
5. Drinking/dining/recreation/meetings/training/religious functions or other gatherings in a room > 750 sq.ft. (> 1,000
sq.ft. for training/adulteducation) or > 49 people? Healthcare/outpatient services for > 5 people who may be unable
to immediately evacuate without assistance? Education for children (academic tutoring for ages 5+ is exempt unless
classified as an E occupancy by the Building Official)? Adult/child daycare? 24-hour care/supervision? Incarceration
or restraint? Hotel/apartment or residential facility with 3+ units and 3+ stories (3-story townhouses/rowhouses
where an independent direct exit to grade is provided for dwelling are exempt)? Congregate housing/dormitories
with 17+ people? High-rise structure (55+ feet to highest occupied floor level)? Architectural Plan (PR200-PR285)
6. Installation/modification of locks delaying or preventing occupants from leaving a space or requiring use of a card,
button, or similar action to open a door in the direction of exit travel? Architectural, Sprinkler, and/or Alarm Plan
depending on the occupancy and type of device installed (PR200-PR280, PR420-PR425, PR500-PR520)
7. Installation/modification/use of spray booths; dust collection; dry cleaning; industrial ovens/drying equipment;
industrial/commercial refrigeration systems; compressed gasses; tanks for cryogenic or flammable/combustible
liquids; vapor recovery; smoke control; battery back-up/charging systems (> 50 gal. electrolyte, > 1,000 lb. lithium
ion); welding/brazing/soldering, open flame torches, cutting/grinding; or other similar operations?
Special Equipment Plan (PR315, PR340-PR382)
8. Storage/use/research with flammable/combustible liquids or other chemicals? Motor vehicle/aircraft
maintenance/repair? Cabinetry/woodworking/finishing facility? Chem Class & floor plan (full architectural plan if
H occupancy); Special Equipment Plans may be necessary. (PR315-PR360, PR232-PR240)
9. Storage or merchandizing areas in excess of 500 sq. ft. where items are located higher than 12’ (6’ for high-hazard
commodities, plastic, rubber, foam, etc.)? High-piled Storage Plan (PR330)
10. Cooking under a Type I commercial hood; installation or modification of a fire extinguishing system located in a
commercial cooking hood? Hood & Duct Extinguishing System, not just the hood mechanical plan. (PR335)
Initial each of the following two items indicating that you have read and understand the statement:
11.*Sprinklers/Alarms: Consult Building/Fire Codes and ordinances to determine sprinkler/alarm requirements; if a system is
required, plans shall be submitted for OCFA review. Existing buildings undergoing remodel must be evaluated by a licensed
Initials contractor to determine if modification is needed; if so, contractor shall submit plans prior to making modifications.
12. Fire Hazard Severity Zone: Consult maps available at building department or on OCFA website to determine if your site is located
in a FHSZ. Buildings in a FHSZ may be subject to special construction requirements detailed in CBC Chapter 7A or CRC R327—
Initials the building department will determine specific requirements.
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name Signature
Phone Number ( )Date / /
Building Department: If you have verified that all of the questions have been answered accurately as “NO”, and the project does not otherwise require OCFA
review of sprinkler or alarm plans*, then you may accept this signed form as a written release that OCFA review is not required. Should you still require that the
applicant have plans approved by OCFA, please initial here or attach an OCFA referral form and have the applicant submit the form along with the
appropriate plans and fees for OCFA review. 10-08-14 EE
COM
2915 W. La Verne Ave.
8 264
O R A N G E C O U N T Y F I R E A U T H O R I T Y
Plan Referral Form
Required for OCFA to review plans upon the request of the Building Department when
the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”.
City / County Official Requesting Review:
City / County Reference #: Date: __________________________________
City / County: _____________________________________ E-Mail: __________________________________
Contact Name: _____________________________________ Phone #: _________________________________
Title: _____________________________________
** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. **
Reason(s) for Review:
Please describe why OCFA Plan Review is or may be required by the City/County :
OCFA COMMENTS:
No further action required on this specific plan type, based
on information provided on: ____/______/______.
Project to be taken in for OCFA Review.
Other:
Name: _________________________________________
Contact #: ______________________________________ Date: _________________________________
Updated: 06/02/2020 rs
1C3
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
EXISTING EQUIPMENT PLAN
SCALE: 3/8" = 1'-0"
NORTH
NOTE:
THE POWER DESIGN FOR ANY AC ELECTRICAL POWER CHANGES IS TO BE
PERFORMED BY OTHERS AND IS SHOWN HERE FOR REFERENCE PURPOSES
ONLY. T-MOBILE IS SOLELY RESPONSIBLE FOR THE ELECTRICAL POWER DESIGN.
NOTES:
·REMOVE THE (12) EXISTING VALVE-REGULATED LEAD-ACID BATTERIES IN THE EXISTING B160 BATTERY CABINET.
·INSTALL (8) NEW ERICSSON 6624 LITHIUM-ION BATTERIES IN THE EXISTING B160 BATTERY CABINET.
EXISTING & NEW
EQUIPMENT PLANS
NOTE:
ESS IS COMPLIANT WITH CFC 1207.5.1
FOR SIZE AND SEPARATION.
4'
-
8
"
3'
-
6
"
6"
11
'
-
0
"
2'
-
9
"
7"
2"
3'-11"
(E)
T-MOBILE
6160
RADIO
CABINET
(E)
T-MOBILE
B160
BATTERY
CABINET
(E) T-MOBILE
19'-4" x 2'-11"
RAISED EQUIPMENT
PAD
(E) T-MOBILE
GPS ANTENNA
(E) T-MOBILE
PPC CABINET
(E) T-MOBILE
EQUIPMENT
(E) T-MOBILE
FIRE EXTINGUISHER
(E) T-MOBILE
METER W/ DISCONNECT
(E) ACCESS
GATE
(E) T-MOBILE
CIENA (TYP)
(E) T-MOBILE
TELCO CABINET
(E) CMU WALL
10' SETBACK
FROM BATTERY
CABINET
EXISTING (12) T-MOBILE
VALVE-REGULATED
LEAD-ACID (VRLA)
BATTERIES TO BE
REPLACED (12 TOTAL)
(E) T-MOBILE
TELCO CABINET
(E) T-MOBILE
SECURITY CAGE OVER
THE COMPOUND
(E) CHAINLINK FENCE
NEW EQUIPMENT PLAN
SCALE: 3/8" = 1'-0"
(P) ERICSSON 6624
LITHIUM-ION
BATTERIES (8 TOTAL)
2'-10"
(E) T-MOBILE
CONCRETE SURFACE
(E) T-MOBILE
UTILITY FRAME
(E) T-MOBILE
SERVICE LIGHT (TYP)
(E) T-MOBILE
EQUIPMENT
NORTH
4'
-
8
"
3'
-
6
"
6"
11
'
-
0
"
2'
-
9
"
7"
2"
3'-11"
(E)
T-MOBILE
6160
RADIO
CABINET
(E)
T-MOBILE
B160
BATTERY
CABINET
(E) T-MOBILE
19'-4" x 2'-11"
RAISED EQUIPMENT
PAD
(E) T-MOBILE
GPS ANTENNA
(E) T-MOBILE
PPC CABINET
(E) T-MOBILE
EQUIPMENT
(E) T-MOBILE
FIRE EXTINGUISHER
(E) T-MOBILE
METER W/ DISCONNECT
(E) ACCESS
GATE
(E) T-MOBILE
CIENA (TYP)
(E) T-MOBILE
TELCO CABINET
(E) CMU WALL
10' SETBACK
FROM BATTERY
CABINET
(E) T-MOBILE
TELCO CABINET
(E) T-MOBILE
SECURITY CAGE OVER
THE COMPOUND
(E) CHAINLINK FENCE
2'-10"
(E) T-MOBILE
CONCRETE SURFACE
(E) T-MOBILE
UTILITY FRAME
(E) T-MOBILE
SERVICE LIGHT (TYP)
(E) T-MOBILE
EQUIPMENT
BATTERY LOADING IN EXISTING BATTERY CABINET:
·(12) EXISTING LEAD-ACID BATTERIES = 12 * (123 lb) = 1476 lb
·(8) NEW LITHIUM-ION BATTERIES = 8 * (91 lb) = 728 lb
·THE PROPOSED LOADING IS 49% OF THE EXISTING
LOADING THEREFORE THE EXISTING BATTERY CABINET IS
ADEQUATE
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------
1C4
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
BATTERY SPECS
NOTES:
1.BATTERY TERMINALS - ELECTRICAL CONNECTION BETWEEN CELLS ON SEPARATE
LEVELS OR RACKS SHALL NOT PUT MECHANICAL STRAIN ON THE BATTERY TERMINALS.
2.VENTS - EACH VENT CELL SHALL BE EQUIPPED WITH A FLAME ARRESTOR.
3.SEALED CELLS - WHERE A BATTERY IS CONSTRUCTED SUCH THAT EXCESSIVE
ACCUMULATION OF PRESSURE COULD OCCUR WITHIN THE CELL DURING OPERATION, A
PRESSURE RELIEF VENT SHALL BE PROVIDED.
4.VENTILATION - PROVISION APPROPRIATE TO THE BATTERY'S TECHNOLOGY SHALL BE
MADE FOR SUFFICIENT DIFFUSION AND VENTILATION AND GASSES FROM THE BATTERY,
IF PRESENT, TO PREVENT THE ACCUMULATION OF AN EXPLOSIVE MIXTURE.
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------
1C5
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
BATTERY DETAILS
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------
1C5A
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
BATTERY DETAILS
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------
1C6
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ESS DETAILS
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------
1C7
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ESS DETAILS
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------
1C8
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
ESS DETAILS
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------
1E1
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
PANEL SCHEDULE &
ONE-LINE DIAGRAM
PANEL SCHEDULE, TABLE 1207.1.1 & BATTERY CALCULATIONS
NOT TO SCALE
ESS IS LOCATED OUTDOORS ON AN
EQUIPMENT PAD. ESS IS NOT
LOCATED IN A HABITABLE AREA.
NOTES
·DISCONNECTS (CBS) INSIDE THE B160 CABINET
PER INDIVIDUAL BATTERY STRING - ALL ARE
EXISTING AND TO BE RE-USED.
·ESS IS DC, NOT AC, THEREFORE IT SHOULD NOT BE
INCLUDED IN THE MAINS LOAD CALCULATION.
ESS/B160 IS CHARGED BY THE 6160 ALREADY IN
THE LOAD TABLE.
OVERVIEW OF BMS OPERATION
IN BATTERY ENERGY STORAGE SYSTEMS, ONE OF THE MOST IMPORTANT HAZARD
BARRIERS HELPING TO ENSURE SAFETY IS THE BATTERY MANAGEMENT SYSTEM
(BMS). THE BMS PROVIDES PRIMARY THERMAL RUNAWAY PROTECTION BY
ENSURING THAT THE BATTERY SYSTEM OPERATES WITHIN A SAFE RANGE OF
PARAMETERS SUCH AS ITS STATE OF CHARGE AND TEMPERATURE.
IN A UL 9540 LISTED BATTERY ENERGY STORAGE SYSTEM, THE BMS MONITORS,
CONTROLS AND OPTIMIZES THE PERFORMANCE OF BATTERY MODULES AND
DISCONNECTS THEM FROM THE SYSTEM IN THE EVENT OF ABNORMAL CONDITIONS.
THE BMS ALSO PROVIDES CHARGE AND DISCHARGE MANAGEMENT OF THE
BATTERIES.
IN CASE OF UNDERVOLTAGE OR OVERVOLTAGE, OVER-TEMPERATURE, OR
OVERCURRENT CONDITIONS, THE BMS WILL ALARM AND THEN LIMIT THE CHARGE
AND DISCHARGE CURRENT OR POWER.
UNDER EMERGENCY CONDITIONS, THE BMS WILL CEASE OPERATIONS AND
ELECTRICALLY DISCONNECT THE BATTERY.
***NEW BATTERIES ARE TO BE INSTALLED IN THE EXISTING BATTERY CABINET. EXISTING CABINET IS NOT BEING REMOVED FOR THIS SCOPE.***
ONE-LINE DIAGRAM
NOT TO SCALE
(E) 6160
RADIO
CABINET
(E)
2P
100A
(E) 120/240, DISTRIBUTION PANEL
(E)
2P
60A
(E)
1P
20A
(E)
1P
20A
(E)
1P
15A
(E) 120/240, 1Ø, 3W, 200A
(E) PPC CABINET NEAR EQUIPMENT AREA
(E) CONDUIT/
CONDUCTORS
(E) SMARTMETER
(E)
(E)
M
(E) 200A, 240V
POWER SOURCE
(E) CONDUIT/
CONDUCTORS
SU
R
G
E
P
R
O
T
E
C
T
O
R
TE
L
C
O
F
A
N
LI
G
H
T
GF
I
(E) B160
BATTERY
CABINET
(E) 1-1/2" CONDUIT
(2#1 + 1#2 GND) FOR 6160 AND
(1#8 + 1#10 GND) FOR B160
BATTERY CABINET IS LOCATED ON AN OUTDOOR PAD AND IS IN COMPLIANCE WITH CEC 703.1(6)
LABELING EXAMPLE ON ESS INTERNAL DISCONNECT IN ESS
DC ONE-LINE DIAGRAM
ELECTRICAL NOTES:
1. ALL NEW CONDUCTORS TO BE INSTALLED SHALL BE
COPPER. ALL CONDUCTORS SHALL BE THHW, THWN, THWN-2,
XHHW, OR XHHW-2 UNLESS NOTED OTHERWISE.
2. CONTRACTOR IS TO FIELD VERIFY ALL EXISTING ITEMS
SHOWN ON THE ELECTRICAL ONE-LINE DIAGRAM AND NOTIFY
THE ENGINEER OF ANY DISCREPANCIES.
3. ALL GROUNDING AND BONDING PER THE CEG.
4. THE POWER DESIGN FOR ANY ELECTRICAL POWER CHANGE
IS TO BE PERFORMED BY OTHERS AND IS SHOWN HERE FOR
REFERENCE PURPOSES ONLY. T-MOBILE IS SOLELY
RESPONSIBLE FOR THE ELECTRICAL; POWER DESIGN SOW.
5. THE E6160AC SUPPORTS AN EXTERNAL BATTERY CABINET
TO SUPPLY BACKUP DC POWER DURING AN AC MAINS
OUTAGE TO THE RECTIFIERS. THE BATTERY CABLE
TERMINALS AND BREAKERS ARE LOCATED AS SHOWN IN
FIGURE 4. EACH BREAKER IS RATED AT 300A. FOR COPPER
WIRES THAT SUPPORT THIS MUCH CURRENT, IT MUST HAVE
A DIAMETER OF AT LEAST 11.684 MM. IT IS BEST TO LOCATE
THE TWO CABINETS ADJACENT TO EACH OTHER TO MINIMIZE
CABLE LENGTH.
NOTE:
THE SECOND 300A BREAKER CONNECTION BETWEEN E6160AC AND B160 SHOULD BE
INSTALLED. THIS IS TO PREVENT BATTERY BREAKERS FROM TRIPPING DURING A COLD
START SCENARIO WHERE INITIAL CURRENT DRAW MAY TRIP THE BATTERY BREAKER AND
REQUIRE FIELD VISIT TO RESET BREAKER.
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------
1G1
SHEET #:REVISION:
SHEET TITLE:
REV.DATE DESCRIPTION
ISSUED FOR CONSTRUCTION
REVISIONS
APPROVED BY:
CHECKED BY:
DRAWN BY:
CW
MEW
FIN
PROJECT INFORMATION:
IE84827A
2915 WEST LA VERNE AVENUE
SANTA ANA, CA 92704
THE INFORMATION CONTAINED IN THIS
SET OF DOCUMENTS IS PROPRIETARY BY
NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO
THE CLIENT IS STRICTLY PROHIBITED.
1200 CONCORD AVENUE
CONCORD, CA 94520
PREPARED FOR:
RMobileT
0 12/11/25
A&E FIRM:
1355 WINDWARD CONCOURSE, SUITE 410
ALPHARETTA, GA 30005
TEL: 678-990-2338
ISSUED FOR CONSTRUCTION101/13/26
WIRE SIZE BURNDY LUG
TYPE HS TYPE 2-YA-2 TYPE XA TYPE YA-2 TYPE GY
#6 AWG GREEN INSULATED
#2 AWG SOLID TINNED
#2 AWG STRANDED
#2/0 AWG STRANDED
#4/0 AWG STRANDED
TYPE VV TYPE VN TYPE NC TYPE SS TYPE GR
YA6C-2TC38
YA3C-2TC38
YA2C-2TC38
YA26-2TC38
YA28-2N
BURNDY GROUND LUG W/
LONG BARREL
(SEE CHART)
NUT
(TYP)
LOCK WASHER
(TYP)
TYPE VS
BURNDY TWO HOLE LUG W/
LONG BARREL
(SEE CHART)
BARE WIRE TO BE
NO-OX AT BOTH ENDS
STRANDED (GREEN INSULATED) ONLY FOR #6 AWG
(SEE CHART)
TYPE VB TYPE PT TYPE GT²
BOLT SIZE
1/2" - 16 NC S 2 BOLT
3/8" - 16 NC S 2 BOLT
3/8" - 16 NC S 2 BOLT
3/8" - 16 NC S 2 BOLT
3/8" - 16 NC S 2 BOLT
HEAT SHRINK
(CLEAR)
GROUNDING
CONDUCTOR
GROUND BAR BOLT
(SEE CHART)
(TYP)
STAINLESS STEEL BOLT
(TYP)
2-HOLE CRIMP/
COMPRESSION
CONNECTOR
STAINLESS STEEL
FLAT WASHER
(TYP)
GROUND
BAR
STAINLESS STEEL
BELLVILLE WASHER
(TYP)
STAINLESS STEEL
FLAT WASHER
(TYP)
STAINLESS STEEL NUT
(TYP)
STAINLESS STEEL BOLT
STAINLESS STEEL
FLAT WASHER
DRAGON TOOTH WASHER
(TYP)
STEEL
3/8-11x1" TAMPER
RESISTANT BOLT
(TYP)
INSULATORS
SEE NOTE 2.
(TYP)
WALL BRACKET
(TYP)
2-HOLE CRIMP/
COMPRESSION
CONNECTOR
STAINLESS STEEL
BELLVILLE WASHER
(TYP)
STAINLESS STEEL
FLAT WASHER
(TYP)
STAINLESS STEEL NUT
(TYP)
STAINLESS STEEL
SELF-DRILLING
METAL SCREW
(TYP)
UNIVERSAL COPPER
GROUND BAR (4"x20")
LOCK WASHER
P/N M10
(TYP)
TW0-HOLE
COMPRESSION LUG
2-HOLE CRIMP/
COMPRESSION
CONNECTOR
DRAGON TOOTH
WASHER
(TYP)
METALLIC OBJECT
STAINLESS STEEL
FLAT WASHER
(TYP)
NOTE: MINIMUM OF
3 THREADS TO BE
VISIBLE
(TYP)
2 HOLE LONG
BARREL TINNED
SOLID COPPER
LUG
(TYP)
S/S NUT
(TYP)
S/S SPLIT
WASHER
(TYP)
S/S FLAT
WASHER
(TYP)
TIN COATED SOLID
COPPER BUS BAR
CHERRY INSULATOR
INSTALLED IF REQUIRED
S/S FLAT
WASHER
(TYP)
S/S BOLT
(TYP)
NOTE:
1. ERICO EXOTHERMIC "MOLD TYPES" SHOWN HERE ARE EXAMPLES. CONSULT WITH CONSTRUCTION MANAGER
FOR SPECIFIC MOLDS TO BE USED FOR THIS PROJECT.
2. MOLD TYPE ONLY TO BE USED BELOW GRADE WHEN CONNECTING GROUND RING TO GROUND ROD.
CADWELD GROUNDING CONNECTIONS
NOT TO SCALE
SIGNAGE
NOT TO SCALE
NOTES:
1. ALL GROUNDING LUGS ARE TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. ALL
HARDWARE BOLTS, NUTS, LOCK WASHERS SHALL BE STAINLESS STEEL. ALL HARDWARE
ARE TO BE AS FOLLOWS: BOLT, FLAT WASHER,GROUND BAR, GROUND LUG, FLAT WASHER
AND NUT.
MECHANICAL LUG CONNECTION
NOT TO SCALE
LUG DETAIL
NOT TO SCALE
SINGLE CONNECTOR AT METALLIC/STEEL OBJECTS
SINGLE CONNECTOR AT STEEL OBJECTS
SINGLE CONNECTOR AT GROUND BARS
HARDWARE DETAIL (EXTERIOR CONNECTIONS)
NOT TO SCALE
NOTES:
1. DOWN LEAD (HOME RUN) CONDUCTORS ARE NOT TO BE INSTALLED ON CROWN CASTLE
USA INC. TOWER, PER THE GROUNDING DOWN CONDUCTOR POLICY QAS-STD-10091. NO
MODIFICATION OR DRILLING TO TOWER STEEL IS ALLOWED IN ANY FORM OR FASHION,
CAD-WELDING ON THE TOWER AND/OR IN THE AIR IS NOT PERMITTED.
2. OMIT INSULATOR WHEN MOUNTING TO TOWER STEEL OR PLATFORM STEEL
USE INSULATORS WHEN ATTACHING TO BUILDINGS OR SHELTERS.
GROUND BAR DETAIL
NOT TO SCALE
GROUNDING DETAILS
01/13/26
s<s<.J-b.J-b,,.a=,,.a=--------