HomeMy WebLinkAbout816 N Figueroa St Bldg A-D - REV 1 - PlanLEGEND AND ABBREVIATIONS
DISCLAIMER: PLEASE NOTE THAT THE ABBREVIATIONS, ANNOTATIONS, AND SYMBOLS LISTED ARE
INTENDED TO ILLUSTRATE THOSE THAT ARE COMMONLY USED; NOT ALL ARE NECESSARILY
UTILIZED WITHIN THIS SET OF DRAWINGS.
ATTIC VENT
FLUSH ATTIC VENT
PVC PIPE VENT
SATELLITE DISH
T-VENT
CHIMNEY
FIRE SETBACKS
METAL PIPE VENT
HARDSCAPE
PROPERTY LINEPL
MAIN PANEL & SUB
PANELS
INVERTER(S) WITH
INTEGRATED DC
DISCONNECT AND AFCI
GENERAL LOCATION OF
EQUIPMENT
METER SOCKET &
DISCONNECTS
PV LOAD CENTER
BESS
(IF APPLICABLE)
GENERAL NOTES
VICINITY MAP
AMPERE
ALTERNATING CURRENT
AC DISCONNECT
AMERICANS WITH DISABILITIES ACT
AVAILABLE FAULT CURRENT
AMERICAN SOCIETY FOR TESTING AND MATERIALS
BATTERY ENERGY STORAGE SYSTEM
BUILDING
CLEAR
CARPORT, NEW
CONCRETE
CONDITIONS OF USE
CARPORT, RETROFIT
DIRECT CURRENT
DIAMETER
DISTANCE
EQUAL
EQUIPMENT GROUNDING CONDUCTOR
EXISTING
EACH
ELECTRICAL METALLIC TUBING
GALVANIZED
GROUNDING ELECTRODE CONDUCTOR
GROUND
HOT DIPPED GALVANIZED
CURRENT
CURRENT AT MAX POWER
INVERTERS
SHORT CIRCUIT CURRENT
KILOVOLT AMPERE
KILOWATT
KILOWATT-HOUR
LOAD BEARING WALL
MAXIMUM
MINIMUM
NEW
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OVERCURRENT PROTECTION
POWER CONTROL SYSTEM
PROPERTY LINES
PHOTOVOLTAIC
POLYVINYL CHLORIDE
ROOF, BALLAST
ROOF, FLUSH MOUNT
SCHEDULE
SQUARE INCHES
STAINLESS STEEL
SEE STRUCTURAL DRAWINGS
STANDARD TESTING CONDITIONS
TYPICAL
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
VERIFY IN FIELD
VOLT
VOLTAGE AT MAX POWER
VOLTAGE AT OPEN CIRCUIT
WATT
NEMA 3R, RAINTIGHT
A
AC
ACDS
ADA
AFC
ASTM
BESS
BLDG
CLR
CN
CONC
C.O.U
CR
DC
DIA
DIST
EQ
EGC
(E)
EA.
EMT
GALV
GEC
GND
HDG
I
Imp
INVS
Isc
kVA
kW
kWh
LBW
MAX
MIN
(N)
NEC
NIC
NTS
OC
OCP
PCS
PL
PV
PVC
RB
RF
SCH
SQ. IN.
SS
SSD
STC
TYP
UON
UPS
VIF
V
Vmp
Voc
W
3R
ABBREVIATIONS
DESIGN WIND SPEED: 95 MPH
EXPOSURE: B
SNOWLOAD: 0 PSF
WEATHER STATION: POLARIS DATA
DESIGN LOW TEMP: -2°C
2% DRY BULB: 38°C
SDS: 1.058
MOUNTING PLANE HEIGHT(S): 30 FT
BUILDING STORIES: 3
CONSTRUCTION TYPE: V
OCCUPANCY GROUP: R-2
AUTOMATIC FIRE SPRINKLERS: No
PROJECT INFORMATION
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
AERIAL MAP
SITE NOTES:
·A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.
·THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
·THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS.
·PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
·ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S
INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.
·NO CHANGE TO PARKING OR STRIPING
·PV MODULES ARE TYPE I FIRE RATED AND THE CARPORT STRUCTURE IS OPEN AIR AND NON-HABITABLE.
EQUIPMENT LOCATIONS:
·ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
·WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND
NEC TABLES 310.15 (B)(1) AND 310.15 (B)(2) IF RACEWAYS ARE < 7/8" ABOVE THE ROOF.
·JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC 690.34.
·ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT.
·ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC APPLICABLE CODES.
·ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE.
STRUCTURAL NOTES:
·RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE
BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL
MANUFACTURER’S INSTRUCTIONS.
·JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL
REQUIREMENTS.
·ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED
CONTRACTOR.
·ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.
·WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS.
DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
·DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO
THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).
·DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH.
·DC DISCONNECT INTEGRATED INTO ROOFTOP DC COMBINER OR INSTALLED WITHIN 6 FT, ACCORDING TO NEC 690.15(B).
·ALL PV CIRCUITS LOCATED OUTSIDE THE ARRAY BOUNDARY OR MORE THAN 3 FT FROM THE POINT OF ENTRY INSIDE A BUILDING SHALL BE LIMITED TO NOT
MORE THAN 30 VOLTS WITHIN 30 SECONDS, CIRCUITS INSIDE THE ARRAY BOUNDARY OR NOT MORE THAN 3 FT FROM THE POINT OF PENETRATION SHALL BE
LIMITED TO NOT MORE THAN 80 VOLTS UPON RAPID SHUT-DOWN INITIATION PER 690.12.
·ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.
WIRING & CONDUIT NOTES:
·ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.
·CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
·ALL CONDUIT MUST ACCOUNT FOR ENVIRONMENTAL CONDITIONS AND THERMAL EXPANSIONS ACCORDING TO NEC 300.7.
·PV WIRE BLACK WIRE MAY BE FIELD-MARKED BY MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATE COLOR CODING, MARKING TAPE,
TAGGING, OR OTHER APPROVED MEANS.
·MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.
·RACKING, MID CLIPS, END CLIPS, AND MODULES UL2703 LISTED
·ACCORDING TO NEC 200.7, SYSTEMS DC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
···DC POSITIVE- RED, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN
···DC NEGATIVE- BLACK, OR ANY COLOR EXCLUDING WHITE, GRAY AND GREEN
·AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
···PHASE A OR L1- BLACK
···PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE
···PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION
···NEUTRAL- WHITE OR GRAY
*IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [NEC 110.15].
CODES AND STANDARDS
SHEET INDEXBILL OF MATERIALS
MODULES:
(537) QCELLS NORTH AMERICA Q.PEAK DUO BLK ML-G10.C+ 410
OPTIMIZERS:
(537) SOLAREDGE U650
INVERTERS:
(12) SOLAREDGE SE11400H-US HOME HUB [208V] [SI1-SB] [CRD-PCS NEM]
(3) SOLAREDGE SE10KUS [208V] [SI1-SB]
(1) SOLAREDGE SE17.3KUS [208V] [SI1-SB]
MONITORING:
(12) CELL-B-R05-US-S-S2
(4) CELL-B-R05-US-S-S4
BESS:
(36) SOLAREDGE BAT-10K1P
(12) SOLAREDGE HOME NET CARD
RACKING:
FLUSH ROOF: TILE ROOF HOOK S
NEW PV AND ENERGY STORAGE SYSTEM:
ON ROOF
PV SYSTEM: 220.17 DCkW, 160 ACkW, 203.27 CEC ACkW
ENERGY STORAGE SYSTEM: 120 ACkW, 349.2 kWH
ANDALUCIA
816 N FIGUEROA ST, SANTA ANA, CA 92703, USA, BLDG A, B, C, & D
APN #: 198-162-03, 198-162-44, 198-162-52
BUILDING: IBC 2024
LOCAL BUILDING: CBC 2025
OCCUPANCY GROUP: R-2
ELECTRICAL: NEC 2023
LOCAL ELECTRICAL: CEC 2025
FIRE: CFC 2025
AHJ: CA-CITY SANTA ANA
UTILITY: SCE
C100 : COVERSHEET
E100 : ELECTRICAL SITE PLAN
E200 : ELECTRICAL PLAN VIEWS
E201 : ELECTRICAL PLAN VIEWS
E300 : ELECTRICAL STRINGING
E301 : ELECTRICAL STRINGING
E400 : ELECTRICAL DETAILS
E401 : ELECTRICAL DETAILS
E500 : ELECTRICAL NOTES
E600 : ONELINE DIAGRAM POI-1
E601 : ONELINE DIAGRAM POI-2
E602 : ONELINE DIAGRAM POI-3
E603 : ONELINE DIAGRAM POI-4
E800 : WARNING LABELS
E801 : WARNING LABELS
E810 : SITE PLACARDS
S100 : STRUCTURAL SITE PLAN
S200 : STRUCTURAL ARRAY DETAIL
S201 : STRUCTURAL ARRAY DETAIL
S202 : STRUCTURAL ARRAY DETAIL
S203 : STRUCTURAL ARRAY DETAIL
S300 : STRUCTURAL SIDE SECTIONS
S400 : STRUCTURAL ATTACHMENT DETAILS
S500 : EQUIPMENT PAD
R100 : REFERENCE SHEETS
R101 : REFERENCE SHEETS
R102 : REFERENCE SHEETS
R103 : REFERENCE SHEETS
R104 : REFERENCE SHEETS
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
COVER SHEET
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
C100
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
PL PL PL PL PL PL PL PL PL PL PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PLPLPLPLPLPLPLPLPLPL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
BLDG A
BLDG C
BLDG B
BLDG D
PO
I
PO
I
PO
I
PO
I
POI
PO
I
PO
I
PO
I
PO
I
POI
PO
I
PO
I
PO
I
POIPOI
PO
I
PO
I
PO
I
POI POI
PO
I
PO
I
PO
I
PO
I
POI
PO
I
PO
I
PO
I
PO
I
POI
PO
I
POIPOIPOIPOI
PO
I
POI POI POI POI
(E) SOLAR
THERMAL
RF01
TL: 18° AZ: 180°
RF02
TL: 18° AZ: 270°
RF03
TL: 18° AZ: 90°
RF04
TL: 18° AZ: 90°
RF05
TL: 18° AZ: 270°
RF06
TL: 18° AZ: 90°
RF07
TL: 18° AZ: 270°
RF08
TL: 18° AZ: 90°
RF09
TL: 18° AZ: 270°
RF10
TL: 18° AZ: 270°
RF11
TL: 18° AZ: 360°
RF12
TL: 18° AZ: 90°
RF13
TL: 18° AZ: 270°
RF14
TL: 18° AZ: 180°
RF15
TL: 18° AZ: 360°
RF16
TL: 18° AZ: 180°
RF17
TL: 18° AZ: 360°
RF18
TL: 18° AZ: 360°
RF19
TL: 18° AZ: 180°
RF20
TL: 18° AZ: 180°
RF21
TL: 18° AZ: 360°
RF22
TL: 18° AZ: 360°
RF23
TL: 18° AZ: 180°
RF24
TL: 18° AZ: 180°
RF25
TL: 18° AZ: 360°
RF26
TL: 18° AZ: 360°
RF27
TL: 18° AZ: 90°
RF28
TL: 18° AZ: 360°
RF29
TL: 18° AZ: 270°
RF30
TL: 18° AZ: 90°
RF31
TL: 18° AZ: 270°
RF32
TL: 18° AZ: 90°
RF33
TL: 18° AZ: 270°
RF34
TL: 18° AZ: 90°
RF35
TL: 18° AZ: 270°
RF36
TL: 18° AZ: 90°
RF37
TL: 18° AZ: 270°
RF38
TL: 18° AZ: 180°RF39
TL: 18° AZ: 90°
RF40
TL: 18° AZ: 180°
RF41
TL: 18° AZ: 270°
RF42
TL: 18° AZ: 90°
RF43
TL: 18° AZ: 270°RF44
TL: 18° AZ: 90°
RF45
TL: 18° AZ: 270°
RF46
TL: 18° AZ: 90°
RF47
TL: 18° AZ: 270°RF48
TL: 18° AZ: 90°
RF49
TL: 18° AZ: 270°
RF50
TL: 18° AZ: 90°
RF51
TL: 18° AZ: 270°RF52
TL: 18° AZ: 90°
RF53
TL: 18° AZ: 90°
RF54
TL: 18° AZ: 270°
RF55
TL: 18° AZ: 360°
HAZARD AVE
N
F
I
G
U
E
R
O
A
S
T
N
H
A
R
B
O
R
B
L
V
D
FIRE SETBACKS
(18" TYP)
816 N FIGUEROA ST,
BLDG B, SANTA ANA,
CA 92703, USA
APN #: 198-162-03,
198-162-44,
198-162-52
ROOF PATHWAYS (3' TYP)
S200
A
S201
A
S202
A
S203
A
(E) SOLAR
THERMAL
(E) SOLAR
THERMAL
(E) SOLAR
THERMAL
816 N FIGUEROA ST,
BLDG D, SANTA ANA,
CA 92703, USA
816 N FIGUEROA ST,
BLDG A, SANTA ANA,
CA 92703, USA
816 N FIGUEROA ST,
BLDG C, SANTA ANA,
CA 92703, USA
(N) SOLAR CANOPY
STRUCTURAL COLUMN
DOWN SLOPE
FLUSH FOOTING
RAIL
LEGEND
ATTIC VENT
FLUSH ATTIC VENT
PVC PIPE VENT
SATELLITE DISH
T-VENT
CHIMNEY
FIRE SETBACKS
METAL PIPE VENT
HARDSCAPE
PROPERTY LINEPL
PITCH
2°
X
XX
DETAIL CUT
SHEET NUMBER
X
XX
SECTION CUT
SHEET NUMBER
GENERAL NOTES
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
·ALL WORK SHALL COMPLY WITH ALL STATE AND
LOCAL CODES AND ANY OTHER REGULATING
AUTHORITIES WHICH HAVE AUTHORITY OVER
ANY PORTION OF THE WORK.
·DRAWINGS HAVE BEEN DETAILED IN
COMPLIANCE WITH UL LISTING REQUIREMENTS,
OSFM SOLAR PHOTOVOLTAIC INSTALLATION
REQUIREMENTS, AND BUILDING CODES FOR
THE MATERIALS SPECIFIED. PRIOR TO
COMMENCEMENT OF ANY WORK, THE
CONTRACTOR SHALL VERIFY EXISTING
CONDITIONS AND NOTIFY THE DESIGN
PROFESSIONAL IN RESPONSIBLE CHARGE
FROM SUNRUN OF ANY DISCREPANCIES. ANY
WORK PERFORMED IN CONFLICT WITH THE
CONTRACT DOCUMENTS SHALL BE CORRECTED
AT THE SUBCONTRACTORS SOLE EXPENSE.
·SUBCONTRACTOR INITIATED CHANGES SHALL
BE SUBMITTED IN WRITING TO SUNRUN FOR
APPROVAL BEFORE MAKING ANY CHANGES OR
DEVIATION FROM PLANS BEFORE WRITTEN
APPROVAL FROM SUNRUN PLACES LIABILITY
ON THE SUBCONTRACTOR.
·ALL EQUIPMENT SHALL BE MOUNTED AS
SHOWN. WHERE DETAILS ARE NOT PROVIDED,
CONTRACTOR SHALL USE STANDARD
CONSTRUCTION PRACTICES.
·ALL SURFACES SHALL BE PATCHED AND
PAINTED AROUND NEW DEVICES AND
EQUIPMENT TO MATCH EXISTING FINISHES.
ANY METAL SHAVINGS FROM SITE WORK SHALL
BE CLEANED FROM ALL SURFACES WHERE
OXIDIZED OR CONDUCTIVE METAL SHAVINGS
MY CAUSE RUST, ELECTRICAL SHORT CIRCUITS,
OR OTHER DAMAGE.
·BEAMS OR PURLINS SHALL NOT BE DRILLED
UNLESS AUTHORIZED OR SHOWN IN THE
DRAWINGS.
·APPROVALS FROM BUILDING INSPECTORS
SHALL NOT CONSTITUTE AUTHORITY TO
DEVIATE FROM THE DRAWINGS.
·NO CHANGE TO PARKING OR STRIPING LAYOUT.
·IT IS THE RESPONSIBILITY OF THE INSTALLER
TO ENSURE THAT RACKING SYSTEMS ARE
BUILT PER THE INSTALLATION MANUAL AND
MEET ALL LOCAL BUILDING CODES. IT IS ALSO
THE RESPONSIBILITY OF THE INSTALLER TO
CHECK THE BUILDING FOR STRUCTURAL
ADEQUACY AND MAKE THE FINAL
DETERMINATION ON CONTINUOUS ARRAY
LENGTH TO ACCOUNT FOR THERMAL
EXPANSION AND CONTRACTION OF THE
SYSTEM.
·FOR BALLASTED RACKING THE CONTRACTOR
SHALL FIELD VERIFY THE ROOF IS SLOPED AT
1/4" PER FOOT OR MORE TO LIMIT EFFECTS OF
PONDING. IF ROOF SLOPE IS LESS THAN 1/4"
PER FOOT, THE CONTRACTOR SHALL NOTIFY
THE SEOR AND/OR SUNRUN PRIOR TO MOVING
FORWARD WITH CONSTRUCTION.
CARPORT FOOTING
XX##
TL: ##° AZ: ###°
ROOF IDENTIFIER
MOUNTING INDEX
MOUNTING TYPE
TILT
AZUMUTH
ROOF FRAMING
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
STRUCTURAL PLAN
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
S100
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
SCALE: 1" = 20'
IFC SECTION 1205.2 ACCESS
PATHWAYS
BLDG
NUMBER
PLAN VIEW
AREA (sqft)
MODULE
COUNT
COVERAGE
(%)
A 8389.7 132 34.2%
B 8276.8 117 30.7%
C 10827.6 125 25.1%
D 11091.2 163 31.9%
Totals 38585 537
(N) SOLAR CANOPY
STRUCTURAL COLUMN
LEGEND
ATTIC VENT
FLUSH ATTIC VENT
PVC PIPE VENT
SATELLITE DISH
T-VENT
CHIMNEY
FIRE SETBACKS
METAL PIPE VENT
HARDSCAPE
PROPERTY LINEPL
CLAMPING ZONES
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
XX##
TL: ##° AZ: ###°
MOUNTING INDEX
MOUNTING TYPE
TILT
AZUMUTH
DOWN SLOPE
FLUSH FOOTING
RAIL
PITCH
2°
CARPORT FOOTING
QCELL NORTH AMERICA
Q.PEAK DUO BLK ML-G10.C+ 410
[DCC] LANDSCAPE CLAMP ZONE
0.79" TO 7.87"
0.8
18.9
19.7
QCELL NORTH AMERICA
Q.PEAK DUO BLK ML-G10.C+ 410
[DCC] PORTRAIT CLAMP ZONE
0.79" TO 19.7"
0.8
7.1
7.9
ROOF FRAMING
ADDITIONAL DETAILS
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED: 95 MPH
LAG SCREWS:
(2)5/16"x3.5": 2.5" MIN EMBEDMENT
NOTE:
INSTALLERS TO VERIFY RAFTER SIZE, SPACING AND
SLOPED SPANS, AND NOTIFY E.O.R. OF ANY
DISCREPANCIES BEFORE PROCEEDING.
ROOF IDENTIFIER
WINDZONES
BLDG A
RF01
TL: 18° AZ: 180°
RF02
TL: 18° AZ: 270°
RF03
TL: 18° AZ: 90°
RF04
TL: 18° AZ: 90°
RF05
TL: 18° AZ: 270°
RF06
TL: 18° AZ: 90°
RF07
TL: 18° AZ: 270°
RF08
TL: 18° AZ: 90°
RF09
TL: 18° AZ: 270°
RF10
TL: 18° AZ: 270°
RF11
TL: 18° AZ: 360°
RF12
TL: 18° AZ: 90°
816 N FIGUEROA ST,
BLDG A, SANTA ANA,
CA 92703, USA
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
STRUCTURAL DETAIL
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
S200
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
SCALE: 3/32" = 1'-0"
BLDG A DETAILS • POI-1A
POI-1 ROOF SCHEDULE
BLDG LABEL RACKING TILT (DEG)AZIMUTH (DEG)BUILDING HEIGHT (FT)MODULE COUNT MODULE AREA (SQFT)KW DC
A RF01 FLUSH MOUNT 18°180°30 13 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]274.6 5.33
A RF02 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
A RF03 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
A RF04 FLUSH MOUNT 18°90°30 12 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]253.5 4.92
A RF05 FLUSH MOUNT 18°270°30 17 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]359.1 6.97
A RF06 FLUSH MOUNT 18°90°30 8 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]169.0 3.28
A RF07 FLUSH MOUNT 18°270°30 8 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]169.0 3.28
A RF08 FLUSH MOUNT 18°90°30 24 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]506.9 9.84
A RF09 FLUSH MOUNT 18°270°30 20 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]422.4 8.20
A RF10 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
A RF11 FLUSH MOUNT 18°360°30 18 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]380.2 7.38
A RF12 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
Totals 132 2788 54
11'-3"
5'
-
6
"
7'
-
1
0
"
7'-9"
12
'
-
6
"
7'-10"
2'-4"
2'
5'
-
1
"
5'-8"
8'
-
3
"
7'
-
1
1
"
5'-8"
13'
-
7
"
12
'
-
3"
2'-6"
1'-9"
11
'
-
7
"
7'-8"
11
'
-
1
0
"
7'-10"
12'-5"
14
'
-
7
"
6'
T
Y
P
ST
A
N
D
O
F
F
SP
A
C
I
N
G
A
S300
14
1
'
-
4
"
60'-7"
(E) SOLAR THERMAL
RE-FAB TRUSS TYP.2X4 @ 24" P
(N) SOLAR CANOPY
STRUCTURAL COLUMN
LEGEND
ATTIC VENT
FLUSH ATTIC VENT
PVC PIPE VENT
SATELLITE DISH
T-VENT
CHIMNEY
FIRE SETBACKS
METAL PIPE VENT
HARDSCAPE
PROPERTY LINEPL
CLAMPING ZONES
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
XX##
TL: ##° AZ: ###°
ROOF IDENTIFIER
MOUNTING INDEX
MOUNTING TYPE
TILT
AZUMUTH
DOWN SLOPE
FLUSH FOOTING
RAIL
PITCH
2°
CARPORT FOOTING
QCELL NORTH AMERICA
Q.PEAK DUO BLK ML-G10.C+ 410
[DCC] LANDSCAPE CLAMP ZONE
0.79" TO 7.87"
0.8
18.9
19.7
QCELL NORTH AMERICA
Q.PEAK DUO BLK ML-G10.C+ 410
[DCC] PORTRAIT CLAMP ZONE
0.79" TO 19.7"
0.8
7.1
7.9
ROOF FRAMING
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED: 95 MPH
LAG SCREWS:
(2) 5/16"x3.5": 2.5" MIN EMBEDMENT
NOTE:
INSTALLERS TO VERIFY RAFTER SIZE, SPACING AND
SLOPED SPANS, AND NOTIFY E.O.R. OF ANY
DISCREPANCIES BEFORE PROCEEDING.
ADDITIONAL DETAILS
WINDZONES
LDG BB
RF28
TL: 18° AZ: 360°
RF29
TL: 18° AZ: 270°
RF30
TL: 18° AZ: 90°
RF31
TL: 18° AZ: 270°
RF32
TL: 18° AZ: 90°
RF33
TL: 18° AZ: 270°
RF34
TL: 18° AZ: 90°
RF35
TL: 18° AZ: 270°
RF36
TL: 18° AZ: 90°
RF37
TL: 18° AZ: 270°
RF38
TL: 18° AZ: 180°RF39
TL: 18° AZ: 90°
RF41
RF43
TL: 18° AZ: 270°
RF45
TL: 18° AZ: 270°
RF47
TL: 18° AZ: 270°
RF49
TL: 18° AZ: 270°
RF51
TL: 18° AZ: 270°
RF54
TL: 18° AZ: 270°
816 N FIGUEROA ST,
BLDG B, SANTA ANA,
CA 92703, USA
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
STRUCTURAL DETAIL
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
S201
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
SCALE: 3/32" = 1'-0"
BLDG B DETAILS • POI-2A
POI-2 ROOF SCHEDULE
BLDG LABEL RACKING TILT (DEG)AZIMUTH (DEG)BUILDING HEIGHT (FT)MODULE COUNT MODULE AREA (SQFT)KW DC
B RF28 FLUSH MOUNT 18°360°30 18 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]380.2 7.38
B RF29 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
B RF30 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
B RF31 FLUSH MOUNT 18°270°30 24 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]506.9 9.84
B RF32 FLUSH MOUNT 18°90°30 19 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]401.3 7.79
B RF33 FLUSH MOUNT 18°270°30 8 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]169.0 3.28
B RF34 FLUSH MOUNT 18°90°30 8 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]169.0 3.28
B RF35 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
B RF36 FLUSH MOUNT 18°90°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
B RF37 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
B RF38 FLUSH MOUNT 18°180°30 13 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]274.6 5.33
B RF39 FLUSH MOUNT 18°90°30 4 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]84.5 1.64
Totals 117 2471 48
11'-5"
8'
-
4
"
11
'
-
5
"
1'-6"
12
'
7'-10"
7'
-
9
"
8'-1"
2'-4"
13
'
-
1
"
9'
6'-2"
3'
-
2
"
6'-6"
1'-7"15
'
-
8
"
9'
-
3
"
6'-5"
17'-2"
9'
-
3
"
11
'
-
8
"
7'-9"
6'
T
YP
ST
A
N
D
OF
F
SP
A
C
ING
A
S300
2X4 @ 24" PRE-FAB TRUSS TYP.
14
2
'
-
5
"
60'-6"
LAR THERMAL(E) SO
(N) SOLAR CANOPY
STRUCTURAL COLUMN
LEGEND
ATTIC VENT
FLUSH ATTIC VENT
PVC PIPE VENT
SATELLITE DISH
T-VENT
CHIMNEY
FIRE SETBACKS
METAL PIPE VENT
HARDSCAPE
PROPERTY LINEPL
CLAMPING ZONES
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
XX##
TL: ##° AZ: ###°
MOUNTING INDEX
MOUNTING TYPE
TILT
AZUMUTH
DOWN SLOPE
FLUSH FOOTING
RAIL
PITCH
2°
CARPORT FOOTING
QCELL NORTH AMERICA
Q.PEAK DUO BLK ML-G10.C+ 410
[DCC] LANDSCAPE CLAMP ZONE
0.79" TO 7.87"
0.8
18.9
19.7
QCELL NORTH AMERICA
Q.PEAK DUO BLK ML-G10.C+ 410
[DCC] PORTRAIT CLAMP ZONE
0.79" TO 19.7"
0.8
7.1
7.9
ROOF FRAMING
ADDITIONAL DETAILS
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED: 95 MPH
LAG SCREWS:
(2) 5/16"x3.5": 2.5" MIN EMBEDMENT
NOTE:
INSTALLERS TO VERIFY RAFTER SIZE, SPACING AND
SLOPED SPANS, AND NOTIFY E.O.R. OF ANY
DISCREPANCIES BEFORE PROCEEDING.
ROOF IDENTIFIER
WINDZONES
BLDG C
RF13
TL: 18° AZ: 270°
RF14
TL: 18° AZ: 180°
RF15
TL: 18° AZ: 360°
RF16
TL: 18° AZ: 180°
RF17
TL: 18° AZ: 360°
RF18
TL: 18° AZ: 360°
RF19
TL: 18° AZ: 180°
RF20
TL: 18° AZ: 180°
RF21
TL: 18° AZ: 360°
RF22
TL: 18° AZ: 360°
RF23
TL: 18° AZ: 180°
RF24
TL: 18° AZ: 180°
RF25
TL: 18° AZ: 360°
RF26
TL: 18° AZ: 360°
RF27
TL: 18° AZ: 90°
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
STRUCTURAL DETAIL
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
S202
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
SCALE: 3/32" = 1'-0"
BLDG C DETAILS • POI-3A
POI-3 ROOF SCHEDULE
BLDG LABEL RACKING TILT (DEG)AZIMUTH (DEG)BUILDING HEIGHT (FT)MODULE COUNT MODULE AREA (SQFT)KW DC
C RF13 FLUSH MOUNT 18°270°30 16 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]337.9 6.56
C RF14 FLUSH MOUNT 18°180°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
C RF15 FLUSH MOUNT 18°360°30 4 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]84.5 1.64
C RF16 FLUSH MOUNT 18°180°30 10 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]211.2 4.10
C RF17 FLUSH MOUNT 18°360°30 13 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]274.6 5.33
C RF18 FLUSH MOUNT 18°360°30 5 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]105.6 2.05
C RF19 FLUSH MOUNT 18°180°30 5 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]105.6 2.05
C RF20 FLUSH MOUNT 18°180°30 9 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]190.1 3.69
C RF21 FLUSH MOUNT 18°360°30 14 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]295.7 5.74
C RF22 FLUSH MOUNT 18°360°30 5 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]105.6 2.05
C RF23 FLUSH MOUNT 18°180°30 5 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]105.6 2.05
C RF24 FLUSH MOUNT 18°180°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
C RF25 FLUSH MOUNT 18°360°30 14 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]295.7 5.74
C RF26 FLUSH MOUNT 18°360°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
C RF27 FLUSH MOUNT 18°90°30 16 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]337.9 6.56
Totals 125 2640 51
14
'
-
3
"
8'-8"
8'-2"
8'
-
1
"
3'-1"
3'
-
4
"
13'-3"
8'
-
8
"
14'-3"3'
-
6
"
13'-11"
6'
-
1
"
9'-6"
6'
-
4
"
8'
-
5
"
16'-10"
15'-8"
4'
6'
-
5
"
7'-11"
5'
-
8
"
14'
7'-7"
3'
-
6
"
8'
-
8
"
13'-1"
8'
-
4
"
8'-8"
11'-6"
8'
-
2
"
6' TYP
STANDOFF
SPACING
A
S300
2X4 @ 24" PRE-FAB
TRUSS TYP.
186'-6"
60
'
-
4
"
(E) SOLAR
THERMAL
(N) SOLAR CANOPY
STRUCTURAL COLUMN
LEGEND
ATTIC VENT
FLUSH ATTIC VENT
PVC PIPE VENT
SATELLITE DISH
T-VENT
CHIMNEY
FIRE SETBACKS
METAL PIPE VENT
HARDSCAPE
PROPERTY LINEPL
CLAMPING ZONES
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
XX##
TL: ##° AZ: ###°
ROOF IDENTIFIER
MOUNTING INDEX
MOUNTING TYPE
TILT
AZUMUTH
DOWN SLOPE
FLUSH FOOTING
RAIL
PITCH
2°
CARPORT FOOTING
QCELL NORTH AMERICA
Q.PEAK DUO BLK ML-G10.C+ 410
[DCC] LANDSCAPE CLAMP ZONE
0.79" TO 7.87"
0.8
18.9
19.7
QCELL NORTH AMERICA
Q.PEAK DUO BLK ML-G10.C+ 410
[DCC] PORTRAIT CLAMP ZONE
0.79" TO 19.7"
0.8
7.1
7.9
ROOF FRAMING
MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 0 PSF
WIND SPEED: 95 MPH
LAG SCREWS:
(2) 5/16"x3.5": 2.5" MIN EMBEDMENT
NOTE:
INSTALLERS TO VERIFY RAFTER SIZE, SPACING AND
SLOPED SPANS, AND NOTIFY E.O.R. OF ANY
DISCREPANCIES BEFORE PROCEEDING.
ADDITIONAL DETAILS
WINDZONES
RF32
TL: 18° AZ: 90°
RF34
TL: 18° AZ: 90°
RF36
TL: 18° AZ: 90°
RF39
TL: 18° AZ: 90°
RF40
TL: 18° AZ: 180°
RF41
TL: 18° AZ: 270°
RF42
TL: 18° AZ: 90°
RF43
TL: 18° AZ: 270°RF44
TL: 18° AZ: 90°
RF45
TL: 18° AZ: 270°
RF46
TL: 18° AZ: 90°
RF47
TL: 18° AZ: 270°RF48
TL: 18° AZ: 90°
RF49
TL: 18° AZ: 270°
RF50
TL: 18° AZ: 90°
RF51
TL: 18° AZ: 270°RF52
TL: 18° AZ: 90°
RF53
TL: 18° AZ: 90°
RF54
TL: 18° AZ: 270°
RF55
TL: 18° AZ: 360°
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
STRUCTURAL DETAIL
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
S203
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
BLDG D
SCALE: 3/32" = 1'-0"
BLDG D DETAILS • POI-4A
POI-4 ROOF SCHEDULE
BLDG LABEL RACKING TILT (DEG)AZIMUTH (DEG)BUILDING HEIGHT (FT)MODULE COUNT MODULE AREA (SQFT)KW DC
D RF40 FLUSH MOUNT 18°180°30 17 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]359.1 6.97
D RF41 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
D RF42 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
D RF43 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF44 FLUSH MOUNT 18°90°30 20 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]422.4 8.20
D RF45 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF46 FLUSH MOUNT 18°90°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF47 FLUSH MOUNT 18°270°30 19 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]401.3 7.79
D RF48 FLUSH MOUNT 18°90°30 18 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]380.2 7.38
D RF49 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF50 FLUSH MOUNT 18°90°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF51 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF52 FLUSH MOUNT 18°90°30 19 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]401.3 7.79
D RF53 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
D RF54 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
D RF55 FLUSH MOUNT 18°360°30 16 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]337.9 6.56
Totals 163 3443 67
12'-9"
8'
-
7
"
8'
-
1
"
7'-10"
12
'
7'-10"
1'-8"
12
'
-
5
"
9'
2'-4"
13
'
-
4
"
6'-4"
6'-3"
8'
-
9
"
1'-10"1'-7"
12
'
-
1
"
14
'
-
5
"
11
'
-
9
"
6'-1"5'-4"
10
'
-
3
"
7'
-
5
"
1'-8"
1'-7"
12
'
-
6
"
14
'
-
1
"
7'-10"
11
'
-
7
"
7'-10"
8'-1"
8'
-
5
"
6'
T
Y
P
ST
A
N
D
O
F
F
SP
A
C
I
N
G
A
S300
2X4 @ 24" PRE-FAB TRUSS TYP.
18
6
'
-
8
"
60'-7"
(E) SOLAR THERMAL
S400
C
30
R
O
O
F
HE
I
G
H
T
(
S
)
SOLAR MODULE
5'-5 1/2" (TYP.)
3'-5 1/2" (TYP.)
3/4"
6 7/8" (TYP.)
(N) TILE ROOF HOOK S ATTACHMENT
A STRUCTURAL SIDE SECTIONS - FLUSH MOUNT
NTS
18°
(E) 2X4 @ 24"
MANUFACTURED
TRUSS
(E) LBW
ATTACHMENT SPECIFICATION
TYPE LANDSCAPE PORTRAIT LAYOUT
MOUNT MAX OC SPACING MAX OVERHANG ¹REDUCED MAX OC
SPACING
¹REDUCED MAX
OVERHANG MAX OC SPACING MAX OVERHANG ¹REDUCED MAX OC
SPACING
¹REDUCED MAX
OVERHANG CONFIGURATION
COMP SHINGLE - UR - ULTRAFOOT 6'-0"2'-4"3'-0"0'-5"6'-0"2'-2"3'-0"0'-5"STACKED
¹REDUCED MAXIMUM SPACINGS AND OVERHANGS APPLY ONLY WITHIN THE ROOF EDGE BOUNDARY REGIONS. SEE DETAIL B/S400
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
STRUCTURAL SIDE SECTIONS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
S300
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
SNAPNRACK ULTRA RAIL TILE ROOF HOOK WS FOR MOUNTING TO W AND S
PROFILE TILE ROOFS
SNAPNRACK ULTRA RAIL
TILE ROOF HOOK WS
S-TILES, TYP.
REFER TO SNAPNRACK ENGINEERING CHARTS FOR APPLICABLE RAIL SPANS.
"BIN" NUMBER ON CHART SHOULD MATCH "BIN" NUMBER ON THIS
DRAWING
MODULE HEIGHT OFF ROOF:
BIN:
7
ROOF SHEATHING, TYP.
SNAPNRACK
ULTRA RAIL
RAFTER OR OTHER STRUCTURAL
ROOF MEMBER, TYP.
TILE BATTEN, TYP.PENETRATION DETAIL
SNAPNRACK
ULTRA RAIL
ROOF SEALANT
SNAPNRACK ULTRA
RAIL MOUNTING
HARDWARE, TYP.
SNAPNRACK ULTRA RAIL
TILE ROOF HOOK WS
STEP 1:
REMOVE TILES TO EXPOSE
ROOF DECKING S-TILES, TYP.
SNAPNRACK ULTRA RAIL
TILE ROOF HOOK WS
ROOF SHEATHING, TYP.
STEP 2:
DRILL 2 QTY. 3/16"Ø PILOT HOLES
INTO
HOOK CAN BE OFFSET FROM
RAFTER UP TO 4" IN EITHER
DIRECTION TO LINE UP WITH
LOW POINT IN S-TILESRAFTER. SEAL ROOF PENETRATIONS
WITH APPROPRIATE SEALANT.
FASTEN BASE TO ROOF WITH 2 QTY.RAFTER OR OTHER STRUCTURAL
ROOF MEMBER, TYP.5/16"Ø LAG SCREWS WITH FLAT WASHERS.
WITH S.S. FLAT WASHERS
5/16"Ø S.S. LAG SCREW MUST EMBED A MIN. OF 2-1/2"
INTO STRUCTURAL MEMBER
5/16"Ø HARDWARE TORQUE SPECIFICATIONS
REFER TO SNAPNRACK INSTALLATION MANUAL FOR
RAILS CAN MOUNT TO EITHER SIDE OF TILE HOOK
(UPSLOPE VS. DOWNSLOPE)
RAILS CAN BE LEVELED UP TO 1-1/4" USING THE SLOT IN
THE TILE HOOK.
UR-40: 6-5/8" TO 7-7/8"
UR-60: 7-1/4" TO 8-1/2"
2-1/2" MIN EMBEDMENT
INTO WOOD RAFTER, TYP.
5/16"Ø S.S. LAG SCREWS WITH
C ULTRA RAIL, TILE ROOF HOOK WS (TYP.)
NTS
UR-40 RAIL | UR-45 RAIL | UR-60 RAIL
FOR USE WITH SNAPNRACK ULTRA SERIES RAILS
2 1 4"
1 1 2"
1 1 2"
1 5 8"1 3
4 "
1 1 2"
2 QTY 5/16"Ø S.S. LAG SCREWS
WITHS.S FLAT WASHERS
B REDUCED SPACING AND OVERHANG DETAIL
NTS
NOTE: IF ARRAY (EXCLUDING SKIRT) IS
WITHIN 12" BOUNDARY REGION OF ANY
ROOF PLANE EDGES (EXCEPT VALLEYS),
THEN ATTACHMENTS NEED TO BE ADDED
AND OVERHANG REDUCED WITHIN THE
12" BOUNDARY REGION ONLY AS
FOLLOWS:
·ALLOWABLE ATTACHMENT SPACING
INDICATED ON PLANS TO BE
REDUCED BY 50% (REFER TO TABLE
ABOVE)
·ALLOWABLE OVERHANG INDICATED
ON PLANS TO BE 1/5TH OF
ALLOWABLE ATTACHMENT SPACING
INDICATED ON PLANS (REFER TO
TABLE ABOVE)
12" BOUNDARY
12" SETBACK DOES
NOT APPLY TO
VALLEYS
48" BOUNDARY
·ALLOWABLE ATTACHMENT
SPACING INDICATED ON PLANS
TO BE REDUCED BY 50% (REFER
TO TABLE ABOVE)
·ALLOWABLE OVERHANG
INDICATED ON PLANS TO BE
1/5TH OF ALLOWABLE
ATTACHMENT SPACING
INDICATED ON PLANS (REFER TO
TABLE ABOVE)
PITCHED/SLOPED ROOFS - REDUCED SPACING AND OVERHANG DETAIL FOR
12" BOUNDARY REGION
FLAT ROOFS - REDUCED SPACING AND OVERHANG DETAIL FOR 48"
BOUNDARY REGION
D ULTRA RAIL MID CLAMP
NTS
1.
4
1
1.57
1.29
1.
3
3
.9
4
1
1.75
.1
9
.33
1.
4
8
.57
SNAPNRACK ULTRA END CLAMP,
FITS 30MM - 46MM MODULE HEIGHTS
"RAIL END OVERHANG"
DISTANCE FROM RAIL END
TO OUTER ROOF ATTACHMENT CENTER.
NOT TO EXCEED 34% OF ALLOWABLE SPAN
STRUCTURAL MEMBER
"RAIL SPAN" DISTANCE BETWEEN
CENTERS OF TWO ROOF ATTACHMENTS
DETAIL A:
SNAPNRACK, ULTRA RAIL END CLAMP
BA
SNAPNRACK ULTRA MID CLAMP,
FITS 30MM - 46MM MODULE HEIGHTS
SNAPNRACK, ULTRA RAIL
PV MODULE, TYP.
SNAPNRACK, ULTRA RAIL
DETAIL B:
SNAPNRACK, ULTRA RAIL MID CLAMP
DETAIL C:
PV MODULE FRAME, TYP.
SNAPNRACK, UNIVERSAL END CLAMP.
MODULE HEIGHT AGNOSTIC AND
HIDDEN BENEATH MODULES
SNAPNRACK, ULTRA RAIL
SNAPNRACK, UNIVERSAL END CLAMP
C
PV MODULE, TYP.
3 4" MODULE SPACING
PV MODULE, TYP.
SNAPNRACK, ULTRA RAIL
OVERVIEW OF THE SNAPNRACK ULTRA RAIL
SYSTEM INSTALLED ON A TYPICAL ROOF
REFER TO SPECIFIC "ATTACHMENT DETAIL"
FOR DETAILS ON ATTACHING AND
WATERPROOFING THE VARIOUS
SNAPNRACK ROOF ATTACHMENT PRODUCTS
REFER TO SPECIFIC "COMPONENT DETAIL"
FOR DETAILS ON VARIOUS SNAPNRACK
ACCESSARY AND COMPONENT PRODUCTS
BOTH THE SNAPNRACK, UNIVERSAL END
CLAMP AND SNAPNRACK, ADJUSTABLE END
CLAMP CAN BE USED ON END MODULES
MODULES MAY BE CLAMPED ON SHORT OR
LONG SIDE PER MODULE MANUFACTURER
REQUIREMENTS
RAILS MAY BE MOUNTED UP/DOWN OR
ACROSS THE SLOPE OF THE ROOF
REFER TO SNAPNRACK INSTALLATION
SPECIFICATIONS
SNAPNRACK, ADJUSTABLE
END CLAMP. SELECT TO
MATCH MODULE HEIGHT
PV MODULE, TYP.
MANUAL FOR 5/16" Ø HARDWARE TORQUE
SNAPNRACK, MID CLAMP.
SELECT TO MATCH MODULE HEIGHT
"MODULE OVERHANG"
SNAPNRACK, ULTRA RAIL DISTANCE FROM RAIL SIDE TO MODULE EDGE.
NOT TO EXCEED 25% OF MODULE LENGTH OR
MODULE MANUFACTURER RECOMMENDATIONS
SNAPNRACK, ULTRA RAIL
END CAP, OPTIONAL
ROOFING MATERIAL,
COMP SHINGLE SHOWN, TYP.
ROOF SHEATHING AND
UNDERLAYMENT MATERIAL, TYP.
STRUCTURAL MEMBER,
WOODEN RAFTER SHOWN, TYP.
SNAPNRACK ROOF ATTACHMENT, VAIRES WITH
ROOF TYPE. REFER TO SPECIFIC "ATTACHMENT DETAIL"
FOR ATTACHMENT & WATERPROOFING DETAILS
BIN:
ALL
A ULTRA RAIL, SYSTEM OVERVIEW ULTRA MIDS & ENDS
NTS
UR-40 RAIL | UR-45 RAIL | UR-60 RAIL
FOR USE WITH SNAPNRACK ULTRA SERIES RAILS
2 1 4"
1 1 2"
1 1 2"
1 5 8"1 3
4 "
1 1 2"
.60 1.50
1.56 .29
35°
54°.96
.90
FLANGE LENGTH
(FLAT SURFACE)
.39 - 1.21
[10.0 - 30.7]
FLANGE THICKNESS
.05 - .10
[1.2 - 2.5]
MIN BOX WIDTH
.22
[5.5]
MODULE FRAME GEOMETRY REQUIREMENTS
.85
E ULTRA RAIL UNIVERSAL END CLAMP
NTS
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
RACKING ATTACHMENT
DETAILS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
S400
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
DETAIL 1. BRACKET INSTALLATION
1.FASTEN BATTERY BRACKET TO WALL STUDS WITH x 2-1/2" LAG SCREWS
2.AFTER THE BATTERY BRACKET IS INSTALLED, FASTEN BATTERY TO BRACKET PER MANUFACTURER GUIDELINES
DETAIL 2. BATTERY INSTALLATION
WALL STUDS
16"
FOR 24" SPACING, USE
OUTER BOLT HOLES
BATTERY BRACKET
SOLARMOUNT BATTERY
BATTERY BRACKET
(2) 1/4" X 2-1/2" LAG SCREWS PER
STUD, INSTALLED AT TOP
AND BOTTOM OF BRACKET
1/4"
A SOLAREDGE BESS WALL MOUNT
NTS
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
EQUIPMENT PAD
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
S500
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
PL PL PL PL PL PL PL PL PL PL PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PLPLPLPLPLPLPLPLPLPL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
BLDG A
BLDG C
BLDG B
BLDG D
PO
I
PO
I
PO
I
PO
I
POI
PO
I
PO
I
PO
I
PO
I
POI
PO
I
PO
I
PO
I
POIPOI
PO
I
PO
I
PO
I
POI POI
PO
I
PO
I
PO
I
PO
I
POI
PO
I
PO
I
PO
I
PO
I
POI
PO
I
POIPOIPOIPOI
PO
I
POI POI POI POI
(E) SOLAR
THERMAL
RF01
TL: 18° AZ: 180°
RF02
TL: 18° AZ: 270°
RF03
TL: 18° AZ: 90°
RF04
TL: 18° AZ: 90°
RF05
TL: 18° AZ: 270°
RF06
TL: 18° AZ: 90°
RF07
TL: 18° AZ: 270°
RF08
TL: 18° AZ: 90°
RF09
TL: 18° AZ: 270°
RF10
TL: 18° AZ: 270°
RF11
TL: 18° AZ: 360°
RF12
TL: 18° AZ: 90°
RF13
TL: 18° AZ: 270°
RF14
TL: 18° AZ: 180°
RF15
TL: 18° AZ: 360°
RF16
TL: 18° AZ: 180°
RF17
TL: 18° AZ: 360°
RF18
TL: 18° AZ: 360°
RF19
TL: 18° AZ: 180°
RF20
TL: 18° AZ: 180°
RF21
TL: 18° AZ: 360°
RF22
TL: 18° AZ: 360°
RF23
TL: 18° AZ: 180°
RF24
TL: 18° AZ: 180°
RF25
TL: 18° AZ: 360°
RF26
TL: 18° AZ: 360°
RF27
TL: 18° AZ: 90°
RF28
TL: 18° AZ: 360°
RF29
TL: 18° AZ: 270°
RF30
TL: 18° AZ: 90°
RF31
TL: 18° AZ: 270°
RF32
TL: 18° AZ: 90°
RF33
TL: 18° AZ: 270°
RF34
TL: 18° AZ: 90°
RF35
TL: 18° AZ: 270°
RF36
TL: 18° AZ: 90°
RF37
TL: 18° AZ: 270°
RF38
TL: 18° AZ: 180°RF39
TL: 18° AZ: 90°
RF40
TL: 18° AZ: 180°
RF41
TL: 18° AZ: 270°
RF42
TL: 18° AZ: 90°
RF43
TL: 18° AZ: 270°RF44
TL: 18° AZ: 90°
RF45
TL: 18° AZ: 270°
RF46
TL: 18° AZ: 90°
RF47
TL: 18° AZ: 270°RF48
TL: 18° AZ: 90°
RF49
TL: 18° AZ: 270°
RF50
TL: 18° AZ: 90°
RF51
TL: 18° AZ: 270°RF52
TL: 18° AZ: 90°
RF53
TL: 18° AZ: 90°
RF54
TL: 18° AZ: 270°
RF55
TL: 18° AZ: 360°
POI-1
AC-1.1
AC-1.2
LC-1.1
INV-1.1
INV-1.2
INV-1.3
INV-1.4
BES-1.1-1.9
(N) SCE PV PRODUCTION METER
REF MTR #: 259000-081403
ADDR: 816 N FIGUEROA ST BLDG A
SOMAH1
(N) SCE PV PRODUCTION METER
REF MTR #: 256000-221416
ADDR: 816 N FIGUEROA ST BLDG B
SOMAH2
POI-2
AC-2.1
AC-2.2
LC-2.1
INV-2.1
INV-2.2
INV-2.3
INV-2.4
BES-2.1-2.9
POI-3
AC-3.1
AC-3.2
LC-3.1
INV-3.1
INV-3.2
INV-3.3
INV-3.4
BES-3.1-3.9
(N) SCE PV PRODUCTION METER
REF MTR #: 234010-284202
ADDR: 816 N FIGUEROA ST BLDG C
SOMAH3
POI-4
AC-4.1
AC-4.2
LC-4.1
INV-4.1
INV-4.2
INV-4.3
INV-4.4
BES-4.1-4.9
(N) SCE PV PRODUCTION METER
REF MTR #: 234010-215697
ADDR: 816 N FIGUEROA ST BLDG D
SOMAH4
HAZARD AVE
N
F
I
G
U
E
R
O
A
S
T
N
H
A
R
B
O
R
B
L
V
D
FIRE SETBACKS
(18" TYP)
816 N FIGUEROA ST,
BLDG B, SANTA ANA,
CA 92703, USA
APN #: 198-162-03,
198-162-44,
198-162-52
ROOF PATHWAYS (3' TYP)
E200
F
E200
G
E201
A
E201
B
E301
A
E300
A
E301
B
E300
B
(E) SOLAR
THERMAL
(E) SOLAR
THERMAL
(E) SOLAR
THERMAL
816 N FIGUEROA ST,
BLDG D, SANTA ANA,
CA 92703, USA
816 N FIGUEROA ST,
BLDG A, SANTA ANA,
CA 92703, USA
816 N FIGUEROA ST,
BLDG C, SANTA ANA,
CA 92703, USA
POINT OF INTERCONNECTION
SEE WARNING LABEL DETAIL 1/E700
PV AC DISCONNECT
SEE WARNING LABEL DETAIL 2/E700
AC DISCO #
LOAD CENTER
SEE WARNING LABEL DETAIL 6 & 7/E700
LOAD CENTER #
XX
PV INVERTER AND DC DISCONNECT
SWITCH
SEE WARNING LABEL DETAIL 3 & 9/E700
INVERTER # XX
H
(N) SOLAR CANOPY
STRUCTURAL COLUMN
DOWN SLOPE
(E) POLE-MOUNTED LIGHT
FIXTURE
(E) FIRE HYDRANT
ELECTRICAL EQUIPMENT
LEGEND
MAIN PANEL & SUB
PANELS
INVERTER(S) WITH
INTEGRATED DC
DISCONNECT AND AFCI
GENERAL LOCATION OF EQUIPMENT
ATTIC VENT
FLUSH ATTIC VENT
PVC PIPE VENT
SATELLITE DISH
T-VENT
FIRE SETBACKS
METAL PIPE VENT
HARDSCAPE
PROPERTY LINEPL
PITCH
2°
POI #
X
XX
SECTION CUT
SHEET NUMBER
XX
X
DETAIL CUT
SHEET NUMBER
RAIL
STANDOFFS &
FOOTINGS
SOLAR MODULES
METER SOCKET & DISCONNECTS
PV LOAD CENTER
POI BOUNDARY
AC-X.X
LC-X.X
INV-X.X
POI-X
XX##
TL: ##° AZ: ###°
ROOF IDENTIFIER
MOUNTING INDEX
MOUNTING TYPE
TILT
AZUMUTH
CHIMNEY
ELECTRICAL CONDUIT
POI
TRENCHING
℄
TESLA BACKUP GATEWAY 2
(IF APPLICABLE)
TESLA PAOWERWALL 2
WALL OR PAD MOUNTED
(IF APPLICABLE)
SOLAREDGE ENERGY BANK
WALL OR PAD MOUNTED
(IF APPLICABLE)
PL PL PL
PL
PL
PLPL
PL
PL
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
ELECTRICAL SITE PLAN
SCALE: 1" = 20'
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E100
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
IFC SECTION 1205.2 ACCESS
PATHWAYS
BLDG
NUMBER
PLAN VIEW
AREA (sqft)
MODULE
COUNT
COVERAGE
(%)
A 8389.7 132 34.2%
B 8276.8 117 30.7%
C 10827.6 125 25.1%
D 11091.2 163 31.9%
Totals 38585 537
POI-1 ROOF SCHEDULE
BLDG LABEL RACKING TILT (DEG)AZIMUTH
(DEG)
BUILDING
HEIGHT (FT)
MODULE
COUNT
MODULE AREA (SQFT)KW DC
A RF01 FLUSH MOUNT 18°180°30 13 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]274.6 5.33
A RF02 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
A RF03 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
A RF04 FLUSH MOUNT 18°90°30 12 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]253.5 4.92
A RF05 FLUSH MOUNT 18°270°30 17 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]359.1 6.97
A RF06 FLUSH MOUNT 18°90°30 8 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]169.0 3.28
A RF07 FLUSH MOUNT 18°270°30 8 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]169.0 3.28
A RF08 FLUSH MOUNT 18°90°30 24 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]506.9 9.84
A RF09 FLUSH MOUNT 18°270°30 20 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]422.4 8.20
A RF10 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
A RF11 FLUSH MOUNT 18°360°30 18 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]380.2 7.38
A RF12 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
Totals 132 2788 54
POI-2 ROOF SCHEDULE
BLDG LABEL RACKING TILT (DEG)AZIMUTH
(DEG)
BUILDING
HEIGHT (FT)
MODULE
COUNT
MODULE AREA (SQFT)KW DC
B RF28 FLUSH MOUNT 18°360°30 18 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]380.2 7.38
B RF29 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
B RF30 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
B RF31 FLUSH MOUNT 18°270°30 24 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]506.9 9.84
B RF32 FLUSH MOUNT 18°90°30 19 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]401.3 7.79
B RF33 FLUSH MOUNT 18°270°30 8 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]169.0 3.28
B RF34 FLUSH MOUNT 18°90°30 8 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]169.0 3.28
B RF35 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
B RF36 FLUSH MOUNT 18°90°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
B RF37 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
B RF38 FLUSH MOUNT 18°180°30 13 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]274.6 5.33
B RF39 FLUSH MOUNT 18°90°30 4 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]84.5 1.64
Totals 117 2471 48
POI-3 ROOF SCHEDULE
BLDG LABEL RACKING TILT (DEG)AZIMUTH
(DEG)
BUILDING
HEIGHT (FT)
MODULE
COUNT
MODULE AREA (SQFT)KW DC
C RF13 FLUSH MOUNT 18°270°30 16 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]337.9 6.56
C RF14 FLUSH MOUNT 18°180°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
C RF15 FLUSH MOUNT 18°360°30 4 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]84.5 1.64
C RF16 FLUSH MOUNT 18°180°30 10 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]211.2 4.10
C RF17 FLUSH MOUNT 18°360°30 13 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]274.6 5.33
C RF18 FLUSH MOUNT 18°360°30 5 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]105.6 2.05
C RF19 FLUSH MOUNT 18°180°30 5 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]105.6 2.05
C RF20 FLUSH MOUNT 18°180°30 9 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]190.1 3.69
C RF21 FLUSH MOUNT 18°360°30 14 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]295.7 5.74
C RF22 FLUSH MOUNT 18°360°30 5 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]105.6 2.05
C RF23 FLUSH MOUNT 18°180°30 5 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]105.6 2.05
C RF24 FLUSH MOUNT 18°180°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
C RF25 FLUSH MOUNT 18°360°30 14 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]295.7 5.74
C RF26 FLUSH MOUNT 18°360°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
C RF27 FLUSH MOUNT 18°90°30 16 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]337.9 6.56
Totals 125 2640 51
POI-4 ROOF SCHEDULE
BLDG LABEL RACKING TILT (DEG)AZIMUTH
(DEG)
BUILDING
HEIGHT (FT)
MODULE
COUNT
MODULE AREA (SQFT)KW DC
D RF40 FLUSH MOUNT 18°180°30 17 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]359.1 6.97
D RF41 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
D RF42 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
D RF43 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF44 FLUSH MOUNT 18°90°30 20 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]422.4 8.20
D RF45 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF46 FLUSH MOUNT 18°90°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF47 FLUSH MOUNT 18°270°30 19 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]401.3 7.79
D RF48 FLUSH MOUNT 18°90°30 18 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]380.2 7.38
D RF49 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF50 FLUSH MOUNT 18°90°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF51 FLUSH MOUNT 18°270°30 7 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]147.8 2.87
D RF52 FLUSH MOUNT 18°90°30 19 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]401.3 7.79
D RF53 FLUSH MOUNT 18°90°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
D RF54 FLUSH MOUNT 18°270°30 3 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]63.4 1.23
D RF55 FLUSH MOUNT 18°360°30 16 Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]337.9 6.56
Totals 163 3443 67
198-162-52
198-162-52
198-162-03
198-162-44 APN MAP
6'
-
3
"
M
A
X
4'
-
0
"
M
I
N
FR
O
M
G
R
A
D
E
B (N) NGO METER SOCKET ≤ 200A
NTS
10"
MIN.
MIN. CLEARANCE
TO OBSTRUCTIONS
OR SIDE WALLS
36" MIN.
(N) HOUSEKEEPING PAD
THE PAD SHALL BE FLUSH WITH
THE BOTTOM OF THE SERVICE EQUIPMENT
AND EXTEND A MINIMUM OF THREE FEET.
10"
MIN.
18" MIN.
MIN. CLEARANCE TO
EDGE OF WINDOW
OR DOOR
- NGO METER WORKING SPACE
TO BE MAINTAINED.
- EQUIPMENT ABOVE OR BELOW
NGOM WILL NOT EXCEED
DEPTH OF NGOM.
- NGOM TO BE MOUNTED ON
STRUT IF NEEDED TO
ACCOUNT FOR ANY DEPTH
DIFFERENCES.
- CENTER OF METER CAN NOT
TO EXCEED 6'-3" MAX, 4'-0" MIN.
-EQUIPMENT AND CONDUIT
SHOWN IS DIAGRAMMATIC
ONLY. SEE LINE DRAWINGS
FOR CONDUIT SIZING.
NOTES
MIN. CLEARANCE TO
PLUMBING FIXTURES
EXTENDING 6" OUT
FROM WALL SURFACE
6'
-
6
"
M
I
N
H
E
I
G
H
T
CL
E
A
R
A
N
C
E
FR
O
M
G
R
A
D
E
(E) GRADE
A (N) AC DISCONNECT
(E) GRADE
6'
-
7
"
M
A
X
H
A
N
D
L
E
HE
I
G
H
T
F
R
O
M
G
R
A
D
E
NOTES
- CENTER OF GRIP IN HIGHEST
POSITION MUST NOT EXCEED
6'-7" MAX.
-EQUIPMENT AND CONDUIT
SHOWN IS DIAGRAMMATIC
ONLY. SEE LINE DRAWINGS
FOR CONDUIT SIZING.
D INVERTER CLEARANCE - SOLAREDGE A-SERIES
4"
2"
16" MIN.
CLEAR
16" MIN.
CLEAR
2"
4"
2"
16" MIN.
CLEAR
8" MIN.
CLEAR
MIN. CLEARANCE
BACK TO BACK
INVERTERS
- LISTED MIN. CLEARANCES FOR
INVERTER TO OTHER
OBJECTS, UNLESS NOTED
- MIN. CLEARANCES REQUIRED
FOR HEAT DISSIPATION
- CONDUIT MAY BE REQUIRE
ADDITIONAL CLEARANCE
NOTES
46.4"
9.84"
BATTERY WEIGHT: 262LBS
31.1" 8" MIN. CLEAR
MIN. CLEARANCE
BATTERY SHOWN ON
OPTIONAL FLOOR STAND
KIT
SOLAREDGE ENERGY BANK
BAT-10K1P
E BESS CLEARANCE - SOLAREDGE ENERGY BANK
·LISTED MIN. CLEARANCES FOR ENERGY BANK TO OTHER
OBJECTS AS REQUIRED BY MANUFACTURER. NEC 110.3(B)
·BATTERY CAN BE WALL MOUNTED OR USE MANUFACTURES
FLOOR STAND KIT.
·8" MIN. CLEARANCES REQUIRED FOR HEAT DISSIPATION
·CONDUIT MAY REQUIRE ADDITIONAL CLEARANCE.
·EQUIPMENT AND CONDUIT SHOWN IS DIAGRAMMATIC ONLY.
·WORKING CLEARANCES SHALL BE IN ACCORDANCE WITH NEC
110.26 FOR ANY COMPONENTS THAT ARE LIKELY TO REQUIRE
EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE
WHILE ENERGIZED.
NOTES
8" MIN.
CLEAR
8" MIN.
CLEAR
8" MIN.
CLEAR
SOLAREDGE ENERGY BANK
WITH 4 BATTERIES ON FLOOR STAND KITS
53.15"
MIN.
6.3"
13.78"
1ST BATTERY FLOOR
STAND TO BE ANCHORED
TO WALL/RACK
SIDE BRACKETS
FOR
ATTACHING
BATTERIES
MIN. CLEAR IF
WALL MOUNTING
DC
CONNECTION
LOCATION
C INVERTER CLEARANCE - SOLAREDGE HOME HUB
MIN. CLEARANCE
BACK TO BACK
INVERTERS 8" MIN.
CLEAR
16" MIN.
CLEAR
8" MIN.
CLEAR
MIN. CLEARANCE
VERTICALLY
STACKED INVERTERS
8" MIN.
CLEAR
MIN. CLEARANCE
SIDE-BY-SIDE INVERTERS
- LISTED MIN. CLEARANCES FOR
INVERTER TO OTHER
OBJECTS, UNLESS NOTED
- MIN. CLEARANCES REQUIRED
FOR HEAT DISSIPATION
- CONDUIT MAY BE REQUIRE
ADDITIONAL CLEARANCE
-EQUIPMENT AND CONDUIT
SHOWN IS DIAGRAMMATIC
ONLY. SEE LINE DRAWINGS
FOR CONDUIT SIZING.
NOTES
8" MIN.
CLEAR
4" MIN.
CLEAR
4" MIN.
CLEAR
4" MIN.
CLEAR
(N) AC DISCONNECT
GENERAL NOTES
·FIELD VERIFY ALL MEASUREMENTS
·ALL WORK SHALL COMPLY WITH ALL STATE AND LOCAL CODES AND ANY OTHER REGULATING AUTHORITIES
WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK.
·DRAWINGS HAVE BEEN DETAILED IN COMPLIANCE WITH UL LISTING REQUIREMENTS, OSFM SOLAR
PHOTOVOLTAIC INSTALLATION REQUIREMENTS, AND BUILDING CODES FOR THE MATERIALS SPECIFIED. PRIOR
TO COMMENCEMENT OF ANY WORK, THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND NOTIFY THE
DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE FROM SUNRUN OF ANY DISCREPANCIES. ANY WORK
PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS SHALL BE CORRECTED AT THE
SUBCONTRACTORS SOLE EXPENSE.
·SUBCONTRACTOR INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO SUNRUN FOR APPROVAL BEFORE
MAKING ANY CHANGES OR DEVIATION FROM PLANS BEFORE WRITTEN APPROVAL FROM SUNRUN PLACES
LIABILITY ON THE SUBCONTRACTOR.
·ALL EQUIPMENT SHALL BE MOUNTED AS SHOWN. WHERE DETAILS ARE NOT PROVIDED, CONTRACTOR SHALL
USE STANDARD CONSTRUCTION PRACTICES.
·ALL SURFACES SHALL BE PATCHED AND PAINTED AROUND NEW DEVICES AND EQUIPMENT TO MATCH EXISTING
FINISHES. ANY METAL SHAVINGS FROM SITE WORK SHALL BE CLEANED FROM ALL SURFACES WHERE OXIDIZED
OR CONDUCTIVE METAL SHAVINGS MY CAUSE RUST, ELECTRICAL SHORT CIRCUITS, OR OTHER DAMAGE.
·APPROVALS FROM BUILDING INSPECTORS SHALL NOT CONSTITUTE AUTHORITY TO DEVIATE FROM THE
DRAWINGS.
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
ELECTRICAL PLAN VIEWS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E200
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
(N) PV POINT OF INTERCONNECTION (POI-1)
(N) PV PRODUCTION METER SOCKET 816 N FIGUEROA ST BLDG A SOMAH1 PV PRODUCTION METER
REFERENCE METER NUMBER: 259000-081403
(N) UTILITY AC DISCONNECT (ACDS-1.1)
(N) MAINTENANCE AC DISCONNECT (ACDS-1.2)
(N) AC LOAD CENTER (LC-1.1)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-1.1)
(N) PV INVERTER AND ESS AC DISCONNECT(INV-1.2)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-1.3)
(N) PV INVERTER (INV-1.4)
(N) SOLAREDGE BAT-10K1P BATTERY WALL MOUNTED
(EACH BATTERY 9.7KWH)
(N) PV POINT OF INTERCONNECTION (POI-2)
(N) PV PRODUCTION METER SOCKET 816 N FIGUEROA ST BLDG B SOMAH2 PV PRODUCTION METER
REFERENCE METER NUMBER: 256000-221416
(N) UTILITY AC DISCONNECT (ACDS-2.1)
(N) MAINTENANCE AC DISCONNECT (ACDS-2.2)
(N) AC LOAD CENTER (LC-2.1)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-2.1)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-2.2)
(N) PV INVERTER AND ESS AC DISCONNECT(INV-2.3)
(N) PV INVERTER (INV-2.4)
F EQUIPMENT PLAN -POI-1 (BLDG A)
SCALE: 1/8" = 1'-0"
G EQUIPMENT PLAN -POI-2 (BLDG B)
SCALE: 3/16" = 1'-0"
(N) SOLAREDGE BAT-10K1P BATTERY MOUNTED WALL MOUNTED
(EACH BATTERY 9.7KWH)
(N) SOLAREDGE BAT-10K1P BATTERY WALL MOUNTED
(EACH BATTERY 9.7KWH)
(N) SOLAREDGE BAT-10K1P BATTERY WALL MOUNTED
(EACH BATTERY 9.7KWH)
(N) BOLLARD
(N) BOLLARD
8"
8"
8"
8"
GENERAL NOTES
·FIELD VERIFY ALL MEASUREMENTS
·ALL WORK SHALL COMPLY WITH ALL STATE AND LOCAL CODES AND ANY OTHER REGULATING AUTHORITIES
WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK.
·DRAWINGS HAVE BEEN DETAILED IN COMPLIANCE WITH UL LISTING REQUIREMENTS, OSFM SOLAR
PHOTOVOLTAIC INSTALLATION REQUIREMENTS, AND BUILDING CODES FOR THE MATERIALS SPECIFIED. PRIOR
TO COMMENCEMENT OF ANY WORK, THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND NOTIFY THE
DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE FROM SUNRUN OF ANY DISCREPANCIES. ANY WORK
PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS SHALL BE CORRECTED AT THE
SUBCONTRACTORS SOLE EXPENSE.
·SUBCONTRACTOR INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO SUNRUN FOR APPROVAL BEFORE
MAKING ANY CHANGES OR DEVIATION FROM PLANS BEFORE WRITTEN APPROVAL FROM SUNRUN PLACES
LIABILITY ON THE SUBCONTRACTOR.
·ALL EQUIPMENT SHALL BE MOUNTED AS SHOWN. WHERE DETAILS ARE NOT PROVIDED, CONTRACTOR SHALL
USE STANDARD CONSTRUCTION PRACTICES.
·ALL SURFACES SHALL BE PATCHED AND PAINTED AROUND NEW DEVICES AND EQUIPMENT TO MATCH EXISTING
FINISHES. ANY METAL SHAVINGS FROM SITE WORK SHALL BE CLEANED FROM ALL SURFACES WHERE OXIDIZED
OR CONDUCTIVE METAL SHAVINGS MY CAUSE RUST, ELECTRICAL SHORT CIRCUITS, OR OTHER DAMAGE.
·APPROVALS FROM BUILDING INSPECTORS SHALL NOT CONSTITUTE AUTHORITY TO DEVIATE FROM THE
DRAWINGS.
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
ELECTRICAL PLAN VIEWS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E201
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
(N) PV POINT OF INTERCONNECTION (POI-3)
(N) PV PRODUCTION METER SOCKET 816 N FIGUEROA ST BLDG C SOMAH3 PV PRODUCTION METER
REFERENCE METER NUMBER: 234010-284202
(N) UTILITY AC DISCONNECT (ACDS-3.1)
(N) MAINTENANCE AC DISCONNECT (ACDS-3.2)
(N) AC LOAD CENTER (LC-3.1)
(N) PV POINT OF INTERCONNECTION (POI-4)
(N) PV PRODUCTION METER SOCKET 816 N FIGUEROA ST BLDG D SOMAH4 PV PRODUCTION METER
REFERENCE METER NUMBER: 234010-215697
(N) UTILITY AC DISCONNECT (ACDS-4.1)
(N) MAINTENANCE AC DISCONNECT (ACDS-4.2)
(N) AC LOAD CENTER (LC-4.1)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-4.1)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-4.2)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-4.3)
(N) PV INVERTER (INV-4.4)
(N) SOLAREDGE BAT-10K1P BATTERY WALL MOUNTED
(EACH BATTERY 9.7KWH)
A EQUIPMENT PLAN -POI-3 (BLDG C)
SCALE: 1/4" = 1'-0"
B EQUIPMENT PLAN -POI-4 (BLDG D)
SCALE: 3/16" = 1'-0"
(N) PV INVERTER AND ESS AC DISCONNECT (INV-3.2)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-3.3)(N) PV INVERTER (INV-3.4)
(N) PV INVERTER AND ESS AC DISCONNECT (INV-3.1)
(N) SOLAREDGE BAT-10K1P BATTERY
WALL MOUNTED (EACH BATTERY 9.7KWH)
(N) SOLAREDGE BAT-10K1P BATTERY
WALL MOUNTED (EACH BATTERY 9.7KWH)
(N) BOLLARD
(N) SOLAREDGE BAT-10K1P BATTERY WALL MOUNTED
(EACH BATTERY 9.7KWH)
8"
(N) BOLLARD
8"
LEGEND
STRING PATH
GENERAL NOTES
·FIELD VERIFY ALL MEASUREMENTS
·SEE SHEET E-100 FOR LEGEND OF SYMBOLS
STRING ID. X
INVERTER ID. #
INTERCONNECTION ID. #
INCREMENT
COUNT
1.1B.A
#
RF01
TL: 18° AZ: 180°
RF02
TL: 18° AZ: 270°
RF03
TL: 18° AZ: 90°
RF04
TL: 18° AZ: 90°
RF05
TL: 18° AZ: 270°
RF06
TL: 18° AZ: 90°
RF07
TL: 18° AZ: 270°
RF08
TL: 18° AZ: 90°
RF09
TL: 18° AZ: 270°
RF10
TL: 18° AZ: 270°
RF11
TL: 18° AZ: 360°
RF12
TL: 18° AZ: 90°
2
345678910
11
2
3
4
5
6 7
8
9
10
11
2
3
4 5
6
7
8
9
10
2
3
4
5
6
7
8
9
10
11
2
3
4
5
6
7
8 9
10
2
3
4
5
6
7 8 9 10 2 3 4 5 6
7891011
2
3
4
5
6
78
9
10
2
3 4
5
67
8
9
10
2
3
4
5
6
7
8
2
3
4
5
6
7
8
9
10
11
12
13
14
2
3
4
5
6
7
8
9
10
11
12
13
1.1.A1.1.A1.1.B
1.
1
.
B
1.
1
.
C
1.
1
.
C
1.
2
.
A
1.
2
.
A
1.
2
.
B
1.
2
.
B
1.
2
.
C
1.2.C 1.3.A
1.3.A 1.3.B
1.
3
.
B
1.
3
.
C
1.
3
.
C
1.
4
.
C
1.
4
.
C
1.
4
.
A
1.
4
.
A
1.
4
.
B
1.
4
.
B
RF28
TL: 18° AZ: 360°
RF29
TL: 18° AZ: 270°
RF30
TL: 18° AZ: 90°
RF31
TL: 18° AZ: 270°
RF32
TL: 18° AZ: 90°
RF33
TL: 18° AZ: 270°
RF34
TL: 18° AZ: 90°
RF35
TL: 18° AZ: 270°
RF36
TL: 18° AZ: 90°
RF37
TL: 18° AZ: 270°
RF38
TL: 18° AZ: 180°RF39
TL: 18° AZ: 90°
RF41
RF43
TL: 18° AZ: 270°
RF45
TL: 18° AZ: 270°
RF47
TL: 18° AZ: 270°
RF49
TL: 18° AZ: 270°
RF51
TL: 18° AZ: 270°
RF54
TL: 18° AZ: 270°
2
34567
89
23
4
5
6
7
8
9
2
3
4
5
6
7
8
2
3
4
5
6
7
8
9
2
3
4
5
6
7
8
9
2
3
4
5
6
7
8
2 3
4 5 6 7 8 9
2 3 4
5
6 7
8
9
2
3
4
56
7
8
2
3
4
5
6
7
8
9
2
3
4
5
6
7
8
9
2
3
4
5
6
7
8
9
2.1.A
2.1.A
2.1.B
2.1.B
2.1.C
2.
1
.
C
2.
2
.
A
2.
2
.
A
2.
2
.
B
2.
2
.
B
2.
2
.
C
2.2.C
2.3.A
2.3.A
2.3.B
2.
3
.
B
2.
3
.
C
2.
3
.
C
2.
4
.
A
2.
4
.
A
2.
4
.
B
2.
4
.
B
2.
4
.
C
2.
4
.
C
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
ELECTRICAL STRINGING
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E300
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
SITE PLAN KEY
E301E300
SCALE: 3/32" = 1'-0"
BLDG A STRINGING • POI-1A SCALE: 3/32" = 1'-0"
BLDG B STRINGING • POI-2B
POI-1 MODULE ALLOCATION
STR-A STR-B STR-C
UNIT INVERTER MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]
INV-1.1 SOLAREDGE SE11400H-US HOME HUB
[208V] [SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (12) RF01 [18°, 180°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (1) RF01 [18°, 180°]; (3) RF02 [18°, 270°]; (8)
RF05 [18°, 270°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (9) RF05 [18°, 270°]; (2) RF07 [18°, 270°];
INV-1.2 SOLAREDGE SE11400H-US HOME HUB
[208V] [SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (6) RF07 [18°, 270°]; (6) RF09 [18°, 270°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (11) RF09 [18°, 270°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (3) RF09 [18°, 270°]; (3) RF10 [18°, 270°]; (5)
RF11 [18°, 360°];
INV-1.3 SOLAREDGE SE11400H-US HOME HUB
[208V] [SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (12) RF11 [18°, 360°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (1) RF11 [18°, 360°]; (3) RF12 [18°, 90°]; (7)
RF08 [18°, 90°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (11) RF08 [18°, 90°];
INV-1.4 SOLAREDGE SE10KUS [208V] [SI1-SB]Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]15 U650 (6) RF08 [18°, 90°]; (8) RF06 [18°, 90°]; (1)
RF04 [18°, 90°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]14 U650 (11) RF04 [18°, 90°]; (3) RF03 [18°, 90°];
POI-2 MODULE ALLOCATION
STR-A STR-B STR-C
UNIT INVERTER MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]
INV-2.1 SOLAREDGE SE11400H-US HOME HUB
[208V] [SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (10) RF38 [18°, 180°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (3) RF38 [18°, 180°]; (3) RF37 [18°, 270°]; (4)
RF35 [18°, 270°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]9 U650 (3) RF35 [18°, 270°]; (6) RF33 [18°, 270°];
INV-2.2 SOLAREDGE SE11400H-US HOME HUB
[208V] [SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (2) RF33 [18°, 270°]; (8) RF31 [18°, 270°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (10) RF31 [18°, 270°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]9 U650 (6) RF31 [18°, 270°]; (3) RF29 [18°, 270°];
INV-2.3 SOLAREDGE SE11400H-US HOME HUB
[208V] [SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (10) RF28 [18°, 360°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (8) RF28 [18°, 360°]; (2) RF30 [18°, 90°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]9 U650 (1) RF30 [18°, 90°]; (8) RF32 [18°, 90°];
INV-2.4 SOLAREDGE SE10KUS [208V] [SI1-SB]Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (10) RF32 [18°, 90°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (1) RF32 [18°, 90°]; (8) RF34 [18°, 90°]; (1)
RF36 [18°, 90°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (6) RF36 [18°, 90°]; (4) RF39 [18°, 90°];
INTERCONNECTION LOCATION
INTERCONNECTION
LOCATION
PV INVERTER AND
ESS AC DISCONNECT
LOCATION
PV INVERTER
LOCATION
BESS LOCATION
BESS LOCATION
PV INVERTER AND
ESS AC DISCONNECT
LOCATION
PV INVERTER
LOCATION
BESS LOCATION
BESS LOCATION
LEGEND
STRING PATH
GENERAL NOTES
·FIELD VERIFY ALL MEASUREMENTS
·SEE SHEET E-100 FOR LEGEND OF SYMBOLS
STRING ID. X
INVERTER ID. #
INTERCONNECTION ID. #
INCREMENT
COUNT
1.1B.A
#
RF13
TL: 18° AZ: 270°
RF14
TL: 18° AZ: 180°
RF15
TL: 18° AZ: 360°
RF16
TL: 18° AZ: 180°
RF17
TL: 18° AZ: 360°
RF18
TL: 18° AZ: 360°
RF19
TL: 18° AZ: 180°
RF20
TL: 18° AZ: 180°
RF21
TL: 18° AZ: 360°
RF22
TL: 18° AZ: 360°
RF23
TL: 18° AZ: 180°
RF24
TL: 18° AZ: 180°
RF25
TL: 18° AZ: 360°
RF26
TL: 18° AZ: 360°
RF27
TL: 18° AZ: 90°
2
3
4
5
6 7
8
9
10
2
34
5
6 7 8 9
2 3
456789
2
3 4 5
6 7
8 9 10
23
4 5 6 7
8 9
2 3
4 5
6 7 8
9
234
5 6 7 8 9
10
2
3
4
5
6
7
8
9
2
3
4 5
6
7
89
2 3
45
678
910
23
45
678
910
2 3
4 5
678
9
3.
1
.
A
3.
1
.
A
3.
1
.
B
3.1.B 3.1.C
3.1.C 3.2.A
3.2.A
3.2.B
3.2.B
3.2.C
3.2.C
3.3.A
3.3.A 3.3.B
3.
3
.
B
3.
3
.
C
3.3.C
3.4.A
3.4.A3.4.B
3.4.B
3.4.C
3.4.C
RF32
TL: 18° AZ: 90°
RF34
TL: 18° AZ: 90°
RF36
TL: 18° AZ: 90°
RF39
TL: 18° AZ: 90°
RF40
TL: 18° AZ: 180°
RF41
TL: 18° AZ: 270°
RF42
TL: 18° AZ: 90°
RF43
TL: 18° AZ: 270°RF44
TL: 18° AZ: 90°
RF45
TL: 18° AZ: 270°
RF46
TL: 18° AZ: 90°
RF47
TL: 18° AZ: 270°RF48
TL: 18° AZ: 90°
RF49
TL: 18° AZ: 270°
RF50
TL: 18° AZ: 90°
RF51
TL: 18° AZ: 270°RF52
TL: 18° AZ: 90°
RF53
TL: 18° AZ: 90°
RF54
TL: 18° AZ: 270°
RF55
TL: 18° AZ: 360°
2
3
4
6
8
9
2
2.
4
.
C
4.
1
.
A
2
3 4 5 6
78910114.1.A4.1.B2
3 4 5 6 7 8
9
10
11
4.
1
.
B
4.
1
.
C
23
4
5
6
7
8
9
10
11
4.
1
.
C
4.
2
.
A
2
3
4
5
6
7
8
9
10
11
4.
2
.
A
4.
2
.
B
2
3
4
5
6
7
8
9
10
11
4.
2
.
B
4.
2
.
C
2
3
4
5
6
78
9
10
11
4.
2
.
C
4.
3
.
A
2
3
4
5
6
7
8
9
10
11
4.
3
.
A
4.
3
.
B
2
3
4
56
7
8
9
10
11
4.
3
.
B
4.
3
.
C
2
3
4
5
6
7
8
9
10
4.
3
.
C
4.
4
.
A
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
4.
4
.
A
4.
4
.
B
2
3
4
5
6
7
89
10
11
1213
14 15
16
17
18
4.4.B 4.4.C
2 3 4
5 6
7 8 9 10
11 12
13
14 15
16
17
4.
4
.
C
BLDG A
BLDG C
BLDG B
BLDG D
816 N FIGUEROA ST,
BLDG B, SANTA ANA,
CA 92703, USA
S200
A
S201
A
S202
A
816 N FIGUEROA ST,
BLDG D, SANTA ANA,
CA 92703, USA
816 N FIGUEROA ST,
BLDG A, SANTA ANA,
CA 92703, USA
816 N FIGUEROA ST,
BLDG C, SANTA ANA,
CA 92703, USA
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
ELECTRICAL STRINGING
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E301
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
SCALE: 1/16" = 1'-0"
BLDG C STRINGING • POI-3A
SCALE: 3/32" = 1'-0"
BLDG D STRINGING • POI-4B
POI-3 MODULE ALLOCATION
STR-A STR-B STR-C
UNIT INVERTER MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]
INV-3.1 SOLAREDGE SE11400H-US HOME HUB [208V]
[SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (11) RF13 [18°, 270°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (5) RF13 [18°, 270°]; (4) RF15 [18°, 360°]; (1) RF17 [18°,
360°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (10) RF17 [18°, 360°];
INV-3.2 SOLAREDGE SE11400H-US HOME HUB [208V]
[SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (2) RF17 [18°, 360°]; (5) RF18 [18°, 360°]; (4) RF21 [18°,
360°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (10) RF21 [18°, 360°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (5) RF22 [18°, 360°]; (5) RF25 [18°, 360°];
INV-3.3 SOLAREDGE SE11400H-US HOME HUB [208V]
[SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (9) RF25 [18°, 360°]; (2) RF26 [18°, 360°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (1) RF26 [18°, 360°]; (9) RF27 [18°, 90°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (7) RF27 [18°, 90°]; (3) RF24 [18°, 180°];
INV-3.4 SOLAREDGE SE10KUS [208V] [SI1-SB]Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (5) RF23 [18°, 180°]; (6) RF20 [18°, 180°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (3) RF20 [18°, 180°]; (5) RF19 [18°, 180°]; (3) RF16 [18°,
180°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]10 U650 (7) RF16 [18°, 180°]; (3) RF14 [18°, 180°];
BLDG C
BLDG D
SITE PLAN KEY
E301E300
INTERCONNECTION
LOCATION
PV INVERTER AND
ESS AC DISCONNECT
LOCATION
BESS LOCATION
PV INVERTER LOCATIONBESS
LOCATION
INTERCONNECTION
LOCATION
BESS LOCATION
PV INVERTER LOCATION
PV INVERTER AND ESS
AC DISCONNECT
LOCATION
BESS LOCATION
POI-4 MODULE ALLOCATION
STR-A STR-B STR-C
UNIT INVERTER MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]MODULE TOTAL MODS OPT BREAKOUT - (QTY) ROOF TAG [TILT,AZM]
INV-4.1 SOLAREDGE SE11400H-US HOME HUB [208V]
[SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (9) RF40 [18°, 180°]; (3) RF41 [18°, 270°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (8) RF40 [18°, 180°]; (3) RF42 [18°, 90°]; (1) RF44 [18°,
90°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (12) RF44 [18°, 90°];
INV-4.2 SOLAREDGE SE11400H-US HOME HUB [208V]
[SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (5) RF43 [18°, 270°]; (7) RF44 [18°, 90°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (2) RF43 [18°, 270°]; (7) RF45 [18°, 270°]; (3) RF46 [18°,
90°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (4) RF46 [18°, 90°]; (8) RF48 [18°, 90°];
INV-4.3 SOLAREDGE SE11400H-US HOME HUB [208V]
[SI1-SB] [CRD-PCS NEM]
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (2) RF47 [18°, 270°]; (10) RF48 [18°, 90°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]12 U650 (12) RF47 [18°, 270°];Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]11 U650 (5) RF47 [18°, 270°]; (6) RF49 [18°, 270°];
INV-4.4 SOLAREDGE SE10KUS [208V] [SI1-SB]Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]19 U650 (1) RF49 [18°, 270°]; (7) RF50 [18°, 90°]; (11) RF52 [18°,
90°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]19 U650 (8) RF52 [18°, 90°]; (7) RF51 [18°, 270°]; (3) RF54 [18°,
270°]; (1) RF55 [18°, 360°];
Q.PEAK DUO BLK ML-G10.C+ 410 [DCC]18 U650 (3) RF53 [18°, 90°]; (15) RF55 [18°, 360°];
STRUT CONDUIT CLAMP
12 GA GALVANIZED
STEEL
SIZED AS APPROPRIATE
1-5/8" STRUT CHANNEL
12 GA, HDG
NOTE: ALL HOLES FOR CONDUIT SHALL BE PROVIDED WITH CONDUIT FITTINGS
HAVING AN ENVIRONMENTAL RATING APPROVED TO MAINTAIN NEMA 3R
ENCLOSURE RATING (UL508A, TABLE 19.2). IN GENERAL COMPONENTS MARKED
"WEATHERPROOF" OR "RAINPROOF" SHALL BE INSTALLED ONLY BELOW THE
LOWEST UNINSULATED LIVE PARTS WITHIN THE ENCLOSURE. CONDUIT
OPENINGS ABOVE THE LOWEST UNINSULATED LIVE PARTS SHALL BE PROVIDED
WITH CONDUIT FITTINGS MARKED "WET LOCATION" OR "RAINTIGHT".
WOOD: MIN. 2" EMBED W/ 3/8" LAG TO
(E) STUD OR 4"xBLOCK W/ A34 EA.
END T&B
MASONRY: USE ICC-APPROVED
MASONRY ANCHORS
STEEL: USE SELF-DRILLING,
SELF-TAPPING SCREWS
OPTION 1 OPTION 2
2-HOLE 12 GA GALV
STEEL STRAP
NTS
CONDUIT SUPPORT - WALLC
USE EXISTING HOLES TO
TERMINATE CONDUCTORS,
TORQUE PER
MANUFACTURER
REQUIREMENTS. USE
GRADE 5 OR LARGER BOLT.
UL LISTED CRIMP RATED FOR 600
VOLTS CRIMPED IN 2 PLACES. USE
MANUFACTURER APPROVED
CRIMPING DEVICE ONLY AND
APPLY ANTIOXIDANT COMPOUND
BEFORE CRIMPING.
SIDE VIEWFRONT VIEW
(E) BUS
NOTE:
ALUMINUM CONDUCTORS SHALL NOT BE TERMINATED WITH MECHANICAL LUGS.
TORQUE MARK BOLT WITH PAINT
PEN AFTER TORQUING NUT/BOLT
B CONDUCTOR TERMINATION DETAIL
NTS
CONTINUOUS GROUND
STRIP INSULATION AT LUG
ENCLOSURE
LOCK NUT
GROUNDING BUSHING
WITH LAY-IN LUG
CONDUIT COMPRESSION FITTING
NTS
CONDUIT GROUNDING DETAILA
NOTE:
ACCESSIBLE MEANS EXTERNAL TO ENCLOSURES FOR
CONNECTING INTERSYSTEM BONDING AND GROUNDING
CONDUCTORS SHALL BE PROVIDED. SEE NEC 250.94.
SERVICE DISCONNECT 1 OF 2
WHERE NEUTRAL TERMINAL BUS IS
INSULATED FROM THE ENCLOSURE,
INSTALL A MAIN BONDING JUMPER
OR SCREW WITH A GREEN SEE NEC
250.8, 250.28. NEUTRAL DISCONNECT
MEANS. SEE NEC 230.75.
WHERE SERVICE ENTRANCE
RACEWAY IS INSTALLED WITH
LOCKNUTS, INSTALL A GROUND
BUSHING OR DEVICE AND BOND TO
THE ENCLOSURE. SEE NEC 250.92
(B) (4).
GROUNDING ELECTRODE SYSTEM –
SEE NEC 250.50.
IF METALLIC CONDUIT, BONDING
REQUIRED (BOTH ENDS) SEE NEC
250.92.
GROUNDING ELECTRODE
CONDUCTOR – SEE NEC 250.62
FOR MATERIAL, NEC 250.64 FOR
INSTALLATION, AND NEC 250.66
FOR SIZE.
CONNECTION TO ELECTRODE –
CONNECT GROUNDING ELECTRODE
CONDUCTOR TO GROUNDING
ELECTRODE WITH LISTED GROUND
SEE NEC 250.70.
BONDING JUMPER SEE NEC
250.92 (A) (2). FOR SIZES,
SEE NEC 250.102 (C).
LAY IN LUG. WHERE LUG IS
INSULATED FROM
ENCLOSURE, INSTALL A
BONDING JUMPER OR
SCREW.
GROUNDED (NEUTRAL) SERVICE
ENTRANCE CONDUCTOR
FROM PV SYSTEM
SERVICE
DISCONNECT
2 OF 2
METER ENCLOSURE
D METER GROUNDING DETAIL
NTS
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
ELECTRICAL DETAILS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E400
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
RAIL
CHANNEL NUT
MODULE
FRAME
MID CLAMP ASSEMBLY
SS BONDING PIN
NOTE:
1.ADJUSTABLE END CLAMPS USE SAME BONDING PIN DESIGN TO
BOND MODULES TO RAIL
C MID CLAMP ASSEMBLY
NTS
NOTES:
1.INSTALL EXPANSION COUPLING EVERY 100' OF
STRAIGHT CONDUIT RUN
2.IF EXPANSION COUPLINGS ARE INSTALLED AT
LESS THAN 100'.THE DISTANCES OF
EXPANSION/CONTRACTION SHALL BE
ADJUSTED PROPORTIONALLY.
3.IF EXPANSION JOINT IS NOT PROVIDED WITH
INTERNAL BONDING JUMBER, AN EXTERNAL
BONDING JUMPER MUST BE INSTALLED.
INSTALL EXPANSION COUPLINGS SO THAT THE
LENGTH CHANGE FOR CONTINUOUS CONDUIT
DOES NOT EXCEED 1/4".
SEE NEC 352.44
FOR STEEL CONDUIT, MULTIPLY THE EXPANSIONS
LISTED IN TABLE 352.44 BY 0.2.
SEE NEC 300.7
0°F - EXTEND 3/8" BEYOND CENTER
60°F - CENTERED
30°F - EXTEND 3/16" BEYOND CENTER
90°F - EXTEND 3/16" BEYOND CENTER
120°F - EXTEND 3/8" BEYOND CENTER
CONDUIT TYPE COEFFICIENT (IN./IN/°F)TEMP °F EXPANSION/ 100FT (IN)
STEEL 6.5 X 10-6 120 0.94
PVC 3.4 X 10-5 120 4.87
B CONDUIT THERMAL EXPANSION DETAIL
NTS
D SNAPNRACK ULTRA RAIL BONDING SPLICE
NTS
RAIL GAP
RANGE
THERMAL EXPANSION GAP:
1/8" - 1/4"
RAIL EDGE MUST NOT PASS THE
BONDING CLIP EDGE, AS SHOWN.
SPLICE ALIGNMENT LIMITS
SNAPNRACK, UR-40/UR-45 RAIL
TORQUE ALL FASTENERS TO
THE SPECIFIED VALUES PRIOR
TO INSTALLING PV MODULES
SNAPNRACK, ULTRA RAIL SPLICE
SNAPNRACK, UR-40/UR-45 SPLICE INSALLED
SNAPNRACK BONDING CLIP, TYPE 2
FOR BONDING ACROSS RAILS
NOTE:
1.ALL HARDWARE IS INCLUDED FROM MANUFACTURER
2.REFER TO SNAPNRACK INSTALLATION MANUAL FOR 5/16"Ø
HARDWARE TORQUE SPEC
3.SPLICE POSITIONING:
3.1.APPROVED - ANYWHERE ALONG RAIL SPAN BETWEEN TWO
ROOF ATTACMENTS
3.2.NOT APPROVED - RAIL OVERHANGS / CANTILEVERS
4.USE OF THE UR-40/UR-45 SPLICE WITH UR-60 RAIL IS PROHIBITED
SNAPNRACK, UR-40 RAIL
1 3/4"
1 5/8"
1 1/2"
1 1/2"
SNAPNRACK, UR-45 RAIL
G SNAPNRACK OMNILUG
NTS
OMNILUG GROUND LUG ON ULTRA RAIL
OMNILUG MPLE ATTACHMENT ON ULTRA RAIL
GROUND LUG NOTE:
1.PLACE THE GROUNDING CONDUCTOR INTO THE
SLOT ON THE BONDING BRACKET UNDERNEATH THE
CONICAL WASHER ON THE SEMS BOLT.
1.1.GROUNDING CONDUCTOR MUST EXTEND
BEYOND THE ENTIRE CONICAL WASHER TO
ASSURE PROPER BONDING.
1.2.TIGHTEN THE MOUNTING BOLT TO 10.8 LB-FT.
2.OPTIMIZERS AND MICROINVERTERS SHOULD
ALWAYS BE INSTALLED PER SPECIFIC
MANUFACTURER'S INSTRUCTION.
MLPE NOTE:
1.PLACE THE MOUNTING PLATE CHASSIS OF THE MLPE
DEVICE ON THE BONDING BRACKET UNDERNEATH
THE CONICAL WASHER ON THE SEMS BOLT.
2.TIGHTEN THE MOUNTING BOLT TO 10.8 LB-FT.
2
1
3
EXPLODED VIEW
ITEM QTY
1
2
3
PARTS LIST
DESCRIPTION
1 SNAPNRACK, OMNILUG, BONDING BRACKET, SS
1 SEMS SCREW, HEX, 5-16IN-18 X 1-1-4IN, 7-8 OD CONICAL WSH, TOOTH, SS
1 SNAPNRACK CHANNEL NUT 5-16IN-18
TOP VIEW
SIDE VIEW
1.78
1.78
0.29
0.41
1.53
E SNR GROUND PATH DETAIL - SOLAREDGE
NTS
X M M M X
TO EGC
X M M M X
U M U U U
TO EGC
U M U U U
GROUND PATH
RAIL RAIL SPLICE MOUNT
EQUIPMENT GROUNDING
CONDUCTOR
GROUND LUG
SOLAREDGE
OPTIMIZER
M MODULE CLAMP
M = MIDCLAMP
X = X-END CLAMP
U = UNIVERSAL END
CLAMP
F SNAPNRACK FRAME MLPE ATTACHMENT
NTS
.66
.14
R.12 .63
.30
2.24
1.50 .50
.95
SOLAR MODULE
SNR MLPE FRAME
ATTACHMENT
MODULE LEVEL POWER
ELECTRONIC
SOLAR MODULE
FRAME
MODULE FRAME MLPE INSTALLATION VIEW
INTEGRATED
SMART CLIP
MODULE FRAME MLPE TOP VIEW
MODULE FRAME MLPE SIDE VIEW
SCE BARRIERS
SCE ESR-3: 16.11 PROTECTIVE BARRIERS (POSTS/ BOLLARDS) FOR SERVICE EQUIPMENT (1-26-2024)A
NOTES:
·MAINTAIN A MINIMUM OF 3' CLEAR AND LEVEL
WORKING SPACE IN FRONT OF ALL THE SERVICE
EQUIPMENT ENCLOSURES.
·90 DEG MIN. OPENING FOR SERVICE EQUIPMENT
DOORS/ PANELS.
·4" GALVANIZED STEEL PIPE (1/4" MIN. WALL)
FILLED WITH CONCRETE AND PAINTED "CAUTION
YELLOW."
·CONCRETE ENCASEMENT 6" MIN. IN STABLE SOIL,
12" MIN. IN SANDY OR UNSTABLE SOIL.
·BARRIERS MUST BE INSTALLED IN LINE WITH
EACH END OF SERVICE EQUIPMENT.
·4'-6" MIN. DISTANCE BETWEEN CENTER OF
BARRIERS.
2'-6"
CONCRETE
6" or 12"
FINAL
GRADE
CONCRETE
FILLED
CONCRETE
CAP
2'-6"
5'-0"
4'-6"
MAX.
3'-0"
MIN.
PULL CAN / SECTION
OR METERS
4'-6"
MAX.
NON-REMOVABLE
BARRIER POST DETAILPLAN VIEW
3"
PARKING SPACES
OR VEHICULAR
TRAFFIC
4'-6"
MAX.
3'-0"
MIN.
4'-6"
MAX.
3'-0"
MIN.
4'-6"
MAX.
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
ELECTRICAL DETAILS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E401
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
GENERAL ELECTRICAL NOTES MODULE CHARACTERISTICS
OPTIMIZER CHARACTERISTICS
STATION CHARACTERISTICS
MAX TEMP [°C]: 38
MIN TEMP [°C]: -2
SINGLE LINE DIAGRAM LEGEND
CURRENT TRANSFORMER
(DOT INDICATES DIRECTION)
METER
CIRCUIT BREAKER
SWITCH
PV MODULE
FUSE
INVERTER~
--
M
CELLULAR ANTENNA
DC COMBINER
TRANSFORMER
BATTERY MODULE
A
B TRANSFER SWITCH (ATS/ MTS)
JUNCTION BOX
+-
INTERCONNECTION NOTES
INTERCONNECTION NOTES
·SUPPLY SIDE INTERCONNECTIONS SHALL COMPLY WITH ART. 705.11 AND ART 230 FOR THE
INSTALLATION OF AN ADDITIONAL SERVICE ENTRANCE
·THE OVERCURRENT PROTECTION DEVICE ON THE SUPPLY SIDE OF THE SERVICE
DISCONNECTING MEANS SHALL BE WITHIN 10 FEET OF THE INTERCONNECTION POINT UNLESS
CABLE LIMITERS OR CURRENT-LIMITED CIRCUIT BREAKERS ARE INSTALLED ON EACH
UNGROUNDED CONDUCTOR AT THE POINT OF INTERCONNECTION PER ART. 705.11(C). THIS
OVERCURRENT DEVICE MUST BE SIZED FOR THE SHORT-CIRCUIT CURRENT SUPPLIED FROM THE
PRIMARY SOURCE(S) OF ELECTRICITY.
·SUPPLY SIDE INTERCONNECTIONS SHALL BE MADE IN ACCORDANCE WITH THE EQUIPMENT
MANUFACTURER'S INSTRUCTIONS AND SHALL NOT INVALIDATE THE NRTL LISTING OF THE
EQUIPMENT.
·RMC OR SCH 80 PVC TYPE CONDUIT SHALL BE USED TO ENCLOSE NEW SERVICE CONDUCTORS
USED FOR A SUPPLY SIDE INTERCONNECTION.
·NEW SERVICE CONDUCTORS USED FOR SUPPLY SIDE INTERCONNECTIONS SHALL BE INSTALLED
IN A SEPARATE RACEWAY FROM ANY LOAD SIDE CONDUCTORS WITHIN THE MAIN SWITCHBOARD
PER NEC 230.7.
GENERAL NOTES
·ALL ELECTRICAL WORK SHALL COMPLY WITH THE NEC 2023 CODE AS AMENDED BY
APPLICABLE STATE AND LOCAL CODES.
·EACH UNGROUNDED CONDUCTOR OF THE MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED
BY PHASE AND SYSTEM PER ART 210.5.
·BRANCH CIRCUITS SUPPLIED FROM DC SYSTEMS MUST BE IDENTIFIED IN COMPLIANCE WITH
ART. 210.5(C)(2) WHERE DC POSITIVE (+) IS RED/ RED-STRIPED AND DC NEGATIVE (-) IS
BLACK/BLACK-STRIPED.
·ALL EQUIPMENT SHALL BE LISTED BY A NRTL IN COMPLIANCE WITH ART 110.3.
·DC CONDUCTORS INSIDE BUILDING SHALL BE IN METALLIC RACEWAY PER ART 690.31(D).
·ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF AT ALL ENTRY INTO BOXES AS
REQUIRED BY NRTL LISTING.
·PARALLEL CONDUCTORS SHALL BE INSTALLED PER ART 310.10(G).
·ALL VALUES FOR Imp, Isc AND Vmp ARE PER MANUFACTURER'S LISTED DATA AT STC. MAXIMUM
VOLTAGE CALCULATED IN ACCORDANCE WITH ARTICLE NEC 690.7.
·REFER TO CURRENT MANUFACTURER'S PLANNING AND INSTALLATION MANUAL FOR
TORQUE SPECS FOR ALL BOLTS AND TERMINAL CONNECTIONS.
·BRANCH CIRCUITS RUN IN OUTDOOR ROOFTOP AMBIENT CONDITIONS SHALL BE INSTALLED
> 7/8 INCH ABOVE ROOF SURFACE.
·ALL PV CIRCUITS LOCATED OUTSIDE THE ARRAY BOUNDARY OR MORE THAN 3 FT FROM THE
POINT OF ENTRY INSIDE A BUILDING SHALL BE LIMITED TO NOT MORE THAN 30 VOLTS
WITHIN 30 SECONDS, CIRCUITS INSIDE THE ARRAY BOUNDARY OR NOT MORE THAN 3 FT
FROM THE POINT OF PENETRATION SHALL BE LIMITED TO NOT MORE THAN 80 VOLTS UPON
RAPID SHUT-DOWN INITIATION PER 690.12.
·PV SYSTEM SHALL CONTAIN OR INTERACT WITH DEVICES CAPABLE OF DETECTING AND
INTERRUPTING ARCING FAULTS WITHIN THE SYSTEM PER 690.11.
·BURIED CONDUCTORS SHALL BE BURIED TO THE MINIMUM DEPTH SPECIFIED IN ART. 300.5
FOR CIRCUITS 1000V AND UNDER AND ART. 300.50 FOR CIRCUITS ABOVE 1000V.
·SPACES ABOUT ELECTRICAL EQUIPMENT 1000V AND UNDER SHALL COMPLY WITH 110.26
AND SPACES ABOUT ELECTRICAL ENCLOSURES ABOUT EQUIPMENT ABOVE 1000V SHALL
COMPLY WITH 110.34.
·REFER TO THE CONDUCTOR SCHEDULE FOR THE TYPE OF CONDUCTORS TO BE USED FOR
THE LISTED CIRCUITS.
·PV WIRE SHALL BE SECURED USING NON-METALLIC UV-RATED TIE WRAPS.
·ALL LINE SIDE AND LOAD SIDE TERMINATIONS OF ALUMINUM AND COPPER CONDUCTORS
SHALL BE MADE WITH HIGH PRESS CRIMP LUGS ON BUSSING UNLESS OTHERWISE NOTED.
·ALL TERMINATIONS OF ALUMINUM CONDUCTORS SHALL BE PROPERLY INSTALLED WITH
BEST PRACTICE PROCEDURES THAT INCLUDE BUT NOT LIMITED TO: USE OF TERMINATION
EQUIPMENT RATED FOR ALUMINUM AT THE CONDUCTOR TEMPERATURE, CURRENT, AND
VOLTAGE; ALLOWANCE FOR MOVEMENT DUE TO THERMAL EXPANSION/CONTRACTION;
PROPER COATING OF EXPOSED ALUMINUM WITH ANTI-OXIDIZATION COMPOUND; USE OF
CALIBRATED DEVICES TO TORQUE AND MARK TERMINALS TO REQUIRED SETTINGS.
·AT MULTIPLE INVERTERS OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT
DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE MAIN OVERCURRENT
DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).
GROUNDING NOTES
·GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND
GROUNDING DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.
·PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE
250.122.
·METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED
GROUNDED IN ACCORD WITH 250.134 AND 250.136.
·EACH MODULE WILL BE GROUNDED USING THE HARDWARE INTEGRATED GROUNDING PINS
OR OTHER MEANS APPROVED BY THE MODULE MANUFACTURE AND AHJ.
·THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE
REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER
MODULE.
··GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR
MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119(A)]
·THE AC & DC GEC SHALL BE CONTINUOUS FROM THE INVERTER GROUND BUSBAR TO THE
MAIN ELECTRICAL SERVICE GROUNDING ELECTRODE SYSTEM. THE DC GEC SHALL BE
ATTACHED TO THE GROUND ELECTRODE USING AN IRREVERSIBLE MEANS AS CALLED OUT
IN ART 250.64 AND 690.47.
·PV INVERTER CONTAINS AN INTEGRATED GFDI CIRCUIT. DO NOT BOND THE GROUNDED DC
CONDUCTOR TO GROUND EXCEPT THROUGH THE INVERTER GFDI.
·ALL EXPOSED METAL PARTS (MODULE FRAMES, RAIL, PIPE, BOXES, ETC) SHALL BE
GROUNDED USING TIN-PLATED COPPER LAY-IN LUGS OR GROUNDING CLIPS LISTED FOR
THE PURPOSE. RAIL CLAMPS SHALL BE MADE ELECTRICALLY CONTINUOUS WITH ATTACHED
RAIL.
·RACKING SYSTEMS SHALL BE BONDED PER MANUFACTURER'S UL 2703 INSTRUCTIONS.
·MIN #10 BARE COPPER EGC AT SOURCE CIRCUITS SHALL BE ROUTED SECURELY TO
MOUNTING HARDWARE IN A MANNER THAT PROTECTS FROM PHYSICAL HARM. #6 BARE
COPPER EGC FOR AREAS SUBJECT TO PHYSICAL DAMAGE.
·MODULE FRAMES SHALL BE GROUNDED AT THE LISTED LOCATION PROVIDED BY THE
MANUFACTURER OR USING LISTED THIRD-PARTY HARDWARE ONLY IF SPECIFICALLY
REFERRED TO IN MANUFACTURER'S INSTRUCTIONS PER UL 1703.INSTALLER SHALL COMPLY
WITH MANUFACTURER GROUND IN BONDING REQUIREMENTS
·BOTH ENDS OF ALL METALLIC CONDUIT CONTAINING GROUNDING ELECTRODE
CONDUCTORS SHALL BE BONDED PER ART 250.64(E).
·GROUNDING ELECTRODE CONDUCTOR TO BE BONDED TO (E) GROUNDING ELECTRODE PER
ART 250.68.
·DC GROUNDING ELECTRODE CONDUCTOR SIZED PER ART 690.47. AC GROUNDING
ELECTRODE CONDUCTOR PER 250.66.
·MAIN BONDING JUMPERS AND GROUNDED CONDUCTORS (NEUTRALS) SHALL BE SIZED PER
250.102 UNLESS OTHERWISE ALLOWED TO BE SIZED PER 705.28(C).
·INCREASES IN DC EQUIPMENT GROUNDING CONDUCTOR SIZE TO ADDRESS VOLTAGE
CONSIDERATIONS SHALL NOT BE REQUIRED PER ART 690.45.
·INCREASES IN AC EQUIPMENT GROUNDING CONDUCTOR SIZE TO ADDRESS VOLTAGE
CONSIDERATIONS SHALL BE REQUIRED PER 250.122(B).
·INSTALLATION SHALL COMPLY WITH ART 250.52, 250.53.
·CIRCUITS OVER 250V SHALL COMPLY WITH ART. 250.97, 250.92(B).
NO CONDUCTOR
PERMITTED IN SHADED
AREA
A SCE METERING NOTES
NTS
GENERATOR
CONDUCTORS
CONNECT ON LOAD
TERMINALS
UTILITY
CONDUCTORS
CONNECT ON LINE
TERMINALS
SELF-CONTAINED ENCLOSURE
COMBINATION CURRENT
TRANSFORMER AND METER CAN
1.WIRING OF A NGO METER SOCKET FOR VIRTUAL NET METERING PROJECTS , THE GENERATOR SHALL BE
CONNECTED TO THE LOAD SIDE OF THE NGO SOCKET.
2.THE HORIZONTAL CLEARANCE FROM THE CENTERLINE OF THE METER TO THE NEAREST SIDE WALL OR
OTHER OBSTRUCTION SHALL BE 10" MINIMUM. A HORIZONTAL CLEARANCE FROM THE EDGE OF THE
METER PANEL TO THE EDGE OF A WINDOW OR DOORWAY (INCLUDING SLIDING GLASS DOORS) SHALL BE
10" MINIMUM.
3.A CLEAR AND LEVEL WORKING SURFACE SHALL BE PROVIDED WITH A THE MINIMUM WIDTH OF THE
WORKSPACE SHALL BE 36 AND A MINIMUM DEPTH OF 36".
4.THE MINIMUM HEIGHT OF THE METER SHALL BE 4' AND MAXIMUM HEIGHT SHALL NOT EXCEED 6'-3"
MEASURED FROM STANDING SURFACE TO CENTERLINE OF METER SOCKET.
4.1.THE MINIMUM HEIGHT CAN BE REDUCED TO 3' IF LOCATED IN A METER ROOM.
5.DRAWING IS FOR WIRE REFERENCE ONLY AND IS NOT REFLECTIVE OF ACTUAL WIRE PENETRATIONS.
5 5
REMOVABLE TEST
PERCH
5
5
℄
℄REFER TO DC
STRING SCHEDULES
FOR FOR STRING
LENGTHS AND
OPTIMIZER
QUANTITY
C STRING WIRING - SINGLE OPTIMIZER (TYP.)
NTS
NOTE:
1.NEGATIVE TOO RUN ALONG SIDE THE POSITIVE WIRE. ALL WIRES MUST BE
SECURED TO UNDERSIDE OF THE RACKING AND MODULES USING SUNRUN
APPROVED METHODS AND MATERIALS WITH APPROPRIATE UV AND
ENVIRONMENTAL RATINGS.
2.CONDUIT TRANSITIONS SHALL BE MADE UNDER ARRAY.
3.INSTALL STRING LABELS ON BOTH ENDS OF HOMERUNS USING LABELS
SUITABLE FOR THE ENVIRONMENT.
4.FIELD INSTALLED CONNECTOR, 1000VDC, MATING MUST MATCH
MANUFACTURES RECOMMENDATIONS (TYP. TWO PER STRING)
5.TOTAL CIRCUIT LENGTH SHALL NOT EXCEED MANUFACTURE SPECIFICATIONS
6.FREE-AIR PV WIRE TO MATCH GAUGE OF DC-X.X CIRCUIT LOCATED ON DC
WIRE SCHEDULES.
4
4
3
3
2 1
(N) SOLAREGDE
OPTIMIZER
(N) PV MODULE
5
6
150' MAX DISTANCE
FOR WIRELESS
OPTIONAL THIRD BATTERY
(N) J-BOX WITH 3 OR 4 PORT POLARIS LUG OR
EQUIV.
(N) SOLAREDGE ENERGY BANK
BAT-10K1P, WALL MOUNTED OR
USING MANUFACTURES FLOOR
STAND KIT (IAC-RBAT-FLRSTD-01)
(N) SOLAREDGE HOME HUB INVERTER
MC-4
CONNECTORS TO
BATTERY
CONNECTION
UNIT
ES-1
ES-2
#CONDUIT CONDUCTOR GROUND
ES-1
FLOOR STAND INTERNAL
CHANNEL OR 3/4" EMT OR
EQUIV.
(2) 10 AWG PV WIRE (1) 10 AWG THHN/THWN-2
ES-2 3/4" EMT OR EQUIV.(2) 8 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2
SOLAREDGE BESS WIRING
NTSB
OPTIMIZER A:
MAKE/MODEL: SOLAREDGE U650
MAX INPUT POWER [W]: 650
MAX INPUT Voc [V]: 60
MAX INPUT Isc [A]: 15
OUTPUT CURRENT [A]: 15
MODULE A:
MAKE/MODEL: QCELLS NORTH AMERICA Q.PEAK DUO BLK ML-G10.C+ 410
POWER [W]: 410
Voc [V]: 45.37
Isc [A]: 11.2
Vmp [V]: 37.64
Imp [A]: 10.89
Voc coeff. [%/degC]: -0.27%
Isc coeff. [%/degC]: 0.04%
# IN SERIES: 1
Vmax CALCULATION: 48.7 VDC = 1 X ( 45.37 VDC - ( 25 - (-2)°C X ( 45.37 X -0.0027 ) V/°C )
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
ELECTRICAL NOTES
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E500
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
#
CAT5E 600V RATED SHIELDED CABLE.
INSTALLER SHALL FOLLOW
MANUFACTURES RECOMMENDATION FOR
WIRE SIZING BASED ON LENGTH.
EQUIPMENT INDEX
EQUIPMENT TYPE
SYSTEM IDENTIFIER X INDICATES LETTERS
# INDICATES NUMBERS
XX-#.#
SYSTEM SUMMARY
40.00 ACKW | 54.12 DCKW | 50.01 CECKW
30.00 BESS ACKW | 87.30 BESS KWH
TOTAL FAULT CURRENTS
UTILITY: 42,000A | GENERATORS: 280.55A
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
1
.
1
.
A
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
1
.
1
.
B
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
1
.
1
.
C
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ES-2
DC-1.1.1
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
A-B
60A
INV-1.1
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
1
.
2
.
A
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
1
.
2
.
B
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ST
R
-
1
.
2
.
C
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ES-2
DC-1.2.2
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
B-C
60A
INV-1.2
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
1
.
3
.
A
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
1
.
3
.
B
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ST
R
-
1
.
3
.
C
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ES-2
DC-1.3.3
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
C-A
60A
INV-1.3
18
14
1
ST
R
-
1
.
4
.
A
-
(
1
5
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
5
)
U
6
5
0
O
P
T
S
.
ST
R
-
1
.
4
.
B
-
(
1
4
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
4
)
U
6
5
0
O
P
T
S
.
DC-1.4.4
3
17
7
1
4B
12
2
A-B-C
35A
INV-1.4
6
LC-1.1
6
8
5
(N) ACDS-2 SYSTEM AC DISCONNECT
SWITCH,, SQUARE D, VHU364R, 600V RATED,
208V OPERATIONAL, 200A, 3 POLE,
NON-FUSIBLE, NEMA 3R. SEE REFERENCE
SHEETS FOR KAIC RATING.
AC-1.2
M9
4
(N) SCE PV PRODUCTION METER SOCKET
ADDRESS: 816 N FIGUEROA ST BLDG A
SOMAH1, COOPER B-LINE, 127TB, 200 A,
SERVICE 3 PHASE 4 WIRE 120/208 VOLT WYE,
NEMA 3R
AC-1.2
10
3
(N) ACDS-1 SYSTEM UTILITY AC DISCONNECT
SWITCH, SQUARE D, VH324NR, 240V RATED,
208V OPERATIONAL, 200A, 3 POLE, FUSIBLE,
NEMA 3R, OR EQUIVALENT ON THE UTILITIES
APPROVED LIST. CLASS R FUSE WITH
REJECTION CLIPS OR CLASS J FOR 200KAIC
RATING.
A-B-C
150AAC-1.1
M
M
M
M
M FACILITY
LOADS
(N) TENANT
METERS (TYP.)
UTILITY METER REFERENCE NUMBER:
259000-081403
SCE UTILITY GRID 208V,
3ø,4W
(N) LUGS ON (E)
HOLES
-
A
11101
600A
(N) CABLE
LIMITERS16
SUPPLY SIDE TAP OF INTERCONNECTION
UTILITY SECTION
CUSTOMER SECTION
SCE PULL SECTION
SCE METERS
A INTERCONNECTION LOCATION
NTS
1. PV MODULES (132) QCELLS NORTH
AMERICA Q.PEAK DUO BLK ML-G10.C+ 410
2. (132) SOLAREDGE DC OPTIMIZER U650
3. DC PV AND ESS CONNECTION UNIT W/
INTEGRAL LOAD BREAK DISCONNECT
4. 4A: (3) SOLAREDGE SE11400H-US HOME
HUB [208V] [SI1-SB] [CRD-PCS NEM],
10,000W, 208VAC, 1ø, 3W
4B: (1) SOLAREDGE SE10KUS [208V]
[SI1-SB], 10,000W, 208VAC, 3ø, 4W
5. NOT USED.
6. (1) LOAD CENTER, 200A, 3ø, MIN.208VAC,
MIN. 10KAIC, NEMA 3R
7. NOT USED
8.(N) ACDS-2 SYSTEM AC DISCONNECT
SWITCH, SQUARE D, VHU364R, 600V
RATED, 208V OPERATIONAL, 200A, 3 POLE,
NON-FUSIBLE, NEMA 3R. SEE REFERENCE
SHEETS FOR KAIC RATING.
9. (N) SCE PV PRODUCTION METER SOCKET
ADDRESS: 816 N FIGUEROA ST BLDG A
SOMAH1, COOPER B-LINE, 127TB, 200A,
SERVICE: 3 PHASE 4 WIRE 120/208 VOLT
WYE, 7 JAW, NEMA 3R, EUSERC: 305
10. (N) ACDS-1 SYSTEM UTILITY AC
DISCONNECT SWITCH, SQUARE D,
VH324NR, 240V RATED, 208V
OPERATIONAL, 200A, 3 POLE, FUSIBLE,
NEMA 3R, OR EQUIVALENT ON THE
UTILITIES APPROVED LIST. CLASS J FOR
200KAIC RATING.
11. (E) MAIN SERVICE EQUIPMENT: 3 PHASE
4 WIRE 120/208 VOLT WYE, 1000A
12. (N) 3 PHASE: CELL-B-R05-US-S-S4
COMMERCIAL CELL CARD OR
EQUIVALENT, 1 PHASE: MANUFACTURER
INTERGRATED CELL CARD
13. (9) SOLAREDGE BAT-10K1P BATTERIES,
9.70KWH, 5,000DCW, NEMA 3R, MOUNTED
TO WALL OR MANUFACTURER FLOOR
MOUNT KIT
14. NOT USED
15. NOT USED
16. (6) 1/0 AWG CABLE LIMITER
1.(E) MAIN SWITCHGEAR AND (N) POINT OF
AC INTERCONNECTION. ALL
CONNECTIONS MADE INSIDE (E)
SWITCHGEAR AT OTHER THAN CIRCUIT
BREAKERS OR FUSED SWITCHES LISTED
FOR USE WITH THAT SWITCHGEAR SHALL
BE PERFORMED FOLLOWING
MANUFACTURERS INSTRUCTIONS OR BE
RE-LISTED BY A NRTL. ALL TERMINATIONS
OF ALUMINUM CONDUCTORS SHALL BE
WITH HIGH PRESS CRIMP LUGS ONLY.
WARNING LABEL DETAIL 1/E800
2.(E) UTILITY TENANT LOAD METER. UTILITY
REFERENCE METER NUMBER:
259000-081403
3.(N) PV SYSTEM UTILITY AC DISCONNECT
'ACDS-1'. WARNING LABEL DETAIL 1/E810
4.(N) UTILITY BIDIRECTIONAL KWH METER.
WARNING LABEL DETAIL 1/E810
5.(N) PV SYSTEM MAINTENANCE AC
DISCONNECT 'ACDS-2'. WARNING LABEL
DETAIL 2/E800 & 1/E810
6.NOT USED
7.(N) GRID-INTERACTIVE PV INVERTER
LISTED TO UL 1741 WITH GROUND FAULT
DETECTION & INTERRUPTION. WARNING
LABEL DETAIL 15/E800.
8.NOT USED
9.NOT USED
10.FOR SUPPLY SIDE CONNECTIONS, A
PLAQUE SHALL BE INSTALLED AT THE
MAIN SERVICE DISCONNECTING DEVICE
AND THE PV SYSTEM UTILITY AC
DISCONNECT INDICATING THE LOCATION
OF THE RESPECTIVE SERVICE
DISCONNECT. WARNING LABEL DETAIL
1/E800 & 1/E810
11.NOT USED
12.CONDUCTORS RUN IN PARALLEL SHALL
BE INSTALLED PER ART 310.4/310.10(G)
AND 250.122 (F).
13.NOT USED
14.NEW PULL/JUNCTION BOXES. PROVIDE
SERVICE LOOP IN ALL DC BRANCH
CONDUCTORS SOURCED FROM
ROOFTOPS, MIN LOOP RADIUS = 12X
CONDUCTOR DIAMETER.
15.NOT USED
16.(N) INVERTER INTERNAL DC DISCONNECT
SWITCH(ES). WARNING LABEL DETAIL
3/E800
17.NOT USED
18.(N) PV MODULE LISTED TO UL 1703.
19.EXTRA MODULES THAT ARE UNABLE TO
BE PAIRED WILL HAVE THEIR OWN
OPTIMIZER.
20.(N) COMMUNICATION WIRING TO FOLLOW
MANUFACTURING SPECIFICATIONS.
21.DURING UTILITY GRID OUTAGE THE PV
GENERATION AND BESS WILL
DISCONNECT FROM THE GRID AND
REMAIN DISCONNECTED UNTIL GRID
VOLTAGE IS RESTORED TO THE
ACCEPTED MEASURE.
22.BATTERY AC OUTPUT POWER IS LIMITED
TO THE CORRESPONDING INVERTER OR
TOTAL BATTERIES CONNECTED TO A
SINGLE INVERTER,WHICHEVER IS LOWER.
23.BATTERIES SHOULD NOT BE INSTALLED IN
DIRECT SUNLIGHT OR LOCATIONS
SUBJECTED TO WATER SPRAY.
SPRINKLERS SHOULD BE DIVERTED
WHEN NECESSARY.
24.BATTERIES CAN COMMUNICATE
WIRELESSLY OR VIA RS-485 TO INVERTER.
BATTERIES WITHIN 150' (IDEALLY 50') OF
RESPECTIVE INVERTER CAN USE
WIRELESS COMMUNICATIONS VIA SEDG
HOME NETWORK CARD.
25.COMBINED PV AND BESS OUTPUT POWER
IS LIMITED TO THE INVERTER AC RATING.
26.NOT USED
816 N FIGUEROA ST BLDG A SOMAH1
POI-1 DC WIRE SCHEDULE
TAG WIRE GAUGE CONDUCTOR
JACKET
MAX ISC 1.25 X MAX
CIRCUIT AMPS
CIRCUIT FUSE
RATING
CCC PER
CONDUIT
MAX AMBIENT
TEMP (C)
C.O.U TEMP.
DERATE
C.O.U CONDUIT
FILL DERATE
75°C AMPACITY COMPLIES WITH
690.8(B)(1)
90°C AMPACITY
WITH C.O.U
COMPLIES WITH
690.8(B)(2)
FAULT CURRENT
FROM PARALLEL
STRINGS
COMPLIES WITH
690.9(A)
GROUNDING
PER CONDUIT
GROUNDING ³EMT RMC PVC 40 PVC 80
DC-1.1.1 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-1.2.2 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-1.3.3 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-1.4.4 CU #10 THWN2 15 18.75 25 A 4 38 91%80%35 YES 29.1 YES 25 YES 2 CU #10 3/4"3/4"3/4"3/4"
POI-1 DC STRING SCHEDULE
STR-A STR-B STR-C
TAG DESTINATION CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
DC-1.1.1 INV-1.1 70 0.36%410 12 U650 8 / 16¹70 0.34%410 12 U650 8 / 16¹75 0.35%410 11 U650 8 / 16¹
DC-1.2.2 INV-1.2 80 0.41%410 12 U650 8 / 16¹85 0.37%410 11 U650 8 / 16¹120 0.56%410 11 U650 8 / 16¹
DC-1.3.3 INV-1.3 115 0.59%410 12 U650 8 / 16¹90 0.40%410 11 U650 8 / 16¹80 0.37%410 11 U650 8 / 16¹
DC-1.4.4 INV-1.4 55 0.34%410 15 U650 10 / 19¹45 0.25%410 14 U650 10 / 19¹------------
¹ MAXIMUM STRING LENGTH IS USING MANUFACTURES EXCEPTION
² LENGTHS ARE ESTIMATED FOR CALCULATIONS, CONTRACTOR IS RESPONSIBLE FOR MEASUREMENTS AND TAKEOFFS
³ WHERE EXPOSED TO PHYSICAL DAMAGE #6 TO BE USED PER NEC 250.120(C)
⁴ AFC VALUES ARE CALCULATED BASED ON WIRE LENGTHS. LENGTHS SHOULD REMAIN GREATER THAN OR EQUAL TO THE LENGTH LISTED IN THE TABLE.
##KEYED NOTES#EQUIPMENT NOTES#
COMMUNICATION
CIRCUIT IDENTIFIER
BATTERY OPERATION NOTE:
INVERTERS WITH ESS ARE CERTIFIED TO UL 1741
PCS CRD AND WILL HAVE EXPORT ONLY MODES
ENABLED. THEY WILL UTILIZE EXCESS PV POWER
TO CHARGE THE BATTERIES AND THE BATTERIES
WILL DISCHARGE DURING SET HOURS.
THE PRODUCERS STORAGE DEVICE(S) WILL NOT
CONSUME POWER FROM THE DISTRIBUTION
PROVIDERS DISTRIBUTION SYSTEM AT ANY TIME
GRID EXPORT IS ALLOWED THROUGH NEMV METER
DURING UTILITY GRID OUTAGE THE PV
GENERATION AND BESS WILL DISCONNECT FROM
THE GRID AND REMAINS DISCONNECTED UNTIL
GRID VOLTAGE IS RESTORED TO THE ACCEPTABLE
MEASURE.
NOTE:
RIGID METAL CONDUIT (RMC) IS REQUIRED FOR THE NEW
SERVICE CONDUCTORS PRIOR TO METERING PER CITY
POLICY. TAPPED CONDUCTORS TO BE ROUTED IN RIGID
METAL CONDUIT PER CITY POLICY.
POI-1 AC WIRE SCHEDULE
LABEL DESTINATION NOMINAL VAC LINE
SELECTION
FLA FLAX1.25 OCPD PHASE
CONDUCTOR
NEUTRAL
CONDUCTOR
GROUNDING
CONDUCTOR
CONDUCTORS
PER PHASE
CONDUIT QTY 75°C AMPS 90°C AMPS 90°C AMPS W/
C.O.U
C.O.U TEMP
DERATE
C.O.U
CONDUIT FILL
CIRCUIT
LENGTH ²
SEGMENT
VD%
DC/AC RATIO AFC START AFC END ⁴EMT IMC PVC 40 PVC 80
INV-1.1 LC-1.1 208 A-B 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%143.5%3,895 3,616 3/4"3/4"3/4"3/4"
INV-1.2 LC-1.1 208 B-C 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%139.4%3,895 3,616 3/4"3/4"3/4"3/4"
INV-1.3 LC-1.1 208 C-A 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%139.4%3,895 3,616 3/4"3/4"3/4"3/4"
INV-1.4 LC-1.1 208 A-B-C 27.8 34.8 35 CU #8 CU #10 CU #10 1 1 50 55 50.1 91%100%5 0.09%118.9%3,895 3,477 3/4"3/4"3/4"3/4"
LC-1.1 AC-1.2 208 A-B-C 111.0 138.8 150 CU #1/0 CU #6 CU #6 1 1 150 170 154.7 91%100%35 0.37%--4,565 3,895 1 1/2"1 1/4"1 1/2"1 1/2"
AC-1.2 AC-1.1 208 A-B-C 111.0 138.8 150 CU #1/0 CU #6 CU #6 1 1 150 170 154.7 91%100%5 0.05%--4,680 4,565 1 1/2"1 1/4"1 1/2"1 1/2"
AC-1.1 POI-1.1 208 A-B-C 111.0 138.8 150 CU #2/0 CU #2/0 CU #4 1 1 175 195 142.0 91%80%18 0.16%--42,000 25,061 2"2"2"2"
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
POI-1 ONE LINE
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E600
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
##KEYED NOTES#EQUIPMENT NOTES#
COMMUNICATION
CIRCUIT IDENTIFIER
##KEYED NOTES#EQUIPMENT NOTES#
A INTERCONNECTION LOCATION
NTS
SYSTEM SUMMARY
40.00 ACKW | 47.97 DCKW | 44.30 CECKW
30.00 BESS ACKW | 87.30 BESS KWH
TOTAL FAULT CURRENTS
UTILITY: 42,000A | GENERATORS: 280.55A
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
2
.
1
.
A
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
2
.
1
.
B
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
2
.
1
.
C
-
(
9
)
4
1
0
W
M
O
D
U
L
E
W
/
(
9
)
U
6
5
0
O
P
T
S
.
ES-2
DC-2.1.1
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
A-B
60A
INV-2.1
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
2
.
2
.
A
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
2
.
2
.
B
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
2
.
2
.
C
-
(
9
)
4
1
0
W
M
O
D
U
L
E
W
/
(
9
)
U
6
5
0
O
P
T
S
.
ES-2
DC-2.2.2
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
B-C
60A
INV-2.2
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
2
.
3
.
A
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
2
.
3
.
B
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
2
.
3
.
C
-
(
9
)
4
1
0
W
M
O
D
U
L
E
W
/
(
9
)
U
6
5
0
O
P
T
S
.
ES-2
DC-2.3.3
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
C-A
60A
INV-2.3
18
14
1
ST
R
-
2
.
4
.
A
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
2
.
4
.
B
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
2
.
4
.
C
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
DC-2.4.4
3
17
7
1
4B
12
2
A-B-C
35A
INV-2.4
6
LC-2.1
6
8
5
(N) ACDS-2 SYSTEM AC DISCONNECT
SWITCH,, SQUARE D, VHU364R, 600V RATED,
208V OPERATIONAL, 200A, 3 POLE,
NON-FUSIBLE, NEMA 3R. SEE REFERENCE
SHEETS FOR KAIC RATING.
AC-2.2
M9
4
(N) SCE PV PRODUCTION METER SOCKET
ADDRESS: 816 N FIGUEROA ST BLDG B
SOMAH2, COOPER B-LINE, 127TB, 200 A,
SERVICE 3 PHASE 4 WIRE 120/208 VOLT WYE,
NEMA 3R
AC-2.2
10
3
(N) ACDS-1 SYSTEM UTILITY AC DISCONNECT
SWITCH, SQUARE D, VH324NR, 240V RATED,
208V OPERATIONAL, 200A, 3 POLE, FUSIBLE,
NEMA 3R, OR EQUIVALENT ON THE UTILITIES
APPROVED LIST. CLASS R FUSE WITH
REJECTION CLIPS OR CLASS J FOR 200KAIC
RATING.
A-B-C
150AAC-2.1
M
M
M
M
M FACILITY
LOADS
(N) TENANT
METERS (TYP.)
UTILITY METER REFERENCE NUMBER:
256000-221416
SCE UTILITY GRID 208V,
3ø,4W
(N) LUGS ON (E)
HOLES
-
A
11101
800A
CUSTOMER
SECTION
UTILITY
SECTION
(N) INSULATING RED
GLASTIC BARRIER
BARRIER INSTALLATION REQUIREMENTS:
1.INSTALLATION WILL HAVE INSULATED (GLASTIC) RED
BARRIER SEPARATING THE BOTTOM AND TOP
SECTIONS
2.ONLY RIGID BUSSING TO EXTEND THROUGH GLASTIC
BARRIERS
3.BOTH SECTIONS TO BE SEALABLE
4.SEPARATE COVERS TO BE PROVIDED FOR (N)
SECTIONS WHERE THE BARRIER(S) ARE INSTALLED
5.ALL EQUIPMENT MUST MAINTAIN (E) ENVIRONMENTAL
RATING
6.LABELING SHALL BE REQUIRED AT SOLAR AND
UTILITY TERMINATION POINT LOCATED BELOW
GRADE, AT GRADE, OR ON THE BUILDING EXTERIOR.
LABELING SHALL CONSIST OF:
7.MACHINE-ENGRAVED LAMINATED PHENOLIC (OR
EQUIVALENT) TAG
7.1.ONE-QUARTER OF AN INCH WHITE LETTERS ON
RED-COLORED MATERIAL WHICH IS READILY
VISIBLE
7.2.MECHANICALLY ATTACHED TO THE FACE OF THE
TERMINATION COMPARTMENT. THE
COMPARTMENT LABEL(S) SHALL BE WORDED AS:
7.2.1."SOLAR INTERCONNECTION TERMINATION
COMPARTMENT"
7.2.2."UTILITY SERVICE TERMINATION
COMPARTMENT”
8.CONDUCTORS FROM THE (N) GENERATOR FACILITY
ARE NOT TO PASS-THROUGH UTILITY METER OR PULL
SECTIONS
#
CAT5E 600V RATED SHIELDED CABLE.
INSTALLER SHALL FOLLOW
MANUFACTURES RECOMMENDATION FOR
WIRE SIZING BASED ON LENGTH.
EQUIPMENT INDEX
EQUIPMENT TYPE
SYSTEM IDENTIFIER X INDICATES LETTERS
# INDICATES NUMBERS
XX-#.#
SUPPLY SIDE TAP OF INTERCONNECTION
UTILITY SECTION
CUSTOMER
SECTION
SCE PULL SECTION
GLASTIC
BARRIER
32
"
MA
X
2
6
"
SCE METERS
1. PV MODULES (117) QCELLS NORTH
AMERICA Q.PEAK DUO BLK ML-G10.C+ 410
2. (117) SOLAREDGE DC OPTIMIZER U650
3. DC PV AND ESS CONNECTION UNIT W/
INTEGRAL LOAD BREAK DISCONNECT
4. 4A: (3) SOLAREDGE SE11400H-US HOME
HUB [208V] [SI1-SB] [CRD-PCS NEM],
10,000W, 208VAC, 1ø, 3W
4B: (1) SOLAREDGE SE10KUS [208V]
[SI1-SB], 10,000W, 208VAC, 3ø, 4W
5. NOT USED.
6. (1) LOAD CENTER, 200A, 3ø, MIN.208VAC,
MIN. 10KAIC, NEMA 3R
7. NOT USED
8.(N) ACDS-2 SYSTEM AC DISCONNECT
SWITCH, SQUARE D, VHU364R, 600V
RATED, 208V OPERATIONAL, 200A, 3 POLE,
NON-FUSIBLE, NEMA 3R. SEE REFERENCE
SHEETS FOR KAIC RATING.
9. (N) SCE PV PRODUCTION METER SOCKET
ADDRESS: 816 N FIGUEROA ST BLDG B
SOMAH2, COOPER B-LINE, 127TB, 200A,
SERVICE: 3 PHASE 4 WIRE 120/208 VOLT
WYE, 7 JAW, NEMA 3R, EUSERC: 305
10. (N) ACDS-1 SYSTEM UTILITY AC
DISCONNECT SWITCH, SQUARE D,
VH324NR, 240V RATED, 208V
OPERATIONAL, 200A, 3 POLE, FUSIBLE,
NEMA 3R, OR EQUIVALENT ON THE
UTILITIES APPROVED LIST. CLASS J FOR
200KAIC RATING.
11. (E) MAIN SERVICE EQUIPMENT: 3 PHASE
4 WIRE 120/208 VOLT WYE, 800A
12. (N) 3 PHASE: CELL-B-R05-US-S-S4
COMMERCIAL CELL CARD OR
EQUIVALENT, 1 PHASE: MANUFACTURER
INTERGRATED CELL CARD
13. (9) SOLAREDGE BAT-10K1P BATTERIES,
9.70KWH, 5,000DCW, NEMA 3R, MOUNTED
TO WALL OR MANUFACTURER FLOOR
MOUNT KIT
14. NOT USED
15. NOT USED
16. NOT USED
1.(E) MAIN SWITCHGEAR AND (N) POINT OF
AC INTERCONNECTION. ALL
CONNECTIONS MADE INSIDE (E)
SWITCHGEAR AT OTHER THAN CIRCUIT
BREAKERS OR FUSED SWITCHES LISTED
FOR USE WITH THAT SWITCHGEAR SHALL
BE PERFORMED FOLLOWING
MANUFACTURERS INSTRUCTIONS OR BE
RE-LISTED BY A NRTL. ALL TERMINATIONS
OF ALUMINUM CONDUCTORS SHALL BE
WITH HIGH PRESS CRIMP LUGS ONLY.
WARNING LABEL DETAIL 1/E800
2.(E) UTILITY TENANT LOAD METER. UTILITY
REFERENCE METER NUMBER:
256000-221416
3.(N) PV SYSTEM UTILITY AC DISCONNECT
'ACDS-1'. WARNING LABEL DETAIL 1/E810
4.(N) UTILITY BIDIRECTIONAL KWH METER.
WARNING LABEL DETAIL 1/E810
5.(N) PV SYSTEM MAINTENANCE AC
DISCONNECT 'ACDS-2'. WARNING LABEL
DETAIL 2/E800 & 1/E810
6.NOT USED
7.(N) GRID-INTERACTIVE PV INVERTER
LISTED TO UL 1741 WITH GROUND FAULT
DETECTION & INTERRUPTION. WARNING
LABEL DETAIL 15/E800.
8.NOT USED
9.NOT USED
10.FOR SUPPLY SIDE CONNECTIONS, A
PLAQUE SHALL BE INSTALLED AT THE
MAIN SERVICE DISCONNECTING DEVICE
AND THE PV SYSTEM UTILITY AC
DISCONNECT INDICATING THE LOCATION
OF THE RESPECTIVE SERVICE
DISCONNECT. WARNING LABEL DETAIL
1/E800 & 1/E810
11.NOT USED
12.CONDUCTORS RUN IN PARALLEL SHALL
BE INSTALLED PER ART 310.4/310.10(G)
AND 250.122 (F).
13.NOT USED
14.NEW PULL/JUNCTION BOXES. PROVIDE
SERVICE LOOP IN ALL DC BRANCH
CONDUCTORS SOURCED FROM
ROOFTOPS, MIN LOOP RADIUS = 12X
CONDUCTOR DIAMETER.
15.NOT USED
16.(N) INVERTER INTERNAL DC DISCONNECT
SWITCH(ES). WARNING LABEL DETAIL
3/E800
17.NOT USED
18.(N) PV MODULE LISTED TO UL 1703.
19.EXTRA MODULES THAT ARE UNABLE TO
BE PAIRED WILL HAVE THEIR OWN
OPTIMIZER.
20.(N) COMMUNICATION WIRING TO FOLLOW
MANUFACTURING SPECIFICATIONS.
21.DURING UTILITY GRID OUTAGE THE PV
GENERATION AND BESS WILL
DISCONNECT FROM THE GRID AND
REMAIN DISCONNECTED UNTIL GRID
VOLTAGE IS RESTORED TO THE
ACCEPTED MEASURE.
22.BATTERY AC OUTPUT POWER IS LIMITED
TO THE CORRESPONDING INVERTER OR
TOTAL BATTERIES CONNECTED TO A
SINGLE INVERTER,WHICHEVER IS LOWER.
23.BATTERIES SHOULD NOT BE INSTALLED IN
DIRECT SUNLIGHT OR LOCATIONS
SUBJECTED TO WATER SPRAY.
SPRINKLERS SHOULD BE DIVERTED
WHEN NECESSARY.
24.BATTERIES CAN COMMUNICATE
WIRELESSLY OR VIA RS-485 TO INVERTER.
BATTERIES WITHIN 150' (IDEALLY 50') OF
RESPECTIVE INVERTER CAN USE
WIRELESS COMMUNICATIONS VIA SEDG
HOME NETWORK CARD.
25.COMBINED PV AND BESS OUTPUT POWER
IS LIMITED TO THE INVERTER AC RATING.
26.NOT USED
816 N FIGUEROA ST BLDG B SOMAH2
POI-2 DC STRING SCHEDULE
STR-A STR-B STR-C
TAG DESTINATION CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
DC-2.1.1 INV-2.1 160 0.68%410 10 U650 8 / 16¹175 0.70%410 10 U650 8 / 16¹160 0.61%410 9 U650 8 / 16¹
DC-2.2.2 INV-2.2 140 0.59%410 10 U650 8 / 16¹100 0.40%410 10 U650 8 / 16¹105 0.40%410 9 U650 8 / 16¹
DC-2.3.3 INV-2.3 60 0.25%410 10 U650 8 / 16¹50 0.20%410 10 U650 8 / 16¹45 0.17%410 9 U650 8 / 16¹
DC-2.4.4 INV-2.4 80 0.33%410 10 U650 10 / 19¹90 0.35%410 10 U650 10 / 19¹130 0.54%410 10 U650 10 / 19¹
¹ MAXIMUM STRING LENGTH IS USING MANUFACTURES EXCEPTION
² LENGTHS ARE ESTIMATED FOR CALCULATIONS, CONTRACTOR IS RESPONSIBLE FOR MEASUREMENTS AND TAKEOFFS
³ WHERE EXPOSED TO PHYSICAL DAMAGE #6 TO BE USED PER NEC 250.120(C)
⁴ AFC VALUES ARE CALCULATED BASED ON WIRE LENGTHS. LENGTHS SHOULD REMAIN GREATER THAN OR EQUAL TO THE LENGTH LISTED IN THE TABLE.
POI-2 DC WIRE SCHEDULE
TAG WIRE GAUGE CONDUCTOR
JACKET
MAX ISC 1.25 X MAX
CIRCUIT AMPS
CIRCUIT FUSE
RATING
CCC PER
CONDUIT
MAX AMBIENT
TEMP (C)
C.O.U TEMP.
DERATE
C.O.U CONDUIT
FILL DERATE
75°C AMPACITY COMPLIES WITH
690.8(B)(1)
90°C AMPACITY
WITH C.O.U
COMPLIES WITH
690.8(B)(2)
FAULT CURRENT
FROM PARALLEL
STRINGS
COMPLIES WITH
690.9(A)
GROUNDING
PER CONDUIT
GROUNDING ³EMT RMC PVC 40 PVC 80
DC-2.1.1 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-2.2.2 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-2.3.3 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-2.4.4 CU #10 THWN2 15 18.75 25 A 6 38 91%80%35 YES 29.1 YES 25 YES 3 CU #10 3/4"3/4"3/4"1"
BATTERY OPERATION NOTE:
INVERTERS WITH ESS ARE CERTIFIED TO UL 1741
PCS CRD AND WILL HAVE EXPORT ONLY MODES
ENABLED. THEY WILL UTILIZE EXCESS PV POWER
TO CHARGE THE BATTERIES AND THE BATTERIES
WILL DISCHARGE DURING SET HOURS.
THE PRODUCERS STORAGE DEVICE(S) WILL NOT
CONSUME POWER FROM THE DISTRIBUTION
PROVIDERS DISTRIBUTION SYSTEM AT ANY TIME
GRID EXPORT IS ALLOWED THROUGH NEMV METER
DURING UTILITY GRID OUTAGE THE PV
GENERATION AND BESS WILL DISCONNECT FROM
THE GRID AND REMAINS DISCONNECTED UNTIL
GRID VOLTAGE IS RESTORED TO THE ACCEPTABLE
MEASURE.
NOTE:
RIGID METAL CONDUIT (RMC) IS REQUIRED FOR THE NEW
SERVICE CONDUCTORS PRIOR TO METERING PER CITY
POLICY. TAPPED CONDUCTORS TO BE ROUTED IN RIGID
METAL CONDUIT PER CITY POLICY.
POI-2 AC WIRE SCHEDULE
LABEL DESTINATION NOMINAL VAC LINE
SELECTION
FLA FLAX1.25 OCPD PHASE
CONDUCTOR
NEUTRAL
CONDUCTOR
GROUNDING
CONDUCTOR
CONDUCTORS
PER PHASE
CONDUIT QTY 75°C AMPS 90°C AMPS 90°C AMPS W/
C.O.U
C.O.U TEMP
DERATE
C.O.U
CONDUIT FILL
CIRCUIT
LENGTH ²
SEGMENT
VD%
DC/AC RATIO AFC START AFC END ⁴EMT IMC PVC 40 PVC 80
INV-2.1 LC-2.1 208 A-B 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%118.9%4,194 3,872 3/4"3/4"3/4"3/4"
INV-2.2 LC-2.1 208 B-C 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%118.9%4,194 3,872 3/4"3/4"3/4"3/4"
INV-2.3 LC-2.1 208 C-A 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%118.9%4,194 3,872 3/4"3/4"3/4"3/4"
INV-2.4 LC-2.1 208 A-B-C 27.8 34.8 35 CU #8 CU #10 CU #10 1 1 50 55 50.1 91%100%5 0.09%123.0%4,194 3,713 3/4"3/4"3/4"3/4"
LC-2.1 AC-2.2 208 A-B-C 111.0 138.8 150 CU #1/0 CU #6 CU #6 1 1 150 170 154.7 91%100%40 0.43%--5,120 4,194 1 1/2"1 1/4"1 1/2"1 1/2"
AC-2.2 AC-2.1 208 A-B-C 111.0 138.8 150 CU #1/0 CU #6 CU #6 1 1 150 170 154.7 91%100%5 0.05%--5,265 5,120 1 1/2"1 1/4"1 1/2"1 1/2"
AC-2.1 POI-2.2 208 A-B-C 111.0 138.8 150 CU #2/0 CU #2/0 CU #4 1 1 175 195 142.0 91%80%5 0.04%--42,000 35,361 2"2"2"2"
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
POI-2 ONE LINE
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E601
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
##KEYED NOTES#EQUIPMENT NOTES#
COMMUNICATION
CIRCUIT IDENTIFIER
##KEYED NOTES#EQUIPMENT NOTES#
A INTERCONNECTION LOCATION
NTS
SYSTEM SUMMARY
40.00 ACKW | 51.25 DCKW | 47.33 CECKW
30.00 BESS ACKW | 87.30 BESS KWH
TOTAL FAULT CURRENTS
UTILITY: 42,000A | GENERATORS: 280.55A
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
3
.
1
.
A
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ST
R
-
3
.
1
.
B
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
3
.
1
.
C
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ES-2
DC-3.1.1
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
A-B
60A
INV-3.1
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
3
.
2
.
A
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ST
R
-
3
.
2
.
B
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
3
.
2
.
C
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ES-2
DC-3.2.2
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
B-C
60A
INV-3.2
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
3
.
3
.
A
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ST
R
-
3
.
3
.
B
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ST
R
-
3
.
3
.
C
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
ES-2
DC-3.3.3
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
C-A
60A
INV-3.3
18
14
1
ST
R
-
3
.
4
.
A
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ST
R
-
3
.
4
.
B
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ST
R
-
3
.
4
.
C
-
(
1
0
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
0
)
U
6
5
0
O
P
T
S
.
DC-3.4.4
3
17
7
1
4B
12
2
A-B-C
35A
INV-3.4
6
LC-3.1
6
8
5
(N) ACDS-2 SYSTEM AC DISCONNECT
SWITCH,, SQUARE D, VHU364R, 600V RATED,
208V OPERATIONAL, 200A, 3 POLE,
NON-FUSIBLE, NEMA 3R. SEE REFERENCE
SHEETS FOR KAIC RATING.
AC-3.2
M9
4
(N) SCE PV PRODUCTION METER SOCKET
ADDRESS: 816 N FIGUEROA ST BLDG C
SOMAH3, COOPER B-LINE, 127TB, 200 A,
SERVICE 3 PHASE 4 WIRE 120/208 VOLT WYE,
NEMA 3R
AC-3.2
10
3
(N) ACDS-1 SYSTEM UTILITY AC DISCONNECT
SWITCH, SQUARE D, VH324NR, 240V RATED,
208V OPERATIONAL, 200A, 3 POLE, FUSIBLE,
NEMA 3R, OR EQUIVALENT ON THE UTILITIES
APPROVED LIST. CLASS R FUSE WITH
REJECTION CLIPS OR CLASS J FOR 200KAIC
RATING.
A-B-C
150AAC-3.1
M
M
M
M
M FACILITY
LOADS
(N) TENANT
METERS (TYP.)
UTILITY METER REFERENCE NUMBER:
234010-284202
SCE UTILITY GRID 208V,
3ø,4W
(N) LUGS ON (E)
HOLES
-
A
11101
800A
CUSTOMER
SECTION
UTILITY
SECTION
(N) INSULATING RED
GLASTIC BARRIER
BARRIER INSTALLATION REQUIREMENTS:
1.INSTALLATION WILL HAVE INSULATED (GLASTIC) RED
BARRIER SEPARATING THE BOTTOM AND TOP
SECTIONS
2.ONLY RIGID BUSSING TO EXTEND THROUGH GLASTIC
BARRIERS
3.BOTH SECTIONS TO BE SEALABLE
4.SEPARATE COVERS TO BE PROVIDED FOR (N)
SECTIONS WHERE THE BARRIER(S) ARE INSTALLED
5.ALL EQUIPMENT MUST MAINTAIN (E) ENVIRONMENTAL
RATING
6.LABELING SHALL BE REQUIRED AT SOLAR AND
UTILITY TERMINATION POINT LOCATED BELOW
GRADE, AT GRADE, OR ON THE BUILDING EXTERIOR.
LABELING SHALL CONSIST OF:
7.MACHINE-ENGRAVED LAMINATED PHENOLIC (OR
EQUIVALENT) TAG
7.1.ONE-QUARTER OF AN INCH WHITE LETTERS ON
RED-COLORED MATERIAL WHICH IS READILY
VISIBLE
7.2.MECHANICALLY ATTACHED TO THE FACE OF THE
TERMINATION COMPARTMENT. THE
COMPARTMENT LABEL(S) SHALL BE WORDED AS:
7.2.1."SOLAR INTERCONNECTION TERMINATION
COMPARTMENT"
7.2.2."UTILITY SERVICE TERMINATION
COMPARTMENT”
8.CONDUCTORS FROM THE (N) GENERATOR FACILITY
ARE NOT TO PASS-THROUGH UTILITY METER OR PULL
SECTIONS
#
CAT5E 600V RATED SHIELDED CABLE.
INSTALLER SHALL FOLLOW
MANUFACTURES RECOMMENDATION FOR
WIRE SIZING BASED ON LENGTH.
EQUIPMENT INDEX
EQUIPMENT TYPE
SYSTEM IDENTIFIER X INDICATES LETTERS
# INDICATES NUMBERS
XX-#.#
SUPPLY SIDE TAP OF
INTERCONNECTION
UTILITY SECTION
CUSTOMER
SECTION
SCE METERS
SCE PULL SECTION
32
"
GLASTIC BARRIER
MA
X
2
6
"
1. PV MODULES (125) QCELLS NORTH
AMERICA Q.PEAK DUO BLK ML-G10.C+ 410
2. (125) SOLAREDGE DC OPTIMIZER U650
3. DC PV AND ESS CONNECTION UNIT W/
INTEGRAL LOAD BREAK DISCONNECT
4. 4A: (3) SOLAREDGE SE11400H-US HOME
HUB [208V] [SI1-SB] [CRD-PCS NEM],
10,000W, 208VAC, 1ø, 3W
4B: (1) SOLAREDGE SE10KUS [208V]
[SI1-SB], 10,000W, 208VAC, 3ø, 4W
5. NOT USED.
6. (1) LOAD CENTER, 200A, 3ø, MIN.208VAC,
MIN. 10KAIC, NEMA 3R
7. NOT USED
8.(N) ACDS-2 SYSTEM AC DISCONNECT
SWITCH, SQUARE D, VHU364R, 600V
RATED, 208V OPERATIONAL, 200A, 3 POLE,
NON-FUSIBLE, NEMA 3R. SEE REFERENCE
SHEETS FOR KAIC RATING.
9. (N) SCE PV PRODUCTION METER SOCKET
ADDRESS: 816 N FIGUEROA ST BLDG C
SOMAH3, COOPER B-LINE, 127TB, 200A,
SERVICE: 3 PHASE 4 WIRE 120/208 VOLT
WYE, 7 JAW, NEMA 3R, EUSERC: 305
10. (N) ACDS-1 SYSTEM UTILITY AC
DISCONNECT SWITCH, SQUARE D,
VH324NR, 240V RATED, 208V
OPERATIONAL, 200A, 3 POLE, FUSIBLE,
NEMA 3R, OR EQUIVALENT ON THE
UTILITIES APPROVED LIST. CLASS J FOR
200KAIC RATING.
11. (E) MAIN SERVICE EQUIPMENT: 3 PHASE
4 WIRE 120/208 VOLT WYE, 800A
12. (N) 3 PHASE: CELL-B-R05-US-S-S4
COMMERCIAL CELL CARD OR
EQUIVALENT, 1 PHASE: MANUFACTURER
INTERGRATED CELL CARD
13. (9) SOLAREDGE BAT-10K1P BATTERIES,
9.70KWH, 5,000DCW, NEMA 3R, MOUNTED
TO WALL OR MANUFACTURER FLOOR
MOUNT KIT
14. NOT USED
15. NOT USED
16. NOT USED
1.(E) MAIN SWITCHGEAR AND (N) POINT OF
AC INTERCONNECTION. ALL
CONNECTIONS MADE INSIDE (E)
SWITCHGEAR AT OTHER THAN CIRCUIT
BREAKERS OR FUSED SWITCHES LISTED
FOR USE WITH THAT SWITCHGEAR SHALL
BE PERFORMED FOLLOWING
MANUFACTURERS INSTRUCTIONS OR BE
RE-LISTED BY A NRTL. ALL TERMINATIONS
OF ALUMINUM CONDUCTORS SHALL BE
WITH HIGH PRESS CRIMP LUGS ONLY.
WARNING LABEL DETAIL 1/E800
2.(E) UTILITY TENANT LOAD METER. UTILITY
REFERENCE METER NUMBER:
234010-284202
3.(N) PV SYSTEM UTILITY AC DISCONNECT
'ACDS-1'. WARNING LABEL DETAIL 1/E810
4.(N) UTILITY BIDIRECTIONAL KWH METER.
WARNING LABEL DETAIL 1/E810
5.(N) PV SYSTEM MAINTENANCE AC
DISCONNECT 'ACDS-2'. WARNING LABEL
DETAIL 2/E800 & 1/E810
6.NOT USED
7.(N) GRID-INTERACTIVE PV INVERTER
LISTED TO UL 1741 WITH GROUND FAULT
DETECTION & INTERRUPTION. WARNING
LABEL DETAIL 15/E800.
8.NOT USED
9.NOT USED
10.FOR SUPPLY SIDE CONNECTIONS, A
PLAQUE SHALL BE INSTALLED AT THE
MAIN SERVICE DISCONNECTING DEVICE
AND THE PV SYSTEM UTILITY AC
DISCONNECT INDICATING THE LOCATION
OF THE RESPECTIVE SERVICE
DISCONNECT. WARNING LABEL DETAIL
1/E800 & 1/E810
11.NOT USED
12.CONDUCTORS RUN IN PARALLEL SHALL
BE INSTALLED PER ART 310.4/310.10(G)
AND 250.122 (F).
13.NOT USED
14.NEW PULL/JUNCTION BOXES. PROVIDE
SERVICE LOOP IN ALL DC BRANCH
CONDUCTORS SOURCED FROM
ROOFTOPS, MIN LOOP RADIUS = 12X
CONDUCTOR DIAMETER.
15.NOT USED
16.(N) INVERTER INTERNAL DC DISCONNECT
SWITCH(ES). WARNING LABEL DETAIL
3/E800
17.NOT USED
18.(N) PV MODULE LISTED TO UL 1703.
19.EXTRA MODULES THAT ARE UNABLE TO
BE PAIRED WILL HAVE THEIR OWN
OPTIMIZER.
20.(N) COMMUNICATION WIRING TO FOLLOW
MANUFACTURING SPECIFICATIONS.
21.DURING UTILITY GRID OUTAGE THE PV
GENERATION AND BESS WILL
DISCONNECT FROM THE GRID AND
REMAIN DISCONNECTED UNTIL GRID
VOLTAGE IS RESTORED TO THE
ACCEPTED MEASURE.
22.BATTERY AC OUTPUT POWER IS LIMITED
TO THE CORRESPONDING INVERTER OR
TOTAL BATTERIES CONNECTED TO A
SINGLE INVERTER,WHICHEVER IS LOWER.
23.BATTERIES SHOULD NOT BE INSTALLED IN
DIRECT SUNLIGHT OR LOCATIONS
SUBJECTED TO WATER SPRAY.
SPRINKLERS SHOULD BE DIVERTED
WHEN NECESSARY.
24.BATTERIES CAN COMMUNICATE
WIRELESSLY OR VIA RS-485 TO INVERTER.
BATTERIES WITHIN 150' (IDEALLY 50') OF
RESPECTIVE INVERTER CAN USE
WIRELESS COMMUNICATIONS VIA SEDG
HOME NETWORK CARD.
25.COMBINED PV AND BESS OUTPUT POWER
IS LIMITED TO THE INVERTER AC RATING.
26.NOT USED
816 N FIGUEROA ST BLDG C SOMAH3
POI-3 DC STRING SCHEDULE
STR-A STR-B STR-C
TAG DESTINATION CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
CIRCUIT LENGTH ²VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
DC-3.1.1 INV-3.1 45 0.21%410 11 U650 8 / 16¹70 0.28%410 10 U650 8 / 16¹60 0.25%410 10 U650 8 / 16¹
DC-3.2.2 INV-3.2 60 0.28%410 11 U650 8 / 16¹110 0.44%410 10 U650 8 / 16¹130 0.55%410 10 U650 8 / 16¹
DC-3.3.3 INV-3.3 150 0.70%410 11 U650 8 / 16¹180 0.72%410 10 U650 8 / 16¹185 0.79%410 10 U650 8 / 16¹
DC-3.4.4 INV-3.4 90 0.41%410 11 U650 10 / 19¹50 0.22%410 11 U650 10 / 19¹45 0.19%410 10 U650 10 / 19¹
¹ MAXIMUM STRING LENGTH IS USING MANUFACTURES EXCEPTION
² LENGTHS ARE ESTIMATED FOR CALCULATIONS, CONTRACTOR IS RESPONSIBLE FOR MEASUREMENTS AND TAKEOFFS
³ WHERE EXPOSED TO PHYSICAL DAMAGE #6 TO BE USED PER NEC 250.120(C)
⁴ AFC VALUES ARE CALCULATED BASED ON WIRE LENGTHS. LENGTHS SHOULD REMAIN GREATER THAN OR EQUAL TO THE LENGTH LISTED IN THE TABLE.
POI-3 DC WIRE SCHEDULE
TAG WIRE GAUGE CONDUCTOR
JACKET
MAX ISC 1.25 X MAX
CIRCUIT AMPS
CIRCUIT FUSE
RATING
CCC PER
CONDUIT
MAX AMBIENT
TEMP (C)
C.O.U TEMP.
DERATE
C.O.U CONDUIT
FILL DERATE
75°C AMPACITY COMPLIES WITH
690.8(B)(1)
90°C AMPACITY
WITH C.O.U
COMPLIES WITH
690.8(B)(2)
FAULT CURRENT
FROM PARALLEL
STRINGS
COMPLIES WITH
690.9(A)
GROUNDING
PER CONDUIT
GROUNDING ³EMT RMC PVC 40 PVC 80
DC-3.1.1 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-3.2.2 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-3.3.3 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-3.4.4 CU #10 THWN2 15 18.75 25 A 6 38 91%80%35 YES 29.1 YES 25 YES 3 CU #10 3/4"3/4"3/4"1"
BATTERY OPERATION NOTE:
INVERTERS WITH ESS ARE CERTIFIED TO UL 1741
PCS CRD AND WILL HAVE EXPORT ONLY MODES
ENABLED. THEY WILL UTILIZE EXCESS PV POWER
TO CHARGE THE BATTERIES AND THE BATTERIES
WILL DISCHARGE DURING SET HOURS.
THE PRODUCERS STORAGE DEVICE(S) WILL NOT
CONSUME POWER FROM THE DISTRIBUTION
PROVIDERS DISTRIBUTION SYSTEM AT ANY TIME
GRID EXPORT IS ALLOWED THROUGH NEMV METER
DURING UTILITY GRID OUTAGE THE PV
GENERATION AND BESS WILL DISCONNECT FROM
THE GRID AND REMAINS DISCONNECTED UNTIL
GRID VOLTAGE IS RESTORED TO THE ACCEPTABLE
MEASURE.
NOTE:
RIGID METAL CONDUIT (RMC) IS REQUIRED FOR THE NEW
SERVICE CONDUCTORS PRIOR TO METERING PER CITY
POLICY. TAPPED CONDUCTORS TO BE ROUTED IN RIGID
METAL CONDUIT PER CITY POLICY.
POI-3 AC WIRE SCHEDULE
LABEL DESTINATION NOMINAL VAC LINE
SELECTION
FLA FLAX1.25 OCPD PHASE
CONDUCTOR
NEUTRAL
CONDUCTOR
GROUNDING
CONDUCTOR
CONDUCTORS
PER PHASE
CONDUIT QTY 75°C AMPS 90°C AMPS 90°C AMPS W/
C.O.U
C.O.U TEMP
DERATE
C.O.U
CONDUIT FILL
CIRCUIT
LENGTH ²
SEGMENT
VD%
DC/AC RATIO AFC START AFC END ⁴EMT IMC PVC 40 PVC 80
INV-3.1 LC-3.1 208 A-B 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%127.1%4,008 3,713 3/4"3/4"3/4"3/4"
INV-3.2 LC-3.1 208 B-C 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%127.1%4,008 3,713 3/4"3/4"3/4"3/4"
INV-3.3 LC-3.1 208 C-A 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%127.1%4,008 3,713 3/4"3/4"3/4"3/4"
INV-3.4 LC-3.1 208 A-B-C 27.8 34.8 35 CU #8 CU #10 CU #10 1 1 50 55 50.1 91%100%5 0.09%131.2%4,008 3,566 3/4"3/4"3/4"3/4"
LC-3.1 AC-3.2 208 A-B-C 111.0 138.8 150 CU #1/0 CU #6 CU #6 1 1 150 170 154.7 91%100%35 0.37%--4,721 4,008 1 1/2"1 1/4"1 1/2"1 1/2"
AC-3.2 AC-3.1 208 A-B-C 111.0 138.8 150 CU #1/0 CU #6 CU #6 1 1 150 170 154.7 91%100%15 0.16%--5,111 4,721 1 1/2"1 1/4"1 1/2"1 1/2"
AC-3.1 POI-3.3 208 A-B-C 111.0 138.8 150 CU #2/0 CU #2/0 CU #4 1 1 175 195 142.0 91%80%8 0.07%--42,000 32,298 2"2"2"2"
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
POI-3 ONE LINE
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E602
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
#
A INTERCONNECTION LOCATION
NTS
SYSTEM SUMMARY
40.00 ACKW | 66.83 DCKW | 61.63 CECKW
30.00 BESS ACKW | 87.30 BESS KWH
SUPPLY SIDE TAP INTERCONNECTION
UTILITY SECTION
CUSTOMER SECTION
32
"
GLASTIC BARRIER MA
X
2
6
"
SCE PULL SECTION
#
CAT5E 600V RATED SHIELDED CABLE.
INSTALLER SHALL FOLLOW
MANUFACTURES RECOMMENDATION FOR
WIRE SIZING BASED ON LENGTH.
EQUIPMENT INDEX
EQUIPMENT TYPE
SYSTEM IDENTIFIER X INDICATES LETTERS
# INDICATES NUMBERS
XX-#.#
1. PV MODULES (163) QCELLS NORTH
AMERICA Q.PEAK DUO BLK ML-G10.C+ 410
2. (163) SOLAREDGE DC OPTIMIZER U650
3. DC PV AND ESS CONNECTION UNIT W/
INTEGRAL LOAD BREAK DISCONNECT
4. 4A: (3) SOLAREDGE SE11400H-US HOME
HUB [208V] [SI1-SB] [CRD-PCS NEM],
10,000W, 208VAC, 1ø, 3W
4B: (1) SOLAREDGE SE10KUS [208V]
[SI1-SB], 10,000W, 208VAC, 3ø, 4W
5. NOT USED.
6. (1) LOAD CENTER, 200A, 3ø, MIN.208VAC,
MIN. 10KAIC, NEMA 3R
7. NOT USED
8.(N) ACDS-2 SYSTEM AC DISCONNECT
SWITCH, SQUARE D, VHU364R, 600V
RATED, 208V OPERATIONAL, 200A, 3 POLE,
NON-FUSIBLE, NEMA 3R. SEE REFERENCE
SHEETS FOR KAIC RATING.
9. (N) SCE PV PRODUCTION METER SOCKET
ADDRESS: 816 N FIGUEROA ST BLDG D
SOMAH4, COOPER B-LINE, 127TB, 200A,
SERVICE: 3 PHASE 4 WIRE 120/208 VOLT
WYE, 7 JAW, NEMA 3R, EUSERC: 305
10. (N) ACDS-1 SYSTEM UTILITY AC
DISCONNECT SWITCH, SQUARE D,
VH324NR, 240V RATED, 208V
OPERATIONAL, 200A, 3 POLE, FUSIBLE,
NEMA 3R, OR EQUIVALENT ON THE
UTILITIES APPROVED LIST. CLASS J FOR
200KAIC RATING.
11. (E) MAIN SERVICE EQUIPMENT: 3 PHASE
4 WIRE 120/208 VOLT WYE, 800A
12. (N) 3 PHASE: CELL-B-R05-US-S-S4
COMMERCIAL CELL CARD OR
EQUIVALENT, 1 PHASE: MANUFACTURER
INTERGRATED CELL CARD
13. (9) SOLAREDGE BAT-10K1P BATTERIES,
9.70KWH, 5,000DCW, NEMA 3R, MOUNTED
TO WALL OR MANUFACTURER FLOOR
MOUNT KIT
14. NOT USED
15. NOT USED
16. NOT USED
1.(E) MAIN SWITCHGEAR AND (N) POINT OF
AC INTERCONNECTION. ALL
CONNECTIONS MADE INSIDE (E)
SWITCHGEAR AT OTHER THAN CIRCUIT
BREAKERS OR FUSED SWITCHES LISTED
FOR USE WITH THAT SWITCHGEAR SHALL
BE PERFORMED FOLLOWING
MANUFACTURERS INSTRUCTIONS OR BE
RE-LISTED BY A NRTL. ALL TERMINATIONS
OF ALUMINUM CONDUCTORS SHALL BE
WITH HIGH PRESS CRIMP LUGS ONLY.
WARNING LABEL DETAIL 1/E800
2.(E) UTILITY TENANT LOAD METER. UTILITY
REFERENCE METER NUMBER:
234010-215697
3.(N) PV SYSTEM UTILITY AC DISCONNECT
'ACDS-1'. WARNING LABEL DETAIL 1/E810
4.(N) UTILITY BIDIRECTIONAL KWH METER.
WARNING LABEL DETAIL 1/E810
5.(N) PV SYSTEM MAINTENANCE AC
DISCONNECT 'ACDS-2'. WARNING LABEL
DETAIL 2/E800 & 1/E810
6.NOT USED
7.(N) GRID-INTERACTIVE PV INVERTER
LISTED TO UL 1741 WITH GROUND FAULT
DETECTION & INTERRUPTION. WARNING
LABEL DETAIL 15/E800.
8.NOT USED
9.NOT USED
10.FOR SUPPLY SIDE CONNECTIONS, A
PLAQUE SHALL BE INSTALLED AT THE
MAIN SERVICE DISCONNECTING DEVICE
AND THE PV SYSTEM UTILITY AC
DISCONNECT INDICATING THE LOCATION
OF THE RESPECTIVE SERVICE
DISCONNECT. WARNING LABEL DETAIL
1/E800 & 1/E810
11.NOT USED
12.CONDUCTORS RUN IN PARALLEL SHALL
BE INSTALLED PER ART 310.4/310.10(G)
AND 250.122 (F).
13.NOT USED
14.NEW PULL/JUNCTION BOXES. PROVIDE
SERVICE LOOP IN ALL DC BRANCH
CONDUCTORS SOURCED FROM
ROOFTOPS, MIN LOOP RADIUS = 12X
CONDUCTOR DIAMETER.
15.NOT USED
16.(N) INVERTER INTERNAL DC DISCONNECT
SWITCH(ES). WARNING LABEL DETAIL
3/E800
17.NOT USED
18.(N) PV MODULE LISTED TO UL 1703.
19.EXTRA MODULES THAT ARE UNABLE TO
BE PAIRED WILL HAVE THEIR OWN
OPTIMIZER.
20.(N) COMMUNICATION WIRING TO FOLLOW
MANUFACTURING SPECIFICATIONS.
21.DURING UTILITY GRID OUTAGE THE PV
GENERATION AND BESS WILL
DISCONNECT FROM THE GRID AND
REMAIN DISCONNECTED UNTIL GRID
VOLTAGE IS RESTORED TO THE
ACCEPTED MEASURE.
22.BATTERY AC OUTPUT POWER IS LIMITED
TO THE CORRESPONDING INVERTER OR
TOTAL BATTERIES CONNECTED TO A
SINGLE INVERTER,WHICHEVER IS LOWER.
23.BATTERIES SHOULD NOT BE INSTALLED IN
DIRECT SUNLIGHT OR LOCATIONS
SUBJECTED TO WATER SPRAY.
SPRINKLERS SHOULD BE DIVERTED
WHEN NECESSARY.
24.BATTERIES CAN COMMUNICATE
WIRELESSLY OR VIA RS-485 TO INVERTER.
BATTERIES WITHIN 150' (IDEALLY 50') OF
RESPECTIVE INVERTER CAN USE
WIRELESS COMMUNICATIONS VIA SEDG
HOME NETWORK CARD.
25.COMBINED PV AND BESS OUTPUT POWER
IS LIMITED TO THE INVERTER AC RATING.
26.NOT USED
816 N FIGUEROA ST BLDG D SOMAH4
BATTERY OPERATION NOTE:
INVERTERS WITH ESS ARE CERTIFIED TO UL 1741
PCS CRD AND WILL HAVE EXPORT ONLY MODES
ENABLED. THEY WILL UTILIZE EXCESS PV POWER
TO CHARGE THE BATTERIES AND THE BATTERIES
WILL DISCHARGE DURING SET HOURS.
THE PRODUCERS STORAGE DEVICE(S) WILL NOT
CONSUME POWER FROM THE DISTRIBUTION
PROVIDERS DISTRIBUTION SYSTEM AT ANY TIME
GRID EXPORT IS ALLOWED THROUGH NEMV METER
DURING UTILITY GRID OUTAGE THE PV
GENERATION AND BESS WILL DISCONNECT FROM
THE GRID AND REMAINS DISCONNECTED UNTIL
GRID VOLTAGE IS RESTORED TO THE ACCEPTABLE
MEASURE.
NOTE:
RIGID METAL CONDUIT (RMC) IS REQUIRED FOR THE NEW
SERVICE CONDUCTORS PRIOR TO METERING PER CITY
POLICY. TAPPED CONDUCTORS TO BE ROUTED IN RIGID
METAL CONDUIT PER CITY POLICY.
##KEYED NOTES#EQUIPMENT NOTES#
COMMUNICATION
CIRCUIT IDENTIFIER
###
COMMUNICATION
CIRCUIT IDENTIFIER
TOTAL FAULT CURRENTS
UTILITY: 42,000A | GENERATORS: 280.55A
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
4
.
1
.
A
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
4
.
1
.
B
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
4
.
1
.
C
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ES-2
DC-4.1.1
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
A-B
60A
INV-4.1
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
4
.
2
.
A
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
4
.
2
.
B
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
4
.
2
.
C
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ES-2
DC-4.2.2
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
B-C
60A
INV-4.2
+-
18
14
1
13
14
ES-1
(3
)
S
O
L
A
R
E
D
G
E
B
A
T
-
1
0
K
1
P
B
A
T
T
E
R
I
E
(
S
)
ST
R
-
4
.
3
.
A
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
4
.
3
.
B
-
(
1
2
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
2
)
U
6
5
0
O
P
T
S
.
ST
R
-
4
.
3
.
C
-
(
1
1
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
1
)
U
6
5
0
O
P
T
S
.
ES-2
DC-4.3.3
SO
L
A
R
3
16 BA
T
T
E
R
Y
7
12
4A
C-A
60A
INV-4.3
18
14
1
ST
R
-
4
.
4
.
A
-
(
1
9
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
9
)
U
6
5
0
O
P
T
S
.
ST
R
-
4
.
4
.
B
-
(
1
9
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
9
)
U
6
5
0
O
P
T
S
.
ST
R
-
4
.
4
.
C
-
(
1
8
)
4
1
0
W
M
O
D
U
L
E
W
/
(
1
8
)
U
6
5
0
O
P
T
S
.
DC-4.4.4
3
16
7
1
4B
12
2
A-B-C
35A
INV-4.4
6
LC-4.1
6
8
5
(N) ACDS-2 SYSTEM AC DISCONNECT
SWITCH,, SQUARE D, VHU364R, 600V RATED,
208V OPERATIONAL, 200A, 3 POLE,
NON-FUSIBLE, NEMA 3R. SEE REFERENCE
SHEETS FOR KAIC RATING.
AC-4.2
M9
4
(N) SCE PV PRODUCTION METER SOCKET
ADDRESS: 816 N FIGUEROA ST BLDG D
SOMAH4, COOPER B-LINE, 127TB, 200 A,
SERVICE 3 PHASE 4 WIRE 120/208 VOLT WYE,
NEMA 3R
AC-4.2
10
3
(N) ACDS-1 SYSTEM UTILITY AC DISCONNECT
SWITCH, SQUARE D, VH324NR, 240V RATED,
208V OPERATIONAL, 200A, 3 POLE, FUSIBLE,
NEMA 3R, OR EQUIVALENT ON THE UTILITIES
APPROVED LIST. CLASS R FUSE WITH
REJECTION CLIPS OR CLASS J FOR 200KAIC
RATING.
A-B-C
150AAC-4.1
M
M
M
M
M FACILITY
LOADS
(N) TENANT
METERS (TYP.)
UTILITY METER REFERENCE NUMBER:
234010-215697
SCE UTILITY GRID 208V,
3ø,4W
(N) LUGS ON (E)
HOLES
-
A
11101
800A
CUSTOMER
SECTION
UTILITY
SECTION
(N) INSULATING RED
GLASTIC BARRIER
BARRIER INSTALLATION REQUIREMENTS:
1.INSTALLATION WILL HAVE INSULATED (GLASTIC) RED
BARRIER SEPARATING THE BOTTOM AND TOP
SECTIONS
2.ONLY RIGID BUSSING TO EXTEND THROUGH GLASTIC
BARRIERS
3.BOTH SECTIONS TO BE SEALABLE
4.SEPARATE COVERS TO BE PROVIDED FOR (N)
SECTIONS WHERE THE BARRIER(S) ARE INSTALLED
5.ALL EQUIPMENT MUST MAINTAIN (E) ENVIRONMENTAL
RATING
6.LABELING SHALL BE REQUIRED AT SOLAR AND
UTILITY TERMINATION POINT LOCATED BELOW
GRADE, AT GRADE, OR ON THE BUILDING EXTERIOR.
LABELING SHALL CONSIST OF:
7.MACHINE-ENGRAVED LAMINATED PHENOLIC (OR
EQUIVALENT) TAG
7.1.ONE-QUARTER OF AN INCH WHITE LETTERS ON
RED-COLORED MATERIAL WHICH IS READILY
VISIBLE
7.2.MECHANICALLY ATTACHED TO THE FACE OF THE
TERMINATION COMPARTMENT. THE
COMPARTMENT LABEL(S) SHALL BE WORDED AS:
7.2.1."SOLAR INTERCONNECTION TERMINATION
COMPARTMENT"
7.2.2."UTILITY SERVICE TERMINATION
COMPARTMENT”
8.CONDUCTORS FROM THE (N) GENERATOR FACILITY
ARE NOT TO PASS-THROUGH UTILITY METER OR PULL
SECTIONS
POI-4 DC STRING SCHEDULE
STR-A STR-B STR-C
TAG DESTINATION CIRCUIT LENGTH
²
VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
CIRCUIT LENGTH
²
VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
CIRCUIT LENGTH
²
VD%MODULE
WATTAGE
MODULE QTY OPTIMIZER MIN/MAX
MODULES
DC-4.1.1 INV-4.1 180 0.92%410 12 U650 8 / 16¹185 0.89%410 12 U650 8 / 16¹160 0.82%410 12 U650 8 / 16¹
DC-4.2.2 INV-4.2 155 0.79%410 12 U650 8 / 16¹145 0.70%410 12 U650 8 / 16¹140 0.71%410 12 U650 8 / 16¹
DC-4.3.3 INV-4.3 105 0.54%410 12 U650 8 / 16¹100 0.48%410 12 U650 8 / 16¹105 0.49%410 11 U650 8 / 16¹
DC-4.4.4 INV-4.4 80 0.40%410 19 U650 10 / 19¹80 0.37%410 19 U650 10 / 19¹90 0.42%410 18 U650 10 / 19¹
¹ MAXIMUM STRING LENGTH IS USING MANUFACTURES EXCEPTION
² LENGTHS ARE ESTIMATED FOR CALCULATIONS, CONTRACTOR IS RESPONSIBLE FOR MEASUREMENTS AND TAKEOFFS
³ WHERE EXPOSED TO PHYSICAL DAMAGE #6 TO BE USED PER NEC 250.120(C)
⁴ AFC VALUES ARE CALCULATED BASED ON WIRE LENGTHS. LENGTHS SHOULD REMAIN GREATER THAN OR EQUAL TO THE LENGTH LISTED IN THE TABLE.
POI-4 DC WIRE SCHEDULE
TAG WIRE GAUGE CONDUCTOR
JACKET
MAX ISC 1.25 X MAX
CIRCUIT AMPS
CIRCUIT FUSE
RATING
CCC PER
CONDUIT
MAX AMBIENT
TEMP (C)
C.O.U TEMP.
DERATE
C.O.U CONDUIT
FILL DERATE
75°C AMPACITY COMPLIES
WITH
690.8(B)(1)
90°C AMPACITY
WITH C.O.U
COMPLIES
WITH
690.8(B)(2)
FAULT
CURRENT
FROM
PARALLEL
STRINGS
COMPLIES
WITH 690.9(A)
GROUNDING
PER CONDUIT
GROUNDING ³EMT RMC PVC 40 PVC 80
DC-4.1.1 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-4.2.2 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-4.3.3 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
DC-4.4.4 CU #8 THWN2 15 18.75 NONE 6 38 91%80%50 YES 40.0 YES 30 YES 3 CU #10 1"1"1"1 1/4"
POI-4 AC WIRE SCHEDULE
LABEL DESTINATION NOMINAL VAC LINE
SELECTION
FLA FLAX1.25 OCPD PHASE
CONDUCTOR
NEUTRAL
CONDUCTOR
GROUNDING
CONDUCTOR
CONDUCTORS
PER PHASE
CONDUIT QTY 75°C AMPS 90°C AMPS 90°C AMPS W/
C.O.U
C.O.U TEMP
DERATE
C.O.U
CONDUIT FILL
CIRCUIT
LENGTH ²
SEGMENT
VD%
DC/AC RATIO AFC START AFC END ⁴EMT IMC PVC 40 PVC 80
INV-4.1 LC-4.1 208 A-B 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%147.6%3,923 3,640 3/4"3/4"3/4"3/4"
INV-4.2 LC-4.1 208 B-C 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%147.6%3,923 3,640 3/4"3/4"3/4"3/4"
INV-4.3 LC-4.1 208 C-A 48.1 60.1 60 CU #6 CU #10 CU #10 1 1 65 75 68.3 91%100%5 0.11%143.5%3,923 3,640 3/4"3/4"3/4"3/4"
INV-4.4 LC-4.1 208 A-B-C 27.8 34.8 35 CU #8 CU #10 CU #10 1 1 50 55 50.1 91%100%5 0.09%229.6%3,923 3,499 3/4"3/4"3/4"3/4"
LC-4.1 AC-4.2 208 A-B-C 111.0 138.8 150 CU #1/0 CU #6 CU #6 1 1 150 170 154.7 91%100%40 0.43%--4,721 3,923 1 1/2"1 1/4"1 1/2"1 1/2"
AC-4.2 AC-4.1 208 A-B-C 111.0 138.8 150 CU #1/0 CU #6 CU #6 1 1 150 170 154.7 91%100%15 0.16%--5,111 4,721 1 1/2"1 1/4"1 1/2"1 1/2"
AC-4.1 POI-4.4 208 A-B-C 111.0 138.8 150 CU #2/0 CU #2/0 CU #4 1 1 175 195 142.0 91%80%8 0.07%--42,000 32,298 2"2"2"2"
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
POI-4 ONE LINE
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E603
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
12 SERVICE DISCONNECT PLACARDS
Scale NTS
2"
8"
2"
8"
SERVICE DISCONNECT
1 OF 2
SERVICE DISCONNECT
2 OF 2
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
NOTE:
1.RED BACKGROUND
2.WHITE LETTERING
3.TEXT HEIGHT: 1/8" MIN.
3 1/8"
NOTE:
1. MARKING PER ART 690.54
2. RED BACKGROUND
3. WHITE LETTERING
4. TEXT HEIGHT: 1/8" MIN.
NOTE:
1. RED BACKGROUND
2. WHITE LETTERING
3. TEXT HEIGHT: 1/8" MIN.
1 POINT OF INTERCONNECTION
Scale NTS
7 INVERTER AC CIRCUIT BREAKER
Scale NTS
8 SHOCK HAZARD
Scale NTS
4 PV SYSTEM MAINTENANCE DISCONNECT
Scale NTS
2 PV SYSTEM UTILITY AC DISCONNECT
Scale NTS
5 MAIN SERVICE WITH REMOTE PV SYSTEM DISCONNECT
Scale NTS
18 UTILITY NET GENERATION OUTPUT
Scale NTS
19 BESS DISCONNECT (IF APPLICABLE)
Scale NTS
9 INVERTER ID
Scale NTS
STRING INVERTERS
CENTRAL INVERTERS
3 1/8"
6 AC COMBINER PANEL
Scale NTS
3 5/8"
3 DC DISCONNECT
Scale NTS
NOTE:
1. MARKING PER ART 690.17, 690.53
2. RED BACKGROUND
3. WHITE LETTERING
4. TEXT HEIGHT: 1/8" MIN.
CAUTION
SOLAR ELECTRIC
SYSTEM CONNECTED
CAUTION
POWER TO THIS BUILDING IS
ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH
DISCONNECT LOCATED AS
SHOWN
!
DO NOT ADD LOADS
PHOTOVOLTAIC SYSTEM
COMBINER PANEL
WARNING !
LABEL LOCATION:
PHOTOVOLTAIC AC COMBINER (IF
APPLICABLE).
PER CODE(S): CEC 2022: 705.12(B)(3)(2),
NEC 2020: 705.12(B)(3)(2), NEC 2017:
705.12(B)(2)(3)(b), NEC 2014:
705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4)
ELECTRICAL SHOCK HAZARD
WARNING!
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 690.13(B), NEC
2020: 690.13(B), NEC 2017: 690.13(B),
NEC 2014: 690.17(E), NEC 2011:
690.17(4)
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
AMPS
VAC
PHOTOVOLTAIC AC DISCONNECT
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): CEC 2022: 690.54, NEC 2020: 690.54, NEC
2017: 690.54, NEC 2014: 690.54, NEC 2011: 690.54
AC SYSTEM DISCONNECT
FOR UTILITY OPERATION
LABEL LOCATION:
UTILITY DISCONNECT
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
LABEL LOCATION:
UTILITY DISCONNECT
INVERTER
DC SYSTEM SIZE :
NUMBER OF STRINGS:
MODULES PER STRING:
kW
DC SYSTEM SIZE ____kW
POINT OF INTERCONNECTION
PHOTOVOLTAIC POWER SOURCE
ELECTRICAL SHOCK HAZARD
WARNING!
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
DC PHOTOVOLTAIC
DISCONNECT
PHOTOVOLTAIC DC DISCONNECT
MAXIMUM POWER POINT VOLTAGE(Vmp):
MAXIMUM POWER POINT CURRENT(Imp):
MAXIMUM SYSTEM VOLTAGE(Voc):
SHORT-CIRCUIT CURRENT(Isc):
V
A
V
A
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): CEC 2022: 690.53, NEC 2020: 690.53, NEC 2017: 690.53, NEC
2014: 690.53, NEC 2011: 690.53
15 INVERTER WARNING
Scale NTS
ELECTRICAL SHOCK HAZARD
WARNING!
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 690.13(B), NEC
2020: 690.13(B), NEC 2017: 690.13(B),
NEC 2014: 690.17(E), NEC 2011:
690.17(4)
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
13 DC PV CIRCUIT INSIDE BLDG
Scale NTS
LABEL LOCATION:
CONDUIT, COMBINER BOX
PER CODE: CEC 690.31(D)(2)
ALL INTERIOR AND EXTERIOR DIRECT-CURRENT
CONDUIT, RACEWAYS, ENCLOSURES, CABLE
ASSEMBLIES, JUNCTION BOXES, COMBINER
BOXES AND DISCONNECTS. MARKING SHALL BE
PLACED ON ALL DC CONDUIT EVERY 10 FEET,
WITHIN 1 FOOT OF TURNS OR BENDS AND WITHIN
1 FOOT ABOVE AND BELOW PENETRATIONS OF
ROOF/CEILING ASSEMBLIES, WALLS OR
BARRIERS
WARNING: PHOTOVOLTAIC
POWER SOURCE
NET GENERATION OUTPUT
METER
LABEL LOCATION:
ON THE METER PANEL OR ADJACENT TO THE METER
SOCKET. ACCEPTABLE METHODS FOR LABELING
CUSTOMER NGO METERING SECTIONS OR PANEL(S)
SHALL BE EITHER BY PERMANENTLY ATTACHED
MACHINE-ENGRAVED LAMINATED PHENOLIC (OR
EQUAL) TAGS, OR BY PERMANENT STENCILED PAINT
LETTERING.
NOTE:
1.TEXT HEIGTH: 1/4" MIN
10 UTILITY NET GENERATION OUTPUT
Scale NTS
16 RAPID SHUTDOWN LABEL
Scale NTS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
6"
3.5"TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTING
MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED.
PER CODE(S): CEC 2022: 690.56(C)(1), NEC 2020: 690.56(C)(1); NEC 2017:
690.56(C)(1)(a)
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC COMBINER PANEL
(IF APPLICABLE).
PER CODE(S): CEC 2022: 690.13(B), NEC 2020: 690.13(B),
NEC 2017: 690.13(B), NEC 2014: 690.17(E), NEC 2011:
690.17(4)
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING!!
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
POWER SOURCE OUTPUT CONNECTION
LABEL LOCATION:
ADJACENT TO PV BREAKER (IF APPLICABLE).
PER CODE(S): CEC 2022: 705.12(B)(3)(2), NEC
2020: 705.12(B)(3)(2), NEC 2017:
705.12(B)(2)(3)(b), NEC 2014: 705.12(D)(2)(3)(b),
NEC 2011: 705.12(D)(7)
NOTES AND SPECIFICATIONS:
·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2023 ARTICLE
110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF
REQUESTED BY THE LOCAL AHJ.
·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS, COLORS AND SYMBOLS.
·LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING METHOD
AND SHALL NOT BE HAND WRITTEN.
·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY SIGNS
AND LABELS, UNLESS OTHERWISE SPECIFIED.
·DO NOT COVER EXISTING MANUFACTURER LABELS.
MAXIMUM AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
AMPS
VAC
PHOTOVOLTAIC AC DISCONNECT
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): CEC 2022: 690.54, NEC 2020: 690.54, NEC
2017: 690.54, NEC 2014: 690.54, NEC 2011: 690.54
ELECTRICAL SHOCK HAZARD
WARNING!
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2022: 690.13(B), NEC
2020: 690.13(B), NEC 2017: 690.13(B),
NEC 2014: 690.17(E), NEC 2011:
690.17(4)
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
INV-1
LABEL LOCATION:
INVERTER (1)
INV-2
LABEL LOCATION:
INVERTER (2)
[When applicable]
INV-3
LABEL LOCATION:
INVERTER (3)
[When applicable]
INV-4
LABEL LOCATION:
INVERTER (4)
[When applicable]
LABEL LOCATION:
INSTALLED WITHIN 3' OF RAPID SHUT DOWN
SWITCH PER CODE(S): NEC 2020: 690.56(C)(2),
CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
11 RAPID SHUTDOWN SWITCH
Scale NTS
ENERGY STORAGE SYSTEM
DISCONNECT
LABEL LOCATION:
ENERGY STORAGE SYSTEM DISCONNECT
PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C)
WARNING!
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): CEC 2022: 705.12(C), NEC
2020: 705.12(C)
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
14 NOT USED
Scale NTS
NOT USED
3 1/8"
CLASS J FUSE ONLY
WARNING!
LABEL LOCATION:
FUSED AC DISCONNECT(S)
FAST-ACTING, CURRENT-LIMIT
EQUIVALENT REQUIRED TO
PREVENT DAMAGE CAUSED BY
SHORT-CIRCUIT EVENTS.
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
WARNING LABELS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E800
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
ENERGY STORAGE SYSTEM DISCONNECT
ARC FLASH AND SHOCK HAZARD
APPROPRIATE PPE AND TOOLS REQUIRED WHILE WORKING ON THIS EQUIPMENT
REFER TO NFPA 70 E.
LABEL LOCATION:
ESS AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020 706.15(C)(4)
3 1/2"
NOMINAL ESS AC VOLTAGE:
MAXIMUM ESS DC VOLTAGE:
AVAILABLE FAULT CURRENT
DERIVED FROM THE ESS:
DATE CALCULATION PREFORMED:
208 VAC
450 VDC
234 A
2/5/26
3 POI-1 ESS ARC FLASH AND SHOCK HAZARD
Scale NTS
ENERGY STORAGE SYSTEM DISCONNECT
ARC FLASH AND SHOCK HAZARD
APPROPRIATE PPE AND TOOLS REQUIRED WHILE WORKING ON THIS EQUIPMENT
REFER TO NFPA 70 E.
LABEL LOCATION:
ESS AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020 706.15(C)(4)
3 1/2"
NOMINAL ESS AC VOLTAGE:
MAXIMUM ESS DC VOLTAGE:
AVAILABLE FAULT CURRENT
DERIVED FROM THE ESS:
DATE CALCULATION PREFORMED:
208 VAC
450 VDC
234 A
2/5/26
4 POI-2 ESS ARC FLASH AND SHOCK HAZARD
Scale NTS
ENERGY STORAGE SYSTEM DISCONNECT
ARC FLASH AND SHOCK HAZARD
WARNING
APPROPRIATE PPE AND TOOLS REQUIRED WHILE WORKING ON THIS EQUIPMENT
REFER TO NFPA 70 E.
LABEL LOCATION:
ESS AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020 706.15(C)(4)
5"
NOMINAL ESS AC VOLTAGE:
MAXIMUM ESS DC VOLTAGE:
AVAILABLE FAULT CURRENT
DERIVED FROM THE ESS:
DATE CALCULATION PREFORMED:
208 VAC
450 VDC
234 A
2/5/26
5 POI-3 ESS ARC FLASH AND SHOCK HAZARD
Scale NTS
ENERGY STORAGE SYSTEM DISCONNECT
ARC FLASH AND SHOCK HAZARD
WARNING!
APPROPRIATE PPE AND TOOLS REQUIRED WHILE WORKING ON THIS EQUIPMENT
REFER TO NFPA 70 E.
LABEL LOCATION:
ESS AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020 706.15(C)(4)
3 1/2"
5"
NOMINAL ESS AC VOLTAGE:
MAXIMUM ESS DC VOLTAGE:
AVAILABLE FAULT CURRENT
DERIVED FROM THE ESS:
DATE CALCULATION PREFORMED:
208 VAC
450 VDC
234 A
2/5/26
6 POI-4 ESS ARC FLASH AND SHOCK HAZARD
Scale NTS
!
WARNING
WARNING!
5"
5"
1 ESS AC DISCONNECT
Scale NTS
LABEL LOCATION:
ON OR NEAR THE ESS DISCONNECTING MEANS I.E
INVERTERS FOR DC-COUPLED ESS
ENERGY STORAGE SYSTEM
AC DISCONNECT
NOTES AND SPECIFICATIONS:
·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2023 ARTICLE
110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF
REQUESTED BY THE LOCAL AHJ.
·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS, COLORS AND SYMBOLS.
·LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING METHOD
AND SHALL NOT BE HAND WRITTEN.
·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY SIGNS
AND LABELS, UNLESS OTHERWISE SPECIFIED.
·DO NOT COVER EXISTING MANUFACTURER LABELS.
1
0 0
N.A.
2 NFPA 704 SIGNAGE - SEDG ENERGY BANK BESS
Scale NTS
15"
15"
6"
7-1/2"7-1/2"
LABEL LOCATION:
SIGNS SHOULD BE PLACED
WHERE THEY ARE EASILY VISIBLE
IN CASE OF AN EMERGENCY,
SUCH AS ON EXTERIOR WALLS OF
BUILDINGS, ENTRANCES TO
ROOMS OR AREAS, AND
PRINCIPAL ACCESS POINTS TO
EXTERIOR STORAGE AREAS.
BATTERY ID
CONNECTED INV LABEL :
INV SERIAL NO.:
BATTERY SERIAL NO.:
LABEL LOCATION:
All Batteries[When applicable].
Use Connected Inv Label names as 1.1, 1.2,..for POI#1, 2.1, 2.2,...for POI#2
and so on.
Last 4 digits of the serial numbers can be used.
INV-
LABEL LOCATION:
ALL INVERTERS
Match Inv labels as shown in
Plans. Ex. 1.1, 1.2, 1.3,
2.1,2.2, 3.1, 3.2 and so on
7 BATTERY MAPPING SIGNAGES
Scale NTS
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
WARNING LABELS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E801
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
SITE PLACARDS
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
E810
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS AS
SHOWN
CAUTION:
816 N FIGUEROA ST, BLDG A, SANTA ANA, CA 92703, USA
PV ARRAY
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF
THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC
SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE INVERTERS ARE REMOTELY LOCATED FROM EACH OTHER, A
DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE INSTALLED AT EACH DC PV
SYSTEM DISCONNECTING MEANS, AT EACH AC DISCONNECTING MEANS, AND
AT THE MAIN SERVICE DISCONNECTING MEANS SHOWING THE LOCATION OF
ALL AC AND DC PV SYSTEM DISCONNECTING MEANS IN THE BUILDING.
[NEC 690.4(D)]
POI-1
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS AS
SHOWN
CAUTION:
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF
THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC
SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE INVERTERS ARE REMOTELY LOCATED FROM EACH OTHER, A
DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE INSTALLED AT EACH DC PV
SYSTEM DISCONNECTING MEANS, AT EACH AC DISCONNECTING MEANS, AND
AT THE MAIN SERVICE DISCONNECTING MEANS SHOWING THE LOCATION OF
ALL AC AND DC PV SYSTEM DISCONNECTING MEANS IN THE BUILDING.
[NEC 690.4(D)]
POI-2
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS AS
SHOWN
CAUTION:
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF
THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC
SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE INVERTERS ARE REMOTELY LOCATED FROM EACH OTHER, A
DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE INSTALLED AT EACH DC PV
SYSTEM DISCONNECTING MEANS, AT EACH AC DISCONNECTING MEANS, AND
AT THE MAIN SERVICE DISCONNECTING MEANS SHOWING THE LOCATION OF
ALL AC AND DC PV SYSTEM DISCONNECTING MEANS IN THE BUILDING.
[NEC 690.4(D)]
POI-3
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS AS
SHOWN
CAUTION:
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF
THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC
SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE INVERTERS ARE REMOTELY LOCATED FROM EACH OTHER, A
DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE INSTALLED AT EACH DC PV
SYSTEM DISCONNECTING MEANS, AT EACH AC DISCONNECTING MEANS, AND
AT THE MAIN SERVICE DISCONNECTING MEANS SHOWING THE LOCATION OF
ALL AC AND DC PV SYSTEM DISCONNECTING MEANS IN THE BUILDING.
[NEC 690.4(D)]
POI-4
POI LOCATION (EXT)
TENET METER (EXT)
AC DISCONNECT FUSED
(EXT)
AC DISCONNECT
NON-FUSED(EXT)
NGO METER(EXT)
BESS LOCATION (EXT)
PV INVERTER AND
ESS AC DISCONNECT
LOCATION (EXT)
BESS LOCATION (EXT)
BLDG A
816 N FIGUEROA ST, BLDG B, SANTA ANA, CA 92703, USA
PV ARRAY
BLDG B
(N) BOLLARDS
BESS
LOCATION (EXT)
BESS
LOCATION (EXT)
PV INVERTER AND
ESS AC DISCONNECT
LOCATION (EXT)
PV INVERTER
LOCATION (EXT)
PV INVERTER
LOCATION (EXT)
POI LOCATION (EXT)
TENET METER (EXT)
AC DISCONNECT FUSED
(EXT)
AC DISCONNECT
NON-FUSED(EXT)
NGO METER(EXT)
816 N FIGUEROA ST, BLDG C, SANTA ANA, CA 92703, USA
PV INVERTER AND
ESS AC DISCONNECT
LOCATION (EXT)
PV INVERTER
LOCATION (EXT)
AC DISCONNECT FUSED
(EXT)
AC DISCONNECT
NON-FUSED(EXT)
NGO METER(EXT)
POI LOCATION (EXT)TENET METER (EXT)
BESS
LOCATION (EXT)
BESS
LOCATION (EXT)
PV ARRAY
BLDG C
816 N FIGUEROA ST, BLDG D, SANTA ANA, CA 92703, USA
AC DISCONNECT FUSED
(EXT)
AC DISCONNECT
NON-FUSED(EXT)
NGO METER(EXT)
POI LOCATION (EXT)TENET METER (EXT)
PV INVERTER
LOCATION (EXT)
PV INVERTER AND
ESS AC DISCONNECT
LOCATION (EXT)
BESS
LOCATION (EXT)
BESS
LOCATION (EXT)
BLDG D
PV ARRAY
NGOM
M
SCE LINE SIDE
DISCONNECT
GENERATION LOAD
SIDE DISCONNECTUTILITY
DISTRIBUTION
SYSTEM
1
3
8
2
7
9
PV
GENERATION
FACILITY
46
5
SCE LINE SIDE DISCONNECT
LABEL LOCATION:
LINE SIDE DISCONNECT
LABEL LOCATION:
LOAD SIDE DISCONNECT
LABEL LOCATION:
IF PANEL MODIFICATIONS ARE MADE
APPROPRIATE PLACARDS MUST BE INSTALLED
LABELING THE SECTIONS.
1
2
7
LABEL LOCATION:
THE WIRING SEQUENCE OF
FACTORY-INSTALLED TEST-BYPASS BLOCKS,
FROM LEFT TO RIGHT, IS LINE-LOAD,
LINE-LOAD, LINE-LOAD. THIS WIRING
SEQUENCE SHALL BE PERMANENTLY
LABELED IN 3/4-INCH BLOCK LETTERS BELOW
THE TEST-BYPASS TERMINALS. LINE AND
LOAD CONDUCTORS SHALL BE CONNECTED
ONLY TO TEST-BYPASS BLOCK TERMINALS
DESIGNED AS LINE AND LOAD,
RESPECTIVELY.
3
LABEL LOCATION:
ON THE METER PANEL OR ADJACENT TO THE
METER SOCKET. ACCEPTABLE METHODS FOR
LABELING CUSTOMER NGO METERING
SECTIONS OR PANEL(S) SHALL BE EITHER BY
PERMANENTLY ATTACHED
MACHINE-ENGRAVED LAMINATED PHENOLIC
(OR EQUAL) TAGS OR BY PERMANENT
STENCILED PAINT LETTERING. TEXT HEIGHT
MIN. 1/4".
8
SCE METERING PLACARDS
NTS
SOLAR INTERCONNECTION
TERMINATION SECTION
LINE LOAD
SCE UTILITY TERMINATION
SECTION
DISCONNECT 1 OF 2
GENERATION LOAD SIDE
DISCONNECT
DISCONNECT 2 OF 2
NET GENERATION OUTPUT
METERING
NOTE: SCE REQUIRES A SAFETY-SOCKET BOX WITH FACTORY-INSTALLED
TEST-BYPASS BLOCKS FOR NON-INSTRUMENT RATED (SELF-CONTAINED)
NGO METERING. FOR SWITCHBOARDS/SWITCHGEAR, THE CUSTOMER MUST
LABEL THE GENERATOR OUTPUT BUS/CABLE DIRECTION (E.G., "TOP
GENERATOR FED"). IF NGO AND PCC METERING ARE SEPARATED BY OVER
100 FEET OR ON DIFFERENT LEVELS, A PERMANENT SIGN AT THE PCC METER
MUST INDICATE THE NGO METER'S LOCATION.
CURRENT FLOW
LABEL LOCATION:
FOR INSTRUMENT TRANSFORMER RATED CT
NGOM PANELS, THE ARROW POINTING
TOWARDS THE UTILITY SIDE DISCONNECT
SHALL BE INSTALLED ON THE INSIDE SIDE
WALL OF PANEL OR ON THE OUTSIDE FRONT
OF NGOM PANEL.
5
SCE LINE SIDE PV LOAD SIDE
LABEL LOCATION:
PULL SECTIONS
4
GRID GENERATION
LABEL LOCATION:
GRID AND GENERATION CONDUCTORS
6
LABEL LOCATION:
PLACE A UNIQUE ADDRESS PLACARD ON THE
NGOM THAT MATCHES THE AHJ PERMIT AND
THE SCE SERVICE REQUEST ADDRESS.
9
123 MAIN ST. SOMAH1
NOTE: IF INTERCONNECTION IS MADE WITHIN A NEW TERMINATION
CAN, THE "SOLAR INTERCONNECTION TERMINATION SECTION"
PLACARD IS REQUIRED
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
REFERENCE SHEET - 1
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
R100
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
REFERENCE SHEET - 2
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
R101
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
REFERENCE SHEET - 3
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
R102
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
REFERENCE SHEET - 4
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
R103
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1216 - ANDALUCIA\VB - UTILITY COMMENTS\FIN REVIEW\CAD\ANDALUCIA_PVPLANS_V0.DWG
REFERENCE SHEET - 5
CONTRACTOR:
ENGINEERING APPROVAL:
600 CALIFORNIA ST #1800, SAN
FRANCISCO, CA 94104
CA CL #750184
UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT
LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS.
ANDALUCIA
816 N FIGUEROA ST, SANTA
ANA, CA 92703, USA
APN:198-162-03, 198-162-44,
198-162-52
DEVELOPER:
C&C DEVELOPMENT
DESCRIPTION DATE REV
0ORIGINAL08/26/25
AINVERTER SWAP 10/12/25
BEQUIPMENT LOCATION UPDATE 02/05/26
PROJECT DETAILS:
PV SYSTEM:
·220.17 kW DC
·160 kW AC
·203.27 CEC AC
ENERGY STORAGE:
·120 kW AC
·349.2 kWH
R104
SHEET SIZE:
REVISION:
SHEET TITLE:
36" X 24" (ARCH D)
DESIGNER: FINS_AP
B
CONTRACT NUMBER:
3003200669
PJT #: PROP-001216
B
Astra v.2.160
CAT 1
Subject: Structural Certification for Proposed Residential Solar Installation.
Job Number: Prop-001216
Client: Andalucia
Address: 816 N Figueroa St, Santa Ana, CA 92703
Attn: To Whom It May Concern
Design Criteria:
• 2025 CRC/CBC/CEBC, 2024 ASCE & 2018 NDS
• Basic (Category II) Wind Speed V=95 mph, Exposure B
• Ground Snow Load = 0 psf
Based on this evaluation, I certify that the alteration to the existing structure by the installation of the PV system meets the requirements of
the applicable existing and/or new building code provisions referenced above.
A field observation of the existing structures at the address indicated above was performed. Structural evaluation of the loading was based
on the site observations and the design criteria listed below.
A site observation of the existing structures was performed by grouping similar buildings and gathering representative framing information
and condition photos for each (referred to as Groups). Sunrun site audit teams performed a unique site audit for each representative
building group. The buildings and roof planes included in each group are shown below (see Table A)
Additionally, I certify that the PV module assembly including all attachments supporting it have been reviewed to be in accordance with the
manufacturer's specifications.
Installer shall inspect the existing roof framing to verify it is in suitable condition and does not exhibit any signs of damage or modification
which may diminish the capacity of its members or connections prior to commencement of PV installation. If actual framing or condition
differs from the representative information, the installer shall notify the engineer of record prior to proceeding with installation
#AStamp
Signed on: 12/30/1899
Results Summary (Hardware Check Includes Uplift Check on Attachments/Fastener, Structure Check Considers Main Structure)
Group 1
Orientation Attachment Spacing/Cantilever Configuration Max DCR Result
Roofing Material Pitch Structure Check
Group 2
Orientation Attachment Spacing/Cantilever Configuration Max DCR Result
Roofing Material Pitch Structure Check
Landscape 72 / 28 Stacked 35%Pass
Portrait 72 / 26 Stacked 44%Pass
Tile 18°Pass
Landscape 72 / 28 Stacked 35%Pass
Portrait 72 / 26 Stacked 44%Pass
Tile 18°Pass
225 Bush St. Suite 1400 San Francisco, CA 94104
Table A: Group Designations
Group Designation Applicable Buidings Applicable Roof Planes
Group 1
Roofing Material Roof Pitch Spacing Hardware Results Structural Results
Hardware Calculations
Attachment Information
Wind Design Criteria (Partially/Fully Enclosed Method, ASCE 2024)
Wind Pressures Zone 1 (up)Zone 2 (up)Zone 3 (up)Down
Snow Design Criteria (ASCE 2024)
Post-PV
Structural Calculations
Gravity Loading Summary
IEBC 5% Check
Tile 18°24''Pass Pass
Attachment:Tile Hook F Uplift Force: 0.6(p - (3psf x cos(pitch))) x trib area =364 lb Uplift Capacity: 829 lb a = 4.1 ft
Basic Wind Speed V 95 mph Wind Speed - Category II
Wind Pressure Exposure Kz 0.57 #N/A
Topographic Factor Kzt 1.0 #N/A
Wind Directionality Factor Kd 0.85 #N/A
Ground Elevation Factor Ke 1.00 Section 26.9
Velocity Pressure qh = 0.00256 x Kz x Kzt x Kd x V²11.43 psf #N/A
Solar Adjustment Factors #N/A
Ext Pressure Coefficient GCp -1.95 -2.53 -3.01 0.57 #N/A
Ext Pressure Coefficient (γp)(γc)(γE)(GCrn)nom -1.95 -2.53 -3.01 0.57 #N/A
Ultimate Design Wind Pressure p = qh x GCp -18.22 psf -17.41 psf -20.71 psf 16.00 psf #N/A
Ground Snow Load Pg 0 psf #N/A
Thermal Factor Ct 1.1 #N/A
Exposure Factor Ce 0.9 #N/A
Snow Importance Factor Is 1 #N/A
Flat Roof Snow Pf =0.7 x Ce x Ct x Pg 0.0 psf #N/A
Sloped Snow Factor Cs 0.87 #N/A
Sloped Snow Load Ps =Pf x Cs 0.0 psf #N/A
Mod Orientation X-Spacing Cantilever Trib Area Demand DCR Final Result
Landscape 72''28''10.3 ft²11.9 psf 35%Pass
Portrait 72''26''18.5 ft²11.9 psf 44%Pass
Load Definitions Initial Pre-PV Load Code Factors Post-PV LoadPg =0 psf | Pf =0.7 x Ce x Ct x Pg Ps = Cs x Pf
Roof Dead Load (D)DL 14.0 psf 14.0 psf 14.0 psf
PV Dead Load (D)PV DL 3.0 psf 0.0 psf 3.0 psf
Roof Live Load (Lr)RLL 20.0 psf 20.0 psf 1.00 0.0 psf
Sloped Snow Load (Pf --> Ps)LL/SL 0.0 psf 0.0 psf 1.00 0.87 0.0 psf
Total Design Load 34.0 psf 17.0 psf
Cd Factor of Governing LC 1.25 (D+Lr)0.9 (D)
Total Design Load (Normalized)27.2 psf 18.9 psf
Net Design Gravity Loading Change (Normalized w/ Cd Factor)-8.3 psf DCR: 69%Pass
Lateral Force: 0.6((p x tan(pitch)) - (3psf x cos(pitch))) x trib area =13.72 lb Lateral Capacity: 272 lb
1.4 γa =0.601γe (Port/Land) =
Group 1 BLDG A
BLDG B
RF01-RF12,
RF28-RF39
Group 2 BLDG C
BLDG D RF13-RF27,
RF40-RF55
Group 2
Roofing Material Roof Pitch Spacing Hardware Results Structural Results
Hardware Calculations
Attachment Information
Wind Design Criteria (Partially/Fully Enclosed Method, ASCE 2024)
Wind Pressures Zone 1 (up)Zone 2 (up)Zone 3 (up)Down
Snow Design Criteria (ASCE 2024)
Post-PV
Structural Calculations
Gravity Loading Summary
IEBC 5% Check
Tile 18°24''Pass Pass
Attachment:Tile Hook F Uplift Force: 0.6(p - (3psf x cos(pitch))) x trib area =364 lb Uplift Capacity: 829 lb a = 4.1 ft
Basic Wind Speed V 95 mph Wind Speed - Category II
Wind Pressure Exposure Kz 0.57 #N/A
Topographic Factor Kzt 1.0 #N/A
Wind DIrectionality Factor Kd 0.85 #N/A
Ground Elevation Factor Ke 1.00 Section 26.9
Velocity Pressure qh = 0.00256 x Kz x Kzt x Kd x V²11.43 psf #N/A
Solar Adjustment Factors #N/A
Ext Pressure Coefficient GCp -1.95 -2.53 -3.01 0.57
Ext Pressure Coefficient (γp)(γc)(γE)(GCrn)nom
Ultimate Design Wind Pressure p = qh x GCp -18.22 psf -17.41 psf -20.71 psf 16.00 psf
Ground Snow Load Pg 0 psf #N/A
Thermal Factor Ct 1.1 #N/A
Exposure Factor Ce 0.9 #N/A
Snow Importance Factor Is 1 #N/A
Flat Roof Snow Pf =0.7 x Ce x Ct x Pg 0.0 psf #N/A
Sloped Snow Factor Cs 0.87 #N/A
Sloped Snow Load Ps =Pf x Cs 0.0 psf #N/A
Mod Orientation X-Spacing Cantilever Trib Area Demand DCR Final Result
Landscape 72''28''10.3 ft²11.9 psf 35%Pass
Portrait 72''26''18.5 ft²11.9 psf 44%Pass
Load Definitions Initial Pre-PV Load Code Factors Post-PV LoadPg =0 psf | Pf =0.7 x Ce x Ct x Pg Ps = Cs x Pf
Roof Dead Load (D)DL 14 psf 14.0 psf 14.0 psf
PV Dead Load (D)PV DL 3 psf 0.0 psf 3.0 psf
Roof Live Load (Lr)RLL 20 psf 20.0 psf 1.00 0.0 psf
Sloped Snow Load (Pf --> Ps)LL/SL 0 psf 0.0 psf 1.00 0.87 0.0 psf
Total Design Load 34.0 psf 17.0 psf
Cd Factor of Governing LC 1.25 (D+Lr)0.9 (D)
Total Design Load (Normalized)27.2 psf 18.9 psf
Net Design Gravity Loading Change (Normalized w/ Cd Factor)-8.3 psf DCR: 69%Pass
Lateral Force: 0.6((p x tan(pitch)) - (3psf x cos(pitch))) x trib area =13.72 lb Lateral Capacity: 272 lb
1.4 γa =0.601
#N/A
-1.95 -2.53 -3.01 0.57 #N/A
#N/A
γe (Port/Land) =