Loading...
HomeMy WebLinkAbout10141226.pdfAAK LOT 2 IN BLOCK C OF BARTLETTS TRACK, IN THE CITY OF SANTA ANA, COUNTY OF ORANGE, STATE OF CALIFORNIA, AS SHOWN PER MAP RECORDED IN BOOK 11, PAGE 1 OF MISCELLANEOUS MAPS, IN THE OFFICE OF THE COUNTY RECORDER OF SAID COUNTY. 1. DOUBLE KITCHEN SINK 2. BUILT-IN DISHWASHER (VERIFY DIMENSIONS WITH MANUFACTURER'S SPECIFICATIONS). PROVIDE AIR CAP AT SINK. 3. 36" CLEAR REFRIDGERATOR SPACE - PROVIDE ROUGH -IN PLUMBING FOR ICE MAKER. NOTE: WIDTH MAY VARY WITI-� BUILDER UPGRADE OPTION - VERIFY. 4. MICROWAVE - PROVIDE SEPERATE ELECTRICAL CIRCUIT. (VERIFY DIMENSIONS WITH MANUFACTURER'S SPECIFICATIONS.) 5. RANGE AND OVEN (VERIFY DIMENSIONS WITH MANUFACTURER'S SPECIFICATIONS.) 6. WASHING MACHINE SPACE - PROVIDE RECESSED BOX WATER AND WASTE. 7. DRYER SPACE - PROVIDE VENT OUTSIDE AIR. PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR THE FINAL SIZE AND LOCATION OF THE DRYER VENT AND SHALL CONFORM TO ALL THE APPLICABLE CODES AND REGULATIONS. 8. 22" X 30" ATTIC ACCESS. 9. PROVIDE 4" SLAB FOR WATER HEATER PER CITY STANDARD. 10. WATER HEATER - PROVIDE(2) SEISMIC STRAPS - (1) TOP AND (1) BOTTOM. FINAL LOCATION OF THE WATER HEATER VENT SHALL BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR AND SHALL CONFORM TO THE APPLICABLE CODES AND REGULATIONS. 11. 32" X 60" FIBERGLASS TUB WITH SHOWER ABOVE. PROVIDE CHROME ROD. 12. 6" PLUMBING WALL 13. 6" STUD WALL 14. 36" X 48" FIBERGLASS SHOWER 15. SHELF AND SINGLE POLE 16. MIRROR 17. GYPSUM BOARD SOFFIT - TOP AT 96" UNLESS NOTED OTHERWISE. 18. GUARDRAIL 36" ABOVE HIGHEST ADJACENT FINISH FLOOR. SEE DETAIL 7/D-3 PER PLAN. 19. LAUNDRY TRAY. 20. DRYER VENT LOCATION ( 5" 26" GA. G.1. - VERIFY PER CODE. 21. VANITY - SEE INTERIOR ELEVATIONS. 22. PROVIDE R-13 BATT INSULATION AT LAUNDRY ROOM WALL AS INDICATED. 23. 6"X6" WOOD COLUMN 24. CRIPPLE WALL 25. SHELF 26. UNDER CABINET FLUOR. LIGHT. 27. MEDICINE CABINET 28. EXTERIOR GRADE R/S PLYWOOD CEILING 29. LINEN CABINET - SEE INTERIOR ELEVATIONS 30. PANTRY - SEE INTERIOR ELEVATION 31. PROVIDE MECHANICAL VENTILATION CAPABLE OF PROVIDING FIVE AIR CHANGES PER HOUR (DUCTLESS FANS ARE NOT ACCEPTABLE IN ROOMS CONTAINING TUBS OR SHOWERS) (1203.3) 32. APPROVED SMOKE DETECTOR PER U.B.C. SEC. 310.9.1. DETECTOR TO BE PERMANENTLY WIRED AND WITHOUT A DISCONNECTION SWITCH OTHER THAN THOSE REQUIRED FOR OVER CURRENT PROTECTION. ALL SMOKE DETECTORS TO BE WIRED TOGETHER FOR SIMULTANIOUS ALARM. ALL SMOKE DETECTOR'S SHALL HAVE APPROVED BATTERY BACKUP. 1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE 2001 CALIFORNIA BUILDING, PLUMBING, MECHANICAL, AND ELECTRICAL CODES, AND LOCAL ORDINANCES. 2. VERIFY ALL DIMENSIONS, DO NOT SCALE DRAWINGS. 3. ULTIMATE CONCRETE STRENGTH TO BE 2500 P.S.I. Q 28 DAYS. 4. LUMBER: USE DOUGLAS FIR COMMERCIAL GRADE #1 FOR ALL POSTS AND 6x AND LARGER BEAMS AND COMMMERICIAL GRADE #2 FOR ALL 4x AND SMALLER, ALL LUMBER SHALL BE GRADE MARKED. 5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES, AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE OF REPAIR OR REPLACEMENT A CONJUNCTION WITH THE PROSECUTION OF THIS WORK. 6. COMPLIANCE SHALL BE MADE WITH THE STATES ENERGY CONSERVATION REQUIREMENTS. FILE REQUIRE DOCUMENTATION ON THE DRAWINGS. 7. DRAWINGS AND WORK MUST SHOW COMPLIANCE WITH GENERAL AND CONVENTIONAL CONSTRUCTION REQUIREMENTS OF C.B.0 SECTIONS2326 AND CHAPTER 18 FOUNDATION REQUIREMENTS. 8. PROVIDE HOUSE STREET NUMBER VISIBLE AND LEGIBLE FROM STREET. NUMBERS SHALL BE 4$1 MINIMUM. A IN% 171 Of'% A I n'"'� "ER AND TUB/SHOWER VALVES ARE REQUIRED. U.P.C. 410.7 E _U i r UD In '-8" 14'-5" 2030 AL.SL. 5040 AL.SL. 24 FL CA) 11 FL BATH 2 N . WARD. BI-PASS N. BEDROOM 4 (14'-0" x 12'-0 ) 32 TYP. � 15 S BI-PASS O �. 110V,/JI N. WARD. ----------- 2� -- 0 ® _ W/H , x �. / < 0 AN w 0 M, 0 31 m � uj E. BEDROOM 2 (10'-6" x 11'-0") N. WARD. 4 BI-PASS 4 BI-PASS N. WARD. -0" WALL HEATER u: 2� N E. DEN / BEDROOM 1 (10'-0" x 12'-0) 20-6 W E. E. E. E. E. PORCH 19 MoTC N WMAI 0 KITCHEN t/ 3 lni IF- E. FAMILY RM. (14'-6" x 12'-011) E. E. E. d- uj CV C11 1326 E. 2ND ST. Santa Ana, California hid DESIGNER: ' HUDGINS DESIGN 27626 PASEO SONATA SAN JUAN CAPISTRANO, CALIFORNIA 92675 TEL: 949.322.7922 FAX: 949.488.8940 ..� 0. 0 PROPERTY OWNER: STEPHANY HALES-PANLILIO 23052-H ALICIA PRWY., #611 MISSION VIEJO, CA, 92692 TEL: 949.378.2100 PROJECT ADDRESS: 1326 E. 2ND ST. ZONE: R-X ASSESSORS PARCEL NO: 398-456-08 LEGAL DESCRIPTION: BARLETTS TRACK BLK C LOT 2 LOT SIZE 5625 SQ.FT. BUILDING SIZE EXISTING FLOOR AREA 663 SQ.FT. EXISTING PORCH AREA 115 SQ.FT. NEW FLOOR AREA 499 SQ.FT. TOTAL 1277 SQ.FT. SITE COVERAGE 22.7% SUBMITTAL SET REVISION DATE PLAN CHECK SUBMITTAL NO. 1 6 OCT 2003 PLAN CHECK SUBMITTAL NO. 2 AL FortS,["'* 3� 0 �(+q `i t y� � u% Fed 4 "$ 4,q'a t�%, air, 4� &jA _ tet R3 �•"..§t L G {�. t.., t". �Ja E � PLAv ' t 0s elfil1 t a @ €v $ E the t � ma n Etc fIOns MUI � � changes ill i Via' aw it 3 ICI malk e s,I` $�on sameIll Wr 1 13-anta Ana. s plan end spec€lglnA,. I :1'0 acceptance O I: gel per€lli noir � l t prr ;visiotjs of A14Y cityordinance r statO L;. PLAN ITE CITY OF SANTA ANA F OOR PLAN 7, - t DEMO PLAN SCALE: 1/4" = V-011 E. E. E. Ul uj Ill EXIST INU rLVUK FLAN SCALE: 1/4" = V-011 1326 E. 2ND STI RESIDENCE REMODEL 1326 E. 2ND ST. Santa Ana, California h I d DESIGNER: HUDGINS DESIGN 27626 PASEO SONATA SAN JUAN CAPISTRANO, CALIFORNIA 92675 TEL: 949.322.7922 FAX: 949.488.8940 0► w -• 0 a PROJECT INFORMATION PROPERTY OWNER: STEPHANY HALES-PANLILIO 23052-H ALICIA PRWY., #611 MISSION VIEJO, CA, 92692 TEL: 949.378.2100 PROJECT ADDRESS: 1326 E. 2ND ST. ZONE: R-X ASSESSORS PARCEL NO: 398-456-08 LEGAL DESCRIPTION: BARLETTS TRACK BLK C LOT 2 LOT SIZE 5625 SQ.FT. BUILDING SIZE EXISTING FLOOR AREA 663 SQ.FT. EXISTING PORCH AREA 115 SQ.FT. NEW FLOOR AREA 499 SQ.FT. TOTAL 1277 SQ.FT. SITECOVERAGE 22.7% SUBMITTAL SET REVISION DATE PLAN CHECK SUBMITTAL NO. 1 6 OCT 2003 PLAN CHECK SUBMITTAL NO. 2 DEMO PLAN EXIST. FLOOR PLAN SCALE: JOB NO: 03015 DATE: 10.03.03 DRAWN BY: S.H. W1YA� : I I C KZ'l lk 11010 1 Ll [0- 11 * REFER TO "SPECIFICATIONS," DETAILS AND BUILDER SPECS FOR ADDITIONAL INFO PERTAINING TO THIS ELEVATION. * GLAZING IN DOORS AND FIXED GLAZED PANELS OF MORE THAN 9 SQ.FT. SHALL HAVE CATEGORY it CLASSIFICATION PER CBC CHAPTER 24 AND UBC STD. 24-2. ❑INDICATES ELEVATION PLAN NOTES SEE NUMBERS BELOW 1. ALL EXPOSED TRIM, ROOF SHEATHING, BEAMS, ETC. WHERE INDICATED SHALL BE S4S & FREE OF LOOSE KNOTS, SPLITS AND SAP AS POSSIBLE. 2. ALL EXPOSED PLYWOOD TO BE 3/8" 303 SIDING EXT.-APA SMOOTH FACE APPLIED OVER 60 MINUTE GRADE "D" PAPER (EXCEPT GARAGE DOORS) & NAILED WITH NON -CORROSIVE NAILS (U.O.N.) 3. LINE OF CEILING BEYOND. 4. (2) 8"x 8" G.I. SCREENED VENTS 5. G.I. FLASHING W/ CAULKING TYP. 6. ROOFING MATERIAL. SEE ROOF PLAN FOR TYPE & "GENERAL NOTE SPECIFICATIONS" SHEET. GN). "ROOFING FOR SPECS." 7. SECTIONAL OVERHEAD GARAGE DOOR W/ STYLE AS INDICATED OR SIMILAR DESIGN. VERIFY MANUFACTURER AND DESIGN. 8. ENTRY DOOR W/ R/S OR RAISED WOOD GRAIN TEXTURE APPLIED AS SHOWN ALTERNATE: RAISED PANEL WOOD TYPE TO BE SELECTED BY BUILDER (VERIFY). 9. 14" X 6" SCREEN VENT (TYP.). 10. ATTIC VENT 14" X 24" RECTANGULAR METAL LOUVER W/ SCREEN (VENTILATION AREA 158 SQUARE IN.). 11. G.I. GUTTER TO MATCH SURFACE. 12. GI DOWN SPOUT PAINTED TO MATCH SURFACE. PROVIDE SPLASH BLOCK. 13. 2X8 RE/S FASCIA (TYP). 14. 2X8 R/S BARGE (TYP). 15. 6"X10' FALSE OUTLOOKER 16. 2X4 0/ 6X10 RE/S PORCH BEAM. 17. 6X6 POSTS. 18. 2X6 FLAT ABOVE 2X4 ON EDGE 19. 2X2 PLANT -ON TRIM 20. 2X2 SQ. PICKETS AT 6" O.C. 21. 2X4 TOP & BOTTOM RAIL. 22. EXT. GRADE PLYSAWN 0/ (1) LAYER 15# FELT. 23. EXT. GRADE BEVEL LAP SIDING 0/ (1) LAYER 15# FELT. 24. 2X6 PLANT-ONS AT ALL CORNERS. 25. STUCCO TO BE TROWLED [SMOOTH] [SMOOTH WITH LIGHT TEXTURE] [LIGHT SPANISH LACE] OVER METAL LATH, 60 MINUTE GRADE "D" PAPER AND WIRE. (SEE FRAMING FOR STRUCTURAL SHEAR WALL REQUIREMENTS FOR LATH.) ALL VERTICAL AND HORIZONTAL OUTSIDE TYPE CORNERS SHALL HAVE [SQUARE] [BULLNOSE] CORNER BEAD. (U.O.N) ALL HORIZONTAL AND VERTICAL INSIDE TYPE CORNERS SHALL BE SQUARE AND/OR SHARP. 26. STUCCO CORNER TO BE SQUARE CORNER BEAD WHERE INDICATED. 27. STUCCO CORNER TO BE BULLNOSE CORNER BEAD WHERE INDICATED. 28. STUCCO OVER _.X_ TRIM (SEE NOTE #30) 29. G.I. STUCCO WEEP SCREED. TYP. 30. 7" MASONITE SIDING. 31. FLAT 1 x4 TRIM 32. 1 1 /2" DIA. INT. HANDRAIL FOUNDATION VENTS TO BE AS CLOSE TO CORNER AS POSSIBLE AS PER 2306.7 1162 SQ.FT.l150 = 7.74 SQ.FT OF VENTILATION REQUIRED OR (13) - 6" X 14" GFI VENTS. REAR ELEVATION SCALE: ,,,.=,.-o. EXISTING ROOF / °P EXIS*G 25 PORCH 25 N FRONT ELEVATION SCALE: ,,<•-,•.o• EAST ELEVATION SCALE: ,,,•=,•-o• Wad WEST ELEVATION EXISTING PORCH n 1MMM91,11[c3 0 • _050 • 0 SCALE: 1 /4" = 1'- 0" (TYP) 1326 E. 2ND RESIDENCE REMODEL 1326 E. 2ND ST. Santa Ana, HUDGINS DESIGN 27626 PASEO SONATA SAN JUAN CAPISTRANO, CALIFORNIA 92675 TEL: 949.322.7922 FAX: 949.488.8940 PROPERTY OWNER: STEPHANY HALES-PANLILIO 23052-H ALICIA PRWY., #t611 MISSION VIEJO, CA, 92692 TEL: 949.378.2100 PROJECT ADDRESS: 1326 E. 2ND ST. ZONE: R-X ASSESSORS PARCEL NO: 398-456-08 LEGAL DESCRIPTION: BARLETTS TRACK BLK C LOT 2 LOT SIZE 5625 SQ.FT. BUILDING SIZE EXISTING FLOOR AREA 663 SQ.FT. EXISTING PORCH AREA 115 SQ.FT. NEW FLOOR AREA 499 SQ.FT. TOTAL 1277 SQ.FT. SITE COVERAGE 22.7% SUBMITTAL SET REVISION PLAN CHECK SUBMITTAL NO. 1 PLAN CHECK SUBMITTAL NO. 2 DATE . OCT•• SCALE: JOB NO: 03015 DATE: 10.03.03 DRAWN BY: S.H. ig 91 it Eel wk 1011 * BUILDING FRAMING SECTIONS REPRESENT APPROXIMATE ARCHITECTURAL RELATIONSHIPS ONLY AND DO NOT NECESSARILY REPRESENT STRUCTURAL ENGINEERING CONDITIONS, CONNECTIONS OR MATERIALS. REFER TO STRUCTURAL ENGINEERING DRAWINGS FOR ALL SUPERCEDING STRUCTURAL REQUIREMENTS. REPORT ANY DISCREPANCIES IMMEDIATELY PRIOR TO PROCEEDING WITH WORK. i i iiiiiii I I II;Iil� �1�llmmmlk I 10 11011111111111011 NAWAA1311111MMIkI * REFER TO SHEET T-1 FOR INSULATION REQUIREMENTS. INDICATES UTILTY PLAN NOTES SEE NUMBERS BELOW 1. ROOF RAFTERS PER STRUCTURAL DRAWINGS. 2. SHEATHING PER STRUCTURAL DRAWINGS. 3. RIDGE BEAM PER STRUCTURAL DRAWINGS. 4. 2X CEILING JOISTS PER STRUCTURAL DRAWINGS. 5. 2X FLOOR JOISTS PER STRUCTURAL DRAWINGS. 6. 2X4 STUDS AT 16" O/C. 7. 2X6 STUDS AT 16" O/C. 8. DBL. 2X TOP PLATES. 9. 2X P.T.D.F. SILL PLATE. 10. 2X SILL PLATE 11. PROVIDE R13 BATT INSULATION AT EXTERIOR WALLS 12. PROVIDE R19 BATT INSULATION AT FLOOR JOISTS. 13. PROVIDE R30 BATT INSULATION AT CEILING. 14. 3/4" PLYWOOD NAIL 10d @ 6" EDGE & 10" FIELD, GLUE. 15. 1/211 DRYWALL (TYP.) 16. 2X BLOCKING 17. FLUSH BEAM WITH APPROVED HANGERS. 18. DROPPED BEAM WITH GYP BOARD OVER. ATTIC VENT SUMMARY 1. ALL VENTS TO BE COVERED WITH 1/4" CORROSION RESISTANT WIRE/METAL MESH (1505.3). 3. ALL VENTS SHALL BE INSTALLED SO AS TO MAKE THEM WATER —PROOF ANS WALL MOUNTED LOUVERS SHALL BE SEALED AN FLASHED WITH "MOISTOP" IN THE SAME MANNER PRESCRIBED FOR WINDOW INSTALLATIONS. 4. PROVIDE APPROVED INSULATION DAMS (BAFFLES) WHERE VENT BLOCKS ARE USED BETWEEN ROOF FRAMING MEMBERS TO PREVENT VENT HOLES BEING BLOCKED BY INSULATION. 5. PAINT VENTS TO MATCH TRIM COLOR. ATTIC VENTILATION CALCULATIONS PER U.B.C. 1505.3 ATTIC AREA : A SQ. FT. A S.F. X 1/300 x 144 — B SQ. IN. AREA AREA #1 AREA #2 A ATTIC AREA ( UNIT : SQ. IN. ) 11162 — — — — B CALCULATE REQ'D NET FREE VENTING AREA: ( UNIT : SQ. IN. ) 558 ---- PROVIDE NET FREE VENTING AREA ATTIC VENTS (EXISITING) = 150 — — — — EAVE VENTS (3 holes) 17 SQ. IN. EACH 17 x 9 = 153 GABLE 12" X VENT`, 18" = 133 SQ. IN. 133 x 2 = 266 — — — — TOTAL PROVIDED 569 SUN. 15/32" CDX PLWD. OR OSB SHIT'G. P.I. 32/16 NAIL 8d @ 617 EDGE & 12 FIELD 1326 E. 2ND ST. RESIDENCE REMODEL 1326 E. 2ND ST. Santa Ana, California DESIGNER: S4--- HUDGINS DESIGN 27626 PASEO SONATA SAN JUAN CAPISTRANO, CALIFORNIA 92675 TEL: 949.322.7922 FAX: 949.488.8940 CONTRACTOR: PROJECT INFORMATION PROPERTY OWNER: STEPHANY HALES-PANLILIO 23052-H ALICIA PRWY., #611 MISSION VIEJO, CA, 92692 TEL: 949.378.2100 PROJECT ADDRESS: 1326 E. 2ND ST. ZONE: R-X ASSESSORS PARCEL NO: 398-456-08 LEGAL DESCRIPTION: BARLETTS TRACK BLK C LOT 2 LOT SIZE 5625 SQ.FT. BUILDINGSIZE EXISTING FLOOR AREA 663 SQ.FT. EXISTING PORCH AREA 115 SQ.FT. NEW FLOOR AREA 499 SQ.FT. TOTAL 1277 SQ.FT. SITE COVERAGE 22.7% SUBMITTAL SET PLAN CHECK SUBMITTAL NO. 1 PLAN CHECK SUBMITTAL NO. 2 6 OCT 2003 SCALE: JOB NO: 03015 DATE: 10.03.03 DRAWN BY: S.H. m SECTION 1 SCALE: 3/8" = 1'41 A OT 1998 CAUFORNIA BUILDING CODE 00LE 23-11-15-11--NAILING SCHEDULE ms�t to I sill or girder.: toenail (3)-8d 2 Bn ging o- )ojs 'd t L t oeno end. 0 each (2)-8d ".1 r X, V.:'(25mm. x 152mm subfloor or less to each joist, face not (2)-8d 4. wider. than r x, V' (25mm x 152mm) subfloor to each joist face nail (3} -8d 5* r. (,5 IM.hi) Moor to j6ist or ow su der, blind and face nail.(2}--16d joist blocking, typical face nail. Sde plate to"' or 16d at 116" (406nm)oc. t so 'ote t or blocking, at braced wall panels. k,� p' to jois (3Y16d per IV' (406mm) 7. Top plate to stud, end nail (2y 16d Stud to sole plate. (+&L toenoill or (2)-16d, end nal. 9. Double studs face nail. 16d at 2*' (6110rwII)oc. 10. Double to p plates; typical face nail. 16d at Zr (40&nm) o.r- Double top plates, lop splice. (8)-16d 11., Blocking between. joists or rafters to top plate,, toenail. (3)-8d -1Z' Mvp joitst. to top plate, toenail 8d 0 6" (152mm) o.c. 13. Topplates, laps and intersections, face nail. (2)-16d 14. Contitnuous: headers, two pieces 16d 0 lir (40&nm) oc. along ecch edge 15: Ceiling joists to plate, toenail, (3)-8d 16. Continuous header to stud, toenail (4)-8d 17.: ing joists, lops over partition, face noil (3)-16d 18., Cejtin4 to parallel raftersface nail joists , , (3y 16d 19.. Rafters; to plate, toenail (3)-8d (25mm) brace. to each stud and plate, face nail (2)-Od 2L V x W (25mm x 203mm) sheathing or less to each bearing, face nail (2),8d 22. Wderjhon 1" x 8" (25mm x'203mm) sheathing to each bearing, face nail '2 (3)-8d 23. Built- u p comer studs r,23.- 16d 0 24* (610mm) oc.. 24 24.,- Built-up girder and beams 20d 0 37' (813mm) o.c. at top and bottom and staggered (2) 20d at ends and at each splice. 25. Z` (�5 Imm) :planks (2)-16d at each beaming 26, Wood - structural panel's and particleboard: Subfloor. and wall. sheathing (to froming)-. I (123mm) and less 6d 19/V1 .. 3A" (15mm - 19mm) 7/8 V (22mrn -- 25mm 8d or 6d 3 8d 11/8". I I/V..(29mm - 32mm) 1W or 'Combination subtloor - Werlayment (to froming)-. un and,* IeSs 6d {ern - 251mm) 8d i tlo! :11 I/Al (2.9mm 32mm) 1W or 8d 27...'��Panel siding- to fronting) -.11/7' (11 7mm) and less 6d 6 5/vo (16mm). 8d 28. Fiberboard sheathing.. No. 11 go. 6d. 4 Na 16 go. 9 25/32!' (20mm) Na 1190 8d 4, No. 16go.,9 29. paneling ....Interior /V' (6,Amm) 4d' (9.5mm) n>I 6d 'Common or box nails may be used except where otherwise stated. 2 N ,alts- spaced at 6 inches (15-2mm) on center at edges, 12 inches (305mm) at intermediate supports except 6' (152mm) at all supports where spans are.48 inches,(1210mm) or more. For nailing of wood structural panel and particleboard diaphragms and shear walls, refer to Section 2315.3.3 and 2315.4. - Nails for wall sheathing may '. be common, box or casing. 3COmmon'or deformed shank. 4 Common. 5beform6d shank. "Cordsion-reeistant siding 'or' casing nails conforming to the requirements of Section 2304.3. Fasteners spacW 3 inches. (76mm) on center at, exterior edges and 6 inches (152mm) on center at intermediate supports. Corrisi6n .. �resiitant roofingnails with 7/1.6 inch (11mm) head and 1 1/2 inch (38mm) length for 1/2 Bloch (12.7mm) sheathing and .�"Mch (44mm). length for 25/32 inch (20mm) sheathing conforming to the requirements of Section 230*4 ap les'' with homi length f I in (12 7mm) sheathing. and Sistant staples'` nal 7/16 inch (1 imm) crown and 1 1/8 inch (29mm) 1 9 or inch - OC 171;2 (38mm) lertqhtj6��*_ 25/32 (20mm) sheathing conforming 'to the requirements of Section 2304.3. $10111141 supports of 16 inches (406mm120 inches (305mm) at intermediate supports. inches. $6not.'s,upports. at 24 (610mm). Casings or finish nails spaced 6 inches (152mm) on panel edges 12 inches (305mm) at'. *Orrnediote supports. NOM 1. Uid.u, ftwing membars at panel edges and bottom plates. Use double too �Pllotm a_t (wall 12) In'' tion is -required 0 all 12 shear walls, by the Engineer or the itect 'of RocbtA if required- by the local 6uDding official. I .,See a0propridti'sh4a wall tronsfer. details on plans. 4_1Ho iOwns as inditc0ted on'the,,pions to be locatedat each end of each shear panel. S., Hddowh.i vs, indicated on - plans between floors to be located at each end of each pa nell to post ow, unless shown otherwise. or beam W Ma from the oil, Noti. ximum allowable load includes. a 25% reduction UBC published values. 7. 11 /V! thick x Z1/41' x 2.7 1/4" plate washer required at all sill plate bolting, and S.: Bott- holes, for ffoldowns: shall be amcna*mum of 1/16" oversize - Inspector to verify. down, ei;tors sh all be tightened just prior to covering the wo IL conn en id. log screws require 2x min. framing, member 10. d s below. 7 1,/ from 'edge of to nals. lit Marc._panel EMBEDDE 'ING FOOTI )LES BY 1C >OXY. (SIKJ MPSON ER N I 9-YA"all 1 [010 191 RM1111k 0 10 10-1 oil] 110 SHEARWALL SCHEDULE BASED ON 1998 C.B.C. Shear Roof Floor Drag Top Plate Wall Sheating Bottom Plate Holdown Wall Diaphragm Strap Connector 1/2" CDX w/ 8d @ 5/8" DIA. x 10" A.B. 6" O.C. @ edges and '12" in None A35S 0 16" O.C. 1/2" CDX w/ 8d's @ 0 2'-0" O.C. None field P.I. #32/16 6" ® edges and 6" in field. k elm #]*a NOTE: PROVIDE 2 1/21" X 2 1/211 X 1/41$ STEEL PLATE SQUARE WASHERS TYPICAL AT ALL ANCHOR BOLT TO PLATE. NOTE: FOUNDATION BOLTS SHALL BE 5/8 INCH MINIMUM DIAMETER EMBEDDED AT LEAST 7 INCHES INTO THE ON OR MASONRY FOUNDATION NOT SPACED MORE THAN 6 FEET APART. (1806.6) 12" WIDE X 12" DEEP CONCRETE FOOTING W/ (1) #4 BAR TOP & BOTTOM. 12" WIDE X 24" DEEP CONCRETE FOOTING W/ (2) #4 BAR TOP & BOTTOM & #3 TIES @ 12" O.C. NOTE: PROVIDE DIAGONAL BRACING AT ALL NON -SHEAR WALLS FOR NEW CONSTRUCTION. FOUNDATION PLAN SCALE: 1/4" V- 011 24" STRAP - W/ 4x BLKG 24" x 18" CRAWL IN SPACE W1 CURB. PROVIDE G.I. SCREEN DOOR #4 BARS EMBEDDED 9 TO EXISTING FOOTING. 3E 3/4" HOLES BY 1011 LONG :ILL W/ EPDXY. (SIKA OR )UAL) SIMPSON EPDXY TIE r-22. WRITTEN DIMENSIONS SHALL BE VERIFIED ON THE JOB SITE. DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO THE COMMENCEMENT OF ANY WORK. HOLDDOWN HOLDDOWWHOLDDOWN HOLDDOWN LSTHD LSTHD8 LSTHD8 LSTHD8 J 01-611 --- L=101-- V17 4X6 HDR. _ V_6 -/4X6 H ALL 2x6 C.J1. @ 16" O.C. TYP DBL F.J. UNDI:. PARALLEL PARTITION 4X6 HDR. L=10"-5" HOLDDOWN LSTHD8 (EPDXY EMBEDDED) V, FAI, I! 'UP 4X6 HDR. E. E. F in Lij 00 X C14 4X4 HDR. 1� A kOLDD8DOWN H [EPDXY &MBEDDED) I co HOLDDOWN LSTHD8 L=5- 2x6 R.R. @ 16" O.C. TYP 4X6 HDR. L=71-910 HOLDDOWN HOLDDOWN LSTHD8 LSTHD8 (EPDXY EMBEDDED) (EPDXY EN EXISTING FRAMING: WALLS: 2X4 FLOOR JOISTS: 2X6 CEILING JOISTS: 2X6 ROOF: 2XIS E.' E. I X E. E. - - - - - - - - - :104 iNTA, 1*] 01 1326 E. 2ND ST. Santa Ana, California hid DESIGNER: HUDGINS DESIGN 27626 PASEO SONATA SAN JUAN GAPISTRANO,CALIFORNIA 92675 TEL: 949.322.7922 FAX: 949.488.8940 PROJECT INFORMATION PROPERTY OWNER: STEPHANY HALES-PANLILIO 23052-H ALICIA PRWY., #611 MISSION VIEJO, CA, 92692 TEL: 949.378.2100 PROJECT ADDRESS: 1326 E. 2ND ST. ZONE: R-X ASSESSORS PARCEL NO: 398-456-08 LEGAL DESCRIPTION: BARLETTS TRACK BLK C LOT 2 a, A0 W/ 4x BLWG LOT SIZE 5625 SQ.FT. BUILDING SIZE EXISTING FLOOR AREA 663 SQ.FT. EXISTING PORCH AREA 115 SQ.FT. NEW FLOOR AREA 499 SQ.FT. TOTAL 1277 SQ.FT. SITE COVERAGE 22.7% SUBMITTAL SET REVISION DATE PLAN CHECK SUBMITTAL NO. 1 6 OCT 2003 PLAN CHECK SUBMITTAL NO. 2 10 OCT 2003 RA ARC141 A C� OR E 1 , pm V fame, a, w.I Ljj I FLU oans� and %100 iz �0 P", 6 00! t, Ir pnal,�,a ('1�31,11 011 35 Out vvtiupar, a An VCaOf this pianand 0' V; A L ovwaiont 004 Int11I`4 an, Ewrl No -61 te 1 j ot ANY Cjt� 0, nane M xCeepted By I 'I, A ;: rA%,YTA ANi - - Clay od d ROOF FRAMING PLAN SCALE: 1/4" V- 01- SCALE: JOB NO: 03015 DATE: 10.09.03 DRAWN BY: S.H. B.N. A35's @ 16" O.C. MAX BORE 40% OF WIDTH 2x4 - (1 3/811 DIA. HOLE) 2x4 STUDS @ 1611 O.C. 2x6 BLOCK 2x6 F.J. @ 16" O.C. 2x SOLID BLOCKING (EXCEPT WHERE ENDS OF JOISTS -WIDTH- 2x6 - (2 1/8" DIA. HOLE) .. 16d @ 8" O.C. ARE NAILED TO A HEADER AND/OR RIM JOIST OR TO 5/8" MIN. A35's @ 16" O.C. 4x6 5/8" CDX T&G PLYWOOD GIRDER AN ADJOINING STUD OR BY OTHER APPROVED MEANS). EDGE DIST. 2x6 BLOCK SHEATHING W/ 10d @ 6- O.C. ---- AT EDGES AND 10" O.C. IN MAX BORE 60% OF WIDTH FIELD - P.I. 32/16 z w ON DBL. STUDS. NO MORE 2x6 F.J. @ B.N.NB. I 16" O.C. 66T EACH SIDE 0 - - a: THAN 2 PER DBL. STUD 2X6 M U D SILL W/ 3/16%l X 3 1/211 4X4 POST POWER DRIVEN PIN W/ 16 0 8 C�'o 2x4 - (2 1/81' DIA. HOLE) GA. WASHER A35 EACH SIDE z 0 0 CN 2x6 - (3 3/16" DIA. HOLE) R-1 9 BATT. 0 INSUL. Z DEPTH (D) 0 0 co 4x6 z MAX NOTCH 25% OF WIDTH 2x6 P.T. D.F. SILL WITH ,5/8"DIA. z X 10- ANC. BOLTS @ 72" O.C. GIRDER CNI cq 2X4 - (7/811 DEEP NOTCH) co 2X6 - (13/811 DEEP NOTCH) 0 01 0 STUD LEFT SHALL BE SOUND 66T NOTCHES NOT PERMITTED WITHIN MIDDLE 1/3 SPAN WOOD, & HAVE NO KNOTS, 04 EA. SIDE N NOTCHES WITHIN 1/2 BUT BORED HOLES ARE BORED HOLES ALSO SPAN EACH END PERMITTED PERMITTED [ BREAKS, SPLITS, EXCESSIVE SLOPE OF GRAIN, ETC. 0 T#4 BARS 4x4 POST CONCRETE PIER 8" SQ. NOTCHING/BORING @ 17 NOTCHING/BORING @ 13 9 INT. 1�STOREY FTG. 11 1..o 11 5 GIRDER PIER 11.11011 1 FLR. JOISTS EXT. & BEARING WALLS 2x6 C.J. AT (4} 16d ---WIDTH- MAX BORE 60% OF WIDTH 16" O.C. 4x10 GIRDER W1 2X4 - (2 1/811 DIA. HOLE) APPROVE HANGERSD JOIST 2x6 RAFTERSPER PLAN 5/8" MIN. 2X6 - (3 3/1611 DIA. HOLE) SIMPSON EDGE DIST. A35 @ 48" 2x6 C.J. AT O.C. 16" O.C. 8d (&, 6" O.C. 2x SOLID I q + BLOCKING MAX NOTCH 40 % OF WIDTH 2x8 JOISTS 2X4 - (1 3/811 DEEP NOTCH) AT 16" O.C. 2x6 - (2 1/8" DEEP NOTCH) NOTCHING/13ORING"' @ 18 14 10 INT, CEILING JST. 6 EAVE DETAIL 11 1 1.wo 11 2 INT. NON®BEAKG WALLS 11V' HARDWARE CLOTH STAPLED PROVIDE APPROVED D OR BAFFLES ... "I (DTO POST PER PLAN AT BACK OF 2X BLOCK -riv BE SIMPSON 8d 6" (�2) (3) 2 1/7' DIA. HOLES (TRUSSES OR RAF1MS)+''T0:- PREVENT A34 EA. END O.C. PER BLOCK EAME VENT HOLE FROM BEING BLOCKED -3 2X EAVE BLOCK (SEE ELEV. BY INSULATION. E�c — ------ AND SECTION MEW BELOW TRUSSES OR RAFTERS INLATION (REFER TO ENERGY -M CALCULATIONS) C13 SEE PLAN 2X BLCK`G 0 -21" 2 0 2X4 FULL HIGH NO BREAK@ CLG LEVEL 5 6 FIREBLOCK 0 A I I CONCRETE 3 PIER (2) #4 BARS EACH WAY SIMP. HD W/ i °° = e °-a"7 RAKE DETAIL 3 STAB BOLT 2x4 STUDS @ 16' O.C. 12" MIN. C.J. PLYWOOD WHERE 16d @ 8' O.C. OCCURS � OVERLAP A35's (cD- 16" O.C. ''i� '�Q (4) 16d NAILS 2X BLOCKING 3/4" CDX T&G PLYWOOD 2x6 BLOCK SHEATHING W/ 10d 6" O.C. 1 EQ. EQ. EQ. EQ. 2x4 TOP @ AT EDGES AND 10" O.C. IN FIELD P.I. 32/16, GLUE. PLATES - B.N. &TIN 2 I'LLE 2x C.J. AT 16" O.C. (PER + + STRUCTURAL 2x6 P.T. D.F. SILL WITH 5/8" DIA. X 10" ANC. BOLTS (g 72" 2x6 @16" O.C. O.C. WITHIN 12" OF ENDS R-1 9 BATT. 00 FRAMING PLAN) B. N. INSUL. + + 1. z 2X4 STUDS @ 16" O.C. .SECTION ELEVATION NOTES: 1, SEE GENERAL NOTES AND PLAN SPECIFICATIONS FOR VENTILATION REQUIREMENTS. co z 2. EACH BLOCK PROVIDES APPDX. 17 SQ. INCHES OF #4 BARS VENTILATION. 3, MINIMUM BLOCK I SIZE 2X4X 14 1/201 4. TYPICAL ATTIC 1 VENT BLOCK AT EVERY THIRD BAY 5. SLOPING CEILING - 1 VENTBLOCK AT.EACH BAY 2C� EAVE VENT BLOCK NT5 16 12 INT. CEILING JOISTS 8 EXTs 1 STOREY FTG. 4 @ PAETITION 1326 E. 2ND ST. RESIDENCE REMODEL 1326 E. 2ND ST. Santa Ana, California h Idl DESIGNER: HUDGINS DESIGN 27626 PASEO SONATA SAN JUAN CAPISTRANO, CALIFORNIA 92675 TEL: 949-322.7922 FAX: 949.488.8940 CONTRACTOR: PROPERTY OWNER: STEPHANY HALES-PANLILIO 23052-H ALICIA PRWY., #611 MISSION VIEJO, CA, 92692 TEL: 949.378.2100 PROJECT ADDRESS: 1326 E. 2ND ST. ZONE: R-X ASSESSORS PARCEL NO: 398-456-08 LEGAL DESCRIPTION: BARLETTS TRACK BLK C LOT 2 LOT SIZE 5625 SQ.FT. BUILDINGSIZE EXISTING FLOOR AREA 663 SQ.FT. EXISTING PORCH AREA 115 SO -FT. NEW FLOOR AREA 499 SQ.FT. TOTAL 1277 SQ.FT. SITE COVERAGE 22.7% SUBMITTAL SET REVISION DATE PLAN CHECK SUBMITTAL NO. 1 6 OCT 2003 PLAN CHECK SUBMITTAL NO. 2 10 OCT 2003 I SCALE: JOB NO: 03015 DATE: 10.09.03 DRAWN BY: S.H. Section 150. Any new low-rise residential building shall meet the following requirements: (a) CeilingInsulation. The opaque portions of ceilings separating conditioned spaces from unconditioned spaces or ambient air shall _-F �.4-ker - '3 k-10yo- meet the reaquire-11tw-nis 0I Clml R 1 �1 4- he�l '. 1. Ceilings shall be insulated between framing members with insulation resulting in an installed thermal resistance of R-19 or greater for the insulation alone. ALTERNATIVE to Section 150(a)l.: Insulation which is not penetrated by framing members may meet an R-value equivalent to installing R-19 insulation between framing members and accounting for the thermal effects of framing members. 2. -The weighted average U-factor of ceilings shall not exceed, the U-factor that w6uid result from installing R-19 insulations between framing members in the entire ceiling and accounting for the effects of framing members. (b) Loose Fill Insulation. When loose fill insulation is installed, the minimum installed weight per square foot shall conform with the Insulation manufGcturePs installed design weight per square foot at the manufacturer's labeled R-value. Wall Insulation. The opaque portions of frame wells separating conditioned spaces from unconditioned spaces or ambient air shall meet the requirements of either 1 or 2 below: 1, Framed walls shall be insulated between framing members with insulation having an installed thermal resistance of R-13 or greater. Framed foundation walls of, heated basements or heated crawl spaces shall be insulated above the adjacent outside ground line with insulation having an installed thermal resistance of at least R-1 3. ALTERNATIVE to Section 150(c)l.: Insulation which is not penetrated by framing members may meet an R-vacue equivalent to installing R-13 insulation between framing members and accounting for the thermal effects of framing ... emnibers. 2. 'The weighted average U-factor of walls shall not exceed the U-factor that would result from installina R-13 insulation between framing members and accounting for the effects of framing members. Raised Floor Insulation. Raised floors separating conditioned space from unconditioned space shall meet the requirements of either 1 or 2 below; 1. Floors shall be insulated between framing members with insulation 111GVing on installed. thleri-nal resistaince 0`1 R-1130 or greater 2. 'The wveiahted M."Crage U-factor of, floor assemblies shall not exceed the U-factor that would result from installing R-13 insulation between framing members and accounting for the efflects of framing r-nernbers. Alternative to Section 150(d)l. and 2.: Raised floor insulation may be omitted if the foundation walls are insulated to meet the wall insulation minimums shown in Tables No. 1-Z1 through 1-Z16, a vapor barrier is placed over the entire floor of the crawl space, and "cur ,Its are f*. + 0% fitted w14- nit+ fires ed 11ouvers that arie. le " with temperature actuated. 00 trtsf atlr sign 9f Fireplace% Decorative Gas Appliances and Gas Loqjs 1. If a masonry or factory -built fireplace is installed, it shall have the following: A. Closable metal or glass doors covering the entire opening of the firebox; B. A combustion air intake to draw air from the outside of the building directly into the firebox, wihi-K ,.. is at least 6-square area and is equipped with a readily accessible, operable, and tight -fighting damper or combustion air control device; an d EXCEPTION to Section 150(e)l.B: An outside combustion air intake is not required if the fireplace will be installed over concrete slab flooring and the fireplace will not be located on an exterior wall. C. A flue damper with a readily accessible control. ,OF_PT1101I to Section 1501-WO.: When a gas log, log lighter, or decorative gas appliance is installed in a fireplace, the flue damper shall I be S blockeopen if required by the manufact-urel U, r1`_Ud installation instruction or the California Mechanical Code. 2. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the out -side of the building, are prohibited. If an infiltration barrier is installed to meet the requirements of Sect -ion 151, it must have an air porosity of less than 5 ft per hour per square foot per inch of mercury pressure difference when tested in accordance with the requirements of ASTM E-283-91. If a vapor barrier functions as an infiltration barrier it shall be located on the conditioned side of the exterior framing. (g) Vapor Barriers. In Climate Zones 14 and 16. a vapor barrier shall be installed on the conditioned space side of all insulation in all exterior walls, unvented attics, and unvented crawl spaces to protect insulation from condensation. If a building has a control ventilation crawl space, a vapor barrier shall be placed over the earth floor of the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the ALTERNATIVE to Section 150(d). Spoce Coradititoning Equipment 1. Building design heat loss rate and design heat gain rate, shall be determined using c! method based on any of the following: A. The American Society of Heating, Refrigeration, and Air -Conditioning Engineers (ASHRAE) Handbook and Product Directory, Equipment Volume (1996), - WAC Applications Volume (1987). and Fundamentals Volume (1993), or B. The Sheet Metal Air Conditioning Contractors N'Gt*onall Asmsocat`oni (11MACNA) Installation Standards for Residential Heating and Air Conditioning Systems, or C, The Air Conditioning Contractors Of America (ACCA) Manual J. The design heat loss rate and design heat gain rate are two of the criteria that shall be used for equipment sizing and selection. NOTE to Section 150(h)1.- Heating Systems must meet the minimum heating capacity required by UBC Section 310.11. The furnace output capacity and other specifications are published in the C-om.rnission*s director,- of certified equipment or other directories approved by the Commission. 2. Design Conditions. For the purpose of sizing the space conditioning (HVAC) system, the indoor design temperatures shall be 70 degrees Fahrenheit for heating and 78 degrees for cooling. The outdoor design temperatures for heating shall be no lower that the Winter Median of [Extremes column. The outdoor design, temperatures for cooling shall be from the 0.5 percent Summer Design Dry Bulb and the 0,5 percent Wet Bulb columns for cooling, based on percent -of -year in ASHRAE publication SPCDX: Climate Data for Region X, Arizona, California, Hawaii and Nevada, 1982, incorporated herein by reference. 1A klj Setback Thernnot-Atuts A1111 hea'Ung aril or coollng systi-ents other than wood stoves shall have an automatic thermostat , with a clock mechanism or other setback mechanism approved by the Executive Director that shuts the system off during periods of non-ute and that allows the building occupant to automatically set back the thermostat set points for at least 2 periods .within 24 hours. EXCEPTION to Section 150(i): Gravity gas wall heaters, gravity floor heaters, gravity room heaters, non -central electric heaters, room air conditioners, and roorn air conditioner heat pumps need not comply with this requirement. Additionally, room air conditioner heat pumps need not comply with Section 112(b). The resulting in energy use due lto ellimilnotlon V11 '#,the setback, thienmostatt shall be factored into the compliance analysis in accordance with a method prescribed by the Executive Director. Pipe and 'rank Systems 1. Skorane tank invZot n inn.. V ...- .--_ A. Storage gas water heaters with an energy factor <0.58 shall be externally wrapped with insulation having an installed thermal resistance, of R-12 or greater. B. Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water heating systems, shall be externally wrapped with insulation having an installed thermal resistance of R-12 or greater or have internal insulation of at least R-1 6 and a label on the exterior of the tank showing the insulation R-value. 2. Piping, whether buried or unburied, for recirculating sections of domestic hot water systems, piping from the heating source to the storage tank for an indirect -fired domestic water heating system, cooling 'system. piping below 55 degrees Fahrenheit, and the first five feet of hot and cold water pipes from the storage tank for non - recirculating systems shall be thermally insulated in accordance with Table No, 1-T. EXCEPTIONS to Section 150(j)2: The following piping does not have to thermally insulated: (1)factory-installed piping within space conditioning equipment; (2) piping that conveys fluids that have a design operating temperature range between 55 degrees and 105 degrees Fahrenheit. NOTE to Section 150 6) 2: Where the executive director approves .a water heater calculation method for a particular water heating recirculation system, piping insulation. require- ments shall be those specified in the approved calculation method. 3. Insulation Protection. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind including but not limited to the following: Insulation exposed to weather shall .be suitable for outdoor service; e.g., protected by ciluminurn, sheet metal, painted canvos;or plastic cover. Cellular foam insulation shall be protected as above or pointed with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall include a vapor retardant located outside the insulation (unless the insulation is inherently vapor retardant), all penetrations and joints of which shall be sealed. 4. Solar water heating systems and or collectors shall be certified by the Solar Rating and Certification Corporation" (k) Lighting. .1 I t i * Lu mil flor geneir-al Ilightiing in, kitchens sholl t M1 $lull I JUY= lamps with an efficacy of not less than 40 lumens per watt. General lighting must provide a sufficient light level for basic kitchen tasks and provide a uniform pattern of illumination. A luminaire which is the only lighting in a kitchen shall be considered general righting. General I* hting shall ble- controlled by the most accessible switches) in the kitchen. Additional luminaires to used only for specific decorative effects need not meet this requirement. 2. Each room containing a shower or bath tub shall have at at least one luminaire with lamps with an efficacy of 40 lumens per watt or greater. If there is more than one luminaire in the room, the high efficacy luminaire shall be switched at an entrance to the room. Alternative to Section 150(k)2.: A high -efficacy luminaire need not be installed in a bathroom if: A. A luminaire with lamps with an efficacy of 40 lumens per watt or greater is installed in a utility room, laundry room, or garage; or B. All luminaires permanently mounted to the residence providing outdoor lighting shall be installed with the following characteristics: (1) Luminaires with lamps with 40 lumens per watt or greater, or (2) Luminaires with lamps with an efficacy of less than 40 lumens per watt shall be equipped with a motion sensor. NOTE: When using this alternative for multiple bathrooms, after I oorr,pying with Item B above for the first bathroom, each add- itional bathroom in which a high -efficacy luminaire is not installed must comply with Item A above alone. 3. Luminaires installed to meet the 40 lumens per watt requirements of Section 150(k)l. or 2. shall not contain medium base incandescent tamp sockets, and shall be on c . separate switches from any incandescent lighting. 4� All incandescent lighting fixtures recessed into insulated ceilings shall be approved for zero -clearance insulation cover (I.C.) by Underwriters Laboratories or other testing/ rating laboratories 'RocognitZed by the Conference of Building Officials. Slab Edge Insulation. Material used for slob insulation shall meet the following minimum specifications: 1, Water absorption rate no greater than 0.3 percent when tested in accordance with ASTM-C-271. 2. Water vapor permeance no greater than 2.0 perm/inch when tested in accordance with ASTM-E-96-95. 3. Concrete slab perimeter insulation must be pratected from physical damage and ultra violet light deterioration. m Air -distribution System Ducts, Plenums, and Fans. 1. CMC compliance. All air -distribution system ducts and plenums, including, but not limited to, mechanical closets and air -handier boxes shall be installed, sealed and insulated to meet the requirement of the 1998 CMC Sections 601, 603, 604, and Standard 6-3, incorporated herein by reference, Portions conveying conditioned air. shall either be insulated to minimum installed level of R-4.2. (or any higher level required by CMC Section 604) or be enclosed entirely in conditioned space. Connections of metal ducts and the 'inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant, or other duct -closure system that meets the applicable requirements of UL 181, UL `181A. or UL 18113. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used. Bulding cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross sectional area of the ducts. 2. Factory -fabricated duct systems. A. All factory -fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, conneatillons, and splices. B. All pressure sensitive tapes, heat -activated tapes, and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181. C. All pressure -sensitive tapes and mastics used with flexible ducts shall comply with UL 181 or UL 181 B. D. Joints and seams of ducts systems and their components shall not be sealed With cloth back rubber adhesive duct tapes unles such 'Lope is used in combination with mastic and drowbands. 3. Field-fabriated duct systems. A. Factory -made rigid fiberglass and flexible ducts for field fabricated ducts ay - O ,sterns shalt corn -ply with. UL 181. All pressum-sensitive tapes, mastics, aerosol sealants, or other closure systems used for installing field -fabricated duct systems shall meet the applicable requit-ements of UL 1188, UL 181A, or UL 181 B. B. Mastics sealants and mesh. i. Sealants shall comply with Ul 181, UL 181A. or UL 181B and be non- toxic and water resistant. ii. Sealants for interior applications shall pass ASTM tests C 731 (ex- trudibiffity after aging) and D 2202 (slump test on vertical surfaces), in- corporated herein by reference. 111. Sealants for exterior applications shall pass ASTM tests C 731, C 732 (artificial weathering test), and D2202, incorporated herein by reference. iv. Sealants and meshes shalt be rated for exterior use. C. Pressure -sensitive tape. Pressure sensetive tapes shall comply with UL 181, UL 181A, Ul 1818. D. Joints and seams of ducts systems and their components shall .not be, sealed with cloth back rubber adhesive duct tapes unles such tape is used in combination with mastic and drawband,§. E. DFdWi5rJhd9 Used With ?1494bic- ducts. i. Drawbands shall be either stainless -steel worm -drive hose clamps or UV resistant: nylon duct tites, ii. Drowbands shall have a minimum tensile strength ranting of 150 pounds. iii Drawbands shall be tightened as recommended by the manufacture, - with an adjustable tensioning tool. F> Aerosol -sealant closures i. Aerosol sealants shall meet the applicable requirements of UL 181, 181A, or 1841B and be applied according to mcnufact, u re -1 3 specifi cations. ii. Tapes or mastics used in combination with aerosol sealing shall meet the requirements of this section. 4. All duct insulation product R-values shall be based on insulation only (excluding air films, vapor barriers, or other duct components) and tested C-values at 75 degree F mean temperature at the installed thickness, in accordance with ASTM C 518-85 or ASTM C 177-85, incorporated herein by reference, and certified pursuant to Section 118. 5. The installed thickness of duct insulation used to determine it's R-value shall be determined as follows: A. For duct board, duct liner, and factory -made rigid ducts not normally sub- jected to oompreassrioni the nominal insulation thickness shall be used, B. For duct wrap, installed thickness shall be assumed to be 75 percent, (25 percent compression) of nominal thickness. C. For factory -made flexible air ducts, the installed thickness shall be deter- rnined by dividing the difference between the actual outsideullt arrie-ter and nominal inside diameter by two. 6. Insulated flexible duct products installed to meet this requirement must include labels, in maximum intervals of 3 feet, showing the thermal performance R-value for the duct insulation itself (excluding air films, vapor barriers, or other duct -ornponental, based on the tests 1- Seatton 150 t%-..N,2 end the tnstalled thickness determined 'by Section 150 (m)3C.­ 7, All fan systems, regardless of volumetric capacity, that exhaust air from the building to the outside shall be provided with backdraft or automatic dampers to prevent air leakage. 8. All gravity ventilating systems that serve conditioned space shall be provided with either automatic or readily accessible, manually operated dampers in all openings to the outside except combustion inlet and outlet air openings and elevator shaft vents. 9. Insulation Protection. Insulation shall be protected from damage. including that due to sunlight, moisture, equipment maintenance, and wind including but not limited to the following - Insulation exposed to weather shall be suitable for outdoor service; e.g., protected by aluminum, sheet metal, painted convas.or plastic cover. Cellular foam insulation shall be protected as above or pointed with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material EXCEPT ON to Section 150 (m) I., The requirements do not apply to ducts and fans integral to a wood heater or fireplace. NOTE: Authority cited: Public Resources Code, Section 25218(e), 25402, and 25402.1. Reference: Public Resources Code, Section 25402. MANIPATOKY MEASORMS CHEC.Ki-IST: RESIPENTIAL Mr-- IR NOTE. LoNrlse residential buildings subject to the Standard-, must contain there measures regardless of the compliance approach used. Items marked with an asterisk M mag be superseded by more stringent compliance requirements listed on the Certificate of Compliance. When this checklist Is Incorporated Into the, permit documents, the features noted shall be considered N all parties as binding minirnvro cornponant performance s-pec4fications for the m.c1nr_*Story .rna M.W-eq- whether they are Mown elsewhere in the documents or on the checklist only. Instructions.. c4wck or initial applicable boxes, when completed or enter WA if not applicable. DES02.IPTION Aiding Envolope, Measures: 4 S150(ci). Hirilmurn R,-iq ceiling Insulation. 6150(b). Loose fill Insulation manufacturer's labeled R-Value. WA * S150(c). Minimum R-0 wall insulation in wood framed walis or equivalent 1.1-Value In metal frame walls (doer, not apply to exterior mass walls). * si50(d): Minimum R-i3 rd!606 floor 16�Uidti6n in fr;�OM6%6 fioor� V/ S15al). 51ab ed9s,;- Insulation -water absorption rate no greater than 0.5%, water vapor transmission rate no greater than :2.0 permAnch. N/A 9115- Insulation specified or installed meets insulation quality standards. indicate type and form. V/ S116-1-7. Fenestration Products, Exterior Poore, and Infiltration/ Exfiltration Controls I. Doors and windows between conditioned spaces designed to limit air leakage. 2. Fenestration products (except flold-faricateci) h.crVe label Kith certified U-Factor, certified 5HG1C and Infiltration certification. 3. Exterior doom and windows we -other stripped; all lolnb5 and penetrations caulked and sealed. V/ S1504-Vapor barriers mandatory in Climate Zones 14 and IC? only. 14/A S 150(f)-.5pecial Infiltration barrier installed to comply with 8151 meets Commission quality standards. WA C350(6)dn5t:allatlon of Fireplaces, Decoratfve 6a5 Appl(anc-ar, and Logs 1. Masonry and factory -built fireplaces hove- c;XAo%oobIo motc4l or 91ciess door b.outsicWP air intake with damper and control r_.r-lue damper and control 2. No continuous bumfrk3 as pilot II his allowed. V/ Space Condibloning, Water Heating and Plumbing System Measures: 19II0-I5-.H\/AC equipment, water heaters, showerheads and faucets certif led I by the Commission. V/ S15ON&Icat'Ing and/or cooling toads calvulacd in accordance with V/ A5HRAE, 5MACNA or AC ,A. 6150(0:5etback thermostat on all applicable heating and/or cooling systems. SI50(P:PIpe and tank insulation 1. Storage gas water heaters rated with an Energy Factor less than 0.55 fntj6t i5e Wropl:566 6xtdrr1dfl9 with im6uldtlorl havIing a th6rMal resistance of R-12 or greater. 2. Fli-st 5 feet of pipes closest to water heater tank, non -recirculating systems, insulated (R-4 or greater} 5. Back-up tanks for solar system, unfired storage tanks, or other indlrect hot water tc�,_ he RI-12 exterml InsulaMon or R-Iro combined internal/external Insulation. 4. All buried or exposed plpIrk3 insulated In recirculating sections ofhotv4ot.-,r 99starng. 5. Cooling system piping below 55 F insulated. b. Piping insulated between heating source and Indirect hot water tank. V/ Sl50frr0.Ducts and Fans 1. All ducts and plemums installed, sealed and Insulated to meet the requirements of the 1146 cHr, Sections 601, 605,604, and Standard 6-8; ducts insulated to a minimum Installed level of R-4 or enclosed entirely in r-onditloned spor-o. CJ:>*nlnS& shot! be sealed with tape, aerosol sealant, or other duct -closure system that meets the applicable requirements, of UL lal, UL 181A, or UL 015. If mc.;5tir- or tape 15 used to seal openings greater that 1/4 inch, the combination of mastic, and either mesh or tape shall be used. 5ulldlru3 cavities sh I oil not to used for corn eying cordit!o",cl air. joints and sea.- of duct systems and their components, shall not be sealed with cloth back rubber adhesive duct tapes unless such tape Is used In combination with mastic and drciwbmd&. 2. Exhaust fan systems have back draft or automatic dampers.. 5. &rcr,/lt;9 ventilating a,95t6rne, serving ci.trdrtioned !&Pa0a 1crVa either automatic or readily accessible, manually operated dampers. '5114;Pool and Spa Heating 5ptemb and Equipment. _T 1. 5ystem is certified with 75% thermal efficlencyon-off switch, weatherproof operating instructions, no electric resistance heating and no pilot light. 2. 5y5tom Is installed with: a.At least 5&' of pipe between filter and heater for future solar heating. b.Cover for outdoor pools and outdoor spas. 5. Pool system has directional Inlets and a circulation pump rwitch. M/A fired central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously burning pilot light. (Exception. Non -electrical cooking appliances with pilot < 150 Btu/hr) V/ Lighting Measures: 9150(k)l -.1-urninaires for general lighting In kitchens shall have lamps with an efficacy of 40 lumens/watt or greater. This general lighting shall be controlled bg a switch on a readily accessible lighting control panel at an entree to 1he 9150(k)2.Rooms with o shower or bathtub must have either at least one luminaire with lamps with an efficacy of 40 lumens/watt or greater switched at the entrance to the room or one of the alternatives to this requirement allowed in Sec. 150(k)2.; and recessed ceiling fixtures are IC (Insutation 60ver) approved. Augu!5t, 20011 CERTIFICATE OF COMPLIANCE: RESIDENTIAL Page 1 CF-lR Project Title .......... Single Fam. Res. Addition Date..09/23/03 11:07:53 Project Address........ 1326 East 2nd Street --------------------- Santa Ana *V6.01* 1 1 Documentation Author... Stephen C. Lilly CEA ******* I Building Permit # I Southland Energy Consultants t 1 8592 La Casita I Plan Check / Date I Fountain Valley, CA 92708 1 1 714-848-3756 I Field Check/ Date 1 Climate Zone........... 08 ---------------------- Compliance Method...... MICROPAS6 v6.01 for 2001 Standards by Enercomp, Inc. MICROPAS6 v6.01 File-E2ND 2 Wth-CTZ08S92 Program -FORM CF-lR User4-MP0298 User -Southland knergy Cons-ulta. Run -Existing Plus Addition 1 ----------- ----------------------------------------------------- GENERAL 1'11GF=4AT'1'0NN ------------------- Conditioned Floor Area..... 1162 sf Building Type .............. Single Family Detached Construction Type ......... Existing Plus Addition Building Front Orientation. Front Facing 0 deg (N) Number of Dwelling Units... 1 Number of Stories.......... 1 Flo'.. ConstruConstructionType ... Raised Floor Glazing Percentage......... 12 % of floor area Average Glazing U-factor ... 1.05 Btu/hr-sf-F Average Glazing SHGC ....... 0.77 Average Ceiling Height..... 8 ft BUILDING SHELL INSULATION Component ------------------------- Frame Cavity Sheathing Total Assembly Type ------------ Type R-value R-value ------- -------- -------- R-value U-factor Location/Comments ------- ------- ------------------------ Wal" Wood R=G R=O R=0 0.386 Wall Wood R-13 R-0 R-13 0.088 Addition Wall Door n/a R-0 R-n/a R-0 0.330 Roof Wood R-19 R-0 R-19 0.051 Addition Floor Wood R-0 R-0 R-0 0.097 Floor Wood PI-19 p. - 0 R-19 0,037 Add,Crawlspace FENESTRATION ------------ Over- Area U_ Interior Exterior hang/ Orientation -------------------- (sf) ----- Factor ------ SHGC ------ Shading --------------- Shading -------------- Fins ----- Window Front (N)- 56.0 1.190 0.800 Standard Standard None Window Left (E) 20.0 1.190 0.800 Standard Standard None Window Left (E) 20.0 0.750 0.700 Standard Standard None Window B ac k (S) 26.9 0.750 0.700 Standard Standard None Window Right (W) 18.0 1.190 0.800 Standard Standard None CERTIFICATE OF COMPLIANCE.- RESIDENTIAL Page 2 CF-lR Project. Title .......... Single Fam. Res. Addition Date..09/23/03 11:07:53 -------------------------------- MICROPAS6v6.01 File-E2ND2 Wth-CTZ08S92 Program -FORM CF-lR User#-MP0298 User -Southland Energy Consulta Run -Existing Plus Addition I ------------------------------------------------------------------------------- HVAC SYSTEMS ------------ Refrigerant Tested ACCA Equipment Minimum Charge and Duct Duct Duct Manual Thermostat Type Efficiency Airflow Location R-value Leakage D Type ------------ ------------ ------- ----------- ------- ------- Furnace 0.630 AFUE n/a None R-n/a n/a ------ ---------- n/a Setback NoCooling 10.00 SEER No None R-n/a n/a n/a Setback SPE-C-111-A-1. FEATURES AND MODELING ASSUMPTIONS ----------------------------------------- Items in this section should be documented on the plans, has insta."Lled to manuz-acturer an(Al CEC specifEil-cations, and verified during plan check and field inspection. This building does not have a cooling system installed. REMARKS New Wall Heater: Monterey NV025 .63 EF 25000 BTUH DHW; My-isting CERTIFICATE OF COMPLIANCE: RESIDENTIAL Page 3 CF-lR Project Title .......... Single Fam. Res. Addition Date..09/23/03 11:07:53 -------------- - ------------ - -------------------------- MICROPAS6 v6z01 File-E2ND 2 Wth-CTZG8.S92 Program -FOAM CF-IR. User#-MP0298 User -Southland Energy Consulta Run -Existing Plus Addition ----------------------------- -------------------------------------------------- COMPLIANCE STATEMENT This Certificate of compliance ii8t8 the buildihq feature8 and perfOrifiat6e specifications needed to comply with Title-24, Parts 1 and 6 of the California Code of Regulations, and the administrative regulations to implement them. This certificate has been signed by the individual with overall design responsibility. When this certificate of compliance is submitted for a single building plan to be btiilt in, M-1-1-tiple orientatior%-- any shading feature that is varied is indicated in the Special Features Modeling Assumptions section. DESIGNER or OWNER DOCUMENTATION AUTHOR Name.... Scott Hudgins Name.... Stephen C. LlilyCEA Company. Hudgins Design Company. Southland Energy Consultants Address. 27626 Paseo Sonata Address. 8592 La Casita San Juan Capistrano CA Fountain Valley, CA 92708 Phone... 949-322-7922 Phone... 714-848-3756 T­ Signed.. Signed. z_ -(date) ENFORCEMENT AGENCY Name.... Title... Agency.. Phone Signed.. U Energy Analys Stephen C. Lil r r NR 98-99-623'! r r R 98_93_203' a KUL* affl AdW 4 :.",o DRAWN 5.CL. CHECKED DATE q/23/03 SCALE I C NONE JO8 NO. 32c15 SHEET OF SHEETS