HomeMy WebLinkAbout406 S Western Ave Unit #2 - Planstructural calculations for 406 S WESTERN AVE addition and remodel 406 S WESTERN AVE SANTA ANA, CALIFORNIA 92703 30-Dec-25 CE JOB NO. : 25-5096 S T R U C T U R A L 3 2 4 E S O U T H S T , L O N G B E A C H , C A L I F O R N I A 9 0 8 0 5 T : 5 6 2 . 9 6 1 . 5 6 0 0 W W W . C A S T I L L O E N G I N E E R I N G . C O M 1 ARCHITECT CASTILLO ENGINEERING, INC.JOB 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC JOB NO. SHEET NO. DESIGN CRITERIA 1 Soil supporting footings is natural grade or engineered fill. 2 Soil allowable bearing pressure used in design_______________________________ 3 Footing shall extend into undisturbed soil or below finish grade whichever is lower, as indicated on foundation plan. 4 All concrete shall develop a minimum compressive strength of 2500 psi in 28 days. 5 Reinforcing steel shall conform to ASTM 615, Grade 60. 6 Structural steel shall conform to the following: Wide flange shapes ASTM A992 TS shapes ASTM A500, Grade B Pipe shapes ASTM A53 , Grade B Other rolled shapes, Bars and plates ASTM A36 7 Structural steel shall be fabricated in a shop of an approved fabricator. 8 All welding shall be done by Certified Welders. 9 Concrete Block shall conform to ASTM C90, Grade N-1. 10 Grout shall develop 2000 psi in 28 days. 11 Mortar shall be Type S and develop 1800 psi in 28 days. 12 All lumber shall be grade marked Douglas Fir. (Grading rule No. 17) Light Framing Construction Joist & Planks No. 2 Beams & Stringers No. 1 Posts & Timbers No. 1 13 Glue Laminated Timbers shall be combination No. 24F-V8. 14 Plywood shall conform to PS 1-95, Structural 1. 15 All material and workmanship shall conform to the requirements of 2022 California Building Code. 2 ARCHITECT CASTILLO ENGINEERING, INC. 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE:SHEET NO. Fb Ft Fcperp.Fc Fv E E min CONSTRUCTION 1000 650 625 1650 180 1,500,000 550,000 NO. 2 900 575 625 1350 180 1,600,000 580,000 NO. 1 1200 825 625 1000 170 1,600,000 580,000 NO. 1 1350 675 625 925 170 1,600,000 580,000 COMBINATION 2400 1100 650 1650 265 1,800,000 930,000 NO. 24F-V8 y-dir 1450 1100 560 1650 230 1,600,000 830,000 WIDTH MORE THAN 2" GREATER THAN THAN 2" GREATER 12/10/2020 11:00 DOUGLAS FIR-LARCH DESIGN VALUES 6" & WIDER 5x5 AND LARGER WIDTH NOT MORE GLU-LAM BEAMS THICKNESS 2" TO 4" THICK 2" TO 4' WIDE 2" TO 4" THICK GRADE THAN THICKNESS 5" & THICKER BEAM & STRINGER DESIGNATION POST & TIMBER LIGHT FRAMING JOIST & PLANKS C:\Users\mcast\Dropbox\CE-OFFICE\CE-ENGINEERING\CE-SOFTWARE-10-CBC\WOOD\W-DESIGN VALUES 3 CASTILLO ENGINEERING PROJECT: 1205 PINE AVENUE, SUITE 201, LONG BEACH, CA 90813 37683.00 Wood :Douglas-Fir/Larch Cr = 1.15 (repetitive member factor)Fv =180 psi (for Light Framing and Joists & Planks) E = 1,500,000 psi (Const Light Framing)Fv =170 psi (for Beams & Stringers and Posts & Timbers) E = 1,600,000 psi (#2 Joists & Planks, #1 Beams & Stringers, #1 Posts & Timbers) FLOOR ROOF MEMBER:SIZE:(35 PCF)PROPERTIES:BENDING STRESS:1.00 (k-ft & k)Cd =1.00 (k-ft & k)Cd =1.25 Nominal Grade Type B (in)D (in)PLF A(in^2)S(in^3)I(in^4)Fb(psi)CF Fb x CF Vmax Mmax Mmax(rep)Vmax Mmax Mmax(rep) 2x4 Const. LF 1.5 3.50 1.3 5.3 3.1 5.4 1000 1.00 1000 0.63 0.26 0.29 0.79 0.32 0.37 2x6 #2 JP 1.5 5.50 2.0 8.3 7.6 20.8 900 1.30 1170 0.99 0.74 0.85 1.24 0.92 1.06 2x8 #2 JP 1.5 7.25 2.6 10.9 13.1 47.6 900 1.20 1080 1.31 1.18 1.36 1.63 1.48 1.70 2x10 #2 JP 1.5 9.25 3.4 13.9 21.4 98.9 900 1.10 990 1.67 1.76 2.03 2.08 2.21 2.54 2x12 #2 JP 1.5 11.25 4.1 16.9 31.6 178.0 900 1.00 900 2.03 2.37 2.73 2.53 2.97 3.41 2x14 #2 JP 1.5 13.25 4.8 19.9 43.9 290.8 900 0.90 810 2.39 2.96 3.41 2.98 3.70 4.26 4x4 Const LF 3.5 3.50 3.0 12.3 7.1 12.5 1000 1.00 1000 1.47 0.60 0.68 1.84 0.74 0.86 4x6 #2 JP 3.5 5.50 4.7 19.3 17.6 48.5 900 1.30 1170 2.31 1.72 1.98 2.89 2.15 2.47 4x8 #2 JP 3.5 7.25 6.2 25.4 30.7 111.1 900 1.30 1170 3.05 2.99 3.44 3.81 3.74 4.30 4x10 #2 JP 3.5 9.25 7.9 32.4 49.9 230.8 900 1.20 1080 3.89 4.49 5.17 4.86 5.62 6.46 4x12 #2 JP 3.5 11.25 9.6 39.4 73.8 415.3 900 1.10 990 4.73 6.09 7.00 5.91 7.61 8.76 4x14 #2 JP 3.5 13.25 11.3 46.4 102.4 678.5 900 1.00 900 5.57 7.68 8.83 6.96 9.60 11.0 6x4 #2 JP 5.5 3.50 4.7 19.3 11.2 19.7 900 1.00 900 2.31 0.84 2.89 1.05 6x6 #1 PT 5.5 5.50 7.4 30.3 27.7 76.3 1200 1.00 1200 3.43 2.77 4.29 3.47 6x8 #1 PT 5.5 7.50 10.0 41.3 51.6 193.4 1200 1.00 1200 4.68 5.16 5.84 6.45 6x10 #1 BS 5.5 9.50 12.7 52.3 82.7 393.0 1350 1.00 1350 5.92 9.31 7.40 11.6 6x12 #1 BS 5.5 11.50 15.4 63.3 121.2 697.1 1350 1.00 1350 7.17 13.6 8.96 17.0 6x14 #1 BS 5.5 13.50 18.0 74.3 167.1 1127.7 1350 0.99 1332 8.42 18.6 10.5 23.2 4 5 6 7 8 A-DESIGN LOADS-comp. shingles CASTILLO ENGINEERING, INC 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ROOF LOADS composite shingles 2.5 psf re-roof 2.0 psf 1/2" plywwod 1.5 psf rafters 4.0 psf insulation 0.5 psf Ceiling 3.0 psf beams/headers 1.0 psf MP&E/ misc.0.5 psf D=15.0 psf Lr=20.0 psf REDUCIBLE FLOOR LOADS flooring 1.0 psf 3/4" plywood 2.3 psf joist 3.0 psf ceiling 4.0 psf beams/headers 2.0 psf MP&E/ misc.2.7 psf D=15.0 psf L=40.0 psf EXTERIOR WALL LOADS 7/8" stucco 10.0 psf 1/2" plywood 1.5 psf 2x6 studs at 16"oc 1.5 psf insulation 0.5 psf 1/2" gyp board 2.3 psf MP&E/ misc.0.2 psf D=16.0 psf INTERIOR WALL LOADS 1/2" gyp board 2.3 psf 1/2" plywood 1.5 psf 2x6 studs at 16"oc 1.5 psf insulation 0.5 psf 1/2" gyp board 2.3 psf MP&E/ misc.1.9 psf D=10.0 psf 9 10 11 12 C.J. B4 H1 H2 H3 H4 H5 H6H7 H8 HB1 B5 B2 B1 HB1 HB1 HB1 HB2 RJ1 RJ 1 RJ 1 RJ1 B3 ROOF FRAMING KEY PLAN 13 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =3.16 ft Member=6x8 A =41.25 in^2 S =51.6 in^3 No. of members=1 I =193.4 in^4 CD=1.25 E =1,600,000 psi CF=1.00 Va =4.675 kips CV=1.00 Ma =5.156 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=3.16ft 0.17 0.17 Uniform load (W1) D L Trib w1,1 (15 +20)x 1.33 =19.95 +26.6 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =83.95 +26.6 =0.111 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 3.16 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 3.16 Shear R1=0.175 kips R2=-0.175 kips Stress Ratio Vmax=0.17 kips Vallow.=5.84 x 1 =5.8438 kips OK .03 Flexure M=0.14 k-ft Mallow.=6.45 x 1 =6.4453 k-ft OK .02 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.001 +0.000 +0.000 +0.000 =0.00 =L <L OK deflection:.00 47300 180 8E-04 +0 D (L Only)=2E-04 +0 +0 +0 =0 =L L OK deflection:.00 196581 240 USE:1- 6X8 flexure: shear: 7/11/25 12:00 AM B1 14 ARCHITECT CASTILLO ENGINEERING JOB 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. NOTCH ON COMPRESSION FACE AT END 1.83 5.8 0.92 4.88 V 170 lbs member type= b=5.5 in Fv=psi d 7.5 in Cd= dn= 4.88 in F'v=psi e= 11.13 in 'e' > 'dn', therefore use Eq.(3.4-2)slope=4 :12 support member width w= 5.5 in 2012 NDS Equation 3.4-5 fv= 2b = 3 x =psi < psi, therefore NA 2 x 5.5 x 7.50 - - 4.88 x 11 Use Eq. (3.4-2) 2012 NDS Equation 3.4-2 fv= 1.5V = psi < psi, therefore Satisfactory (.04) b dn 5.50 4.88dn Rec'd= B1 30 4.88 213 draftrer= 7.50 6x 170 1.25 213 170 w 3V d-(d-dn)/(dn)*e 9 213 11/07/2025 C:\Users\Jesus\OneDrive\Documentos\WORK\EXEL TRABAJO\w-notched beam 15 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =3.16 ft Member=4x8 A =25.38 in^2 S =30.7 in^3 No. of members=1 I =111.1 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =3.045 kips CV=1.00 Ma =2.300 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=3.16ft 0.36 0.36 Uniform load (W1) D L Trib w1,1 (15 +20)x 4.66 =69.9 +93.2 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =133.9 +93.2 =0.227 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 3.16 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 3.16 Shear R1=0.359 kips R2=-0.359 kips Stress Ratio Vmax=0.36 kips Vallow.=3.81 x 1 =3.8063 kips OK .09 Flexure M=0.28 k-ft Mallow.=3.74 x 1 =3.7369 k-ft OK .08 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.003 +0.000 +0.000 +0.000 =0.00 =L <L OK deflection:.01 13236 180 0.003 +0 D (L Only)=0.001 +0 +0 +0 =0 =L L OK deflection:.01 32251 240 USE:1- 4X8 flexure: shear: 7/11/25 12:00 AM B2 16 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 2.58ft 3.92ft L =6.5 ft Member=6x8 A =41.25 in^2 S =51.6 in^3 No. of members=1 I =193.4 in^4 0.24 CD=1.25 E =1,600,000 psi CF=1.00 Va =4.675 kips CV=1.00 Ma =5.156 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=6.5ft 0.78 0.73 Uniform load (W1) D L Trib w1,1 (15 +20)x 3.75 =56.25 +75 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =120.25 +75 =0.195 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (101.15 +134.85)x 1 x 1 =101 +135 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =101 +135 =0.24 kips 2.58 3.92 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 6.5 Shear R1=0.777 kips R2=-0.728 kips Stress Ratio Vmax=0.78 kips Vallow.=5.84 x 1 =5.8438 kips OK .13 Flexure M=1.36 k-ft Mallow.=6.45 x 1 =6.4453 k-ft OK .21 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.025 +0.000 +0.007 +0.000 =0.03 =L <L OK deflection:.07 2404 180 0.025 +0 D (L Only)=0.01 +0 +0 +0 =0.01 =L L OK deflection:.04 5648 240 USE:1- 6X8 flexure: shear: 7/11/25 12:00 AM B3 17 ARCHITECT CASTILLO ENGINEERING JOB 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. NOTCH ON COMPRESSION FACE AT END 1.83 5.8 0.92 4.88 V 730 lbs member type= b=5.5 in Fv=psi d 7.5 in Cd= dn= 4.88 in F'v=psi e= 11.13 in 'e' > 'dn', therefore use Eq.(3.4-2)slope=4 :12 support member width w= 5.5 in 2012 NDS Equation 3.4-5 fv= 2b = 3 x =psi < psi, therefore NA 2 x 5.5 x 7.50 - - 4.88 x 11 Use Eq. (3.4-2) 2012 NDS Equation 3.4-2 fv= 1.5V = psi < psi, therefore Satisfactory (.19) b dn 5.50 4.88dn Rec'd= B3 130 4.88 213 draftrer= 7.50 6x 170 1.25 213 730 w 3V d-(d-dn)/(dn)*e 41 213 11/07/2025 C:\Users\Jesus\OneDrive\Documentos\WORK\EXEL TRABAJO\w-notched beam 18 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 3.42ft 3.66ft L =7.08 ft Member=6x8 A =41.25 in^2 S =51.6 in^3 No. of members=1 I =193.4 in^4 0.78 CD=1.25 E =1,600,000 psi CF=1.00 Va =4.675 kips CV=1.00 Ma =5.156 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=7.08ft 1.51 1.48 Uniform load (W1) D L Trib w1,1 (15 +20)x 7.08 =106.2 +142 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =170.2 +142 =0.312 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (334.3 +445.7)x 1 x 1 =334 +446 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =334 +446 =0.78 kips 3.42 3.66 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 7.08 Shear R1=1.507 kips R2=-1.481 kips Stress Ratio Vmax=1.51 kips Vallow.=5.84 x 1 =5.8438 kips OK .26 Flexure M=3.32 k-ft Mallow.=6.45 x 1 =6.4453 k-ft OK .52 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.057 +0.000 +0.032 +0.000 =0.09 =L <L OK deflection:.19 953 180 0.057 +0 D (L Only)=0.026 +0 +0.02 +0 =0.04 =L L OK deflection:.13 1920 240 USE:1- 6X8 flexure: shear: 7/11/25 12:00 AM B4 19 ARCHITECT CASTILLO ENGINEERING JOB 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. NOTCH ON COMPRESSION FACE AT END 1.83 5.8 0.92 4.88 V 1480 lbs member type= b=5.5 in Fv=psi d 7.5 in Cd= dn= 4.88 in F'v=psi e= 11.13 in 'e' > 'dn', therefore use Eq.(3.4-2)slope=4 :12 support member width w= 5.5 in 2012 NDS Equation 3.4-5 fv= 2b = 3 x =psi > psi, therefore NA 2 x 5.5 x 7.50 - - 4.88 x 11 Use Eq. (3.4-2) 2012 NDS Equation 3.4-2 fv= 1.5V = psi < psi, therefore Satisfactory (.39) b dn 5.50 4.88dn Rec'd= B4 264 4.88 213 draftrer= 7.50 6x 170 1.25 213 1480 w 3V d-(d-dn)/(dn)*e 83 213 11/07/2025 C:\Users\Jesus\OneDrive\Documentos\WORK\EXEL TRABAJO\w-notched beam 20 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 1ft 6.58ft L =7.58 ft Member=6x8 A =41.25 in^2 S =51.6 in^3 No. of members=1 I =193.4 in^4 1.51 CD=1.25 E =1,600,000 psi CF=1.00 Va =4.675 kips CV=1.00 Ma =5.156 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=7.58ft 1.98 0.87 Uniform load (W1) D L Trib w1,1 (15 +20)x 3.25 =48.75 +65 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =112.75 +65 =0.178 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (647.14 +862.85)x 1 x 1 =647 +863 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =647 +863 =1.51 kips 1 6.58 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 7.58 Shear R1=1.984 kips R2=-0.873 kips Stress Ratio Vmax=1.98 kips Vallow.=5.84 x 1 =5.8438 kips OK .34 Flexure M=2.14 k-ft Mallow.=6.45 x 1 =6.4453 k-ft OK .33 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.043 +0.000 +0.030 +0.000 =0.07 =L <L OK deflection:.14 1254 180 0.043 +0 D (L Only)=0.016 +0 +0.02 +0 =0.03 =L L OK deflection:.09 2764 240 USE:1- 6X8 flexure: shear: 7/11/25 12:00 AM B5 21 ARCHITECT CASTILLO ENGINEERING JOB 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. NOTCH ON COMPRESSION FACE AT END 1.83 5.8 0.92 4.88 V 870 lbs member type= b=5.5 in Fv=psi d 7.5 in Cd= dn= 4.88 in F'v=psi e= 11.13 in 'e' > 'dn', therefore use Eq.(3.4-2)slope=4 :12 support member width w= 5.5 in 2012 NDS Equation 3.4-5 fv= 2b = 3 x =psi < psi, therefore NA 2 x 5.5 x 7.50 - - 4.88 x 11 Use Eq. (3.4-2) 2012 NDS Equation 3.4-2 fv= 1.5V = psi < psi, therefore Satisfactory (.23) b dn 5.50 4.88dn Rec'd= B5 155 4.88 213 draftrer= 7.50 6x 170 1.25 213 870 w 3V d-(d-dn)/(dn)*e 49 213 11/07/2025 C:\Users\Jesus\OneDrive\Documentos\WORK\EXEL TRABAJO\w-notched beam 22 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =2 ft Member=4x6 A =19.25 in^2 S =17.6 in^3 No. of members=1 I =48.5 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =2.310 kips CV=1.00 Ma =1.323 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=2ft 0.17 0.17 Uniform load (W1) D L Trib w1,1 (15 +20)x 3 =45 +60 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =109 +60 =0.169 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 2 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 2 Shear R1=0.169 kips R2=-0.169 kips Stress Ratio Vmax=0.17 kips Vallow.=2.89 x 1 =2.8875 kips OK .06 Flexure M=0.08 k-ft Mallow.=2.15 x 1 =2.1506 k-ft OK .04 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.001 +0.000 +0.000 +0.000 =0.00 =L <L OK deflection:.01 30628 180 8E-04 +0 D (L Only)=3E-04 +0 +0 +0 =0 =L L OK deflection:.00 86269 240 USE:1- 4X6 flexure: shear: 7/11/25 12:00 AM H1 23 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =2 ft Member=4x6 A =19.25 in^2 S =17.6 in^3 No. of members=1 I =48.5 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =2.310 kips CV=1.00 Ma =1.323 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=2ft 0.31 0.31 Uniform load (W1) D L Trib w1,1 (15 +20)x 6.92 =103.8 +138 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =167.8 +138 =0.306 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 2 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 2 Shear R1=0.306 kips R2=-0.306 kips Stress Ratio Vmax=0.31 kips Vallow.=2.89 x 1 =2.8875 kips OK .11 Flexure M=0.15 k-ft Mallow.=2.15 x 1 =2.1506 k-ft OK .07 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.001 +0.000 +0.000 +0.000 =0.00 =L <L OK deflection:.01 16904 180 0.001 +0 D (L Only)=6E-04 +0 +0 +0 =0 =L L OK deflection:.01 37400 240 USE:1- 4X6 flexure: shear: 7/11/25 12:00 AM H2 24 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 1ft 3ft L =4 ft Member=4x6 A =19.25 in^2 S =17.6 in^3 No. of members=1 I =48.5 in^4 0.87 CD=1.25 E =1,600,000 psi CF=1.30 Va =2.310 kips CV=1.00 Ma =1.323 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=4ft 1.03 0.59 Uniform load (W1) D L Trib w1,1 (15 +20)x 3.5 =52.5 +70 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =116.5 +70 =0.187 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (372.9 +497.14)x 1 x 1 =373 +497 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =373 +497 =0.87 kips 1 3 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 4 Shear R1=1.026 kips R2=-0.591 kips Stress Ratio Vmax=1.03 kips Vallow.=2.89 x 1 =2.8875 kips OK .36 Flexure M=0.93 k-ft Mallow.=2.15 x 1 =2.1506 k-ft OK .43 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.014 +0.000 +0.018 +0.000 =0.03 =L <L OK deflection:.12 1512 180 0.014 +0 D (L Only)=0.005 +0 +0.01 +0 =0.02 =L L OK deflection:.08 3096 240 USE:1- 4X6 flexure: shear: 7/11/25 12:00 AM H3 25 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =4 ft Member=4x6 A =19.25 in^2 S =17.6 in^3 No. of members=1 I =48.5 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =2.310 kips CV=1.00 Ma =1.323 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=4ft 0.78 0.78 Uniform load (W1) D L Trib w1,1 (15 +20)x 7.42 =111.3 +148 w1,2 (16 +)x 4 =64 +0 w1,3 (10 +)x 6.67 =66.7 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =242 +148 =0.390 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 4 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 4 Shear R1=0.781 kips R2=-0.781 kips Stress Ratio Vmax=0.78 kips Vallow.=2.89 x 1 =2.8875 kips OK .27 Flexure M=0.78 k-ft Mallow.=2.15 x 1 =2.1506 k-ft OK .36 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.029 +0.000 +0.000 +0.000 =0.03 =L <L OK deflection:.11 1657 180 0.029 +0 D (L Only)=0.011 +0 +0 +0 =0.01 =L L OK deflection:.06 4360 240 USE:1- 4X6 flexure: shear: 7/11/25 12:00 AM H4 26 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =5 ft Member=4x6 A =19.25 in^2 S =17.6 in^3 No. of members=1 I =48.5 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =2.310 kips CV=1.00 Ma =1.323 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=5ft 0.81 0.81 Uniform load (W1) D L Trib w1,1 (15 +20)x 7.42 =111.3 +148 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =175.3 +148 =0.324 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 5 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 5 Shear R1=0.809 kips R2=-0.809 kips Stress Ratio Vmax=0.81 kips Vallow.=2.89 x 1 =2.8875 kips OK .28 Flexure M=1.01 k-ft Mallow.=2.15 x 1 =2.1506 k-ft OK .47 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.059 +0.000 +0.000 +0.000 =0.06 =L <L OK deflection:.18 1023 180 0.059 +0 D (L Only)=0.027 +0 +0 +0 =0.03 =L L OK deflection:.11 2232 240 USE:1- 4X6 flexure: shear: 7/11/25 12:00 AM H5 27 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =3 ft Member=4x6 A =19.25 in^2 S =17.6 in^3 No. of members=1 I =48.5 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =2.310 kips CV=1.00 Ma =1.323 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=3ft 0.23 0.23 Uniform load (W1) D L Trib w1,1 (15 +20)x 2.5 =37.5 +50 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =101.5 +50 =0.152 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 3 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 3 Shear R1=0.227 kips R2=-0.227 kips Stress Ratio Vmax=0.23 kips Vallow.=2.89 x 1 =2.8875 kips OK .08 Flexure M=0.17 k-ft Mallow.=2.15 x 1 =2.1506 k-ft OK .08 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.004 +0.000 +0.000 +0.000 =0.00 =L <L OK deflection:.02 10123 180 0.004 +0 D (L Only)=0.001 +0 +0 +0 =0 =L L OK deflection:.01 30673 240 USE:1- 4X6 flexure: shear: 7/11/25 12:00 AM H6 28 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =4 ft Member=4x6 A =19.25 in^2 S =17.6 in^3 No. of members=1 I =48.5 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =2.310 kips CV=1.00 Ma =1.323 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=4ft 0.55 0.55 Uniform load (W1) D L Trib w1,1 (15 +20)x 6.08 =91.2 +122 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =155.2 +122 =0.277 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 4 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 4 Shear R1=0.554 kips R2=-0.554 kips Stress Ratio Vmax=0.55 kips Vallow.=2.89 x 1 =2.8875 kips OK .19 Flexure M=0.55 k-ft Mallow.=2.15 x 1 =2.1506 k-ft OK .26 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.021 +0.000 +0.000 +0.000 =0.02 =L <L OK deflection:.08 2337 180 0.021 +0 D (L Only)=0.009 +0 +0 +0 =0.01 =L L OK deflection:.05 5321 240 USE:1- 4X6 flexure: shear: 7/11/25 12:00 AM H7 29 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =5 ft Member=4x6 A =19.25 in^2 S =17.6 in^3 No. of members=1 I =48.5 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =2.310 kips CV=1.00 Ma =1.323 k-ft Cr=1.00 Total Load L/n=180 Live Load L/n=240 L=5ft 0.63 0.63 Uniform load (W1) D L Trib w1,1 (15 +20)x 5.42 =81.3 +108 w1,2 (16 +)x 4 =64 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =145.3 +108 =0.254 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 5 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 5 Shear R1=0.634 kips R2=-0.634 kips Stress Ratio Vmax=0.63 kips Vallow.=2.89 x 1 =2.8875 kips OK .22 Flexure M=0.79 k-ft Mallow.=2.15 x 1 =2.1506 k-ft OK .37 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.046 +0.000 +0.000 +0.000 =0.05 =L <L OK deflection:.14 1306 180 0.046 +0 D (L Only)=0.02 +0 +0 +0 =0.02 =L L OK deflection:.08 3056 240 USE:1- 4X6 flexure: shear: 7/11/25 12:00 AM H8 30 ARCHITECT CASTILLO ENGINEERING, INC.JOB 406 S WESTERN AVE 1205 Pine Avenue, Suite 201, Long Beach, CA 90813 T:562.961.5600 F:562.961.5700 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. HIP RIDGE BEAM DESIGN L= ft L1=ft w= ( + ) x /2 x 2 / (2)^.5 = + = plf W= x x = k V1=x 1 / 3 = k V2=x 2 / 3 = k <V allow.=k M= 2x x = k-ft <M allow.=k-ft 9 x D= x ( x 12 )^3 = in = 76.7 x x 5.5 x ^3/12 USE: 16.62 11.752015 (.80) 166 291125 16.62 2.42 247 5.84 6.45 11/07/2025 11.75 0.805 16.62.42 0.5 7.5 7.50 3.92 (.73) (3)^.5 HB1 3.50 7.50 2416 1600000 1.227222 6.75 2.42 L 291 6x8 2.42 1.611 0.81 7.50 5.15 16.62 (.28) BEAM L1 L1 L w W V2V1 31 ARCHITECT CASTILLO ENGINEERING JOB 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. NOTCH ON COMPRESSION FACE AT END 1.83 5.8 0.92 4.88 V 805 lbs member type= b=5.5 in Fv=psi d 7.5 in Cd= dn= 4.88 in F'v=psi e= 11.13 in 'e' > 'dn', therefore use Eq.(3.4-2)slope=4 :12 support member width w= 5.5 in 2012 NDS Equation 3.4-5 fv= 2b = 3 x =psi < psi, therefore NA 2 x 5.5 x 7.50 - - 4.88 x 11 Use Eq. (3.4-2) 2012 NDS Equation 3.4-2 fv= 1.5V = psi < psi, therefore Satisfactory (.21) b dn 5.50 4.88dn Rec'd= HB1 143 4.88 213 draftrer= 7.50 6x 170 1.25 213 805 w 3V d-(d-dn)/(dn)*e 45 213 11/07/2025 C:\Users\Jesus\OneDrive\Documentos\WORK\EXEL TRABAJO\w-notched beam 32 ARCHITECT CASTILLO ENGINEERING, INC.JOB 406 S WESTERN AVE 1205 Pine Avenue, Suite 201, Long Beach, CA 90813 T:562.961.5600 F:562.961.5700 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. HIP RIDGE BEAM DESIGN L= ft L1=ft w= ( + ) x /2 x 2 / (2)^.5 = + = plf W= x x = k V1=x 1 / 3 = k V2=x 2 / 3 = k <V allow.=k M= 2x x = k-ft <M allow.=k-ft 9 x D= x ( x 12 )^3 = in = 76.7 x x 5.5 x ^3/12 USE: 6.36 4.502015 (.27) 64 11148 6.36 0.35 1167 2.89 1.05 11/07/2025 4.50 0.118 6.40.35 0.5 3.5 3.50 0.22 (.15) (3)^.5 HB2 3.50 3.50 354 1600000 0.18 1.88 0.35 L 111 4x6 FLAT 0.35 0.236 0.07 3.50 0.29 6.36 (.08) BEAM L1 L1 L w W V2V1 USE 6x8 33 ARCHITECT CASTILLO ENGINEERING JOB 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. NOTCH ON COMPRESSION FACE AT END 1.83 5.8 0.92 4.88 V 118 lbs member type= b=5.5 in Fv=psi d 7.5 in Cd= dn= 4.88 in F'v=psi e= 11.13 in 'e' > 'dn', therefore use Eq.(3.4-2)slope=4 :12 support member width w= 5.5 in 2012 NDS Equation 3.4-5 fv= 2b = 3 x =psi < psi, therefore NA 2 x 5.5 x 7.50 - - 4.88 x 11 Use Eq. (3.4-2) 2012 NDS Equation 3.4-2 fv= 1.5V = psi < psi, therefore Satisfactory (.03) b dn 5.50 4.88dn Rec'd= HB2 21 4.88 213 draftrer= 7.50 6x 170 1.25 213 118 w 3V d-(d-dn)/(dn)*e 7 213 11/07/2025 C:\Users\Jesus\OneDrive\Documentos\WORK\EXEL TRABAJO\w-notched beam 34 CASTILLO ENGINEERING INC.Project 406 S WESTERN AVE 1327 Loma Avenue Long Beach, CA 90804 Engr. Date: Job No.25-5096 Sheet Tag Beam 5 L =11.5 ft Member=2x6 A =8.25 in^2 S =7.6 in^3 No. of members=1 I =20.8 in^4 CD=1.25 E =1,600,000 psi CF=1.30 Va =0.990 kips CV=1.00 Ma =0.567 k-ft Cr=1.15 Total Load L/n=180 Live Load L/n=240 L=11.5ft 0.27 0.27 Uniform load (W1) D L Trib w1,1 (15 +20)x 1.33 =19.95 +26.6 w1,2 (+)x 0 =0 +0 w1,3 (+)x 0 =0 +0 w1,4 (+)x 0 =0 +0 w1,5 (+)x 0 =0 +0 W1 =19.95 +26.6 =0.047 klf Triangular load (W2) D L Trib ` w2,1 (0 +0)x 0 =0 +0 w2,2 (0 +0)x 0 =0 +0 w2,3 (0 +0)x 0 =0 +0 w2,4 (0 +0)x 0 =0 +0 w2,5 (0 +0)x 0 =0 +0 W2 =0 +0 =0.000 klf Point Load (P1) D L Trib.1 Trib.2 p1,1 (+)x 0 x 0 =0 +0 p1,2 (+)x 0 x 0 =0 +0 p1,3 (+)x 0 x 0 =0 +0 p1,4 (+)x 0 x 0 =0 +0 p1,5 (+)x 0 x 0 =0 +0 X1 (ft)X2 (ft) P1 =0 +0 =0.00 kips 0 11.5 Point Load (P2) D L Trib.1 Trib.2 p2,1 (+)x 0 x 0 =0 +0 p2,2 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,4 (+)x 0 x 0 =0 +0 p2,5 (+)x 0 x 0 =0 +0 X3 (ft)X4 (ft) P2 =0 +0 =0.00 kips 0 11.5 Shear R1=0.268 kips R2=-0.268 kips Stress Ratio Vmax=0.27 kips Vallow.=1.24 x 1 =1.2375 kips OK .22 Flexure M=0.77 k-ft Mallow.=1.06 x 1 =1.0599 k-ft OK .73 Deflection D =D w1 +Dw2 +D p1 +Dp2 D (D+L)=0.551 +0.000 +0.000 +0.000 =0.55 =L <L OK deflection:.72 251 180 0.551 +0 D (L Only)=0.315 +0 +0 +0 =0.31 =L L OK deflection:.55 439 240 USE:1- 2X6 flexure: shear: 7/11/25 12:00 AM RJ1 35 F2 0.73K 0.59K F1 0.805K F3 0.118K F4 1.48K 0.78K F6 0.36K F8 0.805K F9 1.611K 1.611K 1.611K 1.611K F6 0.36K F7 0.17K F7 0.17K F5 1.98K CF1 CF 2 CF 1 (E ) C F 1 (E)CF2 (E)CF3 F1 0.805 FOUNDATION KEY PLAN 36 ARCHITECT CASTILLO ENGINEERING, INC.JOB 406 S WESTERN AVE 1205 Pine Avenue, Suite 201, Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. CONTINUOUS FOOTINGS CF-1 LOADING: TRIB. ( + ) x ft = + ( + ) x ft = + ( + ) x ft = + w = + = plf B= plf = ft psf USE: CF-2 LOADING: TRIB. ( + ) x ft = + ( + ) x ft = + ( + ) x ft = + w = + = plf B= plf = ft psf USE: 370.2 16 231.8 4015 0 WALL: 8 11/07/2025 20 D L ROOF: FLOOR: 15 6.92 1275 370.2 128 138.4 0 0 103.8 0 138.4 0 0 0.29 D L 3.3315 20 15 128 49.95 WALL: 16 0 8 FLOOR: 40 0 ROOF: 244.55 0.19 1275 1'-0" WIDE FTG. 66.6 66.6 0 0 177.95 1'-0" WIDE FTG. 244.55 F-CONTINUOUS FOOTINGS-1500 37 ARCHITECT Castillo Engineering, Inc.PROJECT 406 S WESTERN AVE 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. A = 12 ( 32 + 3.50 + 32 ) =L 67.5 in 5.63 ft q = 1500 psf (BEARING CAPACITY)(SELF WEIGHT) PA =1500 -( 5.63 x 2.67 )=K Pload =2.0824 K Pnet =5.76 k 144 5.63 ft2 CF1. CAPACITY CHECK 1000 11/07/2025 40( 5.63 ) 7.84 Pnet = 5.76 38 ARCHITECT Castillo Engineering, Inc.PROJECT 406 S WESTERN AVE 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. A = 12 ( 32 + 3.50 + 32 ) =L 67.5 in 5.63 ft q = 1500 psf (BEARING CAPACITY)(SELF WEIGHT) PA =1500 -( 5.63 x 2.67 )=K Pload =1.3756 K Pnet =6.47 k 144 5.63 ft2 CF2. CAPACITY CHECK 1000 11/07/2025 40( 5.63 ) 7.84 Pnet = 6.47 39 ARCHITECT Castillo Engineering, Inc.PROJECT 406 S WESTERN AVE 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. A = 12 ( 24 + 3.50 + 24 ) =L 51.5 in 4.29 ft q = 1500 psf (BEARING CAPACITY)(SELF WEIGHT) PA =1500 -( 4.29 x 2 )=K Pload =1.3004 K Pnet =4.79 k 144 4.29 ft2 (E)CF1. CAPACITY CHECK EXISTING 1000 11/07/2025 40( 4.29 ) 6.09 Pnet = 4.79 40 ARCHITECT Castillo Engineering, Inc.PROJECT 406 S WESTERN AVE 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. A = 12 ( 24 + 3.50 + 24 ) =L 51.5 in 4.29 ft q = 1500 psf (BEARING CAPACITY)(SELF WEIGHT) PA =1500 -( 4.29 x 2 )=K Pload =1.6639 K Pnet =4.43 k 144 4.29 ft2 (E)CF2. CAPACITY CHECK EXISTING 1000 11/07/2025 40( 4.29 ) 6.09 Pnet = 4.43 41 ARCHITECT Castillo Engineering, Inc.PROJECT 406 S WESTERN AVE 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. A = 12 ( 24 + 3.50 + 24 ) =L 51.5 in 4.29 ft q = 1500 psf (BEARING CAPACITY)(SELF WEIGHT) PA =1500 -( 4.29 x 2 )=K Pload =2.2887 K Pnet =3.80 k 144 4.29 ft2 (E)CF3. CAPACITY CHECK EXISTING 1000 11/07/2025 40( 4.29 ) 6.09 Pnet = 3.80 42 ARCHITECT CASTILLO ENGINEERING INC.JOB 406 S WESTERN AVE 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. SPREAD FOOTINGS P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL =K P ALLOW.= K USE:TYPE 1.5 FOOTING USE CONTINUOUS FOOTING CAPACITY P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL =K P ALLOW.= K USE:TYPE 1.5 FOOTING USE CONTINUOUS FOOTING CAPACITY P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL =K P ALLOW.= K USE:TYPE 1.5 FOOTING USE CONTINUOUS FOOTING CAPACITY P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL = K P ALLOW.= K USE:TYPE 1.5 FOOTING USE CONTINUOUS FOOTING CAPACITY P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL = K P ALLOW.= K USE:TYPE 1.5 FOOTING USE CONTINUOUS FOOTING CAPACITY 11/07/2025 0 0 0.805 3.04 0.73 F1 0.805 0 0 F2 0.118 F3 0.59 3.04 F5 0.78 0 F4 1.48 2.26 3.04 0 3.04 1.98 0 0 0 1.98 0 0 1.32 4X6 4X6 4X6 4X6 4X6 0.118 3.04 0 0 F-SPREAD FOOTINGS1500 43 ARCHITECT CASTILLO ENGINEERING INC.JOB 406 S WESTERN AVE 1205 Pine Avenue, Suite 201 Long Beach, CA 90813 ENGR. MC DATE JOB NO. 25-5096 SHEET NO. SPREAD FOOTINGS P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL =K P ALLOW.= K USE:TYPE 1.5 FOOTING USE CONTINUOUS FOOTING CAPACITY P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL =K P ALLOW.= K USE:TYPE 1.5 FOOTING USE CONTINUOUS FOOTING CAPACITY P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL =K P ALLOW.= K USE:TYPE 1.5 FOOTING USE CONTINUOUS FOOTING CAPACITY P1 = K P2 = K P3 = K P4 = K USE POST P TOTAL = K P ALLOW.= K USE:TYPE 2.5 FOOTING USE CONTINUOUS FOOTING CAPACITY 11/07/2025 0 0 0.36 3.04 0.17 F6 0.36 0 0 F7 0.805 F8 0 3.04 F10 1.611 1.611 F9 1.611 6.444 8.44 1.611 0 0 0.17 4X4 4X6 4X6 4X8 0.805 3.04 0 0 F-SPREAD FOOTINGS1500 44 CE Engineering Software v1.0 PROJECT: == TYPICAL SQUARE PAD FOOTING DESIGN TABLE == (2/99) Bar #Area (in2) Soil Bearing Pressure: Miscellaneous:3 0.11 q =1500 psf column footprint =4 in 4 0.20 qu = q x 1.6 =2400 psf steel spacing factor =10 5 0.31 (for selection of steel spacing vs. size only) 6 0.44 Material Strengths:7 0.60 concrete =2500 psi Notes:8 0.78 fy =60 ksi Assumes Pu = 1.6 (DL + LL)9 1.00 10 1.23 11 1.56 Mark: Size Thick Pmax Depth Mu a As As As min As (ft) -SQ. (in) (k) (in)Vact (k)Vall (k)OK?Vact (k)Vall (k)OK? (k-in) (in) (Req'd)(200/Fy)(.0018) Use USE: 2.0 12 5.40 8 0.7 16.3 Y 6.5 65.3 Y 18 0.05 0.04 0.96 0.52 0.52 3 # 4 2.5 12 8.44 8 2.3 20.4 Y 11.3 65.3 Y 38 0.08 0.09 1.20 0.65 0.65 4 # 4 3.0 12 12.15 8 4.3 24.5 Y 17.3 65.3 Y 69 0.13 0.16 1.44 0.78 0.78 4 # 4 3.5 12 16.5 8 6.9 28.6 Y 24.3 65.3 Y 114 0.18 0.27 1.68 0.91 0.91 5 # 4 4.0 12 21.6 8 10.1 32.6 Y 32.4 65.3 Y 174 0.24 0.41 1.92 1.04 1.04 6 # 4 4.5 12 27.3 8 13.8 36.7 Y 41.6 65.3 Y 253 0.31 0.60 2.16 1.17 1.17 4 # 5 5.0 12 33.8 8 18.0 40.8 Y 51.8 65.3 Y 353 0.39 0.84 2.40 1.30 1.30 5 # 5 5.5 12 40.8 8 22.8 44.9 Y 63.2 65.3 Y 476 0.49 1.14 2.64 1.43 1.51 5 # 5 6.0 15 47.3 11 24.2 67.3 Y 72.3 112.2 Y 607 0.41 1.04 3.60 1.94 1.94 7 # 5 ONE WAY SHEAR: TWO WAY SHEAR: C:\Users\mcast\Dropbox\CE-OFFICE\CE-ENGINEERING\CE-SOFTWARE-10-CBC\FOUNDATION\F-TYPICAL FOOTING1500 45 ASCE Hazards Report Address: 406 S Western Ave Santa Ana, California 92703 Standard:ASCE/SEI 7-22 Latitude:33.742554 Risk Category:II Longitude:-117.891388 Soil Class:Default Elevation:83.97856678180223 ft (NAVD 88) Page 1 of 4https://ascehazardtool.org/Fri Jul 11 2025 46 PGA M : 0.67 SMS : 1.75 SM1 : 1.23 SDS : 1.17 SD1 : 0.82 T L : 8 SS : 1.49 S1 : 0.55 VS30 : 260 Seismic Design Category:D Multi-Period Design Spectrum S (g) vs T(s)a Multi-Period MCE SpectrumR S (g) vs T(s)a Two-Period Design Spectrum S (g) vs T(s)a Two-Period MCE SpectrumR S (g) vs T(s)a Design Vertical Response Spectrum Vertical ground motion data has not yet been made available by USGS. MCE Vertical Response SpectrumR Vertical ground motion data has not yet been made available by USGS. Seismic DefaultSite Soil Class: Results: Page 2 of 4https://ascehazardtool.org/Fri Jul 11 2025 47 Data Accessed: Fri Jul 11 2025 Date Source: USGS Seismic Design Maps based on ASCE/SEI 7-22 and ASCE/SEI 7-22 Table 1.5-2. Additional data for site-specific ground motion procedures in accordance with ASCE/SEI 7-22 Ch. 21 are available from USGS. Page 3 of 4https://ascehazardtool.org/Fri Jul 11 2025 48 The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE. ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE standard. In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE Hazard Tool. Page 4 of 4https://ascehazardtool.org/Fri Jul 11 2025 49 ROOF FRAMING AREA AND WALLS PERIMETER AREA= 2778.87 SQ.FT. PERIMETER= 287.42 FT. 50 Castillo Engineering Inc.JOB: ENGR: JOB NO.SHEET NO. SEISMIC BASE SHEAR (ASCE 7-22) Degrees Degrees (Table 20.3-1) R = (Table 12.2-1) SMS = S1 = SM1 = SDS = (2/3)SMS (11.4-3) = (2/3)x = SD1 = (2/3)SM1 (11.4-4) = (2/3)x = Ta =Ct hn x (12.8-7) =x 13 = V = Cs W VMIN = W VMIN = 0.5 S1 Ie W For S1 is equal to or greater than 0.6g = x x W = W [GOVERNS] VMAX = W =x W = W x V =r W =x x W = x W = W [Strength Level] V = x W =W [Allowable Stress Design] 406 S WESTERN AV 25-5096 D 2.5 FG DATE: 11/07/2025 Latitude: 0.137 1.75 1.23 0.820 0.02 0.75 1.75 0.55 Longitude: 33.742554 -117.8914 SITE CLASS: 1.23 1.167 2.39545 SDS Ie 0.820 1.00 0.137 2.5 SD1 Ie 2.5 T R 0.01 R 0.5 0.5500 1.00 2.5 0.110 0.7 0.43 0.607 1.30.467 0.607 R 1.167 1.00 1.3 51 Castillo Engineering Inc.JOB FG DATE JOB NO. 25-5096 SHEET NO. SEISMIC ANALYSIS WEIGHT Wroof = ( 15 psf + 5.0 psf ) x ft^2 = kips Wwall = 16 psf x 8 ft /2 x ft = kips W2 = kips BASE SHEAR = x = x = kips WTOTAL 406 S WESTERN AV 74.0 55.6 287.42 18.4 2778.9 lbs/sq ft 11/07/2025 VBASE ENGR. VBASE 0.43 31.440.43 74.0 (11.313) 52 X1.1 SHEAR WALLS KEY PLAN X A=430 A=490 A=78.4 X1.2 X3.1 X2.1 53 A=264 SHEAR WALLS KEY PLAN Y Y1 . 1 Y1 . 2 Y2 . 1 Y4 . 1 A=324 A=220 A=142 Y3 . 1 54 ARCHITECT JOB 406 S WESTERN AV ENGR. MC JOB NO. 25-5096 SHEET NO. R=6.5 F1= 11.313 SW U-FORCE T.A. FORCE L1 L2 L3 L4 HEIGHT X1 11.31 430.00 4.86 7.67 4.75 X2 11.31 78.40 0.89 2.82 X3 11.31 490.00 5.54 12.08 Y1 11.31 264.00 2.99 3.42 6.17 Y2 11.31 324.00 3.67 3.82 Y3 11.31 220.00 2.49 6.91 Y4 11.31 142.00 1.61 7.33 SEISMIC FORCES FLOOR 1 Castillo Engineering, Inc. SEISMIC DESIGN FORCES FOR SHEAR OF LEVEL 1 1205 PINE AVE LONG BEACH CA 55 SHEAR WALLS FORCES X1.1 X1.2 X3.1 X2.1 4.86k 0.89k 5.54k 2.99k 3.67k 1.61k2.49k Y1 . 1 Y1 . 2 Y2 . 1 Y4 . 1 Y3 . 1 56 ARCHITECT JOB 406 S WESTERN AV CASTILLO ENGINEERING, INC. 1205 Pine Avenue, Suite 201 ENGR. MC Long Beach, CA 90813 JOB NO. 25-5096 SHEET NO. TAG:X1.1 ( 7.67 ft),X1.2 ( 4.75 ft) FORCE: ###kips ###0.00 ft F1=kips H1:8.00 ft SEISMIC GOVERNS FTOTAL=kips Load Comb.:(0.6-.14SDS) D + 0.7 E SDS= 1.17 SHEAR STRESS X1.1 :L1= ft v= lbs = plf X1.2 :L2= ft ft Ltotal= ft OVERTURNING MOT= x 7.67 x 8.0 = k-ft 12.42 FLOOR: psf x ft = plf FLOOR: psf x ft = plf h/w=1.04 OK WALL: psf x ft = plf w = plf Vallow=510 PLF MR= x 7.67 ^2/2 = k-ft USE: TYPE 4 SHEARWALL - 0.44 x = kips kips OK USE:4 x 4 POST w/ H.D. 2-H.D.11 Tallow= 2X9.34 = 18.68>16.333MIN. HDU-2 MOT= x 4.75 x 8.0 = k-ft 12.42 ROOF: psf x ft = plf FLOOR: psf x ft = plf h/w=1.68 OK WALL: psf x ft = plf w = plf Vallow=510 PLF MR= x 4.75 ^2/2 = k-ft USE: TYPE 4 SHEARWALL - 0.44 x = kips kips OK USE:4 x 4 POST w/ H.D. MIN. HDU2 HDU2 2.97 2.77 HDU2 14.88 4.75 Tallow=3.08 0.158 1.78 T= 14.9 1.78 16 8 128 158 Tributary 15 2 30 0 0 0 WALL:X1.2 4.86 Unit load 0 0.00 0 7.67 Tallow=3.08 0.218 6.41 T= 24.0 16 8.00 128 218 6.41 WALL:X1.1 4.86 15 6.00 Unit load 90 24.03 Tributary 12.42 4.75 12.42 SHEARWALL CALCULATIONS-LEVEL 1 0.00 4.86 4.86 7.67 4865 392 57 ARCHITECT JOB 406 S WESTERN AV CASTILLO ENGINEERING, INC. 1205 Pine Avenue, Suite 201 ENGR. MC Long Beach, CA 90813 JOB NO. 25-5096 SHEET NO. TAG:X2.1 ( 2.82 ft),X2.2 ( 0.00 ft) FORCE: ###kips ###0.00 ft F1=kips H1:8.00 ft SEISMIC GOVERNS FTOTAL=kips Load Comb.:(0.6-.14SDS) D + 0.7 E SDS= 1.17 SHEAR STRESS X2.1 :L1= ft v= lbs = plf X2.2 :L2= ft ft Ltotal= ft OVERTURNING MOT= x 2.82 x 8.0 = k-ft 2.82 FLOOR: psf x ft = plf FLOOR: psf x ft = plf h/w=2.84 2w/h factor=0.90 WALL: psf x ft = plf w = plf Vallow=510 x 0.90 = PLF MR= x 2.82 ^2/2 = k-ft USE: TYPE 4 SHEARWALL - 0.44 x = kips kips OK USE:4 x 4 POST w/ H.D. 2-H.D.11 Tallow= 2X9.34 = 18.68>16.333MIN. HDU-2 457 2.38 HDU2 0 0.00 0 2.82 Tallow=3.08 0.218 0.87 T= 7.1 16 8.00 128 218 0.87 WALL:X2.1 0.89 15 6.00 Unit load 90 7.10 Tributary 2.82 0.00 2.82 SHEARWALL CALCULATIONS-LEVEL 1 0.00 0.89 0.89 2.82 887 315 58 ARCHITECT JOB 406 S WESTERN AV CASTILLO ENGINEERING, INC. 1205 Pine Avenue, Suite 201 ENGR. MC Long Beach, CA 90813 JOB NO. 25-5096 SHEET NO. TAG:X3.1 ( 12.08 ft),X3.2 ( 0.00 ft) FORCE: ###kips ###0.00 ft F1=kips H1:8.00 ft SEISMIC GOVERNS FTOTAL=kips Load Comb.:(0.6-.14SDS) D + 0.7 E SDS= 1.17 SHEAR STRESS X3.1 :L1= ft v= lbs = plf X3.2 :L2= ft ft Ltotal= ft OVERTURNING MOT= x 12.08 x 8.0 = k-ft 12.08 FLOOR: psf x ft = plf FLOOR: psf x ft = plf h/w=0.66 OK WALL: psf x ft = plf w = plf Vallow=510 PLF MR= x 12.08 ^2/2 = k-ft USE: TYPE 4 SHEARWALL - 0.44 x = kips kips OK USE:4 x 4 POST w/ H.D. 2-H.D.11 Tallow= 2X9.34 = 18.68>16.333MIN. HDU-2 2.94 HDU2 0 0.00 0 12.08 Tallow=3.08 0.278 20.28 T= 44.3 16 8.00 128 278 20.28 WALL:X3.1 5.54 15 10.00 Unit load 150 44.35 Tributary 12.08 0.00 12.08 SHEARWALL CALCULATIONS-LEVEL 1 0.00 5.54 5.54 12.08 5543 459 59 ARCHITECT JOB 406 S WESTERN AV CASTILLO ENGINEERING, INC. 1205 Pine Avenue, Suite 201 ENGR. MC Long Beach, CA 90813 JOB NO. 25-5096 SHEET NO. TAG:Y1.1 ( 3.42 ft),Y1.2 ( 6.17 ft) FORCE: ###kips ###0.00 ft F1=kips H1:8.00 ft SEISMIC GOVERNS FTOTAL=kips Load Comb.:(0.6-.14SDS) D + 0.7 E SDS= 1.17 SHEAR STRESS Y1.1 :L1= ft v= lbs = plf Y1.2 :L2= ft ft Ltotal= ft OVERTURNING MOT= x 3.42 x 8.0 = k-ft 9.59 FLOOR: psf x ft = plf FLOOR: psf x ft = plf h/w=2.34 2w/h factor=0.96 WALL: psf x ft = plf w = plf Vallow=340 x 0.96 = PLF MR= x 3.42 ^2/2 = k-ft USE: TYPE 6 SHEARWALL - 0.44 x = kips kips OK USE:4 x 4 POST w/ H.D. 2-H.D.11 Tallow= 2X9.34 = 18.68>16.333MIN. HDU-2 MOT= x 6.17 x 8.0 = k-ft 9.59 ROOF: psf x ft = plf FLOOR: psf x ft = plf h/w=1.30 OK WALL: psf x ft = plf w = plf Vallow=340 PLF MR= x 6.17 ^2/2 = k-ft USE: TYPE 6 SHEARWALL - 0.44 x = kips kips OK USE:4 x 4 POST w/ H.D. MIN. HDU2 326 HDU2 2.26 2.36 HDU2 15.37 6.17 Tallow=3.08 0.173 3.29 T= 15.4 3.29 16 8 128 173 Tributary 15 3 45 0 0 0 WALL:Y1.2 2.99 Unit load 0 0.00 0 3.42 Tallow=3.08 0.173 1.01 T= 8.5 16 8.00 128 173 1.01 WALL:Y1.1 2.99 15 3.00 Unit load 45 8.52 Tributary 9.59 6.17 9.59 SHEARWALL CALCULATIONS-LEVEL 1 0.00 2.99 2.99 3.42 2987 311 60 ARCHITECT JOB 406 S WESTERN AV CASTILLO ENGINEERING, INC. 1205 Pine Avenue, Suite 201 ENGR. MC Long Beach, CA 90813 JOB NO. 25-5096 SHEET NO. TAG:Y2.1 ( 3.82 ft),Y2.2 ( 0.00 ft) FORCE: ###kips ###0.00 ft F1=kips H1:8.00 ft SEISMIC GOVERNS FTOTAL=kips Load Comb.:(0.6-.14SDS) D + 0.7 E SDS= 1.17 SHEAR STRESS Y2.1 :L1= ft v= lbs = plf Y2.2 :L2= ft ft Ltotal= ft OVERTURNING MOT= x 3.82 x 8.0 = k-ft 3.82 FLOOR: psf x ft = plf FLOOR: psf x ft = plf h/w=2.09 2w/h factor=0.99 WALL: psf x ft = plf w = plf Vallow=1020 x 0.99 = PLF MR= x 3.82 ^2/2 = k-ft USE: TYPE 4D SHEARWALL - 0.44 x = kips kips OK USE:4 x 6 POST w/ H.D. 2-H.D.11 Tallow= 2X9.34 = 18.68>16.333MIN. HDU-2 1008 7.49 HDU11 0 0.00 0 3.82 Tallow=9.34 0.218 1.59 T= 29.3 16 8.00 128 218 1.59 WALL:Y2.1 3.67 15 6.00 Unit load 90 29.32 Tributary 3.82 0.00 3.82 SHEARWALL CALCULATIONS-LEVEL 1 0.00 3.67 3.67 3.82 3665 960 61 JOB 406 S WESTERN AVARCHITECT CASTILLO ENGINEERING, INC. 1205 Pine Avenue, Suite 201 ENGR. MC Long Beach, CA 90813 JOB NO. SHEET NO.25-5096 TAG:Y3.1 6.91 ft),(Y3.2 0.00 ft)( FORCE: ######kips 0.00 ft F1=H1:kips 8.00 ft SEISMIC GOVERNS FTOTAL=kips Load Comb.:(0.6-.14SDS) D + 0.7 E SDS= 1.17 SHEAR STRESS Y3.1 :plflbs =v=ftL1= Y3.2 :ftL2=ft ftLtotal= OVERTURNING k-ft=8.0x6.91xMOT= 6.91 plf=ftxpsfFLOOR: plf=ftxpsfFLOOR:h/w=1.16 OK plf=ftxpsfWALL: Vallow=plf=w 510 PLF k-ftx=^2/26.91MR=USE: SHEARWALL4TYPE kips=x-0.44 kips 2-H.D.11 Tallow= 2X9.34 = 18.68>16.333MIN. HDU-2 2.64 OK USE: 4 x 4 POST w/ H.D.HDU2 00.000 6.91 Tallow=3.08 0.158 3.77 19.9T= 1288.0016 158 3.77 WALL:Y3.1 2.49 2.0015 Unit load 30 19.91 Tributary 6.91 0.00 6.91 SHEARWALL CALCULATIONS-LEVEL 1 0.00 2.49 2.49 24896.91 360 62 JOB 406 S WESTERN AVARCHITECT CASTILLO ENGINEERING, INC. 1205 Pine Avenue, Suite 201 ENGR. MC Long Beach, CA 90813 JOB NO. SHEET NO.25-5096 TAG:Y4.1 7.33 ft),(Y4.2 0.00 ft)( FORCE: ######kips 0.00 ft F1=H1:kips 8.00 ft SEISMIC GOVERNS FTOTAL=kips Load Comb.:(0.6-.14SDS) D + 0.7 E SDS= 1.17 SHEAR STRESS Y4.1 :plflbs =v=ftL1= Y4.2 :ftL2=ft ftLtotal= OVERTURNING k-ft=8.0x7.33xMOT= 7.33 plf=ftxpsfFLOOR: plf=ftxpsfFLOOR:h/w=1.09 OK plf=ftxpsfWALL: Vallow=plf=w 340 PLF k-ftx=^2/27.33MR=USE: SHEARWALL6TYPE kips=x-0.44 kips 2-H.D.11 Tallow= 2X9.34 = 18.68>16.333MIN. HDU-2 1.50 OK USE: 4 x 4 POST w/ H.D.HDU2 00.000 7.33 Tallow=3.08 0.158 4.24 12.9T= 1288.0016 158 4.24 WALL:Y4.1 1.61 2.0015 Unit load 30 12.85 Tributary 7.33 0.00 7.33 SHEARWALL CALCULATIONS-LEVEL 1 0.00 1.61 1.61 16067.33 219 63 Company:Date:2/17/2023 Engineer:Page:1/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.2.2311.2 1.Project information Project description: Location: Fastening description: 2. Input Data & Anchor Parameters General Design method:ACI 318-19 Units: Imperial units Anchor Information: Anchor type: Bonded anchor Material: F1554 Grade 36 Diameter (inch): 0.625 Effective Embedment depth, hef (inch): 12.500 Code report: ICC-ES ESR-4057 Anchor category: - Anchor ductility: Yes hmin (inch): 13.88 cac (inch): 33.54 Cmin (inch): 1.75 Smin (inch): 3.00 Base Material Concrete: Normal-weight Concrete thickness, h (inch): 18.00 State: Cracked Compressive strength, f’c (psi): 2500 Ψc,V: 1.0 Reinforcement condition: Supplementary reinforcement not present Supplemental edge reinforcement: Not applicable Reinforcement provided at corners: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Hole condition: Dry concrete Inspection: Continuous Temperature range, Short/Long: 150/110°F Reduced installation torque (for AT-3G): Not applicable Ignore 6do requirement: Not applicable Build-up grout pad: No Recommended Anchor Anchor Name: SET-3G™ - SET-3G w/ 5/8"Ø F1554 Gr. 36 Code Report: ICC-ES ESR-4057 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 64 Company:Date:2/17/2023 Engineer:Page:2/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.2.2311.2 Load and Geometry Load factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: No Anchors subjected to sustained tension: No Apply entire shear load at front row: Yes Anchors only resisting wind and/or seismic loads: No Strength level loads: Nua [lb]: 5645 Vuax [lb]: 0 Vuay [lb]: 0 <Figure 1> Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 65 Company:Date:2/17/2023 Engineer:Page:3/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.2.2311.2 <Figure 2> Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 66 Company:Date:2/17/2023 Engineer:Page:4/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.2.2311.2 3. Resulting Anchor Forces Anchor Tension load, Nua (lb) Shear load x, Vuax (lb) Shear load y, Vuay (lb) Shear load combined, √(Vuax)²+(Vuay)² (lb) 1 5645.0 0.0 0.0 0.0 Sum 5645.0 0.0 0.0 0.0 Maximum concrete compression strain (‰): 0.00 Maximum concrete compression stress (psi): 0 Resultant tension force (lb): 5645 Resultant compression force (lb): 0 Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00 4. Steel Strength of Anchor in Tension (Sec. 17.6.1) Nsa (lb)Nsa (lb) 13110 0.75 9833 5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.6.2) Nb = kc a f’chef1.5 (Eq. 17.6.2.2.1) kc a f’c (psi)hef (in)Nb (lb) 17.0 1.00 2500 12.500 37565 Ncb =(ANc / ANco)ed,N c,N cp,NNb (Sec. 17.5.1.2 & Eq. 17.6.2.1a) ANc (in2)ANco (in2)ca,min (in)ed,N c,N cp,N Nb (lb)Ncb (lb) 450.00 1406.25 2.50 0.740 1.00 1.000 37565 0.65 5782 6. Adhesive Strength of Anchor in Tension (Sec. 17.6.5) k,cr =k,crfshort-termKsat(f’c /2,500)n k,cr (psi)fshort-term Ksat f’c (psi)n k,cr (psi) 1356 1.00 1.00 2500 0.24 1356 Nba =a cr dahef (Eq. 17.6.5.2.1) a cr (psi)da (in)hef (in)Nba (lb) 1.00 1356 0.63 12.500 33281 Na =(ANa / ANa0)ed,Na cp,NaNba (Sec. 17.5.1.2 & Eq. 17.6.5.1a) ANa (in2)ANa0 (in2)cNa (in)ca,min (in)ed,Na cp,Na Nba (lb)Na (lb) 197.36 307.10 8.76 2.50 0.786 1.000 33281 0.65 10922 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 67 Company:Date:2/17/2023 Engineer:Page:5/5 Project: Address: Phone: E-mail: Anchor Designer™ Software Version 3.2.2311.2 11. Results Interaction of Tensile and Shear Forces (Sec. 17.8) Tension Factored Load, Nua (lb)Design Strength, øNn (lb)Ratio Status Steel 5645 9833 0.57 Pass Concrete breakout 5645 5782 0.98 Pass (Governs) Adhesive 5645 10922 0.52 Pass SET-3G w/ 5/8"Ø F1554 Gr. 36 with hef = 12.500 inch meets the selected design criteria. 12. Warnings - Designer must exercise own judgement to determine if this design is suitable. - Refer to manufacturer’s product literature for hole cleaning and installation instructions. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 68 Company:Date:12/29/2025 Engineer:Page:1 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.4.2512.1 1.Project information Project description: Location: Design name: Design Comment: 2. Input Data &Anchor Parameters General Design method:ACI 318-19 Units: Imperial units Anchor Information: Anchor type: Cast-in-place Material: F1554 Grade 36 Diameter (inch): 1.000 Effective Embedment depth,hef (inch): 5.000 Anchor category:- Anchor ductility: Yes hmin (inch): 7.63 Cmin (inch): 6.00 Smin (inch): 6.00 Base Material Concrete: Normal-weight Concrete thickness,h (inch): 18.00 State: Uncracked Compressive strength, f’c (psi): 2500 Reinforcement condition:B tension,B shear Supplemental edge reinforcement: No Reinforcement provided at corners: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Ignore 6do requirement: No Build-up grout pad: No Recommended Anchor Anchor Name: Custom CIP Anchor &Steel Plate Washer -1"Ø F1554 Gr. 36 (2.50 x 2.50 x 0.38) Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 69 Company:Date:12/29/2025 Engineer:Page:2 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.4.2512.1 Load and Geometry Load factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: No Anchors subjected to sustained tension: Not applicable Apply entire shear load at front row: Yes Anchors only resisting wind and/or seismic loads: No Strength level loads: Nua [lb]: 9540 Vuax [lb]:0 Vuay [lb]:0 <Figure 1> Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 70 Company:Date:12/29/2025 Engineer:Page:3 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.4.2512.1 <Figure 2> 3. Resulting Anchor Forces Anchor Tension load, Nua (lb) Shear load x, Vuax (lb) Shear load y, Vuay (lb) Shear load combined, √(Vuax)²+(Vuay)² (lb) 1 9540.0 0.0 0.0 0.0 Sum 9540.0 0.0 0.0 0.0 Maximum concrete compression strain (‰): 0.00 Maximum concrete compression stress (psi):0 Resultant tension force (lb): 9540 Resultant compression force (lb):0 Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 71 Company:Date:12/29/2025 Engineer:Page:4 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.4.2512.1 4. Steel Strength of Anchor in Tension (Sec. 17.6.1) Nsa (lb)Nsa (lb) 35133 0.75 26350 5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.6.2) Nb = kc a f’chef1.5 (Eq. 17.6.2.2.1) kc a f’c (psi)hef (in)Nb (lb) 24.0 1.00 2500 5.000 13416 Ncb =(ANc / ANco)ed,N c,N cp,NNb (Sec. 17.5.1.2 &Eq. 17.6.2.1a) ANc (in2)ANco (in2)ca,min (in)ed,N c,N cp,N Nb (lb)Ncb (lb) 302.24 225.00 17.00 1.000 1.25 1.000 13416 0.70 15769 6. Pullout Strength of Anchor in Tension (Sec. 17.6.3) Npn =c,PNp =c,P8Abrgf’c (Sec. 17.5.1.2, Eq. 17.6.3.1 &17.6.3.2.2a) c,P Abrg (in2)f’c (psi)Npn (lb) 1.4 3.68 2500 0.70 72170 7. Results Interaction of Tensile and Shear Forces (Sec. 17.8) Tension Factored Load,Nua (lb)Design Strength, øNn (lb)Ratio Status Steel 9540 26350 0.36 Pass Concrete breakout 9540 15769 0.60 Pass (Governs) Pullout 9540 72170 0.13 Pass 1"Ø F1554 Gr. 36 (2.50 x 2.50 x 0.38) with hef = 5.000 inch meets the selected design criteria. 8. Warnings -Designer must exercise own judgement to determine if this design is suitable. -Projected breakout area ANc is limited per ACI 318-19 Section 17.6.2.1.3. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 72 CASTILLO ENGINEERING, INC CIVIL & STRUCTURAL ENGINEERS 1205 PINE AVENUE, SUITE 201, LONG BEACH, CA 90813 TEL: 714 725 8320 FAX: 562 961 5700 ENGR. DATE 1513 S SHERBOURNE DR JOB NO. 18-739 SHEAR TRANSFER SHEAR TRANSFER AT ‘A35’ @ 16”: ALLOW FOR 'A35' @ 8" = 0.650 x 12"/8" = 0.487 KLF or 2-‘A35’ @ 16” 'A35' CLIPS @ 8" O.C. SHEAR ALLOW = 0.975 klf SHEAR ALLOW = 975 plf ALLOW FOR 'A35' @ 16" = 0.650 x 12"/16" = 0.487 KLF 'A35' CLIPS @ 16" O.C. SHEAR ALLOW = 0.487 klf SHEAR ALLOW = 487 plf ALLOW FOR 'A35' @ 16" = 0.650 x 12"/32" = 0.487 KLF 'A35' CLIPS @ 32" O.C. SHEAR ALLOW = 0.243 klf SHEAR ALLOW = 243 plf 73 Beam on Elastic Foundation LIC# : KW-06017148, Build:20.24.05.02 CASTILLO ENGINEERING INC.(c) ENERCALC INC 1983-2023 DESCRIPTION:(E)CF1 CASTILLO ENGINEERING INC. Project File: 25-5096.ec6 Project Title: Engineer: Project ID: Project Descr: CODE REFERENCES Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 Material Properties 2.50 7.50 145.0 Elastic Modulus 3,122.0 ksi Soil Subgrade Modulus =200.0 psi / (inch deflection) 11.0Lt Wt FactorO = =60.0 29,000.0 40.0 29,000.0 3 Beam is supported on an elastic foundation, 2 =0.90 0.750 f'c ksi fy - Main Rebar ksi Density 1/2 = fr = f'c * pcf E - Main Rebar ksi psi = Fy - Stirrups ksi == = E - Stirrups ksi E == = Shear : Stirrup Bar Size # Number of Resisting Legs Per Stirrup Phi Values Flexure : \ # I Load Combination :IBC 2021 .Cross Section & Reinforcing Details Rectangular Section, Width = 12.0 in, Height = 18.0 in Span #1 Reinforcing.... 2-#4 at 3.0 in from Bottom, from 0.0 to 12.750 ft in this span 2-#4 at 3.0 in from Top, from 0.0 to 12.750 ft in this span .Service loads entered. Load Factors will be applied for calculations.Applied Loads Load for Span Number 1 Uniform Load : D = 0.0750, Lr = 0.10 k/ft, Tributary Width = 1.0 ft, (ROOF) Uniform Load : D = 0.160 k/ft, Tributary Width = 1.0 ft, (WALL) Point Load : E = -9.540 k @ 8.080 ft Point Load : E = 9.540 k @ 11.50 ft .Design OKDESIGN SUMMARY Maximum Bending Stress Ratio =: 1 Load Combination Span # where maximum occurs Maximum Soil Pressure =ksf at ft Allowable Soil Pressure =OK1.50 ksf Location of maximum on span ft Mn * Phi : Allowable 28.504 k-ft Typical SectionSection used for this span Mu : Applied k-ft Maximum Deflection Max Downward L+Lr+S Deflection in Max Upward L+Lr+S Deflection in Max Downward Total Deflection in Max Upward Total Deflection in .Shear Stirrup Requirements Between 0.00 to 7.95 ft, Vu < PhiVc/2, Req'd Vs = Not Reqd, use stirrups spaced at 0.000 in Between 8.10 to 11.40 ft, PhiVc/2 < Vu <= PhiVc, Req'd Vs = Min 9.6.3.1, use stirrups spaced at 7.500 in Between 11.55 to 12.45 ft, Vu < PhiVc/2, Req'd Vs = Not Reqd, use stirrups spaced at 0.000 in .Maximum Forces & Stresses for Load Combinations Span # Bending Stress Results ( k-ft )Location (ft)Load Combination Mu : Max Stress RatioSegment Length Phi*Mnxin Span MAXimum Bending Envelope 74 Beam on Elastic Foundation LIC# : KW-06017148, Build:20.24.05.02 CASTILLO ENGINEERING INC.(c) ENERCALC INC 1983-2023 DESCRIPTION:(E)CF1 CASTILLO ENGINEERING INC. Project File: 25-5096.ec6 Project Title: Engineer: Project ID: Project Descr: Span # Bending Stress Results ( k-ft )Location (ft)Load Combination Mu : Max Stress RatioSegment Length Phi*Mnxin Span Span # 1 1 12.600 -0.02 28.50 0.00 +1.40D Span # 1 1 12.600 -0.00 28.50 0.00 +1.20D+0.50Lr Span # 1 1 12.600 -0.00 28.50 0.00 +1.20D Span # 1 1 12.600 -0.00 28.50 0.00 +1.20D+1.60Lr Span # 1 1 12.600 -0.00 28.50 0.00 +1.434D+1.30E Span # 1 1 11.550 1.39 28.50 0.05 +1.434D-1.30E Span # 1 1 8.100 26.84 28.50 0.94 +0.90D Span # 1 1 12.600 -0.00 28.50 0.00 +0.6660D+1.30E Span # 1 1 11.550 1.39 28.50 0.05 +0.6660D-1.30E Span # 1 1 8.100 26.84 28.50 0.94 . Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections - Unfactored Loads Span 1Span 1 1 0.0561 12.750 -0.0302 0.000 .Detailed Shear Information Load Combination Vu (k)Span Distance 'd'Comment Phi*Vs Req'd d*Vu/MuMu (ft)(k)(in)Actual Suggest(k-ft)Number (k) Spacing (in) Design Phi*Vc +1.434D-1.30E 1 0.00 15.00 0.11 0.11 0.00 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 0.15 15.00 0.28 0.28 0.01 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 0.30 15.00 0.44 0.44 0.05 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 0.45 15.00 0.61 0.61 0.11 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 0.60 15.00 0.77 0.77 0.20 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 0.75 15.00 0.93 0.93 0.31 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 0.90 15.00 1.08 1.08 0.45 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 1.05 15.00 1.24 1.24 0.61 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 1.20 15.00 1.39 1.39 0.79 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 1.35 15.00 1.54 1.54 0.99 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 1.50 15.00 1.68 1.68 1.22 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 1.65 15.00 1.83 1.83 1.47 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 1.80 15.00 1.97 1.97 1.74 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 1.95 15.00 2.11 2.11 2.03 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 2.10 15.00 2.25 2.25 2.34 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 2.25 15.00 2.38 2.38 2.68 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 2.40 15.00 2.52 2.52 3.03 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 2.55 15.00 2.65 2.65 3.40 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 2.70 15.00 2.77 2.77 3.80 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 2.85 15.00 2.90 2.90 4.21 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 3.00 15.00 3.02 3.02 4.64 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 3.15 15.00 3.14 3.14 5.09 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 3.30 15.00 3.26 3.26 5.56 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 3.45 15.00 3.38 3.38 6.04 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 3.60 15.00 3.49 3.49 6.54 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 3.75 15.00 3.60 3.60 7.06 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 3.90 15.00 3.70 3.70 7.60 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 4.05 15.00 3.81 3.81 8.15 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 4.20 15.00 3.91 3.91 8.72 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 4.35 15.00 4.00 4.00 9.30 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 4.50 15.00 4.10 4.10 9.90 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 4.65 15.00 4.19 4.19 10.51 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 4.80 15.00 4.28 4.28 11.13 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 4.95 15.00 4.36 4.36 11.77 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 5.10 15.00 4.44 4.44 12.42 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 5.25 15.00 4.52 4.52 13.08 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 5.40 15.00 4.59 4.59 13.76 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 5.55 15.00 4.66 4.66 14.44 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 5.70 15.00 4.72 4.72 15.14 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 5.85 15.00 4.78 4.78 15.84 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 6.00 15.00 4.84 4.84 16.56 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 6.15 15.00 4.89 4.89 17.28 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 75 Beam on Elastic Foundation LIC# : KW-06017148, Build:20.24.05.02 CASTILLO ENGINEERING INC.(c) ENERCALC INC 1983-2023 DESCRIPTION:(E)CF1 CASTILLO ENGINEERING INC. Project File: 25-5096.ec6 Project Title: Engineer: Project ID: Project Descr: Detailed Shear Information Load Combination Vu (k)Span Distance 'd'Comment Phi*Vs Req'd d*Vu/MuMu (ft)(k)(in)Actual Suggest(k-ft)Number (k) Spacing (in) Design Phi*Vc +1.434D-1.30E 1 6.30 15.00 4.94 4.94 18.01 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 6.45 15.00 4.98 4.98 18.75 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 6.60 15.00 5.02 5.02 19.49 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 6.75 15.00 5.05 5.05 20.24 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 6.90 15.00 5.08 5.08 20.99 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 7.05 15.00 5.10 5.10 21.75 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 7.20 15.00 5.11 5.11 22.51 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 7.35 15.00 5.12 5.12 23.27 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 7.50 15.00 5.13 5.13 24.04 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 7.65 15.00 5.12 5.12 24.80 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 7.80 15.00 5.11 5.11 25.57 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 7.95 15.00 5.09 5.09 26.33 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D+1.30E 1 8.10 15.00 7.38 7.38 26.84 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 8.25 15.00 7.41 7.41 25.74 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 8.40 15.00 7.45 7.45 24.63 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 8.55 15.00 7.50 7.50 23.52 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 8.70 15.00 7.55 7.55 22.40 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 8.85 15.00 7.62 7.62 21.27 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 9.00 15.00 7.69 7.69 20.13 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 9.15 15.00 7.77 7.77 18.98 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 9.30 15.00 7.86 7.86 17.82 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 9.45 15.00 7.96 7.96 16.64 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 9.60 15.00 8.07 8.07 15.45 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 9.75 15.00 8.18 8.18 14.25 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 9.90 15.00 8.31 8.31 13.02 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 10.05 15.00 8.44 8.44 11.78 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 10.20 15.00 8.59 8.59 10.52 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 10.35 15.00 8.74 8.74 9.23 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 10.50 15.00 8.91 8.91 7.92 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 10.65 15.00 9.08 9.08 6.59 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 10.80 15.00 9.27 9.27 5.23 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 10.95 15.00 9.46 9.46 3.85 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 11.10 15.00 9.67 9.67 2.43 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 11.25 15.00 9.88 9.88 0.98 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D+1.30E 1 11.40 15.00 10.11 10.11 0.49 1.00 14.33 PhiVc/2 < Vu <= PhiVc Min 9.6.3.1 0.00 7.50 +1.434D-1.30E 1 11.55 15.00 2.11 2.11 1.39 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 11.70 15.00 1.86 1.86 1.07 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 11.85 15.00 1.61 1.61 0.80 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 12.00 15.00 1.34 1.34 0.56 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 12.15 15.00 1.07 1.07 0.36 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 12.30 15.00 0.78 0.78 0.21 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 12.45 15.00 0.49 0.49 0.09 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 +1.434D-1.30E 1 12.60 15.00 0.18 0.18 0.02 1.00 14.33 Vu < PhiVc/2 Not Reqd 0.00 0.00 76 PROJECT : PAGE : CLIENT : DESIGN BY : JOB NO. : DATE : 12/30/25 REVIEW BY : INPUT DATA Exposure category (B, C or D)B Importance factor I = 1.00 Category II Basic wind speed V = 115 mph Topographic factor Kzt =1 Flat Building height to eave he =8 ft Building height to ridge hr =13 ft Building length L = 77.17 ft Building width B = 41.07 ft Effective area of components A = 10 ft2 DESIGN SUMMARY Max horizontal force normal to building length, L, face = 10.03 kips X 0.6= 6.02 kips (ASD) Max horizontal force normal to building length, B, face = 6.52 kips X 0.6= 3.91 kips (ASD) Max total horizontal torsional load = 83 ft-kips Max total upward force = 49.30 kips ANALYSISVelocity pressure where: qh = velocity pressure at mean roof height, h. Kh = velocity pressure exposure coefficient evaluated at height, h,= 0.70 Kd = wind directionality factor =0.85 h = mean roof height =10.50 ft < 60 ft, [Satisfactory] Design pressures for MWFRS p = qh [(G Cpf )-(G Cpi )] where: p = pressure in appropriate zone G Cp f = product of gust effect factor and external pressure coefficient G Cp i = product of gust effect factor and internal pressure coefficient =0.18 or -0.18 a = width of edge strips, MAX[ MIN(0.1B, 0.4h), 0.04B,3] =4.11 ft Net Pressures (psf), Basic Load Cases Net Pressures (psf), Torsional Load Cases 13.68 0.00 13.68 (+GCp i )(-GCp i )(+GCp i )(-GCp i )(+GCp i )(-GCp i ) 1 0.48 5.95 13.20 0.40 4.43 11.68 1T 0.48 1.49 3.30 2 -0.69 -17.53 -10.27 -0.69 -17.53 -10.27 2T -0.69 -4.38 -2.57 3 -0.43 -12.36 -5.11 -0.37 -11.08 -3.83 3T -0.43 -3.09 -1.28 4 -0.37 -11.10 -3.85 -0.29 -9.47 -2.22 4T -0.37 -2.78 -0.96 1E 0.72 10.88 18.13 0.61 8.66 15.91 0.00 2E -1.07 -25.18 -17.93 -1.07 -25.18 -17.93 3E -0.62 -16.17 -8.92 -0.53 -14.30 -7.05 (+GCp i )(-GCp i ) 4E -0.55 -14.74 -7.49 -0.43 -12.29 -5.04 1T 0.40 1.11 2.92 5 -0.45 -12.69 -5.44 -0.45 -12.69 -5.44 2T -0.69 -4.38 -2.57 6 -0.45 -12.69 -5.44 -0.45 -12.69 -5.44 3T -0.37 -2.77 -0.96 4T -0.29 -2.37 -0.55 CASTILLO Net Pressure withG Cp f Wind Analysis for Low-rise Building Roof angle q = G Cp f Net Pressure with 25-5096 Surface Roof angle q = G Cp f Net Pressure with Surface Roof angle q = G Cp f Net Pressure with ENGINEERING Surface Roof angle q = 77 Basic Load Cases in Transverse Direction Basic Load Cases in Longitudinal Direction Area Area (ft2)(+GCp i )(-GCp i )(ft2)(+GCp i )(-GCp i ) 1 552 3.28 7.28 1 357 1.58 4.17 2 1457 -25.54 -14.97 2 1305 -22.87 -13.40 3 1457 -18.02 -7.45 3 1305 -14.46 -4.99 4 552 -6.12 -2.12 4 357 -3.38 -0.79 1E 66 0.71 1.19 1E 74 0.64 1.18 2E 174 -4.37 -3.11 2E 326 -8.21 -5.85 3E 174 -2.81 -1.55 3E 326 -4.67 -2.30 4E 66 -0.97 -0.49 4E 74 -0.91 -0.37 Horiz. 8.94 8.94 Horiz. 6.52 6.52 Vert. -49.30 -26.31 Vert. -48.78 -25.79 10 psf min.Horiz. 10.03 10.03 10 psf min.Horiz. 4.31 4.31 Sec. 6.1.4.1 Vert. -31.69 -31.69 Sec. 6.1.4.1 Vert. -31.69 -31.69 Torsional Load Cases in Transverse Direction Torsional Load Cases in Longitudinal Direction Area Area (ft2)(+GCp i )(-GCp i )(+GCp i )(-GCp i )(ft2)(+GCp i )(-GCp i )(+GCp i )(-GCp i ) 1 243 1.45 3.21 25 55 1 142 0.63 1.66 4 10 2 642 -11.25 -6.59 -46 -27 2 979 -17.15 -10.05 78 46 3 642 -7.94 -3.28 32 13 3 979 -10.84 -3.75 -49 -17 4 243 -2.70 -0.94 46 16 4 142 -1.34 -0.31 8 2 1E 66 0.71 1.19 25 41 1E 74 0.64 1.18 10 19 2E 174 -4.37 -3.11 -36 -25 2E 326 -8.21 -5.85 37 27 3E 174 -2.81 -1.55 23 13 3E 326 -4.67 -2.30 -21 -10 4E 66 -0.97 -0.49 33 17 4E 74 -0.91 -0.37 15 6 1T 309 0.46 1.02 -9 -20 1T 216 0.24 0.63 -2 -6 2T 815 -3.57 -2.09 16 10 2T 1305 -5.72 -3.35 -52 -31 3T 815 -2.52 -1.04 -12 -5 3T 1305 -3.61 -1.25 33 11 4T 309 -0.86 -0.30 -17 -6 4T 216 -0.51 -0.12 -5 -1 83 83 55.5 55.5 Design pressures for components and cladding p = qh[ (G Cp) - (G Cpi)] where: p = pressure on component pmin = 16 psf (Sec. 30.2.2) G Cp = external pressure coefficient. see table below Effective Area (ft2) GCP - GCP GCP - GCP GCP - GCP GCP - GCP GCP - GCP Comp.10 0.50 -1.00 0.50 -1.40 0.50 -1.40 1.00 -1.10 1.00 -1.40 Positive Negative Positive Negative Positive Negative Positive Negative Positive Negative 16.00 -23.77 16.00 -31.83 16.00 -31.83 23.77 -25.78 23.77 -31.83 Pressure Surface Pressure (k) with Zone 1 Zone 2 Total Horiz. Torsional Load, MT Comp. & Cladding Zone 1 ( psf ) Zone 3 Zone 4Zone 2 Torsion (ft-k) Total Horiz. Torsional Load, MT Zone 5 Zone 3 Zone 4 Zone 5 Pressure (k) withTorsion (ft-k)Surface S Surface Pressure (k) withPressure (k) with S Surface 78 O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Submittal Criteria Form Required for Single Family or Duplex Residences (Use Commercial form for lots with 3+ dwelling units or new residential tracts) Complete the Project Information and Questionnaire below, then sign and date the Applicant Certification. Project Information  New Single Family Residence/Duplex  Addition/Remodel  ADU  Other Address: Unit #: City or Unincorporated County Area: ZIP: Scope of Work: Existing Area: Area to be Added: Total Resulting Area: Stories: Area Added in Past 2 Years (excluding this project): Yes No Questionnaire OCFA Plan Type if “Yes” 1.   New – Is this a new single family residence or duplex? *(PR160) Residential Site with Water Availability (PR400-402) Fire Sprinkler 2.   ADU – Is this a new Accessory Dwelling Unit (ADU) on the same property as a house that already has fire sprinklers or a house that will have fire sprinklers added as part of this project? (PR400-402) Fire Sprinkler 3.   Addition – Is this (A) an addition to a currently sprinklered building, or (B) an addition requiring a fire sprinkler retrofit based on a threshold set by local ordinance? (PR400-402) Fire Sprinkler 4.   Distance – Is the most remote portion of the addition, ADU or other detached structure greater than 140-feet from the fire access roadway? *(PR160) Residential Site 5.   Total Area – Will the addition result in a total area of greater than 3,600 square feet (sf) for non- sprinklered buildings, or greater than 6,200 sf for sprinklered buildings, including the area of all enclosed spaces, such as garages, stairs, and detached structures separated by less than 10-feet? *(PR160) Residential Site with Water Availability 6.   Remodel – Is this a remodel of a sprinklered building with a scope of work that includes adding or removing any interior walls? Note: If “Yes”, then project must be evaluated by a C-16 licensed contractor to determine if a fire sprinkler modification is needed. (PR400-402) Fire Sprinkler 7.   Detached Structure – Is this a new detached utility or accessory structure (not an ADU), such as a garage, workshop, game room, pool house, barn, etc., requiring fire sprinklers based on a threshold set by local ordinance? *(PR160) Residential Site (PR400-402) Fire Sprinkler 8.   Gate – Is a gate being installed across a driveway or road that is designated as a fire department access roadway, or a driveway or road that serves more than a single home/duplex? (PR180) Gate 9.   Methane – Is project located in or less than 100’ from a “Division of Oil, Gas, and Geothermal Resources” (DOGGR) field boundary or well (active or abandoned), less than 300-feet from an oil/gas seep, or less than 1000-feet from a landfill? (Note: For projects in Yorba Linda, this requirement only applies to new homes, enclosed accessory structures, addition to existing structure greater than 1000 sf, and ADU’s). *(PR160) Residential Site *(PR172-174) Methane Test/Mitigation Plans 10.   Vegetation – Is the property/structure (A) on the perimeter of a community containing, or adjacent to slopes or hills, or (B) adjacent to an open space or wildland area containing non-irrigated vegetation, or (C) in a State Responsibility Area or Local Responsibility Area “Fire Hazard Severity Zone”, as defined by the State, or (D) near an area that could be affected by a wildfire in the open space. *(PR125) Fuel Modification (PR182) Accessory Structure *OCFA approval required before issuance of a grading/building permit. All other plans types may be deferred submittals. Applicant Certification I certify, under penalty of perjury, under the laws of the State of California, that the information above is true: Print Name:_______________________________________ Signature:___________________________________________ Date:______________ Phone Number:_____________________________________________ Email:_____________________________________________________________ Attention Building Department Staff – After you’ve verified all questions were answered accurately as “No”, then you may accept this signed form as a written release that an OCFA review is not required. If any questions were answered as “Yes”, then the plan type on the right side may be required. ______If all answers are “No” and the Building Department still requires the applicant to have their plans reviewed by OCFA, or if any answers are “Yes” and the Building Department prefers for OCFA to determine if a review is required, please initial this line and provide an explanation on the Plan Referral Form (on the reverse), to be submitted along with the appropriate plans to OCFA for a determination. For questions and submittal information, please visit ocfa.org, or call OCFA at (714) 573-6100 SFR PROJECT SUMMARY ARCHITECTURAL/DESIGNER 1451 Warren Ave Long Beach, CA 90813 909.333.9159 LOCATION MAP CONSULTANTS CONSTRUCTION NOTES NOTES: 1.IF ADVERSE SOIL CONDITIONS ARE ENCOUNTERED, A SOILS INVESTIGATION REPORT MAY BE REQUIRED. (R401.4) 2.CONSTRUCTION WASTE SHALL BE REDUCED BY 65%, CONSTRUCTION WASTE WILL BE HANDLED CERTIFIED HAULER SHEET INDEX COVER SHEET, PROJECT INFORMATION & (E) PLOT PLAN (N) PLOT PLAN (E) FLOOR PLAN WITH DEMOLITION & (N) ADU FLOOR PLAN ROOF PLAN & SCHEMATIC ELECTRICAL PLAN ELEVATIONS FLASHING DETAILS TITLE 24 STRUCTURAL NOTES TYPICAL DETAILS TYPICAL DETAILS TYPICAL DETAILS TYPICAL DETAILS FOUNDATION PLANS ROOF FRAMING PLANS FOUNDATION DETAILS ROOF FRAMING DETAILS ROOF FRAMING DETAILS 00-C1 01-A1.0 01-A1.1 01-A1.2 01-A1.3 01-A2 03-T1 02-S1.0 02-S1.1 02-S1.2 02-S1.3 02-S1.4 02-S2.0 02-S2.2 02-S3.0 02-S5.0 02-S5.1 OAK TREE ON ADJOINING PROPERTY: YES NO EASEMENT: P.U.E. YES NO POOL: YES NO ANY NEW LANSCAPING MORE THAN 500 SF: YES NO Yolanda Castro DEFERRED SUBMITTALS NONE 1.ALL PRODUCTS (CARPETS, SEALANTS, WOOD, ETC.) MUST FOLLOW CALIFORNIA GREEN BUILDING CODE VOC AND FORMALDEHYDE LIMITS. 2.PROVIDE WATER RESISTANT BACKING BOARD AS A BASE FOR TILE OR WALL PANELS FOR TUB OR SHOWER ENCLOSURES OR WATER CLOSET COMPARTMENT WALLS. 3.SHOWER COMPARTMENTS AND WALL ABOVE BATHTUB WITH SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH, NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72 INCHES ABOVE DRAIN INLET. 4.SHOWERS AND SHOWER-TUBS SHALL BE PROVIDED WITH INDIVIDUAL CONTROL VALVES ON THE PRESSURE BALANCE, THERMOSTATIC, OR COMBINATION PRESSURE BALANCE/THERMOSTATIC MIXING VALVE TYPE THAT PROVIDE SCALD AND THERMAL SHOCK. [408.3 CPC] 5.TANKLESS WATER HEATERS SHALL BE NATIONALLY LISTED AND BE INSTALLED IN ACCORDANCE WITH THE INSTALLATION INSTRUCTIONS THAT WERE APPROVED AS PART OF THEIR LISTING. " THE GAS PIPING SERVING THIS APPLIANCE MUST BE SIZED IN COMPLIANCE WITH THE WATER HEATER'S INSTALLATION INSTRUCTIONS AND THE 2022 CALIFORNIA PLUMBING CODE. 6. STRAP WATER HEATER AT UPPER AND LOWER 1 3 OF VERTICAL HEIGHT. THE LOWER STRAP SHALL MAINTAIN 4" ABOVE THE CONTROLS. [ 507.2 CPC] 7.PER SB 407, ALL NON COMPLIANT PLUMBING FIXTURES SHALL BE REPLACED WITH WATER CONSERVING PLUMBING FIXTURES CONFORMING TO THE LIST BELOW: MAXIMUM FLOW RATES: WATER CLOSETS 1.28 GAL/FLUSH SHOWERHEADS 2.0 GPM MAX FLOW RATE AT 80 psi AND SHALL BE CERTIFIED TO THE PERFORMANCE OF THE U.S.EPA WATERSENSE SPECS. LAVATORY FAUCETS 1.2 GPM AT 60 psi AND MIN FLOW OF 0.8 GPM AT 20 psi KITCHEN FAUCETS 1.8 GPM AT 60 psi 8.CONVENTIONAL IONIZATION SMOKE ALARMS THAT ARE SOLELY BATTERY POWERED SHALL BE EQUIPPED WITH A 10 YEAR BATTERY AND HAVE A SILENCE FEATURE. 9.SMOKE ALARMS SHALL BE TESTED AND MAINTAINED IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS. SMOKE ALARMS SHALL BE REPLACED AFTER 10 YEARS FROM THE DATE OF MANUFACTURED MARKED ON THE UNIT. 10.AN APPROVED CARBON MONOXIDE ALARM SHALL BE INSTALLED WITHIN WHICH FUEL-BURNING APPLIANCES ARE INSTALLED. 11.COMBUSTION AIR FOR FUEL BURNING WATER HEATERS WILL BE PROVIDED IN ACCORDANCE TO THE PLUMBING CODE. 12.PROVIDE A.F.C.I. PROTECTION FOR ALL NEW INTERIOR OUTLETS. 13.PROVIDE BATHROOM A MINIMUM OF (1) 20 AMP CIRCUIT RECEPTACLE OUTLET. SUCH CIRCUIT SHALL HAVE NO OTHER OUTLETS. THIS CIRCUIT MAY SERVE MORE THAN ONE BATHROOM. 14.A 15 AMP BRANCH CIRCUIT SHALL SUPPLY ONLY LIGHTING FIXTURES AND A 20 AMP BRANCH CIRCUIT SHALL BE PERMITTED TO SUPPLY LIGHTING FIXTURES, RECEPTACLES, FIXED APPLIANCES. 15.PROVIDE RECEPTACLE OUTLETS AT EVERY 12' IN LIVING SPACE AND EVERY 4' IN KITCHEN WHERE THERE IS A COUNTER SPACE WIDER THAN 12". 16.TAMPER-RESISTANT RECEPTACLES SHALL BE INSTALLED PER CURRENT CODE. ALL NONLOCKING-TYPE 12-VOLT: 15-AND 20- AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT RECEPTACLES. 17.PROVIDE EXHAUST FAN AND VANITY LIGHTING IN EACH BATHROOM OR A COMBINATION FAN, MIN 50 CFM. EXHAUST FANS SHALL BE ENERGY STAR RATED AND SHALL BE CONTROLLED BY A HUMIDISTAT CAPABLE OF AN ADJUSTMENT BETWEEN 50% AND 80% HUMIDITY. 18.ERODED SEDIMENTS AND POLLUTANTS SHALL BE RETAINED ON SITE AND SHALL NOT BE TRANSPORTED FROM THE SITE VIA SHEET FLOW, SWALES, AREA DRAINS, NATURAL DRAINAGE OR WIND. 19.STOCKPILES OF EARTH AND OTHER CONSTRUCTION-RELATED MATERIALS SHALL BE COVERED AND/OR PROTECTED FROM BEING TRANSPORTED FROM THE SITE BY WIND OR WATER. 20.EXCESS OR WASTE CONCRETE MAY NOT BE WASHED INTO THE PUBLIC WAY OR ANY DRAINAGE SYSTEM. PROVISIONS SHALL BE MADE TO RETAIN CONCRETE WASTE ON-SITE UNTIL IT CAN BE APPROPRIATELY DISPOSED OF OR RECYCLED. 21.TRASH AND CONSTRUCTION RELATED SOLID WASTES MUST BE DEPOSITED INTO A COVERED RECEPTACLE TO PREVENT CONTAMINATION OF STORM WATER AND DISPERSAL BY WIND. 22.SEDIMENTS AND OTHER MATERIALS SHALL NOT BE TRACKED FROM THE SITE BY VEHICLE TRAFFIC. THE CONSTRUCTION ENTRANCE ROADWAYS MUST BE STABILIZED SO AS TO INHIBIT SEDIMENTS FROM BEING DEPOSITED INTO THE STREET/PUBLIC WAYS. ACCIDENTAL DEPOSITIONS MUST BE SWEPT UP IMMEDIATELY AND MAY NOT BE WASHED DOWN Y RAIN OR BY ANY OTHER MEANS. 23.CLEANOUT IS REQUIRED FOR AN ADU BUILDING DRAIN/SEWER. 24.EXISTING LET-IN-BRACING SHALL REMAIN. 25.RANGE EXHAUST FAN FOR STOVE AT KITCHEN TO BE 250 CFM MIN. 26.EXHAUST FAN WITH HUMIDISTAT IN BATHROOM TO BE 50 CFM MIN. SCOPE OF WORK APPLICABLE CURRENT CODES: 2022 CALIFORNIA BUILDING CODE (CBC) 2022 CALIFORNIA MECHANICAL CODE (CMC) 2022 CALIFORNIA PLUMBING CODE (CPC) 2022 CALIFORNIA ELECTRICAL CODE (CEC) 2022 CALIFORNIA ENERGY CODE 2022 CALGREEN BUILDING CODE CITY OF SANTA ANA ORDINANCES 2022 CALIFORNIA RESIDENTIAL CODE (CRC) ORTH 1. Existing unit at rear with 291 square feet, will be converted into a new 2 bedrooms, 1 bath only into 1 Accessory dwelling unit with addition of 494 square feet becoming into a 785 square feet ADU. “Deferred Submittals shall be reviewed by architect or engineer of record prior to submittal to the Building Official”. The reviewed documents shall include a notation indicating, “The deferred submittal documents have been reviewed and found to be in general. 1-800-227-2600 NO WORK SHALL BE DONE ON THIS SITE UNTIL BELOW AGENCY IS NOTIFIED OF INTENTION TO GRADE OR EXCAVATE. TWO WORKING DAYS BEFORE YOU DIG FOOT PRINT FLOOR AREA RATIO CALCULATION WITHOUT 2529/ 5,000= 0.50= 50% OF TOTAL LOT AREA MAIN HOUSE DESCRIPTION EXISTING REMAIN AS IT IS ADDITIONREMODEL TOTAL COVERED PORCH 2,599 (sq ft) 2-CAR GARAGE ------------- 1,280 (sq ft) 464 (sq ft) (E) UNIT CONVERTED TO ADU ------------- Analysis Table ------------- 418 (sq ft) 785 (sq ft) 70 (sq ft)70 (sq ft) -------------494 (sq ft) (E) UNIT CONVERTED TO A PART OF ADU (E) STRUCTURES PER PLAN (N) ADDITION TO ADU New attached Accessory Dwelling Unit MATIAS MIRANDA 406 S Western Ave, Unit #2, Santa Ana, CA 92703 Assessor's Parcel Number (APN) No: 007-223-06 Lot/Parcel Area (Calculated): 6,540 sq ft Site Address: 406 S Western Ave, Unit #2, Santa Ana, CA 92703 Lot: 45 Tract: 2494 Property Type: Single Family Residential # of Stories: 1 Zoning: R-1 Lot Features: - Occupancy: R-3 Type of Construction V-B Fire Sprinklers No (E) Bedrooms / Bathrooms 3/2 (E) Living Area 1,280 s.f. (E) 1-Car Garage 418 s.f. (E) Porch /Covered Patio 70 s.f. Phone# 310-913-6515 -------------------------- ------------- 291 (sq ft) 1,280 (sq ft) 1 SCALE: 1/8"=1'-0" (E) PLOT PLAN (E) SINGLE FAMILY DWELLING 1,280 SQ.FT. N.I.C. (E) 2-CAR GARAGE 418 SQ.FT. N.I.C. (E) UNIT TO CONVERT INTO AN A.D.U. 291SQ.FT. 5'-4" 3' - 1 1 / 2 " 24 ' - 7 " 10 ' - 1 1 " 18 ' - 1 0 " 21 ' - 7 " S Western Ave, Santa Ana, CA GA S WM (E) 3/4" Water meter to remain (E) PORCH 70 SQ.FT. N.I.C. PROPERTY LINE 60.0' PR O P E R T Y L I N E 1 0 9 . 0 ' 60'-0" 10 9 ' - 0 " ELEC. (E) GAS METER PROPERTY LINE 60.0'PR O P E R T Y L I N E 1 0 9 . 0 ' (E) LANDSCAPE 664 SQ.FT. (E ) LA N D S C A P E 13 0 S Q . F T . (E) LANDSCAPE 129 SQ.FT. (E) CONC. DRIVEWAY 1,336 SQ.FT. (E) CONC. SLAB 328 SQ.FT. (E) LANDSCAPE 630 SQ.FT. (E) PAVER 336 SQ.FT. (E) CONC. SLAB 369 SQ.FT. 12 ' - 9 1 / 2 " 17 ' - 2 1 / 2 " 22'-0 1/2"12'-4 1/2" 21 ' - 7 " 18 ' - 1 0 " 35 ' - 6 " 33 ' - 1 1 / 2 " (E) LANDSCAPE 55 SQ.FT. (E) DRIVEWAY APPROACH (E) SIDEWALK (E) PARKWAY (E)1% (E ) 1 % (E ) 1 % (E) 6' BLOCK WALL 25'-7" (E)1% (E) 6' BLOCK WALL (E) 3' BLOCK WALL (E) 6' STEEL CHAIN LINK FENCE (E) 6' STEEL CHAIN LINK FENCE (E ) 1 % (E ) 1 % (E ) 2 % (E ) 2 % (E ) 2 % (E ) 2 % ENGINEER LIC # 4808 Castillo Engineering STRUCTURAL Margarito Castillo S.E. 1147 E Market St Long Beach, CA 90805 562.961.5600 ENERGY 8135 Catalina Ave Whittier, CA 90602 562-698-0818 ENGINEER Nucleus Energy CONDITIONS OF APPROVALS 60'-0" (E) public utility easement (P.U.E.) ELEC. POLE (E) 100 Amp elec. panel 22'-2"19'-11"12'-7" 6'-5 1/2" 10 ' - 1 1 " PARK & RECREATION DEVELOPMENT FEE CALCULATION EXISTING SINGLE-FAMILY RESIDENCE (SFD) LIVING AREA: 1,280 SQ. FT. (MAIN HOUSE – HABITABLE AREA ONLY) PROPOSED ADU LIVING AREA: 785 SQ. FT. (291 SQ. FT. EXISTING LIVING AREA + 494 SQ. FT. ADDITION) ADU TO SFD SQUARE FOOTAGE RATIO: 785 / 1,280 = 0.61 1.ADU sf / SFD sf ratio is for Park & Rec fee purpose only. The applicant is responsible for the given “SFR sf” of the existing primary residence; Building Safety staff are not responsible for the accuracy of the given “SFR sf”. 2.All concealed work installed without permits must be exposed for inspection to the satisfaction of the Building Inspector. This includes methods of attachment and all footings, structural members, mechanical, electrical, plumbing and insulation. 3.Mechanical, electrical and plumbing are not part of this plan review and approval. MEP are subject to building field inspection. 4.Utilities will be undergrounded per SAMC 41-626 GENERAL NOTES PL PL PL PL PL 5'-4" PL = PROPERTY LINE OR T H NS W E OF SHEET NO. DATE ISSUED DRAWN BY CHECKED BY SCALE PRINT:REVISION: SH E E T N A M E : THESE DRAWINGS, DESIGN AND SPECIFICATIONS ARE THE PROPERTY AND COPY RIGHT OF YOLANDA CASTRO AND/OR C+P DESIGN CONSTULTANTS AND SHALL NOT BE USED ON ANY OTHER WORK EXCEPT BY AGREEMENT WITH YOLANDA CASTRO. WRITTEN DIMENSIONS SHALL TAKE REFERENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED ON THE JOB SITE, ANY DISCREPANCY SHALL BE BROUGHT TO THE NOTICE OF YOLANDA CASTRO TO THE COMMENCEMENT OF ANY WORK PR O J E C T : OW N E R : AD D R E S S : Y.C. C+P 25 C P 0 0 6 1 AS SHOWN 5/3/2025 STAMP APPROVAL 11-05-2025 A. P . N . 40 6 S W e s t e r n A v e , U n i t # 2 S a n t a A n a , C A 9 2 7 0 3 NE W A C C E S S O R Y D W E L L I N G U N I T Ma t i a s M i r a n d a 00 7 - 2 2 3 - 0 6 12-22-2025 2 01-20-2026 02/27/2026 00-C1 CO V E R S H E E T , PR O J E C T I N F O R M A T I O N & (E ) P L O T P L A N SCOPE OF WORK (E) STRUCTURES PER PLAN (N) ADU 1 SCALE: 1/8"=1'-0" (N) PLOT PLAN (E) SINGLE FAMILY DWELLING 1,280 SQ.FT. N.I.C. (E) 2-CAR GARAGE 418 SQ.FT. N.I.C. (N) ADDITION TO CONVERT INTO AND A.D.U. 494 SQ.FT. (E) UNIT TO CONVERT INTO AN A.D.U. 291SQ.FT. (N)ACCESSORY DWELLING UNIT 785 SQ.FT. 5'-4" 3' - 1 1 / 2 " 24 ' - 7 " 10 ' - 1 1 " 18 ' - 1 0 " 21 ' - 7 " S Western Ave, Santa Ana, CA GA S WM (E) 3/4" Water meter to remain (E) PORCH 70 SQ.FT. N.I.C. PROPERTY LINE 60.0' PR O P E R T Y L I N E 1 0 9 . 0 ' 60'-0" 10 9 ' - 0 " ELEC. (E) Gas meter PR O P E R T Y L I N E 1 0 9 . 0 ' (E) LANDSCAPE 664 SQ.FT. (E ) LA N D S C A P E 13 0 S Q . F T . (E) LANDSCAPE 129 SQ.FT. (E) CONC. DRIVEWAY 1,336 SQ.FT. (E) CONC. SLAB 328 SQ.FT. (E) LANDSCAPE 630 SQ.FT. (E) PAVER 336 SQ.FT. (E) CONC. SLAB 369 SQ.FT. 12 ' - 9 1 / 2 " 6' - 1 1 " 10 ' - 3 1 / 2 " 6'-4"27'-2"14'-1 1/2"12'-4 1/2" 21 ' - 7 " 18 ' - 1 0 " 35 ' - 6 " 22 ' - 1 0 " 10 ' - 3 1 / 2 " (E) LANDSCAPE 55 SQ.FT. (E) DRIVEWAY APPROACH (E) SIDEWALK (E) PARKWAY (N)5% (N)5% (N)2% (N)5% (N)2% (E ) 5 % (E ) 5 % (E ) 5 % (E)1% (E ) 1 % (E ) 1 % (E) 6' BLOCK WALL (E) 6' BLOCK WALL (E) 3' BLOCK WALL (E) 6' STEEL CHAIN LINK FENCE (E ) 1 % (E ) 1 % (E ) 2 % (E ) 2 % (E ) 2 % (E ) 1 % 2% (N) tankless W/H (E) public utility easement (P.U.E.) ELEC. POLE (N) minisplit Fujitsu AOU24RLXFZ over evel concrete pad extending not less than 3 inches above the adjoining ground. [CMC 1105.2]. (E) 100 Amp elec. panel 3'-0" 4' - 0 " utilities will be undergrounded per SAMC 41-626 22'-2"19'-11"12'-7" 6'-5 1/2" 10 ' - 1 1 " PROPERTY LINE 60.0'PL PL PL PL PL 4'-4" 5'-4" eave dist. 9' - 3 1 / 2 " ea v e d i s t a n c e 1'-0" 11'-7" eave distance 1'-0" (E) UNIT CONVERTED TO A PART OF ADU (E) STRUCTURES PER PLAN (N) ADDITION TO ADU = PROPERTY LINEPL OR T H NS W E 1 Future HPWH ready space (see detail HP/01-A1.1) OF SHEET NO. DATE ISSUED DRAWN BY CHECKED BY SCALE PRINT:REVISION: SH E E T N A M E : THESE DRAWINGS, DESIGN AND SPECIFICATIONS ARE THE PROPERTY AND COPY RIGHT OF YOLANDA CASTRO AND/OR C+P DESIGN CONSTULTANTS AND SHALL NOT BE USED ON ANY OTHER WORK EXCEPT BY AGREEMENT WITH YOLANDA CASTRO. WRITTEN DIMENSIONS SHALL TAKE REFERENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED ON THE JOB SITE, ANY DISCREPANCY SHALL BE BROUGHT TO THE NOTICE OF YOLANDA CASTRO TO THE COMMENCEMENT OF ANY WORK PR O J E C T : OW N E R : AD D R E S S : Y.C. C+P 25 C P 0 0 6 1 AS SHOWN 5/3/2025 STAMP APPROVAL 11-05-2025 A. P . N . 40 6 S W e s t e r n A v e , U n i t # 2 S a n t a A n a , C A 9 2 7 0 3 NE W A C C E S S O R Y D W E L L I N G U N I T Ma t i a s M i r a n d a 00 7 - 2 2 3 - 0 6 12-22-2025 2 01-20-2026 02/27/2026 01-A1.0 (N ) P L O T P L A N SYM.WIDTH TYPE MANU.MATERIAL 1 S.C.3'-0"1 3 4" 2 3 THICKNESS H.C. 6'-8" HEIGHT 6'-8" DOOR SCHEDULE WOOD QTY. 1 3 8" 6'-8" 4 6'-8" 5 6'-0"6'-8" S.C.-SOLID CORE H.C.-HOLLOW CORE F.R.-FRENCH DOOR F.L.-FOLDING DOOR S.L.-SLIDING DOOR P.O.-POCKET DOOR 1 1 1 2 4 2'-6"H.C.WOOD 1 3 8" WOODCLOSET TYPE MANU.GLAZING REMARKS 1 VINYL SL5'-0" WINDOW SCHEDULE 3 CLEARS.L. 4 VINYL SLS.L. U-FACTOR1 SHGC2 1 BTU/H FT2.*F 2 SOLAR HEAT GAIN COEFFICIENT WIDTH HEIGHT 4'-0" SYM. SIZE 2'-0"2'-0" QTY. 2 1 VINYL SLS.L.2'-0"4'-0" 2 VINYL SL4'-0"CLEARS.L.4'-0"1 DUAL GLAZED 5 VINYL SLS.L.5'-0"4'-0"2 GLAZING @ WINDOWS 1. ALL NEW WINDOWS SHALL BE DUAL GLAZED & 1-PANE TEMPERED. 2. THE LOAD RESISTANCE OF GLASS UNDER UNIFORM LOAD SHALL BE DETERMINED IN ACCORDANCE WITH ASTM E1300. DUAL GLAZED (E) 1 CLEAR DUAL GLAZED CLEAR CLEAR DUAL GLAZED DUAL GLAZED S.L. d) FIBERGLASS SHOWER c) ON-SITE BUILT-UP SHOWERb) SHOWER ENCLOSUREa) SHOWER ENCLOSUR (PLAN VIEW) e) BASE FOR TILE SHOWER CONSTRUCTION 1.19 0.23 0.30 0.23 S.L. (N) FLOOR PLAN2SCALE: 3/16"=1'-0" OR T H NS W A.D.U. 0.30 0.23 0.30 0.23 0.30 0.23 4'-0" 2'-8" PATIO WOOD/ TEMP. GLASS 11'-3" 11 ' - 0 " 11 ' - 0 " W/ D KING 76X80" 3' - 0 " 7' - 7 " TWIN 39X80TWIN 39X80 6'-0"3' - 0 " 21'-0" 11 ' - 1 1 1 / 2 " 3' - 2 " 3'-6" 3' - 0 " (E) KITCHEN Ch=8'-0" (E) LIVING AREA Ch=8'-0" (N) BEDROOM #1 h=8'-0" (N) BEDROOM #2 Ch=8'-0" (N) HALLWAY h=8'-0" (N) BATH ch=8'-0" shower closet closet (N) DEN Ch=8'-0" (E) BREEZEWAY (E) wall to be converted into 1-hr fire rated wall (separation garage-home) to remain (E) wall to be demolished for (N) 5x4 window (E) wall to be demolished (E) wall to be demolished (E) BEDROOM #3 Ch=8'-0' (E) BATH Ch=8'-0' (E) BATH Ch=8'-0' (E) KITCHEN Ch=8'-0' (E) BEDROOM #2 Ch=8'-0' (E) BEDROOM #1 Ch=8'-0' (E) LIVING ROOM Ch=8'-0' (E) LIVING ROOM Ch=8'-0' (E) 2-CAR GARAGE Ch=varies (E) wall to be partial demolished and remove window for a (N) entrance door 18 ' - 5 " (E) BREEZEWAY 3' - 1 0 " 2' - 0 " 5' - 5 " 3' - 1 1 " 2' - 0 " 5' - 5 " 2' - 1 0 " 3' - 0 " 2' - 0 " 5' - 5 " 11 ' - 4 " 11 ' - 4 " 13 ' - 3 " 8'-1"3'-0"11'-1"6'-11"4'-7"2'-5"2'-0"4'-0" 11'-7"8'-8"4'-4"1'-6"2'-2"1'-6"1'-9"2'-10"1'-0"1'-6"5'-4" 11 " 8' - 0 " 9' - 6 " 11 ' - 4 " 2' - 0 " 2' - 0 " 10 ' - 2 " 2' - 6 " 7' - 1 1 " 3' - 2 " 5' - 3 " 2' - 0 " 5' - 6 " 1 233 5 5 4 2 3 4 4 5 5 1 EXISTING WALLS TO BE DEMOLISHED EXISTING WINDOW TO BE REPLACED AND/OR REMOVED EXISTING DOOR TO BE REPLACED AND/OR REMOVED (E) 2X4 STUD WALL - TO 1 HR FIRE RATED (E) & (N) FLOOR PLAN LEGEND EXISTING 2X4 STUD WALL NEW 2X4 STUD WALL ATTIC ACCESS 30"x30" w/min 30" head-room W/APPROVED GASKET AT PERIMETER OF ACCESS OPENING (N) 2X4 STUD WALL - 1 HR FIRE RATED NEW 2X6 STUD WALL - WET WALL INTERCONNECTED HARD-WIRED CARBON MONOXIDE ALARM WITH BATTERY BACKUP OUTSIDE OF EACH BEDROOM, AND OCCUPIABLE LEVEL IF DWELLING UNIT. (R315) INTERCONNECTED HARD-WIRED “SMOKE ALARM” WITH BATTERY BACKUP IN EACH SLEEPING ROOM, IMMEDIATE VICINITY OF THE BEDROOMS, EACH ADDITIONAL STORY OF DWELLING, AND NOT LESS THAN 3-FT FROM THE BATHROOM THAT CONTAINS BATHTUB OR SHOWER. (R314) SD 1'-6"1'-0"8'-8"1'-0"1'-3"2'-11"2'-1 1/2"2'-0"6'-8 1/2" 6' - 2 " 2' - 0 " 3' - 3 " 3' - 5 " 2' - 6 " 5' - 1 1 " 3"2'-0"3'-10"2'-6"5'-4" 7" 1' - 0 " 1' - 7 " 1' - 1 1 " 6" 7' - 4 " 11'-8"2'-3"5'-4"3'-5"18'-5" 41'-1" 23 ' - 3 " 70 ' - 3 " 15 ' - 1 1 " 42'-1" E (E) FLOOR PLAN1SCALE: 3/16"=1'-0" OR T H NS W A.D.U. E WOOD/ TEMP. GLASS 1 3 4" 1 3 8" 1 2" MAX. AT 1:2 SLOPE 2 1 14" MAX. DOOR 7 3 4" MAX NOTES: 1.A MIN OF 1" IF SPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING AND THE LOCATION OF VENTS (CRC R806.3) 2.WALL COVERINGS IN SHOWERS AND TUBS WITH SHOWERHEADS SHALL BE CEMENT PLASTER , TILE, OR EQUAL TO 6 FEET (72") ABOVE DRAIN. ENCLOSURES MUST BE OF APPROVED SAFETY GLAZING AND DOORS (22” MIN. WIDTH) MUST SWING OUT OF SHOWERS. 3.WINDOWS IN ENCLOSURE WALLS SHALL BE LABELED SAFETY GLAZING WHEN LESS THAN 60" ABOVE THE DRAIN.” CRC R307.2. 4.GLAZING IN ENCLOSURE FOR OR WALLS FACING HOT TUBS, BATHTUBS, SHOWERS, WHIRL-POOLS, SAUNAS, STEAM ROOMS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS THAN 60” ABOVE THE ANY STANDING SURFACE AGING IN PLACE/FALL PREVENTION NOTES: W A-3 E A-3 N A-3 S A-3 4" CLOTHES DRYER MOISTURE EXHAUST DUCT TO ROOF W/BACK-DRAFT DAMPER island (N) minisplit Fujitsu AOU24RLXFZ over level concrete pad extending not less than 3 inches above the adjoining ground. [CMC 1105.2]. (E) Wall to be converted 1-hr fire rated for units separation with 5 8" type "X" Gyp. Bd. see detail B /01-A1.3 RIDGID PIPE NOT TO EXCEED 2" THROUGH DRYER BOX SEE DETAIL DRYERBOX DRYERBOX DETAIL FLEX TRANSITION HOSE 2" NOTE: DRYERBOX MODEL 425 CAN BE MOUNTED UPSIDE DOWN FOR THROUGH FLOOR VENTING APPLICATIONS BOTTOM OF DRYERBOX SHOULD BE 4 1/2" ABOVE CENTER OF DRYER EXHAUST Model 466 Dryerjack (Optional) www.dyerjack.com 1'-218" DRYER BOX MODEL 425 TO ROOF JACK @ 2X6 WALL The clothes dryer exhaust duct shall be a minimum 4-inch diameter, be made of rigid metal, have a smooth interior surface, vent to outside air (at least 3 ft away from any building opening), and have a maximum duct length of 14 feet. The maximum duct length includes two 90-degree elbows. [CMC 504.4] NOTES FOR FUTURE ELEC. APPLIANCES Cooktop is proposed as gas or propane: A dedicated 240-volt branch circuit wiring shall be installed within 3 feet from the cooktop and accessible to the cooktop with no obstructions. The branch circuit conductors shall be rated at 50 amps minimum. The blank cover shall be identified as "240V ready." All electrical components shall be installed in accordance with the California Electrical Code. The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a future electric cooktop installation. The reserved space shall be permanently marked as "For Future 240V use." Clothes dryer is proposed as gas or propane: A dedicated 240-volt branch circuit wiring shall be installed within 3 feet from the clothes dryer location and accessible to the clothes dryer location with no obstructions. The branch circuit conductors shall be rated at 30 amps minimum. The blank cover shall be identified as "240V ready." All electrical components shall be installed in accordance with the California Electrical Code. The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a future electric clothes dryer installation. The reserved space shall be permanently marked as "For Future 240V use." 60 CMF MIN. EXHAUST FAN SHALL BE ENERGY STAR RATED, EXHAUSTED DIRECTLY TO OUTSIDE, W/ HUMIDITY SENSOR CONTROL 3'-0" 4' - 0 " 1' - 6 " 2' - 0 " 6' - 5 1 / 2 " 3' - 1 1 / 2 " ELEC. ELEC. (E) 100 AMP ELEC. PANEL (E) 100 AMP ELEC. PANEL BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED WITH MECHANICAL VENTILATION CAPABLE OF 60 CFM EXHAUSTED DIRECTLY TO THE OUTSIDE (R303.3) 280 CFM MIN, CHANGE EXHAUST FAN (RANGE HOOD) EXHAUSTED DIRECTLY TO THE OUTSIDE 1.TWO LAYERS OF GRADE D PAPER SHALL BE INSTALLED OVER WOOD BASE SHEATHING (CBC 2506.4) 2.WEEP SCREED FOR STUCCO AT THE FOUNDATION PLATE LINE A MINIMUM OF 4 INCHES ABOVE EARTH OR 2 INCHES ABOVE PAVED AREAS. (CBC 2512.1.2) 3.EXTERIOR WALL COVERING OVER WEATHER-RESISTIVE BARRIER. CBC 1403.2 @ 16" O.C R-15 INSUL. 1/2" DRYWALL 2X SILL PLATE & FRAM. SCHEDULE WALL ASSEMBLY DETAIL PLWD. SHEAR PANEL SEE FRAM. PLAN & SCHEDULE GRADE "D" BUILD. PAPER (2) LAYERS 16 GA. WIRE LATH 2x4 STUDS SEE SHEARWALL CONC. FTG.5/8" A.B 7/8" EXT. PLASTER 26 GA. STUCCO WEEP SCREED WITH MINIMUM 3-1/2” TALL ATTACHMENT FLANGE PLACED AT OR BELOW THE SILL/CONCRETE INTERFACE 4" MIN. above NG 2" MIN. above FS 8" MIN. above NG 6" MIN. above FS THRESHOLD DETAIL CM SDCM SD SD 280 CMF MIN. EXHAUST FAN SHALL BE ENERGY STAR RATED, EXHAUSTED DIRECTLY TO OUTSIDE (N) ADU TANKLESS WH 24" CLEAR 2' - 6 " 30 " C L E A R 15 " M I N . 30"MIN. CLEAR te m p e r e d tempered tempered 36x37.5 TH - A' 1/01-A1.3 A 1/01-A1.3 1.SMOKE ALARM a.shall be interconnected hard-wired with battery backup and shall be installed in accordance with NFPA 72. b.smoke alarms placed within 20 feet of a permanently installed cooking appliance shall be an ionization or photoelectric type and shall not be within 10 feet of the appliance. 2.CARBON MONOXIDE ALARM a.shall be interconnected hard-wired with battery backup. b.shall be physically or wirelessly interconnected in such a manner that the activation of one alarm shall activate all the alarms. CRC R315.5] FIRE PROTECTION NOTES FUTURE HPWH READY SPACE (see detail HP/-) HEAT PUMP WATER HEATER DETAIL TH WALL ASSEMBLY DETAIL HP a. Water closet – 1.28 gallon per flush b. Shower head – 1.8 gallons per minute at 80 psi. c. Lavatory faucets – 1.2 gallon per minute at 60 psi. d. Kitchen faucet – 1.8 gallon per minute at 60 psi. PLUMBING FIXTURES FLOW RATE LIMITATION (SECTION 4.303) OF SHEET NO. DATE ISSUED DRAWN BY CHECKED BY SCALE PRINT:REVISION: SH E E T N A M E : THESE DRAWINGS, DESIGN AND SPECIFICATIONS ARE THE PROPERTY AND COPY RIGHT OF YOLANDA CASTRO AND/OR C+P DESIGN CONSTULTANTS AND SHALL NOT BE USED ON ANY OTHER WORK EXCEPT BY AGREEMENT WITH YOLANDA CASTRO. WRITTEN DIMENSIONS SHALL TAKE REFERENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED ON THE JOB SITE, ANY DISCREPANCY SHALL BE BROUGHT TO THE NOTICE OF YOLANDA CASTRO TO THE COMMENCEMENT OF ANY WORK PR O J E C T : OW N E R : AD D R E S S : Y.C. C+P 25 C P 0 0 6 1 AS SHOWN 5/3/2025 STAMP APPROVAL 11-05-2025 A. P . N . 40 6 S W e s t e r n A v e , U n i t # 2 S a n t a A n a , C A 9 2 7 0 3 NE W A C C E S S O R Y D W E L L I N G U N I T Ma t i a s M i r a n d a 00 7 - 2 2 3 - 0 6 12-22-2025 2 01-20-2026 02/27/2026 01-A1.1 (E ) F L O O R P L A N W I T H DE M O L I T I O N & ( N ) A D U FL O O R P L A N (N ) 4 : 1 2 (N) RIDGE (N ) 4 : 1 2 (E ) 4 : 1 2 (E) RIDGE (E ) 4 : 1 2 1'-0" 1'-0" 1' - 0 " 22 ' - 1 0 " (N)4:12 (N)4:12 (N ) 4 : 1 2 (N)4:12 (E)4:12 (E)4:12 (E ) 4 : 1 2 (E ) 4 : 1 2 (E ) 4 : 1 2 (E)4:12 NOTES: 1. INSTALL VENTS SO AS TO PROVIDE PROPER CROSS VENTILATION. 2. A) VENTILATION OPENINGS SHALL HAVE A LEAST DIMENSION OF 116" MIN. AND 14" MAX. AND PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL. B) TILE ROOFING SHALL BE INSTALLED PER THE PROVISIONS OF SECTION R905.3 AND LISTED & TESTED AS A CLASS "A" ROOFING IN ACCORDANCE WITH UL 790 OR ASTM E108. 3. a. IF SPACES ARE CREATED BETWEEN THE ROOF COVERING (MAINLY TILES) AND THE COMBUSTIBLE ROOF DECKING (SHEATHING), THEN THE SPACES SHALL BE EITHER: III. PROVIDE ONE LAYER OF NO. 72 MINERAL-SURFACE NONPERFORMANCE CAP SHEET MEETING ASTM D3909 b. VALLEY FLASHING SHALL BE NOT LESS THAN 0.019-INCH (NO. 26 GALVANIZED SHEET GAGC) CORROSION- RESISTANT METAL INSTALLED OVER A 36-IN. WIDE UNDERLAYMENT CONSISTING OF ONE LAYER OF NO. 72 CAP SHEET RUNNING THE FULL LENGTH OF THE VALLEY. ATTIC VENTILATION REQUIRED 1/150 OF ATTIC AREA (785/150) 785 SQ.FT. 5.23 SQ.FT. / NFA 5.23X144 754 SQ.IN. / NFA ATTIC AREA 432 SQ.IN / NFAPROVIDE 6 VENTS 792 SQ.IN / NFATOTAL VENTILATION PROVIDED (EXHAUST & INTAKE) REQUIRED INTAKE 72 SQ.IN / NFA PROVIDE 5 VENTS 360 SQ.IN / NFA 377/72 SQ.IN / NFA O'hagin standard* composition shingle, slate & shake (natural/synthetic) 72 SQ.IN / NFAO'hagin standard* composition shingle, slate & shake (natural/synthetic) 12'-11"1'-0"1'-0"27'-2" 1' - 0 " 54 ' - 4 " 1' - 0 " 1'-0"22'-2"1'-0" 1' - 0 " 28 ' - 9 " 1' - 0 " 24 ' - 7 " 1' - 0 " 1' - 1 1 / 2 " 1' - 0 " 12 ' - 9 1 / 2 " 1' - 0 " (N) ROOF PLAN1SCALE: 3/16"=1'-0" OR T H NS W E 377/72 SQ.IN / NFA O'hagin standard* composition shingle, slate & shake (natural/synthetic)O'hagin standard* composition shingle, slate & shake (natural/synthetic) RIGID INSULATION - "PROVIDE R30-VALUE/DEPTH PER CLIMATE ATTIC INSULATION SITE BUILT ATTIC ENCLOSURE - MECHANICALLY SECURED SEAL AT WEATHERSTRIPPING MECHANICAL LATCH TO PRESSURE WHOLE HOUSE FAN A.ALL CONTINUOUSLY OPERATING FANS SHALL BE RATED AT A MAXIMUM OF 1.0 SONE. B.EXHAUST FAN WILL BE CONTROLLED BY A STANDARD ON/OF SWITCH BUT SWITCH MUST BE LABELED TO INFORM THE OCCUPANT THAT EXHAUST FAN IS THE WHOLE-BUILDING VENTILATION. LABEL NEEDS TO MAKE CLEAR WHAT THE CONTROL IS FOR AND THE IMPORTANCE OF OPERATING THE SYSTEM. THIS MAY BE AS SIMPLE AS "VENTILATION CONTROL" OR MIGHT INCLUDE WORDING SUCH AS: "OPERATE WHEN THE HOUSE IS IN USE" OR "KEEP ON EXCEPT WHEN GONE OVER 7 DAYS" OR "FAN IS TO BE LEFT ON TO ENSURE INDOOR AIR QUALITY" C.EXHAUST FANS SHALL BE SWITCHED SEPARATELY FROM LIGTHLING SYSTEM [150.0(k)2B] WHOLE HOUSE FAN 1 1 WALL SWITCH SINGLE POLE WALL POLE SWITCHS 3S WALL SWITCH 3-WAY DS WALL SWITCH W/DIMMER DUPLEX 110 V RECEPTACLE OUTLET ARC FAULT CIRCUIT INTERUPTER FLUORESCENT LIGHTF RECESSED LIGHT FIXTURE LIGHT SYMBOLS SMOKE DETECTORS EXHAUST FANS WEATHERPROOF SWITCH SINGLE POLEWPS WEATHERPROF DUPLEXWP GFI OUTDOOR WALL HUNG LIGHT FIXTURE MOTION (SENSOR WITH PHOTO) CONTROL U.N.O. F MS WALL SWITCH SENSOR WITH PHOTO GROUND FAULT INTERRUPTER (1) 20 AMP. DEDICATED OWN CIR. BREAKER CABLE TELEVISION HOOK-UP. TELEPHONE HOOK-UP JACK. RECESSED CAN LIGHT FIXTURE (FLUORESCENT).F SPECIALTY LIGHT (IE STRIP LIGHTING OVER VANITY). 2-TUBE X 4'-0" FLUORESCENT SURFACE LIGHT FIXTURE. 60" ABV. FINISH FLR. COMBINATION LIGHT/FAN (FLUORESCENT). VSS WALL SWITCH W/VACANT SENSOR NOTES: 1.ALL PERMANENTLY INSTALLED OUTDOOR LIGHTING MUST BE HIGH EFFICACY AND MUST BE CONTROLLED BY A MANUAL ON AND OFF SWITCH AND USE ONE OF THESE AUTOMATIC CONTROL TYPES AS PER CALIFORNIA ENERGY CODE 150.0(K)3 AND TABLE 150.0-A A). PHOTOCONTROL AND MOTION SENSOR, OR B). PHOTOCONTROL AND AUTOMATIC TIME SWITCH CONTROL, OR C). ASTRONOMICAL TIME CLOCK THAT AUTOMATICALLY TURN OUTDOOR LIGHTING OFF DURING DAYLIGHT HOURS , OR ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) THAT PROVIDES THE FUNCTIONALLY OF AN ASTRONOMICAL TIME CLOCK. EMCS DOES NOT HAVE AN OVERRIDE OR BYPASS THAT ALLOWS THE LUMINARIES TO ALWAYS ON AND IS PROGRAMMED TO AUTOMATICALLY TURN THE OUTDOOR LIGHTING OFF DURING DAYLIGHT HOURS . 2.RECESSED DOWNLIGHT LUMINAIRES IN CEILING, FOR INSTANCE, PIN-BASED CFLS MUST BE JA8 CERTIFIED TO BE INSTALLED IN CEILING RECESSED DOWNLIGHTS. ALL CEILING RECESSED DOWNLIGHTS AND ENCLOSED LUMINARIES MUST BE CONTROLLED BY A DIMMER OR VACANCY SENSOR AS PER CALIFORNIA ENERGY CODE 150.0(K)(C). 3.NEW RECEPTACLES SHALL BE TAMPER PROOF 280 CFM MIN, CHANGE EXHAUST FAN (RANGE HOOD) 1.785SF x 3 WATTS 2.5 x 1,500 WATTS APPLIANCES 3.ADDITIONAL APPLIANCES 4.LAUNDRY CIRCUIT 5.SUBTOTAL 6.1ST 3,000 WATTS @100% DIFFERENCE 7. BALANCE @35% =11,355 x 0.35 8.DRYER - 1 TOTAL 9.AC LOAD 5,000 10.APPLIANCES IN PLACE A.WATER HEATER B.MICROWAVE C.DISHWASHER D.CLOTHES WASHER E.GARBAGE DISPOSAL F.KITCHEN OVEN G.EV CHARGING STATION 11.TOTAL APPLIANCES IN PLACE 12.75% OF 14,574= 14,574x 0.75 13.TOTAL NUMBER OF WATTS TOTAL LOAD / 240V =10930/ 240= 46AMP SERVICE AMPS= 2,355 7,500 3,000 1,500 =14,355 -3,000 =11,355 =3,974 3,000 5,000 3,600 3,000 2,500 800 700 10,600 10,930 55.61 CONCEPT WATTS USE 125 AMP ELECTRICAL PANEL SIZE AFCI ROPE LIGHTING LANDSCAPING FLOOR LAMP SPOT LIGHT WHOLE HOUSE EXHAUST FAN CLOTHES DRYER MOISTURE EXHAUST DUCT MUST BE 4-IN. IN DIAMETER AND LENGTH IS LIMITED TO 14-FT. WITH 2 ELBOWS. THE DUCT LENGTH SHALL BE REDUCED BY 2-FT. FOR EVERY ELBOW IN EXCESS OF TWO. (MC 504.4.2) PROVIDE J-BOX. PUSH BUTTON. HOSE BIBB GFI RECEPTACLE OUTLET MAX (6 1 2 FT) ABOVE GRADE LEVEL WITH WEATHERPROOF CASING FLOOR OUTLET CLOTHES WASHER 220 VOLT DISHWASHER CW DW (N) SCHEMATIC ELEC. PLAN2SCALE: 3/16"=1'-0" OR T H NS W E F F F F F F F F F F F F F F F F F F FFF F F D S S S DS D DSS DS DS D S S D DS F F DS DS MSDS DS DSDS DS S D F DS S V S S SD S D MS S M M S CW DW 4" CLOTHES DRYER MOISTURE EXHAUST DUCT TO ROOF W/BACK-DRAFT DAMPER +15" WP GFI +48" WP GFI +60" WP GFI AF C I WP GFI +42 WP GFI +42 WP GFI +34 WP GFI +34 +60" TV AF C I AF C I +60" TV OWNER DECIDES TO UPGRADE TO 200 AMPS ELECTRICAL PANEL IF NOT USE 125 AMP ELEC PANEL (E) KITCHEN Ch=8'-0" (E) LIVING AREA Ch=8'-0" (N) BEDROOM #1 h=8'-0" (N) BEDROOM #2 Ch=8'-0" (N) HALLWAY h=8'-0" (N) BATH ch=8'-0" shower closet closet (N) DEN Ch=8'-0" (E) BREEZEWAY SDCM SD SD INTERCONNECTED HARD-WIRED CARBON MONOXIDE ALARM WITH BATTERY BACKUP OUTSIDE OF EACH BEDROOM, AND OCCUPIABLE LEVEL IF DWELLING UNIT. (R315) INTERCONNECTED HARD-WIRED “SMOKE ALARM” WITH BATTERY BACKUP IN EACH SLEEPING ROOM, IMMEDIATE VICINITY OF THE BEDROOMS, EACH ADDITIONAL STORY OF DWELLING, AND NOT LESS THAN 3-FT FROM THE BATHROOM THAT CONTAINS BATHTUB OR SHOWER. (R314) SD MECHANICAL VENTILATION CAPABLE OF 60 CFM EXHAUSTED DIRECTLY TO THE OUTSIDE (R303.3) WITH HUMIDITY SENSOR CM 60 CMF MIN. EXHAUST FAN SHALL BE ENERGY STAR RATED, EXHAUSTED DIRECTLY TO OUTSIDE, W/ HUMIDITY CONTROL 280 CMF MIN. EXHAUST FAN SHALL BE ENERGY STAR RATED, EXHAUSTED DIRECTLY TO OUTSIDE OF SHEET NO. DATE ISSUED DRAWN BY CHECKED BY SCALE PRINT:REVISION: SH E E T N A M E : THESE DRAWINGS, DESIGN AND SPECIFICATIONS ARE THE PROPERTY AND COPY RIGHT OF YOLANDA CASTRO AND/OR C+P DESIGN CONSTULTANTS AND SHALL NOT BE USED ON ANY OTHER WORK EXCEPT BY AGREEMENT WITH YOLANDA CASTRO. WRITTEN DIMENSIONS SHALL TAKE REFERENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED ON THE JOB SITE, ANY DISCREPANCY SHALL BE BROUGHT TO THE NOTICE OF YOLANDA CASTRO TO THE COMMENCEMENT OF ANY WORK PR O J E C T : OW N E R : AD D R E S S : Y.C. C+P 25 C P 0 0 6 1 AS SHOWN 5/3/2025 STAMP APPROVAL 11-05-2025 A. P . N . 40 6 S W e s t e r n A v e , U n i t # 2 S a n t a A n a , C A 9 2 7 0 3 NE W A C C E S S O R Y D W E L L I N G U N I T Ma t i a s M i r a n d a 00 7 - 2 2 3 - 0 6 12-22-2025 2 01-20-2026 02/27/2026 01-A1.2 RO O F P L A N & S C H E M A T I C EL E C . P L A N WEST ELEVATIONWSCALE: 3/16"=1'-0" FRONT VIEW NORTH ELEVATIONNSCALE: 3/16"=1'-0" LEFT SIDE VIEW SOUTH ELEVATIONSSCALE: 3/16"=1'-0" RIGHT SIDE VIEW EAST ELEVATIONESCALE: 3/16"=1'-0" FRONT VIEW 9 (N) 5 8" TYPE X GYPSUM BOARD (E ) L I V I N G A R E A (N ) A . D . U . L I V I N G A R E A 4" CONC. SLAB (E)2X4 STUDS @16" or 24" oc Location: Between units Fire rating: 1 hr (N)R-15 MINERAL WOOL INSULATION (FULL HEIGHT) CEILING HT. (N)CEILING HT. B ELEVATION KEY NOTES CRICKET (E) WINDOW 3 6 12 (N) 7 8" THICK STUCCO (EXTERIOR FINISH) 2-LAYERS OF GRADE "D" PAPER, PAINTED WITH EVERSHIELD Exterior Flat Paint, Icy White DEHW 10 OR SIMILAR 2 1 (E) ROOF CLASS A 4:12 ASPHALT SHINGLE OVER (N) DOOR (ALL EXTERIOR DOORS ARE SOLID CORE) 5 (N) CLEAR GLASS WINDOW 7 (N)TEMPERED GLASS 9 (E) STUCCO (EXTERIOR FINISH) 13 (N) RED BRICK SIDING, MATCH TO EXISTING 14 (N) FROSTY TEMPERED GLASS WINDOW 8 (N) ROOF CLASS A 4:12 ASPHALT SHINGLE OVER 2-15#FELT. ICC ESR #1475 15/32" OSB W/RADIANT BARRIER OR CDX PLYWD. USE GAF - Timberline Cool Series - Weathered Roof CRRC Product ID# 0676-0042 Solar Reflectance : Initial = 0.28 3 year = 0.27 Thermal Emittance: Initial = 0.92 3 year = 0.90 SRI: Initial = 30 3 year = 28 ASTM D3161 Class F (110 mph) and ASTM D7158 Class H (150 mph) BUILDING ADDRESS. MUST BE A MINIMUM OF 4" TALL WITH EACH STROKE A MINIMUM OF 1/2" WIDE. NUMBERS ARE REQUIRED TO BE ON A BACKGROUND OF A CONTRASTING COLOR. 15 15 16 1 99 15 1 8" 6' - 8 " 1' - 4 " 8" 1 1 1 2 1 23 4 ADDRESS 8" 6' - 8 " 1' - 4 " 8" 8" 6' - 8 " 1' - 4 " 8" 8" 6' - 8 " 1' - 4 " 8" 1 1 1 3 2 2 4 4 5 5 5 5 5 5 5 5 10 (E) RED BRICK SIDING (EXTERIOR FINISH) 10 10 6 66 6 6 6 8 8 8 8 (E) FENCE (SEE PLOT PLAN FOR SPECS) 14 16 (E) PREMANUFACTURED BY OWNER METAL DOOR 16 13 13 12 12 12 9 9 9 9 9 9 9 12 ' - 1 1 " 11 ' - 4 " 13 ' - 3 1 / 2 " 13 ' - 3 1 / 2 " 12 ' - 1 1 " 1515 FIRE BLOCKING AT TOP PLATE FIRE RESISTIVE SEALANT AT FLOOR LINE (N) 7/8" 25 GA RESILIENT CHANNEL @ 24" O.C. MAX INSTALLED PER GA-216 tempered tempered tempered tempered 1 1 / 2 " 6' - 8 " 8' - 0 " CROSS SECTION A-A'1 SCALE: 3/16"=1'-0" STONE VENEER OR BRICK DETAIL (N) 5 8" TYPE X GYPSUM BOARD 1.ALL PENETRATIONS SHALL BE SEALED WITH APPROVED ACOUSTICAL SEALANT. 2.NO BACK-TO-BACK ELECTRICAL BOXES PERMITTED. 1 HR WOOD STUD FIRE PARTITION GA FILE NO. WP 3655 WITH RESILIENT CHANNEL (ENHANCED SOUND CONTROL) FIRE RESISTIVE SEALANT AT FLOOR LINE CONTINUOS CAULK BLOCKING BOTH SIDES 2 OF SHEET NO. DATE ISSUED DRAWN BY CHECKED BY SCALE PRINT:REVISION: SH E E T N A M E : THESE DRAWINGS, DESIGN AND SPECIFICATIONS ARE THE PROPERTY AND COPY RIGHT OF YOLANDA CASTRO AND/OR C+P DESIGN CONSTULTANTS AND SHALL NOT BE USED ON ANY OTHER WORK EXCEPT BY AGREEMENT WITH YOLANDA CASTRO. WRITTEN DIMENSIONS SHALL TAKE REFERENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED ON THE JOB SITE, ANY DISCREPANCY SHALL BE BROUGHT TO THE NOTICE OF YOLANDA CASTRO TO THE COMMENCEMENT OF ANY WORK PR O J E C T : OW N E R : AD D R E S S : Y.C. C+P 25 C P 0 0 6 1 AS SHOWN 5/3/2025 STAMP APPROVAL 11-05-2025 A. P . N . 40 6 S W e s t e r n A v e , U n i t # 2 S a n t a A n a , C A 9 2 7 0 3 NE W A C C E S S O R Y D W E L L I N G U N I T Ma t i a s M i r a n d a 00 7 - 2 2 3 - 0 6 12-22-2025 2 01-20-2026 02/27/2026 01-A1.3 EL E V A T I O N S SLAB OR WOOD FRAME SLIDING DOOR PROTECTO WRAP MEMBRANE OR PROTECTO DECK DECK LEDGER BOARD 1. PROTECTOWRAP 2. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 3. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS 4. ALL SURFACES MUST BE CLEAN, DRY, FREE OF DIRT AND OTHER FOREIGN MATERIALS. 5. CUT A PIECE OF PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE THE LENGTH OF THE THRESHOLD OPENING EXTENDING APPROXIMATELY 1" MINIMUM UP THE SIDES OF THE DOOR JAM. 6. PEEL OFF RELEASE LINER AND BEGIN APPLYING PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE TO THE DOOR SILL PLATE BY SMOOTHING AS THE ADHESIVE COMES INTO CONTACT WITH THE DOOR SILL. 7. PLACE THE THRESHOLD OVER THE PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE AND SECURE. PROTECTO SEALANT 25XL PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE DOOR THRESHOLD EXTERIOR DOOR SILL CROSS SECTION SHOWING PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE 1. PROTECTO WRAP 2. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 3. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS 4. ALL SURFACES MUST BE CLEAN, DRY, FREE OF DIRT AND OTHER FOREIGN MATERIALS. 5. CUT A PIECE OF PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE THE LENGTH OF THE THRESHOLD OPENING EXTENDING APPROXIMATELY 1" MINIMUM UP THE SIDES OF THE DOOR JAM. 6. PEEL OFF RELEASE LINER AND BEGIN APPLYING PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE TO THE DOOR SILL PLATE BY SMOOTHING AS THE ADHESIVE COMES INTO CONTACT WITH THE DOOR SILL. 7. PLACE THE THRESHOLD OVER THE PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE AND SECURE. SLAB OR WOOD FRAME SWING DOOR PROTECTO SEALANT 25XL PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE DOOR THRESHOLD PROTECTO WRAP MEMBRANE OR PROTECTO DECK DECK LEDGER BOARD EXTERIOR DOOR SILL CROSS SECTION SHOWING PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE 1. PROTECTOWRAP 2. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 3. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS 4. INSTALL PROTECTO WRAP PRODUCTS IN ORDER AS SHOWN BY NUMBERS 5. SCORE AND FOLD WEATHER RESISTIVE BARRIER ABOVE HEADER TO ALLOW PROTECTO WRAP PRODUCTS TO BE INSTALLED 6. INSTALL HEAD FLASHING UNDER WEATHER RESISTIVE BARRIER; MECHANICALLY FASTEN AS NECESSARY 7. FOLD WEATHER RESISTIVE BARRIER BACK OVER HEAD FLASHING AND SEAL EDGES 2 3 WEATHER RESISTIVE BARRIER (CHECK LOCAL BUILDING CODE FOR REQUIREMENTS) 2 MECHANICALLY FASTEN AS NECESSARY IN CORNERS THROUGH PROTECTO WRAP MEMBRANE 4 4 5 EXTERIOR SHEATHING FOLD UP WEATHER RESISTIVE BARRIER AND TEMPORARILY SECURE 1 1 PROTECTO WRAP MEMBRANE SILL PLATE SEAL TOP OF JOISTS UNDER DECKING WITH PROTECTO DECK ACQ FLASHING TAPE PROTECTO WRAP MEMBRANE OR PROTECTO DECK ACQ FLASHING TAPE BEHIND WRB SEE PW-PD05 PROTECTO DETAIL TAPE WRAP CUT WRB BACK FROM OPENING EXTERIOR SLIDING DOOR WITH DECK FLASHING INSTALLATION AFTER WEATHER RESISTIVE BARRIER 1. PROTECTOWRAP 2. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 3. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS 1 WEATHER RESISTIVE BARRIER OVER PW MEMBRANE (CHECK LOCAL BUILDING CODE FOR REQUIREMENTS) DOOR ROUGH OPENING PROTECTO PREMIUM DUAL GUARD THRESHOLD TAPE, WRAPPED UP SIDES 1" SUBFLOOR RIM JOIST PROTECTO WRAP MEMBRANE OR PROTECTO DECK ACQ FLASHING TAPE 3 PROTECTO DECK ACQ FLASHING TAPE SEAL TOP OF JOISTS UNDER DECKING 2 PROTECTO DECK ACQ FLASHING TAPE UNDER HANGERS PROTECTO WRAP DETAIL TAPE EXTERIOR DOOR SILL CORNER ATTACH SILL STRIP WITH TOP EDGE LEVEL WITH ROUGH SILL; EXTEND BEYOND EDGE OF ROUGH OPENING AT LEAST 8". SECURE ALL BUILDING PAPER OR SIMILAR APPROVED FLASHING MATERIAL WITH GALVANIZED NAILS OR POWER DRIVEN STAPLES. ATTACH JAMB STRIPS WITH SIDE EDGE EVEN WITH ROUGH-JAMB FRAMING. START STRIP 1" BELOW LOWER EDGE OF SILL STRIP AND EXTEND 4" ABOVE LOWER EDGE OF LINTEL. INSTALL WINDOW INTO ROUGH OPENING WITH SILL AND JAMB FLANGES OVER PREVIOUSLY INSTALLED FLASHING. ATTACH HEAD FLASHING OVER THE WINDOW FLANGE. COMMENCING AT THE BOTTOM(SOLE PLATE) OF THE WALL, LAY BUILDING PAPER UNDER SILL STRIP. CUT ANY EXCESS BUILDING PAPER THAT MAY EXTEND CUT ANY EXCESS BUILDING PAPER THAT MAY EXTEND ABOVE THE SILL FLANGE LINE ON EACH SIDE OF OPENING (SHOWN AS DASHED LINE). DO NOT CUT BUILDING PAPER HORIZONTALLY SO THE PAPER WILL LAP OVER THE JAMB STRIPS. INSTALL SUCCESSIVE LINES OF BUILDING PAPER (B,C,D ETC) OVER JAMB AND HEAD FLANGES, LAPPING EACH COURSE. WINDOW FLASHING DETAIL 1. PROTECTO WRAP 2. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 3. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS SILL PLATE WALL SHEATHING PROTECTO WRAP DETAIL TAPE IN LOWER CORNERS PROTECTO SILL DRAINAGE SYSTEM BEAD OF PROTECTO SEALANT 25XL IN CORNER, AT EDGE OF PSDS PROTECTO WRAP MEMBRANE, OVER WRB AND DETAIL TAPE, UNDER PSDS WRB "BIB" PROTECTO WRAP MEMBRANE PROTECTO SILL DRAINAGE SYSTEM 1 3 2 WRB "BIB" INSTALLED TO ALLOW MIN. 1" ADHESION OF FLASHING TO SHEATHING PROTECTO SEALANT 25XL, OPTIONAL ALONG TOP EDGE OF PSDS BACKDAM 1. PROTECTOWRAP 2. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 3. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS 4. PROTECTO WRAP COMPANY RECOMMENDS AN INTERIOR AIR SEAL WHEN USING THESE OPTIONS OPTION B SILL PLATE "L" METAL OR EQUIVALENT BACKDAM RECOMMENDED OPTION A PROTECTO WRAP MEMBRANE COMPATIBLE TAPERED WOOD SIDING SILL PLATE WALL SHEATHING PROTECTO WRAP DETAIL TAPE PROTECTO WRAP MEMBRANE PROTECTO WRAP MEMBRANE WALL SHEATHING PROTECTO WRAP DETAIL TAPE PROTECTO WRAP MEMBRANE PROTECTO SEALANT 25XL WRB "BIB" INSTALLED TO ALLOW MIN. 1" ADHESION OF SILL FLASHING TO SHEATHING WRB "BIB" INSTALLED TO ALLOW MIN. 1" ADHESION OF SILL FLASHING TO SHEATHING WINDOW SILL PAN PROTECTO SILL DRAINAGE SYSTEM WINDOW SILL PAN OPTIONS A & B WEATHER RESISTIVE BARRIER (OPTIONAL) PROTECTO WRAP UNDERLAYMENT WALL SHEATHING PROTECTO WRAP DETAIL TAPE CONTINUOUS BEAD OF PROTECTO WRAP JS160 H MASTIC PROTECTO WRAP UNDERLAYMENT SL O P E 1. PROTECTO WRAP 2. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 3. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS 4. EDGE LAPS ARE MINIMUM 2" AND END LAPS ARE MINIMUM 6"- REFER TO TECHNICAL DATA SHEET FOR PRODUCT SPECIFIC REQUIREMENTS SLOPE ROOF DECK 1. PROTECTOWRAP 2. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 3. EXTEND PROTECTO WRAP UNDERLAYMENT ON THE WALL SHEATHING ABOVE THE HIGHEST EXPECTED LEVEL OF SNOW AND ICE 3. EXTEND PROTECTO WRAP UNDERLAYMENT ON THE ROOF DECK ABOVE THE HIGHEST EXPECTED LEVEL OF WATER BACK-UP FROM ICE DAMS 4. EXTEND PROTECTO WRAP UNDERLAYMENT BEYOND EAVE ONTO VERTICAL SIDE WALL 5. THE METAL FLASHING IS INSTALLED OVER THE PROTECTO WRAP UNDERLAYMENT 6. INSTALL PROTECTO WRAP UNDERLAYMENT IN ORDER AS SHOWN BY NUMBERS 7. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS 8. EDGE LAPS ARE MINIMUM 2" AND END LAPS ARE MINIMUM 6"- REFER TO TECHNICAL DATA SHEET FOR PRODUCT SPECIFIC REQUIREMENTS METAL DRIP EDGE BY OTHERS ROOF DECK VERTICAL SIDEWALL PROTECTO WRAP UNDERLAYMENT KICK OUT FLASHING (OPTIONAL) EXPOSED ROOF COVERING EXPOSED WALL COVERING WEATHER RESISTIVE BARRIER (OPTIONAL) METAL STEP FLASHING CONTINUOUS BEAD OF JS 160 H MASTIC PROTECTO WRAP UNDERLAYMENT PROTECTO WRAP UNDERLAYMENT CONTINUOUS BEAD OF JS 160 H MASTIC AT SEAMS 1 4 3 2 1 2 1 EXTEND PROTECTO WRAP UDERLAYMENT ABOVE HIGHEST EXPECTED LEVEL OF SNOW AND ICE BUILD-UP VERTICAL SIDE WALL 1. VALLEYS REQUIRE A MINIMUM 18" WIDE ROLL CENTERED DOWN THE FULL LENGTH OF THE VALLEY 2. INSTALL MEMBRANE STARTING AT THE LOWEST POINT OF ROOF SLOPE AND WORK UP THE SLOPE 3. PROTECTO WRAP UNDERLAYMENTS SHOULD BE INSTALLED TO FORM WATER-SHEDDING LAPS 4. INSTALL IN ORDER AS SHOWN BY NUMBERS 5. REFER TO TECHNICAL DATA SHEET FOR MORE INFORMATION 6. VISIT PROTECTOWRAP.COM FOR THE MOST CURRENT INFORMATION 1 2 26" min. PROTECTO WRAP UNDERLAYMENT LAP VALLEY FLASHING DETAIL 9" min . OUTSIDE CORNER WALL TO ROOF DECK 3 2 1 7 6 5 11 10 9 8 4 CLASS A FIRE RESISTANT ROOFING / ROOF ASSEMBLY SOLID BLOCKING FROM TOP PLATE TO UNDER SIDE OF ROOF SHEATING. EAVES BETWEEN 2 AND 5 FEET : 7/8" STUCCO FINISH CLASS A FIRE RESISTANT ROOFING / ROOF ASSEMBLY FIRE RESISTANT EXTERIOR WALL AND EAVE PROTECTION (TYP.) EN EN EN 45° PROTECT UNDERSIDE OF EAVE WITH 1-HOUR PROTECTION AND NO EAVES VENTS. STUCCO FINISH (TYP.) EAVES BETWEEN 2 AND 5 FEET : PROTECT UNDERSIDE OF EAVE WITH 1-HOUR PROTECTION AND EAVES BETWEEN 2 AND 5 FEET : FIRE RESISTANT EXTERIOR WALL AND EAVE PROTECTION (TYP.) FR2FR1 11 5/8" TYPE "X" GYP BD. 2X4 STUD WALL WITH R-15 INSULATION 5/8" TYPE "X" GYP BD. 2X4 STUD WALL WITH R-15 INSULATION OPENINGS PER STORY (DOORS, WINDOWS, MECHANICAL VENTS, SCUPPERS) ARE ALLOWED WHERE THE CUMULATIVE AREA OF THE OPENINGS NOT EXCEED 25% OF THE EXTERIOR WALL AREA PER STORY 5'-5" 5'-0" 5'-5" 5'-0" 7/8" STUCCO FINISH OPENINGS PER STORY (DOORS, WINDOWS, MECHANICAL VENTS, SCUPPERS) ARE ALLOWED WHERE THE CUMULATIVE AREA OF THE OPENINGS NOT EXCEED 25% OF THE EXTERIOR WALL AREA PER STORY NO EAVES VENTS. STUCCO FINISH (TYP.) PR O P E R T Y L I N E PR O P E R T Y L I N E OF SHEET NO. DATE ISSUED DRAWN BY CHECKED BY SCALE PRINT:REVISION: SH E E T N A M E : THESE DRAWINGS, DESIGN AND SPECIFICATIONS ARE THE PROPERTY AND COPY RIGHT OF YOLANDA CASTRO AND/OR C+P DESIGN CONSTULTANTS AND SHALL NOT BE USED ON ANY OTHER WORK EXCEPT BY AGREEMENT WITH YOLANDA CASTRO. WRITTEN DIMENSIONS SHALL TAKE REFERENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED ON THE JOB SITE, ANY DISCREPANCY SHALL BE BROUGHT TO THE NOTICE OF YOLANDA CASTRO TO THE COMMENCEMENT OF ANY WORK PR O J E C T : OW N E R : AD D R E S S : Y.C. C+P 25 C P 0 0 6 1 AS SHOWN 5/3/2025 STAMP APPROVAL 11-05-2025 A. P . N . 40 6 S W e s t e r n A v e , U n i t # 2 S a n t a A n a , C A 9 2 7 0 3 NE W A C C E S S O R Y D W E L L I N G U N I T Ma t i a s M i r a n d a 00 7 - 2 2 3 - 0 6 12-22-2025 2 01-20-2026 02/27/2026 01-A2 FL A S H I N G D E T A I L S OF SHEET NO. DATE ISSUED DRAWN BY CHECKED BY SCALE PRINT:REVISION: SH E E T N A M E : THESE DRAWINGS, DESIGN AND SPECIFICATIONS ARE THE PROPERTY AND COPY RIGHT OF YOLANDA CASTRO AND/OR C+P DESIGN CONSTULTANTS AND SHALL NOT BE USED ON ANY OTHER WORK EXCEPT BY AGREEMENT WITH YOLANDA CASTRO. WRITTEN DIMENSIONS SHALL TAKE REFERENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED ON THE JOB SITE, ANY DISCREPANCY SHALL BE BROUGHT TO THE NOTICE OF YOLANDA CASTRO TO THE COMMENCEMENT OF ANY WORK PR O J E C T : OW N E R : AD D R E S S : Y.C. C+P 25 C P 0 0 6 1 AS SHOWN 5/3/2025 STAMP APPROVAL 11-05-2025 A. P . N . 40 6 S W e s t e r n A v e , U n i t # 2 S a n t a A n a , C A 9 2 7 0 3 NE W A C C E S S O R Y D W E L L I N G U N I T Ma t i a s M i r a n d a 00 7 - 2 2 3 - 0 6 12-22-2025 2 01-20-2026 02/27/2026 03-T1 TI T L E 2 4 STRUCTURAL NOTES S1.0 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 STRUCTURAL NOTES TYPICAL DETAIL1TYPICAL DETAIL2TYPICAL DETAIL4 TYPICAL DETAIL5TYPICAL DETAIL6TYPICAL DETAIL7TYPICAL DETAIL8 TYPICAL DETAIL12 TYPICAL DETAIL11 TYPICAL DETAIL10 TYPICAL DETAIL9 TYPICAL DETAIL3 S1.1 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 TYPICAL DETAILS TYPICAL DETAIL2TYPICAL DETAIL4 TYPICAL DETAIL5TYPICAL DETAIL6TYPICAL DETAIL8 TYPICAL DETAIL12 TYPICAL DETAIL9TYPICAL DETAIL10 S1.2 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 TYPICAL DETAILS TYPICAL DETAIL1TYPICAL DETAIL2TYPICAL DETAIL4 TYPICAL DETAIL12 TYPICAL DETAIL11 TYPICAL DETAIL3 TYPICAL DETAIL9TYPICAL DETAIL10 S1.3 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 TYPICAL DETAILS TYPICAL DETAIL1TYPICAL DETAIL2TYPICAL DETAIL4 TYPICAL DETAIL6TYPICAL DETAIL7TYPICAL DETAIL8 TYPICAL DETAIL12 TYPICAL DETAIL11 TYPICAL DETAIL3 TYPICAL DETAIL10 TYPICAL DETAIL9 S1.4 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 TYPICAL DETAILS N1FOUNDATION PLAN SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 S2.0 FOUNDATION PLAN GENERAL NOTES:1. Sill plates along braced wall lines in buildings assigned to Seismic Design Category D shall be anchored with anchor bolts not less than 1/2" diameter with steel plate washers between the foundation sill plate and the nut, or approved anchor straps load-rated in accordance with Section 2304.10.4 and spaced to provide equivalent anchorage. Plate washers shall be not less than 0.229 inch by 3 inches by 3 inches in size. The hole in the plate washer is permitted to be diagonally slotted with a width of up to 3/16 inch larger than the bolt diameter and a slot length not to exceed 13/4 inches, provided that a standard cut washer is placed between the plate washer and the nut. CBC 2308.3.1.12. Concrete shall be poured monolithically with slab or clearly show the required 7 embedment below the cold joint for two pour concrete option. (CBC 2022, 2308.3.1) N1ROOF FRAMING PLAN C.J. C.J. X2.1 Y3 . 1 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 S2.2 ROOF FRAMING PLAN DETAIL1DETAIL2DETAIL4 DETAIL5DETAIL6DETAIL7DETAIL8 DETAIL12 DETAIL11 DETAIL10 DETAIL9 DETAIL3 S3.0 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 FOUNDATION DETAILS DETAIL1DETAIL2DETAIL4 DETAIL5DETAIL6DETAIL7DETAIL8 DETAIL12 DETAIL11 DETAIL10 DETAIL9 DETAIL3 S5.0 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 ROOF FRAMING DETAILS DETAIL1DETAIL2DETAIL4 DETAIL6DETAIL8 DETAIL12 DETAIL11 DETAIL10 DETAIL9 DETAIL3 S5.1 SHEET NUMBER PR O J E C T A D D R E S S : SHEETSOF REVISIONS CONSTRUCTION SHALL CONFORM TO THE ENGINEER. ALL WORK. REPORT DISCREPANCIES BEFORE PROCEEDING WITH THE CHECK AND VERIFY ALL DIMENSIONS DRAWN : CHECKED : DATE : JOB NO. TO THE C.B.C. MARK DATE PROJECT: 25-5096 JUVENTINO MC 10 FEB 26 . . . . . . . . . . . . TITLE AD D I T I O N A N D R E M O D E L 40 6 S W E S T E R N A V E 40 6 S W E S T E R N A V E SA N T A A N A , C A . 9 2 7 0 3 3 1 2 3 ENGINEER: Margarito Castillo, S.E. CASTILLO ENGINEERING T: 562-961-5600 WWW.CASTILLOENGINEERING.COM 1147 E. MARKET ST. LONG BEACH, CA 90805 ROOF FRAMING DETAILS CERTIFICATE NO. 100059 SANTA ANA UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES FEE CERTIFICATION OF COMPLIANCE AND RECEIPT FOR PAYMENT FOR Project Number:PRJ-3382461 Project Request ID:8ARTXSLW8L Request Contact:YOLANDA CASTRO (DEVELOPER) Job Location / Address: 406 S. Western Ave 2, Santa Ana, CA 92703 Permit Issuing Office: City of Santa Ana This is to certify that all fees due to the Santa Ana Unified School District under Provision of Government Code Section 65995 as a prerequisite to the issuance of a Building Permit have been received, based on the above referenced information, this Certification is hereby Executed. PMT-419613 Address Development Type Construction Type Square Feet 406 S Western Ave unit #2, Santa Ana, CA 92703 Residential Accessory Dwelling Unit (ADU) 785 Permit Number 101125303 Plan Check Number 101125303 419613-Residential Accessory Dwelling Unit (ADU) fees as required in the amount of:$4,058.45 ($5.17 [Rate] x 785 [Square Footage]) Address Development Type Construction Type Square Feet 406 S Western Ave Unit #2, Santa Ana, CA 92703 Residential Tear-Down / Rebuild 291 Permit Number See other attachments 419613-Residential Tear-Down / Rebuild Credit given as required in the amount of:$-1,504.47 ($5.17 [Rate] x 291 [Square Footage]) Developer Fees Paid:$2,553.98 Payment Method: ECHECK: xxxx 7763 Payment Date: 03/31/2026 09:23 am Jeremy Cogan School District Representative Date: 03/31/2026 CERTIFICATE NO. 100059 NOTICE OF 90-DAY PERIOD FOR PROTEST OF FEES Pursuant to Section 66020 of the California Government Code and other applicable law, you have a period of ninety (90) days from the date of payment of school fees, mitigation payments or other extractions to protest the validity thereof. This ninety (90) day period commences upon such payment of performance of any other requirement as provided in Section 66020. Any such protest must be in writing and received by the Santa Ana Unified School District within ninety (90) calendar days of the date of the School District Certification above. Page 1 of 1 EXISTING ONE & TWO FAMILY DWELLINGS ELECTRICAL SERVICES UNDERGROUND EXCEPTION CEC 2022 ELC-04 All new utility connections are required to be installed below grade by Santa Ana Municipal Code 41- 626(b). There is a standing exception for one and two family dwellings. This exception applies only when the new electrical service is designed to be fed from below grade as well as overhead. This diagram is a typical unit. The utility is able to feed this cabinet from the top or the bottom without interfering with the distribution wiring. All the circuit breakers and branch circuits are contained in the circuit breaker side of this cabinet. Only listed combination overhead and underground feed service boxes may be used to connect to an overhead utility drop. This exception to an underground fed service applies only to existing single family and two family residences. Planning & Building Agency Permits & Plan Check Section 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 Rigid Conduit Service Entrance Conductor Riser Underground Service Lateral METER Rev. 1/21/2020