Loading...
HomeMy WebLinkAbout163157_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: PROJECT ADDRESS: PLAN CHECK ENGINEER:TEL:714FAX:714 647-5897 TYPE OF CONSTRUCTION: OCCUPANCY CLASSIFICATION(S): PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION INITIAL REVIEW EXPIRATION RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. 3. TEL: FAX: VALUATION: EMAIL: FLOOD ZONE: APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) for an appointment.Clearly indicate the scope of work under this building permit application: - Revise project job description on the building permit application worksheet to reflect the work to be done under the subject building permit application.– Include new demising wall and creation of new unit. Provide planning approval for new unit. an unit number assignment may be required.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700) - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039)Provide on the drawings a complete “fire resistance design schedule” which shall include the following: - Evidence of appropriate fire resistance for each building element in accordance with specific UL listing or ICC Note on the floor plan the use and occupancy load of each room and/or area. Relate each use to a CBC Table item. Note occupant loads which are the greater number based on CBC Section 1004 and Table 1004.1.1 or the actual number of occupants. – CALLOUT USE OF NEW UNIT AT REAR.Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636.Note ICC Research Report Number on the drawings for the suspended ceiling system.Tenant improvements in the MainPlace Mall shall show compliance with the following special provisions and CBC Section 402: - CBC Section 106.3. Tenant improvements at 2800 North Main, Main Place Mall, shall show compliance with “Code Analysis and Fire Protection and Life Safety Concept” prepared by Code Consultants Incorporated, dated “Revised February 18, 1986, and February 22, 1990 (1991 Mall Expansion).” - Note on drawings: Duct and smoke removal system modification is not allowed and shall be in compliance with the “Code Analysis and Fire Protection and Life Safety Concept.” - CBC Sections 402.7.2 and 708. Each tenant space shall be separated from other tenant spaces by a wall having a fire-resistive rating of not less than one hour. The separation wall shall extend from the floor to the underside of the ceiling above.CBC Section 402.12, Security grilles and doors. Horizontal sliding or vertical security grilles or doors, which are part of a required means of egress, shall conform to the following: (if applicable) - They must remain secured in the full open position during the period of occupancy by the general public. - Doors or grilles shall not be brought to the closed position when there are more than 10 persons occupying spaces served by a single exit or 50 persons occupying spaces served by more than one exit. - The doors or grilles shall be openable from within without the use of any special knowledge or effort when the space is occupied. - When two or more exits are required, not more than one half of the exits may be equipped with horizontal sliding or vertical rolling grilles or doors. - Note on Drawings: Post a legible sign at security grill/door closing controls stating “Security grill/door shall remain secured in the full open position during the period of occupancy by the general public.”CBC Section 402.15.5.2, Plastic panel and plastic signs. Within every story or level and from side wall to side wall or each tenant space or mall, plastic panels and plastic signs shall be limited as follows: (if applicable) - Plastics, other than foam plastics, shall comply with CBC Section 402.15.4. - Foam plastics shall have a maximum heat-release rate of 150 kilowatts when tested in accordance with approved recognized standards (see CBC Section 402.15.5) and shall have the following physical characteristics: - A density not less than 20 pounds per cubic foot; and a thickness not greater than ½”. - They shall not exceed 20 percent of the wall area facing the mall; - They shall not exceed a height of 36” except that if the sign is vertical then the height shall not exceed 96” and the width shall not exceed 36”; and - They shall be located a minimum distance of 18” from adjacent tenants.Note On Drawings: (Santa Ana Police Department Requirement)SANTA ANA POLICE DEPARTMENT REQUIREMENTS FOR MAINPLACEOVERHEAD/ROLLING GRILLESECURITYORDINANCE REQUIREMENTSTUBES ARE TO BE “DOUBLE TUBED” (NO MORE THAN ½” APART) AND CONSTRUCTED OF ½” STEELOR BE STEEL REINFORCED TUBES WITHIN 40” OF ALL LOCKING HARDWARE. PERFORATED SLATSCAN BE USED INSTEAD OF THE AFOREMENTIONED AS LONG AS THEY ARE CONSTRUCTED OF MINIMUM 20 GA STEEL.LOCKING MECHANISM TO BE STEEL SLIDEBOLTS BOTH SIDES OF DOOR. SLIDEBOLTSTO EMBED AMINIMUM OF ½” INTO THE RECEIVING GUIDE.CURTAIN GRILLES ARE NOT TO BE UTILIZED.FIRE DEPARTMENT REQUIRED EMERGENCY RELEASE MUST BE LOCATED NO MORE THAN 40” FROM THE EXTERIOR SIDE OF THE GRILLE.THE LOCKING MECHANISM’S INTERIOR THUMBTURN MUST BE SHIELDED BY AN INTERIOR HOOD TO PREVENT ITS MANIPULATION FROM THE EXTERIOR SIDE OF THEGRILLE.