HomeMy WebLinkAbout163212_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: PROJECT ADDRESS: PLAN CHECK ENGINEER:TEL:714FAX:714 647-5897 TYPE OF CONSTRUCTION: OCCUPANCY CLASSIFICATION(S): PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION INITIAL REVIEW EXPIRATION RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. 3. TEL: FAX: VALUATION: EMAIL: FLOOD ZONE: APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) for an appointment.Please return marked up set of drawings with corrections.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2010 California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review.A California licensed architect is required for this projectComplete building code analysis is required, including and not limited to occupancy requirements, building type of construction, allowable area and height, exit plan, fire resistive construction and disabled accessibility requirements.Clearly indicate the scope of work under this building permit application: - Revise project job description on the building permit application worksheet to reflect the work to be done under the subject building permit application.CBC Sections A106.1 and A106.3.4.1, All drawings and supporting documents shall be prepared, stamped and signed by a California licensed architect or registered civil engineer.Include address and telephone number of the all design consultants including the licensed architect, engineer of record, geotechnical engineer, energy consultant …This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700) - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039) - School District Compliance Certificate; a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of work. Refer to the attached handout. - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceState Division of Occupational Safety Permit (Cal/OSHA) (939-0145). A Cal/OSHA permit is required for: - Construction of trenches or excavations which are 5‘or deeper and into which a person is required to descend. - The construction or demolition of any building, structure, false-work, or scaffolding more than three stories high or the equivalent height.A separate Building Permit Application is required for: - Fence(s) - Block wall(s) - Light standard(s) - Pedestrian protection - Demolition - Site improvementsProvide pedestrian protection in accordance with CBC Section 3306. Show location and type of protection on plan view. Provide typical construction details, sections, and elevations of pedestrian protection required. Pedestrian protection constructed within a public right of way shall require a building permit issued by the Building Safety Division and a separate approval from the City’s Public Works Agency (714) 647-5039.Provide a statement on the title sheet of the plans that this project shall comply with following codes:- 2010 California Residential Code (CRC) - 2010 California Building Code (CBC) - 2010 California Electrical Code (CEC) - 2010 California Mechanical Code (CMC) - 2010 California Plumbing Code (CPC) - 2010 California Green Building Standards Code (CGBS) or CALGreen - 2010 California Energy Code (CEnC) - City of Santa Ana Municipal CodeProvide the following: - Provide a fully dimensioned site plan on each set of plans. - Disabled access compliance must be shown on the site plan. - Show all property lines of record on the site plan. Show compliance with CBC Section 704 and CBC Tables 601, 602, and 704.8.Show on the plans: - Complete legal description - Assessor’s Parcel Number - Occupancy Classification(s) - Type of Construction - Area tabulation justifying floor area(s) of building(s) (CBC Sections 503, 505, 506, 507, and 508 and CBC Table 503) - Fire Sprinkler System (State purpose of sprinkler system, for example, area increase under CBC Section 506.3, required by CBC Section 903 for type of occupancy, etc.) - Number, width, and purpose (cite code section) of yards required - Number of stories/mezzanines and building height in feetSpecify finish floor elevation of first floor.Flood zone.This project is in a special flood hazard area designated on the flood insurance rate map (FIRM) as zone A. This zone requires that the lowest finish floor elevation (including basement) of the structure shall be at (or above) base flood elevation determined by a hydrology study for the A zone on the flood insurance rate map. All elevations must be referenced to the National Geodetic Vertical Datum. Reference should be made to the Flood Plain Management Ordinance, Santa Ana Municipal Code, Chapter 7, for complete requirements. Drawings shall show compliance with said ordinance including noting flood zone and finish floor elevation. Note on Plans: A Federal Emergency Management Agency National Flood Insurance Program ELEVATION CERTIFICATE shall be completed by a California Licensed Land Surveyor or California Registered Civil Engineer who is authorized to practice land surveying. The completed ELEVATION CERTIFICATE must be submitted to the Building Inspector at the time of foundation inspection, and a final certificate must be submitted at the time of final inspection.The National Flood Insurance Program (NFIP) requires the following to be wet flood proofed: ____________________. Refer to FEMA Technical Bulletin 7-93 and the attached city handout on Flood proofing for general requirements and restrictions. Revise the drawings to show compliance.Label and note hourly fire rating of: - Exterior walls - All corridors - Fire walls - Fire barriers - Shafts - Stair enclosures - Exit passageways - Horizontal exits - HallwaysProvide on the drawings a complete “fire resistance design schedule” which shall include the following: - The building elements which require fire-resistive construction. - The hourly rating of the building element as required by the Code. - Evidence of appropriate fire resistance for each building element in accordance with specific UL listing or ICC Evaluation Report for each material selected. Evidence shall include appropriate material thickness for each building element. - Non-standard fire-resistive designs requiring adhesives, overcoats, metal lath-netting, or special thicknesses shall be detailed.Reference each fire-resistive assembly to a CBC Chapter 7, Table and Item number: - Walls - Ceilings - Columns - Shafts - Structural Elements - Fire walls - Fire barriers - Stair enclosures - Horizontal exits - Exit passageway - Hallways - CorridorsCBC Section 504.3 and 1509.2.4: Towers, spires and other roof structures shall comply with type of construction requirements of these sections.Plans shall indicate how required structural and fire resistive integrity will be maintained where a penetration will be made for electrical, mechanical, plumbing and communication conduits, pipes and similar systems. CBC Section 106.1.1 and CBC Chapter 7. Note on the plans the ICC Research Report number, U.L. number, State Fire Marshal number, or approval number of another agency accepted by the City of Santa Ana.CBC Section 717.2.2, Provide fire blocking in concealed spaces of stud walls and partitions, including furred spaces at the ceiling and floor level and at 10 ft. intervals both vertical and horizontal.Fireblocking. In combustible construction, fireblocking shall be installed to cut off concealed draft openings (both vertical and horizontal) and shall form an effective barrier between floors, between a top story and a roof or attic space. Fireblocking shall be installed in the locations specified in CBC Sections 717.2.2 through 717.2.7.CBC Section 717.2.6, Architectural trim. Fireblocking shall be installed within concealed spaces of exterior wall finish and other exterior architectural elements where permitted to be of combustible construction as specified in Section 1406 or where erected with combustible frames, at maximum intervals of 20’, so that there will be no open space exceeding 100 square feet. Where wood furring strips are used, they shall be of approved wood of natural decay resistance or preservative-treated wood. If non-continuous, such elements shall have closed ends, with at least 4” of separation between sections.CBC Section 708.9, Penetrations in a fire partition by ducts and air transfer openings shall comply with Section 716.Provide on the drawings interior wall and ceiling finish schedule showing compliance with CBC Section 803 and CBC Table 803.5.Interior floor finishes shall show compliance with CBC Section 804.Provide complete details on the drawings showing compliance with CBC Section 1405 requirements for veneer construction.Provide complying exiting plan for the “reminder” area. Note the use of adjacent units.CBC Section 1004.3, Posting of occupant load. Every room or space that is assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.Note on the floor plan the use and occupancy load of each room and/or area. Relate each use to a CBC Table item. Note occupant loads which are the greater number based on CBC Section 1004 and Table 1004.1.1 or the actual number of occupants.Provide width of exit complying with: - CBC Section 1005 (Egress Width) - CBC Section 1028 (Assembly Occupancy)CBC Section 1007.2, Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: Accessible Routes, Stairways, Elevators, Horizontal Exits, Ramps, or Areas of Refuge.CBC Section 1014.2, Egress through intervening spaces. Egress through intervening spaces shall comply with this section.Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not a high hazard occupancy and provide a discernible path of egress travel to an exit.CBC Section 1015.3, Boiler, Incinerator and furnace rooms. Two exit access doorways are required in boiler, incinerator and furnace rooms where the area is over 500 square feet and any fuel-fired equipment exceeds 400,000 British thermal units (Btu) input capacity. Where two exit access doorways are required, one is permitted to be a fixed ladder or an alternating tread device. Exit access doorways shall be separated by a horizontal distance equal to one-half the length of the maximum overall diagonal dimension of the room. Refer to Sections 1015.4 through 1015.6 for additional comments.CBC Section 1016.1. Travel distance limitations. Exits shall be so located on each story such that the maximum length of exit access travel, measured from the most remote point within a story to the entrance to an exit along the natural and unobstructed path of egress travel, shall not exceed the distances given in Table 1016.1.CBC Section 1016.1. Where the path of exit access includes unenclosed stairways or ramps within the exit access or includes unenclosed exit ramps or stairways as permitted in Section 1020.1, the distance of travel on such means of egress components shall also be included in the travel distance measurement. The measurement along stairways shall be made on a plane parallel and tangent to the stair tread nosing in the center of the stairway.CBC Sections 1024.6 and 1018.1. Exiting from any occupied point in a building or structure on the subject site must be continuous, unobstructed, and undiminished to a public way. This includes gates which must show compliance with CDB Section 1008.2. Revise drawings to show compliance.Corridors shall be fire-resistance rated in accordance with Table 1017.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partitions.CBC Section 1017.4.1, Corridor ceiling. Use of the space between the corridor ceiling and the floor or roof structure above as a return air plenum is not permitted. See CBC Section 1017.4 for exceptions.Provide a complete architectural section of 1-HR. corridor detailing fire resistive rated construction of the walls and ceilings. Detail all duct and other penetrations CBC Sections 708.4, 1017.1, 715.1, Table 715.4 & 716.5.4.Provide typical complete section view through one-hour corridor(s) showing compliance with CBC Sections 1017 and 708: - Size, spacing, and material of framing members. Note gauge and ICC number and installation/construction requirements for metal framing members. - Method of attaching framing to the building structure. Compliance shall be shown with CBC Section 1607.13 for lateral support of the walls. Do not support top of walls to suspended ceiling system unless calculations and drawings prepared by a registered engineer are submitted for review. Submit structural engineering calculations for walls in rooms with a floor to building structure above height greater than 14’. - Sheathing material and details of attachment. Note type, size, and spacing of fasteners. - Height of partition, suspended ceiling, structure above. - Reference each wall and ceiling fire-resistive assembly to a CBC Chapter 7 Table and item number. - Fire blocks and draft stops in combustible construction in accordance with CBC Section 717. Show location(s) and provide typical construction details. - Fire/smoke damper locations, installation requirements, and required access doors. Refer to CBC Section 716 and Mechanical Code Section 606.Include the following notes with typical one-hour corridor section view: - Interior openings for other than doors or ducts shall be protected by fixed glazing listed and labeled for a fire protection rating of at least three-fourths hour in accordance with CBC Section 715.5. - Penetrations in fire-resistive walls shall comply with CBC Sections 715 and 716. - Cabinets such as recessed electrical panels, fire hose cabinets, and recess fire extinguisher cabinets constructed of steel are permitted, provided that the openings in the fire rated corridor are sealed with approved sealant material to prevent the passages of smoke. - Other cabinets should be installed or recessed so that there is no reduction in the fire rating of the wall, or opening which would allow smoke to pass. This would mean that the cabinet must be surrounded with material which provides the equivalent of one-hour fire resistance.Provide on the drawings a complete door schedule, showing: - Hardware complying with exiting and disabled accessibility requirements (CBC Sections 1008.1.8 and 1133B.2.5) - Fire-rating of door assembly complying with CBC Section 715 Opening Protection - Note smoke seal (in accordance with CBC Section 715.4.3, required for doors forming part of the one-hour exit corridor envelope) - Show compliance with the City of Santa Ana’s Security Ordinance (Contact the Santa Ana Police Department Crime Prevention Section by telephoning 714-647-5840)CBC Section 1008.1.8, Note on drawing: “Exit doors shall be openable from the inside without the use of a key or any special knowledge or effort.”CBC Section 1008.1, Exit doors shall be marked so that they are readily distinguishable from the adjacent construction.Panic hardware shall comply with CBC Section 1008.1.9. Panic hardware shall be provided as required by CBC Section(s): - An Occupancy with an occupant count > 50. - Electrical rooms with equipment rated 1,200 amperes or more and over 6’ wide that contain over current devices, switching devices or control devices with exit access doors shall be equipped with panic hardware and doors shall swing in the direction of egress. - By the Fire Department All doors require a level floor landing on each side in accordance with CBC Sections 1008.1.4, 1008.1.5, 1008.1.6, and 1133B.2.4 and CBC Figures 11B-26A and 11B-26B. Provide typical door threshold details and details of change in floor covering material.The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. CBC Section  1126A.3.2.Provide specifications for doors hardware (i.e., lever type, push-pull panic, etc) to comply with disabled access requirements. CBC Section 1133B.2.5.2.The floor or landing at each side of an exit door shall be level and having a length in the direction of the door swing of at least 60” and the length opposite the direction of door swing of 44” as measured at right angles to the plane of the door in the closed position. CBC Section 1126A.3.1.All entrances and exterior ground-floor exit doors to buildings and facilities shall be made accessible to persons with disabilities. Doorways shall have a minimum clear opening of 32” with the door open 90 degrees, measure between the face of the door and the opposite stop. Doorways require dimensioning on the plans to insure compliance with the required landing area/maneuvering clearances at doors in accordance with CBC Section 1133B.2.4.2 and CBC Figures 11B-26A and 11B-26B.CBC Section 1133B.2.5.1, Hand-activated door opening hardware shall be centered between 30” and 44” above the floor. Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever-type hardware, by panic bars, push-pull activating bars, or other hardware designed to provide passage without requiring the ability to grasp the opening hardware. Locked exit doors shall operate as above in egress direction.CBC Section 1133B.2.5, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.CBC Section 1127B.3, All building entrances that are accessible to and usable by persons with disabilities shall be identified with a least one standard sign and with an additional directional signs, as required, to be visible to persons along approaching pedestrian ways.CBC Section 1133B.2.6, Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.Stairways shall show compliance with CBC Sections 1009 and 1133B.4 including applicable disabled accessibility requirements. - Provide complete architectural plan view, sections, details, and notes for stairway(s). - Dimension stairway width showing compliance with CBC Sections 1009.1, 1005, and 1007.3. - Dimension rise of steps shall be not less than 4” or greater than 7”. The run shall notbe less than 11”. - Treads, nosing, and risers require compliance with CBC Section 1133B.4.5, including no open risers and slip resistant treads. - CBC Section 1009.2, Dimension stairway headroom clearance. 6’ 8” minimum clearance.CBC Section 1133B.4.4, The upper approach and the lower tread of each interior stair shall be marked by a strip of clearly contrasting color at least 2” wide placed parallel to and close to (not more than 1” from) the nose of the step or landing to alert the visually impaired. The strip shall be of material that is at least as slip-resistant as the other treads of the stairs.CBC Section 1133B.4.4, Where stairways occur outside a building, the upper approach and all treads shall be marked by a strip of clearly contrasting color at least 2” wide and placed parallel to and not more than 1” from the nose of the step or landing to alert the visually impaired. The strip shall be of a material that is at least as slip-resistant as the other treads of the stair. A painted strip shall be acceptable.Provide handrail details on the drawings showing compliance with CBC Section 1009.10, 1012, and 1133B.4.1. - Stairways shall have handrails on each side. - Every stairway required to be more than 88” in width shall be provided with not less than one intermediate handrail for each 88” of required width. Intermediate handrails shall be spaced approximately equally across with the entire width of the stairway. - Handrails shall be 34 to 38” above the nosing of treads. - Handrails shall extend a minimum of 12” beyond the top nosing, and shall extend a minimum of 12” plus the tread width beyond the bottom nosing. - Ends of handrails shall be returned or shall terminate in newel posts of safety terminals. - Handrails projecting from a wall shall have a space of 1½” between the wall and the handrail. - The handgrip potion of handrails shall not be less than 1¼” nor more than 1½” cross-sectional dimension or the shape shall provide an equivalent gripping surface. The handgrip portion of handrails shall have a smooth surface with no sharp corners. Any wall or other surface adjacent to the handrail shall be free of sharp or abrasive elements. Edges shall have a minimum radius of 1/8”.CBC Section 1012.1, Where required. Handrails for stairways and ramps shall be adequate in strength and attachment in accordance with CBC Section 1607.7. Handrails required for stairways by Section 1009.10 shall comply with CBC Sections 1012.2 through 1012.8. Handrails required for ramps by CBC Section 1010.8 shall comply with CBC Sections 1012.2 through 1012.7.CBC Section 1009.10, Handrails. Stairways shall have handrails on each side and shall comply with Section 1012. Where glass is used to provide the handrail, the handrail shall also comply with Section 2407 of the California Building Code.CBC Section 1133B.4.2.2. Handrails shall extend a minimum of 12” beyond the top nosing and 12”, plus the tread width, beyond the bottom nosing. At the top, the extension shall be parallel with the floor or ground surface. At the bottom, the handrail shall continue to slope for a distance of one tread width from the bottom riser; the remainder of the extension shall be horizontal. See Figures 11B-35 and 11B-37.Guards shall be detailed to show compliance with Sections 1013 and 1607.7. Dimension finish floor to top of guard height. Unenclosed floor and roof openings, open and glazed sides of stairways, landings and ramps, balconies or porches, which are more than 30” above grade or floor below, and roofs used for other than service of the buildings shall be protected by a guardrail.CBC Section 1013.3. Open guards shall have intermediate rails or an ornamental pattern such that a sphere 4” in diameter cannot pass through. - The open space between the intermediate rails or ornamental pattern of guards in commercial and industrial-type occupancy areas, which are not accessible to the public, may be such that a sphere 12” cannot pass through. - The triangular opening formed by the riser, tread, or bottom elements of a guard at the open side of a stairway may be of such size that a sphere 6” indiameter cannot pass through.Any accessible route of travel shall be considered a ramp if its slope is greater than 1’ rise in 20’ of horizontal run (5-percent gradient) and show compliance with CBC Sections 1010 and 1133B.5.1. - Pedestrian ramps used as exits shall show compliance with CBC Sections 1010 and 1133B.5. - Provide complete architectural plan views, sections, details, and notes for pedestrian ramps. - An aisle ramp slope in occupancies of Group A shall comply with Section 1025.11. - CBC Sections 1010.3 and 1133B.5.3.1. The slope measured perpendicular to the direction of travelof a ramp shall not be steeper than one unit vertical in 48 units horizontal (2-percent slope). - CBC Sections 1010.4 and 1133B.5.3. The rise for any ramp run shall be 30” maximum.CBC Section 1133B.5.2, Width. Pedestrian ramps shall have a minimum clear width of 48”, unless required to be wider by some other provision of this code. Pedestrian ramps serving entrances to buildings where the ramp is the only exit discharge path and serves an occupant load of 300 or more shall have a minimum clear width of 60”. CBC Section 1133B.5.4.2, Size of top and bottom landings. Top landings shall be not less than 60” wide and shall have a length of not less than 60” in the direction of ramp run. Landings at the bottom of ramps and at intermediate landings with change in direction shall have a dimension in the direction of ramp run of not less than 72”.CBC Section 1010.6.1, Slope. Landings shall have a slope not steeper than one unit vertical in 48 units horizontal (2-percent slope) in any direction. Changes in level are not permitted.CBC Section 1133B.5.5.1, Handrails for ramps: - Are required on ramps that provide access if  the slope exceeds 1’ rise in 20’ of horizontal run (5-percent gradient), except that at exterior door landings - Are not required on ramps less than 6” rise or 72” in length - Shall be placed on each side of each ramp, shall be continuous the full length of the ramp - Shall be 34 to 38” above the ramp surface to the top of the handrails - Shall extend a minimum of 1’ beyond the top and bottom of the ramp and shall be parallel with the floor or ground surface - The inside handrail on switchback or dogleg ramps shall always be continuous - The ends of handrails shall be either rounded or returned smoothly to floor, wall or post - Handrails projecting from a wall shall have a space of 1½” between the wall and the handrail - Handrails may be located in a recess if the recess is a maximum of 3” deep and extends at least 18” above the top of the rail - The grip portion shall not be less than 1¼” nor more than 1½“ in cross-sectional nominal dimension or the shape shall provide an equivalent gripping surface - All surfaces shall be smooth with no sharp corners - Handrails shall not rotate within their fittings - Any wall or other surface adjacent to the handrail shall be free of sharp or abrasive elements - Edges shall have a minimum radius of 1/8” - Curb ramps do not require handrailsCBC Section 1133B.5.6, Wheel guides. Where the ramp surface is not bounded by a wall, the ramp shall comply with Section 1133B.5.6.1 or 1133B.5.6.2.Exit illumination and exit sign requirements in accordance with CBC Section 1011 shall be shown on the drawings. Be specific as to the type of exit signs to be installed.CBC Sections 1011.6 and 1011.7. Show compliance on the drawings for floor-level exit sign in all interior corridors of Group A occupancies, Group I occupancies, and in all interior rated exit corridors serving guest rooms of hotels in Group R, Division I occupancies and exit path marking requirements in all interior rated exit corridors of un-sprinklered Group A occupancies, and Groups R-1 and R-2 occupancies. Refer to respective code sections for exceptions.CBC Section 1011.1. Provide a directional exit sign at changes in exiting direction.CBC Section 1011, Requires exit signs to be readily visible from any direction of approach. No point shall be more than 100’ from the nearest visible exit sign. Revise the drawings to show compliance.CBC Section 1006, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Show compliance on the drawings.Tactile exit signs shall be required at the following locations: - Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.” - Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp shall be identified by a tactile exit sign with the following words as appropriate:“EXIT STAIR DOWN”“EXIT RAMP DOWN”“EXIT STAIR UP”“EXIT RAMP UP” - Each exit door that leads directly to a grade-level exterior exit by means of an exit enclosure, or an exit passageway, shall be identified by a tactile exit sign with the words “EXIT ROUTE.” - Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.” - Each exit door through a horizontal exit shall be identified by a sign with the words “TO EXIT.”It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards.Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC Section 1134B/Chapter 11B: - An accessible entrance - An accessible route to the altered area - Accessible restrooms - Accessible telephone (if any) - Accessible drinking fountains, and - Parking, signage and alarmsCBC Section 1104B. Provide accessible requirements for Group A occupancies.Assistive listening systemsWheelchair seatingSemi-ambulant persons seatingAccess to performing areasCBC Section 1104B.6 Religious facilities. Religious facilities shall be made accessible to persons with disabilities per this section.CBC Section 1007.1, Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1015.1 or 1019.1 from any accessible space, each accessible portion of the space shall be served by accessible means of egress in at least the same number as required by Section 1015.1 or 1019.1, Chapter 11A or 11B, as applicable.CBC Section 1127B.1. Site development shall be designed to provide access to all entrances and exterior ground-floor exits and access to normal paths of travel; and where necessary, to provide access shall incorporate pedestrian ramps, curb ramps, etc.CBC Section 1127B.1. When more than one building or facility is located on a site, accessible routes of travel shall be provided between buildings and accessible site facilities.At every entrance and at every major junction along or leading to an accessible route of travel, there shall be a sign displaying the international symbol of accessibility. Signs shall indicate the direction to accessible building entrances and facilities and shall comply with the requirements found in CBC Sections 1117B.5 and 1127B.3.CBC Sections 1102B, 1124B.1 and 1127B.1. Provide a continuous walking surface from each exit door to public way.Walks and sidewalks shall have a continuous common surface, not interrupted by steps or abrupt changes in level. Surfaces shall be slip resistant. Refer to CBC Sections1124B and 1133B.7 for additional requirements including maximum slopes (cross slopes and along the path of travel) allowed, grading and level areas.If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 1133B.8.5. Detectable Warning Product Approval. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products and directional surfaces shall be installed in accordance with CBC Section 1133B.8.5.CBC Section 1127B.5. Item 4. Curb ramps shall comply with CBC Section 1127B.5. A level landing 4’ deep shall be provided at the upper end of each curb ramp over its full width to permit safe egress from the ramp surface, or the slope of the fanned or flared sides of the curb ramp shall not exceed 1 unit vertical to 12 units horizontal (8.33% slope).Each lot or parking structure where parking is provided for the public as clients, guest or employees, shall provide accessible parking as required by CBC Section 1129B.CBC Section 1129B.3, Item 2. One in every eight accessible spaces, but not less than one, shall be served by an access aisle 8’-0” (96”) wide minimum and shall be designated van accessible as required by Section 1129B.4. The words NO PARKING shall be painted on the ground within each eight’ loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. See Figure 11B-18B.Provide parking space identification in accordance with CBC Section 1129B.4 including: - Each parking space reserved for persons with physical disabilities shall be identified by a reflecting sign permanently posted immediately adjacent to and visible from each stall or space, consisting of a profile view of a wheelchair with occupant in white on dark blue background. The sign shall not be smaller than 70 square inches in area and, when in path of travel, shall be posted at a minimum height of 80” from the bottom of the sign to the parking space finished grade and shall be un-obscured by a parked vehicle. Signs may also be centered on the wall at the interior end of the parking space. An additional sign or additional language below the symbol of accessibility shall state “Minimum Fine $250.” Spaces complying with CBC Section 1129B.3, Item 2 shall have an additional sign stating “Van Accessible” mounted below the symbol of accessibility. - An additional sign shall also be posted in a conspicuous place at each entrance to off-street parking facilities, or immediately adjacent to and visible from each stall or space. The sign shall not be less than 17” by 22” in size with lettering not less than 1” in height, with clearly and conspicuously states the following:Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards or license plates issued for persons with disabilities may be towed away at owner’s expense. Towed vehicles may be reclaimed by telephoning the Santa Ana Police Department at (714) 245-8665. CVC 22658a. - Provide assurance on the drawings that existing signage language reflects the paragraph above.Plumbing facilities shall be provided in accordance with the California Plumbing Code (CPC) Section 412.0 and CPC Table 4-1.Sanitary facilities serving the area of new work shall be disabled accessible. Revise the drawings to show compliance with CBC Section1115B.CBC Sections 1115B and 1210. Sanitation facility toilet room floors shall have a smooth, hard, non-absorbent surface such as Portland cement, concrete, ceramic tile or other approved material which extends upward onto the walls at least 6”. Walls within 2’ of the front and sides of urinals and water closets shall be similarly finished to a height of 4’.Drinking fountains serving the area of new work shall be accessible. CBC Section 1115B.4.6 and California Plumbing Code Section 406.5.CBC Section 1025.1, Assembly. All occupancies in Group A, including those which contain seats, tables, displays, equipment or other material, shall comply Section 1025.1.CBC Section 1025.9.1. Every occupied portion of any occupancy in Group A that contains seats, tables, displays, and similar fixtures or equipment shall be provided with aisles leading to exits or exit access doorways in accordance with CBC Section 1025.9.1. Aisle access ways for tables and seating shall comply with CBC Section 1014.4.3.Provide on the drawings a complete window schedule showing: - Type and thickness of glazing (type of safety glazing for hazardous locations noted under CBC Section 2406.3Note on drawings: - CBC Section 1205.4, Stairway illumination. Stairways within dwelling units and exterior stairways serving a dwelling unit shall have an illumination level on tread runs of not less than 1’candle (11 lux). Stairs in other occupancies shall be governed by Chapter 10.This building is subject to the State of California Energy Conservation Regulations: - The permit applicant shall be responsible for obtaining an energy plan check from a consultant who is qualified to perform an energy efficiency analysis in accordance with the California Code of Regulations (CCR,) Title 24, Par 6, 2008 California Energy Code. The plan check consultant must sign documentation certifying that a thorough, competent review has been performed on behalf of the Enforcement Agency. - The corrected/final ARCHITECTURAL drawings shall have the required energy efficiency compliance documentation with completed signature blocks filed on the plans. The same information may be copied on the Electrical Plans for the Electrical Plan Checker. - Provide cool roofing as required by 2008 Energy Standards. - The energy plan check consultant must complete the attached “Energy Conservation Plan Check Consultant Qualification Statement.” - Refer to the attached information sheet.The reflected ceiling plan and details must show compliance with CBC Sections 711.3.1, 803, 1613, and 1705 (special inspection) for suspended ceiling systems.Project shall comply with CALGreen building code requirements. See attached checklist and required certification forms.