HomeMy WebLinkAbout170316_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
PROJECT ADDRESS:
PLAN CHECK ENGINEER:TEL:714FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B (Non-Sprinklered)
OCCUPANCY CLASSIFICATION(S):
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
Dental Office
INITIAL REVIEW
EXPIRATION
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
3.
TEL:
FAX:
VALUATION:
EMAIL:
FLOOD ZONE:
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 4corrected sets of plans. All attachment handouts in this report are included in mark up set of drawings.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831 for an appointment.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information. Please remove sheets when applicable.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceNote on the floor plan the use and occupancy load of each room and/or area. Relate each use to a CBC Table item. Note occupant loads which are the greater number based on CBC Section 1004 and Table 1004.1.1 or the actual number of occupants.CBC Section 1015.1, Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists:
- The occupant load of the space exceeds the values in Table 1015.1.
- The common path of egress travel exceeds the limitations of Section 1014.3.
- Where required by Sections 1015.3, 1015.4 and 1015.5.Table 1017.1 Corridor Fire Resistance Rating:
OccupancyOccupant LoadRequired Fire-Resistance Rating (Hours)Served By CorridorWithout sprinklerWith sprinklersystemsystem
B, SGreater than 3010Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms. In fully sprinklered office buildings, corridors may lead through enclosed elevator lobbies if all areas of the building have access to at least one required exit without passing through the elevator lobby. [SFM]CBC Section 715.5.7.2. Where corridor walls are required to be one-hour fire-resistive construction by Section 1017, windows shall be protected by fixed glazing listed and labeled for a fire-protection rating of at least three-fourths hour in accordance with Section 715.5. The total area of windows in any portion of an interior corridor shall not exceed 25 percent of the area of the corridor wall of the room which it is separating from the corridor.CBC Section 715.4. When corridor walls are required to be of one-hour fire-resistive construction by Section 1017, every interior door opening shall be protected by a tight-fitting smoke-and-draft-control assembly having a fire-protection rating of not less than 20 minutes. Viewport in 20-minute rated door limited to 1” in diameter. Said doors shall not have louvers. The lobby shall completely separate the elevators from the corridor by construction conforming to Section 1017.1 and all openings into the lobby wall contiguous with the corridor shall be protected as required by CBC Section 715.4.3.Provide typical section view detail of all new partitions and ceilings showing:
- Referencesheet A8.1, revise detail A and B to show lateral support of partition wall to top of trusses.Method of attaching framing to the building structure. Compliance shall be shown with CBC Section 1607.13
for lateral support of the walls. Do not support top of walls to bottom of trusses. Top of walls/bracing must be braced to support to top of trusses.
- Heights of partition, suspended ceiling, structure above.
- Reference each fire-resistive assembly to a CBC Chapter 7 Table and Item number.
- Fire-blocks and draft-stops in combustible construction in accordance with CBC Section 717. Show
location(s) and provide typical construction details.
- Fire/smoke damper locations, installation requirements and required access doors. Refer to CBC Section 716
and mechanical Code Section 606.The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. CBC Section 1126A.3.2.Provide specifications for doors hardware (i.e., lever type, push-pull panic, etc) to comply with disabled access requirements. CBC Section 1133B.2.5.2.All entrances and exterior ground-floor exit doors to buildings and facilities shall be made accessible to persons with disabilities. Doorways shall have a minimum clear opening of 32” with the door open 90 degrees, measure between the face of the door and the opposite stop. Doorways require dimensioning on the plans to insure compliance with the required landing area/maneuvering clearances at doors in accordance with CBC Section 1133B.2.4.2 and CBC Figures 11B-26A and 11B-26B.CBC Section 1127B.3, All building entrances that are accessible to and usable by persons with disabilities shall be identified with a least one standard sign and with an additional directional signs, as required, to be visible to persons along approaching pedestrian ways.CBC Section 1133B.2.6, Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.CBC Section 1133B.2.5, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds. Applies to all doors and when relocated.Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC Section 1134B/Chapter 11B:
- An accessible entrance
- An accessible route to the altered area
- Accessible restrooms (provide enlarge drawings)
- Accessible telephone (if any)
- Accessible drinking fountains, and
- Parking, signage and alarmsValuation of proposed project is calculated as $114,900.00. A minimum of 20% of valuation of construction is required to be spent towards providing disabled access in the priority order noted in the immediate previous item as noted in CBC Section 1134B. Revise the drawings to show compliance. Show both existing elements and how they will be upgraded to current standards.Show landing at hallway side of toilet room door to have a length in the direction of the door swing of at least 60” and the length. A 60” hall way is required for accessibility compliance. Section 1115B.3.2 of 2010 CBC. CBC Sections 1115B and 1210. Sanitation facility toilet room floors shall have a smooth, hard, non-absorbent surface such as Portland cement, concrete, ceramic tile or other approved material which extends upward onto the walls at least 6”. Walls within 2’ of the front and sides of urinals and water closets shall be similarly finished to a height of 4’.CBC Section 1607.7. Provide complete grab bar details on the drawings showing compliance with CBC Section 1115B.8 including structural strength and positive attachment detail to support a 250 pound point load.CBC Section 1115B.4.3 Item 4. Note on the drawings hot water and drain pipes under lavatory shall be insulated.Ensure sanitary facilities comply with CBC Section 1115B.8.1 and that the bottom of the mirror is no higher than 40” from the floor.Provide dimensioned sit plan to show site, parking and path of travel accessibility. Refer to the attached handout for Exterior Routes of Travel. CBC Sections 1133B.7.1 and 1133B.7.5. Sidewalks accommodating the disabled must be at least forty-eight inches (48”) wide and at least sixty inches (60”) where door swings over walk.Walks and sidewalks shall have a continuous common surface, not interrupted by steps or abrupt changes in level. Surfaces shall be slip resistant. Refer to CBC Sections1124B and 1133B.7 for additional requirements including maximum slopes (cross slopes and along the path of travel) allowed, grading and level areas.Walks and sidewalks shall not have cross slopes exceeding ¼” per foot (2% slope). Slopes along the path of travel shall not exceed 5% unless designed as a pedestrian ramp in accordance with CBC Section1133B.5. For curb ramps refer to CBC Section 1127B.5.If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 1133B.8.5. Clarify the applicability on the site plan.Exit illumination and exit sign requirements in accordance with CBC Section 1011and CBC Section 1006, requires means of egress from all occupied parts of the building to be provided with at least 1’ candle of light at floor level. Show compliance on the drawings. Also refer to drawings for additional red marks on the drawings. Drinking fountains serving the area of new work shall be accessible. CBC Section 1115B.4.6 and California Plumbing Code Section 406.5. High and low drinking fountains are required.CBC Section 1122B.1. Where a single counter are provided, at least 5 percent, but never less than one, of each type of station shall be located at a section of counter that is at least 36” long and no more than 28 to 34” high. Provide elevation of counter and sink in the exam rooms to insure compliance.Reference sheet A2.0, Item # 32, please note all millwork is required to comply with accessibility as noted above.Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use.
Note on drawings:- Provide mechanical ventilation for each area/room in accordance with the 2010 California Mechanical Code.Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use.
Note on drawings:- CBC Section 1205.3, Artificial light. Artificial light shall be provided that is adequate to provide an average illumination of 10’candles (107 lux) over the area of the room at a height of 30”above the floor level.Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636.In lieu of providing structural calculations,Note ICC Research Report Number on the drawings for the suspended ceiling system. (ICC Report Number 1308)CBC Section 1129B.2. Medical care outpatient units and facilities require at least 10 percent of the total number of parking spaces provided be disabled accessible. Units and facilities that specialize in the treatment or services for persons with mobility impairments require at least 20 percent of the total number or parking spaces provided be disabled accessible.Each lot or parking structure where parking is provided for the public as clients, guest or employees, shall provide accessible parking as required by CBC Section 1129B.CBC Section 1129B.1. Accessible parking spaces serving a particular building shall be located on the shortest accessible route of travel from adjacent parking to an accessible entrance. In parking facilities that do not serve a particular building, accessible parking shall be located on the shortest accessible route of travel to an accessible pedestrian entrance of the parking facility.Provide parking data on the site plan showing the total number of parking spaces provided, the number of disabled accessible spaces and the number of van accessible spaces, showing compliance with CBC Section 1129B and CBC Table 11B-6.CBC Section 1129B.3, Item 3. Parking spaces must be located so that the disabled are not compelled to walk or wheel behind parked cars other than their own.CBC Section 1129B.3, Item 4. Surface slopes of accessible parking spaces shall be the minimum possible and shall not exceed 1 unit vertical to 50 units horizontal (2% slope) in any direction.CBC Section 1129B.3, Item 2. One in every eight accessible spaces, but not less than one, shall be served by an access aisle 8’-0” (96”) wide minimum and shall be designated van accessible as required by Section 1129B.4. The words NO PARKING shall be painted on the ground within each eight’ loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. See Figure 11B-18B.Disabled accessible parking spaces should be sized as follows:
- CBC Section 1129B.3, Item 1. Where single spaces are provided, they shall be a 9’ wide parking area with
an outlined 5’ wide (8’ wide for van accessible space) loading and unloading aisle ON THE PASSENGER SIDE
OF THE VEHICLE. The minimum length of each parking space shall be 18’. The loading and unloading access
aisles shall be marked by a border painted blue. Within the blue border, hatched lines a maximum of 36” on
center, shall be painted a color contrasted with the parking surface, preferably blue or white. Parking access
aisles shall be part of an accessible route of travel (complying with Section 1114B.1.2) to the building or facility
entrance. Parked vehicle overhangs shall not reduce the clear width of an accessible route. The words NO
PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be
painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials.
See Figure 11B-18A.
- CBC Section 1129B.3, Item 1. When more than one space is provided, two 9’ wide parking areas may be
outlined on each side of a 5’ wide (8’ wide for van accessible space(s)) loading and unloading aisle. The
minimum length of each parking space shall be 18’. The loading and unloading access aisles shall be marked
by a border painted blue. Within the blue border, hatched lines a maximum of 36” on center, shall be painted
a color contrasted with the parking surface, preferably blue or white. See Figure 11B-18A. Parking access
aisles shall be part of an accessible route of travel (complying with Section 1114B.1.2) to the building or facility
entrance. Parked vehicle overhangs shall not reduce the clear width of an accessible route. The words NO
PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be
painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials.
See Figure 11B-18A.CBC Section 1129B.3, Item 3. In each parking area, a bumper or curb shall be provided and located to prevent encroachment of cars over the required width of walkways (account for front of car overhang).Refer to the attached parking handout for additional plan check comments. Provide parking space identification in accordance with CBC Section 1129B.4 including:
- Each parking space reserved for persons with physical disabilities shall be identified by a reflecting sign
permanently posted immediately adjacent to and visible from each stall or space, consisting of a profile view of
a wheelchair with occupant in white on dark blue background. The sign shall not be smaller than 70 square
inches in area and, when in path of travel, shall be posted at a minimum height of 80” from the bottom of the
sign to the parking space finished grade and shall be un-obscured by a parked vehicle. Signs may also be
centered on the wall at the interior end of the parking space. An additional sign or additional language below
the symbol of accessibility shall state “Minimum Fine $250.” Spaces complying with CBC Section 1129B.3,
Item 2 shall have an additional sign stating “Van Accessible” mounted below the symbol of accessibility.
- An additional sign shall also be posted in a conspicuous place at each entrance to off-street parking facilities,
or immediately adjacent to and visible from each stall or space. The sign shall not be less than 17” by 22” in
size with lettering not less than 1” in height, with clearly and conspicuously states the following:Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards or license plates issued for persons with disabilities may be towed away at owner’s expense. Towed vehicles may be reclaimed by telephoning the Santa Ana Police Department at (714) 245-8665. CVC 22658a.
- Provide assurance on the drawings that existing signage language reflects the paragraph above.The surface of each accessible parking space or stall shall have a surface identification duplicating either of the following schemes:
- By outlining or painting the stall or space in blue and outlining on the ground in the stall or space in white or
suitable contrasting color a profile view depicting a wheelchair with occupant; or
- By outlining a profile view of a wheelchair with occupant in white on blue background. The profile view shall
be located so that it is visible to a traffic enforcement officer when a vehicle is properly parked in the space
and shall be 36” high by 36” wide. See CBC Figures 11B-18A through 11B-18C.