HomeMy WebLinkAbout173877_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: PROJECT ADDRESS: PLAN CHECK ENGINEER:TEL:714FAX:714 647-5897 TYPE OF CONSTRUCTION: OCCUPANCY CLASSIFICATION(S): PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION INITIAL REVIEW EXPIRATION RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. 3. TEL: FAX: VALUATION: EMAIL: FLOOD ZONE: APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance All interior floor finishes shall show compliance with CBC Section 804. Provide on the drawings a complete door schedule, showing: - Hardware complying with exiting and disabled accessibility requirements (CBC Sections 1008.1.8 and 1133B.2.5) - Show compliance with the City of Santa Ana’s Security Ordinance (Contact the Santa Ana Police Department Crime Prevention Section by telephoning 714-647-5840)Provide specifications for doors hardware (i.e., lever type, push-pull panic, etc) to comply with disabled access requirements. CBC Section 1133B.2.5.2.CBC Section 1133B.2.5, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.CBC Section 1133B.2.6, Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.Exit illumination and exit sign requirements in accordance with CBC Section 1011 shall be shown on the drawings. Be specific as to the type of exit signs to be installed. Provide additional exit sign as marked on the drawings.CBC Section 1006, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Show compliance on the drawings.Tactile exit signs shall be required at the following locations: - Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”For the purpose of Section 1011.3, the term “tactile exit signs” shall mean those required signs that comply with Section 1117B.5.1, Item 1.It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. When applicable please remove notes referring to ADA compliance from drawings. This project is reviewed for compliance with State Accessibility Standards.CBC Section 1133B.2.6, Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.Glass and glazing shall be in accordance with CBC Chapter 24. Note on the drawings all windows and doors having glazing. Indicate the type and thickness of each light of glazing on the drawings. Glass shall be firmly supported on all four edges in a frame. Show on the drawings how compliance shall be made with CBC Section 2404. For glass not firmly supported on all four edges, design shall be submitted to the building official for approval. Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use. Note on drawings:- Provide mechanical ventilation for each area/room in accordance with the 2010 California Mechanical Code.Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use. Note on drawings: - CBC Section 1205.3, Artificial light. Artificial light shall be provided that is adequate to provide an average illumination of 10’candles (107 lux) over the area of the room at a height of 30”above the floor level.Tenant improvements in the Main Place Mall shall show compliance with the following special provisions and CBC Section 402: - CBC Section 106.3. Tenant improvements at 2800 North Main, Main Place Mall, shall show compliance with “Code Analysis and Fire Protection and Life Safety Concept” prepared by Code Consultants Incorporated, dated “Revised February 18, 1986, and February 22, 1990 (1991 Mall Expansion).” - Note on drawings: Duct and smoke removal system modification is not allowed and shall be in compliance with the “Code Analysis and Fire Protection and Life Safety Concept.”Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636.In lieu of providing structural calculations, note ICC Research Report Number on the drawings for the suspended ceiling system. (ICC Report Number 1308)CBC Section 402.12, Security grilles and doors. Horizontal sliding or vertical security grilles or doors, which are part of a required means of egress, shall conform to the following:(If applicable) - They must remain secured in the full open position during the period of occupancy by the general public. - Doors or grilles shall not be brought to the closed position when there are more than 10 persons occupying spaces served by a single exit or 50 persons occupying spaces served by more than one exit. - The doors or grilles shall be openable from within without the use of any special knowledge or effort when the space is occupied. - When two or more exits are required, not more than one half of the exits may be equipped with horizontal sliding or vertical rolling grilles or doors. - Note on Drawings: Post a legible sign at security grill/door closing controls stating “Security grill/door shall remain secured in the full open position during the period of occupancy by the general public.”Note On Drawings: (Santa Ana Police Department Requirement)SANTA ANA POLICE DEPARTMENT REQUIREMENTS FOR MAINPLACE OVERHEAD/ROLLING GRILLESECURITYORDINANCE REQUIREMENTSTUBES ARE TO BE “DOUBLE TUBED” (NO MORE THAN ½” APART) AND CONSTRUCTED OF ½” STEEL OR BE STEEL REINFORCED TUBES WITHIN 40” OF ALL LOCKING HARDWARE. PERFORATED SLATS CAN BE USED INSTEAD OF THE AFOREMENTIONED AS LONG AS THEY ARE CONSTRUCTED OF MINIMUM 20 GA STEEL.LOCKING MECHANISM TO BE STEEL SLIDEBOLTS BOTH SIDES OF DOOR. SLIDEBOLTS TO EMBED AMINIMUM OF ½” INTO THE RECEIVING GUIDE.CURTAIN GRILLES ARE NOT TO BE UTILIZED.FIRE DEPARTMENT REQUIRED EMERGENCY RELEASE MUST BE LOCATED NO MORE THAN 40” FROM THE EXTERIOR SIDE OF THE GRILLE.THE LOCKING MECHANISM’S INTERIOR THUMBTURN MUST BE SHIELDED BY AN INTERIOR HOOD TO PREVENT ITS MANIPULATION FROM THE EXTERIOR SIDE OF THE GRILLE.Plans shall indicate how required structural and fire resistive integrity will be maintained where a penetration will be made for electrical, mechanical, plumbing and communication conduits, pipes and similar systems. CBC Section 106.1.1 and CBC Chapter 7. Note on the plans the ICC Research Report number, U.L. number, State Fire Marshal number, or approval number of another agency accepted by the City of Santa Ana.Please correct Type of construction to Type II-B( Non-combustible) Spk.Complete all soffit and furred out wall including suspended details. Provide complete detailing, including number, type, location of fasteners and how attachment is made to the building structureShowpositive attachment to deck above including bracing for lateral support. Structural calculations for design and justification for incomplete details may be required. See mark up set of drawings.Show minimum of 44” between racks in the storage area and note deferred submittal on each sheet where racks are shown.Show 44” clearance between Cash warp and back warp area for accessibility compliance e.CBC Section 1133B.6. Every portion of every building in which are installed seats, tables, merchandise, equipment, or similar materials shall be provided with aisles leading to an exit. Every aisle shall not be less than 36” wide if serving only one side, and not less than 44” wide if serving both sides.Reference sheet A2.0 and a3.0, show fire retardant woos veneer and show compliance with Section 806, 806.1.2 of CBC for additional requirement. Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636.The reflected ceiling plan and details must show compliance with CBC Sections 711.3.1, 803, 1613, and 1705 (special inspection) for suspended ceiling systems.Note ICC Research Report Number on the drawings for the suspended ceiling system. (ICC Report Number 1308) in lieu of providing structural calculations.