HomeMy WebLinkAbout174430_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
PROJECT ADDRESS:
PLAN CHECK ENGINEER:TEL:714FAX:714
647-5897
TYPE OF CONSTRUCTION:
OCCUPANCY CLASSIFICATION(S):
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
Acc project
INITIAL REVIEW
EXPIRATION
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
3.
TEL:
FAX:
VALUATION:
EMAIL:
FLOOD ZONE:
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit corrected sets of plans.Please return marked up set of drawings with corrections.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceNote on the floor plan the use and occupancy load of each room and/or area. Relate each use to a CBC Table item. Note occupant loads which are the greater number based on CBC Section 1004 and Table 1004.1.1 or the actual number of occupants.Separation of exits must comply with CBC Section 1015.2.1. A minimum of 39 feet is required between two exit doors.Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. Revise location of exit doors.Label and note hourly fire rating of ( When applicable, Reference each fire-resistive assembly to a CBC Chapter 7, Table and Item number)
- All corridors, existing or newPlans shall indicate how required structural and fire resistive integrity will be maintained where a penetration will be made for electrical, mechanical, plumbing and communication conduits, pipes and similar systems. CBC Section 106.1.1 and CBC Chapter 7. Note on the plans the ICC Research Report number, U.L. number, State Fire Marshal number, or approval number of another agency accepted by the City of Santa Ana.CBC Section 708.9, Penetrations in a fire partition by ducts and air transfer openings shall comply with Section 716.Provide typical section view detail of all new partitions and ceilings showing:- Fire/smoke damper locations, installation requirements and required access doors. Refer to CBC Section 716
and mechanical Code Section 606.Provide on the drawings interior wall and ceiling finish schedule showing compliance with CBC Section 803, 804 and CBC Table 803.5.CBC Section 1017.4, Air movement in corridors. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts when required to be fire-resistive rated in accordance with Table 1017.1.Provide typical complete section view through one-hour corridor(s) showing compliance with CBC Sections 1017 and 708:
- Fire/smoke damper locations, installation requirements, and required access doors. Refer to CBC Section
716 and Mechanical Code Section 606.Include the following notes with typical one-hour corridor section view:
- Interior openings for other than doors or ducts shall be protected by fixed glazing listed and labeled for a fire
protection rating of at least three-fourths hour in accordance with CBC Section 715.5.
- Penetrations in fire-resistive walls shall comply with CBC Sections 715 and 716.
- Cabinets such as recessed electrical panels, fire hose cabinets, and recess fire extinguisher cabinets
constructed of steel are permitted, provided that the openings in the fire rated corridor are sealed with
approved sealant material to prevent the passages of smoke.
- Other cabinets should be installed or recessed so that there is no reduction in the fire rating of the wall, or
opening which would allow smoke to pass. This would mean that the cabinet must be surrounded with
material which provides the equivalent of one-hour fire resistance.Note on the drawings CBC Section 715 requirements for a pair of doors installed in a one-hourcorridor wall.
- A labeled assembly having a fire-protection rating of not less than 20 minutes.
- Self-closer or automatic-closer actuated by a smoke detector.
- Automatic flush bolts, the door leaf having the automatic flush bolts shall have no doorknob or surface-
mounted hardware. The unlatching of any leaf shall not require more than one operation.
- Full mortise hinges – three minimum.
- Tight-fitting clearances and provided with a gasket so installed as to provide a seal where the door meets the
stop on both sides and across the top. Clearances for a pair of swinging doors shall be as follows: With a
minus 1/16” tolerance – 1/8” along the top, 1/8” along the hinge and latch jambs, 1/8”along the meeting edge
of the doors, and ¼” at the bottom of the doors.
- An overlapping astragal extending the full height of the doors is required along the meeting edges of the
doors. A coordinating device is also required to insure proper closing.”Show 180 degree door closer for doors identified on the floor plan where located in the corridor area. Doors in fully open position shall not reduce the required corridor width by more than 7”. Show compliance with followings on the door schedule:
- Hardware complying with exiting and disabled accessibility requirements (CBC Sections 1008.1.8 and
1133B.2.5)
- Compliance with limitation of viewport size (CBC Section 715.4.3)Reference sheet A-2.0-1, corridor area 105, the width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. CBC Section 1126A.3.2. Please note the active side of doors 110 and 111 for accessibility.See door # 851.1CBC Section 1133B.2.5, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.CBC Section 1006, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Show compliance on the drawings.If emergency warning systems are required, they shall activate a means of warning the hearing impaired. Emergency warning systems, as part of the fire-protective signaling system, shall be designed and installed in accordance with NFPA 72 as amended in CBC Chapter 35. CBC Section 1007.9. Tactile exit signs shall be required at the following locations: Provide cross reference from Reflected ceiling plans where exit signs are shown to sheet A-6.0 where tactile signage is shown.
- Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp shall be
identified by a tactile exit sign with the following words as appropriate:“EXIT STAIR DOWN”“EXIT RAMP DOWN”“EXIT STAIR UP”“EXIT RAMP UP”
- Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual
exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”
- Each exit door through a horizontal exit shall be identified by a sign with the words “TO EXIT.”For the purpose of Section 1011.3, the term “tactile exit signs” shall mean those required signs that comply with Section 1117B.5.1, Item 1.It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. If applicable please remove notes referring to ADA compliance from drawings. This project is reviewed for compliance with State Accessibility Standards.Provide on the drawings a complete window schedule showing: Clarify window legend # 4 on the drawings.
- Window sizes
- Type and thickness of glazing (type of safety glazing for hazardous locations noted under CBC Section 2406.3Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use.
Note on drawings:- Provide mechanical ventilation for each area/room in accordance with the 2010 California Mechanical Code.Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use.
Note on drawings: - CBC Section 1205.3, Artificial light. Artificial light shall be provided that is adequate to provide an average illumination of 10’candles (107 lux) over the area of the room at a height of 30”above the floor level.